System Sensor Home Security System S1224MC User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
SpectrAlert Selectable Output Strobes,  
Horns, and Horn/Strobes  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
For use with the following models:  
Strobes - 12/24 volt: S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW  
Combo - 12/24 volt: P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, P1224MCPW  
Horns - H12/24, H12/24W  
Suffix “W” indicates white housing models. Suffix “SP” indicates “FUEGO” (Spanish word for “FIRE”) lettering on housing.  
Suffix “P” indicates plain housing (no lettering).  
The Products to which this manual applies may be covered by one or more of the  
following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 5,931,569; 6,793,375; 6,822,400; 6,833,783; 6,838,997  
Specifications  
Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)  
Electrical  
Horns, Strobes, and  
Horn/Strobes Voltages:  
Operational Voltage Ranges:  
Synchronous Applications  
with MDL Module:  
Regulated 12 DC/FWR and Regulated 24 DC/FWR  
12V=8-17.5 Volts; 24V=16-33 Volts  
12V=9-17.5 Volts; 24V=17-33 Volts  
10-93% RH (non-condensing)  
Operational Humidity Range:  
NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.  
Flash Rate:  
1 flash per second  
Operating Temperature:  
Selectable Light Outputs:  
12/24 Volt Applications:  
24 Volt Application:  
32° F to 120° F (0° C to 49° C)  
All candelas are selectable via a manual slide switch.  
15 or 15/75 candela  
30, 75, 110 candela  
15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis  
(straight ahead). 15, 30, 75, or 110 are rated for that candela.  
Sound output levels are established at Underwriters Laboratories in their reverber-  
ant room. Always use the sound output specified as UL Reverberant Room when  
comparing products.  
Sound Output:  
Listings:  
UL S5512 (Strobe); UL S4011 (Combo)  
Note for Strobes:  
Do not exceed: 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70  
strobe lights when connecting the MDL Sync module with a maximum line im-  
pedance of 4 ohms per loop and; 3) maximum line impedance as required by the  
fire alarm control manufacturer.  
The models S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW, P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, and  
P1224MCPW incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The benefit to  
the customer is a high quality strobe device.  
General Description  
stalled after July 1, 1996, must produce Temporal Coded Signals.  
The SpectrAlert series notification appliances are designed to  
Signals other than those used for evacuation purposes do not have  
to produce the Temporal Coded Signal. Temporal coding is accom-  
plished by interrupting a steady sound in the following manner:  
meet the requirements of most agencies governing these devices,  
including: NFPA, ADA, The National Fire Alarm Code, UL, ULC,  
FM, CSFM, MEA. Also, check with your local Authority Having  
Jurisdiction for other codes or standards that may apply.  
The SpectrAlert series can be installed in systems using 12- or 24-  
volt panels having DC or full-wave rectified (FWR) power supplies.  
The series can also be installed in systems requiring synchroniza-  
tion (module MDL or compatible equivalent required) or systems  
that do not require synchronization (no module required).  
1
1
1
1
1
/
2
Sec.  
On  
/
2
Sec.  
Off  
/
2
Sec.  
On  
/
2
Sec.  
Off  
/
2
Sec.  
On  
11/2 Sec.  
Off  
Repeats  
Power Supply Considerations  
Panels typically supply DC filtered voltage or FWR (full-wave  
rectified) voltage. The system design engineer must calculate the  
number of units used in a zone based on the type of panel supply.  
Be certain the sum of all the device currents do not exceed the  
current capability of the panel. Calculations are based on using  
the device current found in the subsequent charts and must be  
the current specified for the type of panel power supply used.  
NOTICE: This manual shall be left with the owner/user of this equipment.  
Fire Alarm System Considerations  
Temporal and Non-Temporal Coded Signals:  
The American National Standards Institute and the National Fire  
Alarm Code require that all horns used for building evacuation in-  
D900-28-00  
1
I56-1796-011R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: SpectrAlert selectable output strobes, set at 15 and 15/75cd,  
automatically work on both 12V and 24V power supplies.  
Figure 2: Candela Selections  
For strobe candela selection, adjust slide switch located  
on the rear of the product while watching the viewing win-  
dow on the side of the reflector.  
NOTE: The strobe is not listed for 12V operating voltages when  
set to 30, 75 or 110 candelas. Use only those settings marked as  
OK in the chart above.  
Permissible Candela Settings:  
Candela  
Setting  
Operating Voltage  
NOTE: The low volume setting of some tones must NOT be used  
for public mode applications when the device is powered from a 12-  
volt panel. Refer to the Sound Output Guide on the previous page.  
12V  
OK  
24V  
OK  
OK  
OK  
OK  
OK  
15  
15/75  
30  
OK  
Temp/Non-Temp  
ON=NON-Temporal, OFF=Temporal  
3KHz/Electromechanical  
A0133-00  
75  
Viewing Window  
110  
ON=3KHz, OFF=Electromechanical  
Check terminal polarity before wiring. For proper operation, make sure the correct wire  
polarity is applied to the unit.  
WARNING  
Figure 5: Horns and strobes powered in tandem  
NOTE: Supply power must be continuous for proper operation.  
Figure 3: Horn Factory Default Setting  
The factory default setting is High, Temporal 3, and Electrome-  
chanical tone.  
TANDEM OPERATION  
Factory  
HORN/STROBE COMBO  
DIP Switch  
OFF  
ON  
Default  
Horn +  
Low  
High  
TO NEXT  
DEVICE OR  
EOL  
FACTORY  
INSTALLED  
JUMPERS  
+
FROM:  
FACP, MODULE  
OR PREVIOUS  
DEVICE  
A0110-00  
Temporal  
Non-Temporal  
3000Hz  
Strobe +  
Strobe – Horn –  
Electromech.  
A0112-00  
Base (rear)  
Horn selections using 3-position DIP switch on horn/  
strobe (refer to Figure 3):  
Figure 6: Any combination of models powered by a  
NOTE: When powered from a FWR supply, the horn will be mod-  
ulated (turned on and off) by 120Hz causing it to sound different  
than if powered by a DC supply.  
4-wire circuit to provide independent horn and strobe op-  
eration (remove factory installed jumpers, see Figure 8)  
NOTE: Strobes must be powered continuously for horn operation.  
High/Low Volume  
ON=High Volume, OFF=Low Volume  
(+)  
(+)  
(+)  
H
O
R
N
H
O
R
N
System Operation – Non-Synchronized Devices:  
Figure 4a: Any combination of models powered by a  
2-wire circuit:  
E
O
L
(–)  
(+)  
(–)  
(–)  
(–)  
C
O
M
B
O
HORN  
HORN/STROBE  
STROBE ONLY  
(+)  
(+)  
(+)  
(+)  
TWO WIRE SYSTEM  
ANY MIX OF MODELS  
WIRED FOR TANDEM  
OPERATION  
E
O
L
(+)  
(–)  
(+)  
(–)  
S
T
R
O
B
E
S
T
R
O
B
E
E
O
L
(–)  
(–)  
(–)  
(–)  
A0111-00  
System Operation – Synchronized Devices:  
Figure 4b: Any combination of models powered by a  
2-wire circuit:  
A0113-00  
HORN  
HORN/STROBE  
STROBE ONLY  
(+)  
(–)  
(+)  
(+)  
(+)  
TWO WIRE SYSTEM  
ANY MIX OF MODELS  
WIRED FOR TANDEM  
OPERATION  
E
O
L
(–)  
(–)  
(–)  
SYNCHRONIZATION MODULE  
A0111-00  
D900-28-00  
3
I56-1796-011R  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 7: Horns and strobes powered independently  
(horn operated on coded power supply)  
Figure 8: Removal of horns and strobes from  
mounting plates  
NOTE: Strobes must be powered continuously for horn operation. To remove units from mounting plates, insert Quick Click Re-  
moval Tool as shown to unlock snap. While pushing in Removal  
Tool to release the snap, pull back on the horn/strobe. Hinge the  
horn/strobe module, disengage the Locking Rib, and lift the horn/  
INDEPENDENT OPERATION  
HORN AND STROBE  
HORN +  
FACTORY INSTALLED  
strobe away from the mounting plate.  
JUMPER WIRES REMOVED  
PLASTIC SNAP LEVER  
STROBE +  
INSERT REMOVAL TOOL  
NOTE: STROBES MUST  
BE POWERED CONTINUOUSLY  
FOR HORN OPERATION.  
HORN +  
TO NEXT  
DEVICE OR  
EOL  
STROBE +  
STROBE –  
STROBE –  
FROM:  
TO NEXT  
DEVICE OR  
EOL  
FACP, MODULE (MDL)  
OR PREVIOUS  
DEVICE  
HORN –  
HORN –  
Break wire as shown for  
supervision of connection.  
DO NOT allow stripped wire  
leads to extend beyond switch  
housing. DO NOT loop wires.  
A0114-00  
A0115-00  
TAB SLOT  
TAB  
Mounting Diagrams:  
Screw types used for mounting:  
Strobe or Horn/Strobe with small footprint  
mounting plate:  
S-MP, S-MPW  
2-INCH BACK BOX  
3
A = 8-32 x ⁄  
4
flat head  
B
B = 6-32 x 15⁄  
16  
pan head  
Strobe or Horn/Strobe with universal mounting plate:  
D-MP, D-MPW, D-MP-FC, D-MPW-FC  
B
4-INCH BACK BOX  
WALL OPENING MUST  
EQUAL PLATE OPENING  
A
LOCKING RIB SLOT  
LOCKING RIB  
1. Mount plate to back box using screws B.  
2. Break off four tabs from unit.  
A0116-00  
3. Complete field wiring, making sure wall opening is large enough for  
terminals to fit through.  
4. Insert locking rib into slot on plate.  
5. Press into plate; unit will make a “click” when it has locked into place.  
A
WALL OPENING MUST  
EQUAL PLATE OPENING  
A0117-00  
LOCKING RIB  
LOCKING RIB SLOT  
Strobe or Horn/Strobe surface mount:  
BBS, BBSW  
4-INCH BACK BOX  
1. Mount plate to back box using screws A, making sure wall  
opening is equal to the plate opening.  
2. Complete field wiring.  
A
3. Insert locking rib into slot on plate.  
4. Press into plate, unit will make a “click” when it has locked  
into place.  
A
LOCKING RIB SLOT  
LOCKING RIB  
1. Mount skirt to back box with screws A.  
2. Complete field wiring.  
A0118-00  
3. Insert locking rib on unit into slot on skirt.  
4. Press into skirt; unit will make a “click” when it has locked into place.  
(NOTE: Strobe and skirt may also be mounted to a 2-inch box using  
screws B instead of screws A.)  
Please refer to insert for the Limitations of Fire Alarm Systems  
Three-Year Limited Warranty  
System Sensor warrants its enclosed horn. strobe, or horn/strobe to be free from defects in materials  
to: System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.  
Please include a note describing the malfunction and suspected cause of failure. The Company  
shall not be obligated to repair or replace units which are found to be defective because of dam-  
age, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no  
case shall the Company be liable for any consequential or incidental damages for breach of this or  
any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the  
Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or  
consequential damages, so the above limitation or exclusion may not apply to you. This Warranty  
gives you specific legal rights, and you may also have other rights which vary from state to state.  
and workmanship under normal use and service for a period of three years from date of manu-  
facture. System Sensor makes no other express warranty for this horn, strobe, or horn/strobe. No  
agent, representative, dealer, or employee of the Company has the authority to increase or alter  
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be  
limited to the repair or replacement of any part of the horn, strobe, or horn/strobe which is found  
to be defective in materials or workmanship under normal use and service during the three year  
period commencing with the date of manufacture. After phoning System Sensor’s toll free number  
800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid  
FCC Statement  
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the limits for a  
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide  
reasonable protection against harmful interference when the equipment is operated in a com-  
mercial environment. This equipment generates, uses, and can radiate radio frequency energy  
and, if not installed and used in accordance with the instruction manual, may cause harmful  
interference to radio communications. Operation of this equipment in a residential area is likely  
to cause harmful interference in which case the user will be required to correct the interference  
at his own expense.  
D900-28-00  
4
I56-1796-011R  
© 2005 System Sensor  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Shure Microphone 55S User Manual
Sony Car Stereo System D E706CK User Manual
Sony Computer Accessories MSPSMS11000 User Manual
Sony Home Theater System MHC LX10000 User Manual
Sony Microphone ECM DS70P User Manual
Sony Satellite TV System SA VE230 User Manual
Sony TV Mount MB 522 User Manual
Sony Wireless Office Headset MDRAS600BT B User Manual
StarTechcom Switch SV231UADVI User Manual
Stow Chainsaw CC813H20 User Manual