Trane Heat Pump PKGP PRC001 EN User Manual

Packaged Heat Pumps  
Voyager™  
12½ – 20Tons — 60 Hz  
PKGP-PRC001-EN  
October 2003  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction  
2
4
8
Features and Benefits  
Application Considerations  
9
Selection Procedure  
Model Number Description  
General Data  
10  
11  
13  
Performance Data  
13  
16  
21  
Cooling Performance  
Fan Performance  
Heat Performance  
26  
27  
38  
48  
Controls  
Electric Power  
Dimension and Weights  
Mechanical Specifications  
PKGP-PRC001-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
WeatherTight Top and Cabinet  
• Actual shipping tests were performed  
to determine packaging requirements.  
Units were test shipped around the  
country to determine the best  
packaging. Factory shake and drop  
tests were used as part of the package  
design process to help assure that the  
unit arrives at the job site in top  
condition.  
Conversionless Units  
Voyager units incorporate either a one  
piece top or the Trane-Tite-Top (T3).  
Each part of the top (either two or three  
pieces) overlaps in such a way that  
water cannot leak into the unit.These  
overlapped edges are gasketed and  
sealed to ensure superior water  
integrity.  
The dedicated design units (either  
downflow or horizontal) require no  
panel removal or alteration time to  
convert in the field — a major cost  
savings during installation.  
Horizontal units come complete with  
duct flanges so the contractor doesnt  
have to field fabricate them.These duct  
flanges are a time and cost saver.  
• Rigging tests include lifting a unit into  
the air and letting it drop one foot,  
assuring that the lifting lugs and rails  
hold up under stress.  
Quick- Access (12½-20 tons) panels  
reduce the number of possible water  
entry points.  
U-shaped Airflow  
U-shaped airflow allows for improved  
For added water integrity, Voyager has  
a raised 11/8" lip around the supply and  
return of the downflow units to prevent  
water from blowing into the ductwork.  
• We perform a 100% coil leak test at the  
factory.The evaporator and condenser  
coils are leak tested at 200 psig and  
pressure tested to 450 psig.  
static capabilities.  
Quality And Reliability Testing  
• All parts are inspected at the point of  
final assembly. Sub-standard parts are  
identified and rejected immediately.  
The fan and idler arm assembly  
designs have been tested to over  
300,000 cycles each. Our combined  
cycle testing is now over 7,000,000  
cycles.  
• Every unit receives a 100% unit run test  
before leaving the production line to  
make sure it lives up to rigorous Trane  
requirements.  
All of Voyagers designs were  
rigorously rain tested at the factory to  
ensure water integrity.  
We test designs at our factory not on our  
customers!  
PKGP-PRC001-EN  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
• Eliminates the need for field-installed  
components with its built-in anti-short-  
cycle timer, time delay relay and  
minimum on time controls.These  
controls are factory tested to assure  
proper operation.  
• Requires no special tools to run the unit  
through its paces during testing. Simply  
place a jumper betweenTest 1 andTest  
2 terminals on the Low VoltageTerminal  
Board and the unit will stage through its  
operational steps.The unit  
automatically returns control after 60  
minutes to the zone sensor after  
stepping through the test mode a single  
time, even if the jumper is left on the  
unit.  
ReliaTel™  
Several years ago,Trane was the first to  
introduce ReliaTel into the Light  
Commercial Market.That design, along  
with immeasurable experience, has  
provided the technology forTranes  
second-generation ReliaTel  
• As long as the unit has power and the  
LED is lit, the ReliaTel is operational.  
The light indicates that the ReliaTel is  
functioning properly.  
microprocessor controls.  
ReliaTel:  
• Features expanded diagnostic  
capabilities when used with Tranes  
Integrated ComfortTM Systems.  
• Provides unit control for heating,  
cooling, and ventilating by utilizing  
input from sensors that measure  
outdoor and indoor temperature.  
• As an energy benefit, softens electrical  
‘’spikesby staging on fans,  
compressors and heaters.  
Improves quality and reliability  
through the use of time-tested  
microprocessor controls and logic.  
• The Intelligent Fallback or Adaptive  
Control is a benefit to the building  
occupant. If a component goes astray,  
the unit will continue to operate at  
predetermined temperature set points.  
• Prevents the unit from short cycling,  
considerably improving compressor  
life.  
Intelligent Anticipation is a standard  
feature of the ReliaTel. Functioning  
constantly, the ReliaTel and zone  
sensors work together in harmony, to  
provide tight comfort control.  
• Ensures that the compressor will run  
for a specific amount of time, which  
allows oil to return for better  
lubrication, enhancing the reliability of  
the compressor.  
• Reduces the number of components  
required to operate the unit, thereby  
reducing possibilities for component  
failure.  
PKGP-PRC001-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Easy Access Low Voltage Terminal Board  
Voyagers Low Voltage Terminal Board is  
external to the electrical control cabinet.  
It is extremely easy to locate and attach  
the thermostat wire.This is another cost  
and time saving installation feature.  
Standardized Components  
Components are placed in the same  
location on all Voyager units.  
Familiarize yourself with one Voyager  
and you are familiar with every  
Voyager.  
Low Voltage Connections  
The wiring of the low voltage  
connections to the unit and the zone  
sensors is as simple as 1-1, 2-2, and 3-3.  
This simplified system makes it easy for  
the installer to wire.  
ReliaTel can fit all Voyager Packaged  
Gas/Electrics, Cooling with Electric  
Heat, and Heat Pump models.This  
provides standardization of parts for  
the contractors. Less money is tied up  
in inventory using the ReliaTel.  
Quick-Adjust Idler Arm  
Colored And Numbered Wiring  
With the Quick-Adjust Idler Arm, the belt  
and sheaves on all 12½-20 tons can be  
quickly adjusted without moving the  
mounted fan motor.The result is a major  
savings in time and money.  
You save time and money tracing wires  
and diagnosing the unit.  
VariTrac™  
Contractors/owners can stock fewer  
parts due to standardized components  
throughout Voyager units.  
When Tranes changeover VAV System  
for light commercial applications is  
coupled with Voyager, it provides the  
latest in technological advances for  
comfort management systems and can  
allow thermostat control in every zone  
served by VariTrac.  
Single Side Service  
Single side service is standard on all  
Voyager 12½-20 tons.  
Quick-Access Panels On The 12½-20Tons  
Remove three or fewer screws for access  
to the standardized internal components  
and wiring.  
VariTrac  
PKGP-PRC001-EN  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Capacity Modulation  
Flexible Applications  
Factory Built Roof Curbs  
Available for the downflow units.  
Zone Sensors  
The 12½-20 tons have dual  
Only two roof curbs for the entire  
compressors.  
Voyager line simplifies curb selection.  
Compressors  
Airflow is outstanding.The Voyager can  
replace an older machine with old  
ductwork and, in many cases, improve  
the comfort through better air  
distribution.  
Available in programmable, automatic  
and manual styles.  
Voyager contains the best compressor  
technology available to achieve the  
highest possible performance. The  
dual compressor models are  
outstanding for humidity control, light  
load cooling conditions and system  
back-up applications.  
The following options round-out the  
complete line of Voyager accessories:  
— 0 - 25% manual outside air hood  
— Motorized outside air for 12½-20 tons  
• A wide variety of Factory Installed  
Options (FIOPs) are available.  
One Of Our Finest Assets:  
Trane Communication Interface (TCI)  
Low Ambient Cooling  
Trane Sales Representatives are a  
Support group that can assist you with:  
— Product  
— Application  
— Service  
Training  
— Special Applications  
— Specifications  
Available factory or field installed.This  
module when applied with the Micro  
easily interfaces with Tranes Integrated  
ComfortTM System.  
All Voyager 12½-20 tons have cooling  
capabilities down to 0°F as standard.  
Power Exhaust Option  
Single Point Power  
This option is available on the 12½-20  
tons downflow units. It provides exhaust  
of the return air, when using a downflow  
economizer, to maintain proper building  
pressurization. Great for relieving most  
building overpressurization problems.  
A single electrical connection powers the  
unit.  
— Computer Programs and much more  
Sloped Drain Pans  
Voyager has the features and benefits  
that make it first class in the light  
commercial rooftop market. Designed  
with input from field contractors and  
engineers, its U-shaped airflow  
performance is outstanding.  
Standard on every unit.  
Downflow And Horizontal Economizers  
CO2 Sensing  
The economizers come with three  
control options — dry bulb is standard,  
enthalpy and differential enthalpy are  
optional.  
The CO2 sensor has the ability to monitor  
space occupancy levels within the  
building by measuring the parts per  
million of CO2 (Carbon Dioxide) in the air.  
As the CO2 levels increase, the outside air  
damper modulates to meet the CO2  
space ventilation requirements.The CO2  
sensor kit is available as a field installed  
accessory.  
If all of your customers knew about  
Voyager, all would insist on it.  
High Static Drive Accessory  
Available on many models, this high  
static drive accessory extends the  
capability of the standard motor. Avoid  
expensive motors and operating costs  
by installing this optimized sheave  
accessory.  
Ventilation Override Accessory  
With the Ventilation Override Accessory  
installed, the unit can be set to transition  
to up to 3 different pre-programmed  
sequences for Smoke Purge,  
Pressurization, and Exhaust.The  
transition occurs when a binary input on  
the RTOM is closed (shorted).This would  
typically be a hard wired relay output  
from a smoke detector of fire control  
panel.The ventilation override kit is  
available as a field installed accessory.  
ReliaTel  
PKGP-PRC001-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Application of this product should be  
within the cataloged airflow and cooling  
considerations.  
Condensate Trap  
The evaporator is a draw-thru  
configuration. A trap must be field  
provided prior to start-up on the cooling  
cycle.  
Low Ambient Cooling  
This Voyager line features, as standard,  
low ambient cooling down to 0°F.  
Contact your localTrane Representative  
for more assistance with low ambient  
cooling applications.  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate  
serviceability, maximum capacity and  
peak operating efficiency. Actual  
clearances which appear inadequate  
should be reviewed with the localTrane  
sales personnel.  
Barometric Relief  
This product line offers an optional  
barometric relief damper included in the  
downflow economizer accessory.This  
accessory consists of gravity dampers  
which open with increased pressure. As  
the building air pressure increases, the  
pressure in the unit return air section  
also increases, opening the dampers  
and relieving the conditioned space.  
Unit Pitch  
These units have sloped condensate  
drain pans. Units must be installed level,  
any unit slope must be toward access  
side of unit.  
NOTE:THE EFFECTIVENESS OF  
BAROMETRIC RELIEF DAMPER  
DURING ECONOMIZING OPERATION  
IS SYSTEM RELATED.  
PRESSURE DROP OFTHE RETURN AIR  
SYSTEM SHOULD BE CONSIDEREDTO  
CONTROL BUILDING PRESSURIZA-  
TION.  
Power Exhaust Accessory  
The power exhaust accessory is  
available on all 12½-20 tons downflow  
units.This accessory can be field  
installed and will assist in relieving  
building pressurization.  
PKGP-PRC001-EN  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedure  
Example:  
Step 3  
Step 5  
Table PD-3 shows that a WCD180B4 has  
a gross cooling capacity of 183.0 MBh  
and 129.0 MBh sensible capacity at 95  
degree ambient and 6000 cfm with 80  
DB/67 WB air entering the evaporator.  
Cooling Capacity  
If the performance will not meet the  
required load of the building, try a  
selection at the next higher size unit.  
Step 1  
Calculate the buildings total and sensible  
cooling loads at design conditions. Use  
the American Standard calculation form  
or any other standard accepted method.  
Heating Capacity  
To Find Capacity at Interm iediate  
Conditions  
Step 1  
Calculate the building heating load using  
the American Standard calculation form  
or other standard accepted method.  
Step 2  
When the design conditions are between  
two numbers that are in the capacity  
table, interpolation is required to  
approximate the capacity.  
Given the following building  
requirements:  
A
Electrical Characteristics: 460/60/3  
B
Summer Design Conditions:  
Entering Evaporator Coil: 80 DB/ 67 WB  
Outdoor Ambient: 95 DB  
C
Total Cooling Load: 172 MBh  
D
Sensible Cooling Load: 122 MBh  
E
Airflow: 6000 cfm  
F
Step 2  
Note: Extrapolation outside of the table  
conditions is not recommended.  
Size the equipment usingTable PD-15 to  
match the heating loads at design  
conditions.  
Step 4  
Verify that there will be enough capacity  
by determining net capacity. In order to  
select the correct unit which meets the  
buildings requirements, the fan motor  
heat must be deducted from the gross  
cooling capacity.The amount of heat that  
the fan motor generates is dependent on  
the effort by the motor cfm and static  
pressure.To determine the total unit static  
pressure, add the following:  
A
Total Heating Load: 88 MBh  
B
Outdoor Ambient (Winter) 17 DB  
C
Indoor Return Temperature: 70 DB  
D
Airflow: 6000 Cfm  
External Static Pressure: .50 in. w.g.  
G
Rooftop - downflow configuration.  
H
Accessories  
Economizer  
Use the integrated portion of Table  
PD-15 for the WCD180B4 to determine  
capacity at winter design conditions.The  
mechanical heating portion of the heat  
pump will provide 45 MBh.  
External Static: 0.50 in.  
Standard Filter 1 in: 0.11 in. (from table  
PD-12)  
Supplementary Electric Heat  
I
Economizer Return Air: 0.04 in. (from  
table PD-12)  
Step 3  
Because 45 MBh is less than the  
buildings required heating capacity at  
winter design conditions, a  
supplementary heater must be selected.  
88 MBh - 45 MBh = 43 MBh  
Heating Capacity 88 MBh  
460 volt/3 phase Electric Supplemental  
Heat - at 6000 cfm  
Electric Heater Size 18 kW: .06 in.  
Total Static Pressure: .71 in.  
Note:The Evaporator Fan Performance  
Table PD-7 has already accounted for the  
pressure drop for standard filters and wet  
coils.  
Size the equipment usingTable PD-3.  
As a starting point, a rough determination  
of the size of the unit must be made.This  
selection will then be confirmed after  
examining the performance at the given  
conditions. Divide the total cooling load by  
nominal BTUH per ton (12 MBh per ton);  
then round up to the nearest unit size.  
172 MBh/12 MBh = 14.33 (approx. 15  
tons.)  
From Table PD-19, at 480 volts, the 18 kW  
Heater will be adequate to do the job.  
18 kW 61 MBh  
Therefore, the actual Total Static  
Pressure is .71 - .11 = .60.  
With 6000 cfm and .60 inches,Table PD-7  
shows 2.66 Bhp.  
From Table ED-3 select heater  
AYDHTRK418A (18 kW 460/60/3).  
The note below Table PD-7 gives a  
formula to calculate Fan Motor Heat:  
3.15 x bhp = MBh  
3.15 x 2.66 = 8.38 MBh  
Now subtracting the fan motor heat from  
the gross cooling capacity of the unit:  
NetTotal Cooling Capacity =  
183-8.38=170.62  
Net Sensible Cooling Capacity=  
129-8.38=120.62  
PKGP-PRC001-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Num ber  
Description  
Packaged Heat Pump Unit Model Nomenclature  
W
C
D
1
5
0
C
3
0
0
B
A
1
2
3
4
5
6
7
8
9
10  
11  
12  
Digits 1,2 Product Type  
WC = Heat Pump, Packaged  
Digit 7- Major Development Sequence  
Digit 8 - Electrical Characteristics  
WF = With Factory Installed Options  
3 = 208-230/60/3  
4 = 460/60/3  
Digit 3 - Airflow Configuration  
W = 575/60/3  
D = Downflow  
H = Horizontal  
Digits 9, 10 - Factory Installed Options  
Digits 4, 5, 6 - Nominal Gross Cooling  
Capacity (MBh)  
O O = Packed Stock, No Options  
OA = Factory Installed Downflow  
Economizer  
150  
180  
240  
=
=
=
12½ ton  
15 ton  
20 ton  
OB = Oversize Motor  
OC = Downflow Economizer and Oversize  
Motor  
OF = Trane Communications Interface (TCI)  
O G = Downflow Economizer and TCI  
Digit 11- Minor Design Sequence  
Digit 12- Service Digit  
PKGP-PRC001-EN  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(1Ton)  
Table GD-1 — General Data  
12½ Ton Downflow and Horizontal Units  
WCD150B3, B4, BW  
WCH150B3, B4, BW  
Cooling Perform ance1  
Gross Cooling Capacity  
EER2  
152,00  
9.5  
152,000  
9.5  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part Load Value3  
System Power KW  
4,400 / 4,400  
144,000  
9.9  
4,400 / 4,400  
144,000  
9.9  
15.16  
15.16  
Heating Perform ance1  
High Temp. Btuh Rating  
System Power KW/COP  
Low Temp. Btuh Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
135,000  
12.76/3.10  
78,000  
10.88/2.1  
132,000  
12.48/3.10  
72,000  
10.55/2.0  
Com pressor  
No./Type  
ARI Sound Rating (BELS)4  
2/Climatuff Scroll  
9.2  
2/Climatuff Scroll  
9.2  
Outdoor Coil — Type  
Tube Size (in.) OD  
Face Area (sq ft)  
Rows/FPI  
Hi-Performance  
.375  
23.96  
Hi-Performance  
.375  
23.96  
2/16  
2/16  
Refrigerant Control  
Expansion Valve  
Expansion Valve  
Indoor Coil — Type  
Tube Size (in.)  
Face Area (sq ft)  
Hi-Performance  
.375  
15.83  
Hi-Performance  
.375  
17.50  
Rows/FPI  
2/15  
2/15  
Refrigerant Control  
Drain Connection No./Size (in.)  
Capillary Tube  
1/1.00 NPT  
Capillary Tube  
1/1.00 NPT  
Outdoor Fan — Type  
No. Used/Diameter (in.)  
Drive Type/No. Speeds  
CFM  
Propeller  
Propeller  
2/26  
Direct/1  
10,800  
2/.50  
2/26  
Direct/1  
10,800  
2/.50  
No. Motors/HP  
Motor RPM  
1,110  
1,110  
Indoor Fan — Type  
No. Used  
FC Centrifugal  
FC Centrifugal  
1
1
Diameter x Width (in.)  
Drive Type/No. Speeds  
No. Motors  
15 x 15  
Belt/1  
1
15 x 15  
Belt/1  
1
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size (Standard/Oversized)  
3.0/5.0  
1,740/3,450  
145T/145T  
3.0/5.0  
1,740/3,450  
145T/145T  
Filters — Type Furnished6  
(No.) Size Recommended (in.)  
Throwaway  
(2) 20 x 20 x 2  
(4) 20 x 25 x 2  
Throwaway  
(2) 20 x 20 x 2  
(4) 20 x 25 x 2  
Refrigerant Charge (Lbs of R-22)5  
11.1/11.4/Circuit  
11.5/11.8/Circuit  
NOTES:  
1. Cooling Perform ance and Heating Perform ance is rated at 95°F am bient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan m otor  
heat. ARI capacity is net and includes the effect of fan m otor heat. Units are suitable for operation to ±20% of nom inal cfm . Certified in accordance with the Unitary Large  
Equipm ent certification program , which is based on ARI Standard 340/360-93.  
2. EER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm .  
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.  
5. Refrigerant charge is an approxim ate value. For a m ore precise value, see unit nam eplate and service instructions.  
6. Optional 2 inch pleated filter also available.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(15, 20 Ton)  
Table GD-2 — General Data  
15 Ton Downflow and Horizontal Units  
WC*180B3, B4, BW  
20 Ton Downflow and Horizontal Units  
WCD240B3, B4, BW  
WCH240B3, B4, BW  
Cooling Perform ance1  
Gross Cooling Capacity  
EER2  
183,500  
9.5  
233,000  
10.0  
237,000  
10.5  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part Load Value3  
System Power KW  
6,000 / 5,300  
174,000  
10.0  
8,000 / 8,000  
222,000  
9.7  
8,000/7,000  
224,000  
10.3  
18.31  
22.2  
21.3  
Heating Perform ance1  
High Temp. Btuh Rating  
System Power KW/COP  
Low Temp. Btuh Rating  
System Power KW/COP  
HSPF (Btu/Watts-hr)  
160,000  
15.12/3.10  
88,000  
12.89/2.0  
208,000  
19.65/3.10  
128,000  
18.75/2.0  
204,000  
19.29/3.10  
118,000  
17.29/2.00  
Com pressor  
No./Type  
Sound Rating (BELS)4  
2/Trane 3-D Scroll  
9.2  
2/Copeland Scroll  
9.4  
2/Copeland Scroll  
9.4  
Outdoor Coil — Type  
Tube Size (in.) OD  
Face Area (sq ft)  
Rows/FPI  
Hi-Performance  
.375  
Hi-Performance  
.375  
35.3  
Hi-Performance  
.375  
35.3  
3/16  
28.21  
2/16  
3/16  
Refrigerant Control  
Expansion Valve  
Expansion Valve  
Expansion Valve  
Indoor Coil — Type  
Tube Size (in.)  
Hi-Performance  
.375  
Hi-Performance  
.375  
Hi-Performance  
.375  
Face Area (sq ft)  
17.50  
26.00  
26.00  
Rows/FPI  
2/15  
3/15  
3/15  
Refrigerant Control  
Drain Connection No./Size (in.)  
Capillary Tube  
1/1.00 NPT  
Capillary Tube  
1/1.00 NPT  
Capillary Tube  
1/1.00 NPT  
Outdoor Fan — Type  
No. Used/Diameter (in.)  
Drive Type/No. Speeds  
CFM  
Propeller  
2/26  
Direct/1  
11,200  
2/.50  
Propeller  
2/28  
Direct/1  
13,800  
2/1.0  
Propeller  
2/28  
Direct/1  
13,800  
2/1.0  
No. Motors/HP  
Motor RPM  
1,100  
1,125  
1,125  
Indoor Fan — Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
FC Centrifugal  
1
1
Diameter x Width (in.)  
Drive Type/No. Speeds  
No. Motors  
15 x 15  
Belt/1  
1
18 x 18  
Belt/1  
1
18 x 18  
Belt/1  
1
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size (Standard/Oversized)  
3.0/5.0  
1,740/3,450  
145T/145T  
5.0/7.5  
3,450/3,450  
184T/184T  
5.0/7.5  
3,450/3,450  
184T/184T  
Filters — Type Furnished6  
(No.) Size Recommended (in.)  
Throwaway  
(2) 20 x 20 x 2  
(4) 20 x 25 x 2  
Throwaway  
(4) 20 x 20 x 2  
(4) 20 x 25 x 2  
Throwaway  
(8) 20 x 25 x 2  
Refrigerant Charge (Lbs of R-22)5  
13.2/12.8/Circuit  
22.0/21.0/Circuit  
22.0/21.0/Circut  
NOTES:  
1. Cooling Perform ance and Heating Perform ance is rated at 95°F am bient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan m otor  
heat. ARI capacity is net and includes the effect of fan m otor heat. Units are suitable for operation to ±20% of nom inal cfm . Certified in accordance with the Unitary Large  
Equipm ent certification program , which is based on ARI Standard 340/360-93.  
2. EER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm .  
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.  
5. Refrigerant charge is an approxim ate value. For a m ore precise value, see unit nam eplate and service instructions.  
6. Optional 2 inch pleated filter also available.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Perform ance  
Data  
(1Ton)  
Table PD-1 — Gross Cooling Capacities (MBh) 12½ Ton Downflow Three Phase WCD150B  
Ambient Temperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
Entering Wet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 140.0 113.0 153.0 90.8 158.0 57.9 128.0 106.0 149.0 83.3 160.0 56.3 116.0 99.8 137.0 83.3 157.0 53.5 104.0 93.3 124.0 77.1 148.0 48.9  
80 141.0 134.0 154.0 105.0 159.0 78.3 130.0 128.0 149.0 104.0 161.0 77.4 119.0 119.0 138.0 98.3 157.0 74.3 109.0 109.0 125.0 91.8 148.0 69.6  
85 146.0 146.0 155.0 124.0 160.0 94.3 139.0 139.0 150.0 125.0 162.0 95.8 129.0 129.0 138.0 119.0 158.0 94.9 119.0 119.0 125.0 113.0 148.0 90.2  
90 153.0 153.0 156.0 143.0 162.0 111.0 148.0 148.0 151.0 145.0 163.0 114.0 140.0 140.0 139.0 139.0 158.0 114.0 130.0 130.0 129.0 129.0 148.0 111.0  
75 143.0 119.0 154.0 93.5 159.0 59.0 132.0 113.0 152.0 87.2 161.0 57.4 119.0 106.0 141.0 88.6 159.0 54.8 107.0 99.5 127.0 82.3 151.0 50.9  
80 145.0 141.0 156.0 108.0 160.0 79.2 134.0 134.0 152.0 109.0 162.0 79.5 124.0 124.0 141.0 104.0 160.0 77.2 114.0 114.0 128.0 97.5 151.0 72.9  
85 150.0 150.0 157.0 128.0 162.0 97.0 145.0 145.0 153.0 131.0 164.0 98.4 135.0 135.0 142.0 127.0 160.0 98.9 125.0 125.0 129.0 120.0 152.0 95.3  
90 156.0 156.0 158.0 148.0 164.0 112.0 153.0 153.0 155.0 153.0 165.0 118.0 146.0 146.0 146.0 146.0 161.0 120.0 136.0 136.0 136.0 136.0 152.0 118.0  
75 145.0 124.0 155.0 96.1 160.0 60.0 135.0 119.0 153.0 90.7 162.0 58.5 122.0 112.0 144.0 93.8 160.0 55.7 110.0 105.0 130.0 87.4 154.0 52.4  
80 147.0 147.0 157.0 111.0 162.0 80.5 139.0 139.0 154.0 113.0 163.0 80.9 129.0 129.0 144.0 110.0 161.0 79.9 118.0 118.0 131.0 103.0 154.0 75.9  
85 153.0 153.0 158.0 132.0 164.0 97.4 149.0 149.0 155.0 137.0 165.0 101.0 140.0 140.0 145.0 134.0 162.0 102.0 130.0 130.0 132.0 128.0 154.0 100.0  
90 159.0 159.0 160.0 152.0 166.0 115.0 157.0 157.0 157.0 157.0 166.0 121.0 151.0 151.0 151.0 151.0 163.0 125.0 141.0 141.0 141.0 141.0 154.0 124.0  
75 147.0 128.0 156.0 98.4 160.0 60.0 138.0 125.0 155.0 92.7 163.0 59.5 125.0 118.0 147.0 88.6 161.0 57.2 112.0 111.0 132.0 92.4 155.0 52.5  
80 150.0 150.0 158.0 113.0 162.0 81.2 144.0 144.0 156.0 117.0 164.0 82.1 133.0 133.0 147.0 115.0 162.0 82.1 122.0 122.0 133.0 108.0 156.0 78.7  
85 156.0 156.0 159.0 135.0 164.0 98.4 153.0 153.0 157.0 142.0 166.0 103.0 145.0 145.0 148.0 141.0 163.0 106.0 134.0 134.0 134.0 134.0 156.0 104.0  
90 160.0 160.0 161.0 156.0166.0 116.0 160.0160.0160.0160.0 167.0 123.0155.0155.0155.0155.0165.0129.0 146.0 146.0 146.0 146.0 157.0 130.0  
4500  
5000  
5500  
6000  
NOTES:  
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.  
3. MBH = Total Gross Capacity  
4. SHC = Sensible Heat Capacity  
Table PD-2 — Gross Cooling Capacities (MBh) 12½ Ton HorizontalThree Phase WCH150B  
Ambient Temperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
Entering Wet Bulb (F)  
73 61 67  
CFM  
Bulb  
61  
67  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 140.0 113.0 153.0 91.1 159.0 58.0 128.0 106.0 149.0 83.3 160.0 56.2 116.0 100.0 137.0 82.9 157.0 53.5 104.0 93.5 124.0 76.7 147.0 48.9  
80 141.0 134.0 154.0 105.0 160.0 78.3 130.0 128.0 149.0 104.0 161.0 77.5 119.0 119.0 138.0 98.4 157.0 74.3 109.0 109.0 124.0 91.9 148.0 69.6  
85 146.0 146.0 155.0 124.0 161.0 94.3 139.0 139.0 149.0 125.0 162.0 96.0 129.0 129.0 138.0 119.0 158.0 95.0 119.0 119.0 125.0 113.0 148.0 90.2  
90 153.0 153.0 156.0 143.0 163.0 110.0 148.0 148.0 151.0 145.0 163.0 114.0 140.0 140.0 139.0 139.0 158.0 115.0 130.0 130.0 129.0 129.0 148.0 111.0  
75 143.0 119.0 154.0 93.3 160.0 59.0 132.0 113.0 151.0 86.8 161.0 57.4 119.0 106.0 141.0 88.2 159.0 54.7 107.0 99.8 127.0 81.8 151.0 50.8  
80 145.0 142.0 156.0 109.0 162.0 79.9 134.0 134.0 152.0 109.0 162.0 79.6 124.0 124.0 141.0 104.0 159.0 77.3 114.0 114.0 128.0 97.7 151.0 72.9  
85 150.0 150.0 157.0 129.0 164.0 96.6 145.0 145.0 152.0 131.0 164.0 98.7 135.0 135.0 142.0 127.0 160.0 99.1 125.0 125.0 129.0 121.0 151.0 95.5  
90 156.0 156.0 158.0 149.0 164.0 112.0 153.0 153.0 153.0 153.0 165.0 118.0 146.0 146.0 146.0 146.0 161.0 120.0 136.0 136.0 136.0 136.0 151.0 118.0  
75 145.0 124.0 156.0 95.9 160.0 60.1 135.0 119.0 153.0 90.8 162.0 58.5 122.0 112.0 144.0 93.2 160.0 55.8 110.0 106.0 130.0 86.9 153.0 52.3  
80 147.0 147.0 157.0 111.0 162.0 80.8 139.0 139.0 154.0 114.0 163.0 81.0 129.0 129.0 144.0 110.0 161.0 80.1 118.0 118.0 130.0 103.0 154.0 76.0  
85 154.0 154.0 158.0 133.0 164.0 97.9 149.0 149.0 155.0 137.0 165.0 101.0 140.0 140.0 145.0 135.0 162.0 103.0 130.0 130.0 132.0 128.0 154.0 100.0  
90 159.0 159.0 160.0 153.0 166.0 115.0 157.0 157.0 157.0 157.0 167.0 121.0 151.0 151.0 151.0 151.0 163.0 125.0 141.0 141.0 141.0 141.0 154.0 124.0  
75 147.0 129.0 157.0 98.2 161.0 60.6 138.0 125.0 155.0 92.9 163.0 59.5 125.0 118.0 146.0 88.7 161.0 57.1 111.0 111.0 132.0 91.8 155.0 52.5  
80 150.0 150.0 158.0 114.0 163.0 81.5 144.0 144.0 156.0 118.0 164.0 82.1 133.0 133.0 147.0 115.0 162.0 82.3 122.0 122.0 133.0 109.0 155.0 78.8  
85 156.0 156.0 160.0 136.0 165.0 99.1 153.0 153.0 157.0 143.0 166.0 103.0 145.0 145.0 148.0 142.0 163.0 106.0 134.0 134.0 134.0 134.0 156.0 105.0  
90 161.0 161.0 162.0 157.0 167.0 117.0 160.0160.0160.0160.0168.0124.0155.0155.0155.0155.0164.0130.0 146.0 146.0 146.0 146.0156.0130.0  
4500  
5000  
5500  
6000  
NOTES:  
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.  
3. MBH = Total Gross Capacity  
4. SHC = Sensible Heat Capacity  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Perform ance  
Data  
(15 Ton)  
Table PD-3 — Gross Cooling Capacities (MBh) 15Ton Downflow and HorizontalThree Phase WC*180B  
AmbientTemperature ( F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
CFM  
Entering Wet Bulb (F)  
73 61  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
5400  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 170.0 133.0 186.0 104.0 194.0 71.6 156.0 126.0 180.0 100.0 194.0 69.4 141.0 118.0 166.0 102.0 189.0 66.1 125.0 110.0 150.0 95.1 177.0 60.6  
80 170.0 157.0 186.0 126.0 196.0 96.2 157.0 150.0 180.0 123.0 195.0 93.4 143.0 142.0 167.0 117.0 189.0 89.3 130.0 130.0 150.0 109.0 177.0 83.8  
85 175.0 175.0 188.0 147.0 197.0 114.0 165.0 165.0 181.0 146.0 196.0 115.0 153.0 153.0 167.0 140.0 190.0 113.0 141.0 141.0 151.0 132.0 178.0 107.0  
90 183.0 183.0189.0169.0 199.0 133.0 177.0 177.0 182.0169.0 197.0 136.0165.0165.0169.0164.0 190.0 135.0153.0153.0153.0153.0178.0130.0  
75 173.0 140.0 187.0 115.0 195.0 71.9 160.0 133.0 183.0 105.0 195.0 70.8 145.0 125.0 170.0 109.0 191.0 67.7 129.0 117.0 153.0 101.0 181.0 62.1  
80 175.0 165.0 189.0 130.0 197.0 100.0 162.0 159.0 183.0 129.0 197.0 98.9 148.0 148.0 171.0 123.0 191.0 92.5 135.0 135.0 154.0 115.0 181.0 87.3  
85 180.0 180.0 190.0 153.0 199.0 115.0 172.0 172.0 184.0 153.0 198.0 118.0 160.0 160.0 171.0 148.0 192.0 117.0 148.0 148.0 155.0 140.0 181.0 112.0  
90 188.0 188.0 192.0 175.0 201.0 136.0183.0183.0186.0178.0200.0140.0173.0173.0175.0 174.0 193.0 141.0 160.0160.0160.0160.0182.0 137.0  
75 176.0 145.0 189.0 119.0 196.0 74.1 164.0 140.0 185.0 107.0 196.0 72.2 148.0 132.0 174.0 115.0 193.0 68.6 132.0 123.0 157.0 108.0 183.0 64.8  
80 178.0 172.0 191.0 133.0 198.0 99.0 166.0 166.0 186.0 134.0 197.0 98.4 153.0 153.0 175.0 129.0 193.0 95.5 140.0 140.0 157.0 121.0 184.0 90.6  
85 184.0 184.0 192.0 157.0 201.0 120.0 178.0 178.0 187.0 160.0 200.0 121.0 166.0 166.0 175.0 156.0 194.0 121.0 153.0 153.0 159.0 149.0 184.0 118.0  
90 191.0 191.0 194.0 181.0 203.0140.0 187.0 187.0 189.0186.0202.0144.0179.0179.0179.0179.0 196.0 146.0 167.0 167.0 166.0166.0185.0144.0  
75 179.0 151.0 190.0 122.0 197.0 75.3 167.0 146.0 187.0 111.0 197.0 73.5 151.0 138.0 177.0 121.0 194.0 69.1 135.0 130.0 159.0 114.0 185.0 65.5  
80 181.0 179.0 192.0 136.0 199.0 100.0 171.0 171.0 188.0 138.0 199.0 99.9 158.0 158.0 177.0 135.0 195.0 98.4 145.0 145.0 160.0 127.0 186.0 93.4  
85 187.0 187.0 194.0 161.0 202.0 122.0 182.0 182.0 189.0 166.0 201.0 124.0 172.0 172.0 179.0 164.0 196.0 125.0 159.0 159.0 162.0 156.0 186.0 123.0  
90 194.0 194.0 196.0 186.0205.0144.0 191.0 191.0 191.0 191.0 203.0148.0184.0184.0184.0184.0 198.0 151.0 172.0172.0172.0172.0 187.0 150.0  
6000  
6600  
7200  
NOTES:  
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.  
3. MBH = Total Gross Capacity  
4. SHC = Sensible Heat Capacity  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Perform ance  
Data  
(20 Ton)  
Table PD-4 — Gross Cooling Capacities (MBh) 20Ton Downflow Three Phase WCD240B  
Ambient Temperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
CFM  
Entering Wet Bulb (F)  
73 61  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 212.0 177.0 233.0 137.0 243.0 89.7 198.0 173.0 228.0 133.0 244.0 87.3 179.0 164.0 211.0 130.0 239.0 83.1 160.0 154.0 189.0 115.0 225.0 76.8  
80 219.0 218.0 234.0 165.0 246.0 122.0 204.0 204.0 229.0 168.0 247.0 123.0 188.0 188.0 212.0 160.0 240.0 118.0 172.0 172.0 190.0 150.0 225.0 112.0  
85 229.0 229.0 236.0 197.0 249.0 148.0 220.0 220.0 231.0 202.0 249.0 153.0 205.0 205.0 215.0 196.0 242.0 153.0 189.0 189.0 194.0 186.0 226.0 146.0  
90 238.0238.0238.0 227.0 252.0 174.0 234.0234.0233.0233.0252.0183.0222.0222.0222.0222.0242.0186.0206.0206.0206.0206.0 227.0 181.0  
75 218.0 193.0 237.0 144.0 244.0 91.2 204.0 185.0 232.0 139.0 246.0 89.1 184.0 175.0 216.0 131.0 242.0 85.0 162.0 162.0 193.0 128.0 229.0 78.8  
80 224.0 224.0 239.0 173.0 247.0 123.0 213.0 213.0 233.0 176.0 249.0 126.0 196.0 196.0 217.0 170.0 243.0 124.0 180.0 180.0 195.0 160.0 230.0 117.0  
85 234.0 234.0 241.0 207.0 250.0 150.0 228.0 228.0 235.0 213.0 252.0 158.0 215.0 215.0 221.0 210.0 244.0 159.0 197.0 197.0 197.0 197.0 230.0 155.0  
90 242.0242.0245.0238.0253.0178.0240.0240.0240.0240.0254.0190.0 231.0 231.0 231.0 231.0 246.0195.0 216.0216.0216.0216.0232.0193.0  
75 223.0 201.0 238.0 148.0 245.0 93.4 209.0 196.0 235.0 145.0 248.0 90.6 189.0 186.0 220.0 138.0 244.0 86.8 168.0 168.0 196.0 136.0 232.0 80.6  
80 229.0 229.0 241.0 177.0 248.0 139.0 220.0 220.0 236.0 184.0 250.0 128.0 204.0 204.0 221.0 180.0 246.0 129.0 186.0 186.0 199.0 170.0 233.0 122.0  
85 238.0 238.0 244.0 212.0 252.0 152.0 234.0 234.0 239.0 223.0 253.0 161.0 222.0 222.0 226.0 223.0 247.0 165.0 205.0 205.0 205.0 205.0 233.0 164.0  
90 245.0245.0 247.0 245.0255.0 181.0 245.0245.0245.0245.0256.0 195.0 238.0238.0238.0238.0249.0203.0224.0224.0224.0224.0236.0205.0  
75 226.0 208.0 241.0 151.0 246.0 94.2 214.0 206.0 236.0 148.0 249.0 91.4 191.0 191.0 223.0 144.0 245.0 88.6 174.0 174.0 199.0 143.0 235.0 82.4  
80 232.0 232.0 243.0 185.0 250.0 126.0 226.0 226.0 238.0 190.0 251.0 115.0 211.0 211.0 225.0 189.0 247.0 123.0 193.0 193.0 203.0 179.0 235.0 127.0  
85 241.0 241.0 245.0 222.0 253.0 155.0 239.0 239.0 242.0 231.0 255.0 165.0 229.0 229.0 229.0 229.0 249.0 170.0 212.0 212.0 212.0 212.0 236.0 171.0  
90 248.0248.0 247.0 247.0 256.0184.0248.0248.0248.0248.0258.0200.0243.0243.0243.0243.0252.0 210.0 231.0 231.0 231.0 231.0 239.0215.0  
7200  
8000  
8800  
9600  
NOTES:  
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.  
3. MBH = Total Gross Capacity  
4. SHC = Sensible Heat Capacity  
Table PD-5 — Gross Cooling Capacities (MBh) 20Ton Horizontal Three Phase WCD240B  
Ambient Temperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
CFM  
Entering Wet Bulb (F)  
73 61  
Bulb  
61  
67  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 217.0 181.0 238.0 140.0 248.0 91.4 202.0 177.0 233.0 136.0 249.0 88.9 183.0 167.0 215.0 132.0 244.0 84.7 163.0 157.0 192.0 117.0 229.0 78.3  
80 224.0 223.0 239.0 168.0 250.0 124.0 208.0 208.0 233.0 171.0 251.0 126.0 192.0 192.0 216.0 163.0 245.0 121.0 175.0 175.0 194.0 153.0 229.0 114.0  
85 233.0 233.0 241.0 201.0 253.0 151.0 224.0 224.0 235.0 206.0 254.0 156.0 209.0 209.0 219.0 200.0 246.0 156.0 192.0 192.0 198.0 190.0 230.0 149.0  
90 242.0 242.0242.0230.0256.0 177.0 238.0238.0238.0238.0 257.0 186.0226.0226.0226.0226.0 247.0 189.0 210.0 210.0 210.0 210.0 231.0 185.0  
75 223.0 197.0 241.0 147.0 249.0 93.5 208.0 188.0 236.0 142.0 251.0 90.8 188.0 178.0 220.0 134.0 247.0 86.6 165.0 165.0 196.0 130.0 233.0 80.3  
80 228.0 228.0 244.0 176.0 252.0 126.0 217.0 217.0 237.0 180.0 254.0 128.0 200.0 200.0 221.0 174.0 248.0 126.0 183.0 183.0 199.0 163.0 234.0 119.0  
85 238.0 238.0 246.0 211.0 255.0 153.0 233.0 233.0 240.0 217.0 256.0 161.0 219.0 219.0 225.0 214.0 249.0 163.0 201.0 201.0 201.0 201.0 234.0 158.0  
90 246.0 246.0250.0243.0258.0 181.0 245.0245.0245.0245.0259.0 194.0 235.0235.0235.0235.0 251.0 199.0 220.0220.0220.0220.0236.0 197.0  
75 228.0 205.0 243.0 151.0 250.0 95.2 213.0 200.0 239.0 147.0 252.0 92.3 193.0 189.0 224.0 140.0 249.0 88.5 172.0 172.0 200.0 138.0 237.0 82.1  
80 233.0 233.0 245.0 181.0 253.0 142.0 224.0 224.0 240.0 187.0 255.0 131.0 208.0 208.0 225.0 183.0 250.0 131.0 190.0 190.0 203.0 173.0 237.0 124.0  
85 242.0 242.0 248.0 216.0 256.0 155.0 239.0 239.0 243.0 227.0 258.0 165.0 227.0 227.0 230.0 227.0 252.0 169.0 209.0 209.0 209.0 209.0 238.0 167.0  
90 249.0 249.0252.0250.0260.0184.0249.0249.0249.0249.0 261.0 199.0 242.0242.0242.0242.0254.0 207.0 228.0228.0228.0228.0240.0208.0  
75 231.0 212.0 245.0 153.0 251.0 96.0 218.0 210.0 241.0 151.0 253.0 93.1 195.0 195.0 227.0 146.0 250.0 90.3 177.0 177.0 203.0 146.0 239.0 84.0  
80 237.0 237.0 247.0 188.0 254.0 128.0 230.0 230.0 243.0 194.0 256.0 117.0 215.0 215.0 229.0 193.0 251.0 125.0 196.0 196.0 207.0 183.0 240.0 130.0  
85 245.0 245.0 249.0 226.0 258.0 158.0 243.0 243.0 246.0 236.0 260.0 168.0 233.0 233.0 233.0 233.0 253.0 173.0 216.0 216.0 216.0 216.0 241.0 175.0  
90 253.0 253.0252.0252.0 261.0 187.0 253.0253.0253.0253.0263.0204.0 247.0 247.0 247.0 247.0 256.0214.0235.0235.0235.0235.0244.0219.0  
7200  
8000  
8800  
9600  
NOTES:  
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.  
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.  
3. MBH = Total Gross Capacity  
4. SHC = Sensible Heat Capacity  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Perform ance  
Data  
(1Ton)  
Table PD-6 — Evaporator Fan Performance — 12½ Ton — WC*150B  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Field Supplied Low Static Drive (1)  
3 HP Standard Motor & Drive  
4000  
4500  
5000  
5500  
6000  
506  
541  
580  
626  
674  
0.69  
0.98  
1.31  
1.68  
2.10  
537  
572  
612  
656  
699  
0.80  
1.09  
1.39  
1.80  
2.28  
568  
603  
640  
682  
727  
0.92  
1.21  
1.51  
1.89  
2.37  
599  
634  
672  
709  
749  
1.03  
1.32  
1.67  
2.04  
2.48  
631  
664  
700  
738  
774  
1.15  
1.43  
1.78  
2.22  
2.66  
662  
693  
727  
763  
801  
1.26  
1.55  
1.90  
2.34  
2.85  
694  
721  
754  
788  
825  
1.37  
1.68  
2.03  
2.46  
3.00  
726 1.48  
749 1.81  
779 2.18  
813 2.60  
848 3.13  
756 1.59  
777 1.94  
805 2.32  
837 2.76  
871 3.27  
511  
551  
597  
644  
0.87  
1.16  
1.54  
1.99  
3 HP Standard Motor & High  
Static Drive Accessory  
Table PD-6 — Evaporator Fan Performance — 12½ Ton —WC*150B — Continued  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Drive  
3 HP Standard Motor & High Static Drive Accessory  
4000  
4500  
5000  
5500  
6000  
786  
806  
830  
860  
893  
1.70  
2.06  
2.47  
2.92  
3.43  
815  
833  
855  
883  
915  
1.82  
2.18  
2.61  
3.08  
3.59  
843  
860  
880  
906  
936  
1.94  
2.30  
2.74  
3.24  
3.77  
870  
886  
905  
929  
957  
2.06  
2.43  
2.88  
3.39  
3.94  
897  
912  
930  
952  
978  
2.20  
2.56  
3.01  
3.54  
4.12  
923  
937  
954  
975  
999  
2.34  
2.69  
3.15  
3.69  
4.29  
949  
962  
978  
997  
1020  
2.48  
2.83  
3.29  
3.84  
4.46  
974  
986  
1001  
1020  
1041  
2.64  
2.98  
3.43  
3.99  
4.62  
998 2.80  
1010 3.13  
1024 3.58  
1042 4.14  
1062 4.78  
1022 2.96  
1033 3.28  
1047 3.73  
1064 4.29  
1083 4.94  
5 HP Oversized Motor & Drive  
Trane's factory supplied motors, in commercial equipment, are definite  
purpose motors, specifically designed and tested to operate reliably and  
continuously at all cataloged conditions, Using the full horsepower range  
of our fan motors as shown in our tabulated data will not result in nuisance  
tripping or premature motor failure. Our product's warranty will not be  
affected.  
Fan motor heat (MBH) = 3.15 x Fan BHP.  
Data includes pressure Drop Due to Wet Coils and Filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-19 to determine add’l static pressure drop  
due to other options/accessories.  
Notes:  
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be  
necessary.  
PKGP-PRC001-EN  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15 Ton)  
Perform ance  
Data  
Table PD-7 — Evaporator Fan Performance — 15Ton — WC*180B  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Field Supplied Low Static Drive (1)  
3 HP Standard Motor & Drive  
4800  
5400  
6000  
6600  
7200  
546  
593  
648  
702  
761  
1.07  
1.34  
1.92  
2.63  
3.39  
574  
620  
674  
731  
789  
1.18  
1.49  
2.10  
2.72  
3.48  
601  
647  
699  
754  
811  
1.29  
1.65  
2.28  
2.92  
3.65  
629  
673  
727  
778  
831  
1.41  
1.80  
2.37  
3.08  
3.88  
657  
701  
749  
803  
855  
1.52  
1.96  
2.48  
3.17  
4.02  
685  
730  
774  
823  
877  
1.63  
2.13  
2.66  
3.29  
4.12  
713  
756  
801  
845  
895  
1.75  
2.25  
2.85  
3.47  
4.24  
740  
781  
825  
870  
915  
1.89  
2.37  
3.00  
3.70  
4.43  
767 2.03  
806 2.51  
848 3.13  
893 3.89  
938 4.68  
793 2.17  
830 2.66  
871 3.27  
914 4.03  
960 4.91  
5 HP Oversized Motor & Drive  
Table PD-7 — Evaporator Fan Performance — 15Ton —WC*180B — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM BHP RPM BHP RPM BHP  
1.10  
RPM BHP  
1.20  
RPM BHP  
1.30  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Drive  
3 HP Standard Motor & Field Supplied High Static Drive Accessory (2)  
4800  
5400  
6000  
6600  
7200  
819  
853  
893  
935  
980  
2.30  
2.82  
3.43  
4.18  
5.09  
846  
877  
915  
956  
999  
2.43  
2.98  
3.59  
4.33  
5.25  
872  
900  
936  
976  
2.56  
3.13  
3.77  
4.50  
5.40  
897  
924  
957  
996  
1037  
2.69  
3.28  
3.94  
4.68  
5.57  
922  
947  
978  
1016  
1056  
2.82  
3.43  
4.12  
4.87  
5.75  
947  
970  
999  
1035  
2.96  
3.58  
4.29  
5.07  
971  
993  
1020  
1054  
3.09  
3.72  
4.46  
5.26  
995  
1016  
1041  
1073  
3.24  
3.87  
4.62  
5.45  
1018 3.38  
1038 4.02  
1062 4.78  
1092 5.64  
1041 3.54  
1060 4.17  
1083 4.94  
1018  
5 HP Oversized Motor & Drive  
Fan motor heat (MBH) = 3.15 x Fan BHP.  
Data includes pressure Drop Due to Wet Coils and Filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-19 to determine add’l static pressure drop  
due to other options/accessories.  
5 HP Oversized Motor & Field  
Supplied High Static Drive (2)  
Notes:  
1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary.  
2. Field Supplied Motor Sheave IVP50 Required.  
Trane's factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed  
and tested to operate reliably and continuously at all cataloged conditions, Using the full horsepower range of  
our fan motors as shown in our tabulated data will not result in nuisance tripping or premature motor failure.  
Our product's warranty will not be affected.  
PKGP-PRC001-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(20 Ton)  
Perform ance  
Data  
Table PD-8 — Evaporator Fan Performance — 20Ton — WC*240B  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
5 HP Standard Motor & Field Supplied Low Static Drive (1)  
5 HP Standard Motor & Drive  
6400  
7200  
8000  
8800  
9600  
531  
576  
627  
678  
729  
1.80  
2.16  
3.16  
4.10  
5.21  
556  
605  
655  
705  
755  
1.97  
2.60  
3.39  
4.34  
5.49  
582  
631  
679  
729  
779  
2.14  
2.81  
3.63  
4.61  
5.77  
610  
655  
702  
751  
800  
2.28  
3.00  
3.86  
4.87  
6.06  
634  
678  
724  
771  
820  
2.44  
3.18  
4.07  
5.12  
6.34  
658  
701  
745  
791  
839  
2.61  
3.36  
4.28  
5.36  
6.61  
681  
722  
766  
811  
857  
2.79  
3.55  
4.48  
5.59  
6.88  
705 2.98  
743 3.74  
786 4.68  
830 5.81  
875 7.13  
729 3.19  
763 3.94  
805 4.90  
848 6.03  
893 7.37  
552  
605  
648  
702  
2.23  
3.01  
3.83  
4.91  
(2)  
7.5 HP Oversized Motor & Drive  
Table PD-8 — Evaporator Fan Performance — 20Ton —WC*240B — Continued  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
5 HP Standard Motor & Drive  
5 HP Standard Motor & High Static Drive Accessory  
6400  
7200  
8000  
8800  
9600  
753  
784  
824  
866  
910  
3.39  
4.15  
5.11  
6.26  
7.61  
776  
806  
842  
884  
927  
3.59  
4.38  
5.32  
6.49  
7.85  
799  
827  
860  
901  
943  
3.80  
4.61  
5.55  
6.73  
8.10  
822  
848  
880  
917  
960  
4.02  
4.84  
5.80  
6.96  
8.35  
844  
869  
899  
934  
975  
4.24  
5.07  
6.06  
7.20  
8.61  
865  
889  
918  
951  
4.47  
5.30  
6.31  
7.46  
886  
910  
937  
969  
4.69  
5.54  
6.56  
7.74  
906  
930  
956  
986  
4.92  
5.79  
6.81  
8.02  
925 5.16  
950 6.04  
974 7.07  
1004 8.30  
944 5.40  
969 6.29  
993 7.33  
7.5 HP Oversized Motor & Drive  
Trane's factory supplied motors, in commercial equipment, are definite  
purpose motors, specifically designed and tested to operate reliably  
and continuously at all cataloged conditions, Using the full horsepower  
range of our fan motors as shown in our tabulated data will not result in  
nuisance tripping or premature motor failure. Our product's warranty  
will not be affected.  
Notes:  
Fan motor heat (MBH) = 3.15 x Fan BHP.  
Data includes pressure Drop Due to Wet Coils and Filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-19 to determine add’l static pressure drop  
due to other options/accessories.  
Notes:  
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be  
necessary.  
2. 7.5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 Required. Field  
Supplied Belt may be necessary.  
PKGP-PRC001-EN  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Perform ance  
Data  
Table PD-9 — Standard Motor & Drive/Fan Speed (RPM)  
Unit  
Model No.  
6 Turns  
Open  
5 Turns  
Open  
4 Turns  
Open  
3 Turns  
Open  
2 Turns  
Open  
1 Turn  
Open  
Tons  
Closed  
12½  
15  
20  
WC*150B  
WC*180B  
WC*240B  
640  
679  
615  
680  
721  
659  
720  
764  
703  
760  
806  
747  
800  
849  
791  
840  
891  
835  
N/A  
N/A  
N/A  
Factory set at 3 turns open.  
Table PD-10 — Standard Motor With High Static Drive Fan Speed (RPM)  
Unit  
Model No.  
6 Turns  
Open  
5 Turns  
Open  
4 Turns  
Open  
3 Turns  
Open  
2 Turns  
Open  
1 Turn  
Open  
Tons  
Closed  
12½  
20  
WC*150B  
WC*240B  
807  
835  
857  
879  
908  
923  
958  
967  
1009  
1011  
1059  
1055  
N/A  
N/A  
Table PD-11 — Oversized Motor & Drive/Fan Speed (RPM)  
Unit  
Model No.  
6 Turns  
Open  
5 Turns  
Open  
4 Turns  
Open  
3 Turns  
Open  
2 Turns  
Open  
1 Turn  
Open  
Tons  
Closed  
12½  
15  
20  
WC*150B  
WC*180B  
WC*240B  
869  
806  
816  
923  
856  
853  
978  
907  
890  
1032  
957  
928  
1087  
1008  
965  
1141  
1058  
1002  
N/A  
N/A  
N/A  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Perform ance  
Data  
Table PD-12 — Static Pressure Drops Through Accessories (Inches Water Column)  
Econom izer with  
OA /RA Dam pers1  
Electric Heater  
Accessory (KW)2  
Unit  
Model No.  
Standard  
2 Inch  
Tons  
12½  
CFM  
Filters3 Pleated Filters4  
100% OA  
100% RA  
5-12  
14-23  
36  
54  
72  
4000  
5000  
6000  
0.05  
0.07  
0.11  
0.08  
0.11  
0.15  
0.20  
0.26  
0.35  
0.02  
0.03  
0.04  
0.03  
0.04  
0.06  
0.03  
0.05  
0.07  
0.04  
0.06  
0.09  
WC*150B  
WC*180B  
WCD240B  
WCH240B  
4800  
6000  
7200  
0.07  
0.11  
0.15  
0.10  
0.15  
0.19  
0.24  
0.35  
0.42  
0.03  
0.04  
0.05  
0.04  
0.06  
0.09  
0.04  
0.07  
0.10  
0.05  
0.08  
0.12  
15  
6400  
8000  
9600  
0.07  
0.11  
0.16  
0.11  
0.15  
0.02  
0.22  
0.31  
0.44  
0.04  
0.05  
0.07  
0.06  
0.10  
0.14  
0.08  
0.12  
0.17  
0.09  
0.14  
0.20  
20  
6400  
8000  
9600  
0.06  
0.09  
0.13  
0.01  
0.13  
0.17  
0.22  
0.31  
0.44  
0.04  
0.05  
0.07  
0.06  
0.10  
0.14  
0.08  
0.12  
0.17  
0.09  
0.14  
0.20  
NOTES:  
1. OA = Outside Air and RA = Return Air.  
2. Nom inal KW ratings at 240, 480, 600 volts.  
3. Tested with:2" filters 12½-20 tons.  
4. Difference in pressure drop should be considered when utilizing optional 2” pleated filters.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(1Ton)  
Perform ance  
Data  
Table PD-13 — 12½ Ton Downflow Three Phase Heating Capacities (Net) WCD150B3, B4, BW At 5000 CFM  
Integrated Heating Capacity (MBh/1000)  
At Indicated Indoor Dry Bulb Tem p.  
Total Power in Kilowatts At  
Indicated Indoor Dry Bulb Tem p.  
Outdoor  
Tem p.  
F.  
60  
51.9  
56.8  
62.1  
67.9  
74.1  
80.7  
87.8  
70  
50.3  
55.3  
60.7  
66.4  
72.6  
79.1  
86  
75  
49.6  
54.6  
60  
65.7  
71.9  
78.3  
85.1  
80  
49  
54  
59.4  
65.1  
71.1  
77.6  
84.3  
60  
70  
75  
80  
-8  
-3  
2
7
9.56  
9.61  
9.74  
9.85  
9.98  
10.13  
10.3  
10.48  
10.68  
10.89  
11.11  
11.93  
12.2  
10.37  
10.45  
10.55  
10.72  
10.87  
11.03  
11.22  
11.41  
11.62  
11.84  
12.07  
12.96  
13.25  
13.49  
13.86  
14.24  
14.64  
10.83  
10.92  
11.03  
11.2  
11.32  
11.42  
11.53  
11.71  
11.88  
12.06  
12.26  
12.48  
12.7  
12.94  
13.18  
14.14  
14.43  
14.67  
15.04  
15.44  
15.85  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
11.36  
11.53  
11.72  
11.92  
12.14  
12.37  
12.61  
13.53  
13.83  
14.06  
14.43  
14.82  
15.23  
95.3  
93.3  
92.3  
91.4  
103.2  
111.1  
119.2  
138.6  
148.1  
155.6  
168.8  
179.3  
189.9  
101  
99.9  
98.9  
108.6  
116.4  
135.3  
144.5  
151.4  
164.2  
174.3  
184.5  
107.4  
115.1  
133.8  
142.9  
149.4  
161.9  
171.8  
181.8  
106.3  
113.9  
132.3  
141.2  
147.4  
159.7  
169.4  
179.1  
12.46  
12.8  
13.17  
13.55  
For other airflow conditions, see heating capacity correction factor (Table PD-18).  
Net Heating Capacity and Power Input include indoor fan heat at nom inal cfm and .35 inch ESP. To obtain net  
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.  
Heating capacities and powers are integrated to include the effects of defrost in the frost region.  
All heating capacities and power (Kw) are at 70% OD relative hum idity.  
Table PD-14— 12½ Ton HorizontalThree Phase Heating Capacities (Net) WCH150B3, B4, BW At 5000 CFM  
Integrated Heating Capacity (MBh/1000)  
At Indicated Indoor Dry Bulb Tem p.  
Total Power in Kilowatts At  
Indicated Indoor Dry Bulb Tem p.  
Outdoor  
Tem p.  
F.  
60  
48.2  
52.7  
70  
46.6  
51.3  
75  
46  
50.6  
55.7  
80  
45.4  
50  
60  
70  
75  
80  
-8  
-3  
2
7
9.18  
9.23  
9.35  
9.46  
9.58  
9.73  
9.88  
10.06  
10.25  
10.45  
10.67  
11.53  
11.8  
12.04  
12.37  
12.72  
13.1  
9.96  
10.4  
10.87  
10.96  
11.07  
11.24  
11.4  
11.58  
11.77  
11.98  
12.2  
12.42  
12.66  
13.66  
13.96  
14.19  
14.55  
14.93  
15.33  
10.03  
10.13  
10.29  
10.43  
10.59  
10.77  
10.96  
11.16  
11.37  
11.6  
12.52  
12.8  
13.04  
13.39  
13.76  
14.15  
10.48  
10.58  
10.75  
10.9  
11.07  
11.25  
11.45  
11.66  
11.88  
12.11  
13.07  
13.36  
13.6  
57.7  
56.3  
55.1  
60.4  
66.1  
72.1  
78.4  
85.1  
92.1  
99.1  
106.3  
130.9  
139.8  
146.1  
158.4  
168.2  
178  
63.1  
61.7  
61.1  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
68.9  
67.5  
66.8  
75.2  
73.6  
72.9  
81.8  
80.1  
79.3  
88.9  
87  
86  
96.3  
94.2  
93.1  
103.7  
111.3  
137.3  
146.8  
154.4  
167.7  
178.1  
188.8  
101.4  
108.7  
133.9  
143.1  
150.1  
162.9  
173.1  
183.4  
100.2  
107.5  
132.4  
141.4  
148.1  
160.7  
170.6  
180.7  
13.95  
14.33  
14.73  
For other airflow conditions, see heating capacity correction factor (Table PD-18).  
Net Heating Capacity and Power Input include indoor fan heat at nom inal cfm and .40 inch ESP. To obtain net heating at  
other conditions, subtract fan heat at this condition and add fan heat at new condition.  
Heating capacities and powers are integrated to include the effects of defrost in the frost region.  
All heating capacities and power (Kw) are at 70% OD relative hum idity.  
PKGP-PRC001-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15 Ton)  
Perform ance  
Data  
Table PD-15 — 15Ton Downflow Three Phase Heating Capacities (Net) WC*180B3, B4, BW At 6000 CFM  
Integrated Heating Capacity (MBh/1000)  
At Indicated Indoor Dry Bulb Tem p.  
Total Power in Kilowatts At  
Indicated Indoor Dry Bulb Tem p.  
Outdoor  
Tem p.  
F.  
60  
59.4  
65  
70.9  
77.3  
84.3  
91.6  
99.3  
107.5  
116  
124.5  
133.3  
165.5  
176.4  
187.7  
198.5  
210.5  
222.7  
70  
58.3  
63.9  
69.9  
76.3  
83.1  
90.4  
98  
105.9  
114.2  
122.5  
131  
75  
57.9  
63.6  
69.5  
75.9  
82.7  
89.8  
97.3  
105.2  
113.4  
121.6  
130  
80  
57.7  
63.4  
69.3  
75.6  
82.3  
89.4  
96.8  
104.6  
112.7  
120.7  
129  
60  
70  
75  
80  
-8  
-3  
2
7
12.02  
12.05  
12.09  
12.15  
12.24  
12.34  
12.47  
12.62  
12.8  
12.65  
12.78  
12.9  
13.11  
13.27  
13.42  
13.57  
13.74  
13.92  
14.13  
14.36  
14.61  
14.88  
15.16  
16.12  
16.46  
16.82  
17.2  
13.64  
13.84  
14.01  
14.19  
14.39  
14.6  
14.83  
15.09  
15.36  
15.64  
15.94  
16.94  
17.29  
17.66  
18.05  
18.24  
18.71  
13.02  
13.16  
13.32  
13.51  
13.71  
13.94  
14.18  
14.44  
15.35  
15.68  
16.03  
16.19  
16.64  
17.1  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
13  
13.22  
14.04  
14.32  
14.63  
14.82  
15.24  
15.67  
162.5  
173.1  
184  
193.7  
205.4  
217.1  
161.1  
171.5  
182.3  
197  
202.8  
214.3  
159.8  
170  
180.5  
195  
200.3  
211.5  
17.42  
17.88  
For other airflow conditions, see heating capacity correction factor (Table PD-18).  
Net Heating Capacity and Power Input include indoor fan heat at nom inal cfm and .35 inch ESP. To obtain net  
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.  
Heating capacities and powers are integrated to include the effects of defrost in the frost region.  
All heating capacities and power (Kw) are at 70% OD relative hum idity.  
PKGP-PRC001-EN  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(20 Ton)  
Perform ance  
Data  
Table PD-16 — 20Ton Downflow Three Phase Heating Capacities (Net) WCD240B3, B4, BW At 8000 CFM  
Integrated Heating Capacity (MBh/1000)  
At Indicated Indoor Dry Bulb Tem p.  
Total Power in Kilowatts A  
Indicated Indoor Dry Bulb Tem p.  
Outdoor  
Tem p.  
F.  
60  
70  
75  
80  
60  
70  
75  
80  
-8  
-3  
2
7
78.1  
86.8  
96.0  
75.8  
84.4  
93.6  
74.9  
83.4  
92.4  
74.0  
82.5  
91.4  
16.7  
16.8  
16.9  
17.1  
17.3  
17.5  
17.7  
18.0  
18.3  
18.5  
18.7  
18.9  
19.0  
19.4  
19.9  
20.3  
20.8  
17.8  
17.9  
18.1  
18.3  
18.6  
18.8  
19.0  
19.3  
19.6  
19.8  
20.0  
20.2  
20.4  
20.8  
21.2  
21.7  
22.2  
18.4  
18.6  
18.7  
18.9  
19.2  
19.5  
19.8  
20.0  
20.3  
20.5  
20.7  
20.9  
21.1  
21.5  
21.9  
22.4  
23.0  
19.1  
19.3  
19.5  
19.7  
20.0  
20.2  
20.5  
20.8  
21.1  
21.3  
21.5  
21.7  
21.9  
22.3  
22.7  
23.2  
23.8  
106.4  
119.9  
131.0  
142.5  
154.5  
167.2  
180.8  
194.0  
213.9  
228.5  
243.4  
262.1  
278.3  
295.6  
103.8  
117.1  
128.0  
139.4  
151.2  
163.6  
176.9  
189.8  
209.0  
223.1  
237.4  
255.5  
271.2  
288.1  
102.0  
115.8  
126.6  
137.9  
149.6  
161.7  
174.8  
187.5  
206.6  
220.4  
234.5  
252.3  
267.7  
284.3  
100.9  
114.6  
125.3  
136.4  
148.0  
160.0  
172.9  
185.5  
204.3  
217.8  
231.7  
249.1  
264.1  
280.5  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
For other airflow conditions, see heating capacity correction factor (Table PD-18).  
Net Heating Capacity and Power Input include indoor fan heat at nom inal cfm and .40 inch ESP. To obtain net  
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.  
Heating capacities and powers are integrated to include the effects of defrost in the frost region.  
All heating capacities and power (Kw) are at 70% OD relative hum idity.  
Table PD-17 — 20Ton HorizontalThree Phase Heating Capacities (Net) WCH240B3, B4, BW At 8000 CFM  
Integrated Heating Capacity (MBh/1000)  
At Indicated Indoor Dry Bulb Tem p.  
Total Power in Kilowatts At  
Indicated Indoor Dry Bulb Tem p.  
Outdoor  
Tem p.  
F.  
60  
70  
75  
80  
60  
70  
75  
80  
--8  
-3  
2
77.7  
86.3  
95.5  
75.4  
84.0  
93.0  
74.5  
82.9  
92.0  
73.6  
82.0  
90.9  
15.4  
15.5  
15.6  
15.8  
16.0  
16.2  
16.4  
16.6  
16.9  
17.6  
17.9  
18.3  
19.0  
19.4  
19.8  
20.3  
20.8  
16.4  
16.5  
16.7  
16.9  
17.1  
17.3  
17.6  
17.8  
18.1  
18.9  
19.2  
19.6  
20.3  
20.7  
21.1  
21.6  
22.1  
17.0  
17.1  
17.3  
17.5  
17.8  
18.0  
18.2  
18.5  
18.7  
19.6  
19.9  
20.3  
21.0  
21.4  
21.9  
22.3  
22.9  
17.6  
17.8  
18.0  
18.2  
18.4  
18.7  
18.9  
19.2  
19.5  
20.4  
20.7  
21.0  
21.8  
22.2  
22.6  
23.1  
23.7  
7
105.9  
109.9  
120.0  
130.6  
141.6  
153.2  
179.7  
192.9  
210.6  
225.0  
239.6  
256.8  
272.6  
289.6  
103.2  
107.3  
117.3  
127.7  
138.5  
149.9  
175.9  
188.7  
205.8  
219.6  
233.7  
250.3  
265.7  
282.2  
101.5  
106.1  
116.1  
126.4  
137.1  
148.2  
173.8  
186.5  
203.4  
217.0  
230.9  
247.2  
262.3  
278.5  
100.4  
105.0  
114.8  
125.0  
135.6  
146.6  
172.0  
184.5  
201.1  
214.4  
228.0  
244.0  
258.8  
274.8  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
For other airflow conditions, see heating capacity correction factor (Table PD-18).  
Net Heating Capacity and Power Input include indoor fan heat at nom inal cfm and .40 inch ESP. To obtain net  
heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.  
Heating capacities and powers are integrated to include the effects of defrost in the frost region.  
All heating capacities and power (Kw) are at 70% OD relative hum idity.  
PKGP-PRC001-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Perform ance  
Data  
Table PD-18— Heating Capacity Correction Factors  
% Variation of Nom inal CFM  
Total Gross Capacity Multiplier  
- 20  
.96  
- 10  
.98  
0
+ 10  
1.01  
+ 20  
1.02  
1.0  
Table PD-19 — Auxiliary Electric Heat Capacity  
Total2  
Stage 1  
Stage 2  
Unit  
Model No.  
KW  
Input1  
MBh  
Output1  
No. of  
Stages  
KW  
Input1  
MBh  
Output1  
KW  
Input1  
MBh  
Output1  
Tons  
18.00  
36.00  
54.00  
61.00  
123.00  
184.00  
1
2
2
18.00  
18.00  
36.00  
61.00  
61.00  
123.00  
18.00  
18.00  
61.00  
61.00  
12½, 15  
WC*150B3, B4, BW  
WC*180B3, B4, BW  
36.00  
54.00  
72.00  
123.00  
184.00  
246.00  
2
2
2
18.00  
36.00  
36.00  
61.00  
123.00  
123.00  
18.00  
18.00  
36.00  
61.00  
61.00  
123.00  
20  
WC* 240B3, B4, BW  
NOTES:  
1. Does not include indoor fan power or heat.  
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =(  
Voltage  
2
)
x rated cap.  
Rated Voltage  
Table PD-20 —Electric Heater Voltage  
Correction Factors (Applicable to Auxiliary  
Heat Capacity)  
Nom inal  
Voltage  
Distribution  
Voltage  
Capacity  
Multiplier  
208  
230  
240  
0.75  
0.92  
1.00  
240  
480  
600  
440  
460  
480  
0.84  
0.94  
1.00  
540  
575  
600  
0.81  
0.92  
1.00  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Perform ance  
Data  
Table PD-21— AirTemperature Rise Across Electric Heaters (Degree F)  
12½ Ton  
5000 CFM  
Three Phase  
WC*150B  
15 Ton  
6000 CFM  
Three Phase  
WC*180B  
20 Ton  
8000 CFM  
Three Phase  
WC*240B  
KW  
9.00  
Stages  
1
1
1
2
2
2
2
11.4  
23.0  
34.1  
9.5  
19.0  
28.4  
17.30  
18.00  
27.00  
36.00  
54.00  
72.00  
14.2  
21.3  
28.5  
Table PD-22 — Electric Heater Temperature Rise Correction Factors  
% Variation From Nom inal CFM  
Tem perature Rise Multiplier  
- 20  
- 15 - 10  
1.17 1.11  
- 5  
0
+5  
+10  
+15  
+20  
1.25  
1.05 1.00  
0.95  
0.91  
0.87  
0.83  
PKGP-PRC001-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
Digital Display Zone Sensor  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone  
sensors.This  
sensor includes a  
digital display of  
set point  
adjustment and  
CO2 Sensing —The CO2 sensor has the  
ability to monitor space occupancy levels  
within the  
building by  
measuring the  
parts per million  
of CO2 (Carbon  
Dioxide) in the air.  
As the CO2 levels  
Field Installed Control Options  
Zone Sensors  
Zone sensors are the building occupants  
comfort control devices.They replace the  
conventional electro-mechanical  
thermostats.The following zone sensor  
options are available for Voyager units  
with the ReliaTel™ control:  
Manual Changeover  
Heat, Cool or Off  
System Switch. Fan  
Auto or Off Switch.  
One temperature  
setpoint lever.  
space temperature  
in F (Fahrenheit) or  
C (Celsius).  
Includes FAN and  
SYSTEM buttons  
(supports the  
service functions of  
increase, the  
outside air  
damper  
modulates to  
meet the CO2 space ventilation  
requirements.The CO2 sensor kit is  
available as a field installed accessory.  
the standard  
Economizer Controls  
sensor). E-squared memory stores last  
programmed set points. Requires 24 VAC  
(Volts AC).This sensor should be utilized  
with ReliaTel™ controls.  
The standard equipment offering is a  
fixed dry bulb changeover control. In  
addition, there are two optional controls,  
Enthalpy and Differential Enthalpy  
Control.  
Manual/Automatic Changeover  
Auto, Heat, Cool or Off System Switch.  
Fan Auto or Off  
Switch.Two  
temperature  
setpoint levers.  
Optional Status  
Indication LED lights,  
System On, Heat,  
Cool, or Service.  
Programmable Night Setback  
Auto or manual changeover with seven-  
day programming. Keyboard selection  
Enthalpy Control  
Replaces the dry bulb control with a wet  
bulb changeover controller which has a  
fully adjustable set point. Enthalpy control  
offers a higher level of comfort control,  
along with energy savings potential, than  
the standard dry bulb control. This is due  
to the additional wet bulb sensing  
capability.  
Differential Enthalpy  
Replaces the standard dry bulb control  
with two enthalpy sensors that compare  
total heat content of the indoor air and  
outdoor air to determine the most  
efficient air source.This control option  
offers the highest level of comfort control,  
plus energy efficiency, available.  
Remote Sensor  
Sensor(s) available  
for all zone sensors to  
provide remote  
of Heat, Cool, Fan, Auto, or On. All  
programmable sensors have System On,  
Heat, Cool, Service LED/indicators as  
standard. Night Setback Sensors have  
one (1) Occupied, one (1) Un-occupied,  
and two (2) Override programs per day.  
sensing capabilities.  
Remote Potentiometer  
Minimum position setting of economizer  
can be remotely adjusted with this  
accessory.  
Integrated  
Differential Pressure Switches  
ComfortTM  
This factory or field-installed option  
allows individual fan failure and dirty filter  
indication. The fan failure switch will  
disable all unit functions and “flash” the  
Service LED on the zone sensor. The dirty  
filter switch will light the Service LED on  
the zone sensor and will allow continued  
unit operation.  
System  
Sensor(s)  
available with  
optional  
temperature  
adjustment and  
override buttons  
to provide central  
control through a  
Trane Integrated  
ComfortTM system.  
DualThermistor Remote Zone Sensor  
This sensor will allow the customer to  
reduce the total number of remote  
sensors to obtain space temperature  
averaging. This sensor should be utilized  
with ReliaTel controls.  
Trane Communication Interface (TCI)  
This factory or field-installed micro-  
processor interface allows the unit to  
communicate toTranes Integrated  
ComfortTM system.  
PKGP-PRC001-EN  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-1 — Unit Wiring  
Standard Indoor Fan Motor  
Oversize Indoor Fan Motor  
Minimum Maxim um Fuse Size  
Unit  
Minimum  
Circuit  
Maxim um Fuse Size  
or Maximum  
Circuit Breaker1  
Unit  
Operating  
Circuit  
or Maximum  
Circuit Breaker1  
Tons  
12½  
ModelNo.  
Voltage Range  
Ampacity  
Ampacity  
WC*150B3  
WC*150B4  
WC*150BW  
187-253  
414-506  
517-633  
66.0  
31.0  
25.0  
80  
40  
30  
72.0  
34.0  
28.0  
80  
40  
35  
WC*180B3  
WC*180B4  
WC*180BW  
187-253  
414-506  
517-633  
77.0  
40.0  
32.0  
90  
45  
35  
83.0  
43.0  
34.0  
100  
50  
40  
15  
WC*240B3  
WC*240B4  
WC*240BW  
187-253  
414-506  
517-633  
96.0  
49.0  
38.0  
125  
60  
45  
103.0  
53.0  
41.0  
125  
60  
50  
20  
NOTE:  
1. HACR type circuit breaker per NEC.  
Table ED-2 — Electrical Characteristics — Power Exhaust Accessory  
Accessory  
Operating  
Voltage  
Am ps  
Accessory  
Tons  
Model Num ber  
Phase  
HP  
RPM  
FLA  
LRA  
BAYPWRX019  
BAYPWRX020  
BAYPWRX021  
208-230  
460  
1
1
1
3/4  
3/4  
3/4  
1040  
1040  
1040  
6.6  
3.2  
2.1  
13.5  
8.4  
12½, 15, 20  
575  
5.2  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)  
Standard Indoor Motor  
Oversize Indoor Motor  
Max Fuse Size Or  
To Use  
With  
Heater  
Model No.  
Heater  
Control  
Stages  
Max Fuse Size Or  
Tons  
12½  
KW Rating1  
MCA  
Max Circuit Breaker2  
MCA  
Max Circuit Breaker2  
2 0 8 /2 3 0 Vo lt s Th re e P h a s e  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
113/120  
160/175  
207/229  
125/125  
175/175  
225/250  
119/127  
166/181  
213/235  
125/150  
175/200  
225/250  
WCD150B3  
WCH150B3  
WCD180B3  
WCH180B3  
WCD240B3  
WCH240B3  
AYHHTRN318A  
AYHHTRP336A  
AYHHTRP354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
113/120  
160/175  
207/229  
125/125  
175/175  
225/250  
119/127  
166/181  
213/235  
125/150  
175/200  
225/250  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
124/131  
171/185  
218/240  
125/150  
175/200  
225/250  
130/137  
177/191  
224/246  
150/150  
200/200  
225/250  
15  
AYHHTRN318A  
AYHHTRP336A  
AYHHTRP354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
124/131  
171/185  
218/240  
125/150  
175/200  
225/250  
130/137  
177/191  
224/246  
150/150  
200/200  
225/250  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
190/204  
237/258  
284/312  
200/225  
250/300  
300/350  
197/212  
244/266  
291/320  
200/225  
250/300  
300/350  
20  
AYHHTRN336A  
AYHHTRN354A  
AYHHTRN372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
190/204  
237/258  
284/312  
200/225  
250/300  
300/350  
197/212  
177/266  
224/320  
200/225  
250/300  
300/350  
NOTES:  
1. Heater kw ratings are at 208/240 for 208/230V unit  
480V for 460 V unit  
2. HACR type circuit breaker per NEC.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)  
Standard Indoor Motor  
Oversize Indoor Motor  
Max Fuse Size Or  
To Use  
With  
Heater  
Model No.  
Heater  
Control  
Stages  
Max Fuse Size Or  
Tons  
12½  
KW Rating1  
MCA  
Max Circuit Breaker2  
MCA  
Max Circuit Breaker2  
4 6 0 Vo lt s Th re e P h a s e  
AYDHTRK418A  
AYDHTRK436A  
AYDHTRK454A  
18.0  
36.0  
54.0  
1
2
2
58  
85  
112  
60  
90  
61  
88  
70  
90  
WCD150B4  
WCH150B4  
WCD180B4  
WCH180B4  
WCD240B4  
WCH240B4  
125  
115  
125  
AYHHTRP418A  
AYHHTRP436A  
AYHHTRP454A  
18.0  
36.0  
54.0  
1
2
2
58  
85  
112  
60  
90  
61  
88  
70  
90  
125  
115  
125  
AYDHTRK418A  
AYDHTRK436A  
AYDHTRK454A  
18.0  
36.0  
54.0  
1
2
2
67  
94  
121  
70  
100  
125  
70  
97  
124  
70  
100  
125  
15  
AYHHTRP418A  
AYHHTRP436A  
AYHHTRP454A  
18.0  
36.0  
54.0  
1
2
2
67  
94  
121  
70  
90  
125  
70  
97  
124  
70  
100  
125  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
36.0  
54.0  
72.0  
2
2
2
104  
131  
158  
110  
150  
175  
107  
134  
161  
110  
150  
175  
20  
AYHHTRN436A  
AYHHTRN454A  
AYHHTRN472A  
36.0  
54.0  
72.0  
2
2
2
104  
131  
158  
110  
150  
175  
107  
134  
161  
110  
150  
175  
NOTES:  
1. Heater kw ratings are at 480V for 460V unit  
2. HACR type circuit breaker per NEC.  
PKGP-PRC001-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)  
Standard Indoor Motor  
Oversize Indoor Motor  
Max Fuse Size Or  
To Use  
With  
Heater  
Model No.  
Heater  
Control  
Stages  
Max Fuse Size Or  
Tons  
12½  
KW Rating1  
MCA  
Max Circuit Breaker2  
MCA  
Max Circuit Breaker2  
5 7 5 Vo lt s Th re e P h a s e  
AYDHTRKW18A  
AYDHTRKW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
47  
69  
90  
50  
70  
90  
49  
71  
93  
50  
80  
100  
WCD150BW  
WCH150BW  
WCD180BW  
WCH180BW  
WCD240BW  
WCH240BW  
AYHHTRNW18A  
AYHHTRQW36A  
AYHHTRPW54A  
18.0  
36.0  
54.0  
1
2
2
47  
69  
90  
50  
70  
90  
49  
71  
93  
50  
80  
100  
AYDHTRKW18A  
AYDHTRKW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
54  
76  
97  
60  
80  
100  
56  
78  
99  
60  
80  
100  
15  
AYHHTRNW18A  
AYHHTRQW36A  
AYHHTRPW54A  
18.0  
36.0  
54.0  
1
2
2
54  
76  
97  
60  
80  
100  
56  
78  
99  
60  
80  
100  
AYDHTRLW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
81  
103  
125  
90  
110  
125  
84  
106  
128  
90  
110  
150  
20  
AYHHTRNW36A  
AYHHTRNW54A  
AYHHTRNW72A  
36.0  
54.0  
72.0  
2
2
2
81  
103  
125  
90  
110  
125  
84  
106  
128  
90  
110  
150  
NOTES:  
1. Heater kw ratings are at 600V for 575V unit  
2. HACR type circuit breaker per NEC.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-4 — Electrical Characteristics — Evaporator Fan Motors — 60 Cycle  
Standard Evaporator Fan Motor  
Oversized Evaporator Fan Motor  
Am ps  
FLA LRA  
16.7 109.8  
Am ps  
Unit  
Tons  
12½  
Model No.  
No.  
Volts  
Phase  
HP  
FLA  
LRA  
No.  
Volts  
Phase  
HP  
WC*150B3  
WC*150B4  
WC*150BW  
1
1
1
208-230  
460  
575  
3
3
3
3.00  
3.00  
3.00  
10.6  
4.8  
3.9  
81.0  
40.5  
31.0  
1
1
1
208-230  
460  
3
3
3
5.00  
5.00  
5.00  
7.6  
6.1  
54.9  
41.6  
575  
WC*180B3  
WC*180B4  
WC*180BW  
1
1
1
208-230  
460  
575  
3
3
3
3.00  
3.00  
3.00  
10.6  
4.8  
3.9  
81.0  
40.5  
31.0  
1
1
1
208-230  
460  
575  
3
3
3
5.00  
5.00  
5.00  
16.7 109.8  
15  
20  
7.6  
6.1  
54.9  
41.6  
WC*240B3  
WC*240B4  
WC*240BW  
1
1
1
208-230  
460  
575  
3
3
3
5.00  
5.00  
5.00  
16.7  
7.6  
6.1  
109.8  
54.9  
41.6  
1
1
1
208-230  
460  
575  
3
3
3
7.50  
7.50  
7.50  
17.6 120.4  
8.6  
7.0  
74.0  
60.0  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-5 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle  
Com pressor Motors  
Condenser Fan Motors  
Am ps1  
FLA  
Am ps1  
Unit  
Tons  
12½  
Model No.  
No.  
Volts  
Phase  
HP2  
RPM  
RLA  
21.7  
10.0  
8.2  
LRA  
No.  
Phase  
HP  
LRA  
8.8  
4.0  
3.2  
WC*150B3  
WC*150B4  
WC*150BW  
2
2
2
208-230  
460  
575  
3
3
3
6.00 3450  
6.00 3450  
6.00 3450  
156  
75  
54  
2
2
2
1
1
1
.50  
.50  
.50  
3.2  
1.6  
1.3  
WC*180B3  
WC*180B4  
WC*180BW  
2
2
2
208-230  
460  
575  
3
3
3
7.50 3450  
7.50 3450  
7.50 3450  
26.5 181.5  
2
2
2
1
1
1
.50  
.50  
.50  
3.2  
1.6  
1.3  
8.8  
4.0  
3.2  
15  
14.0  
11.2  
95  
69  
WC*240B3  
WC*240B4  
WC*240BW  
2
2
2
208-230  
460  
575  
3
3
3
9.00 3500  
9.00 3500  
9.00 3500  
30.1  
15.8  
12.2  
225  
114  
80  
2
2
2
1
1
1
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
18.3  
9.3  
5.7  
20  
NOTES:  
1
Am p draw for each m otor; m ultiply value by num bers of m otors to determ ine total am ps.  
2. HP for each com pressor.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J obsite  
Connections  
Zone Sensors Typical Number Of Wires  
DISCONNECT  
SWITCH  
(BY OTHERS)  
A— Manual Changeover...................................... 6  
Manual/Auto Changeover ............................. 7  
Manual/Auto Changeover with  
ZONE SENSORS  
ROOFTOP  
UNIT  
Status Indication LED’s .......................... 10  
Programmable Night Setback with  
Status Indication LED’s ............................ 7  
B— 3 Power Wires + 1 Ground Wire (three phase)  
2 Power Wires + 1 Ground Wire (single phase)  
For specific wiring inform ation, see the installation instructions.  
All wiring except power wires is low voltage.  
All custom er supplied wiring to be copper and m ust conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the custom er.  
PKGP-PRC001-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Typical  
Wiring  
PKGP-PRC001-EN  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Typical  
Wiring  
PKGP-PRC001-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Typical  
Wiring  
PKGP-PRC001-EN  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Typical  
Wiring  
PKGP-PRC001-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ , 15 Ton)  
Dim ensional  
Data  
All dimensions are in inches.  
NOTE:  
Du c t fla n g e s m o u n t 7-7 /16 " d ow n  
in s id e t h e c u rb o n t h e 1 ½ " c u rb  
fla n g e s . Se e re c o m m e n d e d d u c t  
d im e n s io n s o n t h e n ext p a g e .  
Ro o fc u rb is in t e n d e d fo r  
d ow n flow u s e o n ly.  
Downflow Unit Clearance  
PKGP-PRC001-EN  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ , 15 Ton)  
Dim ensional  
Data  
All dimensions are in inches.  
1"  
Downflow Duct Connections — Field Fabricated  
17 7/8"  
59 7/16"  
26 5/16"  
1"  
52 1/2"  
1 1\2"  
PERIMETER  
CURB FLANGE  
14 1/16"  
7 7/16"  
RETURN  
SUPPLY  
NOTE:  
Du c t fla n g e s m o u n t 7-7 /16 " d ow n  
in s id e t h e c u rb o n t h e 1 ½ " c u rb  
fla n g e s .  
Ro o fc u rb is in t e n d e d fo r  
d ow n flow u s e o n ly.  
Horizontal Unit Supply/Return and Unit Clearance  
PKGP-PRC001-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(20 Ton)  
Dim ensional  
Data  
All dimensions are in inches.  
NOTE:  
Du c t fla n g e s m o u n t 7-7 /16 " d ow n  
in s id e t h e c u rb o n t h e 1 ½ " c u rb  
fla n g e s . Se e re c o m m e n d e d d u c t  
d im e n s io n s o n t h e n ext p a g e .  
Ro o fc u rb is in t e n d e d fo r  
d ow n flow u s e o n ly.  
Downflow Unit Clearance  
PKGP-PRC001-EN  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(20 Ton)  
Dim ensional  
Data  
All dimensions are in inches.  
1"  
Downflow Duct Connections — Field Fabricated  
19 5/16"  
73 7/16"  
26 5/16"  
1"  
66 1/2"  
1 1\2"  
PERIMETER  
CURB FLANGE  
14 1/16"  
7 7/16"  
RETURN  
SUPPLY  
NOTE:  
Du c t fla n g e s m o u n t 7-7 /16 " d ow n  
in s id e t h e c u rb o n t h e 1 ½ " c u rb  
fla n g e s .  
Ro o fc u rb is in t e n d e d fo r  
d ow n flow u s e o n ly.  
Horizontal Unit Supply/Return and Unit Clearance  
PKGP-PRC001-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim ensional  
Data  
(12½ - 20 Tons)  
Accessories  
All dimensions are in inches.  
Note:  
When applying econom izer to horizontal units,  
connecting ductwork m ust be run full size to  
allow proper operation of Econom izer Dam per.  
Table DD-1  
Tons  
A
B1  
C2  
12½, 15  
20  
171/2  
191/2  
53¾  
64¾  
36  
39  
NOTES:  
1. Horizontal dimension only. Downflow economizer is  
width of end panel.  
2. Power exhaust is applied on downflow economizer  
only.  
PKGP-PRC001-EN  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim ensional  
Data  
Factory Installed  
Options (FIOPS)  
All dimensions are in inches.  
Table DD-2  
Unit  
Model #  
A
B
C
WCD150-180  
WCD240  
423/  
8
483/  
56  
8
31  
381/2  
291/2  
PKGP-PRC001-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim ensional  
Data  
Factory Installed  
Options (FIOPS)  
Disconnect Switch  
or Circuit Breaker  
Fan Failure Switch  
Clogged Filter Switch  
Powered Or Unpowered  
Convenience Outlet  
Trane Communication Interface  
Hinged Access Door  
Black Epoxy Coated  
Outdoor Coils  
Hinged Access Door  
Through the Base  
Electrical  
High Pressure Cut Out  
Supply and/or Return  
Smoke Detectors  
PKGP-PRC001-EN  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Dim ensional  
Data  
Table DD-3 — 12½-20Tons  
Condensate Drain Location  
Condensate  
Drain Size  
Downflow  
Horizontal  
Tons  
Downflow Only  
A
B
C
D
F
G
H
E
J
E
K
12½, 15  
20  
267/  
267/  
16  
16  
221/  
283/  
2
4
1811/  
1915/  
16  
16  
41/  
41/  
4
4
41/  
41/  
4
4
627/  
765/  
16  
16  
5411/  
6811/  
16  
16  
1 NPT  
1 NPT  
255/  
263/  
8
4
53/  
53/  
8
8
PKGP-PRC001-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½ - 20 Tons)  
Weights  
Table W-1 — Accessory Net Weights (Lbs)  
High  
Econom izer1  
Outside Air Dam per  
Unit  
Power  
Exhaust4  
Roof  
Curb4  
Oversized  
Motor  
Static  
Drive  
Tons  
Model No.  
Net  
Ship  
Manual  
Motorized  
Adder  
12½,15  
20  
WCD150,180B  
WCD240B  
65  
80  
205  
265  
32  
32  
60  
75  
95  
95  
205  
235  
5
5
10/NA  
10  
12½,15  
20  
WCH150,180B  
WCH240B  
50  
65  
150  
210  
32  
32  
60  
75  
5
5
10/NA  
15  
Table W-1 — (Continued)  
Electric Heaters  
Unit  
Model No.  
All Zone  
Sensors  
5-18 KW  
240/480V2  
23-36 KW  
240/480V2  
54 KW  
240/480V2  
72 KW  
240/480V2  
3
3
3
3
Tons  
12½,15  
20  
WCD150,180B  
WCD240B  
1
1
28/21  
31/27  
33/27  
38/32  
40/32  
43/34  
12½,15  
20  
WCH150,180B  
WCH240B  
1
1
28/21  
31/27  
33/27  
38/32  
40/32  
43/34  
NOTES:  
1. Net weight should be added to unit weight when ordering factory installed economizer or oversize motor.  
2. For 600V heaters net weights are same as 480V heaters.  
3. To estimate shipping weight add 5 lbs to net weight.  
4. Downflow only.  
*Indicates both downflow and horizontal units.  
PKGP-PRC001-EN  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table W- 2 — Maximum Unit Weights, Corner Weights (Lbs) And Cente1r Of Gravity Dimensions (In.)  
1
Maxim um Weights (Lbs)  
Corner Weights (Lbs)  
Center of Gravity (In.)  
Unit  
Tons  
Model No.  
Shipping  
Net  
A
B
C
D
Length  
Width  
12½  
15  
20  
WC*150  
WC*180  
WC*240  
1719  
1857  
2467  
1351  
1489  
2008  
465  
547  
707  
344  
368  
510  
231  
231  
331  
311  
343  
460  
46  
43  
51  
29  
27  
34  
1. Corner weights are given for information only. 10-20 ton models must be supported continuously by a curb or equivalent frame support.  
Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3  
Accessory  
Model  
Accessory  
Num ber  
Weight  
FIYHEMT001,002  
FIYHEMT003-005  
FIYHEMT006-008  
FIYHNGE002  
15  
49  
36  
10  
27  
High Efficiency Motors  
Hinged Doors  
FIYHNGE003-009  
Powered Convenience Outlet  
Through the Base Electrical  
FIYCOPO101-206  
FIYTBUE101-111  
FIYTBUE201-216  
FIYUCB4150  
38  
16  
23  
5
Unit Mounted Circuit Breaker  
FIYUCB3175-3250  
FIYUDC4150,6100  
FIYUDC3250  
10  
5
10  
Unit Mounted Disconnect  
NOTES:  
1. Weights for FIOP accessories not listed are >5 lbs.  
2. Net weight should be added to unit weight when ordering factory installed accessories.  
3. See Table W-1 for standard factory installed econom izer, electric heater and oversized m otor.  
PKGP-PRC001-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
General  
Filters  
Indoor Fan  
The units shall be dedicated downflow  
or horizontal airflow.The operating range  
shall be between 115°F and 0°F in  
cooling as standard from the factory for  
all units. Cooling performance shall be  
rated in accordance with ARI testing  
procedures. All units shall be factory  
assembled, internally wired, fully  
charged with R-22, and 100 percent run  
tested to check cooling operation, fan  
and blower rotation and control  
sequence, before leaving the factory.  
Wiring internal to the unit shall be  
colored and numbered for simplified  
identification. Units shall be UL listed  
and labeled, classified in accordance to  
UL 1995/CAN/CSA No. 236-M90 for Heat  
Pumps. Canadian units shall be CSA  
Certified.  
Two inch standard filters shall be factory  
supplied on all units. Optional two inch  
pleated media filters shall be available for  
12½-20 ton models.  
Units above shall have belt driven, FC  
centrifugal fans with adjustable motor  
sheaves. Units with standard motors  
above 12½ tons shall have an adjustable  
idler-arm assembly for quick-adjustment  
of fan belts and motor sheaves. All  
motors shall be thermally protected.  
Oversized motors shall be available for  
high static application. All indoor fan  
motors meet the U.S. Energy Policy Act of  
1992 (EPACT).  
Compressors  
External high pressure cutout shall be  
provided on all 15 and 20 models. Low  
pressure switches shall be standard. All  
12½-20 tons shall have direct-drive,  
hermetic, scroll type compressors with  
centrifugal type oil pumps. Motor shall  
be suction gas-cooled and shall have a  
voltage utilization range of plus or minus  
10 percent of nameplate voltage. Internal  
overloads shall be provided with the  
scroll compressors. Crankcase heaters  
shall be utilized with all scroll  
Controls  
Unit shall be completely factory wired  
with necessary controls and contactor  
pressure lugs or terminal block for  
power wiring. Unit shall provide an  
external location for mounting a fused  
disconnect device. ReliaTel controls shall  
be provided for all 24 volt control  
functions.The resident control  
algorithms shall make all heating,  
cooling, and/or ventilating decisions in  
response to electronic signals from  
sensors measuring indoor and outdoor  
temperatures.The control algorithm  
maintains accurate temperature control,  
minimizes drift from set point, and  
provides better building comfort. A  
centralized control shall provide anti-  
short cycle timing and time delay  
between compressors to provide a  
higher level of machine protection.  
compressors.  
Refrigerant Circuits  
Casing  
Each refrigerant circuit shall have  
independent fixed orifice or thermostatic  
expansion devices, service pressure  
ports, and refrigerant line filter driers  
factory installed as standard. An area  
shall be provided for replacement  
suction line driers.  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Units surface shall be tested 500 hours  
in a salt spray test in compliance with  
ASTM B117. Cabinet construction shall  
allow for all maintenance on one side of  
the unit. Service panels shall have lifting  
handles and be removeing not more  
than three screws on the 12½-20 tons  
while providing a water and air tight  
seal. All exposed vertical panels and top  
covers in the indoor air section shall be  
insulated with a 1/2 inch, 1 pound  
density matt-faced, fire-resistant,  
Evaporator and Condenser Coils  
Internally finned, 3/8" copper tubes  
mechanically bonded to a configured  
aluminum plate fin shall be standard.  
Coils shall be leak tested at the factory to  
ensure the pressure integrity.The  
evaporator coil and condenser coil shall  
be leak tested to 200 psig and pressure  
tested to 450 psig. All dual compressor  
units shall have intermingled evaporator  
coils. Sloped condensate drain pans are  
standard.  
Defrost Controls  
A time initiated, temperature terminated  
defrost system shall ship with a setting  
of 70 with a choice of 50 or 90 minute  
cycle.Timed override limits defrost cycle  
to 10 minutes shall be available on all  
12½-20 tons.  
permanent, odorless, glass fiber  
material.The base of the downflow unit  
shall be insulated with 1/2 inch, 1 pound  
density foil-faced, closed-cell material.  
The downflow units base pan shall have  
no penetrations within the perimeter of  
the curb other than the raised 11/8 inch  
high supply/return openings to provide  
an added water integrity precaution, if  
the condensate drain backs up.The base  
of the unit shall have provisions for  
forklift and crane lifting.  
Outdoor Fans  
The outdoor fan shall be direct-drive,  
statically and dynamically balanced,  
draw-through in the vertical discharge  
position.The fan motor(s) shall be  
permanently lubricated and shall have  
built-in thermal overload protection.  
Unit Top  
The top cover shall be one piece, or  
where seams exist, double hemmed and  
gasket sealed to prevent water leakage.  
PKGP-PRC001-EN  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Remote Potentiometer  
LonTalk® Communications Interface  
The LonTalk communications interface,  
when installed in a Voyager unit, allows  
the unit to communicate as aTracer™LCI-  
V device or directly with generic LonTalk  
Network Building Automation System  
Controls.  
Accessories  
Electric Heaters  
The minimum position setting of the  
economizer shall be adjusted with this  
accessory.  
Electric heat modules shall be available  
for installation within basic unit. Electric  
heater elements shall be constructed of  
heavy-duty nickel chromium elements  
internally delta connected for 240 volt,  
wye connected for 480 and 600 volt.  
Staging shall be achieved through  
ReliaTel. Each heater package shall have  
automatically reset high limit control  
operating through heating element  
contactors. All heaters shall be  
individually fused from the factory,  
where required, and shall meet all NEC  
and CEC requirements when properly  
installed. Power assemblies shall provide  
single-point connection. Electric heat  
modules shall be UL listed or CSA  
certified.  
Powered Exhaust  
The field installed powered exhaust shall  
provide exhaust of return air, when  
using an economizer, to maintain better  
building pressurization.  
CO2 Sensing  
The CO sensor has the ability to monitor  
space o2ccupancy levels within the  
building by measuring the parts per  
million of CO (Carbon Dioxide) in the air.  
As the CO le2vels increase, the outside air  
damper m2odulates to meet the CO2  
space ventilation requirements.The CO2  
accessory kit is available as a field  
installed accessory.  
Manual Outside Air Damper  
Field installed rain hood and screen shall  
provide up to 25 percent outside air.  
Motorized Outside Air Dampers  
Manually set outdoor air dampers shall  
provide up to 50 percent outside air.  
Once set, outdoor air dampers shall  
open to set position when indoor fan  
starts.The damper shall close to the full  
closed position when indoor fan shuts  
down.  
Ventilation Override Accessory  
With the Ventilation Override Accessory  
installed, the unit can be set to transition  
up to 3 different pre-programmed  
sequences for Smoke Purge,  
Roof Curb - Downflow  
High Static Drive  
The roof curb shall be designed to mate  
with the downflow unit and provide  
support and a water tight installation  
when installed properly.The roof curb  
design shall allow field-fabricated  
rectangular supply/return ductwork to be  
connected directly to the curb. Curb  
design shall comply with NRCA  
requirements. Curb shall be shipped  
knocked down for field assembly and  
shall include wood nailer strips.  
Field installed high static drive option  
shall allow the standard motor on the  
12½ and 20 ton units to operate with  
improved external static capabilities.  
Pressurization, and Exhaust.The  
transition occurs when a binary input on  
the RTOM is closed (shorted).This would  
typically be a hard wired relay output  
from a smoke detector or fire control  
panel.The ventilation override kit is  
available as a field installed accessory.  
Oversized Motors  
Factory or field installed oversized  
motors shall be available for high static  
applications.  
Digital Display Zone Sensor  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone sensors.This sensor  
includes a digital display of set point  
adjustment and space temperature in F  
(Fahrenheit) or C (Celsius). Includes FAN  
and SYSTEM buttons (supports the  
service functions of the standard sensor).  
E-squared memory stores last  
Control Options  
Trane Communication Interface (TCI)  
This factory or field installed option shall  
allow communication with the Trane  
Integrated ComfortTM Systems.  
Economizer - Downflow  
This accessory shall be either field or  
factory-installed.The assembly includes  
fully modulating 0-100 percent motor  
and dampers, barometric relief,  
minimum position setting, preset  
linkage, wiring harness with plug, fixed  
dry bulb and spring return actuator.The  
barometric relief damper shall be  
standard with the downflow economizer  
and shall provide a pressure operated  
damper that shall be gravity closing and  
shall prohibit entrance of outside air  
during the equipment off” cycle. Solid  
state enthalpy and differential enthalpy  
control shall be field-installed options.  
Zone Sensors  
This option shall be provided to interface  
with the Micro equipped Voyagers and  
shall be available in either manual,  
automatic, programmable with night  
setback, with system malfunction lights  
or remote sensor options.  
programmed set points. Requires 24 VAC  
(Volts AC).This sensor should be utilized  
with ReliaTel™ controls.  
DualThermistor Remote Zone Sensor  
This sensor will allow the customer to  
reduce the total number of remote  
sensors to obtain space temperature  
averaging. This sensor should be utilized  
with ReliaTel controls.  
Differential Pressure Switches  
These field installed options allow for  
individual fan failure and dirty filter  
indication.The fan failure switch will  
disable all unit functions and “flash” the  
Service LED on the zone sensor.The dirty  
filter switch will light the Service LED on  
the zone sensor and will allow continued  
unit operation.  
Economizer - Horizontal  
This accessory shall be field-installed  
only.The horizontal economizer shall  
contain the same features as the  
downflow economizer with the  
exception of barometric relief.  
PKGP-PRC001-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Reference or Comparative Enthalpy  
Reference or Comparative Enthalpy  
option shall be available when a factory  
installed Downflow Economizer is  
ordered.This option is available on all  
12½-20 tons downflow models.  
Additional Factory Installed  
Options (FIOPS)  
Electric Heaters  
Factory installed and wired electric  
heaters are available for all 3 phase  
horizontal and downflow 12½ - 20 tons. If  
ordering the Through the Base Electrical  
option with an Electric Heater, the heater  
must be factory installed.  
High Pressure Cutout  
This option is offered for units that do  
not have High Pressure cutout as  
standard.The Voyager units with High  
Pressure Cutout as standard are  
WC*180-240B.  
Through the Base Electrical with Circuit  
Breaker  
This option is a factory installed thermal  
magnetic, molded case, HACR Circuit  
Breaker with provisions for through the  
base electrical connections.The circuit  
breaker will be installed in a water tight  
enclosure in the unit with access through  
a swinging door. Factory wiring will be  
provided from the switch to the unit high  
voltage terminal block.The circuit  
breaker will provide overcurrent  
Hinged Access Doors  
Sheet metal hinges are available factory  
installed on the Filter/Evaporator Access  
Door and the Compressor/Control  
Access Door.This option is available on  
all 12½-20 tons downflow models.  
Trane Communications Interface (TCI)  
An option for a factory installed Trane  
Communication Interface is available to  
allow twisted wire pair communication  
with an Integrated Comfort ™ System.  
Order this option when a combination of  
TCI and oversized motor is desired.  
protection, be sized per NEC and UL  
guidelines, and be agency recognized by  
UL/CSA.This option is available on all  
12½-20 tons downflow models.  
Powered or Unpowered Convenience  
Outlet  
Discharge Air Sensing Kit  
This kit provides true discharge air  
sensing in heating models.This sensor is  
a status indicator readable through  
Tracer™ orTracker™.The kit is functional  
only with the ReliaTel Options Module.  
This option is a GFCI, 120v/15amp, 2  
plug, convenience outlet, either powered  
or unpowered. When the convenience  
outlet is powered, a service receptacle  
disconnect will be available.The  
convenience outlet is powered from the  
line side of the disconnect or circuit  
breaker, and therefore will not be  
affected by the position of the disconnect  
or circuit breaker.This option can only be  
ordered when the Through the Base  
Electrical with either the Disconnect  
Switch, or Circuit Breaker, option is  
ordered.This option is available on all  
12½-20 tons downflow models.  
Coil Guards  
Hail protection quality coil guards shall be  
either factory or field-installed for  
condenser coil protection.  
High Efficiency Motors  
This option is available with efficiency  
ratings from 86.5 up to 91.0. It is not  
available for all models.  
Clogged Filter/Fan Failure Switch  
A dedicated differential pressure switch  
is available to achieve active fan failure  
indication and/or clogged filter  
indication.These indications will be  
registered with either a zone sensor with  
status indication lights or an Integrated  
Comfort™ System.  
PKGP-PRC001-EN  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Supply and/or Return Air Smoke  
Detector  
Novar Return Air Sensor  
This option, when used in conjunction  
with Novar Controls, will contain a  
factory provided wired zone temperature  
sensor located in the return air stream.  
With this option installed, if smoke is  
detected, all unit operation will be shut  
down. Reset will be manual at the unit.  
Return Air Smoke Detectors require  
minimum allowable airflow when used  
with certain models. See the Installation,  
Operation, and Maintenance (IOM)  
manual for the models affected and the  
minimum allowable airflow required.  
This option is available on all 12½-20  
tons downflow models.  
Through the Base Utilities Access  
An electrical service entrance shall be  
provided allowing electrical access for  
both control and main power  
connections inside the curb and through  
the base of the unit. Option will allow for  
field installation of liquid-tight conduit and  
an external field installed disconnect  
switch.  
Black Epoxy Coated Condenser Coil  
The coil provides corrosion protection to  
condenser coils for seacoast application.  
The protection is a factory applied  
thermoset vinyl coating, bonded to  
normal aluminum fin stock.The uniform  
thickness of the bonded vinyl layer  
exhibits excellent corrosion protection in  
salt spray tests performed in accordance  
with ASTM B117.  
Through the Base ElectricalWith  
Disconnect Switch  
Factory installed 3-pole, molded case,  
disconnect switch with provisions for  
through the base electrical connections  
are available.The disconnect switch will  
be installed in the unit in a water tight  
enclosure with access through a swinging  
door. Factory wiring will be provided from  
the switch to the unit high voltage  
terminal block.The switch will be UL/CSA  
agency recognized. Note:The disconnect  
switch will be sized per NEC and UL  
guidelines but will not be used in place of  
unit overcurrent protection.This option is  
available on all 12½-20 tons downflow  
models.  
Frostat  
This factory or field installed option is to  
be utilized as a safety device.The Frostat  
opens when temperatures on the  
evaporator coil fall below 1F. The  
temperature will need to rise to 50°F  
before closing.This option should be  
utilized in low airflow or high outside air  
applications.  
Two-Inch Pleated Filters  
Novar Unit Controls  
Two inch pleated media filters shall be  
available on all 12½-20 ton models.  
Novar rooftop unit controls will be factory  
installed and tested.The Novar electronic  
thermostat module will interface to the  
unit microprocessor and will control the  
unit to the desired stage of cooling or  
heating.The Novar electronic thermostat  
module will monitor the following unit  
information: fan failure status, cooing  
stage 1 on status, cooling stage 2 on  
status, heating on status, clogged filter  
status or unit shutdown status, and  
discharge air temperature.The Novar  
electronic thermostat module will have  
the ability to enable the unit mounted  
economizer.  
PKGP-PRC001-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*Downflow Units only  
Literature Order Number  
PKGP-PRC001-EN  
File Number  
PL-UN-PKGP-WCD/WCH12½-20TONS-PRC001-EN-10-03  
PKGP-PRC001-EN 09-03  
Supersedes  
Trane  
Stocking Location  
07-03Webb/Mason 10-03 Electronic Only  
A business of Am erican Standard Com panies  
www.trane.com  
For more information contact your local dealer  
(distributor), local district office, or e-mail us at  
Trane has a policy of continuous product and product data improvement and reserves the right to change design  
and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tech Craft TV Video Accessories FLEX37WB User Manual
Toastmaster Oven TC2000 User Manual
Toshiba Computer Drive MK4006GAH User Manual
Toshiba Laptop X205 S9349 User Manual
Toshiba Telephone Accessories CIX UG STDTELVB User Manual
TP Link Network Card TL PA2030 User Manual
Troy Bilt Trimmer TB425CS TB475SS User Manual
Uniden Cordless Telephone DSS3435+1 User Manual
Vivotek DVD Recorder st501 User Manual
VTech Cordless Telephone VT 1711 User Manual