Studer Innotec Universal Remote RCC 02 User Manual

User Manual  
Remote control and  
programming unit  
RCC-02 and RCC-03  
for the Xtender  
Studer Innotec  
Rue des Casernes 57  
CH - 1950 Sion  
Tel: +41 (0)27 205 60 80  
Fax: +41 (0)27 205 60 88  
V 2.1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Table of contents  
Foreword...............................................................................................................................................................7  
Conventions .....................................................................................................................................................7  
Product recycling............................................................................................................................................7  
Studer Innotec contact details .....................................................................................................................8  
Your reseller’ contact details.........................................................................................................................8  
Warnings and caution........................................................................................................................................8  
Warnings and caution........................................................................................................................................9  
Warranty ...........................................................................................................................................................9  
Limitation of responsability.............................................................................................................................9  
Safety instructions............................................................................................................................................9  
Acceptance of the software licence and updates..................................................................................9  
Introduction........................................................................................................................................................11  
Models concerned........................................................................................................................................11  
Controls and indicators ................................................................................................................................11  
SD card............................................................................................................................................................11  
Connection........................................................................................................................................................12  
Series connection..........................................................................................................................................12  
Dimensions..........................................................................................................................................................13  
RCC-02 ............................................................................................................................................................13  
RCC-03 ............................................................................................................................................................13  
Quick Start Guide..............................................................................................................................................14  
Adjustment of the language .......................................................................................................................14  
Adaptation to the source ............................................................................................................................14  
Adaptation to the batterie..........................................................................................................................15  
Activation of the function Smart-Boost......................................................................................................16  
Basic displays .....................................................................................................................................................17  
Activating and deactivating the combi Xtender........................................................................................18  
Adjustment of the RCC remote control.........................................................................................................19  
Adjustment of the language {5000} ...........................................................................................................19  
Adjustment of date {5002) and time {5001}..............................................................................................19  
Adjustment of the contrast {5006} ..............................................................................................................19  
Adjustment of the back-lighting {5007} .....................................................................................................19  
Back-lighting always off {5008}................................................................................................................19  
Duration of the back-lighting {5009}.......................................................................................................20  
Red back-lighting if the Xtender is OFF and if there is a fault {5026}.................................................20  
Inactivity period before returning to the standard display {5010}.........................................................20  
Duration of display for quick messages {5011} .........................................................................................20  
Acoustic alarm {5027}...................................................................................................................................20  
User level {5012} .............................................................................................................................................20  
Drive the remote control to the user level basic {5019} ..........................................................................20  
Backup and restoring {5013}........................................................................................................................20  
Backup of statistics {5014} ........................................................................................................................20  
Backup of remote control configurations {5015}..................................................................................21  
Backup of Xtender configurations {5017} ..............................................................................................21  
Loading the remote control configurations {5016} ..............................................................................21  
Loading the Xtender configurations {5018}...........................................................................................21  
Loading a master file {5034}.....................................................................................................................21  
Separator of the csv files {5032}...............................................................................................................21  
Information on the operating mode of the installation ..............................................................................22  
Display of the parallel and three-phase systems .....................................................................................23  
Event history .......................................................................................................................................................24  
Alarm Low battery voltage..........................................................................................................................24  
Stop Battery voltage too low.......................................................................................................................24  
Stop High battery voltage............................................................................................................................24  
Message AC IN synchronisation in progress..............................................................................................24  
Error Incorrect input frequency ...................................................................................................................25  
Error Input voltage too high.........................................................................................................................25  
Error Input voltage too low...........................................................................................................................25  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Stop Inverter overvoltage ............................................................................................................................25  
Stop Overtemperature .................................................................................................................................25  
Stop Excessive battery voltage ripple........................................................................................................25  
Message Power sharing exceeded; transfer prohibited.........................................................................26  
Error Voltage at AC Out ...............................................................................................................................26  
Error Phase not defined ................................................................................................................................26  
Stored events .................................................................................................................................................26  
Adjustment of the combi Xtender..................................................................................................................27  
General...........................................................................................................................................................27  
Configuration on a system with several Xtenders....................................................................................27  
Utilisation and access levels ........................................................................................................................27  
Pre-defined functions of the auxiliary relays .............................................................................................27  
Menu ...............................................................................................................................................................27  
Basic configurations {1100}.......................................................................................................................28  
Maximum current of the AC source (power sharing) {1107}...........................................................28  
Locking {1123}.........................................................................................................................................28  
Authorised inverter {1124} ..............................................................................................................28  
Authorised charger {1125} .............................................................................................................29  
Smart boost authorised {1126}.......................................................................................................29  
Authorised transfer {1128} ..............................................................................................................29  
Automatic restart {1129} .......................................................................................................................29  
Number of battery under-voltages allowed before final stop {1304} and ............................29  
Leadtime to counting the battery under-voltages allowed before final stop {1404}..........29  
Number of critical battery under-voltages before final stop {1305} and...............................30  
Leadtime to counting the critical battery under-voltages allowed before final stop {1405}  
............................................................................................................................................................30  
Restore default configurations {1395}.................................................................................................30  
Battery cycle and charger {1137}...........................................................................................................30  
Charge current {1138}...........................................................................................................................33  
Temperature correction coefficient {1139}........................................................................................33  
Battery maintenance voltage (floating) {1140}................................................................................33  
Force passage to floating mode {1467}.............................................................................................33  
New cycle {1141} ...................................................................................................................................33  
Force new cycle {1142}..................................................................................................................33  
Voltage 1 for a new cycle {1143} and Duration at undervoltage 1 for a new cycle {1144}  
............................................................................................................................................................33  
Voltage 2 for a new cycle {1145} and Duration at undervoltage 2 for a new cycle {1146}  
............................................................................................................................................................33  
New priority cycle on the absorption and equalization phases {1149}..................................33  
Absorption phase {1451}.......................................................................................................................34  
Authorised absorption {1155} ........................................................................................................34  
Absorption voltage {1156}..............................................................................................................34  
Duration of absorption {1157}........................................................................................................34  
Completion of absorption released by the current {1158}.......................................................34  
Current at end of absorption {1159}.............................................................................................34  
Equalization phase {1452}.....................................................................................................................34  
Start equalization {1162}.................................................................................................................34  
Authorised equalization {1163}......................................................................................................34  
Equalization before absorption phase {1291}.............................................................................35  
Equalization current {1290}.............................................................................................................35  
Equalization voltage {1164} ...........................................................................................................35  
Duration of equalization {1165}.....................................................................................................35  
Number of cycles prior to equalization {1166}............................................................................35  
Equalization at set intervals {1284]................................................................................................35  
Weeks between equalizations {1285} ..........................................................................................35  
End of equalization activated by the current {1168} ................................................................36  
End of equalization current {1169}................................................................................................36  
Inverter configurations {1186} ..................................................................................................................36  
Standby level {1187} ..............................................................................................................................36  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Output voltage {1286}...........................................................................................................................36  
Level of battery under-voltage at no load {1108}............................................................................37  
Acoustic alarm of the battery under-voltage {1196}.......................................................................37  
Duration of the acoustic alarm {1469}................................................................................................37  
Combi configurations Inverter-Charger {1197}.....................................................................................37  
Minimum AC In voltage to authorise the charging {1309}..............................................................37  
Transfer AC-In for delayed transfer opening {1199}..........................................................................37  
Delay before passing to inverter {1198}..............................................................................................38  
Immediate transfer AC-In voltage {1200}...........................................................................................38  
Activate immediate detection of grid outage (UPS) {1435}...........................................................38  
Authorisation for exceeding the power sharing current without interrupting the transfer {1436}  
..................................................................................................................................................................38  
Solsafe presence {1438}........................................................................................................................38  
Delay before closing of the transfer relay {1528}..............................................................................38  
Configurations for auxiliary contacts 1 and 2 {1201} {1310}................................................................38  
Simple functions .........................................................................................................................................39  
Switching mode {1202} {1311}..............................................................................................................39  
Combination of events mode {1497} {1498}......................................................................................39  
Limit the time of activation {1512} {1513}...........................................................................................40  
Maximum duration of activation {1514} {1515}.................................................................................40  
Temporal restrictions {1203} {1312} ......................................................................................................40  
Contacts activated by an event {1455} {1456}.................................................................................40  
Xtender OFF {1225} {1333}..............................................................................................................40  
Battery undervoltage alarm {1226} {1334} ..................................................................................40  
Battery overvoltage {1227) {1335} ................................................................................................40  
Inverter or smart boost overload {1228} {1336}...........................................................................41  
Overtemperature {1229} {1337}.....................................................................................................41  
No Overtemperature alarm {1520} {1521}...................................................................................41  
Active charger {1231} {1339}.........................................................................................................41  
Active inverter {1232} {1340}..........................................................................................................41  
Smart boost active {1233} {1341} ..................................................................................................41  
AC In present with fault {1234} {1342} ..........................................................................................41  
AC In present {1235} {1343}............................................................................................................41  
Transfer relay drawn {1236} {1344}................................................................................................41  
AC Out present {1237} {1345}........................................................................................................41  
Battery charging in bulk charge phase {1238} {1346} ...............................................................41  
Battery charging in absorption phase {1239} {1347}..................................................................41  
Battery charging in equalization phase {1240} {1348}...............................................................41  
Battery charging in floating phase {1242} {1350} .......................................................................41  
Contacts activated by the battery voltage {1245} {1353}..............................................................41  
Dynamic compensation of the thresholds {1288} {1354} ..........................................................42  
Deactivate if the battery is in floating mode {1516} {1517}......................................................42  
Contacts activated by inverter power or smart boost {1257} {1366} ............................................42  
Contacts activated with set schedules {1269} {1378}......................................................................42  
Extended functions {1489}........................................................................................................................43  
Generator startup {1490} ......................................................................................................................43  
Generator startup {1491} ......................................................................................................................43  
Duration of starter impulse {1492}........................................................................................................43  
Number of startup attempts {1493}.....................................................................................................43  
Duration between the starter attempts {1494}..................................................................................43  
Multi Xtender {1282}...................................................................................................................................43  
3-phase integral mode {1283} .................................................................................................................43  
Information on the system ...............................................................................................................................44  
Remote controls.............................................................................................................................................44  
Xtender............................................................................................................................................................44  
Updates ..............................................................................................................................................................45  
Updating process ..........................................................................................................................................45  
Compatibility..................................................................................................................................................45  
Application examples ......................................................................................................................................46  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
général use : Inverter, Charger with grid...................................................................................................46  
Use of a limited power source.....................................................................................................................46  
Use to increase the power on an existing installation .............................................................................47  
Load shedding of the second priority loads .............................................................................................47  
Annexes ..............................................................................................................................................................48  
Annexe 1 : List of configuration interdependencies................................................................................48  
Notes ...................................................................................................................................................................50  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
FOREWORD  
This manual contains information relating to the functioning of the RCC-02 and RCC-03 remote  
controls.  
The use of certain functions sometimes requires increased knowledge in various fields. This manual  
cannot provide this. In case of doubt, please contact your reseller or installer.  
CONVENTIONS  
This symbol is used to indicate the presence of a dangerous voltage that is sufficient  
to constitute a risk of electric shock.  
This symbol is used to indicate a risk of material damage.  
This symbol is used to indicate information that is important or which serves to  
optimise your system.  
Terminology:  
The following terms are used in the manual to provide greater clarity:  
RCC is used to indicate the remote control RCC-02 or RCC-03 if the description applies to both  
models.  
Installation is used to describe all the electrical equipment connected together. This may be the  
source (public grid or generator), and one or more Xtender(s) with or without remote control as well  
as electrical consumers.  
System is used to describe the entirety of Xtenders with or without remote control.  
Xtender or combi is used to describe one or more Xtender(s) connected together.  
PRODUCT RECYCLING  
The RCC remote control conforms to the European directive 2002/95/EC on hazardous substances  
and does not contain the following elements: lead, cadmium, mercury, hexavalent chrome, PBB or  
PBDE.  
To dispose of this product, please use the service for the collection of electrical waste and observe  
all applicable obligations according to the place of purchase.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
STUDER INNOTEC CONTACT DETAILS  
Studer Innotec  
Rue des Casernes 57  
CH – 1950 Sion  
Tel. +41 (0)27 205 60 80  
Fax. +41 (0)27 205 60 88  
Customer service:  
After-sales service:  
Technical support:  
Website:  
YOUR RESELLERCONTACT DETAILS  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
WARNINGS AND CAUTION  
WARRANTY  
Studer Innotec issues on this product, which they have manufactured and offered for sale, a two  
year warranty against any material defect or manufacturing fault from the date of despatch by an  
agreed Studer Innotec distributor.  
Any warranty claim will be refused if it is not sent back to the point of sale, or another place  
indicated by Studer Innotec, in appropriate packaging and accompanied by a copy of the dated  
proof of purchase.  
No warranty claims will be accepted for damage resulting from handling, usage or processing that  
does not explicitly appear in this manual.  
Cases of damage arising from the following causes are notably excluded from the warranty:  
Inappropriate use  
The presence of liquids in the device or oxidation resulting from condensation  
Damage resulting from falls or mechanical shocks  
The opening or alteration of the RCC remote control, carried out without the explicit authorisation  
of Studer Innotec  
Damage due to atmospheric surge voltage (lightning)  
Damage from transportation due to inappropriate packaging  
LIMITATION OF RESPONSABILITY  
The placement, commissioning, use, maintenance and servicing of the RCC remote control cannot  
be the subject of monitoring by Studer Innotec. For this reasons Studer Innotec assumes no  
responsibility and liability for damage, costs or losses resulting from an installation that does not  
conform to the instructions, defective functioning or deficient maintenance.  
The use of Studer Innotec devices is the responsibility of the customer in all cases. This equipment is  
neither designed nor guaranteed to supply installations used for vital medical care nor any other  
critical installation carrying significant potential damage risks to people or the environment.  
Studer Innotec does not assume any responsibility for the infringement of patent rights or other  
rights of third parties that result from using the devices.  
The responsibility of Studer Innotec may not under any circumstances exceed the amount spent to  
purchase the product.  
Studer Innotec reserves the right to make any modifications to the product without prior  
notification.  
SAFETY INSTRUCTIONS  
Carefully read the following safety instructions in order to avoid any injury or risk of damaging this  
product and those that are connected to it.  
Only use the connection cable specified and supplied by Studer Innotec. Under no circumstances  
should you use a damaged cable. In case of doubt about the condition of this device, it should be  
inspected by a qualified technician.  
Do not use the RCC remote control in a humid environment.  
Do not use the RCC remote control in an explosive environment.  
ACCEPTANCE OF THE SOFTWARE LICENCE AND UPDATES  
By using the RCC remote control, you are accepting the terms and conditions of the following  
licence agreement. Please read this carefully.  
Studer Innotec is granting a limited licence to use the software installed in this equipment in its  
executable binary format during the normal functioning of the product. The title, the property rights  
and the copyrights relating to this software, remain the property of Studer Innotec.  
You acknowledge that the software is the property of Studer Innotec and that it is protected by  
copyright law according to the international copyright treaties.  
You also acknowledge that the structure, organisation and software code are valuable  
commercial secrets belonging to Studer Innotec. You agree not to decompile, disassemble, alter or  
reverse either the unit or the engineering or make the software readable, irrespective of which part  
of the software, or to create any work whatever that is based on this software.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Updating must be done in the full awareness of the cause and is always the responsibility of the  
customer. Partial updates may cause ruptures in the compatibility or in its stochastic operation.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
INTRODUCTION  
Congratulations! The purchase of an RCC remote control offers you unlimited access to the various  
functions of the devices in the Xtender series. Numerous configurations that can now be accessed  
allow you to optimise the operation of the installation. Despite all these options, the Xtender works  
on a simple basis.  
Different figure scenarios as well as associated configurations are presented at the end of this  
manual.  
The manual for the RCC remote control is divided into several distinct parts:  
The first part is devoted to the adjustments of the RCC remote control, whether this is the language  
used or the clock, which are sometimes necessary for the whole installation to work well.  
The second part is concerned with immediate information on the installation. This gives access to  
the electric values such as the battery voltage, inverter load and many more.  
The third part shows the functions for saving events occurring in the installation. This may be  
necessary for diagnosing a weakness or simply to check that the whole unit is working well during its  
whole service life.  
The fourth part, which is more technical, presents various options for configuring the Xtender.  
Do not change the configurations except when you have the technical knowledge; otherwise, the  
operation of the installation could at risk or installation itself could be partly damaged.  
MODELS CONCERNED  
The RCC remote control may be connected to any Xtender, the use of which is clearly detailed in  
its operating instructions.  
CONTROLS AND INDICATORS  
The RCC remote control is equipped with four operating keys as well as a graphic display  
with back-lighting. The function of the keys may change according to the context of  
utilisation and a reminder of the function in progress is given at the right of the display.  
Generally the keys UP and DOWN are used to alter values or options relating to what is on  
the display and the two central keys are used to access, confirm or quit the item shown.  
If the back-lighting function is activated, pressing one of the keys starts it up.  
SD CARD  
The RCC remote control is equipped with an SD (smart data)-type memory card  
reader. This card (not supplied) is used for various functions described in this  
manual. It allows, amongst others, the following  
functions: recording statistics, updates, backups or  
restoration of configurations or adjustments. The  
filing system used for the data is the FAT system. This  
card can be read using any standard SD card  
reader.  
As far as the RCC-03 is concerned, the use of the  
SD card requires removing the remote control since  
the access to the SD lies behind.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
CONNECTION  
The RCC-02 remote control must be firmly fastened using 3 screws on a flat support. The remote  
control RCC-03 is meant to be integrated. It must be mounted by means of 4 screws (not supplied)  
on a flat place without any mechanical constraints to the front plate. Once the RCC remote  
control is fastened it can be connected to the inverter using the authorised cable only. If the cable  
is damaged or if a socket is detached, the cable must not be connected since this can cause the  
whole installation to malfunction.  
A maximum of 3 remote controls can be connected to one unit.  
SERIES CONNECTION  
To connect several RCC remote controls in series, you must activate termination at the two  
extremities on both units and deactivate it on the intermediate units.  
Termination is activated on each Studer Innotec product by default.  
Activate the termination on each element of the series connection with a single cable.  
Deactivate the termination on each element of the series connection with two cables.  
To deactivate the termination on an inverter or RCC remote control, turn the switch to the right.  
RCC-02 termination activated (position T)  
RCC-02 termination deactivated (position O)  
RCC-03 termination activated  
(left position)  
RCC-03 termination deactivated  
(right position)  
To activate the termination on the Xtender,  
move the two mini-switches to position T, and  
to deactivate it, move them downwards to  
position O.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
DIMENSIONS  
RCC-02  
RCC-03  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
QUICK START GUIDE  
The remote control RCC gives you access to a many settings possibilities. However, in most cases  
the setting of two parameters is required for the perfect running of your installation.  
ADJUSTMENT OF THE LANGUAGE  
To begin, set your remote control RCC for a display of the information in English.  
The basic display is:  
Press 2 times on the key “arrow downwards” to display the  
following screen:  
Once beyond this screen you can come back to it by means  
of the key ”arrow upwards”.  
Press the key SET to enter the remote control settings. The  
screen of the language choice appears.  
Press once more the key SET to modify the current language.  
The language then appears in reverse video.  
With the keys “arrow upwards” and “arrow downwards” choose the language you wish. Then  
validate your choice by means of the key SET (OK).  
We can now leave the setting of the remote control with the key ESC.  
ADAPTATION TO THE SOURCE  
It is a matter of indicating to the Xtender the power available to charge the batteries and to supply  
the users.  
In order to adapt your installation to the source it is connected to, proceed as follows :  
The basic display is:  
Press 3 times on the key “arrow downwards” to display the  
following screen:  
Once beyond this screen you can come back to it by means  
of the key ”arrow upwards”.  
Press the key SET to access to the settings.  
Then again on the key SET to access to the basic parameters.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
You can now adapt your installation to the source which it is  
connected to.  
Max. current of the AC source (power-sharing) {1107}.  
In case of using the Xtender on a public grid, it is actually the value of the circuit  
breaker on the source side (fuse or breaker).  
In a building, this value lies generally between 8 and 16A.  
In the case of a shorepower or of a camping terminal, it lies between 2 and 6A.  
In case of using the Xtender on a genset, you can divide the genset power by the  
operating voltage (for instance for a genset of 3500VA, or 3500W, and 230V you get  
3500/230=15.2).  
Caution: the powers given on the gensets are often overestimated compared to  
their real performances. To obtain a useable value it is necessary to multiply this  
result by 0.6 or 0.7 (in that case 15.2*0.7=10.64).  
Press the key SET to modify the value of this parameter (it appears in reverse video). By means of  
the keys “arrow upwards” and “arrow downwards” change the value to adapt it to your source  
and validate your setting with the key SET (OK).  
ADAPTATION TO THE BATTERIE  
Charge current {1138}  
In order that your Xtender manages the best possible the energy stored in your batteries and that it  
charges them optimally, it is necessary to indicate the current which they can be charged with.  
You will find this value in the technical data provided by your batteries manufacturer.  
In the case of lead-acid batteries, one generally uses one tenth or one fifth of the  
battery capacity value.  
For instance for a 500Ah battery: 500/10=50A to 500/5=100A.  
The basic display is this one:  
Press 3 times the key « arrow downwards » to display the  
following screen:  
If you go overpass this screen you can come back to it by  
means of the key « arrow upwards »  
Press the key SET to access to the settings.  
With the key “arrow downwards”, access the menu “Battery  
and charger cycle”.  
Press the key SET to access this menu.  
You are now going to set the charge current for the batteries:  
Press the key SET to modify the value of this parameter (it  
appears in reverse video). With the keys “arrow upwards” and  
“arrow downwards” change the value to adapt your battery  
and validate your setting with the key SET (OK).  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
ACTIVATION OF THE FUNCTION SMART-BOOST  
If your AC-In source is limited in power, the Xtender can work as a support and add the missing  
power for your loads.  
First of all, check that you have adapted the Xtender to your source (see previous chapter:  
Adaptation to the source {1107})  
The basic display is the following:  
Press 3 times the key « arrow downwards » to display the  
following screen:  
If you go overpass this screen you can come back to it by  
means of the key « arrow upwards »  
Press the key SET to access the settings.  
Then again the key SET to access the basic parameters.  
Press the key DOWN to access the following parameter: the  
menu of disabling. Then again the key SET to get to the menu.  
Go down with the key DOWN until the function Smart-Boost  
authorization parameter {1126}.  
You can now authorize the function. Press the key SET to  
access this parameter in modification mode, then the keys UP  
or DOWN to change the option. To end up, validate with the  
key SET.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
BASIC DISPLAYS  
When the remote control is connected to an Xtender, it is possible to access different display  
menus divided into distinct categories.  
Real time information displays on the operating mode of  
the installation  
The history of events occurring in the installation  
Adjustment of RCC remote control options  
Adjustment of configurations on the Xtender(s)  
Information on the system  
To go from one display to the other, use the keys UP and DOWN on the RCC remote control.  
To visualize or modify the options of one of the basic displays, press the key SET when this one is  
displayed.  
In the case of a system in 3-phase or in parallel, the following displays are available too:  
Real time display of information on the state of running of the  
installation.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
ACTIVATING AND DEACTIVATING THE COMBI XTENDER  
When one of the displays is visible, it is possible to activate or deactivate the Xtender. To do this,  
simply press the key ESC. The key request on the screen indicates whether you are going to  
activate or deactivate the unit.  
Once the key has been pressed, you must confirm your  
choice using the key YES. If you do not want the action to  
be carried out, it can be cancelled by pressing the NO  
key.  
Note: This is a comprehensive signal and leads to the stoppage or starting of all  
Xtenders connected to the remote control.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
ADJUSTMENT OF THE RCC REMOTE CONTROL  
This screen gives you access to the remote control basic  
settings. From one of the basic menu items, use the keys  
UP and DOWN until reaching the item “Adjustment of the  
remote control”, then confirm using the key SET.  
When the item to be modified appears on the screen, press the key SET to be able to  
modify it. This value then displays in inverse video. Now use the keys UP and DOWN to  
modify it. Once the correct value has been obtained, confirm by using the SET key or exit  
without modifying using the key ESC.  
Each configuration has a unique ID displayed top right (see example below) these  
numbers are indicated between curly brackets in this manual : {xxxx}  
EXAMPLE to modify the current date  
Go to the following screen using the UP and DOWN keys.  
Press the key SET to access the remote control adjustment.  
Go to the following screen using the key DOWN.  
Press the key SET to modify the configuration  
Set the correct date using the keys UP and DOWN  
Go to the adjustment of the month using the key SET  
Also set the month using the keys UP and DOWN  
To complete, go to the year adjustment using the key SET  
After having adjusted the year using the keys UP and  
DOWN, confirm using the key SET.  
ADJUSTMENT OF THE LANGUAGE {5000}  
The default language is English and the Xtender can store up to four languages simultaneously. This  
configuration allows you to choose one of them.  
ADJUSTMENT OF DATE {5002) AND TIME {5001}  
The Xtender has a perpetual calendar and an internal clock powered by a backup battery. The  
correct adjustment of the date and time allows accurate recording of events occurring in the  
installation as well as correct use of time-related functions, e.g. the disabling of the auxiliary relays  
during the night.  
ADJUSTMENT OF THE CONTRAST {5006}  
The adjustment of the contrast allows the display to be adjusted in terms of lighting and to a  
reading position that allows excellent visibility.  
ADJUSTMENT OF THE BACK-LIGHTING {5007}  
Back-lighting always off {5008}  
This adjustment allows you to activate or deactivate the back-lighting. Its activation gives access to  
an additional configuration that is the duration of the back-lighting.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Duration of the back-lighting {5009}  
This configuration allows you to determine after how much time of inactivity the back-lighting will  
switch off.  
Red back-lighting if the Xtender is OFF and if there is a fault {5026}  
If the Xtender is stopped by a fault (battery undervoltage, overload, etc.) the back-lighting flashes  
red.  
INACTIVITY PERIOD BEFORE RETURNING TO THE STANDARD DISPLAY {5010}  
This configuration allows you to determine the time after which the display returns to the basic  
display if no key is pressed.  
DURATION OF DISPLAY FOR QUICK MESSAGES {5011}  
Messages of low importance are displayed for a limited period. This adjustment enables you to  
adapt this duration at your convenience.  
ACOUSTIC ALARM {5027}  
In the event of an alarm an acoustic signal is activated. You can always deactivate this signal by  
using this configuration.  
USER LEVEL {5012}  
The adjustment of the user level allows you to choose the access to the Xtender according to your  
level of expertise.  
The INFO ONLY level may be selected by entering the code 460081. This level does not allow the  
Xtender configurations to be modified, it only allows information to be displayed on the system.  
Use the INFO ONLY level after adjusting the configurations if the remote control is  
located in a public place or if it is accessible by people who are not authorised to  
carry out adjustments on your system.  
You may change the level at any time to make new adjustments, by entering the  
appropriate code.  
The BASIC level allows you to configure basic Xtender functions, limiting the field of actions to  
simple configurations. Please note that the incorrect adjustment of basic configurations may lead  
to the malfunctioning of the installation. This level is selected by default. To return to this level after a  
change, enter code 943274.  
The EXPERT level allows access to more complex Xtender configurations and this level of usage may  
only be used with extensive specialist knowledge. To access the expert level, enter code 426468.  
DRIVE THE REMOTE CONTROL TO THE USER LEVEL BASIC {5019}  
You can with this option bring the remote control back to the level “user Basic”.  
Use this function at the end of the system setting to go out of the EXPERT mode.  
BACKUP AND RESTORING {5013}  
The different options of this menu allow you to do a safety backup of your system or various actions  
in relation to the SD card.  
Backup of statistics {5014}  
Backup the data on the operation of your Xtender(s) using the SD card. The data are written into a  
file in CSV format, which can be reread in practically all spreadsheets and word processing  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
programs. The file is written in a directory called STATS and in a subdirectory which indicates the  
date of backup.  
Backup of remote control configurations {5015}  
This function writes useful configurations for the operation of the remote control on to the SD card.  
You can use this function to do a backup of the remote control parameters or to visualize on a  
computer the values that you have selected.  
The file in CSV format is written in a directory called CSVFILES\« FID »\DATE.  
The directory FID indicates the unique identification of your remote control and contains the  
subdirectory which indicates the date of backup.  
Backup of Xtender configurations {5017}  
This function writes the operational configurations on to the SD card of the Xtender. You can use  
this function to do a backup of the remote control parameters or to visualize on a computer the  
values that you have selected.  
The file in CSV format is written in a directory called CSVFILES\« FID »\DATE.  
The directory FID indicates the unique identification of your Xtender and contains the subdirectory  
which indicates the date of backup.  
Loading the remote control configurations {5016}  
Reload the remote control configurations. If several files have been created with different remote  
controls, the loaded file is the one that corresponds to the remote control being used. If the  
parameters have been backed-up several times at different dates, the last backup will be loaded.  
Loading the Xtender configurations {5018}  
Reload the Xtender configurations. If several files have been created with different Xtenders, the  
loaded file is the one that corresponds to the Xtender being used. If the parameters have been  
backed-up several times at different dates, the last backup will be loaded.  
Loading a master file {5034}  
If your installer provides you with a file of parameters for your installation, you can load it by means  
of this menu. Insert the SD card and launch the loading by pressing the key SET. Caution, the various  
operations carried out by this process take some minutes.  
Separator of the csv files {5032}  
This option allows you to choose the field separator for the csv file. As per the operating system and  
the language that you are using, the separator must be adapted in order to be correctly  
interpreted. In the case of systems in English, the comma (,) is normally used.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
INFORMATION ON THE OPERATING MODE OF THE INSTALLATION  
There are two different views for displaying information on the system :  
A simplified and a configurable display. When one of these two displays is visible, it is possible to  
activate or deactivate the system. For further information, please refer to the paragraph on  
activating and deactivating the combi Xtender.  
The simplified display only indicates the current time and  
the mode of the Xtender (ON or OFF)  
The configurable display shows the system in its entirety, represented by a synopsis of distinct  
information blocks.  
Information on the battery (A)  
Information on the grid input (B)  
Information on the grid output (C)  
Information on the auxiliary contacts (D)  
Information on the transfer and output relays (E)  
Information on the power sharing mode of the smart boost (F)  
Information on possible locking of the function (G)  
Two pieces of information related to blocks A, B and C may be viewed simultaneously. To change  
displayed information, proceed as follows:  
Press the key SET (one of the pieces of information is  
displayed in inverse video).  
Go to the value to be changed using the UP and DOWN  
keys.  
Enter into modification using the key SET. You may now  
view the values that can be displayed in this area.  
Using the keys UP and DOWN, select the new information  
that you want to appear.  
Confirm your selection using the key SET.  
To escape at any time, use the key ESC to return to the starting display.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
The following information is available:  
With regard to the grid input  
AC In input voltage  
AC In input current  
AC In input power  
Input frequency  
Energy from AC-In of the previous day  
Energy from AC-In of the current day  
With regard to the grid output  
Output voltage  
Output current  
Output power  
Output frequency  
Consumers energy of the previous day  
Consumers energy of the of the current day  
With regard to the battery  
Battery voltage  
Actual charge current of the batteries  
Programmed charge current  
Ripple voltage of the batteries  
Charging phase (bulk charge, absorption, float charge, etc.)  
Dynamic compensation of the battery (compensation of the thresholds due to the internal  
resistance of the battery)  
Operating mode (inverter, charger, etc.)  
Battery temperature (if a sensor is present)  
The battery temperature’s inherent compensation (if a sensor is present)  
Discharge of battery of the previous day  
Discharge of battery of the current day  
If a piece of information is not available, the screen displays - - - -.  
Information on the auxiliary relays as well as the output and transfer relays appears as open or  
closed in the synopsis according to their current state.  
Auxiliary relays are indicated with their corresponding number as well as the letter A if they are  
operating in automatic mode and M if they are controlled manually.  
Other letters may be displayed with regard to specific programming. Please refer to the  
corresponding chapter.  
The general operating mode of the combi Xtender is displayed in large letters on the two  
visualisation screens (ON or OFF).  
DISPLAY OF THE PARALLEL AND THREE-PHASE SYSTEMS  
While using several Xtenders in parallel or in three-phase, an additional view is available. This view  
summarizes the various electrical values of the system. Like for the display of a system with one  
single Xtender, you can access to the displayed values in order to modify them.  
Each summarized view gives access to the display of one  
Xtender.  
In the view of the three-phase, you have access to the detail  
of one phase by pushing the key SET and then, by pushing UP  
or DOWN, you can choose the phase you want to see  
displayed in details.  
If the phase consists of several Xtenders in parallel or if the  
system is a single phase one but with several Xtenders in  
parallel, you can then have access to the display of each  
Xtender by selecting in the view parallel one of the three  
available inverters.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
EVENT HISTORY  
This screen allows you to view the various events that  
have occurred in the installation.  
The events that occur in your installation are displayed on the remote control screen. The events  
are classified within two categories:  
The events that may have serious consequences are displayed up to the moment where the  
user confirms that he has taken note of them by pressing on an RCC remote control key. These  
events are recorded in the event history and may be consulted subsequently.  
Events not posing a risk are indicated briefly on the display and then disappear. Some are  
recorded in the event history and others are not (see the list of elements stored further on).  
On the other hand, the messages may have different origins and they are preceded by an  
attribute to enable you to understand the importance:  
Message : normal event but one that conditions or influences the operation of the Xtender.  
Error: an event that prevents the correct or normal operation of the Xtender.  
Alarm: an event that may cause a malfunction of the installation if it is not corrected.  
Stop: The system had to be stopped as a major event is preventing its operation.  
ALARM LOW BATTERY VOLTAGE  
The battery is almost completely discharged. If the situation persists, the inverter function of the  
Xtender will be deactivated.  
Solution: Recharge your batteries more frequently or increase the power available for charging  
(e.g. .with more solar generators).  
This message is generated in conjunction with the undervoltage of the battery  
configuration {1108} and not with acoustic alarm {1196}.  
The service life of the batteries is greatly conditioned by their state of charge.  
Prolonged or repeated operation at a low charge may cause damage.  
With the smart boost function activated, it is also possible to discharge the batteries  
even if connected to a source of energy.  
STOP BATTERY VOLTAGE TOO LOW  
The Xtender inverter and boost functions are deactivated since the batteries are discharged.  
Solution: Recharge your batteries to automatically reactivate these functions.  
STOP HIGH BATTERY VOLTAGE  
The battery voltage present on the Xtender is too high. The system is stopped for safety reasons.  
Solution: Check that the rated voltage of the battery conforms to that required by your Xtender.  
Where an external charger is being used, check that this is charging the batteries at a voltage  
admissible for the Xtender.  
MESSAGE AC IN SYNCHRONISATION IN PROGRESS  
A valid voltage has been detected on the AC IN input and the Xtender is synchronising. Once  
synchronised, the consumers will be transferred to it and the battery will be charged.  
Note: It is possible to prohibit the transfer or the battery charging.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
ERROR INCORRECT INPUT FREQUENCY  
The voltage at AC IN does not have a frequency included in the admissible range for the Xtender.  
Solution: When operating on a generator, check its speed.  
If you are not equiped to measure the generator frequency, measure its voltage  
with no load. Indeed, if the voltage is correct, the frequency is generally correct as  
well.  
ERROR INPUT VOLTAGE TOO HIGH  
The voltage at the AC IN is too high for the Xtender and represents a danger for the consumers; the  
transfer relay is not activated.  
Solution: Reduce the voltage on the AC IN input to come into an admissible range.  
ERROR INPUT VOLTAGE TOO LOW  
The voltage at AC IN is too low for the Xtender. The transfer of consumers and battery charging are  
not activated.  
Solution: Reduce the voltage on the AC IN input to come into an admissible range.  
Do not increase the voltage of the generator during the battery charging or when  
the consumers are connected to it: If the consumers stop, an overvoltage may arise  
which will destroy components of your installation.  
If the transfer of the consumers is carried out and the message appears some  
seconds after the start of the battery charging, check that you have not adjusted  
the charging voltage of the batteries too high in relation to your source.  
Also check the adjustment of the power sharing configuration.  
STOP INVERTER OVERVOLTAGE  
The consumers require more power than the Xtender inverter can supply.  
Solution: Adapt the maximum power output of your consumers to the maximum power output of  
the Xtender.  
STOP OVERTEMPERATURE  
The Xtender stops due to overheating.  
Solution: Adapt the maximum power output of your consumers to the rated power output of the  
Xtender.  
Check that the ventilation holes of the Xtender are not obstructed.  
Check that the Xtender is not situated in a place where the ambient temperature is too high.  
The overtemperature is disadvantageous for the service life of certain electronic  
components. If the stoppages due to overtemperature happen frequently,  
corrective measures will be required.  
STOP EXCESSIVE BATTERY VOLTAGE RIPPLE  
The Xtender is stopped as the voltage ripple at the battery cables is too high.  
Solution: Check that the battery cable section is correct.  
Check the tightness of the battery cables.  
Check that the charge current matches your battery.  
Check the state of your batteries.  
The use of batteries of an inappropriate capacity may also cause this error  
message. In this case, reduce the charge current or lower the power output of the  
consumers.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
The voltage ripple on the batteries may be caused by their ageing. In this case,  
lower the charge current.  
MESSAGE POWER SHARING EXCEEDED; TRANSFER PROHIBITED  
The power output of the consumers exceeds the one specified for the source, and the transfer  
relay cannot be activated. The Xtender operates in inverter mode.  
Solution: Check that the configuration of the maximum current for the source corresponds to the  
maximum current of the source connected at AC In.  
Reduce the number or power output of the consumers.  
In this case, the transfer relay is not activated and the recharging of the batteries  
cannot take place. If this situation continues, you risk discharging your batteries.  
ERROR VOLTAGE AT AC OUT  
An unwanted voltage is present at AC Out.  
Solution: Check the installation cabling. No source should be connected to the Xtender output (AC  
Out).  
ERROR PHASE NOT DEFINED  
The Xtender cannot operate without the phase being defined.  
Solution: Check the phase definition jumper in the cable connection zone.  
Refer to the Xtender manual for more information.  
STORED EVENTS  
Events are stored in the remote control. Any system not permanently connected to a remote  
control does not store the events.  
Disconnection due to inverter overload  
Disconnection due to battery overvoltage  
Disconnection due to battery undervoltage  
Disconnection due to Xtender overtemperature  
AC In voltage too high  
Bulk charge too long (risk of short-circuited element)  
Battery voltage ripple too high (charge current too high for the battery used)  
Voltage at AC Out  
Results of the autonomy tests  
Overrunning of the power source and transfer relay opening  
To access the event history via one of the basic displays,  
change the screen using the keys UP and DOWN until the  
“event history” screen appears and then validate using  
the key SET.  
The number shown at the top right indicates the message  
number. In a system with several Xtenders, the events are  
presented in chronological order and the lower line  
indicates the Xtender to which the event refers.  
Each event is recorded as well as the date and time of its  
occurrence. The keys UP and DOWN allow you to view all  
the events that have occurred.  
Where there is a system with multiple Xtenders, each  
message also contains the number of the Xtender that  
has generated the message.  
Quit the message display using the key ESC.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
ADJUSTMENT OF THE COMBI XTENDER  
GENERAL  
The Xtender inverter/charger has been designed to  
ensure that all basic functions of an energy management  
system work completely independently. In its original  
version, no adjustment is usually required.  
Nevertheless, in certain installation conditions, it may be necessary to adjust some operating  
configurations. This is why the RCC remote control gives access to the adjustment of many  
configurations and within a range largely exceeding the usual values. Use these adjustment options  
with care and only with due specialist knowledge. Changing configurations is not the responsibility  
of Studer Innotec. Please refer to the chapter on limitation of responsibility for more information on  
this topic.  
CONFIGURATION ON A SYSTEM WITH SEVERAL XTENDERS  
When there is a system to which several Xtenders are connected, the changing of a configuration  
is global. It will be applied to all the Xtenders connected together. To carry out adjustments on a  
single Xtender, it is necessary to remove the connection cables and only keep the connection  
between the remote control and the Xtender on which the different adjustment is being carried  
out. It is thereby possible to configure each Xtender of a system independently. Once the  
configuration has been carried out, the original connection can be re-established.  
Note: If you have carried out an individual configuration, once a configuration has  
been changed, the system reconnected by the data connection cable modifies  
this configuration for all the Xtenders connected.  
UTILISATION AND ACCESS LEVELS  
The functions described below refer to the EXPERT level. Depending on the user level selected,  
access to all the functions may not be possible. Refer to the chapter on adjusting the user level of  
the remote control for more information on this subject.  
PRE-DEFINED FUNCTIONS OF THE AUXILIARY RELAYS  
The two auxiliary relays (dry contacts) of the inverter-charger Xtender are already programmed  
with factory settings and can be activated with various functions. They react to different signals.  
The factory settings depend on the Xtender models.  
For more information on the auxiliary contacts pre-set functions, please see the inverter-charger  
Xtender manual.  
Caution, if your installer or supplier has done pre-settings, these pre-set functions  
may have been changed.  
To check the different programmings, use the function backup of the Xtender  
parameters on the SD card, described there above in this manual.  
MENU  
The Xtender configurations are divided into several categories:  
Basic configurations  
Battery and its charge cycle configurations  
Inverter configurations  
Combi configurations (inverter/charger)  
First auxiliary contact configurations  
Second auxiliary contact configurations  
Auxiliary contact extended function configurations  
Three-phase or parallel operation configurations  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
According to the user level selected, it is possible to  
access several hundred configurations. For this reason,  
each configuration has a unique ID displayed top right. In  
the event of questions on the subject of a configuration,  
ensure that you have this number at hand.  
When you modify a configuration, a star is displayed to  
the left of the value if it corresponds to the factory-set  
value.  
The various configurations can be adjusted within a large range. Nevertheless, some configurations  
are interdependent and cannot be adjusted beyond the value of other configurations. You can  
consult the list of dependencies on the list in appendix 1.  
Basic configurations {1100}  
The basic configurations serve to adapt the Xtender characteristics to the elements that surround it.  
Use these configurations in order to optimise the operation of the inverter/charger and to benefit  
from the maximum performance of your installation.  
Maximum current of the AC source (power sharing) {1107}  
Adjust this configuration in the event of  
connection to a limited power source, for  
example, a generator of moderate power  
output or a dock or camping connection. The  
adjustment of this value limits the instantaneous  
power consumed from the source in charger  
mode. The power available is attributed by first  
priority to consumers and then to battery  
charging. If the consumption level changes, the  
battery charge current is automatically adjusted.  
A. Power available and used to recharge the  
batteries  
B. Maximum AC source current (adjusted to 10  
A here)  
C. Consumer current  
D. Power supplied by the inverter (smart boost  
function)  
If the consumption level is higher than the controlled level, the maximum source  
current will be exceeded, except when the smart boost function is activated.  
Locking {1123}  
In certain cases it may be useful to deactivate the Xtender functions to obtain specific behaviour.  
Different possible locks may be accumulated in order to refine the system operation.  
Where there is lock on the inverter, charger or transfer  
function,  
a
small padlock is displayed on the  
configuration display.  
Authorised inverter {1124}  
This configuration authorises operation in inverter mode. If the inverter is deactivated, a voltage will  
be present on the output terminals (AC OUT) only if a correct voltage is present at the input (AC-in)  
and the transfer is not prohibited.  
This function can be used for supplying non-critical consumers while ensuring that  
the battery is not discharged even if the source is faulty.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Note, that if the smart boost function is activated, it is possible to discharge the  
battery even if the inverter function is locked.  
Authorised charger {1125}  
The battery charger function is either activated or not. If this function is not authorised, it is  
necessary to charge the batteries using a source of energy not connected to the Xtender.  
Smart boost authorised {1126}  
The function Smart-Boost is deactivated by default. In this case no assistance will be provided to  
the source and if the source is overloaded, the energy from the battery is not drawn. Do authorise  
this function if you have a low power source (generator, shore power or camping plug) and you  
want more power available.  
When the smart boost function is active, it is possible to discharge the batteries,  
even if the Xtender is connected to a source and the charger is active.  
Authorised transfer {1128}  
The transfer relay is authorised or not. If the transfer is not authorised, a correct voltage at the AC IN  
input will not be transferred to the output and to the users. The battery charger function is not  
possible and the Xtender operates only in inverter mode.  
Automatic restart {1129}  
In the event of an anomaly on the installation, the combi Xtender stops automatically. Depending  
on the seriousness of the fault, when this disappears, the Xtender may restart automatically without  
any user intervention (fault confirmation). The following functions allow the events for automatic  
restart to be defined.  
After battery undervoltage {1130}  
Number of battery under voltages allowed before final stop {1304}  
Leadtime to counting the battery under-voltages allowed before final stop {1404}  
Number of critical battery under-voltages before final stop {1305}  
Leadtime to counting the critical battery under-voltages allowed before final stop {1405}  
After battery overvoltage {1131}  
After inverter or smart boost overload {1132}  
After overtemperature {1134}  
Whatever the restart method, the event is recorded in the event history so that it  
can be called at any time.  
Number of battery under-voltages allowed before final stop {1304} and  
Leadtime to counting the battery under-voltages allowed before final stop {1404}  
If battery under-voltage faults occur to your system, the inverter and Smart-boost functions are  
deactivated in order to protect the battery against deep discharges.  
These functions can be reactivated automatically if the fault disappears. With the parameter  
{1304}, you can adjust the number of the faults before these functions are definitely deactivated. In  
this case, an intervention is necessary to reactivate these functions (fault acknowledgement).  
The duration parameter allows setting the time during which these faults can be repeated.  
Once this duration has come to an end, if the number of faults is not reached, the counter goes  
back to 0 and the faults can occur again.  
To cancel the automatic reactivation, set 1 for the number of battery under-  
voltages allowed before final stop.  
For a permanent automatical reactivation, set 0.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Number of critical battery under-voltages before final stop {1305} and  
Leadtime to counting the critical battery under-voltages allowed before final stop {1405}  
The critical battery under-voltages can also be automatically acknowledged in case of  
undervoltage disappearance. Like for the under-voltages (see previous paragraph) you can adjust  
the number of restarts of the inverter and Smart-boost functions once the fault disappears.  
Restore default configurations {1395}  
Use this function to re-establish the original combi Xtender adjustments.  
If your installer has carried out settings while commissioning your installation, this  
function brings back these settings and not the factory settings.  
Battery cycle and charger {1137}  
These configurations are intended to adjust the battery charge cycle to the data supplied by its  
manufacturer. The basic battery cycle is described in the Xtender manual.  
Caution : the Xtender charger is meant only to the charge of lead batteries.  
Note: Incorrect values may lead to early ageing or even the destruction of the  
batteries.  
For further information, contact your battery supplier who will give you the correct values.  
The graphic presentation of the battery cycle shows the options for linking the various phases:  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
The bulk charge and floating phases cannot be deactivated. If the conditions for starting a new  
battery charge cycle have come together, the bulk charge phase starts immediately.  
The battery cycle fits a large number of batteries by default, irrespective of whether they are gel  
batteries or not.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Charge current {1138}  
Use this value in order to adapt the charge current to the battery. With this configuration, the  
maximum current to be used for charging your battery is adjusted. The current appropriate for the  
battery can be found in its technical data. The value set by this configuration is used during the  
whole bulk charge phase.  
Use this setting to adapt the charge current only with regard to the battery. To  
adapt the charge current to your source, use the parameter for maximum current  
at the source (power sharing) {1107}.  
The right setting of these two values is essential for correct operation as well as the  
lifetime of your installation.  
Temperature correction coefficient {1139}  
If a battery temperature sensor is used, the charge and discharge voltages are automatically  
adapted to the temperature of the batteries. The compensation is given in millivolts by degree  
Celsius (°C) and by battery cell.  
Battery maintenance voltage (floating) {1140}  
Use this configuration to adjust the voltage that will be used when the battery is completely  
charged. This voltage prevents automatic discharging and maintains the battery at its maximum  
level of charge.  
Force passage to floating mode {1467}  
This configuration may be used to force a battery cycle in progress and to bring it to the end of  
charge values. If the battery voltage level is higher, the charger is temporarily disconnected. If the  
battery level is lower, the charging current is increased up to the maximum in order to reach the set  
level as quickly as possible.  
New cycle {1141}  
Battery charging is a complex function that generally ends with a maintenance phase (floating) of  
indeterminate duration. The configurations below allow adjustment of the conditions that lead to  
the starting of a new charge cycle.  
Force new cycle {1142}  
This configuration allows a new charge cycle to be forced, and the bulk phase follows straight  
away.  
Voltage 1 for a new cycle {1143} and Duration at undervoltage 1 for a new cycle {1144}  
Voltage 2 for a new cycle {1145} and Duration at undervoltage 2 for a new cycle {1146}  
The battery voltage value, below which a new cycle is started, can be specified. The battery  
voltage must remain below this threshold for the duration that is also to be determined. Two  
voltages associated with two durations are configurable. Generally, a higher voltage is used with a  
longer duration and a lower voltage with a shorter duration.  
New priority cycle on the absorption and equalization phases {1149}  
Activate this configuration to accept or interrupt the absorption and equalization phases to start a  
new cycle. In the opposite case, even if the conditions are fulfilled for starting a new charge cycle,  
the battery charging proceeds normally by following the programmed phases.  
In the event of battery charging with renewable energy sources such as solar  
energy, for example, this configuration must remain deactivated (*no) in order to  
avoid cycles taking place too frequently.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Absorption phase {1451}  
During this phase, the battery accumulates the final percentages of the energy it is storing. This  
phase is carried out with a constant voltage.  
Authorised absorption {1155}  
This configuration determines whether or not the absorption phase is used. If this phase is  
deactivated, the charger goes directly to the authorised phase that follows it.  
Absorption voltage {1156}  
Use this configuration to adjust the voltage that is used for the absorption phase.  
Duration of absorption {1157}  
Use this configuration to adjust the duration of the absorption. The absorption phase starts once the  
set voltage {1156} is reached. When the duration has run out, the charger automatically goes to  
the authorised phase that follows it.  
Completion of absorption released by the current {1158}  
The absorption phase may be interrupted if the battery charge current automatically passes below  
a certain threshold. This may be used in order to limit the duration of the operation of a generator  
while there is an acceptable battery charge.  
During the absorption phase, as a matter of fact, the charge current reduces  
progressively. If the bulk charge has been carried out with a current correct for the  
battery, it is not necessary to adhere to a fixed duration to end the charging.  
Current at end of absorption {1159}  
Set the current value below which the absorption phase is considered to be at an end. When the  
current of the charger goes below this value, the next step starts.  
Equalization phase {1452}  
Certain types of battery require equalization in order to avoid the stratification of water and acid  
that they contain. Use the configurations below in order to adjust the usage conditions for this  
charge phase.  
During an equalization phase, a large quantity of gas is released that is highly  
explosive (hydrogen). Ensure that you adhere to the battery manufacturer’s  
instructions for this function. In all cases, ensure that there is sufficient ventilation  
around the batteries.  
During the equalization phase, the water of the battery is separated into gases  
(hydrogen and oxygen) and this action serves to decrease the level of liquid in the  
batteries. Check their level regularly.  
Start equalization {1162}  
Use this configuration to force the start of an equalization phase.  
It is only possible to force an equalization phase if the equalization is authorised.  
Once the phase has started, prohibiting the phase does not stop the equalization.  
To stop the equalization, use Force passage to maintenance (floating) or Force new  
cycle.  
Authorised equalization {1163}  
This configuration determines whether or not the equalization may be used on the installation.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Equalization before absorption phase {1291}  
This configuration determines in the charge cycle, in which equalization will be activated, if the  
equalization is carried out after or before the absorption phase. The equalization phase is carried  
out before the absorption phase by default.  
A. Equalization  
B. Absorption  
C. Floating  
Equalization current {1290}  
The equalization phase can be carried out with a limited current, which can be adjusted using this  
configuration. In all cases the current does not exceed that of the bulk charge phase {1138}  
Equalization voltage {1164}  
Set the voltage at which the equalization is carried out using this configuration.  
Duration of equalization {1165}  
Use this configuration to adjust the duration of the equalization. The equalization phase starts once  
the set voltage {1164} is reached. When the duration has run out, the charger automatically goes  
to the authorised phase that follows it.  
Number of cycles prior to equalization {1166}  
Equalization is not carried out at each charging cycle. This configuration allows the number of  
charging cycles to be adjusted where equalization is not active.  
Equalization at set intervals {1284]  
In the event of usage with few charge cycles, it may be necessary to carry out equalization cycles  
at set intervals and not with a number of set cycles. If this configuration is activated, a new battery  
charge cycle with an activated equalization phase with the programmed interval is started {1285}.  
Weeks between equalizations {1285}  
Use this configuration to determine the time intervals that separate the battery charge cycles with  
active equalization phases.  
Should incomplete charge cycles occur (for example, when charging using solar  
generators), this function is also useful in order to limit the frequency of equalization  
cycles.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
End of equalization activated by the current {1168}  
The equalization phase can be interrupted if the charge current of the battery goes under a  
certain threshold. This can be used to limit the operating period of a genset while keeping an  
acceptable battery charge.  
During the equalization phase, the charge current decreases progressively in a  
natural way. If the bulk charge has been achieved with a current suitable for the  
battery, it is not necessary to respect a fixed period to complete the charge.  
End of equalization current {1169}  
Set the current under which the equalization phase will be considered as completed. When the  
charge current goes under this value the next phase starts.  
Inverter configurations {1186}  
Use this menu to adjust the different inverter configurations.  
Standby level {1187}  
The standby function allows energy to be saved if there is no consumer present at the inverter  
output. In this case, the inverter disconnects its output and periodically emits a load search pulse. If  
a consumer is detected, it goes back into operational mode while measuring the power supplied  
and returns to standby if the consumer is deactivated.  
This configuration allows adjustment of the power output at which the inverter goes into standby  
mode.  
Proceed as follows to adjust this configuration:  
Make sure that the inverter mode is active (no voltage present at the AC In input). The input  
voltage is 0 and the input relay is indicated as open in real time on the information screen.  
Increase the standby level value {1187} to the maximum  
Activate the smallest consumer that can be detected and ensure that all the others are  
deactivated.  
Wait for the inverter to pass to standby, and the consumer then engages intermittently around  
once a second.  
Progressively reduce the standby level value {1187} until the consumer runs permanently. If the  
consumer works for several seconds then stops, decrease the value of the standby level again.  
An adjustment value between 0 and 100 is displayed. The value 100 represents the minimum  
sensitivity (biggest consumer detected).  
If you would like to deactivate the standby function, it is sufficient to adjust the  
detection level to 0. In this case, the Xtender remains permanently activated if it is  
working in inverter mode.  
Output voltage {1286}  
The output voltage can be adjusted using this configuration.  
In certain fields of application – for example, when the energy source is limited (solar  
or generator only) – it may be useful to reduce the output voltage of the inverter.  
This generally leads to a resulting reduction in the energetic consumption without  
significantly decreasing comfort. For example, a 100 W light bulb consumes around  
100 W at 220 V and 15% more at 230 V.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Level of battery under-voltage at no load {1108}  
Allows adjustment of the battery’s low  
voltage level at which the inverter and smart  
boost functions are deactivated. This  
adjustment is applied in the case of a zero  
charge and is automatically adapted with  
regard to the power required from the  
batteries. This configuration is a factory  
setting for lead-acid batteries. Poor  
adjustment of this value leads to early  
ageing of the batteries due to deep  
discharges.  
A. Battery voltage  
B. Duration of undervoltage before  
disconnection {1190}  
C. Disconnection due to undervoltage  
D. Undervoltage level {1108}  
Adjust this configuration using the technical data for your battery.  
The battery undervoltage level is automatically adapted to the instantaneous  
power of the consumers to compensate for internal losses in the battery and cables.  
Acoustic alarm of the battery under-voltage {1196}  
When the battery is discharged, the inverter stops in order to protect it from deep discharge. Before  
disconnecting, the inverter indicates this state via a message and activates the acoustic alarm.  
The alarm goes out when the inverter stops or after a defined duration {1469}  
Duration of the acoustic alarm {1469}  
The acoustic alarm stops automatically after a certain time and you can adjust the duration using  
this configuration.  
Combi configurations Inverter-Charger {1197}  
These configurations manage the combined  
functions between the charger and inverter.  
The conditions for passing from one function  
to another are adjusted in this category.  
A. Stoppage of charger operation {1309}  
B. Disconnection of transfer subject to  
delay {1199}  
C. Delay before opening of the transfer  
{1198}  
D. Immediate passage to the inverter  
threshold {1200}  
Minimum AC In voltage to authorise the charging {1309}  
In the event of sources with limited power output (such as a generator, for example) the use of  
strong consumers at the output may lead to a drop in voltage. The adjustment of this configuration  
allows disconnection of the battery charging function and thus maintains the power available to  
other consumers without influencing the voltage of the source.  
Transfer AC-In for delayed transfer opening {1199}  
This configuration determines the voltage below which the transfer relay will open after a certain  
period of time. The Xtender will then run in inverter mode.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Delay before passing to inverter {1198}  
When the input voltage is below the transfer voltage to the inverter, the transfer relay does not  
open immediately. With this configuration, the period during which the transfer remains drawn can  
be specified. After this duration, the transfer relay is opened and the inverter function is activated (if  
the function has not been blocked or deactivated).  
This delay is particularly useful on less stable grids or with generators with an output  
voltage that varies considerably during the activation of heavy loads.  
Immediate transfer AC-In voltage {1200}  
Use the adjustment of this configuration to adjust the critical voltage for the operation of  
equipment that must not experience interruptions. In the case of a fluctuating grid, if its voltage  
passes below the value of the configuration this immediately activates the inverter function,  
thereby ensuring supply to the consumers.  
Activate immediate detection of grid outage (UPS) {1435}  
This parameter allows to starting the inverter mode as quick as possible in case of fluctuations of the  
AC-In grid. This function is useful when it comes to very sensitive loads that require an uninterruptible  
power supply (UPS). If this function is active, being connected to a fluctuating source (weak grid or  
unstable generator) will lead to a frequent switching between inverter and charger modes by  
opening and closing of the transfer relay.  
Authorisation for exceeding the power sharing current without interrupting the transfer  
{1436}  
The parameter {1107} allows you to adapt the running of the Xtender to the maximum power of the  
source. In case this value is overrun, the transfer relay is not open and the circuit breaker on the  
source side may go on default. With this parameter you can force the transfer relay to open itself  
and the Xtender to work in inverter mode.  
Use this function if you have available a source that is smaller than the Xtender and  
if you don’t use the function Smart-Boost. In this way, in case of overload of the  
source, all the power is supplied by the Xtender, up to its own limits.  
Solsafe presence {1438}  
This parameter allows the connection on the AC-Out side of an inverter for grid feeding. It also  
authorizes the Xtender to accept the energy coming from the output and to use it to charge the  
batteries.  
Delay before closing of the transfer relay {1528}  
This parameter enables to delay the closing of the transfer relay even if the AC-In voltage is  
present.  
This function can be useful while working with gensets having a pre-warming delay.  
Configurations for auxiliary contacts 1 and 2 {1201} {1310}  
The Xtender inverter/charger is equipped with two auxiliary relays each with one free of potential  
contact (reverser). These two relays allow multiple functions to be carried out by using adequate  
cabling as well as simple programming.  
The programming of each contact is carried out independently except when conditions require  
the use of two relays. In this case, the programmed events for activating the second relay are  
automatically deactivated.  
The extended functions of the auxiliary contacts are described at the end of the chapter on simple  
functions.  
The auxiliary contacts are activated immediately in response to the programmed signals. When the  
activation conditions are no longer fulfilled, they are deactivated with a delay of 2 seconds to  
avoid overswitching.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
The auxiliary contacts respond to various signal types presented graphically below.  
The following types of basic events may activate the contacts:  
Simple event  
Scheduled event  
Level  
In the following description, each parameter has two reference numbers. The reference on the left  
relates to auxiliary contact 1 and the reference on the right to auxiliary contact 2 ({reference of the  
auxiliary contact 1} {reference of the auxiliary contact2}).  
Simple functions  
Switching mode {1202} {1311}  
The auxiliary contacts may be controlled in 4 different ways:  
Manual ON: In this mode, the contact is permanently drawn whatever the external conditions or  
programming  
Manual OFF: In this mode, the contact is permanently released whatever the external conditions or  
programming  
Automatic: In this mode, the auxiliary contact is activated according to the conditions and  
restrictions of its programming.  
Reversed automatic: In this mode, the conditions and restrictions define the release of the contact.  
Combination of events mode {1497} {1498}  
This configuration defines how the various events intended to activate the auxiliary contact are  
combined.  
Either a single event suffices to activate the contact (OR function) or it must have all the active  
events in order for the contact to be activated (AND function).  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
Limit the time of activation {1512} {1513}  
Maximum duration of activation {1514} {1515}  
When the conditions are met, either one or two relays are activated permanently. If you wish that  
the activation duration is limited in time, even if the conditions are met, you can activate this  
function. Once the relay is activated, a countdown runs according to the duration you have  
selected. Once this countdown is completed the relay is released, even if the conditions are still  
there. The relay can not be anymore activated as long as the activation conditions have not disap-  
peared.  
Temporal restrictions {1203} {1312}  
These configurations allow the time frame to be defined in which the contact should under no  
circumstances be activated. Three distinct schedules are accessible in the form of restriction  
programs (programs 1 to 3). For each program, it is possible to select the day of the week where  
the restriction is activated. If the day is selected it appears on the screen and if it is not selected it is  
represented on the screen by two horizontal lines.  
Once the days are selected, it is necessary to adjust the time frame where the restriction is active  
using the “starting time” and “finishing time” configurations. If the finishing time is programmed  
before the starting time, the restriction time frame is not taken into account. Below are the  
configurations with their references:  
Program 1 {1204} {1313}  
o
o
o
Days of the week {1205} {1314}  
Starting time {1206} {1315}  
Finishing time {1207} {1316}  
Program 2 {1208} {1317}  
o
o
o
Days of the week {1209} {1318}  
Starting time {1210} {1319}  
Finishing time {1211} {1320}  
Program 3 {1212} {1321}  
o
o
o
Days of the week {1213} {1322}  
Starting time {1214} {1323}  
Finishing time {1215} {1324}  
If your installer has made additional adjustments, it is possible that the restrictions  
could be active even if they do not appear in one of the three programs available  
to you.  
Contacts activated by an event {1455} {1456}  
The auxiliary contacts may be activated by the states or events occurring in the installation. Each  
event may be combined with another to establish complex functions.  
Xtender OFF {1225} {1333}  
The contact is activated if the Xtender inverter/charger is switched off, either following a fault or  
manually.  
Battery undervoltage alarm {1226} {1334}  
If the undervoltage threshold is reached, this activates the contact. In contrast to the acoustic  
alarm that is deactivated after a set time, this signal remains active as long as the battery voltage is  
below the threshold. If the undervoltage fault cuts in, this condition remains active as does the  
contact.  
Battery overvoltage {1227) {1335}  
Activates the contact in the event of battery overvoltage.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Inverter or smart boost overload {1228} {1336}  
Activates the contact in the event of an error due to excessive power in the inverter or the Smart  
Boost function. In the event that the inverter disconnects due to excess power and it is attempting  
to restart, the contact is not activated until the end of the attempts.  
Overtemperature {1229} {1337}  
Activates the contact in the event of overtemperature in the electronics or the transformer.  
No Overtemperature alarm {1520} {1521}  
Activates the auxiliary contact if the charger function is active. When the function Smart-Boost is  
running, the condition is not met to activate the contact.  
Active charger {1231} {1339}  
Activates the auxiliary contact if the charger function is active. When the smart boost function is  
operating, the condition for activating the contact is not fulfilled.  
Active inverter {1232} {1340}  
Activates the auxiliary contact if the inverter function is active.  
Smart boost active {1233} {1341}  
Activates the auxiliary contact if the smart boost function is active. For more information on the  
smart boost function, refer to the manual for the Xtender inverter/charger.  
AC In present with fault {1234} {1342}  
Activates the auxiliary contact if there is voltage present at the AC In input but this voltage does  
not fulfil the conditions for activating the transfer relay.  
AC In present {1235} {1343}  
Activates the auxiliary contact if a voltage is present at the AC In input. This condition is  
independent of the state of the transfer relay.  
Transfer relay drawn {1236} {1344}  
Activates the auxiliary contact if the transfer relay is drawn.  
AC Out present {1237} {1345}  
Activates the auxiliary contact if a voltage is present at the output of the Xtender inverter/charger.  
Battery charging in bulk charge phase {1238} {1346}  
Activate the auxiliary contact if the battery is in bulk charge phase.  
Battery charging in absorption phase {1239} {1347}  
Activates the auxiliary contact if the battery is in absorption phase. If the periodic extended  
absorption function is activated, the contact is also activated in this phase.  
Battery charging in equalization phase {1240} {1348}  
Activates the auxiliary contact if the battery is in equalization phase.  
Battery charging in floating phase {1242} {1350}  
Activates the auxiliary contact if the battery is in maintenance phase. If the extended reduced  
floating function is activated, the contact is also activated in this phase.  
Contacts activated by the battery voltage {1245} {1353}  
These configurations allow activation of the auxiliary contacts if the battery voltage passes below a  
selected voltage during a period that is configurable as well. Three voltages linked to three  
durations are configurable to activate the auxiliary contact.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
The auxiliary contact will only be activated after the battery exceeds again a certain voltage value  
and also after a duration, both independently of the activation parameters.  
This voltage and this duration are programmable too.  
Dynamic compensation of the thresholds {1288} {1354}  
Voltage 1 active {1246} {1355}  
Voltage 1 {1247} {1356}  
Duration 1 {1248} {1357}  
Voltage 2 active {1249} {1358}  
Voltage 2 {1250} {1359}  
Duration 2 {1251} {1360}  
Voltage 3 active {1252} {1361}  
Voltage 3 {1253} {1362}  
Duration 3 {1254} {1363}  
Voltage for deactivation of the auxiliary contact {1255} {1364}  
Duration over battery voltage for deactivation {1256} {1365}  
Deactivate if the battery is in floating mode {1516} {1517}  
Dynamic compensation of the thresholds {1288} {1354}  
If the contacts are activated according to the battery voltage, you can use the voltage  
compensated dynamically for each threshold.  
If this function is not activated, then the average battery voltage will be used.  
If this function is activated, the real battery voltage is compensated according to power used.  
Deactivate if the battery is in floating mode {1516} {1517}  
If you activate one of the auxiliary contacts according to the battery voltage, you can force the  
deactivation if the battery is in floating mode. In this way, even if the deactivation voltage is not  
reached or if the duration of the voltage deactivation is not completed, the auxiliary contact will  
be released.  
Contacts activated by inverter power or smart boost {1257} {1366}  
If the power output of the inverter exceeds a certain level, the contact may be activated. The  
exceedance is linked to a duration. Three power levels linked to three durations are configurable to  
activate the auxiliary contact.  
The auxiliary contact will only be activated after the output power passes below a value and  
during a duration, both independently of the activation configurations.  
If the smart boost function is active, these configurations are also taken into account with the  
power of the boost.  
Power 1 active {1258} {1367}  
Power 1 {1259} {1368}  
Duration 1 {1260} {1369}  
Power 2 active {1261} {1370}  
Power 2 {1262} {1371}  
Duration 2 {1263} {1372}  
Power 3 active {1264} {1373}  
Power 3 {1265} {1374}  
Duration 3 {1266} {1375}  
Power for deactivation of the auxiliary contact {1267} {1376}  
Duration below power for deactivation {1268} {1377}  
Contacts activated with set schedules {1269} {1378}  
The auxiliary contact can also be activated like a programmable clock. Three different weekly  
programs are available.  
For each program, the time frame may be applied to one or several days of the week.  
If the finishing time is programmed before the starting time, the time frame is not taken into  
account.  
Program 1 {1270} {1379}  
o
Days of the week {1271} {1380}  
o
Time of start of activation {1272} {1381}  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
o
Time of end of activation {1273} {1382}  
Program 2 {1274} {1383}  
o
o
o
Days of the week {1275} {1384}  
Time of start of activation {1276} {1385}  
Time of end of activation {1277} {1386}  
Program 3 {1278} {1387}  
o
o
o
Days of the week {1279} {1388}  
Time of start of activation {1280} {1389}  
Time of end of activation {1281} {1390}  
Extended functions {1489}  
Generator startup {1490}  
The two contacts may be combined in order to automatically start up a generator equiped with  
an electric starter. In this case the two contacts are dedicated to this function.  
Auxiliary contact 1 serves as an operational contact and auxiliary contact 2 as a startup contact.  
The startup condition of the generator must  
be programmed with the configurations of  
auxiliary contact 1. The startup is carried out  
by first activating the operational contact  
and then activating the startup contact. The  
latter engages several times, if necessary, to  
start up the motor. If a voltage appears at  
the terminals of AC In, the startup contact is  
released.  
A. Duration of starter impulse {1492}  
B. Duration between attempts {1494}  
C. Number of attempts {1493}  
Generator startup {1491}  
Activates the combination of the two auxiliary contacts for the generator start and the mana-  
gement of the start impulses.  
Duration of starter impulse {1492}  
With this configuration you can adjust the time at which the startup contact is activated.  
Number of startup attempts {1493}  
The startup contact is activated a limited number of times in order to protect the starter if the  
generator has a fault. Once the maximum number of startups has been reached, the operational  
contact is also deactivated. For a new attempt to be made the condition that generated the  
startup must disappear and reappear.  
Duration between the starter attempts {1494}  
This configuration determines the duration between the startup attempts. It also determines the  
duration between the activation of the operational contact and the first attempt at restarting.  
Multi Xtender {1282}  
This section allows setting the operating possibilities of systems with several Xtenders. Either parallel  
or 3-phase.  
3-phase integral mode {1283}  
If you activate this parameter, the system will work in order to have either a 3-phase output, or no  
output voltage. For instance in case of one phase overload, if the integral mode is activated, the  
cut of this phase will lead to the cut of all phases.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
INFORMATION ON THE SYSTEM  
The system information allows you to check the versions of the various elements of your installation.  
REMOTE CONTROLS  
You will receive information on the hardware and software versions for each remote control.  
Furthermore, you have access to its unique ID number. This unique number is marked FID followed  
by its ID.  
XTENDER  
For each Xtender connected at the remote control, you can consult the following information:  
the hardware version of the motherboard itself as well as the powerboard, the software version of  
the Xtender program and the unique ID of the Xtender. This unique number is also marked FID and  
followed by its ID.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
UPDATES  
The RCC remote control program as well as the code in the inverters/chargers of the Xtender series  
can be updated in order to integrate new features.  
For the RCC remote control it is also possible to implement new display languages (up to a  
maximum of 4 on each RCC remote control). You may obtain information about the availability of  
updates or additional languages from your installer or consult the website: www.studer-  
innotec.com.  
UPDATING PROCESS  
Before introducing the SD card to carry out the updating, do switch off all Xtenders  
(off).  
To carry out an update, enter the SD card containing the correct files in the RCC remote control  
slot intended for this.  
The system checks the compatibility of the hardware with the software present on the SD card and  
if it proves to be compatible the update is carried out automatically.  
The SD card must not be removed before the end of the updating process. Yet if the updating  
process is interrupted, the SD card has to be inserted again and the process will carry on.  
The steps of the updating process are the following:  
Updating the code of the remote control.  
Updating of the files of the remote control.  
Updating of the files of the inverters.  
Updating of the code of the inverters.  
The updating process takes 3 to 15 minutes, depending on the number of inverters connected to  
the remote control.  
Once the update has been carried out, the remote control displays the basic screen and you have  
immediate access to the new functions.  
When there is a change of language, the system restarts automatically with the new language as  
the current language.  
If the installation consists of several remote controls, each of them has to be updated separately.  
Beware: the updating will stop the running of all Xtenders connected to the remote  
control.  
COMPATIBILITY  
Studer Innotec guarantees the compatibility of the software updates with the hardware for one  
year, starting from the date of purchase. The updates are no longer guaranteed beyond this date  
and a hardware upgrade may be required. Please contact your reseller for any additional  
information on compatibility.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
APPLICATION EXAMPLES  
The examples below illustrate some implementation options for current installations. Useful  
configurations for these situations are also given. These are common and non-obligatory  
configurations.  
For more details on each configuration shown, please refer to the complete description given  
above in this manual.  
GÉNÉRAL USE : INVERTER, CHARGER WITH GRID  
Description:  
In this configuration, the Xtender is connected to a  
grid with high power output. The basic functions  
are configured for this type of application. The  
loads are supplied by the grid via the transfer relay  
and this helps to charge the battery. In the event  
of a disconnection from the grid, the transfer is  
stopped  
and  
the  
inverter  
is  
activated  
automatically.  
Associated current configurations:  
Battery charge current {1138} Adapt this configuration to the technical data for the batteries for  
the best charging capacity.  
Adjustment of the standby level {1187} Adjust this configuration if the minimum load has not  
been detected or, conversely, if the inverter remains engaged when all the loads have been  
deactivated.  
Additional configurations:  
Battery curve {1140} {1156} {1157} Adapt these configurations in order to adjust the voltage levels  
and the durations of charge to your battery manufacturer’s data.  
USE OF A LIMITED POWER SOURCE  
Description:  
For example, a source such as a generator, a  
camping or dock connection. In this case the  
power available is limited. In the case of high  
power consumers the source is insufficient and  
needs an assistance by means of the energy  
stored in the batteries.  
Associated current configurations:  
Maximum current of the AC source {1107} By adjusting this configuration to the maximum current  
that the source can supply, the power available is ideally shared between the battery charging  
and the consumers. For example, if a load is deactivated, the battery charger current is  
automatically increased.  
Locking: Smart boost active {1126} In the event that the maximum source current is exceeded,  
the inverter supplies the energy required to keep the source current at the set maximum level.  
Thus, the inopportune stopping of the generator is avoided, the circuit breaker of the dock or  
camping connection is not activated and the supply of the loads is assured.  
Option of exceeding the power sharing value without opening the transfer relay {1436}. Allows  
retention of the drawn transfer in the event of consumption of peak currents such as compressor  
startups.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
USE TO INCREASE THE POWER ON AN EXISTING INSTALLATION  
Description:  
The availability of an inverter or a inverter/charger  
allows its power to be extended with an Xtender  
connected in cascade. The maximum power of  
the first inverter is limited by the maximum current  
from the transfer relay of the Xtender.  
Associated current configurations:  
Maximum current of the AC source {1107} Adjust this configuration in relation to the maximum  
current that can supply the old inverter.  
Locking: Smart boost inactive {1126} Suppress the locking of this function: This way, when the first  
inverter has reached it maximum power, the power consumed that will be supplied by the  
Xtender could be increased.  
Locking: Inactive charger {1125} This lock, without which the battery energy would be taken by  
the first inverter, is returned by the Xtender charger. This would only have the effect of  
discharging the battery with losses caused in the two inverters or inverter/chargers.  
LOAD SHEDDING OF THE SECOND PRIORITY LOADS  
Description:  
Consumers with different supply priorities allow  
automatic disconnection of the supply to  
consumers of lower priority if the battery becomes  
weak. The supply of the priority loads is thus  
assured, such as lighting or computers, for  
example. In this case, the low-priority loads must  
be cabled via one of the auxiliary relays. The  
reference for the example below correspond to  
the auxiliary contact no 1.  
Associated current configurations:  
Communication mode {1202}  
Relay activated by the battery voltage {1245}  
Voltage 1 active {1246}  
Voltage 1 {1247}  
Duration 1 active {1248}  
Voltage for deactivation of the auxiliary relay {1255}  
Duration for deactivation {1256}  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
ANNEXES  
ANNEXE 1 : LIST OF CONFIGURATION INTERDEPENDENCIES  
N°  
Configuration  
N°  
Minimum limit by  
N°  
Maximum limit by  
1108 Undervoltage of the  
empty battery  
1109  
Undervoltage of the  
charged battery  
1110 Reactivation voltage  
after battery  
undervoltage  
1109 Undervoltage of the  
charged battery  
1108 Undervoltage of the  
empty battery  
1110 Reactivation voltage 1108  
after battery  
Undervoltage of the  
empty battery  
undervoltage  
1113 Activation  
temperature for  
1114  
Deactivation  
temperature for buzzer  
buzzer  
1114 Deactivation  
temperature for  
buzzer  
1113 Activation temperature  
for buzzer  
1115 Maximum operating 1116  
Restart temperature  
Temperature at which  
the charge current  
begins to reduce  
temperature  
1308  
1292  
Temperature for the  
start of the output  
correction (Uout)  
1116 Restart temperature  
1115 Maximum operating  
temperature  
1117 Activation  
temperature for  
ventilator speed 1  
1118  
1120  
Deactivation  
temperature for  
ventilator speed 1  
1118 Deactivation  
temperature for  
1117 Activation temperature  
for ventilator speed 1  
ventilator speed 1  
1119 Activation  
temperature for  
ventilator speed 2  
Deactivation  
temperature for  
ventilator speed 2  
1120 Deactivation  
temperature for  
1119 Activation temperature  
for ventilator speed 2  
ventilator speed 2  
1121 Maximum operating 1122  
voltage  
Reactivation voltage  
after battery  
overvoltage  
1122 Reactivation voltage  
after battery  
1121 Maximum operating  
voltage  
overvoltage  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
1115 Maximum operating  
1308 Temperature at  
which the charge  
current begins to  
reduce  
temperature  
1140 Battery maintenance  
voltage (floating)  
1156 Battery absorption  
voltage  
1152 Startup voltage of  
the timer before  
alarm  
1156 Battery absorption  
voltage  
1156 Battery absorption  
voltage  
1140  
1156  
Battery maintenance  
voltage (floating)  
1164 Battery equalization  
voltage  
Battery absorption  
voltage  
1172 Reduced  
maintenance  
voltage  
1140 “Battery maintenance  
voltage (floating)”  
1174 Periodic absorption  
voltage  
1172  
Reduced  
maintenance voltage  
1292 Temperature for the  
start of the output  
1115 Maximum operating  
temperature  
correction (Uout)  
1195 Adaptable maximum 1108  
low voltage  
Undervoltage of the  
empty battery  
1199 Transfer voltage to  
the inverter  
1200  
Immediate open  
critical threshold for  
the transfer (UPS)  
1200 Immediate open  
critical threshold for  
the transfer (UPS)  
1199 Transfer voltage to the  
inverter  
1255 Deactivation voltage 1247  
Voltage 1  
Voltage 2  
Voltage 3  
1250  
1253  
1267 Deactivation power  
1259 Power 1  
1262 Power 2  
1265 Power 3  
1364 Deactivation voltage 1356  
Voltage 1  
Voltage 2  
Voltage 3  
1359  
1362  
1376 Deactivation power  
1368 Power 1  
1371 Power 2  
1374 Power 3  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Studer Innotec  
NOTES  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RCC  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Flat Panel Television LC 30HV6U User Manual
Sharp Stereo System CD MPS600 User Manual
Shure Microphone 515BSLX User Manual