Socket Mobile Network Card Ethernet Blaster Communications Cable User Manual

EthernetBlaster Communications Cable  
User Guide  
101 Innovation Drive  
UG-120904-1.0  
P25-10326-00  
Document Version:  
Document Date:  
1.0  
December 2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Altera Corporation  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
iv  
Altera Corporation  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1. About the  
EthernetBlaster  
Communications Cable  
The EthernetBlaster communications cable connects to a standard  
Ethernet network port with an RJ-45 connector. This cable communicates  
with client systems using the TCP/IP protocol and supports both static  
and dynamic IP addressing. The EthernetBlaster communications cable  
can be plugged into an existing 10/100 Base-T Ethernet network to  
communicate with clients remotely or interfaced directly via a standard  
10/100 Base-T Ethernet port using a crossover cable. Because design  
changes are downloaded directly to the device, prototyping is easy and  
you can accomplish multiple design iterations in quick succession.  
Harnessing the power of an Ethernet network, multiple users can  
remotely access Altera® devices, bringing a new level of productivity to  
prototyping and debugging.  
Introduction  
Supported Devices  
You can use the EthernetBlaster communications cable to download  
configuration data to the following Altera devices:  
Stratix® series FPGAs  
Cycloneseries FPGAs  
MAX® series CPLDs  
APEXseries FPGAs  
ACEX® 1K FPGAs  
MercuryFPGAs  
FLEX® series FPGAs  
ExcaliburFPGAs  
You can perform in-system programming of the following devices:  
Advanced configuration devices, including EPC2, EPC4, EPC8,  
EPC16, and EPC1441 devices.  
Serial configuration devices, including EPCS1, EPCS4, EPCS16, and  
EPCS64 devices.  
In addition, the EthernetBlaster communications cable supports target  
systems using 5.0-V TTL, 3.3-V LVTTL/LVCMOS, and single-ended I/O  
standards from 3.3 V down to 1.5 V.  
Altera Corporation  
December 2004  
1–1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Introduction  
Power Requirements  
The EthernetBlaster communications cable requires between 1.5 V and  
5.0 V from the target circuit board, and 12.0 VDC (0.875A) input power  
for the EthernetBlaster VCCSUPPLY (a 12.0 VDC wall transformer is  
supplied).  
The EthernetBlaster VCC(TARGET) pin must be connected to the appropriate  
voltage for the device being programmed. The pull-up resistors on the  
target circuit board for the configuration/programming signals must be  
connected to the same power supply as the EthernetBlaster VCC(TARGET)  
.
Software Requirements  
The EthernetBlaster communications cable is available on the Windows,  
UNIX, and Linux platforms, including the following:  
Windows NT 4.0  
Windows 2000  
Windows XP  
Solaris 2.6  
Solaris 2.7/7  
Solaris 8/9  
Red Hat Linux version 7.3  
Red Hat Linux version 8.0  
Red Hat Enterprise Linux WS 3.0  
HP-UX version 11.0  
Use the Quartus® II software beginning with version 4.0 to configure your  
device. The EthernetBlaster communications cable also supports the  
following tools:  
Quartus II Programmer (for programming and configuration),  
which you can run within the Quartus II software or as a stand-alone  
version  
Quartus II SignalTap II Logic Analyzer (for logic analysis), which  
you can run within the Quartus II software or as a stand-alone  
version  
Nios® II IDE (for software downloading and debugging)  
Nios II IDE Flash Programmer (for programming Flash devices)  
Connections  
The EthernetBlaster communications cable houses an Ethernet port on  
one side and a 10-pin female target port on the opposite side. The  
Ethernet port side contains an Ethernet port, a reset button, and a DC12V  
1–2  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
     
About the EthernetBlaster Communications Cable  
jack. The target port side includes the 10-pin female target port and LED  
status light. The base of the cable includes the MAC address and host  
name. Figure 1–1 shows the side and base views of the hardware.  
Figure 1–1. EthernetBlaster Communications Cable Ethernet Port, Target Port, and Base Views  
Ethernet Port View  
Target Port View  
DC12V  
ETHERNET  
TARGET  
STATUS  
Ethernet Port  
Machine Reset  
DC12V Jack  
10-Pin Target Port  
Status LED  
Base View  
Ethernet Blaster  
Copyright 2004 Altera Corporation  
MAC Address  
Host Name  
D0:07:ED:05:XX:XX  
Host Name: acebXXXX  
The status LED on the target port side of the cable displays the operation  
status of the EthernetBlaster communications cable. See Table 1–1 for a  
description of each LED status modes.  
Table 1–1. Status LED Modes  
Status LED  
Status Description  
Red-Green  
Power on, reset  
Green, blinking  
Green, steady  
Blue, blinking  
Cable initialization  
Cable ready  
Downloading data to target printed circuit board  
Altera Corporation  
December 2004  
1–3  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Cable Setup  
Static & Dynamic IP Addressing  
The EthernetBlaster communications cable supports both static IP and  
dynamic IP addressing, the latter by means of Dynamic Host  
Configuration Protocol (DHCP). By default, the EthernetBlaster cable is  
configured at the factory to use dynamic IP addressing. Upon power up,  
the cable attempts to obtain an IP address from your network DHCP  
server. The Status LED is green and blinking while the network address  
is being obtained and the cable is initializing. This process may take up to  
two minutes.  
When an IP address is obtained and the cable is ready to use, the status  
LED emits a steady green light. If the attempt to obtain an IP address is  
unsuccessful (the DHCP server may be down or absent), the cable  
switches to static IP addressing. The default IP address is configured to  
192.168.0.50. If static IP addressing is used, you must configure your  
computer to an IP address in the same subnet as the cable to communicate  
with it. The default setting requires your address to be in the 192.168.0.X  
network domain.  
Refer to your operating system manual or contact your network  
administrator to verify that your network supports DHCP  
services and for instruction on how to change your IP address.  
To maintain your computer’s IP address and change the  
EthernetBlaster communications cable’s default IP address, see  
The EthernetBlaster communications cable includes a self-hosted  
administrative web page, allowing you to configure various aspects of  
cable operation. The following section describes how to access this web  
page based on your mode of connection.  
This section describes how to install and set up the EthernetBlaster  
communications cable for device configuration or programming  
including the following setups:  
Cable Setup  
1–4  
Altera Corporation  
EthernetBlaster Communications Cable User Guide  
December 2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
About the EthernetBlaster Communications Cable  
For plug and header dimensions, pin names, and operating  
conditions, see Chapter 3, “EthernetBlaster Communications  
Cable Specifications.”  
Remote Connection via Network Using Default Factory Settings  
Use the following steps to connect remotely to the EthernetBlaster  
communications cable:  
These steps assume no changes have been made to the default  
factory settings.  
1. Disconnect the power cable from the circuit board.  
2. Plug one end of a standard CAT 5 UTP 4-pair patch cable into the  
Ethernet jack on the EthernetBlaster communications cable, and the  
other end into a network port of a switch, router, or hub. See  
Figure 1–2 below.  
Figure 1–2. Remote Connection via Network  
EthernetBlaster Communications Cable,  
Ethernet Port Side View  
Switch, Router, or Hub  
DC12V  
ETHERNET  
ETHERNET  
Ethernet  
Jack  
CAT 5 UTP  
Standard Cable  
Ethernet Jack  
Pin EIA/TIA 568B Wire Color  
1
2
3
4
5
6
7
8
White with Orange Stripe  
Orange with White Stripe  
White with Green Stripe  
Blue with White Stripe  
White with Blue Stripe  
Green with White Stripe  
White with Brown Stripe  
Brown with White Stripe  
1
.
.
.
8
CAT 5 UTP  
Standard Cable  
Ethernet Connector  
EIA/TIA 568B  
3. Connect the 10-pin female plug of the flexible, PCB-shielded cable  
labeled “BLASTER SIDE” to the 10-pin female target port on the  
Ethernet communications cable, and the 10-pin female plug of the  
cable labeled “TARGET SIDE” to the 10-pin male header on the  
target circuit board as shown in Figure 1–3 on page 1–6.  
Altera Corporation  
December 2004  
1–5  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Cable Setup  
Figure 1–3. Connecting the EthernetBlaster Communications Cable to the Target Circuit Board  
10-pin Female Connector (connects  
to the target printed circuit board  
10-pin male header)  
Pin 1 of the Flexible PCB  
Shielded-Cable Facing this Side  
netBlaster  
ETHERNET  
DC12V  
4. Plug the supplied 12.0 VDC wall transformer into a power outlet  
and then into the EthernetBlaster communications cable.  
Always connect the network patch cable as instructed in  
step 2 before connecting the power cord. This allows the  
EthernetBlaster communications cable to obtain a DHCP  
address (if your network is configured to do so). Wait until  
the Status LED emits a steady green light.  
5. Reconnect the power cable to the circuit board to reapply power.  
6. If your network supports DHCP, see step 7 on the following page  
for configuration instructions. If your network does not support  
DHCP, see step 8 on the following page for configuration  
instructions.  
7. If your network supports DHCP, you can access the EthernetBlaster  
Configuration administrative web page using a web browser with  
the hostname as the address. The hostname is located on the label  
on the base of the EthernetBlaster communications cable as shown  
1–6  
Altera Corporation  
December 2004  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
About the EthernetBlaster Communications Cable  
Figure 1–4. MAC Address & Host Name  
EthernetBlaster Communications Cable Bottom View  
Ethernet Blaster  
Copyright 2004 Altera Corporation  
D0:07:ED:05:XX:XX  
Host Name: acebXXXX  
The last 4 digits of the MAC address  
are the same as the last 4 digits of  
the host name.  
Use the hostname as the address  
to access the EthernetBlaster  
communications cable  
configuration administrative  
web page.  
Browse to http://<host name> and specify the host name from the  
label on the base of your EthernetBlaster communications cable. The  
EthernetBlaster login window opens.  
Note that the last 4 digits of the MAC address match the last  
4 digits of the host name on the label on the base of your  
EthernetBlaster cable.  
or  
If you know the IP address obtained by the EthernetBlaster  
communications cable, you can access the administrative web page  
by entering this address in your browser.  
See step 9 on the following page for system configuration  
details.  
8. If your network does not support DHCP, you must configure your  
computer to an address in the 192.168.0.X network domain, and  
then browse to http://192.168.0.50. See step 9 on the following page  
for system configuration details.  
Refer to your operating system manual or contact your  
network administrator for instruction on how to change  
your IP address.  
Altera Corporation  
December 2004  
1–7  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Cable Setup  
To maintain your computer’s IP address and change the  
EthernetBlaster communications cable default IP address,  
9. In the EthernetBlaster login window, enter admin as the login and  
password as the default password. The EthernetBlaster Status  
page opens, displaying the status of your EthernetBlaster  
communications cable, including the current IP address. See  
Figure 1–5. EthernetBlaster Configuration Administrative Page  
See Chapter 2, “Managing Passwords,” to manage your  
password after initial login.  
Quartus II Software” on page 1–13 to set up your hardware in the  
Quartus II software.  
Direct Connection to a Computer Using Default Factory Settings  
The EthernetBlaster communications cable can be connected directly to  
the network port of a computer. This setup does not allow remote users  
to access the EthernetBlaster communications cable.  
Use the following steps to connect the EthernetBlaster communications  
cable directly to your system:  
1–8  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
     
About the EthernetBlaster Communications Cable  
These steps assume no changes have been made to the  
default factory settings.  
1. Disconnect the power cable from the circuit board.  
2. Plug the EIA/TIA 568B connector of a crossover CAT 5 UTP 4-pair  
patch cable into the Ethernet jack on the EthernetBlaster  
communications cable, and the EIA/TIA 568A connector into your  
computer. See Figure 1–6 below.  
Figure 1–6. Direct Connection to a Computer Using a Crossover Cable  
Computer  
EthernetBlaster Communications Cable,  
Ethernet Port Side View  
Ethernet Jack  
ETHERNET  
DC12V  
ETHERNET  
Ethernet  
Jack  
CAT 5 UTP  
Crossover Cable  
Pin EIA/TIA 568A Wire Color  
. . .  
1
8
1
White with Green Stripe  
Green with White Stripe  
White with Orange Stripe  
Blue with White Stripe  
White with Blue Stripe  
Orange with White Stripe  
White with Brown Stripe  
Brown with White Stripe  
. . .  
1
8
Pin EIA/TIA 568B Wire Color  
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
White with Orange Stripe  
Orange with White Stripe  
White with Green Stripe  
Blue with White Stripe  
White with Blue Stripe  
Green with White Stripe  
White with Brown Stripe  
Brown with White Stripe  
Ethernet EIA/TIA 568A Connector  
Connected to the Computer  
Ethernet EIA/TIA 568B Connector Connected  
to the EthernetBlaster Communications Cable  
CAT 5 UTP Crossover Cable  
CAT 5 UTP Crossover Cable  
or  
Plug one end of a standard CAT5 UTP 4-pair patch cable into the  
Ethernet jack on the EthernetBlaster communications cable, and add  
a crossover adapter to the other end of the cable. Plug the adapter  
end of the cable into your computer. See Figure 1–7 on page 1–10.  
Altera Corporation  
December 2004  
1–9  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Cable Setup  
Figure 1–7. Direct Connection to a Computer Using a Standard Cable and a Crossover Adapter  
Computer  
ETHERNET  
EthernetBlaster Communications Cable,  
Ethernet Port Side View  
ETHERNET  
Ethernet Jack  
DC12V  
Crossover  
Adapter  
ETHERNET  
Ethernet  
Jack  
EIA/TIA 568B  
Connector  
EIA/TIA 568B  
Connector  
CAT 5 UTP  
Standard Cable  
3. Connect the 10-pin female plug of the flexible, PCB-shielded cable  
labeled “BLASTER SIDE” to the 10-pin female target port on the  
Ethernet communications cable, and the 10-pin female plug of the  
cable labeled “TARGET SIDE” to the 10-pin male header on the  
target circuit board as shown in Figure 1–3 on page 1–6.  
4. Plug the supplied 12.0 VDC wall transformer into a power outlet  
and then into the EthernetBlaster communications cable.  
5. Reconnect the power cable to the target circuit board to reapply  
power.  
6. To access the EthernetBlaster Status web page, configure your  
computer to an address in the 192.168.0.X network domain and then  
browse to http://192.168.0.50. The EthernetBlaster login window  
opens.  
Refer to your operating system manual or contact your  
network administrator for instruction on how to change  
your IP address.  
To maintain your computer’s IP address and change the  
EthernetBlaster communications cable default IP address, see  
1–10  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
 
About the EthernetBlaster Communications Cable  
7. In the EthernetBlaster login window, enter admin as the login and  
password as the default password. The EthernetBlaster Status  
page opens displaying the status of your EthernetBlaster  
communications cable including the current IP address. See  
See Chapter 2, “Managing Passwords,” to manage your  
password after initial login.  
8. To set up the EthernetBlaster communications cable in the  
Configuring the EthernetBlaster Hardware to Use Static IP  
Addressing  
By default, the EthernetBlaster communications cable is factory  
configured to use dynamic IP addressing.  
Depending on your connection mode, this section assumes that  
you have completed the steps in “Remote Connection via  
To configure your cable to use static IP addressing and complete your  
remote connection, follow the directions below:  
1. Open the EthernetBlaster Status page.  
2. Click the Change Settings tab and select Static IP from the  
Connection Type menu. Enter the desired IP address and other  
appropriate data in the settings fields. See Figure 1–8 on page 1–12.  
Contact your network administrator if you do not know the  
settings to complete the Change Settings page.  
Altera Corporation  
December 2004  
1–11  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Cable Setup  
Figure 1–8. EthernetBlaster Change Settings Page  
3. Click Apply. The EthernetBlaster communications cable  
automatically restarts. When the status LED returns to a steady  
green state, the EthernetBlaster communications cable has  
successfully restarted and can now be added to the Quartus II  
Configuring the EthernetBlaster Hardware to Use Dynamic IP  
Addressing  
To configure the EthernetBlaster communications cable to use dynamic  
IP addressing, follow the directions below:  
Depending on your connection mode, this section assumes that  
you have completed the steps in “Remote Connection via  
1. Open the EthernetBlaster Status page.  
1–12  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
   
About the EthernetBlaster Communications Cable  
2. Click the Change Settings tab and select DHCP from the  
Connection Type menu. See Figure 1–8 below.  
Figure 1–9. EthernetBlaster Change Settings Page  
Contact your network administrator if you do not know the  
settings to complete the Change Settings page.  
3. Click Apply. The EthernetBlaster communications cable  
automatically restarts. When the status LED returns to a steady  
green state, the EthernetBlaster communications cable has  
successfully restarted and can now be added to the Quartus II  
Setting Up the EthernetBlaster Hardware in the Quartus II  
Software  
Use the following steps to set up the EthernetBlaster communications  
cable in the Quartus II software.  
1. Start the Quartus II software.  
Altera Corporation  
December 2004  
1–13  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Cable Setup  
2. Choose Programmer (Tools menu).  
3. Click Hardware Setup. The Hardware Settings tab of the Hardware  
Setup dialog box is displayed.  
4. Click Add Hardware. The Add Hardware dialog box is displayed.  
Select EthernetBlaster and click Auto Detect.  
The server name list is automatically populated with the  
EthernetBlaster communications cable detected on your  
subnet if Auto Detect is selected. However, if the cable is  
not on your subnet, you must manually type the name or IP  
address of the EthernetBlaster cable in the Server Name  
field of the Add Hardware dialog box.  
If you are using a direct connection to your computer, type  
192.168.0.50 in the Server Name field.  
5. Type the server password in the Server password field (“password”  
is the factory default), and click OK.  
6. EthernetBlaster is now visible in the Available hardware items list  
of the Hardware Setup dialog box, as shown in Figure 1–10 below.  
Figure 1–10. Hardware Setup Dialog Box  
7. Click Close to close the Hardware Setup dialog box.  
1–14  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
 
About the EthernetBlaster Communications Cable  
8. In the Mode list, select the desired mode (Programmer window).  
Table 1–2 describes each mode.  
The EthernetBlaster communications cable supports the  
Joint Test Action Group (JTAG), Passive Serial  
Programming, and Active Serial modes.  
Table 1–2. Programming Modes  
Mode  
Mode Description  
Joint Test Action Group (JTAG) Programs or configures all Altera devices  
supported by the Quartus II software, excluding  
FLEX 6000 devices.  
In-Socket Programming  
Not supported by the EthernetBlaster cable.  
Passive Serial Programming  
Configures all Altera devices supported by the  
Quartus II software, excluding the following  
devices: MAX 3000 and MAX 7000 devices,  
advanced configuration devices, and serial  
configuration devices.  
Active Serial Programming  
Programs a single EPCS1, EPCS4, EPCS16,  
or EPCS64 serial configuration device.  
Removing the EthernetBlaster Hardware from the Quartus II  
Software  
Changes to the EthernetBlaster communications cable setup, including  
password change and IP addressing mode change, necessitate removal of  
the cable from the Quartus II Programmer Hardware setup on client  
systems, followed by adding the cable back into the Quartus II  
Programmer Hardware setup. To remove the EthernetBlaster  
communications cable from the Quartus II Programmer hardware setup,  
follow the instructions below.  
1. Start the Quartus II software.  
2. Choose Programmer (Tools menu).  
3. Click Hardware Setup. The Hardware Settings tab of the Hardware  
Setup dialog box is displayed.  
4. Click JTAG Settings. The JTAG Settings dialog box is displayed.  
Select the corresponding hostname or IP address of the  
EthernetBlaster hardware to remove. Click Remove Server.  
Altera Corporation  
December 2004  
1–15  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Cable Setup  
Quartus II Software” on page 1–13 for instructions to add  
the EthernetBlaster communications cable back into the  
Quartus II Programmer Hardware setup.  
For details about programming devices and creating secondary  
programming files, see the “Programming & Configuration” chapter of  
the Introduction to Quartus II Manual.  
For further information, see the Programming module of the Quartus II  
online tutorial.  
For further information, refer to the following topics in the Quartus II  
online Help:  
Changing the Hardware Setup  
Programmer Introduction  
Overview: Working with Chain Description Files  
Overview: Converting Programming Files  
1–16  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
Chapter 2. EthernetBlaster  
Communications Cable  
Administration  
This chapter describes how to administer your EthernetBlaster  
communications cable:  
Introduction  
Changing the Quartus® II Remote Connection Password  
Networking allows multiple users in both remote and local locations to  
use the EthernetBlaster communications cable, increasing the  
productivity in prototyping and debugging. However, because of this  
flexibility, it is necessary to limit and control user access using the  
provided password service in the EthernetBlaster communications cable  
setup.  
Managing  
Passwords  
The EthernetBlaster communications cable contains two types of  
passwords, an administrative password and a Quartus II remote  
connection password.  
The administrative password is the master password used to enter the  
EthernetBlaster administrative web page. If you know the administrative  
password you have full control of settings and the ability to modify both  
the administrative password and the Quartus II remote connection  
password.  
The Quartus II remote connection password enables clients to add the  
EthernetBlaster hardware to their Quartus II Programmer hardware  
setup. This password is used to control who has access to the  
EthernetBlaster communications cable. However, they do not have access  
to the EthernetBlaster administrative web page and cannot modify the  
settings or change passwords.  
Altera Corporation  
December 2004  
2–1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Managing Passwords  
When you change the Quartus II remote connection password,  
client systems using the EthernetBlaster communications cable  
must remove the hardware from their Quartus II Programmer  
hardware setup. See Chapter 1, “Removing the EthernetBlaster  
Hardware from the Quartus II Software Programmer Hardware  
Setup” for details. The hardware then needs to be added back  
into the Quartus II software. See Chapter 1, “Setting Up the  
EthernetBlaster Hardware in the Quartus II Software” for  
details.  
Changing the Administrative Password  
To change the administrative password, follow the directions below:  
1. Open and log into the EthernetBlaster administrative web page in  
your browser.  
See Chapter 1, “Setup,” for instructions on accessing the  
administrative web page using your specific connection.  
2. Click the Change Admin Password tab. See Figure 2–1 below.  
Figure 2–1. Change Admin Password Page  
3. Enter the new administrative password in the New Password field  
and again in the Confirm New Password field. Click Apply.  
2–2  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
   
EthernetBlaster Communications Cable Administration  
The new password takes effect immediately when logging back into  
the administrative web page.  
The EthernetBlaster communications cable does not restart  
when the administrative password is reset.  
Changing the Quartus II Remote Connection Password  
To change the Quartus II remote connection password, follow the  
directions below:  
1. Open and log into the EthernetBlaster administrative web page in  
your browser.  
See Chapter 1, “Setup,” for instructions on accessing the  
administrative web page using your specific connection.  
2. Click the Change EthernetBlaster Settings tab. See Figure 2–2  
below.  
Figure 2–2. Change Quartus II Remote Connection Password Page  
3. Enter the new Quartus II remote connection password in the New  
Password field and again in the Confirm New Password field. Click  
Apply.  
Altera Corporation  
December 2004  
2–3  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Resetting the Hardware  
The EthernetBlaster communications cable restarts. When the status  
LED emits a steady green light, the EthernetBlaster has successfully  
reset and the new password is effective.  
The EthernetBlaster communications cable reset button is located on the  
Ethernet port side of the hardware. See Figure 2–3.  
Resetting the  
Hardware  
Figure 2–3. Machine Reset button  
DC12V  
ETHERNET  
Machine Reset  
Paper clip  
Use a small pointed object such as a paper clip to press the machine reset  
button to restart and reset all values to the default factory settings. See  
Table 2–1 for a list of factory default settings.  
Table 2–1. Default Factory Settings  
Setting  
Value  
Connection Type  
Host name  
DHCP  
acebXXXX (1)  
Clear  
Domain name  
Timeserver Name/IP  
IP Address  
Clear  
192.168.0.50  
255.255.255.0  
192.168.0.1  
0.0.0.0  
Subnet Mask  
Default Router  
DNS Server 1  
DNS Server 2  
0.0.0.0  
Administrative Password  
password  
password  
Quartus II Remote Connection Password  
Note:  
(1) The host name and MAC address are located on the label on the base of  
your cable. The last 4 digits of the MAC address represent the “XXXX” in the  
host name.  
2–4  
Altera Corporation  
EthernetBlaster Communications Cable User Guide  
December 2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EthernetBlaster Communications Cable Administration  
When the EthernetBlaster is reset, existing client systems using  
passwords other than the factory default must remove the  
EthernetBlaster hardware from their Quartus II Programmer  
Hardware Setup. See Chapter 1, “Removing the EthernetBlaster  
Hardware from the Quartus II Software Programmer Hardware  
Setup” for instructions on removal of the EthernetBlaster  
hardware. The hardware then needs to be added back into the  
Quartus II software. See Chapter 1, “Setting Up the  
EthernetBlaster Hardware in the Quartus II Software” for  
details.  
The EthernetBlaster communications cable has been designed to enable  
remote firmware upgrade when a new version of firmware is available  
from Altera Corporation. New firmware may contain enhanced features,  
better performance, or bug fixes.  
Firmware  
Upgrade  
Do not turn off the EthernetBlaster communications cable power  
when performing the firmware upgrade or severe damage will  
occur.  
Firmware upgrades are included in Quartus II releases. Firmware  
upgrades and GPL source code updates are also available on the Altera  
website. For details, go to www.altera.com/ethernetblaster.  
To upgrade the EthernetBlaster communications firmware, follow the  
directions below.  
1. Open and log into the EthernetBlaster Configuration  
administrative web page in your browser.  
See Chapter 1, “Setup” for instructions on accessing the  
administrative web page using your specific connection.  
2. Click the Upgrade Firmware tab. See Figure 2–4 on page 2–6.  
Altera Corporation  
December 2004  
2–5  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Firmware Upgrade  
Figure 2–4. Upgrade Firmware Page  
3. Click Browse and then locate and select the firmware file on your  
system. Click Apply.  
The EthernetBlaster communications cable restarts automatically  
after the firmware has been successfully upgraded. When the status  
LED returns to a steady green state, the EthernetBlaster  
communications cable has restarted successfully.  
2–6  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
 
Chapter 3. EthernetBlaster  
Communications Cable  
Specifications  
This chapter provides comprehensive information about the  
EthernetBlaster communications cable, including the following:  
Overview  
EthernetBlaster hardware connections  
Operating conditions  
The EthernetBlaster cable connects to an Ethernet cable with a RJ45 jack  
to a 10/100Base-T Ethernet hub/switch (via a straight 8-wire data cable)  
or a 10/100Base-T Ethernet port of a PC (via a crossover data cable).  
Depending on your connection (remote or direct), data is downloaded  
through the EthernetBlaster communications cable to the circuit board  
via the connections discussed in this section.  
EthernetBlaster  
Hardware  
Connections  
Voltage Requirements  
The EthernetBlaster VCC(TARGET) pin must be connected to a specific  
voltage for the device being programmed. Connect pull-up resistors to  
the same power supply as the EthernetBlaster VCC(TARGET). See Table 3–1.  
Table 3–1. EthernetBlaster VCC(TARGET) Pin Voltage Requirements  
Device Family  
EthernetBlaster VCC Voltage Required  
MAX® II devices  
As specified by VCCIO of Bank 1  
MAX 7000S devices  
5 V  
MAX 7000AE and MAX 3000A devices  
MAX 7000B devices  
3.3 V  
2.5 V  
Stratix® II, Stratix GX, and Stratix devices  
As specified by VCCSEL  
CycloneII, Cyclone, APEXII, APEX 20K, and Mercurydevices  
As specified by VCCIO  
5 V  
FLEX 10K®, FLEX® 8000, and FLEX 6000 devices  
FLEX 10KE devices  
2.5 V  
FLEX 10KA and FLEX 6000A devices  
EPC2 devices  
3.3 V  
5 V or 3.3 V  
3.3 V  
EPC4, EPC8, and EPC16 devices  
EPCS1, EPCS4, EPCS16, and EPCS64 devices  
3.3 V  
Altera Corporation  
December 2004  
3–1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
EthernetBlaster Hardware Connections  
EthernetBlaster Ethernet Jack Connection  
The Ethernet cable Ethernet jack connects to the EthernetBlaster  
communications cable Ethernet port. The Ethernet jack pin number  
designations are shown in Figure 3–1 below.  
Figure 3–1. Ethernet Jack Pin Number Designations  
Pin Signal  
1
2
3
4
5
6
7
8
TxData +  
TxData  
RecvData +  
-
-
-
8
1
RecvData  
-
-
-
EthernetBlaster Plug Connection  
The 10-pin female plug connects to a 10-pin male header on the circuit  
board containing the target device. See Figure 3–2.  
Figure 3–2. EthernetBlaseter 10-Pin Female Target-Side Plug Dimensions  
0.425 Typ.  
10  
9
8
7
6
5
4
3
2
1
0.250 Typ.  
0.100 Sq.  
0.025 Sq.  
0.700 Typ.  
Dimensions are shown in inches. Spacing between pin centers is 0.1 inches.  
3–2  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
       
EthernetBlaster Communications Cable User Guide  
Table 3–2 identifies the 10-pin female plug pin names and the  
corresponding programming mode.  
Table 3–2. EthernetBlaster Female Plug Signal Names & Programming Modes  
AS Mode  
Description  
PS Mode  
JTAG Mode  
Signal Name Description  
TCK  
Pin  
Signal Name  
DCLK  
Signal Name  
DCLK  
Description  
1
2
3
Clock signal  
Clock signal  
Clock signal  
Signal ground  
Signal ground  
Signal ground  
GND  
GND  
GND  
TDO  
Configuration  
done  
Configuration  
done  
Data from  
device  
CONF_DONE  
CONF_DONE  
4
5
6
7
8
Target power  
supply  
Target power  
supply  
Target power  
supply  
VCC(TARGET)  
nCONFIG  
nCE  
VCC(TARGET)  
VCC(TARGET)  
Configuration  
control  
Configuration  
control  
JTAG state  
machine control  
nCONFIG  
TMS  
Cyclone chip  
enable  
No connect  
No connect  
No connect  
No connect  
nSTATUS  
Active serial data  
out  
Configuration  
status  
DATAOUT  
nCS  
Serial  
No connect  
configuration  
device chip select  
9
Active serial data  
in  
Data to device  
Signal ground  
Data to device  
Signal ground  
ASDI  
GND  
DATA0  
GND  
TDI  
GND  
10  
Signal ground  
The circuit board must supply VCC(TARGET) and ground to the  
EthernetBlaster cable for the I/O drivers.  
Circuit Board Header Connection  
The circuit board's 10-pin male header, which connects to the  
EthernetBlaster cable's 10-pin female plug, has two rows of five pins.  
These pins are connected to the device’s programming or configuration  
pins. Figure 3–3 on page 4 shows the dimensions of a typical 10-pin male  
header.  
Altera Corporation  
December 2004  
3–3  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operating Conditions  
Figure 3–3. 10-Pin Male Header Dimensions  
Top View  
Side View  
0.100  
0.025 Sq  
.
0.100  
0.235  
Dimensions are shown in inches.  
Tables 3–3 through 3–5 summarize the maximum ratings, recommended  
operating conditions, and DC operating conditions for the cable.  
Operating  
Conditions  
Table 3–3. EthernetBlaster Cable Absolute Maximum Ratings  
Symbol  
Parameter  
Conditions  
With respect to ground  
With respect to ground  
TDO or dataout  
Min  
–0.3  
Max Unit  
VCC(TARGET) Target supply voltage  
5.5  
V
VCC(SYS)  
System supply voltage  
Input current  
–0.5  
14.0  
10.0  
10.0  
V
II  
–10.0  
–10.0  
mA  
mA  
Io  
Output current  
TCK, TMS, TDI, nCS, nCE  
Table 3–4. EthernetBlaster Cable Recommended Operating Conditions  
Symbol Parameter Conditions  
Min  
Max Unit  
VCC(TARGET) Target supply voltage, 5.0-V operation  
Target supply voltage, 3.3-V operation  
Target supply voltage, 2.5-V operation  
Target supply voltage, 1.8-V operation  
Target supply voltage, 1.5-V operation  
4.75  
3.0  
5.25  
3.6  
V
V
V
V
V
2.375 2.625  
1.71  
1.43  
1.89  
1.57  
3–4  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altera Corporation  
December 2004  
     
EthernetBlaster Communications Cable User Guide  
Table 3–5. EthernetBlaster Cable DC Operating Conditions  
Symbol  
Parameter  
High-level input voltage  
High-level input voltage  
Low-level input voltage  
Conditions  
Min  
VCC(TARGET) –0.2  
3.1  
Max Unit  
VCC(TARGET) < or = 3.3 V  
VCC(TARGET) > 3.3 V  
VIH  
V
V
VIL  
0.15  
V
V
V
V
V
V
V
V
V
V
V
5.0-V high-level output voltage VCC(TARGET) = 4.5 V, IOH = 20 µA  
3.3-V high-level output voltage VCC(TARGET) = 3.0 V, IOH = 20 µA  
2.5-V high-level output voltage VCC(TARGET) = 2.375 V, IOH = 20 µA  
1.8-V high-level output voltage VCC(TARGET) = 1.71 V, IOH = 20 µA  
1.5-V high-level output voltage VCC(TARGET) = 1.43 V, IOH = 20 µA  
VOH  
3.3  
2.0  
1.6  
1.15  
0.95  
5.0-V low-level output voltage  
3.3-V low-level output voltage  
2.5-V low-level output voltage  
1.8-V low-level output voltage  
1.5-V low-level output voltage  
Operating current (No Load)  
VCC(TARGET) = 5.5 V, IOL = 1 mA  
VCC(TARGET) = 3.6 V, IOL = 1 mA  
VCC(TARGET) = 2.625 V, IOL = 1 mA  
VCC(TARGET) = 1.89 V, IOL = 1 mA  
VCC(TARGET) = 1.57 V, IOL = 1 mA  
Typical ICC(SYS) = 350mA @ VCC(SYS) = 12V  
VOL  
0.4  
0.4  
0.4  
0.4  
0.4  
ICC(SYS)  
700 mA  
For more information on configuration and in-system programmability  
(ISP), see the following sources:  
References  
“Configuring Cyclone FPGAs” chapter in the Cyclone Device  
Handbook  
“Configuring Cyclone II Devices” chapter in the Cyclone II Device  
Handbook  
Configuring Stratix II Devices” chapter in Volume 2 of the Stratix II  
Device Handbook  
Configuring Stratix and Stratix GX Devices” chapter in the Stratix  
Device Handbook  
“In-System Programmability Guidelines for MAX II Devices”  
chapter in the MAX II Device Handbook  
Serial Configuration Devices Data Sheet  
“Programming & Configuration” chapter in the Introduction to  
Quartus II manual  
The Programming module of the Quartus II online tutorial  
Refer to the following glossary definitions in Quartus II Help:  
“EthernetBlaster Cable” (general description)  
“Configuration scheme” (general description)  
“Programming files” (general description)  
Altera Corporation  
December 2004  
3–5  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Revision History  
Refer to the following procedures in Quartus II Help:  
Programming a Single Device or Multiple Devices in JTAG or  
Passive Serial Mode  
Programming a Single Device in Active Serial Programming  
Mode  
Selecting the Communications Cable for the SignalTap II Logic  
Analyzer  
Refer to the following introduction and overview topics in  
Quartus® II Help:  
Programmer Introduction  
Overview: Working with Chain Description Files  
Overview: Converting Programming Files  
The table below shows the revision history of this user guide.  
Revision History  
Chapter  
Date  
Version  
Changes Made  
All  
December 2004 1.0  
Initial release  
For the most up-to-date information about Altera products, go to the  
Altera world-wide web site at www.altera.com. For technical support on  
this product, go to www.altera.com/mysupport. For additional  
information about Altera products, consult the sources shown below.  
How to Contact  
Altera  
Information Type  
USA & Canada  
All Other Locations  
Technical support  
(800) 800-EPLD (3753)  
(408) 544-7000 (1)  
(7:00 a.m. to 5:00 p.m. Pacific Time)  
(7:00 a.m. to 5:00 p.m. Pacific Time)  
Product literature  
Altera literature services  
Non-technical customer  
service  
(800) 767-3753  
(7:00 a.m. to 5:00 p.m. Pacific Time)  
(408) 544-7000  
(7:00 a.m. to 5:00 p.m. Pacific Time)  
FTP site  
Note:  
(1) You can also contact your local Altera sales office or sales representative.  
3–6  
Altera Corporation  
December 2004  
EthernetBlaster Communications Cable User Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     

Shindaiwa Brush Cutter 81644 User Manual
Shure Musical Instrument ULX User Manual
Sony Clock Radio ICF C1T User Manual
Sony Home Theater System VGX XL2 User Manual
Sony MP3 Player VGF WA1 User Manual
Sony Security Camera SNC CH110 User Manual
SOYO Computer Drive Lite Motherboard User Manual
Stanley Black Decker Cordless Saw CR27 User Manual
Suncast Outdoor Storage BMS7700 User Manual
Suzuki Automobile XL7 User Manual