PI Manufacturing Portable Generator AC generators User Manual

Installation, Service & Maintenance  
Manual  
AC generators with the following for prefixes:  
UCI; UCM; UCD 224 & 274 .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTROMAGNETIC COMPATIBILITY  
Additional Information  
FOREWORD  
The function of this book is to provide the user of the  
Stamford generator with an understanding of the  
principles of operation, the criteria for which the generator  
has been designed, and the installation and maintenance  
procedures. Specific areas where the lack of care or use  
of incorrect procedures could lead to equipment damage  
and/or personal injury are highlighted, with WARNING  
and/or CAUTION notes, and it is important that the  
contents of this book are read and understood before  
proceeding to fit or use the generator.  
European Union  
Council Directive 89/336/EEC  
For installations within the European Union, electrical  
products must meet the requirements of the above  
directive, and STAMFORD ac generators are supplied on  
the basis that:  
They are to be used for power-generation or related  
function.  
STAMFORD Service, Sales and Technical staff of are  
always ready to assist and reference to the company for  
advice is welcomed.  
They are to be applied in one of the following  
environments:  
Incorrect  
installation,  
operation,  
Portable (open construction - temporary site supply)  
servicing or replacement of parts can  
result in severe personal injury or  
death, and/or equipment damage.  
Service personnel must be qualified  
to perform electrical and mechanical  
service.  
Portable (enclosed  
-
temporary site supply)  
Containerised (temporary or permanent site supply)  
Ship-borne below decks (marine auxiliary power)  
Commercial vehicle (road transport / refrigeration  
etc) Rail transport (auxiliary power)  
Industrial vehicle (earthmoving, cranes etc)  
Fixed installation (industrial - factory / process plant)  
Fixed installation (residential, commercial and light  
industrial - home / office / health)  
Warning !  
EC DECLARATION OF INCORPORATION  
All Stamford generators are supplied with a declaration of  
incorporation for the relevant EC legislation, typically in  
the form of a label as below.  
Energy management (Combined heat and power  
and/or peak lopping)  
Alternative energy schemes.  
The standard generators are designed to meet the  
‘industrial’ emissions and immunity standards.  
Where the generator is required to meet the  
residential, commercial and light industrial emissions  
and immunity standards reference should be made  
to document reference N4/X/011, as additional  
equipment may be required.  
The installation earthing scheme involves connection  
of the generator frame to the site protective earth  
conductor using a minimum practical lead length.  
Maintenance and servicing with anything other than  
factory supplied genuine STAMFORD parts will  
invalidate warranty and our liability for EMC  
compliance.  
Installation, maintenance and servicing is carried out  
by adequately trained personnel fully aware of the  
requirements of the relevant EC directives  
Under the EC Machinery Directive section 1.7.4. It is the  
responsibility of the generator set builder to ensure the  
generator identity is clearly displayed on the front cover  
of this book.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
SAFETY PRECAUTIONS  
FOREWORD  
1
CONTENTS  
SECTION 1  
2&3  
4
INTRODUCTION  
1.1  
1.2  
1.3  
INTRODUCTION  
DESIGNATION  
4
4
SERIAL NUMBER LOCATION  
AND IDENTITY NUMBER LOCATION  
RATING PLATE AND CE MARKING  
PRINCIPLE OF OPERATION  
SELF-EXCITED AVR CONTROLLED GENERATORS  
PERMANENT MAGNET GENERATOR (PMG) EXCITED -  
AVR CONTROLLED GENERATORS  
AVR ACCESSORIES  
TRANSFORMER CONTROLLED GENERATORS  
APPLICATION OF THE GENERATOR  
INSTALLATION - PART 1  
LIFTING  
4
4
5
5
1.4  
SECTION 2  
2.1  
2.2  
5
5
5
6
8
8
2.3  
2.4  
SECTION 3  
SECTION 4  
4.1  
4.2  
ASSEMBLY  
8
4.2.1  
4.2.2  
4.2.3  
4.3  
NO FOOT OPTION  
8
9
9
9
TWO BEARING GENERATORS  
SINGLE BEARING GENERATORS  
EARTHING  
4.4  
PRE-RUNNING CHECKS  
INSULATION CHECK  
DIRECTION OF ROTATION  
VOLTAGE AND FREQUENCY  
AVR SETTINGS  
TYPE SX460 AVR  
TYPE SX440 AVR  
TYPE SX421 AVR  
TYPE MX341 AVR  
9
9
4.4.1  
4.4.2  
4.4.3  
4.4.4  
4.4.4.1  
4.4.4.2  
4.4.4.3  
4.4.4.4  
4.4.4.5  
4.4.5  
10  
10  
10  
10  
10  
11  
11  
11  
TYPE MX321 AVR  
TRANSFORMER CONTROLLED  
EXCITATION SYSTEM (Series 5)  
GENERATOR SET TESTING  
TEST METERING/CABLING  
INITIAL START-UP  
12  
12  
12  
12  
13  
13  
4.5  
4.5.1  
4.6  
4.7  
4.7.1  
4.7.1.1  
LOAD TESTING  
AVR CONTROLLED GENERATORS - AVR ADJUSTMENTS  
UFRO (Under Frequency Roll Off)  
(AVR Types SX460, SX440, SX421, MX341 and MX321)  
EXC TRIP (Excitation Trip)  
OVER/V (Over Voltage)  
TRANSIENT LOAD SWITCHING ADJUSTMENTS  
RAMP BUILD UP TIME  
TRANSFORMER CONTROLLED GENERATORS -  
TRANSFORMER ADJUSTMENT  
ACCESSORIES  
INSTALLATION - PART 2  
GENERAL  
GLANDING  
EARTHING  
PROTECTION  
13  
14  
14  
14  
15  
4.7.1.2  
4.7.1.3  
4.7.1.4  
4.7.1.5  
4.7.2  
15  
15  
16  
16  
16  
16  
16  
16  
4.8  
SECTION 5  
5.1  
5.2  
5.3  
5.4  
5.5  
COMMISSIONING  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
SECTION 6  
ACCESSORIES  
REMOTE VOLTAGE ADJUST (ALL AVR TYPES)  
PARALLEL OPERATION  
DROOP  
SETTING PROCEDURE  
ASTATIC CONTROL  
MANUAL VOLTAGE REGULATOR (MVR) -  
MX341 and MX321 AVR  
17  
17  
17  
17  
18  
18  
6.1  
6.2  
6.2.1  
6.2.1.1  
6.2.2  
6.3  
18  
6.4  
OVERVOLTAGE DE-EXCITATION BREAKER  
SX421 and MX321 AVR  
18  
19  
19  
19  
20  
21  
21  
21  
21  
23  
23  
23  
23  
23  
24  
24  
24  
25  
25  
26  
26  
6.4.1  
6.5  
6.5.1  
6.6  
RESETTING THE BREAKER  
CURRENT LIMIT - MX321 AVR  
SETTING PROCEDURE  
POWER FACTOR CONTROLLER (PFC3)  
SERVICE AND MAINTENANCE  
WINDING CONDITION  
WINDING CONDITION ASSESSMENT  
METHODS OF DRYING OUT GENERATORS  
BEARINGS  
SECTION 7  
7.1  
7.1.1  
7.1.2  
7.2  
7.3  
7.3.1  
7.4  
7.4.1  
7.4.2  
7.4.3  
7.4.4  
7.4.5  
7.4.6  
7.4.7  
7.5  
AIR FILTERS  
CLEANING PROCEDURE  
FAULT FINDING  
SX460 AVR - FAULT FINDING  
SX440 AVR - FAULT FINDING  
SX421 AVR - FAULT FINDING  
TRANSFORMER CONTROL - FAULT FINDING  
MX341 AVR - FAULT FINDING  
MX321 AVR - FAULT FINDING  
RESIDUAL VOLTAGE CHECK  
SEPARATE EXCITATION TEST PROCEDURE  
GENERATOR WINDINGS, ROTATING DIODES and  
PERMANENT MAGNET GENERATOR (PMG)  
BALANCED MAIN TERMINAL VOLTAGES  
UNBALANCED MAIN TERMINAL VOLTAGES  
EXCITATION CONTROL TEST  
AVR FUNCTION TEST  
RANSFORMER CONTROL  
REMOVAL AND REPLACEMENT OF COMPONENT  
ASSEMBLIES  
REMOVAL OF PERMANENT MAGNET GENERATOR (PMG)  
REMOVAL OF BEARINGS  
REMOVAL OF ENDBRACKET AND EXCITER STATOR  
REMOVAL OF THE ROTOR ASSEMBLY  
RETURNING TO SERVICE  
7.5.1  
26  
26  
27  
27  
27  
28  
7.5.1.1  
7.5.1.2  
7.5.2  
7.5.2.1  
7.5.2.2  
7.5.3  
28  
28  
28  
28  
29  
29  
30  
30  
30  
32  
33  
35  
7.5.3.1  
7.5.3.2  
7.5.3.3  
7.5.3.4  
7.6  
SECTION 8  
SECTION 9  
SPARES AND AFTER SALES SERVICE  
RECOMMENDED SPARES  
AFTER SALES SERVICE  
PARTS IDENTIFICATION  
TYPICAL SINGLE BEARING GENERATOR (Fig. 11)  
TYPICAL TWO BEARING GENERATOR (Fig. 12)  
8.1  
8.2  
TYPICAL TWO BEARING (SERIES 5) GENERATOR (Fig. 13) 37  
ROTATING RECTIFIER ASSEMBLY (Fig. 14) 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1  
INTRODUCTION  
1.4 RATING PLATE  
1.1 INTRODUCTION  
The generator has been supplied with a self adhesive rating  
plate label to enable fitting after final assembly and painting.  
The UC22/27 range of generators is of brushless rotating field  
design, available up to 660V/50Hz (1500 rpm) or 60Hz (1800  
rpm), and built to meet BS5000 Part 3 and international  
standards.  
All the UC22/27 range are self-excited with excitation power  
derived from the main output windings, using either the  
SX460/SX440/SX421 AVR. The UC22 is also available with  
specific windings and a transformer controlled excitation  
system.  
It is intended that this label will be stuck to the outside of the  
terminal box on the left hand side when viewed from the  
N.D.E. To assist with squarely positioning the label, location  
protrusions have been made in the sheet metalwork.  
A CE Mark label is also supplied loose for fitment after final  
assembly and painting. This should be attached to an external  
surface of the Generator at a suitable location where it will not  
be obscured by the customer's wiring or other fittings.  
A permanent magnet generator (PMG) powered excitation  
system is available as an option using either the MX341 or  
MX321 AVR.  
The surface in the area where a label is to be stuck must be  
flat, clean, and any paint finish be fully dry before attempting  
to attach label. Recommended method for attaching label is  
peel and fold back sufficient of the backing paper to expose  
some 20 mm of label adhesive along the edge which is to be  
located against the sheet metal protrusions. Once this first  
section of label has been carefully located and stuck into  
position the backing paper can be progressively removed, as  
the label is pressed down into position. The adhesive will  
achieve a permanent bond in 24 hours.  
Detailed specification sheets are available on request.  
1.2 DESIGNATION  
.
1.3 SERIAL NUMBER LOCATION AND IDENTITY  
NUMBER LOCATION  
Each generator is metal stamped with it’s own unique serial  
number, the location of this number is described below.  
UCI and UCM generators have their serial number stamped  
into the upper section of the drive end frame to end bracket  
adaptor ring, shown as item 31 in the parts lists at the back of  
this book.  
UCD generators have their serial number stamped into the  
top of the drive end adaptor /fan shroud casting. If for any  
reason this casting is removed, it is imperative that care is  
taken to refit it to the correct generator to ensure correct  
identification is retained.  
Inside the terminal box two adhesive rectangular labels have  
been fixed, each carrying the generators unique identity  
number. One label has been fixed to the inside of the terminal  
box sheet metal work, and the second label fixed to the main  
frame of the generator.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 2  
PRINCIPLE OF OPERATION  
The PMG system provides a constant source of excitation  
2.1 SELF-EXCITED AVR CONTROLLED  
power irrespective of main stator loading and provides high  
motor starting capability as well as immunity to waveform  
distortion on the main stator output created by non linear  
loads, e.g. thyristor controlled dc motor.  
The MX341 AVR senses average voltage on two phases  
ensuring close regulation. In addition it detects engine speed  
and provides an adjustable voltage fall off with speed, below a  
pre-selected speed (Hz) setting, preventing over-excitation at  
low engine speeds and softening the effect of load switching  
to relieve the burden on the engine. It also provides over-  
excitation protection which acts following a time delay, to de-  
excite the generator in the event of excessive exciter field  
voltage.  
The main stator provides power for excitation of the exciter  
field via the SX460 (SX440 or SX421) AVR which is the  
controlling device governing the level of excitation provided to  
the exciter field. The AVR responds to a voltage sensing  
signal derived from the main stator winding. By controlling the  
low power of the exciter field, control of the high power  
requirement of the main field is achieved through the rectified  
output of the exciter armature.  
The MX321 provides the protection and engine relief features  
of the MX341 and additionally incorporates 3 phase rms  
sensing and over-voltage protection.  
The detailed function of all the AVR circuits is covered in the  
load testing (subsection 4.7).  
2.3 AVR ACCESSORIES  
The SX440, SX421, MX341 and MX321 AVRs incorporate  
circuits which, when used in conjunction with accessories, can  
provide for parallel operation either with 'droop' or 'astatic'  
control, VAR/PF control and in the case of the MX321 AVR,  
short circuit current limiting.  
The SX460 or SX440 AVR senses average voltage on two  
phases ensuring close regulation. In addition it detects engine  
speed and provides voltage fall off with speed, below a pre-  
selected speed (Hz) setting, preventing over-excitation at low  
engine speeds and softening the effect of load switching to  
relieve the burden on the engine.  
Function and adjustment of the accessories which can be  
fitted inside the generator terminal box are covered in the  
accessories section of this book.  
The SX421 AVR in addition to the SX440 features has three  
phase rms sensing and also provides for over voltage  
protection when used in conjunction with an external circuit  
breaker (switchboard mounted).  
Separate instructions are provided with other accessories  
available for control panel mounting.  
2.2 PERMANENT MAGNET GENERATOR (PMG)  
EXCITED - AVR CONTROLLED GENERATORS  
2.4 TRANSFORMER CONTROLLED GENERATORS  
The main stator provides power for excitation of the exciter  
field via a transformer rectifier unit. The transformer combines  
voltage and current elements derived from the main stator  
output to form the basis of an open-loop control system, which  
is self regulating in nature. The system inherently  
compensates for load current magnitude and power factor  
and provides short circuit maintenance in addition to a good  
motor starting performance.  
Three phase generators normally have a three phase  
transformer control for improved performance with  
unbalanced loads but a single phase transformer option is  
available.  
No accessories can be provided with this control system.  
The permanent magnet generator (PMG) provides power for  
excitation of the exciter field via the AVR (MX341 or MX321)  
which is the controlling device governing the level of excitation  
provided to the exciter field. The AVR responds to a voltage  
sensing signal derived, via an isolating transformer in the  
case of MX321 AVR, from the main stator winding. By  
controlling the low power of the exciter field, control of the  
high power requirement of the main field is achieved through  
the rectified output of the exciter armature.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
APPLICATION OF THE GENERATOR  
The generator is supplied as a component part for installation  
in a generating set. It is not, therefore, practicable to fit all the  
necessary warning/hazard labels during generator  
manufacture. The additional labels required are packaged  
with this Manual, together with a drawing identifying their  
locations. (See below).  
The generators are of air-ventilated screen protected drip-  
proof design and are not suitable for mounting outdoors  
unless adequately protected by the use of canopies. Anti-  
condensation heaters are recommended during storage and  
for standby duty to ensure winding insulation is maintained in  
good condition.  
When installed in a closed canopy it must be ensured that the  
ambient temperature of the cooling air to the generator does  
not exceed that for which the generator has been rated.  
The canopy should be designed such that the engine air  
intake to the canopy is separated from the generator intake,  
particularly where the radiator cooling fan is required to draw  
air into the canopy. In addition the generator air intake to the  
canopy should be designed such that the ingress of moisture  
is prohibited, preferably by use of a 2 stage filter.  
The air intake/outlet must be suitable for the air flow given in  
the following table with additional pressure drops less than or  
equal to those given below :  
Air Flow  
50Hz  
Additional  
(intake/outlet)  
Pressure Drop  
6mm water gauge  
(0.25”)  
Frame  
60Hz  
0.216m³/sec  
458cfm  
0.281m³/sec  
595cfm  
UC22  
0.25m³/sec  
530cfm  
0.514m³/sec  
1090cfm  
0.31m³/sec  
657cfm  
0.617m³/sec  
1308cfm  
6mm water gauge  
(0.25”)  
6mm water gauge  
(0.25”)  
UCD22  
UC27  
0.58m³/sec  
1230cfm  
0.69m³/sec  
1463cfm  
6mm water gauge  
(0.25”)  
UCD27  
Important ! Reduction in cooling air flow or inadequate  
protection to the generator can result in  
damage and/or failure of windings.  
Dynamic balancing of the generator rotor assembly has been  
carried out during manufacture in accordance with BS 6861  
Part 1 Grade 2.5 to ensure vibration limits of the generator are  
in accordance with BS 4999 Part 142.  
The main vibration frequencies produced by the component  
generator are as follows:- :  
4 pole  
1500 rpm  
1800 rpm  
25 Hz  
30 Hz  
However, vibrations induced by the engine are complex and  
contain frequencies of 1.5, 3, 5 or more times the fundamental  
frequency of vibration. These induced vibrations can result in  
generator vibration levels higher than those derived from the  
generator itself. It is the responsibility of the generating set  
designer to ensure that the alignment and stiffness of the  
bedplate and mountings are such that the vibration limits of  
BS5000 Part 3 are not exceeded.  
It is the responsibility of the generating set manufacturer to  
ensure that the correct labels are fitted, and are clearly visible.  
The generators have been designed for use in a maximum  
ambient temperature of 40°C and altitude less than 1000m  
above sea level in accordance with BS5000.  
Ambients in excess of 40°C and altitudes above 1000m can  
be tolerated with reduced ratings - refer to the generator  
nameplate for rating and ambient. In the event that the  
generator is required to operate in an ambient in excess of the  
nameplate value or at altitudes in excess of 1000 metres  
above sea level, refer to the factory.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
In standby applications where the running time is limited and  
reduced life expectancy is accepted, higher levels than  
specified in BS5000 can be tolerated, up to a maximum of  
18mm/sec.  
The terminal box is constructed with removable panels for  
easy adaptation to suit specific glanding requirements. Within  
the terminal box there are insulated terminals for line and  
neutral connections and provision for earthing. Additional  
earthing points are provided on the generator feet.  
Two bearing generators open coupled require a substantial  
bedplate with engine/generator mounting pads to ensure a  
good base for accurate alignment. Close coupling of engine to  
generator can increase the overall rigidity of the set. For the  
purposes of establishing set design the bending moment at  
the engine flywheel housing to generator adaptor interface  
should not exceed 1000ft.lb. (140 kgm). A flexible coupling,  
designed to suit the specific engine/generator combination, is  
recommended to minimise torsional effects.  
The neutral is NOT connected to the frame.  
The main stator winding has leads brought out to the  
terminals in the terminal box.  
No earth connections are made on the  
generator  
regulations for earthing must be made.  
Incorrect earthing or protection  
and  
reference  
to  
site  
Belt driven applications of two bearing generators require the  
pulley diameter and design to be such that the side load or  
force applied to the shaft is central to the extension and does  
not exceed the values given in the table below : -  
arrangements can result in personal  
injury or death.  
Warning !  
Fault current curves (decrement curves), together with  
generator reactance data, are available on request to assist  
the system designer to select circuit breakers, calculate fault  
currents and ensure discrimination within the load network.  
Shaft  
Extension  
mm  
Side Load  
Frame  
kgf  
408  
510  
N
Incorrect  
installation,  
service  
or  
UC22  
UC27  
4000  
5000  
110  
140  
replacement of parts can result in severe  
personal injury or death, and/or  
equipment damage. Service personnel  
must be qualified to perform electrical  
and mechanical service.  
In instances where shaft extensions greater than specified in  
the table have been supplied reference must be made to the  
factory for appropriate loadings.  
Warning !  
Alignment of single bearing generators is critical and vibration  
can occur due to the flexing of the flanges between the engine  
and generator. As far as the generator is concerned the  
maximum bending moment at this point must not exceed  
1000ft.lb.  
(140kgm).  
A
substanial  
bedplate  
with  
engine/generator mounting pads is required.  
It is expected that the generator will be incorporated into a  
generating set operating in an environment, where the  
maximum shock load experienced by the generator will not  
exceed 3g. in any plane. If shock loads in excess of 3g are to  
be encountered, anti-vibration mountings must be  
incorporated into the generating set to ensure they absorb the  
excess.  
The maximum bending moment of the engine flange must be  
checked with the engine manufacturer.  
Generators can be supplied without a foot, providing the  
option for customers own arrangement. See SECTION 4.2.1  
for assembly procedure.  
Torsional vibrations occur in all engine-driven shaft systems  
and may be of a magnitude to cause damage at certain  
critical speeds.  
It is therefore necessary to consider the torsional vibration  
effect on the generator shaft and couplings. It is the  
responsibility of the generator set manufacturer to ensure  
compatibility, and for this purpose drawings showing the shaft  
dimensions and rotor inertias are available for customers to  
forward to the engine supplier. In the case of single bearing  
generators coupling details are included.  
Important ! Torsional incompatibility and/or excessive  
vibration levels can cause damage or failure  
of generator and/or engine components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
INSTALLATION - PART 1  
Once the bar is removed, to couple the rotor to engine, the  
4.1 LIFTING  
Warning !  
rotor is free to move in the frame, and care is needed during  
coupling and alignment to ensure the frame is kept in the  
horizontal plane.  
Incorrect lifting or inadequate lifting  
capacity can result in severe personal  
injury or equipment damage. MINIMUM  
LIFTING CAPACITY REQUIRED IS 750Kg.  
Generator lifting lugs should NOT be used  
for lifting the complete generator set.  
Generators fitted with a PMG excitation system are not fitted  
with retaining bar. Refer to frame designation to verify  
generator type (subsection 1.2)  
Two lifting lugs are provided for use with a shackle and pin  
type lifting aid. Chains of suitable length and lifting capacity  
must be used. Lifting points are designed to be as close to the  
centre of gravity of the generator as possible, but due to  
design restrictions it is not possible to guarantee that the  
generator frame will remain horizontal while lifting. Care is  
therefore needed to avoid personal injury or equipment  
damage. The correct lifting arrangement is shown on the label  
attached to the lifting lug. (See sample below).  
4.2 ASSEMBLY  
During the assembly of the generator to the engine it will be  
necessary firstly to carefully align, then rotate, the combined  
generator rotor - engine crankshaft assembly, as part of the  
construction process, to allow location, insertion and  
tightening of the coupling bolts. This requirement to rotate the  
combined assemblies exists for both single and two bearing  
units.  
During the assembly of single bearing units it is necessary to  
align the generator's coupling holes with the engine flywheel  
holes; it is suggested that two diametrically opposite location  
dowel pins are fitted to the engine flywheel, over which the  
generator coupling can slide into final location into the engine  
flywheel spigot recess. The dowels must be removed and  
replaced by coupling bolts before the final bolt tightening  
sequence.  
While fitting and tightening the coupling bolts it will be  
necessary to rotate the engine crankshaft - generator rotor  
assembly. Care should be taken to ensure that rotation is  
carried out in an approved manner that ensures safe working  
practice when reaching inside the machine to insert or tighten  
coupling bolts, and that no component of the assembly is  
damaged by nonapproved methods of assembly rotation.  
Engine manufacturers have available a proprietary tool or  
acility designed to enable manual rotation of the crankshaft  
assembly. This must always be used, having been  
engineered as an approved method of assembly rotation,  
engaging the manually driven pinion with the engine flywheel  
starter ring-gear.  
Before working inside the generator,  
during the aligning and fitting of coupling  
Caution !  
bolts, care should be taken to lock the  
assembly to ensure there is no possibility  
of rotational movement.  
Single bearing generators are supplied fitted with a rotor  
retaining bar at the non-drive end of the shaft.  
4.2.1 NO FOOT OPTION  
To remove retaining bar :  
Generators can be supplied without a foot providing the option  
for customers own arrangement. For details of mounting this  
arrangement, see the general arrangement drawing supplied  
with the generator. Alternatively refer to the STAMFORD  
factory for a copy of the latest general arrangement drawing  
showing the 'NO FOOT OPTION' appropriate to your  
generator.  
1. Remove the four screws holding the sheet metal cover at  
the non drive end and remove cover  
2. Remove central bolt holding the retaining bar to the shaft  
3. Refit sheet metal cover.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Offer the a.c. generator to engine and engage both  
coupling discs and housing spigots at the same time,  
finally pulling home by using the housing and coupling  
bolts. Use heavy gauge washers between bolt head and  
discs on disc to flywheel bolts.  
4.2.2 TWO BEARING GENERATORS  
A flexible coupling should be fitted and aligned in accordance  
with the coupling manufacturer's instruction. If a close  
coupling adaptor is used the alignment of machined faces  
must be checked by offering the generator up to the engine.  
Shim the generator feet if necessary. Ensure adaptor guards  
are fitted after generator/engine assembly is complete. Open  
coupled sets require a suitable guard, to be provided by the  
set builder. In the case of belt driven generators, ensure  
alignment of drive and driven pulleys to avoid axial load on  
the bearings. Screw type tensioning devices are  
recommended to allow accurate adjustment of belt tension  
whilst maintaining pully alignment. Side loads should not  
exceed values given in SECTION 3. Belt and pulley guards  
must be provided by the set builder.  
1. Tighten coupling disc to flywheel. Refer to engine manual  
for torque setting of disc to flywheel bolts.  
1. Remove wooden wedges.  
Incorrect guarding and/or generator  
Caution !  
alignment can result in personal injury  
and/or equipment damage.  
4.3 EARTHING  
Important ! Incorrect belt tensioning will result in  
excessive bearing wear.  
The generator frame should be solidly bonded to the  
generating set bedplate. If antivibration mounts are fitted  
between the generator frame and its bedplate a suitably rated  
earth conductor (normally one half of the cross sectional area  
of the main line cables) should bridge across the antivibration  
mount.  
Incorrect guarding and/or generator  
alignment can result in personal injury  
and/or equipment damage.  
Caution !  
4.2.3 SINGLE BEARING GENERATORS  
Alignment of single bearing generators is critical. If necessary  
shim the generator feet to ensure alignment of the machined  
surfaces.  
Refer to local regulations to ensure that  
the correct earthing procedure has been  
followed.  
Warning !  
For transit and storage purposes the generator frame spigot  
and rotor coupling plates have been coated with a rust  
preventative.  
4.4 PRE-RUNNING CHECKS  
4.4.1 INSULATION CHECK  
This MUST BE removed before assembly to engine.  
A practical method for removal of this coating is to clean the  
mating surface areas with a de-greasing agent based on a  
petroleum solvent.  
Before starting the generating set, both after completing  
assembly and after installation of the set, test the insulation  
resistance of windings. The AVR should be disconnected  
during this test. A 500V Megger or similar instrument should  
be used. Disconnect any earthing conductor connected  
between neutral and earth and megger an output lead  
terminal U, V or W to earth. The insulation resistance reading  
should be in excess of 5MΩ to earth. Should the insulation  
resistance be less than 5MΩ the winding must be dried out as  
detailed in the Service and Maintenance section of this  
Manual.  
Care should be taken not to allow any  
cleaning agent to come into prolonged  
contact with skin.  
Caution !  
The sequence of assembly to the engine should generally be  
as follows:  
1. On the engine check the distance from the coupling  
mating face on the flywheel to the flywheel housing  
mating face. This should be within +/-0.5mm of nominal  
dimension. This is necessary to ensure that a thrust is not  
applied to the a.c. generator bearing or engine bearing.  
Important ! The windings have been H.V. tested during  
manufacture and further H.V. testing may  
degrade the insulation with consequent  
reduction in operating life. Should it be  
necessary to demonstrate H.V. testing, for  
customer acceptance, the tests must be  
carried out at reduced voltage levels i.e.  
Test Voltage= 0.8 (2 X Rated Voltage + 1000)  
1. Check that the bolts securing the flexible plates to the  
coupling hub are tight and locked into position. Torque  
tightening is 24.9kgfm (244Nm; 180 lb ft).  
2a. UCD224 Only  
Torque tightening is 15.29 kgfm (150Nm; 110 lb ft).  
1. Remove covers from the drive end of the generator to  
gain access to coupling and adaptor bolts.  
1. Check that coupling discs are concentric with adaptor  
spigot. This can be adjusted by the use of tapered  
wooden wedges between the fan and adaptor.  
Alternatively the rotor can be suspended by means of a  
rope sling through the adaptor opening.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.2 DIRECTION OF ROTATION  
The generator is supplied to give a phase sequence of U V W  
with the generator running clockwise looking at the drive end  
(unless otherwise specified at the time of ordering). If the  
generator phase rotation has to be reversed after the  
generator has been despatched apply to factory for  
appropriate wiring diagrams.  
UCI224, UCI274, UCM224, UCM274  
Machines are fitted with bi-directional fans and are suitable for  
running in either direction of rotation.  
UCD224, UCD274  
Machines are fitted with uni-directional fans and are suitable  
for running in one direction only.  
4.4.3 VOLTAGE AND FREQUENCY  
Check that the voltage and frequency levels required for the  
generating set application are as indicated on the generator  
nameplate.  
4.4.4.2 TYPE AS440 AVR  
The following 'jumper' connections on the AVR should be  
checked to ensure they are correctly set for the generating set  
application.  
Three phase generators normally have a 12 ends out  
reconnectable winding. If it is necessary to reconnect the  
stator for the voltage required, refer to diagrams in the back of  
this manual.  
Refer to Fig. 2 for location of selection links.  
1. Frequency selection terminals  
50Hz operation  
60Hz operation  
LINK C-50  
LINK C-60  
4.4.4 AVR SETTINGS  
To make AVR selections and adjustments remove the AVR  
cover and refer to 4.4.4.1, 4.4.4.2, 4.4.4.3, 4.4.4.4 or 4.4.4.5  
depending upon type of AVR fitted. Reference to the  
generator nameplate will indicate AVR type (SX460, SX440,  
SX421, MX341 or MX321).  
2. Stability selection terminals  
Frame UC22  
LINK A-C  
LINK B-C  
Frame UC27  
3. Sensing selection terminals  
LINK 2-3  
LINK 4-5  
LINK 6-7  
Most of the AVR adjustments are factory set in positions  
which will give satisfactory performance during initial running  
tests. Subsequent adjustment may be required to achieve  
optimum performance of the set under operating conditions.  
Refer to 'Load Testing' section for details.  
4. Excitation Interruption Link  
LINK K1-K2  
4.4.4.1 TYPE SX460 AVR  
The following 'jumper' connections on the AVR should be  
checked to ensure they are correctly set for the generating set  
application. Refer to Fig. 1 for location of selection links.  
1. Frequency selection  
50Hz operation  
60Hz operation  
LINK C-50  
LINK C-60  
2. External hand trimmer selection  
No external hand trimmer LINK 1-2  
External hand trimmer required -  
REMOVE LINK 1-2 and  
connect trimmer across  
terminals 1 and 2.  
3. AVR Input Selection  
High voltage  
Low voltage  
(220/240V) Input NO LINK  
(110/120V) Input LINK 3-4  
Refer to diagram in the back of this manual to determine  
wiring.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.4.5 TYPE MX321 AVR  
The following 'jumper' connections on the AVR should be  
checked to ensure they are correctly set for the generating set  
application.  
4.4.4.4 TYPE MX341 AVR  
The following 'jumper' connections on the AVR should be  
checked to ensure they are correctly set for the generating set  
application.  
Refer to Fig. 5 for location of setting links.  
Refer to Fig. 4 for location of setting links.  
Fig. 5  
1. Frequency selection terminals  
50Hz operation LINK 2-3  
1. Frequency selection terminals  
60Hz operation LINK 1-3  
50Hz operation  
60Hz operation  
LINK 2-3  
LINK 1-3  
2. Stability selection terminals  
Frame UC22 LINK A-C  
2. Stability selection terminals  
Frame UC22  
Frame UC27 LINK B-C  
LINK A-C  
LINK B-C  
Frame UC27  
3. Sensing selection terminals *  
LINK 2-3  
LINK 4-5  
LINK 6-7  
3. Terminals K1 - K2  
Excitation circuit breaker closed.  
If this option not fitted, K1 - K2 linked at auxiliary terminal  
block.  
4. Excitation Interruption Link  
LINK K1-K2  
Fig. 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
voltage is reached. Refer to Fig. 6a, 6b, 6c, 6d or 6e for  
control potentiometer location.  
4.4.5 TRANSFORMER CONTROLLED EXCITATION  
SYSTEM (Series 5)  
Important ! Do not increase the voltage above the rated  
generator voltage shown on the generator  
nameplate.  
This control system is identified with the digit 5 as the last digit  
of the frame size quoted on the nameplate.  
The excitation control is factory set for the specific voltage  
shown on the nameplate and requires no adjustment.  
The STABILITY control potentiometer will have been pre-set  
and should normally not require adjustment, but should this  
be required, usually identified by oscillation of the voltmeter,  
refer to Fig. 6a, 6b, 6c, 6d or 6e for control potentiometer  
location and proceed as follows :-  
4.5 GENERATOR SET TESTING  
During testing it may be necessary to  
remove covers to adjust controls exposing  
'live' terminals or components. Only  
personnel qualified to perform electrical  
service should carry out testing and/or  
1. Run the generating set on no-load and check that speed  
is correct and stable  
2. Turn the STABILITY control potentiometer clockwise,  
then turn slowly anti-clockwise until the generator voltage  
starts to become unstable.  
adjustments.  
Warning !  
4.5.1 TEST METERING/CABLING  
The correct setting is slightly clockwise from this position (i.e.  
where the machine volts are stable but close to the unstable  
region).  
Connect any instrument wiring and cabling required for initial  
test purposes with permanent or spring-clip type connectors.  
Minimum instrumentation for testing should be line - line or  
line to neutral voltmeter, Hz meter, load current metering and  
kW meter. If reactive load is used a power factor meter is  
desirable.  
Important ! When fitting power cables for load testing  
purposes, ensure cable voltage rating is at  
least equal to the genrator rated voltage.  
The load cable termination should be placed  
on top of the winding lead termination and  
clamped with the nut provided.  
Check that all wiring terminations for  
internal or external wiring are secure, and  
fit all terminal box covers and guards.  
Failure to secure wiring and/or covers may  
result in personal injury and/or equipment  
failure.  
Caution !  
4.6 INITIAL START-UP  
During testing it may be necessary to  
remove covers to adjust controls exposing  
'live' terminals or components. Only  
personnel qualified to perform electrical  
service should carry out testing and/or  
adjustments. Refit all access covers after  
adjustments are completed.  
Warning !  
On completion of generating set assembly and before starting  
the generating set ensure that all engine manufacturer's  
prerunning procedures have been completed, and that  
adjustment of the engine governor is such that the generator  
will not be subjected to speeds in excess of 125% of the rated  
speed.  
Important ! Overspeeding of the generator during initial  
setting of the speed governor can result in  
damage  
to  
the  
generator  
rotating  
components.  
In addition remove the AVR access cover (on AVR controlled  
generators) and turn VOLTS control fully anti-clockwise. Start  
the generating set and run on no-load at nominal frequency.  
Slowly turn VOLTS control potentiometer clockwise until rated  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.7 LOAD TESTING  
During testing it may be necessary to  
remove covers to adjust controls  
exposing 'live' terminals or components.  
Only personnel qualified to perform  
electrical service should carry out testing  
and/or adjustments. Refit all access  
covers after adjustments are completed.  
Warning !  
4.7.1 AVR CONTROLLED GENERATORS – AVR  
ADJUSTMENTS  
Refer to Fig. 6a, 6b, 6c, 6d or 6e for control potentiometer  
locations.  
Having adjusted VOLTS and STABILITY during the initial  
startup procedure, other AVR control functions should not  
normally need adjustment.  
If however, poor voltage regulation on-load or voltage  
collapse is experienced, refer to the following paragraphs on  
each function to a) check that the symptoms observed do  
indicate adjustment is necessary, and b) to make the  
adjustment correctly.  
4.7.1.1 UFRO (Under Frequency Roll Off) (AVR  
Types SX460, SX440, SX421, MX341 and MX321)  
The AVR incorporates an underspeed protection circuit which  
gives a voltage/speed (Hz) characteristic as shown :  
Fig. 7  
The UFRO control potentiometer sets the "knee point".  
Symptoms of incorrect setting are a) the light emitting diode  
(LED) indicator, just above the UFRO Control potentiometer,  
being permanently lit when the generator is on load, and b)  
poor voltage regulation on load, i.e. operation on the sloping  
part of the characteristic.  
Clockwise adjustment lowers the frequency (speed) setting of  
the "knee point" and extinguishes the LED. For Optimum  
setting the LED should illuminate as the frequency falls just  
below nominal frequency, i.e. 47Hz on a 50Hz generator or  
57Hz on a 60Hz generator.  
Important ! With AVR Types MX341 and MX321. If the  
LED is illuminated and no output voltage is  
present, refer to EXC TRIP and/or OVER/V  
sections below.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.7.1.2 EXC TRIP (Excitation Trip)  
AVR Types MX341 and MX321  
DIP  
AVR Types SX421, MX341 and MX321  
An AVR supplied from a permanent magnet generator  
inherently delivers maximum excitation power on a line to line  
or line to neutral short circuit or large overload. In order to  
protect the generator windings the AVR incorporates an over  
excitation circuit which detects high excitation and removes it  
after a pre-determined time, i.e. 8-10 seconds.  
AVR Types SX421, MX341 and MX321  
The dip function control potentiometer adjusts the slope of the  
voltage/speed (Hz) characteristic below the knee point as  
shown below :  
Symptoms of incorrect setting are the generator output  
collapses on load or small overload, and the LED is  
permanently illuminated.  
The correct setting is 70 volts +/-5% between terminals X and  
XX.  
4.7.1.3 OVER/V (Over Voltage)  
AVR Type SX421, MX321  
Over voltage protection circuitry is included in the AVR to  
remove generator excitation in the event of loss of AVR  
sensing input.  
The MX321 has both internal electronic de-excitation and  
provision of a signal to operate an external circuit breaker.  
Fig. 8  
The SX421 only provides a signal to operate an external  
breaker, which MUST be fitted if over voltage protection is  
required.  
DWELL  
AVR Type MX321  
Incorrect setting would cause the generator output voltage to  
collapse at no-load or on removal of load, and the LED to be  
illuminated.  
The dwell function introduces a time delay between the  
recovery of voltage and recovery of speed.  
The purpose of the time delay is to reduce the generator kW  
below the available engine kW during the recovery period,  
thus allowing an improved speed recovery.  
The correct setting is 300 volts +/-5% across terminals E1,  
E0. Clockwise adjustment of the OVER/V control  
potentiometer will increase the voltage at which the circuit  
operates.  
Again this control is only functional below the "knee point", i.e.  
if the speed stays above the knee point during load switching  
there is no effect from the DWELL function setting.  
4.7.1.4 TRANSIENT LOAD SWITCHING  
ADJUSTMENTS  
AVR Types SX421, MX341 and MX321  
Clockwise adjustment gives increased recovery time.  
The additional function controls of DIP and DWELL are  
provided to enable the load acceptance capability of the  
generating set to be optimised. The overall generating set  
performance depends upon the engine capability and  
governor response, in conjunction with the generator  
characteristics.  
It is not possible to adjust the level of voltage dip or recovery  
independently from the engine performance, and there will  
always be a 'trade off' between frequency dip and voltage dip.  
The graphs shown above are representations only, since it is  
impossible to show the combined effects of voltage regulator  
and engine governor performance.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.7.1.5 RAMP  
AVR Type MX321  
The RAMP potentiometer enables adjustment of the time  
taken for the generator's initial build up to normal rated  
voltage during each start and run up to speed. The  
potentiometer is factory set to give a ramp time of three  
seconds, which is considered to be suitable for most  
applications. This time can be reduced to one second by  
turning the pot. fully counter clockwise, and increased to eight  
seconds by turning the pot. fully clockwise.  
4.7.2  
TRANSFORMER  
CONTROLLED  
GENERATORS - TRANSFORMER ADJUSTMENT  
Normally no adjustment is required but should the no-load  
voltage and/or on-load voltage be unacceptable, adjustment  
of the transformer air gap can be made as follows.  
Stop the generator. Remove transformer cover box. (Normally  
left hand side of the terminal box when viewed from the non  
drive end).  
Slacken the three transformer mounting bolts along the top of  
the transformer.  
Start the set with a voltmeter connected across the main  
output terminals.  
Adjust the air gap between the transformer top lamination  
section and the transformer limbs to obtain required voltage  
on no-load. Slightly tighten the three mounting bolts. Switch  
load 'on' and 'off' two or three times. Application of load will  
normally raise the voltage setting slightly. With the load 'off'  
recheck the no-load voltage.  
Readjust air gap and finally tighten mounting bolts.  
Refit the access cover.  
Failure to refit covers can result in  
operator personal injury or death.  
Warning !  
4.8 ACCESSORIES  
Refer to the "ACCESSORIES" - Section 6 of this Manual for  
setting up procedures related to generator mounted  
accessories.  
If there are accessories for control panel mounting supplied  
with the generator refer to the specific accessory fitting  
procedures inserted inside the back cover of this book.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5  
INSTALLATION - PART 2  
Reference to local electricity regulations  
or safety rules should be made to ensure  
correct earthing procedures have been  
followed.  
5.1 GENERAL  
Caution !  
The extent of site installation will depend upon the generating  
set build, e.g. if the generator is installed in a canopied set  
with integral switchboards and circuit breaker, on site  
installation will be limited to connecting up the site load to the  
generating set output terminals . In this case reference should  
be made to the generating set manufacturer's instruction book  
and any pertinent local regulations. If the generator has been  
installed on a set without switchboard or circuit breaker the  
following points relating to connecting up the generator should  
be noted.  
5.4 PROTECTION  
It is the responsibility of the end user and his  
contractors/subcontractors to ensure that the overall system  
protection meets the needs of any inspectorate, local  
electricity authority or safety rules, pertaining to the site  
location.  
To enable the system designer to achieve the necessary  
protection and/or discrimination, fault current curves are  
available on request from the factory, together with generator  
reactance values to enable fault current calculations to be  
made.  
5.2 GLANDING  
The terminal box is most conveniently glanded on either the  
right or left hand side. Both panels are removable for  
drilling/punching to suit glands/or glanding boxes. If single  
core cables are taken through the terminal box side panel an  
insulated or non-magnetic gland plate should be fitted.  
Incorrect installation and/or protective  
systems can result in personal injury  
and/or equipment damage. Installers must  
Incoming cables should be supported from either below or  
above the box level and at a sufficient distance from the  
centre line of the generating set so as to avoid a tight radius  
at the point of entry into the terminal box panel, and allow  
movement of the generator set on its anti-vibration mountings  
without excessive stress on the cable.  
be  
qualified  
to  
perform  
electrical  
installation work.  
Warning !  
5.5 COMMISSIONING  
Ensure that all external cabling is correct and that all the  
generating set manufacturer's pre-running checks have been  
carried out before starting the set.  
Before making final connections, test the insulation resistance  
of the windings. The AVR should be disconnected during this  
test.  
The generator AVR controls will have been adjusted during  
the generating set manufacturer's tests and should normally  
not require further adjustment.  
A 500V Megger or similar instrument should be used. Should  
the insulation resistance be less than 5MΩ the windings must  
be dried out as detailed in the Service and Maintenance  
section of this manual.  
Should malfunction occur during commissioning refer to  
Service and Maintenance section 'Fault Finding' procedure  
(subsection 7.4).  
When making connections to the terminals the incoming cable  
termination should be placed on top of the winding lead  
termination(s) and clamped with the nut provided.  
Important ! To avoid the possibility of swarf entering  
any electrical components in the terminal  
box, panels must be removed for drilling.  
5.3 EARTHING  
The neutral of the generator is not bonded to the generator  
frame as supplied from the factory. An earth terminal is  
provided inside the terminal box adjacent to the main  
terminals. Should it be required to operate with the neutral  
earthed a substantial earth conductor (normally equivalent to  
one half of the section of the line conductors) must be  
connected between the neutral and the earth terminal inside  
the terminal box. Additional earth terminals are provided on  
the generator feet. These should be already bonded to the  
generating set bedplate by the generating set builder, but will  
normally be required to be connected to the site earth system.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 6  
ACCESSORIES  
Generator control accessories may be fitted, as an option, in  
It is important to recognise that :  
the generator terminal box. If fitted at the time of supply, the  
wiring diagram(s) in the back of this book shows the  
connections. When the options are supplied separately, fitting  
instructions are provided with the accessory.  
1. True kW are derived from the engine, and speed  
governor characteristics determine the kW sharing  
between sets  
The following matrix indicates availability of accessories with  
the differing AVRs.  
and  
2. kVAr are derived from the generator, and excitation  
control characteristics determine the kVAr sharing.  
Reference should be made to the generating set  
manufacturer's instructions for setting the governor  
controls.  
Note the SX460 is not suitable for operation with accessories.  
Paralleling  
Droop or  
Astatic  
Manual  
Voltage  
Regulator  
Var/PF  
Control  
Current  
Limit  
AVR Model  
SX460  
AS440  
MX341  
MX321  
X
O
O
O
X
O
O
O
X
O
O
O
X
6.2.1 DROOP  
The most commonly used method of kVAr sharing is to create  
a generator voltage characteristic which falls with decreasing  
power factor (increasing kVAr). This is achieved with a current  
transformer (C.T.) which provides a signal dependent on  
current phase angle (i.e. power factor) to the AVR.  
6.1 REMOTE VOLTAGE ADJUST (ALL AVR TYPES)  
A remote voltage adjust (hand trimmer) can be fitted.  
The current transformer has a burden resistor on the AVR  
board, and a percentage of the burden resistor voltage is  
summed into the AVR circuit. Increasing droop is obtained by  
turning the DROOP control potentiometer clockwise.  
SX460  
Remove link 1-2 on the AVR and  
connect adjuster to terminals 1 and 2.  
AS440  
Remove link 1-2 at the auxiliary  
terminals  
and connect adjuster to terminals 1  
and 2.  
The diagrams below indicate the effect of droop in a simple  
two generator system : -  
MX341 and MX321  
6.2 PARALLEL OPERATION  
Understanding of the following notes on parallel operation is  
useful before attempting the fitting or setting of the droop kit  
accessory. When operating in parallel with other generators or  
the mains, it is essential that the phase sequence of the  
incoming generator matches that of the busbar and also that  
all of the following conditions are met before the circuit  
breaker of the incoming generator is closed on to the busbar  
(or operational generator).  
1. Frequency must match within close limits.  
2. Voltages must match within close limits.  
3. Phase angle of voltages must match within close limits.  
A
variety of techniques, varying from simple  
synchronising lamps to fully automatic synchronisers, can  
be used to ensure these conditions are met.  
Important ! Failure to meet conditions 1, 2, and 3 when  
closing the cricuit breaker, will generate  
excessive  
mechanical  
and  
electrical  
stresses, resulting in equipment damage.  
Once connected in parallel a minimum instrumentation level  
per generator of voltmeter, ammeter, wattmeter (measuring  
total power per generator), and frequency meter is required in  
order to adjust the engine and generator controls to share kW  
in relation to engine ratings and kVAr in relation to generator  
ratings.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Generally 5% droop at full load current zero p.f. is sufficient to  
ensure kVAr sharing.  
Should the generator be required to be converted from  
standard droop to 'astatic' control, diagrams are available on  
request.  
If the droop accessory has been supplied with the generator it  
will have been tested to ensure correct polarity and set to a  
nominal level of droop. The final level of droop will be set  
during generating set commissioning.  
The setting procedure is exactly the same as for DROOP.  
(Subsection 6.2.1.1)  
Important ! When using this connection arrangement a  
shorting switch is required across each C.T.  
burden (terminals S1 and S2.)The switch  
must be closed a) when a generating set is  
not running and b) when a generating set is  
selected for single running.  
The following setting procedure will be found to be helpful.  
6.2.1.1 SETTING PROCEDURE  
Depending upon available load the following settings should  
be used - all are based on rated current level.  
6.3 MANUAL VOLTAGE REGULATOR (MVR) -  
MX341 and MX321 AVR  
0.8 P.F. LOAD (at full load current)  
Zero P.F. LOAD (at full load current) SET DROOP TO 5%  
SET DROOP TO 3%  
This accessory is provided as an 'emergency' excitation  
system, in the event of an AVR failure.  
Setting the droop with low power factor load is the most  
accurate. Run each generator as a single unit at rated  
frequency or rated frequency + 4% depending upon type of  
governor and nominal voltage. Apply available load to rated  
current of the generator. Adjust 'DROOP' control  
potentiometer to give droop in line with above table.  
Clockwise rotation increases amount of droop. Refer to Fig  
9a, 9b, 9c or 9d for potentiometer locations.  
Powered from the PMG output the unit is manually set, but  
automatically controls the excitation current, independent of  
generator voltage or frequency.  
The unit is provided with 'MANUAL', 'OFF', 'AUTO' switching  
facility.  
Note 1)  
'MANUAL'  
- position connects the exciter field to the MVR output.  
Generator output is then controlled by the operator adjusting  
the excitation current.  
Reverse polarity of the C.T. will raise the generator voltage  
with load. The polarities S1-S2 shown on the wiring diagrams  
are correct for clockwise rotation of the generator looking at  
the drive end. Reversed rotation requires S1-S2 to be  
reversed.  
'OFF'  
- disconnects the exciter field from both MVR and the normal  
AVR.  
Note 2)  
'AUTO'  
The most important aspect is to set all generators equal. The  
precise level of droop is less critical.  
- connects the exciter field to the normal AVR and the  
generator output is controlled at the pre-set voltage under  
AVR control.  
Note 3)  
A generator operated as a single unit with a droop circuit set  
at rated load 0.8 power factor is unable to maintain the usual  
+/-0.5% regulation. A shorting switch can be connected  
across S1-S2 to restore regulation for single running.  
switching mode of operation should be carried out with the  
generator set stationary to avoid voltage surges on the  
connected load, although neither the MVR nor AVR will be  
damaged should the switching be carried out with the set  
running.  
Important ! LOSS OF FUEL to an engine can cause its  
generator to motor with consequent damage  
to the generator windings. Reverse power  
relays should be fitted to trip main circuit  
breaker.  
6.4 OVERVOLTAGE DE-EXCITATION BREAKER  
MX321 AVR  
This accessory provides positive interruption of the excitation  
power in the event of overvoltage due to loss of sensing or  
internal AVR faults including the output power device.  
LOSS OF EXCITATION to the generator can  
result in large current oscillations with  
consequent damage to generator windings.  
Excitation loss detection equipment should  
be fitted on trip main circuit breaker.  
With the MX321 AVR this accessory is supplied loose for  
fitting in the control panel.  
6.2.2 ASTATIC CONTROL  
Important ! When the circuit breaker is supplied loose,  
the AVR is fitted with a link on terminals K1-  
K2 to enable operation of the AVR. When  
connecting the circuit breaker this link must  
be removed.  
The 'droop' current transformer can be used in a connection  
arrangement which enables the normal regulation of the  
generator to be maintained when operating in parallel. This  
feature is only supplied from the factory as a fitted droop kit,  
however, if requested at the time of order, the diagrams inside  
the back cover of this book will give the necessary site  
connections. The end user is required to provide a shorting  
switch for the droop current transformer secondary.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4.1 RESETTING THE BREAKER  
In the event of operation of the circuit breaker, indicated by  
loss of generator output voltage, manual resetting is required.  
When in the "tripped" state the circuit breaker switch lever  
shows "OFF". To reset move the switch lever to the position  
showing "ON".  
When fitted in the generator, access to the breaker is gained  
by removal of the AVR access cover.  
Terminals which are LIVE with the  
generating set running are exposed when  
the AVR access cover is removed.  
Resetting of the circuit breaker MUST be  
carried out with the generating set  
Danger !  
stationary, and engine starting circuits  
disabled.  
The circuit breaker is mounted on the AVR mounting bracket  
either to the left or to the right of the AVR depending upon  
AVR position. After resetting the circuit breaker replace the  
AVR access cover before restarting the generating set.  
Should resetting of the circuit breaker not restore the  
generator to normal operation, refer to subsection 7.5.  
6.5 CURRENT LIMIT - MX321 AVR  
These accessories work in conjunction with the AVR circuits  
to provide an adjustment to the level of current delivered into  
a fault. One current transformer (CT) per phase is fitted to  
provide current limiting on any line to line or line to neutral  
fault.  
Note: The W phase CT can also provide "DROOP". Refer to  
6.2.1.1 for setting droop independent of current limit.  
Adjustment means is provided with the "I/LIMIT" control  
potentiometer on the AVR. Refer to Fig. 9d for location. If  
current limit transformers are supplied with the generator the  
limit will be set in accordance with the level specified at the  
time of order, and no further adjustment will be necessary.  
However, should the level need to be adjusted, refer to the  
setting procedure given in 6.5.1.  
6.5.1 SETTING PROCEDURE  
Run the generating set on no-load and check that engine  
governor is set to control nominal speed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Stop the generating set. Remove the link between terminals  
K1-K2 at the auxiliary terminal block and connect a 5A switch  
across the terminals K1-K2.  
Turn the "I/LIMIT" control potentiometer fully anticlockwise.  
Short circuit the stator winding with a bolted 3 phase short at  
the main terminals. An AC current clip-on ammeter is required  
to measure the winding lead current.  
With the switch across K1-K2 open start the generating set.  
Close the switch across K1-K2 and turn the "I/LIMIT" control  
potentiometer clockwise until required current level is  
observed on the clip-on ammeter. As soon as correct setting  
is achieved open the K1-K2 switch.  
Should the current collapse during the setting procedure, the  
internal protective circuits of the AVR will have operated. In  
this event shut down the set and open the K1-K2 switch.  
Restart the set and run for 10 minutes with K1-K2 switch  
open, to cool the generator windings, before attempting to  
resume the setting procedure.  
Important ! Failure to carry out the correct COOLING  
procedure, may cause overheating and  
consequent damage to the generator  
windings.  
6.6 POWER FACTOR CONTROLLER (PFC3)  
This accessory is primarily designed for those generator  
applications where operation in parallel with the mains supply  
is required.  
Protection against loss of mains voltage or generator  
excitation is not included in the unit and the system designer  
must incorporate suitable protection.  
The electronic control unit requires both droop and kVAr  
current transformers. When supplied with the generator,  
wiring diagrams inside the back cover of this manual show the  
connections and the additional instruction leaflet provided  
gives details of setting procedures for the power factor  
controller (PFC3).  
The unit monitors the power factor of the generator current  
and adjusts excitation to maintain the power factor constant.  
This mode can also be used to control the power factor of the  
mains if the point of current monitoring is moved to the mains  
cables. Refer to the factory for appropriate details.  
It is also possible to operate the unit to control kVAr of the  
generator if required. Refer to the factory for appropriate  
details.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7  
SERVICE AND MAINTENANCE  
As part of routine maintenance procedures, periodic attention  
Any temporarily reduction in IR values can be restored to  
expected values by following one of the drying out  
procedures.  
to winding condition (particularly when generators have been  
idle for a long period) and bearings is recommended. (Refer  
to subsections 7.1 and 7.2 respectively).  
7.1.1 WINDING CONDITION ASSESSMENT  
The AVR should be disconnected and the  
When generators are fitted with air filters regular inspection  
and filter maintenance is required. (Refer to subsection 7.3).  
Caution !  
Resistance Temperature Detector (R.T.D.)  
leads grounded during this test.  
7.1 WINDING CONDITION  
Service and fault finding procedures  
present hazards which can result in severe  
personal injury or death. Only personnel  
qualified to perform electrical and  
mechanical service should carry out these  
procedures. Ensure engine starting  
The condition of the windings can be assessed by  
measurement of insulation resistance [IR] between phase to  
phase, and phase to earth.  
Measurement of winding insulation should be carried out : -  
1. As part of a periodic maintenance plan.  
circuits are disabled before commencing  
Warning !  
service or maintenance procedures.  
Isolate any anti-condensation heater  
supply.  
2. After prolonged periods of shutdown.  
3. When low insulation is suspected, e.g. damp or wet  
windings.  
Guidance of Typical Insulation Resistance [IR]  
Values  
Care should be taken when dealing with windings that are  
suspected of being excessively damp or dirty. The initial  
measurement of the [IR] Insulation Resistance should be  
The following is offered as general information about IR  
values and is aimed at providing guidance about the typical IR  
values for generators from new through to the point of  
refurbishment.  
established using  
a
low voltage (500V) megger type  
instrument. If manually powered the handle should initially be  
turned slowly so that the full test voltage will not be applied,  
and only applied for long enough to very quickly assess the  
situation if low values are suspected or immediately indicated.  
New Machines  
The generators Insulation Resistance, along with many other  
critical factors, will have been measured during the alternator  
manufacturing process. The generator will have been  
transported with an appropriate packaging suitable for the  
method of delivery to the Generating Set assemblers works.  
Where we expect it to be stored in a suitable location  
protected from adverse environmental conditions.  
Full megger tests or any other form of high voltage test should  
not be applied until the windings have been dried out and if  
necessary cleaned.  
Procedure for Insulation Testing  
Disconnect all electronic components, AVR, electronic  
protection equipment etc. Ground the [RTD's] Resistance  
Temperature Detection devices if fitted. Short out the diodes  
on the rotating diode assembly. Be aware of all components  
connected to the system under test that could cause false  
readings or be damaged by the test voltage.  
However, absolute assurance that the generator will arrive at  
the Gen-set production line with IR values still at the factory  
test levels of above 100 MΩ cannot be guaranteed.  
At Generating Set Manufacturers Works  
Carry out the insulation test in accordance with the ‘operating  
instructions for the test equipment.  
The generator should have been transported and stored such  
that it will be delivered to the assembly area in a clean dry  
condition. If held in appropriate storage conditions the  
generator IR value should typically be 25 MΩ.  
The measured value of insulation resistance for all windings  
to earth and phase to phase should be compared with the  
guidance given above for the various 'life stages' of a  
generator. The minimum acceptable value must be greater  
than 1.0 MΩ.  
If the unused/new generators IR values fall below 10 MΩ then  
a drying out procedure should be implemented by one of the  
processes outlined below before being despatched to the end  
customer’s site. Some investigation should be undertaken into  
the storage conditions of the generator while on site.  
If low winding insulation is confirmed use one or more of  
the methods, given below, for drying the winding should  
be carried out.  
Generators in Service  
1. METHODS OF DRYING OUT GENERATORS  
Whilst It is known that a generator will give reliable service  
with an IR value of just 1.0 MΩ. For a relatively new generator  
to be so low it must have been subjected to inappropriate  
operating or storage conditions.  
Cold Run  
Consider a good condition generator that has not been run for  
some time, and has been standing in damp, humid conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
It is possible that simply running the gen set unexcited – AVR  
terminals K1 K2 open circuit - for a period of say 10 minutes  
will sufficiently dry the surface of the windings and raise the IR  
sufficiently, to greater than 1.0 MΩ , and so allow the unit to  
be put into service.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rebuild the genset, replace all covers and re-commission as  
appropriate.  
Blown Air Drying  
Remove the covers from all apertures to allow the escape of  
the water-laden air. During drying, air must be able to flow  
freely through the generator in order to carry off the moisture.  
If the set is not to be run immediately ensure that the  
anticondensation heaters are energised, and retest the  
generator prior to running.  
Direct hot air from two electrical fan heaters of around 1 – 3  
kW into the generator air inlet apertures. Ensure the heat  
source is at least 300mm away from the windings to avoid  
over heating and damage to the insulation.  
TYPICAL DRYING OUT CURVE  
Whichever method is used to dry out the generator the  
resistance should be measured every half-hour and a curve  
plotted as shown. (fig 6.)  
Apply the heat and plot the insulation value at half hourly  
intervals. The process is complete when the parameters  
covered in the section entitled, ‘Typical Drying Out Curve’, are  
met.  
Remove the heaters, replace all covers and re-commission as  
appropriate.  
If the set is not to be run immediately ensure that the  
anticondensation heaters are energised, and retest prior to  
running.  
Short Circuit Method  
NOTE: This process should only be performed by  
competent engineer familiar with safe operating practices  
within and around generator sets of the type in question.  
a
The illustration shows a typical curve for a machine that has  
absorbed a considerable amount of moisture. The curve  
indicates a temporary increase in resistance, a fall and then a  
gradual rise to a steady state. Point ‘A’, the steady state, must  
be greater than 1.0 MΩ. (If the windings are only slightly  
damp the dotted portion of the curve may not appear).  
Ensure the generator is safe to work on, initiate all mechanical  
and electrical safety procedures pertaining to the genset and  
the site.  
For general guidance expect that the typical time to reach  
point 'A' will be :  
Bolt a short circuit of adequate current carrying capacity,  
across the main terminals of the generator. The shorting link  
should be capable of taking full load current.  
1 hour for a BC16/18,  
2 hours for a UC22/27  
3 hours for an HC4,5,6&7  
Drying should be continued after point “A” has been reached  
for at least one hour.  
Disconnect the cables from terminals “X” and “XX” of the  
AVR.  
Connect a variable dc supply to the “X” (positive) and “XX”  
(negative) field cables. The dc supply must be able to provide  
a current up to 2.0 Amp at 0 - 24 Volts.  
It should be noted that as winding temperature increases,  
values of insulation resistance may significantly reduce.  
Therefore, the reference values for insulation resistance can  
only be established with windings at a temperature of  
approximately 20°C.  
Position a suitable ac ammeter to measure the shorting link  
current.  
Set the dc supply voltage to zero and start the generating set.  
Slowly increase the dc voltage to pass current through the  
exciter field winding. As the excitation current increases, so  
the stator current in the shorting link will increase. This stator  
output current level must be monitored, and not allowed to  
exceed 80% of the generators rated output current.  
If the IR value remains below 1.0 MΩ, even after the above  
drying methods have been properly conducted, then a  
Polarisation Index test [PI] should be carried out.  
If the minimum value of 1.0 MΩ for all components cannot be  
achieved rewinding or refurbishment of the generator will be  
necessary.  
After every 30 minutes of this exercise:  
The generator must not be put into service until the  
minimum values can be achieved.  
Stop the generator and switch off the separate excitation  
supply, and measure and record the stator winding IR values,  
and plot the results. The resulting graph should be compared  
with the classic shaped graph. This drying out procedure is  
complete when the parameters covered in the section entitled  
'Typical Drying Out Curve' are met.  
Important ! The short circuit must not be applied with  
the AVR connected in circuit. Current in  
excess of the rated generator current will  
cause damage to the windings.  
Once the Insulation Resistance is raised to an acceptable  
level - minimum value 1.0 MΩ − the dc supply may be  
removed and the exciter field leads “X” and “XX” re-connected  
to their terminals on the AVR.  
After drying out, the insulation resistances should be  
rechecked to verify minimum resistances quoted above are  
achieved.  
On re-testing it is recommended that the main stator  
insulation resistance is checked as follows :-  
Separate the neutral leads  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ground V and W phase and megger U phase to ground  
Ground U and W phase and megger V phase to ground  
Ground U and V phase and megger W phase to ground  
If the minimum value of 1.0MΩ is not obtained, drying out  
must be continued and the test repeated.7.2 BEARINGS  
7.4 FAULT FINDING  
Important ! Before commencing any fault finding  
procedure examine all wiring for broken or  
loose connections.  
All bearings are supplied sealed for life and are, therefore, not  
regreasable.  
Important ! The life of a bearing in service is subject to  
Four types of excitation control system, involving four types of  
AVR, can be fitted to the range of generators covered by this  
manual. The systems can be identified by a combination of  
AVR type, where applicable, and the last digit of the generator  
frame size designation. Refer to the generator nameplate then  
proceed to the appropriate subsection as indicated below :-  
the  
working  
conditions  
and  
the  
environment.  
Important ! Long stationary periods in an environment  
where there is vibration can cause false  
brinnelling which puts flats on the ball and  
grooves on the races. Very humid  
atmospheres or wet conditions can emulsify  
the grease and cause corrosion.  
DIGIT  
EXCITATION CONTROL  
SX460 AVR  
SUBSECTION  
7.4.1  
6
4
4
5
3
3
AS440 AVR  
7.4.2  
7.4.3  
Important ! High axial vibration from the engine or  
misalignment of the set will stress the  
bearing.  
Transformer control  
MX341 AVR  
7.4.4  
7.4.5  
MX321 AVR  
7.4.6  
The bearing, in service, is affected by a variety of factors that  
together will determine the bearing life. We recommend that  
the health of the bearings be monitored, using ‘spike energy’  
vibration monitoring equipment. This will allow the timely  
replacement of bearings, that exhibit a deteriorating trend,  
during a major engine overhaul.  
7.4.1 SX460 AVR - FAULT FINDING  
1. Check speed  
2. Check residual voltage. Refer to  
subsection 7.4.7.  
3. Follow Separate Excitation Test  
Procedure to check generator and  
AVR.  
No voltage  
build-up when  
starting set  
If excessive heat, noise or vibration is detected, change the  
bearing as soon as practicable. Failure to do so could result in  
bearing failure.  
Unstable voltage  
1. Check speed stability.  
either on no-load 2. Check stability setting. Refer to  
In the event that ‘spike energy’ vibration monitoring equipment  
is not available, it is strongly recommend that consideration  
be given to changing the bearing during each ‘major engine  
overhaul’.  
or with load  
subsection 4.6.  
High voltage  
1. Check speed.  
either on no-load 2. Check that generator load is not  
or with load  
capacitive (leading power factor).  
1. Check speed.  
Low voltage  
no-load  
Belt driven application will impose an additional load on  
bearings. The bearing life will therefore be significantly  
affected. It is important that the side load limits given in  
SECTION 3 are not exceeded and the health of the bearing is  
monitored more closely.  
2. Check link 1-2 or external hand  
trimmer leads for continuity.  
1. Check speed.  
2. Check UFRO setting. Refer to  
subsection 4.7.1.1.  
Low voltage  
on-load  
3. Follow  
Separate  
Excitation  
7.3 AIR FILTERS  
Procedure to check generator and  
AVR. Refer to subsection 7.5.  
The frequency of filter maintenance will depend upon the  
severity of the site conditions. Regular inspection of the  
elements will be required to establish when cleaning is  
necessary.  
7.3.1 CLEANING PROCEDURE  
Removal of filter elements enables access  
to LIVE parts. Only remove elements with  
the generator out of service.  
Danger !  
Remove the filter elements from the filter frames. Immerse or  
flush the element with a suitable detergent until the element is  
clean. Dry elements thoroughly before refitting.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.2 SX440 AVR - FAULT FINDING  
1. Check link K1-K2 on auxiliary  
7.4.4 TRANSFORMER CONTROL - FAULT FINDING  
terminals.  
2. Check speed  
3. Check residual voltage. Refer to  
subsection 7.4.7.  
No voltage  
build-up when  
starting set  
1. Check transformers rectifiers.  
2. Check transformer secondary  
winding for open circuit.  
1. Check speed.  
No voltage  
build-up when  
starting set  
4. Follow Separate Excitation Test  
Procedure to check generator and  
AVR. Refer to subsection 7.5.  
Low voltage  
2. Check transformer air gap setting.  
Refer to subsection 4.7.2.  
1. Check speed.  
2. Check transformer air gap setting.  
Refer to subsection 4.7.2.  
Unstable voltage  
either on no-load 2. Check stability setting. Refer to  
1. Check speed stability.  
High voltage  
3. Check  
transformer  
secondary  
or with load  
subsection 4.6.  
winding for open circuit.  
1. Check speed drop on-load.  
2. Check transformers rectifiers.  
3. Check transformer air gap setting.  
Refer to subsection 4.7.2.  
High voltage  
1. Check speed.  
Excessive  
voltage/speed  
dip on load  
switching  
either on no-load 2. Check that generator load is not  
or with load  
capacitive (leading power factor).  
1. Check speed.  
2. Check link 1-2 or external hand  
trimmer leads for continuity.  
1. Check speed.  
Low voltage  
no-load  
2. Check UFRO setting. Refer to  
subsection 4.7.1.1.  
Low voltage  
on-load  
3. Follow  
Separate  
Excitation  
Procedure to check generator and  
AVR. Refer to subsection 7.5.  
7.4.3 SX421 AVR - FAULT FINDING  
1. Check circuit breaker ON. Refer to  
subsection 6.4.1.  
2. Check speed  
3. Check residual voltage. Refer to  
subsection 7.4.7.  
4. Follow Separate Excitation Test  
Procedure to check generator and  
AVR. Refer to subsection 7.5.  
1. Check speed stability.  
No voltage  
build-up when  
starting set  
Unstable voltage  
either on no-load 2. Check stability setting. Refer to  
or with load  
subsection 4.6.  
1. Check speed.  
2. Check link 1-2 or external hand  
trimmers leads for continuity. Check  
continuity of leads 7-8 and P3-P2 for  
continuity.  
High voltage  
either on no-load  
or with load  
3. Check that generator load is not  
capacitive (leading power factor).  
1. Check speed.  
2. Check link 1-2 or external hand  
trimmer leads for continuity.  
1. Check speed.  
Low voltage  
no-load  
2. Check UFRO setting. Refer to  
subsection 4.7.1.1.  
Low voltage  
on-load  
3. Follow  
Separate  
Excitation  
Procedure to check generator and  
AVR. Refer to subsection 7.5.  
Excessive  
voltage/speed  
dip on load  
switching  
1. Check governor response.  
2. Refer to generating set manual.  
Check ‘DIP’ setting. Refer to  
subsection 4.7.1.4.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.5 MX341 AVR - FAULT FINDING  
7.4.6 MX321 AVR - FAULT FINDING  
1. Check link K1-K2 on auxiliary  
terminals  
2. Follow Separate Excitation Test  
Procedure to check machine and  
AVR. Refer to subsection 7.5.  
1. Check link K1-K2 on auxiliary  
No voltage  
build-up when  
starting set  
No voltage  
build-up when  
starting set  
terminals. Follow Separate Excitation  
Test Procedure to check machine  
and AVR. Refer to subsection 7.5.  
Voltage very slow 1. Check setting of ramp potentiometer.  
1. First stop and restart set. If no  
voltage or voltage collapses after  
short time, follow Separate Excitation  
Test Procedure. Refer to subsection  
7.5.  
to build up  
Refer to 4.7.1.5.  
1. First stop and restart set. If no  
voltage or voltage collapses after  
short time, follow Separate Excitation  
Test Procedure. Refer to subsection  
7.5.  
Loss of voltage  
when set runninig  
Loss of voltage  
when set running  
Generator  
voltage high  
followed by  
collapse  
1. Check sensing leads to AVR.  
2. Refer to Separate Excitation Test  
Procedure. Refer to subsection 7.5.  
Generator  
voltage high  
followed by  
collapse  
1. Check sensing leads to AVR.  
2. Refer to Separate Excitation Test  
Procedure. Refer to subsection 7.5.  
1. Check speed stability.  
Voltage unstable,  
either on no-load  
or with load  
2. Check “STAB” setting. Refer to Load  
Testing section for procedure. Refer  
to subsection 4.6.  
1. Check speed.  
2. If correct check “UFRO” setting.  
Refer to subsection 4.7.1.1.  
1. Check speed stability.  
Voltage unstable,  
either on no-load  
or with load  
2. Check “STAB” setting. Refer to Load  
Testing section for procedure. Refer  
to subsection 4.6.  
1. Check speed.  
2. If correct check “UFRO” setting.  
Refer to subsection 4.7.1.1.  
1. Check governor response. Refer to  
generating set manual. Check “DIP”  
setting. Refer to subsection 4.7.1.4.  
1. Check governor response. Refer to  
generating set manual. Check  
“DWELL” setting. Refer to Load  
Testing section 4.7.1.4.  
Low voltage  
on-load  
Low voltage  
on-load  
Excessive  
voltage/speed  
dip on load  
switching  
Sluggish  
recovery on load  
switching  
1. Check governor response. Refer to  
generating set manual. Check “DIP”  
setting. Refer to subsection 4.7.1.4.  
Excessive  
voltage/speed dip  
on load switching  
1. Check governor response. Refer to  
generating set manual.  
Sluggish  
recovery on load  
switching  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.7 RESIDUAL VOLTAGE CHECK  
7.5.1 GENERATOR WINDINGS, ROTATING DIODES  
and PERMANENT MAGNET GENERATOR (PMG)  
This procedure is applicable to generators with either SX460  
or SX440 or SX421 AVR.  
Important ! The resistances quoted apply to a standard  
winding. For generators having windings or  
voltages other than those specified refer to  
factory for details. Ensure all disconnected  
leads are isolated and free from earth.  
With the generator set stationary remove AVR access cover  
and leads X and XX from the AVR.  
Start the set and measure voltage across AVR terminals 7-8  
on SX460 AVR or P2-P3 on SX440 or SX421 AVR.  
Important ! Incorrect  
speed  
setting  
will  
give  
proportional error in voltage output.  
Stop the set, and replace leads X and XX on the AVR  
terminals. If the measured voltage was above 5V the  
generator should operate normally.  
CHECKING PMG  
Start the set and run at rated speed. Measure the voltages at  
the AVR terminals P2, P3 and P4. These should be balanced  
and within the following ranges :-  
If the measured voltage was under 5V follow the procedure  
below.  
Using a 12 volt d. c. battery as a supply clip leads from battery  
negative to AVR terminal XX, and from battery positive  
through a diode to AVR terminal X. See Fig. 10.  
50Hz generators - 170-180 volts  
60Hz generators - 200-216 volts  
Should the voltages be unbalanced stop the set, remove the  
PMG sheet metal cover from the non drive endbracket and  
disconnect the multipin plug in the PMG output leads. Check  
leads P2, P3, P4 for continuity. Check the PMG stator  
resistances between output leads. These should be balanced  
and within +/-10% of 2.3 ohms. If resistances are unbalanced  
and/or incorrect the PMG stator must be replaced. If the  
voltages are balanced but low and the PMG stator winding  
resistances are correct - the PMG rotor must be replaced.  
Important ! A diode must be used as shown below to  
ensure the AVR is not damaged.  
CHECKING GENERATOR WINDINGS AND  
ROTATING DIODES  
This procedure is carried out with leads  
X
and XX  
disconnected at the AVR or transformer control rectifier bridge  
and using a 12 volt d.c. supply to leads X and XX.  
Start the set and run at rated speed.  
Measure the voltages at the main output terminals U, V and  
W. If voltages are balanced and within +/-10% of the  
generator nominal voltage, refer to 7.5.1.1.  
Important ! If the generating set battery is used for field  
flashing the generator main stator neutral  
must be disconnected from earth.  
Check voltages at AVR terminals 6, 7 and 8. These should be  
balanced and between 170-250 volts.  
Restart the set and note output voltage from main stator,  
which should be approximately nominal voltage, or voltage at  
AVR terminals 7 and 8 on SX460, P2-P3 on SX440 or SX421  
which should be between 170 and 250 volts.  
If voltages at main terminals are balanced but voltage at 6, 7  
and 8 are unbalanced, check continuity of leads 6, 7 and 8.  
Where an isolating transformer is fitted (MX321 AVR) check  
transformer windings. If faulty the transformer unit must be  
replaced.  
Stop the set and unclip battery supply from terminals X and  
XX. Restart the set. The generator should now operate  
normally. If no voltage build-up is obtained it can be assumed  
a fault exists in either the generator or the AVR circuits.  
Follow the SEPARATE EXCITATION TEST PROCEDURE to  
check generator windings, rotating diodes and AVR. Refer to  
subsection 7.5.  
If voltages are unbalanced, refer to 7.5.1.2.  
7.5.1.1 BALANCED MAIN TERMINAL VOLTAGES  
If all voltages are balanced within 1% at the main terminals, it  
can be assumed that all exciter windings, main windings and  
main rotating diodes are in good order, and the fault is in the  
AVR or transformer control. Refer to subsection 7.5.2 for test  
procedure.  
7.5 SEPARATE EXCITATION TEST PROCEDURE  
The generator windings, diode assembly and AVR can be  
checked using the appropriate following section.  
7.5.1 GENERATOR WINDINGS, ROTATING DIODES and  
PERMANENT MAGNET GENERATOR (PMG)  
If voltages are balanced but low, there is a fault in the main  
excitation windings or rotating diode assembly. Proceed as  
follows  
to  
identify  
:-  
7.5.2 EXCITATION CONTROL TEST.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UCD27J  
UCD27K  
2.08  
2.08  
20  
20  
-
-
-
-
0.182  
0.182  
Rectifier Diodes  
* Used with 1 phase transformer controlled 3 phase or 1  
phase generators.  
** Used with 3 phase transformer controlled 3 phase  
generators.  
The diodes on the main rectifier assembly can be checked  
with a multimeter. The flexible leads connected to each diode  
should be disconnected at the terminal end, and the forward  
and reverse resistance checked. A healthy diode will indicate  
a very high resistance (infinity) in the reverse direction, and a  
low resistance in the forward direction. A faulty diode will give  
a full deflection reading in both directions with the test meter  
on the 10,000 ohms scale, or an infinity reading in both  
directions.  
7.5.1.2 UNBALANCED MAIN TERMINAL VOLTAGES  
If voltages are unbalanced, this indicates a fault on the main  
stator winding or main cables to the circuit breaker.  
NOTE : Faults on the stator winding or cables may also cause  
noticeable load increase on the engine when excitation is  
applied. Disconnect the main cables and separate the winding  
leads U1-U2, U5-U6, V1-V2, V5-V6, W1-W2, W5-W6 to  
isolate each winding section. (U1-L1, U2-L4 on single phase  
generators).  
On an electronic digital meter a healthy diode will give a low  
reading in one direction, and a high reading in the other.  
Replacement of Faulty Diodes  
The rectifier assembly is split into two plates, the positive and  
negative, and the main rotor is connected across these plates.  
Each plate carries 3 diodes, the negative plate carrying  
negative biased diodes and the positive plate carrying positive  
biased diodes. Care must be taken to ensure that the correct  
polarity diodes are fitted to each respective plate. When fitting  
the diodes to the plates they must be tight enough to ensure a  
good mechanical and electrical contact, but should not be  
overtightened. The recommended torque tightening is 4.06 -  
4.74Nm (36-42lb in).  
Measure each section resistance - values should be balanced  
and within +/-10% of the value given below:-  
AVR CONTROLLED GENERATORS  
SECTION RESISTANCES  
FRAME  
SIZE  
WINDING  
311  
WINDING  
17  
WINDING  
05  
WINDING  
06  
UC22C  
UC22D  
UC22E  
UC22F  
UC22G  
0.09  
0.065  
0.05  
0.033  
0.028  
0.14  
0.1  
0.075  
0.051  
0.043  
0.045  
0.033  
0.028  
0.018  
0.014  
0.03  
0.025  
0.02  
0.012  
0.01  
Surge Suppressor  
UC27C  
UC27D  
UC27E  
UC27F  
UC27G  
UC27H  
UCD27J  
UCD27K  
0.03  
0.019  
0.016  
0.012  
0.01  
0.008  
0.006  
0.006  
0.044  
0.026  
0.025  
0.019  
0.013  
0.014  
0.009  
0.009  
0.016  
0.01  
0.009  
0.007  
0.006  
0.004  
-
0.011  
0.007  
0.008  
0.005  
0.004  
0.004  
-
The surge suppressor is a metal-oxide varistor connected  
across the two rectifier plates to prevent high transient  
reverse voltages in the field winding from damaging the  
diodes. This device is not polarised and will show a virtually  
infinite reading in both directions with an ordinary resistance  
meter. If defective this will be visible by inspection, since it will  
normally fail to short circuit and show signs of disintegration.  
Replace if faulty.  
-
-
Main Excitation Windings  
TRANSFORMER CONTROLLED GENERATOR  
SECTION RESISTANCES, 3 PHASE WINDINGS  
If after establishing and correcting any fault on the rectifier  
assembly the output is still low when separately excited, then  
the main rotor, exciter stator and exciter rotor winding  
resistances should be checked (see Resistance Charts), as  
the fault must be in one of these windings. The exciter stator  
resistance is measured across leads X and XX. The exciter  
rotor is connected to six studs which also carry the diode lead  
terminals. The main rotor winding is connected across the two  
rectifier plates. The respective leads must be disconnected  
before taking the readings.  
FRAME  
SIZE  
380V  
50Hz  
0.059  
0.054  
0.041  
0.031  
0.022  
400V  
50Hz  
0.078  
0.056  
0.05  
415V  
50Hz  
0.082  
0.057  
0.053  
0.033  
0.028  
416V  
60Hz  
0.055  
0.049  
0.038  
0.025  
0.021  
460V  
60Hz  
0.059  
0.054  
0.041  
0.031  
0.022  
UC22C  
UC22D  
UC22E  
UC22F  
UC22G  
0.032  
0.026  
Measure insulation resistance between sections and each  
section to earth.  
Resistance values should be within +/-10% of the values  
given in the table below :-  
Unbalanced or incorrect winding resistances and/or low  
insulation resistances to earth indicate rewinding of the stator  
will be necessary. Refer to removal and replacement of  
component assemblies subsection 7.5.3.  
FRAME  
SIZE  
Main  
Rotor  
0.59  
0.64  
0.69  
0.83  
0.94  
Exciter Stator  
Type 1 Type 2* Type 3**  
Exciter  
Rotor  
0.142  
0.142  
0.156  
0.156  
0.156  
UC22C  
UC22D  
UC22E  
UC22F  
UC22G  
21  
21  
20  
20  
20  
28  
28  
30  
30  
30  
138  
138  
155  
155  
155  
7.5.2 EXCITATION CONTROL TEST  
7.5.2.1 AVR FUNCTION TEST  
All types of AVR's can be tested with this procedure :  
UC27C  
UC27D  
UC27E  
UC27F  
UC27G  
UC27H  
1.12  
1.26  
1.34  
1.52  
0.69  
0.82  
20  
20  
20  
20  
20  
20  
-
-
-
-
-
-
-
-
-
-
-
-
0.156  
0.156  
0.182  
0.182  
0.182  
0.182  
1. Remove exciter field leads X & XX (F1 & F2) from the  
AVR terminals X & XX (F1 & F2).  
2. Connect a 60W 240V household lamp to AVR terminals  
X & XX (F1 & F2).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Set the AVR VOLTS control potentiometer fully  
clockwise.  
Low insulation resistance, unbalanced primary or secondary  
winding resistances, open or short circuited winding sections  
indicates the transformer unit should be replaced.  
4. Connect a 12V, 1.0A DC supply to the exciter field leads  
X & XX (F1 & F2) with X (F1) to the positive.  
Rectifier units - Three phase and single phase  
5. Start the generating set and run at rated speed.  
With the leads 10-11-12-X and XX removed from the rectifier  
unit (lead 12 is not fitted on single phase transformer rectifier  
units), check forward and reverse resistances between  
terminals 10-X, 11-X, 12-X, 10-XX, 11-XX and 12-XX with a  
multimeter.  
6. Check that the generator output voltage is within +/-10%  
of rated voltage.  
Voltages at AVR terminals 7-8 on SX460 AVR or P2-P3 on  
SX440 or SX421 AVR should be between 170 and 250 volts.  
If the generator output voltage is correct but the voltage on 7-  
8 (or P2- P3) is low, check auxiliary leads and connections to  
main terminals.  
A low forward resistance and high reverse resistance should  
be read between each pair of terminals. If this is not the case  
the unit is faulty and should be replaced.  
7.5.3 REMOVAL AND REPLACEMENT OF  
COMPONENT ASSEMBLIES  
Voltages at P2, P3, P4 terminals on MX341 and MX321 hould  
be as given in 7.5.1.  
METRIC THREADS ARE USED THROUGHOUT  
The lamp connected across X-XX should glow. In the case of  
the SX460, SX440 and SX421 AVRs the lamp should glow  
continuously. In the case of the MX341 and MX321 AVRs the  
lamp should glow for approximately 8 secs. and then turn off.  
Failure to turn off indicates faulty protection circuit and the  
AVR should be replaced. Turning the "VOLTS" control  
potentiometer fully anti-clockwise should turn off the lamp with  
all AVR types.  
When lifting single bearing generators,  
care is needed to ensure the generator  
frame is kept in the horizontal plane. The  
rotor is free to move in the frame and can  
Caution !  
slide out if not correctly lifted. Incorrect  
lifting can cause serious personal injury.  
7.5.3.1 REMOVAL OF PERMANENT MAGNET  
GENERATOR (PMG)  
Should the lamp fail to light the AVR is faulty and should be  
replaced.  
1. Remove 4 screws holding the sheet metal cylindrical  
cover at the non-drive end and remove the cover.  
Important ! After this test turn VOLTS control  
potentiometer fully anti-clockwise.  
2. Disconnect the in line connector from the PMG stator (3  
wires go to this connector). It may be necessary to cut off  
the nylon cable tie first.  
7.5.2.2 TRANSFORMER CONTROL  
The transformer rectifier unit can only be checked by  
continuity, resistance checks and insulation resistance  
measurement.  
3. Remove the 4 threaded pillars and clamps holding the  
PMG stator onto the end bracket.  
Two phase transformer  
4. Tap the stator out of the 4 spigots and withdraw. The  
highly magnetic rotor will attract the stator. Take care to  
avoid contact which may damage the windings.  
Separate primary leads T1-T2-T3-T4 and secondary leads 10-  
11. Examine windings for damage. Measure resistances  
across T1-T3 and T2-T4. These will be a low value but should  
be balanced. Check that there is resistance in the order of 8  
ohms between leads 10 and 11. Check insulation resistance  
of each winding section to earth and to other winding  
sections.  
5. Remove the bolt in the centre from the rotor shaft and  
pull off the rotor. It may be necessary to gently tap the  
rotor away. Take care to tap gently and evenly - the rotor  
has ceramicmagnets which are easily broken by shock.  
Low insulation resistance, unbalanced primary resistance,  
open or short circuited winding sections, indicates the  
transformer unit should be replaced.  
Important ! The rotor assembly must not be dismantled.  
Replacement is a reversal of the above procedure.  
Three phase transformer  
7.5.3.2 REMOVAL OF BEARINGS  
Separate primary leads T1-T2-T3 and secondary leads 6-7-8  
and 10-11-12.  
Important ! Position the main rotor so that a full pole  
face of the main rotor core is at the bottom  
of the stator bore.  
Examine windings for damage. Measure resistances across  
T1-T2, T2-T3, T3-T1. These will be low but should be  
balanced.  
NOTE: Removal of the bearings may be effected either after  
the rotor assembly has been removed OR more simply by  
removal of endbracket(s). Refer to 7.5.3.3. and 7.5.3.4.  
Check that resistances are balanced across 6-10, 7-11 and  
8-12 and in the order of 18 ohms. Check insulation resistance  
of each winding section to earth and to other winding  
sections.  
The bearings are pre-packed with grease and sealed for life.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The bearing(s) are a press fit and can be removed from the  
shaft with 3 leg or 2 leg manual or hydraulic bearing pullers.  
4. Remove the screens and louvres (if fitted) at each side  
on the drive end.  
SINGLE BEARING ONLY : Before trying to pull off the  
bearing remove the small circlip retaining it.  
Now ensure that the rotor is positioned with a full pole face at  
the bottom centre line. This is to avoid damage to the bearing  
exciter, or rotor winding, by limiting the possible rotor  
downward movement to the air gap length.  
When fitting new bearings use a bearing heater to expand the  
bearing before fitting to the shaft. Tap the bearing into place  
ensuring that it contacts the shoulder on the shaft.  
5. Remove 6 bolts holding drive endbracket onto adaptor  
ring DE. The boltheads face towards the non-drive end.  
The top bolt passes through the centre of the lifting lug.  
Refit the retaining circlip on single bearing generators.  
6. Tap the drive endbracket away from the adaptor ring DE  
and withdraw the endbracket.  
7.5.3.3 REMOVAL OF ENDBRACKET AND EXCITER  
STATOR  
7. Ensure the rotor is supported at the drive end on a sling.  
1. Remove exciter leads X+, XX- at the AVR.  
8. Tap the rotor from the non-drive end to push the bearing  
clear of the endbracket and its position within an 'O' ring.  
2. Slacken 4 bolts (2 each side) situated on horizontal  
centre line holding the terminal box.  
9. Continue to push the rotor out of the stator bore,  
gradually working the sling along the rotor as it is  
withdrawn, to ensure that it is fully supported all the  
time.  
3. Remove 2 bolts holding lifting lug, at the non-drive end,  
and remove lug.  
4. Remove sheet metal cylindrical cover (4 screws) over  
PMG (if fitted) or Remove shallow sheet metal cover (4  
screws) at the nondrive end.  
SINGLE BEARING GENERATORS  
1. Remove the screws, screens and louvres (if fitted) at  
each side on drive end adaptor.  
5. Ease up the terminal box and support clear of the  
nondrive endbracket.  
2. UCI224, UCI274, UCM224, UCM274, UCD274 Only  
Remove 6 bolts holding the adaptor at the drive end. It  
may be preferred to sling the adaptor on a hoist. The bolt  
heads face towards the non-drive end. The top bolt  
passes through the centre of the lifting lug.  
6. Remove 6 bolts holding the non-drive endbracket to the  
stator bar assembly. The endbracket is now ready for  
removal.  
7. Replace the lifting lug onto the endbracket and sling the  
endbracket on a hoist to facilitate lifting.  
2a. UCD224 Only Remove 6 bolts holding the adaptor at the  
drive end. It may be preferred to sling the adaptor on a hoist.  
8. Tap the endbracket around its perimeter to release from  
the generator. The endbracket and exciter stator will  
come away as a single assembly.  
3. UCI224, UCI274, UCM224, UCM274, UCD274 Only Tap  
the adaptor away from stator bar adaptor ring.  
9. Remove the 4 screws holding the exciter stator to the  
endbracket and gently tap the exciter stator to release it.  
Replacement is a reversal of the above procedure.  
3a. UCD224 Only Tap the adaptor away from stator bar  
assembly.  
ALL SINGLE BEARING GENERATORS  
7.5.3.4 REMOVAL OF THE ROTOR ASSEMBLY  
4. Ensure the rotor is supported at drive end on a sling.  
Remove the permanent magnet generator. Refer to 7.5.3.1  
or  
Remove the four screws holding the sheet metal cover at the  
non drive end and remove cover.  
5. Tap the rotor from the non-drive end to push the bearing  
clear of the endbracket and its position within an 'O' ring.  
6. Continue to push the rotor out of the stator bore,  
gradually working the sling along the rotor as it is  
withdrawn, to ensure that it is fully supported at all times.  
With the PMG rotor removed single  
bearing generator rotors are free to move  
in the frame. Ensure frame is kept in the  
horizontal plane when lifting.  
Caution !  
Replacement of rotor assemblies is a reversal of the  
procedures above.  
TWO BEARING GENERATORS  
Before commencing re-assembly, components should be  
checked for damage and bearing(s) examined for loss of  
grease.  
1. Remove 2 screws holding the sheet metal cover around  
the adaptor at the drive end and remove the cover.  
2. Remove the bolts holding the adaptor to the endbracket  
at the drive end.  
Fitting of new bearing(s) is recommended during major  
overhaul.  
3. Tap off the adaptor. It may be preferred to sling the  
adaptor first depending on its size and weight.  
Before replacement of a single bearing rotor assembly, check  
that the drive discs are not damaged, cracked or showing  
other signs of fatigue. Also check that the holes in the discs  
for drive fixing screws are not elongated.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Damaged or worn components must be replaced.  
When major components have been  
replaced, ensure that all covers and  
guards are securely fitted, before the  
Caution !  
generator is put into service.  
7.6 RETURNING TO SERVICE  
After rectification of any faults found, remove all test  
connections and reconnect all control system leads. Restart  
the set and adjust VOLTS control potentiometer on AVR  
controlled generators by slowly turning clockwise until rated  
voltage is obtained. Refit all terminal box covers/access  
covers and reconnect heater supply.  
Failure to refit all guards, access covers  
and terminal box covers can result in  
Caution !  
personal injury of death.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 8  
SPARES AND AFTER SALES SERVICE  
8.1 RECOMMENDED SPARES  
Service parts are conveniently packaged for easy  
identification. Genuine parts may be recognised by the Nupart  
name.  
We recommend the following for Service and Maintenance. In  
critical applications a set of these service spares should be  
held with the generator.  
AVR Controlled Generators  
1. Diode Set (6 diodes with surge suppressor) RSK 2001  
2. AVR SX440  
AVR SX460  
E000 24030  
E000 24602  
E000 24210  
E000 23212  
E000 23410  
AVR SX421  
AVR MX321  
AVR MX341  
3. Non drive end Bearing  
UC22 051  
01032  
01049  
01044  
01050  
UC27 051  
UC22 051  
UC27 051  
4. Drive end Bearing  
Transformer Controlled Generators (UC22 Only)  
1. Diode Set (6 diodes with surge suppressor) RSK 2001  
2. Diode Assembly  
E000 22006  
3. Non drive end Bearing  
4. Drive end Bearing  
UC22 051  
UC22 051  
01032  
01044  
When ordering parts the machine serial number or machine  
identity number and type should be quoted, together with the  
part description. For location of these numbers see paragraph  
1.3.  
Orders and enquiries for parts should be addressed to:  
STAMFORD & AvK Parts Department  
Barnack Road  
STAMFORD  
Lincolnshire  
PE9 2NB  
ENGLAND  
Telephone: 44 (0) 1780 484000  
Fax: 44 (0) 1780 766074  
Or any of our subsidiary companies listed on the back cover.  
8.2 AFTER SALES SERVICE  
A full technical advice and on-site service facility is available  
from our Service Department at Stamford or through our  
Subsidiary Companies. A repair facility is also available at our  
Stamford Works.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
TYPICAL SINGLE BEARING GENERATOR  
Plate Ref.  
1
Description  
Stator  
2
Rotor  
3
4
Exciter Rotor  
Exciter Stator  
5
N.D.E. Bracket  
6
Cover N.D.E.  
7
8
Bearing ‘O’ Ring N.D.E.  
Bearing N.D.E.  
9
Bearing Circlip N.D.E.  
D.E. Bracket/Engine Adaptor  
D.E. Screen  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
Coupling Disc  
Couplimg Bolt  
Foot  
Frame Cover Bottom  
Frame Cover Top  
Air Inlet Cover  
Terminal Box Lid  
Endpanel D.E.  
N.D.E.  
D.E.  
P.M.G.  
A.V.R.  
Non Driven End  
Driven End  
Permanent Magnet Generator  
Automatic Voltage Regulator  
Endpanel N.D.E.  
AVR  
Side Panel  
AVR Mounting Bracket  
Main Rectifier Assembly - Forward  
Main Rectifier Assembly - Reverse  
Varistor  
Diode - Forward Polarity  
Diode - Reverse Polarity  
Lifting Lug - D.E.  
Lifting Lug - N.D.E.  
Frame to Endbracket Adaptor Ring  
Main Terminal Panel  
Terminal Link  
Edging Strip  
Fan  
Foot Mounting Spacer  
Cap Screw  
AVR Access Cover  
AVR Anti-Vibration Mounting Assembly  
Auxiliary Terminal Assembly  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 11.  
TYPICAL SINGLE BEARING GENERATOR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
TYPICAL TWO BEARING GENERATOR  
Plate Ref.  
1
Description  
Stator  
2
Rotor  
3
4
5
6
Exciter Rotor  
Exciter Stator  
N.D.E. Bracket  
Cover N.D.E.  
7
8
Bearing ‘O’ Ring N.D.E.  
Bearing N.D.E.  
9
Bearing Wave Washer.D.E.  
D.E. Bracket  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
D.E. Screen  
Bearing D.E.  
Foot  
Frame Cover Bottom  
Frame Cover Top  
Air Inlet Cover  
Terminal Box Lid  
Endpanel D.E.  
Endpanel N.D.E.  
AVR  
Side Panel  
AVR Mounting Bracket  
Main Rectifier Assembly - Forward  
Main Rectifier Assembly - Reverse  
Varistor  
Diode - Forward Polarity  
Diode - Reverse Polarity  
Lifting Lug - D.E.  
Lifting Lug - N.D.E.  
Frame to Endbracket Adaptor Ring  
Main Terminal Panel  
Terminal Link  
N.D.E.  
D.E.  
P.M.G.  
A.V.R.  
Non Driven End  
Driven End  
Permanent Magnet Generator  
Automatic Voltage Regulator  
Edging Strip  
Fan  
Foot Mounting Spacer  
Cap Screw  
AVR Access Cover  
AVR Anti-Vibration Mounting Assembly  
Auxiliary Terminal Assembly  
PMG Exciter Rotor  
PMG Exciter Stator  
PMG Bolt  
PMG Pillar  
PMG Clamp  
PMG Dowel  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 12.  
TYPICAL TWO BEARING GENERATOR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
TYPICAL TWO BEARING (SERIES 5) GENERATOR  
Plate Ref.  
1
Description  
Stator  
2
Rotor  
3
4
Exciter Rotor  
Exciter Stator  
5
N.D.E. Bracket  
6
Cover N.D.E.  
7
8
Bearing ‘O’ Ring N.D.E.  
Bearing N.D.E.  
9
Bearing Wave Washer N.D.E.  
D.E. Bracket  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
D.E. Screen  
Bearing D.E.  
Foot  
N.D.E.  
D.E.  
Non Driven End  
Driven End  
Frame Cover Bottom  
Frame Cover Top  
Air Inlet Cover  
Terminal Box Lid  
Endpanel D.E.  
Endpanel N.D.E.  
Series 5 Control Gear  
Side Panel  
Main Rectifier Assembly - Forward  
Main Rectifier Assembly - Reverse  
Varistor  
Diode - Forward Polarity  
Diode - Reverse Polarity  
Lifting Lug - D.E.  
Lifting Lug - N.D.E.  
Frame to Endbracket Adaptor Ring  
Main Terminal Panel  
Terminal Link  
Edging Strip  
Fan  
Foot Mounting Spacer  
Cap Screw  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 13.  
TYPICAL TWO BEARING (SERIES 5) GENERATOR  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 14.  
ROTATING RECTIFIER ASSEMBLY  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.C. GENERATOR WARRANTY  
WARRANTY PERIOD  
A.C. Generators  
In respect of a.c. generators the Warranty Period is eighteen months from the  
date when the goods have been notified as ready for despatch by N.I. or twelve  
months from the date of first commissioning (whichever is the shorter period).  
DEFECTS AFTER DELIVERY  
We will make good by repair or, at our option, by the supply of a replacement,  
any fault which under proper use appears in the goods within the period  
specified on Clause 12, and is found on examination by us to be solely due to  
defective material and workmanship; provided that the defective part is promptly  
returned, carriage paid, with all identification numbers and marks intact, or our  
works or, if appropriate to the Dealer who supplied the goods.  
Any part repaired or replaced, under warranty, will be returned by N.I. free of  
harge (via sea freight if outside the UK).  
We shall not be liable for any expenses which may be incurred in removing or  
replacing any part sent to us for inspection or in fitting any replacement supplied  
by us. We shall be under no liability for defects in any goods which have not  
been properly installed in accordance with N.I. recommended installation  
practices as detailed in the publications 'N.I. Installation, Service and  
Maintenance Manual' and 'N.I. Application Guidelines', or which have been  
improperly stored or which have been repaired, adjusted or altered by any  
person except ourselves or our authorised agents, or in any second-hand  
goods, proprietary articles or goods not of our own manufacture although  
supplied by us, such articles and goods being covered by the warranty (if any)  
given by the separate manufacturers.  
Any claim under this clause must contain fully particulars of the alleged defect,  
the description of the goods, the date of purchase, and the name and address  
of the Vendor, the Serial Number (as shown on the manufacturers identification  
plate) or for Spares the order reference under which the goods were supplied.  
Our judgement in all cases of claims shall be final and conclusive and the  
claimant shall accept our decision on all questions as to defects and the  
exchange of a part or parts.  
Our liability shall be fully discharged by either repair or replacement as above,  
and in any event shall not exceed the current list price of the defective goods.  
Our liability under this clause shall be in lieu of any warranty or condition implied  
by law as to the quality or fitness for any particular purpose of the goods, and  
save as expressly provided in this clause we shall not be under any liability,  
whether in contract, tort or otherwise, in respect of defects in goods delivered or  
for any injury, damages or loss resulting from such defects or from any work  
undone in connection therewith.  
MACHINE SERIAL NUMBER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REGISTERED OFFICE AND ADDRESS:  
BARNACK ROAD  
STAMFORD  
LINCOLNSHIRE  
PE9 2NB ENGLAND  
Telephone: 44 (0) 1780 484000  
Fax: 44 (0) 1780 484100  
SUBSIDIARY COMPANIES  
7. NORWAY:  
NEWAGE NORGE A/S  
1. AUSTRALIA : NEWAGE ENGINEERS PTY. LIMITED  
PO Box 6027, Baulkham Hills Business Centre,  
Baulkham Hills NSW 2153.  
Økern Naeringspark, Kabeigt. 5  
Postboks 28, Økern, 0508 Oslo  
Telephone: Oslo (47) 22 97 44 44  
Fax: (47) 22 97 44 45  
Telephone: Sydney (61) 2 9680 2299  
Fax: (61) 2 9680 1545  
8. SINGAPORE:  
NEWAGE ASIA PACIFIC PTE LIMITED  
10 Toh Guan Road #05-03  
TT International Tradepark  
Singapore 608838  
Telephone: Singapore (65) 794 3730  
Fax: (65) 898 9065  
2. CHINA:  
WUXI NEWAGE ALTERNATORS LIMITED  
Plot 49-A, Xiang Jiang Road  
Wuxi High - Technical Industrial Dev. Zone  
Wuxi, Jiangsu 214028  
PR of China  
Tel: (86) 51 027 63313  
Telex: RS 33404 NEWAGE  
Fax: (86) 51 052 17673  
9. SPAIN:  
STAMFORD IBERICA S.A.  
3. GERMANY: NEWAGE ENGINEERS G.m.b.H.  
Rotenbrückenweg 14, D-22113 Hamburg.  
Telephone: Hamburg (49) 40 714 8750  
Fax: (49) 40 714 87520  
Ctra. Fuenlabrada-Humanes, km.2  
Poligono Industrial "Los Linares"  
C/Pico de Almanzor, 2  
E-28970 HUMANES DE MADRID (Madrid)  
Telephone: Madrid (34) 91 604 8987/8928  
Fax: (34) 91 604 81 66  
4. INDIA:  
5. ITALY:  
6. JAPAN:  
C.G. NEWAGE ELECTRICAL LIMITED  
C33 Midc, Ahmednagar 414111, Maharashtra.  
Telephone: (91) 241 778224  
10. U.S.A.:  
NEWAGE LIMITED  
4700 Main St, N.E.  
Fridley  
Minnesota 55421  
Telephone: (1) 800 367 2764  
Fax: (1) 800 863 9243  
Fax: (91) 241 777494  
NEWAGE ITALIA S.r.I.  
Via Triboniano, 20156 Milan.  
Telephone: Milan (39) 02 380 00714  
Fax: (39) 02 380 03664  
NEWAGE INTERNATIONAL JAPAN  
8 - 5 - 302 Kashima  
Hachioji-shi  
Tokyo, 192-03  
Telephone: (81) 426 77 2881  
Fax: (81) 426 77 2884  
© 2006  
TD_UC MAN GB_10.06_  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Music Mixer XRD 680 PLUS User Manual
Peerless Industries TV Mount SUA746PU User Manual
Pelco Home Security System CC3320 2 User Manual
Philips Refrigerator LPS 100 User Manual
Pioneer Car Amplifier VSX 822 K User Manual
Pioneer CD Player DEH 2000MP User Manual
Planet Technology Network Card PL 501v2 EU User Manual
Polaroid Digital Camera t1232 User Manual
Precision Power Speaker PRO15 User Manual
ProForm Treadmill PFTL795100 User Manual