Installation
Owner
Diagnostics
TM
Axiom Horizontal/Vertical
Water-Source Comfort System
Models GEH and GEV
15 - 25 Ton
1/2 - 5 Ton
6 - 10 Ton
6 - 15 Ton
Models
“A” and later Design Sequence
GEH
GEV
006 - 060 – 60 HZ
006 - 060 – 50 HZ
072 - 180 – 60 HZ
072 - 150 – 50 HZ
006 - 060 – 60 HZ
006 - 060 – 50 HZ
072 - 300 – 60 HZ
072 - 240 – 50 HZ
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Installation/Startup/Commissioning
Pre-installation Checklist
General Information
4
4
5
7
Dimensions/Weights
48
67
Installation Instructions
Electrical Requirements
73
74
Pre-Startup Checklist
Startup/Commissioning
Sequence of Operation
74
81
82
83
84
86
Startup Checklist & Log
Maintenance
Warranty Information
Troubleshooting Checklist
Unit Wiring
WSHP-SVX01D-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Pre-installation
Checklist
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this
product during installation, maintenance or repair will expose you to
airborne particles of glass wool fibers and ceramic fibers known to the
state of California to cause cancer through inhalation. Glass wool fibers
may also cause respiratory, skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of
lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifica-
tions.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been com-
pleted. Check for damage promptly after the unit(s) are unloaded. Once the
bill of lading is signed at the jobsite, the unit(s) are now the property of the
SOLD TO party and future freight claims MAY NOT be accepted by the
freight company.
4. Verify that the refrigerant charge has been retained during shipment by use
of gauges. Schrader taps are located internal to the cabinet.
5. After assuring that charge has been retained, reinstall the schrader caps to
assure that refrigerant leakage does not occur.
WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification site for
microbial growth (mold), which may cause odors and serious health
related indoor air quality problems. If there is evidence of microbial
growth (mold) on the interior insulation, remove or replace the
insulation prior to operating the system. Failure to remove microbial
growth could result in serious health problems.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to
the elements, and to prevent possible IAQ contaminant sources from growing,
the unit should be stored indoors. If indoor storage is not possible, the following
provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the ground to assure ade-
quate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent
moisture from standing on the unit(s) surfaces. Wet interior unit insulation
can become an amplification site for microbial growth (mold) which has
been determined to be a cause of odors and serious health related indoor air
quality problems.
4. Store units in the normal UP orientation to maintain oil in the compressor.
5. Horizontal units may be stacked no more than three units high. Do not stack
the vertical unit configurations.
4
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Information
Unit Nameplate
pabilities depends upon the type of
sensor and/or remote panel selected.
Troubleshooting and connection dia-
grams for the 24 Volt control systems
compressor disable, condensate over-
flow, unit safety control, diagnostics
and a generic relay (which may be
available for field use). See page 56 for
The unit nameplate is located on the
outside of the control box access panel
at the front of the unit. It includes the
unit model number, serial number,
electrical characteristics, refrigerant
charge, and other pertinent unit data.
may be located in the back of this man- diagnostic information and thermostat
ual. All digital control troubleshooting
tips and connection diagrams are lo-
cated in WSHP-IOP-2 (ZN510) or
WSHP-PRB002-EN (ZN524).
connections.
(option) Tracer ZN510 or ZN524
Controls
The digital ZN510 and ZN524 control-
Compressor Nameplate
The nameplate for the compressors
are located on the compressor shell.
Basic 24V Controls
ler is designed to support the 1/2
Safety devices for equipment contain- through 25 ton water-source heat
Unit Description
ing the basic 24V control option in-
clude a low pressure switch or suction
line temperature sensor to prevent
pumps in either a standalone, peer-to-
peer with a Tracer Loop Controller, or
as a full building automation (open
Before shipment, each unit is leak test-
ed, dehydrated, charged with refriger-
ant and run tested for proper control
operation.
compressor operation during low tem- protocal) system. The 1/2 through 5
perature activity. The switch or sensor
is set to activate at refrigerant pres-
sures of 20 psig (1/2 to 5 ton units) or
7 psig (6 to 25 ton units) to fit most ap- ception to this would be if the equip-
plications.
ton units that incorporate direct digital
controls will typically come equipped
with the ZN510 control board. The ex-
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum
fin, mechanically bonded to the cop-
per tubing.
ment contained hot gas reheat,
Water-to-Refrigerant Coil
waterside economizer, or boilerless
control with electric heat. The ZN524
digital control board is designed to in-
terface and run these mechanical op-
tions. All units over 5 tons would ship
with the Tracer ZN524 control board.
A high pressure switch prevents com-
pressor operation during high or ex-
cessive discharge pressures
exceeding 395 psig.
The water-to-refrigerant coil is a cop-
per or cupro-nickel (option) and steel
tube (tube-within-a-tube) design, leak
tested to assure there is no cross leak-
age between the water tube (copper/
cupro-nickel) and refrigerant gas (steel
tube).
The lockout relay communicates the
low or high pressure situation to the
compressor to prevent operation. For
units that contain a condensate over-
flow switch option, a condensate over-
flow situation will also be
communicated to the compressor
through the lockout relay if an over-
flow condition exists. The relay may
be reset at the thermostat, or by cy-
cling power to the unit.
For installation, operation and diag-
nostics of the ZN510 and ZN524
WSHP-IOP-2 (ZN510) and/or WSHP-
PRB002-EN (ZN524).
Controls
The control system offered to con-
trol the unit is a Basic 24 Volt control
for the 1/2 through 5 ton sizes, a De-
luxe 24 Volt control option for all unit
(option) Waterside Economizer
Instructions for mechanical connec-
tion of the waterside economizer to
the water-source heat pump may be
found in the dimensional section of
this manual.
TM
sizes, a TracerTM ZN510, LonTalk
certified controloption for the 1/2
through 5 ton unit sizes, or a Tracer
ZN524, LonTalk certified control op-
tion for all unit sizes.
General alarm is accomplished
through the lockout relay and is used
in driving light emitting diodes (LEDs).
This feature will drive dry contacts
only, and cannot be used to drive field
installed control inputs.
The waterside economizer is designed
to begin economizing mode when wa-
ter temperatures fall below the field
adjustable temperature of 25, 35, 45,
55 or 65 F (for the Deluxe control op-
tion), or below the programmed set-
point (for the ZN524 control option).
All power wiring to the equipment is
made at the unit contactor for the 1/2
through 5 ton, and at the high voltage
terminal block for the 6 through 25 ton.
All low voltage wiring is made at the
unit’s low voltage terminal board.
(option) Deluxe 24V Controls
Units containing the Deluxe 24V con-
trol design will incorporate a micro-
processor-based control board. The
Trane microprocessor board is factory
wired to a terminal strip to provide all
necessary terminals for field connec-
tion. The deluxe board is equipped
with a random start relay, anti-short
cycle timer, brown out protection,
When the temperature is less than the
setpoint, fluid will flow into the econo-
mizing coil, while simultaneously halt-
ing mechanical operation of the
compressor. Mechanical cooling will
continue on a call for a second stage
from the thermostat or system control.
System Input Devices and
Functions
A thermostat, zone sensor or building
automation system is required to op-
erate the water-source heat pump. The
flexibility of having several mode ca-
WSHP-SVX01D-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Information
(option) Boilerless Control/Electric
Heat
Systems that do not contain a boiler
(option) Hot Gas Reheat
With the reheat option, the return-air
from the space is conditioned by the
air-to-refrigerant coil, then reheated
may contain a boilerless control with
electric heat. Trane offers both a facto- by the reheat coil to control not only
ry mounted electric heat option, and a
field mounted duct heater option.
the space temperature, but to also re-
duce the relative humidity of the
space. When operating in the reheat
mode (meaning the sensible tempera-
ture has been met in the space), the
humidistat signals the reheat relay coil
to energize, allowing the high pres-
sure refrigerant gas to flow from the
compressor through the reheat valve,
into the reversing valve, or reheat coil
for dehumidification.
If the 1/2 through 5 ton GEH and GEV
unit incorporates the factory mounted
option, the unit will ship from the fac-
tory with an internally mounted
nichrome open wire heating element,
designed to start-up electric heat as
the systems primary heat in the event
entering water temperature falls be-
low 55 F. Once the entering water tem-
perature rises above 60 F, the
A switching relay has been provided
for the reheat application to adjust the
blower motor from normal operation
to low speed when the hot gas reheat
is energized (for 1/2 through 5 ton
equipment only).
boilerless controller returns the unit to
normal compressor heating operation,
and locks out the electric heater.
If the unit contains a cooling only heat
pump design, the electric heat contac-
tor is wired directly to the thermostat
for primary heating, and the compres-
sor contactor for cooling.
Notes:
•
A high static blower motor is re-
quired to support the hot gas re-
heat option for the 1/2 through 5
ton equipment.
For units comprised of the field in-
stalled duct heater option, the unit will
ship from the factory with controls
available to interface with the field
provided electric heat selection.
•
•
Units containing the hot gas reheat
option should not be used as a
make-up air unit.
Note: For geothermal applications, the
boilerless controller has an adjustable
setting of 25, 35, 45, 55 and 60 de-
grees.
Water regulating valves should not
be used with the hot gas reheat op-
tion. Trane places a thermal expan-
sion valve on all WSHPs as well as
GSHPs to regulate refrigerant flow
vs. water flow to the unit.
(option) Supplemental or
Boilerless Electric Heat
The 6 through 25 ton models which
contain boilerless control electric heat
or supplemental electric heat will con-
tain the controls interface ONLY for
field provided electric heat selection.
The heater for this model shall be ex-
ternal to the equipment by the contrac-
tor for ease of installation. All power
connections for the electric heater will
be completely separate from the unit
for field supplied electric heat.
Note: When the unit has boilerless
control, the electric heat is not used as
supplemental electric heat, but as a
primary heat.
6
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Table 1: Unit weights
GEH
60 HZ
GEH
50 HZ
GEV
60 HZ
GEV
50 HZ
Shipping Weight
with pallet
Shipping Weight
w/o pallet
006-015 006-012
018-030 015-024
036-042 030-036
048-060 042-060
188 lb (85 kg)
278 lb (125 kg)
318 lb (143 kg)
428 lb (193 kg)
701 lb (318 kg)
714 lb (325 kg)
831 lb (377 kg)
907 lb (412 kg)
999 lb (454 kg)
178 lb (80 kg)
268 lb (121 kg)
308 lb (139 kg)
396 lb (178 kg)
158 lb (71 kg)
248 lb (112 kg)
288 lb (130 kg)
398 lb (179 kg)
652 lb (296 kg)
666 lb (303 kg)
789 lb (359 kg)
865 lb (393 kg)
957 lb (435 kg)
158 lb (71 kg)
248 lb (112 kg)
288 lb (130 kg)
248 lb (112 kg)
Operating Weight
577 (262 kg)
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches
to verify proper center of gravity lift
point. To avoid dropping of unit,
reposition lifting point if unit is not
level. Failure to properly lift unit could
result in death or serious injury or
possible equipment or property-only
damage.
072
090
120
150
180
-
072
090
120
150
006-015
018-030, 040
036, 042
006-012
015-024
030, 036
042-060
048, 060
072
090
120
150
180
240
300
-
617 lb (280 kg)
648 (294 kg)
072
090
120
150
180
240
608 (276 kg)
861 (391 kg)
821 (373 kg)
1215 lb (547 kg)
1225 lb (551 kg)
1615 lb (727 kg)
1665 lb (749 kg)
1170 lb (527 kg)
1180 lb (531 kg)
1580 lb (711 kg)
1640 lb (738 kg)
Table 2: Waterside economizer weight
GEV
60 HZ
GEV
50 HZ
Economizer
Weight
GEH
GEH
50 HZ
Economizer
Weight
GEH
60 HZ
GEH
50 HZ
Economizer
Weight
60 HZ
006-015
018-030
036-042
048-060
072
090
-
072
148 lb (67 kg)
168 lb (76 kg)
207 lb (94 kg)
275 lb (125 kg)
310 lb (141 kg)
395 lb (179 kg)
006-012
015-024
030-036
042-060
54 lb (24.5 kg)
65 lb (29.5 kg)
76 lb (35 kg)
97 lb (44 kg)
072
090
120
150
180
-
138 lb (63 kg)
144 lb (65 kg)
166 lb (75 kg)
213 lb (97 kg)
213 lb (97 kg)
072
090
120
150
120
090
150, 180
240
120, 150
180
300
240
Weight Distribution for Hanging
the GEH Model
•
Approximate weight distribution
for proper hanging of the GEH unit
is indicated by the diagram to the
right.
•
•
Tolerance on the weights deter-
mined are 15%.
1/2 through 5-ton
6 through 15-ton
Total weights for each unit size are
listed above.
WSHP-SVX01D-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Clearance
GEH Clearance Dimensions
Access to the unit for service pur-
poses should be provided at instal-
lation. All 1/2 through 5 ton
configurations require an 18" (457
mm) surround clearance from oth-
er mechanical and electrical equip-
ment (where shown) to enable
panel removal from the unit for
service/maintenance ability. Some
local codes require a greater ser-
vice clearance than listed below.
Check all code requirements prior
to unit installations.
Equipment containing a same-side
supply/return combination re-
quires a 3" (229 mm) limitation on
one side. Access to the TXV may
not be possible with this 3" (229
mm) clearance. This configuration
is typically applied in a corridor in-
stallation, where space limitations
force the left or right side of the
unit against a wall.
Service clearance dimensions for
the 6 through 15 ton horizontal in-
cludes a two side access appropri-
ate for control and blower motor/
wheel access. Some local codes
require a greater service clearance
than listed below. Check all code
requirements prior to unit installa-
tions.
GEH 1/2 through 5 Ton Clearance
GEH 6 through 15 Ton Clearance
8
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Clearance
GEV 1/2 through 5 Ton Clearance
Dimensions (Figure 1)
Access to the unit for service purposes
should be provided at installation. All
configurations require an 24" (610 mm)
surround clearance from other me-
chanical and electrical equipment
(where shown) to enable panel remov-
al from the unit for service/mainte-
nance ability. Some local codes require
a greater service clearance than listed
below. Check all code requirements
prior to unit installations. Units in afree
return application will require more
than a 1" (25.4) clearance to provide
proper air flow to the units air-to-refrig-
erant coil.
Figure 1: GEV 1/2 through 5 Ton Clearance
GEV 6 through 10 Ton Clearance
Dimensions (Figure 2)
Minimum access for service clearances
are provided below. Any one unit side
other than the control panel or return-
air side may be placed against a wall.
The unit may be serviced through the
three remaining open sides. Some lo-
cal codes require a greater service
clearance than listed below. Check all
code requirements prior to unit instal-
lations.
GEV 12 1/2 through 25 Ton
Figure 2: GEV 6 through 10 Ton Clearance
Clearance Dimensions (Figure 3)
The diagram below outlines the mini-
mum required unit service clearances.
Any one unit side other than the con-
trol panel or return-air side may be
placed against a wall. The unit may be
serviced through the three remaining
open sides. Some local codes require a
greater service clearance than listed
below. Check all code requirements
prior to unit installations.
Figure 3: GEV 12 1/2 through 25 Ton Clearance
WSHP-SVX01D-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Left Return/Left Supply
L
M
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
Unit
A
B
C
D
E
F
G
H
J
K
N
P
Q
R
S
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
40"
(1016)
40"
(1016)
46"
(1168)
46"
(1168)
50"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
17"
(432)
17"
(432)
19"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
18"
(457)
18"
(457)
20"
6 7/8"
(175)
6 7/8"
(175)
8 1/4"
(210)
8"
(203)
11 1/2" 4 1/4"
(292) (108)
2 1/8"
(54)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
48 3/4" 23 3/4" 17 5/8" 23 1/2" 3 1/4"
(1238) (603) (448) (597) (83)
56 3/4" 31 3/4" 19 5/8" 23 1/2" 5 1/2"
(806) (498) (597) (140)
006,009
012, 015
018
9 7/8" 11 1/2" 4 1/4"
(251) (292) (108)
9 3/4" 13 1/2" 4 3/4"
(248) (343) (121)
2 5/8"
(67)
2 7/8"
(73)
8 1/4" 11 3/8" 13 1/2" 4 3/4"
(210)
2 7/8"
(73)
024, 030
036, 042
048, 060
(289)
(343)
(121)
4"
(102)
6 5/8"
(168)
10 1/2" 13 1/2" 16 3/8"
1 3/4"
(45)
(1270)
58"
(1473)
(635)
33"
(838)
(483)
21"
(533)
(635)
25"
(635)
(508)
28"
(711)
(267)
13 7/8" 13 7/8"
(352) (352)
(343)
(416)
18"
(457)
2"
(51)
(25.4)
(25.4) (1441)
10
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Left Return/Back Supply
L
M
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
Unit
A
B
C
D
E
F
G
H
J
K
N
P
Q
R
S
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
40"
(1016)
40"
(1016)
46"
(1168)
46"
(1168)
50"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
17"
(432)
17"
(432)
19"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
18"
(457)
18"
(457)
20"
6 7/8"
(175)
6 7/8"
(175)
8 1/4"
(210)
8"
(203)
11 1/2" 4 1/4"
(292) (108)
2 1/8"
(54)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
48 3/4" 23 3/4" 17 5/8" 23 1/2" 3 1/4"
(1238) (603) (448) (597) (83)
56 3/4" 31 3/4" 19 5/8" 23 1/2" 5 1/2"
006,009
012, 015
018
9 7/8" 11 1/2" 4 1/4"
(251) (292) (108)
9 3/4" 13 1/2" 4 3/4"
(248) (343) (121)
2 5/8"
(67)
2 7/8"
(73)
8 1/4" 11 3/8" 13 1/2" 4 3/4"
(210)
2 7/8"
(73)
024, 030
036, 042
048, 060
(289)
(343)
(121)
4"
(102)
6 5/8"
(168)
10 1/2" 13 1/2" 16 3/8"
1 3/4"
(45)
(1270)
58"
(1473)
(635)
33"
(838)
(483)
21"
(533)
(635)
25"
(635)
(508)
28"
(711)
(267)
13 7/8" 13 7/8"
(352) (352)
(343)
(416)
18"
(457)
2"
(51)
(25.4)
(25.4) (1441)
(806)
(498)
(597)
(140)
WSHP-SVX01D-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Left Return/Right Supply
Unit
60 HZ 50 HZ
Unit
L
M
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
A
B
C
D
E
F
G
H
J
K
N
P
Q
R
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
40"
(1016)
40"
(1016)
46"
(1168)
46"
(1168)
50"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
17"
(432)
17"
(432)
19"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
18"
(457)
18"
(457)
20"
6 7/8"
(175)
6 7/8"
(175)
8 1/4"
(210)
8"
(203)
11 1/2" 4 1/4"
(292) (108)
2 1/8"
(54)
38 3/4" 18 3/4" 13 5/8" 18 1/2"
(984) (476) (346) (470)
38 3/4" 18 3/4" 13 5/8" 18 1/2"
(984) (476) (346) (470)
44 3/4" 21 3/4" 15 5/8" 18 1/2"
(1137) (552) (397) (470)
44 3/4" 21 3/4" 15 5/8" 18 1/2"
(1137) (552) (397) (470)
48 3/4" 23 3/4" 17 5/8" 23 1/2"
(1238) (603) (448) (597)
56 3/4" 31 3/4" 19 5/8" 23 1/2"
(806) (498) (597)
006-009 006
9 7/8" 11 1/2" 4 1/4"
(251) (292) (108)
9 3/4" 13 1/2" 4 3/4"
(248) (343) (121)
2 5/8"
(67)
012-015 009-012
2 7/8"
(73)
018
015
8 1/4" 11 3/8" 13 1/2" 4 3/4"
(210)
2 7/8"
(73)
024-030 018-024
036-042 030-036
048-060 042-060
(289)
(343)
(121)
4"
(102)
6 5/8"
(168)
10 1/2" 13 1/2" 16 3/8"
(267)
1 3/4"
(45)
(1270)
58"
(1473)
(635)
33"
(838)
(483)
21"
(533)
(635)
(508)
(343)
(416)
18"
(457)
29 1/2" 21 1/2" 13 7/8" 13 7/8"
(749) (546) (352) (352)
2"
(51)
(25.4)
(25.4) (1441)
12
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Right Return/Left Supply
L
M
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
Unit
A
B
C
D
E
F
G
H
J
K
N
P
Q
R
S
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
40"
(1016)
40"
(1016)
46"
(1168)
46"
(1168)
50"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
17"
(432)
17"
(432)
19"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
18"
(457)
18"
(457)
20"
6 7/8"
(175)
6 7/8"
(175)
8 1/4"
(210)
8"
(203)
11 1/2" 4 1/4"
(292) (108)
2 1/8"
(54)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
48 3/4" 23 3/4" 17 5/8" 23 1/2" 3 1/4"
(1238) (603) (448) (597) (83)
56 3/4" 31 3/4" 19 5/8" 23 1/2" 5 1/2"
(806) (498) (597) (140)
006,009
012, 015
018
9 7/8" 11 1/2" 4 1/4"
(251) (292) (108)
9 3/4" 13 1/2" 4 3/4"
(248) (343) (121)
2 5/8"
(67)
2 7/8"
(73)
8 1/4" 11 3/8" 13 1/2" 4 3/4"
(210)
2 7/8"
(73)
024, 030
036, 042
048, 060
(289)
(343)
(121)
4"
(102)
6 5/8"
(168)
10 1/2" 13 1/2" 16 3/8"
1 3/4"
(45)
(1270)
58"
(1473)
(635)
33"
(838)
(483)
21"
(533)
(635)
25"
(635)
(508)
28"
(711)
(267)
13 7/8" 13 7/8"
(352) (352)
(343)
(416)
18"
(457)
2"
(51)
(25.4)
(25.4) (1441)
WSHP-SVX01D-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Right Return/Back Supply
L
M
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
Unit
A
B
C
D
E
F
G
H
J
K
N
P
Q
R
S
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
40"
(1016)
40"
(1016)
46"
(1168)
46"
(1168)
50"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
17"
(432)
17"
(432)
19"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
18"
(457)
18"
(457)
20"
6 7/8"
(175)
6 7/8"
(175)
8 1/4"
(210)
8"
(203)
11 1/2" 4 1/4"
(292) (108)
2 1/8"
(54)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
48 3/4" 23 3/4" 17 5/8" 23 1/2" 3 1/4"
(1238) (603) (448) (597) (83)
56 3/4" 31 3/4" 19 5/8" 23 1/2" 5 1/2"
(806) (498) (597) (140)
006,009
012, 015
018
9 7/8" 11 1/2" 4 1/4"
(251) (292) (108)
9 3/4" 13 1/2" 4 3/4"
(248) (343) (121)
2 5/8"
(67)
2 7/8"
(73)
8 1/4" 11 3/8" 13 1/2" 4 3/4"
(210)
2 7/8"
(73)
024, 030
036, 042
048, 060
(289)
(343)
(121)
4"
(102)
6 5/8"
(168)
10 1/2" 13 1/2" 16 3/8"
1 3/4"
(45)
(1270)
58"
(1473)
(635)
33"
(838)
(483)
21"
(533)
(635)
25"
(635)
(508)
28"
(711)
(267)
13 7/8" 13 7/8"
(352) (352)
(343)
(416)
18"
(457)
2"
(51)
(25.4)
(25.4) (1441)
14
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Right Return/Right Supply
L
M
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
Unit
A
B
C
D
E
F
G
H
J
K
N
P
Q
R
S
NPTI
1/2"
(12.7)
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
3/4"
(19)
1"
40"
(1016)
40"
(1016)
46"
(1168)
46"
(1168)
50"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
17"
(432)
17"
(432)
19"
20"
(508)
20"
(508)
23"
(584)
23"
(584)
25"
15"
(381)
15"
(381)
18"
(457)
18"
(457)
20"
6 7/8"
(175)
6 7/8"
(175)
8 1/4"
(210)
8"
(203)
11 1/2" 4 1/4"
(292) (108)
2 1/8"
(54)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
38 3/4" 18 3/4" 13 5/8" 18 1/2" 3 3/8"
(984) (476) (346) (470) (86)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
44 3/4" 21 3/4" 15 5/8" 18 1/2" 4 1/4"
(1137) (552) (397) (470) (108)
48 3/4" 23 3/4" 17 5/8" 23 1/2" 3 1/4"
(1238) (603) (448) (597) (83)
56 3/4" 31 3/4" 19 5/8" 23 1/2" 5 1/2"
006,009
012, 015
018
9 7/8" 11 1/2" 4 1/4"
(251) (292) (108)
9 3/4" 13 1/2" 4 3/4"
(248) (343) (121)
2 5/8"
(67)
2 7/8"
(73)
8 1/4" 11 3/8" 13 1/2" 4 3/4"
(210)
2 7/8"
(73)
024, 030
036, 042
048, 060
(289)
(343)
(121)
4"
(102)
6 5/8"
(168)
10 1/2" 13 1/2" 16 3/8"
1 3/4"
(45)
(1270)
58"
(1473)
(635)
33"
(838)
(483)
21"
(533)
(635)
25"
(635)
(508)
28"
(711)
(267)
13 7/8" 13 7/8"
(352) (352)
(343)
(416)
18"
(457)
2"
(51)
(25.4)
(25.4) (1441)
(806)
(498)
(597)
(140)
WSHP-SVX01D-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Left Return/Top Supply
Unit
GEV
W.I.
NPTI NPTI FPT
1/2" 1/2" 3/4"
(12.7) (12.7) (19)
W.O. Drain
A
B
C
D
E
F
G
H
J
K
L
M
N
19 1/2" 31 1/4" 21 1/2" 11 1/2"
(495) (794) (546) (292)
4"
(102)
3 3/4"
(95)
16 1/2"
(419)
15"
(381)
18"
(457)
6 7/8"
(175)
8"
3/4"
(19)
2"
(51)
006-015
(203)
9 3/4"
(248)
11 3/8"
(289)
018, 024, 21 1/2" 39 1/4" 21 1/2" 13 1/2"
030, 040
4"
(102)
4"
(1021)
17 1/2" 23 3/4"
(445)
17"
(432)
8 1/4"
(368)
3/4"
(19)
2"
(51)
3/4"
(19)
3/4"
(19)
3/4"
(19)
(546)
(997)
(546)
(343)
(603)
24 1/2" 41 7/8" 26 1/2"
(622) (1064) (673)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
18"
(457)
18"
(457)
18"
3 1/4"
(83)
1 7/8"
(48)
2"
(51)
2"
19 1/2"
(495)
19"
(483)
29"
(737)
29"
23"
(584)
27"
(686)
27"
10 1/2" 13 1/2"
(267) (343)
13 7/8" 13 7/8"
(352) (352)
13 1/8" 11 3/8"
(333) (289)
1 3/4"
(19)
3/4"
(19)
1"
3/4"
(19)
1"
3/4"
(19)
3/4"
036, 042
Std-048
0
4 1/4"
(108)
4 1/4"
(108)
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(25.4) (25.4) (19)
1" 1" 3/4"
(25.4) (25.4) (19)
Hi-048,
060
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(457)
(51)
(737)
(686)
16
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Left Return/Back Supply
Unit
GEV
W.I.
NPTI NPTI FPT
1/2" 1/2" 3/4"
(12.7) (12.7) (19)
W.O. Drain
A
B
C
D
E
F
G
H
J
K
L
M
N
19 1/2" 31 1/4" 21 1/2" 11 1/2"
(495) (794) (546) (292)
4"
(102)
3 3/4"
(95)
16 1/2"
(419)
15"
(381)
18"
(457)
6 7/8"
(175)
8"
3/4"
(19)
2"
(51)
006-015
(203)
9 3/4"
(248)
11 3/8"
(289)
018, 024, 21 1/2" 39 1/4" 21 1/2" 13 1/2"
030, 040
4"
(102)
4"
(1021)
17 1/2" 23 3/4"
(445)
17"
(432)
8 1/4"
(368)
3/4"
(19)
2"
(51)
3/4"
(19)
3/4"
(19)
3/4"
(19)
(546)
(997)
(546)
(343)
(603)
24 1/2" 41 7/8" 26 1/2"
(622) (1064) (673)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
18"
(457)
18"
(457)
18"
3 1/4"
(83)
1 7/8"
(48)
2"
(51)
2"
19 1/2"
(495)
19"
(483)
29"
(737)
29"
23"
(584)
27"
(686)
27"
10 1/2" 13 1/2"
(267) (343)
13 7/8" 13 7/8"
(352) (352)
13 1/8" 11 3/8"
(333) (289)
1 3/4"
(19)
3/4"
(19)
1"
3/4"
(19)
1"
3/4"
(19)
3/4"
036, 042
Std-048
0
4 1/4"
(108)
4 1/4"
(108)
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(25.4) (25.4) (19)
1" 1" 3/4"
(25.4) (25.4) (19)
Hi-048,
060
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(457)
(51)
(737)
(686)
WSHP-SVX01D-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Right Return/Top Supply
Unit
GEV
W.I.
NPTI NPTI FPT
1/2" 1/2" 3/4"
(12.7) (12.7) (19)
W.O. Drain
A
B
C
D
E
F
G
H
J
K
L
M
N
19 1/2" 31 1/4" 21 1/2" 11 1/2"
(495) (794) (546) (292)
4"
(102)
3 3/4"
(95)
16 1/2"
(419)
15"
(381)
18"
(457)
6 7/8"
(175)
8"
3/4"
(19)
2"
(51)
006-015
(203)
9 3/4"
(248)
11 3/8"
(289)
018, 024, 21 1/2" 39 1/4" 21 1/2" 13 1/2"
030, 040
4"
(102)
4"
(1021)
17 1/2" 23 3/4"
(445)
17"
(432)
8 1/4"
(368)
3/4"
(19)
2"
(51)
3/4"
(19)
3/4"
(19)
3/4"
(19)
(546)
(997)
(546)
(343)
(603)
24 1/2" 41 7/8" 26 1/2"
(622) (1064) (673)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
18"
(457)
18"
(457)
18"
3 1/4"
(83)
1 7/8"
(48)
2"
(51)
2"
19 1/2"
(495)
19"
(483)
29"
(737)
29"
23"
(584)
27"
(686)
27"
10 1/2" 13 1/2"
(267) (343)
13 7/8" 13 7/8"
(352) (352)
13 1/8" 11 3/8"
(333) (289)
1 3/4"
(19)
3/4"
(19)
1"
3/4"
(19)
1"
3/4"
(19)
3/4"
036, 042
Std-048
0
4 1/4"
(108)
4 1/4"
(108)
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(25.4) (25.4) (19)
1" 1" 3/4"
(25.4) (25.4) (19)
Hi-048,
060
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(457)
(51)
(737)
(686)
18
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Right Return/Back Supply
Unit
GEV
W.I.
NPTI NPTI FPT
1/2" 1/2" 3/4"
(12.7) (12.7) (19)
W.O. Drain
A
B
C
D
E
F
G
H
J
K
L
M
N
19 1/2" 31 1/4" 21 1/2" 11 1/2"
(495) (794) (546) (292)
4"
(102)
3 3/4"
(95)
16 1/2"
(419)
15"
(381)
18"
(457)
6 7/8"
(175)
8"
3/4"
(19)
2"
(51)
006-015
(203)
9 3/4"
(248)
11 3/8"
(289)
018, 024, 21 1/2" 39 1/4" 21 1/2" 13 1/2"
030, 040
4"
(102)
4"
(1021)
17 1/2" 23 3/4"
(445)
17"
(432)
8 1/4"
(368)
3/4"
(19)
2"
(51)
3/4"
(19)
3/4"
(19)
3/4"
(19)
(546)
(997)
(546)
(343)
(603)
24 1/2" 41 7/8" 26 1/2"
(622) (1064) (673)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
26 1/2" 46 7/8" 30 1/2"
(673) (1191) (775)
18"
(457)
18"
(457)
18"
3 1/4"
(83)
1 7/8"
(48)
2"
(51)
2"
19 1/2"
(495)
19"
(483)
29"
(737)
29"
23"
(584)
27"
(686)
27"
10 1/2" 13 1/2"
(267) (343)
13 7/8" 13 7/8"
(352) (352)
13 1/8" 11 3/8"
(333) (289)
1 3/4"
(19)
3/4"
(19)
1"
3/4"
(19)
1"
3/4"
(19)
3/4"
036, 042
Std-048
0
4 1/4"
(108)
4 1/4"
(108)
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(25.4) (25.4) (19)
1" 1" 3/4"
(25.4) (25.4) (19)
Hi-048,
060
21 1/2"
(546)
2 1/4"
(57)
3 1/2"
(89)
(457)
(51)
(737)
(686)
WSHP-SVX01D-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Right Return/Left Supply
GEH 072-120 (60 Hz)
GEH 072-090 (50 Hz)
GEH
60 Hz
GEH
50 Hz
A
B
C
D
36 1/4" 15 5/8"
(921) (397)
36 1/8" 12 3/4"
6 5/8"
(168)
6 3/4"
(171)
7 1/4"
(184)
1 1/4"
(32)
072
090
120
-
1 1/4"
(32)
072
090
(917)
36 1/8"
(917)
(324)
13"
(330)
1 1/2"
(38)
20
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Right Return/Back Supply
GEH 072-120 (60 Hz)
GEH 072-090 (50 Hz)
GEH
60 Hz
GEH
50 Hz
A
B
C
D
36 1/4" 15 5/8"
(921) (397)
36 1/8" 12 3/4"
6 5/8"
(168)
6 3/4"
(171)
7 1/4"
(184)
1 1/4"
(32)
072
090
120
-
1 1/4"
(32)
072
090
(917)
36 1/8"
(917)
(324)
13"
(330)
1 1/2"
(38)
WSHP-SVX01D-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Left Return/Right Supply
GEH 072-120 (60 Hz)
GEH 072-090 (50 Hz)
GEH
60 Hz
GEH
50 Hz
A
B
C
D
36 1/8"
(917)
17"
(432)
8"
1 1/4"
(32)
072
090
120
-
(203)
7 3/4"
(197)
7 1/4"
(184)
36 1/8" 13 3/4"
1 1/4"
(32)
072
090
(917)
36 1/8"
(917)
(349)
13"
(330)
1 1/2"
(38)
22
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Left Return/Back Supply
GEH 072-120 (60 Hz)
GEH 072-090 (50 Hz)
GEH
60 Hz
GEH
50 Hz
A
B
C
D
36 1/8"
(917)
17"
(432)
8"
1 1/4"
(32)
072
090
120
-
(203)
7 3/4"
(197)
7 1/4"
(184)
36 1/8" 13 3/4"
1 1/4"
(32)
072
090
(917)
36 1/8"
(917)
(349)
13"
(330)
1 1/2"
(38)
WSHP-SVX01D-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Right Return/Left Supply
GEH 150-180 (60 Hz)
GEH 120-150 (50 Hz)
24
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Right Return/Back Supply
GEH 150-180 (60 Hz)
GEH 120-150 (50 Hz)
WSHP-SVX01D-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Left Return/Right Supply
GEH 150-180 (60 Hz)
GEH 120-150 (60 Hz)
26
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
GEH-Left Return/Back Supply
GEH 150-180 (60 Hz)
GEH 120-150 (50 Hz)
WSHP-SVX01D-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Front Return/Back Supply
6 - 10 Ton (60 HZ)
6 and 7 1/2 Ton (50 HZ)
Unit Size
6 Ton
A
B
C
6 5/8" 18 3/8" 1 1/4"
(168) (467)
6 5/8" 18 3/8" 1 1/4"
(168) (403)
7. 5 To n
10 Ton
6 1/2" 18 1/2" 1 1/2"
(165) (470)
28
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Front Return/Top Supply
6 - 10 Ton (60 HZ)
6 and 7 1/2 Ton (50 HZ)
Unit Size
6 Ton
A
B
C
6 5/8" 18 3/8" 1 1/4"
(168) (467)
6 5/8" 18 3/8" 1 1/4"
(168) (403)
7. 5 To n
10 Ton
6 1/2" 18 1/2" 1 1/2"
(165) (470)
WSHP-SVX01D-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Back Return/Front Supply
6 - 10 Ton (60 HZ)
6 and 7 1/2 Ton (50 HZ)
Unit Size
6 Ton
A
B
C
6 5/8" 18 3/8" 1 1/4"
(168) (467)
6 5/8" 18 3/8" 1 1/4"
(168) (403)
7. 5 To n
10 Ton
6 1/2" 18 1/2" 1 1/2"
(165) (470)
30
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Back Return/Top Supply
6 - 10 Ton (60 HZ)
6 and 7 1/2 Ton (50 HZ)
Unit Size
6 Ton
A
B
C
6 5/8" 18 3/8" 1 1/4"
(168) (467)
6 5/8" 18 3/8" 1 1/4"
(168) (403)
7. 5 To n
10 Ton
6 1/2" 18 1/2" 1 1/2"
(165) (470)
WSHP-SVX01D-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Front Return/Back Supply
12 1/2 and 15 Ton (60 HZ)
and
10 and 12 1/2 Ton (50 HZ)
32
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Back Return/Front Supply
12 1/2 and 15 Ton (60 HZ)
and
10 and 12 1/2 Ton (50 HZ)
WSHP-SVX01D-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Front Return/Top Supply
12 1/2 and 15 Ton (60 HZ)
and
10 and 12 1/2 Ton (50 HZ)
34
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Back Return/Top Supply
12 1/2 and 15 Ton (60 HZ)
and
10 and 12 1/2 Ton (50 HZ)
WSHP-SVX01D-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Front Return/Back Supply
20 and 25 Ton (60 HZ)
and
15 and 20 Ton (50 HZ)
Unit
60 HZ
Unit
50 HZ
A
B
C
D
E
15 5/8" 13 1/2"
(397) (341)
12"
(305)
51 5/8" 20 7/8"
(1310) (530)
20 Ton
15 Ton
25 Ton
20 Ton
14 3/4" 15 7/8" 13 7/8" 49 1/8" 23 1/2"
Std Static Std Static (375)
25 Ton 20 Ton 15 5/8" 13 1/2"
High Static High Static (397) (343)
(403)
(352)
(1248)
51 5/8" 23 1/2"
(1311) (597)
(597)
12"
(305)
36
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Back Return/Front Supply
20 and 25 Ton (60 HZ)
and
15 and 20 Ton (50 HZ)
Unit
60 HZ
Unit
50 HZ
A
B
C
D
E
15 5/8" 13 1/2"
(397) (341)
12"
(305)
51 5/8" 20 7/8"
(1310) (530)
20 Ton
15 Ton
25 Ton
Std Static Std Static
25 Ton 20 Ton
20 Ton
14 3/4" 15 7/8" 13 7/8" 49 1/8" 23 1/2"
(375)
(403)
(352)
(1248)
51 5/8" 23 1/2"
(1311) (597)
(597)
15 5/8" 13 1/2"
12"
(305)
High Static High Static (397)
(343)
WSHP-SVX01D-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Front Return/Top Supply
20 and 25 Ton (60 HZ)
and
15 and 20 Ton (50 HZ)
Unit
60 HZ
Unit
50 HZ
A
B
C
D
15 5/8" 13 1/2"
(397) (341)
12"
(305)
20 7/8"
(530)
20 Ton
15 Ton
25 Ton
20 Ton
14 3/4" 15 7/8" 13 7/8" 23 1/2"
Std Static Std Static
25 Ton 20 Ton
High Static High Static (397)
(375)
15 5/8" 13 1/2"
(343)
(403)
(352)
(597)
12"
(305)
23 1/2"
(597)
38
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Back Return/Top Supply
20 and 25 Ton (60 HZ)
and
15 and 20 Ton (50 HZ)
Unit
60 HZ
Unit
50 HZ
A
B
C
D
15 5/8" 13 1/2"
(397) (341)
12"
(305)
20 7/8"
(530)
20 Ton
15 Ton
25 Ton
Std Static Std Static
25 Ton 20 Ton
20 Ton
14 3/4" 15 7/8" 13 7/8" 23 1/2"
(375)
(403)
(352)
(597)
15 5/8" 13 1/2"
12"
(305)
23 1/2"
(597)
High Static High Static (397)
(343)
WSHP-SVX01D-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Waterside Economizer
Model GEH
Unit
60 HZ
Unit
50 HZ
A
B
Filter Size
(nominal)
C
D
E
F
G
H
J
K
L
M
N
NPTI
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
1"
NPTI
1/2"
(12.7)
3/4"
(19)
3/4"
(19)
1"
16 1/8" 13 5/8" 1 1/2" 10 3/4"
(410) (346) (38) (273)
18 1/2" 15 5/8" 1 1/2" 13 3/4"
(470)
21"
23"
(584)
26"
(660)
30"
(762)
34"
(864)
2 1/4"
(57)
7 1/2"
(191)
6 7/8"
(175)
6 1/4"
(159)
5 7/8"
(149)
1/2"
(12.7)
1/2"
(12.7)
1 1/4"
(32)
1"
(25.4)
1"
(25.4)
2"
(50.8)
2"
(50.8)
4"
(102)
4"
18 1/2"
(470)
14 3/4" x 23 3/4"
375 mm x 518 mm
16 3/4" x 23 3/4"
426 mm x 603 mm
18 3/4" x 25 1/2"
476 mm x 648 mm
20 3/4" x 29 7/8"
528 mm x 759 mm
006-015 006-012
018-030 015-024
036-042 030-036
048, 060 042-060
3 1/4"
(83)
18 1/2"
(470)
(397)
17 5/8" 2 1/4" 16 1/2"
(448) (57) (419)
(38)
(349)
(102)
3 3/4"
(95)
4 1/2" 23 1/2"
(114) (597)
4 1/2" 23 1/2"
(114) (597)
(533)
23 1/8" 19 5/8" 2 1/2" 19 1/2"
(587) (498) (64) (495)
5 1/4"
(133)
1 1/4"
(32)
(25.4)
(25.4)
40
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Waterside Economizer
Hanging Unit
Unit
60 HZ
Unit
50 HZ
Hanging
Weight
Shipping
Weight
A
B
C
D
E
38 3/4"
(984)
18 3/4"
(476)
21 3/4"
(552)
17"
(432)
54 lbs
(24.5 kg)
84 lbs
(38.2 kg)
006-015
018-030
036-042
048-060
006-012
015-024
030-036
042-060
0"
44 3/4"
(1137)
21 3/4"
(552)
24 3/4"
(629)
21"
(533)
1"
(25.4)
65 lbs
(29.5 kg)
95 lbs
(43.2 kg)
48 3/4"
(1238)
23 3/4"
(603)
28 3/4"
(730)
21"
(533)
2"
(50.8)
76 lbs
(35 kg)
106 lbs
(48 kg)
56 3/4"
(1442)
31 3/4"
(806)
32 3/4"
(832)
25"
(635)
1"
(25.4)
97 lbs
(44 kg)
127 lbs
(58 kg)
WSHP-SVX01D-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
Waterside Economizer
GEH 072-120, Right Return (60 Hz)
GEH 072-090, Right Return (50 Hz)
GEH
60 Hz
GEH
50 Hz
A
B
C
D
E
1 1/4"
(32)
1 3/8"
(35)
31"
(787)
9 7/8"
(251)
3 7/8"
(98)
072-090
120
072
090
1 1/2"
(38)
1 5/8"
(41)
30 3/4" 12 1/2"
(781) (318)
4 1/2"
(114)
42
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
Waterside Economizer
GEH 072-120, Left Return (60 Hz)
GEH 072-090, Left Return (50 Hz)
GEH
60 Hz
GEH
50 Hz
A
B
C
D
E
1 1/4"
(32)
1 3/8"
(35)
31"
(787)
9 7/8"
(251)
3 7/8"
(98)
072-090
120
072
090
1 1/2"
(38)
1 5/8"
(41)
30 3/4" 12 1/2"
(781) (318)
4 1/2"
(114)
WSHP-SVX01D-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
Waterside Economizer
GEH 150-180, Right Return (60 Hz)
GEH 120-150, Right Return (50 Hz)
44
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
Waterside Economizer
GEH 150-180, Left Return (60 Hz)
GEH 120-150, Left Return (50 Hz)
WSHP-SVX01D-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Waterside Economizer
6 - 10 Ton (60 HZ)
6 and 7 1/2 Ton (50 HZ)
Unit Size
A
B
C
1 3/8"
(35)
1 3/8"
(35)
4"
(102)
6 & 7 1/2 Ton
1 5/8"
(41)
1 5/8"
(41)
4 3/8"
(111)
10 Ton
46
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights
Waterside Economizer
GEV 12 1/2 through 25 Ton
Unit
60 HZ
Unit
50 HZ
A
NPTI
B
I.D.
OPERATING
WEIGHT
C
D
1 1/2"" 1 5/8" 15 7/8" 4 3/8"
275 lb
(125 kg)
12 1/2, 15 Ton 10, 12 1/2 Ton
(38)
(41)
(403)
(111)
310 lb
(141 kg)
20 Ton
25 Ton
15 Ton
20 Ton
2"
(51)
2 1/8" 16 1/4" 4 7/8"
(54) (413) (124)
395 lb
(179)
WSHP-SVX01D-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
General Installation Checks
The checklist below is a summary of
the steps required to successfully in-
stall a commercial unit. This checklist
is intended to acquaint the installing
personnel with what is required in the
installation process. It does not re-
place the detailed instructions called
out in the applicable sections of this
manual.
13 Inspect the heater junction box
and control panel; tighten any
loose connections.
6
7
Fabricate and install duct work.
Install and connect a condensate
drain line and trap to the drain
connection.
14 Check electric heat circuits for
continuity.
Low Voltage Wiring (AC & DC)
Requirements
15 Install the zone thermostat, with
WARNING
Hazardous
or without switching subbase.
Voltage!
1
Remove packaging and inspect the
unit. Check the unit for shipping
damage and material shortage; file
a freight claim and notify appropri-
ate sales representation.
Disconnect all electric power,
including remote disconnects
before servicing. Follow proper
lockout/tagout procedures to
ensure the power can not be
inadvertently energized. Failure to
disconnect power before
16 Connect properly sized control
wiring to the proper termination
points between the zone thermo-
stat and the unit control panel.
Note: The 1/2 through 5 ton units
have been tied to the skid by (2)
shipping bolts. The removal of
these bolts will require a 3/8" (9.7
mm) ratchet with a 1/2" (12.7 mm)
socket.
Filter Installation
servicing could result in death or
serious injury.
17 Each unit ships with 1" (25.4) or 2"
(50.8 mm) filters. The quantity of
filters is determined by unit size.
The horizontal1/2 through 5 ton
units requires a field installation
of the 1"/2" filter rack. All sheet-
metal bracket, filter and hardware
are in a box located on the side of
the unit within the unit packaging.
All 1/2 through 25 ton verticals
and 6 through 15 ton horizontal
units ship with the filter rack and
filters factory installed.
Main Electrical
8
Verify the power supply complies
with the unit nameplate specifica-
tions.
The GEV 6 through 25 ton units
have been anchored to the skid
with (4) angle brackets. Remove
these brackets before lifting unit
into place.
9
Inspect all control panel compo-
nents; tighten any loose connec-
tions.
10 Connect properly sized and pro-
tected power supply wiring to a
field-supplied/installed discon-
nect switch and to the main pow-
er terminal block 1K1 for 1/2
The GEH 6 through 15 ton units are
anchored to the cross brace of the
skid with (4) wood screws. Re-
move these screws prior to lifting
the unit into place.
Note: Do not operate the unit without
filters.
through 5 ton equipment or
1TB1for 6 through 25 ton equip-
ment in the unit control panel.
2
3
Verify the correct model, options
and voltage from the unit name-
plate.
11 Install proper grounding wires to
an earth ground.
Pull out all field attached parts (i.e.
filter rack, duct collar, filter and
mounting screws) from the unit
packaging for field mounting.
Note: All field-installed wiring must
comply with NEC and applicable local
codes.
Electric Heat Requirements
12 Verify that the power supply com-
plies with the electric heater
specifications on the unit and
heater nameplate.
4
5
Verify the installation location of
the unit will provide the required
clearance for proper operation.
Remove refrigeration access panel
and inspect the unit. Be certain the
refrigerant tubing has clearance
from adjacent parts.
48
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Supply-Air Ductwork
Install the 1" (25.4 mm) supply-air duct
flange to the vertical and horizontal
equipment with the (8) 5/16" (7.94 mm)
factory supplied Torx head screws.
The duct collar assembly for each unit
is located:
•
Model GEH 1/2 to 5 ton = in a box
on the side of the unit
• Model GEV 1/2 to 10ton = inside of
the refrigeration section of the unit
•
Model GEH 6 to 15 ton = of the re-
frigeration section of the unit
• Model GEV 12 1/2 to 25 ton = facto-
ry ship with a duct collar installed
for units containing a top supply-
air location. For units with a back
or front supply-air location, the
duct collar assembly must be or-
dered separately from the factory,
or be field provided.
Figure 4: Flexible supply-air connector (field provided)
When attaching the field ductwork to
the unit, provide a watertight flexible
connector at the unit to prevent oper-
ating sounds from transmitting
through the ductwork. See Figure 4.
Elbows with turning vanes or splitters
are recommended to minimize air
noise due to turbulence and to reduce
static pressure.
Return-Air Ductwork
Install the 1"/2" (25.4/50.8 mm) adjust-
able filter rack to the horizontal equip-
ment only with the use of (4) 5/16"
(7.94 mm) factory supplied Torx head
screws. The vertical equipment factory
ships with the filter rack and filter(s) in-
stalled.
When attaching the field ductwork to
the unit, provide a water tight flexible
connector at the unit to prevent oper-
ating sounds from transmitting
through the ductwork. See Figure 5.
Elbows with turning vanes or splitters
are recommended to minimize air
noise due to turbulence and to reduce
static pressure.
Figure 5: Flexible return-air connector (field provided)
WSHP-SVX01D-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Dual Filtration (GEH 1/2 to 5 ton)
The horizontal, GEH model, allows the
installer flexibility in design applica-
tions such as a dual filtration option.
With the dual filtration design, the unit
will contain a lower static which trans-
lates into a decrease in filter mainte-
nance. For installation of a dual
1
filtration accessory for the GEH mod-
el, verify that an extra set of return-air
filter racks and filter have been or-
dered from the factory. This accessory
will be shipped separate from the unit,
and should be located in a separate
box than the unit.
2
3
(1) Remove the return-air side panel
from the GEH unit. This panel is held
in place by six Torx head screws.
Note:
The dual-filtration design is
typically used in a free-return
application.
(2) Install the top/bottom filter rack at
the new opening. The 1"/2" (25.4/50.8
mm) adjustable filter rack is held in
place with four Torx head screws that
once held the panel.
(3) Install the 1"/2" (25.4/50.8 mm)
filter.
Return-Air Duct Panel
The return-air arrangement may be
easily converted from a free return-air
system, to a ducted return-air system
with the addition of a return-air side
panel on the GEH unit. By replacing
the filter racks with the return-air pan-
el, a complete seal from the ductwork
to the unit is possible. The 1 1/2" (38
mm) duct flange facilitates ease of
field hook-up to the mechanical
system.
1
(1) Install the return-air duct panel to
the return-air opening with the six
Torx head screws provided for the fil-
ter rack assembly.
Note:
Table 3: Opening size and part number
The ducted panel design is
typically used in combination
with a field installed ceiling
filter rack design.
Unit Size
60 HZ
Unit Size
50 HZ
Duct Collar
A
B
Part Number
006-015
018-030
036-042
048-060
006-012
015-024
030-036
042-060
17 1/2" (445)
20 1/2" (521)
22 1/2" (572)
26 1/2" (673)
13" (330)
15" (381)
17" (432)
19" (483)
4474 1133 0100
4474 1134 0100
4474 1135 0100
4474 1136 0100
50
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Sound Attenuation Pad
For sound sensitive installations, a vi-
bration pad (field provided) should be
placed beneath the horizontal or verti-
cal equipment. For the horizontal unit,
the pad should be approximately
twice the size of the unit foot print. For
the vertical unit, the pad should be 1/2"
(12.7 mm) thick, and equal to the over-
all unit foot print.
WARNING
Improper Unit Lift!
Test lift unit approximately 24
inches to verify proper center of
gravity lift point. To avoid drop-
ping of unit, reposition lifting
point if unit is not level. Failure to
properly lift unit could result in
death or serious injury or
possible equipment or prop-
erty-only damage.
Hanging the Horizontal Unit
To hang the horizontal configuration:
(1) Install the hanging isolators (locat-
ed in the return-air section of the unit)
into the four hanging brackets.
(2) Secure the equipment to a joist,
concrete, etc. with the use of 3/8"
(9.7 mm) field provided (all-thread)
rod. Each corner should contain field
provided nuts and washers to com-
plete the hanging installation.
(3) Unit slope or pitch should conform
to national and local codes. This is the
responsibility of the contractor.
Condensate Drain Connection
Install proper trapping to the equip-
ment. The unit drain connection is 3/4"
(19 mm) for all GEH and GEV models.
When designing the condensate trap
for the water-source system, it’s im-
portant to consider the unit’s draw-
thru design requiring negative pres-
sure trapping.
In a properly trapped system,
when condensate forms during
normal operation, the water level
in the trap rises until there is a
constant flow. It is imperative to
maintain water in the trap and
not allow the trap to dry out dur-
ing heating season. Keeping
trap primed at all times will
enable the water to flow
properly. See Figure 6 for
appropriate dimensions
required in a negative pressure
system.
Figure 6: Negative pressure system
WSHP-SVX01D-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Note:
The Figure 7 example
Supply/Return Pipe Connections
Connect the supply and return hoses to
the water-inlet (from supply) and
water-outlet (to return)
of the unit. For
vibration isola-
tion, it is rec-
ommended
that flexible
steel braided
hoses be in-
incorporates the Hays
Measurflo balancing hose kit and a 2-posi-
tion isolation valve into the system design.
An isolation valve is often used in variable
speed pumping applications. The isolation
valve is designed to stop water flow to the
unit during non operation times. This al-
lows the loop water pumps to run only
when a requirement for pumping is needed
for greater energy efficiency of the overall
system design.
stalled instead
of hard piping
the equipment
to the main
loop system.
Figure 7 shows
connection of a
Hays Measurf-
lo balancing
hose kit to the
water-in and
water-out of a
vertical unit.
Figure 7: Supply/Return pipe connections
Types of Hose Connections
Whether installing the units in a central
pump (main/auxiliary pump for the en-
tire zone) design, or as a distributed
pump (1-pump per unit) design, a shut-
off device and flexible hose is recom-
mended to transition from the hard pip-
ing of the closed or open loop water
system to the unit. There are multiple
hose combinations which may be used
to fit the design or specification criteria
for the installation.
Option 1: Flexible hoses
(1) A steel braided hose without a shut-
off device is the least expensive means
of connecting the heat pump to the sup-
ply/return water loop.
(2) With the addition of a shut-off device
on the supply and return of the system,
the unit may be isolated during service
or maintenance situation. This system
may be installed as a wide open (full wa-
ter flow to the equipment) design, or
manually balanced by utilizing the pres-
sure/temperature ports on the top of the
ball valve/shut-off device.
Option 2: Flexible hoses with ball valves
52
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Types of Hose Connections
(3) A circuit setter provides a means of
manually balancing the water flow to
the heat pump. This manual in-line
balancing method is accurate up to
20%. In order to determine flow rate,
the user must record both handle posi-
tion, and differential pressure drop.
Then, the user must consult a chart
containing both pieces of information
and make the necessary adjustments
to the circuit setter.
(4) For self balancing flow control, a
Hays Measurflo® balancing hose kit
provides a constant flow rate over the
pressure differential range of 2 to 80
psid. As system pressures change
(through the addition of heat pumps,
for example) each individual flow con-
trol valve will automatically adjust to
the new system conditions.
Option 3: Flexible hoses with ball valves and circuit setter
Additional accessories, such as a
strainer are recommended for use to
eliminate contaminants from entering
the co-axial water-to-refrigerant heat
exchanger.
Option 4: Flexible hoses with automatic balancing flow control
Cleaning and Flushing
the Water Loop
After the piping system is complete,
the flexible hose connectors should be to the system to replace the volume
doubled back to complete the water
circuit external to the unit (avoiding
trash settle-out in the condenser). An (3) With the air vented and the water
Note: Make up water must be available (5)Open the system at the lowest point
for the initial blow down (making sure
the make up water is equal to the water
being dumped). Continue blow down
until the water leaving the drain runs
clear, but not less than 2 hours.
formerly occupied by the air that is
bled off.
extra pipe may be necessary to con-
nect the hose kits.
circulating, the entire system should
be checked for leaks with repairs made
as required.
(6) Shut down pumps and supplemen-
tary heat system. Reconnect the hoses
placing the water-to-refrigerant heat
exchanger in the water circulating sys-
tem.
(1)Water circulation system should be
filled with clean water using the water
make up connections. Note: Air vents
should be open during filling.
(4) Operate the supplementary heat
system (boiler) making checks per
manufacturer’s instructions. During
this operation, visual checks should be
made for leaks that may have occurred
due to increased heat. Repair as re-
quired.
(2) With the air vents closed, start the
circulating pump and then crack the air
vents to bleed off the trapped air, as-
suring circulation through all compo-
nents of the system.
Note: Vents should be open when the
pumps and supplementary heat sys-
tem are shut down.
WSHP-SVX01D-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Connecting a
Water Regulating Valve
The water regulating valve assembly
is shipped as a separate item. Connec-
tions from the valve assembly to the
unit must be made by the installing
contractor.
Note:
Water regulating valves are most com-
monly applied with vapor-cycle refrigera-
tion systems that use capillary tube
metering devices to maintain suitable
head or suction pressure levels for proper
compressor loading. They are seldom ap-
plied when thermal expansion valves
(TXV’s) are used.
IMPORTANT: These valves are not
positive shut-off devices. Use a slow-
closing solenoid valve in the heat
pump’s leaving water line to assure
positive shut-off in variable-pump-
ing applications.
Installation for
Single Compressor Units
(1) Connect the MPT connection on
the valve assembly to the unit water
out FPT connection. Note: A field sup-
plied union or elbow may be required
to connect the water regulating valve
assembly to the unit. All field supplied
fittings should be brass or copper.
(2) Connect the valve depressor with a
1/4" (6.35 mm) flare nut to the 1/4"
(6.35 mm) schrader tap on the unit.
Note: The pressure-sensing lines from
both regulators have been "tee’d" to-
gether.
(3) Adjust the regulator head pressure
to meet specified conditions. See
Table 4.
Table 4: Typical water regulating valve
operating pressures
Note: If the unit has not been ordered
with a water regulating tap, and the
tap is field installed, it is important the
tap be made on the copper tube be-
tween the reversing valve and the wa-
ter-to-refrigerant heat exchanger. This
is the only part of the heat pump re-
frigerant circuit that serves as both a
discharge line during the cooling cy-
cle, and a suction line during the heat-
ing cycle. To avoid shavings, particles
and dirt from entering the system, it is
recommended that the 1/4" (6.35 mm)
hole be burned in the copper vs.
drilled in the copper.
Installation for
Multiple Compressor Units
Discharge
Pressure
Cooling Cycle
Suction
Pressure
Heating Cycle
Water Temp
Entering WSHP
Unit
A water regulating schrader option is
not available factory shipped on the
12 1/2 through 25 ton units. All prepa-
rations for the acceptance of a water
regulating valve assembly must be
made in the field.
80F Return Air 70F Return-Air
160 psig
46-54 psig
(minimum)
45 F
50 F
55 F
160 psig
52-60 psig
(minimum)
160 psig
56-66 psig
(minimum)
60 F
65 F
166-190 psig
178-204 psig
60-72 psig
62-74 psig
54
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Power Wiring
Field Installed Power Wiring
Power wiring to the equipment must
conform to National and Local Electric
Codes (NEC) by a professional
electrician.
The high voltage connection is made
at the 1K1 contactor or 1TB1 power
block inside the unit control box. See
Figure 8. Refer to the customer con-
nection diagram that is shipped with
the unit for specific termination points.
Provide proper grounding for the unit
in accordance with the local and na-
tional codes.
WARNING
Live Electrical
Components!
Control Power Transformer
The 24-volt control power transform-
ers are to be used only with the acces-
sories called out in this manual.
Transformers rated greater than 50 VA
are equipped with internal circuit
breakers. If a circuit breaker trips, turn
OFF all power to the unit before at-
tempting to reset it.
During installation, testing, ser-
vicing and troubleshooting of this
product, it may be necessary to
work with live electrical compo-
nents. Have a qualified licensed
electrician or other individual
who has been properly trained in
handling live electrical compo-
nents perform these tasks. Failure
to follow all electrical safety pre-
cautions when exposed to live
electrical components could re-
sult in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, in-
cluding remote disconnects be-
fore servicing. Follow proper
lockout/tagout procedures to en-
sure the power can not be inad-
vertently energized. Failure to
disconnect power before servic-
ing could result in death or seri-
ous injury.
Verify that the power supply available
is compatible with the unit’s name-
plate. Use only copper conductors to
connect the power supply to the unit.
CAUTION
Use Copper
Conductors Only!
Unit terminals are not designed
to accept other types of conduc-
tors. Failure to use copper con-
ductors may result in equipment
damage.
The transformer is located in the
control panel.
Main Unit Power Wiring
A field supplied disconnect switch
must be installed at or near the unit
in accordance with the National Elec-
tric Code (NEC latest edition).
Location of the applicable electric
service entrance for HIGH (line volt-
age) may be found on the unit sub-
mittal at the front of this manual
(pages 10 through 47).
Figure 8: Example of power wiring
WSHP-SVX01D-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Low Voltage Wiring
Thermostat Location
Location of the thermostat or zone
sensor is an important element of ef-
fective room control.
Areas where the thermostat or zone
sensor should not be located include:
Behind doors or corners; Near hot or
cold air ducts; Near radiant heat (heat
emitted from appliances or the sun);
Near concealed pipes or chimneys; On
outside walls or other non conditioned
surfaces; In air-flows from adjacent
zones or other units. See Figure 9 for
thermostat/sensor location.
Figure 9: Thermostat/sensor location
Controls Using 24 VAC
Before installing any wire, refer to the
electrical access locations on the unit
submittals located on page 10.
Ensure that the AC control wiring be-
tween the controls and the unit’s ter-
mination point does not exceed three
(3) ohms/conductor for the length of
the run.
Note: Resistance in excess of 3-ohms
per conductor may cause component
failure due to insufficient AC voltage
supply.
Check all loads and conductors for
grounds, shorts, and mis-wiring.
Use copper conductors unless other-
wise specified.
Do not run the AC low voltage wiring
in the same conduit with the high volt-
age power wiring.
Table 5: 24V AC conductors
Distance
from unit to Control
Recommended
Wire Size
000-460 feet
461-732 feet
733-1000 feet
18 gauge
16 gauge
14 gauge
Low voltage connection diagrams for
basic and deluxe 24 volt control pack-
ages mounted on 1/2 through 5 ton
equipment sizes are shown in Figure
10.
Figure 10: Low voltage connection (1/2
through 5 ton equipment)
56
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Low Voltage Wiring
Controls Using 24 VAC
There are two factory thermostat op-
tions for the dual circuited (6 through
25 ton) equipment. Low voltage con-
nection diagrams for deluxe 24 volt
control packages for these thermo-
stats mounted on 6 through 25 ton
equipment sizes are shown in Figure
11.
For controls using DC analog input/
outputs, see appropriate installation,
operation and diagnostic manuals for
connection. WSHP-IOP-2 (ZN510) and
WSHP-PRB002-EN (ZN524).
Figure 11: Low voltage connection (6 to 25 ton)
Table 6: Deluxe controller diagnostic LEDs
Deluxe Board Diagnostics
Color: Green
Color: Red
Controller
Three light emitting diodes (LEDs) are
provided for indicating the operating
mode of the Deluxe Controller. The
LEDs are intended to aid in trouble-
shooting and for unit maintenance.
The LEDs are labeled on the circuit
board with numbers as referenced in
Table 6.
Mode
LED1
OFF
ON
LED2
LED3
OFF
OFF
OFF
Control OFF
Normal/Compressor OFF
OFF
ON
OFF
FLASH Anti-short cycle
ON
OFF
ON
OFF
ON
Normal/Compressor ON
FLASH
ON
ON
Brownout Condition
FLASH
FLASH
ON
Soft Lockout (low pressure)
ON
FLASH Soft Lockout (high pressure)
ON Manual Lockout (low pressure)
FLASH Manual Lockout (high pressure)
ON
ON
ON
ON
FLASH
OFF
Manual Lockout (condensate over-
flow)
ON
ON
OFF
Compressor Disable
WSHP-SVX01D-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Air Flow Adjustment
Blower Motor Speed-Tap Retrofit (for 1/2 Through 5 Ton Units ONLY)
Motors installed in the unit include 4-speed and 3-speed configurations. All voltages include a 4-speed configuration, with
the exception of 380V, 415V, 460V which contain a 3-speed arrangement and 575V which contains a 2-speed arrangement.
To modify the rpm of the motor, the following steps may be followed.
WARNING
Hazardous Voltage!
Disconnect all electric power, in-
cluding remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Step 2
Step 1
Step 3
Remove service access panel at the unit
front.
Find the blower motor relay. The relay is
highlighted above. The relay location is
consistent in all control configurations.
Step 4:
Step 5:
Step 6:
For units w/o Hot Gas Reheat
For units w/o Hot Gas Reheat
Install service front panel.
Remove undesired speed-tap wire from 1K4 Select desired speed-tap wire.
Reconnect power to the unit.
relay at spade 3. Wire tie the lead, to
eliminate a short.
Connect desired speed tap wire to 1K4 relay
at spade 3.
For units with Hot Gas Reheat
For units with Hot Gas Reheat
Remove undesired speed-tap wire from 1K8 Select desired speed-tap wire.
relay at spade 6. Wire tie the lead, to
eliminate a short.
Connect desired speed tap wire to 1K8 relay
at spade 6.
4-Speed Motor (115, 208, 230, 265)
3-Speed Motor (380, 415, 460)
2-Speed Motor (575)
Lead Colors
Lead Colors
Lead Colors
Black
High
Blue
Medium Medium
High Low
Orange
Red
Low
Black
High
Blue
Orange
Low
Black
High
Blue
Low
Lead
Speed
Lead
Speed
Lead Speed
Medium
Note: When using the medium or low speed tap, the
purple wire must be jumpered to the high speed tap (blk).
58
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Air Flow Adjustment
Air Flow Adjustment
(6 through 25 ton units ONLY)
To increase CFM, loosen the turns
open set screw on the sheave, and
turn the sheave clockwise.
To decrease CFM, Loosen the turns
open set screw on the sheave, and
turn the sheave counterclockwise.
To increase belt tension, loosen the
adjustment bolt and pull motor
mounting plate back until the belt is
tight. Tighten the adjustment bolt after
the belt has reached the desired ten-
sion.
See Figure 12 for fan motor and
sheave adjustment.
WARNING
Rotating Components!
Disconnect all electric power, in-
cluding remote disconnects be-
fore servicing. Follow proper
lockout/tagout procedures to en-
sure the power can not be inad-
vertently energized. Failure to
disconnect power before servic-
ing could result in death or seri-
ous injury.
Figure 12: Fan motor and sheave
adjustment
WSHP-SVX01D-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Waterside Economizer
systems be made via 3-screws
spaced evenly across the top,
3-screws spaced evenly across
the bottom (installed immediate-
ly after hanging the unit), and 2-
screws on each side.
6 Install the SUPPLY and RETURN
WARNING
Hazardous
Voltage!
hoses to the (1) 2-position valve’s
threaded connection (2) water-
out threaded connection of the
water-source heat pump.
Disconnect all electric power,
including remote disconnects
before servicing. Follow proper
lockout/tagout procedures to
ensure the power can not be
inadvertently energized. Failure to
disconnect power before
servicing could result in death or
serious injury.
The following steps were sequenced
to aid in the installation and mating of
a water side economizer to a water-
source heat pump (GEH 1/2 to 5 ton).
Step 4
1 Remove the control side service
panel of the water-source heat
pump unit.
5 Install the 18-inch steel braided
hose between the upper most
piping connection of the econo-
mizer, and the water-in of the
heat pump. The hose is shipped
loose with the water-side econo-
mizer.
Step 6
7 VERIFY
2 Remove rubber isolation grom-
mets from the return-air section.
Place them in a convenient loca-
tion.
The control board for the water
side economizer is located at the
back of the control box. The tem-
perature rating of this board is
factory set to 55ºF.
3 Attach ducted panel to the water-
source heat pump unit with six
factory provided Torx® head
screws. This panel is shipped
loose with the water-source heat
pump but must be field installed
to the unit.
For units with boilerless (electric
heat) control and water side
economizer, the boilerless con-
trol board is factory set to 45ºF.
Step 5
Step 3
4 Attach the water side economiz-
ing unit to the ducted panel of the
water-source heat pump with 10-
factory provided Torx head
Step 7
screws. The economizing pack-
age fits to the outside of the of the
water-source heat pump. Trane
recommends the mating of the
60
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Waterside Economizer
8 Thread the bulb and wire through
the low voltage hole of the water-
source heat pump.
11 Thread the valve’s wire lead
through the low voltage hole of
the heat pump.
14 Install control side service panel.
15 Install the six hanging isolation
grommets into the hanging
brackets The unit isolators were
located in the return-air section
of the unit. See Step 2. Isolators
for the economizing package are
located with the economizer.
Step 8
9 Wire-tie the sensor to the water
SUPPLY side of the piping (ON,
or BEFORE) the 2-position valve.
Step 11
12 Wire the valve to the terminal
strip according to the unit wire
diagram located on the service
control panel.
Step 15
16 Insulate the economizing piping
package and the supply/return/
by-pass hoses (3-hoses) via field
provided pipe insulation. Insu-
lating the piping will stop con-
densation from forming on the
pipe and dripping onto the ceil-
ing tiles.
Note: Trane does not provide in-
sulation on the economizing
piping package. This insulation
must be field provided and field
installed.
Step 9
10 Bundle excess sensor wire, and
wire tie the bundle neatly.
RED = 1TB1-14
BLK = 1TB1-18
WHT = 1TB1-15
17 Install filter rack (top and bottom)
to the economizing package. The
filter rack is located in the unit’s
packaging along with the filter.
13 Bundle excess valve wire, and
wire tie the bundle neatly.
18 Hang Unit. See page 51 for hang-
ing of the packaged unit.Bottom
screws referenced in step 4
must be installed at this time.
Step 10
Step 13
WSHP-SVX01D-EN
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Waterside Economizer
19 Field pipe the drain lines of the
waterside economizer and wa-
ter-source heat pump together
prior to installing a condensate
trap. See page 51 for proper
trapping of condensation.
Step 19
Unit
60 HZ
Unit
50 HZ
Waterside Economizer
Part Number
006-015
018-030
036-042
048-060
006-012
015-024
030-036
042-060
4474 1690 0100
4474 1691 0100
4474 1692 0100
4474 1693 0100
62
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Waterside Economizer
cabinet to the unit compressor
compartment center post.
15 Connect the factory installed
WARNING
Hazardous
wire harness to the to the wire
harness supplied with the 3-way
valve.
8 Install the field portion of the wa-
ter piping and the 3-way valve to-
gether.
Voltage!
Actuator Wire #
Factory Harness Wire #
Color
Disconnect all electric power, in-
cluding remote disconnects be-
fore servicing. Follow proper
lockout/tagout procedures to en-
sure the power can not be inad-
vertently energized. Failure to
disconnect power before servic-
ing could result in death or seri-
ous injury.
Color
1 BLK
=
=
=
25L-Black
23T-White
73A-White
9
VERIFY
2 WHT
3 WHT
The control board for the water-
side economizer is located at the
back of the control box. The tem-
perature rating of this board is
factory set to 55ºF.
16 Bundle excess valve wire, and
wire tie the bundle neatly.
10 Thread the economizer’s enter-
ing water temperature sensor
(4RT1) through the water-in line
of the water-source heat pump.
This sensor is used by the econo-
mizer’s 3-way valve to determine
if water flow should be directed
through the waterside economiz-
ing coil.
17 Install control side service panel
to the heat pump.
The following steps were sequenced
to aid in the installation and mating of
a waterside economizer to a water-
source heat pump (GEV and GEH 6
through 25 ton models).
18 Install the unit filter frame to the
economizing inlet.
1 Remove the filter frame from the
unit.
19 Insulate the economizing piping
package with field supplied pipe
insulation. Insulating the piping
will help stop condensation from
forming on the pipe.
2
Remove the waterside service
panel from the unit.
11 Tie wrap the thermistor to the
water line (supply side) upstream
of the water pipe to the econo-
mizer. The thermistor must be sit-
uated so that the thermistor is
capable of reading the actual en-
tering water temperature regard-
less of the economizer’s on or off
situation.
3
Remove the control box service
panel from the unit.
Note: Trane does not provide
insulation on the economizing
piping package. This insulation
must be field provided and field
installed.
4 Remove the economizer and mis-
cellaneous mounting parts from
it’s packaging.
20 Install waterside service panel to
5 GEV ONLY: Mount the economiz-
er support angle (4475 1637 0100)
found in the economizer packag-
ing in the same holes of the re-
turn air filter frame removed in
step 1. The support angle screws
into the unit roof.
the heat pump.
12 Insulate the thermistor with tub-
ing insulation.
21 Field pipe the drain lines of the
waterside economizer and water-
source heat pump together prior
to installing a condensate trap.
See page 51 for proper trapping
of condensation. The economizer
condensate line must be trapped
prior to the unit’s drain line. This
helps prevent air from being
sucked through the drain line
causing condensate to spit or
build-up in the economizer or
unit drain pans.
13 Tie wrap each end of the tubing
insulation to prevent air filtration.
The tie wraps and insulation are
located in a baggie and shipped
inside of the unit.
6 GEV ONLY: Hang the economizer
assembly from the economizer
support angle mounted in step 5.
14 Thread the factory wire harness
through the low voltage hole of
the heat pump to the 3-way
valve’s wire harness.
7 Secure the economizer to the unit
using the four plates (4475 1630
0100) found in the economizer
packaging. Two plates should be
applied to each economizer side.
GEV ONLY: Secure the bracket on
the bottom of the economizer
WSHP-SVX01D-EN
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Waterside Economizer
Start-up Sequence
1
2
3
Set the thermostat to the highest position.
Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized.
Adjust water flow utilizing pressure/temperature plugs and comparing to tables contained in specification sheet data.
Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9-12ºF);
blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction
line should be cool with no frost observed in the refrigerant circuit.
4
5
Check the cooling refrigerant pressures against values in Table 7 on page 75. NOTE: If cooling mode is activated, and
the entering water temperature of the heat pump falls below 55ºF, the 2-position, water side economizing valve will
become energized (open) and compressor operation will halt allowing for free cooling in the space.
Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-
energize.
6
7
8
9
Leave unit off for approximately FIVE minutes to allow for pressure equalization.
Turn the thermostat to the lowest setting.
Set the thermostat system switch to the HEAT position.
Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water
temperature decrease of approximately 5-9 F leaving the heat exchanger should be noted. The blower and compressor
operation should be smooth with no frost observed in the refrigeration circuit.
10 Check the heating refrigerant pressures against values in Table 7 on page 75. NOTE: For units with boilerless electric
heat option...In heating mode, if the entering water temperature of the heat pump falls below 45ºF, the electric heater
will be energized, and compressor operation will halt. Once the entering water temperature rises above 50ºF, the boil-
erless controls returns the unit to normal operation.
11 Set the thermostat to maintain the desired space temperature.
12 Instruct the owner on system operation.
64
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Waterside Economizer
Waterside Economizing Three-Way Valve Specifications
Valve
Valve
Valve
Valve
Temperature
Range
Unit Size
60 HZ
Unit Size
50 HZ
Connection Pressure Close-off
Actuator
Size
Rating
Pressure
200 psi
• Non-spring return type
• 24 VAC +/- 20%
• 135 second stroke time
• 10 Cv at full port
GEH
006-015
GEH
006-012
0ºF to 212ºF
-18ºC to 121ºC
1/2" FPT
600 psi
• Non-spring return type
• 24 VAC +/- 20%
GEH
018-042
GEH
015-036
0ºF to 212ºF
-18ºC to 121ºC
3/4" FPT
1" FPT
600 psi
600 psi
600 psi
600 psi
600 psi
200 psi
200 psi
200 psi
200 psi
200 psi
• 135 second stroke time
• 30 Cv at full port
• Non-spring return type
• 24 VAC +/- 20%
• 135 second stroke time
• 23 Cv at full port
GEH
048-060
GEH
042-060
0ºF to 212ºF
-18ºC to 121ºC
• Non-spring return type
• 24 VAC +/- 20%
GEV/GEH
6 - 7 1/2 Ton
GEV
6 Ton
0ºF to 212ºF
-18ºC to 121ºC
1 1/4 FPT
• 135 second stroke time
•
33 Cv at full port
• Non-spring return type
• 24 VAC +/- 20%
• 135 second stroke time
• 37 Cv at full port
GEV/GEH
7 1/2-12 1/2 1 1/2" FPT
Ton
GEV/GEH
10-15 Ton
0ºF to 212ºF
-18ºC to 121ºC
• Non-spring return type
• 24 VAC +/- 20%
• 135 second stroke time
• 57 Cv at full port
GEV
GEV
0ºF to 212ºF
-18ºC to 121ºC
2" FPT
20 & 25 Ton 15 & 20 Ton
The valve body is constructed from forged brass with nickel plating, with the ball
and stem constructed of stainless steel.
For other information pertaining to the economizing water valve, see the valve’s
data plate.
WSHP-SVX01D-EN
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E1-Electrical performance
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric
Electric
Heat
Amps
Circuit
Overcur-
rent
Heat
kW
Ampacity
Protec-
tive
Device
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
25
15
15
15
15
15
15
15
15
15
20
15
15
15
15
15
20
15
20
15
20
15
20
15
20
15
20
15
20
20
25
15
25
15
15
006
115/60/1
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
220-240/50/1
265/60/1
265/60/1
115/60/1
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
220-240/50/1
265/60/1
265/60/1
115/60/1
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
220-240/50/1 12.02
265/60/1
265/60/1
220-240/50/1
220-240/50/1
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
6.8
3.4
4.48
3.4
4.88
3.6
7.3
3.0
5.5
8.3
4.0
6.48
4.0
7.08
5.0
9.72
3.6
8.0
12.2
5.7
8.5
5.70
2.80
2.8
2.80
2.8
3.10
3.1
2.45
2.5
7.20
3.40
3.4
3.40
3.4
4.30
4.3
3.10
3.1
10.60
5.00
5.0
5.00
5.0
4.80
4.8
4.30
4.3
6.3
6.3
5.40
5.4
5.40
5.4
6.30
6.3
4.80
4.8
7.6
7.6
7.6
7.6
6.3
6.3
7.60
7.6
7.60
7.6
9.90
9.9
6.30
6.3
36.2
17.7
17.7
17.7
17.7
18.8
18.8
15.0
15.0
45.6
22.2
22.2
22.2
22.2
22.2
22.2
18.8
18.8
56.7
27.9
27.9
27.9
27.9
27.0
27.0
22.2
22.2
32.0
32.0
29.0
29.0
29.0
29.0
32.0
32.0
27.0
27.0
45.0
45.0
45.0
45.0
32.0
32.0
45.0
45.0
45.0
45.0
55.0
55.0
32.0
32.0
25.0
25.0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
9.1
4.6
4.6
4.6
4.6
5.2
5.2
3.9
3.9
10.9
6.4
6.4
6.4
6.4
6.6
6.6
5.2
5.2
16.0
8.3
8.3
8.3
8.3
8.5
8.5
6.6
6.6
10.0
10.0
9.2
9.2
9.2
1.20
0.60
0.60
0.60
0.60
0.52
0.52
0.52
0.52
1.20
0.60
0.60
0.60
0.60
0.72
0.72
0.52
0.52
1.57
0.70
0.70
0.70
0.70
0.72
0.72
0.72
0.72
0.80
0.80
0.70
0.70
0.70
0.70
1.53
1.53
0.72
0.72
0.9
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/12
1/8
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8.3
4.1
5.6
4.1
6.1
4.4
9.2
3.6
6.9
10.2
4.9
8.1
4.9
8.9
6.1
12.2
4.4
10.0
14.8
7.0
10.6
7.0
11.8
6.7
15.0
6.1
13.4
8.7
18.1
7.5
12.9
7.5
14.5
9.4
0
0
0.82
0
1.00
0
1.64
0
1.33
0
0
1.23
0
1.50
0
2.17
0
2.00
0
0
1.63
0
2.00
0
2.70
0
2.65
0
3.28
0
2.00
0
2.50
0
3.28
0
3.30
0
2.46
0
3.0
0
4.00
0
2.46
0
3.00
0
0
0
3.9
0
4.3
0
6.8
0
5.0
0
0
5.9
0
6.5
0
9.0
0
7.5
0
0
7.8
0
8.7
0
11.3
0
10.0
0
13.7
0
9.6
0
10.9
0
13.7
0
12.5
0
11.8
0
13.0
0
15.1
0
11.8
0
13.0
0
009
1/8
1/12
1/12
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/3
1/3
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/3
1/3
1/3
1/3
1/3
1/3
012
5.7
9.4
5.5
5.0
10.72
7.1
14.5
6.1
10.3
6.1
11.6
015 - Std
Static
015 - Hi
Static
9.2
7.8
10.0
10.0
8.5
220-240/50/1 15.23
19.0
6.7
265/60/1
265/60/1
208/60/1
208/60/1
230/60/1
230/60/1
265/60/1
265/60/1
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
5.5
13.22
8.5
12.7
8.5
13.9
7.1
15.9
9.4
13.6
9.4
14.8
11.4
8.5
16.5
10.4
15.9
10.4
17.4
8.7
19.9
11.6
17.4
11.6
18.9
13.9
24.5
9.4
018 - Std
Static
13.0
13.0
13.0
13.0
10.0
10.0
13.0
13.0
13.0
13.0
13.8
13.8
10.0
10.0
5.4
0.90
0.90
0.90
0.80
0.80
2.10
2.10
2.10
2.10
1.53
1.53
1.53
1.53
0.95
0.95
018 - Hi
Static
220-240/50/1 19.63
265/60/1
265/60/1
380-415/50/3
4.35
0
4.00
0
18.1
0
15.1
0
7.8
16.63
4.9
1/3
1/3
1/3
1/3
20.8
5.8
14.3
3.90
3.9
380-415/50/3 11.45
5.4
4.35
10.5
66
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E2-Electrical performance (continued)
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric
Electric
Heat
Amps
Circuit
Overcur-
rent
Heat
kW
Ampacity
Protec-
tive
Device
25
25
25
25
25
35
20
30
15
15
15
15
15
15
15
15
30
30
30
30
30
40
25
35
15
20
15
20
15
15
15
15
35
35
35
40
30
45
25
25
25
25
15
15
15
15
35
40
35
45
35
45
25
25
25
25
15
20
024
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
220-240/50/1
265/60/1
265/60/1
208/60/3
208/60/3
230/60/3
230/60/3
380-415/50/3
380-415/50/3
460/60/3
460/60/3
208/60/1
208/60/1
230/60/1
230/60/1
220-240/50/1
220-240/50/1
265/60/1
265/60/1
208/60/3
208/60/3
230/60/3
230/60/3
380-415/50/3
380-415/50/3
460/60/3
460/60/3
208/60/1
208/60/1
230/60/1
230/60/1
265/60/1
265/60/1
208/60/3
208/60/3
230/60/3
230/60/3
380-415/50/3
380-415/50/3
460/60/3
460/60/3
208/60/1
208/60/1
230/60/1
230/60/1
265/60/1
265/60/1
208/60/3
208/60/3
230/60/3
230/60/3
460/60/3
460/60/3
12.7
17.5
12.7
19.2
12.4
24.03
11.4
21.53
9.3
10.8
9.3
11.8
5.0
8.45
4.9
7.65
14.2
21.5
14.2
23.5
16.4
29.97
12.4
26.43
9.5
13.2
9.5
14.4
6.6
10.8
5.0
10.90
10.9
10.90
10.9
10.90
10.9
9.90
9.9
7.50
7.5
7.50
7.5
4.00
4.0
3.90
3.9
12.40
12.4
12.40
12.4
13.60
13.6
10.90
10.9
7.70
7.7
7.70
7.7
4.90
4.9
4.00
4.0
16.00
16.0
16.00
16.0
13.60
13.6
10.40
10.4
10.40
10.4
4.80
4.8
56.0
56.0
56.0
56.0
58.0
58.0
55.0
55.0
51.0
51.0
51.0
51.0
28.0
28.0
25.0
25.0
61.0
61.0
61.0
61.0
64.0
64.0
58.0
58.0
55.0
55.0
55.0
55.0
33.0
33.0
28.0
28.0
82.0
82.0
82.0
82.0
64.0
64.0
65.5
65.5
65.5
65.5
40.0
40.0
33.0
33.0
82.0
82.0
82.0
82.0
83.0
83.0
70.0
70.0
70.0
70.0
33.0
33.0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
15.3
15.3
15.3
15.3
15.3
15.3
13.8
13.8
10.5
10.5
10.5
10.5
5.6
2.10
2.10
2.10
2.10
1.53
1.53
1.53
1.53
2.10
2.10
2.10
2.10
0.95
0.95
0.95
0.95
2.10
2.10
2.10
2.10
2.77
2.77
1.53
1.53
2.10
2.10
2.10
2.10
1.70
1.70
0.95
0.95
3.60
3.60
3.60
3.60
2.77
2.77
3.60
3.60
3.60
3.60
1.70
1.70
1.70
1.70
3.60
3.60
3.60
3.60
2.77
2.77
3.60
3.60
3.60
3.60
1.70
1.70
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/2
1/2
1/3
1/3
1/3
1/3
1/3
1/3
1/2
1/2
1/3
1/3
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
15.7
22.3
15.7
24.0
15.2
30.0
13.9
26.9
11.5
13.9
11.5
15.1
6.0
0
3.26
0
4.00
0
5.40
0
5.30
0
3.26
0
4.00
0
5.40
0
5.30
0
4.10
0
5.00
0
6.52
0
6.60
0
4.10
0
5.00
0
6.52
0
6.60
0
4.90
0
6.00
0
7.95
0
4.90
0
6.00
0
7.15
0
7.95
0
5.40
0
6.60
0
8.80
0
5.40
0
15.7
0
17.4
0
22.5
0
20.0
0
9.0
0
10.0
0
7.5
0
6.7
0
19.7
0
21.7
0
27.2
0
24.9
0
11.4
0
12.6
0
9.1
0
8.3
0
23.6
0
26.1
0
30.0
0
13.6
0
15.1
0
9.9
0
10.0
0
26.0
0
28.7
0
33.2
0
15.0
5.6
5.4
5.4
10.6
5.8
9.6
030
17.4
17.4
17.4
17.4
19.1
19.1
15.3
15.3
10.8
10.8
10.8
10.8
6.9
17.6
27.3
17.6
29.8
19.8
37.5
15.2
33.0
11.7
16.9
11.7
18.4
7.8
6.9
5.6
5.6
13.5
6.0
9.25
19.3
26.87
19.3
29.37
16.4
32.77
13.7
16.87
13.7
18.37
6.5
11.6
23.6
34.0
23.6
37.1
19.8
41.0
16.6
21.5
16.6
23.4
7.7
036
22.4
22.4
22.4
22.4
19.1
19.1
14.6
14.6
14.6
14.6
6.7
11.6
6.6
6.7
6.9
6.9
14.5
7.8
4.90
4.9
11.7
19.4
29.27
19.4
31.97
17.8
35.97
13.3
18.27
13.3
19.87
6.8
14.6
23.6
37.0
23.7
40.4
21.5
45.0
16.1
23.3
16.1
25.3
8.1
GEV 040
16.1
16.1
16.1
16.1
15.0
15.0
10.0
10.0
10.0
10.0
5.1
22.5
22.5
22.5
22.5
21.0
0.0
14.0
14.0
14.0
14.0
7.1
0
6.60
0
0
16.6
0
12.7
5.1
7.1
15.9
8.80
11.0
WSHP-SVX01D-EN
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E3-Electrical performance (continued)
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric
Electric
Heat
Amps
Circuit
Overcur-
rent
Heat
kW
Ampacity
Protective
Device
40
40
40
45
25
25
25
30
15
20
15
20
15
15
20
50
50
50
60
35
35
35
35
15
20
15
25
15
50
50
50
50
35
35
35
35
15
25
15
60
60
60
60
50
50
50
50
25
25
15
25
15
042 - Hi
Static
208/60/1
208/60/1
230/60/1
230/60/1
208/60/3
208/60/3
230/60/3
230/60/3
380-415/50/3
380-415/50/3
460/60/3
460/60/3
575/60/3
380-415/50/3
380-415/50/3
208/60/1
208/60/1
230/60/1
230/60/1
208/60/3
208/60/3
230/60/3
230/60/3
380-415/50/3
380-415/50/3
460/60/3
460/60/3
575/60/3
208/60/1
208/60/1
230/60/1
230/60/1
208/60/3
208/60/3
230/60/3
230/60/3
460/60/3
460/60/3
575/60/3
208/60/1
208/60/1
230/60/1
230/60/1
208/60/3
208/60/3
230/60/3
230/60/3
380-415/50/3
380-415/50/3
460/60/3
460/60/3
575/60/3
21.3
30.67
21.3
33.67
14.7
19.07
14.7
20.87
9.1
14.7
6.5
13.4
5.4
18.00
18.0
18.00
18.0
11.40
11.4
11.40
11.4
6.40
6.4
4.80
4.8
4.10
6.4
6.4
20.40
20.4
20.40
20.4
14.00
14.0
14.00
14.0
7.50
7.5
96.0
96.0
96.0
96.0
75.0
75.0
75.0
75.0
42.0
42.0
40.0
40.0
31.0
42.0
42.0
102.0
102.0
102.0
102.0
91.0
91.0
91.0
91.0
49.5
49.5
42.0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
25.2
25.2
25.2
25.2
16.0
16.0
16.0
16.0
8.9
8.9
6.7
6.7
5.7
3.60
3.60
3.60
3.60
3.60
3.60
3.60
3.60
2.70
2.70
1.70
1.70
1.31
1.40
1.40
5.40
5.40
5.40
5.40
5.40
5.40
5.40
5.40
2.70
2.70
2.70
2.70
2.20
2.80
2.80
2.80
2.80
2.80
2.80
2.80
2.80
1.40
1.40
1.10
5.40
5.4
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
26.1
38.8
26.1
42.5
17.9
24.3
17.9
26.5
10.7
18.4
7.7
0
5.70
0
7.00
0
5.70
0
7.00
0
8.60
0
9.30
0
0
8.60
0
6.50
0
8.00
0
6.50
0
8.00
0
8.60
0
10.60
0
0
6.50
0
8.00
0
6.50
0
8.00
0
10.60
0
0
6.50
0
8.00
0
6.50
0
8.00
0
8.60
0
0
27.4
0
30.4
0
15.8
0
17.6
0
12.0
0
11.7
0
0
12.0
0
31.3
0
34.8
0
18.0
0
20.1
0
12.0
0
13.3
0
0
31.3
0
34.8
0
18.0
0
20.1
0
13.3
0
0
31.3
0
34.8
0
18.0
0
20.1
0
12.0
0
1
1/2
1/2
1/2
1/2
1/2
1
1
1
1
1
1
1
1
1
1
1
1
1
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1
1
1
1
1
1
1
1
1
16.8
6.4
9.4
042 - Std
Static
048 - Hi
Static
7.8
8.9
8.9
13.4
25.8
36.7
25.8
40.2
19.4
23.4
19.4
25.5
10.2
14.7
9.1
16.8
30.9
45.9
30.9
50.3
22.9
29.3
22.9
31.9
12.1
18.4
10.7
20.0
8.7
28.3
42.6
28.3
47.0
20.3
26.0
20.3
28.6
9.4
28.5
28.5
28.5
28.5
19.7
19.7
19.7
19.7
10.5
10.5
8.9
6.40
6.4
16.0
7.4
42.0
39.0
8.9
7.3
5.20
20.4
20.4
20.4
20.4
14.0
14.0
14.0
14.0
6.4
048 - Std
Static
23.2
34.1
23.2
37.6
16.8
20.8
16.8
22.9
7.8
102.0
102.0
102.0
102.0
91.0
91.0
91.0
91.0
42.0
28.5
28.5
28.5
28.5
19.7
19.7
19.7
19.7
8.9
14.7
6.3
6.4
5.2
42.0
39.0
8.9
7.3
18.4
7.6
060
33.4
36.7
33.4
40.2
25.4
25.4
25.4
25.5
12.8
14.7
10.2
16.0
8.6
28.00
28.0
28.00
28.0
20.00
20.0
20.00
20.0
10.00
10.0
7.50
7.5
169.0
169.0
169.0
169.0
123.0
123.0
123.0
123.0
62.0
62.0
49.5
49.5
40.0
39.0
39.0
35.0
39.0
28.0
27.0
28.0
27.0
14.0
14.0
10.5
10.5
9.0
40.4
45.9
40.4
50.3
30.4
30.4
30.4
31.9
15.2
18.4
12.1
20.0
10.2
5.40
5.4
5.40
5.4
5.40
5.4
2.70
2.7
2.70
2.7
1
1
1
1
10.60
0
13.3
0
6.40
2.20
68
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E4-Electrical performance (continued)
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric
Electric
Heat
Amps
Circuit
Overcur-
rent
Heat
kW
Ampacity
Protective
Device
50
50
60
60
60
60
20
35
35
20
15
35
35
20
15
40
40
20
15
25
50
50
60
60
60
60
20
35
35
20
15
35
35
20
15
40
40
20
15
45
45
20
15
45
45
25
20
15
50
45
25
20
15
50
50
25
20
15
GEH 072
208/60/1
230/60/1
208/60/1
230/60/1
208/60/1
230/60/1
380-415/50/3
208/60/3
230/60/3
380-415/50/3
460/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
380-415/50/3
208/60/1
230/60/1
208/60/1
230/60/1
208/60/1
230/60/1
380-415/50/3
208/60/3
230/60/3
380-415/50/3
460/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
38.6
38.5
41.3
40.9
43.2
42.2
12.9
24.3
24.6
13.3
11.6
26.4
25.6
14.2
23.5
27.9
27.0
14.6
12.9
16.7
38.6
38.5
41.3
40.9
43.2
42.2
12.9
24.3
24.6
13.3
11.6
26.4
25.6
14.2
12.2
27.9
27.0
14.6
12.9
28.9
29.2
13.0
11.0
31.0
30.2
18.0
13.6
11.2
32.5
31.6
18.4
14.3
11.6
34.8
33.6
20.5
15.3
12.6
16.00
16.00
16.00
16.00
16.00
16.00
6.40
10.40
10.40
6.40
82.0
82.0
82.0
82.0
82.0
82.0
42.0
65.5
65.5
42.0
33.0
65.5
65.5
42.0
33.0
65.5
65.5
42.0
33.0
42.0
82.0
82.0
82.0
82.0
82.0
82.0
42.0
65.6
65.6
42.0
33.0
65.6
65.6
42.0
33.0
65.6
65.6
42.0
33.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
22.4
22.4
22.4
22.4
22.4
22.4
8.9
14.6
14.6
8.9
6.9
14.6
14.6
8.9
6.9
14.6
14.6
8.9
6.9
8.9
22.4
22.4
22.4
22.4
22.4
22.4
8.9
14.6
14.6
8.9
6.9
14.6
14.6
6.55
6.47
9.34
8.94
11.20
10.23
1.70
3.50
3.80
2.10
1.80
5.60
4.80
3.00
2.40
7.10
6.20
3.40
3.11
5.50
6.55
6.47
9.34
8.94
11.20
10.23
1.70
3.50
3.80
2.10
1.80
5.60
4.80
3.00
2.40
7.10
6.20
3.40
3.11
3.50
3.80
1.80
1.70
5.60
4.80
3.00
2.40
1.90
7.10
6.20
3.40
3.11
2.30
9.40
8.20
5.50
4.10
3.30
1
1
1.5
1.5
2
2
0.75
1
1
1
1
1.5
1.5
1.5
1.5
2
2
2
2
3
1
1
1.5
1.5
2
2
.75
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
42.6
42.5
45.3
44.9
47.2
46.2
14.5
26.9
27.2
14.9
12.8
29.0
28.2
15.8
13.4
30.5
29.6
16.2
14.1
18.3
42.6
42.5
45.3
44.9
47.2
46.2
14.5
26.9
27.2
14.9
12.8
29.0
28.2
15.8
13.4
30.5
29.6
16.2
14.1
32.4
32.7
14.6
12.3
34.5
33.7
19.9
15.2
12.5
36.0
35.1
20.3
15.9
12.9
38.3
37.1
22.4
16.9
13.9
4.90
10.40
10.40
6.40
4.90
10.40
10.40
6.40
4.90
6.40
16.00
16.00
16.00
16.00
16.00
16.00
6.40
10.40
10.40
6.40
GEV 072
1
1
4.90
10.40
10.40
6.40
1.5
1.5
1.5
1.5
2
2
2
2
1
1
1
8.9
6.9
14.6
14.6
8.9
6.9
4.90
10.40
10.40
6.40
4.90
GEH 090
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
16.0/19.7
16.0/19.7
6.7/8.9
5.2/7.3
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
5.2/7.3
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
5.2/7.3
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
5.2/7.3
1
1.5
1.5
1.5
1.5
1.5
2
2
2
2
2
3
3
3
3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
3
WSHP-SVX01D-EN
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E5-Electrical performance (continued)
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric
Electric
Heat
Amps
Circuit
Ampacity
Overcur-
rent
Protective
Device
45
Heat
kW
GEV 090
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
28.9
29.2
17.1
13.0
11.0
31.0
30.2
18.0
13.6
11.2
32.5
31.6
18.4
14.3
11.6
34.8
33.6
20.5
15.3
12.6
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
11.4/14.00 75.0/91.0
11.4/14.00 75.0/91.0
4.8/7.50 40.0/46.5
4.8/6.40 40.0/42.0
4.1/5.20 31.0/39.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
3.50
3.80
2.10
1.80
1.70
5.60
4.80
3.00
2.40
1.90
7.10
6.20
3.40
3.11
2.30
9.40
8.20
5.50
4.10
3.30
1
1
1
1
1
1.5
1.5
1.5
1.5
1.5
2
2
2
2
2
3
3
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
32.4
32.7
19.0
14.6
12.3
34.5
33.7
19.9
15.2
12.5
36.0
35.1
20.3
15.9
12.9
38.3
37.1
22.4
16.9
13.9
45
25
20
15
45
45
25
20
15
50
45
25
20
15
50
50
5.2/7.3
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
5.2/7.3
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
5.2/7.3
16.0/19.7
16.0/19.7
6.7/10.5
6.7/8.9
25
20
15
5.2/7.3
3
GEH 120 380-415/50/3
208/60/3
20.3
44.2
43.4
21.2
17.4
14.7
45.7
44.8
21.6
18.1
15.1
48.0
46.8
23.7
19.1
16.1
54.6
52.6
27.5
22.0
18.0
44.2
43.4
17.4
14.7
45.7
44.8
18.1
15.1
48.0
46.8
19.1
16.1
54.6
52.6
22.0
18.0
23
9.10
19.30
19.30
9.10
7.50
6.40
19.30
19.30
9.10
7.50
6.40
19.30
19.30
9.10
7.50
6.40
19.30
19.30
9.10
7.50
6.40
58.0
123.0
123.0
58.0
49.5
40.0
123.0
123.0
58.0
49.5
40.0
123.0
123.0
58.0
49.5
40.0
123.0
123.0
58.0
49.5
40.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
12.8
27.0
27.0
12.8
10.5
9.0
27.0
27.0
12.8
10.5
9.0
27.0
27.0
12.8
10.5
9.0
27.0
27.0
12.8
10.5
9.0
27.0
27.0
10.5
9.0
27.0
27.0
10.5
9.0
27.0
27.0
10.5
9.0
27.0
27.0
10.5
9.0
2.10
5.60
4.80
3.00
2.40
1.90
7.10
6.20
3.40
3.11
2.30
9.40
8.20
5.50
4.10
3.30
16.00
14.00
9.30
7.00
5.20
5.60
4.80
2.40
1.90
7.10
6.20
3.11
2.30
9.40
8.20
4.10
3.30
16.00
14.00
7.00
5.20
3.00
3.40
5.50
1
1.5
1.5
1.5
1.5
1.5
2
2
2
2
2
3
3
3
3
3
5
5
5
5
5
1.5
1.5
1.5
1.5
2
2
2
2
3
3
3
3
5
5
5
5
1.5
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
22.6
49.0
48.2
23.5
19.3
16.3
50.5
49.6
23.9
20.0
16.7
52.8
51.6
26.0
21.0
17.7
59.4
57.4
29.8
23.9
19.6
49.0
48.2
19.3
16.3
50.5
49.6
20.0
16.7
52.8
51.6
21.0
17.7
59.4
57.4
23.9
19.6
25.5
25.9
28.0
25
60
60
30
25
20
60
60
30
25
20
70
70
35
25
20
70
70
40
30
25
60
60
25
20
60
60
25
20
70
70
25
20
70
70
30
25
35
35
35
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
GEV 120
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
380-415/50/3
380-415/50/3
380-415/50/3
19.30
19.30
7.50
123.0
123.0
49.5
6.40
40.0
19.30
19.30
7.50
123.0
123.0
49.5
6.40
40.0
19.30
19.30
7.50
123.0
123.0
49.5
6.40
40.0
19.30
19.30
7.50
123.0
123.0
49.5
40.0
64.0
64.0
64.0
6.40
10.00
10.00
10.00
14.0
14.0
14.0
23.4
25.5
3
70
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E6-Electrical performance (continued)
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric Electric
Circuit
Overcur-
rent
Heat
kW
Heat
Ampacity
Amps
Protective
Device
60
60
40
30
25
60
60
40
30
25
70
70
40
30
25
70
70
45
35
30
60
60
35
35
25
70
70
35
35
25
70
70
35
35
30
80
80
40
30
90
80
40
30
90
90
45
35
100
100
45
35
GEH 150
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3
44.2
43.4
27.0
20.6
17.7
45.7
44.8
27.4
21.3
18.1
48.0
46.8
29.5
22.3
19.1
54.6
52.6
33.3
25.2
21.0
45.7
44.8
23
19.30
19.30
12.00
9.10
137.0
137.0
90.5
62.0
50.0
137.0
137.0
90.5
62.0
50.0
137.0
137.0
90.5
62.0
50.0
137.0
137.0
90.5
62.0
50.0
137.0
137.0
64.0
62.0
50.0
137.0
137.0
64.0
62.0
50.0
137.0
137.0
64.0
62.0
50.0
164.0
164.0
100.0
78.0
164.0
164.0
100.0
78.0
164.0
164.0
100.0
78.0
164.0
164.0
100.0
78.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
27.0
27.0
17.0
12.8
11.0
27.0
27.0
17.0
12.8
11.0
27.0
27.0
17.0
12.8
11.0
27.0
27.0
17.0
12.8
11.0
27.0
27.0
14.0
14.0
11.0
27.0
27.0
14.0
14.0
11.0
27.0
27.0
14.0
14.0
11.0
35.0
35.0
17.0
13.0
35.0
35.0
17.0
13.0
35.0
35.0
17.0
13.0
35.0
35.0
17.0
13.0
5.60
4.80
3.00
2.40
1.90
7.10
6.20
3.40
3.11
2.30
9.40
8.20
5.50
4.10
3.30
16.00
14.00
9.30
7.00
5.20
7.10
6.20
3.00
3.11
2.30
9.40
8.20
3.40
4.10
3.30
16.00
14.00
5.50
7.00
5.20
7.10
6.20
3.11
2.30
9.40
8.20
4.10
3.30
16.00
14.00
7.00
5.20
25.00
21.60
10.80
8.20
1.5
1.5
1.5
1.5
1.5
2
2
2
2
2
3
3
3
3
3
5
5
5
5
5
2
2
1.5
2
2
3
3
2
3
3
5
5
3
5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
49.0
48.2
30.0
22.9
19.7
50.5
49.6
30.4
23.6
20.1
52.8
51.6
32.5
24.6
21.1
59.4
57.4
36.3
27.5
23.0
50.5
49.6
25.5
25.6
20.0
52.8
51.6
25.9
26.6
21.0
59.4
57.4
28.0
29.5
22.9
63.4
62.5
30.1
23.2
65.7
64.5
31.1
24.2
72.3
70.3
34.0
26.1
81.3
77.9
37.8
29.1
7.90
19.30
19.30
12.00
9.10
7.90
19.30
19.30
12.00
9.10
7.90
19.30
19.30
12.00
9.10
7.90
GEV 150
19.30
19.30
10.00
10.00
7.85
19.30
19.30
10.00
10.00
7.85
19.30
19.30
10.00
10.00
7.85
25.00
25.00
12.00
9.30
25.00
25.00
12.00
9.30
25.00
25.00
12.00
9.30
25.00
25.00
12.00
9.30
23.11
18
48
46.8
23.4
24.1
19
54.6
52.6
25.5
27
20.9
57.1
56.2
27.1
20.9
59.4
58.2
28.1
21.9
66.0
64.0
31.0
23.8
75.0
71.6
34.8
26.8
5
2
2
2
2
3
3
3
3
5
5
5
GEH 180
5
7.5
7.5
7.5
7.5
WSHP-SVX01D-EN
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
E7-Electrical performance (continued)
Model No.
Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum Maximum Electric
Electric
Heat
Amps
Circuit
Overcur-
rent
Heat
kW
Ampacity
Protec-
tive
Device
90
80
40
40
30
90
90
40
45
35
100
100
45
45
35
110
110
50
50
40
125
110
60
50
40
125
125
60
50
45
150
150
70
70
50
150
150
60
GEV 180
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
59.4
58.2
27.4
28.1
21.9
66
64
29.5
31
25.00
25.00
12.00
12.00
9.30
25.00
25.00
12.00
12.00
9.30
25.00
25.00
12.00
12.00
9.30
164.0
164.0
90.5
100.0
78.0
164.0
164.0
90.5
100.0
78.0
164.0
164.0
90.5
100.0
78.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
35.0
35.0
17.0
17.0
13.0
35.0
35.0
17.0
17.0
13.0
35.0
35.0
17.0
17.0
13.0
49.5
49.5
26.0
22.0
17.5
49.5
49.5
26.0
22.0
17.5
49.5
49.5
26.0
22.0
17.5
49.5
49.5
26.0
22.0
17.5
66.0
66.0
27.5
27.5
22.2
66.0
66.0
27.5
27.5
22.2
66.0
66.0
27.5
27.5
22.2
66.0
66.0
27.5
27.5
22.2
9.40
8.20
3.40
4.10
3.30
16.00
14.00
5.50
7.00
5.20
25.00
21.60
9.30
10.80
8.20
16.00
14.00
5.50
7.00
5.20
3
3
2
3
3
5
5
3
5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
65.7
64.5
30.4
31.1
24.2
72.3
70.3
32.5
34.0
26.1
81.3
77.9
36.3
37.8
29.1
87.4
85.4
43.1
38.7
30.4
96.4
93.0
46.9
42.5
33.4
104.7
99.4
50.6
45.7
36.2
119.5
114.2
55.3
53.6
42.7
122.0
120.0
49.6
51.1
40.8
131.0
127.6
53.4
54.9
43.8
139.0
134.0
57.1
58.1
46.6
150.8
146.6
61.6
64.6
51.9
23.8
75
5
7.5
7.5
5
7.5
7.5
5
5
3
5
5
71.6
33.3
34.8
26.8
79.4
77.4
38.9
35.2
27.6
88.4
85
GEV 240
31.70
31.70
16.70
14.10
11.20
31.70
31.70
16.70
14.10
11.20
31.70
31.70
16.70
14.10
11.20
31.70
31.70
16.70
14.10
11.20
47.10
47.10
19.60
19.60
15.80
47.10
47.10
19.60
19.60
15.80
47.10
47.10
19.60
19.60
15.80
47.10
47.10
19.60
19.60
15.80
232.0
261.0
133.0
112.0
92.0
232.0
261.0
133.0
112.0
92.0
232.0
261.0
133.0
112.0
92.0
232.0
261.0
133.0
112.0
92.0
245.0
245.0
118.0
125.0
100.0
245.0
245.0
118.0
125.0
100.0
245.0
245.0
118.0
125.0
100.0
245.0
245.0
118.0
125.0
100.0
25.00
21.60
9.30
10.80
8.20
7.5
7.5
5
42.7
39
7.5
7.5
10
10
7.5
10
10
15
15
10
15
15
5
5
3
5
5
7.5
7.5
5
7.5
7.5
10
10
7.5
10
10
15
15
10
15
15
30.6
96.4
91.4
46.4
42.2
33.4
108.2
104
50.9
48.5
38.6
110.2
108.2
44.7
46.2
36.8
119.2
115.8
48.5
50
39.8
127.2
122.2
52.2
53.2
42.6
139
134.8
56.7
59.5
47.8
33.00
28.00
13.00
14.00
11.00
44.80
40.60
17.50
20.30
16.20
16.00
14.00
5.50
7.00
5.20
25.00
21.60
9.30
10.80
8.20
33.00
28.00
13.00
14.00
11.00
44.80
40.60
17.50
20.30
16.20
GEV 300
70
50
175
150
70
70
50
175
175
70
70
60
175
175
80
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
208/60/3
230/60/3
380-420/50/3
460/60/3
575/60/3
80
60
E8-Electrical minimum and maximum
E8-Electrical minimum and maximum (continued)
Digit 8
Rated
Voltage
HZ
Ph
Minimum Maximum
Utilization Utilization
Digit 8
Rated
Voltage
HZ
Ph
Minimum
Utilization
Voltage
518
Maximum
Utilization
Voltage
633
Voltage
104
Voltage
126
5
6
7
8
9
0
1
115
208
230
208
460
60
60
60
60
60
1
1
1
3
3
575
220-240
265
60
50
60
60
60
3
1
1
3
3
197
229
198
264
2
3
4
207
253
239
292
187
229
230
207
253
414
506
380-415
342
456
72
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Pre-Start
Checklist
Pre-Start-up Checklist
Before energizing the unit, the following system devices must be checked:
____ Is the high voltage power supply correct and in accordance with the nameplate ratings?
____ Is phasing of the unit correct per compressor rotation (scroll compressor only)?
____ Is the field wiring and circuit protection the correct size?
____ Is the low voltage control circuit wiring correct per the unit wiring diagram?
____ Is the piping system clean/complete and correct?(A recommendation of all system flushing of debris from the water-
to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger be done in accor-
dance with the Closed-Loop/Ground Source Heat Pump Systems Installation Guide).
____ Is vibration isolation provided? (i.e. unit isolation pad, hosekits)
____ Is unit serviceable? (See clearance specifications on pages 8 and 9).
____ Are the low/high-side pressure temperature caps secure and in place?
____ Are all the unit access panels secure and in place?
____ Is the thermostat in the OFF position?
____ Is the water flow established and circulating through all the units?
____ Is the duct work correctly sized, run, taped, insulated and weather proofed with proper unit arrangement?
____ Is the condensate line properly sized, run, trapped, pitched and primed?
____ Is the zone sensor correctly wired and in a good location?
____ Does the indoor blower turn freely without rubbing?
____ Has all work been done in accordance with applicable local and national codes?
____ Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?
WSHP-SVX01D-EN
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Sequence
of Operation
Initial Unit Start-up
Note: Start-up for the Terminal Unit Controller (TUC) may be found in WSHP-IOP-1. Start-up for the Tracer ZN510 controller may
be found in WSHP-IOP-2. Start-up for the Tracer ZN524 controller may be found in WSHP-PRB002-EN.
Start-up with the conventional thermostat is included below:
1.Set the thermostat to the highest position.
2.Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
3.Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized.
Adjust water flow utilizing pressure/temperature plugs and comparing to tables contained in specification sheet data.
Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9-12ºF);
blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction
line should be cool with no frost observed in the refrigerant circuit.
4.Check the cooling refrigerant pressures against values in Table 7. (Page 75).
5.Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-
energize.
6.Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7.Turn the thermostat to the lowest setting.
8.Set the thermostat system switch to the HEAT position.
9.Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water
temperature decrease of approximately 5-9ºF leaving the heat exchanger should be noted. The blower and
compressor operation should be smooth with no frost observed in the refrigeration circuit.
10.Check the heating refrigerant pressures against values in Table 7. (Page 75)
11.Set the thermostat to maintain the desired space temperature.
12.Instruct the owner on system operation.
74
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Pressures
Operating Pressures
GENERAL: There are many variables (airflow, air temperatures) in an air conditioning system that will affect operating refrigerant pressures and
temperatures. The charts below shows approximate conditions and is based on air flow at the rated SCFM, entering air at 80.6 °F(DB), 66.2 °F(WB)
in cooling, 68 °F(DB) in heating. (+)Heating data with 35 °F EWT is based on the use of an anti-freeze solution having a freezing point 20 °F lower
than the minimum expected entering temperature.
Table 7: Operating pressures in cooling/heating
Operating Data
Model
GEH/GEV
Entering
Water Temp,
°F
Water
Flow
GPM
Cooling
Suction Pres- Discharge
Heating
Water
Air Temp
Drop
°F DB
Suction
Pressure
PSIG
42 - 48
Discharge
Water Temp
Air Temp
Rise
°F DB
23 - 29
23 - 29
sure,
PSIG
Pressure,
PSIG
Temp Rise
°F
Pressure
Drop
°F
6 - 7
5 - 6
PSIG
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
165 - 210
168 - 214
006 (60 HZ)
45 - 52
68 - 78
68 - 78
68 - 79
68 - 78
71 - 82
70 - 81
73 - 84
72 - 83
75 - 86
74 - 85
76 - 87
75 - 86
143 - 182
134 - 170
139 - 177
129 - 164
153 - 195
144 - 183
172 - 219
163 - 207
206 - 262
196 - 250
231 - 294
222 - 282
14 - 18
11 - 14
13 - 17
11 - 14
13 - 16
10 - 13
13 - 16
10 - 13
12 - 16
10 - 13
12 - 16
10 - 13
24 - 30
24 - 31
23 - 30
24 - 30
23 - 29
23 - 29
23 - 29
23 - 29
22 - 28
23 - 29
22 - 28
22 - 28
52 - 60
56 - 64
63 - 73
67 - 77
78 - 90
82 - 94
85 - 98
89 - 103
95 - 109
99 - 114
176 - 224
180 - 229
189 - 241
193 - 246
206 - 262
210 - 268
214 - 272
219 - 279
225 - 287
231 - 294
7 - 9
6 - 7
8 - 10
7 - 8
10 - 12
8 - 10
10 - 13
8 - 11
11 - 14
9 - 12
26 - 34
27 - 34
30 - 39
31 - 39
35 - 45
36 - 45
38 - 48
38 - 48
41 - 52
41 - 52
44 - 50
45 - 51
52 - 60
54 - 62
63 - 72
65 - 75
78 - 89
80 - 92
85 - 98
87 - 100
96 - 110
97 - 112
163 - 208
166 - 211
174 - 221
176 - 224
186 - 236
188 - 239
201 - 256
204 - 259
211 - 268
213 - 271
221 - 281
223 - 284
5 - 7
4 - 5
6 - 8
5 - 7
7 - 9
6 - 8
9 - 11
7 - 9
9 - 12
8 - 10
10 - 13
9 - 11
21 - 26
21 - 27
24 - 30
24 - 31
27 - 34
28 - 35
31 - 40
32 - 40
33 - 42
34 - 43
36 - 46
37 - 47
009 (60 HZ)
006 (50 HZ)
69 - 79
69 - 79
71 - 81
70 - 81
72 - 83
72 - 83
73 - 84
73 - 84
75 - 86
74 - 86
76 - 88
76 - 87
134 - 171
131 - 167
137 - 174
132 - 168
157 - 199
151 - 192
173 - 221
167 - 212
205 - 261
198 - 252
235 - 299
228 - 290
13 - 16
10 - 13
12 - 16
10 - 13
12 - 15
10 - 12
12 - 15
10 - 12
11 - 15
9 - 12
21 - 27
21 - 27
20 - 26
20 - 26
20 - 25
20 - 25
19 - 24
19 - 25
19 - 24
19 - 24
18 - 23
18 - 23
11 - 14
9 - 12
012 (60 HZ)
009 (50 HZ)
42 - 48
43 - 50
52 - 59
53 - 61
58 - 66
59 - 68
63 - 72
64 - 74
67 - 77
68 - 79
71 - 81
72 - 83
159 - 202
161 - 205
170 - 216
172 - 218
178 - 227
180 - 229
184 - 234
186 - 237
187 - 238
189 - 240
194 - 247
196 - 249
5 - 7
4 - 6
6 - 8
5 - 7
7 - 9
6 - 7
8 - 10
6 - 8
9 - 11
7 - 9
9 - 12
7 - 9
21 - 27
21 - 27
24 - 30
24 - 31
26 - 33
27 - 34
29 - 37
29 - 37
30 - 38
30 - 39
32 - 40
32 - 41
68 - 78
68 - 79
69 - 80
70 - 80
71 - 82
71 - 82
72 - 83
72 - 83
74 - 85
74 - 85
75 - 86
75 - 86
149 - 190
144 - 184
133 - 169
128 - 163
158 - 201
153 - 195
175 - 223
170 - 217
204 - 259
199 - 253
235 - 299
230 - 293
14 - 18
11 - 14
13 - 17
10 - 13
13 - 16
10 - 13
13 - 16
10 - 13
13 - 16
10 - 13
12 - 16
10 - 12
22 - 28
23 - 29
21 - 27
22 - 27
21 - 26
21 - 26
20 - 26
20 - 26
19 - 25
20 - 25
19 - 24
19 - 24
015 (60 HZ)
012 (50 HZ)
43 - 49
44 - 51
52 - 60
54 - 62
62 - 72
64 - 73
74 - 85
75 - 87
79 - 91
80 - 92
83 - 96
84 - 97
166 - 211
167 - 213
179 - 227
180 - 230
191 - 244
193 - 246
207 - 264
209 - 266
214 - 272
216 - 275
215 - 274
217 - 276
5 - 6
4 - 5
6 - 8
5 - 6
7 - 9
6 - 8
8 - 11
7 - 9
9 - 11
7 - 9
10 - 12
8 - 10
20 - 26
21 - 26
23 - 30
24 - 30
27 - 34
27 - 35
31 - 39
31 - 39
32 - 41
33 - 41
34 - 43
34 - 43
69 - 79
68 - 79
70 - 80
69 - 80
71 - 82
71 - 82
72 - 83
72 - 83
74 - 85
73 - 84
75 - 86
75 - 86
117 - 149
112 - 143
127 - 162
123 - 156
151 - 192
147 - 187
168 - 213
164 - 208
199 - 254
194 - 247
228 - 291
222 - 283
12 - 16
10 - 13
12 - 15
10 - 12
12 - 15
9 - 12
11 - 15
9 - 12
11 - 14
9 - 11
21 - 27
21 - 27
21 - 26
20 - 26
20 - 25
20 - 25
19 - 25
19 - 25
19 - 24
19 - 24
18 - 23
18 - 23
11 - 14
9 - 11
WSHP-SVX01D-EN
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Pressures
Operating Data
Cooling
Model
GEH/GEV
Entering
Water Temp,
°F
Water
Flow
GPM
Heating
Discharge Water Temp
Suction Pres- Discharge
Water
Temp Rise
°F
Air Temp
Drop
°F DB
Suction
Pressure
PSIG
Air Temp
Rise
°F DB
sure,
PSIG
Pressure,
PSIG
Pressure
Drop
PSIG
°F
018 (60 HZ)
015 (50 HZ)
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
4.4
5.5
4.4
5.5
4.4
5.5
4.4
5.5
4.4
5.5
4.4
5.5
4.4
5.5
5.5
6.9
5.5
6.9
5.5
6.9
5.5
6.9
5.5
6.9
5.5
6.9
5.5
6.9
6.6
8.3
6.6
8.3
6.6
8.3
6.6
8.3
6.6
8.3
6.6
8.3
6.6
8.3
7.4
9.2
7.4
9.2
7.4
9.2
7.4
9.2
7.4
9.2
7.4
9.2
7.4
9.2
39 - 45
40 - 46
47 - 55
49 - 56
56 - 65
58 - 67
68 - 78
70 - 80
74 - 85
76 - 87
83 - 96
85 - 98
155 - 197
156 - 198
164 - 209
165 - 211
174 - 222
176 - 224
188 - 239
189 - 241
195 - 248
197 - 251
207 - 263
209 - 266
5 - 7
4 - 5
6 - 8
5 - 6
7 - 9
6 - 8
9 - 11
7 - 9
10 - 12
8 - 10
10 - 13
8 - 11
21 - 26
21 - 27
24 - 30
24 - 31
27 - 34
27 - 35
31 - 39
32 - 40
33 - 42
34 - 43
36 - 46
37 - 47
70 - 81
70 - 80
72 - 83
72 - 82
74 - 85
74 - 85
75 - 87
75 - 86
77 - 88
76 - 88
78 - 89
77 - 89
110 - 141
107 - 136
132 - 167
127 - 162
149 - 190
144 - 183
164 - 209
159 - 202
195 - 248
189 - 240
223 - 284
217 - 276
14 - 18
11 - 14
14 - 18
11 - 14
13 - 17
10 - 13
13 - 16
10 - 13
13 - 16
10 - 13
13 - 16
10 - 13
23 - 29
23 - 29
23 - 29
23 - 29
22 - 28
22 - 28
21 - 27
21 - 27
20 - 26
20 - 26
19 - 24
19 - 25
024 (60 HZ)
018 (50 HZ)
42 - 48
43 - 49
50 - 58
52 - 59
59 - 68
61 - 70
70 - 81
72 - 82
75 - 87
77 - 88
82 - 95
84 - 97
163 - 207
164 - 209
175 - 223
177 - 225
188 - 239
190 - 242
204 - 259
206 - 263
211 - 269
214 - 272
220 - 281
223 - 284
6 - 7
5 - 6
7 - 9
6 - 7
8 - 10
7 - 8
9 - 12
8 - 10
10 - 13
8 - 10
11 - 14
9 - 11
21 - 27
22 - 28
25 - 32
26 - 32
29 - 36
29 - 37
33 - 42
33 - 42
35 - 44
35 - 45
37 - 47
38 - 48
67 - 77
66 - 76
69 - 79
68 - 79
72 - 82
71 - 82
73 - 84
73 - 83
75 - 86
74 - 86
77 - 88
76 - 87
125 - 160
120 - 153
137 - 174
131 - 166
163 - 207
155 - 198
181 - 231
174 - 221
215 - 274
207 - 263
246 - 313
238 - 302
15 - 18
12 - 15
14 - 18
12 - 15
14 - 17
11 - 14
14 - 17
11 - 14
13 - 17
10 - 13
13 - 16
10 - 13
23 - 30
23 - 30
22 - 28
22 - 29
21 - 27
22 - 28
21 - 27
21 - 27
20 - 26
20 - 26
19 - 25
20 - 25
030 (60 HZ)
024 (50 HZ)
42 - 48
43 - 50
51 - 58
52 - 59
59 - 68
60 - 69
69 - 80
71 - 81
74 - 86
76 - 87
81 - 93
82 - 95
161 - 205
163 - 207
172 - 219
174 - 221
185 - 235
187 - 238
199 - 254
201 - 256
206 - 262
208 - 264
217 - 277
219 - 279
5 - 6
4 - 5
6 - 8
5 - 6
7 - 9
6 - 7
8 - 10
7 - 8
9 - 11
7 - 9
9 - 12
8 - 10
20 - 25
20 - 26
23 - 29
23 - 30
26 - 33
27 - 34
30 - 38
30 - 39
32 - 40
32 - 41
34 - 43
34 - 44
67 - 77
67 - 77
68 - 78
67 - 77
71 - 82
71 - 82
73 - 84
73 - 83
75 - 86
74 - 86
76 - 88
76 - 87
118 - 151
115 - 146
129 - 165
126 - 160
154 - 196
150 - 191
171 - 217
166 - 212
201 - 256
196 - 250
229 - 292
224 - 285
13 - 16
10 - 13
12 - 16
10 - 13
12 - 15
10 - 12
12 - 15
10 - 12
12 - 15
9 - 12
22 - 28
22 - 27
21 - 27
21 - 27
20 - 26
21 - 26
20 - 25
20 - 26
19 - 25
20 - 25
19 - 24
19 - 24
11 - 14
9 - 11
036 (60 HZ)
030 (50 HZ)
39 - 45
41 - 47
49 - 57
51 - 58
59 - 68
60 - 69
72 - 83
74 - 85
78 - 90
80 - 93
88 - 101
91 - 104
155 - 198
158 - 201
169 - 215
170 - 217
181 - 230
183 - 233
197 - 251
200 - 254
206 - 262
209 - 266
218 - 278
222 - 282
5 - 6
4 - 5
6 - 8
5 - 6
7 - 9
6 - 8
9 - 11
7 - 9
10 - 12
8 - 10
10 - 13
8 - 11
19 - 24
19 - 24
23 - 29
23 - 29
26 - 33
26 - 34
30 - 39
31 - 39
33 - 42
33 - 42
35 - 45
36 - 45
66 - 77
66 - 76
69 - 79
69 - 79
71 - 82
71 - 82
73 - 84
73 - 84
75 - 86
74 - 86
76 - 88
76 - 88
118 - 150
113 - 144
132 - 168
126 - 161
156 - 199
151 - 192
173 - 220
167 - 212
202 - 257
195 - 248
228 - 290
221 - 282
13 - 16
10 - 13
12 - 16
10 - 13
12 - 16
10 - 13
12 - 15
10 - 12
12 - 15
10 - 12
12 - 15
10 - 12
21 - 26
21 - 26
20 - 26
21 - 26
20 - 25
20 - 26
20 - 25
20 - 26
20 - 25
20 - 26
20 - 25
20 - 26
040 (60 HZ)
39 - 45
40 - 46
48 - 56
50 - 58
57 -65
59 - 67
69 - 79
71 - 81
76 - 88
78 - 90
83 - 95
85 - 97
167 - 213
168 -214
180 - 230
181 - 231
194 - 246
195 - 249
211 - 269
213 - 271
221 - 281
223 - 283
234 - 298
236 - 300
5 - 6
4 - 5
6 - 7
5 - 6
7 - 8
5 - 7
8 -10
6 - 8
9 - 11
7 - 9
19 - 25
20 - 25
23 - 29
23 - 29
26 - 33
26 - 33
30 - 38
30 - 39
32 - 41
33 - 42
35 - 44
35 - 45
63 - 73
62 - 72
66 - 76
66 - 76
69 - 79
69 - 79
71 - 81
71 - 81
73 - 83
73 - 83
74 - 86
74 - 86
119 - 151
115 - 147
133 - 169
128 - 164
157 - 199
151 - 193
172 - 218
166 - 212
200 - 254
193 - 245
225 - 287
217 - 277
13 - 16
10 - 13
13 - 16
10 - 13
12 - 16
10 - 12
12 - 15
10 - 12
12 - 15
9 - 12
21 - 27
21 - 27
21 - 27
21 - 27
21 - 26
21 - 26
20 - 26
20 - 26
20 - 25
20 - 25
19 - 24
19 - 24
9 - 12
8 - 10
11 - 14
9 - 12
76
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Pressures
Operating Data
Cooling
Model
GEH/GEV
Entering
Water Temp,
°F
Water
Flow
GPM
Heating
Discharge Water Temp
Suction Pres- Discharge
Water
Temp Rise
°F
Air Temp
Drop
°F DB
Suction
Pressure
PSIG
Air Temp
Rise
°F DB
sure,
PSIG
Pressure,
PSIG
Pressure
PSIG
Drop
°F
042 (60 HZ)
036 (50 HZ)
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
35°
45°
55°
68°
75°
86°
95°
7.8
9.7
7.8
9.7
7.8
9.7
7.8
9.7
7.8
9.7
7.8
9.7
7.8
9.7
8.8
11
8.8
11
8.8
11
8.8
11
8.8
11
8.8
38 - 44
40 - 46
47 - 54
48 - 55
55 - 64
57 - 66
68 - 78
69 - 80
74 - 85
76 - 87
83 - 95
84 - 97
163 - 207
165 - 210
176 - 225
178 - 227
192 - 245
194 - 247
213 - 271
215 - 273
223 - 283
225 - 286
236 - 301
238 - 303
5 - 6
4 - 5
6 - 7
5 - 6
7 - 9
6 - 7
8 - 10
7 - 8
9 - 11
7 - 9
10 - 12
8 - 10
19 - 24
19 - 25
22 - 28
22 - 29
25 - 32
26 - 32
29 - 37
30 - 38
32 - 40
32 - 41
34 - 43
34 - 44
66 - 76
66 - 75
67 - 77
66 - 76
70 - 81
70 - 80
72 - 82
71 - 82
73 - 85
73 - 84
75 - 86
75 - 86
122 - 155
118 - 150
133 - 170
129 - 164
156 - 199
151 - 192
172 - 219
166 - 212
200 - 255
194 - 248
227 - 289
220 - 280
13 - 16
10 - 13
13 - 16
10 - 13
12 - 15
10 - 12
12 - 15
10 - 12
12 - 15
9 - 12
21 - 27
21 - 27
21 - 27
21 - 27
21 - 26
21 - 26
20 - 26
20 - 26
19 - 25
19 - 25
19 - 24
19 - 24
11 - 14
9 - 12
048 (60 HZ)
042 (50 HZ)
40 - 46
41 - 47
49 - 56
50 - 57
57 - 66
59 - 67
69 - 79
70 - 81
73 - 84
74 - 85
77 - 89
78 - 90
155 - 197
156 - 199
165 - 209
166 - 211
175 - 223
177 - 225
189 - 241
191 - 243
195 - 249
197 - 250
201 - 256
202 - 257
5 - 6
4 - 5
6 - 8
5 - 6
7 - 9
6 - 7
8 - 11
7 - 9
9 - 11
7 - 9
9 - 12
8 - 10
20 - 25
20 - 26
23 - 29
23 - 30
26 - 33
27 - 34
30 - 38
31 - 39
32 - 40
32 - 41
33 - 42
34 - 43
66 - 77
66 - 76
69 - 79
68 - 79
72 - 82
71 - 82
73 - 84
72 - 83
74 - 85
74 - 85
76 - 87
75 - 86
117 - 149
113 - 144
132 - 168
127 - 162
156 - 199
150 - 192
172 - 219
166 - 211
200 - 255
193 - 246
226 - 288
219 - 279
14 - 17
11 - 14
13 - 17
11 - 14
13 - 17
10 - 13
13 - 16
10 - 13
12 - 16
10 - 13
12 - 15
10 - 12
21 - 27
22 - 28
21 - 27
21 - 27
20 - 26
21 - 26
20 - 25
20 - 26
19 - 25
19 - 25
19 - 24
19 - 24
11
8.8
11
060 (60 HZ)
048 (50 HZ)
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
11.6
14.5
40 - 46
41 - 47
48 - 55
49 - 57
58 - 67
59 - 68
70 - 81
72 - 82
76 - 88
78 - 90
85 - 98
87 - 100
164 - 209
166 - 211
175 - 223
177 - 225
187 - 238
188 - 240
202 - 257
203 - 259
209 - 266
211 - 269
220 - 280
222 - 282
5 - 6
4 - 5
6 - 8
5 - 6
7 - 9
6 - 7
8 - 11
7 - 9
9 - 12
7 - 9
21 - 27
21 - 27
24 - 31
24 - 31
27 - 35
28 - 35
31 - 40
32 - 40
33 - 42
34 - 43
36 - 45
36 - 46
64 - 74
64 - 74
67 - 77
67 - 77
70 - 80
69 - 80
70 - 81
70 - 81
71 - 82
71 - 82
72 - 83
72 - 83
111 - 142
108 - 138
127 - 162
123 - 156
152 - 194
147 - 187
168 - 214
163 - 207
197 - 250
190 - 242
223 - 283
216 - 274
12 - 15
9 - 12
12 - 15
9 - 12
12 - 15
9 - 12
12 - 15
9 - 12
11 - 14
9 - 12
11 - 14
9 - 11
21 - 27
21 - 26
20 - 26
21 - 26
20 - 26
20 - 26
20 - 25
20 - 26
20 - 25
20 - 25
19 - 24
19 - 25
10 - 13
8 - 10
060 (50 HZ)
36 - 41
37 - 42
44 - 51
45 - 52
54 - 62
55 - 64
66 - 76
68 - 78
72 - 83
74 - 85
81 - 93
83 - 95
151 - 192
152 - 193
161 - 206
163 - 207
173 - 220
175 - 222
188 - 239
190 - 242
196 - 249
197 - 251
2069 - 263
208 - 265
4 - 5
3 - 4
5 - 7
4 - 6
6 - 8
5 - 6
7 - 9
6 - 8
8 - 10
7 - 8
9 - 11
7 - 9
17 - 22
17 - 22
21 - 26
21 - 27
23 - 30
24 - 30
27 - 34
27 - 35
29 - 37
29 - 37
31 - 39
31 - 39
67 - 77
67 - 77
70 - 81
70 - 80
72 - 83
72 - 83
73 - 84
73 - 84
74 - 85
74 - 85
75 - 86
75 - 86
114 - 145
111 - 141
129 - 165
125 - 159
155 - 197
149 - 190
171 - 217
165 - 210
199 - 253
193 - 245
225 - 286
218 - 277
11 - 14
9 - 11
11 - 14
9 - 11
11 - 14
9 - 11
11 - 14
9 - 11
11 - 14
9 - 11
11 - 13
8 - 11
20 - 26
20 - 26
20 - 25
20 - 25
20 - 25
20 - 25
19 - 25
20 - 25
19 - 24
19 - 24
19 - 24
19 - 24
WSHP-SVX01D-EN
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Pressures
Operating Data
Cooling
Model
GEH/GEV Water Temp,
Entering
Water
Flow
GPM
Heating
Discharge Water Temp
Suction Pres- Discharge
Water
Temp Rise
°F
Air Temp
Drop
°F DB
Suction
Pressure
Air Temp
Rise
sure,
PSIG
Pressure,
PSIG
Pressure
Drop
°F
PSIG
26 - 33
27 - 34
36 - 46
37 - 48
47 - 60
49 - 62
63 - 80
66 - 84
71 - 90
76 - 97
84 - 107
91 - 116
PSIG
°F
5 - 7
3 - 4
7 - 8
4 - 6
8 - 10
5 - 7
9 - 12
6 - 8
10 - 12
7 - 8
11 - 14
7 - 9
°F DB
14 - 18
14 - 19
18 - 23
19 - 24
22 - 29
23 - 29
28 - 36
29 - 37
31 - 39
32 - 41
35 - 44
37 - 47
072 (60 HZ)
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
12
18
12
18
12
18
12
18
12
18
12
18
12
139 - 177
140 - 179
152 - 193
153 - 195
165 - 210
168 - 213
184 - 235
188 - 239
194 - 246
200 - 254
209 - 266
217 - 276
69 - 79
68 - 78
70 - 80
69 - 79
71 - 82
70 - 81
72 - 83
71 - 82
74 - 85
73 - 84
76 - 88
75 - 86
107 - 136
98 - 125
14 - 18
9 - 12
14 - 18
9 - 12
13 - 17
9 - 11
13 - 17
9 - 11
13 - 16
8 - 11
12 - 16
8 - 10
21 - 26
21 - 27
20 - 26
20 - 26
19 - 25
20 - 25
19 - 24
19 - 25
18 - 24
19 - 24
18 - 23
18 - 23
127 - 162
118 - 150
156 - 199
145 - 185
173 - 220
161 - 205
202 - 257
188 - 240
228 - 290
213 - 271
18
090 (60 HZ)
072 (50 HZ)
15.0
22.5
15.0
22.5
15.0
22.5
15.0
22.5
15.0
22.5
15.0
22.5
15.0
22.5
20
30
20
30
20
30
20
30
20
26 - 45
27 - 46
36 - 55
37 - 57
47 - 66
49 - 69
63 - 83
66 - 87
71 - 93
76 - 97
84 - 110
91 - 116
0 - 0
139 - 204
140 - 206
152 - 217
153 - 219
165 - 231
168 - 234
184 - 250
188 - 254
194 - 262
200 - 266
209 - 281
217 - 286
0 - 0
5 - 6
3 - 4
6 - 8
4 - 6
7 - 9
5 - 6
9 - 11
6 - 8
9 - 12
6 - 8
10 - 13
7 - 9
83 - 106
83 - 106
5 - 6
3 - 4
6 - 8
4 - 6
8 - 10
5 - 7
16 - 21
17 - 22
20 - 25
20 - 26
23 - 30
24 - 31
28 - 36
29 - 37
31 - 39
32 - 41
34 - 44
36 - 46
-60 - -77
-60 - -77
19 - 24
19 - 25
22 - 28
22 - 28
24 - 31
25 - 32
28 - 36
29 - 37
31 - 39
31 - 40
34 - 44
35 - 45
69 - 80
68 - 80
70 - 80
69 - 80
71 - 82
70 - 82
72 - 83
71 - 82
73 - 85
73 - 84
74 - 88
74 - 86
0 - 0
107 - 148
98 - 135
14 - 18
9 - 12
13 - 17
9 - 11
13 - 17
9 - 11
13 - 17
9 - 11
13 - 16
8 - 11
12 - 16
8 - 10
-31 - -40
-31 - -40
13 - 17
9 - 11
13 - 17
9 - 11
13 - 17
9 - 11
13 - 17
8 - 11
13 - 17
8 - 11
13 - 16
8 - 11
20 - 26
20 - 26
20 - 25
20 - 25
19 - 24
19 - 25
19 - 24
19 - 24
18 - 23
18 - 24
18 - 23
18 - 23
70 - 90
70 - 90
19 - 25
19 - 25
19 - 25
19 - 25
19 - 24
19 - 24
19 - 24
19 - 24
18 - 23
18 - 23
18 - 23
18 - 23
127 - 173
118 - 160
156 - 213
145 - 196
173 - 235
161 - 216
202 - 274
188 - 253
228 - 310
213 - 285
0 - 0
0 - 0
0 - 0
120 (60 HZ)
090(50 HZ)
35 - 45
36 - 46
43 - 55
45 - 57
52 - 66
54 - 69
65 - 83
68 - 87
73 - 93
76 - 97
87 - 110
91 - 115
161 - 204
162 - 206
170 - 217
172 - 219
181 - 231
183 - 234
196 - 250
200 - 254
205 - 262
209 - 266
220 - 281
225 - 286
0 - 0
0 - 0
70 - 80
70 - 80
70 - 80
70 - 80
71 - 82
71 - 82
72 - 83
71 - 82
73 - 84
73 - 84
74 - 85
74 - 85
116 - 148
106 - 135
136 - 173
126 - 160
167 - 213
154 - 196
185 - 235
170 - 216
215 - 274
199 - 253
244 - 310
224 - 285
9 - 11
6 - 8
9 - 12
6 - 8
11 - 14
7 - 9
30
20
30
20
30
78
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Pressures
Operating Data
Cooling
Model
Entering
Water
Flow
GPM
Heating
Suction
Pressure,
PSIG
Discharge
Pressure,
PSIG
Water
Temp Rise
°F
Air Temp
Drop
°F DB
Suction
Pressure
PSIG
Discharge
Water Temp
Air Temp
Rise
GEH/GEV Water Temp,
Pressure
Drop
°F
5 - 8
3 - 5
7 - 9
4 - 6
8 - 11
5 - 8
9 - 13
°F
PSIG
°F DB
17 - 23
18 - 24
20 - 26
20 - 26
22 - 29
23 - 31
26 - 34
27 - 36
28 - 37
30 - 39
31 - 41
33 - 43
150 (60 HZ)
120 (50 HZ)
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
25.0
37.5
25.0
37.5
25.0
37.5
25.0
37.5
25.0
37.5
25.0
37.5
25.0
37.5
30
45
30
45
30
45
30
45
30
45
30
45
30
45
40
60
40
60
40
60
40
60
40
60
40
60
40
60
50
75
50
75
50
75
50
75
50
75
50
75
50
34 - 44
36 - 46
42 - 54
42 - 55
51 - 65
54 - 70
64 - 82
68 - 88
71 - 92
77 - 99
85 - 109
92 - 118
151 - 193
153 - 196
160 - 204
161 - 205
169 - 216
172 - 220
182 - 232
186 - 238
189 - 242
194 - 248
201 - 257
208 - 266
69 - 80
69 - 80
69 - 80
69 - 80
70 - 81
70 - 81
71 - 82
71 - 82
72 - 84
72 - 84
73 - 85
73 - 85
100 - 128
96 - 123
12 - 16
8 - 11
18 - 25
18 - 25
18 - 24
18 - 24
18 - 24
18 - 24
18 - 24
18 - 24
17 - 23
18 - 23
17 - 23
17 - 23
120 - 153
115 - 147
148 - 189
142 - 182
164 - 210
158 - 202
192 - 246
185 - 237
218 - 278
210 - 268
12 - 16
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
11 - 16
7 - 11
7 - 9
10 - 14
7 - 10
12 - 16
8 - 12
180 (60 HZ)
150 (50 HZ)
30 - 40
32 - 42
38 - 49
40 - 53
46 - 59
50 - 64
58 - 75
63 - 81
65 - 84
71 - 92
78 - 100
85 - 109
147 - 189
150 - 192
156 - 199
159 - 203
165 - 211
169 - 216
178 - 227
183 - 234
185 - 237
191 - 245
198 - 253
206 - 263
5 - 8
3 - 5
6 - 9
4 - 7
8 - 11
5 - 8
9 - 13
6 - 9
10 - 14
7 - 10
12 - 16
8 - 12
17 - 23
18 - 24
20 - 26
21 - 27
23 - 30
24 - 31
26 - 35
28 - 37
29 - 37
30 - 40
32 - 42
34 - 44
66 - 77
66 - 77
66 - 77
66 - 77
68 - 79
67 - 78
68 - 80
68 - 79
70 - 81
69 - 81
71 - 82
70 - 82
106 - 136
102 - 131
126 - 161
120 - 153
154 - 196
147 - 187
170 - 217
162 - 208
199 - 254
190 - 243
224 - 287
215 - 274
12 - 17
8 - 11
12 - 17
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
18 - 25
18 - 25
18 - 24
18 - 24
18 - 24
18 - 24
18 - 24
18 - 24
17 - 23
17 - 23
17 - 23
17 - 23
GEV
240 (60 HZ)
180 (50 HZ)
31 - 40
32 - 42
37 - 48
40 - 51
45 - 58
48 - 61
55 - 72
59 - 76
62 - 80
66 - 85
72 - 93
77 - 99
157 - 201
160 - 204
166 - 212
168 - 215
174 - 223
177 - 227
186 - 238
190 - 243
193 - 247
198 - 252
205 - 261
210 - 268
5 - 8
3 - 5
7 - 10
4 - 7
8 - 11
5 - 8
9 - 12
6 - 9
10 - 13
7 - 10
11 - 15
8 - 11
19 - 25
20 - 26
21 - 28
22 - 29
23 - 31
24 - 32
27 - 35
28 - 36
28 - 37
30 - 39
31 - 41
33 - 43
65 - 76
65 - 76
66 - 77
65 - 76
67 - 78
67 - 77
67 - 79
67 - 78
69 - 80
68 - 80
70 - 81
69 - 81
113 - 145
109 - 140
134 - 171
125 - 160
163 - 209
152 - 195
180 - 231
169 - 215
210 - 269
197 - 251
238 - 303
222 - 284
13 - 18
9 - 12
13 - 18
9 - 12
13 - 18
9 - 12
13 - 18
9 - 12
13 - 18
9 - 12
13 - 18
9 - 12
19 - 25
19 - 25
19 - 25
19 - 25
18 - 25
19 - 25
18 - 24
18 - 24
18 - 24
18 - 24
18 - 23
18 - 24
GEV
300 (60 HZ)
240 (50 HZ)
27 - 36
30 - 39
35 - 45
37 - 49
43 - 55
46 - 60
55 - 71
60 - 77
62 - 80
68 - 87
74 - 95
81 - 104
162 - 207
165 - 211
171 - 219
175 - 224
181 - 232
186 - 237
195 - 249
201 - 257
203 - 260
210 - 268
216 - 277
224 - 287
5 - 7
3 - 5
6 - 9
4 - 6
7 - 10
5 - 7
9 - 12
6 - 9
10 - 13
7 - 10
11 - 15
8 - 11
18 - 24
19 - 25
20 - 27
21 - 28
23 - 30
24 - 31
26 - 34
27 - 36
28 - 37
29 - 39
31 - 40
33 - 43
64 - 74
64 - 74
65 - 76
66 - 77
66 - 77
67 - 78
67 - 78
68 - 79
68 - 79
69 - 81
69 - 81
69 - 80
115 - 148
111 - 142
134 - 171
128 - 164
160 - 205
154 - 197
176 - 225
169 - 216
203 - 260
196 - 250
228 - 292
220 - 281
13 - 17
8 - 12
12 - 17
8 - 12
12 - 16
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
12 - 16
8 - 11
18 - 24
18 - 24
18 - 24
18 - 24
18 - 23
18 - 23
17 - 23
17 - 23
17 - 23
17 - 23
17 - 22
17 - 22
75
WSHP-SVX01D-EN
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation Pressures
Water Pressure Drop
Tables 8 and 9 should be used to define feet of head/pressure drop. Please note the feet of pressure (ft/head) provided is at ARI/ISO stan-
dard. Note: To calculate feet of head, when using gauges that read in PSIG,multiply PSI by 2.31.
Table 9: Heating water pressure drops (WPD) in feet of head
Table 8: Cooling water pressure drops (WPD) in feet of head
Unit Size
60 HZ
006
Unit Size
50 HZ
-
EWT
F
Unit Size
60 HZ
006
Unit Size
50 HZ
-
EWT
F
Ft.
Pressure
2.5
4.2
7.6
6.5
6.9
6.9
12.6
8.7
GPM
GPM
Ft. Pressure
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
86
1.5
2.1
2.8
3.5
4.2
5.5
6.9
8.3
9.2
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
86
86
86
86
86
86
86
1.5
2.1
2.8
3.5
4.2
5.5
6.9
8.3
9.2
2.7
4.7
8.3
7.2
7.6
8.1
14.5
9.9
12.5
14.0
9.7
14.2
13.5
14.4
16.9
15.5
16.4
19.3
12.7
13.2
13.6
13.7
19.3
13.2
12.7
009
012
015
018
024
030
036
040
042
048
060
-
GEH 072
GEH 090
GEH 120
GEH 150
GEH 180
GEV 072
GEV 090
GEV 120
GEV 150
GEV 180
GEV 240
GEV 300
006
009
012
015
018
024
030
-
036
042
048
060
009
012
015
018
024
030
036
040
042
048
060
-
GEH 072
GEH 090
GEH 120
GEH 150
GEH 180
GEV 072
GEV 090
GEV 120
GEV 150
GEV 180
GEV 240
GEV 300
006
009
012
015
018
024
030
-
036
042
048
060
11.4
12.4
9.1
9.7
9.7
11.0
18.0
14.5
18.0
22.5
30.0
37.5
45.0
18.0
22.5
30.0
37.5
45.0
60.0
18.0
11.0
14.5
14.5
18.0
22.5
30.0
37.5
45.0
18.0
22.5
30.0
37.5
45.0
60.0
75.0
12.5
12.5
12.7
13.2
13.6
13.7
19.3
12.7
13.2
13.6
13.7
19.3
13.2
13.1
-
-
GEH 072
GEH 090
GEH 120
GEH 150
-
GEV 072
GEV 090
GEV 120
GEV 150
GEV 180
GEV 240
GEH 072
GEH 090
GEH 120
GEH 150
-
GEV 072
GEV 090
GEV 120
GEV 150
GEV 180
GEV 240
Water Volume
Table 10 is provided for use in calculating glycol requirements for the unit.
Table 10: Water volume
Water Side Water Side Water Side
Unit Size
60 HZ
Unit Size
50 HZ
Volume
Cubic In.
13.6
Volume
Cubic Ft.
0.008
0.010
0.021
0.028
0.032
0.041
0.044
0.061
0.099
0.105
0.125
0.227
0.296
0.453
0.615
Volume
Gallons
0.059
0.074
0.156
0.208
0.238
0.307
0.329
0.455
0.740
0.783
0.927
1.690
2.201
3.374
4.576
006-009
012
015-018
024
030
036
042
048
060
072
090
120
150, 180
240
300
006
009
015
018
024
030
036
042
048, 060
-
072
090
120, 150
180
240
17.0
36.0
48.0
55.0
71.0
76.0
105.0
171.0
181.0
214
390
508
779
1057
80
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-up Checklist
and Log
Installing Contractor: Use this form to thoroughly check-out the system and units before and during
start-up. (This form need not be returned to the factory unless requested during technical service support).
Job Name:
Model Number:
Date:
Serial Number:
In order to minimize troubleshooting and costly system failures, complete the following checks and data
entries before the system is put into full operation.
MODE
HEAT
COOL
Entering fluid temperature
Leaving fluid temperature
Temperature differential
Return-air temperature DB/WB
Supply-air temperature DB/WB
Temperature differential
F
F
F
F
F
F
F
F
F
F
F
F
PSIG
PSIG
Water coil heat exchanger
(Water Pressure IN)
PSIG
PSIG
PSIG
PSIG
Water coil heat exchanger
(Water Pressure OUT)
Pressure Differential
COMPRESSOR
Amps
Volts
Discharge line temperature
F
F
(after 10 minutes)
WSHP-SVX01D-EN
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Preventive Maintenance
disconnect power before servic-
ing could result in death or seri-
ous injury.
Table 11: Water Quality Table
Scaling
Maintenance on the unit is simplified
with the following preventive sugges-
tions:
Calcium and magnesium
Less than 350 ppm
(total hardness)
Filter maintenance must be performed
to assure proper operation of the
equipment. Filters should be inspect-
ed at least every three months, and re-
placed when it is evident they are
dirty. Filter sizing includes:
Check the contactors and relays within
the control panel at least once a year.
It is good practice to check the tight-
ness of the various wiring connections
within the control panel.
Corrosion
pH
7-9.5
Hydrogen Sulfide
Sulfates
Less than 1 ppm
Less than 25 ppm
Less than 125 ppm
Less than 75 ppm
A strainer (60 mesh or greater) must
be used on an open loop system to
keep debris from entering the unit heat
exchanger and to ensure a clean sys-
tem.
Chlorides
Carbon Dioxide
Size
60 HZ
Size
50 HZ
Filter Size
Total dissolved solids
(TDS)
Less than 1000 ppm
GEH
Biological Growth
14 5/8" x 20 1/4"
(371 x 514)
006-015
018-030
036-042
048-060
072-120
150-180
006-012
015-024
030-036
042-060
072-090
120-150
For units on well water, it is important
to check the cleanliness of the water-
to-refrigerant heat exchanger. Should
it become contaminated with dirt and
scaling as a result of bad water, the
heat exchanger will have to be back
flushed and cleaned with a chemical
that will remove the scale. This service
should be performed by an experi-
enced service person.
Iron Bacteria
Low
Low
Erosion
16 3/8" x 23 5/8"
(416 x 600)
Suspended Solids
18 5/8" x 25 3/8"
(473 x 645)
20 5/8" x 29 3/4"
(524 x 755)
Condensate Trap
For units incorporating a negative trap
design, ensure that the condensate
system is primed with water at all
times. Allowing a negative, pressure
condensate system to run dry could
cause a break in the condensate seal
allowing the fan to draw water from
the condensate line to spray moisture
into the mechanical system. By
20 x 20 (3)
(508 x 508)
25 x 25 (3)
(635 x 635)
GEV
WARNING
Hazardous
Chemicals!
15 7/8" x 19 7/8"
(403 x 504)
006-015
006-012
015-024
030-036
042-060
090
018-030,
040
17 7/8" x 24 7/8"
(454 x 632)
maintaining a primed condensate trap,
a seal will be created and will help
prevent these complications.
Coil cleaning agents can be either
acidic or highly alkaline. Handle
chemical carefully. Proper han-
dling should include goggles or
face shield, chemical resistant
gloves, boots, apron or suit as re-
quired. For personal safety, refer
to the cleaning agent manufactur-
ers Materials Safety Data Sheet
and follow all recommended safe
handling practices. Failure to fol-
low all safety instructions could
result in death or serious injury.
19 7/8" x 24 7/8"
(504 x 632)
036-042
048-060
27 7/8" x 29 7/8"
(708 x 759)
GEV 072-
120
20 x 20 (4)
(508 x 508)
19 5/8" x 24 5/8" (6)
(498 x 625)‘
150-300
120-240
WARNING
Hazardous
It should be noted that the water qual-
ity should be checked periodically. See
Table 11.
Voltage!
Disconnect all electric power, in-
cluding remote disconnects be-
fore servicing. Follow proper
lockout/tagout procedures to en-
sure the power can not be inad-
vertently energized. Failure to
82
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
Information
Warranty Information
Standard Warranty
The standard water-source heat pump warranty is The Trane Company parts-only warranty, running 12
months from startup, not to exceed 18-months from shipment.
Extended Warranty
The optionalextended warranty is a second through fifth year warranty. The time starts at the end of the stan-
dard 1-year coverage through the fifth year.
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems
Group sales territories and must be ordered prior to start-up.
WSHP-SVX01D-EN
83
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Checklist
WARNING
Hazardous Service Procedures!
The maintenance and trouble shooting procedures recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these procedures. When possible, disconnect all electrical pow-
er including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained in handling live electrical components
per these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or
serious injury.
Problem
Heating Cooling Cause
Correction
Check fuses
Replace
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Main power off
Defective control transformer
Broken or loose connection
Defective thermostat
No response to any
thermostat setting
Repair
Replace
Transformer
Reset Transformer
Relocate
Unit short cycles
Thermostat or sensor improperly located
Defective compressor overload
Defective compressor contactor
Supply Voltage too low
Defective compressor capacitor
Defective windings
Replace (if external)
Replace
Blower runs, but compressor does not
Correct
Replace
Replace
Limit switches open
Check cause/Replace or repair
Replace/clean
Correct
Dirty filter
Blower RPM too low
Loss of conditioned air due to leaks in
ductwork
X
X
X
Repair leaks
Introduction of excessively hot return-air
Introduction of excessively cold return-air
Correct
Correct
X
X
Locate leak, repair and recharge by
weight (not by superheat)
X
Low on refrigerant charge
Insufficient capacity
X
X
X
X
X
X
X
X
X
X
X
X
X
Restricted thermal expansion valve
Defective reversing valve
Thermostat improperly located
Unit undersized
Replace
See WSHP-IOM-# for touch test chart
Relocate
Recalculate heat gains/losses
Increase GPM
Inadequate water flow
Scaling in heat exchanger
Water too hot
Clean or replace
Decrease temperature
Increase temperature
Increase water flow to unit
Decrease temperature
Check, clean blower and coil
Clean/replace
X
Water too cold
X
X
Inadequate GPM
Water too hot
X
X
X
X
Inadequate air flow
High pressure switch open
Dirty filter
X
X
Overcharged with refrigerant
Defective pressure switch
Decrease charge
Check or replace
84
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Checklist
Problem
Heating Cooling Cause
Correction
X
X
X
X
X
Trash in heat exchanger
Low water flow
Backflush
Increase GPM
X
X
X
X
X
X
X
Overcharge of refrigerant
Non-condensable in system
Water too hot
Decrease charge
Evacuate and recharge by weight
Decrease temperature
Clean / replace
High head pressure
Dirty filter
Inadequate air flow
Undercharged
Check, clean blower and coil
Locate leak, repair and recharge
Repair / replace
X
X
X
X
Restricted thermal expansion valve
Inadequate air flow
Dirty filter
Low suction pressure
Check, clean blower and coil
Clean/replace
X
X
X
Inadequate GPM
Increase GPM
Inadequate GPM
Increase GPM
Water too cold
Increase temperature
Increase CFM
X
X
X
X
X
Inadequate air flow
Dirty filter
Low Pressure switch open
Clean/replace
X
X
X
Undercharged with refrigerant
Defective pressure switch
Heat transfer fluid too cold
Increase charge
Replace
Raise water temperature
Deluxe Controls
Troubleshooting units which contain the deluxe control option may be made easy by using the three LEDs (light emitting
diodes). These LEDs are provided for indicating the operating mode of the controller. The LEDs are intended to aid in trou-
bleshooting maintenance. The LEDs are labeled on the circuit board with numbers as referenced in Table 12.
Table 12: Diagnostic LEDs
Color: Green
Color: Red
Controller
Mode
LED1
OFF
ON
LED2
LED3
OFF
OFF
OFF
Control OFF
Normal/Compressor OFF
OFF
ON
OFF
FLASH Anti-short cycle
ON
OFF
ON
OFF
ON
Normal/Compressor ON
FLASH
ON
ON
Brownout Condition
FLASH
FLASH
ON
Soft Lockout (low pressure)
ON
FLASH Soft Lockout (high pressure)
ON Manual Lockout (low pressure)
FLASH Manual Lockout (high pressure)
ON
ON
ON
ON
FLASH
OFF
Manual Lockout (condensate over-
flow)
ON
ON
OFF
Compressor Disable
WSHP-SVX01D-EN
85
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
Basic
208 V-60 HZ-1 PH
86
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
Deluxe
380-420V-50 HZ-3 PH
WSHP-SVX01D-EN
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
ZN510
208V-60 HZ-1 PH
88
WSHP-SVX01D-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
ZN524
460 V-60 HZ-3 PH
WSHP-SVX01D-EN
89
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
WSHP-SVX01D-EN
SV-UN-WSHP-SVX01D-0404
SV-UN-WSHP-SVX01C-0104
Inland
Supersedes
Trane
Stocking Location
A business of American Standard Companies
For more information, contact your local district
office or e-mail us at [email protected]
Trane has a policy of continuous product and data improvement and reserves the right to change
design and specifications without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
|