State Industries Water Heater SRT80 120NE User Manual

Rooftop Water Heater Model SRT80 120NE  
COMMERCIAL GAS WATER HEATER  
GAS-FIRED POWER BURNER  
FOR DOMESTIC HOT WATER  
• INSTALLATION • OPERATION • SERVICE • MAINTENANCE • LIMITED WARRANTY  
Thank you for buying this energy efficient water heater from  
State Industries. We appreciate your confidence in our  
products.  
WARNING: If the information in these  
instructions is not followed exactly, a fire  
or explosion may result causing property  
damage, personal injury or death.  
– Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
– WHAT TO DO IF YOU SMELL GAS:  
• Do not try to light any appliance.  
• Do not touch any electrical switch;  
CAUTION  
do not use any phone in your  
TEXT PRINTED OR OUTLINED IN RED CONTAINS  
INFORMATION RELATIVE TO YOUR SAFETY. PLEASE  
building.  
• Immediately call your gas supplier  
from a neighbor's phone. Follow the  
gas supplier's instructions.  
READ THOROUGHLY BEFORE INSTALLINGAND USING  
THIS APPLIANCE.  
• If you cannot reach your gas supplier,  
call the fire department.  
– Installation and service must be  
performed by a qualified installer,  
service agency or the gas supplier.  
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
PLACE THESE INSTRUCTIONSADJACENT TO HEATERAND  
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.  
PRINTED IN U.S.A. 1005  
PART NO. 197242-000  
SUPERSEDES PART NO. 196758-000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION INFORMATION  
OUTBACK  
0 btuh  
es: 0"  
s: 1.50"  
Sensitive  
nting required  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOREWORD  
This design complies with the current edition of ANSI Z21.10.3 as  
an automatic circulating tank type water heater and automatic  
storage water heater.  
In addition to these instructions, the equipment shall be  
installed in accordance with all local codes. The authority  
having jurisdiction should be consulted before installing.  
Detailed installation diagrams are found in this manual. These  
diagrams will serve to provide the installer with a reference for the  
materials and methods of piping necessary. It is highly essential  
that all water, gas piping and wiring be installed as shown on the  
diagrams.  
In the absence of local codes, the installation must comply  
with the current editions of the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54 and the National Electric Code, NFPA 70.  
The former is available from the Canadian Standards  
Association, 8501 East Pleasant Valley Road, Cleveland, OH  
44131, and both documents are available from the National  
Fire Protection Association, 1 Batterymarch Park, Quincy, MA  
02269.  
Particular attention should be given to the installation of  
thermometers at the locations indicated on the diagrams as these  
are necessary for checking the proper functioning of the heater.  
TABLE OF CONTENTS  
PAGE  
PAGE  
ROUGH-INDIMENSIONS ....................................................................  
INSTALLATION INFORMATION ...........................................................  
FOREWORD .......................................................................................  
FEATURES .........................................................................................  
Water Temperature Control...........................................................  
High Limit Switch (E.C.O.) .............................................................  
Dishwashing Machine Requirement .............................................  
Circulating Pump ............................................................................  
PLUMBING MANIFOLDASSEMBLY ...................................................  
Flow Diagram ................................................................................  
Automatic Air Bleed Valve ............................................................  
Hot Return Recirculation Pump .....................................................  
Drain Valve ....................................................................................  
AIR SYSTEMASSEMBLY ..................................................................  
Blower Assembly..........................................................................  
Blower Plenum ..............................................................................  
Air Hose ........................................................................................  
Flue Adapter ..................................................................................  
Exhaust Vent .................................................................................  
CONTROL SYSTEM ...........................................................................  
Blocked Outlet Switch ..................................................................  
Blocked Inlet/Prover Switch ..........................................................  
Low Gas Pressure Switch ...........................................................  
On/Off Switch ...............................................................................  
Hot Surface Igniter ........................................................................  
OIM - Outdoor Interface Module ...................................................  
WR Ignition Control Board .............................................................  
Low Water Cutoff Board and Probe ............................................  
Thermostat/E.C.O. Probes ............................................................  
Transformer ..................................................................................  
Junction Box .................................................................................  
TANKASSEMBLY SYSTEM ..............................................................  
Tank Insulation ...............................................................................  
CABINETASSEMBLY .........................................................................  
Cabinet Panels ..............................................................................  
ADDITIONAL CONTROLS ..................................................................  
Gas Valve ......................................................................................  
Flame Sensor ................................................................................  
INSTALLATION INSTRUCTIONS .........................................................  
Required Ability .............................................................................  
Insulation Blankets ........................................................................  
2
3
4
5
5
6
5
6
6
5
5
7
7
7
7
7
8
8
8
8
8
8
9
9
9
Chemical Vapor Corrosion ............................................................  
VENTING ............................................................................................  
Vent Terminals ...............................................................................  
Pressure Switches .......................................................................  
Gas Piping ..................................................................................... 15-16  
Connection of Gas Pipe ................................................................ 16  
Purging ..........................................................................................  
Gas Meter Size - City Gases Only ...............................................  
Gas Pressure Regulation ..............................................................  
Gas Valves....................................................................................  
SYSTEMCONNECTIONS ...................................................................  
Thermometers ...............................................................................  
Relief Valve ...................................................................................  
Water Line Connections ...............................................................  
Closed System ..............................................................................  
Water (Potable) Heating and Space Heating ................................  
Water Heater Wiring...................................................................... 17-18  
OPERATION ........................................................................................ 19-20  
Sequence of Operation ................................................................ 21  
Error Codes ...................................................................................  
Fault Conditions ............................................................................. 21-22  
PRIOR TO START-UP .........................................................................  
Required Ability .............................................................................  
OPERATINGINSTRUCTIONS ..............................................................  
14  
15  
15  
15  
16  
16  
16  
17  
17  
17  
17  
17  
17  
17  
21  
22  
22  
23  
Adjustment Procedure (Initial Start-Up) ........................................ 23-24  
9
9
Cathodic Protection .......................................................................  
Precautions ...................................................................................  
Lighting & Operating Label............................................................  
GENERALINFORMATION ..................................................................  
Power Burner ...............................................................................  
High Limit .......................................................................................  
High Altitude Installations ..............................................................  
24  
24  
25  
26  
26  
26  
26  
10  
10  
10  
10  
10  
10  
11  
11  
11  
11  
11  
11  
11  
11  
MAINTENANCE .................................................................................. 26  
General..........................................................................................  
Maintenance Schedule .................................................................  
Flushing .........................................................................................  
Draining .........................................................................................  
Sediment Removal.........................................................................  
26  
26  
26  
26  
26  
Lime Scale Removal ...................................................................... 26-27  
Anode Inspection and Replacement .............................................  
Drain Valve and Access Panels ...................................................  
Relief Valve ...................................................................................  
Circulating Pump ............................................................................ 27  
Vent System .................................................................................. 27  
INSTALLATION DIAGRAMS ............................................................... 28-32  
CHECKLISTAND SERVICE INFORMATION ........................................ 33  
TROUBLE-SHOOTING ........................................................................ 33-34  
REPLACEMENTPARTS ...................................................................... 34  
27  
27  
27  
Locating The Heater...................................................................... 11-12  
Provide Unit Support ..................................................................... 12  
Roof Curb ...................................................................................... 12-13  
Rig and Place Unit .........................................................................  
Outdoor Stand ...............................................................................  
Clearances ....................................................................................  
Hard Water ....................................................................................  
Air Requirements ..........................................................................  
13  
14  
14  
14  
14  
LIMITED WARRANTY .........................................................................  
35  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 1 shows the approximate time-to-burn relationship for  
normal adult skin. Short repeated heating cycles caused by small  
hot water uses can cause temperatures at the point of use to  
exceed the thermostat setting by up to 20°F/-11°C. If you experience  
this type of use, you should consider using lower temperature  
settings to reduce scald hazards.  
FEATURES  
IMPORTANT  
IT IS REQUIRED THAT A QUALIFIED SERVICE TECHNICIAN  
PERFORM THE INITIALFIRING OF THE HEATER.  
ACHECKLISTAND SERVICE INFORMATION section are included  
at the rear of this manual. By using this checklist the user may be  
able to make minor operational adjustments and save himself  
unnecessary service calls. However, the user should not attempt  
repairs which are not listed in this section.  
WATER TEMPERATURE CONTROL  
Temperature  
Setting  
Time to Produce 2nd & 3rd  
Degree Burns on Adult Skin  
180°F / 82°C  
170°F / 77°C  
160°F / 71°C  
150°F / 66°C  
140°F / 60°C  
130°F / 54°C  
120°F / 49°C  
Nearly instantaneous  
Nearly instantaneous  
About 1/2 second  
About 1-1/2 seconds  
Less than 5 seconds  
About 30 seconds  
More than 5 minutes  
DANGER  
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE  
THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT  
WATER TEMPERATURES REQUIRED FOR AUTOMATIC  
DISHWASHERAND LAUNDRY USE CAN CAUSE SCALD BURNS  
RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH.  
THE TEMPERATUREAT WHICH INJURY OCCURS VARIES WITH  
THE PERSON’S AGE AND TIME OF EXPOSURE. THE SLOWER  
RESPONSE TIME OF CHILDREN, THE ELDERLY OR DISABLED  
PERSONS INCREASESTHE HAZARDS TO THEM. NEVERALLOW  
SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW  
THEIR OWN BATH WATER. NEVER LEAVEACHILD OR DISABLED  
PERSON UNATTENDED INABATHTUB OR SHOWER.  
FIGURE 1  
Valves for reducing point-of-use temperature by mixing cold and  
hot water are available (see Figure 2). Also available are  
inexpensive devices that attach to faucets to limit hot water  
temperatures. Contact a licensed plumber or the local plumbing  
authority.  
THE WATER HEATER SHOULD BE LOCATED INANAREAWHERE  
THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET  
TEMPERATURES.  
The water temperature is controlled using the Touch Pad Buttons  
on the Display at the front of the unit (See Figure 1). This control  
utilizes two temperature probes to determine the tank temperature.  
The upper temperature probe is located on top of the unit in the  
back and the lower probe is located on the front center axis of the  
tank.  
The temperature may be adjusted from 70°F/21°C to 180°F/82°C.  
The thermostat was adjusted to 70°F/21°C before the heater was  
shipped from the factory. It is recommended that lower water  
temperatures be used to avoid the risk of scalding. It is further  
recommended, in all cases, that the water temperature be set for  
the lowest temperature which satisfies your hot water needs. This  
will also provide the most energy efficient operation of the water  
heater and minimize scale formation.  
SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C  
WILL REDUCE THE RISK OF SCALDS. Some states require  
settings at specific lower temperatures.  
FIGURE 2  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
HIGH LIMIT SWITCH (E.C.O.)  
The top immersion well of the upper probe also contains the high  
limit (energy cutoff) sensor. The high limit switch interrupts the  
main burner gas flow should the water temperature reach  
approximately 199°F/93°C.  
Should the high limit switch activate, it must be reset by cycling  
power to the unit. The water temperature must drop below 180°F/  
82°C before the controller can be reset.  
Continued manual resetting of the high limit control, preceded  
by higher than usual water temperature is evidence of high  
limit switch operation. For example, a malfunction of the control  
system allowing the gas valve to stay open could cause water  
temperature to rise until the high limit switch opens. Contact  
your dealer or servicer if continued high limit switch operation  
occurs.  
DISHWASHING MACHINE REQUIREMENT  
All dishwashing machines meeting the National Sanitation  
Foundation requirements are designed to operate with water  
flow pressures between 15 and 25 pounds per square inch  
(103 kPa and 173 kPa). Flow pressures above 25 pounds per  
square inch (173 kPa), or below 15 pounds per square inch  
(103 kPa), will result in improperly sanitized dishes. Where  
pressures are high, a water pressure reducing or flow  
regulating control valve should be used in the 180°F (82°C)  
line to the dishwashing machine, and should be adjusted to  
deliver water between these limits.  
The National Sanitation Foundation also recommends circulation  
of 180°F (82°C) water. Where this is done, the circulation should  
be very gentle so that it does not cause any unnecessary  
turbulence inside the water heater. The circulation should be  
just enough to provide 180°F (82°C) water at the point of take-  
off to the dishwashing machine. Adjust flow by means of the  
plug cock in the circulating line. (See INSTALLATION DIAGRAMS  
section.)  
CIRCULATING PUMP  
AUTOMATICAIR BLEED VALVE  
A circulating pump is used when a system requires a circulating  
loop or there is a storage tank used in conjunction with the heater.  
Refer to the piping diagrams at rear of manual for electrical hookup  
information and install in accordance with the current version of  
the National Electric Code NFPA No. 70.  
The tank assembly utilizes an automatic air bleed valve. The  
purpose for this automatic air bleed valve is to allow air to escape  
the tank when the unit is filled with water. When the unit is drained,  
the opposite occurs with the valve allowing air to replace the drained  
water. It removes the pressure vacuum that occurs in the system  
causing incomplete drainage. This valve is automatic which allows  
it to sense when the tank assembly is filled with water, see  
Figure 4.  
All bronze circulators are recommended for use with commercial  
water heaters.  
Although circulators are oiled and operated by the manufacturer  
some circulators must be oiled again before being operated.  
Please refer to manufacturer's instructions.  
PLUMBING MANIFOLD ASSEMBLY  
FLOW DIAGRAM  
The plumbing manifold assembly is composed of several  
components with each having a unique function. Please see  
Figures 3, 5, and 6 to observe the water flow to the plumbing  
manifold assembly and the components that make it up.  
FIGURE 4  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
HOT RETURN RECIRCULATION PUMP  
BLOWER ASSEMBLY  
The hot return recirculation pump circulates the hot water through  
the hot water line to eliminate delays at plumbing fixtures, see  
Figure 5.  
The blower assembly functions by pulling in air from outside the  
unit to supply to the burner assembly for proper combustion. The  
blower pushes the air through the burner assembly and heat  
exchanger where the flue gases then exit the exhaust system  
assembly, see Figure 8.  
FIGURE 5  
DRAIN VALVE  
The drain valve is used to drain the water from the tank assembly  
and plumbing manifold assembly, see Figure 6.  
FIGURE 8  
BLOWER PLENUM  
The blower plenum is used to draw air into the blower inlet. The  
inlet of the air system must maintain enough height from the ground  
to take into account yearly snow levels to prevent possible inlet  
vent blockage. The air plenum allows the blower to pull air into the  
unit from a higher inlet location to provide protection required, see  
Figure 9.  
FIGURE 6  
AIR SYSTEM ASSEMBLY  
The air system assembly is comprised of the blower assembly,  
blower plenum, air hose, and inlet vent terminal. This is where  
combustion air is acquired for combustion, see Figure 7.  
FIGURE 7  
FIGURE9  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIR HOSE  
CONTROL SYSTEM  
The air hose is used to provide a flexible air path from the blower  
to the burner assembly. It is held in place with two standard hose  
clamps, see Figure 10.  
The control system is comprised of an Outdoor Interface Module  
that monitors the functions of the WR ignition system, pressure  
switches, low water cutoff and temperatures in the tank.  
FIGURE 10  
FLUE ADAPTER  
The flue adapter is made of a flat metal plate with an exhaust  
adapter to mate with the exhaust elbow. This is where the flue  
gases exit the heat exchanger. This is a very hot region and is  
covered with a layer of high temperature fiberglass insulation, see  
Figure 11.  
FIGURE 13  
BLOCKED OUTLET SWITCH  
The Blocked Outlet Switch is set up to shut the unit off when a  
pressure buildup in the exhaust vent pipe occurs. This switch is a  
positive pressure switch that requires an increase in pressure to  
change the electrical contacts from normally closed to open. When  
this switch prevents the unit from igniting, most likely the exhaust  
is blocked. Check for obstructions in the exhaust venting and  
exhaust vent terminal, see Figure 14.  
BLOCKED INLET/PROVER SWITCH  
FIGURE 11  
The Blocked Inlet/Prover Switch is set up to shut the unit off when  
a reduction in pressure in the intake vent occurs. This switch is a  
negative pressure switch that requires an increase in negative  
pressure to change the electrical contacts from normally open to  
closed. The switch is connected to the pressure tap connected to  
the housing of the blower. When this switch prevents the unit from  
ignition, most likely the intake is blocked. Check for obstructions in  
the inlet vent terminal, see Figure 14.  
EXHAUST VENT  
The exhaust vent elbow mates with the flue adapter. The elbow  
mates with the exhaust terminal to dispose the flue gases to the  
outdoors. This venting section is covered with a fiberglass  
insulated wrap to protect from heat and condensation. These  
pipes are sealed with a high temperature gasket integral to the  
vent pipe fittings, see Figure 12.  
FIGURE 14  
The blocked Inlet/Prover Switch has a second function. It is provided  
on the heater to verify that the fan is operating. When the fan  
increases in negative pressure, the electrical contacts close  
signaling that the blower is operational and is at peak performance.  
The controller requires that the electrical contacts on the switch  
close before it will allow the blower to come on.  
FIGURE 12  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOW GAS PRESSURE SWITCH  
OIM - OUTDOOR INTERFACE MODULE  
The OIM is a device that monitors the control system. It monitors  
the ignition control assembly, the tank and outlet temperatures,  
the low water cutoff device, and the pressure switches. The display  
board provides operating information. It records and logs error  
messages for diagnostics. The module is equipped with a touch  
pad for easy access to observe menus and current status of  
control, see Figure 18.  
The Low Gas Pressure Switch is a single pole, normally open  
pressure switch that will close its contacts when a rising pressure  
of 6.2 inches (1.53 kPa) w.c. is encountered. The contacts will  
open when the pressure falls below the fixed set point of 6.2 inches  
of w.c. The Low Gas Pressure Switch monitors the gas supply  
pressure to the heater. If the gas supply falls below the 6.2 inches  
of w.c., the main burner is extinguished (if heater is running) or the  
heater will not start up, see Figure 15.  
FIGURE 15  
ON/OFF SWITCH  
FIGURE 18  
The ON/OFF Switch is a single pole, single throw rocker switch.  
This switch provides 120V from the electrical source to the heater,  
see Figure 16.  
WR IGNITION CONTROL BOARD  
The WR Ignition Control Board performs the ignition sequence for  
the water heater. It controls the diagnostics of the system and  
monitors all the pressure switches, the flame sensing device, the  
thermostats, the E.C.O., and components that make up the control  
system. The difference between the WR Ignition Control Board is  
that the OIM board monitors all the controls and provides that  
information through the LCD display where the WR Ignition Control  
Board provides the means to control the complete sequence of  
operation and switches, see Figure 19.  
FIGURE 16  
HOT SURFACE IGNITER  
The Hot Surface Igniter is a device that ignites the main burner by  
high temperature (1800°F). When the 120 VAC is applied to the  
igniter, sufficient heat is generated to ignite the main burner.  
Although improvements have been made to strengthen the igniter,  
it is still fragile and care must be taken when handling the igniter to  
prevent breakage, see Figure 17.  
FIGURE 17  
FIGURE 19  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
grounding screw to tie into the metal panel to assure the unit is  
grounded, see Figure 23.  
LOW WATER CUTOFF BOARD AND PROBE  
The Low Water Cutoff Board and Probe monitors the water level to  
confirm the tank is completely full. This function is very important  
when the unit is first filled with water and when complete loss of  
power is encountered during freezing temperatures (in case the  
unit drains while using the anti-freeze kit), see Figure 20.  
FIGURE 23  
TANK ASSEMBLY SYSTEM  
The Tank Assembly is an 80 gallon unit with a U-shaped heat  
exchanger. It incorporates two inlet tubes to control flow inside the  
tank. The heat exchanger is equipped with a stainless steel baffle  
which is non-removable. The working pressure is 150 psi, see  
Figure 24.  
FIGURE 20  
THERMOSTAT/E.C.O. PROBES  
The Outback utilizes a two probe system. The upper probe located  
on top of the unit toward the back of the cabinet consists of a  
thermostat and E.C.O. The thermostat monitors the top temperature  
in the tank. The E.C.O. high limit switch interrupts the main burner  
gas flow should the water temperature reach approximately 205°F.  
The lower probe measures the water temperature in the lower half  
of the tank assembly.  
FIGURE 24  
TANK INSULATION  
The tank assembly is wrapped in foam insulation sealed inside a  
round jacket. The ends of the tank consist of high temperature  
fiberglass insulation and foam dams to prevent foam leakage,  
see Figure 25.  
FIGURE 21  
TRANSFORMER  
The control system utilizes a 120/24 VAC step down transformer.  
Most of the control system utilizes 24 VAC for operation. See wiring  
diagram for those components utilizing 24 VAC and 120 VAC, see  
Figure 22.  
FIGURE 22  
JUNCTION BOX  
The junction box is where the 120 VAC is supplied to the unit and  
tied into the rest of the controls. The junction box provides a  
FIGURE 25  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLAME SENSOR  
CABINET ASSEMBLY  
CABINET PANELS  
The flame sensor is used to sense the burner flame. When there  
is sufficient flame, and the burner is properly grounded, the flame  
sensor signals back to the ignition board that the burner is operating  
properly and to maintain the operation of the gas valve until the  
thermostat is satisfied.  
There are five panels that comprise the cabinet assembly. The  
ends of the cabinet allow access to all controls and plumbing.  
Please confirm all joints are attached correctly and sealed to  
prevent water leakage inside the cabinet, see Figure 26.  
FIGURE 28  
INSTALLATION INSTRUCTIONS  
REQUIRED ABILITY  
INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRES  
ABILITY EQUIVALENTTO THAT OFALICENSED TRADESMAN IN  
THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS  
SUPPLYAND ELECTRICAL WORK ARE REQUIRED.  
FIGURE 26  
INSULATION BLANKETS  
ADDITIONAL CONTROLS  
GAS VALVE  
Insulation blankets available to the general public for external use  
on gas water heaters are not approved for use on your State  
water heater. The purpose of an insulation blanket is to reduce the  
standby heat loss encountered with storage tank water heaters.  
Your State water heater meets or exceeds the ASHRAE/IES 90.1b  
1999 standards with respect to insulation and standby loss  
requirements, making an insulation blanket unnecessary.  
The gas valve is used to supply the gas to the unit during heat up  
periods. The ignition control board monitors the thermostat's call  
for heat and sends a signal to the gas valve when to open to allow  
gas flow, see Figure 27.  
LOCATING THE HEATER  
WARNING  
THERE ISARISK IN USING FUEL BURNINGAPPLIANCES SUCH  
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER  
AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR  
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,  
OPERATED OR REPAIRED. FLAMMABLE VAPORSARE HEAVYAND  
TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE  
HEATER’S IGNITER OR MAIN BURNER FLAMES CAUSING FIRE  
OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF  
GAS APPLIANCES IF INSTALLED 18 INCHES (46 cm) OR MORE  
ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION  
IN SUCHANAREACANNOT BEAVOIDED.  
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS  
NOT SUBJECT TO PHYSICALDAMAGE BYAMOVING VEHICLE.  
DO NOT LOCATE THE HEATER WHERE NOISE FROM THE  
EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS  
INCLUDES LOCATIONS CLOSE TO ORACROSS FROM WINDOWS  
AND DOORS.  
FIGURE 27  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE29  
WARNING  
the unit full of water. (Full weight of approximately 1300 lbs. Add  
extra load and safety factors.) This is very important and the user's  
responsibility, see Figure 29. If you are uncertain as to the load  
bearing capability of the roof, consult a licensed structural  
engineering expert.  
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY  
OTHER POTENTIALFIRE HAZARDOUSARTICLES MUST NEVER  
BE PLACED ON OR ADJACENT TO THE HEATER. OPEN  
CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE  
STORED OR USED IN THE SAME ROOM WITH THE HEATER.  
The unit should be placed on a solid level roof curb of adequate  
strength. A properly designed roof curb is provided through  
State Order Entry.  
Water heater life depends upon water quality, water pressure and  
the environment in which the water heater is installed. Water  
heaters are sometimes installed in locations where leakage may  
result in property damage, even with the use of a drain pan piped  
to a drain. However, unanticipated damage can be reduced or  
prevented by a leak detector or water shutoff device used in  
conjunction with a piped drain pan. These devices are available  
from some plumbing supply wholesalers and retailers, and detect  
and react to leakage in various ways:  
IMPORTANT: THE WATER HEATER SHOULD BE EMPTYOF WATER  
DURING LIFTING. MAKE SUREALLFASTENERS ON THE BASE OF  
THE UNITARE IN PLACE DURING LIFTING.  
The location of the unit on the roof should be such that exhaust  
gas is not located near any air intakes or ventilation ducts.  
Provide a minimum of 36" on each side of the unit for servicing.  
Sensors mounted in the drain pan that trigger an alarm or turn  
off the incoming water to the water heater when leakage is  
detected.  
Plumbing connections for water are made from inside the building.  
Gas and electric connections are made from the rooftop. Remote  
control wiring passes through the leak-tight fitting in the base of  
the unit.  
Sensors mounted in the drain pan that turn off the water supply  
to the entire home when water is detected in the drain pan.  
ROOF CURB  
Water supply shutoff devices that activate based on the water  
pressure differential between the cold water and hot water  
pipes connected to the water heater.  
Assemble and install accessory roof curb in accordance with  
instructions shipped with curb.  
Devices that will turn off the gas supply to a gas water heater  
while at the same time shutting off its water supply.  
IMPORTANT: THE GASKETING OF THE UNITTO THE ROOF CURB  
IS CRITICAL FOR A WATER TIGHT SEAL. INSTALL GASKET  
SUPPLIED WITH THE ROOF CURB AS SHOWN IN FIGURE 30.  
PROVIDE UNIT SUPPORT  
Curb should be level. Refer to Accessory Roof Curb Installation  
Instructions for additional information as required.  
Before locating the unit on the roof, make sure the strength of the  
roof and beams are adequate at that point to support the weight of  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE30  
Be sure that unit is installed such that snow will not block the  
RIG AND PLACE UNIT  
combustion intake or flue outlet.  
Inspect unit for transportation damage. File any claim with  
transportation agency. Keep unit upright and do not drop. Spreader  
bars are not required if top crating is left on unit. Rollers may be  
used to move unit across the roof. Level the unit by using unit  
frame.  
Unit may be installed directly on wood flooring or on Class A, B, or  
C roof covering material when roof curb is used.  
Although unit is weatherproof, guard against water from higher  
level runoff and overhangs.  
Lifting holes are provided in base rails as shown in Figure 31. All  
panels must be in place when rigging.  
Exhaust vent terminal must have a minimum horizontal clearance  
of 4 ft. from electric and gas meters, gas regulators, and gas relief  
equipment. Minimum distance between unit and other electrically  
live parts is 48 inches.  
The unit cannot be placed on the curb with a fork lift or other lifting  
device through the fork lift openings. Doing so would interfere with  
placement on the roof curb.  
Flue gases can deteriorate building materials. Orient unit such  
that flue gas will not affect building materials.  
Maintain clearance around and above the unit to provide minimum  
distance from combustible materials, proper air flow, and service  
access.  
Adequate combustion and ventilation air space must be provided  
for proper operation of this equipment.  
Do not install unit in an indoor location. Do not locate unit air inlets  
near exhaust vents or other sources of contaminated air.  
After unit is in position, remove rigging skids and shipping  
materials.  
FIGURE31  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OUTDOOR STAND  
WARNING  
DO NOT USE THISAPPLIANCE IFANY PART HAS BEEN UNDER  
WATER. IMMEDIATELY CONTACT A QUALIFIED INSTALLER OR  
SERVICEAGENCY TO REPLACE A FLOODED WATER HEATER.  
DO NOTATTEMPTTO REPAIRTHE UNIT! ITMUST BE REPLACED!  
This rooftop water heater is approved for an outdoor installation  
with an optional stand. Contact State Order Entry to acquire  
optional stand kit.  
The rooftop stand is constructed of a tubular steel frame along  
with tubular steel legs. See Figure 32. The legs are three feet in  
length and slide into the corners of the tubular steel frame. The  
legs may be cut to length to reduce the overall height of the stand  
if necessary.  
CLEARANCES  
These heaters are approved for outdoor installations on  
combustible flooring (roof) with the minimum clearances of 0" for  
sides and 1.50" for top.  
The rooftop unit is located on the stand the same way as located  
on the roof curb. Please locate panels at one end of the stand.  
This area is used to run the water lines into the rooftop unit. It  
provides added protection to the water lines. For additional  
information see Optional Stand Kit Instructions.  
Always disconnect electrical power before servicing the unit.  
HARD WATER  
Where hard water conditions exist, water softening or the  
threshold type of water treatment is recommended. This will  
protect the dishwashers, coffee urns, water heaters, water  
piping and other equipment.  
See MAINTENANCE section for details of tank cleanout procedure.  
AIR REQUIREMENTS  
KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE  
MATERIALS, GASOLINEAND OTHER FLAMMABLE VAPORSAND  
LIQUIDS.  
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND  
VENTILATINGAIR.  
WARNING  
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR  
COMBUSTIONAND VENTILATION. AN INSUFFICIENTSUPPLY OF  
AIR WILL CAUSE RECIRCULATION OF COMBUSTION  
PRODUCTS RESULTING IN CONTAMINATION THAT MAY BE  
HAZARDOUS TO LIFE. SUCHACONDITION OFTEN WILLRESULT  
IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING  
CARBONING OR SOOTING OF THE COMBUSTION CHAMBER,  
BURNERS AND FLUE TUBES AND CREATES A RISK OF  
ASPHYXIATION.  
FIGURE32  
When installing the heater, consideration must be given to proper  
location. Location selected should be as close to the intake and  
exhaust termination points as practicable, with adequate air supply  
and as centralized with the piping system as possible.  
CHEMICAL VAPOR CORROSION  
WARNING  
LOCATE IT NEARADRAIN. THE HEATER SHOULD BE LOCATED  
IN AN AREA WHERE LEAKAGE FROM THE HEATER OR  
CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE  
ADJACENTAREAOR TO LOWER FLOORS OF THE STRUCTURE.  
CORROSION OF THE FLUE WAYS AND VENT SYSTEM MAY  
OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN  
CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN  
FAILUREAND RISK OFASPHYXIATION.  
When such locations cannot be avoided, it is recommended that a Spray can propellants, cleaning solvents, refrigerator and air  
conditioning refrigerants, swimming pool chemicals, calcium and  
sodium chloride, waxes, and process chemicals are typical  
compounds which are potentially corrosive.  
suitable drain pan, adequately drained, be installed under the  
appliance.  
State Water Heater provides an after market anti-freeze kit for use  
when there is a loss of power. This kit provides drainage to the  
tank and plumbing manifold to prevent freeze-up. When power is  
restored, the system is equipped with automatic air bleed and a  
low-water cut-off device to prove the tank is full of water prior to  
startup. See kit instructions for complete details.  
PRODUCTS OF THIS SORT SHOULD NOT BE STORED NEAR  
THE HEATER. ALSO,AIR WHICH IS BROUGHTIN CONTACTWITH  
THE HEATER SHOULD NOT CONTAIN ANY OF THESE  
CHEMICALS. IF NECESSARY, UNCONTAMINATEDAIR SHOULD  
BE OBTAINED FROM REMOTE OR OUTSIDE SOURCES.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The vent shall terminate a minimum of 12" (30.5 cm) above expected  
snowfall level to prevent blockage of vent termination.  
VENTING  
WARNING  
WARNING  
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST  
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR  
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE  
SOOTING OR RISKS OF FIREANDASPHYXIATION.  
USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT.  
TERMINATION OF A VENT SYSTEM WITH A DEVICE OTHER  
THAN THE SUPPLIED VENT TERMINATIONS WILL AFFECT  
SYSTEM PERFORMANCEAND RESULT INASAFETY HAZARD.  
WARNING  
PRESSURE SWITCHES  
NEVER OPERATE THE HEATER UNLESS IT IS VENTED TO  
THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID  
RISKS OF IMPROPER OPERATION, FIRE, EXPLOSION OR  
ASPHYXIATION.  
The SRT80-120NE is provided with three pressure switches.  
These switches are essential to the safe and proper operation of  
the unit. All switches are wired in series. The controller is set up to  
shut the unit down whenever there is a failure of any of the switches.  
CAUTION  
DO NOT TERMINATE THE VENTING WHERE NOISE FROM THE  
EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS  
INCLUDES LOCATIONS CLOSE TO ORACROSS FROM WINDOWS  
AND DOORS.  
CAUTION  
THE WATER HEATER IS POLARITY SENSITIVE. BEFORE  
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT  
SUPPLY NEUTRALWIRE TO GROUND CHECK INDICATES ZERO  
VOLTAGE.  
GAS PIPING  
Contact your local gas service company to ensure that adequate  
gas service is available and to review applicable installation codes  
for your area.  
TABLE 3  
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR  
(Based upon a Pressure Drop of 0.5 inch Water Column  
and 0.6 Specific Gravity Gas  
LENGTH  
IN  
NORMAL IRON PIPE SIZES (INCHES)  
INPUT IN THOUSANDS BTU/HR  
FEET  
1/2" 3/4" 1" 1 1/4" 1 1/2" 2"  
2 1/2"  
3"  
4"  
10  
175 360 680 1400 2100 3960 6300 11000 23000  
20  
30  
40  
50  
60  
70  
80  
90  
100  
125  
150  
175  
200  
120 250 485  
950  
770  
660  
580  
530  
490  
460  
430  
400  
360  
325  
300  
280  
1460 2750 4360 7700 15800  
1180 2200 3520 6250 12800  
990 1900 3000 5300 10900  
900 1680 2650 4750 9700  
810 1520 2400 4300 8800  
750 1400 2250 3900 8100  
690 1300 2050 3700 7500  
650 1220 1950 3450 7200  
620 1150 1850 3250 6700  
550 1020 1650 2950 6000  
200 375  
170 320  
151 285  
138 260  
125 240  
220  
205  
195  
175  
160  
145  
135  
500  
460  
430  
950 1500 2650 5500  
850 1370 2450 5000  
800 1280 2280 4600  
LENGTH  
IN  
NORMAL IRON PIPE SIZES (INCHES)  
INPUT IN KW  
METERS 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2"  
3"  
4"  
FIGURE 33  
3.0  
6.1  
51 105 199  
410  
278  
225  
193  
170  
155  
143  
135  
126  
117  
105  
95  
615 1160 1845 3221 6735  
35  
73  
59  
50  
44  
40  
37  
142  
110  
94  
83  
76  
70  
64  
60  
57  
51  
47  
42  
40  
428  
346  
290  
264  
237  
220  
202  
190  
182  
161  
146  
135  
126  
805 1277 2255 4626  
644 1031 1830 3748  
9.1  
VENT TERMINALS  
12.2  
15.2  
18.3  
21.3  
24.4  
27.4  
30.5  
38.1  
45.7  
53.3  
61.0  
556  
492  
445  
410  
381  
357  
337  
299  
278  
249  
234  
878  
776  
703  
659  
600  
571  
542  
483  
439  
401  
375  
1552 3192  
1391 2840  
1259 2577  
1142 2372  
1083 2196  
1010 2108  
952  
864  
776  
717  
688  
The vent system must terminate so that proper clearances are  
maintained as cited in local codes or the current edition of the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54.  
1962  
1757  
1610  
1464  
1347  
The SRT80-120NE series is designed with an internal vent  
construction. The exhaust vent terminal and the inlet air terminal  
are located on the sides of the appliance. Do not add vent pipe to  
the appliance, see Figure 33.  
88  
82  
Size the main gas line in accordance with Table 3. The figures  
shown are for straight lengths of pipe at 0.5 in. (125 kPa) W.C.  
pressure drop, which is considered normal for low pressure  
systems. Note that fittings such as elbows and tees will add to the  
pipe pressure drop.  
Assure the exhaust vent terminal is not in a public area where the  
hoods are exposed. The exhaust vent terminal gets very HOT  
during operation and can cause burns. Please use caution when  
working around the exhaust vent terminal.  
It is imperative that the area around the vent terminal hoods are  
kept clear from obstructions so plenty of fresh air is available for  
combustion.  
CAUTION  
DO NOT USE FLEXIBLE GAS PIPING.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
Apply joint compounds (pipe dope) sparingly and only to the male  
threads of pipe joints. Do not apply compound to the first two  
threads. Use compounds resistant to the action of liquefied  
petroleum gases.  
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER  
THAN 14.0" WATER COLUMN (1/2 POUND OR 3.45 kPa PER  
SQUARE INCH) SUPPLYGAS PRESSURE. HIGHER GAS SUPPLY  
PRESSURES REQUIRE SUPPLEMENTAL REDUCING SERVICE  
REGULATION. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE  
MAY CAUSE DAMAGE TO THE GAS CONTROLS WHICH COULD  
RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS  
OCCURRED SUCHAS THROUGH IMPROPER TESTING OF GAS  
LINES OR EMERGENCYMALFUNCTION OFTHE SUPPLY SYSTEM  
THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION.  
MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY  
REGULATORSANDTHE SAFETY VENTVALVESARE PROTECTED  
AGAINST BLOCKAGE. THESEARE PARTS OF THE GAS SUPPLY  
SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR  
DURING ICE STORMS.  
DISCONNECT THEAPPLIANCEAND ITS MANUAL GAS SHUTOFF  
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY  
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 kPa).  
GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED  
FROM THE HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45  
kPa). OR LESS, THEAPPLIANCE NEED NOT BE DISCONNECTED,  
BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST  
BY CLOSING THE MANUALGAS SHUTOFF VALVE.  
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR  
GAS LEAKAGE. USE SOAPAND WATER SOLUTION OR OTHER  
MATERIALACCEPTABLE FOR THE PURPOSE OF LOCATING GAS  
LEAKS. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER  
SOURCES OF IGNITION FOR THIS PURPOSE.  
ITIS IMPORTANTTO GUARDAGAINST GAS VALVE FOULING FROM  
CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAYCAUSE  
IMPROPER OPERATION, FIRE OR EXPLOSION.  
PURGING  
IF COPPER SUPPLY LINES ARE USED THEY MUST BE  
INTERNALLY TINNEDAND CERTIFIED FOR GAS SERVICE.  
Gas line purging is required with new piping or systems in  
which air has entered.  
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS  
PIPE IS CLEAN ON THE INSIDE.  
CAUTION  
PURGING SHOULD BE PERFORMED BY PERSONS  
EXPERIENCED IN THIS TYPE OF GAS SERVICE. TOAVOID RISK  
OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT ENTER  
CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR.  
THEAREAMUST BE WELLVENTILATEDANDALL SOURCES OF  
IGNITION MUST BE INACTIVATED OR REMOVED.  
TO TRAPANY DIRTOR FOREIGN MATERIALIN THE GAS SUPPLY  
LINE, ADIRT LEG (SOMETIMES CALLEDASEDIMENTTRAP OR  
DRIP LEG) MUST BE INCORPORATED IN THE PIPING. THE DIRT  
LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO  
FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH  
RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFERTO  
THE NATIONAL FUELGAS CODE.  
GAS METER SIZE - CITY GASES ONLY  
Be sure that the gas meter has sufficient capacity to supply the full  
rated gas input of the water heater as well as the requirements of  
all other gas fired equipment supplied by the meter. If the gas  
meter is too small, ask the gas company to install a larger meter  
having adequate capacity.  
GAS PRESSURE REGULATION  
Main line gas pressure to the water heater should be between a  
maximum 14.0" (3.45 kPa). W.C. and a minimum of 6.2 W.C. (1.53  
kPa).  
FIGURE 34  
The inlet gas pressure must not exceed the maximum value. A  
service regulator must be installed within 10' (305 cm) of unit.  
CONNECTION OF GAS PIPE  
GAS VALVES  
WARNING  
PERFORM THE GAS LEAKTESTANY TIME WORK IS DONE ONA  
GAS SYSTEM TO AVOID THE POSSIBILITY OF FIRE OR  
EXPLOSION WITH PROPERTY DAMAGE, PERSONAL INJURY OR  
LOSS OF LIFE.  
WARNING  
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAILTO  
SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO  
THEAPPLIANCE.  
The gas leak test is performed as follows: Paint pipe connections  
upstream of gas control with a rich soap and water solution to test  
for leaks before operating main burner. Bubbles indicate gas leak.  
To stop leak, tighten pipe connections. After piping connections  
are checked, turn on main burner. With main burner in operation,  
paint pipe joints (including flanges), pilot gas tubing connections  
and control inlet and outlet with rich soap and water solution.  
Bubbles indicate gas leak. To stop leak, tighten flange screws,  
joints and pipe connections. Replace part if leak can’t be stopped.  
SYSTEM CONNECTIONS  
The system installation must conform to these instructions and to  
the local code authority having jurisdiction. Good practice requires  
that all heavy piping be supported.  
THERMOMETERS (Not Supplied)  
To prevent damage, care must be taken not to apply too much Thermometers should be obtained and field installed as shown  
torque when attaching gas supply pipe to gas valve inlet. in the installation diagrams.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Thermometers are installed in the system as a means of detecting  
the temperature of the outlet water supply.  
bypass) is installed in the cold water line between the water heater  
and street main (or well).  
RELIEF VALVE  
Excessive pressure may develop causing premature tank failure  
or intermittent relief valve operation. This type of failure is not  
covered by the limited warranty. An expansion tank or a similar  
device may be required in the inlet supply line between the  
appliance and the meter or valve to compensate for the thermal  
expansion of water under supply pressure.  
This heater is equipped with an approved temperature and  
pressure relief valve. ASME ratings cover pressure relief. CSA  
ratings cover release rate with temperature actuation.  
FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF  
VALVE(S) MUST NOT BE REMOVED OR PLUGGED.  
Water heater damage due to installation in a closed system is not  
covered by the limited warranty. The solution is to install a thermal  
expansion tank between the check valve and the water heater.  
In addition to the appliance relief valve, each remote storage tank  
which may be used in conjunction with this appliance shall also  
be installed with a properly sized, rated and approved temperature  
(ANSI) and pressure (ASME) relief valve(s). This relief valve shall  
comply with the standard for relief valves and automatic gas shutoff  
devices for hot water supply systems, ANSI Z21.22.  
WATER (POTABLE) HEATING AND SPACE HEATING  
1. All piping components connected to this unit for space heating  
applications shall be suitable for use with potable water.  
2. Toxic chemicals, such as those used for boiler treatment,  
shall NEVER be introduced into this system.  
3. This unit may never be connected to any existing heating  
system or component(s) previously used with non-potable  
water heating appliance.  
4. When the system requires water for space heating at  
temperatures higher than required for domestic water  
purposes, a tempering valve must be installed. Please refer  
to installation diagrams on pages 29 through 33 in back of  
manual for suggested piping arrangements.  
Your local code authority may have other specific relief valve  
requirements.  
WARNING  
THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE  
PRESSURE OR TEMPERATURE INTO THE STEAM RANGE,  
WHICH MAY CAUSE SCALDINGATFIXTURES, TANK EXPLOSION,  
SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED  
BETWEEN THE RELIEF VALVEAND THE TANK.  
ADRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO  
DIRECT DISCHARGE TOASAFE LOCATION TOAVOID SCALDING  
OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM  
THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN  
VALVES OR RESTRICTIONS, NOR SHOULD IT BE LOCATED IN  
FREEZINGAREAS. DO NOT THREAD OR CAPTHE END OF THIS  
LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT  
THE PURPOSE OF THE VALVEAND IS UNSAFE. THE DISCHARGE  
LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE  
OF BOTH THE VALVEAND LINE.  
WATER HEATER WIRING  
IFANYOFTHEORIGINALWIREASSUPPLIEDWITHTHEAPPLIANCE  
MUST BE REPLACED, IT MUST BE REPLACED WITH 105C WIRE OR  
ITSEQUIVALENT, EXCEPTINTHEBURNERHOUSING. INTHISCASE  
USE 200°C WIRE.  
THE COMPUTER CONTROLREQUIRESASOURCE OF STABLE  
CLEAN ELECTRICITY FOR PROPER OPERATION. INSTALLING  
THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC  
NOISE, IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVELOR  
HAS AN APPLIANCE WHICH GENERATES EMF OF RFI  
INTERFERENCE CAN CAUSE THE CONTROLLER TO  
MALFUNCTION. AHIGH QUALITY POWER CONDITIONER MUST  
BE INSTALLED IF THE ABOVE CONDITIONS EXIST.  
MALFUNCTIONS CAUSED BYAPOOR ELECTRICALSUPPLYARE  
NOT COVERED UNDER YOUR WARRANTY.  
CAUTION  
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN  
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE  
IMPROPERAND DANGEROUS OPERATION.  
FIGURE 35  
WATER LINE CONNECTIONS  
CAUTION  
This manual provides detailed installation diagrams (see back  
section of this manual) for typical methods of application for the  
water heaters.  
VERIFY PROPER OPERATIONAFTER SERVICING UNIT.  
The controller is wired to the heater. The model and rating  
plate provides the electrical information needed to size the  
complete heater branch supply.  
The water heater may be installed by itself, or with a separate  
storage tank. When used with a separate storage tank, the  
circulation may be either by gravity or by means of circulating pump.  
When a circulating pump is used, it is important to note that the  
flow rate should be slow so that there will be a minimum of  
turbulence inside the heater.  
All electrical work must be installed in accordance with the  
National Electrical Code and local requirements.  
When installed, the appliance must be electrically grounded in  
accordance with local codes or, in the absence of local codes,  
with the National Electrical Code, NFPA 70.  
CLOSED SYSTEM  
CAUTION  
NOTE: This controller is polarity sensitive. If the hot and  
neutral supply voltage is reversed, the controller will not  
sense flame. Verify polarity before connecting the unit.  
A closed system will exist if a check valve (without bypass),  
pressure reducing valve (without bypass), or a water meter (without  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
MENU NAVIGATION  
The EMC-5000 Interface has 5 buttons on the touch panel of the interface.  
The EMC-5000's menus are navigated through the touch panel, as shown to  
the right, which can be found on the outdoor and remote interface box. Basic  
navigation through the menus begins with the Main Menu. With the exception  
of changing a user set point, touching {menu} will bring you to the Main Menu,  
as is illustrated here:  
> Temperatures  
System Status  
From the Main Menu, you can use the [up] and [down] arrow keys to navigate through the Main Menu. The arrow > on the left  
displays the current item that you have selected. Touching [select] will select the item from the menu and navigate to its  
appropriate sub menu. Navigation through the sub menus is the same as navigation through the Main Menu.  
Note: Some sub menus do not have the > visible, navigation through the screen operates through touching [up] and [down].  
The up and down arrows, and  
, found on the right of the screen are an indication that there are more items available on the  
current screen. As described above, touching [up] and [down] will allow you to display these items.  
The User Settings sub menu contains items that are adjustable by the user. These items can be adjusted by following these  
steps:  
1. Move the > to the items you wish to adjust by touching [up] and [down].  
2. Touch [select] to adjust the parameter.  
3. Touch [up] and [down] to adjust the value.  
4. Touch [select] to accept the new value, or touch [menu] to cancel any changes made.  
Changes will not be made until the [select} key is pressed again to accept the changed value.  
The following example steps through the process of adjusting the operating set point:  
1. Touch [menu] to display the Main Menu:  
> Temperatures  
System Status  
2. Touch [down] until User Settings is selected:  
System Status  
> User Settings  
3. Touch [select] to enter the User Settings sub menu:  
> Setpoint 120°F  
Diff  
20°F  
4. To adjust the operating set point, touch [select] once. The > should now be blinking indicating that you are adjusting this  
parameter.  
5. Touch [up] and [down] to adjust the parameter.  
6. Touch [select] again to accept the new parameter (or touch [menu] to return to cancel any changes and return to the previous  
setting).  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Menu Tree  
Main Menu  
Temperatures  
Outlet  
Description  
Displays the temperature of the outlet tank probe.  
Tank  
Displays the temperature of the probe located in the tank.  
System Status  
LWCO  
Low Water Cut-Off status. The status can be either Closed or Open. A Closed status indicates that there is not  
a low water condition in the tank. An Open status indicates that there is a low water condition in the tank.  
ECO  
Emergency Cut-Off status. The status can be either Closed or Open. A Closed status indicates safe operation.  
An Open status indicates that the system is locked out due to the water temperature reaching an unsafe  
temperature value.  
BlwPrv  
Blower prover status. The status can be either Closed or Open. A Closed status indicates that combustion air  
is adequate. An Open status indicates that combustion air is inadequate.  
Blk Out  
Low Gas  
Blocked outlet status. The status can be either Closed or Open. A Closed status indicates normal operation.  
An Open status indicates that the exhaust outlet is blocked.  
Low gas status. The status can be either Closed or Open. A Closed status indicates normal operation. An  
Open status indicates low supply gas pressure.  
Freeze State (Anti-Freeze kit only)  
This indicates the status of the freeze condition aquastat. The status can either be OK or Freeze. An OK  
status indicates normal operation. A Freeze condition indicates that freezing conditions exist and the system  
is responding.  
Tank Drain  
Tank Pump  
(Anti-Freeze kit only)  
Tank drain status. This status can either be Closed or Open. A Closed status indicates that the system is in  
normal operation and the tank drain valve is closed. An Open status indicates that the system is draining the  
tank to deter freezing.  
Status of the tank pump. This indicates if the tank pump is enabled by the control. The status is either On or  
Off. An On status indicates the control is asking for the tank pump to be turned on. An Off status indicates that  
the control is asking for the tank pump to be turned off.  
Loop Pumps Status of the loop pumps. This indicates if the loop pumps are enabled by the control. The status is either  
Enabled or Disabled. An Enabled status indicates the control is asking for the loop pumps to be turned on.  
A Disabled status indicates that the control is asking for the loop pumps to be turned off.  
User Settings  
Setpoint  
Diff  
The setpoint is the temperature to which water will be heated and stored. Allowable range is 100°F to 180°F.  
Temperature difference below the operating set point before the system will call for heat. Allowable range of  
0°F to 50°F.  
Temp Units  
Netwrt Addr  
Temperature unit of the system for display. This can either be °F or °C.  
(PC Networking only)  
Network address of the heater on State Industries Networking network. This number must be unique to all  
devices on the network. Allowable range of 1 to 32 on the network, or 0 to place the device off the network.  
Log Info  
Run Min  
Cycles  
The total number of minutes of heating.  
The total number of cycles the heater achieved. A cycle is defined as a transition from an idle state to a heat  
state.  
kBTU  
(for reference only)  
This is a factory setting for reference only.  
Prop Rev  
Current Error  
Error History  
This will display the current software revision.  
The current error screen displays the current error, if the system is in an error state.  
The error history screen will display the previous nine recorded errors by the system along with the running  
minutes of when the error occurred.  
Reload Defaults Allows for re-setting the system to its factory defaults.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the control will automatically return to step 5 and repeat the  
entire operating cycle. During this entire process, if the control  
detects an improper operating state for external devices such  
as the ECO switch, blower prover switch, etc., the appropriate  
indication will be given on the interface modules.  
SEQUENCE OF OPERATION  
1. When the control is powered up the outdoor interface and the  
remote interface should display a blank line and copyright on  
the 2-line display.  
2. After one second, the display should switch to indicate that the  
touch switches are calibrating. During this process, the  
Running LED will flash once per second until all of the switches  
have been calibrated. This is an automatic process and can  
take several seconds. Placing hands or fingers near the  
switches can delay this process.  
ERROR CODES  
These error codes will be displayed if there is a problem with  
ignition or operation of the heater. They will be displayed on the  
LCD screen on the outdoor interface module and the remote  
interface module.  
3. The control is now initialized and the display will change to  
display the temperatures screen if no error is detected.  
The following error codes are codes related to the temperature  
probes:  
4. The system is checked for faults and, if detected, the Service Outlet Probe  
light will flash. If the fault is a temperature probe fault, the Service  
LED will remain on without flashing. Whenever a fault is  
Tank Probe  
detected, the display will switch to display the Current Error  
screen.  
The following error codes are related directly to the Ignition Module:  
I.M. Lock Out  
I.M. PS Closed  
I.M. PS Open  
I.M. ECO  
5. If the control determines that the actual water temperature  
inside the tank is below the programmed temperature setpoint  
less the differential, a call for heat is activated. This call for heat  
is generated even if the ignition module has detected an error,  
however, if the ignition module has detected a fault, the ignition  
sequence will not advance. Provided that no fault has been  
detected, the Running LED will turn on.  
I.M. 115V Reversed  
I.M. Low Flame  
I.M. Igniter  
6. If the Low-Water Cut-Off is satisfied, the ignition module will  
then perform selected system diagnostic checks. This includes  
confirming the proper state of the air switches and the ECO  
limit device.  
I.M. Flame Fault  
Note: The ignition module faults are only reset after a one hour  
delay period after the fault, or by cycling the power.  
7. If all checks are successfully passed, the combustion blower  
is energized for the pre-purge cycle.  
FAULT CONDITIONS  
Fault: OUTLET PROBE  
There is a problem with the outlet temperature probe  
8. When the pre-purge cycle is complete, power is applied to the  
igniter element for the igniter warm-up period.  
Possible Cause  
Remedy  
9. At the conclusion of the igniter warm-up period, the gas valve  
will open, allowing gas to enter the burner chamber.  
1. Outlet temperature probe  
is not connected (Wiring  
disconnect)  
1. Check that the temperature  
probe is connected properly  
10. The igniter will remain on for a short predetermined time period,  
then it will be turned off.  
2. Outlet temperature probe  
wiring is open or closed  
2. Repair wiring  
3. Replace probe  
11. The control will monitor the flame sense probe to confirm a  
flame is present. If a flame is not verified within the  
predetermined flame prove time, the gas valve will immediately  
be closed and the blower will continue to run for approximately  
10 seconds. The control will then return to step 6.  
3. Defective outlet  
temperature probe  
Fault: TANK PROBE  
12. If a flame is confirmed, the control will enter the heating mode  
where it will continue heating the tank until the setpoint  
temperature is reached. At this point, the gas valve is closed  
and the control enters the post-purge cycle.  
There is a problem with the tank temperature probe  
Possible Cause Remedy  
1. Tank temperature probe is 1. Check that the temperature  
13. The combustion blower will run for the duration of the postpurge  
cycle to purge the system of all combustion gasses. When the  
post purge cycle is complete, the blower is deenergized and  
will coast to a stop.  
not connected (Wiring  
disconnect)  
probe is connected properly  
2. Tank temperature probe  
wiring is open or closed  
2. Repair wiring  
14. The control will now enter the standby state as indicated by the  
Standby LED. The control will continue to monitor the tank  
water temperature and the state of the other system devices. If  
the temperature drops below the setpoint value less differential,  
3. Defective tank temperature 3. Replace probe  
probe  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The following are fault conditions related to the ignition module: Fault: I.M. IGNITER  
There is a problem with the ignition module  
Fault: I.M. LOCK OUT  
I.M Failed an internal hardware or software check  
Possible Cause  
Remedy  
Possible Cause  
Remedy  
1. Igniter is not wired in or  
the wiring is damaged  
1. Check that the igniter is  
wired in properly or that  
the wiring is not damaged  
1. Ignition Module Failure  
1. Replace Ignition Module  
Fault: I.M. PS CLOSED  
The pressure switch is stuck closed  
2. Igniter is damaged  
2. Replace igniter  
Possible Cause  
Remedy  
3. The ignition module is  
damaged  
3. Replace ignition module  
1. Pressure switch is shorted 1. Check and replace wiring  
or not wired properly  
Fault: I.M. FLAME FAULT  
A flame was detected when there is not supposed to be a flame  
(no call for heat).  
2. Defective pressure switch 2. Replace pressure switch  
Fault: I.M. PS OPEN  
The pressure switch is stuck open  
Possible Cause  
Remedy  
Possible Cause  
Remedy  
1. Flame sense wiring is  
damaged  
1. Check and repair wiring  
1. Pressure switch is not  
connected  
1. Check that the pressure  
switched is wired properly  
2. Ignition module is  
damaged  
2. Replace ignition module  
2. Pressure switch is open or 2. Check and repair wiring  
not wired properly  
3. Defective pressure switch 3. Replace pressure switch  
PRIOR TO START UP  
4. Insufficient pressure  
developed by combustion  
blower  
4. Verify blower operation  
to the ignition module  
REQUIRED ABILITY  
Fault: I.M. ECO  
INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRES  
ABILITY EQUIVALENT TO THAT OFALICENSED TRADESMAN IN  
THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS  
SUPPLYAND ELECTRICAL WORKARE REQUIRED.  
Emergency cut-off, water temperature has reached an unsafe  
temperature  
Possible Cause  
Remedy  
1. Temperature probe is  
damaged  
1. Check that the temperature  
probe is not damaged and  
replace probe if necessary  
Before attempting start-up, thoroughly study and familiarize yourself  
with the exact sequence of operation and all other details on the  
specific heater being used.  
2. Temperature probe wiring 2. Check and repair wiring  
is damaged  
The power burner is equipped with an ignition system which  
automatically sequences prepurge and ignition, senses and  
ignites main burner flame and sequences burner operation. Heater  
is equipped with an ignition control which locks out after three  
unsuccessful ignition attempts. Familiarize yourself with the  
sequence of operation of this unit prior to start-up.  
3. Water in tank too hot  
3. Normal condition when  
water temperature exceeds  
safety limit. Allow water  
to cool or admit water into  
tank and manually reset the  
control. Determine cause  
for over temp condition  
Be certain that the water heater is full of water, that air is purged  
from all lines, there are no leaks (gas and water), and all inlet  
water lines are open.  
Fault: I.M. 115V REVERSED  
The line hot and the neutral line are reversed wired  
The following test equipment should be on hand (all test equipment  
must be acclimated to ambient temperature before calibration and  
use.)  
Possible Cause  
Remedy  
1. Line hot and neutral  
reversed  
1. Check wiring and reverse  
line hot and neutral  
Two U-tube manometers or calibration 0-10" (0-2.5 kPa) and  
0-35" (0-2.5 kPa) W.C. pressure gauges.  
Fault: I.M. LOW FLAME  
Low flame has been sensed  
Attach a gas pressure gauge or manometer to the upstream  
side of main gas cock and a gas pressure gauge or manometer  
to the manifold pressure tap.  
Possible Cause  
Remedy  
1. Weak or insufficient flame 1. Check flame rod  
detected  
You are now ready to begin the burner start-up procedure.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Check manifold pressure (see Table 4) using a pressure gauge  
(manometer) connected to the manifold pressure tap on the  
gas control valve.  
OPERATING INSTRUCTIONS  
IMPORTANT  
ITIS RECOMMENDED THATAQUALIFIED SERVICE TECHNICIAN  
PERFORM THE INITIAL FIRING OF THE HEATER. AT THIS TIME  
THE USER SHOULDASK THE TECHNICIANANY QUESTIONS IN  
REGARDTO THE OPERATIONAND MAINTENANCE OFTHE UNIT.  
If full rate adjustment is required, remove cover screw from top of  
the gas control valve.  
Using a small screwdriver, turn adjusting screw clockwise  
increase or counterclockwise to decrease gas pressure to  
obtain 4.5" (1 kPa) for natural gas Water Column.  
to  
CAUTION  
BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT,  
MAKE SURE HEATER AND SYSTEM ARE FILLED WITH WATER  
ANDALLAIR IS EXPELLED FROM HEATERAND PIPING.  
3. Cycle the burner on and off several times to check its operation.  
4. Check the operation of the limit and operating controls.  
5. Check the input rate:  
NEVER OPERATE THE HEATER WITHOUTFIRSTBEING CERTAIN  
IT IS FILLED WITH WATER AND A TEMPERATURE AND A  
PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE  
OPENING OF THE HEATER. DO NOT ATTEMPT TO OPERATE  
HEATER WITH COLD WATER INLET VALVE CLOSED.  
For appliance installation locations with elevations above 2000  
feet (610 m) refer to HIGH ALTITUDE INSTALLATIONS section of  
this manual.  
FILLING:  
1. Close the heater drain valve.  
a. Attach a pressure gauge (manometer) to the manifold  
pressure tap and refer to Table 4, page 26 for correct  
pressure.  
2. Open a nearby hot water faucet to permit the air in the system  
to escape.  
b. Use this formula to “clock” the meter. Be sure other gas  
consuming appliances are not operating during this interval.  
3. Fully open the cold water inlet pipe valve allowing the heater  
and piping to be filled.  
3600 X H = Btuh  
T
4. Close the hot water faucet as water starts to flow.  
5. The heater is ready to be operated.  
Should it be necessary to adjust the gas pressure to the  
burner, to obtain the full input rate, the steps below should  
be followed:  
THE MAIN MANUAL GAS SHUTOFF VALVE MUST HAVE BEEN  
CLOSED FORATLEAST FIVE (5) MINUTES. THIS WAITING PERIOD  
IS AN IMPORTANT SAFETY STEP. ITS PURPOSE IS TO PERMIT  
GAS THAT MIGHT HAVEACCUMULATED IN THE COMBUSTION  
CHAMBER TO CLEAR. IF YOU DETECT GAS AT THE END OF  
THIS PERIOD, DO NOT PROCEED WITH LIGHTING. RECOGNIZE  
THAT GAS ODOR, EVEN IF IT SEEMS WEAK, MAY INDICATE THE  
PRESENCE OFACCUMULATED GAS SOMEPLACE IN THEAREA  
WITH A RISK OF FIRE OR EXPLOSION. SEE THE FRONT PAGE  
FOR STEPS TO BE TAKEN.  
T = Time in seconds to burn 1 cubic foot of gas. (With a stopwatch  
read the gas meter and measure the amount of time required  
for the heater to consume 1 cubic foot of gas.)  
H = Heating value of gas (in Btu’s per cubic foot of gas).  
Btuh = Actual heater input rate, in Btuh.  
EXAMPLE: (Using RTF-120 heater)  
DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER  
WATER. IMMEDIATELY CALLAQUALIFIED SERVICE TECHNICIAN  
TO INSPECT THE HEATERAND TO REPLACEANY PART OFTHE  
CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS  
BEEN UNDER WATER.  
T = 18.9 seconds  
3600 X 1050 = 199,900 Btuh (59 kW)  
18.9  
H = 1050 Btu/ft.3  
LIGHT THE UNIT IN ACCORDANCE WITH THE OPERATING  
INSTRUCTIONS LABELATTACHED TO THE HEATER.  
For high altitude installations, compare result to the derated input  
required for the elevation at the installation location.  
THESE INSTRUCTIONSARE REPEATED IN THE LIGHTING AND  
OPERATING LABEL ILLUSTRATION IN THIS MANUAL.  
c. Remove the pressure regulator cover screw and adjust the  
pressure by turning the adjusting screw with a small  
screwdriver. Do not exceed 4.5" (1 kPa) Water Column.  
INITIAL START-UP  
Clockwise to increase gas pressure and input rate.  
A minimum gas supply pressure of 6.2" W.C. for natural gas is  
required before making any adjustment to the gas control pressure  
regulator. Attempts to adjust the regulator during periods of low  
gas supply pressure could result in overfiring of the heater when  
the gas supply pressure returns to normal.  
Counterclockwise to decrease gas pressure and input  
rate.  
d. “Clock” the meter as in step (b) above.  
1. Check gas line pressure with a manometer.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
e. Repeat steps (c) and (d) until the specified input rate is is present, there will probably be an unusual sound such as air  
achieved.  
escaping through the pipe as the water begins to flow. There should  
be no smoking or open flame near the faucet at the time it is open.  
f. Turn the manual gas valve to “OFF”. Replace the pressure  
regulator cover screw. Remove the pressure gauge or  
manometer from the manifold pressure tap. Replace the set  
screw in the manifold pressure tap. If the gas pressure  
regulator cannot be adjusted to give the full input rating with  
sufficient gas pressure at the valve, check to ensure the unit  
is equipped with the correct orifice.  
PRECAUTIONS  
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT  
OPERATE HEATER UNTILALLCORRECTIVE STEPS HAVE BEEN  
MADE BYAQUALIFIED SERVICEMAN.  
1. FLOODING TO OR ABOVE THE LEVEL OF THE BURNER OR  
CONTROLS  
WARNING  
UNDER NO CIRCUMSTANCES SHOULD THE INPUT EXCEED  
THE RATE SHOWN ON THE HEATER RATING PLATE.  
OVERFIRING COULD RESULT IN DAMAGE OR SOOTING OF THE  
HEATER.  
2. EXTERNAL FIRING  
3. DAMAGE  
4. FIRING WITHOUT WATER  
5. SOOTING  
CATHODIC PROTECTION  
CAUTION  
NEVER OPERATE THE HEATER WITHOUTFIRST BEING CERTAIN  
IT IS FILLED WITH WATER AND A TEMPERATURE AND  
PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE  
OPENING OF THE HEATER.  
HYDROGEN GAS CAN BE PRODUCED INAHOT WATER SYSTEM  
SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A  
LONG PERIOD OF TIME (GENERALLYTWO WEEKS OR MORE).  
HYDROGEN GAS IS EXTREMELY FLAMMABLE. To reduce the risk  
of injury under these conditions, it is recommended that a hot  
water faucet be opened for several minutes before using any  
electrical appliance connected to the hot water system. If hydrogen  
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAILTO  
SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO  
THEAPPLIANCE.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING:IF YOU DO NOT FOLLOW THESE INSTRUCTIONS  
EXACTLY, AFIRE OR EXPLOSION MAYRESULT CAUSING  
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.  
BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATERANDAIR PURGED FROMALL LINES.  
A. This appliance does not have a pilot. It is equipped with an C. Use only your hand to push in or turn the gas control knob.  
ignitor device which automatically lights the burner.  
Never use tools. If the knob will not push in or turn by hand,  
don’t try to repair it, call a qualified service technician. Force or  
attempted repair may result in a fire or explosion.  
Do not try to light the burner by hand.  
B. BEFORE OPERATING smell all around the appliance area  
for gas. Be sure to smell next to the floor because some gas  
is heavier than air and will settle on the floor.  
D. Do not use this appliance if any part has been under water.  
Immediately contact a qualified installer or service agency to  
replace a flooded water heater. Do not attempt to repair the  
unit! It must be replaced!  
WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not touch any electric switch;  
do not use any phone in your building.  
Immediately call your gas supplier from a neighbor’s phone.  
Follow the gas supplier’s instructions.  
If you cannot reach your gas supplier, call the fire department.  
OPERATING INSTRUCTIONS  
1.  
STOP! READ THE SAFETY INFORMATION  
ABOVE ON THIS LABEL.  
5. Push in control knob slightly and turn clockwise  
to "OFF".  
6. Wait five (5) minutes to clear out any gas. If you smell gas,  
STOP! Follow "B" in the safety information above on  
this label. If you don't smell gas, go on to the next step.  
2. Set the thermostat to lowest setting.  
2. Turn off all electrical power to the appliance.  
4. This appliance is equipped with a device which automatically  
7. Turn gas control knob counterclockwise  
to "ON".  
lights the burner. Do not try to light the burner by hand.  
8. Turn on all electric power to the appliance.  
9. Set thermostat to desired setting.  
10. If the Appliance will not operate, follow the instructions "To  
Turn Off gas to Appliance" and call your service technician or  
gas supplier.  
GAS CONTROL KNOB  
TO TURN OFF GAS TOAPPLIANCE  
1. Set the thermostat to lowest setting.  
2. TURN OFF ALL ELECTRICAL POWERTOTHE APPLIANCE IF SERVICE ISTO BE PERFORMED.  
3. Push in gas contol knob slightly and turn clockwise  
to "OFF", do not force.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE SCHEDULE  
GENERAL INFORMATION  
Following are the instructions for performing some of the  
recommended maintenance. Unit inspection and adjustment  
should be performed by a competent technician.  
POWER BURNER  
The SEQUENCE OF OPERATION is provided on page 21 and the  
INITIAL START-UP procedure of the unit on page 23.  
FLUSHING  
HIGH LIMIT  
1. Turn off the heater electrical disconnect switch.  
2. Open the drain valve and allow water to flow until it runs clean.  
3. Close the drain valve when finished flushing.  
The high limit switch (not adjustable) is factory set to cutout at  
199°F (93°C). The controller must be manually reset by cycling the  
power to the unit and the water temperature must be below  
180°F (82°C).  
4. Turn on the heater electrical disconnect switch.  
DRAINING  
TABLE 4  
Maintenance and service procedures may also require draining  
the heater.  
GAS SUPPLY SPECIFICATIONS  
Max. Gas Supply Pressure W.C.  
Nominal Gas Supply Press. W.C  
Minimal Gas Supply Press. W.C.  
RTF-120 Natural Gas  
14.0 (3 kPa)  
7.0 (1.74 kPa)  
1. Turn off the heater electrical disconnect switch.  
2. Close the cold water inlet valve to heater.  
6.2 (1.53 kPa)  
3. Open a nearby hot water faucet to vent the system.  
4. Open the gate valve on plumbing manifold.  
Manifold Press. W.C.  
4.5 (1 kPa)  
5. If the heater is being drained for an extended shutdown, it is  
suggested the drain valve be left open during this period.  
• Follow FILLING instructions when restoring hot water service.  
HIGH ALTITUDE INSTALLATIONS  
WARNING  
THE SRT80-120E IS CERTIFIED FOR USE WITHOUTMODIFICATION  
FOR ALTITUDES UP TO 2000 FEET. INSTALLATIONS ABOVE 2000  
FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE IN  
ACCORDANCEWITHTHENATIONALFUELGASCODE(ANSIZ223.1/  
NFPA 54). FAILURE TO REPLACE THE ORIFICE WILL RESULT IN  
IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE,  
PRODUCING CABON MONOXIDE GAS IN EXCESS OF SAFE LIMITS,  
WHICHCOULDRESULTINSERIOUSPERSONALINJURYORDEATH.  
SEDIMENT REMOVAL  
Waterborne impurities consist of the particles of soil and sand  
which settle out and form a layer of sediment on the bottom of the  
tank.  
For convenience, sediment removal and lime scale removal  
should be performed at the same time.  
Some gas utility companies derate their gas for altitude, making it  
unnecessary to install high altitude orifices. Call the local gas or  
utility company to verify BTU content.  
LIME SCALE REMOVAL  
The amount of calcium carbonate (lime) released from water is  
in direct proportion to water temperature and usage. The higher  
the water temperature or water usage, the more lime deposits  
are dropped out of the water. This is the lime scale which forms in  
pipes, heaters and on cooking utensils.  
Due to the input rating reduction at high altitudes, the output rating  
of the appliance is also reduced and should be compensated for  
in the sizing of the equipment for applications.  
MAINTENANCE  
Lime accumulation not only reduces the life of the equipment but  
also reduces efficiency of the heater and increases fuel  
consumption.  
GENERAL  
KEEPAPPLIANCEAREACLEARAND FREE FROM COMBUSTIBLE  
MATERIALS, GASOLINEAND OTHER FLAMMABLE VAPORSAND  
LIQUIDS. (SEE WARNING ON PAGE 11, LOCATINGTHE HEATER).  
The usage of water softening equipment greatly reduces the  
hardness of the water. However, this equipment does not  
always remove all of the hardness (lime). For this reason it is  
recommended that a regular schedule for deliming be  
maintained.  
Water heater maintenance includes periodic tank flushing and  
cleaning, and removal of lime scale. The unit should be inspected  
and adjusted to maintain proper combustion. Refer to the following  
table. A periodic inspection of the venting system should be made.  
Where used, the water circulating pump should be oiled.  
The depth of lime buildup should be measured periodically.  
Heaters will have about 3" (7.6cm) of lime buildup when the level  
of lime has reached the bottom of the cleanout opening or about  
1" (2.5cm) of lime buildup if it has reached the drain valve opening.  
A schedule for deliming should be set up, based on the amount  
of time it would take for a 1" (2.5cm) buildup of lime.  
COMPONENT  
Tank  
OPERATION  
INTERVAL  
REQUIRED  
Sediment Removal  
Lime Scale Removal Semi-Annually UN-LIME® Delimer  
Monthly  
Flushing  
Tank  
Anode Rods  
Inspect  
Inspect  
Oiling  
Semi-Annually  
Semi-Annually  
Four Months  
Replace as  
Required  
Example 1:  
Relief Valve  
Initial six-month inspection shows 1/2" (1.3cm) of lime  
accumulation. Therefore, the heater can be delimed once  
a year.  
Circulating  
Pump (1)  
SAE No. 20  
non-detergent  
motor oil  
Blower  
Clean Inlet Screen  
and Blower Wheel  
As Required  
Soft Brush  
Example 2 :  
Vent System  
Inspect  
Every 3 Months Joints should  
be sealed  
Initial six-month inspection shows 2" (5cm) of lime  
accumulation. Therefore, the heater should be delimed every  
3 months.  
(1) If furnished with oiling provision.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sediment and lime scale removal may be accomplished through  
the cleanout opening furnished on the heater. The heater must  
be drained, see DRAINING, before removing cleanout cover on  
tank.  
DRAIN VALVEAND ACCESS PANELS  
The heater is equipped with a 3/4" drain valve.  
An access panel covers the front of the tank.  
To dissolve and remove the more stubborn mineral deposits,  
SRT80-120NE UN•LIME® Professional Delimer should be used.  
RELIEF VALVE  
At least twice a year, the temperature and pressure relief valve  
should be checked to ensure that it is in operating condition. To  
check the relief valve, lift the lever at the end of the valve several  
times. The valve should seat properly and operate freely.  
SRT80-120NE UN•LIME® Professional Delimer is an easy to  
handle patented food grade acid formulated specifically for lime  
scale removal from all types of water using equipment. Available  
in 1 gallon (3.8L) (part no. 4763) and 5 gallon (19L) (part no.  
4813) sizes. Hydrochloric base acids are not recommended for  
use on glass-lined tanks.  
If water does not flow, remove and inspect for obstructions or  
corrosion. Replace with a new valve of the recommended size as  
necessary. Inspection of the valve should be performed at least  
every three years. Do not attempt to repair the valve, as this could  
result in improper operation and a tank explosion. In areas with  
poor water conditions, it may be necessary to inspect the T&P  
valve more often than every three years.  
SRT80-120NE Form No. 4800, entitled “Why, When and How”,  
describes tank cleaning methods and materials. UN•LIME and  
the booklet may be obtained through your State dealer or  
distributor.  
To clean heater through cleanout opening, proceed as follow:  
CAUTION  
BEFORE MANUALLY OPERATING THE VALVE, MAKE SURE THAT  
ADRAIN LINE HAS BEENATTACHED TO THE VALVE TO DIRECT  
THE DISCHARGE TOAN OPEN DRAIN. FAILURE TO TAKE THIS  
PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT  
WATER PASSING OUT THE VALVE DURING THIS CHECKING  
OPERATION.  
1. Turn off water inlet valve, the heater electrical disconnect switch  
and open gate valve.  
2. Drain the tank.  
3. Remove cover from cleanout opening on front of tank assembly.  
4. Remove lime, scale or sediment using care not to damage  
the glass-lining.  
5. Inspect cleanout plate gasket.  
6. Install cleanout plate. Be sure to draw plate up tight by  
tightening screws securely.  
7. Close gate valve, open water inlet line and turn on the power  
burner electrical disconnect switch.  
If the temperature and pressure relief valve on the heater  
discharges periodically or continuously, it may be due to thermal  
expansion of water in a closed water supply system, or, it may be  
due to a faulty relief valve.  
8. Check for water leakage.  
Thermal expansion is the normal response of water when it is  
heated. In a closed system, thermal expansion will cause the  
system pressure to build until the relief valve actuation pressure is  
equaled. Then, the relief valve will open, allowing some water to  
escape, slightly lowering the pressure.  
ANODE INSPECTION AND REPLACEMENT  
This water heater is equipped with a sacrificial anode. Anodes  
protect the glass-lined tank from corrosion by sacrificing  
themselves through electrolysis. When the anode material is  
consumed, there is no more protection and corrosion of the tank  
accelerates  
Water heater damage due to installation in a closed system is  
not covered by the limited warranty. The solution is to install a  
thermal expansion tank between the check valve and the water  
heater.  
Inspection of the anode every 6 to 12 months allows you to identify  
a spent anode and replace it. Replace the anode when its  
diameter is 3/8" (1cm) of an inch, or annually which ever is first.  
Aggressive, very hot and softened water causes rapid  
consumption of the anode requiring frequent inspections. Anodes  
are available from your distributor or State Industries.  
ABOVEALL, DO NOTPLUGTHE TEMPERATUREAND PRESSURE  
RELIEF VALVE. THIS IS NOTA SOLUTION AND CAN CREATE A  
HAZARDOUS SITUATION.  
CIRCULATING PUMP  
To inspect or replace an anode:  
The water heating system includes several circulating pumps.  
It should be lubricated as directed by the circulator  
manufacturer.  
The anodes on this heater are easily accessible from the front of  
the heater making replacement simple and quick.  
1. Turn the heater off per the lighting instructions.  
2. Open the drain valve to flush any sediment out of the bottom of  
the heater.  
3. Shut off the cold water supply. Make sure all hot water fixtures  
and circulating pumps are turned off.  
VENT SYSTEM  
Examine the vent system every 3 months. Points of inspection are  
as follows:  
4. Make sure tank is drained. Remove the anode using a socket  
of the appropriate size. Do not use an impact wrench.  
5. Inspect and replace the anode as required. Use a pipe tape  
or sealant when reinstalling the anode.  
6. Close the drain valve. Open a hot water fixture to allow air to  
escape. Open the cold water supply to heater and allow the  
tank to fill. Follow the lighting instructions.  
1. Check for obstructions and/or deterioration of vent terminals.  
2. Vent from screen should be cleaned of foreign material and  
soot. The screen is located inside the vent outlet and is  
accessible from the outside of the hood. Do not reach inside  
the vent terminal when the heater is in operation.  
3. Check all vent system connections for leakage and reseal as  
required using Hi Temp Silicone sealer or equivalent (inside  
cabinet).  
7. Check your anode and drain valve for leaks.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION DIAGRAMS  
ONE TEMPERATURE - ONE HEATER VERTICALSTORAGE TANK FORCED CIRCULATION  
WITH OR WITHOUT BUILDING RECIRCULATION  
CAUTION: IF BUILDING COLD WATER SUPPLYHAS ABACK-FLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL  
EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED  
NOTE: CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP (IF USED) TO COLD WATER INLET LINE.  
* PIPE TO OPEN DRAIN  
INSTALL IN ACCORDANCE WITH LOCAL CODES  
ONE TEMPERATURE - ONE HEATER HORIZONTAL STORAGE TANK  
FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION  
DANGER  
T
S
T
IF
N
O
W
*P
IN
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE  
WITH OR WITHOUT BUILDING RECIRCULATION  
DANGER  
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5. IF HIGHER  
PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.  
CAUTION: IF BUILDING COLD WATER SUPPLYHAS ABACK-FLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL  
EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.  
*PIPE RELIEF VALVE TO OPEN DRAIN.  
NOTE: IF TEMPERED WATER IS RECIRCULATED, RETURN LINE SHOULD BE CONNECTED AT POINT “A”.  
INSTALL IN ACCORDANCE WITH LOCAL CODES.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE  
WITH OR WITHOUT BUILDING RECIRCULATION  
TWO TEMPERATURE - THREE HEATERS (TWO PRE-HEATERS/ONE BOOSTER HEATER)  
WITH OR WITHOUT BUILDING RECIRCULATION  
FOR MULTIPLE HEATER INSTALLATION SEE MANIFOLD KIT  
SPECIFICATIONS.  
DANGER  
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE  
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE  
CONTROL WARNING ON PAGE 5. IF HIGHER PREHEAT  
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE  
BOOSTER OUTPUT,ADDANANTI-SCALD VALVE FOR HOTWATER  
SUPPLIED TO FIXTURES.  
CAUTION: IF BUILDING COLD WATER SUPPLYHASABACK-FLOW  
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK  
VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN  
THE HOT WATER SYSTEM MUST BE PROVIDED.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)  
WITH OR WITHOUT BUILDING RECIRCULATION  
* PIPE RELIEF VALVETO OPEN DRAIN  
DANGER  
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE  
** 140°F (60°C)TO 150°F (66°C) SHOULD BE MAXIMUM WATER  
TEMPERATUREMAINTAINEDINTHEPRE-HEATERS.  
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE  
CONTROL WARNING ON PAGE 5. IF HIGHER PREHEAT  
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE  
BOOSTER OUTPUT,ADDANANTI-SCALD VALVE FOR HOTWATER  
SUPPLIED TO FIXTURES.  
120°F (49°C) SHOULD BE THE MINIMUMTEMPERATURE OF WATER  
INTHEPRE-HEATERS.  
CONNECT CIRCULATING LINE FROM FIXTURES, IF USED,TO COLD  
WATER SUPPLY LINE OF PRE-HEATER.  
CONNECTCIRCULATINGLINEOF180°F(82°C)ORBOOSTEDWATER,  
IF USED, TO INLETWATER LINETO BOOSTER.  
INSTALL INACCORDANCE WITH LOCALCODES.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE  
WITH RECIRCULATION OF SANITIZING LOOP  
NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER  
DANGER  
CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHER.  
TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE RINSE  
OPERATION AND OPEN (OFF) WHEN DISHWASHER IS NOT  
OPERATING OR WHEN ON LONG STANDBY.  
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE  
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE  
CONTROL WARNING ON PAGE 5. IF HIGHER PREHEAT  
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE  
BOOSTER OUTPUT,ADDANANTI-SCALD VALVE FOR HOTWATER  
SUPPLIED TO FIXTURES.  
NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN  
UNINSULATED TEE BEYOND THE DISHWASHER TAKEOFF IN  
THE SANITIZING LOOP. CONTROL SHOULD BE SET AT 185°F  
(85°C).  
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-  
FLOW PREVENTER, CHECK VALVE OR WATER METER WITH  
CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF  
WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.  
NOTE 3: ADJUST PLUG COCK SOTHE SANITIZING LOOP FLOW  
RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE  
TANK.  
*PIPE RELIEF VALVE TO OPEN DRAIN.  
NOTE 4: IF TEMPERED WATER IS RECIRCULATED, RETURN  
INSTALL IN ACCORDANCE WITH LOCAL CODES.  
LINE SHOULD BE CONNECTED AT POINT A.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER HEATER MAKES SOUNDS  
CHECKLIST AND SERVICE INFORMATION  
IMPORTANT  
1. Sediment or lime scale accumulations cause rumbling and  
pounding noises when the heater is operating.  
The installer may be able to observe and correct certain problems  
which might arise when the unit is put into operation or when it  
is re-fired after a prolonged shutdown. HOWEVER, it is  
recommended that only qualified servicemen, using appropriate  
test equipment, be allowed to service the heater.  
The sounds are normal, however, the tank bottom should  
be cleaned. Refer to MAINTENANCE for details.  
2. Some of the electrical components of the water heater make  
sounds which are normal.  
BE SURE TO TURN OFF THE ELECTRICITY WHENEVER  
POSSIBLE ORAPPROPRIATE WHILE CHECKING EQUIPMENT.  
Contacts click or snap as the heater starts and stops.  
Transformers often hum.  
WARNING  
WATER LEAKAGE IS SUSPECTED  
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN  
SERIOUS PERSONAL INJURY OR DEATH.  
1. Check to see if the water heater gate valve is tightly closed. Also  
check the cleanout opening for leakage.  
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION  
WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE  
IMPROPERAND DANGEROUS OPERATION.  
2. The apparent leakage may be condensation which forms on  
cool surfaces of the heater and piping.  
VERIFY PROPER OPERATIONAFTER SERVICING.  
3. If the outlet of the relief valve is leaking it may represent:  
• Excessive water pressure.  
BURNER OPERATIONAL PROBLEMS  
1. Refer to TROUBLESHOOTING.  
• Excessive water temperature.  
• Faulty relief valve.  
NOT ENOUGH OR NO HOT WATER  
Excessive water pressure is the most common cause of relief  
valve leakage. It is often caused by a “closed system”. If a check  
valve is in the inlet system it will not permit the expanded hot water  
volume to equalize pressure with the main. The relief valve must  
release this water or the water heater or plumbing system will be  
damaged. Refer to MAINTENANCE-RELIEF VALVE section in this  
manual.  
1. Be certain the electrical disconnect switch serving the water  
heater is in the ON position.  
2. Check the fuses.  
The electrical disconnect switch usually contains fuses.  
3. The capacity of the heater may have been exceeded by a large  
demand for hot water.  
Water heater damage due to installation in a closed system is not  
covered by the limited warranty. The solution is to install a thermal  
expansion tank between the check valve and the water heater.  
Large demands require a recovery period to restore water  
temperature.  
4. Colder incoming water temperature will lengthen the time  
required to heat water to the desired temperature.  
TROUBLE-SHOOTING  
If the heater was installed when incoming water temperature  
was warm, colder water creates the effect of less hot water.  
1. Verify that all vent terminals are free of debris.  
2. Check supply wire polarity - hot to hot and neutral to neutral and  
no "stray" current in neutral.  
5. Look for hot water wastage and leaking or open hot water  
faucets.  
3. Heater is properly grounded.  
6. Sediment or lime scale may be affecting water heater operation.  
Refer to MAINTENANCE for details.  
Checking these four (4) items first will often result in a timely  
solution to the service call.  
7. The heater’s temperature high limit sensor has activated. Reset  
high limit.  
WARNING  
JUMPING OUT COMPONENTS AND/OR CIRCUITS DURING  
TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH  
THE UNIT’S OPERATING SEQUENCEAND IGNITION SAFETY. IF  
YOU DO NOT HAVETHE PROPER TEST EQUIPMENT, I.E.AVOLT-  
OHM METER AND A MICROAMMETER, DO NOT ATTEMPT TO  
TROUBLESHOOT OR REPAIR.  
8. Burner may not be firing at proper rate.  
Check gas pressure. Adjust to obtain required manifold  
pressure.  
9. Burner fan wheel may be dirty.  
ALTERING THE CONTROLLER AND/OR CONTROLLER  
WIRING IN ANY WAY COULD RESULT IN INTERNAL DAMAGE  
TO THE MODULE CIRCUITS, POSSIBLY ALTERING THE  
IGNITION SEQUENCE ALLOWING GAS VALVES TO OPEN  
BEFORE THE HOT SURFACE IGNITER IS UP TO IGNITION  
TEMPERATURE.  
Clean fan wheel with a stiff brush.  
WATER IS TOO HOT  
1. Refer to WATER TEMPERATURE CONTROL.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If there is 24V AC at the gas valve during the four second ignition  
trial and the manifold pressure does not increase above 0"  
W.C. then verify that the manual gas control valve is in the “ON”  
position. If the valve is in the “ON” position and the previous  
voltage and gas pressure conditions are met, then the gas  
valve is defective and must be replaced.  
NOTE: ANY BYPASS ORALTERATION OF THE UNITS SAFETIES  
WILLRESULT IN VOIDING THEAPPLIANCE WARRANTY.  
Before performing any troubleshooting familiarize yourself with  
the particular appliance.  
Refer to the SEQUENCE OF OPERATION on page 21 before  
continuing.  
Note that a positive manifold pressure reading of approximately  
1.5" (.38 kPa) W.C. is normal during the prepurge portion of the  
ignition cycle due to the location of the gas orifice.  
Make sure the appliance is connected to a 120V AC power supply,  
manual gas valve is in the ON position, and all electrical  
connections are secure before continuing to troubleshoot this  
appliance.  
MOTOR RUNS, BURNER LIGHTS MOMENTARILY,  
THEN LOCKS OUT  
1. Reset the appliance two more times to ensure that all of the air  
has been purged from the gas line.  
CAUTION  
THE WATER HEATER IS POLARITY SENSITIVE. BEFORE  
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT  
SUPPLY NEUTRALWIRE TO GROUND CHECK INDICATES ZERO  
VOLTAGE.  
2. If the burner lights momentarily but does not sustain ignition,  
verify that the inlet pressure is not greater than 14.0" (3.5 kPa)  
W.C. or lower than the minimal gas supply pressure, as shown  
in Table 4: that is, 6.0" for Natural Gas. Also, the manifold  
pressure should rise during the three (3) second trial for  
ignition. If the manifold pressure is not correct then adjust  
accordingly. See ADJUSTMENT PROCEDURE in OPERATING  
INSTRUCTIONS section, page 18, for the manifold pressure  
adjustment procedure.  
3. Check for the reversed polarity in the supply wiring. This  
controller is polarity sensitive. If the hot and neutral supply wires  
are reversed, the controller will not sense flame. Reverse the  
supply wires and try to fire the unit.  
BLOWER MOTOR WILL NOT RUN  
1. Confirm 120V AC to the controller. Also, to verify correct polarity,  
check for 120 V AC between hot supply and ground.  
If there is no voltage, check for a loose connection where it  
connects to the controller.  
2. If there is 120 volts to the controller, check for loose connections  
or a locked rotor. If the rotor cannot be freed the motor and  
blower assembly must be replaced.  
NOTE: Always turn off and disconnect main supply wiring before  
servicing the unit.  
MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN  
FLAME NOT ESTABLISHED.  
4. Check connecting wire to the flame sensor. Verify that the flame  
sensor has not been damaged in any way.  
5. Verify that the air supply is adequate. The air inlet screen or  
blower wheel may be restricted. Also, check the installation for  
proper ventilation. See AIR REQUIREMENTS.  
1. Check to see if main manual gas valve is open.  
2. Check for a loose connection at the transformer, or a defective  
transformer.  
3. Check for a loose connection at the gas valve.  
4. Check for open pressure switches or open E.C.O. Check for  
blockage in the intake and exhaust vent hoods. If no blockage  
is found, check vinyl tubing for cuts or crimps. If this tubing is  
damaged it must be replaced. If these steps do not eliminate  
the problem, replace the pressure switches.  
6. Check the venting hoods for obstructions. See VENTING.  
7. Check for a maximum inlet pressure of 14" Natural Gas (3  
kPa), and the manifold pressure as listed in Table 4: that is, for  
Natural Gas, 4.5". Please note that the manifold pressure listed  
is the maximum value for the manifold pressure. Do not set the  
manifold pressure higher than the value shown for your heater  
in Table 4. Overfiring the heater will result in rough ignition and/  
or noisy operation.  
5. Check to see if there is resistance across the igniter terminal  
with an ohmmeter. If there is no continuity, the igniter is broken  
and should be replaced.  
8. Confirm that the air inlet screen is free of obstructions.  
CAUTION  
If the igniter appears to function properly, then verify that the inlet  
pressure is 14" Natural Gas (3 kPa) maximum. The gas valve  
supplied on this appliance is not designed to open against a  
higher pressure. At this time also check that the inlet pressure  
is not lower than the minimal gas supply pressure, as shown  
in Table 4: that is, for Natural Gas, 6.2" W.C. If the inlet pressure  
is not within these limits then adjust the supply pressure  
accordingly.  
Do not reach into the burner housing or combustion chamber if  
the heater is still hot. Allow the heater to cool and always use  
gloves as the combustion chamber and the burner sleeve and  
housing can become very hot after operation. Overfiring is a  
dangerous condition that must be corrected immediately.  
GAS FAILS TO SHUT OFF  
Check for defective gas valve or thermostat. If operation is incorrect,  
replace.  
If the inlet pressure falls within the allowable limits, then verify  
that the manifold pressure, when the gas is fully open, with the  
heater running, is as called out in Table 4: that is, 4.5" (1 kPa)  
W.C. for Natural Gas. If the manifold pressure is not correct  
then adjust accordingly. See ADJUSTMENT PROCEDURE in  
OPERATING INSTRUCTIONS selection, page 21, for the  
manifold pressure adjustment procedure.  
REPLACEMENT PARTS  
Replacement parts may be ordered through State dealers,  
authorized servicers or distributors. Refer to the Yellow Pages for  
where to call or contact the State Water Heaters, 500 Tennessee  
6. If the inlet and manifold pressures are within the limits specified Waltz Parkway, Ashland City, TN 37015, 1-800-821-2017. When  
in step 5, then reset the appliance. Verify 24VAC at the gas valve ordering parts be sure to state the quantity, part number and  
during the three (3) second ignition trial, after the igniter reaches description of the items including the complete model and serial  
operating temperature. If 24V AC at the gas valve is not seen number as it appears on the product. Refer to the parts list for  
during this period, the controller must be replaced.  
more information.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL SRT80 120NE LIMITED WARRANTY  
State Water Heaters, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.  
1. THE TANK  
If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable water  
therein, during the first THREE years after initial installation, the warrantor will supply a replacement tank less burner and controls or a complete new  
State water heater of equivalent size and current model at the warrantor's option. Some government agencies are requiring energy efficient standards  
for water heaters. In the event regulations prohibit sale of a model of equivalent size and construction, State will provide a model which complies with  
the regulations of your area., in which case the consumer will be charged the difference in price between the like replacement and the energy efficient  
model required. The warranty on the replacement water heater will be limited to the unexpired term of the original warranty.  
2. ALL OTHER PARTS  
If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in  
material or workmanship, the warrantor will repair or replace such part or portion at its option.  
3. CONDITIONS AND EXCEPTIONS  
This warranty shall apply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and regulations, the  
printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by A.G.A. and approved  
by the American Society of Mechanical Engineers, must have been installed.  
a. This warranty shall apply only when the heater is used:  
(1)  
(2)  
(3)  
(4)  
(5)  
(6)  
(7)  
(8)  
(9)  
at temperatures not exceeding the maximum setting of its thermostat;  
at water pressure not exceeding the working pressure shown on the heater;  
when operated free of the damaging effects of uncontrolled water hammer;  
when filled with potable water, free to circulate at all times;  
in a non-corrosive and non-contaminated atmosphere;  
with factory approved anode(s) installed;  
in the United States, its territories or possessions, and Canada;  
sized in accordance with proper sizing techniques for commercial and/or residential water heaters;  
bearing a rating plate which has not been altered, defaced or removed, except as required by the warrantor;  
(10) operated with properly installed dirt leg;  
(11) fired with the fuel for which it was factory built;  
(12) fired at the factory rated input;  
b. Any accident to the boiler, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, or any attempt to repair  
tank leaks will void this warranty.  
c. This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is connected  
to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The relief valve  
installed on the heater is not an acceptable method.  
d. This warranty shall be void and shall have no effect if the design or structure of the water heater is, or is attempted to be modified or altered in any  
way, including, but not limited to, by attaching non-company approved appliances or equipment.  
4. SERVICE AND REPAIR EXPENSES  
Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs. Such  
costs may include but are not limited to:  
a. Labor charges for service removal, repair or reinstallation of the water heater or any component part;  
b. Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and returning  
the claimed defective heater or part to such distributor.  
c. All cost necessary or incidental for any material and/or permits required for installation of the replacement.  
5. LIMITATIONS ON IMPLIED WARRANTIES  
Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state law are limited to one (1) year duration for  
the heater or any of its parts. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.  
6. CLAIM PROCEDURE  
Any claim under the warranty should be initiated with the dealer who sold the boiler, or with any other dealer handling the warrantor’s products. If this  
is not practicable, the owner should contact:  
State Water Heaters  
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
a. The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the  
warrantor.  
b. Dealer replacements are made subject to in-warranty validation by warrantor.  
7. DISCLAIMERS  
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY  
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE BOILER. THE WARRANTOR SHALL NOT BE  
RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER  
CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY  
PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR TORT.  
a. Some states do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may not apply  
to you.  
b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.  
Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the heater’s rating  
plate.  
Model No.  
Dealer’s Name____________________________________________________________________________________________________________  
Dealer’s Address _______________________________________________________________ Phone No._______________________________  
__  
Serial No. _________________________________________ Date Installed_____________________  
City and State____________________________________________________________________ Zip Code________________________________  
KEEPTHISWARRANTYPOSTEDADJACENTTOTHEHEATERFORFUTUREREFERENCE  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
500TENNESSEE WALTZ PARKWAY  
ASHLAND CITY, TN 37015  
Phone: 800-821-2017 Fax: 800-644-9306  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sennheiser Satellite Radio SKP 2000 User Manual
Sharp CRT Television LC 65RX1X User Manual
Shindaiwa Trimmer 89300 User Manual
Sony Clock Radio ICF C263 User Manual
Sony Computer Monitor CPD E230 User Manual
Sony DVD Player DVP NC625 User Manual
Sony DVR ICD UX60 User Manual
Sony Tablet SGP312U1 W User Manual
Sterling Plumbing Indoor Furnishings C711FAS User Manual
Sterling Refrigerator 8829309201 User Manual