Precisionaire Air Cleaner Alpha 95 User Manual

®
Alpha 95  
Bulletin PB1400-1106  
95% DOP Filter  
FOREMOST IN AIR FILTRATION  
General  
Standard Alpha 95 filters have 1.7 times the cfm  
capacity of standardAlpha Cell 99.97% DOP HEPA  
filters at the same clean pressure drop. They are  
normally rated at 500 fpm so that filter banks with  
95% DOP filters can be sized the same as  
ASHRAE-rated filter banks.  
Flanders Alpha 95 filters are designed for use in  
HVAC applications requiring cleaner air than is  
possible with ASHRAE rated filters, but where  
HEPA filtered air is not required. The filters are  
rated at 95% efficiency on 0.30 micrometer  
particles by the DOP test method. The Alpha 95  
is rated MERV 17 per ASHRAE Standard 52.2.  
Typical applications for Alpha 95 include:  
• Hospitals  
Alpha 95 filters are identical in design and con-  
struction to theAlpha Cell HEPA filters except that  
the media is 95% efficient on 0.30 micrometer par-  
ticles.  
• Biomedical  
• Pharmaceutical  
• Biotechnology  
Installation Considerations  
• Genetic Research  
• Universities  
Alpha 95 filters should be installed in Flanders  
leak tight Alpha HEPA frames or Surelock Side  
Access HEPA Housings on the positive-pressure  
side of the system fan to prevent air bypass.  
Sureaire diffuser sections, air mixing baffles or  
long transitions should be used if the bank is close  
to the fan.  
• Laboratories  
• Food Processing  
• Photo Processing  
• Semiconductor Fabrication  
• Industrial Processing Systems Product  
Installation of Flanders ASHRAE efficiency  
prefilters upstream of the fan is recommended to  
ensure economical Alpha 95 filter life.  
Important Features  
Minimum efficiency is 95% on 0.30 micrometer  
particles.  
Manufactured in a variety of wood and metal  
frame types.  
Available with a media pack with aluminum  
separators or with a separatorless pack.  
Available in a variety of sizes with either a gasket  
or gel seal.  
Flanders Filters ~ Foremost in Air Filtration  
Toll Free: 1-800-637-2803  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALPHA 95 COMPONENT CHART  
0 - 00J - W - 08 - 03 - IU - 12 - 00 - GG - F  
Hardware  
0 = None  
T = Extractor Clips  
Filter Depth  
D = 5-7/8”  
F = 11-1/2”  
Efficiency  
00J = 95% DOP  
Filter Face Size (HxW)  
Capacity/Pack Style  
C = Separator  
D = 4 inch Pureform  
F = 8 inch Pureform  
W = 11 inch Pureform  
B = 8”  
C = 12”  
E = 18”  
G = 24”  
N = 30”  
P= 36”  
H = 42”  
Q = 48”  
R = 60”  
S = 72”  
U = 11-3/8”  
Y = 23-3/8”  
Frame Material  
Odd Size Designator  
02 = 16 GA 409 Stainless  
03 = 16 GA 304 Stainless  
04 = 3/4 in. FIRE RETARDANT PLYWOOD  
05 = FABRICATED ALUMINUM  
07 = 3/4 in. FIRE RETARDANT  
PARTICLE BOARD  
08 = 16 GA. GALVANNEAL  
11 = 3/4 in. NON FIRE RETARDANT  
PARTICLE BOARD  
Odd size designators are anAlpha Numeric description. The  
first two digits specify the height whole number with an alpha  
designator specifying the height fraction. The second two  
digitsspecifythewidthwholenumberwithanalphadesignator  
specifying the width fraction. And the last alpha designator  
specifies the depth. If the height or width is less than 10  
inches,use a 0 in front of the dimension.  
A= 0”  
B = 1-1/16” G = 3/8”  
C = 1/8” H = 7/16”  
D = 3/16” J = 1/2”  
E = 1/4” K = 9/16”  
F = 5/16”  
L= 5/8”  
M = 11/16”  
N = 3/4”  
P = 13/16”  
Q = 7/8”  
16 or 17 = CORROSION-RESISTANT  
24 GA. STEEL  
Frame Style  
00 = BOX  
01 = SINGLE HEADER (13/16”)  
02 = DOUBLE HEADER (13/16”)  
03 = DOUBLE TURNED FLANGE  
05 = 3/4 IN. DEEP CHANNEL GEL SEAL  
08 = DOUBLE-TURNED FLANGE, ONE SIDE  
R = 15/16”  
Sealant Material  
IU = URETHANE  
IH = HOT MELT  
Gasket material  
0 = NONE  
Faceguard Material  
0 = NONE  
1 = GALVANIZED 4X4 MESH  
G = ALUMINIZED EXPANDED METAL  
2 = 17GA.SS 4X4 MESH  
5 = 22 GA.SS 4X4 MESH  
Faceguard Location  
0 = NONE  
1 = UPSTREAM  
2 = DOWNSTREAM  
Gasket location  
0 = NONE  
1 = UPSTREAM  
2 = DOWNSTREAM  
3 = BOTH SIDES  
1 = NEOPRENE  
5 = BLUE JEL  
Frame: Alpha 95 filters are available in a variety of wood and metal frame materials such as particle board, plywood,  
galvanized steel and stainless steel. Alpha 95 filters are also available in 24 gauge corrosion resistant steel in single or  
double headers for installation in side access or plenum applications.  
Seal: The standard gasket seal is 0.75” x 0.25” neoprene for installation on either the upstream, downstream or both  
sides of the filter. The standard Fluid Seal is Flanders Blu-Jel® Seal which is a two-part silicone material suitable for  
temperatures up to 390°F.  
Faceguards: Faceguards are used to protect the filter media from mechanical damage. The typical faceguard material  
is expanded aluminized steel. Galvanized 4 x 4 mesh welded wire and Type 304 stainless steel faceguards are also  
available.  
UL: Alpha 95 filters are either UL900 Class 1 or Class 2 listed depending on materials of construction.  
Banks: Alpha Frames are designed forAlpha 95 filters in built-up filter banks. Each filter is secured in the frame with  
four bolt-type fasteners that either compress the gasket or press the knife edge into the gel in the filter channel to  
maintain a leak-tight seal. Surelock B or C-3 gasket seal and Surelock C-4 for Blu Jel HEPA Filter Housings are  
recommended for side-access applications. The filters are sealed in place with either spring-loaded swing arm assem-  
blies or a locking mechanism. The swing arm assemblies or locking mechanism either compress the gasket or press  
the knife edge into the gel in the filter channel to maintain a leak-tight seal.  
Flanders Filters ~ Foremost in Air Filtration  
Toll Free: 1-800-637-2803  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide Specifications  
1.0  
General  
1.1 Alpha 95 filters shall be extended media  
(separator type) (Pureform separatorless  
type) filters as manufactured by Flanders.  
2.2 The filter pack shall be sealed into a  
(galvaneal) (409 stainless steel) (304  
stainless steel) (particleboard) (fire retardant  
particleboard) (fire retardant plywood) frame  
with a fire retardant (polyurethane foam)  
(solid urethane) sealant. (Steel frames shall  
be 16 ga.) (Wood frames shall be 3/4”  
thick.)  
1.2 Filter sizes, capacities and construction op-  
tions shall be as scheduled on the drawings.  
1.3 Filters shall be (UL 900 Class 1)( UL 900  
Class 2) listed.  
2.3 (A 40-durometer closed-cell neoprene  
gasket) (Silicone gel in a channel) shall be  
provided on one or more sides to seal the  
filter in the mounting device.  
2.0 Filter Construction  
2.1 The filter pack shall be constructed by pleat-  
ing a continuous sheet of non-woven water-  
resistant fiberglass media around hemmed-  
edge corrugated aluminum separators. The  
filter pack shall be constructed by pleating a  
continuous sheet of formed, corrugated me-  
dium so that the pack is self-supporting  
without the use of spacers of any kind,  
including separators, tape strings, adhesives  
or strips of media.  
3.0 Performance  
3.1 Initial and final resistances shall not exceed  
the scheduled values.  
3.2 The rated minimum efficiency of 95% on 0.3  
micrometer size particles shall be as  
determined by the DOP Test Method  
®
Represented By:  
Flanders Filters, Inc.  
531 Flanders Filter Road  
Washington, NC 27889  
Phone: (252) 946-8081  
Fax: (252) 946-3425  
Toll Free: (800) 637-2803  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Music Mixer SRM 2410 User Manual
Philips Battery Charger TEA1104 User Manual
Philips Bottle Warmer SCF606 User Manual
Philips DVD Recorder DVDR 725H 05 User Manual
Philips Indoor Furnishings 44992 30 16 User Manual
Planet Technology Switch GSW 2416SF User Manual
Plantronics Conference Phone MCD100 M User Manual
Polycom Webcam 3725 22724 003 A User Manual
Porter Cable Grinder 7425 User Manual
ProForm Treadmill 590 rt User Manual