Installation Manual
Cooling Solutions
EcoBreeze™ System
ACECFR20101SE, ACECFR20200SE,
ACECFR20201SE, ACECFR40101SE,
ACECFR40200SE, ACECFR40201SE
990-3976D-001
Publication Date: June 2014
L
SP
LW
L
S
L
LW
I
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Inspecting the Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Other components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Remote display interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Refrigeration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Service access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Lifting and Rigging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
i
Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
ii
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
Safety
Read and adhere to the following important safety considerations when working with this
cooling unit.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work must be performed by licensed electricians. Practice Lockout/Tagout procedures. Do
not wear jewelry when working with electrical equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD FROM MOVING PARTS
Keep hands, clothing, and jewelry away from moving parts. Check the equipment for
foreign objects before closing the doors and starting the equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
DAMAGE TO EQUIPMENT OR PERSONNEL
The equipment is heavy and can easily be tipped. For safety purposes, adequate
personnel must be present when moving this equipment.
Failure to follow these instructions can result in death, injury, or equipment
damage.
CAUTION
HAZARD TO EQUIPMENT OR PERSONNEL
All work must be performed by Schneider Electric authorized personnel.
Failure to follow these instructions can result in injury or equipment damage.
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
1
Inspecting the Equipment
Inspect for missing components. All shipped loose components are identified by part number
and description on the bill of lading. Ensure each item is present before accepting delivery of
the unit.
Filing a claim. If damage has occurred, or if shipped loose parts are missing, report it
immediately to the delivering carrier and note the problem on the receiving copy of the bill of
lading. Failure to do so will result in replacement parts and repairs being billed to the customer.
In case of shipping damage, do not operate the equipment. Keep all packaging for inspection
by the shipping company and contact Schneider Electric.
Storing the equipment before installation
WARNING
DAMAGE TO EQUIPMENT OR PERSONNEL
• Do not remove tension rods until the EcoBreeze™ Frame is placed and secured on
its supports.
• Move the EcoBreeze Frame directly from the truck to its permanent foundation or
supports. If it must be stored temporarily, it must be placed on a flat and level
surface to avoid damage.
• Leave the protective plastic wrap in place until you are prepared to install the
equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Heavy: Ensure the lifting equipment has sufficient capacity for the load.
The recommended tools for moving the equipment include the following:
Crane
(Frame,
ductwork)
2
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Model Identification
Model identification label location
Frames
SKU
Description
ACECFR20101SEn* 6 m (20 ft) ISO Frame 400/3/50
ACECFR20200SEn* 6 m (20 ft) ISO Frame 480/3/60
ACECFR20201SEn* 6 m (20 ft) ISO Frame 600/3/60
ACECFR40101SEn* 12 m (40 ft) ISO Frame 400/3/50
ACECFR40200SEn* 12 m (40 ft) ISO Frame 480/3/60
ACECFR40201SEn* 12 m (40 ft) ISO Frame 600/3/60
*Where n is the number of Modules populating the Frame upon order.
Modules
SKU
Description
ACEC101SE
ACEC200SE
ACEC201SE
EcoBreeze Module 400/3/50
EcoBreeze Module 480/3/60
EcoBreeze Module 600/3/60
Other components
SKU
Description
ACECINS100SE
ACECCP100SE
ACECSJ100SE
Frame install kit
EcoBreeze remote interface panel
EcoBreeze screw-jack assembly
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Access Door and Panel Operation
Module access doors and panels have latches with a locking mechanism. Secondary door
latches are provided on doors on compartments that have positive air pressure to prevent the
doors from opening quickly if a door is opened while the unit is in operation.
WARNING
HAZARD OF ELECTRIC SHOCK
To avoid possible personal injury or death, re-engage the access door locking mechanism
after access to a compartment for inspection or service requirements.
Failure to follow these instructions can result in death or serious injury.
Frame access panels and the main power enclosure have locking latches that open with a key.
4
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Component Identification
COIL
ACCESS
Y
SUPPL
BLOWER
ACCESS
C
R
I
C
C
C
LR
c
Quantity Quantity
20 ft 40 ft
Item Description
EcoBreeze Frame and Module assembly*
Remote display interface
1
1
1
4
4
1
5
1
1
4
8
1
5
1
Frame electrical panel latch tool
Module access door latch tool
Water treatment module signal generator key
Technical manuals
Pipe adapter kit (50 Hz only)
3/4 NPT x 3/4 - 14 BSPT (4)
2-in. NPT x 2 - 11 BSPT (1)
* Version shown is the 12 m (40 ft) model.
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
5
EcoBreeze Frame and Modules
COIL
ACCESS
Y
SUPPL
BLOWER
ACCESS
I
I
Item Description
ISO corner fittings
Return air inlets
Module anchor brackets
Module
Tension rods and mounts
Screw-jack mounting points
Water drain outlet
Water supply inlets
Frame main power enclosure
Frame power distribution panel
Direct digital controller (DDC)
panel
6
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Module — front
Item Description
Condenser coil
Sprayer head and mist
eliminator access door
COIL
ACCESS
Water coupling and water
strainer access door
Y
SUPPL
BLOWER
ACCESS
COIL
ACCESS
Air filter and DX evaporator
coil access door
Module supply air duct access
door
Outdoor air intake
Compressor and wiring
connections access door
Indoor air fans access door
Remote display interface
Item Description
NEMA case
Display
LCD touch screen
Escape key
Left arrow key
Up arrow key
Down arrow key
Right arrow key
Enter key
Esc
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Site Preparation
Incoming power supply requirements
NOTE: This equipment requires three-phase electrical service. Electrical service must conform
to national and local electrical codes. The equipment must be grounded.
NOTE: To facilitate routing of main power supply wiring, run parallel wires for the main power
connections.
Ductwork
Provide supply and return ducting at the site to connect to the supply and return ductwork on
the EcoBreeze System.
See the ductwork drawings in submittal package for recommendations for ducting
sizes and supply and return duct configurations.
Water supply
Supply water requirements. The water supply must be clean, potable water. The inlet water
pressure provided to the unit must be between 207 and 448 kPa (30 and 65 psig). If the water
pressure available is less than 207 kPa (30 psig), a booster pump (not supplied) may be
needed to operate the equipment properly. If the water pressure available is higher than 448
kPa (65 psig), use an external pressure regulator (not supplied).
NOTE: Installation of back flow prevention and a water hammer arrestor is recommended.
NOTICE
DAMAGE TO EQUIPMENT
External water piping must have adequate freeze protection and must be correctly applied
based on local climatic conditions and best practices. Any exposed piping must be
electrically heat-traced and insulated (supplied by others).
Failure to follow these instructions can result in equipment damage.
Foundation
Provide a foundation for the EcoBreeze System as recommended in the submittal package.
installed on the top surface before the frame is placed on the permanent supports.
See EcoBreeze Frame Install Kit installation instructions for additional information.
8
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Environment
NOTE: Locating the EcoBreeze system near areas of increased airborne debris may result in
more frequent service intervals.
Piping/plumbing diagram
WATER RETURN GUTTER
X
FIELD
CONNECTIONS
X
OPTIONAL SAND FILTER CONNECTIONS
Item Description
Item Description
Clear T-strainer
Check valves
Two-way motorized valve*
Quick connect coupling
Water treatment module
Automatic vent
Pump line drain solenoid valve
Basin overflow
Supply water piping drain solenoid valve**
Basin drain valve
Pressure relief valve
Conductivity sensors
Water level sensors
Water supply A & B pressure switches***
Supply water A & B solenoid valves**
Blow down valve
Pump suction vent valve
Water sample service valve
Pump suction isolation valve
Redundant water pumps
Drain line cap
Basin water supply pipe
Piping to other modules
Spray nozzles
Module water pressure switch
*Controlled from module
** Use electric schematic #APC-CFR-02 to confirm valve wiring connections
*** Make sure the pressure switches are set to 7 psi
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
9
PRIMARY WATER SUPPLY
SECONDARY WATER SUPPLY
Item Description
Shut-off
Water pressure reducing valve (if necessary)
Backflow preventer
Water hammer arrestor
Alternate water supply (if available)
Inline strainer
Water pressure booster pump (if necessary)
EcoBreeze Frame
Note: All plumbing components shown are field installed.
Refrigeration
Each EcoBreeze Module contains its own closed refrigeration circuit. No field connections are
required.
10
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Service access
Install a service platform (not supplied) to facilitate maintenance activities. Regular
maintenance activities require a of minimum 1219 mm (48 in.) clearance on all sides to
remove, maneuver, and install Modules and components.
1219 (48)
1219 (48)
1219 (48)
1219 (48)
NOTE: Consider local soil conditions, codes, and loading when determining appropriate
support footings.
To prevent short cycling of outdoor air, each EcoBreeze Frame must have a minimum of 1219
mm (48 in.) clearance on each side, totaling 2438 mm (96 in.) between Frames, and 1219 mm
(48 in.) at the end of the Frame.
1219 (48)
1219 (48)
2438 (96)
1219 (48)
WALL OR OTHER OBSTRUCTION
* Dimensions are shown in millimeters with inches in parentheses.
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Weights and Dimensions
Frame
†
ACECFR20101SEn
2438 (96)
ACECFR20200SEn
ACECFR20201SEn
6058 (238.5)
CI
14)
2896 (1
LE
2438 (96)
12192 (480)
14)
2896 (1
C
U
BE
I
SP
C
BE
ACECFR40101SEn
ACECFR40200SEn
ACECFR40201SEn
* Dimensions are shown in millimeters, with inches in parentheses.
† Where n is the number of Modules populating the Frame upon order.
Frame (fully populated with Modules)
Weight (dry)
ACECFR20101SE4, ACECFR20200SE4, ACECFR20201SE4
ACECFR40101SE8, ACECFR40200SE8, ACECFR40201SE8
7 863 kg (17,300 lb)
14 290 kg (31,440 lb)
Frame (with Modules and water)
Weight (wet)
ACECFR20101SE4, ACECFR20200SE4, ACECFR20201SE4
ACECFR40101SE8, ACECFR40200SE8, ACECFR40201SE8
8 203 kg (18,047 lb)
14 630 kg (32,187 lb)
Frame (no Modules)
Weight
ACECFR20101SE0, ACECFR20200SE0, ACECFR20201SE0
ACECFR40101SE0, ACECFR40200SE0, ACECFR40201SE0
2 863 kg (6,300 lb)
4 290 kg (9,440 lb)
Module
Weight
ACEC101SE, ACEC200SE, ACEC201SE
1 250 kg (2,750 lb)
12
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Lifting and Rigging
WARNING
DAMAGE TO EQUIPMENT OR PERSONNEL
• Do not remove tension rods until the EcoBreeze Frame is placed and secured on
its supports.
• Before lifting the EcoBreeze Frame, ensure the lifting equipment is adequately
sized for the load.
• Lift and rig the EcoBreeze Frame from the top four ISO corners only.
• Move the EcoBreeze Frame directly from the truck to its permanent foundation. If
the Frame must be placed elsewhere temporarily, it must be placed on a flat and
level surface in order to avoid damage.
• Check for overhead obstructions such as power cables.
• Maintain a minimum safe distance while equipment is hoisted.
• Control access of personnel at lift site.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
EcoBreeze Frame. The EcoBreeze Frame is not equipped with forklift pockets. Lift and rig only
from the four upper ISO corner blocks on each EcoBreeze Frame using a crane.
Recommended horizontal sling angles are greater than 45 degrees. Lifting equipment must be
rated for at least 18 144 kg (40,000 lb) for lifting a 12.2 m (40 ft) Frame, and at least 12 247 kg
(27,000 lb) for a 6 m (20 ft) Frame.
L
LW
L
I
U
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
13
Mechanical Connections
Install the EcoBreeze Frame per the EcoBreeze Frame Install Kit instructions.
Position the EcoBreeze
NOTE: The power and plumbing connections for the EcoBreeze Frame are located on the end
where the unpacking sheet is placed on the protective wrap. Typically this is the end that will
face the building.
1. Ensure that clamp connectors and vibration damper pads are installed per the
EcoBreeze Frame Install Kit instructions.
2. Use a crane with sufficient lifting capacity to place the EcoBreeze onto the permanent
supports. Typically the end of the frame with plumbing and power connections is placed
nearest to the building.
3. Using a 15/16-in. open-end wrench to turn the drive stud, lock down the clamp
connectors located at each of the four corners. Maximum torque on the drive stud is 68
N-m (50 ft/lb).
14
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Unwrap the equipment
NOTICE
DAMAGE TO EQUIPMENT
• Do not remove the plastic wrap until the EcoBreeze Frame is placed on its
permanent supports and you are prepared to install the return air ductwork. If the
plastic is removed, ensure that the return air plenums on top of the Frame are
protected.
• When removing protective plastic wrap, be careful to cut only the plastic and not
damage the exterior of the equipment.
• The plastic wrap protects the return air plenum openings on top of the Frame until
the return air ductwork is installed.
Failure to follow these instructions can result in equipment damage.
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
15
Remove the tension rods
WARNING
DAMAGE TO EQUIPMENT OR PERSONNEL
• Loosen the nuts on the ends of the tension rods to relieve tension before removing
tension rod brackets.
• Do not remove the tension rods until EcoBreeze Frame is placed and secured on
its supports.
• Move the EcoBreeze Frame directly from the truck to its permanent foundation or
supports. If it must be stored temporarily, it must be placed on a flat and level
surface to avoid damage.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Tension rods are installed diagonally across each Module bay to provide support during
shipping.
1. Release tension on the rods by loosening the nuts on the ends of the tension rods.
2. Using an M12 wrench, remove the eight bolts securing the tension rod brackets.
3. Remove the tension rods and brackets.
16
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Lower Module drop-down box
1. Open the lower-right door on each Module.
2. For shipping, the drop-down box is secured upside down inside the Module. Remove the
screws securing the drop-down box (a).
NOTE: The screws will be re-used to install the drop-down box.
3. Turn the drop-down box over (b) so it faces right-side up (c).
COIL
ACCESS
Y
SUPPL
BLOWER
ACCESS
COIL
ACCESS
Y
SUPPL
BLOWER
ACCESS
COIL
ACCESS
Y
SUPPL
OWER
ACCESS
BL
COIL
ACCESS
Y
SUPPL
OWER
BL
ACCESS
4. Drop the drop-down box through the opening in the bottom of the Module and attach it to
the Module with the supplied screws (a).
5. Line up the drop-down box with the supply air transition and attach it to the supply air
transition (b).
NOTE: The drop-down box is flexible enough to adjust for slight misalignments.
NOTE: Hardware to attach the drop-down box to the supply air transition is field
supplied.
MODULE DROP-
DOWN BOX
FOR CLARITY,
MODULE STRUCTURE
IS NOT SHOWN
MODULE
SUPPLY AIR
TRANSITION
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
17
6. Locate the insulation strips packed in the ship-loose kit.
7. Remove the backing from the insulation and apply the insulation around the air transition
ducts.
8. Open the damper on the supply air transition.
Water supply connection
NOTE: There are two water supply inlets on the EcoBreeze Frame. Use separate sources if
possible to provide a redundant water supply.
NOTICE
DAMAGE TO EQUIPMENT
Install adequate freeze protection (not supplied) on all external water piping.
Freeze protection (which may consist of any combination of insulation and electric
heat-tracing) must be correctly applied based on local climatic conditions and best
practices.
Failure to follow these instructions can result in equipment damage.
Sand filtration connections are provided if further filtration of the water supply is required. Sand
filtration systems can be acquired from a third-party vendor.
18
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Connect the water supply to the two 3/4-inch water supply fittings on the EcoBreeze Frame. If
WATER DRAIN
WATER INLET
(60 Hz) 2-in. NPT FEMALE FITTING
(60 HZ) 3/4-in. NPT FEMALE
(50 Hz) 2 - 11 BPST PIPE ADAPTER
FITTING
(50 Hz) 3/4 - 14 BSPT PIPE
ADAPTER
OPTIONAL SAND FILTER
CONNECTIONS
WATER INLET
(60 HZ) 3/4-in. NPT FEMALE
FITTING
(50 Hz) 3/4 - 14 BSPT PIPE
ADAPTER
334.44 (13.16)
69.85 (2.75)
1120.78 (44.13)
1303.27 (51.31)
1317.63 (51.88)
* Dimensions are shown in millimeters with inches in parentheses.
Drain
Connect the external 2-in. drain line on the EcoBreeze Frame to an open drain used for
collection of wastewater. If necessary, make the connection using the appropriate fitting from
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
19
NOTE: Separate the drain line from the EcoBreeze Frame and the external drain line by a
50 mm (2 in.) air gap in order to prevent back up of contaminated water into the cooling system.
AIR GAP
NOTE: Pitch the external drain piping at a minimum of 25 mm (1 in.) per 3048 mm (10 ft)
towards the wastewater drain.
20
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Connections
The electrical connections required are the following:
• Power to Frame
• Control (remote display interface)
• Communication - Building Management System (BMS) - optional
Make all electrical connections in accordance with applicable industry guidelines as well as
national and local codes.
Make all low-voltage connections, including data and control connections, with properly
insulated wires. The low-voltage wires and connections must have at least 300V insulation.
DANGER
HAZARD OF ELECTRIC SHOCK
Use a voltmeter to ensure that power is turned off before making any electrical
connections.
Failure to follow these instructions will result in death or serious injury.
NOTE: Three-phase electrical service is required. Electrical service must conform to national
and local electrical codes.
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
21
Power supply to EcoBreeze Frame
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work must be performed by licensed electricians. Practice Lockout/Tagout procedures. Do
not wear jewelry when working with electrical equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD TO EQUIPMENT AND PERSONNEL
Only Schneider Electric authorized personnel may energize the equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
1. Use a punch tool to create an access hole as needed for power supply wires entering
the main power enclosure.
2. Attach the conduit connector to the access hole on the main power enclosure.
NOTE: A service loop is factory-installed in the main power enclosure.
3. If permitted by local and national codes, route the cable to the disconnect switch as
shown. If local and national codes do not permit service loops, make all connections per
code.
4. Connect the power wiring to the disconnect switch. Connect the phases as marked next
to the disconnect switch.
5. Connect the ground wire to the grounding lug beside the disconnect switch.
L1
L3
L2
GND
22
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Remote display interface
NOTICE
DAMAGE TO EQUIPMENT
Damage to LCD display will result from exposure to temperatures below 0°C (32°F).
Outdoor installations will require a third-party heat source as needed to ensure the LCD
display is not subjected to temperatures below 0°C (32°F).
Failure to follow these instructions can result in equipment damage.
See EcoBreeze remote display installation instructions for additional information.
The remote display interface enclosure contains the LCD display that is used to control the
EcoBreeze from a remote location. The EcoBreeze connects to the remote display interface
over an expansion bus.
NOTE: Separate incoming power cables from low voltage wiring by 150 mm (6 in.).
NOTE: Communication wiring from the EcoBreeze to the remote display interface enclosure
must be a minimum of 24-gauge, 3-core wire with shield with a maximum length of 300 m (984
ft).
1. Install the remote display interface enclosure in the desired location.
IMPORTANT: For outdoor applications, use weather-proof conduit connectors.
OPERATING CONDITIONS: Ambient temperature 0 - 55°C (32 - 131°F). Relative
humidity 5% - 95% non-condensing.
NOTE: Connect shield wire to GND.
2. Connect the bus wiring to the contacts labeled 124, 125, and 126 on the expansion bus
terminal block, located behind the direct digital controller (DDC) access door on the
Frame.
DDC PANEL
ENCLOSURE
124
125
126
GND
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
23
3. Wire the expansion bus to the 124, 125, and 126 contacts on the terminal block in the
remote display interface enclosure.
L1
AC POWER
(85-265
VAC,
50/60 Hz)
L2N
PE - GND
SUPPLY AIR DP SIGNAL
POWER RETURN / SIGNAL
ANALOG INPUT
(4-20mA OR 0-10
VDC)
ACTIVE SENSOR POWER (+24 VDC)
RUN / DAMPER END COMMON
RUN SIGNAL
DIGITAL
INPUTS
(DRY
DAMPER END SWITCH SIGNAL
DAMPER COMMON
CONTACT)
DIGITAL
OUTPUTS
(DRY
CONTACT,
5A, 250VAC)
DAMPER OPERATION
ALARM COMMON
ALARM (NORMALLY OPEN)
CAN - H
FRAME
BUS
CAN - L
(CAN)
CAN - GND
24
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Building Management System
The Modbus interface allows the EcoBreeze System to communicate with a building
management system (BMS).
The Modbus connection is available in two locations on the Modbus hub:
• RJ-45 In port
• 3-wire on terminal block
For an RJ-45 connection, wire as follows:
Pin 4
Pin 5
Pin 8
D(A)
D(B)
Ground
For a direct 3-wire connection, connect to the corresponding contacts on the green terminal
block on the side of the Modbus hub. No connection is necessary to the 0V contact.
DDC PANEL
ENCLOSURE
WIRING CONTACTS
FOR DIRECT 3-WIRE
CONNECTION
RJ-45 IN PORT
1MOD
D(B)
D(A)
1MOD
0 V
EcoBreeze System Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Worldwide Customer Support
Customer support is available at no charge via e-mail or telephone. Contact information is available at
© Schneider Electric is owned by Schneider Electric Industries S.A.S., or its affiliated companies. All other
trademarks are property of their respective owners.
990-3976D-001
6/2014