System Sensor Stud Sensor PDRP 1001 User Manual

3825 Ohio Avenue  
St. Charles, IL 60174  
1-800-SENSOR2  
Fax: (630) 377-6495  
PDRP-1001  
Series  
Deluge - Preaction Control  
Panel  
Instruction Manual  
Document 50734  
I56-933-01  
D
04/06/2001  
Rev:  
PN 50734:D0  
ECN 00-543  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adherence to the following will aid in problem-free  
installation with long-term reliability:  
Installation Precautions  
WARNING - Several different sources of power can be con-  
nected to the fire alarm control panel. Disconnect all sources  
of power before servicing. Control unit and associated equip-  
ment may be damaged by removing and/or inserting cards,  
Like all solid state electronic devices, this system may  
operate erratically or can be damaged when subjected to light-  
ning-induced transients. Although no system is completely  
immune from lightning transients and interferences, proper  
modules, or interconnecting cables while the unit is energized. grounding will reduce susceptibility. Overhead or outside  
Do not attempt to install, service, or operate this unit until this  
manual is read and understood.  
aerial wiring is not recommended, due to an increased sus-  
ceptibility to nearby lightning strikes. Consult with the Techni-  
cal Services Department if any problems are anticipated or  
encountered.  
CAUTION - System Reacceptance Test after Software  
Changes. To ensure proper system operation, this product  
must be tested in accordance with NFPA 72 Chapter 7 after  
any programming operation or change in site-specific soft-  
ware. Reacceptance testing is required after any change, ad-  
dition or deletion of system components, or after any modifica-  
tion, repair or adjustment to system hardware or wiring.  
Disconnect AC power and batteries prior to removing or in-  
serting circuit boards. Failure to do so can damage circuits.  
Remove all electronic assemblies prior to any drilling, filing,  
reaming, or punching of the enclosure. When possible, make  
all cable entries from the sides or rear. Before making modifi-  
cations, verify that they will not interfere with battery, trans-  
former, and printed circuit board location.  
All components, circuits, system operations, or software func-  
tions known to be affected by a change must be 100% tested.  
In addition, to ensure that other operations are not inadvert-  
ently affected, at least 10% of initiating devices that are not  
directly affected by the change, up to a maximum of 50 de-  
vices, must also be tested and proper system operation veri-  
fied.  
Do not tighten screw terminals more than 9 in-lbs.  
Over-tightening may damage threads, resulting in reduced  
terminal contact pressure and difficulty with screw terminal  
removal.  
Though designed to last many years, system components  
can fail at any time. This system contains static-sensitive  
components. Always ground yourself with a proper wrist strap  
before handling any circuits so that static charges are re-  
moved from the body. Use static-suppressive packaging  
to protect electronic assemblies removed from the unit.  
This system meets NFPA requirements for operation at  
0-49° C/32-120° F and at a relative humidity of 85% RH (non-  
condensing) at 30° C/86° F. However, the useful life of the  
system's standby batteries and the electronic components  
may be adversely affected by extreme temperature ranges  
and humidity. Therefore, it is recommended that this system  
and all peripherals be installed in an environment with a nomi-  
nal room temperature of 15-27° C/60-80° F.  
Follow the instructions in the installation, operating, and  
programming manuals. These instructions must be followed  
to avoid damage to the control panel and associated  
equipment. FACP operation and reliability depend upon  
proper installation by authorized personnel.  
Verify that wire sizes are adequate for all initiating and  
indicating device loops. Most devices cannot tolerate more  
than a 10% I.R. drop from the specified device voltage.  
FCC Warning  
Canadian Requirements  
WARNING: This equipment generates, uses, and can  
radiate radio frequency energy and if not installed and  
used in accordance with the instruction manual, may  
cause interference to radio communications. It has  
been tested and found to comply with the limits for class  
A computing device pursuant to Subpart B of Part 15 of  
FCC Rules, which is designed to provide reasonable  
protection against such interference when operated in a  
commercial environment. Operation of this equipment in  
a residential area is likely to cause interference, in which  
case the user will be required to correct the interference  
at his own expense.  
This digital apparatus does not exceed the Class A  
limits for radiation noise emissions from digital  
apparatus set out in the Radio Interference Regulations  
of the Canadian Department of Communications.  
Le present appareil numerique n'emet pas de bruits  
radioelectriques depassant les limites applicables aux  
appareils numeriques de la classe A prescrites dans le  
Reglement sur le brouillage radioelectrique edicte par le  
ministere des Communications du Canada.  
LimWarLg.p65 01/10/2000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NFPA Standards  
NFPA Standards  
This control panel complies with the following NFPA standards:  
• NFPA 13 - Sprinkler Systems  
• NFPA 15 - Water Spray Systems  
• NFPA 16 - Foam-Water Deluge Systems and Foam-Water Spray Systems  
NFPA 72 - Central Station Signaling Systems (Automatic, Manual, and Waterflow) - Protected  
Premises Unit  
Requires NOTI-FIRE 911AC DACT or 411UDAC Universal Digital Alarm Communicator  
NFPA72-LocalFireAlarmSystems(Automatic,Manual,WaterflowandSprinklerSupervisory)  
NFPA 72 - Auxiliary Fire Alarm Systems (Automatic, Manual, and Waterflow)  
Requires 4XTM  
NFPA 72 - Remote Station Fire Alarm Systems (Automatic, Manual, and Waterflow)  
Requires 4XTM or NOTI•FIRE 911AC DACT or 411UDAC  
Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.  
Before proceeding, the installer should be familiar with the following documents.  
NFPA Standards  
• The above listed documentation  
• NFPA 72 - Automatic Fire Detectors  
• NFPA 72 - Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems  
• NFPA 72 - Testing Procedures for Signaling Systems  
Underwriters Laboratories Documents  
• UL 38 - Manually Actuated Signaling Boxes  
• UL 217 - Smoke Detectors, Single and Multiple Station  
• UL 228 - Door Closers - Holders for Fire Alarm Systems  
• UL 268 - Smoke Detectors for Fire Alarm Systems  
• UL 268A - Smoke Detectors for Duct Applications  
• UL 346 - Waterflow Indicators for Fire Protective Signaling Systems  
• UL 464 - Audible Signaling Appliances  
• UL 521 - Heat Detectors for Fire Protective Signaling Systems  
• UL 864 - Standard for Control Units for Fire Alarm Systems  
• UL 1481 - Power Supplies for Fire Protective Signaling Systems  
• UL 1638 - Visual Signaling Appliances  
• UL 1971 - Signaling Devices for the Hearing Impaired  
• CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems  
• CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm System  
Other  
• NEC Article 300 - Wiring Methods  
• NEC Article 760 - Fire Protective Signaling Systems  
• Applicable Local and State Building Codes  
• Requirements of the Local Authority Having Jurisdiction  
• ADA - Americans with Disabilities Act  
Refer to "Appendix B: Compatible Devices" on page 39 for a listing of all compatible initiating, indicating  
and releasing devices.  
4
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Table of Contents  
NFPA Standards.......................................................................................................... 4  
NFPA Standards .................................................................................................... 4  
Underwriters Laboratories Documents ................................................................. 4  
Other....................................................................................................................... 4  
1. Product Description  
Overview ...................................................................................................................... 7  
Features ....................................................................................................................... 7  
Options ........................................................................................................................ 7  
Circuits......................................................................................................................... 8  
Input Circuits.......................................................................................................... 8  
Output circuits........................................................................................................ 8  
Front Panel Control Switches ................................................................................ 8  
Suplemental Documentation ...................................................................................... 8  
Control Panel............................................................................................................... 9  
DIP Switch Functions................................................................................................ 10  
Options ....................................................................................................................... 10  
Transmitter Module - 4XTM .............................................................................. 10  
Zone Relay Module - 4XZM .............................................................................. 10  
Remote Annunciator - RZA-4X .......................................................................... 11  
LED Interface Module - 4XLM .......................................................................... 11  
Meter Module (Volts-Amps) - 4XMM ............................................................... 11  
Specifications ............................................................................................................. 12  
AC Power............................................................................................................. 12  
Battery (lead acid only)........................................................................................ 12  
Initiating Device Circuits..................................................................................... 12  
Notification Appliance and Releasing Circuits.................................................... 12  
Alarm and Trouble Relays ................................................................................... 12  
Resettable Power.................................................................................................. 12  
Nonresettable Power ............................................................................................ 12  
RMS Regulated Power......................................................................................... 12  
2. Installation  
Cabinet Mounting ..................................................................................................... 13  
Removal of Circuit Board.................................................................................... 13  
Mounting of Cabinet ............................................................................................ 13  
Attaching Conduit................................................................................................ 13  
Reinstallation of Circuit Board ............................................................................ 14  
Installing Optional Voltmeter/Ammeter................................................................. 15  
Power Connections.................................................................................................... 16  
AC Connections ................................................................................................... 16  
Battery (DC) Connections.................................................................................... 16  
Power-limited Wiring Requirements ...................................................................... 17  
Initiating Device Circuits.......................................................................................... 18  
Four-Wire Smoke Detector Connections............................................................. 19  
Output Circuits.......................................................................................................... 20  
Notification Appliance Circuits ........................................................................... 20  
Releasing Circuits ................................................................................................ 21  
Alarm Relay Circuit............................................................................................. 22  
Trouble Relay Circuit........................................................................................... 22  
Powering External Devices....................................................................................... 22  
Optional Modules...................................................................................................... 23  
Overview.............................................................................................................. 23  
Installation - Upper Position ................................................................................ 23  
Installation - Lower Position................................................................................ 24  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Setup and Configuration....................................................................................... 25  
Transmitter Module - 4XTM ........................................................................ 25  
Zone Relay Module - 4XZM ........................................................................ 26  
LED Interface Module - 4XLM.................................................................... 27  
Setting Mode of Operation ....................................................................................... 28  
Basic Program ...................................................................................................... 28  
Discharge Timer................................................................................................... 29  
Power-Up Procedure................................................................................................. 30  
3. System Operation  
System Status LEDs .................................................................................................. 31  
Control Switches........................................................................................................ 32  
Zone Status LEDs...................................................................................................... 32  
Piezo............................................................................................................................ 33  
Supervisory Service................................................................................................... 33  
Zone Disable............................................................................................................... 33  
Last Event Recall....................................................................................................... 34  
Non-Silenceable Service............................................................................................ 34  
Sprinkler Supervisory Tracking .............................................................................. 34  
System Events ............................................................................................................ 34  
Standby Condition................................................................................................ 34  
System Trouble Condition ................................................................................... 34  
Single Zone in Alarm (Cross Zone) Condition .................................................... 35  
Both Zones in Alarm (Cross Zone) Condition..................................................... 35  
Brownout Condition............................................................................................. 35  
Appendix A: Secondary Power Calculations  
Standby Battery Requirements................................................................................ 37  
Calculating the Battery Capacity............................................................................. 38  
Appendix B: Compatible Devices  
Two-wire Smoke Detectors, UL Listed.................................................................... 39  
Four-wire Smoke Detectors, UL Listed................................................................... 40  
FM Approved Releasing Devices ............................................................................. 40  
Notification Appliances, UL Listed.......................................................................... 41  
Door Holders, UL Listed........................................................................................... 43  
24 VDC Relays, UL Listed........................................................................................ 43  
Appendix C: NFPA Standard-Specific Requirements  
Minimum System Requirements.......................................................................... 45  
Additional Requirements...................................................................................... 45  
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)45  
NFPA 72 - Auxiliary Fire Alarm System ..................................................... 45  
NFPA 72 - Remote Station Fire Alarm System............................................ 45  
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC............................. 46  
Universal Digital Alarm Communicator - 411UDAC............................................ 47  
Local Energy Municipal Box.................................................................................... 48  
Remote Station Receiver - RS82-9........................................................................... 49  
Appendix D: Testing & Maintenance  
Testing ........................................................................................................................ 51  
Inspection ............................................................................................................. 51  
Alarm Test............................................................................................................ 51  
Maintenance............................................................................................................... 51  
Troubleshooting......................................................................................................... 51  
6
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Product Description  
Overview  
The PDRP-1001 Series Deluge - Preaction Control System has been designed as a control center for use  
in single- and dual-hazard deluge and preaction applications. The panel is a feature-packed control unit  
suitable to perform detection and control functions associated with the release of water-based fire  
protection systems. The panel is designed for maximum reliability with 100% solid state circuitry and  
isolated relay contacts for outside interfacing and features programmable options to allow on-site  
customization of the unit for various operating configurations.  
An integral standby battery system, with charger, is provided. In case of commercial AC power  
interruption, automatic switchover to the battery system will provide power to the panel for a minimum  
of 24 hours.  
The control panel is supplied complete with backbox, hinged door, control switches, and indicator LEDs.  
The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm)  
conduit knockouts available.  
The PDRP-1001 and PDRP-1001A are 110/120 VAC control panels. The PDRP-1001E is a 220/240 VAC  
control panel.  
Features  
• Microprocessor-controlled  
• 7 amp-hour (AH) to 18 AH battery options, up to 90  
hours standby  
• Alarm and trouble resound  
• Resettable and nonresettable regulated power  
outputs  
• Four Style B/D Initiating Device Circuits  
• Two Style Y/Z Notification Appliance Circuits  
• Two Style Y Release Circuits  
• Extensive transient protection  
• Watchdog timer to supervise microprocessor  
• Output circuits protected against false activations  
• Slide-in zone identification labels  
• General alarm and trouble relays  
• Designed for sprinkler standards NFPA 13, 15 & 16.  
• Disable/enable controls per Initiating Device Circuit  
• Last Event Recall  
• Steel cabinet 14.5” (36.83cm) wide by 16.00”  
(40.64cm) high by 4.75” (12.07cm) deep  
• Battery/Earth fault supervision  
• Dual Hazard operation  
• Municipal Box output  
• Adjustable discharge timer  
• Current protection on all notification circuits  
• RMS regulated output power, 2.25 amps  
Options  
• 4XTM Transmitter Module - Complies with NFPA  
72 Auxiliary and Remote Station Protective  
Signaling systems  
• 4XMM Volt/Amp Meter Module  
• Cross-zone option  
• Dead-front dress panel option (DP-4X)  
(Required for Canadian applications)  
• 4XZM Zone Relay Module for zone/function relays  
• RZA-4X Supervised remote annunciator (requires  
4XLM Interface Module)  
• Trim ring for flush mount between 16 in. (40.64 cm)  
center studs (TR-4XR)  
• 411UDAC or NOTI•FIRE 911AC Digital  
Communicator - Complies with NFPA 72 Central  
Station and Remote Station Protective Signaling  
systems  
Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Product Description  
Circuits  
Circuits  
Input Circuits  
Initiating Device Circuit #1 (Style B/D)  
Initiating Device Circuit #2 (Style B/D)  
Waterflow (Style B/D)  
Supervisory (Style B/D)  
Output circuits  
NAC 1 - Alarm/Waterflow (Style Y/Z)  
NAC 2 - Waterflow/Supervisory (Style Y/Z)  
Releasing Circuit 1 (Style Y)  
Releasing Circuit 2 - Supervisory (Style Y)  
Note: Zone Relay Module (4XZM) tracks these four circuits.  
Front Panel Control Switches  
Switch 1 - Tone Silence  
Switch 2 - Alarm Silence  
Switch 3 - Alarm Activate  
Switch 4 - System Reset  
Suplemental Documentation  
The table below lists document sources containing additional information regarding the PAR-3:  
For information on...  
Refer to...  
Part Number  
Digital Alarm  
Communicator/Transmitters  
NOTI-FIRE 911AC Instruction  
Manual  
74-06200-005  
411UDAC Instruction Manual  
Fire•Lite RS82-9 Instruction Manual  
4X Series Power Meter PID  
51073  
15400  
15396  
Remote Station Receiver  
Voltmeter/Ammeter  
8
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Panel  
1. Product Description  
Control Panel  
Relays  
Notification Appliance Circuits  
Alarm Contacts  
Trouble Contacts  
Style Z (Class A) / Style Y (Class B)  
Releasing Circuits  
Style Y (Class B)  
24VDC  
Regulated Nonresettable  
Regulated Resettable  
RMS-Regulated  
Initiating Device Circuits - #1 to #4  
Style D (Class A) / Style B (Class B)  
Water-  
Super-  
flow  
visory  
IN #4  
OUT#4  
B+ B–  
IN #2  
IN #3  
OUT#1  
OUT#2  
OUT#3  
B+ B–  
IN #1  
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–  
B+ A+ A– B– B+ A+ A– B–  
TB1  
TB4  
TB3  
TB2  
JP1  
GEN  
ALM1  
SUPV 1  
SUPV 2  
GEN  
J1  
J4  
J5  
AC POWER  
ZONE 1  
SYSTEM  
ALARM  
RELEASE  
SUPERVISORY  
SYSTEM  
TROUBLE  
TB5  
OPT1  
WATERFLOW  
CIRCUIT  
TROUBLE  
J2  
AMP  
ALARM  
SILENCED  
SUPERVISORY  
POWER  
TROUBLE  
J9  
J3  
J10  
TONE  
ALARM  
ALARM SYSTEM  
SILENCE SILENCE ACTIVATE RESET  
OPT2  
J7  
J8  
SW1  
PEM2-board.cdr  
SW1 - DIP Switch  
Battery Fail LED  
J4 - J5 - J7 - J8  
Optional Module  
Connectors  
Micro Fail LED  
Ground Fault LED  
Figure 1 Control Panel  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Product Description  
DIP Switch Functions  
DIP Switch Functions  
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode  
of Operation" on page 28.  
#1 & #2  
Mode of  
Determines how NACs and Releasing Circuits respond to an alarm.  
Operation  
#3, #4 & #5  
Timer  
Selects Discharge Timer setting.  
Note: See “Setting Mode of Operation” on page 28 for a more detailed explanation of DIP switch  
functions.  
Options  
Three optional modules are available for use on the control panel. The control panel provides mounting  
slots for two of these optional module boards.  
Transmitter Module - 4XTM  
TB1  
The Transmitter Module provides a supervised output for a Local Energy  
Municipal Box transmitter and alarm and trouble reverse polarity circuits for  
Remote Station Service. Also included is a DISABLE switch and disable  
trouble LED.  
Note: As a jumper option, the alarm reverse polarity circuit will open on trouble if no  
alarm exists.  
TBL  
J1  
SpecificationsforLocalEnergyMunicipalBoxservice(NFPA72Auxiliary  
Fire Alarm System)  
J2  
Supervisory current: 5.0 mA.  
Trip current: 0.35 amps (subtracted from Notification Appliance  
power).  
Coil Voltage: 3.65 VDC.  
Coil resistance: 14.6 ohms.  
Maximum allowable wire resistance between panel and trip coil: 3 ohms.  
Municipal Box wiring can leave the building.  
Specifications for Remote Station Service (NFPA 72 Remote Station Fire Alarm System)  
Maximum load for each circuit: 10 mA.  
Reverse polarity output voltage: 24 VDC.  
Remote Alarm and Remote Trouble wiring can leave the building.  
TB1  
Zone Relay Module - 4XZM  
The Zone Relay module provides Form-C contacts for the following:  
• Relay #1 - Alarm/Alarm Pressure NAC  
• Relay #2 - Alarm Pressure/Auxiliary Supervisory NAC  
• Relay #3 - Release 1  
• Relay #4 - Auxiliary Supervisory NAC/Release 2  
• Relay #5 - System Alarm  
J2  
• Relay #6 - System Trouble  
Note: As a jumper option, the first four relays can be made silenceable.  
DISABLE  
Specifications  
LATCH  
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30  
VAC (resistive).  
10  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
1. Product Description  
Remote Annunciator - RZA-4X  
TheRemoteAnnunciatormountsonastandardsingle-gangbox,andprovides  
LED indication of the same functions as the Zone Relay Module.  
• Alarm/Alarm Pressure (red)  
• Alarm Pressure/Aux Supervisory (red)  
• Releasing Circuit 1 (red)  
SYSTEM TROUBLE  
RE-SOUND  
TONE  
SILENCE  
• Aux Supervisory/Releasing Circuit 2 (red)  
• System Trouble LED (yellow)  
FIRE ALARM ANNUNCIATOR  
A local troublesounder and silence switch are also provided. AllLED wiring  
is supervised for open conditions. Any open condition will cause the System  
Trouble LED to illuminate. Slide-in paper labels permit an easy change of  
information.  
Note: The Remote Annunciator requires the use of an LED Interface Module as described below.  
LED Interface Module - 4XLM  
The LED Interface Module supports the RZA-4X Remote Annunciator  
Module. Annunciator wiring is supervised for open conditions by this module.  
The module mounts to the main board on the J8 option connector.  
Specifications  
Maximum voltage/current, each output: 27.6 V / 8 mA.  
Outputs are power-limited.  
J2  
Meter Module (Volts-Amps) - 4XMM  
10  
20  
The Meter Module provides a voltmeter to measure the voltage across the  
batteries and anammetertomeasurethe chargingcurrenttothebatteries. The  
meters are provided as an assembly that mounts to the lower left-hand corner  
of the cabinet.  
30  
0
DC VOLTS  
0
3
3
DC AMPERES  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Product Description  
Specifications  
Specifications  
AC Power  
PDRP-1001 and PDRP-1001A: 110/120 VAC, 50/60 Hz, 1.2 amps  
PDRP-1001E: 220/240 VAC, 50/60 Hz, 0.6 amps  
Wire size: minimum #14 AWG with 600V insulation  
Battery (lead acid only)  
Maximum Charging Circuit: 27.6V, 1.5 amps  
Maximum Battery Capacity: 18 AH.  
Note: Batteries larger than 12 AH require Notifier BB-17 or other UL-listed external battery cabinet.  
Initiating Device Circuits  
Power-limited circuitry  
Operation: Style B (Class B) or Style D (Class A)  
Normal Operating Voltage: 24 VDC (ripple = 1.0V p-p)  
Alarm current: 15 mA minimum  
Short circuit current: 40 mA maximum  
Maximum detector current in standby: 2 mA (max) per zone  
Maximum loop resistance: 100 ohms  
End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed)  
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.  
Supervisory current: 5 mA (including End-of-Line Resistor)  
Notification Appliance and Releasing Circuits  
Power-limited circuitry  
Maximum allowable voltage drop due to wiring: 2 VDC  
Normal Operating Voltage: 24 VDC  
Total current available to all external devices: 2.25 amps  
Maximum signaling current per circuit: 1.5 amps  
End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed)  
Alarm and Trouble Relays  
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).  
Note: Any power connected to these relay contacts must come from a power-limited supply. Fail-safe operation  
ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power).  
Resettable Power  
Up to 200 mA is available for powering four-wire smoke detectors. Maximum ripple voltage: 1.0 V p-p.  
Nonresettable Power  
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke detector  
power). Maximum ripple voltage: 1.0 V p-p.  
RMS Regulated Power  
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available  
to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.  
12  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Cabinet Mounting  
Carefully unpack the system and check for shipping damage.  
Select a suitable location in a clean, dry, vibration-free environment that is not subject to extreme  
temperatures. Locate the top of the cabinet approximately five feet above the floor with the hinge on the  
left. The panel must be easily accessible for maintenance; the hinged door requires a minimum clearance  
of 14 in. (35.56cm) to open.  
Removal of Circuit Board  
To prevent damage to the printed circuit board it should be removed prior to mounting of cabinet.  
Step Action  
1
2
3
Disconnect the transformer wires from the circuit board at the J1  
connector.  
Remove the four (4) phillips head screws securing circuit board to  
backbox rails.  
Carefully set board aside in a secure place.  
Mounting of Cabinet  
Securely mount the cabinet using the mounting holes provided.  
Step Action  
1
Mark and predrill holes for the top two keyhole mounting screws using the  
dimensions shown in Figure 2 on page 14.  
2
3
4
5
Install two upper screws in the wall with the heads protruding.  
Using the upper keyholes, mount the backbox over the two screws.  
Mark and drill the lower two holes.  
Secure backbox by installing the remaining fasteners and tightening all  
screws.  
6
If required, attach optional Trim Ring (TR-4XR) using the provided  
instructions.  
Attaching Conduit  
Select and remove knockouts according to the number of conduits required.  
Attach conduits to backbox as required.  
Determine the number of conductors required for the devices to be employed. Pull required conductors  
into the box through the knockouts provided.  
Note: All wiring should be in accordance with the National and/or Local codes for fire alarm systems, including  
"Power-limited Wiring Requirements" on page 17.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Cabinet Mounting  
The figure below shows the exterior dimensions and mounting hole locations for the cabinet backbox and  
dimensions of the optional trim ring:  
5.375”  
(13.65cm)  
14.625”  
(37.15cm)  
16.125”  
(40.96cm)  
16.00”  
(40.64cm)  
4.75”  
(12.07cm)  
1.00”  
(2.54cm)  
14.50”  
(36.83cm)  
12.50”  
(31.75cm)  
1.00”  
(2.54cm)  
9.50”  
(24.13cm)  
1.5”  
(3.81cm)  
16.125”  
(40.96cm)  
14.625”  
(37.15cm)  
Figure 2 Cabinet Mounting Dimensions  
Reinstallation of Circuit Board  
Reinstall the printed circuit board as follows:  
Step Action  
1
Position circuit board over stand-offs on backbox rail and secure with four  
(4) phillips screws. Tighten securely.  
2
Connect transformer wires to J1 connector on circuit board.  
14  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Optional Voltmeter/Ammeter  
2. Installation  
Installing Optional Voltmeter/Ammeter  
To monitor battery voltage and battery charging current, a 4XMM Meter Module is required. To install  
the power meter module follow the steps below:  
Step Action  
1
2
Cut the jumper wire labeled “AMP”.  
Secure the module to the backbox with the hardware provided. Refer to  
Product Installation Drawing (PID) for detailed instructions.  
3
4
Connect meter cable P2 to connector J2 on the main circuit board.  
Connect meter cable P3 to connector J3 on the main circuit board.  
The figure below shows the mounting location and connections for the Voltmeter/Ammeter.  
TB5  
‘AMP’ Jumper  
J2  
AMP  
J9  
J3  
10  
20  
30  
0
DC VOLTS  
0
3
3
DC AMPERES  
Figure 3 Mounting and Connecting the Meters  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Power Connections  
Power Connections  
WARNING: Do not apply any type power to this control panel until all connections have been  
made and verified.  
!
AC Connections  
Disconnect (open) the circuit breaker in the AC main breaker panel and tag it “Out of Service”.  
Note: Refer to "Power-Up Procedure" on page 30 before closing AC breaker.  
Primary power required for the PDRP-1001 and PDRP-1001A control panels is 110/120 VAC, 50/60 Hz,  
1.2 amps and for the PDRP-1001E is 220/240 VAC, 50/60 Hz, 0.6 amps.  
OvercurrentprotectionforthiscircuitmustcomplywithArticle760oftheNationalElectricalCode(NEC)  
and/or local codes. Use #14 AWG (2.00 mm2) or larger wire with 600V insulation rating.  
A separately fused and protected power connection to the panel should be supplied to prevent voltage  
fluctuation and interruption of power.  
Ground  
Neutral  
TB5  
Hot  
J2  
AMP  
J9  
J3  
Figure 4 AC Power Connections  
Battery (DC) Connections  
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and  
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with  
water for 15 minutes and seek immediate medical attention.  
!
CAUTION: Do NOT connect the battery interconnect wire at this time. Make this connection AFTER  
initial system primary power connection.  
!
Place batteries into bottom of cabinet as shown below. See "Appendix A: Secondary Power Calculations"  
on page 37 for calculation of correct battery rating.  
Note: Batteries are shipped separately and should be mounted only after the cabinet has been installed, the conduit  
connected, and all wiring pulled, tested, and made ready to be terminated.  
Continued on the next page...  
16  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power-limited Wiring Requirements  
2. Installation  
Observe polarity when connecting the batteries. Connect the battery cable (p/n 75203 or 75202, depending  
on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided.  
Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries.  
Do NOT connect battery interconnect wire at this time.  
TB5  
J2  
AMP  
J9  
J3  
Figure 5 Battery Installation and Connection  
Power-limited Wiring Requirements  
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-  
limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit  
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass  
through separate knockouts and/or conduits.  
Power-limited  
Circuits  
Nonpower-limited  
Circuits  
Power-limited Circuits  
OUT#
+ B
ALARM  
IN #1  
IN #2  
IN #3  
IN #4  
OUT#1  
OUT#2  
OUT#3  
B+ B–  
BA+ AB B+ A+ AB
NO NC  
C
B+ A+ AB BA+ AB B+ A+ AB BA+ AB–  
TB1  
TB4  
TB3  
TB2  
JP1  
GEN  
ALM1  
SUPV  
1
TB1  
SUPR  
2
GEN  
ALM
J1  
TBL  
AC POWER  
J1  
J2  
ZONE  
1
2
3
4
SYSTEM  
ALARM  
ALARM TEST  
ZONE  
SUPERVISORY  
SYSTEM  
TROUBLE  
TB5  
TB1  
ZONE  
ZONE  
CIRCUIT  
TROUBLE  
Power-limited  
Circuits  
J2  
AMP  
ALARM  
SILENCED  
POWER  
TROUBLE  
J9  
J3  
TONE ALARM SYSTEM  
SILENCE SILENCE ACTIVATE RESET  
ALARM  
Nonpower-limited  
Circuits  
J2  
DISABLE  
LATCH  
SW1  
AC Power  
Figure 6 Power-limited Wiring Requirements  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Initiating Device Circuits  
Initiating Device Circuits  
The control panel provides four (4) Initiating Device Circuits (#1, #2, #3 and #4) and they may be  
configured as either Style D (Class A) or Style B (Class B).  
Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and  
Waterflow alarm devices.  
Note: Refer to the "Appendix B: Compatible Devices" on page 39 for compatible devices.  
• Wire all alarm initiating devices sequentially for proper supervision.  
• Observe polarity when connecting polarized devices.  
• All circuits are supervised and power-limited.  
• Leave dummy load resistor (provided) on all unused circuits.  
Style D (Class A)  
Initiating Device  
Circuit  
Heat  
Detector  
Style B (Class B)  
Supervisory  
Circuit  
Style B (Class B)  
Initiating Device  
Circuit  
Style B (Class B)  
Initiating Device  
Circuit  
4.7K, 1/2-Watt ELR  
PN 71252  
(UL listed)  
Two-wire  
Smoke  
Detector  
Normally Open  
Tamper or  
Pressure  
Normally Open  
Waterflow  
Devices  
Switches  
Manual  
Pull Station  
Note: Silk screen printing on circuit board moved to bottom for clarity  
Figure 7 Initiating Device Circuits  
18  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Initiating Device Circuits  
2. Installation  
Four-Wire Smoke Detector Connections  
A maximum of 200mA is available from the 24VDC Resettable Power circuit on TB1 (+24VR terminals).  
Any power that is drawn from the 24VDC Nonresettable Power on TB2 (+24VNR terminal) must be  
subtracted from available resettable power. See "Specifications" on page 12 and "Powering External  
Devices" on page 22.  
Note: Refer to the "Appendix B: Compatible Devices" on page 39 for suitable 4-wire smoke detectors.  
Notes on Style D (Class A) and Style B (Class B) field wiring:  
1. The Power Supervision Relay coil leads must be connected to the last detector base 24V screw  
terminals.  
2. Calculation of the maximum allowable resistance in the 24VDC resettable power wiring:  
(20.6 - Vom)  
Rmax =  
(N x Is) + (Na x Ia) + (Ir)  
Where:  
Rmax = maximum resistance of the 24 VDC wires  
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts  
N = total number of detectors on the 24 VDC supply circuit  
Is = detector current in standby  
Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm  
Ia = detector current in alarm  
Ir = end-of-line relay current  
4.7K, 1/2-Watt ELR  
PN 71252 (UL listed)  
+
+
+
+
Power  
Supervision  
Relay  
24 VDC Four-wire  
Smoke Detectors  
(A77-716B)  
TB4  
TB1  
IN #1  
IN  
B+ A+ A– B–  
B+ A+  
Control Panel  
Power Circuit  
Style B  
Initiating Device Circuit  
Figure 8 Typical Connection for Four-Wire Smoke Detectors  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Output Circuits  
Output Circuits  
Notification Appliance Circuits  
The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits,  
which are supervised and power-limited.  
Each circuit is capable of 1.5 amps of current. Total current drawn from both NACs and both Releasing  
Circuits (see "Releasing Circuits" on page 21) cannot exceed 2.25 amps.  
Note: Refer to the "Appendix B: Compatible Devices" on page 39 for suitable devices.  
• For DIP switch configuration, see "Setting Mode of Operation" on page 28.  
• For non-silenceable service on NAC#1, see "Non-Silenceable Service" on page 34.  
• Unused circuits must be connected with a dummy load as shown.  
Style Y  
(Class B)  
4.7K, 1/2-Watt ELR  
PN 71252 (UL listed)  
Style Z  
(Class A)  
Polarized  
Bell  
Polarized  
Strobe  
Unused Style Y Circuit  
4.7K, 1/4-Watt ELR  
PN 71252 (UL listed)  
Polarized  
Horn  
TB2  
Figure 9 Notification Appliance Circuits  
20  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Output Circuits  
2. Installation  
Releasing Circuits  
CAUTION: To prevent accidential discharge, connect releasing devices after initial panel tests are  
completed.  
!
The control panel provides two Style Y (Class B) Releasing Circuits, which are nonpower-limited.  
Note: All wiring must follow the requirements as specified under "Power-limited Wiring Requirements" on page 17.  
Each circuit is capable of 1.5 amps of current. Total current drawn from both Releasing Circuits and both  
NACs (see "Notification Appliance Circuits" on page 20) cannot exceed 2.25 amps.  
• UL listed and FM approved releasing devices must be used.  
• Unused circuits must be connected with a dummy load as shown.  
Releasing Circuits  
TB2  
Canadian Applications  
Unused Releasing Circuits  
4.7K, 1/4-Watt ELR  
REL-4.7K  
PN 71252 (UL listed)  
TB2  
Figure 10 Releasing Circuits  
Wiring must be configured to maintain a minimum voltage of 20.4 VDC on releasing Circuits. Calculation  
of maximum allowable resistance:  
20.6 VDC – 20.4 VDC  
Rmax =  
Is  
Where:  
Rmax = maximum allowable resistance of wiring  
Is = Solenoid current  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Powering External Devices  
Alarm Relay Circuit  
One Form-C dry contact alarm relay is provided in the basic panel for controlling supplementary devices.  
Contacts are rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and are non-silenceable when  
an alarm occurs.  
Trouble Relay Circuit  
One Form-C dry contact trouble relay is provided in the basic panel for controlling supplementary devices.  
It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and will restore to normal when the trouble  
condition is cleared.  
Note: Power connected to these relay contacts must come from a power-limited supply. Power may be obtained from  
TB1 Terminals 24VU or 24VR and TB2 Terminals 24VNR, or a UL-listed power-limited power supply.  
TB3  
Figure 11 Schematic Representation of Alarm/Trouble Coils & Contacts  
Powering External Devices  
CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources  
!
of power before servicing. The panel and associated equipment may be damaged by removing and/or  
inserting cards, modules, or interconnecting cables while this unit is energized.  
DC power connections are available from TB1 and TB2 on the control panel as shown below:  
TB2  
TB1  
Nonresettable Power -  
RMS-Regulated Power -  
24 VDC filtered, nonresettable power  
can be drawn from these terminals.  
The combined current draws from the  
Resettable and Nonresettable outputs  
cannot exceed 200 mA.  
24 VDC power for inductive-type  
devices such as door holders can  
be connected to these terminals.  
This output is not suitable for  
powering devices requiring  
filtered DC power.  
Resettable Power -  
24 VDC filtered, resettable power for four-wire smoke  
detectors can be obtained from these terminals.  
The combined current draws from the Resettable and  
Nonresettable outputs cannot exceed 200 mA.  
Figure 12 Power Terminals  
22  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Modules  
2. Installation  
Optional Modules  
Overview  
The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules  
are available for the panel and they can be used in any combination, including duplicate modules. The  
corresponding option jumper must be cut before installation of an optional module, to enable module  
supervision.  
• The 4XZM Zone Relay and the 4XTM Transmitter Modules can be installed in either position.  
• The 4XLM Interface Module must be installed in the lower position only.  
Installation - Upper Position  
To install either the 4XZM or 4XTM module in the upper position follow these instructions:  
Step Action  
1
2
Cut jumper ‘OPT1’ on main circuit board.  
Insert the two stand-offs into the holes located on the right-side edge of the  
main board. Secure with nuts and tighten securely.  
3
Align the pins of J5 (and J4) connectors on the main board with the holes on  
the underside of the J2 (and J1) connector on the optional board. Carefully  
press down on the optional board until the pins are through the connectors  
and it rests on the stand-offs.  
4
5
Secure optional board to stand-offs with screws. Tighten securely.  
Affix the terminal identification label (provided with the module) on the  
back surface of the backbox, aligning it with the terminals on the module.  
IN #2  
IN #3  
IN #4  
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–  
TB4  
TB1  
Install Stand-offs here  
J2  
J4  
J5  
DISABLE  
LATCH  
OPT1  
OPT1 - Cut prior to  
installation of module  
J10  
OPT2  
J7  
J8  
Figure 13 Module Installation - Upper Position  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Optional Modules  
Installation - Lower Position  
To install either the 4XTM, 4XZM or 4XLM module in the lower position follow these instructions:  
Step Action  
1
2
Cut jumper ‘OPT2’ on main circuit board.  
Remove the lower-right screw securing the main board to the lower rail.  
Replace with a stand-off and tighten securely.  
3
4
Insert one stand-off into the other hole located on the right-side edge of the  
main board. Secure with nut and tighten securely.  
Align the pins of J8 (and J7) connectors on the main board with the holes on  
the underside of the J2 (and J1) connector on the optional board. Carefully  
press down on the optional board until the pins are through the connectors  
and it rests on the stand-offs.  
5
6
Secure optional board to stand-offs with screws. Tighten securely.  
Affix the terminal identification label (provided with the module) on the  
back surface of the backbox, aligning it with the terminals on the module.  
IN #2  
IN #3  
IN #4  
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–  
TB4  
Install Stand-offs here  
J4  
J5  
OPT1  
OPT2 - Cut prior to  
installation of module  
J10  
J2  
OPT2  
J7  
J8  
Figure 14 Module Installation - Lower Position  
24  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Modules  
2. Installation  
Setup and Configuration  
Transmitter Module - 4XTM  
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module  
as shown below. Polarities shown in activated positions.  
Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.  
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.  
PushingtheDisconnectSwitchdownwillpreventunwantedactivationoftheMunicipalBoxduringtesting  
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is  
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the  
Municipal Box.  
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.  
The wiring of this module must follow the requirements as specified under "Power-limited Wiring  
Requirements" on page 17.  
TB1  
+
Remote Alarm (Power-limited)  
+
Remote Trouble (Power-limited)  
No Connection  
+
Municipal Box (Nonpower-limited)  
TBL Jumper  
TBL  
J1  
Disconnect LED  
Disconnect Switch  
J2  
Figure 15 4XTM Configuration  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Optional Modules  
Zone Relay Module - 4XZM  
Note: The PAR-3 includes one (1) Zone Relay Module (4XZM).  
Relay #1 through #4 on this module will activate with outputs #1 through #4.  
For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the  
relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.  
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,  
located on the door of the control panel.  
TB1  
J2  
DISABLE  
LATCH  
“Latch” Jumper  
Disable Switch  
Figure 16 Wiring the Zone Relay Module  
The wiring of this module must follow the requirements specified under "Power-limited Wiring  
Requirements" on page 17.  
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of  
dry contacts to maintain the required separation between circuit types.  
• If this module is used to drive both nonpower-limited and power-limited relays that are next to each  
other, refer to the figure below which shows the one allowable arrangement.  
Power-Limited  
Circuit  
No Connection  
Nonpower-Limited  
Circuit  
Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits  
26  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Modules  
2. Installation  
LED Interface Module - 4XLM  
Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA-  
4X Remote Annunciator.  
Make wiring connections with system power off.  
Maximum wire impedance is 50 ohm per wiring connection.  
The wiring of this module must follow the requirements as specified under "Power-limited Wiring  
Requirements" on page 17.  
+24V  
Out #1  
Out #2  
Out #3  
Out #4  
Sysyem Trouble  
Sound  
Resound  
J2  
Connect to corresponding  
terminals of the RZA-4X  
Remote Annunciator.  
Single-gang  
Box  
SYSTEM TROUBLE  
RE-SOUND  
TONE  
SILENCE  
FIRE ALARM ANNUNCIATOR  
Side View  
Front View  
Figure 18 Connection of 4XLM to RZA-4X  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Setting Mode of Operation  
Setting Mode of Operation  
Select operating mode by setting the SW1 DIP switches as described below.  
After any changes are made to the configuration of the switches, the panel must be reset.  
For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 34.  
SW1  
Basic Programming  
Switch 1: Cross Zone  
Switch 2: Dual Hazard  
Not Used  
Discharge Timer  
Switch 3: Discharge Timer  
Switch 4: Discharge Timer  
Switch 5: Discharge Timer  
Figure 19 DIP Switch Settings  
Basic Program  
Select the desired mode of operation and set DIP Switches 1 and 2 per the appropriate column.  
Mode 1  
Two Zone  
Single Hazard  
Mode 2  
Cross Zone  
Single Hazard  
Mode 3  
Combined Release  
Dual Hazard  
Mode 4  
Split Release  
Dual Hazard  
Switch 1  
Switch 2  
OFF  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
Output 1 & 3 -  
Activated by an  
alarm on either IDC  
1 or 2.  
Output 1 -  
Output 1 -  
Output 1 -  
Activated by an  
alarm on either IDC  
1 or 2.  
Activated by an  
alarm on either IDC  
1 or 2 or a waterflow  
alarm on IDC 3.  
Output 2 -  
Activated by an  
alarm on either IDC  
1 or 2 or a waterflow  
alarm on IDC 3.  
Output 2 -  
Output 2 -  
Output 2 -  
Activated by a  
waterflow alarm on  
IDC 3.  
Activated by a  
waterflow alarm on  
IDC 3.  
Activated by a  
supervisorycondition supervisorycondition  
Activated by a  
Output 4 -  
Output 3 -  
on IDC 4.  
on IDC 4.  
Activated by a  
supervisorycondition on both IDC 1 and 2.  
on IDC 4.  
Activated by alarms  
Output 3 & 4 -  
Activated by an  
alarm on either IDC  
1 or 2.  
Output 3 -  
Activated by an  
alarm on IDC 1.  
Output 4 -  
Activated by an  
alarm on IDC 2.  
Output 4 -  
Activated by a  
supervisorycondition  
on IDC 4.  
Note: Output 1 and 2 refer to Notification Appliance Circuits; Output 3 and 4 refer to Releasing Circuits.  
28  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setting Mode of Operation  
2. Installation  
Discharge Timer  
Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly.  
• For NFPA 13 and 15 applications timer must be set to “Disabled”.  
• For NFPA 16 applications timer may be set to “10 Minutes” or “15 Minutes”.  
Disabled  
OFF  
10 Minutes  
ON  
15 Minutes  
ON  
Switch #3  
Switch #4  
Switch #5  
OFF  
ON  
ON  
OFF  
OFF  
ON  
Note: Timer will always start at Zone 2 normal to alarm transition. Upon timeout, corresponding release circuits will  
shut off.  
Note: Zone 1 will always override timer shutoff (except for Mode #4 - Split Release).  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Power-Up Procedure  
Power-Up Procedure  
WARNING: Prior to energizing this panel, notify all personnel and authorities, including any  
personnel who may be working on, around, or near this unit.  
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and  
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with  
water for 15 minutes and seek immediate medical attention.  
!
CAUTION: Observe polarity of batteries. Improper connection will cause damage and VOID  
WARRANTY.  
!
Follow these steps to power-up the FACP:  
1. Conduct Visual Inspection. A careful visual inspection should be made before applying power to  
the system. See “Inspection” on page 51.  
2. Notification. Notify personnel who may be working with the AC power circuits before removing  
the “Out of Service” tag.  
3. Apply Primary Power. Switch the circuit breaker to the ‘closed’ position, providing power to the  
circuit.  
• The green AC power LED will illuminate.  
• The Trouble LED will illuminate until battery power is applied.  
4. Connect Secondary Power. Connect battery interconnect wire as shown below.  
• The trouble LED will clear. If the trouble light does not clear, refer to "Troubleshooting Table" on  
page 52.  
Battery Interconnect Wire  
Figure 20 Battery Connections  
30  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. System Operation  
System Status LEDs  
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged  
(TONE or ALARM SILENCE), at which point the LED will illuminate steadily.  
AC POWER  
ZONE 1  
SYSTEM  
ALARM  
RELEASE  
ZONE 2  
System  
SUPERVISORY  
Status  
LEDs  
SYSTEM  
TROUBLE  
WATERFLOW  
CIRCUIT  
TROUBLE  
ALARM  
SILENCED  
SUPERVISORY  
POWER  
TROUBLE  
TONE  
ALARM  
ALARM SYSTEM  
SILENCE SILENCE ACTIVATE RESET  
MICRO  
FAIL  
BATT EARTH  
Figure 21 System Status LEDs  
AC Power - Green LED that illuminates steadily to indicate presence of AC power.  
System Alarm - Red LED that flashes when an alarm occurs.  
Release - RedLED thatilluminatessteadily when release occurs. AftertheDischarge Timer has expired,  
the LED will flash.  
Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch)  
on IDC 4.  
System Trouble - Yellow LED that flashes for any trouble condition, including those associated with  
optional boards.  
Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits (notification and  
releasing).  
Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been  
pushed after an alarm.  
Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions.  
The following LEDs are located below the main panel and are visible only when the panel door is open.  
Battery Fail (BATT) - Yellow LED that illuminates steadily on motherboard when battery is low or not  
detected.  
Ground Fault (EARTH) - Yellow LED that illuminates steadily on motherboard during a ground fault  
condition.  
Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor  
failure.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. System Operation  
Control Switches  
Control Switches  
TONE  
ALARM  
ALARM SYSTEM  
SILENCE SILENCE ACTIVATE RESET  
Figure 22 Control Panel Switches  
Tone Silence - Pressing this switch acknowledges alarms, troubles and supervisories. The panel has  
alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate  
steadily on TONE SILENCE and the piezo turns off. A second trouble will resound the piezo. Trouble  
conditions are self-restoring. Alarms latch and require pressing SYSTEM RESET to clear. Unless the unit  
is set for non-latching supervisory service, supervisories latch and require pressing SYSTEM RESET to  
clear. The piezo has three tones for different conditions (see "Piezo" on page 33).  
Alarm Silence - Pressing this switch acknowledges for alarms and supervisories. This switch will  
silence the local piezo, change any flashing alarm LEDsto steady, and turn off the notification circuits (not  
the Releasing Circuits). The “Alarm Silenced” LED will illuminate. Alarm silence is a latching function  
and requires pressing SYSTEM RESET to clear.  
Note: Releasing Circuits will turn off only if Discharge timer criteria is satisfied (see "Setting Mode of Operation" on  
page 28).  
Alarm Activate - This switch may be used to activate Notification Appliance Circuits (NACs). It also  
activates the System Alarm Relay. This is a latching function. Pressing ALARM SILENCE silences the  
NACs and System Alarm Relay, and lights the Alarm Silenced LED. Pressing SYSTEM RESET returns  
the system to normal.  
System Reset - This switch breaks power to all initiating circuits, four-wire smoke detector power and  
optional boards and will clear any activated output circuits. If any alarm or trouble still exists after reset,  
they will reactivate the panel. Holding SYSTEM RESET down will perform a LAMP TEST function and  
will activate the piezo sounder.  
Zone Status LEDs  
The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM  
SILENCE), at which point the LED(s) will illuminate steadily.  
ZONE 1  
Alarm LED  
ZONE 2  
Trouble LED  
WATERFLOW  
Not Used  
SUPERVISORY  
Figure 23 Zone Status LEDs  
32  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Piezo  
3. System Operation  
Piezo  
The piezo (local buzzer) generates different tone patterns for different event conditions:  
Alarm - Generates a steady tone, no pulse.  
Trouble - Pulses one second on, one second off. Repeats 30 pulses per minute.  
Supervisory - Pulses one-half second on, one-half second off. Repeats 60 pulses per minute.  
Supervisory Service  
Initiating Device Circuit #4 is always used for monitoring supervisory devices (such as valve tamper  
switches). A short circuit on this IDC (activation of a N.O. contact) will cause the Supervisory LED and  
the Zone 4 (Supervisory) trouble LED to flash. The piezo will sound one-half-second on, one-half-second  
off. PressingTONESILENCE willsilence the piezoandcause the Supervisory LED to illuminatesteadily,  
but the Zone 4 (Supervisory) trouble LED will continue to flash. Supervisory signals latch and require  
SYSTEMRESETtoclear(unlessunitisprogrammedfornon-latchingoperation).TheALARMSILENCE  
switch will silence the piezo, causing the Supervisory LED to illuminate steadily and turn off the  
Supervisory Notification Circuit. An open circuit on Zone 4 (Supervisory) will be reported as a trouble.  
Note: The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching  
operation is the default setting. Canadian regulations require latching operation; for programming instructions, see  
"Sprinkler Supervisory Tracking" on page 34.  
Zone Disable  
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the piezo  
or any output circuit. If both power sources are removed from the system, all zones will be re-enabled upon  
restoration of power. Disable status will be lost.  
The Zone Disable routine makes use of the four panel  
switches as follows:  
TONE  
ALARM  
ALARM SYSTEM  
SILENCE SILENCE ACTIVATE RESET  
1. Press and hold in the TONE SILENCE switch.  
2. With the TONE SILENCE switch held in, press  
(in sequence) the ALARM SILENCE switch, the  
ALARM ACTIVATE switch, and then the  
SYSTEM RESET switch.  
Press  
&
Hold  
Press ---> Press ---> Press  
3. The Zone 1 Alarm LED will flash.  
4. To disable Zone 1, press the SYSTEM RESET switch. The Zone 1 yellow LED will light to show  
that the zone is disabled.  
Note: The SYSTEM RESET switch toggles disable status for the selected zone.  
5. To select the next zone, press the ALARM SILENCE switch.  
6. To select the previous zone, press the ALARM ACTIVATE switch.  
7. When disable selections are complete, release the TONE SILENCE switch.  
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. System Operation  
Last Event Recall  
Last Event Recall  
Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use  
of the four panel switches as follows:  
1. Press and hold in the TONE SILENCE switch.  
2. With the TONE SILENCE switch held in, press (in sequence) the SYSTEM RESET switch, the  
ALARM ACTIVATE switch, and then the ALARM SILENCE switch.  
3. LEDs will light to indicate the last event recorded in the panel’s buffer.  
4. Release the TONE SILENCE switch to return to normal operation.  
To clear the Last Event buffer, press SYSTEM RESET twice.  
Non-Silenceable Service  
Notification Appliance Circuit #1 can be programmed as non-silenceable by following these steps:  
1. Press and hold in the TONE SILENCE switch.  
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then  
the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.  
3. Release the TONE SILENCE switch.  
Note: If both primary and secondary power sources are removed from the system, these settings will be lost. When  
power is restored, Notification Appliance Circuit #1 will default to silenceable operation.  
Sprinkler Supervisory Tracking  
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation;  
latching operation is the default setting. Canadian regulations require latching operation.  
1. Press and hold in the TONE SILENCE switch.  
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then  
the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.  
3. Release the TONE SILENCE switch.  
Note: If both primary and secondary power sources are removed from the system, this setting will be lost. When  
power is restored, supervisory will default to latching operation.  
System Events  
Standby Condition  
Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.  
System Trouble Condition  
Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The  
Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off,  
and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will  
remain in the trouble state until the trouble condition has been cleared and the panel reset.  
34  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Events  
3. System Operation  
Single Zone in Alarm (Cross Zone) Condition  
Upon actuation of a single-zone initiating device, a red alarm LED will illuminate to indicate whether  
Zone 1 or Zone 2 is in alarm.  
In addition to the LED, a single-zone alarm will activate the Alarm Relay; the piezo and NAC #1 will start  
sounding. In alarm condition, the piezo will generate a steady tone. The piezo can be silenced by pressing  
the trouble silence switch. If the fire is extinguished before a second zone alarm is activated, return the  
system to normal standby condition by pressing the reset switch inside the panel and holding it for three  
(3) seconds.  
Both Zones in Alarm (Cross Zone) Condition  
When the first alarm occurs, the panel will function as described above.  
Upon the occurrence of a second alarm, the second alarm LED will illuminate, NAC #2 will energize, and  
the solenoid valve(s) will energize to activate releasing devices.  
Brownout Condition  
The total power being provided to the system’s power supply should not exceed the current draw during  
fully loaded panel operation. Brownout circuitry annunciates degradation of the incoming AC voltage  
supply. Abrownout condition isannunciated when theACpowerdecreases. When thebrownoutthreshold  
is reached, the system reacts as if AC power is totally lost:  
• Battery backup begins supplying power to operate the control panel  
• General Trouble Relay contact transfers  
• Green AC Power LED turns off  
Yellow System Trouble LED illuminates  
• The piezo will sound one second on, one second off, and repeat until the Trouble is cleared.  
When the AC voltage returns or increases above the brownout threshold, the green AC Power LED will  
illuminate. The power supply circuitry will return to primary power functions and begin to recharge the  
backup battery supply.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. System Operation  
System Events  
Notes  
36  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A: Secondary Power Calculations  
Standby Battery Requirements  
The Standby Battery Current obtained in the table below represents the amount of current that must be  
supplied by the secondary power source (batteries) to sustain control panel operation for one hour.  
Note: The control panel will support the installation of one or two optional modules, including two of the same type of  
module. Only one 4XLM can be included in this count.  
# of  
Devices  
Current  
(amps)  
Total Current  
(amps)  
Device Type  
Main Circuit Board  
1
X
X
0.088  
0.008  
=
=
0.088  
4XZM  
Zone Relay Module  
[
[
]
]
X
0.011  
=
4XTM  
Transmitter Module  
• Reverse Polarity  
Alarm output  
[
[
[
]
]
]
X
X
X
X
X
X
X
X
0.005  
0.005  
=
=
=
=
=
=
=
=
• Reverse Polarity  
Trouble output  
RZA-4X/4XLM  
Remote Annunciator  
0.019  
0.001  
1
(1 max)  
4XMM  
Meter Module  
[
[
[
[
[
]
]
]
]
]
2-wire  
Detector Heads  
[
[
]
1
4-wire  
Detector Heads  
]
2
[
]
End-of-line Relays  
Current Draw from  
[
]
3
TB2 (nonalarm)  
Standby Battery Current  
=
amps  
1. Refer to the "Appendix B: Compatible Devices" on page 39 for smoke detector standby current.  
2. Must use compatible listed Power Supervision Relay.  
3. The total standby current must include both the resettable (TB1 - +24VR terminals) and  
nonresettable (TB2 - +24VNR terminals) power. Caution must be taken to ensure that current  
drawn from these outputs during alarm does not exceed maximum ratings specified.  
Table 1 Standby Battery Current  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A: Secondary Power Calculations  
Calculating the Battery Capacity  
Calculating the Battery Capacity  
Use this table to determine the battery capacity required by the system.  
Standby Battery Current  
(from Table 1)  
Required Standby Time in Hours  
1
2
3
Standby  
Amp Hours  
(typically 24 , 60 or 90 hours)  
] hrs  
[
] amps  
X
=
[
Enter:  
4
0.25 for 5 minutes in alarm, or  
0.50 for 10 minutes in alarm  
Alarm  
Amp Hours  
Total Standby and Alarm Load  
Multiply by derating factor  
Battery size required in AH  
+
X
=
1.2  
1. NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24 hours of standby time.  
2. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby time.  
3. Factory Mutual Systems require 90 hours of standby for preaction and deluge sprinkler systems.  
4. Alarm AH assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 AH) or for 10 minutes (0.5AH).  
Table 2 Amp Hour Calculations  
The battery charger in this panel will charge a maximum of 18 AH of batteries within 48 hours (7 AH  
minimum). Batteries larger than 12 AH will require a UL-listed battery cabinet (e.g. BB-17).  
Select a battery with an equal or greater AH rating than the value obtained in the table above.  
Note: Batteries must be lead-acid type.  
38  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B: Compatible Devices  
Two-wire Smoke Detectors, UL Listed  
Use the two-wire detectors listed below.  
Standby  
Identifier Current  
(mA)  
Detector  
Identifier  
Model  
Base  
Model  
Detectors  
per Zone  
Type  
System Sensor 1400  
System Sensor 1451  
A
A
Ionization  
Ionization  
n/a  
n/a  
A
0.10  
0.12  
20  
B401/B401B/  
B406B  
15/15/1  
System Sensor 1851DH  
System Sensor 2400  
A
A
A
Ionization  
DH1851DC  
A
0.12  
0.12  
0.12  
15  
15  
15  
Photoelectric  
n/a  
n/a  
n/a  
n/a  
System Sensor 2400AIT  
Photo/  
Isolated  
Thermal/Horn  
System Sensor 2400AT  
System Sensor 2400TH  
System Sensor 2451  
A
A
A
A
Photo/  
Thermal/Horn  
n/a  
n/a  
n/a  
n/a  
A
0.12  
0.12  
0.12  
0.12  
15  
Photo/  
Thermal  
15  
Photoelectric B401/B401B/  
B406B  
15/15/1  
15/15/1  
System Sensor 2451TH  
Photo/  
Thermal  
B401/B401B/  
B406B  
A
System Sensor 2851DH  
System Sensor 1451DH  
System Sensor 2451  
A
A
A
A
Photoelectric DH2851DC  
A
A
0.12  
0.12  
0.12  
0.12  
15  
15  
15  
15  
Ionization  
DH400  
DH400  
n/a  
Photoelectric  
A
System Sensor 2300T  
Photo/  
n/a  
Thermal  
System Sensor 1800  
System Sensor 1851B  
System Sensor 1851B  
System Sensor 2800  
System Sensor 2800TH  
A
A
A
A
A
Ionization  
Ionization  
n/a  
B101B  
B107B  
n/a  
n/a  
A
0.12  
0.12  
0.12  
0.12  
0.12  
n/a  
n/a  
n/a  
n/a  
n/a  
Ionization  
A
Photoelectric  
n/a  
n/a  
Photo/  
n/a  
Thermal  
System Sensor 2851B  
System Sensor 2851B  
System Sensor 2851BTH  
A
A
A
Photoelectric  
Photoelectric  
B101B  
B107B  
B101B  
A
A
A
0.12  
0.12  
0.12  
n/a  
n/a  
n/a  
Photo/  
Thermal  
System Sensor 2851BTH  
System Sensor 1151  
A
A
Photo/  
Thermal  
B107B  
A
A
0.12  
0.12  
n/a  
Ionization  
B401/  
B110LP/  
B116LP  
15/15/1  
System Sensor 2151  
A
Photoelectric  
B401/  
B110LP/  
B116LP  
A
0.12  
15/15/1  
Table 3 Two-wire Smoke Detectors  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B: Compatible Devices  
Four-wire Smoke Detectors, UL Listed  
Four-wire Smoke Detectors, UL Listed  
Use the four-wire detectors listed below.  
Max Standby Max Alarm  
Current (mA) Current (mA)  
Detector/Base  
Type  
System Sensor 2424  
Photoelectric  
Photoelectric  
Photoelectric  
Photoelectric  
Ionization  
0.10  
0.10  
41  
41  
System Sensor 2424TH  
System Sensor 2451  
0.10  
39  
System Sensor 2451TH w/B402 Base  
System Sensor 1424  
0.10  
39  
0.10  
41  
System Sensor 1451 w/B402 Base  
System Sensor 2412  
Ionization  
0.10  
39  
Photoelectric  
Photoelectric  
Photoelectric  
Photoelectric  
Base  
0.12  
77  
System Sensor 2412AT  
System Sensor 2412TH  
System Sensor 2312/24TB  
System Sensor B112LP  
System Sensor B114LP  
System Sensor B404B  
0.12  
58  
0.12  
77  
0.12  
50  
See Note  
See Note  
See Note  
10  
39  
Base  
75  
Base  
See Note  
28.4  
95  
System Sensor 6424  
Projected Beam  
Ionization Duct  
Photoelectric Duct  
Ionization  
System Sensor DH400ACDCI  
System Sensor DH400ACDCP  
System Sensor 1112/24  
System Sensor 2112/24  
System Sensor 2112/24B  
System Sensor 2112/24T  
25  
25  
95  
0.05  
50  
Photoelectric  
Photoelectric  
0.05  
50  
0.05  
65  
Photoelectric w/135°  
Thermal  
0.05  
50  
System Sensor 2112/24TSRB  
Photoelectric w/135°  
15  
45  
Thermal Supervisory Relay  
Note: Contact manufacturer for currents.  
Table 4 Four-wire Smoke Detectors  
FM Approved Releasing Devices  
(System Sensor’s PDRP-1001/PDRP-1001A/PDRP-1001E)  
Note: Refer to the FM approval guide for automatic water control valves which are compatible with solenoids listed.  
Manufacturer  
Model  
Voltage  
Watts Amps  
NPS  
Orfice  
Solenoid Group A  
Skinner  
LV2LBX25  
24 VDC  
11  
458 mA  
1/2”  
5/8”  
Solenoid Group B  
These valves are interchangeable  
ASCO  
T8210A107  
R8210A107  
8210A107  
24 VDC  
24 VDC  
24 VDC  
16.8  
16.8  
16.8  
700 mA  
700 mA  
700 mA  
1/2”  
1/2”  
1/2”  
5/8”  
5/8”  
5/8”  
ASCO  
ASCO  
Solenoid Group C  
Star Sprinkler Corp.  
Kidde-Fenwal  
Kidde-Fenwal  
Kidde-Fenwal  
Kidde-Fenwal  
p/n 5550  
p/n 890181  
p/n 899175  
p/n 48650001  
p/n 897494  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
24 VDC  
part of Model D Deluge Valve  
2.0  
2.0  
0.2  
33.0  
1.5  
Table 5 Solenoid Release Valves  
40  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notification Appliances, UL Listed  
Appendix B: Compatible Devices  
Notification Appliances, UL Listed  
Control panels suppling Special Application (FWR, Filtered) power must use the Notification Appliances  
listed below.  
• Rated Voltage is nominal operating voltage  
• All currents are in millamperes and worst case average.  
Rated  
Voltage  
FWR Filtered  
Product  
DC  
DC  
System Sensor MA-12/24D Electronic Sounder  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
73  
*
46  
30  
System Sensor SS24 Strobe  
System Sensor SS24LO Strobe  
45  
25  
System Sensor SS24LOC Ceiling Strobe (SS24LOBC - beige)  
System Sensor SS24M Strobe  
45  
25  
125  
125  
118  
118  
118  
118  
198  
198  
*
75  
System Sensor SS24MC Ceiling Strobe  
75  
System Sensor MASS24D Electronic Sounder/Strobe  
System Sensor MASS24LO Electronic Sounder/Strobe  
System Sensor MASS24LOC Electronic Ceiling Sounder/Strobe  
System Sensor MASS24LOLA Electronic Sounder/Strobe w/Fuego lens  
System Sensor MASS24M Electronic Sounder/Strobe  
System Sensor MASS24MC Electronic Ceiling Sounder/Strobe  
System Sensor PA400R Sounder  
71  
71  
71  
71  
121  
121  
15  
System Sensor PS24LO Add-on Strobe  
45  
25  
System Sensor SS2415ADA Signaling Strobe  
90  
75  
System Sensor SS2475ADA Signaling Strobe  
200  
245  
120  
125  
180  
163  
273  
318  
193  
163  
193  
110  
135  
240  
135  
90  
170  
210  
93  
System Sensor SS24110ADA Signaling Strobe  
System Sensor SS241575ADA Signaling Strobe  
System Sensor SS2415ADAS Signaling Strobe with Synch. Circuit  
System Sensor SS241575ADAS Signaling Strobe with Synch. Circuit  
System Sensor MASS24110ADA Sounder/Signaling Strobe  
System Sensor MASS2475ADA Sounder/Signaling Strobe  
System Sensor MASS24110ADA Sounder/Signaling Strobe  
System Sensor MASS241575ADA Sounder/Signaling Strobe  
System Sensor MASS24110ADAS Sounder/Signaling Strobe w/Sync. Ckt.  
System Sensor MASS241575ADAS Sounder/Signaling Strobe w/Sync. Ckt.  
System Sensor PS2415ADA Mini-Sounder/Strobe  
System Sensor PS2475ADA Mini-Sounder/Strobe  
System Sensor PS24110ADA Mini-Sounder/Strobe  
System Sensor PS241575ADA Mini-Sounder/Strobe  
System Sensor SP1R2415ADA Speaker/Signaling Strobe  
System Sensor SP1R2475ADA Speaker/Signaling Strobe  
System Sensor SP1R24110ADA Speaker/Signaling Strobe  
System Sensor SP1R241575ADA Speaker/Signaling Strobe  
System Sensor V4R2415ADA Speaker/Signaling Strobe  
System Sensor V4R2475ADA Speaker/Signaling Strobe  
System Sensor V4R24110ADA Speaker/Signaling Strobe  
System Sensor V4R241575ADA Speaker/Signaling Strobe  
System Sensor SP100W24LOC Ceiling Speaker/Strobe, 8” round grill  
System Sensor SP101R24LO Speaker/Strobe, 5” square grill  
106  
115  
121  
216  
256  
139  
121  
139  
90  
108  
225  
108  
75  
200  
245  
120  
90  
170  
210  
93  
75  
200  
245  
120  
45  
170  
210  
93  
25  
45  
25  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B: Compatible Devices  
Notification Appliances, UL Listed  
Rated  
Voltage  
FWR Filtered  
Product  
DC  
DC  
System Sensor SP101R24M Speaker/Strobe, 5” square grill  
24VDC  
24VDC  
125  
125  
75  
75  
System Sensor SP100W24MC Ceiling Speaker/Strobe, 8” round grill  
System Sensor MA12/24EH Multi Alert Horn with Mechanical Tone  
12VDC/  
24VDC  
20/64  
38/43  
System Sensor MAEH24LO Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH24LOC Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH24LOLA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH24M Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH24MC Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH1215ADA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH121575ADA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH2415ADA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH2475ADA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH241575ADA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH24110ADA Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical Tone/Strobe  
System Sensor H12 SpectrAlert Horn  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
12VDC  
12VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
24VDC  
12VDC  
24VDC  
12VDC  
12VDC  
24VDC  
24VDC  
24VDC  
24VDC  
12VDC  
12VDC  
24VDC  
24VDC  
24VDC  
24VDC  
12VDC  
12VDC  
24VDC  
24VDC  
24VDC  
24VDC  
109  
109  
153  
189  
189  
240  
310  
278  
273  
343  
318  
198  
253  
25  
68  
68  
96  
118  
118  
191  
246  
216  
216  
271  
256  
152  
241  
14  
System Sensor H24 SpectrAlert Horn1  
42  
37  
System Sensor S1215 SpectrAlert Strobe  
159  
182  
142  
132  
170  
220  
173  
196  
165  
177  
215  
265  
200  
240  
90  
133  
168  
83  
System Sensor S121575 SpectrAlert Strobe  
System Sensor S2415 SpectrAlert Strobe1  
System Sensor S241575 SpectrAlert Strobe1  
System Sensor S2475 SpectrAlert Strobe1  
76  
145  
169  
144  
179  
94  
System Sensor S24110 SpectrAlert Strobe1  
System Sensor P1215 SpectrAlert Horn/Strobe  
System Sensor P121575 SpectrAlert Horn/Strobe  
System Sensor P2415 SpectrAlert Horn/Strobe1  
System Sensor P241575 SpectrAlert Horn/Strobe1  
111  
180  
214  
170  
255  
75  
System Sensor P2475 SpectrAlert Horn/Strobe  
System Sensor P24110 SpectrAlert Strobe1  
System Sensor RP1215ADAA Retrofit Strobe Plate  
System Sensor RP121575ADAA Retrofit Strobe Plate  
System Sensor RP2415ADAA Retrofit Strobe Plate  
System Sensor RP241575ADAA Retrofit Strobe Plate  
120  
200  
245  
93  
System Sensor RP2475ADAA Retrofit Strobe Plate  
170  
210  
System Sensor RP24110ADAA Retrofit Strobe Plate  
Note 1: Refer to manufacturer’s installation instructions for more information.  
* Contact manufacturer for currents.  
Table 6 Notification Appliances  
42  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Door Holders, UL Listed  
Appendix B: Compatible Devices  
Door Holders, UL Listed  
Use the Door Holders listed below.  
Current  
(mA)  
Model  
Type  
FM-980-24  
FM-986-24  
FM-998-24  
DH150A  
Floor Mount, Single  
Wall Mount, Surface Wiring  
Wall Mount, Concealed Wiring  
Floor Mount  
68  
68  
68  
96  
96  
96  
DH154A  
Flush Mount  
DH158A  
Surface Mount  
Table 7 Door Holders  
24 VDC Relays, UL Listed  
Use the Relays listed below.  
Current  
(mA)  
Vendor  
Model  
System Sensor  
Air Products & Controls, LTD  
A77-716B  
20  
MR-101/C  
MR-201/C  
15  
35  
Table 8 24 VDC Relays  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B: Compatible Devices  
24 VDC Relays, UL Listed  
Notes  
44  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C: NFPA Standard-Specific Requirements  
Minimum System Requirements  
The control panel has been designed for use in commercial, industrial, and institutional applications and  
meets the requirements for service under the National Fire Protection Association (NFPA) Standards  
outlined in this appendix. The minimum system components required for compliance with the appropriate  
NFPA standard are listed below.  
Fire Alarm Control Panel. Contains the main control board, cabinet (backbox and door), main  
supply transformer and power supply.  
Batteries. Refer to "Appendix A: Secondary Power Calculations" on page 37  
Initiating Devices. Connected to one of the control panel's Initiating Device Circuits.  
Notification Appliances. Connected to one of the control panel's Notification Appliance Circuits.  
Releasing Devices. Connected to one of the control panel’s Releasing Circuits.  
Additional Requirements  
The following additional equipment is needed for compliance with the NFPA standards listed below. The  
relaycontactsofthiscontrolpanelmaybeusedtotripanydialerthatisULlistedforCentralStation/Remote  
Station services. The illustrations in this appendix provide examples of possible system configurations.  
Note: Applications which require the the NOTI-FIRE 911AC are not FM approved.  
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)  
NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter (DACT) connected to a  
compatiblelistedCentralStationDACRorProtectedPremisesReceivingUnit. See"DigitalAlarm  
Communicator/Transmitter-Noti-Fire911AC"on page46forinstallationinstructionsforthisunit.  
411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central  
StationDACRorProtectedPremisesReceivingUnit. See"UniversalDigitalAlarmCommunicator  
- 411UDAC" on page 47 for installation instructions for this unit.  
NFPA 72 - Auxiliary Fire Alarm System  
4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box.  
See "Local Energy Municipal Box" on page 48 for installation instructions for this unit.  
NFPA 72 - Remote Station Fire Alarm System  
Fire•Lite RS82-9 Remote Station Receiver connected to a 4XTM Transmitter Module. See  
"Remote Station Receiver - RS82-9" on page 49 for installation instructions for this unit.  
NOTI-FIRE 911AC DACT connected to a compatible listed Central Station DACR. See "Digital  
Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 46 for installation instructions for  
this unit  
411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central  
Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 47 for  
installation instructions for this unit.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C: NFPA Standard-Specific Requirements Digital Alarm Communicator/Transmitter - Noti-Fire 911AC  
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC  
Note: This application is not FM approved  
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises  
Receiving Unit.  
• AC Wiring for DACT/FACP must be connected to the same circuit.  
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less  
than 20 ft. (609.6 cm) in length in the same room.  
• For additional information refer to the Noti-Fire 911AC Instruction manual.  
See Below for Terminal  
Connections  
To Central  
Station  
PS 1270  
12Volt  
+
7AH Battery  
To AC Power  
Control Panel  
IN #1  
IN #2  
IN #3  
IN #4  
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–  
TB4  
TB3  
4XZM Zone  
Relay Module  
TB1  
JP1  
SUPV 1  
SUPR 2  
J2  
DISABLE  
LATCH  
STD DACT  
OPT1  
To Common  
Terminal of Relay  
Jumper  
TB3  
Place jumper over pins as shown when employing  
a DACT. This directs the control panel to transmit  
all trouble conditions except AC LOSS.  
Figure 24 DACT Connections  
46  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Universal Digital Alarm Communicator - 411UDAC  
Appendix C: NFPA Standard-Specific Requirements  
Universal Digital Alarm Communicator - 411UDAC  
The following figure illustrates an example of Central Station/Remote Station Receiver or Protected  
Premises Receiving Unit reporting using a 411UDAC. The relay contacts of the MRP-4424 may be used  
to trip any dialer listed for Central Station/Remote Station services. For additional information refer to the  
Instruction Manual for the 411UDAC.  
• All connections between the control panel and the 411UDAC must be in conduit, less than 20 feet  
(6.1 meters) in length in the same room.  
• The PDRP-1001 Series is non suitable for transmission of a supervisory signal to the DACT.  
• Any zone of the 411UDAC can be wired to function as alarm or trouble; the unit must be  
programmed accordingly. In this example, Zone 1 is wired to the control panel’s alarm relay, Zone2  
iswiredtothecontrolpanel’stroublerelay,andZone3iswiredtotheoptionalmodule’ssupervisory  
relay.  
• AC power is supplied directly to the 411UDAC, not through the control panel. AC wiring for both  
the 411UDAC and the control panel must be connected to the same AC branch circuit.  
• End-of-Line Resistors must terminate all circuits. In this example, Zone 4 is unused and is  
terminated at the board.  
• When employing a DACT, place the JP1 jumper, on the control panel, as shown below. This directs  
the panel to transmit all trouble conditions except AC LOSS. The DACT must be configured to  
transmit AC power loss to the central station.  
Zone 1  
Zone 2  
Zone 3  
Secondary Phone Line  
Primary Phone Line  
Alarm  
Trouble  
Control Panel  
RELAY 1  
NO NC  
RELAY 2  
NO NC  
+12V PWR ZONE 1 ZONE 2 ZONE 3  
ZONE 4  
NAC  
C
C
B+ B-  
+
-
B+ B- B+ B- B+ A+ A- BB+ B-  
TB4  
TB1  
TB2  
PH1  
PH2  
Modular Cable  
P/N MCBL-6  
411 UDAC  
Supervisory  
4XZM Zone  
Relay Module  
Jumper  
Figure 25 411UDAC Connections  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C: NFPA Standard-Specific Requirements  
Local Energy Municipal Box  
Local Energy Municipal Box  
Using the 4XTM Transmitter Module for connection to a Local Energy Municipal Box.  
• The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for  
direct short between two wires. It is not a power-limited circuit.  
• This application is not suitable for separate transmission of sprinkler supervisory or trouble  
conditions.  
• Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.  
FIRE  
Municipal Box Circuit  
+
TB1  
Local Energy  
Municipal Box  
TBL  
J1  
J2  
4XTM Transmitter Module  
(activated polarities shown)  
Figure 26 Municipal Box Connection  
48  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Remote Station Receiver - RS82-9  
Using the 4XTM Transmitter Module for connection to a Fire•Lite RS82-9 Remote Station Receiver.  
• Intended for connection to a polarity reversal circuit of a remote station receiving unit having  
compatible ratings.  
• All connections are power-limited and supervised with the exception of the reverse polarity loop.  
• Supervision of the loop is the responsibility of the receiver.  
Fire•Lite RS82-9  
Remote Station  
Receiver  
+
+
Remote  
Alarm  
TB1  
Remote  
Trouble  
4XTM Transmitter  
Module  
TBL  
J1  
J2  
Figure 27 RS82-9 Connections  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C: NFPA Standard-Specific Requirements  
Remote Station Receiver - RS82-9  
Notes  
50  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix D: Testing & Maintenance  
Testing  
Inspection  
Perform the following prior to applying power to the system.  
• Check the actual wiring hookup with the wiring diagrams.  
• Insure that no pieces of wire have fallen into the circuitry.  
• Check for missing or damaged parts.  
Alarm Test  
An initial alarm test should be conducted following installation to determine that all parts of the system  
are functioning properly. The panels should remain powered for 24 to 36 hours proir to connecting the  
releasingsolenoids.Thisprecautionwillavoidfalsedischargesofgasincaseoffaultyorimproperlyplaced  
detectors.  
To perform an alarm test on the panel follow this procedure  
1. Disconnect AC power and battery power.  
2. Disconnect the installed solenoid valve circuit leads an connect spare solenoid valves, or connect  
an end-of-line device to serve as a dummy load.  
3. Reconnect AC power and battery power.  
4. Initiate a first zone alarm condition by blowing smoke into one of the Zone 1 smoke detectors. This  
should cause the first zone alarm condition.  
• The alarm relay will energize.  
• The red zone alarm LED will be illuminated.  
• The remote Indicating Circuit #1 audible alarm and the local piezo will start sounding.  
Maintenance  
A regular schedule of inspection, testing, and maintenance is vital to insure proper and reliable operation  
of the control panel. The procedures should be performed as required by the local authority having  
jurisdiction. Refer to NFPA for further details.  
Troubleshooting  
A troubleshooting table is included on the following page which provides for symptoms, problems and  
their solutions.  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix D: Testing & Maintenance  
Troubleshooting  
Table 9 Troubleshooting Table  
Symptom  
Problem  
Solution  
1. Check TB2 for proper connections.  
2. Remove all field wiring and install dummy ELR at  
output circuit. Check for supervisory voltage across it,  
(Normal -2.3 V), if problem persists, replace circuit  
board.  
Circuit trouble Notification appliance circuit  
LED ON  
trouble  
3. Removed dummy ELR, reconnect field wiring and  
measure voltage across output; (trouble-5V, short 0V).  
4. Check for ELR at last device.  
5. Check field wiring.  
1. Check TB4 for proper connections.  
2. Remove field wiring for zone in trouble and install  
dummy ELR (4.7K). If problem persists, replace  
circuit board.  
Any of the right  
column yellow  
LEDs flashing  
Initiating zone open circuit  
trouble  
3. Check for ELR at last device.  
4. Check field wiring.  
1. Check installation manual.  
Any of the right  
column yellow  
LEDs steady  
ON  
Zone disable  
System trouble  
LED ON  
1. Check battery connections.  
Missing or  
Disconnected  
1. Remove batteries, check voltage across charger  
output (17 to 19V), otherwise replace circuit board.  
Battery trouble  
Batt yellow  
LED ON  
Low or  
damaged  
battery  
2. Reconnect batteries, measure battery voltage at  
battery terminals. If voltage is less than 85% of rated  
voltage, allow them to charge for 48 hours.  
Power trouble  
LED ON  
AC  
3. If problem persists, replace batteries.  
Power  
LED ON  
1. Remove field wiring from main panel and optional  
module(s) (if installed). Install dummy ELR (4.7K).  
2. Remove both battery leads.  
Ground fault trouble  
Earth yellow LED ON  
3. If trouble clears, connect one circuit at the time to  
pin point the problem.  
4. If trouble doesn’t clear, replace circuit board.  
1. Move Municipal Box disconnect switch SW1 up.  
Yellow LED on  
4XTM ON  
4XTM  
1. Install optional module(s) or replace jumper if  
module(s) is not used.  
OPT1, OPT2 jumper cut  
1. Install dummy load if Municipal Box option isn’t  
used.  
Municipal Box open circuit  
2. Check Municipal Box wiring.  
1. Remove field wiring and install ELR. If trouble  
clears, look for faulty or incorrectly wired devices.  
Any of the right column red LEDs  
ON  
Short on initiating circuit wiring  
1. Cut associated jumper OPT1 or OPT2.  
Disconnecting Municipal Box  
switch ON 4XTM does not create  
a trouble  
Jumper for optional modules  
isn’t cut  
1. Make sure module is properly installed.  
4XZM: associated LED doesn’t  
activate for alarm, trouble or  
supervisory conditions  
2. Move disable switch SW1 on 4XZM to the left.  
Optional module trouble  
1. Make sure that 4XLM module is installed on J8.  
2. Check field wiring.  
RZA-4X piezo doesn’t sound for  
alarm, trouble or supervisory  
conditions  
4XLM  
1. Replace circuit board.  
1. Press system reset.  
Micro Fail yellow LED ON  
Microprocessor damaged  
Power wasn’t removed prior to  
installation  
All RZA-4X LEDs stay ON  
1. Check incoming power (TB5).  
1. Replace circuit board.  
Loss of main power  
AC  
Power  
LED OFF  
System trouble LED ON  
Damaged circuit breaker  
Microprocessor damaged  
1. Replace circuit board.  
Micro Fail yellow LED ON  
52  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Index  
Cross Zone 28, 35  
Numerics  
current 12, 21  
110/120 VAC 12  
current draw 35  
220/240 VAC 12  
411UDAC 45, 47  
D
4XLM LED Interface Module 11, 23  
4XMM Meter Module 11, 15  
4XTM Transmitter Module 10, 23, 45, 48, 49  
4XZM Zone Relay Module 10, 23  
911AC DACT 45, 46  
DC power connections 22  
detector, four-wire smoke 32  
detectors, type of 18  
devices 21  
devices, supplementary 22  
dialer 45, 47  
A
DIP switch 20, 28, 29  
DIP switch functions 10  
direct short 48  
disable switch 26  
disabled zone 33  
AC branch circuit 47  
AC power 31, 47, 51  
accidential discharge 21  
acknowledge 32  
additional equipment 45  
alarm 31, 47  
Alarm Relay 35  
alarm relay 22, 51  
allowable resistance 19  
ammeter 11  
annunciator wiring 11  
audible alarm 51  
authority having jurisdiction 51  
discharge timer 29  
discharge, accidential 21  
Disconnect LED 25  
Disconnect Switch 25  
dry contacts 26  
Dual Hazard 28  
dummy load 20, 21  
dummy load resistor 18  
duplicate modules 23  
B
E
backbox 13  
earth fault 31  
backbox rail 13, 14  
Batteries 16, 45  
battery  
ELR 18, 19, 20, 21  
End-of-Line Resistor 12, 47  
energize 35  
cable 17  
event 31  
capacity 38  
exterior dimensions 14  
external battery cabinet 12  
external devices 12  
charger 38  
interconnect wire 16, 17  
power 51  
BB-17 12, 38  
black wire 17  
Brownout circuitry 35  
buffer 34  
F
Fire Alarm Control Panel 45  
first alarm 35  
first zone 51  
FM approved 45, 46  
Form-C contacts 10, 12  
four-wire smoke detector 12, 32  
C
Canadian 28, 33, 34  
Central Station 45, 46, 47  
charging current 15  
circuit  
Remote Alarm 25  
Remote Trouble 25  
reverse polarity 10  
circuit board 13  
G
ground fault 31, 48  
I
Indicating Circuit #1 51  
initial alarm test 51  
initiating circuits 32  
initiating device 35, 45  
Initiating Device Circuit 34  
circuit breaker 16  
Combined Release 28  
conductors 13  
conduit 13, 47  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
inspection 51  
National Electrical Code, Article 760 16  
National Fire Protection Association 45  
negative 17  
interconnect wire, battery 30  
Interface Module 11  
interruption of circuits 34  
NFPA 51  
NFPA standards 45  
non-latching 26, 32  
J
nonpower-limited 17, 21, 26  
nonresettable power 19, 22  
non-silenceable service 20  
Notification Appliance Circuit 32  
Notification Appliances 45  
J1 connector 13, 14  
J2 Connector 15  
J3 Connector 15  
J9 Connector 17  
JP1 jumper 47  
jumper 23, 24  
LATCH 26  
O
opens 48  
K
operating mode 28  
operating voltage 19  
optional boards 32  
Out of Service 30  
output circuits 32  
overcurrent protection 16  
keyhole 13  
knockouts 13, 17  
L
label  
Protected Premises Unit 26  
terminal identification 23, 24  
LAMP TEST function 32  
latch 32, 33  
LATCH jumper 26  
latching operation 33, 34  
LED  
P
paper labels 11  
piezo 32, 33, 34, 35, 51  
piezo tones 32  
polarity 17, 18, 30  
polarity reversal circuit 49  
polarized devices 18, 20  
positive 17  
Disconnect 25  
System Trouble 25  
LED Interface Module 11, 23  
LEDs  
power connection 16  
Power Supervision Relay 19  
power-limited 17, 20, 26, 49  
power-limited power supply 22  
previous panel status 34  
primary power 16, 30  
programmed 47  
Alarm, Trouble and Supervisory 31  
Local Energy Municipal Box 10  
loop resistance 48  
lower position 23, 24  
M
Protected Premises Receiving Unit 45, 46, 47  
main breaker panel 16  
maintenance 51  
R
rail 24  
Manual Pull Stations 18  
maximum allowable resistance 21  
Maximum Battery Capacity 12  
Maximum Charging Circuit 12  
maximum resistance 19  
Meter Module 11, 15  
microprocessor 31  
rail, backbox 13, 14  
red wire 17  
regulated power 22  
relay contacts 47  
Relay, System Alarm 32  
release 31  
releasing 21  
minimum clearance 13  
minimum voltage 21  
module connectors 23  
motherboard 31  
mounting hole locations 14  
mounting holes 13  
Municipal Box 25, 48  
Releasing Circuit 20, 21  
releasing device 35  
Releasing Devices 45  
Remote Alarm circuit 25  
Remote Annunciator 11  
Remote Station 45, 47  
Remote Station Service 10  
Remote Trouble circuit 25  
reset switch 35  
N
NACs 20  
54  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
resettable power 19, 22  
resistance, allowable 19  
resistor 47  
troubleshooting 51  
Two Zone 28  
U
resound 32  
reverse polarity 25  
UL listed 45  
unused circuits 20, 21  
upper position 23  
reverse polarity circuit 10  
reverse polarity loop 49  
RS82-9 Remote Station Receiver 45, 49  
RZA-4X Remote Annunciator 11  
V
visual inspection 30  
voltage 15  
S
second alarm 35  
voltage drop 12  
voltmeter 11  
Secondary Power 30  
secondary power source 37  
self-restoring 32  
W
separate transmission 48  
short circuit 33  
silence switch 11  
Single Hazard 28  
watchdog timer 31  
Waterflow 18  
wire, primary power 16  
wires, transformer 13  
Slide-in paper labels 11  
solenoid valve 35, 51  
Split Release 28  
Z
zone 47  
Zone Relay Module 10, 23  
sprinkler 33, 34  
sprinkler supervisory 48  
Standby Battery Current 37  
stand-off 14, 23, 24  
Style B (Class B) 18  
Style D (Class A) 18  
Style Y (Class B) 20, 21  
Style Z (Class A) 20  
sulfuric acid 30  
supervised 20  
supervisory device 31, 33  
Supervisory LED 33  
supervisory signal 47  
supplementary devices 22  
switch, disable 26  
system alarm 31  
System Alarm Relay 32  
System Trouble LED 25  
T
tag, “Out of Service” 30  
terminal identification label 23, 24  
testing 51  
timer, watchdog 31  
tone patterns 33  
tones, piezo 32  
tracking operation 33, 34  
transformer wires 13, 14  
Transmitter Module 10, 23, 48, 49  
trim ring 14  
trouble 47  
condition 31, 34, 48  
relay 22  
trouble sounder 11  
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
System Sensor® warrants its products to be free from defects in materials and workman-  
ship for eighteen (18) months from the date of manufacture, under normal use and ser-  
vice. Products are date stamped at time of manufacture. The sole and exclusive  
obligation of System Sensor® is to repair or replace, at is option, free of charge for parts  
and labor, any part which is defective in materials or workmanship under normal use and  
service. For products not under System Sensor® manufacturing date-stamp control, the  
warranty is eighteen (18) months from date of original purchase by System Sensor® dis-  
tributor unless the installation instructions or catalog sets forth a shorter period, in which  
case the shorter period shall apply. This warranty is void if the product is altered, repaired  
or serviced by anyone other than System Sensor® or its authorized distributors or if there  
is a failure to maintain the products and systems in which they operate in proper and work-  
able manner. In case of defect, secure a Return Authorization Number from our Customer  
Service Department. Return product, transportation prepaid, to System Sensor Repair  
Department, RA #_____, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note  
describing the malfunction and suspected cause of failure.  
This writing constitutes the only warranty made by System Sensor® with respect to its  
products. System Sensor® does not represent that its products will prevent any loss by  
fire or otherwise, or that its products will in all cases provide the protection for which they  
are installed or intended. Buyer acknowledges that System Sensor® is not an insurer and  
assumes no risk for loss or damages or the cost of any inconvenience, transportation,  
damage, misuse, abuse, accident or similar incident.  
SYSTEM SENSOR® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MER-  
CHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE  
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO  
CIRCUMSTANCES SHALL SYSTEM SENSOR® BE LIABLE FOR ANY LOSS OF OR  
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING  
OUT OF THE USE OF, OR INABILITY TO USE SYSTEM SENSOR® PRODUCTS. FUR-  
THERMORE, SYSTEM SENSOR® SHALL NOT BE LIABLE FOR ANY PERSONAL  
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,  
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.  
This warranty replaces all previous warranties and is the only warranty made by System  
Sensor®. No increase or alteration, written or verbal, of the obligation of this warranty is  
authorized.  
3825 Ohio Avenue  
St. Charles, IL 60174  
1-800-SENSOR2  
Fax: (630) 377-6495  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Shure Headphones SRH840 User Manual
SIIG TV Mount 04 0660A User Manual
Soleus Air Water Dispenser WA1 02 21A User Manual
Sony CD Player CDP XE200 User Manual
Sony Computer Drive CRX320EE User Manual
Sony Computer Drive R505 User Manual
Sony MP3 Player CFD V20 User Manual
Sterling Dehumidifier SDA AP 1 User Manual
Sunwave Tech Universal Remote SRC 7000 User Manual
Sylvania CRT Television 6427FE User Manual