Model EEDU
and HEEDU
Indoor/Power-Vented
Duct Furnaces
INSTALLATION FORM RGM 421 (Version A)
APPLIES TO:
Installation/Operation/Service
Table of Contents
Paragraph No.
Page No.
Installation and Operation ........................ 1-26.......................... 1-20
Check Installation and Start-Up .............. 27 ............................. 21
Service/Maintenance/Troubleshooting ..... 28-33........................ 22-24
Index by Page Number
Air Flow Requirements ................................. 13
Blower Connections ..................................... 14
Burner Air Adjustment.................................. 21
Burner Rack Removal .................................. 22
Burners .......................................................... 21
Bypass Duct.................................................. 13
Carryover System ......................................... 21
Check Installation and Start-Up ................... 21
CHLORINES .................................................. 5
Cleaning Pilot and Main Burners................. 22
Cleaning the Heat Exchanger ....................... 23
Clearances ...................................................... 4
Combustion Air ............................................... 4
Combustion Air Proving Switch .................. 15
Condensate Drain, Option CS1 .................... 13
Coupling Two, Three, Four or Five
Mounting the Furnace .................................... 6
Pilot and Ignition Systems ........................... 20
Reversing Air Flow ........................................ 6
SERVICE ...................................................... 22
Start-Up ........................................................ 21
Suspending the Furnace ................................. 6
Thermostat .................................................... 15
Troubleshooting ...................................... 23, 24
Optional Two-Stage Operation..................... 19
Uncrating ........................................................ 4
Valve ............................................................. 19
Venter............................................................ 23
Venting ........................................................... 9
Warranty ......................................................... 2
Wiring Diagrams ..................................... 16-17
Furnaces ..................................................... 7
Dimensional Data ........................................... 3
Disconnect Switch ........................................ 15
Duct Connections ......................................... 12
Operating Sequence ...................................... 16
Optional Ductstat ......................................... 19
Electrical Supply and Connections .............. 15
Optional Electronic Modulation .................. 20
Fan Control (Optional) ................................. 18
Gas Piping and Pressures ............................... 8
GENERAL...................................................... 1
HAZARD INTENSITY LEVELS .................. 2
Installation Codes ........................................... 2
Limit Switch ................................................. 17
MAINTENANCE ......................................... 22
Reference: Replacement Parts Form, RGM 735
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don't touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
FOR YOUR SAFETY
The use and storage of gasoline or other
flammable vapors and liquids in open
containers in the vicinity of this appliance is
hazardous.
WARNING: Gas-fired appliances are not
designed for use in hazardous atmospheres
containing flammable vapors or combustible
dust, in atmospheres containing chlorinated
or halogenated hydrocarbons, or in
applications with airborne silicone substances.
See Hazard Levels, Page 2.
WARNING: Improper installation, adjustment,
alteration, service, or maintenance can cause
property damage, injury or death. Read the
installation, operation, and maintenance
instructions thoroughly before installing or
servicing this equipment.
GENERAL
Model
EEDU
Characteristics
Indoor, Power-Vented, Standard CFM, 80%
Thermal Efficient
Installation should be done by a qualified agency in accordance
with the instructions in this manual and in compliance with all
codes and requirements of authorities having jurisdiction. The
instructions in this manual apply to the duct furnace models
shown on the right.
Indoor, Power-Vented, High CFM, 80%
Thermal Efficient
HEEDU
RGM Form 421, Mfg No. 150492, Page 1
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Dimensions
Figure 1
C
D
5"
16"
K
L
(centerline of hangers)
(127mm) (406mm)
F
Electric Supply
M
6-3/4"
(171mm)
H
Limit
Keep
clear for
service
18"
(457mm)
Airflow
A
29"
(737mm)
8-1/8"
(206mm)
3-1/2"
(89mm)
Combustion
Air Opening
4" (102mm)
Minimum unit
spacing
Combustion
Air Opening
E
View
port
(both
sides)
26"
(660mm)
J
B
(Duct width)
G = Gas
Connection
(not supply line)
Front View
Side View
Rear View
K
Dimensions (inches)
Size
A
B
C
D
E
F
G
H
J
L
M
Nat Pro
34-3/8 14-1/4 35-11/16 14-5/8 4-3/8 3-15/16 1/2 1/2
34-3/8 17 35-11/16 17-3/8 4-3/8 3-15/16 1/2 1/2
34-3/8 19-3/4 35-11/16 20-1/8 4-3/8 3-15/16 1/2 1/2
34-3/8 22-1/2 35-11/16 22-7/8 4-3/8 3-15/16 1/2 1/2
5/8
5/8
5/8
5/8
12-1/2 7-1/4 7-7/16 4-5/8
15-1/4 7-1/4 7-7/16
18 7-1/4 7-7/16 7-3/8
20-3/4 7-1/4 7-7/16 8-3/4
75, 100
125, 140
170
6
200
34-3/8 25-1/4 35-11/16 25-5/8 4-3/8 4-15/16 1/2 1/2 1-3/8 23-1/2 7-1/4 7-7/16 10-1/8
34-3/8 28 35-11/16 28-3/8 7-1/8 4-15/16 1/2 1/2 1-3/8 26-1/4 7-1/4 7-7/16 11-1/2
34-3/8 33-1/2 38-1/8 33-7/8 9-7/8 5-15/16 3/4 1/2 1-3/8 31-3/4 9-9/16 7-5/8 13-7/8
34-3/8 39 38-1/8 39-3/8 12-5/8 5-15/16 3/4 1/2 1-3/8 37-1/4 9-9/16 7-5/8 16-5/8
34-3/8 44-1/2 38-1/8 44-7/8 15-3/8 5-15/16 3/4 1/2 1-3/8 42-3/4 9-9/16 7-5/8 19-3/8
225
250
300
350
400
Dimensions (mm)
Size
A
B
C
D
E
F
G
H
J
K
L
M
Nat Pro
13 13
13 13
13 13
13 13
13 13
13 13
19 13
19 13
19 13
873
873
873
873
873
873
873
873
873
362
432
502
572
641
711
851
991
1130
906
906
906
906
906
906
968
968
968
371
441
511
581
651
721
860
1000
1140
111
111
111
111
111
181
251
321
391
100
100
100
100
125
125
151
151
151
16
16
16
16
35
35
35
35
35
318
387
457
527
597
667
806
946
1086
184
184
184
184
184
184
243
243
243
189
189
189
189
189
189
194
194
194
117
152
187
222
257
292
352
422
492
75, 100
125, 140
170
200
225
250
300
350
400
RGM Form 421, Mfg No. 150492, Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Uncrating and Preparation
5. Location, Clearances, and
Combustion Air
This furnace was test operated and inspected at the factory prior to
crating and was in operating condition. If the furnace has incurred any
damage in shipment, file a claim with the transporting agency.
Unit must be installed so that the following clearances are provided for
combustion air space, service and inspection, and for proper spacing
from combustible construction.
CAUTION: Remove the panel from the bottom rear of the
furnace (See Paragraph 28) and check the burner rack as-
sembly. The burner rack "drawer" should be setting level with
each side on a support rail. Check to assure that EXCES-
SIVE shipping vibration has not caused the burner rack as-
sembly to "drop off" the support rails into the bottom pan. If
the burner rack assembly is positioned properly, close the
back panel. If the burner rack has fallen, remove the screws
holding the burner rack assembly and pull out the burner rack
"drawer". Re-assemble by sliding the burner rack "drawer"
into the heater, being sure that both sides are resting on the
support rails. Re-attach to the support brackets underneath
the burners. Re-insert the burner rack screws and close the
back panel.
NOTE: See Figure 5 for service clearance illustration.
REQUIRED CLEARANCES
Front Top Flue Connector Sides Bottom Rear
6"
6"
6"
6"
12"
29"
152mm 152mm
152mm
152mm 305mm 737mm
CAUTION: Do not locate heater where it may
be exposed to liquid spray, rain or dripping
water.
These duct furnaces are designed to take combustion air from the space
in which the furnace is installed. The air that enters into the combus-
tion process is vented to the outdoors. Sufficient air must enter the
equipment location to replace the air exhausted through the vent sys-
tem. Modern construction methods involve the greater use of insula-
tion, improved vapor barriers and weather-stripping, with the result
that buildings generally are much tighter structurally than they have
been in the past. The combustion air supply for gas-fired equipment
can be affected by these construction conditions because infiltration
that would have existed in the past may not be adequate. Extensive use
of exhaust fans aggravates the situation. In the past the filtration of
outside air assumed in heat loss calculations (one air change per hour)
was assumed to be sufficient. However, current construction methods
may now require the introduction of outside air through wall openings
or ducts.
Check the rating plate for the gas specifications and electrical charac-
teristics of the furnace to be sure that they are compatible with the gas
and electric supplies at the installation site. Read this booklet and be-
come familiar with the installation requirements of your particular fur-
nace. If you do not have knowledge of local requirements, check with
the local gas company or any other local agencies who might have
requirements concerning this installation. Before beginning, make
preparations for necessary supplies, tools, and manpower.
Check to see if there are any field-installed options that need to be
assembled to the furnace prior to installation.
Option Parts -- Some gas control options will have parts either shipped
loose with the heater or shipped separately. If your unit is equipped
with any of the following gas control options, be sure these parts are
available at the job site.
WARNING: These furnaces are designed to take
combustion air from the space in which the unit
is installed and are not designed for connection
to outside combustion air intake ducts. Use of
outside air ducts voids the warranty and could
cause hazardous operation. (See Hazard Levels,
page 2.)
Heating -- Gas Option AG7
Control Option Amplifier, P/N 48035
Thermostat, P/N 48033
Makeup Air -- Option AG3
Gas Control
Options
Control Switch, P/N 29054
Gasket, P/N 7726
Requirements for combustion air and ventilation air depend upon
whether the unit is located in a confined or unconfined space. An "un-
confined space" is defined as a space whose volume is not less than 50
cubic feet per 1000 BTUH of the installed appliance. Under all condi-
tions, enough air must be provided to ensure there will not be a nega-
tive pressure condition within the equipment room or space. A posi-
tive seal must be made in all return-air connections and ducts. Even a
slight leak can create a negative pressure condition in a confined space
and affect combustion.
Gasket Retainer Plate, P/N 7727
Option AG8
Temperature Sensor, P/N 48041
Amplifier, P/N 48037
Control Switch, P/N 29054
Option AG9
Remote Temperature Selector, P/N 48042
Temperature Sensor, P/N 48041
Amplifier, P/N 48035
(All of these
options also
require a
shipped-
separate fan
control, Opt
CQ1 (P/N
57960), which
should be
at the job
site.
Installation in a Confined Space
Control Switch, P/N 29054
Option AG15 or AG16
Figure 2 -
Confined Space: A
space whose volume
is less than 50 cubic
feet per 1000 BTUH
of the installed
appliance input
rating
Remote Temperature Selector, P/N 115848
Stage Adder M odule, P/N 115849
Control Switch, P/N 29054
Transformer 115 to 24V, P/N 103055 or
208/230 to 24V, P/N 103497; and 1/2" locknut,
P/N 16222 (for transformer)
Display M odule, P/N 115852 (AG16 only)
Do not install a unit in a confined space without providing wall open-
ings leading to and from the space. Provide openings near the floor
and ceiling for ventilation and air for combustion as shown in Figure
Other shipped-separate options could include a gas shutoff valve, a
condensate drain fitting, a thermostat, a hanger kit, a coupling kit, a fan
control, or high temperature sealing tape.
Form 421, Page 4
Download from Www.Somanuals.com. All Manuals Search And Download.
2, depending on the combustion air source as noted in Items 1, 2, and
3 below the illustration.
Figure 3A - Limit Control Location - When reversing
air flow, the limit control must be re-located. The
limit control MUST be on the discharge end of the
heat exchanger
Add total BTUH of all appliances in the confined space and divide by
figures below for square inch free area size of each (top and bottom)
opening.
1. Air from inside the building -- openings 1 square inch free area per
1000 BTUH. Never less than 100 square inches free area for each open-
ing. See (1) in Figure 2.
2. Air from outside through duct -- openings 1 square inch free area
per 2000 BTUH. See (2) in Figure 2.
3. Air direct from outside -- openings 1 square inch free area per 4000
BTUH. See (3) in Figure 2.
NOTE: For further details on supplying combustion air to a confined
space, see the National Fuel Gas Code ANSI Z223.1a (latest edition ).
Location of
the
factory-
installed
Limit
Control
Bracket on
a Furnace
with
Hazards of Chlorines
The presence of chlorine vapors in the combustion air of gas-fired heat-
ing equipment presents a potential corrosion hazard. Chlorine will,
when exposed to flame, precipitate from the compound, usually freon
or degreaser vapors, and go into solution with any condensation that is
present in the heat exchanger or associated parts. The result is hydro-
chloric acid which readily attacks all metals including 300 grade stain-
less steel.
Standard
Air Flow
Direction
Care should be taken to separate these vapors from the combustion
process. This may be done by wise location of the furnace with regard
to exhausters or prevailing wind direction. Remember, chlorine is
heavier than air. This fact should be kept in mind when determining
installation locations of heating equipment and building exhaust sys-
tems.
NOTE: Actual gas valve
may not be as illustrated.
Figure 3B - Model EEDU has a top and bottom
support assembly and individual baffles.
6. Instructions for Reversing Air Flow
by Changing Directional Air Baffles
in the Heat Exchanger
Duct furnaces are equipped with directional air baffles between the
heat exchanger tubes. Facing the control compartment of the furnace,
the standard direction of air flow is from the rear of the furnace (gas
valve location) toward the front of the furnace. If the installation site
requires air flow from the front to the rear, the unit may be field adapted
by re-locating the limit control and reversing the position of the direc-
tional air baffles.
Instructions:
NOTE: If the unit has optional outer side panels, locate the limit con-
trol and remove the outer panel on that side of the furnace.
1. All Models - Refer to Figure 3A. Remove the screws attaching the
limit control bracket to the side of the furnace. Carefully pull the bracket/
control assembly through the hole. (Do not disconnect wires.)
2. All EEDU Models (see below for high CFM HEEDU Models) -
Refer to Figure 3B and follow Steps a)-d) below to reverse the direc-
tion of the baffles.
a) Remove Screws "A". Individually lift each baffle slightly and slide
forward. Remove all baffles completely from the heat exchanger.
All HEEDU Models (see above for EEDU Models) - Refer to
Figure 3C and follow Steps a) and b) below to move the top
baffle to the entering air end of the heater exchanger.
a) Remove screws B and the baffle.
b) Re-position the baffle on the "entering air" end of the heat exchanger
and attach.
b) Remove Screws B and the top baffle support assembly. Re-position
the assembly on the opposite send of the heat exchanger and attach.
c) Remove Screws C and the assembled bottom baffle support and
brackets. Plug the holes in the heat exchanger bottom by re-insert-
ing the screws in the holes. Position the assembly on the opposite
end of the heat exchanger and attach using field-supplied sheet metal
screws.
d) Re-install all of the individual baffles by reversing procedure in
Step a) above.
RGM Form 421, Mfg No. 150492, Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 4A - Suspending a Single Furnace
6. Instructions for Reversing Air
Flow (cont'd)
Figure 3C - Model
as only a
ear heat
r baffle.
)
her
Centerline of hangers
A
350
400
3. All Models - Relocate the limit control.
39-3/8" 1000mm
44-7/8" 1140mm
a) At the discharge end on the same side of the heat exchanger, mea-
sure down 4-1/2" and in 1-11/16". Using that point as the center,
punch a 2-1/4" diameter hole in the side panel.
NOTE: It may be necessary to move cable connections. Re-insert
screws to plug all holes in the side panel. After the limit control is
installed, the cable connections may be re-attached using field-sup-
plied sheet metal screws.
Figure 4B - Option
CK3 Hanger Kit (P/N
57959) with four
Free-turning
threaded
socket
b) With the limit control on the heat exchanger side of the bracket,
slide the limit control/bracket assembly into the hole. Attach the
bracket with two sheet metal screws.
threaded sockets
(1" pipe)
c) Cover all of the original factory-made limit control holes with a
field-supplied sheet metal plate. Do not leave any open holes in the
side panel or the heat exchanger bottom.
4. The furnace is now ready for installation with the air flow from front
to rear (gas valve side).
Mounting the Furnace
Change position of the hanger bracket as shown in Figure 5. When the
furnace is mounted on combustible material, a minimum clearance of
12" is required.
7. Suspending or Mounting the
Furnace
Before installing the furnace, check the supporting structure to be used
to verify that it has sufficient load-carrying capacity to support the weight
of the unit.
Figure 5 - Base Mounted Furnace
As shipped location of hanger
support angle
Net Weight
Size 75 100 125 140 170 200 225 250 300 350 400
Limit
Lbs 104 104 126 128 150 172 194 216 262 306 328
Control
Suspending the Furnace
Airflow
Direction
The furnace is provided with four 15/32" diameter holes to provide
four-point suspension. To suspend the unit, cut lengths of 7/16"-16
threaded rod to provide unit height. See Figure 4A for details. NOTE:
A hanger adapter kit Option CK3 is available to facilitate suspension.
See Figure 4B.
Access
Panel
Access
Panel
10"
(254
mm)
Combustion
Air Inlet
Combustion Air Inlet
Keep clean and maintain 29"
(737mm) clearance for burner
rack service
6" (152mm)
minimum
clearance
6"
WARNING: Units must be level for proper
operation. Do not place or add additional weight
to the suspended furnace. See Hazard Levels,
page 2.
12" (305mm)
Hanger Support Angle
Form 421, Page 6
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Coupling Two, Three, Four or Five Furnaces using Optional Coupling Kits
Refer to illustrations and follow the instructions below.
Figure 6B - Installing Coupling Kit
Coupling Kit, Option CR1 (P/N
57963), for Two Furnaces
Qty P/N Description
Tie Plate
4"
1
2
1
2
57964 Filler Plate
2
57965 Tie Plate
9557 Threaded Socket Assembly
3
2
2
5095 3/8-16 x 1-1/4" lg Hex
Head Bolts
5197 Split Ring Lock Washer
Unit
2
6
Unit
1
5
20 11813 #10 x 1/2" lg Sheetmetal
Screws
7
7
Additional Kits:
3 Furnaces - Option CR2 (P/N 82654)
4 Furnaces - Option CR3 (P/N 82655)
5 Furnaces - Option CR4 (P/N 82656)
Item
Description
Socket Assembly
Bolt
1
2
3
5
6
7
Lockwasher
Spotweld Nut
Tie Plate
Figure 6A - Coupling Furnaces
Hanger Angles
Instructions for Coupling Furnaces (Refer to Figures 6A,
6B, 6C and 6D)
1. Attach the tie plate to the first furnace using threaded socket assem-
blies. Tie plate must be positioned below the hanger angles. Secure
fasteners firmly.
2. Move the second furnace into position next to the first furnace. Tie
plate must be below the hanger angle. Secure the tie plate to the
hanger angle using the 3/8-16 bolts, the washers, and the spotweld
nuts on the tie plate.
3. Position the filler plates to furnaces as shown in Figure 6A. Using a
filler plate as a template, drill 1/8" diameter holes. Attach filler plates
using the sheet metal screws provided. Offset of filler plate allows
alignment with unit duct flanges. See Figure 6C.
4. Coupled units require access panels in the top or bottom of the
outlet duct for limit control service. See Figure 6D and Paragraph
11.
Figure 6C - Front View of Coupled Furnaces
Figure 6D - Top View of Coupled Furnaces (NOTE:
Access panel may be in top or bottom of ductwork.)
A + 2"
(51mm)
A
Limit
Control
Limit
Limit Control
Control
Access panel for
limit control
service and
observation of
coupled unit
Discharge Duct
Size
"A"
14-5/8"
75-100
371mm
371mm
371mm
371mm
371mm
371mm
860mm
125-140 17-3/8"
170
200
225
250
300
350
400
20-1/8"
22-7/8"
25-5/8"
28-3/8"
33-7/8"
39-3/8" 1000mm
44-7/8" 1140mm
RGM Form 421, Mfg No. 150492, Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Gas Piping and Pressures
WARNING: This appliance is equipped for a
maximum gas supply pressure of 1/2 pound, 8
ounces, or 14 inches water column. Supply
pressure higher than 1/2 pound requires
installation of an additional service regulator
external to the unit.
PRESSURE TESTING SUPPLY PIPING
Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve
from the gas supply line which is to be tested. Cap or plug the supply
line.
NOTE: To permit
burner removal,
this nipple must
extend beyond
edge of heater.
Test Pressures Below 1/2 PSI: Before testing, close the manual valve
on the heater.
All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI/Z223.1a (latest edition), published by
the American Gas Association or CAN/CGA-B149.1 and B149.2, pub-
lished by the Canadian Gas Association (See Paragraph 1). Gas supply
piping installation should conform with good practice and with local
codes.
Figure 7 - Supply Piping Connection
with a minimum 3" drip leg. Local codes may require a minimum drip
leg longer than 3" (typically 6").
Gas connection sizes are included in the Dimensional Tables in Para-
graph 3. After all connections are made, disconnect the pilot supply at
the control valve and bleed the system of air. Reconnect the pilot line
and leak-test all connections by brushing on a soap solution.
Duct furnaces for natural gas are orificed for operation with gas having
a heating value of 1000 (+ or - 50) BTUH per cubic ft. If the gas at the
installation does not meet this specification, consult the factory for
proper orificing.
Gas Connection to Single-Stage Valve
(Not Gas Supply Line Size)
Pipe joint compounds (pipe dope) shall be resistant to the action of
liquefied petroleum gas or any other chemical constituents of the
gas being supplied.
Unit Size
75-250
300-400
Natural Gas
Propane Gas
1/2"
1/2"
3/4"
1/2"
WARNING: All components of a gas supply
system must be leak tested prior to placing
equipment in service. NEVER TEST FOR
LEAKS WITH AN OPEN FLAME. Failure to
comply could result in personal injury, property
damage or death.
Install a ground joint union and manual shut-off valve upstream of the
unit control system, as shown in Figure 7. The 1/8" plugged tapping in
the shut-off valve provides connection for supply line pressure test
gauge. The National Fuel Gas Code requires the installation of a trap
Manifold or Orifice Pressure Settings
Measuring manifold gas pressure cannot be done until the heater is in
operation. It is included in the steps of the "Check-Test-Start" proce-
dure in Paragraph 24. The following warnings and instructions apply.
WARNING: Manifold gas pressure must never
exceed 3.5" w.c. for natural gas and 10" w.c. for
propane gas.
Capacity of Piping
Cubic Feet p er Hour based on 0.3" w.c. Pressure Drop
Sp ecific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BT U /Cubic Ft)
Sp ecific Gravity for Prop ane Gas -- 1.6 (Prop ane G as -- 2550 BT U/Cubic Ft)
Length
of
Diameter of Pipe
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
20'
30'
40'
50'
60'
70'
80'
90'
100'
125'
150'
175'
200'
92
73
63
56
50
46
43
40
38
34
31
28
26
56
45
38
34
31
28
26
24
23
21
19
17
16
190
152
130
115
105
96
90
84
79
72
116
93
79
70
64
59
55
51
48
44
39
36
34
350
285
245
215
195
180
170
160
150
130
120
110
100
214
174
149
131
119
110
104
98
92
79
73
67
730
590
500
440
400
370
350
320
305
275
250
225
210
445
360
305
268
244
226
214
195
186
168
153
137
128
1100
890
760
670
610
560
530
490
460
410
380
350
320
671
543
464
409
372
342
323
299
281
250
232
214
195
2100
1650
1450
1270
1105
1050
990
930
870
780
710
1281
1007
885
775
674
641
604
567
531
476
433
397
372
64
59
55
650
610
61
Note: When sizing sup p ly lines, consider p ossibilities of future exp ansion and increased requirements.
Refer to National Fuel Gas Code for additional information on line sizing.
Form 421, Page 8
Download from Www.Somanuals.com. All Manuals Search And Download.
For Natural Gas: Manifold gas pressure is regulated by
the combination valve to 3.5" w.c. Inlet pressure to the valve
must be a minimum of 5" w.c. or as noted on the rating
plate and a maximum of 14" w.c.
Instructions for Checking Manifold Pressure:
1) With the manual valve (on the combination valve) positioned to prevent flow to
the main burners, connect a manometer to the 1/8" pipe outlet pressure tap in the
valve. NOTE: A manometer (fluid-filled gauge) is recommended rather than a
spring type gauge due to the difficulty of maintaining calibration of a spring type
gauge.
For Propane Gas: Manifold gas pressure is regulated by
the combination valve to 10" w.c. Inlet pressure to the valve
must be a minimum of 11" w.c. and a maximum of 14" w.c.
2) Open the valve and operate the heater. Measure the gas pressure to the mani-
fold. Normally adjustments should not be necessary to the factory preset regulator.
Before attempting to measure or adjust manifold gas pres-
sure, the inlet (supply) pressure must be within the speci-
fied range for the gas being used both when the heater is in
operation and on standby. Incorrect inlet pressure could
cause excessive manifold gas pressure immediately or at
some future time.
If adjustment is necessary, set pressure to correct settings by turning the regulator
screw IN (clockwise) to increase pressure. Turn regulator screw OUT (counter-
clockwise) to decrease pressure.
Consult the valve manufacturer's literature provided with the furnace for more
detailed information.
10. Venting
WARNING: Failure to provide proper venting
could result in death, serious injury, and /or
property damage. Unit must be installed with a
flue connection and proper vent to the outside of
the building. Follow installation codes listed in
Paragraph 1 and all venting instructions. Safe
operation of any gas-fired equipment requires a
properly operating vent system, correct provision
for combustion air (See Paragraph 5) and regular
maintenance and inspection. See Hazard Levels,
page 2.
WARNING: Units installed in multiples require
individual vent pipe runs and vent caps.
Manifolding of vent runs is not permitted due to
possible recirculation of combustion products
into the building and possible back pressure
effects on the combustion air proving switch.
Comply with the specific requirements and instructions in the follow-
ing paragraphs.
Specific Venting Requirements (read all before installing)
1. Venter (Flue) Outlet
Venter Outlet
Diameter
Size
Venting must be in accordance with the National Fuel Gas Code Z223.1
or CAN/CGA B149.1 and B149.2, Installation Code for Gas Burning
Appliances and Equipment, and all local codes. Local requirements
supersede national requirements.
75 - 200
225 - 250
300 - 400
4"
5"
6"
These power-vented units are designed to operate safely and efficiently
with either a horizontal or vertical vent. (Horizontal vent run is recom-
mended for maximum fuel savings.) Use either vent pipe approved for
a Category III heater or appropriately sealed single-wall pipe. Or, if at
least half of the equivalent length of the vent system is vertical, vent
pipe approved for a Category I heater may be used. A vent cap of a type
approved for use with this heater is required. If a vent cap is shipped
with the heater, it is packaged attached to the venter housing. Detach
the vent cap from the housing.
Venter Outlet Attachment Requirements:
o If the pipe used in the vent run is larger than the diameter of the
venter outlet (See Vent Length Table 2), make the transition at the
venter outlet.
o The venter is factory-installed as illustrated in Figure 8A. If re-
quired, the venter housing may be rotated as shown in Figure 8B.
The vent may be run in either of the three directions as indicated by
1, 2, and 3 in the illustrations. Follow the instructions to rotate the
venter housing.
Figure 8A - Factory-Installed Position of the Venter
Housing
Instructions for Rotating Venter Housing
Figure 8B -
1. Remove the three screws that attach the venter
Alternate
housing to the outlet duct (pipe from furnace
to the venter). The assembly will remain in
Position of
the Venter
place.
Housing
2. Remove the three screws holding the motor
plate to the venter housing. Holding the motor,
rotate the venter housing to the alternate posi-
tion (Figure 8B). Re-attach the motor plate to
the housing. (To ensure correct venter wheel
alignment, pre-punched holes are provided in
the motor plate.)
3. Using the holes in the venter housing as a tem-
WARNING: Only the venter housing may be rotated. The
motor and combustion air proving switch MUST remain as
received from the factory. Unsafe or improper operation will
result if the standard position is varied. See Paragraph 16 for
explanation of combustion air proving switch.
plate, drill three 1/8" diameter holes in the out-
let duct. Re-attach the venter housing to the
outlet duct using the three screws removed in
Step 1. Rotation is complete.
RGM Form 421, Mfg No. 150492, Page 9
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Vent System Joints - Vent system joints depend on the installa-
tion and the type of pipe being used.
10. Venting (cont'd)
Specific Venting Requirements (read all before installing) (cont'd)
If installed as a Category III heater (required if more than half of
the equivalent length of the vent system is horizontal) and single-
wall vent pipe is being used, use at least two non-corrosive screws
per vent pipe joint and seal all joints to prevent leakage of flue
gases into the building. For sealing joints, the use of Aluminum or
TEFLON® (trademark of DuPont Corporation) tape suitable for
550oF is recommended (required in California). Vent tape of this
type is available from the heater manufacturer as P/N 98266.
If installed as a Category III heater (required if more than half of
the equivalent length of the vent system is horizontal) and vent
pipe specifically approved for Category III vent systems is be-
ing used, follow the pipe manufacturer's instructions for proper
sealing.
If installed with a Category I vent system (allowed only if at
least half of the equivalent length of the vent system is vertical),
use at least two non-corrosive screws per vent pipe joint on single-
wall pipe or follow the pipe manufacturer's instructions for joining
double-wall pipe.
5. Vent System Support - Support lateral runs every six feet, us-
ing a non-combustible material such as strap steel or chain. Do not
rely on the heater for support of either horizontal or vertical vent
pipe.
1. Venter (Flue) Outlet (cont'd)
Venter Outlet Attachment Requirements (cont'd):
o A minimum of 12" of straight pipe is required at the venter outlet
(or transition fitting) before installing an elbow in the vent system.
An elbow should never be attached directly to the venter.
2. Vent Pipe
If installed with a horizontal vent run, use either vent pipe approved
for a Category III heater or appropriately sealed 26-gauge galvanized
steel or equivalent single-wall pipe. If at least half of the equivalent
length of the vent system is vertical, vent pipe approved for a Category
I heater may be used. Single-wall pipe or double-wall (Type B) vent
pipe are suitable for use with a Category I heater.
Use only one of the flue pipe diameters listed in the Vent Length Tables
for the furnace size being installed.
3. Vent Length Tables
Table 1: Maximum Permissible Vent Lengths with
S tandard Vent Pipe Diameters
Vent Pipe
Size Diameter
(inches)
Maximum
Vent Length
Equivalent Straight
Length* - ft (M)
90O El bo w 4 5 O El bo w
(see Note 1 below)
40 ft (12.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
50 ft (15.2 M)
75
4
4
4
4
4
4
5
5
6
6
6
6 (1.8)
7 (2.1)
7 (2.1)
7 (2.1)
7 (2.1)
7 (2.1)
9 (2.7)
9 (2.7)
3 (.9)
6. Condensation - Single wall vent pipe exposed to cold air or run
through unheated areas must be insulated. Where extreme conditions
are anticipated, install a means of condensate disposal.
100
125
140
170
200
225
250
300
350
400
3.5 (1.1)
3.5 (1.1)
3.5 (1.1)
3.5 (1.1)
3.5 (1.1)
4.5 (1.4)
4.5 (1.4)
7. Vent Terminal (Pipe and Vent Cap) - The vent system must be
terminated with a suitable vent cap that is the same size as the vent run.
Heaters with an A.G.A. rating plate that are ordered with an optional
vent cap and all heaters with a C.G.A. rating plate have a vent cap
packaged with the heater. If the "standard" size (Vent Length Table 1)
of vent pipe is used, install the vent cap provided. If a vent cap is not
included or if a non-standard size (Vent Length Table 2) of vent pipe is
used, a field-provided cap must be used. If the vent cap is field-sup-
plied, use a Type L Breidert Air-x-hauster® or equivalent vent cap.
(Type L Air-x-hauster® is a trademark of The G. C. Breidert Com-
pany.) Use of a vent cap supplied by the pipe manufacturer is not
permitted; the vent cap must be the type approved for use with this
heater. A different style vent cap could cause nuisance problems or
unsafe conditions.
11 (3.4) 5.5 (1.7)
11 (3.4) 5.5 (1.7)
11 (3.4) 5.5 (1.7)
*Reduce the maximumvent length by the amount indicated
for each elbow used.
Table 2: Optional Maximum Permissible Vent Lengths
(Requires an increase in vent pipe diameter.)
See the illustrations in Figures 9 and 10 for requirements of both verti-
cal and horizontal vent termination. The vent terminal section may be
either single-wall or double-wall (Type B) vent pipe.
Vent Pipe
Size Diameter
(inches)
Maximum
Vent Length
Equivalent Straight
Length* - ft (M)
90O El bo w 4 5 O El bo w
(see Note 1 below)
60 ft (18.3 M)
70 ft (21.3 M)
70 ft (21.3 M)
70 ft (21.3 M)
70 ft (21.3 M)
80 ft (24.3 M)
90 ft (27.4 M)
If double-wall pipe is used in the vent terminal, follow the instructions
below to attach the vent cap and to connect the double-wall pipe to the
single-wall vent pipe run.
170
200
225
250
300
350
400
5
5
6
6
7
7
7
9 (2.7)
9 (2.7)
4.5 (1.4)
4.5 (1.4)
11 (3.4) 5.5 (1.7)
12 (3.7) 6 (1.8)
INSTRUCTIONS FOR DOUBLE WALL PIPE INSTALLA-
TION: Material Required: Double wall (Type B) Vent Pipe (Note:
Using only one piece of vent pipe is recommended.); a thimble de-
signed for double wall pipe (if construction is combustible); six
3/4" long sheetmetal screws; the vent cap; and a tube of silicone
sealant
13 (4.0) 6.5 (2.0)
13 (4.0) 6.5 (2.0)
14 (4.3)
7 (2.1)
Instructions to attach VENT CAP to DOUBLE WALL (Type B)
VENT TERMINAL
Look for the "flow" arrow on the vent pipe. Attach the vent cap to
the "exhaust" end of the double wall pipe.
*Reduce the maximumvent length by the amount indicated
for each elbow used.
NOTE 1: If the system contains all vertical pipe or a combination
of vertical and horizontal vent pipe, the Maximum Permissible Vent
Length shown in Tables 1 and 2 may be increased one foot for each
foot of vertical pipe, up to a maximum increase of 10 feet for Model
Sizes 75 - 125 and up to 20 feet for Model Sizes 140 - 400.
1) Slide the vent cap inside the pipe.
2) Drill a hole through the pipe and the vent cap. (Hole should be
slightly smaller than the sheet metal screw being used.) Using a
3/4" long sheet metal screw, attach the cap to the pipe.
3) Repeat Step 2) drilling and inserting two additional screws evenly
spaced (120° apart) around the pipe.
Form 421, Page 10
Download from Www.Somanuals.com. All Manuals Search And Download.
Instructions to connect the SINGLE WALL VENT system to a
DOUBLE WALL (Type B) VENT TERMINAL:
3) Repeat Step 2) drilling and inserting two additional screws evenly
spaced (120° apart).
1) Slide the single wall pipe inside the inner wall of the double-wall
terminal pipe.
2) Drill a hole through both walls of the double wall pipe and the
single wall pipe. (Hole should be slightly smaller than the sheet
metal screws being used .) Using a 3/4" long sheet metal screw,
attach the two pieces of pipe. Do not overtighten.
4) To seal the annular opening (the gap between the single and double
wall pipe), run a large bead of silicone sealant in the opening. The
bead of sealant must be large enough to seal the opening, but it is
not necessary to fill the full volume of the annular area.
Figu
Vert
Ven
Term
Figure 10 -
Horizontal
Vent
Terminal
Horizontal Vent Terminal Clearances
Minimum Clearances for Vent Termination
Location (all directions unless specified)
3 ft (0.9m) above
The location of the termination of the hori-
zontal vent system must be in accordance with
National Fuel Gas Code Z223.1. See table for
required minimum clearances.
Structure
Forced air inlet within 10 ft (3.1m)
Combustion air inlet of another appliance
6 ft (1.8m)
If the vent terminal is to be installed near
ground level, position it at least six inches
above maximum anticipated snow depth.
NOTE: Maintain the required clearance
from the wall to the vent terminal cap for
stability under wind conditions and to pro-
tect the building.
Door, window or gravity air inlet (any building 4 ft (1.2m) horizontally
opening)
4 ft (1.2m) below
3 ft (0.9m) above
Electric meter, gas meter * and relief equipment 4 ft (1.2m) horizontally
Gas regulator *
3 ft (0.9m)
Adjoining building or parapet
Grade (ground level)
6 ft (1.8m)
7 ft (2.1m) above
*Do not terminate the vent directly above a gas meter or service regulator.
RGM Form 421, Mfg No. 150492, Page 11
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Duct Connections
Figure 12A - Connecting Ductwork to the Furnace
1
Flanges on the heater turn out as shown.
Shape duct connection as shown -- "U" on top and bottom;
"L" on sides.
Figure 11 - Duct
Connection Dimensions
(inches)
2
3
4
Slide "U" form over heater flange making connection.
Form "U" strips to seal ends. Drill and lock with sheetmetal
screws.
Size
75, 100
125, 140
170
G
12-1/2" 318
15-1/4" 387
18"
457
20-3/4" 527
23-1/2" 597
26-1/4" 641
31-3/4" 806
37-1/4" 946
42-3/4" 1086
200
225
250
300
350
400
NOTE: If the furnace is equipped with a unit-mounted ductstat (Op-
tion AG3), the sensing bulb must be removed from the mounting bracket
(save the retainer clip) before the ductwork can be attached. See in-
structions in Paragraph 22 for re-mounting the sensor.
Figure 12B -
Attachment
of
F
Requirements and Suggestions for Connecting
and Installing Ducts
•
Type of Ductwork - The type of duct installation to be used de-
pends in part on the type of construction of the roof (whether wood
joist, steelbar joist, steel truss, pre-cast concrete) and the ceiling
(whether hung, flush, etc.).
•
•
Ductwork Material - Rectangular duct should be constructed of
not lighter than No. 26 U.S. gauge galvanized iron or No. 24 B & S
gauge aluminum.
Ductwork Structure - All duct sections 24 inches or wider, and
over 48 inches in length, should be cross broken on top and bottom
and should have standing seams or angle-iron braces. Joints should
be S and drive strip, or locked.
•
•
Through Masonry Walls - No warm air duct should come in con-
tact with masonry walls. Insulate around all air duct through ma-
sonry walls with not less than 1/2" (1" is recommended) of insula-
tion.
Through Unheated Space - Insulate all exposed warm air ducts
passing through an unheated space with at least 1/2" (1" is recom-
mended) of insulation.
•
•
Duct Supports - Suspend all ducts securely from adjacent build-
ings members. Do not support ducts from unit duct connections.
Duct Sizing - Proper sizing of the supply air ductwork is necessary
to ensure a satisfactory heating installation. The recognized author-
ity for such information is the Air Conditioning Contractors Asso-
ciation, 1228 17th Street N.W., Washington, D.C. 20036. A manual
covering duct sizing in detail may be purchased directly from them.
Figure 12C -The
seals between the
furnace and the
duct must be
mechanical. "U"
channel method is
illustrated here.
•
•
Removable Panels - The ducts should have removable access pan-
els on both upstream and downstream sides of the furnace. These
openings must be accessible when the furnace is in service and
should be a minimum of 6" x 10" in size so smoke or reflected light
may be observed inside the casing to indicate the presence of leaks
in the heat exchanger. The covers for the openings must be attached
in such a manner as to prevent leakage. See Figure 12A.
Supply Air Duct/Furnace Horizontal Connection - The seal be-
tween the furnace and the duct must be mechanical. Duct connec-
tion should be made with "U" type flanges on the top and bottom of
the connecting duct. Slide the duct over the flanges of the heater
giving an airtight fit. Provide "U" type channels for the other side
flanges to ensure tight joints. Use sheetmetal screws to fasten ducts
and "U" channels to the furnace flange. See Figures 12B and 12C.
CAUTION: Joints where ducts attach to furnace
must be sealed securely to prevent air leakage
into burner rack area. Leakage can cause poor
combustion, pilot problems, shorten heat
exchanger life and cause poor performance. See
Hazard levels, page 2.
Form 421, Page 12
Download from Www.Somanuals.com. All Manuals Search And Download.
12. Condensate Drain, Option CS1, for Furnaces Used with
Refrigeration Systems
Figure 13 - Condensate Drain, Option CS1 (P/N 31765)
These furnaces are certified for installation upstream or downstream
from refrigerated units supplying air below the dew point of the ambi-
ent air surrounding the furnace. When installed downstream from a
refrigeration system, condensation will form and therefore, adequate
provision must be made to dispose of the condensate. A drain flange,
Option CS1, may be installed on the furnace casing as shown in Figure
13. When using Option CS1, seal all holes in the bottom pan. Termi-
nate the drain outside of the building. NOTE: A 4-inch minimum clear-
ance is required under the furnace if a 90o street elbow is used.
Seal holes in bottom pan. Terminate drain outside of
building. Periodic cleaning of the condensate collector and
disposal system is required.
Periodic cleaning of the condensate collection and the disposal system
is required.
13. Duct Furnace Air Flow Requirements
The duct furnace must be installed on the positive pressure side of the field supplied blower. The air throughput must be within the CFM range
stated on the heater rating plate. The air distribution must be even over the entire heat exchanger. Turning vanes should be employed in elbows or
turns in the air inlet to ensure proper air distribution (See Paragraph 15). If it is determined that the blower CFM is greater than allowed or desirable,
see Paragraph 14 for instructions on determining the correct size of bypass duct required. To determine temperature rise, the inlet and outlet air
temperatures should be measured at points not affected by heat radiating from the heat exchanger. The following charts show the approved
temperature rise range with the required CFM and the internal pressure drop for each size of unit.
Model EEDU (80% thermal efficient)
Size
75
100
125
140
170
200
225
250
300
350
400
Temperature
Rise
CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D.
1105 0.24 1475 0.43 1840 0.49 2065 0.65 2505 0.67 2945 0.67 3315 0.69 3685 0.67 4420 0.70 5160 0.75 5895 0.77
920 0.16 1225 0.30 1535 0.33 1720 0.43 2085 0.46 2455 0.46 2765 0.47 3070 0.45 3685 0.47 4300 0.52 4915 0.52
790 0.10 1050 0.21 1315 0.25 1475 0.32 1790 0.33 2105 0.35 2370 0.36 2630 0.34 3160 0.35 3685 0.38 4210 0.38
695 0.07 920 0.16 1150 0.20 1290 0.24 1565 0.25 1840 0.26 2070 0.27 2300 0.26 2765 0.27 3225 0.28 3685 0.28
615 0.05 815 0.12 1020 0.17 1145 0.20 1390 0.19 1635 0.20 1840 0.21 2045 0.20 2455 0.22 2565 0.23 3275 0.22
50°F
60°F
70°F
80°F
90°F
Model HEEDU (80% thermal efficient, high CFM)
Size
75
100
125
140
170
200
225
250
300
350
400
Temperature
Rise
CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D. CFM P.D.
2765 0.60 3685 1.09 4605 1.14 5160 1.50 6265 1.64 7370 1.64 8295 1.69 9215 1.67 11060 1.64 12900 1.64 14745 1.64
1840 0.28 2455 0.50 3070 0.52 3440 0.66 4175 0.73 4915 0.73 5530 0.75 6140 0.72 7370 0.73 8600 0.73 9830 0.73
1380 0.16 1840 0.28 2300 0.27 2580 0.36 3130 0.38 3685 0.39 4145 0.40 4605 0.40 5530 0.39 6450 0.40 7370 0.38
1105 0.12 1475 0.18 1840 0.18 2065 0.22 2505 0.24 2945 0.24 3315 0.26 3685 0.24 4420 0.24 5160 0.25 5895 0.24
920 0.10 1225 0.13 1535 0.14 1720 0.17 2085 0.17 2455 0.17 2765 0.18 3070 0.17 3685 0.17 4300 0.18 4915 0.17
850 0.08 1130 0.11 1415 0.12 1585 0.15 1925 0.14 2265 0.14 2552 0.15 2835 0.14 3400 0.14 3970 0.15 4535 0.15
20°F
30°F
40°F
50°F
60°F
65°F
--
--
--
--
--
--
--
-- 1790 0.12 2105 0.12 2370 0.13 2630 0.11 3160 0.12 3685 0.13 4210 0.13
70°F
14. Constructing Bypass Duct
Bypass CFM
Pressure Drop through the Furnace
Width 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50
When the CFM of air throughput is greater than desirable or permis-
sible for the unit, a bypass duct may be constructed. Follow these in-
structions to determine the correct size of the bypass duct.
"A"
3"
4"
5"
6"
7"
8"
9"
10"
490 530 610 700 780 830 900 960 1010
630 750 870 980 1090 1160 1250 1310 1400
850 1010 1190 1300 1410 1520 1640 1730 1810
1050 1290 1480 1650 1800 1940 2090 2200 2320
1250 1510 1760 1960 2180 2320 2500 2650 2800
1490 1810 2100 2350 2560 2760 2940 3110 3290
1700 2100 2400 2700 2970 3200 3400 3600 3800
1920 2350 2760 3090 3650 4020 4300 4550 4800
2) Subtract the allowable CFM from the actual CFM of the installa-
tion to determine how much air must be diverted through the by-
pass duct.
Example:
Blower CFM 3000
Allowable CFM -1790
Bypass CFM 1210
Figure 13 - Bypass Duct
Directions for Sizing Bypass Duct
1) From the tables in Paragraph 13, find the pressure drop (P.D.) and
3) Go to the column in the Bypass CFM Chart that is closest to the
pressure drop through the heater. Move down in that column until
you find the CFM closest to the answer in Step 2).
the allowable CFM for the furnace that is being installed.
Example:
Standard Size 170 @ 70oF temperature rise;
P.D. .33; CFM 1790
Example:
P.D. .35
Bypass CFM 1520
RGM Form 421, Mfg No. 150492, Page 13
Download from Www.Somanuals.com. All Manuals Search And Download.
15. Furnace Blower Connections
14. Bypass Duct (cont'd)
Requirements: Proper arrangements of blower and duct furnace with respect to
angle of approach of the duct connection and the arrangement of the discharge
opening of the blower are shown. Blowers should be bottom horizontal dis-
charge when coupled to the duct furnace. When a top horizontal discharge blower
is connected to the duct furnace, be sure that sufficient length of duct is pro-
vided to permit even flow of air at the end of the duct. Or, baffles may be in-
serted between the blower and the heater to assure an even flow of air across the
heat exchanger. See illustrations in Figure 14.
4) Move to the left column to find out the required size of
the bypass duct.
Example:
Bypass Duct
Size is 5"
Depth of the bypass duct is 18" on both inlet and outlet ends.
Bypass duct must be located on side opposite controls and 2"
from the heat exchanger side panel.
NOTE: Not all capacities are covered in this chart. If your
installation is not covered, the correct size may be determined
by consulting the factory representative.
WARNING: The furnace must be installed on the
positive pressure side of the air-circulating blower. See
Hazard Levels, page 2.
Figure 14
Form 421, Page 14
Download from Www.Somanuals.com. All Manuals Search And Download.
16. Combustion Air Proving
Switch
Figure - 15 - Field Wiring Connections
Connect Field
Wiring in the
Electrical Box
The combustion air proving switch is a pressure sensitive switch
that monitors air pressure to ensure that proper combustion air flow
is available. The switch is a single pole - normally open - device
which closes when a decreasing pressure is sensed in the outlet duct
of the flue gas collection box.
On start-up when the heater is cold, the sensing pressure is at the
most negative level, and as the heater and flue system warm up, the
sensing pressure becomes less negative. After the system has reached
equilibrium (about 20 minutes), the sensing pressure levels off.
If a restriction or excessive flue length or turns cause the sensing
pressure to become less than the switch setpoint, the pressure switch
will function to shut off the main burners. The main burners will
remain off until the system has cooled and/or the flue system resis-
tance is reduced. The Table on the below lists the approximate water
column negative pressure readings and switch setpoints for sea level
operating conditions.
Line Voltage
Connection Tabs
Operating Sequence
1. Set thermostat at lowest setting
2. Turn on the power to the unit.
3. Turn on main and pilot manual gas valve.
4. Set thermostat at desired setting.
Start-Up Cold Equilibrium Set Point "Off" Set Point "On"
5. Thermostat calls for heat energizing the venter motor.
6. Pressure switch closes, energizing the pilot gas valve and spark gap to
produce a pilot flame on each operating cycle. The sensing probe proves
the presence of pilot flame and energizes the safety switch portion of
the control. The switch action de-energizes the spark gap and ener-
gizes the main gas valve.
-1.0" w.c.
-0.60" w.c.
-0.48" w.c.
-0.65" w.c.
DANGER: Safe operation of this unit requires
proper venting flow. NEVER bypass
combustion air proving switch or attempt to
operate the unit without the venter running and
the proper flow in the vent system. Hazardous
conditions could result. See Hazard Levels,
page 2.
7. Fan control (Optional) senses heat exchanger temperature energizing
the fan or blower motor of the air handler.
8. If the pilot flame is extinguished during main burner operation, the
sensing probe detects the absence of the flame and causes the safety
switch to close the main valve. On units with standard intermittent
spark pilot systems, the spark gap recycles. On units with optional
spark ignition with lockout, if the pilot is not established within the
timing cycle (approximately 120 seconds), the unit locks out and must
be reset by interrupting power to the control circuit.
17. Electrical Supply and
Connections
Disconnect Switch
A disconnect switch is a required part of this installation. Switches are
available, as options or parts, or may be purchased locally. When ordered
as an optional component, the disconnect switch is shipped separately.
All electrical wiring and connections, including electrical ground-
ing MUST be made in accordance with the National Electric Code
ANSI/NFPA No. 70 (latest edition) or, in Canada, the Canadian Elec-
trical Code, Part I-C.S.A. Standard C22.1. In addition, the installer
should be aware of any local ordinances or gas company require-
ments that might apply.
The disconnect switch may be fusible or non-fusible. When installing, be
careful that the conduit and switch housing are clear of furnace panels
and inspection plates. Allow at least four feet of service room between
the switch and removable panels.
Check the rating plate on the heater for the supply voltage and cur-
rent requirements. A separate line voltage supply with fused discon-
nect switch should be run directly from the main electrical panel to
the furnace, making connection to leads in the junction box. All
external wiring must be within approved conduit and have a mini-
mum temperature rise of 63oF. Conduit from the disconnect switch
must be run so as not to interfere with the service panels of the
furnace.
Control Thermostat
A thermostat is not standard equipment but is an installation requirement.
Use either an optional thermostat available with the heater or a field-
supplied thermostat. Install according to the thermostat manufacturer's
instructions.
A 24 volt thermostat must be used to actuate low voltage gas controls. If
line voltage from the thermostat to the unit is desired, consult the factory
representative.
If the heater has field-installed options that require electrical con-
nections, consult the instruction sheet and wiring diagram supplied
in the option package.
Wiring between the thermostat and the heater must be suitable for a tem-
perature rise of 63oF. Labeled thermostat leads are provided in the heater
junction box for connection of thermostat wiring.
CAUTION: If any of the original wire as
supplied with the appliance must be replaced,
it must be replaced with wiring material having
a temperature rating of at least 105oC, except
for sensor lead wires which must be 150oC. See
Hazard Levels, page 2.
Thermostats should be located five feet above the floor on an inside wall,
not in the path of warm or cold air currents, not in corners where air may
be pocketed. Do NOT install on cold air walls. For specific connection
details, refer to instruction packet with the thermostat.
If more than one unit is cycled from one thermostat, separately activated
relays must be substituted at unit thermostat connections.
Specific wiring diagrams that include standard and factory-installed
options are included with the heater. Typical wiring diagrams are
on page 17.
RGM Form 421, Mfg No. 150492, Page 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical Wiring Diagrams -- Refer to the diagram supplied with the heater for specific
controls or optional equipment.
Single-Stage with Intermittent Spark Pilot System with or without Lockout
W.D. 110920
Field and Replacement Wiring Notes
1. Dotted wiring supplied by others.
2. Thermostat supplied as optional equipment.
3. Use #14 gauge wire for line wiring to unit.
4. Use #18 gauge wire for control wiring.
5. Line and blower motor branch circuit wire sizes should be of a size to
prevent voltage drops beyond 5% of supply line voltage.
6. On 208-230V units, the control transformer has dual voltage primary.
For 208 volt units, use black and red leads (cap yellow).
For 230 volt units, use black and yellow leads (cap red).
On 115 volt units, the control transformer is single voltage primary. Use
black and yellow leads for 115 volt.
Secondary side of transformer (24V), use blue and brown leads.
7. Sizes 75-250, 208 volts, the venter motor wires are black and white (cap
red).
Sizes 75-250, 230 volts, the venter motor wires are red and white (cap
black).
Sizes 75-250, 115 volts, the venter motor wires are black and white.
Sizes 300-400, all voltages, the venter motor wires are black and white.
CAUTION: If any of the original wire as supplied
Field Control Wiring - Length and Gauge
with the appliance must be replaced, it must be
Minimum
Recommended Wire
Gauge
Total Wire
Length
Distance from Unit
to Control
replaced with wiring material having a
temperature rating of at least 105oC, except for
sensor lead wires which must be 150oC. See
Hazard Levels, page 2.
150'
250'
350'
75'
125'
175'
#18 gauge
#16 gauge
#14 gauge
Form 421, Page 16
Download from Www.Somanuals.com. All Manuals Search And Download.
Two-Stage with Intermittent Spark Pilot System with or without Lockout
W.D. 110824
6
L1
(HOT)
L2
(COM)
7
LINE/1/60
OPERATING SEQUENCE
1. SET THERMOSTAT SWITCH AT "OFF" POSITION.
VENTER MOTOR
(SEE NOTE #7
FOR WIRING)
8
2. TURN ON MAIN AND PILOT MANUAL GAS VALVES.
VENTER RELAY
CONTACTS
3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT SWITCH AT "ON" POSITION.
5. LOW STAGE OF THERMOSTAT CALLS FOR HEAT ENERGIZING THE VENTER MOTOR.
6. PRESSURE SWITCH CLOSED ENERGIZING THE PILOT GAS VALVE AND SPARK GAP
TO PRODUCE A PILOT FLAME ON EACH OPERATING CYCLE. THE SENSING PROBE
PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZES THE SAFETY
SWITCH PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE
SPARK GAP AND ENERGIZES THE LOW STAGE GAS VALVE.
BK
2
BK
4
BK OR R
W
9
BK OR R
LIMIT CONTROL
BK BK
R
LINE VOLT
BK
Y
10
11
12
13
14
15
16
17
18
19
20
21
22
40 VA. CONTROL
TRANSFORMER
7. HIGH STAGE OF THERMOSTAT CALLS FOR HEAT ENERGIZING THE HIGH STAGE
GAS VALVE, FIRING UNIT AT FULL RATE.
BL
BL
BR
8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION THE
SAFETY SWITCH CLOSES THE MAIN VALVE AND RECYCLES THE SPARK GAP.
ON UNIT EQUIPPED WITH G77ONGC-4 LOCKOUT CONTROL, IF PILOT IS
NOT ESTABLISHED WITHIN 120 SECONDS (APPROX.) UNIT LOCKS OUT
AND MUST BE REST BY INTERRUPTING POWER TO CONTROL CIRCUIT.
(SEE LIGHTING INSTRUCTIONS)
24V
O
O
12
BR
VENTER
RELAY COIL
9
CR
3
1
NOTES
1. DOTTED WIRING SUPPLIED AND INSTALLED BY OTHERS.
BR
BR
2. CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE
MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING
A TEMPERATURE RATING OF A LEAST 105 DEGREES C., EXCEPT FOR ENERGY
CUT-OFF OR SENSOR LEAD WIRE WHICH MUST BE 150 DEGREES C.
3. LIMIT WIRE TO BE #18 GA. 200 C. SF-1 OF SEW-1.
4. USE #14 GA. WIRE FOR LINE WIRING TO UNIT.
5. LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZES SHOULD BE OF A SIZE
TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.
6. ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.
FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).
GRND.
STRIP
W
FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).
ON 115V. UNITS THE CONTROL TRANSFORMER IS SINGLE VOLTAGE PRIMARY.
USE BLACK AND YELLOW LEADS FOR 115V.
SECONDARY SIDE OF TRANSFORMER (24V.) USE BLUE AND BROWN LEADS.
O7.N 75-250 208V UNITS, THE VENTER MOTOR WIRES ARE BLACK AND WHITE (CAP RED)
ON 75-250 230V UNITS, THE VENTER MOTOR WIRES ARE RED AND WHITE (CAP BLACK)
ON 75-250 115V UNITS AND 300-400 UNITS ALL VOLTAGES, THE VENTER MOTOR WIRES
ARE BLACK AND WHITE.
G67BG-5
W.R. TWO STAGE
REDUNDANT
GAS VALVE
RECYCLE
OR
G770NGC-4
LOCKOUT
BK
3
1
IGNITION
CONTROLLER
FLAME SENSING
PROBE
FIELD CONTROL WIRING
TOTAL WIRE MINIMUM RECOMMENDED
BR
R
4
2
LENGTH
150 FEET
250 FEET
350 FEET
WIRE SIZE
#18 GA.
#16 GA.
#14 GA.
O
PRESSURE
SWITCH
BK
IGNITOR
GRND
O
BK
W1
2
BL
1
4
3
CHASSIS GRND.
R
R
W2
18. Limit Switch
Figure 16 - Access
to the limit switch
depends on the
installation
A non-adjustable high limit switch mounted at the outlet air side of the
heat exchanger acts to shut off the gas supply in the event of air handler
motor failure, lack of correct air flow (See Paragraph 13), or restriction
due to filters and/or duct design. See Figure 16 for mounting and ser-
vice.
Depending on accessibility, the limit switch may be serviced from ei-
ther the outside of the unit or from the inside through the access panel
in the discharge duct. When units are installed side by side, the service
access panel must be in either the top or bottom of the ductwork for
limit switch service. (See Paragraphs 8 and 11.)
View of limit
switch from
"inside" the
furnace
WARNING: If you turn off the power supply,
turn off the gas. See Hazard Levels, page 2.
Access to
limit switch
from
"outside"
the furnace
RGM Form 421, Mfg No. 150492, Page 17
Download from Www.Somanuals.com. All Manuals Search And Download.
19. Fan Control (Optional,
Field Installed)
NOTE: Required with makeup air gas control options; see
Paragraphs 22 and 23.
Figure 17 - Installation of Optional Fan Control
Kit, Option CQ1 (P/N 57960)
1. Fan control provides the following: a) Delay of fan op-
eration preventing circulation of cold air, and b) Fan op-
eration as long as the unit is hot.
2. The fan control provides additional safety by keeping the
fan in operation in the event that the gas valve fails to
close when the thermostat is satisfied.
3. To be sure that the fan can continue to operate, the power
supply to the heater MUST NOT be interrupted except
when servicing the heater.
4. If the customer wants the heater off at night, the gas valve
circuit SHOULD BE OPENED by a single pole switch
wired in series with the thermostat. Some thermostats are
provided with this feature. Multiple units controlled from
a single thermostat are shut off in the same manner. For
proper operation, be sure fan control wiring is observed.
See Figure 17 for installation of fan control and wiring.
WARNING: If you turn off the power
supply, turn off the gas. See Hazard
Levels, page 2.
Location of the Fan
Control Mounting Holes
Typical Fan Control
Wiring (W.D. 145977)
Install the gasket supplied in
the option kit between the
fan control and the duct.
Drill 13/16" diameter hole for element
Drill four 1/8" diameter holes for screws
4"
(102mm)
Fan Control P/N 147611,
Honeywell Model
L4064A1347
3"
(76mm)
3/4"
(19mm)
3"
(76mm)
Heater
2-3/8"
(60mm)
Discharge Duct
Recommended dial setting for most
conditions 130oF ON and 100oF OFF
DP-ST Control Switch (Used with Options
AG3, AG8, AG9, AG15, and AG16)
Form 421, Page 18
Download from Www.Somanuals.com. All Manuals Search And Download.
20. Gas Valve
Figure 18 - Ductstat/Sensing Bulb Locations for
Furnace with Option AG3
All furnaces are equipped with a 24-volt combination valve which
includes the automatic electric on-off valve controlled by the room
thermostat, the pressure regulator, the safety pilot valve, and the
manual shutoff valve. The standard gas valve allows for single-stage
control from a single-stage, 24-volt thermostat.
The ductstat provided with Op-
tion AG3 is attached to the side
of the furnace at the factory.
The sensor is mounted on a
bracket on the inner part of
the furnace duct side.
WARNING: The operating valve is the prime
safety shutoff. All gas supply lines must be free
of dirt or scale before connecting the unit to
ensure positive closure. See Hazard Levels, page
2.
Side
View
Ductstat
Front
View
Bulb
Retaining
Clip
Ductstat
Bracket
21. Optional Two-Stage Operation -
Heating Only Application
Sensing
Bulb
NOTE: This option is not available on Size 75 using propane gas.
The standard combination control valve is replaced with a two-stage
combination gas control valve providing for low fire or high fire
operation controlled by a two-stage thermostat. First stage (low fire)
is factory set (not field adjustable). Both high and low stages are
controlled by a Servo regulator, maintaining constant gas input un-
der wide variations in gas supply pressure. See instructions packed
with the unit for specific gas valve specifications, wiring, and oper-
ating instructions.
Du
Sensing Bulb
Bracket
The Sensor and the ductstat are connected by a permanently attached
capillary tubing. In order to attach the discharge ductwork, the sensor
must be removed form the bracket (save the retaining clip) and the
capillary tubing moved out of the way. After the ductwork is attached
to the furnace (See Paragraph 12), a hole must be made in the duct-
work to allow for the sensor to be re-installed on the bracket (capil-
lary tubing with sensor will run through the hole). A removable ac-
cess panel must be provided in the ductwork as shown in Figure 12A,
Paragraph 12.
22. Optional Two-Stage Operation -
Makeup Air Application
NOTES: Requires field installed fan control, see Paragraph 19. This
option is not available on Size 75 using propane gas.
Two-stage makeup air units are equipped with a two-stage gas valve,
but instead of control from a two-stage room thermostat, the outlet
air temperature is monitored and controlled by a two-stage ductstat.
When the discharge air temperature drops to the setpoint, low fire is
energized. If low fire cannot satisfy the ductstat setting, high fire is
energized.
Parts Required and Instructions:
Since the sensor is larger than
Qty P/N
Description
the tubing, a gasket and gasket
retainer plate are needed to plug
the hole and protect the capillary
tubing where it passes through
1
1
7726 Gasket
7727 Gasket Retainer Plate
Makeup air applications are usually adjusted to discharge an outlet
air temperature between 65oF and 75oF. In all applications, the al-
lowable temperature rise of the furnace in the installation dictates the
limits of the ductstat temperature setting.
the ductwork. These parts were shipped loose with the furnace. Two
field-supplied sheet metal screws will be needed to attach the plate.
1) Drill the Holes - Refer to the illustration below and select a loca-
tion on the ductwork so that a minimum length of capillary tubing
will be inside the ductwork. Following the pattern, drill holes in
the ductwork.
Depending on the option selection, the factory-installed sensor is
either field-connected by capillary tubing to the unit-mounted ductstat
(Option AG3), Figures 18 and 19, or electrically connected to a re-
mote electronic remote temperature selector (Options AG15 or AG16,
Figure 20). The remote temperature selector is available with or with-
out a display module.
Optional Ductstat with Capillary Tubing (Option AG3) -- The
ductstat is attached to the side of furnace and is connected by capil-
lary tubing to the sensor which is mounted on a bracket on the inner
part of the furnace duct side (See Figure 18). In order to attach the
discharge ductwork to the furnace, the sensor must be removed from
the bracket and the capillary tubing moved out of the way. Follow
the illustrated instructions in Figure 18 for re-connecting the ductstat
after the ductwork is attached.
2) Re-Mount the Sensor on the Bracket - Push the sensor through
the hole. Remove the ductwork access plate. Reaching through
the access hole, use the retaining clip to re-mount the sensor on
the bracket.
3) Install the Gasket - Slide the gasket and hole retainer plate over
the capillary tubing. With the gasket next to the ductwork, attach
the hole retaining plate with field-supplied sheet metal screws (as
illustrated above). Close the ductwork access panel.
The ductstat dial is illustrated in Figure 19. The dial has an adjust-
able range from 60oF to 100oF with a fixed differential of 2-1/2oF.
Due to different CFM settings and outside air temperatures, the aver-
age downstream outlet air temperature may not match the ductstat
exactly. After the installation is complete, adjust the ductstat setpoint
to achieve the desired average outlet air temperature.
RGM Form 421, Mfg No. 150492, Page 19
Download from Www.Somanuals.com. All Manuals Search And Download.
els. Electronic modulation control systems for makeup air applications
controlled by a duct sensor and temperature selector (55-90oF) are iden-
tified as either Option AG8 or Option AG9. The temperature selector
setting for Option AG8 is on the amplifier; Option AG9 has a remote
temperature selector. Both systems are available with an override ther-
mostat. Options AG8 and AG9 for makeup air applications apply to
duct furnace and packaged systems.
22. Optional 2-Stage Operation (cont'd)
Dial has no temperature markings. Pin on adjustment
screw pointing to "B" equals approximately 70oF.
Computer Controlled Electronic Modulation between 50% and
100% Firing Rate (Option AG21) - With this
option the furnace is equipped with a Maxitrol A200
Figure 19 -
Ductstat
Control in
Option AG3
(Mounted in
inverted
signal conditioner which operates much the same
way as the amplifier above to control the regulator
valve. The conditioner accepts an input signal of
either 4-20 milliamps or 0-10 volts from a customer-
supplied control device such as a computer. With the dip switches on
the conditioner in the "on" positions, the conditioner accepts a 4-20
milliamp signal. In the "off" positions, the conditioner accepts a 0-10V
signal. The conditioner converts the signal to the 0 to 20 volt DC cur-
rent required to control the modulating valve.
position)
Optional Ductstat with Electronic Remote Setpoint Module (Op-
tions AG15 and AG16) -- The field-installed sensing probe is field-
wired to a remote temperature selector with a temperature operating
range to 130oF. The remote modules and a required transformer are
shipped separately for field installation. (Do not wire the remote mod-
ule to the control transformer on the furnace.) Follow the wiring dia-
gram with the unit and the manufacturer's instructions for wiring and
installation. There will be one module for selecting temperature and
one-stage adder module. Option AG16 includes the digital display
module. See Figure 20.
24. Pilot and Ignition Systems
A gas-fired intermittent pilot is standard. The vertical pilot is located
under the aeration panel on the control end of the burner tray and is
accessible only after the burner rack has been removed. Remove the
pilot for maintenance or service, such as checking the wiring and clean-
ing. (See Paragraph 30.) All pilots are target type with lint-free feature.
Pilot gas pressure should be the same as supply line pressure. (See
Paragraph 9.) If required, adjust the pilot flame length to approximately
1-1/4" with the pilot adjustment screw in the control valve body.
CAUTION: The remote temperature selector
heat/cool selector switch is factory-set in cool
position. To function properly, set switch to heat
position.
NOTE: This model furnace manufactured prior to 11/95 had a hori-
zontal pilot with a spark gap of 7/64".
Intermittent Spark Ignition Safety Pilot Systems -- There are two
types of intermittent spark pilots -- one type shuts off the pilot gas flow
between the cycles and the other not only shuts off the pilot gas flow
between cycles but also has a lockout device that stops the gas flow to
the pilot if the pilot fails to light in 120 seconds. This lockout feature
requires manual reset by interruption of the thermostat circuit. Pro-
pane units require the spark ignition system with the lockout device.
Figure 20 - Remote
Temperature
Selector, Stage-
Adder Module, and
Optional Display
Module for Ductstat
in Two-Stage
Ignition Controller -- As part of the intermittent safety pilot systems,
the ignition controller provides the high voltage spark to ignite the
pilot gas and also acts as the flame safety device. After ignition of the
pilot gas, the ignition controller electronically senses the pilot flame. A
low voltage DC electrical signal is imposed on the separate metal probe
in the pilot assembly. The metal probe is electrically insulated from
ground. The pilot flame acts as a conduction path to ground complet-
ing the DC circuit and proving pilot flame. With pilot flame proven,
the ignition controller energizes the main gas valve.
Makeup Air Control
Options (Option
AG15 or AG16)
23. Optional Electronic Modulation
Note: Requires field-installed fan control.
The type and capability of the electronic modulation system, depends
on the option selected. Electronic modulation options are identified by
a suffix to the Serial No. printed on the heater rating plate. AG7 is
identified as MV-1; AG8 is identified as MV-3; AG9 is identified as
MV-4; and AG21 is identified as MV-A.
If no spark occurs, check the following:
a) Voltage between blue and white terminals (non-lockout type pilot)
and Terminals 2 and 5 (lockout type pilot) on the ignition controller
should be at least 20 volts and no higher than 32 volts. Refer to
Troubleshooting (Paragraph 32) if no voltage is observed.
b) Short to ground in the high tension lead and/or ceramic insulator.
c) Pilot spark gap should be approximately .100". (NOTE: This model
furnace manufactured prior to 11/95 had a horizontal pilot with a
spark gap of 7/64".)
Electronic Modulation between 50% and 100% Firing Rate (Op-
tions AG7, AG8, AG9) - Depending on the heat requirements as es-
tablished by the thermistor sensor, the burner modulates between 100%
and 50% firing. The thermistor is a resistor that is temperature sensi-
tive in that as the surrounding temperature changes, the Ohms resis-
tance changes through the thermistor. This change is monitored by the
solid state control center (amplifier) which furnishes varying DC cur-
rent to the modulating valve to adjust the gas input.
NOTE: When checking for spark with the pilot burner assembly re-
moved from the burner rack, the pilot assembly must be grounded to
the heater for proper spark.
Each modulating valve is basically a regulator with electrical means of
raising and lowering the discharge pressure. When no DC current is
fed to this device, it functions as a gas pressure regulator, supplying
3.5" w.c. pressure to the main operating valve.
If the above conditions are normal and no spark occurs, replace the
ignition controller.
If the main gas valve fails to open with a normal full size pilot flame
established, check for the following:
a) Voltage between black and brown leads on the main gas valve is 20
to 32 VAC and there is no main gas flow with the built-in manual
valve in FULL OPEN position -- the main valve is defective.
Refer to the wiring diagram supplied with the furnace for proper wir-
ing connections. Electronic modulation for heating controlled by a spe-
cially designed room thermostat (60o-85oF) is identified as Option AG7
and is available on unit heater, duct furnace and packaged heater mod-
Form 421, Page 20
Download from Www.Somanuals.com. All Manuals Search And Download.
b) No voltage between black and brown leads on the main
gas valve -- check for disconnected or shorted flame sen-
sor lead or flame sensor probe.
26. Burner Air Adjustment
Burner air shutters are not normally required on natural gas furnaces. Air shut-
ters are supplied on propane gas units and may require adjustment.
When the above conditions are normal and the main gas flow
is still off, the ignition controller is probably defective.
Before making any adjustments to the air shutters, allow the heater to operate for
about fifteen minutes with the air shutters open. The slotted screw on the end
manifold bracket moves the air shutters and adjusts all burners simultaneously.
Turning the screw clockwise opens the shutters; counterclockwise closes the
shutters. After the furnace has been in operation for 15 minutes, close the air
shutters observing the flame for yellow-tipping. Open the shutters until the yel-
low disappears. A limited amount of yellow-tipping is permissible for propane
gas. Other fuels should not display any yellow-tipping.
25. Burners and Carryover
System
These duct furnaces have individually formed steel burners
with accurately die-formed ports to give controlled flame
stability without lifting or flashback with either natural or
propane gas. The burners are lightweight and factory mounted
in an assembly which permits them to be removed as a unit
for inspection or service.
When making the adjustment, close the air shutters no more than is necessary to
eliminate the problem condition.
DANGER: Failure to install and/or adjust air shutters
according to directions could cause property damage,
personal injury, and or death.
All burners are equipped with two flash carryover systems
that receive a supply of gas simultaneously with the main
burner. During regular service, check the main burner ports,
the carryover assemblies, and the orifices for cleanliness.
27. Check Installation and Start-Up
Check the installation prior to start-up:
Start-Up
oCheck suspension. Unit must be secure and level.
oTurn electric and gas supply on to the furnace. Adjust the thermo-
stat or ductstat so that a call for heat exists. Observe for complete
sequencing of safety pilot and ignition.
oBe certain the electrical supply matches voltage rating of the fur-
nace. (Refer to the rating plate.)
Check installation after start-up:
oWith the unit in operation, measure manifold gas pressure. Mani-
fold pressure for natural gas should be 3.5" w.c. and 10" w.c. for
propane gas. See Paragraph 9.
oCheck all field wiring against the wiring diagram. Be sure wire
gauges are as required for the electrical load. Verify that fuses or
circuit breakers are in place and sized correctly.
oCheck clearances from combustibles. Requirements are shown in
oTurn the unit off and on, pausing two minutes between each cycle.
Paragraph 5.
Observe for smooth ignition. On two-stage or modulating burner
systems, manipulate temperature adjustment slowly up and down to
see if control is sequencing or modulating properly. Raising tem-
perature setting drives burner on or to full fire.
oIf installed in a confined space, verify that the furnace has adequate
combustion air supply. See Paragraph 5.
oCheck vent system to be sure that it is installed according to the
instructions in Paragraph 10. Be sure to have used an approved
vent terminal.
oObserve burner flame at full fire. Natural gas flame should be about
1-1/2" in height with blue coloring. Propane gas flame should be
approximately the same length with blue coloring. Yellow tipping
may appear on propane gas. If yellow extends beyond 1/2 to 3/4",
adjust air shutters. See Paragraph 26 .
oCheck piping for leaks and proper gas line pressure. Bleed gas
lines of trapped air. See Paragraph 9.
a) Turn manual shutoff valve to off position.
b) Turn gas supply on.
oChecked the limit control. With the heater on, completely block off
distribution air. The limit control should open within a few minutes,
shutting off the gas supply to the main burners.
c) Observe gas meter for movement, or
d) Attach pressure gauge readable to .1" w.c. and after turning gas on
for ten seconds, turn gas supply off. No change in pressure should
occur over a three-minute period.
oPlace "Owner's Envelope" containing Limited Warranty Card, this
e) If either c) or d) above indicate a leak, locate leak by brushing a
leak-detecting solution on all fittings. Bubbles will appear at a leak.
Repair and repeat tests.
booklet, and any optional information in an accessible location near
the heater. Follow the instructions on the envelope.
DANGER: The gas burner in this gas-fired equipment is designed and equipped to provide safe and
economically controlled complete combustion. However, if the installation does not permit the burner
to receive the proper supply of combustion air, complete combustion may not occur. The result is
incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe
operation of indirect-fired gas burning equipment requires a properly operating vent system which
vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING
WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY
OR DEATH.
Always comply with the combustion air requirements in the installation codes and in Paragraph 5.
Combustion air at the burner should be regulated only by manufacturer-provided equipment. NEVER
RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER.
Indoor units installed in a confined space must be supplied with air for combustion as required by
Code and in Paragraph 5 of this heater installation manual. MAINTAIN THE VENT SYSTEM IN
STRUCTURALLY SOUND AND PROPERLY OPERATING CONDITION.
RGM Form 421, Mfg No. 150492, Page 21
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE AND MAINTENANCE
WARNING: If you turn off the power supply,
turn off the gas. See Hazard Levels, page 2.
CAUTION: When cleaning, wearing eye
protection is recommended.
Maintenance Requirements -- Like all quality equipment, this unit
will operate with a minimum of maintenance. However, to ensure long
life and satisfactory performance, the following service schedule is rec-
ommended. When servicing, follow standard safety procedures and
those specific instructions and warnings in this manual.
Figure 22 --
Vertical Spark
Pilot
Furnaces should be inspected at the beginning of each heating season
and then once every four (4) months where the equipment is working
under normal conditions. If the furnace is located where an unusual
amount of dust or soot or other impurities are contained in the air,
more frequent inspection is recommended. Clean the heat exchanger
(inside and outside) annually.
When re-installing
the pilot, be sure to
include the pilot
hole cover plate.
Figure 23 - Pilot Location
Burner
28. Burner Rack Removal Instructions
1. Turn off the gas supply.
Rear
2. Turn off the electric supply.
Support
3. Remove bottom rear panel (located on the manifold side of the fur-
nace) by removing the two screws from each side.
4. Mark and disconnect electric valve leads.
6. Uncouple the union in the gas supply.
7. Remove two sheet metal screws in the bottom of the burner rack
assembly.
of burner
3/4"
(+ or - 1/32")
of pilot and
sensor
8. Pull "drawer-type" burner rack out of the furnace.
To disassemble the burner rack:
1. Remove flash carryover system (screws located at rear of burner
drawer).
2. Remove burner hold down clamp (located inside burner drawer un-
derneath the pilot).
3. Pull main burners horizontally away from injection opening and
lift out.
disassemble the ignition controller. There are no field replaceable com-
ponents in the control enclosure.
Follow the instructions in Paragraph 29 to clean. To re-assemble and
replace, reverse the above procedures being careful not to create any
unsafe conditions.
CAUTION: Due to high voltage on pilot spark
wire and pilot electrode, do not touch when
energized. See Hazard Levels, page 2.
Burners - Normally it is unnecessary to clean the main burners but
during the annual cleaning of the heat exchanger tubes it is wise to
inspect the burners for plugged ports. Main burners may be cleaned
using air pressure. Use an air nozzle to blow out scale and dust accu-
mulation from the burner ports. Alternately blow through the burner
ports and the venturi. Use a fine wire to dislodge any stubborn par-
ticles. Do not use anything that might change the port size.
29. Cleaning Pilot and Main Burners
Pilot - The pilot is located under the aeration panel on the control end
of the burner tray and is accessible only after the burner rack assembly
has been removed. In the event the pilot flame is short and/or yellow,
check the pilot orifice for blockage caused by lint or dust accumula-
tion. Remove the pilot orifice and clean with air pressure. DO NOT
REAM THE ORIFICE. Check and clean the aeration slot in the pilot
burner.
Clean the metal sensing probe and the pilot hood with an emery cloth
and wipe off the ceramic insulator. Check the spark gap; spark gap
should be maintained
Clean the burner rack flash carryover systems with air pressure.
Burner Orifices for Sea Level Operation
to .100". After the
Size
Qty Natural Gas
Propane Gas
pilot is cleaned, blow
any dirt away with
compressed air. The
combination valve
includes a pilot ad-
justment screw. To
adjust, remove cap
screw and adjust the
Drill Size P/N Drill Size P/N
75
4
4
5
5
6
7
8
9
45
41
41
38
38
38
38
39
39
39
39
38678 1.2 mm 63003
11792 1.45 mm 61652
11792 1.45 mm 61652
45870 1.55 mm 61653
45870 1.55 mm 61653
45870 1.55 mm 61653
45870 1.55 mm 61653
45871 1.55 mm 61653
100
125
140
170
200
225
250
300
350
400
Figure 21 - Pilot Burner Spark Gap
pilot flame to ap-
proximately 1-1/4".
Pilot System - No periodic maintenance of the ignition control box
is required. However, each season the lead wires should be checked for
insulation deterioration and good connections. Proper operation of the
electronic spark ignition system requires a minimum flame signal of
0.2 microamps as measured by a microampmeter. Do not attempt to
11
13
15
45871
45871
45871
53
53
53
9789
9879
9879
NOTE: Use only factory-authorized replacement parts.
Form 421, Page 22
Download from Www.Somanuals.com. All Manuals Search And Download.
All Sizes 75, 100 and 125 (do not have heat exchanger "V" baffles)
and Sizes 140-400 manufactured prior to 11/95 (do not have heat
exchanger "V" baffles) -- Remove the burner rack assembly. Use a
furnace brush (or a piece of heavy wire to which a piece of steel wool
is attached). Brush up and down within the tubes until all soot is re-
moved. With an air hose or brush, clean the outside space between the
lower portions of the heat exchanger tubes to remove any accumulated
dust or light deposits.
30. Cleaning the Heat Exchanger
CAUTION: When cleaning, wearing eye
protection is recommended.
Outer Surfaces (circulating air side) - To clean the outer sur-
faces of the heat exchanger, gain access by removing the inspection
panels in the ductwork or remove the ductwork. Depending on whether
or not the furnace is designed for high CFM (Model prefix "H"), there
may be directional baffles between the heat exchanger tubes. The stan-
dard furnace has baffles between the heat exchanger tubes as shown in
Figure 3B, page 5. (High CFM furnaces have only the top baffle sup-
port which does not need to be removed for cleaning.)
Sizes 140 - 400 manufactured beginning 11/95 (have heat exchanger
"V" baffles) -- Remove the burner rack assembly. Make sure that the
flue pipe is supported. Remove the three screws that attach the venter
housing to the outlet duct (pipe from furnace to venter). The venter
assembly will remain in place. Remove the six screws used to attach
the flue collection box to the top of the furnace. Remove the flue col-
lection box exposing the heat exchanger tubes. The V-shaped tube
baffles can now be removed.
To remove the baffles, remove the screws marked "A" in Figure 3B,
and slide each baffle forward. Use a brush and/or an air hose to remove
accumulated dust and grease deposits from the heat exchanger tubes
and the baffles. Re-install the baffles by sliding them into the rear slot
and replacing the screw. Secure ductwork as necessary.
All Sizes -- After cleaning is complete, reverse the procedure to re-
assemble the furnace. Use extreme care so that no unsafe conditions
are created. Check the furnace for proper operation.
Inner Surfaces (combustion gas side) - The inner surfaces of the
heat exchanger can be reached for cleaning with the burner rack re-
moved (See Paragraph 28.) An air hose; a long (18 to 24-inch), 1/2"
diameter stiff brush; a flashlight; and a mirror are needed. The required
procedure depends on the size of the furnace and the date of manufac-
ture. Follow these instructions to clean the inner surfaces of the heat
exchanger.
31. Venter
Motor - Remove dirt from the outer surface. The venter motor is per-
manently lubricated; no oiling is required.
Venter Relay - The venter relay controls the venter motor. If relay
contacts fail to "make", the venter motor will not run. If relay contacts
fail to "open, the venter motor will not shut off.
32. Troubleshooting
TROUBLE
PROBABLE CAUS E
REMEDY
No power to unit.
Turn on power, check supply fuses, or circuit breaker.
Turn up thermostat; check control transformer output. Check for loose wire connections.
Replace relay.
Replace motor or capacitor.
Open manual valve.
Venter
motor will
not start
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
a)
b)
c)
d)
e)
f)
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
a)
b)
c)
d)
e)
f)
No 24 volt power to venter relay.
Venter relay defective.
Defective motor or capacitor.
Manual valve not open.
Air in gas line.
Dirt in pilot orifice.
Gas pressure too high or too low.
Kinked pilot tubing.
Pilot valve does not open.
No spark:
Loose wire connections
Transformer failure.
Pilot will
not light
(venter
Bleed gas line.
Remove and clean with compressed air or solvent (do not ream).
Adjust supply pressure. (See Paragraph 9).
Replace tubing.
operating)
If 24 volt available at valve, replace valve.
Be certain all wires connections are solid.
Be certain 24 volts is available.
Maintain spark gap at .100".
Replace worn or grounded spark cable.
Replace pilot if ceramic spark electrode is cracked or grounded.
Make sure all panels are in place and tightly secured to prevent drafts at pilot.
Make certain ignition control is grounded to furnace chassis
If 24 volt is available to ignition controller and all other causes have been eliminated,
Incorrect spark gap.
Spark cable shorted to ground.
Spark electrode shorted to ground.
Drafts affecting pilot.
Ignition control not grounded.
Faulty ignition controller.
g)
h)
g)
h)
replace ignition control.
Optional lockout device interrupting Reset lockout by interrupting control at thermostat.
8.
9.
8.
Faulty combustion air proving
Manual valve not open.
Main valve not operating.
Defective valve.
Replace combustion air proving switch.
Open manual valve.
9.
1.
2.
a)
b)
Pilot lights, 1.
main valve 2.
will not open a)
b)
If 24 volt is measured at valve connections and valve remains closed, replace valve.
Check and tighten all wiring connections.
Loose wire connections.
(Troubleshooting is continued on page 24.)
RGM Form 421, Mfg No. 150492, Page 23
Download from Www.Somanuals.com. All Manuals Search And Download.
32. Troubleshooting (cont'd)
TROUBLE (cont'd) PROBABLE CAUSE (cont'd)
REMEDY (cont'd)
3.
Ignition control does not power main valve.
Pilot lights, main
3.
valve will not open
(cont'd)
Loose wire connections.
Flame sensor grounded. (Pilot lights - spark
Check and tighten all wiring connections.
Be certain flame sensor lead is not grounded or insulation or
a)
b)
a)
b)
continues)
ceramic is not cracked. Replace as required.
Set supply pressure at 5" w.c. to 14" w.c. for natural gas and
Gas pressure incorrect.
c)
c)
11" w.c. to 14" w.c. for propane gas.
Cracked ceramic at sensor.
Faulty ignition controller.
Replace sensor.
If all checks indicate no other cause, replace ignition
d)
e)
d)
e)
controller. Do not attempt to repair ignition controller; it has no
field replaceable components.
Dirty Filters
Incorrect manifold pressure or orifices.
Clean or replace filters.
Check manifold pressure (See Paragraph 9).
No heat (Heater
Operating)
1.
2.
1.
2.
Cycling on limit control.
Improper thermostat location or adjustment. See thermostat manufacturer's instructions.
4.
Belt slipping on blower.
Fan control improperly located or adjusted.
Defective fan control.
Blower set for too low temprrature rise.
Incorrect manifold pressure.
Circuit open.
Check air throughput (See Paragraph 15).
3.
4.
5.
3.
Adjust belt tension.
Relocate or adjust fan control (See Paragraph 19).
Replace fan control.
Slow down blower or increase static pressure..
Check manifold line pressure (See Paragraph 9).
Check wiring and connections.
Replace fan control.
Replace motor or capacitor.
Relocate or adjust fan control (See Paragraph 19).
Replace fan control.
Check motor load against motor rating plate. Replace motor
5.
1.
2.
3.
4.
1.
2.
3.
1.
2.
3.
Cold air delivered 1.
On Start-up 2.
During Operation 3.
4.
Motor will not run 1.
2.
Fan control inoperative.
Defective motor or capacitor.
Fan control improperly located or adjusted.
Defective fan control.
3.
Motor turns on and 1.
off while burner is 2.
Motor overload device cycling on and off.
operating (See
3.
if needed.
"Motor... " below)
3 phase motor rotating in opposite
Improper motor pulley and/or adjustment.
Interchange 2 legs on supply connections.
See instructions on air throughput.
4.
4.
1.
Blower motor cuts 1.
Improper static pressure in the duct system. Adjust duct system dampers.
2.
out on overload
2.
Low voltage.
Check power supply.
3.
3.
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:
FIRST:
Contact the installer.
Name
_______________________________________________________________________________________
Address ________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
Phone ________________________________________________________________________________________
SECOND:
THIRD:
Contact the nearest distributor (See telephone Yellow Pages.)
Contact:
REZNOR®, Thomas & Betts Corporation
150 McKinley Avenue
Mercer, PA 16137
Phone: (724) 662-4400
Model No. _______________________________________
Unit Serial No. ___________________________________
Date of Installation ________________________________
©2000 Thomas & Betts Corporation, All rights reserved.
Printed in the U.S.A.
MANUFACTURER OF GAS, OIL, ELECTRIC HEATING AND VENTILATING SYSTEMS
Trademark Note: Reznor® is registered in the United States and other countries.
3/00 YL Form 421-A.5
Form 421, Page 24
Download from Www.Somanuals.com. All Manuals Search And Download.
|