Tamron Satellite Radio MST2000 User Manual

OPERATION MANUAL  
MST2000 SERIES  
Loop Powered Multivariable SMARTFLOW® Transmitter  
For English and Metric Unit Versions  
SeeSection15forapprovalinformation  
Let us point you in the right direction.  
Eng lish Unit Soft ware Release H03  
Met ric Unit Soft ware Re lease HM3  
CSA Approvals  
MA37-2000-00, November 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
This manual is designed to optimize the performance of the MST2000 Series Loop Powered  
Multivariable SMARTFLOW® Transmitter. Theendusershouldreadandreviewitcarefullybeforein-  
stalling,usingormaintainingthetransmitter.Theinformationcontainedinthismanualcorresponds  
to the re vi sion level of the soft ware shipped with your MST2000. You can down load a copy of the lat-  
est ver sion of this man ual along with other in for ma tion from our web site.  
IMPORTANT: ThismanualcoversboththeENGLISHandMETRICUnitVersionsoftheMST2000oper-  
atingsoftware. TheENGLISHorMETRICconfigurationmustbeselectedatthetimeoforderand con-  
figured at the factory. ENGLISH or METRIC UNIT CONFIGURATION IS NOT FIELD SELECTABLE.  
It is the desire of Thermo Brandt Instruments that the MST2000 be setup and used as effec-  
tively and efficientlyaspossible. Ifyouhaveanyquestionsorconcernspleasecontactyour  
Thermo Brandt representative or Thermo Brandt Instruments at the following:  
Telephone:  
Facsimile:  
Web Address:  
E-mail:  
(919) 552-9011. Customer Service:Extension28  
(919) 552-9716  
TABLE OF CONTENTS  
Page  
Model Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
MST2100 Dimensional Drawing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
MST2400 Dimensional Drawing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Section 1, Mounting and Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Section 2, Continuous Purge Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Section 3, Integral “High Pressure” Blowdown System Option . . . . . . . . . . . . . . . . . . . 6  
Section 4, Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Section 5, LCD Display and IntegralKeyPad. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Section 6, MST2000 OperationalModesandStartup. . . . . . . . . . . . . . . . . . . . . . . . 8  
Section 7, Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Section 8, Program Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Section 9, Alarm ProgrammingInformation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Section 10, Formulas & Conversion Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Section 11, Test Jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Section 12, Optional Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Section 13, MST2000 HART®CommunicationsInformation . . . . . . . . . . . . . . . . . . . . 23  
Section 14, Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Section 15, CSA Hazardous Area Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
Section 16, CalibrationoftheMST2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
PRODUCT OVERVIEW  
Thermo Brandt Instruments’ MST2000 Se ries Loop Powered Multivariable SMARTFLOW® Trans-  
mitter providesthenecessaryversatilityrequiredtosatisfytoday’sdemandingindustrialprocess ap-  
plications. With programmable constants, input/output options and communication features the  
MST2000willconcurrentlymeasureand/orapplythenumerousprocessvariablesforatruemass flow  
measurement.  
TheMST2000’sconfigurationisuserfriendlyandisaccomplishedthroughtheintegralkeyp ad (no ex-  
ternalsoftwareorhardwareisrequired).TheMST2000iscapableofproducinganddisplayingsignals  
forDifferentialPressureorforFlow.Optionalinput,digitalI/Oandcommunicationmod ules can be in-  
stalled at the factory or in the field as required.  
Page 4  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
MODEL NUMBER  
SERIES: LOOP POWERED MULTIVARIABLE SMARTFLOWTM TRANSMITTER  
MST21 = MST2100, NEMA 1 Panel Mount En clo sure, Dif fer en tial Pres sure Con fig u ra tion & Non-isolated 4 Wire RTD In put Stan dard. u  
MST24 =MST2400, NEMA4X, FiberglassEnclosure, DifferentialPressureConfiguration&Non-isolated 4 Wire RTD In put Stan dard. u  
ISOLATEDINPUTMODULE: AbsolutePressureTransmitter  
0 = None  
1 = Iso lated In put Mod ule: Ac cepts 4-20mA in put sig nal from an Ex ter nal Ab so lute Pres sure Trans mit ter. u  
2 = Isolated Input Module with Integral Absolute Pressure Transmitter, 0-25 PSI (0-1.7 bar) range standard. Consult factory for  
other ranges. MST2400 only. Requires Integral 24V Power Supply. See Output option 2 below.  
ISOLATE  
D INPUT  
MODULE:TemperatureTransmitter  
0 = None  
CERTIFICATION  
0 = None  
2 = CSA Ap proved Di vi sion 2.  
1 = CSA Ap proved In trin sically Safe  
Review Sec tion 15 of this man ual for ap proval in for ma tion.  
COMMUNICATIONS  
MODULE  
0 = None  
H = HART® CommunicationsModule. u  
DIGITAL I/O  
MODULE  
0 = None  
D = Dig i tal I/O Mod ule with 1 In put, 1 Out puts.v  
PRESSURE RANGES  
1S =StandardRange1Max.Span:0-0.10(0to2.54mm)W.C. Turndownto0.010(0.254mm)W.C.(10:1).  
2S=StandardRange2Max. Span:0-0.25(0-6.35mm)W.C. Turndownto0.025(0.635mm)W.C. (10:1).  
3S = Stan dard Range 3 Max. Span: 0-1.00“ (0-25.4mm) W.C. Turn down to 0.10“ (2.54mm) W.C. (10:1).  
4S=StandardRange4Max. Span:0-4.00(0-101.6mm)W.C. Turndownto0.40(10.16mm) W.C. (10:1).  
5S =StandardRange5Max. Span:0-16.0(0-406.4mm)W.C. Turndownto1.60(40.64mm)W.C. (10:1).  
6S=StandardRange6Max. Span:0-50.0(0-1270.0mm)W.C. Turndownto5.00127.0mm)W.C. (10:1).  
CR = Com pound RangeConsultfactory. SupplydesiredCompoundRange.  
All max i mum pres sure ranges have a turn down of 10:1.  
Spec ify Pres sure Range # in model num ber (ex am ple 1S or CR).  
StandardRanges: MST2000willbecalibratedatMaximumSpan.IfanInitialRangeSettingisdesired,supply with  
or der and unit will be shipped with this Ini tial Range pre set. (Ex am ple: 3S set to 0 to 0.5” W.C.).  
CompoundRanges:MST2000willbecalibratedatdesiredCompoundRange. Supplycompoundrangewithorder  
(ex am ple: -0.25 to +0.25” W.C.).  
All spans will be cal i brated in Inches of W.C. Other Units of mea sure will be con verted to Inches of W. C.  
OUTPUT & VERSION. See Note Be low.  
1 = 4-20mA Out put. Eng lish Units Ver sion. u  
2 = 4-20mA Out put with In te gral 120VAC to 24VDC Power Sup ply. 120VAC  
Source Re quired. MST2400 only. Eng lish Units Ver sion.  
3 = 4-20mA Out put. Met ric Units Ver sion. u  
4 = 4-20mA out put with In te gral 120VAC to 24VDC Power Sup ply. 120VAC Source  
Re quired. MST2400 only. Met ric Units Ver sion.  
OPTIONS  
0 = None  
B = In te gral High Pres sure Blowdown Sys tem. MST2400 Only. Re quires  
Dig i tal I/O Mod ule. 120VAC source re quired. Reg u lated air sup plied to  
100 PSIG. En clo sure size will change. Con sult Fac tory for spec i fi ca tions  
andavailability.  
P = Con tin u ous Purge to Flowmeter. MST2400 Only. Spans of 0.25” W.C.  
(6.35mmWC) or greater. A fil tered air sup ply source of 20 to 100 PSI  
(1.4 to 6.9 bar) is re quired. u  
ACCESSORIES  
0 = None  
P = Pipe Mount. MST2400 Only.  
uDenotesoptions&featuresavailablewithCSAIntrinsicallySafe  
andDivision2hazardousareaapprovals.  
v
De notes op tions & fea tures avail able with CSA Di vi sion 2 Ap-  
provals Only.  
Review Section15, forCSAapprovalinformation.  
MST24  
1
1
1
H
D
2S  
1
0
P
MST2000’s with Eng lish or Met ric Unit Ver sions are avail able but must be se lected at time of orderandconfiguredat  
the fac tory. IT IS NOT A FIELD SELECTABLE OPTION.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
SPECIFICATIONS  
FUNCTIONAL SPECIFICATIONS  
Service:  
Clean, dry, non-corrosive Air or Gas. Other me dia may be pos si ble with the use of the Con-  
tinuousPurgeoption.Consultfactory.  
PressureRanges:  
StandardPressureRanges:  
Range 1: 0 to 0.10” (0 TO 2.54mm) W.C.  
Range 4: 0 to 4.0” (0 to 101.6mm) W.C.  
Range 2: 0 to 0.25” (0 to 6.35mm) W.C.  
Range 3: 0 to 1.0” (0 to 25.4mm) W.C.  
Range 5: 0 to 16.0” (0 to 406.4mm) W.C.  
Range 6: 0 to 50.0” (0 to 1270.0mm) W.C.  
OutputSignals:  
Analog:4-20 mA sig nal (Max. Loop re sis tance = 615 Ohms @ 24 VDC) is user pro gram ma-  
bletoDifferentialPressureorFlowParameters. Externalinputsorprogrammedconstants  
fortemperatureandabsolutepressurealongwithconstantsforEffectiveAreaandStandard  
Den sity, are nec es sary for a true flow mea sure ment.  
OptionalDigital:One(1)optionaldigital(opencollector)outputavailable.Activationpro-  
gram ma ble by end user.  
Communications:  
Optional:digitalHART® Communicationsmodule. SeeSection13, page23forHART® com-  
municationinformation.  
Alarms:  
Display:  
Programmablehard ware alarms, underrange and overrange.  
High Con trast, 2 line, al pha nu meric LCD with -20 to 150o F (-28 to 66oC)operatingtemper-  
ature.  
PowerSupplyRequired:  
24 to 40 VDC loop power, min i mum 11 volts re quired at in puts.  
ReversePolarityProtection: Yes  
Turn On Time:  
4seconds(maximum).  
Operating:-40 to 150oF (-40 to 66oC)  
TemperatureLimits:  
Overpressure Limits:  
Storage:-40 to 180o F (-40 to 82oC)  
ProofPressure: 10 PSID (0.7 Bar)  
Burst Pres sure: 50 PSID (3.45 Bar)  
Max Line Pres sure: 50 PSIG (3.45 Bar).  
Damping:  
Stan dard Time Con stant: 500 mSec. Additionaldampingadjustableviaintegralkeypad  
from 0.5 to 5 Sec onds in 0.5 sec ond in cre ments.  
HumidityLimits:  
Inputs:  
100% Non-condensing, (MST2400 Only).  
Standard: Non-isolated, 4 wire RTD in put con nec tion.  
Optional4-20mAIsolatedInputs: In put ranges are soft ware rangeable.  
& ExternalTemperature:4-20mAInput  
& ExternalAbsolutePressure: 4-20 mA In put  
OptionalDigitalInput:Oneoptionaldigital(TTL level) in put is avail able.  
PERFORMANCE SPECIFICATIONS  
Accuracy:  
For spans from 40% to 100% of max i mum range with TD of 1:1 to 2.5:1 then ac cu racy =  
0.15% of Re-ranged Span.  
For spans from 20% to 39% of max i mum range with TD of 2.5:1 to 5:1 then accuracy=  
(0.15 + 0.005 X TD)% of Re-ranged Span.  
For spans from 10% to 19% of max i mum range with TD of 5:1 to 10:1 then accuracy=  
(0.15 + 0.010 X TD)% of Re-ranged Span.  
& TD = Max i mum Range / Re-ranged Span  
Stability:  
0.1% of Max i mum Range / 12 Months  
AmbientTemperature:  
Zero: No Ef fect Span: Less than 0.001% of Re-ranged Span per Deg F. Cor rected by in-  
ternaltemperaturesensor.  
MountingPositionEffect:  
VibrationEffect:  
MinoreffectonZero. Correctedbysetupparameters.  
Less than 0.2% of Max i mum Range / g, 10-130 Hz.  
PHYSICAL SPECIFICATIONS:  
EnclosureTypes:  
MST2100: NEMA1,AnodizedAluminum.  
MST2100: 1/8” NPTF  
MST2400: NEMA 4X, Fi ber glass.  
ProcessConnections:  
Electrical Connections:  
MST2400: 1/4” NPTF Stain less Steel  
MST2100 & MST2400: Cage Clamp style ter mi nal block. 12-24 AWG wire size.  
MST2400: ½Liquid-Tightflexibleconduitconnections.  
Weight:  
MST2100: 2.5 . (1.14 kg)  
MST2400: 8.0 lbs. (3.63 kg)  
Page 6  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
DIMENSIONS  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOUNTING AND PROCESS CONNECTIONS  
OPERATION MANUAL  
1. MOUNTING AND PROCESS CONNECTIONS  
The MST2000 can be mounted in any direction. There may be a minor effect on Zero  
that can be corrected by the setup parameters.  
1.1 MST2100: NEMA 1 Enclosure  
A. Review the dimensional drawing on page 5.  
B. Pro cess con nec tions are via 1/8" NPT fe male ports lo cated on the bot tom of the hous ing. The high  
pressure port is la beled “HIGH”, the Low pres sure port is la beled “LOW” on the mount ing plate.  
1.2 MST2400: NEMA 4X Enclosure  
A. Review the dimensional drawing on page 5.  
B. With out a con tin u ous purge op tion, pro cess air should be non-corrosive and dry. If a con tinuous  
purge option is installed please review section 2 on the continuous purge. The continuous purge  
must be balanced.  
C. Pro cess con nec tions are via 1/4" NPT fe male ports lo cated on the bot tom of the en clo sure. The high  
pressure port is la beled “HIGH”, the Low pres sure port is la beled “LOW”.  
1.3 Three Valve Manifold  
A. It is recommended that a three valve manifoldbeinstalledintheprocess, unless a continuous  
purge is installed . A three valve manifold is available from the factory. It is installed in the process  
lines to isolate the processsignalduringinstallationand/orremovaloftheMST2000thus preventing  
possible trans ducer over-pressurization and to zero trans mit ter.  
þNotes:  
þNote: MST2000 DP sen-  
sormaximumoperating  
static pres sure is 25  
PSID.  
& Be fore con nec tions are made blow out pro cess lines throughly.  
& It is rec om mended that pipe thread tapes not be used on pneu matic pip ing.  
& Soap test all joints and fit tings for leaks.  
& Pro cess lines should be the same di am e ter and ap prox i mately the same length.  
2. CONTINUOUS PURGE OPTION  
TheMST2400canbeorderedwithaContinuous  
PurgeOption.Thisoptionsuppliesacontinuous  
pneumatic purge to a Thermo Brandt pitot flow  
sen sor to keep the sens ing ports free from plug-  
gingduringoperation.TherearePurgeBalance  
adjustments located on the front panel which  
provideforthezeroingofprocessairresistance.  
If the Continuous Purge Option has been or-  
dered, please read the following setup instruc-  
tions. TheContinuousPurgeOptionmustbe  
balanced once the process is connected to  
the MST2400.  
A 1/4" NPT fe male air sup ply port is pro vided on  
the bot tom of the en clo sure for the Purge.  
An internalfilter is sup plied with the unit, but air  
supply should also be filtered and regulated.  
þPROCESS LINE LENGTH & SIZE  
& When a con tin u ous purge op tion is used, the pro cess  
lines (Hi and Low lines) must be the same di am e ter  
(pref er a bly 3/8" or larger) and the length of each line  
should be the same within +/- 5%.  
þIMPORTANT:  
& The Con tin u ous purge op tion air sup ply should be only clean, in stru ment qual ity air and should be greater than 20  
psi (1.4 bar) and not ex ceed 100 psi (6.9 bar). A pre-filter should be in stalled in the sup ply line if the air qual ity is  
sus pect. A 5 mi cron fil ter and a 0.3 mi cron co ales cent fil ter are rec om mended. Fail ure toprovideclean,instrument  
qual ity air through the Con tin u ous Purge can cause the MST2000 to give er ratic read ings. Failuresattributedtoa  
contaminatedairsupplyarenotcoveredunderthewarranty.  
Page 8  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
Integral “High Pressure” Blowdown System  
2.1 Bal ancing the Purge if the Pro cess is in Op er a tion  
A. Review the draw ing on page 5.  
B. Pro cess must be in a steady state.  
C. Dis con nect the HIGH and LOW lines from the trans mit ter. Mea sure the DP from the pro cess witha  
pressure calibrator or other DP measuringdevice..  
D. Record the DP reading. ______________________________  
E. Reconnect the HIGH and LOW lines back to the transmitter. Make sure the Purge is operating.  
F. Ad just the “HIGH” and “LOW” Purge Bal ance ad just ments on the mount ing plate un til the dis play  
reading equals the read ing re corded in Step D. See the draw ing on page 5.  
2.2 Bal ancing the Purge if the Pro cess is not in Op er a tion  
A. Review the draw ing on page 5.  
B. Ensure that there is no flow in the process. If the flow can not be stopped completely follow the in-  
structionsinSection2.1.  
C. At tach the HIGH and LOW lines to flow me ter.  
D. Ad just the “HIGH” and “LOW” Purge Bal ance ad just ments on the front panel till the dis play reading  
equals 0.0000 Inch W.C. See drawing on page 5.  
þIMPORTANT: It is rec om mended that a Three Valve Man i fold not be used with an MST2400 which con-  
tains the ContinuousPurgeOption.Consultfactory.  
2.3 Integral 5 MicronCoalescentFilter  
A. The MST2400 with continuous purge comes with an integral 5 micronCoalescentFilter.See the  
Drawing on page 5.  
B. The filter is intended as a secondary device. The supplyairshouldberegulatedandfiltered before  
enteringtheenclosure.  
C. The integral filter will turn “RED” as it cleans the air. Replace the filterbeforetheRED” reaches the  
right side, or outlet end.  
3. Integral “High Pressure” Blowdown System  
The MST2400 can be ordered with an Integral “High Pressure” Blowdown System. This op tion is de-  
signedtocleanoutPitotAveragingFlowsensorsusingablastofHighPressureAir(upto 100 PSIG or  
6.9 bar) while holding the last out put sig nal from the MST2400.  
TheMST2400iscapableofbeingprogrammedtoperformablowdownsequenceanywherefromeve ry  
2minutesuptoonceevery24hours(1440minutes). Theblowdownsequencecanalsobeactivated by  
a re mote pulse from a DCS or other controller.  
A. Specifications:  
a. Air Sup ply: Max i mum of 100 PSIG (6.9 bar) . If air sup ply is over 100 PSIG then a reg u la tor must be  
installed.  
b. Voltage: 120 VAC. Optioncontainsintegral24VDCpowersupply.  
c. Se quence Du ra tion: Approximately 30 sec onds from time sig nal is held till sig nal is re stored.  
d. Temperature: Maximum150oF.  
e. Programmable intervals: 2 min utes to 1440 min utes (24 hours).  
f. PulseSignalfromexternalcontroller:Contactclosurefor½second(500milliseconds).  
B. Sequence of Operation  
a. The MST2400 be gins the Blowdown se quence by hold ing the last out put sig nal. “-HOLD-” will ap-  
pear on the LCD. The Blowdown Status In di ca tor will also be lit. See the sec tion on the LCD Display.  
b. Valves are ac ti vated to iso late and vent the trans mit ter from the pro cess to pre vent dam a ge.  
c. The Hi & Low pro cess lines are al ter nately blown down for ap prox i mately 11 sec onds each.  
d. ValvesareautomaticallyactivatedtorestoresignalfromprocessbacktoMST2400.  
C. External Activation Signal  
TheMST2400IntegralBlowdowncanbeactivatedbysecondexternalcontactclosurepulsesig-  
nal.TheBlowdowncanbecontrolledbythissignalonlyorincombinationwiththeintegralcontrolofthe  
MST2400. TheMST2000mustbeprogrammedtoacceptthissignal. RefertoProgrammingParame-  
ters, Sec tion 8. See Wiring Di a grams in Sec tion 14.  
þNote: A 110VAC power source is re quired for the In te gral Blowdown Sys tem. An internal 24VDC  
power sup ply is fur nished with the Blowdown. DO NOT USE THIS POWER SUPPLY TO POWER THE  
LOOP SIGNAL.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL CONNECTIONS  
OPERATION MANUAL  
4. ELECTRICAL CONNECTIONS  
4.1 MST2100: NEMA 1 Enclosure  
A. Review the MST2100 and MST2400 dimensional  
drawings.  
B. Refer to the MST2000 TerminalBlockDrawing.  
C. MST2000InstrumentElectricalConnectionsare  
cage clamp style for 12-24 AWG. Wire should be  
stripped back a min i mum of 3/16" inches (5mm).  
D. The MST2000 Multivariable differential pressure  
transmitter is a HART® compatible loop-powered  
4-20 milliamp transmitter.Powerconnectionis  
made at the two left terminalpositions marked  
LOOP+ and LOOP-. Nominalpowersupplyvoltage  
is 24 volts DC which allows up to 600 ohms series  
resistance in the loop circuit.  
þForHART®applications,minimumloopresistanceis  
250 ohms.  
4.2 MST2400: NEMA 4X Enclosure  
A. A ½" Liquid Titeconduitconnectionislocatedon  
thebottomoftheEnclosure.  
B. Conduitshouldbeinstalledtopreventcondensation  
fromcollectingintheinstrument.  
4.3 IntegralPowerSupplyOption.  
A. The Integral Power SupplyOptionrequiresanexternal120VoltPowerSupply.  
B. A six (6) positionscrewtypeterminalblockand½"Liquid Tite Conduit connection are suppliedwith  
theIntegralPowerSupplyOption.  
4.4 CanadianStandardsAssociationHazardousAreaApprovals  
TheMST2100andMST2400havebeenapprovedbyCSAforhazardousareainstallations.  
See Sec tion 15 for de tails or con tact the fac tory.  
5. LCD DISPLAY and INTEGRAL KEY PAD  
AllcontrolsandindicatorsareLocatedonthefrontpaneloftheMST2000. RefertotheLCD& Key Pad  
Drawing.  
5.1 Key Pad  
All programming and control operations are per-  
formed using four (4) pushbuttons on the key pad.  
Following are summaries of each key.  
MODE: ! Toggles the MST2000 between  
RUN Mode and PROGRAM  
Mode.  
! Also used to change the edit cur-  
sor when entering a numeric  
value.  
EDIT: ! Selectstheparametertoedit  
when in Programming Mode.  
! Also saves the edited parameter  
data to memory.  
INCREMENT: ! Increments (steps forward) through parameters and/or numeric values.  
DECREMENT: ! Decrements(stepsbackwards)throughparametersand/ornumericvalues.  
RESET: ! Resets the CPU. Re starts pro gram and loads in pro grammed vari ables stored in  
the E-Prom  
Page 10  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
MST2000 OPERATIONAL MODES and START UP  
5.2 LCD Display  
The MST2000 High Contrast LCD display will  
displaytwo(2)linessimultaneously.Thedisplay  
is used to setup and calibratetheMST2000and  
displayandmonitorinputandoutputsignalsand  
other variables.  
The lines of displayare:  
Num eric: ! Where the val ues for DP or  
Flow are displayed.  
! Thevariablesforparameters  
are edited and displayed.  
Alphanum eric: ! Where units of measure and  
parameter names are dis-  
played.  
S t a t u s ! Used to display the operationalstatus of the MST2000. The Statusindicator will  
Indicators:  
indicate when the MST2000 is in “RUN Mode”, if there is an Alarm and whether  
an AutoZero or Blowdown sequenceisinprocess.  
6. MST2000 OPERATIONAL MODES and START UP  
The MST2000 has two basic operational Modes. They are:  
RUN MODE ! In this mode the MST2000 is operating and displaying the measurements.  
PROGRAM ! In this mode the MST2000 is ready for programming. Note: The PROGRAM Mode  
MODE  
can be password protected.  
Startup  
Whenpowerisfirstapplied,theMST2000LiquidCrystalDisplay(LCD)willfirstdisplayRESETfollowed  
by READEE and then display the selected runtime parameter. The available runtime parameters are  
listed below.  
ENGLISH UNITS VERSION  
METRIC UNITS VERSION  
DP in Inches of Wa ter Col umn  
DP inmillimetersofWaterColumn  
Gas Flow in Nor mal Cu bic Me ters per Hour  
Gas Flow in Cu bic Me ters per Hour  
Mass Flow in Ki lo grams per Hour  
ProcessTemperatureinDegreesCelsius  
ProcessAbsolutePressureinBar  
MST2000 Alarm Sta tus  
INWC  
SCFM  
MMWC  
NM3-HR  
M3-HR  
Gas Flow in Stan dard Cu bic Feet per Min ute  
Gas Flow in Ac tual Cu bic Feet per Min ute  
Mass Flow in Pounds per Hour  
ACFM  
LBHR  
KG-HR  
ProcessTemperatureinDegreesFahrenheit  
Process Ab so lute Pres sure in PSI  
MST2000 Alarm Sta tus  
TEMP  
TEMP  
ABS_PR  
ALARMS  
ABS_PR  
ALARMS  
The default display mode is initially set at the factory for inches of wa ter col umn (INWC) or mil li-  
metersofwatercolumn(MMWC). The user may select other runtime flow variablesbypressing  
the INC (increment) or the DEC (decrement)keys.Note: English or Metric Unit Configura-  
tions are not field selectable. They must be set at the factory.  
The MODE key is used to togglebetween RUN mode and PROGRAM mode.  
The EDIT key is used to clear ‘latched’ alarms in runtime (RUN) mode.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROGRAMMING  
OPERATION MANUAL  
7. PROGRAMMING  
The MST2000 PROGRAM mode is accessed by pressing the MODE key. When the MODE key is  
pressed one of the followingwilloccur.  
þNOTE:  
& TheMST2000canbePasswordprotectedtopreventunauthorizedaccesstoprogrammingparameters.The  
MST2000 is shipped from the fac tory with the Pass word dis abled.  
7.1 If the PasswordParameterisEnabled(elsegotoSection7.2)  
A. The MST2000 will then display ENT_PW prompting the user to enter the requiredpassword.  
þNOTE:  
& The user must press the EDIT key within 4 sec onds to be gin en ter ing the cur rent pass word or the MST2000 will re-  
turn to RUN mode. The pass word is a unique num ber be tween 1 and 9999 and is en tered as de scribed in Sec tion  
7.5.  
& Dur ing pass word en try, if no keys are pressed for more than 4 sec onds, the MST2000 will re turn to RUN mode.  
7.2 If the PasswordParameterisDisabledorafterthePasswordissuccessfullyentered.  
After the passwordhasbeenproperlyentered, Brandt and verXXX willbemomentarilydisplayed  
and then followedbythefirstavailablePROGRAMparameter.  
þNOTE: verXXX indicates the installed software revisionlevel.  
7.3 SelecttheParametertoEdit  
A. Once the ParametersaredisplayedusetheINC and DEC keys to scroll up and down through the  
available parameters.Seeparameters,Section8.0.  
B. To edit a selected parameter, press the EDIT key and the editingmenuswillbecomeactive.  
C. Parameters are eitheranumericvalue(example:EffectiveArea)orcontrolahardware/operating  
mode.  
7.4 Editing of a Hardware/Operating Mode Parameter.  
A. Ifaparametercontrolsahardwareoroperatingmodefeature,usethe INC and DEC keys to scroll  
throughtheavailablesettings.  
B. Af ter the de sired set ting is se lected, press theEDIT key again to save the selected set ting to mem-  
ory.  
C. The LCD will display SAVED for approximately 1 sec ond and then redisplay the new set ting.  
7.5 Editing a Numeric Value Parameter.  
A. If the selected pa ram e ter to edit is a nu meric value,  
the ed it ing menus will dis play the cur rent value and  
thecurrentcursorpositionforthedecimalposition.  
B. Use the INC and DEC keys to incrementordecre-  
ment the numeric value at the current cursor posi-  
tion.  
C. To change the cursor position press the MODE  
key. The LCD will display ‘x 1’ if the ones column is  
to be changed, ‘x 10’ for the tens column, ‘x D1’ for  
the tenths col umn, ‘x D01’ for the hun dredths col-  
umn, etc. The number will not incrementordecre-  
ment if the pa ram e ter limit is reached. See the  
Chart Below and the examples to the right.  
Page 12  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
PROGRAM PARAMETERS  
LEFT OF  
DECIMAL  
RIGHT OF  
DECIMAL  
1000000. 100000. 10000. 1000. 100. 10.  
1.  
X
.1  
X
.01  
X
.001  
.0001  
X1  
X D1  
X D01  
X10  
X
X100  
X1K  
X
X D001  
X D0001  
X
X
X
X10K  
X100K  
X1M  
X
X
X
D. Af ter the num ber is changed to the de sired value, press theEDIT key again to save the new value to  
memory.  
E. The LCD will display saved for approximately1secondandthenredisplaythenewsetting.  
8. PROGRAM PARAMETERS  
TheAvailablePROGRAMparametersareshownbelowalongwithadescriptionofhoweachparame-  
ter is applied. They are listed in the order they ap pear in the PROGRAM menus.  
Parameter  
Description  
FactoryDefault  
LCDCON  
LCD Con trastad just ment. Avail able range is from 0 to 10. Use lower  
settingsforbestcontrastincolderenvironmentsandhighersettingsfor  
bestcontrastinhotterenvironments.  
5
420OUT  
4-20 milliamp Out putassignment. Availableassignmentsare:  
0 = INWC or MMWC  
English Units Version: 0 = INWC (pri mary vari able), 1 = SCFM,  
2 = ACFM, 3 = LBHR.  
MetricUnitsVersion: 0 = MMWC (pri mary vari able), 1 = NM3-HR,  
2 = M3-HR, 3 = KG-HR  
420_ZE  
420_SP  
4 Milliamp Zero setting. The 4 milliamp zero setting adjusts the Set equal to the low  
range of the natural  
span.  
milliamp lower range of the primary variable (INWC or MMWC). The  
availablerangeisthenaturalspanofthedifferentialpressuresensor.  
20 Milliamp Span setting. The 20 milliamp span setting adjusts the Set equal to the  
upper range of the  
natural span.  
milliamp span value of the primary variable (INWC or MMWC). The  
availablerangeisthenaturalspanofthedifferentialpressuresensor.  
þNOTE: The 420_SP value (span) must al ways be greater than the 420_ZE  
value (zero) for proper op er a tion.  
F_SPAN  
Flow Span setting. The flow span setting controls the upper 4-20 20000  
milliamp value assignment (turn down) when the 4-20 output is as-  
signed to the runtime cal cu lated flow vari ables (SCFM, ACFM, LBHR  
or NM3-HR, M3-HR, KG-HR). The lower 4-20 milliamp value assign-  
ment is al ways ref er enced to zero (0). The avail able range is:  
English Unit Version: 0 to 10,000,000 (no units).  
Metric Unit Version: 0 to 50,000,000 (no units).  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROGRAM PARAMETERS  
OPERATION MANUAL  
Parameter  
Description  
FactoryDefault  
E_AREA  
Effective Area of flow meter device. The effective area is required for 1.0000 for English.  
0.0929 for Metric.  
flowcalculationsandisenteredtobethesameasshownontheThermo  
Brandt flow me ter la bel. The avail able range is:  
EnglishUnitVersion: 0.0000 to 500.0000 square feet.  
Metric Unit Version: 0.0000 to 100.0000 square meters.  
þNOTE: Some flow me ter de vices use ‘K fac tors’ in stead of ef fec tive ar eas to  
definemassflowrelationships.Effectiveareascanbecalculatedfromgiven  
K fac tors. See For mulas, Sec tion 10.  
þNOTE: Thermo Brandt flow meter de vices are spec i fied in square feet. To  
con vert to square me ters, mul ti ply the square feet value by 0.0929.  
STDDEN  
Standard Density. The standard density is required for mass flow 0.07517 for English.  
1.20367 for Metric.  
calculations and is entered for the specific gas being measured. The  
standard density is entered at the standard reference temperature of 68  
degrees F or 20 de grees C. The avail able range is:  
EnglishUnitVersion: 0.0000 to 2.0000 pounds per cubicfoot.  
Metric Unit Version: 0.0000 to 40.0000 Kilograms per cubicmeter.  
TMPSRC  
TMPCON  
Temperature source.Available assignments are 0 = CONstant,  
1 = EXTernal and 2 = RTD.  
0 = CONstant  
Temperature Constant. The temperature constant can be used for 68.0000 for English.  
20.0000 for Metric  
mass flow calculations when no external temperature inputs are  
available and is entered as the average gas temperature. The available  
range is:  
EnglishUnitVersion: -50.0000 to 900.0000 degreesF.  
Metric Unit Version:-50.0000 to 900.0000 degrees C.  
RTDCAL  
RTD Calibration offset. The RTD calibration offset constant allows the 0.0000  
user to offset the actual measured value from the direct RTD input. The  
value may be positive or negative and is entered in degrees F. The  
available range is :  
EnglishUnitVersion: -10.0000 to 10.0000 degrees F.  
Metric Unit Version:-10.0000 to 10.0000 degrees C.  
EX_TPZ  
TPZCAL  
External Temperature Zero. The External Temperature Zero is the 0.0000  
lower range (4 milliamp zero) setting for the external 4-20 milliamp  
‘temperature’ input channel. The available range is:  
EnglishUnitVersion: -50.0000 to 100.0000 degreesF.  
Metric Unit Version:-50.0000 to 100.0000 degrees C.  
Temperature Zero Calibration. The Temperature Zero Calibration 4175  
value is the 4 milliamp (zero) count value from the external 4-20 milliamp  
‘temperature’ input channel. This parameter is used to calibrate the zero  
point of the incoming 4-20 signal from the external 4-20 temperature  
device. To calibrate the zero point of the incoming 4-20 signal, press the  
EDIT key. The screen will display IN4MA. Set the incoming signal for 4  
milliamps (or connect an external 4-20 calibrator set for 4 milliamps) and  
press the EDIT key. The MST2000 will measure the external temperature  
input channel and save the new 4 milliamp reference to memory.  
If an external  
temperature option  
is pre-installed and  
calibrated at the  
factory this will be  
custom set for that  
unit.  
Page 14  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
PROGRAM PARAMETERS  
Parameter  
Description  
FactoryDefault  
EX_TPS  
External Temperature Span. The External Temperature Span is the 200.0000  
upper range setting for the external 4-20 milliamp ‘temperature’ input  
channel. The avail able range is:  
English Unit Version: 0.000 to 990.0000 degrees F.  
Metric Unit Version:0.000 to 990.0000 de grees C.  
TPSCAL  
Temperature Span Calibration. The Temperature Span Calibration 21000  
Value is the 20 milliamp (span) count value from the external 4-20  
milliamp ‘temperature’ input channel. This parameter is used to  
calibrate the span point of the incoming 4-20 signal from the external  
temperature device. To calibrate the span of the incoming 4-20 signal,  
press the EDIT key. The screen will display IN20MA. Set the incoming  
signal for 20 milliamps (or connect an external 4-20 calibrator set for 20  
milliamps) and press the EDIT key. The MST2000 will measure the  
external temperature input channel and save the new 20 milliamp  
reference to memory.  
If an external  
temperatureoption  
is pre-installed and  
calibrated at the  
factory this will be  
custom set for that  
unit.  
APRSRC  
APRCON  
AbsolutePressureSource.Available assignments are 0 =CONstant 0 = CONstant  
and 1 = EXTernal.  
þNote: MST2000 DP sen sor max i mum op er at ing static pres sure is 25 PSID.  
Absolute Pressure Constant. The absolute pressure constant can 14.6960 for English.  
1.01325 for Metric.  
be used for mass flow calculations when no external absolute pressure  
input is available and is entered as the average absolute pressure  
inside the duct. The avail able range is:  
English Unit Version: 0.000 to 100.0000 PSIA.  
Metric Unit Version:0.000 to 100.0000 Bar.  
EX_APZ  
APZCAL  
External Absolute Pressure Zero. The External Absolute Pressure 0.000  
Zero is the lower range (4 milliamp zero) setting for the external 4-20  
milliamp ‘absolute pressure’ input channel. The avail able range is:  
English Unit Version: 0.000 to 100.0000 PSIA.  
þNote: MST2000 DP sensormaximum  
operating staticpressureis25PSID.  
Metric Unit Version:0.000 to 100.0000 Bar.  
Absolute Pressure Zero Calibration The Absolute Pressure Zero 4175  
Calibration value is the 4 milliamp (zero) count value from the external  
4-20 milliamp ‘absolute pressure’ input channel. This parameter is  
used to calibrate the zero point of the incoming 4-20 signal from the  
external 4-20 absolute pressure device. To calibrate the zero point of  
the incoming 4-20 signal, press the EDIT key. The screen will display  
IN4MA. Set the incoming signal for 4 milliamps (or connect an external  
4-20 calibrator set for 4 milliamps) and press the EDIT key. The  
MST2000 will measure the external absolute pressure channel and  
save the new 4 milliamp reference to memory.  
If an external  
absolute pressure  
option is  
pre-installed and  
calibrated at the  
factory this will be  
custom set for that  
unit.  
EX_APS  
External Absolute Pressure Span. The External Absolute Pressure 25.0000 for English.  
1.7237 for Metric  
Span is the upper range setting for the external 4-20 milliamp ‘absolute  
pressure’ input channel. The available range is:  
English Unit Version: 0.000 to 100.0000 PSIA.  
þNote: MST2000 DP sensormaximum  
Metric Unit Version:0.000 to 100.0000 Bar.  
operating staticpressureis25PSID.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROGRAM PARAMETERS  
OPERATION MANUAL  
Parameter  
Description  
FactoryDefault  
APSCAL  
Absolute Pressure Span Calibration. The Absolute Pressure Span 21000  
Calibration value is the 20 milliamp (span) count value from the external  
4-20 milliamp ‘absolute pressure’ input channel. This parameter is used  
to calibrate the span point of the incoming 4-20 signal from the external  
absolute pressure device. To calibrate the span point of the incoming  
4-20 signal, press the EDIT key. The screen will display IN20MA. Set the  
incoming signal for 20 milliamps (or connect an external 4-20 calibrator  
set for 20 milliamps) and press the EDIT key. The MST2000 will measure  
the external absolute pressure channel and save the new 20 milliamp  
reference to memory.  
If an external  
absolute pressure  
option is  
pre-installed and  
calibrated at the  
factory this will be  
custom set for that  
unit.  
INPUTO  
INPUTG  
OUTPTO  
Input Offset. The Input Offset parameter allows the user to adjust This is a factory  
default setting  
(calibrate) the actual pressure (zero) value to the MST2000 displayed  
value. The input offset parameter is displayed and stored in memory as  
counts. After the EDIT key is pressed, the edit menu displays the real  
time pressure input. The user then uses the INC and DEC keys to adjust  
the desired offset. The pressure input must be connected to a pressure  
source and be at minimum range value (zero reference) during this  
determined during  
calibration. It should  
be recorded by the  
user in the event it  
will be necessary to  
restore the Input  
adjustment. Use the MODE key to adjust the cursor position (i.e.. x D1, x Offset to the original  
value. This setting  
is also recorded on a  
label located under  
the cover of the  
MST2000.  
D10, x D100, etc.) to change the offset count by different increments. The  
available range is –50,000 to 50,000 counts (approximately +/- 20%  
adjustment of full scale). The factory default is as set by the factory during  
initial system calibration.  
Input Gain. The Input Gain parameter allows the user to adjust the gain This is a factory  
default setting  
of the actual pressure (full scale) value to the MST2000 displayed value.  
The input gain parameter is displayed and stored in memory as a gain  
multiplier. After the EDIT key is pressed, the edit menu displays the real  
time pressure input. The user then uses the INC and DEC keys to adjust  
the desired gain. The pressure input must be connected to a pressure  
source and at maximum range value during this adjustment. Use the  
determined during  
calibration. It should  
be recorded by the  
user in the event it  
will be necessary to  
restore the Input  
MODE key to adjust the cursor position (i.e.., x D1, x D01, x D001 etc.) to Gain to the original  
value. This setting  
is also recorded on a  
label located under  
the cover of the  
MST2000.  
change the gain multiplier by different increments. The available range is  
0.8000 to 1.2000 (approximately +/- 20 % adjustment of full scale). The  
factory default is as set by the factory during initial system calibration.  
Output Offset.The Output Offset parameter allows the user to adjust the This is a factory  
default setting  
actual 4 milliamp (zero) output value as referenced to the MST2000  
displayed zero value. The output offset parameter is displayed and  
stored in memory as counts. After the EDIT key is pressed, the edit menu  
displaystheactualcountoffsetandthemicroprocessorsetstheoutputto  
the 4.000 milliamp value. The user then presses the INC and DEC keys  
to adjust the desired milliamp offset. Use the MODE key to adjust the  
determined during  
calibration. It should  
be recorded by the  
user in the event it  
will be necessary to  
restore the Output  
cursor position (i.e. x D1, x D10, x D100, etc.) to change the offset count Offset to the original  
value. This setting is  
also recorded on a  
label located under  
the cover of the  
MST2000.  
by different increments. The available range is –1,000 to 10,000 counts  
(approximately 3.9 to 6.5 milliamp adjustment range). The factory default  
is as set by the factory during initial system calibration.  
Page 16  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
PROGRAM PARAMETERS  
Parameter  
Description  
FactoryDefault  
OUTPTG  
Output Gain.The Output Gain parameter allows the user to adjust the This is a factory  
default setting  
actual 20 milliamp (span) output value as referenced to the MST2000  
displayed full scale value. The output gain parameter is displayed and  
stored in memory as a gain multiplier. After the EDIT key is pressed, the  
edit menu displays the actual multiplier value and the microprocessor  
sets the output to the 20.000 milliamp value. The user then uses the  
INC and DEC keys to adjust the desired full scale milliamps. Use the  
determined during  
calibration. It should  
be recorded by the  
user in the event it  
will be necessary to  
restore the Output  
MODE key to adjust the cursor position (i.e., x D1, x D01, x D001 etc.) Gain to the original  
value. This setting  
is also recorded on a  
label located under  
the cover of the  
MST2000.  
to change the gain multiplier in different increments. The available  
range is 0.8000 to 1.1000. (Approximately 16.5 to 20.5 milliamp  
adjustment range). The factory default is as set by the factory during  
initial system calibration.  
þNOTE: The minimum and maximum output current range is 3.9 milliamps  
and 20.5 milliamps (3.8 milliamps is reserved for fault ‘low’ current and  
21.0 milliamps is reserved for fault ‘high’ current).  
þNote: If HART® communicationsareenabled,theminimumcurrentislim-  
ited to 4.0 milliamps.  
AVGFAC  
DEFDSP  
Averaging Factor. The Averaging Factor controls the digital filtering 1= No Filtering  
level (damping) of the displayed pressure value (and the 4-20 milliamp  
output). The average factor parameter controls the size (depth) of the  
digital FILO (first in – last out) filter algorithm. Available range is 1 to 10.  
The average factor does not affect the inherent update rate of the LCD  
or 4-20 milliamp output (approximately two times per second) except  
during power up initialization when the FILO registers are first being  
loaded.  
Default Display. The Default Display parameter assignment selects 0 = INWC for  
English.  
0 = MMWC for  
Metric.  
the LCD display mode after power up and initialization. Available  
assignments are:  
EnglishUnitVersion:0 = INWC (pri mary vari able), 1 = SCFM, 2 = ACFM,  
3=LBHRor4=SCAN.SelectingSCANwillcausethedisplaytosequence  
throughthecalculatedvariablesat4secondintervals.  
Metric Unit Version: 0 = MMWC (primary variable), 1 = NM3-HR, 2 =  
M3-HR, 3=KG-HRor4=SCAN. SelectingSCANwillcausethedisplayto  
sequence through the calculatedvariablesat4secondintervals.  
DSPRES  
aLARMS  
Display Resolution. The Display Resolution parameter assignment 3 = X.XXX  
controls the number of digits that are displayed to the right of the  
decimal. The display resolution can be set as fol lows:  
EnglishUnitVersion:From1to4Digitstotherightofthedecimal. Metric  
Unit Ver sion: From 1 to 3 Digits to the right of the dec i mal.  
The MST2000 has multiple alarm features. Alarms are available for 0 = Alarms Disabled  
4-20 milliamp limit checks (under-range and over-range), RTD faults,  
external 4-20 milliamp PCB communication failures and internal  
hardware circuit faults. Alarms are enabled and disabled by setting the  
individual binary bits in the ALARM WORD register to a ‘1’ or ‘0’  
respectively. Since the individual binary bits cannot be displayed on the  
LCD, the user must input the decimal word equivalent representing the  
enabled and disabled bits. The individual alarm bit assignments and  
the associated binary values are shown in Sec tion 9.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROGRAM PARAMETERS  
OPERATION MANUAL  
Parameter  
Description  
FactoryDefault  
P_WORD  
Password. The password is used to prevent unauthorized access to the 0 = Password  
Disabled  
programming parameters. The password may be any value between 0  
and 9999. A password value of 0 disables the password feature.  
BD_ENB  
Blow Down Enable. The Blow Down Enable parameter allows the user 0 = Blowdown  
Disabled.  
to enable or disable the integrated blow down sys tem.  
A value of ‘0’ disables the Blowdown Sequence.  
A value of ‘1’ enablestheblowdownfunctionwithexternaltrigger  
only. An external trigger must be appliedtotheIN1terminalto  
initiate the Blowdown sequence.  
A value between 2 and 1440 en ables the MST2000 to con trol the  
Blowdown sequence on timed intervals (in min utes). The time in-  
terval be gins as soon as the MST2000 is put back in ‘RUN’  
mode. For values be tween 2 and 1440 min utes, an ex ter nal trig-  
ger may also be applied to commandadditionalblowdownse-  
quences. The external trigger event does not re set the MST2000  
blowdown internaltimer.  
þNote: The min i mum ex ter nal trig ger pulse width is 500 mil li sec onds.  
HT_ENB  
HARTEnable. The HART® Enableparameterallowstheusertoenable 0 = Default if no  
HART® option  
installed.  
ordisabletheHART® Communicationoption. Availableassignmentsare  
0 = Dis abled and 1 = En abled.  
1 = Enabled if  
HART® option  
installed.  
þNote: IF the HART® option is enabled, 3.8 milliamp ‘fault current’ and 3.9  
milliamp ‘un der range’ cur rent val ues are not al lowed on the 4-20mA out put  
terminalsduringRUNMode.  
Page 18  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
ALARM PROGRAMMING INFORMATION  
9. ALARM PROGRAMMING INFORMATION  
9.1 Alarm ‘ENABLE’ Word Definition  
The ALARM ‘ENABLE’ WORD (16 bit word) is divided into two 8 bit bytes. The lower order byte (bits 1 –  
8) is used to enable and disable the alarm functions. The higher order byte (bits 9 – 16) is used to control  
how the alarm is displayed and/or output to the user interface. Some bits are currently undefined and  
reserved for future use.  
BIT  
16  
BIT  
15  
BIT  
14  
BIT  
13  
BIT  
12  
BIT  
11  
BIT  
10  
BIT  
9
BIT  
8
BIT  
7
BIT  
6
BIT  
5
BIT  
4
BIT  
3
BIT  
2
BIT  
1
32768  
16384  
8192  
4096  
2048  
1024  
512  
256  
128  
64  
32  
16  
8
4
2
1
9.2 Low Byte ‘BIT’ Definitions  
A. Under-range: Enabling the un der-range alarm bit will cause the under-range alarm to become ac-  
tive when the 4-20 milliamp output cur rent reaches 3.9 milliamps.  
B. Over-range: Enabling the over-range alarm bit will cause the over-range alarm to become active  
when the 4-20 milliamp output current reaches 20.5 milliamps.  
C. RTD Fault: Enabling the RTD fault alarm bit will cause the RTD fault alarm to become active if an  
open circuit or short circuit is sensed in the 4-wire RTD loop connection. See Section 9.3 G  
D. ISO Comm error: Enabling the ISO Comm er ror alarm bit will cause the ISO Comm erroralarm(s)  
to become active if any communication er rors or hard ware faults are de tected from any of theexter-  
nal 4-20 milliamp input boards. (ISO = IsolatedOutputModule). SeeSection9.3G.  
E. Hardware Fault: Enabling the Hardware Fault error alarm bit will cause the Hardware Fault error  
alarm to become active if any internal hardware circuit faults (including microprocessor watchdog  
timer faults) are detected from the MST2000 internal circuitry.  
þNote: For each alarm fault bit above, in di vid ual alarm sta tus bit(s) are pro vided in the ALARM STATUS word to  
iden tify which alarm is ac tive. Each alarm sta tus bit and the as so ci ated bi nary val ues are de scribed later in this  
section.  
9.3 High Byte ‘BIT’ Definitions  
A. Fail-low: Enabling the Fail-low bit will cause the 4-20 milliamp output to change to the fault current  
value of 3.8 milliamps if any alarm is active.  
B. Fail-high: Enabling the Fail-high bit will cause the 4-20 milliamp output to change to the fault current  
value of 21.0 milliamps if any alarm is active.  
C. Last-val: Enabling the Last-val bit will cause the 4-20 milliamp output to hold at the last value if any  
alarm is active.  
þNote:  
& The user must insure that only one of the 3 fault current control bits is set for proper operation.  
& When entering PROGRAM mode, the 4-20 milliamp output current will change to the fault current as set by the fault  
current control bits.  
D. LCD Icon: Enabling the LCD Icon bit will cause the LCD ‘Alarm’ icon to be turned on if any alarm is  
active.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALARM PROGRAMMING INFORMATION  
OPERATION MANUAL  
E. Latched Output: Enabling the Latched Output bit will cause any active alarm to become latched  
and held active even if the alarm condition clears. Any ‘latched’ alarms can be cleared during RUN  
mode by pressing the EDIT key (if the active alarm(s) are no longer active). After pressing the EDIT  
key, any latched alarms that are no longer active will be cleared and any alarms that are still active  
will remain latched.  
F. Digital Out1: Enabling the Digital Out1 bit will cause the digital output channel (OUT1) to change to  
the LOW state if any alarm is active.  
þNote: The OUT1 (and OUT2) channels are ‘open collector’ style outputs. The user must externally  
connect an active pull-up voltage to the output pins for proper operation. The maximum external pull-up  
voltage that can be applied to the output pins is 24 volts DC.  
G. External Constants: Enabling the Ex ter nal Con stants bit will cause the pro grammed con stants for  
temperature or pressure to be used in the mass flow calculations if eithertheexternaltemperature  
or pressureinputsareselectedandinfaultconditions.  
9.4 Alarm ‘STATUS’ Word Definition  
The ALARM STATUS word indicates which alarms are active during RUN mode. Since the  
individual binary bits cannot be displayed on the LCD, the decimal word equivalent representing the  
active alarm status bits is displayed. The individual alarm status bit assignments and the associated  
binary values are shown below.  
þNote: If alarms are ac tive, the alarm ICON on the LCD will be lit and the ALARM sta tus value will be dis-  
played ev ery 10 sec onds. The user may also use the INC/DEC keys to ac cess the alarm sta tus value on  
the LCD.  
BIT  
16  
BIT  
15  
BIT  
14  
BIT  
13  
BIT  
12  
BIT  
11  
BIT  
10  
BIT  
9
BIT  
8
BIT  
7
BIT  
6
BIT  
5
BIT  
4
BIT  
3
BIT  
2
BIT  
1
32768  
16384  
8192  
4096  
2048  
1024  
512  
256  
128  
64  
32  
16  
8
4
2
1
9.5 AlarmStatusBITDefinitions  
A. Under-range: Indicates Under-range alarm is active.  
Binary value = 1.  
B. Over-range: Indicates Over-range alarm is active.  
Binary value = 2.  
C. RTD Fault: Indicates RTD fault (open circuit or short circuit) alarm is active.  
Binary value = 4.  
D. ISO Comm1 error: Indicates communication or hardware fault error alarm from external 4-20 PCB  
channel 1 is active.  
Binary value = 8.  
E. ISO Comm2 error: Indicates communication or hardware fault error alarm from external 4-20 PCB  
channel 2 is active.  
Binary value = 16.  
F. ISO Comm3 error: Indicates communication or hardware fault error alarm from external 4-20 PCB  
channel 3 is active.  
Binary value = 32.  
Page 20  
MST2000 Multivariable SMARTFLOW® Transmitter  
ThermoBrandtInstruments  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
ALARM PROGRAMMING INFORMATION  
G. Hardware Fault: Indicates hardware fault error from MST2000 internal circuitry is active.  
Bi nary value = 64.  
H. Watchdog Timer Fault: Indicates watchdog timer fault error from internal microprocessor is active.  
Bi nary value = 128.  
9.6 Alarm ‘ENABLE’ Word Decimal CalculationExamples  
To calculate the decimal word equivalent for the ALARM ‘ENABLE’ WORD the user must determine  
which alarms and alarm control bits are to be enabled and then sum the binary values of each enabled  
bit. The decimal word equivalent is then programmed into the ALARM ‘ENABLE’ WORD using the  
programming menus.  
A. EXAMPLE 1  
The user desires to enable the following alarm/alarm control enable bits:  
LCD Icon, Fail-low, RTD Fault and Under-range.  
a. LCD Icon bi nary value = 2048  
b. Fail-low bi nary value = 256  
c. RTD Fault bi nary value = 4  
d. Un der-range bi nary value = 1  
Decimalequivalent sum = 2309 (dec i mal value to pro gram into ALARM ‘EN ABLE’ WORD).  
B. EXAMPLE 2  
The user desires to enable the following alarm/alarm control enable bits:  
Digital Out1, Latched Output, Fail-high, ISO Comm error, Over-range and Under-range.  
a. Dig i tal Out1 bi nary value = 8192  
b. Latched Out put bi nary value = 4096  
c. Fail-high bi nary value = 512  
d. ISO Comm er ror bi nary value = 8  
e. Over-range bi nary value = 2  
f. Un der-range bi nary value = 1  
Decimalequivalent sum = 12811 (dec i mal value to pro gram into ALARM ‘EN ABLE’ WORD).  
9.7 Alarm ‘STATUS’ Word Decimal Decode Examples  
To determine which individual alarm status bits are active, the user must take the decimal equivalent  
value from the ALARM ‘STATUS’ WORD register and decode it into the associated binary bit values.  
This is accomplished using binary division of the decimal word. The examples below show manual  
division. The user may also use a decimal to binary calculator to simplify this procedure.  
A. Example 1  
ALARM ‘STATUS’ WORD = 37  
Using binary division, divide the decimal word by each bi nary bit value start ing with the most sig-  
nificant bit value (bit 8 = 128) and then each successivelowerbit.  
a.  
b.  
c.  
d.  
37 B 128 = 0 with a re main der of 37 . . . . . . . bit 8 (Watch dog timer fault) = 0  
37 B 64 = 0 with a remainderof37 . . . . . . . . bit 7 (Hard ware fault) = 0  
37 B 32 = 1 with a remainderof5 . . . . . . . . . bit 6 (ISO comm3 er ror) = 1  
5 B 16 = 0 with a re main der of 5 . . . . . . . . . bit 5 (ISO comm2 er ror) = 0  
e. 5 B 8 = 0 with a re main der of 5 . . . . . . . . . . . bit 4 (ISO comm1 er ror) = 0  
f.  
5 B 4 = 1 with a re main der of 1 . . . . . . . . . . . bit 3 (RTD fault) = 1  
g. 1 B 2 = 0 with a remainder of 1 . . . . . . . . . . bit 2 (Over-range) = 0  
h.  
1 B 1 = 1 with a re main der of 0 . . . . . . . . . . . bit 1 (Un der-range) = 1  
The decimal ALARM ‘STATUS’ WORD of 37 indicatesthefollowingactivealarms:  
ISO Comm3 error, RTD fault and Under-range.  
B. Example 2  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FORMULAS & CONVERSION FACTORS  
ALARM ‘STATUS’ WORD = 206  
OPERATION MANUAL  
Using bi nary di vi sion, di vide the dec i mal word by each bi nary bit value start ing with the most sig-  
nificant bit value (bit 8 = 128) and then each successive lower bit.  
a.  
206 B 128 = 1 with a remainderof78 . . . . . . bit 8 (Watchdog timer fault) = 1  
b.  
78 B 64 = 1 with a remainderof14. . . . . . . . bit 7 (Hard ware fault) = 1  
c. 14 B 32 = 0 with a remainder of 14 . . . . . . . . bit 6 (ISO comm3 er ror) = 0  
d.  
14 B 16 = 0 with a remainder of 14 . . . . . . . . bit 5 (ISO comm2 er ror) = 0  
e. 14 B 8 = 1 with a remainderof6 . . . . . . . . . . bit 4 (ISO comm1 er ror) = 1  
f.  
g.  
h.  
6 B 4 = 1 with a re main der of 2 . . . . . . . . . . . bit 3 (RTD fault) = 1  
2 B 2 = 1 with a re main der of 0 . . . . . . . . . . . bit 2 (Over-range) = 1  
0 B 1 = 0 with a re main der of 0 . . . . . . . . . . . bit 1 (Un der-range) = 0  
The decimal ALARM ‘STATUS’ WORD of 206 indicatesthefollowingactivealarms:  
Watchdog timer fault, Hardware fault, ISO Comm1 error, RTD fault and Over-range.  
10. FORMULAS & CONVERSION FACTORS  
The following formulas are used in the MST2000 software calculations:  
Velocity =1096.845 ´ DP ¸ Density  
ACFM = Ae ´ 667.657 ´ DP ´ T ¸ P  
(
)
SCFM = Ae ´ 23972..677 ´ DP ´ P ¸ T  
LB / HR = SCFM ´ Standard Density (@68o F) ´ 60  
(
)
Ae or Effective Area (sq.ft) = Kfactor ´ Nominal Area (sq.ft). Thermo Brandt supplies the  
Effective Area (Ae) specification with each of its flowmeters.  
Where:  
6 Velocityis in Feet per Min ute  
6 DP (Dif fer en tial Pres sure) is in Inches of Wa ter Col umn  
6 T (Temperature)isindegreesRankine(degreesRankine=degreesFahrenheit+459.67)  
6 P (Ab so lute pres sure) is in pounds per square inch (PSI)  
6 Density is in pounds per cu bic foot (Lb/FT3)  
6 Ae (Ef fec tive Area) is in Square Feet.  
Metric Conversion Factors  
Meters per second x 196.850 = Feet per minute  
Bar x 14.5038 = PSIA  
Square me ters x 10.7643 = Square feet  
Millimeters of watercolumn B 25.4 = Inches of WaterColumn  
Kilograms per hour x 2.205 = Pounds per hour  
Kilograms per cubicmeterB 16.0136 = Pounds per cubic foot.  
Cu bic meters per hour x 0.5885 = Cubic feet per minute  
(De grees C + 273.15) x 1.8 = de grees Ran kine  
Ae or Ef fec tive area (in square feet) = Kfactor x Nom i nal Area (square me ters) x 0.0929.  
Thermo Brandt supplies the EffectiveArea(Ae) specificationwith each of its flowmeters. The  
user must converttosquaremetersbeforeenteringtheeffectiveareparameterintheE_AREA’  
programming menu.  
11.  
Page 22  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
TEST JACK  
TEST JACK  
ATestJackisstandardontheNonI.S. ApprovedMST2000’s.ItallowstheusertomonitorthemAout-  
putoftheunitwithoutdisconnectingtheloop.Reviewdimensionaldrawingsonpage4. The Test Jack  
is removed for all I.S. and Division 2 approved MST2000’s.  
TomonitorthemAoutputoftheMST2000youwillneedaprecisionmilliammeter.Pushthepositivel ead  
from the meter into the positive jack (RED) and the negative lead from the meter into the negativejack  
(BLACK).  
12. OPTIONAL MODULE INSTALLATION  
The MST2000 Loop Powered Multivariable SMARTFLOW® Transmitters design is such that op-  
tionalinput,digitalI/OandHART® communicationmodulescanbeinstalledinthefield. Thisallowsthe  
usertheversatilitytochangeandadapttodifferentapplicationneeds.Thissectioncontains guidelines  
forinstallingtheoptionalmodulesandupdatingtheMST2000’sprogrammingifnecessary.Please re-  
view this section before attempting to make any upgrades. If there are any questions or problems  
please call the factory for assistance.  
þNOTE:  
& Any upgrades should be made in a clean and dust free environment.  
& Anti-static discharge precautions should be adhered to.  
12.1 Isolated 4-20mA Input Modules(ISOModule)  
A. Thermo Brandt Part Number FP37-OPTN-ISO  
a. The Iso lated 4-20mA In put Mod ule (ISO) al lows the MST2000 to ac cept an iso lated 4-20mA sig nal  
fromeitheranAbsolutePressureTransmitteror ExternalTemperatureTransmitter.The 2nd D.P.  
Transmitter Op tion is un avail able at the time this man ual was printed.  
b. All iso lated 4-20mA In put Mod ules are iden ti cal, but they must be mounted in the cor rect lo c ationon  
the Main Board. See pho to graph and draw ings in this sec tion.  
c. The Mod ule will be shipped in a sealed bag along with stand offs (2) and in struc tion sheet.  
B. Installing the ISO Module Option.  
a. Dis con nect all power from the MST2000.  
b. De cide which slot the ISO Mod ule will fill. Re move the Op tion Cover La bel cov er ing that slot.  
c. Take off the MST2000 Cover by re mov ing the 4 flat head screws. It is not nec es sary to re move the  
Main Board from the hous ing.  
d. Lo cate the slot, con nec tor and two mount ing holes for the ISO Mod ule on the Main Board.  
e. Re move the ISO Mod ule and two (2) stand offs from the bag.  
f. Snap the Stand offs into the two holes lo cated on the Main Board as shown in the draw ing. Note the  
orientationofthestandoff.  
g.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL MODULE INSTALLATION  
OPERATION MANUAL  
Align the ISO Mod ule such that the re set but ton and LED are to ward the LCD and fac ing up. The  
connector will be on the bot tom of the board. Snap the ISO Mod ule into the stand offs while mak ing  
sure the con nec tor and header are prop erly aligned.  
h. Re place the cover.  
i. Hook up the MST2000 as per the terminalblockwiringdiagramonpage7.  
j. Ap ply Power to the MST2000.  
C. Programming the MST2000 to recognize the ISO Module(s)  
a.  
ReviewSection7onProgrammingandSection8onParameters.  
b. De pending on which slot the ISOModulewasinstalled, selectoneofthefollowingparameterstoedit:  
c.  
TMPSRC: TemperatureSource.  
d.  
APRSRC: AbsolutePressureSource.  
e.  
Use the INC or DEC but tons to scroll to ‘1=EXT’ (1 = EXTernal)  
f. Press the EDIT key to save this change to memory.  
D. Calibrating the ISO Module  
a. ExternalAbsolutePressureTransmitterISOModule.ReviewtheProgramParametersinsection8.  
i. Connecta4-20mAsourcetotheAbsolutePressureTransmitterISOModuleinputterminals  
(marked EXTIN 1). See ter mi nal block draw ing on page 7.  
ii.  
MakesureparameteraprSRC (Ab so lute Pres sure Zero Source) is set to 1 (1 = EXTernal).  
Set the EX_APZ (AbsolutePressureZero)parameter.  
Set the APZCAL (AbsolutePressureZeroCalibration)parameter:  
iii.  
iv.  
.
.
! Press the Edit key. Dis play will change to read IN4mA.  
! Ap ply 4.0 milliamps. Press the Edit Key to read and store the 4 milliamp cal i bra tion value.  
v.  
Set the EX_ABS(AbsolutePressureSpan)parameter.  
Set the APSCAL(AbsolutePressureSpanCalibration)parameter.  
vi.  
.
.
! Press the Edit key. Dis play will change to read IN20mA.  
! Ap ply 20.0 milliamps. Press the Edit Key to read and store the 20 milliamp cal i bra tion value.  
þNOTE: For those MST2400 with the Integral Absolute Pressure Transmitter option installed , the ISO  
Module has been calibrated at the factory.  
Page 24  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
OPTIONAL MODULE INSTALLATION  
b. ExternalTemperature TransmitterISOModule.ReviewtheProgramParametersinsection 8.  
i. Connecta4-20mAsourcetotheExternalTemperatureTransmitterISOModuleinputterminals  
(marked EXTIN 2). See ter mi nal block draw ing on page 7.  
ii.  
Makesureparameter TMPSRC (Tem per a ture Source) is set to1 (1 = EXTernal).  
Set the EX_TPZ (TemperatureZero)parameter.  
Set the TPZCAL (TemperatureZeroCalibration)parameter.  
iii.  
iv.  
.
.
! Press the Edit key. Dis play will change to read IN4mA.  
! Ap ply 4.0 milliamps. Press the Edit Key to read and store the 4 milliamp cal i bra tion value.  
v.  
Set the EX_TPS(TemperatureSpan)parameter.  
Set the TPSCAL (TemperatureSpanCalibration)parameter.  
vi.  
.
.
! Press the Edit key. Dis play will change to read IN20mA.  
! Ap ply 20.0 milliamps. Press the Edit Key to read and store the 20 milliamp calibrationvalue.  
12.2 Digital Input / Output Module Installation  
A. Thermo Brandt Part Number FP37-OPTN-DIO  
a. The Dig i tal I/O mod ule al lows the MST2000 to ac cept one (1) dig i tal in put and out put (1) digitalout-  
puts.  
b. The Dig i tal I/O mod ule must be in stalled on the right most con nec tor. See pho to graph and drawings  
in this sec tion.  
c. The Dig i tal I/O module will be shipped in a sealed bag along with stand offs (2) and in struc tion sheet.  
B. Installing the Digital I/O Module Option.  
a. Dis con nect all power from the MST2000.  
b. Take off the MST2000 Cover by re mov ing the 4 flat head screws. It is not nec es sary to re move the  
Main Board from the hous ing.  
c. Lo cate the slot, con nec tor and two mount ing holes for the Dig i tal I/O module on the Main Board.  
d. Re move the Dig i tal I/O module and two (2) stand offs from the bag.  
e. Snap the standoffs into the two holes lo cated on the Main Board as shown in the draw ing. Note the  
orientationofthestandoffs.  
f. Align the Digital I/O mod ule such that con nec tor will be on the bot tom of the board. Snap the module  
into the stand offs while mak ing sure the con nec tor and header are prop erly aligned.  
g. Re place the cover.  
h. Hook up the MST2000 as per the ter mi nal block wir ing di a gram on page 7.  
i. Ap ply Power to the MST2000.  
C. For Digital I/O wiring configurationssee section14.  
12.3 HART® CommunicationsModule  
A. Thermo Brandt Part Number FP37-OPTN-HART  
a. The HART® CommunicationmoduleallowstheMST2000tocommunicatewithstandardHART® In-  
terfaces.  
b. The HART® Communicationmodulemustbeinstalledontheupperleftmost connector. Seephoto-  
graph and drawingsinthissection.  
c. The HART® Com mu ni ca tion mod ule will be shipped in a sealed bag along with stand offs (2) and in-  
structionsheet.  
B. Installing the HART® Communication Module Option.  
a. Dis con nect all power from the MST2000.  
b. Take off the MST2000 Cover by re mov ing the 4 flat head screws. It is not nec es sary to re move the  
Main Board from the hous ing.  
c. Lo cate the slot, con nec tor and two mount ing holes for the HART® mod ule on the Main Board.  
d. Re move the HART® mod ule and two (2) stand offs from the bag.  
e. Snap the Stand offs into the two holes lo cated on the Main Board as shown in the draw ing. Note the  
orientationofthestandoff.  
f.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MST2000 HART® Communications Information  
OPERATION MANUAL  
Align the HART® mod ule such that con nec tor will be on the bot tom of the board. Snap the mod ule  
into the stand offs while mak ing sure the con nec tor and header are prop erly aligned.  
g. Re place the cover.  
h. Hook up the MST2000 as per the terminalblockwiringdiagramonpage7.  
i. Ap ply Power to the MST2000.  
13. MST2000 HART® Communications Information  
13.1 Power and Loop Conditions  
The MST2000 Multivariable differential pressure transmitter is a HART® conforming loop-powered  
4-20 milliamp transmitter. Power connection is made at the two left terminal positions marked LOOP+  
and LOOP-. Nominal power supply voltage is 24 volts DC which allows up to 600 ohms series  
resistance in the loop circuit. Higher loop resistance can be used with higher power supply voltages as  
required. See the loop resistance-voltage graph below in determining the minimum loop voltage  
required.  
Note: For HART® communication applications, minimum loop resistance is 250 ohms.  
13.2 HART® Connections  
Maximum resistance  
versus DC loop voltage  
All electrical connections are per standard HART® connections. Refer to HART® Communication  
Foundation Document HCF_SPEC-54 (HART® FSK Physical Layer Specification, Revision 8.0) for  
additional information. The current sense resistor may be connected in either the high or low sideof the  
field loop wiring. HART® communication devices must be connected in accordance with  
HCF_SPEC-54forproperoperation. Typicalconnectionmethodsareshowninthefollowingdiagrams.  
13.3 CablingRequirements  
The field wiring of a HART® based system should use shielded twisted pair cable. When using cable  
with multiple twisted pairs, it is important not to use the other pairs for signals that might interfere with  
the HART® communication signals.  
Typical multi-drop  
connection with digital  
communications.  
Page 26  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
MST2000 HART® Communications Information  
Typical Point to Point  
Connection with  
analog signaling.  
Ifthecableislongerthanseveralmeters,it’sresistanceandcapacitancemaybecomesignificantinthe  
HART®RCtime-constantlimitation®xC65microseconds).Whenusingasinglefielddeviceanda  
hostwitha250ohmloadandnoothersignificantresistance,the65microsecondlimitationwouldallow  
0.26 uFofcapacitanceforthesystem.Allowing0.01uF(10,000 pF) for the host and field de vice (each  
having a CN=1), the to tal ca ble ca pac i tance could be up to 0.25uF. However, if the cable resistance  
was110ohms,thesystemresistancebecomes360ohms,whichthenallowsforatotalpermittedcable  
capacitanceof0.18uF.Thiscorrespondstoanominalcablelengthof900metersforacablewitharat-  
ing of 200 pF/meter. If the cable needs to be extended upward towards the maximum HART® cable  
length of 1500 meters, acablewithalowercapacitanceratingmustbeselected.  
In a multi-dropped system, the additionalcapacitance from each networkedtransmittermust  
also be considered. Each transmitter has an es tab lished CN value. A CN value of 1 in di cates  
that the transmitterrepresents 5000 pF of load capacitance.  
The MST2000 trans mit ter has a CN Value of 1 ( 5000pF).  
The internalresistance of the MST2000 trans mit ter is in ex cess of 100,000 ohms and can be ig-  
nored in the cable length calculations.  
13.4 HART® Communication Distance  
Up to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies  
depending on type of cable used.  
Use the following formula to determine cable length for specific applications:  
65´ 106  
C +10000  
(
)
f
L =  
-
R ´ C  
C
(
)
Where:  
L = Length in Meters or Feet  
R = Resistance in Ohms (W ) including barrier resistance.  
C = Cable capacitance in pF/m or pF/ft  
Cf = Maximum shunt capacitance of receiving devices in pF/m or pF/ft.  
13.5 Power Supply Requirements  
To minimize signal degradation of the HART® communication signals, the following power supply  
specifications are required.  
Voltage: . . . . . . . . . . . . . . . . . . . . . . . 24 V DC (typical)  
Max i mum rip ple (47 to 125 Hz): . . . . . . . . . . 0.2 V (peak to peak)  
Max i mum noise (500 Hz to 10 kHz): . . . . . . . . 1.2 mV  
Maximumseriesimpedance(500Hzto10kHz):. . 10 ohms  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MST2000 HART® Communications Information  
OPERATION MANUAL  
13.6 Intrinsic Safety Considerations  
Intrinsic safety approvals for the MST2000 are pending. Contact the factory for additional information  
involving hazardous applications with the use of safety barriers.  
13.7 HART® Command Information  
The MST2000 transmitter is compliant with HART® Command Revision 5.1. The following commands  
are supported. Reference HART® Document HCF_LIT-20 (HART® Technical Overview) for additional  
information.  
COMMAND  
HART® Command Set  
Description  
0
Universal  
Universal  
Read Unique Identifier  
Read Primary Variable (pv)  
Read (pv) current and percent of range  
Read (pv) current and four predefined variables  
Write Polling Address  
1
2
Universal  
3
Universal  
6
Universal  
11  
12  
13  
14  
15  
16  
17  
18  
19  
35  
50  
51  
59  
Universal  
Read Unique Identifier associated with Tag  
Read Message  
Universal  
Universal  
Read Tag, Descriptor, Date  
Universal  
Read sensor information  
Universal  
Read output information  
Universal  
Read final assembly number  
Write message  
Universal  
Universal  
Write tag, descriptor, date  
Universal  
Write final assembly number  
Write (pv) range values  
Common Practice  
Common Practice  
Common Practice  
Common Practice  
Read dynamic variable assignments  
Write dynamic variable assignments  
Write number of response preambles  
pv = primary variable  
13.8 Thermo Brandt Instruments HART® ManufacturerIdentification Code = 96 Hex, 150 Decimal  
13.9 MST2000 HART® TransmitterVariableCodeAssignments.  
VariableCode  
ENGLISH UNIT VERSION  
DP in Inches of W.C.  
METRIC UNIT VERSION  
D.P. InMillimetersofW.C.  
0 or 1  
2
3
4
5
6
Stan dard Cu bic Feet Per Min ute (SCFM)  
Ac tual Cu bic Feet per Min ute (ACFM)  
Mass in Pounds per Hour (LB/HR)  
ExternalTemperatureinDegreeFahrenheit  
ExternalAbsolutePressureinPSIA  
Nor mal Cu bic Me ters Per Hour (NM3-HR)  
Cu bic Me ters per Hour (M3-HR)  
Mass in Ki lo grams per Hour (KG-HR)  
ExternalTemperatureinDegreeCelsius  
ExternalAbsolutePressureinBAR  
Page 28  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
Wiring Diagrams  
14. Wiring Diagrams  
FourWireConnectionwithAbsolutePressureTransmitter  
Dual2WireConnectionwithAbsolutePressureTransmitter  
The MST2000 with a Ab so lute Pres sure Trans mit ter can be wired to re-  
placeyourexistingfourwiretransmitter  
TheMST2000withAbsolutePressureTransmittercanbewiredtoreplace  
your ex ist ing four wire trans mit ter. Re quires two 24Vdc power sources.  
ThreeWireConnectionwithAbsolutePressureTransmitter.  
Power Sup ply & Ab so lute Pres sure Trans mit ter  
The MST2000 with Ab so lute Pres sure Trans mit ter can be wired to re place The MST2000 with Ab so lute Pres sure Trans mit ter can be sup plied with a  
yourexistingthreewiretransmitter. powersupplytopowertheMST2000andAbsolutePressureTransmitter.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
OPERATION MANUAL  
PowerSupplyandAbsolutePressureTransmitter  
2 Wire RTD Connection  
The MST2000 with Ab so lute Pres sure Trans mit ter can be sup plied with a  
power sup ply to power the Ab so lute Pres sure only. The MST2000 will be  
pow ered by a 24Vdc, 4-20mA loop.  
3 Wire RTD Connection  
4 Wire RTD Connection  
Page 30  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
MST2000HazardousAreaInstallation  
Digital I/O Connections for Integral Blowdown System  
15. MST2000 Hazardous Area Installation  
The MST2000 Multivariable SMARTFLOWTM TransmitterisCanadianStandards As-  
sociationapproved for the following hazardousareaclassifications.  
15.1 IntrinsicallySafeInstallations  
A. Model MST2100 (NEMA 1): In trin sically Safe for CL. I, Grps. C & D  
B. Model MST2400 (NEMA 4X): In trin sically Safe for CL. I, Grps. C & D. CL. II, Grps.  
E, F & G  
ForIntrinsicallySafeapplications, unitmustbeinstalledperThermoBrandtinstallationdrawingnumber  
SC37-4000-00. See Page 29.  
In trin sically safe en tity pa ram e ters: Vmax = 40 VDC, Imax = 165mA, Ci = 0uf, Li = 240uH.  
Maximumoperatingambienttemperature:66DegreesC(151DegreesF)  
15.2 Division 2 And Other Installations:  
A. Model MST2100 (NEMA 1): CL I, Div. 2, Grps. C & D  
B. Model MST2400 (NEMA 4X): CL I, Div. 2 Grps. C & D. CL II, Div. 2 Grps. E, F & G. CL. III, Div. 2  
ForDivision2applications, unitmustbeinstalledperCanadianand/orNationalElectrical Code re quire-  
ments for Division2areas.Intrinsicsafetybarriersarenotrequired.  
Di vi sion 2 power rat ings: Vmax = 40 VDC, Imax = 165mA.  
Maximumoperatingambienttemperature:66degreesC(151DegreesF).  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MST2000 Hazardous Area Installation  
OPERATION MANUAL  
15.3 Approved Options.  
See the chart below and re view the Model Num ber De scrip tion on Page 2.  
MST2100  
OPTION  
MST2400  
Intrinsically  
Safe  
Not  
Certified  
Intrinsically  
Safe  
Not  
Division2  
Division2  
Certified  
HART COMMUNICATIONS  
4 Wire RTD  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ISO4-20mATemperatureInputModule  
ISO4-20mAPressureInputModule  
DigitalI/OCard  
X
X
X
High Pres sure Blow Down  
Integral120VACPowerSupply  
AbsolutePressureTransmitter  
Heater  
N/A  
N/A  
N/A  
N/A  
N/A  
X
ContinuousPurge  
X
X
Test Jacks  
TerminalBlock4  
X
15.4 MST2000 I.S. Installation Drawing SC37-4000-00  
See Notes for Draw ing SC37-4000-00 on next page:  
Page 32  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION MANUAL  
CalibrationoftheMST2000  
15.5 Notes for MST2000 I.S. Installation DrawingSC37-4000-00  
ForI.S.Installations,fieldwiringshallbeinstalledinaccordancewithCanadianElect ricalCodeand/orNational  
ElectricalcodeANSI/NFPA70,Article504-30  
1.  
Wiring ca ble shall be 24 AWG or heavier, sep a rate shielded pairs.  
2.  
3.  
4.  
5.  
The ground ing con nec tion be tween the safety bar rier and earth ground must be less than 1 ohm.  
Con trol room equip ment must not gen er ate more than 250 Volts rms.  
Safety Bar riers must be of ap proved types and used in an ap proved con fig u ra tion where the transmitterVmax  
value is greater than the bar rier Voc rat ing and the trans mit ter Imax value is greater than the BarrierIscrating.  
Thetransmitterinputcapacitance(Ci)plusthetotalcablecapacitanceforeachloopmust not ex ceed the bar rier  
Carating.  
6.  
Thetransmitterinputinductance(Li)plusthetotalcableinductanceforeachloopmustnot ex ceed the bar rier La rat ing.  
Trans mit ter en clo sure must be grounded to earth ground us ing the pro vided ground lug on the enclosure.  
TheMST2000TransmitterisIntrinsicallySafefor:  
7.  
8.  
9.  
! Class I, Di vi sion 1, Groups C and D  
! Class II, Di vi sion 1 Groups E, F and G.  
Loopentityparameterspercircuitare:  
10.  
! Vmax = 40 VDC  
! Imax = 165mA  
! Ci = 0uF  
! Li = 240uH  
Use only CSA ap proved I.S. Pres sure trans mit ters where the Vmax and Imax of the trans mit ter is greater than the Voc and Isc of the bar rier.  
TheCiandLiofthetransmittermustbeincludedinsystemtotalcapacitanceandinductance cal cu la tion and must be less than bar rier Ca  
and La Rat ings.  
11.  
12.  
Approvedmethodsforseparationofeachloopare:  
! RunningLoopsinseparatecables  
! RunningLoopsinseparateshields  
WhenconnectingHARTcommunicatortheVmaxandImaxofthecommunicatormustbegreaterthan the Voc and Isc of the bar rier. Voc of  
communicatorplusVocofbarriermustbelessthanVmaxoftransmitter, ISCofCommunicator plus Isc of Bar rier must be less than Imax of  
Transmitter. LiofTransmitterplusLiofCommunicatormustbelessthanLaofBarrier, CioftransmitterplusCiofCommunicatormustbe  
less than Ca of Bar rier.  
13.  
Use only listed and ap proved dust tight seal for Class II and Class III Haz ard ous Lo ca tions.  
OtherwireterminalsnotavailableforuseonIntrinsicallySafeversion  
14.  
15.  
16.  
NorevisionsshallbemadewithoutnotificationofApprovalAgency(s).  
16. Calibration of the MST2000  
BasiccalibrationoftheMST2000Seriestransmittersisdoneintwoparts:1)settingthe4-20mAoutput  
fromthedigitaltoanalogconverterand2)settingthe0&100%valuesofthedisplayedDP. Both parts  
are done by the settingofparameters,enteredviatheintegralkeypad.  
16.1 OUTPUT mA CALIBRATION  
A. ZERO and SPAN of the mA outputaresetbytheOUTPTOandOUTPTGparameters, respectively.  
You do not need to apply any DP signalforthemAcalibration, onlyanaccuratemAtestmeter is re-  
quired.  
B. Fol low ing the pro ce dures of Sec tion 7, en ter the PROGRAMMING Mode and se lect the OUTPTO  
parameter. The existing value of OUTPUT OFFSET will be displayed.  
C. Press the EDIT/SAVE key once to force the digitaltoanalogconvertertoits0%outputvalue and to  
allow you to adjust the output to exactly 4.00mA as read on a mA test me ter. Use the INCREMENT  
& DECREMENT keys as needed.  
D. Press the EDIT/SAVE key to exit the edit mode and save the OUTPUT OFFSET value (even if there  
was no adjustment made). Now step to the OUTPTG parametertodisplaytheexistingvalueof  
OUTPUT GAIN.  
E. Press the EDIT/SAVE key once to force the digitaltoanalogconverteroutputtoits100%value and  
to al low you to ad just the out put to ex actly 20.00mA as read on a mA test me ter. Use the  
INCREMENT & DECREMENT keys as needed.  
F. Press the EDIT/SAVE key to exit the edit mode and save the OUTPUT GAIN value. This completes  
theoutputmAcalibration.  
G. Exit the PROGRAMMING Mode, by pressing the MODE key, or continuewiththeDPcalibration.  
Brandt Instruments, Inc.  
MST2000 Multivariable SMARTFLOW® Transmitter  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CalibrationoftheMST2000  
OPERATION MANUAL  
16.2 DP CALIBRATION  
þNOTE: For MST2000 Trans mit ters with CONTINUOUS PURGE OPTION. Do not use a hand pump, or com-  
pres sion cyl in der type of pres sure source for the DP test sig nals. You must use a vented source to per-  
mitcontinuousflowofpurgeair. Contactthefactoryforadditionalinformationoncalibrating  
transmitterswithcontinuouspurge.  
þNOTE: Do not turn off the purge air sup ply to use the trans mit ter as though it does not have the purge  
op tion; this will cause er rors.  
A. Connect an accurate test DP sig nal to the MST2000, equal to the 0% minimum range value.  
B. While in the PROGRAMMING MODE, step to the INPUTO parameter to display the existing value  
of INPUT OFFSET.  
C. Press the EDIT/SAVE key once to dis play the DP read ing. Use the INCREMENT/DECREMENT  
keys as needed to ad just the dis play to match the test DP sig nal value.  
D. Press the EDIT/SAVE key to exit the edit mode and to save the INPUT OFFSET value, (even if it  
was not changed).  
E. Ad just the test DP sig nal to the 100% max i mum range value. Step to the INPUTG pa ram e ter to dis-  
play the ex ist ing value of INPUT GAIN.  
F. Press the EDIT/SAVE key once to dis play the DP read ing. Use the INCREMENT/DECREMENT  
keys as needed to ad just the dis play to match the test DP sig nal value.  
G. Press the EDIT/SAVE key to exit the edit mode and to save the INPUT GAIN value.  
þNOTE: Changes to INPUTO or INPUTG will af fect both the dis play & the mA for any ap plied DP value.  
Ad justing OUTPTO or OUTPTG will af fect only the mA value for any ap plied DP value.  
Page 34  
MST2000 Multivariable SMARTFLOW® Transmitter  
Brandt Instruments, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Smooth Fitness Treadmill 945TV User Manual
Speco Technologies Camcorder VL7038IRVF User Manual
SPX Cooling Technologies Electric Heater 92 1322C User Manual
SPX Cooling Technologies Humidifier BA 07011 User Manual
Stamina Products Fitness Equipment 4500 User Manual
Sterling Plumbing Hot Tub 6103 Series User Manual
Stiga Lawn Mower 13 6103 19 User Manual
Sunbeam Toaster 3822 033 User Manual
Symphonic Flat Panel Television STL1504 User Manual
Tally Genicom Model Vehicle I 12013 1 User Manual