Trane Air Conditioner RTPRC002 EN User Manual

Packaged Cooling with  
Electric Heat Rooftop Units  
Voyager™  
12½ - 25Tons - 60 Hz  
RT-PRC002-EN  
October 2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
2
4
Introduction  
Features and Benefits  
Application Considerations  
9
10  
12  
13  
Selection Procedure  
Model Number Description  
General Data  
17  
Performance Data  
17  
31  
47  
Cooling Performance  
Fan Performance  
Heat Performance  
Controls  
49  
50  
70  
81  
Electric Power  
Dimension andWeights  
Mechanical Specifications  
RT-PRC002-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Factory Installed Options  
• Black Epoxy Pre-Coated Coils  
• Dehumidification Option  
• High Efficiency Motors  
• High Pressure Cutout  
• Hinged Access Doors  
• Novar Unit Controls  
Factory or Field Installed Options  
Clogged Filter/Fan Failure Switch  
Differential Pressure Switches  
Discharge Air Sensing Kit  
Downflow – Economizer  
Electric Heaters  
Frostat  
• Novar Return Air Sensor  
• Powered or Unpowered Convenience  
Outlet  
• Supply and/or Return Air Smoke  
Detector  
LonTalk® Communications Interface  
Oversized Motors  
Reference or Comparative Enthalpy  
Tool-less Hail Guards  
Trane Communications Interface (TCI)  
• Thermal ExpansionValve/Face-Split  
Evaporator Coil Option  
• Through the Base Electrical with Circuit  
Breaker  
• Through the Base ElectricalWith  
Disconnect Switch  
• Through the Base Utilities Access  
Two-Inch Pleated Filters  
Field Installed Options  
CO2 Sensing  
Digital Display Zone Sensor  
DualThermistor Remote Zone Sensor  
Low Static Drive  
High Static Drive  
Manual Outside Air Damper  
Motorized Outside Air Dampers  
Powered Exhaust  
Downflow – Roof Curb  
Horizontal – Economizer  
Remote Potentiometer  
Ventilation Override Accessory  
Zone Sensors  
RT-PRC002-EN  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Quality and Reliability are enhanced  
through ReliaTel control and logic:  
ReliaTel MakesTesting Easy  
Easy to Install, Service and  
Maintain  
ReliaTel requires no special tools to run  
theVoyager unit through its paces.  
Simply place a jumper betweenTest 1  
andTest 2 terminals on the LowVoltage  
Terminal Board and the unit will walk  
through its operational steps  
automatically.  
—prevents the unit from short cycling,  
considerably improving  
compressor life.  
Because todays owners are very cost-  
conscious when it comes to service and  
maintenance, theTrane Voyager was  
designed with direct input from service  
contractors.This valuable information  
helped to design a product that would get  
the serviceman off the job quicker and  
save the owner money.Voyager does  
this by offering:  
—ensures that the compressor will run  
for a specific amount of time which  
allows oil to return for better  
lubrication, enhancing the reliability of  
the compressor.  
—The unit automatically returns  
control to the zone sensor after  
stepping through the test mode a  
single time, even if the jumper is  
left on the unit.  
Voyager with ReliaTel reduces the  
number of components required to  
operate the unit, thereby reducing  
possibilities for component failure.  
Quality and Reliability  
ReliaTel™ Controls (LCI-R)  
As long as the unit has power and the  
“system on” LED is lit, ReliaTel is  
operational.The light indicates that the  
controls are functioning properly.  
ReliaTel Makes Installing and  
Servicing Easy  
ReliaTel eliminates the need for field  
installed anti-shortcycle timer and time  
delay relays. ReliaTel controls provide  
these functions as an integral part of the  
unit.The contractor no longer has to  
purchase these controls as options and  
pay to install them.  
ReliaTel features expanded diagnostic  
capabilities when utilized withTrane  
Integrated Comfort™ Systems.  
Some zone sensor options have central  
control panel lights which indicate the  
mode the unit is in and possible  
diagnostic information (dirty filters for  
example).  
The wiring of the low voltage connections  
to the unit and the zone sensors is as  
easy as 1-1, 2-2, and 3-3.This simplified  
system makes wiring easier for the  
installer.  
Other ReliaTel Benefits  
ReliaTel controls provide unit control for  
heating, cooling and ventilating utilizing  
input from sensors that measure outdoor  
and indoor temperature.  
The ReliaTel built-in anti-shortcycle timer,  
time delay relay and minimum “on” time  
control functions are factory tested to  
assure proper operation.  
ReliaTel softens electrical “spikes” by  
staging on fans, compressors and  
heaters.  
Intelligent Fallback is a benefit to the  
building occupant. If a component goes  
astray, the unit will continue to operate at  
predetermined temperature setpoint.  
ReliaTel™  
Intelligent Anticipation is a standard  
ReliaTel feature. It functions continuously  
as ReliaTel and zone sensor(s) work  
together in harmony to provide much  
tighter comfort control than conventional  
electro-mechanical thermostats.  
The same ReliaTel Board fits allVoyager  
Packaged Gas/Electrics, Cooling with  
Electric Heat, and Heat Pump models.  
This provides standardization of parts for  
contractors. Less money is tied up in  
inventory with ReliaTel.  
RT-PRC002-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Condenser Coil  
High Static Drive Accessory  
Outstanding Standard and  
Optional Components  
Voyager boasts a patent-pending 1+1+1  
condenser coil, permanently gapped for  
easy cleaning.  
Available on many models, this high  
static drive accessory extends the  
capability of the standard motor. Avoid  
expensive motors and operating costs by  
installing this optimized sheave  
accessory.  
Black Epoxy Pre-Coated Coils  
The pre-coated coils are an economical  
option for protection in mildly corrosive  
environments.  
Hinged Access Doors  
Cabinet Integrity  
These doors permit easy access to the  
filter, fan/heat, and compressor/control  
sections. They reduce the potential roof  
damage from screws or sharp access  
door corners.  
For added water integrity, Voyager has a  
raised 11/ " lip around the supply and  
return of8the downflow units to prevent  
water from blowing into the ductwork.  
Clogged Filter/Fan Failure Switch  
LonTalk® Communications Interface  
The LonTalk communications interface  
allows the unit to communicate as a  
Tracer™LCI-V device or directly with  
generic LonTalk Network Building  
Automation System Controls.  
A dedicated differential pressure switch is  
available to achieve active fan failure  
indication and/or clogged filter indication.  
CO2 Sensing  
The CO2 sensor has the ability to monitor  
space occupancy levels within the  
building by measuring the parts per  
million of CO2 (Carbon Dioxide) in the air.  
As the CO2 levels increase, the outside air  
damper modulates to meet the CO2  
space ventilation requirements.The CO  
sensor kit is available as a field installed2  
accessory.  
Digital Display Zone Sensor  
Power Exhaust Option  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone sensors. This sensor  
should be utilized with ReliaTel™ controls.  
This option is available on downflow units  
and provides exhaust of the return air,  
when using a downflow economizer, to  
maintain proper building pressurization.  
Great for relieving most building  
overpressurization problems.  
Discharge Air Sensing Kit  
Provides true discharge air sensing in  
heating models. The kit is functional only  
with the ReliaTel Options Module.  
Quick-Access Panels  
ColoredAnd NumberedWiring  
Save time and money tracing wires and  
diagnosing the unit.  
Remove three or fewer screws for  
access to the standardized internal  
components and wiring.  
DownflowAnd Horizontal Economizers  
The economizers come with three control  
options — dry bulb is standard, enthalpy  
and differential enthalpy are optional.  
Compressors  
Quick-Adjust Idler Arm  
Voyager contains the best compressor  
technology available to achieve the  
highest possible performance. Dual  
compressors are outstanding for  
humidity control, light load cooling  
conditions and system back-up  
applications. Dual compressors are  
available on all models.  
With the Quick-Adjust Idler Arm, the belt  
and sheaves can be quickly adjusted  
without moving the mounted fan motor.  
The result is a major savings in time and  
money.  
DualThermistor Remote Zone Sensor  
This sensor will reduce the total number  
of remote sensors to obtain space  
temperature averaging. This sensor  
should be utilized with ReliaTel controls.  
Factory Built Roof Curbs  
Available for downflow units. Only two  
roof curbs for the entireVoyager line  
simplifies curb selection.  
Refrigerant Circuits  
AllVoyager 12½-25 ton units shall have  
crankcase heaters, low and high pressure  
controls as standard.  
Fresh Air  
0 - 25% manual or 0 - 50% motorized  
outside air hoods are available.  
RT-PRC002-EN  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Reference or Comparative Enthalpy  
Measures and communicates humidity  
while maximizing comfort control.  
VariTrac  
Actual shipping tests were performed to  
determine packaging requirements. Units  
were test shipped around the country to  
determine the best packaging. Factory  
shake and drop tests were used as part  
of the package design process to help  
assure that the unit arrives at the job site  
in top condition.  
WhenTrane’s changeover VAV System  
for light commercial applications is  
coupled withVoyager, it provides the  
latest in technological advances for  
comfort management systems and can  
allow thermostat control in every zone  
served by VariTrac.  
Sloped Drain Pans  
Standard on every unit.  
Standardized Components  
Components are placed in the same  
location on allVoyager units. Familiarize  
yourself with oneVoyager and you are  
familiar with every Voyager.  
Ventilation Override Accessory  
Rigging tests include lifting a unit into the  
air and letting it drop one foot, assuring  
that the lifting lugs and rails hold up under  
stress.  
With theVentilation Override Accessory  
installed, the unit can be set to transition  
to up to 3 different pre-programmed  
sequences for Smoke Purge,  
Due to standardized components  
throughout theVoyager line, contractors/  
owners can stock fewer parts.  
We perform a 100% coil leak test at the  
factory.The evaporator and condenser  
coils are leak tested at 200 psig and  
pressure tested to 450 psig.  
Pressurization, and Exhaust.The  
transition occurs when a binary input on  
the RTOM is closed (shorted).This would  
typically be a hard wired relay output  
from a smoke detector or fire control  
panel.The ventilation override kit is  
available as a field installed accessory.  
Supply and/or Return Air Smoke  
Detector  
With this option installed, if smoke is  
detected, all unit  
All parts are inspected at the point of final  
assembly. Sub-standard parts are  
identified and rejected immediately.  
operation will be shut  
down. Reset will be  
manual at the unit.  
Return Air Smoke  
Detectors require  
minimum allowable  
airflow when used  
with certain models.  
Every unit receives a 100% unit run test  
before leaving the production line to  
make sure it lives up to rigorousTrane  
requirements.  
Zone Sensors  
Available in programmable, automatic  
and manual styles.  
Rigorous Testing  
Voyager units incorporate either a one  
piece top or theTrane-Tite-Top (T3). Each  
part of the top (either two or three pieces)  
overlaps in such a way that water cannot  
leak into the unit.These overlapped edges  
are gasketed and sealed to ensure  
superior water integrity.  
The fan and idler arm assembly designs  
have been tested to over 300,000 cycles  
each. Our combined cycle testing is now  
over 7,000,000 cycles.  
Tool-less Hail Guards  
Tool-less, hail  
protection quality coil  
guards shall be either  
All of Voyagers designs were rigorously  
rain tested at the factory to ensure water  
integrity.  
factory or field-installed for condenser  
coil protection.This option protects the  
condenser coil from vandalism and/or  
hail damage.  
VariTrac™  
Trane Communication Interface (TCI)  
Available factory or field installed.This  
module when applied with the ReliaTel™  
easily interfaces withTrane’s Integrated  
ComfortTM System.  
RT-PRC002-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Powered or Unpowered Convenience  
Outlet  
Factory Installed Options  
A wide variety of Factory Installed  
Options (FIOPs) are available.  
Easy to Install and Service  
Conversionless Units  
The dedicated design units (either  
downflow or horizontal) require no panel  
removal or alteration time to convert in  
the field — a major cost savings during  
installation.  
This option is a GFCI, 120v/15amp, 2 plug,  
convenience outlet, either powered or  
unpowered.This option can only be  
ordered when theThrough the Base  
Electrical with either the Disconnect  
Switch, or Circuit Breaker, option is  
ordered.This option is available on all  
downflow models.  
Added Efficiency  
Airflow  
Airflow is outstanding.TheVoyager can  
replace an older machine with old  
ductwork and, in many cases, improve  
the comfort through better air  
distribution.  
Horizontal units come complete with duct  
flanges so the contractor doesn’t have to  
field fabricate them.These duct flanges  
are a time and cost saver.  
High Efficiency Motors  
Easy Access LowVoltageTerminal Board  
Voyagers LowVoltageTerminal Board is  
external to the electrical control cabinet. It  
is extremely easy to locate and attach the  
thermostat wire.This is another cost and  
time saving installation feature.  
This option is available with efficiency  
ratings from 86.5 up to 91.0. It is not  
available for all models.  
U-shaped Airflow  
U-shaped airflow allows for improved  
static capabilities.  
LowAmbient Cooling  
Cooling capabilities down to 0°F as  
standard.  
Oversized Motors  
Factory or field installed oversized  
motors available for high static  
applications.  
One of our FinestAssets:  
Trane Sales Representatives are a  
Support group that can assist you with:  
— Product  
Single Point Power  
A single electrical connection powers the  
unit.  
Single Side Service  
Single side service is standard on all  
units.  
— Application  
LowVoltage Connections  
— Service  
Training  
The wiring of the low voltage connections  
to the unit and the zone sensors is as  
simple as 1-1, 2-2, and 3-3.This simplified  
system makes it easy for the installer to  
wire.  
— Special Applications  
— Specifications  
Through the Base Electrical with Circuit  
Breaker  
This option is a factory installed thermal  
magnetic, molded case, HACR Circuit  
Breaker with provisions for through the  
base electrical connections. This option is  
available on all downflow models.  
— Computer Programs and much more  
Voyager has the features and benefits  
that make it first class in the light  
commercial rooftop market. Designed  
with input from field contractors and  
engineers, its U-shaped airflow  
performance is outstanding.  
Through the Base Electrical with  
Disconnect Switch  
Factory installed 3-pole, molded case,  
disconnect switch with provisions for  
through the base electrical connections  
are available. This option is available on  
all downflow models.  
Through the Base UtilitiesAccess  
Electric Heaters  
An electrical service entrance shall be  
provided allowing electrical access for  
both control and main power connections  
inside the curb and through the base of  
the unit. Option will allow for field  
installation of liquid-tight conduit and an  
external field installed disconnect switch.  
Electric heat modules are available within  
the basic unit. If ordering theThrough the  
Base Electrical option with an Electrical  
Heater, the heater must be factory  
installed.  
RT-PRC002-EN  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Application of this product should be  
within the cataloged airflow and cooling  
considerations.  
Power Exhaust Accessory  
The power exhaust accessory is available  
on all 12½-25 ton downflow units.This  
accessory can be field installed and will  
assist in relieving building pressurization.  
LowAmbient Cooling  
ThisVoyager line features, as standard,  
low ambient cooling down to 0°F. The  
following options need to be included/  
considered when low ambient  
Condensate Trap  
The evaporator is a draw-thru  
configuration. A trap must be field  
provided prior to start-up on the cooling  
cycle.  
applications are required: continuous fan  
operation, crankcase heaters, thermal  
expansion valves, frostat. Contact your  
localTrane Representative for more  
assistance with low ambient cooling  
applications.  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate  
serviceability, maximum capacity and  
peak operating efficiency. Actual  
clearances which appear inadequate  
should be reviewed with the localTrane  
sales personnel.  
Barometric Relief  
This product line offers an optional  
barometric relief damper included in the  
downflow economizer accessory.This  
accessory consists of gravity dampers  
which open with increased pressure. As  
the building air pressure increases, the  
pressure in the unit return air section  
also increases, opening the dampers and  
relieving the conditioned space.  
Unit Pitch  
These units have sloped condensate  
drain pans. Units must be installed level,  
any unit slope must be toward access  
side of unit.  
NOTE:THE EFFECTIVENESS OF  
BAROMETRIC RELIEF DAMPER DURING  
ECONOMIZING OPERATION IS SYSTEM  
RELATED.  
PRESSURE DROP OF THE RETURN AIR  
SYSTEM SHOULD BE CONSIDEREDTO  
CONTROL BUILDING PRESSURIZATION.  
RT-PRC002-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedures  
Step 5  
To Find Capacity at Intermediate  
Conditions Not in theTable  
Cooling Capacity  
Step 1  
Calculate the buildings total and sensible  
cooling loads at design conditions. Use  
theTrane calculation methods or any  
other standard accepted method.  
If the performance will not meet the  
required load of the building -total or  
sensible cooling load, try a selection at  
the next higher size unit.  
When the design conditions are between  
two numbers that are in the capacity  
table, interpolation is required to  
approximate the capacity. Note:  
Extrapolation outside of the table  
conditions is not recommended.  
Heating Capacity  
Step 1  
Calculate the building heating load using  
theTrane calculation form or other  
standard accepted method.  
Factors used in unit selection:  
A
Step 4  
Total Cooling Load: 180 MBh  
In order to select the correct unit which  
meets the buildings requirements, the  
fan motor heat must be deducted from  
the gross cooling capacity.The amount of  
heat that the fan motor generates is  
dependent on the effort by the motor -  
cfm and static pressure.To determine the  
total unit static pressure you add the  
external static pressure to the additional  
static related by the added features:  
B
Sensible Cooling Load: 129 MBh  
Step 2  
C
Size the system heating capacity to  
Airflow: 6000 cfm  
match the calculated building heating  
D
load.The following are building heating  
Electrical Characteristics: 460/60/3  
requirements:  
A
E
Summer Design Conditions: Entering  
Total heating load of 115.0 MBH  
Evaporator Coil: 80 DB, 67WB Outdoor  
Ambient: 95 DB  
B
6000 cfm  
F
C
External Static (duct system)  
0.49 wg  
External Static Pressure: 0.49 in. wg  
460 volt/3 phase Power Supply  
G
Standard Filter 1 in.  
fromTable PD-35  
0.10 wg  
Rooftop - downflow configuration  
The electric heat accessory capacities are  
listed inTable PD-36. From the table, a 36  
kw heater will deliver 122.94 MBH at 480  
volts. In order to determine capacity at  
460 volts, the heater voltage correction  
factor fromTable PD-37 must be used.  
Therefore, 122.94 MBH x .94 (voltage  
correction factor) = 115.6 MBH.  
H
Accessories  
• Roof curb  
Economizer  
0.04 wg  
Economizer  
(100% Return Air) fromTable PD-35  
Electric Heat  
I
Heating  
Electric Heater Size 36 kw 0.07 wg  
fromTable PD-35  
Capacity 115 MBh  
460 volt/3 phase Electric Heat —at 6000  
cfm  
Air Delivery Selection  
External static pressure drop through the  
air distribution system has been  
Total Static Pressure  
0.60 wg  
Step 2  
As a starting point, a rough determination  
must be made of the size of the unit.The  
final selection will be made after  
examining the performance at the given  
conditions. Divide the total cooling load by  
nominal BTUH per ton (12 MBh per ton);  
then round up to the nearest unit size.  
calculated to be 0.50 inches of water.  
FromTable PD-35 static pressure drop  
through the economizer is 0.04 and the  
36 kw heater is 0.07 inches of water (0.49  
+ 0.04 + 0.07). EnterTable PD-18 for a  
TCD180B4 at 6000 cfm and 0.50 static  
pressure.The standard motor at 777 rpm  
will give the desired airflow at a rated bhp  
of 2.71.  
Note:The Evaporator Fan Performance  
Table PD-18 has already accounted for  
the pressure drop for standard filters and  
wet coils (see note belowTable PD-18).  
Therefore, the actual total static pressure  
is 0.60 -0.10 (fromTable PD-35) = 0.50 wg.  
With 6000 cfm and 0.50 wg.  
Table PD-18 shows 2.56 bhp for this unit.  
Note below the table gives a formula to  
calculate Fan Motor Heat,  
3.15 x bhp = MBH.  
3.15 x 2.56 = 8.06 MBH.  
180 MBh / 12 MBh = 15.0Tons  
Step 3  
Table PD - 2 shows that aTCD180B4 has a  
gross cooling capacity of 184 MBh and  
130 MBh sensible capacity at 6000 cfm  
and 95 DB outdoor ambient with 80 DB,  
67 WB air entering the evaporator.  
Now subtract the fan motor heat from  
the gross cooling capacity of the unit:  
NetTotal Cooling Capacity  
= 184 MBH - 8.06 = 175.9 MBH.  
Net Sensible Cooling Capacity  
= 130 MBH - 8.06 = 121.9 MBH.  
RT-PRC002-EN  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedure  
Dehumidification Selection  
68°F DB,  
67°F WB  
OA  
Determine normal unit cooling and  
heating capacities as previously  
described in the selection procedures on  
prior page.  
75°F DB,  
RA'  
52% RH  
MA' 72.2°F DB  
65°F WB  
OA  
MA'  
RA'  
Typical 20 tonTFD241C  
47°F DB  
6400 cfmTotal Supply airflow  
2560 cfm Outside Air (40%)  
3840 cfm Return Air  
SA'  
73°F DB  
SA  
0.41” External Static Pressure  
SA  
REHEAT  
SA'  
OA Conditions  
Part load day and raining  
68°F db  
67°F wb  
Chart C-1  
66.5 dp  
95% RH  
Step 3a: Determine leaving  
evaporator temperature SA’  
Leaving UnitTemperature = SA’  
Step 5: Determine leaving unit  
temperature with reheat active (SA)  
Reheat temperature (obtained in step 3)  
+ SA’ = SA  
17.55°F db + 53.6°F = 71.2°F db  
SA’=71.2°F  
RA’ conditions  
75°F db  
Utilizing the manual selection method as  
previously described and the formula  
63°F wb  
52% RH  
55.9 dp  
Temp = cooling capacity in Bth  
51 wb  
20.8 RH  
29.4 dp  
(cfm)(1.085)  
Step 1: Determine the mixed/  
entering air condition (MA)  
MA’ = (% outside air*outside air dry-bulb  
temperature) + (% return air*return air  
dry-bulb temperature)  
MA’ = (0.40*68°F) + (0.60*75°F)  
MA’ = 72.20°F db  
Note: Repeat for wet-bulb  
temperature (wb).  
Plot on psychrometric chart.  
or using the TOPSS™ program  
determine the leaving evaporator  
temperature (temperature without the  
addition of fan heat).  
Consider Chart C-1. If the space relative  
humidity is equal to or above the space  
relative humidity setpoint, the  
Dehumidification option will:  
517.74 db  
51.03 wb  
• Energize compressor or both  
compressors (2 stage compressor units).  
• Hot gas reheat valve is energized and  
hot gas is diverted to the reheat coil.  
• Dehumidification/reheat is terminated  
when space humidity is reduced to 5%  
below relative humidity setpoint.  
Step 3b: Determine leaving unit  
temperature in standard cooling  
mode  
Find the leaving unit temperature  
including fan heat as discussed in prior  
selection procedures and using the  
temperature formula from Step 3a or  
refer to yourTOPSS selection.  
53.6 db  
MA’  
72.2°F db  
64.7°F wb  
Step 2: Determine static pressure  
drop add for reheat  
At MA’, air enters the RTU.The RTU filters,  
cools, and dehumidifies the air as it  
moves through the evaporator coil. Air  
leaves the evaporator coil saturated at  
the preset dew point condition (SA) and  
is reheated by the hot gas reheat coil to  
deliver 71°F (SA) supply air to the space.  
Table PD-35 shows a static pressure drop  
of 0.35” for the reheat coil and an  
additional .04 for the mandatory 2”  
pleated filters required when ordering the  
dehumidification option.Total static  
pressure =  
51 wb  
84% RH  
49% dp  
1.0+0.035+0.04=1.075  
Step 4: Determine reheat  
temperature rise  
Using the leaving evaporator temp, go to  
PD-39 and find the reheat temperature  
rise for that particular cfm: 17.55°F db  
(1.1 for manual calculations)  
Do not forget to also add any additional  
static from other accessories.  
Table PD-29 (airflow table for 20 ton  
dehumidification units) indicates that a  
standard motor and drive is needed for  
this airflow and static pressure range.  
Note: Reheat temperature rise is based  
on supply airflow and leaving  
evaporator coil temperature.  
RT-PRC002-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Number  
Description  
Packaged Cooling with Electric Heat UnitTypical Model Nomenclature  
T
C
D
1
5
0
C
3
0
0
A
A
1
2
3
4
5
6
7
8
9
10  
11  
12  
Digits 1, 2 - Product Type  
Digit 7- Major Development Sequence  
Digit 8 - Electrical Characteristics  
TC = Packaged Cooling, Electric  
Heat  
TF = With Factory Installed  
Options  
3 = 208-230/60/3  
4 = 460/60/3  
W= 575/60/3  
K = 380/60/3  
Digit 3 - Airflow Configuration  
D = Downflow  
H = Horizontal  
Digit 9, 10 - Factory-Installed Options  
00 = No Factory-installed Options  
0A = Factory-installed Economizer  
0B = Oversized Motor  
Digits 4, 5, 6 - Nominal Gross Cooling  
Capacity (MBh)  
0C = Downflow Economizer and  
Oversized Motor  
0F = Trane Communications Interface  
(TCI)  
0G= Downflow Economizer and TCI  
0H = TXV/Face-Split Evaporator  
0J = Oversized Motor and TXV/Face-Split  
Evaporator  
150 =  
151 =  
180 =  
181 =  
210 =  
211 =  
240 =  
241 =  
300 =  
301 =  
12½ Tons Standard Efficiency  
12½ Tons High Efficiency  
15 Tons Standard Efficiency  
15 Tons High Efficiency  
17½ Tons Standard Efficiency  
17½ Tons High Efficiency  
20 Tons Standard Efficiency  
20 Tons High Efficiency  
0K = Downflow Economizer, Oversized  
Motor, and TXV/Face-Split Evaporator  
0L = Downflow Economizer with TXV/Face-  
Split Evaporator  
25 Tons Standard Efficiency  
25 Tons High Efficiency  
0M = Reheat Coil  
0N= Downflow Economizer and Reheat  
Coil  
0P = Oversized Motor and Reheat Coil  
0R = Downflow Economizer, Oversized  
Motor and Reheat Coil  
Digit 11- Minor Design Sequence  
Digit 12- Service Digit  
RT-PRC002-EN  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(12½, 15 Ton)  
Standard Efficiency  
Table GD - 1— General Data  
12½Ton Downflow and Horizontal Units  
TC*150D3, D4, DW, DK  
15Ton Downflow and Horizontal Units  
TC*180B3, B4, BW, BK  
Cooling Performance1  
Gross Cooling Capacity  
EER2  
150,000  
9.8  
182,000  
9.9  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part LoadValue3  
System Power (KW)  
Compressor  
5,000/4,400  
142,000  
10.5  
6,000/5,300  
174,000  
10.2  
14.49  
17.57  
No./Type  
2/Scrolls  
9.2  
Hi-Performance  
.375  
2/Scrolls  
9.2  
Hi-Performance  
.375  
Sound Rating (BELS)4  
Outdoor Coil Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
24.18  
27.12  
Rows/FPI  
2/16  
3/16  
Indoor Coil Type  
Tube Size (in.)  
Hi-Performance  
.375  
Hi-Performance  
.375  
Face Area (sq ft)  
17.5  
17.5  
Rows/FPI  
2/15  
2/15  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice  
1/1.00 NPT  
Propeller  
2/26  
Direct/1  
10,600  
Short Orifice  
1/1.00 NPT  
Propeller  
2/26  
Direct/1  
10,200  
No. Motors/HP  
2/.50  
2/.50  
Motor RPM  
1,100  
1,100  
Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
15 x 15  
Belt/1  
1
15 x 15  
Belt/1  
1
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size (Standard/Oversized)  
Filters Type Furnished6  
(No.) Size Recommended (in.)  
Downflow  
3.0/5.0  
3.0/5.0  
1,740/3,450  
145T/145T  
Throwaway  
1,740/3,450  
145T/145T  
Throwaway  
(2) 20 x 20 x 2, (4) 20 x 25 x 2  
(2) 20 x 20 x 2, (4) 20 x 25 x 2  
9.3/9.4/Circuit  
(2) 20 x 20 x 2, (4) 20 x 25 x 2  
(2) 20 x 20 x 2, (4) 20 x 25 x 2  
17.5/9.5/Circuit  
Horizontal  
Refrigerant Charge (Lbs of R-22)5  
Notes:  
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net  
and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification  
program, which is based on ARI Standard 340/360-93.  
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.  
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI  
rated cfm.  
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.  
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
6. Optional2inchpleatedfiltersarealsoavailable.  
7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(17½, 20, 25Ton)  
Standard Efficiency  
Table GD - 2 — General Data  
17½Ton  
20Ton  
25Ton  
Downflow and Horizontal Units  
TC*210C3, C4, CW, CK  
Downflow and Horizontal Units  
TC*240B3, B4, BW, BK  
Downflow and Horizontal Units  
TC*300B3, B4, BW, BK  
Cooling Performance1  
Gross Cooling Capacity  
EER2  
210,000  
9.8  
242,000  
9.7  
290,000  
9.7  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part LoadValue3  
System Power (KW)  
Compressor  
7,000/5,800  
196,000  
10.0  
8,000/7,000  
232,000  
10.0  
10,000/8,750  
272,000  
9.8  
20.0  
23.91  
28.05  
No./Type  
2/Scrolls  
9.4  
Hi-Performance  
.375  
2/Scrolls  
9.4  
Hi-Performance  
.375  
2/Scrolls  
9.4  
Hi-Performance  
.375  
Sound Rating (BELS)4  
Outdoor Coil Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
27.12  
35.30  
36.43  
Rows/FPI  
3/16  
3/16  
2/16  
Indoor Coil Type  
Tube Size (in.)  
Hi-Performance  
.375  
Hi-Performance  
.375  
Hi-Performance  
.375  
Face Area (sq ft)  
17.50  
26.00  
26.00  
Rows/FPI  
4/15  
2/15  
3/15  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice  
1/1.00 NPT  
Propeller  
2/26  
Direct/1  
13,400  
Short Orifice  
1/1.00 NPT  
Propeller  
2/26  
Direct/1  
14,600  
Short Orifice  
1/1.00 NPT  
Propeller  
2/28  
Direct/1  
16,700  
No. Motors/HP  
2/1.0  
2/1.0  
2/1.0  
Motor RPM  
1,125  
1,125  
1,125  
Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
15 x 15  
Belt / 1  
1
18 x 18  
Belt / 1  
1
18 x 18  
Belt / 1  
1
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size (Standard/Oversized)  
Filters Type Furnished7  
(No.) Size Recommended (in.)  
Downflow  
5.0/7.5  
5.0/7.5  
7.5/NA  
3,450/3,470  
145T/184T  
Throwaway  
3,450/3,470  
145T/184T  
Throwaway  
3,470/NA  
184T/NA  
Throwaway  
(2) 20 x 20 x 2, (4) 20 x 25 x 2  
(2) 20 x 20 x 2, (4) 20 x 25 x 2  
21.0/14.3/Circuit6  
(4) 20 x 20 x 2, (4) 20 x 25 x 2  
(8) 20 x 25 x 2  
(4) 20 x 20 x 2, (4) 20 x 25 x 2  
(8) 20 x 25 x 2  
Horizontal  
Refrigerant Charge (Lbs of R-22)5  
18.9/21.0/Circuit  
17.0/Circuit  
Notes:  
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net  
and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary Large  
Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.  
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.  
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI  
rated cfm.  
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.  
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit.  
7. Optional two inch pleated filters are also available.  
8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(12½, 15 Ton)  
High Efficiency  
Table GD - 3 — General Data  
12½Ton  
15Ton  
Downflow and Horizontal  
TC*151C3,C4,CW  
Downflow and Horizontal  
TC*181C3,C4, CW  
Cooling Performance1  
Gross Cooling Capacity  
EER2  
154,000  
11.3  
189,000  
11.58  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part LoadValue3  
System Power KW  
Compressor  
5,000/4,400  
146,000  
11.5  
6,000/5,300  
180,000  
13.3  
12.92  
15.653  
No./Type  
2/Scrolls  
9.2  
Hi-Performance  
0.375  
2/Scrolls  
9.2  
Hi-Performance  
0.375  
Sound Rating (BELS)4  
Outdoor Coil Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
27.12  
35.30  
Rows/FPI  
3/16  
3/16  
Indoor Coil Type  
Tube Size (in.)  
Hi-Performance  
0.375  
Hi-Performance  
0.375  
Face Area (sq ft)  
17.50  
26.00  
Rows/FPI  
3/15  
3/15  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice9  
1/1.0 NPT  
Propeller  
2/26  
Short Orifice8  
1/1.0 NPT  
Propeller  
2/26  
Direct/1  
10,400  
Direct/1  
11,000  
No. Motors/HP  
2/.50  
2/.50  
Motor RPM  
1100  
1100  
Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
15 x 15  
BELT/1  
1
18 x 18  
BELT/1  
1
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size (Standard/Oversized)  
Filters Type/Furnished?  
(No.) Size Recommended (in.)  
3.0/5.0  
3.0/5.0  
1740/3450  
145T/145T  
Throwaway/Yes8  
(2)20 x 20 x 2  
(4)20 x 25 x 2  
Hi-Performance  
0.375  
1740/3450  
145T/145T  
Throwaway/Yes8  
(4) 20 x 20 x 2  
(4) 20 x 25 x 2  
Hi-Performance  
0.375  
Optional Hot Gas Reheat Coil Type  
Tube Size (in.) OD  
Face Area (sq. ft.)  
17.5  
26  
Rows/FPI  
1/16  
1/16  
Refrigerant Charge (Lbs of R-22)5/Circuit  
Standard  
15.0/13.89  
15.3/14.3  
25.0/13.08  
27.8/11.4  
Optional Hot Gas Reheat Coil  
Notes:  
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net  
and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification  
program, which is based on ARI Standard 340/360-93.  
2. EER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI  
rated cfm.  
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.  
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
6. Face area for Indoor Coil on horizontal models is 12.36.  
7. Horizontal models have 4 - 20 x 25 x 2 filters.  
8. Optional two inch pleated filters are also available for 12½ ton models.  
9. TXV/Face-SplitOption(DownflowOnly)TCD151C3,4,W(RefrigerantControl):ExpansionValve;(RefrigerantCharge):13.4/12.0.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(17½, 20, 25 Ton)  
High Efficiency  
General  
Data  
Table GD - 4 — General Data  
17½Ton  
20Ton  
25Ton  
Downflow and Horizontal  
TC*211C3,C4,CW  
Downflow and Horizontal  
TC*241C3,C4,CW  
Downflow and Horizontal  
TC*301C3,C4,CW  
Cooling Performance1  
Gross Cooling Capacity  
EER2  
220,000  
11.0  
268,0009  
10.6  
300,00011  
10.411  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part LoadValue3  
System Power KW  
Compressor  
7,000/6,200  
208,000  
12.0  
8,000/7,000  
250,0009  
11.2  
10,000/8,750  
278,000  
11.011  
18.91  
23.589  
26.7311  
No./Type  
2/Scrolls  
2/Scrolls  
2/Scrolls  
Sound Rating (BELS)4  
Outdoor Coil —Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
9.4  
9.4  
Hi-Performance  
0.375  
9.4  
Hi-Performance  
0.375  
Hi-Performance  
0.375  
35.30  
35.30  
Rows/FPI  
3/16  
3/16  
3/16  
Indoor Coil Type  
Tube Size (in.)  
Hi-Performance  
Hi-Performance  
0.375  
Hi-Performance  
0.375  
0.375  
Face Area (sq ft)  
26.000  
26.00  
26.00  
Rows/FPI  
4/15  
Short Orifice  
1 /1.0 NPT  
Propeller  
2/26  
Direct/1  
12,800  
4/15  
4/15  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice9  
1/1.0 NPT  
Propeller  
2/26  
Short Orifice11  
1/1.0 NPT  
Propeller  
2/26  
Direct/1  
Direct/1  
13,700  
13,700  
No. Motors/HP  
2/1.00  
2/1.00  
2/1.00  
Motor RPM  
1125  
1125  
1125  
Indoor Fan Type  
No. Used  
FC Centrifugal  
FC Centrifugal  
1
FC Centrifugal  
1
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
18 x 18  
BELT/1  
1
18 x 18  
BELT/1  
1
18 x 18  
BELT/1  
1
Motor HP (Standard/Oversized)  
Motor RPM(Standard/Oversized)  
Motor Frame Size (Standard/Oversized)  
Filters Type Furnished7  
(No.) Size Recommended (in.)  
Optional Hot Gas Reheat Coil Type  
Tube Size (in.) OD  
5.0/7.5  
3450/3470  
145T/184T  
5.0/7.5  
7.5/NA  
3470/NA  
184T/NA  
3450/3470  
145T/184T  
Throwaway  
(4/4)20 x 20 x 2/20 x 25 x 26  
Hi-Performance  
0.375  
Throwaway  
Throwaway  
(4/4)20 x 20 x 2/20 x 25 x 26  
(4/4)20 x 20 x 2/20 x 25 x 26  
Face Area  
Rows/FPI  
26  
1/16  
Refrigerant Charge (Lbs of R-22)5 / Circuit  
Standard  
25.7/12.510  
21.8/21.89  
21.3/21.0  
24.5/24.511  
Optional Hot Gas Reheat Coil  
Notes:  
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net  
and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on ARI  
Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.  
2. EER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI  
rated cfm.  
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.  
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
6. Horizontal models have 8 - 20 x 25 x 2 filters.  
7. Optional two inch pleated filters are also available.  
8. TXV/Face-SplitOption(DownflowOnly)TCD181C3,4,W(EER):11.4;(SystemPowerkW):15.79;(RefrigerantControl):ExpansionValve;(RefrigerantCharge):26.0/12.0  
9. TXV/Face-SplitOption(DownflowOnly)TCD241C3,4,W(GrossCoolingCapacity):259,000;(ARINetCoolingCapacity):244,000;(SystemPowerkW):23.02;  
(RefrigerantControl):ExpansionValve;(RefrigerantCharge):21.5/22.2  
10.TXV/Face-SplitOption(DownflowOnly)TCD211C3,4,WRefrigerantCharge):27.0/10.0  
11. TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross Cooling Capacity): 294,000; (ARI Net Cooling Capacity): 272,000; (IPLV): 10.6; System Power kW): 27.2;  
RefrigerantControl:ExpansionValve;(RefrigerantCharge):21.0/23.0  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½, 15Ton)  
Standard Efficiency  
Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK  
AmbientTemperature  
85  
95  
105  
115  
67  
Enter  
Dry  
EnteringWet Bulb  
67  
CFM  
Bulb  
61  
67  
73  
61  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5  
80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6  
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5  
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0  
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6  
80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2  
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9  
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0  
75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9  
80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7  
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0  
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0  
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0  
80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5  
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8  
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0  
4500  
5000  
5500  
6000  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Cooling Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK  
AmbientTemperature  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2  
80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7  
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0  
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0  
75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9  
80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9  
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0  
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0  
75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1  
80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6  
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0  
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0  
75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2  
80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4  
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0  
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0  
5400  
6000  
6600  
7200  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(17½, 20Ton)  
Standard Efficiency  
Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase TC*210C3, C4, CW, CK  
AmbientTemperature  
85  
95  
105  
115  
67  
Enter  
Dry  
EnteringWet Bulb  
67  
CFM  
Bulb  
61  
67  
73  
61  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8  
80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0  
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0  
90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0  
75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4  
80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0  
85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0  
90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0  
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0  
80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0  
85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0  
90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0  
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5  
80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0  
85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0  
90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0  
6300  
7000  
7700  
8400  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Cooling Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*240B3, B4, BW, BK  
AmbientTemperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5  
80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0  
85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0  
90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0  
75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1  
80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0  
85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0  
90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0  
75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6  
80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0  
85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0  
90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0  
75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2  
80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0  
85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0  
90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0  
7200  
8000  
8800  
9600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(25Ton)  
Standard Efficiency  
Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase TC*300B3, B4, BW, BK  
AmbientTemperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
266 224 299 174 319 118 247 215 285 167 309 113 228 205 266 172 297 108 209 196 244 163 280 99.9  
270 268 300 215 321 161 252 252 285 209 311 155 237 237 266 200 297 149 221 221 244 190 280 142  
286 286 301 255 323 196 272 272 286 250 312 194 256 256 267 242 298 189 240 240 246 233 281 183  
301 301 304 295 326 232 289 289 289 289 314 231 275 275 275 275 300 229 259 259 259 259 282 224  
272 237 303 180 322 120 253 227 290 174 312 115 234 218 271 165 300 109 214 208 249 156 284 102  
277 277 304 223 324 171 262 262 290 219 314 161 246 246 271 211 301 155 229 229 249 201 284 147  
294 294 306 266 327 208 282 282 291 263 316 200 266 266 273 257 302 197 249 249 253 248 285 192  
308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 235  
275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188 301 111 216 214 251 178 285 103  
282 282 306 227 325 174 267 267 292 223 315 162 250 250 273 216 302 157 233 233 251 206 286 150  
298 298 308 272 328 216 286 286 294 270 317 203 270 270 276 264 304 200 253 253 256 255 286 196  
312 312 311 311 330 256 301 301 301 301 320 244 288 288 288 288 306 244 273 273 272 272 288 241  
278 248 306 185 324 123 258 239 293 181 315 118 239 229 275 172 302 113 217 217 253 184 286 104  
286 286 308 231 325 160 271 271 294 228 316 163 254 254 276 221 304 160 237 237 253 212 287 153  
301 301 310 277 327 224 289 289 296 276 319 205 274 274 278 271 305 204 257 257 257 257 288 200  
314 314 314 314 330 266 304 304 304 304 321 248 291 291 291 291 307 249 276 276 276 276 289 246  
9000  
10000  
10500  
11000  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½Ton)  
High Efficiency  
Performance  
Data  
Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*151C3, C4, CW— Standard Refrigeration System  
AmbientTemperature  
85  
95  
105  
115  
Enter  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8  
80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6  
85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0  
90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0  
75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7  
80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5  
85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0  
90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0  
75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6  
80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1  
85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0  
90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0  
75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6  
80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2  
85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0  
90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0  
4500  
5000  
5500  
6000  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Cooling Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½Ton)  
High Efficiency  
Performance  
Data  
Table PD-7 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase T*D151C3, C4, CW — Dehumidification (Hot Gas Reheat) or TXV Option  
AmbientTemperature  
85  
95  
105  
115  
Enter  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 123.8 88.0 138.9 73.4 155.2 55.8 118.2 84.4 132.8 70.1 148.6 52.6 112.1 80.7 126.2 66.6 141.5 49.2 105.6 76.8 119.1 62.8 133.8 45.6  
80 123.9 100.8 139.0 85.5 155.2 69.8 118.3 97.3 132.9 82.0 148.7 66.4 112.1 93.3 126.3 78.3 141.5 62.8 105.7 89.6 119.2 74.4 133.9 59.0  
85 124.0 113.6 139.1 98.3 155.3 82.5 118.5 110.1 133.0 94.7 148.8 79.1 112.5 106.3 126.4 91.0 141.6 75.4 104.3 104.3 119.3 87.1 134.0 71.6  
90 126.0 124.6 139.0 110.8 155.4 95.2 120.6 120.6 133.0 107.2 148.8 91.7 115.5 115.5 126.4 103.5 141.7 88.0 110.3 110.3 119.4 99.5 134.1 84.2  
75 133.0 99.5 148.7 80.0 165.5 59.1 126.7 95.9 141.9 76.4 158.2 55.7 120.0 91.9 134.7 72.5 150.4 52.2 112.8 87.8 126.9 68.5 142.0 48.5  
80 133.1 115.7 148.8 96.0 165.6 76.1 126.9 112.0 142.1 92.4 158.3 72.5 120.2 108.1 134.8 88.6 150.5 68.8 113.2 104.1 127.0 84.5 142.1 64.9  
85 132.7 132.7 148.8 111.9 165.7 92.0 128.6 126.0 142.1 108.2 158.4 88.4 122.5 121.6 134.8 104.3 150.6 84.7 116.2 116.2 127.1 100.4 142.3 80.7  
90 139.8 139.8 148.9 127.6 165.7 107.7 134.5 134.5 142.2 124.0 158.4 104.1 128.9 128.9 135.0 120.1 150.7 100.5 122.8 122.8 127.5 116.3 142.4 96.5  
75 139.3 109.8 155.4 86.2 172.5 61.7 132.6 106.1 148.2 82.5 164.7 58.3 125.4 102.0 140.4 78.6 156.4 54.7 117.8 97.8 132.2 74.5 147.6 50.9  
80 139.6 128.9 155.5 105.4 172.6 81.5 133.1 125.4 148.3 101.7 164.8 77.8 126.2 121.5 140.6 97.7 156.5 74.0 119.0 115.2 132.3 93.6 147.7 70.1  
85 143.2 143.2 155.5 124.1 172.8 100.5 137.6 137.6 148.3 120.4 165.0 96.8 131.5 131.5 140.7 116.6 156.7 93.0 125.0 125.0 132.4 112.5 147.8 89.0  
90 151.0 151.0 156.1 143.3 172.8 119.2 145.3 145.3 149.0 139.6 165.0 115.6 139.0 139.0 141.6 136.1 156.7 111.7 132.4 132.4 134.0 129.4 147.9 107.6  
75 142.5 116.0 158.8 90.2 176.0 63.3 135.6 112.2 151.3 86.4 168.0 59.8 128.2 108.3 143.3 82.4 159.5 56.2 120.4 104.1 134.9 78.2 150.4 52.4  
80 143.3 137.5 158.8 111.1 176.2 84.8 135.1 135.1 151.4 107.3 168.1 81.1 130.0 127.1 143.5 103.5 159.6 77.3 122.7 122.1 135.0 99.3 150.5 73.3  
85 149.0 149.0 159.0 131.9 176.3 105.6 143.1 143.1 151.6 128.2 168.2 101.9 136.7 136.7 143.6 124.2 159.8 98.2 129.9 129.9 135.2 120.1 150.7 94.2  
90 157.2 157.2 160.1 153.3 176.4 126.4 151.1 151.1 151.1 151.1 168.3 122.6 144.6 144.6 145.9 142.5 159.7 118.6 137.6 137.6 138.2 137.5 150.8 114.8  
75 145.1 121.9 161.6 93.7 179.0 64.7 138.1 118.3 154.0 89.9 170.8 61.2 130.5 114.2 145.8 85.9 162.0 57.3 122.6 110.1 137.1 81.7 152.7 53.3  
80 145.6 145.6 161.6 116.5 179.2 87.9 140.4 138.6 154.0 112.8 170.9 84.2 133.1 133.1 145.8 108.8 162.1 80.3 126.2 126.2 137.1 104.5 152.9 76.3  
85 154.1 154.1 162.0 139.4 179.3 110.7 147.9 147.9 154.4 135.7 171.0 106.9 141.3 141.3 146.3 131.7 162.2 103.0 134.2 134.2 137.7 127.6 153.1 99.2  
90 162.6 162.6 162.5 162.5 179.5 133.2 156.3 156.3 157.1 154.9 171.2 129.5 149.5 149.5 149.4 149.4 162.4 125.5 142.2 142.2 142.2 142.2 153.1 121.5  
75 147.5 127.8 164.0 97.2 181.5 66.0 140.3 124.0 156.2 93.3 173.1 62.2 132.6 119.9 147.8 89.3 164.1 58.4 124.6 116.0 138.9 85.1 154.7 54.3  
80 150.2 149.4 164.1 121.8 181.7 90.9 143.5 143.5 156.2 117.9 173.2 87.1 136.8 136.8 147.9 114.0 164.3 83.2 129.7 129.7 139.0 109.8 154.8 79.2  
85 158.5 158.5 164.6 146.7 181.8 115.5 152.1 152.1 156.8 142.9 173.4 111.8 145.3 145.3 148.6 139.0 164.4 107.8 138.0 138.0 140.0 134.9 154.9 103.7  
90 167.4 167.4 167.9 167.1 182.1 139.9 160.8 160.8 160.7 160.7 173.6 136.1 153.8 153.8 153.7 153.7 164.6 132.2 146.3 146.3 146.2 146.2 155.1 128.2  
75 149.6 133.5 165.9 100.3 183.7 67.0 142.2 129.6 158.0 96.4 175.1 63.2 134.4 125.6 149.5 92.5 166.0 59.4 126.4 121.7 140.5 88.3 156.4 55.3  
80 153.4 153.4 166.1 126.9 183.8 93.6 147.0 147.0 158.1 123.0 175.2 90.0 140.2 140.2 149.6 118.9 166.1 86.1 132.8 132.8 140.6 115.0 156.5 82.0  
85 162.5 162.5 166.9 153.7 183.9 120.1 155.9 155.9 159.1 150.0 175.3 116.3 148.8 148.8 148.7 148.7 166.2 112.5 141.3 141.3 142.4 138.6 156.6 108.4  
90 171.6 171.6 171.6 171.6 184.3 146.4 164.8 164.8 164.7 164.7 175.7 142.6 157.6 157.6 157.5 157.5 166.5 138.7 149.9 149.9 149.9 149.9 157.0 134.7  
2500*  
3250*  
4000*  
4500  
5000  
5500  
6000  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate  
airflow table notes.  
2. MBH = Total Gross Cooling Capacity  
3. SHC = Sensible Heat Capacity  
*Unit applications below 4000 CFM  
Electric heaters restricted on applications below 4000 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4000 CFM.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15Ton)  
High Efficiency  
Performance  
Data  
Table PD-8 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*181C3, C4, CW— Standard Refrigeration System  
AmbientTemperature  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
172 144 194 112 205 75.2 159 138 185 107 200 71.9 147 131 172 101 193 68 130 130 158 97 183 63.4  
175 169 195 138 207 103 164 162 186 134 202 99.7 153 153 173 128 194 95.4 142 142 158 122 183 90.5  
185 185 196 164 209 126 176 176 186 161 203 124 165 165 174 156 195 122 155 155 155 155 184 117  
195 195 195 195 211 149 188 188 190 184 204 148 178 178 179 179 196 147 168 168 167 167 184 144  
177 153 197 116 207 76 164 147 189 112 202 73.2 151 140 176 106 195 69.3 138 131 162 99.8 185 64.8  
181 180 198 144 209 105 170 170 189 142 204 103 159 159 177 136 196 99.4 148 148 162 130 186 94.6  
192 192 199 172 211 129 183 183 190 171 206 129 173 173 173 173 197 127 162 162 162 162 186 124  
201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 152  
181 162 198 123 208 76.6 168 155 191 117 204 74.4 152 152 180 111 197 70.6 142 139 165 105 187 66.2  
186 186 200 151 210 107 177 177 192 148 206 105 166 166 180 144 198 102 154 154 166 137 188 98.6  
197 197 202 179 213 131 189 189 194 180 208 132 179 179 183 173 199 132 168 168 170 166 189 129  
204 204 205 202 215 157 199 199 199 199 209 159 191 191 191 191 201 160 181 181 181 181 190 160  
184 170 200 127 209 79.1 168 168 193 121 206 76.4 156 156 182 116 198 71.9 145 145 168 110 189 67.4  
191 191 202 153 211 108 182 182 194 154 207 107 171 171 183 151 199 105 159 159 169 145 190 102  
200 200 204 185 214 134 194 194 194 194 209 136 185 185 187 181 201 135 174 174 174 174 191 134  
207 207 208 207 217 160 203 203 203 203 211 163 195 195 195 195 203 166 186 186 186 186 192 167  
5400  
6000  
6600  
7200  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15 Ton)  
High Efficiency  
Performance  
Data  
Table PD-9 — Gross Cooling Capacities (MBH) 15 Ton Three Phase T*D181C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option  
AmbientTemperature  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 150.0 106.0 168.0 88.9 187.7 68.3 144.0 102.3 161.4 85.3 180.6 64.8 137.5 98.4 154.4 81.6 173.0 61.2 130.8 94.4 147.1 77.8 165.0 57.5  
80 150.2 121.0 168.1 103.0 187.8 84.7 144.1 117.3 161.5 99.3 180.7 81.1 137.7 113.4 154.6 95.4 173.1 77.2 131.0 109.3 147.3 91.5 165.1 73.3  
85 150.2 135.8 168.2 117.9 187.9 99.5 144.2 132.1 161.7 114.1 180.8 95.8 137.9 128.1 154.8 110.3 173.2 92.0 130.7 122.5 147.5 106.2 165.2 88.0  
90 151.8 148.3 168.4 132.7 188.0 114.2 146.3 144.5 161.9 128.9 180.9 110.5 140.5 140.5 155.0 125.0 173.3 106.7 134.9 134.9 147.7 120.9 165.4 102.7  
75 161.5 119.8 180.4 96.8 201.0 72.4 154.8 115.8 173.1 93.0 193.0 68.7 147.7 111.8 165.4 89.0 184.6 64.9 140.2 107.5 157.2 84.8 175.7 61.0  
80 161.7 138.5 180.6 115.6 201.1 92.3 154.9 134.5 173.3 111.7 193.1 88.5 147.8 130.4 165.6 107.6 184.7 84.5 140.4 126.1 157.4 103.5 175.8 80.4  
85 162.6 155.0 180.8 134.3 201.3 110.9 156.3 150.7 173.5 130.3 193.3 107.0 149.8 146.3 165.8 126.3 184.9 103.0 142.9 141.9 157.7 122.0 176.0 98.9  
90 168.5 168.5 180.9 152.7 201.5 129.4 162.8 162.8 173.6 148.8 193.5 125.5 156.8 156.8 165.9 144.6 185.1 121.5 150.5 150.5 157.9 140.4 176.2 117.3  
75 169.6 132.0 189.0 104.3 210.2 75.6 162.4 127.9 181.2 100.4 201.5 71.8 154.7 123.7 172.8 96.2 192.4 67.9 146.6 119.2 164.1 91.9 182.8 63.9  
80 170.0 154.3 189.3 126.8 210.4 98.8 162.9 150.3 181.4 122.7 201.7 94.8 155.4 146.0 173.1 118.6 192.6 90.7 147.5 139.4 164.4 114.3 183.0 86.5  
85 173.4 173.4 189.5 149.0 210.6 121.0 166.9 166.9 181.7 145.0 201.9 117.0 160.5 160.5 173.3 140.7 192.8 112.9 153.7 153.7 164.6 136.3 183.3 108.6  
90 182.3 182.3 189.9 171.1 210.8 143.1 176.1 176.1 182.2 167.0 202.2 139.1 169.5 169.5 169.3 169.3 193.1 134.9 162.5 162.5 165.7 155.6 183.6 130.6  
75 173.7 139.5 193.4 108.9 214.8 77.5 166.2 135.3 185.2 104.9 205.8 73.7 158.3 130.9 176.6 100.7 196.3 69.7 150.0 126.5 167.6 96.4 186.4 65.6  
80 174.6 164.4 193.7 133.7 215.0 102.8 164.2 164.2 185.5 129.6 206.0 98.7 159.8 153.0 176.9 125.4 196.5 94.5 152.1 148.0 167.9 121.0 186.6 90.3  
85 180.1 180.1 193.9 158.1 215.3 127.3 173.8 173.8 185.8 154.0 206.3 123.2 167.0 167.0 177.2 149.7 196.8 119.0 159.9 159.9 168.2 145.3 186.9 114.7  
90 189.8 189.8 189.8 189.8 215.5 151.6 183.3 183.3 183.3 183.3 206.6 147.6 176.4 176.4 179.1 170.7 197.1 143.4 169.1 169.1 170.7 165.6 187.2 139.0  
75 177.2 146.6 197.0 113.2 218.7 79.2 169.4 142.4 188.6 109.1 209.4 75.4 161.3 138.0 179.8 104.9 199.6 71.3 152.8 133.5 170.5 100.5 189.4 67.0  
80 178.8 171.0 197.4 140.3 218.9 106.5 169.8 169.8 189.0 136.2 209.6 102.4 164.0 161.4 180.1 131.9 199.8 98.2 155.8 155.8 170.9 127.5 189.6 93.9  
85 186.4 186.4 197.6 166.9 219.2 133.3 179.8 179.8 189.3 162.7 209.9 129.2 172.8 172.8 180.6 158.4 200.2 125.0 165.3 165.3 171.5 153.9 190.0 120.6  
90 196.7 196.7 196.5 196.5 219.4 159.9 189.8 189.8 189.7 189.7 210.2 155.8 182.6 182.6 183.8 180.6 200.5 151.6 174.9 174.9 174.8 174.8 190.2 146.9  
75 180.2 153.4 200.2 117.4 221.9 80.8 172.3 149.2 191.5 113.2 212.4 76.8 164.0 144.8 182.5 108.9 202.4 72.6 155.4 140.2 172.9 104.5 191.9 68.2  
80 182.9 179.1 200.5 146.6 222.1 110.1 175.6 174.4 191.9 142.5 212.6 105.9 167.6 167.6 182.7 138.0 202.6 101.7 160.2 160.2 173.2 133.4 192.1 97.3  
85 192.0 192.0 201.0 175.4 222.5 139.1 185.1 185.1 192.5 171.2 213.0 134.9 177.8 177.8 183.6 166.9 203.0 130.7 170.1 170.1 169.9 169.9 192.5 126.2  
90 202.7 202.7 204.3 199.9 222.7 167.8 195.5 195.5 196.3 195.1 213.2 163.5 188.0 188.0 187.9 187.9 203.2 159.2 180.0 180.0 179.9 179.9 192.8 154.7  
75 182.8 160.1 202.8 121.3 224.7 82.1 174.8 155.8 194.0 117.1 214.9 78.0 166.4 151.4 184.7 112.8 204.7 73.7 157.7 146.8 175.0 108.4 193.9 69.4  
80 186.0 186.0 203.2 152.8 224.9 113.4 179.1 179.1 194.2 148.3 215.2 109.3 171.8 171.8 185.0 143.9 205.0 105.0 164.1 164.1 175.4 139.3 194.3 100.6  
85 196.9 196.9 204.0 183.7 225.2 144.5 189.8 189.8 195.4 179.5 215.6 140.5 182.3 182.3 182.1 182.1 205.4 136.2 174.3 174.3 177.1 167.2 194.7 131.7  
90 207.9 207.9 207.8 207.8 225.4 175.3 200.6 200.6 200.5 200.5 215.8 171.1 192.8 192.8 192.6 192.6 205.7 166.7 184.5 184.5 184.4 184.4 195.1 162.2  
3000*  
3900*  
4800*  
5400  
6000  
6600  
7200  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate  
airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unit applications below 4800 CFM  
Electric heaters restricted on applications below 4800 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 4800 CFM.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(17½Ton)  
High Efficiency  
Table PD-10 — Gross Cooling Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW — Standard Refrigeration Option  
AmbientTemperature  
85  
95  
105  
115  
Enter  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2  
80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0  
85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0  
90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0  
75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0  
80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0  
85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0  
90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0  
75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7  
80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0  
85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0  
90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0  
75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2  
80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0  
85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0  
90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0  
6300  
7000  
7700  
8400  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Cooling Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(17½Ton)  
High Efficiency  
Table PD-11 — Gross Cooling Capacities (MBH)17½ Ton Three Phase T*D211C3, C4, CW— TXV Option  
AmbientTemperature  
85  
95  
105  
115  
67  
Enter  
Dry  
EnteringWet Bulb  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 178.1 125.2 199.2 102.8 222.1 78.3 170.4 120.6 190.9 98.4 213.1 74.0 162.3 115.7 182.1 93.7 203.6 69.5 153.6 110.7 172.8 88.9 193.6 64.9  
80 178.3 143.9 199.4 121.1 222.2 97.7 170.6 139.3 191.1 116.5 213.3 93.4 162.4 134.5 182.3 111.8 203.8 88.8 153.8 129.5 173.1 106.8 193.7 84.0  
85 178.6 163.0 199.6 139.7 222.4 116.2 171.0 158.4 191.3 135.0 213.5 111.9 163.0 153.7 182.5 130.2 204.0 107.2 151.7 151.7 173.3 125.2 194.0 102.4  
90 181.8 177.2 199.8 158.2 222.6 134.6 175.2 171.7 191.5 153.5 213.7 130.2 168.1 165.8 182.7 148.7 204.2 125.5 160.6 160.1 173.5 143.8 194.2 120.6  
75 190.8 142.2 212.7 113.0 236.1 82.3 182.3 137.4 203.5 108.3 226.2 78.0 173.3 132.4 193.9 103.4 215.8 73.4 163.8 127.2 183.7 98.3 204.8 68.6  
80 191.2 166.4 213.0 136.6 236.3 106.8 182.8 161.6 203.8 131.8 226.5 102.3 173.9 156.6 194.1 126.9 216.0 97.5 164.7 151.5 184.0 121.8 205.1 92.6  
85 193.7 186.8 213.2 160.2 236.6 130.2 186.2 180.5 204.1 155.4 226.8 125.6 178.3 173.9 194.4 150.4 216.3 120.8 169.9 167.2 184.3 145.3 205.3 115.8  
90 201.2 201.2 213.6 183.9 236.9 153.5 194.2 194.2 204.7 179.3 227.0 148.9 186.6 186.6 195.2 174.4 216.6 144.0 178.5 178.5 185.2 169.3 205.6 139.0  
75 199.5 157.9 221.6 122.1 245.5 85.7 190.5 153.0 212.0 117.4 234.9 81.2 180.9 147.9 201.7 112.4 223.8 76.5 171.0 142.6 190.9 107.3 212.2 71.6  
80 200.9 187.5 221.9 150.5 245.8 114.8 192.2 182.6 212.3 145.8 235.3 110.1 179.9 179.9 202.0 140.8 224.1 105.2 173.8 166.9 191.2 135.6 212.5 100.2  
85 207.3 204.9 222.5 179.2 246.2 142.9 199.3 198.8 213.0 174.6 235.4 138.1 190.6 190.6 202.7 169.6 224.4 133.3 182.0 182.0 192.0 164.4 212.8 128.2  
90 217.4 217.4 224.2 208.4 246.5 171.0 209.5 209.5 214.9 203.9 235.8 166.2 201.4 201.4 201.3 201.3 224.8 161.4 192.6 192.6 195.4 187.3 213.2 156.4  
75 203.9 167.7 226.2 127.9 250.3 87.7 194.8 162.9 216.2 123.2 239.2 83.0 185.0 157.7 205.6 118.1 227.8 78.4 174.8 152.4 194.5 112.9 215.8 73.  
80 202.9 202.9 226.5 159.5 250.5 119.7 195.2 195.2 216.6 154.8 239.4 114.8 188.9 182.8 206.0 149.7 228.1 110.1 179.6 175.4 194.9 144.5 216.1 105.0  
85 214.6 214.6 227.5 191.5 250.9 150.9 206.7 206.7 217.4 186.6 239.8 146.1 198.1 198.1 207.2 181.8 228.5 141.3 189.1 189.1 196.3 176.6 216.5 136.2  
90 226.3 226.3 226.2 226.2 251.4 182.3 218.0 218.0 221.1 212.1 240.4 177.4 209.4 209.4 211.9 204.9 228.9 172.4 200.2 200.2 202.0 197.2 217.2 167.6  
75 207.8 177.3 229.9 133.4 254.2 89.6 198.5 172.5 219.7 128.6 242.8 84.9 188.5 167.4 208.8 123.5 231.1 80.1 178.2 162.0 197.4 118.3 218.8 75.1  
80 212.0 205.1 230.4 168.2 254.5 124.4 203.5 198.3 220.0 163.5 243.1 119.6 194.3 190.9 209.4 158.4 231.4 114.7 184.7 183.5 198.1 153.1 219.2 109.6  
85 221.9 221.9 231.8 203.6 254.9 158.8 213.4 213.4 221.6 198.6 243.5 153.8 204.7 204.7 211.2 193.7 231.8 149.0 195.4 195.4 200.2 188.5 219.6 143.9  
90 234.1 234.1 236.8 229.0 255.6 193.4 225.4 225.4 227.5 221.6 244.3 188.5 216.5 216.5 217.7 214.0 232.5 183.4 206.9 206.9 207.6 206.7 220.6 178.6  
75 211.3 186.8 233.0 138.7 257.4 91.4 201.8 181.9 222.6 133.9 245.7 86.5 191.8 176.7 211.5 128.8 233.8 81.7 181.3 171.3 199.9 123.5 221.3 76.7  
80 217.2 212.9 233.7 176.7 257.8 129.0 208.4 206.0 223.3 171.9 246.1 124.1 199.0 198.7 212.3 166.8 234.2 119.3 189.0 189.0 200.8 161.5 221.7 114.1  
85 228.2 228.2 235.8 215.3 258.2 166.4 219.5 219.5 225.5 210.3 246.5 161.4 210.4 210.4 210.3 210.3 234.6 156.6 200.8 200.8 200.7 200.7 222.2 151.5  
90 241.0 241.0 242.8 238.1 259.2 204.2 231.9 231.9 233.1 230.7 247.7 199.3 222.4 222.4 222.3 222.3 235.7 194.2 212.6 212.6 212.6 212.6 223.5 189.2  
75 214.5 195.9 235.7 143.9 260.2 92.9 204.9 191.1 225.0 139.0 248.3 88.0 190.7 190.7 213.7 133.9 236.1 83.2 181.3 181.3 201.9 128.6 223.4 78.2  
80 221.9 220.3 236.6 185.0 260.5 133.5 212.1 212.1 225.8 180.0 248.6 128.5 203.1 203.1 214.8 175.0 236.5 123.7 193.4 193.4 203.2 169.7 223.8 118.5  
85 233.9 233.9 239.5 226.8 261.0 173.9 224.8 224.8 224.7 224.7 249.2 168.9 215.5 215.5 215.4 215.4 236.9 163.8 205.5 205.5 207.7 200.6 224.4 158.9  
90 247.0 247.0 248.0 246.9 262.4 214.8 237.7 237.7 237.6 237.6 250.7 209.8 227.8 227.8 227.8 227.8 238.6 204.7 217.8 217.8 217.7 217.7 226.3 199.7  
3500*  
4550*  
5600  
6300  
7000  
7700  
8400  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Cooling Capacity  
3. SHC = Sensible Heat Capacity  
*Unit applications below 5600 CFM  
Electric heaters restricted on applications below 5600 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 5600 CFM.  
RT-PRC002-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(20Ton)  
High Efficiency  
Table PD-12 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*241C3, C4, CW — Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
246 205 273 158 284 105 228 196 263 152 280 101 208 186 246 145 273 96.5 191 176 222 136 261 91.5  
250 245 274 192 287 142 232 232 264 190 283 141 216 216 246 183 274 135 201 201 223 172 261 130  
263 263 275 227 290 171 251 251 265 228 285 173 236 236 248 221 275 170 219 219 225 211 262 168  
274 274 278 262 293 201 266 266 268 265 288 206 254 254 254 254 277 205 239 239 237 237 262 205  
253 218 275 163 285 107 234 209 267 159 282 103 214 199 252 152 275 98.3 194 189 228 142 266 93.6  
257 257 277 199 289 144 243 243 268 199 285 143 227 227 252 194 277 140 210 210 228 184 266 136  
270 270 279 236 292 174 261 261 270 240 288 177 247 247 255 237 278 177 230 230 232 226 266 177  
280 280 282 273 295 205 274 274 274 274 291 212 264 264 264 264 280 214 250 250 248 248 267 218  
258 230 278 167 287 109 240 221 270 164 284 105 219 211 256 159 277 100 199 199 232 149 269 95.5  
264 264 280 204 290 155 252 252 271 208 287 145 236 236 257 205 279 144 218 218 233 195 269 141  
276 276 282 244 293 177 268 268 274 250 290 181 256 256 260 251 281 182 240 240 238 238 269 185  
285 285 286 281 297 209 280 280 280 280 293 217 271 271 271 271 283 221 258 258 258 258 271 229  
262 240 280 169 288 110 246 233 273 169 285 106 225 223 260 166 278 102 205 205 236 156 271 97.1  
270 270 282 209 291 161 260 260 274 215 288 147 245 245 261 215 281 147 226 226 237 205 271 146  
280 280 284 250 295 179 274 274 277 260 291 184 263 263 265 263 282 186 248 248 246 246 272 193  
288 288 288 288 298 212 284 284 284 284 294 222 276 276 276 276 285 228 264 264 265 265 275 240  
7200  
8000  
8800  
9600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(20Ton)  
High Efficiency  
Table PD-13 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— TXV Option  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 208.5 149.1 233.3 122.6 260.1 94.5 199.6 143.8 223.6 117.3 249.8 89.3 190.1 138.1 213.4 111.9 238.6 84.0 180.0 132.3 202.5 105.8 226.9 78.5  
80 208.7 171.1 233.4 144.4 260.2 117.1 199.9 165.6 223.8 139.1 249.8 111.8 190.4 159.9 213.6 133.4 238.7 106.3 180.4 153.9 202.7 127.6 226.9 100.7  
85 209.5 193.0 233.6 166.3 260.3 138.9 200.8 187.5 224.0 160.9 249.9 133.7 191.4 181.7 213.8 155.2 238.9 128.1 181.6 175.7 203.0 149.3 227.1 122.4  
90 212.7 212.7 233.9 188.1 260.5 160.6 205.2 205.2 224.3 182.6 250.1 155.2 197.4 197.4 214.1 176.8 239.1 149.7 189.0 189.0 203.4 170.8 227.3 143.9  
75 223.8 169.6 249.5 135.2 277.5 99.6 213.8 163.8 238.8 129.6 265.8 94.2 203.4 157.8 227.5 123.9 253.4 88.6 192.4 151.6 215.6 117.8 240.4 82.9  
80 224.5 197.4 249.7 163.1 277.6 128.2 214.8 191.6 239.1 157.5 265.9 122.7 204.4 185.6 227.8 151.6 253.6 117.0 193.5 179.4 215.9 145.6 240.6 111.1  
85 226.7 222.0 249.9 190.8 277.9 155.9 217.9 215.9 239.4 185.1 266.2 150.3 208.8 208.8 228.2 179.2 253.8 144.5 199.6 199.6 216.3 173.0 240.8 138.6  
90 237.7 237.7 250.8 218.3 278.1 183.4 229.4 229.4 240.3 212.6 266.5 177.8 220.4 220.4 229.2 206.6 254.1 172.0 211.0 211.0 217.5 200.4 241.1 165.9  
75 234.3 187.9 260.5 146.4 289.2 103.7 223.9 182.1 249.1 140.7 276.7 98.2 212.8 175.9 237.1 134.8 263.3 92.5 201.1 169.5 224.3 128.7 249.4 86.5  
80 235.9 221.8 260.8 180.1 289.4 138.0 225.7 215.9 249.4 174.3 276.9 132.3 214.9 209.8 237.3 168.2 263.6 126.5 202.8 202.8 224.6 161.9 249.6 120.4  
85 243.8 243.8 261.4 213.2 289.7 171.3 234.9 234.9 250.1 207.4 277.2 165.6 225.3 225.3 238.2 201.3 264.0 159.7 215.3 215.3 225.7 195.0 250.0 153.6  
90 257.1 257.1 263.2 246.7 290.1 204.5 247.9 247.9 252.1 240.8 277.5 198.6 238.1 238.1 240.6 234.8 264.3 192.6 227.7 227.7 228.5 224.2 250.4 186.3  
75 239.8 199.6 266.0 153.5 295.0 106.1 229.0 193.6 254.2 147.8 282.1 100.6 217.6 187.4 241.8 141.7 268.2 94.7 205.6 180.9 228.6 138.4 253.8 88.7  
80 242.3 237.5 266.3 190.6 295.3 144.0 230.8 230.8 254.6 184.7 282.3 138.3 221.3 221.1 242.2 178.6 268.6 132.4 210.7 210.7 229.2 172.3 254.2 126.2  
85 253.7 253.7 267.4 227.6 295.7 181.1 244.3 244.3 255.7 221.6 282.7 175.3 234.3 234.3 243.5 215.5 269.1 169.3 223.6 223.6 230.6 209.1 254.6 163.1  
90 267.6 267.6 270.3 265.1 296.0 217.7 257.9 257.9 257.8 257.8 283.2 211.9 247.5 247.5 247.5 247.5 269.6 205.7 236.6 236.6 236.6 236.6 255.3 199.4  
75 244.5 210.8 270.7 160.1 299.8 108.3 233.4 204.7 258.5 154.3 286.5 102.8 221.8 198.5 245.8 148.2 272.4 96.9 209.5 191.9 232.3 141.9 257.5 90.8  
80 248.1 248.1 271.1 200.8 300.1 149.8 238.5 238.5 259.0 194.8 286.8 144.0 228.4 228.4 246.3 188.7 272.8 138.1 217.6 217.6 232.9 182.3 258.0 131.8  
85 262.5 262.5 272.6 241.6 300.5 190.5 252.6 252.6 260.7 235.6 287.3 184.7 242.1 242.1 248.1 229.3 273.3 178.7 231.0 231.0 235.0 222.9 258.3 172.1  
90 277.2 277.2 277.0 277.0 301.0 230.6 266.9 266.9 266.8 266.8 288.0 224.7 256.0 256.0 256.0 256.0 274.1 218.5 244.6 244.6 244.5 244.5 259.4 212.1  
75 248.5 221.7 274.6 166.6 303.7 110.4 237.3 215.6 262.1 160.6 290.2 104.8 225.4 209.3 249.0 154.6 275.8 98.9 213.0 202.7 235.3 148.3 260.6 92.7  
80 255.2 255.2 275.2 210.8 304.0 155.3 245.3 245.3 262.8 204.7 290.6 149.6 234.7 234.7 249.8 198.5 276.2 143.5 223.6 223.6 236.2 192.0 261.1 137.3  
85 270.2 270.2 277.2 255.2 304.3 199.4 259.9 259.9 265.1 249.2 291.0 193.6 249.0 249.0 252.3 242.9 276.7 187.4 237.5 237.5 239.1 236.5 261.6 180.9  
90 285.5 285.5 285.4 285.4 305.2 243.0 274.8 274.8 274.8 274.8 292.1 237.2 263.5 263.5 263.5 263.5 277.9 231.0 251.5 251.5 251.5 251.5 263.0 224.5  
75 252.1 232.3 277.9 172.8 306.9 112.3 240.7 226.2 265.2 166.9 293.3 106.7 228.7 219.9 251.7 160.6 278.6 100.7 216.3 213.3 237.8 154.1 263.2 94.5  
80 261.5 261.5 278.7 220.4 307.3 160.6 251.2 251.2 266.1 214.3 293.8 155.0 240.4 240.4 252.8 208.0 279.2 148.9 228.8 228.8 238.9 201.5 263.8 142.6  
85 277.0 277.0 281.4 268.6 307.7 208.4 266.4 266.4 269.2 262.5 294.2 202.3 255.1 255.1 254.9 254.9 279.7 196.0 243.1 243.1 243.0 243.0 264.4 189.6  
90 292.8 292.8 292.8 292.8 308.7 255.2 281.8 281.8 281.8 281.8 295.6 249.4 270.1 270.1 270.1 270.1 281.3 243.2 257.7 257.7 257.7 257.7 266.2 236.7  
4000*  
5200*  
6400  
7200  
8000  
8800  
9600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unit applications below 6400 CFM  
Electric heaters restricted on applications below 6400 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(20Ton)  
High Efficiency  
Table PD-14 — Gross Cooling Capacities (MBH) 20 Ton Three Phase T*D241C3, C4, CW— Dehumidification (Hot Gas Reheat)  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 197.5 138.9 222.3 116.0 249.8 89.2 188.8 133.4 213.0 110.6 239.6 83.8 179.7 127.6 203.1 105.0 228.8 78.3 170.1 121.7 192.6 99.2 217.3 72.5  
80 197.7 159.2 222.6 135.8 249.8 111.4 189.0 153.7 213.3 130.3 239.6 105.8 180.0 147.9 203.4 124.6 228.8 100.1 170.4 141.9 193.0 118.7 217.4 94.2  
85 198.2 179.3 222.9 156.3 250.0 132.0 189.7 173.8 213.5 150.7 239.8 126.4 180.8 168.1 203.7 145.0 229.0 120.7 171.4 162.2 193.3 139.1 217.7 114.8  
90 200.5 196.8 223.1 176.7 250.3 152.5 192.8 190.9 213.7 171.0 240.1 147.0 184.8 184.8 203.8 165.2 229.3 141.2 176.9 176.9 193.5 159.3 217.9 135.3  
75 213.1 158.3 239.0 127.6 267.2 94.6 203.5 152.5 228.5 121.8 255.7 88.9 193.2 146.3 217.5 115.8 243.7 83.1 182.7 140.0 206.0 109.6 231.1 77.1  
80 213.5 183.8 239.3 153.7 267.4 122.1 204.0 178.0 228.9 147.9 255.9 116.3 194.0 171.9 217.9 141.9 243.9 110.3 183.5 165.7 206.4 135.7 231.3 104.1  
85 215.3 209.9 239.7 179.7 267.7 148.3 204.6 204.6 229.1 173.7 256.2 142.4 197.0 194.2 218.1 167.6 244.2 136.4 187.4 187.4 206.7 161.4 231.6 130.3  
90 224.3 224.3 240.1 205.2 268.0 174.4 216.2 216.2 229.8 199.4 256.6 168.6 207.6 207.6 218.9 193.3 244.5 162.5 198.7 198.7 207.6 187.1 232.0 156.4  
75 223.7 175.3 250.2 138.3 279.0 98.8 213.5 169.3 239.0 132.3 266.6 93.0 202.6 163.0 227.2 126.1 253.7 87.0 191.3 156.4 214.9 119.7 240.2 80.8  
80 224.9 206.3 250.6 169.7 279.2 131.4 214.8 200.3 239.4 163.6 266.8 125.3 204.2 194.1 227.7 157.5 253.9 119.2 193.2 187.7 215.2 151.0 240.5 112.9  
85 230.5 230.5 251.0 200.6 279.6 162.9 221.7 221.7 239.8 194.5 267.2 156.9 212.5 212.5 228.1 188.2 254.3 150.7 202.8 202.8 215.9 181.8 240.9 144.4  
90 243.6 243.6 252.4 231.7 280.0 194.4 234.6 234.6 241.5 225.7 267.7 188.3 225.1 225.1 230.0 219.5 254.6 181.9 215.2 215.2 215.6 215.6 241.2 175.5  
75 229.2 185.9 255.7 150.2 284.8 101.3 218.6 179.7 244.1 144.1 272.0 95.4 207.4 173.3 231.9 138.0 258.6 89.4 195.8 166.7 219.1 131.7 244.7 83.2  
80 231.1 220.6 256.3 179.6 285.1 137.0 220.8 214.5 244.6 173.3 272.3 130.9 208.4 208.4 232.5 167.0 258.9 124.7 199.2 197.3 219.8 160.4 245.0 118.3  
85 240.3 240.3 256.9 213.7 285.5 172.0 231.1 231.1 245.4 207.5 272.7 165.9 221.4 221.4 233.3 201.2 259.4 159.7 211.2 211.2 220.8 194.7 245.5 153.3  
90 254.0 254.0 259.2 248.5 286.0 206.7 244.5 244.5 248.0 242.5 273.2 200.5 234.5 234.5 235.0 235.0 259.8 194.1 224.0 224.0 225.1 224.1 246.0 187.6  
75 233.9 196.0 260.5 150.9 289.7 103.6 223.0 189.8 248.6 144.8 276.5 97.7 211.5 183.3 236.1 138.4 262.7 91.4 199.6 176.7 223.0 131.9 248.4 85.0  
80 234.8 234.8 261.0 188.8 290.0 142.4 225.4 225.4 249.0 182.5 276.9 136.2 215.6 215.6 236.5 176.1 263.1 129.9 205.3 205.3 223.5 169.5 248.8 123.5  
85 249.0 249.0 262.0 226.4 290.5 180.8 239.3 239.3 250.1 220.2 277.4 174.6 229.2 229.2 237.8 213.8 263.6 168.3 218.6 218.6 225.1 207.3 249.2 161.7  
90 263.3 263.3 263.7 263.7 291.0 218.5 253.3 253.3 254.6 253.1 277.9 212.2 242.9 242.9 243.3 243.3 264.2 205.8 231.9 231.9 232.3 232.3 249.9 199.2  
75 237.9 205.8 264.5 156.8 293.8 105.7 226.7 199.5 252.2 150.6 280.3 99.6 215.1 193.0 239.4 144.2 266.1 93.2 202.9 186.3 226.0 137.6 251.5 86.6  
80 242.3 242.3 265.0 197.7 294.1 147.5 232.1 232.1 252.7 191.4 280.6 141.3 221.9 221.9 239.9 184.9 266.6 135.0 211.2 211.2 226.6 178.2 251.9 128.4  
85 256.5 256.5 266.4 238.7 294.7 189.2 246.5 246.5 254.3 232.4 281.0 182.8 235.9 235.9 241.8 226.0 267.0 176.3 224.9 224.9 228.9 219.4 252.4 169.7  
90 271.4 271.4 271.8 271.8 295.2 229.9 261.0 261.0 261.4 261.4 281.8 223.6 250.1 250.1 250.5 250.5 267.9 217.2 238.7 238.7 239.1 239.1 253.4 210.5  
75 241.4 215.2 267.8 162.4 297.1 107.4 230.0 208.9 255.3 156.2 283.4 101.2 218.2 202.3 242.2 149.7 269.0 94.8 205.9 195.6 228.4 143.0 254.0 88.2  
80 248.0 248.0 268.4 206.4 297.6 152.5 237.9 237.9 255.9 200.0 283.8 146.2 227.5 227.5 242.8 193.4 269.5 139.8 216.4 216.4 229.3 186.7 254.6 133.2  
85 263.1 263.1 270.3 250.7 298.0 197.1 252.8 252.8 258.1 244.3 284.3 190.7 241.9 241.9 245.5 237.9 270.0 184.1 230.5 230.5 230.7 230.7 255.1 177.4  
90 278.6 278.6 278.9 278.9 298.9 241.1 267.9 267.9 268.3 268.3 285.3 234.7 256.6 256.6 257.0 257.0 271.1 228.2 244.7 244.7 245.1 245.1 256.4 221.5  
4000*  
5200*  
6400  
7200  
8000  
8800  
9600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unit applications below 6400 CFM  
Electric heaters restricted on applications below 6400 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 6400 CFM.  
RT-PRC002-EN  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(25Ton)  
High Efficiency  
Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three Phase TC*301C3, C4, CW - Standard Refrigeration System  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
75  
80  
85  
90  
277 243 306 187 316 117 258 234 295 178 314 115 238 224 276 169 305 110 218 214 253 163 292 104  
284 284 307 225 321 169 269 269 295 225 317 161 252 252 277 217 307 158 235 235 254 207 293 151  
300 300 309 269 325 198 289 289 298 271 320 202 273 273 280 266 308 201 256 256 259 256 293 198  
312 312 313 312 329 236 305 305 305 305 321 240 293 293 293 293 310 245 277 277 277 277 295 244  
284 258 310 188 319 121 264 249 299 185 316 117 244 239 282 178 308 112 224 224 259 168 295 106  
294 294 310 233 323 175 280 280 300 236 319 170 263 263 283 230 309 163 245 245 260 221 296 158  
307 307 313 280 327 202 298 298 303 286 322 207 284 284 287 284 312 208 267 267 267 267 297 208  
318 318 318 318 331 241 312 312 312 312 324 248 301 301 301 301 314 255 287 287 287 287 299 257  
286 265 311 190 320 122 267 256 300 189 316 118 247 246 284 182 309 113 228 228 261 172 296 107  
297 297 312 237 324 178 285 285 302 241 320 174 267 267 285 237 310 165 249 249 262 227 298 162  
310 310 315 285 328 204 302 302 305 293 323 210 289 289 289 289 313 212 272 272 272 272 299 213  
320 320 320 320 332 244 314 314 314 314 325 251 305 305 305 305 316 260 292 292 292 292 301 264  
289 272 312 192 321 123 270 264 302 192 317 119 249 249 286 186 309 114 231 231 263 176 297 108  
300 300 313 240 324 181 289 289 304 246 321 177 272 272 287 243 311 170 253 253 265 234 299 165  
312 312 316 289 329 205 305 305 307 299 324 212 293 293 293 293 314 215 276 276 276 276 300 217  
322 322 321 321 332 246 317 317 317 317 326 255 308 308 308 308 317 265 295 295 295 295 303 270  
9000  
10000  
10500  
110 0 0  
Notes  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(25Ton)  
High Efficiency  
Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC*301C3, C4, CW— TXV Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 241.0 176.5 269.7 142.7 300.9 107.2 229.7 169.7 257.6 135.9 287.8 100.8 217.8 162.6 244.9 129.0 274.0 94.1 205.5 155.3 231.6 122.0 259.8 87.3  
80 241.4 204.6 269.9 170.5 300.9 135.9 230.2 197.7 257.8 163.8 287.8 129.3 218.4 190.5 245.1 156.8 274.1 122.5 206.2 183.2 231.9 149.6 259.8 115.6  
85 243.0 233.0 270.1 198.3 301.1 163.7 229.2 229.2 258.1 191.5 288.1 157.0 221.3 216.5 245.4 184.5 274.4 150.1 209.9 208.3 232.2 177.3 260.1 143.1  
90 251.2 251.2 270.6 226.1 301.4 191.2 241.6 241.6 258.6 219.2 288.3 184.4 231.6 231.6 246.0 212.1 274.6 177.5 221.2 221.2 233.0 204.8 260.4 170.4  
75 256.8 201.4 286.5 157.9 318.8 113.1 244.6 194.3 273.3 150.9 304.2 106.4 231.8 186.9 259.5 143.8 289.2 99.5 218.4 179.4 245.1 136.5 273.6 92.5  
80 258.2 237.2 286.8 193.2 318.9 149.3 246.1 230.1 273.6 186.2 304.4 142.3 233.6 222.8 259.8 179.0 289.4 135.3 220.7 215.4 245.4 171.6 273.9 128.1  
85 264.6 264.6 287.3 228.5 319.2 184.3 254.2 254.2 274.1 221.4 304.7 177.3 243.2 243.2 260.4 214.1 289.7 170.2 231.7 231.7 246.2 206.6 274.1 162.9  
90 279.1 279.1 288.7 263.8 319.5 219.2 268.4 268.4 275.8 256.7 305.0 212.1 257.3 257.3 262.4 249.5 290.0 205.0 245.6 245.6 245.5 245.5 274.5 197.7  
75 267.9 224.2 297.7 171.5 330.7 118.0 254.9 216.9 283.7 164.4 315.3 111.1 241.5 209.3 269.2 157.1 299.2 104.0 227.5 201.6 254.0 149.6 282.7 96.8  
80 268.8 268.8 298.0 214.0 330.9 161.1 259.3 255.4 284.1 206.8 315.5 154.0 246.8 246.7 269.6 199.5 299.5 146.7 234.0 234.0 254.5 191.9 283.0 139.4  
85 284.5 284.5 299.2 256.4 331.2 203.2 273.2 273.2 285.4 249.2 315.9 196.1 261.3 261.3 271.0 241.8 299.8 188.8 248.9 248.9 256.2 234.3 283.3 181.4  
90 300.3 300.3 300.2 300.2 331.6 245.2 288.7 288.7 290.5 286.0 316.4 238.0 276.5 276.5 276.4 276.4 300.4 230.6 263.8 263.8 263.7 263.7 284.0 223.1  
75 273.6 238.6 303.4 180.1 336.6 120.9 260.4 231.2 289.0 172.8 320.7 114.0 246.7 223.6 273.9 170.7 304.2 106.8 232.5 215.9 258.3 163.2 287.1 99.6  
80 279.6 279.5 303.8 227.0 336.8 168.4 267.3 267.3 289.5 219.8 321.0 161.3 255.2 255.2 274.6 212.4 304.5 154.0 242.6 242.6 259.1 204.8 287.5 146.5  
85 295.1 295.1 305.6 274.3 337.2 215.2 283.4 283.4 291.5 267.1 321.4 208.1 271.0 271.0 276.9 259.7 304.9 200.7 258.0 258.0 261.9 252.2 287.8 193.1  
90 311.9 311.9 311.8 311.8 338.0 261.8 299.6 299.6 299.6 299.6 322.2 254.5 286.9 286.9 286.8 286.8 305.9 247.1 273.5 273.5 273.5 273.5 288.9 239.4  
75 278.6 252.6 308.1 188.2 341.5 123.5 265.2 245.2 293.3 180.9 325.3 116.5 251.3 237.6 278.0 173.5 308.4 109.2 234.1 234.1 262.1 165.9 290.8 101.7  
80 287.6 287.6 308.7 239.7 341.8 175.5 275.5 275.5 294.0 232.5 325.6 168.3 263.1 263.1 278.8 225.0 308.7 160.9 250.0 250.0 263.1 217.3 291.2 153.4  
85 304.6 304.6 311.3 291.9 342.1 226.8 292.3 292.3 297.0 284.7 325.9 219.5 279.4 279.4 279.3 279.3 309.1 212.1 266.0 266.0 267.7 262.9 291.7 204.4  
90 322.2 322.2 322.1 322.1 343.3 277.9 309.3 309.3 309.3 309.3 327.2 270.5 295.9 295.9 295.9 295.9 310.6 263.1 282.0 282.0 282.0 282.0 293.3 255.3  
75 283.1 266.2 312.0 196.0 345.5 125.9 269.5 258.8 296.9 188.7 329.1 118.9 253.1 253.1 281.2 181.2 311.8 111.5 241.4 237.4 265.1 173.5 293.9 104.0  
80 295.1 295.1 312.9 252.1 345.8 182.3 282.8 282.8 297.9 244.7 329.4 175.0 269.9 269.9 282.4 237.2 312.2 167.7 256.4 256.4 266.5 229.4 294.3 160.1  
85 312.9 312.9 312.8 312.8 346.2 237.9 300.0 300.0 299.9 299.9 329.9 230.6 286.7 286.7 288.1 285.2 312.8 223.1 272.8 272.8 272.7 272.7 295.0 215.4  
90 331.2 331.2 331.1 331.1 347.8 293.5 317.8 317.8 317.8 317.8 331.6 286.2 304.0 304.0 303.8 303.8 314.7 278.6 289.3 289.3 289.3 289.3 297.3 271.0  
75 283.8 283.8 315.3 203.6 348.9 128.2 271.5 271.5 299.9 196.2 332.2 121.1 259.9 256.8 284.1 188.6 314.7 113.8 245.2 245.2 267.7 180.9 296.5 106.2  
80 301.8 301.8 316.6 264.1 349.2 188.9 289.0 289.0 301.2 256.6 332.6 181.7 275.9 275.9 285.7 249.1 315.2 174.3 262.0 262.0 269.5 241.3 297.0 166.6  
85 320.3 320.3 322.4 316.7 349.8 248.8 307.0 307.0 308.0 306.9 333.2 241.5 293.2 293.2 293.1 293.1 315.8 233.9 278.8 278.8 278.8 278.8 297.8 226.2  
90 339.1 339.1 339.0 339.0 351.7 308.8 325.4 325.4 325.3 325.3 335.6 301.5 310.9 310.9 310.9 310.9 318.5 294.0 295.9 295.9 295.9 295.9 301.0 286.4  
5000*  
6500*  
8000  
9000  
10000  
110 0 0  
12000  
Notes  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to  
appropriate airflow table notes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unit applications below 8000 CFM  
Electric heaters restricted on applications below 8000 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 8000 CFM.  
RT-PRC002-EN  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance (12½Ton)  
Data  
Standard Efficiency  
Table PD-17 — Evaporator Fan Performance — 12½Ton — TC*150D  
External Static Pressure (Inches of Water)  
.40 .50 .60  
.10  
.20  
.30  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
3 HP Standard Motor & Field  
SuppliedLowStaticDrive  
3HPStandardMotor&Sheaves  
4000  
4500  
5000  
5500  
6000  
547  
595  
643  
1.18  
1.55  
1.99  
581  
627  
673  
1.30  
1.68  
2.12  
565  
603  
643  
685  
727  
0.93  
1.21  
1.54  
1.94  
2.41  
599  
634  
672  
711  
752  
1.03  
1.31  
1.67  
2.08  
2.56  
632  
665  
700  
737  
777  
1.15  
1.43  
1.78  
2.21  
2.71  
663  
694  
727  
763  
801  
1.27  
1.56  
1.91  
2.34  
2.85  
695  
723  
755  
788  
825  
1.38  
1.69  
2.05  
2.47  
2.99  
727 1.48  
750 1.82  
781 2.19  
813 2.62  
848 3.13  
757 1.59  
778 1.94  
806 2.34  
837 2.77  
871 3.27  
571  
613  
656  
701  
1.10  
1.42  
1.81  
2.26  
Table PD-17 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM BHP  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
3HPStandardMotor&Sheaves  
3HPStandardMotor&HighStaticDriveAccessory  
4000  
4500  
5000  
5500  
6000  
786  
806  
830  
861  
894  
1.70  
2.06  
2.48  
2.93  
3.43  
813  
834  
856  
884  
916  
1.81  
2.19  
2.62  
3.10  
3.61  
841  
861  
882  
906  
938  
1.91  
2.31  
2.76  
3.25  
3.79  
867  
886  
907  
930  
959  
2.02  
2.43  
2.89  
3.41  
3.97  
893  
911  
931  
953  
980  
2.12  
2.56  
3.02  
3.56  
4.15  
919  
935  
955  
976  
1000  
2.22  
2.67  
3.16  
3.70  
4.31  
943  
960  
977  
999  
1019  
2.32  
2.79  
3.30  
3.86  
4.46  
966  
983  
1001  
1021  
1040  
2.41  
2.90  
989 2.50  
1011 2.60  
1005 3.02 1028 3.13  
3.44 1022 3.56 1045 3.70  
4.00 1043 4.15 1064 4.31  
4.62 1061 4.78 1082 4.95  
5HPOversizeMotor&Sheaves  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Notes:  
1. FieldSuppliedFanSheaveBK90Required. FieldSuppliedBelt maybenecessary.  
2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt  
maybenecessary.  
5HPOversizeMotor&FieldSuppliedDrive  
Factory supplied motors, in commercial equipment, are definite  
purpose motors, specifically designed and tested to operate  
reliably and continuously at all cataloged conditions. Using the  
full horsepower range of our fan motors as shown in our  
tabular data will not result in nuisance tripping or premature  
motor failure. Our product’s warranty will not be affected.  
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &  
Sheave/FanSpeedtablestodetermineoperatingrange.  
RT-PRC002-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance (15Ton)  
Data  
Standard Efficiency  
Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B  
External Static Pressure (Inches of Water)  
.40 .50 .60  
.10  
.20  
.30  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
3 HP Standard Motor & Field  
SuppliedLowStaticDrive(1)  
3HPStandardMotor&Sheaves  
4800  
5400  
6000  
6600  
7200  
563  
618  
673  
729  
786  
1.17  
1.60  
2.12  
2.76  
3.52  
596  
648  
701  
755  
810  
1.29  
1.72  
2.26  
2.91  
3.69  
626  
676  
727  
780  
834  
1.41  
1.86  
2.41  
3.07  
3.85  
656  
703  
752  
804  
856  
1.52  
1.99  
2.56  
3.23  
4.02  
685  
729  
777  
827  
878  
1.63  
2.12  
2.71  
3.39  
4.20  
714  
756  
801  
849  
899  
1.76  
2.25  
2.85  
3.56  
4.38  
742  
782  
825  
871  
919  
1.90  
2.38  
2.99  
3.72  
4.56  
768 2.04  
807 2.52  
848 3.13  
892 3.88  
939 4.74  
794 2.18  
832 2.68  
871 3.27  
914 4.03  
959 4.91  
585  
643  
701  
760  
1.47  
1.99  
2.61  
3.35  
(2)  
5HPOversizedMotor&Sheaves  
Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*180B — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
3HPStandardMotor&Sheaves  
3HPStandardMotor&HighStaticDriveAccessory  
4800  
5400  
6000  
6600  
7200  
819  
855  
894  
935  
979  
2.30  
2.84  
3.43  
4.18  
5.08  
844  
878  
916  
956  
999  
2.43  
3.00  
3.61  
4.34  
5.25  
871  
901  
938  
977  
1018  
2.57  
3.15  
3.79  
4.51  
5.41  
898  
923  
959  
997  
1038  
2.70  
3.29  
3.97  
4.70  
5.58  
923  
945  
2.83  
3.43  
4.15  
4.90  
5.77  
946  
969  
1000  
1037  
2.96  
3.58  
4.31  
5.10  
970  
993  
1019  
1056  
3.09  
3.73  
4.46 1040  
5.30 1075  
994  
3.23  
1018 3.39 1041 3.54  
1016  
3.88 1038 4.03 1060 4.17  
4.62 1061 4.78 1082 4.95  
5.49 1093 5.67  
980  
1018  
1057  
5HPOversizedMotor&Sheaves  
5HPOversizedMotor&FieldSuppliedDrive(3)  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
definite purpose motors, specifically designed and tested  
to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan  
motors as shown in our tabular data will not result in  
nuisance tripping or premature motor failure. Our  
product’s warranty will not be affected.  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Notes:  
1. FieldSuppliedFanSheaveBK105Required. FieldSuppliedBelt maybenecessary.  
2. 5 HP Oversized Motor with Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may  
benecessary.  
3. 5 HP Oversized Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt  
maybenecessary.  
4. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &  
Sheave/FanSpeedtablestodetermineoperatingrange.  
RT-PRC002-EN  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance (17½Ton)  
Data  
Standard Efficiency  
Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C  
External Static Pressure (Inches of Water)  
.40 .50 .60  
.10  
.20  
.30  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
5HPStandardMotorwithLowStaticDriveAccessory  
5600  
6300  
7000  
7700  
8400  
765  
845  
925  
1006  
788  
866  
944  
1024  
735  
810  
886  
963  
1041  
2.34  
3.23  
4.33  
5.66  
7.24  
759  
831  
2.46  
3.36  
4.48  
5.82  
7.42  
783  
852  
925  
2.60  
3.50  
4.62  
5.98  
7.60  
807  
874  
944  
2.74  
3.65  
4.77  
6.14  
7.78  
830  
895  
963  
2.89  
3.81  
4.93  
6.30 1050  
7.95 1122  
852  
917  
982  
3.03  
3.97  
5.10  
875 3.18  
937 4.13  
1002 5.29 1021 5.47  
898 3.33  
956 4.29  
2.96  
4.02  
5.32  
6.87  
3.10  
4.18  
5.49  
7.06  
906  
982  
1058  
999  
1075  
1016  
1091  
1033  
1107  
6.47 1069 6.66 1086 6.86  
8.13  
1138 8.31  
1154 8.50  
7.5HPOversizeMotor&Sheaves  
5HPStandardMotor&Sheaves  
Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM BHP  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
1.80  
RPM BHP  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
RPM  
BHP  
5HPStandardMotor&Sheaves  
5600  
6300  
7000  
7700  
8400  
923  
976  
1039  
1104  
3.50  
4.46  
5.65  
7.06  
946  
997  
1057  
1122  
3.68  
4.63  
5.82  
7.26  
968  
1019  
1074  
1138  
3.85  
4.82  
6.00  
7.46  
989  
1040  
1092  
1154  
4.03  
5.00  
6.19  
7.66  
1011  
1060  
1111  
1170  
4.21  
5.19  
6.39  
7.84  
1033  
1079  
1130  
1186  
4.39  
5.39  
6.59  
8.05  
1056  
1100  
1150  
1202  
4.58 1078  
4.77 1099 4.96  
1122 5.18  
1157 6.20  
1205 7.46  
5.60  
6.80  
1118  
1168  
5.79  
7.01  
8.47  
1138 6.00  
1186 7.22  
8.25 1220  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
7.5HPOversiveMotor&Sheaves  
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Notes:  
Factory supplied motors, in commercial equipment, are  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/  
Fan Speed” tables to determine operating range.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(20Ton)  
Standard Efficiency  
Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B  
External Static Pressure (Inches of Water)  
.40 .50 .60  
.10  
.20  
.30  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
5 HP Standard Motor & Field Supplied  
LowStaticDrive(1)  
5HPStandardMotor&Sheaves  
6400  
7200  
8000  
8800  
9600  
514  
562  
610  
659  
709  
1.69  
2.29  
3.03  
3.93  
4.99  
546  
592  
639  
687  
735  
1.88  
2.50  
3.26  
4.18  
5.27  
574  
619  
666  
712  
759  
2.05  
2.71  
3.50  
4.43  
5.54  
599  
644  
690  
736  
782  
2.21  
2.91  
3.73  
4.69  
5.82  
624  
667  
712  
758  
804  
2.37  
3.09  
3.96  
4.96  
6.11  
648  
689  
733  
778  
824  
2.54  
3.26  
4.16  
5.20  
6.39  
671  
711  
753  
797  
843  
2.71  
3.45  
4.35  
5.43  
6.67  
695 2.90  
732 3.64  
773 4.55  
816 5.65  
861 6.92  
720 3.11  
752 3.83  
792 4.75  
834 5.86  
878 7.16  
527  
578  
629  
681  
2.08  
2.79  
3.65  
4.67  
5HPStandardMotor&Sheaves  
(2)  
7.5HPOversizedMotor&Sheaves  
Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*240B — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
5HPStandardMotor&Sheaves  
5HPStandardMotor&HighStaticDriveAccessory  
6400  
7200  
8000  
8800  
9600  
744  
773  
811  
852  
895  
3.32  
4.04  
4.96  
6.08  
7.40  
768  
795  
830  
869  
911  
3.52  
4.27  
5.18  
6.30  
7.63  
790  
817  
848  
887  
928  
3.72  
4.50  
5.40  
6.53  
7.86  
811  
839  
867  
904  
944  
3.91  
4.74  
5.64  
6.77  
8.11  
833  
860  
887  
921  
960  
4.13  
4.96  
5.90  
7.01  
855  
880  
907  
938  
976  
4.36  
5.19  
6.16  
7.26  
8.61  
877  
898  
927  
955  
4.59  
5.41  
6.42  
7.52  
897  
917  
946  
973  
4.82  
5.64  
6.68  
7.81  
917 5.05  
937 5.88  
964 6.93  
991 8.09  
936 5.29  
957 6.14  
982 7.18  
8.36  
7.5HPOversizedMotor&Sheaves  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Notes:  
1. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBeltmaybenecessary.  
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required. Field Supplied Belt  
maybenecessary.  
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &  
Sheave/FanSpeedtablestodetermineoperatingrange.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(25Ton)  
Standard Efficiency  
Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B  
External Static Pressure (Inches of Water)  
.40 .50 .60  
.10  
.20  
.30  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
7.5HPStandardMotor&LowStaticDriveAccessory  
7.5HPStandardMotor&Sheaves  
7000  
7500  
8000  
8500  
9000  
9500  
10000  
10500  
11000  
593  
624  
655  
686  
717  
749  
781  
812  
844  
2.42  
2.88  
3.39  
3.97  
4.62  
5.34  
6.13  
7.00  
619  
649  
679  
710  
741  
772  
804  
835  
867  
2.62  
3.10  
3.63  
4.23  
4.89  
5.62  
6.42  
7.31  
8.3  
643  
673  
702  
732  
763  
794  
825  
856  
887  
2.80  
3.31  
3.86  
4.47  
5.15  
5.90  
6.72  
7.62  
667  
695  
724  
754  
784  
814  
844  
875  
2.98  
3.50  
4.07  
4.71  
5.41  
6.18  
7.01  
7.93  
690  
717  
745  
774  
803  
833  
863  
894  
3.16  
3.68  
4.28  
4.94  
5.66  
6.45  
7.31  
8.24  
712  
738  
766  
794  
822  
852  
881  
911  
3.35  
3.88  
4.48  
5.15  
5.89  
6.71  
7.59  
8.54  
733 3.53  
759 4.08  
786 4.68  
813 5.36  
841 6.12  
870 6.95  
899 7.86  
754 3.73  
779 4.28  
805 4.90  
832 5.58  
859 6.35  
887 7.19  
916 8.11  
595  
627  
659  
691  
723  
755  
788  
821  
2.66  
3.16  
3.73  
4.36  
5.06  
5.84  
6.69  
7.63  
595  
628  
661  
695  
729  
762  
796  
2.92  
3.47  
4.08  
4.76  
5.52  
6.35  
7.27  
7.96  
8.60  
7.5HPStandardMotor&HighStaticDriveAccessory  
7.5HPStandardMotor&Sheaves  
Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued  
External Static Pressure (Inches of Water)  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.40  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
7.5HPStandardMotor&Sheaves  
7000  
7500  
8000  
8500  
9000  
9500  
10000  
10500  
11000  
776  
798  
824  
850  
877  
904  
933  
3.95  
4.48  
5.11  
5.81  
6.58  
7.43  
8.36  
798  
818  
842  
868  
894  
921  
949  
4.18  
4.71  
5.32  
6.03  
6.81  
7.67  
8.62  
820  
839  
860  
885  
911  
938  
4.40  
4.95  
5.55  
6.26  
7.05  
7.92  
841  
860  
880  
902  
928  
954  
4.62  
5.19  
5.80  
6.49  
7.29  
8.17  
862  
880  
899  
920  
944  
970  
4.84  
5.42  
6.06  
6.74  
7.53  
8.42  
7.5HPStandardMotor&HighStaticDriveAccessory  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
definite purpose motors, specifically designed and tested  
to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan  
motors as shown in our tabular data will not result in  
nuisance tripping or premature motor failure. Our  
product’s warranty will not be affected.  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop  
data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Note:  
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan  
Speed” tables to determine operating range.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½Ton)  
High Efficiency  
Table PD-22 — Evaporator Fan Performance — 12½Ton — TCD151C — Standard or TXV Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3 HP Standard Motor & Field  
SuppliedLowStaticDrive(2)  
3 HP Standard Motor & Field  
SuppliedHighStaticDrive(2)  
3 HP Standard Motor & Drive  
2500*  
3250*  
4000  
4500  
5000  
5500  
6000  
402  
447  
495  
528  
562  
597  
633  
0.30  
0.49  
0.74  
0.95  
1.20  
1.49  
1.82  
460  
503  
549  
580  
612  
645  
680  
0.39  
0.62  
0.91  
1.14  
1.42  
1.74  
2.10  
510  
552  
596  
627  
657  
689  
722  
0.48  
0.74  
1.07  
1.33  
1.63  
1.98  
2.37  
555  
595  
638  
668  
699  
729  
761  
0.56  
0.86  
1.22  
1.51  
1.84  
2.20  
2.63  
595  
634  
677  
706  
736  
767  
797  
0.64  
0.97  
1.37  
1.68  
2.04  
2.44  
2.87  
633  
672  
712  
742  
771  
801  
832  
0.74  
1.08  
1.52  
1.85  
2.23  
2.66  
3.13  
667  
706  
747  
776  
803  
833  
864  
0.83  
1.19  
1.66  
2.02  
2.41  
2.87  
3.38  
699 0.92  
739 1.30  
778 1.80  
806 2.18  
835 2.61  
864 3.07  
894 3.61  
731 1.02  
769 1.40  
809 1.94  
836 2.34  
865 2.80  
893 3.28  
922 3.83  
378  
430  
466  
503  
540  
579  
0.35  
0.56  
0.74  
0.96  
1.22  
1.53  
5HPOversizeMotor&Drive  
3HPStandardMotor&HighStaticDriveAccessory  
Table PD-22 — Evaporator Fan Performance — 12½ Ton — TCD151C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
RPM  
BHP  
BHP  
BHP  
BHP  
3HPStandardMotor&Drive  
3HPStandardMotor&HighStaticDriveAccessory  
2500*  
3250*  
4000*  
4500  
5000  
5500  
760  
798  
839  
865  
892  
922  
950  
1.11  
1.52  
2.07  
2.50  
2.97  
3.49  
4.05  
789  
827  
867  
892  
920  
949  
977  
1.21  
1.64  
2.21  
2.66  
3.15  
3.70  
4.29  
817  
853  
893  
919  
946  
975  
1.31  
1.76  
2.33  
2.81  
3.33  
3.90  
4.51  
842  
880  
919  
945  
971  
999  
1028  
1.41  
1.88  
2.47  
2.96  
3.50  
4.09  
4.74  
868  
905  
943  
970  
996  
1023  
1052  
1.51  
2.01  
2.59  
3.11  
3.68  
4.28  
4.96  
892  
928  
967  
1.60  
2.13  
2.73  
3.25  
3.85  
4.48  
5.16  
916  
953  
991  
1017  
1043  
1070  
1098  
1.71  
2.26  
2.88  
3.40 1039  
4.02 1066  
4.68 1091  
939  
976  
1013  
1.81  
2.38  
962 1.91  
998 2.51 1020 2.63  
984 2.01  
3.03 1036 3.18 1056.4 3.33  
3.55 1061 3.70 1082.3 3.85  
4.18 1088 4.35 1109.6 4.50  
4.87  
5.59  
994  
1020  
1047  
1074  
1114 5.06 1135.6 5.24  
6000  
1002  
5.38  
1120  
5HPOversizedMotor&Drive  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
*Unit applications below 4000 CFM  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
Electric heaters restricted on applications below 4000 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
are required on applications below 4000 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Note:  
1. FieldSuppliedFanSheaveBK115Required. FieldSuppliedBeltmaybenecessary.  
RT-PRC002-EN  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½Ton)  
High Efficiency  
Table PD-23 — Evaporator Fan Performance — 12½Ton — T*D151C — Dehumidification (Hot Gas Reheat) Option  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3HPStandardMotor&Drivew/Field  
SuppliedLowStaticDriveFanSheave  
3HPStandardMotor&Drive  
2500*  
3000*  
3500*  
4000  
4500  
5000  
5500  
6000  
526  
578  
633  
692  
753  
816  
881  
947  
0.52  
0.74  
1.03  
1.40  
1.87  
2.44  
3.13  
3.93  
570  
618  
670  
727  
785  
846  
908  
972  
0.62  
0.86  
1.16  
1.55  
2.03  
2.61  
3.32  
4.15  
609  
656  
706  
759  
815  
874  
935  
996  
0.73  
0.98  
1.30  
1.71  
2.20  
2.79  
3.51  
4.36  
646  
692  
739  
791  
844  
902  
960  
1021  
0.83  
1.11  
1.44  
1.86  
2.37  
2.98  
3.70  
4.56  
681  
725  
771  
821  
873  
928  
985  
1044  
0.93  
1.23  
1.58  
2.01  
2.54  
3.17  
3.91  
713  
756  
802  
850  
901  
954  
1010  
1.03  
1.35  
1.73  
2.17  
2.71  
3.37  
744 1.14  
786 1.48  
831 1.88  
878 2.34  
928 2.89  
979 3.56  
776 1.25  
814 1.60  
859 2.02  
905 2.50  
953 3.07  
1004 3.75  
534  
594  
656  
720  
786  
853  
921  
0.63  
0.90  
1.26  
1.71  
2.26  
2.91  
3.70  
551  
618  
686  
755  
824  
894  
0.78  
1.11  
1.54  
2.07  
2.71  
3.47  
4.13 1033 4.34 1056 4.54  
5.01 1090 5.24  
4.78 1068  
1112 5.47  
5HPOversizedMotor&Drive  
3HPStandardMotor&HighStaticDriveAccessory  
Table PD-23 — Evaporator Fan Performance — 12½ Ton — T*D151C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM BHP  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM BHP  
1.80  
RPM BHP  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
3HPStandardMotor&HighStaticDriveAccessory  
3HPStandardMotor  
&Drive  
804  
842  
885  
930  
2500*  
3000*  
3500*  
4000  
4500  
5000  
5500  
6000  
1.36  
1.73  
2.17  
2.67  
3.25  
3.94  
4.76  
5.70  
832  
869  
1.48  
1.85  
2.31  
2.85  
3.44  
4.14  
4.97  
859  
895  
1.59  
1.98  
2.45  
3.01  
3.63  
4.35  
5.17  
883  
920  
1.71  
2.11  
2.59  
3.17  
3.83  
4.55  
5.40  
908  
945  
983  
1.83  
2.24  
2.74  
3.34  
4.02  
4.76  
5.62  
931  
968  
1006  
1047  
1093  
1140  
1.95  
2.38  
2.89  
3.50  
4.21  
4.98  
954  
991  
1029  
1069  
1113  
1159  
2.08  
2.51  
3.04 1051  
3.66 1090  
4.38  
5.18  
977  
1014  
2.21  
998 2.33  
1020 2.47  
2.65 1035 2.79 1057 2.94  
910  
935  
959  
3.19  
3.82  
4.57  
5.40  
1072 3.34 1093 3.49  
956  
980  
1003  
1049  
1096  
1146  
1026  
1071  
1118  
1166  
1110 3.99  
1154 4.75  
1200 5.61  
1132 4.16  
1174 4.94  
978  
1002  
1051  
1102  
1026  
1074  
1123  
1134  
1180  
1028  
1079  
1133  
5HPOversizedMotor&Drivew/FieldSuppliedFanSheave  
5HPOversizedMotor&Drive  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Table includes Dehumidification (Hot Gas Reheat Option).  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
*Unit applications below 4000 CFM  
Electric heaters restricted on applications below 4000 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
are required on applications below 4000 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Note:  
1. FieldSuppliedFanSheaveBK115Required. FieldSuppliedBeltmaybenecessary.  
RT-PRC002-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½Ton)  
High Efficiency  
Table PD-24 — Evaporator Fan Performance — 12½Ton — TCH151C — Standard Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
3HPStandardMotor&Drive  
4000  
4500  
5000  
5500  
6000  
534  
581  
628  
1.40  
1.83  
2.34  
510  
551  
593  
637  
682  
0.98  
1.29  
1.67  
2.13  
2.68  
541  
579  
620  
661  
704  
1.10  
1.42  
1.81  
2.28  
2.83  
572  
607  
645  
685  
727  
1.22  
1.56  
1.95  
2.43  
3.00  
602  
635  
671  
709  
749  
1.35  
1.68  
2.11  
2.59  
3.16  
631  
662  
696  
732  
770  
1.48  
1.82  
2.25  
2.76  
3.33  
659  
688  
720  
754  
791  
1.62  
1.98  
2.40  
2.92  
3.52  
687 1.76  
713 2.13  
744 2.56  
777 3.08  
812 3.70  
714 1.91  
738 2.28  
767 2.73  
799 3.25  
833 3.87  
521  
566  
611  
657  
1.17  
1.54  
1.99  
2.51  
5HPOversizedMotor&Drive  
Table PD-24 — Evaporator Fan Performance — 12½ Ton — TCH151C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
3HPStandardMotor&Drive  
3HPStandardMotor&HighStatic  
DriveAccessory  
4000  
4500  
5000  
5500  
6000  
740  
763  
790  
820  
853  
2.07  
2.44  
2.90  
3.43  
4.04  
766  
787  
812  
842  
874  
2.23  
2.61  
3.07  
3.61  
4.23  
791  
811  
835  
862  
893  
2.38  
2.78  
3.24  
3.80  
4.43  
814  
835  
857  
883  
913  
2.54  
2.96  
3.42  
3.98  
4.63  
838  
858  
879  
904  
932  
2.70  
3.13  
3.61  
4.17  
4.83  
860  
880  
901  
924  
951  
2.86  
3.31  
3.81  
4.37  
5.03  
883  
901  
922  
944  
970  
3.02  
3.48  
4.00  
4.57  
5.24  
905  
922  
942  
964  
988  
3.19  
3.66  
4.20  
4.78  
5.45  
926 3.37  
943 3.84  
962 4.39  
984 4.99  
1007 5.66  
948 3.55  
963 4.02  
982 4.59  
1003 5.20  
5HPOversizedMotor&Drive  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop  
due to other options/accessories.  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
Note:  
1. FieldSuppliedFanSheaveBK115Required. FieldSuppliedBeltmaybenecessary.  
RT-PRC002-EN  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15Ton)  
High Efficiency  
Performance  
Data  
Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Standard or TXV Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3 HP Standard Motor &  
FieldSuppliedExtra  
LowStaticDrive(2)  
3 HP Standard Motor & Field  
SuppliedLowStaticDrive(1)  
3000*  
3900*  
4800  
5400  
6000  
6600  
7200  
337  
384  
437  
474  
513  
552  
591  
0.32  
0.55  
0.89  
1.19  
1.55  
1.98  
2.49  
387  
423  
471  
506  
543  
580  
618  
0.42  
0.66  
1.01  
1.33  
1.72  
2.17  
2.70  
432  
462  
503  
536  
571  
606  
643  
0.53  
0.78  
1.14  
1.47  
1.87  
2.35  
2.91  
472  
500  
535  
564  
597  
632  
667  
0.65  
0.91  
1.29  
1.62  
2.03  
2.52  
3.09  
511  
536  
566  
592  
623  
656  
690  
0.77  
1.05  
1.44  
1.78  
2.19  
2.69  
3.27  
547  
569  
598  
621  
648  
679  
712  
0.90  
1.19  
1.60  
1.95  
2.36  
2.87  
3.46  
580  
600  
629  
648  
673  
702  
734  
1.03  
1.35  
1.77  
2.12  
2.55  
3.05  
3.65  
611 1.16  
630 1.51  
658 1.94  
676 2.30  
699 2.74  
725 3.25  
755 3.85  
640 1.29  
660 1.67  
684 2.11  
704 2.49  
723 2.93  
748 3.46  
776 4.06  
341  
399  
445  
479  
519  
560  
0.45  
0.76  
1.04  
1.38  
1.79  
2.28  
3HPStandardMotor&Drive  
5HPOversizedMotor&Drive  
Table PD-25 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM BHP  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
RPM  
BHP  
3HPStandardMotor&Drive  
3 HP Standard Motor & High  
StaticDriveAccessory  
3000*  
3900*  
4800  
5400  
6000  
6600  
7200  
667  
688  
710  
730  
749  
771  
797  
1.43  
1.84  
2.29  
2.68  
3.13  
3.67  
4.29  
693  
715  
735  
755  
774  
794  
818  
1.57  
2.00  
2.48  
2.88  
3.34  
3.88  
4.51  
717  
741  
760  
778  
798  
816  
839  
1.71  
2.17  
2.68  
3.07  
3.56  
4.09  
4.74  
740  
766  
785  
800  
821  
839  
860  
1.86  
2.34  
2.88  
3.28  
3.77  
4.32  
4.96  
763  
790  
809  
823  
842  
862  
881  
2.01  
2.51  
3.09  
3.49  
3.99  
4.56  
5.20  
784  
812  
832  
845  
863  
884  
902  
2.16  
2.68  
3.29  
3.71  
4.20  
4.80  
5.45  
805  
834  
854  
867  
884  
904  
923  
2.31  
2.85  
3.49  
3.94  
4.43  
5.03  
5.70  
825  
855  
876  
889  
904  
924  
2.47  
3.03  
3.69  
4.17  
4.66  
5.27  
845 2.63  
875 3.21  
898 3.90  
910 4.40  
924 4.90  
943 5.51  
864 2.80  
895 3.39  
919 4.10  
931 4.62  
944 5.15  
961 5.75  
5HPOversizedMotor&Drive  
Factory supplied motors, in commercial equipment, are  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
*Unit applications below 4000 CFM  
Electric heaters restricted on applications below 4000 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase  
Heaters  
are required on applications below 4000 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/ccessories.  
Note:  
1. FieldSuppliedFanSheaveBK120Required. FieldSuppliedBelt maybenecessary.Field  
SuppliedBeltmaybenecessary.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(15Ton)  
High Efficiency  
Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Dehumidification (Hot Gas Reheat) Option  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
3HPStandardMotorw/Field 3HPStandardMotorw/Field  
SuppliedMotorSheave(2) SuppliedMotorSheave(1)  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3HPStandardMotorw/FieldSupplied  
LowStaticDriveFanSheave  
3000*  
3600*  
4200*  
4800  
5400  
6000  
6600  
7200  
295  
333  
373  
414  
455  
497  
540  
583  
0.26  
0.40  
0.60  
0.84  
1.14  
1.51  
1.96  
2.50  
346  
379  
415  
452  
491  
531  
572  
613  
0.35  
0.51  
0.72  
0.99  
1.32  
1.73  
2.20  
2.75  
391  
420  
452  
487  
524  
561  
601  
641  
0.45  
0.62  
0.85  
1.13  
1.48  
1.91  
2.42  
3.02  
432  
458  
487  
519  
554  
590  
628  
666  
0.56  
0.74  
0.98  
1.27  
1.64  
2.08  
2.61  
3.23  
471  
494  
520  
550  
582  
617  
653  
690  
0.68  
0.87  
1.12  
1.43  
1.80  
2.26  
2.80  
3.44  
506  
527  
551  
579  
610  
643  
678  
714  
0.80  
1.00  
1.26  
1.59  
1.98  
2.44  
2.99  
3.65  
539  
559  
581  
607  
637  
667  
701  
736  
0.92  
1.14  
1.41  
1.74  
2.15  
2.63  
3.20  
3.86  
569  
589  
610  
635  
662  
692  
724  
758  
1.04  
1.28  
1.57  
1.91  
2.33  
2.83  
3.41  
4.08  
596 1.17  
617 1.43  
638 1.73  
660 2.08  
687 2.51  
715 3.02  
746 3.61  
778 4.30  
622 1.30  
644 1.57  
664 1.89  
686 2.26  
710 2.70  
739 3.22  
768 3.83  
799 4.53  
3HPStandardMotor&Drive  
5HPOversizedMotor&Drive  
Table PD-26 — Evaporator Fan Performance — 15 Ton — T*D181C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
3HPStandardMotor&Drive  
3 HP Standard Motor &  
HighStaticDriveAccessory  
3000*  
3600*  
4200*  
4800  
5400  
6000  
6600  
7200  
646  
669  
690  
711  
734  
761  
789  
819  
1.43  
1.72  
2.06  
2.44  
2.89  
3.42  
4.05  
4.76  
669  
694  
715  
735  
758  
782  
810  
840  
1.56  
1.88  
2.23  
2.63  
3.09  
3.63  
4.26  
5.00  
692  
716  
737  
758  
780  
804  
831  
859  
1.70  
2.02  
2.39  
2.81  
3.29  
3.84  
4.49  
5.23  
714  
738  
760  
780  
801  
824  
850  
879  
1.84  
2.18  
2.57  
3.00  
3.49  
4.05  
4.71  
5.47  
734  
759  
782  
802  
822  
845  
870  
898  
1.98  
2.34  
2.74  
3.19  
3.69  
4.27  
4.94  
5.72  
755  
778  
803  
823  
844  
865  
889  
2.13  
2.49  
2.92  
3.38  
3.91  
4.49  
5.18  
775  
798  
822  
843  
864  
885  
908  
2.28  
2.66  
3.09  
3.58  
4.12  
4.72  
5.41  
793  
817  
842  
864  
883  
904  
927  
2.42  
2.82  
3.28  
3.78  
4.33  
4.95  
5.65  
813 2.58  
835 2.98  
861 3.46  
882 3.97  
903 4.55  
923 5.18  
830 2.72  
854 3.16  
878 3.64  
901 4.17  
921 4.76  
941 5.41  
5HPOversizedMotor&Drive  
3HPStandardMotor&HighStaticDriveAccessory  
Factory supplied motors, in commercial equipment, are  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Table includes Dehumidification (Hot Gas Reheat Option).  
*Unit applications below 4800 CFM  
Electric heaters restricted on applications below 4800 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
are required on applications below 4800 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options accessories.  
Note:  
1. FieldSuppliedFanSheaveBK120Required. FieldSuppliedBelt maybenecessary.Field  
SuppliedBeltmaybenecessary.  
2. FieldSuppliedFanSheaveBK160Required. FieldSuppliedBelt maybenecessary.Field  
SuppliedBeltmaybenecessary.  
RT-PRC002-EN  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(17½Ton)  
High Efficiency  
Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
5 HP Standard Motor &  
FieldSuppliedLowStaticDrive(1)  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
5 HP Standard Motor  
&FieldSuppliedExtra  
LowStaticDrive(2)  
448  
490  
547  
588  
631  
675  
720  
3500*  
4550*  
5600  
6300  
7000  
7700  
8400  
452  
499  
546  
594  
642  
1.14  
1.63  
2.11  
2.75  
3.52  
487  
532  
578  
625  
671  
1.30  
1.76  
2.31  
2.98  
3.78  
0.66  
1.03  
1.60  
2.10  
2.71  
3.43  
4.27  
488  
524  
575  
614  
655  
698  
741  
0.78  
1.17  
1.75  
2.26  
2.89  
3.64  
4.51  
523  
557  
602  
639  
678  
720  
762  
0.91  
1.32  
1.91  
2.43  
3.07  
3.84  
4.73  
557  
590  
629  
663  
701  
741  
782  
1.05  
1.48  
2.08  
2.60  
3.25  
4.03  
4.95  
590  
621  
656  
687  
723  
761  
802  
1.20  
1.64  
2.26  
2.79  
3.44  
4.23  
5.16  
622 1.35  
649 1.80  
683 2.43  
711 2.99  
744 3.64  
782 4.44  
821 5.38  
652 1.50  
676 1.97  
710 2.63  
735 3.19  
766 3.85  
801 4.65  
840 5.60  
457  
518  
561  
606  
651  
697  
0.90  
1.45  
1.94  
2.52  
3.21  
4.03  
5 HP Standard Motor &  
HighStaticDriveAccessory  
Table PD-27— Evaporator Fan Performance — 17½ Ton — TC*211C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
1.80  
RPM BHP  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
RPM  
BHP  
5HPStandardMotor&Drive  
5 HP Standard Motor & High  
StaticDriveAccessory  
3500*  
4550*  
5600  
6300  
7000  
7700  
8400  
680  
703  
736  
759  
788  
821  
858  
1.65  
2.15  
2.83  
3.38  
4.07  
4.87  
5.82  
707  
729  
761  
783  
810  
841  
876  
1.80  
2.34  
3.03  
3.59  
4.29  
5.10  
6.06  
732  
754  
785  
807  
831  
861  
894  
1.95  
2.54  
3.23  
3.82  
4.51  
5.34  
6.30  
756  
779  
807  
830  
852  
881  
912  
2.11  
2.73  
3.43  
4.04  
4.74  
5.59  
6.55  
779  
803  
829  
853  
874  
900  
930  
2.27  
2.92  
3.64  
4.27  
4.97  
5.83  
6.81  
801  
827  
851  
874  
895  
919  
949  
2.43  
3.11  
3.86  
4.49  
5.22  
6.07  
7.08  
822  
849  
872  
894  
917  
939  
967  
2.60  
3.31  
4.09  
4.72  
5.47  
6.32  
7.34  
843  
871  
893  
913  
937  
958  
984  
2.77  
3.50  
4.32  
4.95  
5.72  
6.58  
7.60  
863 2.94  
892 3.70  
914 4.56  
933 5.19  
957 5.97  
978 6.85  
1002 7.87  
882 3.11  
913 3.89  
935 4.80  
952 5.43  
975 6.22  
997 7.12  
7.5OversizeMotor&Drive  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
*Unit applications below 5600 CFM  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
Electric heaters restricted on applications below 5600 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
are required on applications below 5600 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Note:  
1. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBelt maybenecessary.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(20Ton)  
High Efficiency  
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Standard or TXV Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
5 HP Standard Motor & Field Supplied  
ExtraLowStaticDrive(3)  
5 HP Standard Motor & Field  
SuppliedLowStaticDrive(1)  
4000*  
5200*  
6400  
7200  
8000  
8800  
9600  
428  
494  
570  
620  
672  
724  
776  
0.69  
1.22  
2.03  
2.72  
3.56  
4.55  
5.74  
467  
524  
595  
646  
696  
747  
799  
0.82  
1.35  
2.19  
2.92  
3.80  
4.83  
6.04  
504  
555  
620  
668  
719  
769  
820  
0.95  
1.51  
2.34  
3.10  
4.02  
5.10  
6.34  
538  
585  
644  
690  
739  
790  
840  
1.08  
1.67  
2.51  
3.27  
4.22  
5.34  
6.63  
572  
614  
669  
711  
759  
808  
859  
1.23  
1.83  
2.69  
3.45  
4.41  
5.56  
6.90  
603  
642  
693  
733  
778  
826  
876  
1.38  
2.00  
2.89  
3.65  
4.60  
5.77  
7.14  
632 1.55  
670 2.17  
717 3.09  
755 3.86  
797 4.81  
844 5.98  
893 7.37  
660 1.71  
696 2.35  
741 3.29  
777 4.08  
817 5.03  
861 6.20  
909 7.59  
426  
506  
560  
616  
671  
728  
0.94  
1.64  
2.28  
3.07  
4.04  
5.19  
463  
540  
592  
645  
698  
753  
1.09  
1.84  
2.50  
3.31  
4.29  
5.46  
5HPStandardMotor&Drive  
(2)  
7.5HPOversizedMotor&Drive  
Table PD-28 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
5HPStandardMotor&Drive  
5 HP Standard Motor  
&HighStaticDriveAccessory  
4000*  
5200*  
6400  
7200  
8000  
8800  
9600  
688  
722  
765  
799  
837  
879  
925  
1.87  
2.54  
3.49  
4.31  
5.26  
6.43  
7.83  
714  
747  
788  
820  
857  
897  
941  
2.03  
2.73  
3.70  
4.53  
5.51  
6.67  
8.07  
739  
771  
810  
841  
876  
915  
958  
2.20  
2.93  
3.91  
4.76  
5.76  
6.93  
8.32  
764  
795  
832  
862  
896  
933  
974  
2.36  
3.14  
4.12  
4.99  
6.01  
7.19  
787  
817  
854  
883  
915  
951  
2.53  
3.35  
4.34  
5.22  
6.26  
7.46  
810  
839  
875  
902  
934  
969  
2.70  
3.56  
4.57  
5.46  
6.52  
7.74  
831  
861  
896  
922  
953  
986  
2.87  
3.77  
4.80  
5.69  
6.77  
8.01  
852  
882  
916  
942  
971  
3.05  
3.98  
5.04  
5.94  
7.03  
873 3.23  
902 4.19  
936 5.29  
961 6.19  
989 7.29  
892 3.41  
923 4.41  
955 5.54  
980 6.44  
8.58  
7.5HPOversizedMotor&Drive  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
Factory supplied motors, in commercial equipment, are  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
*Unit applications below 6400 CFM  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
Electric heaters restricted on applications below 6400 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
are required on applications below 6400 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Notes:  
1. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBelt maybenecessary.  
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt  
maybenecessary.  
3. FieldSuppliedFanSheaveB5V200andMotorSheaveIVP34required.FieldSuppliedBeltmay  
benecessary.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(20Ton)  
High Efficiency  
Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Dehumidification (Hot Gas Reheat) Option  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
5 HP Standard Motor & Field  
SuppliedFanSheave(1)  
5 HP Standard Motor & Drive & Field Supplied  
LowStaticFanSheave  
5HPStandard  
Motor&Drive  
4000*  
4800*  
5600*  
6400  
7200  
8000  
8800  
9600  
441  
487  
536  
588  
641  
695  
750  
805  
0.77  
1.13  
1.61  
2.24  
3.02  
3.93  
5.03  
6.32  
477  
519  
566  
615  
666  
719  
773  
827  
0.90  
1.27  
1.78  
2.42  
3.23  
4.21  
5.35  
6.68  
511  
550  
594  
641  
690  
742  
794  
848  
1.03  
1.43  
1.95  
2.61  
3.44  
4.45  
5.65  
7.04  
543  
579  
620  
666  
714  
763  
815  
867  
1.17  
1.59  
2.12  
2.80  
3.65  
4.67  
5.91  
7.35  
573  
607  
647  
689  
736  
785  
835  
886  
1.32  
1.74  
2.30  
3.00  
3.86  
4.91  
6.15  
7.63  
603  
635  
672  
713  
758  
805  
854  
904  
1.47  
1.91  
2.49  
3.20  
4.08  
5.14  
6.41  
7.90  
631 1.63  
658 1.78  
686 2.26  
720 2.87  
758 3.62  
799 4.53  
844 5.62  
892 6.93  
941 8.46  
414  
469  
525  
583  
641  
699  
758  
0.84  
1.25  
1.80  
2.50  
3.37  
4.42  
5.67  
452  
504  
558  
613  
669  
725  
782  
0.99  
1.45  
2.03  
2.75  
3.64  
4.72  
6.00  
660 2.08  
696 2.67  
736 3.41  
778 4.30  
825 5.38  
873 6.66  
923 8.18  
7.5HPOversizedMotor&Drive  
(3)  
5HPStandardMotor&HighStaticDrive  
Table PD-29 — Evaporator Fan Performance — 20 Ton — T*D241C — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
RPM RPM RPM  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
5HPStandardMotor&Drive  
5 HP Standard Motor  
&HighStaticDrive  
4000*  
4800*  
5600*  
6400  
7200  
8000  
8800  
9600  
684  
711  
743  
779  
819  
863  
909  
1.94  
2.44  
3.06  
3.82  
4.76  
5.87  
7.19  
708  
735  
765  
800  
840  
881  
927  
2.10  
2.63  
3.26  
4.04  
5.00  
6.12  
7.46  
731  
758  
787  
821  
859  
900  
944  
2.27  
2.81  
3.46  
4.26  
5.23  
6.38  
7.73  
753  
780  
809  
841  
879  
918  
961  
2.43  
3.00  
3.67  
4.48  
5.47  
6.64  
8.01  
775  
802  
830  
861  
898  
936  
978  
2.60  
3.19  
3.88  
4.70  
5.72  
6.90  
8.29  
795  
823  
850  
881  
916  
954  
994  
2.77  
3.38  
4.09  
4.93  
5.96  
7.16  
8.56  
814  
843  
871  
899  
933  
971  
2.94  
3.58  
4.31  
5.16  
6.19  
7.42  
834  
864  
890  
919  
952  
988  
3.12  
3.78  
4.53  
5.41  
6.46  
7.69  
852 3.29  
882 3.97  
910 4.75  
938 5.66  
968 6.70  
870 3.47  
901 4.17  
929 4.98  
956 5.90  
987 6.97  
7.5HPOversizedMotor&Drive  
Factory supplied motors, in commercial equipment, are  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions.  
Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or  
premature motor failure. Our product’s warranty will not be  
affected.  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.  
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.  
Table includes Dehumidification (Hot Gas Reheat Option).  
*Unit applications below 6400 CFM  
Electric heaters restricted on applications below 6400 CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
are required on applications below 6400 CFM.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.  
Notes:  
1. FieldSuppliedMotorSheaveIVP34Required. FieldSuppliedBelt maybenecessary.  
2. FieldSuppliedFanSheaveBK190Required. FieldSuppliedBelt maybenecessary.  
3. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt  
maybenecessary.  
RT-PRC002-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(25Ton)  
High Efficiency  
Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Standard Refrigeraton System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
7.5HPStandardMotor&FieldSuppliedExtraLowStaticDrive(1)  
7.5HPStandardMotor&LowStaticDriveAccessory  
5000*  
6500*  
7000*  
7500*  
8000  
8500  
9000  
576  
649  
678  
708  
739  
771  
802  
834  
866  
898  
1.56  
2.59  
3.06  
3.61  
4.22  
4.90  
5.65  
6.46  
7.35  
8.31  
606  
674  
700  
729  
759  
790  
821  
853  
884  
916  
1.71  
2.78  
3.25  
3.79  
4.41  
5.10  
5.88  
6.72  
7.64  
8.62  
635  
698  
723  
749  
778  
808  
839  
870  
902  
1.88  
2.97  
3.44  
3.98  
4.60  
5.31  
6.09  
6.96  
7.90  
663 2.05  
722 3.18  
745 3.65  
770 4.19  
797 4.81  
826 5.52  
856 6.30  
887 7.18  
918 8.14  
690 2.22  
746 3.38  
768 3.87  
792 4.41  
817 5.03  
844 5.74  
873 6.53  
903 7.41  
934 8.38  
576  
608  
640  
672  
704  
737  
770  
803  
836  
870  
2.11  
2.54  
3.02  
3.56  
4.16  
4.83  
5.58  
6.41  
7.33  
8.33  
601  
633  
665  
696  
728  
760  
792  
825  
858  
891  
2.27  
2.73  
3.24  
3.80  
4.43  
5.12  
5.88  
6.72  
7.64  
8.63  
625  
656  
687  
719  
750  
782  
814  
846  
878  
2.43  
2.89  
3.43  
4.02  
4.68  
5.39  
6.18  
7.04  
7.98  
579  
611  
645  
678  
712  
746  
780  
814  
849  
2.32  
2.78  
3.31  
3.90  
4.56  
5.30  
6.12  
7.03  
8.02  
582  
616  
650  
685  
721  
756  
791  
827  
2.59  
3.07  
3.66  
4.31  
5.04  
5.85  
6.74  
7.71  
9500  
10000  
10500  
11000  
7.5 HP Standard Motor & Drive  
7.5HPStandardMotor& HigherStaticDriveAccessory  
Table PD-30 — Evaporator Fan Performance — 25 Ton — TC*301C — Continued  
External Static Pressure (Inches of Water)  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.40  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
7.5 HP Standard Motor & Drive  
5000*  
6500*  
7000*  
7500*  
8000  
8500  
9000  
716  
769  
790  
813  
837  
863  
890  
919  
949  
2.41  
3.59  
4.09  
4.65  
5.26  
5.97  
6.76  
7.64  
8.62  
741  
792  
812  
833  
857  
881  
908  
936  
2.60  
3.80  
4.31  
4.88  
5.51  
6.21  
7.00  
7.88  
765  
814  
833  
854  
876  
900  
925  
952  
2.80  
4.01  
4.53  
5.12  
5.76  
6.46  
7.25  
8.13  
789  
836  
854  
874  
896  
919  
943  
969  
3.00  
4.22  
4.76  
5.36  
6.01  
6.73  
7.52  
8.40  
812  
857  
875  
894  
915  
937  
961  
985  
3.20  
4.44  
4.99  
5.59  
6.26  
6.99  
7.79  
8.67  
9500  
10000  
10500  
11000  
7.5HPStandardMotor&HighStaticDriveAccessory  
Factory supplied motors, in commercial  
equipment, are definite purpose motors,  
specifically designed and tested to operate  
reliably and continuously at all cataloged  
conditions. Using the full horsepower range  
of our fan motors as shown in our tabular  
data will not result in nuisance tripping or  
premature motor failure. Our product’s  
warranty will not be affected.  
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.  
For Standard Motor & High Static Drive Accessory Fan Speed (RPM),  
referenceTablePD-32.  
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM),  
referenceTablePD-34.  
Fan motor heat (MBH) = 3.15 x Fan BHP  
*Unit applications below 8000 CFM  
Electric heaters restricted on applications below 8000  
CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat  
and Crankcase Heaters are required on applications  
below 8000 CFM.  
Notes:  
Data includes pressure drop due to wet coils and filters.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-35 to determine add’l static pressure drop due to  
other options/accessories.  
*Indicatesbothdownflowandhorizontalunits.  
RT-PRC002-EN  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½-25 Ton)  
Table PD-31— Standard Motor & Drive/Fan Speed (Rpm)  
Unit  
6Turns  
Open  
640  
5Turns  
Open  
680  
4Turns  
Open  
720  
3Turns  
Open  
760  
2Turns  
Open  
800  
1Turn  
Open  
840  
Tons Model No.  
Closed  
N/A  
N/A  
N/A  
941  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
TC*150D3,4,W, TC*151C3,4,W  
TC*150DK  
12½  
705  
756  
806  
857  
907  
957  
TC*180B3,4,W  
TC*180BK  
TC*181C3,4,W  
679  
N/A  
560  
869  
869  
615  
615  
590  
705  
721  
680  
600  
923  
924  
659  
659  
627  
764  
733  
640  
978  
978  
703  
703  
664  
806  
785  
680  
1032  
1032  
747  
747  
701  
849  
837  
720  
1087  
1087  
791  
791  
738  
891  
889  
760  
1141  
1141  
835  
835  
775  
15  
TC*210C3,4,W  
17½ TC*210CK  
TC*211C3,4,W  
TC*240B3,4,W,TC*241C3,4,W  
TC*240BK  
TC*300B/301C3,4,W  
TC*300BK  
20  
742  
738  
779  
775  
817  
812  
854  
849  
891  
886  
25  
701  
Factory set at 3 turns open.  
Table PD-32— Standard Motor & High Static Drive Accessory/Fan Speed (Rpm)  
Unit  
Model No.  
6Turns  
Open  
807  
806  
640  
835  
835  
816  
5Turns  
Open  
857  
849  
680  
879  
879  
853  
4Turns  
Open  
908  
891  
720  
923  
923  
890  
3Turns  
Open  
958  
934  
760  
967  
967  
928  
2Turns  
Open  
1009  
976  
1Turn  
Tons  
12½  
Open  
1059  
1019  
840  
1055  
1055  
1002  
Closed  
TC*151C3,4,W  
TC*180B3,4,W  
TC*181B3,4,W  
TC*211C3,4,W  
TC*240B/241C3,4,W  
TC*300B/301C3,4,W  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
15  
800  
17½  
20  
25  
1011  
1011  
965  
Table PD-33— Oversized Motor & Drive/Fan Speed (Rpm)  
Unit  
6Turns  
Open  
869  
806  
705  
5Turns  
Open  
923  
856  
755  
4Turns  
Open  
978  
907  
806  
3Turns  
2Turns  
1Turn  
Tons Model No.  
12½ TC*150D,151C3,4,W  
Open  
1032  
957  
Open  
1087  
1008  
907  
Open  
1141  
1058  
957  
Closed  
N/A  
N/A  
TC*180B3,4,W  
15  
TC*181C3,4,W  
856  
N/A  
TC*210C3,4,W  
TC*211C3,4,W  
949  
816  
1008  
853  
1068  
890  
1127  
928  
1187  
965  
1246  
1002  
N/A  
N/A  
17½  
20  
TC*240B/241C3,4,W  
816  
853  
890  
928  
965  
1002  
N/A  
Table PD-34 — Standard Motor & Low Static Fan Drive  
Unit  
6Turns  
Open  
5Turns  
Open  
4Turns  
Open  
3Turns  
Open  
2Turns  
Open  
1Turn  
Open  
Tons Model No.  
Closed  
N/A  
17½ TC*210C3,4,W  
705  
594  
755  
631  
806  
668  
856  
705  
907  
742  
957  
779  
25  
TC*300B/301C3,4,W  
N/A  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½-25 Ton)  
Table PD-35 — Static Pressure Drops Through Accessories (Inches Water Column)  
Economizerwith  
OA/RADampers2  
Filters1 Reheat Coil Pleated Filters4 100% OA  
Electric Heater  
Unit  
ModelNo.  
Standard  
Through  
2 Inch  
Accessory (KW)3  
Tons  
12½  
CFM  
4000  
5000  
6000  
2500  
4000  
5000  
6000  
4800  
6000  
7200  
3000  
4800  
6000  
7200  
4800  
6000  
7200  
5600  
7000  
8400  
3500  
5600  
7000  
8400  
5600  
7000  
8400  
6400  
8000  
9600  
4000  
6400  
8000  
9600  
6400  
8000  
9600  
7000  
9000  
11000  
5000  
7000  
9000  
11000  
7000  
9000  
11000  
100% RA  
0.02  
0.03  
0.04  
0.01  
0.02  
0.03  
0.04  
0.03  
0.04  
0.05  
0.03  
0.03  
0.04  
0.05  
0.03  
0.04  
0.05  
0.04  
0.05  
0.06  
0.03  
0.04  
0.04  
0.06  
0.04  
0.04  
0.06  
0.04  
0.05  
0.07  
0.03  
0.04  
0.05  
0.07  
0.04  
0.05  
0.07  
0.04  
0.07  
0.10  
0.03  
0.04  
0.07  
0.10  
0.04  
0.07  
0.10  
5-12  
14-27  
0.03  
0.04  
0.06  
*
0.03  
0.04  
0.06  
0.04  
0.06  
0.09  
*
0.04  
0.06  
0.09  
0.04  
0.06  
0.09  
36  
54  
72  
0.05  
0.07  
0.10  
0.02  
0.05  
0.07  
0.10  
0.07  
0.10  
0.01  
0.03  
0.05  
0.06  
0.08  
0.11  
0.15  
0.03  
0.08  
0.11  
0.15  
0.10  
0.15  
0.19  
0.26  
0.33  
0.07  
0.19  
0.26  
0.33  
0.25  
0.33  
0.40  
0.07  
0.14  
0.20  
0.27  
0.14  
0.20  
0.27  
0.30  
0.39  
0.47  
0.09  
0.18  
0.26  
0.35  
0.18  
0.26  
0.35  
0.22  
0.32  
0.44  
0.11  
0.22  
0.32  
0.44  
0.22  
0.32  
0.44  
0.26  
0.40  
0.57  
0.15  
0.26  
0.40  
0.57  
0.26  
0.40  
0.60  
0.03  
0.05  
0.07  
*
0.04  
0.06  
0.09  
*
TC*150D,TCH151C  
TCD151C  
0.03  
0.05  
0.07  
0.04  
0.07  
0.10  
*
0.04  
0.06  
0.09  
0.05  
0.08  
0.12  
*
TC*180B  
TCD181C  
0.15  
0.19  
0.02/0.01  
0.04/0.03  
0.06/0.05  
0.09/0.07  
0.04/0.03  
0.06/0.05  
0.09/0.07  
0.09  
0.01  
0.02  
0.03  
0.04  
0.02  
0.04  
0.05  
0.07  
0.03/0.02  
0.07/0.06  
0.10/0.09  
0.13/0.11  
0.07/0.06  
0.10/0.09  
0.13/0.11  
0.13  
0.04  
0.07  
0.10  
0.04  
0.07  
0.10  
0.06  
0.10  
0.15  
*
0.05  
0.08  
0.12  
0.05  
0.08  
0.12  
0.07  
0.11  
0.17  
*
15  
TCH181C  
TC*210C  
0.14  
0.20  
0.18  
0.24  
0.02/0.02  
0.06/0.05  
0.09/0.07  
0.12/0.10  
0.06/0.05  
0.09/0.07  
0.12/0.10  
0.07  
0.11  
0.16  
0.03  
0.07  
0.11  
0.16  
0.06  
0.09  
0.13  
0.09  
0.14  
0.21  
0.03/0.03  
0.09/0.08  
0.13/0.11  
0.17/0.14  
0.09/0.08  
0.13/0.11  
0.17/0.14  
0.11  
0.15  
0.20  
0.04  
0.11  
0.15  
0.20  
0.10  
0.13  
0.17  
0.13  
0.18  
0.25  
*
0.05  
0.08  
0.12  
0.05  
0.08  
0.12  
0.06  
0.10  
0.14  
*
0.06  
0.09  
0.13  
0.06  
0.09  
0.13  
0.08  
0.12  
0.17  
*
0.07  
0.11  
0.16  
0.07  
0.11  
0.16  
0.09  
0.14  
0.20  
*
0.09  
0.14  
0.20  
0.09  
0.14  
0.20  
0.11  
0.18  
0.26  
*
17½  
TCD211C  
TCH211C  
TCD240B  
0.06  
0.10  
0.14  
0.06  
0.10  
0.14  
0.08  
0.13  
0.18  
*
0.08  
0.12  
0.17  
0.08  
0.12  
0.17  
0.10  
0.15  
0.22  
*
20  
TCD241C  
TCH240B,TCH241C  
TCD300B  
0.04  
0.09  
0.14  
0.21  
0.07  
0.11  
0.17  
0.06  
0.13  
0.18  
0.25  
0.11  
0.15  
0.22  
0.08  
0.13  
0.18  
0.08  
0.13  
0.18  
0.10  
0.15  
0.22  
0.10  
0.15  
0.22  
0.11  
0.18  
0.26  
0.11  
0.18  
0.26  
25  
TCD301C  
TCH300B,TCH301C  
Notes:  
1. Tested with: 2” filters 12½-25 tons  
2. OA = Outside Air and RA = Return Air.  
3. NominalKWratingsat240, 480, 600volts.  
4. Difference in pressure drop should be considered when utilizing optional 2” pleated filters.  
*Heaters not permitted at airflows below 320 cfm/ton.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(12½-25 Ton)  
Table PD-36 — Auxiliary Electric Heat Capacity  
Total2  
Stage1  
Stage 2  
Unit  
ModelNo.  
KW  
Input1  
MBH  
Output1  
No. of  
Stages  
KW  
Input1  
MBH  
Output1  
KW  
Input1  
MBH  
Output1  
Tons  
18.00  
27.004  
36.00  
54.00  
61.47  
92.15  
122.94  
184.41  
1
2
2
2
18.00  
9.00  
18.00  
36.00  
61.47  
30.72  
61.47  
TC*150D3,D4,DW,DK  
TC*180B3,B4,BW,BK  
TC*151 or 181C3,C4,CW  
18.00  
18.00  
18.00  
61.43  
61.47  
61.47  
12½-15  
122.94  
TC*210C3,C4,CW,CK  
TC*240, 300B3,B4,BW,BK  
TC*211, 241, 301C3,C4,CW  
36.00  
54.00  
72.003  
122.94  
184.41  
245.88  
2
2
2
18.00  
36.00  
36.00  
61.47  
122.94  
122.94  
18.00  
18.00  
36.00  
61.47  
61.47  
122.94  
17½, 20, 25  
Notes:  
2
1. Does not include indoor fan power or heat.  
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =  
3. NotavailableonTC*210C.  
Voltage  
x rated cap.  
(
)
RatedVoltage  
4. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.  
Table PD-37 — Electric Heater Voltage  
Correction Factors (Applicable to Auxiliary  
Heat Capacity)  
Nominal  
Voltage  
Distribution  
Voltage  
Capacity  
Multiplier  
208  
230  
240  
0.75  
0.92  
1.00  
240  
480  
600  
440  
460  
480  
0.84  
0.94  
1.00  
540  
575  
600  
0.81  
0.92  
1.00  
Table PD-38 — Air Temperature Rise Across Electric Heaters (Degree F)  
12½Ton  
15Ton  
17½Ton  
20Ton  
25Ton  
5000CFM  
6000CFM  
7000CFM  
8000CFM  
9000CFM  
ThreePhase ThreePhase ThreePhase ThreePhase ThreePhase  
TC*150  
TC*151  
11.4  
22.8  
34.1  
TC*180  
TC*181  
9.5  
14.22  
19.0  
28.5  
TC*210  
TC*211  
12.221  
16.3  
24.4  
32.5  
TC*240  
TC*241  
10.72  
14.2  
21.3  
28.5  
TC*300  
TC*301  
9.52  
12.6  
19.0  
25.3  
KW  
9.00  
Stages  
1
1
1
2
2
2
2
17.30  
18.00  
27.00  
36.00  
54.00  
72.002  
For minimum design airflow, see airflow performance table for each unit.  
To calculate temp rise at different air flow, use following formula:  
KW x 3413  
Temp. Rise across Elect. Htr =  
1.08 x CFM  
Notes:  
1.NotavailableonTC*210model.  
2. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.  
RT-PRC002-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-39— Hot Gas Reheat Temperature Rise1,2,3  
Leaving Evaporator Dry Bulb [F]1  
Tons  
SCFM  
2500  
3000  
3500  
4000  
4500  
5000  
5500  
6000  
35  
40  
45  
50  
55  
60  
65  
23.4  
21.4  
19.5  
17.8  
16.3  
14.9  
13.5  
12.1  
23.8  
21.6  
19.7  
18.1  
16.7  
15.5  
14.4  
13.4  
25.0  
22.5  
20.4  
18.6  
17.3  
16.2  
15.3  
14.6  
26.9  
24.0  
21.5  
19.6  
18.1  
17.1  
16.2  
15.7  
29.5  
26.0  
23.1  
20.9  
19.2  
18.0  
17.2  
16.7  
32.9  
28.7  
25.2  
22.5  
20.5  
19.2  
18.1  
17.6  
37.0  
31.9  
27.7  
24.5  
22.1  
20.4  
19.1  
18.3  
12½  
Tons  
15  
SCFM  
3000  
3600  
4200  
4800  
5400  
6000  
6600  
7200  
35  
40  
45  
50  
55  
60  
65  
34.4  
29.3  
25.4  
22.3  
19.9  
18.0  
16.4  
15.1  
36.7  
31.2  
27.0  
23.7  
21.2  
19.1  
17.5  
16.1  
38.9  
33.1  
28.6  
25.1  
22.4  
20.3  
18.6  
17.1  
41.2  
35.0  
30.2  
26.5  
23.7  
21.4  
19.6  
18.1  
43.5  
36.9  
31.9  
27.9  
24.9  
22.5  
20.7  
19.1  
45.8  
38.8  
33.5  
29.3  
26.2  
23.7  
21.7  
20.1  
48.1  
40.8  
35.1  
30.7  
27.4  
24.8  
22.8  
21.1  
Tons  
20  
SCFM  
4000  
4800  
5600  
6400  
7200  
8000  
8800  
9600  
35  
40  
45  
50  
55  
60  
65  
22.0  
19.1  
16.6  
14.7  
13.5  
12.9  
12.5  
12.4  
22.5  
19.8  
17.4  
15.5  
14.1  
13.2  
12.9  
12.8  
23.6  
20.9  
18.4  
16.3  
14.7  
13.7  
13.3  
13.1  
25.4  
22.3  
19.5  
17.2  
15.4  
14.2  
13.7  
13.5  
27.7  
24.0  
20.9  
18.2  
16.2  
14.8  
14.2  
13.9  
30.6  
26.1  
22.4  
19.3  
17.0  
15.5  
14.8  
14.5  
34.0  
28.5  
24.0  
20.6  
17.9  
16.2  
15.4  
15.0  
Notes:  
1. Temperature does not account for indoor fan heat.  
2. 70 deg OD Ambient Temperature.  
3. For units with the Dehumidification (Hot Gas Reheat) option.  
RT-PRC002-EN  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
Digital Display Zone Sensor  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone  
CO2 Sensing The CO2 sensor has the  
ability to monitor space occupancy levels  
within the  
Field Installed Control Options  
Zone Sensors  
Zone sensors are the building occupants  
comfort control devices.They replace the  
conventional electro-mechanical  
thermostats.The following zone sensor  
options are available forVoyager units  
with the ReliaTel™ control:  
building by  
sensors.This  
measuring the  
sensor includes a  
parts per million  
digital display of  
of CO2 (Carbon  
set point  
Dioxide) in the air.  
adjustment and  
As the CO2 levels  
Manual Changeover  
Heat, Cool or Off  
System Switch. Fan  
Auto or Off Switch.  
One temperature  
setpoint lever.  
space temperature  
increase, the  
in F (Fahrenheit) or  
outside air  
C (Celsius).  
damper  
Includes FAN and  
modulates to  
SYSTEM buttons  
meet the CO2 space ventilation  
requirements.The CO2 sensor kit is  
available as a field installed accessory.  
(supports the  
service functions of  
the standard  
Economizer Controls  
sensor). E-squared memory stores last  
programmed set points. Requires 24VAC  
(Volts AC).This sensor should be utilized  
with ReliaTel controls.  
The standard equipment offering is a  
fixed dry bulb changeover control. In  
addition, there are two optional controls,  
Enthalpy and Differential Enthalpy  
Control.  
Manual/Automatic Changeover  
Auto, Heat, Cool or Off System Switch.  
Fan Auto or Off  
Programmable Night Setback  
Auto or manual changeover with seven-  
day programming. Keyboard selection  
Enthalpy Control  
Switch.Two  
Replaces the dry bulb control with a wet  
bulb changeover controller which has a  
fully adjustable set point. Enthalpy control  
offers a higher level of comfort control,  
along with energy savings potential, than  
the standard dry bulb control. This is due  
to the additional wet bulb sensing  
capability.  
temperature  
setpoint levers.  
Optional Status  
Indication LED lights,  
System On, Heat,  
Cool, or Service.  
Differential Enthalpy  
Replaces the standard dry bulb control  
with two enthalpy sensors that compare  
total heat content of the indoor air and  
outdoor air to determine the most  
efficient air source.This control option  
offers the highest level of comfort control,  
plus energy efficiency, available.  
Remote Sensor  
Sensor(s) available  
for all zone sensors to  
provide remote  
of Heat, Cool, Fan, Auto, or On. All  
programmable sensors have System On,  
Heat, Cool, Service LED/indicators as  
standard. Night Setback Sensors have  
one (1) Occupied, one (1) Un-occupied,  
and two (2) Override programs per day.  
sensing capabilities.  
Remote Potentiometer  
Minimum position setting of economizer  
can be remotely adjusted with this  
accessory.  
Integrated  
Differential Pressure Switches  
ComfortTM  
This factory or field-installed option  
allows individual fan failure and dirty filter  
indication. The fan failure switch will  
disable all unit functions and “flash” the  
Service LED on the zone sensor. The dirty  
filter switch will light the Service LED on  
the zone sensor and will allow continued  
unit operation.  
System  
Sensor(s)  
available with  
optional  
temperature  
adjustment and  
override buttons  
to provide central  
control through a  
Trane Integrated  
Comfort system.  
DualThermistor Remote Zone Sensor  
This sensor will allow the customer to  
reduce the total number of remote  
sensors to obtain space temperature  
averaging. This sensor should be utilized  
with ReliaTel controls.  
Trane Communication Interface (TCI)  
This factory or field-installed micro-  
processor interface allows the unit to  
communicate toTranes Integrated  
Comfort system.  
RT-PRC002-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard Efficiency)  
Table ED-1 — Unit Wiring — Standard Efficiency  
StandardIndoorFanMotor  
Oversize Indoor Fan Motor  
Unit  
Minimum  
Circuit  
MaximumFuse  
Size or Maximum  
Circuit Breaker1 Ampacity2  
Minimum  
Circuit  
MaximumFuse  
Size or Maximum  
Circuit Breaker1  
Unit  
Operating  
VoltageRange Ampacity2  
Tons  
12½  
ModelNo.  
TC*150D3  
TC*150D4  
TC*150DW  
TC*150DK  
TC*180B3  
TC*180B4  
TC*180BW  
TC*180BK  
187-253  
414-506  
518-633  
342-418  
187-253  
414-506  
517-633  
342-418  
63  
33  
26  
43  
78  
39  
31  
50  
80  
40  
30  
50  
90  
50  
40  
60  
69  
36  
28  
84  
42  
33  
80  
40  
35  
100  
50  
40  
15  
TC*210C3  
TC*210C4  
TC*210CW  
TC*210CK  
TC*240B3  
TC*240B4  
TC*240BW  
TC*240BK  
187-253  
414-506  
517-633  
342-418  
187-253  
414-506  
517-633  
342-418  
88  
44  
35  
57  
100  
50  
100  
50  
45  
70  
125  
60  
96  
47  
38  
107  
54  
43  
125  
60  
45  
125  
60  
50  
17½  
20  
40  
65  
45  
80  
TC*300B3  
TC*300B4  
TC*300BW  
TC*300BK  
187-253  
414-506  
517-633  
342-418  
118  
58  
46  
150  
70  
50  
25  
70  
80  
Notes:  
1. HACRbreakerperNEC.  
2. Values do not include power exhaust accessory.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard Efficiency)  
Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only)  
StandardIndoorMotor  
Oversize Indoor Motor  
Max Fuse Size or  
To Use  
With  
Heater  
ModelNo.  
Heater  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker2  
Tons  
12½  
KW Rating1  
MCA  
MCA  
Max Circuit  
Breaker2  
208/230 Volts Three Phase  
13.5/18.0  
27.0/36.0  
40.5/54.0  
AYDHTRF318A  
AYDHTRF336A  
AYDHTRF354A  
1
2
2
63/68  
108/122  
154/176  
80/80  
69/76  
80/80  
TCD150D3  
110/125  
175/200  
115/130  
162/184  
125/150  
175/200  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
78/78  
108/122  
154/176  
100/100  
110/125  
175/200  
84/84  
115/130  
162/184  
100/100  
125/150  
175/200  
15  
TCD180B3  
TCD210C3  
TCD240B3  
AYDHTRL336A  
AYDHTRL354A  
27.0/36.0  
40.5/54.0  
2
2
115/130  
162/184  
125/150  
175/200  
125/139  
171/193  
125/150  
175/200  
17½  
20  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
125/139  
171/193  
218/247  
150/150  
175/200  
225/250  
25  
TCD300B3  
TCD150D4  
460 Volts Three Phase  
18.0  
36.0  
54.0  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
1
2
2
34  
61  
88  
40  
70  
90  
37  
64  
91  
40  
70  
100  
12½  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
18.0  
36.0  
54.0  
1
2
2
39  
61  
88  
50  
70  
90  
42  
64  
91  
50  
70  
100  
15  
TCD180B4  
TCD210C4  
TCD240B4  
AYDHTRL436A  
AYDHTRL454A  
36.0  
54.0  
2
2
64  
91  
70  
100  
68  
95  
70  
100  
17½  
20  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
36.0  
54.0  
72.0  
2
2
2
64  
91  
118  
70  
100  
125  
68  
95  
123  
70  
100  
125  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
36.0  
54.0  
72.0  
2
2
2
68  
95  
123  
70  
100  
125  
25  
TCD300B4  
TCD150DW  
575 Volts Three Phase  
18.0  
36.0  
54.0  
AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRKW54A  
1
2
2
27  
49  
70  
30  
50  
70  
30  
51  
73  
35  
60  
80  
12½  
AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
31  
49  
70  
40  
50  
70  
33  
51  
73  
40  
60  
80  
15  
TCD180BW  
TCD210CW  
TCD240BW  
AYDHTRMW36A  
AYDHTRLW54A  
36.0  
54.0  
2
2
51  
73  
60  
80  
55  
77  
60  
80  
17½  
20  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
55  
77  
98  
60  
80  
100  
25  
TCD300BW  
Notes:  
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC002-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard Efficiency)  
Table ED-2 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Downflow Only), continued  
StandardIndoorMotor  
Max Fuse Size or  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
KW Rating1  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker2  
Tons  
12½  
MCA  
Max Circuit  
Breaker2  
MCA  
380 Volts Three Phase  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
11.3  
22.6  
33.8  
1
2
2
43  
55  
76  
50  
60  
80  
TCD150DK  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
11.3  
22.6  
33.8  
1
2
2
50  
55  
76  
60  
60  
80  
15  
TCD180BK  
TCD210CK  
TCD240BK  
AYDHTRL436A  
AYDHTRL454A  
22.6  
33.8  
2
2
60  
81  
70  
90  
17½  
20  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
22.6  
33.8  
45.1  
2
2
2
65  
81  
103  
80  
90  
110  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
22.6  
33.8  
45.1  
2
2
2
70  
81  
103  
80  
90  
100  
25  
TCD300BK  
Notes:  
1. Heater kw ratings are at 380V for 380 unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC002-EN  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard Efficiency)  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only)  
StandardIndoorMotor  
Max Fuse Size or  
MCA Max Circuit Breaker2  
Oversize Indoor Motor  
Max Fuse Size or  
MCA Max Circuit Breaker2  
To Use  
With  
Heater  
ModelNo.  
Heater  
Control  
Stages  
Tons  
12½  
KW Rating1  
208/230 Volts Three Phase  
13.5/18.0  
27.0/36.0  
40.5/54.0  
AYHHTRN318A  
AYHHTRN336A  
AYHHTRN354A  
1
2
2
63/68  
108/122  
154/176  
80/80  
69/76  
80/80  
TCH150D3  
110/125  
175/200  
115/130  
162/184  
125/150  
175/200  
AYHHTRN318A  
AYHHTRP336A  
AYHHTRP354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
78/78  
108/122  
154/176  
100/100  
110/125  
175/200  
84/84  
115/130  
162/184  
100/100  
125/150  
175/200  
15  
TCH180B3  
TCH210C3  
TCH240B3  
AYHHTRQ336A  
AYHHTRQ354A  
27.0/36.0  
40.5/54.0  
2
2
115/130  
162/184  
125/150  
175/200  
125/139  
171/193  
125/150  
175/200  
17½  
20  
AYHHTRN336A  
AYHHTRN354A  
AYHHTRN372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
AYHHTRN336A  
AYHHTRN354A  
AYHHTRN372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
132/139  
171/193  
218/247  
150/150  
175/200  
225/250  
25  
TCH300B3  
TCH150D4  
460 Volts Three Phase  
18.0  
36.0  
54.0  
AYHHTRN418A  
AYHHTRN436A  
AYHHTRP454A  
1
2
2
34  
61  
88  
40  
70  
90  
37  
64  
91  
40  
70  
100  
12½  
AYHHTRN418A  
AYHHTRP436A  
AYHHTRP454A  
18.0  
36.0  
54.0  
1
2
2
37  
61  
88  
50  
70  
90  
42  
64  
91  
50  
70  
100  
15  
TCH180B4  
TCH210C4  
TCH240B4  
AYHHTRQ436A  
AYHHTRQ454A  
36.0  
54.0  
2
2
64  
91  
70  
100  
68  
95  
70  
100  
17½  
20  
AYHHTRN436A  
AYHHTRN454A  
AYHHTRN472A  
36.0  
54.0  
72.0  
2
2
2
64  
91  
118  
70  
100  
125  
68  
95  
123  
70  
100  
125  
AYHHTRN436A  
AYHHTRN454A  
AYHHTRN472A  
36.0  
54.0  
72.0  
2
2
2
68  
95  
123  
70  
100  
125  
25  
TCH300B4  
575 Volts Three Phase  
AYHHTRNW18A  
AYHHTRPW36A  
AYHHTRPW54A  
18.0  
36.0  
54.0  
1
2
2
27  
49  
70  
30  
50  
70  
30  
51  
73  
35  
60  
80  
12½  
15  
TCH150DW  
TCH180BW  
AYHHTRNW18A  
AYHHTRPW36A  
AYHHTRPW54A  
18.0  
36.0  
54.0  
1
2
2
31  
49  
70  
40  
50  
70  
33  
51  
73  
40  
60  
80  
AYHHTRPW36A  
AYHHTRQW54A  
36.0  
54.0  
2
2
51  
73  
60  
80  
55  
77  
60  
80  
17½  
20  
TCH210CW  
TCH240BW  
AYHHTRMW36A  
AYHHTRNW54A  
AYHHTRNW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
AYHHTRMW36A  
AYHHTRNW54A  
AYHHTRNW72A  
36.0  
54.0  
72.0  
2
2
2
55  
77  
98  
60  
80  
100  
25  
TCH300BW  
Notes:  
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit..  
2. HACR type circuit breaker per NEC.  
RT-PRC002-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard Efficiency)  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (Horizontal Only) continued  
StandardIndoorMotor  
Max Fuse Size or  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
KW Rating1  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker2  
Tons  
12½  
MCA  
Max Circuit  
Breaker2  
MCA  
380 Volts Three Phase  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
11.3  
22.6  
33.8  
1
2
2
43  
55  
76  
50  
60  
80  
TCD150DK  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
11.3  
22.6  
33.8  
1
2
2
50  
55  
76  
60  
60  
80  
15  
TCD180BK  
TCD210CK  
TCD240BK  
AYDHTRL436A  
AYDHTRL454A  
22.6  
33.8  
2
2
60  
81  
70  
90  
17½  
20  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
22.6  
33.8  
45.1  
2
2
2
65  
81  
103  
80  
90  
110  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
22.6  
33.8  
45.1  
2
2
2
70  
81  
103  
80  
90  
100  
25  
TCD300BK  
Notes:  
1. Heater kw ratings are at 380V for 380 unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC002-EN  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard Efficiency)  
Table ED-4— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency  
CompressorMotors  
CondenserFanMotors  
Unit  
Amps1  
Amps1  
Tons  
12½  
15  
ModelNo.  
No.  
Volts  
Phase  
HP2  
RPM  
RLA  
LRA  
No.  
Phase  
HP  
FLA  
LRA  
TC*150D3  
TC*150D4  
TC*150DW  
TC*150DK  
2
2
2
2
208-230  
460  
575  
3
3
3
3
6.00  
6.00  
6.00  
6.0  
3450  
3450  
3450  
3450  
20.4  
10.8  
8.3  
156  
75  
54  
2
2
2
2
1
1
1
1
.50  
.50  
.50  
.50  
3.2  
1.6  
1.3  
1.9  
8.8  
3.8  
3.2  
5.2  
380  
13.1  
70  
TC*180B3  
TC*180B4  
TC*180BW  
TC*180BK  
2
2
2
2
208-230  
460  
575  
3
3
3
3
9.30/5.10 3450 31.9/20.7  
9.30/5.10 3450 16.3/10.0  
9.30/5.10 3450 13.1/7.4  
9.3/5.1 3450 19.7/12.1  
253/128  
113/63  
85/49  
2
2
2
2
1
1
1
1
.50  
.50  
.50  
.50  
3.2  
1.6  
1.3  
1.9  
8.8  
3.8  
3.2  
5.2  
380  
125/64  
TC*210C3  
TC*210C4  
TC*210CW  
TC*210CK  
2
2
2
2
208-230  
460  
575  
3
3
3
3
9.3/6.0 3450 31.5/20.8  
9.3/6.0 3450 15.9/10.0  
9.3/6.0 3450 12.8/8.2  
9.3/6.0 3450 19.2/12.1  
253/156  
113/75  
85/54  
2
2
2
2
1
1
1
1
1.00  
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
3.5  
18.3  
9.3  
5.7  
8.5  
17½  
20  
380  
125/70  
TC*240B3  
TC*240B4  
TC*240BW  
TC*240BK  
2
2
2
2
208-230  
460  
575  
3
3
3
3
9.30  
9.30  
9.30  
9.3  
3450  
3450  
3450  
3450  
31.7  
16.2  
13.0  
19.6  
253  
113  
85  
2
2
2
2
1
1
1
1
1.00  
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
3.5  
18.3  
9.3  
5.7  
8.5  
380  
125  
TC*300B3  
TC*300B4  
TC*300BW  
TC*300BK  
2
2
2
2
208-230  
460  
575  
3
3
3
3
10.00  
10.00  
10.00  
10.0  
3450  
3450  
3450  
3450  
36.6  
17.9  
14.9  
21.7  
278  
124  
92  
2
2
2
2
1
1
1
1
1.00  
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
3.5  
18.3  
9.3  
5.7  
8.5  
25  
380  
137  
Notes:  
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.  
2. HP for each compressor.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-5 — Unit Wiring - High Efficiency - Standard Refrigeration System  
StandardIndoorFanMotor  
Oversize Indoor Fan Motor  
Unit  
Operating  
VoltageRange  
Minimum  
Circuit  
Ampacity2  
MaximumFuse  
Size or Maximum  
Circuit Breaker1 Ampacity2  
Minimum  
Circuit  
MaximumFuse  
Size or Maximum  
Circuit Breaker1  
Unit  
Tons  
12½  
ModelNo.  
TC*151C3  
TC*151C4  
TC*151CW  
187-253  
414-506  
517-633  
64  
31  
25  
80  
40  
30  
70  
34  
28  
90  
40  
35  
TC*181C3  
TC*181C4  
TC*181CW  
187-253  
414-506  
517-633  
74  
36  
29  
90  
50  
40  
80  
38  
31  
100  
50  
40  
15  
TC*211C3  
TC*211C4  
TC*211CW  
187-253  
414-506  
517-633  
91  
44  
35  
110  
60  
45  
98  
48  
38  
125  
60  
50  
17½  
20  
TC*241C3  
TC*241C4  
TC*241CW  
187-253  
414-506  
517-633  
99  
50  
40  
125  
60  
50  
107  
54  
43  
125  
60  
50  
TC*301C3  
TC*301C4  
TC*301CW  
187-253  
414-506  
517-633  
120  
58  
47  
150  
70  
60  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
25  
Notes:  
1. HACRbreakerperNEC.  
2. Values do not include power exhaust accessory.  
Table ED-6— Unit Wiring - High Efficiency - TXV/Face-Split Evaporator Coil Option (Downflow Only)  
Standard Indoor Fan Motor  
Oversize Indoor Fan Motor  
Unit  
Operating  
Voltage Range  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
Minimum  
Maximum Fuse  
Minimum  
Circuit  
Ampacity2  
65  
Maximum Fuse  
Unit  
Circuit  
Size or Maximum  
Size or Maximum  
Tons  
12½  
Model No.  
TCD151C3  
TCD151C4  
TCD151CW  
TCD181C3  
TCD181C4  
TCD181CW  
TCD211C3  
TCD211C4  
TCD211CW  
TCD241C3  
TCD241C4  
TCD241CW  
TCD301C3  
TCD301C4  
TCD301CW  
Ampacity2  
59  
Circuit Breaker1  
Circuit Breaker1  
70  
35  
30  
90  
50  
40  
125  
60  
45  
125  
60  
50  
150  
70  
50  
80  
40  
30  
90  
50  
40  
125  
60  
50  
125  
70  
30  
24  
74  
37  
30  
91  
45  
36  
99  
51  
40  
117  
57  
32  
26  
80  
39  
32  
99  
49  
39  
107  
54  
43  
N/A  
N/A  
N/A  
15  
17½  
20  
50  
N/A  
N/A  
N/A  
25  
46  
Notes:  
1. HACRbreakerperNEC.  
2. Values do not include power exhaust accessory.  
RT-PRC002-EN  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-7 — Unit Wiring - High Efficiency - Dehumidification (Hot Gas Reheat) Option  
(Downflow Only)  
Standard Indoor Fan Motor  
Oversize Indoor Fan Motor  
Unit  
Operating  
Voltage Range  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
Minimum  
Maximum Fuse  
Minimum  
Maximum Fuse  
Unit  
Circuit  
Size or Maximum  
Circuit  
Size or Maximum  
Tons  
12½  
Model No.  
TCD151C3  
TCD151C4  
TCD151CW  
TCD181C3  
TCD181C4  
TCD181CW  
TCD241C3  
TCD241C4  
TCD241CW  
Ampacity2  
Circuit Breaker1  
Ampacity2  
Circuit Breaker1  
59  
30  
24  
71  
36  
28  
98  
50  
39  
70  
35  
30  
90  
45  
35  
125  
60  
50  
65  
32  
26  
77  
39  
30  
105  
53  
42  
80  
40  
30  
100  
50  
40  
125  
60  
50  
15  
187-253  
414-506  
517-633  
20  
Notes:  
1. HACRbreakerperNEC.  
2. Values do not include power exhaust accessory.  
RT-PRC002-EN  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-8 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System  
(Downflow Only)  
StandardIndoorMotor  
Max Fuse Size or  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
KW Rating  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker2  
Tons  
MCA  
Max Circuit  
Breaker1  
MCA  
208/230 Volts Three Phase  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
64/68  
108/122  
154/176  
80/80  
110/125  
175/200  
70/76  
115/130  
162/184  
90/90  
125/150  
175/200  
12½  
15  
TCD151C3  
TCD181C3  
TCD211C3  
TCD241C3  
TCD301C3  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
74/74  
108/122  
154/176  
100/100  
110/125  
175/200  
80/80  
115/130  
162/184  
100/100  
125/150  
175/200  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
17½  
20  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
125/139  
171/193  
218/247  
150/150  
175/200  
225/250  
25  
460 Volts Three Phase  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
18.0  
36.0  
54.0  
1
2
2
34  
61  
88  
40  
70  
90  
37  
64  
91  
40  
70  
100  
12½  
15  
TCD151C4  
TCD181C4  
TCD211C4  
TCD241C4  
TCD301C4  
AYDHTRL418A  
AYDHTRK427A  
AYDHTRK436A  
AYDHTRK454A  
18.0  
27.0  
36.0  
54.0  
1
2
2
2
36  
47  
61  
88  
50  
50  
70  
90  
38  
64  
91  
50  
70  
100  
AYDHTRL427A  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
27.0  
36.0  
54.0  
72.0  
2
2
2
2
51  
64  
91  
60  
70  
100  
125  
68  
95  
70  
100  
125  
17½  
20  
118  
123  
AYDHTRL427A  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
27.0  
36.0  
54.0  
72.0  
2
2
2
2
51  
64  
91  
60  
70  
100  
125  
68  
95  
70  
100  
125  
118  
123  
AYDHTRL436A  
AYDHTRL427A  
AYDHTRL454A  
AYDHTRK472A  
36.0  
27.0  
54.0  
72.0  
2
2
2
2
68  
58  
95  
70  
70  
100  
125  
25  
123  
575 Volts Three Phase  
AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
27  
49  
70  
30  
50  
70  
30  
51  
73  
35  
60  
80  
12½  
15  
TCD151CW  
TCD181CW  
TCD211CW  
TCD241CW  
TCD301CW  
AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
29  
49  
70  
40  
50  
70  
31  
31  
73  
40  
40  
80  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
17½  
20  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
55  
77  
98  
60  
80  
100  
25  
Notes:  
1. HACR type circuit breaker per NEC.  
2. Values do not include power exhaust accessory.  
RT-PRC002-EN  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-9 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, Standard Refrigeration System  
(Horizontal Only)  
StandardIndoorMotor  
Max Fuse Size or  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
KW Rating  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker2  
Tons  
MCA  
Max Circuit  
Breaker1  
MCA  
208/230 Volts Three Phase  
AYHHTRN318A  
AYHHTRP336A  
AYHHTRP354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
64/68  
108/122  
154/176  
80/80  
110/125  
175/200  
70/76  
115/130  
162/184  
90/90  
125/150  
175/200  
12½  
15  
TCH151C3  
TCH181C3  
TCH211C3  
TCH241C3  
TCH301C3  
AYHHTRM318A  
AYHHTRM336A  
AYHHTRM354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
74/74  
108/122  
154/176  
100/100  
110/125  
175/200  
80/80  
115/130  
162/184  
100/100  
125/150  
175/200  
AYHHTRN336A  
AYHHTRN354A  
AYHHTRN372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
17½  
20  
AYHHTRN336A  
AYHHTRN354A  
AYHHTRN372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
AYHHTRN336A  
AYHHTRN354A  
AYHHTRN372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
125/139  
171/193  
218/247  
150/150  
175/200  
225/250  
25  
460 Volts Three Phase  
AYHHTRN418A  
AYHHTRP436A  
AYHHTRP454A  
18.0  
36.0  
54.0  
1
2
2
34  
61  
88  
40  
70  
90  
37  
64  
91  
40  
70  
100  
12½  
15  
TCH151C4  
TCH181C4  
TCH211C4  
TCH241C4  
TCH301C4  
AYHHTRM418A  
AYHHTRM436A  
AYHHTRM454A  
18.0  
36.0  
54.0  
1
2
2
36  
61  
88  
50  
70  
90  
38  
64  
91  
50  
70  
100  
AYHHTRN436A  
AYHHTRN454A  
AYHHTRN472A  
36.0  
54.0  
72.0  
2
2
2
64  
91  
118  
70  
100  
125  
68  
95  
123  
70  
100  
125  
17½  
20  
AYHHTRN436A  
AYHHTRN454A  
AYHHTRN472A  
36.0  
54.0  
72.0  
2
2
2
64  
91  
118  
70  
100  
125  
68  
95  
123  
70  
100  
125  
AYHHTRN436A  
AYHHTRN454A  
AYHHTRN472A  
36.0  
54.0  
72.0  
2
2
2
68  
95  
123  
70  
100  
125  
25  
575 Volts Three Phase  
AYHHTRNW18A  
AYHHTRPW36A  
AYHHTRPW54A  
18.0  
36.0  
54.0  
1
2
2
27  
49  
70  
30  
50  
70  
30  
51  
73  
35  
60  
80  
12½  
15  
TCH151CW  
TCH181CW  
TCH211CW  
TCH241CW  
TCH301CW  
AYHHTRMW18A  
AYHHTRMW36A  
AYHHTRMW54A  
18.0  
36.0  
54.0  
1
2
2
29  
49  
70  
40  
50  
70  
31  
31  
73  
40  
40  
80  
AYHHTRMW36A  
AYHHTRNW54A  
AYHHTRNW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
17½  
20  
AYHHTRMW36A  
AYHHTRNW54A  
AYHHTRNW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
AYHHTRMW36A  
AYHHTRNW54A  
AYHHTRNW72A  
36.0  
54.0  
72.0  
2
2
2
55  
77  
98  
60  
80  
100  
25  
Notes:  
1. HACR type circuit breaker per NEC.  
2. Values do not include power exhaust accessory.  
RT-PRC002-EN  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and  
151/181/ 241 Reheat Option(Downflow Only)  
StandardIndoorMotor  
Max Fuse Size or  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
KW Rating  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker1,2  
Tons  
MCA  
Max Circuit  
Breaker2  
MCA  
208/230 Volts Three Phase  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
61/68  
108/122  
154/176  
70/70  
110/125  
175/200  
68/76  
115/130  
162/184  
80/80  
125/150  
175/200  
12½  
15  
TCD151C3  
AYDHTRK318A  
AYDHTRK336A  
AYDHTRK354A  
13.5/18.0  
27.0/36.0  
40.5/54.0  
1
2
2
74/74  
108/122  
154/176  
100/100  
110/125  
175/200  
80/80  
115/130  
162/184  
90/90  
125/150  
175/200  
TCD181C3  
TCD181C3  
TCD211C3  
*AYDHTRK318A  
13.5/18.0  
1
71/71  
90/90  
77/77  
100/100  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
17½  
20  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
115/130  
162/184  
209/238  
125/150  
175/200  
225/250  
125/139  
171/193  
218/247  
125/150  
175/200  
225/250  
TCD241C3  
TCD301C3  
AYDHTRL336A  
AYDHTRL354A  
AYDHTRK372A  
27.0/36.0  
40.5/54.0  
54.0/72.0  
2
2
2
125/139  
171/193  
218/247  
150/150  
175/200  
225/250  
25  
460 Volts Three Phase  
AYDHTRL418A  
AYDHTRK436A  
AYDHTRK454A  
18.0  
36.0  
54.0  
1
2
2
34  
61  
88  
35  
70  
90  
37  
64  
91  
40  
70  
100  
12½  
15  
TCD151C4  
AYDHTRL418A  
AYDHTRK427A3  
AYDHTRK436A  
AYDHTRK454A  
18.0  
27.0  
36.0  
54.0  
1
2
2
2
37  
47  
61  
88  
50  
50  
70  
90  
39  
64  
91  
50  
70  
TCD181C4  
TCD181C4  
100  
*AYDHTRL418A  
18.0  
1
36  
45  
39  
50  
AYDHTRL427A3  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
AYDHTRL427A3  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
AYDHTRL427A3  
AYDHTRL436A  
AYDHTRL454A  
AYDHTRK472A  
27.0  
36.0  
54.0  
72.0  
2
2
2
2
51  
64  
91  
60  
70  
100  
125  
68  
95  
70  
100  
125  
17½  
20  
TCD211C4  
TCD241C4  
TCD301C4  
118  
123  
27.0  
36.0  
54.0  
72.0  
2
2
2
2
51  
64  
91  
60  
70  
100  
125  
68  
95  
70  
100  
125  
118  
123  
27.0  
36.0  
54.0  
72.0  
2
2
2
2
57  
68  
95  
70  
70  
100  
125  
25  
123  
Notes:  
1. HACR type circuit breaker per NEC.  
2. Values do not include power exhaust accessory.  
3. Do not use with oversized motor.  
*
Applies only to Dehumidification (Hot Gas Reheat) Models  
RT-PRC002-EN  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and  
151/181/ 241 Reheat Option(Downflow Only), continued  
StandardIndoorMotor  
Max Fuse Size or  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
KW Rating  
Control  
Stages  
Max Fuse Size or  
Max Circuit  
Breaker1,2  
Tons  
MCA  
Max Circuit  
Breaker2  
MCA  
575 Volts Three Phase  
AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
27  
49  
70  
30  
50  
70  
30  
51  
73  
30  
60  
80  
12½  
15  
TCD151CW  
AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRKW54A  
18.0  
36.0  
54.0  
1
2
2
30  
49  
70  
40  
50  
70  
32  
51  
73  
40  
60  
80  
TCD181CW  
TCD181CW  
TCD211CW  
*AYDHTRKW18A  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
18.0  
36.0  
54.0  
72.0  
1
2
2
2
28  
51  
73  
95  
35  
60  
80  
30  
55  
77  
98  
40  
60  
80  
17½  
20  
100  
100  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
51  
73  
95  
60  
80  
100  
55  
77  
98  
60  
80  
100  
TCD241CW  
TCD301CW  
AYDHTRMW36A  
AYDHTRLW54A  
AYDHTRKW72A  
36.0  
54.0  
72.0  
2
2
2
55  
77  
98  
60  
80  
100  
25  
Notes:  
1. HACR type circuit breaker per NEC.  
2. Values do not include power exhaust accessory.  
3. Do not use with oversized motor.  
*
Applies only to Dehumidification (Hot Gas Reheat) Models  
RT-PRC002-EN  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High Efficiency)  
Table ED-11 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, Standard  
Refrigeration System  
CompressorMotors  
Condenser Fan Motors  
Unit  
Amps1  
Amps1  
Tons  
12½  
ModelNo.  
No.  
Volts  
Phase  
HP2  
RPM  
RLA  
LRA  
No.  
Phase  
HP  
FLA  
LRA  
TC*151C3  
TC*151C4  
TC*151CW  
2
2
2
208-230  
460  
575  
3
3
3
5.70  
5.70  
5.70  
3450  
3450  
3450  
20.7  
10.0  
8.2  
156  
75  
54  
2
2
2
1
1
1
.50  
.50  
.50  
3.2  
1.6  
1.3  
8.8  
3.8  
3.2  
TC*181C3  
TC*181C4  
TC*181CW  
2
2
2
208-230  
460  
575  
3
3
3
9.30/4.50 3450 31.5/16.9  
9.30/4.50 3450 15.1/8.2  
9.30/4.50 3450 12.1/6.6  
253/124  
113/59.6  
85/49.4  
2
2
2
1
1
1
.50  
.50  
.50  
3.2  
1.6  
1.3  
8.8  
3.8  
3.2  
15  
TC*211C3  
TC*211C4  
TC*211CW  
2
2
2
208-230  
460  
575  
3
3
3
10.0/5.70 3450 33.3/20.7  
10.0/5.70 3450 16.3/10.0  
10.0/5.70 3450 13.2/8.2  
278/156  
124/75  
92/54  
2
2
2
1
1
1
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
18.3  
9.3  
5.7  
17½  
20  
TC*241C3  
TC*241C4  
TC*241CW  
2
2
2
208-230  
460  
575  
3
3
3
9.30  
9.30  
9.30  
3450  
3450  
3450  
31.6  
16.1  
12.9  
253  
113  
85  
2
2
2
1
1
1
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
18.3  
9.3  
5.7  
TC*301C3  
TC*301C4  
TC*301CW  
2
2
2
208-230  
460  
575  
3
3
3
10.00  
10.00  
10.00  
3450  
3450  
3450  
37.6  
18.3  
14.9  
278  
124  
92  
2
2
2
1
1
1
1.00  
1.00  
1.00  
5.5  
2.9  
2.0  
18.3  
9.3  
5.7  
25  
Notes:  
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.  
2. HP for each compressor.  
Table ED-12 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, TXV/Face-Split  
Evaporator Coil Option (Downflow Only)  
CompressorMotors  
Condenser Fan Motors  
Unit  
Amps1  
Amps1  
Tons  
12½  
ModelNo.  
No.  
Volts  
Phase  
HP2  
5.7  
RPM  
RLA  
LRA  
No.  
Phase  
HP  
FLA  
LRA  
TCD151C3  
TCD151C4  
TCD151CW  
TCD181C3  
TCD181C4  
TCD181CW  
TCD211C3  
TCD211C4  
TCD211CW  
TCD241C3  
TCD241C4  
TCD241CW  
TCD301C3  
TCD301C4  
TCD301CW  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
208-230  
460  
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
18.6  
9.4  
7.4  
156  
75  
54  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.50  
.50  
.50  
.50  
.50  
3.2  
1.6  
1.3  
3.2  
1.6  
1.3  
5.5  
2.9  
2.0  
5.5  
2.9  
2.0  
5.5  
2.9  
2.0  
8.8  
3.8  
3.2  
8.8  
3.8  
3.2  
18.3  
9.3  
5.7  
18.3  
9.3  
5.7  
18.3  
9.3  
5.7  
5.7  
575  
5.7  
208-230  
460  
575  
208-230  
460  
575  
208-230  
460  
575  
208-230  
460  
9.30/4.50  
9.30/4.50  
9.30/4.50  
10.00/5.7  
10.00/5.7  
10.00/5.7  
9.0/9.3  
9.0/9.3  
9.0/9.3  
10.00  
32.1/16.4  
15.6/8.7  
12.3/7.4  
34.8/19.5  
17.0/10.3  
13.8/8.1  
253/124  
113/59.6  
85/49.4  
278/156  
124/75  
92/54  
225/253  
114/113  
80/85  
278  
15  
.50  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
17½  
20  
3500/3450 30.4/32.6  
3500/3450 16.1/16.8  
3500/3450 12.5/13.4  
3450  
3450  
3450  
36.2  
17.7  
14.3  
25  
10.00  
124  
92  
575  
10.00  
Notes:  
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.  
2. HP for each compressor.  
Table ED-13 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat)  
Option (Downflow Only)  
CompressorMotors  
Condenser Fan Motors  
Unit  
Amps1  
Amps1  
Tons  
12½  
ModelNo.  
No.  
Volts  
Phase  
HP2  
RPM  
RLA  
LRA  
No.  
Phase  
HP  
FLA  
LRA  
TCD151C3  
TCD151C4  
TCD151CW  
TCD181C3  
TCD181C4  
TCD181CW  
TCD241C3  
TCD241C4  
TCD241CW  
2
2
2
2
2
2
2
2
2
208-230  
460  
575  
208-230  
460  
575  
208-230  
460  
575  
3
3
3
3
3
3
3
3
3
5.7/5.7  
5.7/5.7  
5.7/5.7  
8.3/5.7  
8.3/5.7  
8.3/5.7  
9.0/9.3  
9.0/9.3  
9.0/9.3  
3450  
3450  
3450  
3450  
3450  
3450  
18.6  
9.7  
7.6  
27.4/19.0  
13.8/10.1  
10.7/7.9  
156  
75  
54  
208/156  
100/75  
68/54  
225/253  
114/113  
80/85  
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
.50  
.50  
.50  
.50  
.50  
3.2  
1.6  
1.3  
3.2  
1.6  
1.3  
5.5  
2.9  
2.0  
8.8  
3.8  
3.2  
8.8  
3.8  
3.2  
18.3  
9.3  
5.7  
15  
.50  
3500/3450 30.1/31.7  
3500/3450 15.6/16.2  
3500/3450 12.1/13.0  
1.00  
1.00  
1.00  
20  
Notes:  
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.  
2. HP for each compressor.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-14 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized  
StandardEvaporatorFanMotor  
OversizedEvaporatorFanMotor  
Amps  
FLA LRA  
16.7 109.8  
Unit  
Amps  
Tons  
12½  
ModelNo.  
No.  
Volts  
Phase  
HP  
FLA  
LRA  
No. Volts  
Phase  
HP  
TC*150D3,TC*151C3  
TC*150D4,TC*151C4  
TC*150DW,TC*151CW  
TC*150DK  
1
1
1
1
208-230  
460  
575  
3
3
3
3
3.00  
3.00  
3.00  
5.0  
10.6  
4.8  
3.9  
9.2  
81.0  
40.5  
31.0  
66.5  
1
1
208-230  
460  
3
3
5.00  
5.00  
5.00  
7.6  
6.1  
54.9  
41.6  
1
575  
3
380  
TC*180B3,TC*181C3  
TC*180B4,TC*181C4  
TC*180BW,TC*181CW  
TC*180BK  
1
1
1
1
208-230  
460  
575  
3
3
3
3
3.00  
3.00  
3.00  
5.0  
10.6  
4.8  
3.9  
9.2  
81.0  
40.5  
31.0  
66.5  
1
1
1
208-230  
460  
575  
3
3
3
5.00  
5.00  
5.00  
16.7 109.8  
7.6  
6.1  
54.9  
41.6  
15  
380  
TC*210C3,TC*211C3  
TC*210C4,TC*211C4  
TC*210CW,TC*211CW  
TC*210CK  
1
1
1
1
208-230  
460  
575  
3
3
3
3
5.00  
5.00  
5.00  
7.5  
16.7  
7.6  
6.1  
109.8  
54.9  
41.6  
83.5  
1
1
1
208-230  
460  
575  
3
3
3
7.50  
7.50  
7.50  
24.2 120.4  
11.0  
9.0  
74.0  
60.0  
17½  
20  
380  
13.3  
TC*240B3,TC*241C3  
TC*240B4,TC*241C4  
TC*240BW,TC*241CW  
TC*240BK  
1
1
1
1
208-230  
460  
575  
3
3
3
3
5.00  
5.00  
5.00  
7.5  
16.7  
7.6  
6.1  
109.8  
54.9  
41.6  
83.5  
1
1
1
208-230  
460  
575  
3
3
3
7.50  
7.50  
7.50  
24.2 120.4  
11.0 74.0  
9.0  
60.0  
380  
13.3  
TC*300B3,TC*301C3  
TC*300B4,TC*301C4  
TC* 300BW,TC*301CW  
TC*300BK  
1
1
1
1
208-230  
460  
575  
3
3
3
3
7.50  
7.50  
7.50  
7.5  
24.2  
11.0  
9.0  
120.4  
74.0  
60.0  
83.5  
25  
380  
13.3  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-15 — Electrical Characteristics — Power Exhaust Accessory  
Accessory  
Operating  
Voltage  
208-230  
460  
\Amps  
LRA  
Tons  
Phase  
HP  
3/4  
3/4  
3/4  
RPM  
1040  
1040  
1040  
FLA  
6.6  
3.2  
2.1  
1,2  
12½  
1
1
1
13.5  
8.4  
15, 17½  
20, 25  
Notes:  
1. 12½ Ton Standard Unit.  
575  
5.2  
2. 12½ Ton High Efficiency Unit.  
RT-PRC002-EN  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Jobsite  
Connections  
Zone Sensors —Typical Number OfWires  
DISCONNECT  
SWITCH  
(BYOTHERS)  
A— ManualChangeover ....................................... 4  
Manual/AutoChangeover ............................... 5  
Manual/AutoChangeoverwith  
StatusIndicationLED’s ........................... 10  
Programmable Night Setback with  
ZONESENSORS  
StatusIndicationLED’s ............................. 7  
ROOFTOP  
UNIT  
B— 3 Power Wires + 1 Ground Wire (three phase)  
2 Power Wires + 1 Ground Wire (single phase)  
For specific wiring information, see the installation instructions.  
All wiring except power wires is low voltage.  
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.  
RT-PRC002-EN  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(12½-25 Ton)  
RT-PRC002-EN  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(12½-25 Ton)  
Typical wiring diagram. For specific  
wiring, see individual Service Facts.  
RT-PRC002-EN  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(12½-25 Ton)  
RT-PRC002-EN  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(12½-25 Ton)  
RT-PRC002-EN  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½Ton) High Efficiency  
Dimensional  
Data  
(12½, 15, 17½Ton)  
Standard Efficiency  
All dimensions are in inches.  
Note: Duct flanges mount 7-7/16" down  
inside the curb on the 1½" curb flanges.  
See recommended duct dimensions on  
the next page.  
Roofcurb is intended for downflow use  
only.  
Downflow Unit Clearance  
RT-PRC002-EN  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½Ton) High Efficiency  
Dimensional  
Data  
(12½, 15, 17½Ton)  
Standard Efficiency  
All dimensions are in inches.  
1"  
Downflow Duct Connections — Field Fabricated  
17 7/8"  
59 7/16"  
26 5/16"  
1"  
52 1/2"  
1 1\2"  
PERIMETER  
CURB FLANGE  
14 1/16"  
7 7/16"  
RETURN  
SUPPLY  
Note:  
Duct flanges mount 7-7/16" down inside  
the curb on the 1½" curb flanges.  
Roofcurb is intended for downflow use  
only.  
Horizontal Unit Supply/Return and Unit Clearance  
RT-PRC002-EN  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15-25Ton) High Efficiency  
Dimensional  
Data  
(20, 25Ton)  
Standard Efficiency  
All dimensions are in inches.  
Note:  
Duct flanges mount 7-7/16" down inside  
the curb on the 1½" curb flanges. See  
recommended duct dimensions on the  
next page.  
Roofcurb is intended for downflow use  
only.  
Downflow Unit Clearance  
RT-PRC002-EN  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(15-25Ton) High Efficiency  
Dimensional  
Data  
(20, 25Ton)  
Standard Efficiency  
All dimensions are in inches.  
1"  
Downflow Duct Connections — Field Fabricated  
19 5/16"  
73 7/16"  
26 5/16"  
1"  
66 1/2"  
1 1\2"  
PERIMETER  
CURB FLANGE  
14 1/16"  
7 7/16"  
RETURN  
SUPPLY  
Note: Duct flanges mount 7-7/16" down  
inside the curb on the 1½" curb flanges.  
Roofcurb is intended for downflow use  
only.  
Horizontal Unit Supply/Return and Unit Clearance  
RT-PRC002-EN  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(12½-25 Ton)  
Accessories  
All dimensions are in inches.  
Note:  
When applying economizer to horizontal units,  
connecting ductwork must be run full size to  
allow proper operation of Economizer Damper.  
Table DD-1  
Unit  
Model#  
A
B1  
C2  
TC*150, 151-180, 210  
TC*181,211-301  
Notes:  
171/2  
53¾  
64¾  
36  
39  
191/2  
1. Horizontal dimension only. Downflow economizer is width  
of end panel.  
2. Power exhaust is applied on downflow economizer only.  
RT-PRC002-EN  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Factory Installed  
Options (FIOPS)  
All dimensions are in inches.  
Table DD-2  
Unit  
Model#  
A
423/  
291/2  
B
483/  
56  
C
31  
381/2  
TCD150, 151, 180, 210  
TCD181,211-301  
8
8
RT-PRC002-EN  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
Factory Installed  
Options (FIOPS)  
Disconnect Switch  
or Circuit Breaker  
Fan Failure Switch  
Clogged Filter Switch  
Powered or Unpowered  
Convenience Outlet  
Trane Communication Interface  
Hinged Access Door  
Black Epoxy Coated  
Outdoor Coils  
Hinged Access Door  
Through the Base Electrical  
High Pressure Cut Out  
Supply and/or Return Smoke Detectors  
RT-PRC002-EN  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(12½-25 Ton)  
Table DD-3 — Standard Efficiency Units  
Condensate  
CondensateDrainLocation  
Downflow Horizontal  
Tons  
DownflowOnly  
Drain Size  
A
267/  
267/  
B
221/  
283/  
C
1811/  
1915/  
D
F
41/  
41/  
G
627/  
765/  
H
5411/  
6811/  
E
J
255/  
263/  
E
K
6
12½, 15, 17½  
20, 25  
16  
16  
2
4
16  
16  
41/  
4
4
16  
16  
16  
16  
1NPT  
1NPT  
8
4
41/  
4
4
53/  
8
Table DD-4 — High Efficiency Units  
Condensate  
Drain Size  
CondensateDrainLocation  
Downflow Horizontal  
Tons  
DownflowOnly  
D
A
B
C
F
G
H
E
J
E
K
12½  
15-25  
267/  
267/  
16  
16  
221/  
283/  
2
4
1811/  
16  
41/  
4
4
41/  
4
4
627/  
765/  
16  
16  
5411/  
6811/  
16  
16  
1NPT  
1NPT  
255/  
263/  
8
4
6
1915/  
16  
41/  
41/  
53/  
8
RT-PRC002-EN  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(12½-25 Ton)  
Weights  
Table W-1 — Accessory Net Weights (Lbs)1, 7  
Oversized  
Motor  
Adder  
High5  
Static  
Drive  
Low5  
Static  
Drive  
Economizer  
Net  
Outside Air Damper  
Manual Motorized  
Power  
Exhaust4  
Roof  
Curb4  
ModelNo.  
TCD150D, 180B  
TCD121,151C,TCD210C  
65  
32  
60  
95  
205  
5
2
2
TCD240B  
TCD181,211,241C  
80  
80  
32  
32  
75  
75  
95  
95  
235  
235  
5
2
2
TCD300B.301C  
N/A  
N/A  
TCH150D, 180B, 210C  
TCH121,151C  
50  
32  
60  
5
2
2
TCH240B  
TCH181,211,241C  
65  
65  
32  
32  
75  
75  
5
2
2
TCH300B,301C  
N/A  
N/A  
Table W-1 Continued  
Electric Heaters  
27-36 KW  
Unit  
ModelNo.  
AllZone  
Sensors  
6-23 KW  
54 KW  
72 KW  
3
3
3
3
240/480V2  
240/480V2  
240/480V2  
38/32  
240/480V2  
TCD150D, 180B, 210C  
TCD121,151,181C  
1
28/216  
31/27  
33/27  
TCD240B  
1
40/32  
43/34  
TCD211,241C  
TCD300B,301C  
1
1
28/216  
33/27  
31/27  
40/32  
38/32  
43/34  
TCH150D, 180B, 210C  
TCH121,151,181C  
TCH240B  
TCH211,241C  
1
1
33/27  
33/27  
40/32  
40/32  
43/34  
43/34  
TCH300B,301C  
Notes:  
1. Net weight should be added to unit weight when ordering factory installed accessories.  
2. For 600V heaters net weights are same as 480V heaters.  
3. To estimate shipping weight add 5 lbs to net weight.  
4. Downflow only.  
5. Not available on all models (See Fan Performance tables for specific models).  
6. 9 - 23 KW Heaters not available for TC*210C.  
7. TC*150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.  
This is provided in compliance with ARI certification program.  
RT-PRC002-EN  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table W-2 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)  
Unit  
ModelNo.  
MaximumWeights(Lbs)  
Corner Weights (Lbs)1  
Center of Gravity (In.)  
Tons  
12½  
15  
Shipping2  
1687/1820  
1866/2361  
2022/2380  
2372/2490  
2365/2475  
Net  
A
B
C
D
Length  
46/45  
42/52  
46/53  
51/53  
53/53  
Width  
29/30  
28/35  
29/35  
34/34  
33/34  
TC*150D/TC*151C  
TC*180B/TC*181C  
TC*210C/TC*211C  
TC*240B/TC*241C  
TC*300B/TC*301C  
1319/1452  
1498/1902  
1654/1921  
1913/2031  
1906/2016  
446/485  
547/643  
565/643  
679/697  
661/695  
339/360  
358/477  
425/495  
482/528  
507/524  
230/259  
234/333  
285/341  
312/348  
320/343  
303/348  
359/447  
378/442  
440/458  
418/454  
17½  
20  
25  
Notes:  
1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support.  
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.  
*Indicates both downflow and horizontal units.  
RT-PRC002-EN  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3  
Accessory  
High Efficiency Motors4  
Weight  
49  
Unit Model Number  
TC*150-181 standard size motor  
TC*210-241 standard size motor  
TC*150-181 oversize motor  
36  
0
TC*210-241 oversize motor  
TC*300-301 standard size motor  
Hinged Doors  
27  
38  
23  
5
AllTC* units  
AllTC* units  
AllTC* units  
Powered Convenience Outlet  
Through the Base Electrical  
Unit Mounted Circuit Breaker  
AllTC* units except those with 54&72 kW heaters  
& 208/230V  
10  
5
All TC* units with 54&72 kW heaters & 208/230V  
Unit Mounted Disconnect  
AllTC* units except those with 54&72 kW heaters  
& 208/230V  
10  
AllTC* units with 54&72 kW heaters & 208/230V  
Smoke Detectors  
Supply/Return  
5
AllTC* units  
Tool-less Hail Guard  
38  
43  
TC*150,151,180,210  
TC*181,211,240,241,300,301  
Novar 2024  
Novar 3051  
Notes:  
7
5
AllTC* units  
AllTC* units  
1. Weights for FIOP accessories not listed are >5 lbs.  
2. Net weight should be added to unit weight when ordering factory installed accessories.  
3. See Table W-1 for standard factory installed economizer and oversized motors.  
4. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high  
efficiency motors are in addition to the standard motor weight.  
RT-PRC002-EN  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
General  
UnitTop  
corrosion resistant steel components. A  
forced combustion blower shall supply  
premixed fuel to a single burner ignited  
by a pilotless hot surface ignition system.  
In order to provide reliable operation, a  
negative pressure gas valve shall be  
used that requires blower operation to  
initiate gas flow. On an initial call for heat,  
the combustion blower shall purge the  
heat exchanger 45 seconds before  
ignition. After three unsuccessful ignition  
attempts, the entire heating system shall  
be locked out until manually reset at the  
thermostat. Units shall be suitable for use  
with natural gas or propane (field  
The units shall be dedicated downflow or  
horizontal airflow.The operating range  
shall be between 115°F and 0°F in cooling  
as standard from the factory for all units.  
Cooling performance shall be rated in  
accordance with ARI testing procedures.  
All units shall be factory assembled,  
internally wired, fully charged with R-22,  
and 100 percent run tested to check  
cooling operation, fan and blower rotation  
and control sequence, before leaving the  
factory.Wiring internal to the unit shall be  
colored and numbered for simplified  
identification. Units shall be UL listed and  
labeled, classified in accordance to UL  
1995/CAN/CSA No. 236-M90 for Heat  
Pumps. Canadian units shall be CSA  
Certified.  
The top cover shall be one piece, or  
where seams exist, double hemmed and  
gasket sealed to prevent water leakage.  
Filters  
Two inch standard filters shall be factory  
supplied on all units. Optional two inch  
pleated media filters shall be available.  
Compressors  
All units shall have direct-drive, hermetic,  
scroll type compressors with centrifugal  
type oil pumps. Motor shall be suction  
gas-cooled and shall have a voltage  
utilization range of plus or minus 10  
percent of nameplate voltage. Internal  
overloads shall be provided with the  
scroll compressors. All models shall have  
crankcase heaters, low and high pressure  
controls as standard.  
installed kit) and shall also comply with  
California requirements for low NOx  
emissions.The 12½-25 tons shall have  
two stage heating.  
Casing  
Outdoor Fans  
Refrigerant Circuits  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
The outdoor fan shall be direct-drive,  
statically and dynamically balanced,  
draw-through in the vertical discharge  
position.The fan motor(s) shall be  
permanently lubricated and shall have  
built-in thermal overload protection.  
Each refrigerant circuit shall have  
independent fixed orifice or thermostatic  
expansion devices, service pressure  
ports, and refrigerant line filter driers  
factory installed as standard. An area  
shall be provided for replacement suction  
line driers.  
weather-resistant baked enamel finish.  
Unit’s surface shall be tested 500 hours in  
a salt spray test in compliance with ASTM  
B117. Cabinet construction shall allow for  
all maintenance on one side of the unit. In  
order to ensure a water and air tight seal,  
service panels shall have lifting handels  
and no more thatn three screws to  
remove. All exposed vertical panels and  
top covers in the indoor air section shall  
be insulated with a 1/2 inch, 1 pound  
density foil-faced, fire-resistant,  
permanent, odorless, glass fiber material.  
The base of the downflow unit shall be  
insulated with 1/2 inch, 1 pound density  
foil-faced, closed-cell material.The  
downflow units base pan shall have no  
penetrations within the perimeter of the  
curb other than the raised 11/8 inch high  
supply/return openings to provide an  
added water integrity precaution, if the  
condensate drain backs up.The base of  
the unit shall have provisions for forklift  
and crane lifting.  
Indoor Fan  
Units above shall have belt driven, FC  
centrifugal fans with adjustable motor  
sheaves. Units with standard motors  
shall have an adjustable idler-arm  
assembly for quick-adjustment of fan  
belts and motor sheaves. All motors shall  
be thermally protected. Oversized motors  
shall be available for high static  
application. All indoor fan motors meet  
the U.S. Energy Policy Act of 1992  
(EPACT).  
Evaporator and Condenser Coils  
Internally finned, 3/8" copper tubes  
mechanically bonded to a configured  
aluminum plate fin shall be standard.  
Coils shall be leak tested at the factory to  
ensure the pressure integrity.The  
evaporator coil and condenser coil shall  
be leak tested to 200 psig and pressure  
tested to 450 psig. All dual compressor  
units shall have intermingled evaporator  
coils. Sloped condensate drain pans are  
standard. Patent-pending 1+1+1  
condenser coil, permanently gapped for  
easy cleaning is available.  
Gas Heating Section  
The heating section shall have a drum  
and tube heat exchanger design using  
RT-PRC002-EN  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Controls  
Hinged Access Doors  
Through the Base Electrical with Circuit  
Breaker  
This option is a thermal magnetic, molded  
case, HACR Circuit Breaker with  
Unit shall be completely factory wired  
with necessary controls and contactor  
pressure lugs or terminal block for power  
wiring. Unit shall provide an external  
location for mounting a fused disconnect  
device. ReliaTel controls shall be provided  
for all 24 volt control functions.The  
resident control algorithms shall make all  
heating, cooling, and/or ventilating  
decisions in response to electronic signals  
from sensors measuring indoor and  
outdoor temperatures.The control  
algorithm maintains accurate  
Sheet metal hinges are available on the  
Filter/Evaporator Access Door and the  
Compressor/Control Access Door.This  
option is available on all downflow  
models.  
provisions for through the base electrical  
connections.The circuit breaker will be  
installed in a water tight enclosure in the  
unit with access through a swinging door.  
Factory wiring will be provided from the  
switch to the unit high voltage terminal  
block.The circuit breaker will provide  
overcurrent protection, be sized per NEC  
and UL guidelines, and be agency  
recognized by UL/CSA.This option is  
available on all downflow models.  
High Efficiency Motors  
This option is available with efficiency  
ratings from 86.5 up to 91.0. It is not  
available for all models.  
High Pressure Cutout  
This option is offered for units that do not  
have High Pressure cutout as standard.  
temperature control, minimizes drift from  
set point, and provides better building  
comfort. A centralized control shall  
provide anti-short cycle timing and time  
delay between compressors to provide a  
higher level of machine protection.  
Powered or Unpowered Convenience  
Outlet  
Through the Base ElectricalWith  
Disconnect Switch  
This option is a GFCI, 120v/15amp, 2 plug,  
convenience outlet, either powered or  
unpowered.When the convenience outlet  
is powered, a service receptacle  
disconnect will be available.The  
convenience outlet is powered from the  
line side of the disconnect or circuit  
breaker, and therefore will not be  
affected by the position of the disconnect  
or circuit breaker.This option can only be  
ordered when theThrough the Base  
Electrical with either the Disconnect  
Switch, or Circuit Breaker, option is  
ordered.This option is available on all  
downflow models.  
Three-pole, molded case, disconnect  
switch with provisions for through the  
base electrical connections are available.  
The disconnect switch will be installed in  
the unit in a water tight enclosure with  
access through a swinging door. Factory  
wiring will be provided from the switch to  
the unit high voltage terminal block.The  
switch will be UL/CSA agency recognized.  
Note:The disconnect switch will be sized  
per NEC and UL guidelines but will not be  
used in place of unit overcurrent  
Defrost Controls  
Adaptive demand defrost shall be  
provided to permit defrost wherever coil  
icing conditions begin to significantly  
reduce unit capacity.  
Factory Installed Options  
Black Epoxy Coated Pre-Coated Coils  
The black epoxy coils have a thermoset  
vinyl coating that is bonded to the  
aluminum fin stock prior to the fin-  
stamping process.The pre-coated coils  
are an economical option for protection in  
mildly corrosive environments.  
protection.This option is available on all  
downflow models.  
Supply and/or Return Air Smoke  
Detector  
Through the Base UtilitiesAccess  
An electrical service entrance shall be  
provided allowing electrical access for  
both control and main power connections  
inside the curb and through the base of  
the unit. Option will allow for field  
With this option installed, if smoke is  
detected, all unit operation will be shut  
down. Reset will be manual at the unit.  
Return Air Smoke Detectors require  
minimum allowable airflow when used  
with certain models. See the Installation,  
Operation, and Maintenance (IOM)  
manual for the models affected and the  
minimum allowable airflow required.This  
option is available on all downflow  
models.  
Dehumidification Option  
The dehumidification (hot gas reheat)  
option shall provide increased  
dehumidification.The option shall consist  
of a hot-gas reheat coil located on the  
leaving air side of the evaporator coil  
prepiped and circuited. Low pressure  
switch(es) and thermostatic expansion  
valve(s)TXV are standard. Frostat™,  
ReliaTel options module, and 2”pleated  
filters are required but not standard.They  
must be ordered and configured  
separately.  
installation of liquid-tight conduit and an  
external field installed disconnect switch.  
Two-Inch Pleated Filters  
Two inch pleated media filters shall be  
available on all models.  
RT-PRC002-EN  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Electric Heaters  
Reference or Comparative Enthalpy  
Reference Enthalpy is used to measure  
and communicate outdoor humidity.The  
unit receives and uses this information to  
provide improved comfort cooling while  
using the economizer. Comparative  
Enthalpy measures and communicates  
humidity for both outdoor and return air  
conditions, and return air temperature.  
The unit receives and uses this  
Factory or Field Installed  
Options  
Clogged Filter/Fan Failure Switch  
A dedicated differential pressure switch is  
available to achieve active fan failure  
indication and/or clogged filter indication.  
These indications will be registered with  
either a zone sensor with status indication  
lights or an Integrated Comfort™ System.  
Electric heat modules shall be available  
for installation within the basic unit.  
Electric heater elements shall be  
constructed of heavy-duty nickel  
chromium elements internally delta  
connected for 240 volt, wye connected  
for 480 and 600 volt. Staging shall be  
achieved through ReliaTel. Each heater  
package shall have automatically reset  
high limit control operating through  
heating element contactors. All heaters  
shall be individually fused from the  
factory, where required, and shall meet  
all NEC and CEC requirements when  
properly installed. Power assemblies  
shall provide single-point connection.  
Electric heat modules shall be UL listed or  
CSA certified. If ordering theThrough the  
Base Electrical option with an Electric  
Heater, the heater must be factory  
installed.  
information to maximize use of  
Differential Pressure Switches  
economizer cooling, and to provide  
maximum occupant comfort control.  
Reference or Comparative Enthalpy  
option shall be available when a factory  
or field installed Downflow Economizer is  
ordered.This option is available on all  
downflow models.  
These options allow for individual fan  
failure and dirty filter indication.The fan  
failure switch will disable all unit functions  
and “flash” the Service LED on the zone  
sensor.The dirty filter switch will light the  
Service LED on the zone sensor and will  
allow continued unit operation.  
Tool-less Hail Guards  
Discharge Air Sensing Kit  
Tool-less, hail protection quality coil  
guards are available for condenser coil  
protection.  
This kit provides true discharge air  
sensing in heating models.This sensor is  
a status indicator readable through  
Tracer™orTracker™.The kit is functional  
only with the ReliaTel Options Module.  
Frostat  
Trane Communication Interface  
This factory or field-installed option shall  
be provided to interface ReliaTel™  
controlled units with theTrane Integrated  
ComfortTM systems.  
This option is to be utilized as a safety  
device.The Frostat opens when  
temperatures on the evaporator coil fall  
below 10°F. The temperature will need to  
rise to 50°F before closing.This option  
should be utilized in low airflow or high  
outside air applications.  
Economizer - Downflow  
The assembly includes fully modulating  
0-100 percent motor and dampers,  
barometric relief, minimum position  
setting, preset linkage, wiring harness  
with plug, fixed dry bulb and spring return  
actuator.The barometric relief damper  
shall be standard with the downflow  
economizer and shall provide a pressure  
operated damper that shall be gravity  
closing and shall prohibit entrance of  
outside air during the equipment off”  
cycle. Solid state enthalpy and differential  
enthalpy control shall be field-installed  
LonTalk® Communications Interface  
The LonTalk communications interface,  
when installed in aVoyager unit, allows  
the unit to communicate as aTracer™LCI-  
V device or directly with generic LonTalk  
Network Building Automation System  
Controls.  
Oversized Motors  
Oversized motors shall be available for  
high static applications.  
RT-PRC002-EN  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Powered Exhaust  
Field Installed Options  
CO2 Sensing  
The powered exhaust shall provide  
exhaust of return air, when using an  
economizer, to maintain better building  
pressurization.  
The CO2 sensor has the ability to monitor  
space occupancy levels within the  
building by measuring the parts per  
million of CO2 (Carbon Dioxide) in the air.  
As the CO2 levels increase, the outside air  
damper modulates to meet the CO2  
space ventilation requirements.  
Roof Curb - Downflow  
The roof curb shall be designed to mate  
with the downflow unit and provide  
support and a water tight installation  
when installed properly.The roof curb  
design shall allow field-fabricated  
rectangular supply/return ductwork to be  
connected directly to the curb. Curb  
design shall comply with NRCA  
Digital Display Zone Sensor  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone sensors.This sensor  
includes a digital display of set point  
adjustment and space temperature in F  
(Fahrenheit) or C (Celsius). Includes FAN  
and SYSTEM buttons (supports the  
service functions of the standard sensor).  
E-squared memory stores last  
requirements. Curb shall be shipped  
knocked down for field assembly and  
shall include wood nailer strips.  
Economizer - Horizontal  
The horizontal economizer shall contain  
the same features as the downflow  
economizer with the exception of  
barometric relief.  
programmed set points. Requires 24VAC  
(Volts AC).This sensor should be utilized  
with ReliaTel™ controls.  
Remote Potentiometer  
DualThermistor Remote Zone Sensor  
This sensor will allow the customer to  
reduce the total number of remote  
sensors to obtain space temperature  
averaging. This sensor should be utilized  
with ReliaTel controls.  
The minimum position setting of the  
economizer shall be adjusted with this  
accessory.  
Ventilation Override Accessory  
With theVentilation Override Accessory  
installed, the unit can be set to transition  
up to 3 different pre-programmed  
sequences for Smoke Purge,  
Pressurization, and Exhaust.The  
transition occurs when a binary input on  
the RTOM is closed (shorted).This would  
typically be a hard wired relay output  
from a smoke detector or fire control  
panel.  
High Static Drive  
The high static drive option shall allow the  
standard motor on the 12½ and 20 ton  
units to operate with improved external  
static capabilities.  
Manual Outside Air Damper  
The rain hood and screen shall provide  
up to 25 percent outside air.  
Motorized Outside Air Dampers  
Zone Sensors  
Manually set outdoor air dampers shall  
provide up to 50 percent outside air. Once  
set, outdoor air dampers shall open to set  
position when indoor fan starts.The  
damper shall close to the full closed  
position when indoor fan shuts down.  
This option shall be provided to interface  
with the Micro equippedVoyagers and  
shall be available in either manual,  
automatic, programmable with night  
setback, with system malfunction lights or  
remote sensor options.  
RT-PRC002-EN  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File Number  
RT-PRC002-EN  
PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-10-04  
PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-09-04  
09-04 Webb/Mason 10-04 Electronic Only  
Supersedes  
Trane  
Stocking Location  
A business ofAmerican Standard Companies  
For more information contact your local dealer  
(distributor), local district office, or e-mail us at  
Trane has a policy of continuous product and product data improvement and reserves the right to change design  
and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Toastess Kitchen Grill TSG 380 User Manual
Toshiba DVD Player SD 185 User Manual
Toshiba Heat Pump A09 01P User Manual
TRENDnet Security Camera TVIP252P User Manual
Tripp Lite Network Cables N201 001 WH User Manual
Tripp Lite TV Cables P166 001 P User Manual
Tunturi Treadmill J 440 User Manual
Uniden Scanner UBC93XLT User Manual
Vestax DJ Equipment PCV 002 User Manual
Volvo Automobile pmn User Manual