Roberts Gorden Heating System 10081601NA Rev H 12 11 User Guide

®
ROBERTS GORDON  
UltraVac  
PATENTED  
Controls for  
Modulating  
®
CORAYVAC  
Infrared Heating  
Systems  
Installation Manual  
Installer  
WARNING  
Please take the time to read and understand  
these instructions prior to any installation.  
Installer must give a copy of this manual to the owner.  
Improper installation, adjustment, alteration, service  
or maintenance can result in death, injury or  
property damage. Read the Installation, Operation  
and Service Manual thoroughly before installing or  
servicing this equipment.  
Owner  
Keep this manual in a safe place in order to provide  
your serviceman with necessary information.  
Installation must be done by an electrician  
qualified in the installation and service of control  
systems for heating equipment.  
Roberts-Gordon LLC  
1250 William Street  
P.O. Box 44  
Buffalo, New York 14240-0044  
Telephone: +1.716.852.4400  
Fax: +1.716.852.0854  
Toll Free: 800.828.7450  
© 2011 Roberts-Gordon LLC  
P/N 10081601NA Rev H 12/11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1.2 What is ROBERTS GORDON® ULTRAVAC™?............2  
GORDON® ULTRAVAC™.......................................... 42  
1.4 CORAYVAC® Design Requirements.............................2 SECTION 8: Commissioning The CORAYVAC® System .... 44  
8.1 Setting The CORAYVAC® End Burner Vacuum......... 44  
2.1 ROBERTS GORDON® ULTRAVAC™ Controller ....... 16  
10.1 ROBERTS GORDON® ULTRAVAC™ Controller  
Replacement Parts.................................................. 56  
10.3 ULTRAVAC™ BMS Link Controller Replacement  
Warranty.......................................................... 62  
Controller and Variable Frequency Drive ...................21  
3.4 Electrical Installation Requirements of ULTRAVAC™  
GORDON® ULTRAVAC™ Controllers........................35  
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the  
property of their respective owners. Roberts-Gordon LLC is not sponsored by or affiliated with any of the trademark or regis-  
tered trademark owners, and make no representations about them, their owners, their products or services. Roberts-Gordon  
LLC is not sponsored by or affiliated with BACnet® or MODBUS®.  
Roberts-Gordon LLC  
© 2011  
All rights reserved. No part of this work covered by the copyrights herein may be reproduced  
or copied in any form or by any means - graphic, electronic, or mechanical, including  
photocopying, recording, taping or information storage and retrieval systems - without the  
written permission of Roberts-Gordon LLC.  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF FIGURES  
Figure 7: ROBERTS GORDON® ULTRAVAC™ Controller  
Specifications .......................................................... 18  
Figure 8: Variable Frequency Drive Components  
Figure 13: ROBERTS GORDON® ULTRAVAC™ Central  
Controller External Wiring ......................................26  
Figure 14: ROBERTS GORDON® ULTRAVAC™ Satellite  
Controller External Wiring ......................................28  
Figure 22: Repeater Communication Wiring Between Multiple  
Figure 25: Communication Between ULTRAVAC™ BMS Link  
Figure 31: ROBERTS GORDON® ULTRAVAC™ Controller  
Components Diagram............................................56  
Figure 33: ULTRAVAC™ BMS Link Controller Components  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 1: INTRODUCTION  
1.1 Safety  
ROBERTS GORDON® ULTRAVAC™, see Page 8,  
Your Safety is Important to Us!  
This symbol is used throughout  
the manual to notify you of  
possible fire, electrical or burn  
hazards. Please pay special atten-  
tion when reading and following  
the warnings in these sections.  
System status and settings are viewed and altered  
from a PC (not supplied) running ROBERTS GOR-  
DON® ULTRAVAC™ Software.  
1.3 General Requirements  
Installation, service and annual inspection of  
controller must be done by an electrician qualified in  
the installation and service of control systems for  
heating equipment.  
DANGER  
Installation, service and annual inspection of heater  
must be done by a contractor qualified in the  
installation and service of gas-fired heating  
equipment.  
Electrical Shock Hazard  
Read this manual carefully before installation,  
operation, or service of this equipment.  
Disconnect electric before service.  
Controller must be properly grounded to an  
electrical source.  
The heater must be applied and operated under the  
general concepts of reasonable use.  
This appliance is not intended for use by persons  
(including children) with reduced physical, sensory or  
mental capabilities, or lack of experience and knowl-  
edge, unless they have been given supervision or  
instruction concerning use of the appliance by a per-  
son responsible for their safety.  
Failure to follow these instructions can  
result in death or electrical shock.  
The ROBERTS GORDON® ULTRAVAC™ series of  
controllers are supplied pre-configured for use with  
ROBERTS GORDON® CORAYVAC® infrared heating  
equipment only. Failure to comply with the installation  
instructions and configuration may invalidate the  
ROBERTS GORDON® ULTRAVAC™ limited war-  
ROBERTS GORDON® ULTRAVAC™ Software  
requires a PC (not supplied) running Windows® 95 or  
higher, with a Pentium® class processor and at least  
64k of RAM.  
Children should be supervised to ensure that they do  
not play with the appliance.  
For optimum heater performance and safe heating  
conditions, inspect and maintain heater(s) before  
every heating season and as necessary. Also, know  
and maintain heater clearances to combustibles, see  
heater Installation, Operation and Service Manual for  
further details. If you require additional manuals, con-  
tact your ROBERTS GORDON® independent distrib-  
utor or Roberts-Gordon at (716) 852-4400, (800)  
828-7450 or at www.rg-inc.com.  
The controller, variable frequency drive, burners,  
repeater, pump and outside air blower must be  
electrically grounded in accordance with the National  
Electrical Code® ANSI/NFPA 70 - latest revision.  
Before proceeding with the installation of the control-  
ler, it will be necessary to check that the following  
points have been considered:  
1.2 What is ROBERTS GORDON® ULTRAVAC™?  
The ROBERTS GORDON® ULTRAVAC™ is a micro-  
processor based control package designed for  
modulating control of CORAYVAC® heaters based on  
outdoor temperatures.  
1.4 CORAYVAC® Design Requirements  
CORAYVAC® burners shall be CRV B-6, B-8, B-9,  
This controller is capable of giving control outputs to  
one vacuum pump and three heating zones. The  
controller also features inputs which are used for  
indoor and outdoor signal condition monitoring.  
B-10 or B-12 burners.  
CORAYVAC® systems designed shall have  
minimum radiant pipe length and 1.5 - 2.0 feet per  
flow unit of tailpipe length.  
For the overall view of connected components for  
2 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
SECTION 1: INTRODUCTION  
ERTS GORDON® independent distributor to obtain  
replacement signs or labels. See Page 4, Figure 1  
-OR-  
CORAYVAC® systems designed shall have  
recommended radiant pipe length and 1.2 - 1.5 feet  
per flow unit of tailpipe length. See the CORAYVAC®  
Design Manual (P/N 127500NA) for minimum and  
recommended radiant pipe length.  
1.5 Example Site Layout  
Page 15, Figure 6 is an example layout for a building  
where ROBERTS GORDON® ULTRAVAC™ will be  
used to control the infrared heating systems shown.  
The layout consists of three zones of ROBERTS  
GORDON® ULTRAVAC™.  
1.6 Check Installation Materials  
1.6.1 Switchable Loads  
The controller relays are rated for switching loads no  
greater than 3 A. The total added current load for all  
8 relays must not exceed 25 A.  
1.6.2 Control Wiring  
Shielded cable (four twisted pairs of stranded 24  
AWG minimum wire) is required for use with  
indoor sensors.  
Shielded cable (one twisted pair of stranded 22  
AWG minimum wire) is required for the outdoor  
air sensor, VFD signal wiring, pressure switch  
and wiring from controller #1 to the PC.  
Shielded cable (one twisted pair of stranded 22  
AWG minimum wire) is required for RS-485  
communications between controllers.  
1.6.3 Control Board and Sensor Power  
The power supply for all sensors is from the “+32 V”  
terminal to be found on the board of the controller.  
Power for the control board is 24 V provided by the  
relay board.  
1.6.4 Programming Details  
Every controller is pre-programmed for one pump  
and up to three heating zones. Use a site  
layout drawing to identify the heating zones.  
1.7 Safety Labels and Their Placement  
Product safety signs or labels should be replaced by  
the product user when they are no longer legible.  
Please contact Roberts-Gordon LLC or your ROB-  
3 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 1: ULTRAVAC™ Controller Label Placement  
Light Label  
Electrical Shock Hazard Label  
Logo Label  
Rating Plate Label  
Front Door Panel (outside)  
External Wiring Label  
+
-
+
-
+
-
+
-
+
-
+
-
PWR  
NC  
C
N
O
N
C
C
N
O
N
C
C
NO NC  
C
NO  
L2 L1  
24VAC  
OUT IN  
G
+32 +5  
G
G
G
REF  
OUT REF IN  
4
3
2
1
RS232 DIRECT  
AUX POWER  
RS485 COMM  
METER INPUTS  
RESET  
ADDRESS  
OH CD RI  
CPU  
UNIVERSAL INPUTS  
8
7
6
5
4
3
2
1
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
IN  
NC  
C NO NC C NO NC C NO NC C NO  
OUT  
499 OHM  
10VDC  
OFF  
ON  
Front Door Panel (inside)  
Description  
Logo Label  
Part Number  
91013207  
91008005  
91008007  
91008004  
91008003  
91008001  
Rating Plate Label  
Light Label  
Control Board Wiring Label  
External Wiring Label  
Shock Hazard label  
Control Board Wiring Label  
4 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 1: INTRODUCTION  
FIGURE 2: ULTRAVAC™ BMS Link Controller Label Placement  
Description  
Logo Label  
Rating Plate Label  
Light Label  
Control Board Wiring Label  
Shock Hazard label  
Part Number  
91008017  
91008016  
91008015  
91008014  
91008001  
5 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 3: VFD Label Placement  
Electrical Shock Hazard Label  
Side Panel (outside)  
Front Door Panel (outside)  
Rating Plate Label  
Power Input  
Rotary Disconnect  
Variable Frequency Driver  
1 Ø Input Model Shown  
L1  
L2/N  
PE  
B-  
B+  
Input Fuse Holder  
Wiring Diagram Label  
U
V
W
PE  
PE  
M16/12.P  
Relay 120 V  
Front Door Panel (inside)  
Description  
Part Number  
Rating Plate Label  
Wiring Label (230 V)  
Wiring Label (460 V)  
Shock Hazard label  
91008006  
91008004  
91008003  
91008001  
6 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 1: INTRODUCTION  
FIGURE 4: Repeater Label Placement  
Description  
Wiring Diagram Label  
Logo Label  
Rating Plate Label  
Shock Hazard Label  
Part Number  
91008020  
91008021  
91008022  
91008001  
7 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 5: Connected Components  
8 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 1: INTRODUCTION  
Connected Components (continued)  
9 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I
9
+
+
-
+
-
+
-
4
3
2
1
Modem Chip  
METER INPUTS  
RESET  
RESS  
OH CD RI  
-
ULTRAVAC™ Software  
P
NC  
C
N
O
N
C
C
N
O
N
C
C
N
O
N
C
C
NO  
L2 L1  
24VAC  
O
U
T
I
N
G
+
3
2
+
5
G
G
G
REFOUT REF IN  
RS485 COMM  
4
3
2
1
RS232 DIRECT  
AUX POWER  
METER INPUTS  
RESET  
ADDRESS  
O
H
C
D
R
I
CPU  
(P/N 100816CDNA) contains:  
ULTRAVAC™ Software,  
UNIVERSAL INPUTS  
8
7
6
5
4
3
2
1
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
IN  
NC  
C NO NC C NO NC C NO NC C NO  
OUT  
499 OHM  
10VDC  
499 OHM  
OFF  
ON  
ULTRAVAC™ Software Manual.  
(P/N 10081600NA)  
Inside View  
ULTRAVAC™ Controller  
ULTRAVAC™ Installation Manual  
(P/N 10081601NA), BACnet®  
Software and Ruinet Manual.  
with Modem Installed  
Repeater (optional)  
Supplied w/24 VAC  
transformer inside  
NEMA 1 enclosure  
(P/N URVRP)  
Inside View  
Indoor Sensor  
(P/N 10081502)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 1: INTRODUCTION  
URVCCM: ULTRAVAC™ Central Controller with Modem  
+
+
-
+
-
+
-
4
3
2
1
Modem Chip  
METER INPUTS  
RESET  
RESS  
OH CD RI  
+
-
+
-
+
-
+
-
+
-
+
-
PWR  
NC  
C
N
O
N
C
C
N
O
N
C
C
N
O
N
C
C
NO  
L2 L1  
24VAC  
O
U
T
I
N
G
+
3
2
+
5
G
G
G
REFOUT REF IN  
RS485 COMM  
4
3
2
1
RS232 DIRECT  
AUX POWER  
METER INPUTS  
RESET  
ADDRESS  
O
H
C
D
R
I
C
UNIVERSAL INPUTS  
8
7
6
5
4
3
2
1
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
IN  
NC  
C NO NC C NO NC C NO NC C NO  
OUT  
499 OHM  
10VDC  
499 OHM  
OFF  
ON  
Inside View  
ULTRAVAC™ Controller  
with Modem Installed  
Repeater (optional)  
Supplied w/24 VAC  
transformer inside NEMA 1  
enclosure (P/N URVRP)  
Inside View  
ULTRAVAC™ Software (P/N 100816CDNA) contains:  
ULTRAVAC™ Software, ULTRAVAC™ Software Manual.  
(P/N 10081600NA), ULTRAVAC™ Installation Manual  
(P/N 10081601NA), BACnet® Software and Ruinet Manual.  
PC Connection Cable Package  
(P/N 10080410)  
Outdoor Sensor  
(P/N 10081501)  
Indoor Sensor  
(P/N 10081502)  
11 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
+
+
-
+
-
+
-
4
3
2
1
Modem Chip  
METER INPUTS  
RESET  
RESS  
OH CD RI  
-
PWR  
NC  
C
N
O
N
C
C
N
O
N
C
C
N
O
N
C
C
NO  
L2 L1  
24VAC  
O
U
T
I
N
G
+
3
2
+
5
G
G
G
REFOUT REF IN  
RS485 COMM  
4
3
2
1
RS232 DIRECT  
AUX POWER  
METER INPUTS  
RESET  
ADDRESS  
O
H
C
D
R
I
CPU  
UNIVERSAL INPUTS  
8
7
6
5
4
3
2
1
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
IN  
NC  
C NO NC C NO NC C NO NC C NO  
OUT  
499 OHM  
10VDC  
499 OHM  
OFF  
ON  
Inside View  
ULTRAVAC™ Controller  
with Modem Installed  
Inside View  
Repeater (optional)  
Supplied w/24 VAC  
transformer inside NEMA 1  
enclosure (P/N URVRP)  
ULTRAVAC™ Software (P/N 100816CDNA) contains:  
ULTRAVAC™ Software, ULTRAVAC™ Software Manual.  
(P/N 10081600NA), ULTRAVAC™ Installation Manual  
(P/N 10081601NA), BACnet® Software and Ruinet Manual.  
Outdoor Sensor  
(P/N 10081501)  
PC Connection Cable Package  
(P/N 10080410)  
RS-485 Converter Package (P/N 10080430)  
Indoor Sensor  
(P/N 10081502)  
Power Supply  
RS-485 Converter  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1: INTRODUCTION  
URVBNC: ULTRAVAC™ BMS Link Controller  
ULTRAVAC™ Software (P/N 100816CDNA) contains:  
ULTRAVAC™ Software, ULTRAVAC™  
Software Manual. (P/N 10081600NA)  
ULTRAVAC™ Installation Manual  
(P/N 10081601NA),BACnet® or  
ULTRAVAC™ BMS Link  
Controller  
Inside View  
MODBUS® Software  
1.9 Standard Parts List  
Table 1: Contents of ULTRAVAC™ Controller and Accessories  
Part No.  
Description  
URVCCL ULTRAVAC™ Central Controller (with TCP/IP Communication Module, Software & Manual), Including:  
URVSC  
Controller, ULTRAVAC™, 1 Pump 3 Zones (Satellite Control & Manual)  
10080142 Modem Chip  
10080440 TCP/IP Communication Module  
10081501 Outdoor Sensor  
10080410 PC Connection Cable Package  
10081502 Indoor Sensor (sold separately)  
URVCCM ULTRAVAC™ Central Controller (with Modem Chip, Software & Manual), Including:  
URVSC  
Controller, ULTRAVAC™, 1 Pump 3 Zones (Satellite Control & Manual)  
10080142 Modem Chip  
1008150 Outdoor Sensor  
10080410 PC Connection Cable Package  
10081502 Indoor Sensor (sold separately)  
URVCCR ULTRAVAC™ Central Controller (with RS-485 Converter, Software & Manual), Including:  
URVSC  
Controller, ULTRAVAC™, 1 Pump 3 Zones (Satellite Control & Manual)  
10080142 Modem Chip  
10080430 RS-485 Converter with 9V Power Supply  
1008150 Outdoor Sensor  
10080410 PC Connection Cable Package  
10081502 Indoor Sensor (sold separately)  
URVBNC ULTRAVAC™ ULTRAVAC™ BMS Link Controller (with Software CD & Manual, IOS Manual)  
URVSC  
Controller, ULTRAVAC™, 1 Pump 3 Zones (Satellite Control & Manual)  
13 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
Table 2: Common Components of ROBERTS GORDON® ULTRAVAC™ Controls  
Part No.  
Description  
Variable Frequency Drives*  
VFD75115 Variable Frequency Drive Assembly, .75 HP 115 V 1 Ø Input  
VFD75230 Variable Frequency Drive Assembly, .75 HP 230 V 1 Ø Input  
VFD20230 Variable Frequency Drive Assembly, 2 HP 230 V 1 Ø Input  
VFD75115N4 Variable Frequency Drive Assembly, .75 HP 115 V 1 Ø Input, NEMA 4  
VFD75230N4 Variable Frequency Drive Assembly, .75 HP 230 V 1 Ø Input, NEMA 4  
VFD75460 Variable Frequency Drive Assembly, .75 HP 480 V 3 Ø Input  
VFD75460N4 Variable Frequency Drive Assembly, .75 HP 480 V 3 Ø Input, NEMA 4  
VFD20230N4 Variable Frequency Drive Assembly, 2 HP 230 V 1 Ø Input, NEMA 4  
VFD20460 Variable Frequency Drive Assembly, 2 HP 480 V 3 Ø Input  
VFD20460N4 Variable Frequency Drive Assembly, 2 HP 480 V 3 Ø Input, NEMA 4  
*NEMA 4 VFDs are special order items. Call for availablity.  
NEMA4 Enclosures**  
10080302 Enclosure, NEMA 4 for URV Controller  
10081510 Enclosure, NEMA 4 for URV Sensor  
**Enclosures only. Controller and/or Sensor must be purchased separately.  
Related Accessories  
10080142 Modem, Plug-In Chip  
10080410 Cable Package, PC Connection  
10080430 RS-485 Converter with 9 V Power Supply  
10080440 TCP/IP Communication Module  
10080600 Telephone Sharing Device, 4-Port  
10081500 Sensor, Adjustable Indoor, °F, URV  
10081501 Sensor, Outdoor, URV  
10081502 Sensor, Adjustable Indoor, °C, URV  
90602450 Voltage Surge Supresser  
90602460 Load Reactor 180 V / 4 A Output  
90602470 Line Reactor 180 V / 4 A Input  
URVRP  
Repeater, URV Communication  
14 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1: INTRODUCTION  
FIGURE 6: Example Site Layout  
NOTE: Conceptual drawing, not to scale. Venting not shown.  
15 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 2: SPECIFICATIONS  
Link Controller.  
2.1 ROBERTS GORDON® ULTRAVAC™ Controller  
Standard enclosures are field  
mounted inside the NEMA 4  
enclosure.  
2.1.1 Standard Enclosure  
Construction: 16 gauge painted steel, hinged  
door, removable knockouts  
provided.  
Construction: 14 gauge painted steel, hinged door  
with 19" (48.3 cm) x (40.6 cm) 16"  
window.  
Dimensions: W x H x D  
(in): 14.7 x 17.7 x 3.5  
(cm): 37.3 x 45.0 x 8.9  
Dimensions: W x H x D  
(in): 24 x 24 x 9  
(cm): 61.0 x 61.0 x 22.9  
2.1.2 Electrical  
Protection  
Rating:  
Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz  
UL Standard: UL 916 / C22.2 No. 205-M1983  
NEMA 4, 12  
Universal Inputs:  
Eight Universal Inputs  
Thermistor  
2.4 Repeater  
2.4.1 Standard Enclosure  
0-10 Vdc  
4-20m A  
Resistance  
Dry contact  
Construction: Fabricated in accordance with UL  
specifications from code gauge steel,  
NEMA 1.  
Finish:  
Austin screw cover boxes standard  
construction galvanized steel with  
ANSI 61 gray polyester powder  
coating.  
Analog Output:  
One Analog Output 0-10 Vdc  
Digital Inputs:  
Digital Inputs: Timed, dry contact  
Dimensions: W x H x D  
(in): 12 x 12 x 4  
(cm): 30.5 x 30.5 x 10.5  
2.4.2 Electrical  
Digital Outputs:  
Eight Digital Output: Single Pole 3 A 120 Vac  
Ports:  
RS-485 Communications Bus  
RS-232 Direct Connect Bus  
RS-232 Modem Socket  
Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz  
Ports:  
RS-485 Communications Bus  
RS-232 Direct Connect Bus  
2.2 ULTRAVAC™ BMS Link Controller  
2.2.1 Standard Enclosure  
2.5 Temperature Sensors  
Indoor Sensor  
Construction: 16 gauge painted steel, hinged  
door, removable knockouts provided.  
Dimensions: W x H x D  
(in): 2.75 x 4.5 x 1.15  
(cm): 7.0 x 11.4 x 2.9  
Dimensions: W x H x D  
(in):14.7 x 17.7 x 3.5  
(cm): 37.3 x 45.0 x 8.9  
Power:  
Operating Temperature Range:  
32° to 158° F (0° to 70° C)  
32 V DC  
2.2.2 Electrical  
Power Supply: 120V (+/-10%) 1 Ø, 60 Hz  
Ports:  
Features:  
LCD temperature display, setpoint  
adjustment, override button  
RS-485 Communications Bus  
Ethernet/IP  
Outdoor Sensor (P/N 10081501)  
Dimensions: W x H x D  
(in): 1.4 x 5.3 x 2  
2.3 NEMA 4 Enclosure (P/N 10080302)  
(cm): 3.6 x 13.5 x 5.1  
Description: NEMA 4 enclosure is sold separately  
as an option, for ULTRAVAC™  
Operating Temperature Range:  
Controller and ULTRAVAC™ BMS  
-40° to 221° F (-40° to 5° C)  
16 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
SECTION 2: SPECIFICATIONS  
Enclosure:  
NEMA 4 gasketed aluminum LB  
housing, ½" threaded connection  
Voltage Surge Suppressor 277 / 480 V  
Construction: NEMA 2X Enclosure  
NEMA 4 Enclosure for Indoor Sensor  
(P/N 10081510)  
Volts:  
277 / 480 V  
50/60 Hz  
Frequency:  
Description: NEMA 4 Enclosure is sold separately  
as an option. The indoor sensor is  
field mounted inside the NEMA 4  
enclosure. Temperature thermistor  
and LCD temperature display will not  
operate properly inside the  
Wiring Size: #12 AWG Standard Wire  
enclosure. LCD display feature should  
be disabled and use of the NEMA 4  
sensor enclosure will require the use  
of an outdoor sensor (P/N 10081501)  
in the space to monitor zone  
temperature.  
Dimensions: W x H x D  
(in): 6.3 x 3.6 x 1.8  
(cm): 16.0 x 9.1 x 4.6  
Construction: Polycarbonate enclosure with clear  
front cover, 4 screw cover closure. 16  
gauge galvanized subpanel.  
Protection  
Rating:  
NEMA 4, 4X  
UL-94-5V  
Flammability  
Rating:  
2.6 Line Reactor 480 V / 4 A Output  
Construction: Fabricated in accordance with UL  
specifications from code gauge steel,  
NEMA 1.  
Dimensions: W x H x D  
(in): 10 x 8 x 8  
(cm): 25 x 20 x 20  
Rated  
Current:  
4 A  
Volts:  
480 V / 3 Ø  
Line Reactor 480 V / 4 A Input  
Construction: Fabricated in accordance with UL  
specifications from code gauge steel,  
NEMA 1.  
Dimensions: W x H x D  
(in): 10 x 8 x 8  
(cm): 25 x 20 x 20  
Rated  
Current:  
4 A  
Volts:  
480 V / 3 Ø  
17 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 7: ROBERTS GORDON® ULTRAVAC™ Controller Specifications  
Note:  
To ensure robust control signaling:  
Do not run line voltage wiring through bottom section  
of enclosure that houses the control board.  
Do not run low voltage wiring through top section  
of enclosure that houses the relay board.  
18 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 2: SPECIFICATIONS  
2.7 Variable Frequency Drive (VFD)  
2.7.1 Enclosure  
.75 HP, 230 V Drive (used with EP-203 pump)  
(P/N VFD75230 or VFD75230N4)  
Power Input: 208/230 V, 1 Ø, 50-60 Hz  
Input Voltage Tolerance: +/- 10%  
Standard Models  
Construction: 14 gauge painted steel, mounting  
panel included, left-hinged door,  
vented.  
Amps:  
6.9/6.0 A  
Dimensions: W x H x D  
(in): 12 x 14.375 x 8  
1 HP, 120 V Drive (used with EP-203 pump)  
(P/N VFD75115 or VFD75115N4)  
Power Input: 120 V, 1 Ø, 50-60 Hz  
Input Voltage Tolerance: +/- 10%  
(cm): 30.5 x 36.5 x 20.3  
Protection:  
UL 50 Type 1, NEMA Type 1  
NEMA 4 Models  
Amps:  
16.6 A  
Description: Drive assembly and components fully  
factory assembled inside NEMA 4  
2 HP, 230 V Drive (used with EP-303 pump)  
(P/N VFD20230 or VFD20230N4)  
Power Input: 208/230 V, 1 Ø, 50-60 Hz  
Input Voltage Tolerance: +/- 10%  
enclosure. Enclosure dimensions and  
construction vary by model.  
Construction: VFD75115N4, VFD20230N4 and  
VFD20460N4 enclosures are  
Amps:  
18.4/16.0 A  
16 gauge painted steel, left hinged  
door, non-vented.  
1 HP, 460 V Drive (used with EP-203 pump)  
(P/N VFD75460 or VFD75460N4)  
Power Input: 400/480 V, 3 Ø, 50-60 Hz  
Input Voltage Tolerance: +/- 10%  
VFD75230N4 and VFD75460N4  
enclosures are 14 gauge steel, left  
hinged door, non-vented.  
Amps:  
3.0/2.5 A  
Dimensions: W x H x D  
VFD75115N4 (in): 20 x 16 x 10  
(cm): 50.8 x 40.6 x 25.4  
2 HP, 460 V Drive (used with EP-303 pump)  
(P/N VFD20460 or VFD20460N4)  
Power Input: 400/480 V, 3 Ø, 50-60 Hz  
Input Voltage Tolerance: +/- 10%  
VFD75230N4 (in): 14 x 12 x 8  
(cm): 35.6 x 30.5 x 20.3  
VFD20230N4 (in): 20 x 16 x 10  
(cm): 50.8 x 40.6 x 25.4  
Amps:  
4.8/4.0 A  
VFD75460N4 (in): 16 x 14 x 10  
(cm): 40.6 x 35.6 x 25.4  
VFD20460N4 (in): 20 x 16 x 10  
(cm): 50.8 x 40.6 x 25.4  
Protection:  
NEMA 3R, 4, 12, 13  
2.7.2 Electrical  
Power Output: 230 V, 3 Ø, 0-60 Hz  
(for 115 V and 230 V models)  
480 V, 3 Ø, 0-60 Hz  
(for 480 V models)  
Speed Reference Follower: 0-10 Vdc or 4-20 mA  
UL Standard: Industrial Controls Equipment  
Ambient Operating Temp.:  
32° F - 104° F (0° C - 40° C)  
19 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 8: Variable Frequency Drive Components (Factory pre-wiring shown)  
20 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 3: INSTALLATION  
SECTION 3: INSTALLATION  
maximum ambient temperature does not exceed  
104°F (40°C). Avoid installing the VFD in mezza-  
nines, direct sunlight, or near external heat  
sources because these locations usually have  
unpredictable temperature rises.  
DANGER  
Note that the maximum distance from the controller  
to any sensor is 300' (120 m). For longer distances,  
larger gauge wire may be needed (Consult your local  
distributor). For multiple controllers, maximum length  
of communication wire from the first controller to the  
last is 4000' (1219 m) without the use of a repeater. A  
repeater is available for wire length greater than  
4000' (1219 m). See Page 36, Section 5.5.1. Wiring  
between the RS-485 converter to the controller  
should not be more than 400' (122 m) in length. See  
Electrical Shock Hazard  
Disconnect electric before service.  
Controller must be properly grounded to an  
electrical source.  
Failure to follow these instructions can  
result in death or electrical shock.  
Installation of the ROBERTS GORDON®  
ULTRAVAC™ Controller and the associated external  
electrical wiring must be done by an electrician  
qualified in the installation of control systems for  
heating equipment.  
3.2.2 Position the controller and VFD at occupant  
level for ease of service. To avoid electrical  
interferences with communications bus, do not  
mount VFD directly next to controller. Allow 2'  
(.6 m) minimum between controller and VFD. If  
the VFD is more than 100' (150 m) from the pump  
a load reactor (P/N 90602460) must be used.  
3.1 Preparation  
FIGURE 9: Controller Mounting  
Before installing the controller, observe the following:  
(Standard enclosure only, NEMA 4 enclosure mount-  
ing varies)  
3.1.1 Ensure that you have a copy of the site layout  
for the project that clearly identifies the separate  
zones.  
3.1.2 Familiarize yourself with the Controller and Vari-  
able Frequency Drive component names and loca-  
3.2 Positioning the ROBERTS GORDON®  
ULTRAVAC™ Controller and Variable Frequency  
Drive  
16.25"  
(41.3 cm)  
3.2.1 Choose a mounting location for the controller.  
For serviceability, it is convenient to mount the con-  
troller and variable frequency drive at occupant level  
in the vicinity of the pump. The variable frequency  
drive should not be more than 50' (15 m) from the  
pump.  
Do not mount controller or VFD outdoors. VFD  
must not be installed where subjected to adverse  
conditions such as: combustible, oily, or hazard-  
ous vapors or dust; excessive moisture or dirt;  
vibration. To avoid damage from possible drips,  
do not mount controller or VFD directly beneath  
pump. Models with NEMA 4 rated enclosures will  
withstand exposure to dust, dirt and water.  
13" (33 cm)  
VFD should be mounted in locations where the  
21 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
VFD75230 or VFD75230N4  
VFD20230 or VFD20230N4  
VFD75460 or VFD75460N4  
VFD20460 or VFD20460N4  
14 AWG  
12 AWG  
14 AWG  
14 AWG  
3.3 Cable Requirements:  
As per individual building specification for class of  
cable to be used. Use copper conductors only.  
VFD(0-10 Vdc) Speed Reference Control Wiring  
Shielded cable - one twisted pair of 22 AWG mini-  
mum or equivalent Belden #8451, #1503A; General  
Cable #C2514.  
3.3.1 ULTRAVAC™ Controller  
Below is the recommended cable for the various  
connections for ULTRAVAC™ Controller:  
Line Power Supply  
The power connection should be made with cable,  
size 14 AWG.  
3.3.4 Repeater  
Below is the recommended cable for the various  
connections for the repeater:  
Eight Digital Output (Relays)  
The control connection for load of each individual  
relay should be made with cable, size 16 AWG.  
Digital Input  
Line Power Supply  
The power connection should be made with cable,  
size 18 AWG.  
The wiring connection for the pressure switch  
should be unshielded cable, size 18 AWG.  
Indoor Sensor Cable  
a)Shielded cable - Four twisted pairs of stranded,  
24 AWG minimum or equivalent Madison Cable  
#08CFJ00004; Belden #9681.  
b)Unshielded cable - Four twisted pairs of stranded,  
24 AWG minimum or equivalent AMP#219538,  
#219513; Belden#1585, #1583A.  
RS485 Communications  
Multiple repeaters may be installed on the main loop  
and all communications cable should be made with  
shielded cable one twisted pair of 18-22 AWG.  
3.4 Electrical Installation Requirements of  
ULTRAVAC™ Controller  
DANGER  
Outdoor Sensor Cable  
Shielded cable - One twisted pair of 22 AWG mini-  
mum or equivalent Belden #8451, #1503A; General  
Cable #C2514.  
Communications between Multiple Controllers  
(RS-485)  
One twisted pairs of 18 AWG minimum or equiva-  
lent shield cable; Belden #1902, General Cable  
#C1670A.  
Electrical Shock Hazard  
Disconnect electric before service.  
3.3.2 ULTRAVAC™ BMS Link Controller  
Controller must be properly grounded to an  
electrical source.  
Below is the recommended cable for the various  
connections for ULTRAVAC™ BMS Link Controller:  
Line Power Supply  
The power connection should be made with cable,  
size 18 AWG.  
Communications between ULTRAVAC™ BMS  
Link and Multiple Controllers  
Failure to follow these instructions can  
result in death or electrical shock.  
• ULTRAVAC™ Controller must be feeding from a  
local fused isolator for a total amperage not  
exceeding 25 A.  
One twisted pair of 22 AWG minimum or equivalent  
shield cable; Belden #1902, General Cable  
#C1670A.  
• Eight digital outputs for each individual relay must  
not exceed 3 A.  
NOTES:  
3.3.3 Variable Frequency Drive (VFD)  
The total added current load for each individual  
relay must not exceed 3 A.  
• The total added current load for all 8 relays must  
not exceed 25 A.  
Below is the recommended cable for the various  
connections for VFD:  
Line Power Supply  
Input Wire Size Requirements  
VFD P/N  
Wire Size  
VFD75115 or VFD75115N4  
12 AWG  
22 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 3: INSTALLATION  
3.5 Pump Requirements  
The pump is powered directly from the Variable  
Frequency Drive (VFD). The VFD will be energized  
via an output from the relay board switched through a  
designated relay.  
3.6 Variable Frequency Drive Requirements  
The VFD must be powered separately from the  
control enclosure. The 230 V drive power supply  
must be 230 V, 50-60 Hz, 1 Ø. The 120V drive power  
supply must be 120 V, 50-60 Hz, 1 Ø. The 480 drive  
power supply must be 480 V, 50-60 Hz, 3 Ø. See  
Page 19, Section 2.7 for additional details. The VFD  
on/off switching is done by an output on the relay  
board. The 0-10 V signal from the ULTRAVAC™  
controller enclosure wired into VFD input relays 5 and  
14) will dictate the speed of the pump. The VFD  
output supply to the pump is 230 V 3 Ø 0-60 Hz for  
115 V and 230 V models and is 480 V, 3 Ø, 0-60 Hz  
for 480 V models. The frequency of the output supply  
signal to the pump will be varied based on the 0-10 V  
signal from the control enclosure. See Page 21, Sec-  
tion 3.2 for additional installation requirements.  
FIGURE 10: Variable Frequency Drive Mounting  
(Standard enclosures only, NEMA 4 enclosure  
mounting varies by model)  
14 .75"  
(37.5 cm)  
10" (25.4 cm)  
23 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
3.7 Indoor Sensor Placement  
or control board damage. Refer to Page 26, Figure  
13 and Page 28, Figure 14 for wiring details.  
The sensor measures the air temperature in the  
building. It is important that the sensor is located in  
an area within the heated zone at occupant level. For  
the most accurate results, sensors should be  
mounted on an inside wall, away from any air vents  
or other sources of heat and cold. In order to avoid  
short system cycles and inaccurate temperature  
readings, do not mount sensors under the first  
section of radiant tube (first 10' (3 m) section of tube  
after the burner), in direct sunlight or in the path of  
other sources of radiant heat. The sensors are suit-  
able for direct surface mounting or 4" (10.2 cm) x  
2.13" (5.4 cm) junction box mounting.  
3.8 Outdoor Sensor Placement  
The outdoor sensor measures air temperature out-  
side the building. It is important that the sensor is  
located on the outside of the building on the north  
facing wall. Failure to mount the sensor on the north  
facing wall will result in artificially high temperature  
readings. If possible, locate the sensor high under an  
eve to prevent incorrect readings from direct sunlight  
and damage due to the elements.  
FIGURE 12: Outdoor Sensor Placement  
North  
FIGURE 11: Indoor Sensor Mounting  
Mounting  
Hole  
Plug-in LCD  
Display  
(grasp here  
to unplug)  
Outside  
Sensor  
Setback  
Override  
Button  
Sensor  
Module  
facing down  
SEN SET  
O/R  
-
+
Setpoint  
Adjustment  
Slide bar  
Mount the outside sensor with the sensor module  
facing down to prevent accumulation of dirt or water.  
Mounting  
Hole  
3.9 Outside Air Supply  
If an outside air blower is to be used, See Page 26,  
Figure 13 for external wiring diagrams. See Page 22,  
Section 3.4 for current load.  
3.7.1 Indoor Sensor Mounting  
Remove the cover of the sensor by the two 1/16"  
allen screws, located in the lower corners of the  
cover. To gain access to the top mounting hole,  
remove the plug-in LCD display. To remove the LCD  
display, grasp the green plug-in board at the lower  
corners and gently pull the board away from the  
sensor back plate. See Page 24, Figure 11. After  
removing the plug-in LCD display from its socket,  
secure the sensor to the wall or junction box using  
the screws provided. Replace the plug-in LCD dis-  
play and secure the cover with the two 1/16" allen  
screws.  
Wiring from 32 V terminals on the controller to  
sensor power terminals "+" and "-" is polarity  
sensitive. Reversing polarity may cause sensor  
24 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
SECTION 4: TYPICAL EXTERNAL DIAGRAMS  
SECTION 4: TYPICAL EXTERNAL DIAGRAMS  
DANGER  
Electrical Shock Hazard  
Disconnect electric before service.  
Controller must be properly grounded to an  
electrical source.  
Failure to follow these instructions can  
result in death or electrical shock.  
25 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 13: ROBERTS GORDON® ULTRAVAC™ Central Controller External Wiring  
26 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 4: TYPICAL EXTERNAL DIAGRAMS  
ROBERTS GORDON® ULTRAVAC™ Central Controller External Wiring (continued)  
27 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 14: ROBERTS GORDON® ULTRAVAC™ Satellite Controller External Wiring  
28 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 4: TYPICAL EXTERNAL DIAGRAMS  
ROBERTS GORDON® ULTRAVAC™ Satellite Controller External Wiring (continued)  
29 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 5: COMMUNICATIONS  
One ROBERTS GORDON® ULTRAVAC™ Controller  
per building (called the "central controller") must  
have equipment for remote communications to a PC.  
This equipment consists of either a modem chip, an  
RS-485 converter, or a TCP/IP communications  
module.  
shielded twisted pair communication wiring.  
To interface with ULTRAVAC™ controllers through a  
Local Area Network (LAN), a TCP/IP Communication  
module is installed at controller #1. Controller #1 is  
wired to the LAN by an Ethernet cable. See Page 32,  
Section 5.3. Any computer on the LAN that has  
ULTRAVAC™ software installed can communicate  
with the controllers. Appropriate precautions must be  
taken to protect the Ethernet wiring from any possible  
electrical interference (noise) caused by surrounding  
machinery or equipment.  
For remote on-site and off-site control and system  
status viewing, the central controller (controller #1) is  
fitted with a modem chip. See Page 30, Section 5.1.  
If only remote on-site control and system status  
viewing is required, two controller communications  
interface devices are available: an RS-485 converter  
or a TCP/IP communication module.  
If multiple ULTRAVAC™ controllers are being used,  
the additional controllers communicate to controller  
#1 through communication wiring arranged in-series  
from one controller to the next. See Page 35, Section  
5.5.  
An RS-485 converter is installed at a single PC, this  
PC can interface with any controller on the network  
of ULTRAVAC™ controllers. The RS-485 converter at  
the PC is wired directly to controller #1 using  
FIGURE 15: Modem Location  
Dip Switch #1  
Set to ON  
Control Board of the  
Central Controller  
1 2 3 4 5 6 7 8  
+
-
+
-
+
-
+
-
+
-
+
-
PWR  
NC  
C
NO NC  
C
NO NC  
C
NO NC  
C
NO  
L2 L1  
24VAC  
OUT IN  
G
+32 +5  
G
G
G
REF  
OUT REF IN  
4
3
2
1
RS232 DIRECT  
AUX POWER  
RS485 COMM  
METER INPUTS  
Modem  
Chip  
RESET  
ADDRESS  
OH CD RI  
CPU  
Installed  
Modem Chip  
UNIVERSAL INPUTS  
8
7
6
5
4
3
2
1
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
IN  
NC  
C NO NC C NO NC C NO NC C NO  
OUT  
499 OHM  
10VDC  
OFF  
ON  
Phone Cable Connection  
Description  
Modem Chip  
Part Number  
10080142  
5.1 Dedicated Phone Line for Central Controller  
Modem  
If multiple ULTRAVAC™ controllers are being used, the  
The Central Controller is fitted with a modem chip. To additional controllers communicate to controller #1  
use the modem, the controller must have a phone through RS-485 communication wiring arranged  
line for modem communications. Install a phone line in-series from one controller to the next. See Page 35,  
near the location of the Central Controller. The phone Section 5.5 This allows multiple controllers to be  
cable is plugged into the phone connection in the controlled from a PC through a single communication  
.
corner of the control board. See Page 30, Figure 15. package at the central controller.  
If the modem option is not used for everyday commu-  
nication to the controller(s), it can still be plugged into  
a phone line for troubleshooting or programming  
assistance. Contact your local ROBERTS GOR-  
DON® independent distributor for details.  
30 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
SECTION 5: COMMUNICATIONS  
5.2 RS-485 Converter for Central Controller  
For remote on-site viewing of system status and  
settings of any controller, use the RS-485 converter  
to connect a single PC (9 pin serial port) to the RS-  
485 terminals on the Central Controller. This will  
allow communication between one PC and any of the  
ULTRAVAC™ controllers on the network. For RS-485  
converter wiring details see Page 31, Figure 16 and  
see Page 35, Section 5.5. Wiring between the RS-  
485 converter to the controller should not be more  
than 400' (122 m) in length.  
For communication cable requirements see Page 22,  
If multiple ULTRAVAC™ controllers are being used, the  
additional controllers communicate to controller #1  
through RS-485 communication wiring arranged  
in-series from one controller to the next. See Page 35,  
Section 5.5 This allows multiple controllers to be  
.
controlled from a PC through a single communication  
package at the central controller.  
FIGURE 16: RS-485 PC Connection  
Description  
Part Number  
RS-485 Converter Package with  
Power Supply  
10080430  
31 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
5.3 TCP/IP Communication Module  
from the controller to computers on the LAN via  
Ethernet cable plugged into the RJ45 jack on the  
module. A setup procedure must be performed on  
the module upon installation to create its IP address  
on the LAN. The setup instructions can be found in  
the ROBERTS GORDON® Software Manual (P/N  
10081600NA).  
For remote on-site viewing of system status and  
settings of any controller, use the TCP/IP communi-  
cation module to connect the controllers to a Local  
Area Network (LAN) via Ethernet cable. Any  
computer on the LAN that has ULTRAVAC™ soft-  
ware installed can be used to communicate with the  
controllers.  
For TCP/IP communication module wiring details, see  
.
The module must be mounted inside the  
ULTRAVAC™ central controller (controller #1)  
enclosure next to the control board. The power (5V)  
for the module will come from the ULTRAVAC™  
control board. The module will communicate to the  
controller via regular phone wire from the RJ11 jack  
on the module to the RS-232 direct connect port on  
the control board. The module will relay the data  
If multiple ULTRAVAC™ controllers are being used, the  
additional controllers communicate to controller #1  
through RS-485 communication wiring arranged  
in-series from one controller to the next. See Page 35,  
Section 5.5 This allows multiple controllers to be  
.
controlled from a PC through a single communication  
package at the central controller.  
FIGURE 17: TCP/IP Communication Module Mounting  
32 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 5: COMMUNICATIONS  
FIGURE 18: TCP/IP Communication Module Wiring  
It is important that the module power wire is connected as shown  
(black=5 V- / red= 5 V+) wire orientation. Make sure to verify  
connection before connecting to the control board.  
Description  
Part Number  
Kit, TCP/IP Communication  
10080440K  
5.4 Direct Connect  
For local viewing of system status and settings of any If a PC does not have a serial port, but does  
controller, a portable PC can be connected. Using have a USB port, purchase of a USB to Serial  
the 9 pin adapter provided, (See Page 34, Figure 19), Converter is required.  
you may connect from your computer serial port to  
A USB to 9-pin Serial Cable will allow connection  
the RS-232 direct connect port on the control board  
via standard 4-wire phone cable. For identification of  
the RS-232 direct connect port, see Page 18, Figure  
7. This can be useful when a PC is in close proximity  
to any ROBERTS GORDON® ULTRAVAC™ Control-  
ler or while troubleshooting at the controller using a  
laptop PC. This type of connector should not be used  
if the phone cable is more than 50’ (15 m) in length.  
between the RS-232 device (ULTRAVAC™ Control  
Board) and the USB port on the PC. The USB to  
serial RS232 DB9 Cable Adapter will be used in con-  
junction with the PC Connection Cable Package  
(P/N 10080410). USB to Serial RS232 DB9 Cable  
Adapters can be purchased at a local computer store  
or on the internet for $20.00 or less. The converter  
should come with drivers and should draw power  
directly from USB, requiring no additional power  
adapter.  
Plug one end of the phone cable into the RS-232  
direct port, plug the other end into the adapter shown  
in on Page 34, Figure 19. Plug the adapter into a 9-  
pin serial port on your computer.  
33 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 19: 9 Pin Adapter for PC  
Description  
Part Number  
PC Connection Cable Package  
10080410  
34 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 5: COMMUNICATIONS  
5.5 Communications Between Multiple ROBERTS GORDON® ULTRAVAC™ Controllers  
If more than one ROBERTS GORDON®  
system status and settings can be viewed for any of  
the controllers on the network.  
ULTRAVAC™ Controller is installed in a building, the  
controllers’ RS-485 communications must be wired in  
series. See Page 35, Figure 20. Connect the  
RS-485 terminal on controller #1 to the RS-485  
terminal on controller #2 and so on in a daisy chain  
fashion. For communication cable requirements,  
The control board identification dip switch must be  
set on each ROBERTS GORDON® ULTRAVAC™  
Controller. See Page 35, Figure 20 for dip switch  
settings. Contact Roberts-Gordon or your  
ROBERTS GORDON® independent distributor, if  
more than 20 controllers are connected.  
From a PC, by dialing into the modem on controller #1  
or by connecting to controller #1 via RS-485  
converter or TCP/IP communication module, the  
FIGURE 20: Communications Between Multiple Controllers  
Controller/Address Dip Switch Order (1,2,3,4,5,6,7,8)  
Controller/Address Dip Switch Order (1,2,3,4,5,6,7,8)  
Number  
Values (1=ON, 0=OFF)  
Number  
Values (1=ON, 0=OFF)  
1 (Central Controller)  
10000000  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
11010000  
2
3
01000000  
00110000  
11000000  
10110000  
4
00100000  
01110000  
5
10100000  
11110000  
6
01100000  
00001000  
7
11100000  
10001000  
8
00010000  
01001000  
9
10010000  
11001000  
10  
01010000  
00101000  
35 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
5.5.1 Repeater  
If the RS-485 communications wire length is above 4000' (1219 m), a repeater must be used to extend the  
signal. The repeater can also be used to install in different methods:  
To extend communications beyond the standard 4000' (1219 m) limitation. See Page 36, Figure 21.  
To add parallel branches of ROBERTS GORDON® ULTRAVAC™ controller communications bus wiring.  
NOTE: The maximum number of ROBERTS GORDON® ULTRAVAC™ Controllers that can be installed is  
242.  
FIGURE 21: Repeater External Wiring  
Description  
Part Number  
Repeater  
URVRP  
36 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 5: COMMUNICATIONS  
FIGURE 22: Repeater Communication Wiring Between Multiple Controllers  
Description  
Part Number  
Repeater  
URVRP  
37 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 6: ULTRAVAC™ BMS LINK CONTROLLER  
6.1 ULTRAVAC™ BMS Link Controller Overview  
Communication of data points from the ULTRAVAC™  
system to the building controls system help allow  
building managers and end users to easily integrate  
ULTRAVAC™ into a single controls solution shared  
between multiple mechanical systems in the building.  
ULTRAVAC™ BMS Link has an option of communi-  
cating to the building control system via BACnet®/IP,  
BACnet® MSTP or MODBUS® protocol. The standard  
ULTRAVAC™ BMS Link architecture is detailed on  
Many customers have building management control  
systems that manage multiple mechanical systems in  
the building such as heating, ventilation, lighting, etc.  
ULTRAVAC™ Controls run a stand-alone proprietary  
program. With the addition of an ULTRAVAC™ BMS  
LINK Controller, the ULTRAVAC™ system can com-  
municate with third party building management con-  
trol systems using BACnet® or MODBUS® protocol.  
FIGURE 23: Standard ULTRAVAC™ BMS Link Architecture  
38 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
SECTION 6: ULTRAVAC™ BMS LINK CONTROLLER  
FIGURE 24: ULTRAVAC™ BMS Link Controller Schematic  
6.2 ULTRAVAC™ BMS Link Controller  
Requirements  
of controllers. The ULTRAVAC™ BMS Link Controller  
is connected via communication wiring on the RS-  
485 communication bus to the ULTRAVAC™ central  
controller.  
The purpose of the ULTRAVAC™ BMS Link Control-  
ler is to integrate with a third party building control  
system. This building control system is provided by  
others and must be capable of communicating via  
one of the ULTRAVAC™ BMS Link communication  
protocols.  
The ULTRAVAC™ BMS Link Controller requires a  
115 V, 20 A dedicated power circuit. The control  
board identification dip switch must be set on each  
ULTRAVAC™ controller. See Page 41, Figure 25.  
This enables ULTRAVAC™ Controls to communicate  
with a variety of controls.  
For interface capability, one ULTRAVAC™ BMS Link  
Controller is needed for each ULTRAVAC™ network  
39 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
6.3 Technical Data  
• Power Supply: 120 VAC.  
• Frequency: 50/ 60 Hz.  
• Network Cable: Standard Ethernet Cables.  
• Communication Ports: RS-485 Communication Bus  
• Memory: Memory Card, SD 1GB.  
6.4 ULTRAVAC™ BMS Link Controller  
Programming  
Each ULTRAVAC™ BMS Link Controller is custom  
programmed before it is shipped. The custom pro-  
gram allows the controller to interface with the proper  
total number of ULTRAVAC™ Controls installed at  
the jobsite. The total number of ULTRAVAC™ Con-  
trols (including the central controller and all satellite  
controllers, but not including the ULTRAVAC™ BMS  
Link Controller) and the job name and location are  
submitted to Roberts-Gordon upon placing the order  
for the ULTRAVAC™ BMS Link Controller.  
Each ULTRAVAC™ BMS Link Controller is supplied  
with a printed report listing all of the available points.  
The information in the report must be communicated  
to the controls manager for use in configuring the  
third party building controls software. This documen-  
tation is intended for the contractor to leave with the  
controls manager or end user upon commissioning  
of the ULTRAVAC™ system. Refer to the  
ULTRAVAC™ BMS Link Controller User Manual  
included on our ULTRAVAC™ Software CD for onsite  
programming instructions.  
40 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 6: ULTRAVAC™ BMS LINK CONTROLLER  
FIGURE 25: Communication Between ULTRAVAC™ BMS Link Controller and Multiple ULTRAVAC™  
Controllers  
Controller Dip Switch Order (1,2,3,4,5,6,7,8) Address  
Controller Dip Switch Order (1,2,3,4,5,6,7,8) Address  
Number  
Values (1=ON, 0=OFF)  
Number  
Number  
Values (1=ON, 0=OFF)  
Number  
1 (Central  
Controller)  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
00110000  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
01000000  
2
10110000  
2
3
11000000  
00100000  
10100000  
01100000  
11100000  
00010000  
10010000  
01010000  
11010000  
3
4
01110000  
11110000  
4
5
00001000  
5
6
10001000  
6
7
01001000  
7
8
11001000  
8
9
00101000  
9
10  
11  
10101000  
10  
41 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 7: VARIABLE FREQUENCY DRIVE PROGRAMMING  
7. 1 V F D Pa r a m e t e r S e tt i n gs For Use With  
7. 1. 2  
ROBERTS GORDON® ULTRAVAC™  
Use the arrow buttons to scroll to the password value  
(the factory set password is 225).  
The VFD parameters come with factory default set-  
tings. The following parameter settings must be  
changed for ROBERTS GORDON® ULTRAVAC™.  
Settings can only be altered when the pump motor is  
stopped.  
Press Mode to enter password.  
Once the correct password value is entered, the dis-  
play will read "P01", which indicates that the  
PROGRAM mode has been accessed at the begin-  
ning of the parameter menu (P01 is the first  
parameter).  
Verify that there is power to the VFD (LCD display will  
be on) and no power to the 24 V power switch on the  
relay board of the ROBERTS GORDON®  
ULTRAVAC™.  
DANGER  
225  
P01  
Electrical Shock Hazard  
NOTE: If the display flashes "Er", the password was  
incorrect, and the process to enter the password  
must be repeated.  
Enclosure contains live electrical  
components.  
Programming must be done by a trained  
technician only.  
7. 1. 3 Use the arrow buttons to scroll to the desired  
parameter number. For new parameter settings, See  
Replace cover before operating.  
7. 1. 4 Once the desired parameter number is found:  
Failure to follow these instructions can result  
in death or electrical shock.  
Press Mode to display present parameter setting  
(example setting is 20.0).  
Upper right decimal point blinks.  
To override the rotary disconnect switch inside the  
VFD enclosure, turn the square rod with a wrench to  
the ON position. In order to be able to close the cover  
of the disconnect, the rods need to be turned back to  
the OFF position.  
Use arrow buttons to change setting.  
7. 1. 1  
Press Mode to store new setting and exit the  
program mode.  
To enter the PROGRAM mode and access the  
parameters, press the Mode button. This will activate  
the PASSWORD prompt (if the password has not  
been disabled).  
7.1.5 To change another parameter, press the  
Mode key again to re-enter the PROGRAM mode  
(the parameter menu will be accessed at the  
parameter that was last viewed or changed  
before exiting).  
Display reads "00"  
Upper right decimal point blinks  
If the Mode key is pressed within two minutes of exit-  
ing the PROGRAM mode, the password is not  
required to access the parameters. After two minutes,  
00  
42 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
SECTION 7: VARIABLE FREQUENCY DRIVE PROGRAMMING  
the password must be entered in order to access the  
parameters again.  
7. 2 A l t e r i n g VFD Parameters  
Using the procedure described on Page 42, Section  
7.1.1 through Section 7.1.5, alter the following parame-  
ters:  
Parameter Parameter Factory  
New  
Setting  
Number  
Name  
Default  
P01  
Line Voltage  
Start Method  
01  
01  
05  
P03  
01  
P05  
Standard  
Speed  
01  
(03) (0-10) Vdc  
(04) (4-20) mA  
Source  
P44  
P45  
Password  
225  
Any #  
000-999  
Speed at  
Minimum  
Signal  
0.0Hz  
Frequency  
Setting noted  
P46  
Speed at  
Maximum  
Signal  
60.0Hz  
Frequency  
Setting noted  
43 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 8: COMMISSIONING THE CORAYVAC® SYSTEM  
NOTE: The ROBERTS GORDON® ULTRAVAC™  
software must be installed on the PC, the communi-  
cation connection must be made to the controller and  
all wiring of the ROBERTS GORDON® ULTRAVAC™  
control boards, relay boards, burners, pumps and  
VFD must be completed before starting the commis-  
sioning procedure.  
vacuum readings in the remaining branches are  
proper. If necessary, adjust the proper damper cou-  
pling to achieve an end vent vacuum of 2.5" - 3.0" wc.  
See Page 45, Figure 26. Damper couplings should  
be found near the end of the radiant portion of the  
pipe in each branch or where a branch connects to  
other branches at a cross or tee. See Page 46, Fig-  
ure 27.  
8.1 Setting The CORAYVAC® End Burner Vacuum  
It is important to understand that the frequency that  
the VFD runs the motor at, determines the speed of  
the impeller in the pump. Variation of the impeller  
speed will increase or decrease vacuum in the sys-  
tem. The following procedure will help you set mini-  
mum and maximum VFD frequency settings to  
achieve proper vacuum in the system.  
Step 8.1.1 At the controller, turn on the 24 V power  
switch on the relay board. At the PC, "connect" to the  
controller (see the ROBERTS GORDON®  
ULTRAVAC™ Software Installation and Operation  
Manual, P/N 10081600NA for details) and then open  
the manual override screen(Alt + M). On the  
screen, click the "ON" button for the vacuum pump.  
Wait 30 seconds then click the ON button for zones 1-  
3.  
Step 8.1.2 The pump should be running and the  
burners should light within 60 seconds. At the VFD,  
verify that the number displayed on the LCD screen  
is "60.0" If it is lower than 60.0, hit the "up" arrow but-  
ton on the VFD until the number reads 60.0 Let the  
burners fire for approximately 20-30 minutes to warm  
up the system. Using a manometer, check the end  
vent vacuum in each zone (each branch of burners).  
If the lowest end vent vacuum reading is above 3.0"  
wc, reduce the vacuum pump speed. Generally, the  
lowest end vent vacuum reading is on the longest  
branch of the system. Use the down arrow button on  
the VFD to reduce the frequency of the output signal  
to the pump, thus reducing the pump speed and low-  
ering the end vent vacuum reading. Continue to  
reduce the frequency until the end vent vacuum read-  
ing is between 2.5" - 3.0" wc. Make note of this fre-  
quency setting below. The frequency is found on the  
VFD’s LCD screen.  
2.5" wc - 3.0" wc VFD Frequency Setting  
Record Frequency Setting Here:  
To avoid damage to the pump motor, do not adjust  
the frequency above 60.0 Hz. Verify that the end vent  
44 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
SECTION 8: COMMISSIONING THE CORAYVAC® SYSTEM  
FIGURE 26: End Vent Vacuum  
Combustion Chamber  
at end burner position  
End Vent  
Insert tubing  
about 6" (15cm)  
into end vent.  
6
5
4
3
2
1
0
1
2
3
4
5
6
Manometer  
Approximate reading after adjusting  
VFD frequency setting and/or  
~
damper couplings. ( 2.5"-3" wc)  
~
45 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 27: Possible Damper Couplings’ Locations  
46 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 8: COMMISSIONING THE CORAYVAC® SYSTEM  
Step 8.1.3 After setting end vent vacuums between  
2.5" wc and 3.0" wc, while all the burners are still  
operating, use the down arrow button on the VFD to  
reduce the frequency of the output signal to the  
pump. Reduce the frequency of the VFD until the  
manometer at each of the end vents reads 1.0" wc -  
1.2" wc, Make note of this frequency setting below.  
The frequency is found on the VFD’s LCD screen.  
1.0" w.c. - 1.2" wc VFD Frequency Setting  
Record Frequency Setting Here:  
Step 8.1.4 Return to the PC and click the pump and  
zones to "OFF".  
Step 8.1.5 Using the procedure described on Page  
lowing parameters on the VFD:Return to the PC and  
click the vacuum pump and three zones to "AUTO",  
then click exit.  
Parameter Parameter Factory  
New  
Setting  
Number  
Name  
Default  
P01  
Line Voltage  
Start Method  
01  
01  
05  
P03  
01  
P05  
Standard  
Speed  
01  
(03) (0-10) Vdc  
(04) (4-20) mA  
Source  
P44  
P45  
Password  
225  
Any #  
000-999  
Speed at  
Minimum  
Signal  
0.0Hz  
Frequency  
Setting noted  
P46  
Speed at  
Maximum  
Signal  
60.0Hz  
Frequency  
Setting noted  
47 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 9: TROUBLESHOOTING  
DANGER  
Electrical Shock Hazard  
Disconnect electric before service.  
More than one disconnect switch may be  
required to disconnect electric to the unit.  
Failure to follow these instructions can result  
in death or electrical shock.  
WARNING  
Explosion Hazard  
Turn off gas supply to heater before service.  
Failure to follow these instructions can result  
in death, injury or property damage.  
48 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 9: TROUBLESHOOTING  
FIGURE 28: Troubleshooting Flow Chart  
49 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
Troubleshooting Flow Chart (continued)  
50 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: TROUBLESHOOTING  
Troubleshooting Flow Chart (continued)  
51 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
Troubleshooting Flow Chart (continued)  
52 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: TROUBLESHOOTING  
FIGURE 29: Troubleshooting Flow Chart - Repeater  
53 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
FIGURE 30: Troubleshooting Flow Chart - BACnet®  
54 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 10: REPLACEMENT PARTS  
SECTION 10: REPLACEMENT PARTS  
WARNING  
DANGER  
Electrical Shock Hazard  
Explosion Hazard  
Carbon Monoxide Hazard  
Fire Hazard  
Use only genuine ROBERTS GORDON® replacement parts per this installation, operation and  
service manual.  
Failure to follow these instructions can result in death, electric shock, injury or property damage.  
55 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
10.1 ROBERTS GORDON® ULTRAVAC™ Controller Replacement Parts  
Caution: Use only genuine ROBERTS GORDON® replacement parts. Use of parts not specified by  
Roberts-Gordon voids warranty.  
FIGURE 31: ROBERTS GORDON® ULTRAVAC™ Controller Components Diagram  
24 V  
Power  
1 A Fuse  
24 V  
Power  
Switch  
Relay  
Board  
Plug-In  
Relays  
Reset  
Button  
Control  
Board  
Analog  
Output  
Board  
Modem Chip  
(only located on  
Central Controller)  
Description  
Control Board (150 style)  
Relay Board  
Analog Output Board  
URV Eprom Chip (150 Style, current version)  
Plug-In Relay  
Modem Chip (located only on central controller)  
1 A Fuse (Relay Board)  
ROBERTS GORDON® ULTRAVAC™ Indoor Sensor °F (not shown)  
ROBERTS GORDON® ULTRAVAC™ Outdoor Sensor (not shown)  
ROBERTS GORDON® ULTRAVAC™ Indoor Sensor °C (not shown)  
PC Connection Cable Package (not shown)  
RS-485 Converter Package (not shown)  
Kit, TCP/IP Communication Module (not shown)  
Telephone Sharing Device, 4 port  
Part Number  
10080102  
10080200  
10080141  
10080122  
10080212  
10080142  
10080211  
10081500  
10081501  
10081502  
10080410  
10080430  
10080440K  
10080600  
56 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 10: REPLACEMENT PARTS  
Description  
Part Number  
Relay 120 V Unitary  
07100  
Lights for 150 Style Control Board  
Lamp Green Enclosure Mount w/o Light  
Lamp Red Enclosure Mount w/o Light  
Light Diode 24 Vac  
91321614  
91321615  
91321616  
10.2 Variable Frequency Drive Replacement Parts  
Caution: Use only genuine ROBERTS GORDON® replacement parts. Use of parts not specified by  
Roberts-Gordon voids warranty.  
FIGURE 32: Variable Frequency Drive Components Diagram  
Variable  
Power Input  
Frequency Drive  
(1 Ø input model shown)  
L1  
L2/N  
PE  
B-  
B+  
Rotary  
Dissconnect  
Base Block  
Relay  
120 V  
Fuse  
Holder  
Levers  
M16/12.P  
U
V
W
PE  
PE  
Grounding  
Block  
Input Fuse Holder  
(1 Ø input model shown, 3 Ø input  
models have an additional input  
fuse holder and VFD power input.)  
Description  
Part Number  
10081201  
10081202  
10081203  
10081204  
10081205  
90429100  
91321410  
91321425  
91321300  
91321400  
91321550  
91321551  
91321552  
Variable Frequency Drive, 1 HP, 120 V, 1 Ø Input (for use with EP-203)  
Variable Frequency Drive, 3/4 HP, 230 V, 1 Ø Input (for use with EP-203)  
Variable Frequency Drive, 2 HP, 230 V, 1 Ø Input (for use with EP-303)  
Variable Frequency Drive, 1 HP, 480 V, 3 Ø Input (for use with EP-203)  
Variable Frequency Drive, 2 HP, 480 V, 3 Ø Input (for use with EP-303)  
Relay, 120 V  
Fuse 10 A (for.75 HP 230 V VFD, 1 HP 480 V VFD and 2 HP 480 V VFD)  
Fuse 25 A (for 1 HP 120 V VFD and 2 HP 230 V VFD)  
Grounding Block  
Fuse Holder  
Rotary Disconnect Base Block  
Rotary Disconnect Handle (not shown)  
Rotary Disconnect Rod (not shown)  
57 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
10.3 ULTRAVAC™ BMS Link Controller Replacement Parts  
FIGURE 33: ULTRAVAC™ BMS Link Controller Components Diagram  
Description  
Communication Module  
Supervisor Board  
Module NetBurner  
Circuit Breaker 5A  
Transformer 100VA001  
Memory Card, SD, 16 GB  
Fuse Micro, 125 V, 1/4A  
Part Number  
10081610  
10081630  
10081640  
10081650  
10081660  
10081680  
10081690  
58 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 10: REPLACEMENT PARTS  
10.4 Repeater Replacement Parts  
FIGURE 34: Repeater Components Diagram  
Description  
Repeater  
Circuit Breaker 5A  
Transformer  
Micro Fuse, 125 V, 1/4A  
Part Number  
10080445  
10081650  
10081661  
10081690  
59 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
10.5 Replacement Parts Instructions  
the doors.  
DANGER  
10.5.4 24V Power 1 A Fuse  
To replace the 1 A fuse, turn off power to the relay  
board and turn off the 24 V power switch on the relay  
board.  
Locate the 1A fuse and remove it from its socket  
using a flathead screwdriver. Twist the fuse a 1/4 turn  
counter-clockwise until the fuse pops out of the  
socket. Replace it with a new fuse.  
Electrical Shock Hazard  
Disconnect electric before service.  
Slide the fuse back into the socket, press down and  
turn the fuse a 1/4 turn clockwise until secure.  
Controller must be properly grounded to an  
electrical source.  
Return 120 V power to the relay board and turn on  
the 24 V power switch on the relay board. Press the  
reset button on the control board and close the doors.  
Failure to follow these instructions can  
result in death or electrical shock.  
10.5.1 Plug-In Relay  
10.5.5 Variable Frequency Drive (VFD)  
To replace the plug-in relay, turn off 120 V power to  
the relay board. Turn off the 24 V power switch on the To replace the Variable Frequency Drive, turn off all  
relay board. Locate the malfunctioning relay and pull power to the drive assembly at the breaker or discon-  
the relay from its socket.  
nect switch. Turn off 120 V power to the relay board  
inside the ROBERTS GORDON® ULTRAVAC™ Con-  
troller. Turn off the 24 V power switch on the relay  
board.  
Fit a new relay in the socket. Return 120 V power to  
the relay board and turn on the 24 V power switch on  
the relay board. Press the reset button on the control  
board and close the doors.  
Mark all wires connected to the VFD, noting the ter-  
minals that they are secured to. Remove all wires  
from the VFD terminals.  
10.5.2 Control Board Power LED  
Remove the VFD from its mounting plate by remov-  
ing the four securing screws.  
The LED is linked to the 24 Vac input which supplies  
the control board with power. If the LED is not lit,  
there is no power to the board. If this is the case,  
check the 120 V power wiring to the relay board, the  
24 Vac power wiring from the relay board to the con-  
trol board and the 24 V power 1 A fuse.  
Verify that the input voltage noted on the rating plate  
of the VFD matches the input voltage of the old VFD.  
Secure the new VFD to the mounting plate with the  
four screws. Return all wires to the correct VFD ter-  
minals. If possible, it may be easier to partially re-  
wire the new VFD before mounting it to the mounting  
plate.  
10.5.3 10080122 Eprom Chip  
The Eprom is where the controller's program  
(not settings) is stored. To take out the Eprom.  
The following steps must be taken:  
Close the door and return power to the VFD. Return  
120 V power to the relay board. Turn on the 24 V  
power switch on the relay board. Press the reset but-  
ton on the control board and close the doors.  
Turn off the power to the control board by turning off  
the 24 V power switch on the relay board.  
Locate the Eprom and with a small terminal screw  
driver placed underneath the device, pry the Eprom  
out of the socket.  
10.5.6 Variable Frequency Drive 25 A or 10 A Fuse  
To replace a fuse, turn off input power to the variable  
frequency drive assembly at the breaker or  
disconnect switch.  
To fit a new Eprom, look for the notch on one end of  
the Eprom.There is a notch on the socket and a  
notch on the Eprom. The Eprom should be fit so that  
the notch on the socket and the Eprom are aligned.  
Turn off 120 V power to the relay board inside the  
ROBERTS GORDON® ULTRAVAC™ Controller. Turn  
off the 24 V power switch on the relay board.  
Turn on the 24 V power switch on the relay board,  
press the reset button on the control board and close  
Inside the VFD assembly, open the fuse holder by  
60 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 10: REPLACEMENT PARTS  
pulling down the lever to expose the fuse. Remove  
the old fuse and insert a new fuse. Verify the correct  
fuse rating, 25 A for 1 HP 120 V VFD or 2 HP 230 V  
VFD, 10 A for the.75 HP 230 V VFD, 1 HP 480 V VFD  
and 2 HP 480 V VFD. Close the fuse holder. Return  
power to the VFD assembly and verify that the VFD  
LCD screen is on. (dashes displayed). Close the  
VFD assembly door.  
Return 120 V power to the relay board. Turn on 24 V  
power switch on the relay board. Press the reset but-  
ton on the control board and close the doors.  
61 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
ROBERTS GORDON ULTRAVAC™ CONTROLLER INSTALLATION MANUAL  
SECTION 11: THE ROBERTS GORDON® ULTRAVAC™ LIMITED WARRANTY  
Within 36 months from date of purchase by buyer or 42  
months from date of shipment by Roberts-Gordon  
READ YOUR INSTALLATION, OPERATION AND  
SERVICE MANUAL.  
If you have questions about your control, contact your  
installing professional. Should you need Replacement  
Parts or have additional questions, call or write:  
(whichever occurs first), replacement parts will be provided  
free of charge for any part of the product which fails due to  
a manufacturing or material defect.  
Roberts-Gordon will require the part in question to be  
returned to the factory. Roberts-Gordon will, at its sole  
discretion, repair or replace after determining the nature of  
the defect and disposition of part in question.  
Roberts-Gordon  
ROBERTS GORDON® Replacement Parts are warranted 1250 William Street  
for a period of 12 months from date of shipment from  
Roberts-Gordon or the remaining ROBERTS GORDON®  
System Control warranty.  
ROBERTS-GORDON WILL NOT PAY FOR:  
Service trips, service calls and labor charges.  
P. O. B ox 4 4  
Buffalo, New York 14240-0044  
716.852.4400  
On the web at: www.rg-inc.com  
Shipment of replacement parts.  
Claims where the total price of the goods have not  
been paid.  
Damage due to:  
• Improper installation, operation or maintenance.  
• Misuse, abuse, neglect, or modification of the  
ROBERTS GORDON® ULTRAVAC™ in any way.  
• Use of the ROBERTS GORDON® ULTRAVAC™ for  
other than its intended purpose.  
Roberts-Gordon's liability, and your exclusive remedy,  
under this warranty or any implied warranty (including  
the implied warranties of merchantability and fitness  
for a particular purpose) is limited to providing  
replacement parts during the term of this warranty.  
Some jurisdictions do not allow limitations on how long an  
implied warranty lasts, so this limitation may not apply to  
you. There are no rights, warranties or conditions,  
expressed or implied, statutory or otherwise, other than  
those contained in this warranty.  
• Incorrect gas or electrical supply, accident, fire, floods,  
acts of God, war, terrorism, or other casualty.  
• Improper service, use of replacement parts or acces-  
sories not specified by Roberts-Gordon.  
• Failure to install or maintain the ROBERTS GORDON®  
ULTRAVAC™ as directed in the Installation, Operation  
and Service Manual.  
• Relocation of the ROBERTS GORDON® ULTRAVAC™  
after initial installation  
• The use of the ROBERTS GORDON® ULTRAVAC™ in  
Roberts-Gordon shall in no event be responsible for  
incidental or consequential damages or incur liability  
for damages in excess of the amount paid by you for  
the ROBERTS GORDON® ULTRAVAC™. Some  
jurisdictions do not allow the exclusion or limitation of  
incidental or consequential damages, so this limitation or  
exclusion may not apply to you. This warranty gives you  
specific legal rights, and you may also have other rights  
which vary from jurisdiction to jurisdiction.  
a corrosive atmosphere containing contaminants.  
Roberts-Gordon shall not be responsible for failure to  
perform under the terms of this warranty if caused by  
circumstances out of its control, including but not limited to  
war, fire, flood, strike, government or court orders, acts of  
God, terrorism, unavailability of supplies, parts or power.  
No person is authorized to assume for Roberts-Gordon  
any other warranty, obligation or liability.  
• The use of the ROBERTS GORDON® ULTRAVAC™ in  
the vicinity of a combustible or explosive material.  
• Any defect in the ROBERTS GORDON® ULTRAVAC™  
arising from a drawing, design, or specification sup-  
plied by or on behalf of the consumer.  
• Damage incurred during shipment. Claim must be filed  
with carrier.  
LIMITATIONS ON AUTHORITY OF  
REPRESENTATIVES:  
No representative of Roberts-Gordon, other than an  
Executive Officer, has authority to change or extend these  
provisions. Changes or extensions shall be binding only if  
confirmed in writing by Roberts-Gordon's duly authorized  
Executive Officer.  
WARRANTY IS VOID IF:  
The ROBERTS GORDON® ULTRAVAC™ is not installed  
by an electrician qualified in the installation and service of  
control systems for heating equipment.  
You cannot prove original purchase date and required  
annual maintenance history.  
The data plate and/or serial number are removed,  
defaced, modified or altered in any way.  
The ownership of the ROBERTS GORDON®  
ULTRAVAC™ is moved or transferred. This warranty is  
nontransferable.  
Roberts-Gordon is not permitted to inspect the damaged  
controller and/or component parts.  
62 of 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

QSC Audio Speaker System SR 46 User Guide
QVS Surge Protector PP103 12C User Guide
Radio Shack Cordless Telephone 43 3558 User Guide
Radio Shack Work Light 270 019 User Guide
RCA CRT Television F20TF20 User Guide
Rotel Car Stereo System RDA975 User Guide
Russound Home Theater Server SMS3 User Guide
Samsung Computer Drive SH S223L User Guide
Sanyo Flat Panel Television LCD 19E30A User Guide
Scotsman Ice Furnace DB 101 User Guide