Pentair Electric Heater MiniMax NT LN User Manual

1  
®
MiniMax NT LN Series  
Pool & Spa Heaters  
OPERATION & INSTALLATION MANUAL  
To  
Consumer  
Retain For  
Future  
Reference  
U.S. Patent Numbers  
6,295,980  
5,318,007 - 5,228,618  
5,201,307 - 4,595,825  
WARNING  
FOR YOUR SAFETY - READ BEFORE OPERATING  
If you do not follow these instructions exactly, a fire or explosion may result,  
causing property damage, personal injury or loss of life.  
Improper installation, adjustment, alteration, service or maintenance can cause  
property damage, personal injury or death. Installation and service must be  
performed by a qualified installer, service agency or the gas supplier.  
Do not store or use gasoline or other flammable vapors and liquids in the vicinity  
of this heater or other appliances.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any phone in your building.  
Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
If you cannot reach your gas supplier, call the fire department.  
For additional free copies of this manual; call (800) 831-7133.  
Pentair Water Pool and Spa, Inc.  
1620 Hawkins Ave., Sanford, NC 27330 (919) 566-8000  
10951 W. Los Angeles Ave., Moorpark, CA 93021 (805) 523-2400  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
Table of Contents  
Section I. Heater Identification Information ........................................................... 4  
Section II. Introduction ............................................................................................ 5  
Important Notices ......................................................................................................................................................................  
Warranty Information .................................................................................................................................................................  
Code Requirements...................................................................................................................................................................  
Consumer Information and Safety .............................................................................................................................................  
5
5
6
6
Section III. Installation .............................................................................................. 7  
Specifications ............................................................................................................................................................................  
Plumbing Connections...............................................................................................................................................................  
Valves ........................................................................................................................................................................................  
Manual By-Pass ........................................................................................................................................................................  
Below Pool Installation ..............................................................................................................................................................  
7
8
8
8
8
Water Connections .................................................................................................................................................................... 9 - 10  
Gas Connections ....................................................................................................................................................................... 11  
Sediment Traps ......................................................................................................................................................................... 11  
Gas Pipe Sizing ......................................................................................................................................................................... 12  
Testing Gas Pressure/Gas Pressure Requirements .................................................................................................................. 13  
Indoor Venting—General Requirements .................................................................................................................................... 14  
Indoor (USA) / Outdoor (Canada) Installations .......................................................................................................................... 15  
Combustion Air Supply .............................................................................................................................................................. 16  
Vent Adaptors ............................................................................................................................................................................ 16  
Indoor Installations —Venting Guidelines .................................................................................................................................. 17  
Outdoor Installations —Venting Guidelines ............................................................................................................................... 18  
Outdoor Vent Kit ........................................................................................................................................................................ 18  
Electrical Connections ............................................................................................................................................................... 19  
Wiring Diagram—NT LN with DDTC .......................................................................................................................................... 20  
Section IV. Operation ................................................................................................ 21  
Basic System Operation ............................................................................................................................................................ 21  
HSI (Hot-Surface Ignition) Lighting/Operation ........................................................................................................................... 21  
Safety Controls .......................................................................................................................................................................... 22 - 23  
Digital Display Temperature Controller (DDTC) ......................................................................................................................... 24 - 27  
Section V. Troubleshooting ....................................................................................... 28  
Troubleshooting (DDTC)............................................................................................................................................................ 28  
Troubleshooting (General) ......................................................................................................................................................... 29  
Service Checks - Ignition Module .............................................................................................................................................. 29  
Section VI. Maintenance ......................................................................................................... 30  
Maintenance Instructions........................................................................................................................................................... 30  
Pressure Relief Valve ................................................................................................................................................................ 30  
Energy Saving Tips.................................................................................................................................................................... 30  
Spring, Fall and Winter Operation ............................................................................................................................................. 31  
Chemical Balance...................................................................................................................................................................... 32  
Replacement Parts — NT LNw/DDTC ....................................................................................................................................... 33 - 34  
Chauffe-eau pour piscine et spa MiniMax® NT/Guide d'Installation et de Fonctionnement.......................... 36-72  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section I.Heater Identification Information  
4
Heater Identification Information  
To identify the heater, see rating plate on the inner front panel of the heater. There are two designators for each  
heater, one is the Model Number and the other is the Heater Identification Number (HIN).  
a. Heater Identification Number (HIN)  
The following example simplifies the identification system:  
1) HTR : Heater  
2) (200, 250, 300 or 400) : Input rating (Btu/hr) X 1000  
3) NT : MiniMax NT Series  
4) LN : Series Character  
5) NH : Gas type (Natural gas) and ignition system (Hot Surface Ignition)  
6) Options :  
Blank: Standard Model  
ASME: ASME Certified (Bronze Headers)  
ASHI: ASME Certified Bronze Header and High Altitude Rating  
HALT: High Altitude Rating  
HEATER IDENTIFICATION INFORMATION — (HIN)  
H. I. N.  
HEATER IDENTIFICATION NUMBER  
ID DESIGNATOR FOR PENTAIR POOL & SPA HEATERS  
HTR  
400  
NT  
LN  
N H  
A S H I  
BLANK = STANDARD MODEL  
ASME = ASME CERTIFIED  
ASHI = ASME CERTIFIED AND HIGH ALTITUDE RATED  
HALT = HIGH ALTITUDE RATED  
H = HOT SURFACE IGNITION  
N = NATURAL GAS  
LN = LOW NOx  
NT = MINIMAX NT SERIES  
MODEL SIZE = BTU INPUT in 1000 of BTU / HR  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section II. Introduction  
5
Introduction  
MiniMax NT® LN Series  
Pool and Spa Heaters  
Congratulations on your purchase of a MiniMax NT LN high performance heating system. Proper installation  
and service of your new heating system and correct chemical maintenance of the water will ensure years  
enjoyment. The MiniMax NT LN is a compact, lightweight, efficient, induced-draft, gas fired high performance  
pool and spa heater that can be directly connected to schedule 40 PVC pipe. The MiniMax NT LN also comes  
equipped with the Pentair multifunction temperature controller which shows, at a glance, the proper functioning  
of the heater. All MiniMax NT LN heaters are designed with a direct ignition device, HSI (hot-surface ignition),  
which eliminates the need for a standing pilot. The MiniMax NT LN requires an external power source  
(120/240 VAC 60 Hz) to operate.  
This instruction manual provides operating instructions, installation and service information for the  
MiniMax NT LN high performance heater. The information in this manual applies to all MiniMax NT LN  
models. It is very important that the owner/installer read and understand the section covering installation  
instructions, and recognize the local and state codes before installing the MiniMax NT LN. History and  
experience has shown that most heater damage is caused by improper installation practices.  
IMPORTANT NOTICES  
...For the installer and operator of the MiniMax NT LN pool and spa heater. The manufacturer’s warranty may  
be void if, for any reason, the heater is improperly installed and/or operated. Be sure to follow the instructions  
set forth in this manual. If you need any more information, or if you have any questions regarding to this pool  
heater, please contact Pentair Water Pool and Spa, Inc. at (800) 831-7133.  
WARRANTY INFORMATION  
The MiniMax NT LN pool heater is sold with a limited factory warranty. Specific details are described on the  
warranty registration card which is included with the product. Return the warranty registration card after  
filling in the serial number from the rating plate inside the heater.  
Pentair Water Pool and Spas high standards of excellence include a policy of continuous product improvement  
resulting in your state-of-the-art heater. We reserve the right to make improvements which change the  
specifications of the heater without incurring an obligation to update the current heater equipment.  
These heaters are designed for the heating of swimming pools and spas, and should never be used as  
space heating boilers, general purpose water heaters, in non-stationary installations, or for the heating  
of salt water. The manufacturer’s warranty may be void if, for any reason, the heater is improperly  
installed and/or operated. Be sure to follow the instructions set forth in this manual.  
CAUTION  
OPERATING THIS HEATER CONTINUOUSLY AT WATER TEMPERATURE BELOW 68° F. WILL CAUSE  
HARMFUL CONDENSATION AND WILL DAMAGE THE HEATER AND VOID THE WARRANTY. Do not use  
the heater to protect pools or spas from freezing if the final maintenance temperature desired is below  
68° F., as this will cause condensation related problems.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section II. Introduction  
6
CODE REQUIREMENTS  
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes. The heater,  
when installed, must be electrically grounded and bonded in accordance with local codes or, in the absence  
of local codes, in the USA, with the National Electrical Code, ANSI/NFPA 7; in Canada, with Canadian  
Electric Code, CSA C22.1.  
CONSUMER INFORMATION AND SAFETY  
WARNING  
The U.S. Consumer Product Safety Commission warns that elevated water temperature can be hazardous.  
See below for water temperature guidelines before setting temperature.  
1. Spa or hot tub water temperatures should never exceed 104° F. A temperature of 100° F. is considered  
safe for a healthy adult. Special caution is suggested for young children. Prolonged immersion in hot  
water can induce hyperthermia.  
2. Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could  
lead to unconsciousness and subsequently result in drowning.  
3. Pregnant women beware! Soaking in water above 100° F. can cause fetal damage during the first three  
months of pregnancy (resulting in the birth of a brain-damaged or deformed child). Pregnant women  
should stick to the 100° F. maximum rule.  
4. Before entering the spa or hot tub, the user should check the water temperature with an accurate  
thermometer. Spa or hot tub thermostats may err in regulating water temperatures by as much as 4° F.  
5. Persons with a medical history of heart disease, circulatory problems, diabetes or blood pressure  
problems should obtain their physician's advice before using spas or hot tubs.  
6. Persons taking medication which induce drowsiness, such as tranquilizers, antihistamines or  
anticoagulants should not use spas or hot tubs.  
WARNING  
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the  
heater. Do not use this heater if any part has been under water. Immediately call a qualified service  
technician to inspect the heater and to replace any part of control system and gas control which has been  
under water.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
7
Installation Instructions  
SPECIFICATIONS  
These installation instructions are designed for use by qualified personnel only, trained especially for  
installation of this type of heating equipment and related components. Some states require installation and  
repair by licensed personnel. If this applies in your state, be sure your contractor bears the appropriate  
license. See Figure 1 for Outdoor and Indoor Installations.  
DIMENSIONS IN INCHES  
24.05  
Heater  
Depth  
3.50  
MODEL  
200  
"A" DIM.  
21.63  
250  
300  
400  
24.63  
27.63  
34.13  
14.50  
4.88  
8.84  
6.64  
LEG  
"A" DIM.  
OUTDOOR INSTALLATION  
15.50  
7.35  
2 in. SOCKET  
30.63  
24.05  
LEG  
INDOOR INSTALLATION  
INDOOR VENT ADAPTOR  
P/N 460506  
P/N 460507  
4 in. Kit  
5 in. Kit  
VENT ADAPTOR  
(See Indoor Venting  
Instructions)  
2.00  
15.50  
7.35  
2 in. SOCKET  
24.05  
30.63  
Figure 1.  
LEG  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
8
MANUAL BY-PASS  
Where the flow rate exceeds the maximum 120 GPM, a  
manual bypass should be installed and adjusted. After  
adjustments are made, the valve handle should be removed  
to avoid tampering. See Figure 2.  
TO  
POOL  
PUMP  
POOL  
HEATER  
FILTER  
MANUAL  
BY-PASS  
GATE  
VALVE  
CHECK  
VALVE  
Model  
200  
Min. (GPM) Max. (GPM) *  
CHECK  
VALVE  
20  
30  
30  
40  
120  
120  
120  
120  
Figure 2.  
FROM  
POOL  
250  
PLUMBING CONNECTIONS  
300  
The MiniMax NT LN heater has the unique capability of  
direct schedule 40 PVC plumbing connections. A set of  
bulkhead fittings is included with the MiniMax NT LN to  
insure conformity with Pentair’s recommended PVC  
plumbing procedure. Other plumbing connections can be  
used. See Figure 2 for plumbing connections.  
400  
* Do not exceed the maximum recommended  
flow rate for the connecting piping.  
Table 1.  
See page 30 for  
Pressure Relief Valve Installations.  
CAUTION  
Before operating the heater on a new installation, turn  
on the circulation pump and bleed all the air from  
the filter using the air relief valve on top of the filter.  
Water should flow freely through the heater. Do not  
operate the heater unless water in the pool/spa is at  
the proper level. If a manual by-pass is installed,  
temporarily close it to insure that all air is purged  
from the heater.  
BELOW POOL INSTALLATION  
If the heater is below water level, the pressure  
switch must be adjusted. This adjustment must be  
done by a qualified service technician.  
See following CAUTION before installation.  
CAUTION  
BELOW OR ABOVE POOL INSTALLATION  
VALVES  
The water pressure switch is set in the factory at  
1½ PSI. This setting is for a heater installed at pool level  
or within 3’ above or 3’ below. If the heater is to be installed  
more that 3’ above or 3’ below, the water pressure switch  
must be adjusted by a qualified service technician. See  
page 22, Figure 21.  
When any equipment is located below the surface of the  
pool or spa, valves should be placed in the circulation piping  
system to isolate the equipment from the pool or spa. Check  
valves are recommended to prevent back siphoning.  
CAUTION  
Exercise care when installing chemical feeders so  
as to not allow back siphoning of chemical into the  
heater, filters or pump. When chemical feeders are  
installed in the circulation of the piping system,  
make sure the feeder outlet line is down stream of  
the heater, and is equipped with a positive seal  
noncorrosive “Check Valve”, (P/N R172288),  
between the feeder and heater.  
FLOW SWITCH  
If the heater is installed more the 6’ above the pool or  
more than 10’ below the pool level, you will be beyond  
the limits of the pressure switch and a flow switch must  
be installed. Locate and install the flow switch externally  
on the outlet piping from the heater, as close as possible  
to the heater. Connect the flow switch wires in place of  
the water pressure switch wires.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
9
WATER CONNECTIONS  
Reversing Headers —  
Reversible Inlet/Outlet Connection  
The MiniMax NT LN Series heater is factory  
assembled with right side inlet/outlet water  
connections. The inlet/outlet header can be reversed  
for left side water connections without removing the  
heat exchanger.  
NOTE  
Do NOT remove the high-limit and pressure  
switches or the thermistor from the front header  
during the reversing procedure, as they will be in  
the proper location when installed on the left side.  
Reversing Water Connections  
3. Disconnect the water pressure switch wiring.  
Tools required:  
Phillips Screw Driver  
9/16 in. Socket and Wrench  
1/2 in. & 9/16 in. Open Wrench  
4. Disconnect the temperature sensor wires from  
the circuit board and feed them back to the  
header.  
1. Remove the right and left large access doors. It is  
not necessary to remove the top of the heater to  
gain access to the headers.  
5. Remove the 8 bolts holding the main inlet/outlet  
head.  
2. Disconnect all wires from the high-limit  
switches except the short jumper wire.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
10  
cont’d.  
Reversible Inlet/Outlet Connection,  
9. Install the temperature sensing probe by passing  
the wires through the hole provided on the left  
side of the brace panel. Route wires through the  
support bracket.  
On the MiniMax NT LN Series heater there is insulation  
installed by the factory on the return head side of the  
heaters. This insulation is there so that if the heads are  
reversed in the field, during initial installation of the  
heater, the high limits will be insulated from the heat  
radiating from the flue collector.  
6. Return head in position before removal. This view  
shows the insulation installed by the factory.  
Remove the 8 bolts holding the return head in place.  
7. When heads are removed, replace the heat  
exchanger tube seal gaskets.  
10. Reconnect all the high limit wires and the  
pressure switch wiring, routing the wires  
through the same hole as the thermostat sensor  
wires.  
8. Exchange the inlet/outlet header with the return  
header. Lift the insulation to allow the main head  
to be installed. Align header with the heat  
exchanger. When head is placed into position,  
release the insulation; it will now shield the high  
limits from the heat produced by the flue collector.  
Install header bolts, and tighten snugly by hand.  
(This will help avoid cross threading.) When  
tightening, use a cross pattern starting from the  
center of the header. DO NOT over tighten.  
11. Pump and bleed system to check the head for  
leaks.  
12. Reinstall the two large inspection plates on the  
appropriate side.  
Remember: The inlet and outlet markings  
on the header are still correct.  
Do not plumb the heater backwards.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
11  
GAS CONNECTIONS  
GAS LINE INSTALLATIONS  
Before installing the gas line, be sure to check which gas the heater has been designed to burn. This is impor-  
tant because different types of gas require different gas pipe sizes. The rating plate on the heater will indicate  
which gas the heater is designed to burn. The tables, shown on page 12, show which size pipe is required for  
the distance from the gas meter to the heater. The table is for natural gas at a specific gravity of .65.  
When sizing gas lines, calculate three (3) additional feet of straight pipe for every elbow used. When installing  
the gas line, avoid getting dirt, grease or other foreign material in the pipe as this may cause damage to the gas  
valve, which may result in heater failure.  
The gas meter should be checked to make sure that it will supply enough gas to the heater and any other  
appliances that may be used on the same meter. The gas line from the meter will usually be of a larger size than  
the gas valve supplied with the heater. Therefore a reduction of the connecting gas pipe will be necessary.  
Make this reduction as close to the heater as possible.  
The heater and any other gas appliances must be disconnected from the gas supply piping system during any  
pressure testing on that system, (greater that ½ PSI). The heater and its gas connection must be leak tested  
before placing the heater in operation. Do not use flame to test the gas line. Use soapy water or another  
nonflammable method.  
NOTE  
A manual main shut-off valve must be installed externally to the heater.  
WARNING  
DO NOT INSTALL THE GAS LINE UNION INSIDE THE HEATER CABINET. THIS WILL VOID YOUR WARRANTY.  
SEDIMENT TRAPS  
Install a sediment in front of  
GAS  
the gas controls. The sediment  
trap shall be either a tee fitting  
with a capped nipple in the  
bottom outlet which can be  
removed for cleaning, as  
illustrated in Figure 3, or a  
other device recognized as an  
effective sediment trap. All  
gas piping should be tested  
after installation in accordance  
with local codes.  
VALVE  
GAS  
SUPPLY  
UNION  
TEE  
FITTING  
MANUAL  
SHUT OFF  
VALVE  
3 INCHES  
MINIMUM  
NIPPLE  
CAP  
HEATER CABINET  
Figure 3.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
12  
GAS PIPE SIZING  
Table 2.  
PIPE SIZING FOR GAS LINE CONNECTIONS  
MAXIMUM EQUIVALENT PIPE LENGTH (Ft.)  
Natural Gas at 1000 B.T.U. per Cubic Foot  
1/2”  
3/4”  
NAT  
30’  
20’  
10’  
-
1”  
NAT  
125’  
70’  
1-1/4” 1-1/2”  
2”  
2-1/2”  
NAT  
NAT  
450’  
250’  
200’  
100’  
NAT  
-
NAT  
NAT  
MODEL  
200  
-
-
-
-
-
-
-
-
-
250  
600’  
400’  
200’  
-
-
300  
50’  
400  
20’  
400’  
“RESIDENTIAL” NATURAL GAS 2 STAGE REGULATION  
In many Natural gas line installations, the gas supplier and/or installer may utilize a two stage regulation  
process where by at the streets main gas supply they will install the first stage gas regulator, which would  
be at a higher pressure. This higher pressure is usually set at 2 psi or 5 psi and can be for long distances  
and in a much smaller pipe size. Then within a short distance of the pool heater, generally around  
24 inches, they will install a second regulator, which is the second stage. This second stage regulator  
would be set at the minimum operating pressure for the heater. For “Natural Gas Pentair Pool Heaters”  
the minimum is 7 inches W.C.  
See “Gas Pressure Requirement Charts”  
Stage One "High Pressure" Gas Pipe Sizing  
2 PSI @ 1000 B.T.U. Per CU. FT.  
Stage Two "Low Pressure" Gas Pipe Sizing  
Stage 2 set at 7 in. W.C.  
MAXIMUM EQUIVALENT PIPE LENGTH  
MAXIMUM EQUIVALENT PIPE LENGTH  
Model  
200 through 300  
400  
0 to 50 Ft. 50 to 100 Ft. 100 to 150 Ft.  
Model  
200 through 300  
400  
0 to 10 Ft.  
3/4 in.  
10 to 20 Ft.  
3/4 in.  
1/2 in.  
3/4 in.  
1/2 in.  
3/4 in.  
1/2 in.  
3/4 in.  
3/4 in.  
1 in.  
5 PSI @ 1000 B.T.U. Per CU. FT.  
Stage 2 set at 7 in. W.C.  
200 through 400 3/4 in.  
200 through 400  
1/2 in.  
1/2 in.  
1/2 in.  
1 in.  
Table 3.  
Table 4.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
13  
TESTING GAS PRESSURE  
Inlet  
Manifold  
1. Push the power switch to “OFF”.  
2. Turn the gas valve knob to “OFF”.  
3. Remove 1/8 in. NPT plug on the outlet side  
of the valve and screw in the fitting from the  
Manometer kit.  
4. Connect the Manometer hose to the fitting.  
5. Turn the gas valve knob to “ON”.  
6. Turn on the heater and read the Manometer.  
7. The Manometer must read per the values of the Gas  
Pressure Requirement Table, on manifold side of the  
gas valve, while operating.  
8. If reading is below specified; check the inlet pressure  
while the heater is running to make sure of proper  
supply before attempting adjustments.  
MiniMax NT LN  
Illustration above is for Natural Gas, see Table 5.  
9. For adjustment, remove the Regulator Adjustment  
Cap and using a screwdriver turn the screw clockwise to increase - counterclockwise to decrease gas  
pressure.  
CAUTION  
The use of Flexible Connectors (FLEX) is NOT recommended as they cause excessive high gas pressure drops.  
GAS PRESSURE REQUIREMENTS  
Natural  
Gas Pressure  
Model  
Inches  
W.C.  
Regulator Adjustment Cap  
1/8" NPT Plug  
(Inlet Press)  
Maximum Inlet  
Minimum Inlet  
Manifold  
LN  
LN  
LN  
10  
5*  
4
ON  
NOTE: All readings must be taken while  
heater is operating. Any adjustments or  
readings made while heater is off will result in  
performance problems.  
OFF  
1/8" NPT Plug  
(Manifold Press)  
Figure 4.  
All Values are +/- 0.2 inch W.C.  
* 6 inch. W.C. for LN 400 Model.  
Table 5.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
14  
INDOOR VENTING — General Requirements  
The vent pipe must be the same size or larger. The MiniMax NT LN heaters are capable of a 360-degree discharge  
rotation and operate with a positive vent static pressure and with a vent gas temperature less than 400° F. The total length  
of the horizontal run must not exceed the length that is listed below in the tables.  
NOTE  
The allowable vent runs for each vent pipe diameter are different and can not be exceeded.  
Each 90-degree elbow reduces the maximum horizontal vent run by 8 feet and each 45-degree elbow in  
the vent run reduces the maximum vent run by 4 feet. See the tables below for the maximum vent  
lengths using 90-degree and 45-degree elbows.  
The MiniMax NT LN is a “Category III” appliance and is an induced-draft pool and spa  
4 inch Vent Pipe  
heater which uses positive pressure to push flue gases through the vent pipe to the outside.  
This requires a completely sealed vent system—single wall vent pipe with sealed-seams  
and joints. Flue gases under positive pressure may escape into the dwelling with any  
cracks or loose joints in the vent pipe, or improper vent installation. The vent pipe must  
be of a sealed-seam construction, such as those listed for use with “Category III Appliances”,  
and for operating temperatures less than 400° F. The use of listed thimbles, roof jacks and/  
or side vent terminals are required; and the proper clearances to combustible materials  
must be maintained in accordance with type of vent pipe employed—in the absence of a  
clearance recommendation by the vent pipe manufacturer, the requirements of the Uniform  
Mechanical Code should be met. The ventilation air requirements for the MiniMax NT  
heater can be found on page 16. It is recommended that vent  
Number of  
Elbows  
Maximum  
Vent Run  
(Feet)  
90°  
45°  
1
1
1
1
2
22  
18  
14  
2
14  
Table 6.  
runs over 18 feet be insulated to reduce condensation related  
5 inch Vent Pipe  
5 inch Vent Pipe  
problems and/or the use of a condensate trap in the vent run  
close to the heater may be necessary in certain installations  
such as cold climates. The MiniMax NT LN heater is suitable  
for through-the-wall venting, see table and dimensions below.  
Number of  
Elbows  
Number of  
Elbows  
Maximum  
Vent Run  
(Feet)  
Maximum  
Vent Run  
(Feet)  
90°  
45°  
2
90°  
45°  
2
Recommended sources for Side-wall vent hood terminals  
include: The Field Controls Co. (2308 Airport Road, Kingston,  
NC 28501, (800)742-8368) and Tjernlund Products Inc. (1601  
Ninth Street, White Bear Lake, MN 55110, (800) 255-4208)—  
consult manufacturer for model information and availability.  
0
1
1
1
1
2
2
45  
45  
41  
37  
33  
37  
33  
2
2
2
3
3
3
4
29  
25  
21  
29  
25  
21  
1
3
4
2
1
3
CAUTION  
Do NOT combine exhaust vent pipes to a common exhaust  
vent in multiple unit installations. Run separate vent pipes.  
1
2
21  
Table 7.  
C
F
THROUGH WALL VENT KITS FOR HEATERS  
Part  
Dim. A Dim. B Dim. C Dim. D Dim. E Dim. F  
Number  
B
A
E
471532 4 in. Dia. 6 in. Dia. 8½ in. 6 5/16 in. 12 5/8 in. 10 5/8 in.  
471543 5 in. Dia. 8 in. Dia. 8½ in.  
8 in.  
12 5/8 in. 10 5/8 in.  
D
Table 8.  
Figure 5.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
15  
(USA ONLY)  
INDOOR INSTALLATION  
Chimney or Gas Vent  
Vent Cap and  
Riser Furnished  
by Installer  
OUTDOOR SHELTER INSTALLATION (CANADA)  
See page 16 for Vent Adaptors  
All products of combustion and vent gases must be  
completely removed to the outside atmosphere through a  
vent pipe which is connected to the stack adaptor. A vent  
pipe extension of the same size must be connected to the  
vent adaptor and extended at least 2 feet higher than highest  
point of the roof within a 10 foot horizontal radius, and at  
least 3 ft. higher than the point at which it passes through  
the roof, or as permitted by local code; see Figures 6, 7  
and 12. The vent should terminate with an approved vent  
cap (weather cap) for protection against rain or blockage  
by snow. Insulated vent pipe and an approved roof jack  
shall be employed through the roof penetration.  
Outlet Air  
Opening  
Optional  
Side  
Wall Vent  
Inlet Air  
Opening  
Heater  
Figure 6.  
The heater must be located as close as practical to a  
chimney or gas vent.  
Chimney or Gas Vent  
Vent Cap and  
Riser Furnished  
by Installer  
CAUTION  
The heater should be installed at least 5 feet away  
from the pool or spa.  
The heater must be placed in a suitable room with adequate  
ventilation and on a leveled floor, where leakage from heat  
exchanger or water connections will not result in damage  
to the area adjacent to the heater or the structure. When  
such locations cannot be avoided, it is recommended that  
a suitable drain pan with adequate drainage, be installed  
under the heater. The pan must not restrict air flow.  
Outlet Air Opening  
Optional  
Side  
Wall Vent  
Inlet Air Opening  
It is recommended to install the heater on fire-resistance  
slabs. Do not install the heater directly on a combustible  
wood floor without placing a non-combustible material  
between the floor and the heater. Heaters must NEVER  
be installed directly on carpeting.  
Heater  
Figure 7.  
The heater should not be installed closer than 6 inches to  
any fences, walls or shrubs at any side or back, nor  
closer than 18 inches at the plumbing side. A minimum  
clearance of 24 inches must be maintained at the front of  
the heater.  
Installations in basements, garages, or underground  
structures where flammable liquids may be stored must  
have the heater elevated 18 inches from the floor. The  
following minimum clearances from combustible materials  
must be provided.  
6"  
INSTALLATION  
SIDE  
OF  
HEATER  
INDOOR  
(Outrdoor Shelter)  
OUTDOOR  
6"  
24"  
INCHES  
INCHES  
WATER PIPING  
BLANK  
18  
6
18  
6
REAR  
6
6
Open Un-roofed Area  
24  
18"  
TOP *  
18  
24  
FRONT  
Figure 8.  
* To ceiling or roof.  
Table 9.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
16  
Air Supply Requirements Guide  
for MiniMax NT LN Heaters  
COMBUSTION AIR SUPPLY  
For indoor installation, the heater location must  
provide sufficient air supply for proper combustion  
and ventilation of the surrounding area.  
Net Free open Area for  
Each Opening * (Square Inches)  
Heater  
Size  
Ducted from  
Outside  
Direct from  
Outside  
The requirements for the air supply specify that the  
room in which a heater is installed should be provided  
with two permanent air supply openings; one within  
12 inches of the ceiling, the other within 12 inches of  
the floor. These openings shall directly, or through  
duct, connect to outdoor air.  
200  
250  
300  
400  
100  
125  
150  
200  
50  
63  
75  
100  
Pentair Water Pool and Spa, Inc. does not recommend  
indoor installations that do not provide combustion  
air from outside the building.  
*
Area indicated is for one of two openings; one at floor  
level and one at the ceiling.  
NOTE: If using louvered type or screen type openings,  
check with Louver/Screen Manufacturers to correct for  
the Louver/Screen resistance.  
Table 10.  
CAUTION  
Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive  
chemical fumes which can void the warranty.  
1. Remove the six (6) retaining screws from the old  
VENT ADAPTORS  
exhaust grill and discard the screws, gasket, and  
exhaust grill as shown in Figure 10.  
(FITS ALL MODELS)  
EXHAUST GRILL  
The proper vent adaptor must be installed on the heater  
SCREWS (6)  
as shown below in Figure 9.  
GASKET  
Product No. Vent Dia.  
460506  
460507  
4 in.  
5 in.  
Figure 10.  
Vent  
Adaptor  
2. Install the Vent Adaptor as shown in Figure 11.  
Make sure the holes in the gasket, metal flange of  
the main vent assembly, and heater cover are  
alignedbeforesecuringintoplaceusingthesix(6)  
screws provided in the Vent Adaptor Kit.  
METAL FLANGE  
SCREWS (6)  
GASKET  
Figure 9.  
Figure 11.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
Section III. Installation  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
Section III. Installation  
OUTDOOR INSTALLATION  
(Outdoor Shelter Installation in Canada, see page 15)  
For outdoor installation with an exhaust grill, the heater must be placed in a suitable area on a level, noncombustible surface. Do not  
install the heater under an overhang with clearances less than 3 feet from the top of the heater. The area under an overhang must be  
open on three sides.  
IMPORTANT!  
• In an outdoor installation it is important to ensure water is diverted from overhanging eves with a proper  
gutter/drainage system. The heater must be set on a level foundation for proper drainage.  
• Under certain conditions, “heavy rains or unusually high winds”, it may be necessary to install an outdoors  
vent. In this situation, use Outdoor Vent Kit, P/N 460424, (see below).  
• This unit shall not be operated outdoors at temperatures below -20o F.  
OUTDOOR INSTALLATION  
VENTING GUIDELINES  
4'  
3'  
SIDE VIEW  
4'  
Property Line  
4 ft.  
4'  
Window  
Force  
Air Inlet  
Exhaust Grill  
(Vent)  
4 ft.  
Building  
Vent Termination:  
Must be at least 3 ft. above any forced  
air inlet located within a 10 ft. radius.  
Heater  
(side view)  
Must be located 4 feet away from the building wall  
openings, and at the following distances away from  
any door, window, or gravity air inlet:  
Figure 13.  
4 ft. below,  
4 ft. horizontally  
OUTDOOR VENT KIT  
1. Remove the six (6) retaining screws from the old exhaust grill and discard the screws, gasket, and exhaust grill as shown in Figure 14.  
2. Install the Outdoor Vent Kit, (P/N 460424), as shown in Figure 15. Make sure the holes in the gasket, metal flange of the main vent  
assembly, and heater cover are aligned before securing into place using the six (6) screws provided in the Outdoor Vent Kit.  
EXHAUST GRILL  
METAL FLANGE  
SCREWS (6)  
SCREWS (6)  
GASKET  
GASKET  
Figure 15.  
Figure 14.  
CAUTION  
If installing the heater next to or near an air conditioning unit or a heat pump, allow a minimum of 36 in.  
between the air conditioning unit and the heater.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section III. Installation  
19  
ELECTRICAL CONNECTIONS  
Electrical Rating  
60 Hz  
120 / 240 Volts AC, single phase  
CAUTION  
This heater is designed to operate at 120 or 240 VAC. It is not recommended to be connected to OR operate on a 208 VAC.  
NOTE  
• The MiniMax NT LN heater is prewired for 240-volt AC connection using the “RED” connector and the “BEIGE” common  
connector; see below, Figure 16. For 120-volt AC supply, remove the “BEIGE” common connector and plug it into the “BLUE”  
common connector.  
• When connecting the power supply to the “Line Terminal Block” inside the junction box, follow the polarity as shown below.  
Connecting to 120 VAC, make sure that you connect the wire to the terminal (L), the neutral wire is connected to the neutral  
terminal (N) and the ground is connected to the ground terminal (GND); see below, Figure 17.  
• If any of the original wiring supplied with this heater must be replaced, installer must supply (No. 18 AWG, 600V, 105° C.  
U.L. approved AWM low energy stranded) copper wire or it’s equivalent. Thermal fuse wiring must be replaced with 18 AWG,  
600V, 150° C. temp. rating.  
CAUTION  
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes. If an external electrical  
source is utilized, the heater, when installed, must be electrically grounded and bonded in accordance with local  
codes or, in the absence of local codes, in the USA, with the National Electrical Code, ANSI/NFPA 7; in Canada, with  
Canadian Electric Code, CSA C22.1.  
Always use crimp type connectors when connecting two wires.  
TRANSFORMER  
CONNECTOR  
BLUE  
120V CONNECTOR  
BEIGE  
COMMON CONNECTOR  
TERMINAL BLOCK  
FOR AC INPUT  
You need to open the right  
door then remove the  
control panel cover for  
120 / 240 VOLT SINGLE  
RED  
240V CONNECTOR  
PHASE "See Below"  
Figure 16.  
servicing the Line Terminal  
Block as shown in Figures  
16 & 17, (see item 40 in the  
exploded view on page 33).  
LINE TERMINAL BLOCK  
GROUND  
CONNECTION  
GREEN WIRE  
INTERNAL  
FACTORY WIRES  
NEUTRAL / WHITE 120 VAC  
LINE #1 FOR 240 VAC  
WHITE WIRE  
BLACK WIRE  
N
L
HOT / BLACK 120 VAC  
LINE #2 FOR 240 VAC  
Figure 17.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
Section III. Installation  
WIRING DIAGRAM–NT LN/W DDTC  
W
Y
B K  
O
P R  
THERMISTER  
Y
Y
R
R
P R  
P R  
FAN  
24VAC  
SPA  
COM  
{
POOL  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
21  
Operation Instruction  
BASIC SYSTEM OPERATION  
1. Start pump, make sure the pump is running and is primed, to close the water pressure switch and supply power to  
heater. Be sure the pool and/or spa is properly filled with water. Follow the Lighting/Operating instructions below.  
MINIMAX NT LN HSI ELECTRONIC IGNITION LIGHTING/OPERATION  
FOR YOUR SAFETY: READ BEFORE LIGHTING  
WARNING  
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal  
injury or loss of life.  
Do not attempt to light the heater if you suspect a gas leak. Lighting the heater can result in a fire or explosion  
which can cause personal injury, death, and property damage.  
A. This appliance does not have a pilot. It is equipped with  
an ignition device which automatically lights the burners.  
Do not try to light the burners by hand.  
-
If you cannot reach your gas supplier, call the Fire  
Department.  
C. Use only your hand to push in or turn the gas control knob.  
Never use tools. If the knob will not push in or turn by hand,  
don't try to repair it, call a qualified service technician. Forced  
or attempted repair may result in a fire or explosion.  
B. BEFORE OPERATING, smell all around the appliance  
area for gas. Be sure to smell next to the floor because some  
gas is heavier than air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
D. Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect  
the appliance and to replace any part of the control system  
and any gas control which has been under water.  
-
-
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any phone in  
your building.  
-
Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
OPERATING INSTRUCTIONS  
9. Set the thermostat to the desired temperature setting.  
a. Ignition module is energized and the pre-purge cycle is  
started, approximately 15 seconds.  
1. STOP! Read the safety information above, (A through D).  
2. Open the access doors. Set power switch to ”OFF”, (see  
Figure 25).  
b. Fan motor starts, which closes Vacuum Air Pressure (fan)  
switch.  
c. Check for powering-up the (glow coil) hot-surface ignitor  
by viewing through the glass window or opening on the  
burner face plate.  
3. Set the thermostat to ”OFF”, (see page 27).  
4. This appliance is equipped with an ignition device which  
automatically lights the burners. Do not try to light the burn-  
ers by hand.  
5. Push in gas control knob slightly and turn clockwise  
to “OFF”.  
10. If the appliance will not operate, follow the instructions  
"To Turn Off Gas To Appliance" and call your service tech-  
nician or gas supplier.  
NOTE: Knob cannot be turned to “OFF” unless knob is  
pushed in slightly. Do not force.  
6. Wait five (5) minutes to clear out any gas. If you then smell  
gas, STOP! Follow "B" in the safety information above.  
If you don't smell gas, go to the next step.  
Gas  
Inlet  
7. Turn gas control knob counterclockwise  
See Figure 19.  
to “ON”.  
ON  
OFF  
8. Close the access doors and set the thermostat to desired  
Mode: “POOL, SPA or REMOTE”.  
Figure 19.  
Gas control knob shown in “ON” position.  
TO TURN OFF GAS TO APPLIANCE  
1. Turn off all electric power to the appliance if service is to  
3. Open access doors.  
be performed.  
2. Set the thermostat to “OFF”.  
4. Push in gas control knob slightly and turn clockwise  
to "OFF". Do not force.  
5. Close access doors.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
22  
SAFETY CONTROLS  
Figure 20.  
VACUUM AIR PRESSURE (FAN) SWITCH  
The air pressure switch, (see Figure 20), is a safety device  
used to insure that the combustion air blower (fan) is  
operating and has been designed to monitor the vacuum  
(negative) pressure within the blower housing. The air  
pressures switch is factory set and is connected upstream  
of the ignition module. The ignition module does not  
operate unless the air pressure switch and all safety switches  
are closed.  
WATER PRESSURE SWITCH  
Air Pressure Switch  
The water pressure switch, (see Figure 21), closes when  
there is a sufficient flow of water to the heat exchanger to  
safely operate the heater. The switch has been preset by  
the Factory at 1½ PSI for operation. NOTE: See, Below  
Pool Level Installation instructions on page 8. The switch  
may remain closed with no water flow if there is more  
than a 3 ft. elevation difference between the heater (heat  
exchanger) and the pool water line—if this is the case, the  
water pressure switch must be reset by a qualified service  
technician to maintain open switch contacts with no water  
flow.  
Figure 21.  
Adjustment Knob  
NOTE  
If the pool is more than one floor above or one floor  
below the heater, the water pressure switch may  
have to be replaced with a flow switch.  
Typical Water Pressure Switch  
Figure 22.  
THERMAL FUSE  
This is a single-use switch, mounted on combustion  
chamber jacket divider (inner front panel). The fuse, (see  
Figure 22), is activated by excessive temperature due to  
abnormal operating conditions. Upon detection of  
excessive heat within the inner front panel, the fuse will  
open the safety circuit causing shutdown of the heater.  
Thermal Fuse  
Figure 23.  
LOW GAS PRESSURE SWITCH  
The MiniMax NT LN model heater uses a low gas supply  
pressure switch, (see Figure 23), ahead of the gas valve, to  
prevent operation of the heater when the gas supply  
pressure is below the minimum required for proper  
operation of the burners. The switch is factory set. In the  
event that the switch does not close and prevents the firing  
of the heater, the cause of the low gas supply pressure must  
be corrected. Typical causes are undersized supply piping,  
undersized gas meter or low gas regulator setting (gas  
supply regulator and gas meter problems are typically  
corrected by your local gas company).  
Low Gas Pressure Switch  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
23  
SAFETY CONTROLS, (cont’d.)  
HIGH LIMITS  
Flame Current  
Check Point  
Diagnostic LED  
1 Flash - Air Flow Fault  
2 Flashes - Flame no Call for Heat  
3 Flashes - Lock Out  
A “High Limit”, is a safety device that opens the electrical  
circuit and shuts off the heater based on a water temperature  
set point within the “High Limit Device”. The MiniMax NT  
LN series of heaters contains two (2) high limit devices which  
are located on the main inlet / outlet header, one sensing the  
inlet water temperature and one sensing the outlet water  
temperature.  
OPERATION OF IGNITION MODULE  
Figure 24.  
The Ignition Module, (see Figure 24), is microprocessor based  
and operates on 24 VAC supplied by the transformer. The  
control utilizes a microprocessor to continually and safely monitor, analyze, and control the proper operation of the gas  
burners. The module with the presence of the flame sensor, using flame rectification, allows the heater to operate.  
1. HEAT MODE  
• When a call for heat is received from the thermostat supplying 24 volts to the (TH) terminal, the module will check  
the pressure switch for normally open contact. The combustion blower is then energized and, once the air pressure  
switch contacts close, the 15-second "pre-purge" period begins. After pre-purge, the hot surface igniter is energized  
for approximately 40-second heat-up period, followed by the gas valve for the "trial for ignition" (TFI) period, for  
maximum of 7 seconds for the LN model.  
• When the flame is detected during the TFI period, through the flame sensor, the igniter is deactivated and the gas  
valve remains energized.  
Note: After the pre-purge period the combustion blower slows down to half normal speed during the heat-up and TFI  
periods and continues thereafter for another 30 seconds at low speed, then return to full speed for the remainder of  
the heating cycle.  
• The thermostat, air pressure switch and burner flame are constantly monitored to assure that the system operates  
properly. When the thermostat is satisfied and the demand for heat ends, the gas valve is immediately de-energized,  
the module senses the loss of flame signal and initiates the 45-second "post-purge" period before de-energizing the  
combustion blower.  
2. FAILURE TO LIGHT THE BURNER—LOCK OUT  
Should the main burner fail to light, or the flame is not detected during the  
first TFI (try for ignition) cycle, the gas valve is de-energized and the ignition  
module performs an "inter-purge" delay (approximately 15 seconds) before  
attempting another TFI cycle. The module will attempt 2 additional TFI's  
cycles before locking out. The gas valve will be turned off immediately. The  
combustion blower will be turned off following 45 seconds "post-purge"  
period.  
The module will automatically reset after one hour, if the thermostat  
is still calling for heat, and attempt a new TFI cycle.  
INTERNAL POWER SWITCH  
3. FLAME FAILURE—RE-IGNITION  
Figure 25.  
If the established flame signal is lost while the burner is operating, the control  
will respond within .08 second. The gas valve is de-energized and the control  
starts a new ignition sequence in an attempt to relight the burner. The ignition attempt will be repeated (3) times. If the  
burner does not relight, the control will go into lockout as previously described in the “Failure to Light the Burner—Lock  
Out”. If flame is reestablished, normal operation resumes.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
24  
DIGITAL DISPLAY TEMPERATURE CONTROLLER (DDTC)  
REMOTE BUTTON  
POOL BUTTON  
POWER  
REMOTE  
POOL  
SPA  
PRESSURE SW  
SYSTEM  
INDICATOR  
LIGHTS  
THERMOSTAT  
HEATING  
SPA BUTTON  
OFF BUTTON  
OFF  
TEMPERATURE SETTING  
POOL  
SPA  
SERVICE  
TEMP. UP  
PRESS ANY ARROW ONCE TO  
CHECK SET TEMPERATURE  
SPA AND POOL  
TEMPERATURE  
SET BUTTONS  
Figure 26.  
TEMP. DOWN  
The DDTC board, shown in Figure 26, is a digital temperature controller capable of controlling the pool, spa  
or both to a minimum temperature of 65° F. (below 65° F. display reads "Off") and a maximum of 104° F.  
The DDTC board also functions as a system status indicator, using LED lights and programmed error codes.  
During normal operation, the DDTC will display the current temperature of the water returning to the  
heater, depending on which mode has been selected, “Pool” or “Spa”. This is accomplished by a thermister  
(sensor) on the inlet port of the water header of the heater and working in conjunction with the internal  
microprocessor controlling the operation of the heater.  
Changing the desired pool or spa temperature is easily done by simply depressing the appropriate up or  
down arrow until the display reads the desired set-point temperature. For example, set pool to 78° F. and the  
spa to 104° F., when releasing the up or down arrow the display will flash once then return to the current  
temperature.  
At any time, you wish to know the temperature setting of the pool or spa, simply press the appropriate up or  
down arrow, the display will flash once and display the set-point temperature for three (3) seconds, then  
flash once again and return to the current temperature.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
25  
Figure 27.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
26  
SET UP  
The MiniMax NT LN Heater comes from the factory preset with a pool temperature setting of 78° F. and a  
preset spa temperature of 100° F., and in the off mode setting. Once the power is turned on, the DDTC  
board will do a self diagnostic internal check, during this time the display will first read “888”, then the  
display will switch to three dashes “- - -“, this process takes approximately ten (10) seconds. The DDTC  
will then illuminate the “Power” LED and “Off” LED, see Figure 27.  
1. Turn on the power to the heater; the switch is on the bottom of the electrical junction box located inter-  
nally on the right side of the cabinet. The DDTC will now go through the self-diagnostic’s test as stated  
above.  
2. Turn on the circulating system pump and make sure that adequate water is being delivered to the heater,  
The “PRESSURE SW” LED will now illuminate.  
3. If you are using the heater with a remote control system, open the right door of the heater to access the  
rear portion of the DDTC. Locate the three terminals marked “Pool” (J5), “Spa” (J6) and “Com” (J8).  
If the remote system is a three-wire remote unit, connect the pool lead to the “pool” terminal J5, connect  
the spa lead to the “spa” J6 terminal and connect the common wire to the “com” terminal J8. If the  
remote system is a two-wire remote, the remote system will be used to turn the heater on for a selected  
body of water, Pool or Spa, select which application you are working with and connect one wire to the  
common terminal J8 and the other wire to either “Pool J5” or “Spa J6”. Close and latch the door.  
LED INDICATORS  
There are nine lights that can be seen from the front of the control panel, (five are system indicators and four  
are mode indicators), which helps you understand the operation of the heater, see Figure 26. If something  
should go wrong, the lights will aid in troubleshooting the problem. An additional four lights can be seen  
after opening the control panel. These four lights are diagnostic indicators for the service technician to  
troubleshoot the system.  
On the right front of the DDTC board there are four Buttons and corresponding LED lights, see Figure 26.  
Using the buttons allows you to select one of the four modes and the lights indicate which operational mode  
that the heater is in, Off, Spa mode, Pool mode or Remote mode. If the heater is not connected to a remote  
system then the remote mode will not be used.  
The following are descriptions of the five system indicators:  
• POWER  
The light is on at all times, in any switch position, indicating 24 VAC power is being supplied to the control  
circuit. If it fails to light, no other light will be on. Possible causes are:  
1. External power to the heater is disconnected; check service panel circuit breaker or fuses;  
2. Transformer has failed.  
• PRESSURE SW (WATER PRESSURE SWITCH)  
This light is on when Spa/Pool Selector switch is on, indicates the circulating pump is running properly.  
If pressure light fails to light, the pump may have lost its prime or water flow may be restricted by an  
inadvertently closed valve or clogged filter or pump basket. If you have determined that there is no water  
flow restriction to the heater, you should call a qualified technician.  
• THERMOSTAT  
This light is on when the thermostat contacts close, signaled by the water temperature falling below the  
set-point, calling for the heater to fire to maintain the desired water temperature.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section IV. Operation  
27  
• HEATING  
The heating light is on any time the thermostat has signaled a call for heat which initializes the ignition  
safety circuit — the light comes on indicating successful firing of the main burners and stays on until the  
pool/spa reach the water temperature setting.  
• SERVICE  
The service light is off during normal operation of heater. The light only comes on if a problem with a  
control has occurred or when the heater is first firing. The problem must be investigated by the technician  
prior to attempts to fire the heater again.  
TEMPERATURE SETTING  
The heater comes factory set at 78° F. for the pool mode and 100° F. for the spa mode, using the up and  
down arrows, you can set the thermostats to a minimum temperature of 65° F., or a maximum of 104° F.  
If you desire to heat only one body of water, the thermostat is capable of an off mode. As an example, if you  
only wish to heat the spa and not the pool, simple depress and hold the pool down arrow, and the thermostat  
will lower its setting to 65° F. then go to an off mode. If there is a remote system connected to the heater,  
please see the special thermostat setting features under Heating Mode Selection & Remote mode.  
HEATING MODE SELECTION  
1. Off Mode: The heater will not come on. NOTE: The "Off" display on the Digital Display Temperature  
Controller does not mean that the heater is off. It only states that the pool or spa thermostat has been  
turned off.  
2. Spa Mode: The heater will operate and heat the spa to the desired temperature.  
3. Pool Mode: The heater will operate and heat the pool to the desired temperature.  
4. Remote Mode: The DDTC is compatible with two and three wire remote control systems. In order to  
operate by a remote control system, the REMOTE mode must be selected on the front panel. When the  
REMOTE mode is selected, the REMOTE LED will light up.  
REMOTE CONTROL  
THE TWO-WIRE REMOTE CONTROL SYSTEM is typically installed and connected to the heater for spa  
heating. The two-wire remote system is usually provided with a water temperature sensor that monitors the  
system temperature and turns the heater on or off in response to the temperature of the spa. To heat a spa, it  
should be connected to terminals J6 and J8. Pool heating remote control would require connecting to  
terminals J5 and J8. If the REMOTE mode is set at the front panel LED light, the DDTC will respond to a  
contact closure by remote system and heater will operate until the remote system temperature setting is  
satisfied.  
NOTE: With this type of two-wire remote, with its own temperature sensors and system control, using the  
up arrows on the front of the DDTC, hold down the up arrow until you reach the maximum setting of  
104° F., this allows the remote system thermostat to operate the heater at any set-point below 104° F., the  
heater thermostats then act as a secondary controller if water temperature reaches 104° F.  
THE THREE-WIRE REMOTE CONTROL SYSTEM will be connected to terminals J5, J6 & J8. J8 is the  
common terminal. If the heater is in the REMOTE mode, the DDTC will monitor the terminals and respond  
to a contact closure between J5 & J8 or J6 & J8. A contact closure between J5 & J8 will cause the DDTC to  
switch to the POOL setting and control the heater to the DDTC pool set-point temperature. A contact  
closure between J6 & J8 will cause the DDTC to switch to the SPA setting and control the heater to the  
DDTC spa set-point temperature. If only heating the spa, then depress the pool down arrow until the display  
goes to “Off”.  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section V. Troubleshooting  
28  
Troubleshooting Instruction  
TROUBLESHOOTING (DDTC)  
The DDTC temperature display contains three LED’s with a decimal point between the first and second, this  
display is also used to display an error code if for some reason there is a failure within the heater control  
system or a DDTC internal fault. The DDTC will display the actual temperature or set-point temperature or  
OFF, as selected by the user. When DDTC detects an error, the display will show Exx, see Figure 27, where  
Exx is the error code of DDTC fault, see Table 11. Codes 1 through 9 indicate a “soft lockout” error that  
means after these errors are fixed, the heater will resume normal operation and restart immediately. Code  
ERR indicates a “hard lockout” error that means after these errors are fixed, you need to reset the power of  
the heater through the switch on the bottom of the electrical junction box on the right side of the cabinet.  
NOTE: If Code ERR is shown on the LED display at any time, turn the heater off, (from power switch),  
then turn on the heater again. If the error code is still displayed, call a certified Pentair Service Technician  
for repair.  
Error Code  
Error Description  
E01  
System Low Voltage  
E02  
High Temperature Limit  
Thermal Fuse Open  
E03  
E04  
Fan Failure  
E05  
Ignition / Flame Failure  
Gas Valve / Module Failure  
Not Used  
E06  
E07, E08, E09  
ERR  
Call Pentair's Technical Service Department at: (800) 831-7133  
Table 11.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
Section V. Troubleshooting  
TROUBLESHOOTING (GENERAL)  
Possible Cause  
Remedy  
Heater will not come on  
Check if electrical connections are  
correct and securely fastened –  
If YES, call serviceperson.  
Place pump in operation  
Check for leaks  
Automatic ignition system fails  
Pump not running  
Pump air locked  
Filter dirty  
Clean filter  
Pump strainer clogged  
Defective wiring or connection  
Defective pressure switch  
Defective gas controls  
On-Off switch in "OFF" position  
Clean strainer  
Repair or replace wires  
Replace switch  
Call serviceperson  
Turn switch to "ON"  
Heater Short Cycling (Rapid On and Off Operation)  
Insufficient water flow  
Clean filter and pump strainer  
Defective wiring  
Repair or replace wiring  
Call serviceperson  
Call serviceperson  
Defective flow valve or out of adjustment  
Defective hi-limit and/or thermostat  
Heater Makes Knocking Noises,  
make sure all valves on system are open.  
Heater operating after pump has shut off  
Heater exchanger scaled  
Shut off gas supply and call serviceperson  
Shut off gas supply and call serviceperson  
SERVICE CHECKS—IGNITION MODULE  
Symptom  
Cause/Cure  
A. Miswired  
1. Dead  
B. Transformer bad  
C. Fuse/Circuit breaker bad  
D. Bad control  
2. Thermostat on—no ignition A. Miswired  
B. Bad thermostat no voltage at terminal  
3. Valve on, no ignition  
A. Defective ignitor  
B. Miswired  
C. Bad control (check voltage at ignitor)  
4. Ignitor on, no valve action A. Valve coil open  
B. Open valve wire  
C. Bad control (check voltage)  
A. Bad flame sensor  
B. Bad wires  
5. Flame okay during  
Try For Ignition (TFI),  
no flame sense (after TFI) C. Poor ground at burner  
D. Poor flame (check flame current)  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section VI. Maintenance  
30  
CAUTION  
REMOVE THE FLOW VALVE ASSEMBLY WHEN DRILLING  
THE HOLE TO INSTALL A PRV, OTHERWISE, YOU WILL  
DRILL INTO THE VALVE ASSEMBLY.  
Maintenance Instruction  
It is recommended that you check the following items at  
least every six months and at the beginning of every  
swimming season.  
PRESSURE RELIEF VALVE  
1. Examine the venting system. Make sure there are no  
obstructions in the flow of combustion and  
ventilation air.  
In some installations, a pressure relief valve (PRV)  
is required on the MiniMax NT LN Series. To install a  
PRV, remove the  
2. Visually inspect the main burner and the hot surface  
ignitor. The normal color of the flame is blue. When  
flame appears yellow, burners should be inspected  
and cleaned. Check ignitor for damage.  
RELIEF  
VALVE  
access doors,  
remove Flow Valve  
assembly, then  
carefully drill a  
FOR PRV  
INSTALLATION  
DRILL THRU  
THE NPT PORT  
3/8 in. hole in  
3. Inspect the heat exchanger for soot. Clean as  
necessary.  
center of 3/4 in.  
NPT port (on main  
header) being  
careful to drill only  
through wall at  
4. Remove burner tray and clean burners and main  
burner orifices.  
REMOVE FLOW VALVE  
BEFORE DRILLING  
THE NPT PORT  
5. Keep the heater area clean and free from  
combustibles and flammable liquids.  
bottom of 3/4 in.  
6. Check wire ends and wire connections. They should  
be clean and tight.  
NPT port and no  
deeper—now thread in  
Figure 29.  
the 3/4 in. NPT PRV.  
7. Check the gas pressure (supply and manifold) as  
described in this manual.  
RELIEF VALVE  
NOTE: (A.S.M.E.  
version varies slightly.  
It is of bronze  
construction, and is  
supplied with the  
A.S.M.E. Section IV,  
pressure relief valve  
pre-installed at  
TO WINTERIZE,  
OPEN DRAIN VALVE  
factory.)  
Figure 28.  
Test the relief valve  
A.S.M.E. VERSION  
at least once a year  
LN  
by lifting up lever.  
ENERGY SAVING TIPS  
5. Set time clock to start circulation system no earlier  
than daybreak. The swimming pool loses less heat  
at this time.  
6. For pools that are only used on the weekends, it is  
not necessary to leave the thermostat set at 78° F.  
Lower the temperature to a range that can be  
achieved easily in one day. Generally, this would  
be 10° F. to 15° F., if pool heater is sized properly.  
7. During the winter or while on vacation, turn the  
heater off.  
8. Set up a regular program of preventative  
maintenance for the heater each new swimming  
season. Check heat exchanger, controls, burners,  
operation, etc.  
1. If possible, keep pool or spa covered when not in  
use. This will not only cut heating costs, but also  
keep dirt and debris from settling in the pool and  
conserve chemicals.  
2. Reduce the pool thermostat setting to 78° F. or  
lower. This is accepted as being the most healthy  
temperature for swimming by the American Red  
Cross.  
3. Use an accurate thermometer.  
4. When the proper maximum thermostat settings  
have been determined, tighten the thermostat knob  
stopper.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section VI. Maintenance  
31  
SPRING AND FALL OPERATION  
If the pool is being used occasionally, do not turn the heater completely off. Set the thermostat down to  
65° F. This will keep the pool and the surrounding ground warm enough to bring the pool up to a  
comfortable swimming temperature in a shorter period of time.  
WINTER OPERATION  
CAUTION  
• Operating this heater continuously at water temperatures below 68° F. will cause harmful condensation and will  
damage the heater and void the warranty.  
• If the heater has been drained for freezing condition, do NOT turn "ON" until the system is circulating water.  
Water trapped in the heat exchanger can result in freeze damage to the exchanger or headers. Freeze damage is  
specifically not covered by the warranty.  
If the pool won't be used for a month or more, turn the heater off at the main gas valve. For areas where  
there is no danger of water freezing, water should circulate through the heater all year long, even though you are  
not heating your swimming pool. The MiniMax NT LN should not be operated outdoors at temperatures  
below 0° F. for propane and -20° F. for natural gas. Where freezing is possible, it is necessary to drain  
the water from the heater. This may be done by opening the drain valve, located at the inlet/outlet header,  
(see Figure 29), allowing all water to drain out of the heater. It would be a good practice to use compressed  
air to blow the water out of the heat exchanger. (See additional notes under Important Notices in  
Introduction.)  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
32  
Section VI. Maintenance  
RULE: 7.4 to 7.6 is a desirable pH range. It is essential  
to maintain correct pH, see Table 13.  
CHEMICAL BALANCE  
POOL AND SPA WATER  
If pH becomes too high (over alkaline), it  
has these effects:  
Your Pentair Pool Products pool heater was designed  
specifically for your spa or pool and will give you many  
years of trouble-free service, provided you keep your  
water chemistry in proper condition.  
1. Greatly lowers the ability of chlorine to destroy  
bacteria and algae.  
2. Water becomes cloudy.  
Three major items that can cause problems with your  
pool heater are: improper pH, disinfectant residual, and  
total alkalinity. These items, if not kept properly  
balanced, can shorten the life of the heater and cause  
permanent damage.  
3. There is more danger of scale formation on the  
plaster or in the heat exchanger tubing.  
4. Filter elements may become blocked.  
If pH is too low (over acid) the following  
conditions may occur:  
CAUTION  
Heat exchanger damage resulting from chemical  
imbalance is not covered by the warranty.  
1. Excessive eye burn or skin irritation.  
2. Etching of the plaster.  
3. Corrosion of metal fixtures in the filtration and  
recirculation system, which may create brown, blue,  
green, or sometimes almost black stains on the  
plaster.  
WHAT A DISINFECTANT DOES  
Two pool guests you do not want are algae and bacteria.  
To get rid of them and make pool water sanitary for  
swimming - as well as to improve the water's taste, odor  
and clarity - some sort of disinfectant must be used.  
4. Corrosion of copper tubes in the heater, which may  
cause leaks.  
Chlorine and bromine are universally approved by health  
authorities and are accepted disinfecting agents for  
bacteria control.  
5. If you have a sand and gravel filter, the alum used as  
a filter aid may dissolve and pass through the filter.  
CAUTION: Do not test for pH when the chlorine  
residual is 3.0 ppm or higher, or bromine residual  
is 6.0 ppm or higher. See your local pool supply  
store for help in properly balancing your water  
chemistry.  
WHAT IS A DISINFECTANT  
RESIDUAL?  
When you add chlorine or bromine to the pool water, a  
portion of the disinfectant will be consumed in the  
process of destroying bacteria, algae and other oxidizable  
materials. The disinfectant remaining is called chlorine  
residual or bromine residual. You can determine the  
disinfectant residual of your pool water with a reliable test  
kit, available from your local pool supply store.  
RULE: Chemicals that are acid lower pH. Chemicals  
that are alkaline raise pH.  
pH Control Chart  
Table 13.  
You must maintain a disinfectant residual level adequate  
enough to assure a continuous kill of bacteria or virus  
introduced into pool water by swimmers, through the air,  
from dust, rain or other sources.  
6.8  
7.0  
7.2  
7.4 7.6  
7.8  
8.0 8.2 8.4  
Add Acid  
Add Soda, Ash or  
Sodium Bicarbonate  
Marginal Ideal Marginal  
It is wise to test pool water regularly. Never allow  
chlorine residual to drop below 0.6 ppm (parts per  
million). The minimum level for effective chlorine or  
bromine residual is 1.4 ppm.  
ALKALINITY High or Low:  
"Total alkalinity" is a measurement of the total amount  
of alkaline chemicals in the water, and control pH to a  
great degree. (It is not the same as pH which refers  
merely to the relative alkalinity/acidity balance.) Your  
pool water's total alkalinity should be 100 - 140 ppm to  
permit easier pH control.  
pH - The term pH refers to the acid/alkaline balance of  
water expressed on a numerical scale from 0 to 14. A test  
kit for measuring pH balance of your pool water is  
available from your local pool supply store; see Table 12.  
A total alkalinity test is simple to perform with a reliable  
test kit. You will need to test about once a week and  
make proper adjustments until alkalinity is in the proper  
range. Then, test only once every month or so to be sure  
it is being maintained. See your local pool dealer for  
help in properly balancing the water chemistry.  
pH Chart  
Table 12.  
Strongly Acid  
Neutral  
Strongly Alkaline  
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14  
Muriatic Acid has a pH of about 0. Pure water is 7  
(neutral). Weak Lye solution have a pH of 13-14.  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
REPLACEMENT PARTS — NT LN w/DDTC  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
34  
\ꢂꢈꢠꢍꢅꢂ ꢂꢊꢁꢏꢗꢍꢆꢁꢄ3ꢕ^ꢏ_ꢕ  
ꢀꢁꢂ  
ꢃꢂꢄꢅꢆꢇꢈꢁꢇꢉꢊ  
ꢋꢌꢍꢊꢁꢇꢁꢎꢏ  
ꢐꢑꢑ  
ꢐꢒꢑ  
ꢓꢑꢑ  
ꢔꢑꢑ  
ꢁꢂꢃꢄꢅꢆꢇꢈꢉꢊꢋꢌꢌꢈꢍꢎꢉꢄꢆꢏꢐꢇꢈ  
ꢚꢛꢑꢓꢜꢑ  
ꢚꢛꢀꢛ;ꢀ  
ꢉꢄꢆꢏꢐꢇꢒꢈꢁꢂꢃꢄꢅꢆꢇꢈꢉꢊꢋꢌꢌ  
ꢔꢕꢖꢈꢗꢕꢘꢐꢊꢈꢍꢎꢙꢕꢆꢇꢆ  
ꢚꢛꢑꢓꢜꢓ  
ꢚꢛꢑꢓꢜꢛ  
ꢚꢛꢑꢓꢝꢀ  
ꢚꢛꢑꢓꢜꢚ  
ꢚꢛꢑꢓꢜ$  
ꢚꢛꢑꢓꢜꢜ  
ꢚꢛꢑꢓꢜꢛ  
ꢚꢛꢑꢓꢝꢑ  
ꢚꢛꢑꢓꢜꢝ  
ꢚꢛꢑꢓꢛꢓ  
ꢁꢂꢃꢄꢅꢆꢇꢈꢞꢆꢆꢐ "ꢌꢟ  
%ꢌꢕꢍꢐꢊꢈꢍꢎꢉꢄꢆꢏꢐꢇ  
ꢉꢄꢆꢏꢐꢇꢒꢈ%ꢌꢕꢍꢐꢊ  
ꢚꢛꢀꢝꢀ;  
&ꢌꢅꢐꢈꢗꢕꢌꢌꢐ'ꢇꢕꢊꢈ  
ꢚꢛꢑ;;<  
ꢚꢛꢑ;;ꢛ  
ꢚꢛꢑ;;ꢝ  
ꢚꢛꢑ;;ꢜ  
<
=ꢠꢆꢅꢌꢄꢇꢋꢕꢠꢒꢈ?ꢐꢄ@ꢐꢊꢎ?ꢋBJꢋ ꢋꢇ  
Kꢐꢇꢅꢊꢠꢈ?ꢐꢄ@ꢐꢊꢈꢞꢆꢆꢐ "ꢌꢟ  
%ꢕꢌꢇꢒꢈ?ꢐꢄꢇꢈꢁꢂ'ꢃꢄꢠꢡꢐꢊ  
Xꢄꢆꢃꢐꢊꢒꢈ?ꢐꢄꢇꢈꢁꢂ'ꢃꢄꢠꢡꢐꢊ  
&ꢋꢊꢐꢈ%ꢕꢂꢈꢞꢆꢆꢐ "ꢌꢟ  
ꢚꢛꢑꢑꢛ;  
$
ꢚꢛꢀ$$ꢀ  
ꢚꢛꢀꢝꢑꢑ  
;ꢛꢑꢀ<ꢚ  
ꢀ;  
ꢀꢀ  
ꢀꢑ  
ꢀꢝ  
ꢀꢝ  
ꢚꢛꢀ$;ꢚ  
ꢚꢛꢀ$ꢀ;  
ꢚꢛꢀ$ꢓꢓ  
ꢚꢛꢀ<ꢓꢜ  
ꢚꢛꢀ$ꢑꢑ  
ꢚꢛꢀ$ꢑ<  
ꢚꢛꢀ$ꢓꢜ  
ꢚꢛꢑꢓꢓꢑ  
ꢚꢛꢀ<ꢓ<  
ꢚꢛꢀ$ꢓꢝ  
?ꢐꢄꢇꢈꢁꢂ'ꢃꢄꢠꢡꢐꢊꢈꢍꢎ?ꢐꢄ@ꢐꢊꢆ  
?ꢐꢄꢇꢈꢁꢂ'ꢃꢄꢠꢡꢐꢊꢈꢍꢎꢕꢈ?ꢐꢄ@ꢐꢊꢆ  
ꢚꢛꢀꢛ<ꢜ  
ꢚꢛꢀ$ꢓꢚ  
ꢀꢓ  
ꢀꢚ  
<ꢈꢎꢈꢀꢝꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈ  
%ꢄꢢꢢꢌꢐꢒꢈ?ꢐꢄꢇꢈꢁꢂ'ꢃꢄꢠꢡꢐꢊ  
ꢚꢛꢀꢝꢚꢑ  
ꢚꢛꢀꢝꢚꢀ  
ꢚꢛꢀ<$ꢝ  
ꢚꢛꢀꢝꢚ;  
Zꢑ;;ꢒꢈꢑꢜ;ꢒꢈꢓ;;ꢈꢎꢈꢚ;;[  
ꢀꢜ  
ꢀꢝ  
ꢀꢛ  
ꢀ<  
ꢀ$  
ꢑ;  
ꢑꢀ  
ꢑꢑ  
ꢑꢓ  
ꢑꢚ  
ꢑꢜ  
ꢑꢝ  
ꢑꢛ  
ꢑ<  
ꢑ$  
ꢓ;  
ꢓꢀ  
ꢓꢑ  
ꢓꢓ  
ꢓꢚ  
ꢔꢃꢐꢊ ꢋꢆꢇꢕꢊꢈꢙꢊꢕ"ꢐ  
ꢚꢛꢀꢜꢝꢝ  
?ꢋBJꢋ ꢋꢇꢈꢔꢃꢐꢊ ꢕꢆꢇꢄꢇꢈBꢈꢀꢀꢜLꢈ&]  
?ꢋBJꢋ ꢋꢇꢈꢔꢃꢐꢊ ꢕꢆꢇꢄꢇꢈBꢈꢀꢜ;Lꢈ&]  
Xꢄꢇꢐꢊꢈꢙꢊꢐꢆꢆꢅꢊꢐꢈ^ꢍꢋꢇ'ꢃ  
=ꢠꢎ_ꢅꢇꢈꢔꢕꢖꢈ^ꢅ"B?ꢐꢄ@ꢐꢊꢈꢞꢆꢆꢐ "ꢌꢟ  
=ꢠꢎ_ꢅꢇꢈ`ꢄꢋꢠꢈ?ꢐꢄ@ꢐꢊꢈꢞꢆꢆꢐ "ꢌꢟ  
=ꢠꢎ_ꢅꢇꢈ%ꢕꢇꢇꢕ ꢈ^ꢅ"B?ꢐꢄ@ꢐꢊ  
ꢗꢄꢖꢒꢈ=ꢠꢎ_ꢅꢇꢈ%ꢕꢇꢇꢕ ꢈ^ꢅ"B?ꢐꢄ@ꢐꢊ  
_BKꢋꢠꢡꢒꢈꢞ@ꢄꢖꢇꢐꢊ  
ꢚꢛꢀꢜ<ꢛ  
ꢚꢛꢀꢝ$ꢚ  
ꢚꢛꢑꢀꢑꢜ  
ꢚꢛꢑꢓꢝꢓ  
ꢚꢛꢀ$$ꢑ  
ꢚꢛꢑꢓꢝꢚ  
ꢚꢛꢀꢚꢑ;  
ꢑꢛꢚꢚ$ꢚ  
ꢑꢛꢚꢚꢚ;  
ꢚꢛꢀꢚꢚꢀ  
;ꢛ;$ꢜꢀ  
ꢚꢛꢀꢛꢜ;  
ꢚꢛꢑꢓꢓ;  
ꢚꢛꢀꢝ;ꢀ  
ꢞ@ꢄꢖꢇꢐꢊꢒꢈ%ꢅꢌꢏꢃꢐꢄ@ꢈKꢋꢠꢡ  
ꢞ@ꢄꢖꢇꢐꢊꢒꢈ%ꢅꢌꢏꢃꢐꢄ@ꢒꢈꢑ{  
ꢉꢄꢆꢏꢐꢇꢒꢈ&ꢋꢠꢈꢔꢅ"ꢐꢒꢈ^ꢐꢄꢌ  
&ꢌꢕꢍꢈ|ꢄꢌꢘꢐꢈꢞꢆꢆꢐ "ꢌꢟ  
ꢙꢕꢍꢐꢊꢈꢁꢌꢐ ꢐꢠꢇꢒꢈ&ꢌꢕꢍꢈ|ꢄꢌꢘꢐ  
ꢉꢄꢆꢈ|ꢄꢌꢘꢐꢈBꢈ}ꢄꢇꢅꢊꢄꢌꢈꢉꢄꢆ  
%ꢅꢊꢠꢐꢊꢈꢔꢊꢄꢟꢈꢞꢆꢆꢐ "ꢌꢟ  
=ꢡꢠꢋꢇꢐꢊ  
ꢀ<  
ꢚꢛꢀ$;ꢜ  
ꢚꢛꢑ;;ꢚ  
ꢚꢛꢑ;ꢀꢝ  
ꢚꢛꢀ$ꢑꢓ  
ꢚꢛꢀ$<ꢀ  
ꢚꢛꢑ;;ꢀ  
ꢚꢛꢀꢝ$ꢝ  
ꢚꢛꢑ;<ꢓ  
ꢚꢛꢀꢜ$ꢛ  
ꢉꢄꢆꢈꢙꢊꢐꢆꢆꢅꢊꢐꢈ^ꢍꢋꢇ'ꢃ  
^ꢅ"Bꢉꢄꢆꢈ`ꢄꢠꢋꢢꢕꢌ@  
ꢉꢄꢆꢈ`ꢄꢠꢋꢢꢕꢌ@ꢈꢍꢎ_ꢊꢋꢢꢋ'ꢐꢆꢒꢈ;Bꢑ;;;~  
ꢚꢛꢑ;;ꢓ  
ꢚꢛꢑ;;ꢑ  
ꢚꢈꢎꢈꢜꢈꢎꢈꢝꢈꢎꢈ<ꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈ  
ꢓꢜ  
ꢓꢝ  
ꢉꢄꢆꢈ_ꢊꢋꢢꢋ'ꢐꢒꢈ;Bꢑ;;;~  
%ꢅꢊꢠꢐꢊ  
ꢚꢛꢀ$<ꢚ  
ꢚꢛꢀꢝꢝ<  
Zꢑ;;ꢈꢎꢈꢑꢜ;ꢈꢎꢈꢓ;;ꢈꢎꢈꢚ;;[  
ꢚꢈꢎꢈꢜꢈꢎꢈꢝꢈꢎꢈ<ꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈ  
Zꢑ;;ꢈꢎꢈꢑꢜ;ꢈꢎꢈꢓ;;ꢈꢎꢈꢚ;;[  
ꢓꢛ  
ꢓ<  
ꢓ$  
ꢚ;  
ꢚꢀ  
ꢚꢑ  
ꢚꢓ  
ꢄ'ꢏꢐꢇꢒꢈꢖꢖꢐꢊꢈꢙꢄꢠꢐꢌꢒꢈJꢐꢢꢇ  
ꢚꢛꢀꢜꢛꢜ  
ꢚꢛꢀꢜꢛꢝ  
ꢚꢛꢀꢛꢝꢛ  
ꢚꢛꢑꢜ;ꢜ  
ꢄ'ꢏꢐꢇꢒꢈꢖꢖꢐꢊꢈꢙꢄꢠꢐꢌꢒꢈKꢋꢡꢃꢇ  
ꢄ'ꢏꢐꢇꢒꢈꢖꢖꢐꢊꢈ^ꢅ"Bꢙꢌꢄꢇꢐ  
ꢅꢠ'ꢇꢋꢕꢠꢈ%ꢕꢂꢈꢞꢆꢆꢐ "ꢌꢟ  
ꢞꢋꢊꢈꢙꢊꢐꢆꢆꢅꢊꢐꢈ^ꢍꢋꢇ'ꢃꢒꢈ;Bꢑ;;;~  
`ꢕ@ꢅꢌꢐꢒꢈ=ꢡꢠꢋꢇꢋꢕꢠꢈꢗꢕꢠꢇꢊꢕꢌ  
ꢚꢛꢑꢀꢛ<  
ꢚꢛꢀ$;;  
ꢚꢛꢑꢀ<;  
ꢚꢛꢑꢀ<ꢀ  
ꢚꢛꢑꢀ<ꢑ  
ꢚꢛꢀꢛꢑꢝ  
ꢚꢛꢑꢚꢚꢛ  
ꢚꢛꢑꢀ;;  
ꢚꢛꢀꢛꢑꢛ  
ꢚꢛꢑꢓꢛꢑ  
ꢔꢐ ꢖꢐꢊꢄꢇꢅꢊꢐꢈꢗꢕꢠꢇꢊꢕꢌꢌꢐꢊꢈꢞꢆꢆꢐ "ꢌꢟ  
Kꢋꢡꢃꢇꢈ‚ꢕꢕꢊꢈꢞꢆꢆꢐ "ꢌꢟꢈꢍꢋꢇꢃꢈꢗꢕꢠꢇꢊꢕꢌꢌꢐꢊ  
Kꢋꢡꢃꢇꢈ‚ꢕꢕꢊꢈꢞꢆꢆꢐ "ꢌꢟꢈꢍꢎꢕꢈꢗꢕꢠꢇꢊꢕꢌꢌꢐꢊ  
Jꢐꢢꢇꢈ‚ꢕꢕꢊꢈꢞꢆꢆꢐ "ꢌꢟ  
ꢚꢚ  
ꢚꢜ  
}ꢞ  
}ꢞ  
}ꢞ  
}ꢞ  
ꢚꢛꢑꢓꢀ<  
ꢚꢛꢀ$ꢀ<  
ꢔꢃꢐꢊ ꢄꢌꢈꢗꢅꢇBꢕꢢꢢꢈZ}ꢕꢇꢈ^ꢃꢕꢍꢠ[  
ꢔꢊꢄꢠꢆꢢꢕꢊ ꢐꢊꢒꢈꢚ;ꢈ|ꢞꢈZ}ꢕꢇꢈ^ꢃꢕꢍꢠ[  
Xꢋꢊꢐꢈ?ꢄꢊꢠꢐꢆꢆꢈꢞꢆꢆꢐ "ꢌꢟꢈZ}ꢕꢇꢈ^ꢃꢕꢍꢠ[  
=ꢠ@ꢕꢕꢊꢈ|ꢐꢠꢇꢈꢞ@ꢄꢖꢇꢕꢊꢈZ^ꢐꢐꢈꢖꢡ]ꢀꢝ[  
;ꢛꢜꢀꢛꢓ  
ꢚꢛꢀꢜꢛꢀ  
ꢚꢛꢑꢜ;ꢛ  
ꢚꢝ;ꢜ;ꢝꢈZꢚ{[ꢈ ꢈꢚꢝ;ꢜ;ꢛꢈZꢜ{[  
`
ꢕꢉꢁꢂꢖꢏꢗꢍꢆꢁꢄꢏꢘꢉꢆꢏꢙꢚꢛꢜꢏꢍꢊꢝꢏꢞꢇꢟꢞꢏꢍꢠꢁꢇꢁꢌꢝꢂꢏ%ꢍ+ꢉꢡꢂꢏꢐꢑꢑꢑ<=ꢏꢍꢆꢂꢏꢊꢉꢁꢏꢠꢇꢄꢁꢂꢝꢏꢍ+ꢉꢡꢂ>ꢏꢈꢠꢂꢍꢄꢂꢏꢅꢉꢊꢁꢍꢅꢁꢏ  
ꢉꢌꢆꢏJꢌꢄꢁꢉ ꢂꢆꢏꢚꢂꢆꢡꢇꢅꢂꢏꢃꢂꢈꢍꢆꢁ ꢂꢊꢁꢏꢘꢉꢆꢏꢝꢂꢁꢍꢇꢠꢄ[ꢏ  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
NOTES  
Rev. E 4-19-05  
P/N 472089  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAVE THESE INSTRUCTIONS  
Pentair Water Pool and Spa, Inc.  
1620 Hawkins Ave., Sanford, NC 27330 (919) 566-8000  
10951 W. Los Angeles Ave., Moorpark, CA 93021 (805) 523-2400  
P/N 472089  
Rev. E 4-19-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pelco Computer Drive NSM5200 User Manual
Philips DVD Player BDP3480 User Manual
Philips Microphone SHM1000 User Manual
Philips Mouse SPT3700 User Manual
Philips MP3 Player 10FF2XLE User Manual
Philips Stereo System CDC 925 User Manual
Planet Technology Network Router VIP 462DG User Manual
PQI Computer Drive U510 Pro User Manual
PYLE Audio Computer Monitor PLHR9TSB User Manual
PYLE Audio Microphone PDWM2300 User Manual