Vulcan Hart Electric Steamer ML 136058 User Manual

SERVICE MANUAL  
C24EA SERIES  
ELECTRIC CONVECTION  
STEAMERS  
C24EA6  
ML-136058  
C24EA10 ML-136059  
C24EA6 SHOWN  
- NOTICE -  
This Manual is prepared for the use of trained Vulcan Service  
Technicians and should not be used by those not properly  
qualified. If you have attended a Vulcan Service School for this  
product, you may be qualified to perform all the procedures  
described in this manual.  
This manual is not intended to be all encompassing. If you have  
not attended a Vulcan Service School for this product, you should  
read, in its entirety, the repair procedure you wish to perform to  
determine if you have the necessary tools, instruments and skills  
required to perform the procedure. Procedures for which you do  
not have the necessary tools, instruments and skills should be  
performed by a trained Vulcan Service Technician.  
Reproduction or other use of this Manual, without the express  
written consent of Vulcan, is prohibited.  
For additional information on Vulcan-Hart Company or to locate an authorized  
A product of VULCAN-HART  
LOUISVILLE, KY 40201-0696  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - GENERAL  
GENERAL  
WATER SUPPLY REQUIREMENTS  
INTRODUCTION  
Supply pressure should be  
20-60 psig  
This manual is applicable to the models and ML  
numbers listed on the cover page. Procedures apply  
to all models unless specified otherwise.  
In line strainer for supply line  
(Supplied)  
Total dissolved solids (TDS)*  
Total alkalinity  
less than 60 ppm  
less than 20 ppm  
less than 13 ppm  
less than 4.0 ppm  
6.5 to 8  
Steam Cooking  
Silica  
Convection steamers offer an efficient way to  
produce many foods in either small portions or larger  
batches. Convection steam cooking will steam cook  
fresh foods or will steam defrost and cook frozen  
foods providing the maximum color, flavor and  
nutritional value with the least expenditure of energy  
and labor. The atmospheric steaming compartment  
allows the operator to open and close the door  
anytime during a cooking cycle. The generator  
heating elements will shut off when the door is  
opened then re-start when the door is closed.  
Total Chloride  
PH factor  
Undissolved Solids  
*17.1 ppm = 1 grain of hardness  
less than 5 microns  
Water hardness below 4 grains/gal requires water  
treatment to reduce potential corrosion. Hardness  
above 6 grains/gal should be treated by water  
conditioner, water softener or in-line treatment.  
Water Conditioning  
MODELS COVERED  
It is recommended that a local water treatment  
specialist be consulted before the installation of any  
steam generating equipment.  
Model Designations (based on 2.5 inch pan  
depth)  
Furnishing the steam generator with properly  
conditioned water to reduce scale formation is  
important. Scale formation will reduce steam output,  
cause premature component failure and shorten  
equipment life. Most water supplies contain scale  
producing minerals such as calcium and magnesium.  
As steam is generated, the minerals remain and  
dissolve into the remaining water. As the  
concentration of these minerals increases past a  
certain point, they precipitate from the water and  
coat the inside of the steam generator, heating  
elements, thermostat bulbs and water level probes.  
Because of the high temperature of these surfaces,  
the precipitated minerals bake onto them and  
become very difficult to remove.  
C24EA6 - Six pan (3 pans per compartment)  
C24EA10 - Ten pan (5 pans per compartment)  
SPECIFICATIONS  
All C24EA steamers, with exception of 480V  
steamers, are shipped pre-wired for 208/60/3  
operation. Steamer heating element wiring change is  
required if connecting to 208/60/1, 240/60/1 or  
240/60/3 electrical service.  
ELECTRICAL SPECIFICATIONS  
C24EA6  
C24EA10  
Volts  
Phase  
Total  
Total  
Amps  
Amps  
KW  
16.9  
19.0  
16.9  
19.0  
17.2  
KW  
25.6  
25.6  
25.2  
25.6  
25.6  
This phenomenon causes several problems:  
208  
240  
1
1
3
3
3
81  
79  
48  
51  
21  
121  
110  
72  
1. Reduces the heat transfer efficiency of heating  
elements.  
2. Causes premature failure of heating elements.  
3. Water level probes will give false readings.  
208  
240  
67  
480  
32  
4. Temperature sensing bulbs will sense  
temperature incorrectly.  
1. Voltage values are @ 60HZ.  
NOTES:  
These problems are common to any manufacturer's  
steamer regardless of design, but they can all be  
prevented by furnishing the steam generator with  
properly conditioned water. Vulcan recommends the  
water contain less than 60ppm of total dissolved  
solids (TDS) and have a PH factor between 6.5 to 8.  
2. Heating elements on three phase  
machines are not wired as a balanced  
load. The amps listed are the  
maximum on any leg.  
3. Total KW and amps include heat  
exchanger elements.  
Page 3 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - GENERAL  
Other chemical properties in water supplies can also  
TOOLS  
affect good steam generation and vary from within  
each state and locality.  
Standard set of hand tools.  
The water level probes in the steam generator use  
ions in the water to detect the water level. Do not use  
fully demineralized or de-ionized water since it is  
non-conductive and the water level can not be  
detected.  
VOM with A/C current tester (any quality VOM  
with a sensitivity of at least 20K ohms per volt  
can be used).  
Anti Static Kit, Part No. TL - 84919.  
Special  
NOTE: The use of strainers, or filters will not remove  
minerals from the water.  
Torque Wrench - Capable of measuring  
70 in-lbs.  
Steamers that operate over a long period of time  
without the benefit of properly conditioned water, and  
have developed a heavy scale build up, should be  
cleaned before connecting to a conditioned water  
supply.  
Aluminum Foil Tape - (McMaster-Carr Part No.  
7631A21) or equivalent.  
Single use Constant Tension Band Clamps for  
the specific hose size being used. Refer to parts  
catalog for part number.  
REFERENCE MATERIAL  
Pressure Gauge Assembly  
For replacement parts, refer to Catalog of  
Replacement Parts F35454.  
Low Pressure Gauge - 0 to 5 psi.  
recommended (Grainger Part No. 2C641).  
For operation, cleaning and maintenance  
instructions, refer to Installation and Operation  
Manual F35430.  
Water Hose Coupling - swivel type  
(Grainger Part No. 4KG87).  
Reducer Bushing (Grainger Part No.  
6MN61).  
LUBRICATION  
Pipe thread sealant (as required).  
Component  
Lubrication Type  
All NPT Fittings Pipe Thread Sealant, Loctite 565  
Door Handle  
Lubriplate 630AA  
Sliding Bracket  
F35453 (July 2008)  
Page 4 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - COVERS AND PANELS  
COVERS AND PANELS  
FRONT BASE PANEL  
RIGHT AND LEFT SIDE BASE  
PANELS  
1. Remove screws from the bottom of panel.  
NOTE: Removal of left side panel is identical to the  
procedure for the right side panel.  
1. Remove FRONT BASE PANEL.  
2. Remove screws from the bottom of panel.  
2. Pull bottom of panel out and slide down to clear  
tabletop cover.  
3. Pull bottom of panel out and slide down to clear  
tabletop cover.  
3. Reverse procedure to install.  
4. Reverse procedure to install.  
Page 5 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - COVERS AND PANELS  
REAR BASE PANEL  
COOKING COMPARTMENT  
RIGHT AND LEFT SIDE PANELS  
1. Remove electrical power connection to  
machine.  
NOTE: Removal of left side panel is identical to the  
procedure for the right side panel.  
2. Turn off water supply and disconnect plumbing  
to machine.  
1. Remove screws from the bottom of panel.  
3. Remove screws securing water valves to panel.  
4. Remove screws from the bottom of panel.  
2. Pull bottom of panel out and slide down to clear  
top cover.  
3. Reverse procedure to install.  
5. Pull bottom of panel out and slide down to clear  
tabletop cover.  
6. Reverse procedure to install.  
F35453 (July 2008)  
Page 6 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - DOOR  
DOOR  
REMOVAL  
GASKET  
1. Close door.  
1. Open door.  
2. Remove COOKING COMPARTMENT LEFT  
SIDE PANEL as outlined under COVERS AND  
PANELS.  
2. Remove the shoulder screws and pan pusher  
bracket from gasket plate.  
3. Remove nuts from upper hinge located inside  
front panel.  
3. Remove gasket plate.  
4. Remove gasket from inner door panel.  
4. Open door slightly, and while holding door, pull  
upper hinge away from front panel.  
5. Remove RTV from bottom part of inner door  
panel. Apply RTV 109 to bottom of door where  
shown when assembling gasket to door.  
5. Pull upper hinge out of upper door hinge  
bushing.  
6. Lift door assembly up and off lower door hinge.  
7. Reassemble parts removed in reverse order.  
8. Check door for fit and proper sealing of gasket.  
6. Place a small amount of RTV109 into the inner  
door panel gasket screw holes before  
assembly.  
7. Position the new gasket on gasket plate and  
reverse procedure to install.  
Page 7 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - DOOR  
DOOR HANDLE  
Removal  
1. Open door.  
2. Remove screws from top and bottom of door  
assembly.  
4. Install lock nuts and tighten until no gap exists  
between handle, step spacer and lock nut. Do  
not over-tighten lock nuts.  
5. Close inner door panel so that latch mechanism  
engages striker on front panel.  
6. Install outer door housing onto inner door panel.  
7. Align the top and bottom screw holes of outer  
door housing with inner door panel.  
3. Pull outer door housing away from inner door  
panel starting at the hinge side of door to  
separate the door halves.  
NOTE: The smaller radius of the step spacers fit into  
the slots of the outer door housing and is used to  
provide clearance for handle operation.  
8. Install screws to secure door halves together.  
Apply Loctite 242 to threads of screws before  
assembly.  
9. Check opening and closing operation of door.  
4. Remove lock nuts and stepped spacers from  
threaded studs of door handle.  
Installation  
1. Apply Lubriplate 630AA around slots of outer  
door housing where step spacers contact  
housing.  
2. Install door handle into outer door housing such  
that hinge side of door housing is to the left and  
arrow on handle is pointed upward.  
3. Install step spacer with smaller radius toward  
handle and door housing. Smaller radius is a  
slip fit with outer door housing slot.  
F35453 (July 2008)  
Page 8 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - DOOR  
Assembly  
LATCH ASSEMBLY  
1. Apply Lubriplate 630AA to sides of sliding  
Removal and Disassembly  
bracket.  
1. Separate outer door housing assembly from  
inner door panel as outlined under DOOR  
HANDLE.  
2. Insert spring pin into bottom of sliding bracket.  
A. Place spring over spring pin.  
3. Assemble sliding bracket into stationary  
bracket.  
2. Remove screws securing latch assembly to  
inner door panel and remove latch mechanism.  
4. While holding head of spring pin against bottom  
of sliding bracket, insert spring pin into keeper  
hole in bottom of stationary bracket.  
3. Remove E-clip from latch assembly pins and  
pull pins from latch mechanism.  
A. Secure spring pin in place with retaining  
pin.  
NOTE: Install pins such that heads of pins will be  
facing inward toward hinge side of inner door panel  
when latch assembly is installed.  
5. Install pins to assemble stationary and sliding  
brackets together.  
A. Secure pins into position with E-clip.  
4. Remove retaining pin from spring pin.  
5. Separate sliding bracket from stationary  
bracket.  
Page 9 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - DOOR  
8. Remove outer door housing.  
Do not drive bearing into place. The inner  
Installation  
1. Install latch assembly onto inner door panel with  
spring pin toward bottom of door panel.  
door panel could be damaged. Press bearing into  
position.  
A. Apply Loctite 271 to threads of screws  
before assembly and secure latch  
assembly to inner door panel.  
NOTE: When replacing door hinge bearings, replace  
both hinge bearings.  
9. Position replacement hinge bearing over hinge  
opening in door assembly.  
2. Install outer door housing assembly as outlined  
under DOOR HANDLE.  
A. Press hinge bearing fully into door  
assembly using a C-clamp or equivalent.  
3. Check opening and closing operation of door.  
10. Reassemble parts removed in reverse order.  
4. Check steamer for proper operation and leaks  
around door seal.  
11. Check door for fit and proper door gasket  
sealing.  
HINGE BEARINGS  
DOOR LATCH ADJUSTMENT  
1. Close door.  
2. Remove COOKING COMPARTMENT LEFT  
SIDE PANEL as outlined under COVERS AND  
PANELS.  
Opening a Jammed Door  
Should the steamer door jam and cannot  
be opened, do not force or pry the door as damage  
will occur.  
3. Remove nuts from upper hinge located inside  
front panel.  
1. Lift up on bottom of door at the handle end to  
disengage latch.  
A. If door does not open, remove COOKING  
COMPARTMENT RIGHT SIDE PANEL as  
outlined under COVERS AND PANELS.  
4. Open door slightly, and while holding door, pull  
upper hinge away from front panel.  
5. Pull upper hinge out of upper door hinge  
bearing.  
6. Lift door assembly up and off lower door hinge.  
7. Pry hinge bearing out from door assembly.  
F35453 (July 2008)  
Page 10 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - DOOR  
B. Locate the striker that catches on door  
Adjustment  
latch near steam chamber on front panel.  
1. Reinstall striker with slot pointing upward and  
hand tighten nut only.  
2. Close door to center striker in front panel  
mounting hole.  
3. Open door and check striker slot for horizontal  
alignment. The slot on striker must be kept  
horizontal in order for door latch to catch  
properly and latch.  
4. Once proper slot alignment has been set, hold  
striker close to its base then tighten the striker  
nut. Be careful not to damage striker slot when  
tightening or door may not latch properly.  
NOTE: Do not over-tighten nut. If over-tightened,  
striker may turn and change alignment.  
C. Remove the nut from striker and this  
should release it from the panel.  
NOTE: If door does not open easily, add shims  
between striker and cabinet front. When adding  
shims make certain that door gasket seals properly  
and steamer does not leak. Remove shims as  
necessary until leaking stops.  
D. Open door.  
2. Remove striker.  
3. Remove any burrs on striker that may cause  
latch to stick.  
4. Apply Loctite 271 to threads of striker.  
5. Reinstall striker with slotted side up. Snug  
striker nut. Perform Adjustment, so door will not  
jam.  
Page 11 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - THERMOSTATS AND HIGH LIMITS  
THERMOSTAT AND HIGH LIMITS  
HEAT EXCHANGER HIGH LIMIT  
STEAM GENERATOR HIGH LIMIT  
Removal  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
2. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
A. Turn off water supply.  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
3. Disconnect electrical lead wires from heat  
exchanger high limit.  
3. Remove heating element (1HTR) from steam  
generator as outlined under HEATING  
ELEMENTS AND CONTACTORS.  
4. Loosen hose clamps securing heat exchanger  
high limit to the heat exchanger surface.  
4. Fully loosen capillary tube compression nut and  
slide it away from heating element.  
5. Remove capillary tube mounting nut from  
heating element mounting plate.  
5. Remove heat exchanger high limit.  
6. Disconnect electrical wiring to high limit.  
7. Remove high limit from the rear of low voltage  
control box.  
6. Reassemble parts removed in reverse order.  
7. Check steamer for proper operation.  
F35453 (July 2008)  
Page 12 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - THERMOSTATS AND HIGH LIMITS  
4. Secure high limit to low voltage control box then  
coil excess capillary tube length near the high  
limit.  
5. Check steamer for proper operation and leaks  
around heating element gasket and high limit  
capillary tube nuts.  
CONDENSATE THERMOSTAT  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
RIGHT SIDE SHOWN  
A. Turn off water supply.  
2. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
8. Remove capillary tube from heating element.  
Installation  
3. Disconnect electrical wiring to condensate  
thermostat.  
1. Route capillary bulb through the opening in  
heating element mounting plate. Ensure there  
are no sharp bends in capillary tubing while  
installing.  
4. Remove condensate thermostat from the rear of  
drain box.  
A. Insert capillary bulb into the holding tube  
on heating element.  
2. Apply pipe thread sealant to threads then install  
large capillary tube mounting nut.  
A. Ensure capillary bulb is centered in the  
holding tube. Tighten the capillary tube  
compression nut.  
REAR OF DRAIN BOX SHOWN  
5. Reassemble parts removed in reverse order.  
Apply pipe thread sealant to threads of  
thermostat before assembly.  
6. Check steamer for proper operation and leaks  
around condensate thermostat.  
3. Install heating element with a new gasket.  
Torque mounting nuts to 70 in-lbs and tighten  
using an alternating pattern.  
Page 13 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - TIMERS  
TIMERS  
REMOVAL AND REPLACEMENT  
NOTE: When the timer reaches zero, an external  
buzzer will sound and steam will stop entering the  
cooking compartment. The constant steam setting  
allows for continuous steam operation.  
1. Remove COOKING COMPARTMENT RIGHT  
SIDE PANEL as outlined under COVERS AND  
PANELS.  
2. Note electrical connections then disconnect  
wiring from timer being serviced.  
4. Reverse procedure to install.  
5. Check steamer for proper operation.  
UPPER COMPARTMENT SHOWN  
3. Pull knob from timer shaft.  
A. Remove rotary shaft seal from timer shaft  
then remove timer from front panel.  
B. Inspect rotary shaft seal. Replace if  
damaged, worn or signs of moisture  
migration into control area around timer  
shaft is evident.  
F35453 (July 2008)  
Page 14 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEATING ELEMENTS AND CONTACTORS  
HEATING ELEMENTS AND CONTACTORS  
REMOVAL AND REPLACEMENT  
Heating Elements  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
A. Turn off water supply.  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
3. Remove top screw securing cover to high  
voltage box.  
4. Note electrical connections for the heating  
element being replaced then disconnect heating  
element lead wires from contactors.  
HEATING ELEMENT (1HTR) WITH STEAM  
GENERATOR HIGH LIMIT SHOWN  
A. If replacing heating element (1HTR),  
remove STEAM GENERATOR HIGH  
LIMIT.  
B. Pull heating element out of steam  
generator.  
6. Reassemble parts removed in reverse order.  
Torque mounting nuts to 70 in-lbs and tighten  
using an alternating pattern.  
NOTE: When installing heating element 2HTR or  
3HTR, install pipe plug in the center of heating  
element mounting plate. Apply pipe thread sealant to  
threads before assembly. Use a new gasket  
whenever installing a heating element.  
NOTE: Refer to STEAM GENERATOR HIGH LIMIT  
for proper placement of capillary bulb.  
5. Remove mounting nuts and lock washers  
securing heating element to steam generator.  
7. Check steamer for proper operation and leaks  
around heating element.  
Page 15 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEATING ELEMENTS AND CONTACTORS  
Contactors  
HEATING ELEMENTS  
DIAGNOSTIC CHECK  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
3. Remove top screw securing cover to high  
voltage box.  
4. Note electrical connections for the contactor  
being replaced then disconnect lead wires from  
contactor terminals and coil.  
5. Remove screws securing contactor to high  
voltage control box then remove contactor.  
1. Check voltage across heating element lead  
wires at the limiting and regulating contactor  
terminals and verify against data plate.  
A. If voltage is correct, check current draw  
(step 2).  
B. If voltage is not correct, check the  
following:  
1) Voltage supply to steamer.  
2) Fuses or breaker blown.  
3) Power to contactor coils.  
4) Contactors not pulling in (mechanical  
problem).  
2. Check current draw (amps) through heating  
element lead wires using an amp clamp meter.  
NOTE: Checking current draw is the preferred  
method over a resistance check when an amp clamp  
meter is available.  
6. Reassemble parts removed in reverse order.  
7. Check steamer for proper operation.  
A. If current is correct, then heating element is  
ok. See table for proper values.  
B. If current is not correct, turn power switch  
off and disconnect power to machine.  
1) Install a replacement heating element.  
F35453 (July 2008)  
Page 16 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEATING ELEMENTS AND CONTACTORS  
3. If unable to check current draw, a resistance check may indicate a malfunctioning element.  
A. Turn power switch off and disconnect power to machine.  
B. Disconnect heating element lead wires and check the individual element resistance using a VOM.  
C. If resistance readings are not correct, replace heating element.  
4. Check steamer for proper operation.  
KW PER  
CURRENT PER  
RESISTANCE PER  
ELEMENT (OHMS)  
VOLTAGE  
ELEMENT  
8.0  
ELEMENT  
12.8  
208 1  
240 1  
480 2  
208 1  
240 1  
480 2  
16.2  
16.2  
28.8  
16.2  
16.2  
28.8  
10.5  
8.0  
14.8  
9.6  
8.0  
12.8  
10.5  
8.0  
14.8  
9.6  
1 Dual voltage elements.  
2 480V elements are connected in Wye configuration for 277V across each element.  
NOTE: Values in table are nominal. Tolerance is ±10 %.  
Page 17 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEAT EXCHANGER ELEMENTS AND RELAYS  
HEAT EXCHANGER ELEMENTS AND RELAYS  
REMOVAL AND REPLACEMENT  
Heat Exchanger Elements  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
A. Turn off water supply.  
2. Remove FRONT BASE PANEL and RIGHT  
SIDE BASE PANEL as outlined under COVERS  
AND PANELS.  
3. Note electrical connections for the heat  
exchanger element being replaced then  
disconnect lead wires from heat exchanger  
relay and contactor.  
NOTE: When installing, align the flat on delime valve  
stem and the locking pins on delime valve to the  
motorized control assembly.  
NOTE: The two electrical plugs on the motorized  
control assembly are identical. Note location of  
electrical wiring if disconnecting from motorized  
control assembly. If the electrical plugs not  
connected correctly, the motorized delime valve will  
not function.  
5. Remove heat exchanger element from heat  
exchanger.  
4. Remove motorized control assembly from  
delime valve. Rotate the assembly CCW  
approximately 1/8 turn to disengage from  
delime valve.  
NOTE: To access heat exchanger element (1),  
remove heat exchanger element (2) and the 3/8"  
vent tube on vacuum relief valve (outlet side).  
F35453 (July 2008)  
Page 18 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEAT EXCHANGER ELEMENTS AND RELAYS  
HEAT EXCHANGER ELEMENTS  
DIAGNOSTIC CHECK  
1. Check voltage across heat exchanger element  
lead wires at the limiting and regulating  
contactor terminals and verify against data  
plate.  
A. If voltage is correct, check current draw  
(step 2).  
6. Reassemble parts removed in reverse order.  
Apply pipe thread sealant to threads of heat  
exchanger element before assembly.  
B. If voltage is not correct, check the  
following:  
7. Check steamer for proper operation and leaks  
around heat exchanger element.  
1) Voltage supply to steamer.  
2) Fuses or breaker open.  
Heat Exchanger Relays (K10, K12)  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
3) Heat exchanger relay (K10) (heat  
exchanger element 1) or heat  
exchanger relay (K12) (heat  
exchanger element 2).  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
4) Power to contactor coils.  
3. Remove top screw securing cover to high  
voltage control box.  
5) Contactors not pulling in (mechanical  
problem)  
4. Note electrical connections for the heat  
exchanger relay being replaced then disconnect  
lead wires from relay terminals and coil.  
2. Check current draw (amps) through heat  
exchanger element lead wires using an amp  
clamp meter.  
5. Remove screws securing heat exchanger relay  
to high voltage control box then remove relay.  
NOTE: Checking current draw is the preferred  
method over a resistance check when an amp clamp  
meter is available.  
A. If current is correct, then heat exchanger  
element is ok. See table for proper values.  
B. If current is not correct, turn power switch  
off and disconnect power to machine.  
1) Install replacement heat exchanger  
element.  
6. Reassemble parts removed in reverse order.  
7. Check steamer for proper operation.  
Page 19 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEAT EXCHANGER ELEMENTS AND RELAYS  
3. If unable to check current draw, a resistance check may indicate a malfunctioning element.  
A. Turn power switch off and disconnect power to machine.  
B. Disconnect heat exchanger element lead wires and check resistance using a VOM.  
C. If resistance is not correct, replace heat exchanger element.  
4. Check steamer for proper operation.  
WATTS PER  
ELEMENT  
CURRENT PER  
ELEMENT  
RESISTANCE PER  
ELEMENT (OHMS)  
MODEL  
VOLTAGE  
208 1  
240 1  
480 2  
208 1  
240 1  
480 2  
450  
600  
600  
600  
800  
800  
2.20  
2.50  
2.20  
2.90  
3.30  
2.90  
96.1  
96.0  
128.0  
72.1  
72.0  
95.9  
C24EA6  
C24EA10  
1
2
Dual voltage elements.  
480V Elements are connected in Wye configuration for 277V across each element.  
NOTE: Values in table are nominal. Tolerance is ±10 %.  
F35453 (July 2008)  
Page 20 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - WATER LEVEL CONTROL COMPONENTS  
WATER LEVEL CONTROL COMPONENTS  
WATER LEVEL CONTROL - LOW LEVEL CUT-OFF AND  
DIFFERENTIAL OPERATION  
The steamer is equipped with three water level sensing probes  
(high, low and low level cut-off) and a water level control. The  
water level control performs two functions:  
1. Provide low level cut-off protection to shut off the heat  
source in case the water level drops below the low level  
cut-off (LLCO) probe.  
2. Perform as a differential level control to maintain the water  
level between the low and high water level probes.  
The water level control (WLC) has input voltage (120VAC) across terminals 11 and 12 which powers the primary  
side of the transformer. On one side of the transformer secondary, power is provided to the control by a series  
path through chassis ground (terminal 10). The other side of the transformer secondary (12VAC) is attached to the  
probe that directs power to the other side of WLC relay coils (LLCO and HL) and to the inverse latching relay  
(ILR) electronic circuit on the WLC. As water enters the steam generator, it becomes part of the WLC circuit. When  
the water level in the steam generator reaches a probe, that circuit is completed.  
The inverse latching relay of the WLC is de-energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.) contacts in their  
shelf state.  
When the main power switch is turned on, power is supplied to the WLC which energizes the high level (HL) relay,  
closes HL-1 normally open contacts, and illuminates the HL relay LED. With the HL-1 contacts closed, the slow fill  
solenoid is energized and water begins filling the steam generator.  
When the water level reaches the low level cut-off (LLCO) probe, the LLCO relay is energized and illuminates the  
LLCO LED. With the LLCO-1 contacts closed, the heat source can be energized provided the auxiliary control(s) in  
the heating circuit are satisfied. The LLCO relay will remain energized and its LED will stay lit until the water level  
in the steam generator drops below the LLCO probe.  
When the water level reaches the low level (LL) probe, power to terminal 2 on the WLC is present but no switching  
occurs.  
After the water level reaches the high level (HL) probe, the inverse latching relay of the WLC is energized and  
locked through the low level probe (LL) and ILR-1 contacts. With ILR-2 contacts open, HL relay is de-energized  
and the HL LED goes out. With the HL-1 contacts open, the slow fill solenoid is de-energized, stopping the flow of  
water into the steam generator.  
When the water level drops below the low level (LL) probe, power is removed from the inverse latching relay, the  
HL relay energizes through ILR-2 and HL contacts change state. The slow fill solenoid is energized through HL-1  
to refill the steam generator and the HL LED is lit. The HL relay and LED will toggle on and off during a cooking  
cycle as needed.  
Page 21 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - WATER LEVEL CONTROL COMPONENTS  
WATER LEVEL CONTROL  
WATER LEVEL PROBES  
1. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
2. Note locations of electrical wiring and  
disconnect lead wires to water level probes.  
WATER LEVEL PROBE ELECTRICAL  
CONNECTIONS  
1. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
Water Level  
Control  
Wiring  
Water Level  
Probe  
2. Squeeze tab on plastic standoffs (5) to release  
water level control.  
H
# 5 A - Blue  
H - High Level  
L - Low Level  
L
# 6 B - Yellow  
LLCO - Low Level  
Cut-Off  
LLCO  
# 7 C - Red  
3. Remove probes from probe housing.  
3. Note electrical connections then disconnect  
lead wires from water level control (WLC). Refer  
to the machine schematic when installing water  
level control.  
4. Reassemble parts and lead wires removed in  
reverse order.  
5. Check steamer for proper operation.  
NOTE: Probes should be cleaned thoroughly.  
Remove all accumulated deposits from insulator  
using a soft cloth. Do not use anything abrasive on  
insulators. If probes are dirty, delime steam  
generator after assembling.  
NOTE: Apply pipe thread sealant to threads of probe  
before installation.  
4. Reverse procedure to install.  
NOTE: Perform steam generator DELIMING.  
F35453 (July 2008)  
Page 22 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - WATER LEVEL CONTROL COMPONENTS  
FILTERED AND NON-FILTERED  
DUAL WATER SOLENOID  
VALVES  
NOTE: The filtered and non-filtered water solenoid valves are constructed as dual water valve assemblies. The  
two water valve assemblies used on the steamer have different flow rates and should not be interchanged.  
DUAL WATER VALVE FLOW RATES (GPM)  
Filtered Water  
Fast Fill/Flush Valve  
(3SOL)  
Slow Fill Valve  
(4SOL)  
(Steam Generator Fill)  
4.8  
0.28  
Non-Filtered Water  
Cavity Condensate Valve  
Drain Cooling Valve  
(Condensate/Drain Cooling)  
(2SOL)  
(1SOL)  
3.8  
3.8  
1. Turn off machine to drain steam generator. Allow steamer to complete drain cycle.  
A. Turn off water supply.  
2. Disconnect incoming water to the dual water solenoid valve being replaced (filtered or non-filtered).  
3. Remove RIGHT SIDE BASE PANEL as outlined under COVERS AND PANELS.  
4. Note electrical connections then disconnect wires from solenoid valve.  
5. Note hose connections then disconnect hoses from the outlet of solenoid valve.  
NOTE: Use new band clamps when connecting hoses. See TOOLS.  
DUAL WATER VALVES SHOWN  
Page 23 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - WATER LEVEL CONTROL COMPONENTS  
6. Remove screws (2) securing dual water  
solenoid valve to rear panel.  
7. Reassemble parts removed in reverse order.  
8. Verify water supply is connected to the correct  
dual water solenoid valve (filtered or non  
filtered).  
9. Check steamer for leaks and proper operation.  
5. Push in on the manual drain override knob to  
disengage the gear set.  
MOTORIZED DRAIN VALVE  
A. Rotate knob CW to manually open the  
drain valve. When the slot in knob is  
vertical, the drain valve is open. When the  
slot in knob is horizontal, the drain valve is  
closed.  
1. Turn power switch off.  
A. Allow steamer to complete drain cycle.  
B. If motorized drain valve has malfunctioned  
and the steam generator will not drain  
normally, refer to Drain Steam Generator  
Manually for draining procedure.  
Drain Steam Generator Manually  
1. Turn off water supply to steamer.  
B. Return manual drain override knob to the  
closed position.  
2. Disconnect power to steamer allowing time for  
water in steam generator to cool to 140EF  
before attempting to manually open drain valve.  
Removal  
3. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
1. Turn off water supply to steamer.  
2. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
4. Locate motorized drain valve found at the front  
of steam generator.  
3. Remove motorized control assembly from drain  
valve. Rotate motorized control assembly CCW  
approximately 1/8 turn to disengage assembly  
from drain valve.  
F35453 (July 2008)  
Page 24 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - WATER LEVEL CONTROL COMPONENTS  
8. Reassemble parts removed in reverse order.  
Apply pipe thread sealant to pipe threads before  
installation.  
NOTE: If motorized drain valve is in the open  
position when power is applied to the steamer with  
the power switch on, drain valve will not close and fill  
water will flow through the steam generator into the  
drain.  
9. Verify power switch is in the off position and the  
motorized drain valve is closed before applying  
power to steamer.  
NOTE: When power is applied and power switch is  
off steamer will enter a drain cycle.  
10. Check steamer for proper operation and leaks  
around drain valve.  
NOTE: When installing, align the flat on delime valve  
stem and the locking pins on delime valve to the  
motorized control assembly.  
NOTE: The two electrical plugs on the motorized  
control assembly are identical. If the electrical wiring  
is not connected correctly, the motorized drain valve  
will not function.  
4. Note location of electrical wiring then disconnect  
from motorized control assembly.  
5. Disconnect drain and drain cooling hoses from  
pipe tee located below drain valve.  
NOTE: Use new band clamps when connecting  
hoses. See TOOLS.  
6. Remove drain valve from steam generator.  
7. Remove pipe tee and nipple plumbing assembly  
from drain valve.  
Page 25 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - SWITCHES, SOLENOIDS, RELAY, AND BUZZER  
SWITCHES, SOLENOIDS, RELAYS AND BUZZER  
NOTE: If replacing the switch assembly (gaskets,  
power and delime switches), remove the switch  
POWER AND DELIME SWITCHES  
bezel from the front panel.  
5. Reassemble parts removed in reverse order.  
6. Check steamer for proper operation.  
DOOR SWITCH  
1. Remove COOKING COMPARTMENT RIGHT  
SIDE PANEL as outlined under COVERS AND  
PANELS.  
2. Locate switch on front panel.  
Removal  
1. Remove COOKING COMPARTMENT RIGHT  
SIDE PANEL as outlined under COVERS AND  
PANELS.  
2. Open cooking compartment door.  
3. Note electrical connections then disconnect  
lead wires from switch.  
LOWER COMPARTMENT SHOWN  
3. Disconnect electrical plug from the switch being  
replaced.  
4. Remove switch from bezel on the front panel.  
UPPER COMPARTMENT SHOWN  
4. Remove switch from the door switch mounting  
bracket. Retain hardware.  
F35453 (July 2008)  
Page 26 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - SWITCHES, SOLENOIDS, RELAY, AND BUZZER  
2. Remove FRONT BASE PANEL as outlined  
Installation  
under COVERS AND PANELS.  
1. Verify E-clip is installed on door switch linkage  
in groove nearest front panel.  
3. Locate pressure switch on the left side of the  
switch piping assembly.  
2. Loosely install door switch onto door switch  
mounting bracket.  
A. Close door.  
B. Push switch up against switch linkage as  
far as possible.  
C. Tighten switch mounting hardware.  
3. Check door switch operation.  
4. Disconnect electrical wiring to pressure switch.  
5. Remove pressure switch from piping.  
A. Set meter to measure resistance and place  
meter leads across the COMMON and  
NORM OPEN terminals of switch. With  
door closed, meter should indicate a  
closed circuit.  
6. Reassemble parts removed in reverse order.  
A. Apply pipe thread sealant to threads of  
pressure switch before installation.  
B. Verify Mylar cover is in position covering  
electrical connections.  
B. Open door. Meter should indicate an open  
circuit as door is opened.  
NOTE: Refinement of pressure switch cut-out setting  
is found under Adjustment. Always check and adjust  
pressure switch setting whenever pressure switch is  
being serviced.  
4. Check steamer for proper operation.  
PRESSURE SWITCH (1PAS)  
C. If pressure switch is being replaced, check  
the initial pressure switch setting using the  
reference scale on the pressure switch.  
The top surface of adjustment wheel  
should be aligned slightly below the 5 psi  
mark on pressure switch.  
Removal  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
7. Perform pressure switch Check.  
Page 27 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - SWITCHES, SOLENOIDS, RELAY, AND BUZZER  
NOTE: Operating pressures will vary slightly  
Check  
between machine being serviced and gauge  
used.  
NOTE: Pressure can be checked with the small air  
pocket that exists between the delime port cap and  
water level probe housing in the delime hose. Make  
certain that no leaks exist in the steam generator  
connections or pressure gauge fittings.  
7. While observing pressure gauge, listen for  
contactor to release indicating that pressure  
switch contacts have opened. Correct range for  
pressure switch cut-out is between 3.5 to 3.7  
psi.  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
A. Listen for switch contacts to close  
(contactor will energize).  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
B. Observe pressure gauge for three  
complete cycles to find the average cut-out  
pressure. Record pressure.  
3. Remove cap from delime port and install  
pressure gauge.  
C. If pressure is outside tolerance (3.5 to 3.7  
psi), adjustment is necessary. Refer to  
Adjustment.  
D. If cut-out pressure is within specifications,  
turn power switch off. Allow time for  
steamer to drain.  
8. Remove test gauge and reinstall delime cap.  
Adjustment  
1. Allow steam production to stabilize as outlined  
under Check.  
NOTE: Make small incremental adjustments (1/8  
turn of toothed adjustment wheel) when adjusting  
cut-out pressure.  
2. Referring to cut-out pressure recorded in Check  
procedure, turn adjustment wheel to bring cut-  
out pressure into tolerance.  
4. Close cooking compartment doors.  
5. Mark one tooth of pressure switch adjustment  
wheel to aid in identifying position of wheel.  
Make a second mark on body of pressure  
switch in alignment with mark on adjustment  
wheel.  
A. From looking down on pressure switch:  
1) Turn adjustment wheel CCW to  
decrease cut-out pressure.  
2) Turn adjustment wheel CW to  
increase cut-out pressure.  
6. Turn on machine and allow to pressurize (ready  
light on).  
A. Set one cook timer for approximately 15  
minutes.  
B. Allow steamer to cycle three times for  
steam production to stabilize.  
F35453 (July 2008)  
Page 28 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - SWITCHES, SOLENOIDS, RELAY, AND BUZZER  
B. Check cut-out pressure after making  
VACUUM RELIEF SOLENOID  
adjustment. Repeat Check and Adjustment  
as necessary until cut-out pressure is  
within 3.5 to 3.7 psi.  
PRESSURE SWITCH (2PAS)  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
2. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
3. Locate vacuum relief solenoid connected to the  
water level probe housing and condensate coil.  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
3. Locate pressure switch on the right side of the  
switch piping assembly.  
4. Disconnect electrical wiring to solenoid coil.  
5. Disconnect compression fitting from the outlet  
side of solenoid valve.  
A. Remove solenoid from the pipe nipple and  
tee connected to water level probe  
housing.  
4. Disconnect electrical wiring to pressure switch.  
5. Remove pressure switch from piping.  
6. Reassemble parts removed in reverse order.  
6. Reassemble parts removed in reverse order.  
A. When installing solenoid valve, use two  
wrenches to avoid bending condensate coil  
tubing. Install valve with the outlet side of  
valve connected to the vent tubing that  
leads to the floor (behind drain box). Apply  
pipe thread sealant to pipe threads before  
assembly.  
A. Apply pipe thread sealant to threads of  
pressure switch before installation.  
7. Check steamer for proper operation.  
7. Check steamer for proper operation.  
Page 29 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - SWITCHES, SOLENOIDS, RELAY, AND BUZZER  
COMPARTMENT STEAM  
TIME DELAY RELAY  
SOLENOID  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
1. Turn off machine to drain steam generator.  
Allow steamer to complete drain cycle.  
2. Remove FRONT BASE PANEL as outlined  
under COVERS AND PANELS.  
2. Remove RIGHT SIDE BASE PANEL as  
outlined under COVERS AND PANELS.  
3. Note electrical connections for the time delay  
relay then disconnect lead wires from relay.  
3. Locate compartment steam solenoid connected  
to cooking compartment.  
4. Remove screw securing relay to low voltage  
control box then remove relay.  
LOWER COMPARTMENT SOLENOID SHOWN  
5. Reassemble parts removed in reverse order.  
6. Check steamer for proper operation.  
4. Disconnect electrical wiring to solenoid coil.  
NOTE: When installing, ensure time delay knob is  
rotated fully CCW to the lowest setting (approx. 2  
seconds). Remove jumper wire for proper operation  
at steamer control circuit voltage (120VAC).  
5. Disconnect steam hose from the outlet side of  
solenoid.  
NOTE: Use new band clamps when connecting  
hoses. See TOOLS.  
6. Remove solenoid from steam supply manifold.  
A. Remove pipe fittings from solenoid.  
7. Reassemble parts removed in reverse order.  
Apply pipe thread sealant to pipe threads before  
installation.  
8. Check steamer for proper operation.  
F35453 (July 2008)  
Page 30 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - SWITCHES, SOLENOIDS, RELAY, AND BUZZER  
5. Remove remaining hardware securing door  
BUZZER  
switch mounting bracket to front panel then  
remove door switch mounting bracket, door  
switch and buzzer as an assembly.  
6. Remove buzzer from door switch mounting  
bracket.  
7. Reassemble parts removed in reverse order.  
Perform DOOR LATCH ADJUSTMENT as  
outlined under DOOR.  
1. Remove COOKING COMPARTMENT RIGHT  
SIDE PANEL as outlined under COVERS AND  
PANELS.  
2. Locate buzzer on the door switch mounting  
bracket.  
3. Disconnect electrical wiring from the buzzer and  
door switch.  
4. Remove door striker.  
Page 31 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
CONTROL BOARD  
REMOVAL AND REPLACEMENT  
1. Remove FRONT BASE PANEL as outlined under COVERS AND PANELS.  
2. Disconnect electrical connectors from control board.  
3. Squeeze tab on plastic standoffs (10) to release control board.  
4. Reassemble parts removed in reverse order.  
5. Check steamer for proper operation.  
NOTE: When installing, ensure the board jumpers are set to factory defaults as follows: Delime time delay relay  
jumper set to 60 minutes; drain time delay relay jumper set to 3 minutes; and machine type set to floor model.  
F35453 (July 2008)  
Page 32 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
LAYOUT AND LED LEGEND  
The control board provides a central location for wire harness connections and power transfer through board  
relays (K1-K9, and K11) and time delay relays (delime 1, delime 2 and drain) to the steamer controls. Also,  
provides a condition or component troubleshooting indicator by utilizing eighteen LED’S on the board.  
LED LEGEND  
LED ON = Condition satisfied or component energized. LED OFF = Condition not satisfied or component de-energized.  
LED  
1
Component  
Board powered (120VAC).  
LED  
10  
11  
12  
13  
14  
15  
16  
17  
18  
Component  
Drain relay (K3).  
Drain relay (K5).  
2
Limiting contactor (1CON).  
Regulating contactor 1 (2CON). 1  
Regulating contactor 2 (3CON). 2  
Relay (K1) energized.  
Upper cavity relay (K8). 3  
Lower cavity relay (K9). 3  
3
Vacuum relief solenoid (2SOL). 4  
Delime 1 time delay relay powered.  
Delime relay (K4).  
4
5
6
Delime relay (K2).  
7
Delime relay (K6).  
8
Heat exchanger relay (K10).  
Drain time delay relay (TDR).  
Delime relay (K7).  
9
High limit relay (K11).  
1. Contactor will cycle heating elements to maintain steam generator pressure when one or both compartments are in use;  
or when idling to maintain pressure when compartments are not in use.  
2. Contactor will cycle heating elements as necessary to maintain steam generator pressure when both compartments are  
in use.  
3. K8 and K9 must be energized for heat exchanger relay (K12) to be energized. Heat exchanger element (2) is then  
powered.  
4. Allows venting of steam generator.  
Page 33 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
STEAM GENERATOR OPERATIONAL STATUS  
(LED INDICATORS)  
Use the tables below to determine the operational status of a component or condition by utilizing the LED  
indicators on the board. The sections are divided according to their operational step.  
NOTE: If steamer power switch is off when line voltage applied, the steamer enters a timed drain cycle then shuts  
off.  
Starting Conditions  
Power and water supplied to steamer.  
Power switch (1S) off.  
Delime switch (2S) off (center position).  
Steamer previously operated and drain cycle timed out.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
X
OFF  
1
9
Power to control board (120V)  
Power to drain (TDR)  
Main transformer (1T) powered.  
X
Relay timed out, no output to drain circuit.  
Pressure switch closed (2PAS). Allows  
venting of steam generator during fill.  
12  
13  
X
X
Vacuum relief solenoid (2SOL) energized.  
Power to delime 1 (TDR)  
Relay timed out, no output to delime circuit.  
All other LED's are off.  
Power Switch on  
Power light (3LT) (amber) on.  
HL LED is on. Water level control powered.  
Water fills steam generator at fast fill rate.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
9
X
Same as starting conditions  
X
Power removed from drain (TDR)  
Same as starting conditions  
K4 relay energized. K4-6/2 contacts open.  
K4 relay energized. K4-6/2 contacts open.  
12  
13  
X
X
Power removed from delime 1 (TDR)  
All other LED's are off.  
F35453 (July 2008)  
Page 34 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
Water Level at LLCO Probe  
LLCO LED is on (water level control) (LED is on until water drops below LLCO probe).  
All contactors energized (steam generator begins heating).  
Water fill of the steam generator changes to slow fill rate.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
2
X
Same as Starting Conditions  
Limiting contactor (1CON) energized.  
Water level is satisfied (LLCO probe).  
X
X
Limiting contactor (1CON) will remain  
energized with the water level satisfied.  
Regulating contactor 1 (2CON) energized. Pressure switch (1PAS) closed; Heating  
elements powered.  
3
Regulating contactor 2 (3CON) energized. Pressure switch (1PAS) closed; Heating  
elements powered.  
4
X
X
12  
Same as Starting Conditions  
All other LED's are off.  
Water Level at Low level (L) Probe  
Water level control no changes.  
Control Board no changes.  
Water Level at High Level (H) Probe  
HL LED off (water level control).  
Water fill of steam generator ends (slow fill valve de-energized).  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
X
OFF  
1
2
3
4
Same as Starting Conditions  
X
Same as Water Level at LLCO Probe  
Same as Water Level at LLCO Probe  
Same as Water Level at LLCO Probe  
X
Heating elements remain powered.  
Heating elements remain powered.  
X
Vacuum relief solenoid (2SOL) de-  
energized.  
Pressure switch opens (2PAS). Allows  
steam generator to fully pressurize.  
12  
X
All other LED's are off.  
Page 35 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
Steam Generator at Operating Pressure  
Ready lights (1LT) (green) lit for the upper and lower compartments.  
All contactors de-energized (heating stops).  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
2
X
Same as Starting Conditions  
Same as Water Level at LLCO Probe  
Limiting contactor (1CON) remains energized  
with the water level satisfied (LLCO probe).  
X
Regulating contactor 1 (2CON) de-  
energized.  
Power removed from heating elements.  
Contactor will cycle on/off as necessary to  
maintain pressure in steam generator with  
call for heat from pressure switch (1PAS).  
3
X
X
Regulating contactor 2 (3CON) de-  
energized.  
Power removed from heating elements.  
Contactor will cycle on/off as necessary to  
maintain pressure in steam generator with  
call for heat from pressure switch (1PAS).  
4
5
Pressure switch opens (1PAS). Power to  
cooking compartment controls (except during  
delime cycle).  
X
Relay (K1) energized.  
All other LED's are off.  
Timers Set (Upper and lower Compartments)  
Cook lights (2LT) (red) lit and cooking compartment steam solenoids energize.  
Heat exchanger heating elements energize.  
LED 3 will cycle on/off with Regulating Contactor 1 (2CON) to maintain steam generator pressure.  
LED 4 will cycle on/off with Regulating Contactor 2 (3CON) to maintain steam generator pressure.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
X
OFF  
1
2
Same as Starting Conditions.  
X
Same as Water Level at LLCO Probe.  
Same as Steam generator at Operating  
Pressure.  
5
X
6
7
X
X
Upper cavity relay (K8) energized. 3  
Lower cavity relay (K9) energized. 3  
Upper compartment timer set.  
Lower compartment timer set.  
Cavity drain water is cooled.  
Cavity condensate solenoid (2SOL)  
energized.  
8
X
Heat exchanger element (1) powered when  
one or both compartment timers are set.  
Heat exchanger relay (K10) energized.  
All other LED's are off.  
NOTE: No LED is associated with heat exchanger relay (K12). Relays K8 and K9 must both be energized for heat  
exchanger relay (K12) to be energized. Refer to SCHEMATIC DIAGRAM.  
Water Refill  
HL LED lit (water level control) (cycles with water level control circuit).  
Slow fill solenoid begins until water level reaches H (high level ) probe. HL contacts cycle with water level  
control circuit as water level raises and lowers between L (low level) and H (high level) probes.  
Control Board LED's no changes.  
F35453 (July 2008)  
Page 36 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
Timers Reach Zero (Upper and lower Compartments)  
Buzzer sounds until timer turned to off, constant or additional time is set.  
Cook lights (2LT) (red) turn off and cooking compartment steam solenoids de-energize.  
Heat exchanger heating elements de-energize.  
LED 3 and 4 will cycle as described under Timers Set (Upper and lower Compartments).  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
X
OFF  
1
2
Same as Starting Conditions  
X
Same as Water Level at LLCO Probe.  
Same as Steam generator at Operating  
Pressure.  
5
X
6
7
X
X
Upper cavity relay (K8) de-energized. 3  
Lower cavity relay (K9) energized. 3  
Upper compartment timer timed out.  
Lower compartment timer timed out.  
Cavity drain water cooling stops.  
Cavity condensate solenoid (2SOL) de-  
energized.  
8
X
Power removed from heat exchanger  
element (1).  
Heat exchanger relay (K10) de-energized.  
All other LED's are off.  
Power Switch (1S) off  
Power light (3LT) (amber) and ready light (1LT) (green) off.  
Drain valve energized (steam generator begins draining).  
Condensate thermostat closes (1TAS) and drain cooling solenoid energized (1SOL).  
HL LED off until water drops below L (low level) probe then turns on (water level control).  
LLCO led lit until water level drops below LLCO probe (water level control). Fast fill/flush solenoid energized.  
LED 2 remains lit until water level drops below LLCO probe then turns off. Limiting contactor (1CON) de-  
energized.  
LED 10 remains lit during 3 minute drain cycle then turns off.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
X
Same as Starting Conditions  
Pressure switch closed (1PAS). Power  
removed from cooking compartment  
controls.  
5
X
Relay (K1) de-energized.  
Drain time delay relay (TDR) energized.  
Steamer turned off and 3 minute drain cycle  
started. Drain transformer (2T) powered.  
Drain valve energized and opens.  
9
X
X
Vacuum relief solenoid (2SOL) energized.  
Delime 1 time delay relay powered.  
Pressure switch closed (2PAS). Allows  
venting of steam generator during draining.  
12  
Output from delime 1 (TDR) load terminal is  
not active (delime 1 circuit not powered)  
until input voltage trigger is received during  
the delime cycle.  
13  
X
Drain Cycle Ends  
LED's 1, 9, 12 and 13 remain lit.  
All other LED's are off.  
Steamer is off.  
Page 37 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
DELIMING CYCLE STATUS  
(LED INDICATORS)  
Conditions same as listed under STARTING CONDITIONS.  
Delime time delay relay 2 (TDR) and drain time delay relay (TDR) jumpers on the control board are set at their  
default times as shown on the schematic.  
Delime valve closed.  
Delime solution added to steam generator.  
NOTE: Heat exchanger elements are not energized during delime cycle.  
Delime Switch On  
Delime switch pressed to DELIME position (momentary on - hold 2 sec).  
Power light (3LT) (amber) on.  
Delime light (4LT) (red) on.  
HL Led is on. Water level control powered.  
Water fills steam generator at fast fill rate.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
X
OFF  
1
Same as starting conditions  
Same as starting conditions  
12  
X
Relay timed out, no output to delime circuit. LED  
remains lit as in Turning Steamer Off.  
13  
14  
X
X
Power to delime 1 (TDR)  
Delime Relay (K4) energized.  
Delime 2 (TDR) powered thru K4-6/4 closed contacts  
(N.O.). 120VAC output from delime 2 (TDR) load  
terminal for 60 minutes.  
Power to heating circuit, power light (3LT) and WLC  
thru K4-5/3 closed contacts (N.O.).  
15  
X
Delime Relay (K2) energized.  
K2-6/4 contacts close (powers delime light)  
K2-5/1 contacts open. Power to cooking  
compartment controls is locked out (no power to  
timers or lights).  
Power to delime 1 (TDR) input trigger and delime 1  
(TDR) is energized. 120VAC output from load  
terminal remains on for 3 additional minutes after  
power is removed from input trigger to allow heat  
exchanger to drain (delime valve energized). Total  
time 63 minutes unless canceled (delime 2 TDR  
default time of 60 minutes plus delime 1 TDR of 3  
minutes).  
Delime transformer (3T) powered. Delime valve  
energized and opens.  
Delime valve end switch contacts close.  
17  
X
Delime Relay (K7) energized.  
K7 powered from delime 1 (TDR) output from load  
terminal.  
K7-5/1 N.C contacts open. X1 potential removed  
from power switch (1S).  
K7-5/3 N.O. contacts close. Allows delime 1 (TDR) to  
remain powered to hold K7 energized for a delay on  
drop out (120VAC output from load terminal remains  
on) after K4-6/2 N.C. contacts open.  
All other LED's are off.  
F35453 (July 2008)  
Page 38 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
Water Level at LLCO Probe  
LLCO LED is on (water level control) (LED is on until water drops below LLCO probe).  
All contactors energized (steam generator begins heating).  
Water fill of the steam generator changes to slow fill rate.  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
2
X
Same as Starting Conditions  
Limiting contactor (1CON) energized.  
Water level is satisfied (LLCO probe).  
X
Limiting contactor (1CON) will remain  
energized with the water level satisfied.  
Regulating contactor 1 (2CON) energized. Pressure switch (1PAS) closed; Heating  
elements powered.  
3
4
X
X
Regulating contactor 2 (3CON) energized. Pressure switch (1PAS) closed; Heating  
elements powered.  
12  
13  
14  
15  
17  
X
X
X
X
X
Same as Starting Conditions  
Same as Delime Switch On  
Same as Delime Switch On  
Same as Delime Switch On  
Same as Delime Switch On  
All other LED's are off.  
Water Level at Low level (L) Probe  
Water level control no changes.  
Control Board no changes.  
Water Level at High Level (H) Probe  
HL LED off (water level control).  
Water fill of steam generator ends (slow fill valve de-energized).  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
X
OFF  
1
2
3
4
Same as Starting Conditions  
X
Same as Water Level at LLCO Probe  
Same as Water Level at LLCO Probe  
Same as Water Level at LLCO Probe  
X
Heating elements remain powered.  
Heating elements remain powered.  
X
Vacuum relief solenoid (2SOL) de-  
energized.  
Pressure switch opens (2PAS). Allows  
steam generator to fully pressurize.  
12  
X
13  
14  
15  
17  
X
X
X
X
Same as Delime Switch On  
Same as Delime Switch On  
Same as Delime Switch On  
Same as Delime Switch On  
All other LED's are off.  
Page 39 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
Steam Generator at Operating Pressure  
All contactors de-energized (heating stops).  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
2
X
Same as Starting Conditions  
Same as Water Level at LLCO Probe  
Limiting contactor (1CON) remains energized  
with the water level satisfied (LLCO probe).  
X
Regulating contactor 1 (2CON) de-  
energized.  
Power removed from heating elements.  
Contactor will cycle on/off as necessary to  
maintain pressure in steam generator with  
call for heat from pressure switch (1PAS).  
3
X
X
Regulating contactor 2 (3CON) de-  
energized.  
Power removed from heating elements.  
4
5
Contactor will remain off for the rest of  
delime cycle.  
Relay (K1) energized.  
Pressure switch opens (1PAS). With Delime  
Relay (K2) energized (LED 15 on), K2-5/1  
contacts are open to lock out power to the  
cooking compartment controls.  
X
13  
14  
15  
17  
X
X
X
X
Same as Delime Switch On  
Same as Delime Switch On  
Same as Delime Switch On  
Same as Delime Switch On  
All other LED's are off.  
Steam Generator Maintains Operating Pressure  
Heat cycles as necessary to maintain steam generator pressure during the delime cycle.  
LED 3 will cycle on/off with Regulating Contactor 1 (2CON).  
LED's 1, 2, 5, 13, 14, 15 & 17 remain on.  
Water level maintained by water level control circuit. HL LED (water level control) will cycle on/off.  
Delime Time Reaches Zero  
Delime light (4LT) (red) on until time expires on Delime 2 (TDR).  
Delime cycle heating ends. Limiting contactor (1CON) and regulating contactor 1 (2CON) de-energized.  
Drain cycle starts (drain TDR energized). Drain valve energized to allow steam generator to drain. Delime valve  
energized to allow heat exchanger to drain.  
Condensate thermostat closes (1TAS) and drain cooling solenoid energized (1SOL).  
HL LED off until water drops below L (low level) probe then turns on (water level control).  
LLCO led on until water level drops below LLCO probe (water level control). Fast fill/flush solenoid energized.  
LED 2 remains lit until water level drops below LLCO probe then turns off. Limiting contactor (1CON) de-  
energized.  
LED 10 remains lit during 3 minute drain cycle then turns off.  
F35453 (July 2008)  
Page 40 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - CONTROL BOARD  
STATUS  
LED  
COMPONENT  
DESCRIPTION  
ON  
OFF  
1
3
5
9
X
Same as Starting Conditions  
Regulating contactor 1 (2CON) de-  
energized.  
Power removed from heating elements.  
Pressure switch (1PAS) contacts close.  
X
X
Relay (K1) de-energized.  
Drain (TDR) energized thru K4-6/2  
contacts.  
120VAC output from drain (TDR) load  
terminal. Drain circuit energized.  
X
X
Drain relay (K5) is energized thru delime  
valve end switch closed contacts (N.O.).  
K5-6/4 contacts close and delime light (4LT)  
is lit.  
11  
K5-5/3 latching circuit close contacts allow  
LED 11 to light.  
Vacuum relief solenoid (5SOL)  
energized.  
Pressure switch (2PAS) contacts close.  
Solenoid valve opens to provide air vent and  
allow steam generator to drain.  
12  
X
X
13  
14  
Same as Delime Switch On  
X
X
Delime Relay (K4) de-energized.  
K4-5/3 contacts open. Power light off.  
K4-6/4 contacts open. Power removed from  
delime 2 (TDR).  
15  
Delime Relay (K2) de-energized.  
K2-6/4 contacts open. Delime light off.  
Power removed from delime 1 (TDR) input  
trigger, delime 1 (TDR) remains powered  
thru K7-5/3 N.O. contacts to hold delime  
relay (K7) energized for a delay on dropout  
(120VAC output from load terminal remains  
on). Allows heat exchanger to drain (along  
with steam generator during the 3 minute  
drain cycle time.  
K2-5/1 contacts open. Power to cooking  
compartment controls no longer locked out.  
17  
X
Same as Delime Switch On  
All other LED's are off.  
Delime Cycle Ends  
LED's 1, 9, 12 and 13 remain lit.  
All other LED's are off.  
Steamer is off.  
Page 41 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEAT EXCHANGER  
HEAT EXCHANGER  
REMOVAL AND REPLACEMENT  
1. Turn off machine to drain steam generator. Allow  
steamer to complete drain cycle.  
A.  
Turn off water supply.  
2. Remove FRONT and RIGHT SIDE BASE  
PANELS as outlined under COVERS AND  
PANELS.  
3. Disconnect heat exchanger element wiring as  
outlined under HEAT EXCHANGER ELEMENTS  
AND RELAYS.  
4. Remove control assembly from MOTORIZED  
DELIME VALVE.  
5. Disconnect lead wires from HEAT EXCHANGER  
HIGH LIMIT.  
6. Disconnect steam hoses from heat exchanger  
and separate union.  
8. Remove the following parts from heat exchanger  
for reuse:  
NOTE: Use new band clamps when connecting  
hoses. See TOOLS.  
A.  
B.  
C.  
D.  
Heat exchanger elements.  
Heat exchanger high limit.  
Delime valve, pipe nipple and union.  
Hose barb fittings.  
9. If removed or replacing the heat exchanger,  
install insulation around the heat exchanger.  
Secure into position using high temperature  
aluminum foil tape.  
10.  
Reinstall parts removed in reverse order.  
Apply pipe thread sealant to all pipe  
threads connected to the heat exchanger.  
Do not apply thread sealant to fill union  
fitting.  
11.  
Check steamer for proper operation.  
Inspect all connections to the heat  
exchanger for leaks.  
7. Remove heat exchanger.  
A.  
Lift heat exchanger off rear support bracket  
and move it away from union. Tilt front of  
heat exchanger down and lower it onto the  
bottom frame cover.  
B.  
Rotate heat exchanger and remove it from  
steamer.  
F35453 (July 2008)  
Page 42 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - HEAT EXCHANGER  
MOTORIZED DELIME VALVE  
NOTE: The motorized delime valve (normally closed)  
can be opened or closed manually by pushing in on  
the manual override knob on top of the valve to  
disengage the gear set. Rotate knob CW to open the  
valve (slot in knob vertical); or CCW to close the  
valve (slot in knob is horizontal).  
Removal  
1. Turn off power to machine. Allow steamer to  
complete drain cycle.  
A.  
Turn off water supply to steamer.  
7. Remove pipe nipple and union from delime valve.  
2. Remove RIGHT SIDE BASE PANEL as outlined  
under COVERS AND PANELS.  
8. Reassemble parts removed in reverse order.  
Apply pipe thread sealant to pipe threads before  
installation.  
3. Locate motorized delime valve connected to heat  
exchanger.  
9. Verify motorized delime valve is closed before  
applying power to steamer.  
4. Remove motorized control assembly from delime  
valve. Rotate motorized control assembly CCW  
approximately 1/8 turn to disengage assembly  
from valve.  
NOTE: When power is applied and power switch is  
off steamer will enter a delime cycle.  
10.  
Check steamer for proper operation and  
leaks around delime valve.  
5. Note location of electrical wiring then disconnect  
from motorized control assembly.  
NOTE: The two electrical plugs on the motorized  
control assembly are identical. If the electrical wiring  
is not connected correctly, the motorized delime  
valve will not function.  
NOTE: When installing, align the flat on delime valve  
stem and the locking pins on delime valve to the  
motorized control assembly.  
6. Separate union then remove delime valve from  
heat exchanger.  
Page 43 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - STEAM GENERATOR  
STEAM GENERATOR  
REMOVAL AND REPLACEMENT  
1. Turn off machine to drain steam generator. Allow  
steamer to complete drain cycle.  
A.  
Turn off water supply.  
2. Remove FRONT, LEFT and RIGHT SIDE BASE  
PANELS from generator base and COOKING  
COMPARTMENT RIGHT SIDE PANEL as  
outlined under COVERS AND PANELS.  
3. Remove HEAT EXCHANGER.  
4. Remove VACUUM RELIEF SOLENOID.  
5. Disconnect compressions fittings then remove  
condensate coil tubing.  
6. Remove delime hose from water level probe  
housing.  
8. Disconnect compression fitting then remove the  
fill piping assembly from steam generator fill tube.  
NOTE: Use new band clamps when connecting  
hoses. See TOOLS.  
9. Remove MOTORIZED DRAIN VALVE.  
10.  
Remove HEATING ELEMENTS from  
steam generator.  
7. Disconnect pop-off tubing then remove relief  
valve from steam generator.  
11.  
Remove high voltage control box from  
steamer.  
A.  
B.  
Disconnect electrical supply connections  
from terminal block and ground.  
Disconnect two wiring harness connectors.  
F35453 (July 2008)  
Page 44 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - STEAM GENERATOR  
Remove four bolts securing high voltage  
C.  
control box to frame.  
16.  
Remove the following parts from steam  
generator for reuse:  
A.  
B.  
Drip shield (above elements).  
Remaining pipe nipples, tees and elbows.  
17.  
If removed or replacing steam generator,  
install insulation around the generator.  
Secure into position using high  
temperature aluminum foil tape.  
18.  
19.  
Reinstall parts removed in reverse order.  
Apply pipe thread sealant to all pipe  
threads connected to the steam generator.  
12.  
Remove low voltage control box from  
steamer.  
Check steamer for proper operation.  
Inspect all connections for leaks.  
A.  
Disconnect wiring harness connector  
leading to cooking compartment controls.  
DELIMING  
Refer to the Installation & Operation manual under  
the MAINTENANCE section for specific instructions.  
RIGHT SIDE SHOWN  
B.  
C.  
Disconnect delime valve and drain valve  
harness connectors from control board.  
Remove four bolts securing low voltage  
control box to frame.  
13.  
14.  
Remove WATER LEVEL PROBES.  
Remove ground wire from water level  
probe housing.  
15.  
Remove hardware securing steam  
generator to frame (four places) then  
remove generator.  
Page 45 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
ELECTRICAL OPERATION  
COMPONENT FUNCTION  
STEAM GENERATOR CONTROLS  
Water Level Control (WLC) . . . . . . . . . . . . . . . Controls water level by monitoring conditions of the three water  
level probes H, L and LLCO.  
Probe (H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High water level probe connected to internal latch relay circuit  
on WLC. Water must reach this level before internal latch relay  
is energized.  
Probe (L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low water level probe connected to internal latch relay circuit on  
WLC.  
Probe (LLCO) . . . . . . . . . . . . . . . . . . . . . . . . . . Low Level Cut-Off (LLCO) probe connected to WLC. Controls  
power to heating and fast fill/flush solenoid.  
Contactor, (1CON) Limiting . . . . . . . . . . . . . . Connects one side of heating elements to power. Energized  
whenever WLC (LLCO) coil is energized.  
Contactor 1, (2CON) Regulating . . . . . . . . . . . Connects heating elements to power. On constantly when one  
or both cooking compartment timers are set.  
Contactor 2, (3CON) Regulating . . . . . . . . . . . Connects heating elements to power. On constantly when both  
cooking compartment timers are set.  
Elements, Heating . . . . . . . . . . . . . . . . . . . . . . Located in steam generator. Heats water to produce steam.  
Elements, Heat Exchanger . . . . . . . . . . . . . . . Two cartridge type heating elements located in the heat  
exchanger. Provides additional energy to raise the steam  
temperature delivered to the cooking compartments.  
Fuse, (1FU & 2FU) . . . . . . . . . . . . . . . . . . . . . . . Slow blow 3A fuse. Located on primary side of main transformer  
(1T). Protects control circuitry from over-currents.  
Relay, Time Delay . . . . . . . . . . . . . . . . . . . . . . Controlled by delime switch for delime cycle only. Power switch  
must be off and delime switch pressed and held for more than 2  
seconds to activate time delay relay output and start delime  
cycle. Time delay prevents the delime cycle from immediately  
starting, if the delime switch is accidentally pressed.  
Solenoid (1SOL), Drain Cooling . . . . . . . . . . . Controlled by the condensate thermostat. Mixes cold water with  
hot drain water from steam generator to reduce water  
temperature at the drain.  
Solenoid, (2SOL) Cavity Condensate . . . . . . Controlled by cavity relay K8 on control board. Solenoid is  
energized when timer is on. Mixes cold water with hot  
condensate water from cooking compartment to reduce water  
temperature at drain.  
Solenoid (3SOL), Fast Fill/Flush . . . . . . . . . . Initial steam generator fill. Used during last stage of drain cycle  
to flush drain opening free of debris.  
Solenoid (4SOL), Slow Fill . . . . . . . . . . . . . . . Secondary steam generator fill. Energized as necessary to  
replenish water in steam generator.  
Solenoid (5SOL), Vacuum Relief . . . . . . . . . . . Provides open air line to steam generator during filling and  
draining. When generator is draining, keeps a vacuum from  
developing to prevent cooking compartment flex; and allows  
faster draining. When generator is filling, keeps pressure from  
building up to allow the generator to completely fill.  
Solenoid, Drain Valve (N.C.) . . . . . . . . . . . . . . Controlled by delime relay K7 and delime circuit operation.  
When energized by 24VAC, valve opens to drain the steam  
generator.  
F35453 (July 2008)  
Page 46 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Solenoid, Delime Valve . . . . . . . . . . . . . . . . . . Controlled by delime relay K7 and drain circuit operation. When  
energized by 24VAC, valve opens to allow deliming of the heat  
exchanger and elements during a delime cycle.  
Switch (1PAS), Pressure . . . . . . . . . . . . . . . . . Pressure cut-out protection. Range is between 4.5 to 4.7 psi.  
Removes power from heating circuit if steam generator pressure  
rises above the pressure switch setting.  
Switch (2PAS), Pressure . . . . . . . . . . . . . . . . . Vacuum and fill pressure sensing for the steam generator.  
When generator is draining, provides power to vacuum relief  
solenoid to prevent a vacuum from developing in the steamer.  
When generator is initially heating and pressurizes above 4"  
W.C. the pressure switch opens to remove power from vacuum  
relief solenoid to allow generator to reach operating pressure.  
Thermostat (1TAS), Condensate . . . . . . . . . . . Monitors temperature of water entering the facility drain system.  
Controls the drain cooling solenoid during cooking operation and  
drain cycle (130EF close).  
High-Limit (2TAS), Steam Generator . . . . . . . Protects steam generator heating elements from over-  
temperatures. Capillary tube device (257EF cut-out; 246°F auto  
reset).  
High-Limit (3TAS), Heat Exchanger . . . . . . . . Protects heat exchanger elements from over-temperatures.  
Surface mount device (500EF cut-out; auto reset 450°F).  
Transformer (1T), Main . . . . . . . . . . . . . . . . . . Step down transformer from line voltage to 120VAC control  
circuit voltage.  
Relay, Heat Exchanger (K10) . . . . . . . . . . . . . Connects heat exchanger element (1) to power. On constantly  
whenever one or both cooking compartment timers are set.  
Relay, Heat Exchanger (K12) . . . . . . . . . . . . . Connects heat exchanger element (2) to power. On constantly  
whenever both cooking compartment timers are set.  
Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . Controls steam generator operation, draining and deliming  
functions. Provides a central location for wire harness  
connections and power transfer thru board relays K1 thru K9  
and K11 to the steamer controls. Houses 18 LED's for visual  
operation status and troubleshooting.  
NOTE: The relay’s below are mounted on the control board and are individually replaceable.  
Relay (K1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controlled by pressure switch (1PAS). K1 relay is energized  
when the pressure switch N.O. contacts close.  
Relay (K2), Delime . . . . . . . . . . . . . . . . . . . . . . Controlled by delime circuit. K2 relay is energized when delime  
switch is turned on (momentary).  
Relay (K3), Drain Relay . . . . . . . . . . . . . . . . . . Controlled by drain time delay relay. K3 relay is powered when  
power switch is turned off and drain time delay is energized for  
the drain cycle.  
Relay (K4), Delime . . . . . . . . . . . . . . . . . . . . . . Controlled by delime circuit. K4 relay is energized when delime  
switch is turned on (momentary).  
Relay (K5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controlled by delime circuit. When delime valve is energized,  
the delime valve end switch contacts close and K5 relay is  
energized.  
Relay (K6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controlled by delime switch. K6 relay is energized when delime  
switch is turned to CANCEL to stop a delime cycle.  
Relay (K7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controlled by delime circuit. K7 relay is energized when delime  
time delay relay 1 is energized during delime cycle.  
Relay (K8), Cavity . . . . . . . . . . . . . . . . . . . . . . Controlled by upper cooking compartment timer. When timer is  
set, K8 relay is energized and K8- 5/3 contacts close to provide  
power to cavity condensate solenoid and heat exchanger relay  
(K10). Heat exchanger element (1) energized.  
Page 47 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Relay (K9), Cavity . . . . . . . . . . . . . . . . . . . . . . Controlled by lower cooking compartment timer. When timer is  
set, relay is energized and power is provided thru K8-1/5 N.C.  
contacts to cavity condensate solenoid and heat exchanger  
relay (K11). Heat exchanger element (2) energized.  
Relay (K11), High Limit . . . . . . . . . . . . . . . . . . Controlled by high limit thermostat (2TAS). Relay is energized if  
high limit thermostat opens. When high limit closes, relay  
remains energized thru K11-5/3 contacts until power is removed  
from steamer.  
COOKING COMPARTMENT CONTROLS  
The upper section of the steamer consists of two separate cooking compartments. Each compartment functions  
independently with its own set of controls. Power is supplied to the compartment controls after steam generator  
reaches operating pressure.  
Switch (1S), Power . . . . . . . . . . . . . . . . . . . . . Controls 120VAC to steam generator control circuit in the on  
position. The switch must be in the off position to provide  
120VAC to power delime control circuit.  
Switch (2S), Delime . . . . . . . . . . . . . . . . . . . . . Controls 120VAC to initially energize delime control circuit  
(momentary on). Press and hold switch for approximately 2  
seconds to energize external time delay relay and start delime  
cycle.  
Switch, Door . . . . . . . . . . . . . . . . . . . . . . . . . . Plunger activated switch wired in series with timer. When switch  
is closed and timer is set, regulating contactor(s) are energized  
after ready light is on (pressure switch 1PAS satisfied).  
Timer, Cooking . . . . . . . . . . . . . . . . . . . . . . . . . Used to set cooking time between 0-60 minutes or select  
constant steam. When timer is set, energizes the steam  
solenoid valve to allow steam into the cooking compartment.  
When time expires, energizes buzzer until timer is turned off.  
Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Creates audible signal when timed cook cycle is complete.  
Lamp (1LT), Ready . . . . . . . . . . . . . . . . . . . . . Green (GN) colored lamp. On when door is closed and steam  
generator is pressurized (pressure switch 1PAS operated).  
Lamp (2LT), Cook . . . . . . . . . . . . . . . . . . . . . . Red (RD) colored lamp. On when door is closed and timer is  
set.  
Lamp (3LT), Power . . . . . . . . . . . . . . . . . . . . . Amber (AM) colored lamp. On when power switch is on and  
steam generator high limits are closed.  
Lamp (4LT), Delime . . . . . . . . . . . . . . . . . . . . . Red (RD) colored lamp. On when power switch is off and delime  
switch is operated.  
Solenoid, Compartment Steam . . . . . . . . . . . . When energized by timer, steam solenoid opens to allow steam  
into cooking compartment (normally closed valve).  
F35453 (July 2008)  
Page 48 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
COMPONENT LOCATION  
Steam Generator Base  
Page 49 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
F35453 (July 2008)  
Page 50 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Water Level Control  
Cooking Compartment Controls  
Page 51 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
SMART CYCLE POWER  
MANAGEMENT  
Reduces energy use by not powering all the heating elements in steam generator and heat exchanger when the  
steamer is at operating pressure and one cooking compartment in use. When both cooking compartments are in  
use, all of the heating elements in the steam generator and heat exchanger are powered.  
Heating Elements  
Steam  
Generator Exchanger  
Heat  
Steamer  
Description  
6 pan  
2
3
2
2
One cooking compartment in use, only one steam generator heating  
element and one heat exchanger element are powered thru limiting  
contactor (1CON) and regulating contactor 1 (2CON).  
10 pan  
One cooking compartment in use, two steam generator heating elements  
and one heat exchanger element are powered thru limiting contactor  
(1CON) and regulating contactor 1 (2CON).  
6 or  
10 pan  
As listed  
above  
As listed  
above  
Two cooking compartments in use, all steam generator heating elements  
and both heat exchanger elements are powered thru limiting contactor  
(1CON), regulating contactor 1 (2CON) and regulating contactor 2  
(3CON).  
SEQUENCE OF OPERATION  
Refer to the following diagrams when reviewing sequence of operation: Steam generator schematic, cooking  
compartment schematic and heating element wiring diagrams (for heat exchanger relay contacts K10 and K12).  
The control board delime time delay relay 2 (TDR) and drain time delay relay (TDR) jumpers are set at their default  
times as shown on the schematic.  
NOTE: If power switch is off when service voltage is applied, steamer will enter timed drain cycle.  
Initial Fill and Pre-Heat  
1. Conditions (steamer previously operated and drain cycle timed out).  
A. Steamer connected to correct voltage.  
1) 120VAC potential across X1 and X2 on secondary side of main transformer.  
B. Steamer connected to cold water supply with correct water requirements.  
C. LED 1 lit (power to control board).  
D. Power switch is off (1S).  
1) LED 13 lit. Delime 1 (TDR) on control board timed out. Time delay has no output from load  
terminal.  
2) Delime 2 (TDR) on control board timed out. Time delay has no output from load terminal.  
3) LED 9 lit. Drain (TDR) on control board timed out. Time delay has no output from load terminal.  
E. Delime switch (2S) is off (center position).  
F. Compartment timers off and doors open.  
G. Condensate thermostat thermostat (1TAS) open.  
H. Pressure switch (2PAS) closed.  
1) LED 12 lit. Vacuum relief solenoid (5SOL) energized. Solenoid valve must be open to provide air  
vent to allow steam generator to fill.  
I.  
Steam generator high limit (2TAS) closed.  
J. Heat exchanger high limit (3TAS) closed.  
F35453 (July 2008)  
Page 52 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
K. Pressure switch (1PAS) closed.  
L. Drain valve closed and steam generator is empty.  
M. Delime valve closed and heat exchanger empty.  
1) Delime valve end switch N.O. contacts are open.  
N. Water level control (WLC) and steam generator properly grounded.  
2. Power switch turned on (1S).  
A. LED 13 off. Power removed from delime 1 (TDR) on control board.  
B. LED 9 off. Power removed from drain (TDR) on control board.  
C. X1 potential thru steam generator high limit (2TAS) and heat exchanger high limit (3TAS).  
1) Power light (3LT) (amber) on control panel lit.  
2) X1 potential to L1 of water level control (WLC) thru K3-1/5 drain relay N.C. contacts.  
a. 120VAC across L1 and L2 of WLC.  
b. HL LED lit. High level relay coil (HL) on WLC energized.  
3) Fast fill/flush solenoid (3SOL) energized thru WLC (LLCO) N.C. contacts. Steam generator begins  
fast fill.  
3. Water level reaches Low Level Cut-Off (LLCO) probe.  
A. LLCO LED lit. Low level coil relay (LLCO) on WLC energized.  
B. LLCO N.C. contacts open. Fast fill/flush solenoid (3SOL) de-energized.  
C. WLC (LLCO) N.O. contacts close. X1 potential thru WLC (LLCO) closed contacts and K3-6/2 N.C. drain  
relay contacts.  
1) Slow fill solenoid (4SOL) energized thru pressure switch (1PAS) N.C contacts and WLC (HL) closed  
contacts. Steam generator changes to slow fill.  
2) LED 2 lit. Limiting contactor (1CON) energized.  
3) LED 4 lit. Regulating contactor 2 (3CON) energized thru K1-5/1 N.C. contacts.  
4) Heat exchanger relay (K12) energized.  
a. K12-5/3 N.O. contacts close.  
5) LED 3 lit. Regulating contactor 1 (2CON) energized.  
D. Power to heating elements. Steam generator heating begins.  
4. Water level reaches low level (L) probe.  
A. No action as internal latching relay ILR-1 contacts on WLC are open.  
5. Water level reaches high level (H) probe.  
A. Internal latching relay coil (ILR) on WLC energized and locked thru the low level probe (L) and ILR-1  
closed contacts.  
B. HL LED off. High level (HL) coil de-energized by ILR-2 contacts opening on WLC.  
1) WLC (HL) contacts open. Slow fill solenoid (4SOL) de-energized.  
6. Pressure switch (2PAS) operates (approx. 4" W.C.) and N.C. contacts open.  
A. LED 12 off. Vacuum relief solenoid (5SOL) de-energized. Solenoid valve must close to allow steam  
generator to fully pressurize.  
7. Steam generator up to pressure (approx. 4 psi).  
A. Pressure switch (1PAS) operates and N.C. contacts open.  
1) LED 5 lit. Relay (K1) energized.  
a. K1-5/3 N.O. contacts close. X1 potential thru K1-5/3 contacts and K2-5/1 N.C. contacts to  
cooking compartment controls.  
Page 53 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
a) Ready lights (1LT) (green) are lit for the upper and lower compartments.  
b. K1-5/1 N.C. contacts open.  
a) LED 4 off. Regulating contactor 2 (3CON) de-energized.  
2) LED 3 off. Regulating contactor 1 (2CON) de-energized.  
B. Power removed from heating elements. Steam generator heating stops.  
Timers Set (Upper & Lower Compartments)  
1. Timers set for timed cooking and doors closed.  
A. Upper compartment - Timer contacts 11/13 and 21/23 close.  
1) LED 6 lit. Upper cavity relay (K8) energized. K8-3/5 N.O. contacts close.  
a. LED 8 lit. Cavity condensate solenoid (2SOL) energized. Compartment drain line condensate  
cooled.  
b. Heat exchanger relay (K10) energized. K10-3/5 N.O. contacts close and heat exchanger  
element (1) begins heating.  
c. K8-6/4 N.O. contacts close.  
2) Cook light (2LT) (red) lit. Steam solenoid energized (steam enters cooking compartment).  
3) Timer motor energized.  
B. Lower compartment - Timer contacts 11/13 and 21/23 close.  
1) LED 7 lit. Lower cavity relay (K9) energized. K9-3/5 N.O. contacts close.  
a. LED 8 lit. With upper compartment timer already set, cavity condensate solenoid (2SOL) and  
heat exchanger relay (K10) are energized thru K8-3/5 closed contacts.  
a) K10-3/5 contacts close and heat exchanger element (1) begins heating.  
b. Heat exchanger relay (K12) energized thru K8-6/4 and K9-3/5 N.O. contacts. Heat exchanger  
element (2) begins heating.  
c. If lower compartment timer is the only timer set, cavity condensate solenoid (2SOL) and heat  
exchanger relay (K10) are energized thru K8-1/5 N.C. contacts. Compartment drain line  
condensate is cooled. K10-3/5 contacts close and heat exchanger element (1) is energized.  
2) Cook light (2LT) (red) lit. Steam solenoid energized (steam enters cooking compartment).  
3) Timer motor energized.  
2. Steam generator pressure drops below pressure switch (1PAS) set point.  
A. Regulating contactor 1 (2CON) and regulating contactor 2 (3CON) are energized and power the heating  
elements until pressure switch is satisfied. The pressure switch will cycle the heating circuit as necessary  
to maintain steam generator pressure.  
1) LED 3 will cycle on/off with regulating contactor 1 (2CON). LED 4 will cycle on/off with regulating  
contactor 2 (3CON).  
Water Refill (After Initial Fill)  
1. The water refill cycle will occur whenever the water level is below the low level probe and will not affect the  
operation of either the preheat or cook cycle.  
A. Water level drops below low level (L) probe.  
1) Internal latching relay coil (ILR) on WLC de-energized. ILR-1 contacts return to N.O. condition.  
2) HL LED lit. High level coil (HL) energized by ILR-2 contacts returning to N.C. condition.  
a. WLC (HL) contacts close. Slow fill solenoid (4SOL) energized.  
B. Water level reaches high level (H) probe.  
1) Internal latching relay coil (ILR) on WLC energized and locked thru the low level probe (L) and ILR-  
1 closed contacts.  
F35453 (July 2008)  
Page 54 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
2) HL LED off. High level (HL) coil de-energized by ILR-2 contacts opening.  
a. WLC (HL) contacts open. Slow fill solenoid (4SOL) de-energized.  
2. Timers reach zero (Upper & Lower Compartments).  
A. Upper compartment - Timer contacts 11/13 and 21/23 open.  
1) LED 6 off. Upper cavity relay (K8) de-energized. K8-3/5 contacts return to N.O. condition.  
a. LED 8 off. Cavity condensate solenoid (2SOL) de-energized.  
b. Heat exchanger relay (K10) de-energized. K10- 3/5 contacts return to N.O. condition and heat  
exchanger element (1) de-energized.  
c. K8-6/4 contacts return to N.O. condition.  
2) Cook light (2LT) (red) off. Steam solenoid de-energized.  
3) Timer motor de-energized.  
B. Lower compartment - Timer contacts 11/13 and 21/23 open.  
1) LED 7 off. Lower cavity relay (K9) de-energized. K9-3/5 contacts return to N.O. condition.  
a. LED 8 off. With upper compartment timer expired, cavity condensate solenoid (2SOL) and  
heat exchanger relay (K10) are de-energized. K8-3/5 contacts are open.  
a)  
K10-3/5 contacts open and heat exchanger element (1) de-energized.  
b. Heat exchanger relay (K12) de-energized. K8-6/4 and K9-3/5 contacts return to N.O. condition.  
Heat exchanger element (2) de-energized.  
2) Cook light (2LT) (red) off. Steam solenoid de-energized.  
3) Timer motor de-energized.  
C. Buzzer energized through timer N.O. contacts 11/14 (upper or lower cooking compartment timer).  
1) Buzzer remains energized until: Timer turned to OFF; New time or CONSTANT steam selected; Or  
power switch turned off.  
Turning Steamer Off  
1. Timers off (upper and lower cooking compartments).  
2. Power switch (1S) turned off.  
A. Power light (3LT) (amber) on control panel off.  
3. LED 9 Lit. Drain (TDR) energized thru K4-6/2 N.C. contacts. 120VAC output from load terminal on drain  
(TDR) for 3 minute (default) drain cycle time.  
A. LED 10 Lit. Drain relay (K3) energized.  
1) K3-3/5 N.O. contacts close. HL LED off; LLCO LED lit. WLC remains powered.  
2) K3-1/5 N.C. contacts open. Prevents possible short circuit in the event power switch is turned on.  
3) K3-6/2 N.C. contacts open. Removes power from heating circuit and compartment controls. Ready  
lights (1LT) (green) are off for the upper and lower compartments.  
B. Drain transformer (2T) powered (120/24VAC).  
1) 24VAC drain valve energized. Valve opens and steam generator begins draining.  
4. Drain water temperature above 130°F. Condensate thermostat (1TAS) contacts close (N.O. contacts - close  
on temperature rise).  
A. Drain cooling valve (1SOL) energized until drain water temperature is below 120°F.  
5. Pressure switch (2PAS) N.C. contacts return to closed condition when steam generator pressure drops below  
4" W.C.  
A. LED 12 lit. Vacuum relief solenoid (5SOL) energized. Solenoid valve must be open to provide air vent  
and allow steam generator to drain.  
Page 55 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
6. LED 13 Lit. Power to delime 1 (TDR). Time delay relay has no output from load terminal until input trigger  
voltage is received by delime switch (2S) at the start of a delime cycle.  
7. Water level drops below low level (L) probe.  
A. Internal latching relay coil (ILR) on WLC de-energized. ILR-1 contacts return to N.O. condition.  
B. HL LED lit. High level coil (HL) energized by ILR-2 contacts returning to N.C. condition. WLC (HL)  
contacts close.  
8. Water drops below LLCO probe.  
A. LLCO LED off. Low level relay coil (LLCO) on WLC de-energized.  
1) WLC (LLCO) N.C. contacts return to closed condition.  
a. Fast fill/flush solenoid (3SOL) energized. Water flushes steam generator drain opening to clear  
debris.  
2) WLC (LLCO) N.O. contacts return to open condition.  
B. LED 2 off. Limiting contactor (1CON) de-energized.  
9. Drain (TDR) time elapses.  
A. 120VAC removed from drain TDR load terminal.  
1) LED 10 off. Drain relay (K3) de-energized. K3 contacts return to normal conditions. Power removed  
from WLC.  
2) Power removed from drain transformer (2T). Drain valve de-energized and valve closes.  
10. Drain water temperature below 120°F. Condensate thermostat (1TAS) contacts return to open condition.  
Drain cooling solenoid (1SOL) de-energized.  
11. LED's 1, 9, 12 and 13 lit. Draining complete and steamer is off.  
Deliming Cycle  
NOTE: Allow steam generator to completely drain and the drain valve to close before adding delime solution.  
Refer to Installation & Operation manual for deliming procedure.  
1. Power switch (1S) off and steam generator empty. LED's and components conditions are in the same state as  
outlined at the end of Turning Steamer Off.  
2. Press delime switch (2S) to DELIME position (momentary) and hold until delime (4LT) (red) and power (3LT)  
(amber) lights are lit (approx. 2 seconds). Release delime switch to return to center off position.  
A. LED 15 lit. Delime relay (K2) energized.  
1) K2-6/4 N.O. contacts close. Delime light (4LT) lit.  
2) Power to delime 1 (TDR) input trigger and delime 1 (TDR) is energized. LED 13 remains lit as in  
Turning Steamer off. 120VAC output from load terminal remains on for 3 additional minutes after  
power is removed from input trigger to allow heat exchanger to drain (delime valve energized). Total  
time 63 minutes unless canceled (delime 2 TDR default time of 60 minutes plus delime 1 TDR of 3  
minutes).  
a. Delime transformer (3T) powered. Delime valve energized and opens (approx. 10 second  
delay while valve motor capacitor charges).  
b. Delime valve end switch contacts close.  
c. LED 17 lit. Delime relay (K7) energized.  
a) K7-5/1 N.C contacts open. X1 potential removed from power switch (1S).  
b) K7-5/3 N.O. contacts close. Allows delime 1 (TDR) to remain powered during delime cycle  
after K4-6/2 N.C. contacts open.  
3) K2-5/1 N.C. contacts open. Power to cooking compartment controls is locked out.  
B. LED 14 lit. Delime relay (K4) energized thru K6-5/1 N.C contacts.  
1) Delime 2 (TDR) powered thru K4-6/4 closed contacts (N.O.). 120VAC output from delime 2 (TDR)  
load terminal for 60 minutes.  
F35453 (July 2008)  
Page 56 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
a. Delime relay (K2) remains powered. LED 15 remains lit from pressing delime switch (2S).  
b. Power to heating circuit, power light (3LT) (amber) and WLC thru K4-5/3 closed contacts  
(N.O.).  
a) Steam generator fills and operates as outlined in steps 2A thru 7B under Initial Fill and  
Pre-heat with this exception. After pressure switch (1PAS) is satisfied, LED 4 will remain  
off and regulating contactor 2 (3CON) will remain de-energized. LED 3 and regulating  
contactor 1 (2CON) will cycle on/off as necessary to maintain steam generator pressure.  
3. After 60 minutes, time expires on delime 2 (TDR).  
A. LED 15 and LED 14 off. Delime relays (K2) and (K4) are de-energized and contacts return to normal  
conditions.  
1) Power light (3LT) (amber) off.  
4. With power removed from delime 1 (TDR) input trigger (K2-6/4 contacts open), delime 1 (TDR) remains  
powered thru K7-5/3 N.O. contacts to hold delime relay (K7) energized for a delay on dropout (120VAC  
output from load terminal remains on). Allows heat exchanger to drain (delime valve energized) along with  
steam generator during the 3 minute (default) drain cycle time.  
5. Steamer enters 3 minute drain cycle. Drain cycle operates as outlined in steps 3 thru 8. B. under Turning  
Steamer Off. Continue with sequence for remainder of delime cycle operation  
A. With drain (TDR) energized (LED 9 lit) (120VAC output from load terminal); and delime 1 (TDR)  
powered (LED 13 lit) and receiving voltage to input trigger terminal; and delime valve end switch  
contacts closed.  
1) Drain relay (K5) is energized thru delime valve end switch closed contacts (N.O.).  
a. K5-6/4 contacts close and delime light (4LT) is lit.  
b. LED 11 lit. K5-5/3 latching circuit contacts close.  
6. After 3 minutes, time expires on drain (TDR) and the drain cycle ends. 120VAC removed from drain TDR load  
terminal.  
A. LED 10 off. Drain relay (K3) de-energized. K3 contacts return to normal conditions. Power removed from  
WLC.  
B. Power removed from drain transformer (2T). Drain valve de-energized and valve closes.  
1) LED 11 off. Delime relay (K5) de-energized. Latching circuit contacts K5-5/3 return to open  
condition. Contacts K5-6/4 return to open condition.  
a. Power removed from delime 1 (TDR) input trigger.  
b. Delime light (4LT) off.  
7. Drain water temperature below 120°F. Condensate thermostat (1TAS) contacts return to open condition.  
Drain cooling solenoid (1SOL) de-energized.  
8. Time expires on delime 1 (TDR).  
A. Delime transformer (3T) is de-energized. Delime valve closes and delime valve end switch contacts  
return to open condition.  
B. Delime relay (K7) de-energized. Contacts K7-5/3 and K7-5/1 return to normal condition.  
9. LED's 1, 9, 12 and 13 lit. Draining complete and steamer is off.  
Cancel Deliming  
1. Press delime switch (2S) to CANCEL position (off).  
A. If delime valve has not opened, the steamer is ready to use (approx. 10 second delay while valve motor  
capacitor charges). Allows an unintended delime cycle to be canceled.  
B. If delime valve has opened, the steamer will go thru a drain cycle before it can be turned on.  
1) LED 16 lit. Delime relay (K6) energized. K6-5/1 N.C contacts open.  
a. Delime relay (K4) de-energized.  
a) LED 9 lit. K4-6/2 return to N.C condition and drain (TDR) energized.  
b) Drain circuit powered. Steam generator drains and shuts off as outlined under Turning  
Steamer Off.  
Page 57 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
SCHEMATIC DIAGRAMS  
F35453 (July 2008)  
Page 58 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
- THIS PAGE INTENTIONALLY LEFT BLANK -  
Page 59 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Steam Generator Base  
F35453 (July 2008)  
Page 60 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Page 61 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
WIRING DIAGRAMS  
Heating Element Wiring  
F35453 (July 2008)  
Page 62 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Page 63 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
F35453 (July 2008)  
Page 64 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - ELECTRICAL OPERATION  
Cooking Compartment  
Page 65 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - TROUBLESHOOTING  
TROUBLESHOOTING  
Before performing any of the troubleshooting checks listed below, remove the front generator base panel and  
check the LED’S on the control board for the status of the condition or component in the operating sequence. By  
utilizing the troubleshooting LED’S, the Service Technician can easily determine if a component is functioning  
properly or in need of repair. Refer to CONTROL BOARD.  
SYMPTOM  
POSSIBLE CAUSES  
Drain water not being cooled properly.  
1. Water supply off or supply pressure incorrect.  
2. Condensate thermostat (1TAS) malfunction.  
3. Drain cooling solenoid (1SOL) malfunction (clogged).  
4. Cavity condensate solenoid (2SOL) not receiving power.  
A. Timer malfunction (upper or lower compartment).  
B. Control board upper cavity relay (K8); or lower cavity  
relay (K9) malfunction.  
5. Cavity condensate solenoid (2SOL) malfunction (clogged).  
1. Lime scale build-up on water level probes (shorted to ground).  
2. Contactor malfunction.  
Heat coming on without water in steam  
generator.  
3. WLC- LLCO contacts stuck closed. Water level control (WLC)  
malfunction.  
Excessive time for steam generator to reach 1. Supply voltage incorrect.  
operating pressure (over 25 min).  
2. Heating elements not wired correctly.  
3. Contactor(s) malfunction.  
4. Steam generator not filled. See Symptom - Steam generator  
not filling or is slow to fill.  
5. Pressure switch (2PAS) malfunction (not opening).  
6. Vacuum relief solenoid (5SOL) energized or stuck open  
(steam generator continues to vent and release pressure).  
7. Cooking compartment steam solenoid stuck open (steam  
inside compartment with timer off).  
Steamer leaks water.  
1. Loose connections in water, steam or drain lines.  
Water running out of drain during fill.  
1. Drain valve (motorized) stuck open.  
2. Control board malfunction (drain TDR).  
3. Condensate thermostat (1TAS) malfunction.  
Steam generator water level too high.  
1. Slow fill solenoid (4SOL) or fast fill/flush solenoid (3SOL) does  
not shut off.  
2. Lime scale build-up on high level probe (open circuit).  
3. Water level control malfunction.  
F35453 (July 2008)  
Page 66 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Steamer will not heat.  
1. Check incoming voltage.  
2. Steam generator not filled. See Symptom - Steam generator  
not filling or is slow to fill.  
3. Power switch (1S) malfunction.  
4. Steam generator high limit (2TAS) open.  
5. Heat exchanger high limit (3TAS) open.  
6. WLC-LLCO normally open contacts not closed. Water level  
control (WLC) malfunction.  
7. Control board drain relay (K3) malfunction.  
8. Limiting (1CON) contactor malfunction.  
9. Pressure switch (1PAS) not adjusted properly or malfunction.  
10. Regulating contactor 1 (2CON) malfunction.  
11. Relay (K1) malfunction.  
12. Regulating contactor 2 (3CON) malfunction.  
13. Heating element(s) inoperative.  
14. Water too pure for probes to properly conduct electricity.  
Steam generator not filling or is slow to fill.  
1. Water supply off, supply pressure incorrect or filtering system  
clogged.  
2. Water level control not receiving power. Control board drain  
relay (K3) malfunction.  
3. WLC-LLCO normally closed contacts are open (no power to  
fast fill/flush solenoid 3SOL). Water level control (WLC)  
malfunction.  
4. Fast fill/flush solenoid (3SOL) clogged or malfunction.  
5. WLC-HL normally open contacts are not closing (no power to  
slow fill solenoid 4SOL). Water level control (WLC)  
malfunction.  
6. Slow fill solenoid (4SOL) clogged or malfunction.  
7. Drain valve (motorized) stuck open.  
8. Pressure switch (2PAS) malfunction (not closed).  
9. Vacuum relief solenoid (5SOL) opening is clogged (not  
allowing steam generator to vent).  
10. Lime scale build-up on water level probes (shorted to ground).  
11. Water level control (WLC) malfunction.  
1. Worn or damaged door gasket.  
2. Drain line obstructed or not to an open gap drain.  
1. Steamer not level.  
Steam leaks around door.  
Water leaks around door.  
2. Drain line obstructed or not to an open gap drain.  
3. Worn or gasket Door gasket damaged.  
1. Compartment steam solenoid stuck open.  
2. Timer malfunction.  
Steam generated inside cooking  
compartment when timer is off.  
Timer motor does not run  
1. Door open or door switch malfunction.  
2. Timer malfunction.  
Door not closing properly.  
1. Door latch assembly.  
2. Striker adjustment.  
Door won’t open.  
1. Latch won’t release. See DOOR LATCH ADJUSTMENT.  
1. Timer malfunction.  
Buzzer not operating.  
2. Buzzer malfunction.  
Page 67 of 68  
F35453 (July 2008)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL C24EA - TROUBLESHOOTING  
- N O T E S -  
F35453 (July 2008)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Toshiba Barcode Reader B 411 SERIES User Manual
Toshiba Network Card PROSEC T3H User Manual
TP Link Switch TL SG105E TL SG108E User Manual
TRENDnet Network Hardware TEW690AP User Manual
Uniden Cordless Telephone XCA550 55 User Manual
Vidikron VCR VP 103VHD User Manual
Vivitar Binoculars VIV AV 750 User Manual
VTech Laptop 80 067848 User Manual
Vulcan Hart Charcoal Grill MG24CB User Manual
Wayne Dalton Universal Remote WDHC 20 User Manual