Trion Air Compressor 147207 001 User Manual

Air Boss ATS  
(Air Treatment Systems)  
ATS SERIES  
INSTALLATION  
OPERATION  
SERVICE  
Electrostatic Precipitators for  
Commercial & Industrial  
Applications  
101 McNeill Road Sanford, NC 27330  
(919) 775-2201 Fax: (919) 774-8771  
(800) 884-0002  
MANUAL PART NO. 147207-001 December 2002  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To provide access to the system components (except  
the blower section), gasketed doors with push-button  
latches and lift-off hinges are located 90 degrees to the  
direction of airflow on one side of the cabinet. Access  
preference should be noted when unit is ordered.  
Access to the blower section is obtained by removing  
the bolts retaining the discharge end panel.  
SECTION I DESIGN  
FOR THE SYSTEM DESIGN ENGINEER  
1. Introduction  
ATS units are Air Treatment Systems designed to  
efficiently remove a variety of contaminants from an air  
stream. These contaminants my range from those found  
in normal kitchen ventilation air to weld fumes or oils  
and effluents from various manufacturing processes. A  
range of units is available to clean specific air volumes.  
The power supplies providing the necessary high  
voltage for the electronic air cleaner and the controls  
initiating and sequencing the wash cycle are housed in  
a NEMA 12 enclosure designed for remote mounting. In  
addition, the enclosure is a central junction for the  
primary wiring.  
Each unit is made up of mechanical and electronic “dirt”  
collecting modules and efficient, trouble free operation  
is absolutely dependent upon the periodic removal of  
the collected contaminate from the cleaning elements.  
Unit design simplifies this requirement.  
The standard 16-gallon detergent system is furnished  
as a completely assembled unit to be piped directly to  
the wash water supply, into the wash manifold headers.  
When properly installed, operated and maintained, the  
ATS unit will effectively and efficiently perform its  
designed task.  
Note: 30 or 55-gallon detergent tanks are available as  
an option.  
Note: Trion Tridex Detergent is specially formulated for  
use with Trion electronic air cleaners. Use of other  
cleaners and detergents, not specifically approved by  
Trion, can cause possible failures in the unit and will void  
any warranties on our equipment.  
2. General Description  
The standard major components supplied with each  
ATS unit are as follows:  
Base unit consisting of five modular sections: 1)  
impinger, 2) electronic air cleaner 3) bag type media  
filter 4) activated carbon adsorber and 5)  
blower/motor.  
The strainer is to be installed in the wash water supply  
line. Factory installed solenoid valves are located in the  
piping inside the impinger and the electronic air cleaner  
sections.  
Washer control including high voltage power  
supply(s) to be mounted remotely.  
Detergent system to be located remotely.  
Wash water supply-line strainer.  
An optional chemical fire suppression system may be  
specified to be included with the ATS unit if it is a  
requirement of the application. The system available  
from the factory must be completed at the  
installation site by a qualified and authorized fire  
control contractor. In addition to final hook-up, he will  
complete tie-in with other existing systems, test, final  
inspect and if necessary, coordinate his work with local  
or other designated fire inspectors. The fire suppression  
system includes strategically located, spray nozzles and  
an electrical fire detection device to signal a control  
head that opens a valve to discharge a chemical  
cylinder. An auxiliary mechanical “Pull” is also supplied  
to be installed at a remote location to manually activate  
the system. The general contractor should coordinate  
his work with that required by the fire control contractor.  
Refer to fire control system outline drawing, Figure 7.  
The impinger section contains impinger panels to collect  
grease and liquid particulate, oscillating front and rear  
wash manifolds and metal mesh pre-filters (and after-  
filter when specified).  
The electronic air cleaner section contains the ionizing-  
collecting cells to remove very fine particles; oscillating  
front and rear wash manifolds and metal mesh pre-  
filters and after-filters.  
When a factory installed fire suppression system is  
specified, both the impinger and electronic air cleaner  
sections include spray nozzles. Fire control is usually  
required in kitchen exhaust and similar applications.  
The media section contains bag type filters providing  
safety filtration for the electronic air cleaner in the event  
of any accumulated blow-off or contaminant penetration  
in the event of an electrical outage.  
The following are standard options that may be  
specified on the basic systems:  
1. Without carbon section  
2. Without media section*  
3. Without carbon and media sections  
4. Without blower section  
For odor control, the adsorber section contains the  
activated carbon panels in a vee bank configuration.  
5. Additional electronic air cleaner section (double  
pass unit)  
6. 30 or 55 gallon detergent system  
7. Perforated plate in lieu of the metal mesh filters  
8. Fire suppression system  
With the exception of the wash manifolds and the  
blower/motor, all the major components slide in and out  
of the housing for ease of service.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
for the safety of operating personnel. Any additional  
access that may be provided in the system, where  
there is access to high voltage, must be equipped with  
such interlocks. Interlocks are readily available from  
the factory.  
*A carbon section without a media section is not  
recommended by TRION.  
3. System Design and Layout  
(Refer to, or request, submittal drawings for dimensions  
and data pertaining to a specific unit that is not included  
in this manual).  
Water wash drain lines from the cabinet drain basin  
should be trapped or otherwise sealed against the  
system pressure (in accordance with local codes).  
Wash water to the unit must meet the volume required  
for the specific unit involved, and between 35 PSIG Min.  
– 50 PSIG Max. at full flow to provide proper spray  
patterns from the wash nozzles. The wash water MUST  
be Hot water (1400F recommended) and installed as  
close as possible to the unit and detergent system.  
The arrangement of the supplied components and the  
general layout of the system will vary according to  
application, adjoining equipment and available space.  
However, there are several basic factors pertaining to  
all installations that must be considered:  
To maintain the selected cleaning efficiency, it is  
important to assure that the total air volume (capacity in  
CFM) is uniformly distributed across the entire face area  
of the unit. The metal mesh filters, perforated plate or  
mist suppressors, provide some resistance to effect  
even air distribution. However, since most air ducts are  
designed to handle air velocities greater than the rated  
velocity of the air cleaner, it is necessary to properly  
transition any attached ducting. If possible, a contraction  
ratio of 1 in 3 (approximately 20°) should be maintained.  
If space prohibits, turning vanes, air baffles or other  
means may be utilized. Ducting – where attached to the  
cabinet collars – should be gasketed, caulked or  
otherwise made watertight. The bottom of the air-  
entering duct should be reasonably flat and sloped  
toward the impinger drain pan for a length of 18 inches.  
This will assure that any wash water splashback is  
returned to the drain basin. The ducting and duct  
connections should be designed in accordance with  
applicable code requirements.  
NOTE: THE HOT WATER TANK IS NOT PROVIDED BY  
TRION.  
When applicable, the detergent system, the wash water  
inlet piping and the drain lines must be protected from  
freezing temperatures.  
Each installation varies according to needs, but the  
water wash control must be located indoors, out of the  
weather, and as closed to the air cleaner as practical.  
Ideal mounting height is at eye level for ease in reading  
the instrumentation, and to facilitate service. The  
instructions furnished for manually operating the fire  
extinguishing system shall be posted conspicuously  
near the control in the kitchen or well-occupied work  
area.  
For ease in maintenance and component removal,  
adequate space, 39” Minimum Required, must be  
provided in front of all access doors, motors, pump and  
accessory equipment. Special consideration should be  
given in this respect for installations where the unit is  
suspended overhead. Catwalks or platforms should be  
provided.  
When there is a danger of rain, snow or debris being  
drawn into the system with outside air, the make-up air  
intake should be protected with rain louvers, hooding  
and hardware cloth to prevent the rain, snow or debris  
from entering the electronic air cleaner.  
Some contaminants to be collected, such as oils in  
vaporous state, must be condensed into particulate form  
prior to entering the ionizing-collecting cells in order to  
maintain the anticipated efficiency. Gases, vapors or  
any non-particulate cannot be precipitated and will  
therefore pass through the collecting elements. Any  
condensing that takes place downstream from the air  
cleaner defeats the purpose. By the same token, heavy  
concentrations of water vapor, or other matter that  
becomes highly conductive when condensed, must be  
prevented from entering and/or condensing in the  
electronic air cleaner to prevent electrical arc over and  
shorting. The impinger module aids in this process and  
will adequately handle light concentrations, however, it  
is recommended to insulate upstream ducting  
conveying warm air that is subjected to cold  
temperatures on applications such as kitchen exhaust.  
CAUTION  
In addition to the above space requirement, installation  
of the Model ATS in NFPA applications shall have a  
clearance of at least 18 inches to a combustible  
material, 3 inches to limited combustible material, and  
0 inches to noncombustible material. Any reduction in  
clearance or exceptions must be in compliance with  
NFPA and acceptable to the Authority Having  
Jurisdiction.  
****WARNING****  
Fire Suppression Systems  
Extreme caution should be exercised when this unit is  
installed in applications that are collecting volatile or  
potentially flammable contaminates such as cooking  
grease and petroleum based oils.  
Trion strongly recommends a fire suppression system  
be installed in the ductwork and on the Model ATS in  
cases where these contaminates are collected on the  
cell plates and collect on the attached ductwork.  
Contact the factory for questions or concerns  
regarding a fire suppression system.  
SAFETY NOTE:  
Factory designed access to all electrically charged  
high voltage components contain electrical interlocks  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
directional arrows concur with the designed airflow  
through the cabinet.  
To enable the factory to respond efficiently to  
manufacturing requests, the equipment purchase order  
must contain the following information in addition to the  
model and options.  
3. Connect Adjoining Duct Work  
When the adjoining ducting is installed on the air  
entering side, the bottom of the horizontal duct run  
should be relatively flat and sloped toward the section  
housing drain pan for an 18-inch length. This will enable  
any wash water splashback occurring during the  
washing operation to run back into the drain pan.  
1. The application and as much contaminate load data  
as possible. This will enable the wash control to be  
preset and adjusted to the optimum setting.  
2. The high-voltage lead length required if longer than  
the standard length of 50 feet.  
3. The side of the blower section the blower motor  
starter is to be installed. Left or right as determined  
when standing in the direction of air flow with the air  
striking your back.  
Secure the adjoining ducting to the section housing  
utilizing the .375-inch clearance holes provided. The  
seams should be made air and watertight by caulking or  
gasketing.  
4. The external static pressure that the blower/motor  
will handle due to ducting, hooding or other  
equipment.  
Upstream ducting conveying warm air and subjected to  
cold temperatures must be insulted to prevent  
excessive condensation.  
Contact the local Trion Sales Office or the factory if  
questions arise, or if any additional information is  
required.  
4. Mount Detergent System  
Refer to Figures 1 and 4. The detergent system should  
be located as close to the unit as practical in a level  
position. Service space must be provided for periodical  
manual filling of the detergent tank, and to gain access  
to the pump and motor assembly. When positioned, the  
assembly may be secured in place at the predrilled  
factory mounting pads, either by bolting or welding.  
SECTION II INSTALLATION  
FOR THE INSTALLING CONTRACTOR  
1. Unpack and Inspect  
At the time the unit is received, all shipping containers  
and their contents should be examined for damage. Any  
damage occurring in shipment must be immediately  
reported to the carrier, an inspection report completed  
and a claim filed at the receiving point.  
5. Connect Drain  
Connect a drain line to the 2” NPT couplings provided in  
the drain basins of the impinger and electronic air  
cleaner sections in accordance with the governing  
plumbing codes. The drain line must be sealed with a  
trap or other means to prevent air by pass. If a trap is  
used, it should hold sufficient water column to overcome  
the system air pressure and to assure that loss of liquid  
from evaporation between cleaning periods will not  
break the seal. The drain line should not be smaller than  
the drainpipe coupling, or it will otherwise restrict the  
flow of water. Refer to Figure 5.  
The unit modular sections are shipped completely  
assembled and joined and, where size permits, the  
electronic air cleaner ionizing-collecting cells are  
shipped inside the cabinet. On large units, the upper tier  
of cells may be shipped in separate containers. The  
wash control, detergent feeder and other separate  
accessories are shipped in the containers as noted on  
the packing list.  
6. Connect Water Wash Supply  
The items furnished for field installation in the water  
wash supply are a strainer, a back flow preventer (not  
supplied) and a detergent system. Refer to the Piping  
Schematic Figure 5.  
2. Position Air Cleaner Cabinet  
If advantageous, to remove weight for ease in handling,  
the filtration elements can be removed from their  
respective cabinets. Position the unit in the designated  
location giving consideration to the following points:  
Unless otherwise specified, the water wash supply  
should be hot (1400F recommended-WATER HEATER  
NOT SUPPLIED BY TRION) at the volume specified for  
the given unit, and at a full flow pressure between 40  
and 50 PSIG.  
WARNING: Adequate precautions should be taken  
in the event the water supply, detergent system and  
drains are subjected to freezing temperatures.  
(a) Excluding the blower section, there are access  
doors on one side of the section modules. Provide  
sufficient clearance in front of the doors on at least  
one side for service and element removal. Normally  
the side on which the factory installed blower motor  
starter is mounted is the pre-planned side for single  
side access.  
(b) Level the unit to assure proper drainage from the  
drain pans.  
Although not required, a pressure gage and a manual  
service valve are recommended as shown in the  
diagram. The components should be located within the  
system to provide for service access.  
After the cabinet has been properly located, it may be  
secured into place by bolting or welding. Reinstall any  
section elements removed during installation making  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
*One each for impinger and electronic air cleaner  
7. Mount Control  
Mount the wash control, also containing the high voltage  
power supplies, in the selected location. It must be  
mounted indoors out of the weather and should be at  
eye level to ease in monitoring unit operation and as  
close to the ATS unit as practical. Allow sufficient space  
in front of the access door for service. Refer to Figure 3  
for mounting hole layout and dimensions.  
9. Fire Suppression System (when specified to be  
factory supplied)  
The installation of the fire suppression nozzles, fire  
sensor device, the components within the chemical  
cylinder housing and the interconnections of the  
components has been completed at the factory. The  
authorized fire control contractor must complete the  
remote mechanical “Pull,” any other hookup or tie-in,  
final test and inspection. Refer to fire control system  
outline drawing, Figure 7.  
8. Complete Wiring  
(a). High Voltage Wiring  
WARNING:  
Mount the fire extinguishing system instructions in the  
designated area that is conspicuously located. This  
should be in the kitchen or a well occupied work area  
and is normally near the control.  
EXERCISE ALL THE NORMAL PRECAUTIONS  
WHEN WORKING WITH HIGH VOLTAGE AND  
COMPLY WITH NEC AND ALL APPROPRIATE  
LOCAL CODES.  
10. Check Out for System Start-up  
When the installation has been completed, assure that  
the equipment is ready for start-up by checking the  
following:  
The high voltage wiring entails interconnecting the  
power supply(s) with the ionizing-collecting cell(s)  
located in the electronic air cleaner section cabinet.  
On multicell units, the wiring between the cells  
within a tier is automatically made with intercell  
spring contacts.  
A. All construction debris is removed from the modular  
section cabinets and the adjoining ductwork.  
B. The inside of the power supply/control housing and  
the detergent feeder tank is clear of any foreign  
materials.  
C. The drain lines from the section drain basin are  
clear and that the line is completely connected to its  
point of termination.  
D. All supply line piping is completed and wash water  
is available.  
E. When required, assurance that the fire suppression  
system has been inspected and tagged into service  
by an authorized person.  
Refer to the Field Wiring Diagram Figure 6. Two 50  
ft., (or the length specified) high voltage leads, one  
for the ionizer and one for the collector, are factory  
furnished. When the installation requires more than  
one power supply, a set on leads is furnished for  
each supply. Ring type connectors have been  
factory installed at the cell termination of the leads.  
After the leads have been run and cut to the proper  
length, the slip-on connectors, shipped on their  
respective power supply terminals, should be  
secured by both crimping and soldering. For  
working ease, the power supply(s) may be  
F. Supply line power is available and electrical wiring  
is completed to the following components:  
removed from their retaining slide channels by  
removing the single bolt in the top corner of the  
circuit board. Each lead is to be run in separate  
rigid conduit and must be of continuous run. (Do  
not splice.) Knockouts are provided in the section  
housing pilasters for conduit connection.  
1. ATS Control  
2. Blower motor starter  
3. Manifold drive motors  
4. Solenoid valve  
5. Door interlock  
6. Temperature sensor (when specified)  
7. Ionizing-collecting dells  
8. Fire suppression system, as applicable  
(b). Primary Wiring  
Refer to the Field Wiring Diagram - Figure 6. The  
primary wiring should be completed using rigid  
conduit in accordance with prevailing electrical  
codes.  
G. NOTE: Do not put the initial supply of detergent  
into the detergent tank. This is to be done after  
volume settings are made at start-up.  
The wash control is the main distribution point for all  
primary wiring. The wiring includes the input supply  
to the control and the interconnections between the  
control and the following components:  
1. Detergent feeder  
2. Manifold drive motors*  
3. Solenoid valves*  
4. Door interlocks*  
5. Blower motor starter/disconnect  
6. Temperature sensor (when specified)  
7. Fire suppression control (when specified)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
The power supply(s) convert the 115-volt, 60Hz, single-  
phase AC supply to the high voltage DC needed to  
power the cell(s). The power supplies are solid state,  
pulse width modulated (PWM), line and load regulated.  
Potential output voltages of 12.5 KVDC are required for  
the ionizer and 6.25 KVDC for the collector at a  
maximum current of 6 MA. Each supply is retained in  
the control in slide channels and secured with one bolt  
located in the top corner of the circuit board.  
SECTION III OPERATION  
WARNING  
RISK OF ELECTRIC SHOCK  
These servicing instructions are for use by qualified  
personnel only. To reduce the risk of electric shock,  
do not perform any servicing other than that  
contained in the operating instructions unless you  
are qualified to do so.  
At a predetermined frequency the remotely located  
control automatically activates an integral wash system  
to flush away the collected contaminant. When  
activated, the duration of the washing cycle is  
approximately 80 minutes.  
FOR THE MAINTENANCE ENGINEER  
1. Description and Principles of Operation  
The basic ATS units are made up of five modular  
sections. Each of the first three sections employs  
different mechanisms to remove and capture particulate  
matter from the air.  
The wash system consists of a series of spray nozzles  
soldered into oscillating water wash manifolds. The  
manifolds are located in the front and rear of each cell  
tier. They are mechanically interconnected with a drive-  
belt and driven through direct linkage by a fractional HP  
motor. A detergent feeder is also incorporated into the  
wash system. The amount of detergent needed for each  
wash is readily field adjustable and that amount is  
dependent upon wash water temperature, the type and  
amount of contaminant collected.  
The first section, an impinger, is primarily designed for,  
and is especially effective in, capturing relatively large  
greasy liquid particulate. The impinger is constructed of  
two equally spaced layers of roll formed baffles. The  
spacing creates and air flow pattern which causes the  
contaminate to collect and flow down the baffles. Holes  
in the frame permit the liquid to drip into the drain basin  
below. Periodically, at a predetermined setting a  
remotely located control automatically activates  
oscillating wash manifolds located on both sides of the  
impinger to flush away any remaining tenacious matter.  
(Refer to the electronic air cleaner section below for  
additional description on the integral washer. It is  
identical to the impinger washer.)  
In addition to the preset automatic wash cycle, the  
washing operation may be initiated manually when  
required. The events in a wash cycle are:  
A. Power pack(s) and system blower ”OFF”  
B. Washer and detergent “ON” (each module)  
C. Washer and detergent “OFF” (each module)  
D. Pause for detergent to react  
The second section houses an electronic air cleaner,  
technically known as an electrostatic precipitator. In this  
type of equipment, all airborne particles, even of  
microscopic size, are electrically charged (positively) as  
they pass through a high voltage ionizer. These charged  
particles are then attracted and adhere to a series of  
parallel collecting plates, which form the negative  
elements of an electrostatic field.  
E. Washer “ON” for rinse (each module)  
F. Washer “OFF” (each module)  
G. Blower “ON” for forced dry  
The ionizer consists of charged stainless steel spiked  
blades spaced between grounded electrodes. The  
collecting section consists of parallel plates arranged so  
that each alternate plate is charged while the  
intermediate plates are electrically grounded.  
H. Power pack(s) “ON”  
When a fire control system is specified, both the  
impinger and electronic air cleaner sections contain  
chemical spray nozzles.  
The ionizing-collecting cells (contaminate collecting  
elements) are housed in the cabinet on slide rails. They  
can be removed from the cabinet as required, through  
the end access door, by sliding them out like drawers.  
On multicell units, all of the electrical connections  
between cells in a given tier are automatically made  
through spring connectors. On the access end, the high  
voltage from the power pack(s) is made with cables.  
When installing cells into the cabinet, observe the  
directional arrows on the cell end plates. The side of the  
cell containing the spiked ionizer blades always must be  
located on the air entering side.  
The third section houses a bag filter(s). In the event of  
an electrical outage in the electronic air cleaner, the bag  
filter acts as a safety backup collector.  
Also, in some applications, the bag filter will collect any  
precipitated agglomerates that may tend to “blow-off”  
the electronic air cleaner.  
When the bags become saturated with contaminant  
they must be removed and replaced. However, this  
requirement is relatively infrequent due to the pre-  
filtration upstream from the bag.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
A series of long deep pockets arranged side-by-side  
form the configuration of each bag. The ultra fine fibers  
used in the makeup of the filtering media offer to trap  
the contaminant.  
shall be forwarded to the authority having jurisdiction.  
For a fire suppression system supplied with the ATS  
unit refer to Figure 7.  
A. Inspect the inside of the adjoining ductwork and  
Trion cabinet to be sure it is clean and free of any  
debris or construction materials. Especially note the  
opening in the drain basin for any restrictions. The  
ducting, where secured to the cabinet collars,  
should be sealed watertight with either gasketing or  
caulking.  
The fourth section is employed in the ATS unit for odor  
control. Panels, filled with activated carbon granules,  
are arranged in a vee bank configuration to provide  
adequate surface area. The surface of each granule is  
extremely porous and absorbs materials that are in a  
gaseous or vaporized state that cannot be removed by  
the particulate filters. Using the carbon filters without the  
pre-filtration by the bag filters is not recommended.  
When the panels have become saturated or fully loaded  
they may be replaced with new or reactivated carbon.  
B. Inspect the ionizing-collecting cells to see that all of  
the ionizing blades are intact and that no large  
pieces of foreign material are lodged between the  
plates. Also verify that the cells are properly  
installed in the cabinet with the spiked ionizing  
blades located on the air entering side (Follow the  
air flow directional arrows).  
The fifth section, the blower/motor section, has been  
rated to handle the air movement requirements for the  
systems and the adjoining ducting.  
When the fire suppression system has been specified to  
be factory furnished it consists of strategically located  
chemical spray nozzles located in the impinger and  
electronic air cleaner modules. The fire suppression  
C. Check the high voltage leads to see that they are  
connected to the proper terminals, both at the  
ionizing-collecting cells and inside the power pack.  
Refer to Figures 6.  
chemical is stored in  
a
cylinder housed in  
a
weatherproof enclosure mounted on one side of the  
blower module. An electrical detection device, mounted  
downstream from the impinger module in the electronic  
air cleaner module, activates the system by sending a  
signal to a control head discharging the chemical  
cylinder.  
D. Be sure that the drain lines from the drain basins  
are completely connected and properly terminated.  
A trap or seal of some type should be incorporated  
in the line to prevent air bypass.  
E. Check the water supply line to be sure water is  
available and that the strainer, back flow preventer  
(by others) and detergent system are properly  
installed and connected. Refer to piping diagram  
Figure 5.  
In addition to the electrical detection device, a remotely  
located pull station is provided for mechanical activation  
of the system manually.  
Depending on the installation and any local, or other  
governing requirements, the ATS unit fire suppression  
system may be tied-in with other fire suppression  
devices. When the fire suppression system is activated,  
the unit electrical input power is disconnected to the  
ATS unit blower and the high voltage required for the  
electric air cleaner is disconnected. After the fire  
suppression system has been activated, the  
authorized fire suppression contractor must put it  
back into service. For a system supplied, with the ATS  
unit, refer to Figure 7.  
F. Be sure that electrical power is available, that the  
wiring is completed, and that the system blower is  
ready to energize. Refer to field wiring diagram  
Figure 6.  
G. Be sure that all access doors are closed.  
H. Close the system electrical supply switches, making  
power available to the control and blower motor  
starter. Check to verify blower rotation is as shown  
on the rotation indicator arrow.  
2. Initial Start-up  
I. Turn the “ON-OFF” selector switch to the control  
“ON”. The blower should run (if installed) and the  
power supply(s) should be energized. Electrical arc-  
over within the ionizing-collecting cells may occur. It  
is a normal occurrence caused by accumulation  
dust from constructions or other sources in the  
cell(s) and should soon subside. If the arc-over in  
continuous and does not subside, recheck the  
routing of the high voltage leads between the power  
supply(s) and the cell(s). Refer to field wiring  
diagram Figure 6. The ionizer lead must be  
connected to the ionizer and the connector lead to  
the collector. If arc-over still occurs, or difficulty  
Prior to equipment start-up, the fire extinguishing  
system employed in the ATS unit (and possibly  
adjoining equipment) must be inspected by properly  
trained and qualified personnel. This includes all  
actuation components including remote manual pull  
stations, mechanical or electrical devices, detectors,  
fire-actuated dampers, etc. These items shall be  
checked for proper operation during the inspection in  
accordance with the manufactures listed procedures. In  
addition to these requirements, the specific inspection  
requirements of the applicable NFPA standard shall  
also be followed. If required, certificates of inspection  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
other than that outlined above, refer to the Trouble  
Shooting reference chart Section IV.  
In our example, the restaurant operates Monday  
through Saturday (closed Sunday) and opens daily at  
6:00 a.m. and closes daily at 11:30 p.m. This busy  
schedule presents a relatively heavy dirt loading and  
being of greasy nature should be washed away daily.  
The best time being shortly after closing when the  
atmosphere has settled but before the greasy  
contaminant collected has had a chance to harden  
and setup.  
J. Be sure the detergent tank is clean, and then fill the  
tank 1/8 full with clean water. Do not fill with the  
detergent until start-up adjustments have been  
completed.  
K. (Review this paragraph in its entirety before initiating  
the wash start button.)  
From the above, a wash schedule of every day  
except Sunday at 1:00 a.m. can be established. As  
the duration of events preset at the factory is  
approximately 80 minutes, the cycle will end at  
approximately 2:20 a.m.  
Next, set the detergent volume setting per wash at  
the detergent feeder. Manually initiate the wash  
cycle by pushing the "Wash Start" button on the  
control. The wash control duration is 80 minutes  
and by means of a factory preset programmable  
logic controller (PLC) will sequence the washing  
events as previously outlined. When the detergent  
pump is energized, note the amount that is used by  
observing the reduction in the liquid level in the  
tank. The usage should be approximately 1 part of  
detergent to 20 parts of water. The water and  
detergent requirements for each unit model are  
listed in Table 1 on the Piping Schematic, Figure 5.  
To adjust the volume output from the pump, refer to  
the Detergent System Outline, Figure 4. The pump  
is a constant displacement type and the amount of  
detergent forced into the water supply to wash the  
unit is dependent upon the setting of the control  
valve in the bypass return line to the reservoir. The  
side of the translucent reservoir is marked with  
volume markers. Adjust the control valve to obtain  
the correct usage for the given unit model, then  
secure the setting with the Allen head set screw  
located in the valve adjustment knob. When the  
correct adjustment has been made, remove the  
remaining water from the reservoir and fill the tank  
with initial supply of detergent furnished.  
Prior to setting the initiator clock it will be necessary  
to charge the battery located inside the clock. This is  
accomplished by turning the selector switch on the  
front of the control to the "ON" position. A light inside  
the switch will glow. If it does not glow, check to be  
sure there is supply line power to the control. DO  
NOT PUSH THE WASH BUTTON. Allow the control  
to remain in the "ON" position for 24 to 36 hours  
while the battery is charging.  
L. When the wash control has cycled out, manually set  
the programmable timer relay (TR), or initiator clock,  
located in the control for automatic initiation of the  
washing operation. This setting can be tailored to the  
washing frequency best suited for the specific  
application and may be best explained by example.  
To set the initiator clock, it is first necessary to set the  
existing time, then the program times that are to be  
initiated.  
To set existing time:  
Suppose the application of the equipment is to clean  
restaurant kitchen exhaust air. The collected  
contaminant to be washed away is of greasy nature,  
containing particulate such as smoke and fume from  
the grill, mist and vapors from the French Fryer, flour  
dust and other various matter that is created by  
normal kitchen operation.  
1. Depress the reset (R) button to cancel out any  
previous settings.  
2. Slide the P-Run switch to the clock position.  
Monday (MO) will be indicated.  
3. Push the (1 ... 7) button until the present day of  
the week is indicated.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Push the hour (h) button to the present hour of  
the day.  
12. After the wash program has been set for TU,  
repeat the same setting procedure for WE, TH, FR  
and SA. Omit SU.  
5. Push the minute (m) button to the minutes past  
the hour of the day.  
13. Slide the P-Run switch to the run position. The  
existing time of day will show on the display. The six  
selected washdays established in the example have  
been set.  
6. Slide the P-Run switch to the run position. The  
colon will blink indicating the clock has been set.  
To set the programs (wash times) according to the  
times in the example outlined above.  
NOTE: Using the above procedures, different washing  
days and "ON - OFF" times may be established and  
set into the initiator clock to best serve a specific  
application.  
1. Slide the auto-manual switch to the auto position.  
2. Slide the P-Run switch to the program (P)  
position. The word "ON" and the number 1 will  
appear on the display. This indicates the time the  
first program is to be turned "ON."  
NOTICE: Once the reset key (R) is pressed, the  
previous time and program will be cleared to the  
initial state.  
3. Push the day (1 ... 7) button until only the day  
Monday (MO) appears on the display.  
Kitchen Exhaust Applications  
M. For safe and proper operation adhere to the following  
instructions and procedures:  
4. Push the hour (h) button until the designate hour  
(01:00) appears on the display.  
5. It is not necessary to set the minute (m), as 1:00  
o'clock on the hour was the selected wash initiation  
"ON" time. The "ON" time has now been set.  
1. Exhaust systems shall be operated during all  
periods of cooking in restaurant applications.  
2. Filter-equipped exhaust systems shall not be  
operated with filters removed.  
6. Next, set the program "OFF" time. This will be 1  
minute after the "ON" time. A 1-minute duration is  
adequate program time as the initiation signal is  
sent to the wash control logic timer instantaneously.  
3.The posted instructions for manually operating the  
fire extinguishing system shall be kept conspicuously  
posted in the kitchen and reviewed periodically with  
employees by the management.  
Push the I/0 (P) button. The word "OFF" and the  
number 1 will appear on the display. This indicates  
the set time the first program is to be turned "OFF."  
4. Listed exhaust hoods shall be operated in  
accordance with the terms of their listings and the  
manufacture instructions.  
7. Push the day (1 ... 7) button until only the day  
Monday (MO) appears on the display.  
5. Cooking equipment shall not be operated while its  
fire-extinguishing system or exhaust system is not  
operating or otherwise impaired.  
8. Push the hour (h) button until the hour 01:00  
appears on the display.  
9. Push the minute (m) button until the time 01:01  
appears on the display. Program 1, wash time "ON"  
and "OFF," for Monday has now been set.  
3. Wash Control and Detergent System Settings  
The total time required for the complete wash cycle is  
approximately 80 minutes. Four main events take place  
during the wash cycle: Wash, Soak, Rinse and Dry.  
Once the Wash Control has been initiated, either by  
manually pushing the washer start button, or through  
the means of the automatic time clock, the wash events  
will take place automatically. The time for each event  
has been preset at the factory in the programmable  
logic control (PLC).  
10. Next set the second program which will be the  
Tuesday (TU) washing. Push the program I/0 (P)  
button. The word "ON" and the number "2" will  
appear on the display.  
11. Repeat the setting process for TU as outlined  
above in steps 3 through 9 for MO "ON" - "OFF"  
time.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Some dirt is more tenacious than others to remove and  
may require a stronger detergent solution. Average  
settings have been factory set. Best possible settings  
for any given installation, however, are determined  
through experience. Determination can be made by  
visually examining the collecting elements after the first  
few washings.  
The front panel of the control contains indicating  
lights for the power supplies, one or two depending  
on the size of the ATS unit. The lights should be  
observed on a daily basis to ensure that the  
electronic air cleaners are operating.  
5. Preventative Maintenance  
To adjust the volume of detergent used within the given  
time setting, loosen the knurled knob with an Allen  
wrench on the control valve located in the by-pass line.  
Refer to the Detergent System Outline, Figure 4.  
Turning the knob clockwise increases the volume and  
counter clockwise decreases the volume. When  
adjustment has been made, be sure to retighten the  
setscrew.  
A. Washing frequency – as required.  
The washing schedule and detergent reservoir level  
as outlined under routine maintenance is again  
referenced here as excessively large contaminant  
buildup on the collecting elements invites down  
time. Established routine washing is a preventative  
maintenance  
requirement.  
The  
frequencies  
suggested below should be altered if necessary.  
4. Routine Maintenance  
B. Fire control system - Every 4 to 6 months or as  
required.  
A. Washing Frequency  
Inspection, cleaning and servicing of the fire  
extinguishing system and all listed exhaust hoods  
shall be completed by properly trained and qualified  
personnel. For a fire control system supplied with  
the ATS unit refer to Figure 7.  
The frequency that the collected dirt is to be washed  
from the unit depends upon the type and amount of  
dirt in the air to be cleaned. Dirt, which is greasy in  
nature, tends to harden after collection and should  
be washed away often. Likewise, units operating  
under extremely heavy dirt loads should be washed  
more often as a large build-up of collected material  
will have a tendency to “blow-off” if permitted to  
remain on the collecting elements for long periods  
of time. In that the type and amount of dirt varies  
geographically (and from one location to another in  
any given area) it is recommended to start operation  
with a washing frequency of at least once a week,  
for most applications except kitchen exhaust.  
Kitchen exhaust applications should be washed  
daily. Schedules may then be altered as needed  
after visual examinations of the collected material  
contained on the ionizing-collecting cells. Also, daily  
washing is not unusual for units operating on heavy  
welding fume, kitchen exhaust hoods or similar  
applications.  
All actuation components, including remote manual  
pull stations, mechanical or electrical devices,  
detectors, fire-actuated dampers, etc., shall be  
checked for proper operation in accordance with the  
manufacturers listed procedures. In addition to  
these requirements, the specific inspection  
requirements of the applicable NFPA standard shall  
also be followed. If required, certificates of  
inspection and maintenance shall be forwarded to  
the authority having jurisdiction.  
C. Grease removal devices and components – every 4  
to 6 months  
Hoods, impingers, metal mesh filters, ionizing-  
collecting cell(s) fan, ducts and other appurtenances  
shall be cleaned to bare metal at frequent intervals  
prior to surfaces becoming heavily contaminated  
with grease or oily sludge. It may be advantageous  
to clean readily removable items, such as  
impingers, metal mesh filters, ionizing-collecting  
cell(s) or other grease removal devices in a soak  
tank, with a pressure hose or pressure cleaner.  
After cleaning to the bare metal, components shall  
not be coated with powder, oils or other substance.  
B. Detergent  
Effective washing is dependent upon detergent. The  
detergent reservoir should be examined on a  
routine basis; a minimum tank level established and  
never permitted to empty. An empty tank not only  
means poor washing, but can also be detrimental to  
the pump. The inside of the tank should be kept  
clean, free from dirt and foreign objects. The  
detergent as supplied by Trion, Inc., is formulated  
specifically for electronic air cleaners and should not  
be diluted when charging the tank. If substitutes are  
used, they must be approved by Trion, so as to not  
void the warranty and should be safe for use in  
ventilation systems and non-caustic, as 95% of the  
ionizing-collecting cells are constructed of aluminum  
and special high voltage insulation and gasket  
seals.  
When a cleaning service is used, a certificate  
showing date of inspection and/or cleaning should  
be maintained on the premises. Areas not cleaned  
will be noted.  
Flammable solvents or other flammable cleaning  
aids shall not be used.  
At start of cleaning process, electrical switches that  
could be accidentally activated shall be locked out.  
Components of the fire suppression system shall  
C. Electrical Operation  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
not be rendered inoperable during the cleaning  
process.  
Care shall be taken not to apply cleaning chemicals  
on fusible links or other detection devices of the  
automatic extinguishing system.  
When cleaning procedures are completed, all  
electrical switches and system components shall be  
returned to an operable state. All access panels  
and/or doors and cover plates shall be replaced.  
Dampers and diffusers shall be positioned for  
proper airflow.  
D. Water Wash System – every 4 to 6 months  
The water wash spray pattern should be checked  
on each nozzle to ensure that a full spray pattern is  
developed. Distorted patterns are usually caused by  
dirt in the nozzle orifice, which can be cleaned by  
inserting a small gage, soft copper wire into the  
orifice. If any one manifold contains several nozzles  
that are restricted, the drain plug at the idler end of  
the manifold should be removed, after the nozzles  
have been cleaned, and the manifold flushed with  
clean water. The main supply line strainer and the  
strainer in the detergent system should be checked  
and cleaned. Check the wash manifold drive belt  
and linkage connections and replace or tighten as  
required.  
WARNING:  
DO NOT USE HIGH PRESSURE STEAM CLEANING  
EQUIPMENT TO CLEAN CELLS. THE EXCESSIVE  
HEAT AND PRESSURE WILL CAUSE THE PLATES  
TO WARP AND IN TURN POSSIBLY CAUSE  
EXCESSIVE ARCING.  
E. Power Supply(s) and Control every 12 months  
Examine the electrical components located inside  
the control housing for any accumulated dirt or dust.  
If necessary, clean with a good brand of electrical  
contact cleaner.  
F. Blower Bearings - every 4 to 6 months  
Grease the two blower bearings at the grease fitting  
provided with Shell Alvania #2, Texaco Multifac #2  
or Mobilux #2. At this time, examine the blower for  
any accumulated dirt and clean as required.  
G. Motors – every 24 months  
As the operation of detergent pump motor is limited,  
frequent oiling is not required. Lubricate with several  
drops of SAE 10 motor oil every two years. DO NOT  
OVER OIL. The manifold drive, detergent pump and  
blower motors have sealed bearings, are factory  
lubricated for life and require no oiling.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A flickering light with an arcing noise is an indication of  
a high resistance short circuit and a light that is not  
glowing is an indication of a dead short. (A light that is  
not glowing can also be an indication of an open circuit  
in the primary circuit. Refer to the paragraph on open  
circuits.) The short may be in the power supply, the  
high voltage cables or the ionizing-collecting cell(s). To  
isolate the short to any one of these three  
components, proceed as follows:  
SECTION IV TROUBLE SHOOTING  
1. Trouble Shooting  
WARNING:  
EXERCISE THE USUAL PRECAUTIONS WHEN WORKING  
WITH HIGH VOLTAGE. THE MAXIMUM OPERATING  
OUTPUT FROM THE POWER SUPPLY IS 15,000 VDC AND  
5.5 MA. to 11.0 MA. WHEN IN PARALLEL.  
IF SAFETY SWITCHES ARE CLOSED AND CIRCUIT IS  
ENERGIZED, DO NOT TOUCH HIGH VOLTAGE. WHEN  
THE CIRCUIT IS DE-ENERGIZED, ALWAYS BLEED OFF  
REMAINING STATIC CHARGE WITH AN INSULATED  
HANDLED SCREW DRIVER BY SHORTING GROUND  
THE POINTS OF HIGH VOLTAGE DC POTENTIAL.  
WARNING  
When safety interlock switches are closed, do not  
come in contact with high voltage components. The  
operating output from the high voltage power  
supply(s) is 12,500 VDC and 6 MA.  
When the power supply(s) is de-energized there is a  
20 second delay for the voltage to decay. Always  
short from ground to a point of high voltage with a  
Well-insulated jumper wire or an insulated handled  
screwdriver to bleed-off any remaining residual  
charge.  
WARNING  
Risk of Electrical Shock  
The servicing Instructions are for use by qualified  
personnel only. To reduce the risk of electric shock, do  
not perform any servicing other than that contained in  
the service instructions unless you are qualified to do  
so.  
1. Disconnect both high voltage leads from their  
respective terminals in the power supply and support  
them away from any point of contact.  
A. Introduction  
This section on trouble shooting provides a description  
of potential malfunctions, their cause, location and  
correction. A Trouble Reference Chart listing the most  
probable causes and corrections follows the general  
text.  
2. Energize the power supply:  
a. If the light still flickers or does not glow; the trouble  
is indicated to be in the power supply. First, Replace  
the power supply in its entirety.  
NOTE: All repair to the fire suppression system (If  
supplied), must be completed by the authorized fire control  
contractor. For a system supplied with the ATS unit refer to  
Figure 7.  
b. If the light glows steady with the leads disconnected  
the power supply is indicated to be normal.  
3. Next reconnect both high voltage leads to their  
respective terminals inside the power supply and  
disconnect them at the ionizing-collecting cell(s).  
Support them away from any point of contact and  
energize the power supply.  
The electronic air cleaner is the unit within the system  
that has the highest efficiency collection rating and is  
also the one with the highest potential for malfunction.  
When a malfunction does occur, the outage is usually  
found in the electrical secondary circuit in the  
ionizing-collecting cell(s).  
NOTE: It will be necessary to close the access door  
electrical interlock switch operated by the access door  
and affix the junction box lid with hardware supplied to  
close the electrical interlock switch on the box, to  
complete the primary circuit to the power supply.  
Indicating lights are installed in the face panel of the  
control to monitor the electrical operation of each  
power supply and the ionizing-collecting cell(s) they  
energize. The quantity of power supplies per unit is  
dependent upon unit size with one supply to each  
ionizing-collecting cell tier in height. Other than the  
basic hand tools, it is advantageous to have a volt-  
meter with a 20 KVDC high voltage probe. These  
instruments are standard catalog items by several  
manufactures.  
a. If either high voltage lead is defective, the light will  
indicate the trouble. Each lead may then be checked  
separately by disconnecting them, one at a time, from  
their respective terminals at the power supply. When a  
lead is found to be defective, replace it in its entirety. Do  
not repair or splice.  
b. If the light glows steady with the leads disconnected at  
the ionizing-collecting cell(s) the trouble is then indicated  
to be in the ionizing-collecting cell(s).  
B. Secondary Short Circuit  
The most common outage is a short in the secondary  
circuit and is best located through the process of  
elimination. Symptoms are a flickering indicating light  
accompanied by an arcing noise in the  
ionizing-collecting cell(s) or an indicating light that is  
not glowing.  
The trouble can then be isolated to a single cell or  
ionizing or collector section of a given cell as follows:  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(1) First determine if the short is in the ionizing section  
or the collecting section by connecting each high  
voltage lead to its respective section, one at a time,  
and energizing the power pack. (The lead not con-  
nected must be supported away from any point of  
contact.) The short symptoms will still exist for the  
section in which the short is located. If the trouble  
causing the short is bridging both sections, then the  
short will be indicated in both sections when they  
are individually connected.  
(2) When the short is isolated to a cell tier, remove all  
the cells within the tier and visually check the sec-  
tions indicated to contain the short.  
(a). If the short is in the ionizer section look for a  
broken or defective insulator.  
(b). If the short is in the collector section look for a  
large piece of foreign material bridging the  
collector plates or a defective insulator.  
(c). If the short is indicated to be in both sections, it  
will probably be a foreign object bridging the air gap  
between the ionizer and the collector.  
c. Open Circuits  
Although open circuits can occur in the secondary they  
usually take place in the primary. If the unit contains  
only one power supply and the indicating light does not  
glow the outage is probably one of the following. (1)  
Supply line power to the control disconnected.  
Reconnect.  
(2) Open access door interlock in control of electronic  
air cleaner. Be sure all access doors are properly closed  
and secured.  
(3) Outage in the power supply. Look for charred or  
burned components or a loose wiring connection.  
Replace power supply or reconnect wiring.  
(4) Defective indicating light. Replace light.  
d. Malfunctions other than short or open circuits. Refer  
to trouble reference chart in this section.  
8. Spare Parts  
Recommended spare part quantities are usually based  
on the unit size and the amount of units per installation.  
For specific recommendations, consult the Trion factory  
or nearest Sales Office. Consideration, however, should  
be given to stocking the following components;  
DESCRIPTION  
QTY.  
Complete Power Supply  
Power Supply Indicating Light  
Ionizing-Collect Cell Insulator  
Trion Detergent  
1
1
6
55 gal.  
Part Numbers are not listed as they are subject to  
change. Always state Unit Model and Serial Numbers  
when ordering parts.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Reference Chart  
LOCATION  
PROBLEM/  
SYMPTOM  
PROBABLE  
CAUSE  
REASON - CORRECTION  
Ionizing Section of Cell  
Collecting Section of Cell  
1. Dirty insulator(s) – Clean  
2. Defective insulator(s) – Replace  
3. Foreign Object Between Ionizing Bar  
and Ground electrode - Remove  
Indicating Light Not  
Glowing  
Short Circuit  
1. Dirty insulator(s) - Clean  
2. Defective insulator(s) – Replace  
3. Foreign Material Bridging Plates -  
Remove  
4. Bent Plates – Straighten or Replace  
High Voltage Leads  
1. Disconnected High Voltage Lead  
Contacting Ground - Reconnect  
2. Defective Lead/Insulation Breakdown  
– Replace Entire Lead  
Power Supply  
Control  
Charred/Over Heated Components –  
Replace Power Supply  
1. Disconnected Supply Line Power –  
Reconnect  
2. Faulty indicting Light - Replace  
Indicating Light Not  
Glowing  
Open Circuit  
Power Supply  
1. Disconnected Wire – Resolder  
2. Charred/Over Heated Components –  
Replace Power Supply  
Electronic Air Cleaner Housing 1. Electrical Interlock Switch Not Closed  
– Close Access Door  
2. Junction Box interlock switch not  
closed – Secure Cover  
3. Faulty Electrical Interlock Switch -  
Replace  
1. Ionizer High Voltage Lead Connected  
to Plate Section and Plate Lead to  
Ionizer – Reconnect Leads  
Indicating Light  
Flickering  
High Resistance Short High Voltage Circuit  
2. Loose or Disconnect high Voltage  
Lead-Tighten or Reconnect  
3. Loose or Defective Intercell  
Connection (on Multicell Units) –  
Tighten or Replace  
4. Foreign Object Adrift in Ionizer or  
Plate Section of Cell – Remove  
5. Clean cells and replace in unit.  
Loss In Capturing  
Velocity  
1. Metal Mesh Filters Dirty – Clean  
2. Bag Filter Saturated - Replace  
Restriction In Air  
Flow  
Modular Sections  
Loss in Collecting  
Efficiency  
1. Disconnected high Voltage Lead -  
Reconnect  
2. Cell(s) in Multicell Unit Not Connected  
– Repair or Replace Intercell High  
Voltage Connectors  
Disconnected  
Components  
Electronic Air Cleaner  
Loss in Odor Control  
1. Saturated Activated Carbon –  
Replace with New or Refurbished  
Panels  
Decrease In  
Adsorption Ability  
Adsorber Module  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technicolor Thomson MP3 Player PDP2325 User Manual
Topcom Blood Pressure Monitor BPM WRIST 2301B User Manual
Toro Sprinkler 860S User Manual
Toshiba Switch TS Series User Manual
Viper Home Security System VIPER4706V User Manual
Viper Remote Starter VSM200 User Manual
Vision Fitness Elliptical Trainer X6600iNetTV User Manual
Vox DJ Equipment AC15H1TV User Manual
VTech CRT Television VT181CH User Manual
VXI Switch SM8000 User Manual