MODELS GPG/GPV-540A, 650A AND 740A
COMMERCIAL GAS, GLASS-LINED, TANK-TYPE LOW NOx
WATER HEATER
• INSTALLATION • OPERATION • MAINTENANCE • LIMITED WARRANTY
CAUTION
TEXT IN BLACK BOLD TYPE OR UNDERLINED
CONTAINS INFORMATION RELATIVE TO YOUR
SAFETY. PLEASE READ THOROUGHLYBEFORE
INSTALLINGAND USING THISAPPLIANCE.
ASHLAND CITY, TN
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED IN U.S.A. 1004
PART NO. 195047-000
Download from Www.Somanuals.com. All Manuals Search And Download.
In the absence of local codes, the installation must conform with
the instructions as outlined in the latest publication of National
Fuel Gas Code (NFPA-54/ANSI Z223.1) and National Electric
Code (NFPA-70). These manuals can be purchased from the
Canadian Standards Association Laboratories, 8501 East
Pleasant Valley Road, Cleveland, OH 44131, National Fire
Protection Association, 1 Batterymarch Park, Quincy MA 02269.
In addition to these instructions, the equipment shall be installed
in accordance with those installation regulations in accordance
with those installation regulations in force in the local area where
the installation is to be made. These shall be carefully followed
in all cases. Authorities having jurisdiction should be consulted
before installations are made.
TABLE OF CONTENTS
PAGE
PAGE
Heater Wiring ...............................................................................19
STARTUP ............................................................................................ 19
Important ...................................................................................... 19
Filling ............................................................................................ 19
Purging .........................................................................................19
Wiring Diagram ...................................................................... 20,21
Lighting and Operating Label ......................................................22
Sequence of Operation ............................................................... 23
Water Temperature Control ......................................................... 23
Adjustment Procedure (Initial Start-Up) ................................ 23,24
Adjustment Procedure for Fire-Rate, Low Nox and
High Elevation (Fine-Tune) .................................................... 24-26
GENERALINFORMATION .................................................................... 27
Power Burner ..............................................................................27
Thermostat ..................................................................................27
High Limit...................................................................................... 27
MAINTENANCE ....................................................................................27
General ........................................................................................27
Maintenance Schedule ................................................................27
Electrical Servicing ......................................................................27
Flushing ....................................................................................... 27
Draining........................................................................................28
Sediment Removal .......................................................................28
Lime Scale ...................................................................................28
Relief Valve ........................................................................... 28,29
Circulating Pump .......................................................................... 29
Low Emission Power Burner ......................................................29
Cleaning Flues .............................................................................29
Barometric Draft Control .............................................................29
Vent System ................................................................................29
CHECKLISTAND SERVICE INFORMATION .................................... 29-30
TROUBLESHOOTING ..................................................................... 30-32
Replacement Parts ......................................................................32
WARRANTY ........................................................................................33
PARTS LIST .................................................................................... 34-39
ROUGH-IN-DIMENSIONS ........................................................................2
FOREWORD ....................................................................................... 2,3
TABLE OF CONTENTS ........................................................................... 3
GENERALSAFETY INFORMATION ....................................................... 3
Precautions ...................................................................................3
Liquid Petroleum Models ................................................................3
Chemical Vapor Corrosion ........................................................ 3,4
Improper Combustion .................................................................... 4
EXTENDEDNON-USEPERIODS ............................................................. 4
Cathodic Protection .......................................................................4
Insulation Blankets.........................................................................4
High Altitude Installations .............................................................. 4
FEATURES ............................................................................................. 4
Low Emmission Control .................................................................4
High Limit Switch (E.C.O.) ......................................................... 4,5
Dishwashing Machine Requirement ............................................. 5
INSTALLATION INSTRUCTIONS ............................................................. 5
Required Ability .............................................................................5
Uncrating ....................................................................................... 5
Locating the Heater ................................................................... 5,6
Hard Water ....................................................................................6
Clearances ....................................................................................6
Air Requirements........................................................................... 6
Venting....................................................................................... 6,7
Vertical Venting - For GPG Models ...............................................7
Horizontal (Side-wall) Venting - For GPV Models .................... 7,8
Direct Venting - For GPV Models ............................................ 9-11
Gas Piping ............................................................................. 11-12
Gas Meter Size ............................................................................12
Gas Pressure Regulation ............................................................12
Gas Valves ............................................................................ 12,13
Water Line Connections ..............................................................13
Thermometers .............................................................................13
Relief Valve .................................................................................13
INSTALLATION DIAGRAMS ........................................................... 14-17
Manifold Kits ................................................................................18
GENERAL SAFETY INFORMATION
are different from natural gas models. A natural gas heater
will not function safely on LP gas and no attempt should be
made to convert a heater from natural gas to LP gas.
PRECAUTIONS
DO NOTUSE THISAPPLIANCE IFANYPART HAS BEEN UNDER
WATER. Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system and
any gas control which has been under water.
GPG/GPV-540A, 650A & 740A models are not available for use
with Liquefied Petroleum or LP gas. If you have obtained a
GPG/GPV-540A, 650A or 740A model with the intent to use it
with Liquefied Petroleum, LP gas - STOP! Immediately contact
your dealer to obtain a correct model.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT
OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE
BEEN MADE BY A QUALIFIED SERVICEMAN.
CHEMICAL VAPOR CORROSION
1. EXTERNAL FIRE.
2. DAMAGE.
3. FIRING WITHOUT WATER.
4. SOOTING.
WARNING
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY
OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN
CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN
FAILUREAND RISK OFASPHYXIATION.
LIQUID PETROLEUM MODELS
WARNING
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium
Water heaters for propane or liquefied petroleum gas (LPG)
3
Download from Www.Somanuals.com. All Manuals Search And Download.
and sodium chloride (water softener salt), waxes, and process 2. INSULATION BLANKETS CAN RESTRICT THE AIR FLOW
chemicals are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which
is brought in contact with the heater should no contain any of
these chemicals. If necessary, uncontaminated air should be
obtained from remote or outside sources. The limited warranty
is voided when failure of water heater is due to a corrosive
atmosphere. (Refer to the limited warranty for complete terms
and conditions).
NEEDED FOR PROPER OPERATION OF THE COMBUSTION
SYSTEM AND COULD RESULT IN FIRE, ASPHYXIATION,
SERIOUS PERSONALINJURYOR DEATH.
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN
SERIOUS PERSONALINJURYOR DEATH.
HIGH ALTITUDE INSTALLATIONS
IMPROPER COMBUSTION
Your State water heater has been designed to operate at altitudes
below 2000 Ft. (609.6 m), for appliance installation locations
with elevations above 2000 Ft. (609.6 m), special considerations
need to be taken. Adjustments for high altitude can only be made
by a State authorized GPG/GPV Start-up Agent. To ensure your
water heater operates properly at high elevation, a State
authorized GPG/GPV Start-up Agent will readjust the air-intake
damper setting and the gas manifold pressure (if required).
WARNING
ATTICAND OR EXHAUST FANS OPERATING ON THE PREMISES
WITHAWATER HEATER CAN RESULT IN CARBON MONOXIDE
POISONINGAND DEATH.
OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE
DRAFT IN THE AREA OF THE WATER HEATER PREVENTING
THE PRODUCTS OF COMBUSTION FROM EXHAUSTING
THROUGH THE CHIMNEY OR VENT PIPE.
NOTE: Some gas utility companies derate the heating value of
the supplied gas at high elevation. Your authorized start-up agent
must adjust for actual heating value of the gas at the time of start
up.
The venting of the water heater should be inspected by a qualified
service technician at the time of installation and periodically
thereafter to ensure a down-draft condition does not exist.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND
VENTILATION AIR, ADEQUATE AIR FOR COMBUSTION AND
VENTILATION MUST BE PROVIDED FOR SAFE OPERATION.
FEATURES
LOW EMISSION CONTROL
EXTENDED NON-USE PERIODS
CATHODIC PROTECTION
CAUTION
Your State water heater has been designed to comply with
standards established by California South Coast Air Quality
Management District (SCAQMD), the most stringent emissions
control agency in the nation. To ensure compliance with SCAQMD
Rule 1146.2, your heater is equipped with an internal recirculation
premix power burner, and must be started/adjusted by a
State Authorized GPG/GPV Start-Up Agent.
HYDROGENGASCANBEPRODUCEDINAHOTWATERSYSTEM
SERVED BY THIS HEATER THAT HAS NOT BEEN USED FORA
LONG PERIOD OF TIME (GENERALLYTWO WEEKS OR MORE).
HYDROGEN GAS IS EXTREMELY FLAMMABLE. To reduce the
risk of injury under these conditions, it is recommended that a
hot water faucet be opened for several minutes before using any
electrical appliance connected to the hot water system. If
hydrogen is present, there will probably be an unusual sound
such as air escaping through the pipe as the water begins to
flow. There should be not smoking or open flame near the
faucet at the time it is open.
HIGH LIMIT SWITCH (E.C.O.)
The dual bulb controller also contains the high limit (energy
cutoff) sensor. The high limit switch interrupts main burner gas
flow should the water temperature reach 205°F (96°C).
In the event of high limit switch operation, the appliance cannot
be restarted unless the water temperature is reduced by 20°F
(11°C) approx. and the high limit reset button on front of limit
control is depressed, see Figure 1.
INSULATION BLANKETS
WARNING
INSULATION BLANKETAVAILABLE TO THE GENERAL PUBLIC
FOR EXTERNAL USE ON GAS WATER HEATERS ARE NOT
APPROVED FOR USE ON YOUR STATE WATER HEATER. THE
PURPOSE OF AN INSULATION BLANKET IS TO REDUCE THE
STANDBY HEAT LOSS ENCOUNTERED WITH STORAGE TANK
WATER HEATER. YOUR STATE WATER HEATER MEETS OR
EXCEEDS THE ASHRAE/IES 90.1B 2001 STANDARDS WITH
RESPECT TO INSULATION AND STANDBY LOSS
REQUIREMENTS, MAKING AN INSULATION BLANKET
UNNECESSARY. THE USE OF INSULATION BLANKETS IN
CONJUNCTIONWITHASTATEWATERHEATERWILLALSOVOID
THE STATE WARRANTYFOR THE FOLLOWING REASONS:
1. INSULATION BLANKETS COVER IMPORTANT OPERATING
INSTRUCTIONS AND SAFETY LABELS.
FIGURE 1.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Continued manual resetting of high limit control, preceded by
higher than usual water temperature is evidence of high limit
switch operation. The following are possible reasons for high
limit switch operation.
LOCATING THE HEATER
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the stack
chimney as practicable, with adequate air supply and as
centralized with the piping system as possible.
•
A malfunction in the thermostatic controls would allow the
gas valve to remain open causing water temperature to exceed
the thermostat setting. The water temperature would continue
to rise until high limit switch operation.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
•
An improper thermostat setting for a short repetitive usage AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER
pattern may lead to a stacking effect. This causes a AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,
OPERATED OR REPAIRED. FLAMMABLE VAPORSARE HEAVY
AND TRAVELALONG THE FLOORAND MAYBE IGNITED BYTHE
HEATER’S IGNITER OR MAIN BURNER FLAMES CAUSING FIRE
OR EXPLOSION. SOME LOCALCODES PERMIT OPERATION OF
GASAPPLIANCES IF INSTALLED 18 INCHES OR MOREABOVE
THEFLOOR. THISMAYREDUCETHERISKIFLOCATIONINSUCH
ANAREACANNOT BEAVOIDED.
temperature gradient increasing from the bottom to the top of
the tank. It is possible that the water at the high limit switch
sensor could reach its maximum temperature before the water
temperature at the thermostat reaches the dial setting,
causing the high limit switch to activate.
•
A warming of ambient conditions associated with seasonal
change could magnify the stacking process described above
to the point where high limit switch operation would occur.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
Contact your dealer or servicer if continued high limit switch
operation occurs.
WARNING
DISHWASHING MACHINE REQUIREMENT
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER
BE PLACED ON OR ADJACENT TO THE HEATER. OPEN
CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE HEATER.
All dishwashing machines meeting the National Sanitation
Foundation requirements are designed to operate with water
flow pressures between 15 and 25 pounds per square inch.
Flow pressures above 25 pounds per square inch, or below
15 pounds per square inch, will result in improperly sanitized
dishes. Where pressures are high, a water pressure reducing
or flow regulating control valve should be used in 180°F (82°C)
line to the dishwashing machine, and should be adjusted to
deliver water between these limits.
THE HEATER MUST NOT BE LOCATED INAN AREAWHERE IT
WILL BE SUBJECT TO FREEZING.
LOCATE IT NEARAFLOOR DRAIN. THE HEATER SHOULD BE
LOCATED INANAREAWHERE LEAKAGE FROM THE HEATER
OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE
ADJACENT AREA OR TO LOWER FLOORS OF THE
STRUCTURE.
The National Sanitation Foundation also recommends
circulation of 180°F (82°C) water. Where this is done, the
circulation should be very gentle so that it does not cause any
unnecessary turbulence inside the water heater. The circulation
should be just enough to provide 180°F (82°C) water at the point
of take-off to the dishwashing machine. Adjust flow by means of
the plug cock in the circulating line.
WHEN SUCH LOCATIONS CANNOT BEAVOIDED, ASUITABLE
DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER. Such
pans should be fabricated with sides at least 2” (50.8 mm) deep,
with length and width at least 2” (50,8 mm) greater than the
diameter of the heater and must be piped to an adequate drain.
THE PAN MUST NOT RESTRICT COMBUSTIONAIRFLOW.
INSTALLATION INSTRUCTIONS
Water heater life depends upon water quality, water pressure
and the environment in which the water heater is installed. Water
heaters are sometimes installed in locations where leakage
may result in property damage, even with the use of a drain pan
piped to a drain. However, unanticipated damage can be reduced
or prevented by a leak detector or water shut-off device used in
conjunction with a piped drain pan. These devices are available
from some plumbing supply wholesalers and retailers, and
detect and react to leakage in various ways:
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS WATER HEATER
REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED
TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR
SUPPLY, VENTING, GAS SUPPLYAND ELECTRICALWORKARE
REQUIRED. NOTE:AUTHORIZED START-UPIS REQUIRED.
• Sensors mounted in the drain pan that trigger an alarm or turn
off the incoming water to the water heater when leakage is
detected.
UNCRATING
The heater is shipped in standard form for vertical venting with a
barometric draft control assembly in a separate carton.
• Sensors mounted in the drain pan that turn off the water supply
to the entire home when water is detected in the drain pan.
Optional horizontal vent models are shipped with one (1) exhaust
vent hood and one (1) flue reducer in a separate carton. Optional
direct vent models are shipped with two (2) vent hoods in separate
cartons. The exhaust vent hood carton contains one (1) exhaust
vent hood and one (1) flue reducer. The intake vent hood carton
contains one (1) intake vent hood and one (1) inlet adapter. All
parts should be installed as received without alteration.
• Water supply shut-off devices that activate based on the water
pressure differential between the cold water and hot water
pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater
while at the same time shutting off its water supply.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Units, which are to be installed on combustible flooring, must A clearance of 30” (762 mm) shall be maintained from
be supported by a full layer of hollow concrete blocks, from serviceable parts, such as power burners, relief valves flue
8” (203.2 mm) to 12” (304.8 mm) thick and extending
12” (304.8 mm) minimum beyond the heater in all directions.
The concrete blocks must provide an unbroken concrete surface
under the heater with the hollows running continuously and
horizontally. A 3/16-inch steel plate must cover the concrete
blocks, see Figure 2.
baffles, thermostats or drain valves.
AIR REQUIREMENTS
KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE
MATERIALS, GASOLINEANDOTHERFLAMMABLEVAPORSAND
LIQUIDS.
NOTE: If electrical conduits run under the floor of the proposed
heater location, insulate the floor as recommended above.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATINGAIR.
For appliances installation locations with elevations above 2000
feet (609.6 m), refer to HIGHALTITUDE INSTALLATIONS section.
WARNING
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR
COMBUSTIONAND VENTILATION. AN INSUFFICIENT SUPPLY
OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION
PRODUCTS RESULTING INAIR CONTAMINATION THAT MAYBE
HAZARDOUSTOLIFE. SUCHACONDITIONOFTENWILLRESULT
IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING
CARBONING OR SOOTING OF THE COMBUSTION CHAMBER,
BURNERS AND FLUE TUBES AND CREATES A RISK OF
ASPHYXIATION.
Where an exhaust fan is installed in the same room with a heater,
sufficient openings for air must be provided in the walls.
UNDERSIZED OPENINGS WILLCAUSEAIR TO BE DRAWN INTO
THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION. SOOTING MAY RESULT IN SERIOUS DAMAGE
TO THE HEATERAND RISK OF FIRE OR EXPLOSION.
PROPER INSTALLATION ON COMBUSTIBLE FLOORING
FIGURE 2.
UNCONFINEDSPACE
HARD WATER
In buildings of conventional frame, brick or stone construction,
Where hard water conditions exist, water softening or the unconfined spaces may provide adequate air for combustion
threshold type of water treatment is recommended. This will
protect the dishwasher, Coffee urns, water heaters, water piping
and other equipment.
and ventilation.
If the unconfined space is within a building of tight construction,
(building using the following construction: weather stripping,
heavy insulation, caulking, vapor barrier, etc.), air for combustion
and ventilation must be obtained from outdoors or spaces freely
communicating with the outdoors. The installation instructions
for confined spaces in tightly constructed buildings must be
followed to ensure adequate air supply.
See MAINTENANCE section for details of tank cleanout
procedure.
CLEARANCES
These heaters are designed for installation on non-combustible
flooring in an alcove with clearances to combustible construction CONFINEDSPACE
of 6” (152.4 mm) from the sides and rear, 24” (610 mm) from the
When drawing combustion and dilution air from inside a
top with a 6” (152.4 mm) minimum between vent pipe and ceiling.
Minimum clearance from flue pipe to combustible material is
6” (152.4 mm), see Figure 3.
conventionally constructed building to a confined space, such a
space shall be provided with two permanent openings, ONE IN
OR WITHIN 12 INCHES (304.8 mm) OF THE ENCLOSURE TOP
AND ONE IN OR WITHIN 12 INCHES (304.8 mm) OF THE
ENCLOSURE BOTTOM. Each opening shall have a free area of
at least one square inch per 1000 Btuh of the total input of all
appliances in the enclosure, but not less than 100 square inches.
If the confined space is within a building of tight construction, air
for combustion and ventilation must be obtained from outdoors.
When directly communication with the outdoors through vertical
ducts, two permanent openings, located in the above manner,
shall be provided. Each opening shall have a free area of not
less than one square inch per 4000 Btuh of the total input of all
appliances in the enclosure.
VENTING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUSTBE
FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE
SOOTING OR RISKS OF FIREANDASPHYXIATION.
PROPER INSTALLATION CLEARANCES
FIGURE 3.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Heater must be protected from freezing downdrafts during
shutdown periods.
NOTE:ANEGATIVE DRAFTMUST BE MAINTAINED IN VENTING.
A negative draft of 0.02” to 0.04” w.c. Must be maintained in
venting system. Measure draft at the location illustrated in
Figure 4. Adjust the control counter-weights if necessary as
shown in the MAINTENANCE portion of this manual.
The GPG 540A, 650A and 750A water heater are classified as a
category I appliance (non-positive vent pressure, non-
condensing) when installed with the supplied barometric draft
control assembly in a vertical vent installation.
Where an existing chimney or vent is to be used, be sure that the
chimney or vent has adequate capacity for the number and sizes
of gas appliances being vented through it. Inspect the chimney
or vent and remove all soot or other obstructions, which will
retard free draft.
The GPV 540A through 740A heater is classified as a category
III appliance (positive vent pressure, non-condensing) when
installed with supplied sidewall vent kits or direct vent kit.
All regulations pertaining to the venting of these heaters must
be followed.
Vent connectors making horizontal runs must have a minimum
upward slope toward the chimney or vent of ¼ inch per foot. Vent
connector length should be kept as short as possible. Be sure
that the vent pipe does not extend beyond the inside wall of a
chimney, see Figure 4.
The following vent installation instructions cover vertical,
horizontal, and direct vent applications.
VERTICAL VENTING - FOR GPG MODELS
BAROMETRIC DRAFT CONTROLASSEMBLY
A double-acting barometric draft control assembly is provided
with any unit intended for chimney venting. The purpose of this
draft control is twofold. During downdrafts it acts as a pressure
relief control to prevent the downdraft from blowing into the heater.
It also allows for makeup air to enter the chimney without being
drawn through the heater. In both cases the control prevents the
heater performance from being adversely affected by conditions
within the chimney.
The draft control assembly must be installed without alteration.
This assembly is factory adjusted for horizontal application only
and must be attached to the heater as shown in Figure 4. The
direction in which the outlet to the draft controls assembly faces
is arbitrary. The assembly must be fitted to the jacket cover such
that it is plumb and level to the ground. Fasten the draft control
assembly to the top cover using sheet metal screws at three
locations, or more, as required.
FIGURE 4.
In venting systems where a continuous or intermittent back
(positive) draft is found to exist, the cause must be determined
and corrected. In some cases, a special vent cap may be
required.
Damper or other obstructions must not be installed between the
heater and the barometric draft control assembly.
WARNING
Do not adjust settings on gate.
Failure to correct back drafts may cause air contamination
and unsafe conditions.
When installed, the damper gate must pivot freely in the ring
guides. This gate will automatically adjust to regulate the
chimney draft imposed on the heater.
Do not connect the heater to a common vent or chimney with
solid fuel burning equipment. This practice is prohibited by
many local building codes as is the practice of venting gas fired
equipment to the ductwork of ventilation systems.
VENT CONNECTIONS
Vent connections must be made to an adequate stack or chimney.
Refer to the National Fuel Gas Code or to the vent pipe
manufacturer’s gas vent and chimney sizing table to properly
design and size the venting system. Refer to Table 1 for the vent
pipe size required for installation to the barometric draft control
assembly outlet.
Connectors shall not be connected to a chimney, vent or venting
system served by a power exhauster, unless the connection is
made on the negative pressure side of the exhauster.
Do not connect any heater vented by natural draft to any vent
serving mechanical draft equipment operating under positive
vent pressure such as category III or category IV appliances.
TABLE 1.
Model
Flue Outlet
HORIZONTAL (SIDE-WALL) VENTING -
FOR GPV MODELS
GPG-540A
GPG-650A
GPG-740A
9” (228.6 mm)
9” (228.6 mm)
9” (228.6 mm)
An exhaust vent hood, vent hood and a flue reducer are supplied
with any unit intended for through-the-wall horizontal venting.
Single-wall or type B venting may be used with these heaters in These parts must be installed without alteration. The vent hood
adapter is designed for use with Selkirk Metalbestos Model PS
or Model G venting, see Figure 7 on page 10.
vertical vent installations. All local and utility regulations on
venting must be followed.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Shall not be closer than 3 feet (0.9 m) from the inside corner
of an L- shaped structure.
Refer to Table 2 for limitations of venting system design for
horizontal venting.
TABLE 2
6. Shall be located above the snow line in geographical areas
where snow accumulates.
GPV-540A-740A
Flue Outlet Dia. (Inches/mm)
Flue Reducer
9” (228.6)
VENT SYSTEM INSTALLATION
9” x 8”
Dimensions -Supplied (Inches/mm)
Minimum Outlet Vent Dia. (Inches/mm)
228.6 x 203.2
This heater is a category III appliance when horizontally vented
through a wall using the supplied sidewall vent terminal. All
national and local codes pertaining to the installation of such
venting systems must be followed.
8” (203.2)
Maximum Number
90°
45°
4
8
Of Elbows
Maximum Total Vent System
Length, Equiv. Feet/Meters
75
Horizontal portions of the vent system must be installed with a
minimum upward slope of 1/4” per foot of length.
(23 m)
All joints and seams in the venting system must be sealed gas
tight. If a silicone sealer is used, it must have a continuous
temperature rating of at least 500°F (260°C); Dow Corning
736 or equivalent must be used.
When calculating the equivalent length of a venting system each
90° elbow is equivalent to 10 feet (3 m) of straight pipe. In no
case 45° elbow is equivalent to 5 feet (1.5 m) of straight pipe. In
no case may the sum of the straight pipe lengths and the
equivalent length of the elbows exceeds 80 feet (24.3 m).
CAUTION
Note the minimum vent diameter in Table 2.
Use only the vent hood supplied with this kit. Only supplied
hood provides required clearances from combustibles, both
through the wall and the exterior siding. Termination of a
sidewall vent system with a device other than the supplied
vent hood could affect system performance and result in a
safety hazard.
Refer to Table 3 for the correct vent terminal size for each heater.
The dimensions noted in Table 3 refer to Figure 5.
TABLE 3
Heater Terminal
Rough-In
IMPORTANT
Model
GPV
Model
A
B
C
D
Dimensions
Plan the layout of the vent system backward from the vent
termination to the water heater.
540A-
740A
VH-1-8” 19-7/8” 13” 10-9/16” 8-5/8”
11-1/16”
1. Use the layout of the vent system backward from the vent
termination to the water heater.
BEWARE OF CONCEALED WIRINGAND PIPING INSIDE OF
WALL. REFER TO TABLE 5 FOR THE MAXIMUM WALL
THICKNESS “B” FOR EACH MODEL.
2. Slide hood through opening from outside. Fasten hood to
exterior wall with anchors and screws supplied.
3. Install covers plate and fasten to inside wall with 4 screws.
4. Attach a seal ring (Meltalbestos SR or equivalent) to the vent
hood collar, see Figure 7. Attach Selkirk Metalbestos model
PS or model G venting to the seal ring following the venting
manufacturer’s instructions. For total safety, it is
recommended that only venting listed for use with category III
appliances (positive vent pressure, non-condensing) should
be used between the heater and the vent hood, even through
national or local codes may allow the use of type B or single-
wall vent.
FIGURE5
Use only the sidewall vent terminal supplied with the heater.
These terminals are specifically listed for use on these
State heaters.
VENT TERMINAL LOCATIONS-EXHAUST
When considering location for sidewall vent terminals refer to
the latest edition of the National Fuel Gas Code which
recommends that vent terminals:
5. Install the remaining vent sections back to the heater, following
the venting manufacturer’s instructions on assembling and
sealing joints. Follow good venting practice regarding
properly supporting vent system and keeping the number of
offsets to a minimum. See Table 2 for the maximum allowable
number of elbows in venting system.
1. Shall be located not less than 12” (304.8 mm) above grade.
2. Shall be located not less than 7 feet (2.1 m) above grade
when adjacent to a public walkway.
6. Install the flue reducer included with the exhaust hood between
the vent system and the heater.
3. Shall terminate at least 3 feet (0.9 m) above any forced air
inlet within 10 feet (3 m).
7. Seal all vent connections and venting with sealants supplied
by vent pipe manufacturer or with a high-temperature silicone
sealant suitable for continuous temperatures of 500°F
(260°C). Acceptable sealant include Dow Corning 736
or equivalent.
4. Shall terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m)
horizontally from or 1 foot above any door, window or gravity
air inlet into any building.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 6.
DIRECT VENTING - FOR GPV MODELS
TABLE 5.
Dimension in
GPV
All exhaust vent terminal, flue reducer, and intake vent terminal
are supplied with any unit intended for direct venting. These
parts must be installed without alteration.
Inches (mm)
Flue Outlet Dia.
Flue Reducer Dimension
(Supplied)
Min. Exhaust Vent Dia. Inch (mm)
Min. Intake Vent Dia. Inch (mm)
Maximum Number Of
Elbows, Intake
540A -740A
9 (229)
9 x 8
(229 x 203)
8 (203)
8 (203)
4
This heater is category III appliance when used in a direct vent
application. All national and local codes pertaining to the
installation of such an appliance must be followed.
90°
45°
8
Maximum Number Of
Elbows, Exhaust
Total Intake Vent
Length, Equiv. Ft.
Total Exhaust Vent
90°
45°
Max.
Min.
Max.
Min.
4
8
Horizontal portions of the exhaust vent system must be installed
with a minimum upward slope of 1/4” (6.35 mm) per foot of
length.
75 (23 m)
3 (1 m)
75 (23 m)
6 (1.8)
Selkirk metalbestos model PS or G vent is approved for use as
exhaust venting on these models. Model PS is a double-wall
vent with a 1” (25.4 mm) air space between pipes. Model G is a
single-wall variation of model PS for use where combustible
clearance is not a concern, see Table 4.
Length, Equiv. Ft.
Note: Barometric draft control is not used in direct vent installations
as the venting system must be sealed.
When calculating the equivalent length of a venting system each
90 elbow is equivalent to 10 feet of straight pipe. Each 45 elbow
is equivalent to 5 feet (1.5 m) of straight pipe. Do not exceed the
maximum number of elbows as shown in Table 5. In no case may
the sum of the straight pipe lengths and the equivalent lengths of
the elbows exceed the valves in Table 5.
TABLE 4.
Selkirk Metalbestos Model PS
Clearance to Combustibles
Interior
Exterior
6” (152.4 mm)
6” (152.4 mm)
VENT TERMINALLOCATIONS-EXHAUST
8” diameter PVC or galvanized pipe is approved for use as
intake venting on these models. Class 63, 100, 125, 200, and
schedule 40 pipe may be used for PVC pipe. Intake venting
must be adequately supported to avoid unnecessary stress on
vent hood, venting, or burner.
See “Horizontal Venting” in this manual for acceptable locations
for exhaust hoods.
VENT TERMINALLOCATIONS-INTAKE
See Table 5 limitations on venting system design for direct vent
installations.
When considering locations for the intake terminal, bear in mind
that the terminal:
9
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Shall be located not less than 12” (304.8 mm) above grade. DIRECT VENT SYSTEM INSTALLATION
2. Shall be located not less than 3 (.9144 m) feet horizontally Plan the vent system backwards from the vent hood to the heater.
from and not less than 3 feet (.9144 m) below an exhaust vent
terminal.
1. Use the inside wall cover plate as a template to mark two
holes in the appropriate places on the wall. Cut holes
1/2” (12.7 mm) larger to facilitate easy installation of vent
hoods, see Figures 6 and 7.
3. Shall not be located directly above an exhaust terminal.
4. Shall be located 12” (304.8 mm) above the snow line in
geographical areas where snow accumulates.
BEWAREOFCONCEALEDWIRINGANDPIPINGINSIDEWALL.
REFER TO TABLE 3 FOR THE MAXIMUM WALL THICKNESS
“B” FOR EACH MODEL.
5. Shall be located not less than 7 feet 2.1 m) above grade
when adjacent to a public walkway.
2. Slide hoods through openings from outside. Fasten hoods
to exterior wall with anchors and screws supplied.
6. Shall not be closer than 3 feet (.9144 m) from the inside
corner of an L - shaped structure.
3. Install cover plate and fasten to inside wall with 4 screws
7. Shall be located not less than 3 feet (.9144 m) horizontally or
3 feet (.9144 m) vertically from gas line, meter, or other gas 4. Attach a seal ring (Selkirk Metalbestos Model SR or equivalent)
supply entering a structure, see Figure 6.
to the vent hood collar, see Figure 7.
FIGURE 7B.
FIGURE 7.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Attach a properly sized length of Selkirk Metalbestos model
PS or model G venting to the exhaust vent adapter using the
inner vee bands, see Figures 7 and 7B on page 10.
WARNING
PRIMERSAND CEMENTSARE EXTREMELYFLAMMABLE, AND
MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME.
ALLOWADEQUATECURINGTIMEBEFOREOPERATINGHEATER.
6. Fill the grooves in both inner vee bands with high-temp
silicone sealant, Dow Corning 736 or equivalent.
DRAIN VALVEANDACCESS PANELS
7. Position the inner vee bands around the inner pipe flanges
and tighten the screws securing the bands.
The heaters are equipped with a 3/4” NPT drain valves mounted
above and to the left of the burner.
8. Align the outer channel band with the outer pipe grooves
and tighten the screws securing the bands.
An access panel is located above and to the right of the burner,
see Figure 8. This panel covers the cleanout opening in the tank
which is sealed by a gasket and cover. Another cleanout access
panel is located towards the back of the heater.
9. Repeat steps 6-8 for each successive pipe length until the
venting reaches the heater.
10. Follow the manufacturer’s instructions for proper support
and guide spacing for horizontal runs of pipe, see Table 6.
TABLE 6.
Vent Diameter
S
F
8” - GPV -540A, 650A & 740A
15’ 3”
7’ 6”
S = Maximum spacing between two guides or a support
and a guide in either a vertical or horizontal direction.
F = Maximum height above a guide or support for free
standing system above a roof or parapet wall.
FIGURE 8.
11. Use an expansion joint between any two fixed points in the
exhaust venting system wherever the expansion may exceed
1/4”. Selkirk Metalbestos model PS and model G venting
will expand by one inch per 100°F in gas temperature per
100 feet of vent length. The expansion can be calculated by
the following formula:
GAS PIPING
Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation
codes for your area.
Size the main gas line in accordance with Table 9 and 9A.
Minimum required gas supply pipe size is 1 1/4”. The figures
shown are for straight lengths of pipe at 0.5 in. w.c. pressure
drop, which is considered normal for low pressure systems.
Note that fittings such as elbows and tees will add to the pipe
pressure drop.
Expansion,
Inches
Vent length between
two fixed points, feet
5
=
x
100
If the expansion calculated is greater than 1/4”, an expansion
joint must be used between the two fixed points.
TABLE 9
12. Attach the flue reducer included in the exhaust vent hood
package to the flue collar on the heater.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR
(Based upon a Pressure Drop of 0.5 inch Water Column
and 0.5 Specific Gravity Gas and max. gas press. of .5 psig)
13. Attach the flue reducer to the vent system using a seal ring.
Attach this ring to the venting using the inner vee bands as
outlined in Steps 5-7.
LENGTH
IN
FEET
10
Nominal Iron Pipe Sizes, Inches
1" 1 1/4" 1 1/2" 2" 2 1/2"
175 360 680 1400 2100 3960 6300
1/2" 3/4"
3"
4"
14. Attach 8” air-intake connector to intake vent hood collar. It
may be necessary to use a slip-slip coupling to fit the pipe
to the intake vent hood.
11000 23000
7700 15800
6250 12800
5300 10900
20
30
40
50
60
70
120 250 485
950
770
660
580
530
490
460
430
400
360
325
300
280
1460 2750 4360
1180 2200 3520
97
82
73
66
61
57
53
50
44
40
37
35
200 375
170 320
151 285
138 260
125 240
118 220
110 205
103 195
93
84
77
72
990
900
810
750
690
650
620
550
500
460
430
1900 3000
1680 2650
1520 2400
1400 2250
1300 2050
1220 1950
1150 1850
1020 1650
4750
4300
3900
3700
3450
3250
2950
2650
2450
2280
9700
8800
8100
7500
7200
6700
6000
5500
5000
4600
15. Attach 8” air-intake connector back to the 6” burner air inlet
with 8” x 6” reducer. Prime and cement each joint to assure
gas-tight construction.
80
90
100
125
150
175
200
16. Seal all joints at the vent hoods with silicone sealant. Also
seal the joints at the flue collar and air inlet adapter. Joint on
the exhaust side must be sealed with high-temp silicone
sealant, Dow Corning 736 or equivalent.
175
160
145
135
950
850
800
1500
1370
1280
11
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 9A
ANY SUPPLY PRESSURE TESTING EXCEEDING
1/2 PSIG. GAS SUPPLY LINE MUST BE CAPPED WHEN
DISCONNECTED FROM THE HEATER. FOR TEST
PRESSURES OF ½ PSIG OR LESS, THE APPLIANCE NEED
NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM
THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL
GAS SHUT-OFF VALVE.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR
(Based upon a Pressure Drop of 0.5 inch Water Column
and 0.5 Specific Gravity Gas and max. gas press. of .5 psig)
LENGTH
IN
Nominal Iron Pipe Sizes, Millimeters
1" 1 1/4" 1 1/2"
METERS 1/2" 3/4"
2"
2 1/2"
3"
4"
3.0
6.1
9.1
51
35
28
24
21
19
18
17
16
15
13
12
11
105 199
410
278
225
193
170
155
143
135
126
117
105
95
615
428
346
290
264
237
220
202
190
182
161
146
135
1160 1845
3221
2255
1830
1552
1391
1259
1142
1083
1010
952
6735
4626
3748
3192
2840
2577
2372
2196
2108
1962
1757
1610
1464
73
59
50
44
40
37
35
32
30
27
25
23
142
110
94
83
76
70
64
60
57
51
47
42
805
644
556
492
445
410
381
357
337
299
278
249
1277
1031
878
776
703
659
600
571
542
483
439
401
12.2
15.2
18.3
21.3
24.4
27.4
30.5
38.1
45.7
53.3
864
776
717
88
61.0
10
21
40
82
126
234
375
688
1347
WARNING
THE HEATER IS NOT INTENDED FOR OPERATIONAT HIGHER
THAN 14” (3.5 kPa) WATER COLUMN (1/2 POUND PER SQUARE
INCH) SUPPLY GAS PRESSURE. HIGHER GAS PRESSURES
REQUIRE SUPPLEMENTALREDUCING SERVICE REGULATION.
EXPOSURE TO HIGHER GAS SUPPLYPRESSURE MAY CAUSE
DAMAGE TO THE GAS CONTROLS WHICH COULD RESULT IN
FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED
SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR
EMERGENCYMALFUNCTIONOFTHESUPPLYSYSTEM, THEGAS
VALVEMUSTBECHECKEDFORSAFEOPERATION. MAKESURE
THATTHEOUTSIDEVENTSONTHESUPPLYREGULATORSAND
THE SAFETY VENT VALVES ARE PROTECTED AGAINST
BLOCKAGE. THESEARE PARTS OF THE GAS SUPPLYSYSTEM,
NOT THE HEATER. VENT BLOCKAGE MAYOCCUR DURING ICE
STORMS.
GAS PIPING AND DIRT LEG INSTALLATION
FIGURE 9.
BEFOREPLACINGTHEHEATERINOPERATION,CHECKFORGAS
LEAKAGE. USE SOAP AND WATER SOLUTION OR OTHER
MATERIAL ACCEPTABLE FOR THE PURPOSE IN LOCATING
GAS LEAKS. DO NOT USE MATCHES, CANDLES, FLAME OR
OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
GAS METER SIZE – CITY GASES ONLY
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROMCONTAMINANTSINTHEGASWAYS. SUCHFOULINGMAY
CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLYTINNEDAND CERTIFIED FOR GAS SERVICE.
Be sure that the gas meter has sufficient capacity to supply the
full rated gas input of the water heater as well as the requirements
of all other gas fired equipment supplied by the meter. If the gas
meter is too small, request the gas company to install a larger
meter having adequate capacity.
BEFOREATTACHING THE GAS LINE, BE SURE THATALL GAS
PIPE IS CLEAN ON THE INSIDE.
GAS PRESSURE REGULATION
TOTRAPANYDIRTORFOREIGNMATERIALINTHEGASSUPPLY
LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR
DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG.
10) THE DIRT LEG MUST BE READILYACCESSIBLEAND NOT
SUBJECT TO FREEZING CONDITIONS. INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS
SUPPLIERS. REFER TO THE NATIONAL FUEL GAS CODE.
Main line gas pressure to the water heater should be between
8” w.c. (2 kPa) minimum (dynamic pressure or net pressure)
and 14” (3.5 kPa) maximum w.c. (static pressure). The inlet gas
pressure must not exceed the maximum value. A service
regulator is necessary if higher gas pressures are encountered,
see Table 10.
Due to pressure drop along gas supply line, to maintain
8” w.c. (2 kPa) minimum dynamic pressure, initial gas inlet
pressure must be set at higher than 8” w.c. (2 kPa). The gas
regulator must be properly sized to prevent unstable control or
excessive pressure drop.
To prevent damage, care must be taken not to apply too much
torque when attaching gas supply to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the
male threads of pipe joints. Do not apply compound to the first
two threads. Use compounds resistant to the action of liquefied
petroleum gases.
GAS VALVES
Figure 10 shows the gas control valve that is supplied on these
DISCONNECT THE APPLIANCE AND ITS MANUAL GAS SHUT-
OFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING heaters.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
to the local code authority having jurisdiction. Good practice
requires that all heavy piping be supported.
THERMOMETERS (Not supplied)
Thermometers should be obtained and field installed as shown
in the installation diagrams.
Thermometers are installed in the system as a means of
detecting the temperature of the outlet water supply.
RELIEF VALVE
This heater is equipped with an approved temperature and
pressure relief valve. ASME ratings cover pressure relief.
A.G.A ratings cover release rate with temperature actuation.
ROBERTSHAW® 7000 DERHC GAS CONTROL VALVE
FIGURE 10.
FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF
VALVE(S) MUST NOT BE REMOVED OR PLUGGED.
WATER LINE CONNECTIONS
Following are detailed installation diagrams for typical methods
of application for the water heaters.
In addition to the appliance relief valve, each remote storage
tank that may be used in conjunction with this appliance shall
also be installed with a properly sized, rated and approved
temperature (ANSI) and pressure (ASME) relief valve(s). This
relief valve shall comply with the standard for relief valves and
automatic gas shut-off devices for hot water supply systems,
ANSI Z21.22/CSA 4.4.
The water heater may be installed by itself, or with a separate
storage tank, on both single and two-temperature systems.
When used with a separate storage tank, the circulation may be
either by gravity or by means of a circulating pump. When a
circulating pump is used it is important to note that the flow rate
should be slow so that there will be a minimum of turbulence
inside the heater.
Your local code authority may have other specific relief valve
requirements.
If a water heater is installed in a closed water system, contact
the water supplier or local plumbing inspector on how to control
this situation.
WARNING
THE PURPOSE OF A RELIEF VALVE IS TOAVOID EXCESSIVE
PRESSUREORTEMPERATUREINTOTHESTEAMRANGE,WHICH
MAY CAUSE SCALDINGAT FIXTURES, TANK EXPLOSION, AND
SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED
BETWEEN THE RELIEF VALVEAND THE TANK.
CAUTION
A closed system will exist if a check valve (without bypass)
pressure reducing valve (without bypass), or a water meter
(without bypass) is installed in the cold water line between
the water heater and street main (or well).
ADRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO
DIRECTDISCHARGETOASAFELOCATIONTOAVOIDSCALDING
ORWATERDAMAGE. THISLINEMUSTNOTBEREDUCEDFROM
THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN
VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN
FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS
LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFECT
THE PURPOSE OF THE VALVEAND IS UNSAFE. DISCHARGE
LINE SHALLBE INSTALLED TOALLOW COMPLETE DRAINAGE
OF BOTH THE VALVEAND LINE.
Excessive pressure may develop causing premature tank failure
or intermittent relief valve operation. This is not a warranty failure.
An expansion tank or a similar device may be required in the
inlet supply line between the appliance and the meter or valve to
compensate for the thermal expansion of water under supply
pressure.
SYSTEM CONNECTIONS
The system installation must conform to these instructions and
® Robertshaw is a registered trademark of the Robertshaw Controls
Company Corporation.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION DIAGRAMS
ONE TEMPERATURE - ONE HEATER VERTICALSTORAGE TANK
FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION
DANGER
IF BUILDING COLD WATER SUPPLY HAS A
BACKFLOW PREVENTER, CHECK VALVE OR
WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF
WATER IN THE HOT WATER SYSTEM MUST BE
PROVIDED.
NOTE: CONNECT RETURN LINE FROM HOT
WATER RECIRCULATING LOOP (IF USED) TO
COLD WATER INLET LINE.
NOTE:
WHEN USING A State T-140, 200, 350 OR 400
STORAGE TANK, USE LOWER 3/4” OPENING FOR TANK TEMP. CONTROL
ONE TEMPERATURE - ONE HEATER HORIZONTALSTORAGE TANK
FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 23. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
CIRCULATING PUMP WIRING DIAGRAM
*PIPETOOPENDRAIN
INSTALL INACCORDANCE WITH LOCALCODES
14
Download from Www.Somanuals.com. All Manuals Search And Download.
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE
WITH OR WITHOUT BUILDING RECIRCULATION
*PIPE RELIEF VALVE TO OPEN DRAIN
NOTE: IF TEMPERED WATER
IS
RECIRCULATED, RETURN LINE
SHOULD BE CONNECTED AT
POINT “A”.
INSTALL IN ACCORDANCE WITH LOCAL
CODES
DANGER
TEMPERATURE SETTING SHOULD NOT
EXCEED SAFE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 23. IF
HIGHER PREHEAT TEMPERATURES ARE
NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD
VALVE FOR HOT WATER SUPPLIED TO
FIXTURES.
CAUTION: IF BUILDING COLD WATER
SUPPLY HAS A BACKFLOW PREVENTER,
CHECK VALVE OR WATER METER WITH
CHECK VALVE, PROVISIONS FOR
THERMAL EXPANSION OF WATER IN THE
HOT WATER SYSTEM MUST BE
PROVIDED.
WIRING DIAGRAM FOR TEMPERED WATER LOOP (IF USED)
CIRCULATING PUMPWIRING DIAGRAM
TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATURE
WITH OR WITHOUT BUILDING RECIRCULATION
15
Download from Www.Somanuals.com. All Manuals Search And Download.
TWO TEMPERATURE - THREE HEATERS (TWO PRE-HEATERS/ONE BOOSTER)
WITH OR WITHOUT BUILDING RECIRCULATION
DANGER
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A
BACKFLOW PREVENTER, CHECK VALVE OR WATER
METER WITH CHECK VALVE, PROVISIONS FOR
THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 23. IF
HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADDANANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO
FIXTURES.
FOR MULTIPLE HEATER INSTALLATION SEE
MANIFOLD KIT SPECIFICATIONS, PAGE 18.
TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)
WITH OR WITHOUT BUILDING RECIRCULATION
CIRCULATING PUMPWIRING DIAGRAM
* PIPE RELIEF VALVETO OPEN DRAIN.
CONNECT CIRCULATING LINE FROM FIXTURES, IF
USED, TO COLD WATER SUPPLY LINE OF PRE-
** 140°F TO 150°F SHOULD BE MAXIMUM HEATER.
WATERTEMPERATUREMAINTAINEDINTHE
PRE-HEATERS.
CONNECT CIRCULATINGLINEOF180°FORBOOSTED
WATER, IFUSED,TOINLETWATERLINETOBOOSTER.
120°F SHOULD BE THE MINIMUM
TEMPERATURE OF WATER IN THE PRE-
HEATERS.
INSTALLINACCORDANCE WITH LOCALCODES.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE
WITH RECIRCULATION OF SANITIZING LOOP
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE
AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON
PAGE 23. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO
OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE
FOR HOT WATER SUPPLIED TO FIXTURES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT
WATER SYSTEM MUST BE PROVIDED.
*PIPE TO OPEN DRAIN
INSTALL IN ACCORDANCE WITH LOCAL CODES
NOTE 1: TOGGLE SWITCH CONTROLS 180° WATER CIRCULATION.
INSTALL ON OR CLOSE TO DISHWASHING MACHINE.
TOGGLESWITCHMUSTBECLOSED(ON)DURINGTHERINSE
OPERATIONAND OPEN (OFF) WHEN DISHWASHER IS NOT
OPERATING OR WHEN ON LONG STANDBY.
NOTE 2: INSTALLLINETEMPERATURECONTROLINANUNINSULATED
TEEBEYONDTHE DISHWASHINGMACHINE TAKEOFFINTHE
SANITIZING LOOP. CONTROL SHOULD BE SETAT 185°F.
NOTE 3: ADJUSTPLUG COCK SO THE SANITIZING LOOPFLOW RATE
DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE
TANK.
NOTE 4: IF TEMPERED WATER IS RECIRCULATED, RETURN LINE
SHOULD BE CONNECTEDAT POINT “’A”.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
TWO UNIT MANIFOLD KIT
PART NO. 195702
MANIFOLD KITS
Precision cut type “L” all copper State manifold kits assure water
flow balance of all units. Without this balance, the full water
heating and storage potential of the system cannot be achieved.
Plus, the units with the higher water flow may have a shortened
life. Unions shown in piping diagrams are not included in the
manifold kits.
Dimensions shown are for minimum space occupied by the
water heaters assemblies.
Space for the barometric draft control assemblies, combustion
clearances and servicing must be added.
WARNING
FAILURE TO PROPERLY MANIFOLD MULTIPLE WATER
HEATERSAND PROVIDEADEQUATE STORAGE CAPACITY IN
ACCORDANCEWITHPROPERSIZINGTECHNIQUESCANRESULT
IN IMPROPER OPERATIONAND POSSIBLE FIRE RESULTING IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
HEATERS SHOULD BE MANIFOLDED IN PARALLEL FOR
UNIFORM HYDRONIC LOADING PER THE DIAGRAMS SHOWN
IN THIS MANUAL.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Open a nearby hot water faucet to permit the air in the system
to escape.
HEATER WIRING
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED
WITH 105°C WIRE OR ITS EQUIVALENT, EXCEPT IN THE
BURNER HOUSING USE 200°C WIRE.
3. Fully open the cold water inlet pipe valve allowing the heater
and piping to be filled.
4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.
The power burner is wired to the heater as shown in Figure 11
for GPG models and Figure 12 for GPV models. The model
and rating plate provided the electrical information needed
to size the complete heater branch supply.
PURGING
Gas line purging is required with new piping or systems in which
air has entered.
All electrical work must be installed in accordance with the
National Electrical Code and local requirements.
When installed, the appliance must be electrically grounded in
accordance with local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70-1987.
CAUTION
PURGINGSHOULDBEPERFORMEDBYPERSONSEXPERIENCED
IN THIS TYPE GAS SERVICE. TO AVOID RISK OR FIRE OR
EXPLOSION, PURGEDISCHARGEMUSTNOTENTERCONFINED
AREAOR SPACES WHERE IGNITION CAN OCCUR. THEAREA
MUST BE WELL VENTILATEDANDALLSOURCES OF IGNITION
MUST BE INACTIVATED OR REMOVED.
DONOTENERGIZETHEBRANCHCIRCUITBEFORETHEHEATER
TANK IS FILLED WITH WATER.
START UP
The following test equipment should be on hand: (all test
equipment must be acclimated to ambient temperature before
calibration and use.)
IMPORTANT
AUTHORIZED START-UP REQUIRED. Start-up by a State
Authorized GPG/GPV Start-Up Agent is required on the model
covered by this manual. Start-up and Operation of this unit by
other than an Authorized GPG/GPV Start-Up Agent will void the
warranty.
– CO2 indicator (Fyrite or similar) or O2 analyzer
– CO indicator (Monoxor or similar)
– Stack thermometer
If you have not already done so, contact your local State Sales
Representative or Authorized GPG/GPV Start-Up Agent and
set-up a date for the start-up service.
– Draft Gauge or inlined manometer
– Two U-Tube manometers or calibrated 0-10” and 0-35” w.c.
pressure gauges
The time to ask any questions you may have about your unit is
when the State Authorized GPG/GPV Start-Up Agent is there.
Please do not hesitate to ask the agent any questions which you
may have regarding the units start-up, operation or maintenance.
– Combination volt/ammeter
•
Attach a gas pressure gauge or manometer to upstream
side of main gas cock and a gas pressure gauge or
manometer to the manifold pressure tapping.
CAUTION
BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT,
MAKE SURE HEATER AND SYSTEMARE FILLED WITH WATER
ANDALLAIR IS EXPELLED FROM HEATERAND PIPING.
•
•
•
Check voltage at disconnect switch to make certain that it
matches that shown on the burner label.
Apply a few drops of No. 20 SAE non-detergent oil to motor
bearings.
NEVER OPERATE THE HEATER WITHOUT FIRST BEING
CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE
AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF
VALVE OPENING OF THE HEATER.
Drill max. 5/16” hole in breeching as close as possible to flue
connection on heater to install stack thermometer and
combustion analyzing equipment, see Figure 4.
FILLING
1. Close the heater drain valve by turning handle clockwise.
• You are now ready to begin the burner start-up procedure.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 11.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 12.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury
or loss of life.
BEFOREOPERATING:ENTIRESYSTEMMUSTBEFILLEDWITHWATERANDAIRPURGEDFROMALLLINES.
•
If you cannot reach your gas supplier, call the fire
department.
A. This appliance is equipped with an ignition device which
automatically lights the burner.
Do NOT try to light burner by hand.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don’t try to repair it, call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
B. BEFORE LIGHTING: Smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
WHATTO DO IFYOU SMELLGAS:
•
•
Do not try to light any appliance.
Do not touch any electric switch;
do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
E. Do not operate appliance unless unit is filled with water and
inlet lines are fully open.
FIGURE “A”
FIGURE “B”
“OFF POSITION”
“ON POSITION”
OPERATING INSTRUCTIONS
8. Turn on all electric power to the appliance.
9. Set thermostat to desired setting.
10. Turn switch to “ON” position.
1.
STOP! Read the safety information above on this
label.
2. Remove appliance thermostat cover. Rotate thermostat dial
counterclockwise to lowest setting.
11. Heater will automatically begin operation. Blower motor will
run approximately 40 seconds, then pilot gas valve will
open. Upon confirming the pilot flame the main gas valve
will open and the heater will operate in heating mode.
Reference “Sequence of Operation” section of manual for
details.
3. Turn off all electric power to the appliance.
4. This appliance is equipped an ignition device which
automatically lights the burner. Do NOTtry to light the burner
by hand.
5. Refer to diagrams above. Turn top knob of gas control
clockwise to “OFF” position (Figure A).
12. Heater is equipped with an ignition module which locks out
after one (1) unsuccessful ignition attempt. Blower motor
will continue to run. If lockout occurs, turn burner switch to
“OFF” position for at least one minute, then turn the switch
back to “ON”. Heater will automatically begin operation.
6. Wait five (5) minutes to clear out any gas. If you then smell
gas,
STOP! Follow “B” in the safety information above
on this label. If you don’t smell gas, go to next
step.
13. Replace thermostat control cover.
14. If the appliance will not operate, follow the instructions “TO
TURN OFF GAS APPLIANCE” and call your service
technician or gas supplier.
7. Turn top knob of gas control counterclockwise
“ON” (Figure B).
to
TO TURN OFF GAS TO APPLIANCE
4. Turn off all electric power to the appliance if service is to
1. Remove thermostat control cover.
be performed.
5. Turn top knob of gas control to the “OFF” position. Refer to
Step5of‘OPERATINGINSTRUCTION”above.
2. Set thermostat to lowest setting.
3. Turn burner switch to “OFF”.
6. Replace thermostat control cover.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
SEQUENCE OF OPERATION
DANGER
– Power on.
– Heater in standby mode.
– Thermostat calls for heat.
– Blower motor starts.
– Blower operation closes the normally open blower prover/
blocked outlet safety pressure switch.
– On proof of airflow, Honeywell S8680J flame control module
energized.
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE
THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT
WATER TEMPERATURES REQUIRED FOR AUTOMATIC
DISHWASHERAND LAUNDRYUSE CAN CAUSE SCALD BURNS
RESULTING IN SERIOUS PERSONALINJURYAND/OR DEATH.
THE TEMPERATUREAT WHICH INJURYOCCURS VARIES WITH
THE PERSON'S AGE AND TIME OF EXPOSURE. THE SLOWER
RESPONSETIMEOFCHILDREN, AGEDORDISABLEDPERSONS
INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL
CHILDREN TO USE A HOT WATER TAP, OR TO DRAW THEIR
OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED
PERSON UNATTENDED INABATHTUB OR SHOWER.
– 45 seconds prepurge cycle begins.
– Following prepurge cycle, the pilot gas valve is energized.
– At the same time, the electronic spark generator in the module
produces a high voltage spark pulse output.
– The voltage generates a spark at the ignitor that lights the
pilot.
THEWATERHEATERSHOULDBELOCATEDINANAREAWHERE
THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET
TEMPERATURES.
– If the pilot does not light (or flame signal is less than 1 micro
A) within 15 seconds system locks out and must be reset by
turning burner switch “OFF” for a minimum of 1 minute. During
system lockout, blower still runs.
SETTING THE WATER HEATER TEMPERATUREAT 120°F (49°C)
WILL REDUCE THE RISK OF SCALDS. Some states or provinces
require settings at specific lower temperatures.
– When the pilot flame is established (flame is sensed by flame
rod), the main gas valve is energized.
– Main gas flows to main burner where it’s ignited by the pilot
flame. Now heater is in Heating Mode.
Below you will find listed the approximate time-to-burn
relationship for normal adult skin. Short repeated heating cycles
caused by small hot water uses can cause temperatures at the
point of use to exceed the thermostat setting by up to 20F°. If you
experience this type of use, you should consider using lower
temperature settings to reduce scald hazards.
– During the Heating Mode:
If gas line pressure drops below the setting point, the flame
module is de-energized, gas valves closed, blower still runs.
If gas line pressure drops below the setting point then gas
line pressure increases to above the setpoint, heater starts
again from purging cycle.
Temperature
Setting
180°F (82°C)
170°F (77°C)
160°F (71°C)
150°F (66°C)
140°F (60°C)
130°F (54°C)
120°F (49°C)
Time to Produce 2nd & 3rd
Degree Burns on Adult Skin
Nearly instantaneous
If gas line pressure fluctuates around the setpoint too quick
(less than a second) burner may still run with excessive gas
valve ON/OFF cycle you must turn off the unit immediately,
re-adjust the gas line regulator and/or install a larger gas
supply line!
Nearly instantaneous
About 1/2 second
About 1-1/2 seconds
Less than 5 seconds
About 30 seconds
If the blower inlet and/or intake hood, or flue outlet/hood is/
are blocked for any reason, the safety switches will open,
which will de-energize the flame control module.
More than 5 minutes
– The spark generator is off.
– The flame module monitors pilot flame current. Should the
flame failure occur during the Heating Mode, the unit will start
again from purging cycle.
– Thermostat is satisfied, switch opens.
– Power is interrupted to the flame control module and blower
motor. Gas valves are closed.
Valves for reducing point-of-use temperature by mixing cold and
hot water are available. Also available are inexpensive devices
that attach to faucets to limit hot water temperatures. Contact a
licensed plumber or the local plumbing authority.
– Heater is in Standby Mode.
The water temperature is controlled by a thermostat, fig. 2, which
has two sensing elements. One sensor is located near the top
of the tank and the other is near the center. The thermostat is set
in the lowest position before the heater leaves the factory.
– Thermostat is satisfied, switch opens.
– Power is interrupted to burner, turning off blower and ignition
control module. Solenoid and main gas valves are closed.
– Insufficient blower pressure causes safety pressure switches
to open.
The dial is adjustable and may be set for 1200 (49°C) to 1800F
(82°C) water temperature, but 1200F (49°C) is the recommended
starting point. It is suggested the dial be placed on the lowest
setting which produces an acceptable hot water supply. This
will always give the most energy efficient operation. The
temperature control has a 4F° fixed differential.
WATER TEMPERATURE CONTROL
ADJUSTMENT PROCEDURE (Initial Start-Up)
A minimum dynamic gas supply pressure of 8” w.c. for natural
gas is required before making any adjustment to the gas control
pressure regulator. Attempts to adjust the regulator during
periods of low gas supply pressure could result in overfiring of
the heater when the gas supply pressure returns to normal.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Check gas line pressure with a manometer.
it’s a high elevation application and/or a direct vent (long air
intake vent) application.
Set initial gas line pressure at 9-10” w.c. before turning the
heater “ON”.
1. Fire Rate Adjustment (including direct vent installation).
Read gas line pressure and gas manifold pressure when
the heater main gas is “ON”.
a.
b.
Make sure the gas supply line pressure reads
8” w.c. (2 kPa) or higher when the heater is running.
Adjust gas line regulator setting if the gas line pressure drops
below 8” w.c. when heater main gas is “ON”.
Remove the pressure regulator cover screw
(Figure 10) and adjust the pressure by tuning the
adjustment screw w/a small screwdriver clockwise to
increase gas pressure into the burner and fire rate.
Counterclockwise to decrease gas pressure and input
rate.
Check heater gas manifold pressure (see Table 10) using a
manometer connected to the manifold pressure tap on the
Robertshaw gas control valve, see Figure 10.
Important Note: Use gas manifold pressure as initial setup
only. The final air and gas settings should be based on fire rate
and flue gas 02/C02 reading, see Table 10 for normal 02/C02
reading.
c.
Clock gas meter, repeat above Step (b) to achieve the
specific input rate.
d.
Measure flue gas O2 and/or CO2 (see Table 10) for
acceptable O2/CO2 range.
WARNING
Excessive gas line pressure drop and/or burner manifold
pressure too low may cause burner start/operate with
excessive noise!
If the O2 or CO2 reading is within the acceptable range,
then proceed to Step (f).
If the O2 or CO2 reading is out of range, adjust air
damper is required.
2. Cycle the burner “ON” and “OFF” several times to check its
operation. Make sure the gas line pressure is below
14” w.c. when burner is “OFF”. If gas line pressure exceeds
14” w.c. when the burner is off, the gas supply line size must
be increased to correct this problem (see Table 9 for gas
pipe size).
e.
f.
Repeat Steps (b), (c), (d) if air damper is adjusted.
Cycle heater ON/OFF.
g.
Replace the gas regulator cover, pressure tap and
tighten the damper center bolt.
3. Check the operation of the limiting and operating controls.
4. Check the vent system seams and joints and ensure that
there is no discharge of flue products into the room. For
standard vertical vent systems, check the barometric damper
control to make sure it operates freely and there is no
discharge of flue products into the room.
2. Adjustment for Low NOx Emission Application.
The water heater is preset at factory for Low Nox emission
combustion. Due to the installation variations, fine-tune
adjustments may be required. To lower NOx emission level
(30PPM corrected at 3% O2 or lower is required by SCAQMD),
air damper setting may need to be slightly increased. To
increase air damper setting, loosen the center nut of the inlet
air damper, rotate the damper clockwise slightly, then tighten
the center nut. After re-set the air damper, cycle heater
ON/OFF and check fire-rate and flue gas CO2/O2 reading.
5. Check the input rate by clocking the gas meter.
ADJUSTMENT PROCEDURE FOR FIRE-RATE,
LOW NOX AND HIGH ELEVATION (Fine-Tune)
An acceptable input rate is within 2% of the rated input for the
model. Should it be necessary to adjust the gas pressure to the
burner and/or air damper of the blower to obtain the full input
rate, these steps should be followed:
3. Adjustment for High Elevation Application
Installation above 2000 feet sea level require new air damper
settings. All the final settings should be based on flue gas
CO2/O2 reading, see Table 10. To increase air damper setting,
loosen the center bolt of the inlet air damper, rotate the damper
clockwise slightly, then tighten the center bolt. After re-setting
the air damper, cycle heater ON/OFF and check fire-rate and
flue gas CO2/O2 reading.
WARNING
Never set burner combustion too lean (causing noisy
operation) or too rich (causing combustion chamber premature
failure) see Table 10 for proper settings.
WARNING
WARNING
Never set air damper outside of its adjustment range of the
rated fire rate unless authorized by a State Service Center.
UNDERNOCIRCUMSTANCESSHOULDTHEINPUTRATEEXCEED
THE INPUT RATE SHOWN IN THE HEATER RATING PLATE.
OVERFIRING COULD RESULT IN DAMAGE OR SOOTING OF THE
HEATER.
Important Note: Final gas and air settings should be based on
flue gas CO2 or O2 reading (see Table 10). Increase burner
manifold pressure will increase fire rate and flue gas CO2 reading.
Increase air damper setting will decrease fire rate and decrease
flue gas CO2 reading. Adjustable air damper is preset for the
rated fire-rate prior to delivery, should not be re-adjusted unless
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUALGAS CONTROLVALVE
TO THE APPLIANCE.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
PREMIX LOW NOx BURNER - EXPLODED VIEW FOR GPG MODELS
FIGURE 13.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
PREMIX LOW NOx BURNER - EXPLODED VIEW FOR GPV MODELS
FIGURE 14.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
to the following table. A periodic inspection of the venting system
should be made. Where used the water heating system
circulating pump should be oiled.
GENERAL INFORMATION
POWER BURNER
MAINTENANCE SCHEDULE
The initial start-up procedure of the gas power burner is provided
on page 18 thru 21. Refer to Figure 12, burner exploded view for
burner components location.
Following are the instructions for performing some of the
recommended maintenance. Power burner inspection and
adjustment should be performed by a competent technician.
The sequence of operation of the power burner is provided on
page 15. For detailed Power Burner Operation, Maintenance
and Troubleshooting refer to the separate Power Burner Manual
provided with this water heater.
MAINTENANCESCHEDULE
Component
Operation
Interval
Required
Sediment
Removal
THERMOSTAT
Tank
Monthly
Flushing
It is suggested the thermostat be turned to the lowest setting,
which satisfies the hot water requirements of the system. This
helps minimize scale formation in the heater.
Lime Scale
Removal
UN-LIME®
Delimer
Semi-Annually
Semi-Annually
Relief Valve
Inspect
Oiling
HIGH LIMIT
SAE No. 20
Four Months non-detergent
motor oil
The high limit (not adjustable) is factory set to cutout at 205°F
(96°C). The high limit switch must be manually reset by
depressing the reset button on front of the control when water
temperature drops to about 180°F (82°C).
Circulating Pump(1)
Clean Inlet
PowerBurnerBlower Screen and
Blower Wheel
As Required
Soft Brush
GASANDAIR SUPPLYSPECIFICATIONS TABLE 10
Model
Min. Dynamic Gas
Supply Line
Pressure
Max. Static Gas
Supply Line
Pressure
GPG/GPV-540A GPG/GPV-650A GPG/GPV-750A
8” w.c. (2 kPa) When heater is ON
Power Burner and
Ignition Device(2)
Inspection Semi-Annually
14” w.c. (3.5 kPa) When heater is OFF
Make sure gate
swings freely,
no spillage
Barometric Damper
Inspect
Every 3
Months
Gas Manifold
Pressure
4.7”w.c. 1.1 kPa)
(Ref.)*
4.7”w.c. (1.1kPa)
(Ref.)*
4.7”w.c. (1.1 kPa)
(Ref.)*
into room
Gas Orifice Size
Air Inlet Damper
Dial Setting
Combustion
Emissions
1/2”
11/16”
N/A
4.5**
5.6**
3**
Flue
Cleaning
Inspect
As Required
Wire Brush
Flue Gas O2: 5 - 6.5%**
(or CO2 reading 8 - 9%)
Every 3
Months
Joints should
be sealed
Range
Vent System
(1) If furnished with oiling provisions.
(2) If flange gasket is damaged, it must be replaced.
*
Note: Flue gas excess O2 below 3% may cause combustion
chamber premature failure; flue gas excess O2 above 7%
may cause rough operation or incomplete combustion. Final
manifold pressure settings should be based on flue O2/CO2
reading!
ELECTRICAL SERVICING
CAUTION
** Note: Air inlet damper setting needs to be adjusted at field for
direct vent and/or high elevation installations.
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPERAND DANGEROUS OPERATION.
MAINTENANCE
VERIFYPROPER OPERATIONAFTER SERVICING.
FLUSHING
GENERAL
KEEPAPPLIANCEAREACLEARANDFREEFROMCOMBUSTIBLE
MATERIALS, GASOLINEANDOTHERFLAMMABLEVAPORSAND
LIQUIDS. (SEE WARNING PAGE 6).
1. Turn off the heater electrical disconnect switch.
2. Open the drain valve and allow water to flow until it runs clean.
3. Close the drain valve when finished flushing.
Water heater maintenance includes periodic tank flushing and
cleaning, and removal of lime scale. The power burner should
be inspected and adjusted to maintain proper combustion. Refer
4. Turn on the heater electrical disconnect switch.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
State UN•LIME® Delimer is an easy to handle patented food
grade acid formulated specifically for lime scale removal from
all types of water using equipment. Available in 1 gallon (part
no. 4763) and 5 gallon (part no. 4813) sizes. Hydrochloric base
acids are not recommended for use on glass-lined tanks.
DRAINING
The heater must be drained if it is to be shut down and exposed
to freezing temperatures. Maintenance and service procedures
may also require draining the heater.
1. Turn off the heater electrical disconnect switch.
2. Close the cold water inlet valve to heater.
3. Open a nearby hot water faucet to vent the system.
4. Open the heater drain valve.
State Form No. 4800 entitled “Why, When and How”, describes
tank cleaning methods and materials. UN•LIME® and the booklet
may be obtained through your State dealer or distributor.
The cleanout opening is shown in Figure 9.
To clean heater through cleanout opening, proceed as follows:
5. If the heater is being drained for an extended shutdown, it is
suggested the drain valve be left open this period.
1. Turn off water inlet valve, the heater electrical disconnect
switch and open drain valve.
• Follow FILLING instructions when restoring hot water service.
2. Remove outer cover plate from lower side of heater jacket.
3. Remove cover from cleanout opening.
SEDIMENT REMOVAL
Waterborne impurities consist of the particles of soil and sand
which settle out and form a layer of sediment on the bottom of
the tank.
4. Remove lime, scale or sediment using care not to damage
the glass lining.
5. Inspect cleanout plate gasket; if new gasket is required,
replace with State part no. 99038.
For convenience, sediment removal and lime scale removal
should be performed at the same time.
6. Install cleanout plate. Be sure to draw plate up tight by
tightening screws securely.
LIME SCALE REMOVAL
7. Close drain valve, open water inlet line and turn on the burner
electrical disconnect switch.
The amount of calcium carbonate (lime) released from water is
in direct proportion to water temperature and usage. The higher
the water temperature or water usage, the more lime deposits
are dropped out of the water. This is the lime scale which forms
in pipes, heaters and on cooking utensils.
8. Check for water leakage.
9. Replace outer jacket cover plate.
RELIEF VALVE
Lime accumulation not only reduces the life of the equipment
but also reduces efficiency of the heater and increases fuel
consumption.
At least twice a year, the temperature and pressure relief valve
should be checked to ensure that it is in operating condition. To
The usage of water softening equipment greatly reduces the check the relief valve, lift the lever at the end of the valve several
hardness of the water. However, this equipment does not always
remove all of the hardness (lime). For this reason it is
recommended that a regular schedule for deliming be
maintained.
times. The valve should seat properly and operate freely.
CAUTION
BEFORE MANUALLYOPERATINGARELIEF VALVE, MAKE SURE
THATADRAIN LINE HAS BEENATTACHED TO THE VALVE TO
DIRECTTHEDISCHARGETOANOPENDRAIN. FAILURETOTAKE
THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY
HOT WATER, PASSING OUT OF THE VALVE, DURING THIS
CHECKINGOPERATION.
The depth of lime build-up should be measured periodically.
Heaters will have about 3” (76 mm) of lime build-up when the
level of lime has reached the bottom of the cleanout opening or
about 1” of lime build-up if it has reached the drain valve opening.
A schedule for deliming should be set up; based on the amount
of time it would take for a 1” (25.4 mm) build-up of lime.
If the temperature and pressure relief valve on the heater
discharges periodically or continuously, it may be due to thermal
expansion of water in a closed water supply system, or, it may be
due to faulty relief valve.
Example 1 – Initial inspection shows 1/2” (12.7 mm) of lime
accumulation. Therefore, the heater can be
delimed once a year.
Thermal expansion is the normal response of water when it is
heated. In a closed system, thermal expansion will cause the
system pressure to build until the relief valve actuation pressure
is equaled. Then, the relief valve will open, allowing some water
to escape, slightly lowering the pressure.
Example 2 – Initial inspection shows 2” (50.8 mm) of lime
accumulation. Therefore, the heater should be
delimed every 3 months.
Sediment and lime scale removal may be accomplished through
the cleanout opening furnished on the heater, see FEATURES.
The heater must be drained. See DRAINING, before removing
cleanout cover on tank.
Contact your water supplier or local plumbing inspector on how
to control this situation.
To dissolve and remove the more stubborn mineral deposits, Two common corrections are listed in the CHECKLIST AND
State UN•LIME® Professional delimer should be used.
SERVICE INFORMATION that appears later in this manual.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
ABOVEALL, DONOTPLUGTHETEMPERATUREANDPRESSURE
RELIEF VALVE. THIS IS NOTASOLUTIONAND CAN CREATEA
HAZARDOUS SITUATION.
CIRCULATING PUMP
The water heating system may include a circulating pump. Where
used, it should be lubricated as directed by the circulator
manufacturer.
LOW EMISSION POWER BURNER
FIGURE 15
KEEP THE AREA AROUND THE BURNER CLEAR AND FREE OF
COMBUSTIBLEMATERIALS, GASOLINEOROTHERFLAMMABLE
LIQUIDS OR VAPORS. DO NOT OBSTRUCT BURNER AIR
OPENINGS OR VENTILATION GRILLES FOR COMBUSTIONAIR.
REMOVE LINTACCUMULATION FROMAIR INTAKE GRILL.
To test gate for operation, gently tap gate and observe. DO NOT
OIL.
Adjust the number of counter-weight washers on the control to
maintain a negative draft of 0.02” to 0.04” w.c. in the venting. See
VERTICAL VENTING, page 8.
The main burner flame should be visually checked once a year
for proper operation. This can be observed through the “peep
sight” port on the burner mounting plate. Burner flame should
be kept blue.
NOTE THAT THIS CONTROL WILL ONLY BE PRESENT IN A
VERTICALVENT INSTALLATION.
At least annually, contact a qualified service agency for burner
cleaning and other routine maintenance. For burner related
Maintenance Schedule, Troubleshooting, Flame Rod, Ignitor,
Thermal Cut-Off Switch Replacement Procedures, use burner
Operation & Maintenance Manual provided with this heater.
VENT SYSTEM
Examine the vent system every 3 months. Points of inspection
are as follows:
1. Check for obstructions and/or deterioration of vent piping and
vent hood. Replace immediately where needed.
CLEANING FLUES
The following describes how to gain access to the tank flues for
cleaning if necessary.
2. Vent pipe and vent hood screen should be cleaned of foreign
material and soot. The screen is located inside the vent
hood outlet and is accessible from the outside of the hood.
Do not reach inside the vent when the heater is in operation.
1. Turn off the heater electrical disconnect switch.
2. Remove the vent connector from on top of the heater.
3. Check all vent system connections for leakage and re-seal
as required using Hi Temp Silicone sealer or equivalent.
3. Remove the jacket top from the heater by taking out the screws
and lifting it off.
4. Remove the insulation from the top of the heater.
CHECKLIST AND SERVICE
5. Remove the inner cover by taking out the pipe collar around
the water inlet and outlet nipple.
INFORMATION
6. The flue baffles may now be removed by lifting out.
IMPORTANT
7. Using a wire brush, a nylon brush must not be used, remove
soot from flue passages in heater tank.
The installer may be able to observe and correct certain problems
which might arise when the unit is put into operation or when it is
re-fired after a prolonged shutdown. HOWEVER, it is
recommended that only qualified servicemen, using appropriate
test equipment, be allowed to service the heater.
CAUTION
While cleaning tank flue passages, care must be taken that
brush does not come in contact with neither the combustion
chamber lining nor the baffle or funnel which are an integral
part of the combustion chamber, as damage could occur. The
flue passages are 48-1/2” (1,232 mm) long x 3” (76.2 mm)
diameter.
BE SURE TO TURN OFF THE ELECTRICITY WHENEVER
POSSIBLE ORAPPROPRIATE WHILE CHECKING EQUIPMENT.
BURNER OPERATIONALPROBLEMS
8. Upon completion of cleaning, return heater to operation by
following this procedure in reverse.
1. Refer to TROUBLESHOOTING for comprehensive service
information provided with both heater and burner manuals.
BAROMETRIC DRAFT CONTROL
- FOR GPG MODELS
NOT ENOUGH OR NO HOT WATER
The heater is equipped with a double acting barometric draft
control as shown in Figure 15. The damper gate must pivot
freely in the ring guides.
1. Be certain the electrical disconnect switch serving the water
heater is in the ON position.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Check the fuses.
•
•
•
Excessive water pressure
Excessive water temperature
Faulty relief valve
•
The electrical disconnect switch usually contains fuses.
3. The capacity of the heater may have been exceeded by a
large demand for hot water.
Excessive water pressure is the most common cause of relief
valve leakage. It is often caused by a “closed system”. If a check
valve, back flow preventer, or pressure-reducing valve is in the
inlet system it will not permit the expanded hot water volume to
equalize pressure with the main. The relief valve must release
this water or the water heater or plumbing system will be
damaged. Refer to MAINTENANCE – RELIEF VALVES.
4. Colder incoming water temperature will lengthen the time
required to heat water to the desired temperature.
•
If the heater was installed when incoming water
temperature was warm, colder water creates the effect
of less hot water.
When such a condition is encountered, local codes or inspection
agency should be consulted to determine which system is
acceptable in your area. These may consist of:
5. Look for hot water wastage and leaking or open hot water
faucets.
6. Sediment or lime scale may be affecting water heater
operation. Refer to MAINTENANCE for details.
•
•
Installation of a second relief valve with lower setting than the
primary relief valve.
7. Heater or burner may be dirty.
An expansion tank of suitable size and pressure rating and
provision to avoid water logging.
•
•
Clean all heater flue pipes and flue connector, see
MAINTENANCE.
HOT WATER ODOR
Have burner properly cleaned and readjusted.
On occasion, hot water may develop a strong odor. If this occurs,
drain the heater completely, flush thoroughly, and refill. If the
problem persists, chlorinating of the heater and replacement of
the factory installed magnesium anodes with aluminum anodes
may correct the condition.
8. Burner may not be firing at proper rate.
Check gas pressure
9. Burner fan wheel may be dirty.
•
Occasionally water softener companies recommend removal of
heater anodes for odor reasons.
•
Clean fan wheel with a soft brush.
10. Reset button on high limit control (Figure 1) has operated.
Press reset button.
CAUTION
Unauthorized removal of the anode(s) will void the warranty.
For further information contact your dealer.
WATER IS TOO HOT
1. Refer to WATER TEMPERATURE CONTROL.
WATER HEATER MAKES SOUNDS
TROUBLESHOOTING
WARNING
1. Sediment or lime scale accumulation cause rumbling and
pounding noises when the heater is operating.
JUMPING OUT COMPONENTS AND/OR CIRCUITS DURING
TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH
THE POWER BURNER’S OPERATING SEQUENCEAND IGNITION
SAFETY. IFYOU DO NOT HAVE THE PROPER TEST EQUIPMENT,
I.E. A VOLT-OHM METER AND A MICRO-AMMETER DO NOT
ATTEMPT TO TROUBLESHOOT OR REPAIR STATE EQUIPMENT.
•
The sounds are normal, however, the tank bottom should
be cleaned. Refer to MAINTENANCE for details.
2. Some of the electrical components of the water heater make
sounds which are normal.
ALTERING THE IGNITION MODULE AND/OR CONTROL BOX
WIRING INANYWAYCOULD RESULT IN INTERNALDAMAGE TO
THE MODULE CIRCUITS, POSSIBLYALTERING THE IGNITION
SEQUENCEALLOWING GAS VALVES TO OPEN BEFORE THE
HOT SURFACE IGNITER IS UP TO IGNITION TEMPERATURE.
•
•
Contacts click or snap as the heater starts and stops.
Transformers often hum.
NOTE: ANYBYPASS ORALTERATION OFTHE UNITS SAFETIES
WATER LEAKAGE IS SUSPECTED
WILLRESULTIN VOIDING THEAPPLIANCE WARRANTY.
1. Check to see if the water heater drain valve is tightly closed.
Also check the cleanout opening for leakage.
Before performing any troubleshooting familiarize yourself with
the particular appliance. State power burners are supplied with
Honeywell® ignition control systems and Robertshaw® gas
control valves, see Figures 10 and 11.
2. The apparent leakage may be condensation that forms on
cool surfaces of the heater and piping.
Refer to the SEQUENCE OF OPERATION and burner exploded
view, see Figure 12 and the wiring diagram located on page 20,
3. If the outlet of the relief valve is leaking it may represent:
®Honeywell is a registered trademark of Honeywell International Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
30
and the troubleshooting section of burner manual before
continuing.
•
•
•
Check for the continuity between the flame rod and
sensor connection at Honeywell flame control module
by the ohm meter.
Make sure the appliance is connected to a 120 Vac power supply,
burner switch is “ON” and manual gas valve is in the “ON”
position, and all electrical connections are secure before
continuing to troubleshoot this appliance.
Check for ignitor wire connections and spark leakage
(call AOS service center for steps of spark leakage
checking).
MOTOR WILL NOT RUN
Following burner manual instructions to re-install the
pilot assembly.
1. Confirm 120 Vac. Also, to verify correct polarity, check for
120 Vac between black wire and G.
6. Turn on the Robertshaw gas valve, turn the burner switch to
“ON” position. Cycle the heater ON/OFF several times to
ensure the problem is solved.
If there is no voltage, check for a loose connection or open
switch at the high limit or thermostat.
2. If there is 120 volts between black wire and white wire, check
for loose connections or a locked rotor. If the rotor cannot be
freed the motor and blower assembly must be replaced.
MOTORRUNSCONTINUOUSLY, PREPURGETIMEELAPSESBUT
MAIN FLAME NOT ESTABLISHED (BURNER LIGHT NEVER ON)
1. When the heater is first installed, gas line must be purged
properly prior to start-up. This heater is equipped with a flame
control module that only allows one “trial for ignition” for
15 seconds and locks out if no flame signal is detected. For
initial start-up, two or more resets may be required to ensure
that all the air has been purged from the gas pilot line. To
reset the heater, turn the burner power switch to “OFF” position
for at least one minute, then turn it back “ON”.
BURNER LOCKOUT ONCE IN A WHILE
Under this condition, the burner operates properly for days, and
burner lockout occurs once in a while. The root causes for the
burner occasional lockout include: (1) Gas inlet pressure too
low; (2) Condensation over the ignitor area; (3) the pilot flame is
too weak to light the main flame reliably; (4) the pilot air/gas ratio
is out of range causing pilot flame to be unreliable.
2. Check for gas supply line manual valves in “ON” position,
and line pressure. Make sure the pilot manual gas cock
(nearby the main gas valve) is fully open.
1. Turn burner switch to “OFF” position and turn off the main
gas valve (Robertshaw®).
2. Install manometers for gas inlet pressure, manifold pressure,
and pilot gas pressure, see Figure 12 for the pressure ports
location).
3. After the 45-seconds prepurge cycle, the pilot gas valve
(mounted on the panel) “click” sound should be heard. If you
hear the pilot gas energized, proceed to Step 5.
3. Check for the gas inlet pressure, reset the service regulator
(if required) to get 9” w.c. (2.2 kPa) - 10” w.c. (2.4 kPa) inlet
pressure while the burner is in the “OFF” position.
4. Check 24 Vac control circuit in the following systematic
approach:
4. Turn the burner “ON”,
•
Check for 24V between “24V” and “GND” of Honeywell Flame
Control Module, which is located inside the burner control
panel. If voltage is OK, proceed to Step 5.
•
Take blower pressure at the pressure port during the
purge cycle, see Figure 12 for location.
•
If there’s no voltage, check for 24V between the air switch
“COM” terminal and GND (the air switch is mounted on the
control panel, the switch cover needs to be removed to access
the wiring terminal “COM” and “NO”). If there’s no 24 V, check
for a loose connection between the 24V transformer and air
switch, or a defective transformer.
•
Take the pilot gas pressure at the same pressure port
during the ignition period (following 45 seconds purge
cycle).
•
•
The pilot gas pressure should be 0.6” - 0.9” w.c. higher
than blower pressure, if not, adjust the pilot gas regulator
(during the ignition cycle, see Figure 12.
•
If there’s 24V at “COM” terminal, check for 24V between the
air switch terminal “NO” (normally open) and GND. If there’s
no 24V, the air switch pressure may be set too high or a
defective air switch or loose connections of pressure sensing
tubings. To lower the air switch setting, make sure the blower
is running and blower wheel and air inlet are free from dirt,
counterclockwise turn the switch setting-screw until the switch
is closed. Call the State Technical Center before you reset
the switch.
If burner lights on during the ignition cycle, cycle the
unit on/off several times to ensure pilot system is
reliable. Turn off the burner, then follow Step 6.
5. Turn the burner “OFF”, follow burner manual instructions to
remove the pilot assembly (also refer to Figure 12 in this
manual) and procedures to check pilot assembly. Items to
check for the pilot system include:
•
•
•
Check for condensation over ignitor area.
Check for the ignitor gap (1/8” - 3/16”).
•
•
If there’s 24V at “NO” terminal of the air switch, check for 24V
at the air intake pressure switch connectors, (this switch is
only supplied for direct vent systems). If there’s no 24V at the
switch connectors, check for loose connections, air intake
blockage, or a defective air switch.
Check for the thermal cutoff continuity by ohm meter,
replace it if the thermal cutoff is open.
•
Check for the low gas pressure switch by ohm meter
(while pilot gas pressure is 7” w.c. [1.7 kPa] or higher).
Do not proceed to Step 5 unless 24V is detected at “24V”
terminal of the Honeywell Module.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
5. As soon as the pilot gas valve is energized, check for the 2. Check for 24V at the Robertshaw gas valve when the main
gas light is on. If there’s no 24V at the valve, check loose wire
connection.
burner pilot flame through the burner peek-hole. If the pilot
flame is established inside the burner, then proceed to
Step 6.
3. Check for gas supply line pressure. The gas line pressure
before the valve should be maintained at minimum
8” w.c. when main flame is “ON”. If the gas line pressure
drops below 8” w.c. (2 kPa), the service regulator pressure
setting must be increased to keep 8” w.c. (2 kPa) minimum
gas pressure. After adjusting the gas regulator setting, turn
off the heater, make sure the gas line pressure does not
exceed 14” w.c. (3.5 kPa) if it does exceed 14” w.c. (3.5 kPa)
static pressure, the gas supply line size must be increased
accordingly to avoid gas line pressure exceeding 14” w.c.
(3.5 kPa)
•
•
Turn the burner switch to “OFF” position for at least one minute
to reset the heater.
Check for 24V between “PV” terminal and “MV/PV” terminal
after 45 seconds prepurge cycle (this 24V may only last
15 seconds starting after 45S prepurge). If there’s no 24V at
the “PV” terminal ever, and there’s 24V at “24V” terminal, the
Honeywell flame control module needs to be replaced.
•
•
If 24V is detected for a period of 15 seconds, check for the
changes of gas supply line pressure when the pilot gas valve
is energized. If no visible pressure change during the pilot
ignition period, check for loose connection of the pilot valve or
a defective pilot gas valve.
4. Check the gas valve manifold pressure (refer to Table 10),
see ADJUSTMENT PROCEDURE to adjust the manifold
pressure.
5. Check for defective gas valve for failing to open or shut off.
Adjust the pilot gas regulator setting during the pilot ignition
period (15 seconds). Do not set too much or too little pilot
gas. This adjustment should only be performed during the
15 seconds ignition period. A clockwise or counter-clockwise
0.5 to 1 turn should be able to correct the problem. Refer to
burner manual for detailed pilot gas setting procedure.
6. Verify that the air supply is adequate. The air inlet screen or
blower wheel may be restricted.
7. Check the installation for proper ventilation, see AIR
REQUIREMENTS.
•
If still no pilot flame inside the burner, check for the spark 8. Verify the air switch setting is not too high.
ignitor wiring, ignitor tip location and visually check the spark
(burner pilot assembly needs to be taken out for the visual 9. Check the venting system for the correct sizing, excessive or
check). Refer to the burner manual for detailed spark ignition
troubleshooting procedures.
insufficient draft, and proper operation of the barometric draft
control, see VENTING.
6. Pilot flame established but not detected by the flame control
module. Use Micro Amp meter to measure flame signal during
the pilot ignition period. Refer to burner manual for testing
procedures.
NOISYBURNER OPERATION
1. Check for flue gas excess O2 or CO2 reading (refer to Table
10). If combustion is too lean (flue gas O2 reads more than
7.5%), the combustion flame front may not be stable, which
will cause noisy operation. See ADJUSTMENT.
•
If pilot flame is confirmed visually through the burner peek
hole, and the flame signal is zero, the thermal-cutoff safety
switch (mounted nearby the flame rod, inside the burner mixing
chamber) may be broken or check for loose wire connections
or low gas switch (mounted inside control panel) may be
broken. If the thermal cutoff switch or low gas switch is broken
2. Check the venting system for the correct sizing, excess or
insufficient draft, and proper operation of the barometric draft
control, see VENTING.
(by checking the switch continuity), the switches must be 3. If the burner operation is still noisy, then remove the burner,
replaced before the heater can operate again.
examine the burner diffuser, blast-tube tip, anti-flashback
corrugated tube, center mixing, refer to the burner manual for
details.
•
•
If it’s confirmed that the thermal cutoff switch is damaged
(open), call the State Technical Center to analyze the root
cause (too lean combustion) and proper gas/air ratio
adjustment. Flashback will cause the thermal cutoff switch
broken (open).
GAS FAILS TO SHUT OFF
Check for defective gas valve or thermostat. If operation is
incorrect, replace.
If the flame signal is not zero but below 1µA, relocate flame
rod or replace flame rod will be required. Refer to burner
manual for detailed procedure of replacing flame rod.
REPLACEMENT PARTS
Replacement parts may be ordered through State
dealers, unauthorized servicers or distributors. Refer to
the Yellow Pages for where to call or contact the State Water
Heaters, 500 Lindahl Parkway, Ashland City, TN 37015, 1-800-
When ordering parts be sure to state the quantity, part number
and description of the items including the complete model and
serial number as it appears on the product. Refer to the parts
list for more information.
MOTOR RUNS CONTINUOUSLY, BURNER LIGHTS ON
MOMENTARILYTHEN LOCKS OUT OR EXCESSIVE
ON/OFFCYCLE
Under this condition, the burner will start the purge cycle again,
then pilot ignition and main flame cycle. If main flame cannot be
sustained:
1. Make sure main manual gas valve (right after the Robertshaw
gas valve) is fully open;
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Model GPG/GPV Limited Warranty
State Industries, Inc., the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.
1. THE TANK
If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to the natural corrosion from potable
water therein, during the first THREE years after installation, the warrantor will supply a complete new State water heater of equivalent size and
current model. Some government agencies are requiring energy efficient standards for water heaters. In the event regulations prohibit sale of
a model of equivalent size and construction, State will provide a model which complies with the regulations of your area, in which case the
consumer will be charged the difference in price between the like replacement and the energy efficient model required. The warranty on the
replacement water heater will be limited to the unexpired term of the original warranty.
2. ALL OTHER PARTS
If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective
in material or workmanship, the warrantor will repair or replace such part or portion at its option.
3. CONDITIONS AND EXCEPTIONS
This warranty shall supply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and
regulations, the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by
A.G.A and approved by the American Society of Mechanical Engineers, must have been installed.
a) This warranty shall apply only when the heater is used:
(1) used at temperatures not exceeding the maximum calibrated setting of its thermostat;
(2) used at water pressure not exceeding the working pressure shown on the heater;
(3) filled with potable water, free to circulate at all times and with the tank free of damaging water sediment or scale deposits;
(4) used in a non-corrosive and non-contaminated atmosphere;
(5) used with factory approved anode(s) installed;
(6) in its original installation location;
(7) in the United States, its territories or possessions, and Canada;
(8) sized in accordance with proper sizing techniques for commercial and/or residential water heaters;
(9) bearing a rating plate which has not been altered, defaced or removed, except as required by the warrantor;
(10) operated with properly installed dirt leg;
(11) fired with the fuel for which it was factory built;
(12) fired at the factory rated input;
b) Any accident to the water heater, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, or any
attempt to repair tank leaks will void this warranty.
c) This warranty is voided if a device as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is
connected to unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The
relief valve installed on the heater is not an acceptable method.
4. SERVICEAND REPAIR EXPENSES
Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other
costs. Such costs may include bat are not limited to:
a) Labor charges for services removal, repair or reinstallation of the water heater or any component part;
b) Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and
returning the claimed defective heater or part to such distributor.
c) All cost necessary or incidental for material and /or permits required for installation of the replaced heater or part.
5. LIMITATIONS ON IMPLIED WARRANTIES
Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state law are limited to one (1) year duration
for the heater or any of its parts. Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply
to you.
6. CLAIM PROCEDURE
Any claim under the warranty should be initiated with the dealer who sold the heater, or with any other dealer handling the warrantor’s products.
If this is not practicable, the owner should contact:
State Water Heaters
500 Lindahl Parkway
Ashland City, TN 37015
Telephone 1-800-323-2636
a) The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by
the warrantor.
b) Dealer replacements are made subject to in-warranty validation by warrantor.
7. DISCLAIMERS
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILLBE MADE IN BEHALF OF THE WARRANTOR WITH RESPECTTOTHE MERCHANTABILITY
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE HEATER. THE WARRANTOR SHALL NOT BE
RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OFTHE UNIT, INCONVENIENCE, LOSS OR DAMAGETO PERSONALPROPERTYOR OTHER
CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT A LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY
PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT,AND WHETHERARISING IN CONTRACTOR INTORT.
Fill in the warranty for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the
heater’s rating plate.
Model No.____________________________________ Serial No. ________________________________Date Installed_____________________
Dealer’s Name ________________________________________________________________________________________________________
Dealer’s Address ______________________________________________________________________Phone No._______________________
City and State_________________________________________________________________________Zip _____________________________
KEEPTHIS WARRANTY POSTEDADJACENT TO THE HEATER FOR FUTURE REFERENCE.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMERCIAL TANK TYPE WATER HEATER
REPLACEMENT PARTS LIST
MODELS GPG/GPV-540A THRU 740A
3
SERIES 104
5
9
9A
4
9B
GPV VENT KIT
11
11A
11C
11B
CLEANOUTASSEMBLY
6
4
12
7
10
RELIEF
VALVE
BAROMETRIC
DRAFTCONTROL
8
(Part numbers are listed on page 35)
STATE WATER HEATERS
500 Lindahl Parkway, Ashland City, TN 37015
Phone: 1-800-821-2017 • Fax: 1-800-6449306
34
Download from Www.Somanuals.com. All Manuals Search And Download.
PART LIST FOR PAGE 34
Item
Description
GPG-540A
GPG-650A
GPG-740A
1 ........Anode, Plug ........................................................................ 183523-48(4) ............... 183523-48(4) ................ 83523-48(4)
2 ........Baffle, Flue ........................................................................... 194974(16) ................. 194974(16) ................... 194974(16)
3 ........Cover, Jacket ........................................................................... 195046 ........................195046 ......................... 195046
4 ........Valve, Relief ............................................................................99465-3 ....................... 99465-3 ....................... 99465-3
5 ........Thermostat W.E.C.O. ................................................................ 192828 ........................192828 ......................... 192828
6 ........Cover, Front ............................................................................. 181260 ........................181260 ......................... 181260
7 ........Valve, Drain .............................................................................26273-6 ....................... 26273-6 ....................... 26273-6
8 ........Jacket Base ............................................................................. 195045 ........................195045 ......................... 195045
10 ......Burner Assembly ....................................................................195036-2 ..................... 195036-1 ....................... 195036
11.......Cleanout Assembly
..........(includes the following items)
..........11A.... Cleanout Cover............................................................. 99037 ..........................99037 ........................... 99037
..........11B .... Gasket .......................................................................... 99038 ..........................99038 ........................... 99038
GPG
..........11C .... Screw - Thread Rolling .................................................69852-1 ....................... 69852-1 ....................... 69852-1
12 ......Barometric Draft Control ..........................................................170777-5 ..................... 170777-5 ..................... 170777-5
Item
Description
GPV-540A
GPV-650A
GPV-740A
1 ........Anode, Plug ........................................................................ 183523-48(4) ............ 183523-48(4) ................... 83523-48(4)
2 ........Baffle, Flue ........................................................................... 194974(16) ...............194974(16) ...................... 194974(16)
3 ........Cover, Jacket ........................................................................... 195046 ..................... 195046 ............................ 195046
4 ........Valve, Relief ............................................................................99465-3 .................... 99465-3 .......................... 99465-3
5 ........Thermostat W.E.C.O. ................................................................ 192828 ..................... 192828 ............................ 192828
6 ........Cover, Front ............................................................................. 181260 ..................... 181260 ............................ 181260
7 ........Valve, Drain .............................................................................26273-6 .................... 26273-6 .......................... 26273-6
8 ........Jacket Base ............................................................................. 195045 ..................... 195045 ............................ 195045
9 ........GPVVent Kit ........................................................................... 192049-1 .................... 192049 ............................ 192049
GPV
..........(includes the following items, 2 pieces of hood required for direct vent)
..........9A ..... Hood, Vent - Side Wall .................................................. 191235 ..................... 191235 ............................ 191235
..........9B ..... Reducer - Flue ............................................................. 191981 ..................... 191981 ............................ 191981
10 ......Burner Assembly .................................................................... 196795-2 .................. 196795-1 .......................... 196795
11.......Cleanout Assembly
..........(includes the following items)
..........11A.... Cleanout Cover............................................................. 99037 ....................... 99037 .............................. 99037
..........11B .... Gasket .......................................................................... 99038 ....................... 99038 .............................. 99038
..........11C .... Screw - Thread Rolling.................................................69852-1 .................... 69852-1 .......................... 69852-1
*Items not illustrated.
# Quantities, if more than one, shown in parenthesis next to part number.
Part numbers underlined are recommended stock items for emergency replacement.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
GPG BURNER ASSEMBLY
(Part numbers are listed on page 37)
36
Download from Www.Somanuals.com. All Manuals Search And Download.
PART LIST FOR BURNER (see drawing on page 36)
Item
Description
GPG-540A
GPG-650A
GPG-740A
1 ....... Ignition Control .................................................................................. 6207 ............................. 6207 ............................ 6207
2 ....... Motor - 1/4 HP 3450 RPM ................................................................ 6207-1 ..........................6207-1 .......................... 6207-1
3 ....... Valve 24/60 .................................................................................... 6207-2 ..........................6207-2 .......................... 6207-2
4 ....... Gas Valve ...................................................................................... 6207-4 ..........................6207-4 .......................... 6207-4
5 ....... Air Switch ...................................................................................... 6207-5 ..........................6207-5 .......................... 6207-5
6 ....... Transformer 120/24 ....................................................................... 6207-6 ..........................6207-6 .......................... 6207-6
7 ....... Low Gas Pressure Switch ............................................................. 6207-8 ..........................6207-8 .......................... 6207-8
8 ....... FlameRod ...................................................................................... 6207-9 ..........................6207-9 .......................... 6207-9
GPG
9 ....... Igniter ............................................................................................ 6207-10 ....................... 6207-10 ........................ 6207-10
10 ....... Thermostat .................................................................................... 6207-11 ........................6207-11 ........................ 6207-11
11........ Regulator 3/8" ............................................................................... 6207-12 ....................... 6207-12 ........................ 6207-12
12 ....... Grounding Lug .............................................................................. 6207-13 ....................... 6207-13 ........................ 6207-13
13 ....... Std Hardware - Purchase Locally .................................................. - - - - - ..........................- - - - - .......................... - - - - -
14 ....... Tubing - 3/8 X 1/4 .......................................................................... 6207-14 ....................... 6207-14 ........................ 6207-14
15 ....... Brass Reducer 3/8 X 1/4 ............................................................... 6207-15 ....................... 6207-15 ........................ 6207-15
16 ....... Brass Tee - 1/4” ............................................................................ 6207-47 ....................... 6207-47 ........................ 6207-47
17 ....... Brass Tube 1/4 X 1/8 .................................................................... 6207-17 ....................... 6207-17 ........................ 6207-17
18 ....... Std Hardware - Purchase Locally (2)............................................. - - - - - ..........................- - - - - .......................... - - - - -
19 ....... Std Hardware - Purchase Locally .................................................. - - - - - ..........................- - - - - .......................... - - - - -
20 ....... Std Hardware - Purchase Locally .................................................. - - - - - ..........................- - - - - .......................... - - - - -
21 ....... Pipe Plug 1 1/4" Drilled & Tapped ................................................... 6207-18 ....................... 6207-18 ........................ 6207-18
22 ....... Orifice Spring ................................................................................ 6207-19 ....................... 6207-19 ........................ 6207-19
23 ....... Junction Box ................................................................................. 6207-20 ....................... 6207-20 ........................ 6207-20
GPG
24 ....... Junction Box Cover ....................................................................... 6207-21 ....................... 6207-21 ........................ 6207-21
25 ....... Ball Valve - 1" ................................................................................ 6207-22 ....................... 6207-22 ........................ 6207-22
26 ....... Pilot Ass’y (Includes Items 8, 9 & 10) ............................................ 6207-23 ....................... 6207-23 ........................ 6207-23
27 ....... Air Staging Band ........................................................................... 6207-24 ....................... 6207-24 ........................ 6207-24
28 ....... Frame Motor Plate ......................................................................... 6207-25 ....................... 6207-25 ........................ 6207-25
29 ....... Damper Stop ................................................................................. 6207-26 ....................... 6207-26 ........................ 6207-26
30 ....... 90 Degree Adapter Ass’y ............................................................. 6207-27 ....................... 6207-27 ........................ 6207-27
31 ....... Housing Ass’y ............................................................................... 6207-28 ....................... 6207-28 ........................ 6207-28
32 ....... Back Mount Panel Ass’y ................................................................ 6207-29 ....................... 6207-29 ........................ 6207-29
33 ....... Premix Air Housing Wheel ............................................................. 6207-30 ....................... 6207-30 ........................ 6207-30
34 ....... Panel Box Door ............................................................................. 6207-31 ....................... 6207-31 ........................ 6207-31
35 ....... Pie Damper Inner Plate ................................................................... 6207-32 ....................... 6207-32 ........................ 6207-32
36 ....... Pie Damper Middle Plate ................................................................. 6207-33 ....................... 6207-33 ........................ 6207-33
37 ....... Outer Pie Damper .......................................................................... 6207-34 ....................... 6207-34 ........................ 6207-34
GPG
38 ....... Wheel ............................................................................................ 6207-36 ....................... 6207-36 ........................ 6207-36
39 ....... Amber Light................................................................................... 6207-37 ....................... 6207-37 ........................ 6207-37
40 ....... Std Hardware - Purchase Locally .................................................. - - - - - ..........................- - - - - .......................... - - - - -
41 ....... Flat Washers, 3/8” ........................................................................ 6207-49 ....................... 6207-49 ........................ 6207-49
42 ....... Tubing to FP 90° 70-42, 1/4” X 1/8” ............................................... 6207-50 ....................... 6207-50 ........................ 6207-50
43 ....... El Fitting 1/4 X 1/8 .......................................................................... 6207-40 ....................... 6207-40 ........................ 6207-40
44 ....... Hex Nipple, 1/4” ............................................................................. 6207-51 ....................... 6207-51 ........................ 6207-51
45 ....... Ball Valve, Model 740, 1/4” ............................................................ 6207-52 ....................... 6207-52 ........................ 6207-52
46 ....... Std Hardware - Purchase Locally .................................................. - - - - - ..........................- - - - - .......................... - - - - -
47 ....... Orifice - Aluminum 1 1/4" ............................................................... 6207-42 ....................... 6207-42 ........................ 6207-42
48 ....... Std Hardware - Purchase Locally .................................................. - - - - - ..........................- - - - - .......................... - - - - -
49 ....... Conduit Clamp ............................................................................... 6207-43 ....................... 6207-43 ........................ 6207-43
50 ....... Premix Diffuser Ass’y ................................................................... 6207-53 ....................... 6207-53 ........................ 6207-53
51 ....... Pilot Tubing (3) .............................................................................. 6207-54 ....................... 6207-54 ........................ 6207-54
52 ....... Rocker Switch .............................................................................. 6207-46 ....................... 6207-46 ........................ 6207-46
GPG
53 ....... ORing Seal ................................................................................... 6207-55 ....................... 6207-55 ........................ 6207-55
54 ....... Plastic Cap, SC-1 1” Pipe ............................................................... 6207-56 ....................... 6207-56 ........................ 6207-56
37
Download from Www.Somanuals.com. All Manuals Search And Download.
GPV BURNER ASSEMBLY
(Part numbers are listed on page 39)
38
Download from Www.Somanuals.com. All Manuals Search And Download.
PART LIST FOR BURNER (see drawing on page 38)
Item
Description
GPV-540A
GPV-650A
GPV-740A
1 ....... Ignition Control .................................................................................. 6207 ............................. 6207 ............................ 6207
2 ....... Motor - 1/4 HP 3450 RPM ................................................................ 6207-1 ..........................6207-1 .......................... 6207-1
3 ....... Valve 24/60 .................................................................................... 6207-2 ..........................6207-2 .......................... 6207-2
4 ....... Gas Valve ...................................................................................... 6207-4 ..........................6207-4 .......................... 6207-4
5 ....... Thermodisk Relay ............................................................................ 12S10 ........................... 12S10 .......................... 12S10
6 ....... Transformer 120/24 ....................................................................... 6207-6 ..........................6207-6 .......................... 6207-6
7 ....... Low Gas Pressure Switch............................................................. 6207-8 ..........................6207-8 .......................... 6207-8
8 ....... FlameRod ...................................................................................... 6207-9 ..........................6207-9 .......................... 6207-9
9 ....... Igniter ............................................................................................ 6207-10 ....................... 6207-10 ........................ 6207-10
10 ....... Thermostat .................................................................................... 6207-11 ........................6207-11 ........................ 6207-11
GPV
11........ Regulator 3/8" ............................................................................... 6207-12 ....................... 6207-12 ........................ 6207-12
12 ....... Grounding Lug .............................................................................. 6207-13 ....................... 6207-13 ........................ 6207-13
13 ....... Std Hardware - Purchase Locally .................................................. - - - - - .......................... - - - - - .......................... - - - - -
14 ....... Tubing - 3/8 X 1/4.......................................................................... 6207-14 ....................... 6207-14 ........................ 6207-14
15 ....... Brass Reducer 3/8 X 1/4 ............................................................... 6207-15 ....................... 6207-15 ........................ 6207-15
16 ....... Brass Tee - 1/4” ............................................................................ 6207-47 ....................... 6207-47 ........................ 6207-47
17 ....... Brass Tube 1/4 X 1/8 .................................................................... 6207-17 ....................... 6207-17 ........................ 6207-17
18 ....... Std Hardware - Purchase Locally (2)............................................. - - - - - .......................... - - - - - .......................... - - - - -
19 ....... Std Hardware - Purchase Locally .................................................. - - - - - .......................... - - - - - .......................... - - - - -
20 ....... Std Hardware - Purchase Locally .................................................. - - - - - .......................... - - - - - .......................... - - - - -
21 ....... Pipe Plug 1 1/4" Drilled &Tapped ................................................... 6207-18 ....................... 6207-18 ........................ 6207-18
22 ....... Orifice Spring ................................................................................ 6207-19 ....................... 6207-19 ........................ 6207-19
23 ....... Junction Box ................................................................................. 6207-20 ....................... 6207-20 ........................ 6207-20
24 ....... Junction Box Cover ....................................................................... 6207-21 ....................... 6207-21 ........................ 6207-21
25 ....... Ball Valve - 1" ................................................................................ 6207-22 ....................... 6207-22 ........................ 6207-22
GPV
26 ....... Pilot Ass’y (Includes Items 8, 9 & 10) ............................................ 6207-23 ....................... 6207-23 ........................ 6207-23
27 ....... Air Staging Band ........................................................................... 6207-24 ....................... 6207-24 ........................ 6207-24
28 ....... Frame Motor Plate ......................................................................... 6207-25 ....................... 6207-25 ........................ 6207-25
29 ....... Damper Stop ................................................................................. 6207-26 ....................... 6207-26 ........................ 6207-26
30 ....... 90 Degree Adapter Ass’y ............................................................. 6207-27 ....................... 6207-27 ........................ 6207-27
31 ....... Housing Ass’y ............................................................................... 6207-28 ....................... 6207-28 ........................ 6207-28
32 ....... Back Mount Panel Ass’y ................................................................ 6207-29 ....................... 6207-29 ........................ 6207-29
33 ....... Premix Air Housing Wheel ............................................................. 6207-30 ....................... 6207-30 ........................ 6207-30
34 ....... Panel Box Door ............................................................................. 6207-31 ....................... 6207-31 ........................ 6207-31
35 ....... Pie Damper Inner Plate................................................................... 6207-32 ....................... 6207-32 ........................ 6207-32
36 ....... Pie Damper Middle Plate ................................................................. 6207-33 ....................... 6207-33 ........................ 6207-33
37 ....... Outer Pie Damper .......................................................................... 6207-34 ....................... 6207-34 ........................ 6207-34
38 ....... Air Intake Kit .................................................................................. 6207-48 ....................... 6207-48 ........................ 6207-48
39 ....... Wheel ............................................................................................ 6207-36 ....................... 6207-36 ........................ 6207-36
40 ....... Amber Light............................
G
.................................
P
...................... 6207-37 ....................... 6207-37 ........................ 6207-37
V
41 ....... Std Hardware - Purchase Locally .................................................. - - - - - .......................... - - - - - .......................... - - - - -
42 ....... Flat Washers, 3/8” ........................................................................ 6207-49 ....................... 6207-49 ........................ 6207-49
43 ....... Tubing to FP 90° 70-42, 1/4” X 1/8” ............................................... 6207-50 ....................... 6207-50 ........................ 6207-50
44 ....... El Fitting 1/4 X 1/8.......................................................................... 6207-40 ....................... 6207-40 ........................ 6207-40
45 ....... Hex Nipple, 1/4” ............................................................................. 6207-51 ....................... 6207-51 ........................ 6207-51
46 ....... Ball Valve, Model 740, 1/4” ............................................................ 6207-52 ....................... 6207-52 ........................ 6207-52
47 ....... Std Hardware - Purchase Locally .................................................. - - - - - .......................... - - - - - .......................... - - - - -
48 ....... Orifice - Aluminum 1 1/4" ............................................................... 6207-42 ....................... 6207-42 ........................ 6207-42
49 ....... Std Hardware - Purchase Locally .................................................. - - - - - .......................... - - - - - .......................... - - - - -
50 ....... Conduit Clamp ............................................................................... 6207-43 ....................... 6207-43 ........................ 6207-43
51 ....... Premix Diffuser Ass’y ................................................................... 6207-53 ....................... 6207-53 ........................ 6207-53
52 ....... Pilot Tubing (3) .............................................................................. 6207-54 ....................... 6207-54 ........................ 6207-54
53 ....... Rocker Switch .............................................................................. 6207-46 ....................... 6207-46 ........................ 6207-46
54 ....... ORing Seal ................................................................................... 6207-55 ....................... 6207-55 ........................ 6207-55
GPV
55 ....... Plastic Cap, SC-1 1” Pipe ............................................................... 6207-56 ....................... 6207-56 ........................ 6207-56
56 ....... IS2 Air Switch, +0.3” (Blocked Flue)............................................... 171040 ......................... 171040 ........................ 171040
57 ....... IS2 Air Switch, +0.9” (Blower Proof).............................................. 171080 ......................... 171080 ........................ 171080
58 ....... IS2 Air Switch, -0.3” (Air Intake) .................................................... 171070 ......................... 171070 ........................ 171070
59 ....... NPM Panel Bracket ......................................................................... K10304 ......................... K10304 ........................ K10304
STATE WATER HEATERS
500 Lindahl Parkway, Ashland City, TN 37015
Phone: 1-800-821-2017 • Fax: 1-800-6449306
39
Download from Www.Somanuals.com. All Manuals Search And Download.
500 Lindahl Parkway, Ashland City, TN 37015
Phone: 800-821-2017 Fax: 800-644-9306
Download from Www.Somanuals.com. All Manuals Search And Download.
|