Series R™ Helical Rotary
Liquid Chillers
Model RTHD
175-450Tons (60 Hz)
125-450Tons (50 Hz)
Built for Industrial and Commercial Applications
RLC-PRC020-EN
June 2006
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
2
4
Introduction
Features and Benefits
Options
6
8
Controls
10
12
14
16
19
22
29
30
Application Considerations
Selection Procedure
Model Nomenclature
General Data
Electrical Data and Connections
Dimensions andWeights
Mechanical Specifications
Conversion Table
RLC-PRC020-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
ApplicationVersatility and High
Performance
• Generic Building Automation System
points are available for easy access to
operational information.
• Extensive information on professional
design selection and layout is available
in a simple, highly readable electronic
format.
• Standard model RTHD configurations
are in stock and available for immediate
delivery, andTrane offers the fastest
ship cycles in the industry for built-to-
order units.
• Industrial / LowTemperature Process
Cooling – Excellent operating
temperature range and precise control
capabilities enable tight control with
single chiller or series configuration.
• Ice/Thermal Storage – Specifiers and
operators benefit from dual setpoint
control and industry-leading
temperature, efficiency, and control
capabilities, plus outstanding support
through partnership with Calmac, a
strongTrane partner providing proven
installation examples, templates, and
references that minimize design time
and energy costs.
• Heat Recovery – Maximum condenser
temperature exceeds those of previous
technologies, providing hot water and
tight control that minimizes operating
costs for the chilled water plant and
boiler/hot water heater, and consistent
dehumidification.
Simple, Economical Installation
• Compact size makes the model RTHD
well suited for the retrofit and
replacement market.
• All units fit through standard double-
width doors.
• Screw compressor technology and the
electronic expansion valve provide
reliable performance in an expanded
range of operating temperatures.
•Tight water temperature control extends
to operation of multiple chillers in
parallel or series configurations, offering
further system design flexibility for
maximum efficiency.
• Advanced design enables chilled water
temperature control to +/- 0.5°F (.28°C)
for flow changes up to 10 percent per
minute, plus handling of flow changes up
to 30 percent per minute for comfort
cooling.
•Two-minute stop-to-start and five-minute
start-to-start anti-recycle timer allows
tight chilled water temperature control
in constant or transient low-load
applications.
• LonMark communications capability
provides excellent, trouble-free
interoperability.
• Bolt-together construction makes for
fast, easy unit disassembly.
• Small RTHD footprint saves valuable
equipment room space and alleviates
access concerns for most retrofit jobs.
• Lightweight design simplifies rigging
requirements, further reducing
installation time requirements and
costs.
• Full factory refrigerant or nitrogen and
oil charges reduce required field labor,
materials, and installation cost.
• Only evaporator and condenser water
piping is required; no starter water
cooling (with its associated safety
concerns) or field piping is necessary.
• Oil cooler and purge system
connections have been eliminated.
• Simple power connection simplifies
overall installation.
• Standard unit-mounted starter for
Wye-Delta and Solid State eliminates
additional jobsite installation
considerations and labor requirements.
•Trane has conducted extensive factory
testing, and also offers options for in-
person and/or documented system
performance verification.
• CH530 controls easily interface with
Tracer Summit™ building automation
systems through single twisted-pair
wire.
Applications in this catalog specifically
excluded from the ARI certification
program are:
• Low temperature applications, including
ice storage
• Glycol
• 50Hz units below 200 nominal tons
Pueblo
Business Unit
4
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
State-of-the-Art, Precision Control
• Microprocessor-based CH530 controls
monitor and maintain optimal operation
of the chiller and its associated sensors,
actuators, relays, and switches, all of
which are factory-assembled and
extensively tested.
• Easy interface with computers hosting
Tracer Summit™ building automation/
energy management systems allows
the operator to efficiently optimize
comfort system performance and
minimize operating costs.
•TheTrane helical rotary compressor is a
proven design resulting from years of
research and thousands of test hours,
including extensive testing under
extraordinarily severe operating
conditions.
•Trane is the world’s largest
manufacturer of large helical rotary
compressors, with tens of thousands of
commercial and industrial installations
worldwide demonstrating a reliability
rate of greater than 99 percent in the
first year of operation.
• PID (proportional integral derivative)
control strategy ensures stable, efficient
chilled water temperature control,
maintaining +/- 1°F (0.56°C) control by
proactively reacting to instantaneous
load changes of up to 50 percent.
• Adaptive Control™ attempts to maintain
chiller operation under adverse
conditions, when many other chillers
might simply shut down.
• Easy-to-use operator interface displays
all operating and safety messages, with
complete diagnostics information, on a
highly readable panel with a scrolling
touch-screen display.
•The RTHD features a complete range of
chiller safety controls.
• Over 120 diagnostic and operating
points are available, with standard
displays including chiller current draw,
condenser pressure, and evaporator
pressure.
Operating and Life Cycle
Cost-Effectiveness
• Electronic expansion valve enables
exceptionally tight temperature control
and extremely low superheat, resulting
in more efficient full-load and part-load
operation than previously available.
• Precise compressor rotor tip clearance
ensures optimal efficiency.
• Condenser and evaporator tubes use
the latest heat transfer technology for
increased efficiency.
•The RTHD includes standard electrical
demand limiting.
• Chilled water reset based on return
water temperature is standard.
• High compressor lift capabilities and
tight chilled water temperature control
allow highly efficient system design with
minimal operational concerns.
Design capabilities include:
• variable primary flow;
• series chiller arrangements for
evaporator and/or condenser;
• low evaporator and condenser flow.
Reliability and Ease of Maintenance
• Direct drive, low-speed compressor – a
simple design with only three moving
parts – provides maximum efficiency,
high reliability, and low maintenance
requirements.
• Electronic expansion valve, with fewer
moving parts than alternative valve
designs, offers highly reliable operation.
• Suction gas-cooled motor stays
uniformly cool at lower temperatures
for longer motor life.
RLC-PRC020-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Options
Insulation
2-Way CondenserWater RegulatingValve
For water regulation, a field-installed,
2-way butterfly-type (lug-style) valve,
with integral electrical operator and
factory-mounted valve actuator, is
available.The single-phase, reversible
motor can be factory-wired for 115VAC,
60 Hz or 220VAC, 50 Hz; the 2-way valve
is field-wired and controlled by the chiller
regulating valve control output; valves
are available in 6" and 8" (152.4 and
203.2 mm) sizes.
Main Power Disconnect
Options:
All low temperature surfaces are
covered with factory installed 3/4 inch
(19.05 mm) Armaflex II or equal (k=0.28)
insulation, including the evaporator and
water boxes, suction line, and motor
housing. 3/8" foam insulation is used on
the liquid level sensor and gas pump
assembly, including piping.
Non-fused Disconnect
A UL-approved non-fused molded case
disconnect switch, factory pre-wired with
terminal block power connections and
equipped with a lockable external
operator handle, is available to
disconnect the chiller from main power.
Low-Temperature Evaporator
Addition of an oil cooler to the oil circuit
enables evaporator operation down to
minimum leaving water temperature of
10°F (-12.2°C).
Standard Interrupting Capacity Circuit
Breaker
Nitrogen Charge
Unit is shipped with a nitrogen holding
charge in lieu of refrigerant.
A UL-approved standard interrupting
molded case capacity circuit breaker,
factory pre-wired with terminal block
power connections and equipped with a
lockable external operator handle, is
available to disconnect the chiller from
main power.
High-Temperature Condenser
Addition of an oil cooler to the oil circuit
enables condenser operation up to
maximum leaving water temperature of
114°F (45.6°C).
Seal Kit for Reassembly
Ideal for situations when the bolt-together
construction of the RTHD will be
separated for installation, this seal kit
provides replacement gaskets and rings
for reassembly.
High Interrupting Capacity Circuit
Breaker
Smooth-Bore CondenserTubes
Smooth-bore copper or premium cupro-
nickel condenser tubes, 3/4" (19.05 mm) in
diameter with .035" (0.889 mm) wall
thickness, are available for high fouling
water applications.
A UL-approved high interrupting molded
case capacity circuit breaker, factory pre-
wired with terminal block power
connections and equipped with a lockable
external operator handle, is available to
disconnect the chiller from main power.
Solid State Starter
Solid State Starter is unit-mounted with a
NEMA 1 gasketed enclosure.To extend
starter life, contactors bypass current
from the silicon control rectifiers (SCRs)
after startup.
Refrigerant Isolation Valves
Factory-installed condenser inlet and
outlet refrigerant valves allow isolation of
the full refrigerant charge in the
Ground Fault Circuit Breaker
Under/Over-Voltage Protection
Unit receives protection against
variations in voltage (current lag and
spike protection is standard).
A UL-approved standard interrupting
molded case capacity circuit breaker with
ground fault interrupting capability,
factory pre-wired with terminal block
connections and equipped with a lockable
external operator handle, is available to
disconnect the chiller from main power.
condenser while servicing the chiller.
MarineWater Boxes
Addition of marine water boxes for the
condenser allows tube cleaning without
water pipe interference.
Performance andWitnessTests
ARI-certified RTHD Performance and
WitnessTests are available, based on
requested operating points, to certify
chiller performance before delivery.
300 psig Evaporator and Condenser
Water Boxes
Water boxes are designed for 300 psig
maximum waterside working pressure,
and grooved pipe water connections are
provided for ease of installation.
6
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Options
Programmable Relays
ControlOptions:
Default-set, factory-installed,
Tracer Summit Communications
Link to factory-installed, tested
communication board, via single twisted-
pair wiring, addsTracer Summit
communications to the system.
programmable relays allow the operator
to select four relay outputs from a list of
eight. Available relays are: Alarm-
Latching, Alarm-Auto Reset, General
Alarm,Warning, Chiller Limit Mode,
Compressor Running, Head Pressure
Relief Request, andTracer Control.
LonTalk LCI-C Interface
LonTalk (LCI-C) communications
capabilities are available, with
communication link via single twisted-pair
wiring to factory-installed, tested
communication board.
ChilledWater Reset – OutdoorAir
Temperature
Controls, sensors, and safeties allow
reset of chilled water temperature, based
on temperature signal, during periods of
low outdoor air temperature (chilled
water reset based on return chilled water
temperature is standard).
External ChilledWater Setpoint
External ChilledWater Setpoint is
communicated to a factory-installed,
tested communication board through a 2-
10Vdc or 4-20mA signal.
Condenser-RegulatingValve Control
Chiller applies a Proportional Integrative
Control (PID) algorithm to control water
regulating valve via 0-10Vdc signal.
External Current Limiting
External Current Limit Setpoint is
communicated to a factory-installed,
tested communication board through a 2-
10Vdc or 4-20mA signal.
Percent of Full Run LoadAmps Output
Control system indicates the active chiller
percent of full run load amps, based on a
0-10Vdc signal.
External Base Loading
External Base Loading is communicated
to a factory-installed and tested
communication board through a
2-10Vdc or 4-20mA signal.
Condenser Pressure Output
Control system indicates chiller
differential pressure or condenser
pressure, based on a 0-10Vdc signal.
Ice Making Control
Controls and safeties allow operation
with brine temperatures down to 20°F
(-6.7°C) , and dual setpoints enable both
ice making and daytime comfort cooling.
Refrigerant Monitor Input
Control system indicates refrigerant
monitor status of 0-100 or 0-1000 ppm
(user selectable), based on a 2-10Vdc /
4-20 mA signal.
RLC-PRC020-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
• Fast, easy access to available chiller
data in tabbed format, including:
— Modes of operation, including normal
cooling and icemaking
—Water temperatures and setpoints
— Loading and limiting status and
setpoints
— Evaporator, condenser, and
compressor reports containing all
operational information on individual
components, including:
-Water and air temperatures
- Refrigerant levels, temperatures,
and approach
LCD Touch-Screen Display
with Multi-Language Support
The standard DynaView display provided
with the CH530 control panel features an
LCD touch-screen, allowing access to all
operational inputs and outputs.This
display supports eleven languages:
English, Chinese, Dutch, French, German,
Italian, Japanese, Korean, Portugese,
Spanish andThai.
— Average line current
— Outdoor air temperature
— Start/stop differential timers
— Auto/Manual mode for EXV, slide
valve, and head pressure control
— Pump status and override
— Chilled water reset, start point, ratio,
and outdoor start point
— External setpoints, including:
- chilled water
- Oil pressure
- Flow switch status
- EXV position
- Head pressure control command
- Compressor starts and run-time
- Line phase percent RLA, amps, and
volts
Additional Display Features Include:
• LCD touch-screen with LED backlighting,
for scrolling access to input and output
operating information
•Weather-proof enclosure for reliable
operation in non-standard indoor
environments
• Spin value buttons to allow continuously
variable setpoints when applicable
• Radio and action buttons for easy, one-
time actions and settings
• Single-screen, folder/tab-style display of
all available information on individual
components (evaporator, condenser,
compressor, etc.)
• Automatic and immediate stop
capabilities for standard or immediate
manual shutdown
• Manual override indication
• Password entry/lockout system to
enable or disable display
— Alarm and diagnostic information,
including:
- Flashing alarms with touch-screen
button for immediate address of
alarm condition
- Scrollable list of last ten active
diagnostics
- Specific information on applicable
diagnostic from list of over one-
hundred
- Automatic or manual resetting
diagnostic types
- current limit
- ice building
- base loading
— Display specifics, including:
- date
- format
- time
- display lockout
- display units
- language setting
- Reports, listed on a single tabbed
screen for easy access, including:
• ASHRAE, containing all guideline 3
report information
• Evaporator
• Condenser
• Compressor
8
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Tracer Summit features standard report
templates listing key operating data for
troubleshooting and verifying
performance. Reports for each type of
Trane chiller and three and six-chiller
systems are also standard. Detailed
reports showing chiller runtimes aid in
planning for preventative maintenance.
LonTalk Communications Interface for
Chillers (LCI-C) provides a generic
Trane Chiller PlantAutomation
Trane’s depth of experience in chillers and
controls makes us a well-qualified choice
for automation of chiller plants using air-
cooled Series R® chillers®.The chiller plant
control capabilities of theTraneTracer
Summit® building automation system are
unequaled in the industry. Our chiller plant
automation software is fully pre-
engineered and tested. It is a standard
software application, not custom
programming which can prove to be
difficult to support, maintain, and modify.
automation system with the LonMark
chiller profile inputs/outputs. In addition to
the standard points,Trane provides other
commonly used network output variables
for greater interoperability with any
automation system. The complete
reference list ofTrane LonTalk points is
available on the LonMark website. Trane
controls or another vendor’s system can
use the predefined list of points with ease
to give the operator a complete picture of
how the system is running.
Swift Emergency Response
We understand the importance of
maintaining chilled water production
while protecting your chillers from costly
damage. If no water flow is detected to a
chiller’s piping, the start sequence is
aborted to protect the chiller.The next
chiller in the sequence is immediately
started to maintain cooling.
Energy Efficiency
Trane chiller plant automation intelligently
sequences starting of chillers to optimize
the overall chiller plant energy efficiency.
Individual chillers are designated to
operate as base, peak, or swing based on
capacity and efficiency. Sophisticated
software automatically determines which
chiller to run in response to current
conditions.The software also
Hardwire Points
Remote devices wired from the control
panel are another reliable method of
providing auxiliary control to a building
automation system. Inputs and outputs
can be communicated via a typical 4-20
mA electrical signal (or an equivalentVdc
signal of 0-10 or 2-10) or by utilizing
contact closures.
In the event of a problem, the operator
receives an alarm notification and
diagnostic message to aid in quick and
accurate troubleshooting. A snapshot
report showing system status just prior to
an emergency shutdown helps operators
determine the cause. If emergency
conditions justify an immediate manual
shutdown, the operator can override the
automatic control.
automatically rotates individual chiller
operation to equalize runtime and wear
between chillers.
• External ChilledWater Setpoint
• External Current Limit Setpoint
• Condenser-RegulatingValve Control
• Percent of Full Run Load Amps Output
• Condenser Pressure Output
Trane chiller plant automation enables
unique energy-saving strategies. An
example is controlling pumps, and chillers
from the perspective of overall system
energy consumption.The software
intelligently evaluates and selects the
lowest energy consumption alternative.
Integrated Comfort™ Capabilities
When integrated with aTracer Summit
building management system
performing building control,Trane chiller
plant automation coordinates withTracer
Summit applications to optimize the total
building operation.With this system
option, the full breadth ofTrane’s HVAC
and controls experience are applied to
offer solutions to many facility issues. If
your project calls for an interface to other
systems,Tracer Summit can share data
via BACnet™, the ASHRAE open systems
protocol.
• Refrigerant Monitor Input
• Programmable Relays
Allows the selection of 4 relay outputs
from a list of eight different default
settings: Alarm-Latching, Alarm-Auto
Reset, General Alarm,Warning, Chiller
Limit Mode, Compressor Running, Head
Pressure Relief Request, andTracer
Control. These contact closures may be
used to trigger jobsite supplied audible or
visual alarms
Regulatory Compliance Documentation
Comprehensive documentation of
refrigerant management practices is now
a fact of life.Trane chiller plant automation
generates the reports mandated in
ASHRAE Guideline 3.
Keeping Operators Informed
A crucial part of efficiently running a
chiller plant is assuring that the
LonTalk Chiller Controls
• Ice Making Control
operations staff is instantly aware of
what is happening in the plant. Graphics
showing schematics of chillers, piping,
pumps, and towers clearly depict the
chiller plant system, enabling building
operators to easily monitor overall
conditions. Status screens display both
current conditions and upcoming
automated control actions to add or
subtract chiller capacity. Series R™ and
other chillers can be monitored and
controlled from a remote location.
LonTalk is a communications protocol
developed by the Echelon Corporation.
The LonMark association develops
control profiles using the LonTalk
communication protocol. LonTalk is a unit
level communications protocol, unlike
BACNet used at the system level.
Provides an interface with ice making
control system and safeties, enabling
both ice making and daytime comfort
cooling
• ChilledWaterTemperature Reset
Supplies controls, sensors and safeties to
reset the chilled water temperature
setpoint based upon return water
temperature (standard) or outdoor air
temperature (optional)
RLC-PRC020-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Condenser WaterTemperatures
Reduced sensitivity to condenser water
startup temperatures is one major
enhancement in the newest-generation
water-cooled Series R chiller.With the
model RTHD chiller, a condenser water
control method is necessary only if the
unit starts with entering water
temperatures below 55°F (12.8°C), or
between 45°F (7.2°C) and 55°F (12.8°C),
when a temperature increase of 1°F
(0.56°C) per minute to 55°F (12.8°) is not
possible.
power input required, but the ideal
temperature for optimizing total system
power consumption will depend on the
overall system dynamics. From a system
perspective, some improvements in
chiller efficiency may be offset by the
increased tower fan and pumping costs
required to achieve the lower tower
temperatures. Contact your localTrane
systems solution provider for more
information on optimizing system
performance.
Some basic rules should be followed
whenever using these system design and
operational savings methods with the
RTHD.The proper location of the chilled
water temperature control sensor is in
the supply (outlet) water.This location
allows the building to act as a buffer, and
it assures a slowly changing return water
temperature. If there is insufficient water
volume in the system to provide an
adequate buffer, temperature control can
be lost, resulting in erratic system
operation and excessive compressor
cycling.To ensure consistent operation
and tight temperature control, the chilled
water loop should be at least two
minutes. If this recommendation cannot
be followed, and tight leaving water
temperature control is necessary, a
storage tank or larger header pipe should
be installed to increase the volume of
water in the system.
The minimum acceptable refrigerant
pressure differential between condenser
and evaporator is 23 psid.The chiller
control system will attempt to obtain and
maintain this differential at startup, but for
continuous operation a design should
maintain a 25°F (13.9°C) differential from
evaporator leaving water temperature to
condenser leaving water temperature.
When the application requires startup
temperatures below the prescribed
minimums, a variety of options are
available.To control a 2-way or 3-way
valve,Trane offers a Condenser
RegulatingValve Control option for the
CH530 controls.This option enables the
CH530 controls to send a signal for
opening and closing the valve as
necessary to maintain chiller differential
pressure.The 2-way valves are available
as a ship-with option.Tower bypass is
also a valid control method if the chiller
temperature requirements can be
maintained.
Variable Evaporator Flow and Short
EvaporatorWater Loops
For variable primary flow applications,
the rate of chilled water flow change
should not exceed 10 percent of design
per minute to maintain +/-0.5°F (0.28°C)
leaving evaporator temperature control.
For applications in which system energy
savings is most important and tight
temperature control is classified as
+/-2°F (1.1°C), up to 30 percent changes in
flow per minute are possible. Flow rates
should be maintained between the
minimum and maximum allowed for any
particular chiller configuration.
Variable evaporator flow is an energy-
saving design strategy which has quickly
gained acceptance as advances in chiller
and controls technology have made it
possible.With its linear unloading
compressor design and advanced CH530
controls, the RTHD has excellent
capability to maintain leaving water
temperature control within +/-0.5°F
(0.28°C) , even for systems with variable
evaporator flow and small chilled water
volumes.
Trane Series R chillers start and operate
successfully and reliably over a range of
load conditions with controlled entering
condenser water temperature. Reducing
the condenser water temperature is an
effective method of lowering chiller
10
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Series Chiller Arrangements
Like series arrangements on the
Water Pumps
Another energy-saving strategy is to
design the system around chillers
arranged in series, on the evaporator,
condenser, or both.The actual savings
possible with such strategies depends on
the application dynamics and should be
researched by consulting yourTrane
Systems Solutions Representative and
applying theTrane System Analyzer
program. It is possible to operate a pair of
chillers more efficiently in a series chiller
arrangement than in a parallel
evaporator, series arrangements on the
condenser may enable savings.This
approach may allow reductions in pump
and tower installation and operating
costs. Maximizing system efficiency
requires that the designer balance
performance considerations for all
system components; the best approach
may or may not involve multiple chillers,
or series arrangement of the evaporators
and/or condensers. This ideal balance of
design integrity with installation and
operating cost considerations can also be
obtained by consulting aTrane
Where noise limitation and vibration-free
operation are important,Trane strongly
encourages the use of 1750-rpm (60 Hz),
1450-rpm (50 Hz) pumps. Specifying or
using 3600-rpm (60 Hz), 3000-rpm (50 Hz)
condenser water and chilled water
pumps must be avoided, because such
pumps may operate with objectionable
levels of noise and vibration. In addition, a
low frequency beat may occur due to the
slight difference in operating rpm
between 3600-rpm (60 Hz), 3000-rpm
(50 Hz) water pumps and Series R chiller
motors. Important Note:The chilled water
pump must not be used to stop the chiller.
arrangement. It is also possible to achieve
higher entering-to-leaving chiller
differentials, which may, in turn, provide
the opportunity for lower chilled water
design temperature, lower design flow,
and resulting installation and operational
cost savings.TheTrane screw
representative and applying theTrane
System Analyzer program.
Acoustic Considerations
Water Treatment
For chiller sound ratings, installation tips,
and considerations on chiller location,
pipe isolation, etc., refer to theTrane
Water-Cooled Series R Chillers Sound
Ratings and Installation Guide. Using the
information provided in this bulletin,
contact a certified sound consultant to aid
in proper mechanical room design and
treatment.
The use of untreated or improperly
treated water in chillers may result in
scaling, erosion, corrosion, and algae or
slime buildup. It is recommended that the
services of a qualified water treatment
specialist be engaged to determine what
treatment, if any, is advisable.Trane
assumes no responsibility for the results
of using untreated or improperly treated
water.
compressor also has excellent
capabilities for “lift”, which affords an
opportunity for savings on the
evaporator and condenser water loops.
Figure 1. Typical series chiller arrangement
RLC-PRC020-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Trane Series R chiller performance is
rated in accordance with the ARI
Standard 550/590-2003 Certification
Program. Chiller selection assistance and
performance information can be
obtained by using the Series R chiller
selection program, available through
localTrane sales offices.
Part Load Performance
Actual air-conditioning system loads are
frequently less than full-load design
conditions. Depending on the number of
chillers on the job and the load profile,
chillers may operate at full load a small
percentage of the time.With their
excellent part-load performance
characteristics and highly energy-efficient
operation, Series R chillers can provide
significant operating savings at these
part-load conditions.
Performance
The computerized Series R chiller
selection program provides performance
data for each possible chiller selection at
both full-load and part-load design points,
as required.
System Considerations
Part-load chiller operation is frequently
associated with reduced condenser
water temperatures. However, rather
than focusing only on the chiller, it is
important to balance these temperatures
to achieve the most efficient system
operation possible. At part-load
It should be noted that changing the
number of water passes or the water
flow rates will generally alter the
performance of a particular chiller.To
attain maximum benefit from the wide
range of chiller models and options
available, designers are encouraged to
first develop performance specifications
and then use the chiller selection program
to optimize all selections.This will help
ensure selection of the compressor-
evaporator-condenser combination that
most closely meets the job requirements.
To optimize system performance, all
selections should also be balanced with
other system components.
operation, the heat rejected to the cooling
tower is less than at full-load operation.
Part-load chiller operation is also typically
associated with reduced outside wet bulb
temperatures, resulting in improved
cooling tower performance.The net result
of reduced heat rejection and lower wet
bulb temperatures can be cooler
condenser water entering the chiller,
ultimately improving unit performance.
However, this does not improve pump or
tower efficiency.To achieve the most
efficient system operation possible, it is
best to minimize the total power draw of
the chiller, tower, and pumps, which may
not mean limiting the condenser water
temperature to what the tower can
provide.To determine specific unit and
system part-load performance for chiller
selection purposes, use the Series R
chiller computer selection program or
contact the localTrane sales office.
Fouling Factors
ARI Standard 550 includes a definition of
clean tube fouling.The recommended
standard fouling adjustments are 0.0001
hr-sq ft-deg F/Btu (0.0176 sq m-deg C/kW)
for the evaporator and 0.00025 hr-sq ft
deg F/Btu (0.044 sq m-deg C/kW) for the
condenser, from an increment of 0.0000
“clean.” Chiller specifications should be
developed using the most current
standard fouling factors.
12
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Unit Performance with Fluid Media
OtherThanWater
Electrical DataTables
Compressor motor electrical data is
provided in the data section for each
compressor size. Rated load amperes
(RLA), locked rotor wye amperes (LRA)
and expected inrush for theWye-delta
and Solid State Starter configurations are
shown.
Series R chillers can be provided with a
wide variety of fluid media other than
water, including ethylene glycol and
propylene glycol— in the evaporator,
condenser or both. Chillers using media
other than water are excluded from the
ARI 550/590-2003 Certification Program,
but are rated in accordance with ARI
Standard 550/590-2003.Trane factory
performance tests are only performed
with water as the cooling and heat-
rejection media.When considering
selection of media other than water,
contact the localTrane sales office for
chiller selections and factory
Although the terms “LRA” and “expected
inrush” are often used interchangeably,
the distinction applied here is that LRA is
the rated inrush for the motor, but
expected inrush is that allowed by the
starter, based on the specific
configuration.
Selecting starters in theWye-delta or
Solid State configuration lowers
expected inrush vs. the Delta (or “across-
the-line”) configuration. A Solid State
Starter configuration lowers the
expected inrush by approximately 50
percent, whileWye-Delta lowers it by
approximately 66 percent.
performance testing information.
Fluid media other than water lowers the
heat transfer coefficient, and therefore
reduces chiller performance. In general, it
is good practice to hold the percent glycol
added to within the minimum allowed by
theTrane selection program, based on
either (a) unit operating temperatures, or
(b) the operating temperatures the
evaporator or condenser water will
experience under its full range of
conditions. Adding more glycol than
required for the specific application is
equivalent to selecting a less efficient
chiller. Lower-viscosity glycols such as
ethylene will have less adverse impact
on chiller performance than higher-
viscosity glycols such as propylene.
The RLA is based on the motor’s
performance when reaching full rated
horsepower.The kW rating of the motor
will equal or exceed the kW requirement
indicated by the Series R computer
selection program at design conditions. If
motor kW draw at design conditions is
less than the kW rating of the motor, the
RLA at design conditions is determined
by multiplying the motor RLA (at the
desired voltage) by this ratio: design kW/
motor kW rating.This calculation is
performed within the Series R chiller
computer selection program, making
RLA available as part of the design
predictions. Predicted values include
power factor variation from point to point.
Evaporator and Condenser Pressure
Drop
Pressure drop data is determined by the
Series R chiller computer selection
program available through localTrane
sales offices.
A voltage utilization range is tabulated for
each voltage listed. Series R chillers are
designed to operate satisfactorily over a
utilization range of 10 percent of the
standard design voltages: (a) 200V, 230V,
380V, 460V, and 575V for 60 Hertz, 3-
phase, and (b) 380V, 400V,
Dimensional Drawings
Dimensional drawings provided for
selection purposes illustrate overall
measurements of the unit.The
recommended service clearances are
those required to easily service the
Series R chiller.
415V for 50 Hertz, 3-phase.
All catalog dimensional drawings are
subject to change, and current submittal
drawings should be referenced for more
detailed dimensional information.
Dimensional drawings are also available
from the selection program. Contact the
localTrane sales office for submittal
information.
RLC-PRC020-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Nomenclature
RTH
D
U
5
D
6
2
7
F
8
0
9
A0
10,11
U
12
A
G
3
15
A
16
4
17
L
18
A
19
L
20
G
21
3
22
F
23
2
24
L
25
A
L
1,2,3 4
13 14
26 27
Digits 01, 02, 03 – Series R™
Digit 09 – Specials
Digit 18 – Evaporator Water Connection
L = Left Hand Evaporator Connection
R = Right Hand Evaporator Connection
RTH = Series R
X = No specials
C = All specials denoted by digits elsewhere
S = Uncategorized special not denoted by
other digits
Digit 04 – Dev Sequence
D = 4th Major Development
Digit 19 – Evaporator Connection Type
A = Standard Grooved Pipe
Digit 05 – Design Control
U = WCBU
Digits 10, 11 – Design Sequence
** = First Design, etc. increment when parts
are affected for service purposes
Digit 20 – Evaporator Waterside Pressure
L = 150 psi
H = 300 psi
Digit 06 – Compressor Frame
B = B Compressor
Digit 12 – Agency Listing
X = No agency listing
U = C/UL
C = C Compressor
Digit 21 – Condenser
B = B Frame
D = D Compressor
E = E Compressor
D = D Frame
Digit 13 – Pressure Vessel Code
A = ASME
L = Chinese Pressure Vessel Code
E = E Frame
Digit 07 – Compressor Capacity
1 = Smaller Capacity for Frame
2 = Larger Capacity for Frame
3 = 50Hz Capacity
F = F Frame
G = G Frame
Digit 14 – Evaporator Frame
B = B Frame
Digit 22 – Condenser Capacity
1 =Tube count #1
Digit 08 – Unit Power Supply
A = 200V/60Hz/3Ph power
C = 230V/60Hz/3Ph power
D = 380V/60Hz/3Ph power
R = 380V/50Hz/3Ph power
T = 400V/50Hz/3Ph power
U = 415V/50Hz/3Ph power
F = 460V/60Hz/3Ph power
H = 575V/60Hz/3Ph power
C = C Frame
2 =Tube count #2
D = D Frame
3 =Tube count #3
E = E Frame
4 =Tube count #4
F = F Frame
5 =Tube count #5
G = G Frame
Digit 23 – Condenser Tube Type
A = Enhanced Fin Copper
B = Smooth Bore Copper
Digit 15 – Evaporator Capacity
1 =Tube count #1
2 =Tube count #2
C = Smooth Bore 90/10 CU/NI
3 =Tube count #3
4 =Tube count #4
Digit 24 – Condenser Passes
2 = 2 Pass
5 =Tube count #5
6 =Tube count #6
Digit 25 – Condenser Water Connection
L = Left Hand Connection
R = Right Hand Connection
Digit 16 – Evaporator TubeType
A = Enhanced Fin Copper
Digit 17 – Evaporator Water Pass
Configuration
2 = 2 pass
Digit 26 – Condenser Connection Type
A = Standard Grooved Pipe
C = Marine
3 = 3 pass
4 = 4 pass
Digit 27 – Condenser Waterside Pressure
L = 150 psi
H = 300 psi
14
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Nomenclature
A
V
X
Q
X
E
X
A
A
B
D
Y
444
D
A
X
A
4
X
X
X
R
51
X
V
X
28 29 30 31 32 33 34 35 36 37 38 39 40,41,42 43 44 45 46 47 48
49 50
52 53 54
Digit 28 – Condenser Leaving Water
Temperature
Digit 48 – External Chilled Water and Current
Limit Setpoint
X = None
4 = 4-20mA input
2 = 2-10Vdc
Digit 38 – Factory Test
X = Standard Test
C = Witness Test
A = Standard
D = Performance Test
Digit 29 – Refrigerant Specialties
X = No Refrigerant Isolation Valves
V = With Refrigerant Isolation Valves
Digit 39 – StarterType
Y = Wye Delta Closed Transition Starter
A = Solid State Starter
Digit 49 – External Base Loading
X = None
4 = 4-20mA input
2 = 2-10Vdc input
Digit 30 – Oil Cooler
X = Without Oil Cooler
C = With Oil Cooler
Digits 40, 41, 42 – Design RLA (for starter)
*** = Selection Assigned
Digit 50 – Icemaking
X = None
A = Icemaking with Relay
B = Icemaking without Relay
Digit 31 – Thermal Insulation
X = No Insulation
Q = Factory Installed Insulation
Digit 43 – Power Line Connection Type
A =Terminal Blocks
B = Mechanical Disconnect Switch
D = Circuit Breaker
F = High Interrupt Circuit Breaker
H = Ground Fault Circuit Breaker
J = Ground Fault High Interrupt Circuit
Breaker
Digit 32 – Acoustic Insulation
X = No Insulation
A = Standard Insulation
Digit 51 – Programmable Relays
X = None
R = With
Digit 33 – Label and Literature Language
Digit 52 – Chilled Water Reset
X = Chilled Water Reset – Return Water
T = Chilled Water Reset – Outdoor Air
Temperature
C = Spanish
E = English
F = French
Digit 44 – Enclosure Type
A = NEMA 1
Digit 45 – Under/Over Voltage Protection
X = None
Digit 34 – Safety Devices
Digit 53 – Control Outputs
X = Standard
X = None
U = With Under/Over Voltage Protection
V = Condenser Regulating Valve Control &
Digit 35 – Factory Charge
A = Factory Refrigerant Charge (134a)
B = Factory Nitrogen Charge
Percent RLA
Digit 46 – Operator Interface Language
A = Dyna-View/English
B = Dyna-View/French
C = Dyna-View/Italian
D = Dyna-View/Spanish
E = Dyna-View/German
F = Dyna-View/Dutch
P = Condenser Pressure (% HPC) & Percent
RLA
D = Chiller Differential Pressure & Percent
RLA
Digit 36 – Shipping Package
A = No Skid (standard)
B = Shrink Wrap
C = Skid
D = Skid + Shrink Wrap
J = Special
Digit 54 – Refrigerant Monitor Input
X = None
A = 100 ppm / 4-20mA
B = 1000 ppm / 4-20mA
C = 100 ppm / 2-10Vdc
D = 1000 ppm / 2-10Vdc
G = Dyna-View/Traditional Chinese
H = Dyna-View/Simple Chinese
J = Dyna-View/Japanese
K = Dyna-View/Portuguese
L = Dyna-View/Korean
Digit 37 – Flow Switch
X = No Flow Switch
M = Dyna-View/Thai
A = Evaporator (NEMA 1)
B = Evaporator and Condenser (NEMA 1)
C = Evaporator (NEMA 4)
D = Evaporator and Condenser (NEMA 4)
Digit 47 – Digital Communication Interface
X = None
4 =Tracer Interface
5 = LCI-C (LonTalk)
RLC-PRC020-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
General Data
Nominal Data
Nominal Compressor
Tonnage (60 Hz)
B1
175-200
B2
200-225
C1
225-275
C2
275-325
D1
325-400
D2
375-450
D3
N/A
E3
N/A
Tonnage (50 Hz)
125-150
150-175
175-225
225-275
275-325
300-350
325-375 375-450
Notes:
1. Chiller selections can be optimized through the use of the ARI-Certified Series R selection program and by contacting your local
Trane sales office.
General Data
Evaporator
Water Storage
Condenser
Water Storage
Refrigerant
Charge
Compressor
Evaporator
Code
B1
Condenser
Code
B1
Refrigerant
Type
Code
B1
B1
B2
B2
C1
C1
C1
C2
C2
C2
D1
D1
Gallons
41
55
45
58
45
52
82
52
Liters
155
208
170
220
170
197
310
197
295
405
261
386
515
545
280
405
545
602
280
405
545
602
Gallons
Liters
106
117
110
129
110
121
226
121
178
231
166
216
299
344
178
231
299
367
178
231
299
367
lb
kg
186
222
186
222
222
222
238
222
222
284
216
284
---
318
216
284
---
318
216
284
---
28
31
29
34
29
32
60
32
47
61
44
57
79
91
47
61
79
97
47
61
79
97
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
HFC-134a
410
490
410
490
490
490
525
490
490
625
475
625
---
700
475
625
---
700
475
625
---
C1
B2
C2
D6
D5
E1
D4
D3
F2
D1
F1
G1
G2
D2
D1
B2
D2
E5
E4
F1
E4
E3
F3
E1
F2
G1
G2
E2
78
107
69
102
136
144
74
107
144
159
74
1
D1
D12
D2/D3
D2/D3
D2/D31
D2/D32
E3
F2
F3
G2
G3
D2
F2
G2
G3
G1
G3
E2
F3
G1
G3
E3
107
144
159
1
E3
2
E3
700
318
Notes:
1. 50 Hz units only.
2. 60 Hz units only.
16
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General Data Water Flow Rates
Minimum/Maximum Evaporator Flow Rates (Gallons/Minute )
TwoPass
Three Pass
Four Pass
Evaporator
Code
B1
Nominal
Max Conn Size (In.)
Nominal
Max Conn Size (In.)
Nominal
Conn Size (In.)
Min
253
288
320
347
415
450
486
351
351
293
450
563
604
—-
Min
168
192
213
232
275
300
324
234
234
196
300
376
404
505
550
622
Min
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
379
411
466
Max
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
1104
1266
1412
1531
1812
1980
2131
1542
1542
1287
1980
2478
2667
—-
8
8
8
8
8
8
8
8
8
8
8
10
10
—-
—-
—-
736
844
941
6
6
6
6
8
8
8
8
8
8
8
8
8
10
10
10
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
8
B2
C1
C2
D1
D2
D3
D4
D5
D6
E1
F1
F2
G1
G2
G3
1022
1206
1320
1417
1028
1028
860
1320
1655
1780
2218
2413
2732
—-
1666
1807
2050
—-
—-
—-
—-
8
8
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Minimum/Maximum Evaporator Flow Rates (Liters/Second)
TwoPass
Three Pass
Four Pass
Evaporator
Code
B1
Nominal
Max Conn Size (mm) Min
Nominal
Max Conn Size (mm) Min
Nominal
Max Conn Size (mm)
Min
16
18
20
22
26
28
31
22
22
18
28
36
38
—-
—-
—-
70
80
89
200
200
200
200
200
200
200
200
200
200
200
250
250
—-
11
12
13
15
17
19
20
15
15
12
19
24
25
32
35
39
46
53
59
65
76
83
89
65
65
54
83
104
112
140
152
172
150
150
150
150
200
200
200
200
200
200
200
200
200
250
250
250
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
24
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
105
114
129
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
200
200
200
B2
C1
C2
D1
D2
D3
D4
D5
D6
E1
F1
F2
G1
G2
G3
97
114
125
134
97
97
81
125
156
168
—-
—-
—-
—-
—-
26
29
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Minimum/Maximum Condenser Flow Rates
Minimum/Maximum Condenser Flow Rates
(Gallons/Minute)
(Liters/Second)
Two Pass
Two Pass
Condenser
Code
B1
Nominal
Condenser
Code
B1
Nominal
Min
193
212
193
212
291
316
325
245
206
375
355
385
444
535
589
Max
850
935
850
935
1280
1390
1420
1080
910
1650
1560
1700
1960
2360
2600
Conn Size (In.)
Min
12
13
12
13
18
20
21
15
13
24
22
24
28
34
37
Max Conn Size (mm)
54
59
54
59
81
88
90
68
57
104
98
107
124
149
164
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8
150
150
150
150
200
200
200
200
200
200
200
200
200
200
200
B2
D1
D2
E1
E2
E3
E4
E5
F1
F2
F3
G1
G2
G3
B2
D1
D2
E1
E2
E3
E4
E5
F1
F2
F3
G1
G2
G3
Notes:
Notes:
1. Minimum flow rates are based on water only.
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
2. All water connections are grooved pipe.
RLC-PRC020-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
General Data
Brine Flow Rates
Minimum/Maximum Evaporator Flow Rates (GPM)
TwoPass
Three Pass
Four Pass
Evaporator
Code
B1
Nominal
Max Conn Size (In.)
Nominal
Max Conn Size (In.)
Nominal
Conn Size (In.)
Min
303
346
346
375
498
541
584
422
422
352
487
676
725
—-
Min
200
233
254
276
330
357
389
281
281
233
357
454
487
606
660
747
Min
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
454
492
557
Max
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
1104
1266
1412
1531
1812
1980
2131
1542
1542
1287
1980
2478
2667
—-
8
8
8
8
8
8
8
8
8
8
8
10
10
—-
—-
—-
736
844
941
6
6
6
6
8
8
8
8
8
8
8
8
8
10
10
10
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
8
B2
C1
C2
D1
D2
D3
D4
D5
D6
E1
F1
F2
G1
G2
G3
1022
1206
1320
1417
1028
1028
860
1320
1655
1780
2218
2413
2732
—-
1666
1807
2050
—-
—-
—-
—-
8
8
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
Minimum/Maximum Evaporator Flow Rates (Liters/Second)
TwoPass
Three Pass
Four Pass
Evaporator
Code
B1
Nominal
Max Conn Size (mm) Min
Nominal
Max Conn Size (mm) Min
Nominal
Max Conn Size (mm)
Min
19
70
80
89
200
200
200
200
200
200
200
200
200
200
200
250
250
—-
13
15
16
17
21
23
25
18
18
15
23
29
31
38
42
47
46
53
59
65
76
83
89
65
65
54
83
104
112
140
152
172
150
150
150
150
200
200
200
200
200
200
200
200
200
250
250
250
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
29
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
105
114
129
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
—-
200
200
200
B2
C1
C2
D1
D2
D3
D4
D5
D6
E1
F1
F2
G1
G2
G3
22
22
23
31
34
37
27
27
22
28
43
46
—-
—-
—-
97
114
125
134
97
97
81
125
156
168
—-
—-
—-
—-
—-
31
35
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
Minimum/Maximum Condenser Flow Rates
Minimum/Maximum Condenser Flow Rates
(Liters/Second)
(GPM)
Two Pass
Two Pass
Condenser
Code
B1
Nominal
Condenser
Code
B1
Nominal
Conn Size (In.)
Min
15
16
15
16
22
24
25
19
16
28
27
29
33
41
45
Max Conn Size (mm)
54
59
54
59
81
88
90
68
57
104
98
107
124
149
164
Min
230
255
230
255
350
380
390
295
250
450
430
460
530
650
710
Max
850
935
850
935
1280
1390
1420
1080
910
1650
1560
1700
1960
2360
2600
150
150
150
150
200
200
200
200
200
200
200
200
200
200
200
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8
B2
D1
D2
E1
E2
E3
E4
E5
F1
F2
F3
G1
G2
G3
B2
D1
D2
E1
E2
E3
E4
E5
F1
F2
F3
G1
G2
G3
Notes:
Notes:
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
1. Minimum flow rates are based on brine solution.
2. All water connections are grooved pipe.
18
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Data
and Connections
Compressor Motor Electrical Data (60 Hertz)
NominalVoltage
Voltage
200
180/
220
230
208/
254
174
484
818
2617
249
698
380
342/
418
174
291
488
1561
249
421
460
414/
506
174
241
400
1280
249
349
575
516/
633
174
193
329
1053
249
279
375
1162
329
367
612
1984
Compressor
Code
Utilization Range
Max kW
174
B1, B2
RLA @ Max kW
LRAY
557
970
LRAD
Max kW
RLA @ Max kW
LRAY
LRAD
Max kW
RLA @ Max kW
LRAY
3103
249
C1, C2
812
1173
3634
329
888
1690
5477
936
558
469
2901
329
888
1532
4966
1727
329
549
850
2755
1453
329
455
730
2366
D1, D2
Notes:
LRAD
1. See Selection Procedure Section for details.
2.The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.
3. Electrical component sizing should be based on actual jobsite operating conditions.This factor can be obtained through the
use of the Series R chiller selection program available through localTrane sales offices.
Compressor Motor Electrical Data (50 Hertz)
NominalVoltage
Voltage
380
342/
418
139
233
391
1229
201
349
456
1414
271
455
711
400
360/
440
145
233
412
1296
209
349
480
1488
280
455
748
2424
301
488
748
2424
415
374/
457
148
233
428
1348
213
349
498
1544
284
455
776
2515
306
488
776
2515
Compressor
Code
Utilization Range
Max kW
RLA @ Max kW
LRAY
B1, B2
LRAD
Max kW
RLA @ Max kW
LRAY
C1, C2
LRAD
Max kW
D1, D2, D3
RLA @ Max kW
LRAY
LRAD
2303
288
488
711
Max kW
E3
RLA @ Max kW
LRAY
LRAD
2303
Notes:
1. See Selection Procedure Section for details.
2.The RLA @ Max kW is based on the performance of the motor developing full rated horsepower.
3. Electrical component sizing should be based on actual jobsite operating conditions.This factor can be obtained through the
use of the Series R chiller selection program available through localTrane sales offices.
Electrical Connections
Starter Panel
Connection
Selection
RLA
Lug Size
L1-L3 (Each Phase)
(2) #4-500 MCM
(4) 4/0-500 MCM
(1) #4-350 MCM
(2) 2/0-250 MCM
(2) 3/0-350 MCM
(2) #1-500 MCM
(4) 4/0-500 MCM
Terminals Only
000-760
761-888
000-185
186-296
297-444
445-592
593-888
Main Circuit
Breaker or
Non-Fused
Disconnect Switch
Note:
1. Lug sizes are independent of starter type.
RLC-PRC020-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Data
and Connections
20
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Data
and Connections
RLC-PRC020-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
Shipping and Operating Weights
Compressor
Code
B1
Evaporator
Code
B1
Condenser
Code
B1
OperatingWeight
ShippingWeight
(lbs)
(kg)
(lbs)
(kg)
9,867
10,554
10,019
10,653
13,397
13,673
15,818
13,672
15,044
17,560
15,385
17,537
20,500
21,065
15,570
18,220
20,700
21,641
15,728
18,356
20,800
4,476
4,787
4,545
4,832
6,077
6,202
7,175
6,201
6,824
7,965
6,978
7,955
9,299
9,555
7,062
8,264
9,389
9,816
7,134
8,326
9,435
9,292
4,215
4,462
4,265
4,515
5,797
5,884
6,676
5,884
6,351
7,334
6,551
7,342
8,437
8,667
6,605
7,629
8,482
8,849
6,677
7,691
8,528
B1
B2
B2
C1
C1
C1
C2
C2
C2
D1
D1
D1
C1
B2
C2
D6
D5
E1
D4
D3
F2
D1
F1
G1
G2
D2
D1
B2
D2
E5
E4
F1
E4
E3
F3
E1
F2
G1
G2
E2
9,837
9,402
9,953
12,780
12,973
14,718
12,972
14,002
16,168
14,443
16,187
18,600
19,107
14,562
16,820
18,700
19,508
14,720
16,956
18,800
D1
D2, D3
D2, D3
D2, D3
D2, D3
E3
F2
F3
G2
G3
D2
F2
G2
G1
G3
E2
F3
G1
E3
E3
E3
G3
G3
21,786
9,882
19,653
8,914
Notes:
1. All weights +- 3%.
2. Shipping weights include standard 150 psig water boxes, refrigerant charge, and oil charge.
3. Operating weights include refrigerant, oil, and water charges.
22
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
BBB Configuration
Recommended Clearances
36" (914 mm)
Front
Back
36" (914 mm)
Either End
Other End*
Top
36" (914 mm)
108" (2743 mm)
36" (914 mm)
* Clearance for tube removal
Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to
submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each
compressor.
RLC-PRC020-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
BCD Configuration
Recommended Clearances
36" (914 mm)
Front
Back
36" (914 mm)
Either End
Other End*
Top
36" (914 mm)
126" (3200 mm)
36" (914 mm)
* Clearance for tube removal
Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to
submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each
compressor.
24
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
CDE, DDE, EDE Configuration
Recommended Clearances
Front
Back
Either End
Other End*
36" (914 mm)
36" (914 mm)
36" (914 mm)
108" (2743 mm)
36" (914 mm)
Top
* Clearance for tube removal
Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to
submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each
compressor.
RLC-PRC020-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
CEF Configuration
Recommended Clearances
36" (914 mm)
Front
Back
36" (914 mm)
Either End
Other End*
Top
36" (914 mm)
126" (3200 mm)
36" (914 mm)
* Clearance for tube removal
Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to
submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each
compressor.
26
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
CFF, DFF, EFF Configuration
Recommended Clearances
Front
Back
Either End
Other End*
36" (914 mm)
36" (914 mm)
36" (914 mm)
126" (3200 mm)
36" (914 mm)
Top
* Clearance for tube removal
Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to
submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each
compressor.
RLC-PRC020-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and
Weights
DGG, EGG Configuration
Recommended Clearances
Front
Back
Either End
Other End*
36" (914 mm)
36" (914 mm)
36" (914 mm)
126" (3200 mm)
36" (914 mm)
Top
* Clearance for tube removal
Note:
1. Dimensions are based on 3 Pass Evap / 2 Pass
Cond and LH/LH water connections. Refer to
submittals for exact configuration.
2. Refer to the Nominal Capacity Data table in the
General Data section for capacity ranges of each
compressor.
28
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
General
All water pass arrangements are
The display will identify the fault, indicate
date, time, and operating mode at time of
occurrence, and provide type of reset
required and a help message.The
diagnostic history will display the last ten
diagnostics with their times and dates of
occurrence.
Exposed metal surfaces are painted with
air-dry beige, direct-to-metal, single-
component paint. Each unit ships with full
operating charges of refrigerant and oil.
Molded neoprene isolation pads are
supplied for placement under all support
points. Startup and operator instruction
by factory-trained service personnel are
included.
available with grooved connections (150
or 300 psig waterside). All connections
may be either right- or left-handed.
Waterside shall be hydrostatically tested
at 1.5X design working pressure.
Refrigerant Circuit
An electronically controlled expansion
valve is provided to maintain proper
refrigerant flow.
Clear Language Display Panel
Factory-mounted to the control panel
door, the operator interface has an LCD
touch-screen display for operator input
and information output.This interface
provides access to the following
information: evaporator report,
condenser report, compressor report,
ASHRAE Guideline 3 report, operator
settings, service settings, service tests,
and diagnostics. All diagnostics and
messages are displayed in “clear
language.”
Compressor and Motor
Unit Controls (CH530)
The unit is equipped with a semi-
hermetic, direct-drive, 3600-rpm (3000
rpm @ 50 Hz) rotary compressor that
includes a capacity control slide valve, oil
sump heater, and differential pressure
refrigerant oil flow system. Four
pressure-lubricated, rolling-element
bearing groups support the rotating
assembly.
The microprocessor-based control panel
is factory-installed and factory-tested.The
control system is powered by a control
power transformer, and will load and
unload the chiller through adjustment of
the compressor slide valve.
Microprocessor-based chilled water reset
based on return water is standard.
The CH530 microprocessor automatically
acts to prevent unit shutdown due to
abnormal operating conditions
associated with low evaporator
refrigerant temperature, high condensing
temperature, and/or motor current
overload. If an abnormal operating
condition continues and the protective
limit is reached, the machine should shut
down.
The motor is a suction gas-cooled,
hermetically sealed, two-pole, squirrel
cage induction-type.
Data contained in available reports
includes:
•Water and air temperatures
• Refrigerant levels and temperatures
• Oil pressure
• Flow switch status
• EXV position
• Head pressure control command
• Compressor starts and run-time
• Line phase percent RLA, amps, and
volts
Unit-Mounted Starter
The unit is supplied with a NEMA 1 type
enclosure with top power-wiring access
and three-phase, solid state overload
protection.The starter is available in a
Wye-Delta configuration, factory-
mounted and fully pre-wired to the
compressor motor and control panel. A
factory-installed, factory-wired 600VA
control power transformer provides all
unit control power (120VAC secondary)
and CH530 module power (24VAC
secondary). Optional starter features
include circuit breakers, ground fault
circuit breakers, and mechanical, non-
fused disconnects.
The panel includes machine protection
shutdown requiring manual reset for the
following conditions:
• low evaporator refrigerant temperature
and pressure
• high condenser refrigerant pressure
• low oil flow
• critical sensor or detection circuit faults
• motor current overload
• high compressor discharge temperature
• lost communication between modules
• electrical distribution faults: phase loss,
phase imbalance, or phase reversal
• external and local emergency stop
• starter transition failure
All necessary settings and setpoints are
programmed into the microprocessor-
based controller via the operator
interface.The controller is capable of
receiving signals contemporaneously
from a variety of control sources, in any
combination, and priority order of control
sources can be programmed.The control
source with priority determines active
setpoints via the signal it sends to the
control panel. Control sources may be:
• the local operator interface (standard)
• a hard-wired 4-20 mA or 2-10VDC
signal from an external source
(interface optional; control source not
supplied)
Evaporator and Condenser
Shells are carbon steel plate.The
evaporator and condenser are designed,
tested, and stamped in accordance with
ASME Code for refrigerant-side/
working-side pressure of 200 psig.
The panel also includes machine
protection shutdown with automatic
reset for the following correctable
conditions:
• momentary power loss
• under/over voltage
All tube sheets are made of carbon steel;
tubes are mechanically expanded into
tube sheets and mechanically fastened to
tube supports. Evaporator tubes are 1.0-
inch (25.4 mm) diameter and condenser
tubes are 0.75-inch
(19.05 mm) diameter. Both types can be
individually replaced. Standard tubes are
externally finned, internally enhanced
seamless copper with lands at all tube
sheets.
• Generic BAS (optional points; control
source not supplied)
• LonTalk LCI-C (interface optional; control
source not supplied)
• loss of evaporator or condenser water
flow
•TraneTracer Summit™ system (interface
optional)
When a fault is detected, the control
system conducts more than 100
diagnostic checks and displays results.
RLC-PRC020-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
ConversionTable
30
RLC-PRC020-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
RLC-PRC020-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
RLC-PRC020-EN
PL-RF-RLC-000-PRC020-EN-0606
RLC-PRC020-EN-00406
Inland
Supersedes
Trane
A business ofAmerican Standard Companies
Stocking Location
For more information, contact
your local sales office or
e-mail us at [email protected].
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.