Packaged Cooling with
Electric Heat Rooftop Units
Precedent™
TSC060-120
50 Hz
RT-PRC016-EN
November 2003
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Introduction
2
4
Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
9
10
12
13
14
33
34
35
36
44
45
Performance Data
Zone Controls
Electrical Data
Jobsite Connections
Dimensional Data
Weights
Mechanical Specifications
RT-PRC016-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Easy Access Panels
Remove two screws for access to the
standardized internal components and
wiring.
Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.
Patented Condenser Coil
Precedent boasts a patented 1+1+1
Hybrid coil, permanently gapped for
easy of cleaning.
Unit Cabinet
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed
top is not only aesthetically pleasing, it is
designed to prevent water from pooling.
Single Point Power
A single electrical connection powers the
unit.
Colored And Numbered Wiring
You save time and money tracing wires
and diagnosing the unit.
Convertible Units
• The units ship in a downflow
configuration. They can be easily
converted to horizontal by simply
moving two panels.
Sloped Drain Pans
Every Precedent unit has a non-
corrosive, removable, double-sloped
drain pan that’s easy to clean and
reversible to allow installation of drain
trap on either side of the unit.
• Units come complete with horizontal
duct flanges so the contractor doesn’t
have to field fabricate them. These
duct flanges are a time and cost saver.
Compressors
Through the Base Condensate
Every unit includes provisions for
through the base condensate drain
connections. This allows the drain to be
connected through the roof curb instead
of a roof penetration.
Precedent™ contains the best
compressor technology available to
achieve the highest possible
performance. Our compressor line
includes Trane built reciprocating and
scrolls.
Foil-Faced Insulation
Easy Access Panels
All panels in the Evaporator section of
the unit have cleanable foil-faced
insulation. All edges are either captured
or sealed to ensure no fibers get into the
airstream.
Easy access panels reduce the number of
possible water entry points.
Low Ambient Cooling
All Precedent units have cooling
capabilities down to 0°F as standard.
Unit Base
For added water integrity, Precedent has
a raised 29 mm (1 1/8") lip around the
unit’s downflow supply and return to
prevent water from blowing into the
ductwork.
RT-PRC016-EN
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Flexible Applications
Standardized Components
• Only two roof curbs for the 5-10 ton
Precedent line. . .simplifies curb
• RseelleiacTtieolnm. icroprocessor controls to
meet either the simple or the more
complex application.
• Components are placed in the same
location on all Precedent™ units.
Familiarize yourself with one Precedent
and you are familiar with every
Precedent.
• Airflow is outstanding. The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt drive — standard or oversized
supply fan motors meet a wide airflow
range.
• Precedent offers ultimate flexibility.
Options and components are not pre-
packaged at the factory. Units are built
to order in our standard “shortest in
the industry” ship cycle time.
Easy Access Low Voltage Terminal
Board
Precedent’s Low Voltage Terminal Board
is external to the electrical control
cabinet. It is extremely easy to locate and
attach the thermostat wire. This is
another cost and time saving installation
feature.
Low Voltage Connections
The wiring of the low voltage
connections to the unit and the zone
sensors is as simple as 1-1, 2-2, and 3-3.
This simplified system makes it easy for
the installer to wire
Single-Side Service
Single-side service is standard on all
Precedent units.
RT-PRC016-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
• Eliminates the need for field-installed
components with its built-in anti-
short-cycle timer, time delay relay
and minimum ‘’on’’ time controls.
These controls are factory tested to
assure proper operation.
• Requires no special tools to run the
Precedent unit through its paces
during testing. Simply place a
jumper between Test 1 and Test 2
terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps. The
unit automatically returns control to
the zone sensor after stepping
through the test mode a single time,
even if the jumper is left on the unit.
Micro Controls
Several years ago,Trane was the first to
introduce microprocessor controls into
the Light Commercial Market. That
design, along with immeasurable
experience, has provided the
technology for Trane’s second-
generation ReliaTel™ microprocessor
controls.
• As long as the unit has power and
the LED is lit, the Micro is
operational. The light indicates that
the Micro is functioning properly.
• Features expanded diagnostic
capabilities when used with Trane’s
Integrated Comfort ™ Systems.
• As an energy benefit, softens
electrical ‘’spikes’’ by staging on fans,
compressors and heaters.
ReliaTel™ Micro:
• Provides unit control for heating,
cooling, and ventilating by utilizing
input from sensors that measure
outdoor and indoor temperature.
• The Intelligent Fallback or Adaptive
Control is a benefit to the building
occupant. If a component goes
astray, the unit will continue to
operate at predetermined
• Improves quality and reliability
through the use of time-tested
microprocessor controls and logic.
temperature set points.
• Intelligent Anticipation is a standard
feature of the Micro. Functioning
constantly, the Micro and zone
• Prevents the unit from short cycling,
considerably improving compressor
life.
sensors work together in harmony,
to provide tight comfort control.
• Ensures that the compressor will run
for a specific amount of time, which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
• Reduces the number of components
required to operate the unit, thereby
reducing possibilities for component
failure.
RT-PRC016-EN
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Factory-installed Options
Hinged Access Doors
The following options round-out the
complete line of Precedent™ options:
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.
— 0 - 50% Manual or Motorized
Outside Air
— Hail Protection Quality Coil Guards
— Electric Heaters (available as field
installed accessories)
Economizer
— Discharge Air Sensor
Equipped with either dry bulb, reference
or comparative enthalpy sensing, this
feature provides free cooling as the
outdoor temperature and/or humidity
decreases. Economizers, correctly
installed, offer a valuable energy
savings. Factory-installed economizers
save time and ensure proper installation.
— Wide array of Zone Sensors and
Thermostats
— Factory built Roof Curb
One of Our Finest Assets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
Clogged Filter/Fan Fail Switches
These sensors allow a zone sensor
service light or Integrated Comfort
System to indicate a dirty filter or a fan
that’s not working. The field installation
charges for these valuable feedback
devices often eliminate them from
consideration. Factory installation can
make such features a good investment.
— Computer Programs and much more
Precedent has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its airflow performance is
outstanding.
Comm-3/4 Trane Communication
Interface
Available factory or field-installed. This
module when applied with ReliaTel™
easily interfaces with Trane’s Integrated
Comfort™ System.
Precedent…The same Trane
quality…with added flexibility.
RT-PRC016-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Quality And Reliability Testing
• We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 1375 kPa (200
psig) and pressure tested to 3100 kPa
(450 psig).
• All Precedent™ designs were rigorously
rain tested at the factory to ensure
water integrity.
• Actual shipping tests were performed
to determine packaging requirements.
Units were test shipped around the
country to determine the best
packaging.
• All parts are inspected at the point of
final assembly. Sub-standard parts are
identified and rejected immediately.
• Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
• Factory shake and drop tests were
used as part of the package design
process to help assure that the unit
arrives at the job site in top condition.
We test designs at our factory not on
our customers!
• Rigging tests include lifting a unit into
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.
VariTrac™
VariTrac
When Trane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
RT-PRC016-EN
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
Low Ambient Cooling
The Precedent™ line features, with
ReliaTel™ microprocessor controls, low
ambient cooling down to 18°C (0°F).
Contact your local Trane Representative
for more assistance with low ambient
cooling applications.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate service
maximum capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be reviewed
with the localTrane sales personnel.
Barometric Relief
This product line offers an optional
barometric relief damper. for use in
conjunction with economizer option.
This accessory consists of gravity
dampers which open with increased
pressure. As the building air pressure
increases, the pressure in the unit return
air section also increases, opening the
dampers and relieving the conditioned
space.
Unit Pitch
These units have reversible sloped
condensate drain pans. Units must be
installed level, any unit slope must be
toward the side of unit where
condensate drain is connected.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDERED TO
CONTROL BUILDING PRESSURIZA-
TION.
RT-PRC016-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure - SI Units
Cooling Capacity
Step 3
Heating Capacity
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount
of heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure.To determine
the total unit static pressure:
Step 1
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
the Trane calculation methods or any
other standard accepted method.
Calculate the building heating load using
the Trane calculation form or other
standard accepted method.
Step 2
Factors used in unit selection:
Size the system heating capacity to
match the calculated building heating
load. The following are building heating
requirements:
A
Total Cooling Load: 16.7 kW
External Static (duct system)
110 Pa
B
A
Sensible Cooling Load: 11.7 kW
Standard Filter 1 in.
from Table PD-21
37 Pa
Total heating load of 5 kW
C
B
Airflow: 3400 m3/h
Economizer
5 Pa
2000 cfm
D
(100% Return Air)
Table PD-21
from
C
Electrical Characteristics: 380-415/50/3
380 volt/3 phase Power Supply
E
Electric Heater Size 7.5 kW
from Table PD-21
17 Pa
The electric heat accessory capacities are
listed in Table PD-23. From the table, the
smallest heater will deliver 7.5 kW at
380 V. Referring to Table ED-2, the
electric heater selection is
Summer Design Conditions: Entering
Evaporator Coil: 27 DB, 19 WB Outdoor
Ambient: 35
Total Static Pressure
169 Pa
Note: The Evaporator Fan Performance
Table PD-6 has deducted the pressure
drop for a 25 mm filter already in the
unit (see note below Table PD-6).
Therefore, the actual total static pressure
is 169-17 (from Table PD-21) = 152 Pa.
With 3400 m3/h and 152 Pa
Table PD-6 shows .67 kW for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
Fan Motor Heat (kw) =
1.144 x (Fan kW) + 0.132
F
External Static Pressure: 110 Pa
BAYHTRR412A.
Air Delivery Selection
Step 2
External static pressure drop through the
air distribution system has been
calculated to be 110 Pa. From Table PD-
21 static pressure drop through the
economizer is 5 Pa and the 7.5 kW heater
is 17 Pa (110 + 5 + 17). EnterTable PD-6
for a TSC060AD at 3400 m3/h and 132 Pa
static pressure. The standard motor will
give the desired airflow at a rated kW of
0.64.
Table PD-1 shows that a TSC060AD has a
gross cooling capacity of 17.8 kW and
14.4 kW sensible capacity at 3400 m3/h
and 35 DB outdoor ambient with 27 DB,
19 WB air entering the evaporator.
To Find Capacity at Intermediate
Conditions Not in the Table
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
= 1.144 x 0.67 + 0.132 = 0.90 kW
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
Net Total Cooling Capacity
Accessory Selection
Select accessories needed to
accommodate the application.
= 17.8 kW - 0.9 = 16.9 kW.
Net Sensible Cooling Capacity
= 14.4 kW - 0.9 = 13.5 kW.
Step 4
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
RT-PRC016-EN
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure - IP Units
Step 3
Heating Capacity
Cooling Capacity
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount
of heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure. To determine
the total unit static pressure:
Step 1
Step 1
Calculate the building heating load using
the Trane calculation form or other
standard accepted method.
Calculate the building’s total and sensible
cooling loads at design conditions. Use
the Trane calculation methods or any
other standard accepted method.
Step 2
Size the system heating capacity to
match the calculated building heating
load. The following are building heating
requirements:
Factors used in unit selection:
A
Total Cooling Load: 59 MBh
External Static (duct system)
0.45 wg
B
A
Sensible Cooling Load: 40 MBh
Standard Filter 1 in.
from Table PD-21a
0.15 wg
Total heating load of 15 MBH
C
B
Airflow: 2000 cfm
Economizer
0.02 wg
from
2000 cfm
D
(100% Return Air)
Table PD-21a
C
Electrical Characteristics: 380-415/50/3
380 volt/3 phase Power Supply
E
Electric Heater Size 26 MBh
from Table PD-21a
0.07 wg
The electric heat accessory capacities are
listed in Table PD-23a. From the table,
the smallest heater will deliver 26 MBh at
380 volts. Referring to Table ED-2, the
electric heater accessory selection is
BAYHTRR412A.
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67 WB Outdoor
Ambient: 95
Total Static Pressure
0.69 wg
Note: The Evaporator Fan Performance
Table PD-6a has deducted the pressure
drop for a 1 in. filter already in the unit
(see note below Table PD-6a). Therefore,
the actual total static pressure is 0.69 -
0.15 (from Table PD-21a) = 0.50 wg.
F
External Static Pressure: 0.45 in. wg
Step 2
Air Delivery Selection
Table PD-1a shows that a TSC060AD has
a gross cooling capacity of 62.0 MBh and
46.4 MBh sensible capacity at 2000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
External static pressure drop through the
air distribution system has been
calculated to be 0.45 inches of water.
From Table PD-21a static pressure drop
through the economizer is 0.02 and the
26 kW heater is 0.07 inches of water (0.45
+ 0.02 + 0.07). EnterTable PD-6a for a
TSC060AD at 2000 cfm and 0.54 static
pressure. The standard motor will give
the desired airflow at a rated bhp of
about 1.01.
With 2000 cfm and 0.50 wg.
Table PD-6a shows .83 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
Fan Motor Heat (MBh) =
2.915 x (Fan BHP) + 0.451
To Find Capacity at Intermediate
Conditions Not in the Table
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
= 2.915 x 0.83 + 0.451 = 2.87 MBh
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
Net Total Cooling Capacity
Accessory Selection
Select accessories needed to
accommodate the application.
= 62 MBh - 2.87 = 59.1 MBh.
Net Sensible Cooling Capacity
= 46.4 MBh - 2.87 = 43.5 MBh.
Step 5
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
RT-PRC016-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Num ber
Description
T
1
S
2
C
060
A
D
8
R
9
O
A
**
C
0
0
0
0
0
0
0
0
0
0
1
3 4,5,6 7
10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
Digit 1 - Unit Function
= DX Cooling
Digit 14 - Fresh Air Selection
0 = No Fresh Air
Digit 18 - Through the Base Provisions
0 = No Through the Base Provisions
T
A = Manual Outside Air Damper 0-50%
B = Motorized Outside Air Damper 0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
Digit 2 - Efficiency
= Standard Efficiency
Digit 19 - Disconnect/Circuit Breaker
0 = No Disconnect or Circuit Breaker
S
Digit 3 - Airflow
C = Convertible
Digit 20 - Convenience Outlet
0 = No Convenience Outlet
Digits 4,5,6 - Nominal Gross Cooling
Capacity (MBh)
Digit 21 - Communications Options
0 = No Communications Interface
1 = Comm-3/4 Communications Interface
2 = Comm-5 Communications Interface
kW
060 = 17.6
072 = 21.1
090 = 26.4
102 = 29.9
120 = 35.1
Tons
5
6
7.5
8.5
10
Digit 22 - Refrigeration System Option
0 = Standard Refrigeration System
Digit 23 - Refrigeration Controls
0 = No Refrigeration Control
Digit 7 - Major Design Sequence
A = First
Digit 15 - Supply Fan/Drive Type/Motor
0 = Standard Drive
1 = Oversized Motor
Digit 24 - Smoke Detector
0 = No Smoke Detector
Digit 8 - Unit Voltage
D = 380-415/50/3
Digit 25 - Monitoring Controls
0 = No Monitoring Control
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = Discharge Air Sensing Tube
4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
Digit 16 - Hinged Service Access/Filters
0 = Standard Panels/Standard Filters
A = Hinged Access Panels/Standard Filters
B = Standard Panels/
50 mm (2”) Pleated Filters
C = Hinged Access Panels/
Digit 9 - Unit Controls
R = ReliaTel™ Microprocessor
Digit 10 - Heating Capacity
0 = No Electric Heat
Digit 11 - Minor Design Sequence
A = First Sequence
50 mm (2”) Pleated Filters
Digit 17 - Condenser Coil Protection
0 = Standard Coil
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil
3 = Epoxy Coated Condenser Coil with
Hail Guard
Digits 12, 13 - Service Sequence
**= Factory Assigned
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
RT-PRC016-EN
12
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
Table GD - 1 — General Data
Convertible Units
Convertible Units
Convertible Units
TSC090AD
Convertible Units
TSC102AD
Convertible Units
TSC120AD
TSC060AD
TSC072AD
Cooling Performance 1
Gross Capacity - kW (MBh)
COP (EER)2
Nominal Airflow - m3/h (cfm)
Rated Airflow - m3/h (cfm)
Net Capacity - kW (MBh)
System Power - kW
18.2 (62.0)
2.99 (10.2)
3400 (2000)
3400 (2000)
17.3 (59.0)
5.78
23.2 (79.0)
3.08 (10.5)
4080 (2400)
3570 (2100)
22.0 (75.0)
7.14
26.7 (91.0)
3.02 (10.3)
5100 (3000)
4460 (2625)
25.2 (86.0)
8.35
31.1 (106.0)
3.02 (10.3)
5780 (3400)
5100 (3000)
29.9 (102.0)
9.90
34.9 (119.0)
2.99 (10.2)
6800 (4000)
5950 (3500)
33.1 (113.0)
11.08
Compressor
Number -Type
Outdoor Sound Rating - dB 3
Outdoor Coil -Type
1-Climatuff Scroll
80
1-Trane 3-D Scroll
85
1-Trane 3-D Scroll
85
2-Climatuff Scroll
83
2-Climatuff Scroll
79
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size - in. OD
Face Area - m2 (sq ft)
Rows / FPI
0.3125
1.02 (10.96)
3 / 17
0.3125
1.29 (13.88)
2 / 17
0.3125
1.29 (13.88)
2 / 17
0.3125
1.75 (18.89)
2 / 17
0.3125
2.41 (25.92)
2 / 17
Indoor Coil -Type
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size OD - in.
Face Area - m2 (sq ft)
Rows / FPI
0.3125
0.62 (6.68)
3 / 16
0.3125
0.92 (9.89)
2 / 16
0.3125
0.92 (9.89)
3 / 16
0.3125
1.15 (12.36)
3 / 16
0.3125
1.15 (12.36)
4 / 16
Refrigerant Control
Drain Connection No. / Size - in.
Outdoor Fan -Type
No. Used / Diameter - in.
DriveType / No. Speeds
CFM
Short Orifice
1 / 0.75 NPT
Propeller
1 / 22
Direct / 1
2900
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5100
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5200
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5500
Short Orifice
1 / 0.75 NPT
Propeller
1 / 26
Direct / 1
5800
No. Motors / kW (HP)
Motor RPM
1 / 0.30 (0.40)
950
1 / .56 (0.75)
950
1 / .56 (0.75)
950
1 / .56 (0.75)
950
1 / .56 (0.75)
950
Belt Drive Indoor Fan -Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Fan Diameter x Width - mm (in.)
DrvieType / No. Speeds
No. Motors
280 X 280 (11 x 11)
Belt / Variable Speed
1
305 X 305 (12 x 12)
Belt / Variable Speed
1
305 X 305 (12 x 12)
Belt / Variable Speed
1
381 X 381 (15 x 15)
Belt / Variable Speed
1
381 X 381 (15 x 15)
Belt / Variable Speed
1
Standard Motor Power - kW (HP)
Oversized Motor Power - kW (HP)
Motor RPM - Standard / Oversized
Motor Frame Size
1.1 (1.5)
1.1 (1.5)
1.5 (2.0)
1450 / 1450
56
1.5 (2.0)
2.2 (3.0)
1450 / 2850
56
1.5 (2.0)
2.2 (3.0)
1450 / 2850
56
2.2 (3.0)
-
-
1450 / -
56
2850 / -
56
Filters - Type Furnished
(No.) Size Reccommended - mm
(No.) Size Reccommended - in.
Refrigerant Charge - kg (lbs) of R-22 4
Throwaway
(2) 508 X 762 X 25
(2) 20 X 30 X 1
3.7 (8.2)
Throwaway
(4) 406 X 635 X 50
(4) 16 X 25 X 2
3.7 (8.2)
Throwaway
(4) 406 X 635 X 50
(4) 16 X 25 X 2
4.5 (10.0)
Throwaway
(4) 508 X 635 X 50
(4) 20 X 25 X 2
Circuit 1 - 3.8 (8.3)
Circuit 2 - 2.0 (4.4)
Throwaway
(4) 508 X 635 X 50
(4) 20 X 25 X 2
Circuit 1 - 3.4 (7.5)
Circuit 2 - 3.3 (7.3)
Notes:
1. Cooling Perform ance is rated at 35.0 C (95 F) am bient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan m otor
heat. Net capacity includes the effect of fan m otor heat. Units are suitable for operation to ± 20 % of nom inal airflow.
2. EER are rated at ARI conditions.
3. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For m ore inform ation refer to Perform ance Data Table "Sound Power Level".
4. Refrigerant charge is an approcim ate value. For a m ore precise value, see unit nam eplate and service literature.
RT-PRC016-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-1 — Gross Cooling Capacities (kW) -TSC060AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
Temp
(C)
24
27
30
33
24
27
30
33
24
27
30
33
24
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Airflow
16
19
22
16
22
16
22
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
16.2 13.9 18.5 11.3 19.9 8.3 15.0 13.3 17.4 11.3 19.3 8.0 13.9 12.7 16.1 10.7 18.4 7.5 12.7 12.1 14.7 9.5 17.3 7.0
16.7 16.7 18.6 14.1 20.0 11.1 15.8 15.8 17.4 13.6 19.4 10.8 14.8 14.8 16.1 13.0 18.5 10.3 13.8 13.8 14.7 12.3 17.3 9.8
18.1 18.1 18.7 16.9 20.2 13.6 17.2 17.2 17.7 16.5 19.5 13.5 16.2 16.2 16.5 15.9 18.5 13.1 15.1 15.1 15.1 15.1 17.3 12.6
19.3 19.3 19.2 19.2 20.3 16.2 18.5 18.5 18.5 18.5 19.6 16.1 17.6 17.6 17.6 17.6 18.7 15.9 16.6 16.6 16.6 16.6 17.5 15.4
16.7 14.8 18.8 11.8 20.1 8.6 15.5 14.2 17.8 11.3 19.5 8.3 14.2 13.5 16.5 11.4 18.7 7.7 13.1 12.9 15.0 10.8 17.6 7.2
17.5 17.5 18.9 14.9 20.2 11.4 16.5 16.5 17.8 14.4 19.6 11.2 15.4 15.4 16.5 13.8 18.8 10.8 14.4 14.4 15.1 13.1 17.6 10.3
18.8 18.8 19.1 17.9 20.4 14.1 17.9 17.9 18.2 17.6 19.7 14.1 16.9 16.9 17.0 17.0 18.8 13.8 15.8 15.8 15.8 15.8 17.7 13.4
19.8 19.8 19.8 19.8 20.6 16.8 19.2 19.2 19.2 19.2 19.9 16.9 18.3 18.3 18.3 18.3 19.0 16.8 17.4 17.4 17.4 17.4 17.9 16.4
17.1 15.6 19.1 12.3 20.2 8.8 15.9 15.0 18.1 11.8 19.7 8.5 14.6 14.3 16.8 11.2 18.9 7.9 13.4 13.4 15.3 11.4 17.8 7.5
18.1 18.1 19.2 15.5 20.4 11.6 17.1 17.1 18.2 15.1 19.8 11.5 16.0 16.0 16.9 14.6 19.0 11.3 14.9 14.9 15.4 13.9 17.9 10.8
19.3 19.3 19.5 18.7 20.6 14.5 18.5 18.5 18.6 18.6 20.0 14.6 17.6 17.6 17.6 17.6 19.1 14.4 16.5 16.5 16.5 16.5 17.9 14.1
20.2 20.2 20.2 20.2 20.8 17.4 19.6 19.6 19.6 19.6 20.2 17.6 18.9 18.9 18.9 18.9 19.3 17.6 18.0 18.0 18.0 18.0 18.3 17.4
17.4 16.4 19.3 12.6 20.3 9.1 16.2 15.8 18.4 12.2 19.8 8.8 14.9 14.9 17.1 11.7 19.0 8.1 13.9 13.9 15.5 12.1 18.0 7.7
18.6 18.6 19.4 16.1 20.5 12.3 17.7 17.7 18.4 15.8 19.9 11.8 16.6 16.6 17.2 15.3 19.1 11.6 15.4 15.4 15.8 14.6 18.1 11.2
19.7 19.7 19.7 19.4 20.7 14.9 19.0 19.0 19.0 19.0 20.1 15.0 18.1 18.1 18.1 18.1 19.3 15.0 17.1 17.1 17.1 17.1 18.2 14.7
20.5 20.5 20.5 20.5 20.9 17.9 20.0 20.0 20.0 20.0 20.4 18.2 19.3 19.3 19.3 19.3 19.5 18.3 18.4 18.4 18.4 18.4 18.6 18.2
3060
3400
3740
27
30
33
4080
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-1a — Gross Cooling Capacities (MBH) _ TSC060AD _ (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
Temp
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Airflow
61
67
73
61
73
61
73
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
56.1 47.1 64.4 37.0 68.8 25.1 51.6 44.7 60.6 36.7 66.9 23.9 47.0 42.4 55.6 34.5 64.0 22.6 42.4 40.1 50.2 30.3 60.0 20.8
57.3 56.5 64.6 45.8 69.3 34.2 53.3 53.3 60.7 43.9 67.3 32.9 49.5 49.5 55.7 41.6 64.2 31.4 45.7 45.7 50.4 39.2 60.1 29.6
61.3 61.3 64.9 54.5 69.7 42.0 57.7 57.7 61.0 52.9 67.6 41.4 53.9 53.9 56.3 50.7 64.4 40.3 50.0 50.0 51.2 48.3 60.2 38.4
65.0 65.0 65.8 63.3 70.4 49.7 62.1 62.1 62.4 62.2 68.0 49.7 58.5 58.5 58.5 58.5 64.6 48.8 54.4 54.4 54.4 54.4 60.3 47.2
57.5 49.8 65.4 38.5 69.3 25.5 53.0 47.5 61.8 38.7 67.5 24.4 48.3 45.1 56.9 36.6 64.7 23.0 43.7 42.8 51.3 34.2 60.9 21.4
59.3 59.3 65.6 47.9 69.8 35.4 55.7 55.7 62.0 46.4 68.0 34.2 51.6 51.6 57.1 44.1 65.0 32.7 47.7 47.7 51.5 41.6 61.0 30.9
63.6 63.6 66.0 57.3 70.5 43.1 60.3 60.3 62.5 56.2 68.3 43.0 56.4 56.4 58.0 54.1 65.2 42.1 52.2 52.2 52.8 51.7 61.2 40.6
66.9 66.9 67.2 66.5 71.1 51.4 64.4 64.4 64.4 64.4 68.9 51.8 61.0 61.0 61.0 61.0 65.6 51.3 57.1 57.1 57.1 57.1 61.5 50.1
58.8 52.5 66.1 39.8 69.6 25.9 54.3 50.2 62.8 38.1 67.9 24.9 49.4 47.8 58.0 38.6 65.3 23.4 44.8 44.8 52.2 36.2 61.6 21.7
61.5 61.5 66.4 49.8 70.3 36.8 57.8 57.8 63.0 48.6 68.3 35.0 53.6 53.6 58.2 46.5 65.6 33.9 49.4 49.4 52.6 44.0 61.8 32.2
65.4 65.4 67.0 59.8 71.0 44.6 62.4 62.4 63.7 59.2 69.0 44.3 58.7 58.7 59.4 57.4 66.0 43.8 54.3 54.3 54.3 54.3 62.0 42.5
68.4 68.4 68.4 68.4 71.7 52.8 66.1 66.1 66.1 66.1 69.6 53.6 63.1 63.1 63.0 63.0 66.4 53.6 59.3 59.3 59.3 59.3 62.4 52.7
60.0 55.1 66.6 40.8 70.0 26.4 55.5 52.8 63.6 39.6 68.3 25.3 50.6 50.4 59.0 37.4 65.7 24.0 46.2 46.2 53.1 38.2 62.2 22.1
63.2 63.2 67.1 51.4 70.7 37.7 59.6 59.6 63.8 50.7 68.8 35.8 55.4 55.4 59.2 48.8 66.2 35.0 51.1 51.1 53.5 46.3 62.4 33.4
66.7 66.7 67.8 62.0 71.5 45.3 64.1 64.1 64.8 61.9 69.5 45.5 60.5 60.5 60.8 60.6 66.6 45.2 56.3 56.3 56.2 56.2 62.7 44.3
69.5 69.5 69.5 69.5 72.1 54.1 67.4 67.4 67.4 67.4 70.2 55.3 64.6 64.6 64.5 64.5 67.1 55.7 61.1 61.1 61.0 61.0 63.2 55.1
1800
2000
2200
80
85
90
2400
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-2 — Gross Cooling Capacities (kW) -TSC072AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
Temp
(C)
24
27
30
33
24
27
30
33
24
27
30
33
24
30
35
19
40
45
19
Entering Wet Bulb Temperature (C)
m3/h
Airflow
16
19
22
16
22
16
19
22
16
22
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
20.9 17.5 23.3 14.6 24.6 10.3 19.7 16.8 22.4 13.6 24.0 9.9 18.4 16.1 21.2 12.9 23.2 9.4 17.1 15.4 19.7 12.9 22.0 9.0
21.6 21.2 23.4 17.4 24.8 13.5 20.4 20.4 22.5 17.0 24.1 13.3 19.4 19.4 21.2 16.4 23.3 12.8 18.2 18.2 19.8 15.7 22.1 12.3
22.9 22.9 23.6 20.6 25.0 16.5 22.1 22.1 22.7 20.4 24.3 16.3 21.0 21.0 21.5 19.9 23.5 16.1 19.9 19.9 20.2 19.2 22.2 15.6
24.0 24.0 24.1 23.8 25.2 19.4 23.4 23.4 23.3 23.3 24.5 19.3 22.5 22.5 22.4 22.4 23.6 19.3 21.4 21.4 21.4 21.4 22.3 18.8
21.5 18.5 23.6 15.2 24.8 10.6 20.3 17.9 22.8 14.2 24.2 10.1 19.0 17.2 21.6 13.6 23.4 9.8 17.6 16.4 20.1 12.9 22.3 9.3
22.3 22.3 23.8 18.1 25.1 14.5 21.3 21.3 22.9 17.9 24.3 13.6 20.2 20.2 21.6 17.3 23.6 13.4 19.0 19.0 20.2 16.6 22.4 12.8
23.6 23.6 24.0 21.6 25.3 17.6 22.9 22.9 23.2 21.5 24.6 16.8 21.8 21.8 22.0 21.1 23.7 16.7 20.7 20.7 20.8 20.5 22.5 16.3
24.6 24.6 24.6 24.6 25.5 20.0 23.9 23.9 23.9 23.9 24.8 20.1 23.1 23.1 23.1 23.1 23.9 20.1 22.1 22.1 22.1 22.1 22.7 19.8
22.0 19.5 23.9 15.8 25.0 10.7 20.8 18.9 23.1 14.7 24.4 10.4 19.5 18.2 21.9 14.2 23.5 10.1 18.1 17.4 20.5 13.5 22.5 9.6
22.9 22.9 24.0 18.7 25.3 13.9 22.1 22.1 23.2 18.6 24.5 13.9 20.9 20.9 22.0 18.2 23.7 13.6 19.7 19.7 20.6 17.6 22.6 13.3
24.1 24.1 24.3 22.4 25.5 17.4 23.4 23.4 23.5 22.4 24.8 17.3 22.5 22.5 22.5 22.2 23.9 17.2 21.3 21.3 21.3 21.3 22.8 17.0
25.0 25.0 25.0 25.0 25.7 20.7 24.4 24.4 24.4 24.4 25.1 20.8 23.7 23.7 23.7 23.7 24.2 20.8 22.6 22.6 22.6 22.6 23.1 20.7
22.4 20.3 24.1 16.3 25.2 10.9 21.2 19.8 23.2 15.1 24.5 10.7 19.9 19.1 22.2 14.7 23.6 10.3 18.5 18.4 20.8 14.0 22.7 9.9
23.4 23.4 24.3 19.3 25.5 14.5 22.6 22.6 23.4 19.2 24.7 14.7 21.5 21.5 22.3 19.0 23.8 14.0 20.3 20.3 20.9 18.4 22.8 13.7
24.5 24.5 24.6 23.2 25.6 17.8 23.8 23.8 23.9 23.2 25.0 17.8 23.0 23.0 23.0 23.0 24.1 17.7 21.8 21.8 21.8 21.8 23.0 17.7
25.4 25.4 25.4 25.4 25.9 21.2 24.8 24.8 24.8 24.8 25.3 21.4 24.1 24.1 24.1 24.1 24.4 21.4 23.1 23.1 23.1 23.1 23.4 21.6
3670
4080
4490
27
30
33
4900
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-2a — Gross Cooling Capacities (MBH) -TSC072AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
Temp
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Airflow
61
67
73
61
73
61
73
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
72.2 59.1 80.6 47.1 85.1 31.0 67.5 56.5 77.7 44.1 82.7 29.6 62.6 53.9 73.0 41.8 79.9 28.0 57.4 51.2 67.5 39.2 75.5 26.0
73.8 70.7 81.0 56.1 85.8 42.2 69.4 68.2 77.9 55.0 83.4 40.7 65.0 65.0 73.1 52.6 80.4 39.0 60.6 60.6 67.6 50.0 75.8 36.8
77.7 77.7 81.4 66.3 86.3 51.7 74.3 74.3 78.2 65.6 83.8 50.1 70.3 70.3 73.6 63.5 80.7 49.2 66.0 66.0 68.3 61.0 76.1 47.4
81.3 81.3 82.4 76.3 87.1 59.8 78.8 78.8 79.4 76.0 84.6 59.4 75.1 75.1 75.3 74.6 81.3 59.0 70.8 70.8 70.7 70.7 76.6 57.4
74.2 62.5 81.6 49.2 85.7 31.5 69.3 59.9 78.7 46.0 83.4 30.1 64.4 57.3 74.2 43.7 80.2 28.5 59.1 54.6 68.9 41.1 76.3 26.6
76.1 75.0 82.1 58.2 86.5 43.7 72.1 72.1 79.0 57.4 84.2 42.1 67.9 67.9 74.4 55.4 80.9 40.4 63.3 63.3 69.0 53.0 76.8 38.4
80.0 80.0 82.6 69.1 86.8 52.8 77.1 77.1 79.5 68.7 84.7 51.6 73.1 73.1 75.3 67.3 81.4 50.7 68.7 68.7 70.1 65.0 77.2 49.4
83.3 83.3 83.8 79.7 87.1 61.5 80.7 80.7 80.9 79.4 85.5 61.5 77.5 77.5 77.5 77.5 82.1 61.1 73.3 73.3 73.3 73.3 77.8 60.2
75.8 65.6 82.3 50.7 86.2 32.0 71.0 63.2 79.4 49.8 84.0 30.7 66.0 60.6 75.4 45.6 80.7 29.0 60.6 57.8 70.0 42.9 77.0 27.2
78.1 78.1 82.9 60.1 87.2 44.1 74.6 74.6 79.8 59.4 84.7 44.3 70.3 70.3 75.6 58.1 81.2 41.3 65.7 65.7 70.1 55.7 77.6 39.8
81.7 81.7 83.6 71.6 88.2 54.0 79.1 79.1 80.5 71.3 85.4 53.6 75.4 75.4 76.6 70.7 82.0 52.1 70.9 70.9 71.6 68.7 78.1 51.3
84.8 84.8 85.0 82.5 89.1 62.3 82.3 82.3 82.3 82.3 86.1 61.2 79.4 79.4 79.4 79.4 82.8 63.0 75.2 75.2 75.2 75.2 78.7 62.8
77.0 68.3 82.9 52.2 86.6 32.5 72.5 66.4 80.0 51.4 84.5 31.2 67.5 63.7 76.2 47.1 81.2 29.5 62.1 61.0 70.8 44.7 77.6 27.8
79.6 79.6 83.7 61.8 87.6 44.7 76.6 76.6 80.6 61.3 85.4 44.0 72.4 72.4 76.5 60.5 81.8 42.1 67.7 67.7 71.1 58.2 78.1 40.9
83.0 83.0 84.4 73.9 88.7 54.9 80.4 80.4 81.5 73.9 86.2 54.1 77.1 77.1 77.8 73.8 82.7 53.5 72.7 72.7 72.9 71.9 78.8 53.0
85.9 85.9 86.0 85.0 89.6 65.2 83.6 83.6 83.6 83.6 87.0 63.2 81.0 81.0 81.0 81.0 83.5 65.0 76.8 76.8 76.8 76.8 79.5 65.3
2160
2400
2640
80
85
90
2880
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-3 — Gross Cooling Capacities (kW) -TSC090AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
Temp
(C)
24
27
30
33
24
27
30
33
24
27
30
33
24
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Airflow
16
19
22
16
22
16
22
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24.5 21.6 26.9 17.1 28.1 12.0 22.7 20.6 25.8 16.3 27.7 11.5 20.8 19.6 24.1 15.4 26.8 11.0 19.0 18.7 22.0 14.8 25.6 10.3
25.4 25.4 27.1 21.1 28.5 15.9 24.1 24.1 25.9 20.8 27.8 15.9 22.5 22.5 24.3 20.0 27.0 15.5 20.9 20.9 22.2 19.0 25.7 14.8
27.0 27.0 27.4 25.3 28.7 19.5 26.0 26.0 26.4 25.3 28.1 19.7 24.8 24.8 25.0 24.8 27.1 19.6 23.2 23.2 23.1 23.1 25.8 19.2
28.1 28.1 28.1 28.1 29.0 23.3 27.5 27.5 27.5 27.5 28.4 23.6 26.5 26.5 26.5 26.5 27.4 23.9 25.3 25.3 25.3 25.3 26.1 23.6
25.1 23.0 27.2 18.1 28.4 12.4 23.4 22.1 26.2 17.1 27.8 11.9 21.4 21.1 24.6 16.8 27.1 11.3 19.7 19.7 22.5 15.3 25.9 10.7
26.3 26.3 27.4 22.0 28.6 16.3 25.1 25.1 26.4 22.0 28.0 16.2 23.6 23.6 24.9 21.4 27.2 16.0 21.9 21.9 22.8 20.4 26.0 15.6
27.6 27.6 27.8 26.4 29.0 20.2 26.8 26.8 27.0 26.8 28.3 20.4 25.7 25.7 25.7 25.7 27.4 20.6 24.3 24.3 24.3 24.3 26.2 20.4
28.6 28.6 28.6 28.6 29.3 24.1 28.1 28.1 28.1 28.1 28.7 24.6 27.3 27.3 27.3 27.3 27.8 25.0 26.2 26.2 26.2 26.2 26.6 25.1
25.6 24.2 27.4 18.4 28.4 12.5 24.0 23.5 26.5 18.3 28.0 12.2 22.0 22.0 25.1 17.1 27.3 11.7 20.4 20.4 22.9 16.2 26.2 11.1
26.9 26.9 27.7 22.8 28.8 16.5 25.9 25.9 26.8 23.0 28.3 16.7 24.5 24.5 25.4 22.7 27.4 16.5 22.8 22.8 23.5 21.8 26.3 16.3
28.0 28.0 28.1 27.3 29.1 20.6 27.4 27.4 27.4 27.4 28.7 21.2 26.5 26.5 26.4 26.4 27.7 21.4 25.2 25.2 25.2 25.2 26.5 21.4
28.9 28.9 28.9 28.9 29.5 24.7 28.5 28.5 28.5 28.5 29.1 25.6 27.8 27.8 27.8 27.8 28.1 26.0 26.8 26.8 26.8 26.8 27.0 26.3
26.1 25.4 27.6 18.5 28.5 12.7 24.5 24.5 26.7 19.1 28.1 12.5 22.8 22.8 25.4 18.0 27.4 12.0 21.1 21.1 23.4 17.0 26.3 11.4
27.3 27.3 27.9 23.4 28.9 16.8 26.5 26.5 27.1 23.9 28.5 17.1 25.3 25.3 25.8 23.8 27.7 17.0 23.6 23.6 24.1 23.1 26.5 16.9
28.3 28.3 28.4 28.1 29.2 21.0 27.8 27.8 27.8 27.8 28.8 21.8 27.0 27.0 27.0 27.0 27.9 22.1 25.8 25.8 25.8 25.8 26.8 22.3
29.1 29.1 29.1 29.1 29.6 25.2 28.8 28.8 28.8 28.8 29.3 26.4 28.2 28.2 28.2 28.2 28.4 26.9 27.3 27.3 27.3 27.3 27.4 27.4
4590
5100
5610
27
30
33
6120
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-3a — Gross Cooling Capacities (MBH) -TSC090AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
Temp
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Airflow
61
67
73
61
73
61
73
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
84.4 72.7 92.7 55.2 96.6 35.6 77.7 69.1 89.4 52.6 95.2 34.0 70.4 65.4 83.4 50.6 92.5 32.0 63.7 61.9 75.3 46.9 88.2 29.8
86.5 86.5 93.3 67.5 97.8 48.9 81.2 81.2 89.6 66.8 96.2 48.4 75.1 75.1 83.8 64.0 93.1 46.6 69.4 69.4 75.8 60.3 88.5 44.1
91.5 91.5 94.2 80.6 98.9 59.9 87.7 87.7 90.6 80.8 97.2 60.5 82.5 82.5 85.1 78.8 93.5 59.5 76.4 76.4 77.7 75.2 88.8 58.1
95.1 95.1 95.7 93.2 100.0 71.0 92.6 92.6 92.5 92.5 97.5 71.8 88.7 88.7 88.7 88.7 94.3 72.6 83.7 83.7 83.6 83.6 89.5 71.8
86.5 77.3 93.5 56.9 97.1 36.1 80.0 73.9 90.6 56.4 95.8 34.6 72.6 70.1 85.2 52.3 93.2 32.7 65.6 65.6 76.9 49.9 89.1 30.5
89.4 89.4 94.3 70.0 98.3 52.8 84.9 84.9 91.0 70.2 96.9 49.4 78.8 78.8 85.6 68.2 93.9 48.9 72.7 72.7 77.8 64.5 89.6 46.3
93.6 93.6 95.4 83.8 99.4 61.1 90.6 90.6 92.2 85.2 98.0 62.3 86.1 86.1 87.3 84.2 94.5 61.9 80.1 80.1 80.1 80.1 90.0 61.2
96.8 96.8 97.0 96.7 100.5 72.8 94.8 94.8 94.8 94.8 99.0 75.4 91.5 91.5 91.4 91.4 95.4 75.8 87.0 87.0 87.0 87.0 90.9 75.9
88.1 81.3 94.3 59.1 97.5 36.7 82.1 78.5 91.4 58.6 96.2 35.2 74.1 74.1 86.4 54.8 93.7 33.4 68.1 68.1 78.5 51.2 89.8 31.2
91.4 91.4 95.1 72.1 98.7 50.2 87.6 87.6 92.1 73.3 97.4 50.3 82.2 82.2 87.1 72.0 94.5 49.7 75.6 75.6 79.7 68.7 90.4 48.3
95.1 95.1 96.2 86.6 99.8 62.1 92.7 92.7 93.6 89.0 98.5 63.8 88.8 88.8 89.2 89.1 95.2 64.0 83.5 83.5 83.5 83.5 90.9 63.9
97.9 97.9 97.9 97.9 101.0 74.3 96.4 96.4 96.3 96.3 99.7 77.5 93.5 93.5 93.5 93.5 96.3 78.6 89.4 89.4 89.4 89.4 92.1 79.5
89.5 85.0 95.1 60.6 97.8 37.2 84.0 83.1 92.2 60.7 96.6 35.7 76.7 76.7 87.5 57.3 94.1 34.0 70.4 70.4 80.0 53.8 90.4 31.9
92.9 92.9 95.6 74.0 99.0 50.8 89.7 89.7 93.0 76.0 97.8 51.0 84.8 84.8 88.3 75.6 95.2 50.9 78.1 78.1 81.6 72.8 90.9 49.5
96.2 96.2 96.9 88.9 100.2 63.1 94.2 94.2 94.7 92.3 99.0 65.1 90.7 90.7 90.7 90.7 95.8 65.8 86.0 86.0 86.0 86.0 91.7 66.3
98.7 98.7 98.7 98.7 101.3 75.7 97.5 97.5 97.5 97.5 100.1 79.4 94.9 94.9 94.9 94.9 97.0 81.1 91.2 91.2 91.2 91.2 93.0 82.7
2700
3000
3300
80
85
90
3600
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-4 — Gross Cooling Capacities (kW) - TSC102AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
Temp
(C)
24
27
30
33
24
27
30
33
24
27
30
33
24
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Airflow
16
19
22
16
22
16
22
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
28.0 24.3 31.5 19.5 33.4 14.1 26.0 23.3 30.0 18.7 32.5 13.5 23.9 22.2 27.8 17.7 31.3 12.9 21.6 21.6 25.4 17.3 29.7 12.2
29.0 28.4 31.6 24.3 33.6 18.7 27.4 27.1 30.1 23.6 32.7 18.5 25.6 25.6 28.0 22.7 31.4 17.8 23.9 23.9 25.6 21.6 29.8 17.1
31.0 31.0 31.9 29.0 33.9 23.0 29.7 29.7 30.5 28.6 32.9 22.8 28.1 28.1 28.1 28.1 31.5 22.5 26.3 26.3 26.5 25.7 29.9 22.0
32.6 32.6 32.7 32.1 34.1 27.3 31.6 31.6 31.6 31.4 33.2 27.3 30.4 30.4 30.3 30.3 31.8 27.2 28.9 28.9 28.8 28.8 30.2 26.8
28.8 25.8 31.9 20.4 33.6 14.4 26.8 24.8 30.5 19.6 32.8 13.9 24.2 24.2 28.5 18.7 31.6 13.4 22.5 22.5 26.0 17.6 30.1 12.6
30.1 29.8 32.1 25.4 34.0 19.2 28.6 28.6 30.7 25.0 32.9 19.1 26.8 26.8 28.8 24.2 31.7 18.6 25.0 25.0 26.3 23.1 30.2 17.9
32.0 32.0 32.5 30.5 34.2 23.7 30.9 30.9 30.9 30.9 33.2 23.7 29.4 29.4 29.4 29.4 31.9 23.6 27.6 27.6 27.7 27.2 30.3 23.2
33.4 33.4 33.4 33.2 34.5 28.1 32.6 32.6 32.5 32.5 33.6 28.5 31.4 31.4 31.4 31.4 32.3 28.5 30.0 30.0 30.0 30.0 30.8 28.3
29.5 27.3 32.2 21.1 33.8 14.7 27.6 26.3 31.0 20.5 33.0 14.4 25.1 25.1 29.1 19.6 31.8 13.8 23.5 22.9 26.5 18.5 30.4 12.9
31.0 31.0 32.5 26.5 34.2 19.7 29.7 29.7 31.2 26.3 33.3 19.5 27.9 27.9 29.4 25.6 32.0 19.2 26.0 26.0 27.0 24.5 30.5 18.7
32.7 32.7 33.0 31.7 34.6 24.5 31.7 31.7 31.7 31.7 33.6 24.6 30.4 30.4 30.5 29.9 32.3 24.5 28.8 28.8 28.8 28.6 30.7 24.3
34.0 34.0 34.0 34.0 34.8 28.9 33.2 33.2 33.2 33.2 33.9 29.5 32.1 32.1 32.1 32.1 32.7 29.7 30.9 30.9 30.9 30.9 31.3 29.7
30.1 28.7 32.5 21.7 33.9 15.1 27.9 27.9 31.3 21.4 33.1 14.7 26.0 26.0 29.3 20.4 32.2 14.2 24.2 23.9 27.0 19.4 30.6 13.3
31.7 31.7 32.8 27.4 34.4 20.0 30.5 30.5 31.6 27.4 33.4 20.0 28.8 28.8 29.8 26.9 32.3 19.7 26.9 26.9 27.6 25.9 30.7 19.4
33.2 33.2 33.2 33.2 34.8 25.0 32.3 32.3 32.4 31.7 33.7 25.2 31.2 31.2 31.2 30.9 32.6 25.4 29.7 29.7 29.7 29.7 31.0 25.3
34.4 34.4 34.4 34.4 35.2 30.0 33.7 33.7 33.7 33.7 34.2 30.4 32.9 32.9 32.9 32.9 33.1 30.8 31.5 31.5 31.5 31.5 31.4 31.4
5200
5780
6360
27
30
33
6940
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-4a — Gross Cooling Capacities (MBH) - TSC102AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
Temp
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Airflow
61
67
73
61
73
61
73
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
96.7 81.9 109.1 63.4 115.0 42.2 89.1 78.1 104.0 60.7 112.1 40.4 81.2 74.1 96.3 59.2 107.9 38.3 73.7 70.3 87.0 55.2 102.4 35.8
98.2 98.2 109.4 78.3 116.1 58.1 92.7 90.8 104.2 76.3 113.0 56.2 85.7 85.2 96.6 72.9 108.5 53.9 79.3 79.3 87.4 68.8 102.7 51.3
105.0 105.0 110.2 93.1 117.3 70.8 100.0 100.0 105.0 91.8 113.6 70.4 93.6 93.6 98.0 88.8 108.9 68.7 86.8 86.8 89.2 84.7 103.1 66.7
110.4 110.4 111.6 107.4 118.0 84.0 106.5 106.5 106.4 106.4 114.4 83.5 101.4 101.4 101.7 99.6 109.6 83.1 94.8 94.8 94.9 94.6 103.5 81.6
99.3 87.0 110.2 65.9 115.6 42.9 91.8 83.2 105.8 63.7 112.9 41.1 83.6 79.1 98.7 60.6 108.8 39.0 75.2 75.2 89.0 58.6 103.4 36.5
102.5 100.4 110.9 81.6 116.9 59.2 96.7 95.9 106.0 80.4 113.8 58.8 89.7 89.7 99.0 77.4 109.6 56.1 82.9 82.9 89.7 73.3 103.9 53.5
108.4 108.4 111.9 97.4 118.2 72.7 104.1 104.1 107.2 97.0 114.6 72.7 98.2 98.2 100.8 94.9 110.1 71.5 91.0 91.0 91.0 91.0 104.2 70.0
113.2 113.2 113.1 113.1 119.5 86.5 109.7 109.7 109.9 107.6 115.6 86.6 105.1 105.1 105.1 104.4 111.0 86.9 99.4 99.4 99.2 99.2 105.1 86.0
101.6 91.8 111.3 67.8 116.2 43.6 94.3 88.2 107.1 66.5 113.5 41.8 84.7 84.7 100.4 63.0 109.5 39.6 78.4 76.4 90.9 59.0 104.2 37.1
105.4 104.4 112.1 84.5 117.6 60.0 100.3 100.3 107.4 84.0 114.7 59.4 93.4 93.4 100.9 81.6 110.0 57.9 86.1 86.1 91.7 77.7 104.8 55.6
111.0 111.0 113.3 101.2 118.9 74.2 107.0 107.0 108.9 101.7 116.0 74.8 101.8 101.8 101.8 101.8 111.2 73.8 94.9 94.9 94.9 94.9 105.3 72.9
115.2 115.2 115.2 115.2 120.3 88.6 112.1 112.1 112.1 111.1 116.5 89.3 107.8 107.8 107.7 107.7 112.1 90.2 102.6 102.6 102.6 102.6 106.4 90.0
103.5 96.3 112.1 69.5 116.6 43.8 94.9 94.9 107.9 68.7 114.0 42.5 87.5 87.5 101.8 65.6 110.0 40.3 80.7 79.5 92.4 61.7 104.8 37.8
107.9 107.9 113.0 87.1 118.1 60.8 103.1 103.1 108.6 87.3 115.3 60.3 96.8 96.8 102.5 85.6 110.7 59.5 89.1 89.1 93.7 82.0 105.4 57.5
112.9 112.9 114.4 104.5 119.5 75.5 109.3 109.3 110.4 105.7 116.7 76.5 104.5 104.5 104.5 104.5 111.9 76.7 98.2 98.2 98.6 96.7 106.2 75.5
116.7 116.7 116.7 116.7 120.9 90.6 113.9 113.9 113.8 113.8 117.9 92.9 109.9 109.9 109.8 109.8 113.0 93.2 104.9 104.9 104.9 104.9 107.5 93.5
3060
3400
3740
80
85
90
4080
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-5 — Gross Cooling Capacities (kW) -TSC120AD - (SI)
Ambient Temperature (C)
Enter.
Dry
Bulb
Temp
(C)
24
27
30
33
24
27
30
33
24
27
30
33
24
30
35
40
45
19
Entering Wet Bulb Temperature (C)
19 22 16 19
m3/h
Airflow
16
19
22
16
22
16
22
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
31.9 28.6 35.3 22.8 37.2 15.9 29.6 27.4 33.6 21.7 36.5 15.4 27.1 26.2 31.0 20.5 35.2 14.8 24.6 24.6 28.4 19.9 33.2 14.0
33.4 33.4 35.5 28.2 37.7 21.4 31.6 31.6 33.9 27.8 36.7 21.4 29.5 29.5 31.3 26.6 35.3 20.7 27.5 27.5 28.9 25.5 33.3 19.9
35.5 35.5 36.0 33.8 38.1 26.5 34.2 34.2 34.5 33.8 37.0 26.7 32.3 32.3 32.2 32.2 35.5 26.6 30.4 30.4 30.4 30.4 33.4 25.9
37.1 37.1 37.1 37.1 38.5 31.6 36.2 36.2 36.2 36.2 37.3 31.9 34.8 34.8 34.8 34.8 35.9 32.3 33.2 33.2 33.2 33.2 34.0 31.8
32.7 30.4 35.7 23.8 37.5 16.3 30.5 29.3 34.2 22.8 36.8 15.9 27.8 27.8 31.9 21.8 35.5 15.3 25.7 25.7 29.0 21.2 33.7 14.5
34.5 34.5 36.0 29.5 38.0 21.9 32.9 32.9 34.5 29.4 37.0 22.0 30.9 30.9 32.3 28.5 35.7 21.7 28.7 28.7 29.7 27.4 33.8 21.0
36.3 36.3 36.6 35.4 38.4 27.4 35.3 35.3 35.3 35.3 37.3 27.6 33.7 33.7 33.7 33.7 35.9 27.8 31.8 31.8 31.7 31.7 34.0 27.5
37.9 37.9 37.8 37.8 38.9 32.8 37.0 37.0 37.0 37.0 37.8 33.3 35.9 35.9 35.9 35.9 36.5 33.9 34.4 34.4 34.4 34.4 34.7 33.8
33.5 32.2 36.0 24.7 37.8 16.9 31.1 31.1 34.7 23.9 37.0 16.3 28.9 28.9 32.4 22.9 35.8 15.7 26.6 26.6 29.6 22.5 34.1 14.9
35.3 35.3 36.4 30.6 38.2 22.4 34.0 34.0 35.0 30.8 37.4 22.7 32.0 32.0 33.0 30.2 36.0 22.5 29.9 29.9 30.5 29.1 34.2 22.0
37.0 37.0 37.0 37.0 38.7 28.1 36.1 36.1 36.1 36.1 37.9 28.9 34.7 34.7 34.7 34.7 36.4 29.1 32.9 32.9 32.9 32.9 34.5 29.0
38.4 38.4 38.3 38.3 39.2 33.7 37.7 37.7 37.7 37.7 38.4 34.9 36.7 36.7 36.7 36.7 37.0 35.4 35.3 35.3 35.3 35.3 35.3 35.3
33.9 33.9 36.3 24.9 37.9 17.3 32.0 32.0 35.0 25.6 37.5 16.1 29.8 29.8 32.8 23.9 36.1 16.2 27.5 27.5 29.8 23.6 34.4 15.3
35.9 35.9 36.7 31.7 38.5 22.8 34.8 34.8 35.5 32.2 37.7 23.2 32.9 32.9 33.6 31.9 36.3 23.2 30.6 30.6 30.6 30.6 34.5 23.0
37.5 37.5 37.5 37.5 38.9 28.8 36.7 36.7 36.7 36.7 38.1 29.8 35.5 35.5 35.5 35.5 36.7 30.2 33.7 33.7 33.7 33.7 34.9 30.5
38.8 38.8 38.7 38.7 39.5 34.6 38.4 38.4 38.2 38.2 38.7 36.1 37.3 37.3 37.3 37.3 37.4 36.7 36.0 36.0 36.0 36.0 36.0 36.0
6120
6800
7480
27
30
33
8160
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-5a — Gross Cooling Capacities (MBH) -TSC120AD - (IP)
Ambient Temperature (F)
Enter.
Dry
Bulb
Temp
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
85
95
105
115
67
Entering Wet Bulb Temperature (F)
67 73 61 67
CFM
Airflow
61
67
73
61
73
61
73
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
109.9 96.4 122.1 73.8 128.5 47.6 101.2 92.1 116.7 70.3 125.9 45.7 91.8 87.5 107.7 67.7 121.6 43.4 82.1 82.1 97.2 63.2 115.0 40.9
113.5 113.5 122.6 90.4 129.9 65.7 106.6 106.6 117.1 89.2 127.2 65.0 99.0 99.0 108.4 85.4 122.2 62.4 91.0 91.0 98.2 81.0 115.2 59.7
120.2 120.2 123.8 108.0 131.3 80.9 115.2 115.2 118.5 107.9 127.8 81.5 108.1 108.1 110.5 104.9 122.6 80.6 100.3 100.3 100.3 100.3 115.4 78.4
125.4 125.4 125.4 125.4 132.7 96.3 121.8 121.8 121.8 121.8 128.7 97.3 116.4 116.4 116.4 116.4 123.6 98.2 109.2 109.2 109.2 109.2 116.4 97.0
112.7 102.4 123.1 75.6 129.3 48.4 104.2 98.3 118.5 73.6 126.9 46.6 93.7 93.7 109.9 70.9 122.7 44.3 85.6 85.6 99.3 67.2 116.5 41.9
117.3 117.3 124.1 94.1 130.8 66.9 111.1 111.1 119.0 94.0 128.2 66.8 103.5 103.5 110.8 90.8 123.5 65.3 95.2 95.2 100.8 86.6 116.8 62.5
123.2 123.2 125.6 112.8 132.3 82.9 119.0 119.0 120.8 114.1 129.5 84.5 112.5 112.5 112.5 112.5 124.1 84.2 104.9 104.9 104.8 104.8 117.1 83.0
127.9 127.9 127.9 127.9 133.8 99.2 124.9 124.9 124.9 124.9 130.8 102.4 120.2 120.2 120.2 120.2 125.3 103.1 113.9 113.9 113.8 113.8 118.4 102.9
115.1 108.2 124.5 77.5 130.0 49.2 107.0 104.4 119.8 77.6 127.6 47.4 97.3 97.3 111.7 73.2 123.6 45.2 88.7 88.7 101.1 71.1 117.6 42.7
120.1 120.1 125.3 97.3 131.6 67.9 114.9 114.9 120.6 98.4 129.0 68.2 107.3 107.3 112.9 96.1 124.5 68.1 98.9 98.9 103.1 92.0 118.0 65.1
125.5 125.5 127.0 116.9 133.1 84.7 121.9 121.9 122.8 119.6 130.5 87.0 116.4 116.4 116.3 116.3 125.3 88.0 108.7 108.7 108.7 108.7 118.4 87.0
130.0 130.0 129.7 129.7 134.7 101.8 127.3 127.3 127.2 127.2 131.9 105.9 123.0 123.0 123.0 123.0 126.7 107.5 117.2 117.2 117.2 117.2 120.2 108.4
117.1 113.2 125.5 81.7 130.6 50.0 108.8 108.8 120.8 80.6 128.3 48.2 100.5 100.5 113.2 76.3 124.3 46.1 91.6 91.6 102.7 72.1 118.5 43.6
122.3 122.3 126.5 100.7 132.2 68.9 117.8 117.8 122.0 102.4 129.8 69.5 110.5 110.5 114.9 101.3 125.7 69.3 102.2 102.2 105.2 97.3 119.0 67.7
127.2 127.2 128.4 121.1 133.8 86.3 124.1 124.1 124.1 124.1 131.2 89.2 119.0 119.0 119.0 119.0 126.5 90.9 112.0 112.0 112.0 112.0 119.7 90.9
131.3 131.3 131.5 131.5 135.4 104.2 129.3 129.3 129.0 129.0 132.8 108.9 125.2 125.2 125.2 125.2 127.8 111.4 119.8 119.8 119.8 119.8 121.7 113.3
3600
4000
4400
80
85
90
4800
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC016-EN
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-6 — Belt Drive Evaporator Fan Performance - TSC060AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.12 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Drive
0.49 985 0.54 1023 0.59 1060 0.64
0.58 1028 0.64 1067 0.70 1104 0.76
2720
3060
3400
3740
4080
-
-
703
760
821
885
950
0.27
0.35
0.46
0.60
0.76
757
815
873
930
990
0.31
0.40
0.51
0.65
0.80
806
861
918
977
0.35
0.45
0.57
0.71
854
904
958
1016 0.77
1074 0.93
0.39
0.49
0.62
899
947
998
1053 0.82
1110 1.00
0.43
0.54
0.67
944
988
706
773
840
909
0.32
0.43
0.56
0.71
1036 0.71 1073 0.76 1111 0.82 1147 0.89
1089 0.88
1143 1.06
1124 0.93
1177 1.12
1158 0.98
1209 1.17
1191 1.03
1241 1.23
1034 0.87
External Static Pressure (Pascals)
300 325 350
RPM RPM
275
RPM
375
RPM
CFM
kW
RPM
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Drive
2720
3060
3400
3740
4080
Notes:
1093 0.69
1138 0.82
1182 0.96
1226 1.10
1272 1.29
1126 0.74
1171 0.87
1215 1.02
1258 1.17
1160 0.79
1203 0.93
1246 1.09
1290 1.25
1190 0.84
1232 0.98
1276 1.15
1222 0.90
1262 1.04
1306 1.21
1.12 Nom kW Standard Motor &
Hi Static Drive
←
-
-
-
-
-
-
-
-
-
-
-
-
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Table PD-6a — Belt Drive Evaporator Fan Performance -TSC060AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
1800
2000
2200
2400
-
-
703
760
821
885
950
0.36
0.47
0.62
0.80
1.02
757
815
873
930
990
0.41
0.54
0.69
0.87
1.08
806
861
918
977
0.47
0.60
0.76
0.95
854
904
958
1016 1.03
1074 1.25
0.52
0.66
0.83
899
947
998
1053 1.10
1110 1.34
0.58
0.72
0.90
944
988
0.65
985
0.73 1023 0.79 1060 0.86
706
773
840
909
0.42
0.57
0.75
0.96
0.78 1028 0.86 1067 0.94 1104 1.02
1036 0.96 1073 1.02 1111 1.10 1147 1.19
1089 1.17
1143 1.419 1177 1.50
1124 1.24
1158 1.31
1209 1.57
1191 1.39
1241 1.65
1034 1.16
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
1-1/2 HP Standard Motor & Drive
1600
1800
2000
2200
2400
Notes:
1093 0.92
1138 1.10
1182 1.28
1226 1.48
1272 1.73
1126 0.99
1171 1.17
1215 1.37
1258 1.57
1160 1.06
1203 1.25
1246 1.46
1290 1.67
1190 1.13
1232 1.32
1276 1.54
1222 1.20
1262 1.39
1306 1.62
1-1/2 HP Standard Motor &
Hi Static Drive
←
-
-
-
-
-
-
-
-
-
-
-
-
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
RT-PRC016-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-7 - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
125
RPM
150
RPM
1.12 Nom kW Standard Motor & Drive
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
1.12 Nom kW Std Motor & Low Static Drive
2720
3060
3400
3740
4080
707
778
850
923
997
0.26
0.36
0.48
0.63
0.80
774
840
908
978
0.31
0.41
0.54
0.69
837
897
961
1028 0.76
1096 0.94
0.37
0.48
0.60
898
953
1012 0.67
1075 0.83
1140 1.02
0.43
0.54
953
0.48
1001 0.54
1058 0.67
1111 0.81
1166 0.99
1223 1.18
1045 0.59 1087 0.65 1129 0.71 1168 0.77
1008 0.60
1062 0.74
1120 0.91
1183 1.10
1102 0.73
1157 0.88
1211 1.06
1266 1.27
1143 0.79
1198 0.95
1254 1.14
1181 0.85
1237 1.02
1294 1.22
1219 0.92
1274 1.09
1330 1.29
1049 0.87
-
-
-
-
-
-
1.12 Nom kW Standard Motor & Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM RPM
275
RPM
375
RPM
CFM
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Drive
2720
3060
3400
3740
4080
1206 0.83
1256 0.99
1309 1.16
1241 0.89
1291 1.05
1343 1.24
1275 0.96
1326 1.12
1376 1.31
1306 1.02
1359 1.19
1338 1.09
1390 1.26
1.12 Nom kW Standard Motor &
Hi Static Drive
←
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Table PD-7a - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor &
Low Static Drive
1-1/2 HP Standard Motor & Drive
1600
1800
2000
2200
2400
707
778
850
923
997
0.35
0.48
0.65
0.84
1.07
774
840
908
978
0.42
0.56
0.73
0.93
837
897
961
1028 1.02
1096 1.27
0.50
0.64
0.81
898
953
1012 0.90
1075 1.12
1140 1.37
0.57
0.72
953
0.65
1001 0.72
1058 0.89
1111 1.09
1166 1.32
1223 1.59
1045 0.80 1087 0.87 1129 0.95 1168 1.03
1008 0.81
1062 1.00
1120 1.22
1183 1.48
1102 0.98
1157 1.19
1211 1.43
1266 1.70
1143 1.06
1198 1.28
1254 1.53
1181 1.15
1237 1.37
1294 1.63
1219 1.23
1274 1.47
1330 1.74
1049 1.17
-
-
-
-
-
-
1-1/2 HP Standard Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
1/2 HP Standard Motor & Drive
1-1/2 HP Standard Motor & Hi Static Drive
1600
1800
2000
2200
2400
1206 1.12
1256 1.32
1309 1.56
1241 1.20
1291 1.41
1343 1.66
1275 1.28
1326 1.50
1376 1.76
1306 1.37
1359 1.60
1338 1.46
1390 1.69
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
RT-PRC016-EN
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-8 — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.12 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
1.12 Nom kW Standard Motor & Drive
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
573
602
635
670
706
0.25
0.31
0.38
0.47
0.58
630
656
682
715
749
0.30
0.37
0.45
0.54
0.64
680
706
732
758
789
0.36
0.43
0.51
0.60
0.71
726
751
777
802
830
0.41
0.49
0.58
0.68
0.79
769
792
818
845
870
0.47
0.55
0.64
0.75
0.87
811
832
856
883
909
0.52
0.61
0.71
0.82
0.95
851 0.58
871 0.67
893 0.77
919 0.89
945 1.02
889 0.65
908 0.74
930 0.84
953 0.96
979 1.10
548
584
621
660
0.26
0.33
0.42
0.51
569
612
0.35
0.45
1.12 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM
275
RPM
375
RPM
CFM
kW
RPM
kW
kW
kW
kW
1.12 Nom kW Std Motor
& Drive
1.12 Nom kW Standard Motor
& Hi Static Drive
3260
3670
4080
4490
4890
925
944
964
986
0.71
0.81
0.91
1.04
960
978
998
1019 1.11
1043 1.26
0.77
0.87
0.99
994
0.83
1026 0.89
1043 1.01
1063 1.14
1082 1.27
1103 1.42
1057 0.95
1073 1.08
1092 1.21
1112 1.35
1133 1.51
1010 0.94
1030 1.06
1051 1.19
1073 1.34
1011 1.18
1.50 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Table PD-8a — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor
&
Low Static Drive
1-1/2 HP Standard Motor
&
Drive
0.70
0.81
0.95
1.10
1.27
1920
2160
2400
2640
2880
-
-
-
-
-
-
573
602
635
670
706
0.34
0.42
0.52
0.64
0.78
630
656
682
715
749
0.41
0.50
0.60
0.72
0.86
680
706
732
758
789
0.48
0.58
0.69
0.81
0.96
726
751
777
802
830
0.55
0.65
0.77
0.91
1.06
769
792
818
845
870
0.62
0.73
0.86
1.01
1.16
811
832
856
883
909
851 0.78
871 0.90
893 1.04
919 1.20
945 1.37
889 0.87
908 0.99
930 1.13
953 1.29
979 1.48
548
584
621
660
0.35
0.45
0.56
0.69
-
-
569
612
0.47
0.60
1-1/2 HP Standard Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
1-1/2 HP Standard Mtr
& Drive
1920
2160
2400
2640
2880
925
944
964
986
0.95
1.08
1.22
1.39
960
978
998
1019 1.49
1043 1.69
1.03
1.17
1.32
994
1.11
1026 1.19
1043 1.36
1063 1.53
1082 1.71
1103 1.90
1057 1.27
1073 1.44
1092 1.63
1112 1.81
1133 2.02
1-1/2 HP Standard Motor
Hi Static Drive
&
1010 1.26
1030 1.42
1051 1.60
1073 1.79
←
1011 1.58
2 HP Over-Sized Mtr & Hi Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
RT-PRC016-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
Low Static Drive
125
RPM
150
RPM
1.12 Nom kW Standard Motor
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
&
kW
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor
&
Drive
3260
3670
4080
4490
4890
-
-
565
609
660
710
762
0.23
0.31
0.40
0.51
0.64
627
663
701
745
795
0.29
0.36
0.45
0.56
0.70
679
716
751
788
828
0.34
0.42
0.51
0.62
0.76
726
762
798
833
869
0.39
0.48
0.59
0.69
0.82
771
804
839
875
911
0.45
0.54
0.65
0.77
0.91
814
843
877
914
950
0.51
0.60
0.71
0.85
0.99
857
883
914
949
986
0.57
0.67
0.78
0.91
899 0.63
922 0.74
950 0.85
939 0.70
960 0.81
984 0.93
566
619
672
726
0.26
0.35
0.45
0.58
984 0.98 1016 1.06
1.07 1019 1.14 1051 1.22
1.12 Nom kW Standard Motor
& Hi Static Drive
1.12 Nom kW Standard Motor
&
Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM RPM
275
RPM
375
RPM
CFM
kW
kW
kW
kW
kW
1.12 Nom kW Standard Motor & Hi Static Drive
3260
3670
4080
4490
4890
978
996
1020 1.00
1049 1.14
1081 1.30
0.76
0.87
1015 0.83
1034 0.95
1055 1.08
1081 1.23
1112 1.38
1051 0.90
1069 1.02
1089 1.16
1113 1.31
1141 1.47
1086 0.97
1103 1.09
1122 1.23
1144 1.40
1170 1.57
1118 1.04
1136 1.17
1154 1.31
1176 1.48
1199 1.66
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor
&
Drive
1920
2160
2400
2640
2880
-
-
565
609
660
710
762
0.31
0.41
0.54
0.68
0.86
627
663
701
745
795
0.39
0.48
0.60
0.76
0.94
679
716
751
788
828
0.45
0.57
0.69
0.83
1.02
726
762
798
833
869
0.52
0.64
0.78
0.93
1.11
771
804
839
875
911
0.60
0.72
0.87
1.04
1.21
814
843
877
914
950
0.69
857
883
914
949
986
0.77
0.90
1.04
1.22
899 0.85
922 0.99
950 1.14
939 0.93
960 1.08
984 1.24
566
619
672
726
0.35
0.47
0.61
0.77
0.80
0.95
1.13
1.33
984 1.31 1016 1.42
1.44 1019 1.53 1051 1.63
1-1/2 HP Standard Motor
&
Drive
1-1/2 HP Std Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
1-1/2 HP Standard Motor
&
Hi Static Drive
1920
2160
2400
2640
2880
978
996
1020 1.35
1049 1.53
1081 1.74
1.02
1.17
1015 1.11
1034 1.27
1055 1.45
1081 1.65
1112 1.86
1051 1.20
1069 1.36
1089 1.55
1113 1.76
1141 1.97
1086 1.30
1103 1.46
1122 1.66
1144 1.87
1170 2.10
1118 1.39
1136 1.56
1154 1.76
1176 1.98
1199 2.22
2 HP Over-Sized Motor
&
High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
RT-PRC016-EN
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-10 — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.50 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
1.50 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
-
-
-
-
-
701
743
789
836
885
0.47
0.59
0.74
0.92
1.14
750
787
827
873
921
0.54
0.66
0.82
1.00
1.22
794
830
867
908
954
0.60
0.74
0.90
1.08
1.30
834
871
906
944
986
0.67
0.82
0.98
1.17
873
908
944
980
0.73
0.89
1.06
1.26
909 0.80
943 0.96
980 1.15 1013 1.23
1016 1.35 1050 1.45
945 0.87
977 1.04
699
747
797
848
0.53
0.68
0.85
1.06
703
755
809
0.61
0.77
0.96
713
771
0.69
0.88
1.39 1019 1.49 1052 1.58 1085 1.69
1.50 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM
275
RPM
375
RPM
CFM
kW
RPM
kW
kW
kW
kW
1.50 Nom kW Std Motor
& Drive
1.50 Nom kW Standard Motor
& Hi Static Drive
4080
4590
5100
5610
6120
980
0.95
1013 1.02
1043 1.19
1076 1.39
1111 1.63
1148 1.89
1046 1.10
1074 1.27
1105 1.47
1141 1.72
1177 1.99
1076 1.17
1105 1.36
1134 1.56
1168 1.80
1204 2.08
1106 1.25
1134 1.44
1163 1.65
1197 1.90
1232 2.18
1010 1.11
1045 1.31
1081 1.54
1116 1.79
2.24 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-10a — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
.80
.90
1.00
CFM
RPM BHP
2 HP Standard Motor
RPM BHP
RPM BHP
Low Static Drive
RPM BHP
RPM BHP
RPM BHP
2 HP Standard Motor
&
&
2400
2700
3000
3300
3600
-
-
-
-
-
-
-
-
-
-
-
-
701
743
789
836
885
0.63
0.79
0.99
1.24
1.53
750
787
827
873
921
0.72
0.89
1.10
1.34
1.63
794
830
867
908
954
0.81
0.99
1.20
1.45
1.74
834
871
906
944
986
0.90
1.09
1.31
1.57
873
908
944
980
0.98
1.19
1.43
1.69
909 1.08
943 1.29
980 1.54
1016 1.82
945 1.17
977 1.39
1013 1.65
1050 1.94
699
747
797
848
0.70
0.91
1.15
1.42
703
755
809
0.81
1.03
1.29
713
771
0.93
1.19
1.87 1019 1.99 1052 2.13 1085 2.26
2 HP Standard Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
CFM
2 HP Standard Mtr
& Drive
2 HP Standard Motor &
Hi Static Drive
2400
2700
3000
3300
3600
980
1.27
1010 1.49
1045 1.76
1081 2.06
1116 2.39
1013 1.37
1046 1.47
1076 1.57
1105 1.82
1134 2.09
1168 2.42
1204 2.79
1106 1.68
1043 1.60
1076 1.87
1111 2.18
1148 2.53
1074 1.71
1105 1.98
1141 2.30
1177 2.66
1134 1.93
1163 2.21
1197 2.55
1232 2.93
3 HP Over-Sized Mtr & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
RT-PRC016-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
125
RPM
150
RPM
1.50 Nom kW Standard Motor
175
RPM
200
RPM
Drive
225
RPM kW
250
RPM kW
m3/h
1.50 Nom kW Std Motor & Low Static Drive
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
4080
4590
5100
5610
6120
-
-
673
738
805
873
942
0.42
0.56
0.74
0.96
1.22
718
773
837
903
970
0.47
0.62
0.81
1.03
1.30
769
817
870
930
996
0.54
0.68
0.87
1.10
1.37
814
862
912
963
0.61
0.76
0.94
1.17
855
904
951
1000 1.25
1052 1.52
0.67
0.85
1.03
893
941
989
0.73
0.92
929
975
0.81
0.98
965 0.88
1009 1.06
999 0.96
1041 1.14
702
771
842
913
0.51
0.68
0.89
1.14
1.12 1025 1.21 1056 1.28 1088 1.36
1037 1.34 1073 1.45 1106 1.55 1136 1.63
1086 1.61 1121 1.71 1153 1.82 1184 1.93
1021 1.45
1.50 Nom kW Standard Motor
&
Drive
1.50 Nom kW Standard Motor &
Hi Static Drive
2.24 Nom kW OS
Motor & Hi Static Drive
External Static Pressure (Pascals)
300 325 350
RPM RPM RPM
1.50 Nom kW Standard Motor & Hi Static Drive
275
RPM
375
RPM kW
CFM
kW
kW
kW
kW
4080
4590
5100
5610
6120
1035 1.04
1073 1.22
1117 1.44
1165 1.72
1215 2.04
1070 1.12
1104 1.31
1146 1.53
1194 1.80
1242 2.13
1104 1.19
1136 1.40
1176 1.62
1220 1.88
1269 2.22
1137 1.27
1167 1.48
1205 1.72
1248 1.98
1295 2.31
1168 1.35
1198 1.57
1233 1.82
1275 2.08
1319 2.40
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
2 HP Std Motor & Low Static Drive
2 HP Standard Motor
&
2400
2700
3000
3300
3600
-
-
673
738
805
873
942
0.56
0.76
1.00
1.29
1.63
718
773
837
903
970
0.63
0.83
1.08
1.38
1.74
769
817
870
930
996
0.72
0.92
1.17
1.47
1.84
814
862
912
963
0.82
1.02
1.26
1.57
855
904
951
1000 1.68
1052 2.04
0.90
1.13
1.38
893
941
989
0.98
1.23
929
975
1.08
965 1.18
999 1.29
702
771
842
913
0.68
0.91
1.19
1.53
1.32 1009 1.42 1041 1.52
1.51 1025 1.62 1056 1.72 1088 1.82
1037 1.80 1073 1.94 1106 2.08 1136 2.19
1086 2.16 1121 2.29 1153 2.44 1184 2.59
1021 1.94
2 HP Standard Motor
&
Drive
2 HP Std Motor & Hi Static Drive
3 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
2 HP Standard Motor
&
Hi Static Drive
2400
2700
3000
3300
3600
1035 1.39
1073 1.64
1117 1.93
1165 2.30
1215 2.73
1070 1.50
1104 1.76
1146 2.05
1194 2.41
1242 2.86
1104 1.60
1136 1.87
1176 2.17
1220 2.52
1269 2.98
1137 1.70
1167 1.99
1205 2.31
1248 2.66
1295 3.10
1168 1.81
1198 2.11
1233 2.44
1275 2.79
1319 3.22
3 HP Over-Sized Motor
&
High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Com m ercial Equipm ent, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Prem ature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
RT-PRC016-EN
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-12 — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
1.50 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
1.50 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
4620
5200
5780
6350
6930
-
-
-
-
-
-
-
-
-
-
-
-
613
650
689
729
770
0.45
0.55
0.68
0.82
0.98
655
688
724
764
804
0.54
0.64
0.76
0.92
1.09
695
725
759
795
834
0.62
0.73
0.86
1.01
1.19
733
761
792
826
864
0.71
0.83
0.96
1.11
1.30
769
796
825
857
892
0.81
0.93
1.07
1.22
1.40
802 0.90
828 1.03
856 1.18
887 1.34
920 1.52
833 1.00
861 1.13
887 1.28
916 1.46
948 1.64
611
651
693
738
0.48
0.59
0.72
0.89
612
659
706
0.51
0.64
0.80
622
671
0.56
0.71
1.50 Nom kW Standard
Motor & Hi Static Drive
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
1.50 Nom kW Std Mtr & Drive
1.50 Nom kW Std Mtr & Hi Static Dr
4620
5200
5780
6350
6930
863
891
917
945
976
1.11
1.24
1.40
1.58
1.78
892
919
946
974
1.21
1.35
1.51
1.70
920
946
974
1001 1.82
1029 2.04
1.33
1.46
1.63
946
973
1001 1.75
1028 1.95
1055 2.17
1.44
1.58
973
999
1026 1.88
1054 2.08
1081 2.30
1.55
1.71
999
1.67
1025 1.79 1050 1.90 1073 2.02 1098 2.14
1048 1.96 1072 2.09 1096 2.22 1119 2.34
1074 2.14 1099 2.27 1121 2.41 1143 2.55
1103 2.34 1126 2.48 1148 2.62 1170 2.76
1130 2.58 1154 2.72 1176 2.85 1199 3.01
1024 1.83
1051 2.01
1079 2.20
1105 2.43
1002 1.91
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-12a — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
769
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
2 HP Standard Motor
&
Low Static Drive
2 HP Standard Motor
&
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
613
650
689
729
770
0.60
0.74
0.91
1.10
1.32
655
688
724
764
804
0.72
0.85
1.02
1.23
1.46
695
725
759
795
834
0.84
0.98
1.15
1.35
1.60
733
761
792
826
864
0.95
1.11
1.29
1.49
1.74
1.08
1.25
1.43
1.64
1.88
802 1.21
828 1.38
856 1.58
887 1.79
920 2.04
833 1.34
861 1.52
887 1.72
916 1.96
948 2.20
611
651
693
738
0.64
0.79
0.97
1.19
796
825
857
892
612
659
706
0.68
0.86
1.08
622
671
0.76
0.96
2 HP Standard Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
2 HP Standard Mtr & Drive
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
1.60
RPM BHP
1.70
1.80
1.90
2.00
CFM
RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Hi Static Drive
2720
3060
3400
3740
4080
863
891
917
945
976
1.48
1.66
1.87
2.11
2.38
892
919
946
974
1.63
1.81
2.03
2.28
920
946
974
1001 2.44
1029 2.73
1.78
1.96
2.18
946
973
1001 2.34
1028 2.61
1055 2.91
1.93
2.12
973
999
1026 2.52
1054 2.78
1081 3.09
2.08
2.29
999
2.24
1025 2.39 1050 2.55 1073 2.71 1098 2.88
1048 2.63 1072 2.80 1096 2.98 1119 3.14
1074 2.86 1099 3.05 1121 3.23 1143 3.41
1103 3.14 1126 3.32 1148 3.51 1170 3.71
1130 3.45 1154 3.65 1176 3.83 1199 4.03
1024 2.46
1051 2.69
1079 2.96
1105 3.26
1002 2.56
3 HP Over-Sized Motor & Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-13 — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
125
RPM
150
RPM
175
RPM
1.50 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
1.50 Nom kW Std Mtr & Low Static Drive
&
Drive
4620
5200
5780
6350
6930
-
-
-
-
646
693
743
799
857
0.50
0.64
0.82
1.04
1.31
689
735
781
830
883
0.58
0.73
0.91
1.12
1.39
734
773
819
865
913
0.67
0.82
1.01
1.23
1.48
781
812
853
899
945
0.77
0.92
1.11
1.34
1.60
826
855
886
930
977
0.88
1.03
1.21
1.45
865
897
925
960
0.98
1.15
1.34
1.56
898 1.07
934 1.27
964 1.47 1000 1.60
994 1.68 1028 1.82
928 1.16
969 1.38
616
675
735
796
0.51
0.68
0.89
1.14
654
711
770
828
0.57
0.75
0.97
1.23
1.72 1006 1.84 1034 1.96 1061 2.08
1.50 Nom kW Std Mtr
& High Static Drive
2.24 Nom kW Over-Sized
Motor & High Static Drive
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
1.50 Nom kW Standard Motor & High Static Drive
4620
5200
5780
6350
6930
956
999
1034 1.73
1063 1.96
1093 2.23
1.25
1.49
982
1.33
1008 1.42
1052 1.68
1094 1.97
1129 2.26
1157 2.53
1033 1.51
1078 1.78
1120 2.08
1158 2.40
1188 2.70
1056 1.60
1101 1.88
1145 2.20
1185 2.53
1218 2.86
1079 1.69
1124 1.98
1168 2.31
1210 2.66
1245 3.01
1102 1.78 1125 1.87 1146 1.95 1168 2.04
1146 2.08 1168 2.18 1188 2.27 1209 2.37
1191 2.42 1213 2.53 1234 2.63 1254 2.74
1234 2.78 1256 2.90 1278 3.03 1299 3.15
1026 1.58
1067 1.86
1098 2.11
1125 2.38
1273 3.16 1297 3.31
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-13a — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Mtr & Low Static Drive
2 HP Standard Motor
&
Drive
2720
3060
3400
3740
4080
-
-
-
-
646
693
743
799
857
0.67
0.86
1.10
1.40
1.76
689
735
781
830
883
0.78
0.98
1.22
1.51
1.86
734
773
819
865
913
0.90
1.10
1.36
1.65
1.99
781
812
853
899
945
1.04
1.23
1.49
1.79
2.15
826
855
886
930
1.18
1.39
1.62
1.94
865
897
925
960
1.31
1.55
1.79
2.09
898 1.44
934 1.70
964 1.97 1000 2.14
994 2.26 1028 2.44
928 1.56
969 1.85
616
675
735
796
0.69
0.92
1.20
1.53
654
711
770
828
0.77
1.01
1.30
1.65
977
2.30 1006 2.47 1034 2.63 1061 2.79
3 HP Over-Sized Mtr & Drive
2 HP Std Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
2 HP Standard Motor
1.20
RPM BHP
1.30
RPM BHP
High Static Drive
1.40
RPM BHP
1.50
RPM BHP
1.60
RPM BHP
1.70
RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Over-Sized Motor Drive
1102 2.38 1125 2.5 1146 2.62 1168 2.74
1146 2.79 1168 2.92 1188 3.05 1209 3.18
1191 3.24 1213 3.39 1234 3.53 1254 3.68
1234 3.73 1256 3.89 1278 4.06 1299 4.23
1.80
1.90
2.00
CFM
&
&
2720
3060
3400
3740
4080
956
999
1.67
1.99
982
1.79
1008 1.91
1052 2.26
1094 2.64
1129 3.03
1157 3.40
1033 2.03
1078 2.39
1120 2.79
1158 3.21
1188 3.62
1056 2.14
1101 2.52
1145 2.94
1185 3.39
1218 3.83
1079 2.26
1124 2.66
1168 3.09
1210 3.56
1245 4.03
1026 2.12
1067 2.49
1098 2.84
1125 3.19
1034 2.32
1063 2.63
1093 2.99
1273 4.24 1297 4.44
-
-
-
-
3 HP Over-Sized Motor
&
Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-14 — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
2.24 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
2.24 Nom kW Standard Motor
&
Drive
5440
6120
6800
7480
8160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
718
764
814
864
916
0.72
0.90
1.11
1.36
1.64
754
797
844
894
945
0.82
0.99
1.21
1.48
1.77
789
829
874
922
972
0.93
1.10
1.32
1.59
1.90
822
860
903
948
997
1.03
1.22
1.44
1.70
856 1.14
892 1.34
932 1.56
887 1.25
922 1.46
960 1.69
731
782
834
887
0.81
1.01
1.24
1.52
715
773
833
0.81
1.04
1.31
747
803
861
0.90
1.14
1.42
741
803
0.95
1.21
975 1.82 1001 1.95
2.02 1022 2.14 1046 2.27
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
2.24 Nom kW Standard Motor & Drive
5440
6120
6800
7480
8160
917
951
988
1028 2.09
1071 2.41
1.36
1.57
1.82
945
979
1015 1.95
1053 2.23
1095 2.55
1.47
1.69
973
1.60
999
1.72
1024 1.84
1059 2.07
1093 2.35
1128 2.66
1166 3.02
1048 1.97
1082 2.20
1117 2.48
1152 2.81
1189 3.17
1072 2.10
1107 2.34
1142 2.63
1176 2.95
1212 3.33
1095 2.23
1130 2.49
1164 2.76
1198 3.10
1117 2.37
1152 2.63
1187 2.91
1221 3.25
1140 3.36
1173 3.71
1209 4.11
1007 1.82
1042 2.08
1078 2.38
1119 2.70
1033 1.94
1068 2.21
1103 2.52
1142 2.86
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-14a — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor Drive
.80
.90
1.00
CFM
RPM BHP
RPM BHP
3 HP Standard Motor
RPM BHP
RPM BHP
Low Static Drive
RPM BHP
RPM BHP
&
&
3200
3600
4000
4400
4800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
718
764
814
864
916
0.97
1.20
1.49
1.82
2.20
754
797
844
894
945
1.10
1.33
1.63
1.98
2.38
789
829
874
922
972
1.25
1.48
1.77
2.13
2.55
822
860
903
948
997
1.38
1.63
1.93
2.28
856 1.53
892 1.79
932 2.09
887 1.67
922 1.95
960 2.27
731
782
834
887
1.08
1.35
1.67
2.04
715
773
833
1.09
1.40
1.76
747
803
861
1.21
1.53
1.90
741
803
1.27
1.62
975 2.44 1001 2.62
2.71 1022 2.87 1046 3.04
External Static Pressure (Inches of Water)
1.10
RPM BHP
1.20
RPM BHP
3 HP Standard Motor & Drive
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
1.60
RPM BHP
1.70
1.80
1.90
2.00
CFM
RPM BHP RPM BHP RPM BHP RPM BHP
3200
3600
4000
4400
4800
917
951
988
1028 2.81
1071 3.23
1.82
2.11
2.44
945
979
1015 2.62
1053 3.00
1095 3.42
1.97
2.27
973
2.14
999
2.30
1024 2.47
1059 2.78
1093 3.15
1128 3.57
1166 4.04
1048 2.65
1082 2.95
1117 3.33
1152 3.77
1189 4.25
1072 2.82 1095 3.00 1117 3.17 1140 3.36
1107 3.14 1130 3.33 1152 3.52 1173 3.71
1142 3.52 1164 3.70 1187 3.91 1209 4.11
1007 2.43
1042 2.79
1078 3.19
1119 3.62
1033 2.60
1068 2.97
1103 3.38
1142 3.83
1176 3.96 1198 4.15 1221 4.36
1212 4.46
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-15 — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
RPM
2.24 Nom kW Standard Motor & Low Static Drive
125
RPM
150
RPM
175
RPM
2.24 Nom kW Standard Motor
200
RPM
225
RPM kW
250
RPM kW
m3/h
RPM
kW
RPM
kW
RPM
kW
kW
kW
kW
kW
kW
&
Drive
1.28 965 1.41 1000 1.53
1.53 1002 1.67 1038 1.81
5440
6120
6800
7480
8160
-
-
691
761
833
905
977
0.67
0.91
1.22
1.58
2.02
730
792
860
931
0.75
0.99
1.29
1.67
771
829
890
955
0.84
1.08
1.38
1.75
807
865
923
983
0.94
1.19
1.50
1.86
844
898
956
1014 1.99
1074 2.42
1.04
1.30
1.62
886
930
986
1.16
1.41
926
965
729
802
876
950
0.84
1.13
1.49
1.91
1.73 1015 1.85 1044 1.98 1077 2.12
1045 2.12 1072 2.25 1098 2.37 1125 2.51
1102 2.56 1131 2.71 1156 2.84 1181 2.98
1002 2.11
1025 2.20
1048 2.30
2.24 Nom kW Standard Motor & High Static Drive
External Static Pressure (Pascals)
375 400
RPM RPM
275
RPM
300
RPM
325
RPM
350
RPM
425
RPM
450
RPM
475
RPM kW
500
RPM kW
m3/h
kW
kW
kW
kW
kW
kW
kW
kW
2.24 Nom kW Std Mtr & Drive
5440
6120
6800
7480
8160
1029 1.64
1072 1.95
1111 2.28
1152 2.65
1205 3.12
1057 1.75
1106 2.10
1143 2.43
1182 2.81
1229 3.27
1084 1.86
1134 2.22
1174 2.58
1211 2.97
1108 1.96
1160 2.35
1204 2.74
1241 3.14
1132 2.06
1185 2.47
1232 2.90
1270 3.31
1155 2.17
1209 2.59
1260 3.05
1177 2.27 1198 2.37 1219 2.48 1239 3.46
1231 2.70 1252 2.82 1274 2.94 1295 4.10
1283 3.18 1306 3.32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-15a — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
RPM BHP RPM BHP RPM BHP RPM BHP
Drive
926
965
.80
.90
1.00
CFM
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
RPM BHP
3 HP Standard Motor & Low Static Drive
3 HP Standard Motor
&
3200
3600
4000
4400
4800
-
-
691
761
833
905
977
0.89
1.22
1.63
2.12
2.70
730
792
860
931
1.00
1.32
1.73
2.24
771
829
890
955
1.13
1.45
1.86
2.35
807
865
923
983
1.26
1.60
2.01
2.49
844
898
956
1.39
1.74
2.17
886
930
986
1.55
1.89
1.72
965 1.89 1000 2.06
2.06 1002 2.24 1038 2.43
729
802
876
950
1.13
1.52
1.99
2.56
2.32 1015 2.48 1044 2.65 1077 2.85
1045 2.84 1072 3.01 1098 3.18 1125 3.36
1014 2.66
1074 3.24
1002 2.84
1025 2.96
1048 3.08
1102 3.43
1131 3.63
1156 3.81
1181 4.00
3 HP Standard Motor
&
High Static Drive
External Static Pressure (Inches of Water)
1.10
RPM BHP
3 HP Std Mtr & Drive
1.20
RPM BHP
1.30
RPM BHP
1.40
RPM BHP
1.50
RPM BHP
1.60
RPM BHP
1.70
1.80
1.90
2.00
CFM
RPM BHP RPM BHP RPM BHP RPM BHP
3200
3600
4000
4400
4800
1029 2.20
1072 2.62
1111 3.05
1152 3.55
1205 4.19
1057 2.35
1084 2.49
1134 2.98
1174 3.47
1211 3.99
1108 2.63
1160 3.15
1204 3.68
1241 4.21
1132 2.77
1185 3.31
1232 3.88
1270 4.44
1155 2.91
1209 3.47
1260 4.09
1177 3.05 1198 3.18 1219 3.32 1239 3.46
1231 3.63 1252 3.78 1274 3.94 1295 4.10
1106 2.81
1143 3.26
1182 3.76
1229 4.39
1283 4.27 1306 4.46
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor
&
High Static Drive
Notes:
Factory Supplied Motors, In Com m ercial Equipm ent, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Prem ature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-16 — Standard Motor & Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
N/A
N/A
5 Turns
Open
898
698
752
4 Turns
Open
967
751
806
3 Turns
Open
1036
806
860
786
2 Turns
Open
1105
859
914
835
1 Turns
Open
1174
913
968
885
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1243
967
1020
934
N/A
N/A
688
782
737
838
894
950
1006
1062
Factory set at 3 turns open
Table PD-17 — Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
N/A
N/A
5 Turns
Open
691
537
671
4 Turns
Open
760
590
714
3 Turns
Open
829
644
757
2 Turns
Open
898
698
800
1 Turns
Open
967
752
843
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1036
806
886
811
N/A
N/A
629
717
664
754
701
799
737
844
773
885
922
Factory set at 3 turns open
Table PD-18 — Standard Motor & High Static Drive Accessory Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
N/A
1020
936
5 Turns
Open
1243
967
1073
981
4 Turns
Open
1311
1021
1127
1032
1174
3 Turns
Open
1379
1075
1181
1083
1229
2 Turns
Open
1450
1128
1235
1134
1285
1 Turns
Open
1515
1183
1289
1182
1341
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1588
1235
N/A
N/A
N/A
1062
1118
Factory set at 3 turns open
Table PD-19 — Oversized Motor & Drive Sheave/Fan Speed (RPM)
Unit
6 Turns
Open
N/A
1112
N/A
5 Turns
Open
967
1182
971
4 Turns
Open
1021
1252
1041
N/A
3 Turns
Open
1075
1322
1111
N/A
2 Turns
Open
1128
1392
1181
N/A
1 Turns
Open
1183
1460
1251
N/A
Model No.
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Closed
1235
N/A
1321
N/A
N/A
N/A
Factory set at 3 turns open
Table PD-20 — Sound Power Level - dB (ref. 10 -12 Watts)
Unit
Octave Center Frequency
Overall
dBA
80
85
85
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Note:
63
84
83
83
83
83
125
91
90
90
89
86
250
79
86
86
84
80
500
77
82
83
81
77
1000
74
79
80
77
2000
71
4000
8000
63
63
64
62
68
70
71
69
66
75
75
72
69
83
79
73
60
Tests follow ARI 270-95
RT-PRC016-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-21 — Static Pressure Drops Through Accessories - (Pascals)
Economizer
Electric Heater
OA/RA Dampers2
Accessory (kW)3
Unit
Model No.
TSC060AD
Airflow
(m3/h)
2720
3400
4080
3260
4080
4890
4080
5100
6120
4620
5780
6930
5440
6800
8160
Standard Pleated Filters
100% OA
100% RA
100% OA
100% RA
Filters1
25
(50 mm)
37
Downflow
Horizontal
9
11
17
25
-
13-27
13
21
30
5
40
-
-
-
-
30
46
64
25
27
33
27
35
52
31
47
75
42
65
85
11
17
26
2
5
10
5
12
17
7
15
17
12
17
22
30
46
64
15
20
25
20
30
62
22
45
77
35
75
87
4
6
9
5
5
37
55
55
72
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Notes:
10
17
15
22
-
8
-
22
30
10
5
-
-
13
8
-
-
15
22
25
32
12
20
10
15
22
12
20
25
-
-
-
16
25
6
-
-
-
35
45
12
20
20
27
-
-
-
-
10
15
9
14
20
-
-
10
17
26
30
40
17
25
27
37
40
50
-
1. Tested with standard filters. The TSC060AD has 25 m m (1 inch) standard fiters. The TSC072AD - 120AD has 50 m m (2 inch) standard filters.
The difference in pressure drop should be considered when utilizing optional 50 m m (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nom inal kW ratings at 415 V
Table PD-21a — Static Pressure Drops Through Accessories - (Inches of Water Column)
Economizer
Electric Heater
OA/RA Dampers2
Accessory (kW)3
Unit
Model No.
TSC060AD
Airflow
(CFM)
1600
2000
2400
1920
2400
2880
2400
3000
3600
2720
3400
4080
3200
4000
4800
Standard Pleated Filters
100% OA
100% RA
100% OA
100% RA
Filters1
0.10
0.15
0.22
0.04
0.06
0.09
0.06
0.10
0.14
0.05
0.08
0.12
0.07
0.11
0.16
(2 inch)
0.15
0.22
0.29
0.07
0.09
0.12
0.09
0.13
0.18
0.08
0.11
0.16
0.10
0.15
0.20
Downflow
Horizontal
9
13-27
0.053
0.083
0.120
0.021
0.034
0.052
0.034
0.063
0.102
0.026
0.041
0.059
0.036
0.056
0.081
40
-
-
-
-
-
-
-
-
-
-
-
0.12
0.18
0.26
0.10
0.11
0.13
0.11
0.14
0.21
0.12
0.19
0.30
0.17
0.26
0.34
0.04
0.07
0.10
0.01
0.02
0.04
0.02
0.05
0.07
0.03
0.06
0.07
0.05
0.07
0.09
0.12
0.18
0.26
0.06
0.08
0.10
0.08
0.12
0.25
0.09
0.18
0.31
0.14
0.30
0.35
0.01
0.02
0.04
0.02
0.02
0.04
0.02
0.05
0.08
0.04
0.06
0.09
0.05
0.08
0.10
0.045
0.070
0.100
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Notes:
-
-
-
-
-
-
-
-
-
-
-
-
-
0.042
0.070
0.106
1. Tested with standard filters. The TSC060AD has 25 m m (1 inch) standard fiters. The TSC072AD - 120AD has 50 m m (2 inch) standard filters.
The difference in pressure drop should be considered when utilizing optional 50 m m (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nom inal kW ratings at 415 V
Table PD-22 - Electric Heater Voltage Correction Factors (Apply to Auxiliary Electric Heat
Capacity)
Nominal
Voltage
Distribution
Voltage
380
Capacity
Multipiler
0.84
415
400
0.93
415
1.00
RT-PRC016-EN
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-23 — Auxiliary Electric Heat Capacity (SI)
Total2
Stage 1
Stage 2
Unit
Unit
Model No.
Voltage
KW
No. Stages
KW
KW
7.5 / 9.0
2
2
2
1
2
2
1
2
2
2
2
2
2
2
3.75 / 4.5
5.45 / 6.5
3.75 / 4.5
5.45 / 6.5
5.45 / 6.5
—-
5.6 / 6.7
11.3 / 13.5
—-
5.6 / 6.7
11.3 / 13.5
5.6 / 6.7
11.3 / 13.5
5.6 / 6.7
11.3 / 13.5
22.5 / 26.9
TSC060AD
TSC072AD
380-415/50/3
380-415/50/3
10.9 / 13.0
14.4 / 17.2
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
33.9 / 40.4
8.95 / 10.7
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.5
11.3 / 13.6
11.3 / 13.7
11.3 / 13.8
11.3 / 13.9
11.3 / 13.10
TSC090AD
TSC102AD
380-415/50/3
380-415/50/3
TSC120AD
380-415/50/3
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 380V / 415V. For other than rated voltage, CAP=(Voltage/Rated Voltage)2 x Rated Cap.
Table PD-23A — Auxiliary Electric Heat Capacity (IP)
Total2
Stage 1
Stage 2
Unit
Unit
Model No.
Voltage
MBH
26 / 31
38 / 45
50 / 59
39 / 47
58 / 69
78 / 92
39 / 47
58 / 69
78 / 92
58 / 69
78 / 92
58 / 69
78 / 92
116 / 138
No. Stages
MBH
13 / 16
19 / 23
31 / 37
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
39 / 47
MBH
13 / 16
19 / 23
19 / 23
—-
20 / 23
39 / 47
—-
20 / 23
39 / 47
20 / 23
39 / 47
20 / 23
39 / 47
77 / 92
2
2
2
1
2
2
1
2
2
2
2
2
2
2
TSC060AD
TSC072AD
380-415/50/3
380-415/50/3
TSC090AD
TSC102AD
380-415/50/3
380-415/50/3
TSC120AD
380-415/50/3
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 380 / 415V. For other than rated voltage, CAP=(Voltage/Rated Voltage)2 x Rated Cap.
RT-PRC016-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Perform ance
Data
Table PD-24 — Air Temperature Rise Across Electric Heaters (Degrees C)
kW
3400 m3/h
TSC060AD
6.6 / 7.9
9.6 / 11.4
—-
4100 m3/h
TSC072AD
—-
—-
8.3 / 9.9
—-
12.4 / 14.8
16.5 / 19.7
—-
5100 m3/h
TSC090AD
—-
—-
6.6 / 7.9
—-
9.9 / 11.8
13.2 / 15.7
—-
5800 m3/h
TSC102AD
—-
6800 m3/h
TSC120AD
—-
380V / 415V
07.5 / 09.0
10.9 / 13.0
11.3 / 13.5
14.4 / 17.2
16.9 / 20.2
22.6 / 26.9
33.8 / 40.4
Voltage
Stages
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
2
2
1
2
2
2
2
—-
—-
—-
—-
—-
—-
12.6 / 15.1
—-
8.7 / 10.4
11.7 / 13.9
—-
7.4 / 8.9
9.9 / 11.8
14.8 / 17.7
—-
—-
Note:
For m inim um design airflow, see perform ance table for each unit.
To calculate tem p rise at differrent airflow, use following form ula:
Tem p. Rise (C0) across Elect Htr = (kW x 2985)/( m 3/h)
Table PD-24A — Air Temperature Rise Across Electric Heaters (Degrees F)
kW
2000 CFM
TSC060AD
11.9 / 14.2
17.2 / 20.5
—-
2400 CFM
TSC072AD
—-
—-
14.9 / 17.8
—-
22.3 / 26.6
29.8 / 35.4
—-
3000 CFM
TSC090AD
—-
—-
11.9 / 14.2
—-
17.8 / 21.3
23.8 / 28.3
—-
3400 CFM
TSC102AD
—-
4000 CFM
TSC120AD
—-
380V / 415V
07.5 / 09.0
10.9 / 13.0
11.3 / 13.5
14.4 / 17.2
16.9 / 20.2
22.6 / 26.9
33.8 / 40.4
Voltage
Stages
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
2
2
1
2
2
2
2
—-
—-
—-
—-
—-
—-
22.8 / 27.2
—-
15.7 / 18.8
21.0 / 25.0
—-
13.4 / 16.0
17.9 / 21.3
26.7 / 31.9
—-
—-
Note:
For m inim um design airflow, see perform ance table for each unit.
To calculate tem p rise at differrent airflow, use following form ula:
Tem p. Rise (F0) across Elect Htr = (kW x 3414)/(1.08 x CFM)
RT-PRC016-EN
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Zone Controls
Non-programmable manual auto
changeover with digital LCD Display —
Auto, heat, cool or off mode selection
button. Auto or off fan bottom. Status
indication LCD indicators — System on,
heat, cool, or service.
Zone Sensors
Conventional Thermostats
Zone Sensors are the building
occupant’s comfort control devices for
Precedent™ units with the ReliaTel
control. The zone sensor offering
operates with the Reliatel
Conventional Thermostats are the
building occupant’s comfort control
devises when a generic thermostat is
desired.
Manual
microprocessor
Changeover —
One Heat, One
Cool Thermostat.
Heat, Cool or Off
System Switch.
Fan Auto or On
Switch. Set Point
Dial. Adjustable
Heat Anticipator.
Manual Changeover — Heat, Cool or Off
System Switch. Fan Auto or Off Switch.
One
temperature
setpoint lever.
Automatic Changeover — One Heat,
Two Cool Thermostat. Off, Auto System
Switch. Auto/On Fan Switch.
Programmable Night Setback — Auto
or manual changeover with seven-day
programming. Keyboard selection of
Heat, Cool, Fan, Auto, or On.
Manual/Automatic Changeover —Auto,
Heat, Cool or Off System Switch. Fan
Auto or Off
All programmable sensors have
Switch. Two
temperature
setpoint
levers. Optional
Status Indication
LED lights,
System On,
Heat, Cool, or
Programmable Electronic Night Setback
Thermostat — Heating setback and
cooling setup with 7-day, programming
capability. Available in two-stage
heating/cooling or one-stage heating/
cooling versions with automatic
changeover.
Service.
System On, Heat, Cool, Service LED/
indicators as standard. Night Setback
Sensors have one (1) Occupied, one (1)
Unoccuped, and two (2) Override
programs per day.
Integrated Comfort™ System —
Sensor(s) available with optional
temperature
Remote Sensor — Sensor(s) available
for all zone sensors to provide
remote sensing
capabilities.
adjustment and
override buttons
to provide
central control
through a Trane
Integrated
Comfort™
system.
RT-PRC016-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-1 — Unit Wiring
Standard Indoor Fan Motor
Oversized Indoor Fan Motor
Unit
Minimum
Maximum Fuse
Minimum
Maximum Fuse
Unit
Operating
Voltage Range
342-456
Circuit
Ampacitiy
17.7
23.2
24.8
Size Or Maximum
Circuit
Ampacitiy
17.7
24.2
26.5
Size Or Maximum
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Circuit Breaker1
Circuit Breaker1
25
35
35
35
40
25
35
35
35
40
342-456
342-456
342-456
342-456
26.8
31.2
28.5
31.2
Notes:
1. All units to be installed under local codes
Table ED-2 — Unit Wiring With Electric Heat Single Point Connection — 380-415 Volts
Standard Indoor Fan Motor
Oversized Indoor Fan Motor
Minimum
Circuit
Maximum Fuse
Minimum
Circuit
Maximum Fuse
Size Or Maximum
Circuit Breaker1
25 / 25
Unit
Model No.
TSC060AD
Heater
Model No.
Heater2
MBH
Control
Stages
Size Or Maximum
Circuit Breaker1
25 / 25
kW Rating
7.5 / 9.0
Ampacitiy
19.8 / 21.0
26.1 / 28.0
32.8 / 35.3
26.9 / 28.9
37.5 / 40.5
48.3 / 52.1
28.1 / 30.1
38.8 / 41.8
49.5 / 53.4
38.8 / 41.8
49.5 / 53.4
40.9 / 43.9
51.6 / 55.5
73.1 / 79.0
Ampacitiy
19.8 / 21.0
26.1 / 28.0
32.8 / 35.3
28.1 / 30.1
38.8 / 41.8
49.5 / 53.4
30.3 / 32.3
40.9 / 43.9
51.6 / 55.5
40.9 / 43.9
51.6 / 55.5
40.9 / 43.9
51.6 / 55.5
73.1 / 79.0
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRT427A
BAYHTRT436A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
26 / 31
38 / 45
50 / 59
39 / 47
58 / 69
78 / 92
39 / 47
58 / 69
78 / 92
58 / 69
78 / 92
58 / 69
78 / 92
116 / 138
2
2
2
1
2
2
1
2
2
2
2
2
2
2
10.9 / 13.0
14.4 / 17.2
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
11.3 / 13.5
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
16.9 / 20.2
22.6 / 26.9
33.8 / 40.4
30 / 30
35 / 40
35 / 35
40 / 45
50 / 60
35 / 35
40 / 45
50 / 60
40 / 45
50 / 60
45 / 45
60 / 60
30 / 30
35 / 40
35 / 35
40 / 45
50 / 60
35 / 35
45 / 45
60 / 60
45 / 45
60 / 60
45 / 45
60 / 60
TSC072AD
TSC090AD
TSC102AD
TSC120AD
80 / 80
80 / 80
Notes:
1. All units to be installed under local codes
2. kW and MBH shown for 380V / 415V
Table ED-3 — Electrical Characteristics - Evaporator Fan Motor - 50 Hz
Standard Evaporator Fan Motor
Oversized Evaporator Fan Motor
Unit
Amps
Amps
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
No.
1
1
1
1
Volts
Phase
HP
1.5
1.5
2.0
2.0
3.0
FLA
4.3
4.3
5.3
5.3
7.0
LRA
25.3
25.3
36.4
36.4
57.0
No.
Volts
-
380-415
380-415
380-415
-
Phase
HP
-
2.0
3.0
3.0
-
FLA
-
5.3
7.0
7.0
-
LRA
-
36.4
57.0
57.0
-
380-415
380-415
380-415
380-415
380-415
3
3
3
3
3
-
1
1
1
-
-
3
3
3
-
1
Table ED-4 — Electrical Characteristics - Compressor Motor and Condenser Motor - 50 Hz
Compressor Motor
Condenser Fan Motor
Unit
Amps
Amps
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
No.
1
1
1
2
Volts
Phase
HP1
5.7
7.5
8.3
6.0/3.8
6.0/4.8
RPM
2875
2875
2875
2875
2875
RLA1
9.5
12.7
13.20
9.3/6.9
9.9/8.5
LRA1
74.00
95.00
No.
Phase
HP
FLA
1.9
2.8
2.8
2.8
2.8
LRA
2.8
7.1
7.1
7.1
380-415
380-415
380-415
380-415
380-415
3
3
3
3
3
1
1
1
1
1
1
1
1
1
1
0.40
0.75
0.75
0.75
0.75
100.00
74.0/48.0
74.0/61.8
2
7.1
Note:
1. Com p1/Com p2
RT-PRC016-EN
34
Download from Www.Somanuals.com. All Manuals Search And Download.
J obsite
Connections
Zone Sensors — Typical Number Of Wires
DISCONNECT
SWITCH
(BY OTHERS)
A — Manual Changeover . . . . . . . . . . . . . . . . . 4
Manual/Auto Changeover . . . . . . . . . . . . . 5
Manual/Auto Changeover with
ZONE SENSOR
OR THERMOSTAT
Status Indication LED’s . . . . . . . . . . . . . 10
Programmable Night Setback with
Status Indication LED’s . . . . . . . . . . . . . . 7
ROOFTOP
UNIT
Thermostats — Typical Number of Wires
A — 3 wires, 24-volts, Cooling Only
4 wires, 24-volts, with Electric Heat
B — 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
For specific wiring inform ation, see the installation instructions.
All wiring except power wires is low voltage.
All custom er supplied wiring to be copper and m ust conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the custom er.
RT-PRC016-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Dim ensional
Data
TSC060
All dimensions are in inches/millimeters.
TSC060
RT-PRC016-EN
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Dim ensional
Data
TSC060
All dimensions are in inches/millimeters.
TSC060 — Downflow Airflow Supply/Return
TSC060 — Horizontal Airflow Supply/Return
TSC060 — Unit Clearance and Roof Opening
RT-PRC016-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Dim ensional
Data
TSC060
All dimensions are in inches/millimeters.
TSC060 — Roof Curb
TSC060 — Downflow Duct Connections — Field Fabricated
RT-PRC016-EN
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Dim ensional
Data
TSC072-120
All dimensions are in inches/millimeters.
TSC072-090
TSC102-120
RT-PRC016-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Dim ensional
Data
TSC072-120
All dimensions are in inches/millimeters.
TSC072-120 — Downflow Airflow Supply
and Return
TSC072-120 — Horizontal Airflow Supply
and Return
TSC072-120 — Unit Clearance and Roof
Opening
RT-PRC016-EN
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Dim ensional
Data
TSC072-120
All dimensions are in inches/millimeters.
TSC072-120 — Roof Curb
TSC072-120 — Downflow Duct Connections —
Field Fabricated
ALL FLANGES 1 1/4” (31 MM)
RT-PRC016-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
TSC060
Options/Accessories
Dim ensional
Data
All dimensions are in inches/millimeters.
TSC060 — Barometric Relief Damper Hood
TSC060 — Economizer , Manual or Motorized Fresh Air Damper
TSC060 — Swing Diameter for Hinged Doors Option
RT-PRC016-EN
42
Download from Www.Somanuals.com. All Manuals Search And Download.
TSC072-120
Options/Accessories
Dim ensional
Data
All dimensions are in inches/millimeters.
TSC072-120 — Economizer and Barometric
Relief Damper Hoods
TSC072-120 — Swing Diameter for
Hinged Door(s) Option
RT-PRC016-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
Table W-1 - Maximum Unit and Corner Weights and Center of Gravity Dimensions (SI)
Maximum Weights(2) (kg)
Corner Weights(1) (kg)
Center of Gravity (mm)
Unit
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Shipping(2)
259
Net(2)
235
326
389
405
445
A
75
107
131
133
147
B
56
83
101
106
115
C
D
56
78
89
94
Length
790
970
970
990
Width
480
560
530
560
48
58
67
72
81
365
428
445
485
104
990
560
Notes:
(1) Corner weights are given for inform ation only. All m odels m ust be supported continuously by a curb or equivalent fram e support.
(2) Weights are approxim ate.
Table W-1a - Maximum Unit and Corner Weights and Center of Gravity Dimensions (IP)
Maximum Weights (lbs)
Corner Weights(1) (lbs)
Center of Gravity (in)
Unit
Model No.
TSC060AD
TSC072AD
TSC090AD
TSC102AD
TSC120AD
Shipping(2)
572
805
944
980
1069
Net
518
718
857
893
982
A
B
C
D
Length
31
38
38
39
Width
165
235
289
294
323
124
182
222
233
253
105
128
148
159
178
124
173
197
207
229
19
22
21
22
22
39
Notes:
(1) Corner weights are given for inform ation only. All m odels m ust be supported continuously by a curb or equivalent fram e support.
(2) Weights are approxim ate.
Table W-2a - Accessory Net Weights(1) (2) (lbs)
Table W-2 - Accessory Net Weights(1) (2) (kg)
Net Weights(2)
Net Weights(2)
TSC072-120
Accessory(3)
TSC060
TSC072-120
Accessory(3)
TSC060
Economizer
26
7
20
16
70
5
12
10
15
36
10
30
26
115
8
20
12
30
Economizer
12
3
9
7
32
2
5
5
7
16
5
14
12
52
4
9
5
14
Barometric Relief
Motorized Outside Air Damper
Manual Outside Air Damper
Roof Curb
Oversized Motor
Coil Guards
Barometric Relief
Motorized Outside Air Damper
Manual Outside Air Damper
Roof Curb
Oversized Motor
Coil Guards
Hinged Doors
Electric Heaters
Hinged Doors
Electric Heaters
Notes:
Notes:
(1) Weights for options not listed are < 5 lbs.
(1) Weights for options not listed are < 3 kg.
2) Net weight should be added to unit weight when ordering factory-installed
accessories.
(3) Som e accessories not available on all units.
(2) Net weight should be added to unit weight when ordering factory-installed
accessories.
(3) Som e accessories not available on all units.
RT-PRC016-EN
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Outdoor Fans
Unit Top
General
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position. The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.
The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasket-
sealed. The ribbed top adds extra
strength and prevents water from
pooling on unit top.
The units shall be convertible airflow.
The operating range shall be between
46°C and -18°C (115°F and 0°F) in
cooling as standard from the factory for
all units. All units shall be factory
assembled, internally wired, fully
charged with R-22, and 100 percent run
tested to check cooling operation, fan
and blower rotation, and control
sequence before leaving the factory.
Wiring internal to the unit shall be
colored and numbered for simplified
identification.
Indoor Fan
Filters
All units shall have belt drive motors.
Units with belt drive motors shall have
an adjustable idler-arm assembly for
quick-adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. Oversized motors shall be
available for high static operations.
One inch, throwaway filters shall be
standard on all 5 ton units. The filter rack
can be converted to two inch capability.
50 mm (2 inch) filters shall be factory
supplied on all 6-10 ton units. Optional
50 mm (2 inch) pleated filters shall be
available.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Cabinet construction shall allow for all
maintenance on one side of the unit.
Service panels shall have lifting
handles and be removed and
reinstalled by removing only a single
fastener while providing a water and
air tight seal. All exposed vertical
panels and top covers in the indoor air
section shall be insulated with a
cleanable foil-faced, fire-retardent
permanent, odorless glass fiber
material. The base of the unit shall be
insulated with 13 mm, 16 kg (1/2 inch,
1 pound) density foil-faced, closed-cell
material. All insulation edges shall be
either captured or sealed.The unit’s
base pan shall have no penetrations
within the perimeter of the curb other
than the raised 29 mm (11/8 inch high
downflow supply/return openings to
provide an added water integrity
precaution, if the condensate drain
backs up. The base of the unit shall
have provisions for forklift and crane
lifting, with forklift capabilities on three
sides of the unit.
Controls
Compressors
All units shall have direct-drive,
Unit shall be completely factory-wired
with necessary controls and contactor
pressure lugs or terminal block for
power wiring. Units shall have single
point power connection as standard.
Unit shall provide an external location
for mounting a fused disconnect device.
hermetic, scroll type compressors with
centrifugal type oil pumps. Motor shall
be suction gas-cooled and shall have a
voltage utilization range of plus or minus
10 percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. Low and high
pressure switches shall be standard.
Microprocessor controls provide for all
24 volt control functions. The resident
control algorithms shall make all
heating, cooling, and/or ventilating
decisions in response to electronic
signals from sensors measuring indoor
and outdoor temperatures. The control
algorithm maintains accurate
temperature control, minimizes drift
from set point, and provides better
building comfort. A centralized
Microprocessor shall provide anti-short
cycle timing and time delay between
compressors to provide a higher level of
machine protection.
Refrigerant Circuits
Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.
Evaporator and Condenser Coils
Internally finned, 8 mm (5/16”) copper
tubes mechanically bonded to a
configured aluminum plate fin shall be
standard. Coils shall be leak tested at the
factory to ensure the pressure integrity.
The evaporator coil and condenser coil
shall be leak tested to 1375 kPa (200
psig) and pressure tested to 3100 kPa
(450 psig). The condenser coil shall have
a patent pending 1 + 1 + 1 hybrid coil
designed with slight gaps for ease of
cleaning. A removeable, reversible,
double-sloped condensate drain pan
with provision for through the base
condensate drain is standard.
RT-PRC016-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Economizer — This accessory shall be
either field or factory-installed and shall
be available with or without barometric
relief. The assembly includes fully
modulating 0-100 percent motor and
dampers, minimum position setting,
preset linkage, wiring harness with plug,
spring return actuator and fixed dry bulb
control. The barometric relief shall
provide a pressure operated damper that
shall be gravity closing and shall prohibit
entrance of outside air during the
equipment “off” cycle. Optional solid
state or differential enthalpy control shall
be available for either factory or field
installation. The factory-installed
Motorized Outside Air Dampers —
Factory or field-installed manually set
outdoor air dampers shall provide up to
50 percent outside air. Once set, outdoor
air dampers shall open to set position
when indoor fan starts. The damper
shall close to the full closed position
when indoor fan shuts down.
Accessories/Options
Electric Heaters — Field-installed electric
heat modules shall be available for
installation within basic unit. Electric
heater elements shall be constructed of
heavy-duty nickel chromium elements
internally delta connected for 200 volt,
wye connected for 380-415 volt. Staging
shall be achieved through the unitary
control processor (UCP). Each heater
package shall have automatically reset
high limit control operating through
heating element contactors. All heaters
shall be individually fused from the
factory, where required. Power
Discharge Air Sensing — This factory of
field-installed option provides true
discharge air sensing in heating models.
This sensor is a status indicator readable
through Tracer™ or Tracker™.
Oversized Motors — Factory or field-
installed oversized motors shall be
available for high static applications.
assemblies shall provide single-point
connection.
economizer arrives in the shipping
position and shall be moved to the
operating position by the installing
contractor.
Clogged Filter/Fan Failure Switch — A
dedicated differential pressure switch is
available, factory-installed, to achieve
active fan failure indication and/or
clogged filter indication. These
indications will be registered with either
a zone sensor with status indication
lights or an Integrated Comfort™ System.
Roof Curb — The roof curb shall be
designed to mate with the unit’s
downflow supply and return and provide
support and a water tight installation
when installed properly.The roof curb
design shall allow field-fabricated
rectangular supply/return ductwork to be
connected directly to the curb. Curb shall
be shipped knocked down for field
assembly and shall include wood nailer
strips.
Remote Potentiometer — The minimum
position setting of the economizer shall
be adjusted with this accessory.
Manual Outside Air Damper — Factory
or field-installed rain hood and screen
shall provide up to 50 percent outside air.
RT-PRC016-EN
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
High Pressure Cutout — Standard on all
units.
Differential Pressure Switches — These
factory or field-installed sensors allow
individual fan failure and dirty filter
indication for microprocessor controlled
units. The fan failure switch will disable
all unit functions and “flash” the Service
LED on the zone sensor.The dirty filter
switch will light the Service LED on the
zone sensor and will allow continued
unit operation.
Control Options
Comm-3/4 Trane Communication
Interface — This factory or field-installed
option shall be provided to interface
microprocessor controlled units with the
Trane Integrated Comfort™ systems.
Hinged Access Doors — Sheet metal
hinges are available factory-installed on
the Filter/Evaporator, Supply Fan/Heat,
and the Compressor/Control Access
Doors.
Comm-5 LonTalk Communication
Interface — This factory or field-installed
option shall be provided to allow the unit
to communicate as a Trane Comm-5
device or directly with generic LonTalk
Network Building Automation System
Controls.
Black Epoxy Coated Condenser Coil —
The coil provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory-applied
thermoset vinyl coating, bonded to
normal aluminum fin stock. The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection.
Reference Enthalpy Control — Replaces
the dry bulb control with a wet bulb
changeover controller which has a fully
adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential,
than the standard dry bulb control. This
is due to the additional wet bulb sensing
capability.This option shall be available
for microprocessor controlled units. It
can be field-installed, or factory-installed
with the factory-installed economizer.
Zone Sensor — This field-installed
control shall be provided to interface
with the Micro equipped units and shall
be available in either manual, automatic
programmable with night setback, with
system malfunction lights, or remote
sensor options.
Thermostats —Two stage heating and
cooling operation or one stage heating
and cooling shall be available, for field
installation, in either manual or
automatic changeover. Automatic
programmable electronic with night set
back shall also be available.
Differential Enthalpy Control — Replaces
the standard dry bulb control with two
enthalpy sensors that compare total heat
content of the indoor air and outdoor air
to determine the most efficient air
source. This control option offers the
highest level of comfort control, plus
energy efficiency, available. This option
shall be available for microprocessor
controlled units. It can be field-installed,
or factory-installed with the factory-
installed economizer.
Low Ambient Cooling — All
microprocessor units shall have cooling
capabilities down to 18°C (0°F) as
standard.
RT-PRC016-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
RT-PRC016-EN
PL-UN-000-RT-PRC016-EN-11-03
PL-UN-000-RT-PRC016-EN-10-03
03-03 Webb/Mason 11-03 Electronic Only
Supersedes
Trane
A business of American Standard Companies
www.trane.com
Stocking Location
Trane has a policy of continuous product and product data improvement and reserves the right to change
design and specifications without notice
For more information, contact your local district
Download from Www.Somanuals.com. All Manuals Search And Download.
|