Toshiba Heat Pump A09 01P User Manual

FILE NO : A09-01P  
Quick reference  
AIR TO WATER HEAT PUMP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 3  
Notes on System Design  
• The input water temperature to the Hydro Unit must be 55°C or less.  
Especially, be careful when there is an external heating source such as a boiler.  
When hot water over 55°C returns, it may result in a failure of the unit or water leakage.  
• The flow rate of the circulating water must meet the following range:-  
11 and 14 kW  
8 kW  
17.5 L/minute or more  
13 L/minute or more  
If the flow rate becomes less than the minimum, the protective device is activated to stop operation.  
Ensure the flow rate with a bypass valve, etc. when you use a flow rate valve for the Hydro Unit.  
• Do not drive water by power other than the pump built in the Hydro Unit.  
• The backup heater operates supplementary to exert a prescribed capacity when the heat pump  
cannot exert its capacity at a low outside temperature.  
• Install the Hydro Unit and water pipes in a place in which they do not freeze.  
• Make the water circuit closed. Never use it as an open circuit.  
• To prevent damage to the system during outdoor defrost the circulating water must be 20 litres  
or more. If total water amount is not enough, the unit may not function fully due to protective  
operation.  
Options required for each function  
Toshiba Supply  
Procure locally  
Part name  
Purpose  
Part name  
Model code  
Radiator(s),  
Space Heating  
-
-
-
Fan coil(s),  
Under floor heating  
Space Heating &  
Space Cooling  
(All Rooms)  
-
-
Fan coil(s) only  
Fan coil(s) plus  
Radiator(s)  
or Under floor heating  
Motorized 2-way  
valve  
Space Heating &  
Space Cooling  
(partly heating only)  
-
150L Hot water cylinder  
150L Hot water cylinder  
210L Hot water cylinder  
210L Hot water cylinder  
300L Hot water cylinder  
300L Hot water cylinder  
HWS-1501CSHM3-E  
HWS-1501CSHM3-UK  
HWS-2101CSHM3-E  
HWS-2101CSHM3-UK  
HWS-3001CSHM3-E  
HWS-3001CSHM3-UK  
Motorized 3-way  
valve  
Earth leakage breaker  
Domestic Hot Water  
2-zone control  
Motorized mixing  
valve  
Circulator pump  
Buffer tank  
-
-
Interlocking with  
boiler  
Interlocking with  
booster heater  
Output control board kit  
(1)  
TBC-PCIN3E  
-
Boiler  
-
Electric heater  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 4  
Installation Examples  
Space Cooling and Space Heating with Domestic Hot Water  
When both cooling and heating are used, install a 2-way valve (for cooling) to the pipe to the room  
for heating only.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 5  
Installation Examples (cont.)  
2-Zone Space Heating with Domestic Hot Water  
The following shows an example of the 2-zone temperature control.  
A buffer tank and a water pump are required for the 2-zone temperature control. This example is  
Heating only, if the Fan Coils are to be used for Cooling then a 2-Way valve must be fitted.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 6  
Hydro Unit – Exploded View  
1 : Expansion vessel  
2 : Hi pressure switch (4.15 MPa)  
3 : Temperature sensor (for Heat pump outlet -TWO)  
4 : Pressure sensor  
5 : Heat exchanger  
6 : Flow switch (13.0 L/min 17.5 L/min)  
7 : Temperature sensor (for refrigerant -TC)  
8 : Temperature sensor (for water inlet -TWI)  
9 : Drain nipple  
10 : Water inlet connection  
11 : Refrigerant liquid connection  
12 : Air relief valve  
13 : Pressure relief valve (0.3 MPa (3 bar))  
14 : Thermal protector (auto)  
15 : Temperature sensor (for water outlet THO)  
16 : Thermal protector (Single operation)  
17 : Water pump  
18 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3)  
19 : Manometer  
20 : Water outlet connection  
21 : Refrigerant gas connection  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 7  
Refrigerant Piping  
Refrigerant Pipe Lengths and Height  
The length and height of the refrigeration pipe must be within the following values.  
Minimum Pipe Length  
HWS-802H-E :  
HWS-1102H-E :  
HWS-1402H-E :  
5 m  
3 m  
3 m  
Maximum Pipe Length and Height  
H: Max. ±30 m (above or below)  
L: Max. 30 m  
Note  
The maximum pipe length cannot be increased using additional  
refrigerant.  
Refrigeration and Water Cycle Diagrams  
Hydro Unit  
Pressure  
relief  
valve  
Air vent valve  
Pressure  
Gauge  
Expansion vessel  
THO  
Sensor  
Thermal  
Protector  
Hi_P_Switch  
Pump  
TWO  
Sensor  
Water Out  
(1 1/4")  
Refrigerant pipe  
at gas side  
(Outer ø15.88)  
Backup heater  
P_Sensor  
TWI  
Sensor  
Flow_Switch  
TC  
Sensor  
Refrigerant pipe  
at liquid side  
(Outer ø9.52)  
Water IN  
(1 1/4")  
Water Heat exchanger  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 8  
Outdoor Unit  
HWS-802H-E  
HWS-1102H-E, 1402H-E  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 9  
Water Piping  
• Install water pipes according to the regulations of respective countries.  
• Install water pipes in a freeze-free place.  
• Make sure that water pipes have sufficient pressure resistance (The setting value of the pressure  
relief valve is 0.3 MPa).  
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.  
Water Connections  
Install a strainer with 30 to 40 meshes (procure locally) at  
the water inlet of the Hydro Unit.  
Install drain cocks (procure locally) for water charge and  
discharge at the lower part of the Hydro Unit.  
Water Piping Limitations  
Design the water pipe length within the QH  
characteristics of the pump (flow-rate and pump  
head).  
The maximum height difference for the water pipes is  
7 metres.  
Piping to hot water tank (option)  
Water supplied to the hot water cylinder is branched by a  
motorized 3-way valve (procured locally).  
Connect the hot water cylinder to port A (open when  
energized) of the valve.  
Piping to 2-zone operation (option)  
To perform 2-zone temperature control circulate water using another pump (procured locally)  
through a motorized mixing valve (procured locally) and a buffer tank (procured locally).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 10  
Checking water volume and initial pressure of expansion vessel  
The expansion vessel of the Hydro Unit has a capacity of 12 litres.  
The initial pressure of the expansion vessel is 0.1 MPa (1 bar).  
The suggested initial water charge is 0.2MPa (2 bar).  
The pressure of the safety valve is 0.3 MPa (3 bar).  
Verify whether the capacity of the expansion vessel is sufficient using the following expression. If  
the volume is insufficient, install an appropriate external expansion vessel.  
V
Action  
< 12 L  
Internal Expansion Vessel Size OK  
Internal Expansion Vessel Size too small.  
Install appropriate external expansion vessel  
> 12 L  
V:  
Necessary total vessel capacity (L)  
Ɛ:  
Water expansion coefficient at average hot water temperature  
Total water volume in the closed system (Do not include Hot Water Cylinder)  
System pressure at tank setting position (Mpa_abs*).  
(Pipe inner pressure during pump operation before heating device operates = water supply  
pressure)  
Vs:  
P1:  
P2:  
Maximum pressure used during operation at tank setting position (MPa_abs*).  
(= safety valve setting pressure)  
* The absolute pressure value (abs.) is obtained by adding the atmospheric pressure (0.1 MPa (1  
bar)) to the gauge pressure.  
Water temperature and expansion coefficient (Ɛ)  
Water temperature and expansion coefficient (Ɛ)  
Expansion rate  
Expansion rate  
Hot water temperature  
(°C)  
Hot water temperature  
(°C)  
(Ɛ)  
(Ɛ)  
0
4
5
0.0002  
0.0000  
0.0000  
0.0003  
0.0008  
0.0017  
0.0029  
0.0043  
0.0050  
0.0078  
0.0100  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95  
-
0.0121  
0.0145  
0.0171  
0.0198  
0.0229  
0.0258  
0.0292  
0.0324  
0.0961  
0.0967  
-
10  
15  
20  
25  
30  
35  
40  
45  
Example  
Maximum Hot Water temperature: 55°C, initial  
water charge: 0.2MPa and system volume: 200 L.  
The calculated Vessel capacity (V) is 11.6 L:-  
0.0145  
1
x
-
200  
(0.2+0.1)  
(0.3+0.1)  
11.6  
=
In this case V < 12 L therefore the internal  
expansion vessel is sufficient.  
There is no need to install an external expansion  
vessel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 11  
Pump operation / configuration  
Change Pump speed, so that water flow is always greater than the minimum flow rate. If water flow  
is lower than the minimum rate during operation, the unit detects error.  
Water charging  
Charge water until the pressure gauge shows 0.2 MPa (2 bar).  
Hydraulic pressure may drop when the trial run begins. In that case, add water.  
Air may enter if the charged hydraulic pressure is low.  
Loosen the purge valve cap by two turns to release air.  
Loosen the cap of the pressure relief valve to release air.  
Water may come out of the pressure relief valve.  
Release the air completely from the water circuit. Failure to do so  
may disable correct operation.  
Water quality  
The water used must satisfy EN directive 98/83 EC.  
Piping insulation  
It is recommended that insulation treatment be applied to all pipes. To perform optional cooling  
operation, apply insulation treatment of 20 t or more to all pipes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 12  
Electrical Connections  
E Box layout  
Terminal Block Connections  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 13  
Power Lines Schematic  
Control Lines Schematic  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 14  
Electrical supply / cable specifications  
Wiring specifications (power line)  
POWER  
SUPPLY  
Maximum  
current  
Installation  
fuse rating  
Connection  
destination  
Description  
Cable size  
14 kW 230 V ~ 50 Hz  
11 kW 230 V ~ 50 Hz  
8 kW 230 V ~ 50 Hz  
22.8 A  
22.8 A  
20.8 A  
25 A  
25 A  
25 A  
2.5 mm² or more  
2.5 mm² or more  
2.5 mm² or more  
1.5 mm² or more  
1.5 mm² or more  
2.5 mm² or more  
2.5 mm² or more  
1.5 mm² or more  
1.5 mm² or more  
L
N
Outdoor unit power  
Outdoor-Hydro  
,
1
L
2
N
3
,
,
,
,
,
3 kW 230 V ~ 50 Hz  
13 A  
16 A  
(TB02)  
Hydro inlet heater  
power  
L1  
N
L
L2  
L3  
6 kW 400 V 3N ~ 50 Hz 15 A (13 A x 2P) 25 A  
9 kW 400 V 3N ~ 50 Hz 23 A (13 A x 3P) 25 A  
(TB02)  
N
Hydro cylinder heater power 230 V ~ 50 Hz  
Hydro - cylinder  
12 A  
12 A  
16 A  
TB03)  
(
(TB03)  
,
,
1
2
Wiring specification (control line)  
Maximum  
current  
Maximum  
length  
Connection  
destination  
Description  
Line spec  
Cable Size  
7
8
9
3
4
,
,
,
,
3-way valve control  
2 line or 3 line  
100 mA  
12 m  
0.75 mm² or more  
(TB05)  
1
2
,
or  
2
Mixing valve control  
3 line  
2 line  
100 mA  
12 m  
0.75 mm² or more  
3
,
(TB04)  
C
A
1
D
B
2
2-zone thermo sensor  
Cylinder thermo sensor  
Second remote controller  
100 mA  
100 mA  
50 mA  
5 m  
0.75 mm² or more  
0.75 mm² or more  
0.75 mm² or more  
,
,
,
(TB06)  
(TB06)  
(TB07)  
2+GND (shield  
wire)  
5 m  
2 line  
50 m  
Control parts specifications  
Maximum  
current  
Description  
Power  
Type  
Motorized 3-way valve (for  
hot water)  
Spring return type Note: 3-wire SPST and SPDT type can be  
used by changing the function code.  
AC 230 V 100 mA  
Motorized 2-way valve (for  
cooling)  
AC 230 V 100 mA  
AC 230 V 100 mA  
spring return type (normally open )  
Motorized mixing valve type  
1 (for 2-zone)  
60 sec 90º. SPDT type Note: SPST and 20 to 240 sec type  
can be used by changing the function code.  
Output line specifications  
Maximum Max  
Maximum  
length  
Description  
Output  
current  
voltage  
Interlocked with the Hydro Unit  
pump  
Output as required when outdoor  
air temperature is -20°C or less  
External pump No. 1  
External booster heater  
AC230V  
AC230V  
1 A  
12 m  
12 m  
1 A  
Non-  
0.5 A  
1 A  
AC230 V  
DC24 V  
AC230 V  
DC24 V  
AC230 V  
DC24 V  
AC230 V  
DC24 V  
12 m  
12 m  
12 m  
12 m  
12 m  
12 m  
12 m  
12 m  
Output as required when outdoor  
air temperature is -10°C or less  
Boiler control  
voltage  
contacts  
Non-  
voltage  
contacts  
Non-  
voltage  
contacts  
Non-  
voltage  
contacts  
0.5 A  
1 A  
ALARM Output  
Operation Output  
Defrost Output  
0.5 A  
1 A  
0.5 A  
1 A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 15  
Input line specifications  
Description  
Input  
Maximum length  
Emergency stop control  
Cylinder thermostat input  
Cooling thermostat input  
Heating thermostat input  
Non-voltage  
Non-voltage  
Non-voltage  
Non-voltage  
12 m  
12 m  
12 m  
12 m  
CAUTION  
Earthing arrangements  
The Hydro Unit and related equipment must be earthed in accordance with your local and national  
electrical regulations.  
It is essential that the equipment is earthed to prevent the electric shock and damage to the  
equipment.  
Electrical connection to hydro unit  
• Remove the front cover and the electrical box cover from the Hydro Unit.  
• The Hydro Unit power cable must be sized in accordance with refer to “Electrical supply/cable  
specifications”.  
• Connect the Hydro Unit power cable to Terminal 02 as shown below.  
Single Phase Units:  
Live conductor – Terminal L1  
Neutral conductor – Terminal L2  
Earth conductor – Earth terminal  
Phase 1 conductor – Terminal L1  
Phase 2 conductor – Terminal L2  
Phase 3 conductor – Terminal L3  
Neutral conductor – Terminal N  
Earth conductor – Earth  
Three Phase Units:  
• Ensure the Hydro Unit power cable is secured using the cable clamp fitted in the electrical box.  
• Ensure the Hydro Unit power cable connection terminals are tight.  
Outdoor unit to hydro unit electrical connection  
• Ensure electrical circuits are isolated before commencing work.  
• The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with refer to  
“Electrical supply/cable specifications”.  
• Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram above.  
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp  
fitted in the electrical box.  
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 16  
Electrical connection for external booster heater  
CAUTION  
The maximum current available from the booster heater output is 1 A. Do not connect the  
booster heater directly to Terminal Block 05 on the Hydro Unit. The AC230 V 1 A output  
from the Hydro Unit must only be used to energize an external contactor (Supplied locally).  
• The booster heater can be installed only for room heating and cannot be used for hot water  
supply.  
• Install the booster heater downstream of the 3-way valve on the indoor unit side.  
• The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during  
low ambient conditions.  
• The output from the Hydro Unit is only enabled when the outdoor air temperature is less than -  
20°C.  
• Ensure the external booster heater is installed and set up in accordance with all Local, National  
and International regulations.  
• Connect the coil, of the field supplied contactor, to terminals 5 & 6 on Terminal Block 05. The  
contactor will energize in the event of low ambient conditions.  
• A separate dedicated electrical supply must be used for the external booster heater. This must  
be connected through the contacts on the field supplied contactor (see diagram below):-  
Electrical connection for external additional pump (P2)  
CAUTION  
The maximum current available from the additional pump output is 1 A. Do not connect the  
additional pump directly to Terminal Block 05 on the Hydro Unit. The AC230 V 1 A output  
from the Hydro Unit must only be used to energize an external contactor (Supplied locally).  
• The Hydro Unit has the facility to connect an additional circulating pump, if required, into the  
heating or cooling system.  
• Install the external pump so that its motive power does not affect the internal pump.  
• The output for the pump is synchronized with the operation of the main circulating pump (P1)  
inside the Hydro Unit.  
• Connect the coil, of the field supply contactor, to terminals 1 & 2 on Terminal Block 05.  
• A separate dedicated electrical supply must be used for the additional pump. This must be  
connected through the contacts on the field supplied contactor (see diagram below):-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 17  
2-way valve (for cooling) connection  
Required Valve Specification:  
Electrical Specification: 230 V; 50 Hz; <100 mA  
Return Mechanism: 2-wire spring return.  
• The Hydro Unit has the facility to connect a 2-way valve to  
isolate Space Conditioning Units that do not perform cooling,  
when Cooling Mode is selected.  
• Connect the 2-way valve in accordance with the diagram  
(opposite):-  
3-way valve (diverter) connection  
Required Valve Specification:  
Electrical Specification: 230 V; 50 Hz; <100 mA  
Valve Diameters: Port A, Port B: Ø 1 1/4"  
Return Mechanism: 3 types of 3-way valve (diverter) can be used.  
Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board.  
Diverter Valve Description  
SW13-1  
OFF  
OFF  
Type 1  
Type 2  
Type 3  
2-wire spring return  
3-wire SPST  
3-wire SPDT  
ON  
Continuous operation of the valve motor at the fully open position is not recommended.  
• The 3-way diverter valve is used to select either domestic hot water or space heating.  
• Connect the 3-way diverter valve in accordance with the diagram below:-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 18  
3-way mixing valve connection  
Required Actuator Specification  
Electrical Specification:230 V; 50 Hz; <100 mA  
The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating  
system.  
• Connect the 3-way mixing valve in accordance with the diagrams below:-  
Hot water cylinder connection (optional)  
• Please refer to “Electrical supply/cable specifications” for fuse/cable size and for  
connection details.  
Electrical Connection (Hot Water Cylinder Electric Heater)  
• The electric heater, incorporated in the hot water cylinder, requires a separate supply to Hydro  
Unit.  
• Connect the hot water cylinder heater electrical supply in accordance with shown below:  
Live conductor: Terminal L on Terminal Block 03  
Neutral conductor: Terminal N on Terminal Block 03  
Earth Conductor: Earth terminal on Terminal Block 03  
• Connect the hot water cylinder heater to the Hydro Unit as shown below:  
Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03  
Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03  
Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03  
Electrical Connection (Hot Water Cylinder temperature Sensor)  
• Connect the hot water cylinder temperature sensor as shown below to terminals A & B on  
Terminal Block 06 in the Hydro Unit.  
• Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder,  
is connected to earth at both ends of the cable using the shield wire.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 19  
Setting DIP Switches on the Board  
in the Hydro Unit  
• Detach the front cover and the electric parts box cover of  
the Hydro Unit.  
• Set the DIP switches on the main board.  
Switch mode  
SW10  
Description  
Default setting  
Continuous operation  
Alternate  
Internal pump P1 operating  
mode  
1
3
OFF  
OFF  
ON  
ON  
HP synchronized  
Interlocked with the  
internal pump  
synchronized with P1.  
External P2 pump operation  
Continuous operation  
Switch mode  
SW11  
Description  
Default setting  
Alternate  
Internal backup heater  
operation  
1
Operate  
OFF  
ON  
Not operate  
Hot water cylinder heater  
operation  
2
3
Operate  
Operate  
OFF  
OFF  
ON  
ON  
Not operate  
Not operate  
Booster heater operation  
Switch mode  
SW12  
Description  
Default setting  
Default setting  
Alternate  
Invalid  
1
2
3
Hot water supply operation  
Zone 1 operation  
Valid  
OFF  
OFF  
OFF  
ON  
Valid  
Invalid  
ON  
ON  
Invalid  
Zone 2 operation  
Valid  
Switch mode  
SW13  
Description  
Alternate  
• 2-wire spring return type  
• 3-wire SPST type  
1
Type of motorized 3-way valve  
OFF  
ON  
3-wire SPDT type  
2
3
Interlocking with boiler  
Invalid  
OFF  
OFF  
ON  
ON  
Valid  
Auto restart for power failure  
Auto restart  
Manual restart  
Switch mode  
SW02  
Description  
Default setting  
Alternate  
4
Room thermostat  
Invalid  
OFF  
ON  
Valid  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 20  
Hydro Unit Remote Control  
Buttons and Functions  
1. TEMP. button:  
10. NIGHT button:  
Changes the set temperature for  
each operation mode (ZONE1/2 hot  
water) by 1°C step.  
Controls the night set back  
operation.  
2. SCHEDULE  
button:  
11. AUTO TEMP.  
button:  
Switches setting temperature  
automatically according to outside  
temperature. (Pressing this button  
long changes the mode to data  
setting mode).  
Sets the current time and  
scheduled weekly operation.  
3. TIME button:  
4. SET button:  
5. CL button:  
Changes time for current time  
setting and scheduled weekly  
operation setting with and ▲  
buttons.  
12. OPERATE  
MODE button:  
Selects ZONE1/2 operation mode  
(heating or cooling).  
13. ZONE1, 2  
button:  
Determines the entered current  
time setting and scheduled weekly  
operation setting.  
Turns on/off the zone (floor  
heating/radiator/FCU) operation.  
14. ANTI BACTERIA Regularly increases the hot water  
button:  
temperature in the tank for  
sterilization. (Pressing this button  
long changes the mode to data  
setting mode).  
Clears settings for the current time  
and scheduled weekly operation.  
6. DAY button:  
15. HOT WATER  
BOOST button:  
Sets days of the week for current  
time setting and scheduled weekly  
operation setting.  
Boosts boiling when high tapping  
temperature is required temporarily.  
7. STEP button:  
8. TEST button:  
16. HOT WATER  
button:  
Specifies switching STEP number  
in a day for weekly schedule.  
Turns on/off hot water operation.  
17. SELECT button:  
Selects an operation mode when  
changing the set temperature of  
each operation mode.  
Used for test run or service.  
9. FROST  
PROTECTION  
button:  
Controls minimum operation for  
unused period (going out,  
absence,etc.) for anti freezing.  
NOTE  
Some functions are not provided depending on the system specification in use.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 21  
Display Explanation  
18: ZONE1, ZONE2  
20: HOT WATER  
Description  
Display  
Description  
Display  
Lights when floor heater or radiator  
is connected (when the system has  
floor heater or radiator).  
Lights when hot water supply system is  
connected (when the system has hot  
water supply).  
ZONE1 selected for Temperature  
to be changed.  
Lights when system configured to  
have 2 zones.  
ZONE2 selected for Temperature  
to be changed.  
HOT WATER selected for Temperature  
to be changed.  
Lights during heating or cooling  
operation using the heat pump.  
Lights when hot water supply operation  
is performed by heat pump.  
Lights when the internal heater is  
energized during heating  
operation.  
Lights when the internal heater is  
energized during hot water supply  
operation.  
Lights when heating is selected.  
Lights when cooling is selected.  
Lights during hot water supply operation.  
Lights while hot water boost is activated.  
Lights when the FROST  
PROTECTION button is pressed  
and goes out when the button is  
pressed again.  
Lights when the ANTI BACTERIA button  
is pressed and goes out when the button  
is pressed again.  
Lights when Auto operation is  
selected.  
Lights when unit enters the data set  
mode.  
Displays heating/cooling set  
temperature. (Heating: 20 to 55°C,  
factory setting: Auto, cooling: 10 to  
30°C) Goes out when Auto  
operation is selected.  
Displays hot water set temperature.  
(40 to 80°C, factory setting: 65°C)  
Lights when the set temperature or  
sensor's water temperature is  
displayed with the 7-segment  
indicator.  
Lights when the set temperature or  
sensor's water temperature is displayed  
with the 7-segment indicator.  
°C  
°C  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 22  
Display Explanation (cont.)  
19: TIMER  
21: OPERATION  
Description  
Display  
Description  
Display  
Clock: Displays the current time  
(AM or PM).  
Lights while internal pump (P1) or  
external pump (P2) is driven.  
Displays days of the week (Sunday  
to Saturday).  
Lights during backup operation only by  
the heater.  
Lights when the NIGHT button is  
pressed and goes out when the  
button is pressed again.  
Lights when the unit enters the data set  
mode and goes out when the unit exits  
the data set mode.  
Lights when the unit enters the service  
mode and goes out when the unit exits  
the service mode.  
Lights when night time quiet  
operation is set.  
Indicates scheduled operation 1  
status (including setting time).  
Lights when an error occurs and goes  
out when the error is cleared.  
Displays the scheduled operation  
step when the scheduled operation  
STEP1-5 program is set.  
Lights for two seconds when settings are  
completed.  
Lights during time setting and  
scheduled operation setting.  
Lights for two seconds when settings  
failed.  
Function Code Access  
Set function codes for various operation modes, input using the remote controller.  
There are 2 types of settings:-  
1) Hydro Unit function code setting.  
2) Remote controller function code setting.  
Setting procedure for Hydro Unit function code  
1. Press the TEST  
+ SET  
+ SELECT  
buttons  
for four seconds or more to enter the hydro unit function code setting mode.  
2. Set the function code number with the TEMP. buttons  
(CODE No.: 01 to 91).  
3. Set data (DATA) with the TIME buttons  
.
4. Press the SET button to confirm the settings.  
5. The CL button  
is enabled only before the SET button is  
pressed and the function code is changed.  
6. Press the TEST button  
to finish the settings.  
Setting procedure for Remote Controller function code  
1. Press the TEST  
+ CL  
+ TEMP. buttons for four seconds  
or more to enter the remote controller function code setting mode.  
2. Set the function code number with the TEMP. buttons  
(CODE No.: 01 to 13).  
3. Set data (DATA) with the TIME buttons  
.
4. Press the SET button to determine the settings.  
5. The CL button  
pressed and the function code is changed.  
6. Press the TEST button to end the settings.  
is enabled only before the SET button is  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 23  
Main setting items  
(1) Setting Hot Water Temperature Range (function code 18 to 1F)  
• Set the temperature range for heating (zone 1, zone 2), cooling, and hot water.  
• The upper-limit and lower-limit temperatures of each mode can be set.  
(2) Setting Heat Pump Operation Conditions for Hot Water Supply (function code 20 and 21)  
• Set the heat pump start water temperature and heat pump stop water temperature.  
• The heat pump starts working when the water temperature lowers below the set start water temperature. It  
is recommended that the default value be used.  
(3) Compensating Hot Water Temperature (function code 24 and 25)  
• Compensate the target temperature from the remote controller set temperature when the hot water  
temperature lowers below the set outside air temperature.  
(4) Setting Hot Water Boost (function code 08 and 09)  
• Set the control time and target temperature when the HOT WATER BOOST  
controller is pressed.  
button on the remote  
(5) Setting Anti-Bacteria  
• Set the control for the hot water cylinder when ANTI BACTERIA  
is set with the remote controller.  
• Set the target temperature, control period, start time (24-hour notation), and target temperature retention  
period.  
• Make this control setting according to regulations and rules of respective countries.  
(6) Setting Priority Mode Temperature  
• Set the outside air temperature that changes the preferred operation mode.  
• Hot Water - Heating Switching Temperature  
Heating operation takes precedence when the temperature lowers the set temperature.  
• Boiler HP Switching Temperature  
When the temperature lowers the set temperature, the HP operation stops and the external boiler output is  
made.  
(7) Setting Heating Auto Mode Temperature (function code 27 to 31)  
• Compensate the target temperature when Auto is set for temperature setting on the remote controller.  
• The outside air temperature can be set to one of three points (T1, T2, and T3) within a range of -20 to 20°C.  
• The target temperature can be set to a value from 20 to 55°C.  
• However, A > B > C > D > E.  
• The entire curve can be adjusted plus and minus 5°C by function code 27.  
(8) Setting Frost Protection Temperature (function code 3A to 3B)  
• Set the function when the FROST PROTECTION  
button on the remote controller is pressed.  
• Set enabling/disabling of this function and the target water temperature.  
• If disabling is set, the frost protection operation is not performed even when the FROST PROTECTION  
is pressed.  
button  
(9) Setting Frequency of Output to Internal Heater (function code 33 to 34)  
• The increase/decrease time is used to set the response time.  
(10)Setting Night Setback (function code 26. remote controller function code 0F to 11)  
• Set the function when the NIGHT  
button on the remote controller is pressed.  
• Set enabling/disabling of this function, reduction temperature, start time, and end time.  
• If disabling is set, the night setback operation is not performed even when the NIGHT  
button is pressed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 24  
Main setting item (cont.)  
(11)Setting 2-Way Valve (for Cooling) Operation (function code 3C)  
• When using both cooling and heating operations and there is an indoor unit only for heating (such as floor  
heating), install the 2-way valve and set this function code.  
(12)Setting 3-Way Valve Operation (function code 54)  
• This setting is not necessary for normal installation. Make this setting to invert the logic circuit in case ports  
A and B of the 3-way valve are wrongly attached and it cannot be rectified on site.  
(13)Mixing valve types and setting  
• Set the time period from full close to full open of the 2-zone control mixing valve. Set a value that is 1/10 of  
the actual time.  
(14)Setting Heating/Hot Water Switching when Boiler Is Used (function code 3E)  
• When boiler is used, make this setting to operate the Hydro Unit by the instruction from the boiler.  
(15)Setting Heat Pump Operating Time for Hot Water Supply Operation  
• Set the time period from the start of heat pump run to the start of heater energization at the beginning of hot  
water supply operation. If a long period is set, it takes long time for heating water.  
(16)Setting Cooling ON/OFF  
• Set this function when performing cooling operation.  
(17)Remote controller time indication  
• 24-hour or 12-hour notation is selected for the timer.  
(18)Setting Nighttimes Quiet Operation  
• Issue an instruction for low-noise mode operation to the outdoor unit. Enabling/disabling of this function, start  
time, and end time can be set.  
(19)Setting Alarm Tone  
• The remote controller alarm tone can be set.  
Function Code  
Function Code List  
Number  
Hydro  
Unit  
Remote  
Controller  
Function  
Range  
Default  
1A  
1B  
1C  
1D  
18  
19  
1E  
1F  
20  
21  
-
-
-
-
-
-
-
-
-
-
37 ~55  
20 ~ 37  
37 ~55  
20 ~ 37  
18 ~ 30  
10 ~ 18  
50 ~ 75  
40 ~ 60  
20 ~ 45  
40 ~ 50  
55  
20  
55  
20  
25  
10  
75  
40  
38  
45  
Zone 1 - heating upper temperature limit °C  
Zone 1 - heating lower temperature limit °C  
Zone 2 - heating upper limit temperature °C  
Zone 2 - heating lower limit temperature °C  
Cooling mode - upper temperature limit °C  
Cooling mode - lower temperature limit °C  
Hot water - upper temperature limit °C  
Hot water - lower temperature limit °C  
Heat pump start temperature °C  
Setting  
Temperature  
Range  
Hot Water  
Operation  
Heat pump stop temperature °C  
Hot Water  
Temperature  
Compensation  
Temperature compensation - start outside air  
temperature °C  
24  
-
-20 ~ 10  
0
25  
08  
09  
0A  
-
-
-
0 ~ 15  
3 ~ 18  
40 ~ 75  
70 ~ 75  
0 ~ 10  
0 ~ 23  
0 ~ 60  
3
6
Compensation temperature °C  
Operation time x 10 min  
Setting temperature °C  
Setting temperature °C  
Start cycle (day)  
Hot Water Boost  
-
75  
75  
7
-
0D  
0C  
-
Anti - Bacteria  
-
22  
30  
Start time (hour)  
0B  
Operation time (min)  
Hot water and heating switching  
temperature °C  
Boiler and heat pump switching  
temperature °C  
22  
23  
-
-
-20 ~ 20  
-20 ~ 20  
0
Priority Mode  
-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 25  
Function Code Number  
Function Code List (cont.)  
Remote  
Controller  
Function  
Hydro Unit  
Range  
Default  
29  
-
-
-
-
-
-
-
-
-
-
-
-
-
-15 ~ 0  
0
-10  
0
Outside temperature T1 °C  
Outside temperature T2 °C  
2B  
2C  
2D  
2E  
2F  
30  
31  
27  
3A  
3B  
0 ~ 15  
20 ~ 55  
20 ~ 55  
20 ~ 55  
20 ~ 55  
20 ~ 55  
0 ~ 100  
-5 ~ 5  
10  
40  
35  
30  
25  
20  
80  
0
Outside air temperature T3 °C  
Setting temperature A at -20 °C  
Setting temperature B at T1°C  
Setting temperature C at T2°C  
Setting temperature D at T3°C  
Setting temperature E at +20°C  
Ratio of Zone 2 in Zone 1 Auto mode (%)  
Temperature shift of entire Auto curve (°C)  
Function 0 = Valid; 1 = Invalid  
Setting temperature °C  
Heating  
Auto Curve  
Settings  
0 ~ 1  
1
Frost Protection  
8 ~ 20  
15  
Back up heater downtime. 0=5min; 1=10min;  
2=15min; 3=20min  
33  
34  
58  
-
-
-
0 ~ 3  
0 ~ 3  
0 ~ 1  
1
0
0
Back Up Heater  
Control  
Back up heater uptime. 0=10min; 1=20min;  
2=30min; 3=40min  
Zone Selection: 0=Zones 1 and Zone 2;  
1=Zone 1 Only  
26  
-
-
3 ~ 20  
0 ~ 23  
0 ~ 23  
5
Change Setback temperature °C  
Start time (hour)  
Night Setback  
0E  
0F  
22  
06  
End time (hour)  
-
Room temperature control adjustment. 0=Valid;  
1=Invalid  
-
02  
-
0 ~ 1  
0
1
6
Compensation for temperature °C  
35  
36  
1 ~ 5  
Room Temperature  
Setting  
1 ~ 24  
(5 ~ 120mins)  
Downtime Zone B (x 5min)  
-
1 ~ 24  
(5 ~ 120mins)  
Uptime Zone C (x5min)  
37  
-
-
6
0
2 way valve activation for cooling.  
0=activated during cooling;  
1=not activated during cooling  
2 Way Valve  
Operation Control  
3C  
0 ~ 1  
0 ~ 1  
3 way valve activation.  
0=activated during hot water operation;  
1=not activated during hot water operation  
3 Way valve  
Operation Control  
54  
-
0
2 Zone Mixing  
Valve Drive Time open (x 10 sec)  
Specified Drive Time for Mixing Valve to 90°  
0C  
3E  
-
-
3 ~ 24  
0 ~ 1  
6
0
Boiler & Heat  
Pump  
Synchronisation  
Boiler synchronisation with heat pump.  
0=synchronised; 1=not synchronised  
Maximum  
Operation Time of Maximum heat pump operation time in hot  
Hot Water Heat water operation priority mode (minutes)  
Pump  
07  
02  
-
-
1 ~ 120  
0 ~ 1  
30  
1
Activate cooling mode.  
Cooling Operation 0=cooling & heating mode;  
1=heating mode only  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 26  
Function Code Number  
Function Code List (cont.)  
Remote  
Controller  
Function  
Hydro Unit  
Range  
Default  
Remote Controller 24 hour or 12 hour remote control display.  
-
-
05  
09  
0 ~ 1  
0 ~ 1  
0
0
Indication  
0=24hr; 1=12hr  
0 = Function invalid  
1 = Function valid  
Outdoor Night Time  
Low Noise  
Start time (hour)  
End time (hour)  
-
-
0A  
0B  
0 ~ 23  
0 ~ 23  
22  
06  
Operation  
Alarm Tone  
Tone Switching 0: OFF, 1: ON  
11  
-
0 ~ 1  
0 ~ 1  
1
0
Pump P2 remote 0 = Not Shown;  
controller Display 1 = Shown  
42  
46  
Outdoor Forced 0 = Forced Defrost OFF;  
Defrost Mode  
-
-
0 ~ 1  
0 ~ 3  
0
0
1 = Forced Defrost ON  
0 = a contact “ON” = Forced stop  
Optional ON/OFF 1 = b contact “OFF” = Forced stop  
52  
Command  
2 = ON/OFF = Start / Stop  
3= HA Specification  
0 = Symbol displayed when mode is valid  
Outdoor Night Time (controlled by Function Code Only);  
56  
57  
-
-
0 ~ 1  
0 ~ 1  
0
0
Mode Button  
1 = Symbol displayed when mode is activated  
(controlled by Function Code and Button)  
Control Logic for 0 = Cooling thermo on – contact open;  
Room Thermostat 1 = Cooling thermo on – contact close  
Settings by Purpose  
Settings when hot water supply function is not used  
• When the hot water supply function is not used, set DIP SW12-1 on the Hydro Unit board to ON.  
Setting for cooling  
• For Space Conditioning Units that do not perform cooling (radiators and Under floor heating, etc.), procure a  
motorized 2-way valve (for cooling) locally and attach it to the water pipe that is not used for cooling. Connect the  
valve cables (as described in Electrical section).  
• Press long the TEST  
Hydro Unit function code, and change address 02 to 0, and then press the SET button to enable the function.  
Press the TEST button to exit the setting mode.  
+ SET  
+ SELECT  
switches on the remote controller to change the  
• Stick the optional insulator for cooling to the bottom of the Hydro Unit.  
Settings for hot water supply  
• Prepare the optional hot water cylinder.  
• Procure a motorized 3-way (diverter) valve locally and perform piping. Connect the valve cables (as described in  
Electrical section).  
• Set DIP SW12-1 on the Hydro Unit board to OFF.  
• Connect the power supply unit for the hot water cylinder heater to terminals TB03 L and N of the Hydro Unit.  
• Connect cables between the Hydro Unit and the hot water cylinder as follows:  
Hydro Unit terminals  
TB03 (1), (2), and earth — Hot water cylinder (1), (2), and earth  
TB06 A, B, and earth Hot water cylinder A, B, and earth  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 27  
Settings by Purpose (cont)  
Settings for 2-zone temperature control  
• Procure a motorized mixing valve locally and perform piping. Connect the valve cables (as described in Electrical  
section).  
• Procure a buffer tank locally.  
• Procure a water pump locally, and connect its cables (as described in Electrical section).  
To inhibit interlocking the water pump with the internal pump of the Hydro Unit, set DIP SW10-3 on the Hydro  
Unit board to OFF.  
• Set DIP SW12-3 on the Hydro Unit board to ON.  
Attach the temperature sensor (TFI) connected to terminals TB06 C and D of the Hydro Unit near the hot water  
inlet of the Hydro Unit.  
• Contact the temperature sensor closely with the pipe, fix it with aluminium tape or the like, and then perform  
insulation treatment for the sensor.  
• Fix TFI sensor on the room heating supply pipe by using the connector procured in locally.  
• Cover the cables with insulation tube (minimum 1 mm) or conduit so that the user cannot touch them directly.  
• Connect the functional earth wire of TFI sensor in the tank unit.  
• Cover the TFI sensor's cables and sensor with insulation tube (minimum 1 mm) shown in the diagram on the  
right.  
Test Run  
Use operation buttons usually to conduct a test run.  
If the outside air temperature or water temperature is outside the setting value range, press the TEST  
button on  
the remote controller and then start a test run. Since the protection setting is disabled in the TEST mode, do not  
continue a test run longer than 10 minutes.  
• Press the TEST  
button on the remote controller. An indication “TEST” appears on the remote controller.  
button and select “heating” with the OPERATE MODE button.  
• Press the ZONE1, 2  
The pump is activated in 30 seconds.  
If air is not released completely, the flow rate switch is activated to stop operation. Release air again according to the  
piping procedure. Little air bite is discharged from the purge valve.  
• Check that the air bite sound disappears.  
• Check that the hydraulic pressure has become the predetermined pressure 0.1 to 0.2 MPa (1 to 2 bar). If the  
hydraulic pressure is insufficient, replenish water.  
• Heating operation starts. Check that the hydro unit starts heating.  
• Press the OPERATE MODE  
button and select “cooling.”  
• Cooling operation starts. Check that the hydro unit starts cooling and that the floor heating system is not cooled.  
• Press the ZONE1, 2  
button to stop operation.  
• Press the HOT WATER  
button to start hot water supply operation.  
• Check that there is no air bite.  
• Check that hot water is present at the connection port of the hot water cylinder.  
• Press the HOT WATER  
• Press the TEST  
button to stop the hot water supply operation.  
button to exit the test mode.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 28  
Sensor Temperature Monitoring Function  
The sensor sensing temperature is displayed on the remote controller. This function allows you to make sure whether  
the sensor is installed properly.  
1) Press the TEST  
+ CL  
buttons for four seconds or more.  
2) Select the Code No. with the TEMP.  
buttons.  
3) Press the TEST  
button to exit the test mode.  
Code No.  
06  
Location  
Indication  
Return water temperature °C  
08  
Hot water temperature °C  
09  
Hydro unit  
2-zone sensor temperature °C  
0A  
Hot water cylinder temperature sensor °C  
Motorized mixing valve position  
0B  
60  
Heat exchanger temperature °C  
Outside air temperature °C  
61  
62  
Outdoor unit  
Refrigerant discharge temperature °C  
Refrigerant intake temperature °C  
Current value (in the inverter) A  
63  
6A  
70  
Compressor operating frequency  
Hydro unit AC pump total operating hours x100 hours  
Hot water cylinder heater total operating hours x100 hours  
Hydro unit heater total operating hours x100 hours  
F4  
F5  
Operating hours  
F6  
Fault Symptoms  
Symptom  
Possible cause  
Corrective action  
Check remote controller operation and temperature  
setting  
Incorrect remote controller setting  
Check function code setting with the function code  
table.  
Incorrect function code setting  
Room is not heated or  
cooled. Water is not hot  
enough.  
Backup heater disconnected  
Insufficient capacity  
Check backup heater and bimetal thermostat.  
Check selection of equipment.  
Check whether temperature sensor is installed at  
the normal position.  
Sensor defect  
Power is not supplied.  
Incorrect setting  
Check power supply wiring.  
Nothing is displayed on  
the remote controller.  
Check DIP switch setting on the Hydro Unit board.  
Check the setting with the function code table.  
Air bite in the pump  
Release air completely according to the procedure.  
Set hydraulic pressure considering pipe height, and  
replenish water until manometer shows a value of  
set hydraulic pressure or more.  
Low hydraulic pressure  
Flow rate switch is  
activated. Error code  
[A01]  
Strainer is clogged.  
Clean the strainer.  
Widen water path to the hydro unit or adopt a  
bypass valve.  
Large resistance on the hydro side  
Malfunction of motorized 3-way  
valve for hot water supply  
Check wiring and parts.  
Set hydraulic pressure considering pipe height, and  
replenish water until manometer shows a value of  
set hydraulic pressure or more.  
Check expansion tank capacity compared to total  
water amount. If it is insufficient, install another  
expansion tank.  
Excessive hydraulic pressure  
Hot water leaks from  
pressure relief valve.  
Insufficient capacity of expansion  
tank  
Expansion tank failure  
Check the air pressure.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 29  
Alarm Indications  
Alarm  
indication  
Alarm description and generation/reset conditions  
Regular communication error between hydro unit and remote controller (system controller) If there is no  
regular communication from the remote controller for three minutes, the hydro unit regards it as no  
remote controller. If there is no communication from both sides, alarm E03 occurs. Auto-reset: When  
successful regular communication is made  
E03  
Regular communication error between hydro unit and outdoor unit When serial signal from the outdoor  
unit cannot be received though normal serial signal is sent to the outdoor unit 1) When serial signal  
cannot be received continuously for 60 seconds (S code communication) 2) Communication is still not  
successful for 80 seconds through three retries if serial signal cannot be received for 20 seconds after  
new communication (f code) starts When the remote controller starts operation, serial transmission  
starts with the new communication format. Auto-reset: When successful regular communication is  
made  
E04  
Condensing temperature TC sensor defect  
F03  
F10  
F11  
F14  
F17  
F18  
F23  
If short-circuit or open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Hydraulic heat exchanger inlet temperature TWI sensor defect  
If short-circuit or open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Hydraulic heat exchanger outlet temperature TWO sensor defect  
If short-circuit or open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Hot water cylinder temperature TTW sensor defect  
If short-circuit or open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Floor inlet temperature TFI sensor defect  
If short-circuit or open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Internal heater outlet temperature TWO sensor defect  
If short-circuit or open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Low-pressure sensor defect  
If open-circuit state continues for two seconds, an alarm occurs.  
Auto-reset: When normal value is confirmed  
Hydraulic heat exchanger EEPROM defect  
One mismatch is detected if there is no verification ACK after data write to the EEPROM Reset  
condition: This alarm is inhibited while the unit is not working.  
(When EEPROM1K is mounted, this alarm cannot be reset.)  
F29  
Floor inlet temperature TFI sensor disconnection or wrong installation (This alarm is reset by stopping  
operation and is checked again.)  
F20  
F30  
Onboard expansion IC defect This alarm is not reset automatically.  
Group line in an hydro unit  
This alarm is checked during initial communication immediately after power-on. This alarm occurs  
immediately after operation start.  
L07  
This alarm is not reset automatically. (This alarm is inhibited while the unit is not working, but occurs  
again after the unit operates.)  
Hydro unit capacity has not been set.  
L09  
This alarm is checked immediately after power-on. This alarm is not reset automatically. (This alarm is  
inhibited while the unit is not working, but occurs again after the unit operates.)  
A01  
A02  
A03  
A04  
A07  
Pump defect or abnormal flow rate This alarm is not reset automatically.  
Excessive water temperature increase by the heating heater Auto-reset:  
Excessive water temperature increase in the hot water cylinder  
Freezing is detected. Auto-reset:  
High-pressure switch malfunction This alarm is not reset automatically.  
A08  
Low-pressure sensor malfunction This alarm is not reset automatically.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 30  
Alarm Indications (cont)  
A09  
Overheat preventive operation malfunction Auto-reset: When operation mode is changed  
Release preventive operation malfunction This alarm occurs when the Hydro Unit enters the forced-  
stop zone 10 times.  
A11  
Self-hydro unit is stopped due to alarm of other hydro unit. When alarm occurs in an hydro unit in the  
group, other hydro units must also be stopped with refrigerant control.  
When alarm E03, L03 or L07 occurs in the header unit in the group, other hydro units must also be  
stopped  
P31  
because they do not know which header unit (remote controller) to follow.  
Auto-reset: When the first alarm is reset  
Outdoor Alarm indication  
Alarm  
indication  
Main failure part  
Description  
Outdoor unit discharge  
temperature sensor TD  
defect  
When open- or short-circuit of discharge temperature sensor TD is  
detected  
F04  
F06  
F08  
Outdoor unit temperature  
sensor TE or TS defect  
Outdoor unit outside air  
temperature sensor TO  
defect  
When open- or short-circuit of heat exchanger temperature sensor  
TE or TS is detected  
When open- or short-circuit of outside air temperature sensor TO is  
detected  
When min-Hz is reached by current release control or when short-  
circuit current (Idc) is detected after direct current excitation  
H01  
H02  
H03  
H06  
L29  
Compressor breakdown  
Compressor locked  
When compressor lock is detected  
When abnormal current is detected in AC-CT or phase loss is  
detected  
Current detector defect  
Low-pressure system defect Ps pressure sensor defect or low-pressure protective operation  
Other outdoor unit faults: 1) Inter-MCU communication error between  
Other outdoor unit faults  
IPDU and CDB 2) abnormal GBT heat sink temperature  
When phase sequence of 3-phase power supply is incorrect  
(thermostat OFF operation continued), etc.  
When abnormal temperature is detected by discharge temperature  
release control  
L31  
P03  
Phase sequence error, etc.  
Abnormal outdoor unit  
discharge temperature  
High-pressure system  
defect  
When high-pressure switch , IOL is activated or when abnormality is  
detected by high-pressure release control by TE  
P04  
P22  
P26  
P29  
Outdoor unit fan defect  
Inverter Idc operation  
Position detection error  
When over current or lock in outdoor unit fan drive circuit is detected  
When short-circuit protection is activated for compressor driver  
devices (G-Tr, IGBT)  
When compressor motor position detection error is detected  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Guide - Page 31  
Outdoor Fault Diagnosis  
You can perform fault diagnosis of the outdoor unit with the LED's on the P.C. board of the outdoor unit in addition  
to check codes displayed on the wired remote controller of the hydro unit.  
Use the LED’s and check codes for various checks.  
Check of the current abnormal status  
Check of the abnormal status in the  
past although the abnormal status is  
not occurred now.  
1. Set bit 1 of DIP switch SW803 to ON.  
2. Jot down the states of LED800 to  
LED804. (Display mode 1)  
3. Press SW800 for at least one second.  
The LED status changes to display  
mode 2.  
1. Check that DIP switch SW803 is set to all OFF.  
2. Jot down the states of LED800 to LED804. (Display mode 1)  
3. Press SW800 for at least one second. The LED status changes to  
display mode 2.  
4. Check the code whose display mode 1 equals the jotted LED status and  
display mode 2 equals the current flashing status of LED800 to LED804  
from the following table to identify the cause.  
4. Find an error whose display mode 1  
equals the jotted LED status and display  
mode 2 equals the current flashing  
status of LED800 to LED804 from the  
following table to identify the error.  
• An outside air temperature (TO)  
sensor error can be checked only while  
an error occurs.  
DISPLAY MODE 1  
DISPLAY MODE 2  
No. Cause  
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804  
1
2
3
4
Normal  
Discharge sensor (TD) error  
Heat exchanger sensor (TE) error  
Heat exchanger sensor (TL) error  
Outside air temperature sensor (TO)  
error  
5
6
7
Suction sensor (TS) error  
Heat sink sensor (TH) error  
Outdoor temperature sensor (TE/TS)  
connection error  
Outdoor EEPROM error  
8
9
10 Compressor lock  
11 Compressor lock  
12 Current detect circuit error  
13 Thermostat for compressor activated  
Model data not set (on the service P.C.  
board)  
14  
15 MCU-MCU communication error  
16 Discharge temperature error  
Abnormal power (open phase detected  
or abnormal voltage)  
17  
18 Heat sink overheat  
19 refrigerant leak detected  
20 4-way valve reverse error  
21 High pressure release operation  
22 Outdoor fan motor error  
Compressor driver short circuit  
protection  
Position detect circuit error in one-line  
display  
23  
24  
: ON  
: OFF  
: FLASHING  
Download from Www.Somanuals.com. All Manuals Search And Download.  

TechniSat Satellite TV System DIGIT MF4 S User Manual
Telex Stereo Amplifier 795 10 User Manual
Texas Instruments Network Card DEM PCM2912A EVM User Manual
Trane Dehumidifier 120 GEH User Manual
Transition Networks Network Router SSEFE10XX 10X User Manual
Tripp Lite Surge Protector PS7224 20HW User Manual
Uniden Cordless Telephone TRUc46 User Manual
Uniden Film Camera GC43 User Manual
Unitech Network Card MSR120 Series User Manual
Viking Refrigerator DDBF036 User Manual