Server Technology Switch C 16HF1 C20 User Manual

Rack-Mount Fail-Safe  
Transfer Switch  
Installation and Operations Manual  
C-8HFx  
C-16HFx  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1: Introduction  
Quick Start Guide  
The following instructions will help you quickly install and configure your Rack-Mount Fail-Safe  
Transfer Switch for use on your network. For detailed information on each step, go to the page number  
listed to the right.  
1. Mount the Rack-Mount Fail-Safe Transfer Switch ....................................................................7  
2. Optimize the transfer thresholds.................................................................................................7  
3. Connect to the power sources.....................................................................................................7  
4. Connect the devices to the Fail-Safe Transfer Switch................................................................7  
Technical Support  
Experience Server Technology's FREE SMARTER Technical Support - Learn more...  
Server Technology understands that there are often questions when installing and/or using a new  
product. Free Technical Support is provided from 6:00 AM to 7:00 PM, Monday-Friday, Pacific Time.  
Server Technology, Inc.  
1040 Sandhill Drive  
Reno, Nevada 89521 USA  
Tel: 775.284.2000  
Fax: 775.284.2065  
4 Introduction  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Equipment Overview  
1. The Voltage Selector switch configures the Rack-Mount Fail-Safe Transfer Switch for the installed  
operational voltage.  
NOTE: This configures the brownout/over-voltage switching points.  
2. The power inlets connect the Rack-Mount Fail-Safe Transfer Switch to the electrical power  
sources.  
3. LEDs display the input feeds power status.  
1
2
3
Figure 1. Sentry Rack-Mount Fail-Safe Transfer Switch Views  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Introduction 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2: Installation  
Before installing your Rack-Mount Fail-Safe Transfer Switch, refer to the following lists to ensure that  
you have all the items shipped with the unit as well as all other items required for proper installation.  
Standard Accessories  
Mounting hardware: Two removable flanges with M4 screws.  
Outlet retention clips (208-240V models).  
Additional items for Cx-xxx-C20 models:  
Separate power input cords.  
Power input retention bracket hardware (may be installed):  
Four removable T-brackets with four 40mm screws.  
Additional Required Items  
Flathead and Phillips screwdrivers  
Screws, washers and nuts to attach the CDU to your rack  
Safety Precautions  
This section contains important safety and regulatory information that should be reviewed before  
installing and using the Sentry Rack-Mount Fail-Safe Transfer Switch. For input and output current  
Only for installation and use in a  
Service Access Location in  
accordance with the following  
installation and use instructions.  
Destiné à l'installation et l'utilisation  
dans le cadre de Service Access  
Location selon les instructions  
d'installation et d'utilisation.  
Nur für Installation und Gebrauch an  
Anschlusszugriffspunkten gemäß der  
folgenden Installations- und  
Gebrauchsanweisungen.  
This equipment is designed to be  
installed on a dedicated circuit.  
Cet équipement est conçu à être installé  
sur un circuit spécialisé.  
Diese Ausrüstung ist zur Installation in  
einem festen Stromkreis vorgesehen.  
Dedicated circuit must have circuit  
breaker or fuse protection.  
CDUs have been designed without  
a master circuit breaker or fuse to  
avoid becoming a single point of  
failure. It is the customer’s  
responsibility to provide adequate  
protection for the dedicated power  
circuit. Protection of capacity equal  
to the current rating of the CDU  
must be provided and must meet  
all applicable codes and  
regulations. In North American,  
protection must have a 10,000A  
interrupt capacity.  
Le circuit spécialisé doit avoir un  
disjoncteur ou une protection de  
fusible. CDUs ont été conçus sans  
disjoncteur général ni fusible pour éviter  
que cela devient un seul endroit de  
panne. C’est la responsabilité du client  
de fournir une protection adéquate pour  
le circuit-alimentation spécialisé.  
Protection de capacité équivalant à la  
puissance de l'équipement, et  
Der feste Stromkreis muss mit einem  
Schutzschalter oder einem  
Sicherungsschutz versehen sein.  
CDUs verfügt über keinen  
Hauptschutzschalter bzw. über keine  
Sicherung, damit kein einzelner  
Fehlerpunkt entstehen kann. Der  
Kunde ist dafür verantwortlich, den  
Stromkreis sachgemäß zu schützen.  
Der Kapazitätsschutz entspricht der  
aktuellen Stromstärke der Geräte und  
muss alle relevanten Codes und  
Bestimmungen erfüllen. Für Installation  
in Nordamerika müssen Ausschalter  
bzw. Sicherung über 10.000 A  
respectant tous les codes et normes  
applicables. Les disjoncteurs ou fusibles  
destinés à l'installation en Amérique du  
Nord doivent avoir une capacité  
d'interruption de 10.000 A.  
Unterbrechungskapazität verfügen.  
The plug on the power supply cord  
shall be installed near the  
equipment and shall be easily  
accessible.  
La prise sur le cordon d’alimentation  
sera installée près de l’équipement et  
sera facilement disponible.  
Der Stecker des Netzkabels muss in  
der Nähe der Ausrüstung installiert  
werden und leicht zugänglich sein.  
Always disconnect the power  
supply cords before opening to  
avoid electrical shock.  
Toujours déconnecter le cordon  
d’alimentation avant d’ouvrir pour éviter  
un choque électrique.  
Ziehen Sie vor dem Öffnen immer das  
Netzkabel heraus, um die Gefahr eines  
elektrischen Schlags zu vermeiden.  
WARNING! High leakage current!  
Earth connection is essential  
before connecting supply!  
ATTENTION ! Haut fuite très possible !  
Une connection de masse est  
essentielle avant de connecter  
l’alimentation !  
ACHTUNG! Hoher Ableitstrom! Ein  
Erdungsanschluss ist vor dem  
Einschalten der Stromzufuhr  
erforderlich!  
WARNING! Cx-xxE-x units  
Double Pole/Neutral Fusing  
ATTENTION! Les unités Cx-xxE-x  
Double Pôle/Fusible sur le Neutre  
ACHTUNG!: Cx-xxE-x  
Zweipolige bzw. Neutralleiter-Sicherung  
6 Installation  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the Power Input Retention Bracket  
For units with a total maximum output <30A, it may be  
necessary to install the power input retention bracket prior to  
mounting the unit within the rack.  
To install the power input retention bracket:  
1. Remove the two screws attaching the IEC 60320 C19 inlet  
to the enclosure.  
2. Assemble and attach the retention bracket to the enclosure  
as shown.  
Figure 2.1 Retention Bracket assembly  
Mounting  
1. Select the appropriate bracket mounting points for  
proper mounting depth within the rack.  
2. Attach the brackets to these mounting points with two  
screws for each bracket.  
3. Install the enclosure into your rack, using the slots in  
each bracket. The slots allow about ¼ inch of  
horizontal adaptability to align with the mounting  
holes of your rack.  
NOTE: A mounting bracket kit for 23” wide racks or cabinets is  
available. Contact your Server Technology Sales Representative for  
more information.  
Figure 2. Mounting  
Optimizing the Transfer Thresholds  
The Voltage Selector switch is used to optimize the transfer threshold by configuring the Transfer  
Switch for the nominal operational voltage of the installation. The Transfer Switch uses this setting to  
calculate the brownout and over-voltage threshold (± 13% ).  
To optimize the transfer threshold:  
Select the voltage setting that most closely matches the nominal operating voltage of the power sources.  
Connecting to the Power Source  
To attach a power cord to the unit:  
1. Plug the female end of the power cord firmly into its connector at the base.  
2. Use a screwdriver to tighten the two screws on the retention bracket.  
To connect to the power source:  
Plug the male end of the power cord into the AC power source.  
Connecting Devices  
1. Keep the device’s on/off switch in the off position until after it is plugged into the outlet.  
2. Connect devices to the CDU outlets.  
NOTE: Server Technology recommends even distribution of attached devices across all available outlets to avoid  
exceeding the outlet, branch or phase limitations. See Power Ratings on page 9 for more information.  
Always disconnect ALL power supply cords before opening to avoid electrical shock.  
Afin d’éviter les chocs électriques, débranchez TOUTES les cables électrique avant d’ouvrir.  
Immer ALLE Netzleitungen auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Installation 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Chapter 3: Operations  
Modes of Operation  
The Sentry Rack-Mount Fail-Safe Transfer Switch is designed to operate in the following modes:  
Normal  
Infeed A provides power to branches A1 & A2 and Infeed B provides power to branches B1 & B2.  
Each infeed is monitored individually for voltage and current.  
Input Failure  
The equipment powered by the failed input is transferred to the remaining input. The input current  
LED display of the failed input will be blank and the remaining display will report the total current  
load for the unit.  
Recovery from Input Failure  
When voltage is restored to the failed input and remains within ±7% of nominal for 2 seconds, the  
equipment normally supported by that input is transferred back returning the Sentry to a ‘Normal’  
mode with the input current LED displays reporting the total current load for each respective  
infeed.  
Brownout/Over-Voltage  
When an input’s voltage varies from its nominal by ±13% or more, the equipment powered by that  
input is transferred to the remaining input. The input current LED display of the input in the  
brownout/over-voltage state will be blank and the remaining display will report the total current  
load for the unit.  
Nominal Voltage*  
Brownout  
Recovery Voltage  
Over-Voltage  
100V  
110V  
115V  
120V  
208V  
220V  
230V  
240V  
87.0V  
95.7V  
93.0V  
102.3V  
106.9V  
111.6V  
193.4V  
204.6V  
213.9V  
223.2V  
107.0V  
117.7V  
123.0V  
128.4V  
222.6V  
235.4V  
246.1V  
256.8V  
113.0V  
124.3V  
129.9V  
135.6V  
235.0V  
248.6V  
259.9V  
271.2V  
100.0V  
104.4V  
181.0V  
191.4V  
200.1V  
208.8V  
* Nominal operating voltage is configured by the Voltage Selector Switch.  
Recovery from Brownout/Over-Voltage  
When the input’s voltage returns to and remains within ±7% of nominal for 2 seconds, the  
equipment normally supported by that input is transferred back returning the Sentry to a ‘Normal’  
mode input current LED displays reporting the total current load for each respective infeed.  
Critical Brownout  
A critical brownout is when an input’s voltage drops below its nominal by -25%.  
When an input is already in a brownout/over-voltage state AND the remaining input  
experiences a critical brownout, ALL equipment will be transferred to the input only  
experiencing a brownout/over-voltage.  
When an input has already failed AND the remaining input experiences a critical  
brownout, ALL outlets will turn off.  
Recovery from Critical Brownout  
When the input’s voltage returns to and remains within ±7% of nominal for 2 seconds, the  
equipment normally supported by that input is transferred back.  
8 Operations  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 4: Appendices  
Appendix A: Technical Specifications  
Domestic Models  
Model  
Rated Voltage  
Input Cordset and Plug (10’)  
Outlets  
C-8HF2-C203  
C-8HF2-L303  
C-16HF1-C20  
C-16HF1-L30  
C-16HF2-C20  
C-16HF2-L30  
208-240V, 50/60Hz  
208-240V, 50/60Hz  
100-120V, 50/60Hz  
100-120V, 50/60Hz  
208-240V, 50/60Hz  
208-240V, 50/60Hz  
IEC 60320 C201  
8 IEC 60320/C19  
8 IEC 60320/C19  
16 NEMA 5-20R  
16 NEMA 5-20R  
16 IEC 60320/C13  
16 IEC 60320/C13  
2 x NEMA L6-30P, 30A/208V Locking  
IEC 60320 C201  
2 x NEMA L5-30P, 30A/120V Locking  
IEC 60320 C201  
2 x NEMA L6-30P, 30A/208V Locking  
International Models  
Model  
Rated Voltage  
Input Cordset and Plug (10’)  
Outlets  
C-8HFE-C203  
C-8HFE-P323  
C-16HFE-C20  
C-16HFE-P32  
230V, 50/60Hz  
230V, 50/60Hz  
230V, 50/60Hz  
230V, 50/60Hz  
IEC 60320 C201  
8 IEC 60320/C19  
8 IEC 60320/C19  
16 IEC 60320/C13  
16 IEC 60320/C13  
2 x IEC 60309, 32A 3-pin 6Hr Blue  
IEC 60320 C201  
2 x IEC 60309, 32A 3-pin 6Hr Blue  
1 Input cordset selected at time of purchase  
Power Ratings  
Input Current Ratings1  
L’indice du courant d’entrée  
Eingangsstromstärke  
Output Current Ratings  
L’indice du courant de sortie  
Ausgangsstromstärke  
Model  
Modele  
Modell  
Voltage  
Tension  
Spannung  
100-120V  
50/60Hz  
100-120V  
50/60Hz  
208-240V  
50/60Hz  
208-240V  
50/60Hz  
208-240V  
50/60Hz  
208-240V  
50/60Hz  
230V  
50/60Hz  
230V  
50/60Hz  
230V  
50/60Hz  
230V  
50/60Hz  
Current  
Courrant  
Strom  
A: 16  
B: 16  
A: 24  
B: 24  
A: 16  
B: 16  
A: 24  
B: 24  
A: 16  
B: 16  
A: 24  
B: 24  
A: 16  
B: 16  
A: 32  
B: 32  
A: 16  
B: 16  
A: 32  
B: 32  
Voltage  
Tension  
Spannung  
100-120V  
50/60Hz  
100-120V  
50/60Hz  
208-240V  
60Hz  
208-240V  
60Hz  
208-240V  
60Hz  
208-240V  
60Hz  
230V  
50/60Hz  
230V  
50/60Hz  
230V  
50/60Hz  
230V  
50/60Hz  
Outlet  
Prise  
Branch Circuit  
Circuit de la Branche  
Phase  
Total  
Total  
Anschlussstelle  
Zweigstromkreis  
Insgesamt  
C-16HF1-C20  
C-16HF1-L30  
C-8HF2-C203  
C-8HF2-L303  
C-16HF2-C20  
C-16HF2-L30  
C-8HFE-C203  
C-8HFE-P323  
C-16HFE-C20  
C-16HFE-P32  
16  
16  
16  
24  
16  
24  
16  
24  
16  
32  
16  
32  
16  
16  
16  
12  
12  
16  
16  
10  
10  
16  
16  
16  
16  
16  
16  
20  
16  
20  
1 All current ratings are in amperes. Tous les indices de courant sont en ampères. Alle Angaben der Stromstärke erfolgen in Ampere.  
Physical Specifications  
Operating  
Storage  
Temperature  
32° to 104° F (0° to 40° C)  
-40° to 185° F (-40° to 85° C)  
0 to 50,000 ft (0 to 15000m)  
10 to 90%, non-condensing  
Elevation(above MSL) 0 to 10,000 ft (0 to 3000m)  
Relative Humidity  
10 to 90%, non-condensing  
Dimensions (H x W x D)  
Weight  
C-xHF  
3.5 x 17.0 x 14.0 in.  
(90 x 437 x 356 mm)  
20.7 lbs (9.4 kg)  
Transfer Rate  
Power transfer 18 milliseconds.  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Appendices 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Regulatory Compliance  
Product Safety  
Units have been safety tested and certified to the following standards:  
USA/Canada  
European Union EN60950-1:2001  
UL 60950:2003 and CAN/CSA 22.2 No. 60950-1-03  
This product is also designed for Norwegian IT power system with phase-to phase voltage 230V.  
USA Notification  
Note: This equipment has been tested and found to comply with the limits for a Class A digital device,  
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection  
against harmful interference when the equipment is operated in a commercial environment. This  
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in  
accordance with the instruction manual, may cause harmful interference to radio communications.  
Operation of this equipment in a residential area is likely to cause harmful interference in which case  
the user will be required to correct the interference at the user’s own expense.  
Modifications not expressly approved by the manufacturer could void the user's authority to operated  
the equipment under FCC rules.  
Canadian Notification  
This Class A digital apparatus complies meets all requirements of the Canadian Interference-Causing  
Equipment Regulations.  
Cet appareil numérique de la classe A respecte toutes les exigencies du Règlement sur le matériel  
brouilleur du Canada.  
European Union Notification  
Products with the CE Marking comply with both the EMC Directive (89/336/EEC) and the Low  
Voltage Directive (73/23/EEC) issued by the Commission of the European Community.  
Compliance with these directives implies conformity to the following European Norms:  
EN55022  
EN55024  
EN60950-1 Product Safety  
Electromagnetic Interference  
Electromagnetic Immunity  
EN61000-3 Harmonics and Flicker  
Products with the following mark comply with the RoHS Directive  
(2002/95/EC) issued by the Commission of the European Community.  
Japanese Notification  
この装置は、情報処理装置等電波障害自主規制協議会(VCCI)の基準に基づくクラ  
A情報技術装置です。この装置を家庭環境で使用すると電波妨害を引き起こすことが  
あります。この場合には使用者が適切な対策を講ずるよう要求されることがあります。  
Recycling  
Server Technology Inc. encourages the recycling of its products. Disposal facilities,  
environmental conditions and regulations vary across local, state and country jurisdictions, so  
Server Technology encourages consultation with qualified professional and applicable  
regulations and authorities within your region to ensure proper disposal.  
Waste Electrical and Electronic Equipment (WEEE)  
In the European Union, this label indicates that this product should not be disposed of with  
household waste. It should be deposited at an appropriate facility to enable recovery and  
recycling.  
For information on how to recycle this product responsibly in your country, please visit:  
10 Appendices  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B: Warranty, Product Registration and Support  
Warranty  
For Server Technology Warranty information, please see our website.  
Product Registration  
Registration is your key to special offers and services reserved for Registered Users.  
Excellent Technical Support Services  
Special Update and Upgrade Programs  
Warranty Protection  
Extended Warranty Service  
New Product Information  
Technical Support  
Experience Server Technology's FREE SMARTER Technical Support - Learn more...  
Server Technology understands that there are often questions when installing and/or using a new  
product. Free Technical Support is provided from 6:00 AM to 7:00 PM, Monday-Friday, Pacific Time.  
Server Technology, Inc.  
1040 Sandhill Drive  
Reno, Nevada 89521 USA  
Tel: 775.284.2000  
Fax: 775.284.2065  
Return Merchandise Authorization  
If you have a unit that is not functioning properly and is in need of technical assistance or repair:  
Please review Server Technology’s Return Merchandise Authorization process on our website.  
Rack-Mount Fail-safe Transfer Switch  
Installation and Operations Manual  
Appendices 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Server Technology  
HEADQUARTERS – NORTH AMERICA  
Server Technology, Inc.  
1040 Sandhill Drive  
EMEA  
APAC  
Server Technology Intl  
Sienna Court  
Server Technology, Inc.  
Singapore  
Reno, NV 89521  
United States  
The Broadway  
Maidenhead  
Berkshire  
SL6 1NJ  
United Kingdom  
+44 (0) 1628 509503 Tel  
+44 (0) 1628 509100 Fax  
+65 (0) 6829 7008 Tel  
+65 (0) 6234 4574 Fax  
+1.775.284.2000 Tel  
+1.775.284.2065 Fax  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Shop Vac Vacuum Cleaner 86L650 User Manual
Shure Microphone BG 10 User Manual
Sony Car Stereo System CDX 656X User Manual
Sony Clock Radio ICF C212 User Manual
Sony Computer Monitor BVM L170 User Manual
Sony Digital Camera DSC F505V User Manual
Sony Speaker XS V1650G User Manual
SoundMax Car Stereo System SM CDM1040 User Manual
Star Manufacturing Oven UM1833A User Manual
System Sensor Smoke Alarm 24TSRB User Manual