Omron Marine Instruments BUM100S User Manual

Battery Unit BUM100S/150S/300S Instruction Manual  
• This manual contains important information regarding the safe use of the BUM100S/150S/300S. Please  
read these instructions before installing and/or using the product.  
• Please connect and install the battery unit only after having fully understood the relevant procedures for  
the Backup Power Supply, found in the Backup Power Supply Instruction Manual.  
This manual contains important information regarding the  
safe use of this product.  
Please read these instructions before installation and/or use.  
Safety precautions  
The safety symbols used in this manual are explained below.  
Indicates an imminently hazardous situation which, if not handled  
properly, may result in death or serious injury.  
Warning  
Caution  
Indicates a potentially hazardous situation which, if not handled  
properly, may result in injury or property damage.  
* Property damage means damage to houses/household effects, livestock, and pets.  
: Indicates a prohibited action (something you must not do). For example,  
disassembly is prohibited.  
indicates that  
: Indicates a necessary action (something you must do). For example,  
is necessary.  
indicates that grounding  
Note that some items described as cautions may result in more serious damage under certain conditions.  
The information described here is very important and must be strictly observed.  
Warning  
Do not disassemble, repair, or modify the product.  
• Doing so may cause an electric shock or a fire.  
If liquid leaks from the product, do not touch it.  
• Doing so may cause blindness or burns.  
• If it touches your eyes or skin, wash it out with lots of clean water and consult your doctor.  
Warning (product use)  
Do not use this product in applications which require an extremely high degree  
of reliability and safety, such as those listed below.  
(This product is designed and manufactured for use for OA equipment such as personal computers.)  
• Medical equipment or system that may cause death directly  
• Applications that directly affect the safety of people. (For example, the operation and control of cars and elevators.)  
• Applications in which failure may significantly damage or impact the society and public. (For example, important  
computer systems or communication equipment.)  
• Applications with the same level of importance as those described above.  
Caution (installation)  
Two or more people should work together to carry, unpack and install the  
BUM300S.  
Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.  
Product weights are 20.5 kg (BUM100S), 21.5 kg (BUM150S), and 43.5kg (BUM300S).  
Carefully consider the weight when unpacking/transporting this product.  
Injury may result if the unit falls or is dropped.  
• If you drop the unit, stop using it and have it inspected and repaired. For information about repairs, contact us  
at __________.  
Keep plastic bags out of the reach of children.  
• Children may suffocate if they put their heads into plastic bags.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Caution (battery replacement)  
Do not drop the battery or expose it to strong impact.  
Doing so may cause the battery to leak dilute sulfuric acid.  
Do not short the battery with metal objects.  
• Doing so may cause an electric shock, fire or burn.  
• Some electrical energy remains inside the spent battery.  
Do not put the battery into fire, and do not break it.  
• The battery may explode or leak dilute sulfuric acid.  
Do not use a new battery and an old battery at the same time.  
Doing so may cause the battery to leak dilute sulfuric acid.  
Notes  
Charge the battery (for at least 24 hours) immediately after purchase.  
• If you do not use the unit for a long time after purchase, the battery performance may deteriorate and it may become  
unusable.  
• The battery can be charged once the AC input plug of the UPS is connected to a wall outlet (commercial power).  
When storing the UPS, charge the battery for at least 24 hours and turn OFF the power switch.  
• The battery discharges even when it not being used, and it goes into over discharge state if it is left for a long period of  
time.  
The backup time may become shorter or the battery may become unusable.  
• We recommend keeping the temperature 25°C or less when storing the unit for long periods of time.  
Connect the AC input plug of the UPS to a wall outlet (commercial power) for at least 24 hours at the following intervals:  
- Every 6 months when storage temperature is 25°C or less  
- Every 2 months when storage temperature is 40°C or less  
Turn OFF the power switch of the UPS during storage.  
Do not install or store the unit in a place exposed to direct sunlight.  
• A rise in temperature may cause the built-in battery to deteriorate rapidly and become unusable.  
This unit uses a lead acid battery.  
Lead acid batteries are a valuable recyclable resource. Please recycle.  
For information about recycling, please contact our peripheral device repair center.  
Pb  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1-1 Unpacking the product  
Caution  
Two or more people should work together to carry, unpack and install the  
BUM300S.  
Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.  
Product weights are 20.5 kg (BUM100S), 21.5 kg (BUM150S), and 43.5kg (BUM300S).  
Carefully consider the weight when unpacking/transporting this product.  
Injury may result if the unit falls or is dropped.  
If you drop the unit, stop using it and have it inspected and repaired. For information about repairs,  
contact us at __________.  
Do not install the unit on an unstable base.  
Injury may result if the unit falls or is dropped.  
Open the package box and take out the Battery Unit and accessories.  
1-2 Checking the accessories  
Make sure that all accessories are included and that there is no external damage.  
If you notice any defects, immediately contact the shop of purchase.  
1. Instruction manual (Japanese/English edition).... 1  
2. Battery connection cable + Cable clamps  
(BUM100S only) ............................................. 1 set  
3. Battery connection cable + Signal connection cable  
(BUM300S only) ............................................. 1 set  
4. Warranty card ...................................................... 1  
Instruction manual  
(Japanese / English edition)  
Battery connection cable  
+ Signal connection cable  
(BUM300S only)  
Battery connection cable  
+ Cable clamps  
(BUM100S only)  
Warranty card  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-1 Installation  
Install the additional battery unit.  
Do not use this unit in any position other than the correct positions indicated in the illustration below.  
 For BUM100S/BUM150S  
Correct positions  
Incorrect positions  
* Do not place the UPS or the additional battery unit on top of each other.  
The upper unit may fall down by vibration etc.  
バッテリ  
ブザー停止/テスト  
電源  
出力  
 増設  
-
バイパス  
運転  
バッテリ  
 交換  
BU150SW  
バッテリ  
ブザー停止/テスト  
電源  
出力  
 増設  
-
バイパス  
運転  
バッテリ  
 交換  
BU150SW  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 For BUM300S  
Correct Positions  
Be careful not to get your fingers caught  
when arranging the unit.  
Caster at the bottom may be removed  
when sitting horizontally.  
Incorrect Positions  
B A T T R Y U N I T  
* Do not place the UPS or the additional battery unit on top of each other.  
The upper unit may fall down by vibration etc.  
バッテリ  
ブザー停止/テスト  
電源  
出力  
 増設  
-
バイパス  
運転  
バッテリ  
 交換  
バッテリ  
ブザー停止/テスト  
電源  
出力  
 増設  
-
バイパス  
運転  
バッテリ  
 交換  
Set BUM300S in the same way as setting main body BU3003SW.  
BU1002SW/BU3002SW Instruction Manual p22.  
See also  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-2 Connecting the additional battery unit (BUM100S/150S/300S  
)
You can add only one additional battery unit.  
2-2-1 BUM100S connection procedure / Connectable UPS: BU100SW/BU1002SW  
(1) Remove the cover of the additional battery connector on the  
back of the UPS.  
Also remove the screws on the lower part of the signal card  
expansion slot cover.  
UPS  
BUM100S  
(2) Attach the clamps to the rear of the UPS and the BUM100S  
using 2 screws each. For now, loosen the screw that fastens  
the cable clamp and holds the cable.  
 
Attach with 2 screws  
RS232C  
Attach with 2 screws  
Loosen  
バッテリ  
増設コネ
DC36V/20A  
Use the screws removed in to attach the metal clamps.  
Loosen  
UPS  
BUM100S  
(3) Connect the connection cable to the connectors on the backs  
of the UPS and BUM100S.  
号カード  
   増設  
RS232C  
バッテリ  
増設コネ
DC36V/20A  
Connect to  
the connectors  
冷却ファン  
INPUT  
AC100V-120V  
50/60Hz  
12A  
AC入力  
過電流保護  
15A  
接地  
OUTPUT AC100-120V 50/60Hz 1ø  
出力電力 最大1kVA 700W  
/
(4) Insert the cable into the metal clamps attached in , and then  
Overcurrent protection switch  
ON   OFF  
BUM100S  
tighten the screws (2 each).  
UPS  
号カード  
When a 700W device is connected, the backup time is  
30 minutes (initial battery value at an ambient  
temperature of 20°C).  
When the battery is completely discharged, it takes 24  
hours to charge.  
   増設  
RS232C  
バッテリ  
増設コネク
DC36V/20A  
Tighten  
Tighten  
冷却ファン  
INPUT  
AC100V-120V  
50/60Hz  
12A  
AC入力  
過電流保護  
15A  
(5) Turn ON the overcurrent protection switch on the back of the  
additional battery unit.  
接地  
OUTPUT AC100-120V 50/60Hz 1ø  
出力電力 最大1kVA 700W  
/
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-2-2 BUM150S connection procedure / Connectable UPS : BU150SW  
(1) Connect the end of the battery cable connected to the back of the BUM150S to the UPS additional battery  
connector and additional battery signal connector.  
When a 1050W device is connected, the backup time  
is 20 minutes (initial battery value at an ambient tem-  
perature of 20°C).  
When the battery is completely discharged, it takes  
24 hours to charge.  
BUM150S  
Overcurrent  
UPS  
protection switch  
ON   OFF  
(2) Turn ON the overcurrent protection switch on the back of  
the additional battery unit.  
号カード  
   増設  
RS232C  
AC入力  
過電流保護  
20A  
INPUT  
AC100V-120V入力  
50/60Hz 16A  
冷却ファン  
バッテリ増設コネクタ  
DC36V/40A  
Additional battery  
connector  
バッテリ信  
OUTPUT AC100-120V 50/60Hz 1ø  
出力電力 最大1.5kVA 1500W  
/
Battery connection cable  
Additional battery signal connector  
2-2-3 BUM300S connection procedure / Connectable UPS : BU3002SW  
(1) Connect the battery connection cable to the battery connectors on the rear side of the unit and UPS.  
Connect the signal connection cable to the additional battery signal connector also.  
(2) Turn ON the overcurrent protection switch on the back of the battery unit. Connect the AC input plug of the  
unit to a wall outlet. The additional battery lamp on the unit's operation panel turns ON.  
When a 2100W device is connected, the backup time  
is 24 minutes (initial battery value at an ambient  
temperature of 20°C).  
When the battery is completely discharged, it takes 24  
hours to charge.  
UPS  
BUM300S  
Additional battery  
connection  
Battery connection  
cable  
Additional battery  
signal connection  
Additional battery  
connection  
Additional battery  
signal connection  
Overcurrent protection  
switch  
ON     
OFF  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Replacing the battery  
The battery can be replaced while the UPS is stopped. (power supply output stopped)  
Caution  
When an additional battery unit (BUM100S/BUM150S/BUM300S) is connected to the UPS, replace the UPS  
battery when replacing the batteries of the additional battery unit. You cannot perform battery replacement  
of the additional battery unit only.  
Caution  
When the UPS is used in compliance with UL, CE standards, do not replace the battery while in operation  
(while power is being output). Replacing the battery while in operation does not comply with UL, CE standards.  
Replace the battery while UPS operation is stopped.  
* To replace the battery while the UPS is stopped, stop the connected devices, turn OFF the power switch of  
the UPS, and disconnect the AC input plug from the wall outlet.  
* If an input power supply error such as a power failure occurs when replacing the battery while in operation,  
backup cannot be performed and output stops.  
* Do not replace the battery during backup operation. Output will stop.  
Additional battery unit (BUM100S/BUM150S) replacement procedure  
For information on UPS battery replacement procedure, refer to the UPS instruction manual.  
1. Use a screwdriver to loosen (anti-clockwise rotation) the 2 screws at the top of the front panel of the  
additional battery unit until they turn freely. (The screws cannot be removed from the front panel.)  
Pull the front panel towards you to remove it. ➀  
Loosen the 2 screws.  
1
2. Remove the 2 battery connectors from the plate cover and disconnect the connectors. ➁  
Battery connectors  
Hold here to  
disconnect.  
2
Plate cover  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Remove (anti-clockwise rotation) the 2 screws that hold the plate cover in place.  
Pull the plate cover towards you , and lift it up to remove it. ➂  
Remove the 3 screws.  
4. Remove both battery packs by pulling on the pullout label at the bottom of each battery pack.  
Caution  
Do not hold the connector of cable of the battery pack.  
Red tape  
Use the red tape on top of the battery pack, which is 10 cm  
from the inner edge of the battery, to gauge how much  
further you need to pull the battery to remove it. Hold the  
battery securely with both hands so as not to drop it.  
Battery connector  
Battery pack  
Pullout label  
(Pull here to remove the  
battery pack.)  
5. Insert 2 new battery packs into the additional battery unit as far as they will go. ➀  
Replacement battery pack  
For BUM100S : Model number BP100XS (2 required)  
For BUM150S : Model number BP150XS (2 required)  
Attach the plate cover.  
Insert the tab at the bottom of the cover into the hole in the main body , and push the plate cover towards  
the main body. ➂  
Use a screwdriver to securely tighten (clockwise) the 3 removed screws.  
Do not pinch the cable with the plate cover.  
Tighten the 3 screws.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Securely connect the connectors. ➀  
Secure the connectors to the plate cover.  
You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s  
operation is stopped, but this sound is not abnormal.  
2
Use the 3 supports on  
the plate cover to  
secure the connectors.  
1
If you cannot secure a connector to the plate cover, the connector is not completely  
connected.  
Connect the connector again.  
7.  
Attach the front panel.  
Insert the tab at the bottom of the front panel into the hole in the main body , and push the plate cover  
towards the main body. ➁  
Use a screwdriver to securely tighten (clockwise) the 2 screws at the top of the front panel.  
Tighten the 2 screws.  
1
2
Battery replacement is complete.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Additional battery unit (BUM300S) replacement procedure  
For information on UPS battery replacement procedure, refer to the UPS instruction manual.  
1.  
Use a screwdriver to loosen (anti-clockwise rotation) the 4 screws on the front panel of the additional battery  
unit until they turn freely.  
Loosen the  
4 screws.  
1
2.  
Remove the battery connector from the plate cover and disconnect the connector. ➁  
Battery connector  
Disconnect by holding here.  
1
2
Plate cover  
3.  
Remove (anti-clockwise rotation) the 2 screws that hold the plate cover in place. ➀  
While pulling the plate cover toward you , lift it up and remove the 2 lower battery connectors from the  
eyehole. ➂  
2
Remove the 3 screws.  
3
1
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.  
Remove the 4 battery packs by pulling on the pullout label at the bottom of each battery pack.  
Caution  
Do not hold the connector of cable of the battery pack.  
Use the red tape on top of the battery pack, which is 10 cm  
Red tape  
from the inner edge of the battery, to gauge how much  
further you need to pull the battery to remove it. Hold the  
battery securely with both hands so as not to drop it.  
Battery connector  
Battery pack  
Pullout label  
(Pull here to remove the  
battery pack.)  
5.  
Insert 4 new battery packs into the additional battery unit as far as they will go. ➀  
Replacement battery pack  
For BUM300S : Model number BP150XS (4 required)  
Attach the plate cover.  
Align the teardrop-shaped screw hole at the top of the plate cover with the additional battery unit's top screw  
hole. ➁  
Use a screwdriver to securely tighten (turn clockwise) the 3 removed screws. ➂  
Do not pinch the cable with the plate cover.  
2
Tighten the 3 screws.  
1
3
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Securely connect the connectors. ➀  
Secure the connectors to the plate cover.  
You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s  
operation is stopped, but this sound is not abnormal.  
2
Use the 2 supports at  
the top and bottom of  
the plate cover to secure  
the connectors.  
1
If you cannot secure a connector to the plate cover, the connector is not completely  
connected.  
Connect the connector again.  
7.  
Attach the front panel.  
Push the front panel toward the main body. ➀  
Use a screwdriver to securely tighten (clockwise) the 4 screws at the top of the front panel.  
Tighten the 4 screws.  
1
2
Battery replacement is now complete.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
<After replacing the battery during operation...>  
Press the beep stop/test button for 5 to 10 seconds, to perform a self-diagnostic test. Normal operation  
resumes after the test for about 10 second. If the beeping sounds, the beeping stops at the first press of  
the button and starts test in the second press of the button.  
If the battery replacement indicator is ON and beep sounds before replacing the battery, the indicator is  
OFF and beep stops after test completion, and normal operation resumes.  
<After replacing the battery with operation stopped...>  
Connect the AC input plug to a wall outlet (commercial power), and turn ON the power switch of the  
UPS. When operation starts, the self-diagnostic test is automatically performed. Normal operation  
resumes after the 10-second test.  
Write the usage start date on the label on the top side. Also, if using the UPS monitoring software  
included with the UPS, keep a record of the software usage start date.  
Notes  
This unit uses a lead acid battery.  
Lead acid batteries are a valuable recyclable resource. Please recycle.  
For information about recycling, please contact our peripheral device repair center.  
Pb  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
BUM100S/BUM150S  
<Unit: mm/Tolerance: 1mm>  
145  
BUM100S  
15  
395  
402  
4  
screw  
285  
64  
BUM300S  
<Unit: mm/Tolerance: ±1mm>  
3
360  
99  
213  
21  
BUM300S  
509  
329  
28  
299  
402  
117  
66  
K1L-D-05096C  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Ventilation Hood DA 398 5 User Manual
MTD Tiller 21A 410 022 User Manual
Northern Industrial Tools Air Compressor 2 HP 8 GALLON AIR COMPRESSOR User Manual
Onkyo MP3 Docking Station DS A2X User Manual
Onkyo Portable DVD Player DV SP501 User Manual
Optima Company Stud Sensor EL 1500 User Manual
Oregon Scientific Digital Camera DS 3868 User Manual
Orion Car Audio Car Speaker HCCA52 User Manual
Panasonic Ventilation Hood FV 07VB1 User Manual
Parker Products Video Game Keyboard OPS1200 User Manual