XFyre™- Type H
Condensing Heating Boilers
Models 300-850
Job:
Engineer:
Contractor:
Prepared By:
Model:
Date:
Indoor/Outdoor:
Up to 94% Thermal Efficiency at Full Rate
100% Factory Fire Tested
Maximum Outlet Water Temperature: 210°F
Maximum System Temperature: 200°F
Full Safety Diagnostics with History
Footprint: Less Than 9-1/2 ft2
Limited Twenty-Year Thermal Shock Warranty
Limited Ten-Year Heat Exchanger Warranty
Full Electronic Modulation, Constant Ratio 5:1 Turndown
Soft-Start Modulating Controller with LCD Display
Status and Full Diagnostics Display
Heat Exchanger
All Stainless Steel Construction
Gasketless Heat Exchanger Design
ASME H Stamped
160 PSIG Working Pressure
National Board Approved
ASME Pressure Relief Valve
Multi-Boiler System Controllers
B-36 TempTracker Mod+ Digital
Controller, 2-4 Boilers, OA Reset
B-37 TempTracker Mod+ Digital
Controller, 5-10 Boilers, OA Reset
B-38 TempTracker Mod+ Digital
Controller, 11-16 Boilers, OA Reset
Gas Train
Fuel
Natural Gas
Propane
Zero Governor Regulator
Dual-Seat Combination Valve
Electronic Modulating Firing Mode (H7)
60 PSIG – Standard
Options
PSIG – Optional
Temperature and Pressure Gauge,
Shipped Loose
Construction
D-21 TruSeal™ Combustion Air Inlet
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Electrical, Gas, Vent,
Combustion Air)
Top Connections (Water)
Design Certified ANSI Z21.13/
CSA 4.9
P-
Pump:
Cast Iron
HP, 120V, 1∅, 60Hz
Bronze
Control
S-1
S-2
Low Gas Pressure Switch,
Manual Reset
High Gas Pressure Switch,
Manual Reset
120V, 60Hz, 1Ø, Power Supply
Digital Operating Control with LCD
display.
Outdoor reset with Indirect Priority
0-10 VDC input for BMS
Cascade up to 8 boilers
Spark Ignition (IID)
Remote Flame Sensor
High Limit, Manual Reset, Fixed,
200ºF
Z-12 Condensate Neutralizer Kit
Venting (PVC-CPVC-Stainless.)
Vent Termination
Indoor, Vertical – Option D-11
Indoor, Horizontal – Option D-15
Outdoor
Regulatory Agency Requirements
Auto Limit, Fixed, 210ºF
Alarm Dry Contact Connection
On/Off Power Switch
Flow Switch
Extractor - Optional
By others
Not required
Blocked Vent Pressure Switch
Boiler, DHW & System Pump
Contacts
Water Temperature Sensors (3)
Burner
Ultra-Low NOx: Less than 20 PPM
Catalog No.: 2000.17
Effective: 6-22-09
Replaces: New
Download from Www.Somanuals.com. All Manuals Search And Download.
|