Rackmount Solutions Power Supply E1000RM1U User Guide

Download from Www.Somanuals.com. All Manuals Search And Download.  
Enterprise 1U Rackmount Series User's Manual  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Introduction  
2
Controls and Indicators  
Installation  
6
8
Operation  
12  
15  
16  
19  
20  
22  
23  
25  
Troubleshooting  
Replacing the Battery  
Obtaining Service  
Specifications  
Configurable Parameters & Settings  
10. Limited Product Warranty  
11. Declaration of Conformity  
©
Copyright Para Systems, Inc., 2005  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Thank you for purchasing a MINUTEMAN power protection product. It has been  
designed and manufactured to provide many years of trouble free service.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS !  
Please read this manual before installing your Enterprise 1U Rackmount Se-  
ries UPS, models E700RM1U, E1000RM1U, E1500RM1U, as it provides im-  
portant information that should be followed during installation and maintenance  
of the UPS and batteries allowing you to correctly set up your system for the  
maximum safety and performance. Included is information on customer sup-  
port and factory service if it is required. If you experience a problem with the  
UPS please refer to the Troubleshooting guide in this manual to correct the  
problem or collect enough information so that the MINUTEMAN Technical Sup-  
port Department can rapidly assist you.  
This symbol indicates "ATTENTION"  
This symbol indicates "Risk of Electrical Shock"  
This symbol indicates "Alternating Current Supply Phase"  
This symbol indicates "Alternating Current Supply"  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
This symbol indicates "Direct Current Supply"  
This symbol indicates "Equipment Grounding Conductor"  
CAUTION! Connect the UPS to a two pole, three wire grounding  
AC wall outlet. The receptacle must be connected to the appropriate  
branch protection (circuit breaker or fuse). Connection to any other  
type of receptacle may result in a shock hazard and violate local  
electrical codes. Do not use extension cords, adapter plugs, or surge  
strips.  
CAUTION! To reduce the risk of electrical shock with the installa-  
tion of this UPS equipment and the connected equipment, the user  
must ensure that the combined sum of the AC leakage current does  
not exceed 3.5mA.  
CAUTION! To reduce the risk of electrical shock in conditions  
where the load equipment grounding cannot be verified, disconnect  
the UPS from theAC wall outlet before installing a computer interface  
cable. Reconnect the power cord only after all signaling connections  
are made.  
WARNING: This Uninterruptible Power Supply contains potentially  
hazardous voltages. Do not attempt to disassemble the UPS beyond  
the battery replacement procedure. This UPS contains no user ser-  
viceable parts. Repairs and Battery replacement must be performed  
by QUALIFIED SERVICE PERSONNEL ONLY.  
WARNING: Risk of Electrical Shock. Hazardous live parts inside  
these power supplies are energized from the battery even when the  
AC input is disconnected.  
CAUTION! To de-energize the outputs of the UPS:  
1. If the UPS is on press and release the On/Off/Test button.  
2. Disconnect the UPS from the AC wall outlet.  
3. To de-energize the UPS completely, disconnect the battery.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTICE: This equipment has been tested and found to comply with  
the limits for a ClassAcomputing device in accordance with the speci-  
fications in Subpart J of Part 15 of FCC Rules and the ClassAlimits for  
radio noise emissions from digital apparatus set out in the Radio Interference of  
the Canadian Department of Communications. These limits are designed to  
provide reasonable protection against such interference in a residential installa-  
tion. This equipment generates and uses radio frequency and if not installed  
and used properly, that is, in strict accordance with the manufacturer's instruc-  
tions, this equipment may cause interference to radio and television reception.  
If this equipment does cause interference to radio or television reception, which  
can be determined by turning the equipment off and on, the user is encouraged  
to try to correct the interference by one or more of the following measures:  
Re-orient the receiving antenna.  
Relocate the computer with respect to the receiver.  
Move the computer away from the receiver.  
Plug the computer into a different outlet so that the computer and receiver  
are on different branch circuits.  
Shielded communications interface cables must be used with this product.  
WARNING: Changes or modifications to this unit not expressly ap-  
proved by the party responsible for compliance could void the user's  
authority to operate the equipment.  
Receiving Inspection  
After removing your MINUTEMAN UPS from its carton, it should be inspected  
for damage that may have occurred in shipping. Immediately notify the carrier  
and place of purchase if any damage is found. Warranty claims for damage  
caused by the carrier will not be honored. The packing materials that your UPS  
was shipped in are carefully designed to minimize any shipping damage. In the  
unlikely case that the UPS needs to be returned to MINUTEMAN, please use  
the original packing material. Since MINUTEMAN is not responsible for ship-  
ping damage incurred when the system is returned, the original packing mate-  
rial is inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!  
NOTE: These UPSs are shipped with the batteries disconnected. The batter-  
ies must be connected before putting these UPSs into service. Refer to Sec-  
tion 3 "Installation" for connecting the batteries.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Para Systems Life Support Policy  
As a general policy, Para Systems Inc. (Para Systems) does not recommend  
the use of any of its products in life support applications where failure or mal-  
function of the Para Systems product can be reasonably expected to cause  
failure of the life support device or to significantly affect its safety or effective-  
ness. Para Systems does not recommend the use of any of its products in  
direct patient care. Para Systems will not knowingly sell its products for use in  
such applications unless it receives in writing assurances satisfactory to Para  
Systems that (a) the risks of injury or damage have been minimized, (b) the  
customer assumes all such risks, and (c) the liability of Para Systems Inc. is  
adequately protected under the circumstances.  
Examples of devices considered to be life support devices are neonatal oxygen  
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other  
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia  
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis  
systems, neonatal ventilator incubators, ventilators for both adults and infants,  
anesthesia ventilators, and infusion pumps as well as any other devices desig-  
nated as “critical” by the United States FDA.  
Hospital grade wiring devices and leakage current may be ordered as options  
on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim  
that units with this modification are certified or listed as Hospital Grade by  
PARA SYSTEMS or any other organization. Therefore, these units do not  
meet the requirements for use in direct patient care.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROL PANEL  
The AC normal (green) LED illuminates in a steady state when the  
UPS is on and operating in the AC normal mode. The AC normal  
LED will extinguish when operating in the Battery mode.  
The On-Battery (green) LED illuminates in a steady state when the  
UPS is operating in the Battery mode. The On-Battery LED will  
extinguish when operating in the AC normal, Boost and Buck modes.  
The Boost (yellow) LED illuminates in a blinking state when the  
UPS is operating in the Boost mode. The Boost LED will extinguish  
when operating in theAC normal, Buck and Battery modes.  
The Buck (yellow) LED illuminates in a blinking state when the UPS  
is operating in the Buck mode. The Buck LED will extinguish when  
operating in theAC normal, Boost and Battery modes.  
The Fault (red) LED illuminates in a steady state when the UPS  
detects an internal fault. The Fault LED is extinguished when the  
UPS is operating properly.  
The Weak/Bad Battery (red) LED illuminates in a steady state when  
the UPS detects a weak battery, bad battery or if the battery is  
disconnected. The Weak/Bad Battery LED is extinguished when  
the battery's condition is good.  
The Site Wiring Fault (red) LED illuminates in a steady state when  
the UPS detects a site wiring problem. The Site Wiring Fault LED is  
extinguished when the UPS is connected to proper site wiring.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Load Level Bar Graph operates as follows:  
LED #10: >10% load (green/red/yellow) LED will be green and illu-  
minated when there is at least 10% of the rated capacity.  
LED #30: >30% load (green/yellow) LED will be green and illumi-  
nated when there is at least 30% of the rated capacity.  
LED #50: >50% load (green/yellow) LED will be green and illumi-  
nated when there is at least 50% of the rated capacity.  
LED #70: >70% load (green/yellow) LED will be green and illumi-  
nated when there is at least 70% of the rated capacity.  
LED #90: >90% to approximately 109% load (red/yellow) LED will  
be yellow and illuminated when there is approximately 90% of the  
rated capacity to indicate that unit is near full capacity. The LED  
will turn red at 110% load capacity to indicate an Overload condi-  
tion.  
The Battery Capacity Bar Graph operates as follows:  
LED #90: >90% battery capacity (red/yellow) LED will be yellow  
and illuminated until the battery’s capacity drops below 80% ca-  
pacity and then it will extinguish.  
LED #70: >70% battery capacity (green/yellow) LED will be yellow  
and illuminated until the battery’s capacity drops below 60% ca-  
pacity and then it will extinguish.  
LED #50: >50% battery capacity (green/yellow) LED will be yellow  
and illuminated until the battery’s capacity drops below 40% ca-  
pacity and then it will extinguish.  
LED #30: >30% battery capacity (green/red/yellow) LED will be yel-  
low and illuminated until the battery’s capacity drops below 30%  
capacity and then it will turn red. When the battery capacity drops  
below 20% capacity the LED will extinguish.  
LED #10: >30% battery capacity (green/red/yellow) LED will be yel-  
low and illuminated until the unit issues a Low Battery Warning  
Alarm and then it will turn red to indicate a Low Battery Warning.  
The Multi-Function On/Off/Test Button functions as follows:  
When the UPS is Off, press and release the On/Off/Test button  
after one beep to turn the UPS On.  
When the UPS is On, press and release the On/Off/Test Button  
after one beep to turn the UPS Off.  
When the UPS is On, press and hold the On/Off/Test button for four  
beeps, then release the button. The UPS will perform a 5-second  
Self Test.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
REAR PANEL  
1. The input power cord has a NEMA 5-15P Plug.  
2. The input circuit breaker will trip in the event the load exceeds the UPS’s  
power rating.  
3. The Battery Backup output power receptacles are NEMA 5-15R type. The  
output receptacles are electrically wired into two segments to support the  
"Load Shedding Function". The three receptacles on the left are Segment 1  
and the three receptacles on the right are Segment 2.  
4. The RS232 Communications Interface Port is for UPS monitoring and con-  
trol.  
5. The R-J11/R-J45 modular connectors are used for 10/100 Base-T Network/  
single line Phone/Fax/Modem protection.  
6. The USB Communications Interface Port is for UPS monitoring and control.  
7. The Dipswitches are for setting the Inverter (On-Battery) output voltage.  
8. The option slot will support MINUTEMAN option cards only.  
INSTALLATION PLACEMENT  
The Enterprise 1U Rackmount Series is intended to be install in a temperature  
controlled environment that is free of conductive contaminants. Select a loca-  
tion which will provide good air circulation for the UPS at all times. Avoid loca-  
tions near heating devices, water or excessive humidity, or where the UPS is  
exposed to direct sunlight. Route power cords so they cannot be walked on or  
damaged.  
Operating Temperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F)  
Operating Elevation: 0 to 3,000m (0 to 10,000 ft)  
Operating and Storage Relative Humidity: 95%, non-condensing  
Storage Temperature: -15 to +45 degrees C (+5 to +113 degrees F)  
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Be sure to read the installation placement and all the cautions before installing  
the UPS. Place the UPS in the final desired location and complete the rest of  
the installation procedure. These UPSs are shipped with the internal batteries  
disconnected. The batteries must be connected before putting these UPSs  
into service. Follow the procedure below to connect the batteries and install  
the UPS into the rack. USE CAUTION: The UPS is heavy. Use the appropri-  
ate number of personnel when installing the UPS.  
Connecting the Batteries  
1. Remove the UPS from the shipping box and set on the floor or a bench top.  
2. Grasp the front panel and gently pull it off the UPS. (FIG. 1)  
3. Remove the four retaining screws for the battery retaining bracket. (FIG. 2)  
4. Remove the battery retaining bracket. (FIG. 2)  
5. Grasp the battery tray and gently pull the battery tray out far enough to get to  
the battery connectors (red and black). (FIG. 3)  
6. Connect the battery connectors (red and black) together.  
7. Gently slide the battery tray back into the UPS.  
8. Re-install the battery retaining bracket.  
9. Re-install the four retaining screws for the battery retaining bracket.  
10. Re-install the front panel onto the UPS.  
FIG. 1  
FIG. 2  
FIG. 3  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the UPS in a 4-post rack  
USE CAUTION: The UPS is heavy. Use the appropriate number of personnel  
when installing the UPS.  
1. Install the rails in the 4-post rack. (FIG. 1)  
2. Install the rack ears on the UPS. (FIG. 2)  
3. Align the cleats with the rails and slide the UPS into the rails. (FIG. 3)  
NOTE: The cleats are pre-mounted on the UPS.  
4. Secure the UPS to the rack with the retaining screws (not provided). The  
UPS is ready for normal operation, see connecting your equipment.  
Installing the UPS in a 2-post rack  
USE CAUTION: The UPS is heavy. Use the appropriate number of personnel  
when installing the UPS. MINUTEMAN recommends that the UPS be installed  
at the bottom of the rack and that the rack ears be installed as FIG. 4.  
1. Install the rack ears on the UPS. (FIG. 4)  
NOTE: If you are installing the rack ears in the middle of the UPS, the pre-  
mounted cleats will have to be removed from the UPS.  
2. Secure the UPS to the rack with the retaining screws (not provided). The  
UPS is ready for normal operation; see connecting your equipment.  
FIG. 1  
FIG. 2  
FIG. 3  
FIG. 4  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECTING YOUR EQUIPMENT  
Plug the equipment into the output receptacles on the rear panel of the UPS.  
Do not use extension cords, adapter plugs or surge strips on the output of the  
UPS. Ensure that you do not exceed the maximum output rating of the UPS  
(refer to the information label on the UPS or the Electrical Specifications in this  
manual).  
DO NOT connect a laser printer to the output receptacles on the  
CAUTION!  
UPS, unless the UPS is rated 2000VAor greater. Alaser printer  
draws significantly more power when printing than at idle and  
may overload the UPS.  
CONNECTING THE UPS TO AN AC SOURCE  
Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use  
extension cords, adapter plugs, or surge strips.  
CHECKING THE SITE WIRING FAULT  
After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the  
control panel of the UPS. If the SWF LED is illuminated, the UPS is plugged  
into an improperly wired AC outlet. If the UPS indicates a Site Wiring Fault  
(SWF), have a Qualified Electrician correct the problem.  
CHARGING THE BATTERY  
The Enterprise 1U Rackmount Series UPS will charge the internal batteries  
whenever the UPS is connected to an AC source. It is recommended that the  
UPS's batteries be charged for a minimum of 4 hours before use. The UPS  
may be used immediately, however, the “On-Battery” runtime may be less than  
normally expected. NOTE: If the UPS is going to be out of service or stored for  
a prolonged period of time, the batteries must be recharged for at least twenty-  
four hours every ninety days.  
COMMUNICATIONS PORT CONNECTION (OPTIONAL)  
MINUTEMAN Power Monitoring Software and interface cables kits can be used  
with the Enterprise 1U Rackmount Series UPS. Use only MINUTEMAN or  
MINUTEMAN approved interface cables with these UPSs. Connect the inter-  
face cable (Serial or USB) to the appropriate communications port on the rear  
panel of the UPS. Connect the other end of the cable to the device that will be  
monitoring/controlling the UPS. NOTE: Connecting to the Communications  
Port is optional. The UPS works properly without this connection.  
NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL)  
Connect a 10/100 Base-T network, single line phone, Fax or Modem line to the  
RJ11/45 protection sockets on the rear panel of the UPS. This connection will  
require another length of telephone or network cable. The cable coming from  
the telephone service or networked system is connected to the port marked  
“IN”. The equipment to be protected is connected to the port marked "OUT".  
NOTE: Connecting to the Network/Phone/Fax/Modem protection socket con-  
nection is optional. The UPS works properly without this connection.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM OVERVIEW  
This Line-Interactive 1U Rackmount model UPS protects internetworking and  
telecommunications equipment from blackouts, brownouts, overvoltages, and  
surges. The AVR function continuously corrects the voltages, in-between the  
brownout and overvoltage transfer points (85 - 150VAC), to a safe usable level.  
When the UPS is operating in the AVR mode the audible alarm will remain  
silent and the Boost or the Buck indicator will blink. During normal AC opera-  
tion, the MINUTEMAN UPS will quietly and confidently protect your system  
from power anomalies.  
The UPS will charge the batteries with the UPS in the on or off position as long  
as the UPS is plugged into the wall outlet and there is an acceptableAC voltage  
present. When a blackout, brownout, or an overvoltage condition occurs; the  
UPS will transfer to the battery mode, the On-Battery indicator will illuminate  
and the audible alarm will sound once every ten-seconds indicating that the  
commercial power is lost or unacceptable. When the commercial power re-  
turns or is at an acceptable level, the UPS will automatically transfer back to  
the AC normal mode and start recharging the batteries. During an extended  
outage when there is approximately two-minutes of backup time remaining the  
audible alarm will sound twice every five-seconds. This Low Battery Warning is  
letting the user know that they should save all open files and turn off their  
computer. When the batteries reach the pre-determined level the UPS will  
automatically shutdown protecting the batteries from over discharging. Once  
the commercial power returns the UPS will automatically restart, providing safe  
usable power to the connected equipment and start recharging the batteries.  
TURNING THE UNIT ON/OFF  
On / Off / Test Button  
Press and release the On/Off/Test Button after one beep to turn the UPS on  
and supply power to the load. The load is immediately powered while the UPS  
runs a five-second self test. Press and release the On/Off/Test Button after one  
beep to turn the UPS off. The UPS will continue to charge the batteries when-  
ever it is plugged into a wall outlet and there is AC present.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SELF TEST  
The self test feature is useful to verify the correct operation of the UPS and the  
condition of the batteries. With the UPS in the AC normal mode, press and  
hold the On/Off/Test Button for four beeps, then release the button. The UPS  
will perform a ten-second self test. During the self test, the UPS will switch to  
battery power and the On-Battery LED will illuminate and the audible alarm will  
sound. The length of the test that is automatically performed every two weeks  
is longer than the start-up or user invoked test. This test will run for approxi-  
mately fifteen-seconds to measure the battery’s capability to provide an ac-  
ceptable amount of runtime. If the UPS fails a self test, one of the LEDs will  
remain illuminated indicating the type of problem. NOTE: The UPS will auto-  
matically perform a self test on start-up and every two weeks.  
DIP SWITCH SETTINGS  
The DIP Switch setting may be changed by the user to set the desired Inverter  
(On-Battery) output voltage. The DIP Switch must be set to the desired Inverter  
(On-Battery) output voltage and then the UPS must be turned off and restarted  
to reconfigure the microprocessor and save the changes. The Inverter (On-  
Battery) output voltage setting can be either 120VAC (default) or 127VAC. Chang-  
ing the Inverter (On-Battery) output voltage to 127VAC, will also change the  
Buck setpoint from 130VAC (default) to 137VAC.  
Inverter (On-Battery)output voltage  
Switch  
120V  
127V  
1
(Off)  
(On)  
2
(On)  
(Off)  
LOAD SHEDDING FUNCTION  
The output receptacles are electrically wired into two segments to support the  
"Load Shedding Function". The user can control the two segments individually  
or both at the same time. The Load Shedding Function is controllable by the  
Power Monitoring Software or the SNMP card.  
ALARMS  
ON BATTERY  
When the UPS is operating on the batteries, the On-Battery LED will illuminate  
and the audible alarm will sound once every ten-seconds. The alarm will stop  
once the UPS returns to the AC normal mode.  
LOW BATTERYWARNING  
The UPS will sound two beeps every five-seconds when the battery reserve  
runs low. This condition will continue until AC returns or the UPS shuts down  
from battery exhaustion.  
UPS FAULT  
When the UPS detects a hardware fault, the Fault LED will illuminate and the  
UPS will sound a constant alarm. The fault condition, in some instances, may  
be reset by turning the UPS off and then on.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERLOAD  
When the amount of load attached to the UPS exceeds its power rating, the  
Overload LED will illuminate and the UPS will sound a constant alarm. This  
alarm will remain on until the excess load is removed or the UPS’s self protec-  
tion circuit shuts the UPS down.  
WEAK/BAD BATTERY  
The UPS automatically tests the battery’s condition and will illuminate the Weak/  
Bad Battery LED and sound the alarm. This alarm will be repeated until the  
batteries pass a self test. If the battery is weak, bad or disconnected, the  
Weak/Bad Battery LED will illuminate and the alarm will beep three times every  
five-minutes until the battery is reconnected or replaced. It is recommended  
that the UPS be allowed to charge overnight before performing a battery test to  
confirm a Weak/Bad Battery condition.  
NOTE: If the UPS has a Weak/Bad BatteryAlarm after reconnecting or replac-  
ing the batteries, the user must initiate a self test to clear the Weak/Bad Bat-  
tery Alarm. To initiate a self test see section 4 "SELF TEST".  
COMMUNICATIONS PORTS (RS232 and USB)  
The RS232 communication port is a standard DB9 female with both RS232 and  
simulated contact closure capability. The Enterprise 1U Rackmount Series  
UPS will poll the port and activate the port for RS232 or contact closure in  
accordance with the type of cable it finds connected to the port. To change the  
port configuration requires the unit be turned off and restarted with the desired  
cable connected. The pinout for the port is depicted per the chart below.  
Pin 1: EPO Emergency Power Off (momentarily pull this pin low to completely  
turn off the UPS in any mode. The UPS will have to be turned off and then  
turned back on to restart the unit)  
Pin 2: /TXD  
Pin 3: /RXD and receive UPS shutdown command  
Pin 4: Simulated contact closure AC fail, NO  
Pin 5: Ground  
Pin 6: Simulated contact closure Low Battery Warning, NO  
Pin 7: Simulated contact closure AC fail, NC  
Pin 8: AC fail signal (high to low signal)  
Pin 9: Not Used  
USB PORT  
The USB port will support the MINUTEMAN Power Monitoring Software. See  
the software CD for the USB installation.  
POWER MONITORING SOFTWARE  
The UPS comes with a MINUTEMAN Power Monitoring Software CD. See the  
software CD for the installation of the MINUTEMAN Power Monitoring Software.  
OPTION SLOT  
The option slot on the rear panel of the UPS will only support the MINUTEMAN  
option cards.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
What To Do  
Possible Cause  
Symptom  
Press and release the On/Off/  
Test button to start UPS  
On/Off/Test button not  
pushed  
UPS will not turn on  
InputAC circuit breaker is Reset circuit breaker by  
UPS operates in  
battery mode only,  
even though there is  
normal AC present  
tripped  
pressing the plunger back in.  
If the AC circuit breaker trips  
after UPS starts up, reduce  
the load on the UPS  
Fault LED is  
illuminated  
UPS has detected an  
internal fault  
Call for service  
Have a Qualified Electrician  
correct the service wiring  
Disconnect the computer  
cable from the UPS and press  
the On button. If UPS works  
normally, the software has  
control of the UPS  
Incorrect service wiring  
Site Wiring Fault  
LED is illuminated  
The AC normal The UPS is being  
LED is illuminated, controlled via its  
but there is no out- communications port  
put  
Charge the batteries for 8  
hours and retest. If the runtime  
is still less than expected, the  
batteries may need to be  
replaced, even though the  
Weak/Bad Battery LED is not  
illuminated  
UPS does not  
The batteries may be weak  
provide expected or at the end of useful  
runtime  
service life  
Weak/bad batteries or bad  
connections at the battery  
Weak/Bad Battery  
LED is illuminated  
Check battery connections,  
charge the batteries for 8  
hours, replace the batteries  
Normal operation  
UPS occasionally  
emits a beep  
The UPS is performing its  
intended function  
The load has exceeded the Check the specifications (see  
Overload LED is  
illuminated and a  
constant alarm  
The Boost LED or  
Buck LED is blink-  
ing.  
UPS's capacity  
section 8). Remove part of the  
load  
The UPS is in either the The UPS is performing its  
Boost mode or the Buck intended function  
mode  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLACING THE BATTERY  
(QUALIFIED SERVICE PERSONNEL ONLY)  
The Enterprise 1U Rackmount Series UPS has an easy to replace hot-swappable  
batteries. Please read all of the WARNINGS and CAUTIONS before attempt-  
ing to service the batteries.  
NOTE: If there is a power interruption while replacing the hot-swappable  
batteries, with the UPS on, the load will not be backed up.  
This Uninterruptible Power Supply contains potentially hazardous  
voltages. Do not attempt to disassemble the UPS beyond the  
battery replacement procedure. This UPS contains no  
user serviceable parts. Repairs and Battery replacement must  
be performed by QUALIFIED SERVICE PERSONNEL ONLY.  
WARNING!  
Do not open or mutilate batteries. Released electrolyte is harmful  
to the skin and eyes and may be toxic.  
CAUTION:  
CAUTION:  
Do not dispose of batteries in a fire. The batteries may explode.  
The batteries in this UPS are recyclable. Dispose of the batteries  
properly. The batteries contain lead and pose a hazard to the  
environment and human health if not disposed of properly. Refer  
to local codes for proper disposal requirements or return the  
battery to MINUTEMAN.  
Although battery system voltages are only 24VDC the battery  
system can still present a risk of electrical shock. These batter-  
ies produce sufficient current to burn wire or tools very rapidly,  
producing molten metal. Observe these precautions when re-  
placing the batteries:  
CAUTION:  
1. Remove watches, rings, or other metal objects.  
2. Use hand tools with insulated handles.  
3. Wear protective eye gear (goggles), rubber gloves and boots.  
4. Do not lay tools or other metal parts on top of batteries.  
5. Disconnect the charging source prior to connecting or  
disconnecting the battery terminals.  
6. Determine if the battery is inadvertently grounded. If the bat-  
tery is, remove the source of the grounding. Contact with any  
part of a grounded battery can result in an electrical shock.  
The likelihood of such shock will be reduced, if such grounds  
are removed during installation and maintenance.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION: Replace batteries with the same number and type as originally  
installed in the UPS. These batteries have pressure operated vents.  
These UPSs contain sealed non-spillable lead acid batteries.  
E700RM1U  
4-6V9Ah  
E1500RM1U  
4-6V9Ah  
E1000RM1U  
4-6V9Ah  
Model #  
Battery  
Qty/Rating  
EPOWER  
Part #  
HR9-6  
HR9-6  
HR9-6  
Panasonic  
Part #  
UP-RW0645Ch1  
HRL634WF2FR  
VALANPW 45-6  
UP-RW0645Ch1  
HRL634WF2FR  
VALA NPW 45-6  
UP-RW0645Ch1  
HRL634WF2FR  
VALA NPW 45-6  
CSB  
Part #  
Yuasa  
Part #  
BATTERY REPLACEMENT PROCEDURE  
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING  
TO REPLACE THE BATTERIES  
Hot-swappable batteries mean that the batteries can be replaced without  
powering down the whole UPS system.  
NOTE: If there is a power interruption while replacing the hot-swappable  
batteries, with the UPS on, the load will not be backed up. To  
hot-swap the batteries start with step number 6.  
1. Turn off the equipment that is plugged into the output receptacles of the  
UPS.  
2. Press and release the On/Off/Test button on the front panel to turn the UPS  
OFF.  
3. Unplug the UPS's AC power cord from the AC wall outlet.  
4. Unplug the equipment from the output receptacles of the UPS.  
5. Unplug the computer interface cable from the rear panel of the UPS.  
6. Grasp the front panel and gently pull the front panel off the UPS. (FIG. 2)  
7. Lay the front panel on top of the UPS.  
FIG. 1  
FIG. 2  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Remove the four retaining screws for the battery retaining bracket. (FIG. 3)  
9. Remove the battery retaining bracket. (FIG. 3)  
10. Grasp the battery tray and gently pull the battery tray out far enough to get  
to the battery connectors (red and black). (FIG. 4)  
11. Disconnect the battery connectors (red and black). (FIG. 5)  
12. Gently remove the battery tray from the UPS and set on the floor.  
NOTE: Use Caution, the battery tray is heavy.  
13. Remove the battery jumper wires.  
14. Remove the old batteries from the battery tray.  
15. Install the new batteries into the battery tray in the same position as the  
original batteries.  
16. Verify proper polarity. Re-install the battery jumper wires on the new  
batteries.  
17. Slide the battery tray into the UPS.  
18. Verify proper polarity. Re-connect the battery connectors (red and black).  
NOTE: Some sparking might occur, this is normal.  
19. Re-install the battery retaining bracket.  
20. Re-install the four retaining screws for the battery retaining bracket.  
21. Re-install the front panel on the UPS.  
22. Properly dispose of the old batteries at an appropriate recycling facility or  
return them to the supplier in the packing material for the new batteries.  
23. The UPS is now ready for the normal start-up operation.  
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries,  
the user must initiate a self test to clear the Weak/Bad Battery Alarm. To  
initiate a self test see section 4 "SELF TEST".  
FIG. 4  
FIG. 3  
FIG. 5  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IF THE UPS REQUIRES SERVICE  
1.Use the TROUBLESHOOTING section to eliminate obvious causes.  
2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the  
most common problem.  
3.Call your dealer for assistance. If you cannot reach your dealer, or if they  
cannot resolve the problem call or fax MINUTEMAN Technical Support at the  
following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or  
have the following information available BEFORE calling the Technical  
Support Department.  
A. Your name and address.  
B. Where and when the unit was purchased.  
C. All of the model information about your UPS.  
D. Any information on the failure, including LEDs that may be illuminated.  
E. A description of the protected equipment, including model numbers if  
possible.  
F. A technician will ask you for the above information and, if possible, help  
solve your problem over the phone. In the event that the unit requires  
factory service, the technician will issue you a Return Material  
Authorization Number (RMA #).  
G. If the UPS is under warranty, the repairs will be done at no charge. If not,  
there will be a charge for repair.  
4. Pack the UPS in its original packaging. If the original packaging is no longer  
available, ask the Technical Support Technician about obtaining a new set. It  
is important to pack the UPS properly in order to avoid damage in transit.  
Never use Styrofoam beads for a packing material.  
A. Include a letter with your name, address, day time phone number, RMA  
number, a copy of your original sales receipt, and a brief description of the  
problem.  
5. Mark the RMA # on the outside of all packages. The factory cannot accept  
any package without the RMA # marked on the outside.  
6. Return the UPS by insured, prepaid carrier to:  
Para Systems Inc.  
MINUTEMAN UPS  
1455 LeMay Drive  
Carrollton, TX 75007  
ATTN: RMA# _______  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM SPECIFICATIONS  
E700RM1U  
Model Number  
Topology  
E1000RM1U  
E1500RM1U  
Line-Interactive, Sine Wave  
1000VA  
700W  
700VA  
490W  
1500VA  
900W  
Maximum Power Capacity  
INPUT  
Number of Phase  
Nominal Voltage  
Single (12W +G)  
120VAC  
Acceptable Input voltage  
Voltage Range  
0 - 165VAC  
85 - 150VAC  
Frequency Limits  
50 or 60 Hz, +/-6Hz, autosensing  
85V resets to Utility Power at 90V or higher  
150V resets to Utility Power at 145V or lower  
Resettable Circuit Breaker  
Low Voltage Transfer Point  
High Voltage Transfer Point  
Input Protection  
OUTPUT NON-BATTERYOPERATION  
120VAC: 105 - 132VAC (127VAC: 105 - 137VAC)  
120VAC: -12.5% - +10% (127VAC: -17.3% - +7.8%)  
60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz  
>93% (Full Load)  
Voltage Range  
Voltage Regulation  
Frequency Range  
Efficiency (Line Mode)  
OUTPUT BATTERYOPERATION  
Waveform Type  
Nominal Voltage  
Voltage Regulation  
Frequency  
Sine Wave  
Default 120VAC User selectable 120/127VAC  
Nominal +/-2% (until Low Battery Warning)  
50/60Hz, +/-0.1Hz (unless synchronized to utility)  
<5% (Linear Load)  
<8% (Linear Load)  
Voltage T.H.D.  
Dynamic Response  
Transfer Time  
Slew Rate  
+/-5% @ 100% Load change in 100mS  
2-6 mS Typical  
<1Hz/Second  
110% for 20-Seconds  
Overload Capacity  
Protection  
125% for 10-Seconds  
150% Shutdown Immediately  
Over-Current, Short-Circuit Protected and Latching Shutdown  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BATTERY SYSTEM  
Sealed, Non-Spillable, Maintenance Free, Value Regulated LeadAcid  
Battery Type  
Typical Recharge Time  
Typical Battery Life  
System Voltage  
8 hours from total discharge  
3-5 years, depending on discharge cycles and ambient temp  
24VDC  
4-6V9Ah  
9-Minutes  
4-Minutes  
24VDC  
4-6V9Ah  
7-Minutes  
3-Minutes  
24VDC  
4-6V9Ah  
13-Minutes  
6-Minutes  
Battery Quantity/Rating  
Runtime: Half Load  
Runtime: Full Load  
SURGE PROTECTIONAND FILTERING  
800 J  
Surge energy rating  
Surge current capability  
Surge response time  
6500 Amps total  
0 ns (instantaneous) normal mode; <5 ns common mode  
Surge voltage let-through (as  
a percentage of an applied  
ANSI C62.41 Cat. A +/-6 kV)  
<5%  
10/100 Base-T surge protec-  
tion let-through (as a percent-  
age of an applied +/-6 kV 1.2/  
50 us, 500 a 8/20 uS test)  
<5%  
<1%  
Telephone line surge protec-  
tion let-through (as a percent-  
age of an applied +/-6 kV 1.2/  
50 us, 500a 8/20 uS test)  
Noise filter  
Normal and common mode EMI/RFI suppression  
<45 dBA  
Audible noise at 1 m (3 ft.)  
ENVIRONMENTAL  
0 to 40°C (+32 to 104°F)  
-15 to +45°C (+5 to +113°F)  
95% Non-Condensing  
Operating Temperature (max)  
Storage Temperature  
Operating/Storage Humidity  
Operating Elevation  
Storage Elevation  
0 to 3,000m (0 to 10,000 ft)  
0 to 15,000m (0 to +50,000 ft)  
PHYSICAL  
Size - Net  
H X D X W  
1.75 x 24 x 17"  
44.5 x 610 x 432 mm  
51.2 lb  
23.2 Kg  
51.2 lb  
23.2 Kg  
42.3 lb  
19.2 Kg  
Weight - Net  
Size - Shipping  
H X D X W  
5.2 x 27.6 x 20.9"  
132 x 701 x 531 mm  
52 lb  
23.6 Kg  
61 lb  
27.7 Kg  
61 lb  
27.7 Kg  
Weight - Shipping  
REGULATORYCOMPLIANCE  
Safety and approvals  
EMC Verification  
UL1778, cUL (CSA 22.2 no. 107.1)  
FCC Class A, CE certified  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(These items may require optional software or hardware)  
Description  
User Choices  
Factory  
Default  
Function  
Enterprise 1U  
RM Series  
Use this function to uniquely  
identify the UPS in your network  
configuration  
UPS ID  
Up to 64  
characters  
to define  
the UPS  
Date of  
Date of battery  
Battery  
install  
date  
Enter the current date when  
replacing batteries  
manufacture replacement -  
month/day/year  
XX/XX/XXXX  
Battery 1826  
life in  
days  
Up to 5  
characters  
At first battery replacement, reset  
to reflect actual number of days  
experience in your environment or  
leave factory default  
Enable  
or  
Disable  
When enabled, the UPS will  
automatically restart from a low  
battery shutdown when normal AC  
returns  
Enable/ Enabled  
Disable  
auto  
restart  
Set  
Enabled  
Enabled, at  
low battery,  
disabled  
Enabled - the UPS will emit a  
short beep when in the battery  
mode. At Low Battery the UPS  
will emit two beeps from low  
battery warning until shutdown.  
Disabled - Use only when software  
is controlling the UPS or to  
silence the alarm  
audible  
alarm  
state  
Entire UPS - Turns off the entire  
UPS.  
Shut-  
down  
Type  
Entire UPS or  
UPS output  
Entire UPS  
120VAC  
UPS Output - Turns off the UPS's  
output receptacles only.  
120, 127VAC  
Set  
Changes output voltage for bat-  
tery mode operation  
inverter  
output  
voltage  
Enabled - the UPS will be  
completely powered off and re-  
main off until the UPS is reset  
Enable/ Disabled  
Disable  
EPO  
Enable  
or  
Disable  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Para Systems Inc. (Para Systems) warrants this equipment, when properly  
applied and operated within specified conditions, against faulty materials or  
workmanship for a period of three years from the date of purchase. For equip-  
ment sites within the United States and Canada, this warranty covers repair or  
replacement of defective equipment at the discretion of Para Systems. Repair  
will be from the nearest authorized service center. Replacement parts and  
warranty labor will be borne by Para Systems. For equipment located outside  
of the United States and Canada, Para Systems only covers faulty parts. Para  
Systems products repaired or replaced pursuant to this warranty shall be war-  
ranted for the unexpired portion of the warranty applying to the original product.  
This warranty applies only to the original purchaser who must have properly  
registered the product within 10 days of purchase.  
The warranty shall be void if (a) the equipment is damaged by the customer, is  
improperly used, is subjected to an adverse operating environment, or is oper-  
ated outside the limits of its electrical specifications; (b) the equipment is re-  
paired or modified by anyone other than Para Systems or Para Systems-ap-  
proved personnel; or (c) has been used in a manner contrary to the product’s  
User's Manual or other written instructions.  
Any technical advice furnished before or after delivery in regard to use or appli-  
cation of Para Systems’s equipment is furnished without charge and on the  
basis that it represents Para Systems’s best judgment under the circumstances,  
but it is used at the recipient’s sole risk.  
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRAN-  
TIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT-  
ABILITYAND FITNESS FORAPARTICULAR PURPOSE. Some states do not  
permit limitation of implied warranties; therefore, the aforesaid limitation(s) may  
not apply to the purchaser.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED PRODUCT WARRANTY  
(Continued)  
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE  
LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUEN-  
TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF  
ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Para Sys-  
tems is not liable for any costs, such as lost profits or revenue, loss of equip-  
ment, loss of use of equipment, loss of software, loss of data, cost of substi-  
tutes, claims by third parties, or otherwise. The sole and exclusive remedy for  
breach of any warranty, expressed or implied, concerning Para Systems’s prod-  
ucts and the only obligation of Para Systems hereunder, shall be the repair or  
replacement of defective equipment, components, or parts; or, at Para Systems’s  
option, refund of the purchase price or substitution with an equivalent replace-  
ment product. This warranty gives you specific legal rights and you may also  
have other rights which vary from state to state.  
Longer term and F.O.B. job site warranties are available at extra cost. Contact  
Para Systems (1-972-446-7363) for details.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DECLARATION OF CONFORMITY  
Application of Council Directive(s): 89/336/EEC, 73/23/EEC  
EN55022, EN55024  
EN61000-6-1, EN61000-6-3  
EN61000-4-5  
Standard(s) to which Conformity is declared:  
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS)  
Manufacturer’sAddress: 1455 LeMay Drive  
Carrollton, Texas 75007 USA  
Type of Equipment: Uninterruptible Power Supplies (UPS)  
Model No: E700RM1U (Y), E1000RM1U (Y), E1500RM1U (Y)  
Year of Manufacture: BeginningAugust 1, 2005  
I, the undersigned, hereby declare that the equipment specified above  
conforms to the above Directive(s).  
Robert Calhoun  
Robert Calhoun  
(Name)  
(Signature)  
Manager Engineering  
(Position)  
Date: August 1, 2005  
Place: Carrollton, Texas, USA  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes:  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Para Systems, Inc.  
1455 Lemay Dr.  
Carrollton, TX 75007  
Phone: 1-972-446-7363  
Fax: 1-972-446-9011  
Internet: minutemanups.com  
UPS Sizing: sizemyups.com  
PN - 34000256 Rev.1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Quantum Boiler GAS FIRED BOILERS User Guide
Radio Shack Thermometer Thermometer User Guide
RCA CRT Television F36691 User Guide
Renesas Computer Hardware M16C 29 User Guide
RIDGID Drill R820011 User Guide
Roberts Radio Clock Radio CR9935 User Guide
RocketFish Speaker System RF RBWS02 01 User Guide
Rosewill Power Supply HIVE 550 User Guide
Royal Consumer Information Products Outdoor Fireplace U19023 User Guide
Samsung Security Camera SCC B2033P User Guide