Packaged Cooling with
Electric Heat Rooftop Units
Voyager™
12½ - 25Tons - 60 Hz
RT-PRC002-EN
October 2004
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
2
4
Introduction
Features and Benefits
Application Considerations
9
10
12
13
Selection Procedure
Model Number Description
General Data
17
Performance Data
17
31
47
Cooling Performance
Fan Performance
Heat Performance
Controls
49
50
70
81
Electric Power
Dimension andWeights
Mechanical Specifications
RT-PRC002-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Factory Installed Options
• Black Epoxy Pre-Coated Coils
• Dehumidification Option
• High Efficiency Motors
• High Pressure Cutout
• Hinged Access Doors
• Novar Unit Controls
Factory or Field Installed Options
• Clogged Filter/Fan Failure Switch
• Differential Pressure Switches
• Discharge Air Sensing Kit
• Downflow – Economizer
• Electric Heaters
• Frostat
• Novar Return Air Sensor
• Powered or Unpowered Convenience
Outlet
• Supply and/or Return Air Smoke
Detector
• LonTalk® Communications Interface
• Oversized Motors
• Reference or Comparative Enthalpy
• Tool-less Hail Guards
• Trane Communications Interface (TCI)
• Thermal ExpansionValve/Face-Split
Evaporator Coil Option
• Through the Base Electrical with Circuit
Breaker
• Through the Base ElectricalWith
Disconnect Switch
• Through the Base Utilities Access
• Two-Inch Pleated Filters
Field Installed Options
• CO2 Sensing
• Digital Display Zone Sensor
• DualThermistor Remote Zone Sensor
• Low Static Drive
• High Static Drive
• Manual Outside Air Damper
• Motorized Outside Air Dampers
• Powered Exhaust
• Downflow – Roof Curb
• Horizontal – Economizer
• Remote Potentiometer
• Ventilation Override Accessory
• Zone Sensors
RT-PRC002-EN
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Quality and Reliability are enhanced
through ReliaTel control and logic:
ReliaTel MakesTesting Easy
Easy to Install, Service and
Maintain
ReliaTel requires no special tools to run
theVoyager unit through its paces.
Simply place a jumper betweenTest 1
andTest 2 terminals on the LowVoltage
Terminal Board and the unit will walk
through its operational steps
automatically.
—prevents the unit from short cycling,
considerably improving
compressor life.
Because today’s owners are very cost-
conscious when it comes to service and
maintenance, theTrane Voyager was
designed with direct input from service
contractors.This valuable information
helped to design a product that would get
the serviceman off the job quicker and
save the owner money.Voyager does
this by offering:
—ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
—The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
Voyager with ReliaTel reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
Quality and Reliability
ReliaTel™ Controls (LCI-R)
As long as the unit has power and the
“system on” LED is lit, ReliaTel is
operational.The light indicates that the
controls are functioning properly.
ReliaTel Makes Installing and
Servicing Easy
ReliaTel eliminates the need for field
installed anti-shortcycle timer and time
delay relays. ReliaTel controls provide
these functions as an integral part of the
unit.The contractor no longer has to
purchase these controls as options and
pay to install them.
ReliaTel features expanded diagnostic
capabilities when utilized withTrane
Integrated Comfort™ Systems.
Some zone sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
The wiring of the low voltage connections
to the unit and the zone sensors is as
easy as 1-1, 2-2, and 3-3.This simplified
system makes wiring easier for the
installer.
Other ReliaTel Benefits
ReliaTel controls provide unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.
The ReliaTel built-in anti-shortcycle timer,
time delay relay and minimum “on” time
control functions are factory tested to
assure proper operation.
ReliaTel softens electrical “spikes” by
staging on fans, compressors and
heaters.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate at
predetermined temperature setpoint.
ReliaTel™
Intelligent Anticipation is a standard
ReliaTel feature. It functions continuously
as ReliaTel and zone sensor(s) work
together in harmony to provide much
tighter comfort control than conventional
electro-mechanical thermostats.
The same ReliaTel Board fits allVoyager
Packaged Gas/Electrics, Cooling with
Electric Heat, and Heat Pump models.
This provides standardization of parts for
contractors. Less money is tied up in
inventory with ReliaTel.
RT-PRC002-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Condenser Coil
High Static Drive Accessory
Outstanding Standard and
Optional Components
Voyager boasts a patent-pending 1+1+1
condenser coil, permanently gapped for
easy cleaning.
Available on many models, this high
static drive accessory extends the
capability of the standard motor. Avoid
expensive motors and operating costs by
installing this optimized sheave
accessory.
Black Epoxy Pre-Coated Coils
The pre-coated coils are an economical
option for protection in mildly corrosive
environments.
Hinged Access Doors
Cabinet Integrity
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.
For added water integrity, Voyager has a
raised 11/ " lip around the supply and
return of8the downflow units to prevent
water from blowing into the ductwork.
Clogged Filter/Fan Failure Switch
LonTalk® Communications Interface
The LonTalk communications interface
allows the unit to communicate as a
Tracer™LCI-V device or directly with
generic LonTalk Network Building
Automation System Controls.
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
CO2 Sensing
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.The CO
sensor kit is available as a field installed2
accessory.
Digital Display Zone Sensor
Power Exhaust Option
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors. This sensor
should be utilized with ReliaTel™ controls.
This option is available on downflow units
and provides exhaust of the return air,
when using a downflow economizer, to
maintain proper building pressurization.
Great for relieving most building
overpressurization problems.
Discharge Air Sensing Kit
Provides true discharge air sensing in
heating models. The kit is functional only
with the ReliaTel Options Module.
Quick-Access Panels
ColoredAnd NumberedWiring
Save time and money tracing wires and
diagnosing the unit.
Remove three or fewer screws for
access to the standardized internal
components and wiring.
DownflowAnd Horizontal Economizers
The economizers come with three control
options — dry bulb is standard, enthalpy
and differential enthalpy are optional.
Compressors
Quick-Adjust Idler Arm
Voyager contains the best compressor
technology available to achieve the
highest possible performance. Dual
compressors are outstanding for
humidity control, light load cooling
conditions and system back-up
applications. Dual compressors are
available on all models.
With the Quick-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.
DualThermistor Remote Zone Sensor
This sensor will reduce the total number
of remote sensors to obtain space
temperature averaging. This sensor
should be utilized with ReliaTel controls.
Factory Built Roof Curbs
Available for downflow units. Only two
roof curbs for the entireVoyager line
simplifies curb selection.
Refrigerant Circuits
AllVoyager 12½-25 ton units shall have
crankcase heaters, low and high pressure
controls as standard.
Fresh Air
0 - 25% manual or 0 - 50% motorized
outside air hoods are available.
RT-PRC002-EN
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Reference or Comparative Enthalpy
Measures and communicates humidity
while maximizing comfort control.
VariTrac
Actual shipping tests were performed to
determine packaging requirements. Units
were test shipped around the country to
determine the best packaging. Factory
shake and drop tests were used as part
of the package design process to help
assure that the unit arrives at the job site
in top condition.
WhenTrane’s changeover VAV System
for light commercial applications is
coupled withVoyager, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
Sloped Drain Pans
Standard on every unit.
Standardized Components
Components are placed in the same
location on allVoyager units. Familiarize
yourself with oneVoyager and you are
familiar with every Voyager.
Ventilation Override Accessory
Rigging tests include lifting a unit into the
air and letting it drop one foot, assuring
that the lifting lugs and rails hold up under
stress.
With theVentilation Override Accessory
installed, the unit can be set to transition
to up to 3 different pre-programmed
sequences for Smoke Purge,
Due to standardized components
throughout theVoyager line, contractors/
owners can stock fewer parts.
We perform a 100% coil leak test at the
factory.The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
Pressurization, and Exhaust.The
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.The ventilation override kit is
available as a field installed accessory.
Supply and/or Return Air Smoke
Detector
With this option installed, if smoke is
detected, all unit
All parts are inspected at the point of final
assembly. Sub-standard parts are
identified and rejected immediately.
operation will be shut
down. Reset will be
manual at the unit.
Return Air Smoke
Detectors require
minimum allowable
airflow when used
with certain models.
Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorousTrane
requirements.
Zone Sensors
Available in programmable, automatic
and manual styles.
Rigorous Testing
Voyager units incorporate either a one
piece top or theTrane-Tite-Top (T3). Each
part of the top (either two or three pieces)
overlaps in such a way that water cannot
leak into the unit.These overlapped edges
are gasketed and sealed to ensure
superior water integrity.
The fan and idler arm assembly designs
have been tested to over 300,000 cycles
each. Our combined cycle testing is now
over 7,000,000 cycles.
Tool-less Hail Guards
Tool-less, hail
protection quality coil
guards shall be either
All of Voyager’s designs were rigorously
rain tested at the factory to ensure water
integrity.
factory or field-installed for condenser
coil protection.This option protects the
condenser coil from vandalism and/or
hail damage.
VariTrac™
Trane Communication Interface (TCI)
Available factory or field installed.This
module when applied with the ReliaTel™
easily interfaces withTrane’s Integrated
ComfortTM System.
RT-PRC002-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Powered or Unpowered Convenience
Outlet
Factory Installed Options
A wide variety of Factory Installed
Options (FIOPs) are available.
Easy to Install and Service
Conversionless Units
The dedicated design units (either
downflow or horizontal) require no panel
removal or alteration time to convert in
the field — a major cost savings during
installation.
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered.This option can only be
ordered when theThrough the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered.This option is available on all
downflow models.
Added Efficiency
Airflow
Airflow is outstanding.TheVoyager can
replace an older machine with old
ductwork and, in many cases, improve
the comfort through better air
distribution.
Horizontal units come complete with duct
flanges so the contractor doesn’t have to
field fabricate them.These duct flanges
are a time and cost saver.
High Efficiency Motors
Easy Access LowVoltageTerminal Board
Voyager’s LowVoltageTerminal Board is
external to the electrical control cabinet. It
is extremely easy to locate and attach the
thermostat wire.This is another cost and
time saving installation feature.
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.
U-shaped Airflow
U-shaped airflow allows for improved
static capabilities.
LowAmbient Cooling
Cooling capabilities down to 0°F as
standard.
Oversized Motors
Factory or field installed oversized
motors available for high static
applications.
One of our FinestAssets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
Single Point Power
A single electrical connection powers the
unit.
Single Side Service
Single side service is standard on all
units.
— Application
LowVoltage Connections
— Service
— Training
The wiring of the low voltage connections
to the unit and the zone sensors is as
simple as 1-1, 2-2, and 3-3.This simplified
system makes it easy for the installer to
wire.
— Special Applications
— Specifications
Through the Base Electrical with Circuit
Breaker
This option is a factory installed thermal
magnetic, molded case, HACR Circuit
Breaker with provisions for through the
base electrical connections. This option is
available on all downflow models.
— Computer Programs and much more
Voyager has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its U-shaped airflow
performance is outstanding.
Through the Base Electrical with
Disconnect Switch
Factory installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available. This option is available on
all downflow models.
Through the Base UtilitiesAccess
Electric Heaters
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.
Electric heat modules are available within
the basic unit. If ordering theThrough the
Base Electrical option with an Electrical
Heater, the heater must be factory
installed.
RT-PRC002-EN
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Power Exhaust Accessory
The power exhaust accessory is available
on all 12½-25 ton downflow units.This
accessory can be field installed and will
assist in relieving building pressurization.
LowAmbient Cooling
ThisVoyager line features, as standard,
low ambient cooling down to 0°F. The
following options need to be included/
considered when low ambient
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
applications are required: continuous fan
operation, crankcase heaters, thermal
expansion valves, frostat. Contact your
localTrane Representative for more
assistance with low ambient cooling
applications.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the localTrane
sales personnel.
Barometric Relief
This product line offers an optional
barometric relief damper included in the
downflow economizer accessory.This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers and
relieving the conditioned space.
Unit Pitch
These units have sloped condensate
drain pans. Units must be installed level,
any unit slope must be toward access
side of unit.
NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDEREDTO
CONTROL BUILDING PRESSURIZATION.
RT-PRC002-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedures
Step 5
To Find Capacity at Intermediate
Conditions Not in theTable
Cooling Capacity
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
If the performance will not meet the
required load of the building -total or
sensible cooling load, try a selection at
the next higher size unit.
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
Heating Capacity
Step 1
Calculate the building heating load using
theTrane calculation form or other
standard accepted method.
Factors used in unit selection:
A
Step 4
Total Cooling Load: 180 MBh
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount of
heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure.To determine the
total unit static pressure you add the
external static pressure to the additional
static related by the added features:
B
Sensible Cooling Load: 129 MBh
Step 2
C
Size the system heating capacity to
Airflow: 6000 cfm
match the calculated building heating
D
load.The following are building heating
Electrical Characteristics: 460/60/3
requirements:
A
E
Summer Design Conditions: Entering
Total heating load of 115.0 MBH
Evaporator Coil: 80 DB, 67WB Outdoor
Ambient: 95 DB
B
6000 cfm
F
C
External Static (duct system)
0.49 wg
External Static Pressure: 0.49 in. wg
460 volt/3 phase Power Supply
G
Standard Filter 1 in.
fromTable PD-35
0.10 wg
Rooftop - downflow configuration
The electric heat accessory capacities are
listed inTable PD-36. From the table, a 36
kw heater will deliver 122.94 MBH at 480
volts. In order to determine capacity at
460 volts, the heater voltage correction
factor fromTable PD-37 must be used.
Therefore, 122.94 MBH x .94 (voltage
correction factor) = 115.6 MBH.
H
Accessories
• Roof curb
Economizer
0.04 wg
• Economizer
(100% Return Air) fromTable PD-35
• Electric Heat
I
Heating
Electric Heater Size 36 kw 0.07 wg
fromTable PD-35
• Capacity 115 MBh
• 460 volt/3 phase Electric Heat —at 6000
cfm
Air Delivery Selection
External static pressure drop through the
air distribution system has been
Total Static Pressure
0.60 wg
Step 2
As a starting point, a rough determination
must be made of the size of the unit.The
final selection will be made after
examining the performance at the given
conditions. Divide the total cooling load by
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
calculated to be 0.50 inches of water.
FromTable PD-35 static pressure drop
through the economizer is 0.04 and the
36 kw heater is 0.07 inches of water (0.49
+ 0.04 + 0.07). EnterTable PD-18 for a
TCD180B4 at 6000 cfm and 0.50 static
pressure.The standard motor at 777 rpm
will give the desired airflow at a rated bhp
of 2.71.
Note:The Evaporator Fan Performance
Table PD-18 has already accounted for
the pressure drop for standard filters and
wet coils (see note belowTable PD-18).
Therefore, the actual total static pressure
is 0.60 -0.10 (fromTable PD-35) = 0.50 wg.
With 6000 cfm and 0.50 wg.
Table PD-18 shows 2.56 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
3.15 x bhp = MBH.
3.15 x 2.56 = 8.06 MBH.
180 MBh / 12 MBh = 15.0Tons
Step 3
Table PD - 2 shows that aTCD180B4 has a
gross cooling capacity of 184 MBh and
130 MBh sensible capacity at 6000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
NetTotal Cooling Capacity
= 184 MBH - 8.06 = 175.9 MBH.
Net Sensible Cooling Capacity
= 130 MBH - 8.06 = 121.9 MBH.
RT-PRC002-EN
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Dehumidification Selection
68°F DB,
67°F WB
OA
Determine normal unit cooling and
heating capacities as previously
described in the selection procedures on
prior page.
75°F DB,
RA'
52% RH
MA' 72.2°F DB
65°F WB
OA
MA'
RA'
Typical 20 tonTFD241C
47°F DB
6400 cfmTotal Supply airflow
2560 cfm Outside Air (40%)
3840 cfm Return Air
SA'
73°F DB
SA
0.41” External Static Pressure
SA
REHEAT
SA'
OA Conditions
Part load day and raining
68°F db
67°F wb
Chart C-1
66.5 dp
95% RH
Step 3a: Determine leaving
evaporator temperature SA’
Leaving UnitTemperature = SA’
Step 5: Determine leaving unit
temperature with reheat active (SA)
Reheat temperature (obtained in step 3)
+ SA’ = SA
17.55°F db + 53.6°F = 71.2°F db
SA’=71.2°F
RA’ conditions
75°F db
Utilizing the manual selection method as
previously described and the formula
63°F wb
52% RH
55.9 dp
∆Temp = cooling capacity in Bth
51 wb
20.8 RH
29.4 dp
(cfm)(1.085)
Step 1: Determine the mixed/
entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
MA’ = (0.40*68°F) + (0.60*75°F)
MA’ = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
or using the TOPSS™ program
determine the leaving evaporator
temperature (temperature without the
addition of fan heat).
Consider Chart C-1. If the space relative
humidity is equal to or above the space
relative humidity setpoint, the
Dehumidification option will:
517.74 db
51.03 wb
• Energize compressor or both
compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.
Step 3b: Determine leaving unit
temperature in standard cooling
mode
Find the leaving unit temperature
including fan heat as discussed in prior
selection procedures and using the
temperature formula from Step 3a or
refer to yourTOPSS selection.
53.6 db
MA’
72.2°F db
64.7°F wb
Step 2: Determine static pressure
drop add for reheat
At MA’, air enters the RTU.The RTU filters,
cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 71°F (SA) supply air to the space.
Table PD-35 shows a static pressure drop
of 0.35” for the reheat coil and an
additional .04 for the mandatory 2”
pleated filters required when ordering the
dehumidification option.Total static
pressure =
51 wb
84% RH
49% dp
1.0+0.035+0.04=1.075
Step 4: Determine reheat
temperature rise
Using the leaving evaporator temp, go to
PD-39 and find the reheat temperature
rise for that particular cfm: 17.55°F db
(≅1.1 for manual calculations)
Do not forget to also add any additional
static from other accessories.
Table PD-29 (airflow table for 20 ton
dehumidification units) indicates that a
standard motor and drive is needed for
this airflow and static pressure range.
Note: Reheat temperature rise is based
on supply airflow and leaving
evaporator coil temperature.
RT-PRC002-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
Packaged Cooling with Electric Heat UnitTypical Model Nomenclature
T
C
D
1
5
0
C
3
0
0
A
A
1
2
3
4
5
6
7
8
9
10
11
12
Digits 1, 2 - Product Type
Digit 7- Major Development Sequence
Digit 8 - Electrical Characteristics
TC = Packaged Cooling, Electric
Heat
TF = With Factory Installed
Options
3 = 208-230/60/3
4 = 460/60/3
W= 575/60/3
K = 380/60/3
Digit 3 - Airflow Configuration
D = Downflow
H = Horizontal
Digit 9, 10 - Factory-Installed Options
00 = No Factory-installed Options
0A = Factory-installed Economizer
0B = Oversized Motor
Digits 4, 5, 6 - Nominal Gross Cooling
Capacity (MBh)
0C = Downflow Economizer and
Oversized Motor
0F = Trane Communications Interface
(TCI)
0G= Downflow Economizer and TCI
0H = TXV/Face-Split Evaporator
0J = Oversized Motor and TXV/Face-Split
Evaporator
150 =
151 =
180 =
181 =
210 =
211 =
240 =
241 =
300 =
301 =
12½ Tons Standard Efficiency
12½ Tons High Efficiency
15 Tons Standard Efficiency
15 Tons High Efficiency
17½ Tons Standard Efficiency
17½ Tons High Efficiency
20 Tons Standard Efficiency
20 Tons High Efficiency
0K = Downflow Economizer, Oversized
Motor, and TXV/Face-Split Evaporator
0L = Downflow Economizer with TXV/Face-
Split Evaporator
25 Tons Standard Efficiency
25 Tons High Efficiency
0M = Reheat Coil
0N= Downflow Economizer and Reheat
Coil
0P = Oversized Motor and Reheat Coil
0R = Downflow Economizer, Oversized
Motor and Reheat Coil
Digit 11- Minor Design Sequence
Digit 12- Service Digit
RT-PRC002-EN
12
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(12½, 15 Ton)
Standard Efficiency
Table GD - 1— General Data
12½Ton Downflow and Horizontal Units
TC*150D3, D4, DW, DK
15Ton Downflow and Horizontal Units
TC*180B3, B4, BW, BK
Cooling Performance1
Gross Cooling Capacity
EER2
150,000
9.8
182,000
9.9
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue3
System Power (KW)
Compressor
5,000/4,400
142,000
10.5
6,000/5,300
174,000
10.2
14.49
17.57
No./Type
2/Scrolls
9.2
Hi-Performance
.375
2/Scrolls
9.2
Hi-Performance
.375
Sound Rating (BELS)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
24.18
27.12
Rows/FPI
2/16
3/16
Indoor Coil —Type
Tube Size (in.)
Hi-Performance
.375
Hi-Performance
.375
Face Area (sq ft)
17.5
17.5
Rows/FPI
2/15
2/15
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,600
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,200
No. Motors/HP
2/.50
2/.50
Motor RPM
1,100
1,100
Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
15 x 15
Belt/1
1
15 x 15
Belt/1
1
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters —Type Furnished6
(No.) Size Recommended (in.)
Downflow
3.0/5.0
3.0/5.0
1,740/3,450
145T/145T
Throwaway
1,740/3,450
145T/145T
Throwaway
(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
9.3/9.4/Circuit
(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
17.5/9.5/Circuit
Horizontal
Refrigerant Charge (Lbs of R-22)5
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional2inchpleatedfiltersarealsoavailable.
7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(17½, 20, 25Ton)
Standard Efficiency
Table GD - 2 — General Data
17½Ton
20Ton
25Ton
Downflow and Horizontal Units
TC*210C3, C4, CW, CK
Downflow and Horizontal Units
TC*240B3, B4, BW, BK
Downflow and Horizontal Units
TC*300B3, B4, BW, BK
Cooling Performance1
Gross Cooling Capacity
EER2
210,000
9.8
242,000
9.7
290,000
9.7
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue3
System Power (KW)
Compressor
7,000/5,800
196,000
10.0
8,000/7,000
232,000
10.0
10,000/8,750
272,000
9.8
20.0
23.91
28.05
No./Type
2/Scrolls
9.4
Hi-Performance
.375
2/Scrolls
9.4
Hi-Performance
.375
2/Scrolls
9.4
Hi-Performance
.375
Sound Rating (BELS)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
27.12
35.30
36.43
Rows/FPI
3/16
3/16
2/16
Indoor Coil —Type
Tube Size (in.)
Hi-Performance
.375
Hi-Performance
.375
Hi-Performance
.375
Face Area (sq ft)
17.50
26.00
26.00
Rows/FPI
4/15
2/15
3/15
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
13,400
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
14,600
Short Orifice
1/1.00 NPT
Propeller
2/28
Direct/1
16,700
No. Motors/HP
2/1.0
2/1.0
2/1.0
Motor RPM
1,125
1,125
1,125
Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
15 x 15
Belt / 1
1
18 x 18
Belt / 1
1
18 x 18
Belt / 1
1
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters —Type Furnished7
(No.) Size Recommended (in.)
Downflow
5.0/7.5
5.0/7.5
7.5/NA
3,450/3,470
145T/184T
Throwaway
3,450/3,470
145T/184T
Throwaway
3,470/NA
184T/NA
Throwaway
(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
21.0/14.3/Circuit6
(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
Horizontal
Refrigerant Charge (Lbs of R-22)5
18.9/21.0/Circuit
17.0/Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary Large
Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit.
7. Optional two inch pleated filters are also available.
8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
14
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(12½, 15 Ton)
High Efficiency
Table GD - 3 — General Data
12½Ton
15Ton
Downflow and Horizontal
TC*151C3,C4,CW
Downflow and Horizontal
TC*181C3,C4, CW
Cooling Performance1
Gross Cooling Capacity
EER2
154,000
11.3
189,000
11.58
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue3
System Power KW
Compressor
5,000/4,400
146,000
11.5
6,000/5,300
180,000
13.3
12.92
15.653
No./Type
2/Scrolls
9.2
Hi-Performance
0.375
2/Scrolls
9.2
Hi-Performance
0.375
Sound Rating (BELS)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
27.12
35.30
Rows/FPI
3/16
3/16
Indoor Coil —Type
Tube Size (in.)
Hi-Performance
0.375
Hi-Performance
0.375
Face Area (sq ft)
17.50
26.00
Rows/FPI
3/15
3/15
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice9
1/1.0 NPT
Propeller
2/26
Short Orifice8
1/1.0 NPT
Propeller
2/26
Direct/1
10,400
Direct/1
11,000
No. Motors/HP
2/.50
2/.50
Motor RPM
1100
1100
Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
15 x 15
BELT/1
1
18 x 18
BELT/1
1
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters —Type/Furnished?
(No.) Size Recommended (in.)
3.0/5.0
3.0/5.0
1740/3450
145T/145T
Throwaway/Yes8
(2)20 x 20 x 2
(4)20 x 25 x 2
Hi-Performance
0.375
1740/3450
145T/145T
Throwaway/Yes8
(4) 20 x 20 x 2
(4) 20 x 25 x 2
Hi-Performance
0.375
Optional Hot Gas Reheat Coil —Type
Tube Size (in.) OD
Face Area (sq. ft.)
17.5
26
Rows/FPI
1/16
1/16
Refrigerant Charge (Lbs of R-22)5/Circuit
Standard
15.0/13.89
15.3/14.3
25.0/13.08
27.8/11.4
Optional Hot Gas Reheat Coil
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. Optional two inch pleated filters are also available for 12½ ton models.
9. TXV/Face-SplitOption(DownflowOnly)TCD151C3,4,W(RefrigerantControl):ExpansionValve;(RefrigerantCharge):13.4/12.0.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
(17½, 20, 25 Ton)
High Efficiency
General
Data
Table GD - 4 — General Data
17½Ton
20Ton
25Ton
Downflow and Horizontal
TC*211C3,C4,CW
Downflow and Horizontal
TC*241C3,C4,CW
Downflow and Horizontal
TC*301C3,C4,CW
Cooling Performance1
Gross Cooling Capacity
EER2
220,000
11.0
268,0009
10.6
300,00011
10.411
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue3
System Power KW
Compressor
7,000/6,200
208,000
12.0
8,000/7,000
250,0009
11.2
10,000/8,750
278,000
11.011
18.91
23.589
26.7311
No./Type
2/Scrolls
2/Scrolls
2/Scrolls
Sound Rating (BELS)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
9.4
9.4
Hi-Performance
0.375
9.4
Hi-Performance
0.375
Hi-Performance
0.375
35.30
35.30
Rows/FPI
3/16
3/16
3/16
Indoor Coil —Type
Tube Size (in.)
Hi-Performance
Hi-Performance
0.375
Hi-Performance
0.375
0.375
Face Area (sq ft)
26.000
26.00
26.00
Rows/FPI
4/15
Short Orifice
1 /1.0 NPT
Propeller
2/26
Direct/1
12,800
4/15
4/15
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice9
1/1.0 NPT
Propeller
2/26
Short Orifice11
1/1.0 NPT
Propeller
2/26
Direct/1
Direct/1
13,700
13,700
No. Motors/HP
2/1.00
2/1.00
2/1.00
Motor RPM
1125
1125
1125
Indoor Fan —Type
No. Used
FC Centrifugal
FC Centrifugal
1
FC Centrifugal
1
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
18 x 18
BELT/1
1
18 x 18
BELT/1
1
18 x 18
BELT/1
1
Motor HP (Standard/Oversized)
Motor RPM(Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters —Type Furnished7
(No.) Size Recommended (in.)
Optional Hot Gas Reheat Coil —Type
Tube Size (in.) OD
5.0/7.5
3450/3470
145T/184T
5.0/7.5
7.5/NA
3470/NA
184T/NA
3450/3470
145T/184T
Throwaway
(4/4)20 x 20 x 2/20 x 25 x 26
Hi-Performance
0.375
Throwaway
Throwaway
(4/4)20 x 20 x 2/20 x 25 x 26
(4/4)20 x 20 x 2/20 x 25 x 26
—
—
—
—
—
—
—
—
Face Area
Rows/FPI
26
1/16
Refrigerant Charge (Lbs of R-22)5 / Circuit
Standard
25.7/12.510
—
21.8/21.89
21.3/21.0
24.5/24.511
—
Optional Hot Gas Reheat Coil
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI
Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models have 8 - 20 x 25 x 2 filters.
7. Optional two inch pleated filters are also available.
8. TXV/Face-SplitOption(DownflowOnly)TCD181C3,4,W(EER):11.4;(SystemPowerkW):15.79;(RefrigerantControl):ExpansionValve;(RefrigerantCharge):26.0/12.0
9. TXV/Face-SplitOption(DownflowOnly)TCD241C3,4,W(GrossCoolingCapacity):259,000;(ARINetCoolingCapacity):244,000;(SystemPowerkW):23.02;
(RefrigerantControl):ExpansionValve;(RefrigerantCharge):21.5/22.2
10.TXV/Face-SplitOption(DownflowOnly)TCD211C3,4,WRefrigerantCharge):27.0/10.0
11. TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross Cooling Capacity): 294,000; (ARI Net Cooling Capacity): 272,000; (IPLV): 10.6; System Power kW): 27.2;
RefrigerantControl:ExpansionValve;(RefrigerantCharge):21.0/23.0
*Indicates both downflow and horizontal units.
RT-PRC002-EN
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½, 15Ton)
Standard Efficiency
Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK
AmbientTemperature
85
95
105
115
67
Enter
Dry
EnteringWet Bulb
67
CFM
Bulb
61
67
73
61
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5
80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6
80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0
75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9
80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0
80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0
4500
5000
5500
6000
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK
AmbientTemperature
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb
73 61
CFM
Bulb
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9
80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0
75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1
80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0
75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2
80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
5400
6000
6600
7200
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(17½, 20Ton)
Standard Efficiency
Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase TC*210C3, C4, CW, CK
AmbientTemperature
85
95
105
115
67
Enter
Dry
EnteringWet Bulb
67
CFM
Bulb
61
67
73
61
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8
80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0
90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0
75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4
80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0
85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0
90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0
80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0
85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0
90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5
80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0
85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0
90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0
6300
7000
7700
8400
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*240B3, B4, BW, BK
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5
80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0
85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0
90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0
75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1
80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0
85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0
90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0
75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6
80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0
85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0
90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0
75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2
80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0
85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0
90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0
7200
8000
8800
9600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(25Ton)
Standard Efficiency
Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase TC*300B3, B4, BW, BK
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
266 224 299 174 319 118 247 215 285 167 309 113 228 205 266 172 297 108 209 196 244 163 280 99.9
270 268 300 215 321 161 252 252 285 209 311 155 237 237 266 200 297 149 221 221 244 190 280 142
286 286 301 255 323 196 272 272 286 250 312 194 256 256 267 242 298 189 240 240 246 233 281 183
301 301 304 295 326 232 289 289 289 289 314 231 275 275 275 275 300 229 259 259 259 259 282 224
272 237 303 180 322 120 253 227 290 174 312 115 234 218 271 165 300 109 214 208 249 156 284 102
277 277 304 223 324 171 262 262 290 219 314 161 246 246 271 211 301 155 229 229 249 201 284 147
294 294 306 266 327 208 282 282 291 263 316 200 266 266 273 257 302 197 249 249 253 248 285 192
308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 235
275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188 301 111 216 214 251 178 285 103
282 282 306 227 325 174 267 267 292 223 315 162 250 250 273 216 302 157 233 233 251 206 286 150
298 298 308 272 328 216 286 286 294 270 317 203 270 270 276 264 304 200 253 253 256 255 286 196
312 312 311 311 330 256 301 301 301 301 320 244 288 288 288 288 306 244 273 273 272 272 288 241
278 248 306 185 324 123 258 239 293 181 315 118 239 229 275 172 302 113 217 217 253 184 286 104
286 286 308 231 325 160 271 271 294 228 316 163 254 254 276 221 304 160 237 237 253 212 287 153
301 301 310 277 327 224 289 289 296 276 319 205 274 274 278 271 305 204 257 257 257 257 288 200
314 314 314 314 330 266 304 304 304 304 321 248 291 291 291 291 307 249 276 276 276 276 289 246
9000
10000
10500
11000
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
(12½Ton)
High Efficiency
Performance
Data
Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*151C3, C4, CW— Standard Refrigeration System
AmbientTemperature
85
95
105
115
Enter
Dry
Bulb
EnteringWet Bulb
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0
4500
5000
5500
6000
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
20
Download from Www.Somanuals.com. All Manuals Search And Download.
(12½Ton)
High Efficiency
Performance
Data
Table PD-7 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase T*D151C3, C4, CW — Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature
85
95
105
115
Enter
Dry
Bulb
EnteringWet Bulb
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 123.8 88.0 138.9 73.4 155.2 55.8 118.2 84.4 132.8 70.1 148.6 52.6 112.1 80.7 126.2 66.6 141.5 49.2 105.6 76.8 119.1 62.8 133.8 45.6
80 123.9 100.8 139.0 85.5 155.2 69.8 118.3 97.3 132.9 82.0 148.7 66.4 112.1 93.3 126.3 78.3 141.5 62.8 105.7 89.6 119.2 74.4 133.9 59.0
85 124.0 113.6 139.1 98.3 155.3 82.5 118.5 110.1 133.0 94.7 148.8 79.1 112.5 106.3 126.4 91.0 141.6 75.4 104.3 104.3 119.3 87.1 134.0 71.6
90 126.0 124.6 139.0 110.8 155.4 95.2 120.6 120.6 133.0 107.2 148.8 91.7 115.5 115.5 126.4 103.5 141.7 88.0 110.3 110.3 119.4 99.5 134.1 84.2
75 133.0 99.5 148.7 80.0 165.5 59.1 126.7 95.9 141.9 76.4 158.2 55.7 120.0 91.9 134.7 72.5 150.4 52.2 112.8 87.8 126.9 68.5 142.0 48.5
80 133.1 115.7 148.8 96.0 165.6 76.1 126.9 112.0 142.1 92.4 158.3 72.5 120.2 108.1 134.8 88.6 150.5 68.8 113.2 104.1 127.0 84.5 142.1 64.9
85 132.7 132.7 148.8 111.9 165.7 92.0 128.6 126.0 142.1 108.2 158.4 88.4 122.5 121.6 134.8 104.3 150.6 84.7 116.2 116.2 127.1 100.4 142.3 80.7
90 139.8 139.8 148.9 127.6 165.7 107.7 134.5 134.5 142.2 124.0 158.4 104.1 128.9 128.9 135.0 120.1 150.7 100.5 122.8 122.8 127.5 116.3 142.4 96.5
75 139.3 109.8 155.4 86.2 172.5 61.7 132.6 106.1 148.2 82.5 164.7 58.3 125.4 102.0 140.4 78.6 156.4 54.7 117.8 97.8 132.2 74.5 147.6 50.9
80 139.6 128.9 155.5 105.4 172.6 81.5 133.1 125.4 148.3 101.7 164.8 77.8 126.2 121.5 140.6 97.7 156.5 74.0 119.0 115.2 132.3 93.6 147.7 70.1
85 143.2 143.2 155.5 124.1 172.8 100.5 137.6 137.6 148.3 120.4 165.0 96.8 131.5 131.5 140.7 116.6 156.7 93.0 125.0 125.0 132.4 112.5 147.8 89.0
90 151.0 151.0 156.1 143.3 172.8 119.2 145.3 145.3 149.0 139.6 165.0 115.6 139.0 139.0 141.6 136.1 156.7 111.7 132.4 132.4 134.0 129.4 147.9 107.6
75 142.5 116.0 158.8 90.2 176.0 63.3 135.6 112.2 151.3 86.4 168.0 59.8 128.2 108.3 143.3 82.4 159.5 56.2 120.4 104.1 134.9 78.2 150.4 52.4
80 143.3 137.5 158.8 111.1 176.2 84.8 135.1 135.1 151.4 107.3 168.1 81.1 130.0 127.1 143.5 103.5 159.6 77.3 122.7 122.1 135.0 99.3 150.5 73.3
85 149.0 149.0 159.0 131.9 176.3 105.6 143.1 143.1 151.6 128.2 168.2 101.9 136.7 136.7 143.6 124.2 159.8 98.2 129.9 129.9 135.2 120.1 150.7 94.2
90 157.2 157.2 160.1 153.3 176.4 126.4 151.1 151.1 151.1 151.1 168.3 122.6 144.6 144.6 145.9 142.5 159.7 118.6 137.6 137.6 138.2 137.5 150.8 114.8
75 145.1 121.9 161.6 93.7 179.0 64.7 138.1 118.3 154.0 89.9 170.8 61.2 130.5 114.2 145.8 85.9 162.0 57.3 122.6 110.1 137.1 81.7 152.7 53.3
80 145.6 145.6 161.6 116.5 179.2 87.9 140.4 138.6 154.0 112.8 170.9 84.2 133.1 133.1 145.8 108.8 162.1 80.3 126.2 126.2 137.1 104.5 152.9 76.3
85 154.1 154.1 162.0 139.4 179.3 110.7 147.9 147.9 154.4 135.7 171.0 106.9 141.3 141.3 146.3 131.7 162.2 103.0 134.2 134.2 137.7 127.6 153.1 99.2
90 162.6 162.6 162.5 162.5 179.5 133.2 156.3 156.3 157.1 154.9 171.2 129.5 149.5 149.5 149.4 149.4 162.4 125.5 142.2 142.2 142.2 142.2 153.1 121.5
75 147.5 127.8 164.0 97.2 181.5 66.0 140.3 124.0 156.2 93.3 173.1 62.2 132.6 119.9 147.8 89.3 164.1 58.4 124.6 116.0 138.9 85.1 154.7 54.3
80 150.2 149.4 164.1 121.8 181.7 90.9 143.5 143.5 156.2 117.9 173.2 87.1 136.8 136.8 147.9 114.0 164.3 83.2 129.7 129.7 139.0 109.8 154.8 79.2
85 158.5 158.5 164.6 146.7 181.8 115.5 152.1 152.1 156.8 142.9 173.4 111.8 145.3 145.3 148.6 139.0 164.4 107.8 138.0 138.0 140.0 134.9 154.9 103.7
90 167.4 167.4 167.9 167.1 182.1 139.9 160.8 160.8 160.7 160.7 173.6 136.1 153.8 153.8 153.7 153.7 164.6 132.2 146.3 146.3 146.2 146.2 155.1 128.2
75 149.6 133.5 165.9 100.3 183.7 67.0 142.2 129.6 158.0 96.4 175.1 63.2 134.4 125.6 149.5 92.5 166.0 59.4 126.4 121.7 140.5 88.3 156.4 55.3
80 153.4 153.4 166.1 126.9 183.8 93.6 147.0 147.0 158.1 123.0 175.2 90.0 140.2 140.2 149.6 118.9 166.1 86.1 132.8 132.8 140.6 115.0 156.5 82.0
85 162.5 162.5 166.9 153.7 183.9 120.1 155.9 155.9 159.1 150.0 175.3 116.3 148.8 148.8 148.7 148.7 166.2 112.5 141.3 141.3 142.4 138.6 156.6 108.4
90 171.6 171.6 171.6 171.6 184.3 146.4 164.8 164.8 164.7 164.7 175.7 142.6 157.6 157.6 157.5 157.5 166.5 138.7 149.9 149.9 149.9 149.9 157.0 134.7
2500*
3250*
4000*
4500
5000
5500
6000
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate
airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 4000 CFM
•
•
Electric heaters restricted on applications below 4000 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
(15Ton)
High Efficiency
Performance
Data
Table PD-8 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*181C3, C4, CW— Standard Refrigeration System
AmbientTemperature
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
172 144 194 112 205 75.2 159 138 185 107 200 71.9 147 131 172 101 193 68 130 130 158 97 183 63.4
175 169 195 138 207 103 164 162 186 134 202 99.7 153 153 173 128 194 95.4 142 142 158 122 183 90.5
185 185 196 164 209 126 176 176 186 161 203 124 165 165 174 156 195 122 155 155 155 155 184 117
195 195 195 195 211 149 188 188 190 184 204 148 178 178 179 179 196 147 168 168 167 167 184 144
177 153 197 116 207 76 164 147 189 112 202 73.2 151 140 176 106 195 69.3 138 131 162 99.8 185 64.8
181 180 198 144 209 105 170 170 189 142 204 103 159 159 177 136 196 99.4 148 148 162 130 186 94.6
192 192 199 172 211 129 183 183 190 171 206 129 173 173 173 173 197 127 162 162 162 162 186 124
201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 152
181 162 198 123 208 76.6 168 155 191 117 204 74.4 152 152 180 111 197 70.6 142 139 165 105 187 66.2
186 186 200 151 210 107 177 177 192 148 206 105 166 166 180 144 198 102 154 154 166 137 188 98.6
197 197 202 179 213 131 189 189 194 180 208 132 179 179 183 173 199 132 168 168 170 166 189 129
204 204 205 202 215 157 199 199 199 199 209 159 191 191 191 191 201 160 181 181 181 181 190 160
184 170 200 127 209 79.1 168 168 193 121 206 76.4 156 156 182 116 198 71.9 145 145 168 110 189 67.4
191 191 202 153 211 108 182 182 194 154 207 107 171 171 183 151 199 105 159 159 169 145 190 102
200 200 204 185 214 134 194 194 194 194 209 136 185 185 187 181 201 135 174 174 174 174 191 134
207 207 208 207 217 160 203 203 203 203 211 163 195 195 195 195 203 166 186 186 186 186 192 167
5400
6000
6600
7200
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
22
Download from Www.Somanuals.com. All Manuals Search And Download.
(15 Ton)
High Efficiency
Performance
Data
Table PD-9 — Gross Cooling Capacities (MBH) 15 Ton Three Phase T*D181C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 150.0 106.0 168.0 88.9 187.7 68.3 144.0 102.3 161.4 85.3 180.6 64.8 137.5 98.4 154.4 81.6 173.0 61.2 130.8 94.4 147.1 77.8 165.0 57.5
80 150.2 121.0 168.1 103.0 187.8 84.7 144.1 117.3 161.5 99.3 180.7 81.1 137.7 113.4 154.6 95.4 173.1 77.2 131.0 109.3 147.3 91.5 165.1 73.3
85 150.2 135.8 168.2 117.9 187.9 99.5 144.2 132.1 161.7 114.1 180.8 95.8 137.9 128.1 154.8 110.3 173.2 92.0 130.7 122.5 147.5 106.2 165.2 88.0
90 151.8 148.3 168.4 132.7 188.0 114.2 146.3 144.5 161.9 128.9 180.9 110.5 140.5 140.5 155.0 125.0 173.3 106.7 134.9 134.9 147.7 120.9 165.4 102.7
75 161.5 119.8 180.4 96.8 201.0 72.4 154.8 115.8 173.1 93.0 193.0 68.7 147.7 111.8 165.4 89.0 184.6 64.9 140.2 107.5 157.2 84.8 175.7 61.0
80 161.7 138.5 180.6 115.6 201.1 92.3 154.9 134.5 173.3 111.7 193.1 88.5 147.8 130.4 165.6 107.6 184.7 84.5 140.4 126.1 157.4 103.5 175.8 80.4
85 162.6 155.0 180.8 134.3 201.3 110.9 156.3 150.7 173.5 130.3 193.3 107.0 149.8 146.3 165.8 126.3 184.9 103.0 142.9 141.9 157.7 122.0 176.0 98.9
90 168.5 168.5 180.9 152.7 201.5 129.4 162.8 162.8 173.6 148.8 193.5 125.5 156.8 156.8 165.9 144.6 185.1 121.5 150.5 150.5 157.9 140.4 176.2 117.3
75 169.6 132.0 189.0 104.3 210.2 75.6 162.4 127.9 181.2 100.4 201.5 71.8 154.7 123.7 172.8 96.2 192.4 67.9 146.6 119.2 164.1 91.9 182.8 63.9
80 170.0 154.3 189.3 126.8 210.4 98.8 162.9 150.3 181.4 122.7 201.7 94.8 155.4 146.0 173.1 118.6 192.6 90.7 147.5 139.4 164.4 114.3 183.0 86.5
85 173.4 173.4 189.5 149.0 210.6 121.0 166.9 166.9 181.7 145.0 201.9 117.0 160.5 160.5 173.3 140.7 192.8 112.9 153.7 153.7 164.6 136.3 183.3 108.6
90 182.3 182.3 189.9 171.1 210.8 143.1 176.1 176.1 182.2 167.0 202.2 139.1 169.5 169.5 169.3 169.3 193.1 134.9 162.5 162.5 165.7 155.6 183.6 130.6
75 173.7 139.5 193.4 108.9 214.8 77.5 166.2 135.3 185.2 104.9 205.8 73.7 158.3 130.9 176.6 100.7 196.3 69.7 150.0 126.5 167.6 96.4 186.4 65.6
80 174.6 164.4 193.7 133.7 215.0 102.8 164.2 164.2 185.5 129.6 206.0 98.7 159.8 153.0 176.9 125.4 196.5 94.5 152.1 148.0 167.9 121.0 186.6 90.3
85 180.1 180.1 193.9 158.1 215.3 127.3 173.8 173.8 185.8 154.0 206.3 123.2 167.0 167.0 177.2 149.7 196.8 119.0 159.9 159.9 168.2 145.3 186.9 114.7
90 189.8 189.8 189.8 189.8 215.5 151.6 183.3 183.3 183.3 183.3 206.6 147.6 176.4 176.4 179.1 170.7 197.1 143.4 169.1 169.1 170.7 165.6 187.2 139.0
75 177.2 146.6 197.0 113.2 218.7 79.2 169.4 142.4 188.6 109.1 209.4 75.4 161.3 138.0 179.8 104.9 199.6 71.3 152.8 133.5 170.5 100.5 189.4 67.0
80 178.8 171.0 197.4 140.3 218.9 106.5 169.8 169.8 189.0 136.2 209.6 102.4 164.0 161.4 180.1 131.9 199.8 98.2 155.8 155.8 170.9 127.5 189.6 93.9
85 186.4 186.4 197.6 166.9 219.2 133.3 179.8 179.8 189.3 162.7 209.9 129.2 172.8 172.8 180.6 158.4 200.2 125.0 165.3 165.3 171.5 153.9 190.0 120.6
90 196.7 196.7 196.5 196.5 219.4 159.9 189.8 189.8 189.7 189.7 210.2 155.8 182.6 182.6 183.8 180.6 200.5 151.6 174.9 174.9 174.8 174.8 190.2 146.9
75 180.2 153.4 200.2 117.4 221.9 80.8 172.3 149.2 191.5 113.2 212.4 76.8 164.0 144.8 182.5 108.9 202.4 72.6 155.4 140.2 172.9 104.5 191.9 68.2
80 182.9 179.1 200.5 146.6 222.1 110.1 175.6 174.4 191.9 142.5 212.6 105.9 167.6 167.6 182.7 138.0 202.6 101.7 160.2 160.2 173.2 133.4 192.1 97.3
85 192.0 192.0 201.0 175.4 222.5 139.1 185.1 185.1 192.5 171.2 213.0 134.9 177.8 177.8 183.6 166.9 203.0 130.7 170.1 170.1 169.9 169.9 192.5 126.2
90 202.7 202.7 204.3 199.9 222.7 167.8 195.5 195.5 196.3 195.1 213.2 163.5 188.0 188.0 187.9 187.9 203.2 159.2 180.0 180.0 179.9 179.9 192.8 154.7
75 182.8 160.1 202.8 121.3 224.7 82.1 174.8 155.8 194.0 117.1 214.9 78.0 166.4 151.4 184.7 112.8 204.7 73.7 157.7 146.8 175.0 108.4 193.9 69.4
80 186.0 186.0 203.2 152.8 224.9 113.4 179.1 179.1 194.2 148.3 215.2 109.3 171.8 171.8 185.0 143.9 205.0 105.0 164.1 164.1 175.4 139.3 194.3 100.6
85 196.9 196.9 204.0 183.7 225.2 144.5 189.8 189.8 195.4 179.5 215.6 140.5 182.3 182.3 182.1 182.1 205.4 136.2 174.3 174.3 177.1 167.2 194.7 131.7
90 207.9 207.9 207.8 207.8 225.4 175.3 200.6 200.6 200.5 200.5 215.8 171.1 192.8 192.8 192.6 192.6 205.7 166.7 184.5 184.5 184.4 184.4 195.1 162.2
3000*
3900*
4800*
5400
6000
6600
7200
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate
airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 4800 CFM
•
•
Electric heaters restricted on applications below 4800 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4800 CFM.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(17½Ton)
High Efficiency
Table PD-10 — Gross Cooling Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW — Standard Refrigeration Option
AmbientTemperature
85
95
105
115
Enter
Dry
Bulb
EnteringWet Bulb
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2
80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0
85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0
90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0
75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0
80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0
85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0
90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0
75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7
80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0
85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0
90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0
75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2
80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0
85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0
90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0
6300
7000
7700
8400
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(17½Ton)
High Efficiency
Table PD-11 — Gross Cooling Capacities (MBH)17½ Ton Three Phase T*D211C3, C4, CW— TXV Option
AmbientTemperature
85
95
105
115
67
Enter
Dry
EnteringWet Bulb
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 178.1 125.2 199.2 102.8 222.1 78.3 170.4 120.6 190.9 98.4 213.1 74.0 162.3 115.7 182.1 93.7 203.6 69.5 153.6 110.7 172.8 88.9 193.6 64.9
80 178.3 143.9 199.4 121.1 222.2 97.7 170.6 139.3 191.1 116.5 213.3 93.4 162.4 134.5 182.3 111.8 203.8 88.8 153.8 129.5 173.1 106.8 193.7 84.0
85 178.6 163.0 199.6 139.7 222.4 116.2 171.0 158.4 191.3 135.0 213.5 111.9 163.0 153.7 182.5 130.2 204.0 107.2 151.7 151.7 173.3 125.2 194.0 102.4
90 181.8 177.2 199.8 158.2 222.6 134.6 175.2 171.7 191.5 153.5 213.7 130.2 168.1 165.8 182.7 148.7 204.2 125.5 160.6 160.1 173.5 143.8 194.2 120.6
75 190.8 142.2 212.7 113.0 236.1 82.3 182.3 137.4 203.5 108.3 226.2 78.0 173.3 132.4 193.9 103.4 215.8 73.4 163.8 127.2 183.7 98.3 204.8 68.6
80 191.2 166.4 213.0 136.6 236.3 106.8 182.8 161.6 203.8 131.8 226.5 102.3 173.9 156.6 194.1 126.9 216.0 97.5 164.7 151.5 184.0 121.8 205.1 92.6
85 193.7 186.8 213.2 160.2 236.6 130.2 186.2 180.5 204.1 155.4 226.8 125.6 178.3 173.9 194.4 150.4 216.3 120.8 169.9 167.2 184.3 145.3 205.3 115.8
90 201.2 201.2 213.6 183.9 236.9 153.5 194.2 194.2 204.7 179.3 227.0 148.9 186.6 186.6 195.2 174.4 216.6 144.0 178.5 178.5 185.2 169.3 205.6 139.0
75 199.5 157.9 221.6 122.1 245.5 85.7 190.5 153.0 212.0 117.4 234.9 81.2 180.9 147.9 201.7 112.4 223.8 76.5 171.0 142.6 190.9 107.3 212.2 71.6
80 200.9 187.5 221.9 150.5 245.8 114.8 192.2 182.6 212.3 145.8 235.3 110.1 179.9 179.9 202.0 140.8 224.1 105.2 173.8 166.9 191.2 135.6 212.5 100.2
85 207.3 204.9 222.5 179.2 246.2 142.9 199.3 198.8 213.0 174.6 235.4 138.1 190.6 190.6 202.7 169.6 224.4 133.3 182.0 182.0 192.0 164.4 212.8 128.2
90 217.4 217.4 224.2 208.4 246.5 171.0 209.5 209.5 214.9 203.9 235.8 166.2 201.4 201.4 201.3 201.3 224.8 161.4 192.6 192.6 195.4 187.3 213.2 156.4
75 203.9 167.7 226.2 127.9 250.3 87.7 194.8 162.9 216.2 123.2 239.2 83.0 185.0 157.7 205.6 118.1 227.8 78.4 174.8 152.4 194.5 112.9 215.8 73.
80 202.9 202.9 226.5 159.5 250.5 119.7 195.2 195.2 216.6 154.8 239.4 114.8 188.9 182.8 206.0 149.7 228.1 110.1 179.6 175.4 194.9 144.5 216.1 105.0
85 214.6 214.6 227.5 191.5 250.9 150.9 206.7 206.7 217.4 186.6 239.8 146.1 198.1 198.1 207.2 181.8 228.5 141.3 189.1 189.1 196.3 176.6 216.5 136.2
90 226.3 226.3 226.2 226.2 251.4 182.3 218.0 218.0 221.1 212.1 240.4 177.4 209.4 209.4 211.9 204.9 228.9 172.4 200.2 200.2 202.0 197.2 217.2 167.6
75 207.8 177.3 229.9 133.4 254.2 89.6 198.5 172.5 219.7 128.6 242.8 84.9 188.5 167.4 208.8 123.5 231.1 80.1 178.2 162.0 197.4 118.3 218.8 75.1
80 212.0 205.1 230.4 168.2 254.5 124.4 203.5 198.3 220.0 163.5 243.1 119.6 194.3 190.9 209.4 158.4 231.4 114.7 184.7 183.5 198.1 153.1 219.2 109.6
85 221.9 221.9 231.8 203.6 254.9 158.8 213.4 213.4 221.6 198.6 243.5 153.8 204.7 204.7 211.2 193.7 231.8 149.0 195.4 195.4 200.2 188.5 219.6 143.9
90 234.1 234.1 236.8 229.0 255.6 193.4 225.4 225.4 227.5 221.6 244.3 188.5 216.5 216.5 217.7 214.0 232.5 183.4 206.9 206.9 207.6 206.7 220.6 178.6
75 211.3 186.8 233.0 138.7 257.4 91.4 201.8 181.9 222.6 133.9 245.7 86.5 191.8 176.7 211.5 128.8 233.8 81.7 181.3 171.3 199.9 123.5 221.3 76.7
80 217.2 212.9 233.7 176.7 257.8 129.0 208.4 206.0 223.3 171.9 246.1 124.1 199.0 198.7 212.3 166.8 234.2 119.3 189.0 189.0 200.8 161.5 221.7 114.1
85 228.2 228.2 235.8 215.3 258.2 166.4 219.5 219.5 225.5 210.3 246.5 161.4 210.4 210.4 210.3 210.3 234.6 156.6 200.8 200.8 200.7 200.7 222.2 151.5
90 241.0 241.0 242.8 238.1 259.2 204.2 231.9 231.9 233.1 230.7 247.7 199.3 222.4 222.4 222.3 222.3 235.7 194.2 212.6 212.6 212.6 212.6 223.5 189.2
75 214.5 195.9 235.7 143.9 260.2 92.9 204.9 191.1 225.0 139.0 248.3 88.0 190.7 190.7 213.7 133.9 236.1 83.2 181.3 181.3 201.9 128.6 223.4 78.2
80 221.9 220.3 236.6 185.0 260.5 133.5 212.1 212.1 225.8 180.0 248.6 128.5 203.1 203.1 214.8 175.0 236.5 123.7 193.4 193.4 203.2 169.7 223.8 118.5
85 233.9 233.9 239.5 226.8 261.0 173.9 224.8 224.8 224.7 224.7 249.2 168.9 215.5 215.5 215.4 215.4 236.9 163.8 205.5 205.5 207.7 200.6 224.4 158.9
90 247.0 247.0 248.0 246.9 262.4 214.8 237.7 237.7 237.6 237.6 250.7 209.8 227.8 227.8 227.8 227.8 238.6 204.7 217.8 217.8 217.7 217.7 226.3 199.7
3500*
4550*
5600
6300
7000
7700
8400
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 5600 CFM
•
•
Electric heaters restricted on applications below 5600 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 5600 CFM.
RT-PRC002-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(20Ton)
High Efficiency
Table PD-12 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*241C3, C4, CW — Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
246 205 273 158 284 105 228 196 263 152 280 101 208 186 246 145 273 96.5 191 176 222 136 261 91.5
250 245 274 192 287 142 232 232 264 190 283 141 216 216 246 183 274 135 201 201 223 172 261 130
263 263 275 227 290 171 251 251 265 228 285 173 236 236 248 221 275 170 219 219 225 211 262 168
274 274 278 262 293 201 266 266 268 265 288 206 254 254 254 254 277 205 239 239 237 237 262 205
253 218 275 163 285 107 234 209 267 159 282 103 214 199 252 152 275 98.3 194 189 228 142 266 93.6
257 257 277 199 289 144 243 243 268 199 285 143 227 227 252 194 277 140 210 210 228 184 266 136
270 270 279 236 292 174 261 261 270 240 288 177 247 247 255 237 278 177 230 230 232 226 266 177
280 280 282 273 295 205 274 274 274 274 291 212 264 264 264 264 280 214 250 250 248 248 267 218
258 230 278 167 287 109 240 221 270 164 284 105 219 211 256 159 277 100 199 199 232 149 269 95.5
264 264 280 204 290 155 252 252 271 208 287 145 236 236 257 205 279 144 218 218 233 195 269 141
276 276 282 244 293 177 268 268 274 250 290 181 256 256 260 251 281 182 240 240 238 238 269 185
285 285 286 281 297 209 280 280 280 280 293 217 271 271 271 271 283 221 258 258 258 258 271 229
262 240 280 169 288 110 246 233 273 169 285 106 225 223 260 166 278 102 205 205 236 156 271 97.1
270 270 282 209 291 161 260 260 274 215 288 147 245 245 261 215 281 147 226 226 237 205 271 146
280 280 284 250 295 179 274 274 277 260 291 184 263 263 265 263 282 186 248 248 246 246 272 193
288 288 288 288 298 212 284 284 284 284 294 222 276 276 276 276 285 228 264 264 265 265 275 240
7200
8000
8800
9600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(20Ton)
High Efficiency
Table PD-13 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— TXV Option
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 208.5 149.1 233.3 122.6 260.1 94.5 199.6 143.8 223.6 117.3 249.8 89.3 190.1 138.1 213.4 111.9 238.6 84.0 180.0 132.3 202.5 105.8 226.9 78.5
80 208.7 171.1 233.4 144.4 260.2 117.1 199.9 165.6 223.8 139.1 249.8 111.8 190.4 159.9 213.6 133.4 238.7 106.3 180.4 153.9 202.7 127.6 226.9 100.7
85 209.5 193.0 233.6 166.3 260.3 138.9 200.8 187.5 224.0 160.9 249.9 133.7 191.4 181.7 213.8 155.2 238.9 128.1 181.6 175.7 203.0 149.3 227.1 122.4
90 212.7 212.7 233.9 188.1 260.5 160.6 205.2 205.2 224.3 182.6 250.1 155.2 197.4 197.4 214.1 176.8 239.1 149.7 189.0 189.0 203.4 170.8 227.3 143.9
75 223.8 169.6 249.5 135.2 277.5 99.6 213.8 163.8 238.8 129.6 265.8 94.2 203.4 157.8 227.5 123.9 253.4 88.6 192.4 151.6 215.6 117.8 240.4 82.9
80 224.5 197.4 249.7 163.1 277.6 128.2 214.8 191.6 239.1 157.5 265.9 122.7 204.4 185.6 227.8 151.6 253.6 117.0 193.5 179.4 215.9 145.6 240.6 111.1
85 226.7 222.0 249.9 190.8 277.9 155.9 217.9 215.9 239.4 185.1 266.2 150.3 208.8 208.8 228.2 179.2 253.8 144.5 199.6 199.6 216.3 173.0 240.8 138.6
90 237.7 237.7 250.8 218.3 278.1 183.4 229.4 229.4 240.3 212.6 266.5 177.8 220.4 220.4 229.2 206.6 254.1 172.0 211.0 211.0 217.5 200.4 241.1 165.9
75 234.3 187.9 260.5 146.4 289.2 103.7 223.9 182.1 249.1 140.7 276.7 98.2 212.8 175.9 237.1 134.8 263.3 92.5 201.1 169.5 224.3 128.7 249.4 86.5
80 235.9 221.8 260.8 180.1 289.4 138.0 225.7 215.9 249.4 174.3 276.9 132.3 214.9 209.8 237.3 168.2 263.6 126.5 202.8 202.8 224.6 161.9 249.6 120.4
85 243.8 243.8 261.4 213.2 289.7 171.3 234.9 234.9 250.1 207.4 277.2 165.6 225.3 225.3 238.2 201.3 264.0 159.7 215.3 215.3 225.7 195.0 250.0 153.6
90 257.1 257.1 263.2 246.7 290.1 204.5 247.9 247.9 252.1 240.8 277.5 198.6 238.1 238.1 240.6 234.8 264.3 192.6 227.7 227.7 228.5 224.2 250.4 186.3
75 239.8 199.6 266.0 153.5 295.0 106.1 229.0 193.6 254.2 147.8 282.1 100.6 217.6 187.4 241.8 141.7 268.2 94.7 205.6 180.9 228.6 138.4 253.8 88.7
80 242.3 237.5 266.3 190.6 295.3 144.0 230.8 230.8 254.6 184.7 282.3 138.3 221.3 221.1 242.2 178.6 268.6 132.4 210.7 210.7 229.2 172.3 254.2 126.2
85 253.7 253.7 267.4 227.6 295.7 181.1 244.3 244.3 255.7 221.6 282.7 175.3 234.3 234.3 243.5 215.5 269.1 169.3 223.6 223.6 230.6 209.1 254.6 163.1
90 267.6 267.6 270.3 265.1 296.0 217.7 257.9 257.9 257.8 257.8 283.2 211.9 247.5 247.5 247.5 247.5 269.6 205.7 236.6 236.6 236.6 236.6 255.3 199.4
75 244.5 210.8 270.7 160.1 299.8 108.3 233.4 204.7 258.5 154.3 286.5 102.8 221.8 198.5 245.8 148.2 272.4 96.9 209.5 191.9 232.3 141.9 257.5 90.8
80 248.1 248.1 271.1 200.8 300.1 149.8 238.5 238.5 259.0 194.8 286.8 144.0 228.4 228.4 246.3 188.7 272.8 138.1 217.6 217.6 232.9 182.3 258.0 131.8
85 262.5 262.5 272.6 241.6 300.5 190.5 252.6 252.6 260.7 235.6 287.3 184.7 242.1 242.1 248.1 229.3 273.3 178.7 231.0 231.0 235.0 222.9 258.3 172.1
90 277.2 277.2 277.0 277.0 301.0 230.6 266.9 266.9 266.8 266.8 288.0 224.7 256.0 256.0 256.0 256.0 274.1 218.5 244.6 244.6 244.5 244.5 259.4 212.1
75 248.5 221.7 274.6 166.6 303.7 110.4 237.3 215.6 262.1 160.6 290.2 104.8 225.4 209.3 249.0 154.6 275.8 98.9 213.0 202.7 235.3 148.3 260.6 92.7
80 255.2 255.2 275.2 210.8 304.0 155.3 245.3 245.3 262.8 204.7 290.6 149.6 234.7 234.7 249.8 198.5 276.2 143.5 223.6 223.6 236.2 192.0 261.1 137.3
85 270.2 270.2 277.2 255.2 304.3 199.4 259.9 259.9 265.1 249.2 291.0 193.6 249.0 249.0 252.3 242.9 276.7 187.4 237.5 237.5 239.1 236.5 261.6 180.9
90 285.5 285.5 285.4 285.4 305.2 243.0 274.8 274.8 274.8 274.8 292.1 237.2 263.5 263.5 263.5 263.5 277.9 231.0 251.5 251.5 251.5 251.5 263.0 224.5
75 252.1 232.3 277.9 172.8 306.9 112.3 240.7 226.2 265.2 166.9 293.3 106.7 228.7 219.9 251.7 160.6 278.6 100.7 216.3 213.3 237.8 154.1 263.2 94.5
80 261.5 261.5 278.7 220.4 307.3 160.6 251.2 251.2 266.1 214.3 293.8 155.0 240.4 240.4 252.8 208.0 279.2 148.9 228.8 228.8 238.9 201.5 263.8 142.6
85 277.0 277.0 281.4 268.6 307.7 208.4 266.4 266.4 269.2 262.5 294.2 202.3 255.1 255.1 254.9 254.9 279.7 196.0 243.1 243.1 243.0 243.0 264.4 189.6
90 292.8 292.8 292.8 292.8 308.7 255.2 281.8 281.8 281.8 281.8 295.6 249.4 270.1 270.1 270.1 270.1 281.3 243.2 257.7 257.7 257.7 257.7 266.2 236.7
4000*
5200*
6400
7200
8000
8800
9600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 6400 CFM
•
•
Electric heaters restricted on applications below 6400 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(20Ton)
High Efficiency
Table PD-14 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— Dehumidification (Hot Gas Reheat)
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 197.5 138.9 222.3 116.0 249.8 89.2 188.8 133.4 213.0 110.6 239.6 83.8 179.7 127.6 203.1 105.0 228.8 78.3 170.1 121.7 192.6 99.2 217.3 72.5
80 197.7 159.2 222.6 135.8 249.8 111.4 189.0 153.7 213.3 130.3 239.6 105.8 180.0 147.9 203.4 124.6 228.8 100.1 170.4 141.9 193.0 118.7 217.4 94.2
85 198.2 179.3 222.9 156.3 250.0 132.0 189.7 173.8 213.5 150.7 239.8 126.4 180.8 168.1 203.7 145.0 229.0 120.7 171.4 162.2 193.3 139.1 217.7 114.8
90 200.5 196.8 223.1 176.7 250.3 152.5 192.8 190.9 213.7 171.0 240.1 147.0 184.8 184.8 203.8 165.2 229.3 141.2 176.9 176.9 193.5 159.3 217.9 135.3
75 213.1 158.3 239.0 127.6 267.2 94.6 203.5 152.5 228.5 121.8 255.7 88.9 193.2 146.3 217.5 115.8 243.7 83.1 182.7 140.0 206.0 109.6 231.1 77.1
80 213.5 183.8 239.3 153.7 267.4 122.1 204.0 178.0 228.9 147.9 255.9 116.3 194.0 171.9 217.9 141.9 243.9 110.3 183.5 165.7 206.4 135.7 231.3 104.1
85 215.3 209.9 239.7 179.7 267.7 148.3 204.6 204.6 229.1 173.7 256.2 142.4 197.0 194.2 218.1 167.6 244.2 136.4 187.4 187.4 206.7 161.4 231.6 130.3
90 224.3 224.3 240.1 205.2 268.0 174.4 216.2 216.2 229.8 199.4 256.6 168.6 207.6 207.6 218.9 193.3 244.5 162.5 198.7 198.7 207.6 187.1 232.0 156.4
75 223.7 175.3 250.2 138.3 279.0 98.8 213.5 169.3 239.0 132.3 266.6 93.0 202.6 163.0 227.2 126.1 253.7 87.0 191.3 156.4 214.9 119.7 240.2 80.8
80 224.9 206.3 250.6 169.7 279.2 131.4 214.8 200.3 239.4 163.6 266.8 125.3 204.2 194.1 227.7 157.5 253.9 119.2 193.2 187.7 215.2 151.0 240.5 112.9
85 230.5 230.5 251.0 200.6 279.6 162.9 221.7 221.7 239.8 194.5 267.2 156.9 212.5 212.5 228.1 188.2 254.3 150.7 202.8 202.8 215.9 181.8 240.9 144.4
90 243.6 243.6 252.4 231.7 280.0 194.4 234.6 234.6 241.5 225.7 267.7 188.3 225.1 225.1 230.0 219.5 254.6 181.9 215.2 215.2 215.6 215.6 241.2 175.5
75 229.2 185.9 255.7 150.2 284.8 101.3 218.6 179.7 244.1 144.1 272.0 95.4 207.4 173.3 231.9 138.0 258.6 89.4 195.8 166.7 219.1 131.7 244.7 83.2
80 231.1 220.6 256.3 179.6 285.1 137.0 220.8 214.5 244.6 173.3 272.3 130.9 208.4 208.4 232.5 167.0 258.9 124.7 199.2 197.3 219.8 160.4 245.0 118.3
85 240.3 240.3 256.9 213.7 285.5 172.0 231.1 231.1 245.4 207.5 272.7 165.9 221.4 221.4 233.3 201.2 259.4 159.7 211.2 211.2 220.8 194.7 245.5 153.3
90 254.0 254.0 259.2 248.5 286.0 206.7 244.5 244.5 248.0 242.5 273.2 200.5 234.5 234.5 235.0 235.0 259.8 194.1 224.0 224.0 225.1 224.1 246.0 187.6
75 233.9 196.0 260.5 150.9 289.7 103.6 223.0 189.8 248.6 144.8 276.5 97.7 211.5 183.3 236.1 138.4 262.7 91.4 199.6 176.7 223.0 131.9 248.4 85.0
80 234.8 234.8 261.0 188.8 290.0 142.4 225.4 225.4 249.0 182.5 276.9 136.2 215.6 215.6 236.5 176.1 263.1 129.9 205.3 205.3 223.5 169.5 248.8 123.5
85 249.0 249.0 262.0 226.4 290.5 180.8 239.3 239.3 250.1 220.2 277.4 174.6 229.2 229.2 237.8 213.8 263.6 168.3 218.6 218.6 225.1 207.3 249.2 161.7
90 263.3 263.3 263.7 263.7 291.0 218.5 253.3 253.3 254.6 253.1 277.9 212.2 242.9 242.9 243.3 243.3 264.2 205.8 231.9 231.9 232.3 232.3 249.9 199.2
75 237.9 205.8 264.5 156.8 293.8 105.7 226.7 199.5 252.2 150.6 280.3 99.6 215.1 193.0 239.4 144.2 266.1 93.2 202.9 186.3 226.0 137.6 251.5 86.6
80 242.3 242.3 265.0 197.7 294.1 147.5 232.1 232.1 252.7 191.4 280.6 141.3 221.9 221.9 239.9 184.9 266.6 135.0 211.2 211.2 226.6 178.2 251.9 128.4
85 256.5 256.5 266.4 238.7 294.7 189.2 246.5 246.5 254.3 232.4 281.0 182.8 235.9 235.9 241.8 226.0 267.0 176.3 224.9 224.9 228.9 219.4 252.4 169.7
90 271.4 271.4 271.8 271.8 295.2 229.9 261.0 261.0 261.4 261.4 281.8 223.6 250.1 250.1 250.5 250.5 267.9 217.2 238.7 238.7 239.1 239.1 253.4 210.5
75 241.4 215.2 267.8 162.4 297.1 107.4 230.0 208.9 255.3 156.2 283.4 101.2 218.2 202.3 242.2 149.7 269.0 94.8 205.9 195.6 228.4 143.0 254.0 88.2
80 248.0 248.0 268.4 206.4 297.6 152.5 237.9 237.9 255.9 200.0 283.8 146.2 227.5 227.5 242.8 193.4 269.5 139.8 216.4 216.4 229.3 186.7 254.6 133.2
85 263.1 263.1 270.3 250.7 298.0 197.1 252.8 252.8 258.1 244.3 284.3 190.7 241.9 241.9 245.5 237.9 270.0 184.1 230.5 230.5 230.7 230.7 255.1 177.4
90 278.6 278.6 278.9 278.9 298.9 241.1 267.9 267.9 268.3 268.3 285.3 234.7 256.6 256.6 257.0 257.0 271.1 228.2 244.7 244.7 245.1 245.1 256.4 221.5
4000*
5200*
6400
7200
8000
8800
9600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 6400 CFM
•
•
Electric heaters restricted on applications below 6400 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.
RT-PRC002-EN
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(25Ton)
High Efficiency
Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three Phase TC*301C3, C4, CW - Standard Refrigeration System
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
277 243 306 187 316 117 258 234 295 178 314 115 238 224 276 169 305 110 218 214 253 163 292 104
284 284 307 225 321 169 269 269 295 225 317 161 252 252 277 217 307 158 235 235 254 207 293 151
300 300 309 269 325 198 289 289 298 271 320 202 273 273 280 266 308 201 256 256 259 256 293 198
312 312 313 312 329 236 305 305 305 305 321 240 293 293 293 293 310 245 277 277 277 277 295 244
284 258 310 188 319 121 264 249 299 185 316 117 244 239 282 178 308 112 224 224 259 168 295 106
294 294 310 233 323 175 280 280 300 236 319 170 263 263 283 230 309 163 245 245 260 221 296 158
307 307 313 280 327 202 298 298 303 286 322 207 284 284 287 284 312 208 267 267 267 267 297 208
318 318 318 318 331 241 312 312 312 312 324 248 301 301 301 301 314 255 287 287 287 287 299 257
286 265 311 190 320 122 267 256 300 189 316 118 247 246 284 182 309 113 228 228 261 172 296 107
297 297 312 237 324 178 285 285 302 241 320 174 267 267 285 237 310 165 249 249 262 227 298 162
310 310 315 285 328 204 302 302 305 293 323 210 289 289 289 289 313 212 272 272 272 272 299 213
320 320 320 320 332 244 314 314 314 314 325 251 305 305 305 305 316 260 292 292 292 292 301 264
289 272 312 192 321 123 270 264 302 192 317 119 249 249 286 186 309 114 231 231 263 176 297 108
300 300 313 240 324 181 289 289 304 246 321 177 272 272 287 243 311 170 253 253 265 234 299 165
312 312 316 289 329 205 305 305 307 299 324 212 293 293 293 293 314 215 276 276 276 276 300 217
322 322 321 321 332 246 317 317 317 317 326 255 308 308 308 308 317 265 295 295 295 295 303 270
9000
10000
10500
110 0 0
Notes
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(25Ton)
High Efficiency
Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC*301C3, C4, CW— TXV Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 241.0 176.5 269.7 142.7 300.9 107.2 229.7 169.7 257.6 135.9 287.8 100.8 217.8 162.6 244.9 129.0 274.0 94.1 205.5 155.3 231.6 122.0 259.8 87.3
80 241.4 204.6 269.9 170.5 300.9 135.9 230.2 197.7 257.8 163.8 287.8 129.3 218.4 190.5 245.1 156.8 274.1 122.5 206.2 183.2 231.9 149.6 259.8 115.6
85 243.0 233.0 270.1 198.3 301.1 163.7 229.2 229.2 258.1 191.5 288.1 157.0 221.3 216.5 245.4 184.5 274.4 150.1 209.9 208.3 232.2 177.3 260.1 143.1
90 251.2 251.2 270.6 226.1 301.4 191.2 241.6 241.6 258.6 219.2 288.3 184.4 231.6 231.6 246.0 212.1 274.6 177.5 221.2 221.2 233.0 204.8 260.4 170.4
75 256.8 201.4 286.5 157.9 318.8 113.1 244.6 194.3 273.3 150.9 304.2 106.4 231.8 186.9 259.5 143.8 289.2 99.5 218.4 179.4 245.1 136.5 273.6 92.5
80 258.2 237.2 286.8 193.2 318.9 149.3 246.1 230.1 273.6 186.2 304.4 142.3 233.6 222.8 259.8 179.0 289.4 135.3 220.7 215.4 245.4 171.6 273.9 128.1
85 264.6 264.6 287.3 228.5 319.2 184.3 254.2 254.2 274.1 221.4 304.7 177.3 243.2 243.2 260.4 214.1 289.7 170.2 231.7 231.7 246.2 206.6 274.1 162.9
90 279.1 279.1 288.7 263.8 319.5 219.2 268.4 268.4 275.8 256.7 305.0 212.1 257.3 257.3 262.4 249.5 290.0 205.0 245.6 245.6 245.5 245.5 274.5 197.7
75 267.9 224.2 297.7 171.5 330.7 118.0 254.9 216.9 283.7 164.4 315.3 111.1 241.5 209.3 269.2 157.1 299.2 104.0 227.5 201.6 254.0 149.6 282.7 96.8
80 268.8 268.8 298.0 214.0 330.9 161.1 259.3 255.4 284.1 206.8 315.5 154.0 246.8 246.7 269.6 199.5 299.5 146.7 234.0 234.0 254.5 191.9 283.0 139.4
85 284.5 284.5 299.2 256.4 331.2 203.2 273.2 273.2 285.4 249.2 315.9 196.1 261.3 261.3 271.0 241.8 299.8 188.8 248.9 248.9 256.2 234.3 283.3 181.4
90 300.3 300.3 300.2 300.2 331.6 245.2 288.7 288.7 290.5 286.0 316.4 238.0 276.5 276.5 276.4 276.4 300.4 230.6 263.8 263.8 263.7 263.7 284.0 223.1
75 273.6 238.6 303.4 180.1 336.6 120.9 260.4 231.2 289.0 172.8 320.7 114.0 246.7 223.6 273.9 170.7 304.2 106.8 232.5 215.9 258.3 163.2 287.1 99.6
80 279.6 279.5 303.8 227.0 336.8 168.4 267.3 267.3 289.5 219.8 321.0 161.3 255.2 255.2 274.6 212.4 304.5 154.0 242.6 242.6 259.1 204.8 287.5 146.5
85 295.1 295.1 305.6 274.3 337.2 215.2 283.4 283.4 291.5 267.1 321.4 208.1 271.0 271.0 276.9 259.7 304.9 200.7 258.0 258.0 261.9 252.2 287.8 193.1
90 311.9 311.9 311.8 311.8 338.0 261.8 299.6 299.6 299.6 299.6 322.2 254.5 286.9 286.9 286.8 286.8 305.9 247.1 273.5 273.5 273.5 273.5 288.9 239.4
75 278.6 252.6 308.1 188.2 341.5 123.5 265.2 245.2 293.3 180.9 325.3 116.5 251.3 237.6 278.0 173.5 308.4 109.2 234.1 234.1 262.1 165.9 290.8 101.7
80 287.6 287.6 308.7 239.7 341.8 175.5 275.5 275.5 294.0 232.5 325.6 168.3 263.1 263.1 278.8 225.0 308.7 160.9 250.0 250.0 263.1 217.3 291.2 153.4
85 304.6 304.6 311.3 291.9 342.1 226.8 292.3 292.3 297.0 284.7 325.9 219.5 279.4 279.4 279.3 279.3 309.1 212.1 266.0 266.0 267.7 262.9 291.7 204.4
90 322.2 322.2 322.1 322.1 343.3 277.9 309.3 309.3 309.3 309.3 327.2 270.5 295.9 295.9 295.9 295.9 310.6 263.1 282.0 282.0 282.0 282.0 293.3 255.3
75 283.1 266.2 312.0 196.0 345.5 125.9 269.5 258.8 296.9 188.7 329.1 118.9 253.1 253.1 281.2 181.2 311.8 111.5 241.4 237.4 265.1 173.5 293.9 104.0
80 295.1 295.1 312.9 252.1 345.8 182.3 282.8 282.8 297.9 244.7 329.4 175.0 269.9 269.9 282.4 237.2 312.2 167.7 256.4 256.4 266.5 229.4 294.3 160.1
85 312.9 312.9 312.8 312.8 346.2 237.9 300.0 300.0 299.9 299.9 329.9 230.6 286.7 286.7 288.1 285.2 312.8 223.1 272.8 272.8 272.7 272.7 295.0 215.4
90 331.2 331.2 331.1 331.1 347.8 293.5 317.8 317.8 317.8 317.8 331.6 286.2 304.0 304.0 303.8 303.8 314.7 278.6 289.3 289.3 289.3 289.3 297.3 271.0
75 283.8 283.8 315.3 203.6 348.9 128.2 271.5 271.5 299.9 196.2 332.2 121.1 259.9 256.8 284.1 188.6 314.7 113.8 245.2 245.2 267.7 180.9 296.5 106.2
80 301.8 301.8 316.6 264.1 349.2 188.9 289.0 289.0 301.2 256.6 332.6 181.7 275.9 275.9 285.7 249.1 315.2 174.3 262.0 262.0 269.5 241.3 297.0 166.6
85 320.3 320.3 322.4 316.7 349.8 248.8 307.0 307.0 308.0 306.9 333.2 241.5 293.2 293.2 293.1 293.1 315.8 233.9 278.8 278.8 278.8 278.8 297.8 226.2
90 339.1 339.1 339.0 339.0 351.7 308.8 325.4 325.4 325.3 325.3 335.6 301.5 310.9 310.9 310.9 310.9 318.5 294.0 295.9 295.9 295.9 295.9 301.0 286.4
5000*
6500*
8000
9000
10000
110 0 0
12000
Notes
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unit applications below 8000 CFM
•
•
Electric heaters restricted on applications below 8000 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 8000 CFM.
RT-PRC002-EN
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (12½Ton)
Data
Standard Efficiency
Table PD-17 — Evaporator Fan Performance — 12½Ton — TC*150D
External Static Pressure (Inches of Water)
.40 .50 .60
.10
.20
.30
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3 HP Standard Motor & Field
SuppliedLowStaticDrive
3HPStandardMotor&Sheaves
4000
4500
5000
5500
6000
—
—
547
595
643
—
—
1.18
1.55
1.99
—
—
581
627
673
—
—
1.30
1.68
2.12
—
—
565
603
643
685
727
0.93
1.21
1.54
1.94
2.41
599
634
672
711
752
1.03
1.31
1.67
2.08
2.56
632
665
700
737
777
1.15
1.43
1.78
2.21
2.71
663
694
727
763
801
1.27
1.56
1.91
2.34
2.85
695
723
755
788
825
1.38
1.69
2.05
2.47
2.99
727 1.48
750 1.82
781 2.19
813 2.62
848 3.13
757 1.59
778 1.94
806 2.34
837 2.77
871 3.27
571
613
656
701
1.10
1.42
1.81
2.26
Table PD-17 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM BHP
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
3HPStandardMotor&Sheaves
3HPStandardMotor&HighStaticDriveAccessory
4000
4500
5000
5500
6000
786
806
830
861
894
1.70
2.06
2.48
2.93
3.43
813
834
856
884
916
1.81
2.19
2.62
3.10
3.61
841
861
882
906
938
1.91
2.31
2.76
3.25
3.79
867
886
907
930
959
2.02
2.43
2.89
3.41
3.97
893
911
931
953
980
2.12
2.56
3.02
3.56
4.15
919
935
955
976
1000
2.22
2.67
3.16
3.70
4.31
943
960
977
999
1019
2.32
2.79
3.30
3.86
4.46
966
983
1001
1021
1040
2.41
2.90
989 2.50
1011 2.60
1005 3.02 1028 3.13
3.44 1022 3.56 1045 3.70
4.00 1043 4.15 1064 4.31
4.62 1061 4.78 1082 4.95
5HPOversizeMotor&Sheaves
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. FieldSuppliedFanSheaveBK90Required. FieldSuppliedBelt maybenecessary.
2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt
maybenecessary.
5HPOversizeMotor&FieldSuppliedDrive
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/FanSpeed”tablestodetermineoperatingrange.
RT-PRC002-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (15Ton)
Data
Standard Efficiency
Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B
External Static Pressure (Inches of Water)
.40 .50 .60
.10
.20
.30
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3 HP Standard Motor & Field
SuppliedLowStaticDrive(1)
3HPStandardMotor&Sheaves
4800
5400
6000
6600
7200
—
—
563
618
673
729
786
1.17
1.60
2.12
2.76
3.52
596
648
701
755
810
1.29
1.72
2.26
2.91
3.69
626
676
727
780
834
1.41
1.86
2.41
3.07
3.85
656
703
752
804
856
1.52
1.99
2.56
3.23
4.02
685
729
777
827
878
1.63
2.12
2.71
3.39
4.20
714
756
801
849
899
1.76
2.25
2.85
3.56
4.38
742
782
825
871
919
1.90
2.38
2.99
3.72
4.56
768 2.04
807 2.52
848 3.13
892 3.88
939 4.74
794 2.18
832 2.68
871 3.27
914 4.03
959 4.91
585
643
701
760
1.47
1.99
2.61
3.35
(2)
5HPOversizedMotor&Sheaves
Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
3HPStandardMotor&Sheaves
3HPStandardMotor&HighStaticDriveAccessory
4800
5400
6000
6600
7200
819
855
894
935
979
2.30
2.84
3.43
4.18
5.08
844
878
916
956
999
2.43
3.00
3.61
4.34
5.25
871
901
938
977
1018
2.57
3.15
3.79
4.51
5.41
898
923
959
997
1038
2.70
3.29
3.97
4.70
5.58
923
945
2.83
3.43
4.15
4.90
5.77
946
969
1000
1037
—
2.96
3.58
4.31
5.10
—
970
993
1019
1056
—
3.09
3.73
4.46 1040
5.30 1075
994
3.23
1018 3.39 1041 3.54
1016
3.88 1038 4.03 1060 4.17
4.62 1061 4.78 1082 4.95
5.49 1093 5.67
980
1018
1057
—
—
—
—
—
—
—
—
—
5HPOversizedMotor&Sheaves
5HPOversizedMotor&FieldSuppliedDrive(3)
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. FieldSuppliedFanSheaveBK105Required. FieldSuppliedBelt maybenecessary.
2. 5 HP Oversized Motor with Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may
benecessary.
3. 5 HP Oversized Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt
maybenecessary.
4. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/FanSpeed”tablestodetermineoperatingrange.
RT-PRC002-EN
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (17½Ton)
Data
Standard Efficiency
Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C
External Static Pressure (Inches of Water)
.40 .50 .60
.10
.20
.30
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5HPStandardMotorwithLowStaticDriveAccessory
5600
6300
7000
7700
8400
—
765
845
925
1006
—
—
788
866
944
1024
—
735
810
886
963
1041
2.34
3.23
4.33
5.66
7.24
759
831
2.46
3.36
4.48
5.82
7.42
783
852
925
2.60
3.50
4.62
5.98
7.60
807
874
944
2.74
3.65
4.77
6.14
7.78
830
895
963
2.89
3.81
4.93
6.30 1050
7.95 1122
852
917
982
3.03
3.97
5.10
875 3.18
937 4.13
1002 5.29 1021 5.47
898 3.33
956 4.29
2.96
4.02
5.32
6.87
3.10
4.18
5.49
7.06
906
982
1058
999
1075
1016
1091
1033
1107
6.47 1069 6.66 1086 6.86
8.13
1138 8.31
1154 8.50
7.5HPOversizeMotor&Sheaves
5HPStandardMotor&Sheaves
Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM BHP
1.10
RPM
1.20
RPM
1.30
RPM
1.70
1.80
RPM BHP
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
RPM
BHP
5HPStandardMotor&Sheaves
5600
6300
7000
7700
8400
923
976
1039
1104
—
3.50
4.46
5.65
7.06
—
946
997
1057
1122
—
3.68
4.63
5.82
7.26
—
968
1019
1074
1138
—
3.85
4.82
6.00
7.46
—
989
1040
1092
1154
—
4.03
5.00
6.19
7.66
—
1011
1060
1111
1170
—
4.21
5.19
6.39
7.84
—
1033
1079
1130
1186
—
4.39
5.39
6.59
8.05
—
1056
1100
1150
1202
—
4.58 1078
4.77 1099 4.96
1122 5.18
1157 6.20
1205 7.46
5.60
6.80
1118
1168
5.79
7.01
8.47
—
1138 6.00
1186 7.22
8.25 1220
—
—
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
7.5HPOversiveMotor&Sheaves
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/
Fan Speed” tables to determine operating range.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(20Ton)
Standard Efficiency
Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B
External Static Pressure (Inches of Water)
.40 .50 .60
.10
.20
.30
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5 HP Standard Motor & Field Supplied
LowStaticDrive(1)
5HPStandardMotor&Sheaves
6400
7200
8000
8800
9600
—
—
514
562
610
659
709
1.69
2.29
3.03
3.93
4.99
546
592
639
687
735
1.88
2.50
3.26
4.18
5.27
574
619
666
712
759
2.05
2.71
3.50
4.43
5.54
599
644
690
736
782
2.21
2.91
3.73
4.69
5.82
624
667
712
758
804
2.37
3.09
3.96
4.96
6.11
648
689
733
778
824
2.54
3.26
4.16
5.20
6.39
671
711
753
797
843
2.71
3.45
4.35
5.43
6.67
695 2.90
732 3.64
773 4.55
816 5.65
861 6.92
720 3.11
752 3.83
792 4.75
834 5.86
878 7.16
527
578
629
681
2.08
2.79
3.65
4.67
5HPStandardMotor&Sheaves
(2)
7.5HPOversizedMotor&Sheaves
Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
5HPStandardMotor&Sheaves
5HPStandardMotor&HighStaticDriveAccessory
6400
7200
8000
8800
9600
744
773
811
852
895
3.32
4.04
4.96
6.08
7.40
768
795
830
869
911
3.52
4.27
5.18
6.30
7.63
790
817
848
887
928
3.72
4.50
5.40
6.53
7.86
811
839
867
904
944
3.91
4.74
5.64
6.77
8.11
833
860
887
921
960
4.13
4.96
5.90
7.01
855
880
907
938
976
4.36
5.19
6.16
7.26
8.61
877
898
927
955
—
4.59
5.41
6.42
7.52
—
897
917
946
973
—
4.82
5.64
6.68
7.81
—
917 5.05
937 5.88
964 6.93
991 8.09
936 5.29
957 6.14
982 7.18
—
—
—
—
8.36
—
—
7.5HPOversizedMotor&Sheaves
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBeltmaybenecessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt
maybenecessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/FanSpeed”tablestodetermineoperatingrange.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(25Ton)
Standard Efficiency
Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B
External Static Pressure (Inches of Water)
.40 .50 .60
.10
.20
.30
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5HPStandardMotor&LowStaticDriveAccessory
7.5HPStandardMotor&Sheaves
7000
7500
8000
8500
9000
9500
10000
10500
11000
—
—
—
—
—
—
593
624
655
686
717
749
781
812
844
2.42
2.88
3.39
3.97
4.62
5.34
6.13
7.00
619
649
679
710
741
772
804
835
867
2.62
3.10
3.63
4.23
4.89
5.62
6.42
7.31
8.3
643
673
702
732
763
794
825
856
887
2.80
3.31
3.86
4.47
5.15
5.90
6.72
7.62
667
695
724
754
784
814
844
875
—
2.98
3.50
4.07
4.71
5.41
6.18
7.01
7.93
—
690
717
745
774
803
833
863
894
—
3.16
3.68
4.28
4.94
5.66
6.45
7.31
8.24
—
712
738
766
794
822
852
881
911
—
3.35
3.88
4.48
5.15
5.89
6.71
7.59
8.54
—
733 3.53
759 4.08
786 4.68
813 5.36
841 6.12
870 6.95
899 7.86
754 3.73
779 4.28
805 4.90
832 5.58
859 6.35
887 7.19
916 8.11
595
627
659
691
723
755
788
821
2.66
3.16
3.73
4.36
5.06
5.84
6.69
7.63
595
628
661
695
729
762
796
2.92
3.47
4.08
4.76
5.52
6.35
7.27
—
—
—
—
—
—
—
—
7.96
8.60
7.5HPStandardMotor&HighStaticDriveAccessory
7.5HPStandardMotor&Sheaves
Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued
External Static Pressure (Inches of Water)
1.10
RPM
1.20
RPM
1.30
RPM
1.40
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
7.5HPStandardMotor&Sheaves
7000
7500
8000
8500
9000
9500
10000
10500
11000
776
798
824
850
877
904
933
—
3.95
4.48
5.11
5.81
6.58
7.43
8.36
—
798
818
842
868
894
921
949
—
4.18
4.71
5.32
6.03
6.81
7.67
8.62
—
820
839
860
885
911
938
—
4.40
4.95
5.55
6.26
7.05
7.92
—
841
860
880
902
928
954
—
4.62
5.19
5.80
6.49
7.29
8.17
—
862
880
899
920
944
970
—
4.84
5.42
6.06
6.74
7.53
8.42
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5HPStandardMotor&HighStaticDriveAccessory
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop
data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan
Speed” tables to determine operating range.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½Ton)
High Efficiency
Table PD-22 — Evaporator Fan Performance — 12½Ton — TCD151C — Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3 HP Standard Motor & Field
SuppliedLowStaticDrive(2)
3 HP Standard Motor & Field
SuppliedHighStaticDrive(2)
3 HP Standard Motor & Drive
2500*
3250*
4000
4500
5000
5500
6000
—
—
402
447
495
528
562
597
633
0.30
0.49
0.74
0.95
1.20
1.49
1.82
460
503
549
580
612
645
680
0.39
0.62
0.91
1.14
1.42
1.74
2.10
510
552
596
627
657
689
722
0.48
0.74
1.07
1.33
1.63
1.98
2.37
555
595
638
668
699
729
761
0.56
0.86
1.22
1.51
1.84
2.20
2.63
595
634
677
706
736
767
797
0.64
0.97
1.37
1.68
2.04
2.44
2.87
633
672
712
742
771
801
832
0.74
1.08
1.52
1.85
2.23
2.66
3.13
667
706
747
776
803
833
864
0.83
1.19
1.66
2.02
2.41
2.87
3.38
699 0.92
739 1.30
778 1.80
806 2.18
835 2.61
864 3.07
894 3.61
731 1.02
769 1.40
809 1.94
836 2.34
865 2.80
893 3.28
922 3.83
378
430
466
503
540
579
0.35
0.56
0.74
0.96
1.22
1.53
5HPOversizeMotor&Drive
3HPStandardMotor&HighStaticDriveAccessory
Table PD-22 — Evaporator Fan Performance — 12½ Ton — TCD151C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
RPM
BHP
BHP
BHP
BHP
3HPStandardMotor&Drive
3HPStandardMotor&HighStaticDriveAccessory
2500*
3250*
4000*
4500
5000
5500
760
798
839
865
892
922
950
1.11
1.52
2.07
2.50
2.97
3.49
4.05
789
827
867
892
920
949
977
1.21
1.64
2.21
2.66
3.15
3.70
4.29
817
853
893
919
946
975
1.31
1.76
2.33
2.81
3.33
3.90
4.51
842
880
919
945
971
999
1028
1.41
1.88
2.47
2.96
3.50
4.09
4.74
868
905
943
970
996
1023
1052
1.51
2.01
2.59
3.11
3.68
4.28
4.96
892
928
967
1.60
2.13
2.73
3.25
3.85
4.48
5.16
916
953
991
1017
1043
1070
1098
1.71
2.26
2.88
3.40 1039
4.02 1066
4.68 1091
939
976
1013
1.81
2.38
962 1.91
998 2.51 1020 2.63
984 2.01
3.03 1036 3.18 1056.4 3.33
3.55 1061 3.70 1082.3 3.85
4.18 1088 4.35 1109.6 4.50
4.87
5.59
994
1020
1047
1074
1114 5.06 1135.6 5.24
6000
1002
5.38
1120
—
—
—
—
5HPOversizedMotor&Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 4000 CFM
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
•
•
Electric heaters restricted on applications below 4000 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. FieldSuppliedFanSheaveBK115Required. FieldSuppliedBeltmaybenecessary.
RT-PRC002-EN
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½Ton)
High Efficiency
Table PD-23 — Evaporator Fan Performance — 12½Ton — T*D151C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3HPStandardMotor&Drivew/Field
SuppliedLowStaticDriveFanSheave
3HPStandardMotor&Drive
2500*
3000*
3500*
4000
4500
5000
5500
6000
—
—
—
—
—
—
526
578
633
692
753
816
881
947
0.52
0.74
1.03
1.40
1.87
2.44
3.13
3.93
570
618
670
727
785
846
908
972
0.62
0.86
1.16
1.55
2.03
2.61
3.32
4.15
609
656
706
759
815
874
935
996
0.73
0.98
1.30
1.71
2.20
2.79
3.51
4.36
646
692
739
791
844
902
960
1021
0.83
1.11
1.44
1.86
2.37
2.98
3.70
4.56
681
725
771
821
873
928
985
1044
0.93
1.23
1.58
2.01
2.54
3.17
3.91
713
756
802
850
901
954
1010
1.03
1.35
1.73
2.17
2.71
3.37
744 1.14
786 1.48
831 1.88
878 2.34
928 2.89
979 3.56
776 1.25
814 1.60
859 2.02
905 2.50
953 3.07
1004 3.75
534
594
656
720
786
853
921
0.63
0.90
1.26
1.71
2.26
2.91
3.70
551
618
686
755
824
894
0.78
1.11
1.54
2.07
2.71
3.47
4.13 1033 4.34 1056 4.54
5.01 1090 5.24
4.78 1068
1112 5.47
5HPOversizedMotor&Drive
3HPStandardMotor&HighStaticDriveAccessory
Table PD-23 — Evaporator Fan Performance — 12½ Ton — T*D151C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM BHP
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM BHP
1.80
RPM BHP
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
3HPStandardMotor&HighStaticDriveAccessory
3HPStandardMotor
&Drive
804
842
885
930
2500*
3000*
3500*
4000
4500
5000
5500
6000
1.36
1.73
2.17
2.67
3.25
3.94
4.76
5.70
832
869
1.48
1.85
2.31
2.85
3.44
4.14
4.97
—
859
895
1.59
1.98
2.45
3.01
3.63
4.35
5.17
—
883
920
1.71
2.11
2.59
3.17
3.83
4.55
5.40
—
908
945
983
1.83
2.24
2.74
3.34
4.02
4.76
5.62
—
931
968
1006
1047
1093
1140
—
1.95
2.38
2.89
3.50
4.21
4.98
—
954
991
1029
1069
1113
1159
—
2.08
2.51
3.04 1051
3.66 1090
4.38
5.18
—
977
1014
2.21
998 2.33
1020 2.47
2.65 1035 2.79 1057 2.94
910
935
959
3.19
3.82
4.57
5.40
—
1072 3.34 1093 3.49
956
980
1003
1049
1096
1146
—
1026
1071
1118
1166
—
1110 3.99
1154 4.75
1200 5.61
—
—
1132 4.16
1174 4.94
—
—
—
978
1002
1051
1102
—
1026
1074
1123
—
1134
1180
—
1028
1079
1133
—
—
—
—
—
—
—
—
—
—
—
5HPOversizedMotor&Drivew/FieldSuppliedFanSheave
5HPOversizedMotor&Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
*Unit applications below 4000 CFM
•
•
Electric heaters restricted on applications below 4000 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. FieldSuppliedFanSheaveBK115Required. FieldSuppliedBeltmaybenecessary.
RT-PRC002-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½Ton)
High Efficiency
Table PD-24 — Evaporator Fan Performance — 12½Ton — TCH151C — Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3HPStandardMotor&FieldSuppliedLowStaticDrive(1)
3HPStandardMotor&Drive
4000
4500
5000
5500
6000
—
—
534
581
628
—
—
1.40
1.83
2.34
—
—
510
551
593
637
682
0.98
1.29
1.67
2.13
2.68
541
579
620
661
704
1.10
1.42
1.81
2.28
2.83
572
607
645
685
727
1.22
1.56
1.95
2.43
3.00
602
635
671
709
749
1.35
1.68
2.11
2.59
3.16
631
662
696
732
770
1.48
1.82
2.25
2.76
3.33
659
688
720
754
791
1.62
1.98
2.40
2.92
3.52
687 1.76
713 2.13
744 2.56
777 3.08
812 3.70
714 1.91
738 2.28
767 2.73
799 3.25
833 3.87
521
566
611
657
1.17
1.54
1.99
2.51
5HPOversizedMotor&Drive
Table PD-24 — Evaporator Fan Performance — 12½ Ton — TCH151C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
3HPStandardMotor&Drive
3HPStandardMotor&HighStatic
DriveAccessory
4000
4500
5000
5500
6000
740
763
790
820
853
2.07
2.44
2.90
3.43
4.04
766
787
812
842
874
2.23
2.61
3.07
3.61
4.23
791
811
835
862
893
2.38
2.78
3.24
3.80
4.43
814
835
857
883
913
2.54
2.96
3.42
3.98
4.63
838
858
879
904
932
2.70
3.13
3.61
4.17
4.83
860
880
901
924
951
2.86
3.31
3.81
4.37
5.03
883
901
922
944
970
3.02
3.48
4.00
4.57
5.24
905
922
942
964
988
3.19
3.66
4.20
4.78
5.45
926 3.37
943 3.84
962 4.39
984 4.99
1007 5.66
948 3.55
963 4.02
982 4.59
1003 5.20
—
—
5HPOversizedMotor&Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop
due to other options/accessories.
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
Note:
1. FieldSuppliedFanSheaveBK115Required. FieldSuppliedBeltmaybenecessary.
RT-PRC002-EN
38
Download from Www.Somanuals.com. All Manuals Search And Download.
(15Ton)
High Efficiency
Performance
Data
Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3 HP Standard Motor &
FieldSuppliedExtra
LowStaticDrive(2)
3 HP Standard Motor & Field
SuppliedLowStaticDrive(1)
3000*
3900*
4800
5400
6000
6600
7200
—
—
337
384
437
474
513
552
591
0.32
0.55
0.89
1.19
1.55
1.98
2.49
387
423
471
506
543
580
618
0.42
0.66
1.01
1.33
1.72
2.17
2.70
432
462
503
536
571
606
643
0.53
0.78
1.14
1.47
1.87
2.35
2.91
472
500
535
564
597
632
667
0.65
0.91
1.29
1.62
2.03
2.52
3.09
511
536
566
592
623
656
690
0.77
1.05
1.44
1.78
2.19
2.69
3.27
547
569
598
621
648
679
712
0.90
1.19
1.60
1.95
2.36
2.87
3.46
580
600
629
648
673
702
734
1.03
1.35
1.77
2.12
2.55
3.05
3.65
611 1.16
630 1.51
658 1.94
676 2.30
699 2.74
725 3.25
755 3.85
640 1.29
660 1.67
684 2.11
704 2.49
723 2.93
748 3.46
776 4.06
341
399
445
479
519
560
0.45
0.76
1.04
1.38
1.79
2.28
3HPStandardMotor&Drive
5HPOversizedMotor&Drive
Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM BHP
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
RPM
BHP
3HPStandardMotor&Drive
3 HP Standard Motor & High
StaticDriveAccessory
3000*
3900*
4800
5400
6000
6600
7200
667
688
710
730
749
771
797
1.43
1.84
2.29
2.68
3.13
3.67
4.29
693
715
735
755
774
794
818
1.57
2.00
2.48
2.88
3.34
3.88
4.51
717
741
760
778
798
816
839
1.71
2.17
2.68
3.07
3.56
4.09
4.74
740
766
785
800
821
839
860
1.86
2.34
2.88
3.28
3.77
4.32
4.96
763
790
809
823
842
862
881
2.01
2.51
3.09
3.49
3.99
4.56
5.20
784
812
832
845
863
884
902
2.16
2.68
3.29
3.71
4.20
4.80
5.45
805
834
854
867
884
904
923
2.31
2.85
3.49
3.94
4.43
5.03
5.70
825
855
876
889
904
924
—
2.47
3.03
3.69
4.17
4.66
5.27
—
845 2.63
875 3.21
898 3.90
910 4.40
924 4.90
943 5.51
864 2.80
895 3.39
919 4.10
931 4.62
944 5.15
961 5.75
—
—
—
—
5HPOversizedMotor&Drive
Factory supplied motors, in commercial equipment, are
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 4000 CFM
•
•
Electric heaters restricted on applications below 4000 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heaters
are required on applications below 4000 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/ccessories.
Note:
1. FieldSuppliedFanSheaveBK120Required. FieldSuppliedBelt maybenecessary.Field
SuppliedBeltmaybenecessary.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(15Ton)
High Efficiency
Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
3HPStandardMotorw/Field 3HPStandardMotorw/Field
SuppliedMotorSheave(2) SuppliedMotorSheave(1)
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3HPStandardMotorw/FieldSupplied
LowStaticDriveFanSheave
3000*
3600*
4200*
4800
5400
6000
6600
7200
295
333
373
414
455
497
540
583
0.26
0.40
0.60
0.84
1.14
1.51
1.96
2.50
346
379
415
452
491
531
572
613
0.35
0.51
0.72
0.99
1.32
1.73
2.20
2.75
391
420
452
487
524
561
601
641
0.45
0.62
0.85
1.13
1.48
1.91
2.42
3.02
432
458
487
519
554
590
628
666
0.56
0.74
0.98
1.27
1.64
2.08
2.61
3.23
471
494
520
550
582
617
653
690
0.68
0.87
1.12
1.43
1.80
2.26
2.80
3.44
506
527
551
579
610
643
678
714
0.80
1.00
1.26
1.59
1.98
2.44
2.99
3.65
539
559
581
607
637
667
701
736
0.92
1.14
1.41
1.74
2.15
2.63
3.20
3.86
569
589
610
635
662
692
724
758
1.04
1.28
1.57
1.91
2.33
2.83
3.41
4.08
596 1.17
617 1.43
638 1.73
660 2.08
687 2.51
715 3.02
746 3.61
778 4.30
622 1.30
644 1.57
664 1.89
686 2.26
710 2.70
739 3.22
768 3.83
799 4.53
3HPStandardMotor&Drive
5HPOversizedMotor&Drive
Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
3HPStandardMotor&Drive
3 HP Standard Motor &
HighStaticDriveAccessory
3000*
3600*
4200*
4800
5400
6000
6600
7200
646
669
690
711
734
761
789
819
1.43
1.72
2.06
2.44
2.89
3.42
4.05
4.76
669
694
715
735
758
782
810
840
1.56
1.88
2.23
2.63
3.09
3.63
4.26
5.00
692
716
737
758
780
804
831
859
1.70
2.02
2.39
2.81
3.29
3.84
4.49
5.23
714
738
760
780
801
824
850
879
1.84
2.18
2.57
3.00
3.49
4.05
4.71
5.47
734
759
782
802
822
845
870
898
1.98
2.34
2.74
3.19
3.69
4.27
4.94
5.72
755
778
803
823
844
865
889
—
2.13
2.49
2.92
3.38
3.91
4.49
5.18
—
775
798
822
843
864
885
908
—
2.28
2.66
3.09
3.58
4.12
4.72
5.41
—
793
817
842
864
883
904
927
—
2.42
2.82
3.28
3.78
4.33
4.95
5.65
—
813 2.58
835 2.98
861 3.46
882 3.97
903 4.55
923 5.18
830 2.72
854 3.16
878 3.64
901 4.17
921 4.76
941 5.41
—
—
—
—
—
—
—
—
5HPOversizedMotor&Drive
3HPStandardMotor&HighStaticDriveAccessory
Factory supplied motors, in commercial equipment, are
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 4800 CFM
•
•
Electric heaters restricted on applications below 4800 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 4800 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options accessories.
Note:
1. FieldSuppliedFanSheaveBK120Required. FieldSuppliedBelt maybenecessary.Field
SuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveBK160Required. FieldSuppliedBelt maybenecessary.Field
SuppliedBeltmaybenecessary.
RT-PRC002-EN
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(17½Ton)
High Efficiency
Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5 HP Standard Motor &
FieldSuppliedLowStaticDrive(1)
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
5 HP Standard Motor
&FieldSuppliedExtra
LowStaticDrive(2)
448
490
547
588
631
675
720
3500*
4550*
5600
6300
7000
7700
8400
—
—
452
499
546
594
642
—
—
1.14
1.63
2.11
2.75
3.52
—
—
487
532
578
625
671
—
—
1.30
1.76
2.31
2.98
3.78
—
—
0.66
1.03
1.60
2.10
2.71
3.43
4.27
488
524
575
614
655
698
741
0.78
1.17
1.75
2.26
2.89
3.64
4.51
523
557
602
639
678
720
762
0.91
1.32
1.91
2.43
3.07
3.84
4.73
557
590
629
663
701
741
782
1.05
1.48
2.08
2.60
3.25
4.03
4.95
590
621
656
687
723
761
802
1.20
1.64
2.26
2.79
3.44
4.23
5.16
622 1.35
649 1.80
683 2.43
711 2.99
744 3.64
782 4.44
821 5.38
652 1.50
676 1.97
710 2.63
735 3.19
766 3.85
801 4.65
840 5.60
457
518
561
606
651
697
0.90
1.45
1.94
2.52
3.21
4.03
5 HP Standard Motor &
HighStaticDriveAccessory
Table PD-27— Evaporator Fan Performance — 17½ Ton — TC*211C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
1.80
RPM BHP
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
RPM
BHP
5HPStandardMotor&Drive
5 HP Standard Motor & High
StaticDriveAccessory
3500*
4550*
5600
6300
7000
7700
8400
680
703
736
759
788
821
858
1.65
2.15
2.83
3.38
4.07
4.87
5.82
707
729
761
783
810
841
876
1.80
2.34
3.03
3.59
4.29
5.10
6.06
732
754
785
807
831
861
894
1.95
2.54
3.23
3.82
4.51
5.34
6.30
756
779
807
830
852
881
912
2.11
2.73
3.43
4.04
4.74
5.59
6.55
779
803
829
853
874
900
930
2.27
2.92
3.64
4.27
4.97
5.83
6.81
801
827
851
874
895
919
949
2.43
3.11
3.86
4.49
5.22
6.07
7.08
822
849
872
894
917
939
967
2.60
3.31
4.09
4.72
5.47
6.32
7.34
843
871
893
913
937
958
984
2.77
3.50
4.32
4.95
5.72
6.58
7.60
863 2.94
892 3.70
914 4.56
933 5.19
957 5.97
978 6.85
1002 7.87
882 3.11
913 3.89
935 4.80
952 5.43
975 6.22
997 7.12
—
—
7.5OversizeMotor&Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 5600 CFM
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
•
•
Electric heaters restricted on applications below 5600 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 5600 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBelt maybenecessary.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(20Ton)
High Efficiency
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
5 HP Standard Motor & Field Supplied
ExtraLowStaticDrive(3)
5 HP Standard Motor & Field
SuppliedLowStaticDrive(1)
4000*
5200*
6400
7200
8000
8800
9600
—
—
—
—
428
494
570
620
672
724
776
0.69
1.22
2.03
2.72
3.56
4.55
5.74
467
524
595
646
696
747
799
0.82
1.35
2.19
2.92
3.80
4.83
6.04
504
555
620
668
719
769
820
0.95
1.51
2.34
3.10
4.02
5.10
6.34
538
585
644
690
739
790
840
1.08
1.67
2.51
3.27
4.22
5.34
6.63
572
614
669
711
759
808
859
1.23
1.83
2.69
3.45
4.41
5.56
6.90
603
642
693
733
778
826
876
1.38
2.00
2.89
3.65
4.60
5.77
7.14
632 1.55
670 2.17
717 3.09
755 3.86
797 4.81
844 5.98
893 7.37
660 1.71
696 2.35
741 3.29
777 4.08
817 5.03
861 6.20
909 7.59
426
506
560
616
671
728
0.94
1.64
2.28
3.07
4.04
5.19
463
540
592
645
698
753
1.09
1.84
2.50
3.31
4.29
5.46
5HPStandardMotor&Drive
(2)
7.5HPOversizedMotor&Drive
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
5HPStandardMotor&Drive
5 HP Standard Motor
&HighStaticDriveAccessory
4000*
5200*
6400
7200
8000
8800
9600
688
722
765
799
837
879
925
1.87
2.54
3.49
4.31
5.26
6.43
7.83
714
747
788
820
857
897
941
2.03
2.73
3.70
4.53
5.51
6.67
8.07
739
771
810
841
876
915
958
2.20
2.93
3.91
4.76
5.76
6.93
8.32
764
795
832
862
896
933
974
2.36
3.14
4.12
4.99
6.01
7.19
787
817
854
883
915
951
—
2.53
3.35
4.34
5.22
6.26
7.46
—
810
839
875
902
934
969
—
2.70
3.56
4.57
5.46
6.52
7.74
—
831
861
896
922
953
986
—
2.87
3.77
4.80
5.69
6.77
8.01
—
852
882
916
942
971
—
3.05
3.98
5.04
5.94
7.03
—
873 3.23
902 4.19
936 5.29
961 6.19
989 7.29
892 3.41
923 4.41
955 5.54
980 6.44
—
—
—
—
—
—
—
—
—
—
8.58
—
—
7.5HPOversizedMotor&Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 6400 CFM
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
•
•
Electric heaters restricted on applications below 6400 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 6400 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBelt maybenecessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt
maybenecessary.
3. FieldSuppliedFanSheaveB5V200andMotorSheaveIVP34required.FieldSuppliedBeltmay
benecessary.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(20Ton)
High Efficiency
Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
5 HP Standard Motor & Field
SuppliedFanSheave(1)
5 HP Standard Motor & Drive & Field Supplied
LowStaticFanSheave
5HPStandard
Motor&Drive
4000*
4800*
5600*
6400
7200
8000
8800
9600
—
—
—
—
441
487
536
588
641
695
750
805
0.77
1.13
1.61
2.24
3.02
3.93
5.03
6.32
477
519
566
615
666
719
773
827
0.90
1.27
1.78
2.42
3.23
4.21
5.35
6.68
511
550
594
641
690
742
794
848
1.03
1.43
1.95
2.61
3.44
4.45
5.65
7.04
543
579
620
666
714
763
815
867
1.17
1.59
2.12
2.80
3.65
4.67
5.91
7.35
573
607
647
689
736
785
835
886
1.32
1.74
2.30
3.00
3.86
4.91
6.15
7.63
603
635
672
713
758
805
854
904
1.47
1.91
2.49
3.20
4.08
5.14
6.41
7.90
631 1.63
658 1.78
686 2.26
720 2.87
758 3.62
799 4.53
844 5.62
892 6.93
941 8.46
414
469
525
583
641
699
758
0.84
1.25
1.80
2.50
3.37
4.42
5.67
452
504
558
613
669
725
782
0.99
1.45
2.03
2.75
3.64
4.72
6.00
660 2.08
696 2.67
736 3.41
778 4.30
825 5.38
873 6.66
923 8.18
7.5HPOversizedMotor&Drive
(3)
5HPStandardMotor&HighStaticDrive
Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
RPM RPM RPM
1.10
RPM
1.20
RPM
1.30
RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
5HPStandardMotor&Drive
5 HP Standard Motor
&HighStaticDrive
4000*
4800*
5600*
6400
7200
8000
8800
9600
684
711
743
779
819
863
909
—
1.94
2.44
3.06
3.82
4.76
5.87
7.19
708
735
765
800
840
881
927
—
2.10
2.63
3.26
4.04
5.00
6.12
7.46
—
731
758
787
821
859
900
944
—
2.27
2.81
3.46
4.26
5.23
6.38
7.73
—
753
780
809
841
879
918
961
—
2.43
3.00
3.67
4.48
5.47
6.64
8.01
—
775
802
830
861
898
936
978
—
2.60
3.19
3.88
4.70
5.72
6.90
8.29
—
795
823
850
881
916
954
994
—
2.77
3.38
4.09
4.93
5.96
7.16
8.56
—
814
843
871
899
933
971
—
2.94
3.58
4.31
5.16
6.19
7.42
—
834
864
890
919
952
988
—
3.12
3.78
4.53
5.41
6.46
7.69
—
852 3.29
882 3.97
910 4.75
938 5.66
968 6.70
870 3.47
901 4.17
929 4.98
956 5.90
987 6.97
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5HPOversizedMotor&Drive
Factory supplied motors, in commercial equipment, are
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 6400 CFM
•
•
Electric heaters restricted on applications below 6400 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 6400 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. FieldSuppliedMotorSheaveIVP34Required. FieldSuppliedBelt maybenecessary.
2. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBelt maybenecessary.
3. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt
maybenecessary.
RT-PRC002-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(25Ton)
High Efficiency
Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Standard Refrigeraton System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
7.5HPStandardMotor&FieldSuppliedExtraLowStaticDrive(1)
7.5HPStandardMotor&LowStaticDriveAccessory
5000*
6500*
7000*
7500*
8000
8500
9000
—
—
—
—
—
—
—
—
—
—
—
—
576
649
678
708
739
771
802
834
866
898
—
1.56
2.59
3.06
3.61
4.22
4.90
5.65
6.46
7.35
8.31
—
606
674
700
729
759
790
821
853
884
916
—
1.71
2.78
3.25
3.79
4.41
5.10
5.88
6.72
7.64
8.62
—
635
698
723
749
778
808
839
870
902
—
1.88
2.97
3.44
3.98
4.60
5.31
6.09
6.96
7.90
—
663 2.05
722 3.18
745 3.65
770 4.19
797 4.81
826 5.52
856 6.30
887 7.18
918 8.14
690 2.22
746 3.38
768 3.87
792 4.41
817 5.03
844 5.74
873 6.53
903 7.41
934 8.38
—
—
—
576
608
640
672
704
737
770
803
836
870
2.11
2.54
3.02
3.56
4.16
4.83
5.58
6.41
7.33
8.33
601
633
665
696
728
760
792
825
858
891
2.27
2.73
3.24
3.80
4.43
5.12
5.88
6.72
7.64
8.63
625
656
687
719
750
782
814
846
878
—
2.43
2.89
3.43
4.02
4.68
5.39
6.18
7.04
7.98
—
—
579
611
645
678
712
746
780
814
849
2.32
2.78
3.31
3.90
4.56
5.30
6.12
7.03
8.02
582
616
650
685
721
756
791
827
2.59
3.07
3.66
4.31
5.04
5.85
6.74
7.71
9500
10000
10500
11000
—
—
—
—
—
—
—
—
—
—
7.5 HP Standard Motor & Drive
7.5HPStandardMotor& HigherStaticDriveAccessory
Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Continued
External Static Pressure (Inches of Water)
1.10
RPM
1.20
RPM
1.30
RPM
1.40
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
7.5 HP Standard Motor & Drive
5000*
6500*
7000*
7500*
8000
8500
9000
716
769
790
813
837
863
890
919
949
—
2.41
3.59
4.09
4.65
5.26
5.97
6.76
7.64
8.62
—
741
792
812
833
857
881
908
936
—
2.60
3.80
4.31
4.88
5.51
6.21
7.00
7.88
—
765
814
833
854
876
900
925
952
—
2.80
4.01
4.53
5.12
5.76
6.46
7.25
8.13
—
789
836
854
874
896
919
943
969
—
3.00
4.22
4.76
5.36
6.01
6.73
7.52
8.40
—
812
857
875
894
915
937
961
985
—
3.20
4.44
4.99
5.59
6.26
6.99
7.79
8.67
—
9500
10000
10500
11000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5HPStandardMotor&HighStaticDriveAccessory
Factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range
of our fan motors as shown in our tabular
data will not result in nuisance tripping or
premature motor failure. Our product’s
warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM),
referenceTablePD-32.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM),
referenceTablePD-34.
Fan motor heat (MBH) = 3.15 x Fan BHP
*Unit applications below 8000 CFM
•
Electric heaters restricted on applications below 8000
CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat
and Crankcase Heaters are required on applications
below 8000 CFM.
•
Notes:
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to
other options/accessories.
*Indicatesbothdownflowandhorizontalunits.
RT-PRC002-EN
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½-25 Ton)
Table PD-31— Standard Motor & Drive/Fan Speed (Rpm)
Unit
6Turns
Open
640
5Turns
Open
680
4Turns
Open
720
3Turns
Open
760
2Turns
Open
800
1Turn
Open
840
Tons Model No.
Closed
N/A
N/A
N/A
941
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TC*150D3,4,W, TC*151C3,4,W
TC*150DK
12½
705
756
806
857
907
957
TC*180B3,4,W
TC*180BK
TC*181C3,4,W
679
N/A
560
869
869
615
615
590
705
721
680
600
923
924
659
659
627
764
733
640
978
978
703
703
664
806
785
680
1032
1032
747
747
701
849
837
720
1087
1087
791
791
738
891
889
760
1141
1141
835
835
775
15
TC*210C3,4,W
17½ TC*210CK
TC*211C3,4,W
TC*240B3,4,W,TC*241C3,4,W
TC*240BK
TC*300B/301C3,4,W
TC*300BK
20
742
738
779
775
817
812
854
849
891
886
25
701
Factory set at 3 turns open.
Table PD-32— Standard Motor & High Static Drive Accessory/Fan Speed (Rpm)
Unit
Model No.
6Turns
Open
807
806
640
835
835
816
5Turns
Open
857
849
680
879
879
853
4Turns
Open
908
891
720
923
923
890
3Turns
Open
958
934
760
967
967
928
2Turns
Open
1009
976
1Turn
Tons
12½
Open
1059
1019
840
1055
1055
1002
Closed
TC*151C3,4,W
TC*180B3,4,W
TC*181B3,4,W
TC*211C3,4,W
TC*240B/241C3,4,W
TC*300B/301C3,4,W
N/A
N/A
N/A
N/A
N/A
N/A
15
800
17½
20
25
1011
1011
965
Table PD-33— Oversized Motor & Drive/Fan Speed (Rpm)
Unit
6Turns
Open
869
806
705
5Turns
Open
923
856
755
4Turns
Open
978
907
806
3Turns
2Turns
1Turn
Tons Model No.
12½ TC*150D,151C3,4,W
Open
1032
957
Open
1087
1008
907
Open
1141
1058
957
Closed
N/A
N/A
TC*180B3,4,W
15
TC*181C3,4,W
856
N/A
TC*210C3,4,W
TC*211C3,4,W
949
816
1008
853
1068
890
1127
928
1187
965
1246
1002
N/A
N/A
17½
20
TC*240B/241C3,4,W
816
853
890
928
965
1002
N/A
Table PD-34 — Standard Motor & Low Static Fan Drive
Unit
6Turns
Open
5Turns
Open
4Turns
Open
3Turns
Open
2Turns
Open
1Turn
Open
Tons Model No.
Closed
N/A
17½ TC*210C3,4,W
705
594
755
631
806
668
856
705
907
742
957
779
25
TC*300B/301C3,4,W
N/A
*Indicates both downflow and horizontal units.
RT-PRC002-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½-25 Ton)
Table PD-35 — Static Pressure Drops Through Accessories (Inches Water Column)
Economizerwith
OA/RADampers2
Filters1 Reheat Coil Pleated Filters4 100% OA
Electric Heater
Unit
ModelNo.
Standard
Through
2 Inch
Accessory (KW)3
Tons
12½
CFM
4000
5000
6000
2500
4000
5000
6000
4800
6000
7200
3000
4800
6000
7200
4800
6000
7200
5600
7000
8400
3500
5600
7000
8400
5600
7000
8400
6400
8000
9600
4000
6400
8000
9600
6400
8000
9600
7000
9000
11000
5000
7000
9000
11000
7000
9000
11000
100% RA
0.02
0.03
0.04
0.01
0.02
0.03
0.04
0.03
0.04
0.05
0.03
0.03
0.04
0.05
0.03
0.04
0.05
0.04
0.05
0.06
0.03
0.04
0.04
0.06
0.04
0.04
0.06
0.04
0.05
0.07
0.03
0.04
0.05
0.07
0.04
0.05
0.07
0.04
0.07
0.10
0.03
0.04
0.07
0.10
0.04
0.07
0.10
5-12
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
14-27
0.03
0.04
0.06
*
0.03
0.04
0.06
0.04
0.06
0.09
*
0.04
0.06
0.09
0.04
0.06
0.09
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
36
54
72
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.05
0.07
0.10
0.02
0.05
0.07
0.10
0.07
0.10
—
—
—
0.01
0.03
0.05
0.06
—
0.08
0.11
0.15
0.03
0.08
0.11
0.15
0.10
0.15
0.19
0.26
0.33
0.07
0.19
0.26
0.33
0.25
0.33
0.40
0.07
0.14
0.20
0.27
0.14
0.20
0.27
0.30
0.39
0.47
0.09
0.18
0.26
0.35
0.18
0.26
0.35
0.22
0.32
0.44
0.11
0.22
0.32
0.44
0.22
0.32
0.44
0.26
0.40
0.57
0.15
0.26
0.40
0.57
0.26
0.40
0.60
0.03
0.05
0.07
*
0.04
0.06
0.09
*
TC*150D,TCH151C
TCD151C
0.03
0.05
0.07
0.04
0.07
0.10
*
0.04
0.06
0.09
0.05
0.08
0.12
*
TC*180B
TCD181C
—
—
0.15
0.19
0.02/0.01
0.04/0.03
0.06/0.05
0.09/0.07
0.04/0.03
0.06/0.05
0.09/0.07
0.09
0.01
0.02
0.03
0.04
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.02
0.04
0.05
0.07
—
—
—
—
—
—
—
—
—
0.03/0.02
0.07/0.06
0.10/0.09
0.13/0.11
0.07/0.06
0.10/0.09
0.13/0.11
0.13
0.04
0.07
0.10
0.04
0.07
0.10
0.06
0.10
0.15
*
0.05
0.08
0.12
0.05
0.08
0.12
0.07
0.11
0.17
*
15
TCH181C
TC*210C
—
—
—
—
0.14
0.20
0.18
0.24
0.02/0.02
0.06/0.05
0.09/0.07
0.12/0.10
0.06/0.05
0.09/0.07
0.12/0.10
0.07
0.11
0.16
0.03
0.07
0.11
0.16
0.06
0.09
0.13
0.09
0.14
0.21
0.03/0.03
0.09/0.08
0.13/0.11
0.17/0.14
0.09/0.08
0.13/0.11
0.17/0.14
0.11
0.15
0.20
0.04
0.11
0.15
0.20
0.10
0.13
0.17
0.13
0.18
0.25
*
0.05
0.08
0.12
0.05
0.08
0.12
0.06
0.10
0.14
*
0.06
0.09
0.13
0.06
0.09
0.13
0.08
0.12
0.17
*
0.07
0.11
0.16
0.07
0.11
0.16
0.09
0.14
0.20
*
0.09
0.14
0.20
0.09
0.14
0.20
0.11
0.18
0.26
*
17½
TCD211C
TCH211C
TCD240B
0.06
0.10
0.14
0.06
0.10
0.14
0.08
0.13
0.18
*
0.08
0.12
0.17
0.08
0.12
0.17
0.10
0.15
0.22
*
20
TCD241C
TCH240B,TCH241C
TCD300B
0.04
0.09
0.14
0.21
0.07
0.11
0.17
0.06
0.13
0.18
0.25
0.11
0.15
0.22
0.08
0.13
0.18
0.08
0.13
0.18
0.10
0.15
0.22
0.10
0.15
0.22
0.11
0.18
0.26
0.11
0.18
0.26
25
TCD301C
—
—
—
—
—
—
—
—
TCH300B,TCH301C
—
Notes:
1. Tested with: 2” filters 12½-25 tons
2. OA = Outside Air and RA = Return Air.
3. NominalKWratingsat240, 480, 600volts.
4. Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
*Heaters not permitted at airflows below 320 cfm/ton.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(12½-25 Ton)
Table PD-36 — Auxiliary Electric Heat Capacity
Total2
Stage1
Stage 2
Unit
ModelNo.
KW
Input1
MBH
Output1
No. of
Stages
KW
Input1
MBH
Output1
KW
Input1
MBH
Output1
Tons
18.00
27.004
36.00
54.00
61.47
92.15
122.94
184.41
1
2
2
2
18.00
9.00
18.00
36.00
61.47
30.72
61.47
—
—
TC*150D3,D4,DW,DK
TC*180B3,B4,BW,BK
TC*151 or 181C3,C4,CW
18.00
18.00
18.00
61.43
61.47
61.47
12½-15
122.94
TC*210C3,C4,CW,CK
TC*240, 300B3,B4,BW,BK
TC*211, 241, 301C3,C4,CW
36.00
54.00
72.003
122.94
184.41
245.88
2
2
2
18.00
36.00
36.00
61.47
122.94
122.94
18.00
18.00
36.00
61.47
61.47
122.94
17½, 20, 25
Notes:
2
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =
3. NotavailableonTC*210C.
Voltage
x rated cap.
(
)
RatedVoltage
4. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.
Table PD-37 — Electric Heater Voltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal
Voltage
Distribution
Voltage
Capacity
Multiplier
208
230
240
0.75
0.92
1.00
240
480
600
440
460
480
0.84
0.94
1.00
540
575
600
0.81
0.92
1.00
Table PD-38 — Air Temperature Rise Across Electric Heaters (Degree F)
12½Ton
15Ton
17½Ton
20Ton
25Ton
5000CFM
6000CFM
7000CFM
8000CFM
9000CFM
ThreePhase ThreePhase ThreePhase ThreePhase ThreePhase
TC*150
TC*151
—
—
11.4
—
22.8
34.1
—
TC*180
TC*181
—
—
9.5
14.22
19.0
28.5
—
TC*210
TC*211
—
—
—
12.221
16.3
24.4
32.5
TC*240
TC*241
—
—
—
10.72
14.2
21.3
28.5
TC*300
TC*301
—
—
—
9.52
12.6
19.0
25.3
KW
9.00
Stages
1
1
1
2
2
2
2
17.30
18.00
27.00
36.00
54.00
72.002
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
KW x 3413
Temp. Rise across Elect. Htr =
1.08 x CFM
Notes:
1.NotavailableonTC*210model.
2. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.
RT-PRC002-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-39— Hot Gas Reheat Temperature Rise1,2,3
Leaving Evaporator Dry Bulb [F]1
Tons
SCFM
2500
3000
3500
4000
4500
5000
5500
6000
35
40
45
50
55
60
65
23.4
21.4
19.5
17.8
16.3
14.9
13.5
12.1
23.8
21.6
19.7
18.1
16.7
15.5
14.4
13.4
25.0
22.5
20.4
18.6
17.3
16.2
15.3
14.6
26.9
24.0
21.5
19.6
18.1
17.1
16.2
15.7
29.5
26.0
23.1
20.9
19.2
18.0
17.2
16.7
32.9
28.7
25.2
22.5
20.5
19.2
18.1
17.6
37.0
31.9
27.7
24.5
22.1
20.4
19.1
18.3
12½
Tons
15
SCFM
3000
3600
4200
4800
5400
6000
6600
7200
35
40
45
50
55
60
65
34.4
29.3
25.4
22.3
19.9
18.0
16.4
15.1
36.7
31.2
27.0
23.7
21.2
19.1
17.5
16.1
38.9
33.1
28.6
25.1
22.4
20.3
18.6
17.1
41.2
35.0
30.2
26.5
23.7
21.4
19.6
18.1
43.5
36.9
31.9
27.9
24.9
22.5
20.7
19.1
45.8
38.8
33.5
29.3
26.2
23.7
21.7
20.1
48.1
40.8
35.1
30.7
27.4
24.8
22.8
21.1
Tons
20
SCFM
4000
4800
5600
6400
7200
8000
8800
9600
35
40
45
50
55
60
65
22.0
19.1
16.6
14.7
13.5
12.9
12.5
12.4
22.5
19.8
17.4
15.5
14.1
13.2
12.9
12.8
23.6
20.9
18.4
16.3
14.7
13.7
13.3
13.1
25.4
22.3
19.5
17.2
15.4
14.2
13.7
13.5
27.7
24.0
20.9
18.2
16.2
14.8
14.2
13.9
30.6
26.1
22.4
19.3
17.0
15.5
14.8
14.5
34.0
28.5
24.0
20.6
17.9
16.2
15.4
15.0
Notes:
1. Temperature does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.
RT-PRC002-EN
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone
CO2 Sensing The CO2 sensor has the
ability to monitor space occupancy levels
within the
Field Installed Control Options
Zone Sensors
Zone sensors are the building occupant’s
comfort control devices.They replace the
conventional electro-mechanical
thermostats.The following zone sensor
options are available forVoyager units
with the ReliaTel™ control:
building by
sensors.This
measuring the
sensor includes a
parts per million
digital display of
of CO2 (Carbon
set point
Dioxide) in the air.
adjustment and
As the CO2 levels
Manual Changeover
Heat, Cool or Off
System Switch. Fan
Auto or Off Switch.
One temperature
setpoint lever.
space temperature
increase, the
in F (Fahrenheit) or
outside air
C (Celsius).
damper
Includes FAN and
modulates to
SYSTEM buttons
meet the CO2 space ventilation
requirements.The CO2 sensor kit is
available as a field installed accessory.
(supports the
service functions of
the standard
Economizer Controls
sensor). E-squared memory stores last
programmed set points. Requires 24VAC
(Volts AC).This sensor should be utilized
with ReliaTel controls.
The standard equipment offering is a
fixed dry bulb changeover control. In
addition, there are two optional controls,
Enthalpy and Differential Enthalpy
Control.
Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off
Programmable Night Setback
Auto or manual changeover with seven-
day programming. Keyboard selection
Enthalpy Control
Switch.Two
Replaces the dry bulb control with a wet
bulb changeover controller which has a
fully adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential, than
the standard dry bulb control. This is due
to the additional wet bulb sensing
capability.
temperature
setpoint levers.
Optional Status
Indication LED lights,
System On, Heat,
Cool, or Service.
Differential Enthalpy
Replaces the standard dry bulb control
with two enthalpy sensors that compare
total heat content of the indoor air and
outdoor air to determine the most
efficient air source.This control option
offers the highest level of comfort control,
plus energy efficiency, available.
Remote Sensor
Sensor(s) available
for all zone sensors to
provide remote
of Heat, Cool, Fan, Auto, or On. All
programmable sensors have System On,
Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have
one (1) Occupied, one (1) Un-occupied,
and two (2) Override programs per day.
sensing capabilities.
Remote Potentiometer
Minimum position setting of economizer
can be remotely adjusted with this
accessory.
Integrated
Differential Pressure Switches
ComfortTM
This factory or field-installed option
allows individual fan failure and dirty filter
indication. The fan failure switch will
disable all unit functions and “flash” the
Service LED on the zone sensor. The dirty
filter switch will light the Service LED on
the zone sensor and will allow continued
unit operation.
System
Sensor(s)
available with
optional
temperature
adjustment and
override buttons
to provide central
control through a
Trane Integrated
Comfort system.
DualThermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Trane Communication Interface (TCI)
This factory or field-installed micro-
processor interface allows the unit to
communicate toTrane’s Integrated
Comfort system.
RT-PRC002-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard Efficiency)
Table ED-1 — Unit Wiring — Standard Efficiency
StandardIndoorFanMotor
Oversize Indoor Fan Motor
Unit
Minimum
Circuit
MaximumFuse
Size or Maximum
Circuit Breaker1 Ampacity2
Minimum
Circuit
MaximumFuse
Size or Maximum
Circuit Breaker1
Unit
Operating
VoltageRange Ampacity2
Tons
12½
ModelNo.
TC*150D3
TC*150D4
TC*150DW
TC*150DK
TC*180B3
TC*180B4
TC*180BW
TC*180BK
187-253
414-506
518-633
342-418
187-253
414-506
517-633
342-418
63
33
26
43
78
39
31
50
80
40
30
50
90
50
40
60
69
36
28
–
84
42
33
–
80
40
35
–
100
50
40
–
15
TC*210C3
TC*210C4
TC*210CW
TC*210CK
TC*240B3
TC*240B4
TC*240BW
TC*240BK
187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418
88
44
35
57
100
50
100
50
45
70
125
60
96
47
38
–
107
54
43
–
125
60
45
–
125
60
50
–
17½
20
40
65
45
80
TC*300B3
TC*300B4
TC*300BW
TC*300BK
187-253
414-506
517-633
342-418
118
58
46
150
70
50
–
–
–
–
–
–
–
–
25
70
80
Notes:
1. HACRbreakerperNEC.
2. Values do not include power exhaust accessory.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
50
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard Efficiency)
Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only)
StandardIndoorMotor
Oversize Indoor Motor
Max Fuse Size or
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Max Circuit
Breaker2
Tons
12½
KW Rating1
MCA
MCA
Max Circuit
Breaker2
208/230 Volts Three Phase
13.5/18.0
27.0/36.0
40.5/54.0
AYDHTRF318A
AYDHTRF336A
AYDHTRF354A
1
2
2
63/68
108/122
154/176
80/80
69/76
80/80
TCD150D3
110/125
175/200
115/130
162/184
125/150
175/200
AYDHTRK318A
AYDHTRK336A
AYDHTRK354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
78/78
108/122
154/176
100/100
110/125
175/200
84/84
115/130
162/184
100/100
125/150
175/200
15
TCD180B3
TCD210C3
TCD240B3
AYDHTRL336A
AYDHTRL354A
27.0/36.0
40.5/54.0
2
2
115/130
162/184
125/150
175/200
125/139
171/193
125/150
175/200
17½
20
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
125/139
171/193
218/247
150/150
175/200
225/250
—
—
—
—
—
—
25
TCD300B3
TCD150D4
460 Volts Three Phase
18.0
36.0
54.0
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
1
2
2
34
61
88
40
70
90
37
64
91
40
70
100
12½
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
18.0
36.0
54.0
1
2
2
39
61
88
50
70
90
42
64
91
50
70
100
15
TCD180B4
TCD210C4
TCD240B4
AYDHTRL436A
AYDHTRL454A
36.0
54.0
2
2
64
91
70
100
68
95
70
100
17½
20
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
36.0
54.0
72.0
2
2
2
64
91
118
70
100
125
68
95
123
70
100
125
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
36.0
54.0
72.0
2
2
2
68
95
123
70
100
125
—
—
—
—
—
—
25
TCD300B4
TCD150DW
575 Volts Three Phase
18.0
36.0
54.0
AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A
1
2
2
27
49
70
30
50
70
30
51
73
35
60
80
12½
AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A
18.0
36.0
54.0
1
2
2
31
49
70
40
50
70
33
51
73
40
60
80
15
TCD180BW
TCD210CW
TCD240BW
AYDHTRMW36A
AYDHTRLW54A
36.0
54.0
2
2
51
73
60
80
55
77
60
80
17½
20
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
55
77
98
60
80
100
—
—
—
—
—
—
25
TCD300BW
Notes:
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit.
2. HACR type circuit breaker per NEC.
RT-PRC002-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard Efficiency)
Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only), continued
StandardIndoorMotor
Max Fuse Size or
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
KW Rating1
Control
Stages
Max Fuse Size or
Max Circuit
Breaker2
Tons
12½
MCA
Max Circuit
Breaker2
MCA
380 Volts Three Phase
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
11.3
22.6
33.8
1
2
2
43
55
76
50
60
80
—
—
—
—
—
—
TCD150DK
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
11.3
22.6
33.8
1
2
2
50
55
76
60
60
80
—
—
—
—
—
—
15
TCD180BK
TCD210CK
TCD240BK
AYDHTRL436A
AYDHTRL454A
22.6
33.8
2
2
60
81
70
90
—
—
—
—
17½
20
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
22.6
33.8
45.1
2
2
2
65
81
103
80
90
110
—
—
—
—
—
—
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
22.6
33.8
45.1
2
2
2
70
81
103
80
90
100
—
—
—
—
—
—
25
TCD300BK
Notes:
1. Heater kw ratings are at 380V for 380 unit.
2. HACR type circuit breaker per NEC.
RT-PRC002-EN
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only)
StandardIndoorMotor
Max Fuse Size or
MCA Max Circuit Breaker2
Oversize Indoor Motor
Max Fuse Size or
MCA Max Circuit Breaker2
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Tons
12½
KW Rating1
208/230 Volts Three Phase
13.5/18.0
27.0/36.0
40.5/54.0
AYHHTRN318A
AYHHTRN336A
AYHHTRN354A
1
2
2
63/68
108/122
154/176
80/80
69/76
80/80
TCH150D3
110/125
175/200
115/130
162/184
125/150
175/200
AYHHTRN318A
AYHHTRP336A
AYHHTRP354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
78/78
108/122
154/176
100/100
110/125
175/200
84/84
115/130
162/184
100/100
125/150
175/200
15
TCH180B3
TCH210C3
TCH240B3
AYHHTRQ336A
AYHHTRQ354A
27.0/36.0
40.5/54.0
2
2
115/130
162/184
125/150
175/200
125/139
171/193
125/150
175/200
17½
20
AYHHTRN336A
AYHHTRN354A
AYHHTRN372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
AYHHTRN336A
AYHHTRN354A
AYHHTRN372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
132/139
171/193
218/247
150/150
175/200
225/250
—
—
—
—
—
—
25
TCH300B3
TCH150D4
460 Volts Three Phase
18.0
36.0
54.0
AYHHTRN418A
AYHHTRN436A
AYHHTRP454A
1
2
2
34
61
88
40
70
90
37
64
91
40
70
100
12½
AYHHTRN418A
AYHHTRP436A
AYHHTRP454A
18.0
36.0
54.0
1
2
2
37
61
88
50
70
90
42
64
91
50
70
100
15
TCH180B4
TCH210C4
TCH240B4
AYHHTRQ436A
AYHHTRQ454A
36.0
54.0
2
2
64
91
70
100
68
95
70
100
17½
20
AYHHTRN436A
AYHHTRN454A
AYHHTRN472A
36.0
54.0
72.0
2
2
2
64
91
118
70
100
125
68
95
123
70
100
125
AYHHTRN436A
AYHHTRN454A
AYHHTRN472A
36.0
54.0
72.0
2
2
2
68
95
123
70
100
125
—
—
—
—
—
—
25
TCH300B4
575 Volts Three Phase
AYHHTRNW18A
AYHHTRPW36A
AYHHTRPW54A
18.0
36.0
54.0
1
2
2
27
49
70
30
50
70
30
51
73
35
60
80
12½
15
TCH150DW
TCH180BW
AYHHTRNW18A
AYHHTRPW36A
AYHHTRPW54A
18.0
36.0
54.0
1
2
2
31
49
70
40
50
70
33
51
73
40
60
80
AYHHTRPW36A
AYHHTRQW54A
36.0
54.0
2
2
51
73
60
80
55
77
60
80
17½
20
TCH210CW
TCH240BW
AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A
36.0
54.0
72.0
2
2
2
55
77
98
60
80
100
—
—
—
—
—
—
25
TCH300BW
Notes:
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit..
2. HACR type circuit breaker per NEC.
RT-PRC002-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only) continued
StandardIndoorMotor
Max Fuse Size or
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
KW Rating1
Control
Stages
Max Fuse Size or
Max Circuit
Breaker2
Tons
12½
MCA
Max Circuit
Breaker2
MCA
380 Volts Three Phase
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
11.3
22.6
33.8
1
2
2
43
55
76
50
60
80
—
—
—
—
—
—
TCD150DK
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
11.3
22.6
33.8
1
2
2
50
55
76
60
60
80
—
—
—
—
—
—
15
TCD180BK
TCD210CK
TCD240BK
AYDHTRL436A
AYDHTRL454A
22.6
33.8
2
2
60
81
70
90
—
—
—
—
17½
20
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
22.6
33.8
45.1
2
2
2
65
81
103
80
90
110
—
—
—
—
—
—
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
22.6
33.8
45.1
2
2
2
70
81
103
80
90
100
—
—
—
—
—
—
25
TCD300BK
Notes:
1. Heater kw ratings are at 380V for 380 unit.
2. HACR type circuit breaker per NEC.
RT-PRC002-EN
54
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard Efficiency)
Table ED-4— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency
CompressorMotors
CondenserFanMotors
Unit
Amps1
Amps1
Tons
12½
15
ModelNo.
No.
Volts
Phase
HP2
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
TC*150D3
TC*150D4
TC*150DW
TC*150DK
2
2
2
2
208-230
460
575
3
3
3
3
6.00
6.00
6.00
6.0
3450
3450
3450
3450
20.4
10.8
8.3
156
75
54
2
2
2
2
1
1
1
1
.50
.50
.50
.50
3.2
1.6
1.3
1.9
8.8
3.8
3.2
5.2
380
13.1
70
TC*180B3
TC*180B4
TC*180BW
TC*180BK
2
2
2
2
208-230
460
575
3
3
3
3
9.30/5.10 3450 31.9/20.7
9.30/5.10 3450 16.3/10.0
9.30/5.10 3450 13.1/7.4
9.3/5.1 3450 19.7/12.1
253/128
113/63
85/49
2
2
2
2
1
1
1
1
.50
.50
.50
.50
3.2
1.6
1.3
1.9
8.8
3.8
3.2
5.2
380
125/64
TC*210C3
TC*210C4
TC*210CW
TC*210CK
2
2
2
2
208-230
460
575
3
3
3
3
9.3/6.0 3450 31.5/20.8
9.3/6.0 3450 15.9/10.0
9.3/6.0 3450 12.8/8.2
9.3/6.0 3450 19.2/12.1
253/156
113/75
85/54
2
2
2
2
1
1
1
1
1.00
1.00
1.00
1.00
5.5
2.9
2.0
3.5
18.3
9.3
5.7
8.5
17½
20
380
125/70
TC*240B3
TC*240B4
TC*240BW
TC*240BK
2
2
2
2
208-230
460
575
3
3
3
3
9.30
9.30
9.30
9.3
3450
3450
3450
3450
31.7
16.2
13.0
19.6
253
113
85
2
2
2
2
1
1
1
1
1.00
1.00
1.00
1.00
5.5
2.9
2.0
3.5
18.3
9.3
5.7
8.5
380
125
TC*300B3
TC*300B4
TC*300BW
TC*300BK
2
2
2
2
208-230
460
575
3
3
3
3
10.00
10.00
10.00
10.0
3450
3450
3450
3450
36.6
17.9
14.9
21.7
278
124
92
2
2
2
2
1
1
1
1
1.00
1.00
1.00
1.00
5.5
2.9
2.0
3.5
18.3
9.3
5.7
8.5
25
380
137
Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-5 — Unit Wiring - High Efficiency - Standard Refrigeration System
StandardIndoorFanMotor
Oversize Indoor Fan Motor
Unit
Operating
VoltageRange
Minimum
Circuit
Ampacity2
MaximumFuse
Size or Maximum
Circuit Breaker1 Ampacity2
Minimum
Circuit
MaximumFuse
Size or Maximum
Circuit Breaker1
Unit
Tons
12½
ModelNo.
TC*151C3
TC*151C4
TC*151CW
187-253
414-506
517-633
64
31
25
80
40
30
70
34
28
90
40
35
TC*181C3
TC*181C4
TC*181CW
187-253
414-506
517-633
74
36
29
90
50
40
80
38
31
100
50
40
15
TC*211C3
TC*211C4
TC*211CW
187-253
414-506
517-633
91
44
35
110
60
45
98
48
38
125
60
50
17½
20
TC*241C3
TC*241C4
TC*241CW
187-253
414-506
517-633
99
50
40
125
60
50
107
54
43
125
60
50
TC*301C3
TC*301C4
TC*301CW
187-253
414-506
517-633
120
58
47
150
70
60
N/A
N/A
N/A
N/A
N/A
N/A
25
Notes:
1. HACRbreakerperNEC.
2. Values do not include power exhaust accessory.
Table ED-6— Unit Wiring - High Efficiency - TXV/Face-Split Evaporator Coil Option (Downflow Only)
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Unit
Operating
Voltage Range
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
Minimum
Maximum Fuse
Minimum
Circuit
Ampacity2
65
Maximum Fuse
Unit
Circuit
Size or Maximum
Size or Maximum
Tons
12½
Model No.
TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD211C3
TCD211C4
TCD211CW
TCD241C3
TCD241C4
TCD241CW
TCD301C3
TCD301C4
TCD301CW
Ampacity2
59
Circuit Breaker1
Circuit Breaker1
70
35
30
90
50
40
125
60
45
125
60
50
150
70
50
80
40
30
90
50
40
125
60
50
125
70
30
24
74
37
30
91
45
36
99
51
40
117
57
32
26
80
39
32
99
49
39
107
54
43
N/A
N/A
N/A
15
17½
20
50
N/A
N/A
N/A
25
46
Notes:
1. HACRbreakerperNEC.
2. Values do not include power exhaust accessory.
RT-PRC002-EN
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-7 — Unit Wiring - High Efficiency - Dehumidification (Hot Gas Reheat) Option
(Downflow Only)
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Unit
Operating
Voltage Range
187-253
414-506
517-633
187-253
414-506
517-633
Minimum
Maximum Fuse
Minimum
Maximum Fuse
Unit
Circuit
Size or Maximum
Circuit
Size or Maximum
Tons
12½
Model No.
TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD241C3
TCD241C4
TCD241CW
Ampacity2
Circuit Breaker1
Ampacity2
Circuit Breaker1
59
30
24
71
36
28
98
50
39
70
35
30
90
45
35
125
60
50
65
32
26
77
39
30
105
53
42
80
40
30
100
50
40
125
60
50
15
187-253
414-506
517-633
20
Notes:
1. HACRbreakerperNEC.
2. Values do not include power exhaust accessory.
RT-PRC002-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-8 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System
(Downflow Only)
StandardIndoorMotor
Max Fuse Size or
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
KW Rating
Control
Stages
Max Fuse Size or
Max Circuit
Breaker2
Tons
MCA
Max Circuit
Breaker1
MCA
208/230 Volts Three Phase
AYDHTRK318A
AYDHTRK336A
AYDHTRK354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
64/68
108/122
154/176
80/80
110/125
175/200
70/76
115/130
162/184
90/90
125/150
175/200
12½
15
TCD151C3
TCD181C3
TCD211C3
TCD241C3
TCD301C3
AYDHTRK318A
AYDHTRK336A
AYDHTRK354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
74/74
108/122
154/176
100/100
110/125
175/200
80/80
115/130
162/184
100/100
125/150
175/200
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
17½
20
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
125/139
171/193
218/247
150/150
175/200
225/250
—
—
—
—
—
—
25
460 Volts Three Phase
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
18.0
36.0
54.0
1
2
2
34
61
88
40
70
90
37
64
91
40
70
100
12½
15
TCD151C4
TCD181C4
TCD211C4
TCD241C4
TCD301C4
AYDHTRL418A
AYDHTRK427A
AYDHTRK436A
AYDHTRK454A
18.0
27.0
36.0
54.0
1
2
2
2
36
47
61
88
50
50
70
90
38
—
64
91
50
—
70
100
AYDHTRL427A
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
27.0
36.0
54.0
72.0
2
2
2
2
51
64
91
60
70
100
125
—
68
95
—
70
100
125
17½
20
118
123
AYDHTRL427A
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
27.0
36.0
54.0
72.0
2
2
2
2
51
64
91
60
70
100
125
—
68
95
—
70
100
125
118
123
AYDHTRL436A
AYDHTRL427A
AYDHTRL454A
AYDHTRK472A
36.0
27.0
54.0
72.0
2
2
2
2
68
58
95
70
70
100
125
—
—
—
—
—
—
25
123
—
575 Volts Three Phase
AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A
18.0
36.0
54.0
1
2
2
27
49
70
30
50
70
30
51
73
35
60
80
12½
15
TCD151CW
TCD181CW
TCD211CW
TCD241CW
TCD301CW
AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A
18.0
36.0
54.0
1
2
2
29
49
70
40
50
70
31
31
73
40
40
80
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
17½
20
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
55
77
98
60
80
100
—
—
—
—
—
—
25
Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
RT-PRC002-EN
58
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-9 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System
(Horizontal Only)
StandardIndoorMotor
Max Fuse Size or
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
KW Rating
Control
Stages
Max Fuse Size or
Max Circuit
Breaker2
Tons
MCA
Max Circuit
Breaker1
MCA
208/230 Volts Three Phase
AYHHTRN318A
AYHHTRP336A
AYHHTRP354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
64/68
108/122
154/176
80/80
110/125
175/200
70/76
115/130
162/184
90/90
125/150
175/200
12½
15
TCH151C3
TCH181C3
TCH211C3
TCH241C3
TCH301C3
AYHHTRM318A
AYHHTRM336A
AYHHTRM354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
74/74
108/122
154/176
100/100
110/125
175/200
80/80
115/130
162/184
100/100
125/150
175/200
AYHHTRN336A
AYHHTRN354A
AYHHTRN372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
17½
20
AYHHTRN336A
AYHHTRN354A
AYHHTRN372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
AYHHTRN336A
AYHHTRN354A
AYHHTRN372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
125/139
171/193
218/247
150/150
175/200
225/250
—
—
—
—
—
—
25
460 Volts Three Phase
AYHHTRN418A
AYHHTRP436A
AYHHTRP454A
18.0
36.0
54.0
1
2
2
34
61
88
40
70
90
37
64
91
40
70
100
12½
15
TCH151C4
TCH181C4
TCH211C4
TCH241C4
TCH301C4
AYHHTRM418A
AYHHTRM436A
AYHHTRM454A
18.0
36.0
54.0
1
2
2
36
61
88
50
70
90
38
64
91
50
70
100
AYHHTRN436A
AYHHTRN454A
AYHHTRN472A
36.0
54.0
72.0
2
2
2
64
91
118
70
100
125
68
95
123
70
100
125
17½
20
AYHHTRN436A
AYHHTRN454A
AYHHTRN472A
36.0
54.0
72.0
2
2
2
64
91
118
70
100
125
68
95
123
70
100
125
AYHHTRN436A
AYHHTRN454A
AYHHTRN472A
36.0
54.0
72.0
2
2
2
68
95
123
70
100
125
—
—
—
—
—
—
25
575 Volts Three Phase
AYHHTRNW18A
AYHHTRPW36A
AYHHTRPW54A
18.0
36.0
54.0
1
2
2
27
49
70
30
50
70
30
51
73
35
60
80
12½
15
TCH151CW
TCH181CW
TCH211CW
TCH241CW
TCH301CW
AYHHTRMW18A
AYHHTRMW36A
AYHHTRMW54A
18.0
36.0
54.0
1
2
2
29
49
70
40
50
70
31
31
73
40
40
80
AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
17½
20
AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
AYHHTRMW36A
AYHHTRNW54A
AYHHTRNW72A
36.0
54.0
72.0
2
2
2
55
77
98
60
80
100
—
—
—
—
—
—
25
Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
RT-PRC002-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and
151/181/ 241 Reheat Option(Downflow Only)
StandardIndoorMotor
Max Fuse Size or
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
KW Rating
Control
Stages
Max Fuse Size or
Max Circuit
Breaker1,2
Tons
MCA
Max Circuit
Breaker2
MCA
208/230 Volts Three Phase
AYDHTRK318A
AYDHTRK336A
AYDHTRK354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
61/68
108/122
154/176
70/70
110/125
175/200
68/76
115/130
162/184
80/80
125/150
175/200
12½
15
TCD151C3
AYDHTRK318A
AYDHTRK336A
AYDHTRK354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
74/74
108/122
154/176
100/100
110/125
175/200
80/80
115/130
162/184
90/90
125/150
175/200
TCD181C3
TCD181C3
TCD211C3
*AYDHTRK318A
13.5/18.0
1
71/71
90/90
77/77
100/100
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
17½
20
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
TCD241C3
TCD301C3
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
125/139
171/193
218/247
150/150
175/200
225/250
—
—
—
—
—
—
25
460 Volts Three Phase
AYDHTRL418A
AYDHTRK436A
AYDHTRK454A
18.0
36.0
54.0
1
2
2
34
61
88
35
70
90
37
64
91
40
70
100
12½
15
TCD151C4
AYDHTRL418A
AYDHTRK427A3
AYDHTRK436A
AYDHTRK454A
18.0
27.0
36.0
54.0
1
2
2
2
37
47
61
88
50
50
70
90
39
—
64
91
50
—
70
TCD181C4
TCD181C4
100
*AYDHTRL418A
18.0
1
36
45
39
50
AYDHTRL427A3
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
AYDHTRL427A3
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
AYDHTRL427A3
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A
27.0
36.0
54.0
72.0
2
2
2
2
51
64
91
60
70
100
125
—
68
95
—
70
100
125
17½
20
TCD211C4
TCD241C4
TCD301C4
118
123
27.0
36.0
54.0
72.0
2
2
2
2
51
64
91
60
70
100
125
—
68
95
—
70
100
125
118
123
27.0
36.0
54.0
72.0
2
2
2
2
57
68
95
70
70
100
125
—
—
—
—
—
—
—
—
25
123
Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Do not use with oversized motor.
*
Applies only to Dehumidification (Hot Gas Reheat) Models
RT-PRC002-EN
60
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and
151/181/ 241 Reheat Option(Downflow Only), continued
StandardIndoorMotor
Max Fuse Size or
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
KW Rating
Control
Stages
Max Fuse Size or
Max Circuit
Breaker1,2
Tons
MCA
Max Circuit
Breaker2
MCA
575 Volts Three Phase
AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A
18.0
36.0
54.0
1
2
2
27
49
70
30
50
70
30
51
73
30
60
80
12½
15
TCD151CW
AYDHTRKW18A
AYDHTRMW36A
AYDHTRKW54A
18.0
36.0
54.0
1
2
2
30
49
70
40
50
70
32
51
73
40
60
80
TCD181CW
TCD181CW
TCD211CW
*AYDHTRKW18A
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
18.0
36.0
54.0
72.0
1
2
2
2
28
51
73
95
35
60
80
30
55
77
98
40
60
80
17½
20
100
100
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
TCD241CW
TCD301CW
AYDHTRMW36A
AYDHTRLW54A
AYDHTRKW72A
36.0
54.0
72.0
2
2
2
55
77
98
60
80
100
—
—
—
—
—
—
25
Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Do not use with oversized motor.
*
Applies only to Dehumidification (Hot Gas Reheat) Models
RT-PRC002-EN
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-11 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, Standard
Refrigeration System
CompressorMotors
Condenser Fan Motors
Unit
Amps1
Amps1
Tons
12½
ModelNo.
No.
Volts
Phase
HP2
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
TC*151C3
TC*151C4
TC*151CW
2
2
2
208-230
460
575
3
3
3
5.70
5.70
5.70
3450
3450
3450
20.7
10.0
8.2
156
75
54
2
2
2
1
1
1
.50
.50
.50
3.2
1.6
1.3
8.8
3.8
3.2
TC*181C3
TC*181C4
TC*181CW
2
2
2
208-230
460
575
3
3
3
9.30/4.50 3450 31.5/16.9
9.30/4.50 3450 15.1/8.2
9.30/4.50 3450 12.1/6.6
253/124
113/59.6
85/49.4
2
2
2
1
1
1
.50
.50
.50
3.2
1.6
1.3
8.8
3.8
3.2
15
TC*211C3
TC*211C4
TC*211CW
2
2
2
208-230
460
575
3
3
3
10.0/5.70 3450 33.3/20.7
10.0/5.70 3450 16.3/10.0
10.0/5.70 3450 13.2/8.2
278/156
124/75
92/54
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
17½
20
TC*241C3
TC*241C4
TC*241CW
2
2
2
208-230
460
575
3
3
3
9.30
9.30
9.30
3450
3450
3450
31.6
16.1
12.9
253
113
85
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
TC*301C3
TC*301C4
TC*301CW
2
2
2
208-230
460
575
3
3
3
10.00
10.00
10.00
3450
3450
3450
37.6
18.3
14.9
278
124
92
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
25
Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
Table ED-12 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, TXV/Face-Split
Evaporator Coil Option (Downflow Only)
CompressorMotors
Condenser Fan Motors
Unit
Amps1
Amps1
Tons
12½
ModelNo.
No.
Volts
Phase
HP2
5.7
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD211C3
TCD211C4
TCD211CW
TCD241C3
TCD241C4
TCD241CW
TCD301C3
TCD301C4
TCD301CW
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
208-230
460
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3450
3450
3450
3450
3450
3450
3450
3450
3450
18.6
9.4
7.4
156
75
54
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.50
.50
.50
.50
.50
3.2
1.6
1.3
3.2
1.6
1.3
5.5
2.9
2.0
5.5
2.9
2.0
5.5
2.9
2.0
8.8
3.8
3.2
8.8
3.8
3.2
18.3
9.3
5.7
18.3
9.3
5.7
18.3
9.3
5.7
5.7
575
5.7
208-230
460
575
208-230
460
575
208-230
460
575
208-230
460
9.30/4.50
9.30/4.50
9.30/4.50
10.00/5.7
10.00/5.7
10.00/5.7
9.0/9.3
9.0/9.3
9.0/9.3
10.00
32.1/16.4
15.6/8.7
12.3/7.4
34.8/19.5
17.0/10.3
13.8/8.1
253/124
113/59.6
85/49.4
278/156
124/75
92/54
225/253
114/113
80/85
278
15
.50
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
17½
20
3500/3450 30.4/32.6
3500/3450 16.1/16.8
3500/3450 12.5/13.4
3450
3450
3450
36.2
17.7
14.3
25
10.00
124
92
575
10.00
Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
Table ED-13 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat)
Option (Downflow Only)
CompressorMotors
Condenser Fan Motors
Unit
Amps1
Amps1
Tons
12½
ModelNo.
No.
Volts
Phase
HP2
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
TCD151C3
TCD151C4
TCD151CW
TCD181C3
TCD181C4
TCD181CW
TCD241C3
TCD241C4
TCD241CW
2
2
2
2
2
2
2
2
2
208-230
460
575
208-230
460
575
208-230
460
575
3
3
3
3
3
3
3
3
3
5.7/5.7
5.7/5.7
5.7/5.7
8.3/5.7
8.3/5.7
8.3/5.7
9.0/9.3
9.0/9.3
9.0/9.3
3450
3450
3450
3450
3450
3450
18.6
9.7
7.6
27.4/19.0
13.8/10.1
10.7/7.9
156
75
54
208/156
100/75
68/54
225/253
114/113
80/85
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
.50
.50
.50
.50
.50
3.2
1.6
1.3
3.2
1.6
1.3
5.5
2.9
2.0
8.8
3.8
3.2
8.8
3.8
3.2
18.3
9.3
5.7
15
.50
3500/3450 30.1/31.7
3500/3450 15.6/16.2
3500/3450 12.1/13.0
1.00
1.00
1.00
20
Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
62
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-14 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized
StandardEvaporatorFanMotor
OversizedEvaporatorFanMotor
Amps
FLA LRA
16.7 109.8
Unit
Amps
Tons
12½
ModelNo.
No.
Volts
Phase
HP
FLA
LRA
No. Volts
Phase
HP
TC*150D3,TC*151C3
TC*150D4,TC*151C4
TC*150DW,TC*151CW
TC*150DK
1
1
1
1
208-230
460
575
3
3
3
3
3.00
3.00
3.00
5.0
10.6
4.8
3.9
9.2
81.0
40.5
31.0
66.5
1
1
208-230
460
3
3
5.00
5.00
5.00
—
7.6
6.1
—
54.9
41.6
—
1
—
575
—
3
—
380
TC*180B3,TC*181C3
TC*180B4,TC*181C4
TC*180BW,TC*181CW
TC*180BK
1
1
1
1
208-230
460
575
3
3
3
3
3.00
3.00
3.00
5.0
10.6
4.8
3.9
9.2
81.0
40.5
31.0
66.5
1
1
1
208-230
460
575
3
3
3
5.00
5.00
5.00
—
16.7 109.8
7.6
6.1
—
54.9
41.6
—
15
380
—
—
—
TC*210C3,TC*211C3
TC*210C4,TC*211C4
TC*210CW,TC*211CW
TC*210CK
1
1
1
1
208-230
460
575
3
3
3
3
5.00
5.00
5.00
7.5
16.7
7.6
6.1
109.8
54.9
41.6
83.5
1
1
1
208-230
460
575
3
3
3
7.50
7.50
7.50
—
24.2 120.4
11.0
9.0
—
74.0
60.0
—
17½
20
380
13.3
—
—
—
TC*240B3,TC*241C3
TC*240B4,TC*241C4
TC*240BW,TC*241CW
TC*240BK
1
1
1
1
208-230
460
575
3
3
3
3
5.00
5.00
5.00
7.5
16.7
7.6
6.1
109.8
54.9
41.6
83.5
1
1
1
208-230
460
575
3
3
3
7.50
7.50
7.50
—
24.2 120.4
11.0 74.0
9.0
—
60.0
—
380
13.3
—
—
—
TC*300B3,TC*301C3
TC*300B4,TC*301C4
TC* 300BW,TC*301CW
TC*300BK
1
1
1
1
208-230
460
575
3
3
3
3
7.50
7.50
7.50
7.5
24.2
11.0
9.0
120.4
74.0
60.0
83.5
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
25
380
13.3
*Indicates both downflow and horizontal units.
RT-PRC002-EN
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-15 — Electrical Characteristics — Power Exhaust Accessory
Accessory
Operating
Voltage
208-230
460
\Amps
LRA
Tons
Phase
HP
3/4
3/4
3/4
RPM
1040
1040
1040
FLA
6.6
3.2
2.1
1,2
12½
1
1
1
13.5
8.4
15, 17½
20, 25
Notes:
1. 12½ Ton Standard Unit.
575
5.2
2. 12½ Ton High Efficiency Unit.
RT-PRC002-EN
64
Download from Www.Somanuals.com. All Manuals Search And Download.
Jobsite
Connections
Zone Sensors —Typical Number OfWires
DISCONNECT
SWITCH
(BYOTHERS)
A— ManualChangeover ....................................... 4
Manual/AutoChangeover ............................... 5
Manual/AutoChangeoverwith
StatusIndicationLED’s ........................... 10
Programmable Night Setback with
ZONESENSORS
StatusIndicationLED’s ............................. 7
ROOFTOP
UNIT
B— 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.
RT-PRC002-EN
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(12½-25 Ton)
RT-PRC002-EN
66
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(12½-25 Ton)
Typical wiring diagram. For specific
wiring, see individual Service Facts.
RT-PRC002-EN
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(12½-25 Ton)
RT-PRC002-EN
68
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(12½-25 Ton)
RT-PRC002-EN
69
Download from Www.Somanuals.com. All Manuals Search And Download.
(12½Ton) High Efficiency
Dimensional
Data
(12½, 15, 17½Ton)
Standard Efficiency
All dimensions are in inches.
Note: Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb flanges.
See recommended duct dimensions on
the next page.
Roofcurb is intended for downflow use
only.
Downflow Unit Clearance
RT-PRC002-EN
70
Download from Www.Somanuals.com. All Manuals Search And Download.
(12½Ton) High Efficiency
Dimensional
Data
(12½, 15, 17½Ton)
Standard Efficiency
All dimensions are in inches.
1"
Downflow Duct Connections — Field Fabricated
17 7/8"
59 7/16"
26 5/16"
1"
52 1/2"
1 1\2"
PERIMETER
CURB FLANGE
14 1/16"
7 7/16"
RETURN
SUPPLY
Note:
Duct flanges mount 7-7/16" down inside
the curb on the 1½" curb flanges.
Roofcurb is intended for downflow use
only.
Horizontal Unit Supply/Return and Unit Clearance
RT-PRC002-EN
71
Download from Www.Somanuals.com. All Manuals Search And Download.
(15-25Ton) High Efficiency
Dimensional
Data
(20, 25Ton)
Standard Efficiency
All dimensions are in inches.
Note:
Duct flanges mount 7-7/16" down inside
the curb on the 1½" curb flanges. See
recommended duct dimensions on the
next page.
Roofcurb is intended for downflow use
only.
Downflow Unit Clearance
RT-PRC002-EN
72
Download from Www.Somanuals.com. All Manuals Search And Download.
(15-25Ton) High Efficiency
Dimensional
Data
(20, 25Ton)
Standard Efficiency
All dimensions are in inches.
1"
Downflow Duct Connections — Field Fabricated
19 5/16"
73 7/16"
26 5/16"
1"
66 1/2"
1 1\2"
PERIMETER
CURB FLANGE
14 1/16"
7 7/16"
RETURN
SUPPLY
Note: Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb flanges.
Roofcurb is intended for downflow use
only.
Horizontal Unit Supply/Return and Unit Clearance
RT-PRC002-EN
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(12½-25 Ton)
Accessories
All dimensions are in inches.
Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of Economizer Damper.
Table DD-1
Unit
Model#
A
B1
C2
TC*150, 151-180, 210
TC*181,211-301
Notes:
171/2
53¾
64¾
36
39
191/2
1. Horizontal dimension only. Downflow economizer is width
of end panel.
2. Power exhaust is applied on downflow economizer only.
RT-PRC002-EN
74
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Factory Installed
Options (FIOPS)
All dimensions are in inches.
Table DD-2
Unit
Model#
A
423/
291/2
B
483/
56
C
31
381/2
TCD150, 151, 180, 210
TCD181,211-301
8
8
RT-PRC002-EN
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
Factory Installed
Options (FIOPS)
Disconnect Switch
or Circuit Breaker
Fan Failure Switch
Clogged Filter Switch
Powered or Unpowered
Convenience Outlet
Trane Communication Interface
Hinged Access Door
Black Epoxy Coated
Outdoor Coils
Hinged Access Door
Through the Base Electrical
High Pressure Cut Out
Supply and/or Return Smoke Detectors
RT-PRC002-EN
76
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(12½-25 Ton)
Table DD-3 — Standard Efficiency Units
Condensate
CondensateDrainLocation
Downflow Horizontal
Tons
DownflowOnly
Drain Size
A
267/
267/
B
221/
283/
C
1811/
1915/
D
F
41/
41/
G
627/
765/
H
5411/
6811/
E
J
255/
263/
E
K
6
12½, 15, 17½
20, 25
16
16
2
4
16
16
41/
4
4
16
16
16
16
1NPT
1NPT
—
—
8
4
—
—
41/
4
4
53/
8
Table DD-4 — High Efficiency Units
Condensate
Drain Size
CondensateDrainLocation
Downflow Horizontal
Tons
DownflowOnly
D
A
B
C
F
G
H
E
J
E
K
12½
15-25
267/
267/
16
16
221/
283/
2
4
1811/
16
41/
4
4
41/
4
4
627/
765/
16
16
5411/
6811/
16
16
1NPT
1NPT
—
—
255/
263/
8
4
—
—
6
1915/
16
41/
41/
53/
8
RT-PRC002-EN
77
Download from Www.Somanuals.com. All Manuals Search And Download.
(12½-25 Ton)
Weights
Table W-1 — Accessory Net Weights (Lbs)1, 7
Oversized
Motor
Adder
High5
Static
Drive
Low5
Static
Drive
Economizer
Net
Outside Air Damper
Manual Motorized
Power
Exhaust4
Roof
Curb4
ModelNo.
TCD150D, 180B
TCD121,151C,TCD210C
65
32
60
95
205
5
2
2
TCD240B
TCD181,211,241C
80
80
32
32
75
75
95
95
235
235
5
2
—
2
TCD300B.301C
N/A
N/A
TCH150D, 180B, 210C
TCH121,151C
50
32
60
—
—
5
2
2
TCH240B
TCH181,211,241C
65
65
32
32
75
75
—
—
—
—
5
2
—
2
TCH300B,301C
N/A
N/A
Table W-1 Continued
Electric Heaters
27-36 KW
Unit
ModelNo.
AllZone
Sensors
6-23 KW
54 KW
72 KW
3
3
3
3
240/480V2
240/480V2
240/480V2
38/32
240/480V2
—
TCD150D, 180B, 210C
TCD121,151,181C
1
28/216
31/27
33/27
TCD240B
1
—
40/32
43/34
TCD211,241C
TCD300B,301C
1
1
—
28/216
33/27
31/27
40/32
38/32
43/34
—
TCH150D, 180B, 210C
TCH121,151,181C
TCH240B
TCH211,241C
1
1
—
—
33/27
33/27
40/32
40/32
43/34
43/34
TCH300B,301C
Notes:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600V heaters net weights are same as 480V heaters.
3. To estimate shipping weight add 5 lbs to net weight.
4. Downflow only.
5. Not available on all models (See Fan Performance tables for specific models).
6. 9 - 23 KW Heaters not available for TC*210C.
7. TC*150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.
This is provided in compliance with ARI certification program.
RT-PRC002-EN
78
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
Table W-2 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Unit
ModelNo.
MaximumWeights(Lbs)
Corner Weights (Lbs)1
Center of Gravity (In.)
Tons
12½
15
Shipping2
1687/1820
1866/2361
2022/2380
2372/2490
2365/2475
Net
A
B
C
D
Length
46/45
42/52
46/53
51/53
53/53
Width
29/30
28/35
29/35
34/34
33/34
TC*150D/TC*151C
TC*180B/TC*181C
TC*210C/TC*211C
TC*240B/TC*241C
TC*300B/TC*301C
1319/1452
1498/1902
1654/1921
1913/2031
1906/2016
446/485
547/643
565/643
679/697
661/695
339/360
358/477
425/495
482/528
507/524
230/259
234/333
285/341
312/348
320/343
303/348
359/447
378/442
440/458
418/454
17½
20
25
Notes:
1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
*Indicates both downflow and horizontal units.
RT-PRC002-EN
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3
Accessory
High Efficiency Motors4
Weight
49
Unit Model Number
TC*150-181 standard size motor
TC*210-241 standard size motor
TC*150-181 oversize motor
36
0
TC*210-241 oversize motor
TC*300-301 standard size motor
Hinged Doors
27
38
23
5
AllTC* units
AllTC* units
AllTC* units
Powered Convenience Outlet
Through the Base Electrical
Unit Mounted Circuit Breaker
AllTC* units except those with 54&72 kW heaters
& 208/230V
10
5
All TC* units with 54&72 kW heaters & 208/230V
Unit Mounted Disconnect
AllTC* units except those with 54&72 kW heaters
& 208/230V
10
AllTC* units with 54&72 kW heaters & 208/230V
Smoke Detectors
Supply/Return
5
AllTC* units
Tool-less Hail Guard
38
43
TC*150,151,180,210
TC*181,211,240,241,300,301
Novar 2024
Novar 3051
Notes:
7
5
AllTC* units
AllTC* units
1. Weights for FIOP accessories not listed are >5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer and oversized motors.
4. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high
efficiency motors are in addition to the standard motor weight.
RT-PRC002-EN
80
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
General
UnitTop
corrosion resistant steel components. A
forced combustion blower shall supply
premixed fuel to a single burner ignited
by a pilotless hot surface ignition system.
In order to provide reliable operation, a
negative pressure gas valve shall be
used that requires blower operation to
initiate gas flow. On an initial call for heat,
the combustion blower shall purge the
heat exchanger 45 seconds before
ignition. After three unsuccessful ignition
attempts, the entire heating system shall
be locked out until manually reset at the
thermostat. Units shall be suitable for use
with natural gas or propane (field
The units shall be dedicated downflow or
horizontal airflow.The operating range
shall be between 115°F and 0°F in cooling
as standard from the factory for all units.
Cooling performance shall be rated in
accordance with ARI testing procedures.
All units shall be factory assembled,
internally wired, fully charged with R-22,
and 100 percent run tested to check
cooling operation, fan and blower rotation
and control sequence, before leaving the
factory.Wiring internal to the unit shall be
colored and numbered for simplified
identification. Units shall be UL listed and
labeled, classified in accordance to UL
1995/CAN/CSA No. 236-M90 for Heat
Pumps. Canadian units shall be CSA
Certified.
The top cover shall be one piece, or
where seams exist, double hemmed and
gasket sealed to prevent water leakage.
Filters
Two inch standard filters shall be factory
supplied on all units. Optional two inch
pleated media filters shall be available.
Compressors
All units shall have direct-drive, hermetic,
scroll type compressors with centrifugal
type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage
utilization range of plus or minus 10
percent of nameplate voltage. Internal
overloads shall be provided with the
scroll compressors. All models shall have
crankcase heaters, low and high pressure
controls as standard.
installed kit) and shall also comply with
California requirements for low NOx
emissions.The 12½-25 tons shall have
two stage heating.
Casing
Outdoor Fans
Refrigerant Circuits
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position.The fan motor(s) shall be
permanently lubricated and shall have
built-in thermal overload protection.
Each refrigerant circuit shall have
independent fixed orifice or thermostatic
expansion devices, service pressure
ports, and refrigerant line filter driers
factory installed as standard. An area
shall be provided for replacement suction
line driers.
weather-resistant baked enamel finish.
Unit’s surface shall be tested 500 hours in
a salt spray test in compliance with ASTM
B117. Cabinet construction shall allow for
all maintenance on one side of the unit. In
order to ensure a water and air tight seal,
service panels shall have lifting handels
and no more thatn three screws to
remove. All exposed vertical panels and
top covers in the indoor air section shall
be insulated with a 1/2 inch, 1 pound
density foil-faced, fire-resistant,
permanent, odorless, glass fiber material.
The base of the downflow unit shall be
insulated with 1/2 inch, 1 pound density
foil-faced, closed-cell material.The
downflow unit’s base pan shall have no
penetrations within the perimeter of the
curb other than the raised 11/8 inch high
supply/return openings to provide an
added water integrity precaution, if the
condensate drain backs up.The base of
the unit shall have provisions for forklift
and crane lifting.
Indoor Fan
Units above shall have belt driven, FC
centrifugal fans with adjustable motor
sheaves. Units with standard motors
shall have an adjustable idler-arm
assembly for quick-adjustment of fan
belts and motor sheaves. All motors shall
be thermally protected. Oversized motors
shall be available for high static
application. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT).
Evaporator and Condenser Coils
Internally finned, 3/8" copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity.The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig. All dual compressor
units shall have intermingled evaporator
coils. Sloped condensate drain pans are
standard. Patent-pending 1+1+1
condenser coil, permanently gapped for
easy cleaning is available.
Gas Heating Section
The heating section shall have a drum
and tube heat exchanger design using
RT-PRC002-EN
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Controls
Hinged Access Doors
Through the Base Electrical with Circuit
Breaker
This option is a thermal magnetic, molded
case, HACR Circuit Breaker with
Unit shall be completely factory wired
with necessary controls and contactor
pressure lugs or terminal block for power
wiring. Unit shall provide an external
location for mounting a fused disconnect
device. ReliaTel controls shall be provided
for all 24 volt control functions.The
resident control algorithms shall make all
heating, cooling, and/or ventilating
decisions in response to electronic signals
from sensors measuring indoor and
outdoor temperatures.The control
algorithm maintains accurate
Sheet metal hinges are available on the
Filter/Evaporator Access Door and the
Compressor/Control Access Door.This
option is available on all downflow
models.
provisions for through the base electrical
connections.The circuit breaker will be
installed in a water tight enclosure in the
unit with access through a swinging door.
Factory wiring will be provided from the
switch to the unit high voltage terminal
block.The circuit breaker will provide
overcurrent protection, be sized per NEC
and UL guidelines, and be agency
recognized by UL/CSA.This option is
available on all downflow models.
High Efficiency Motors
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.
High Pressure Cutout
This option is offered for units that do not
have High Pressure cutout as standard.
temperature control, minimizes drift from
set point, and provides better building
comfort. A centralized control shall
provide anti-short cycle timing and time
delay between compressors to provide a
higher level of machine protection.
Powered or Unpowered Convenience
Outlet
Through the Base ElectricalWith
Disconnect Switch
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered.When the convenience outlet
is powered, a service receptacle
disconnect will be available.The
convenience outlet is powered from the
line side of the disconnect or circuit
breaker, and therefore will not be
affected by the position of the disconnect
or circuit breaker.This option can only be
ordered when theThrough the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered.This option is available on all
downflow models.
Three-pole, molded case, disconnect
switch with provisions for through the
base electrical connections are available.
The disconnect switch will be installed in
the unit in a water tight enclosure with
access through a swinging door. Factory
wiring will be provided from the switch to
the unit high voltage terminal block.The
switch will be UL/CSA agency recognized.
Note:The disconnect switch will be sized
per NEC and UL guidelines but will not be
used in place of unit overcurrent
Defrost Controls
Adaptive demand defrost shall be
provided to permit defrost wherever coil
icing conditions begin to significantly
reduce unit capacity.
Factory Installed Options
Black Epoxy Coated Pre-Coated Coils
The black epoxy coils have a thermoset
vinyl coating that is bonded to the
aluminum fin stock prior to the fin-
stamping process.The pre-coated coils
are an economical option for protection in
mildly corrosive environments.
protection.This option is available on all
downflow models.
Supply and/or Return Air Smoke
Detector
Through the Base UtilitiesAccess
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
With this option installed, if smoke is
detected, all unit operation will be shut
down. Reset will be manual at the unit.
Return Air Smoke Detectors require
minimum allowable airflow when used
with certain models. See the Installation,
Operation, and Maintenance (IOM)
manual for the models affected and the
minimum allowable airflow required.This
option is available on all downflow
models.
Dehumidification Option
The dehumidification (hot gas reheat)
option shall provide increased
dehumidification.The option shall consist
of a hot-gas reheat coil located on the
leaving air side of the evaporator coil
prepiped and circuited. Low pressure
switch(es) and thermostatic expansion
valve(s)TXV are standard. Frostat™,
ReliaTel options module, and 2”pleated
filters are required but not standard.They
must be ordered and configured
separately.
installation of liquid-tight conduit and an
external field installed disconnect switch.
Two-Inch Pleated Filters
Two inch pleated media filters shall be
available on all models.
RT-PRC002-EN
82
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Electric Heaters
Reference or Comparative Enthalpy
Reference Enthalpy is used to measure
and communicate outdoor humidity.The
unit receives and uses this information to
provide improved comfort cooling while
using the economizer. Comparative
Enthalpy measures and communicates
humidity for both outdoor and return air
conditions, and return air temperature.
The unit receives and uses this
Factory or Field Installed
Options
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
These indications will be registered with
either a zone sensor with status indication
lights or an Integrated Comfort™ System.
Electric heat modules shall be available
for installation within the basic unit.
Electric heater elements shall be
constructed of heavy-duty nickel
chromium elements internally delta
connected for 240 volt, wye connected
for 480 and 600 volt. Staging shall be
achieved through ReliaTel. Each heater
package shall have automatically reset
high limit control operating through
heating element contactors. All heaters
shall be individually fused from the
factory, where required, and shall meet
all NEC and CEC requirements when
properly installed. Power assemblies
shall provide single-point connection.
Electric heat modules shall be UL listed or
CSA certified. If ordering theThrough the
Base Electrical option with an Electric
Heater, the heater must be factory
installed.
information to maximize use of
Differential Pressure Switches
economizer cooling, and to provide
maximum occupant comfort control.
Reference or Comparative Enthalpy
option shall be available when a factory
or field installed Downflow Economizer is
ordered.This option is available on all
downflow models.
These options allow for individual fan
failure and dirty filter indication.The fan
failure switch will disable all unit functions
and “flash” the Service LED on the zone
sensor.The dirty filter switch will light the
Service LED on the zone sensor and will
allow continued unit operation.
Tool-less Hail Guards
Discharge Air Sensing Kit
Tool-less, hail protection quality coil
guards are available for condenser coil
protection.
This kit provides true discharge air
sensing in heating models.This sensor is
a status indicator readable through
Tracer™orTracker™.The kit is functional
only with the ReliaTel Options Module.
Frostat
Trane Communication Interface
This factory or field-installed option shall
be provided to interface ReliaTel™
controlled units with theTrane Integrated
ComfortTM systems.
This option is to be utilized as a safety
device.The Frostat opens when
temperatures on the evaporator coil fall
below 10°F. The temperature will need to
rise to 50°F before closing.This option
should be utilized in low airflow or high
outside air applications.
Economizer - Downflow
The assembly includes fully modulating
0-100 percent motor and dampers,
barometric relief, minimum position
setting, preset linkage, wiring harness
with plug, fixed dry bulb and spring return
actuator.The barometric relief damper
shall be standard with the downflow
economizer and shall provide a pressure
operated damper that shall be gravity
closing and shall prohibit entrance of
outside air during the equipment “off”
cycle. Solid state enthalpy and differential
enthalpy control shall be field-installed
LonTalk® Communications Interface
The LonTalk communications interface,
when installed in aVoyager unit, allows
the unit to communicate as aTracer™LCI-
V device or directly with generic LonTalk
Network Building Automation System
Controls.
Oversized Motors
Oversized motors shall be available for
high static applications.
RT-PRC002-EN
83
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Powered Exhaust
Field Installed Options
CO2 Sensing
The powered exhaust shall provide
exhaust of return air, when using an
economizer, to maintain better building
pressurization.
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.
Roof Curb - Downflow
The roof curb shall be designed to mate
with the downflow unit and provide
support and a water tight installation
when installed properly.The roof curb
design shall allow field-fabricated
rectangular supply/return ductwork to be
connected directly to the curb. Curb
design shall comply with NRCA
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors.This sensor
includes a digital display of set point
adjustment and space temperature in F
(Fahrenheit) or C (Celsius). Includes FAN
and SYSTEM buttons (supports the
service functions of the standard sensor).
E-squared memory stores last
requirements. Curb shall be shipped
knocked down for field assembly and
shall include wood nailer strips.
Economizer - Horizontal
The horizontal economizer shall contain
the same features as the downflow
economizer with the exception of
barometric relief.
programmed set points. Requires 24VAC
(Volts AC).This sensor should be utilized
with ReliaTel™ controls.
Remote Potentiometer
DualThermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
The minimum position setting of the
economizer shall be adjusted with this
accessory.
Ventilation Override Accessory
With theVentilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust.The
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.
High Static Drive
The high static drive option shall allow the
standard motor on the 12½ and 20 ton
units to operate with improved external
static capabilities.
Manual Outside Air Damper
The rain hood and screen shall provide
up to 25 percent outside air.
Motorized Outside Air Dampers
Zone Sensors
Manually set outdoor air dampers shall
provide up to 50 percent outside air. Once
set, outdoor air dampers shall open to set
position when indoor fan starts.The
damper shall close to the full closed
position when indoor fan shuts down.
This option shall be provided to interface
with the Micro equippedVoyagers and
shall be available in either manual,
automatic, programmable with night
setback, with system malfunction lights or
remote sensor options.
RT-PRC002-EN
84
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
RT-PRC002-EN
PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-10-04
PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-09-04
09-04 Webb/Mason 10-04 Electronic Only
Supersedes
Trane
Stocking Location
A business ofAmerican Standard Companies