Premier Smoke Alarm Fire Alarm Control Panel User Manual

USER MANUAL ,  
MAINTENANCE GUIDE &  
LOG BOOK  
.
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
1. FIRE ALARM CONTROL PANEL SAFETY ISSUES  
There is no need to open this fire alarm during normal operation. Any work carried out on this system must be  
performed by a competent person who is familiar with this type of system.  
This equipment will operate safely provided it has been installed correctly in compliance with the Installation  
Manual.  
It is recommended that the system is serviced frequently. It is customary to arrange a regular maintenance  
contract with a competent organisation. (Ask the installation company for recommendations). The system  
needs a thorough maintenance check annually at the very minimum.  
If any part of this Fire Alarm Control Panel becomes damaged, contact the company responsible for system  
maintenance to arrange repair / replacement.  
European Union Directives Conformance Statement  
This product has been manufactured in conformance with the requirements of all  
applicable EU Council Directives. The Declaration of Conformance for this  
product is located at the following Address: GLT Exports Ltd, 72-78 Morfa Road,  
Hafod, Swansea, SA1 2EN, United Kingdom  
2. THE PURPOSE OF A FIRE ALARM SYSTEM  
A Fire Alarm System is used to provide an early warning of a fire, so that the property can be evacuated and  
the fire extinguished if it can be safely tackled, or the local fire brigade called, according to the company  
evacuation procedure.  
Alarms can come from Smoke or Heat Detectors, or manually be a person operating a Manual Call Point.  
Split the system into Zones, each covering a different area of a building. This will indicate which area of the  
system is giving the alarm (or fault).  
During an alarm, the panel will start its sounders, and indicate which zone has the fire. It will also activate its  
auxiliary relay.  
Fault Monitoring  
All circuits must be checked for line integrity. If a part of the system has a problem which may affect its  
operation, a fault warning must be given by the fire alarm panel (LED & buzzer indication). The fault relay will  
also activate.  
Disablements  
An engineer may be required to work on part of a system, while the system is still active (eg extending a  
detection zone). During such circumstances, it would be advisable to disable that zone, so that it will not give  
false alarms. Similarly you may wish to disable a zone that has a fault that has not been fixed, or a zone  
covering an area with a temporary unusual environment, such as an area which is dusty because of  
construction work etc.  
Delays  
In public places, it may be desirable to delay the activation of an alarm until the responsible person has verified  
the cause of the alarm. (This would avoid a panic evacuation caused by a smoky room, or a maliciously  
activated call point.) On verification of the alarm, the sounders can be started by pressing the override button,  
or the panel can be reset in the case of a false alarm. If a delay has been set, it must be recorded on the  
system configuration chart at the back of this manual.  
Power Supply Equipment- General Description.  
The NPSX FACP has an integral linear power supply capable of supplying 1.2 amps in total. It contains a current  
limited output for charging sealed lead acid batteries (7 Ah maximum). The PSE is monitored for main supply  
failure, the battery not taking a charge and low battery voltage. If the battery voltage drops below approximately  
20VDC (a fault condition), the battery charging current will be turned off , thus stopping charging. This PSE is  
only capable of supplying power to the CIE, and is not designed for any other use.  
Approved Document No: GLT.MAN-102  
PAGE 3  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM  
SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE  
According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings  
(BS5839: Pt 1: 2002), the owner or person having control of the premises should appoint a responsible person  
to oversee the effective operation of the Fire Alarm System (Clause 47.1).  
Below is a summary of the main functions the “Responsible Person” is expected to carry out. This summary is  
not intended to replace Section seven (User responsibilities) of BS5839: Pt 1: 2002 (available from BSI, or your  
local library). It is meant to give a brief outline of user responsibilities for the safe upkeep of the Fire Alarm  
System. The number in brackets shows the relevant BS5839: Pt 1: 2002 clauses.  
The responsible person must:-  
1. Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a)  
2. Check the system at least once every 24 hours to ensure there are no faults present (47.2.b)  
3. Ensure there are arrangements for testing and maintaining the system (47.2.c)  
4. Ensure the log book is up to date, and available for inspection (47.2.d)  
5. Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence  
alarms, silence faults and system reset (47.2.e)  
6. Take appropriate action to limit the rate of false alarms (47.2.f)  
7. Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g)  
8. Liase with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere  
with the functioning and reliability of the fire alarm system (47.2.h).  
9. Ensure any changes to the system are recorded with updated drawings, operating instructions etc (47.2.i)  
10. Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2)  
With the Premier SX Range of Fire Alarm Panels, we recommend the following tests are carried out: -  
Daily Inspection  
Check that the green Power LED is lit.  
If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated  
site maintenance engineer.  
Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests)  
Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate.  
Do not test the same device each week. Test a different zone each week using a different call point or  
detector so that eventually, all the devices will be tested.  
Reset the System by pressing 1,2,3 (Stop sounders, Silence fault tone, Reset).  
Turn key to controls enabled. Press the LED Test button. Check that all LEDs light, and the buzzer sounds  
Check that no call points or fire detectors are obstructed in any way. (eg New furniture or decorations)  
Quarterly Test (to be carried out by authorised service personnel only)  
Check that any servicing or repairs required by all previous logbook entries has been undertaken.  
Visual inspection of the batteries and connections. Check the alarm sounders work on battery only.  
Activate a device from each zone to test the fire alarm. (As per weekly test).  
Annual Test (to be carried out by authorised service personnel only)  
Check every detector, call point, sounder and all auxiliary equipment for correct operation.  
Check Transformer output Voltage (32 VAC), Charger Voltage (28.4V off load, adjusted with VR1) &  
Battery Voltage (25-27V)  
Every Five Years (to be carried out by authorised service personnel only)  
Carry out a complete wiring check in accordance with the testing and inspection requirements of the  
relevant National wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be  
replaced because SLA batteries have a working life of 5 years.  
Approved Document No: GLT.MAN-102  
PAGE 4  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
4. PANEL INDICATIONS & CONTROLS  
FIRE / ZONES  
OFF  
8
8
1
2
3
4
5
6
6
7
7
CONTROLS  
ENABLED  
POWER  
SUPPLY FLT  
FLT  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
STOP-START  
SILENCE  
SCROLL /  
GEN-ZONE TEST  
ENGINEER  
3
1 2  
4
/ LED TEST  
FLT TONE  
GEN-DISABLEMENT  
DELAY  
OVERRIDE  
Two levels of control are available to the User(s) of this Fire Alarm Panel.  
4.1 GENERAL CONTROLS  
When the Panel is in its Normal state, the indicator lights on the front of the enclosure give a  
comprehensive overview of the System’s current status. Any Fire and Fault conditions are clearly  
displayed, and any disablements highlighted. For detailed descriptions of what each indicator means,  
please refer to the table on the opposite page.  
The only functions that can be performed by the User when the Panel is in its Normal state are:  
Overriding any Delays, which may have been programmed into the Panel by pressing the  
Sounder Override button.  
Putting the Panel into the Accessed state – see below.  
4.2 ACCESSED CONTROL (AVAILABLE TO AUTHORISED USERS ONLY)  
To avoid unauthorised changes to critical parts of the Fire Alarm System, controls such as silencing  
the Sounders, resetting an Alarm condition and implementing Disablements are only accessible via a  
secure method of entry which puts the panel into the Accessed state.  
To put the Panel into the Accessed State: Turn the key to the control enable position (please note  
the key should not be removed when in this position). To leave the Accessed state, turn the key back  
to the off position.  
Information on how to used the accessed control can be found on Pages 8 to 11 of this User Manual.  
Approved Document No: GLT.MAN-102  
PAGE 5  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING  
Use the table below to determine the condition of the panel.  
LEDs LIT  
LED CONDITION  
PANEL STATUS  
POWER  
CONSTANTGREEN  
The panel is supplied with power, and has no faults / fires (System Normal)  
GEN FLT  
ONLY  
CONSTANTYELLOW  
Problem with keyswitch connections  
GEN FLT &  
SUPPLY FLT  
CONSTANT YELLOW  
FLASHING YELLOW  
There is a problem with either the mains supply or the battery backup  
There is a wiring problem. One of the cables is touching the earth screen.  
There is an open circuit fault in the wiring of the zone indicated.  
There is a short circuit fault in the wiring of the zone indicated.  
GEN FLT &  
EARTH FLT  
CONSTANT YELLOW  
FLASHING YELLOW  
GEN FLT &  
ZONAL FLT  
CONSTANT YELLOW  
FLASHING YELLOW  
GEN FLT &  
ZONAL FLT  
GEN S/C  
CONSTANT YELLOW  
FLASHING YELLOW  
FLASHING YELLOW  
GEN FLT &  
SND FLT  
CONSTANT YELLOW  
FLASHING YELLOW  
There is an open circuit fault in the wiring of one or both of the sounder  
circuits  
GEN FLT &  
SND FLT  
GEN S/C  
CONSTANT YELLOW  
FLASHING YELLOW  
FLASHING YELLOW  
There is a short circuit fault in the wiring of one or both of the sounder  
circuits  
GEN FLT &  
SYSTEM FLT CONSTANT YELLOW  
CONSTANT YELLOW  
A processor fault has occurred. To reset, turn keyswitch on then back off. If  
problem persists, consult your dealer.  
GEN FIRE  
ONLY  
CONSTANTRED  
A manual evacuation has occurred.  
The sounders will be active.  
GEN FIRE &  
ZONE FIRE  
CONSTANT RED  
CONSTANT RED  
A fire has occurred in the zone indicated.  
The sounders will be active.  
GEN FIRE &  
CONSTANT RED  
A fire has occurred in the zone indicated.  
ZONE FIRE & CONSTANT RED  
GEN DISABLE CONSTANT YELLOW  
The sounders have a delay set, and will become active after the  
programmed delay. To override the display, press delay override.  
& DEL  
CONSTANT YELLOW  
GEN DISABLE FLASHING YELLOW  
(FAST – 4 HZ)  
The panel is ready for selecting disable or test mode  
The panel is in SELECT DISABLEMENT MODE  
GEN DISABLE FLASHING YELLOW  
(SLOW – 0.5 HZ)  
GEN DISABLE FLASHING YELLOW  
The user is scrolling through zones to select which one to disable/or user  
has just enabled the zone.  
ZONE DISABLE  
(SLOW – 0.5 HZ)  
GEN DISABLE CONSTANT YELLOW  
ZONE DISABLE CONSTANT YELLOW  
The indicated zone is disabled.  
GEN DISABLE CONSTANT YELLOW  
The Sounders are delayed by the amount set on the rotary switch.  
The indicated zone is in Test Mode.  
DEL  
CONSTANT YELLOW  
GEN TEST  
ZONE DISABLE  
FLASHING YELLOW  
FLASHING YELLOW  
(VERYSLOW 0.25HZ)  
4.4 CHECKING THE PANELS INDICATION LEDS  
Turn the key switch to “Controls Enabled” position then press the LED test button (Button 4). All the LEDs on the  
front panel will light, and the panel’s internal buzzer will also sound.  
Approved Document No: GLT.MAN-102  
PAGE 6  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
5. THE FIRE CONDITION  
5.1 HOW THE PREMIER SX INDICATES AN ALARM  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
SYSTEM FLT  
SILENCE  
STOP-START  
RESET  
SCROLL /  
GEN-ZONE TEST  
ENGINEER  
3
1 2  
4
/ LED TEST  
FLT TONE  
GEN-DISABLEMENT  
DELAY  
OVERRIDE  
When the Premier SX Fire Alarm Panel is set into alarm by a Detector or Manual Call Point located in a zone that  
is not already in alarm it will: -  
Light the General Fire LED and appropriate Zone Fire LED(s) on the front of its enclosure  
Sound Internal buzzer  
Start the Alarm Sounder and Auxiliary output, (provided there is no Delay set on the sounders).  
The building evacuation procedure should now be followed.  
IMPORTANT NOTE: If a zone has been disabled, it can not be triggered into Alarm. This should be  
remembered when disabling part of the system. (see Disabling zones or sounders later in this manual).  
5.2 TO TURN OFF THE ALARM SOUNDERS  
The Alarm Sounders may be silenced by turning the control key to “Control Enable” position and momentarily  
pressing the Start/Stop button.  
The Alarm Sounders will cease to sound but the light(s) for the Zone(s) in Alarm and the red General Fire light will  
stay lit. The Auxiliary Fire relay will remain active. (The Panels internal buzzer can also be silenced by pressing  
the Silence int flt button (button 2)).  
5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE  
If another detection Zone is activated after the Alarm Sounders have been silenced, the panel will: -  
Restart the sounders  
Light the Zone Fire LED(s) for any new Zone(s) in alarm  
Keep the light(s) for the previous Zone(s) in fire, and General Fire lit.  
5.4 TURNING ON THE ALARM SOUNDERS FROM THE FACP (I.E. TO EVACUATE THE BUILDING).  
With the control key in “Controls Enabled” position, momentarily pressing the Start/Stop will cause the Alarm  
sounders to sound.  
Pressing the Start/Stop button again will Silence the Alarm Sounders.  
Note: If the Alarm Sounders have been disabled, pressing the Stop/Start button will have no effect.  
5.5 RESETTING THE PANEL  
Check the cause of the alarm activation. If the cause of the alarm was an activated call point, reset it (if  
resettable type), or fit a new glass element (if glass type). If the cause of the alarm was by detector activation  
(eg cooking smoke), the smoke will have to be cleared from the room before the panel can be reset. Reset  
the panel by pressing the reset button (3) after the sounders and panel buzzer have been silenced.  
If the call point is still active, or the detector is still smoky, this will cause another alarm straight after the  
panel is reset, so will set off alarm bells again.  
Approved Document No: GLT.MAN-102  
PAGE 7  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
6. THE FAULT CONDITION  
6.1 DIFFERENT TYPES OF FAULT  
The fire alarm monitors itself, and any equipment connected to it, for any faults that can occur. If a fault occurs, the Panel  
responds by activating its Internal buzzer and lighting the General Fault light and any other Fault light(s) relevant to the  
particular fault. The Panel’s Fault relay will also activate. Typical faults are described below: -  
General Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
SYSTEM FLT  
FLT  
The General Fault LED is a common indicator that lights  
when there is a Fault on any part of the Fire Alarm Systems.  
It is usually lit in tandem with at least one other fault light  
which conveys more precise information on the type of  
Fault detected.  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
STOP-START  
SILENCE  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
If this light is lit by itself, it indicates a keyswitch fault.  
GEN-DISABLEMENT DELAY  
OVERRIDE  
Zone Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
The relevant Zone Fault light flashes when there is a  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
wiring problem on a Zone or detector has been removed from  
its base. It should be noted that any alarms raised on the  
fault zone(s) may not be recognised by the Fire Alarm Panel  
until the Fault Conditions have been cleared. It can take up to  
60 seconds from repairing a fault for the display to clear.  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
SILENCE  
STOP-START  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
Short Circuit Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
If the Fault is a short circuit fault, then the S/C LED will be lit.  
This GEN S/C LED will be lit for S/C faults on the zone  
and sounder circuits. It can take up to 60 seconds from repairing  
a fault for the display to clear.  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
SILENCE  
STOP-START  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
Power Supply Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
The Power supply Fault light flashes when the Mains supply  
has failed or the standby batteries or its charger is faulty. If  
the mains supply fails, the panel will only operate for the  
standby period dictated by the size of the batteries fitted. If  
the batteries or charger fails at the same time as the Mains,  
the Panel will be inoperative.  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
SILENCE  
STOP-START  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
System Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
The System Fault LED lights when the Panel’s micro-processor  
has Reset, typically after excessive electrical interference, or if  
the contents of its memory have been corrupted. This fault can  
only be cleared by turning the key switch from off position to  
control enable position and then back to the off position again. If  
the fault re-occurs within two minutes, this is indicative of a  
corrupt memory and expert advice should be sought.  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
SILENCE  
STOP-START  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
Approved Document No: GLT.MAN-102  
Issue: 1.3 Authorised: GH Date: 9/6/2004  
PAGE 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
Earth Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
The Earth Fault light flashes when the panel detects an earth  
fault (short circuit to earth) on the wiring to any part of the  
control panel.  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
STOP-START  
SILENCE  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
Sounder Fault  
FIRE / ZONES  
8
8
1
2
3
4
5
6
6
7
7
POWER  
SUPPLY FLT  
FLT  
The Sounder status light flashes when there is a wiring fault  
on the Sounder Circuits. Depending on where the fault  
has occurred, one or all of the Alarm Sounders may no longer  
be operative.  
If the fault is a short circuit fault, then the S/C LED will also  
be lit.  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
GEN-S/C  
RESET  
SYSTEM FLT  
SILENCE  
STOP-START  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
6.2 WHAT TO DO IF A FAULT CONDITION OCCURS  
If a fault occurs, the responsible person should:  
Turn keyswitch to Controls enabled and press silence flt tone button (button 2) to silence the fault buzzer.  
Write down the fault (s) in the Log Book at the back of this Manual. Take appropriate action to correct the fault  
(Usually by contacting the service engineer)  
On the Premier SX panel, the fault indications (except system fault) are non latching. That is, when the fault has been  
cleared, the fault indication will turn off. When all faults have been cleared, the panel will return to its quiescent (normal)  
condition.  
When a fault has been rectified the indicator light for that Fault is automatically turned off. If all Faults are cleared, the  
General Fault light will go out and the Panel’s Internal Sounder will be silent (if not already muted).  
Approved Document No: GLT.MAN-102  
PAGE 9  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
7. DISABLEMENTS  
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM.  
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For  
example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is  
possible for the user to disable that zone during the risk period and then enable it again afterwards. During a disablement  
of a zone(s), no fire or fault signal will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled,  
that is zones already in fire cannot be disabled.  
External sounders can also be disabled as could be required in certain conditions.  
7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS.  
1.  
2.  
Turn control key to “Controls Enable” position;  
Press “Engineer” switch momentarily, this will cause General Disablement LED to flash (fast). This means the  
panel is in disable/enable mode;  
3.  
4.  
5.  
Press scroll (No. 4) switch once and this will cause the General Disablement LED to flash (slow);  
Press scroll (No. 4) switch once again and this will cause Zone 1 Disablement LED to light steady;  
Pressing scroll (No. 4) switch will cause the zone disablement LED to toggle to zone 2 and so on;  
FIRE / ZONES  
8
1
2
3
4
5
6
7
POWER  
SUPPLY FLT  
FLT  
GEN-FIRE  
GEN-FAULT  
DEL  
ZONAL FAULT / DISABLEMENT / TEST  
1
2
3
4
5
6
7
8
GEN-S/C  
RESET  
SYSTEM FLT  
STOP-START  
SILENCE  
SCROLL  
/
GEN-ZONE TEST  
ENGINEER  
3
1
2
4
/
LED TEST  
FLT TONE  
GEN-DISABLEMENT DELAY  
OVERRIDE  
6.  
7.  
Select zone to be disabled. For example, if Zone 3 is selected and with Zone 3 disablement LED lit (steady) and  
General Disablement LED flashing slow, pressing “Engineer” will cause General Disablement LED light to change  
to steady. This means that zone 3 is now disabled;  
Switch controls key to off position, then both the disabled Zone Disablement LED and the General Disablement  
LED will remain lit (steady.  
7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS.  
1.  
Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED  
with stay lit (steady);  
2.  
3.  
4.  
5.  
Press “Engineer” switch once and this will cause the General Disablement LED to flash (fast);  
Press scroll (No. 4) switch until the light is steady at the disabled zone;  
Press “Engineer” and this will cause the General Disablement LED to flash (slow);  
Turn control Key to “Off” position and this will turn off the General Disablement and Zone Disablement LEDs.  
NOTES:  
The option of disabling or enabling zones 2, 3, 4, 5, 6, 7 and 8 is only available if these zones are present on the  
panel  
Approved Document No: GLT.MAN-102  
PAGE 10  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
8. USING SOUNDER DELAYS  
8.1 WHAT IS A SOUNDER DELAY  
In certain circumstances it may be desirable to have a delay between the panel detecting a fire, and starting its external  
sounders, to allow the responsible person to check the cause of the alarm, to stop building evacuation by an obvious false  
alarm. If the cause of the Alarm is found to be a true fire hazard, the Delay can be overridden and the Alarm Sounders  
activated immediately. Alternatively, in the case of a false alarm, the Panel can be reset.  
8.2 SOUNDER DELAY SETTING  
On the Premier SX panel, the sounder delay is global. That is, all zones will be delayed by the same amount. The delay  
can be set between 1 minute and 9 minutes, by turning the rotary dial to the relevant position, or the delay can be left off  
(sounders activate immediately), by leaving the dial at the 0 position.  
8.3 HOW THE PANEL INDICATES SOUNDER DELAY  
If a Delay has been programmed into the Panel, the General Disablement & DEL(AY) LEDs will be lit. When a zone  
processes an alarm signal, the panel will indicate fire in the usual way, but the sounders will not be active until the delay  
period has expired. To override this delay, press Delay Override Switch, which will cause the external sounders to  
energise. If there is no delay programmed, the Delay Override Switch has no function.  
8.4 A FIRE ALARM CONDITION ON A DELAYED PANEL  
When an alarm occurs on a Delayed Panel, the panel will: -  
Light its General Fire and appropriate Fire Zone light(s)  
Sound its Internal buzzer  
Start the Delay countdown sequence  
Wait until the end of the delay, then start the sounders.  
8.5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE ALARM  
If on investigation the cause of the Alarm is found to be a true fire hazard, pressing the Delay Override, will active the  
Alarm Sounders and Outputs with immediate effect.  
8.6 RESET THE SYSTEM IN THE EVENT OF A FALSE ALARM  
If, on investigation, the cause of the Alarm is found to be false, turn the Key switch to the “Controls Enabled” position and  
press reset button.  
8.7 TO TURN OFF THE SOUNDER DELAY  
There are two ways of turning off the sounder delay:-  
1
2
Return the rotary switch to the 0 position.  
Turn key to controls enabled position. Press engineer button (to select disablement mode). Press delay override  
(the DEL LED will now go off to show that the delay is no longer active). Pressing Delay Override again will  
toggle the delay back on.  
Approved Document No: GLT.MAN-102  
PAGE 11  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
9. SYSTEM DESCRIPTION  
FIRE ALARM SYSTEM SUMMARY:  
FIRE ZONE INFORMATION  
ZONE  
ZONE DESCRIPTION  
QTY  
QTY  
QTY  
NUMBER A brief description of all the rooms and areas contained in each zone  
SNDR MCP  
HEADS  
1
2
3
4
5
6
7
8
Sounder  
Circuit  
SOUNDER CIRCUIT DESCRIPTION  
A brief description of all the rooms and areas contained in each circuit  
QTY  
SNDR  
QTY  
BELLS  
Circuit 1  
Circuit 2  
Any Other Information about The Sounder Circuits  
OUTPUT ROUTING INFORMATION  
TYPE OF OUTPUT  
CONNECTED  
WHAT HAPPENS WHEN ACTIVATED  
Auxiliary Output  
Yes/No  
Fault Output  
Yes/No  
ADDITIONAL INFORMATION  
Any additional information the User needs to know about should be inserted into this box including details  
of the routing of any additional outputs, details of inputs utilised, etc.  
THE INFORMATION ABOVE WAS COMPLETED BY  
NAME:  
_______________________________________________________________________________________  
_______________________________________________________________________________________  
_______________________________________________________________________________________  
_______________________________________________________________________________________  
COMPANY:  
POSITION:  
DATE:  
Approved Document No: GLT.MAN-102  
PAGE 12  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
10. FIRE ALARM LOG BOOK  
It is recommended that this LOG BOOK section of the Manual be maintained by the responsible person(s) on site, who  
should ensure every event is properly recorded (including fire alarm conditions, failures, tests, temporary disconnections,  
disablements, enablements, dates of installing engineers’ visits together with a note of any outstanding work or panel  
conditions). This LOG BOOK must be available for inspection at all times.  
You can photocopy this log book to provide extra pages for when this book is full.  
BS5839 part 1 recommends that fire alarm events should be subdivided & recorded on separate sheets in the log book.  
The event categories are:  
Maintenance work  
False alarms – Where the sounders have activated with no signs of a fire.  
Any other events- This would be genuine alarms or faults.  
Company:  
Site Address:  
System designed by:  
System installed by:  
System commissioned by:  
System maintained by:  
Contract No:  
Contract valid until:  
For Service (Normal hours Mon-Fri) Tel:  
For Service (Other times) Tel:  
Responsible Person(s) on Site:  
Approved Document No: GLT.MAN-102  
PAGE 13  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
MAINTENANCE WORK  
DATE TIME ZONE / LOCATION  
REASON FOR WORK  
WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED  
Approved Document No: GLT.MAN-102  
Issue: 1.3 Authorised: GH Date: 9/6/2004  
PAGE 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
FALSE ALARMS  
DATE TIME ZONE /  
CAUSE (IF KNOWN) MAINTENANCE MAINTENANCE CATEGORY OF FURTHER  
SIGNED  
LOCATION OR ACTIVITIES IN  
VISIT NEEDED  
(YES/NO)  
FINDINGS  
FALSE ALARM ACTION  
REQUIRED  
ALARM AREA  
Approved Document No: GLT.MAN-102  
PAGE 15  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS  
DATE TIME ZONE / LOCATION  
DETAILS OF EVENT  
ACTION  
DATE  
INITIALS  
(INCLUDING CAUSE IF KNOWN)  
REQUIRED  
COMPLETED  
Approved Document No: GLT.MAN-102  
Issue: 1.3 Authorised: GH Date: 9/6/2004  
PAGE 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
11 COMMISSIONING THE SYSTEM, INCLUDING P.S.E.  
The commissioning of this fire alarm system should be performed by a qualified commissioning engineer, who has  
an understanding of sections 2,3,& 4 of BS5839 pt 1:2002 (i.e. Design considerations, Limitations of false alarms,  
Installation recommendations)  
The system layout drawing should be checked for accuracy & stored in a safe place, accessible to any fire officer.  
The system set-up data chart (GLT.MAN-110, section 9) should be checked for accuracy.  
The fire alarm log book contact details should be checked for completeness.  
The insulation of cables should be checked in accordance with BS5839 Pt1: 2002 clause 38.2 for compliance.  
The Earthing should be checked in accordance with BS5839 Pt1: 2002 clause 38.2 for compliance.  
The PSE mains feed from a 3A spur should be checked. It should be protected by an over current device (MCB)  
NOT an earth leakage device (RCD).  
The PSE Charger voltage should be checked & adjusted if necessary (28.3 with batteries disconnected).  
The battery voltage should be checked (should be between 24 & 27V)  
All call points & detectors can signal an alarm condition and indicate the correct zone (and text message) on the fire  
alarm panel.  
The Sound pressure level throughout the building should be checked for compliance with the recommendations of  
BS5839 Pt1: 2002 clause 16.2  
Any deviations from BS5839 Pt1 clause 7.2 should be listed in the Certificate of Installation & Commissioning.  
The Certificate of Installation & Commissioning should be completed, and the whole user manual passed to the  
relevant person on site. (They should be given a brief training on the basic operation of the FACP)  
11.1 DESIGN, INSTALLATION & COMMISSIONING CERTIFICATES  
The guidelines in BS 5839 Pt1: 2002 say that each stage of the system design and installation should have a separate  
certificate. Before this User Manual is handed over to the relevant person(s) on site, the following certificates (or the  
relevant company’s equivalent) should be completed by the system designer, the installation engineer and the  
commissioning engineer. The System Description sheet should also be completed on Page 12 as should the relevant  
parts of the Log Book section on Page 13.  
The user, or responsible person should then complete the acceptance certificate to acknowledge that they have been  
instructed in the use of the fire alarm, have witnessed that it is operational, and have been given all the relevant  
paperwork (drawings, log book, user manual, etc)  
Approved Document No: GLT.MAN-102  
PAGE 17  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
Certificate of Design for the Premier SX Fire Alarm System installed at:  
Address:  
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the  
design of the fire alarm system, particulars of which are set out below, CERTIFY that the said design  
for which I/we have been responsible complies to the best of my/our knowledge and belief with the  
recommendations of section 2 of BS 5839-1:2002 for the system category described below, except  
for the variations, if any, stated in this certificate  
Name (in block letters):  
Signature:  
Position:  
Date:  
For and on behalf of:  
Address:  
Postcode:  
The extent of liability of the signatory is limited to the system described below.  
System Category (see BS 5839-1:2002, Clause 5):  
Variations from the recommendations of section 2 of BS 5839-1:2002 (see Clause 7):  
Extent of system covered by this certificate:  
Brief description of areas protected (not applicable for Category M, L1 or P1 systems):  
Approved Document No: GLT.MAN-102  
PAGE 18  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
Measures incorporated to limit false alarms. Account has to be taken of the guidance contained  
in section 3 of BS 5839-1: 2002 and, more specifically (tick as appropriate):  
The System is manual. Type & siting of manual call points takes account of the guidelines  
contained in section 3 of BS 5839-1  
The system incorporates automatic fire detectors, and account has been taken of reasonably  
foreseeable causes of unwanted alarms, particularly in the selection and siting of detectors  
An appropriate analogue system has been specified  
An appropriate multi-sensor system has been specified  
A time-related system has been specified. Details:  
Fire signals from automatic fire detectors result initially in a staff alarm, which delays a  
general alarm / transmission of signals to an alarm receiving centre (delete as applicable)  
for  
min.  
Appropriate guidance has been provided to the user to enable limitation of false alarms.  
Other measures as follows:  
INSTALLATION & COMMISSIONING RECOMMENDATIONS  
It is strongly recommended that installation and commissioning be undertaken in accordance with  
the recommendations of section 4 and section 5 of BS 5839-1: 2002 respectively.  
SOAK TEST  
In accordance with the recommendations of clause 35.2.6 of BS 5839-1:2002, it is recommended  
that following commissioning a soak period of  
(enter a period of at least 1 week)  
should follow  
As the system incorporates no more than 50 automatic fire detectors, no soak test is necessary  
to satisfy the recommendations of BS 5839-1:2002  
VERIFICATION  
Verification that the system complies with BS 5839-1:2002 should be carried out, on completion, in  
accordance with BS 5839-1:2002 Clause 43  
Yes  
MAINTENANCE  
To be decided by the purchaser or user  
No  
It is strongly recommended that, after completion, the system is maintained in accordance with  
section 6 of BS 5839-1:2002  
USER RESPONSIBILITIES  
The user should appoint a responsible person to supervise all matters pertaining to the fire alarm system  
in accordance with the recommendations of section 7 of BS 5839-1:2002  
Approved Document No: GLT.MAN-102  
PAGE 19  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
Certificate of Installation for the Premier SX Fire Alarm System installed at:  
Address:  
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the  
installation of the fire alarm system, particulars of which are set out below, CERTIFY that the said  
installation for which I/we have been responsible complies to the best of my/our knowledge and belief  
with the specifications described below, and with the recommendations of BS5839-1:2002, except for  
the variations, if any, stated in this certificate  
Name (in block letters):  
Signature:  
Position:  
Date:  
For and on behalf of:  
Address:  
Postcode:  
The extent of liability of the signatory is limited to the system described below.  
Extent of the installation work covered by this certificate.  
Specification against which the system was installed:  
Variations from the specification and/or section 4 of BS 5839-1:2002 (see clause 7)  
The wiring has been tested in accordance with the recommendations of clause 38 of BS 5839-1:2002.  
The test results have been recorded and provided to:  
Unless supplied by others, the “as fitted” drawings have been supplied to the person responsible for  
commissioning the system (see BS 5839-1:2002 clause 36.2m  
Approved Document No: GLT.MAN-102  
PAGE 20  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
Certificate of COMMISSIONING for the Premier SX Fire Alarm System installed at:  
Address:  
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the  
commissioning of the fire alarm system, particulars of which are set out below, CERTIFY that the said  
work for which I/we have been responsible complies to the best of my/our knowledge and belief with the  
recommendations of Clause 39 of BS5839-1:2002, except for the variations, if any, stated in this certificate  
Name (in block letters):  
Signature:  
Position:  
Date:  
For and on behalf of:  
Address:  
Postcode:  
The extent of liability of the signatory is limited to the system described below.  
Extent of the installation work covered by this certificate.  
Variations from the recommendations of clause 39 of BS 5839-1:2002 (see clause 7)  
All equipment operates correctly  
Installation work is, as far as can be reasonably ascertained, of an acceptable standard  
The entire system has been inspected and tested in accordance with the recommendations of 39.2.c  
of BS 5839-1: 2002.  
The system performs as required by the specifications prepared by:  
Taking into account the guidance contained in section 3 of BS 5839-1: 2002, I/we have not  
identified any obvious potential for an unacceptable rate of false alarms.  
The documentation described in Clause 40 of BS 5839-1:2002 has been provided to the user  
The following work should be completed before/after (delete as applicable) the system becomes operational  
The following potential causes of false alarms should be considered at the time of the next service visit:  
Before the system becomes operational, it should be soak tested in accordance with the recommendations  
of Clause 35.2.6 of BS 5839-1:2002 for a period of:  
(enter a period of 1 week, the period  
required by the design specification, or the period recommended by the signatory to this certificate,  
whichever period is the greatest, or delete if not applicable)  
Approved Document No: GLT.MAN-102  
PAGE 21  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK  
Certificate of Acceptance for the Premier SX Fire Alarm System installed at:  
Address:  
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the  
acceptance of the fire alarm system, particulars of which are set out below, ACCEPT the system  
on behalf of:  
Name (in block letters):  
Signature:  
Position:  
Date:  
For and on behalf of:  
Address:  
Postcode:  
The extent of liability of the signatory is limited to the system described below.  
Extent of the system covered by this certificate.  
All installation work appears to be satisfactory.  
The system is capable of giving a fire alarm signal  
The facility for remote transmission of alarms to an alarm receiving centre operates correctly.  
(Delete if not applicable)  
The following documents have been provided to the purchaser or user:  
“As fitted” drawings.  
Operating and maintenance instructions  
Certificates of Design, Installation and Commissioning.  
A log book.  
Sufficient representatives of the user have been properly instructed in the use of the system,  
including, at least, all means of triggering fire signals, silencing and resetting the system, and  
avoidance of false alarms.  
All relevant tests, defined in the purchasing specification, have been witnessed.  
(Delete if not applicable.)  
The following work is required before the system can be accepted:  
Approved Document No: GLT.MAN-102  
PAGE 22  
Issue: 1.3  
Authorised: GH  
Date: 9/6/2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Philips Fax Machine HFC 325 User Manual
Philips Indoor Furnishings TUFFGUARD Series User Manual
Philips Power Supply LR03PB4C User Manual
Philips Stereo Amplifier TDA8559T User Manual
Philips TV Receiver AW1 User Manual
Philips Universal Remote SRU4050 User Manual
Pioneer CD Player DRM 1004XR21 User Manual
Pioneer Stereo System X Z9 User Manual
Poulan Chainsaw 2001 03 User Manual
Precision Power Stereo Amplifier PCX 250 User Manual