Installation Instructions and Use & Care Guide
RESIDENTIAL GAS WATER HEATERS
HIGH EFFICIENCY ATMOSPHERIC VENT
GAS WATER HEATER
(FLAMMABLE VAPOR IGNITION RESISTANT)
FOR SPACE HEATING AND POTABLE WATER HEATING ONLY.
NOT FOR USE IN MOBILE HOMES.
This water heater complies with ANSI Z21.10.1-current
edition regarding the accidental or unintended ignition of
flammable vapors, such as those emitted by gasoline.
For Your Safety
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
WARNING: If the information in these
instructions is not followed exactly, a fire
or explosion may result causing property
damage, personal injury or death.
• Safety Instructions
• Installation
• Operation
• Care and Maintenance
• Troubleshooting
• Parts List
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
INSTALLER:
•
AFFIX THESE INSTRUCTIONS TO OR ADJACENT
TO THE WATER HEATER.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
OWNER:
•
RETAIN THESE INSTRUCTIONS AND WARRANTY
FOR FUTURE REFERENCE. RETAIN THE
ORIGINAL RECEIPT AS PROOF OF PURCHASE.
• Do not touch any electrical switch;
do not use any phone in your
building.
WARNING: Gas leaks can not always be detected by
smell.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
Gas suppliers recommend that you use a gas detector
approved by UL or CSA.
For more information, contact the your gas supplier.
• If you cannot reach your gas
supplier, call the fire department.
If a gas leak is detected, follow the “WHAT TO DO IF YOU
SMELL GAS” instructions.
— Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED.
IF YOU ARE UNSUCCESSFUL, CONTACT RESIDENTIAL TECHNICALASSISTANCE AT 1-800-365-0024 OR WWW.STATEWATERHEATERS.COM.
PRINTED IN THE U.S.A 0410
PART NO. 317998-002
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your water heater to warn you and
others of a potential hazard. Read and obey all safety messages and instructions throughout this manual. It is very important
that the meaning of each safety message is understood by you and others who install, use or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or injury.
DANGER
WARNING indicates a potentially hazardous situation which, if not avoided, could
result in death or injury.
WARNING
CAUTION indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, could result in property damage
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message
and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of
substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses
to warn of potential exposure to such substances.
WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects, or other
reproductive harm.
This appliance can cause low-level exposure to some of the substances included in the Act.
IMPORTANT DEFINITIONS
•
•
•
Qualified Technician: A qualified technician must have ability equivalent to a licensed tradesman in the fields of
plumbing, air supply, venting, and gas supply, including a thorough understanding of the requirements of the National
Fuel Gas Code as it relates to the installation of gas fired water heaters. The qualified technician must also be
familiar with the design features and use of flammable vapor ignition resistant water heaters, and have a thorough
understanding of this instruction manual.
Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fields of
plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the National
Fuel Gas Code as it relates to the installation of gas fired water heaters. The service agency must also have a
thorough understanding of this instruction manual, and be able to perform repairs strictly in accordance with the
service guidelines provided by the manufacturer.
Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of
gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also
offer service and inspection of appliances within the building.
SAFETY PRECAUTIONS
WARNING
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this
or any other appliance. Storage of or use of
gasoline or other flammable vapors or liquids in the
FLAMMABLES
Flammable Vapors
vicinity of this or any other appliance can result in
serious injury or death.
Read and follow water heater warnings and instructions.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell Natural or LP gas.
Do not expose water heater control to excessive gas
pressure.
Use only gas shown on rating plate.
Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended
period of non-use.
Read instruction manual before
installing, using or servicing
water heater.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL INSTALLATION
GET TO KNOW YOUR WATER HEATER - GAS MODELS
A
B
C
D
E
F
G
H
I
Vent Pipe
Draft hood
K
L
Outer door
Union
U
V
Main Burner
Flue
Anode (Not Shown)
Hot Water Outlet
Insulation
Gas Supply Piping
Manual Gas Shut-off Valve
Ground Joint Union
Drip Leg (Sediment Trap)
Inner Door
M
N
O
P
Q
R
S
T
Inlet Water Shut-off Valve
Cold Water Inlet
Inlet Dip Tube
Temperature & Pressure Relief Valve
Rating Plate
Flue Baffle
Gas Control Valve/Thermostat
Drain Valve
W Suitable Metal Drain Pan
X
Y
Control Display
Power Supply Transformer
(Shown detached from Heater)
YY Pressure Switch
(Shown detached from Heater)
Air Intake Chamber
Z
ZZ FV Sensor (Shown without Bracket)
J
*
*
INSTALL IN ACCORDANCE
WITH LOCAL CODES.
DRIP LEG AS REQUIRED
BY LOCAL CODES.
(S) GAS CONTROL VALVE/THERMOSTAT
*
ALL PIPING MATERIALS
TO BE SUPPLIED BY
CUSTOMERS.
TO VENT TERMINATION
ON ROOF
INSTALL THERMAL EXPANSION
TANK IF WATER HEATER IS
INSTALLED IN A CLOSED
WATER SYSTEM
A
IMPORTANT:
WHEN BRUSHING ON AN
APPROVED NONCORROSIVE
LEAK DETECTION SOLUTION,
DO NOT SPLASH SOLUTION
ONTO ELECTRICAL CON-
NECTIONS (SEE PAGE 27).
L
M
N
B
D
PRESSURE
SWITCH/FAN,
FV SENSOR
CONNECTOR
MANIFOLD TUBE
POWER SUPPLY
TRANSFORMER
CONNECTOR
IGNITER/
FLAME
SENSE
VACUUM RELIEF
O
VALVE
*INSTALL PER
LOCAL CODES
DISPLAY, ANODE
ROD CONNECTOR
CONNECTOR
P
E
R
(U) NATURAL GAS BURNER ASSEMBLY
X
MANIFOLD DOOR GASKET
MANIFOLD DOOR ASSEMBLY
MANIFOLD COMPONENT
BLOCK W/ RETAINER CLIP
Q
Z
BURNER
IGNITER / FLAME SENSE
CONNECTOR WIRE
FLAME SENSE
F
G
DISCHARGE PIPE
(DO NOT CAP OR PLUG.)
MANIFOLD
TUBE
S
H
HOT SURFACE
IGNITER
IGNITER / FLAME SENSE
CONNECTOR WIRE
V
T
U
MANIFOLD DOOR ASSEMBLY
I
6” MAXIMUM
AIR GAP
BURNER
MANIFOLD TUBE
FLOOR DRAIN
YY
W
J
ZZ
VIEW PORT
Y
K
IMPORTANT: DO NOT USE AN EXTENSION CORD TO CONNECT
THE WATER HEATER TO AN ELECTRICAL OUTLET.
FIGURE 1.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING YOUR GAS WATER HEATER
Unpacking the Water Heater
Important Information About This Water Heater
This gas water heater was manufactured to voluntary
safety standards to reduce the likelihood of a flammable
vapor ignition incident. New technology used in meeting
these standards makes this product more sensitive to
installation errors or improper installation environments.
Please review the Installation Checklist found at the end of
the installation instructions section and make any required
installation upgrades or changes.
WARNING
Excessive Weight Hazard
Use two or more people to move and install the water heater.
Failure to do so can result in injury (including back injury).
Consumer Information
IMPORTANT: Do not remove any permanent instructions,
labels, or the data label from either the outside of the
water heater or on the inside of water heater panels.
This water heater is design-certified by CSA International
as a Category I, non-direct vented water heater which
takes its combustion air either from the installation area or
from air ducted to the unit from the outside.
This water heater must be installed according to all local
and state codes or, in the absence of local and state
codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition. This is available from the following:
CSA America, Inc.
•
•
•
•
Remove exterior packaging and place installation com-
ponents aside.
Inspect all parts for damage prior to installation and
start-up.
Completely read all instructions before attempting to
assemble and install this product.
8501 East Pleasant Valley Road
Cleveland, OH 44131
National Fire Protection Agency
After installation, dispose of/recycle all packaging
materials.
1 Batterymarch Park
Quincy, MA 02269
Check your phone listings for the local authorities having
jurisdiction over your installation.
Consumer Responsibilities
This manual has been prepared to acquaint you with the
installation, operation, and maintenance of your gas water
heater and provide important safety information in these
areas.
Read all of the instructions thoroughly before attempting
the installation or operation of this water heater.
Do not discard this manual. You or future users of this
water heater will need it for future reference.
Service to the FVIR System should only be performed by a
qualified technician.
Examples of a qualified technician include: licensed
plumbers, authorized gas company personnel, and
authorized service personnel.
IMPORTANT: The manufacturer and seller of this water
heater will not be liable for any damages, injuries, or
deaths caused by failure to comply with the installation and
operating instructions outlined in this manual.
If you lack the necessary skills required to properly install
this water heater, or you have difficulty following the
instructions, you should not proceed but have a qualified
technician perform the installation of this water heater.
Massachusetts code requires this water heater to be
installed in accordance with Massachusetts Plumbing and
Fuel Gas Code 248 CMR Section 2.00 and 5.00.
A rating plate identifying your water heater can be found
on the front of your water heater. When referring to your
water heater, always have the information listed on the
rating plate readily available. Retain your original receipt
as proof of purchase.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
If flammable liquids or vapors have spilled or leaked in
the area of the water heater, leave the area immediately
and call the fire department from a neighbor’s home. Do
not attempt to clean the spill until all ignition sources have
been extinguished.
Location Requirements
WARNING
Carbon Monoxide Poisoning Hazard
Do not install in a mobile home.
WARNING
Doing so can result in carbon monoxide poisoning and death.
Fire or Explosion Hazard
• Read instruction manual before installing, using or
servicing water heater.
The FVIR System is designed to reduce the risk of
flammable vapor-related fires. Flammable liquids (such as
gasoline, solvents, propane, etc,) emit flammable vapors
which can be ignited by a gas water heater’s hot surface
igniter or main burner. The resulting flashback and fire can
cause death or serious burns to anyone in the area.
• Improper use may result in fire or explosion.
• Maintain required clearances to combustibles.
Keep combustibles such as boxes, magazines, clothes, etc. away
from the water heater area.
FIGURE 1A.
Site Location
FV Sensor
•
•
Select a location near the center of the water piping
system. The water heater must be installed indoors
and in a vertical position on a level surface. DO NOT
install in bathrooms, bedrooms, or any occupied room
normally kept closed.
This heater is equipped with a FV sensor for detecting the
presence of flammable vapors. When the sensor detects
those vapors, the unit will shut down and not operate.
Should this happen, please refer to the troubleshooting
guide on pages 31-32 (numbers 9,11,12). Even though this
water heater is a flammable vapors ignition resistant water
heater and is designed to reduce the chances of flamm-
able vapors being ignited, gasoline and other flammable
substances should never be stored or used in the same
vicinity or area containing a gas water heater or other open
flame or spark producing appliance.
Locate the water heater as close to the chimney or gas
vent as practical. Consider the vent system piping and
combustion air supply requirements when selecting the
water heater location. The venting system must be able
to run from the water heater to termination with minimal
length and elbows.
•
•
Locate the water heater near the existing gas piping.
If installing a new gas line, locate the water heater to
minimize the pipe length and elbows.
WARNING
The water heater should be located in an area not
subject to freezing temperatures. Water heaters
located in unconditioned spaces (i.e., attics,
basements, etc.) may require insulation of the water
piping and drain piping to protect against freezing.
The drain and controls must be easily accessible for
operation and service. Maintain proper clearances as
specified on the water heater.
FLAMMABLES
Flammable Vapors
•
•
Do not locate the water heater near an air-moving
device. The operation of air-moving devices such
as exhaust fans, ventilation systems, clothes dryers,
fireplaces, etc., can affect the proper operation of the
water heater. Special attention must be given to condi-
tions these devices may create. Flow reversal of flue
gases may cause an increase of carbon monoxide
inside of the dwelling (Figure 2).
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance. Storage of or use of gasoline or other
flammable vapors or liquids in the vicinity of this or
any other appliance can result in serious injury or
death.
The water heater is to be located as close as possible
to a 120VAC outlet. NOTE: all electrical wiring should
be in accordance to the NEC and all local/state
electrical codes (extension cord is not allowed).
Read and follow water heater warnings and
instructions
NOTE: This water heater must be installed according to all
local and state codes or, in the absence of local and state
codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition and the “National Electrical Code”, ANSI/
NFPS 70 current edition.
Do not use or store flammable products such as gasoline,
solvents, or adhesives in the same room or area near the
water heater. If such flammables must be used, all gas
burning appliances in the vicinity must be shut off and their
pilot lights extinguished. Open the doors and windows for
ventilation while flammable substances are in use.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
EXHAUST FAN
REVERSE FLOW
OF GASES
IMPORTANT: The water heater should be located in an area
where leakage of the tank or connections will not result in
damage to the area adjacent to the water heater or to lower
floors of the structure. Due to the normal corrosive action of
water, the tank will eventually leak after an extended period
of time. Also any external plumbing leak, including those
from improper installation, may cause early failure of the
tank due to corrosion if not repaired. If the homeowner is
uncomfortable with making the repair a qualified technician
should be contacted. A suitable metal drain pan should be
installed under the water heater as shown below, to help
protect the property from damage which may occur from
condensate formation or leaks in the piping connections
or tank. The pan must limit the water level to a maximum
depth of 1-3/4” and be two inches wider than the heater and
piped to an adequate drain. Locate the water heater near a
suitable indoor drain. Outside drains are subject to freezing
temperatures which can obstruct the drain line. The piping
should be at least 3/4” ID and pitched for proper drainage.
FIGURE 2.
Clearances and Accessibility
NOTE: Minimum clearances from combustible materials
are stated on the label on the front of the heater adjacent
to the gas control valve/thermostat of the water heater.
The water heater is certified for installation on a
combustible floor.
•
IMPORTANT: If installing over carpeting, the carpeting
must be protected by a metal or wood panel beneath
the water heater. The protective panel must extend
beyond the full width and depth of the water heater by
at least five inches (127mm) in any direction; or if in an
alcove or closet installation, the entire floor must be
covered by the panel.
Figure 2A may be used as a reference guide to locate
the specific clearance locations. A minimum of 5 inch-
es of front clearance should be provided for inspection
and service.
•
6” min. at
FIGURE 1B.
Pipe to an
adequate drain
Single Wall
Vent Pipe
12” min.
Top to
Ceiling
1-3/4”
max.
0” min.
Back
At least 2” greater
than the water heater.
0” min.
Sides
Water heater life depends upon water quality, water usage,
water temperature and the environment in which the
water heater is installed. Water heaters are sometimes
installed in locations where leakage may result in property
damage, even with the use of a metal drain pan piped to a
drain. However, unanticipated damage can be reduced or
prevented by a leak detector or water shut-off device used
in conjunction with a piped metal drain pan. These devices
are available from some plumbing supply wholesalers and
retailers, and detect and react to leakage in various ways:
0” min.
Air Inlet
Chamber
5” min.
Front
Top View
•
•
•
•
Sensors mounted in the metal drain pan that trigger an
alarm or turn off the incoming water to the water heater
when water is detected.
Minimum Clearance Locations
FIGURE 2A.
Sensors mounted in the metal drain pan that turn off
the water supply to the entire home when water is
detected in the metal drain pan.
State of California
Water supply shut-off devices that activate based on
the water pressure differential between the cold water
and hot water pipes connected to the water heater.
NOTE: The water heater must be braced, anchored, or
strapped to avoid moving during an earthquake. Contact
local utilities for code requirements in your area, visit http://
instructions.
Devices that will turn off the gas supply to a gas water
heater while at the same time shutting off its water
supply.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
GAS SUPPLY
WARNING
Manual Gas
Shut-Off Valve
Ground Joint Union
Install a readily acces-
sible manual shut-off
valve in the gas supply
line as recommended
by the local utility.
Discharge Pipe
(Do Not plug or cap)
Explosion Hazard
Use a new CSA approved gas supply line.
Install a shut-off valve.
Check with local utility
for minimum height.
•
•
•
3” Minimum
Drip Leg
6” Max. Air Gap
Suitable Drain
Do not connect a natural gas water heater to an L.P. gas
supply.
FIGURE 3.
•
•
Do not connect an L.P. gas water heater to a natural gas
supply.
Gas Pressure
Failure to follow these instructions can result in death,
explosion, or carbon monoxide poisoning.
WARNING
Gas Requirements
IMPORTANT: Read the rating plate to be sure the water
heater is made for the type of gas you will be using in
your home. This information will be found on the rating
plate located near the gas control valve/thermostat. If the
information does not agree with the type of gas available,
do not install or light. Call your dealer.
Explosion Hazard
•
•
Gas leaks can not always be detected by smell.
NOTE: An odorant is added by the gas supplier to the gas
used by this water heater. This odorant may fade over an
extended period of time. Do not depend upon this odorant
as an indication of leaking gas.
Gas suppliers recommend that you use a gas
detector approved by UL or CSA.
•
•
For more information, contact your gas supplier.
If a gas leak is detected, follow the “What to do if you
smell gas” instructions on the cover of this manual.
Gas Piping
The gas piping must be installed according to all local and
state codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current
edition.
Tables 1 and 2 on the following page provide a sizing
reference for commonly used gas pipe materials. Consult
the “National Fuel Gas Code” for the recommended gas
pipe size of other materials.
IMPORTANT: The gas supply pressure must not exceed the
maximum supply pressure as stated on the water heater’s rating
plate. The minimum supply pressure is for the purpose of input
adjustment.
Gas Pressure Testing
NOTE: Use pipe joint compound or teflon tape marked
as being resistant to the action of petroleum gases (See
Figure 3.)
1. Install a readily accessible manual shut-off valve in the
gas supply line as recommended by the local utility.
Know the location of this valve and how to turn off the
gas to this unit.
2. Install a drip leg (if not already incorporated as part of
the water heater) as shown. The drip leg must be no
less than three inches long for the accumulation of dirt,
foreign material, and water droplets.
3. Install a ground joint union between the gas control
valve/thermostat and the manual shut-off valve. This
is to allow easy removal of the gas control valve/
thermostat.
IMPORTANT: This water heater and its gas connection must
be leak tested before placing the appliance in operation.
•
If the code requires the gas lines to be tested at a
pressure exceeding 14” W.C., the water heater and its
manual shut-off valve must be disconnected from the gas
supply piping system and the line capped.
•
If the gas lines are to be tested at a pressure less than
14” W.C., the water heater must be isolated from the gas
supply piping system by closing its manual shut-off valve.
NOTE: Air may be present in the gas lines and could prevent
the burner from lighting on initial start-up. The gas lines should
be purged of air by a qualified technician after installation of
the gas piping system. While purging the gas piping system
of air, insure that the fuel is not spilled in the area of the
water heater installation, or any source of ignition (NOTE:
spilled fuel may trip the FV Sensor preventing heater from
starting). If the fuel is spilled while purging the piping
system of air follow the “WHAT TO DO IF YOU SMELL
GAS” instructions on the cover of this manual.
4. Turn the gas supply on and check for leaks. Test all
connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak.
Correct any leak found.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Pipe Capacity Table
WARNING
WARNING
Explosion Hazard
Use a new CSA approved gas supply line.
Install a shut-off valve.
Explosion Hazard
•
•
Gas leaks can not always be detected by smell.
•
•
•
Gas suppliers recommend that you use a gas
detector approved by UL or CSA.
Do not connect a natural gas water heater to an L.P. gas
supply.
•
•
For more information, contact your gas supplier.
If a gas leak is detected, follow the “What to do if you
smell gas” instructions on the cover of this manual.
•
•
Do not connect an L.P. gas water heater to a natural gas
supply.
Failure to follow these instructions can result in death,
explosion, or carbon monoxide poisoning.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
COMBUSTION AIR & VENTILATION
TABLE 3
Minimum
Square
Feet with
8’ Ceiling
WARNING
Typical Room
with 8’ Ceiling
BTUH Input
Carbon Monoxide Warning
Water heater must be vented to outdoors.
30,000
45,000
60,000
75,000
90,000
105,000
120,000
135,000
188
281
375
469
563
657
750
844
9 x 21
14 x 20
15 x 25
15 x 31
20 x 28
20 x 33
25 x 30
28 x 30
Vent must be installed by a qualified technician using
the installation instructions.
Examples of a qualified technican include: gas
technicians, authorized gas company personel, and
authorized service persons.
Failure to so do can result in death or carbon monoxide
poisoning.
IMPORTANT: Air for combustion and ventilation must not
come from a corrosive atmosphere. Any failure due to
corrosive elements in the atmosphere is excluded from
warranty coverage.
The following types of installation (not limited to the
following) will require outdoor air for combustion due to
chemical exposure and may reduce but not eliminate the
presence of corrosive chemicals in the air:
IMPORTANT:
•
The area must be open and be able to provide the
proper air requirements to the water heater. Areas that
are being used for storage or contain large objects
may not be suitable for water heater installation.
•
Water heaters installed in open spaces in buildings
with unusually tight construction may still require out-
door air to function properly. In this situation, outside
air openings should be sized the same as for a con-
fined space.
•
•
•
•
beauty shops
photo processing labs
buildings with indoor pools
water heaters installed in laundry, hobby, or craft
rooms
•
Modern home construction usually requires supplying
outside air into the water heater area.
•
water heaters installed near chemical storage areas
Combustion air must be free of acid-forming chemicals such
as sulfur, fluorine, and chlorine. These elements are found
in aerosol sprays, detergents, bleaches, cleaning solvents,
air fresheners, paint, and varnish removers, refrigerants,
and many other commercial and household products. When
burned, vapors from these products form highly corrosive acid
compounds. These products should not be stored or used
near the water heater or air inlet.
Combustion and ventilation air requirements are determined
by the location of the water heater. The water heater may
be located in either an open (unconfined) area or in a
confined area or small enclosure such as a closet or small
room. Confined spaces are areas with less than 50 cubic
feet for each 1,000 BTUH of the total input for all gas-using
appliances.
Confined Space
For the correct and proper operation of this water heater,
ample air must be supplied for the combustion, ventilation,
and dilution of flue gases. Small enclosures and confined
areas must have two permanent openings so that sufficient
fresh air can be drawn from outside of the enclosure. One
opening shall be within 12 inches of the top and one within
12 inches of the bottom of the enclosure as shown in
Figure 4.
The size of each opening (free area) is determined by the
total BTUH input of all gas utilization equipment (i.e., water
heaters, furnaces, clothes dryers, etc.) and the method by
which the air is provided. The BTUH input can be found
on the water heater rating plate. Additional air can be
provided by two methods:
Unconfined Space
A water heater in an unconfined space uses indoor air for
combustion and requires at least 50 cubic feet for each
1,000 BTUH of the total input for all gas appliances. The
table below shows a few examples of the minimum square
footage (area) required for various BTUH inputs.
1. All air from inside the building.
2. All air from outdoors.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Attic or crawl spaces cannot be closed and must be
properly ventilated to the outside.
12” Max.
Ductwork must be of the same cross-sectional area as
the free area of the opening to which they connect. The
minimum dimension of rectangular air ducts cannot be less
than three inches.
Permanent
openings to
the outside or
additional
rooms within
the building
The size of each of the two openings is determined by the
method in which the air is to be provided. Refer to Table
4 to calculate the minimum free area for each opening.
Figures 6, 7, 8A and 8B are typical examples of each
method.
Closet
or other
confined
space
12” Max.
Louvers and Grilles
In calculating free area for ventilation and combustion
air supply openings, consideration must be given to the
blocking effect of protection louvers, grilles, and screens.
These devices can reduce airflow, which in turn may
require larger openings to achieve the required minimum
free area. Screens must not be smaller than 1/4” mesh. If
the free area through a particular design of louver or grille
is known, it should be used in calculating the specified
free area of the opening. If the design and free area are
not known, it can be assumed that most wood louvers will
allow 20 - 25% of free area while metal louvers and grilles
will allow 60 - 75% of free area.
FIGURE 4.
All Air from Inside the Building
When additional air is to be provided to the confined area
from additional room(s) within the building, the total volume
of the room(s) must be of sufficient size to properly provide
the necessary amount of fresh air to the water heater
and other gas utilization equipment in the area. If you are
unsure that the structure meets this requirement, contact
your local gas utility company or other qualified agency for
a safety inspection.
Each of the two openings shall have a minimum free area
of 1 square inch per 1,000 BTUH of the total input rating of
all gas utilization equipment in the confined area, but not
less than 100 square inches (Figure 5).
Louvers and grilles must be locked open or interconnected
with the equipment so that they are opened automatically
during equipment operation.
Keep louvers and grilles clean and free of debris or other
obstructions.
TABLE 4
Minimum Free Area of Permanent Openings for
Ventilation and Combustion Air Supply - All Air from
Outdoors Only.
Confined
Space
Based on total BTUH input rating for all utilizing
equipment within the confined space.
Permanent
Openings
Minimum Free Area
Opening Source
*Direct to outdoors
Vertical Ducts
Per Opening (sq. in.) Reference Drawing
1 sq. in, per 4000 BTUH
1 sq. in, per 4000 BTUH
1 sq. in, per 2000 BTUH
1 sq. in, per 3000 BTUH
Figure 6
Figure 7
1 Square
inch/1000
BTUH
(min. 100
sq. in.)
Horizontal Ducts
Single Opening
Figure 8A
Figure 8B
Example: A water heater with an input rating of 50,000 BTUH using
horizontal ducts would require each opening to have a minimum free
area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.
FIGURE 5.
These openings connect directly with the outdoors through
a ventilated attic, a ventilated crawl space, or through an
outside wall.
*
All Air from Outdoors
Consult the local codes of your area for specific ventilation
and combustion air requirements.
Outdoor fresh air can be provided to a confined area either
directly or by the use of vertical and horizontal ducts. The
fresh air can be taken from the outdoors or from crawl or
attic spaces that freely communicate with the outdoors.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Alternative
Opening
Location
Gable Vent
to Outdoors
Install Above
Insulation
Confined
Space
1 sq. in. per
3000 BTUH
Confined
Space
Outlet Air
to the Attic
1 sq. in. per
4000 BTUH
Inlet Air
from the
Crawl Space
Alternative
Air Inlet
All Air From Outdoors - Using A Single Permanent Opening
FIGURE 8B.
Open
Foundation
Vent
1 sq. in. per
4000 BTUH
Vent Pipe System
All Air From Outdoors: Inlet Air From Ventilated
Crawl Space/Outlet Air To Ventilated Attic
This water heater uses a non-direct, single-pipe vent
system to remove exhaust gases created by the burning of
fossil fuels. Air for combustion is taken from the immediate
water heater location or is ducted in from the outside (see
“Combustion Air Supply and Ventilation”).
This water heater must be properly vented for the removal
of exhaust gases to the outside atmosphere. Correct
installation of the vent pipe system is mandatory for the
proper and efficient operation of this water heater and is
an important factor in the life of the unit.
The vent pipe must be installed according to all local and
state codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current
edition. The vent pipe installation must not be obstructed
so as to prevent the removal of exhaust gases to the
outside atmosphere.
FIGURE 6.
Gable Vent
to Outdoors
Install Above
Insulation
Outlet Air
Confined
Space
to the Attic
1 sq. in. per
4000 BTUH
Inlet Air Duct
1 sq. in. per
4000 BTUH
IMPORTANT: The use of vent dampers is not
recommended by the manufacturer of this water heater.
Although some vent dampers are certified by CSA
International, this certification applies to the vent damper
device only and does not mean they are certified for use
on this water heater.
12” Max.
All Air from Outdoors Through Ventilated Attic
FIGURE 7.
U.L. recognized fuel gas and carbon monoxide (CO)
detectors are recommended in all applications and should
be installed using the manufacturer’s instructions and local
codes, rules, or regulations.
1 sq. in. per
2000 BTUH
IMPORTANT: If you lack the necessary skills required
to properly install this venting system, you should not
proceed, but get help from a qualified technician.
Confined
Outlet
Space
Draft Hood Installation
Outdoor
Air Ducts
Sheet Metal Screws (Four Provided)
Draft Hood
Legs
Inlet
Legs
1 sq. in. per
2000 BTUH
Slot
Slot
Jacket Top
All Air From Outdoors Using Horizontal Ducts
Install The Draft Hood With The Four Screws Provided.
FIGURE 8A.
FIGURE 9
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Align the legs of the draft hood with the slots provided.
Insert the legs and secure the draft hood to the water
heater’s top with the four screws provided as shown in
Figure 9. Do not alter the draft hood in any way. If you are
replacing an existing water heater, be sure to use the draft
hood supplied with this water heater.
•
The connector must be installed above the extreme
bottom of the chimney to prevent potentially blocking
the flue gases.
The connector must be firmly attached and sealed to
prevent it from falling out.
To aid in removing the connector, a thimble or slip joint
may be used.
The connector must not extend beyond the inner edge
of the chimney as it may restrict the space between it
and the opposite wall of the chimney (Figure 10).
•
•
•
Vent Pipe Size
It is important that you follow the guidelines in these
instructions for sizing a vent pipe system. If a transition
to a larger vent size is required, the vent transition
connection must be made at the draft hood outlet.
2 FT. Minimum Above Any Object
3 FT.
Within 10 FT. Horizontally
Minimum
Vent Connectors
Support Strap
1. Type B, Double wall, U.L. Listed Vent Pipe.
2. Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance
from combustible materials when using type B double wall
vent pipe.
Vent connectors made of type B, double wall vent pipe
material may pass through walls or partitions constructed
of combustible material if the minimum listed clearance is
maintained.
Seal
Maintain
Clearance*
Do Not Extend
Vent Beyond Edge
Of Chimney
Vent
Connector
Slope Up
1/4 Inch
Per Foot
Minimum
Maintain a six inch minimum clearance from all
combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for
water heaters located in attics and may not pass through
attic spaces, crawl spaces or any confined or inaccessible
location. A single wall metal vent connector cannot pass
through any interior wall.
Chimney Termination Vent System
FIGURE 10.
Do not terminate the vent connector in a chimney that has
not been certified for this purpose. Some local codes may
prohibit the termination of vent connectors in a masonry
chimney.
When installing a vent connector, please note the following
(See Figures 10-12):
•
•
•
Install the vent connector avoiding unnecessary bends,
which create resistance to the flow of vent gases.
Install without dips or sags with an upward slope of at
least 1/4-inch per foot.
Joints must be fastened by sheet metal screws or other
approved means. It must be supported to maintain
clearances and prevent separation of joints and
damage.
Vertical Exhaust Gas Vent
Vertical exhaust gas vents must be installed with
U.L. listed type B vent pipe according to the vent
manufacturer’s instructions and the terms of its listing.
It must be connected to the water heater’s draft hood by a
listed vent connector or by directly originating at the draft
hood opening.
•
•
•
•
The length of the vent connector cannot exceed 75% of
the vertical vent height.
The vent connector must be accessible for cleaning,
inspection, and replacement.
Vent connectors cannot pass through any ceiling, floor,
firewall, or fire partition.
It is recommended (but not mandatory) that a minimum
12 inches of vertical vent pipe be installed on the draft
hood prior to any elbow in the vent system.
Vertical gas vents must terminate with a listed cap or
other roof assembly and be installed according to their
manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint
separation, and maintain clearances to combustible
materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a
vertical position to facilitate the removal of the burnt gases.
IMPORTANT: Existing vent systems must be inspected for
obstructions, corrosion, and proper installation.
An unused chimney flue or masonry enclosure may be used
as a passageway for the installation of a gas vent (Figure 12).
Common (combined) venting is allowable with vertical type
B vent systems and lined masonry chimneys as long as
proper draft for the water heater is established under all
conditions of operation. CAUTION: DO NOT common vent
this water heater with any power vented appliance.
Chimney Connection
IMPORTANT: Before connecting a vent to a chimney,
make sure the chimney passageway is clear and free of
obstructions. The chimney must be cleaned if previously
used for venting solid fuel appliances or fireplaces. Also
consult local and state codes for proper chimney sizing
and application or, in the absence of local and state
codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition.
Figures 10-12 are examples of vent pipe system
installations and may or may not be typical for your
specific application. Consult the “National Fuel Gas Code”,
NFPA 54, ANSI Z223.1-current edition and the guidelines
set forth by prevailing local codes.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
2 FT. Minimum Above
Any Object Within
10 FT. Horizontally
WATER SYSTEM PIPING
3 FT.
Piping Installation
Minimum
Piping, fittings, and valves should be installed according
to the installation drawing (Figure 13). If the indoor
installation area is subject to freezing temperatures, the
water piping must be protected by insulation.
Support Strap
Type B Double
Wall Vent Pipe
Maintain
Clearance*
The water supply pressure should not exceed 80 psi. If
this occurs, a pressure reducing valve with a bypass may
need to be installed in the cold water inlet line. This should
be placed on the supply to the entire house in order to
maintain equal hot and cold water pressures.
**Maintain
Specified
Clearance
Vent
Connector
Slope Up
1/4 Inch
Per Foot
Minimum
IMPORTANT: Heat cannot be applied to the water fittings
on the heater as they may contain nonmetallic parts. If
solder connections are used, solder the pipe to the adapter
before attaching the adapter to the hot and cold water
fittings.
Venting Gas Vent System With Type B Double Wall Vent Pipe.
FIGURE 11.
IMPORTANT: Always use a good grade of joint compound
and be certain that all fittings are drawn up tight.
1. Install the water piping and fittings as shown in Figure
13. Connect the cold water supply (3/4” NPT) to the
cold water inlet fitting. Connect the hot water piping
(3/4” NPT) to the hot water outlet fitting.
Listed Vent Cap
Maintain Manufacturer’s
Specified Minimum Clearance
IMPORTANT: Some models may contain energy saving
heat traps to prevent the circulation of hot water within the
pipes. Do not remove the inserts within the heat traps.
**Maintain
Specified
Clearance
Support Strap
Seal
Maintain
Clearance*
2. The installation of unions in both the hot and cold water
supply lines is recommended for ease of removing the
water heater for service or replacement.
Vent Connector
Vent
3. The manufacturer of this water heater recommends
installing a mixing valve or an anti-scald device in the
domestic hot water line as shown in Figure 14. These
valves reduce the point-of-use temperature of the
water by mixing cold and hot water and are readily
available for use.
Connector
Slope Up
1/4 Inch
Per Foot
Minimum
Unused Chimney
Flue Or Masonry
Enclosure
4. If installing the water heater in a closed water system,
install an expansion tank in the cold water line as
specified under Closed System/Thermal Expansion.
Venting Through Chimney With Type B Double Wall Vent Pipe.
5. Install a shut-off valve in the cold water inlet line. It
should be located close to the water heater and be
easily accessible. Know the location of this valve and
how to shut off the water to the heater.
FIGURE 12.
Maintain vent pipe clearance requirements to local, state
and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition.
*
6. A temperature and pressure relief valve must be
installed in the opening marked “Temperature and
Pressure (T & P) Relief Valve” on the water heater.
A discharge line must be added to the opening of
the T&P Relief Valve. Follow the instructions under
Temperature and Pressure Relief Valve.
** NFPA 211, Standard for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances states that these chimneys are
intended to be installed in accordance with the installation
instructions provided with each chimney support assembly.
Minimum air space clearance to combustible materials should be
maintained as marked on the chimney sections.
7. After piping has been properly connected to the water
heater, remove the aerator at the nearest hot water
faucet. Open the hot water faucet and allow the tank
to completely fill with water. To purge the lines of
any excess air, keep the hot water faucet open for
3 minutes after a constant flow of water is obtained.
Close the faucet and check all connections for leaks.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
In a closed system use a
thermal expansion tank
Closed System/Thermal Expansion
Cold Water
Inlet Valve
Pressure Reducing
Valve with Bypass
Hot Water
Outlet
Cold Water Supply
to Fixture
Main Water
Supply
Temperature and Pressure (T&P)
Relief Valve (Optional Top T&P
Relief Valve Not Shown)
Massachusetts:
Install a vacuum relief
in cold water line per
section 19 MGL 142
As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause
premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. The temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This condition is not covered
under the limited warranty.
Discharge line
(Do Not Cap or Plug)
1“ Min.
Drain line 3/4”
ID Min.
Metal Drain
Pan 1-3/4”
Depth Max.
6“ Min.
Drain
Typical water piping installation
FIGURE 13.
A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Contact a plumbing service agency or your retail
supplier regarding the installation of a thermal expansion tank.
Mixed Water
To Fixtures
Unmixed
Hot Water
Temperature and Pressure Relief Valve
Cold Water
Inlet
Explosion Hazard
Hot Water
Outlet
• Temperature-pressure relief
valve must comply with ANSI
Z21.22-CSA 4.4 and ASME
code.
• Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Mixing Valve
(Set To 1200 F)
• Can result in overheating
and excessive tank pressure.
Follow The Mixing Valve
Manufacturer’s Instructions
• Can cause serious injury or
death.
FIGURE 14.
Please note the following:
•
The system should be installed only with piping that is
suitable for potable (drinkable) water such as copper,
CPVC, or polybutylene. This water heater must not be
installed using iron piping or PVC water piping.
Temperature and
Pressure Relief Valve
(T&P)
•
•
Use only pumps, valves, or fittings that are compatible
with potable water.
Discharge line 3/4” Min.
Do not cap or plug.
It is recommend that only full flow ball or gate valves
are used in water piping installations. The use of valves
that may cause excessive restriction to water flow is not
recommended.
Metal Drain Pan
•
•
•
Use only 95/5 tin-antimony or other equivalent solder.
Any lead based solder must not be used.
6” Max.
Drain
Piping that has been treated with chromates, boiler seal,
or other chemicals must not be used.
FIGURE 15A.
Chemicals that may contaminate the potable water
supply must not be added to the piping system.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
For protection against excessive pressures and
pipe. Also ensure that the base of insulation is flush with
the water heater. Once seated, secure the insulation with
duct tape, electrical tape, or equivalent.
temperatures, a temperature and pressure relief valve must
be installed in the opening marked “T & P RELIEF VALVE”
(see Figure 15A). This valve must be design certified by
a nationally recognized testing laboratory that maintains
periodic inspection of the production of listed equipment or
materials as meeting the requirements for Relief Valves for
Hot Water Supply Systems, ANSI Z21.22. The function of
the temperature and pressure relief valve is to discharge
water in large quantities in the event of excessive
7. Repeat steps 5 through 6 for the hot water (outlet) pipe.
8. Add additional sections of pipe insulation as needed.
Manual Relief Lever
T&P Relief Valve
temperature or pressure developing in the water heater.
The valve’s relief pressure must not exceed the working
pressure of the water heater as stated on the rating plate.
IMPORTANT: Only a new temperature and pressure relief
valve should be used with your water heater. Do not use an
old or existing valve as it may be damaged or not adequate
for the working pressure of the new water heater. Do not
place any valve between the relief valve and the tank.
T&P Relief Valve
Drain Line
T&P Relief Valve Insulation
The Temperature & Pressure Relief Valve:
FIGURE 15B.
•
•
•
Must not be in contact with any electrical part.
Must be connected to an adequate discharge line.
Combination Space Heating/Potable
Water System
Must not be rated higher than the working pressure
shown on the rating plate of the water heater.
Some water heater models are equipped with inlet/outlet
connections for use with space heating applications. If this
water heater is to be used to supply both space heating
and domestic potable (drinking) water, the instructions
listed below must be followed.
The Discharge Line:
•
•
•
Must not be smaller than the pipe size of the relief
valve or have any reducing coupling installed in the
discharge line.
Must not be capped, blocked, plugged or contain any
valve between the relief valve and the end of the dis-
charge line.
•
•
•
Be sure to follow the manual(s) shipped with the air
handler system.
This water heater is not to be used as a replacement
for an existing boiler installation.
Must terminate a maximum of six inches above a floor
drain or external to the building. In cold climates, it is
recommended that the discharge pipe be terminated at
an adequate drain inside the building.
Do not use with piping that has been treated with
chromates, boiler seal or other chemicals and do not
add any chemicals to the water heater piping.
•
•
Must be capable of withstanding 250°F (121°C) without
distortion.
•
If the space heating system requires water
temperatures in excess of 120°F, a mixing valve
or an anti-scald device should be installed per its
manufacturer’s instructions in the domestic (potable)
hot water supply to limit the risk of scald injury.
Must be installed to allow complete drainage of both
the valve and discharge line.
T&P Relief Valve and Pipe Insulation
•
•
Pumps, valves, piping and fittings must be compatible
with potable water.
1. Locate the temperature and relief valve on the water
heater (also known as a T&P Relief Valve, Figure 15B).
2. Locate the slit running the length of the insulation.
A properly installed flow control valve is required to
prevent thermosiphoning. Thermosiphoning is the
result of a continuous flow of water through the air
handler circuit during the off cycle. Weeping (blow off)
of the temperature and pressure relief valve (T & P)
or higher than normal water temperatures are the first
signs of thermosiphoning.
3
Spread this slit open and slip it up under the T&P Relief
Valve. See Figure 15B. Apply gentle pressure to the
insulation to ensure it is fully seated on the T&P Relief
Valve. Once sealed secure the insulation with a section
of duct tape, electrical tape, or equivalent.
•
•
The domestic hot water line from the water heater
should be vertical past any mixing valve or supply line to
the air handler to remove air bubbles from the system.
Otherwise, these bubbles will be trapped in the air
handler heat exchanger coil, reducing the efficiency.
IMPORTANT: The insulation or tape must not block the
discharge opening or hinder access to the manual relief
lever. Ensure a discharge pipe is installed into the T&P
valve discharge opening per the instructions manual.
Do not connect the water heater to any system or
components previously used with non-potable water
heating appliances when used to supply potable water.
4. Locate the hot water (outlet) & cold water (inlet) pipes to
the water heater.
5. Locate the slit running the length of a section of pipe
insulation.
6. Spread the slit open and slip the insulation over the cold
water (inlet) pipe. Apply gentle pressure along the length
of the insulation to ensure it is fully seated around the
Some jurisdictions may require a backflow preventer in the
incoming cold water line. This may cause the temperature
and pressure relief valve on the water heater to
discharge or weep due to expansion of the heated water.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
A diaphragm-type expansion tank suitable for potable
water will normally eliminate this weeping condition.
Please read and follow the manufacturer’s instructions for
the installation of such tanks.
Electrical Connections
WARNING
Must Be Vertical To
Domestic
Hot Water
Out
Remove Air Bubbles
Expansion Tank
Cold Water Inlet
Electric Shock Hazard
Vacuum
Relief
Mixing
Valve
Disconnect power before
servicing.
Valve
Flow Control
Pump
Valve
Hot
Out
Water
Out
In
Replace all parts and panels
before operating.
Unions
Coil
To Air
Handler
Failure to do so can result in
death or electrical shock.
Air
Handler
Shut-Off
Valve
Before plugging in the water heater, always make sure:
•
•
•
The Voltage and frequency correspond to that specified
on the water heater.
MASSACHUSETTS CODE
DOES NOT ALLOW THIS
TYPE OF INSTALLATION.
The electrical outlet has the proper overload fuse or
breaker protection.
Typical Mixing Valve Installation Combination
Space Heating/Potable Water Heating System
Unit is to connect to a 120VAC electrical supply outlet
(extension cord is not allowed).
FIGURE 16
Also see Water System Piping for additional instructions on
the safe and correct installation and operation of this water
heater.
IMPORTANT: Do not use an extension cord to connect the
water heater to an electrical outlet.
•
•
The water heater and the outlet are properly grounded.
Installed in accordance with prevailing provisions of
local codes, or in the absence of such, National Electric
Code, ANSI/NFPS 70 current edition.
Solar Installation
If this water heater is used as a solar storage heater
or as a backup for the solar system, the water supply
temperatures to the water heater tank may be in excess of
120°F. A mixing valve or other temperature limiting valve
must be installed in the water supply line to limit the supply
temperature to 120°F.
Completely fill the tank with water and check all con-
nections for leaks. Open the nearest hot water faucet and
let it run for three (3) minutes to purge the water lines of
air and sediment and to ensure complete filling of the tank.
The Electrical power may then be turned on. Verify proper
operation after servicing.
NOTE: Solar water heating systems can often supply
water with temperatures exceeding 180°F and may result
in water heater malfunction.
Wiring Diagram
Gas Control
Air Intake
Valve / Thermostat
Chamber Fan
Anode
Rod
Pressure
Switch
Control Display
CAUTION:
DO NOT USE AN EXTENSION
CORD TO CONNECT THE
TRANSFORMER TO AN
ELECTRICAL OUTLET.
Igniter/Flame
Sense Connector
FV
Sensor
CAUTION:
Power Supply
Transformer
LABEL ALL WIRES PRIOR TO
DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT INFORMATION ABOUT THIS WATER HEATER
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor
ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation
errors. Please review the following checklist and make any required installation upgrades or changes.
Questions? Contact Residential Technical Assistance by referencing the phone number on the front of the Installation
Instructions and Use & Care Guide.
□ Ductwork is the same cross-sectional area as the
Installation Checklist
openings.
Water Heater Location
Vent Pipe System
Water heater location is important and can affect system
Check for proper drafting at the water heater draft hood.
performance. Please check the following:
Refer to the “Checking the Draft” section of this manual for
the test procedure. If the procedure shows insufficient draft
□ Installation area free of corrosive elements and
is present, please check the following.
flammable materials.
□ Draft hood properly installed.
□ Centrally located with the water piping system (For new
installations). Located as close to the gas piping, vent
pipe system and 120VAC outlet as possible.
□ Vent connectors securely fastened with screws and
supported properly to maintain six inch clearance.
□ Located indoors and in a vertical position. Protected
□ Vent connector made of approved material and sized
from freezing temperatures.
correctly.
□ Proper clearances from combustible surfaces
□ Vent pipe system installed according to all local and
state codes or, in the absence of local and state codes,
the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition.
maintained and not installed directly on a carpeted floor.
□ Provisions made to protect the area from water damage.
Metal drain pan installed and piped to an adequate
drain.
□ Flue baffle properly positioned in the flue tube.
□ Sufficient room to service the water heater. See
□ Check the vent system for restrictions/obstructions
and check the vent termination height. Refer to the
“Combustion Air and Ventilation” section of this water
heater manual for specific requirements.
Clearances and Accessibility section of this manual.
□ Water heater not located near an air moving device.
□ Is the installed environment dirty (excessive amounts
of lint, dirt, dust, etc.)? If so, the air intake chamber
louvers located on the side of the water heater
will need to be cleaned periodically. Refer to the
maintenance section of your water heater’s manual
for information on cleaning the “Air Intake Chamber
Louvers”.
□ Recheck for sufficient combustion air supply.
Water System Piping
□ Temperature and pressure relief valve properly installed
with a discharge line run to an open drain and protected
from freezing.
□ All piping properly installed and free of leaks.
□ Heater completely filled with water.
□ Closed system pressure build-up devices installed.
□ Mixing valve (when applicable) installed per
manufacturer’s instructions (See Water Temperature
Regulation section).
Combustion Air Supply and Ventilation
Check for sufficient combustion air supply. Insufficient air
for the combustion of gas will result in a inferior burner
flame “yellow-lazy”, thereby allowing smoking and carbon
formation (sooting) to build up in the combustion chamber.
Is the water heater installed in a closet or other small,
enclosed space? If so:
Gas Supply and Piping
□ Gas type is the same as that listed on the water heater
□ Are there openings for make-up air to enter and exit
rating plate.
the room/area?
□ Gas line equipped with shut-off valve, union, and drip
□ Are the openings of sufficient size? Remember, if
there are other gas-fired or air-consuming appliances
in the same room, you need more make-up air. Refer
to the Location Requirements section of this water
heater manual for specific requirements.
leg.
□ Use pipe joint compound or teflon tape marked as being
resistant to the action of petroleum gases.
□ Adequate pipe size and approved pipe material.
Fresh air not taken from areas that contain negative
pressure producing devices such as exhaust fans, dryers,
fireplaces, etc.
□ An approved noncorrosive leak detection solution used
to check all connections and fittings for possible gas
leaks. Correct any leak found.
□ Is there a furnace/air handler in the same room space
as the water heater? If so, has a return air duct system
been attached that exits the room? If so, check for
leaks on the air duct system. If no air duct system is
present, correct immediately by contacting a local
Heating, Ventilation, Air-Conditioning & Refrigeration
(HVAC-R) authorized service provider.
Electrical Supply
□ Water heater to be located as close as possible to a
120VAC outlet (extension cord is not allowed).
□ Electrical supply installed according to all local and
state codes or, in the absence of local and state codes,
the “National Electrical Code”, ANSI/NFPS 70 current
edition.
□ Fresh air supply free of corrosive elements and
flammable vapors.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING YOUR WATER HEATER
Operating Instructions
Read and understand these directions thoroughly before
attempting to operate the water heater. Make sure the view
port is not missing or damaged (See Figure 25). Make
sure the tank is completely filled with water before
operating the water heater. The gas control valve/
thermostat has a “On/Off Switch” and needs to be turned
on before water heater is operational. Check the label on
the front of heater near the gas control valve/thermostat for
the correct gas. Do not use this water heater with any gas
other than the one listed on the label. If you have any
questions or doubts, consult your gas supplier or gas utility
company.
WARNING
Explosion Hazard
Replace view port if glass is missing
or damaged.
Failure to do so can result in death,
explosion or fire.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury
or loss of life.
FLAMMABLE
BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES.
This appliance does not have a pilot. It is equipped with
an ignition device that will automatically light the
burner. Do not try to light the burner by hand.
BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch;
do not use any phone in your building.
A.
If you cannot reach your gas supplier, call the
fire department.
Use only your hand to push in the electronic display
buttons and gas control switch. Never use tools.
If the control buttons will not push in, don't try to
repair them, call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
C.
D.
B.
Do not use this appliance if any part has been
under water. Immediately contact a qualified
installer or service agency to replace a flooded
water heater. Do not attempt to repair the unit.
It must be replaced!
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
OPERATING INSTRUCTIONS
ON
OFF
ON/OFF
SWITCH
"GAS CONTROL"
"ELECTRONIC DISPLAY"
1.
STOP! Read the safety information
above on the label.
8. Set the ON/OFF switch on the gas control to the
"ON" postition.
2.
3.
Turn on all electrical power to the appliance.
Set the ON/OFF switch on the gas control to the
"ON" position.
Set the Electronic Display to the desired setting by first
9.
Set the Electronic Display to the lowest
4.
pressing the COOLER
and HOTTER
but-
setting by first pressing the COOLER
and
HOTTER
buttons together and holding for 1
tons together and holding for 1 second. Then press
second. Then press the COOLER
the lowest setting.
button to
the HOTTER
is reached.
button until the desired setting
5.
6.
Set the ON/OFF switch on the gas control to the
"OFF" position.
This appliance is equipped with a device
which automatically lights the burner.
DANGER: Hotter water increases the
risk scald injury. Consult the instruction
manual before changing temperature.
If the appliance will not operate, follow the instruc-
tions "TO TURN OFF GAS TO APPLIANCE" and
call your technician or gas supplier.
10.
DO NOT TRY TO LIGHT THE BURNER BY HAND.
Wait five (5) minutes to
If you then smell gas,
clear out any gas.
STOP! Follow "B" in
7.
WARNING: TURN OFF ALL
the safety information above on this label. If you
don't smell gas, go to the next step.
ELECTRIC POWER BEFORE SERVICING.
TO TURN OFF GAS TO APPLIANCE
Set the Electronic Display to the lowest setting by first
1.
2. Set the ON/OFF switch on the gas control to the
"OFF" postition.
pressing the COOLER
tons together and holding for 1 second. Then press
the COOLER button to the lowest setting.
and HOTTER
but-
3.
Turn off all electrical power to the appliance if
service is to be performed.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Heater Operation
Checking the Draft
Figure 17 below shows the water heater’s sequence of
operation when a call for heat is initiated. The ignition
control module will attempt to light the burner three times.
If the ignition control does not detect ignition it will enter
lockout mode, indicated by display flashing status code
WARNING
Burn Hazard
(see status code 3 page 30 and/or status code 9 page 31).
Do not touch vent.
Doing so can result in burns.
Sequence of Operation
After successfully lighting the water heater, allow the unit to
operate for 15 minutes and check the draft hood relief
opening for proper draft (Figure 18). Make sure all other
appliances in the area are operating and all doors are closed
when performing the draft test. Pass a match flame around
the relief opening of the draft hood. A steady flame drawn
into the opening indicates proper draft.
CALL FOR
HEAT INDICATED
BY FLASHING OF
DISPLAY SCREEN
STATUS CODES
FLAME SENSE ROD DETECTS
FLAME OF MAIN BURNER
CONTROL CHECKS TO ENSURE
PRESSURE SWITCH IS OPEN
WATER IN TANK IS HEATED BY
MAIN BURNER AND
DRAFT BLOWER IS ENERGIZED
TEMPERATURE REACHES
THERMOSTAT SETTING
CONTROL CHECKS TO ENSURE
PRESSURE SWITCH IS CLOSED,
INDICATING BLOWER OPERATING
AND THERE ARE NO VENTING
BLOCKAGES (INLET OR OUTLET)
MAIN VALVE DE-ENERGIZES
AND DRAFT BLOWER CONTINUES
FOR A POST PURGE TIME OF
APPROX. 30 SECONDS
MAIN VALVE DE-ENERGIZES
AND BLOWER CONTINUES FOR
A POST PURGE TIME
CONTROL ENERGIZES HOT
SURFACE IGNITER (HSI)
MAIN VALVE ENERGIZES ALLOW-
ING THE BURNER TO BE LIT BY
HSI, DRAFT BLOWER ENERGIZES
HEATER RETURNS TO
STANDBY MODE
DRAFT HOOD
FIGURE 17.
RELIEF
OPENING
MATCH
FIGURE 18.
If the flame flutters or is blown out, combustion products are
escaping from the relief opening. If this occurs, do not operate
the water heater until proper adjustments or repairs are made
to the vent pipe system and/or air supply requirements.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
heater. Mixing valves are available at plumbing supply or
hardware stores, see Figure 14. Follow manufacturer’s
instructions for installation of the valves. Before changing
the factory setting on the thermostat see Figures 20 and
21. Using the lowest hot water temperature that meets
your needs will also provide the most energy efficient
operation of the water heater.
Never allow small children to use a hot water tap, or
to draw their own bath water. Never leave a child or
handicapped person unattended in a bathtub or shower.
Burner Flames
Inspect the burner flames through the viewport and
compare them to the drawings in Figure 19. A properly
operating burner should produce a soft blue flame. Blue
tips with yellow inner cones are satisfactory. The tips
of the flame may have a slight yellow tint. The flame
should not be all yellow or have a sharp blue-orange
color. Contaminated air may cause an orange colored
flame. Contact a qualified technician if the flame is not
satisfactory.
NOTE: A water temperature range of 120°F-140°F
(49°C-60°C) is recommended by most dishwasher
manufacturers.
The thermostat of this water heater has been factory set
at its lowest position. It is adjustable and must be reset to
the desired temperature setting to reduce the risk of scald
injury. The electronic control display temperature should
be set at approximately 120°F (49°C) and this is the pre-
ferred starting point, see Figure 20. Some states have a
requirement for a lower setting. If you need hotter water,
follow directions for temperature adjustment, but beware of
the warnings in this section.
FIGURE 19.
Emergency Shut Down
Water
Temperature
°F
Time for 1st
Degree Burn
(Less Severe Burns)
Time for Permanent Burns
2nd & 3rd Degree
IMPORTANT: Should overheating occur or the gas supply
fails to shut off, turn off the heater’s manual gas control
valve and the electrical power. Call a qualified technician.
(Most Severe Burns)
110
116
116
122
131
140
149
154
(normal shower temp.)
(pain threshold)
35 minutes
Water Temperature Regulation
45 minutes
5 minutes
25 seconds
5 seconds
2 seconds
1 second
1 minute
Water temperature over 125°F (52°C)
can cause servere burns instantly
resulting in severe injury or death.
5 seconds
2 seconds
1 second
Children, the elderly, and the
physically or mentally disabled are at
highest risk for scald injury.
instantaneous
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)
Feel water before bathing or
showering.
FIGURE 20.
Pressing the “COOLER”
and pressing the “HOTTER”
temperature.
button decreases temperature
button increases the
Temperature limiting valves are
available.
To avoid any unintentional changes in water temperature
settings, the control has a tamper resistant feature
for changing the temperature setting. To change the
temperature setting follow these instructions:
Read instruction manual for safe
temperature setting.
Due to the nature of the typical gas water heater, the water
temperature in certain situations may vary up to 30°F (16.7
°C) higher or lower at the point of use such as, bathtubs,
showers, sink, etc.
HOTTER WATER CAN SCALD: Water heaters are
intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes
washing, dish washing, and other sanitizing needs can
scald and permanently injure you upon contact. Some
people are more likely to be permanently injured by hot
water than others. These include the elderly, children,
the infirm, or physically/mentally handicapped. If anyone
using hot water in your home fits into one of these groups
or if there is a local code or state law requiring a certain
temperature water at the hot water tap, then you must
take special precautions. In addition to using the lowest
possible temperature setting that satisfies your hot water
needs, a means such as a mixing valve, should be used
at the hot water taps used by these people or at the water
1. “Wake Up” the temperature indicators by holding down
both “COOLER” and “HOTTER” temperature adjust-
ment buttons at the same time for one second (See
Figure 21). The display will light up. The display will
only remain on for 30 seconds if no further buttons are
pressed. After 30 seconds the control will go back to
“Sleep” mode.
2. Release both of the temperature adjustment buttons.
A. To decrease the temperature press and release the
“COOLER” button until the desired setting is reached.
B. To increase the temperature press and release the
“HOTTER” button until the desired setting is reached.
NOTE: Should overheating occur or the gas supply fail
to shut off, turn off the manual gas control valve to the
appliance.
NOTE: During low demand periods when hot water is not
being used, a lower thermostat setting will reduce energy
22
Download from Www.Somanuals.com. All Manuals Search And Download.
losses and may satisfy your normal hot water needs. If hot
water use is expected to be more than normal, a higher
thermostat setting may be required to meet the increased
demand. When leaving your home for extended periods
(vacations, etc.) Set the electronic control display tem-
perature “COOLER” button to its lowest setting. This
will maintain the water at low temperatures with minimum
energy losses and prevent the tank from freezing during
cold weather.
Good venting is essential for a gas fired water heater
to operate properly as well as to carry away products of
combustion and water vapor.
Gas Control Valve/Thermostat Settings
It is always recommended that a suitable metal drain pan
be installed under the water heater to protect the area
from water damage resulting from normal condensation
production, a leaking tank or piping connections. Refer to
the “Location Requirements” section.
HOTTER
COOLER
Water Heater Sounds
During the normal operation of the water heater, sounds or
noises may be heard. These noises are common and may
result from the following:
1. Normal expansion and contraction of metal parts
during periods of heat-up and cool-down.
2. Condensation causes sizzling and popping within the
burner area and should be considered normal.
3. Sediment buildup in the tank bottom will create varying
amounts of noise and may cause premature tank
failure. Drain and flush the tank as directed under the
“Draining and Flushing” section.
Electronic Control Display
FIGURE 21.
Operational Conditions
Condensation
Whenever the water heater is filled with cold water, some
condensate will form while the burner is on. A water
heater may appear to be leaking when in fact the water is
condensation. This usually happens when:
a. A new water heater is filled with cold water for the first
time.
Smoke/Odor
The water heater may give off a small amount of smoke
and odor during the initial start-up of the unit. This is due
to the burning off of oil from metal parts of a new unit and
will disappear after a brief period of operation.
b. Burning gas produces water vapor in water heaters, par-
ticularly high efficiency models where flue temperatures
are lower.
c. Large amounts of hot water are used in a short time and
the refill water in the tank is very cold.
Safety Shut-off
This water heater is designed to automatically shut-off in
the event of the following:
Moisture from the products of combustion condense on the
cooler tank surfaces and form drops of water which may fall
onto the burner or other hot surfaces to produce a “sizzling”
or “frying” noise.
1. The burner flame is extinguished for any reason.
2. The water temperature exceeds 195°F (91°C).
3. Excessive build up of dust on the louvers of the air
intake chamber. See Maintenance of your Water
Heater Section.
This unit is also equipped with a flammable vapor sensor
(FV Sensor), designed to shut off the gas supply in the
event the water heater has been exposed to flammable
vapors (e.g., spilled gasoline).
Excessive condensation can cause burner flame problems
due to water running down the flue tube onto the main
burner.
Because of the suddenness and amount of water,
condensation water may be diagnosed as a “tank leak”.
After the water in the tank warms up (about 1-2 hours), the
condition should disappear.
Do not assume the water heater is leaking until there has
been enough time for the water in the tank to warm up.
A high temperature limit switch or ECO (Energy Cut Off) in
the tank is used to shut off the unit if the water temperature
exceeds 195°F (91°C). The ECO is a single-use switch,
which, if activated, requires complete replacement of the
entire gas control valve/thermostat. If the ECO should
activate, the water heater cannot be used until the gas
control valve/thermostat is replaced by a qualified technician.
Contact your local dealer for service information.
An undersized water heater will cause more condensation.
The water heater must be sized properly to meet the
family’s demands for hot water including dishwashers,
washing machines and shower heads.
Excessive condensation may be noticed during the
winter and early spring months when incoming water
temperatures are at their lowest.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Powered Anode Operation
Draining and Flushing
To protect the glass-lined water tank from corrosion
through electrolysis, this water heater is equipped with a
non sacrificial powered anode rod. The powered anode
rod is non sacrificial and should not need to be replaced
unless damaged.
If the powered anode rod has been damaged then the
powered anode rod should be removed and replaced
from the water heater tank. IMPORTANT: If the damaged
powered anode rod has not been replaced but has been
remove permanently, this will void any warranties.
Powered Anode System
It is recommended that the tank be drained and flushed
every 6 months to remove sediment which may build up
during operation. The water heater should be drained if
being shut down during freezing temperatures. To drain the
tank, perform the following steps:
To ensure a long, trouble-free
operating life, this water
Powered
Anode
heater is equipped with a
powered anode system.
Rod
The powered anode rod is of
a permanent design and does
not need replacing unless
damaged.
1. Turn off the gas to the water heater at the manual gas
shut-off valve and turn off the electrical power to the
gas control/thermostat valve.
2. Open a nearby hot water faucet until the water is not
longer hot.
FIGURE 22.
NOTE: Whether re-installing or replacing the powered
anode rod, check for any leaks and immediately correct if
found.
3. Close the cold water inlet valve.
4. Connect a hose to the drain valve and terminate it to
an adequate drain or external to the building.
5. Open the water heater drain valve and allow all the
water to drain from the tank. Flush the tank with water
as needed to remove sediment.
In replacing the powered anode:
1. Turn off electrical supply and gas supply to the water
heater.
6. Close the drain valve, refill the tank, and restart the
heater as directed in this manual.
If the water heater is going to be shut down for an
extended period, the drain valve should be left open.
2. Shut off the water supply and open a nearby hot water
faucet to depressurize the water tank.
IMPORTANT: Condensation may occur when refilling the
tank and should not be confused with a tank leak.
3. Drain approximately 5 gallons of water from tank
(Refer to the “Draining and Flushing” section for proper
procedures). Close drain valve.
4. Remove the wiring connection on the top of the
powered anode rod and remove the old powered
anode rod (Figure 22).
5. Use Teflon® tape or approved pipe sealant on threads
and install new anode rod.
Routine Preventive Maintenance
At least annually, a visual inspection should be made of
the venting and air supply system, piping systems, and
main burner. Check the water heater for the following:
•
Obstructions, damage, or deterioration in the venting
system. Make sure the ventilation and combustion air
supplies are not obstructed.
6. Turn on water supply and open nearby hot water faucet
to purge air from water system. Check for any leaks
and immediately correct any if found.
•
•
Clean any dust or debris from the louvers of the air
intake chamber.
Soot and/or carbon on the main burner. Contact a
qualified technician.
7. Turn on electrical and gas supplies. Restart the water
heater as directed under the “Operating Your Water
Heater.” See the “Repair Parts Illustration” section for
anode rod location.
•
•
Leaking or damaged water and gas piping.
Presence of flammable or corrosive materials in the
installation area.
•
•
Presence of combustible materials near the water
heater.
After servicing this water heater, check to make sure
it is working properly. (See “Operating Your Water
Heater” section of this manual.)
TEFLON® is a registered trademark of E.I. Du Pont De Nemours and Company
IMPORTANT: If you lack the necessary skills required to
properly perform this visual inspection, you should not
proceed, but get help from a qualified technician.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
properly. To prevent water damage, the valve must be pro-
perly connected to a discharge line which terminates at an
adequate drain. Standing clear of the outlet (discharged
water may be hot), slowly lift and release the lever handle
on the temperature and pressure relief valve to allow the
valve to operate freely and return to its closed position.
See Figure 23. If the valve fails to completely reset and
continues to release water, immediately shut off the
manual gas control valve and the cold water inlet valve
and call a qualified technician.
Temperature and Pressure Relief Valve
Explosion Harzard
• Temperature-pressure relief
valve must comply with ANSI
Z21.22-CSA 4.4 and ASME
code.
TEMPERATURE AND PRESSURE
RELIEF VALVE
• Properly sized temperature-
pressure relief valve must be
installed in opening provided.
MANUAL RELIEF
VALVE
• Can result in overheating
and excessive tank pressure.
• Can cause serious injury or
death.
DISCHARGE LINE TO DRAIN
Manually operate the temperature and pressure relief
valve at least once a year to make sure it is working
FIGURE 23.
MAINTENANCE OF YOUR WATER HEATER
Replacement Parts
Gas Control Valve/
Thermostat
IMPORTANT: The following maintenance procedures are
for the FVIR System components and should be performed
by a qualified technician.
Replacement parts may be ordered through your plumber
or the local distributor. Parts will be shipped at prevailing
prices and billed accordingly. When ordering replacement
parts, always have the following information ready:
1. model, serial, and product number
2. type of gas
3. item number
4. parts description
See Repair Parts Section for a list of available repair parts.
Manifold Tube
Pressure
Switch / Fan,
FV Sensor
Connector
Power Supply
Transformer
Connector
Igniter/Flame
Sense
Connector
Control Display,
Anode Rod
Connector
Removing the Manifold/Burner Assembly
FIGURE 24.
1. Turn off the gas supply to the water heater at the manual
gas shut-off valve. This valve is typically located beside
the water heater. Note the position of the shut-off valve in
the open/on position then proceed to turn it off (Figure 3).
2. Disconnect power supply to the heater.
3. Remove the outer door. Remove the 2 screw securing
the manifold door assembly to the skirt.
Removing the Burner from the Manifold/
Burner Assembly
Natural Gas Burner
1. Take off the burner by removing the two (2) screws
located underneath the burner.
2. Check the burner to see if it is dirty or clogged. The burner
may be cleaned with soap and hot water (Figure 25).
4. Disconnect all wiring connectors from the gas control
valve/thermostat (Figure 24). Disconnect the manifold
tube at the gas control valve/thermostat.
Manifold Door Assembly
View Port
5. Grasp the manifold tube and push down slightly to free
the manifold from the gas control valve/thermostat.
6. Carefully remove the manifold assembly from the burner
compartment. NOTE: Be sure not to damage internal
parts (Figure 28).
Screws
7. Check the burner to see if it is dirty or clogged. The
burner may be cleaned with soap and hot water.
Igniter/Flame
Sense Connector
Burner
(Bottom View)
FIGURE 25.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Replacing the Flame Sense/Hot Surface igniter Cleaning the Combustion Chamber and Air
Assembly
Diverter Assembly
1. Remove the manifold/burner assembly. See Removing
the Manifold/Burner Assembly.
1. Follow procedure outlined in “Removing the Manifold/
Burner Assembly”.
2. Use a vacuum cleaner/shop vac to remove all loose
debris in the combustion chamber (Figure 28). Use
compressed air to clear any dust or debris that may
have accumulated on the air diverter assembly.
2. Lift the retainer clip straight up from the back of
the manifold component block (using a flat-blade
screwdriver), then remove the manifold component
block from the manifold door (Figure 26.)
3. Remove and keep the screw securing the flame sense/
hot surface igniter assembly (Figure 26)
Combustion
Air Diverter
4. Remove and discard the old flame sense/hot surface
igniter assembly.
Chamber
Assembly
5. Route the new flame sense/hot surface igniter con-
nector wire through manifold/burner door opening as
shown in figure 26. Secure assembly to bracket using
screw removed earlier.
Manifold
Door Gasket
Screw
Retainer Clip
FIGURE 28.
3. Reassemble following the procedure under “Replacing
the Manifold/Burner Assembly”
Flame Sense/
Hot Surface
Igniter Assembly
Replacing the Manifold/Burner Assembly
Manifold Component
Block
WARNING
FIGURE 26.
6. Reposition the manifold component block in the mani-
fold door opening and secure it with the retainer clip.
7. See Replacing the Manifold/Burner Assembly.
Explosion Hazard
External Inspection & Cleaning of the
Air Intake Chamber Screen
Remove any fiberglass between gasket and
•
combustion chamber.
1. At least twice annually inspect the air intake chamber
screen (Figure 27) for any dust or debris that may have
accumulated on the louvers. NOTE: If the water heater
is located in an area that is subjected to lint and dirt,
it may be necessary to check the air intake chamber
screen more frequently.
•
•
Replace viewport if glass is missing or damaged.
Replace two piece wire connector if missing or
removed.
•
•
•
Replace door gasket if damaged.
2. Use a vacuum cleaner with a
hose attachment to remove any
dust or debris that may have
accumulated on the screen.
Tighten both manifold door screws securely.
Failure to follow these instructions can result in
death, explosion, or fire.
1. Check the door gasket for damage or imbedded debris
prior to installation.
2. Inspect the view port for damage and replace as
required.
Air Intake Chamber
Screen
FIGURE 27.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Insert the manifold/burner assembly into the burner
compartment making sure that the tip of the manifold
tube engages in the slot of the bracket inside the
combustion chamber (Figure 29).
4. Inspect the door gasket and make sure there is no
fiberglass insulation between the gasket and the
combustion chamber.
5. Replace the two screws, which secure the manifold/
burner assembly door to the combustion chamber
and tighten securely. Once the manifold/burner
assembly door is tightened, visually inspect the door
gasket between the manifold/burner assembly door
and the combustion chamber for spaces or gaps that
would prevent a seal. IMPORTANT: Do not operate
the water heater if the door gasket does not create a
seal between the manifold door and the combustion
chamber.
6. During the following procedure, do not cross-thread
or apply any thread sealant to any of the fittings listed
below. First, reconnect the manifold tubing to the gas
control valve/thermostat.
7. Reconnect the flame sense/hot surface igniter wire to
the gas control valve/thermostat (Figure 24).
8. Turn gas supply on and refer to the Lighting
Instructions.
3. Turn off the gas supply to the water heater at the
manual gas shut-off valve. This valve is typically located
beside the water heater. Note the position of the shut-
off valve in the open/on position then proceed to turn it
off (Figure 3).
4. Drain the water heater. Refer to the section of
“Draining and Flushing” section and follow the
procedure.
5. Disconnect the the flame sense/hot surface igniter
wire, power supply transformer, pressure switch/
fan and display connector wires from the thermostat
(Figure 24). Disconnect the manifould tube at the
thermostat (Figure 24).
6. Refer to “Gas Piping” section (Figure 3) and disconnect
the ground joint union in the gas piping. Disconnect the
remaining pipe from the gas control valve/thermostat.
7. To remove the gas control valve/thermostat, thread a
correctly sized pipe into the inlet and use it to turn the gas
control valve/thermostat (counterclockwise.) Do not use
pipe wrench or equivalent to grip body. Damage may
result, causing leaks. Do not insert any sharp objects into
the inlet or outlet connections. Damage to the gas control
valve/thermostat may result.
Replacing the Gas Valve:
1. To replace the gas control valve/thermostat,
reassemble in reverse order. When replacing the gas
control valve/ thermostat, thread a correctly sized
pipe into the inlet and use it to turn the gas valve
(clockwise.) DO NOT OVER TIGHTEN or damage may
result. NOTE: Use an approved TEFLON® tape or pipe
compound only on the threaded section of the gas
control valve/thermostat that screws into the tank.
2. Reconnect the gas piping to the gas control valve/
thermostat. NOTE: Use an approved Teflon tape or
pipe compound on the gas piping connections.
3. Reconnect the manifold tube, flame sense/hot surface
igniter wire, power supply transformer, pressure switch/
fan and display connector wires (Figure 24).
9. With the burner lit, check the gas control valve/
thermostat supply line, two piece wire connector, and
manifold tube connections for leaks. Check for leaks by
brushing on an approved noncorrosive leak detection
solution. IMPORTANT: Do Not splash solution onto
the electrical connections. Bubbles forming indicate
a leak. Correct any leak found. All leaks must be fixed
immediately.
10. Replace the outer door (see item K page 5).
Door Gasket
Burner
Slot
4. Fill the tank completely with water. NOTE: To purge the
lines of any excess air, keep the hot water faucet open
for 3 minutes after a constant flow of water is obtained.
5. Turn on the gas supply and test the gas supply
connections by brushing on an approved noncorrosive
leak detection solution. IMPORTANT: Do Not splash
solution onto the electrical connections. Bubbles
forming indicate a leak. Correct any leak found.
6. Check the operation of the burner by following the
lighting instructions on the front of the water heater.
With the burner lit, check the gas control valve/
thermostat supply line, manifold tube connections for
leaks.
Viewport
Manifold Tab
FIGURE 29.
Removing and Replacing the Gas Control
Valve/Thermostat
IMPORTANT: Use only factory authorized replacement
parts.
Removing the Gas Control Valve/Thermostat:
7. Verify proper operation and then replace the outer door.
8. If additional information is required, contact Residential
Technical Assistance by referencing the phone number on
the water heater or on the front cover of this manual.
1. Set the gas control valve/thermostat to its lowest setting
by first depressing the COOLER
buttons together and hold for 1 second. Then press the
and HOTTER
TEFLON® is a registered trademark of E.I. Du Pont De Nemours and Company
COOLER
button until the lowest setting appears
(Figure 21).
2. Unplug the electrical transformer from the wall outlet.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Pressurized Combustion Chamber System
Operational Checklist
1. Manifold gasket properly sealed.
5. No leaks at manifold connection.
6. Manifold door screws securely tightened.
2. Viewport not damaged or cracked.
3. Combustion chamber free of debris and undamaged.
4. Manifold component block properly installed.
TROUBLESHOOTING CHART
PROBLEM
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
1. Transformer unplugged.
2. No power at outlet.
1. Plug transformer back into 120 VAC. outlet.
2. Repair service to outlet.
NO HOT WATER
3. Thermostat defective.
3. Replace Thermostat.
4. Air Intake Chamber Fan defective. 4. Replace Air Intake Chamber Fan Assembly.
5. Pressure Switch defective.
6. Gas Valve/Thermostat Switch in
“OFF POSITION”.
5. Replace Pressure Switch Assembly.
6. Move Gas Valve/Thermostat Switch to “ON
POSITION”.
1. Thermostat set too low.
2. Thermostat defective.
3. Heater undersized.
1. Set temperature control higher.
2. Replace thermostat.
INSUFFICIENT HOT WATER
3. Reduce hot water use.
4. Contact dealer.
4. Low gas pressure.
5. Incoming water is unusually cold.
6. Leaking hot water pipes or fixtures. 6. Have plumber check and repair leaks.
5. Allow more time for heater to reheat.
1. Insufficient secondary air.
2. Water heater flue or vent system
blocked.
1. Provide ventilation to water heater. Check flue
way, flue baffle, and burner.
2. Clean flue, locate source and correct.
3. Check with gas utility company.
4. Replace thermostat.
3. Low gas pressure.
SLOW HOT WATER
RECOVERY
4. Improper calibration.
5. Thermostat set too low.
6. Water heater too small.
7. Wrong piping connections.
8. Wasted hot water.
5. Turn temperature dial to desired setting.
6. Install adequate heater.
7. Correct piping-dip tube must be in cold inlet.
8. Advise customer.
WATER TOO HOT
1. Thermostat set too high.
1. Set temperature control lower.
see, “WATER TEMPERATURE REGULA-
TION”, section.
1. Defective air flow restrictor.
1. Take unit out of service immediately, call a
qualified person to service the unit.
2. Proper dilution air must be provided for
combustion and dilution of flue temp. See
“COMBUSTION AIR SUPPLY/VENT PIPE
SYSTEM”, section.
2. Not enough dilution air to mix with
flue gases in inlet elbow.
VENT PIPE TOO
HOT(ABOVE 170°F)
3. Dilution air too hot for mixing with
flue gases.
3. Supply air is too hot, check for heat sources
around intake terminal and blockage of dilu-
tion air leg.
4. Wrong burner orifice.
4. Install correct orifice.
1. Dirt in burner ports.
1. Turn off heater and gas, clean burner head.
2. Check intake venting arrangements for ob-
structions.
2. Combustion air path restricted.
BURNER FLAME
YELLOW - LAZY
3. Not enough dilution air for proper
combustion.
3. Check intake venting arrangements for ob-
sructions.
4. Main burner line clogged.
4. Clean, locate source and correct.
5. Obstruction in main burner orifice. 5. Clean or replace orifice.
6. Burner flame too high.
7. Flame burns at orifice/thermostat
not functioning properly.
6. Replace with correct orifice.
7. Replace thermostat
8. Low gas pressure.
8. Check with gas utility company.
1. Orifice too large.
2. High gas pressure.
3. Water heater flue or vent system
blocked.
1. Replace with correct-orifice.
2. Check with gas utility company.
3. Clean flue and burner-locate source and cor-
rect.
BURNER FLAME FLOATS
AND LIFTS OFF PORTS
4. Cold drafts.
4. Locate source and correct.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
cont.
PROBLEM
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
1. Insufficient secondary air.
1. Provide ventilation to water heater. Check
flue.
COMBUSTION ODORS
2. Water heater flue or vent system
blocked.
3. Heater installed in a confined area. 3. Provide fresh air ventilation.
2. Clean, located source and correct.
1. Improperly sealed, hot or cold sup- 1. Tighten threaded connections.
ply connections, relief valve, drain
valve or thermostat threads.
WATER LEAKS
2. Leakage from other appliances or
water lines.
2. Inspect other appliances near water heater.
3. Condensation of flue products.
3. See “OPERATIONAL CONDITIONS”, sec-
tion.
4. Excessive water pressure.
4. Use a pressure reducing valve and relief
valve.
5. Heater stacking.
6. Closed water system.
5. Lower the thermostat setting.
6. See “Closed System/Thermal Expansion”.
1. Thermal expansion in closed water 1. Install thermal expansion tank (DO NOT plug
system.
2. Improperly seated valve.
T&P valve).
LEAKING T&P
2. Check relief valve for proper operation (DO
NOT plug T&P valve.
1. High sulfate or mineral content in
water supply.
2. Bacteria in water supply.
1. Drain and flush heater thoroughly then refill.
2. Chlorinate water supply.
HOT WATER ODORS
1. Condensation dripping on burner.
1. See “OPERATIONAL CONDITIONS”, sec-
tion.
WATER HEATER SOUNDS
SIZZLING-RUMBLING
2. Sediment at bottom of heater tank. 2. See “MAINTENANCE OF YOUR WATER
HEATER”, section.
1. Insufficient secondary air.
1. Provide ventilation to water heater. Check flue
way, flue baffle, burner.
SMOKING AND CARBON
FORMATION (SOOTING)
2. Low gas pressure.
3. Water heater flue or vent system
blocked.
2. Check with gas utility company.
3. Clean, locate source and correct.
4. Thermostat not functioning prop-
erly.
4. Replace thermostat.
5. Heater installed in a confined area. 5. Provide fresh air ventilation.
6. Burner flame yellow-lazy.
6. See “Burner Flame Yellow-Lazy”.
HEATING LIGHTS BUT
GOES OUT IN 4-5
SECONDS
1. Outlet polarity is reversed.
1. Test polarity and correct.
1. Thermostat set too high.
2. Sediment or lime in tank.
3. Water heater too small for job.
4. Wrong piping connections.
5. Leaking faucets.
1. Set temperature dial to lower setting.
2. Drain/flush-provide water treatment if needed.
3. Install adequate heater.
HIGH OPERATION COSTS
4. Correct piping-dip tube must be in cold inlet.
5. Repair faucets.
6. Gas leaks.
6. Check with utility-repair at once.
7. Advise customer.
7. Wasted hot water.
8. Long runs of exposed piping.
9. Hot water piping in exposed wall.
8. Insulate piping.
9. Insulate piping.
THERMOSTAT FAILS TO
SHUT-OFF
1. Thermostat not functioning proper- 1. Replace thermostat.
erly.
2. Improper calibration.
2. Replace thermostat.
CONDENSATION
1. Thermostat set too high.
2. Water dripping from draft hood.
1. See “OPERATIONAL CONDITIONS” section.
2. Provide drip “TEE” to catch condensation
from horizontal section of exhaust vent close
to draft hood.
1. Excessive water pressure.
2. Heater stacking.
1. Use a pressure reducing valve and relief
valve.
2. Lower the thermostat setting.
DRIP FROM RELIEF VALVE
3. Closed water system.
3. See “CLOSED SYSTEM/THERMAL EXPAN-
SION”, section.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL DISPLAY TROUBLESHOOTING
ELECTRONIC CONTROL DISPLAY
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service person.
Read the GENERAL SAFETY INFORMATION supplied by the water heater manufacturer.
CONTROL DISPLAY STATUS
“POWER” Flashing
PROBLEM
SOLUTION
1. Check the 5-conductor data cable that
runs between the upper and lower
controls. Check that the wiring is not
broken, and the connectors on both ends
are properly seated in the mating
connectors.
1.
Communication Error
The system has detected a
communication error between the
upper and lower controls.
2. Replace the upper control, if the problem
persists:
3. Replace the lower control.
1. Turn the power off for 10 to 20 seconds
2.
3.
“HEATING” and “SHORT” Flashing
“HEATING” and “OPEN” Flashing
The self-diagnostic tests have
found a problem with an internal
circuit.
then on again to clear the error code.
2. If the error code persists or cannot be
cleared, replace the lower control.
1. Gas supply is turned off – pressure too
low. Ensure supply and manifold gas
pressures are within requirements in the
installation manual. Manifold gas
pressure is non-adjustable, if pressure is
off by more than 0.3” W.C. (75 Pa)
replace the lower control.
Ignition/flame failure.
The water heater has reached the
maximum number of retries and is
currently locked out for one hour.
Cycle the power to the water
heater off and on to reset.
2. Low supply voltage – should be 115 –
125 VAC.
3. Ensure flame sensor is making good
contact with the burner flame, ensure
flame is steady.
4. Ensure the flame sensor is clean – use
TM
ultra fine steel wool or Scotch-Brite pad
to clean the flame sensor.
5. Ensure the hot surface ignitor is
positioned to provide consistent ignition.
6. Check for any cracks in the ignitor
assembly ceramic insulators – replace
ignitor assembly if damaged.
7. Check resistance of the ignitor at room
temperature (77°F – 25°C) at the plug
end. Replace ignitor if the resistance is
not within 1.38 to 2.31 ohms at room
temperature.
1. Ensure flame sensor is making good
contact with the burner flame, ensure
flame is steady.
4.
5.
“HEATING”, “OPEN”, and “SHORT” Flashing
“ECO” and “OPEN” Flashing
Weak flame sensor current.
2. Ensure the flame sensor is clean – use
TM
ultra fine steel wool or Scotch-Brite pad
to clean the flame sensor.
1. Turn the power off for 10 – 20 seconds
Water temperature in the tank has
exceeded 185°F (85°C) and has
activated the ECO.
then on again to clear this error code.
2. Replace the lower control if the error
code persists.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
cont.
CONTROL DISPLAY STATUS
PROBLEM
SOLUTION
1. Clean the screen on the combustion air
intake tube. Retest, if the problem
persists:
6.
“P-SW”, “OPEN”, and “CLEAN SCREEN” Flashing
The air pressure switch contacts
remain open longer than 5
seconds after the combustion fan
is energized.
2. Ensure the pressure switch sensing tube
is in good condition and securely
connected at both ends.
3. Ensure the inner door to the combustion
chamber is secure and the gasket is
properly sealing.
4. Take a pressure reading from the
pressure switch’s sensing point on the
inner door with a digital manometer.
A. If actual pressure reaches design
“make-point” for the switch check
pressure switch contacts continuity
with the combustion fan running. If
switch contacts remain open replace
switch.
B. If pressure does not reach “make-
point” check system for restrictions
and cleanliness.
1. Turn off power to the water hater.
7.
“P-SW” and “SHORT” Flashing
The air pressure switch contacts
remain closed for more than 5
seconds when they should be
open.
2. Locate the pressure switch wiring –
ensure pressure switch wiring is correct
and not jumped.
3. Remove wires to both terminals on
pressure switch.
4. Check pressure switch contacts with an
ohmmeter for continuity.
A. If pressure switch contacts show
continuity (closed circuit) replace
the pressure switch.
B. If pressure switch contacts show
open circuit and all wiring is correct
– replace the lower control.
1. Check all wiring to the hot surface ignitor.
8.
“IGN” Flashing
Open ignitor circuit
2. Check the 3 pin Molex ignitor assembly
plug and receptacle on the lower control
for a good connection. Repair or replace
parts if necessary.
3. Check resistance of the ignitor with an
ohmmeter on the ignitor assembly plug.
Replace ignitor if resistance is not within
1.38 and 2.31 ohms.
4. If above checks are good – turn off
power for 10 seconds and then back on.
If this error code will not clear and the
ignitor resistance is within specifications
– replace the lower control.
Flammable Vapor Sensor has
detected the presence of
flammable vapors and is in lockout
1. Contact a service agency to determine
the cause.
9.
“FV-SENSE” Flashing
The air pressure switch contacts
remain open longer than 5
seconds after the combustion fan
is energized.
1. Clean the screen on the combustion air
intake tube. Retest, if the problem
persists:
10.
“LDO-SW”, “OPEN”, and “CLEAN SCREEN”
Flashing
31
Download from Www.Somanuals.com. All Manuals Search And Download.
cont.
CONTROL DISPLAY STATUS
“FV-SENSE” and “OPEN” Flashing
PROBLEM
SOLUTION
1. Check all wiring to the flammable vapor
sensor.
11.
Flammable Vapor Sensor is open
2. Remove the connectors from the
flammable vapor sensor and measure
the resistance of the sensor with an
ohmmeter.
A. If the reading taken is more than
1.7 million ohms, replace the
flammable vapor sensor.
B. If the reading taken is less than 1.7
million ohms, and the wiring from
the control to the sensor is good,
replace the lower control.
1. Check all wiring to the flammable vapor
12.
“FV-SENSE” and “SHORT” Flashing
Flammable Vapor Sensor is
shorted
sensor.
2. Remove the connectors from the
flammable vapor sensor and measure
the resistance of the sensor with an
ohmmeter.
A. If the reading taken is less than
2000 ohms, replace the flammable
vapor sensor.
B. If the reading taken is more than
2000 ohms, and the wiring from the
control to the sensor is good,
replace the lower control.
1. Turn power off for 10 to 20 seconds then
13.
14.
15.
“THMSTR” and “OPEN” Flashing
“THMSTR” and “SHORT” Flashing
All Segments Flashing
The self-diagnostic test has
detected the temperature sensor
(thermistor) inside the immersion
probe is open.
on again to clear this error code.
2. This part of the control cannot be
replaced or serviced. If the error code
cannot be cleared, the lower control must
be replaced.
1. Turn power off for 10 to 20 seconds then
The self-diagnostic test has
detected the temperature sensor
(thermistor) inside the immersion
probe is shorted.
on again to clear this error code.
2. This part of the control cannot be
replaced or serviced. If the error code
cannot be cleared, the lower control must
be replaced.
1. Press and release each of the
The self-diagnostic check has
detected one or both of the
temperature adjustment buttons
are stuck.
temperature adjustment buttons. If the
above action does not clear the error, the
control will continue to regulate the water
temperature at the last setting. However,
settings will no longer be adjustable – the
upper control should be replaced.
1. Check the wire that runs from the power
anode to the upper control. Check the
wire for damage, and to ensure that the
connectors are fully seated into the
mating connectors on both ends.
16.
“P-ANODE” and “OPEN” Flashing
No current to Power Anode.
2. Check that the tank is full of water. Never
use this water heater unless it is
completely full of water. To prevent
damage to the tank, the tank must be
filled with water. Water must flow from
the hot water faucet before turning “ON”
gas to the water heater.
1. Turn the power off for 10 to 20 seconds
17.
“P-ANODE” Flashing
Power Anode circuit failure.
then on again to clear the error code.
2. If the error code persists or cannot be
cleared, replace the upper control.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING FLOWCHART
APPLY POWER TO
APPLIANCE
NO
REQUEST
FOR HEAT
PRESENT?
3 MINUTE
AUTOMATIC RESET
TIME DELAY
YES
WAIT FOR PRESSURE
SWITCH TO OPEN
DISPLAY ERROR
IS
NO
PRESSURE SWITCH
PROVEN OPEN WITHIN
NUMBER
7
5
SECONDS?
YES
COMBUSTION
FAN ON
IS
WAIT FOR PRESSURE
SWITCH TO OPEN
DISPLAY ERROR
NO
PRESSURE SWITCH
PROVEN OPEN WITHIN
5
SECONDS?
NUMBER
7
IS
WAIT FOR PRESSURE
SWITCH TO CLOSE
DISPLAY ERROR
YES
NO
PRESSURE SWITCH
PROVEN CLOSED
WITHIN
5
NUMBER
6
SECONDS?
ONE HOUR
AUTOMATIC RESTART
TIME DELAY
YES
PREPURGE
COMBUSTION FAN
OFF
TURN OFF
COMBUSTION FAN,
DISPLAY ERROR CODE
NO
IS
IGNITOR
OKAY?
NUMBER
8
YES
IGNITOR ON FOR
WARM-UP TIME
TURN OFF
COMBUSTION FAN
AFTER POST-PURGE
COMBUSTION
FAN OFF
DISPLAY ERROR
3
GAS VALVE OPENS
YES
IS
NO
WAIT FOR PRESSURE
SWITCH TO CLOSE
DISPLAY ERROR
PRESSURE SWITCH
PROVEN CLOSED
COMBUSTION FAN
ON
WITHIN
5
NUMBER
6
SECONDS?
MAIN
BURNER LIGHTS
AND IS SENSED
DURING TRIAL
FOR
YES
NO
LESS
GAS VALVE CLOSES
INTERPURGE
THAN
3
TRIES
FOR IGNITION?
IGNITION
NO
YES
IGNITOR TURNS OFF
YES
LOST
IS
YES
GAS VALVE CLOSES
FLAME SENSE
LOST?
LESS THAN
TIMES?
4
NO
NO
IS
WAIT FOR PRESSURE
SWITCH TO CLOSE
DISPLAY ERROR
NO
PRESSURE SWITCH
PROVEN CLOSED
WITHIN
SECONDS?
5
NUMBER
6
Please Note:
The control continually monitors
YES
internal circuits and external sensors.
Error codes noted above, and those for
self-diagnostic faults can be found on
pages 30 through 32.
YES
IS
COMBUSTION FAN
OFF AFTER POST-
PURGE DELAY
REQUEST FOR HEAT
SATISFIED?
GAS VALVE OFF
NO
33
Download from Www.Somanuals.com. All Manuals Search And Download.
REPAIR PARTS ILLUSTRATION
3
1
2
4
When ordering repair parts always give
the following information:
1. Model, serial, and product number
2. Type of gas
3. Item number
5
8
4. Parts description
6
9
7
10
18
20
19
21
11
12
14
Repair Parts List
Item
No.
Parts Description
1
Draft Hood
2
Flue Baffle
3
Nipple (Hot)
4
Nipple (Cold)
5
Anode Rod
6
Cold Water Inlet Tube
Temperature and Pressure Valve
Control Display
7
8
9
Air Intake Chamber
Gas Control Valve/Thermostat
Drain Valve
10
11
12* Natural Gas Burner
13* Hot Surface Igniter (HSI)
14* Manifold Door Assembly - Natural Gas
15* Manifold Component Block w/Retainer Clip
16* Manifold Door Gasket
LEGEND
Special anode rod (see Anode Rod/Water Odor
17* Viewport Assembly
section)
18
19
20
21
FV Sensor
Temperature and Pressure Relief Valve is required,
but may not be factory installed
Outer Door
Electrical Transformer
Pressure Switch
*Pictured on next page.
Unique: FVIR System parts
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Listed Parts Kits and Illustrations
Item 12A: Burner (Natural Gas)
Item 13:
Item 14:
Flame Sense/Hot Surface Igniter Assembly.
Manifold door assembly which contains the manifold tube, gasket, manifold door, manifold component block
with retainer clip, and flame sense/hot surface igniter assembly. (Natural Gas)
Item 15:
Item 16:
Item 17:
Contains manifold component block with retainer clip.
Contains manifold door gasket.
Contains viewport.
ITEM 13
ITEM 12
ITEM 14
ITEM 15
ITEM 17
ITEM 16
35
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
36
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
37
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
38
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED RESIDENTIAL GAS WARRANTY
THIS WARRANTY IS APPLICABLE TO THE ORIGINAL
OWNER ONLY in accordance with the warranty terms and
conditions specified below.
•
•
in its original installation location;
in the United States, its territories or possessions, and
Canada;
•
•
•
•
sized in accordance with proper sizing techniques for
residential water heaters;
The warrantor will furnish the ORIGINAL OWNER, 1) a
replacement water heater of equivalent size and current
model if the glass-lined tank in this water heater leaks
and, 2) a replacement part for any component part
which fails.
bearing a rating plate which has not been altered, defaced
or removed except as required by the warrantor;
used in an open system or in a closed system with a
properly sized and installed thermal expansion tank;
operated with properly installed drip leg in the gas supply
line;
fired with the fuel for which it was factory built;
fired at the factory rated input;
operated with the inner and outer combustion chamber
doors in place and all factory seals to combustion
chamber intact.
installed with no attempted, nor actual modification or
alteration of the water heater’s design in any way,
including but not limited to, the attachment of non-
company approved appliances or equipment, including
any additional aftermarket equipment introduced into
the sealed system.
THE WATER HEATER REPLACEMENT MODEL
OR PART WILL BE WARRANTED FOR ONLY THE
UNEXPIRED PORTION OF THE ORIGINAL WARRANTY.
The warranty period will be determined by the original
date of purchase of the water heater, or in the absence
of a Bill of Sale verifying said date, from the date of
manufacture indicated on rating plate affixed to this
water heater. This warranty is not transferable and
applies to models listed below:
•
•
•
•
SERIES
TANK
PARTS
6-Year
6-Year Models
6-Year
GP 6
Any accident to the water heater or any part thereof (including
freezing, fire, floods, or lightning), any misuse, abuse or
alteration of it, any operation of it in a modified form, any
operation of the water heater on desalinated (deionized)
water, or any damage caused by attempts to repair tank
leaks or parts, will void this warranty. This warranty does
not cover water heaters replaced for cosmetic reasons or for
reasons of noise, taste, odor, discolored and/or rusty water.
This warranty does not apply to water heaters used to heat
pools, whirlpools or hot tubs or used for space heating where
its sizing does not conform with specifications of the heating
component manufacturer.
When the water heater has been used for other than single
family residential application;
1. The tank warranty shall be reduced to 1 year for 6 year
models and to 3 years for 10 year models.
2. The parts warranty shall be reduced to 1 year for all
models.
CONDITIONS AND EXCEPTIONS
This warranty shall apply only when the water heater is
installed and operated in accordance with 1) all local fire
codes and plumbing codes, ordinances and regulations,
2) the printed instructions provided with it, 3) good industry
practices, and 4) proper safety practices such as but not
limited to a properly sized drain pan if installed in an area
where leakage from the tank or its connections would result
in damage to the area adjacent to the heater. In addition, a
new temperature and pressure relief valve, certified by the
Canadian GasAssociation must have been properly installed
and piped to the nearest drain.
This warranty gives you specific legal rights, and you may
have other rights which vary under the laws of each state. If
any provision of this warranty is prohibited or invalid under
applicable state law, that provision shall be ineffective to the
extent of the prohibition or invalidity without invalidating the
remainder of the affected provision or the other provisions of
this warranty.
SERVICE AND LABOR RESPONSIBILITY
UNDER THIS LIMITED WARRANTY, THE WARRANTOR
WILL PROVIDE ONLY A REPLACEMENT WATER HEATER
OR PART THEREOF. THE OWNER IS RESPONSIBLE FOR
ALL OTHER COSTS. Such costs may include but are not
limited to:
This warranty shall apply only when the heater is:
•
•
•
owned by the original purchaser;
installed for indoor operation only;
used at temperatures not exceeding the maximum
calibrated setting of its thermostat;
a. Labor charges for service, removal, or reinstallation of
the water heater or part thereof.
b. Shipping and delivery charges for forwarding the new water
heater or replacement part from the nearest distributor
and returning the claimed defective heater or part to such
distributor.
c. All cost necessary or incidental for handling and
administrative charges, and for any materials and/or
permits required for installation of the replacement heater
or part.
•
•
used at water pressure not exceeding the working
pressure shown on the heater;
filled with potable water, free to circulate at all times and
with the tank free of damaging water sediment or scale
deposits;
•
•
used in a non-corrosive and non-contaminated
atmosphere;
used with factory approved anode(s) installed;
39
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITATION ON IMPLIED WARRANTIES
NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF
USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE
TO PERSONALPROPERTY, OR OTHER CONSEQUENTIAL
DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE
BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR
DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER
DIRECT OR INDIRECT, AND WHETHER ARISING IN
CONTRACT OR IN TORT.
Implied warranties, including any warranty of merchantability
imposed on the sale of this heater under state law are limited
to one year duration for the heater or any of its parts. Some
states do not allow limitations on how long an implied warranty
lasts, so the above limitations may not apply to you.
CLAIM PROCEDURE
Any claim under this warranty should be initiated with the
dealer who sold the heater, or with any other dealer handling
the warrantor’s products. If this is not practical, the owner
should contact: State Industries, Inc., 500 Tennessee
Waltz Parkway, Ashland City, Tennessee 37015. Phone:
Should governmental regulations or industry standards
prohibit the Manufacturer from furnishing a comparable model
replacement under this warranty, the Owner will be furnished
with the closest comparable water heater meeting the then
current governmental regulations and industry standards. A
supplementary fee may be assessed to cover the additional
cost associated with the changes made to meet applicable
regulations and standards.
Replacement Parts may be ordered through authorized
servicers or distributors. Refer to your local Yellow Pages
for where to call or contact State Industries, Inc., Parts
Fullfillment, 125 Southeast Parkway, Franklin, TN 37068,
phone: 1.800.821.2017.
IMPORTANT INFORMATION
Model Number ________________________________
Serial Number _________________________________
INSTALLATION INFORMATION
The warrantor will only honor replacement with identical or
similar water heater or parts thereof which are manufactured
or distributed by the warrantor.
Dealer replacements are made subject to in-warranty
validation by warrantor.
PROOF-OF-PURCHASE AND PROOF-OF-INSTALLATION
DATE ARE REQUIRED TO SUPPORT WARRANTY CLAIM
FROM ORIGINAL OWNER. THIS FORM DOES NOT
CONSTITUTE PROOF-OF-PURCHASE OR PROOF-OF-
INSTALLATION.
Date Installed _________________________________
Company’s Name ______________________________
Street or P.O. Box ______________________________
City, State, and Zip Code_________________________
Phone Number ________________________________
Plumber’s Name _______________________________
DISCLAIMERS
NO EXPRESSED WARRANTY HAS BEEN OR WILL BE
MADE ON BEHALF OF THE WARRANTOR WITH RESPECT
TO THE MERCHANTABILITY OF THE HEATER OR THE
INSTALLATION, OPERATION, REPAIR OR REPLACEMENT
OF THE HEATER OR PARTS. THE WARRANTOR SHALL
40
Download from Www.Somanuals.com. All Manuals Search And Download.
|