Trane Heating System TR200 User Manual

Operators Guide  
TR200 Vertical Bypass/Non Bypass Panel  
SAFETY WARNING  
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing  
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and  
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or  
serious injury. When working on the equipment, ovserve all precautions in the literature and on the tags,  
stickers, and labels that are attached to the equipment.  
BAS-SVX49A-EN  
August 2011  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
Safety  
Grounding  
WARNING  
Correct protective grounding of the equipment must be  
established in accordance with national and local codes.  
Ground currents are higher than 3mA.  
EQUIPMENT HAZARD!  
The vertical bypass/non bypass panel contains dangerous  
voltages when connected to mains voltage. It is strongly  
recommended that all electrical work conform to the  
National Electrical Code (NEC) and all national and local  
regulations. Installation, start-up and maintenance should  
be performed only by qualified personnel. Failure to follow  
the NEC or local regulations could result in death or  
serious injury.  
Safety Guidelines  
1.  
Disconnect the drive and vertical bypass/non  
bypass panel from mains before commencing  
service work  
2.  
DO NOT touch electrical parts of the vertical  
bypass/non bypass panel or drive when mains is  
connected. After mains has been disconnected,  
wait 15 minutes before touching any electrical  
components or read the label on vertical  
bypass/non bypass panel.  
Motor control equipment and electronic controls are  
connected to hazardous mains voltages. Extreme care  
should be taken to protect against shock. The user must  
be protected against supply voltage and the motor must  
be protected against overload in accordance with  
applicable national and local regulations. Be sure  
equipment is properly grounded. Wear safety glasses  
whenever working on electric control or rotating  
equipment.  
3.  
The user must be protected against supply  
voltage and the motor must be protected against  
overload in accordance with applicable national  
and local regulations.  
4.  
5.  
While programming parameters, the motor may  
start without warning. Activate the [Off] key on  
the keypad when changing parameters.  
Warning against unintended start  
WARNING  
The [Off] key on the keypad does not isolate the  
drive from mains voltage and is not to be used as  
a safety switch.  
UNINTENDED START!  
When the vertical bypass/non bypass panel is connected  
to AC input power, the motor may start at any time. The  
drive, panel, motor, and any driven equipment must be in  
operational readiness. Failure to be in operational  
readiness when panel and drive are connected to AC input  
power could result in death, serious injury, or equipment  
or property damage.  
When the vertical bypass/non bypass panel is connected  
to mains, the motor may be started by means of an  
external switch, a serial bus command, an input reference  
signal, or a cleared fault condition. Use appropriate  
cautions to guard against an unintended start.  
WARNING  
GROUNDING HAZARD!  
For operator safety, it is important to ground drive, vertical  
bypass panel, and motor properly. Follow the grounding  
guidelines of local and national codes. Failure to follow  
grounding guidelines could result in death or serious  
injury.  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1 Introduction  
inputs, and status reporting. The VFD’s logic circuitry is  
1.1.1 Purpose of the Manual  
backed up by an independent panel-mounted power  
supply so that, even if the drive loses power, control and  
communication functions are maintained. Programming  
and display are provided by the keypad. An important  
feature of the ECB is the ability to accept commands from  
a building automation system (BAS) and to report  
operational status in return.  
This manual is intended to provide detailed information for  
the installation and operation of the option panel used in  
conjunction with a Trane variable frequency drive (VFD or  
drive). To enable efficient handling of the equipment,  
requirements are provided for installation of mechanical,  
electrical, control wiring, proper grounding, and environ-  
mental considerations. Pre-start and start up procedures  
are detailed. Also included is a detailed overview of the  
option panel bypass function. In addition, identification of  
other optional components and their operation and start  
up troubleshooting instructions are included. For the  
electronically controlled bypass, additional programming  
and operation information is provided.  
See more detailed descriptions of the EMB2 in 5 Electrome-  
1.1.3 Typical Bypass Operation  
With contactors M1 and M2 closed and contactor M3  
open, the motor is running in drive control. Opening  
contactor M2 removes power to the motor but allows the  
drive to remain under power. This is referred to as test  
mode. With contactors M1 and M2 open and contactor M3  
closed, the motor is running in bypass from the line input  
power.  
1.1.2 Overview  
A variable frequency drive regulates the speed and  
operation of an electric motor. The drive is programmable  
and offers many features and savings compared to  
operating a motor from unregulated line voltage. The  
option panel is a protective enclosure in which the drive  
and various optional components are assembled and  
mounted. The vertical non bypass panel is always  
configured with a disconnect switch and fuses to protect  
the drive. The vertical bypass panel allows switching  
between running the motor from the drive (variable speed)  
or across the line input power (constant speed).  
1.2 Bypass Circuits  
1.2.1 Three-contactor Bypass  
The bypass circuit consists of a bypass contactor (M3)  
interlocked with a drive output contactor (M2), a drive  
input contactor (M1), and an overload relay. For the EMB2,  
a door mounted Drive/OFF/Bypass/Test Selector switch is  
used to electrically select whether the motor is powered  
by the drive, connected to the full speed bypass, or  
disconnected from both. The test position applies power  
to the motor through the bypass (M3 closed) contactor but  
removes power from the drive (M2 open) while keeping  
the drive powered (M1 closed). A Pilot light indicates when  
in bypass. For the ECB, control selection is made through  
the drive keypad by pressing the DRIVE BYPASS key and  
selecting from the available options shown. Display data  
indicates when in bypass. The circuitry may be supplied  
with either an input disconnect switch or an input circuit  
breaker.  
The vertical bypass panel comes with one of two control  
options:  
The electromechanical bypass (EMB2)  
Electronically controlled bypass (ECB)  
The EMB2 is operated by a selector switch on the front of  
the panel. The EMB2 controls a motor by switching  
between drive control, operation in bypass, or off. In  
addition, a test selection is available, which disengages the  
motor from the drive but keeps the drive operational while  
the motor runs in bypass. The switching function activates  
contactors to provide power to the motor through the  
drive or bypass circuitry, as required.  
The ECB also uses contactors to provide power to the  
motor through the drive or bypass circuitry. However, the  
ECB contains a local processor that interacts with the  
drive’s control logic for programmable options, remote  
BAS-SVX49A-EN  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Introduction  
Contactor  
Drive Mode OFF  
Bypass  
Mode  
Open  
Open  
Test Mode  
M1  
M2  
M3  
Closed  
Closed  
Open  
Open  
Closed  
Open  
Open  
Open  
Closed  
Closed  
Table 1.1 Contactor Operation  
Figure 1.1 Basic Non Bypass Circuit  
1.3.4 Basic Fire Mode in Bypass  
1.3 Bypass Options  
This option switches the panel to bypass whenever a  
remote fire mode signal is given to the VFD through the  
input terminals. In either drive or bypass, fire mode is  
intended to ignore common safety and overload inputs for  
emergency situations. The motor will continue to run in  
bypass until fire mode is removed or the drive, panel, or  
motor fails. External safety signals and motor overload are  
ignored when in fire mode.  
1.3.1 Common Run/Stop with Bypass  
Allows a remote signal to initiate operation in either drive  
control or bypass depending upon the position of the  
bypass selector switch.  
1.3.2 Automatic Bypass  
1.3.5 Advanced Fire Mode in Bypass  
This feature automatically transfers the motor from drive to  
bypass without operator intervention when a fault  
condition trips the drive, after a programmable time-out  
period. The VFD’s internal fault circuitry controls this  
action. The time delay permits all automatically resettable  
faults to clear prior to transfer to bypass. Run permissive or  
safety circuit signals override the auto bypass function and  
may prevent or delay bypass operation.  
The advanced fire mode allows for a variety of  
programmable responses to an external fire mode  
command signal. Bypass options are programmed through  
the drive’s fire mode parameters. See 6.1.13 ECB Advanced  
1.3.6 Overload Protection  
1.3.3 Run Permissive in Bypass  
This thermally activated device provides mechanical  
overload protection for the motor while in bypass  
With run permissive active, the drive sends a run request  
and waits for a remote response before commanding the  
motor to start. The response indicates the system is safe to  
operate.  
operation. It measures motor current and is set to the full  
load amps (FLA) of the motor. A 1.2 x FLA service factor is  
built-in and maintained, meaning that should the motor  
current increase above that value, the overload will  
calculate the level of increase to activate timing for the trip  
function. The higher the current draw, the quicker the trip  
response. The overload provides Class 20 motor protection.  
1-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Introduction  
Control Features  
Safety Interlock  
EMB2  
ECB  
X
X
X
X
X
X
1.4 Bypass Platform Configurations  
Common Start / Stop  
Automatic Bypass  
Run Permissive  
X
X
The two bypass platform configurations are ECB and EMB2.  
The features available as options with each platform are  
listed in Table 1.2. The ECB, also listed below, has all option  
features available. See 5 Electromechanical Bypass (EMB2)  
Operation for additional details on the EMB2 and  
ECB.  
X
Basic Fire Mode  
X
Advanced Fire Mode  
Serial Communication  
X
X
Table 1.2 Bypass Configurations  
Figure 1.2 Basic Bypass Circuit  
1.5.1 Control Transformer  
1.5 Switch Mode Power Supply  
A control transformer is included on larger horsepower  
units where the contactor coils are AC. The control  
transformer steps down the line input voltage to 120V AC.  
The coils of AC contactors are isolated from the Switch  
Mode Power Supply via relays.  
The VFD’s logic circuitry is backed up by an independent  
panel-mounted switch mode power supply so if the drive  
loses power, control and communication functions are  
maintained. The SMPS converts three-phase AC input  
power to 24 V DC control power. Since the SMPS draws  
power from all three phases, it offers immunity protection  
from most phase-loss and brown-out conditions. The SMPS  
is internally protected from short circuit on its output and  
three board-mounted fuses provide additional protection.  
The SMPS is not designed for external use and may take  
up to 5 sec. to initialize at power-up. The SMPS will  
maintain a 24 V DC output with a low input line voltage.  
The 200 Volt SMPS will maintain the 24 V DC output with  
a line voltage as low as 150 V AC and the 600 V SMPS to  
335 V AC. Refer to Figure 1.2.  
1.6 Disconnects  
1.6.1 Main Disconnect  
The main disconnect removes line input power to the  
drive and bypass. A main disconnect is available in four  
options.  
Fused disconnect. Two-position (ON/OFF) rotary  
switch, padlock compatible, with three fuses, one  
on each phase, built into the switch. For safety,  
the switch must be in the OFF position before  
BAS-SVX49A-EN  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Introduction  
the option panel door can be opened. (Bypass  
panel only.)  
Disconnect without fuses. For user-supplied fuses  
option. (Bypass panel only.)  
Main circuit breaker. A thermal/ magnetic current  
interrupt device using an ON/TRIP/OFF/RESET  
switch. When in the ON position, a trip fault  
removes power from the drive/bypass circuit and  
the switch moves to the TRIP setting. The switch  
must be moved to the RESET position  
momentarily after the fault has been cleared to  
reset the circuit breaker. (Bypass panel only.)  
Main Disconnect with drive fuses. Non-bypass  
panel two-position (ON/OFF) rotary switch that  
disconnects the main AC line power to the drive  
only.  
1.6.2 Mode Selector Switch  
The mode selector switch is used for 3-contactor bypass  
on EMB2 units. The selector switch allows the operator to  
select from four modes of operation.  
Drive mode: When drive mode is selected, the M1 and M2  
contactors are closed allowing power to flow in and out of  
the drive to the motor.  
Off mode: This mode opens all contactors removing any  
power to the motor.  
Bypass mode:When bypass mode is selected, the M3  
contactor closes and allows the motor to run directly from  
the input line power.  
Test mode:Test mode closes the M1 and M3 contactors  
and allows the motor to be powered by the input line  
power. This also allows the drive to power up without  
being connected to the motor. Refer to Figure 1.2.  
1-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
1.6.3 Panel Configurations  
The TR 200 Drive Series comes in two panel enclosure types. One is the non bypass and the other is the bypass. See  
Table 1.3 for descriptions and available options.  
Non bypass  
Bypass  
Drive plus both of the following:  
1. Fuses  
Drive with bypass:  
1. Fuses  
2. Disconnect  
2. Disconnect/Circuit Breaker  
3. Contactors  
4. Power Supply  
5. Control Module  
Table 1.3 Tier Definitions and Features  
BAS-SVX49A-EN  
1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
1.6.4 Panel Voltage and Frame Ratings  
Table 1.4Table 1.4 defines the voltage and hp ratings of the frames sizes for the panel. See 8 Appendix for overall and  
mounting dimensions.  
Bypass  
TR200  
Non Bypass  
TR200  
Panel P2  
(B3 - Drive)  
Volts VAC  
208 & 230  
460 & 600  
HP (KW)  
HP (KW)  
7.5 (5.5) - 15 (11)  
15 (11) - 25 (18.5)  
7.5 (5.5) - 15 (11)  
15 (11) - 25 (18.5)  
Bypass  
TR200  
Non Bypass  
TR200  
Panel P3  
(B4 - Drive)  
Volts VAC  
208  
20 (15)  
20 (15) - 25 (18.5)  
30 (22) - 50 (37)  
230  
20 (15) - 25 (18.5)  
30 (22) - 50 (37)  
460 & 600  
Bypass  
TR200  
Non Bypass  
TR200  
Panel P4  
(C3 - Drive)  
Volts VAC  
208  
HP (KW)  
25 (18.5)  
30 (22) - 40 (30)  
60 (45) - 75 (55)  
230  
30 (22) - 40 (30)  
60 (45) - 75 (55)  
460 & 600  
Bypass  
TR200  
Non Bypass  
TR200  
Panel P5  
(C4 - Drive)  
Volts VAC  
208 & 230  
460 & 600  
HP (KW)  
50 (37) - 60 (45)  
50 (37) - 60 (45)  
100 (75) - 125 (90)  
100 (75) - 125 (90)  
Table 1.4 Panel Voltage and Frame Ratings  
1.7 Power Component Functions  
1.7.1 Power Fusing  
Drive fusing  
Drive fuses are located ahead of the drive and are a fast-  
acting type. Drive fuses are standard in all bypass and non-  
bypass panels.  
For main panel power fuses, only use the specified fuse or  
an equivalent replacement. For drive fuses only use the  
specified fuse. See the fuse ratings label on the inside  
cover of the unit or Table 3.2Table 3.2, Table 3.3Table 3.3,  
Table 3.4Table 3.4 and Table 3.5Table 3.5.  
5,000 or 100,000 amp SCCR  
The bypass panel supplied with a non fusible Main  
Disconnect Switch is 5,000 amps short-circuit current rating  
(SCCR). The bypass panel supplied with a Fusible  
disconnect or circuit breaker is 100,000 amp SCCR. The  
non bypass panel supplied with a non-fusible Main  
Disconnect is 100,000 amp SCCR. See the panel label for  
SCCR rating.  
Main fusing  
Main fuses are located ahead of the drive and bypass.  
Main fuses are designed to protect the circuitry within the  
bypass panel but is not adequate to protect the drive.  
Main fuses are dual-element, time-delay types and mount  
inside the bypass enclosure.  
NOTE!  
The 600 V circuit breaker option is 5,000 amp (SCCR).  
1-6  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Pre-installation  
2 Pre-installation  
2.1.1 Receiving Inspection  
2.1.2 Pre-installation Check  
Inspect the packaging and equipment closely when  
received. Any indication of careless handling by the carrier  
should be noted on the delivery receipt, especially if the  
equipment will not be immediately uncrated. Obtain the  
delivery person’s signed agreement to any noted damages  
for any future insurance claims. Ensure that the model  
number and power match the order and intended use for  
the drive.  
1.  
2.  
Compare panel model number to what was  
ordered.  
Ensure each of the following are rated for the  
same voltage:  
Drive  
Panel  
Power line  
Motor  
IMPORTANT LOST OR DAMAGED GOODS INSPECT THIS  
SHIPMENT IMMEDIATELY UPON ARRIVAL If goods are  
received short or in damaged condition, insist on a  
notation of the loss or damage across the face of the  
freight bill. Otherwise no claim can be enforced against  
the transportation company. If concealed loss or damage is  
discovered, notify your carrier at once and request an  
inspection. This is absolutely necessary. Unless you do this  
the carrier will not entertain any claim for loss or damage.  
The agent will make an inspection and can grant a  
concealed damage notation. If you give the transportation  
company a clear receipt for equipment that has been  
damaged or lost in transit, you do so at your own risk and  
expense.  
3.  
Ensure that the panel output rating is equal to or  
greater than motor total full load current for full  
motor performance.  
Motor power size and panel must match  
for proper overload protection.  
If panel rating is less than motor; full  
motor output cannot be achieved.  
Check motor wiring:  
4.  
Any disconnect between drive and  
motor should be interlocked to drive  
safety interlock circuit to avoid  
unwanted drive trips.  
Trane is willing to assist you to collect claims for loss or  
damage, but willingness on our part does not make us  
responsible for collection of claims or replacement of  
material. The actual filing and processing of the claim is  
your responsibility.  
Do not connect power factor correction  
capacitors between the drive and motor.  
Two speed motors must be wired  
permanently for full speed.  
Y-start, Δ-run motors must be wired  
permanently for run.  
2.1.3 Installation Site Check  
Because the option panel relies on the ambient  
air for cooling, it is important to observe the  
limitations on ambient air temperature. Derating  
concerns start above 104°F (40°C) and 3300 feet  
(1000m) elevation above sea level.  
Figure 2.1 Sample Panel Label  
It is important with multiple panels to check wall  
strength. Make sure that the proper mounting  
screws or bolts are used.  
Ensure that the wall or floor area for installation  
will support the weight of the unit.  
If construction work continues after the  
equipment is mounted, it is important to keep  
the interior free from concrete dust and similar  
BAS-SVX49A-EN  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Pre-installation  
dirt. If the unit does not have power applied to it,  
supply a protective covering. It is important to  
ensure that the components stay as clean as  
possible. It may be necessary to clean the interior  
once construction is completed.  
Keep drawings and manuals accessible for  
detailed installation and operation instructions. It  
is important that the manuals be available for  
equipment operators.  
2.2 Harsh Environments  
NOTE!  
The mechanical and electrical components within the  
option panel can be adversely affected by the  
environment. The effects of contaminants in the air, either  
solid, liquid, or gas, are difficult to quantify and control.  
2.2.1 Airborne Liquids  
Liquids in the air can condense in components. Water  
carried in the air is easily measured as relative humidity,  
but other vapors are often more difficult to measure or  
control. Steam, oil and salt water vapor may cause  
corrosion of components. In such environments, use TYPE  
12 enclosures to limit the exchange of outside air into the  
option enclosure. Extremely harsh environments may  
require a higher level of protection.  
2.2.2 Airborne Solids  
Particles in the air may cause mechanical, electrical or  
thermal failure in components. A TYPE 1 enclosure  
provides a reasonable degree of protection against falling  
particles, but it will not prevent the fan from pulling dirty  
air into the enclosure.  
2.2.3 Corrosive Chemicals  
In environments with high temperatures and humidity,  
corrosive gases such as sulfur, nitrogen and chlorine  
compounds cause corrosion to occur in components.  
Indications of corrosion are blackened copper or rust on  
steel or oxidized aluminum. In such environments, it is  
recommended that the equipment be mounted in a  
cabinet with fresh air ventilation and that corrosive  
compounds be kept away. A non-ventilated cabinet fitted  
with an air conditioner as a heat exchanger may be used.  
Conformal coated circuit boards may be specified to  
reduce the corrosive effects of a harsh environment.  
2-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
3 Installation  
TOOLS  
Spreader bar capable of lifting up to 750 lbs.  
Max diameter 0.5 in.  
3.1.1 Tools Required  
In addition to the standard tool kit, the tools in Table 3.1  
Forklift, crane, hoist or other lifting device capable of handling  
up to 750 lbs. (Qualified device operator available for operating  
the equipment.)  
are recommended for installation of the option panel.  
Metric Socket Set: 7 - 19mm  
Socket Extensions: 4, 6, and 12 inch  
Torx driver set: T10 - T40  
Torque wrench: 6 - 375 lbs-in  
Allen Wrenches:1/8, 3/16, 1/4, & 5/16 inches  
Metric or English wrenches: 7 - 19mm  
Table 3.1 Tools Required  
3.1.2 Drive Fuses  
To maintain UL, the drive fuses should be replaced only with the fuses specified in , , , and . If an alternate drive fuse is  
desired please consult the factory. See the specifications label inside the cover of the unit for acceptable replacement drive  
fuses. A sample of this data can be seen in Table 3.6  
208 V AC  
UL Motor  
Current  
24,2  
Panel (TR200) Non Bypass  
& Bypass  
Main Fuse (TR200)  
Bussman  
Drive Fuse (TR200)  
Bussman  
JJN-50  
Transformer Fuse (TR200)  
Bussman  
HP (KW)  
7.5 (5.5)  
10 (7.5)  
15 (11)  
20 (15)  
LPJ-40-SP  
30,8  
P2  
LPJ-50-SP  
JJN-50  
46,2  
LPJ-70-SP  
JJN-60  
59,4  
P3  
LPJ-90-SP  
JJN-80  
P3 - Non Bypass P4 -  
Bypass  
25 (18.5)  
74,8  
LPJ-125-SP  
JJN-125  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
88  
LPJ-150-SP  
LPJ-175-SP  
LPJ-250-SP  
LPJ-250-SP  
JJN-125  
JJN-150  
JJN-200  
JJN-250  
P4  
P5  
114  
143  
169  
FNQ-R-1.25  
FNQ-R-1.25  
Table 3.2 Drive Fuses 208 V  
BAS-SVX49A-EN  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
HP (KW)  
230 V AC  
Main Fuse (TR200)  
Bussman  
UL Motor  
Current  
22  
Panel (TR200) Non Bypass  
& Bypass  
Drive Fuse (TR200)  
Bussman  
JJN-50  
Transformer Fuse (TR200)  
Bussman  
7.5 (5.5)  
10 (7.5)  
15 (11)  
20 (15)  
25 (18.5)  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
LPJ-35-SP  
28  
P2  
LPJ-45-SP  
JJN-50  
42  
LPJ-70-SP  
JJN-60  
54  
LPJ-90-SP  
JJN-80  
P3  
P4  
P5  
68  
LPJ-100-SP  
LPJ-125-SP  
LPJ-150-SP  
LPJ-200-SP  
LPJ-250-SP  
JJN-125  
JJN-125  
JJN-150  
JJN-200  
JJN-250  
80  
104  
130  
154  
FNQ-R-1.25  
FNQ-R-1.25  
Table 3.3 Drive Fuses 230 V  
460 V AC  
Main Fuse (TR200)  
Bussman  
UL Motor  
HP (KW)  
Panel (TR200) Non  
Bypass & Bypass  
Drive Fuse (TR200)  
Bussman  
JJS-40  
Transformer Fuse (TR200)  
Bussman  
Current  
15 (11)  
20 (15)  
25 (18.5)  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
75 (55)  
100 (75)  
125 (90)  
21  
27  
LPJ-35-SP  
P2  
P3  
LPJ-40-SP  
JJS-40  
34  
LPJ-50-SP  
JJS-50  
40  
LPJ-60-SP  
JJS-60  
52  
LPJ-80-SP  
JJS-80  
65  
LPJ-100-SP  
LPJ-125-SP  
LPJ-150-SP  
LPJ-200-SP  
LPJ-250-SP  
JJS-100  
JJS-125  
JJS-150  
JJS-200  
JJS-250  
77  
P4  
P5  
96  
124  
156  
FNQ-R-0.60  
FNQ-R-0.60  
Table 3.4 Drive Fuses 460 V  
600 V AC  
Main Fuse (TR200)  
Bussman  
UL Motor  
HP (KW)  
Panel (TR200) Non  
Bypass & Bypass  
Drive Fuse (TR200)  
Bussman  
JJS-35  
Transformer Fuse (TR200)  
Bussman  
Current  
15 (11)  
20 (15)  
25 (18.5)  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
75 (55)  
100 (75)  
125 (90)  
17  
22  
27  
32  
41  
52  
62  
77  
99  
125  
LPJ-30-SP  
P2  
P3  
LPJ-35-SP  
JJS-35  
LPJ-45-SP  
JJS-45  
LPJ-50-SP  
JJS-50  
LPJ-60-SP  
JJS-60  
LPJ-80-SP  
JJS-80  
LPJ-100-SP  
LPJ-125-SP  
LPJ-150-SP  
LPJ-200-SP  
JJS-100  
JJS-125  
JJS-150  
JJS-175  
P4  
P5  
FNQ-R-0.50  
FNQ-R-0.50  
Table 3.5 Drive Fuses 600 V  
3-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
3.1.3 Internal Main Panel Fuses  
Use only the specified fuse or an equivalent replacement for the internal main fuses. See the specifications label inside the  
cover of the unit for acceptable replacement main fuses. A sample of this can be seen in Table 3.6.  
Fuse  
Description  
Primary Transformer  
Main Fuses  
Manufacturer  
Bussmann  
Bussmann  
Bussmann  
Bussmann  
Part Number/Size  
FNQ-R-0.50  
F13A & C  
F15A, B, & C  
F16A, B, & C  
F900, F901,F902  
LPJ-30-SP  
Drive Fuses  
JJS-35  
SMPS - Power Supply  
FWH-020A6F, 500V  
Table 3.6 Sample Fuse Rating Label  
3.2 Mechanical Installation  
3.2.1 Lifting  
3.2.3 Forklift  
Only a competent lift operator with additional  
support personnel should attempt moving the  
unit.  
WARNING  
Heavy Objects!  
Do not use cables (chains or slings) except as shown. Each  
of the cables (chains or slings) used to lift the unit must be  
capable of supporting the entire weight of the unit. Lifting  
cables (chains or slings) may not be of the same length.  
Adjust as necessary for even unit lift. Other lifting  
arrangements may cause equipment or property-only  
damage. Failure to properly lift unit could result in death  
or serious injury. See details below.  
Carefully position forklift and ensure stability prior  
to lift.  
3.2.4 Shipping Weights  
Weights listed in Table 3.7 are approximate for base units.  
Options can add or reduce weight of unit. Weights listed  
are in lbs.  
WARNING  
Frame  
P2  
Non Bypass Panel  
Bypass Panel  
Check the weight of unit to determine the safety of the  
lifting method. Ensure that the lifting device is suitable for  
the task. If necessary, plan for a hoist, crane or forklift with  
appropriate rating to move the units.  
36  
66  
84  
P3  
106  
167  
248  
P4  
106  
155  
P5  
Follow recommendations below. failure to do so could  
result in death or serious injury.  
Table 3.7 Approximate Shipping Weights  
3.2.2 Hoist or Overhead Lift  
Use a solid steel spreader bar for lifting. Slide the  
spreader bar through the two (2) lifting holes on  
the panel. Lifting rings are 0.59in (15mm) in  
diameter (see Figure 3.1). If VFD mounting screws  
interfere with the spreader bar, lifting hooks can  
be used instead of the lifting bar.  
Connect the spreader bar to a hoist or other  
lifting device.  
Carefully lift the unit and secure it to the wall.  
Refer to 8 Appendix for dimensional drawings to  
determine fasteners size and location.  
BAS-SVX49A-EN  
3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Installation  
Figure 3.2 Side Cooling Clearance  
Figure 3.1 Proper Lifting Method  
3.3 Cooling  
Only mount the drive and panel vertically.  
Panels rely on the ambient air for cooling. It is  
important to observe the limitations on ambient  
air temperature. The maximum ambient  
temperature for all bypass panels is 40°C and  
45°C for non bypass panels. Derating concerns  
start above 3300 feet elevation above sea level.  
Most panels may be mounted side-by-side  
without additional side clearance. However, the  
P2 (B3 frame size) units require 1.5 in. minimum  
clearance between units (see Figure 3.2).  
Top and bottom clearance is required for cooling  
(see Figure 3.3). Generally, 2 to 10 inches (50 to  
250mm) minimum clearance is required,  
depending upon the hp (kW) of the unit. See the  
dimensional drawings in 8 Appendix for specific  
requirements.  
No additional back plate is required for drives  
with the bypass and non bypass panels.  
Figure 3.3 Cooling Airflow  
3-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
3.4 Electrical Installation  
WARNING  
INDUCED VOLTAGE!  
WARNING  
Run output motor cables from multiple drives separately.  
Induced voltage from output motor cables run together  
can charge equipment capacitors even with the equipment  
turned off and locked out. Failure to run output motor  
cables separately could result in death or serious injury.  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects  
before servicing. Follow proper lockout/tagout procedures  
to ensure the power cannot be inadvertently energized.  
Failure to disconnect power before servicing could result in  
death or serious injury.  
NOTE!  
Run input power, motor wiring and control wiring in three  
separate metallic conduits or raceways for high frequency  
noise isolation. Failure to isolate power, motor and control  
wiring could result in less than optimum drive and  
associated equipment performance.  
WARNING  
Proper Field Wiring and Grounding Required!  
All field wiring MUST be performed by qualified personnel.  
Improperly installed and grounded field wiring poses FIRE  
and ELECTROCUTION hazards. To avoid these hazards, you  
MUST follow requirements for field wiring installation and  
grounding as described in NEC and your local/state  
electrical codes. Failure to follow codes could result in  
death or serious injury.  
NOTE RUN INPUT POWER, MOTOR WIRING AND CONTROL  
WIRING IN THREE SEPARATE METALLIC CONDUITS OR  
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.  
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL  
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE  
AND ASSOCIATED EQUIPMENT PERFORMANCE.  
WARNING  
Because the motor wiring carries high frequency  
EQUIPMENT HAZARD!  
electrical pulses, it is important that no other  
wires are run together. If the incoming power  
wiring is run in the same conduit as the motor  
wiring, these pulses can couple electrical noise  
back onto the building power grid.  
Rotating shafts and electrical equipment can be hazardous.  
It is strongly recommended that all electrical work conform  
to all national and local regulations. Installation, start-up  
and maintenance should be performed only by qualified  
personnel. Failure to follow local regulations could result in  
death or serious injury.  
At least three separate conduits must be connected to the  
panel (Figure 3.4).  
Motor control equipment and electronic controls  
are connected to hazardous line voltages.  
Extreme care should be taken to protect against  
electrical hazard.  
Power into the panel (and ground back to the  
distribution panel)  
Power from the panel to the motor and earth  
insulated motor ground  
Correct protective grounding of the equipment  
must be established. Ground currents are higher  
than 3mA.  
Control wiring  
Control wiring should always be isolated from the high  
voltage power wiring.  
A dedicated ground wire is required.  
Wear safety glasses whenever working on electric  
control or rotating equipment.  
Avoid getting metal chips into electronics.  
NOTICE!  
Make all power connections with a minimum of 60°C/  
140°F rated copper wire.  
Follow the connection procedures as illustrated in the  
drawing provided with the unit.  
BAS-SVX49A-EN  
3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Figure 3.4 Power Connections  
3-6  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
3.4.1 Component Identification & Customer Connection  
Mechanical layout drawings are intended to provide the installer or equipment user with component identification and  
location for that specific unit. Figure 3.5 represents a typical layout drawing. Table 3.8 provides definitions for drawing  
reference designators. (Not all reference designators are shown.)  
Figure 3.5 P2 Bypass Mechanical Layout Diagram  
ID  
1
Device  
24 V DC  
HPC  
F13  
Definition  
Panel 24 V DC SMPS  
ID  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
Device  
S1  
Definition  
Auto Bypass Selector Switch  
120 V AC control transformer  
Variable frequency drive  
Control Module  
2
High Pot Connector  
T1 primary fuse  
TF  
3
VFD  
EMB2  
ECB  
TB1-C  
TB1-P  
PR1  
4
CB1  
Main Circuit Breaker  
Main or Drive Disconnect  
Main fuse  
5
DS1  
Control Module  
6
F15  
Terminal block 1 - Control  
Terminal block 1 - Power  
Control Relay for M1 Contactor  
Control Relay for M2 Contactor  
Control Relay for M3 Contactor  
Under voltage module  
Top Cover  
7
F16  
Drive fuse  
8
GND  
keypad  
M1  
Ground terminal  
keypad  
9
PR2  
10  
11  
12  
13  
14  
Drive Input contactor  
Drive Output contactor  
Bypass contactor  
Overload for Motor  
Bypass indicator light  
PR3  
M2  
UVM  
TC  
M3  
OL1  
DH  
Disconnect Handle  
PL1  
Table 3.8 Reference Designator Definitions  
BAS-SVX49A-EN  
3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
Figure 3.6 P2 Non Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
3-8  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.7 P3 Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
BAS-SVX49A-EN  
3-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.8 P3 Non Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
3-10  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.9 P4 Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
BAS-SVX49A-EN  
3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.10 P4 Non Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
3-12  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.11 P5 Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
BAS-SVX49A-EN  
3-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.12 P5 Non Bypass Mechanical Layout Diagram.  
See Table 3.8 for reference designator definitions.  
3-14  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
3.4.2 Wire and Cable Access  
WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects  
before servicing. Follow proper lockout/tagout procedures  
to ensure the power cannot be inadvertently energized.  
Failure to disconnect power before servicing could result in  
death or serious injury.  
Refer to through for wire routing and termination  
locations.  
Removable access knockout covers are provided  
for cable connections (see Figure 3.13 and  
Access holes are provided for input power, motor  
leads, and control wiring.  
Figure 3.13 Bypass Panel Conduit Entry Diagram  
Run input power, motor wiring, and control  
wiring in three separate conduits for isolation.  
NOTE!  
IMPORTANT NOTE  
RUN INPUT POWER, MOTOR WIRING AND CONTROL  
WIRING IN THREE SEPARATE METALLIC CONDUITS OR  
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.  
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL  
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE  
AND ASSOCIATED EQUIPMENT PERFORMANCE.  
The drive always resides in the upper section of  
the panel. Connections to the ECB and EMB2 are  
in this area except on the P2 bypass panels.  
Power connections are typically towards the  
bottom side of the panel.  
Control wiring should be isolated from power  
components inside the unit as much as possible.  
Trane has included hardware to allow for the  
separation.  
Figure 3.14 Non Bypass Panel Conduit Entry Diagram  
See the mechanical layout drawings in through  
for connection details and recommended wire  
routing.  
BAS-SVX49A-EN  
3-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation  
Figure 3.15 P2 Panel  
Figure 3.16 P3 Panel  
3-16  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.17 P4 Panel  
BAS-SVX49A-EN  
3-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3.18 P5 Panel  
3-18  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
3.4.3 Wire Size  
WARNING  
ELECTROCUTION AND FIRE HAZARDS WITH IMPROPERLY INSTALLED AND GROUNDED FIELD WIRING!  
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST  
follow requirements for field wiring installation and grounding as described in the National Electrical Codes (NEC) and your  
local/state electrical codes. All field wiring MUST be performed by qualified personnel.  
Failure to follow these requirements could result in death or serious injury.  
NOTE!  
Make all power connections with minimum 60 or 75°C/140 or 155°F rated copper wiring for installations in North America.  
208 V AC  
Minimum Temperature  
Wire Rating " C" Copper  
Maximum Field  
Wiring Size Class B  
or C  
Panel (TR200) Non  
Bypass & Bypass  
Field Ground Wiring  
Size Class B or C  
HP (KW)  
UL Motor Current  
°
Conductor  
7.5 (5.5)  
10 (7.5)  
15 (11)  
20 (15)  
24.2  
30.8  
46.2  
59.4  
8 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
60  
60  
60  
60  
P2  
8 AWG  
4 AWG  
P3  
3 AWG  
P3 - Non Bypass P4 -  
Bypass  
25 (18.5)  
74.8  
2 AWG  
8 AWG  
60  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
88  
2 AWG  
1/0 AWG  
3/0 AWG  
4/0 AWG  
230 VAC  
8 AWG  
6 AWG  
6 AWG  
6 AWG  
60  
75  
75  
75  
P4  
P5  
114  
143  
169  
Maximum Field  
Wiring Size Class B  
or C  
Minimum Temperature  
Panel (TR200) Non  
Bypass & Bypass  
Field Ground Wiring  
Size Class B or C  
HP (KW)  
UL Motor Current  
Wire Rating "Degree C"  
Copper Conductor  
7.5 (5.5)  
10 (7.5)  
15 (11)  
20 (15)  
25 (18.5)  
22  
28  
42  
54  
68  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
8 AWG  
60  
60  
60  
60  
60  
P2  
8 AWG  
6 AWG  
4 AWG  
P3  
P4  
P5  
3AWG  
30 (22)  
80  
3 AWG  
8 AWG  
60  
40 (30)  
50 (37)  
60 (45)  
104  
130  
154  
1 AWG  
2/0 AWG  
3/0 AWG  
6 AWG  
6 AWG  
6 AWG  
75  
75  
75  
Table 3.9 Wire Size Chart, 208 and 230 V  
BAS-SVX49A-EN  
3-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation  
460 VAC  
Maximum Field  
Wiring Size Class B Wiring Size Class B  
Minimum Temperature  
Wire Rating " C" Copper  
Field Ground  
Panel (TR200) Non Bypass  
& Bypass  
HP (KW)  
UL Motor Current  
°
or C  
or C  
Conductor  
15 (11)  
20 (15)  
25 (18.5)  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
75 (55)  
100 (75K)  
125 (90)  
21  
27  
10 AWG  
8 AWG  
6 AWG  
6 AWG  
4 AWG  
3 AWG  
1 AWG  
1 AWG  
2/0 AWG  
3/0 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
8 AWG  
8 AWG  
8 AWG  
6 AWG  
6 AWG  
60  
60  
60  
60  
60  
60  
60  
60  
75  
75  
P2  
P3  
34  
40  
52  
65  
77  
P4  
P5  
96  
124  
156  
600 VAC  
Maximum Field  
Field Ground  
Minimum Temperature  
Panel (TR200) Non Bypass  
& Bypass  
HP (KW)  
UL Motor Current  
Wiring Size Class B Wiring Size Class B Wire Rating "Degree C"  
or C  
or C  
Copper Conductor  
15 (11)  
20 (15)  
25 (18.5)  
30 (22)  
40 (30)  
50 (37)  
60 (45)  
75 (55)  
100 (75)  
125 (90)  
17  
22  
27  
32  
41  
52  
62  
77  
99  
125  
10 AWG  
10 AWG  
8 AWG  
8 AWG  
6 AWG  
4 AWG  
3 AWG  
1 AWG  
1 AWG  
2/0 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
8 AWG  
8 AWG  
8 AWG  
6 AWG  
60  
60  
60  
60  
60  
60  
60  
60  
60  
75  
P2  
P3  
P4  
P5  
Table 3.10 Wire Size Chart 460 and 600 V  
3.4.4 Wire Type Rating  
The wire style rating specifications are provided inTable 3.9 and Table 3.10  
3.4.5 Terminal Tightening Torques  
Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13  
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover.  
See Table 3.15 for a sample of the torque and wire rating data.  
3-20  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
BAS-SVX49A-EN  
3-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
3-22  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
BAS-SVX49A-EN  
3-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
3-24  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Field Connection  
L1, L2, L3/Ground  
2T1, 2T2, 2T3/Ground  
TB1  
Tightening Torque lb-in (N-m)  
25 (2.8) 25 (2.8)  
Temperature & Type Rating  
Use 75  
Use 75  
Use 75  
°
°
°
C Copper Conductor  
C Copper Conductor  
C Copper Conductor  
25 (2.8) 25 (2.8)  
25 (2.8) 25 (2.8)  
Table 3.15 Sample Tightening Torque and Wire Rating Label  
3.4.6 Input Line Connection  
WARNING  
INDUCED VOLTAGE!  
WARNING  
Run output motor cables from multiple drives separately.  
Induced voltage from output motor cables run together  
can charge equipment capacitors even with the equipment  
turned off and locked out. Failure to run output motor  
cables separately could result in death or serious injury.  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects  
before servicing. Follow proper lockout/tagout procedures  
to ensure the power cannot be inadvertently energized.  
Failure to disconnect power before servicing could result in  
death or serious injury.  
NOTE!  
Run input power, motor wiring and control wiring in three  
separate metallic conduits or raceways for high frequency  
noise isolation. Failure to isolate power, motor and control  
wiring could result in less than optimum drive and  
associated equipment performance.  
CAUTION  
RUN INPUT POWER, MOTOR WIRING AND CONTROL  
WIRING IN THREE SEPARATE METALLIC CONDUITS OR  
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.  
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL  
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE  
AND ASSOCIATED EQUIPMENT PERFORMANCE.  
CAUTION  
RUN INPUT POWER, MOTOR WIRING AND CONTROL  
WIRING IN THREE SEPARATE METALLIC CONDUITS OR  
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.  
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL  
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE  
AND ASSOCIATED EQUIPMENT PERFORMANCE.  
Connect 3-phase AC input power wire to  
terminals L1, L2, and L3. See the connection  
drawing inside the cover of the unit.  
Depending on the configuration of the  
equipment, input power may be connected to a  
circuit breaker or disconnect switch.  
Torque terminals in accordance with the  
information provided inTable 3.11 and Table 3.13  
on the label inside the panel cover.  
Use with Isolated Input Source. Many utility  
power systems are referenced to earth ground.  
Although not as common, the input power may  
be an isolated source. All drives may be used  
with an isolated input source as well as with  
ground reference power lines.  
3.4.7 Motor Wiring  
WARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects  
before servicing. Follow proper lockout/tagout procedures  
to ensure the power cannot be inadvertently energized.  
Failure to disconnect power before servicing could result in  
death or serious injury.  
BAS-SVX49A-EN  
3-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
Connect the 3-phase motor wiring to bypass  
terminals T1 (U), T2 (V), and T3 (W). See the  
connection drawing inside the cover of the unit.  
Connect the ground wire directly to a reliable  
earth ground. Grounding studs are provided on  
the back plate of the panel for grounding.  
Depending on the configuration of the  
equipment, motor wiring may be connected to  
overload or terminal block.  
Do not use conduit connected to the panel as a  
replacement for a ground wire.  
A high strand count ground wire is preferred for  
dissipating high frequency electrical noise.  
Torque terminals in accordance with the  
information provided on the connection diagram  
inside the cover of the unit.  
Keep the ground wire connections as short as  
possible.  
Motor wiring should never exceed the following  
maximum distances: 300m (1000 ft) for  
unshielded, 150m (500 ft) for shielded.  
Ground the motor to the panel with insulated  
wire run inside metal conduit with motor leads.  
Motor wiring should always be as short as  
practical.  
3.4.9 Control Wiring  
WARNING  
3.4.8 Grounding (Earthing)  
Electrocution and Fire Hazards with Improperly Installed  
and Grounded  
WARNING  
Field Wiring!  
Improperly installed and grounded field wiring poses FIRE  
& ELECTROCUTION hazards. To avoid these hazards, you  
MUST follow requirements for field wiring installation and  
grounding as described in the National Electrical Codes  
(NEC) and your local/state electrical codes. All field wiring  
MUST be performed by qualified personnel. Failure to  
follow these requirements could result in death or serious  
injury.  
GROUNDING HAZARD!  
for operator safety, it is important to ground the option  
panel properly. Failure to do so could result in death or  
serious injury.  
WARNING  
ELECTROCUTION AND FIRE HAZARDS WITH  
IMPROPERLY INSTALLED AND GROUNDED FIELD  
Detailed instructions for terminal connection, control  
wiring installation, and operation are shown in Section 5  
Electromechanical Bypass (EMB2) Operation and Section 6  
Electronically Controlled Bypass (ECB) Operation.  
WIRING!  
Improperly installed and grounded field wiring poses FIRE  
& ELECTROCUTION hazards. To avoid these hazards, you  
MUST follow requirements for field wiring installation and  
grounding as described in the National Electrical Codes  
(NEC) and your local/state electrical codes. All field wiring  
MUST be performed by qualified personnel. Failure to  
follow these requirements could result in death or serious  
injury.  
It is recommended that control wiring is rated for  
600 V for 480 V and 600 V drives and 300 V for  
200-240 V drives.  
Isolate control wiring from high power  
components in the drive.  
NOTE!  
See 3.4.2 Wire and Cable Access for details.  
It is the responsibility of the user or certified electrical  
installer to ensure correct grounding (earthing) of the  
equipment in accordance with national and local electrical  
codes and standards.  
Follow all local and national codes for proper  
electrical equipment grounding (earthing).  
Correct protective grounding of the equipment  
must be established. Ground currents are higher  
than 3 mA.  
A dedicated ground wire is required for input  
ground.  
3-26  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation  
Programming  
Serial communication point maps, parameter settings, and  
other details for bypass option functionality are included in  
the serial communication materials supplied with the unit.  
1
2
3
4
Figure 3.19 Control Terminals Location  
1.  
2.  
3.  
4.  
EIA-485 terminal  
Jumper wire  
Control terminals  
Grounded restraining clips  
3.4.10 Serial Communication Bus  
Connection  
The ECB reports serial communication data to host systems  
through the drive. Connection to the serial communication  
network is made either through the EIA-485 terminals on  
the drive (see figure above) or, for other protocols,  
terminals located on the communication option card. For  
option card connection, see the option card instructions  
provided with the unit.  
For ECB serial communication protocols using the  
EIA-485 terminals, make connections in the  
following manner.  
NOTE!  
It is recommended to use braided-shielded, twisted-pair  
cables to reduce noise between conductors.  
1.  
Connect signal wires to terminal (+) 68 and  
terminal (-) 69 on control terminals of drive. (See  
the drive support materials for wire size and  
tightening torque.)  
2.  
3.  
Terminate shield to grounded restraining clip  
provided by stripping wire insulation at point of  
contact.  
If shielded cabling is used, do not connect the  
end of the shield to terminal 61.  
BAS-SVX49A-EN  
3-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
3.4.11 Drive Control Terminals  
Definitions of the drive terminals are summarized in  
Connector 1 provides four digital inputs; two  
selectable digital inputs or outputs, 24 V DC  
terminal supply voltage, and a common for  
optional customer supplied 24 V DC voltage.  
Serial communications use EIA-485 connector 2  
with terminal 68 (+) and 69 (-).  
Connector 3 provides two analog inputs, one  
analog output, 10 V DC supply voltage, and  
commons for the inputs and output.  
Figure 3.20 Removable Drive Connectors and Terminals  
A USB port, connector 4, is also available for use  
with the available on the Trane website.  
Also provided are two Form C relay outputs that  
are in various locations depending upon the drive  
configuration and size.  
Terminal No.  
Function  
01, 02, 03, 04, Form-C relay output. Useable for AC or DC voltage and resistive or inductive loads. See drive support materials for  
05, 06  
12, 13  
details on voltage and current ratings and relay location.  
24 V DC digital supply voltage. Useable for digital inputs and external transducers. To use the 24 V DC for digital input  
common, program parameter 5-00 for PNP operation. Maximum output current is 200 mA total for all 24V loads.  
Digital inputs. Selectable for NPN or PNP function in parameter 5-00. Default is PNP.  
Digital inputs or outputs. Programmable for either. Parameter 5-01 for terminal 27 and 5-02 for 29 selects input/output  
function. Default setting is input.  
18, 19, 32, 33  
27, 29  
20  
39  
42  
Common for digital inputs. To use for digital input common, program parameter 5-00 for NPN operation.  
Common for analog output.  
Analog output. Programmable for various functions in parameter 6-5*. The analog signal is 0 to 20 mA or 4 to 20 mA at  
a maximum of 500  
Ω.  
50  
10 V DC analog supply voltage. 15 mA maximum commonly used for a potentiometer or thermistor.  
Analog input. Selectable for voltage (0-10 V) or current (0- or 4-20 mA). Closed is for current and open is for voltage.  
Switches are located on the drive control card behind the removable keypad. See drive support materials for details.  
Common for analog inputs.  
53, 54  
55  
61  
Common for serial communication. Do not use to terminate shields. See drive support materials for proper shield  
termination.  
68 (+), 69 (-)  
RS-485 interface. When the drive is connected to an RS-485 serial communication bus, a drive control card switch is  
provided for termination resistance. ON for termination and OFF for no termination. See drive support materials for  
details.  
Table 3.16 Drive Control Terminals Functions  
3-28  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Start Up  
4 Start Up  
1.  
Input power to the unit must be OFF and locked  
out per OSHA requirements. Do not rely on panel  
disconnect switches.  
11.  
12.  
For multiple winding motors, the motor must be  
wired on run winding, not start winding.  
Confirm motor FLA is equal to or less than  
maximum panel output current. Some motors  
have higher than normal NEMA currents.  
WARNING  
HAZARDOUS VOLTAGE!  
13.  
14.  
Check that the overload relay is set for FLA of  
connected motor. Service factor is built into  
overload relay. Relay trips at 120% of setting.  
if input and output connections have been connected  
improperly, there is potential for high voltage on these  
terminals. If power leads for multiple motors are  
improperly run in same conduit, there is potential for  
leakage current to charge capacitors within the panel, even  
when disconnected from line input. For initial start up,  
make no assumptions about power components. Follow  
pre-start procedures described below. Failure to do so  
could result in death, serious injury or damage to  
equipment.  
For drive start up procedures, see drive  
instruction manual.  
2.  
Use AC voltmeter to verify there is no voltage on  
input terminals L1, L2, and L3, phase-to-phase  
and phase-to-ground, and output terminals T1,  
T2, and T3, phase-to-phase and phase-to-ground.  
3.  
4.  
Use ohmmeter to confirm continuity of the motor  
by measuring T1-T2, T2-T3, and T3-T1.  
Use ohmmeter to confirm open on input by  
measuring L1-L2, L2-L3, and L3-L1. Note that if an  
isolation transformer is between the power  
source and panel, continuity will be present. In  
this case, visually confirm that motor and power  
leads are not reversed.  
5.  
6.  
Inspect the panel for loose connections on  
terminals.  
CheckTable 3.9 and Table 3.10 for proper ground  
wire: panel to main building distribution ground,  
and panel to motor ground.  
7.  
8.  
Confirm control connections terminated per  
connection diagrams supplied with the  
equipment.  
Check for external devices between drive panel  
output and motor. It is recommended that no  
devices be installed between the motor and  
drive.  
9.  
Record motor nameplate data; hp, voltage, full  
load amps (FLA), and RPM. It will be needed to  
match motor and drive later on.  
10.  
Confirm that incoming power voltage matches  
drive label voltage and motor nameplate voltage.  
BAS-SVX49A-EN  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Start Up  
4.1.1 Inspection Prior to Start Up  
Before applying power to the unit, inspect the entire installation as detailed in Table 4.1.  
Inspect For  
Description  
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that may reside on input  
power side of drive or output side to motor. Examine their operational readiness and ensure they are ready in  
all respects for operation at full speed. Check function and installation of pressure sensors or encoders (etc.)  
used for feedback to drive. Remove power factor correction caps on motor, if present.  
Ensure that input power, motor wiring, and control wiring are in three separate metallic conduits for high  
frequency noise isolation. Failure to isolate power, motor, and control wiring could result in less than optimum  
drive and associated equipment performance.  
Auxiliary equipment  
Cable routing  
Control wiring  
Check for broken or damaged wires and connections. Check the voltage source of the signals, if necessary. The  
use of shielded cable or twisted pair is recommended for serial communication. Ensure the shield is terminated  
correctly.  
EMC considerations  
Environmental  
conditions  
Check for proper installation with regard to electromagnetic capability.  
See panel label for the maximum ambient operating temperature. Humidity levels must be less than 95% non-  
condensing. Attitude less than 3300 feet.  
Fusing and circuit  
breakers  
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are in the open  
position.  
The panel requires a dedicated ground wire from its chassis to the building ground. It is required that the  
motor be grounded to the panel chassis. The use of conduit or mounting of the panel to a metal surface is not  
considered a suitable ground. Check for good ground connections that are tight and free of oxidation. Run  
insulated motor ground wire back to panel in conduit with motor wires.  
Grounding  
Input and output  
power wiring  
Check for loose connections. Check for proper fusing or circuit breakers.  
Panel interior must be free of dirt, metal chips, moisture, and corrosion. Check for harmful airborne contam-  
inates such as sulfur based compounds.  
Panel interior  
Proper Cooling  
Clearance  
Switches  
Panels require top and bottom clearance adequate to ensure proper air flow for cooling. See Figure 3.2 and  
Ensure that all switch and disconnect settings are in the proper position.  
Look for any unusual amount of vibration the equipment may be subjected to when mounting panel.  
Vibration  
Table 4.1 Inspection prior to Startup  
1.  
2.  
Perform pre-startup procedure.  
4.1.2 Start Up Procedure  
Ensure that all operator devices are in the OFF  
position. The main disconnect switch on the front  
of the electromechanical bypass panel must be in  
the OFF position. The panel door should be  
closed.  
In the following procedures, changing the equipment  
between drive mode and bypass mode is required.  
Changing modes is different for the ECB and EMB2. The  
ECB uses pushbuttons on the drive keypad while the EMB2  
uses a selector switch on the front of the panel. Be familiar  
with the operation of these devices prior to start up.  
3.  
4.  
Keep main disconnect switch in the OFF position  
and apply voltage to the panel.  
Confirm that input line voltage is balanced within  
3%. If not, correct the input voltage imbalance  
before proceeding.  
WARNING  
HAZARDOUS VOLTAGE!  
The panel contains dangerous voltages when connected to  
line voltage. Installation, start-up and maintenance should  
be performed only by qualified personnel. Failure to  
perform installation, start-up and maintenance by qualified  
personnel only could result in death or serious injury.  
4-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Start Up  
within FLA of drive and balanced within  
3%. If incorrect, see 7.1 Start Up Trouble-  
shooting for isolation procedures.  
CAUTION  
MOTOR START!  
Ensure that motor, system, and any attached equipment is  
ready for start. Failure to do so could result in personal  
injury or equipment damage.  
10.  
Check motor current in bypass mode on the  
motor terminals.  
10a Put the unit in bypass mode.  
5.  
If a bypass is connected, place the Mode Selector  
Switch in drive mode. Apply power by turning  
the main disconnect switch to the ON position.  
10b Check full load amps on terminals T1,  
T2, and T3. Verify the motor amps are  
within motor FLA rated current and  
balanced within 3%. If incorrect, see  
7.1 Start Up Troubleshooting for isolation  
procedures.  
6.  
7.  
Enter drive programming data per the drive  
instruction manual.  
Check motor rotation direction in drive control as  
follows.  
Operation for details.  
7a  
7b  
Put panel in drive mode.  
Hand start drive at minimum speed (see  
drive instruction manual for details).  
11.  
Check operation of any optional functions to  
confirm that they work, as applicable. Options  
may include run permissive, fire mode, common  
start/stop, or others.  
7c  
Confirm directional rotation.  
7d  
If incorrect, stop the drive, remove  
power, and lock out.  
12.  
13.  
Exercise the safety circuit and verify that the unit  
stops running.  
7e  
Reverse connection of T1 & T2 motor  
leads. Do not change incoming power  
leads.  
Exercise the start/stop circuit and verify that the  
unit starts and stops with the system in the Auto  
mode of operation.  
7f  
Remove lockout and apply power.  
Confirm directional rotation.  
7g  
8.  
Check motor rotation direction in bypass as  
follows.  
8a  
8b  
8c  
Momentarily bump motor in bypass.  
Confirm directional rotation.  
If incorrect, stop drive, remove power,  
and lock out.  
8d  
Reverse connection of L1 & L2 input  
power leads to the main disconnect. Do  
not change motor leads.  
8e  
Confirm directional rotation.  
9.  
Check motor current in drive mode on the motor  
terminals.  
9a  
9b  
Put the unit in drive mode.  
Check motor current on motor terminals  
T1, T2, and T3. Verify the motor amps  
are within drive and motor rated current  
and are balanced within 3%. If incorrect,  
see 7.1 Start Up Troubleshooting for  
isolation procedures.  
9c  
Check input current on input terminals  
L1, L2, and L3. Verify that current is  
BAS-SVX49A-EN  
4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start Up  
4-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electromechanical Bypass (EMB2) Operation  
5 Electromechanical Bypass (EMB2) Operation  
5.1.1 Typical Control Connections for Common HVAC Applications  
Drive Terminal  
Parameter Number  
Parameter Name  
Digital I/O Mode  
Value Number  
Value Name  
PNP  
Function  
External Interlock  
External Interlock  
Auto Bypass  
27  
27  
500  
501  
0
Term 27 mode  
0
Input  
29  
502  
Term 29 Mode  
1
Output  
18  
510  
Term 18 digital input  
Term 19 digital input  
Term 27 digital input  
Term 29 digital output  
Relay 1 function  
8
Start  
Common run/stop  
Run Permissive  
External Interlock  
Auto Bypass  
19  
511  
52  
Run Permissive  
External Interlock  
No Alarm  
27  
512  
7
160  
29  
531  
01 & 02  
01 & 02  
540 [0]  
540 [0]  
167  
Start Command Active  
Off Delay  
Run Permissive  
Run Permissive  
Relay 1 off delay  
0.00 seconds  
Table 5.1 EMB2 Default Parameter Settings for Common HVAC Applications  
If the drive is reinitialized, be sure that these settings are maintained or reset for proper bypass.  
Name  
Remote Drive Start (with common start/stop)  
Remote Drive Start (without common start/stop)  
Motor Running on Drive  
Run Request (for run permissive)  
Run Enable (for run permissive)  
Safety Stop  
Function  
Input Command  
Input Command  
Output Status  
Drive Terminals  
EMB2 X59  
EMB2 X55  
3, 4  
13, 18  
04, 05, 06  
Output Command  
Input Command  
Input Command  
Output Status  
11, 12  
1, 2  
5, 6  
Drive Fault  
5, 6, 7  
Fire Mode  
Input Command  
Output Status  
7, 8  
Drive Mode  
1, 2  
3, 4  
Bypass Mode  
Output Status  
Fire Mode  
Output Status  
9, 10  
Table 5.2 Common Functions for Controlling Motor using Bypass and Typical Terminal Connections.  
Commands enable drive functions. Status reports describe conditions, but do not enable a function.  
BAS-SVX49A-EN  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Electromechanical Bypass (E...  
Figure 5.1 Customer Side EMB2 Control Card Terminal Connections  
5-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electromechanical Bypass (EMB2) Operation  
All OFF = no auto bypass operation  
Switch 1 only ON = 30 sec. delay  
Switch 2 only ON = 60 sec. delay  
Switch 3 only ON = 300 sec. delay (maximum)  
Switch 4 = Always OFF  
5.1.2 EMB2 Auto Bypass  
General Information  
Auto bypass allows a fault condition in the drive to  
activate running the motor in bypass without operator  
intervention. Activation of the function is through setting  
DIP switches (S100) located on the EMB2 bypass control  
card (see Figure 5.1). A fault condition enables a delay  
timer prior to tripping the drive into bypass. The fault trip  
and running in bypass are reported as output from the  
bypass control card. The auto bypass function is built in.  
5.1.3 EMB2 Common Run/Stop  
General Information  
The common run/stop function provides remote run and  
stop control of the motor in bypass. Without common run/  
stop, the motor would automatically run at full speed  
whenever the bypass is activated. The remote signal  
provides drive control as well as bypass control, making  
this one input common to both. Common run/stop is  
enabled by factory default. When used with the run  
permissive function, common run/stop permits run request  
operation in bypass.  
Prior to Enabling Auto Bypass  
Complete the start-up procedure to verify that  
the motor rotation direction in bypass is correct  
and that the system is ready in all respects for  
continuous full speed operation in bypass.  
WARNING  
HAZARDOUS VOLTAGE!  
Remove power to the bypass panel before setting auto  
bypass dip switch settings. Bypass can contain high  
voltage. Failure to remove power to bypass panel before  
setting dip switches could result in death or serious injury.  
Prior to Enabling Common Run/Stop  
Complete the start-up procedure to verify motor  
rotation direction in bypass is correct and that  
the system is ready in all respects for continuous  
full speed operation in bypass.  
Operation  
Operation  
With the bypass selector switch in drive and auto  
bypass enabled, a fault signal from the drive will  
activate the auto bypass timer.  
A user supplied remote start command wired to  
connector X55, terminals 3 and 4 initiates remote  
bypass operation. With common run/ stop,  
bypass mode cannot be activated by hand on the  
drive keypad or by serial communication.  
If the fault clears before the time delay is  
complete, the motor remains operating in drive  
mode. This allows temporary faults, such as a  
momentary under or over voltage, to clear  
without transferring the system to bypass.  
Common Run/Stop Setup  
Wire input terminals 3 and 4 on connector X55  
per the system application.  
If the timer completes its cycle before the fault  
clears, the panel trips into bypass mode and the  
motor runs at constant full speed from line input  
voltage.  
To Disable Common Run/Stop  
Common run/stop is enabled by factory default  
when ordered.  
In bypass, the motor will stop if safety or motor  
overload conditions are exceeded.  
To disable the feature, turn switch four on dip  
switch S105. This allows the bypass to start when  
the bypass switch is placed in the bypass  
position.  
Once auto bypass is activated, the only way to  
reset the unit back to drive is by operator  
intervention. Ensure that the fault has been  
cleared, then rotate the bypass switch to the OFF  
position momentarily before setting it back to the  
drive position. This resets the drive and fault  
timer.  
Remove wire from terminal 18 of the drive  
control terminal and insulate the end of the wire  
to prevent shorting. This is required or the drive  
will always have a run command.  
If applicable, connect remote run/stop input to  
terminals 12 and 18 on the drive control card.  
Auto Bypass Function Setup  
Enable auto bypass by closing one or more DIP switches  
on switch S100 located on the bypass control card. (Times  
are approximate.)  
BAS-SVX49A-EN  
5-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Electromechanical Bypass (E...  
5.1.4 EMB2 Run Permissive  
5.1.5 EMB2 Overload  
General Information  
General Information  
Run permissive allows a remote signal to notify the drive  
to start, indicating the system is safe to operate. Run  
permissive works in drive or bypass mode. Run permissive  
is enabled by factory default and can be disabled by  
switching dip switch #4 on S105 to the on position or  
placing a jumper wire between terminal 1 and 2 of the  
X55 customer connector.  
The overload device provides overcurrent protection for  
the motor when running in bypass. The thermally activated  
overload monitors motor current and trips to remove  
power to the motor if a sustained over-current condition  
exists. A Class 20 overload is standard with a variable  
setting for motor current. Test and reset buttons are also  
provided. In drive mode, the drive provides current sensing  
and trip protection. Fuses provide quick action for high  
over current conditions.  
Prior to Enabling Run Permissive  
Complete the start-up procedure to verify that  
Prior to Enabling Overload  
motor rotation direction in bypass is correct and  
that the system is ready in all respects for  
continuous full speed operation in bypass.  
Verify that the overload current dial setting  
matches the motor FLA rating on the motor  
nameplate.  
Verify that the drive is programmed for the run  
permissive function. See the drive support  
manual provided for information on  
If the motor FLA is greater or less than the range  
of the current dial, reconfirm that the motor hp  
and voltage are within the option panel (and  
drive) rating. If greater than the FLA rating,  
replace the panel with one of a proper rating.  
programming the run permissive function.  
Operation  
A start command can be from local hand start on  
the drive keypad or a remote auto start signal  
through digital input connector X55 terminals 3  
and 4, or via the serial communications input.  
CAUTION  
MOTOR DAMAGE!  
Repeated attempts to reset an overload can cause motor  
damage. Correct the overload condition and let the  
overload and motor return to normal operating  
temperature before resetting. See motor manufacturer’s  
recommendations for time between start attempts. Failure  
to correct the overload condition and let the motor return  
to normal operating temperature could cause motor  
damage.  
In response to a start command, an output  
request is sent from X55 terminals 11 and 12 to  
the external equipment (to activate a valve or  
damper, for example).  
When a return run signal on X55 terminals 1 and  
2 is received, the motor is started in either drive  
or bypass mode, depending upon the bypass  
switch position.  
Operation  
Run Permissive Function Setup  
Overloads are rated by class. The class is defined by the  
NEC to determine the maximum time to trip. A Class 20  
overload, for example, has a typical trip delay of 20 sec. or  
less at 600% current and normal operating temperature.  
This allows for high motor inrush current for 20 sec. while  
the motor is ramping up to synchronous speed. The trip  
time, however, is based on the percentage of overload.  
The higher the overload, the shorter the trip time. It is  
important that the overload class not exceed the motor  
class rating or motor damage could occur.  
Remove the factory-installed jumper wire on  
connector X55, terminals 1 and 2.  
Wire the output run request to connector X55,  
terminals 11 and 12.  
Wire the input run permission to connector X55,  
terminals 1 and 2 per the system application.  
Disable Run Permissive  
Run permissive is enabled by factory default  
when ordered.  
Overload Function Setup  
To disable the run permissive function, jumper  
between terminals 1 and 2 on connector X55 or  
use dip switch 4 on 5105.  
Set the overload current dial to the FLA of the  
motor. DO NOT add the service factor of the  
motor into the setting. A service factor of 120%  
for Class 20 is designed into the overload.  
Pressing the test pushbutton verifies the  
operation of the overload. The overload should  
5-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electromechanical Bypass (EMB2) Operation  
trip when pressed. Use the reset pushbutton to  
reset the overload after the test.  
5.1.7 EMB2 Fire Mode  
General Information  
Reset is used to reset the overload after it trips. If  
the overload is still hot, wait until the motor  
reaches normal operating temperature before  
resetting. The overload offers a manual (hand) or  
auto reset selection. It is highly recommended to  
operate in the manual factory setting to prevent  
the risk of damage to the motor.  
Fire mode runs the motor at full speed in bypass and is  
intended to ignore common safety, overload, and mode  
selector switch inputs in emergency situations. The motor  
will continue to run in bypass until fire mode is removed  
or the unit fails.  
Prior to Enabling Fire Mode  
TRIP  
Complete the start-up procedure to verify motor  
MANUAL  
rotation direction in bypass is correct and that  
the system is ready in all respects for continuous  
full speed operation in bypass.  
AUTO  
TEST  
RESET  
Operation  
Activation of fire mode is accomplished by  
closing connector X55, input terminals 7 and 8.  
98NO  
95NC  
97NO  
T1  
96NC  
T3  
When activated, a relay overrides the safety  
circuit, motor overload, and bypass switch (SW1)  
position.  
T2  
Figure 5.2 Sample Overload Device  
Fire mode is deactivated only when removed or  
fuses blow.  
5.1.6 EMB2 Safety Interlock  
Fire mode status can be reported through  
connector X55, terminals 9 and 10, a normally  
open dry contact that closes when fire mode is  
active.  
General Information  
The safety interlock feature prevents the drive or bypass  
from operating. For operation in drive or bypass, the safety  
interlock input contact must be closed. Only a fire mode  
command to run in bypass overrides this function. Safety  
inputs include, but are not limited to, high and low  
pressure limit switches, fire alarm, smoke alarm, high and  
low temperature switches, and vibration sensors.  
Fire Mode Function Setup  
Wire the fire mode input to connector X55,  
terminals 7 and 8.  
Wire the fire mode status output to connector  
X55, terminals 9 and 10.  
Operation  
When an external safety input closes, the panel is in  
operational mode. When open, power is interrupted to the  
drive output and bypass contactors and relays, and the  
bypass ignores all run commands except for fire mode  
operation. When power is interrupted in drive mode, the  
drive display indicates an external fault, meaning the  
problem is external to the drive. In some instances, a fault  
can be caused by a failure within the panel, which will still  
be reported as an external fault from the drive. A factory  
installed jumper allows the unit to operate when no safety  
input is connected. This jumper must be removed when  
connecting a safety interlock in the circuit.  
5.1.8 EMB2 Fault Reporting  
General Information  
A fault indication is provided if the drive experiences a  
fault or bypass input power is lost. The EMB2 bypass  
control card monitors the drive fault output for status  
reporting. The fault contacts are fail-safe, meaning that if  
power is removed, a fault condition is automatically  
reported. Fault status is not monitored in bypass  
operation.  
Operation  
For the EMB2, fault reporting is monitored through a  
Form-C relay (RL2) on the bypass control board. The relay  
reports a fault on connector X59 terminals 5, 6, and 7. In  
normal operation, the relay is powered and terminal 5 is  
closed with terminal 7 open. In a fault condition, power to  
the relay is lost and the relay positions automatically  
reverse, signaling the fault condition. Terminal 6 is  
common to both.  
Safety Interlock Function Setup  
Remove factory-installed jumper between  
terminals 5 and 6 on connector X55  
Wire safety input to terminals 5 and 6 on  
connector X55  
BAS-SVX49A-EN  
5-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Electromechanical Bypass (E...  
Fault Reporting Function Setup  
Fault reporting status is connected to connector  
X55, output terminals 5, 6, and 7.  
5.1.9 EMB2 Switches  
Mode selector switch.  
A panel mounted Drive/OFF/Bypass/Test selector switch is  
used to electrically select whether the motor is controlled  
by the drive (M1 and M2 contactors), connected to the  
full-speed bypass (M3 contactor), or disconnected from  
both. The test position allows for operation in bypass while  
providing power to the drive (M1 and M3). See Figure 1.2.  
5-6  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electronically Controlled Bypass (ECB) Opera-  
tion  
6 Electronically Controlled Bypass (ECB) Operation  
1.  
2.  
3.  
4.  
keypad Display  
Menu keys  
6.1 Electronically Controlled Bypass (ECB)  
Operation  
Menu navigation  
Control keys  
6.1.1 Overview  
Programming and display are provided by the drive’s local  
control panel. (keypad See Figure 6.1)  
Information provided in this section is intended to enable  
the user to connect control wiring, program functions, and  
operate the ECB and its optional features.  
An important feature of the ECB is the ability to accept  
commands from a building automation system (BAS) and  
to report operational status in return.  
The ECB contains a local processor located on the ECB  
control card, which interacts with the drive’s control logic  
for programmable options, remote command input, and  
output status reporting. Rather than panel-mounted  
operator-activated selector switches, as on the electrome-  
chanical option panel, ECB control is provided by the  
drive’s processor.  
Control wiring connections are made to either the drive’s  
control terminals (see Figure 3.20) or terminals provided on  
the ECB control card (see Figure 6.2). Drive analog and  
digital I/O terminals are multifunctional and need to be  
programmed for their intended use while the terminals on  
the ECB control card are dedicated for specific functions.  
The ECB also contains a power supply which provides back  
up for the drive’s logic circuitry, so even if the drive loses  
power, the control and communication functions are  
maintained.  
Programming options for drive terminals are seen by  
pressing the [Main Menu] key or [Quick Menu] key on the  
keypad keypad. Parameter menus appear in the keypad  
display. The arrow keys are used for navigating through  
the parameter lists. Terminal functions are programmed in  
parameter group 5-**. (See Table 6.1 for factory default  
parameter settings for drives with an ECB.) Bypass  
functions are programmed in parameter group 31-** (see  
Table 6.4). See the drive’s supporting materials for detailed  
programming instructions.  
Figure 6.1 keypad  
BAS-SVX49A-EN  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Electronically Controlled B...  
Parameter  
5-01  
Parameter name  
Term 27 Mode  
Term 29 Mode  
Setting title  
Input  
Setting  
Function  
0
1
Customer Interlock  
Auto bypass  
5-02  
Output  
5-10  
5-11  
Term 18 digital input  
Term 19 digital input  
Term 27 digital input  
Term 29 digital output  
Relay 1 function  
Start  
8
Common run/stop  
Run Permissive  
Customer Interlock  
Auto bypass  
Run Permissive  
External Interlock  
No Alarm  
52  
5-12  
7
5-31  
160  
167  
0.00 S  
5-40(0)  
5-40(0)  
Start Command Active  
Off Delay  
Run Permissive  
Run Permissive  
Relay 1 off delay  
Table 6.1 Parameter Group 5-** Factory Default Settings  
6.1.2 ECB Control Card  
The ECB control card (see Figure 6.2) provides input connector X57 for commanding bypass operation remotely and output  
connector X59 for reporting the bypass mode of operation, either drive mode or running in bypass.  
See Table 6.2 for ECB control card terminal types and functions.  
1
2
3
4
1.  
2.  
3.  
4.  
Terminal X58  
Terminal X56  
Terminal X57  
Terminal X59  
6-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Electronically Controlled Bypass (ECB) Opera-  
tion  
Figure 6.2 ECB Control Card Terminal Connections  
BAS-SVX49A-EN  
6-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electronically Controlled B...  
Input Conn.  
Term.  
Function  
Digital input for safety stop  
Common  
Type  
User supplied dry contact  
User supplied dry contact  
1
2
3
4
5
6
7
8
9
Factory use only  
No function  
Factory use only  
Factory use only  
X57  
Factory use only  
Digital input for remote bypass enable  
User supplied dry contact  
Digital input overrides system to Bypass Mode ignoring all User supplied dry contact  
other inputs and commands, except for safety stop on  
terminal 1.  
10  
Digital input for remote overload reset  
Function  
User supplied dry contact  
Output Conn.  
Term.  
1
Common for binary I/O  
2
Common for binary I/O  
3
No function  
4
No function  
X59  
5
Digital output indicates panel is in Drive Mode.  
Digital output indicates panel is in Bypass Mode  
Common for binary I/O  
24 VDC digital output  
24 VDC digital output  
6
7
8
Common for binary I/O  
Relay Output  
X56  
Term.  
1
Function  
N.O. contact for running in bypass or drive  
N.O. contact for running in bypass or drive  
Factory use only  
Relay output for user  
Relay output for user  
2
3-12  
Table 6.2 ECB Card Terminals  
6-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electronically Controlled Bypass (ECB) Opera-  
tion  
6.1.3 ECB Drive or Bypass Selection  
Use the keypad and display to switch between the motor running in drive mode or bypass when operating in local control.  
The display in operating mode is shown below.  
1. Press [Drive Bypass]. Display changes to show  
bypass and drive mode options (shown in Step 2).  
1 = Display  
2 = Info key  
3 = Drive/Bypass Option Key  
2. When running in drive mode, press [OK] on  
keypad to activate bypass mode or press CANCEL  
to remain in drive mode. In bypass, the motor will  
run at full speed.  
3. When running in drive mode, press [OK] on the  
keypad to activate drive mode or press [Cancel] to  
remain in bypass mode.  
4. Press [Status] to return to drive status display.  
BAS-SVX49A-EN  
6-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electronically Controlled B...  
NOTE!  
Pressing [Info] at any time displays tips and guidelines for  
performing the function currently activated.  
6-6  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electronically Controlled Bypass (ECB) Opera-  
tion  
6.1.4 ECB Programming  
Use the keypad and display for programming ECB functional options. All programming options appear in numbered  
parameters. Parameters are arranged in groups by related functions. Programming is performed by accessing the  
parameters through a menu and selecting from displayed options or entering numerical values. See the drives’ supporting  
materials for detailed programming instructions.  
Access parameters to program bypass functions in accordance with the following instructions:  
1. Press [Main Menu] on the keypad to access parameter  
groups. (Note that the memory function of the menu returns  
to the most recently used function. Use [Back] to return to the  
main menu index when necessary.)  
2. Press [ ] or [ ] to scroll through parameter groups. A  
dotted outline surrounds the selected group. Bypass options  
are found in parameter group 31-** Bypass.  
3. Press [OK] to enter the selected parameter group.  
4. Press [ ] or [ ] to scroll through the parameter list.  
5. Press [OK] again to enter programming mode, which allows  
changing parameter options or data. Option is inverse  
highlighted.  
6. Press [ ] or [ ] to scroll through programmable options.  
7. Press [OK] again to activate the selection or [Cancel] to  
cancel.  
8. For entering numeric values, press [  
] or [] to select  
numeric digit, then Press [ ] or [ ] to scroll through digit  
numbers 0-9. Selected digit is inverse highlighted.  
9. Press [OK] to activate the selection or [Cancel] to cancel.  
10. Press [Status] to return to operational display data or [Back]  
to return to parameter menu options.  
BAS-SVX49A-EN  
6-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electronically Controlled B...  
6.1.5 ECB Hand/OFF/Auto  
General Information  
The [Hand on], [Off Reset], and [Auto on] keys on the keypad control both the drive and bypass (see Figure 6.1). [Drive  
Bypass] allows the user to locally select drive or bypass mode of operation. It does not necessarily start or stop the motor.  
Prior to Enabling Hand/Off/Auto  
Complete the start-up procedure to verify that motor rotation direction in bypass is correct and that the system is  
ready in all respects for continuous full speed operation in bypass.  
Programming Key Functions  
For [Off Reset] and [Drive Bypass], Table 6.3 lists the parameters that select functions for the control keys. A password  
protection can also be assigned in these parameters.  
Operation  
[Hand on] allows the user to start the motor locally from the keypad. Press the [Hand on] to start the motor locally  
either in drive or bypass mode.  
[Off Reset] allows the user to stop the motor locally from the keypad. Press the [Off Reset] to stop the motor  
locally, either in drive or bypass mode.  
[Auto on] allows the motor to be started remotely from digital input or serial communications. Press [Auto on] to  
activate the remote motor start and stop from a digital input or serial communications in drive or bypass mode.  
Press [Drive Bypass] to initiate the display to toggle between drive or bypass mode of operation. Press [OK] to  
accept the change or [Cancel] to cancel the action.  
Parameter No.  
00-44  
Key  
Function  
[Off Reset]  
This disables or enables the [Off Reset] key on keypad. (0) disabled,  
(1) enabled, (2) password Default value is (1) enabled.  
This disables or enables the [Drive Bypass] key on keypad. (0)  
disabled, (1) enabled, (2) password Default value is (1) enabled.  
00-45  
[Drive Bypass]  
Table 6.3 keypad Control Keys Programming  
6.1.6 ECB Mode of Operation  
General Information  
The ECB has four modes of operation: drive, bypass, auto bypass, and test. Each mode is selected through the keypad and  
display. Bypass mode select can be accessed directly by pressing [Drive Bypass].  
Prior to Enabling Mode of Operation  
Complete the start-up procedure and verify motor rotation direction in bypass is correct and that the system is  
ready in all respects for continuous full speed operation in bypass.  
Press [Off Reset] to prevent operation of the motor.  
Operation  
Drive mode: The motor is connected to and controlled by the drive. Contactors M1 and M2 are closed while  
contactor M3 is open. The motor will not run until a run command is present.  
Bypass mode: The motor operates at full speed across the line when a run command is present. Contactor M3 is  
closed and M1 and M2 are open.  
Test mode: Test mode puts the panel into bypass mode and will automatically run in bypass. Contactor M1 is  
closed, supplying power to the drive for test purposes while M2 is open. Contactor M3 controls the operation of  
the motor in bypass, closed to run the motor, open to remove power. The control keys on the keypad will not  
control the bypass until test mode is removed.  
6-8  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Electronically Controlled Bypass (ECB) Opera-  
tion  
Auto bypass mode: When in drive mode, auto bypass is a timed interval that allows a fault condition in the drive  
to activate running the motor in bypass without operator intervention.  
Mode of Operation Select  
Mode of operation is programmed through parameter group 31-** . See Table 6.4.  
Par. No.  
31-00  
Selection  
Function  
Bypass Mode  
Selects source of motor power.  
(0) Drive (drive mode) (1) Bypass (bypass  
mode)  
31-01  
31-02  
Bypass Start Time Delay  
Bypass Trip Time Delay  
Sets a delay time for starting in bypass that  
allows for external actions to take place prior  
to line starting the motor.  
0-60 sec. (default value is 5 sec.)  
Setting a value other than 0 sec. enables  
auto bypass. Bypass trip delay sets the delay  
time before switching to bypass mode when  
the drive has a fault.  
0-300 sec. (default is 0 sec. = OFF)  
Setting enabled puts bypass in test mode.  
See the manual for warnings and cautions.  
(0) disabled (default value) (1) enabled  
Read-only display, which shows the bypass  
status in hex. See the next table for details.  
0, 216-1 (default value is 0)  
31-03  
31-10  
31-11  
Test Mode Activation  
Bypass Status Word  
Bypass Running Hours  
Read only display which shows bypass  
running hours.  
Table 6.4 Bypass Parameter Functions  
Bit  
Description  
0
1
2
3
4
5
Test Mode The Test Mode bit will be true when the ECB is in Test Mode.  
Drive Mode The Drive Mode bit will be true when the ECB is in Drive Mode.  
Automatic Bypass Mode The Automatic Bypass Mode bit will be true when the ECB is in Automatic Bypass Mode.  
Bypass Mode The Bypass Mode bit will be true when the ECB is in Bypass Mode.  
Reserved This bit is reserved for future use.  
Motor Running from Bypass/Drive The Motor Running from Bypass/Drive Bit will be true when the motor is running from  
either the drive or the bypass.  
6
7
Overload Trip The Overload Trip Bit will be true when the ECB detects an overload trip.  
M2 Contactor Fault The Contactor Fault Bit will be true when an M2 Contactor Fault is detected.  
M3 Contactor Fault The Contactor Fault Bit will be true when an M3 Contactor Fault is detected.  
External Interlock The External Interlock Bit will be true when an External Interlock fault is detected.  
Manual Bypass Override The Manual Bypass Override Bit will be true when the Manual Bypass Override input is true.  
8
9
10  
Table 6.5 Parameter 31-10 Bypass Status Word Bit Definitions  
BAS-SVX49A-EN  
6-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electronically Controlled B...  
6.1.7 Bypass Status Word Bit Examples  
1.  
Motor running and bypass in drive mode. Status word 22 hexadecimal converts to 00000100010 binary.  
Bit  
10  
0
9
0
8
0
7
0
6
0
5
1
4
0
3
0
2
0
1
1
0
0
Binary  
1.  
External interlock fault (open) and bypass in bypass mode. Status word 208 hexadecimal converts to 01000001000  
binary.  
Bit  
10  
0
9
1
8
0
7
0
6
0
5
0
4
0
3
1
2
0
1
0
0
0
Binary  
-
-
-
a remote start command is removed  
a safety is open  
6.1.8 ECB Auto Bypass  
General Information  
Auto bypass allows a fault condition in the drive to  
motor overload is tripped  
Once auto bypass is activated, the only way to  
reset the unit back to drive mode is by operator  
intervention. Ensure that the fault has been  
cleared, then press [Drive Bypass] and select drive  
mode.  
activate running the motor in bypass without operator  
intervention. Activation of the function is through setting  
timer start parameters in the drive programming. Fault trip  
and running in bypass are reported through the drive  
display, digital outputs, and serial communications. In  
addition, the independently powered ECB card is available  
to report bypass status when the drive is inoperable  
(control card operative) through its serial communications  
or digital outputs.  
Auto Bypass Function Setup  
Enable auto bypass by changing parameters in group 31 in  
the drive extended menu.  
31-01, Bypass start time delay. Setting the timer at  
Prior to Enabling Auto Bypass  
anything other than 0 time activates start delay  
in bypass. Leave at 30 sec. default or set as  
desired up to 60 sec.  
Complete the start-up procedure to verify motor  
rotation direction in bypass is correct and that  
the system is ready in all respects for continuous  
full speed operation in bypass.  
31-02, Bypass trip time delay. Setting the timer at  
anything other than 0 time activates auto bypass.  
Leave at 5 sec. default or set as desired up to 60  
sec.  
Operation  
With the auto bypass function enabled, a fault  
signal from the drive activates the auto bypass  
timer.  
If the fault clears before the time delay is  
complete, the motor remains operating in drive  
mode. This allows temporary faults, such as a  
momentary under or over voltage, to clear  
without transferring the system to bypass.  
If the timer completes its cycle before the fault  
clears, the panel trips into bypass mode and the  
motor runs at constant full speed from line input  
voltage.  
In bypass, the motor will stop:  
-
if the drive receives a remote stop  
command  
Figure 6.3 Bypass Trip Time Delay  
-
local stop ([Off]) on the keypad is  
pressed  
6-10  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Electronically Controlled Bypass (ECB) Opera-  
tion  
Run Permissive Function Setup  
See the drive manual or support materials for  
programming and wiring to the drive control  
terminals.  
Wire the output run request to the drive output  
terminals selected, and program the terminals for  
run request.  
Wire the input run command to the drive input  
terminals selected, and program the terminals for  
run permissive.  
Disable Run Permissive  
Disable run permissive through the drive  
parameters and terminal programming.  
Figure 6.4 Drive Display with Bypass Start Time Delay Active  
6.1.10 ECB Overload  
6.1.9 ECB Run Permissive  
General Information  
General Information  
An overload device provides overcurrent protection for the  
motor when running in bypass. The thermally activated  
overload monitors motor current and trips to remove  
power to the motor if a sustained overcurrent condition  
exists. A Class 20 overload is standard with a variable  
setting for motor current. Test and reset buttons are also  
provided. In drive mode, the drive provides current sensing  
and trip protection. Fuses provide quick action for high  
over current conditions.  
With run permissive active, the drive sends a run request  
and waits for a remote response before notifying the  
motor to start. The response indicates the system is safe to  
operate. Run permissive operates from the keypad  
hand/off/auto select in drive or bypass mode. Run  
permissive is enabled by programming in the drive  
parameters.  
Prior to Enabling Run Permissive  
Prior to Enabling Overload  
Complete the start-up procedure to verify motor  
rotation direction in bypass is correct and that  
the system is ready in all respects for continuous  
full speed operation in bypass.  
Verify that the overload current dial setting  
matches the motor FLA rating on the motor  
nameplate.  
Verify that the drive is programmed for the run  
If the motor FLA is greater or less than the range  
permissive function. See the drive support  
materials for programming the run permissive  
function.  
of the current dial, reconfirm that the motor HP  
and voltage are within the option panel (and  
drive) rating. If greater than the FLA rating,  
replace the panel with one of a proper rating.  
Operation  
A start command can be initiated from local hand  
start, serial communications, or a remote auto  
start signal through digital drive input terminals.  
CAUTION  
MOTOR DAMAGE!  
Repeated attempts to reset overload can cause motor  
damage. Correct the overload condition and let the  
overload and motor return to normal operating  
temperature before resetting. See motor manufacturer’s  
recommendations for time between start attempts. Failure  
to correct the overload condition and let the motor return  
to normal operating temperature could cause motor  
damage.  
In response to the start command, an output  
request is sent from the programmable drive  
relay to the external equipment (to activate a  
valve or damper, for example).  
When a return run signal on the digital input is  
received, the motor is started in either drive or  
bypass, depending upon which mode is active.  
BAS-SVX49A-EN  
6-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Electronically Controlled B...  
Operation  
bypass ignores all run commands except for fire mode  
operation, when applicable. The drive display indicates  
alarm 221, bypass interlock, meaning the problem is  
external to the drive. A factory installed jumper between  
X57 terminals 1 and 2 allows the unit to operate when no  
safety input is connected. This jumper must be removed  
when connecting in a safety interlock circuit.  
Overloads and motors are both rated by class. The class is  
defined by the NEC to determine the maximum time to  
trip. A Class 20 overload, for example, has a typical trip  
delay of 20 sec. or less at 600% current and normal  
operating temperature. This allows for high motor inrush  
current for 20 sec. while the motor is ramping up to  
synchronous speed. The trip time, however, is based on  
the percentage of overload. The higher the overload, the  
shorter the time.  
Safety Interlock Function Setup  
Remove factory-installed jumper between ECB  
connector X57 terminals 1 and 2 on drive control  
terminals.  
TRIP  
MANUAL  
AUTO  
Wire safety input to connector X57 terminals 1  
and 2.  
TEST  
RESET  
For technicians familiar with connecting to drive  
98NO  
95NC  
97NO  
T1  
96NC  
T3  
terminals 12 and 27 for safety interlock, be aware  
that ECB bypass operation will NOT stop with the  
external fault report. Use terminals 1 and 2 on  
connector X57, as indicated, for bypass control.  
T2  
Figure 6.5 Sample Overload Device  
6.1.12 ECB Common Run/Stop  
Overload Function Setup  
General Information  
Set the overload current dial to the FLA of the  
motor. DO NOT add the service factor of the  
motor into the setting. A service factor of 1.2 x  
FLA is designed into the overload.  
The common run/stop function provides remote run and  
stop control of the motor while in either drive or bypass.  
Without common run/stop, the motor would automatically  
run at full speed whenever the bypass is activated. The  
remote signal provides drive control as well as bypass  
control, making this one input common to both. Common  
run/stop is enabled by factory default. When used with the  
run permissive function, common run/stop permits run  
request operation in bypass.  
Pressing the test pushbutton verifies the  
operation of the overload. The overload should  
trip when pressed. Use the reset pushbutton to  
reset the overload after testing.  
Reset is used to reset the overload after it trips. If  
the overload is still hot, wait until the motor  
reaches normal operating temperature before  
resetting. The overload offers a manual (hand) or  
auto reset selection. It is highly recommended to  
operate in the manual factory setting to prevent  
the risk of damage to the motor.  
Operation  
A user supplied remote run command wired to drive  
terminals 13 and 18 initiates remote drive or bypass  
operation. Common run/stop can also be activated by  
hand on the keypad or through serial communication.  
Operation in either drive or bypass is determined by drive  
or bypass mode selection, not the run/stop command.  
6.1.11 ECB Safety Interlock  
Prior to Enabling Common Run/Stop  
Complete the start-up procedure to verify motor  
General Information  
rotation direction in bypass is correct and that  
the system is ready in all respects for continuous  
full speed operation in bypass.  
The safety interlock feature prevents the drive or bypass  
from operating. Only a fire mode command to run  
overrides this function. For operation in drive or bypass  
mode, the safety external interlock input contact must be  
closed. External inputs include, but are not limited to, high  
and low pressure limit switches, fire alarm, smoke alarm,  
high and low temperature switches, and vibration sensors.  
Common Run/Stop Setup  
Wire a remote run/stop to drive input terminals  
13 and 18 (default run input). Ensure that  
parameter 18 is programmed for run (default  
setting).  
Operation  
When an external safety input closes on ECB terminals 1  
and 2 on connector X57, the option panel is in operational  
mode. When open, power to the motor is disabled. The  
6-12  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Electronically Controlled Bypass (ECB) Opera-  
tion  
The drive monitors the ECB card communication and  
detects when communication stops. An ECB card failure or  
communication error could cause this. Contact Trane using  
the phone number on the back of this manual for  
technical support if this happens. The phone number can  
also be found on the label inside the panel cover.  
6.1.13 ECB Advanced Fire Mode  
General Information  
Drive operation in advanced fire mode is programmable. In  
the event the drive does not function, the motor is  
operated in bypass at full speed. Fire mode is intended to  
ignore common safety and overload inputs in emergency  
situations. The fire mode function is built-in. See the drive  
support materials for programmable options.  
Fault Reporting Function Setup  
Automatic function. No set up required.  
Prior to Enabling Fire Mode  
Complete the start-up procedure to verify motor  
rotation direction in bypass is correct and that  
the system is ready in all respects for continuous  
full speed operation in bypass.  
Verify that the drive is programmed for the fire  
mode function. See the drive support materials  
for programming the fire mode function.  
Operation  
Activation of fire mode is accomplished by  
programming the drive for fire mode.  
When activated, the ECB ignores safety circuits  
and motor overload.  
Fire mode is deactivated only when the  
command is removed or the unit fails.  
Fire mode status can be reported through serial  
communications or drive output.  
Fire Mode Function Setup  
Program drive for fire mode.  
If required, program a drive output for fire mode  
status.  
See the drive support materials for programming  
the fire mode function.  
6.1.14 ECB Fault Reporting  
General Information  
The ECB monitors bypass contactors M2 and M3 and  
reports failures to the drive for display and external  
reporting. The drive also monitors the ECB card for bypass  
communication errors.  
Operation  
ECB detected faults are reported by the drive in three  
ways: Warnings and alarms are displayed on the keypad  
display, through serial communication, or through output  
relays. The drive provides a form-C fault relay on terminals  
01, 02, and 03. The fault contacts are fail-safe, meaning  
that if power is removed the contacts close and a fault  
condition is reported.  
BAS-SVX49A-EN  
6-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Electronically Controlled B...  
6-14  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start Up Troubleshooting  
7 Start Up Troubleshooting  
7.1.1 Option Panel Alarm and Warnings  
Code  
Number  
220  
Title  
Overload Trip  
Bypass Interlock  
Definition  
Motor overload has tripped. Indicates excess motor load. Check motor and driven load. To reset,  
press [Off Reset]. Then, to restart the system, press [Auto on] or [Hand on].  
Bypass interlock has opened and caused the motor to stop. Correct the problem. Depending on  
the setting of parameter 14-20, the system will either automatically reset this alarm or require the  
[Off Reset] key to be pressed.  
221  
222  
223  
M2 Open Failed  
M2 Close Failed  
ECB: The contactor that connects the drive to the motor failed to open. The motor can not be  
operated.  
ECB: The contactor that connects the drive to the motor failed to close. The motor can not be  
operated.  
224  
226  
M3 Open Failed  
M3 Close Failed  
ECB: The contactor that connects the motor to the power line has failed to open.  
ECB: The contactor that connects the motor to the power line has failed to close. The motor can  
not be operated.  
227  
Bypass Com Error  
Communication between the main control card and the bypass option has been lost. Motor control  
lost. It will be possible to run the motor using Manual Bypass Override.  
The Option Panel Power Supply has failed, or there is a power problem.  
Terminal 3 on connector X57 of the ECB control card shows an open. This generally means that  
neither motor has been selected in contactor motor select. Select a motor.  
228  
229  
APU Low Voltage  
Motor Disconn.  
Table 7.1 Option Panel Alarms and Warnings (ECB only)  
DisplayText  
Definition  
Bypass Run Starts in:  
Indicates the number of sec. until the motor will be started in bypass. This time delay  
can be adjusted using parameter 31-01.  
Bypass Activates in:  
Indicates the number of sec. left until the system automatically activates Bypass Mode.  
Time delay can be adjusted using parameter 31-02.  
Table 7.2 Option Panel Status Display (ECB only)  
BAS-SVX49A-EN  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Start Up Troubleshooting  
Symptom  
Possible cause  
Test  
Solution  
Missing input power  
Missing or open fuses or circuit  
breaker tripped  
See startup guide for voltage checks.  
See open fuses and tripped circuit  
breaker in this section for possible  
causes.  
Correct voltage at source.  
Reset circuit breaker. If fuses, check for  
opens with power removed from panel.  
Loose connections in panel  
Missing customer connections  
Perform pre-startup check for loose  
connections.  
Tighten loose connections in the panel.  
Missing customer connections can cause See customer connections and make  
the safety circuit or start signal to be  
open.  
sure all applicable connections are  
made or jumpers installed, especially  
customer interlock.  
Loose customer connections  
Check all customer connections for  
tightness. Loose customer connections  
can act like an open circuit.  
Tighten loose customer connections.  
Customer wires incorrectly terminated See customer connection drawing and  
Correct any wrong connections. This  
make sure wires are connected to correct could potentially cause damage to the  
terminals.  
panel.  
No function  
Improper voltage applied  
Incorrect power connections  
Power disconnect open  
Operator switches off  
OL tripped  
See pre-startup check list.  
Correct the voltage mismatch. This  
could potentially damage the panel.  
Use caution when applying power.  
See pre-startup check list to see if motor Correct any wrong connections. This  
and power leads were swapped.  
could potentially cause damage to the  
panel.  
Verify that the disconnect or circuit  
breaker is closed.  
Correct any wrong connections. This  
could potentially cause damage to the  
panel.  
Verify that operator devices are in  
operating position per startup  
procedures.  
Set switches to the correct position.  
A tripped OL will disable the motor from Perform pre-startup checklist and set  
running. Verify that OL relay is in the  
normal operating position per the  
manual.  
OL per instructions.  
Improper voltage applied  
See pre-startup check list and correct  
improper voltages.  
Correct voltage mismatch. This could  
potentially damage the panel. Use  
caution when applying power.  
Incorrect power connections.  
Motor and line voltages swapped. Make Correct any wrong connections. This  
sure the line in and motor out are on  
the correct terminals. See pre-startup  
check list.  
could potentially cause damage to the  
panel.  
Power ground fault  
Phase to phase short  
Check motor and panel power wires to  
ground.  
Eliminate any ground faults detected.  
Eliminate any shorts detected.  
Open power  
fuses or  
Motor or panel has a short phase to  
phase. Check motor and panel phase to  
phase for shorts.  
circuit  
breaker trip  
Motor overload  
Motor is overloaded for the application. Perform startup and verify motor  
current is within specifications. If motor  
current is exceeding nameplate FLA,  
reduce the load on the motor.  
Drive overload  
Drive is overloaded for the application.  
Perform startup and verify that drive  
current is within specifications. If not,  
reduce the load on the motor.  
Tighten loose connections.  
Loose connections  
Perform pre-startup check for loose  
connections.  
Table 7.3 Fault Table  
7-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start Up Troubleshooting  
Symptom  
Possible cause  
Test  
Solution  
Application problem  
Perform startup procedures. Check  
panel output motor current at full  
speed and check for excessive over  
current.  
If current is too high, reduce the load  
on the motor.  
Panel problem  
Perform startup procedures. Check  
panel input current at full load and  
verify it is within acceptable range.  
Monitor incoming power for surges,  
sags and overall quality.  
If current is too high, reduce the load  
on the motor.  
Repeated  
fuse or circuit  
breaker fault.  
Power problem  
Correct any problems found.  
Motor problem  
Test motor for correct function.  
Repair or replace motor if a problem is  
found.  
Improper voltage applied  
See pre-startup check list.  
Correct voltage mismatch. This could  
potentially damage the panel. Use  
caution when applying power.  
Correct any wrong connections. This  
Customer wires incorrectly terminated See the customer connection drawing  
and make sure the wires are connected could potentially cause damage to the  
Open control  
fuse  
to the correct terminals.  
Check all control wires for a short to  
ground.  
panel.  
Control ground fault  
Correct any ground faults found. This  
could potentially cause damage to the  
panel.  
Control short  
Check control wires for a short in  
supply voltage.  
Correct any shorts. This could  
potentially cause damage to the panel.  
Correct voltage mismatch. This could  
potentially damage the panel. Use  
caution when applying power.  
Improper voltage applied  
See pre-startup check list.  
Customer wires incorrectly terminated See the customer connection drawing  
Correct any wrong connections. This  
Open SMPS  
fuse  
and make sure the wires are connected could potentially cause damage to the  
to the correct terminals.  
Check all control wires for a short to  
ground.  
panel.  
Control ground fault  
Control short  
Correct any ground faults found. This  
could potentially cause damage to the  
panel.  
Check control wires for a short in  
supply voltage.  
Correct any shorts. This could  
potentially cause damage to the panel.  
Perform motor rotation procedure in  
Motor  
Rotation incorrect in bypass, drive or  
both  
Motor rotation is backwards in drive  
mode, bypass mode, or both.  
rotation  
incorrect  
BAS-SVX49A-EN  
7-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start Up Troubleshooting  
Symptom  
Possible cause  
Test  
Solution  
Motor overloaded  
Loose connections  
OL not set correctly  
Motor is drawing too much current for Perform startup and verify motor current  
the application.  
is within specifications. If not, reduce the  
load on the motor.  
Look for signs of overheating on  
connections to OL.  
Perform pre-startup check for loose  
connections and tighten. Replace any  
overheated components and wires.  
Overload trips  
An improperly set OL can cause the OL Set correct motor current on OL.  
to trip too soon. See pre-startup  
procedure for correct setting.  
Contamination  
Defective coil  
Remove contactor and check for  
contamination.  
If contamination is found, repair or  
replace.  
Compare coil resistance to contactor  
specification. Inspect the coil for signs  
of overheating and damages.  
Remove auxiliary contacts and test  
contactor action.  
If readings are not the same or if there  
are visible signs of damage, replace the  
coil or contactor.  
Contactor fails  
to pull in  
Auxiliary contact binding action  
Contamination  
If contactor operates with auxiliaries  
removed, replace auxiliary contacts.  
If contamination is found, repair or  
replace.  
Remove the contactor and check for  
contamination.  
Defective coil  
Compare coil resistance to functional  
contactors of the same size.  
If readings are not the same or there are  
visible signs of damage, replace the coil  
or contactor.  
Contactor fails  
to drop out  
Auxiliary contact binding action  
Problem with mains power  
Remove auxiliary contacts and test  
contactor action.  
If the contactor operates with auxiliaries  
removed, replace auxiliary contacts.  
If the imbalanced leg follows the wire, it  
Rotate incoming power leads into  
option panel one position; A to B, B to is a power problem. Causes can vary.  
C, and C to A.  
Contact an electrician or power expert  
for a solution.  
Mains current  
imbalance  
greater than  
3%  
Problem with option panel  
Rotate incoming power leads into  
If the imbalanced leg stays on the same  
option panel one position; A to B, B to option panel input terminal, it is a  
C, and C to A.  
problem with the option panel. Contact  
the factory for assistance.  
Problem with motor or motor wiring Rotate outgoing motor leads one  
position; U to V, V to W, and W to U.  
If the imbalanced leg follows the motor  
lead, the problem is in the motor or  
wiring to the motor. Causes can vary.  
Contact an electrician or motor expert  
for a solution.  
Motor current  
imbalance  
greater than  
3%  
Problem with option panel  
Rotate outgoing motor leads one  
If the imbalanced leg stays on the same  
option panel output terminal, it is a  
problem with the option panel. Contact  
the factory for assistance.  
position; U to V, V to W, and W to U.  
7-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
8 Appendix  
8.1.1 Dimensions  
P2 NON-  
BYPASS  
P3 NON-  
BYPASS  
9.57 [243.0]  
-
P4 NON-  
BYPASS  
12.69 [322.3]  
-
P5 NON-  
BYPASS  
15.13 [384.3]  
-
P2 BYPASS  
P3 BYPASS  
P4 BYPASS  
P5 BYPASS  
A
A1  
B
C
D
a
8.86 [225.0]  
6.66 [169.1]  
9.11 [231.4]  
-
9.57 [243.0]  
-
12.69 [322.2]  
-
15.13 [384.2]  
-
29.92 [759.9] 41.77 [1061.0] 34.33 [872.0] 43.23 [1098.0] 39.58 [1005.4] 54.38 [1381.4] 45.79 [1163.1] 59.64 [1514.9]  
11.45 [290.9]  
-
15.94 [405.0]  
1.10 [28.0]  
11.23 [285.2]  
0.59 [15.0]  
17.70 [449.6]  
0.59 [15.0]  
14.78 [375.5]  
0.59 [15.0]  
17.99 [457.0]  
0.59 [15.0]  
14.78 [375.4]  
0.59 [15.0]  
18.01 [457.5]  
0.59 [15.0]  
5.51 [140.0]  
7.87 [200.0]  
7.87 [200.0]  
7.87 [200.0]  
10.63 [270.0]  
10.63 [270.0]  
12.99 [330.0]  
12.99 [330.0]  
b
c
28.80 [731.5] 41.02 [1042.0] 32.13 [816.0] 41.18 [1046.0] 37.32 [948.0] 51.89 [1318.0] 43.54 [1106.0] 57.09 [1450.0]  
0.27 [6.8]  
0.39 [10.0]  
0.49 [12.5]  
0.27 [6.9]  
0.47 [12.1]  
0.49 [12.5]  
0.31 [8.0]  
0.32 [8.0]  
0.27 [6.8]  
0.43 [11.0]  
0.65 [16.5]  
0.27 [6.8]  
0.47 [12.0]  
0.65 [16.5]  
0.31 [8.0]  
0.31 [8.0]  
0.33 [8.5]  
0.33 [8.5]  
0.33 [8.5]  
0.33 [8.5]  
0.33 [8.5]  
0.33 [8.5]  
d
e
0.47 [12.0]  
0.39 [10.0]  
0.47 [12.0]  
0.59 [15.0]  
0.47 [12.0]  
0.59 [15.0]  
0.72 [18.4]  
0.61 [15.5]  
0.91 [23.0]  
0.75 [19.0]  
0.94 [24.0]  
0.79 [20.0]  
f
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
g
h
j
k
BAS-SVX49A-EN  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Appendix  
8.1.2 Mechanical Diagrams  
Figure 8.1 P2 Bypass  
8-2  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix  
Figure 8.2 P2 Non-bypass  
BAS-SVX49A-EN  
8-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.3 P3 P4 P5 Bypass  
8-4  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.4 P3 P4 P5 Non-bypass  
BAS-SVX49A-EN  
8-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
8.1.3 Typical Wiring Diagrams  
Figure 8.5 EMB2 with Control Relay, Part 1  
8-6  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix  
Figure 8.6 EMB2 with Control Relay, Part 2  
BAS-SVX49A-EN  
8-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.7 EMB2, Part 1  
8-8  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.8 EMB2, Part 2  
BAS-SVX49A-EN  
8-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.9 ECB, Part 1  
8-10  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.10 ECB, Part 2  
BAS-SVX49A-EN  
8-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.11 ECB with Control Relays, Part 1  
8-12  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.12 ECB with Control Relays, Part 2  
BAS-SVX49A-EN  
8-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Figure 8.13 Non-bypass  
8-14  
BAS-SVX49A-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tascam DVR DR 07 User Manual
Taylor Gas Grill 811 User Manual
Technicolor Thomson CRT Television 2 5 D G 1 6 E T User Manual
Telex Stereo System 840 35 User Manual
Topcom Telephone DIABLO 103 User Manual
Toshiba Computer Drive GMAA0020901T User Manual
Triarch Indoor Furnishings 33200 1 User Manual
Tripp Lite Power Supply SUINT10002TXL2UA User Manual
Vivitar Digital Camera Vivicam 2755 User Manual
Vivotek Security Camera FD6111 User Manual