Owner’s Manual
®
APS PowerVerter
Alternative Power Sources (230V, 50 Hz)
• Voltage- and Frequency-Controlled • Peak Power • High Efficiency
Introduction
2
4
5
Important Safety Instructions
Configuration & Connection
Features
11
14
14
15
16
18
Maintenance and Service
Limited Warranty
Troubleshooting
Specifications
Español
1111 W. 35th Street Chicago, IL 60609 USA
PowerVerter ® is a registered trademark of Tripp Lite. All rights reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction continued
3-Stage Battery Charger
15
14
13
12
Your APS recharges your battery faster than
conventional chargers because its three-stage
charger profile (Bulk, Absorption and Float) are
optimized, regardless of the type of battery you use
(Wet or Gel).* In addition, the advanced charging
system protects against over-charge and over-dis-
charge to ensure a longer service life from your bat-
tery.
Stage 2
Absorption
Stage 3
Float
*
The Absorption and Float levels vary according to battery
type, which can be set to either “Wet” or “Gel”cell.
Voltage Regulation
(Select models only)
“VR” APS models regulate incoming AC power by
automatically “boosting” or “cutting” the voltage to
keep your equipment running through brownouts
and overvoltages without draining battery power.
Load Sharing
(Select models only)
Select APS models can be set to limit their own
charging functions so they can charge their
batteries at the quickest rate possible without over-
loading their power input circuits.
Frequency-Controlled
Inverter Output
All APS models feature Frequency-Controlled
Inverter Output which allows devices dependent on
AC line frequency (such as computers, VCRs, CD
players, tape recorders, clocks and turntables) to
operate properly.
Circuit Board Protection
A silicone conformal coating safeguards the
circuit boards against moisture.
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during
the installation, operation and storage of all Tripp Lite APS Systems.
APS Location Warnings
• Install your APS indoors, away from excess moisture or heat, dust or direct sunlight.
• Your APS is NOT waterproof. Contact with water can cause the unit to short circuit and
could cause personal injury due to electric shock. Never immerse your APS. Mount it in
the driest location available.
• Leave adequate space around all sides of the APS for proper ventilation. The heavier the
load of connected equipment, the more heat will be generated by the APS.
• Do not install the APS near magnetic storage media, as this may result in data corruption.
Battery Connection Warnings
• Your APS will not operate with or without utility power until batteries are connected.
• Multiple battery systems must be made up of batteries of the same voltage, age, amp hour
capacity and type.
• Keep battery location well ventilated. Explosive hydrogen gas can accumulate near
batteries if they are not kept well ventilated.
• Sparks may result during final battery connection. Always observe proper polarity as
batteries are connected.
• Do not allow objects to contact the two DC input terminals. Do not short or bridge these
terminals together. Serious injury to property or person could result.
Equipment Connection Warnings
• Do not use Tripp Lite APS Systems in life support applications where a malfunction
or failure of a Tripp Lite APS System could cause failure or significantly alter the
performance of a life support device.
• Do not connect a surge suppressor, line conditioner or UPS to the output of the APS.
• Corded models: Do not modify the APS’s plug in a way that eliminates its ground
connection. Do not use power adaptors that will eliminate the plug’s ground connection.
Connect your APS only to a properly grounded AC power outlet. Do not plug your APS
into itself; this will damage the APS and void your warranty.
Operation Warnings
• Your APS does not require routine maintenance. Do not open your APS for any reason.
There are no user-serviceable parts inside.
• Potentially lethal voltages exist within this unit as long as the battery supply and/or AC
input are connected. During any service work, the battery supply and AC input connection
(if any) should therefore be disconnected.
• Do not connect or disconnect batteries while the APS is operating from the battery supply.
Dangerous arcing may result.
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Configuration
Configuration Dip Switch Settings
DIP SWITCH GROUP A
(All models)
BATTERY TYPE / VOLTAGE POINT
Using a small tool, set the 4 “Battery Type / Voltage Point” Configuration DIP Switches, Group
A (located on the front panel of your APS; see Diagram 1, p. 36) to select battery type and set
the voltage range outside of which your APS will switch to battery power.
• Select Battery Type (DIP Switch #1, Group A)
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be
degraded or damaged over an extended period of time. See “Battery Selection,” page 8 for more information.
Gel Cell
4 3 2 1
Battery Type
Switch Position
Up
Gel Cell (Sealed) Battery
Wet Cell (Vented) Battery
Wet Cell*
Down*
264V
4 3 2 1
• Select High AC Voltage Switch To
Battery Point (DIP Switch #2, Group A)
259V*
Voltage
264V
Switch Position
Up
259V
Down*
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
• Select Low AC Voltage Switch To
Battery Point (DIP Switches #4, Group A & #3, Group A)
201V
182V
163V
144V*
Voltage
201V
182V
163V
144V
Switch Postion
#4 Up & #3 Up
#4 Up & #3 Down
#4 Down & #3 Up
#4 Down & #3 Down*
Most loads will perform adequately when your APS’s High AC
Voltage Point DIP Switch #2 is set to 259V and its Low AC Voltage
Point DIP Switches #3 and #4 are set to 182V. However, if your APS
frequently switches to battery power due to momentary high/low line
voltage swings that would have little effect on equipment operation,
you may wish to adjust these settings. By raising the High AC
Voltage Switch to Battery point and/or lowering the Low AC Voltage
Switch to Battery Point, you may reduce the number of times your
APS switches to battery due to voltage swings.
* Factory default settings
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Configuration continued
DIP SWITCH GROUP B
(Available on Select Models)
LOAD SHARING/EQUALIZE BATTERY CHARGE
Using a small tool, set the “Load Sharing” Configuration DIP Switches, #1 and #2 of Group B
(located on the front panel of your APS; see Diagram 1, p. 36). DIP Switch #3, Group B should
be kept in the “UP” position when you are not equalizing your batteries' charges. DIP Switch #4,
Group B has no function.
• Load Sharing (DIP Switches #1, Group B & #2, Group B)
Your APS features a high-output battery charger that can draw a significant amount of power
from your line power source when charging at its maximum rate. If an APS is supplying its
full AC power rating to its connected load at the same time as it is charging, it could trip its
line source circuit breaker. Tripping this breaker will cut off AC power to your load and stop
battery charging.
To reduce the chance of tripping this breaker, select APS models may be set to automatically
limit their charger output to keep the sum of their AC load and charger power within their circuit
breakers’ rating.
This charger limiting function has four settings, allowing you to choose less charger limiting
for APS configurations with higher rated breakers. The figures below show how to set your
DIP Switches to select how heavy a load can be placed on your APS before charger limiting begins.
Battery Charger Limiting Points
MOST LIMITING (#1 & #2 Up*): Charger limiting takes effect the
moment any load is applied; charger output falls gradually from full
output at no load to no output at full load.
4
3
2
1
LESS LIMITING (#1 Down & #2 Up): Charger limiting begins
when the APS’s load reaches 33% of the APS’s load rating. Charger
output falls gradually from full output at 33% of the APS’s load rating
to about 40% of full output at full load
4
3
2
1
LEAST LIMITING (#1 Up & #2 Down): Charger limiting begins at
when the APS’s load reaches 66% of the APS’s load rating. Charger
output falls gradually from full output at 66% of the APS’s load rating
to about 40% of full output at full load.
4
4
3
3
2
2
1
1
NO LIMITING (#1 & #2 Down): No charger limiting occurs at any
load size.
* Factory default setting.
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Configuration continued
• Equalize Battery Charge (DIP Switch #3, Group B)
This DIP Switch is momentarily engaged to begin the process of equalizing the internal resistance
of your battery’s cells. This can extend the useful life of certain types of batteries; consult with
your battery's manufacturer to determine if your batteries could benefit from this process. The
charge equalization process is automatic and once started can only be stopped by removing the
input power.
Setting Procedure
• Move to “Equalize” (DOWN) position for three seconds.
• Move to “Reset” (UP) position and leave it there.
CAUTION: Battery charge equalization should only be performed in
strict accordance with the battery manufacturer’s instructions and
specifications.
CAUTION: Do not leave DIP switch #3 in the down position after
beginning process.
Battery Charge
Reset
Switch Position
Up*
Reset*
4 3 2 1
Equalize
Down
Equalize
* Factory default setting.
• Limit Battery Charger (DIP Switch #4, Group B) (APSINT1524 only)
To prevent overheating smaller batteries, the charger on this UPS system is initially set to deliver only
a fraction of its maximum power rating to connected batteries. If you are using this system with a
larger (over 100 amp-hours) battery or battery system, you may switch your battery charger to full
power without overheating your batteries.
Battery Charger
Switch Position
Up*
Partial (1/3) Charging Power
Full Charging Power
Partial*
Full
4 3 2 1
Down
* Factory default setting.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Battery Selection
Selecting Battery Type
Select a battery or system of batteries that will provide your APS with proper DC voltage and an
adequate amp hour capacity.* Select ‘Deep-Cycle’ batteries to enjoy optimum performance from
your APS. Batteries of either Wet-Cell (vented) or Gel-Cell/Absorbed Glass Mat (sealed)
construction are ideal. 6 Volt “golf-cart”, Marine Deep-Cycle or 8D Deep-Cycle batteries are also
acceptable.**
* Even though APS models are high-efficiency converters of electricity, their rated output capacities are limited by the
amp-hour size of the external batteries. ** You must set Configuration DIP Switch #1, Group A (Battery Type) to match the
type of batteries you connect or your batteries may be degraded or damaged over an extended period of time. See “APS
Configuration,” page 5 for more information.)
Selecting Battery Amp Hour Capacity
1. Add the Wattage Ratings of your connected equipment to determine the Total Wattage
Required.*
2. Divide the Total Wattage Required (from Step 1) by the battery voltage to determine the DC
Amperes Required.
3. Multiply the DC Amperes Required (from Step 2) by the number of hours you estimate will
pass without AC power before your battery can recharge to determine a Battery Amp-Hours
Required Rough Estimate.**
4. Compensate for inefficiency by multiplying your Battery Amp-Hour Required Rough Estimate
(from Step 3) by 1.2 to determine how many amp-hours of battery backup (from one or
several batteries) you should connect to your APS. Note that the Amp-Hour ratings of
batteries are usually given for a 20 hour discharge rate. Actual Amp-Hour capacities are less
when batteries are discharged at faster rates: batteries discharged in 55 minutes provide only
about 50% of their listed Amp-Hour ratings, while batteries discharged in 9 minutes provide
as little as 30% of their Amp-Hour ratings.
* The wattage rating is usually stated in the equipment’s manuals or on their nameplates. If your equipment is rated in
amperes, convert to watts by multiplying the ampere rating by your nominal AC line voltage (230). ** Your charging amps
multiplied by the charging hours must exceed the discharge amp-hours taken from the batteries between charges or you
will eventually run down your battery bank.
(See Diagram 2, p. 36)
Mounting (Optional)
Horizontal mounting should be used for all vehicular applications. Due to their size and weight,
all APS PowerVerter systems in vehicles should be mounted on a rigid horizontal (not vertical)
surface, mounting plate or bracket before battery connection.User must supply all fasteners and
brackets and verify their suitability for use with the intended mounting surface. Turn your APS
PowerVerter and connected equipment OFF before mounting.
• Install two 8 mm (1/4 in.) fasteners (A) into a rigid horizontal surface using the
measurements in the diagram. Leave the heads of fasteners raised slightly above the
surface in order to engage the slots in the APS’s feet.
• Slide PowerVerter forward to fully engage the fasteners in the APS’s feet. Install two
8 mm (1/4 in.) fasteners (B) into the surface, through the slots in the APS’s two
unsecured feet. Tighten the screws to secure the APS in position.
Download from Www.Somanuals.com. All Manuals Search And Download.
8
Battery Connection
Standard
1. Connect your APS’s positive DC Terminal directly to a fuse.
Tripp Lite recommends that you install a recognized component fuse block and fuse within
18 inches of the battery. The fuse's rating must equal or exceed the Minimum DC Fuse
Rating listed in your APS model’s specifications on pages 16 or 17.
2. Choose a battery configuration appropriate to your batteries.
• Single Battery Connection: Refer to Diagram 4, page 37. When using a single battery,
its voltage must be equal to the voltage of your APS’s Inverter Nominal Input Voltage
(see specs).
• Parallel Battery Connection: Refer to Diagram 5, page 37. When using multiple
batteries in parallel, each battery's voltage must be equal to the voltage of your APS’s
Inverter Nominal Input Voltage (see specs).
• Series Battery Connection: Refer to Diagram 6, page 37. When using multiple batteries
in series, all batteries must be equal in voltage and amp hour capacity, and the sum of
their voltages must be equal to the voltage of your APS's Inverter Nominal Input Voltage
(see specs).
3. Use 2/0 gauge wire ONLY to make external battery connections. Tighten battery terminals
to a torque of 4 N-m.
Battery connection cable lengths should be short as possible, and must not exceed the Maximum
Cable Length listed under Specifications, page 16 or 17. Shorter and heavier gauge cabling limits
DC voltage drop and allows for maximum transfer of current.* You must tighten your battery
terminals to approximately 4 Newton-meters of torque to create an efficient connection and prevent
excessive heating. Insufficiently tightening terminals could void your PowerVerter’s warranty.
* APS models are capable of delivering a much higher wattage output for brief periods of time. Wiring should be
configured to handle this brief high-current draw. Though your APS is a high-efficiency converter of electricity, its rated
output capacity is limited by the length and gauge of the wires running from the battery to the APS.
DC Vehicular
APS systems may be permanently mounted in a car, truck or boat and connected to draw power from
the vehicle’s battery. Note: An APS can ONLY be connected to vehicle batteries with voltage
that matches the APS’s Nominal DC Input—12V vehicle batteries to 12V Nominal DC
Input APS systems, etc. (See Specifications). There are two main ways to make this sort of
vehicular battery connection. Choose the Basic Connection if you are running light hand tools or
other small appliances for a brief period of time (see Diagram 7, p. 38). Choose the Advanced
Connection if you are using your APS to power heavy loads for extended periods of time (see
Diagram 8, p. 38). The Advanced Connection incorporates a battery isolator and separate battery
system to provide battery power to your APS while preventing it from draining your vehicle’s
battery. Note: Depending on your application, you may require more than one Deep Cycle Battery.
Caution: Never operate your APS from an alternator without a battery connected as shown in Diagrams 7 or 8, p. 38.
Download from Www.Somanuals.com. All Manuals Search And Download.
9
Battery Connection continued
DC Ground Connection
APS systems must be connected to a grounded, permanent wiring system. For most installations,
the negative battery conductor must be bonded to the grounding system at one (and only one)
point in the system. All installations must comply with national and local codes and ordinances.
AC Connection
Before AC connection, match the power requirements of your
equipment with the power output of your APS to avoid overload.
When figuring the power requirements of your equipment, do not confuse “continuous” power
ratings with “peak” power ratings. Electric motors require more power to turn on (“peak power”)
than they require to run continuously. “Peak” power ratings are usually 2 to 5 times
“Continuous” ratings. Most electric motors require “peak power” only when they are first turned
on. The electric motors in equipment such as refrigerators and sump pumps, however, constantly
turn on and off according to demand. These motors require “peak power” at multiple, unpredictable
times during their operation.
(See Diagram 3, p. 36)
Hardwired Electrical Connections (All hardwire models)
Consult a qualified electrician and follow all applicable electrical codes and requirements.
HARDWIRE PROCEDURE
1. Remove screws and cover plate from your APS’s Hardwire AC electrical box. Remove the
knockout covers closest to the desired electrical source and to your equipment.
2. Thread your wires through strain reliefs and through the knockouts.
3. Connect all input and output ground wires to the input/output ground tie point.
4. Connect the incoming hot wire to the input hot (brown) terminal.
5. Connect the incoming neutral wire to the input neutral (blue) terminal.
6. Connect the outgoing hot wire to the output hot (black) terminal.
7. Connect the outgoing neutral wire to the output neutral (white) terminal.
8. Tighten and affix strain reliefs. Replace cover plate and tighten screws.
(All corded models)
AC Input Electrical Connection
This IEC receptacle should be connected to a dedicated 15 Amp AC utility outlet that provides
a connection to ground. A detachable IEC cord is provided for this purpose. Plug it into an outlet
providing 230V AC power at 50 Hz. A user-supplied adapter that maintains the UPS’s connection
to ground may be necessary. (A technician may be able to convert your APS to receive 60 Hz.
power. Consult Tripp Lite for details.) Make sure that the circuit you connect your APS to has
adequate overload protection, such as a circuit breaker or a fuse.
Download from Www.Somanuals.com. All Manuals Search And Download.
10
AC Connection continued
AC Output Electrical Connection (All corded models)
Simply plug your equipment into the unit’s AC receptacles. If adapters must be used, choose
adapters that provide a connection to ground.
Set Operating Mode Switch
• Switch to “AUTO/REMOTE” when you are using connected equipment. ADVANTAGE:
Uninterruptible power supply. Provides battery backup power during blackouts or
brownouts.
Note: When the switch is in the “AUTO/REMOTE” position, you can operate a user-supplied switch to transfer
between battery-backup and charge-only modes. (See Remote Connector manual for more information.)
• Switch to “CHARGE ONLY” when you are not using connected equipment. (WARNING!
APS will not provide battery backup!) ADVANTAGES: A) Continues to charge battery
when power is present, and B) Turns OFF the APS’s inverter, preventing battery drain
during blackouts or brownouts.
• Switch to “OFF” to completely turn off the APS and connected equipment or to reset the
APS after it has shut down due to overload or overheating.
Switches, Indicator Lights & Other Features
(See Diagrams 9a and 9b, p. 39 and 40 to locate the following switches, indicator lights
and other features.)
Switches
1. Operating Mode Switch (All models): This switch selects the APS operating mode (either
“AUTO/REMOTE”, “OFF” or “CHARGE ONLY”). See “Set Operating Mode Switch”, pg. 11
to select the optimum setting for this switch.
2. “CONFIGURATION SWITCHES”—DIP Switch Group A (All models): These four
switches must be set for the type of battery your APS will be connected to and the voltage
points at which your APS will switch to battery power. See “Configuration”, pg. 5 to select the
optimum settings for these switches.
3. “CONFIGURATION SWITCHES”—DIP Switch Group B (Select models only): These
DIP Switches allow you to equalize the internal resistance of your battery’s cells and set the
percentage of your model's maximum load at which the APS will limit battery charging. See
“Configuration”, pg. 6 to select the optimum settings for these switches.
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Switches, Indicator Lights & Other Features continued
Indicator Lights
4. “LINE” (All models): This green light will turn continuously ON whenever connected
equipment is receiving utility-supplied AC power and your APS is set to “AUTO/REMOTE”,
meaning that it will provide battery backup if utility power fails. It will flash intermittently
when connected equipment is receiving utility power and your APS’s Operating Mode Switch
is set to “CHARGE ONLY” to warn you that the APS’s inverter is OFF and that the APS WILL
NOT provide battery backup during blackouts, brownouts or overvoltages.
5. “INV” (Inverting—all models): This yellow light will turn continuously ON whenever
connected equipment is receiving battery-supplied AC power (during a blackout, brownout or
overvoltage while connected to utility power or when connected to batteries during vehicular
operation).
6. “LOAD” (All models): This red light will turn continuously ON when the APS’s load is
between 80% and 110% of capacity. The light will flash intermittently when the APS’s inverter
shuts down due to a severe overload or overheating. If this happens, turn Operating Mode
Switch OFF. Remove the overload and let the unit cool. You may then turn the APS ON after
it cools.
7. “CUT/BOOST” (VRI models only): These lights will turn ON whenever your APS is
automatically correcting high (CUT) or low (BOOST) AC line voltage. This is a normal,
automatic operation of your APS that does not drain battery power, and no action is required
on your part.
8. “BATTERY HI/MED/LO” (All models): These three lights will turn ON in several
sequences to show the approximate charge level and voltage of your connected battery bank
and alert you to several fault conditions:
BATTERY CHARGE INDICATION (Approximate)
Indicator
Capacity
Green
91% - Full
Green & yellow
Yellow
81% - 90%
61% - 80%
Yellow & red
Red
41% - 60%
21% - 40%
All three lights off
Flashing red
1% - 20%
0% (Inverter shutdown)
All three lights flash slowly* Excessive discharge
All three lights flash quickly** Overcharge
* Approximately 1/2 second on, 1/2 second off. See Troubleshooting section. ** Approximately 1/4 second on, 1/4 second
off. May also indicate a battery charger fault exists. See Troubleshooting section.
Download from Www.Somanuals.com. All Manuals Search And Download.
12
Switches, Indicator Lights & Other Features continued
Other Features
9. DC Input Terminals (All models): The terminals’ lug screws secure the wires leading from
your external battery or battery system. Your battery or battery system must provide your
APS with proper DC voltage and your equipment with an adequate amp hour capacity. See
Battery Selection section, pg. 8 for more information.
10. AC Receptacles: IEC 320 (Corded models only): These IEC receptacles allow you to
connect equipment that would normally be plugged into a utility outlet. For other plug
configurations, use an adapter that provides a connection to ground.
11. AC Input: IEC 320 (Corded models only): This IEC receptacle should be connected to a
dedicated 15 Amp AC utility outlet via an adapter cord that provides a connection to ground.
A detachable IEC to 5-15 cord is provided for this purpose. DO NOT plug the cord into the
APS’s AC receptacles.
12. Hardwire AC Input/Output Terminal Strip (Hardwire models only): Use the lug screws
on these terminals to secure hardwire connections for AC input and output. See pages 10 & 36
for wiring instructions.
13. Resettable Circuit Breakers (All models): These circuit breakers protect your APS against
damage due to input or output overload. If a breaker trips, remove some of the load on the
APS to prevent overload, then wait 1 minute to allow components to cool before resetting
the circuit breaker.
14. Remote Module Connector (All models): The front panel of all models has an RJ45
receptacle for use with the optional remote module. (Module is included with all VR
models.) See the installation instructions packed with the remote module.
15. Load Sense Potentiometer (All models): In order to save battery power, the APS’s inverter
automatically shuts off when no load is connected. When the unit detects a load, it
automatically turns the inverter on. Users may choose the minimum load the APS will detect
by adjusting the Load Sense Potentiometer. Using a small tool, turn the potentiometer
clockwise to lower the minimum load that will be detected, causing the inverter to turn on
for smaller loads. When the potentiometer is turned fully clockwise, the inverter will operate
even when there is no load. Turn the potentiometer counterclockwise to increase the minimum
load that will be detected, causing the inverter to stay off until the new minimum load is
reached. The factory setting for the potentiometer is fully clockwise, but in areas with
frequent power interruptions, the potentiometer should be adjusted counterclockwise until
the inverter is only in operation when the APS’s load is in use.
Download from Www.Somanuals.com. All Manuals Search And Download.
13
Maintenance & Service
Maintenance
Your APS model requires no maintenance but should be kept dry at all times. Periodically check
all cable connections both at the unit and at the battery. Clean and tighten connections as necessary.
Service
If returning your APS to Tripp Lite, please pack the APS carefully, using the ORIGINAL PACKING
MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If
the APS is within the warranty period, enclose a copy of your sales receipt.
Limited Warranty
Tripp Lite warrants its products to be free from defects in materials and workmanship for a period of one year
(domestic) or 120 days (export) from the date of initial purchase. Tripp Lite’s obligation under this warranty is
limited to repairing or replacing (at its sole option) any such defective products. To obtain service under this
warranty you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an authorized
Tripp Lite service center. Products must be returned to Tripp Lite or an authorized Tripp Lite service center with
transportation charges prepaid and must be accompanied by a brief description of the problem encountered and
proof of date and place of purchase. This warranty does not apply to equipment which has been damaged by
accident, negligence or misapplication or has been altered or modified in any way. This warranty applies only to
the original purchaser who must have properly registered the product within 10 days of purchase.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not
permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not
apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT,
SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT,
EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Tripp Lite is not liable for any costs,
such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs
of substitutes, claims by third parties, or otherwise.
Download from Www.Somanuals.com. All Manuals Search And Download.
14
Troubleshooting
Try these remedies for common APS problems before calling for help. Call Tripp Lite Customer Service at (773)
869-1234 before returning your APS for service.
SYMPTOM
PROBLEMS
CORRECTIONS
APS does not provide
AC output (AC input present)
APS not properly connected to
utility power.
Connect APS to utility power.
Circuit breaker is tripped.
Reset circuit breaker.
APS shutdown due to excessive
battery voltage, indicating possible
charger failure. Line disconnected
to prevent permanent battery
damage.
Turn APS “OFF”. Wait 1 minute and
switch to “AUTO/REMOTE”.
APS is set to “OFF”
Set APS to “AUTO/REMOTE” or
“CHARGE-ONLY”.
APS does not provide
Circuit breaker is tripped.
Reset circuit breaker.
AC output (AC input absent)
Operating Mode Switch is set
to “CHARGE ONLY”.
Set Operating Mode Switch to
“AUTO/REMOTE.”
Load or High Temperature fault.
Turn APS “OFF”. Wait 1 minute.
Remove overload. Switch to
“AUTO/REMOTE”.
Excessive battery discharge.
Connected batteries are dead.
Check battery condition.
APS will not charge the
Check and replace old batteries.
battery (AC input present)
Battery fuse* is blown.
Check and replace fuse.
Battery cabling* is loose or degraded. Check and tighten or replace cabling.
APS charger failure.
Turn APS “OFF”. Wait 1 minute and
switch to “AUTO/REMOTE”. If
automatic shutdown occurs, call
Tripp Lite Customer Service.
All APS Indicator Lights are
OFF (AC input absent)
This is normal if the APS is set
to “CHARGE-ONLY”
—
All APS Indicator Lights are
OFF (AC input is present or
absent)
Excessive battery discharge.
Use an auxiliary charger* to raise
battery voltage. Check external
battery connections and fuse.
Automatically resets when condition
is cleared.
All APS Battery Indicator
Lights are slowly flashing.
Excessive battery discharge.
Use an auxiliary charger* to raise
battery voltage. Automatically resets
when condition is cleared.
APS “LOAD” Battery Light
flashing
Inverter shutdown because battery
voltage dropped too low for more
than 5 seconds. Protects battery
from permanent damage.
Reset by cycling control switch to
“OFF” position then to “AUTO/
REMOTE”.
All APS Battery Lights are
rapidly flashing
High battery voltage shutdown
during Charge mode.
Check all charging sources. Reset by
cycling control switch to “OFF” then
to “AUTO/REMOTE” or “CHARGE-
ONLY”.
APS “LOAD” Indicator Light
is rapidly flashing
Inverter overload caused by
excessive load or short circuit.
If sustained for more then 5
seconds the Inverter is shutdown.
Reset by reducing load and cycling
control switch to “OFF” position then
to “AUTO/REMOTE”.
* User supplied
Download from Www.Somanuals.com. All Manuals Search And Download.
15
Specifications (Corded Models)
CORDED MODELS:
APSINT1012
Weight:
11.9 Kg
INVERTER
Continuous power (@ 20° C):
Surge power (5 seconds):
Efficiency (Full Load):
Minimum DC Fuse Rating:
1000 W
2000 W
88%
170A
DC Input Current @ Nominal V DC
Full Load
No Load
95A
2.6A*
Nominal Input Volts:
12 VDC
DC Input Voltage Range:
Nominal Output Volts:
Nominal Output Frequency:
10-15 VDC
230 VAC 5%
50† Hz .3%
BATTERY CHARGER
Charging Capacity DC:
Maximum Cable Length
Acceptance Volts VDC:
30 A
2 ft.
Selectable
14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel):
Input Voltage AC:
13.3 V (13.6 V)
230 V
Input Current AC:
3.3 A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 144**,163, 182 or 201VAC
Selectable 259** or 264 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Maximum Input Current
(Continuous, Charger at Maximum):
12.0 A
Input Frequency:
50 Hz 10%
4.3 A
Maximum Output AC (Continuous):
Automatic Transfer Time:
4-6 ms
* Load sense can reduce this to 1/30 of the listed current. **Factory default setting.
† A technician may be able to convert your UPS to receive 60 Hz 10%power. Consult Tripp Lite for details.
Download from Www.Somanuals.com. All Manuals Search And Download.
16
Specifications (Hardwired Models)
HARDWIRED MODELS:
APSINT1524
APSINT2012
Weight:
12.7 Kg
17.1 Kg
INVERTER
Continuous power (@ 20° C):
Surge power (5 seconds):
Efficiency (Full Load):
Minimum DC Fuse Rating:
1500 W
3000 W
89%
2000 W
4000 W
87%
90A
370A
DC Input Current @ Nominal V DC
Full Load
No Load
70A
1.5A*
192 A
3 A*
Nominal Input Volts:
24 VDC
12 VDC
DC Input Voltage Range:
Nominal Output Volts:
Nominal Output Frequency:
20-30 VDC
230 VAC 5%
50† Hz .3%
10-15 VDC
230 VAC 5%
50† Hz .3%
BATTERY CHARGER
Charging Capacity DC:
Maximum Cable Length
Acceptance Volts VDC:
10 A**
7 ft.
Selectable
60 A
1 ft.
Selectable
28.8 V**/28.4 V Wet**/Gel
14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel):
Input Voltage AC:
26.6 V (27.2 V)
230 V
13.3 V (13.6 V)
230 V
Input Current AC:
2.2 A**
7.0 A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 144**, 163, 182 or 201 VAC Selectable 144**,163, 182 or 201 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Selectable 259** or 264 VAC
Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
13.0 A
16 A
Input Frequency:
Maximum Output AC (Continuous)
Automatic Transfer Time:
50 Hz 10%
6.5 A
4-6 ms
50 Hz 10%
8.7 A
4-6 ms
HARDWIRED MODELS (Cont.):
Weight:
APSINT2424
18.5 Kg
APSVRI3636
25.6 Kg
INVERTER
Continuous power (@ 20° C):
Surge power (5 seconds):
Efficiency (Full Load):
Minimum DC Fuse Rating:
2400 W
4800 W
89%
3600 W
7200 W
88%
220A
130A
DC Input Current @ Nominal V DC
Full Load
No Load
112 A
1.8 A*
114 A
2 A*
Nominal Input Volts:
24 VDC
36 VDC
DC Input Voltage Range:
Nominal Output Volts:
Nominal Output Frequency:
BATTERY CHARGER
Charging Capacity DC:
Maximum Cable Length
Acceptance Volts VDC:
20-30 VDC
230 VAC 5%
50† Hz .3%
30-45 VDC
230 VAC 5%
50† Hz .3%
30 A
3 ft.
Selectable
30 A
4.5 ft.
Selectable
28.8 V**/28.4 V Wet**/Gel
43.2 V**/42.6 V Wet**/Gel
Float Volts VDC (w/gel):
Input Voltage AC:
26.6 V (27.2 V)
230 V
39.9 V (40.8 V)
230 V
Input Current AC:
7.0 A
10.4 A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 144**,163, 182 or 201 VAC Selectable 144**,163, 182 or 201 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Selectable 259** or 264 VAC
Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
Input Frequency:
Maximum Output AC (Continuous)
Automatic Transfer Time:
17.0 A
50 Hz 10%
10.4 A
26.0 A (30.0 A***)
50 Hz 10%
15.7 A
4-6 ms
4-6 ms
*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming
current.†A technician may be able to convert your UPS to receive 60 Hz 10%power. Consult Tripp Lite for details.
Download from Www.Somanuals.com. All Manuals Search And Download.
17
Diagrams/Esquemas
1.2
1.1
1
See “Configuration”, pg. 5. 1.1 is DIP Switch Group A. 1.2 is DIP Switch Group B.
Refiérase a la sección “Configuración”, página 22. 1.1 representa el Grupo A de Interruptores DIP. 1.2 representa el Grupo B de
Interruptores DIP
2
3
3.3
3.4
3.5
3.6
3.7
OUTPUT/NEUTRA
OUTPUT/HOT
GROUND
INPUT/NEUTRA
INPUT/HOT
“FOR USE WITH COPPER WIRE ONLY”
3.2
3.1
See Hardwire Electrical Connections, pg. 10.
3.1 is the cover plate;
3.2 are the DC input terminals;
3.3 is the output neutral (white);
3.4 is the output hot (black);
3.5 is the input/output ground tie point;
3.6 is the input neutral (blue); and
3.7 is the input hot (brown).
Refiérase a la sección “Conexiones Eléctricas Directas
al Circuito”, página 28.
3.1 representa la cubierta;
3.2 representan las terminales de entrada de CD;
3.3 representa la terminal neutra de salida (blanca);
3.4 representa la terminal positiva de salida (negra);
3.5 representa la terminal entrada/salida de tierra;
3.6 representa la terminal neutra de entrada (azul) y
3.7 representa la terminal positiva de entrada (café).
Download from Www.Somanuals.com. All Manuals Search And Download.
36
Diagrams/Esquemas
4.1
4
X Volts
APS
See Battery Connection, Pg. 9. 4.1 is the fuse. X = Your APS’s Inverter's Nominal Input Voltage. (See specs.)
Refiérase a la sección “Conexión de Baterías”, página 26. 4.1 representa el fusible. X = El Voltaje Nominal de Entrada del
Inversor del APS. (Vea las especificaciones).
5.1
5
X Volts
X Volts
X Volts
X Volts
APS
See Battery Connection, Pg. 9. 5.1 is the fuse. X = Your APS’s Inverter’s Nominal Input Voltage. (See specs.)
Refiérase a la sección “Conexión de Baterías”, página 26. 5.1 representa el fusible. X = El Voltaje Nominal de Entrada del
Inversor del APS. (Vea las especificaciones).
6
6.1
X/2 Volts
X/2 Volts
APS
See Battery Connection, Pg. 9. 6.1 is the fuse. X = Your APS’s Inverter’s Nominal Input Voltage. (See specs.)
Refiérase a la sección “Conexión de Baterías”, página 26. 6.1 representa el fusible. X = El Voltaje Nominal de Entrada del
Inversor del APS. (Vea las especificaciones).
Download from Www.Somanuals.com. All Manuals Search And Download.
37
Diagrams/Esquemas
7.1
7.2
7.3
7.4
7
12V
APS
Basic 12VDC Vehicular Battery Connection. See Pg. 9.
7.1 is the alternator. 7.2 is the vehicle battery ground. 7.3 is the vehicle battery. 7.4 is the fuse.
Conexión Básica de Baterías de 12V de CD en Vehículos. Vea página 27.
7.1 representa el alternador.
7.2 representa la conexión a tierra de la batería del vehículo.
7.3 representa la batería del vehículo. 7.4 representa el fusible.
8.1
8.2
8.3
8.4
8.5
8.6
8
12V
APS
12V
Advanced 12VDC Vehicular Battery Connection. See Pg. 9.
8.1 is the alternator. 8.2 is a battery isolator. 8.3 is the vehicle battery ground. 8.4 is an auxiliary vehicle battery. 8.5 is the
vehicle battery. 8.6 is the fuse.
Conexión Avanzada de Baterías de 12V de CD en Vehículos. Vea página 27.
8.1 representa el alternador. 8.2 representa el aislador de la batería. 8.3 representa la conexión a tierra de la batería.
8.4 representa la batería auxiliar del vehículo.
8.5 representa la baterÍa del vehiculo. 8.6 representa el fusible.
Download from Www.Somanuals.com. All Manuals Search And Download.
38
Diagrams/Esquemas
Corded Model • Modelo con Cable
9a
2
8
14
4
5
6
1
15
13
10
9
16
11
1. Operating Mode Switch (All models)
2. DIP Switch Group A (All models)
1. Interruptor “Operating Mode”
(Modo de operación)
2. Grupo A de Interruptores DIP
(Todos los modelos)
3. DIP Switch Group B (Select models only)
4. “LINE” (All models)
3. Grupo B de Interruptores DIP
(Modelos selectos únicamente)
5. “INV” (Inverting—all models)
6. “LOAD” (All models)
4. “LINE” (Línea) (Todos los modelos)
5. “INV” (Inversor) (Todos los modelos)
6. “LOAD” (Carga Conectada)
8. “BATTERY HI/MED/LO” (All models)
9. DC Input Terminals (All models)
10. AC Receptacles (Corded models only)
8. “BATTERY HI/MED/LO” (Carga de
Baterías Alta/Media/Baja) (Todos los modelos)
11. Fixed AC Input Line Cord fixed
(Corded models only)
9. Terminales de Entrada de CD
(Todos los modelos)
13. Resettable Circuit Breakers (All models)
14. Remote Module Connector (All models)
15. Load Sense Potentiometer (All models)
10. Receptáculos de CA (Solamente en los
modelos con cable de CA)
16. Ground Connector Block
(Corded models only)
11. Cable de Línea de CA (Solamente en los
modelos con cable de CA)
13. Interruptores de Circuito con Restablecimiento
14. Conector para el Módulo de
Control Remoto (Todos los modelos)
15. Potenciómetro Sensor de Carga
Conectada (Todos los modelos)
16. Conexión a Tierra (Solamente en los
modelos con cable de CA)
Download from Www.Somanuals.com. All Manuals Search And Download.
39
Diagrams/Esquemas
Hardwired Model • Modelo con Toma Directa al Circuito
9b
7
3
2
8
14
4
5
6
1
15
OUTPUT/NEUTRA
OUTPUT/HOT
GROUND
13
12
INPUT/NEUTRA
INPUT/HOT
“FOR USE WITH COPPER WIRE ONLY”
9
1. Operating Mode Switch (All models)
2. DIP Switch Group A (All models)
3. DIP Switch Group B (Select models only)
4. “LINE” (All models)
1. Interruptor “Operating Mode”
(Modo de operación) (Todos los modelos)
2. Grupo A de Interruptores DIP
(Todos los modelos)
3. Grupo B de Interruptores DIP
(Modelos selectos únicamente)
5. “INV” (Inverting—all models)
6. “LOAD” (All models)
4. “LINE” (Línea) (Todos los modelos)
5. “INV” (Inversor) (Todos los modelos)
6. “LOAD” (Carga Conectada)
(Todos los modelos)
7. “CUT/BOOST” (VR models only)
8. “BATTERY HI/MED/LO” (All models)
9. DC Input Terminals (All models)
12. AC Input/Output Terminal Strip
(Hardwire models only)
7. “CUT/BOOST” (disminuyendo / elevando)
(Modelos VR solamente)
13. Resettable Circuit Breakers (All models)
14. Remote Module Connector (All models)
15. Load Sense Potentiometer (All models)
8. “BATTERY HI/MED/LO” (Carga de
Baterías Alta/Media/Baja) (Todos los mod-
elos)
9. Terminales de Entrada de CD
(Todos los modelos)
12. Barra de Terminales de Toma Directa
a Entrada/Salida de CA (Modelos con
toma directa al circuito solamente)
13. Interruptores de Circuito con
Restablecimiento
14. Conector para el Módulo de
Control Remoto (Todos los modelos)
15. Potenciómetro Sensor de Carga
Conectada (Todos los modelos)
93-2007 (200106010)