Trane Impact Driver RT PRC031 EN User Manual

Rooftop Air Handlers  
IntelliPak™ II Air Handlers  
Casing A-C, 16000-45000 CFM—60 Hz  
November 2007  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Controls  
Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable  
RT-PRC031-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and Benefits  
Cabinet  
Mechanical  
Standard Features  
Solid double wall construction  
with foam injected insulation  
Airfoil supply fan—standard  
CFM  
16000-45000 CFM (Casings A, B,  
C) industrial/ commercial  
Rooftop Air Handlers  
Stainless steel flue stack on gas  
heat units  
ASHRAE 90.1 - 2010 Efficiency  
Compliant  
Two-inch spring fan isolation  
standard  
IBC (International Building Code)  
Seismic compliance  
UL and CSA approval on  
standard options  
Controls  
Fully integrated, factory  
installed/commissioned  
microelectronic controls  
Figure 1. Solid Double Wall  
Single point latching, hinged  
access doors on control panel,  
filter, supply and exhaust/return  
fan section as well as gas heat  
section  
Unit mounted Human Interface  
Panel with a 2 line x 40 character  
English display and a 16 function  
keypad that includes Custom,  
Diagnostics, and Service Test  
mode menu keys.  
Figure 3. Spring Isolation  
CV or VAV control  
Daytime Warm-up (Occupied  
mode) on VAV models and  
Morning Warm-up operation on  
all units with heating options  
Two-inch high efficiency  
throwaway filters Optional  
Features  
Freeze Stat coil frost protection  
on chilled water coil  
Supply air static over-  
pressurization protection on  
units with inlet guide vanes and  
VFD's.  
Supply airflow proving  
Figure 2. Latching Access Door  
Exhaust/return airflow proving  
on units with exhaust or return  
fan options  
Flexible downflow and  
horizontal discharge/return  
paths  
Supply air tempering control  
Double sloped galvanized drain  
pans  
Supply air heating control on  
VAV units with heat: modulating  
gas, electric, steam and hot  
water  
Extended casing, cooling only  
models  
Pitched roof  
Emergency stop input  
Heavy-gauge, continuous  
construction base rails  
Mappable sensors and setpoint  
sources  
Meets salt spray testing in  
accordance to ASTM B117  
Standard  
Occupied/Unoccupied switching  
Timed override activation  
4
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Features and Benefits  
1.5, 2.0, 2.5, or 3.0” water  
modulating valve with actuator  
and linkage  
0-100 percent modulating fresh  
air economizer  
Optional Features  
0-25 percent motorized fresh air  
damper  
Controls  
External piping enclosure  
Demand control ventilation  
Low and ultra low leak dampers  
(energy saving CO economizer  
2
Cabinet  
control)  
Filtration  
Blank Section Options  
Twinning of up to four units for  
applications on common supply  
and return ducts  
Four foot blank—cooling only  
Pre-Evaporator Coil Filter  
Options  
Eight foot blank—cooling and  
heating  
Variable frequency drive (VFD)  
control of supply/exhaust/return  
fan motor  
Filter rack only (no filters)  
Single Point access doors on  
both sides of the unit  
Two-inch Throwaway filters  
90-95 percent bag filters  
Belt guards for supply and  
exhaust/return fans  
90-95 percent cartridge filters  
Final filters  
Burglar Bars on select  
configured units  
Bag filters  
Standard and high  
temperature cartridge filters  
Mechanical  
Standard and high  
temperature HEPA filters  
Airfoil plenum return fan—  
standard CFM  
Modulating plenum return fan  
with Statitrac™ direct space  
sensing building pressurization  
control  
Heat Options  
Electric, gas, steam or hot water  
Gas heat options:  
Figure 4. Variable Frequency  
Drive  
Forward curved exhaust fan—  
standard and low CFM  
10:1 Modulating Gas Heat 850  
MBH  
Inlet guide vanes on airfoil  
supply fans (VAV only)  
100 percent modulating exhaust  
20:1 Modulating Gas Heat  
1100 and 1800 MBH  
100 percent modulating exhaust  
with Statitrac™ direct space  
sensing building pressurization  
control  
Choose from three economizer  
control options: comparative  
enthalpy, reference enthalpy, dry  
bulb control  
10 year limited warranty on  
Modulating Gas Heat  
Electrical  
Outside air CFM compensation  
on VAV units with IGV (or VFD)  
and economizer  
LonTalk® Communication  
Interface module  
Unit Withstand Rating of 65000  
Amp (480V) and 25000 Amp  
(600V)  
Generic BAS interfaces—0-5  
VDC, and 0-10 VDC  
The Trane air quality (Traq™)  
fresh air measurement damper  
system  
High efficiency totally enclosed  
fan-cooled supply and exhaust/  
return fan motors  
Remote Human Interface Panel  
(controls up to 4 units)  
Five ventilation override  
sequences  
Standard efficiency supply and  
exhaust/return fan motors  
High duct temperature  
thermostats  
Marine lights in serviceable  
compartments  
Electrical convenience outlet  
Chilled Water Cooling  
Through the door non-fused  
disconnect with external handle  
2 to 8 row 5/8” OD chilled water  
coils  
80, 108, 144, and 168 fin spacing  
options  
Galvanized steel coil casing  
Header drain and vent  
connections  
Figure 5. Traq Damper  
Fully drainable coils  
RT-PRC031-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and Benefits  
Unit mounted and remote  
interface panel key pads are  
identical  
Modular control design  
Field Installed  
Accessories  
UL/CSA approval as standard  
All supply, exhaust, and return  
fans are factory balanced  
Roof curbs  
Single twisted wire pair  
communication for ICS interface  
Wireless zone sensor  
Fully insulated floor, roof, panels,  
and gasketed interfaces reduce  
ambient air infiltration.  
Sturdy, double wall, foam  
injected, hinged access doors  
with height adjustable single  
point latches on main  
Programmable sensors with  
night setback—CV and VAV  
Sensors without night setback—  
CV and VAV  
Fixed-speed supply, exhaust/  
return drives for smooth fan  
operation and belt durability.  
compartments for service ease  
Remote zone sensors—used for  
remote sensing with remote  
panels  
Main control box conveniently  
located on end of air handler for  
layout flexibility in tight spaces  
200000 average life fan bearings  
enhance unit durability.  
ICS zone sensors used with  
Built in optional features like  
high withstand rated breakers,  
belt guards and burglar bars  
contribute to safety  
Gas heater with free-floating  
stainless steel heat exchanger  
relieves the stresses of  
expansion and contraction.  
Stainless steel provides  
corrosion resistance through the  
entire material thickness.  
Tracer™ system for zone control  
Outdoor temperature sensor for  
units without economizers  
Convenience outlet and marine  
lights for enhanced service  
capability  
Remote minimum position  
control for economizer  
Module kits available for field  
upgrade of controls  
Factory-wired and  
commissioned controls assure  
efficient and reliable air handler  
operation.  
Features Summary  
IntelliPak™ II air handler features  
make installation and servicing easy  
and operation extremely reliable.  
Roll-formed construction  
enhances cabinet integrity and  
assures a leak-proof casing.  
Trane industrial quality hot  
water, steam and chilled water  
coils are factory pressure and  
leak tested to ensure  
Installation and Service  
Microprocessor unit controls  
coordinate the operation of the  
air handler with quality, industry-  
accepted components for service  
ease.  
dependability  
Figure 6. Convenience Outlet  
Supply and return piping for the  
chilled water coil are easily  
accessed through the external  
piping enclosure  
Unit mounted lifting lugs  
facilitate installation and can be  
used as unit tie-down points  
Controls are factory installed/  
commissioned for ease of start  
up  
Full unit points access—no field  
wiring of required points  
Modularity of unit control design  
Individual replaceable functional  
boards  
Unit mounted Human Interface  
Panel standard  
Figure 7. Lifting Lugs  
User-friendly keypad edit  
parameters  
Reliability  
Dedicated Human Interface  
access panel  
Advanced diagnostics  
Microprocessor controls  
Built-in safeties  
Start up adjustments  
Advanced diagnostics  
6
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and Benefits  
Application Flexibility  
Chilled water or no cooling  
alternatives  
A variety of chilled water coil  
offerings to meet a diverse range  
of capacity requirements  
Multiple downflow and  
horizontal air path options  
An array of heating options are  
available, including Electric,  
Natural Gas, Steam and Hot  
Water. The Gas Heating option  
provides a choice of two-stage  
gas heat, as well as full  
modulating gas heat. Electric  
heating options provide four to  
six steps of capacity. Hot water  
and steam coils have two steaps  
of capacity.  
IntelliPak™ II Air Handler  
Indoor Air Quality (IAQ)  
Traq Damper System for  
precise fresh air  
measurement  
Demand Control Ventilation  
for CO economizer control  
2
Compensated outdoor air  
control  
Statitrac™ direct space  
building pressure control  
Multiple factory installed  
filter types, pre evaporator  
and final filters  
Humidification control output  
Figure 8. Trane Complete Comfort System  
Comparative enthalpy,  
Reference enthalpy, or Dry  
bulb control for economizers  
Integrated Comfort with Trane  
Tracer™ LCI  
Superior Building Automation  
interface through LonTalk  
The Tracer Integrated Comfort™  
install, commission and service. The  
Tracer Integrated Comfort system  
saves time and money by simplifying  
system design and system  
installation.  
System (ICS) improves job profit and  
increases job control by combining  
Trane rooftop air handler units with  
the Trane Tracer building  
Generic BAS interfaces  
Unit mounted or Remote Human  
Interface panels  
management system. This integrated  
system provides total building  
All parameters are editable  
from the Human Interface  
Panel  
When used with Trane DDC/VAV  
terminals (or VariTrane™), system  
balancing almost goes away because  
each VAV box is commissioned and  
tested before it leaves the factory.  
comfort and control. Some of the  
primary motivations for building  
owners/managers in deciding to  
purchase a HVAC controls system are  
energy savings, cost control, and the  
convenience of facility automation.  
Five factory preset ventilation  
override sequences which can be  
redefined in the field  
All the status information and editing  
data from the air handler units, VAV  
terminals, lighting, exhaust and other  
auxiliary equipment is available from  
Tracer for facility control, monitoring  
and service support. Tracer, a family  
of building automation products  
from Trane, is designed with robust,  
application specific software  
Variable Frequency Drives (VFD)  
included With or Without Bypass  
Control for Supply and Exhaust/  
Return Fans.  
Simplifying the Comfort  
System  
Trane technology and innovation  
brings more capabilities, more  
flexibility, and offers equipment and  
systems that are easy to use, easy to  
CV controls stage heat based on  
space requirements.  
RT-PRC031-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and Benefits  
packages to minimize custom  
electric heat stage status  
Interoperability  
programming requirements and  
enable system setup and control  
through simple editing of parameters  
in the standard applications software.  
ventilation override mode status  
Trane Tracer LonTalk Control  
Interface (LCI) for IntelliPak II offers a  
building automation control system  
with outstanding interoperability  
benefits.  
Tracer control points for  
IntelliPak II Air Handlers  
When selecting an Integrated  
Comfort system for a facility, the  
accountability for equipment,  
automation and controls is Trane's,  
Trane's, and Trane's!  
sensor calibration offsets  
cooling and heating setpoints  
LonTalk, which is an industry  
standard, is an open, secure and  
reliable network communication  
protocol for controls, created by  
Echelon Corporation and adopted by  
the LonMark Interoperability  
zone setpoint offsets for use with  
demand limiting  
In addition to high quality, high  
performance, packaged air handler,  
Trane provides precise air delivery  
management with VariTrane VAV  
terminals.  
VAV discharge air setpoints  
supply air pressure setpoint  
Association. It has been adopted by  
several standards, such as: EIA-709.1,  
the Electronic Industries Alliance  
(EIA) Control Network Protocol  
Specification and ANSI/ASHRAE 135,  
part of the American Society of  
Heating, Refrigeration, and Air  
Conditioning Engineer's BACnet  
control standard for buildings.  
Wireless zone sensors minimize the  
installation costs of the VariTrane  
terminals and the packaged air  
handler system in general.  
The IntelliPak™ II air handler, as a  
part of an Integrated Comfort system,  
provides powerful maintenance  
monitoring, control and reporting  
capabilities. The Tracer places the air  
handler in the appropriate operating  
mode for: system on/off, night  
setback, demand limiting, setpoint  
adjustment based on outside  
Interoperability allows application or  
project engineers to specify the best  
products of a given type, rather than  
one individual supplier's entire  
system. It reduces product training  
and installation costs by  
standardizing communications  
across products. Interoperable  
systems allow building managers to  
monitor and control IntelliPak II  
equipment with a Trane Tracer  
Summit or a 3rd party building  
automation system.  
parameters and much more.  
Figure 9. Tracer™  
Many different unit diagnostic  
conditions can be monitored through  
Tracer: sensor failures and loss of  
supply airflow. Further, the addition  
of Building Management Network  
software offers remote scanning,  
automatic receipt of alarms, and easy  
dial-up access to over 100 various  
Tracer sites across town or across the  
country.  
space pressure setpoint  
zone and outdoor temperature  
values  
It enables integration with many  
different building controls such as  
access/intrusion monitoring, lighting,  
fire and smoke devices, energy  
management, and a wide variety of  
sensors (temperature, pressure,  
cooling and heating enable/  
disable  
economizer enable/disable  
economizer setpoint  
economizer minimum position  
light, humidity, occupancy, CO and  
2
IntelliPak™ II Air Handler  
monitoring points available  
through Tracer  
air velocity). For more information on  
LonMark, visit www.lonmark.org or  
Echelon, www.echelon.com.  
activation of ventilation override  
modes  
diagnostics reset  
all active Air Handler diagnostics  
history of last 20 unit diagnostics  
all system setpoints  
unit priority shutdown  
Optimum Building  
Comfort Control  
IntelliPak II Air Handler setup  
and configuration information  
through Tracer  
The modular control design of the  
UCM allows for greater application  
flexibility. Customers can order  
exactly the options required for the  
job, rather than one large control  
package. Unit features are distributed  
among multiple field replaceable  
printed circuit boards. The Trane  
UCM can be setup to operate under  
one of three control applications:  
system sensor inputs  
supply fan mode and status  
supply fan mode  
inlet guide vane position/VFD  
speed  
configuration of supply air reset  
unit heat/cool mode  
ventilation override mode  
configuration  
exhaust/return fan status  
exhaust/return damper position  
default system setpoint values  
economizer position, minimum  
position setpoint, economizing  
setpoint  
1. standalone  
8
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and Benefits  
2. interface with Trane Tracer™  
building management system  
Statitrac™ Direct Space  
Building Pressurization  
Control  
Statitrac Control with Plenum  
Return Fan is State of the Art!  
3. interface with a generic (non-  
Trane) building management  
system. All setup parameters are  
preset from the factory, requiring  
less start-up time during  
Other manufacturers utilize a fan  
tracking control scheme whereby the  
return fan speed tracks the supply fan  
speed in a linear fashion. This  
scheme works well at minimum and  
maximum CFM airflow. However,  
due to the dissimilar performance  
characteristics of the supply and  
return fan, building pressure is  
difficult to control at points between  
minimum and maximum CFM  
airflow.  
Trane Statitrac™ control is a highly  
accurate and efficient method of  
maintaining building pressure  
control with a large air handler.  
installation.  
Building space pressurization control  
is achieved with a 100 percent  
modulating exhaust system that  
features a single forward curved fan,  
with modulating discharge dampers  
that operates only when needed or a  
100% modulating plenum return fan  
with airfoil wheel that operates  
continuously with the supply fan.  
Most of the operating hours of the  
100 percent modulating exhaust  
system are at part load, resulting in  
energy savings.  
The unit mounted Human Interface  
and the Remote Human Interface  
Panels' functions are identical, with  
the exception of the Service mode  
which is not available on the Remote  
Human Interface Panel. This common  
interface feature requires less time  
for building maintenance personnel  
to learn to interact with the unit.  
The Trane return fan/building  
pressurization control system  
eliminates the effects of dissimilar  
supply/return fan characteristics  
experienced in a linear tracking  
control system by modulating the  
exhaust dampers based on space  
pressure, the return/economizer  
dampers based on ventilation  
requirements, and the return fan  
speed based on return plenum static  
pressure. The supply fan, return fan,  
exhaust damper, and return/  
economizer damper systems act  
independently from one another to  
maintain comfort and building  
pressure.  
All air handler control parameters are  
adjustable and can be setup through  
the Remote Human Interface Panel  
such as, but not limited to: system  
on/off, demand limiting type, night  
setback setpoints, and many other  
setpoints. No potentiometers are  
required for setpoint adjustment, all  
adjustments are done through the  
Remote Human Interface keypad.  
Statitrac, with the 100 percent  
modulating exhaust system,  
provides comfort and economy for  
buildings with large air handler  
systems. Statitrac, with the 100%  
modulating plenum return fan  
provides comfort and space pressure  
control in more demanding  
Up to 56 different air handler  
diagnostic points can be monitored  
through the human interfaces such  
as: sensor failures and loss of supply  
airflow. No special tools are required  
for servicing the unit. All diagnostic  
displays are available in clear English  
at the Remote Human Interface and  
will be held in memory, so that the  
operator/service person can  
applications with high return static  
pressure, and applications requiring  
duct returns.  
The return fan operates whenever  
the supply fan is in operation. The  
unit exhaust dampers are modulated  
in response to the space pressure  
signal to maintain space pressure  
within the space pressure deadband.  
The unit economizer and return air  
dampers are modulated based on  
ventilation control, minimum outside  
air economizer position, and  
economizer cooling request. The  
return fan speed is modulated based  
on a return duct static pressure  
deadband control. Using the unit  
mounted Human Interface Panel you  
can:  
Statitrac control with exhaust fan is  
simple! The space pressure control  
turns the exhaust fans on and off as  
required and modulates exhaust  
dampers, or VFD speed, to maintain  
space pressure within the space  
pressure deadband. Economizer and  
return air dampers are modulated  
based on ventilation control and  
economizer cooling request.  
diagnose the root cause of failures.  
The unit mounted Human Interface  
Panel can be used to:  
1. adjust space pressure setpoint  
2. adjust space pressure deadband  
1. adjust space pressure setpoint  
2. adjust space pressure deadband  
3. measure and read building static  
pressure  
The modulating exhaust system  
maintains the desired building  
pressure, while saving energy and  
keeping the building at the right  
pressure. Proper building  
3. measure and read building space  
pressure  
4. measure and read return duct  
static pressure.  
Figure 10. Statitrac  
pressurization eliminates annoying  
door whistling, doors standing open,  
and odors from other zones. The  
Statitrac™ direct space building  
control sequence will also be  
maintained when a variable  
Proper building pressurization  
eliminates annoying door whistling,  
doors standing open, and odors from  
other zones.  
frequency drive is used.  
RT-PRC031-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and Benefits  
Supply Fans with Inlet Guide  
Vanes  
Trane airfoil fans with inlet guide  
vanes pre-rotate the air in the  
direction of the fan wheel, decreasing  
static pressure and horsepower,  
essentially unloading the fan wheel.  
The unloading characteristics result  
in superior part load performance.  
Variable Frequency Drives  
(VFD)  
Variable Frequency Drives are factory  
installed and tested to provide  
supply/exhaust/return fan motor  
speed modulation. VFD's, as  
compared to inlet guide vanes or  
discharge dampers, are quieter, more  
efficient, and may be eligible for  
utility rebates. The VFD's are  
available with or without a bypass  
option. Bypass control will simply  
provide full nominal airflow in the  
event of drive failure.  
10  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
Variable Air Volume (VAV) Only  
Bypass control is offered to provide  
full nominal airflow in the event of  
drive failure.  
Supply Air Static Pressure  
Limit  
The opening of VAV terminals, and  
the amount of supply air provided by  
the inlet guide vanes, or variable  
frequency drive are coordinated  
during start up and transition to/from  
Occupied/Unoccupied modes to  
prevent over pressurization of the  
supply air ductwork.  
However, if for any reason the  
supply air pressure exceeds the user-  
defined supply air static pressure  
limit that was set at the Human  
Interface Panel, the supply fan/VFD is  
shut down and the inlet guide vanes  
(if included) are closed.  
Figure 11. IntelliPak™ II Control Panel  
When in any position other than full  
VAV Units Only  
Note: When noted in this sequence  
“Human Interface Panel,” the  
reference is to both the unit  
mounted and remote  
open, the vanes pre-spin intake air in  
the same direction as supply fan  
rotation. As the vanes approach the  
full-closed position, the amount of  
“spin” induced by the vanes  
The unit is then allowed to restart  
three times. If the over pressurization  
condition occurs on the third time,  
the unit is shut down and a manual  
reset diagnostic is set and displayed  
at the Human Interface Panel and  
BAS/Network.  
increases at the same time that  
intake airflow and fan horsepower  
diminish. The inlet guide vanes will  
close when the supply fan is shut  
down, except during night setback.  
mounted Human Interface  
Panel. All setpoint  
adjustments can be  
accomplished at the unit or  
Remote Human Interface  
Panel.  
Supply Air Temperature  
Controls  
Variable Frequency Drive  
(VFD) Control  
Supply Air Pressure  
Control  
Cooling/Economizer  
Variable frequency drives are driven  
by a modulating 0-10 vdc signal from  
the Rooftop Module (RTM). A  
pressure transducer measures duct  
static pressure, and the VFD is  
modulated to maintain the supply air  
static pressure within an adjustable  
user-defined range.  
During Occupied cooling mode of  
operation, the economizer (if  
available) and cooling are used to  
control the supply air temperature.  
The supply air temperature setpoint  
and deadband are user-defined at  
the Human Interface Panel.  
Inlet Guide Vanes Control  
Inlet guide vanes are driven by a  
modulating 0-10 vdc signal from the  
Rooftop Module (RTM). A pressure  
transducer measures duct static  
pressure, and the inlet guide vanes  
are modulated to maintain the  
supply air static pressure within an  
adjustable user-defined range.  
The supply air temperature setpoint  
may be user-defined from the BAS/  
Network. If the conditions of the  
outside air is appropriate to use  
“free cooling,” the economizer will  
be used first to attempt to satisfy the  
supply air setpoint; then if required  
the hydronic valve will be modulated  
to maintain supply air temperature  
setpoint.  
The range is determined by the  
supply air pressure setpoint and  
supply air pressure deadband, which  
are set through the Human Interface  
Panel or BAS/Network.  
The range is determined by the  
supply air pressure setpoint and  
supply air pressure deadband, which  
are set through the Human Interface  
Panel or BAS/Network.  
Variable frequency drives provide  
supply fan motor speed modulation.  
The drive will accelerate or  
decelerate as required to maintain  
the supply static pressure setpoint.  
When subjected to high ambient  
return conditions the VFD will reduce  
its output frequency to maintain  
operation.  
Inlet guide vane assemblies installed  
on the supply fan inlets regulate fan  
capacity and limit horsepower at  
lower system air requirements.  
On units with economizer, a call for  
cooling will modulate the fresh air  
dampers open. The rate of  
economizer modulation is based on  
deviation of the supply air  
RT-PRC031-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls Variable Air Volume (VAV) Only  
temperature from setpoint, i.e., the  
further away from setpoint, the faster  
the fresh air damper will open.  
Supply Air  
Temperature  
Note: The economizer is only  
allowed to function freely if  
one of the following  
Supply Air  
Temperature  
Setpoint  
conditions is met. For dry  
bulb economizer control the  
ambient temperature must be  
below the dry bulb  
temperature control setting.  
For reference enthalpy  
Amount of  
Temperature  
Reset  
Cooling  
Reset  
Heating  
Reset  
economizer control, outdoor  
air enthalpy must be below  
the enthalpy control setting.  
For comparative enthalpy  
economizer control, outdoor  
air enthalpy must be below  
the enthalpy of the return air.  
Outdoor Air  
or  
Zone  
Temperature  
Ending (Cooling)  
Beginning (Heating)  
Reset Temperature  
Beginning (Cooling)  
Ending (Heating)  
Reset Temperature  
The outdoor air dampers may be set  
for a maximum of 25 percent outdoor  
air, through the unit mounted Human  
Interface Panel or a signal from the  
BAS/network, if the air handler is  
equipped with 0 to 25 percent  
Figure 12. Supply Air Temperature Reset  
supervision. If combustion should  
become unstable for any reason,  
Supply Air Setpoint Reset  
Supply air setpoint reset can be used  
to adjust the supply air temperature  
setpoint on the basis of a zone  
temperature or on outdoor air  
temperature. Supply air setpoint  
reset adjustment is available from  
the Human Interface Panel for supply  
air heating and supply air cooling  
control.  
motorized fresh air dampers.  
heating will automatically shut down  
and be locked out until reset at the  
unit mounted Human Interface panel.  
A temperature sensor, located on the  
entering air side of the chilled water  
coil, will send a signal to the hydronic  
valve to drive it full open when a  
potential freeze condition is detected.  
The supply fan is then turned off and  
the fresh air damper is closed.  
As the heating requirement is  
satisfied, the HEAT module will  
modulate the combustion air damper  
closed and the firing rate will lower  
to maintain the desired outlet  
Outdoor air cooling reset is  
temperature. When the requirement  
is fully satisfied, the heating contacts  
are opened, de-energizing the heat.  
The specific sequence of operation of  
the gas heat will depend on the size  
of the heat exchanger.  
Heating  
sometimes used in applications  
where the outdoor temperature has a  
large effect on building load. When  
the outside air temperature is low  
and the building cooling load is low,  
the supply air setpoint can be raised,  
thereby preventing subcooling of  
critical zones. This reset can lower  
usage of primary cooling, thus  
savings in mechanical cooling kw,  
but an increase in supply fan kw may  
occur.  
Modulating Gas  
Upon a call for heating, the HEAT  
module closes the heating contacts,  
beginning the firing sequence. First,  
the heat exchanger combustion  
blower begins operation. Upon  
positive proving of combustion  
airflow, a 60 second pre-purge cycle  
is executed. Then the ignition  
sequence takes place.  
Electric Heating  
The individual stages of electric heat  
will be sequenced on the zone  
demand. The number of available  
stages will depend on the unit size  
and heat capacity selected.  
Outdoor air heating reset is the  
inverse of cooling, with the same  
principles applied.  
If ignition is not proven, the safety  
control locks out and must be  
manually reset. As long as there is a  
call for heat, the safety control can be  
reset, which starts another purge  
cycle and try for ignition.  
Hot Water or Steam  
On units with hot water or steam  
heating, the supply air temperature  
can be controlled to a heating  
For both outdoor air cooling reset  
and heating reset, there are three  
user-defined parameters that are  
adjustable through the Human  
Interface Panel.  
setpoint during the Occupied mode.  
The supply air temperature heating  
setpoint and deadband are user-  
defined at the Human Interface Panel.  
VAV Occupied heating on hot water  
and steam heat units is enabled by  
closing a field-supplied switch or  
contacts connected to an changeover  
input on the RTM.  
Once ignited, as additional heat is  
required, the combustion air damper  
opens, increasing the firing rate.  
beginning reset temperature  
ending reset temperature  
amount of temperature reset  
During heating operation, an  
electronic flame safety control  
provides continuous flame  
Zone reset is applied to the zone(s) in  
a building that tend to over cool or  
12  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls Variable Air Volume (VAV) Only  
overheat. The supply air temperature  
setpoint is adjusted based on the  
temperature of the critical zone(s).  
This can have the effect of improving  
comfort and/or lowering energy  
usage. The user-defined parameters  
are the same as for outdoor air reset.  
See Figure 12, p. 12  
a. An optional temperature  
sensor may be connected to  
the ventilation control  
module to enable it to control  
a field-installed pre-heater.  
b. An optional CO sensor may  
2
be connected to the  
ventilation control module to  
control fresh air based on  
Supply Air Tempering  
CO Demand Control  
2
Ventilation (DCV).  
Modulating gas, electric, hot water  
and steam heat units only—When  
supply air temperature falls below  
the supply air temperature deadband  
low end, the heat valve will be  
modulated to maintain the set  
minimum supply air temperature.  
Outside Air CFM  
Compensation  
As the supply fan (IGV or VFD)  
modulates, this function  
proportionally adjusts the  
economizer minimum position to  
compensate for the change in total  
airflow, in order to maintain a  
constant percent of outside air. The  
modified economizer minimum  
position is computed as a linear  
function, based on IGV or VFD  
position, given the two endpoints,  
Zone Temperature  
Control  
Unoccupied Zone Heating and  
Cooling  
During Unoccupied mode, the unit is  
operated as a CV unit. Inlet guide  
vanes are driven full open, VFDs  
operate at 100%, and VAV boxes are  
driven full open. The unit controls  
zone temperature within the  
Unoccupied zone cooling and  
heating (heating units only)  
setpoints.  
a. Minimum Position with IGV/  
VFD @ 0%  
b. Minimum Position with IGV/  
VFD @ 100%  
which are user adjustable at the  
Human Interface Panel.  
Daytime warm-up  
This feature is available on all types  
of heating units. During Occupied  
mode, if the zone temperature falls to  
a preset, user-defined zone low limit  
temperature setpoint, the unit is put  
into Unoccupied mode and Daytime  
Warm-up is initiated. The system  
changes over to CV heating (full unit  
airflow), the VAV boxes are fully  
opened and full heating capacity is  
provided until the Daytime Warm-up  
setpoint is reached. The unit is then  
returned to normal Occupied mode.  
Fresh Air Measurement  
Trane air quality (TRAQ™) fresh air  
measurement damper system utilizes  
velocity pressure sensing rings.  
Based on unit design CFM, the  
ventilation control module (VCM)  
monitors and controls the quantity of  
fresh outside air entering the unit.  
The outside airflow can be calibrated  
to accommodate for altitude.  
RT-PRC031-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls Constant Volume (CV) Only  
air enthalpy must be below  
the enthalpy of the return air.  
On all other heat sizes the heating  
section will be shutdown and locked  
out until manually reset at the  
ignition module and unit mounted  
Human Inferface Panel after the first  
shutdown due to flame instability.  
CV Units Only  
If the unit does not include an  
economizer, primary cooling only is  
used to satisfy cooling requirements.  
Occupied Zone  
Temperature Control  
The outdoor air dampers may be set  
for a maximum of 25 percent  
As the heating requirement is  
satisfied, the HEAT module will open  
the second stage heating relay, de-  
energizing the second stage of heat.  
When the requirement is fully  
satisfied, the first stage contacts are  
opened, de-energizing the first stage  
of heat.  
Cooling/Economizer  
outdoor air, through the unit  
During Occupied cooling mode, the  
economizer (if provided) and  
mechanical cooling are used to  
control zone temperature. The zone  
temperature cooling setpoint is user-  
defined at the Human Interface Panel  
or from the BAS/Network.  
mounted Human Interface Panel or a  
signal from the BAS/network, if the  
air handler is equipped with 0 to 25  
percent motorized fresh air dampers.  
A temperature sensor, located on the  
entering air side of the chilled water  
coil, will send a signal to the  
hydronic valve to drive it full open  
when a potential freeze condition is  
detected. The supply fan is then  
turned off and the outside air  
damper is closed.  
Gas Heating: Modulating Gas  
If the conditions of outside air is  
appropriate to use “free cooling, the  
economizer will be used first to  
attempt to satisfy the cooling zone  
temperature setpoint; then if  
required the hydronic valve will be  
modulated to maintain supply air  
temperature setpoint.  
Upon a call for heating, the HEAT  
module closes the heating contacts,  
beginning the firing sequence. First,  
the heat exchanger combustion  
blower begins operation. Upon  
positive proving of combustion  
airflow, a pre-purge cycle is  
Heating  
executed. Then the ignition  
sequence takes place.  
On units with economizer, a call for  
cooling will modulate the fresh air  
dampers open. The rate of  
economizer modulation is based on  
deviation of the zone temperature  
from setpoint, i.e., the further away  
from setpoint, the faster the fresh air  
damper will open.  
Gas Heating: Two-Stage  
Upon a call for heating, the HEAT  
module closes the first stage heating  
contacts beginning the firing  
sequence. First, the heat exchanger  
combustion blower begins  
operation. Upon positive proving of  
combustion airflow, a 60 second pre-  
purge cycle is executed. Then the  
ignition sequence takes place.  
If ignition is not proven, the safety  
control locks out and must be  
manually reset. As long as there is a  
call for heat, the safety control can  
be reset, which starts another purge  
cycle and try for ignition.  
Once ignited, as additional heat is  
required, the combustion air damper  
opens, increasing the firing rate.  
First stage of cooling will be allowed  
to start after the economizer reaches  
full open.  
If ignition is not proven, the safety  
control locks out and must be  
manually reset. As long as there is a  
call for heat, the safety control can  
be reset, which starts another purge  
cycle and try for ignition.  
During heating operation, an  
electronic flame safety control  
provides continuous flame  
supervision. If combustion should  
become unstable for any reason,  
heating will automatically shut down  
and be blocked out until reset at the  
unit mounted Human Interface  
panel.  
Note: The economizer is only  
allowed to function freely if  
one of the following  
conditions is met: For dry  
bulb economizer control, the  
ambient temperature must  
be below the dry bulb  
temperature control setting.  
For reference enthalpy  
As additional heat is required, the  
HEAT module will close the second  
stage heating contacts and  
depending on heat module size, will  
open either the second stage of the  
gas valve, or a second stage gas  
valve.  
As the heating requirement is  
satisfied, the HEAT module will  
modulate the combustion air  
damper closed, and the firing rate  
will lower to maintain the desired  
outlet temperature. When the  
requirement is fully satisfied, the  
heating contacts are opened, de-  
energizing the heat. The specific  
sequence of operation of the gas  
heat will depend on the size of the  
heat exchanger.  
economizer control, outdoor  
air enthalpy must be below  
the enthalpy control setting.  
At outdoor air conditions  
above the enthalpy control  
setting, mechanical cooling  
only is used and the outdoor  
air dampers remain at  
During heating operation, an  
electronic flame safety control  
provides continuous flame  
supervision. If combustion should  
become unstable for any reason,  
heating will automatically shut  
down. On the low heat and medium  
heat for all units, after a one minute  
delay, plus another 60 second pre-  
purge cycle the ignition cycle begins.  
minimum position. For  
comparative enthalpy  
economizer control, outdoor  
14  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls Constant Volume (CV) Only  
Auto Changeover  
When the System Mode is Auto,” the  
mode will change to cooling or  
heating as necessary to satisfy the  
zone cooling and heating setpoints.  
The zone cooling and heating  
setpoints can be as close as 2°F  
apart.  
Electric Heating  
The individual stages of electric heat  
will be sequenced on the zone  
demand. The number of available  
stages will depend on the unit size  
and heat capacity selected.  
Hot Water or Steam Heating  
Upon a call for heat, the UCM will  
send a varying voltage signal to the  
valve actuator. The valve will  
Unoccupied Zone  
Temperature Control  
modulate to meet building demand  
as indicated by the voltage signal.  
When heating is satisfied, the valve  
will modulate closed. A temperature  
sensor is located on the coldest  
section of the coil. When it senses an  
impending freeze condition, a signal  
is sent to the hydronic valve to drive  
it full open. If the supply fan is on, or  
if the outside air damper is open  
when this freezing condition is  
Cooling and Heating  
Cooling and/or heating modes can be  
selected to maintain Unoccupied  
zone temperature setpoints. For  
Unoccupied periods, heating,  
economizer operation or primary  
cooling operation can be selectively  
locked out at the Human Interface  
Panels.  
sensed, the supply fan is turned off  
and the fresh air damper is closed.  
Supply Air Tempering  
For staged gas and electric heat units  
in the occupied Heating mode but  
not actively heating, if the supply air  
temperature drops to 10°F below the  
Occupied zone heating temperature  
setpoint, one stage of heat will be  
brought on to maintain a minimum  
supply air temperature. The heat  
stage is turned off if the supply air  
temperature rises to 10°F above the  
Occupied zone heating temperature  
setpoint.  
On units with hot water or steam  
heating, if the supply air temperature  
drops below 48°F, the heating valve  
is modulated to maintain 50°F supply  
air temperature with a 4°F deadband.  
RT-PRC031-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls VAV and CV  
MWU zone temperature setpoint.  
This method of warm-up is used to  
overcome the “building sink” effect.  
Cycling capacity MWU will operate  
until the MWU setpoint is reached or  
for 60 minutes, then the unit  
VOM Relay - Energized (if so  
equipped)  
Common to VAV and  
CV Units  
Preheat Output - Off  
Return Fan - Off; Exhaust  
Dampers - Closed (if so  
equipped)  
Space Pressure Control -  
Statitrac™  
A pressure transducer is used to  
measure and report direct space  
(building) static pressure. The user-  
defined control parameters used in  
this control scheme are space static  
pressure setpoint, space pressure  
deadband and exhaust enable point.  
switches to Occupied mode.  
Return VFD - Min (if so  
equipped)  
A control algorithm is used to  
increase or decrease the amount of  
heat in order to achieve the MWU  
zone temperature setpoint.  
2. EMERG_DEPRESSURIZE:  
Supply Fan - Off  
Note: When using the Morning  
Warm-up option in a VAV  
heating/cooling air handler,  
airflow must be maintained  
through the air handler unit.  
This can be accomplished by  
electrically tying the VAV  
boxes to the VAV box output  
relay contacts on the Rooftop  
Module (RTM) or by using  
changeover thermostats.  
Either of these methods will  
assure adequate airflow  
through the unit and  
Supply Fan IGV / Supply Fan  
VFD - Closed/Min (if so  
equipped)  
As the economizer opens, the  
building pressure rises and once  
above the exhaust enable point,  
enables the exhaust fan and  
dampers or exhaust VFD. The  
exhaust dampers or VFD then  
modulate to maintain space pressure  
within the deadband.  
Exhaust Fan - On; Exhaust  
Dampers Open/Max (if so  
equipped)  
OA Dampers - Closed; Return  
Damper - Open  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
Occupied/Unoccupied/VAV  
box output - Energized  
Morning Warm-up Options  
This feature may be enabled on all  
types of factory installed heat units  
as well as cooling only units  
configured as “External Heat” (for  
example, VAV boxes with reheat).  
satisfactory heating of the  
building.  
VOM Relay - Energized (if so  
equipped)  
Preheat Output - Off  
Emergency Override  
Return Fan - On; Exhaust  
Dampers - Open (if so  
equipped)  
When a LonTalk communication  
module is installed, the user can  
initiate from the Trane Tracer  
Summit or 3rd party BAS one of five  
(5) predefined, not available to  
configure, Emergency Override  
sequences. The Humidification  
output is deenergized for any  
Emergency Override sequence. Each  
Emergency Override sequence  
commands the unit operation as  
follows:  
At the conclusion of Unoccupied  
mode, while the economizer (if  
supplied) is kept closed, the selected  
zone is heated to the user-defined  
Morning Warm-up setpoint. The unit  
is then released to Occupied mode.  
There are two types of Morning  
Warm-up: full capacity or cycling  
capacity.  
Return VFD - Max (if so  
equipped)  
3. EMERG_PURGE:  
Supply Fan - On  
Supply Fan IGV / Supply Fan  
VFD - Open/Max (if so  
equipped)  
Full Capacity Morning Warm-up  
(MWU)  
Exhaust Fan - On; Exhaust  
Dampers Open (if so  
equipped)  
1. PRESSURIZE_EMERG:  
Full capacity Morning Warm-up uses  
full heating capacity, and heats the  
zone up as quickly as possible. Full  
heating capacity is provided until the  
Morning Warm-up setpoint is met.  
At this point, the unit is released to  
occupied mode.  
Supply Fan - On  
OA Dampers - Open; Return  
Damper - Closed  
Supply Fan IGV / Supply Fan  
VFD Open/Max (if so  
equipped)  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
Exhaust Fan - Off; Exhaust  
Dampers Closed (if so  
equipped)  
Occupied/Unoccupied/VAV  
box output - Energized  
Cycling Capacity Morning Warm-  
up (MWU)  
OA Dampers - Open; Return  
Damper - Closed  
VOM Relay - Energized (if so  
equipped)  
Cycling capacity Morning Warm-up  
provides a more gradual heating of  
the zone. Normal zone temperature  
control with varying capacity is used  
to raise the zone temperature to the  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
Preheat Output - Off  
Return Fan - On; Exhaust  
Dampers - Open (if so  
equipped)  
Occupied/Unoccupied/VAV  
box output - Energized  
16  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls VAV and CV  
Return VFD - Max (if so  
equipped)  
sequence is being requested, the  
sequence with the highest priority is  
initiated first. Sequence hierarchy is  
the sequence A” (UNIT OFF) is first,  
with sequence “E” (PURGE with Duct  
Pressure Control) last.  
Occupied/Unoccupied/VAV  
box output - Energized  
VOM Relay - Energized  
Preheat Output - Off  
4. EMERG_SHUTDOWN:  
Supply Fan - Off  
Return Fan - Off; Exhaust  
Dampers - Closed (if so  
equipped)  
Supply Fan IGV / Supply Fan  
VFD - Closed/Min (if so  
equipped)  
The factory default definitions for  
each mode are as follows:  
Return VFD - Min (if so  
equipped)  
Exhaust Fan - Off; Exhaust  
Dampers Closed (if so  
equipped)  
1. UNIT OFF sequence A”  
When complete system shutdown is  
required the following sequence can  
be used.  
OA Bypass Dampers - Open  
(if so equipped)  
OA Dampers - Closed; Return  
Damper - Open  
Exhaust Bypass Dampers -  
Open (if so equipped)  
Supply Fan - Off  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
Supply Fan IGV / Supply Fan  
VFD - Closed/Min (if so  
equipped)  
3. EXHAUST sequence “C”  
Occupied/Unoccupied/VAV  
box output - Energized  
With only the exhaust fans running  
(supply fan off), the space that is  
conditioned by the air handler would  
become negatively pressurized. This  
is desirable for clearing the area of  
smoke from the now-extinguished  
fire, possibly keeping smoke out of  
areas that were not damaged.  
Exhaust Fan - Off; Exhaust  
Dampers Closed (if so  
equipped)  
VOM Relay - Energized (if so  
equipped)  
Preheat Output - Off  
OA Dampers - Closed; Return  
Damper - Open  
Return Fan - Off; Exhaust  
Dampers - Closed (if so  
equipped)  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
Supply Fan - Off  
Return VFD - Min (if so  
equipped)  
Occupied/Unoccupied/VAV  
box output - Deenergized  
Supply Fan IGV / Supply Fan  
VFD - Closed/Min (if so  
equipped)  
5. EMERG_FIRE - Input from fire  
pull box/system:  
VOM Relay - Energized  
Preheat Output - Off  
Exhaust Fan - On; Exhaust  
Dampers Open (if so  
equipped)  
Supply Fan - Off  
Return Fan - Off; Exhaust  
Dampers - Closed (if so  
equipped)  
Supply Fan IGV / Supply Fan  
VFD - Closed/Min (if so  
equipped)  
OA Dampers - Closed; Return  
Damper - Open  
Return VFD - Min (if so  
equipped)  
Exhaust Fan - Off; Exhaust  
Dampers Closed (if so  
equipped)  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
OA Bypass Dampers - Open  
(if so equipped)  
Occupied/Unoccupied/VAV  
box output - Deenergized  
OA Dampers - Closed; Return  
Damper - Open  
Exhaust Bypass Dampers -  
Open (if so equipped)  
VOM Relay - Energized  
Preheat Output - Off  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
2. PRESSURIZE sequence “B”  
Return Fan - On; Exhaust  
Dampers - Open (if so  
equipped)  
Perhaps a positively pressurized  
space is desired instead of a  
negatively pressurized space. In this  
case, the supply fan should be turned  
on with inlet guide vanes open/VFD  
at 100% speed and exhaust fan  
should be turned off.  
Occupied/Unoccupied/VAV  
box output - Energized  
VOM Relay - Energized (if so  
equipped)  
Return VFD - Max (if so  
equipped)  
Preheat Output - Off  
OA Bypass Dampers - Open  
(if so equipped)  
Return Fan - Off; Exhaust  
Dampers - Closed (if so  
equipped)  
Supply Fan - On  
Exhaust Bypass Dampers -  
Open (if so equipped)  
Supply Fan IGV / Supply Fan  
VFD - Max (if so equipped)  
Return VFD - Min (if so  
equipped)  
4. PURGE sequence “D”  
Exhaust Fan - Off; Exhaust  
Dampers Closed (if so  
equipped)  
Possibly this sequence could be used  
for purging the air out of a building  
before coming out of Unoccupied  
mode of operation on VAV units or  
for the purging of smoke or stale air  
if required after a fire.  
Ventilation Override Module  
(VOM)  
OA Dampers - Open; Return  
Damper - Closed  
The user can customize up to five (5)  
different override sequences for  
purposes of ventilation override  
control. If more than one VOM  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
Supply Fan - On  
RT-PRC031-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls VAV and CV  
Supply Fan IGV/ Supply Fan  
VFD - Max (if so equipped)  
SETUP - Control parameters,  
sensor source selections,  
function enable/disable, output  
definitions, and numerous other  
points can be edited in this  
menu. All points have factory  
preset values so unnecessary  
editing is kept to a minimum.  
Exhaust Fan - On; Exhaust  
Dampers Open (if so  
equipped)  
OA Dampers - Open; Return  
Damper - Closed  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
CONFIGURATION - Preset with  
the proper configuration for the  
unit as it ships from the factory,  
this information would be edited  
only if certain features were  
physically added or deleted from  
the unit. For example, if a field  
supplied Ventilation Override  
Module was added to the unit in  
the field, the unit configuration  
would need to be edited to  
Occupied/Unoccupied/VAV  
box output - Energized  
Figure 13. Human Interface  
Panel (HI)  
VOM Relay - Energized  
Preheat Output - Off  
Human Interface Panel (HI)  
Return Fan - On; Exhaust  
Dampers - Open (if so  
equipped)  
The Human Interface (HI) Panel  
provides a 2 line X 40 character clear  
English liquid crystal display and a 16  
button keypad for monitoring,  
setting, editing and controlling. The  
Human Interface Panel is mounted in  
the unit's main control panel and is  
accessible through an independent  
Return VFD - Max (if so  
equipped)  
reflect that feature.  
SERVICE - used to selectively  
control outputs (for fans, damper  
position, etc.) for servicing or  
troubleshooting the unit. This  
menu is accessible only at the  
unit mounted Human Interface  
Panel.  
OA Bypass Dampers - Open  
(if so equipped)  
Exhaust Bypass Dampers -  
Open (if so equipped)  
The optional remote mount version  
of the Human Interface (RHI) Panel  
has all the functions of the unit  
mount version except Service Mode.  
To use a RHI the unit must be  
5. PURGE with duct pressure  
control sequence “E”  
This sequence can be used when  
supply air control is required for  
smoke control.  
Generic Building Automation  
System Module (GBAS 0-5  
vdc)  
equipped with an optional Inter-  
Processor Communications Bridge  
(IPCB) module. The RHI can be  
located up to 1000 feet from the unit.  
A single RHI can be used to monitor  
and control up to four (4) air  
Supply Fan - On  
The Generic Building Automation  
System Module (GBAS 0-5vdc) is  
used to provide broad control  
capabilities for building automation  
systems other than Trane's Tracer™  
system. The following inputs and  
outputs are provided:  
Supply Fan IGV / Supply Fan  
VFD - (If so equipped)  
Controlled by Supply Air  
Pressure Control function;  
Supply Air Pressure High  
Limit disabled  
handlers, each containing an IPCB.  
Human Interface Panel Main  
Menu  
Exhaust Fan - On; Exhaust  
Dampers Open (if so  
equipped)  
Analog Inputs - Four analog inputs,  
controlled via a field provided  
potentiometer or a 0-5 vdc signal,  
that can be configured to be any of  
the following:  
STATUS - used to monitor all  
temperatures, pressures,  
humidities, setpoints, input and  
output status.  
OA Dampers - Open; Return  
Damper - Closed  
CUSTOM - allows the user to  
create a custom status menu  
consisting of up to four (4)  
screens of the data available in  
the Status menu.  
Heat - All heat stages off;  
Mod Heat output at 0 vdc  
1. Occupied Zone Cooling Setpoint  
(CV only)  
Occupied/Unoccupied/VAV  
box output - Energized  
2. Unoccupied Zone Cooling  
Setpoint (CV only)  
VOM Relay - Energized  
Preheat Output - Off  
3. Occupied Zone Heating Setpoint  
(CV only)  
SETPOINTS - used to review and/  
or modify all the factory preset  
Default setpoints and setpoint  
source selections.  
Return Fan - On; Exhaust  
Dampers - Open (if so  
equipped)  
4. Unoccupied Zone Heating  
Setpoint (CV only)  
DIAGNOSTICS - used to review  
active and historical lists of  
diagnostic conditions. Over one  
hundred different diagnostics  
can be read at the Human  
Interface Panel. The last 20  
unique diagnostics can be held  
in an active history buffer log.  
5. Supply Air Cooling Setpoint (VAV  
only)  
Return VFD - Max (if so  
equipped)  
6. Supply Air Heating Setpoint (VAV  
only)  
OA Bypass Dampers - Open  
(if so equipped)  
7. Space Static Pressure Setpoint  
Exhaust Bypass Dampers -  
Open (if so equipped)  
18  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Controls VAV and CV  
8. Supply Air Static Pressure  
Setpoint  
7. Space Static Pressure Setpoint  
thermostat will trip, the hydronic  
valve will be fully opened, the supply  
fan will shut off, and the fresh air  
dampers will close.  
8. Supply Air Static Pressure  
Setpoint  
9. Minimum Outside Air Flow  
Setpoint  
9. Minimum Outside Air Flow  
Setpoint  
10. Morning Warm Up Setpoint  
Steam and Hot Water Coil -  
Freeze Avoidance  
11. Economizer Dry Bulb Enable  
Setpoint  
10. Morning Warm Up Setpoint  
11. Economizer Dry Bulb Enable  
Setpoint  
Freeze Avoidance is a feature which  
helps prevent freezing of steam or  
hot water heat coils during periods of  
unit inactivity and low ambient  
temperatures. Whenever the unit  
supply fan is off, the outdoor air  
temperature is monitored. If the  
temperature falls below a  
12. Supply Air Reheat Setpoint  
13. Minimum Outside Air Position  
Setpoint  
12. Supply Air Reheat Setpoint  
13. Minimum Outside Air Position  
Setpoint  
14. Occupied Dehumidification  
Setpoint  
14. Occupied Dehumidification  
Setpoint  
15. Unoccupied Dehumidification  
Setpoint  
predetermined value, the heating  
valve is opened to a position selected  
at the unit mounted Human Interface  
to allow a minimum amount of  
steam or hot water to flow through  
the coil and avoid freezing  
15. Unoccupied Dehumidification  
Setpoint  
16. Occupied Humidification  
Setpoint  
16. Occupied Humidification  
Setpoint  
17. Unoccupied Humidification  
Setpoint  
17. Unoccupied Humidification  
Setpoint  
conditions.  
Binary Outputs - each of the five (5)  
relay outputs can be mapped to any/  
all of the available diagnostics.  
Applications with Chilled  
Water Coil  
Analog Outputs—Four analog  
outputs that can be configured to be  
any of the following:  
Binary Input - the single binary input  
can initiate or terminate the Demand  
Limit mode of operation via a field  
supplied switch or contact closure.  
Occupied/Unoccupied  
Switching  
1. Outdoor Air Temperature  
2. Zone Temperature  
Description - 3 ways to switch  
Occupied/Unoccupied:  
3. Supply Air Temperature (VAV  
only)  
Generic Building Automation  
System Module (GBAS 0-10  
vdc)  
1. Night Setback (NSB) Panel  
4. Supply Air Pressure (VAV only)  
5. Space Pressure  
2. Field-supplied contact closure  
(hard wired binary input to RTM)  
The Generic Building Automation  
System Module (GBAS 0-10vdc) is  
used to provide broad control  
capabilities for building automation  
systems other than Trane's Tracer™  
system. The following inputs and  
outputs are provided:  
6. Space Relative Humidity  
7. Outdoor Air Relative Humidity  
3. TRACER (or 3rd Party BAS with  
LCI module)  
8. Space CO Level  
2
Night Setback Sensors  
9. Heat Staging (%)  
Trane's night setback sensors are  
programmable with a time clock  
function that provides  
communication to the air handler  
unit through a 2-wire  
communications link. The desired  
transition times are programmed at  
the night setback sensor and  
communicated to the air handler.  
10. Outdoor Air Damper Position  
11. Outdoor Airflow  
Analog Inputs—Four analog inputs,  
controlled via a field provided  
potentiometer or a 0-10 vdc signal,  
that can be configured to be any of  
the following:  
Binary Output - the single relay  
output can be mapped to any/all of  
the available diagnostics.  
1. Occupied Zone Cooling Setpoint  
(CV only)  
Binary Input - the single binary input  
can initiate or terminate the Demand  
Limit mode of operation, via a field  
supplied switch or contact closure.  
2. Unoccupied Zone Cooling  
Setpoint (CV only)  
Night setback (unoccupied mode) is  
operated through the time clock  
provided in the sensors with night  
setback. When the time clock  
switches to night setback operation,  
the outdoor air dampers close and  
heating/cooling can be enabled or  
disabled depending on setup  
parameters.  
3. Occupied Zone Heating Setpoint  
(CV only)  
Chilled Water Coil - Freeze  
Stat  
4. Unoccupied Zone Heating  
Setpoint (CV only)  
A low limit thermostat, mounted on  
the entering air side of the coil, is  
used to help prevent the chilled water  
coil from freezing during periods of  
low ambient temperature. If the  
temperature falls below a  
5. Supply Air Cooling Setpoint (VAV  
only)  
As the building load changes, the  
night setback sensor energizes the air  
handler heating/cooling (if enabled)  
6. Supply Air Heating Setpoint (VAV  
only)  
predetermined value the low limit  
RT-PRC031-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls VAV and CV  
function and the supply fan. The air  
handler unit will cycle through the  
evening as heating/cooling (if  
enabled) is required in the space.  
When the time clock switches from  
night setback to occupied mode, all  
heating/cooling functions begin  
normal operation.  
135ºF. If either setpoint is reached, the  
air handler unit is shut down.  
Comparative Enthalpy Control  
of Economizer  
An optional Comparative Enthalpy  
system is used to control the  
operation of the economizer, and  
measures the temperature and  
humidity of both return air and  
outside air to determine which  
source has lower enthalpy. This  
system allows true comparison of  
outdoor air and return air enthalpy  
by measurement of outdoor air and  
return air temperatures and  
humidities.  
CO2 Control - Demand Control  
Ventilation (DCV)  
A ventilation reset function that  
provides the necessary ventilation for  
occupants and reduces energy  
consumption by minimizing the  
outdoor air damper position (or the  
OA flow setpoint with TRAQs) below  
the Building Design Minimum, while  
still meeting the ASHRAE Std 62.1-  
2004 ventilation requirements.  
When using the night setback options  
with a VAV heating/cooling air  
handler, airflow must be maintained  
through the air handler unit. This can  
be accomplished by electrically tying  
the VAV boxes to the VAV Box output  
relay contacts on the Rooftop Module  
(RTM) or by using changeover  
thermostats. Either of these methods  
will assure adequate airflow through  
the unit and satisfactory temperature  
control of the building.  
If the space CO level is greater than  
2
Reference Enthalpy Control of  
Economizer  
or equal to the CO Design Setpoint,  
2
the outdoor air damper will open to  
the Design Min Outdoor Air Damper  
(or OA Flow) Setpoint. If there is a call  
for economizer cooling, the outdoor  
air damper may be opened further to  
satisfy the cooling request.  
The optional reference enthalpy  
compares outdoor air temperature  
and humidity to the economizer  
enthalpy control setpoint. If outdoor  
air temperature and humidity are  
below the economizer enthalpy  
control setpoint, the economizer will  
operate freely. This system provides  
more sophisticated control where  
outdoor air humidity levels may not  
be acceptable for building comfort  
and indoor air quality.  
Occupied/Unoccupied input  
on the RTM  
If the space CO level is less than or  
2
This input accepts a field supplied  
switch or contacts closure such as a  
time clock.  
equal to the CO Minimum Setpoint,  
2
the outdoor air damper will close to  
the DCV Minimum Outdoor Air  
Damper (or OA Flow) Setpoint.  
Trane Tracer™ or BAS System  
The Trane Tracer System or a 3rd  
party BAS (with LCI module) can  
control the Occupied/Unoccupied  
status of the air handler.  
Dry Bulb Temperature Control  
of Economizer  
The optional dry bulb system  
Timed Override Activation -  
ICS  
measures outdoor temperature  
comparing it to the economizer  
control temperature setpoint. If the  
outdoor temperature is below the  
economizer dry bulb temperature  
control setpoint, the economizer will  
operate freely. This system is best  
suited for arid regions where the  
humidity levels of fresh air would not  
be detrimental to building comfort  
and indoor air quality.  
This function is operational when the  
RTM is selected as the Zone  
Temperature Sensor source at the  
Human Interface Panel. When this  
function is initiated by the push of a  
override button on the ICS sensor,  
the Tracer will switch the unit to the  
Occupied mode. Unit operation  
(Occupied mode) during timed  
override is terminated by a signal  
from Tracer.  
Emergency Stop Input  
A binary input is provided on the  
Rooftop Module (RTM) for  
installation of field provided switch  
or contacts for immediate shutdown  
of all unit functions.  
Timed Override Activation -  
Non-ICS  
This function is active whenever the  
RTM is selected as the Zone  
Temperature Sensor source at the  
Human Interface Panel. When this  
function is initiated by the push of an  
override button on the zone sensor,  
the unit will switch to the Occupied  
mode. Automatic Cancellation of the  
Timed Override Mode occurs after  
three hours of operation.  
High Duct Temp Thermostat  
Two manual reset, high temperature  
limit thermostats are provided. One  
is located in the discharge section of  
the unit set at 240ºF and the other in  
the return air section of the unit set at  
20  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls VAV and CV  
Twinning requires an LCI module  
installed in each unit and is  
accomplished by binding variables  
between unit communication  
modules, communicating common  
setpoints and conditions  
(temperatures, pressures, fan  
speeds, damper positions,  
occupancy, states, etc.) and allowing  
each unit to run independent  
algorithms.  
Space CO2 Level  
Design  
Min OA  
Damper  
Setpoint  
Min OA  
Damper  
Position  
Target  
Twinned units must share a common  
supply and return duct network.  
DCV Min  
OA  
Twinned units operate:  
Damper  
Setpoint  
a. as part of a Trane ICS™  
installation, with Tracer  
Summit  
b. on an interoperable project  
with a 3rd party LonTalk  
c. as an independent group  
(bound via Rover® or 3rd  
party tool).  
CO2 Min  
Setpoint  
CO2 Design  
Setpoint  
CO2 Level  
Figure 14. CO2 Control  
other cases the return fan is turned  
on or off with the supply fan.  
If there is a call for economizer  
cooling, the outdoor air damper may  
be opened further to satisfy the  
cooling request.  
LonTalk® Building  
Automation System  
If the space CO level is greater than  
2
the CO Minimum Setpoint and less  
2
The LonTalk Communication  
Interface for IntelliPak II (LCI-I)  
than the CO Design Setpoint, the  
2
outdoor air damper position is (or OA  
controller expands communications  
from the unit UCM network to a  
Trane Tracer Summit or a 3rd party  
building automation system, utilizing  
LonTalk, and allows external setpoint  
and configuration adjustment and  
monitoring of status and diagnostics.  
The LCI-I utilizes an FTT-10A Free  
Topology transceiver, which supports  
non-polarity sensitive, free topology  
wiring, which allows the system  
installer to utilize star, bus, and loop  
architectures.This controller works in  
standalone mode, peer-to-peer with  
one or more other units, or when  
connected to a Trane Tracer Summit  
or a 3rd party building automation  
system that supports LonTalk. The  
LCI-I controller is available as a  
factory or field-installed kit.  
flow) modulated proportionally to the  
Space CO level relative to a point  
2
between the CO Min Setpoint and  
2
the CO Design Setpoint. If there is a  
2
call for economizer cooling, the  
outdoor air damper may be opened  
further to satisfy the cooling request.  
See Figure 14, p. 21  
Humidification Control  
A relay output is provided to control  
an externally connected, field  
supplied humidifier. Logic is  
provided for Occupied and  
Unoccupied humidification control  
with safeguards to prevent cycling  
between humidification and  
dehumidification  
Return Fan Control  
Twinning  
A return fan reduces the load on the  
supply fan motor or can allow a unit  
to operate at a higher static pressure.  
Twinning is a Master Unit and one, or  
more, similarly configured Slave  
Unit(s) operating cooperatively, as a  
group, to provide higher capacity  
and/or redundancy at partial capacity.  
The return fan VFD is modulated  
independently to maintain desired  
return air plenum pressure. In all  
RT-PRC031-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Applications Considerations  
Essentially, one large fan by itself is  
Exhaust/Return  
Fan Options  
Application  
normally more efficient than two  
Recommendations  
fans in series because of only one  
drive loss, not two as with return fan  
systems.  
When is it necessary to provide  
building exhaust? Whenever an  
outdoor air economizer is used, a  
building generally requires an  
exhaust system. The purpose of the  
exhaust system is to exhaust the  
proper amount of air to prevent over  
or under-pressurization of the  
building.  
100 Percent Modulating Exhaust  
with Statitrac Control, Constant  
Volume and VAV Units  
In a return fan system, the return fan  
is in series with the supply fan, and  
operates continuously whenever the  
supply fan is operating to maintain  
return air volume. The supply fan  
motor and drives are sized to deliver  
the design CFM based on internal  
and discharge static pressure losses  
only.  
For both CV and VAV air handlers,  
the 100 percent modulating exhaust  
discharge dampers (or VFD) are  
modulated in response to building  
pressure. A differential pressure  
control system, Statitrac, uses a  
differential pressure transducer to  
compare indoor building pressure to  
atmospheric pressure.  
The goal is to exhaust approximately  
10 percent less air than the amount  
of outside air going into the building.  
This maintains a slightly positive  
building pressure.  
The return fan motor and drives are  
sized to pull the return CFM back to  
the unit based on return duct static.  
Therefore, with a return fan system,  
the supply fan ordinarily requires  
less horsepower than a system with  
an exhaust fan  
The FC exhaust fan is turned on  
when required to lower building  
static pressure to setpoint. The  
Statitrac control system then  
modulates the discharge dampers  
(or VFD) to control the building  
pressure to within the adjustable,  
specified deadband that is set at the  
Human Interface Panel.  
The reason for applying either a  
return, or exhaust fan is to control  
building pressure. The Trane 100  
percent modulating exhaust system  
with Statitrac is an excellent choice  
for controlling building pressure in  
the majority of applications.  
IntelliPak™ II Rooftop Air  
Handler Unit Offers Four  
Types of Exhaust/Return Fan  
Systems:  
For more demanding applications,  
Trane's 100 percent modulating  
return fan system with Statitrac is an  
excellent choice for systems with  
high return static pressure losses, or  
duct returns. Both systems employ  
direct digital control technology to  
maintain building pressure. Either  
return or exhaust fan systems with  
Statitrac may be used on any air  
handler application that has an  
outdoor air economizer.  
Economizer and return air dampers  
are modulated independent of the  
exhaust dampers (or VFD) based on  
ventilation control and economizer  
cooling requests.  
1
100 percent modulating exhaust with  
Statitrac™ direct space sensing  
building pressurization control (with  
or without exhaust variable  
frequency drives)  
Advantages:  
The exhaust fan runs only when  
needed to lower building static  
pressure.  
2
Statitrac compensates for  
pressure variations within the  
building from remote exhaust  
fans and makeup air units.  
100 percent modulating exhaust  
without Statitrac  
A building may have all or part of its  
exhaust system in the air handler  
unit. Often, a building provides  
exhaust external to the air handling  
equipment. This external exhaust  
must be considered when selecting  
the air handler exhaust system.  
3
The exhaust fan discharges in a  
single direction resulting in  
more efficient fan operation  
compared to return fan systems.  
100 percent modulating plenum  
return airfoil fan with Statitrac direct  
space sensing building  
pressurization control with variable  
frequency drive  
With an exhaust fan system, the  
supply fan motor and drives must be  
sized to overcome the total system  
static pressure, including return  
losses, and pull return air back to the  
unit during non-economizer  
operation.  
When discharge dampers are  
utilized to modulate the exhaust  
airflow, the exhaust fan may be  
running unloaded whenever the  
economizer dampers are less  
than 100 percent open.  
4
100 percent modulating plenum  
return airfoil fan without Statitrac  
Drivers for applying either return or  
exhaust fan systems range from  
economy, to building pressure  
control, to code requirements, to  
generally accepted engineering  
practices  
However, a supply fan can typically  
overcome return duct losses more  
efficiently than a return air fan  
system.  
22  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Applications Considerations  
The Trane 100 percent modulating  
exhaust system with Statitrac  
Economizer and return air dampers  
are modulated independent of the  
exhaust dampers based on  
ventilation control, and economizer  
cooling requests.  
100 Percent Modulating  
Return Fan Systems with  
Statitrac™ Control, Constant  
Volume and VAV units  
provides efficient control of building  
pressure in most applications simply  
because 100 percent modulating  
exhaust discharge dampers (or VFD)  
are controlled directly from building  
pressure, rather than from an indirect  
indicator of building pressure, such  
as outdoor air damper position.  
For both CV and VAV applications,  
the IntelliPak II air handler offers 100  
percent modulating return fan  
Advantages:  
The exhaust dampers are  
systems. A differential pressure  
control system, Statitrac, uses a  
differential pressure transducer to  
compare indoor building pressure to  
atmospheric pressure. The return fan  
exhaust dampers are modulated,  
based on space pressure, to control  
the building pressure to within the  
adjustable, specified deadband that  
is set at the Human Interface Panel. A  
VFD modulates the return fan speed  
based on return duct static pressure.  
Economizer and return air dampers  
are modulated independent of the  
exhaust dampers based on  
modulated as needed through a  
space pressure sensor input to  
maintain building pressure.  
100 Percent Modulating Exhaust  
System without Statitrac,  
Constant Volume Units Only  
The return fan discharges in two  
directions, thereby balancing  
exhaust and unit return air  
volumes.  
This fan system has performance  
capabilities equal to the supply fan.  
The FC exhaust fans are started by  
the economizer's outdoor air damper  
position and the exhaust dampers  
track the economizer outdoor air  
damper position. The amount of air  
exhausted by this fan is controlled by  
modulating discharge dampers at the  
fan outlet. The discharge damper  
position is controlled by a signal that  
varies with the position of the  
Supply and Return Airflow  
Configurations  
The typical air handler installation  
has both the supply and return air  
paths routed through the roof curb  
and building roof. However, many air  
handler installations require  
horizontal supply and/or return from  
the air handler because of a  
ventilation control and economizer  
cooling requests.  
Advantages:  
economizer dampers. When the  
exhaust fans start, the modulating  
discharge dampers are fully closed,  
and exhaust airflow is 15 to 20  
building's unique design or for  
acoustic considerations.  
The return fan operates  
independently of the supply fan  
to provide proper balance  
With IntelliPak II, there are several  
ways to accomplish horizontal  
supply, see Table 1, p. 24 and/or  
return, see Table 2, p. 24.  
percent of total exhaust capabilities.  
throughout the airflow envelope.  
Statitrac compensates for  
pressure variations within the  
building from remote exhaust  
fans and makeup air units.  
Advantages:  
The exhaust fan runs only when  
the economizer reaches the  
desired exhaust enable point.  
The return fan acts as both  
exhaust and return fan based on  
operation requirements.  
Exhaust dampers are modulated  
based on the economizer  
position.  
The Trane 100 percent modulating  
return system with Statitrac provides  
efficient control of building pressure  
in applications with higher return  
duct static pressure and applications  
requiring duct returns.  
The exhaust fan discharges in a  
single direction resulting in more  
efficient fan operation compared  
to return fan systems.  
When discharge dampers are  
utilized to modulate the exhaust  
airflow, the exhaust fan may be  
running unloaded whenever the  
economizer dampers are less  
than 100 percent open.  
Exhaust discharge dampers are  
controlled directly from building  
pressure, return fan VFD is controlled  
from return static pressure, and  
return/economizer dampers are  
controlled based on ventilation  
control and economizer cooling  
requests. 100 Percent Modulating  
Return Fan without Statitrac™  
Control, Constant Volume Units Only  
The Trane 100 percent modulating  
exhaust system provides excellent  
linear control of building exhaust in  
most applications where maintaining  
building pressure is not important.  
The exhaust discharge dampers are  
modulated in response to building  
pressure. The return fan runs  
continuously while the supply fan is  
energized.  
RT-PRC031-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Applications Considerations  
Table 1 Supply Airflow Configuration  
With Bag  
Final  
Filters  
With  
Cartridge  
Final Filters Final Filters  
Acceptable  
Application  
With HEPA  
Cabinet Configuration  
Standard Length  
Standard Length  
Standard Length  
Supply Airflow Discharge Direction  
Downflow - Standard Option  
Type  
Cooling Only  
Cooling Only  
Cooling Only  
Yes  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Horizontal - Right Side - Standard Option  
Horizontal - Left Side - Field Convertible  
Yes  
Field  
Convert  
Standard Length  
Standard Length  
Downflow - Standard Option  
Gas, Electric, Steam,  
Hot Water Heat  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Horizontal - Right Side - Standard Option Gas, Electric, Steam,  
Hot Water Heat  
Standard Length  
Horizontal - Left Side - Field Convertible Gas, Electric, Steam,  
Hot Water Heat  
Four Foot Blank Section  
Downflow - Standard Option  
Cooling Only  
Cooling Only  
Cooling Only  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Four Foot Blank Section Horizontal - Right Side - Standard Option  
Four Foot Blank Section  
Horizontal - Left Side - Field Convertible  
Field  
Convert  
Four Foot Blank Section  
Downflow - Standard Option  
Gas, Electric, Steam,  
Hot Water Heat  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
No  
Four Foot Blank Section Horizontal - Right Side - Standard Option Gas, Electric, Steam,  
Hot Water Heat  
Four Foot Blank Section  
Horizontal - Left Side - Field Convertible Gas, Electric, Steam,  
Hot Water Heat  
No  
No  
No  
Eight Foot Blank Section  
Downflow - Standard Option  
Cooling Only, Steam  
Heat, Hot Water Heat  
Yes  
Yes  
Yes  
Yes  
Yes  
High  
Yes  
Yes  
Yes  
High  
Eight Foot Blank Section Horizontal - Right Side - Standard Option Cooling Only, Steam  
Heat, Hot Water Heat  
Eight Foot Blank Section Horizontal - Left Side - Field Convertible  
Cooling Only, Steam  
Heat, Hot Water Heat  
Field  
Convert  
Eight Foot Blank Section Downflow - Standard Option  
Gas* or Electric  
Gas* or Electric  
Gas* or Electric  
Yes  
Yes  
Temperature Temperature  
Eight Foot Blank Section Horizontal - Right Side - Standard Option  
Eight Foot Blank Section Horizontal - Left Side - Field Convertible  
High High  
Temperature Temperature  
Field  
Convert  
High  
High  
Temperature Temperature  
Table 2 Return Airflow Configuration  
AirflowConfig  
Exhaust Fan  
No VFD  
Return Fan  
No VFD  
Exhaust Fan VFD  
Return Fan VFD  
Vertical  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
Horizontal - Right  
Horizontal - Left  
Horizontal - End  
Yes  
Field Convert  
Yes  
No  
Yes  
No  
No  
24  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Applications Considerations  
When using an IntelliPak II Air  
Handler for horizontal supply and/or  
return, an additional pressure drop  
must be added to the supply external  
static to account for the 90 degree  
turn the air is making. This additional  
pressure drop depends on airflow  
and air handler size, but a range of  
0.10 inches to 0.30 inches can be  
expected. The openings on the air  
handler all have a one inch lip around  
the perimeter to facilitate ductwork  
attachment.  
Trane can provide five (5) different  
ventilation override sequences on  
both CV and VAV IntelliPak II Air  
Handlers. For convenience, the  
sequences are factory preset but are  
fully field edited from the Human  
Interface Panel or Tracer™. Any or all  
five sequences may be “locked” in  
by the user at the Human Interface  
Panel.  
exchanger. IntelliPak II natural gas  
heat exchangers are not  
recommended for applications with  
mixed air conditions entering the  
heat exchanger below 30°F to insure  
adequate leaving air heating  
temperature.  
For airflow limitations and  
temperature rise across the heat  
exchanger information, see Table 27,  
p. 70.  
The user can customize up to five (5)  
different override sequences for  
purposes such as smoke control. The  
following parameters within the unit  
can be defined for each of the five  
sequences:  
Acoustical Considerations  
Corrosive Atmospheres  
The ideal time to make provisions to  
reduce sound transmission to the  
space is during the project design  
phase. Proper placement of air  
Trane's IntelliPak II Air Handlers are  
designed and built to industrial  
standards and will perform to those  
standards for an extended period  
depending on the hours of use, the  
quality of maintenance performed,  
and the regularity of that  
Supply Fan - on/off  
handler equipment is critical to  
Inlet Guide Vanes - open/closed/  
controlling  
reducing transmitted sound levels to  
the building. The most economical  
means of avoiding an acoustical  
problem is to place any air handler  
equipment away from acoustically  
critical areas. If possible, air handling  
equipment should not be located  
directly above areas such as: offices,  
conference rooms, executive office  
areas and classrooms. Ideal locations  
are above corridors, utility rooms,  
toilet facilities, or other areas where  
higher sound levels are acceptable.  
Variable Frequency Drives - on  
(60 Hz)/off (0 Hz)/controlling  
maintenance. One factor that can  
have an adverse effect on unit life is  
its operation in a corrosive  
Exhaust/Return Fan - on/off  
Exhaust Dampers - open/closed  
environment.  
Economizer dampers - open/  
closed  
Because copper is more resistant to  
corrosion than aluminum, coil life  
expectancy is greatly increased.  
Heat - off/controlling (output for)  
VAV Boxes - open/controlling  
Factory preset sequences include  
unit Off, Exhaust, Purge, Purge with  
duct pressure control, and  
Pressurization. Any of the user-  
defined Ventilation Override  
sequences can be initiated by closing  
a field supplied switch or contacts  
connected to an input on the  
Ventilation Override Module. If more  
than one ventilation override  
sequence is being requested, the  
sequence with the highest priority is  
initiated. Refer to the Ventilation  
Override Module (VOM) page 17 in  
the Control section of this catalog for  
more details on each override  
sequence.  
Ventilation Override  
Sequences  
Several basic guidelines for unit  
placement should be followed to  
minimize sound transmission  
through the building structure:  
One of the benefits of using an  
exhaust fan rather than a return fan,  
in addition to the benefits of lower  
energy usage and improved building  
pressurization control, is that the air  
handler can be used as part of a  
ventilation override system. Several  
types of sequences can be easily  
done when exhaust fans are a part of  
the air handling system.  
1
Locate the unit's center of gravity  
close to or over a column or main  
support beam to minimize roof  
deflection and vibratory noise.  
2
What would initiate the ventilation  
override control sequence? Typically,  
a manual switch is used and located  
near the fire protection control panel.  
This enables the fire department  
access to the control for use during  
or after a fire. It is also possible to  
initiate the sequence from a field-  
installed automatic smoke detector.  
In either case, a contact closure  
begins the ventilation override  
control sequence.  
If the roof structure is very light, roof  
joists should be replaced by a  
structural shape in the critical areas  
described above.  
Natural Gas Heating  
Considerations  
3
Trane uses heavy gauge 304 L  
stainless steel throughout the  
If several units are to be placed on  
one span, they should be staggered  
to reduce deflection over that span.  
construction of its natural gas drum  
and tube heat exchangers for the  
IntelliPak II product. These heat  
exchangers can be applied with  
confidence, particularly with full  
modulation control, when mixed air  
temperatures are below 50°F, and low  
ambient temperatures can cause  
condensation to form on the heat  
It is impossible to totally quantify the  
effect of building structure on sound  
transmission, since this depends on  
the response of the roof and building  
members to the sound and vibration  
of the unit components. However, the  
guidelines listed above are  
ƽCAUTION!  
The ventilation override system  
should not be used to signal the  
presence of smoke caused by a fire.  
experience proven guidelines which  
RT-PRC031-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Applications Considerations  
will help reduce sound transmission.  
The ASHRAE publication "A Practical  
Guide to Noise and Vibration Control  
for HVAC Systems" also provides  
valuable information.  
Figure 15. Unit Placement  
There are several other sources of  
unit sound, i.e., supply fan, exhaust/  
return fans, and aerodynamic noise  
generated at the duct fittings. Refer  
to the ASHRAE Applications  
Handbook, Chapter 47, 2003 edition  
for guidelines for minimizing the  
generation of aerodynamic noise  
associated with duct fittings. A good  
source of information on general  
acoustical considerations for air  
handlers is the 2000 ASHRAE Journal  
article titled, "Controlling Noise from  
Large Rooftop Units".  
Exhaust  
Air  
The Trane Acoustic Program (TAP)  
allows complete modeling of air  
handler acoustical installation  
parameters. The software models  
airborne sound from supply and  
return ducts, as well as duct breakout  
and roof transmission sound, so that  
the designer can identify potential  
sound problems and make design  
alterations before equipment  
Exhaust  
Air  
Actual clearances which appear  
inadequate should be reviewed with  
a local Trane sales engineer.  
installation. Output of the program  
shows the resulting NC (or RC) level  
for any point in the occupied space.  
TAP is also capable of modeling the  
effect of outdoor sound on the  
When two or more units are to be  
placed side by side, the distance  
between the units should be  
increased to 150 percent of the  
recommended single unit clearance.  
The units should also be staggered,  
surrounding area. This program is  
available from Trane's Customer  
TM  
Direct Service Network  
(C.D.S.),  
see Figure 15, p. 26, for two reasons:  
ask your local Trane representative  
for additional information on this  
program.  
1
To reduce span deflection if more  
than one unit is placed on a single  
span. Reducing deflection  
Clearance Requirements  
The recommended clearances  
identified in Figure 31, p. 85 should  
be maintained to assure adequate  
service capability, maximum capacity  
and peak operating efficiency. If the  
clearances shown are not possible on  
a particular job, consider the  
following:  
discourages sound transmission.  
2
To assure proper diffusion of exhaust  
air before contact with the outside air  
intake of adjacent unit.  
Do the clearances available allow  
for major service work such as  
changing coils?  
Do the clearances available allow  
for proper outside air intake and  
exhaust air removal?  
If screening around the unit is  
being used, is there a possibility  
of air recirculation from the  
exhaust to the outside air intake?  
26  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Applications Considerations  
Adding glycol to the cooling  
system water to lower its  
freezing point  
Duct Design  
Protecting Hydronic Coils  
From Freezing  
It is important to note that the rated  
capacities of the air handler can be  
met only if the air handler is properly  
installed in the field. A well-designed  
duct system is essential in meeting  
these capacities.  
Taking in outdoor air to satisfy  
Standard 62s ventilation  
requirement increases the likelihood  
of air stratification. If a layer of air  
below freezing moves through the air  
handler, it can damage unprotected  
hydronic cooling and heating coils.  
External Piping Enclosure  
Space inside the piping enclosure  
limits the ability to house control  
valves and actuators along with coil  
supply and return piping.  
The satisfactory distribution of air  
throughout the system requires that  
there be an unrestricted and uniform  
airflow from the air handler  
When a dangerously low air  
temperature is detected by the low-  
limit thermostat on the entering-air  
side of the coil, it will trip. That  
triggers the water valve to fully open,  
the supply fan to stop, the outdoor  
air damper to close and ultimately  
degrades the buildings indoor air  
quality.  
discharge duct. This discharge  
section should be straight for at least  
several duct diameters to allow the  
conversion of fan energy from  
velocity pressure to static pressure.  
However, when job conditions  
dictate elbows be installed near the  
air handler outlet, the loss of capacity  
and static pressure may be reduced  
through the use of guide vanes and  
proper direction of the bend in the  
elbow. The high velocity side of the  
air handler outlet should be directed  
at the outside radius of the elbow  
rather than the inside as illustrated in  
Two options that can be  
implemented to continue taking in  
outdoor air and avoid coil damage or  
tripping the low-limit thermostat  
include:  
Draining the coils  
PROPER  
IMPROPER  
Figure 16. Duct Design  
RT-PRC031-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Selection Procedure  
This section outlines a step-by-step  
procedure that may be used to select  
a Trane air handler. The sample  
selection is based on the following  
conditions:  
Economizer  
Step 3 - Determine Supply  
Fan Motor Heat Gain  
Modulating 100 percent exhaust  
Having selected air handler casing  
"C" with a 4 row 144 fpf W coil and  
no turbulators, the supply fan BHP  
can be calculated.  
Cooling Capacity Selection:  
Summer Design:  
Step 1 - Coil and Fan  
Selection  
Summer outdoor design  
conditions - 95 DB/76 WB  
ambient temperature  
The supply fan motor heat gain must  
be considered in final determination  
of unit capacity.  
A summation of the peak cooling  
load and the outside air ventilation  
load shows: 980 MBH + 154.0 MBH =  
1134.0 MBH required unit capacity.  
Summer room design  
conditions -78 DB/65 WB  
Supply Air Fan  
Total cooling load - 980 MBH  
(81.6 tons)  
Determine unit total static pressure  
at design supply CFM:  
The supply fan air flow requirement  
is 36,000 cfm.  
Sensible cooling load - 735 MBH  
(61.25 tons)  
From Table 10, p. 39, a 4 row W coil  
with 144 fpf (fins per foot) and no  
turbulators at 80 DB/67 WB and  
36000 supply air cfm has a total  
cooling capacity of 1336 MBH and  
sensible cooling capacity of 969  
MBH. With chilled water coil capacity  
data at 80 DB/67 WB only, TOPSS is  
required for an accurate selection at  
other conditions. TOPSS is also  
required to select the correct water  
control valve for proper flow control,  
in this case a 2 ½ "or 3" valve.  
Supply Duct Static Pressure  
2.2"  
Chilled Water Coil Table 33, p. 72  
0.64"  
0.30"  
Outdoor air ventilation load -  
154.0 MBH (12.8 tons)  
Return Duct Negative Static  
Pressure  
Heat Exchanger Table 34, p. 72  
Throwaway Filter Table 35, p. 73  
Return Damper Table 34, p. 72  
0.03"  
0.26"  
0.34"  
0.57"  
Return air temperature -  
78 DB/65 WB  
Winter Design:  
(i)  
Economizer Damper Table 34,  
Winter outdoor design condition  
is 0°F.  
Unit Total Static Pressure  
4.0"  
(i)  
Add either the economizer damper value or  
return damper value, depending on which  
static pressure is greater. (Do not use both.)  
Total return air temperature is  
70°F.  
Table 3, p. 34 - General Data shows  
that air handler "C" can provide  
36000 total supply CFM.  
Total heating load - 720 MBH  
Using total of 36000 CFM and total  
static pressure of 4.0 inches, enter  
Table 17, p. 48. The table shows 40.4  
Winter outdoor air ventilation  
load - 288.6 MBH  
Thus air handler "C" with a 4 row 144  
fpf W coil having no turbulators at  
45°F entering water and a 10°F rise  
with a 2 ½" valve is selected. The coil  
water flow rate is 266 GPM and  
water side pressure drop is 13.7 ft of  
water.  
BHP with 1097 rpm required for the  
36" supply fan.  
Total winter heating load -  
1008.6 MBH  
From Figure 17, p. 30 supply fan  
motor heat gain = 109.0 MBH, or  
109.0 MBH x 1000 ÷ ( 36000 CFM x  
1.085 ) = 2.8°F supply fan motor heat  
Air Delivery Data:  
Supply fan CFM - 36000 CFM  
Supply duct static pressure - 1.86  
2.2 in wg  
Step 2 - Cooling Coil Entering  
Conditions  
Step 4 - Determine Total  
Required Cooling Capacity  
Minimum outdoor air ventilation  
- 3600 CFM  
Mixed air dry bulb temperature  
determination:  
Required capacity = Total peak load +  
OA load + supply air fan motor heat  
Exhaust fan CFM - 36000 CFM  
Return air duct negative static  
pressure - 0.3 in wg  
Using the minimum percent of OA  
(3600 CFM ÷ 36000 CFM = 10  
percent), determine the mixture dry  
bulb to the cooling coil.  
Required capacity = 980.0 + 154.0 +  
109.0 = 1243.0 MBH  
Electrical Characteristics:  
Voltage/cycle/phase - 460/60/3  
Unit Accessories:  
Step 5 - Determine Unit  
Capacity  
RADB + % OA (OADB - RADB) = 78 +  
(0.10) (95 - 78) = 78 + 1.5 = 79.5°F  
The coil entering air conditions of  
79.5 DB/66.1 WB are close to the  
capacity data table at 80 DB/67 WB  
used for the original selection. The  
unit capacity with the 4 row 144 fpf  
W coil with no turbulators at 45°F  
entering water a 10°F rise, 36000 cfm  
supply air flow and 10% outside air  
Gas fired heat exchanger - High  
Heat  
Approximate wet bulb mixture  
temperature:  
Downflow supply and upflow  
return  
RAWB + % OA (OAWB - RAWB) = 65  
+ (0.10) (76 - 65) = 65 + 1.1 = 66.1°F  
High Efficiency Throwaway  
filters  
28  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Selection Procedure  
at 95°F is approximatly 1336 MBH  
total cooling and 969 MBH sensible  
cooling capacity.  
Heat module temperature rise is  
determined by:  
Step 2 - Determine Total  
Winter Heating Load  
Total Btu = 1.085 x CFM x Air  
temperature rise, °F 1008600 / 1.085 /  
36000 = 25.8°F  
Total winter heating load = peak  
heating load + ventilation load -  
supply fan motor heat = 720 + 288.6 -  
109.0 = 899.6 MBH  
Step 6 - Determine Leaving Air  
Temperature  
Unit supply air temperature = mixed  
air temperature + air temperature  
rise = 65. 8 + 25.8 = 91.F.  
Unit sensible heat capacity corrected  
for supply air fan motor heat = 969  
MBH Sensible - 109.0 MBH Motor  
Electric Heating System  
Unit operating on 460/60/3 power  
supply.  
Steam Heating System  
Heat = 860 MBH.  
Using a 15 psig steam supply. From  
Table 31, p. 71, the saturated  
temperature steam is 250°F. Subtract  
mixed air temperature from the  
steam temperature to determine ITD.  
Supply air dry bulb temperature  
difference =  
From Table 29, p. 70, kw may be  
selected for a nominal 105 ton air  
handler "C" unit operating at 460-volt  
power. The 265 kw heat module  
(904.4 MBH) will satisfy the winter  
heating load of 899.6 MBH.  
Sensible MBH X 1000/1.085 x Supply  
CFM  
Sensible Btu = 860 MBH x 1000 ÷  
(1.085 x 36000 CFM) = 22°F  
ITD = 250°F - 65.8°F = 184.2°F.  
Table 28, p. 70 shows an air  
temperature rise of 23.2°F for 36000  
CFM through the 265 kw heat  
module.  
Divide winter heating load by ITD =  
1008.6 MBH ÷ 184.2°F = 5.48 Q/ITD.  
Supply air dry bulb = 79.5 DB - 22 =  
57.5°F Leaving the cooling coil  
Table 31, p. 71, select the low heat  
module. The low heat module at  
36000 cfm has a Q/ITD = 7.44  
Supply air wet bulb temperature  
difference = (need in RTU catalog  
too)  
Unit supply temperature at design  
heating conditions = mixed air  
temperature + air temperature rise =  
65.8°F + 23.2°F = 89.0°F.  
Heat module capacity, Q = ITD x Q/  
ITD = 185°F x 7.44Q/ITD = 1376 MBH  
Total MBH x 1000 ÷ 4.5 x Supply CFM  
=
Heat module air temperature rise is  
determined by:  
Unit enthalpy difference = 1336 MBH  
x 1000 ÷ (4.5 x 36000 CFM) = 8.25  
Btu/lb.  
Gas Heating System (Natural  
Gas)  
Total Btu = 1.085 x CFM x Air  
temperature rise, °F 1376000 / 1.085 /  
36000 = 35.2°F  
From Table 27, p. 70 select the high  
heat module (1440 MBH output) to  
satisfy winter heating load of 899.6  
MBH at unit CFM.  
Leaving enthalpy = h (ent WB) - h  
(diff). From Table 6, p. 37, p. 40 h (ent  
WB) =  
Unit supply temperature at design  
conditions = mixed air temperature +  
air temperature rise = 65.8°F + 35.2°F  
= 100.1°F.  
30.9 Btu/lb.  
Table 27, p. 70 also shows an air  
temperature rise of 37.0°F for 36000  
CFM through the heating module.  
Leaving enthalpy = 30.9 Btu/lb. - 8.25  
Btu/lb. = 22.65 Btu/lb.  
Air Delivery Procedure  
Unit supply temperature at design  
heating conditions = mixed air  
temperature + air temperature rise =  
65.8°F + 37.0°F = 102.8°F.  
Supply air wet bulb = 54.0 Leaving  
the cooling coil.  
Supply fan performance tables  
include internal resistance of air  
handler.  
Leaving air temperature = 57.5 DB/  
54.0 WB  
For total static pressure  
Hot Water Heating System  
determination, system external static  
must be added to appropriate  
component static pressure drop  
cooling coil, filters, optional  
Heating Capacity Selection  
Using a hot water supply  
temperature of 190°F and an entering  
Step 1 - Determine Air  
Temperature Entering Heating  
Module  
coil temperature of 65.8°F.  
economizer, optional exhaust fan,  
optional heating system, optional  
cooling only extended casing).  
Subtract the mixed air temperature  
from the hot water temperature to  
determine the ITD (initial  
Mixed air temperature = RADB +  
% OA (OADB - RADB) = 70 + (0.10)  
(0 - 70) = 63°F  
Supply Fan Motor Sizing  
temperature difference).  
The supply fan motor selected in the  
cooling capacity determination was  
40.4 BHP and 1097 RPM. Thus, a 40  
HP supply fan motor is selected.  
ITD = 190°F - 65.8°F = 124.2°F.  
Divide the winter heating load by ITD  
= 1008.6 MBH ÷ 124.2°F = 8.12 Q/  
ITD.  
Supply air fan motor heat  
temperature rise = 109000 Btu ÷  
(1.085 x 36000 CFM) = 2.8°F  
Air temperature entering heating  
module = 63.0 + 2.8 = 65.8°F  
Enter Table 39, p. 77 to select the  
proper drive. For anair handler "C"  
with 40 HP motor, a drive letter A -  
1100 RPM is selected.  
From Table 30, p. 71, select the low  
heat module. By interpolation, a Q/  
ITD of 8.12 can be obtained at a gpm  
of 41. Water pressure drop at 41 gpm  
is 0.34 ft. of water.  
RT-PRC031-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection Procedure  
an air density correction is needed to  
project accurate unit performance.  
In order to better illustrate this  
procedure, the following example is  
used:  
Exhaust Fan Motor Sizing  
The exhaust/return fan is selected  
based on total return system  
negative static pressure and exhaust  
fan CFM. Return system negative  
static includes return duct static, and  
any other job site applicable static  
pressure drop.  
Figure 18, p. 37 shows the air density  
ratio at various temperatures and  
elevations.  
Consider an air handler"C" that is to  
deliver 32000 actual CFM at 3-inches  
total static pressure (tsp), 55°F  
leaving air temperature, at an  
elevation of 5000 ft.  
The procedure to use when selecting  
a supply or exhaust/return fan at  
elevations and  
1. From Figure 18, p. 37, the air  
density ratio is 0.86.  
Return duct static pressure = 0.30  
inches.  
temperatures other than standard is  
as follows:  
2. Tsp = 3.0-inches / 0.86 = 3.49  
inches tsp.  
Total return system negative static  
pressure = 0.30 inches.  
1. First, determine the air density  
ratio using Figure 18, p. 37.  
3. From fan performance Table 17,  
p. 48 air handler"C" (without inlet  
vanes) will deliver 32000 CFM at  
3.49 inches TSP at 997 RPM and  
30.27 BHP.  
Exhaust fan CFM = 36000 CFM  
2. Divide the static pressure at the  
nonstandard condition by the air  
density ratio to obtain the  
From Table 39, p. 77 the required  
BHP is 21.44 BHP at 400 RPM. Thus,  
the exhaust fan motor selected is 25  
HP.  
corrected static pressure.  
3. Use the actual CFM and the  
corrected static pressure to  
determine the fan RPM and BHP  
from the performance tables or  
curves.  
4. The RPM is correct as selected -  
997 RPM.  
To select a drive, enter Table 37, p. 75  
for a 25 HP motor and air handler  
"C". Drive selection number 4 - 400  
RPM.  
5. BHP = 30.27 x 0.86 = 26.3 BHP  
actual.  
4. The fan RPM is correct as  
selected.  
Cooling coil MBH should be  
Return Fan Motor Sizing  
calculated at standard and then  
converted to actual using the  
correction factors in Table 6, p. 37,  
these factors to the capacities  
selected at standard CFM so as to  
correct for the reduced mass flow  
rate across the condenser.  
The same static pressure and CFM  
considerations must be taken for  
return fan size, horsepower, and  
drive selection as are required for  
exhaust fan sizing. However, since  
the return fan runs continuously the  
sensible heat generated by the return  
fan motor must be included in the  
entering evaporator coil mixed air  
temperature equation.  
5. BHP must be multiplied by the  
air density ratio to obtain the  
actual operating BHP.  
Heat selections other than gas heat  
will not be affected by altitude.  
Nominal gas capacity (output) should  
be multiplied by the factors given in  
Table 8, p. 37 before calculating the  
heating supply air temperature.  
In this selection, if the return motor  
BHP is equal to the exhaust motor  
BHP, 21.44 BHP = 58.1 MBH x 1000÷  
(1.085 x 36000 Return CFM) = 1.5°F  
added to the return air temperature.  
Where altitudes are significantly  
above sea level, use Table 6, p. 37,  
applicable correction factors.  
FAN MOTOR HEAT  
300  
250  
200  
150  
100  
50  
Std Motor  
Hi Efficiency Motor  
Unit Electrical Requirements  
Selection procedures for electrical  
requirements for wire sizing amps,  
maximum fuse sizing, and dual  
element fuses are given in the  
electrical service section of this  
catalog.  
Altitude Corrections  
The air handler performance tables  
and curves of this catalog are based  
on standard air (.075 lbs/ft). If the  
airflow requirements are at other  
than standard conditions (sea level),  
0
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
PM1206  
Motor Brake Horse Power  
Figure 17. Fan Motor Heat  
30  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model Number Description  
W E H C A00 4 0 A 0 4 1 1 F 7 0 0 0 1 A 0 0 0 0 A 0 D 0 A 0 0 0 0 0 0 0 0  
1 2 3 4 567 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38  
DIGIT 1 — UNIT TYPE  
DIGIT 9 — HEAT CAPACITY  
SELECTION  
DIGIT 14 — FAN MOTOR  
SELECTION  
W Self-Contained (Packaged  
Air Handler)  
0
1
2
3
4
A
B
C
D
E
F
No Heat  
1
2
3
Standard Efficiency Motor(s)  
High Efficiency Motor(s)  
TEFC High Efficiency Motor(s)  
Electric Heat 90 kW  
Electric Heat 140 kW  
DIGIT 2 — UNIT FUNCTION  
Electric Heat 265 kW  
DIGIT 15 — SUPPLY FAN MOTOR  
SELECTION  
Electric Heat 300 kW  
E
F
L
S
X
Electric Heat  
Natural Gas Heat  
Hot Water Heat  
Steam Heat  
Low Gas Heat - 2 stage  
Medium Gas Heat - 2 stage  
High Gas Heat - 2 stage  
Low Gas Heat - Modulating  
Medium Gas Heat - Modulating  
High Gas Heat - Modulating  
F
15 Hp  
20 Hp  
25 Hp  
30 Hp  
40 Hp  
50 Hp  
G
H
J
No Heat  
K
L
DIGIT 3 — SYSTEM TYPE  
Single Zone  
Low Heat Options  
M 60 Hp  
75 Hp  
H
H
J
Low Heat - 1.25 in. (32mm) Valve  
Low Heat - 1.5 in. (38mm) Valve  
Low Heat - 2.0 in. (50mm) Valve  
Low Heat - 2.50 in. (64mm) Valve  
N
K
L
DIGIT 4 — DEVELOPMENT  
SEQUENCE  
DIGIT 16 — SUPPLY FAN RPM  
SELECTION  
M Low Heat - 3.0 in. (76mm) Valve  
C
Third  
7
700  
8
800  
High Heat Options  
9
900  
P
High Heat - 1.25 in.(32mm) Valve  
High Heat - 1.5 in. (38mm) Valve  
High Heat - 2.0 in. (50mm) Valve  
High Heat - 2.50 in. (64mm) Valve  
High Heat - 3.0 in. (76mm) Valve  
DIGIT 5 — UNIT SIZE  
A
B
C
D
E
F
G
H
J
1000  
1100  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
Q
R
T
A
B
C
16,000 - 31,000 CFM  
20,000 - 38,000 CFM  
20,000 - 45,000 CFM  
U
DIGIT 10 & 11— DESIGN  
SEQUENCE  
DIGIT 6 — COOLING COIL  
0
2
4
6
8
No Cooling Coil  
AO  
2 Row Chilled Water  
4 Row Chilled Water  
6 Row Chilled Water  
8 Row Chilled Water  
K
L
DIGIT 12 — UNIT  
CONFIGURATION SELECTION  
DIGIT 17 — EXHAUST/RETURN  
FAN OPTIONS  
4
5
6
1 Piece Unit - without Blank  
Section  
1 Piece Unit with 4 ft. Blank  
Section  
1 Piece Unit with 8 ft. Blank  
Section  
DIGIT 7 — CHILLED WATER COIL  
FIN SERIES  
0
1
None  
High CFM Exhaust w/o Statitrac  
CV Only  
0
No Chilled Water Coil  
2
3
4
5
6
7
8
Low CFM Exhaust w/o Statitrac  
CV Only  
High CFM Exhaust w/o VFD w/  
Statitrac  
Low CFM Exhaust w/o VFD w/  
Statitrac  
High CFM Exhaust w/ VFD w/  
Bypass w/ Statitrac  
Low CFM Exhaust w/ VFD w/  
Bypass w/ Statitrac  
High CFM Exhaust w/ VFD w/o  
Bypass w/ Statitrac  
Low CFM Exhaust w/ VFD w/o  
Bypass w/ Statitrac  
A
B
C
D
E
F
Series 80 without Turbulators  
Series 80 with Turbulators  
Series 108 without Turbulators  
Series 108 with Turbulators  
Series 144 without Turbulators  
Series 144 with Turbulators  
Series 168 without Turbulators  
Series 168 with Turbulators  
DIGIT 13 — AIRFLOW DIRECTION  
1
2
Downflow Supply/Upflow Return  
Downflow Supply/Horizontal End  
Return  
3
4
5
6
Downflow Supply/Horizontal  
Right Return  
Right Side Horizontal Supply/  
Upflow Return  
Right Side Horizontal Supply/  
Horizontal End Return  
Right Side Horizontal Supply/  
Horizontal Right Return  
G
H
DIGIT 8 — VOLTAGE SELECTION  
4
5
460/60/3 XL  
575/60/3 XL  
RT-PRC031-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model Number Description  
A
C
Return w/o Statitrac CV Only  
Return w/ VFD w/ Bypass w/  
Statitrac  
Return w/ VFD w/o Bypass w/  
Statitrac  
J
Econ w/DCV /Ref Enth  
0
None  
K
Econ w/DCV /Comp Enth  
A
B
C
D
1.5" Cooling Valve  
2" Cooling Valve  
2.5" Cooling Valve  
3" Cooling Valve  
DIGIT 22 — DAMPER OPTION  
E
0
1
2
Standard  
Low Leak  
Ultra Low Leak  
DIGIT 18 — EXHAUST/RETURN  
FAN MOTOR SELECTION  
DIGIT 30 — (FUTURE  
DEVELOPMENT)  
DIGIT 23 — PRE COOLING COIL  
FILTER SELECTION  
0
None  
7.5 Hp  
10 Hp  
15 Hp  
20 Hp  
25 Hp  
30 Hp  
40 Hp  
50 Hp  
0
None  
D
E
F
DIGIT 31 — (FUTURE  
DEVELOPMENT)  
0
1
2
3
4
2" High Efficiency Throw Away  
2" Throw Away Rack / Less Filters  
90 - 95%, Bag Filters w/ Pre Filters  
Bag Filter Rack / Less Filters  
90 - 95%, Cartridge Filters w/  
Pre Filters  
Cartridge Rack / Less Filters  
90 - 95% Low PD Cartridge w/  
Pre Filters  
G
H
J
K
L
0
None  
DIGIT 32 — HIGH DUCT  
TEMPERATURE THERMOSTAT  
5
6
0
1
None  
M 60 Hp  
High Duct Temp Thermostat  
DIGIT 19 — EXHAUST/RETURN  
RPM SELECTION  
DIGIT 33 — REMOTE HUMAN  
INTERFACE  
7
Low PD Cartridge Rack / Less  
Filters  
0
3
4
5
6
7
8
9
A
B
C
D
E
None  
300  
0
1
2
None  
RHI & IPCB  
IPCB  
DIGIT 24 — BLANK SECTION  
APPLICATION OPTIONS  
400  
500  
0
A
B
None  
DIGIT 34 — MODULE OPTIONS  
600  
90 - 95% Bag w/Pre Filters  
90 - 95% Low PD Cartridge w/  
Pre Filters  
700  
0
None  
0-5 Volt GBAS  
800  
A
B
C
F
900  
C
D
90 - 95%, Cartridge Filters w/  
Pre Filters  
90 - 95% Hi Temp Cartridge w/  
Pre Filters  
0-10 Volt GBAS  
0-5 / 0-10 Volt GBAS  
LCI  
Ventilation Override  
0-5 Volt GBAS / Ventilation  
Override  
1000  
1100  
1200  
1300  
1400  
D
G
E
F
HEPA w/Pre Filters  
Hi Temp HEPA w/Pre Filters  
H
J
L
0-10 Volt GBAS / Ventilation  
Override  
0-5 / 0-10 V GBAS / Ventilation  
Override  
LCI / Ventilation Override  
DIGIT 20 — SYSTEM CONTROL  
SELECTION  
DIGIT 25 — FUTURE  
DEVELOPMENT  
1
2
3
4
5
Constant Volume (Zone  
Temperature Control)  
VAV w/o Inlet Guide Vanes  
(Discharge Air Control)  
VAV w/ Inlet Guide Vanes  
(Discharge Air Control)  
VFD Supply w/o Bypass  
(Discharge Air Control)  
VFD Supply w/Bypass (Discharge  
Air Control)  
0
DIGIT 26 — UNIT MOUNTED  
POWER CONNECTION  
SELECTION  
DIGIT 35 — ZONE SENSOR  
OPTION  
0
A
None  
A
B
C
Terminal Block  
Dual Setpoint w/Man/Auto  
Changeover  
Non Fused Disconnect  
Non Fused Disconnect w/  
Pwrd conv outlet  
B
C
D
Dual Stpt w/Man/Auto Chgovr &  
Sys Lights  
Room Sensor w/Timed Override  
& Cancel  
Room Snsr w/TO & Cancel &  
Local Stpt Adj  
D
E
Circuit Breaker w/ SCWR  
Ckt Brkr w/ SCWR/ Pwrd conv  
outlet  
DIGIT 21 — FRESH AIR AND  
ECONOMIZER OPTIONS/  
CONTROLS  
DIGIT 27 — (FUTURE  
DEVELOPMENT)  
A
B
C
D
E
0 - 25 % Motorized Damper  
Econ w/Dry Bulb  
Econ w/Reference Enthalpy  
Econ w/Comparative Enthalpy  
Econ w/Fresh Air Measure /Dry  
Bulb  
E
F
CV Programmable Night Setback  
VAV Programmable Night  
Setback  
0
None  
DIGIT 28 — COIL/DRAIN PAN  
G
VAV w/System Lights  
D
E
F
No Drain Pan  
Galvanized Drain Pan  
Cooling Coil - Galv DP  
Cooling Coil - Stnls Steel DP  
F
Econ w/ Fresh Air Measure /Ref  
Enth  
DIGIT 36 — AGENCY APPROVAL  
OPTION  
G
G
H
Econ w/Fresh Air Measure /Comp  
Enth  
Econ w/DCV /Dry Bulb  
0
1
None  
UL/CSA  
DIGIT 29 — CHILLED WATER COIL  
VALVE  
32  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model Number Description  
DIGIT 37 — SERVICE  
ENHANCEMENTS  
0
A
B
Single Side Access Doors  
Dual Side Access Doors  
Single Side Access Doors /  
Marine Lights  
Dual Side Access Doors / Marine  
Lights  
C
DIGIT 38 — BELT GUARDS/  
BURGLAR BARS/MARINE  
LIGHTS  
0
1
2
3
None  
Belt Guards  
Burglar Bars  
Belt Guards / Burglar Bars  
RT-PRC031-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Data  
Table 3 General Data (All dimensions in inches)  
Casing A  
Casing B  
Casing C  
Supply Fans Std CFM  
Number/Size/Type  
Number of Motors  
HP Range  
1/25/ DW AF  
1
15 - 50  
1/32/ DW AF  
1
15 - 60  
1 / 36 DW AF  
1
15 - 75  
CFM Range/CFM at Max SP  
Total SP Range-(In. WG)  
16000-31000/22000  
7.5  
20000-38000/32000  
7.5  
23000-45000/40000  
7.5  
Exhaust Fans Std CFM  
Number/Size/Type  
Number of Motors  
HP Range  
CFM Range/CFM at Max SP  
ESP Range-(In. WG)  
1/25/ DW FC  
1/28/ DW FC  
1 / 32 DW FC  
1
7.5 - 25 hp  
10000-28000/24000  
2.5  
1
7.5 - 50 hp  
13000-35000/30000  
2.5  
1
15 - 60 hp  
23000-40000/40000  
2.5  
Exhaust Fans Low CFM  
Number/Size/Type  
Number of Motors  
HP Range  
CFM Range/CFM at Max SP  
ESP Range-(In. WG)  
-
-
-
-
-
1/25/ DW FC  
1/28/ DW FC  
1
7.5 - 25 hp  
10000-28000/24000  
2.5  
1
7.5 - 50 hp  
13000-35000/30000  
2.5  
Return Fans Std CFM  
Number/Size/Type  
Number of Motors  
HP Range  
CFM Range/CFM at Max SP  
ESP Range-(In. WG)  
1/36/ Plenum  
1
7.5 - 40 hp  
16000-31000  
2.5  
1 / 40 Plenum AF  
1 / 44.5 Plenum AF  
1
1
10 - 40 hp  
23000- 44000/39000  
2.5  
10 - 40 hp  
20000-38000  
2.5  
Electric Heat (60 Hz)  
kw  
90-265  
30 - 37.5 kW  
90-300  
30 - 37.5 kW  
140-300  
35 - 37.5 kW  
Circuit Capacity Steps  
Natural Gas Heat  
2-Stage Gas Heat  
Low Heat Input (MBH)  
Mid Heat Input/Output (MBH)  
High Heat Input/Output (MBH)  
Standard Heating Capacity Steps  
850  
1100  
1800  
2
850  
1100  
1800  
2
850  
1100  
1800  
2
Fully Modulating Steps  
Low Heat Input (MBH)  
Mid Heat Input (MBH)  
High Heat Input (MBH)  
10:1  
20:1  
20:1  
10:1  
20:1  
20:1  
10:1  
20:1  
20:1  
Heat Exchanger Material  
Chilled Water Coil  
Size (inches)  
Rows  
Stainless Steel  
Stainless Steel  
Stainless Steel  
42 x 115  
2, 4, 6, or 8  
42 x 115  
2, 4, 6, or 8  
42 x 115  
2, 4, 6, or 8  
Quantity  
2
2
2
Type  
Fin Series  
Turbulators  
5W, W, or WD  
80, 108, 144, or 168  
Turbulators Available  
5W, W, or WD  
80, 108, 144, or 168  
Turbulators Available  
5W, W, or WD  
80, 108, 144, or 168  
Turbulators Available  
Hot Water Coil  
Size  
33 x 88 x 2 rows  
33 x 88 x 2 rows  
33 x 88 x 2 rows  
Quantity  
2
5W, PrimaFlo  
122  
2
5W, PrimaFlo  
122  
2
5W, PrimaFlo  
122  
Type  
High Heat (fins/ft)  
Low Heat (fins/ft)  
80  
80  
80  
Steam Coil  
Size  
33 x 88 x 1 row  
33 x 88 x 1 row  
33 x 110 x 1 row  
Quantity  
2
NS, SigmaFlo  
112  
2
NS, SigmaFlo  
112  
2
NS, SigmaFlo  
112  
Type  
High Heat (fins/ft)  
Low Heat (fins/ft)  
62  
62  
62  
34  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
General Data  
Table 3 General Data (All dimensions in inches)  
Casing A  
Casing B  
Casing C  
Filters  
Standard 2" High Efficiency  
Throwaway Filters  
21 - 20X24X2  
5 - 12X24X2  
80  
21 - 20X24X2  
5 - 12X24X2  
80  
21 - 20X24X2  
5 - 12X24X2  
80  
Number/Size  
2
Face area (Ft )  
90-95% Bag Filters  
w/Prefilters  
21 - 20X24X19  
5 - 12X24X19  
80  
21 - 20X24X19  
5 - 12X24X19  
80  
21 - 20X24X19  
5 - 12X24X19  
80  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
21 - 20X24X2  
5 - 12X24X2  
21 - 20X24X2  
5 - 12X24X2  
21 - 20X24X2  
5 - 12X24X2  
90-95% Cartridge Filters w/  
Prefilters  
21 - 20X24X2  
5 - 12X24X2  
80  
21 - 20X24X2  
5 - 12X24X2  
80  
21 - 20X24X2  
5 - 12X24X2  
80  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
21 - 20X24X2  
5 - 12X24X2  
21 - 20X24X2  
5 - 12X24X2  
21 - 20X24X2  
5 - 12X24X2  
90-95% Low Pressure Drop  
Cartridge Filters  
w/Prefilters  
21 - 20X24X2  
5 - 12X24X2  
80  
21 - 20X24X2  
5 - 12X24X2  
80  
21 - 20X24X2  
5 - 12X24X2  
80  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
21 - 20X24X2  
5 - 12X24X2  
21 - 20X24X2  
5 - 12X24X2  
21 - 20X24X2  
5 - 12X24X2  
Final Filters  
90-95% Low Pressure Drop  
Cartridge Filters  
(i)  
w/Prefilters  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
15 - 24X24X4  
7 - 12X24X4  
15 - 24X24X4  
7 - 12X24X4  
15 - 24X24X4  
7 - 12X24X4  
90-95% Bag Filters  
(ii)  
w/Prefilters  
15 - 24X24X19  
7 - 12X24X19  
74  
15 - 24X24X19  
7 - 12X24X19  
74  
15 - 24X24X19  
7 - 12X24X19  
74  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
Final Filters  
90-95% Cartridge Filters  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
90-95% High Temp Cartridge  
Filters  
(iii)  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
Number/Size  
2
Face area (Ft )  
Prefilters  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
Number/Size  
HEPA Filters  
w/Prefilters  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
Final Filters  
High Temp HEPA Cartridge Filters w/  
(iii)  
Prefilters  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
15 - 24X24X12  
7 - 12X24X12  
74  
Number/Size  
2
Face area (Ft )  
Prefilters  
Number/Size  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
15 - 24X24X2  
7 - 12X24X2  
(i)  
High Airflow Applications of Cooling only/Steam and Hot Water Units require 4" High Efficiency Throw Away Prefilters with the 90-95% Low PD Cartridge  
Filter Option.  
(ii)  
Standard Airflow Applications of Cooling only/Steam and Hot Water Units include 2" High Efficiency Throw Away Prefilters with the 90-95% Bag and  
HEPA Filter Options.  
(iii) Gas/Electric Units require 2" High Efficiency High Temperature Rated Throwaway Prefilters with High Temperature Rated 90-95% Cartridge and HEPA  
filter options.  
RT-PRC031-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Data  
Table 4 Gas Heat Inputs/Input Ranges  
TWO-STAGE GAS HEAT  
Standard Gas  
Heat Input  
(MBH)  
Modulating  
Gas Heat  
Range (MBH)  
Low Gas Heat High Fire Heat  
Inputs (MBH)  
Input (MBH)  
850  
1100  
1800  
425  
550  
900  
850  
85-850  
55-1100  
90-1800  
1100  
1800  
Table 5 Economizer Outdoor Air Damper Leakage  
(i)  
(at rated airflow)  
Standard Damper  
20  
Optional “Low Leak" Damper  
Optional “Ultra Low Leak” Damper  
10 (Class 2 AMCA 511-99)  
4 (Class 1 AMCA 511-99)  
(i)  
Leakage/ft^2 at 1.0 in WC pressure difference  
36  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Adjustment Factors  
Table 6 Enthalpy of Saturated Air  
Wet Bulb  
Temperature  
Btu per Pound  
15.70  
16.66  
16.17  
16.66  
17.15  
17.65  
18.16  
18.68  
19.21  
19.75  
20.30  
20.86  
21.44  
22.02  
22.62  
23.22  
23.84  
24.48  
25.12  
25.78  
26.46  
27.15  
27.85  
28.57  
29.31  
30.06  
30.83  
31.62  
32.42  
33.25  
41  
43  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
Altitude/Temperature Correction  
Air Density  
Ratio (Density  
at New  
Air Density)  
Condition/Std.  
Air Handler LeavingAirTemperature (degrees F)  
Figure 18. Air Density Ratios  
70  
71  
72  
73  
74  
34.09  
34.95  
35.83  
36.74  
37.66  
Table 7 Cooling Capacity Altitude Correction Factors  
Altitude (Ft.)  
Sea Level  
1000  
0.99  
.98  
2000  
3000  
0.98  
.93  
4000  
0.97  
.91  
5000  
0.96  
.89  
6000  
0.95  
.87  
7000  
0.94  
.85  
Cooling Capacity Multiplier  
1.00  
1.00  
0.99  
.95  
Sensible Heat Ratio Correction Multiplier  
Table 8 Gas Heating Capacity Altitude Correction Factors  
Sea Level To 2000  
2001 to 2501 to 3501 to 4501 to 5501 to 6501 to  
2500  
3500  
4500  
5500  
6500  
7500  
Capacity Multiplier  
1.00  
.92  
.88  
.84  
.80  
.76  
.72  
RT-PRC031-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Performance Data—Chilled Water  
Coil Capacities  
Table 9 Chilled Water Coil Capacities—2 Row 5W  
Entering Dry Bulb/Wet Bulb 80/67 F  
Entering Water 45 F  
Water Temperature Rise F 10 F  
Without Turbulators  
With Turbulators  
Air  
Flow  
CFM  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
capacity capacity Leaving Leaving  
Capacity Capacity Leaving Leaving  
FPF  
80  
(MBH)  
179  
308  
428  
472  
256  
372  
503  
555  
294  
413  
552  
610  
348  
473  
623  
690  
394  
525  
684  
759  
433  
571  
739  
-
(MBH)  
179  
275  
351  
375  
250  
332  
421  
451  
283  
370  
469  
504  
333  
430  
543  
586  
379  
485  
612  
663  
421  
536  
676  
-
DB (F)  
69.9  
64.4  
60.1  
58.8  
68.7  
65.0  
60.9  
59.6  
68.8  
65.4  
61.5  
60.1  
69.2  
66.1  
62.4  
61.0  
69.6  
66.7  
63.2  
61.8  
70.0  
67.2  
63.9  
-
WB (F)  
63.7  
61.2  
58.7  
57.7  
63.2  
61.4  
59.2  
58.3  
63.2  
61.6  
59.6  
58.8  
63.3  
61.9  
60.2  
59.4  
63.5  
62.2  
60.7  
59.9  
63.6  
62.5  
61.1  
-
(ft H O) (MBH)  
(MBH)  
253  
320  
395  
420  
296  
375  
465  
498  
327  
413  
514  
552  
375  
473  
590  
638  
419  
529  
661  
717  
461  
581  
727  
-
DB (F)  
65.7  
61.9  
57.6  
56.2  
66.6  
63.0  
58.9  
57.4  
67.1  
63.7  
59.7  
58.2  
67.9  
64.7  
60.9  
59.3  
68.5  
65.5  
61.8  
60.3  
69.0  
66.1  
62.6  
-
WB (F)  
60.7  
58.8  
56.3  
55.2  
61.3  
59.5  
57.3  
56.3  
61.6  
60.0  
57.9  
56.9  
62.1  
60.6  
58.7  
57.8  
62.4  
61.1  
59.4  
58.5  
62.7  
61.5  
59.9  
-
(ft H O)  
2
2
16000  
20000  
23000  
28000  
33000  
38000  
43000  
45000  
35.7  
61.3  
85.4  
94.1  
51.0  
74.1  
100.3  
110.7  
58.6  
82.3  
110.0  
121.6  
69.4  
94.2  
124.2  
137.5  
78.4  
104.6  
136.4  
151.3  
86.4  
113.8  
147.3  
-
0.2  
0.6  
1.1  
1.3  
0.4  
0.8  
1.4  
1.7  
0.5  
1.0  
1.7  
2.1  
0.7  
1.3  
2.1  
2.6  
0.9  
1.6  
2.5  
3.1  
1.1  
1.8  
2.9  
-
333  
425  
540  
587  
380  
486  
618  
676  
412  
526  
670  
736  
460  
587  
748  
825  
503  
641  
816  
904  
542  
690  
878  
-
66.4  
84.7  
107.7  
117.0  
75.8  
96.8  
123.2  
134.7  
82.1  
104.9  
133.6  
146.7  
91.7  
117.1  
149.1  
164.5  
100.3  
127.8  
162.7  
180.2  
108.1  
137.6  
174.9  
-
1.8  
2.6  
3.8  
4.3  
2.2  
3.2  
4.7  
5.5  
2.5  
3.6  
5.4  
6.4  
2.9  
4.3  
6.5  
7.8  
3.4  
5.0  
7.6  
9.1  
3.8  
5.7  
8.6  
-
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
469  
612  
-
461  
585  
-
70.3  
67.7  
-
63.8  
62.7  
-
93.5  
122.0  
-
1.3  
2.1  
-
578  
735  
-
500  
630  
-
69.4  
66.7  
-
63.0  
61.9  
-
115.2  
146.4  
-
4.2  
6.3  
-
108  
144  
168  
80  
-
-
-
-
-
-
-
-
-
-
-
-
482  
628  
-
476  
603  
-
70.4  
67.8  
-
63.8  
62.8  
-
96.2  
125.1  
-
1.3  
2.2  
-
591  
751  
-
515  
649  
-
69.6  
66.9  
-
63.1  
62.0  
-
117.9  
149.8  
-
4.4  
6.6  
-
108  
144  
168  
-
-
-
-
-
-
-
-
-
-
-
-
38  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data—Chilled Water Coil Capacities  
Table 10 Chilled Water Coil Capacities—4 Row W  
Entering Dry Bulb/Wet Bulb 80/67 F  
Entering Water 45 F  
Water Temperature Rise F 10 F  
Without Turbulators  
With Turbulators  
Air  
Flow  
CFM  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
(ft H O)  
2
capacity capacity Leaving Leaving  
Capacity Capacity Leaving Leaving  
FPF  
80  
(MBH)  
523  
634  
746  
785  
615  
746  
885  
937  
677  
823  
981  
1044  
771  
941  
1128  
1208  
856  
1048  
1262  
1360  
934  
1147  
1386  
-
(MBH)  
378  
443  
500  
518  
452  
531  
604  
628  
504  
593  
678  
707  
586  
692  
795  
833  
664  
785  
906  
953  
737  
873  
1011  
-
DB (F)  
58.6  
54.9  
51.6  
50.6  
59.5  
55.9  
52.6  
51.5  
60.1  
56.6  
53.3  
52.1  
61.0  
57.6  
54.3  
53.0  
61.8  
58.4  
55.1  
53.8  
62.4  
59.2  
55.9  
-
WB (F)  
56.6  
54.1  
51.5  
50.5  
57.3  
55.0  
52.4  
51.4  
57.8  
55.5  
53.0  
52.0  
58.4  
56.3  
53.9  
52.8  
59.0  
57.0  
54.6  
53.6  
59.4  
57.5  
55.3  
-
(ft H O) (MBH)  
(MBH)  
400  
466  
525  
542  
476  
558  
632  
658  
530  
622  
709  
740  
614  
724  
830  
870  
694  
820  
945  
994  
769  
911  
1053  
-
DB (F)  
57.3  
53.6  
50.3  
49.3  
58.4  
54.7  
51.3  
50.2  
59.1  
55.5  
52.0  
50.8  
60.1  
56.5  
53.1  
51.8  
60.9  
57.5  
54.0  
52.7  
61.7  
58.3  
54.9  
-
WB (F)  
55.4  
52.9  
50.1  
49.2  
56.3  
53.8  
51.1  
50.1  
56.8  
54.4  
51.8  
50.7  
57.6  
55.3  
52.8  
51.6  
58.2  
56.0  
53.6  
52.4  
58.7  
56.7  
54.3  
-
2
16000  
20000  
23000  
28000  
33000  
38000  
43000  
45000  
104.3  
126.4  
148.7  
156.4  
122.6  
148.7  
176.3  
186.8  
134.9  
164.1  
195.5  
208.0  
153.6  
187.6  
224.8  
240.9  
170.6  
208.9  
251.6  
271.0  
186.1  
228.5  
276.2  
-
2.5  
3.5  
4.7  
5.2  
3.3  
4.7  
6.4  
7.1  
4.0  
5.6  
7.7  
8.7  
5.0  
7.2  
10.0  
11.3  
6.0  
8.7  
12.3  
14.1  
7.1  
10.3  
14.6  
-
577  
689  
802  
840  
674  
810  
952  
1005  
740  
894  
1055  
1119  
841  
1021  
1214  
1296  
932  
1136  
1357  
1457  
1016  
1241  
1488  
-
115.1  
137.3  
159.8  
167.4  
134.3  
161.5  
189.7  
200.2  
147.5  
178.1  
210.3  
223.1  
167.6  
203.4  
241.9  
258.3  
185.8  
226.4  
270.5  
290.4  
202.5  
247.3  
296.6  
-
7.4  
10.0  
13.0  
14.1  
9.6  
108  
144  
168  
80  
108  
144  
168  
80  
13.2  
17.5  
19.3  
11.3  
15.7  
21.1  
23.4  
14.1  
19.9  
27.0  
30.4  
16.9  
24.0  
33.1  
37.6  
19.7  
28.2  
39.0  
-
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
1006  
1238  
-
806  
958  
-
63.0  
59.8  
-
59.8  
58.0  
-
200.6  
246.7  
-
8.1  
11.8  
-
1093  
1338  
-
840  
997  
-
62.3  
59.0  
-
59.1  
57.2  
-
217.9  
266.7  
-
22.4  
32.2  
-
108  
144  
168  
80  
-
-
-
-
-
-
-
-
-
-
-
-
1034  
1272  
-
833  
990  
-
63.2  
60.0  
-
60.0  
58.2  
-
206.0  
253.6  
-
8.5  
12.5  
-
1123  
1375  
-
867  
1030  
-
62.5  
59.2  
-
59.3  
57.4  
-
223.7  
274.0  
-
23.5  
33.8  
-
108  
144  
168  
-
-
-
-
-
-
-
-
-
-
-
-
RT-PRC031-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data—Chilled Water Coil Capacities  
Table 11 Chilled Water Coil Capacities—6 Row WD  
Entering Dry Bulb/Wet Bulb 80/67 F  
Entering Water 45 F  
Water Temperature Rise F 10 F  
Without Turbulators  
With Turbulators  
Air  
Flow  
CFM  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
(ft H O)  
2
capacity capacity Leaving Leaving  
Capacity Capacity Leaving Leaving  
FPF  
80  
(MBH)  
561  
676  
777  
809  
692  
826  
950  
993  
780  
929  
1070  
1121  
913  
1086  
1255  
1321  
1032  
1229  
1423  
1504  
1141  
1359  
1578  
-
(MBH)  
413  
470  
515  
528  
510  
578  
634  
652  
577  
655  
719  
742  
684  
776  
856  
883  
784  
891  
985  
1019  
879  
1000  
1108  
-
DB (F)  
56.6  
53.4  
50.8  
50.0  
56.9  
53.8  
51.2  
50.4  
57.2  
54.2  
51.6  
50.8  
57.8  
54.9  
52.3  
51.4  
58.5  
55.5  
52.9  
52.0  
59.0  
56.1  
53.6  
-
WB (F)  
55.8  
53.2  
50.7  
49.9  
56.0  
53.5  
51.1  
50.3  
56.2  
53.9  
51.5  
50.7  
56.7  
54.4  
52.2  
51.3  
57.1  
55.0  
52.8  
51.9  
57.6  
55.5  
53.4  
-
(ft H O) (MBH)  
(MBH)  
443  
497  
539  
552  
538  
605  
659  
677  
605  
682  
746  
768  
712  
805  
885  
913  
813  
921  
1017  
1052  
908  
1032  
1143  
-
DB (F)  
54.9  
51.8  
49.5  
48.7  
55.6  
52.6  
50.1  
49.3  
56.1  
53.1  
50.6  
49.7  
56.9  
53.9  
51.3  
50.4  
57.7  
54.7  
52.1  
51.1  
58.3  
55.4  
52.7  
-
WB (F)  
54.1  
51.7  
49.4  
48.6  
54.7  
52.3  
50.0  
49.2  
55.1  
52.8  
50.5  
49.6  
55.8  
53.5  
51.2  
50.3  
56.4  
54.2  
52.0  
51.0  
56.9  
54.8  
52.6  
-
2
16000  
20000  
23000  
28000  
33000  
38000  
43000  
45000  
111.9  
134.7  
154.9  
161.2  
137.8  
164.6  
189.4  
197.8  
155.4  
185.2  
213.3  
223.5  
181.9  
216.5  
250.1  
263.2  
205.7  
244.9  
283.7  
299.7  
227.5  
270.9  
314.6  
-
1.1  
1.6  
2.1  
2.2  
1.6  
2.3  
3.0  
3.3  
2.1  
2.9  
3.8  
4.1  
2.8  
3.9  
5.1  
5.6  
3.5  
4.9  
6.5  
7.2  
4.3  
5.9  
7.9  
-
635  
739  
832  
860  
762  
890  
1008  
1048  
849  
995  
1131  
1181  
983  
1156  
1323  
1388  
1105  
1304  
1499  
1581  
1217  
1439  
1663  
-
126.6  
147.3  
165.8  
171.5  
151.8  
177.3  
200.9  
208.9  
169.2  
198.2  
225.5  
235.3  
195.9  
230.4  
263.7  
276.7  
220.2  
259.8  
298.8  
315.0  
242.5  
286.9  
331.5  
-
2.3  
2.9  
3.5  
3.7  
3.0  
3.9  
4.9  
5.2  
3.6  
4.8  
6.0  
6.4  
4.7  
6.2  
7.9  
8.6  
5.7  
7.7  
9.9  
10.9  
6.8  
9.2  
12.0  
-
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
1242  
1479  
-
969  
1104  
-
59.6  
56.7  
-
58.0  
56.0  
-
247.4  
294.8  
-
5.0  
7.0  
-
1320  
1566  
-
1000  
1138  
-
58.9  
56.0  
-
57.3  
55.3  
-
263.1  
312.0  
-
7.9  
10.7  
-
108  
144  
168  
80  
-
-
-
-
-
-
-
-
-
-
-
-
1279  
1525  
-
1004  
1144  
-
59.8  
56.9  
-
58.1  
56.2  
-
255.0  
303.9  
-
5.3  
7.4  
-
1359  
1614  
-
1035  
1180  
-
59.1  
56.2  
-
57.5  
55.5  
-
270.9  
321.7  
-
8.3  
11.3  
-
108  
144  
168  
-
-
-
-
-
-
-
-
-
-
-
-
40  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Chilled Water Coil Capacities  
Table 12 Chilled Water Coil Capacities—8 Row WD  
Entering Dry Bulb/Wet Bulb 80/67 F  
Entering Water 45 F  
Water Temperature Rise F 10 F  
Without Turbulators  
With Turbulators  
Air  
Flow  
CFM  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
Total  
Sensible  
Water  
Flow  
GPM  
Water  
PD  
capacity capacity Leaving Leaving  
Capacity Capacity Leaving Leaving  
FPF  
80  
(MBH)  
712  
(MBH)  
483  
526  
559  
569  
592  
647  
690  
704  
671  
735  
785  
802  
795  
874  
936  
960  
912  
1006  
1082  
1112  
1025  
1133  
1223  
-
DB (F)  
52.6  
50.2  
48.3  
47.7  
53.1  
50.6  
48.7  
48.1  
53.6  
51.0  
49.1  
48.4  
54.3  
51.7  
49.7  
48.9  
54.9  
52.3  
50.3  
49.4  
55.5  
53.0  
50.8  
-
WB (F)  
52.3  
50.1  
48.2  
47.6  
52.8  
50.5  
48.6  
48.0  
53.1  
50.9  
49.0  
48.3  
53.8  
51.6  
49.6  
48.8  
54.3  
52.2  
50.2  
49.3  
54.9  
52.7  
50.7  
-
(ft H O) (MBH)  
(MBH)  
519  
559  
587  
594  
630  
683  
721  
733  
710  
773  
820  
835  
837  
917  
978  
1000  
958  
1055  
1131  
1160  
1074  
1187  
1278  
-
DB (F)  
50.6  
48.3  
46.7  
46.3  
51.4  
49.0  
47.3  
46.7  
52.0  
49.5  
47.7  
47.1  
52.9  
50.3  
48.3  
47.6  
53.7  
51.0  
48.9  
48.1  
54.4  
51.7  
49.5  
-
WB (F)  
50.3  
48.2  
46.6  
46.2  
51.1  
48.9  
47.2  
46.6  
51.6  
49.4  
47.6  
47.0  
52.4  
50.2  
48.2  
47.5  
53.1  
50.9  
48.8  
48.0  
53.7  
51.5  
49.4  
-
(ft H O)  
2
2
16000  
20000  
23000  
28000  
33000  
38000  
43000  
45000  
141.9  
160.1  
174.9  
179.1  
172.6  
195.5  
214.6  
220.7  
194.0  
220.4  
242.9  
250.5  
227.1  
259.1  
287.3  
297.6  
257.4  
294.9  
329.0  
342.3  
285.4  
328.4  
368.4  
-
2.0  
2.5  
3.0  
3.1  
2.9  
3.7  
4.4  
4.6  
3.6  
4.6  
5.5  
5.9  
4.9  
6.3  
7.6  
8.1  
6.2  
8.0  
9.8  
10.6  
7.5  
9.8  
12.2  
-
795  
876  
158.5  
174.5  
186.6  
189.9  
190.1  
211.4  
228.2  
233.3  
212.3  
237.5  
258.2  
264.8  
247.0  
278.8  
305.8  
315.3  
279.3  
317.4  
350.7  
363.3  
309.4  
353.7  
393.3  
-
4.9  
5.8  
6.5  
6.7  
6.7  
8.1  
9.2  
9.6  
8.2  
9.9  
11.5  
12.0  
10.7  
13.2  
15.6  
16.5  
13.3  
16.7  
20.0  
21.3  
15.9  
20.3  
24.6  
-
108  
144  
168  
80  
803  
877  
936  
899  
953  
866  
954  
108  
144  
168  
80  
981  
1060  
1145  
1171  
1065  
1192  
1295  
1329  
1239  
1399  
1534  
1582  
1401  
1593  
1760  
1823  
1552  
1774  
1973  
-
1077  
1107  
973  
108  
144  
168  
80  
1106  
1219  
1257  
1139  
1300  
1442  
1493  
1291  
1479  
1651  
1717  
1432  
1648  
1849  
-
108  
144  
168  
80  
108  
144  
168  
80  
108  
144  
168  
80  
1563  
1806  
-
1132  
1256  
-
56.1  
53.5  
-
55.3  
53.3  
-
311.5  
360.0  
-
8.9  
11.7  
-
1694  
1946  
-
1186  
1315  
-
55.0  
52.3  
-
54.2  
52.0  
-
337.6  
387.8  
-
18.7  
24.0  
-
108  
144  
168  
80  
-
-
-
-
-
-
-
-
-
-
-
-
1613  
1868  
-
1174  
1304  
-
56.3  
53.7  
-
55.5  
53.4  
-
321.5  
372.2  
-
9.4  
12.4  
-
1748  
2012  
-
1230  
1365  
-
55.2  
52.5  
-
54.4  
52.2  
-
348.5  
401.0  
-
19.8  
25.5  
-
108  
144  
168  
-
-
-
-
-
-
-
-
-
-
-
-
RT-PRC031-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan  
without Inlet Guide Vanes (with or  
without Variable Frequency Drive)  
Table 13 Supply Fan Performance STANDARD CFM — Casing A (25")  
CFM  
Total Static Pressure  
1.00 1.25  
RPM  
Std.  
0.25  
RPM BHP  
0.50  
RPM  
0.75  
RPM  
1.50  
1.75  
2.00  
RPM BHP  
1234 10.38  
Air  
BHP  
6.81  
7.99  
9.31  
BHP  
7.52  
8.74  
BHP  
8.14  
9.46  
RPM  
1152  
1208  
BHP  
8.58  
9.98  
RPM  
1177  
BHP  
RPM  
1205  
BHP  
(i)  
16000 1030  
6.16  
7.30  
8.57  
9.99  
1062  
1121  
1180  
1095  
1152  
1126  
1182  
9.05  
9.67  
17000 1090  
18000 1151  
19000 1211  
1232 10.47 1256 10.99 1282 11.66  
1209 10.07 1238 10.86 1265 11.57 1288 12.05 1311 12.57 1333 13.13  
1239 10.77 1266 11.55 1294 12.41 1321 13.20 1345 13.82 1367 14.34 1388 14.89  
20000 1272 11.57 1299 12.39 1325 13.20 1351 14.08 1377 14.96 1402 15.76 1423 16.31 1444 16.87  
21000 1333 13.30 1359 14.16 1383 15.02 1408 15.91 1433 16.85 1458 17.74 1480 18.48 1500 19.04  
22000 1394 15.21 1419 16.11 1443 17.01 1466 17.90 1490 18.90 1513 19.85 1536 20.76 1556 21.42  
23000 1455 17.28 1479 18.23 1502 19.17 1524 20.11 1547 21.12 1570 22.14 1592 23.11 1613 24.02  
24000 1516 19.55 1539 20.54 1561 21.52 1583 22.49 1604 23.50 1626 24.58 1648 25.64 1669 26.63  
25000 1578 22.01 1600 23.04 1621 24.07 1642 25.09 1662 26.09 1683 27.22 1705 28.33 1725 29.42  
26000 1639 24.67 1660 25.74 1681 26.81 1701 27.87 1721 28.93 1741 30.04 1762 31.22 1781 32.36  
27000 1701 27.54 1721 28.66 1741 29.77 1760 30.88 1780 31.97 1798 33.06 1818 34.29 1838 35.51  
28000 1762 30.62 1782 31.78 1801 32.94 1820 34.09 1838 35.22 1857 36.35 1876 37.58 1895 38.83  
29000 1824 33.94 1843 35.14 1861 36.34 1880 37.53 1898 38.71 1915 39.88 1933 41.08 1952 42.41  
30000 1885 37.48 1904 38.73 1922 39.96 1939 41.19 1957 42.42 1974 43.64 1991 44.86 2009 46.19  
31000 1947 41.27 1965 42.56 1982 43.83 2000 45.11  
CFM  
Total Static Pressure  
3.00 3.25  
RPM BHP RPM BHP  
11.09 1289 11.80 1315 12.50 1341 13.22 1366 13.95 1391 14.67 1415 15.41 1438 16.13  
Std.  
2.25  
RPM BHP  
2.50  
RPM BHP  
2.75  
RPM BHP  
3.50  
RPM BHP  
3.75  
RPM BHP  
4.00  
RPM BHP  
Air  
(ii)  
16000 1262  
17000 1309 12.40 1337 13.18 1362 13.92 1388 14.68 1412 15.45 1435 16.20 1459 17.00 1481 17.74  
18000 1359 13.87 1385 14.67 1410 15.48 1435 16.28 1459 17.08 1481 17.86 1505 18.68 1527 19.49  
19000 1410 15.51 1433 16.28 1458 17.13 1482 17.97 1506 18.84 1528 19.65 1551 20.50 1573 21.36  
20000 1464 17.45 1484 18.09 1507 18.92 1530 19.80 1554 20.70 1577 21.62 1599 22.50 1619 23.34  
21000 1519 19.63 1539 20.26 1558 20.94 1579 21.79 1602 22.73 1623 23.63 1645 24.58 1667 25.53  
22000 1576 22.03 1594 22.65 1612 23.31 1631 24.00 1652 24.92 1672 25.86 1694 26.83 1714 27.80  
23000 1632 24.63 1650 25.27 1668 25.93 1685 26.61 1703 27.34 1722 28.23 1742 29.23 1763 30.28  
24000 1688 27.48 1706 28.13 1724 28.79 1740 29.47 1757 30.19 1775 30.97 1792 31.86 1811 32.87  
25000 1745 30.41 1763 31.23 1780 31.89 1796 32.59 1813 33.31 1828 34.03 1845 34.85 1863 35.76  
26000 1801 33.44 1820 34.48 1836 35.23 1853 35.94 1868 36.66 1884 37.41 1899 38.16 1916 39.02  
27000 1857 36.66 1876 37.79 1893 38.83 1909 39.58 1925 40.30 1940 41.05 1956 41.84 1970 42.62  
28000 1913 40.07 1931 41.26 1949 42.42 1967 43.48 1982 44.22 1996 44.95  
29000 1970 43.70 1987 44.93 2005 46.18  
CFM  
Std.  
Air  
Total Static Pressure  
5.00 5.25  
RPM BHP RPM BHP  
4.25  
RPM BHP  
4.50  
RPM BHP  
4.75  
RPM BHP  
5.50  
RPM BHP  
5.75  
RPM BHP  
6.00  
RPM BHP  
16000 1461 16.88 1484 17.60 1508 18.39 1530 19.15 1551 19.86 1575 20.69 1598 21.47 1620 22.29  
17000 1504 18.52 1527 19.34 1549 20.13 1569 20.86 1591 21.67 1613 22.46 1633 23.25 1656 24.12  
18000 1548 20.29 1571 21.14 1591 21.94 1613 22.78 1633 23.61 1655 24.47 1674 25.26 1694 26.08  
19000 1595 22.23 1615 23.05 1636 23.91 1656 24.77 1676 25.66 1698 26.58 1717 27.44 1737 28.32  
20000 1640 24.22 1661 25.15 1681 26.02 1701 26.94 1722 27.89 1741 28.77 1760 29.69 1779 30.64  
21000 1687 26.43 1707 27.37 1727 28.31 1746 29.23 1766 30.18 1786 31.18 1804 32.10 1823 33.05  
22000 1736 28.82 1755 29.78 1774 30.73 1793 31.71 1813 32.73 1831 33.67 1849 34.64 1867 35.65  
23000 1782 31.26 1803 32.35 1822 33.35 1841 34.34 1859 35.37 1878 36.43 1895 37.40 1913 38.40  
24000 1831 33.92 1851 35.02 1869 36.03 1889 37.15 1908 38.24 1926 39.31 1943 40.33 1960 41.39  
25000 1880 36.77 1899 37.87 1918 38.96 1936 40.08 1954 41.17 1973 42.37 1991 43.46 2007 44.51  
26000 1932 39.88 1949 40.93 1967 42.08 1985 43.21 2003 44.37  
27000 1985 43.44 2000 44.30  
42  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
Table 13 Supply Fan Performance STANDARD CFM — Casing A (25")  
CFM  
Std.  
Air  
Total Static Pressure  
7.00 7.25  
RPM BHP RPM BHP  
6.25  
RPM BHP  
6.50  
RPM BHP  
6.75  
RPM BHP  
7.50  
RPM BHP  
7.75  
RPM BHP  
8.00  
RPM BHP  
16000 1644 23.14 1665 23.93 1687 24.77 1710 25.65 1733 26.56 1754 27.40 1776 28.28 1798 29.18  
17000 1676 24.92 1697 25.75 1719 26.62 1741 27.52 1762 28.41 1784 29.33 1805 30.23 1826 31.17  
18000 1714 26.94 1735 27.82 1755 28.69 1775 29.58 1794 30.44 1814 31.34 1835 32.27 1855 33.23  
19000 1755 29.18 1775 30.07 1793 30.92 1812 31.81 1831 32.72 1851 33.67 1871 34.65 1888 35.51  
20000 1797 31.50 1816 32.45 1836 33.43 1853 34.30 1871 35.21 1890 36.21 1907 37.10 1925 38.01  
21000 1841 34.03 1859 34.98 1878 35.96 1895 36.90 1914 37.94 1930 38.85 1947 39.79 1964 40.76  
22000 1886 36.69 1904 37.71 1921 38.67 1938 39.67 1956 40.70 1974 41.76 1991 42.76 2008 43.79  
23000 1930 39.43 1948 40.50 1967 41.61 1983 42.58 2000 43.68  
24000 1978 42.49 1995 43.54  
CFM  
Std.  
Air  
Total Static Pressure  
9.00  
8.25  
RPM BHP  
8.50  
RPM BHP  
8.75  
RPM BHP  
RPM  
BHP  
16000 1820 30.13 1843 31.11 1863 31.99 1887 33.04  
17000 1846 32.07 1867 33.02 1887 33.92 1910 35.00  
18000 1877 34.22 1895 35.11 1914 36.04 1935 37.08  
19000 1909 36.55 1927 37.47 1946 38.43 1965 39.41  
20000 1944 39.03 1962 40.00 1980 40.99 1997 41.93  
21000 1982 41.75 2000 42.77  
Notes:  
1. Supply fan performance table includes internal resistance of air handler. For total  
static pressure determination, system external static pressure must be added to  
appropriate component sp drops (chilled water coil, filters, optional economizer,  
optional heating system).  
2. Maximum SP leaving the air handler is 5.5" H20 positive.  
(i)  
(ii)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
RT-PRC031-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
25" Supply Fan w/o IGV  
12  
11  
10  
9
2000 RPM  
1900 RPM  
8
1800 RPM  
1700 RPM  
7
1600 RPM  
1500 RPM  
6
5
1400 RPM  
1300 RPM  
4
1200 RPM  
1100 RPM  
3
1000 RPM  
900 RPM  
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
Volumetric Airflow Rate(CFM)  
Table 14 Supply Fan Performance STANDARD CFM — Casing A (25")  
44  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
Table 15 Supply Fan Performance STANDARD CFM —Casing B (32")  
CFM  
Total Static Pressure  
1.00 1.25  
RPM  
Std.  
0.25  
0.50  
0.75  
1.50  
RPM  
1.75  
RPM  
2.00  
RPM  
Air  
RPM  
BHP  
7.51  
RPM  
BHP  
8.48  
RPM  
BHP  
9.46  
BHP  
10.14  
11.29  
12.53  
13.85  
15.16  
16.57  
RPM  
854  
882  
910  
939  
967  
996  
BHP  
10.82  
11.98  
13.22  
14.57  
16.03  
BHP  
11.73  
12.78  
13.98  
15.31  
BHP  
12.74  
13.82  
14.95  
BHP  
13.77  
14.90  
16.08  
(i)  
23000 752  
781  
809  
839  
868  
898  
928  
957  
987  
809  
837  
865  
894  
922  
951  
980  
832  
861  
889  
918  
946  
975  
879  
904  
931  
958  
986  
904  
929  
953  
978  
928  
953  
977  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
782  
8.45  
9.44  
10.49  
11.59  
12.76  
14.01  
15.34  
813  
843  
874  
904  
935  
965  
996  
9.46  
10.47  
11.62  
12.84  
14.14  
15.54  
10.56  
11.73  
13.00  
14.35  
15.80  
16.19 1000 17.30  
16.79 1005 17.61 1025 18.64  
17.60 1014 18.35 1033 19.18 1051 20.08  
16.75 1003 18.04 1024 19.23 1043 20.04 1061 20.86 1078 21.76  
17.03 1009 18.26 1031 19.61 1052 20.86 1072 21.86 1089 22.67 1106 23.56  
17.35 1018 18.62 1038 19.89 1060 21.27 1081 22.61 1100 23.77 1117 24.61 1134 25.48  
32000 1027 19.00 1048 20.31 1068 21.62 1089 23.01 1109 24.42 1129 25.73 1146 26.66 1162 27.53  
33000 1057 20.75 1078 22.11 1098 23.46 1117 24.85 1138 26.34 1157 27.72 1174 28.84 1190 29.74  
34000 1088 22.61 1108 24.00 1127 25.40 1146 26.81 1166 28.35 1185 29.78 1203 31.16 1219 32.07  
35000 1119 24.58 1138 26.02 1157 27.44 1176 28.86 1195 30.45 1214 31.98 1231 33.40 1248 34.54  
36000 1150 26.66 1169 28.14 1187 29.60 1205 31.07 1223 32.66 1242 34.25 1259 35.76 1276 37.13  
37000 1181 28.86 1199 30.38 1217 31.90 1235 33.40 1252 35.00 1271 36.66 1288 38.26 1305 39.74  
38000 1212 31.17 1230 32.74 1247 34.30 1264 35.85 1281 37.42 1299 39.14 1316 40.83 1333 42.40  
39000 1243 33.61 1260 35.22 1277 36.82 1294 38.40 1311 40.00 1328 41.77 1345 43.47 1361 45.13  
40000 1274 36.17 1291 37.82 1308 39.48 1324 41.10 1340 42.73 1357 44.49 1373 46.27 1390 48.02  
41000 1305 38.87 1321 40.56 1338 42.25 1354 43.91 1370 45.59 1386 47.37 1402 49.20 1418 50.98  
42000 1336 41.70 1352 43.44 1368 45.17 1384 46.89 1399 48.58 1415 50.36 1431 52.26 1446 54.12  
43000 1367 44.66 1383 46.44 1398 48.21 1414 49.97 1429 51.72 1444 53.48 1459 55.41 1475 57.34  
44000 1398 47.77 1413 49.60 1429 51.40 1444 53.20 1459 55.00 1473 56.77 1488 58.70  
45000 1429 51.01 1444 52.88 1459 54.73 1474 56.58 1488 58.40  
CFM  
Std.  
Total Static Pressure  
3.00 3.25  
RPM BHP RPM BHP  
16.85 1017 17.93 1037 18.95 1058 20.03 1078 21.09 1097 22.13  
2.25  
2.50  
2.75  
3.50  
RPM BHP  
3.75  
RPM BHP  
4.00  
RPM BHP  
Air  
RPM  
BHP  
14.80  
15.97  
RPM  
BHP  
RPM  
BHP  
23000  
24000  
25000  
952  
975  
999  
974  
997  
15.81  
995  
17.01 1018 18.07 1039 19.18 1060 20.29 1079 21.36 1099 22.49 1118 23.58  
17.18 1021 18.28 1042 19.41 1062 20.50 1082 21.64 1102 22.80 1121 23.95 1140 25.11  
26000 1023 18.47 1045 19.65 1065 20.76 1086 21.95 1105 23.11 1124 24.29 1144 25.50 1162 26.68  
27000 1047 19.82 1069 21.06 1089 22.24 1109 23.42 1128 24.63 1147 25.83 1165 27.05 1184 28.34  
28000 1072 21.27 1092 22.50 1113 23.79 1133 25.03 1152 26.27 1171 27.52 1188 28.75 1207 30.05  
29000 1097 22.82 1117 24.09 1137 25.36 1157 26.67 1176 27.97 1194 29.24 1212 30.52 1229 31.82  
30000 1123 24.49 1142 25.75 1161 27.05 1181 28.38 1200 29.74 1218 31.08 1235 32.37 1253 33.72  
31000 1150 26.42 1168 27.54 1186 28.86 1205 30.22 1224 31.60 1242 33.00 1259 34.35 1276 35.71  
32000 1178 28.47 1194 29.50 1211 30.71 1229 32.08 1248 33.53 1265 34.94 1284 36.43 1301 37.85  
33000 1206 30.67 1222 31.68 1237 32.77 1254 34.10 1272 35.56 1290 37.04 1307 38.53 1325 40.02  
34000 1234 33.03 1249 34.00 1264 35.06 1280 36.27 1297 37.68 1314 39.17 1331 40.73 1348 42.21  
35000 1263 35.48 1277 36.47 1292 37.52 1306 38.60 1322 39.98 1339 41.47 1356 43.03 1372 44.59  
36000 1291 38.10 1306 39.10 1320 40.13 1334 41.25 1348 42.39 1364 43.88 1380 45.44 1396 46.99  
37000 1320 40.85 1334 41.87 1348 42.91 1362 44.00 1375 45.12 1390 46.42 1405 47.98 1421 49.60  
38000 1348 43.78 1362 44.78 1376 45.83 1390 46.93 1403 48.02 1416 49.25 1431 50.64 1446 52.24  
39000 1377 46.73 1391 47.84 1404 48.90 1418 49.98 1431 51.09 1444 52.29 1457 53.57 1472 55.12  
40000 1405 49.66 1420 51.09 1433 52.13 1446 53.24 1459 54.36 1471 55.52 1484 56.75 1497 58.06  
41000 1434 52.74 1449 54.38 1462 55.55 1474 56.64 1487 57.76 1500 58.95  
42000 1462 55.91 1477 57.62 1490 59.11  
43000 1490 59.21  
RT-PRC031-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
Table 15 Supply Fan Performance STANDARD CFM —Casing B (32")  
CFM  
Std.  
Air  
Total Static Pressure  
5.00 5.25  
RPM BHP RPM BHP  
4.25  
RPM BHP  
4.50  
RPM BHP  
4.75  
RPM BHP  
5.50  
RPM BHP  
5.75  
RPM BHP  
6.00  
RPM BHP  
23000 1117 23.23 1138 24.39 1157 25.52 1177 26.71 1197 27.85 1216 29.06 1237 30.34 1255 31.57  
24000 1138 24.74 1157 25.86 1175 26.99 1194 28.17 1213 29.36 1233 30.60 1251 31.78 1270 33.09  
25000 1158 26.23 1177 27.41 1194 28.53 1213 29.77 1231 30.94 1250 32.24 1268 33.46 1286 34.73  
26000 1180 27.86 1198 29.04 1215 30.22 1233 31.46 1250 32.69 1268 33.97 1286 35.24 1303 36.49  
27000 1202 29.58 1219 30.77 1237 32.02 1254 33.31 1271 34.53 1288 35.80 1305 37.13 1321 38.35  
28000 1224 31.30 1242 32.61 1259 33.92 1275 35.15 1292 36.42 1308 37.75 1325 39.05 1342 40.41  
29000 1246 33.13 1263 34.43 1281 35.80 1297 37.09 1313 38.44 1330 39.83 1345 41.11 1361 42.44  
30000 1270 35.09 1286 36.39 1303 37.83 1319 39.17 1336 40.58 1351 41.88 1367 43.31 1383 44.71  
31000 1293 37.07 1310 38.50 1325 39.84 1341 41.25 1358 42.72 1374 44.17 1389 45.58 1404 46.95  
32000 1316 39.21 1333 40.62 1348 42.02 1364 43.49 1381 45.03 1396 46.44 1411 47.92 1427 49.45  
33000 1340 41.44 1357 42.92 1373 44.39 1388 45.83 1403 47.33 1418 48.81 1434 50.35 1448 51.84  
34000 1365 43.77 1380 45.24 1396 46.77 1411 48.27 1427 49.84 1441 51.28 1457 52.87 1471 54.43  
35000 1389 46.21 1405 47.75 1420 49.26 1435 50.83 1450 52.36 1465 53.96 1479 55.41 1494 57.12  
36000 1412 48.60 1429 50.29 1444 51.86 1460 53.50 1473 55.00 1488 56.56 1503 58.28 1517 59.84  
37000 1437 51.20 1452 52.86 1469 54.60 1483 56.20 1498 57.87 1512 59.38  
38000 1461 53.92 1476 55.56 1492 57.26 1507 59.04  
39000 1486 56.67 1501 58.39  
40000 1511 59.68  
CFM  
Std.  
Air  
Total Static Pressure  
7.00 7.25  
RPM BHP RPM BHP  
6.25  
RPM BHP  
6.50  
RPM BHP  
6.75  
RPM BHP  
7.50  
RPM BHP  
7.75  
RPM BHP  
8.00  
RPM BHP  
23000 1275 32.85 1295 34.21 1313 35.47 1332 36.79 1352 38.18 1369 39.44 1390 40.95 1408 42.32  
24000 1288 34.33 1308 35.71 1326 37.00 1344 38.35 1363 39.76 1380 41.05 1400 42.58 1418 43.99  
25000 1305 36.07 1322 37.32 1340 38.63 1358 40.01 1376 41.45 1393 42.76 1413 44.33 1430 45.76  
26000 1321 37.79 1337 39.07 1355 40.41 1373 41.80 1391 43.26 1407 44.61 1424 46.00 1441 47.46  
27000 1338 39.62 1355 41.03 1371 42.32 1389 43.76 1406 45.15 1423 46.61 1440 48.03 1456 49.52  
28000 1358 41.74 1373 43.03 1389 44.37 1407 45.85 1422 47.20 1438 48.60 1454 50.04 1471 51.54  
29000 1377 43.83 1394 45.26 1408 46.57 1423 47.91 1440 49.40 1456 50.84 1471 52.22 1487 53.77  
30000 1398 46.06 1413 47.46 1429 48.91 1444 50.31 1459 51.76 1475 53.25 1488 54.58 1505 56.17  
30000 1398 46.06 1413 47.46 1429 48.91 1444 50.31 1459 51.76 1475 53.25 1488 54.58 1505 56.17  
31000 1420 48.46 1434 49.82 1449 51.23 1464 52.68 1479 54.19 1493 55.63 1508 57.11  
32000 1441 50.83 1455 52.26 1470 53.72 1485 55.24 1500 56.80 1513 58.18 1528  
33000 1463 53.38 1478 54.87 1492 56.41 1507 57.99 1520 59.39  
34000 1485 55.93 1499 57.47 1514 59.08  
5972  
35000 1508 58.69  
CFM  
Std.  
Air  
Total Static Pressure  
9.00  
8.25  
RPM BHP  
8.50  
RPM BHP  
8.75  
RPM BHP  
RPM  
BHP  
23000 1428 43.75 1444 45.03 1464 46.53 1488 48.30  
24000 1437 45.45 1453 46.74 1473 48.32 1490 49.71  
25000 1447 47.14 1464 48.58 1482 50.06 1500 51.61  
26000 1459 48.97 1477 50.55 1493 51.95 1509 53.40  
27000 1473 50.95 1489 52.44 1504 53.87 1523 55.59  
28000 1488 53.11 1503 54.51 1519 56.08 1536 57.71  
29000 1504 55.37 1518 56.78 1533 58.25  
30000 1519 57.58 1535 59.15  
Notes:  
1. Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external  
static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional  
heating system).  
2. Maximum SP leaving the air handler is 5.5" H20 positive.  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
46  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
32" Supply Fan w/o IGV  
12  
11  
10  
9
1600 RPM  
1500 RPM  
8
1400 RPM  
1300 RPM  
7
6
1200 RPM  
1100 RPM  
5
4
1000 RPM  
900 RPM  
3
800 RPM  
700 RPM  
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
50000  
55000  
Volumetric Airflow Rate(CFM)  
Table 16 Supply Fan Performance STANDARD CFM—Casing B (32")  
RT-PRC031-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
Table 17 Supply Fan Performance STANDARD CFM — Casing C (36")  
CFM  
Total Static Pressure  
1.00 1.25  
Std.  
0.25  
0.50  
0.75  
1.50  
1.75  
2.00  
Air  
RPM  
BHP  
5.39  
RPM  
BHP  
6.25  
RPM  
BHP  
6.94  
RPM  
BHP  
7.93  
RPM  
662  
680  
698  
716  
733  
752  
771  
790  
810  
830  
851  
872  
892  
913  
934  
955  
976  
997  
BHP  
8.95  
RPM  
BHP  
9.98  
RPM  
BHP  
RPM  
BHP  
(i)  
23000 553  
582  
603  
624  
645  
666  
686  
707  
728  
749  
771  
792  
813  
834  
856  
877  
899  
921  
942  
964  
986  
607  
627  
648  
668  
689  
710  
730  
752  
772  
793  
814  
835  
856  
877  
898  
919  
940  
961  
982  
636  
654  
672  
691  
710  
730  
750  
771  
792  
812  
833  
854  
875  
896  
917  
938  
958  
979  
688  
705  
722  
740  
758  
776  
793  
812  
830  
849  
868  
888  
909  
929  
950  
970  
991  
712  
729  
746  
763  
780  
798  
816  
834  
851  
869  
888  
906  
925  
945  
965  
986  
11.03  
11.86  
12.72  
13.63  
14.61  
15.67  
16.74  
17.89  
19.06  
20.32  
21.64  
23.04  
24.54  
26.18  
27.97  
736  
752  
768  
785  
802  
819  
836  
854  
872  
890  
907  
925  
944  
962  
981  
12.09  
12.94  
13.87  
14.79  
15.81  
16.90  
18.01  
19.20  
20.44  
21.74  
23.07  
24.50  
26.00  
27.58  
29.24  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
37000  
38000  
39000  
40000  
41000  
42000  
43000  
574  
6.04  
6.99  
7.68  
8.63  
9.71  
10.76  
11.60  
12.50  
13.43  
14.41  
15.44  
16.54  
17.70  
18.95  
20.30  
21.80  
23.40  
25.08  
26.87  
28.76  
595  
617  
638  
660  
682  
704  
726  
748  
770  
791  
813  
836  
858  
880  
902  
924  
946  
968  
991  
6.73  
7.78  
8.48  
9.38  
10.50  
11.32  
12.20  
13.15  
14.17  
15.29  
16.54  
17.86  
19.28  
20.79  
22.39  
24.07  
25.86  
27.73  
29.69  
7.47  
8.59  
9.35  
10.20  
11.11  
12.12  
13.20  
14.37  
15.62  
16.95  
18.36  
19.86  
21.44  
23.05  
24.69  
26.41  
28.21  
30.09  
8.27  
9.45  
10.29  
11.30  
12.39  
13.56  
14.76  
15.99  
17.28  
18.63  
20.06  
21.56  
23.14  
24.79  
26.52  
28.33  
9.14  
10.36  
11.34  
12.37  
13.46  
14.63  
15.85  
17.15  
18.52  
19.97  
21.49  
23.09  
24.80  
26.58  
28.47  
10.07  
11.07  
12.13  
13.25  
14.45  
15.72  
17.06  
18.48  
19.98  
21.56  
23.22  
24.96  
26.80  
28.72  
29.87 1001 31.06  
30.74 1006 31.85 1021 33.04  
31.71 1012 32.83 1026 33.95 1041 35.13  
30.24 1000 32.04 1017 33.73 1033 35.02 1047 36.13 1061 37.31  
30.43 1003 32.22 1021 34.10 1038 35.86 1054 37.33 1068 38.44 1081 39.61  
30.74 1008 32.49 1025 34.31 1042 36.23 1059 38.05 1075 39.73 1089 40.87 1102 42.06  
44000 1013 32.85 1030 34.64 1046 36.47 1063 38.44 1080 40.35 1095 42.11 1109 43.38 1123 44.59  
45000 1035 35.06 1052 36.89 1068 38.74 1084 40.74 1101 42.71 1116 44.56 1130 46.02 1144 47.25  
CFM  
Std.  
Total Static Pressure  
3.00 3.25  
2.25  
2.50  
2.75  
3.50  
RPM  
3.75  
RPM  
4.00  
RPM  
Air  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
847  
860  
872  
886  
902  
916  
933  
948  
965  
981  
998  
BHP  
BHP  
18.91  
19.88  
20.92  
22.07  
23.28  
24.57  
25.94  
27.36  
28.88  
BHP  
20.17  
21.12  
22.24  
23.35  
24.61  
25.86  
27.30  
BHP  
21.44  
22.42  
23.57  
24.71  
25.93  
27.23  
28.62  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
37000  
758  
774  
790  
806  
823  
839  
857  
874  
891  
909  
927  
945  
962  
980  
999  
13.15  
14.04  
15.00  
15.99  
17.04  
18.13  
19.31  
20.53  
21.80  
23.18  
24.57  
26.04  
27.52  
29.13  
780  
796  
811  
827  
843  
859  
876  
894  
910  
928  
945  
963  
981  
998  
14.22  
15.17  
16.18  
17.20  
18.29  
19.41  
20.61  
21.89  
23.19  
24.60  
26.02  
27.55  
29.11  
803  
817  
832  
847  
863  
879  
895  
912  
929  
946  
963  
981  
998  
15.34  
16.29  
17.32  
18.41  
19.53  
20.71  
21.94  
23.25  
24.56  
25.99  
27.47  
29.03  
825  
838  
852  
867  
882  
898  
914  
931  
947  
964  
980  
998  
16.49  
17.43  
18.48  
19.60  
20.78  
21.99  
23.28  
24.61  
25.99  
27.43  
28.92  
17.68  
18.66  
19.70  
20.79  
22.03  
23.26  
24.62  
25.97  
27.42  
28.86  
869  
881  
893  
906  
920  
935  
951  
966  
983  
998  
891  
901  
914  
925  
939  
953  
968  
983  
999  
913  
922  
934  
946  
958  
971  
985  
28.72 1000 30.10  
30.25 1016 31.69  
30.33 1016 31.89 1031 33.27  
30.48 1015 31.96 1031 33.46 1048 34.97  
30.54 1015 32.11 1031 33.59 1048 35.15 1064 36.73  
30.65 1015 32.18 1032 33.75 1049 35.35 1064 36.91 1080 38.49  
30.74 1016 32.36 1033 33.96 1049 35.54 1065 37.14 1081 38.76 1097 40.40  
30.82 1016 32.46 1034 34.15 1051 35.76 1067 37.41 1083 39.01 1099 40.69 1114 42.32  
38000 1017 32.54 1034 34.20 1051 35.91 1069 37.65 1084 39.30 1100 40.97 1115 42.64 1130 44.33  
39000 1036 34.41 1053 36.09 1070 37.81 1086 39.57 1102 41.29 1118 43.02 1133 44.77 1148 46.52  
40000 1055 36.40 1071 38.02 1087 39.75 1103 41.51 1120 43.38 1135 45.10 1151 46.92 1165 48.66  
41000 1075 38.58 1090 40.05 1105 41.79 1122 43.63 1138 45.49 1153 47.29 1168 49.10 1183 50.99  
42000 1095 40.91 1109 42.26 1125 44.02 1140 45.78 1155 47.64 1171 49.60 1186 51.47 1200 53.25  
43000 1116 43.31 1129 44.68 1143 46.20 1158 48.05 1174 49.99 1189 51.93 1203 53.79 1218 55.73  
44000 1136 45.86 1149 47.17 1162 48.59 1177 50.44 1192 52.37 1207 54.30 1221 56.23 1236 58.25  
45000 1156 48.50 1169 49.81 1182 51.24 1195 52.87 1210 54.79 1225 56.80 1239 58.80 1253 60.79  
48  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
Table 17 Supply Fan Performance STANDARD CFM — Casing C (36")  
CFM  
Std.  
Total Static Pressure  
5.00 5.25  
RPM BHP  
26.89 1019 28.31 1043 29.91 1066 31.45 1090 33.09  
4.25  
RPM  
4.50  
RPM  
4.75  
5.50  
RPM BHP  
5.75  
RPM BHP  
6.00  
RPM BHP  
Air  
BHP  
22.77  
23.83  
24.91  
26.07  
27.34  
BHP  
24.09  
25.13  
26.24  
RPM  
BHP  
RPM  
BHP  
23000  
24000  
25000  
26000  
27000  
28000  
934  
944  
954  
966  
978  
990  
955  
964  
974  
984  
996  
976  
984  
994  
25.44  
998  
26.52 1006 28.00 1026 29.45 1045 30.84 1065 32.32 1088 33.98  
27.66 1014 29.11 1033 30.52 1053 32.08 1073 33.59 1091 35.02  
27.43 1004 28.88 1023 30.30 1042 31.81 1061 33.26 1080 34.80 1099 36.42  
28.72 1015 30.13 1034 31.65 1052 33.05 1070 34.61 1088 36.10 1107 37.75  
28.63 1008 30.06 1027 31.51 1045 32.98 1062 34.40 1081 35.99 1098 37.51 1117 39.20  
29000 1003 30.02 1021 31.49 1039 32.92 1057 34.43 1074 35.88 1091 37.42 1109 39.05 1126 40.60  
30000 1018 31.56 1035 32.97 1052 34.45 1070 36.01 1086 37.50 1103 39.07 1119 40.56 1137 42.22  
31000 1032 33.08 1049 34.55 1066 36.09 1082 37.55 1098 39.09 1115 40.71 1131 42.23 1148 43.83  
32000 1048 34.79 1064 36.25 1080 37.78 1096 39.30 1112 40.81 1129 42.48 1144 44.06 1160 45.70  
33000 1064 36.49 1080 38.08 1096 39.60 1111 41.10 1126 42.68 1141 44.23 1157 45.85 1173 47.54  
34000 1079 38.25 1096 39.91 1110 41.41 1126 42.97 1141 44.60 1155 46.12 1171 47.80 1187 49.55  
35000 1096 40.14 1111 41.72 1126 43.37 1142 44.99 1156 46.60 1170 48.18 1186 49.92 1200 51.52  
36000 1112 42.04 1127 43.68 1143 45.40 1157 47.01 1172 48.68 1186 50.31 1200 52.02 1214 53.68  
37000 1129 44.03 1144 45.73 1159 47.43 1173 49.10 1188 50.84 1202 52.54 1216 54.31 1230 56.03  
38000 1146 46.10 1160 47.78 1175 49.54 1189 51.28 1203 52.99 1218 54.86 1232 56.59 1246 58.37  
39000 1163 48.28 1177 49.93 1191 51.75 1206 53.56 1220 55.33 1234 57.17 1247 58.96 1260 60.70  
40000 1180 50.47 1194 52.28 1209 54.07 1222 55.84 1236 57.67 1249 59.47 1263 61.32 1277 63.25  
41000 1197 52.78 1211 54.56 1225 56.40 1239 58.23 1253 60.13 1266 61.99 1280 63.92 1293 65.79  
42000 1214 55.11 1229 57.05 1242 58.86 1256 60.75 1269 62.60 1282 64.52 1296 66.51 1309 68.44  
43000 1232 57.56 1246 59.46 1260 61.45 1273 63.28 1287 65.31 1299 67.18 1313 69.24 1325 71.10  
44000 1250 60.14 1263 62.12 1277 64.06 1291 66.08 1304 68.05 1316 69.98 1329 71.97 1342 73.90  
45000 1268 62.86 1281 64.80 1295 66.81 1308 68.78 1321 70.82 1333 72.80 1346 74.86  
CFM  
Std.  
Air  
Total Static Pressure  
7.00 7.25  
RPM BHP RPM BHP  
6.25  
RPM BHP  
6.50  
RPM BHP  
6.75  
RPM BHP  
7.50  
RPM BHP  
7.75  
RPM BHP  
8.00  
RPM BHP  
23000 1113 34.68 1134 36.20 1156 37.81 1177 39.32 1198 40.92 1217 42.39 1237 43.95 1257 45.59  
24000 1112 35.73 1133 37.25 1156 39.04 1176 40.55 1199 42.34 1217 43.81 1239 45.57 1258 47.20  
25000 1112 36.70 1134 38.41 1154 40.02 1177 41.91 1197 43.50 1217 45.18 1238 46.94 1257 48.55  
26000 1118 37.96 1137 39.58 1154 41.09 1177 43.01 1198 44.81 1217 46.49 1237 48.25 1258 50.10  
27000 1125 39.32 1144 40.97 1161 42.51 1179 44.22 1196 45.80 1217 47.73 1237 49.50 1256 51.35  
28000 1134 40.80 1151 42.39 1169 44.06 1186 45.70 1204 47.41 1222 49.21 1238 50.84 1257 52.75  
29000 1143 42.23 1161 43.94 1177 45.54 1194 47.20 1211 48.95 1229 50.77 1244 52.43 1261 54.16  
30000 1153 43.79 1170 45.54 1186 47.16 1203 48.86 1220 50.64 1237 52.49 1253 54.19 1269 55.95  
31000 1164 45.51 1182 47.29 1197 48.95 1213 50.69 1229 52.38 1245 54.15 1260 55.87 1276 57.66  
32000 1176 47.32 1192 49.02 1208 50.70 1224 52.47 1240 54.31 1255 56.00 1270 57.75 1285 59.56  
33000 1187 49.11 1204 50.95 1220 52.66 1235 54.44 1250 56.08 1265 57.91 1281 59.82 1296 61.68  
34000 1201 51.16 1216 52.84 1231 54.59 1247 56.41 1261 58.07 1277 60.04 1292 61.86 1307 63.75  
35000 1214 53.19 1229 54.92 1244 56.72 1258 58.47 1273 60.29 1287 62.05 1302 63.87 1317 65.78  
36000 1229 55.40 1243 57.19 1256 58.81 1272 60.73 1285 62.47 1299 64.28 1314 66.14 1328 68.08  
37000 1244 57.71 1257 59.44 1270 61.11 1285 63.09 1299 64.88 1313 66.74 1326 68.52 1340 70.35  
38000 1258 59.99 1273 61.90 1286 63.63 1299 65.42 1312 67.27 1326 69.17 1339 71.00  
39000 1274 62.49 1287 64.35 1300 66.13 1314 67.98 1327 69.89 1339 71.57  
40000 1289 64.98 1303 66.90 1316 68.75 1328 70.52 1341 72.48 1354 74.36  
41000 1306 67.72 1319 69.58 1332 71.49 1344 73.32  
42000 1322 70.45 1335 72.38 1347 74.22  
43000 1338 73.03  
RT-PRC031-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan without Inlet Guide  
Vanes (with or without Variable Frequency Drive)  
Table 17 Supply Fan Performance STANDARD CFM — Casing C (36")  
CFM  
Std.  
Air  
Total Static Pressure  
8.25  
RPM BHP  
8.50  
RPM BHP  
23000 1275 47.06 1294 48.70  
24000 1276 48.66 1296 50.45  
25000 1276 50.25 1296 52.02  
26000 1276 51.80 1296 53.57  
27000 1277 53.29 1295 55.06  
28000 1277 54.70 1295 56.48  
29000 1278 55.96 1295 57.81  
30000 1285 57.78 1302 59.68  
31000 1292 59.52 1308 61.45  
32000 1301 61.46 1317 63.42  
33000 1311 63.47 1325 65.33  
34000 1320 65.43 1335 67.46  
35000 1332 67.77 1345 69.54  
36000 1342 69.94  
Notes:  
1. Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external  
static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional  
heating system).  
2. Maximum SP leaving the air handler is 5.5" H20 positive.  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
36" Supply Fan w/o IGV  
12  
11  
10  
9
1300 RPM  
8
7
1200 RPM  
6
1100 RPM  
5
1000 RPM  
4
900 RPM  
3
2
1
0
800 RPM  
700 RPM  
600 RPM  
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
50000  
55000  
Volumetric Airflow Rate(CFM)  
Figure 19. Supply Fan Performance STANDARD CFM —Casing C (36")  
50  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan  
with Inlet Guide Vanes  
Table 18 Supply Fan Performance STANDARD CFM — Casing A (25")  
CFM  
Total Static Pressure  
1.00 1.25  
Std.  
0.25  
RPM BHP  
0.50  
RPM  
0.75  
RPM  
1.50  
RPM BHP  
1211 10.38 1240 11.10 1267 11.80  
1.75  
2.00  
Air  
BHP  
7.69  
9.04  
BHP  
8.35  
9.75  
RPM  
1154  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
(i)  
16000 1064  
7.01  
8.31  
9.77  
1095  
1157  
1125  
1185  
9.02  
1183  
9.69  
17000 1127  
18000 1190  
1213 10.46 1239 11.16 1266 11.88 1293 12.62 1320 13.38  
1218 10.54 1245 11.30 1271 12.05 1297 12.79 1323 13.55 1348 14.33 1373 15.11  
19000 1252 11.40 1280 12.22 1306 13.02 1331 13.81 1355 14.60 1379 15.38 1403 16.18 1428 17.02  
20000 1316 13.20 1341 14.07 1366 14.92 1391 15.76 1414 16.58 1437 17.40 1460 18.23 1483 19.08  
21000 1379 15.19 1404 16.10 1427 16.99 1451 17.87 1473 18.75 1496 19.62 1518 20.49 1539 21.36  
22000 1442 17.37 1466 18.32 1489 19.27 1511 20.20 1533 21.11 1554 22.01 1575 22.92 1596 23.83  
23000 1505 19.76 1528 20.76 1550 21.74 1572 22.71 1593 23.67 1614 24.63 1634 25.58 1654 26.53  
24000 1569 22.35 1591 23.40 1612 24.43 1633 25.45 1653 26.46 1673 27.45 1693 28.44 1712 29.42  
25000 1633 25.17 1654 26.27 1674 27.34 1694 28.41 1714 29.45 1733 30.50 1752 31.53 1771 32.56  
26000 1696 28.22 1717 29.36 1736 30.48 1756 31.60 1775 32.70 1794 33.78 1812 34.87 1830 35.93  
27000 1760 31.52 1780 32.70 1799 33.86 1817 35.01 1836 36.17 1854 37.31 1872 38.42 1890 39.56  
28000 1824 35.05 1843 36.28 1861 37.50 1879 38.70 1897 39.89 1915 41.07 1932 42.23 1949 43.41  
29000 1887 38.85 1906 40.12 1924 41.39 1941 42.63 1959 43.86 1976 45.10 1993 46.31 2009 47.53  
30000 1951 42.92 1969 44.24 1986 45.54 2004 46.82  
31000 2015 47.26  
CFM  
Total Static Pressure  
3.00 3.25  
RPM BHP RPM BHP  
12.49 1320 13.19 1345 13.89 1368 14.53 1390 15.19 1412 15.86 1434 16.53 1456 17.21  
Std.  
2.25  
RPM BHP  
2.50  
RPM BHP  
2.75  
RPM BHP  
3.50  
RPM BHP  
3.75  
RPM BHP  
4.00  
RPM BHP  
Air  
(ii)  
16000 1294  
17000 1346 14.13 1371 14.89 1395 15.61 1419 16.34 1441 17.04 1462 17.74 1484 18.45 1505 19.16  
18000 1398 15.90 1422 16.69 1447 17.49 1470 18.28 1493 19.07 1514 19.81 1534 20.55 1555 21.29  
19000 1452 17.86 1475 18.67 1499 19.53 1521 20.37 1544 21.21 1565 22.01 1586 22.82 1606 23.62  
20000 1506 19.95 1528 20.83 1551 21.71 1573 22.59 1595 23.48 1616 24.36 1637 25.24 1658 26.12  
21000 1561 22.27 1583 23.17 1605 24.11 1626 25.05 1647 25.94 1667 26.86 1689 27.82 1709 28.73  
22000 1617 24.77 1637 25.69 1659 26.69 1679 27.63 1700 28.61 1720 29.58 1741 30.58 1760 31.51  
23000 1674 27.50 1694 28.46 1714 29.46 1733 30.44 1753 31.46 1773 32.47 1793 33.51 1812 34.54  
24000 1732 30.44 1751 31.45 1769 32.44 1788 33.47 1808 34.53 1827 35.57 1846 36.65 1864 37.70  
25000 1790 33.61 1808 34.63 1826 35.69 1844 36.73 1863 37.83 1881 38.90 1899 40.01 1917 41.08  
26000 1848 37.02 1866 38.08 1883 39.15 1901 40.25 1919 41.38 1936 42.48 1954 43.61 1972 44.78  
27000 1907 40.66 1924 41.76 1941 42.89 1958 44.02 1975 45.15 1992 46.27  
28000 1966 44.55 1983 45.71 1999 46.87  
CFM  
Std.  
Air  
Total Static Pressure  
5.00 5.25  
RPM BHP RPM BHP  
4.25  
RPM BHP  
4.50  
RPM BHP  
4.75  
RPM BHP  
5.50  
RPM BHP  
5.75  
RPM BHP  
6.00  
RPM BHP  
16000 1479 17.93 1502 18.68 1523 19.40 1546 20.15 1569 20.94 1592 21.77 1614 22.55 1636 23.33  
17000 1526 19.90 1547 20.65 1568 21.39 1589 22.16 1609 22.92 1630 23.72 1652 24.54 1674 25.41  
18000 1574 22.02 1594 22.78 1614 23.54 1634 24.33 1654 25.15 1673 25.91 1693 26.75 1714 27.62  
19000 1625 24.38 1644 25.17 1663 25.94 1682 26.75 1701 27.58 1720 28.40 1739 29.25 1757 30.08  
20000 1677 26.94 1696 27.80 1714 28.59 1732 29.41 1750 30.26 1767 31.03 1786 31.94 1803 32.77  
21000 1728 29.62 1747 30.55 1765 31.40 1783 32.29 1801 33.15 1817 33.98 1835 34.90 1851 35.72  
22000 1779 32.48 1799 33.48 1817 34.41 1835 35.36 1852 36.23 1868 37.13 1885 38.05 1903 39.00  
23000 1831 35.53 1850 36.56 1868 37.55 1885 38.52 1904 39.58 1921 40.55 1937 41.47 1953 42.42  
24000 1883 38.78 1901 39.83 1919 40.91 1937 41.95 1955 43.03 1972 44.06 1988 45.05 2005 46.07  
25000 1935 42.19 1953 43.33 1971 44.43 1989 45.55 2006 46.63  
26000 1989 45.91 2006 47.06  
RT-PRC031-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data — Supply Fan with Inlet Guide Vanes  
Table 18 Supply Fan Performance STANDARD CFM — Casing A (25")  
CFM  
Std.  
Air  
Total Static Pressure  
7.00 7.25  
RPM BHP RPM BHP  
6.25  
RPM BHP  
6.50  
RPM BHP  
6.75  
RPM BHP  
7.50  
RPM BHP  
7.75  
RPM BHP  
8.00  
RPM BHP  
16000 1657 24.15 1678 24.95 1697 25.68 1719 26.55 1739 27.34 1760 28.16 1780 28.98 1803 29.88  
17000 1694 26.21 1715 27.05 1736 27.92 1755 28.73 1775 29.56 1795 30.43 1815 31.32 1833 32.11  
18000 1734 28.48 1754 29.36 1773 30.16 1794 31.12 1813 31.98 1833 32.88 1853 33.82 1870 34.66  
19000 1776 30.93 1794 31.76 1814 32.74 1833 33.62 1852 34.53 1871 35.48 1889 36.38 1908 37.32  
20000 1820 33.62 1838 34.50 1856 35.41 1874 36.35 1892 37.26 1910 38.18 1929 39.21 1946 40.12  
21000 1869 36.64 1885 37.52 1902 38.42 1919 39.35 1937 40.31 1954 41.30 1971 42.24 1988 43.21  
22000 1918 39.84 1934 40.78 1951 41.75 1967 42.67 1983 43.61 1999 44.58  
23000 1968 43.32 1984 44.25 1999 45.20  
CFM  
Std.  
Air  
Total Static Pressure  
9.00  
8.25  
RPM BHP  
8.50  
RPM BHP  
8.75  
RPM BHP  
RPM  
BHP  
16000 1827 30.81 1849 31.71 1872 32.64 1895 33.60  
17000 1853 33.00 1873 33.91 1892 34.76 1914 35.77  
18000 1888 35.53 1906 36.42 1925 37.33 1944 38.28  
19000 1927 38.29 1945 39.22 1962 40.11 1981 41.10  
20000 1964 41.06 1983 42.11 1999 43.02  
21000 2005 44.20  
Notes:  
1. Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external  
static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional  
heating system).  
2. Maximum SP leaving the air handler is 5.5" H20 positive.  
(i)  
(ii)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
52  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
25" Supply Fan Performance with IGV  
12  
11  
10  
9
2000 RPM  
1900 RPM  
8
1800 RPM  
1700 RPM  
7
1600 RPM  
1500 RPM  
6
5
1400 RPM  
1300 RPM  
4
1200 RPM  
1100 RPM  
3
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
Volumetric Airflow Rate(CFM)  
Figure 20. Supply Fan Performance STANDARD CFM—Casing A (25")  
RT-PRC031-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
Table 19 Supply Fan Performance STANDARD CFM — Casing B (32")  
CFM  
Total Static Pressure  
1.00 1.25  
Std.  
0.25  
0.50  
0.75  
1.50  
RPM  
1.75  
RPM  
2.00  
RPM  
Air  
RPM  
BHP  
5.82  
RPM  
BHP  
6.66  
RPM  
BHP  
7.48  
RPM  
BHP  
8.35  
RPM  
799  
825  
852  
879  
907  
935  
963  
992  
BHP  
9.25  
BHP  
10.13  
11.14  
12.25  
13.42  
14.70  
16.05  
BHP  
10.98  
12.07  
13.23  
14.44  
15.74  
BHP  
11.77  
12.93  
14.16  
15.45  
16.83  
(i)  
20000 683  
713  
743  
773  
804  
834  
865  
896  
926  
957  
988  
742  
771  
800  
829  
859  
889  
919  
949  
979  
771  
798  
826  
854  
883  
912  
941  
971  
826  
851  
877  
904  
931  
958  
986  
851  
876  
902  
928  
954  
981  
873  
899  
925  
951  
977  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
714  
6.65  
7.52  
8.40  
9.30  
10.22  
11.29  
12.42  
13.65  
14.95  
16.37  
745  
777  
808  
840  
871  
903  
935  
966  
998  
7.55  
8.47  
9.38  
10.31  
11.42  
12.62  
13.89  
15.28  
16.77  
8.53  
9.50  
10.46  
11.61  
12.86  
14.20  
15.65  
9.61  
10.62  
11.82  
13.13  
14.52  
16.01  
10.76  
12.02  
13.37  
14.82  
16.37  
17.15 1003 18.27  
17.50 1007 18.63 1029 19.78  
17.89 1013 19.04 1035 20.22 1055 21.39  
17.19 1000 18.35 1021 19.52 1042 20.68 1062 21.89 1082 23.11  
17.62 1010 18.84 1030 20.03 1050 21.23 1070 22.44 1090 23.69 1110 24.97  
18.03 1020 19.32 1040 20.58 1060 21.84 1080 23.07 1099 24.32 1118 25.59 1137 26.88  
31000 1030 19.80 1051 21.14 1071 22.45 1090 23.75 1109 25.03 1128 26.32 1146 27.59 1165 28.93  
32000 1062 21.69 1082 23.08 1102 24.44 1121 25.76 1139 27.09 1157 28.41 1176 29.76 1193 31.10  
33000 1094 23.70 1113 25.13 1133 26.54 1151 27.91 1169 29.28 1187 30.64 1204 32.01 1222 33.39  
34000 1126 25.83 1145 27.30 1163 28.74 1182 30.18 1199 31.59 1216 32.99 1233 34.39 1250 35.81  
35000 1158 28.08 1176 29.60 1194 31.10 1212 32.58 1229 34.04 1246 35.47 1263 36.91 1279 38.37  
36000 1190 30.47 1208 32.04 1225 33.57 1243 35.11 1260 36.60 1276 38.07 1293 39.58 1309 41.08  
37000 1222 32.99 1239 34.60 1257 36.17 1274 37.74 1290 39.31 1306 40.84 1322 42.35 1338 43.89  
38000 1254 35.65 1271 37.29 1288 38.93 1305 40.56 1321 42.14 1336 43.71 1352 45.29 1367 46.85  
39000 1286 38.44 1303 40.13 1319 41.81 1335 43.49 1351 45.11 1367 46.76 1382 48.37 1397 49.96  
40000 1318 41.38 1334 43.12 1351 44.85 1366 46.55 1382 48.24 1397 49.91 1412 51.56 1427 53.25  
41000 1350 44.47 1366 46.27 1382 48.03 1397 49.79 1413 51.52 1427 53.23 1442 54.94 1456 56.61  
42000 1382 47.72 1398 49.55 1413 51.38 1429 53.17 1443 54.94 1458 56.71 1472 58.44 1486 60.17  
43000 1414 51.12 1430 52.99 1445 54.86 1460 56.69 1474 58.52 1488 60.32  
44000 1446 54.68 1462 56.60 1476 58.52 1491 60.39  
45000 1479 58.40 1493 60.36  
CFM  
Std.  
Total Static Pressure  
3.00 3.25  
2.25  
RPM  
2.50  
RPM  
2.75  
3.50  
RPM BHP  
16.25 1008 17.25 1031 18.27 1051 19.22  
3.75  
4.00  
Air  
BHP  
12.60  
13.80  
15.08  
16.43  
BHP  
13.48  
14.67  
15.98  
RPM  
BHP  
14.39  
15.58  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
20000  
21000  
22000  
23000  
24000  
895  
921  
947  
973  
998  
918  
942  
967  
993  
941  
963  
987  
962  
985  
15.28  
985  
16.53 1006 17.49 1028 18.48 1049 19.51 1071 20.57  
16.90 1008 17.85 1028 18.83 1048 19.81 1070 20.89 1090 21.96  
17.38 1012 18.33 1032 19.31 1051 20.28 1071 21.32 1090 22.34 1110 23.42  
17.86 1019 18.87 1038 19.85 1057 20.86 1076 21.86 1094 22.88 1113 23.96 1131 25.01  
25000 1024 19.35 1045 20.43 1064 21.47 1083 22.51 1100 23.53 1118 24.57 1136 25.62 1155 26.78  
26000 1050 20.94 1070 22.06 1090 23.21 1109 24.28 1126 25.33 1144 26.43 1161 27.49 1178 28.61  
27000 1076 22.60 1096 23.80 1116 24.95 1135 26.13 1152 27.24 1169 28.36 1186 29.49 1202 30.56  
28000 1103 24.38 1122 25.59 1141 26.82 1160 28.07 1178 29.24 1195 30.43 1212 31.58 1228 32.71  
29000 1129 26.24 1148 27.49 1168 28.81 1186 30.10 1204 31.34 1221 32.55 1237 33.75 1253 34.96  
30000 1156 28.20 1175 29.54 1194 30.85 1212 32.16 1230 33.49 1247 34.82 1264 36.09 1279 37.30  
31000 1184 30.30 1202 31.63 1220 33.03 1238 34.38 1256 35.78 1273 37.14 1290 38.48 1305 39.76  
32000 1212 32.51 1229 33.88 1247 35.31 1264 36.69 1282 38.13 1299 39.56 1316 40.98 1331 42.33  
33000 1239 34.79 1257 36.25 1274 37.72 1291 39.18 1308 40.65 1325 42.10 1341 43.53 1357 44.95  
34000 1267 37.25 1284 38.74 1301 40.24 1318 41.73 1334 43.21 1351 44.75 1367 46.19 1382 47.69  
35000 1296 39.84 1313 41.37 1329 42.89 1345 44.40 1362 45.98 1378 47.53 1393 49.06 1408 50.56  
36000 1325 42.58 1340 44.07 1357 45.65 1372 47.22 1388 48.80 1404 50.37 1420 51.99 1435 53.57  
37000 1353 45.41 1369 46.99 1384 48.55 1400 50.18 1415 51.77 1431 53.42 1446 55.05 1462 56.72  
38000 1383 48.44 1397 50.00 1413 51.66 1428 53.29 1443 54.89 1458 56.55 1473 58.26 1488 59.93  
39000 1412 51.56 1426 53.18 1441 54.85 1456 56.49 1471 58.18 1486 59.93  
40000 1441 54.87 1456 56.54 1470 58.22 1484 59.86  
41000 1471 58.33 1485 60.00  
54  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
Table 19 Supply Fan Performance STANDARD CFM — Casing B (32")  
CFM  
Std.  
Air  
Total Static Pressure  
5.00 5.25  
RPM BHP RPM BHP  
4.25  
RPM BHP  
4.50  
RPM BHP  
4.75  
RPM BHP  
5.50  
RPM BHP  
5.75  
RPM BHP  
6.00  
RPM BHP  
20000 1072 20.24 1093 21.23 1114 22.28 1136 23.36 1158 24.48 1181 25.62 1204 26.81 1229 28.07  
21000 1091 21.58 1112 22.67 1132 23.72 1150 24.73 1169 25.80 1191 26.98 1212 28.11 1236 29.41  
22000 1110 23.01 1131 24.12 1150 25.22 1168 26.28 1187 27.39 1207 28.56 1225 29.66 1246 30.90  
23000 1130 24.52 1150 25.68 1169 26.81 1187 27.90 1206 29.06 1224 30.21 1242 31.36 1260 32.50  
24000 1150 26.11 1169 27.28 1188 28.40 1207 29.64 1226 30.83 1243 31.96 1261 33.15 1279 34.40  
25000 1173 27.90 1190 29.02 1208 30.19 1226 31.37 1244 32.60 1263 33.89 1281 35.12 1298 36.34  
26000 1195 29.73 1213 30.91 1230 32.09 1247 33.26 1264 34.48 1282 35.76 1300 37.10 1316 38.28  
27000 1219 31.75 1235 32.87 1252 34.11 1268 35.27 1285 36.55 1302 37.82 1318 39.06 1336 40.43  
28000 1243 33.84 1260 35.09 1276 36.26 1291 37.48 1308 38.75 1324 40.01 1340 41.31 1355 42.58  
29000 1269 36.15 1284 37.33 1300 38.56 1316 39.85 1330 41.03 1346 42.34 1362 43.71 1378 45.04  
30000 1295 38.56 1309 39.74 1325 41.03 1339 42.23 1355 43.55 1369 44.84 1385 46.19 1399 47.49  
31000 1321 41.09 1335 42.33 1350 43.61 1365 44.87 1379 46.18 1393 47.45 1408 48.85 1422 50.12  
32000 1347 43.73 1362 45.04 1376 46.31 1390 47.63 1404 48.92 1419 50.34 1432 51.62 1446 52.95  
33000 1373 46.42 1388 47.79 1402 49.13 1416 50.52 1430 51.87 1444 53.27 1457 54.62 1471 56.01  
34000 1399 49.24 1414 50.69 1429 52.18 1442 53.55 1456 54.97 1469 56.34 1483 57.75 1496 59.10  
35000 1424 52.11 1439 53.63 1454 55.20 1468 56.63 1482 58.11 1495 59.55  
36000 1450 55.11 1466 56.80 1480 58.36 1494 59.86  
37000 1476 58.35 1491 59.93  
CFM  
Std.  
Air  
Total Static Pressure  
7.00 7.25  
RPM BHP RPM BHP  
6.25  
RPM BHP  
6.50  
RPM BHP  
6.75  
RPM BHP  
7.50  
RPM BHP  
7.75  
RPM BHP  
8.00  
RPM BHP  
20000 1252 29.28 1276 30.56 1298 31.78 1321 33.08 1344 34.40 1365 35.63 1388 37.02 1408 38.30  
21000 1258 30.65 1278 31.82 1302 33.18 1324 34.48 1347 35.84 1369 37.11 1390 38.47 1413 39.92  
22000 1265 32.06 1285 33.26 1308 34.66 1330 35.98 1349 37.20 1372 38.64 1393 39.98 1414 41.38  
23000 1279 33.75 1297 34.95 1316 36.18 1337 37.54 1356 38.80 1378 40.27 1398 41.63 1418 43.05  
24000 1295 35.56 1312 36.77 1330 38.02 1348 39.30 1366 40.61 1385 41.96 1405 43.36 1425 44.81  
25000 1314 37.54 1331 38.80 1347 40.03 1365 41.38 1381 42.62 1397 43.88 1416 45.34 1433 46.66  
26000 1334 39.66 1351 40.96 1366 42.15 1383 43.56 1399 44.84 1415 46.16 1430 47.44 1445 48.75  
27000 1352 41.71 1369 43.03 1385 44.42 1402 45.78 1417 47.10 1432 48.38 1448 49.80 1463 51.16  
28000 1372 43.98 1389 45.36 1404 46.70 1421 48.18 1437 49.54 1452 50.95 1466 52.21 1482 53.73  
29000 1393 46.33 1408 47.67 1424 49.15 1439 50.49 1454 51.88 1470 53.32 1486 54.82 1501 56.26  
30000 1414 48.84 1429 50.24 1444 51.58 1459 53.07 1475 54.51 1490 56.00 1505 57.44 1521 59.03  
31000 1437 51.53 1452 52.99 1466 54.40 1480 55.75 1495 57.24 1509 58.67 1525 60.26  
32000 1460 54.32 1474 55.74 1488 57.21 1503 58.72 1516 60.06  
33000 1485 57.44 1498 58.82 1512 60.24  
CFM  
Std.  
Air  
Total Static Pressure  
9.00  
8.25  
RPM BHP  
8.50  
RPM BHP  
8.75  
RPM BHP  
RPM  
BHP  
20000 1429 39.64 1451 41.06 1472 42.44 1493 43.90  
21000 1433 41.25 1454 42.65 1474 44.01 1494 45.44  
22000 1436 42.85 1456 44.23 1477 45.68 1497 47.09  
23000 1440 44.53 1459 45.88 1479 47.29 1499 48.75  
24000 1443 46.13 1464 47.69 1483 49.12 1502 50.59  
25000 1450 48.01 1471 49.62 1489 51.07 1508 52.58  
26000 1463 50.17 1480 51.63 1498 53.13 1514 54.45  
27000 1479 52.57 1494 53.91 1509 55.28  
28000 1497 55.08 1511 56.47  
29000 1516 57.77  
Notes:  
1. Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external  
static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional  
heating system).  
2. Maximum SP leaving the air handler is 5.5" H20 positive.  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
RT-PRC031-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
32" Supply Fan Performance with IGV  
12  
11  
10  
9
1600 RPM  
1500 RPM  
1400 RPM  
8
7
1300 RPM  
1200 RPM  
6
5
1100 RPM  
1000 RPM  
4
3
900 RPM  
800 RPM  
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
50000  
Volumetric Airflow Rate(CFM)  
Figure 21. Supply Fan Performance STANDARD CFM—Casing B (32")  
56  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
Table 20 Supply Fan Performance STANDARD CFM — Casing C (36")  
CFM  
Total Static Pressure  
1.00 1.25  
Std.  
0.25  
0.50  
0.75  
1.50  
1.75  
2.00  
Air  
RPM  
BHP  
5.72  
RPM  
BHP  
6.67  
RPM  
BHP  
7.65  
RPM  
BHP  
8.66  
RPM  
670  
688  
706  
725  
744  
763  
782  
801  
821  
841  
861  
881  
902  
922  
943  
964  
985  
BHP  
9.68  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
(i)  
23000 559  
588  
609  
630  
651  
672  
693  
715  
736  
758  
779  
801  
823  
845  
866  
888  
910  
932  
954  
976  
999  
616  
636  
656  
676  
696  
717  
737  
758  
779  
800  
821  
843  
864  
886  
907  
929  
950  
972  
994  
644  
663  
681  
700  
720  
740  
760  
780  
800  
821  
841  
862  
883  
904  
925  
946  
968  
989  
694  
712  
731  
749  
767  
785  
804  
823  
842  
861  
880  
900  
920  
940  
960  
981  
10.64  
11.58  
12.54  
13.54  
14.59  
15.74  
16.91  
18.17  
19.49  
20.88  
22.34  
23.92  
25.54  
27.25  
29.06  
30.97  
716  
734  
753  
771  
789  
807  
825  
844  
862  
881  
900  
919  
939  
958  
978  
998  
11.60  
12.54  
13.59  
14.67  
15.79  
16.97  
18.20  
19.49  
20.87  
22.27  
23.79  
25.38  
27.05  
28.81  
30.62  
738  
755  
773  
791  
809  
827  
846  
864  
882  
901  
919  
938  
957  
976  
995  
12.57  
13.54  
14.61  
15.73  
16.92  
18.16  
19.47  
20.80  
22.23  
23.73  
25.25  
26.89  
28.57  
30.37  
32.22  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
37000  
38000  
39000  
40000  
41000  
42000  
581  
6.41  
7.41  
8.41  
9.47  
10.53  
11.43  
12.39  
13.40  
14.48  
15.64  
16.84  
18.13  
19.49  
20.92  
22.44  
24.04  
25.74  
27.52  
29.38  
603  
625  
647  
669  
691  
713  
735  
757  
779  
802  
824  
846  
869  
891  
914  
936  
959  
981  
7.15  
8.20  
9.24  
10.32  
11.24  
12.21  
13.27  
14.37  
15.57  
16.81  
18.14  
19.55  
21.03  
22.60  
24.24  
25.98  
27.81  
29.72  
7.96  
9.04  
10.12  
11.07  
12.08  
13.16  
14.30  
15.53  
16.82  
18.18  
19.63  
21.16  
22.76  
24.45  
26.23  
28.09  
30.05  
8.82  
9.95  
9.75  
10.93  
11.97  
13.06  
14.24  
15.49  
16.82  
18.21  
19.69  
21.25  
22.89  
24.62  
26.43  
28.34  
30.35  
10.74  
11.80  
12.93  
14.13  
15.40  
16.76  
18.19  
19.70  
21.30  
22.98  
24.76  
26.62  
28.57  
30.63  
32.55 1015 34.22  
31.32 1001 32.94 1018 34.59 1035 36.27  
31.71 1006 33.36 1022 35.02 1038 36.71 1054 38.37  
32.10 1010 33.81 1027 35.49 1043 37.20 1058 38.90 1074 40.65  
32.45 1015 34.24 1032 36.00 1048 37.73 1063 39.47 1079 41.21 1094 42.99  
43000 1004 32.78 1021 34.64 1037 36.49 1053 38.28 1069 40.06 1084 41.85 1100 43.65 1115 45.43  
44000 1026 35.03 1043 36.93 1059 38.82 1075 40.68 1090 42.51 1105 44.33 1120 46.16 1135 48.00  
45000 1035 35.06 1052 36.89 1068 38.74 1084 40.74 1101 42.71 1116 44.56 1130 46.02 1144 47.25  
CFM  
Std.  
Total Static Pressure  
3.00 3.25  
2.25  
2.50  
2.75  
3.50  
RPM  
3.75  
RPM  
4.00  
RPM  
Air  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
846  
860  
873  
888  
903  
919  
935  
952  
969  
987  
BHP  
18.01  
19.12  
20.22  
21.43  
22.72  
24.09  
25.56  
27.08  
28.72  
BHP  
19.16  
20.30  
21.48  
22.70  
23.96  
25.34  
26.82  
28.40  
BHP  
20.31  
21.50  
22.76  
23.97  
25.28  
26.67  
28.16  
BHP  
21.53  
22.69  
23.95  
25.29  
26.58  
28.03  
29.46  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
760  
776  
793  
810  
829  
847  
865  
883  
901  
920  
938  
956  
975  
994  
13.58  
14.59  
15.64  
16.79  
18.05  
19.33  
20.71  
22.11  
23.58  
25.12  
26.73  
28.37  
30.13  
781  
797  
813  
829  
847  
865  
883  
901  
920  
938  
956  
974  
992  
14.64  
15.66  
16.74  
17.89  
19.15  
20.49  
21.90  
23.37  
24.90  
26.52  
28.16  
29.88  
804  
818  
833  
849  
866  
882  
901  
918  
937  
955  
973  
992  
15.75  
16.76  
17.87  
19.04  
20.33  
21.62  
23.09  
24.59  
26.19  
27.87  
29.58  
826  
840  
853  
868  
884  
901  
918  
935  
953  
971  
990  
16.89  
17.96  
19.02  
20.21  
21.48  
22.84  
24.29  
25.84  
27.47  
29.16  
867  
880  
894  
908  
921  
936  
952  
969  
986  
887  
900  
914  
927  
941  
955  
970  
985  
908  
919  
932  
946  
959  
973  
987  
29.69 1002 31.05  
30.05 1002 31.39 1018 32.76  
30.48 1003 31.82 1019 33.17 1035 34.59  
30.94 1006 32.32 1021 33.67 1036 35.02 1051 36.44  
31.38 1009 32.86 1024 34.25 1039 35.66 1054 37.02 1069 38.44  
31.68 1010 33.20 1027 34.76 1042 36.22 1058 37.69 1072 39.11 1086 40.53  
31.98 1011 33.56 1028 35.17 1045 36.74 1061 38.27 1075 39.75 1091 41.31 1105 42.79  
37000 1012 33.86 1029 35.48 1047 37.17 1063 38.76 1078 40.37 1094 41.98 1109 43.53 1122 45.00  
38000 1031 35.84 1048 37.54 1065 39.21 1081 40.88 1097 42.56 1112 44.25 1127 45.87 1141 47.41  
39000 1051 37.92 1067 39.65 1084 41.41 1099 43.10 1115 44.86 1130 46.56 1145 48.25 1159 49.85  
40000 1070 40.11 1086 41.87 1102 43.64 1118 45.43 1134 47.20 1149 48.98 1164 50.75 1178 52.41  
41000 1090 42.42 1106 44.20 1121 46.00 1137 47.79 1151 49.58 1167 51.43 1181 53.19 1196 55.02  
42000 1110 44.79 1125 46.59 1141 48.47 1155 50.27 1170 52.15 1185 54.01 1200 55.85 1214 57.76  
43000 1129 47.20 1145 49.10 1160 50.99 1175 52.89 1189 54.76 1203 56.62 1218 58.54 1232 60.44  
44000 1150 49.83 1164 51.70 1179 53.65 1194 55.55 1208 57.51 1223 59.46 1236 61.38 1251 63.35  
45000 1156 48.50 1169 49.81 1182 51.24 1195 52.87 1210 54.79 1225 56.80 1239 58.80 1253 60.79  
RT-PRC031-EN  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
Table 20 Supply Fan Performance STANDARD CFM — Casing C (36")  
CFM  
Std.  
Total Static Pressure  
5.00 5.25  
RPM BHP  
26.90 1021 28.30 1045 29.80 1067 31.28 1089 32.76  
4.25  
RPM  
4.50  
RPM  
4.75  
5.50  
RPM BHP  
5.75  
RPM BHP  
6.00  
RPM BHP  
Air  
BHP  
22.80  
23.96  
25.22  
26.56  
27.98  
BHP  
24.15  
25.28  
26.52  
RPM  
BHP  
RPM  
BHP  
23000  
24000  
25000  
26000  
27000  
28000  
929  
939  
951  
964  
978  
992  
952  
960  
970  
982  
995  
975  
980  
988  
25.48  
998  
26.55 1003 28.01 1025 29.43 1045 30.82 1069 32.43 1090 33.86  
27.76 1009 29.16 1030 30.63 1050 32.05 1071 33.55 1093 35.13  
27.85 1000 29.15 1017 30.46 1036 31.87 1056 33.34 1077 34.88 1096 36.35  
29.26 1013 30.61 1030 31.97 1048 33.41 1065 34.83 1084 36.28 1102 37.80  
29.42 1010 30.84 1026 32.17 1044 33.58 1060 35.00 1076 36.33 1093 37.81 1110 39.32  
29000 1005 30.90 1022 32.30 1040 33.73 1057 35.24 1073 36.62 1089 38.08 1105 39.53 1122 41.05  
30000 1019 32.49 1036 33.88 1053 35.35 1070 36.90 1087 38.39 1102 39.81 1118 41.30 1134 42.87  
31000 1034 34.13 1050 35.58 1067 37.10 1084 38.63 1100 40.16 1116 41.69 1132 43.22 1147 44.74  
32000 1051 36.03 1066 37.41 1082 38.92 1098 40.50 1114 42.00 1130 43.57 1145 45.13 1161 46.77  
33000 1066 37.87 1082 39.37 1097 40.87 1112 42.36 1128 43.91 1143 45.44 1159 47.14 1174 48.73  
34000 1083 39.86 1098 41.34 1113 42.90 1128 44.36 1142 45.89 1158 47.57 1172 49.13 1188 50.86  
35000 1101 42.01 1115 43.48 1130 45.02 1144 46.54 1158 48.12 1172 49.68 1188 51.40 1201 52.99  
36000 1118 44.18 1132 45.71 1147 47.31 1160 48.81 1174 50.36 1189 52.08 1202 53.66 1216 55.30  
37000 1136 46.54 1150 48.05 1164 49.63 1177 51.18 1191 52.79 1205 54.47 1218 56.12 1232 57.82  
38000 1155 49.01 1168 50.50 1182 52.14 1194 53.66 1207 55.24 1221 56.88 1234 58.58 1248 60.34  
39000 1173 51.52 1186 53.07 1199 54.69 1212 56.27 1225 57.91 1238 59.61 1251 61.26 1264 62.97  
40000 1192 54.15 1205 55.78 1217 57.36 1230 59.01 1243 60.71 1256 62.36 1267 63.96 1280 65.73  
41000 1209 56.73 1223 58.52 1236 60.17 1249 61.88 1261 63.54 1273 65.26 1285 66.92 1297 68.63  
42000 1228 59.55 1241 61.30 1255 63.13 1267 64.80 1279 66.52 1291 68.19 1304 70.03 1315 71.68  
43000 1246 62.40 1260 64.23 1273 66.12 1285 67.86 1298 69.66 1309 71.39 1321 73.17 1333 74.88  
44000 1264 65.30 1278 67.20 1291 69.05 1304 70.97 1316 72.83 1328 74.63  
45000 1268 62.86 1281 64.80 1295 66.81 1322 74.12  
CFM  
Std.  
Air  
Total Static Pressure  
7.00 7.25  
RPM BHP RPM BHP  
6.25  
RPM BHP  
6.50  
RPM BHP  
6.75  
RPM BHP  
7.50  
RPM BHP  
7.75  
RPM BHP  
8.00  
RPM BHP  
23000 1109 34.17 1131 35.76 1151 37.28 1171 38.79 1192 40.40 1212 42.00 1233 43.70 1251 45.26  
24000 1111 35.38 1134 37.05 1154 38.55 1174 40.14 1194 41.73 1214 43.42 1233 44.98 1252 46.62  
25000 1114 36.66 1135 38.27 1155 39.81 1176 41.49 1195 43.06 1215 44.72 1236 46.48 1254 48.11  
26000 1116 37.89 1137 39.52 1158 41.23 1178 42.86 1199 44.59 1218 46.24 1236 47.76 1256 49.59  
27000 1122 39.39 1140 40.88 1161 42.61 1180 44.26 1201 45.98 1219 47.59 1238 49.28 1258 51.07  
28000 1128 40.80 1147 42.50 1166 44.11 1185 45.78 1202 47.33 1222 49.15 1240 50.85 1259 52.62  
29000 1137 42.45 1154 44.05 1172 45.70 1189 47.32 1207 49.00 1225 50.65 1242 52.36 1261 54.15  
30000 1149 44.32 1164 45.83 1180 47.39 1197 49.06 1214 50.80 1231 52.49 1249 54.25 1265 55.84  
31000 1163 46.33 1178 47.89 1192 49.41 1207 50.99 1222 52.61 1238 54.25 1255 56.05 1271 57.80  
32000 1176 48.31 1191 49.92 1205 51.49 1220 53.11 1234 54.69 1248 56.32 1263 57.98 1280 59.91  
33000 1189 50.39 1204 52.03 1218 53.64 1233 55.31 1247 56.94 1261 58.62 1274 60.23 1289 62.03  
34000 1202 52.47 1217 54.14 1232 55.88 1246 57.60 1260 59.26 1273 60.87 1288 62.66 1301 64.38  
35000 1217 54.74 1231 56.46 1245 58.14 1260 60.00 1274 61.69 1288 63.47 1300 65.05 1315 66.95  
36000 1230 57.01 1245 58.77 1260 60.61 1273 62.28 1287 64.01 1300 65.81 1315 67.68 1327 69.35  
37000 1245 59.37 1259 61.19 1273 62.96 1287 64.80 1300 66.57 1314 68.41 1328 70.32 1341 72.01  
38000 1260 61.94 1275 63.83 1287 65.54 1301 67.30 1314 69.12 1328 71.01 1342 72.96  
39000 1277 64.75 1290 66.46 1303 68.22 1316 70.05 1329 71.93 1342 73.73  
40000 1294 67.57 1306 69.34 1318 71.03 1330 72.78 1344 74.73  
41000 1310 70.40 1322 72.23 1335 74.12  
42000 1327 73.51  
CFM  
Std.  
Air  
Total Static Pressure  
8.25  
RPM BHP  
8.50  
RPM BHP  
23000 1271 46.90 1289 48.49  
24000 1272 48.36 1289 49.92  
25000 1273 49.82 1290 51.36  
26000 1274 51.28 1293 53.06  
58  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data — Supply Fan with Inlet Guide Vanes  
Table 20 Supply Fan Performance STANDARD CFM — Casing C (36")  
CFM  
Std.  
Air  
Total Static Pressure  
8.25  
RPM BHP  
8.50  
RPM BHP  
27000 1276 52.75 1294 54.50  
28000 1279 54.48 1297 56.19  
29000 1280 56.01 1299 57.96  
30000 1283 57.73 1302 59.69  
31000 1288 59.61 1304 61.36  
32000 1295 61.65 1311 63.45  
33000 1303 63.72 1318 65.44  
34000 1315 66.15 1328 67.84  
35000 1328 68.64 1341 70.37  
36000 1341 71.22  
Notes:  
1. Supply fan performance table includes internal resistance of air handler. For total static pressure determination, system external  
static pressure must be added to appropriate component sp drops (chilled water coil, filters, optional economizer, optional  
heating system).  
2. Maximum SP leaving the air handler is 5.5" H20 positive.  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
36" Supply Fan Performance with IGV  
12  
11  
10  
9
8
7
6
5
4
3
2
1
0
1300 RPM  
1200 RPM  
1100 RPM  
1000 RPM  
900 RPM  
800 RPM  
700 RPM  
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
50000  
55000  
Volumetric Airflow Rate(CFM)  
Figure 22. Supply Fan Performance STANDARD CFM —Casing C (36")  
RT-PRC031-EN  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Exhaust Fan  
Table 21 Exhaust Fan Performance LOW CFM—Case B, STANDARD CFM—Case A (25" Fan)  
CFM  
Negative Static Pressure  
1.00 1.25  
Std.  
0.25  
0.50  
0.75  
1.50  
1.75  
2.00  
Air  
RPM  
BHP  
1.42  
RPM  
BHP  
1.91  
RPM  
BHP  
2.44  
RPM  
BHP  
3.03  
RPM  
BHP  
3.65  
RPM  
BHP  
4.27  
RPM  
BHP  
4.89  
RPM  
BHP  
5.52  
(i)  
10000 260  
319  
330  
341  
354  
366  
379  
394  
408  
423  
438  
454  
470  
487  
503  
520  
537  
554  
572  
589  
372  
380  
389  
399  
410  
422  
434  
447  
460  
474  
488  
502  
517  
532  
548  
564  
580  
597  
614  
423  
427  
433  
441  
450  
461  
472  
483  
495  
508  
520  
534  
548  
562  
577  
591  
606  
622  
637  
470  
472  
476  
481  
488  
497  
507  
518  
529  
541  
552  
564  
577  
590  
604  
618  
632  
647  
515  
516  
517  
520  
525  
532  
541  
550  
560  
571  
583  
594  
606  
618  
631  
644  
658  
555  
556  
558  
559  
563  
567  
574  
582  
591  
601  
611  
622  
633  
646  
657  
670  
682  
594  
593  
594  
596  
598  
601  
606  
612  
620  
629  
639  
649  
661  
672  
683  
695  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
28000  
CFM  
274  
1.77  
2.32  
2.87  
3.48  
4.14  
4.84  
5.51  
6.18  
288  
303  
319  
335  
352  
368  
385  
403  
420  
437  
455  
473  
491  
508  
527  
545  
563  
2.19  
2.78  
3.38  
4.00  
4.69  
5.41  
6.18  
6.90  
2.67  
3.32  
3.96  
4.61  
5.30  
6.05  
6.85  
7.66  
3.23  
3.92  
4.61  
5.31  
6.02  
6.78  
7.61  
8.46  
3.86  
4.60  
5.35  
6.09  
6.83  
7.60  
8.43  
9.33  
4.58  
5.36  
6.16  
6.95  
7.73  
8.55  
9.39  
10.27  
11.33  
12.55  
13.87  
15.30  
16.87  
18.55  
20.34  
22.27  
24.35  
5.39  
6.21  
7.07  
7.90  
8.74  
9.58  
10.46  
11.63  
12.92  
14.31  
15.81  
17.44  
19.21  
21.08  
23.10  
25.26  
6.29  
7.16  
8.05  
8.95  
9.85  
10.72  
11.98  
13.33  
14.79  
16.37  
18.08  
19.90  
21.86  
23.95  
7.30  
8.21  
9.15  
10.10  
11.35  
12.71  
14.17  
15.77  
17.49  
19.35  
21.35  
23.52  
25.81  
11.05  
12.34  
13.76  
15.29  
16.93  
18.69  
20.59  
22.62  
24.82  
8.41  
9.37  
10.34  
11.65  
13.08  
14.64  
16.32  
18.15  
20.10  
22.20  
24.46  
9.63  
10.63  
12.02  
13.53  
15.16  
16.94  
18.86  
20.92  
23.13  
10.97  
12.43  
14.02  
15.74  
17.60  
19.59  
21.74  
Negative Static Pressure  
Std.  
2.25  
2.50  
Air  
RPM  
630  
630  
629  
631  
632  
635  
638  
642  
649  
657  
666  
676  
686  
697  
708  
719  
BHP  
6.15  
RPM  
666  
664  
664  
664  
665  
667  
669  
673  
677  
684  
692  
701  
711  
721  
732  
BHP  
6.80  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
21000  
22000  
23000  
24000  
25000  
6.87  
7.55  
7.62  
8.38  
8.47  
9.26  
9.34  
10.20  
11.17  
12.16  
13.30  
14.48  
15.84  
17.34  
18.98  
20.72  
22.61  
24.65  
10.23  
11.20  
12.28  
13.49  
14.85  
16.31  
17.91  
19.62  
21.49  
23.45  
25.57  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
60  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data—Exhaust Fan  
25" FC Exhaust Fan Performance w/Damper  
5
4
3
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
Volumetric Airflow Rate(CFM)  
Figure 23. Exhaust Fan Performance LOW CFM—Case B, STANDARD CFM—Case A (25" Fan)  
RT-PRC031-EN  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Exhaust Fan  
Table 22 Exhaust Fan Performance LOW CFM—Case C; STANDARD CFM — Case B (28" Fan)  
CFM  
Std.  
Negative Static Pressure  
1.00 1.25  
0.25  
0.50  
0.75  
1.50  
1.75  
2.00  
Air  
13000 237  
RPM  
BHP  
1.90  
RPM  
BHP  
2.58  
RPM  
BHP  
3.29  
RPM  
BHP  
4.06  
RPM  
BHP  
4.86  
RPM  
BHP  
5.69  
RPM  
BHP  
6.56  
RPM  
BHP  
7.46  
(i)  
289  
297  
305  
313  
322  
332  
342  
352  
361  
372  
382  
393  
404  
415  
427  
439  
450  
462  
474  
487  
499  
511  
524  
335  
341  
347  
354  
362  
370  
379  
387  
397  
406  
416  
426  
436  
446  
456  
466  
477  
488  
499  
510  
522  
534  
546  
377  
382  
387  
392  
399  
406  
413  
421  
429  
438  
446  
456  
465  
474  
484  
494  
504  
514  
524  
535  
545  
556  
567  
417  
420  
424  
429  
434  
439  
446  
452  
460  
468  
476  
484  
493  
502  
511  
520  
530  
540  
549  
560  
569  
579  
590  
455  
457  
459  
462  
467  
471  
477  
483  
490  
497  
504  
511  
520  
528  
537  
545  
554  
564  
573  
583  
593  
602  
612  
490  
491  
493  
495  
498  
502  
507  
512  
518  
524  
531  
538  
545  
553  
561  
570  
578  
587  
596  
605  
615  
624  
634  
524  
524  
525  
527  
529  
532  
536  
541  
546  
551  
557  
564  
571  
578  
585  
593  
601  
609  
618  
626  
636  
645  
654  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
CFM  
247  
2.27  
2.68  
3.15  
3.67  
4.24  
4.89  
5.59  
6.37  
2.98  
3.44  
3.95  
4.51  
5.14  
5.82  
6.57  
7.39  
3.74  
4.23  
4.78  
5.39  
6.06  
6.79  
7.59  
8.46  
4.54  
5.08  
5.65  
6.29  
7.00  
7.77  
8.62  
9.53  
10.52  
11.58  
12.73  
13.94  
15.24  
16.65  
18.14  
19.73  
21.45  
23.25  
25.17  
27.19  
29.33  
31.58  
5.39  
5.96  
6.58  
7.25  
7.98  
8.79  
9.66  
10.63  
11.65  
12.75  
13.95  
15.22  
16.59  
18.03  
19.56  
21.19  
22.93  
24.77  
26.74  
28.79  
30.97  
33.30  
6.25  
6.86  
7.52  
8.23  
9.00  
9.85  
7.14  
7.79  
8.49  
9.25  
8.07  
8.74  
9.49  
257  
267  
278  
289  
301  
312  
324  
336  
349  
361  
374  
386  
399  
412  
424  
437  
450  
463  
476  
489  
502  
10.29  
11.15  
12.06  
13.07  
14.11  
15.24  
16.45  
17.76  
19.14  
20.63  
22.20  
23.88  
25.68  
27.54  
29.53  
31.59  
33.82  
36.11  
38.52  
10.07  
10.94  
11.88  
12.90  
14.01  
15.19  
16.45  
17.80  
19.26  
20.80  
22.44  
24.18  
26.00  
27.95  
29.98  
32.12  
34.38  
36.75  
10.76  
11.75  
12.82  
13.96  
15.18  
16.51  
17.93  
19.43  
20.98  
22.69  
24.45  
26.34  
28.33  
30.46  
32.65  
34.99  
7.21  
8.13  
9.13  
8.30  
9.27  
9.40  
10.41  
11.50  
12.68  
13.95  
15.31  
16.78  
18.33  
19.98  
21.73  
23.59  
25.56  
27.65  
29.85  
10.32  
11.46  
12.68  
13.99  
15.40  
16.89  
18.49  
20.19  
22.00  
23.92  
25.94  
28.09  
10.21  
11.38  
12.64  
13.99  
15.43  
16.98  
18.63  
20.38  
22.25  
24.23  
26.33  
Negative Static Pressure  
Std.  
2.25  
2.50  
Air  
RPM  
557  
557  
556  
557  
558  
561  
564  
567  
572  
577  
583  
589  
595  
602  
609  
616  
624  
632  
640  
BHP  
8.41  
9.06  
RPM  
589  
587  
586  
586  
587  
589  
592  
595  
598  
603  
608  
614  
619  
625  
631  
639  
646  
653  
661  
669  
677  
685  
694  
BHP  
9.40  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
10.04  
10.79  
11.57  
12.44  
13.37  
14.39  
15.44  
16.58  
17.79  
19.09  
20.47  
21.89  
23.43  
25.08  
26.86  
28.70  
30.68  
32.72  
34.90  
37.20  
39.61  
42.14  
9.75  
10.51  
11.34  
12.23  
13.21  
14.22  
15.34  
16.49  
17.74  
19.08  
20.50  
22.03  
23.64  
25.35  
27.17  
29.10  
31.12  
33.28  
35.51  
37.89  
40.35  
648  
i
33000 657  
34000  
35000  
666  
674  
(i)Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
62  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Exhaust Fan  
28" FC Exhaust Fan Performance w/Damper  
5
4
3
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
Volumetric Airflow Rate(CFM)  
Figure 24. Exhaust Fan Performance LOW CFM—Case C; STANDARD CFM—Case B (28" Fan)  
RT-PRC031-EN  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Exhaust Fan  
Table 23 Exhaust Fan Performance STANDARD CFM—Case C (32" Fan)  
CFM  
Negative Static Pressure  
1.00 1.25  
Std.  
0.25  
0.50  
0.75  
1.50  
1.75  
2.00  
Air  
RPM  
BHP  
6.16  
RPM  
BHP  
7.39  
RPM  
BHP  
8.59  
RPM  
BHP  
9.96  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
(i)  
23000 272  
307  
314  
321  
328  
336  
344  
353  
362  
371  
380  
388  
397  
405  
413  
421  
429  
438  
447  
339  
345  
352  
359  
367  
374  
382  
389  
396  
403  
411  
419  
427  
436  
445  
454  
464  
472  
370  
375  
381  
387  
394  
401  
407  
415  
422  
430  
437  
445  
452  
459  
466  
474  
481  
490  
400  
405  
410  
415  
421  
426  
432  
439  
446  
452  
460  
467  
475  
482  
490  
497  
504  
511  
11.36  
12.25  
13.21  
14.21  
15.25  
16.34  
17.55  
18.87  
20.28  
21.75  
23.35  
24.99  
26.72  
28.53  
30.42  
32.41  
34.40  
36.45  
429  
433  
437  
442  
447  
452  
458  
463  
469  
475  
482  
488  
495  
502  
510  
517  
525  
533  
12.87  
13.75  
14.71  
15.79  
16.90  
18.09  
19.30  
20.59  
21.97  
23.42  
25.04  
26.72  
28.52  
30.37  
32.33  
34.42  
36.55  
38.80  
458  
460  
464  
468  
472  
477  
482  
488  
493  
498  
504  
510  
516  
523  
529  
537  
544  
551  
14.48  
15.39  
16.37  
17.43  
18.52  
19.77  
21.10  
22.47  
23.87  
25.35  
26.88  
28.53  
30.32  
32.24  
34.23  
36.35  
38.54  
40.85  
484  
487  
490  
494  
497  
501  
505  
510  
516  
521  
526  
531  
537  
543  
549  
556  
562  
569  
16.02  
17.09  
18.10  
19.19  
20.31  
21.51  
22.83  
24.25  
25.78  
27.35  
28.94  
30.60  
32.38  
34.17  
36.21  
38.32  
40.58  
42.91  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
37000  
38000  
39000  
40000  
CFM  
280  
6.87  
8.17  
9.42  
10.77  
11.66  
12.62  
13.69  
14.84  
16.03  
17.34  
18.69  
20.13  
21.63  
23.22  
24.80  
26.47  
28.23  
30.10  
32.06  
34.17  
288  
296  
305  
314  
323  
333  
343  
353  
363  
373  
383  
393  
403  
413  
423  
433  
7.63  
8.98  
10.31  
11.27  
12.30  
13.38  
14.54  
15.73  
16.96  
18.26  
19.68  
21.17  
22.77  
24.50  
26.33  
28.27  
30.28  
32.35  
8.45  
9.83  
9.34  
10.76  
11.77  
12.88  
14.07  
15.35  
16.70  
18.08  
19.53  
21.04  
22.63  
24.29  
26.08  
27.96  
29.96  
10.30  
11.35  
12.50  
13.73  
15.04  
16.44  
17.91  
19.48  
21.14  
22.89  
24.73  
26.68  
28.72  
Negative Static Pressure  
Std.  
2.25  
2.50  
Air  
RPM  
508  
512  
516  
518  
522  
525  
528  
533  
537  
542  
547  
553  
558  
563  
569  
574  
580  
587  
BHP  
RPM  
533  
536  
538  
542  
545  
548  
551  
555  
559  
563  
567  
573  
578  
583  
589  
594  
599  
605  
BHP  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
37000  
38000  
39000  
40000  
(i)  
17.55  
18.66  
19.86  
20.99  
22.20  
23.44  
24.70  
26.15  
27.65  
29.27  
30.93  
32.72  
34.53  
36.37  
38.34  
40.38  
42.59  
44.97  
19.11  
20.29  
21.48  
22.78  
24.08  
25.34  
26.71  
28.11  
29.63  
31.19  
32.90  
34.74  
36.62  
38.64  
40.69  
42.77  
44.90  
47.20  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
64  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Exhaust Fan  
32" FC Exhaust Fan Performance w/Damper  
5
4
3
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
50000  
55000  
Volumetric Airflow Rate(CFM)  
Table 24 Exhaust Fan Performance STANDARD CFM—Case C (32" Fan)  
RT-PRC031-EN  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Return Fan  
Table 25 Return Fan Performance STANDARD CFM—Case A (36.5" Fan)  
CFM  
Negative Static Pressure  
1.00 1.25  
RPM RPM  
Std.  
0.25  
RPM  
0.50  
RPM  
0.75  
RPM  
1.50  
1.75  
2.00  
Air  
BHP  
2.65  
3.07  
3.55  
4.07  
4.65  
5.29  
5.99  
6.75  
7.57  
8.46  
9.43  
BHP  
3.39  
3.87  
4.39  
4.96  
5.57  
6.25  
6.99  
7.80  
8.66  
9.59  
BHP  
4.15  
4.66  
5.22  
5.84  
6.51  
7.23  
8.02  
8.87  
9.78  
10.75  
BHP  
5.00  
5.53  
6.10  
6.74  
7.45  
8.21  
9.04  
9.93  
10.89  
BHP  
5.83  
6.44  
7.08  
7.72  
8.44  
9.21  
10.07  
11.00  
RPM  
BHP  
6.65  
RPM  
BHP  
7.53  
RPM  
BHP  
8.41  
(i)  
16000 614  
647  
680  
713  
746  
780  
813  
847  
881  
915  
950  
984  
678  
710  
741  
773  
806  
839  
872  
905  
938  
972  
709  
739  
769  
799  
831  
863  
895  
928  
960  
994  
739  
767  
797  
826  
855  
886  
917  
949  
981  
767  
795  
823  
851  
881  
910  
940  
971  
797  
822  
848  
876  
904  
934  
963  
992  
825  
849  
875  
900  
928  
956  
985  
17000  
18000  
19000  
20000  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
648  
7.31  
8.19  
9.11  
683  
717  
752  
787  
822  
858  
893  
928  
964  
999  
8.01  
8.92  
9.89  
8.74  
9.73  
10.69  
11.60  
12.53  
13.54  
9.52  
10.56  
11.45  
12.34  
10.33  
11.17  
12.11  
13.31 1014 14.55  
12.00 1002 13.13 1022 14.33 1043 15.61  
11.92 1014 13.07 1034 14.24 1054 15.46 1074 16.76  
10.60 1006 11.79 1026 13.00 1046 14.21 1066 15.42 1085 16.65 1104 17.95  
10.46 1019 11.67 1039 12.91 1060 14.17 1079 15.43 1098 16.67 1116 17.93 1135 19.24  
28000 1035 11.57 1054 12.82 1073 14.11 1093 15.41 1112 16.73 1131 18.01 1148 19.31 1166 20.64  
29000 1070 12.76 1089 14.06 1108 15.39 1127 16.72 1145 18.09 1163 19.43 1181 20.76 1198 22.11  
30000 1106 14.04 1124 15.38 1142 16.73 1160 18.12 1179 19.53 1196 20.93 1213 22.31 1230 23.72  
31000 1142 15.40 1159 16.77 1176 18.17 1194 19.61 1212 21.05 1229 22.50 1246 23.93 1262 25.35  
CFM  
Std.  
Negative Static Pressure  
2.25  
2.50  
RPM  
Air  
RPM  
BHP  
9.29  
BHP  
10.20  
11.00  
11.84  
12.72  
13.68  
16000  
17000  
18000  
19000  
20000  
21000  
851  
875  
901  
925  
951  
978  
876  
900  
925  
949  
974  
10.04  
10.86  
11.70  
12.61  
13.61 1000 14.69  
22000 1007 14.67 1027 15.78  
23000 1035 15.76 1056 16.95  
24000 1064 16.89 1084 18.16  
25000 1093 18.07 1113 19.41  
26000 1123 19.32 1142 20.72  
27000 1153 20.60 1172 22.06  
28000 1183 21.99 1202 23.49  
29000 1215 23.49 1232 24.97  
30000 1247 25.14 1263 26.58  
31000 1278 26.81 1294 28.28  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
66  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data—Return Fan  
36.5" Return Fan Performance  
10  
9
8
7
6
5
4
3
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
Volumetric Airflow Rate(CFM)  
Figure 25. Return Fan Performance STANDARD CFM—Case A (36.5" Fan)  
RT-PRC031-EN  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Return Fan  
Table 26 Return Fan Performance STANDARD CFM—Case B and Case C (40" Fan)  
CFM  
Std.  
Air  
20000 571  
Negative Static Pressure  
1.00 1.25  
0.25  
RPM  
0.50  
0.75  
1.50  
1.75  
2.00  
BHP  
3.45  
3.89  
4.37  
4.90  
5.47  
6.09  
6.75  
7.46  
8.23  
9.05  
9.92  
10.85  
11.85  
12.90  
14.02  
15.20  
RPM  
BHP  
4.37  
RPM  
BHP  
5.31  
RPM  
BHP  
6.38  
6.92  
7.50  
8.12  
RPM  
BHP  
7.42  
8.04  
8.67  
9.33  
10.03  
10.79  
11.59  
12.49  
13.41  
14.40  
15.46  
16.57  
17.74  
RPM  
BHP  
8.43  
RPM  
BHP  
9.49  
RPM  
BHP  
(i)  
600  
625  
649  
674  
699  
724  
749  
774  
800  
825  
851  
877  
902  
928  
954  
980  
627  
651  
675  
699  
723  
747  
772  
797  
821  
846  
871  
896  
921  
947  
972  
998  
655  
677  
700  
722  
746  
770  
794  
818  
842  
867  
891  
916  
940  
965  
990  
682  
703  
725  
747  
769  
792  
814  
838  
862  
885  
910  
934  
958  
983  
707  
727  
748  
770  
792  
813  
836  
858  
881  
904  
928  
952  
976  
732  
752  
772  
792  
813  
835  
857  
878  
901  
923  
946  
969  
993  
758  
776  
795  
814  
835  
856  
877  
898  
920  
942  
965  
987  
10.60  
11.32  
12.11  
12.91  
13.80  
14.72  
15.68  
16.69  
17.71  
18.80  
19.92  
21.09  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
31000  
32000  
33000  
34000  
35000  
36000  
596  
4.87  
5.39  
5.85  
6.42  
9.10  
9.81  
10.20  
10.94  
11.72  
12.56  
13.44  
14.35  
15.25  
16.24  
17.26  
18.33  
19.50  
622  
648  
674  
700  
726  
752  
779  
805  
831  
858  
884  
911  
937  
964  
990  
5.97  
6.58  
7.04  
7.69  
10.56  
11.31  
12.10  
12.94  
13.83  
14.76  
15.77  
16.88  
18.00  
19.23  
8.81  
9.56  
7.24  
7.95  
8.40  
9.16  
10.37  
11.20  
12.10  
13.07  
14.08  
15.14  
16.25  
17.43  
8.70  
9.50  
9.96  
10.81  
11.71  
12.68  
13.69  
14.76  
15.90  
17.10  
10.37  
11.28  
12.26  
13.29  
14.38  
15.54  
16.76  
20.74 1010 22.30  
18.98 1000 20.48 1016 22.03 1033 23.64  
18.69 1008 20.28 1024 21.83 1040 23.41 1056 25.02  
18.37 1015 19.98 1032 21.63 1048 23.24 1064 24.86 1080 26.48  
16.44 1007 18.05 1023 19.69 1040 21.36 1057 23.05 1073 24.70 1089 26.40 1104 28.06  
37000 1017 17.76 1033 19.41 1049 21.09 1065 22.81 1082 24.54 1098 26.26 1113 27.96 1128 29.65  
38000 1043 19.15 1059 20.84 1075 22.56 1091 24.31 1107 26.09 1122 27.86 1137 29.63 1152 31.35  
39000 1070 20.61 1085 22.35 1100 24.10 1116 25.91 1132 27.71 1147 29.53 1162 31.37 1176 33.15  
40000 1097 22.14 1112 23.92 1126 25.71 1141 27.56 1157 29.41 1172 31.27 1186 33.14 1201 34.99  
41000 1123 23.75 1138 25.58 1152 27.42 1167 29.30 1182 31.20 1196 33.09 1211 35.03  
42000 1150 25.44 1164 27.30 1178 29.19 1193 31.11 1207 33.05 1221 35.00  
43000 1177 27.21 1191 29.11 1204 31.04 1218 33.01  
44000 1204 29.06 1217 31.01  
CFM  
Std.  
Negative Static Pressure  
2.25  
2.50  
Air  
RPM  
BHP  
RPM  
BHP  
20000  
21000  
22000  
23000  
24000  
25000  
26000  
27000  
28000  
29000  
30000  
782  
800  
819  
837  
856  
876  
896  
918  
940  
961  
983  
11.73  
12.46  
13.30  
14.13  
15.02  
16.01  
17.01  
18.09  
19.23  
20.34  
804  
822  
841  
859  
878  
897  
916  
937  
958  
979  
12.83  
13.64  
14.52  
15.39  
16.33  
17.31  
18.33  
19.47  
20.63  
21.86  
21.52 1001 23.11  
31000 1004 22.69 1022 24.38  
32000 1027 23.94 1044 25.69  
33000 1050 25.31 1066 27.04  
34000 1072 26.69 1088 28.44  
35000 1096 28.20 1111 29.98  
36000 1119 29.74 1134 31.52  
37000 1143 31.44 1157 33.16  
38000 1166 33.16 1181 34.98  
39000 1191 34.98 1204 36.82  
40000 1214 36.83  
(i)  
Outlined area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.  
68  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Return Fan  
40" Return Fan Performance  
10  
9
8
7
6
5
4
3
2
1
0
0
5000  
10000  
15000  
20000  
25000  
30000  
35000  
40000  
45000  
Volumetric Airflow Rate(CFM)  
Figure 26. Return Fan Performance STANDARD CFM—Case B and Case C (40" Fan)  
RT-PRC031-EN  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Heat  
1
Table 27 Natural Gas Heating Capacities  
Air Temperature Rise vs. Unit CFM  
CFM  
Heat  
Heat  
GasHeat Input Output  
Case  
Modules (MBh) (MBh) 18000  
20000  
31.3  
22000  
28.5  
24000  
26.1  
26000  
30000  
20.9  
34000  
18.4  
38000  
16.5  
42000  
14.9  
46000  
13.6  
A, B, C  
LOW  
MED  
850  
1100  
1800  
680  
880  
34.8  
24.1  
31.2  
51.0  
40.6  
36.9  
33.8  
27.0  
23.9  
21.3  
19.3  
17.6  
HIGH  
1440  
55.3  
44.2  
39.0  
34.9  
31.6  
28.9  
Notes:  
1. Actual limits may be + or - the values shown; to accurately calculate capacities, contact the local Trane Sales Office or utilize TOPSS.  
2. Follow the supply CFM ranges posted in the General Data for each case size.  
Table 28 Electric Heat Air Temperature Rise  
CFM  
Nominal  
Tons  
kw Input  
(60 Hz)  
Total  
(MBh)  
20000  
22000  
12.9  
37.9  
12.9  
20.0  
37.9  
42.9  
12.9  
37.9  
26000  
10.9  
32.1  
10.9  
16.9  
32.1  
36.3  
10.9  
32.1  
30000  
9.4  
34000  
8.3  
38000  
7.5  
42000  
6.7  
46000  
90  
265  
90  
307.2  
904.4  
307.2  
477.8  
904.4  
1023.9  
307.2  
904.4  
14.2  
A
B
C
-
14.2  
-
27.8  
9.4  
24.5  
8.3  
21.9  
7.5  
19.8  
6.7  
-
-
9.6  
-
140  
265  
300  
90  
14.7  
27.8  
31.5  
9.4  
13.0  
24.5  
27.8  
8.3  
11.6  
21.9  
24.8  
7.5  
10.5  
19.8  
22.5  
6.7  
41.7  
-
20.5  
-
14.2  
-
265  
27.8  
24.5  
21.9  
19.8  
-
Notes: Follow the supply CFM ranges posted in the General Data for each case size  
Table 29 Electric Heat kw Ranges  
Nominal Voltage  
Case  
A, C  
B
460  
575  
90-265  
90-300  
90-265  
90-300  
70  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Performance Data—Heat  
Table 30 Hot Water Coil Heating Capacities (Q/ITD)  
Water  
Flow  
High Capacity  
120  
Low Capacity  
100  
(GPM)  
40  
80  
160  
200  
30  
60  
140  
175  
Airflow  
(CFM)  
WPD  
(ft.)  
Casing  
0.3  
7.57  
8.26  
8.67  
9.21  
9.65  
10.00  
10.29  
10.39  
1.0  
2.1  
3.7  
5.6  
0.2  
0.6  
1.5  
7.05  
8.01  
8.63  
9.52  
10.28  
10.93  
2.8  
4.3  
A, B, C  
16000  
20000  
23000  
28000  
33000  
38000  
43000  
45000  
9.02  
9.59  
9.90  
10.10  
11.52  
12.44  
13.79  
14.94  
15.94  
16.83  
17.15  
5.50  
6.02  
6.34  
6.77  
7.11  
7.38  
7.61  
7.69  
6.54  
7.34  
7.85  
8.56  
9.15  
9.65  
7.29  
7.42  
10.08  
10.75  
11.69  
12.46  
13.11  
13.67  
13.87  
10.84  
11.64  
12.78  
13.74  
14.56  
15.28  
15.54  
11.25  
12.13  
13.39  
14.47  
15.40  
16.21  
16.51  
8.33  
8.50  
9.01  
9.21  
9.99  
10.25  
11.14  
11.93  
12.62  
12.88  
10.84  
11.58  
12.22  
12.46  
10.08  
10.23  
11.50  
11.71  
Notes:  
1. Capacities are expressed as MBH (Q) per degree (F) of initial temperature difference (ITD) between the entering steam temperature (F)  
and the entering (return) air temperature (F) to the coil.  
2. WPD is waterside pressure drop in feet of water  
3. Hot water capacity is at 180°F entering water temperature and 65°F entering air temperature  
4. Maximum entering water temperature is 200°F.  
5. Capacities do not include fan heat.  
Table 31 Steam Coil Heating Capacities (Q/ITD)  
High  
Cap  
Low  
Cap  
Casing  
Airflow(CFM)  
16000  
A, B, C  
7.33  
8.17  
4.99  
5.67  
6.10  
6.71  
7.20  
7.61  
7.95  
8.07  
20000  
23000  
8.73  
28000  
9.55  
33000  
10.27  
10.92  
11.52  
11.74  
38000  
43000  
45000  
Notes:  
1. Capacities are expressed as MBH (Q) per degree (F) of initial temperature difference (ITD)  
between the entering steam temperature (F) and the entering (return) air temperature (F) to  
the coil.  
2. Steam coil capacity is at 15 psig and 65°F entering air temperature.  
3. Capacities are expressed as MBH (Q) per degree (F) of initial temperature difference (ITD)  
between the entering steam temperature (F) and the entering (return) air temperature (F) to  
the coil.  
4. The maximum recommended steam pressure is 35 psig.  
5. Capacities do not include fan heat.  
Table 32 Properties of Steam  
Steam Pressure (psig)  
2
5
10  
15  
20  
25  
30  
40  
50  
Temperature of Steam (F)  
219  
227  
239  
250  
259  
267  
274  
287  
298  
RT-PRC031-EN  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Performance Data—Component  
Static Pressure Drops/Fan Drive  
Selections  
Table 33 Chilled Water Coil Airside Pressure Drop (in H 0)  
2
Chilled Water Coil  
Airside Pressure Drop (in H O)  
2
2 row  
4 row  
6 row  
8 row  
108  
fpf  
144  
fpf  
168  
fpf  
108  
fpf  
144  
fpf  
168  
fpf  
108  
fpf  
144  
fpf  
168  
fpf  
108  
fpf  
144  
fpf  
168  
fpf  
Casing CFM 80 fpf  
80 fpf  
80 fpf  
80 fpf  
16000 0.03  
20000 0.06  
23000 0.07  
0.06 0.09 0.12 0.09 0.13 0.19 0.25 0.13 0.19 0.29 0.36 0.18 0.27 0.39 0.49  
0.09 0.13 0.16 0.13 0.19 0.27 0.34 0.20 0.28 0.40 0.50 0.27 0.38 0.54 0.68  
0.11 0.16 0.19 0.17 0.24 0.33 0.41 0.25 0.35 0.49 0.61 0.34 0.48 0.67 0.83  
0.15 0.21 0.26 0.24 0.33 0.44 0.54 0.35 0.49 0.66 0.81 0.48 0.67 0.89 1.10  
0.19 0.26 0.32 0.31 0.43 0.57 0.69 0.46 0.64 0.85 1.03 0.63 0.87 1.14 1.39  
28000 0.10  
A, B, C  
33000 0.14  
38000 0.18  
43000 0.22  
45000 0.23  
0.24 0.33  
-
-
-
0.40 0.54 0.70  
-
-
-
0.59 0.80 1.04  
-
-
-
0.81 1.09 1.41  
-
-
-
0.29  
0.31  
-
-
0.49 0.65  
0.53 0.70  
-
-
0.73 0.98  
0.78 1.05  
-
-
0.99 1.34  
1.07 1.44  
-
-
Table 34 Component Static Pressure Drops (in. H O)  
2
Hydronic Heating Coil  
Data  
Gas Heating  
Electric  
Heating  
(Horiz.)  
Medium  
Heat  
Hot Water  
Low Heat  
High Heat  
Coil  
Steam Coil  
Econo  
Damper  
(wide  
open in  
H 0)  
2
Traq  
Damper  
(wide  
open in  
H 0)  
2
CFM  
All kw's  
(i)  
Return  
Damper  
Casing  
DF  
Hz  
DF  
Hz  
DF  
Hz  
High Low High Low  
16000  
20000  
23000  
28000  
33000  
38000  
43000  
45000  
0.01  
0.02  
0.03  
0.04  
0.06  
0.07  
0.10  
0.10  
0.01  
0.01  
0.01  
0.02  
0.02  
0.03  
0.04  
0.04  
0.10  
0.16  
0.21  
0.31  
0.42  
0.56  
0.72  
0.79  
0.01  
0.01  
0.01  
0.02  
0.02  
0.03  
0.04  
0.04  
0.12  
0.19  
0.26  
0.38  
0.53  
0.70  
0.89  
0.98  
0.01  
0.01  
0.01  
0.02  
0.02  
0.03  
0.04  
0.04  
0.14  
0.22  
0.30  
0.44  
0.61  
0.81  
1.03  
1.13  
0.13  
0.17  
0.23  
0.32  
0.42  
0.53  
0.65  
0.71  
0.08  
0.11  
0.15  
0.21  
0.28  
0.36  
0.45  
0.49  
0.12  
0.16  
0.22  
0.31  
0.41  
0.52  
0.65  
0.70  
0.08  
0.11  
0.16  
0.22  
0.30  
0.39  
0.49  
0.53  
0.06  
0.09  
0.13  
0.20  
0.28  
0.38  
0.49  
0.53  
0.11  
0.15  
0.23  
0.34  
0.47  
0.63  
0.81  
0.89  
0.19  
0.26  
0.38  
0.57  
0.79  
1.05  
1.34  
1.47  
A, B, C  
(i)  
There is no pressure drop with Electric Heat DF configuration  
72  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Performance Data—Component Static Pressure Drops/  
Fan Drive Selections  
Table 35 Component Static Pressure Drops (in. H O)  
2
Standard Filter Section (Cooling Coil)  
Final Filter Section (Cooling Coil)  
90-95%  
Std  
Temp  
HEPA  
Filters  
w/ 2"  
90-95% 90-95%  
90-95%  
90-95% Hi Temp 90-95%  
StdTemp Cartridge HiTemp  
StdTemp  
Low PD  
Cartridge  
Filters  
Std  
Temp  
Bag  
Filters  
w/ 2"  
Std 2"  
High  
90-95% 90-95% 90-95%  
Low PD Cartridge  
Bag  
Filters  
w/ 2"  
Cartridge  
Filters  
Filters  
w/ 2" Hi  
Temp  
HEPA  
w/ 2"  
Eff  
Cartridge  
Filters  
Filters  
w/ 2"  
Throw  
Away  
Filters  
w/4”  
w/ 2"  
HiTemp Hi Temp  
w/ 2"  
Prefilter  
Prefilter Prefilter Prefilter Prefilter Prefilter Prefilter Prefilter Prefilter  
(i)  
(ii)  
(iii)  
(iv)  
(v)  
(vi)  
(vii)  
(viii)  
Casing CFM  
16000  
0.08  
0.11  
0.11  
0.18  
0.23  
0.28  
0.33  
0.36  
0.24  
0.29  
0.29  
0.49  
0.61  
0.74  
0.89  
0.95  
0.27  
0.32  
0.32  
0.49  
0.61  
0.76  
0.92  
0.99  
0.34  
0.39  
0.39  
0.56  
0.67  
0.78  
0.91  
0.96  
0.23  
0.29  
0.29  
0.51  
0.65  
0.81  
0.98  
1.05  
0.36  
0.42  
0.42  
0.61  
0.73  
0.86  
1.00  
1.06  
0.29  
0.34  
0.34  
0.54  
0.69  
0.86  
1.05  
1.13  
0.35  
0.42  
0.42  
0.68  
0.86  
1.06  
1.30  
1.40  
0.54  
0.66  
0.66  
1.01  
1.22  
-
0.48  
0.58  
0.58  
0.88  
1.06  
-
20000  
23000  
28000  
A, B, C  
33000  
38000  
43000  
-
-
45000  
-
-
(i)  
(ii)  
Case A, B, C Max CFM 50000  
Case A, B, C Max CFM 50000  
(iii) Case A, B, C Max CFM 55500  
(iv) Case A, B, C Max CFM 46250  
(v)  
Case A, B, C Max CFM 46250  
(vi) Case A, B, C Max CFM 46250  
(vii)Case A, B, C Max CFM 37000  
(viii)Case A, B, C Max CFM 37000  
RT-PRC031-EN  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Performance Data—Component Static Pressure Drops/  
Fan Drive Selections  
Table 36 Supply Air Fan Drive Selections  
Horse Power (HP)  
30 HP 40 HP  
15 HP  
20 HP  
25 HP  
50 HP  
60 HP  
75 HP  
Low/  
Std  
Casing  
RPM  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1500  
1400  
1300  
1200  
1100  
1000  
900  
Drive No. Drive No. Drive No. Drive No. Drive No. Drive No. Drive No. Drive No.  
L
K
J
A
Std  
H
G
F
E
E
F
E
E
D
C
D
B
Std  
C
B
B
A
A
9
9
(i)  
1300  
1200  
1100  
1000  
900  
D
C
D
C
B
B
A
C
Std  
A
9
9
8
9
8
800  
8
(i)  
If a 75HP motor is chosen on a fan with IGV, drives D and E are allowed. If it is chosen on a fan without IGV only drive D is allowed.  
74  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance Data—Component Static Pressure Drops/  
Fan Drive Selections  
Table 37 Exhaust Air Fan Drive Selections  
Horse Power (HP)  
20 HP 25 HP  
Drive No. Drive No. Drive No. Drive No. Drive No. Drive No. Drive No. Drive No. Drive No.  
7.5 HP  
10 HP  
15 HP  
30 HP  
40 HP  
50 HP  
60 HP  
Casing  
Low/ Std  
RPM  
700  
600  
500  
400  
700  
600  
500  
400  
600  
500  
400  
300  
600  
500  
400  
300  
500  
400  
300  
7
6
5
7
6
6
5
4
6
5
4
6
5
4
Std  
A
7
6
5
7
6
6
5
4
6
5
4
6
5
4
B
B
Low  
Std  
6
5
4
6
5
4
6
5
4
6
5
4
6
5
5
4
3
4
3
4
3
6
5
4
6
5
4
6
5
4
6
5
4
6
5
5
4
3
C
C
Low  
Std  
4
3
4
3
6
6
5
4
5
4
5
4
5
5
Table 38 Return Air Fan Drive Selections  
Horse Power (HP)  
Low/  
Std  
Casing  
RPM  
7.5  
10 15 HP  
20 HP  
25 HP  
30 HP  
40 HP  
Drive No. Drive No. Drive No. Drive No. Drive No. Drive No. Drive No.  
1400  
1300  
1200  
1100  
1000  
900  
E
D
C
C
B
A
A
Std  
A
9
800  
8
7
8
700  
1200  
1100  
1000  
900  
C
B
B
A
A
B, C  
Std  
9
800  
8
700  
7
RT-PRC031-EN  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical Data  
equal a standard fuse size as listed in  
NEC 240-6, select the next higher  
standard fuse rating.  
NEC 240-6, select the next higher  
standard fuse rating.  
Electrical Service Sizing  
To correctly size electrical service  
wiring for a unit, find the appropriate  
calculations listed below. Each type  
of unit has its own set of calculations  
for MCA (Minimum Circuit  
Note: If the selected RDE is greater  
than the selected MOP value,  
then select the RDE value to  
equal the MOP value.  
Note: If the selected RDE is greater  
than the selected MOP value,  
then select the RDE value to  
equal the MOP value.  
Ampacity), MOP (Maximum  
GENERAL NOTE  
Overcurrent Protection), and RDE  
(Recommended Dual Element fuse  
size). Read the load definitions that  
follow and then find the appropriate  
set of calculations based on unit  
type.  
Set 2. Cooling with Electric Heat  
Note: The selected MOP value is  
stamped in the MOP field on  
the nameplate.  
To arrive at the correct MCA, MOP,  
and RDE values for these units, two  
sets of calculations must be  
performed. First calculate the MCA,  
MOP, and RDE values as if the unit  
was in cooling mode (use the  
equations given in Set 1). Then  
calculate the MCA, MOP, and RDE  
values as if the unit were in the  
heating mode as follows.  
Note: Set 1 is for cooling only and  
cooling with gas heat units,  
and set 2 is for cooling with  
electric heat units.  
Load Definitions: (To determine load  
values, see the Electrical Service  
Sizing Data Tables on the following  
page.)  
MCA = 1.25 x (LOAD1 + LOAD2 +  
LOAD4) + LOAD3  
LOAD1 = CURRENT OF THE  
LARGEST MOTOR  
The nameplate MCA value will be  
the larger of the cooling mode MCA  
value or the heating mode MCA  
value calculated above.  
LOAD2 = SUM OF THE CURRENTS  
OF ALL REMAINING MOTORS  
MOP = (2.25 x LOAD1) + LOAD2 +  
LOAD3 + LOAD4  
LOAD3 = CURRENT OF ELECTRIC  
HEATERS  
The selection MOP value will be the  
larger of the cooling mode MOP  
value or the heating mode MOP  
value calculated above.  
LOAD4 = ANY OTHER LOAD RATED  
AT 1 AMP OR MORE  
Set 1. Cooling with Gas Heat Air  
Handling Units  
Select a fuse rating equal to the MOP  
value. If the MOP value does not  
equal a standard fuse size as listed in  
NEC 240-6, select the next lower  
standard fuse rating.  
MCA = (1.25 x LOAD1) + LOAD2 +  
LOAD4  
MOP = (2.25 x LOAD1) + LOAD2 +  
LOAD4  
Note: If selected MOP is less than  
the MCA, then select the  
lowest standard maximum  
fuse size which is equal to or  
larger than the MCA,  
Select a fuse rating equal to the MOP  
value. If the MOP value does not  
equal a standard fuse size as listed in  
NEC 240-6, select the next lower  
standard fuse rating.  
provided the selected fuse  
size does not exceed 800  
amps.  
Note: If selected MOP is less than  
the MCA, then select the  
lowest standard maximum  
fuse size which is equal to or  
larger than the MCA,  
RDE = (1.5 x LOAD1) + LOAD2 +  
LOAD3 + LOAD4  
The selection RDE value will be the  
larger of the cooling mode RDE  
value or the heating mode RDE value  
calculated above.  
provided the selected fuse  
size does not exceed 800  
amps.  
RDE = (1.5 x LOAD1) + LOAD2 +  
LOAD4  
Select a fuse rating equal to the RDE  
value. If the RDE value does not  
equal a standard fuse size as listed in  
Select a fuse rating equal to the RDE  
value. If the RDE value does not  
76  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical Data  
Table 39 Electrical Service Sizing Data—Motors  
Supply Fan Motors  
Motor Horsepower  
460 V  
FLA  
19.3  
25.5  
30.5  
37.5  
48.5  
61  
575 V  
FLA  
15.4  
20.4  
24.5  
30  
15  
20  
25  
30  
40  
50  
60  
75  
39  
49.2  
58  
72  
88  
70  
Exhaust/Return Fan Motors  
Motor Horsepower  
460 V  
FLA  
10  
575 V  
FLA  
8
7.5  
10  
15  
20  
25  
30  
40  
50  
60  
13.2  
19.3  
25.5  
30.5  
37.5  
48.5  
61  
10.3  
15.4  
20.4  
24.5  
30  
39  
49.2  
58  
72  
Table 40 Electrical Service Sizing Data—Electric Heat Module  
(Electric Heat units Only)  
Voltage  
460  
FLA  
575  
FLA  
Module kw  
90  
108.3  
168.4  
318.8  
360.8  
86.6  
134.7  
255  
140  
265  
300  
288.7  
Table 41 Electrical Service Sizing Data—Control Power  
Transformer (Heating Mode Only)  
Voltages  
460  
FLA  
3
575  
FLA  
3
Digit 2 Unit  
Function  
Unit Size  
E, L, S, X  
F (850 MBH)  
F (1100 MBH)  
F (1800 MBH)  
4
4
A, B, C  
4
4
4
4
RT-PRC031-EN  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical Data  
Table 42 Voltage Utilization Range  
Unit Voltage  
460/60/3  
575/60/3  
414-506  
517-633  
Table 43 Electrical Service Sizing Data - Convenience Outlet Transformer  
Nominal Tons  
Voltage  
460  
575  
FLA Add  
2.6  
FLA Add  
90-150  
3.3  
78  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Figure 27. Unit Top/Front View  
RT-PRC031-EN  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensional Data  
Unit Dimensions  
Table 44 Unit Dimensions (In.)—One-Piece Unit  
ONE-PIECE Dimensions  
Lifting Lug Locations  
Air Handler Side  
Unit Dimensions  
Unit Width  
Blank  
Section  
Casing  
A
B
C1  
66  
66  
66  
C2  
C3  
C4  
n/a  
n/a  
n/a  
M
N
None  
4Ft  
334 2/16 159 15/16  
382 5/16 159 15/16  
430 9/16 159 15/16  
252 14/16  
n/a  
139 13/16 143 8/16  
139 13/16 143 8/16  
139 13/16 143 8/16  
A, B, C  
252 14/16 368 6/16  
252 14/16 416 10/16  
8Ft  
Return  
Fan  
Exhaust  
Fan  
Unit Height  
Casing  
O
P
J
K
103 12/16 97 9/16  
103 12/16 97 9/16  
103 12/16 97 9/16  
103 12/16 97 9/16  
103 12/16 97 9/16  
103 12/16 97 9/16  
29 3/16  
29 3/16  
29 3/16  
n/a  
17  
17  
17  
17  
17  
17  
A, B, C  
n/a  
n/a  
80  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Unit Dimensions  
Table 45 Downflow/Horizontal Airflow Configuration Dimensions (In.)  
DOWNFLOW Opening Dimensions  
Return Opening—with or  
without Exhaust Fan  
Return Opening—with Return Fan  
Blank  
Gas Heat Section  
Casing  
X1  
Y1  
W1  
L1  
X1  
Y1  
W1  
L1  
No Gas  
No Gas  
No Gas  
Gas  
None  
4Ft  
14 13/16  
14 13/16  
14 13/16  
14 13/16  
14 13/16  
8 14/16  
8 14/16  
8 14/16  
8 14/16  
8 14/16  
48 3/16 121 15/16 14 13/16 42 14/16  
48 3/16 121 15/16 14 13/16 42 14/16  
48 3/16 121 15/16 14 13/16 42 14/16  
48 3/16 121 15/16 14 13/16 42 14/16  
48 3/16 121 15/16 14 13/16 42 14/16  
DOWNFLOW Opening Dimensions  
48 3/16  
48 3/16  
48 3/16  
48 3/16  
48 3/16  
53 14/16  
53 14/16  
53 14/16  
53 14/16  
53 14/16  
A, B, C  
8Ft  
None  
8Ft  
Gas  
Supply Opening  
Blank  
Casing  
Gas Heat Section  
X2  
Y2  
13  
13  
13  
13  
13  
W2  
L2  
No Gas  
No Gas  
No Gas  
Gas  
None  
4Ft  
256 1/16  
304 4/16  
352 8/16  
256 1/16  
352 8/16  
47 14/16 102 8/16  
47 14/16 102 8/16  
A, B, C  
8Ft  
47 14/16 102 8/16  
None  
8Ft  
47 14/16 102 8/16  
Gas  
47 14/16 102 8/16  
HORIZONTAL Opening Dimensions  
Return Side Opening  
Return End Opening  
Blank  
Gas Heat Section  
Casing  
X3  
Y3 W3  
H1  
X1  
Y3  
H3  
H1  
No Gas  
No Gas  
No Gas  
Gas  
None  
4Ft  
9 5/16  
9 5/16  
9 5/16  
9 5/16  
9 5/16  
10 10/16 54 12/16 84 15/16  
10 10/16 54 12/16 84 15/16  
10 10/16 54 12/16 84 15/16  
10 10/16 54 12/16 84 15/16  
10 10/16 54 12/16 84 15/16  
6 5/16  
6 5/16  
6 5/16  
6 5/16  
6 5/16  
8 3/16  
8 3/16  
8 3/16  
8 3/16  
8 3/16  
35 3/16 127 2/16  
35 3/16 127 2/16  
35 3/16 127 2/16  
35 3/16 127 2/16  
35 3/16 127 2/16  
A, B, C  
8Ft  
None  
8Ft  
Gas  
HORIZONTAL Opening Dimensions  
Supply Opening  
Blank  
Gas Heat Section  
Casing  
X4  
Y4  
W4  
H2  
No Gas  
No Gas  
No Gas  
Gas  
None  
4Ft  
254 12/16 10 10/16 54 12/16 84 15/16  
302 15/16 10 10/16 54 12/16 84 15/16  
351 3/16 10 10/16 54 12/16 84 15/16  
254 12/16 10 10/16 54 12/16 66 11/16  
351 3/16 10 10/16 54 12/16 84 15/16  
A, B, C  
8Ft  
None  
8Ft  
Gas  
RT-PRC031-EN  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Electrical Entry Details  
Figure 28. Electrical Entry Details/Bottom View  
11  
31  
16  
16  
3
4
60  
11  
53  
16  
5
1
4
51  
81  
8
1
1
76  
48  
16  
1
4
1
4
71  
3
4
46  
16  
44  
5
5
5
6
61  
16  
16  
Outside edge of  
base rail  
1
External customer  
16 connection points  
Ø1  
7
1
2
Marine lights  
Ø
Ø1  
customer supplied 8  
5
8
Ø3  
Unit power  
power service  
entrance  
82  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Piping  
Figure 29. Piping Enclosure  
RT-PRC031-EN  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Figure 30. Chilled Water Piping Locations  
84  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Minimum Clearance Details  
(i)  
Figure 31. Minimum Required Clearance  
AH  
R
Cool  
Coil  
(R)  
ER Fltr  
(L&R) (R)  
Blank Section  
Fnl  
Fltr (R)  
Fltr  
(R)  
Fresh  
Air  
Std  
Option  
Std  
As Req.  
Exh  
Ctrl Box  
Final  
Filter  
(L&R)  
Exhaust  
Filters  
Std  
C Box  
VFD  
VFD  
Heat  
Fresh  
Air  
Cool  
Coil  
(F)  
Fnl  
Fltr (F)  
Sup  
Mtr  
Std  
Heat  
(L&R)  
As Req.  
Rtn  
Mtr  
Sup  
VFD  
As Req.  
Rtn  
VFD  
ER Fltr  
(L&R) (F)  
Fltr  
(F)  
Std  
As Req.  
As Req.  
Std  
Std  
Std  
AH  
L
(i)  
Unit drawing is representative only and may not accurately depict all models.  
Table 46 Minimum Required Clearance  
Unit Option Selection (Door Swing Ft. and In.)  
Standard  
VFD  
Heat  
Electric/  
Return/  
Exhaust  
Hot Water/ Two-side  
Door Location  
Exhaust Motor  
Availability  
Std  
A,B,C  
2' 2"  
*
Supply  
Steam  
Access  
Final Filter  
*
2' 2"  
*
*
*
*
*
*
*
*
Exhaust VFD  
As Req.  
Std  
*
Filter (Front)  
2' 8"  
*
*
*
*
*
Filter (Rear)  
Option  
Std  
*
*
*
2’ 2"  
*
*
Cooling Coil (Front)  
Cooling Coil (Rear)  
or Cooling Coil (Rear)  
Supply Motor  
2' 2"  
2' 8"  
*
*
*
*
*
*
Std  
*
*
*
*
Option  
Std  
*
*
*
*
*
2' 8"  
*
*
*
*
*
*
Supply VFD  
As Req.  
As Req.  
As Req.  
As Req.  
Std  
*
2' 2"  
*
*
*
*
Heat (Left & Right)  
Final Filter (Front)  
Final Filter (Rear)  
Control Box (L & R)  
*
*
2' 2"  
*
*
*
*
*
*
*
2' 2"  
2' 2"  
*
*
*
*
*
*
3' 2"  
*
*
*
*
Minimum Required Clearance (Ft.)  
Control  
Box  
AH_L  
AH_R  
Exh  
8’  
8’  
8’  
6’  
RT-PRC031-EN  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dimensional Data  
Downflow Roof Curb  
Figure 32. Optional Roof Curb (Downflow)  
Table 47 Downflow Roof Curb Dimensions (In.)  
Dimensions  
Blank  
Casing Section  
A
B
C
D
123  
E
F
G
H
I
J
None  
11 15/16 49 8/16  
11 15/16 49 8/16  
11 15/16 49 8/16  
5 15/16  
5 15/16  
5 15/16  
253 2/16 49 8/16 20 15/16  
301 5/16 49 8/16 20 15/16  
349 9/16 49 8/16 20 15/16  
104  
104  
104  
11 15/16 1 13/16  
11 15/16 1 13/16  
11 15/16 1 13/16  
A, B, C  
4Ft  
8Ft  
123  
123  
Dimensions  
Blank  
Casing Section  
K
L
M
P
R
S
T
None  
1 13/16 314 9/16 134 14/16 163 15/16 139 7/16 28 15/16 29 1/16  
1 13/16 362 12/16 134 14/16 163 15/16 139 7/16 28 15/16 29 1/16  
A, B, C  
4Ft  
8Ft  
1 13/16  
411  
134 14/16 163 15/16 139 7/16 28 15/16 29 1/16  
Cross Member Location  
Blank  
Casing Section  
U1  
n/a  
n/a  
n/a  
U2  
n/a  
n/a  
n/a  
W1  
W2  
W3  
W4  
W5  
W6  
n/a  
n/a  
W7  
n/a  
n/a  
n/a  
None  
103 6/16 145 11/16 183 6/16 218 4/16  
n/a  
A, B, C  
4Ft  
8Ft  
103 6/16 145 11/16 187 15/16 231 10/16 266 8/16  
103 6/16 145 11/16 189 15/16 234 3/16 279 13/16 314 11/16  
86  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Field Installed Sensors — Variable Air Volume (VAV)  
Figure 33. Field Installed VAV Zone Sensors  
SINGLE SETPOINT SENSOR WITH SYSTEM FUNCTION LIGHTS  
(BAYSENS021*)  
Notes:  
PROGRAMMABLE NIGHT-SETBACK SENSOR (BAYSENS020*)  
1. Remote sensors are available for use with all zone sensors  
to provide remote sensing capabilities.  
RT-PRC031-EN  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Field Installed Sensors — Constant Volume (CV)  
Figure 34. Field Installed CV Zone Sensors  
PROGRAMMABLE NIGHT-SETBACK SENSOR (BAYSENS019*)  
DUAL SETPOINT, MANUAL/AUTOMATIC CHANGEOVER  
SENSOR WITH SYSTEM FUNCTION LIGHTS (BAYSENS010*)  
WITHOUT LED STATUS INDICATORS (BAYSENS008*)  
SINGLE SETPOINT WITHOUT LED STATUS INDICATORS  
(BAYSENS006*)  
Notes:  
1. Remote sensors are available for use with all zone sensors  
to provide remote sensing capabilities.  
88  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Field Installed Sensors — VAV and CV  
Figure 35. Field Installed VAV and CV Zone Sensors  
1-3/32 [27,43 mm]  
2-29/32 [73,55 mm]  
2-29/32 [73,55 mm]  
4-11/16 [118,75 mm]  
4-11/16 [118,75 mm]  
RIGHT  
FRONT  
RIGHT  
FRONT  
ZONE TEMPERATURE SENSOR W/TIMED  
OVERRIDE BUTTON AND LOCAL  
SETPOINT ADJUSTMENT (BAYSENS074*)  
ZONE TEMPERATURE SENSOR W/TIMED OVERRIDE  
BUTTONS (BAYSENS073*)  
ALSO AVAILABLE SENSOR ONLY (BAYSENS077*)  
TEMPERATURE SENSOR (BAYSENS016*)  
Notes:  
1. Remote sensors are available for use with all zone sensors  
to provide remote sensing capabilities.  
REMOTE MINIMUM POSITION POTENTIOMETER CONTROL (BAYSTAT023*)  
RT-PRC031-EN  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Field Installed Sensors — VAV and CV  
Figure 36. Field Installed VAV and CV Zone Sensors  
2.90 in. (73.5 mm)  
1.08 in. (2.75 mm)  
TYP 0.12 in. (3.0 mm)  
3.27 in.  
(83 mm)  
4.78 in. (121.4 mm)  
Mounting hole  
TYP R0.07 in.  
(R1.9 mm)  
17.8 in.  
(0.70 mm)  
Note: The dimensions are the  
same for both the sensor  
and the receiver.  
2.62 in. (66.5 mm)  
WIRELESS ZONE SENSOR  
WALL OR DUCT MOUNT CO2 ZONE SENSORS  
90  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table 48 Approximate Operating Weights (Lbs.)  
Roof Curb  
(Minimum)  
Nominal Tons  
Unit (Minimum)  
A
8580  
8782  
8910  
1066  
B
C
1066  
1066  
Notes:  
1. Weights shown include the following features: standard coils, 0-25% Fresh Air, throwaway filters, low cfm supply fan, minimum motor sizes (high  
efficiency), constant volume, 460 XL, No heat  
2. Weights shown represent approximate operating weights and have a + 5% accuracy. To calculate weight for a specific unit configuration, utilize TOPSS  
or contact the local Trane sales representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT NAMEPLATE.  
Table 49 Component Weights (Lbs.)  
A
B
C
Size  
Wt (lbs.)  
Size  
Wt (lbs.)  
Size  
Wt (lbs.)  
Supply Fan Assembly  
Supply Fan & FanBoard Assy.  
IGV  
25"  
1226  
112  
116  
233  
284  
181  
206  
358  
413  
495  
604  
-
32"  
1419  
88  
36"  
1530  
66  
Belt Guard  
116  
233  
284  
181  
206  
358  
413  
495  
604  
776  
-
116  
233  
284  
181  
206  
358  
413  
495  
604  
776  
879  
Supply VFD (50 HP and below)  
Supply VFD (60 thru 75 HP)  
Supply-Exh Fan Motor - 15 HP  
Supply-Exh Fan Motor - 20 HP  
Supply-Exh Fan Motor - 25 HP  
Supply-Exh Fan Motor - 30 HP  
Supply-Exh Fan Motor - 40 HP  
Supply-Exh Fan Motor - 50 HP  
Supply-Exh Fan Motor - 60 HP  
Supply-Exh Fan Motor - 75 HP  
Return/Exhaust Fan Assembly  
Return Fan & Dampers  
-
36"  
25"  
-
2284  
879  
-
40"  
25"  
28"  
2333  
879  
963  
119  
244  
295  
160  
181  
206  
206  
358  
413  
495  
604  
-
40"  
28"  
32"  
2333  
963  
1417  
119  
244  
295  
-
Exhaust Fan & Dampers - Low CFM  
Exhaust Fan & Dampers - Hi. CFM  
Belt Guard  
119  
244  
295  
160  
181  
206  
206  
358  
-
Exhaust VFD (50 HP and below)  
Exhaust VFD (60 HP)  
Exh Fan Motor - 7.5 HP  
Exh Fan Motor - 10 HP  
181  
206  
206  
358  
413  
495  
604  
776  
Exh Fan Motor - 15 HP  
Exh Fan Motor - 20 HP  
Exh Fan Motor - 25 HP  
Exh Fan Motor - 30 HP  
Exh Fan Motor - 40 HP  
-
Exh Fan Motor - 50 HP  
-
Exh Fan Motor - 60 HP  
-
Chilled Water Assy.  
2 Row 5W Chilled Water Coil -  
80 FPF  
992  
992  
992  
2 Row 5W Chilled Water Coil -  
108 FPF  
1042  
1106  
1148  
1042  
1106  
1148  
1042  
1106  
1148  
2 Row 5W Chilled Water Coil -  
144 FPF  
2 Row 5W Chilled Water Coil -  
168 FPF  
RT-PRC031-EN  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Weights  
Table 49 Component Weights (Lbs.)  
A
B
C
Size  
Wt (lbs.)  
Size  
Wt (lbs.)  
Size  
Wt (lbs.)  
4 Row W Chilled Water Coil -  
80 FPF  
1523  
1622  
1750  
1835  
2046  
2195  
2387  
2515  
2643  
2842  
3098  
3268  
1523  
1622  
1750  
1835  
2046  
2195  
2387  
2515  
2643  
2842  
3098  
3268  
1523  
1622  
1750  
1835  
2046  
2195  
2387  
2515  
2643  
2842  
3098  
3268  
4 Row W Chilled Water Coil -  
108 FPF  
4 Row W Chilled Water Coil -  
144 FPF  
4 Row W Chilled Water Coil -  
168 FPF  
6 Row WD Chilled Water Coil -  
80 FPF  
6 Row WD Chilled Water Coil -  
108 FPF  
6 Row WD Chilled Water Coil -  
144 FPF  
6 Row WD Chilled Water Coil -  
168 FPF  
8 Row WD Chilled Water Coil -  
80 FPF  
8 Row WD Chilled Water Coil -  
108 FPF  
8 Row WD Chilled Water Coil -  
144 FPF  
8 Row WD Chilled Water Coil -  
168 FPF  
External Piping Cabinet  
External Piping Cabinet - Shipping  
External Piping Cabinet - Operation  
Gas/Electric Heat  
Gas Heat Low  
353  
268  
353  
268  
353  
268  
0.85M  
1.1M  
1.8M  
690  
840  
0.85M  
1.1M  
1.8M  
690  
840  
0.85M  
1.1M  
1.8M  
690  
840  
Gas Heat Med  
Gas Heat High  
1150  
485  
1150  
485  
1150  
485  
Electric Heat  
Hydronic Heat  
Steam Heat Low  
946  
946  
946  
Steam Heat High  
1014  
1080  
1125  
1014  
1080  
1125  
1014  
1080  
1125  
Hot Water Heat Low  
Hot Water Heat High  
Filters  
Filter Rack - Throwaway Filters  
Filter Rack - Bag Filters  
Filter Rack - Cartridge Filters  
Final Filters - Bag Filters  
181  
395  
662  
392  
607  
181  
395  
662  
392  
607  
181  
395  
662  
392  
607  
Final Filters - Cartridge Filters  
w/ 2" pre-filter  
Final Filters - Cartridge Filters  
w/ 4" pre-filter  
638  
638  
638  
Final Filters - High Temp. Cartridge  
Final Filters - HEPA  
Final Filters - HEPA High Temp.  
Fresh Air  
669  
1777  
1839  
669  
1777  
1839  
669  
1777  
1839  
0-25% Damper  
611  
759  
715  
611  
759  
715  
611  
759  
715  
Econ  
Econ w/ Air Measure  
Cabinet  
Cabinet  
5971  
846  
5971  
846  
5971  
846  
Cabinet - 4' Blank Section  
Cabinet - 8' Blank Section  
1650  
1650  
1650  
92  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table 49 Component Weights (Lbs.)  
A
B
C
Size  
Wt (lbs.)  
Size  
Wt (lbs.)  
Size  
Wt (lbs.)  
Control Box - Main  
Control Box - Main  
Convenience Outlet  
454  
36  
454  
36  
454  
36  
Table 50 Roof Curb Weights  
Installed  
Weight  
Shipping  
Weight  
Casing  
Blank  
None  
4 Ft  
1066  
1147  
1228  
1334  
1415  
1497  
A, B, C  
8 Ft  
RT-PRC031-EN  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
A full range of factory installed  
options are available, allowing for  
the air handler design that best suits  
each individual application.  
For both CV and Variable Air  
Volume (VAV) air handlers, the  
100 percent modulating exhaust  
discharge dampers are  
modulated in response to  
building pressure. A differential  
pressure control system,  
Statitrac, uses a differential  
pressure transducer to compare  
indoor building pressure to  
atmospheric pressure. The FC  
exhaust fan is turned on when  
required to lower building static  
pressure to setpoint. The  
Statitrac control system then  
modulates the discharge  
Blank Sections  
Four Foot Blank Section—Solid  
double wall construction with  
foam injected insulation. The  
blank section is located at the  
airflow discharge. Single point  
latching, hinged access doors  
are located on either side of the  
blank section. Final filter options  
are available for cooling only  
units.  
Chilled Water Cooling  
ARI certified type 5W, W, or WD  
coils provided with water  
modulating valve and actuator.  
Turbulators and various row, fin  
series, and valve options are  
available.  
Eight Foot Blank Section—Solid  
double wall construction with  
foam injected insulation. The  
blank section is located at the  
airflow discharge. Single point  
latching, hinged access doors  
are located on either side of the  
blank section. Final filter options  
are available for all units.  
Cooling Only/Heating Casings  
Cooling Only—Extended casing  
of solid double wall construction  
with foam injected insulation  
throughout the air handler.  
dampers to control the building  
pressure to within the  
adjustable, specified deadband  
that is set at the Human Interface  
Panel.  
Electric Heat—Nickel-chromium  
electric heating elements in  
individually fused circuits of 48  
amps or less and with all  
100 Percent Modulating Exhaust  
Fan with Statitrac Control and  
Variable Frequency Drive—  
Provided with all the necessary  
controls to control/maintain  
building space pressure through  
a CV or VAV air handler. The  
Variable Frequency Drive (VFD)  
modulates the speed of the  
exhaust fan motor in response  
to building pressure. A  
Fan Options  
Standard CFM supply exhaust/  
necessary safeties. A full range  
of sizing options is available.  
return fans—Available to meet  
standard airflow application  
needs.  
Natural Gas Heat-Two-Stage—  
Two-pass stainless steel tubular  
free floating heat exchanger has  
industrial type burner and  
combustion blower. Available  
with high, medium and low fire  
and UL and CSA approval.  
Low CFM exhaust fans—  
Available to meet low leaving air  
temperature requirements.  
differential pressure control  
system, Statitrac, uses a  
Power Supply  
Natural Gas Heat-Full  
Air Handlers are available with 460  
or 575 voltage, 3 phase 60 hertz  
power supply.  
differential pressure transducer  
to compare indoor building  
pressure to atmospheric  
Modulation—The heat  
exchanger drum, tubes and front  
and rear headers are  
pressure. The 0-100%  
constructed of corrosion  
resistant stainless steel.  
Available with high, medium  
and low fire and UL and CSA  
approval.  
modulating relief dampers  
modulate in response to a signal  
from the unit microprocessor,  
based upon the space static  
pressure, and causes the  
Exhaust  
No Exhaust—Air Handlers can  
be built for makeup air  
applications with no exhaust.  
Relief opening is sealed  
watertight.  
damper to modulate open or  
closed as required to maintain  
the space pressure within the  
deadband.  
Steam Heat—ARI certified type  
NS coil with non-freeze steam  
distribution. Coils are pitched for  
drainage and are provided with  
steam modulating valve with  
actuator. High and low heat  
options are available.  
100 Percent Modulating Exhaust  
Fan—A double width, double  
inlet forward-curved fan can  
exhaust up to 100 percent  
supply air. The fan operates  
when economizer damper is  
open greater than minimum  
position. Discharge dampers at  
fan outlet modulate in response  
to economizer damper position  
on Constant Volume (CV) air  
handlers.  
100 Percent Modulating Exhaust  
Fan with Statitrac Control and  
Variable Frequency Drive and  
Bypass—Bypass control  
provides full nominal airflow in  
the event of drive failure.  
Hot Water Heat—ARI certified  
type 5W coil mounted for  
drainage and provided with hot  
water modulating valve with  
actuator. High and low heat  
options are available.  
Return  
100 Percent Modulating Return  
Fan—A single width plenum fan  
with airfoil blade can relieve up  
100 Percent Modulating Exhaust  
Fan with Statitrac™ Control—  
94  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Options  
to 100 percent supply air. The fan  
operates in conjunction with the  
supply fan. The relief damper  
modulates in response to  
economizer damper position on  
Constant Volume air handlers.  
Standard throwaway filters—U.L.  
eight-foot blank section, as well  
as steam and hot water units  
with eight-foot blank section,  
unit casing only.  
Class 2, two-inch nominal  
thickness, high efficiency pleated  
media filters rated MERV 7 per  
ASHRAE 52.2. Filters are  
mounted in a galvanized steel  
filter rack.  
Nineteen-inch deep bag filters  
are U.L. Class 2 and have  
synthetic media mounted to a  
7/8” nominal thickness header  
frame. These bag filters have an  
efficiency rating of MERV 15 per  
ASHRAE 52.2. To ensure  
maximum bag final filter life,  
two-inch prefilters are included  
with the bag filters. Filters are  
mounted in a galvanized steel  
filter frame bank.  
100 Percent Modulating Return  
Fan with Statitrac Control and  
Variable Frequency Drive and  
Bypass—Provided with all the  
necessary controls to control/  
maintain building space pressure  
through a VAV air handler. The  
Variable Frequency Drive (VFD)  
modulates the speed of the  
return fan motor in response to  
return plenum pressure. A  
differential pressure control  
system, Statitrac, uses a  
differential pressure transducer  
to compare indoor building  
pressure to atmospheric  
pressure. The Statitrac control  
system modulates the relief  
dampers to control the building  
pressure to within the  
MERV 15, 90-95 percent bag filter  
option—Nineteen-inch deep bag  
filters are U.L. Class 2 and have  
synthetic media mounted to a  
7/8” nominal thickness header  
frame. These bag filters have an  
efficiency rating of MERV 15 per  
ASHRAE 52.2. To ensure  
maximum bag filter life, two-inch  
prefilters are included with the  
bag filters. Filters are mounted in  
a galvanized steel filter rack.  
MERV 14, 90-95 percent low  
pressure drop, totally  
incinerable, standard  
temperature rated, cartridge,  
final filter option—Available on  
cooling only units with four or  
eight-foot blank section, as well  
as steam and hot water units  
with eight-foot blank section,  
unit casing only.  
MERV 14, 90-95 percent cartridge  
filter option—Twelve-inch deep  
cartridge filters are U.L. Class 1  
and are mounted a 7/8” nominal  
thickness header frame. These  
cartridge filters have an  
efficiency rating of MERV 14 per  
ASHRAE 52.2. To ensure  
maximum cartridge filter life,  
two-inch (or four-inch, depending  
on the application) prefilters are  
included with the cartridge  
adjustable, specified deadband  
that is set at the Human Interface  
Panel.  
Twelve-inch deep cartridge filters  
are U.L. Class 2 and are mounted  
with a rigid 7/8” nominal  
thickness header frame. These  
cartridge filters have an  
efficiency raing of MERV 14 per  
ASHRAE 52.2. To ensure  
maximum cartridge final filter  
life, four-inch prefilters are  
included with the low pressure  
drop cartridge filters. Filters shall  
be mounted in a galvanized steel  
filter frame bank.  
100 Percent Modulating Return  
Fan with Statitrac Control and  
Variable Frequency drive and  
Bypass—Bypass control  
provides full nominal airflow in  
the event of drive failure.  
filters. Filters are mounted in a  
galvanized steel filter rack.  
MERV 14, 90-95 percent, low  
pressure drop, totally  
incinerable, cartridge filter  
option—Twelve-inch deep  
cartridge filters are U.L. Class 2  
and mounted with a rigid 7/8”  
nominal thickness header frame.  
These low pressure drop  
cartridge filters have an  
efficiency rating of MERV 14 per  
ASHRAE 52.2. To ensure  
maximum cartridge filter life,  
two-inch or four-inch prefilters  
(depending on airflow) are  
included with the high-flow,  
cartridge filters. Filters are  
mounted in a galvanized steel  
filter rack.  
Filters  
No filters (two-inch nominal  
thickness throwaway filter rack  
only) option—Includes a  
galvanized steel filter rack (less  
filter media) with filter channels  
to handle a complete set of two-  
inch nominal thickness  
MERV 14, 90-95 percent,  
standard temperature rated,  
cartridge, final filter option—  
Available on cooling only units  
with four or eight-foot blank  
section, as well as steam and hot  
water units with eight-foot blank  
section, unit casing only.  
throwaway filters to  
accommodate applications  
which require field supplied  
filters.  
No filters (bag/cartridge filter  
rack with throwaway prefilter  
rack only) option—Includes a  
galvanized steel filter rack (less  
filter media) to handle a  
complete set of two-inch or four-  
inch (depending on airflow)  
nominal thickness throwaway  
prefilters and 7/8” nominal  
header thickness bag or cartridge  
filters to accommodate  
Twelve-inch deep cartridge filters  
are U.L. Class 1 and are mounted  
with a 7/8” nominal thickness  
header frame. These cartridge  
filters have an efficiency rating of  
MERV 14 per ASHRAE 52.2. To  
ensure maximum cartridge filter  
life, two-inch prefilters are  
included with the cartridge  
filters. Filters are mounted in a  
galvanized steel filter frame  
bank.  
Final filter section filter options  
mount integral within the  
optional blank section of the unit  
and are accessible by hinged  
access doors.  
MERV 15, 90-95 percent,  
standard temperature rated, bag,  
final filter option—Available on  
cooling only units with four or  
applications which require field  
supplied filters.  
RT-PRC031-EN  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
Fresh Air  
MERV 14, 90-95 percent, high  
temperature rated, cartridge,  
final filter option—Available on  
gas and electric heat units with  
eight foot blank section unit  
casing option only.  
airflow can be controlled  
dynamically and documented to  
verify compliance with ASHRAE  
Standard 62.1.  
0 to 25 percent Motorized  
Outside Air Damper—includes  
only an outside air opening with  
moisture eliminator and  
Demand Control Ventilation—  
When equipped with a CO  
2
motorized position damper for  
drawing up to 25 percent outside  
air. The damper position can be  
set at the unit mounted Human  
Interface panel.  
sensor and the (VCM) module,  
the IntelliPak II controller  
Twelve-inch deep cartridge filters  
are U.L. Class 1 and are mounted  
in a galvanized steel casing with  
a 7/8” nominal thickness header  
frame. These cartridge filters  
have an efficiency rating of  
MERV 14 per ASHRAE 52.2. To  
ensure maximum cartridge final  
filter life, high temperature rated  
two-inch prefilters are included  
with the cartridge filters. Filters  
are mounted in a galvanized  
steel filter frame bank.  
modulates the fresh air damper  
position in order to minimize the  
unit energy consumption yet  
simultaneously meet the  
ventilation requirements of  
ASHRAE Std 62.1. The Traq  
airflow monitoring solution  
augments the system, allowing  
for measurement and control of  
fresh air airflow.  
Economizer—Includes the  
primary temperature controls  
necessary to automatically use  
outdoor air for free cooling.  
Option includes modulating  
return and outside air dampers,  
high ambient temperature  
lockout, minimum position  
control and spring return motor.  
System Control  
MERV 17, 99.97 percent, standard  
temperature rated, HEPA, final  
filter option—Available on  
cooling only units with four or  
eight-foot blank section, as well  
as steam and hot water units  
with eight-foot blank section,  
unit casing only.  
Standard outside air dampers  
are provided with a leakage rate  
of 20 cfm/ft^2 at 1.0 in w.g.  
pressure difference. Optional  
Low leakage dampers are  
available with a leakage rate of  
10 cfm/ft^2 (AMCA Class 2) at 1.0  
inch w.g. pressure difference, as  
well as Ultra Low leakage  
dampers with a leakage rate of 4  
cfm/ft^2 (AMCA Class 1) at 1.0  
inch w.g. pressure difference.  
Constant Volume (CV)—Provided  
with all the necessary controls to  
operate the air handler from a  
zone sensor, including CV  
microprocessor unit control  
module and a unit mounted  
Human Interface Panel.  
Variable Air Volume (VAV)  
Twelve-inch deep HEPA filters  
are U.L. Class 1 and are mounted  
in a galvanized steel casing.  
These filters have an efficiency  
rating of MERV 17 per ASHRAE  
52.2 and an efficiency of 99.97%  
on a 0.3 micron DOP particle size.  
To ensure maximum HEPA final  
filter life, two-inch prefilters are  
included with the HEPA final  
filters. Filters are mounted in a  
galvanized steel filter frame  
bank.  
Supply Air Temperature control  
without inlet guide vanes—  
Provided with all the necessary  
controls to operate a VAV air  
handler from the discharge air  
temperature, including discharge  
air microprocessor controller  
and discharge air sensor. The  
microprocessor controller  
The 0 to 100% fresh air  
economizer has three optional  
economizer controls available:  
comparative enthalpy, reference  
enthalpy, or dry bulb control.  
coordinates the economizer  
control and the stages of cooling  
with zone or outdoor air reset  
capabilities and an adjustable  
control band to fine-tune the  
control to specific applications.  
Fresh Air Measurement—The  
Trane Traq™ airflow-monitoring  
solution allows direct  
measurement and control of  
fresh air. The Traq damper  
assembly consists of butterfly-  
type dampers. The bellmouth  
inlet of each damper guides air  
uniformly through a flow-  
MERV 17, 99.97 percent, high  
temperature rated, HEPA, final  
filter option—Available on gas  
and electric heat units with eight  
foot blank section unit casing  
option only.  
VAV Supply Air Temperature  
control with inlet guide vanes—  
Provided with all the necessary  
controls to control/operate a VAV  
air handler from the discharge air  
temperature, including a  
discharge air microprocessor  
controller, a discharge air sensor,  
pressure sensor and inlet guide  
vanes on the supply fan. The  
microprocessor controller  
coordinates the economizer  
control and the stages of cooling  
with zone or outdoor air reset  
capabilities and an adjustable  
control band to fine-tune the  
control to specific applications.  
The inlet guide vanes are used  
sensing ring that accurately  
measures total and static  
Twelve-inch deep HEPA filters  
are U.L. Class 1 and are mounted  
in a galvanized steel casing.  
These filters have an efficiency  
rating of MERV 17 per ASHRAE  
52.2 and an efficiency of 99.97%  
on a 0.3 micron DOP particle size.  
To ensure maximum HEPA final  
filter life, high temperature rated  
two-inch prefilters are included  
with the HEPA final filters. Filters  
are mounted in a galvanized  
steel filter frame bank.  
pressure from 15 to 100 percent  
of nominal airflow. The damper  
assembly ventilation control  
module (VCM) produces a vdc  
signal that is proportional to  
airflow, re-calibrates itself once  
every 60 seconds, and  
automatically adjusts for  
temperature variations. When  
applied as part of an Integrated  
Comfort™ system (ICS) with the  
Tracer Summit™ building  
automation system, ventilation  
96  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
with VAV air handlers to control  
duct static pressure. Option  
includes vanes and static  
pressure controls. Airfoil supply  
fans with inlet vanes are an  
efficient way to mechanically  
modulate airflow.  
handle enables the operator to  
Low Leak Dampers—Return air,  
fresh air and relief air dampers  
have chlorinated polyvinyl  
chloride gasketing to seal to a  
leakage rate of 10 cfm/ft^2  
(AMCA Class 2) at 1.0 in w.g.  
pressure difference.  
disconnect unit power with the  
control box door closed for  
safety.  
Unit Interrupt Rating—Using a  
non-fused circuit breaker for  
disconnect switch purposes a  
65000 Amp rating is optionally  
available on 460/3/60 powered  
units and a 25000 Amp rating is  
available on 575/3/60 units. Fan  
motors and electric heat (if  
applicable) circuits are also  
equipped with series rated circuit  
breakers.  
VAV Supply Air Temperature  
Control with Variable Frequency  
Drives w/o Bypass—Provided  
with all necessary controls to  
operate a VAV air handler from  
the discharge air temperature,  
including discharge air  
Ultra Low Leak Fresh Air  
Dampers—Dampers have  
chlorinated polyvinyl chloride  
gasketing to seal to a leakage  
rate of 4 cfm/ft^2 (AMCA Class 1)  
at 1.0 in w.g. pressure difference.  
High Duct Temperature  
microprocessor controller and  
discharge air sensor. The  
Thermostats—Two manual reset  
thermostats are provided with  
one located in the discharge  
section of the unit set at 240°F  
and the other in the return  
section set at 135°F. The air  
handler will shut down if the  
thermostats are tripped.  
GFI Convenience Outlet (Factory  
Powered)—A 15A, 115V Ground  
Fault Interrupter convenience  
outlet is factory installed. It is  
wired and powered from a  
factory mounted transformer.  
Unit mounted non-fused  
disconnect with external handle  
is furnished with factory  
powered outlet.  
microprocessor controller  
coordinates the economizer  
control and the stages of cooling  
with discharge air temperature  
reset capabilities. Includes  
factory installed and tested  
variable frequency drives (VFD)  
to provide supply fan motor  
speed modulation. VFD receives  
0-10 vdc from the unit  
microprocessor based upon  
supply static pressure and  
causes the drive to accelerate or  
decelerate as required to  
High Efficiency Motors—Supply  
and exhaust/return fans are  
provided with high efficiency  
motors.  
Economizer Control with  
Comparative Enthalpy—used  
with the fresh air economizer,  
two enthalpy sensors are  
provided to compare total heat  
content of the indoor air and  
outdoor air to determine the  
most efficient air source when  
economizing.  
High Efficiency TEFC Motors—  
Supply and exhaust/return fans  
are provided with high efficiency  
Totally Enclosed Fan Cooled  
motors.  
maintain the supply static  
pressure setpoint.  
VAV Supply Air Temperature  
Control with Variable Frequency  
Drives and Bypass—Bypass  
control provides full nominal  
airflow in the event of drive  
failure.  
Belt Guards—Supply and  
exhaust fans can be optionally  
equipped with a universal size  
belt guard to accommodate any  
applicable drive configuration.  
The guard totally encloses the  
drive system and is provided  
with a two-piece removable front  
panel for servicing. Return fan  
guards are also available with  
individually sized belt guard with  
a single-piece removable panel  
for servicing.  
Economizer Control with  
Reference Enthalpy—used with  
the fresh air economizer, an  
outdoor enthalpy sensor is  
provided to compare the total  
heat content of outdoor air to a  
locally adjustable setpoint. The  
setpoint is programmed at the  
human interface, or remote  
human interface, to determine if  
the outdoor enthalpy condition is  
suitable for economizer  
Agency Approval  
Air Handlers can be provided with  
UL/CSA approval.  
Miscellaneous Options  
Marine Lights (Customer  
Airflow Paths—In addition to the  
traditional downflow supply and  
upflow return, horizontal supply  
and return is available. End  
return is also available on select  
units. For additional details on  
airflow configuration, see  
Powered)—A 120V master light  
switch is factory installed in the  
main unit control box for lighting  
control. The master switch is  
wired into an isolated terminal  
block with access for customer  
provided service. Marine light  
fixtures are supplied with 150W  
incandescent bulbs. Marine light  
fixtures are placed in the Supply  
Section (2), Fresh Air Section (1),  
Return Section (1), and Extended  
Casing Section (1) for units  
without Heat.  
operation.  
Economizer Control with Dry  
Bulb—used with the fresh air  
economizer, an outdoor  
temperature sensor is included  
for comparing the outdoor dry  
bulb temperature to a locally  
adjustable temperature setpoint.  
The setpoint is programmed  
either at the human interface, or  
remote human interface, to  
determine if outdoor air  
Burglar Bars—A grate system is  
available for the supply and  
return air duct connection areas  
on non-horizontal airflow path  
units to minimize unwanted  
intrusion into duct systems.  
temperature is suitable for  
economizer operation.  
Generic Building Automation  
System (GBAS 0-5vdc) Module—  
Non-Fused Disconnect Switch  
with External Handle—External  
RT-PRC031-EN  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
Provided for those cases where  
non-Tracer building  
management system is used.  
The GBAS module provides a  
binary input for Demand  
Limiting, four (4) analog inputs  
for setpoint adjustment and five  
(5) relay outputs for diagnostic  
reporting. Inputs can use a  
potentiometer or 0-5 vdc signal.  
Override Module installed, the  
setpoint and AUTO/OFF system  
switch. Status indication LED  
lights; System On, Heat, Cool,  
and Service are provided.  
Sensors are available to be used  
with VAV units.  
unit can be programmed to  
transition to up to 5 different  
programmed sequences for  
Smoke Purge, Evacuation,  
Pressurization, Purge, Purge with  
duct control sequence and Unit  
off. The transition occurs when a  
binary input on the VOM is  
closed (shorted); this would  
typically be a hard wired relay  
output from a smoke detector or  
fire control panel.  
Remote Sensor—Can be used for  
remote zone temperature  
sensing capabilities when zone  
sensors are used as remote  
panels.  
Generic Building Automation  
System Module  
(GBAS 0-10 vdc)—Used to  
provide broad control  
capabilities for building  
automation systems other than  
Trane's Tracer™ system.  
Full Warm-Up Sensor—Morning  
warm-up sensor for use with  
VAV units.  
Inter-Processor Communication  
Bridge (IPCB)—This module  
provides an amplified and  
filtered version of the IPC link for  
connection to a Remote Human  
Interface Panel. Each air handler  
that is tied into a Remote Human  
Interface Panel must have a IPCB  
installed into it.  
Integrated Comfort™ System  
sensors—Used for zone  
temperature sensing when  
Tracer™ is communicating with  
the air handler. The sensors are  
available with options such as  
sensor only, sensor with timed  
override button, and a sensor  
with local temperature  
The GBAS module provides a  
binary input for Demand  
Limiting, four (4) analog inputs  
for setpoint adjustment and four  
(4) analog outputs as well as one  
(1) relay output for diagnostic  
reporting. Inputs can use a  
Trane LonTalk® Communication  
Interface Module—Provides an  
interface to the Trane Integrated  
Comfort System (ICS), which  
allows control and monitoring of  
the air handler by a Tracer or 3rd  
party building management  
system utilizing LonTalk  
adjustment control, with timed  
override button.  
potentiometer or 0-10 vdc signal.  
Remote Human Interface Panel  
(RHI)—Remote Human Interface  
Panel can perform all the same  
functions as unit mounted  
Human Interface Panel, except  
for the Service Mode. Up to 4 air  
handler units can be monitored  
and controlled with a single  
Remote Human Interface Panel.  
Remote Minimum Position  
Potentiometer—Minimum  
position setting of economizer  
can be remotely adjusted with  
this accessory.  
protocol.  
Temperature Sensor—Bullet or  
pencil type sensor that could be  
used for temperature input such  
as return air duct temperature.  
Field Installed Accessories  
Electronic Zone Sensors  
Zone Sensors—Two temperature  
setpoint levers, heat, auto, off, or  
cool system switch, fan auto or  
fan on switch. Optional status  
indication LED lights, System On,  
Heat, Cool, and Service are  
available. These sensors are  
used with CV units.  
This panel uses the same  
attractive enclosure as the  
Tracker™ building control panel.  
With features such as a  
2 line X 40 character clear  
English display, a red LED light  
to indicate an alarm condition  
(alarm also shown on the two  
line display), a simple 16 key  
keypad that is used in  
conjunction with the display to  
prompt the infrequent user when  
making desired changes and an  
attractive hinged door makes the  
RHI very suitable for mounting  
on any wall.  
Wireless Zone Sensor—The  
Trane Wireless Zone has the  
advantage of easy and flexible  
installation and uses a radio that  
is specifically designed for the  
application. It includes sensor,  
receiver, wiring harness, and two  
AA lithium batteries. Standard  
functions include zone  
Programmable Night Setback  
Sensors—Electronic  
programmable sensors with  
auto or manual changeover with  
seven day programming.  
Keyboard selection of heat, cool,  
fan auto or on. All  
programmable sensors have  
System On, Heat, Cool, Service  
LED/indicators as standard.  
Night setback sensors have (1)  
Occupied, (1) Unoccupied and (2)  
Override programs per day.  
Models are available for CV zone  
temperature control and VAV  
supply air temperature control.  
temperature, temperature  
setpoint (in Fahrenheit or  
Celsius), and occupied/  
unoccupied override.  
Inter-Processor Communication  
Bridge kit—Included in this kit is  
an Inter-Processor  
Communicating Bridge (IPCB)  
module which is required for  
communication with a Remote  
Human Interface Panel.  
The RHI can be mounted inside a  
building, up to 5000 feet from  
the unit. The RHI is wired to the  
IPCB mounted in the air handler  
with twisted wire pair  
communication wiring and 24V  
control wiring.  
Remote Human Interface Panel  
kit—Can control up to four air  
handlers. The Remote Human  
Interface Panel has all the  
features of the Unit Mounted  
Human Interface Panel, except  
Ventilation Override Module  
(VOM)—With the Ventilation  
Zone Sensor—Sensor with  
supply air single temperatures  
98  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
no service mode interface is  
allowed remotely for safety  
reasons.  
Trane LonTalk® Communication  
Interface kit—For future  
opportunities and upgrade  
flexibility, this kit contains a  
LonTalk Communication  
Interface (LCI-I) module, which is  
required for communication with  
Tracer Summit or a 3rd party  
building automation system.  
The CO sensor has the ability to  
2
monitor space occupancy levels  
within the building by measuring  
the parts per million of CO  
2
(Carbon Dioxide) in the air. As  
the CO levels increase, the  
2
outside air damper modulates to  
meet the CO space ventilation  
2
requirements.  
Roof Curb  
Roof Curb—Curb supports the air  
handler and allows for smooth  
transition of airflow from the air  
handler to the ductwork. Curb  
ships from stock and ductwork  
can be attached directly. Two-  
inch by four-inch nailer strip is  
also provided, as well as  
gasketing to seal supply and  
return openings. Curb is 14  
inches high and is manufactured  
to the guidelines of the National  
Roofing Contractors Association.  
RT-PRC031-EN  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
positive latching at three points.  
General  
Electrical System  
Access doors shall provide a door  
stop mechanism to latch the door in  
the open position to prevent unsafe  
door closure by wind.  
Units shall be specifically designed  
for outdoor air handler installation  
on a roof curb and be completely  
factory assembled and tested, piped,  
internally wired and shipped in one  
piece.  
Convenience Outlet  
A 15A, 115V Ground Fault Interrupter  
convenience outlet shall be wired  
and powered from a factory  
mounted transformer. A unit  
mounted, non-fused disconnect with  
external handle is furnished with the  
convenience outlet.  
Doors of laminated double wall  
construction with a polyurethane  
foam core between the exterior  
sheet metal pane and the interior  
liner, with an insulating value of R8  
shall be provided on the air handler's  
serviceable compartments such as  
return/exhaust fan, filters, coil and  
blank sections. Two single wall doors  
shall be provided for access to the  
control panel.  
Air handlers shall be available as  
either no cooling or chilled water  
cooling units. Heat options include  
natural gas, electric, hot water,  
steam or no heat. Filters, outside air  
system, exhaust air system, optional  
non-fused disconnect switches and  
all operating and safety controls  
shall be furnished factory installed.  
Non-Fused Disconnect Switch  
An external handle mounted on the  
control box door shall be provided to  
disconnect unit power.  
Blank Sections  
Unit Interrupt Rating  
All units shall be UL/CSA approved  
and factory run tested. All units shall  
also be compliant with IBC Seismic  
requirements. All units shall have  
decals and tags to aid in service and  
indicate caution areas. Electrical  
diagrams shall be printed on long  
life water resistant material and shall  
ship attached to control panel doors.  
A four or eight foot blank section of  
laminated double wall construction  
with a polyurethane foam core  
between the exterior sheet metal  
panel and the interior liner, with an  
insulating value of R8 shall be  
provided with similarly built, hinged,  
access doors on either side  
A 65000 Amp rating (480V) and  
25000 Amp rating (600V) shall be  
applied to the unit enclosure using a  
non-fused circuit breaker for  
disconnect switch purposes. Fan  
motors and electric heat circuits  
shall be provided with series rated  
circuit breakers that will provide the  
unit rated level of protection. The  
unit shall be marked with approved  
UL markings and will adhere to UL  
508A regulations.  
Casing  
Airflow Path  
Exterior panels shall be zinc coated  
galvanized steel, phosphatized and  
painted with a slate grey air-dry  
finish durable enough to withstand a  
minimum of 500 hours consecutive  
salt spray application in accordance  
with standard ASTM B117. Screws  
shall be coated with zinc-plus-zinc  
chromate.  
Unit shall have downflow discharge  
conditioned air path or horizontal  
discharge. Return airflow path shall  
be either upflow or horizontal.  
Marine Lights (Customer  
Powered)  
Burglar Bar  
A 120V master light switch shall be  
factory installed in the main unit  
control box for lighting control. The  
master switch shall be wired into an  
isolated terminal block with access  
for customer provided service.  
Marine light fixtures shall be  
supplied with 150W incandescent  
bulbs. Marine light fixtures shall be  
placed in the Supply Section (2),  
Fresh Air Section (1), Return Section  
(1), and Extended Casing Section (1)  
for units without Heat.  
A grate system shall be installed in  
supply and return air duct  
connection areas on non-horizontal  
airflow path units to minimize  
unwanted intrusion into duct  
systems.  
The Air Handler shall be laminated  
double-wall construction with  
polyurethane foam core between  
sheet metal panels and liners.  
Insulation value shall be R8. All  
interior surfaces shall be suitable for  
cleaning per ASHRAE 62. All access  
doors and panels shall have  
neoprene gaskets. Unit base shall be  
watertight with heavy gauge formed  
load bearing members and curb  
overhang. Unit lifting lugs shall  
accept chains or cables for rigging.  
Lifting lugs shall also serve as unit  
tie down points.  
Belt Guard  
Supply and exhaust fans shall have a  
universal size belt guard to  
accommodate any applicable drive  
configuration. The guard totally  
encloses the drive system and is  
provided with a two-piece  
removable front panel for servicing.  
Return fan guards shall be  
individually sized with a single piece  
removable panel for servicing.  
Supply/Exhaust/Return Motors  
Supply, exhaust/return motors are  
either standard efficiency open drip-  
proof, high efficiency open drip-  
proof, or high efficiency totally  
enclosed fan cooled. All supply,  
exhaust/return motors meet the U.S.  
Energy Policy Act of 1992 (EPACT).  
Access Doors  
Access doors shall be hinged with a  
single, exterior mounted, height and  
tension adjustable, handle to provide  
100  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Mechanical Specifications  
below first critical speed. Fan shafts  
shall be mounted on two grease  
lubricated ball bearings designed for  
200,000 hours average life. Extended  
grease lines shall allow greasing of  
bearings from section base rail. Fan  
motor and fan assembly shall be  
mounted on common base to allow  
consistent belt tension with no  
relative motion between fan and  
motor shafts. Entire assemblies shall  
be completely isolated from unit by  
two-inch deflection spring isolators.  
Management Network. The  
Cooling System  
microprocessors shall be equipped  
with onboard diagnostics, indicating  
that all hardware, software and  
interconnected wiring are in proper  
operating condition.  
Chilled Water Coil  
Coils shall be of type 5W, W, or WD  
and have a tube in sheet design with  
5/8” OD, 0.020” copper tubing  
mechanically bonded to aluminum  
fins. Headers shall be constructed of  
copper tubing with steel pipe  
connections. Coil casing shall be a  
minimum 16-gauge G90 galvanized  
steel with formed end supports and  
top and bottom channels.  
The modules (boards) shall be  
protected to prevent RFI and voltage  
transients from affecting the board  
circuits. All field wiring shall be  
terminated at separate, clearly  
marked terminal strip. Direct field  
wiring to the I/O boards is not  
acceptable.  
Multiple row and fin series options  
shall be available including 2, 4, 6, or  
8 rows and 80, 108, 144, or 168 fins  
per foot. Optional, performance  
enhancing, turbulators shall  
available for all chilled water coils. All  
coils shall be factory burst tested at  
300 PSIG and leak tested at 200 PSIG.  
Controls  
The microprocessor's memory shall  
be non-volatile EEPROM type  
requiring no battery or capacitive  
backup, while maintaining all data.  
Unit shall be completely factory  
wired with necessary control and  
contactor pressure lugs or terminal  
block for power wiring. Units shall  
provide an internal location for a  
non-fused disconnect with external  
handle for safety.  
2
Zone sensors shall be available in  
several combinations with selectable  
features depending on sensor.  
All coils shall have drain holes.  
Water diverters and a double sloped  
galvanized drain pan shall be  
provided to direct condensate to both  
sides of the unit.  
Unit Controller  
3
DDC microprocessor controls shall  
be provided to control all unit  
The Human Interface Panel keypad  
display character format shall be 40  
characters x 2 lines. The character  
font shall be 5 x 7 dot matrix plus  
cursor. The display shall be  
Supertwist Liquid Crystal Display  
(LCD) with blue characters on a gray/  
green background which provides  
high visibility and ease of interface.  
The display format shall be in clear  
English.  
functions. The control system shall  
be suitable to control CV or VAV  
applications. The controls shall be  
factory installed and mounted in the  
main control panel. All factory  
installed controls shall be fully  
commissioned (run tested) at the  
factory. The unit shall have a Human  
Interface Panel with a 16 key keypad,  
a 2 line X 40 character clear English  
display as standard to provide the  
operator with full adjustment and  
display of control data functions. The  
unit controls shall be used as a stand-  
alone controller, or as part of a  
building management system  
Water Valve  
A 1.5, 2.0, 2.5, or 3.0” water  
modulating valve with actuator and  
linkage shall be provided by the  
manufacturer. Valve, actuator, and  
linkage shall be field installed and  
piped by the piping contractor.  
External Piping Enclosure  
A piping cabinet shall be supplied by  
the manufacturer (factory  
assembled) when the chilled water  
cooling option is selected. The  
piping cabinet shall be mounted  
external to the air handler unit and  
shipped separate to be field installed.  
The piping cabinet shall have a  
removable panel.  
4
The keypad shall be equipped with  
16 individual touch-sensitive  
membrane key switches. The  
switches shall be divided into four  
separate sections and be password  
protected from change by  
unauthorized personnel. The six  
main menus shall be STATUS,  
SETPOINTS, DIAGNOSTICS, SETUP,  
CONFIGURATION and SERVICE  
MODE.  
involving multiple units.  
1
The unit shall be equipped with a  
complete microprocessor control  
system. This system shall consist of  
temperature and pressure  
Air Handling System  
(thermistor and transducer) sensors,  
printed circuit boards (modules), and  
a unit mounted Human Interface  
Panel. Modules (boards) shall be  
individually replaceable for ease of  
service. All microprocessors, boards  
and sensors shall be factory  
Supply Fan  
Trane LonTalk® Communication  
Interface Module (LCI-I)  
Standard or low airflow supply fan  
shall have a single fan assembly with  
double width, double inlet, airfoil fan,  
motor and fixed pitch sheave drive.  
All fans shall be statically and  
The LCI-I provides an interface to a  
Tracer Summit system or other  
control system that supports LonTalk  
and shall be factory installed,  
allowing for control and monitoring  
of the unit through a RS485, two-wire  
communication link.  
mounted, wired and tested.  
dynamically balanced for the  
operating envelop. It shall be tested  
in the factory. Supply fans shall be  
test run in unit as part of the unit test.  
Fan operating envelop rpm shall be  
The microprocessor boards shall be  
standalone DDC controls not  
dependent on communications with  
an on-site PC or a Building  
RT-PRC031-EN  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
MERV 14, 90-95 Percent Cartridge  
Filters Option  
MERV 14, 90-95 Percent,  
Cartridge, Final Filter Option  
Filters  
General  
Twelve-inch deep cartridge filters  
shall be U.L. Class 1 and be mounted  
with a 7/8” nominal thickness header  
frame. These cartridge filters shall  
have an efficiency rating of MERV 14  
per ASHRAE 52.2. To ensure  
Note: Available on cooling only  
units with four or eight-foot  
blank section, as well as  
steam and hot water units  
with eight-foot blank section,  
unit casing only.  
Filter options shall mount integral  
within the unit and be accessible by a  
hinged access door with a single  
point latching device.  
maximum cartridge filter life, two-  
inch (or four-inch, depending on the  
application) prefilters shall be  
included with the cartridge filters.  
Filters shall be mounted in a  
galvanized steel filter rack.  
Cooling Coil Filter Options  
Twelve-inch deep cartridge filters  
shall be U.L. Class 1 and be mounted  
with a 7/8” nominal thickness header  
frame. These cartridge filters shall  
have an efficiency rating of MERV 14  
per ASHRAE 52.2. To ensure  
maximum cartridge filter life, two-  
inch prefilters shall be included with  
the cartridge filters. Filters shall be  
mounted in a galvanized steel filter  
frame bank.  
No Filters (Two-inch Nominal  
Thickness Throwaway Filter Rack  
Only)  
Shall provide a galvanized steel filter  
rack (less filter media) with filter  
channels to handle a complete set of  
two-inch nominal thickness  
throwaway filters to accommodate  
applications which require field  
supplied filters.  
MERV 14, 90-95 Percent, Low  
Pressure Drop, Totally  
Incinerable, Cartridge Filters  
Option  
Twelve-inch deep cartridge filter shall  
be U.L. Class 2 and mounted with a  
rigid 7/8” nominal thickness header  
frame. These low pressure drop  
cartridge filters shall have an  
efficiency rating of MERV 14 per  
ASHRAE 52.2. To ensure maximum  
cartridge filter life two-inch or four-  
inch prefilters (depending on airflow)  
shall be included with the high-flow,  
cartridge filters. Filters shall be  
mounted in a galvanized steel filter  
rack.  
No Filters (Bag or Cartridge Filter  
Rack with Throwaway Prefilter  
Rack Only)  
Shall provide a galvanized steel filter  
rack (less filter media) to handle a  
complete set of two-inch or four-inch  
(depending on airflow) nominal  
thickness throwaway prefilters and  
7/8” actual header thickness bag or  
cartridge filters to accommodate  
applications which require field  
supplied filters.  
Final Filters Options (Available  
Only on Units with Blank  
Section)  
Merv 7 Throwaway Filters  
(Standard)  
Final filter section filter options shall  
mount integral within the blank  
section unit casing and be accessible  
by hinged access doors.  
Shall be provided as standard—U.L.  
Class 2, two-inch nominal thickness,  
high efficiency pleated media filters  
rated MERV 7 per ASHRAE 52.2.  
Filters shall be provided mounted in  
a galvanized steel filter rack.  
MERV 15, 90-95 Percent, Bag,  
Final Filter Option  
Note: Available on cooling only  
units with four or eight-foot  
blank section, as well as  
steam and hot water units  
with eight-foot blank section,  
unit casing only.  
MERV 15, 90-95 Percent Bag  
Filters Option  
Nineteen-inch deep bag filters shall  
be U.L. Class 2 and have synthetic  
media mounted to a 7/8” nominal  
thickness header frame. These bag  
filters shall have an efficiency rating  
of MERV 15 per ASHRAE 52.2. To  
ensure maximum bag filter life two-  
inch prefilters shall be included with  
the bag filters. Filters shall be  
mounted in a galvanized steel filter  
rack.  
Nineteen-inch deep bag filters shall  
be U.L. Class 2 and have synthetic  
media mounted to a 7/8” nominal  
thickness header frame. These bag  
filters shall have an efficiency rating  
of MERV 15 per ASHRAE 52.2. To  
ensure maximum bag final filter life  
two-inch prefilters shall be included  
with the bag filters. Filters shall be  
mounted in a galvanized steel filter  
frame bank.  
102  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
Filters shall be mounted in a  
shall be completely isolated from  
unit with 2-inch spring isolation.  
Discharge dampers at unit outlet  
shall modulate exhaust airflow in  
response to OA damper position.  
MERV 14, 90-95 Percent, Low  
Pressure Drop, Totally  
Incinerable, Cartridge, Final Filter  
Option  
galvanized steel filter frame bank.  
MERV 17, 99.97 Percent, High  
Temperature Rated, HEPA, Final  
Filter Option  
Note: Available on cooling only  
units with four or eight-foot  
blank section, as well as  
steam and hot water units  
with eight-foot blank section,  
unit casing only.  
100 Percent Modulating Exhaust  
Fan with Statitrac™ Control  
Option  
Note: Available on gas and electric  
heat units with eight-foot  
blank section casing only.  
Fan design shall be double width,  
double inlet forward-curved type. Fan  
shall be mounted on a shaft with  
fixed sheave drive. All fans shall be  
dynamically balanced and tested in  
factory before being installed in unit.  
Exhaust fan shall be test run as part  
of unit final run test. Fan operating  
envelop rpm shall be below first  
critical speed. Fan shaft shall be  
mounted on two grease lubricated  
ball or roller bearings designed for  
200000-hour average life. Extended  
grease lines shall be provided to  
allow greasing of bearings from  
section base rail.  
Twelve-inch deep HEPA filters shall  
be U.L. Class 1 and be mounted in a  
galvanized steel casing. These filters  
have an efficiency rating of MERV 17  
per ASHRAE 52.2 and an efficiency of  
99.97% on a 0.3 micron DOP particle  
size. To ensure maximum HEPA final  
filter life high temperature rated two-  
inch prefilters shall be included with  
the HEPA final filters. Filters shall be  
mounted in a galvanized steel filter  
frame bank.  
Twelve-inch deep cartridge filter shall  
be U.L. Class 2 and mounted with a  
rigid 7/8” nominal thickness header  
frame. These cartridge filters shall  
have an efficiency rating of MERV 14  
per ASHRAE 52.2. To ensure  
maximum cartridge final filter life  
four-inch prefilters shall be included  
with these cartridge filters. Filters  
shall be mounted in a galvanized  
steel filter frame bank.  
MERV 14, 90-95 Percent, High  
Temperature Rated, Cartridge,  
Final Filter Option  
Exhaust Air  
General  
Fan motor and assembly shall be  
mounted on common base to allow  
consistent belt tension with no  
relative motion between fan and  
motor shafts. The entire assembly  
shall be completely isolated from  
unit with 2-inch spring isolators. For  
both CV and VAV air handlers, the  
100 percent modulating exhaust  
discharge damper (or VFD) shall be  
modulated in response to building  
pressure.  
Note: Available on gas and electric  
heat units with eight-foot  
Exhaust air options shall include no  
relief, 100 percent modulating  
exhaust fan and 100 percent  
modulating exhaust fan with direct  
space building pressurization control.  
blank section casing only.  
Twelve-inch deep cartridge filters  
shall be U.L. Class 1 and be mounted  
in a galvanized steel casing with a  
7/8” nominal thickness header frame.  
These cartridge filters shall have an  
efficiency rating of MERV 14 per  
ASHRAE 52.2. To ensure maximum  
cartridge final filter life high  
temperature rated two-inch prefilters  
shall be included with the cartridge  
filters. Filters shall be mounted in a  
galvanized steel filter frame bank.  
Exhaust fans shall be either standard  
or low airflow  
No Relief (Standard)  
Relief air opening shall be sealed  
with panel and made watertight.  
A differential pressure control  
system, (Statitrac), shall use a  
differential pressure transducer to  
compare indoor building pressure to  
outdoor ambient atmospheric  
100 Percent Modulating Exhaust  
Fan Option  
Fan design shall be double width,  
double inlet forward-curved type. Fan  
shall be mounted on a shaft with  
fixed sheave drive. All fans shall be  
dynamically balanced and tested in  
factory before being installed in unit.  
It shall be test run in unit as part of  
unit test. Fan operating envelop rpm  
shall be below first critical speed. Fan  
shaft shall be mounted on two grease  
lubricated ball or roller bearings as  
applicable designed for 200000-hour  
average life. Extended grease lines  
shall be provided to allow greasing of  
bearings from section base rail.  
MERV 17, 99.97 Percent, Standard  
Temperature Rated, HEPA, Final  
Filter Option  
pressure. The FC exhaust fan shall be  
turned on when required to lower  
building static pressure setpoint. The  
(Statitrac) control system shall then  
modulate the discharge dampers (or  
VFD) to control the building pressure  
to within the adjustable, specified  
deadband that shall be adjustable at  
the Human Interface Panel.  
Note: Available on cooling only  
units with four or eight-foot  
blank section, as well as  
steam and hot water units  
with eight-foot blank section,  
unit casing only.  
Twelve-inch deep HEPA filters shall  
be U.L. Class 1 and be mounted in a  
galvanized steel casing. These filters  
have an efficiency rating of MERV 17  
per ASHRAE 52.2 and an efficiency of  
99.97% on a 0.3 micron DOP particle  
size. To ensure maximum HEPA final  
filter life two-inch prefilters shall be  
included with the HEPA final filters.  
Fan motor and assembly shall be  
mounted on common base to allow  
consistent belt tension with no  
relative motion between fan and  
motor shafts. The entire assembly  
RT-PRC031-EN  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
mounted on common base to allow  
consistent belt tension with no  
relative motion between fan and  
motor shafts. The entire assembly  
shall be completely isolated from  
unit with 2-inch spring isolators. The  
100 percent modulating relief  
damper shall be modulated in  
response to building pressure. A  
differential pressure control system,  
(Statitrac), shall use a differential  
pressure transducer to compare  
indoor building pressure to outdoor  
ambient atmospheric pressure. The  
(Statitrac) control system shall  
modulate the discharge dampers to  
control the building pressure to  
within the adjustable, specified  
deadband that shall be adjustable at  
the Human Interface Panel. The  
return fan VFD shall modulate in  
response to return duct static  
pressure.  
0-100 Percent Modulating  
Economizer Option  
Return Air  
General  
Operated through the primary  
temperature controls to  
automatically utilize OA for “free”  
cooling. Automatically modulated  
return and OA dampers shall  
Return air options shall include 100  
percent modulating return fan and  
100 percent modulating return with  
direct space building pressurization  
control. Return fans shall be either  
standard or low airflow.  
maintain proper temperature in the  
conditioned space. Economizer shall  
be equipped with an automatic  
lockout when the outdoor high  
ambient temperature is too high for  
proper cooling. Minimum position  
control shall be standard and  
adjustable at the Human Interface  
Panel or with a remote potentiometer  
or through the building management  
system. A spring return motor shall  
ensure closure of OA dampers during  
unit shutdown or power interruption.  
Mechanical cooling shall be available  
to aid the economizer mode at any  
ambient. Standard economizer  
dampers shall have a leakage rate of  
20 cfm/ft^2 at 1.0 in W.C. pressure  
difference.  
100 Percent Modulating Return  
Fan  
A single width plenum fan with airfoil  
blade shall be mounted on a shaft  
with fixed sheave drive. The fan shall  
be dynamically balanced for the  
operating envelop and tested in  
factory before being installed in unit.  
The plenum fan shall be test run in  
unit as part of unit test. Fan operating  
envelop rpm shall be below first  
critical speed. Fan shaft shall be  
mounted on two grease lubricated  
ball or roller bearings designed for  
200,000-hour average life. Extended  
grease lines shall be provided to  
allow greasing of bearings from  
section base rail. Fan motor and  
assembly shall be mounted on  
common base to allow consistent  
belt tension with no relative motion  
between fan and motor shafts. The  
entire assembly shall be completely  
isolated from unit with 2-inch spring  
isolators. Discharge dampers at unit  
outlet shall modulate relief airflow in  
response to OA / return air damper  
position. The return fan VFD shall  
operate in conjunction with the  
supply fan.  
Fresh Air  
General  
Low Leak and Ultra Low Leak  
Economizer Dampers Option  
Three outside air options: 0 to 25  
percent motorized controlled outside  
air, 0-100 percent fully modulating  
economizer, and 0-100 percent fully  
modulating economizer with fresh air  
measurement.  
Low leak dampers shall be provided  
with chlorinated polyvinyl chloride  
gasketing added to the damper  
blades and rolled stainless steel jamb  
seals to the sides of the damper  
assembly. The low leak dampers  
shall have a leakage rate of 10 cfm/  
ft^2 (AMCA Class 2) at 1.0 in W.C.  
pressure difference.  
Demand Control Ventilation  
The fresh air damper position shall  
modulate in response to a CO  
2
sensor in the conditioned space, in  
order to minimize the unit energy  
consumption, yet simultaneously  
meet the ventilation requirements of  
ASHRAE Std 62.1.  
Ultra low leak damper will have  
added sealing under the jam seals  
and in the frame. The ultra low leak  
dampers shall have a leakage rate of  
4 cfm/ft^2 (AMCA Class 1) at 1.0 in  
W.C. pressure difference.  
100 Percent Modulating Return  
Fan with Statitrac™ Control  
Option  
Fresh Air Measurement  
A factory mounted airflow  
Note: Based on testing completed  
in accordance with AMCA  
Standard 500D.  
A single width plenum fan with airfoil  
blade shall be mounted on a shaft  
with fixed sheave drive. The fan shall  
be dynamically balanced for the  
operating envelop and tested in  
factory before being installed in unit.  
The plenum fan shall be test run as  
part of unit final run test. Fan  
operating envelop rpm shall be  
below first critical speed. Fan shaft  
shall be mounted on two grease  
lubricated ball or roller bearings  
designed for 200,000-hour average  
life. Extended grease lines shall be  
provided to allow greasing of  
measurement station (TRAQ) shall be  
provided in the fresh air opening to  
measure airflow. The airflow  
measurement station shall measure  
from 15 to 100 percent of unit airflow.  
The airflow measurement station  
shall adjust for temperature  
variations.  
0-25 Percent Motorized Outside  
Air Damper Option  
0-25 percent motorized outside air  
damper shall provide up to 25  
percent outside air. The damper  
position will be adjustable at the  
Human Interface Panel.  
bearings from section base rail. Fan  
motor and assembly shall be  
104  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
unit. Units shall be UL/CSA approved  
specifically for outdoor applications  
downstream from chilled water coils.  
All gas piping shall be threaded  
connection with a pipe cap provided.  
Gas supply connection shall be  
provided through the side on  
Economizer Control with  
Comparative Enthalpy  
Steam Heating Option  
Steam coils shall be Type NS with  
non-freeze steam distribution  
circuits. Distributor tubes shall be  
located concentrically within  
condensing tubes to assure even  
steam distribution. Coils shall be  
pitched to provide complete  
Used with the fresh air economizer,  
two enthalpy sensors are provided to  
compare total heat content of the  
indoor air and outdoor air to  
determine the most efficient air  
source when economizing.  
horizontal discharge units, and  
through the bottom and side for  
downflow discharge units. All units  
shall be fire tested prior to shipment.  
drainage. Steam modulating valve  
with actuator shall be provided.  
Economizer Control with  
Reference Enthalpy  
Heat Exchanger shall be tubular  
two pass design with stainless  
steel primary and secondary  
surfaces. Free floating design  
shall eliminate expansion and  
contraction stresses and noises.  
Gasketed cleanout plate shall be  
provided for cleaning of tubes/  
turbulators. Heat exchanger shall  
be factory pressure and leak  
tested.  
Hot water Heating Option  
Used with the fresh air economizer,  
an outdoor enthalpy sensor is  
provided to compare the total heat  
content of outdoor air to a locally  
adjustable setpoint. The setpoint is  
programmed at the human interface,  
or remote human interface, to  
determine if the outdoor enthalpy  
condition is suitable for economizer  
operation.  
Hot water coils shall be Type 5W and  
factory mounted in the air handling  
unit to provide complete drainage of  
coil. Hot water modulating valve with  
actuator shall be provided.  
Accessories  
Roof Mounting Curb  
Burner shall be a stainless steel  
industrial type with an air  
Roof mounting curb shall be heavy  
gauge zinc coated steel with nominal  
two-inch by four-inch nailer setup.  
Piping enclosure and supply/return  
air opening gasketing shall be  
provided. Curb shall ship knocked  
down for easy assembly. Channel  
shall be provided to allow for  
adjustment of return air opening  
location. Curb shall be manufactured  
to National Roofing Contractors  
Association guidelines.  
Economizer Control with Dry  
Bulb  
proving switch to prevent burner  
operation if the burner is open  
for maintenance or inspection.  
Ceramic cone shall be provided  
to shape the flame to prevent  
impingement on sides of heat  
exchanger drum. Burner  
Used with the fresh air economizer,  
an outdoor temperature sensor is  
included for comparing the outdoor  
dry bulb temperature to a locally  
adjustable temperature setpoint. The  
setpoint is programmed at the  
human interface, or remote human  
interface, to determine if outdoor air  
temperature is suitable for  
assembly shall house ignition  
and monitoring electrode.  
Combustion Blower shall be  
centrifugal type fan to provide air  
required for combustion. Fan  
motor shall have built-in thermal  
overload protection.  
economizer operation.  
Electronic Zone Sensors  
Heating System  
Zone Sensors shall provide two  
temperature setpoint levers,  
Heat, Auto, Off, or Cool system  
switch, Fan Auto or Fan On  
switch. Optional status indication  
LED lights, System On, Heat,  
Cool, and Service shall be  
Electric Heating Option  
Gas Safety Controls shall include  
electronic flame safety controls  
to require proving of combustion  
air prior to ignition sequence  
which shall include a 60 second  
pre-purge cycle. Pilot ignition  
shall be provided on 850, 1100  
and 1800 MBH heat exchanger  
units. Sixty second delay shall be  
provided between first and  
second stage gas valve operation  
on two-stage heaters.  
All electric heat models shall be  
completely assembled and have  
wired electric heating system integral  
within the air handler. Heavy duty  
nickel chromium elements internally  
wired with a maximum density of 40  
watts per square inch shall be  
provided.  
available. These sensors shall be  
used with CV units.  
Programmable Night Setback  
Sensors shall be electronic  
programmable sensors with  
auto or manual changeover with  
7 day programming. Keyboard  
shall provide selection of Heat,  
Cool, Fan Auto or On. All  
Heater circuits shall be 48 amps or  
less, each individually fused.  
Automatic reset high limit control  
shall operate through heater backup  
contactors. The units shall have  
optional factory mounted non-fused  
disconnect switch located in the main  
control panel to serve the entire unit.  
Continuous electronic flame  
supervision shall be provided as  
standard.  
programmable sensors shall  
have System On, Heat, Cool,  
Service LED/indicators as  
standard. Night setback sensors  
shall have (1) Occupied, (1)  
Unoccupied and (2) Override  
programs per day. Sensors shall  
be available for CV zone  
Full Modulation Gas Heaters  
shall be made from grades of  
stainless steel suitable for  
condensing conditions. The  
heater shall have a turn down  
ratio of at least 10 to 1 on the 850  
and 20 to 1 on the 1100 and 1800  
MBH  
Gas Fired Heating Option  
All gas fired units shall be completely  
assembled and have a wired gas  
fired heating system integral within  
RT-PRC031-EN  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
temperature control and VAV  
Supply Air temperature control.  
VAV zone sensor shall be  
provided with supply air single  
temperature setpoint and AUTO/  
OFF system switch. Status  
indication LED lights shall  
include: System On, Heat, Cool  
and Service. Sensor shall be  
provided for zone temperature  
control with VAV units.  
Remote Sensor shall be available  
to be used for remote zone  
temperature sensing capabilities  
when zone sensors are used as  
Remote panels.  
Fast Warm-Up Sensor shall be  
used as Morning warm-up  
sensor with VAV units.  
Integrated Comfort™ System  
sensors shall be available with  
sensor only, sensor with timed  
override, and sensor with local  
temperature setpoint adjustment  
with timed override.  
Remote Minimum Position  
Potentiometer shall be available  
to remotely adjust the minimum  
position setting of the unit  
economizer.  
Wireless Zone Sensor shall be  
available with a RF wireless zone  
temperature, setpoint and timed  
override transmitter and a RF  
receiver that connects directly to  
the IntelliPak II controller and  
uses spread spectrum  
technology. Sensor battery life  
shall provide at least 5 years life  
under normal operating  
conditions and shall provide a  
readily visual indication of  
battery condition.  
CO Sensing  
2
The CO sensor shall have the  
2
ability to monitor space  
occupancy levels within the  
building by measuring the parts  
per million of CO (Carbon  
2
Dioxide) in the air. As the CO  
2
levels increase, the outside air  
damper modulates to meet the  
CO space ventilation  
2
requirements.  
106  
RT-PRC031-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
Date  
RT-PRC031-EN  
November 2007  
New  
Supersedes  
WWW.Trane.com  
Trane has a policy of continuous product and product data improvement and reserves the right to  
change design and specifications without notice.  
For more information, contact your local Trane  
office or e-mail us at [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technicolor Thomson MP3 Player EH308 User Manual
Timex Watch Reebok User Manual
Timex Watch W 865 User Manual
Toshiba Blu ray Player BDX2200KU User Manual
Toshiba Copier E STUDIO223 User Manual
Toshiba DVD Player SD 185 User Manual
Trane Heat Pump 18 BC55D1 2 User Manual
Tricity Bendix Freezer TB 44 UF User Manual
Tripp Lite TV Cables EZA VGAX 2 User Manual
True Manufacturing Company Refrigerator T 23DT User Manual