Regency Indoor Fireplace L900E NG User Guide

TM  
Owners &  
LIBERTY L900E Gas Fireplace  
Installation Manual  
Unit requires 120V to  
operate. See “Wiring Diagram”  
section in manual for more  
details. Receptacle is included  
with manual package.  
MODELS: L900E-NG Natural Gas L900E-LP Propane  
FOR YOUR SAFETY  
WARNING:  
What to do if you smell gas:  
Iftheinformationintheseinstructionsarenotfollowedexactly,  
a fire or explosion may result causing property damage,  
personal injury or loss of life.  
Do not try to light any appliance  
Do not touch any electrical switch:  
do not use any phone in your  
building.  
Immediately call your gas supplier  
from a neighbour's phone. Follow  
the gas supplier's instructions.  
If you cannot reach your gas  
supplier, call the fire department.  
FOR YOUR SAFETY  
Do not store or use gasoline or other flammable vapors and  
liquids in the vicinity of this or any other appliance.  
Installation and service must be performed by a qualified  
installer, service agency or the gas supplier.  
Tested by:  
Installer: Please complete the details on the back cover  
and leave this manual with the homeowner.  
Homeowner: Please keep these instructions for future reference.  
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4  
01/07/08  
918-623a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
High Elevation .............................................................26  
Gas Line Installation....................................................26  
Pilot Adjustment...........................................................26  
Gas Pipe Pressure Testing..........................................26  
SIT 845 Valve Description ...........................................26  
Aeration Adjustment ....................................................26  
Back-Up Battery Installation........................................27  
Brick Panel Installation................................................28  
Log Set Installation......................................................30  
Wiring Diagram ...........................................................32  
SAFETY LABEL  
Copy of Safety Decal.....................................................4  
REQUIREMENTS  
MA Code - CO Detector  
(for the State of Massachusetts only)............................5  
UNIT DIMENSIONS  
OPERATING INSTRUCTIONS  
Unit Dimensions ............................................................6  
Matching Remote Handset & Control Box ID Code ....33  
Operating Instructions .................................................33  
First Fire ......................................................................33  
Lighting Procedure ......................................................33  
Shutdown Procedure...................................................33  
Normal Operating Sounds of Gas Appliances.............34  
Operation During Power Outage.................................34  
Backup Battery............................................................34  
Copy of Lighting Plate Instructions..............................35  
Maintenance Instructions ............................................36  
General Vent Maintenance..........................................36  
Log Replacement ........................................................36  
Glass Gasket...............................................................36  
INSTALLATION  
Important Message ......................................................7  
Before You Start ............................................................7  
General Safety Information ...........................................7  
Installation Checklist......................................................7  
Manufactured Mobile Home Additional Requirements ..8  
Locating Your Gas Fireplace .........................................8  
Heatwave Duct Kit ........................................................8  
Heat Release Kit ..........................................................8  
Hearth Requirements ....................................................8  
Clearances ....................................................................9  
Mantel Clearances ......................................................10  
Mantel Leg Clearances ...............................................10  
Framing & Finishing ....................................................11  
Unit Assembly Prior To Installation ..............................12  
Top Standoff Assembly ........................................12  
Side Nailing Strips ...............................................12  
Finishing Template.......................................................12  
Venting Introduction.....................................................13  
Vent Restrictor Position...............................................13  
Exterior Vent Termination Requirements.....................14  
Venting Arrangements ................................................15  
Horizontal Termination (Flex)...............................15  
Rigid Pipe Venting Systems ........................................16  
Basic Horizontal & Vertical Terminations .............16  
5” x 8” Rigid Pipe Cross Reference Chart...................17  
Venting Arrangements ................................................19  
Allowable Horizontal Terminations.......................19  
Venting Arrangements ................................................22  
Allowable Vertical Terminations ...........................22  
Unit Installation with Horizontal Termination................23  
Unit Installation with Vertical Termination ....................24  
Horizontal Termination with Flex Vent System ............25  
MAINTENANCE  
Door Glass ..................................................................36  
Glass Replacement.....................................................36  
Back-up Battery Replacement.....................................37  
Control Box Replacement ...........................................37  
Valve Tray Replacement..............................................39  
PARTS LIST  
Main Assembly ............................................................41  
Burner & Log Assembly...............................................42  
WARRANTY  
The Warranty: Limited Lifetime ...................................43  
Regency® L900E Direct Vent Gas Fireplace  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY LABEL  
This is a copy of the label that accompanies  
each L900E-NG and L900E-LP Direct Vent  
Gas Fireplace. We have printed a copy of the  
contents here for your review. The safety label  
is located on the right hand side of the unit,  
visible when the exterior right side brick panel  
is removed.  
`
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ETIQUETTE  
322  
Serial No. / No de serie  
Listed: VENTED GAS FIREPLACE  
Tested to: ANSI Z21.88-2005/CSA 2.33-2005, CAN/CGA-2.17-M91,  
ANSI Z21.50-2003/CSA 2.22-2003, ANSI Z21.50A-2003/  
CSA 2.22A-2003, ANSI Z21-50B-2003/CSA Z22b-2003  
Certified for / Certifiée pour: CANADA AND U.S.A.  
NOTE: Regency® units are constantly being  
improved. Check the label on the unit and if  
there is a difference, the label on the unit is  
the correct one.  
NATURAL GAS FIREPLACE: MODEL L900E-NG  
Factory Equipped For Altitude 0-4500ft. (0-1372m)  
Min. Supply Pressure  
Low Setting Man. Pressure  
Max. Manifold Pressure  
Orifice Size (Front Burner)  
Orifice Size (Back Burner)  
Minimum Input  
5“  
1.6"  
3.5"  
#47  
#30  
11,000  
48,000  
WC  
WC  
WC  
DMS  
DMS  
Btu/h (3.22 kW)  
Btu/h (14.06 kW)  
(1.25 kpa)  
(0.39 kpa)  
(0.87 kpa)  
Maximum Input  
PROPANE GAS FIREPLACE: MODEL L900E-LP  
Factory Equipped For Altitude 0-4500ft. (0-1372m)  
Min. Supply Pressure  
Low Setting Man. Pressure  
Max. Manifold Pressure  
Orifice Size (Front Burner)  
Orifice Size (Back Burner)  
Minimum Input  
12"  
3.6"  
10"  
#56  
#50  
9,500  
46,500  
WC  
WC  
WC  
(2.98 kpa)  
(0.9 kpa)  
(2.49 kpa)  
DMS  
DMS  
Btu/h (2.78 kW)  
Btu/h (13.62 kW)  
Maximum Input  
VENTED GAS FIREPLACE  
This appliance must be installed in accordance with the manufacturer’s installation  
instructions and with local codes, if any; if none, follow the current ANSI Z223.1 in  
the USA or the current CAN 1-B149 in Canada.  
This vented gas fireplace is not for use with air filters.  
For Manufactured Home Installation: This Direct Vent System Appliance must be  
installed in accordance with the manufacturer's installation instructions and  
Manufactured Home Construction and Safety Standard Title 24 CFR, Part 3280, or the  
current Standard for Fire Safety Criteria for Manufactured Home Installation, Sites, and  
CommunitiesANSI/NFPA501A, and with CAN/CSAZ240 MH Mobile Home Standard in  
Canada.  
This appliance is only for use with the type of gas indicated on the rating plate and may  
be installed in an aftermarket, permanently located, manufactured (mobile) home  
where not prohibited by local codes. See owner's manual for details. This appliance is  
notconvertible foruse with other gases, unless acertified kitisused (Kit#546-969).  
Certified foruse with Heat Wave (Kit#946-556) and Heat Release (Kit#946-570).  
Foruse with glass doors certified with theappliance only.  
Electrical Supply: 120 V, 0.22 A, 60 Hz  
NOT FOR USE WITH SOLID FUEL  
Minimum Clearances to Combustibles from Fireplace  
Side Walls  
For the State of Massachusetts, installation  
and repair must be done by a plumber or  
gasfitter licensed in the Commonwealth of  
Massachusetts.  
*A 16"  
(406mm)  
Ceiling  
B
C
49"  
(1245mm)  
B
Min. Mantel Height  
Max. Mantel Depth  
Alcove Width  
Alcove Depth  
17-1/2" (445mm)  
D
F
**D 13”  
E
F
(330mm)  
(2134mm)  
(914mm)  
For the State of Massachusetts, flexible  
connectors shall not exceed 36 inches in  
length.  
84"  
36"  
A
I
C
H
Non-Combustible Hearth Extension  
G
E
For the State of Massachusetts, the appli-  
ances individual manual shut-off must be a  
t-handle type valve.  
Hearth Height  
Hearth Width  
G
H
2"  
(51mm)  
33-1/8” (841mm)  
* Alcove side wall must have a min. of 16” (406mm) clearance on one side.  
** Mantel depth taken at 27-1/2” (699mm) from front facing.  
The State of Massachusetts requires the  
installation of a carbon monoxide alarm in  
accordance with NFPA720 and a CO alarm  
withbatterybackupinthesameroomwhere  
the gas appliance is installed.  
FPI Fireplace Products International Ltd., Delta BC, CANADA  
MADE IN CANADA / FABRIQUE AU CANADA  
918-624  
Regency® L900E Direct Vent Gas Fireplace  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
REQUIREMENTS  
MA Code - CO Detector  
(for the State of Massachusetts only)  
5.08: Modifications to NFPA-54, Chapter 10  
(2) Revise 10.8.3 by adding the following additional requirements:  
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for  
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than  
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall  
be satisfied:  
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled  
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is  
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery  
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure  
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of  
qualified licensed professionals for the installation of hard wired carbon monoxide detectors  
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon  
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.  
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of  
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon  
monoxide detector with an alarm shall be installed.  
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions  
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight  
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The  
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL  
OBSTRUCTIONS".  
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation  
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR  
5.08(2)(a)1 through 4.  
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by  
the Board; and  
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or  
structure used in whole or in part for residential purposes.  
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product  
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the  
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:  
1. Detailed instructions for the installation of the venting system design or the venting system components; and  
2. A complete parts list for the venting system design or venting system.  
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a  
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies  
"special venting systems", the following requirements shall be satisfied by the manufacturer:  
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and  
detailed installation instructions.  
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,  
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of  
the installation.  
Regency® L900E Direct Vent Gas Fireplace  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS  
UNIT DIMENSIONS  
Regency® L900E Direct Vent Gas Fireplace  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
12) Installationandanyrepairstothisappliance  
should be done by an authorized service  
person.Aprofessionalservicepersonshould  
be called to inspect this appliance annually.  
Make it a practice to have all of your gas  
appliances checked annually.  
YOUNG CHILDREN SHOULD BE  
CAREFULLY SUPERVISED WHEN  
THEY ARE IN THE SAME ROOM AS  
THE APPLIANCE.  
IMPORTANT MESSAGE  
SAVE THESE  
INSTRUCTIONS  
The L900E Direct Vent Fireplace must be  
installed in accordance with these instructions.  
Carefully read all the instructions in this manual  
first.Consultthe"authorityhavingjurisdiction"to  
determine the need for a permit prior to starting  
the installation. It is the responsibility of the  
installer to ensure this fireplace is installed in  
compliancewithmanufacturersinstructionsand  
all applicable codes.  
CLOTHINGOROTHERFLAMMABLE  
MATERIALSHOULDNOTBEPLACED  
ON OR NEAR THE APPLIANCE.  
13) Do not slam shut or strike the glass door.  
14) Under no circumstances should any solid  
fuels (wood, paper, cardboard, coal, etc.)  
be used in this appliance.  
15) The appliance area must be kept clear and  
free of combustible materials, (gases and  
other flammable vapours and liquids).  
GENERAL SAFETY  
INFORMATION  
1) The appliance installation must conform  
with local codes or, in the absence of local  
codes,withthecurrentCanadianorNational  
Gas Codes, CAN1-B149 or ANSI Z223.1  
Installation Codes.  
Emissions from burning wood or gas could  
contain chemicals known to the State of  
California to cause cancer, birth defects or  
other reproductive harm.  
BEFORE YOU START  
Safe installation and operation of this appliance  
requires common sense, however, we are  
required by the Canadian Safety Standards  
and ANSI Standards to make you aware of  
the following:  
2) The appliance when installed, must be  
electrically grounded in accordance with  
localcodes, orintheabsenceoflocalcodes  
with the current National Electrical Code,  
ANSI/NFPA 70 or CSA C22.1 Canadian  
Electrical Code.  
INSTALLATION  
CHECKLIST  
INSTALLATION AND REPAIR SHOULD  
BE DONE BY AN AUTHORIZED  
SERVICE PERSON. THE APPLIANCE  
SHOULD BE INSPECTED BEFORE  
USE AND AT LEAST ANNUALLY BY A  
PROFESSIONAL SERVICE PERSON.  
MORE FREQUENT CLEANING MAY  
BE REQUIRED DUE TO EXCESSIVE  
LINT FROM CARPETING, BEDDING  
MATERIAL, ETC. IT IS IMPERATIVE  
THAT CONTROL COMPARTMENTS,  
BURNERS AND CIRCULATING AIR  
PASSAGEWAYS OF THE APPLIANCE  
BE KEPT CLEAN.  
1) Locate appliance  
3) See general construction and assembly  
instructions. The appliance and vent should  
be enclosed.  
a) Room location (Refer to "Locating Your  
Gas fireplace" section)  
b) Clearances to Combustibles (Refer to  
"Clearances" section)  
4) This appliance must be connected to the  
specified vent and termination cap to the  
outsideofthebuildingenvelope. Nevervent  
to another room or inside a building. Make  
sure that the vent is fitted as per Venting  
instructions.  
c) Mantle Clearances (Refer to "Mantel  
Clearances" section)  
d) Framing & Finishing Requirements  
(Refer to "Framing & Finishing"  
section)  
e) Venting Requirements (Refer to  
"Venting" section)  
5) Inspect the venting system annually for  
blockage and any signs of deterioration.  
2) Assemble Top Standoffs (Refer to "Unit  
Assembly Prior to Installation).  
6) Venting terminals shall not be recessed into  
a wall or siding.  
DUE TO HIGH TEMPERATURES, THE  
APPLIANCE SHOULD BE LOCATED  
OUT OF TRAFFIC AND AWAY FROM  
FURNITURE AND DRAPERIES.  
3) Install back-up batteries. Refer to "Back-up  
Battery Installation" section.  
7) Any safety glass removed for servicing  
must be replaced prior to operating the  
appliance.  
4) Slide unit into place.  
5) Installvent(Referto"Venting Arrangement"  
8) To prevent injury, do not allow anyone who  
is unfamiliar with the operation to use the  
fireplace.  
WARNING: FAILURE TO INSTALL THIS  
APPLIANCE CORRECTLY WILL VOID  
YOUR WARRANTY AND MAY CAUSE  
A SERIOUS HOUSE FIRE.  
sections).  
6) Make gas connections (Refer to "Gas Line  
Installation section).  
9) Wearglovesandsafetyglassesforprotection  
while doing required maintenance.  
7) Makeelectricalconnections(Referto"Wiring  
Diagram" section). NOTE: Unit requires  
120V to operate.  
CHILDREN AND ADULTS SHOULD BE  
ALERTED TO THE HAZARDS OF HIGH  
SURFACE TEMPERATURES, ESPE-  
CIALLY THE FIREPLACE GLASS, AND  
SHOULDSTAYAWAYTOAVOIDBURNS  
OR CLOTHING IGNITION.  
10) Be aware of electrical wiring locations in  
walls and ceilings when cutting holes for  
termination.  
8) Test the pilot (Refer to "Pilot Adjustment"  
section).  
11) Under no circumstances should this  
appliancebemodified. Partsthathavetobe  
removed for servicing should be replaced  
prior to operating this appliance.  
9) Test Gas Pressure (Refer to "Gas Pipe  
Pressure Testing" section).  
10) Installstandardandoptionalfeatures. Refer  
to the following sections:  
Regency® L900E Direct Vent Gas Fireplace  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
HEAT RELEASE KIT  
a)  
b)  
c)  
d)  
Interior Brick Panels  
Log Set  
The Heat Release Kit expels warm air from the  
fireplace to the outside of the building, allowing  
thereplacetobeoperatedwithlessheatentering  
the room. The kit may be used on either the left  
or right side.  
Exterior Brick Panels  
Remote Control - refer to "Matching  
Remote Handset & Control Box  
ID Code" section.  
A) Flat on Wall  
B) Flat on Wall Corner  
C) Recessed into  
Wall/Alcove  
11) Final check.  
See Heat Release installation manual for  
complete details and clearances from side  
only.  
Before leaving this unit with the customer, the  
installer must ensure that the appliance is firing  
correctly and operation fully explained to  
customer.  
D) Corner  
HEARTH  
This includes:  
REQUIREMENTS  
Diagram 1  
1) Clocking the appliance to ensure the correct  
firing rate (rate noted on label 48,000 (NG)  
Btu/h, 46,500 (LP) Btu/h) after burning  
appliance for 15 minutes.  
Aminimum33-1/8"(838mm)widex12"(305mm)  
deep x 2" (51mm) thick non-combustible hearth  
is required if the finished floor is not flush with the  
base of the unit. The maximum height between  
the finished floor and sub-floor is 1" (25mm).  
4) This appliance is Listed for bedroom  
installations using the standard FireWizard  
Remote (millivolt thermostat system). Some  
areas may have further requirements, check  
local codes before installation.  
2) Ifrequired,adjustingtheprimaryairtoensure  
that the flame does not carbon. First allow  
the unit to burn for 15-20 min. to stabilize.  
5) The L900E Direct Vent Gas Fireplace  
is approved for alcove installations, see  
"Clearances" section for details.  
CAUTION: Any alteration to the product that  
causes sooting or carboning that results  
in damage is not the responsibility of the  
manufacturer.  
6) We recommendthatyouplanyourinstallation  
on paper using exact measurements for  
clearances and floor protection before  
actually installing this appliance. Have an  
authorized inspector, dealer, or installer  
review your plans before installation.  
MANUFACTURED  
MOBILE HOME  
ADDITIONAL  
Note: For vent terminations refer to  
"ExteriorVent TerminationLocations"  
section.  
REQUIREMENTS  
1) Ensure that structural members are not cut  
or weakened during installation.  
HEATWAVE  
DUCT KIT  
2) Ensure proper grounding using the #8  
ground lug provided. See "Wiring Diagram"  
section.  
The HeatWave Air Duct Kit increases the  
effectivenessofyourreplacebydispersingwarm  
air from the fireplace to remote locations in the  
same room or other rooms in your home.  
LOCATING YOUR  
GAS FIREPLACE  
2” (51mm)  
NOTE: No hearth is required when the unit is  
flush with the finished floor as shown  
below.  
Up to two kits may be installed on the fireplace.  
Please Note: Only 1 HeatWave kit may be  
operated at one time.  
1) When selecting a location for your fireplace,  
ensure that the clearances are met.  
Theminimumoorclearancemustbemaintained  
from the top surface of the carpet, etc. to the  
unit base.  
2) The appliance must be installed on a flat,  
solid, continuous surface (e.g. wood, metal,  
concrete). This may be the floor, or raised up  
on a platform to enhance its visual impact.  
The appliance must be installed on a metal  
or wood panel extending the full width and  
depth of the appliance.  
See HeatWave installation manual for complete  
details and clearances from side only.  
3) The L900E Direct Vent Gas Fireplace can  
be installed in a recessed position or framed  
out into the room as in A, B, C and D. See  
Diagram 1.  
The HeatWave Duct Kit has different  
clearance and framing requirements, check  
the HeatWave manual for details.  
Regency® L900E Direct Vent Gas Fireplace  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
CLEARANCES  
The clearances listed below are Minimum distances unless otherwise stated:  
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest  
importance that this fireplace and vent system be installed only in accordance with these instructions.  
Caution Requirements  
The top, back and sides of the fireplace are defined by  
standoffs. The metal ends of the standoff may NOT be  
recessed into combustible construction.  
Clearance to Combustibles from:  
Back  
Side  
Floor  
0"  
0"  
0"  
(0mm)  
(0mm)  
(0mm)  
Minimum Clearance from Top of Front Facing:  
Mantel min. 17-1/2" (445mm)  
Ceiling  
49"  
(1245mm) from top of front facing  
Side Wall to Unit:  
16"*  
(406mm)  
Horizontal Vent Clearances to Combustibles:  
Top  
3"  
2"  
2"  
(76mm)  
(51mm)  
(51 mm)  
Side  
Bottom  
Vertical Vent Clearances to Combustibles:  
All Sides  
2"  
(51mm)  
Alcove Clearances:  
Min. Depth  
36"  
(914mm)  
(2134mm)  
(2134mm)  
Min. Width* 84"  
Min. Height 84"  
* Alcove side wall must have a minimum of 16" (406mm) clearance on one side.  
WARNING  
Fire hazard is an extreme risk  
if these clearances (air space) to combustible materials  
are not adhered to. It is of greatest importance that this  
fireplace and vent system be installed only in  
accordance with these instructions.  
Regency® L900E Direct Vent Gas Fireplace  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
MANTEL CLEARANCES  
Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing  
are shown in the diagram below.  
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible  
board.  
Note: Ensure the paint that is used  
on the mantel and the facing is  
"heat resistant" or the paint may  
discolour.  
MANTEL LEG CLEARANCES  
Combustible mantel leg clearances as per diagram:  
Regency® L900E Direct Vent Gas Fireplace  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
FRAMING & FINISHING  
1) Frame in the enclosure for the unit with framing material. The framed  
Drywall  
Header  
(On Edge)  
opening for the assembled kit is 50-3/4" high x 52" wide x 26-1/2"  
deep (1289mm x H 1321mm W x 673mm D). See Diagram 1. Also  
see Diagram 2 for corner installations.  
Header  
(On Edge)  
83"  
(2108mm)  
Min. 26-1/2"  
(673mm)  
Non-Combustible  
Material  
52”  
(1321mm)  
5”  
(127mm)  
Diagram 1  
2”  
(51mm)  
26-1/2”  
(673mm)  
Diagram 3  
6”  
(152mm)  
Note: When constructing the framed opening, please ensure  
thereisaccesstoinstallthegaslineswhentheunitisinstalled.  
See diagram 3 for details.  
Diagram 2  
2) For exterior walls, insulate the enclosure to the same degree as the  
rest of the house, apply vapour barrier and drywall, as per local instal-  
lation codes. (Do not insulate the fireplace itself.)  
Non-Combustible Requirements  
3) The unit does not have to be completely enclosed in a chase. The  
clearance on top of the unit from the top standoffs is 0" so combusti-  
ble building materials can be laid directly on top of the standoffs. You  
must maintain clearances from the vent to combustible materials: See  
"Clearances" section. Combustible materials can be laid against the  
side and back standoffs and the stove base.  
Stud  
53-3/4"  
(1365mm)  
Non-combustible  
Material  
Note: When installing this fireplace there are two warnings on the  
front face of the unit. The areas indicated here are painted  
black and indicate that no nails, screws, or other punctures  
can be made at these points as there are sensitive electronic  
components directly behind these markings.  
33-1/8"  
(838mm)  
DONOT  
NAIL  
HERE  
10-5/16"  
(254mm)  
NO  
3"  
(76mm)  
NAIL  
HERE  
Regency® L900E Direct Vent Gas Fireplace  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
SIDE NAILING STRIPS  
UNIT ASSEMBLY  
PRIOR TO  
FINISHING TEMPLATE  
Thesidenailingstripscomeattachedtotheunit.  
There are 3 plates, one on the top and bottom  
that can be folded out as required.  
In order to maintain a clean face; the L900E  
allows for a 1/8” in overlap of finishing material,  
such as rock or tile, on both the left and right  
hand sides of the unit (top and bottom sides do  
not allow for an overlap), this overlap must not  
be exceeded or the glass door will no longer  
open properly.  
INSTALLATION  
TheTopFacingSupport, theSideNailingStrips  
and the 2 Top Standoffs must be correctly  
positioned and attached to the top before unit  
is slipped into position.  
Non-combustible wall board is installed up  
to the flanges on all sides of the unit. When  
installing any additional facing material use  
the Finishing Template (included with the unit)  
to ensure that the finishing material does not  
exceed the allowable overlap.  
TOP STANDOFF ASSEMBLY  
The top standoffs are shipped in a flat position  
and must be folded into shape and attached.  
1) Remove the standoffs from the fireplace  
The Finishing Template uses two magnets to  
attach itself to the flange on the left or right side  
oftheunit(seediagrambelow).Installthefacing  
material up to the outside edge (when facing  
theunit)ofthenishingtemplate. Thistemplate  
may be discarded after the facing material has  
been installed.  
top.  
2) Takeeachstandoffandbendintothecorrect  
shape. Bend up at the bend lines until the  
screw holes in the standoff and the pre-  
punched screw holes on the fireplace top  
line up.  
3) Attach the standoff securely to the top  
with 2 screws per standoff (on opposite  
corners).  
Side Nailing Strips shown folded out.  
Regency® L900E Direct Vent Gas Fireplace  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
To set the vent restriction as indicated in the  
venting arrangements diagrams, refer to the  
instructions below;  
Screws for plugging the holes.  
VENTING  
(all holes must be plugged with a screw).  
INTRODUCTION  
Screw holes for fixing the restrictor plate.  
1) Remove the glass door.  
The L900E uses the "balanced flue" technology  
CoAxial system. The inner liner vents products  
of combustion to the outside while the outer  
liner draws outside combustion air into the  
combustion chamber thereby eliminating the  
needtouseheatedroomairforcombustionand  
losing warm room air up the chimney.  
a. Release the 2 door latches on the left  
and right side at the top of the firebox.  
Note: These flue pipes must not be  
connected to any other appliance.  
Latch Location  
The gas appliance and vent system must be  
vented directly to the outside of the building,  
and never be attached to a chimney serving a  
separate solid fuel or gas burning appliance.  
Eachdirectventgasappliancemustuseit'sown  
separate vent system. Common vent systems  
are prohibited.  
Factory Set Vent Restrictor Setting  
(no adjustment required)  
Latch  
VENT RESTRICTOR  
POSITION  
Vent restriction is required for certain venting  
installations, see the diagrams in the "Venting  
Arrangements" section to determine if they are  
required for your installation.  
b. Swingthedooroutfromthetopandrelease  
the hinges on the left and right side of the  
door by lifting them up.  
TheVentRestrictorplateislocatedontheinside  
top of the firebox.  
Hinge  
Vent Restrictor Plate  
Door  
2) Removethescrewsthatholdtheventrestric-  
tor plate in place.  
3) Adjusttheventrestrictorplatetotherequired  
vent restrictor position as per the diagrams  
shown.  
4) Oncetheventrestrictorplateisintherequired  
position, secure with screws.  
Regency® L900E Direct Vent Gas Fireplace  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
EXTERIOR VENT TERMINATION REQUIREMENTS  
A= Clearance above grade, veranda, porch, deck, or balcony *(min.  
12"/30cm)  
B= Clearance to window or door that may be opened *(12"/30cm)  
#(9"/23cm)  
G= Clearance to inside corner: with AstroCap Termination Cap (min.  
18")  
H= Not to be installed above a meter/regulator assembly within (3'/90cm)  
horizontally from the centerline of the regulator.  
C= Clearance to permanently closed window *(min. 12"/30cm)  
D= Vertical clearance to ventilated soffit located above the terminal within  
a horizontal distance of (24"/60cm) from the centerline of the terminal  
(min. 33"/84cm) check with local code.  
E= Clearance to unventilated soffit (min. 33"/84cm)  
F= Clearance to outside corner: with AstroCap Termination Cap (min.  
13")  
J= Clearance to service regulator vent outlet *(min. 36"/90cm)  
K= Clearance to non-mechanical air supply inlet to building or the  
combustion air inlet to any other appliance *(12"/30cm) #(9"/23cm)  
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m) #3' (91cm)  
above if within 10' (3m) horizontally.  
M= Clearance above paved sidewalk or a paved driveway located on  
public property *(min. 84"/2.1m)  
N= Clearance under veranda, porch, deck, or balcony *(min. 33"/84cm)  
Note:  
- Excluding direct vent or non-condensing appliances, a vent shall not terminate directly above a sidewalk or paved driveway which is located between  
two single family dwellings and serves both dwellings.  
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.  
- If the vent termination is accessible, a certified guard shall be installed.  
* As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.  
# In accordance with the current ANSI Z223.1/NFPA 54, Natioinal Fuel Gas Code.  
Regency® L900E Direct Vent Gas Fireplace  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
VENTING ARRANGEMENTS  
HORIZONTAL TERMINATION (FLEX)  
Regency® Direct Vent System  
These venting systems, in combination with the L900E, have been tested and listed as a direct vent system by Warnock Hersey. The location of the  
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.  
FPI Direct Vent (Flex) System Termination Kits include all the  
parts needed to install the L900E using a flexible vent.  
FPI Kit #  
Length Contains:  
#946-618  
6 Feet  
1) 8” flexible liner (Kit length)  
2) 5” flexible liner (Kit length)  
3) spring spacers (3)  
4) thimble (2)  
5) AstroCap termination cap (1)  
6) screws (12)  
#946-616  
10 Feet  
7) tube of Mill Pac (1)  
8) plated screws (8)  
9) S.S. screws #8 x 1-1/2” drill point, (4)  
10) vinyl siding standoff  
Vinyl Siding  
Standoff  
Vent Guard - if required*  
(Part #946-506/P)  
Wall Thimble  
(Mandatory in all  
Horizontal Terminations)  
AstroCap XLTM  
Termination Cap  
(Part #946-623/P)  
5” dia. flue pipe  
8” dia.  
Flue pipe  
spring spacer  
* A Vent Guard is required when the AstroCap  
is installed above grade at 7 feet or lower.  
Notes:  
1) Liner sections should be continuous without any joints  
or seams.  
2) Only Flex pipe purchased from FPI may be used for Flex  
installations.  
3) Horizontal vent must be supported every 3 feet.  
4) Awallthimbleismandatoryforallhorizontalterminations  
due to high temperatures.  
Regency® L900E Direct Vent Gas Fireplace  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
RIGID PIPE VENTING SYSTEMS  
BASIC HORIZONTAL & VERTICAL TERMINATIONS  
Rigid Pipe Vent Systems offer a complete  
line of component parts for installation of both  
horizontalandverticalinstallations. Manyitems  
are offered in decorative black, as well as gal-  
vanized finish.  
Vertical Terminal  
Storm Collar  
Vinyl Siding  
Standoff (Optional)  
The minimum components required for a basic  
horizontal termination are:  
Flashing  
Vent Guard - if required*  
(Part #946-506/P)  
1
1
1
1
1
AstroCap XL  
AstroCap XL  
Termination Cap  
(Part #946-623/P)  
90o Elbow  
Ceiling Firestop  
Rigid Pipe Adaptor  
Wall Thimble  
Length of pipe to suit wall thickness  
Wall Thimble  
(Mandatory in all  
Horizontal Terminations)  
The minimum components required for a basic  
vertical termination are:  
Pipe Length  
Adj.Pipe Length  
11" - 14-5/8"  
90o Elbow  
1
1
1
Vertical Termination Cap  
Rigid Pipe Adaptor  
Lengths of pipe to adequately  
penetrate roof  
24”  
Pipe  
Length  
1
1
1
Ceiling Firestop  
Flashing  
Storm Collar  
Rigid Pipe  
Adapter  
(770-994)  
Wall thickness is measured from the back  
standoffs to the inside mounting surface of  
termination cap. For siding other than vinyl  
furring strips may be used, instead of the vinyl  
siding standoff, to create a level surface to  
mount the vent terminal. The Terminal must  
not be recessed into siding. Measure the wall  
thickness including furring strips.  
If a Vinyl Siding Standoff is required (it must  
be used with vinyl siding), measure to outside  
surface of wall without siding and add 2  
inches.  
* A Vent Guard is required when the AstroCap  
is installed above grade at 7 feet or lower.  
WARNING:  
IMPORTANT NOTE  
• The Simpson Dura-Vent and Selkirk Direct  
Temp horizontal termination caps cannot  
be used in any applications.  
Do not combine venting components from  
different venting systems.  
Alternate  
Horizontal Termination  
Caps  
TM  
• Only the AstroCap XL and Snorkels are  
certified for horizontal terminations.  
Use of the the AstroCap XL is acceptable  
with all systems.  
ThisproducthasbeenevaluatedbyIntertekfor  
using a Rigid Pipe Adaptor in conjunction with  
Duravent Direct-Vent GS and Selkirk Direct-  
Temp systems. Use of these systems with  
the Rigid Pipe adaptor is deemed acceptable  
and does not affect the Intertek WHI listing of  
components.  
When using Rigid Vent other than  
Simpson Dura-Vent, 3 screws must be  
used to secure rigid pipe to adaptor.  
Part # 5DT-ST14 (14")  
Part # 5DT-ST36 (36")  
The FPI AstroCap XLTM is certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS and Selkirk Direct-Temp.  
AstroCap XLTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary  
trademarks of Simpson Dura-Vent Co. Inc.  
Regency® L900E Direct Vent Gas Fireplace  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
5” X 8” RIGID PIPE CROSS REFERENCE CHART  
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.  
Simpson  
Simpson  
Metal-Fab®  
Sure Seal  
Selkirk  
Direct Vent GS®  
Discontinued  
Description  
Direct Vent Pro®  
Direct-Temp™  
6” Pipe Length, Galvanized  
6” Pipe Length, Black  
58DVA-06  
1208  
5DT-6  
5D6  
58DVA-06B  
58DVA-09  
1208B  
1207  
5DT-6B  
5DT-9  
5D6B  
N/A  
9” Pipe Length, Galvanized  
9” Pipe Length, Black  
58DVA-09B  
58DVA-12  
1207B  
1206  
5DT-9B  
5DT-12  
5DT-12B  
5DT-18  
5DT-18B  
5DT-24  
5DT-24B  
5DT-36  
5DT-36B  
5DT-48  
5DT-48B  
N/A  
N/A  
12” Pipe Length, Galvanized  
12” Pipe Length, Black  
5D12  
5D12B  
5D18  
5D18B  
5D24  
5D24B  
5D36  
5D36B  
5D48  
5D48B  
N/A  
58DVA-12B  
58DVA-18  
1206B  
18” Pipe Length, Galvanized  
18” Pipe Length, Black  
58DVA-18  
58DVA-18B - N/A from FPI  
58DVA-18B - N/A from FPI  
24” Pipe Length, Galvanized  
24” Pipe Length, Black  
58DVA-24  
1204  
58DVA-24B  
58DVA-36  
1204B  
36” Pipe Length, Galvanized  
36” Pipe Length, Black  
1203  
58DVA-36B  
58DVA-48  
1203B  
48” Pipe Length, Galvanized  
48” Pipe Length, Black  
1202  
58DVA-48B  
58DVA-60  
1202B  
60” Pipe Length, Galvanized  
60” Pipe Length, Black  
58DVA-60  
58DVA-60B - N/A from FPI  
58DVA-60B - N/A from FPI  
N/A  
N/A  
Adjustable Length 3”-10”, Galvanized  
Adjustable Length 3”-10”, Black  
Adjustable Length 11”-14”, Galvanized  
Adjustable Length 11”-14”, Black  
Adjustable Length 17”-24”, Galvanized  
Adjustable Length 17”-24”, Black  
Extension Pipe 8-1/2”, Galvanized  
Extension Pipe 8-1/2”, Black  
N/A  
N/A  
N/A  
5DAL  
5DALB  
N/A  
N/A  
N/A  
N/A  
Disc - See 58DV-08A  
Disc - See 58DV-08AB  
Disc - See 58DV-16A  
Disc - See 58DV-16AB  
58DVA-08A - N/A from FPI  
Disc - See 58DV-08A  
Disc - See 58DV-08AB  
Disc - See 58DV-16A  
Disc - See 58DV-16AB  
58DVA-08A - N/A from FPI  
5DT-AJ  
5DT-AJB  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
58DVA-08AB  
58DVA-08AB  
N/A  
N/A  
58DVA-16A - N/A from FPI  
58DVA-16A - N/A from FPI  
Extension Pipe 16”, Galvanized  
Extension Pipe 16”, Black  
N/A  
N/A  
58DVA-16AB  
58DVA-16AB  
N/A  
N/A  
45º Elbow, Galvanized  
45º Elbow, Black  
58DVA-E45  
1245  
5DT-EL45  
5DT-EL45B  
N/A  
N/A  
58DVA-E45B  
Disc - See 58DVA-E45  
Disc - See 58DVA-E45B  
58DVA-E90  
1245B  
N/A  
45º Elbow, Swivel, Galvanized  
45º Elbow, Swivel, Black  
90º Elbow, Galvanized  
90º Elbow, Black  
1245G  
5D45L  
5D45LB  
N/A  
1245BG  
N/A  
58DVA-E90  
58DVA-E90B  
Disc - See 58DVA-E90  
Disc - See 58DVA-E90B  
N/A  
5DT-EL90S  
5DT-EL90SB  
N/A  
58DVA-E90B  
Disc - See 58DVA-E90  
Disc - See 58DVA-E90B  
N/A  
N/A  
90º Elbow, Swivel, Galvanized  
90º Elbow, Swivel, Black  
90º Starter Elbow, Swivel, Galvanized*  
Adaptor*  
5D90L  
5D90LB  
5D90A  
5DDA  
N/A  
N/A  
N/A  
N/A  
N/A  
Ceiling Support  
58DVA-DC  
1240  
1241  
1288  
N/A  
5DT-CS  
5DT-CSS  
5DT-WS/B  
5DT-OS  
5DT-WT  
N/A  
5DSP  
5DRS  
5DWS  
N/A  
Cathedral Support Box  
Wall Support/Band  
58DVA-CS  
58DVA-WS  
58DVA-ES - N/A from FPI  
58DVA-WT  
Offset Support  
Wall Thimble, Black  
Wall Thimble Support Box/Ceiling Support  
Firestop Spacer  
1247  
N/A  
5DWT  
N/A  
58DVA-DC - N/A from FPI  
58DVA-FS  
1263  
1242  
5DT-FS  
5DT-TP  
5DFS  
5DCP  
Trim Plate, Black  
58DAV-WFS  
Regency® L900E Direct Vent Gas Fireplace  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.  
Simpson  
Simpson  
Metal-Fab®  
Sure Seal  
Selkirk  
Direct Vent GS®  
Discontinued  
Description  
Direct Vent Pro®  
Direct-Temp™  
Round Support / Radiation Sheild  
Flat Flashing  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Attic Insulation Shield 12”  
58DVA-IS - N/A from FPI  
58DVA-IS - N/A from FPI N/A  
N/A  
Basic Horizontal Termination Kit (A)  
Horizontal Termination Kit (B)  
Vertical Termination Kit  
N/A  
N/A  
5DT-HKA  
5DT-HKB  
N/A  
N/A  
N/A  
58DVA-KHA  
58DVA-VCH  
N/A  
1291  
5DT-VKC  
High Wind Vertical Cap  
High Wind Horizontal Cap  
Horizontal Square Termination Cap  
Vertical Termination Cap  
Storm Collar  
N/A  
N/A  
N/A  
N/A  
DISC.  
N/A  
1285  
1284  
N/A  
N/A  
N/A  
5DT-HHC  
5DT-HVC  
5DT-SC  
5DHT  
5DVT  
5DSC  
N/A  
58DVA-SC  
1253  
Adjustable Flashing, 0/12-6/12  
Adjustable Flashing, 6/12-12/12  
58DVA-F6  
1243  
5DT-AF6  
5DF  
58DVA-F12  
1243S  
5DT-AF12  
5DF-12  
Vinyl Siding Standoff  
58DVA-VSS  
N/A  
1250  
N/A  
5DT-VS  
5DVS  
N/A  
Vinyl Siding Shield Plate  
5DT-VSP  
Snorkel Termination 14”  
Snorkel Termination 36”  
58DVA-SNK14  
N/A  
1282  
1281  
5DT-ST14  
5DT-ST36  
5DST14  
5DST36  
Restrictor Disk  
58DVA-RD  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Colinear Flex Liner Adapter (3” Ø)  
FPI  
946-604/P  
770-994  
Simpson Direct Vent Vent Guard (Optional)  
Rigid Pipe Adapter (Must use with all Rigid Piping)  
946-623/P  
946-506/P  
946-625  
AstroCap XL Horizontal Cap  
Vent Guard (Optional)  
Vinyl Siding Standoff - AstroCap XL  
*NOTE: When using Metal-Fab Sure Seal Rigid Piping please note that either the Adaptor (5DDA) or 90º Starter Elbow  
(5D90A) must be used in conjunction with FPI Rigid Pipe Adaptor (770-994).  
L676 & L900 Direct Vent Fireplace  
IMPORTANT NOTE  
• A Vent Guard is required when the AstroCap is installed above grade at 7 feet or lower.  
• The Simpson Dura-Vent and Selkirk Direct Temp horizontal termination caps cannot be used in any applications.  
• Only the AstroCap XL and Snorkels are certified for horizontal terminations.  
Offset Pipe Selection:  
Use this table to determine offset pipe lengths.  
Forspecificinstructionsordetailsonparticular  
venting components please visit the following  
websites:  
5” x 8” Venting  
Pipe Length  
Run (X)  
Rise (Y)  
Simpson Direct Vent Pro: www.duravent.com  
Selkirk Direct-Temp: www.selkirkcorp.com  
Metal-Fab Sure Seal: www.mtlfab.com  
0”(0mm)  
5-11/16”(144mm)  
8-13/16”(224mm)  
10-15/16”(278mm)  
13”(330mm)  
15-5/16”(389mm)  
18-7/16”(468mm)  
20-9/16”(522mm)  
22-11/16”(576mm)  
31-1/16”(789mm)  
39-7/16”(1002mm)  
47-7/8”(1216mm)  
6”(152mm)  
9”(229mm)  
12”(305mm)  
24”(610mm)  
36”(914mm)  
48”(1219mm)  
L
Y
21-7/16”(697mm)  
29-13/16”(757mm)  
38-1/4”(972mm)  
X
NOTE: Horizontal runs of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards  
the termination. Never allow the vent to run downward. This could cause high temperatures and  
may present a possible fire hazard.  
Regency® L900E Direct Vent Gas Fireplace  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
VENTING ARRANGEMENTS  
ALLOWABLE HORIZONTAL TERMINATIONS  
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o two 45o elbows equal one 90o elbow).  
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.  
* A Vent Guard is required when the AstroCap  
is installed above grade at 7 feet or lower.  
IMPORTANT NOTE  
• The Simpson Dura-Vent and Selkirk Direct Temp horizontal termination caps  
cannot be used in any applications.  
• Only the AstroCap XL and Snorkels are certified for horizontal terminations.  
VENT RESTRICTOR SETTING:  
Vent restrictor at 0" - factory set, no adjustment required unless otherwise indicated.  
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1, Set 2 or Set 3 if required.  
A vent guard is required when the AstroCap is installed above grade at 7 feet or lower.  
A vent guard may also be required in other installations as per local codes, refer to "Exterior Vent Termination Requirements" section  
for details.  
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.  
Maintain clearances to combustibles as listed in "Clearances" section  
Horizontal vent must be supported every 3 feet.  
Firestops are required at each floor level and whenever passing through a wall.  
A wall thimble is mandatory for all horizontal terminations due to high temperatures.  
Regency® L900E Direct Vent Gas Fireplace  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Horizontal Venting with Two (2) 90o Elbows  
One 90o elbow = Two 45o elbows.  
Option  
A)  
V
H + H1  
2' Max.  
4' Max.  
8' Max.  
9' Max.  
10' Max.  
With these options,  
maximum total pipe length  
is 30 feet with minimum of  
10 feet total vertical and  
maximum 10 feet total  
horizontal.  
3' Min.  
4' Min.  
6' Min.  
8' Min.  
10' Min.  
B)  
C)  
D)  
E)  
Please note minimum 1 foot between 90o elbows is  
required.  
VENT RESTRICTOR SETTING:  
Vent restrictor at 0" - factory set, no adjustment required.  
Horizontal Venting with Three (3) 90o Elbows  
One 90o elbow = Two 45o elbows.  
Option  
A)  
V
H
V + V1 H + H1  
With these options,  
max. total pipe length  
is 30 feet with min. of  
11 feet total vertical  
and max. 10 feet total  
horizontal.  
2' Min. 1' Max. 5' Min. 2' Max.  
3' Min. 1' Max. 6' Min. 3' Max.  
4' Min. 3' Max. 8' Min. 6' Max.  
5' Min. 4 Max. 10' Min. 8' Max.  
5' Min. 4' Max. 11' Min. 10' Max.  
B)  
C)  
D)  
E)  
Please note min. 1  
foot between 90o  
VENT RESTRICTOR SETTING:  
Vent restrictor at 0" - factory set, no adjustment  
required.  
Regency® L900E Direct Vent Gas Fireplace  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Vertical Venting with Three (3) 90o Elbows  
One 90o elbow = Two 45o elbows.  
Option  
A)  
V
H + H1 V + V1  
With these options, max.  
total pipe length is 30 feet  
with min. of 10 feet total  
vertical and max. 8 feet  
total horizontal.  
2' Min. 3' Max. 4' Min.  
3' Min. 4' Max. 6' Min.  
4' Min. 5' Max. 8' Min.  
5' Min. 6' Max. 9' Min.  
6' Min. 8' Max. 10' Min.  
B)  
C)  
D)  
E)  
Please note min. 1 foot  
between 90o elbows is  
required.  
VENT RESTRICTOR SETTING:  
Vent restrictor at 0" - factory set, no  
adjustment required.  
Regency® L900E Direct Vent Gas Fireplace  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
VENTING ARRANGEMENTS  
ALLOWABLE VERTICAL TERMINATIONS  
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with  
Rigid Pipe Venting Systems for Propane and Natural Gas. Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed.  
2
4
8
14  
0
6
10  
12  
40  
38  
36  
34  
32  
30  
28  
Vent Restrictor on Set 3  
26  
24  
22  
20  
18  
16  
14  
12  
10  
Vent Restrictor on Set 2  
Vent Restrictor on Set 1  
8
6
4
2
0
Vent must be supported at offsets.  
Firestops are required at each floor level and whenever passing through a wall.  
Maintain clearances to combustibles as listed in the "Clearances" section.  
Refer to "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1, Set 2 or Set 3 if required.  
Note: Must use optional flue adapter when using Rigid Pipe (Part # 770-994).  
Regency® L900E Direct Vent Gas Fireplace  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Horizontal runs of vent must be supported 7) Ensure that the pipe clearances to  
UNIT INSTALLATION  
WITH HORIZONTAL  
every 3 feet (0.9meter). Wall straps are  
available for this purpose.  
combustible materials are maintained  
(Diagram 5). Install the termination cap.  
TERMINATION  
Note: If installing termination on a vinyl  
siding covered wall, a vinyl siding  
standofforfurringstripsmustbeused  
to ensure that the termination is not  
recessed into the siding.  
6) Mark the wall for a 11" x 11" (279mm x  
279mm) square hole. The center of the  
square hole should line up with the center-  
line of the horizontal pipe. Cut and frame the  
11 inch (279mm) square hole in the exterior  
wall where the vent will be terminated. See  
diagram 2 for center line requirements.  
(Rigid Vent Systems)  
Atopclearanceof3"(76mm)andside&bottom  
clearance of 2"(51mm) must be maintained;  
except when passing through a wall, ceil-  
ing, or at the termination where the use of a  
firestop or wall thimble reduces the required  
clearance to 1-1/2" (38mm). We recommend  
framing a 11"(279mm) x 11"(279mm) (inside  
dimensions) hole to give structural rigidity  
for mounting the termination.  
If the wall being penetrated is constructed of  
non-combustiblematerial,i.e.masonryblock  
or concrete, an 8" (203mm) diameter hole  
is acceptable.  
Install the vent system according to the  
manufacturer's instructions included with the  
components.  
1) Set the unit in its desired location. Check to  
determine if wall studs or roof rafters are in  
thewaywhentheventingsystemisattached.  
If this is the case, you may want to adjust  
the location of the unit. Rough in the gas  
preferably on the right side of the unit and  
the electrical (junction block is on the left  
side) on the left.  
Diagram 5  
Thefourwoodscrewsprovidedshouldbere-  
placedwithappropriatefastenersforstucco,  
brick, concrete, or other types of sidings.  
2) DirectVentpipeandttingsaredesignedwith  
specialtwist-lockconnectionstoconnectthe  
venting system to the appliance flue outlet.  
A twist-lock appliance adaptor is required.  
8) Before connecting the horizontal run of vent  
pipe to the vent termination, slide the Wall  
Thimble over the vent pipe. The wall thimble  
is required for all horizontal terminations.  
3) In conjunction with the Simpson Dura-Vent  
Direct Vent GS system. Install the adaptor  
after the unit is set in its desired location.  
Put a bead of high temperature silicone  
inside the outer section of the adapter and  
a bead of Mill Pack on the inner collar. Slip  
the adapter over the existing inner and outer  
fluecollar. Fastentotheoutercollaronlywith  
the 3 supplied screws (drilling pilot holes will  
make this easier).  
9) Slide the appliance and vent assembly  
towards the wall carefully inserting the vent  
pipeintotheventcapassembly.Itisimportant  
that the vent pipe extends into the vent cap  
sufficientdistancesoastoresultinaminimum  
pipeoverlapof1-1/4inches(32mm). Secure  
the connection between the vent pipe and  
the vent cap.  
Diagram 2  
Note:  
a) The horizontal run of vent must be level,  
or have a 1/4 inch rise for every 1 foot  
of run towards the termination. Never  
allow the vent to run downward. This  
could cause high temperatures and may  
present the possibility of a fire.  
4) Levelthereplaceandfastenittotheframing  
using nails or screws through the top and  
side nailing strips.  
10) Install wall thimble in the center of the 11"  
(279mm)squareandattachwithwoodscrews  
(Diagram 7).  
5) Assemble the desired combination of pipe  
and elbows to the appliance adaptor and  
twist-lock for a solid connection.  
b) The location of the horizontal vent  
terminationonanexteriorwallmustmeet  
all local and national building codes, and  
must not be blocked or obstructed. See  
"Exterior Vent Termination Locations"  
section for more details.  
Note: For best results and optimum  
performance with each approved  
venting system, it is highly  
recommended to apply “Mill-Pac”  
sealant (supplied) to every inner pipe  
connection.Failuretodosomayresult  
in drafting or performance issues not  
coveredunderwarranty. Silicone(red  
RTV) is optional.  
Diagram 7  
NOTE: A Vent Guard is required when  
the AstroCap is installed above grade  
at 7 feet or lower.  
Diagram 1  
Regency® L900E Direct Vent Gas Fireplace  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
4) Assemble the desired lengths of pipe and  
elbows. Ensure that all pipes and elbow  
connections are in the fully twist-locked  
position and sealed.  
UNIT INSTALLATION  
WITH VERTICAL  
TERMINATION  
Note:  
(Rigid Vent Systems)  
Diagram 5  
For best results and optimum performance  
with each approved venting system, it is  
highly recommended to apply “Mill-Pac”  
sealant(supplied)toeveryinnerpipeconnec-  
tion. Failure to do so may result in drafting  
or performance issues not covered under  
warranty. Silicone (red RTV) is optional.  
Note: A clearance of 2"(51mm) must be  
maintained; except when passing  
through a wall, ceiling, or at the  
terminationwheretheuseofarestop  
or wall thimble reduces the required  
clearance to 1-1/2" (38mm). We  
recommend framing a 11"(279mm) x  
11"(279mm) (inside dimensions) hole  
togivestructuralrigidityformounting  
the termination.  
Minimum Vent  
Height  
Roof Pitch  
Feet  
2
Meters  
0.61  
0.61  
0.61  
0.76  
0.99  
1.22  
1.52  
1.83  
2.13  
2.29  
flat to 7/12  
over 7/12 to 8/12  
over 8/12 to 9/12  
over 9/12 to 10/12  
over 10/12 to 11/12  
over 11/12 to 12/12  
over 12/12 to 14/12  
over 14/12 to 16/12  
over 16/12 to 18/12  
over 18/12 to 20/12  
2
2
1) Maintain the 2" (51mm)  
clearances (air spaces)  
to combustibles when  
passing through ceilings,  
walls, roofs, enclosures,  
attic rafter, or other nearby  
combustible surfaces.  
Do not pack air spaces  
with insulation. Check  
"Venting Arrangemnt  
- Vertical Termination"  
2.5  
3.25  
4
5
6
5) Cut a hole in the roof centered on the small  
drilled hole placed in the roof in Step 2. The  
hole should be of sufficient size to meet  
the minimum requirements for clearance to  
combustiblesof1-1/2"(38mm).Sliptheashing  
under the shingles (shingles should overlap  
half the flashing) as per Diagram 4.  
7
7.5  
s e c t i o n  
f o r  
t h e  
A poor draft, or down drafting can result from  
highwindconditionsnearbigtreesoradjoining  
roof lines, in these cases, increasing the vent  
height may solve the problem.  
maximum vertical rise  
of the venting system and  
the maximum horizontal  
offset limitations.  
Diagram 1  
2) Setthegasappliance  
initsdesiredlocation.  
Drop a plumb bob  
downfromtheceiling  
to the position of the  
appliance flue exit,  
andmarkthelocation  
where the vent will  
penetratetheceiling.  
Drill a small hole at  
his point. Next, drop  
a plumb bob from  
the roof to the hole  
previously drilled in  
theceiling, andmark  
the spot where the  
7) Ensure vent is vertical and secure the base  
of the flashing to the roof with roofing rails,  
slide storm collar over the pipe section and  
seal with a mastic.  
8) Install the vertical termination cap by twist-  
locking it.  
Note: Anyclosetsorstoragespaces,which  
the vent passes through must be  
enclosed.  
Diagram 4: The upper half of the flashing is  
installed under the roofing material and not  
nailed down until the chimney is installed.  
This allows for small adjustments.  
Offset Chart  
Diagram 2  
ventwillpenetratetheroof.Determineifceiling  
joists,roofraftersorotherframingwillobstruct  
the venting system. You may wish to relocate  
theapplianceortooffset,asshowninDiagram  
2 to avoid cutting load bearing members.  
6) Continue to assemble pipe lengths.  
Note: If an offset is necessary in the attic  
to avoid obstructions, it is important  
to support the vent pipe every 3  
feet (0.9 meter), to avoid excessive  
stress on the elbows, and possible  
separation. Wall straps are available  
for this purpose  
3) AFirestop spacer must be installed in the floor  
or ceiling of every level.  
(Diagram 2).  
Galvanizedpipeisdesirableabovetheroofline  
duetoitshighercorrosionresistance.Continue  
to add pipe sections through the flashing until  
the height of the vent cap meets the minimum  
heightrequirementsspecifiedinDiagram5or  
local codes. Note that for steep roof pitches,  
the vertical height must be increased.  
Diagram 3  
Regency® L900E Direct Vent Gas Fireplace  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
4) Separatethe2halvesofthewallthimbleand  
securely fasten the one with the tabs to the  
outside wall making sure that the tabs are  
on top and bottom. Fasten the other thimble  
half to the inside wall. The thimble halves  
slip inside each other and can be adjusted  
for 2 x 4 or 2 x 6 walls.  
IMPORTANT: Do not locate termination  
hood where excessive snow or ice  
buildup may occur. Be sure to check vent  
terminationareaaftersnowfalls, andclear  
to prevent accidental blockage of venting  
system. When using snow blowers, make  
sure snow is not directed towards vent  
termination area.  
UNIT INSTALLATION  
HORIZONTAL TERMINATION  
WITH FLEX VENT SYSTEM  
Note: A top clearance of 3"(76mm) and  
side&bottomclearanceof2"(51mm)  
must be maintained; except when  
passing through a wall, ceiling, or  
at the termination where the use of  
arestoporwallthimblereducesthe  
required clearance to 1-1/2" (38mm).  
Werecommendframinga11"(279mm)  
x 11"(279mm) (inside dimensions)  
hole to give structural rigidity for  
mounting the termination.  
5) Slip the assembled liner and termination  
assembly through the thimble making sure  
the termination cap faces up (there are  
markings on the cap that show which way  
is up). This will position the termination cap  
with proper down slope for draining water.  
Fasten the cap to the outer wall with the 4  
supplied screws.  
ASTROCAP XL  
DIMENSIONS (946-623/P)  
1) Locate the unit in the framing, rough in the  
gas (preferably on the right side of the unit)  
and the electrical (Junction block is on the  
left side) on the left. Locate the centerline of  
the termination and mark wall accordingly.  
Cut an 11"(279mm) hole in the wall (inside  
dimension).  
6) Pull the centre 5"(127mm) liner and outer  
8"(203mm) liner out enough to slip over  
the flue collars of the fireplace. (You may  
wish to cut the liner shorter to make it more  
workable.) Do not bend liner more than 90o.  
The liners must slip over the collars a  
minimum of 1-3/8".  
7) Apply Mill Pac over the fireplace inner collar  
and slip the 5"(127mm) liner down over it  
and attach with 3 supplied screws.  
8) Do the same with the 8"(203mm) liner.  
9) Applyabeadofsiliconebetweenthethimble  
and termination and around the outer edge  
of the terminal at the wall in order to keep  
the water out.  
Note: If installing termination on a siding  
covered wall, a vinyl siding standoff  
or vinyl furring strips must be used  
to ensure that the termination is not  
recessed into the siding.  
2) Level the fireplace and fasten it to the fram-  
ing using nails or screws through the nailing  
strips.  
3) Assemble the vent assembly by applying  
Mill Pac to the 5"(127mm) inner collar of  
theterminationand slippingthe5"(127mm)  
liner over it at least 1-3/8" (35mm). Fasten  
with the 3 screws (drilling pilot holes will  
make this easier). Apply Mill Pac or high  
temperature silicone to the 8"(203mm) flex  
pipe and slip it over the 8" outer collar of  
the vent terminal at least 1-3/8"(35mm) and  
fasten with the 3 screws.  
NOTE: Horizontal sections must be sup-  
ported at intervals not exceeding 3  
feet (0.9 meter). (Flame picture and  
performance will be affected by sags  
in the liner).  
Regency® L900E Direct Vent Gas Fireplace  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
SIT 845 VALVE DESCRIPTION  
PILOT ADJUSTMENT  
L900E-NG SYSTEM DATA  
Min. Supply Pressure 5" WC (1.25 kpa)  
Periodically check the pilot flames. Correct  
flame pattern has three strong blue flames:  
1 around the flame sensor and 1 flowing  
across the burner (it does not have to be  
touching the burner).  
1) On-Off Solenoid Valve EV1  
2) On-Off Solenoid Valve EV2  
3) Inlet Pressure Test Point  
4) Outlet Pressure Test Point  
5) Connection for Pressure Regulator /  
Combustion Chamber Compensation  
6) Pressure Regulator for Minimum and  
Maximum Outlet Pressure  
7) Gas Outlet Pressure Electric Modulator  
8) Pilot Outlet  
9) Main Gas Outlet  
10) Side Outlet  
11) Main Gas Inlet  
Low Setting Man.  
Pressure  
1.6" WC (0.39 kpa)  
3.5" WC (0.87 kpa)  
#47 DMS  
Max. Manifold  
Pressure  
Orifice Size (Front  
Burner)  
Orifice Size (Back  
Burner)  
#30 DMS  
Minimum Input  
11,000 Btu/h  
(3.22 kW)  
Maximum Input  
48,000 Btu/h  
(12.3 kW)  
Note: Ifyouhaveanincorrectamepattern,  
contact your Regency® dealer for  
further instructions.  
L900E-LP SYSTEM DATA  
Min. Supply Pressure 12" WC (2.98 kpa)  
11  
Low Setting Man.  
Pressure  
3.6" WC (2.49 kpa)  
10" WC (2.98 kpa)  
#56 DMS  
Incorrect flame pattern will have small,  
probably yellow flames, not coming into  
proper contact with the rear burner or flame  
sensor.  
3
Max. Manifold  
Pressure  
1
Orifice Size (Front  
Burner)  
7
GAS PIPE PRESSURE  
TESTING  
The appliance must be isolated from the gas  
supply piping system by closing its individual  
manual shut-off valve during any pressure  
testing of the gas supply piping system at  
test pressures equal to or less than 1/2 psig.  
(3.45 kPa). Disconnect piping from valve at  
pressures over 1/2 psig.  
M D  
Orifice Size (Back  
Burner)  
#50 DMS  
6
10  
2
Minimum Input  
9,500 Btu/h  
(2.64 kW)  
Maxiumm Input  
46,500 Btu/h  
(11.72 kW)  
4
5
8
9
HIGH ELEVATION  
This unit is approved in Canada for altitude 0  
to 4500 ft. (CAN1 2.17-M91).  
Themanifoldpressureiscontrolledbyaregulator  
builtintothegascontrol, andshouldbechecked  
at the pressure test point.  
AERATION  
ADJUSTMENT  
Note: Toproperlycheckgaspressure,both  
inlet and manifold pressures should  
be checked using the valve pressure  
ports on the valve.  
GAS LINE  
INSTALLATION  
Since some municipalities have additional  
local codes it is always best to consult with  
your local authorities and the CAN/CGA B149  
installation code.  
The burner aeration is factory set but may need  
adjusting due to either the local gas supply or  
altitude. Open the air shutter for a blue flame or  
close for a more yellow flame.  
1) Make sure the unit is turned OFF.  
2) Loosen the "IN" and/or "OUT" pressure  
tap(s), turning counterclockwise with a  
1/8" wide flat screwdriver.  
In order to adjust the aeration, the logs, grate  
and burners will need to be removed to be able  
to access the shutters.  
For USA installations follow local codes and/or  
the current National Fuel Gas Code, ANSI  
Z223.1.  
3) Attach manometer to "IN" and/or "OUT"  
Minimum Air Shutter Opening:  
pressure tap(s) using a 5/16" ID hose.  
NG  
Front Burner  
Rear Burner  
1/4"  
1/2"  
4) Turn the unit ON.  
When using copper or flex connectors use only  
approved fittings. Always provide a union so  
that gas lines can be easily disconnected for  
servicing. Flare nuts for copper lines and flex  
connectors are usually considered to meet this  
requirement.  
LP  
Front Burner  
Rear Burner  
1/4"  
3/8"  
5) The pressure check should be carried out  
with the unit burning and the setting should  
be within the limits specified on the safety  
label.  
CAUTION: Carbonwillbeproducedifairshutter  
is tightly closed.  
6) When finished reading manometer, turn off  
theunit,disconnectthehoseandtightenthe  
screw(clockwise)witha1/8"atscrewdriver.  
Note: Screw should be snug, but do not  
over tighten.  
Important:Alwayscheckforgasleakswitha  
soapandwatersolutionorgasleakdetector.  
Do not use open flame for leak testing.  
Note: Any damage due to carboning  
resulting from improperly setting  
the aeration controls is NOT covered  
under warranty.  
Regency® L900E Direct Vent Gas Fireplace  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
BACK-UP BATTERY INSTALLATION  
1) Unsecure the battery from the outer firebox base flange by cutting the  
6) Connect the red and black wires to the battery accordingly.  
cable tie and remove from protective wrapping.  
2) Remove the plastic pin protectors from the battery.  
3) Loosen the screw that holds the right side heat shield in place.  
7) Place the battery into position on the velcro at the base of the firebox  
as shown.  
Heat  
Shield  
4) Lift the heat shield up and pull out slightly to clear the head screws  
and then hang it on the top bracket (located directly above the heat  
shield, close to the top of the firebox).  
5) Pull out the battery wires from the right side of the firebox.  
8) Re-install the heat shield.  
Battery  
Wires  
Regency® L900E Direct Vent Gas Fireplace  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
BRICK PANEL INSTALLATION  
IMPORTANT: Must install 1 set of brick panels. The operation of this unit without the brick panels is prohibited.  
Dangerous operating conditions may occur if the panels are broken.  
Handle with care. DO NOT FORCE INTO POSITION.  
3) Remove the 2 brick panel clips on the inside left and right side of the  
Interior Brick Panel Installation:  
firebox by removing the screw.  
1) Remove the glass door.  
a. Release the 2 door latches on the left and right side at the top of  
the firebox.  
Brick  
Panel  
Clip  
Screw  
Latch Location  
Latch  
4) Place the 2 small back brick panels at the base of the firebox on the  
left and right side of the rear log tray.  
Note: The left and right side back brick panels are different.  
b. Swing the door out from the top and release the hinges on the left  
and right side of the door by lifting them up.  
Left Side Back  
Brick Panel  
Right Side Back  
Brick Panel  
Hinge  
Door  
c. Place the door on a soft surface to prevent scratching.  
2) Unwrap the brick panels from the protective wrapping.  
Note: The logs must not be in the unit.  
Right Side  
Back Brick  
Panel  
Left Side  
Back Brick  
Panel  
Regency® L900E Direct Vent Gas Fireplace  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
5) Install the back brick panel by carefully placing it against the back  
7) Slide the left side brick panel into position and secure in place with  
wall of the firebox.  
the brick panel clip that was removed in step 3.  
L e f t  
Side  
Brick  
Panel  
Back Brick Panel  
Exterior Brick Panel Installation:  
1) Ensure installation of the logs and glass door has been completed  
before installing the exterior brick panels.  
2) Line up the pins in the exterior base brick panel with the holes on  
the outerbox of the firebox and fit in place.  
6) Place the top brick panel into position and hold it in place while slid-  
ing the right side brick panel into position and secure using the brick  
panel clip that was removed in step 3.  
Top Brick Panel  
Outerbox of Firebox  
3) Install the right side exterior brick panel by placing the bottom tab  
into the slot of the exterior base brick panel.  
The top of the brick panel is held in place by a magnet that sits  
against the bracket as shown in the image below.  
Top Brick Panel  
Repeat for left side exterior brick panel.  
Right Side  
Brick Panel  
Bracket  
Brick  
Panel  
Clip  
Tab  
Base Brick Panel Slot  
Regency® L900E Direct Vent Gas Fireplace  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
LOG SET INSTALLATION  
Installation of Interior Brick Panels must be completed before installing the log set.  
Read the instructions below carefully and refer to the diagrams.  
If the logs are broken do not use the unit until they are replaced.  
Broken logs can interfere with pilot operation.  
3) Place log 03-42 on the front left side of the burner. Place the right  
end of the log into the pin and rest the notch on the left end of the  
log on the grate.  
Log kit (Part No. 546-930 and 546-935) contain the following pieces:  
a) 03-41  
b) 03-42  
c) 03-43  
d) 03-44  
e) 03-45  
Log Rear  
Log Front Left  
Log Front Right  
Log Cross Left  
Log Cross Right  
03-42  
f) 902-154 Embers Lava  
g) 902-179 Vermiculite  
h) 946-669 Platinum Embers (supplied with packaged manual)  
Grate  
03-41  
03-44  
03-45  
4) Spread some vermiculite on the front log tray next to log 03-42 as  
shown in the image below.  
Note: Do not build up vermiculite as this will cause the next log  
(03-43) not to sit all the way down. Vermiculite is only  
needed to conceal the metal inbetween the left and right  
front logs.  
03-43  
03-42  
The "03" reference numbers (i.e. 03-41) are  
molded into the rear of each log.  
1) Carefully remove the logs from the box and unwrap them. The logs  
are fragile, handle with care - do not force into position.  
2) Place log 03-41 on the rear log support pins.  
03-42  
03-41  
Regency® L900E Direct Vent Gas Fireplace  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
5) Place the left end of log 03-43 into the pin while fitting the notch  
onto the burner tube. Slide the right end of the log forward until it is  
approximately 3/8" away from the back side of the grate.  
8) Spread all of the Embers on the bottom brick panel around the burner  
tube and on the inside of the grate as shown.  
Separate platinum embers and place on the embers around the  
burner tube and on the inside of the grate. Avoid stacking platinum  
embers.  
03-43  
Embers on bottom brick panel.  
Burner Tube  
6) Line up the two holes on the underside of log 03-44 with the pins on  
logs 03-41 and 03-42 and fit in place.  
03-44  
03-41  
03-42  
Embers on inside of grate.  
9) Spreadthevermiculiteonthebasebrickpanelcoveringtheremaining  
exposed base brick.  
7) Line up the two holes on the underside of log 03-45 with the pins on  
logs 03-41 and 03-43 and fit in place.  
03-45  
03-41  
03-43  
Regency® L900E Direct Vent Gas Fireplace  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
WIRING DIAGRAM  
Black  
Orange  
Lockout Led  
Black  
Reset Button  
Green  
Flame Sensor  
1
2
white  
J7  
NG/LP  
jumper  
ECS MODULE  
black  
yellow  
Spark Ignitor  
green  
white  
white  
black  
orange  
A
D
B
C
B
E
120V Power Source  
NEUTRAL (white)  
LIVE (black)  
red  
black  
MODULATING  
COIL  
(REAR)  
MAIN  
BURNER  
(EMBER)  
red  
SECONDARY  
BURNER  
black  
Battery  
Pin  
3
P.OUT  
4
2
1
VENT  
EV1  
EV2  
R.Q.  
ADJ.  
red  
red  
black  
black  
9V SOLENOID  
VALVE  
Areceptacle is provided on the left hand side of the unit. 120 VoltAC power  
must be wired to the receptacle and the control module plugged in for the  
unit to operate fully. The front and rear burners will operate on low, when  
the unit is running on battery back-up.  
Caution: Ensure that the wires do not touch any hot  
surfaces and are away from sharp edges.  
CAUTION:Labelallwirespriortodisconnectionwhen  
servicing controls. Wiring errors can cause improper  
and dangerous operation.  
(Do not cut the ground terminal off under any circumstances.)  
Regency® L900E Direct Vent Gas Fireplace  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
DO NOT BURN THE APPLIANCE  
MATCHING REMOTE  
HANDSET & CONTROL  
BOX ID CODE  
OPERATING  
WITHOUT THE GLASS FRONT IN  
PLACE.  
INSTRUCTIONS  
DO NOT ATTEMPT TO CLEAN THE  
GLASS WHILE IT IS STILL HOT!  
1) Read and understand these instructions  
before operating this appliance.  
The Remote Control Handset has a set of  
unique ID codes that is pre-programmed into its  
memory. This set of ID codes helps to differenti-  
ate one Remote Control Handset from another  
so that only the control box with a matching ID  
code will respond to the appropriate Remote  
Control Handset.  
2) Check to see that all wiring is correct and  
During the first few fires, a white film  
may develop on the glass front as part of  
the curing process. The glass should be  
cleaned after the unit has cooled down  
or the film will bake on and become very  
difficult to remove. Use a non-abrasive  
cleanerandDONOTATTEMPTTOCLEAN  
THE GLASS WHILE IT IS HOT.  
enclosed to prevent possible shock.  
3) Check to ensure there are no gas leaks.  
4) Make sure the glass in the door frame is  
properly positioned. Never operate the  
appliance with the glass removed.  
To ensure the remote control is matched to  
the receiver correctly, please follow the steps  
below:  
5) Verify that the venting and cap are  
unobstructed.  
1. Install the 2 xAAAalkaline batteries into the  
LIGHTING  
PROCEDURE  
Remote Control.  
6) Ensure that the brick panels are installed.  
2. Unplug and re-plug the power cord. The  
power cord is located on the left hand side  
of the appliance and will be plugged into the  
receptacle.  
7) Verify log placement. If the pilot cannot be  
seen when lighting the unit, the logs have  
been incorrectly positioned.  
1) Plug the power cord into a power outlet.  
2) Press and release the ON/OFF button once  
8) The unit should never be turned off, and on  
again without a minimum of a 60 second  
wait.  
on the Remote Control.  
3. Press and hold the PROG and FAN buttons  
simultaneouslyforupto20seconds.During  
this time, the remote will display LC while it  
is transmitting codes to the receiver.  
3) After approximately 3 seconds the spark  
ignition system will spark for 30 seconds to  
light the main burner.  
FIRST FIRE  
TheFIRSTFIREinyourheaterispartofthepaint  
curing process. To ensure the paint is properly  
cured,it is recommendedyou burnyourreplace  
for at least four (4) hours the first time.  
4. Once it is successfully transmitted, wait for  
20 seconds and press the ON/OFF button  
on the remote control once and the burners  
will come on.  
4) The unit will turn on.  
NOTE:  
If the unit does not turn on within 90 seconds  
of pressing the ON/OFF button on the Remote  
Control, this means that the system is in lockout  
mode.  
Ifisdoesnotworkthersttime,repeatsteps  
2 and 3.  
When first operated, the unit will release an  
odour caused by the curing of the paint and the  
burning off of any oils remaining from manufac-  
turing. Smoke detectors in the house may go off  
at this time. Open a few windows to ventilate  
the room for a couple of hours. The glass may  
require cleaning.  
5. The remote control is now programmed to  
the receiver and the appliance can now be  
operated with it.  
The unit will need to be reset as follows;  
a) Remove the left side exterior brick panel.  
b) Hold the reset button for 3 to 5 seconds or  
until the LED stops blinking.  
The control box will only learn the Remote ID  
codes during the first 30 seconds after power  
is applied and will ignore this special command  
from the Remote after the first 30 seconds.  
c) Repeat step 2.  
NOTE: The main burner will always start on  
"HIGH" and resume it's last setting after  
20 seconds of operation.  
Note:Forcompleteremotecontrolfunctionality  
refer to the Fire Wizard manual.  
NOTE: This must only be performed by a quali-  
fied installer.  
NOTE: Whentheglassiscoldandtheappliance  
is lit, it may cause condensation and fog  
the glass. This condensation is normal  
and will disappear in a few minutes as  
the glass heats up.  
SHUTDOWN  
PROCEDURE  
1) Press and release the ON/OFF button once  
on the Remote Control.  
2) If service is to be preformed, you must  
disconnectbothsourcesofpowertotheunit;  
main power and the battery.  
Regency® L900E Direct Vent Gas Fireplace  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
NORMAL OPERATING  
SOUNDS OF  
OPERATION DURING  
BACKUP BATTERY  
POWER OUTAGE  
Listedbelowareapprovedbatterytypesthatcan  
be used for replacement:  
GAS APPLIANCES  
In the event of a power failure, the unit will be  
fully functional for the first 45 minutes using the  
backup-battery system.  
Itispossiblethatyouwillhearsomesoundsfrom  
yourgasappliance.Thisisperfectlynormaldueto  
the fact that there are various gauges and types  
of steel used within your appliance. Listed below  
a) Powersonic 1.3AH  
b) Panasonic 1.3AH  
c) Henda 1.3AH  
If power resumes within the first 45 minutes you  
d) Magnacharge 1.3AH  
are some examples. All are normal operating can continue using the unit as normal.  
soundsandshouldnotbeconsideredasdefects  
CAUTION:  
in your appliance.  
If power is restored after 45 minutes you will  
need to reset the unit as follows;  
Risk of Energy Hazard, 12V, 1.3 Amphere-hour  
battery. Before replacing batteries, remove con-  
ductivejewelrysuchaschains,wristwatches,and  
rings. High energy through conductive materials  
could cause severe burns.  
Burner Tray:  
The burner tray is positioned directly under the  
burner tube and logs and is made of a different  
gauge material from the rest of the firebox and  
body.Therefore, thevaryingthicknessesofsteel  
will expand and contract at slightly different  
rates which can cause "ticking" and "cracking"  
sounds. You should also be aware that as there  
are temperature changes within the unit these  
sounds will likely re-occur. Again, this is normal  
for steel fireboxes.  
a) Remove the left side exterior brick panel.  
b) Hold the reset button for 3 to 5 seconds or  
until the LED stops blinking.  
Dispose of batteries at an authorized battery  
disposal site. Do not dispose of batteries in a  
fire. The batteries may explode.  
c) Press and release the ON/OFF button once  
on the Remote Control.  
Do not open or mutilate batteries. Released  
material is harmful to the skin and eyes. It may  
be toxic.  
Reset Button  
Pilot Flame:  
While the pilot flame is on it can make a very  
slight "whisper" sound.  
NOTE: This must only be performed by a quali-  
fied installer.  
Gas Control Valve:  
As the gas control valve turns ON and OFF, a  
dull clicking sound may be audible, this is normal  
operation of a gas regulator or valve.  
Unit Body/Firebox:  
Different types and thicknesses of steel will  
expand and contract at different rates resulting  
in some "cracking" and "ticking" sounds will be  
heard throughout the cycling process.  
Located on the left hand side of the  
firebox behind the exterior brick panel.  
Regency® L900E Direct Vent Gas Fireplace  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
COPY OF LIGHTING PLATE INSTRUCTIONS  
FOR YOUR SAFETY READ BEFORE LIGHTING  
This appliance must be installed in accordance with local codes, if any;  
if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or  
Natural Gas and Propane Installation Codes, CSA B149.1.  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life. Improper  
installation, adjustment, alteration, service or maintenance can cause injury  
or property damage. Refer to the owner’s information manual provided with  
this appliance. For assistance or additional information consult a qualified  
installer, service agency or gas supplier.  
A) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor  
because some gas is heavier than air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
- Do not try to light any appliance.  
- Do not touch any electric switch, do not use any phone in your building.  
- Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s  
instructions.  
- If you cannot reach your gas supplier, call the fire department.  
B) Do not use this appliance if any part has been under water. Immediately call a qualified service  
technician to inspect the appliance and to replace any part of the control system and any gas  
control which has been under water.  
C) This appliance needs fresh air for safe operation and must be installed so there are provisions for  
adequate combustion and ventilation air.  
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due  
to high surface temperatures keep children, clothing and furniture, gasoline and  
otherliquidshavingammablevaporsaway.Keepburnerandcontrolcompartment  
clean. See installation and operating instructions accompanying appliance.  
LIGHTING INSTRUCTIONS  
STOP! Read the safety information above on this label.  
1) Plug the power cord into a power outlet.  
2) Press and release the ON/OFF button once on the Remote Control.  
3) After approximately 3 seconds the spark ignition system will spark for 30  
seconds to light the main burner.  
4) If the main burner does not light within 90 seconds, you must reset the  
unit. See instruction manual for details.  
TO TURN OFF GAS APPLIANCE  
1) Press the ON/OFF button once on the Remote Control.  
2) If service is to be performed, you must disconnect both sources of power  
to the unit; main power and the battery.  
918-628  
DO NOT REMOVE THIS INSTRUCTION PLATE  
Regency® L900E Direct Vent Gas Fireplace  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
MAINTENANCE  
INSTRUCTIONS  
1) Always turn off the unit before cleaning. For  
relighting,refertolightinginstructions.Keep  
the burner and control compartment clean  
by brushing and vacuuming at least once  
a year. When cleaning the logs, use a soft  
clean paint brush as the logs are fragile and  
easily damaged.  
GENERAL VENT  
MAINTENANCE  
Conduct an inspection of the venting system  
semiannually. Recommended areas to inspect  
as follows:  
GLASS GASKET  
If the glass gasket requires replacement use a  
tadpole glass gasket (Part # 936-155).  
DOOR GLASS  
1) Check the Venting System for corrosion in  
areas that are exposed to the elements.  
These will appear as rust spots or  
streaks, and in extreme cases, holes.  
These components should be replaced  
immediately.  
Your Regency® fireplace is supplied with high  
temperature 5mm-Ceramic glass. If your glass  
requires cleaning, we recommend using an  
approvedglasscleaneravailableatallauthorized  
dealers. Do not use abrasive materials.  
2) Clean appliance and door with a damp  
cloth (never when unit is hot). Never use  
an abrasive cleaner. The glass should be  
cleaned with a gas fireplace glass cleaner.  
The glass should be cleaned when it  
starts looking cloudy.  
2) Remove the Cap, and shine a flashlight  
down the Vent. Remove any bird nests, or  
other foreign material.  
CAUTION & WARNINGS:  
*
Do not clean when the glass is hot.  
3) Check for evidences of excessive  
condensation,suchaswaterdropletsforming  
in the inner liner, and subsequently dripping  
outthejoints,Continuouscondensationcan  
cause corrosion of caps, pipe, and fittings.  
It may be caused by having excessive  
lateral runs, too many elbows, and exterior  
portions of the system being exposed to  
cold weather.  
* Theuseofsubstituteglasswillvoidallproduct  
3) The heater is finished in a heat resistant  
paintandshouldonlyberefinishedwithheat  
resistant paint. Regency® uses StoveBright  
Paint - Metallic Black #6309.  
warranties.  
* Care must be taken to avoid breakage of the  
glass.  
*
Do not strike or abuse the glass.  
* Do not operate this fireplace without the  
glass front or with a cracked or broken glass  
front.  
4) Make a periodic check of burner for proper  
position and condition. Visually check the  
flameoftheburnerperiodically,makingsure  
the flames are steady; not lifting or floating.  
If there is a problem, call a qualified service  
person.  
* Wear gloves when removing damaged or  
broken glass.  
* Replacement of the glass panel(s) should be  
done by a licensed or qualified service per  
son.  
4) Inspect joints, to verify that no pipe  
sections or fittings have been disturbed,  
and consequently loosened. Also check  
mechanical supports such as Wall Straps,  
or plumbers' tape for rigidity.  
5) The appliance and venting system must be  
inspected before use, and at least annually,  
byaqualifiedeldserviceperson, toensure  
that the flow of combustion and ventilation  
air is not obstructed.  
GLASS REPLACEMENT  
Intheeventthatyoubreakyourglassbyimpact,  
purchase your replacement from an authorized  
Regency® dealer only.  
LOG REPLACEMENT  
Note: Never operate the appliance without  
the glass properly secured in place.  
The unit should never be used with broken logs.  
Turn off the unit and allow the unit to cool before  
opening door and carefully remove the logs. If  
for any reason a log should need replacement,  
you must use the proper replacement log. The  
position of these logs must be as shown in the  
diagrams under Log Installation.  
Replacement glass is shipped already installed  
into the door frame.  
6) Donotusethisapplianceifanyparthasbeen  
under water. Immediately call a qualified  
service technician to inspect the appliance  
andtoreplaceanypartofthecontrolsystem  
and any gas control which has been under  
water.  
CAUTION: Wear gloves when  
removing damaged or broken  
glass.  
Note: Improper positioning of logs may  
create carbon build-up and will  
severely alter the unit's performance  
which is not covered under  
warranty.  
7) In the event this appliance has been  
serviced check that the vent-air system  
has been properly resealed & reinstalled  
in accordance with the manufacturer's  
instructions.  
WARNING: Do not operate the  
appliance with the glass panels  
removed, cracked or broken.  
Replacement of the glass panels  
should be done by a licensed or  
qualified service person.  
8) Verify operation after servicing.  
Regency® L900E Direct Vent Gas Fireplace  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTAINENCE  
CONTROL BOX REPLACEMENT  
1) Remove the exterior brick panels.  
BACK-UP BATTERY REPLACEMENT  
1) Disconnect the power cord, located on the left hand side of the  
firebox.  
Power  
Receptacle  
2) Remove the glass door.  
a. Release the 2 door latches on the left and right side at the top of  
the firebox.  
Latch Location  
Latch  
Heat  
Shield  
2) Loosen the 2 screws that hold the right side heat shield in place.  
3) Lift the heat shield up and pull out slightly to clear the head screws  
and then hang it on the top bracket (located directly above the heat  
shield, close to the top of the firebox).  
4) Remove the battery by lifting off the velcro and bring out from the side  
b. Swing the door out from the top and release the hinges on the  
left and right side of the door by lifting them up.  
of the firebox.  
Backup  
Battery  
Hinge  
Door  
3) Loosen the 2 screws that hold the right side heat shield in place.  
5) Disconnect the wires connected to the battery.  
Heat  
Shield  
6) Replace with new battery and reconnect battery wires accordingly.  
7) Re-install the battery to the right side of the firebox.  
8) Re-install the right side heat shield.  
Regency® L900E Direct Vent Gas Fireplace  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
4) Disconnect both sources of power; the power cord, located on the  
left hand side of the firebox and the wires connected to the back-up  
battery located on the right side of the firebox.  
7) Disconnect the spark cable and valve sensor wires from the control  
board.  
Backup  
Power  
Battery  
Receptacle  
5) Remove the control box by carefully lifting off the velcro and sliding it  
8) Remove the cable tie from control box to release the wires. Do not  
out from the side of the firebox.  
discard cable tie.  
9) Remove the Ground screw from the control box.  
6) Disconnect the wire harnesses from the control board labelled A, C,  
D, E & F. Do not disconnect the the jumper cables labelled B.  
F
10) Replace the control box.  
11) Reverse steps 9 to 1. When re-connecting wire harnesses. Ensure  
that the cables match the letters labelled on the control box and are  
securely connected.  
A
C
D
E
Jumper Cable 'B'  
DO NOT REMOVE  
Regency® L900E Direct Vent Gas Fireplace  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
VALVE TRAY REPLACEMENT  
1) Remove the exterior brick panels.  
3) Loosen the screw that holds the right side  
8) Remove the grate by undoing the 2 screws  
heat shield in place.  
on the right and left side.  
2) Remove the glass door.  
a. Release the 2 door latches on the left  
and right side at the top of the firebox.  
Latch Location  
Grate  
Heat  
Shield  
9) Remove the front burner by removing the  
screw.  
Latch  
4) Lift up and pull out the heat shield slightly  
to clear the screwheads and then hang it  
on the top bracket (located directly above  
the heat shield).  
5) Disconnect both sources of power; the  
power cord, located on the left hand side of  
the firebox and the wires connected to the  
back-up battery located on the right side of  
the firebox.  
b. Swingthedooroutfromthetopandrelease  
the hinges on the left and right side of the  
door by lifting them up.  
Front Burner  
Backup  
Battery  
Hinge  
Door  
Power  
Receptacle  
Front Burner Removed  
10) Remove the back burner by removing the  
screw.  
c. Placethedooronasoftsurfacetoprevent  
scratching.  
6) Remove the log set.  
7) Remove the interior brick panels.  
Back Burner  
Regency® L900E Direct Vent Gas Fireplace  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
11) Remove the rear log stand by removing  
16) Remove the igniter wire and the  
the 4 screws.  
thermocouple wire from the control box.  
Rear Log Stand  
Valve Tray Slightly Removed  
20) Ensure that all wiring is free and clear  
of any obstructions. Completely pull out the  
valve tray.  
17) Release the two grey wire clips on the  
bottom of the fireplace to release the wires  
attached to the valve assembly.  
12) Carefully remove the bottom brick panel.  
21) Replace the valve tray and reverse steps  
to re-install.  
22) Turn on the gas supply and check for gas  
leaks.  
23) Re-connect both sources of power.  
24) Re-install the left heat shield.  
25) Re-install the grate.  
Bottom Brick Panel  
13) Disconnect the inlet gas line from the  
26) Re-install the interior brick panels.  
27) Re-install the log set.  
valve.  
18) Disconnect the black and red wires from  
14) Disconnect the 2 connectors from the  
the solenoid valve.  
modulating coil.  
28) Re-install the glass door.  
29) Check the inlet and outlet pressures.  
30) Re-install the right heat shield.  
31) Check operation of flame control.  
32) Check for proper flame appearance.  
33) Re-install the exterior brick panels.  
15) Disconnect the molex connector from the  
valve.  
19) Remove the 16 screws that hold the valve  
tray to the firebox and slightly pull out the  
valve tray.  
Molex Connector  
Valve Tray  
Modulating Coil  
Regency® L900E Direct Vent Gas Fireplace  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
MAIN ASSEMBLY  
Part #  
Description  
1
2
1) 521-527  
2) 502-008  
Flue Collar Inner Assembly  
Flue Collar Outer  
5) 904-751  
6) W260280  
7) 770-066F  
8) 942-117  
9) W260260  
Capscrew 1/4 x 4-1/2  
Gasket Top Relief Plate  
Top Relief Plate  
Top Relief Frame  
Top Relief Frame Gasket  
11) 910-950  
910-075  
IPI Control Box and Battery Backup  
Backup Battery (Not shown)  
Door Frame Assembly with Glass  
Glass  
5
6
7
12) 546-540  
940-354/P  
13) 546-013  
One Piece Faceplate  
8
15) 521-021F  
16) 521-019  
17) 546-070  
18) 521-072  
Control Arm  
Bracket Control Arm  
Heat Shield Valve  
Gas Line Screen Plate  
9
20) 546-901  
546-902  
Brick Panel Set - Standard Brown  
Brick Panel Set - Standard Red  
*
Left Side Panel (Interior)  
Top Panel (Interior)  
*
*
Back Panel (Interior)  
Right Side Panel (Interior)  
Right Side Panel (Exterior)  
Base Panel (Exterior)  
Left Side Panel (Exterior)  
Heat Wave Kit  
*
*
*
*
946-556  
946-570  
546-969E  
918-623  
Heat Release Kit  
LP Converison Kit  
12  
Manual  
15  
17  
* Not available as a replacement part.  
13  
16  
11  
18  
20  
Regency® L900E Direct Vent Gas Fireplace  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
BURNER & LOG ASSEMBLY  
Part #  
Description  
Part #  
Description  
910-937  
Valve Solenoid  
30) 521-015  
31) 546-016  
32) 546-042  
Bracket Log Tray  
Log Tray  
Deflector Log Tray  
546-930  
546-935  
Birch Log Set  
Oak Log Set  
35) 948-459  
36) 948-458  
37) 546-050  
Burner Rear NG/LP  
Burner Front NG/LP  
Grate  
910-960  
918-619  
FireWizardTM Remote Control  
Manual FireWizardTM-E  
41) 502-061  
42) 380-013  
43) W840470  
Pilot Shield  
Pilot Holder  
Gasket Pilot Assembly  
46) 521-007  
47) 546-025  
48) 910-480  
Valve Tray  
Valve Bracket  
31  
Valve 845 SIT Electric  
546-547  
Valve Tray Assembly  
49) 910-952  
910-953  
Pilot Assembly - NG  
Pilot Assembly - LP  
904-617  
904-622  
904-241  
904-641  
NG - Orifice #30  
NG - Orifice #47  
LP - Orifice #56  
LP - Orifice #50  
32  
35  
41  
36  
49  
42  
43  
37  
47  
46  
48  
Regency® L900E Direct Vent Gas Fireplace  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit  
thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a  
Regency® Product. This warranty is not transferable.  
The Warranty: Limited Lifetime  
The combustion chamber, heat exchanger, burner tubes, logs, brick panels (against defective manufacture only) are covered under the Limited Lifetime Warranty for five (5) years  
for parts and subsidized labour* and parts only thereafter.  
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for five (5) years and parts only thereafter from date of purchase.  
Electrical and mechanical components such as switches, wiring, FPI remote controls, pilot assembly components, control boards and gas valves are covered for two years parts  
and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue as if new with appliance. ie. twelve  
(12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.  
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.  
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.  
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any item  
shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.  
Conditions:  
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided  
that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.  
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for  
manufacturer defect.  
The authorized selling dealer is responsible for all in-field service work carried out on your Regency® product. FPI will not be liable for results or costs of workmanship from  
unauthorized service persons or dealers.  
At all times FPI reserves the right to inspect product in the field which is claimed to be defective.  
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name, purchase  
date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.  
Exclusions:  
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.  
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured.  
ie. as products evolve, field modifications or upgrades will not be performed.  
FPI will not be liable for travel costs for service work.  
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.  
Embers, gaskets, and paint are not covered under the terms of this warranty policy.  
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.  
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence  
or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical  
systems such as furnaces, fans, clothes dryer, etc.  
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.  
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.  
Performance problems due to operator error will not be covered by this warranty policy.  
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty on  
this product.  
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.  
* Subsidy according to job scale as predetermined by FPI.  
Regency® L900E Direct Vent Gas Fireplace  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FPI fireplaces are designed with reliability and simplicity  
in mind. In addition, our internal Quality Assurance Team  
carefully inspects each unit thoroughly before it leaves  
our door.  
FPI FireplaceProductsInternationalLtd.ispleasedtoextend  
this Limited Lifetime Warranty to the original purchaser of  
a FPI Product.  
See the inside back cover for details.  
Register your Regency® online at  
Installer: Please complete the following information  
Dealer Name & Address:______________________________________________  
___________________________________________________________________  
Installer: ___________________________________________________________  
Phone #: ___________________________________________________________  
Date Installed: ______________________________________________________  
Serial No.:__________________________________________________________  
Regency, Liberty, AstroCap, HeatWave, Heat Release and FireWizard are trademarks of FPI Fireplace Products International Ltd.  
© Copyright 2008, FPI Fireplace Products International Ltd. All rights reserved.  
Printed in Canada  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Q See DVR QSD42908 User Guide
Radio Shack Clock Radio 12 1655 User Guide
Raymarine TV Mount E46034 User Guide
RCA Home Theater System RTD980 User Guide
RocketFish Headphones RF 9640 User Guide
Roland Electronic Keyboard FP 2 User Guide
Saleen Automobile Parts S281SC User Guide
Samsung Digital Camera 3500 User Guide
Sangean Electronics Clock Radio WR5 User Guide
Sears Lawn Mower 94436201 User Guide