Powerware Power Supply FE QFE UPS User Manual

®
Powerware FERRUPS  
FE/QFE UPS  
User’s Guide  
500 VA–18 kVA, 50 and 60 Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
Powerware FERRUPS  
FE/QFE UPS  
User’s Guide  
500 VA–18 kVA, 50 and 60 Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Class A EMC Statements  
FCC Part 15  
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to  
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when  
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency  
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio  
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case  
the user will be required to correct the interference at his own expense.  
ICES-003  
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment  
Regulations ICES-003.  
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.  
For Users in Germany  
We hereby certify that the uninterruptible power system (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, 1.4 kVA, 1.8 kVA,  
2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) complies with the RFI suppression  
requirements of Vfg. 243/1991 and Vfg. 46/1992. The German Postal Service was notified that the equipment is being  
marketed. The German Postal Service has the right to retest the equipment and verify compliance.  
Hiermit wird bescheinigt, daß die unterbrechungsfreie Stromversorgung (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA,  
1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) in Übereinstimmung mit  
den Bestimmungen der Vfg. 243/1991 und Vfg. 46/1992 funkentstört ist. Der Deutschen Bundespost wurde das  
Inverkehrbringen dieses Gerätes angezeigt und die Berechtigung zur Überprüfung der Serie auf Einhaltung der  
Bestimmung eingeräumt.  
Powerware reserves the right to change specifications without prior notice.  
Powerware and CheckUPS are registered trademarks and EnviroCom is a trademark of Powerware Corporation.  
Microsoft and Windows are registered trademarks of Microsoft Corporation.  
HyperTerminal is a registered trademark of Hilgraeve.  
TeleVideo is a registered trademark of TeleVideo, Inc.  
WYSE is a registered trademark of WYSE Technology Inc.  
Copyright 2002 Powerware, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any  
way without the express written approval of Powerware.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
Identifying Your UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
3 UPS Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Startup for the FE and QFE 500 VA–3.1 kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Startup for the FE and QFE 4.3–18 kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Rear Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Front Panel Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Using the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Changing Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Entering Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
Displaying and Changing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Locking and Unlocking the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Using the Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Automatic System Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Logic Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Inverter Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Extended Power Outages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
5 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Powerware Software Suite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Connecting a Terminal or Computer to the RS-232 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
Entering Commands from a Terminal or Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Remote Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
Remote Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
6 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Environmental Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Extended Runtimes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Warranties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
8 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59  
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59  
Alarm and Inverter Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
Reading the Alarm Log from a Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
Reading the Inverter Log from a Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
Reading the Alarm Log from a Terminal or Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Reading the Inverter Log from a Terminal or Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
Alarm Code Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
Service and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 1  
INTRODUCTION  
Welcome to the growing Powerware FERRUPS uninterruptible power  
system (UPS) family. This UPS represents a breakthrough in the design  
of advanced, online UPSs.  
Identifying Your UPS  
NOTE Before starting up the UPS, verify that it has been installed according to the  
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide.  
FERRUPS UPSs come in different sizes (see Figure 1). If your UPS is a  
500 VA–3.1 kVA model, continue with “Startup for the FE and  
QFE 500 VA–3.1 kVA UPS” on page 17. If your UPS is a 4.3–18 kVA  
model, continue with “Startup for the FE and QFE 4.3–18 kVA UPS” on  
page 19.  
4.3–18 kVA Models  
500 VA–3.1 kVA Models  
Figure 1. FERRUPS UPS  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 2  
SAFETY WARNINGS  
Read the following precautions before you install the UPS.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you  
should follow during installation and maintenance of the UPS and batteries. Please  
read all instructions before operating the equipment and save this manual for future  
reference.  
DANGER  
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed  
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER  
SERVICEABLE PARTS inside the UPS.  
WARNING  
: This UPS contains its own energy source (batteries). The output receptacles may  
carry live voltage even when the UPS is not connected to an AC supply.  
: Do not remove or unplug the input cord when the UPS is turned on. This removes  
the safety ground from the UPS and the equipment connected to the UPS.  
: To reduce the risk of fire or electric shock, install this UPS in a temperature and  
humidity controlled, indoor environment, free of conductive contaminants. Ambient  
temperature must not exceed 40°C (104°F). Do not operate near water or  
excessive humidity (95% max).  
: To comply with international standards and wiring regulations, the total equipment  
connected to the output of this UPS must not have an earth leakage current  
greater than 1.5 milliamperes.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
CAUTION  
: Batteries can present a risk of electrical shock or burn from high short-circuit  
current. Observe proper precautions. Servicing should be performed by qualified  
service personnel knowledgeable of batteries and required precautions. Keep  
unauthorized personnel away from batteries.  
: Proper disposal of batteries is required. Refer to your local codes for disposal  
requirements.  
: Never dispose of batteries in a fire. Batteries may explode when exposed to flame.  
Sikkerhedsanvisninger  
VIGTIGE SIKKERHEDSANVISNINGER  
GEM DISSE ANVISNINGER  
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE  
SIKKERHEDSANVISNINGER  
FARE  
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og  
vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af  
UPS’ens indvendige dele kan repareres af brugeren.  
ADVARSEL!  
: Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan  
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.  
: Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er  
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.  
: Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit  
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk  
stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær  
vand eller høj fugtighed (maksimalt 95%).  
: I overensstemmelse med internationale normer og bestemmelser for el-installation  
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke  
overskride en jordafdelingsspænding på mere end 1,5 milliampere.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
ADVARSEL  
: Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj  
kortslutningsspænding. De korrekte forholdsregler bør overholdes.  
: Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for  
bortskaffelsesprocedurer.  
: Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere  
ved åben ild.  
Belangrijke Veiligheidsinstructies  
BELANGRIJKE VEILIGHEIDSINSTRUCTIES  
BEWAAR DEZE INSTRUCTIES  
DEZE HANDLEIDING BEVAT BELANGRIJKE  
VEILIGHEIDSINSTRUCTIES  
GEVAAR  
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en  
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden  
uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER  
kunnen worden GEREPAREERD.  
WAARSCHUWING  
: Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen  
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is  
aangesloten.  
: Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit  
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen  
aardebeveiliging meer hebben.  
: Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in  
een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd,  
waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur  
mag 40°C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge  
vochtigheid (max. 95%).  
: Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de  
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen  
aardlekstroom van meer dan 1,5 milliampère hebben.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
OPGELET  
: Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als  
gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.  
: De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw  
plaatselijke voorschriften.  
: Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.  
Tarkeita Turvaohjeita  
TÄRKEITÄ TURVAOHJEITA - SUOMI  
SÄILYTÄ NÄMÄ OHJEET  
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA  
VAARA  
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot  
on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä  
MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.  
VAROITUS  
: Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla  
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.  
: Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa  
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.  
: Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,  
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia  
epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä  
ja vältä kosteita tiloja (95 % maksimi).  
: Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän  
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä  
1,5 milliampeeria (mA).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
VARO  
: Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään  
oikosulkuun. Noudata asianmukaisia ohjeita.  
: Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia  
määräyksiä.  
: Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.  
Consignes de sécurité  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ  
IMPORTANTES  
DANGER!  
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de  
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.  
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.  
AVERTISSEMENT!  
: Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie  
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le  
secteur.  
: Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous  
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.  
: Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur  
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la  
température et l’humidité ambiantes sont contrôlées. La température ambiante ne  
doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère  
excessivement humide (95 % maximum).  
: Afin d’être conforme aux normes et règlements internationaux de câblage, le  
courant de fuite à la terre de la totalité du matériel branché sur la sortie de  
l’onduleur ne doit pas dépasser 1,5 mA.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
ATTENTION!  
: Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par  
des courts-circuits de haute intensité. Prendre les précautions nécessaires.  
: Une mise au rebut réglementaire des batteries est obligatoire. Consulter les  
règlements en vigueur dans votre localité.  
: Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire  
exploser.  
Sicherheitswarnungen  
WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN.  
DIESES HANDBUCH ENTHÄLT WICHTIGE  
SICHERHEITSANWEISUNGEN.  
WARNUNG  
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten  
sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine  
vom Benutzer zu wartenden Komponente.  
ACHTUNG  
: Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den  
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an  
einer Wechselspannungsquelle angeschlossen ist.  
: Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet  
ist, weil hierdurch die Sicherheitserdung von der USV und den daran  
angeschlossenen Geräten entfernt wird.  
: Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden  
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine  
leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C  
nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher  
Luftfeuchtigkeit (max. 95 %) betreiben.  
: Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an  
den Ausgang dieser USV angeschlossenen Geräte zusammen einen  
Erdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
VORSICHT!  
: Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder  
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind  
unbedingt zu beachten.  
: Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen  
Bestimmungen zu beachten.  
: Batterien niemals verbrennen, da sie explodieren können.  
:
:
:
°
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
:
:
:
:
Avvisi di sicurezza  
IMPORTANTI ISTRUZIONI DI SICUREZZA  
CONSERVARE QUESTE ISTRUZIONI  
QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI  
SICUREZZA  
PERICOLO  
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le  
operazioni di riparazione e di manutenzione devono essere effettuate  
ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo  
statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.  
AVVERTENZA  
: Questo gruppo statico di continuità contiene una fonte di energia autonoma (le  
batterie). Le prese di uscita possono condurre tensione energizzata quando il  
gruppo statico di continuità non è collegato con una fonte di alimentazione a  
corrente alternata.  
: Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di  
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di  
sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di  
continuità in un ambiente interno a temperatura ed umidità controllata, privo di  
agenti contaminanti conduttivi. La temperatura ambiente non deve superare i  
40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità  
eccessiva (95% max).  
: Per conformità con gli standard internazionali e con le norme in merito al  
cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di  
continuità non deve avere una corrente di dispersione di terra superiore a  
1,5 milliampere.  
ATTENZIONE  
: Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da  
alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.  
: Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento  
fare riferimento alle disposizioni locali.  
: Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle  
fiamme.  
Viktig Sikkerhetsinformasion  
FARLIG  
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må  
kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE  
SERVICE PÅ NOEN AV DELENE i UPS’en.  
FARLIG  
: Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være  
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.  
: Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at  
ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet  
med den.  
: For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et  
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for  
ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må  
ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere  
total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med  
internasjonale standarder og forkablingsbestemmelser.  
FORSIKTIG  
: Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy  
kortslutningsstrøm. Følg instruksene.  
: Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om  
fjerning av batterier.  
: Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.  
Regulamentos de Segurança  
INSTRUÇÕES DE SEGURANÇA IMPORTANTES  
GUARDE ESTAS INSTRUÇÕES  
ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA  
IMPORTANTES  
CUIDADO  
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser  
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não  
há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.  
ADVERTÊNCIA  
: Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída  
podem conter voltagem ativa quando a UPS não se encontra conectada a uma  
fonte de alimentação de corrente alternada.  
: Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto  
removerá o aterramento de segurança da UPS e do equipamento conectado.  
: Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente  
interno com temperatura e umidade controladas e livres de contaminadores  
condutíveis. A temperatura ambiente não deve exceder 40°C. Não opere próximo a  
água ou em umidade excessiva (máx: 95%).  
: Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o  
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga  
à terra maior que 1,5 miliampères.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
PERIGO  
: As baterias podem apresentar o risco de choque elétrico, ou queimaduras  
provenientes de alta corrente de curto-circuito. Observe as instruções adequadas.  
: Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do  
local para maiores informações sobre os regulamentos de descarte de produtos.  
: Nunca jogue as baterias no fogo, porque há risco de explosão.  
Предупреждения по мерам безопасности  
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
СОХРАНИТЕ ЭТИ УКАЗАНИЯ  
ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ  
УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
ОПАСНО  
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ.  
Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО  
УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ.  
Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.  
ПРЕДУПРЕЖДЕНИЕ  
: Данный ИБП содержит собственные источники энергии  
(аккумуляторы). На выходных розетках может иметься напряжение,  
даже когда ИБП не подключен к сети переменного тока.  
: Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки  
при включенном ИБП. При этом защитное заземление отключается  
от ИБП и от оборудования, подключенного к ИПБ.  
: Для снижения опасности пожара или поражения электрическим  
током устанавливайте ИБП в закрытом помещении с  
контролируемыми температурой и влажностью, в котором  
отсутствуют проводящие загрязняющие вещества. Температура  
окружающего воздуха не должна превышать 40°С. Не  
эксплуатируйте устройство около воды или в местах с повышенной  
влажностью (макс. 95%).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Для обеспечения соблюдения требований международных  
стандартов и требований к разводке электрических цепей,  
суммарная величина тока утечки на землю всего оборудования,  
подключенного к выходу ИБП, не должна превышать  
1,5 миллиампера.  
ОСТОРОЖНО  
: Аккумуляторы могут вызвать опасность поражения электрическим  
током или ожога от тока короткого замыкания. Соблюдайте  
соответствующие меры предосторожности.  
: Необходимо соблюдать правила утилизации аккумуляторов.  
Обратитесь к местным нормативным актам за информацией о  
требованиях к утилизации.  
: Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут  
взорваться под воздействием огня.  
Advertencias de Seguridad  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD  
IMPORTANTES  
PELIGRO  
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico  
deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO  
AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro  
del SIE.  
ADVERTENCIA  
: Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de  
salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a  
un suministro de corriente alterna (c.a.).  
: No retire o desenchufe el cable de entrada mientras el SIE se encuentre  
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos  
conectados al SIE.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un  
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes  
conductores. La temperatura ambiente no debe exceder los 40°C. No trabaje cerca  
del agua o con humedad excesiva (95% máximo).  
: Para cumplir con los estándares internacionales y las normas de instalación, la  
totalidad de los equipos conectados a la salida de este SIE no debe tener una  
intensidad de pérdida a tierra superior a los 1,5 miliamperios.  
PRECAUCIÓN  
: Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras  
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones  
correspondientes.  
: Es necesario desechar las baterías de un modo adecuado. Consulte las normas  
locales para conocer los requisitos pertinentes.  
: Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las  
expone a la llama.  
Säkerhetsföreskrifter  
VIKTIGA SÄKERHETSFÖRESKRIFTER  
SPARA DESSA FÖRESKRIFTER  
DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA  
SÄKERHETSFÖRESKRIFTER  
FARA  
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD  
SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som  
ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.  
VARNING  
: Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan  
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.  
: Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort  
skyddsjordningen från både UPS-enheten och den anslutna utrustningen.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Minska risken för brand eller elektriska stötar genom att installera denna  
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga  
ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C.  
Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).  
: För att överensstämma med internationell standard och installationsföreskrifter får  
inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha  
läcksström som överstiger 1,5 milliampere.  
VIKTIGT  
: Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.  
Följ tillämpliga anvisningar.  
: Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.  
: Använda batterier får aldrig brännas upp. De kan explodera.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 3  
UPS STARTUP  
This section provides step-by-step instructions for starting the  
Powerware FERRUPS UPS. Follow these procedures closely to avoid  
potential damage to your equipment or the UPS and to protect yourself  
and others from hazardous operating conditions.  
Startup for the FE and QFE 500 VA–3.1 kVA UPS  
To start the FE and QFE 500 VA–3.1 kVA UPS, use the following steps:  
1. Confirm the equipment to be protected by the UPS is powered  
off.  
2. For FE Plug-Receptacle UPSs: Plug the UPS power cord into a  
power outlet.  
NOTE If the plug does not match your receptacle outlet, ask your electrician to install  
the proper outlet.  
For QFE Plug-Receptacle UPSs: Disconnect the power cord from  
the computer or other equipment to be protected by the UPS  
and plug it into the UPS. Plug the other end of the power cord  
into a power outlet.  
NOTE Do not use the cord supplied with the UPS; this cord is for plugging the  
equipment into the UPS output receptacles.  
NOTE If the plug does not match your receptacle outlet, ask your electrician to install  
the proper outlet.  
NOTE If you need to order a UPS power cord, please call your service representative.  
For Hardwired UPSs: Confirm that an electrician has completed  
and tested the connection to the proper power source and  
connected your protected equipment according to the  
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation  
Guide. Turn the AC line disconnect switch to the ON position.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
3. The AC LINE indicator illuminates (see Figure 2).  
NOTE The AC LINE indicator does not illuminate for FE models with serial numbers  
25000 and greater until the UPS ON/OFF switch is turned to the ON position.  
ALARM  
AC LINE  
READY CHARGING BATTERY  
POWER  
Figure 2. Front Panel Indicators  
4. If you have an external battery cabinet with a DC switch, turn  
the switch to the ON position.  
5. Turn the UPS ON/OFF switch to the ON position. After a short  
startup test, the READY indicator flashes for a few seconds and  
then remains illuminated. The UPS is ready to supply output  
power.  
NOTE The UPS and external battery cabinets are shipped with the batteries charged.  
However, batteries may lose some of the charge during shipping and storage. You can  
use the UPS immediately after unpacking, but it may not provide the full-rated backup  
time during a power failure. Upon initial startup, the UPS may need to operate for  
24 hours before the battery is fully charged and full battery-backup time is available. If  
the CHARGING indicator is illuminated, operate the UPS for 24 hours to fully charge  
the battery.  
6. For Plug-Receptacle UPSs: Plug the equipment to be protected  
into the UPS output receptacles.  
NOTE For QFE models, use the supplied UPS cord to connect your equipment to the  
UPS output receptacles.  
For Hardwired UPSs: Turn the bypass switch to the UPS position.  
7. Turn on the equipment that is connected to the UPS.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
Startup for the FE and QFE 4.3–18 kVA UPS  
To start the FE and QFE 4.3–18 kVA UPS, use the following steps:  
1. Confirm the equipment to be protected by the UPS is powered  
off.  
2. For Plug-Receptacle UPSs: Verify that the AC input power is off  
at the service panel. Plug the UPS power cord into a power  
outlet.  
NOTE If the plug does not match your receptacle outlet, ask your electrician to install  
the proper outlet.  
For Hardwired UPSs: Confirm that an electrician has completed  
and tested the connection to the proper power source and  
connected your protected equipment according to the  
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation  
Guide. Confirm that your AC line disconnect switch and the  
UPS ON/OFF switch are both in the OFF position.  
3. If your UPS has a DC switch, turn on the switch according to  
the UPS model:  
4.3–7 kVA: If you have an external battery cabinet(s) with a DC  
switch, turn the switch to the ON position.  
If you do not have an external battery cabinet(s): unlock the  
UPS front cover panel using the FERRUPS key and remove the  
front cover panel. Locate the DC switch behind the UPS front  
cover panel. If there is a precharge button next to the switch,  
press it for a few seconds. Turn the DC switch to the ON  
position and reinstall the UPS front cover panel.  
10–18 kVA: If you have an external battery cabinet(s) with a DC  
switch, turn the switch to the ON position.  
4. Starting the UPS on battery power: Use the key to turn the  
ON/OFF switch to the ON position. After a brief self-check, the  
BATTERY POWER and READY indicators illuminate. The UPS  
beeps every 20 seconds, indicating the UPS is running on  
battery power. The control panel scrolls this display:  
)(55836  
0RGHꢀ  
&KDUJHUꢀ  
$XWR  
2II  
%HHSHUꢀ (QDEOHG  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
NOTE If the ALARM indicator is on, read the alarm message on the control panel  
display, turn the ON/OFF and DC switches to the OFF position, and call your service  
representative.  
For Plug-Receptacle UPSs: Turn the AC input power on at the  
service panel. The AC LINE indicator illuminates. After a few  
seconds, the UPS switches from battery power to AC input  
power. The BATTERY POWER indicator turns off.  
For Hardwired UPSs: Turn the AC line disconnect switch to the  
ON position. The AC LINE indicator illuminates. After a few  
seconds, the UPS switches from battery power to AC input  
power. The BATTERY POWER indicator turns off. Now, turn  
the UPS bypass switch (either on the back of the UPS or  
mounted nearby) to the UPS position.  
NOTE The UPS and external battery cabinets are shipped with the batteries charged.  
However, batteries may lose some of the charge during shipping and storage. You can  
use the UPS immediately after unpacking, but it may not provide the full-rated backup  
time during a power failure. Upon initial startup, the UPS may need to operate for  
24 hours before the battery is fully charged and full battery-backup time is available. If  
the CHARGING indicator is illuminated, operate the UPS for 24 hours to fully charge  
the battery.  
5. For Plug-Receptacle UPSs: Plug the equipment you want to  
protect into the UPS receptacles and turn on the equipment. If  
the ALARM indicator illuminates, see “Alarms” on page 59.  
For Hardwired UPSs: Turn on the equipment connected to the  
UPS. If the ALARM indicator illuminates, see “Alarms” on  
page 59.  
6. Set the time and date using the control panel.  
NOTE The correct time and date for is needed for the UPS alarm and inverter logs.  
Reset the time and date whenever the UPS has been shut down.  
Time is parameter 0; see “Parameters” on page 32 for more  
information. To set the time, follow these steps:  
Press this key:  
[DISPLAY]  
[0]  
Display shows:  
'LVSOD\ꢀ  
'LVSOD\ꢀ  
[ENTER]  
[PROGRAM]  
ꢁꢁ 7LPHꢀ ꢂꢂꢀꢃꢁꢀꢄꢁ  
ꢁꢁ 3JPꢀ  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
The date is parameter 10. To display the date, follow these  
steps:  
Press this key:  
[DISPLAY]  
[1][0]  
Display shows:  
'LVSOD\ꢀ  
'LVSOD\ꢀ  
ꢂꢁ  
[ENTER]  
[PROGRAM]  
ꢂꢁ 'DWHꢀ ꢁꢂꢅꢁꢂꢅꢆꢇ  
ꢂꢁ 3JPꢀ  
7. If your FERRUPS UPS is configured to use an external battery  
cabinet, you must program the battery capacity in ampere-hour  
(Ah) for the total number of battery packs used in the UPS. If  
you purchased one of the FERRUPS battery pack options  
available from Powerware, select the Ah value from Table 1.  
Before programming the battery Ah, enter the user password  
following the instructions in “Entering Passwords” on page 28.  
To change the battery Ah, parameter 69 (Batt Ah), follow these  
steps:  
Press this key:  
Display shows:  
[DISPLAY] [6] [9] [ENTER] ꢇꢆ %DWW $+ >'HIDXOW@  
[PROGRAM]  
[Ah Value from Table 1]  
[ENTER]  
ꢇꢆ 3JPꢀ  
ꢇꢆ 3JPꢀ  
ꢇꢆ 3JPꢀ  
>[[[@  
>QHZ YDOXH@  
where [[[ is the Battery Ah value from Table 1.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
Table 1. External Battery Pack Ah Values  
Battery Pack  
1ME  
Battery Ah  
100  
150  
200  
225  
300  
400  
600  
75  
Battery Pack  
1FE  
Battery Ah  
100  
150  
200  
225  
300  
400  
600  
75  
2ME  
2FE  
3ME  
3FE  
4ME  
4FE  
5ME  
5FE  
6ME  
6FE  
7ME  
7FE  
8ME  
8FE  
9ME  
100  
150  
200  
225  
300  
400  
600  
75  
9FE  
100  
150  
200  
225  
300  
400  
600  
100  
150  
200  
225  
300  
400  
600  
10ME  
11ME  
12ME  
13ME  
14ME  
15ME  
21ME  
24ME  
25ME  
EBPS10  
EBPS12.5  
EBPS18  
10FE  
11FE  
12FE  
13FE  
14FE  
15FE  
16FE  
17FE  
18FE  
19FE  
20FE  
21FE  
22FE  
150  
200  
33  
75  
75  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
Rear Panels  
This section shows the rear panels of the FERRUPS models.  
RS-232  
Communication  
Port  
Alarm Silence  
Switch  
On/Off Switch  
Power Cord  
Output  
Receptacles  
Figure 3. FERRUPS 500–850 VA UPS Rear Panel  
RS-232  
Communication  
Port  
Alarm Silence  
Switch  
On/Off Switch  
Output  
Receptacles  
Figure 4. FERRUPS 1.15–1.4 kVA Rear Panel  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Startup  
ON/OFF Switch  
RS-232  
Communication  
Port  
Alarm Silence  
Switch  
Output  
Receptacles  
Figure 5. FERRUPS 1.8–3.1 kVA Rear Panel  
Receptacle Panel  
(Optional for 7 kVA)  
RS-232  
Communication Port  
RS-232  
Communication Port  
Optional Receptacle  
Panel  
4.3–5.3 kVA Models  
7–18 kVA Models  
Figure 6. FERRUPS 4.3–18 kVA Rear Panels  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 4  
OPERATION  
This section describes:  
: The UPS front panel indicators  
: Using the control panel  
: Automatic system testing  
: Parameters  
: Shutting down the UPS  
Front Panel Indicators  
The UPS front panel indicators indicate how the UPS is operating and  
also alert you of potential power problems. Figure 7 shows the UPS  
front panel indicators. Table 2 explains the status of each indicator.  
ALARM  
AC LINE  
READY CHARGING BATTERY  
POWER  
Figure 7. Front Panel Indicators  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Table 2. Indicator Status  
Indicator  
Status  
Explanation  
AC LINE  
On  
The UPS is getting power from the AC input power source.  
The AC LINE indicator does not illuminate for FE models with serial numbers  
25000 and greater until the UPS ON/OFF switch is turned to the ON position.  
Off  
: The UPS is not getting input power.  
: There is a power outage.  
: The AC input breaker is tripped.  
: The UPS is unplugged.  
: For FE models with serial numbers 25000 and greater, the ON/OFF switch is not in  
the ON position.  
Flashing Not applicable.  
READY  
On  
The UPS is ready to provide battery backup power when needed.  
Off  
The UPS cannot provide battery backup power because:  
: It is in the Line Condition mode or the Off mode (see “Using the Control Panel” on  
page 27).  
: The batteries may be discharged.  
: It may be running on battery power.  
Flashing The UPS is testing the batteries as part of the automatic system test (see “Automatic  
System Test” on page 31); or, you have started a timed shutdown (see Table 8 on  
page 44).  
CHARGING  
On  
The UPS is charging its batteries.  
Off  
The battery charger is off; batteries are at full charge.  
Flashing Not applicable.  
BATTERY POWER  
On  
The UPS is providing power from its batteries; it is in the Inverter On mode.  
Off  
The UPS is providing conditioned power from the AC input power source, or the UPS is  
off.  
Flashing The UPS is testing the inverter as part of the automatic system test (see “Automatic  
System Test” on page 31).  
ALARM  
On  
The UPS is warning you that an alarm exists. If you have not silenced the alarm, the  
beep sequence identifies the problem (see “Alarms” on page 59.) If you have a control  
panel, an alarm message appears on its display.  
Off  
No alarm exists.  
Flashing Not applicable.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Using the Control Panel  
The control panel comes with all FE/QFE 4.3–18 kVA models. If you  
have an FE/QFE 500 VA–3.1 kVA, you may have ordered the control  
panel as an option (refer to TIP 407 to connect the control panel).  
The control panel is attached to the front of the UPS with a 6-ft (1.8m)  
cable, providing hand-held operation. The control panel’s READY,  
BATTERY POWER, and ALARM indicators work like the READY,  
BATTERY POWER, and ALARM indicators on the front of the UPS (see  
“Front Panel Indicators” on page 25.)  
You can use the control panel to change UPS system modes and display  
and change parameters. You can also lock the control panel and change  
some of its features. If you press the wrong key at any time, press  
[CLEAR] and then the correct key. The control panel makes a clicking  
noise each time you press a key.  
Changing Operating Modes  
There are four UPS operating modes:  
: Auto  
: Inverter On  
: Line Condition  
: Off  
The FERRUPS UPS selects the appropriate operating mode  
automatically; however, there may be times when you need to set the  
operating mode manually from the control panel. Notice that names of  
the operating modes appear in red on the bottom of keys 1–4.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Table 3. Operating Modes  
Operating Mode How to Select It What It Means  
Off  
Press [CTRL]-[1]  
[ENTER] [ENTER].  
The UPS does not provide power to your equipment, but you can still use the  
control panel if battery power is present. The READY indicator is off.  
Auto  
Press [CTRL]-[2]  
[ENTER] [ENTER].  
This is the normal operating mode. The UPS conditions AC input power and  
provides the conditioned power to your equipment. The UPS is ready to switch  
to battery power if necessary. The AC LINE and READY indicators are  
illuminated.  
Line Condition  
Press [CTRL]-[3]  
[ENTER] [ENTER].  
The UPS is conditioning AC input power and providing the conditioned power  
to your equipment, but if there is a brownout or power outage, the UPS does  
not switch to battery power. Instead, the UPS shuts down its output until AC  
input power is available again. The READY indicator is off when the UPS is in  
this mode.  
Inverter On  
(Battery Power)  
Press [CTRL]-[4]  
[ENTER] [ENTER].  
The UPS converts battery power to AC power for your equipment. It does not  
charge the batteries. The BATTERY POWER indicator is on. The UPS calculates  
the runtime remaining and sounds an alarm when runtime starts to get low.  
Entering Passwords  
Before you can change some parameter values, you must enter a  
password. You must also enter a password before you enter some of the  
commands listed on page 44.  
NOTE Some parameters, such as Time, Date, and User ID, are not  
password-protected initially. If you change parameter 39 to “Yes,” a User password is  
required to change these parameters, use [CTRL] keys, or use some commands. See  
“Parameters” on page 32 and “Entering Commands from a Terminal or Computer” on  
page 44 for more information.  
The User Password is 377. If you need a higher password, call your  
service representative. To enter the User Password, follow these steps:  
Press this key:  
[CLEAR]  
Display shows:  
)(55836  
[PROGRAM]  
[3] [7] [7]  
[ENTER]  
3DVVZRUGꢀ  
3DVVZRUGꢀ  
/HYHOꢀ  
ꢃꢈꢈ  
8VHU  
To clear the password, press [CLEAR] until 3DVVZRUG &OHDUHG  
appears on the control panel display.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Displaying and Changing Parameters  
The names of the first 11 parameters appear in green on the top of the  
number keys. To display a parameter, press [DISPLAY], the parameter  
number, and [ENTER]. For example, to display parameter 0 (time),  
follow these steps:  
Press this key:  
[DISPLAY]  
[0]  
Display shows:  
'LVSOD\ꢀ  
'LVSOD\ꢀ  
[ENTER]  
ꢁꢁ 7LPH  
ꢁꢈꢀꢁꢉꢀꢁꢊ  
To change a parameter, display it first. Then, press [PROGRAM], enter  
the new value for the parameter, and press [ENTER]. For example, to  
change parameter 0 (time), follow these steps:  
Press this key:  
[DISPLAY] [0] [ENTER]  
[PROGRAM]  
[9] [3] [0]  
Display shows:  
ꢁꢁ 7LPH ꢁꢈꢀꢁꢉꢀꢁꢊ  
ꢁꢁ 3JPꢀ  
ꢁꢁ 3JPꢀ  
ꢆꢃꢁ  
[ENTER]  
ꢁꢁ 7LPH ꢁꢆꢀꢃꢁꢀꢁꢁ  
Locking and Unlocking the Control Panel  
You may need to lock the control panel if you want to limit its use.  
When disabled the control panel does not respond to the key functions  
until it is enabled again. To disable the panel, press the keys shown in  
the following example (verify that you have the necessary code to  
unlock the control panel).  
Press this key:  
Display shows:  
[CLEAR] and [ENTER] together  
ꢋ.H\SDG /RFNHGꢋ  
When you lock the control panel, it beeps and shows the display above  
for approximately two seconds. The control panel beeps and shows this  
display whenever you try to use the keys. The front panel indicators  
continue to show the UPS status, and the control panel shows UPS  
alarms. To enable the control panel again,  
Press this key:  
Display shows:  
[CLEAR] and [ENTER] together  
[8] [2] [0] [4] [9]  
[ENTER]  
8QORFN ꢌꢀ  
8QORFN ꢌꢀ ꢊꢄꢁꢉꢆ  
.H\SDG 8QORFNHG  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
After approximately two seconds, the control panel shows the same  
display it showed before you unlocked it. If you enter the wrong unlock  
number, the control panel displays ꢋ.H\SDG /RFNHGꢋ for two  
seconds, and the control panel remains locked.  
Using the Configuration Menu  
The control panel includes a Configuration Menu that lets you adjust its  
baud rate and brightness, turn the beeper on or off, turn on and off the  
click you hear when you press keys, and control other features. The  
label on the back of your control panel includes more information on  
this menu (see Figure 8).  
5HPRWH &RQWURO 3DQHO ꢀ5&3ꢁ  
>(17(5@  
>352*5$0@  
>&/($5@  
0HQX,WHP 5DQJH  
1RWHV  
Figure 8. Remote Control Panel  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Automatic System Test  
The UPS performs an automatic system test every seven days to test the  
memory, batteries, and inverter. During the system test, the BATTERY  
POWER and READY indicators Flash. For the results of the last system  
test, you can display parameter 26 (see page 35).  
Logic Test  
First, the UPS checks its memory. If it finds a problem, the UPS sounds  
alarm O, Memory Check (– – –). See “Alarms” on page 59.  
Inverter Test  
The inverter converts DC battery power into the AC power your  
equipment uses. During the inverter test, the UPS pulses its inverter to  
see if it delivers the proper amount of current. If not, the UPS sounds  
alarm N, Check Inverter (:). See “Alarms” on page 59.  
Although it is testing the inverter, the UPS is not in Inverter On mode.  
The UPS continues to condition input power and is ready to provide  
battery power if there is a power outage. The BATTERY POWER  
indicator flashes during this part of the test.  
NOTE FE models with serial numbers 25000 and greater do not perform an individual  
inverter test.  
Battery Test  
The UPS also checks its batteries to verify that they can support your  
equipment for the minimum specified runtime. If not, the UPS sounds  
alarm M, Check Battery (– –). See “Alarms” on page 59. The READY  
indicator flashes during this part of the test.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Parameters  
Table 4 shows the first 26 parameters. You can view or reset the  
parameters using the control panel or a terminal or computer.  
If you plan to view or change parameters from the control panel, see  
“Using the Control Panel” on page 27 for instructions.  
If you plan to view or change parameters from a terminal or computer  
that you have connected to the RS-232 port, see “Entering Commands  
from a Terminal or Computer” on page 44. When you use commands to  
display or change parameters, identify the parameter with either its  
number or name (see Table 4). If you use the name, you can enter the  
entire parameter name or just the short form; you can also abbreviate  
the parameter name as long as your abbreviation includes the letters in  
the short form.  
Although you do not need a password to view any of the first  
26 parameters, all of them require a password to change (see the  
password column in Table 4.) See “Entering Passwords” on page 28 or  
“Entering Commands from a Terminal or Computer” on page 44 for  
password information.  
NOTE All changeable parameters except 0 (Time), 10 (Date), and 15 (Unit ID) are set  
at the factory. Only qualified technicians using the proper metering equipment should  
change other parameters. Improper calibration may cause the FERRUPS UPS to  
malfunction. Call your service representative before you attempt to change any  
parameters except 0, 10, and 15.  
Table 4. Parameters  
Parameter  
Number  
Sample Display  
Password  
Parameter Name Explanation  
(Short Form)  
0
00 Time 07:04:00  
None  
time  
(t)  
System Time. The UPS uses this time to  
record alarms and inverter runs. When the  
DC power has been off and you restart the  
UPS, the time shown is the last recorded  
time before shutdown. Reset time when DC  
power has been off.  
1
2
01 V In 120.7  
Service  
Service  
acvoltsin  
(vi)  
The input voltage the UPS is receiving. When  
this value drops below the brownout voltage,  
the UPS switches to inverter.  
02 V Out 120.7  
acvoltsout  
(vo)  
The voltage the UPS is providing to your  
equipment.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Parameter  
Number  
Sample Display  
Password  
Parameter Name Explanation  
(Short Form)  
3
4
03 --Reserved--  
04 I Out 3.1  
Reserved  
Service  
acampsiout  
(o)  
The current your equipment is drawing from  
the UPS.  
5
05 VA Out 374  
Change Not  
Allowed  
vaout  
(va)  
Volt-Amps Out. The total “apparent power”  
your equipment is drawing from the UPS.  
This value is based on parameter 2 multiplied  
by parameter 4, and should be less than or  
equal to the VA or kVA rating of the UPS. See  
VA Limit, parameter 19.  
6
06 I Batt 0.0  
Service  
Service  
ibatt  
(ib)  
Battery Current. When the UPS is running on  
AC input, this is the charging current inA.  
When the UPS runs on battery power  
(inverter), this is the amount of current (inA)  
the batteries are supplying to the UPS.  
7
8
07 V Batt 48.51  
08 Freq 60.43 Hz  
vbatt  
(vb)  
Battery Volts. The present battery voltage.  
The UPS sounds an alarm if this value is too  
low.  
Change Not  
Allowed  
frequency  
(f)  
In normal operation, this is the frequency of  
power the UPS is receiving from the AC input  
source. If this value falls outside preset  
limits, the UPS goes to battery power. When  
the UPS is running on battery power, this is  
the frequency the UPS is supplying to your  
equipment.  
9
09 RunTime 12m  
Change Not  
Allowed  
runtime  
(rt)  
Estimated Runtime Remaining. The amount  
of time the UPS continues to support your  
equipment when the UPS is running on  
battery power. The UPS sounds an alarm  
when this value falls below a preset limit.  
10  
10 Date 06/01/93  
11 Amb Temp 23c  
None  
date  
(d)  
System Date. The UPS uses this date to  
record alarms and inverter runs. The date  
must be reset when you restart the UPS after  
DC power is turned off.  
11 or  
[DISPLAY]  
[1] [1] [ENTER]  
Change Not  
Allowed  
ambtemp  
(at)  
The temperature (in Celsius) inside the UPS.  
The UPS sounds an alarm and shuts down if  
this value is too high.  
12  
12 SinkTemp 26c  
13 --Reserved--  
Change Not  
Allowed  
heatsinktemp  
(st)  
The temperature of the heatsink. The UPS  
sounds an alarm if this value is too high.  
13  
Reserved  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Parameter  
Number  
Sample Display  
Password  
Parameter Name Explanation  
(Short Form)  
14  
14 XfmrTemp 28c  
Change Not  
Allowed  
xfmrtemp  
(xt)  
The temperature of the transformer. The UPS  
sounds an alarm and shuts down if this value  
is too high.  
This parameter is only active on some  
models; for other models, the display always  
shows -63c.  
15  
15 Unit ID  
Network #1 UPS (See “Entering  
Passwords” on  
None  
unitident  
(id)  
UPS ID. An identification string that can be  
configured for use with your network.  
page 28.)  
16  
16 FullLoad% 075  
Change Not  
Allowed  
fullload  
(l)  
Percent of Full Load. The percentage of the  
UPS’s total capacity that is actually being  
used by your equipment.  
17  
18  
17 Watts 374  
Change Not  
Allowed  
watts  
(w)  
The total “real power” your equipment is  
drawing from the UPS.  
18 PF 0.73 Dist  
Change Not  
Allowed  
powerfact  
(pf)  
The power factor of your equipment; the  
difference in the way it draws voltage and  
current. Power factor is equal to Watts Out  
(parameter 17) divided by VA Out  
(parameter 5). This parameter also tells  
whether the power factor is leading (Lead),  
lagging (Lag), or distortion (Dist).  
19  
19 VALimit 500  
Change Not  
Allowed  
valimit  
(val)  
The maximum volt-amps the UPS can supply  
to your equipment at the present power  
factor. The UPS sounds an alarm when VA  
Out (parameter 5) is higher than this value.  
20  
21  
20 #PwrOut 1  
21 #OvrLds 0  
Change Not  
Allowed  
powerout  
(po)  
The number of times there has been a loss of  
input power since you started the UPS.  
Change Not  
Allowed  
overloads  
(ol)  
The number of times the UPS has sensed an  
overload; that is, the number of times VA Out  
has been greater than VA Limit.  
22  
23  
22 SysHrs 00000  
23 InvMin 0000.0  
Change Not  
Allowed  
syshours  
(sh)  
The total number of hours the UPS has been  
operating, regardless of mode. This number  
does not increase when the UPS ON/OFF  
switch is in the OFF position.  
Change Not  
Allowed  
invmin  
(im)  
The total number of minutes the inverter has  
run since startup.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Parameter  
Number  
Sample Display  
Password  
Parameter Name Explanation  
(Short Form)  
24  
24 Inverter Log  
L 0319 2127 1215  
Change Not  
Allowed  
inverterlog  
(il)  
A record of the date, time, duration and  
reason for the last 20 inverter (battery power)  
runs (see “Alarm and Inverter Logs” on  
page 62).  
25  
26  
25 Alarm Log  
Change Not  
Allowed  
alarmlog  
(al)  
A record of the date, time, duration and  
reason for the last 20 alarms (see “Alarm and  
Inverter Logs” on page 62).  
A 0319 2127 1215  
26 Test Results  
(See explanation.)  
Change Not  
Allowed  
testresults  
(tr)  
This parameter records the results of the last  
system test. The parameter display includes  
the time and date of the test and the results  
of each part of the system test (see  
“Automatic System Test” on page 31.)  
The microprocessor in the UPS keeps track of more than 100 parameters. Parameters 27 and  
above are alarm and operation set points, calibration factors and other settings. You usually do not need access to these  
parameters for normal operation of the UPS. If you need information about the full range of UPS parameters, call your  
service representative to ask for TIP 407 or TIP 503. TIP 407 describes communication from a control panel. TIP 503  
describes communication through the RS-232 port.  
UPS Shutdown  
The FERRUPS UPS is designed for many years of round-the-clock  
operation. Usually, you do not need to shut down the UPS, even if your  
equipment is shut down for several days. Even when it’s not powering  
your equipment, the UPS monitors its internal condition and keeps the  
Time and Date parameters current.  
There are times, though, when you want to shut down the UPS, such as:  
1. When you do not expect to use it for an extended period of  
time.  
2. When it is being serviced.  
3. Before you move it.  
4. When it has gone into the Off mode because the batteries have  
been discharged during an extended outage.  
5. When a system malfunction requires a UPS shutdown.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
CAUTION  
When AC input voltage is present, the UPS system can provide output voltage even  
though its batteries are disconnected. To confirm that there is no UPS output voltage,  
always disconnect the AC input source; if the UPS has one or more separate battery  
cabinets, open the DC disconnect switch on each battery cabinet or disconnect the  
battery cabinet from the UPS.  
1. UPSs with no bypass switch: Turn off the protected equipment.  
Continue to Step 2.  
If you need to use the equipment while the UPS is off, plug the  
equipment into standard wall outlets and restart the equipment.  
UPSs with a Break-Before-Make (BBM) bypass switch (see the label  
on the side of the switch): Shut down the protected equipment.  
Turn the bypass switch to the LINE position. Continue to  
Step 2.  
If you need to use the equipment while the UPS is off, restart  
the equipment. The equipment receives direct AC line instead  
of conditioned power from the UPS.  
UPSs with a Make-Before-Break (MBB) bypass switch (see the label  
on the side of the switch): Verify that the AC LINE indicator is  
on, the BATTERY POWER indicator is off, and the UPS is  
providing output. If all three of these conditions are present,  
turn the bypass switch to the LINE position. Your equipment  
receives direct AC line instead of conditioned power from the  
UPS. Continue to Step 2.  
If all three of these conditions are not present, follow Steps 2–4  
before you turn the bypass switch to the LINE position. This  
causes a break in power to your equipment between shutting  
down the UPS and turning the bypass switch to the LINE  
position.  
CAUTION  
Equipment can be damaged if you change the switch position when line is applied and  
the UPS is off or on battery! Refer to TIP 410.  
2. Turn the UPS ON/OFF switch to the OFF position.  
3. If the UPS is plugged in, unplug it. For hardwired models, turn  
the AC line disconnect switch to the OFF position.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
4. 500 VA–3.1 kVA: If you have a battery cabinet that has a DC  
switch on the front, turn the switch to the OFF position. If your  
battery cabinet does not have a DC switch on the front, unplug  
the connector between the battery cabinet(s) and the UPS; be  
sure to reconnect this connector before you start the UPS again.  
4.3–18 kVA: Unlock the lock in the center of the front panel and  
remove the panel. If there is a DC switch behind the panel, turn  
it to the OFF position. Reattach the panel to the UPS. If your  
UPS has separate battery cabinets, turn the DC switch at each  
battery cabinet to the OFF position.  
5. If the UPS is turned off for an extended period of time, recharge the  
batteries every 90–120 days to prevent battery damage. To  
restart the UPS, see “Startup” on page 17.  
Extended Power Outages  
If the power is out for an extended time, the UPS continues to provide  
power for your equipment until it gets near the end of its runtime. You  
can check the remaining battery runtime by reading parameter 9 (see  
page 33.) At a preset number of minutes before the end of the runtime  
(factory-default setting is five minutes), the UPS sounds a Low Runtime  
alarm (– : :). Shut down your equipment and turn off the UPS to  
conserve the remaining battery power (see “UPS Shutdown” on  
page 35). When AC input power returns, turn on the UPS to recharge  
the batteries.  
If your UPS shuts itself down because its battery voltage is too low, shut  
down the UPS until the AC input power returns (see “UPS Shutdown”  
on page 35).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 5  
COMMUNICATION  
The FERRUPS UPS is capable of full-duplex communication and can  
communicate with a computer, a Local Area Network (LAN), or a  
multi-user computer system. If your system comes with UPS monitoring  
and automatic shutdown software, the FERRUPS UPS can communicate  
with that software. If your system does not have software, you can use  
the CheckUPS II Power Management Software included on the  
Powerware Software Suite CD-ROM.  
If you do not plan to use CheckUPS II software or other UPS monitoring  
software, you can still set up RS-232 communication with the UPS and  
use commands and parameters to control UPS operation.  
Powerware Software Suite  
Each UPS ships with the Powerware Software Suite CD-ROM and a  
communication cable. To begin installing CheckUPS II software, refer  
to the instructions accompanying the Powerware Software Suite  
CD-ROM.  
CheckUPS II software uses an RS-232 serial link to communicate with  
the UPS, and (using Microsoft Windows ) it provides you with  
up-to-date graphics of UPS power and system data and power flow. It  
also gives you a complete record of critical power events and notifies  
you of important UPS or power information. If there is a power outage  
and the UPS system battery power becomes low, CheckUPS II software  
can automatically shut down your computer system to protect your data  
before the UPS Low Battery shutdown occurs.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Communication Port  
The communication port cable pins are identified in Figure 9 and the  
pin functions are described in Table 5.  
Figure 9. Communication Port  
Table 5. Communication Port Pin Functions  
Pin  
Function  
Function  
2
Transmit Data (in)  
Receive Data (out)  
Request to Send  
Clear to Send  
3
4
To enable hardware handshaking on these pins, call your service  
representative.  
5
6
+12V Level (0.01A) when the UPS is operating  
Signal Ground  
7
11  
Contact opens when on  
inverter  
These relay contacts are rated at 25 Vac/Vdc and 250 mA (see “Remote  
Monitoring” on page 47).  
FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have  
equivalently rated DC solid state switches.  
12  
13  
Contact closes when on  
inverter  
Common Inverter Signal  
Contact  
14  
18  
20  
21  
23  
+12V, 0.5A (500 VA–3.1 kVA) or 0.3A (4.3–18 kVA) Do not use for setting logic levels.  
+12V Level (0.01A) when UPS is operating  
AS/400 Option  
Remote Shutdown  
Contact closes on alarm  
Common Alarm Signal Contact  
Contact opens on alarm  
These relay contacts are rated at 25 Vac/Vdc and 250 mA (see “Remote  
Monitoring” on page 47).  
Pins 23 and 25 change status when the UPS is turned off.  
FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have  
equivalently rated DC solid state switches.  
24  
25  
Pins 2–5 and 7 are for RS-232 communication, Pins 11–13 and 23–25 are for remote monitoring, and Pin 21 (used  
with 6 or 18) is for remote shutdown. The following sections describe how to take advantage of these features. Pin 20 is  
for option use only.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Connecting a Terminal or Computer to the RS-232 Port  
CAUTION  
Do not make connections to the RS-232 communication port if the UPS is connected to  
a positive ground battery system. The RS-232 ground must be isolated or equipment  
damage will result. For help, contact your service representative.  
If you are connecting a terminal to the RS-232 port, the terminal must  
be capable of serial communication.  
If you are connecting a computer, the computer must be running  
terminal emulation software (such as HyperTerminal ). Most modem  
software packages can emulate a terminal; if you do not have a terminal  
emulation program, please contact your service representative for more  
information.  
1. To connect the FERRUPS UPS DB-25S (female) RS-232 port to  
your terminal or computer, you need a cable designed  
specifically for this purpose. (See Figure 10 and Figure 11.)  
Powerware offers cables for computers or terminals using  
25-pin or 9-pin serial ports; call your service representative to  
order one of these cables. If you would like to build your own  
cable, follow these requirements:  
: Use a high-quality, shielded cable.  
: Do not use a standard 25-conductor straight-through cable;  
only include straight-through connections for the pins  
shown in Figure 10 and Figure 11.  
For RS-232 communication, use Pins 2 (transmit data), 3  
(receive data), and 7 (signal ground). For hardware  
handshaking (request to send on Pin 4 and clear to send on Pin  
5), contact your service representative. No other pins should be  
connected from the UPS RS-232 port to your terminal or  
computer.  
For more information on pin connections and the function of  
the non-serial pins on the RS-232 port, see Table 5 on page 40  
and “Remote Monitoring” and “Remote Shutdown” on page 47.  
NOTE To connect a modem, see TIP 503.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Figure 10. DB-9 to UPS Pinout  
Figure 11. DB-25 to UPS Pinout  
2. Connect the cable from the RS-232 port on the back of the UPS  
to the serial port on your terminal or computer.  
3. Your terminal or computer should be set to: 1200 baud, 8 bits,  
No parity, 1 stop bit, and full duplex.  
The terminal or terminal emulation software should also be set  
to full duplex. If you are using a terminal, note that the  
FERRUPS UPS supports the Televideo 900 series, ADM3A and  
WYSE 50 emulation.  
Table 6 shows the standard settings at the UPS DB-25S port and  
the settings that can be adjusted. Call your service  
representative if you need to adjust any of the settings.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Table 6. DB-25 Port Settings  
Specification  
Connector  
Format  
Standard Setting  
Adjustable to  
25 pin D (female) wired as DCE.  
ASCII, 8 bits, 1 stop bit.  
Most significant bit set to 0.  
Standard setting or  
7/8 bits, 1/2 stop  
Baud Rate  
Parity  
1200  
None  
Full  
50–38400  
Odd, Even, or None  
Full or Half  
Duplex  
4. Turn your terminal on or run your terminal emulation  
software. Then press [ENTER] on your keyboard; a prompt  
appears on the screen. The prompt varies depending on your  
current password level:  
=>  
Normal prompt  
User=> User Password has been entered  
5. Press [ENTER] on your keyboard a few times to verify that the  
UPS responds.  
6. To control or monitor the UPS, simply type the desired  
command and press [ENTER].  
Table 7 shows what keystrokes to use as you type commands or  
view displays. See Table 8 for more information on UPS  
commands.  
Table 7. Keystroke Commands  
Action  
Key Sequence  
[BACKSPACE] or [CTRL]-[H]  
[CTRL]-[X]  
Delete last character typed.  
Delete line.  
Pause displays that take more than one screen.  
Resume scrolling. (Turn Pause off.)  
[CTRL]-[S]  
[CTRL]-[Q]  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Entering Commands from a Terminal or Computer  
To monitor or control the FERRUPS UPS from a terminal or computer,  
simply type in one of the commands and press [ENTER] (see Table 8).  
Use the following command syntax:  
: type the command in uppercase or lowercase  
: use the entire command or the short form (you can also abbreviate  
the command as long as you include the letters in the short form  
: use a semicolon to separate more than one command on a line  
Table 8. Commands  
Command  
Short  
Form  
Password Function  
alarmshelp  
ah  
None  
Shows a list of all possible alarm messages, the audio code and letter for  
each alarm and whether the alarm is active.  
alarmlog  
al  
None  
Displays Alarm Log. See “Alarm and Inverter Logs” on page 62.  
alarmtest  
at  
None  
Allows you to test the alarm function.  
alarm (J). See page 61.  
sounds the User Test  
alarmtest cancel  
chargermode  
at c  
None  
Turns the User Test alarm off.  
chm  
None*  
Shows the UPS battery charger mode. By entering a mode after the  
command, you can change the charger mode:  
: chargermode off (chm f) or chargermode disable (chm d) = charger off  
: chargermode on (chm o) or chargermode enable (chm e) = charger on  
: chargermode auto (chm a) = charger enabled if AC input voltage and  
battery voltage are acceptable  
clearalarms  
clearhistory  
ca  
ch  
None  
None  
Clears all active alarms.  
Clears the minimum and maximum parameter values shown when you  
use the  
Clears the current password.  
Displays a list of all valid commands.  
or  
commands.  
clearpassword  
commands  
cp  
cm  
cd  
None  
None  
contdisplay  
Depends Continuously displays the parameter that you are currently displaying.  
on  
You can specify other parameters for the continuous display by entering  
parameter  
password  
the name or number of each parameter after the  
command.  
contstatus  
cs  
None  
Continuously displays the Status information (see the  
command.)  
*If you change parameter 39 to “Yes,” this command requires a User password.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Command  
date  
Short  
Form  
Password Function  
da  
None*  
None  
Displays system time and date. To set the date, enter  
.
delay  
dl  
Delays next command when you enter a number after  
. Each unit  
would cause a 2.5 millisecond  
represents 2.5 milliseconds, so  
delay. For a 1-second delay, enter  
.
display  
d
Depends Displays the values of one or more parameters (see Table 4 on page 32).  
on  
Format: display [parameter # or name] [parameter # or name]  
parameter  
password  
Example:  
displays the values of parameters 1, 16 and 21  
extendedhistory  
format  
xh  
f
None  
None  
Displays the minimum and maximum values of parameters 1 (Vac In),  
2 (Vac Out), 7 (Vdc) and 5 (VA Out); the command then clears the  
minimum and maximum values (see Table 4 on page 32).  
Displays an 80-character line containing information on the FERRUPS’  
status. CheckUPS II and other UPS monitoring software use this data.  
help  
? or he  
h
None  
None  
Shows a list of terminal/computer commands.  
history  
Displays the minimum and maximum values of parameter 1 (Vac In); the  
command then clears the minimum and maximum values.  
identify  
I
None  
Shows Powerware’s address and telephone number and the software  
version.  
inverterlog  
logs  
il  
l
None  
None  
Displays the Inverter Log. See “Alarm and Inverter Logs” on page 62.  
Displays both the Alarm and Inverter Logs. See “Alarm and Inverter Logs”  
on page 62.  
off [time]  
o [time]  
None*  
Shuts down the UPS a given number of seconds. The READY indicator  
flashes until the UPS shuts down, and the UPS beeps five seconds before  
shutdown. Example:  
shuts down the UPS in 60 seconds.  
off [time] autostart  
o [time]  
a
None*  
None*  
Shuts down the UPS in a given number of seconds (see above), and  
restarts the UPS shortly after power returns.  
off cancel  
o c  
p
Cancels timed shutdown.  
parameters  
Depends Shows a list of system parameters. See “Parameters” on page 32. You  
on  
can also display a range of parameters by entering the starting and  
ending parameter number or name after the command.  
parameter  
password  
Example:  
displays parameters 1 through 10.  
*If you change parameter 39 to “Yes,” this command requires a User password.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Command  
Short  
Form  
Password Function  
paramkeywords  
pk  
Depends Displays all parameters and their keywords (the names you can use with  
on  
commands). You can also display a range of parameters by entering the  
numbers or names of the starting and ending parameters.  
parameter  
password  
password  
program  
pw  
pr  
None  
Allows you to enter the User Password. Typing  
the current password.  
alone clears  
Example:  
enters the User Password.  
Depends Lets you set the value of any parameter. You must enter the appropriate  
on  
password before you reset the value. See the Password command above.  
Format: PR [parameter # or name] [newvalue]  
parameter  
password  
Example:  
resets the time (parameter 0) to 8:15 a.m.  
remote  
rm  
None  
Configures the RS-232 port so the connected terminal works like a  
control panel.  
shutdown  
or  
shutdown autostart  
sd  
None*  
Shuts down the UPS output in 60 seconds (if you enter shutdown alone)  
or the number of seconds you specify after the command. The READY  
indicator flashes until the UPS shuts down. If you specify autostart, the  
UPS restarts shortly after power returns.  
sd a  
shutdown cancel  
shutup  
sd c  
sh  
s
None*  
None  
None  
Cancels a shutdown started with the shutdown command.  
Turns off audible alarm.  
status  
Shows date, time, system status, present system mode, active alarms,  
and the value of various system parameters.  
systemmode _  
sm  
None*  
None*  
Typing  
You can use  
below.  
alone displays which system mode is now active.  
with , , , or to enter one of the modes  
systemmode auto  
sm a  
Enters the Auto mode. This is the normal FERRUPS UPS mode. In this  
mode, the UPS provides conditioned AC power to your equipment; if  
there is a power outage, the UPS is ready to switch to battery power.  
systemmode off  
sm f  
sm I  
sm l  
None*  
None*  
None*  
Enters the Off mode. In this mode, the UPS is not providing power to your  
equipment, but you can still use the UPS control panel.  
systemmode inverter  
Enters the Inverter On mode. In this mode, the UPS is converting DC  
battery power to AC power for your equipment.  
systemmode  
linecondition  
Enters the Line Condition mode. In this mode, the UPS provides  
conditioned AC power to your equipment, but it does not switch to  
battery power if there is a power outage. Instead, the UPS sounds a Low  
AC Out alarm.  
*If you change parameter 39 to “Yes,” this command requires a User password.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Command  
Short  
Form  
Password Function  
systemtest  
time  
stst  
t
None*  
None  
Starts a system test of the logic, inverter and battery.  
Shows the current UPS time. To set the time, enter  
the command.  
after  
unshutup  
u
None  
Turns audible alarm back on.  
*If you change parameter 39 to “Yes,” this command requires a User password.  
Remote Monitoring  
Alarm Signal Contacts: These are relay contacts (rated at 25 Vac/Vdc and  
250 mA) that change status on any alarm condition or when the UPS is  
turned off. Contacts that close on an alarm are available between Pins 23  
and 24. Contacts that open on an alarm are available between Pins 24  
and 25.  
Inverter On Signal Contacts: These are relay contacts (rated at 25 Vac/Vdc  
and 250 mA) that change status when the inverter turns on. Contacts  
that close on inverter operation are available between Pins 12 and 13.  
Contacts that open on inverter operation are available between Pins 11  
and 13.  
NOTE FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have  
equivalently rated DC solid state switches.  
Remote Shutdown  
The FERRUPS UPS can be connected to a remote shutdown switch to  
shut off output from the UPS to your protected equipment. The  
shutdown switch must have a set of contacts that can apply the UPS’s  
+12 Vdc on Pin 6 to the UPS’s Pin 21. (You can use Pin 18 instead of  
Pin 6; do not use Pin 14.) Use a shielded, single twisted-pair cable to  
connect the switch to the UPS pins. A connection between Pins 6 and 21  
(or 18 and 21) shuts down UPS output power to the protected  
equipment.  
When the UPS Remote Shutdown feature has been activated, the UPS is  
in the Off mode and the Emergency Power Off alarm sounds. A control  
panel or a terminal connected to the UPS displays “Emergency PwrOff.”  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
To restart the UPS, break the connection between Pins 6 and 21 (or  
between Pins 18 and 21) at the UPS’s RS-232 port. Then, follow the  
steps in “Startup” on page 17 for your model. Note that the 12V level on  
Pin 6 or Pin 18 is only available when the UPS is operating.  
You can change the type of signal that the UPS responds to and how  
quickly it responds. You can also set up the UPS to restart automatically  
when the shutdown signal stops. See TIP 503 or contact your service  
representative for more information.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 6  
OPTIONS  
Powerware offers many options for your FERRUPS UPS. If you would  
like more information, contact your local Powerware office or  
distributor.  
Bypass Switches  
If your UPS does not have a plug, a bypass switch lets you transfer your  
protected equipment to direct AC input power conveniently when it’s  
time to service the UPS. Contact your local Powerware office or  
distributor for recommendations and additional information on the  
different bypass switches.  
Control Panel  
Control panels and extension cables are available that provide UPS  
monitoring and operation from a remote location.  
Environmental Monitoring  
Powerware’s EnviroComZ monitors office and UPS conditions and  
phones you when there is a problem. EnviroCom II also lets you:  
: call the UPS for an update on its status and environment  
: control and communicate with the UPS through a modem  
Extended Runtimes  
If you want extended runtimes, call your local Powerware office or  
distributor for information on adding additional battery capacity or an  
optional battery charger.  
Warranties  
Besides our standard two-year warranty, Powerware offers several  
warranty enhancement plans to meet your service and maintenance  
needs. Contact your local Powerware office or distributor for more  
information.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 7  
MAINTENANCE  
NOTE Technicians must observe important safety precautions while performing these  
checks.  
The FERRUPS UPS is designed to provide years of trouble-free  
operation. Its internal control system checks the batteries and inverter  
periodically to ensure reliable operation. In fact, you’ll probably find  
that your FERRUPS system requires less maintenance than any of your  
other computer peripherals.  
Nevertheless, the FERRUPS UPS and optional external battery cabinets  
do require some attention to assure continued reliable service.  
Powerware recommends that you schedule preventive maintenance  
checks at least every six months. At these checks, the service technician  
should follow Powerware’s recommended maintenance schedule, which  
includes the following items:  
: Check operating environment for clean, cool, dry conditions.  
: Inspect and clean the unit.  
: View and record the alarm and inverter logs.  
: Check the batteries.  
: Check the AC and DC meter functions and recalibrate if necessary.  
: Perform an outage test.  
: Check and record the values of the first 19 parameters while the UPS  
is online and on battery.  
For more information on preventive maintenance checks, contact your  
service representative.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 8  
SPECIFICATIONS  
Table 9. FE and QFE 500 VA–3.1 kVA  
Model  
500 VA/  
350W  
700 VA/  
500W  
850 VA/ 1.15 kVA/ 1.4 kVA/  
600W 800W 1 kW  
1.8 kVA/  
1.25 kW  
2.1 kVA/  
1.5 kW  
3.1 kVA/  
2.2 kW  
AC Input Voltage and Current, Standard Charger  
FE: 120 Vac  
208 Vac  
220 Vac  
240 Vac  
QFE: 120 Vac  
220 Vac  
4.6A  
2.4A  
2.3A  
2.1A  
4.4A  
2.6A  
2.5A  
2.4A  
5.6A  
2.8A  
2.7A  
2.5A  
5.8A  
3.9A  
3.8A  
3.5A  
6.6A  
3.7A  
2.5A  
3.2A  
7.0A  
4.4A  
4.2A  
4.0A  
8.9A  
5.0A  
4.6A  
4.2A  
8.4A  
4.9A  
4.6A  
4.4A  
11A  
6.0A  
5.8A  
5.3A  
11A  
5.7A  
5.4A  
5.2A  
16A  
9.2A  
7.8A  
8.2A  
15A  
7.9A  
7.5A  
7.2A  
19A  
11A  
9.4A  
9.2A  
16A  
8.2A  
7.8A  
7.4A  
25A  
14A  
12A  
12A  
24A  
13A  
12A  
12A  
1
1
230 Vac  
240 Vac  
Recommended  
AC Input Service:  
60 Hz with  
10A  
10A  
10A  
15A  
15A  
20A  
20A  
30A  
1
120 Vac  
2
Output Voltage and Maximum Output Current  
FE: 120 Vac  
208 Vac  
220 Vac  
240 Vac  
QFE: 120 Vac  
220 Vac  
4.1A  
2.3A  
2.1A  
4.1A  
2.2A  
2.2A  
2.1A  
5.9A  
3.3A  
2.8A  
5.7A  
3.2A  
3.1A  
2.9A  
7.0A  
4.0A  
3.4A  
7.1A  
3.8A  
3.6A  
3.5A  
9.3A  
5.3A  
5.0A  
4.7A  
9.4A  
5.0A  
4.8A  
4.6A  
12A  
6.5A  
6.1A  
5.6A  
12A  
6.4A  
6.2A  
5.9A  
15A  
8.4A  
8.0A  
7.3A  
14A  
7.9A  
7.6A  
7.2A  
17A  
9.9A  
9.0A  
8.6A  
17A  
9.3A  
8.9A  
8.5A  
26A  
15A  
14A  
13A  
25A  
14A  
13A  
13A  
230 Vac  
240 Vac  
Efficiency on AC  
Line  
85%  
86%  
85%  
88%  
88%  
90%  
90%  
91%  
On Line  
BTU/hour:  
kW/hour:  
210  
.062  
277  
.081  
361  
.106  
372  
.109  
465  
.136  
474  
.139  
568  
.166  
742  
.217  
Audible Noise  
(dB)  
41  
41  
47  
49  
49  
51  
51  
51  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Model  
500 VA/  
350W  
700 VA/  
500W  
850 VA/ 1.15 kVA/ 1.4 kVA/  
1.8 kVA/ 2.1 kVA/  
3.1 kVA/  
2.2 kW  
600W  
800W  
1 kW  
1.25 kW  
1.5 kW  
Runtime (minutes)  
QFE Full Load:  
Half Load:  
9
25  
9
14  
35  
11  
11  
28  
9
18  
48  
8
14  
37  
11  
11  
30  
11  
9
25  
9
14  
35  
14  
FE  
Full Load:  
Weight :  
Without Battery:  
60 Hz Models:  
50 Hz Models:  
With Battery:  
60 Hz Models:  
50 Hz Models:  
44 lb  
22.2 kg  
46 lb  
25 kg  
51 lb  
27.7 kg  
92 lb  
41.7 kg  
106 lb  
45.4 kg  
120 lb  
58.1 kg  
132 kg  
63.5 kg  
144 lb  
69 kg  
54 lb  
28 kg  
62 lb  
36.3 kg  
67 lb  
39 kg  
102 lb  
59.9 kg  
122 lb  
69.9 kg  
176 lb  
83 kg  
188 lb  
89 kg  
248 lb  
116.1 kg  
Dimensions  
(H x W x D)  
12x 10x 21.25”  
30.5 x 25.5 x 54.0 cm  
15.1x 15.2x 20.2”  
38.5 x 39.0 x 51.5 cm  
21.2x 15.25x 22.9”  
54.0 x 39.0 x 58.5 cm  
1
Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown  
are for the U.S. and Canada.  
At 0.7 leading power factor.  
2
Table 10. FE and QFE 4.3–18 kVA  
Model  
4.3 kVA/  
3 kW  
5.3 kVA/  
3.7 kW  
7 kVA/  
5 kW  
10 kVA/  
7.5 kW  
12.5 kVA/  
10 kW  
18 kVA/  
15 kW  
AC Input Voltage and Current, Standard Charger  
1
1
1
FE: 120 Vac  
208 Vac  
220 Vac  
240 Vac  
QFE: 220 Vac  
230 Vac  
32A  
38A  
22A  
21A  
19A  
21A  
20A  
19A  
51A  
30A  
27A  
26A  
27A  
26A  
24A  
18A  
17A  
16A  
19A  
18A  
17A  
45A  
41A  
39A  
43A  
41A  
39A  
58A  
53A  
50A  
55A  
53A  
51A  
86A  
81A  
76A  
81A  
78A  
75A  
240 Vac  
1
1
1
Recommended Input  
Service for 60 Hz  
Models  
120 = 40A  
120 = 50A  
120 = 65A  
208 = 25A  
240 = 20A  
208 = 30A  
240 = 25A  
208 = 40A  
240 = 35A  
208 = 60A  
240 = 50A  
208 = 75A  
240 = 65A  
208 = 115A  
240 = 100A  
2
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Model  
4.3 kVA/  
3 kW  
5.3 kVA/  
3.7 kW  
7 kVA/  
5 kW  
10 kVA/  
7.5 kW  
12.5 kVA/  
10 kW  
18 kVA/  
15 kW  
3
Output Voltage and Maximum Output Current  
FE: 120 Vac  
208 Vac  
220 Vac  
240 Vac  
QFE: 220 Vac  
230 Vac  
34A  
20A  
19A  
17A  
19A  
18A  
17A  
44A  
26A  
24A  
22A  
23A  
22A  
21A  
58A  
34A  
31A  
29A  
31A  
30A  
28A  
82A  
48A  
46A  
41A  
45A  
43A  
41A  
103A  
58A  
55A  
51A  
56A  
52A  
51A  
149A  
84A  
82A  
73A  
84A  
76A  
73A  
240 Vac  
Efficiency On AC  
Line  
90%  
90%  
90%  
90%  
91%  
92%  
On Line BTU/hour:  
kW/hour:  
1138  
.333  
1403  
.411  
1896  
.556  
2844  
.833  
3375  
.989  
4452  
1.3  
Audible Noise (dB)  
50  
51  
54  
55  
56  
57  
Runtime (minutes)  
Full Load:  
Half Load:  
8
20  
20  
50  
12  
33  
11  
26  
18  
48  
10  
26  
Weight :  
Without Battery:  
60 Hz Models:  
50 Hz Models:  
With Battery:  
60 Hz Models:  
50 Hz Models:  
243 lb  
115.7 kg  
268 lb  
131.1 kg  
362 lb  
176.5 kg  
442 lb  
217.7 kg  
505 lb  
251.3 kg  
625 lb  
312.1 kg  
348 lb  
163.3 kg  
484 lb  
229.1 kg  
578 lb  
274.4 kg  
395 lb  
(179.2 kg)  
535 lb  
(242.7 kg)  
675 lb  
(306.2 kg)  
N Cabinet with  
Standard Batteries  
Dimensions  
(H x W x D)  
29.5” x 15.5” x 25”  
75.0 x 39.5 x 63.5 cm  
36.5” x 19” x 32”  
93.0 x 48.5 x 81.5 cm  
5
1
FE 4.3 kVA,5.3 kVA, and 7 kVA models have optional 120 Vac input voltage.  
Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown  
2
are for the U.S. and Canada.  
3
At 0.7 to 0.83 leading power factor.  
FE and QFE 10 kVA, 12.5 kVA, and 18 kVA models do not have internal batteries. Batteries are in a separate battery  
4
cabinet or rack.  
5
If your model has an internal bypass switch, add 8” (20.0 cm) to the depth.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table 11. Electrical Input and Output  
Nominal Frequency  
Online: 60 Hz (FE) or 50 Hz (QFE) with nominal power line grid stability of 0.005 Hz.  
On inverter: 60 Hz (FE) or 50 Hz (QFE) 0.03 Hz. Output frequency tracks input line frequency  
up to limit, which is adjustable from 0.01 Hz to 3.00 Hz. Inverter turns on if line frequency  
exceeds the selected limit.  
Regulation  
3% load regulation (under any line, load, or battery condition to within -8.3% and +5% of  
nominal)  
Voltage Waveform  
Overload Capability  
Sine wave; <5% THD at rated linear loads, computer-grade power  
On line (nominal Vac in): 150% surge and 125% for 10 minutes.  
On inverter (nominal Vdc in): 150% surge and 110% for 10 minutes.  
Overload operation is not thermally limited. The FERRUPS UPS microprocessor continuously  
monitors output VA and sounds an alarm before loss of output voltage regulation occurs.  
DC Input Protection  
Output Protection  
DC fuse and battery charger fuse  
Output Protection: The ferroresonant transformer inherently limits current and provides  
overload protection. The FERRUPS UPS has high AC and low AC output voltage alarms, as  
well as an overload alarm. If the AC output voltage falls below the low AC output voltage  
alarm setpoint, the UPS sounds an alarm after five seconds. If the AC output voltage falls  
below the low AC output shutdown setpoint, the UPS sounds an alarm and shuts down.  
Some models have output receptacles protected by fuses or circuit breakers.  
Lightning and Surge  
Protection  
The FERRUPS UPS provides 2000-to-1 spike attenuation. Tested using lightning standard  
per ANSI/IEEE C62.41 Category A (6000V spike and 200A) and Category B (6000V spike  
and 3000A) test, and ANSI/IEEE C62.45 test procedures.  
Isolation, Including  
The FERRUPS UPS provides a true separately derived power source, as defined by National  
Output Neutral to Ground Electrical Code Article 250-5d, with output neutral bonded to ground. There is no direct  
Bonding  
connection between input and output, and less than 2 pF of effective input to output  
capacitance.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table 12. Environmental and Safety  
Operating Temperature  
Storage Temperature  
0°C to 40°C (32°F to 104°F)  
UPS with batteries: -20° to +40°C (-4° to 104°F)  
UPS without batteries: -20° to +60°C (-4° to 140°F)  
Relative Humidity  
Operating Altitude  
0–95% noncondensing  
Up to 3,050 meters above sea level (10,000 ft)  
The maximum operating ambient temperature decreases 1°C per 300m above 1525m  
(2°F per 1000 ft above 5000 ft)  
Ventilation  
The air around the UPS must be clean and free of dust, corrosive chemicals, and other  
contaminants. The FERRUPS UPS uses internal fans to circulate the air for cooling. The air  
must be free to circulate around the UPS and battery cabinet(s). Do not operate the UPS in  
a sealed room or container.  
Noise Rejection  
Common Mode: Greater than 120 dB with output neutral bonded to ground  
Transverse (Normal) Mode: Greater than 60 dB  
Table 13. Battery  
Voltage  
500–850 VA models: Nominal battery voltage is 24 Vdc for 60 Hz, 12 Vdc for 50 Hz.  
Standard battery charger output is rated at 2A.  
1.15–1.4 kVA models: Nominal battery voltage is 48 Vdc Vdc for 60 Hz, 12 Vdc for 50 Hz.  
Standard battery charger output is rated at 2A.  
1.8–3.1 kVA models: Nominal battery voltage is 48 Vdc. Standard battery charger output is  
rated at 4A.  
4.3–7 kVA models: Nominal battery voltage is 48 Vdc. Standard battery charger output is  
rated at 5A.  
10–18 kVA models: Nominal battery voltage is 120 Vdc. Standard battery charger output is  
rated at 5A.  
Type  
Standard batteries are sealed, gas recombinant, lead-acid type, especially designed for  
UPS use.  
Optional battery chargers at higher current ratings are available. Call your local Powerware office or distributor for  
more information.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 9  
TROUBLESHOOTING  
When your FERRUPS UPS detects an alarm condition, the UPS displays  
the alarm with the following indications:  
: the ALARM indicator on the front panel (and the control panel if you  
have one) illuminates  
: sounds an audible alarm  
: displays an alarm message on the control panel (if you have one).  
NOTE If the control panel does not display the message, press [CLEAR] until you  
reach the scrolling display.  
Alarms  
When an alarm occurs, follow these steps:  
1. Find out which alarm condition the UPS is detecting.  
: If you have a control panel, you can read the alarm on the  
display.  
: If you do not have a control panel, listen to the alarm code;  
the UPS sounds the Morse Code for the alarm letter.  
2. Find the alarm in Table 14 and follow the instructions to  
resolve the problem.  
3. To silence the alarm:  
FE/QFE 500 VA–3.1 kVA models: Turn the Alarm Silence Switch on  
the UPS rear panel to the OFF position.  
FE/QFE 4.3–18 kVA models: Press [CTRL]-[5] [ENTER] [ENTER]  
on the control panel.  
4. After the alarm condition is cleared, turn the alarm beep back  
on (using either the switch or the control panel).  
NOTE If you do not turn the alarm beep back on, the UPS is not able to sound an  
alarm code the next time there is an alarm.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Table 14. Alarms  
Letter Audio  
Code  
Alarm  
Message  
What It Means  
What To Do  
A
: –  
Low  
Battery  
The UPS has shut down after running on  
battery and discharging the batteries.  
Wait for AC input power to be restored.  
When AC input power returns, turn on the  
UPS. The CHARGING indicator illuminates  
as the UPS begins recharging batteries.  
B
C
D
E
: : : Near Low The battery voltage has reached the Near  
The alarm should clear itself when the  
battery charger has charged the batteries  
enough.  
Battery  
Low Battery setpoint.  
: :  
: :  
:
High  
The battery voltage is too high because of Contact your service representative.  
a problem with the charging circuit or  
parameter settings.  
Battery  
Low  
Runtime  
The UPS is running on battery power, and  
the battery runtime remaining is low.  
Shut down your equipment and turn off the  
UPS to conserve battery power. When AC  
input power returns, turn the UPS on again.  
Low AC  
Output  
The output voltage is below a  
preprogrammed setpoint.  
The UPS shuts down. Shut down your  
equipment or bypass the UPS, and turn the  
UPS switch off. Contact your service  
representative.  
F
: : :  
High AC The output voltage is higher than the alarm Contact your service representative.  
Output  
setting.  
G
– – :  
Output  
Overload  
Power requirements exceed UPS capacity  
(check the UPS VA rating) or the load is  
defective.  
Turn off and unplug the UPS. Remove some  
of the equipment from the UPS. Restart the  
UPS.  
If the overload condition persists (125% for  
10 minutes), the UPS automatically shuts  
down.  
H
: : : : Hi Ambient The temperature inside the UPS is too high. If the UPS has shut down, contact your  
Temp  
If the temperature reaches a preset point,  
the UPS shuts down.  
service representative. If not, shut down  
the protected equipment and the UPS,  
correct the cause of the high temperature if  
possible, and turn the UPS on again. If the  
problem persists, contact your service  
representative.  
I
: :  
Hi  
The inverter temperature is too high. If the If the UPS has shut down, contact your  
Heatsink  
Temp  
temperature reaches a preset point, the  
UPS shuts down.  
service representative. If not, shut down  
your equipment or bypass the UPS; turn the  
UPS off. Contact your service  
representative.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Letter Audio  
Code  
Alarm  
Message  
What It Means  
What To Do  
J
: – – – User Test The user is testing the alarm feature.  
To start the user test alarm from the  
control panel, press [CTRL]-[8] [ENTER]  
[ENTER]. Repeat the procedure to turn the  
alarm off.  
Alarm  
K
: –  
Hi  
The transformer temperature is too high. If The UPS may have shut down; if so,  
the temperature reaches a preset point, the contact your service representative. If the  
Transfmr  
Temp  
UPS shuts down.  
UPS has not shut down, shut down your  
equipment or bypass the UPS; then, turn  
the UPS off and contact your service  
representative.  
L
M
N
O
: : :  
– –  
Check  
The UPS has detected a charger problem.  
Contact your service representative.  
Contact your service representative.  
Contact your service representative.  
Charger  
Check  
Battery  
The batteries have failed the automatic  
system test.  
:  
Check  
Inverter  
The inverter has failed the automatic  
system test.  
– – –  
Memory Possible microprocessor problem.  
Check  
Shut down your equipment or bypass the  
UPS; turn off the UPS. Contact your service  
representative.  
P
: – – : Emergency The Remote Shutdown feature has been  
To restart the UPS, disconnect the signal to  
activated at the RS-232 port (see “Remote Pin 21 on the RS-232 port. If you have a  
PwrOff  
Shutdown” on page 47.)  
control panel, put the UPS in Auto mode. If  
not, turn the On/Off switch off and then on  
again.  
Q
– – : –  
Hi PFM  
Res  
Temp  
The Power Factor Module’s temperature is If the UPS has shut down, contact your  
too high. If the temperature reaches a  
preset point, the UPS shuts down.  
service representative. If not, shut down  
your equipment or bypass the UPS; then,  
turn the UPS off and contact your service  
representative.  
R
S
: :  
Probe  
A temperature probe is missing or  
damaged.  
The UPS may shut down. Contact your  
service representative.  
Missing  
: : :  
High AC The input voltage is higher than the alarm Contact your service representative.  
Input  
setting.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Letter Audio  
Code  
Alarm  
Message  
What It Means  
What To Do  
T
Call  
Service  
The UPS has detected a problem that  
requires service.  
The UPS shuts down. Contact your service  
representative.  
W
: – –  
Fan Alarm The fan has stopped.  
The UPS may have shut down; if so,  
contact your service representative. If the  
UPS has not shut down, shut down your  
equipment or bypass the UPS; then, turn  
the UPS off and contact your service  
representative.  
Alarm and Inverter Logs  
Your FERRUPS UPS makes an entry in its logs every time it sounds an  
alarm or switches to inverter (battery power). This information can be  
helpful in diagnosing problems.  
You can view the Alarm and Inverter Logs from either the UPS control  
panel or a terminal or computer that you have connected to the RS-232  
port (see “Connecting a Terminal or Computer to the RS-232 Port” on  
page 41).  
Reading the Alarm Log from a Control Panel  
The Alarm Log is parameter 25. To display the Alarm Log from a control  
panel, follow these steps:  
Press this key: Display shows:  
[DISPLAY]  
[2][5]  
'LVSOD\ꢀ  
'LVSOD\ꢀ  
ꢄꢍ  
[ENTER]  
ꢄꢍ $ODUP /RJ  
The display scrolls through the 20 most recent entries in the Alarm Log.  
If you have not had 20 alarm conditions, the display scrolls through the  
entries FERRUPS has recorded. You can use the number keys as you  
view this scrolling display:  
Use this key:  
[0]  
To do this:  
Pause the scrolling and start it again.  
[1] through [9] Go to the next log entry.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Each log entry consists of four pieces of information: the alarm code,  
the date (month/day) of the alarm, the time (in 24-hour time) and the  
duration (in hours and minutes).  
For instance, one entry might look like this:  
B 0205 1017 0005  
In this example, “B” means the alarm was “Near Low Battery” (see  
“Alarms” on page 59); if alarm B was active, there would be an asterisk  
(*) after “B.” “0205” means the alarm occurred on February 5 (2/5).  
“1017” means the alarm occurred at 10:17 a.m. “0005” means the alarm  
condition lasted for 0 hours and 5 minutes.  
Reading the Inverter Log from a Control Panel  
The Inverter Log is parameter 24. To display the Inverter Log, follow  
these steps:  
Press this key: Display shows:  
[DISPLAY]  
[2][4]  
'LVSOD\ꢀ  
'LVSOD\ꢀ  
ꢄꢉ  
[ENTER]  
ꢄꢉ ,QYHUWHU /RJ  
The display scrolls through the 20 most recent entries in the Inverter  
Log. If the inverter has not run 20 times, the display scrolls through the  
entries the UPS has recorded. You can use the number keys as you view  
this scrolling display:  
Use this key:  
[0]  
To do this:  
Pause the scrolling and start it again.  
[1] through [9] Go to the next log entry.  
Each entry includes four pieces of information: the inverter code, the  
date (month/day) of the inverter run, the time (in 24-hour time) and the  
duration (in hours and minutes). For instance, one entry might look  
like this:  
L 0205 0951 0015  
In this example, “L” means the the UPS went to inverter because it lost  
AC input power; if the inverter was still running, there would be an  
asterisk (*) after the “L.” “0205” means the inverter ran on  
February 5 (2/5). “0951” means the inverter ran at 9:51 a.m. “0015”  
means the inverter ran for 0 hours and 15 minutes.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Table 15. Inverter Codes  
Inverter Code  
Meaning  
Explanation  
T
B
L
System Test  
Brownout  
Line Loss  
Manual  
UPS went to inverter to test the batteries.  
AC input voltage was too low.  
AC input power was lost.  
M
F
The inverter was started manually.  
Input frequency was too high or too low.  
A system reset was performed.  
Frequency  
Reset  
R
Reading the Alarm Log from a Terminal or Computer  
To display the Alarm Log on a terminal or computer, you can use the  
alarmlog or logs command (see “Entering Commands from a Terminal  
or Computer” page 44). These commands display up to 20 log entries in  
a table. For example, the log might look like this table:  
Active EventDate  
EventTime  
11:25:32  
12:13:18  
12:05:07  
Duration Code/Event  
No  
No  
No  
08/25/1993  
08/24/1993  
08/24/1993  
00:00:45  
00:01:08  
00:08:11  
J-User Test Alarm  
A-Low Battery  
B-Near Low Battery  
The table shows whether the alarm is active now (Active), the date and  
time of each alarm, how long it lasted (Duration), and what caused the  
alarm (Code/Event).  
You can also display parameter 25 to view the Alarm Log; this display is  
the same as the control panel display.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Reading the Inverter Log from a Terminal or Computer  
To display the Inverter Log on a terminal or computer, you can use the  
inverterlog or logs command (see “Entering Commands from a  
Terminal or Computer” page 44). These commands display up to 20 log  
entries in a table. For example, the log might look like this:  
Active EventDate  
EventTime  
11:25:32  
12:13:18  
Duration Code/Event  
No  
No  
08/25/1993  
08/24/1993  
00:00:45  
00:01:08  
M-Manual turnon  
L-Line fault  
The table shows whether the UPS is running on inverter (battery power)  
now (Active), the date and time that the UPS ran on battery power, the  
length of time the UPS ran on battery power (Duration), and the reason  
(Code/Event).  
You can also display parameter 24 to view the Inverter Log; this display  
is the same as the control panel display.  
Alarm Code Summary  
A
: –  
: : : Near Low Battery  
: : High Battery  
Low Battery  
L
: : :  
– –  
:  
– – –  
: – – :  
– – : –  
: :  
: : :  
Check Charger  
Check Battery  
Check Inverter  
Memory Check  
Emergency PwrOff  
Hi PFM Res Temp  
Probe Missing  
High AC Input  
Call Service  
B
C
D
E
F
G
H
I
M
N
O
P
Q
R
S
T
: :  
Low Runtime  
:
Low AC Output  
: : : High AC Output  
– – : Output Overload  
: : : : Hi Ambient Temp  
Hi Heatsink Temp  
: – – – User Test Alarm  
: – Hi Transfmr Temp  
Figure 12. Alarm Code Summary  
: :  
J
K
W : – –  
Fan Alarm  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Service and Support  
If you have any questions or problems with the UPS, call your Local  
Distributor or the Help Desk at one of the following telephone numbers  
and ask for a UPS technical representative.  
In the United States:  
Europe, Middle East, Africa:  
Asia:  
or  
Australia:  
Please have the following information ready when you call the Help  
Desk:  
: Model number  
: Serial number  
: Version number (if available)  
: Date of failure or problem  
: Symptoms of failure or problem  
: Customer return address and contact information  
If repair is required, you will be given a Returned Material Authorization  
(RMA) Number. This number must appear on the outside of the  
package and on the Bill Of Lading (if applicable). Use the original  
packaging or request packaging from the Help Desk or distributor. Units  
damaged in shipment as a result of improper packaging are not covered  
under warranty. A replacement or repair unit will be shipped, freight  
prepaid for all warrantied units.  
NOTE For critical applications, immediate replacement may be available. Call the  
Help Desk for the dealer or distributor nearest you.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pelco Home Security System CC1400HZ16 2 User Manual
Philips Computer Monitor 105S26 User Manual
Philips Computer Monitor 107B10 User Manual
Philips MP3 Player TDA9605H User Manual
Philips Speaker System SBA3010 00 User Manual
Philips Stereo System SDV7700K User Manual
Philips Thermometer SBC SC201 User Manual
Porter Cable Drill 2620 User Manual
Proctor Silex Microwave Oven E8020NP SI User Manual
PYLE Audio DVD Player PLDVD168 User Manual