Omega Weather Radio CNI16 User Manual

MADE IN  
USA  
Use r s Gu id e  
Shop on line at  
www.omega.com  
e-mail: info@omega.com  
iSeries info:  
www.omega.com/specs/iseries  
Te m p e ra tu re & Pro ce ss Co n tro lle r Ma n u a l  
CNi8, CNi8C, CNi8DH, CNi8DV,  
CNi16, CNi16D, CNi32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Part 1: Introduction............................................................................................2  
1.1  
1.2  
1.3  
Description .................................................................................2  
Safety Considerations ...............................................................3  
Before You Begin .......................................................................4  
Part 2: Setup.......................................................................................................5  
2.1  
2.2  
2.3  
Front Panel .................................................................................6  
Rear Panel Connections............................................................7  
Electrical Installation .................................................................7  
2.3.1 Power Connections........................................................7  
2.3.2 Thermocouple - Input Connection................................8  
2.3.3 Two / Three / Four Wire RTD-Hookups.........................9  
2.3.4 Process Current - Wiring Hookup...............................10  
2.3.5 Process Voltage - Wiring Hookup...............................10  
2.3.6 Wiring Outputs - Wiring Hookup.................................11  
2.3.7 Dual Display Color Setup ............................................13  
Part 3: Operation: Configuration Mode .........................................................14  
3.1  
Introduction ..............................................................................14  
Turning your Instrument On for the First Time  
Buttons Functions in Configuration Mode  
3.2  
Menu Configuration ................................................................15  
3.2.1 ID Number .....................................................................16  
3.2.2 Setpoints.......................................................................17  
3.2.3 Configuration Menu ....................................................18  
3.2.4 Input Type Menu...........................................................18  
Input Type (Thermocouple) ........................................19  
Input Type (RTD)...........................................................20  
Input Type (Process) ...................................................21  
3.2.5 Reading Configuration Menu .....................................21  
3.2.6 Alarm 1 Menu ...............................................................25  
3.2.7 Analog Output (Retransmission) Menu......................29  
3.2.8 Alarm 2 Menu................................................................32  
3.2.9 Loop Break Time Menu/Field Calibration...................33  
3.2.10 Output 1 Menu ..............................................................35  
3.2.11 Output 2 Menu ..............................................................42  
3.2.12 Ramp and Soak Menu..................................................45  
3.2.13 ID Code Menu ...............................................................47  
3.2.14 Communication (Options) Menu.................................49  
3.2.15 Display Color Selection Menu.....................................55  
Part 4: Specifications ......................................................................................58  
Part 5: Factory Preset Values .........................................................................62  
Part 6: CE APPROVAL INFORMATION...........................................................64  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIST OF FIGURES:  
Figure 2.1  
Figure 2.2  
Figure 2.3  
Figure 2.4  
Figure 2.5  
Figure 2.6  
Front Panel Display..............................................................................5  
Rear Panel Power and Output Connector Labels..............................6  
Rear Panel Input Connector Labels....................................................6  
Main Power Connections.....................................................................7  
Thermocouple Wiring Hookup ............................................................8  
Two/Three/Four-wire RTD  
a) RTD-1000 ohm and 500 ohm Wiring Hookup ..............................9  
b) RTD-100 ohm Wiring Hookup .......................................................9  
Process Current Wiring Hookup  
Figure 2.7  
Figure 2.8  
(Internal and External Excitation) .....................................................10  
Process Voltage Wiring Hookup  
a) Without Sensor Excitation ..........................................................10  
b) With Sensor Excitation................................................................10  
Output Connections:  
Figure 2.9  
a) Mechanical Relay and SSR Outputs – Wiring Hook up............11  
b) Pulse and Analog Outputs – Wiring Hook up............................11  
Typical Application .............................................................................11  
Communication Output:  
Figure 2.10  
Figure 2.11  
a) RS-232 Output – Wiring Hook up ...............................................12  
b) RS-485 Output – Wiring Hook up ...............................................12  
Excitation Output................................................................................12  
Snubber Circuits Wiring Hookup......................................................12  
i/8DH and i/8DV Locations of S1 and Jumper Positions ................13  
i/16D Location of S1 and Jumper Positions ....................................13  
Flow Chart for ID and Setpoints........................................................15  
Flow Chart for Configuration Menu ..................................................18  
Flow Chart for Input Type Menu........................................................18  
Flow Chart for Reading Configuration .............................................21  
Flow Chart for Alarm 1.......................................................................25  
Flow Chart for Analog Output (Retransmission).............................29  
Flow Chart for Alarm 2.......................................................................32  
Flow Chart for Loop Break Time/Field Calibration..........................33  
Flow Chart for Output 1 .....................................................................35  
Flow Chart for Output 2 .....................................................................42  
Flow Chart for Ramp and Soak .........................................................45  
Flow Chart for ID Code.......................................................................47  
Flow Chart for Communication Option ............................................49  
Flow Chart for Display Color Selection............................................55  
Figure 2.12  
Figure 2.13  
Figure 2.14  
Figure 2.15  
Figure 3.1  
Figure 3.2  
Figure 3.3  
Figure 3.4  
Figure 3.5  
Figure 3.6  
Figure 3.7  
Figure 3.8  
Figure 3.9  
Figure 3.10  
Figure 3.11  
Figure 3.12  
Figure 3.13  
Figure 3.14  
LIST OF TABLES:  
Table 2.1  
Table 2.2  
Table 2.3  
Table 2.4  
Table 3.1  
Table 3.2  
Table 4.1  
Table 5.1  
Front Panel Annunciators....................................................................5  
Rear Panel Connector..........................................................................6  
Fuse Requirement ................................................................................7  
TC Wire Color Chart .............................................................................8  
Button Function in Configuration Mode...........................................14  
Conversion Table................................................................................24  
Input Properties..................................................................................61  
Factory Preset Values ........................................................................62  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES, WARNINGS and CAUTIONS  
Information that is especially important to note is identified by following labels:  
• NOTE  
• WARNING or CAUTION  
• IMPORTANT  
• TIP  
NOTE: Provides you with information that is important to successfully  
setup and use the Programmable Digital Meter.  
CAUTION or WARNING: Tells you about the risk of electrical shock.  
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or  
practices that can effect the instrument’s functionality and must refer  
to accompanying documents.  
TIP: Provides you helpful hints.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
PART 1  
INTRODUCTION  
1.1 Description  
This device can be purchased as monitor (read process value only) or as  
a controller.  
The iSeries controller offers unparalleled flexibility in process measurement.  
Each unit allows the user to select the input type, from 10 thermocouple  
types (J, K, T, E, R, S, B, C, N and J DIN), Pt RTDs (100, 500 or 1000 Ω,  
with either 385 or 392 curve), DC voltage, or DC current. The voltage/current  
inputs are fully scalable to virtually all engineering units, with selectable  
decimal point, perfect for use with pressure, flow or other process input.  
The temperature control can be achieved by using on/off or PID heat/cool  
control strategy. Control can be optimized with an auto tune feature. The  
instrument offers a ramp to setpoint with timed soak period before switching  
off the output.  
The iSeries device features a large, three color programmable display with  
capability to change a color every time the Alarm is triggered. The standard  
features include dual outputs with relay, SSR, dc pulse, analog voltage or  
current. Options include programmable RS-232 or RS-485 serial  
communication and excitation. Analog Output is fully scalable and may be  
configured as a proportional controller or retransmission to follow your  
display. Universal power supply accepts 90 to 240 Vac. Low voltage power  
option accepts 24 Vac or 12 to 36 Vdc.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.2 Safety Considerations  
This device is marked with the international caution symbol. It is important  
to read this manual before installing or commissioning this device as it  
contains important information relating to Safety and EMC  
(Electromagnetic Compatibility).  
This instrument is a panel mount device protected in accordance with  
EN 61010-1:2001, electrical safety requirements for electrical equipment  
for measurement, control and laboratory. Installation of this instrument  
should be done by qualified personnel. In order to ensure safe operation,  
the following instructions should be followed.  
This instrument has no power-on switch. An external switch or circuit-  
breaker shall be included in the building installation as a disconnecting  
device. It shall be marked to indicate this function, and it shall be in close  
proximity to the equipment within easy reach of the operator. The switch or  
circuit-breaker shall meet the relevant requirements of IEC 947–1 and  
IEC 947-3 (International Electrotechnical Commission). The switch shall  
not be incorporated in the main supply cord.  
Furthermore, to provide protection against excessive energy being drawn  
from the main supply in case of a fault in the equipment, an overcurrent  
protection device shall be installed.  
Do not exceed voltage rating on the label located on the top of the  
instrument housing.  
Always disconnect power before changing signal and power  
connections.  
Do not use this instrument on a work bench without its case for safety  
reasons.  
Do not operate this instrument in flammable or explosive atmospheres.  
Do not expose this instrument to rain or moisture.  
Unit mounting should allow for adequate ventilation to ensure  
instrument does not exceed operating temperature rating.  
Use electrical wires with adequate size to handle mechanical strain  
and power requirements. Install without exposing bare wire outside the  
connector to minimize electrical shock hazards.  
EMC Considerations  
Whenever EMC is an issue, always use shielded cables.  
Never run signal and power wires in the same conduit.  
Use signal wire connections with twisted-pair cables.  
Install Ferrite Bead(s) on signal wires close to the instrument if EMC  
problems persist.  
Failure to follow all instructions and warnings may result in injury!  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.3 Before You Begin  
Inspecting Your Shipment:  
Remove the packing slip and verify that you have received everything  
listed. Inspect the container and equipment for signs of damage as soon  
as you receive the shipment. Note any evidence of rough handling in  
transit. Immediately report any damage to the shipping agent. The carrier  
will not honor damage claims unless all shipping material is saved for  
inspection. After examining and removing the contents, save the packing  
material and carton in the event reshipment is necessary.  
Customer Service:  
If you need assistance, please call the nearest Customer Service  
Department, listed in this manual.  
Manuals, Software:  
The latest Operation and Communication Manual as well as free  
configuration software and ActiveX controls are available from the  
website listed in this manual or on the CD-ROM enclosed with your  
shipment.  
For first-time users: Refer to the QuickStart Manual for basic operation  
and set-up instructions.  
If you have the Serial Communications/Ethernet Option you can easily  
configure the controller on your computer or on-line.  
To Disable Outputs:  
To ensure that menu changes are properly stored, Standby Mode should  
be used during setup of the instrument. During Standby Mode, the  
instrument remains in a ready condition, but all outputs are disabled.  
Standby Mode is useful when maintenence of the system is necessary.  
When the instrument is in "RUN" Mode, push d twice to disable all  
outputs and alarms. It is now in "STANDBY" Mode. Push d once more  
to resume "RUN" Mode.  
PUSH d TWICE to disable the system during an EMERGENCY.  
To Reset the Meter:  
When the controller is in the "MENU" Mode, push c once to direct  
controller one step backward of the top menu item.  
Push c twice to reset controller, prior to resuming "Run" Mode except  
after "Alarms", that will go to the "Run" Mode without resetting the  
controller.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refer to the Quick Start  
Guide for assembly and  
disassembly instructions.  
PART 2  
SETUP  
2.1 Front Panel  
Figure 2.1 Front Panel Display  
Table 2.1 Front Panel Annunciators  
1
2
°C  
°F  
PV  
SV  
a
Output 1/Setpoint 1/ Alarm 1 indicator  
Output 2/Setpoint 2/ Alarm 2 indicator  
°C unit indicator  
°F unit indicator  
Upper Display shows the Process Value  
Lower Display shows the Setpoint 1 Value  
Changes display to Configuration Mode  
and advances through menu items*  
Used in Program Mode and Peak Recall*  
Used in Program Mode and Valley Recall*  
Accesses submenus in Configuration Mode  
and stores selected values*  
b
c
d
* See Part 3 Operation: Configuration Mode  
The Dual Display model allows the user to observe the Process Value  
(upper display) and Setpoint 1 Value (lower display) at the same time.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2 Rear Panel Connections  
The rear panel connections are shown in Figures 2.2 and 2.3.  
6
5
4
6
5
4
6
5
4
3
2
1
3
2
1
8
7
6
5
4
3
2
1
Figure 2.2 Rear Panel Power and Output Connections  
Figure 2.3 Rear Panel Input Connections  
Table 2.2 Rear Panel Connector  
POWER  
AC/DC Power Connector: All models  
Input Connector:  
INPUT  
All models TC, PR (Process), RTD  
OUTPUT 1 Based on one of the following models:  
Relay SPDT  
Solid State Relay  
Pulse  
Analog Output (Voltage and Current)  
OUTPUT 2 Based on one of the following models:  
Relay SPDT  
Solid State Relay  
Pulse  
Based on one of the following models:  
OPTION  
RS-232C or RS-485 programmable  
Excitation  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3 Electrical Installation  
2.3.1 Power Connections  
Caution: Do not connect power to your device until you have completed all  
input and output connections. Failure to do so may result in injury!  
Connect the main power connections as shown in Figure 2.4.  
Use copper conductors  
only for power connections  
Figure 2.4 Main Power Connections  
Table 2.3 Fuse Requirement (see specifications)  
FUSEConnector  
Output  
Power  
Power  
Type  
N/A  
N/A  
For  
115Vac  
100 mA(T)  
N/A  
For  
100 mA(T)  
400 mA(T)  
230Vac  
FUSE 1  
FUSE 2  
100 mA(T)  
N/A  
For the low voltage power option, in order to maintain the same degree of  
protection as the standard high voltage input power units (90 - 240 Vac),  
always use a Safety Agency Approved DC or AC source with the same  
Overvoltage Category and pollution degree as the standard AC unit (90 -  
240 Vac).  
The Safety European Standard EN61010-1 for measurement, control,  
and laboratory equipment requires that fuses must be specified based on  
IEC127. This standard specifies for a Time-lag fuse, the letter code “T”.  
The above recommended fuses are of the type IEC127-2-sheet III. Be  
aware that there are significant differences between the requirements  
listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a  
result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse  
is approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to  
consult the manufacturer’s data sheets for a cross-reference.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3.2 Thermocouple  
The figure below shows the wiring hookup for any thermocouple type. For  
example, for Type K hookup, connect the yellow wire to the "2" terminal and the  
red wire to the "1(-)" terminal.  
When configuring your controller, select Thermocouple and Thermocouple  
Type in the Input Type menu (see Part 3).  
Figure 2.5 Thermocouple Wiring Hookup  
Table 2.4 TC Wire Color Chart  
TYPEInput  
Connector  
Jacket  
Extension  
dark-Brown  
(external  
Grade  
Black  
insulation)  
Terminal 1 (-) Terminal 2 (+)  
J
K
T
Red  
Red  
Red  
Red  
Red  
Red  
Red  
Red  
White  
Yellow  
Blue  
dark-Brown  
dark-Brown  
Yellow  
Blue  
E
N
R
S
B
Purple  
Orange  
Black  
Black  
Gray  
dark-Brown  
dark-Brown  
Purple  
Brown  
Green  
Green  
Black  
-
-
-
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3.3 Two/Three/Four-Wire RTD  
The figures below show the input connections and input connector jumpers  
(shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD.  
RTD (100) 4-Wire  
RTD (1000/500) 4-Wire  
RTD (100) 3-Wire  
RTD (1000/500) 3-Wire  
RTD (100) 2-Wire  
RTD (1000/500) 2-Wire  
Figure 2.6 a) RTD-1000 ohm and  
500 ohm Wiring Hookup  
b) RTD-100 ohm Wiring Hookup  
The two-wire connection is simplest method, but does not compensate for  
lead-wire temperature change and often requires calibration to cancel lead-wire  
resistance offset.  
The three-wire connection works best with RTD leads closely equal in  
resistance. The device measures the RTD, plus upper and lower lead drop  
voltage and the subtracts twice the measured drop in the lower supply current  
lead producing excellent lead-resistance cancellation for balanced  
measurements.  
The four-wire RTD hookup is applicable to unbalanced lead resistance and  
enables the device to measure and subtract the lead voltage, which produces  
the best lead-resistance cancellation.  
When configuring your controller, select RTD type and RTD value in the  
Input Type menu (see Part 3).  
If the input wires of the meter get disconnected or broken, it will display  
+OPN “Input (+) Open” message except in case of 500/1000 Ω 2-wire  
RTD. In this case the display shows -OPN “Input (-) Open” message. For  
safety purpose you may want to set up your alarm to be triggered when  
input is open. See Alarm 1 & 2 chapters for details.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3.4 Process Current  
The figure below shows the wiring hookup for Process Current 0 – 20 mA.  
Figure 2.7 Process Current Wiring Hookup  
(Internal and External Excitation)  
When configuring your instrument, select Process Type in the Input Type Menu  
(see Part 3).  
2.3.5 Process Voltage  
The figure below shows the wiring hookup for Process Voltage 0 – 100 mV,  
0 – 1 V, 0 – 10 V.  
Figure 2.8  
a) Process Voltage Wiring Hookup b) Process Voltage Wiring Hookup  
with Sensor Excitation  
without Sensor Excitation  
RL - Voltage limited resistor, which allows to convert 24 Vdc internal excitation  
voltage to the appropriate process input value. For instance: if the potentiometer  
value is equal to 10 kΩ, the minimum RL is 14 kΩ for 10 V process input.  
When configuring your instrument, select Process Type in the Input Type Menu  
(see Part 3).  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3.6 Wiring Outputs  
This meter has two factory installed outputs. The SPDT Mechanical Relay, SPST  
Solid State Relay, Pulse and Analog Output Connection are shown below.  
Use copper conductors  
only for power connections  
Figure 2.9  
a) Mechanical Relay and SSR  
Outputs Wiring Hookup  
b) Pulse and Analog  
Outputs Wiring Hookup  
dc CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH dc VOLTAGE SSR DRIVER OUTPUT  
TEMPERATURE  
CONTROLLER  
dc INPUT  
CONTROL  
SIDE  
LOAD  
SIDE  
SSR  
HEATER  
4
3
1
2
Vac  
Vac  
0 or 5 Vdc,  
TYPICALLY  
FAST BLOW  
FUSE  
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT  
TEMPERATURE  
CONTROLLER  
ac INPUT  
CONTROL  
SIDE  
LOAD  
SIDE  
SSR  
HEATER  
4
3
1
2
Vac  
Vac  
FAST BLOW  
FUSE  
Vac  
DRIVING  
SSR  
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT  
CONTROL SIDE  
TEMPERATURE  
ac INPUT  
LOAD  
LOAD  
SIDE  
CONTROLLER  
SSR  
RESISTOR  
HEATER  
4
3
1
2
Vac  
Vac  
FAST BLOW  
FUSE  
Vac  
DRIVING  
SSR  
Figure 2.10 Typical Applications  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This device may have a programmable communication output. The  
RS-232 and RS-485 Output Connection are shown below.  
External RS-232 connections are not available with -EI or C4EI options.  
Figure 2.11  
a) RS-232 Output Wiring Hookup b) RS-485 Output Wiring Hookup  
This device may also have an  
excitation output.  
If the Dual Display model has a Low  
Voltage power supply option, then  
excitation is not available.  
Excitation is not available if  
communication option is installed.  
Figure 2.12 Excitation Output  
This device has snubber circuits  
designed to protect the contacts of the  
mechanical relays when it switches to  
inductive loads (i.e. solenoids, relays).  
These snubbers are internally  
connected between the Common (C)  
and Normally Open (NO) relay contacts  
of Output 1 and Output 2.  
If you have an inductive load  
connected between Common (C) and  
Normally Closed (NC) contacts of the  
mechanical relays and you want to  
protect them from the rush current  
during the switching period, you have  
to connect an external snubber circuit  
between Common (C) and Normally  
Closed (NC) contacts as indicated in  
Figure 2.13.  
Figure 2.13  
Snubber Circuits Wiring  
Hookup  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3.7 Dual Display Color Setup  
The dual display option allows the user to change the color of the upper and  
lower displays.  
To change the color of the upper display, see Section 3.2.15  
(Display Color section).  
To change the color of the lower display follow the instructions below:  
The unit should be removed from the panel and opened.  
Refer to the Quick Start Guide for assembly and disassembly instructions.  
The S1 jumper is located on the back side of the display board.  
The location of S1 and pin selection jumpers are shown below.  
Use a jumper for GREEN or RED, never leave S1 open.  
i/8DH  
Dual  
Horizontal  
i/8DV  
Dual  
Vertical  
Figure 2.14 i/8D Location of S1 and Selectable Jumper Positions  
Figure 2.15 i/16D Location of S1 and Selectable Jumper Positions  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PART 3  
OPERATION: Configuration Mode  
3.1 Introduction  
The instrument has two different modes of operation. The first, Run Mode, is  
used to display values for the Process Variable, and to display or clear Peak  
and Valley values. The other mode, Menu Configuration Mode, is used to  
navigate through the menu options and configure the controller. Part 3 of this  
manual will explain the Menu Configuration Mode. For your instrument to  
operate properly, the user must first "program" or configure the menu options.  
Turning your Controller On for the First Time  
The device becomes active as soon as it is connected to a power source. It  
has no On or Off switch. The device at first momentarily shows the software  
version number, followed by reset  
, and then proceeds to the Run Mode.  
RST  
For first-time users: Refer to the QuickStart Manual for basic operation  
and set-up instructions.  
If you have the Serial Communications/Ethernet Option you can easily  
configure the controller on your computer or on-line.  
Table 3.1 Button Function in Configuration Mode  
To enter the Menu, the user must first press button.  
a
• Use this button to advance/navigate to the next menu item. The user can navigate  
a
MENU  
through all the top level menus by pressing  
.
a
• While a parameter is being modified, press to escape without saving the parameter.  
a
Press the up button to scroll through “flashing” selections. When a numerical value is  
b
displayed press this key to increase value of a parameter that is currently being modified.  
• Holding the button down for approximately 3 seconds will speed up the rate at which  
the set point value increments.  
b
b
(UP)  
• In the Run Mode press causes the display to flash the PEAK value – press again to  
b
return to the Run Mode.  
Press the down button to go back to a previous Top Level Menu item.  
c
Press this button twice to reset the controller to the Run Mode.  
• When a numerical value is flashing (except set point value) press to scroll digits from  
c
left to right allowing the user to select the desired digit to modify.  
c
(DOWN)  
• When a setpoint value is displayed press to decrease value of a setpoint that is  
c
currently being modified. Holding the button down for approximately 3 seconds will  
c
speed up the rate at which the setpoint value is decremented.  
• In the Run Mode press c causes the display to flash the VALLEY value – press again to  
return to the Run Mode.  
Press the enter d button to access the submenus from a Top Level Menu item.  
Press d to store a submenu selection or after entering a value — the display will flash a  
d
ENTER  
message to confirm your selection.  
STRD  
To reset flashing Peak or Valley press d.  
• In the Run Mode, press d twice to enable Standby Mode with flashing  
.
STBY  
Reset: Except for Alarms, modifying any settings of the menu configuration  
will reset the instrument prior to resuming Run Mode.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2 Menu Configuration  
It is required that you put the controller in the Standby Mode for any  
configuration change other than Setpoints & Alarms.  
Figure 3.1 Flow Chart for ID and Setpoints  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.1 ID Number  
SEE ID MENU SELECTION IN CONFIGURATION SECTION FOR  
ENABLE/DISABLE OR CHANGE ID CODE.  
If ID Code is Disabled or set as Default (0000) the menu will skip ID step  
to Setpoint Menu.  
If ID Code is set to Full Security Level and user attempts to enter the  
Main Menu, they will be prompted for an ID Code.  
If ID Code is set to Setpoint/ID Security Level and user attempts to enter  
the Configuration Menu, they will be prompted for an ID Code.  
ENTERING YOUR NON-DEFAULT FULL SECURITY ID NUMBER.  
Press a  
1) Display shows  
.
ID  
2) Display advances to  
Press d  
.
____  
Press b & c 3) Press to increase digit 0-9. Press to activate next digit  
b
c
(flashing). Continue to use and c to enter your 4-digit ID  
b
code.  
Press d  
4) If the correct ID code is entered, the menu will advance to the  
Setpoint 1 Menu, otherwise an error message  
will be  
ERRo  
displayed and the instrument will return to the Run Mode.  
To change ID Code, see ID Menu in the Configuration section.  
ENTERING YOUR NON-DEFAULT SETPOINT/ID SECURITY ID NUMBER.  
Press a  
Press a  
Press a  
Press d  
5) Display shows  
6) Display shows  
7) Display shows  
Setpoint 1 Menu.  
Setpoint 2 Menu.  
SP1  
SP2  
ID Code Menu.  
ID  
8) Display advances to  
.
____  
Press b & c 9) Use b and c to change your ID Code.  
Press d 10) If correct ID Code is entered, the display will advance to the  
Input Menu, otherwise the error message will be  
INPT  
ERRo  
displayed and the controller will return to the Run Mode.  
To prevent unauthorized tampering with the setup parameters, the  
instrument provides protection by requiring the user to enter the ID Code  
before allowing access to subsequent menus. If the ID Code entered  
does not match the ID Code stored, the controller responds with an error  
message and access to subsequent menus will be denied.  
Use numbers that are easy for you to remember. If the ID Code is  
forgotten or lost, call customer service with your serial number to access  
and reset the default to  
.
0000  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.2 Set Points  
SETPOINT 1:  
Press a  
1) Press a, if necessary until  
prompt appears.  
SP1  
Press d  
2) Display shows previous value of “Setpoint 1”.  
Press b & c 3) Press b and c to increase or decrease Setpoint 1  
respectively.  
Holding b & c buttons down for approximately 3 seconds will speed up the  
rate at which the Setpoint value increments or decrements.  
Press b & c 4) Continue to use b and c to enter your 4-digit Setpoint 1 value.  
Press d  
5) Display shows  
stored message momentarily and then  
STRD  
only, if a change was made, otherwise press  
advances to  
SP2  
a to advance to  
Setpoint 2 Menu.  
SP2  
SETPOINT 2:  
Press d  
6) Display shows previous value of “Setpoint 2”.  
Press b & c 7) Press b and c to increase or decrease Setpoint 2  
respectively.  
Holding b & c buttons down for approximately 3 seconds will speed up  
the rate at which the setpoint value increments or decrements.  
Press d  
8) Display shows  
stored message momentarily and then  
STRD  
only, if a change was made, otherwise press  
advances to  
CNFG  
a to advance to  
Configuration Menu.  
CNFG  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.3 Configuration Menu  
Figure 3.2 Flow Chart for Configuration Menu  
Enter Configuration Menu:  
Press a  
Press d  
Press a  
1) Press a, if necessary, until  
prompt appear.  
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Pressing and releasing a to scroll through all available  
menus of Configuration section.  
3.2.4 Input Type Menu  
Figure 3.3 Flow Chart for Input Type Menu  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input Type (Thermocouple)  
ENTER INPUT TYPE MENU:  
Press a  
Press d  
Press d  
1) Press a, if necessary, until  
prompt appears.  
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Display flashes  
,
or  
(Thermocouple, RTD or  
, press a to skip to  
T.ç RTD PROC  
Process). If the displayed input type is  
T.ç  
step 6 ( stops flashing).  
T.ç  
THERMOCOUPLE SUBMENU:  
Press b  
4) Scroll through the available selection to  
(flashing).  
T.ç  
stored message momentarily and then  
Press d  
5) Display shows  
STRD  
(not flashing).  
T.ç  
Press d  
Press b  
Press d  
6) Display flashes previous thermocouple type selection. i.e.  
J
(see below for types).  
7) Scroll through the available thermocouple types to the  
selection of your choice.  
8) Display shows  
stored message momentarily and then  
STRD  
Reading Configuration Menu.  
advances to the  
RDG  
Use the Input Type (Thermocouple) (RTD) or (Process) and verify your  
Electrical Installation (see section 2.3).  
Thermocouple Types: J, K, T, E, N, DIN J, R, S, B, C  
Display:  
J K T E N DNJ R S B C  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input Type (RTD)  
ENTER INPUT TYPE MENU:  
Press a  
Press d  
Press d  
1) Press a, if necessary, until  
prompt appears.  
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Display flashes  
,
or  
(Thermocouple, RTD or  
, press a to skip to  
T.ç RTD PROC  
Process). If the displayed input type is  
RTD  
step 6 ( stops flashing).  
RTD  
RTD SUBMENU:  
Press b  
4) Scroll through the available selection to  
(flashing).  
RTD  
stored message momentarily and then  
Press d  
5) Display shows  
STRD  
(not flashing).  
RTD  
Press d  
Press b  
Press d  
6) Display flashes previous RTD type selection i.e.  
392.2  
(see below for RTD types selection).  
7) Scroll through the available RTD types to the selection of  
your choice.  
8) Display shows  
stored message momentarily and then  
STRD  
advances to  
RTD value.  
RTD  
RTD Types: 392  
Display:  
385  
392.2 392.3 392.4 385.2 385.3 385.4  
Two, Three or Four-wire  
,
,
,
,
,
Last digit indicates: 2-, 3- or 4-wire input.  
RTD VALUE SUBMENU:  
Press d  
Press b  
Press d  
9) Display flashes previous RTD value selection i.e.  
100_  
(see below for RTD value selection).  
10) Scroll through the available RTD values to the selection of  
your choice.  
11) Display shows  
stored message momentarily and then  
STRD  
Reading Configuration Menu.  
advances to  
RDG  
RTD Values: 100 ohm  
Display:  
500 ohm  
500_  
1000 ohm  
1000  
100_  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input Type (Process)  
ENTER INPUT TYPE MENU:  
Press a  
Press d  
Press d  
1) Press a, if necessary, until  
prompt appears.  
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Display flashes  
,
or  
(Thermocouple, RTD or  
, press a to skip to  
T.ç RTD PROC  
Process). If the displayed input type is  
PROC  
step 6 ( stops flashing).  
PROC  
PROCESS SUBMENU:  
Press b  
4) Scroll through the available selection to  
(flashing).  
PROC  
stored message momentarily and then  
Press d  
5) Display shows  
STRD  
(not flashing).  
PROC  
Press d  
Press b  
Press d  
6) Display flashes previous Process type selection. i.e.  
0-10  
(see below for Process types selection).  
7) Scroll through the available Process types to the selection of  
your choice.  
8) Display shows  
stored message and then advances to  
STRD  
Reading Configuration Menu.  
RDG  
Process Types: 100 mV 1 V  
10 V  
0-0.1 0-1.0 0-10  
0 – 20 mA  
0-20  
Display:  
For 4-20 mA Input select 0-20 mA then adjust the Input/Reading accordingly.  
To adjust 4-20 mA input, see example under INPUT/READING submenu. The  
factory preset value is 4-20 mA.  
3.2.5 Reading Configuration  
It is required that you put the controller in the Standby Mode for any  
configuration change other than Set Points & Alarms.  
Figure 3.4 Flow Chart for Reading Configuration Menu  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ENTER READING CONFIGURATION MENU:  
Press  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
d
a
CNFG  
Input Menu.  
2) Display advances to  
3) Display advances to  
4) Display advances to  
INPT  
RDG  
DEC  
Reading Configuration Menu.  
Decimal Point.  
DECIMAL POINT SUBMENU:  
Press  
5) Display flashes previous selection for Decimal location.  
d
b
Press  
6) Scroll though the available selections and choose Decimal  
location:  
or  
FFFF FFF.F  
(also  
and  
— if  
F.FFF PROC  
FF.FF  
Process type was selected in the Input Type Menu).  
Press  
7) Display shows stored message momentarily and then  
d
STRD  
Temperature Unit.  
advances to  
TEMP  
Decimal Point for Process Input Type is passive.  
TEMPERATURE UNIT SUBMENU:  
Press  
8) Display flashes previous Temperature Unit selection.  
9) Scroll though the available selections to the Temperature Unit  
of your choice: or  
d
b
Press  
.
°F °C  
10) Display shows  
Press  
stored message momentarily and then  
d
STRD  
Filter Constant.  
advances to  
FLTR  
FILTER CONSTANT SUBMENU:  
Press  
11) Display flashes previous selection for Filter Constant.  
d
b
Press  
12) Scroll though the available selections:  
,
,
,
,
,
,
,
0001 0002 0004 0008 0016 0032 0064 0128  
Press  
13) Display shows  
stored message momentarily only, if  
STRD  
d
change was made, otherwise press to advance to the next  
a
menu.  
If Process was selected in the Input Type Menu the display will  
advance to  
Input/Reading Submenu, otherwise the  
IN.RD  
display advances to the  
Alarm 1 Menu.  
ALR1  
The Filter Constant Submenu allows the user to specify the  
number of readings stored in the Digital Averaging Filter.  
For PID control select filter value 0001-0004. A filter value of 2 is  
approximately equal to 1 second RC low pass time constant.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reading Configuration (If Process was selected)  
INPUT/READING (SCALE AND OFFSET) SUBMENU:  
Input Voltage or Current can be converted or scaled into values appropriate for  
the process or signal being measured. So, a reading may be displayed, for  
example, in units of weight or velocity instead of in amperes or volts.  
The instrument determines Scale and Offset values based on two user-provided  
input values entered with the corresponding readings. Note that “In1” Input 1 and  
“In2” Input 2 are represented and entered as a product of the input  
voltage/current and the conversion number from the Table 3.1.  
The following instructions include details for a specific scenario in which a  
4-20 mA input (in the 20 mA Process Mode) is to be represented as a  
measurement of 0-100 percent.  
Press  
14) Press at the  
prompt. Display shows  
Input 1  
IN1  
d
d
IN.RD  
submenu.  
st  
Press  
Press  
15) Display shows Input 1 value with 1 digit flashing.  
d
b
&
&
16) Use and buttons to enter  
value.  
c
b
c
IN1  
The  
value = min. input value * conversion number.  
IN1  
Disregard the position of the decimal point (2000 counts may  
actually appear as “200.0”, “20.00”, or “2.000”).  
Example: 4 mA as 4(mA) x 500 = 2000.  
Press  
Press  
17) Display advances to  
Reading 1 Submenu.  
RD1  
d
b
18) Use and buttons to enter  
value.  
c
b
c
RD1  
in terms of some meaningful  
This value represents  
IN1  
engineering units. To show the 4 mA as zero percent enter  
RD1  
value = 0000.  
RD1  
19) Display IN!2 Input 2 Submenu.  
Example:  
value = 0000.  
Press  
Press  
d
d
st  
20) Display shows Input 2 value with 1 digit flashing.  
The IN!2 value = max. input value * conversion number.  
Example: 20(mA) x 500 = 10000 (9999).  
Press  
Press  
Press  
&
&
21) Use and c buttons to enter IN!2 value.  
b
d
b
c
c
b
22) Display advances to RD!2 Reading 2 Submenu.  
23) Use b and c buttons to enter RD!2 value.  
Example: RD!2 value = 0100.  
Press  
24) Display flashes  
stored message momentarily and  
d
STRD  
only, if change was made, otherwise  
then advances to  
ALR1  
to advance to  
press  
Alarm 1 Menu.  
ALR1  
d
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Conversion number is a coefficient of conversion between input values  
and real full display range (10000 counts shown as 9999). See Table 3.2  
below for proper conversion number.  
Table 3.2 Conversion Table  
RANGE  
100 mV  
1 V  
10 V  
0 -20 mA  
CONVERSION NUMBER  
10000 / (100 x 1) = 100  
10000 / (1000 x 1) = 10  
10000 / (1000 x 10) = 1  
10000 / (20 x 1) = 500  
Example =  
0 - 1 V = 0 - 100.0  
In 1 = 0  
Rd 1 = 0  
Inp 2 = 9999  
Rd 2 = 100.0  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.6 Alarm 1  
This unit is equipped with two physical outputs that can only be configured as  
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output1  
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out  
available only if Analog Output Option board is factory installed.  
If Analog Output Option is installed, the controller will skip Alarm 1 Menu  
item to Analog Output.  
Alarm must be DISABLED if Ramp is ENABLED.  
Figure 3.5 Flow Chart for Alarm 1  
ENTER ALARM 1 MENU:  
Press a  
Press d  
Press a  
1) Press a, if necessary, until  
prompt appears.  
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press a, if necessary, until Display advances to  
Alarm 1  
ALR1  
Enable or Disable  
ENBL DSBL  
Menu.  
Press d  
4) Display advances to Alarm 1  
Submenu and flashes the previous selection.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALARM 1 ENABLE/DISABLE SUBMENU:  
Press b  
5) Scroll though the available selection until  
displays to  
ENBL  
use Alarm 1.  
Press d  
6) Display shows  
stored message momentarily and then  
STRD  
advances to  
only if it was changed, otherwise press a to  
ABSo  
advance to  
Alarm 1 Absolute/Deviation Submenu.  
ABSo  
If  
Alarm 1 Disabled was selected, all submenus of Alarm  
DSBL  
1 Menu will be skipped and meter advances to  
Alarm 2  
ALR2  
Alarm 1 Enabled was selected, Output 1 would  
Menu. If  
ENBL  
be automatically Disabled, and reassigned as Alarm 1.  
ALARM 1 ABSOLUTE/DEVIATION SUBMENU:  
Press  
7) Display flashes previous selection. Press to  
ABSo  
d
d
b
Absolute or  
Deviation.  
_DEV  
8) Display shows  
Press  
stored message momentarily and then  
STRD  
advances to  
only if it was changed, otherwise press a to  
LTçH  
advance to  
Alarm 1 Latch/Unlatch Submenu.  
LTçH  
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the  
process being monitored does not change often, then "Absolute" Mode is  
recommended.  
Deviation Mode allows changes to Setpoint 1 to be made automatically to  
Alarm 1. Deviation mode is typically the ideal mode if the process temperature  
changes often. In Deviation Mode, set Alarm 1 a certain number of degrees or  
counts away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is  
changed.  
ALARM 1 LATCH/UNLATCH SUBMENU:  
Press  
9) Display flashes previous selection. Press to  
LTçH  
d
d
b
Latched or  
Unlatched.  
UNLT  
10) Display shows  
Press  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press a to  
advances to  
CT.CL  
Contact Closure Submenu.  
advance to  
CT.CL  
Latched Mode: Relay remains "latched" until reset. To reset already latched  
alarm, select Alarm Latch and press Max twice (i.e. Unlatch and then back to  
Latch) or from a Run Mode, push twice to put the controller in Standby Mode  
d
and then push one more time to return to the Run Mode.  
d
Unlatched Mode: Relay remains latched only as long as the alarm condition is  
true.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTACT CLOSURE SUBMENU:  
Press  
11) Display flashes previous selection. Press b to  
Normally  
N.ç.  
d
Closed or  
Normally Open.  
N.o.  
12) Display shows  
Press  
stored message momentarily and then  
d
STRD  
advances to  
only if it was changed, otherwise press to  
AçTV  
a
advance to  
Active Submenu.  
AçTV  
Normally Open: If this feature is selected, then the relay is "energized" only  
when an alarm condition occurs.  
Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"  
conditions and becomes de-energized during alarm or power failure.  
ACTIVE SUBMENU:  
Press  
13) Display flashes previous selection. Press to scroll through  
d
b
Below,  
the available selections:  
Above,  
ABoV  
BELo  
_DEV  
HI.Lo  
Deviation was  
HI/Low and  
selected).  
Band. (Band is active if  
BAND  
Press  
14) Display shows  
stored message momentarily and then  
STRD  
d
advances to  
only if it was changed, otherwise press a to  
A.P.oN  
advance to  
Submenu.  
Alarm Enable/Disable at Power On  
A.P.oN  
Above: Alarm 1 condition triggered when the process variable is greater than the  
Alarm Hi Value (Low value ignored).  
Below: Alarm 1 condition triggered when the process variable is less than the  
Alarm Low Value (Hi value ignored).  
Hi/Low: Alarm 1 condition triggered when the process variable is less than the  
Alarm Low Value or above the Hi Value.  
Band: Alarm 1 condition triggered when the process variable is above or below  
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A  
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.  
The Band for the AL 1 would be following the Setpoint 1 value  
The Band for the AL 2 would be following the Setpoint 2 value.  
The Band or the Deviation Value should be entered under:  
AL1 High (if they want Alarm 1)  
AL2 High (if they want Alarm 2)  
AL Low value is ignored in the Band mode.  
Example: if customer requires a Deviation Value of 10 degrees around a  
setpoint (using Output 2 as alarm)  
Output 2: disabled (this enables the Alarm 2)  
Alarm 2: - Deviation  
Contact Closure type: Deviation---Band  
AL2 High: 10 (Band they want around Setpoint 2)  
Then the Band Value is to be entered under AL2 HI: 10 not 80+10 = 90  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALARM ENABLE/DISABLE AT POWER ON:  
Press 15) Display flashes previous selection. Press to enable  
ENBL  
d
b
or  
disable.  
DSBL  
16) Display shows  
Press d  
stored message. momentarily and then  
STRD  
only if it was changed, otherwise press to  
advances to  
ALR.L  
advance to the  
a
Alarm 1 Low Value Submenu.  
ALR.L  
If the alarm is enabled at Power On, the alarm will be active right after  
reset. If the alarm is disabled at Power On, the alarm will become  
enabled when the process value enters the non alarm area. The alarm is  
not active while the process value is approaching Setpoint 1.  
ALARM 1 LOW VALUE SUBMENU:  
st  
Press  
17) Display flashes 1 digit of previous value. Use and to  
d
b
c
enter new value.  
Press  
Press  
&
18) Use and to enter Alarm 1 Low Value.  
b
d
c
b
c
19) Display shows  
storage message momentarily and  
STRD  
ALR.H  
ALR.H  
then advances to  
only, if it was changed, otherwise press  
a to advance to  
Alarm 1 Hi Value Submenu.  
ALARM 1 HI VALUE SUBMENU:  
st  
Press  
20) Display flashes 1 digit of previous value. Use and to  
d
b
c
enter new value.  
Press  
Press  
&
21) Use and to enter Alarm1 Hi Value.  
b
d
c
b
c
22) Display shows  
stored message momentarily and then  
STRD  
advances to the next menu only, if it was changed, otherwise  
press to advance to the next menu.  
a
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.7 Analog Output (Retransmission)  
Analog Output can be configured as Retransmission or Control outputs.  
In this section we will discuss Retransmission Output.  
This unit is equipped with two physical outputs that can only be configured as  
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output  
1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog  
Output is available only, if Analog Output Option board is factory installed.  
If Analog Output Option is not installed, the instrument will skip to Alarm 2 Menu.  
Figure 3.6 Flow Chart for Analog Output (Retransmission)  
ENTER ANALOG OUTPUT MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
a
ANLG  
Analog Output Menu.  
Press  
4) Display advances to Analog Output  
Enable or  
ENBL DSBL  
d
Disable Submenu and flashes the previous selection.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANALOG OUTPUT ENABLE/DISABLE SUBMENU:  
Press  
5) Scroll though the available selection until  
displays to  
ENBL  
b
use Analog Output Retransmission (output proportional to the  
input signal).  
Press  
6) Display shows  
stored message momentarily and then  
d
STRD  
or  
advances to  
Submenu only if it was changed,  
CURR VoLT  
otherwise press a to advance to  
or  
CURR VoLT  
Current/Voltage Submenu.  
If  
Analog Output Disabled was selected, all submenus of Analog  
DSBL  
Output Menu will be skipped and the meter will advance to  
Alarm 2  
ALR2  
Analog Output Enabled was selected, Output 1 would be  
Menu. If  
ENBL  
automatically Disabled, and reassigned as Analog Output.  
CURRENT/VOLTAGE SUBMENU:  
Press  
7) Display flashes  
Current or Voltage.  
VoLT  
d
b
CURR  
8) Scroll through the available selection: Current or Voltage  
(Example ).  
Press  
VoLT  
9) Display shows  
Press  
stored message momentarily and then  
d
STRD  
Submenu only if it was changed, otherwise  
advances to  
RD1  
press to advance to  
a
Reading 1 Submenu.  
RD1  
READING 1:  
st  
Press  
10) Display flashes 1 digit of previous “Reading 1” value.  
d
b
d
Press  
&
11) Enter “Reading 1” value. (Example 0000)  
12) Display advances to  
c
Press  
Out 1 Submenu.  
OUT.1  
OUT 1:  
st  
Press d  
13) Display flashes 1 digit of previous “Out 1” value.  
Press b & c 14) Enter “Out 1” value. (Example 00.00)  
Press d  
15) Display advances to RD!2 Reading 2 Submenu.  
READING 2:  
st  
Press  
16) Display flashes 1 digit of previous “Reading 2” value.  
d
b
d
Press  
&
17) Enter “Reading 2” value. (Example 9999)  
18) Display advances to  
c
c
Press  
Out 2 Submenu.  
OUT.2  
OUT 2:  
t
st  
Press  
Press  
Press  
19) Display flashes 1 digit of previous “Out 2” value.  
d
b
d
&
20) Enter “Out 2” value. (Example 10.00)  
21) Display advances to the  
Alarm 2 Menu.  
ALR2  
The above example is for 0-10 V of the entire range of the Process Input  
and Analog Output. For 0-20 mA output you need to set “Analog Type” to  
Current and OUT 2 to 20.00.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accuracy of Analog Output board is +/-1% of FS (Full Scale) when following  
conditions are satisfied:  
1. The input is not scaled below 1% of Input FS (10 mV @ 1 V or 0.2 mA @  
20 mA input ranges).  
2. Analog Output is not scaled below 3% of Output FS (300 mV @ 10 V or  
0.6 mA @ 20 mA output ranges).  
Otherwise certain corrections need to be applied.  
For example:  
For entire range of process input, the Analog Output on 10 V FS scaled for  
300 mV output range:  
Rd1 = 0000, Out1 = 00.00  
RD2 = 9999, Out2 = 00.30  
The measured output will be as follows:  
Rd1 = 0000, Out1 = -0.07 V  
Rd2 = 9999, Out2 = 0.23 V  
This means that for 300 mV output range we have -70 mV offset at zero and at  
full scale. In order to compensate this 70 mV offset the correct scaling will be  
as follows:  
Rd1 = 0000, Out1 = 00.07  
Rd2 = 9999, Out2 = 00.37  
The above corrections need to be applied only for Input scaled below 1% of FS  
and Output scaled below 3% of FS or if you need the Analog Output  
accuracy to be better than 1% of FS.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.8 Alarm 2  
This unit is equipped with two physical outputs that can only be configured as  
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1  
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out  
available only if Analog Output Option board is factory installed.  
Alarm must be DISABLED if Ramp is ENABLED.  
Figure 3.7 Flow Chart for Alarm 2  
ENTER ALARM 2 MENU:  
Press  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
d
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
Alarm 2 Menu.  
Disable  
a
ALR2  
DSBL  
4) Display advances to Alarm 2  
Enable or  
ENBL  
Submenu.  
ALARM 2 ENABLE/DISABLE SUBMENU:  
Press  
5) Display flashes previous selection. Press until  
displays  
ENBL  
d
b
to use Alarm 2.  
Press  
6) Display shows  
stored message momentarily and then  
STRD  
d
advances to  
only if it was changed, otherwise press to  
ABSo  
a
advance to  
Absolute/Deviation Submenu.  
ABSo  
If  
Alarm 2 Disabled was selected, all submenus of Alarm 2 will  
LOOP  
Alarm 2 Enabled was selected, Output 2 will automatically  
DSBL  
be skipped and meter advances to  
Loop Break Time Menu. If  
ENBL  
Disabled, and reassigned as Alarm 2.  
The remaining Alarm 2 menu items are identical to Alarm 1 Menu. Modifying  
Alarm Settings will not reset the instrument.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.9 Loop Break Time/Field Calibration  
It is required  
that you put  
the controller  
in the Standby Mode  
for any configuration  
change other than Set  
Points & Alarms.  
Figure 3.8 Flow Chart for Loop Break Time/Field Calibration  
ENTER LOOP BREAK TIME MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
Loop  
LOOP  
a
Break Time Menu.  
Press  
4) Display advances to Loop Break Time  
Enable or  
DSBL  
d
ENBL  
Disable Submenu and flashes the previous selection.  
LOOP BREAK ENABLE/DISABLE SUBMENU:  
Press b 5) Scroll through the available selections:  
Press  
or  
.
ENBL DSBL  
stored message momentarily and then  
6) Display shows  
d
STRD  
Loop Break Time Value Submenu.  
advances to  
B.TIM  
Loop Break is an additional safety feature intended to monitor the rate of change of the  
process value, while approaching the SP1. It is strictly intended as an additional warning  
system, therefore its use is entirely optional. An active Loop Break will cause the Process  
Value digits to blink in a rotating pattern. If the process value reaches the set point the  
blinking will stop and  
is completed successfully, otherwise  
Break Alarm  
B.TIM  
BR.AL  
warning will flash, and Output 1 will be turned off.  
LOOP BREAK TIME VALUE SUBMENU:  
st  
Press  
Press  
Press  
7) Display flashes 1 digit of previous Loop Value.  
d
b
d
&
8) Press and buttons to enter a new Loop Value (0 to 99.59).  
c
b
c
9) Display shows  
stored message momentarily and then  
STRD  
advances to  
Reading Adjust Submenu.  
R.ADJ  
Loop Break Time Value allows the user to determine the time interval in MM:SS (from  
zero to 99 minutes and 59 seconds) that the Process Value changes at least 10 counts or  
if the Input Type is either RTD or Thermocouple, the value changes 4° Fahrenheit or 2°  
Celsius. At the specified time interval, if the process value change is less than the stated  
rate, flashing  
will be displayed, the output 1 will be de-energized, and Alarm 1  
B.TIM  
energized. Loop break time will be disabled when the Process Value (PV) enters the  
control band.  
READING ADJUST SUBMENU:  
st  
Press  
10) Display flashes 1 digit of previous Reading Adjust value.  
d
b
Press  
&
11) Press and buttons to enter a new Reading Adjust value  
c
b
c
(-1999 to 9999).  
Press  
12) Display shows  
stored message momentarily and then  
STRD  
Setpoint Deviation Menu.  
d
advances to  
SP.DV  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.9 Loop Break Time/Field Calibration (continued)  
Reading Offset Adjust allows the user to fine tune a minor error of the transducer,  
however some applications may require a large offset adjust.  
(Displayed Process Value = Measured Process Value R.ADJ).  
Reading Adjust is adjustable between -1999 to 9999. For Temperature Reading only,  
not Process  
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:  
Press  
13) Display advances to Setpoint Deviation  
Enable or  
DSBL  
d
ENBL  
Disable Submenu and flashes the previous selection.  
14) Scroll through the available selections: or .  
DSBL  
Press  
Press  
b
d
ENBL  
stored message momentarily and then  
15) Display shows  
STRD  
°
CAL1  
advances to  
Menu.  
Setpoint Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be made  
automatically to Setpoint 2. This mode is very helpful if the Process Value changes often.  
In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts away from  
SP1 - this relation remains fixed when SP1 is changed. For instance: Setting SP1=200  
and SP2=20 and enabling  
means that the absolute value of SP2=220. Moving  
SP.DV  
SP1 to 300, the absolute value of SP2 becomes 320.  
THERMOCOUPLE FIELD CALIBRATION SUBMENU:  
CAUTION: Do not perform the following steps until you fully  
understand this entire section.  
RTD and Process are perfectly calibrated. This section is applicable to  
Thermocouple (TC) calibration only.  
Be sure that the TC being used to calibrate the meter is of the type  
selected in the TC submenu. Place the TC in an ice-bath (or other  
0°C / 32°F environment). In ambient temperature conditions: connect the  
TC to the meter, apply power to the meter.  
CAUTION: Do not proceed with TC calibration unless the above  
conditions have been in effect for at least one hour.  
°
CAL1  
Press  
Press  
Press  
Press  
7) Display shows  
.
a
d
a
d
8) Display shows flashing  
.
0000  
9) Display will still show flashing  
*
*
.
0000  
(meaning Calibration is complete)  
10) Display shows  
OUT1  
*
If you accidently engage the flashing  
(CAL° alert) simply re-press  
0000  
the last button you pressed, to avoid unintentionally mis-calibrating your  
meter.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.10 Output 1  
Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contacts  
on the rear panel connector. If Alarm 1 or Analog Output (Retransmission) is  
Enabled, Output 1 is automatically Disabled.  
It is required that you put  
the controller in the  
Standby Mode for any  
configuration change other  
than Set Points & Alarms.  
Figure 3.9 Flow Chart for Output 1  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ENTER OUTPUT 1 MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
Output  
OUT1  
a
1 Menu.  
4) Display advances to  
Press  
Self Submenu.  
SELF  
d
SELF SUBMENU:  
The Self Option allows the output of the instrument to be controlled manually  
from the front panel.  
Press  
5) Display flashes the current setting of Self,  
Enabled or  
ENBL  
d
Disabled.  
DSBL  
6) Press the button to select between Enable and Disable.  
Press  
Press  
b
d
b
7) If Self  
Enabled was selected, display shows  
ENBL STRD  
stored message momentarily and then advances to the next  
menu (Output 1 setting is completed).  
The output is now under the direct control of the operator and  
can be adjusted in the Run Mode (  
to ), by pressing  
M00.0 M99.9  
the and buttons, where M calls for the Manual (Self)  
b
c
Control. For example, setting of  
M50.0  
to 10 Vdc would produce roughly 5 Vdc at the output.  
of an Analog Output of 0  
8) If Self  
Disabled was selected, display shows  
DSBL  
STRD  
oPLO  
stored message momentarily and then advances to  
Minimum/Percent Low Submenu of Output 1 Menu.  
There is a shorter way to Enable or Disable Self Mode. From a Run  
Mode, press and then press . Self Mode is Enabled now. Press or  
d
a
b
to display MXX.X. To disable Self, press and then press . Display  
c
d
a
goes to the Run Mode. Self Mode is Disabled now.  
MINIMUM/PERCENT LOW SUBMENU:  
Specify in percent, the minimum value (0000) for control output. If the output is  
analog proportional (Current or Voltage), then the minimum voltage or current, in  
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),  
then the minimum duty-cycle, in percent, is specified.  
Press  
Press  
Press  
9) Display flashes 1st digit of previous “Percent Low” setting.  
d
b
d
&
10) Use and buttons to enter a new value for “Percent Low”.  
c
b
c
11) Display shows  
stored message momentarily and then  
STRD  
advances to  
Maximum/Percent High Submenu.  
oPHI  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAXIMUM/PERCENT HIGH SUBMENU:  
Specify in percent, the maximum value (99) for control output. If the output is  
analog proportional (Current or Voltage), then the maximum voltage or current, in  
percent, is specified. If the output is time proportional (Relay, SSR, or Pulse),  
then the maximum duty-cycle, in percent, is specified.  
st  
Press  
Press  
Press  
12) Display flashes 1 digit of previous “Percent High” setting.  
d
b
d
&
13) Use and buttons to enter a new value for “Percent High”.  
c
b
c
14) Display shows  
stored message momentarily and then  
STRD  
Control Type Submenu.  
advances to  
CTRL  
Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90,  
cause the minimum on the control output to be 1 V and the maximum on the  
control output to be 9 V. The same setting on a time proportional output, will  
cause 10% duty cycle for the minimum control output and 90% duty cycle for  
maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI  
is at other values than the default (%LO = 00, %HI =99),  
is disabled.  
SOAK  
*CONTROL TYPE OUTPUT:  
(Relay, SSR, Pulse or Analog)  
Press  
15) Display flashes  
On/Off or  
Proportional, Integral,  
PID  
d
ON.OF  
Derivative.  
Press  
Press  
16) Scroll through the available selections: “ON/OFF” or “PID”.  
b
d
17) Display flashes  
then advances to  
stored message momentarily and  
STRD  
only, if it was changed, otherwise press  
Action Type Submenu.  
AçTN  
AçTN  
a to advance to  
The ON/OFF control is a coarse way of controlling the process. The “Dead  
Band” improves the cycling associated with the On/Off control. The PID control is  
best for processes where the Setpoint is continuously changing and/or a tight  
control of the process variable is required. PID control requires tuning and  
adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate"  
terms by a trial-and-error method. The instrument provides an "Auto Tuning"  
feature making the tuning process automatic, possibly optimum.  
* If Analog Output (Current/Voltage) is your control Output 1, this menu i.e.  
CTRL  
for a  
type will not appear, instead  
Current will be displayed. Select  
4-20  
4-20 mA current (2-10 V Voltage) outputs or  
ENBL  
for a 0-20 mA current (0-10 V  
DSBL  
Voltage) outputs. If 4-20 mA is enabled, %HI/LO setting will have no effect.  
Both Current and Voltage control outputs are active simultaneously.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACTION TYPE SUBMENU:  
The error that results from the measurement of the Process Variable may be  
positive or negative since it may be greater or smaller than the Setpoint. If a  
positive error should cause the instrument output to increase (i.e. cooling), it would  
be called Direct Acting. If a negative error should cause the output to increase  
(i.e. heating), it would be called Reverse Acting.  
Press  
Press  
Press  
18) Display flashes  
Direct or Reverse.  
RVRS  
d
b
d
DRçT  
19) Scroll through the available selections: “Direct” or “Reverse”.  
20) Display shows  
stored message momentarily and then  
only, if it was changed, otherwise press to  
STRD  
advances to  
AUTo  
a
advance to  
selected).  
Auto PID Submenu (if PID Control Type was  
AUTo  
If “ON/OFF” was selected in the Control Type, the display skips  
to the Dead Band Submenu.  
AUTO PID SUBMENU:  
Press  
21) Display flashes  
or .  
ENBL DSBL  
d
b
Press  
22) Scroll through the available selections: “Enable” or  
“Disable”.  
Press  
23) Display shows  
stored message momentarily and then  
d
STRD  
only, if it was changed, otherwise press to  
advances to  
ANTL  
Anti Integral Submenu.  
a
advance to  
ANTL  
If “Enabled”, the controller can determine, by enabling Start PID, the  
optimum values for the three adjustments — Proportional, Reset and  
Rate corresponding to P, I, and D. These values may be changed once  
the auto tuning is complete.  
If “Disabled” is selected, the user will manually enter these three  
adjustment values. If you want the instrument to do the auto PID and the  
P , PI or PID, first select auto disable and enter 0000 for unwanted  
parameter. i.e. for PI enter 0000 for the rate.  
ANTI INTEGRAL SUBMENU:  
Press  
Press  
Press  
24) Display flashes  
or .  
ENBL DSBL  
d
b
d
25) Scroll through the available selections: “Enable” or “Disable”.  
26) Display shows stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
STRT  
was Enabled).  
STRT  
a
advance to  
to Start Auto Tune PID Submenu (If auto PID  
If Auto PID was disabled display advances to  
Proportional Band Submenu.  
PRoP  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows  
the error term outside the proportional band to be calculated and  
accumulated for integration. This may be an important feature in  
applications where fast response time is desirable.  
START AUTO TUNE PID:  
Press  
Press  
Press  
27) Display flashes  
or .  
ENBL DSBL  
d
b
d
28) Scroll through the available selections: “Enable” or “Disable”.  
29) Display shows stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
CYCL  
Cycle Time Submenu.  
a
advance to  
CYCL  
If “Enabled”, the controller is ready to calculate P, PI or PID parameters.  
The instrument performs this by activating the output and observing the  
delay and rate at which the Process Value changes. The setpoints must  
be at least 18°F or 10°C above the (PV) Process Value in order to  
perform Auto Tune, otherwise an error message will be displayed.  
To start Auto Tune PlD select PID, enable Auto PID and enable Start PID.  
Sometimes Auto PID parameter needs fine tuning i.e. for each 5°F over  
shoot increase the Proportional Band (PB) by 15% and for each 1°F  
fluctuation at the Setpoint (SP) increase reset by 20%.  
Once started, display shows A.TUN with letters blinking in the rotating  
pattern. When auto tune stops, display will show process value. Do not  
perform any operations or settings before first stopping Auto Tune. Any  
alarms or other output is disabled during Auto Tune.  
If “AUTO PID” was “DISABLED”, the display will show the following  
three submenus. This allows the user to manually enter values for  
Proportional, Reset and Rate terms corresponding to P, I, and D. It also  
can be used for auto PID for disabling unwanted parameter i.e. PI enter  
0000 for rate.  
PROPORTIONAL BAND SUBMENU:  
st  
Press  
Press  
Press  
30) Display flashes 1 digit of the previous P  
Proportional  
PRoP  
d
b
d
band value.  
&
31) Press and buttons to enter a new “Proportional Band”  
c
b
c
value.  
32) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
REST  
Reset Setup Submenu.  
a
advance to  
REST  
Proportional band is in degrees of temperature or counts of process. Proportional  
band is defined, as the change in the instrument input to cause a 100% change in  
the controller output.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESET SETUP SUBMENU:  
st  
Press  
Press  
Press  
33) Display flashes 1 digit of the previous I  
Reset value.  
d
b
d
REST  
34) Press and buttons to enter a new “Reset” value.  
&
c
b
c
35) Display shows  
advances to  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
RATE  
Rate Setup Submenu.  
a
advance to  
RATE  
Reset unit is in seconds 0-3999.  
RATE SETUP SUBMENU:  
st  
Press  
Press  
Press  
36) Display flashes 1 digit of previous D  
Rate value.  
d
b
d
RATE  
37) Press and buttons to enter a new  
&
value.  
c
b
c
RATE  
stored message momentarily and then  
38) Display shows  
STRD  
only, if it was changed, otherwise press  
advances to the  
CYCL  
Cycle Time submenu for RTD and  
a
to advance to  
CYCL  
Thermocouple types.  
Rate unit is in seconds 000.0-399.9.  
If the Output 1 is Analog Option the display skips to Damping  
Factor.  
CYCLE TIME SUBMENU:  
st  
Press  
Press  
Press  
39) Display flashes 1 digit of the previous  
Cycle Time  
CYCL  
d
b
d
value.  
&
40) Press and buttons to enter a new “Cycle Time” value.  
c
b
c
(1 to 199 seconds)  
41) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
DPNG  
Damping Factor Submenu.  
a
advance to  
DPNG  
A Cycle Time selected between 1 and 199 seconds determines the total On/Off  
time of each proportional cycle. For example, a 15 second cycle time means that  
every 15 seconds the output will turn on for part or all of the cycle. For Relay  
control outputs, do not select a cycle time of less than 7 seconds or the relays’  
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or  
DC pulse. Use an external SSR with the DC pulse option for higher currents  
(higher than 1 Amp).  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DAMPING FACTOR SUBMENU:  
Press  
42) Display flashes the previous “Damping Factor” selection.  
43) Scroll through the available selections:  
d
b
Press  
,
0000 0001 0002  
,
,
,
,
,
,
.
0003 0004 0005 0006 0007  
Press  
44) Display flashes  
stored message and then advances  
STRD  
d
to  
to  
only, if it was changed, otherwise press to advance  
OUT2  
OUT2  
a
Output 2 Menu.  
Damping Factor is a measure of speed, overshoot, and undershoot in which the  
process variable responds to the output changes of the instrument, which were  
used during the Auto Tune. This value is typically set to the ratio of Rate to  
Reset. This Default value is (0003). For fast response time, this value should be  
decreased while for slow response time it should be increased.  
The "DEADBAND" Submenu will only appear if "ON/OFF" was  
selected from the "Control Type" Menu.  
DEADBAND SUBMENU:  
st  
Press  
45) Display flashes 1 digit of the previous  
Deadband  
DEAD  
d
value.  
Press  
Press  
&
46) Press and buttons to enter a new “Deadband” value.  
b
d
c
b
c
47) Display shows  
OUT2  
OUT2  
stored message and then advances to  
STRD  
only, if it was changed, otherwise press to advance to  
a
Output 2 Menu.  
Dead Band units are the same as Proportional Band units.  
The Dead Band or neutral zone is the number of degrees or counts  
(if Input Type is Process) around the Setpoint which the Process Variable  
must pass above or below the Setpoint, before the output changes state.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.11 Output 2  
Output 2 and Alarm 2 share the same contacts on the rear panel connector. If  
Alarm 2 is Enabled, Output 2 is automatically Disabled.  
It is required that you put  
the controller in the  
Standby Mode for any  
configuration change other  
than Set Points & Alarms.  
Figure 3.10 Flow Chart for Output 2  
ENTER OUTPUT 2 MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
a
OUT2  
Output 2 Menu.  
4) Display advances to  
Press  
Control Type Submenu.  
CTRL  
d
CONTROL TYPE SUBMENU:  
Press 3) Display flashes  
ON/OFF, or PID.  
PID  
d
ON.OF  
4) Scroll through the available selections: “ON/OFF” or “PID”.  
Press b  
Press  
5) Display shows  
stored message momentarily and then  
STRD  
d
advances to  
only, if it was changed, otherwise press to  
Action Type Submenu.  
AçTN  
a
advance to  
AçTN  
The ON/OFF control is a coarse way of controlling the Process. The “Dead  
Band” improves the cycling associated with the ON/Off control. The PID control  
is best for processes where the Setpoint is continuously changing and/or tight  
control of the Process Variable is required.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACTION TYPE SUBMENU:  
The error that results from the measurement of the Process Variable may be  
positive or negative since it may be greater or smaller than the Setpoint. If a  
positive error should cause the instrument output to increase (i.e. cooling), it  
would be called Direct Acting. If a negative error should cause the output to  
decrease (i.e. heating), it would be called Reverse Acting.  
Press  
Press  
Press  
6) Display flashes  
Direct or Reverse.  
RVRS  
d
b
d
DRçT  
7) Scroll through the available selections: “Direct” or “Reverse”.  
8) Display shows  
stored message momentarily and then  
STRD  
AUTo  
advances to  
only, if it was changed, otherwise press to  
a
advance to  
selected).  
Auto PID Submenu (If PID Control type was  
AUTo  
If ON/OFF was selected in the Control Type, the display skips to  
the Dead Band Submenu.  
AUTO PID SUBMENU:  
Press  
Press  
9) Display flashes  
Enable or  
Disable.  
DSBL  
d
b
ENBL  
10) Scroll through the available selections: “Enable” or “Disable”.  
If "Enabled", the PID parameter of Output 1 will be copied to  
Output 2.  
Press  
11) Display shows  
stored message momentarily and then  
STRD  
d
advances to the next submenu only, if it was changed, otherwise  
press to advance to the next submenu.  
a
If AUTO PID was ENABLED", the display skips to the  
CYCL  
CYCLE TIME submenu. If "AUTO PID" was "DISABLED", the  
display will show PROPORTIONAL BAND Submenu  
PRoP  
allowing the user to manually enter the Proportional Band value.  
The Reset and Rate value are the same as Output 1.  
PROPORTIONAL BAND SUBMENU:  
st  
Press  
Press  
Press  
12) Display flashes 1 digit of the previous Proportional Band  
d
b
d
value.  
&
13) Press and buttons to enter a new Proportional Band  
c
b
c
value.  
14) Display shows  
CYCL  
advance to the  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
a
Cycle Time Submenu.  
CYCL  
Refer to “Proportional Band” Submenu of “Output 1” Menu.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CYCLE TIME SUBMENU:  
st  
Press  
15) Display flashes 1 digit of the previous “Cycle Time” value.  
d
b
Press  
&
16) Press and buttons to enter a new “Cycle Time” value  
c
b
c
(1 to 199 seconds).  
17) Display shows  
advances to  
Press  
stored message momentarily and then  
d
STRD  
only, if it was changed, otherwise press to  
RAMP  
Ramp Value Submenu.  
a
advance to  
RAMP  
A cycle time selected between 1 to 199 seconds indicates the total On/Off time  
of each proportional cycle. For example, a 15 second cycle time means that  
every 15 seconds the output will turn on for part or all of the cycle. For Relays’  
Control Outputs, do not select a cycle time of less than 7 seconds or the relays’  
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or  
DC pulse. Use an external SSR with the DC pulse option for higher current  
(higher than 1 Amp).  
The DEADBAND Submenu will only appear if the ON/OFF was  
selected from the "Control Type" Submenu.  
DEADBAND SUBMENU:  
Press  
Press  
Press  
18) Display flashes 1st digit of the previous “Dead Band” value.  
d
b
d
&
19) Press and buttons to enter a new “Dead Band” value.  
c
b
c
20) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
RAMP  
Ramp Value Menu.  
a
advance to  
RAMP  
Dead Band units are the same as Proportional Band units.  
The Dead Band or neutral zone is the number of degrees or counts  
(if Input Type is Process) around the Setpoint which the Process Variable  
must pass above or below the Setpoint, before the output changes state.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.12 Ramp & Soak  
Alarm must be DISABLED if Ramp is ENABLED.  
It is required that you put the controller in the Standby Mode for any  
configuration change other than Set Points & Alarms.  
Figure 3.11 Flow Chart for Ramp and Soak  
ENTER RAMP AND SOAK MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
Ramp  
RAMP  
a
and  
Soak Menu.  
SOAK  
RAMP ENABLE/DISABLE SUBMENU:  
Press  
4) Display advances to “Ramp Enable/Disable” Submenu and  
flashes or  
d
.
ENBL DSBL  
5) Scroll through the available selections: “Enable” or “Disable”.  
6) Display shows stored message momentarily and then  
Press  
Press  
b
d
STRD  
Soak Enable/Disable Menu.  
advances to  
SOAK  
If  
Disable was selected, display skips to the next menu  
RAMP  
item (ID Code).  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOAK ENABLE/DISABLE SUBMENU:  
Press  
Press  
Press  
7) Display flashes  
or .  
ENBL DSBL  
d
b
d
8) Scroll through the available selections: “Enable” or “Disable”.  
9) Display shows stored message momentarily and then  
STRD  
advances to “Ramp Value” Submenu.  
Ramp & Soak provides users with the flexibility to slowly bring the Process  
Variable (PV) to the desired setpoint. Ramp & Soak values are specified in  
HH.MM format. The Ramp value indicates the time specified to bring the  
process variable to Setpoint 1 (SP1). Once the set point is reached, the PID  
takes over and the Process Variable will be controlled at the desired set point  
indefinitely. If Soak is enabled, PID will control the Process Variable at the  
specified Setpoint for the duration of Soak time and then will turn off Output 1.  
To start a new Ramp/Soak cycle, reset the instrument by pressing and then  
a
c
button.  
An active Ramp/Soak will change SP1 one degree above the PV and will cause  
the most significant digit to blink. The SP1 will be incremented by one degree  
until it reaches the original SP1. The minimum Ramp time must be at least twice  
the time that it will take the PV to reach the Setpoint Value (SV) with OUT 1 fully  
ON.  
RAMP VALUE SUBMENU:  
st  
Press  
Press  
Press  
10) Display flashes 1 digit of previous stored “Ramp Value”.  
d
b
d
&
11) Press and buttons to enter a new “Ramp Value”.  
STRD  
advances to “Soak Value” Submenu.  
c
b
c
12) Display shows  
stored message momentarily and then  
SOAK VALUE SUBMENU:  
Press  
Press  
Press  
13) Display flashes 1st digit of previous stored “Soak Value”.  
14) Press and buttons to enter a new “Soak Value”.  
d
b
d
&
c
b
c
STRD  
15) Display shows  
stored message and advances to the  
ID Code Menu.  
ID  
The Ramp and Soak time is 00:00 to 99:59 i.e. HH.MM. (from zero to 99 hours  
and 59 minutes) During Ramp & Soak do not perform any operations or settings  
before first stopping it. Any alarms or other output are disabled during this time.  
To stop Ramp & Soak first put instrument into Standby Mode, then go to Ramp &  
Soak Menu and disable it.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.13 ID CODE  
Figure 3.12 Flow Chart for ID Code  
ENTER ID CODE MENU:  
Press 1) Press , if necessary, until  
prompt appears.  
a
a
CNFG  
Input Menu.  
Press d  
Press  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to ID Code  
ID  
a
a
Menu.  
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID CODE:  
st  
Press d  
4) Display advances to  
with 1 under score flashing.  
____  
Press  
&
5) Press and to enter your 4-digit “ID Code” number.  
c
b
b
c
Press d  
6) Display advances to  
Change ID Code Submenu.  
CH.ID  
If entered “ID Code” is incorrect display shows  
Error  
ERRo  
message momentarily and then skips to the Run Mode.  
Press  
7) Display flashes the first digit of previous entered “ID Code”  
number.  
d
Press  
Press  
&
8) Press and buttons to enter your new “ID Code” number.  
b
d
c
b
c
9) Display shows  
stored message momentarily and then  
STRD  
advances to the  
Full Security Submenu.  
FULL  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:  
Enter menu (Repeat steps from 1 to 3).  
ID  
Press  
Press  
10) Display advances to  
11) Display shows  
0000  
Change ID Code Submenu.  
d
d
CH.ID  
message with flashing 1 digit.  
st  
If you want to change your default “ID Code” you can do it now,  
otherwise press and menu will skip to  
Full Security  
FULL  
a
Submenu.  
Press  
Press  
&
12) Press and buttons to enter your new “ID Code” number.  
b
d
c
b
c
13) Display shows  
stored message momentarily and then  
STRD  
Full Security Submenu.  
advances to the  
FULL  
FULL SECURITY LEVEL SUBMENU:  
Press  
Press  
Press  
14) Display flashes  
Enable or Disable.  
DSBL  
d
b
d
ENBL  
15) Scroll through the available selections: “Enable” or “Disable”.  
16) Display shows stored message momentarily and then  
STRD  
Setpoint/ID Submenu.  
advances to  
SP.ID  
If "Full" Security Level is "Enabled" and the user attempts to  
enter the Main Menu, they will be prompted for an ID Code. The  
ID Code should be correct to enter the instrument Menu item.  
SETPOINT/ID SECURITY LEVEL SUBMENU:  
This Security Level can be functional only if  
Level is Disabled.  
Security  
FULL  
Press  
Press  
Press  
17) Display flashes  
Enable or  
Disable.  
DSBL  
d
b
d
ENBL  
18) Scroll through the available selections: “Enable” or “Disable”.  
19) Display shows  
stored message momentarily and then  
STRD  
Communication Submenu.  
advances to  
COMM  
If "Setpoint/ID" Security Level is "Enabled" and the user  
attempts to advance into the Configuration Menu, he will  
CNFG  
be prompted for ID Code number. The ID Code should be  
correct to proceed into the Configuration Menu, otherwise  
display will show an Error and skip to the Run Mode.  
If “Full” and “Setpoint/ID” Security Levels are "Disabled", the  
ID code will be “Disabled” and user will not be asked for ID  
Code to enter the Menu items (“ID” Submenu will not show upin  
“ID/Setpoint” Menu).  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.14 COMMUNICATION OPTION  
Purchasing the controller with Serial Communications permits an instrument to be configured  
or monitored from an IBM PC compatible computer using software available from the  
website or on the CD-ROM enclosed with your shipment. For complete instructions on  
the use of the Serial Comm.Option, refer to the Serial Comm. Reference Manual.  
*
Valid only for -C24  
and -EI options.  
** Valid only for -C24  
and -C4EI options.  
External RS-232 connections are not available with -EI or -C4EI options.  
Figure 3.13 Flow Chart for Communication Option  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ENTER COMMUNICATION OPTION MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
a
COMM  
Communication Options Menu.  
Press  
4) Display advances to  
Submenu.  
Communication Parameters  
C.PAR  
d
If Communication Option is not installed, the display shows  
and skips to the Color Display Menu.  
NONE  
COMMUNICATION PARAMETERS SUBMENU:  
Allows the user to adjust Serial Communications Settings of the instrument.  
When connecting an instrument to a computer or other device, the  
Communications Parameters must match. Generally the default settings  
(as shown in Section 5) should be utilized.  
Press  
5) Display advances to  
Baud Submenu.  
BAUD  
d
BAUD SUBMENU:  
Press  
6) Display flashes previous selection for  
value.  
BAUD  
d
b
Press  
7) Scroll through the available selections:  
,
300_ 600_ 1200  
,
,
,
,
,
.
2400 4800 9600 19.2K  
8) Display shows  
Press  
stored message momentarily and then  
d
STRD  
only, if it was changed, otherwise press to  
advances to  
PRTY  
Parity Submenu.  
a
advance to  
PRTY  
PARITY SUBMENU:  
Press  
Press  
Press  
9) Display flashes previous selection for “Parity”.  
d
b
d
10) Scroll through the available selections: NO, ODD, EVEN.  
11) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
DATA  
Data Bit Submenu.  
a
advance to  
DATA  
DATA BIT SUBMENU:  
Press  
Press  
Press  
12) Display flashes previous selection for “Data Bit”.  
d
b
d
13) Scroll through the available selections: 7-BIT, 8-BIT.  
14) Display shows  
STOP  
STOP  
stored message and then advances to  
STRD  
only, if it was changed, otherwise press to advance to  
a
Stop Bit Submenu.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STOP BIT SUBMENU:  
Press  
Press  
Press  
15) Display flashes previous selection for “Stop Bit”.  
16) Scroll through the available selections:  
d
b
d
,
.
1-BIT 2-BIT  
17) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
BUS.F  
Bus Format Submenu.  
a
advance to  
BUS.F  
BUS FORMAT SUBMENU:  
Determines Communications Standards and Command/Data Formats for  
transferring information into and out of the controller via the Serial  
Communications Bus. Bus Format submenus essentially determine how and  
when data can be accessed via the Serial Communications of the device.  
Press  
18) Display advances to  
Modbus Submenu.  
M.BUS  
d
MODBUS PROTOCOL SUBMENU:  
Press  
Press  
Press  
19) Display flashes previous selection for  
.
d
b
d
M.BUS  
20) Scroll through the available selections: NO, YES.  
21) Display shows stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
_LF_  
Line Feed submenu.  
a
advance to  
_LF_  
To select iSeries Protocol, set Modbus submenu to “No”.  
To select Modbus Protocol, set Modbus submenu to “Yes”.  
If Modbus Protocol was selected, the following Communications  
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not  
attempt to change these parameters.  
LINE FEED SUBMENU:  
Determines if data sent from the instrument will have a Line Feed appended to  
the end - useful for viewing or logging results on separate lines when displayed  
on communications software at a computer.  
Press  
Press  
Press  
22) Display flashes previous selection for “Line Feed”.  
d
b
d
23) Scroll through the available selections: NO, YES.  
24) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
ECHO  
Echo Submenu.  
a
advance to  
ECHO  
ECHO SUBMENU:  
When valid commands are sent to the instrument, this determines whether the  
command will be echoed to the Serial Bus. Use of echo is recommended in most  
situations, especially to help verify that data was received and recognized by the  
controller.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Press  
Press  
Press  
25) Display flashes previous selection for “Echo”.  
d
b
d
26) Scroll through the available selections: NO, YES.  
27) Display flashes  
stored message momentarily and then  
STRD  
only if it was changed, otherwise press to  
advances to  
STND  
Communication Standard Submenu.  
a
advance to  
STND  
COMMUNICATION INTERFACE STANDARD SUBMENU:  
Determines whether device should be connected to an RS-232C serial port  
(as is commonly used on IBM PC-compatible computers) or via an RS-485 bus  
connected through appropriate RS-232/485 converter. When used in RS-485  
Mode, the device must be accessed with an appropriate Address Value as  
selected in the Address Submenu described later.  
Press  
Press  
Press  
28) Display flashes previous selection for “Standard”.  
d
b
d
29) Scroll through the available selections: 232C, 485.  
30) Display shows  
stored message momentarily and then  
STRD  
advances to  
only, if it was changed, otherwise press to  
MoDE  
MoDE  
a
advance to  
Data Flow Mode Submenu.  
DATA FLOW MODE SUBMENU:  
Determines whether the instrument will wait for commands and data requests  
from the Serial Bus or whether the instrument will send data automatically and  
continuously to the Serial Bus. Devices configured for the RS-485  
Communications Standard operate properly only under Command Mode.  
Press  
31) Display flashes previous selection for “Mode”.  
32) Scroll through the available selections:  
d
b
Press  
“Command”,  
_
CMD  
“Continuous”.  
CoNT  
33) Display shows  
Press  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
d
advances to  
SEPR  
Data Separation Submenu.  
a
advance to  
SEPR  
DATA SEPARATION CHARACTER SUBMENU:  
Determines whether data sent from the device in Continuous Data Flow Mode  
will be separated by spaces or by Carriage Returns.  
Press  
34) Display flashes previous selection for “Separation” Submenu.  
35) Scroll through the available selections: “Space” or  
d
b
Press  
SPCE  
“Carriage Return”.  
_çR_  
36) Display shows  
Press  
stored message momentarily and then  
STRD  
d
advances to  
only, if it was changed, otherwise press to  
DAT.F  
a
advance to  
Data Format Submenu.  
DAT.F  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DATA FORMAT SUBMENU:  
Preformatted data can be sent automatically or upon request from the controller.  
Use the Data Format Submenus to determine what data will be sent in this  
preformatted data string. Refer to the iSeries Communications Manual for more  
information about the data format. At least one of the following suboptions must  
be enabled and hence output data to the Serial Bus.  
This menu is applicable for Continuous Mode of RS-232 communication.  
Press  
37) Display advances to  
Alarm Status Submenu.  
STAT  
d
ALARM STATUS SUBMENU:  
Includes Alarm Status bytes in the data string.  
Press  
Press  
Press  
38) Display flashes previous selection for “Status” (alarm status).  
d
b
d
39) Scroll through the available selections: NO, YES.  
40) Display shows  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
advance to  
RDNG  
Reading Submenu.  
a
RDNG  
MAIN READING SUBMENU:  
Includes Main Reading in the data string.  
Press  
Press  
Press  
41) Display flashes previous selection for “Reading”.  
42) Scroll through the available selections: NO, YES.  
43) Display shows stored message momentarily and then  
d
b
d
STRD  
only, if it was changed, otherwise press to  
advances to  
PEAK  
Peak Submenu.  
a
advance to  
PEAK  
PEAK VALUE SUBMENU:  
Includes Peak Value in the data string.  
Press  
Press  
Press  
44) Display flashes previous selection for  
Submenu.  
d
b
d
PEAK  
45) Scroll through the available selections: NO, YES.  
46) Display shows stored message momentarily and then  
STRD  
only, it was changed, otherwise press to  
advances to  
advance to  
VALY  
Valley Submenu.  
a
VALY  
VALLEY VALUE SUBMENU:  
Includes Valley Value in the data string.  
Press  
Press  
Press  
47) Display flashes previous selection for “Valley”.  
48) Scroll through the available selections: NO, YES.  
49) Display shows stored message momentarily and then  
d
b
d
STRD  
advances to  
only, if it was changed, otherwise press to  
UNIT  
a
advance to  
Temperature Unit Submenu.  
UNIT  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TEMPERATURE UNIT SUBMENU:  
Includes a byte in the data string to indicate whether reading is in Celsius or  
Fahrenheit.  
Press  
Press  
Press  
50) Display flashes previous selection for  
.
d
b
d
UNIT  
51) Scroll through the available selections: NO, YES.  
52) Display shows stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
advances to  
ADDR  
Address Setup Submenu.  
a
advance to  
ADDR  
ADDRESS SETUP SUBMENU:  
This menu is applicable to the RS-485 Option only.  
Press  
53) Display advances to “Address Value” (0000 to 0199) Submenu.  
d
ADDRESS VALUE SUBMENU:  
st  
Press  
Press  
Press  
54) Display flashes 1 digit of previously stored Address Value.  
d
b
d
&
55) Press and to enter new “Address Value”.  
c
b
c
56) Display shows  
advances to  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
TR.TM  
Transmit Time Interval Submenu.  
a
advance to  
TR.TM  
TRANSMIT TIME INTERVAL SUBMENU:  
This menu is applicable if “Continuous” Mode was selected in the “Data  
Flow Mode” Submenu and the device is configured as an RS-232C  
Standard device. Also, one or more options under the Data Format  
Submenu must be enabled.  
Press  
57) Display advances to “Transmit Time Value” Submenu.  
d
TRANSMIT TIME INTERVAL VALUE SUBMENU:  
Determines the interval at which data will be emitted to the RS-232 Serial Bus  
when the instrument is in Continuous Data Flow Mode.  
st  
Press  
Press  
Press  
58) Display flashes 1 digit of previous “Transmit Time Value” in  
seconds.  
d
b
d
&
59) Press and to enter new “Transmit Time Value”, e.g.  
0030 will send the data every 30 seconds in Continuous Mode.  
c
b
c
60) Display shows  
advances to  
stored message momentarily and then  
STRD  
only, if it was changed, otherwise press to  
COLR  
Color Display Selection Menu.  
a
advance to  
COLR  
For more details, refer to the Communication Manual available at  
the website listed in the cover page of this manual.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.15 DISPLAY COLOR SELECTION  
This submenu allows the user to select the color of the display.  
Figure 3.14 Flow Chart for Display Color Selection  
ENTER DISPLAY COLOR SELECTION MENU:  
Press  
Press  
Press  
1) Press , if necessary, until  
prompt appears.  
a
d
a
a
CNFG  
Input Menu.  
2) Display advances to  
INPT  
3) Press , if necessary, until Display advances to  
a
COLR  
Display Color Selection Menu.  
Press  
4) Display advances to  
Normal Color Submenu.  
N.CLR  
d
NORMAL COLOR DISPLAY SUBMENU:  
Press  
Press  
Press  
5) Display flashes the previous selection for “Normal Color”.  
6) Scroll through the available selections: or  
d
b
d
,
.
GRN RED AMBR  
stored message momentarily and then  
7) Display shows  
STRD  
only, if it was changed, otherwise press to  
advances to  
advance to  
1.CLR  
Alarm 1 Display Color Submenu.  
a
1.CLR  
The menu below allows the user to change the color of display when alarm is  
triggered.  
ALARM 1 DISPLAY COLOR SUBMENU:  
Press  
8) Display flashes previous selection for “Alarm 1 Color  
d
Display”.  
Press  
Press  
9) Scroll through the available selections:  
,
or .  
b
d
GRN RED AMBR  
stored message momentarily and then  
STRD  
10) Display shows  
advances to  
only, if it was changed, otherwise press to  
2.CLR  
a
advance to  
Alarm 2 Display Color Submenu.  
2.CLR  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALARM 2 DISPLAY COLOR SUBMENU:  
Press  
Press  
Press  
11) Display flashes previous selection for “Alarm 2 Color Display”.  
12) Scroll through the available selections: or  
d
b
d
,
.
GRN RED AMBR  
stored message momentarily and then  
13) Display shows  
STRD  
momentarily shows the software version number, followed by  
Reset, and then proceeds to the Run Mode.  
RST  
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY  
COLOR ON ALL THREE SUBMENUS ABOVE.  
If user wants the Display to change color every time when both Alarm 1  
and Alarm 2 are triggered, the Alarm values should be set in such a way  
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value  
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not  
change when Alarm 2 is triggered.  
Example 1:  
Output 1 & Output 2 = SSR  
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200, Alarm 1  
HI Value “ALR.H” = 400  
"Color Display" Setup: Normal Color “N.CLR” = Green, Alarm 1 Color  
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red  
Display Colors change sequences:  
GREEN RED  
AMBER  
-- ------------------------------ ----------------------------- ------------------------------  
 
0
AL2.H = 200  
AL1.H = 400  
Example 2:  
Output 1 & Output 2 = Pulse  
Alarm Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300, Alarm 1  
Low Value “ALR.L” = 100  
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red  
Display Colors change sequences:  
AMBER RED  
GREEN  
-------------- ---------------------------------- ------------------------------------------- --  
0
AL1.L = 100  
AL2.L = 300  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 3:  
Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,  
Output 2 = Relay, Setpoint 2 = 200  
Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10  
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red  
Display Colors change sequences:  
RED  
--------------- ------ ------ -------------------------------- ------ ------- ----------------  
RED  
RED  
GREEN  
RED  
➤  
0
190 200 210  
290 300 310  
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.  
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.  
If Analog Output Option board is installed (Alarm 1 is disabled), only  
Alarm 2 is active and only two colors are available.  
Example 4:  
Output 1 = Relay, Setpoint 1 = 200  
Output 2 = Relay, Setpoint 2 = 200  
Alarm 1 Setup: Deviation, Band, “ALR.H” = 20  
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5  
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red  
Display colors change sequences:  
AMBER RED GREEN GREEN  
RED  
AMBER  
-- --------------- ---------------- ------------- -------------- ------------- ---------------------  
➤  
0
180  
195  
200  
210  
220  
Reset: The instrument automatically resets after the last menu of  
the Configuration Mode has been entered. After the instrument  
resets, it advances to the Run Mode.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PART 4  
INPUT  
Input Types  
SPECIFICATIONS  
Thermocouple, RTD, Analog Voltage,  
Analog Current  
Accuracy  
0.5°C temp; 0.03% reading process  
Thermocouple Type (ITS 90)  
J, K, T, E, R, S, B, C, N, L  
Resolution  
1°/0.1°; 10 µV process  
Thermocouple Lead Resistance  
100 ohm max  
Temperature Stability  
1) RTD: 0.04°C/°C  
2) TC @ 25°C (77°F): 0.05°C/°C  
- Cold Junction Compensation  
3) Process: 50 ppm/°C  
RTD Input (ITS 68)  
100/500/1000 Ω Pt sensor, 2-, 3- or  
4-wire; 0.00385 or 0.00392 curve  
NMRR  
60 dB  
Voltage Input  
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc  
CMRR  
Input Impedance  
10 MΩ for 100 mV  
1 MΩ for 1 or 10 Vdc  
120 dB  
A/D Conversion  
Dual slope  
Current Input  
0 to 20 mA (5 ohm load)  
Reading Rate  
3 samples per second  
Configuration  
Single-ended  
Digital Filter  
Programmable  
Polarity  
Unipolar  
Display  
4-digit, 9-segment LED  
Step Response  
0.7 sec for 99.9%  
10.2 mm (0.40"): i32, i16, i16D (Dual  
Display), i8DV (Dual Vertical)  
• 21 mm (0.83"): i8  
• 10.2 mm (0.40”) and 21 mm (0.83”):  
i8DH (Dual Horizontal)  
Decimal Selection  
None, 0.1 for temperature  
None, 0.1, 0.01 or 0.001 for process  
red, green and amber programmable  
colors for process variable, set point  
and temperature units  
Setpoint Adjustment  
-1999 to +9999 counts  
Warm up to Rated Accuracy  
30 min.  
Span Adjustment  
0.001 to 9999 counts  
Offset Adjustment  
-1999 to +9999  
CONTROL  
Action  
Reverse (heat) or direct (cool)  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Modes  
DC Pulse  
Time and Amplitude Proportional  
Control Modes; selectable Manual or  
Auto PID, Proportional, Proportional  
with Integral, Proportional with  
Derivative with Anti-reset Windup and  
ON/OFF  
Non-Isolated; 10 Vdc @ 20 mA  
Analog Output (Output 1 only)  
Non-Isolated, Proportional 0 to 10 Vdc  
or 0 to 20 mA; 500 Ω max  
NETWORK AND COMMUNICATIONS  
(Optional -C24, -C4EI, -EI)  
Ethernet: Standards Compliance IEEE  
802.3 10Base-T  
Supported Protocols: TCP/IP, ARP,  
HTTPGET  
Rate  
0 to 399.9 seconds  
Reset  
0 to 3999 seconds  
Cycle Time  
RS-232/RS-422/RS-485/MODBUS:  
Selectable from menu; both ASCII and  
modbus protocol selectable from menu.  
Programmable 300 to 19.2 K baud;  
complete programmable setup  
capability; program to transmit current  
display, alarm status, min/max, actual  
measured input value and status.  
1 to 199 seconds; set to 0 for ON/OFF  
operation  
Gain  
0.5 to 100% of span; Setpoints 1 or 2  
Damping  
0000 to 0008  
RS-485  
Addressable from 0 to 199  
Soak  
00.00 to 99.59 (HH:MM), or OFF  
Connection  
Screw terminals  
Ramp to Setpoint  
00.00 to 99.59 (HH:MM), or OFF  
ALARM 1 & 2 (programmable):  
Type  
Same as Output 1 & 2  
Auto Tune  
Operator initiated from front panel  
CONTROL OUTPUT 1 & 2  
Relay  
250 Vac or 30 Vdc @ 3 A  
(Resistive Load); configurable for  
on/off, PID and Ramp and Soak  
Operation  
High/low, above/below, band,  
latch/unlatch, normally open/normally  
closed and process/deviation; front  
panel configurations  
Output 1: SPDT type, can be  
ANALOG OUTPUT (programmable)  
Non-Isolated, Retransmission 0 to 10  
Vdc or 0 to 20 mA, 500 Ω max (Output  
1 only). Accuracy is + 1% of FS when  
following conditions are satisfied.  
1) Input is not scaled below 1% of  
Input FS.  
configured as Alarm 1 output  
Output 2: SPDT type, can be  
configured as Alarm 2 output  
SSR  
20-265 Vac @ 0.05-0.5 A  
(Resistive Load); continuous  
2) Analog Output is not scaled below  
3% of Output FS.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCITATION  
Environmental Conditions  
(optional in place of Communication) • All models: 0 to 55°C (32 to 131°F),  
24 Vdc @ 25 mA  
Not available for Low Power Option  
90% RH non-condensing  
• i8DV, i8DH, i8C, i16D: 0 to 50°C  
(32 to122°F) for UL only.  
INSULATION  
Power to Input/Output  
2300 Vac per 1 min. test  
90% RH non-condensing  
Protection  
1500 Vac per 1 min. test  
(Low Voltage/Power Option)  
Power to Relays/SSR Outputs  
2300 Vac per 1 min. test  
NEMA-4x/Type 4x/IP65 front bezel:  
i32, i16D, i8C  
NEMA-1/Type 1 front bezel: i8, i8DH,  
i8DV  
Relays/SSR to Relay/SSR Outputs  
2300 Vac per 1 min. test  
Dimensions  
i/8 Series:  
48 H x 96 W x 127 mm D  
(1.89 x 3.78 x 5")  
RS-232/485 to Inputs/Outputs  
500 Vac per 1 min. test  
Approvals  
FM, UL, C-UL, and  
see CE Approval Section  
i/8 Compact Series:  
48 H x 96 W x 74 mm D  
(1.89 x 3.78 x 2.91")  
GENERAL  
i/16 Series:  
Line Voltage/Power  
48 H x 48 W x 127 mm D  
(1.89 x 1.89 x 5")  
90-240 Vac +/-10%, 50-400 Hz*  
110-375 Vdc, equivalent voltage  
4 W, power for i8, i8C, i16, i32 Models  
5 W, power for i8DV, i8DH, i16D Models  
* No CE compliance above 60 Hz  
i/32 Series:  
25.4 H x 48 W x 127 mm D  
(1.0 x 1.89 x 5")  
Low Voltage/Power Option  
12-36 Vdc, 3 W, power for i8, i16, i32  
20-36 Vdc, 4 W, power for i8DV, i8DH, i16D  
External power source must meet  
Safety Agency Approvals.  
* Units can be powered safely with 24 Vac  
power but, no Certification for CE/UL are  
claimed.  
Panel Cutout  
i/8 Series: 45 H x 92 mm W  
(1.772" x 3.622 "), 1/8 DIN  
i/16 Series:  
45 mm (1.772") square, 1/16 DIN  
i/32 Series:  
22.5 H x 45 mm W  
(0.886" x 1.772"), 1/32 DIN  
External Fuse Required  
Time-Delay, UL 248-14 listed:  
100 mA/250 V  
Weight  
400 mA/250 V (Low Voltage/Power Option)  
Time-Lag, IEC 127-3 recognized:  
100 mA/250 V  
i/8 Series: 295 g (0.65 lb)  
i/16 Series: 159 g (0.35 lb)  
i/32 Series: 127 g (0.28 lb)  
400 mA/250 V (Low Voltage/Power Option)  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4.1 Input Properties  
TC  
Input Type  
Iron-Constantan  
Range  
-210 to 760°C  
Accuracy*  
0.4°C  
0.7°F  
J
-346 to 1400°F  
-270 to -160°C  
-160 to 1372°C  
-454 to -256°F  
-256 to 2502°F  
-270 to -190°C  
-190 to 400°C  
-454 to -310°F  
-310 to 752°F  
-270 to -220°C  
-220 to 1000°C  
-454 to -364°F  
-364 to 1832°F  
-50 to 40°C  
40 to 1788°C  
-58 to 104°F  
104 to 3250°F  
-50 to 100°C  
100 to 1768°C  
-58 to 212°F  
1.0°C  
0.4°C  
1.8°F  
CHROMEGA®-  
ALOMEGA®  
K
0.7°F  
1.0°C  
0.4°C  
1.8°F  
Copper-Constantan  
T
0.7°F  
1.0°C  
0.4°C  
1.8°F  
CHROMEGA-  
Constantan  
E
R
S
0.7°F  
1.0°C  
0.5°C  
1.8°F  
Pt/13%Rh-Pt  
0.9°F  
1.0°C  
0.5°C  
1.8°F  
Pt/10%Rh-Pt  
212 to 3214°F  
200 to 640°C  
640 to 1820°C  
212 to 1184°F  
1184 to 3308°F  
0 to 2354°C  
0.9°F  
1.0°C  
0.5°C  
1.8°F  
0.9°F  
0.4°C  
0.7°F  
1.0°C  
0.4°C  
1.8°F  
0.7°F  
0.4°C  
0.7°F  
30%Rh-Pt/  
6%Rh-Pt  
B
C
N
5%Re-W/  
26%Re-W  
32 to 4253°F  
-250 to -100°C  
-100 to 1300°C  
-418 to -148°F  
-148 to 2372°F  
-200 to 900°C  
-328 to 1652°F  
200 to 900°C  
-328 to 1652°F  
-200 to 850°C  
-328 to 1562°F  
0 to 100 mV, 0 to 1 V,  
0 to 10 Vdc  
Nicrosil-Nisil  
J
DIN  
L
RTD  
RTD  
PROCESS  
Pt, 0.00385, 100 Ω,  
500 Ω, 1000 Ω  
Pt, 0.00392, 100 Ω,  
500 Ω, 1000 Ω  
Voltage  
0.4°C  
0.7°F  
0.4°C  
0.7°F  
0.03% rdg  
0.03% rdg  
0.03% rdg  
PROCESS Current  
0 to 20 mA, 4 to 20 mA  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PART 5  
FACTORY PRESET VALUES  
Table 5.1 Factory preset value  
MENU ITEMS  
FACTORY PRESET VALUES  
NOTES  
Set Point 1 (SP1)  
Set Point 2 (SP2)  
000.0  
000.0  
Input:  
Input Type (INPT)  
TC, type K  
Reading Configuration (RDG):  
Decimal Point (DEC.P)  
Temperature unit (TEMP)  
Filter value (FLTR)  
FFF.F  
°F  
0004  
:
Alarm 1 & 2  
Alarm 1 (ALR1), Alarm 2 (ALR2)  
Absolute/Deviation (ABSO/DEV)  
Latch/Unlatch (LTCH/UNLT)  
Contact Closure (CT.CL)  
Active (ACTV)  
Disable (DSBL)  
Absolute (ABSO)  
Unlatch (UNLT)  
Normally Open (N.O.)  
Above (ABOV)  
Disable (DSBL)  
-100.0  
Alarm At Power On (A.P.ON)  
Alarm Low (ALR.L)  
Alarm 1 only  
Alarm High (ALR.H)  
400.0  
LOOP:  
Loop Break Time (LOOP)  
Loop Value (B.TIM)  
Disable (DSBL)  
00:59  
Reading Adjust Value (R.ADJ)  
Setpoint Deviation (SP.dV)  
000.0  
Disable (DSBL)  
ANALOG OUTPUT (Retransmission):  
Analog Output (ANLG)  
Current/Voltage (CURR/VOLT)  
Scale and Offset  
Enabled (ENBL)  
Voltage (VOLT)  
Reading: 0 - 999.9 cts, Output: 0 - 10 V  
OUTPUT 1 & 2:  
Self (SELF)  
Disabled (DSBL)  
0000  
0099  
On/Off  
Reverse (RVRS)  
020.0  
Disable (DSBL)  
Disable (DSBL)  
020.0  
0180  
0000  
Output 1 only  
Output 1 only  
Output 1 only  
% Low Value (%LO)  
% High Value (%HI)  
Control Type (CTRL)  
Action Type (ACTN)  
Dead Band (DEAD)  
PID Auto (AUTO)  
Anti Integral (ANTI)  
Proportion Value (PROP)  
Reset Value (REST)  
Rate Value (RATE)  
Cycle Value (CYCL)  
Damping Factor (DPNG)  
Output 1 only  
Output 1 only  
Output 1 only  
0007  
0003  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MENU ITEMS  
Ramp & Soak (RAMP)  
Ramp (RAMP)  
Soak (SOAK)  
Ramp Value (RAMP)  
Soak Value (SOAK)  
FACTORY PRESET VALUES  
NOTES  
:
Disable (DSBL)  
Disable (DSBL)  
00:00  
00:00  
:
ID  
ID Value  
0000  
Full ID (FULL)  
Set Point ID (ID.SP)  
Disable (DSBL)  
Disable (DSBL)  
Communication Parameters:  
Baud Rate (BAUD)  
Parity (PRTY)  
9600  
Odd  
Data bit (DATA)  
7 bit  
Stop Bit  
1 bit  
Modbus Protocol (M.BUS)  
Line Feed (LF)  
No  
No  
Echo (ECHO)  
Yes  
Standard Interface (STND)  
Command Mode (MODE)  
Separation (SEPR)  
Alarm Status (STAT)  
Reading (RDNG)  
RS-232 (232C)  
Command (CMD)  
Space (SPCE)  
No  
Yes  
No  
Peak  
Valley (VALY)  
No  
Units (UNIT)  
No  
Multipoint Address (ADDR)  
Transmit Time (TR.TM)  
Display Color (COLR):  
Normal Color (N.CLR)  
Alarm 1 Color (1.CLR)  
Alarm 2 Color (2.CLR)  
0001  
0016  
Green (GRN)  
Red (RED)  
Amber (AMBR)  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PART 6  
CE APPROVALS INFORMATION  
This product conforms to the EMC directive 89/336/EEC amended by  
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.  
Electrical Safety EN61010-1:2001  
Safety requirements for electrical equipment for measurement, control and laboratory.  
Double Insulation  
Pollution Degree 2  
Dielectric withstand Test per 1 min  
Power to Input/Output:  
Power to Input/Output:  
(Low Voltage dc Power Option*)  
2300Vac (3250Vdc)  
1500Vac (2120Vdc)  
Power to Relays/SSR Output:  
Ethernet to Inputs:  
Isolated RS232 to Inputs:  
Isolated Analog to Inputs:  
Analog/Pulse to Inputs:  
Measurement Category I  
2300Vac (3250Vdc)  
1500Vac (2120Vdc)  
500Vac (720Vdc)  
500Vac (720Vdc)  
No Isolation  
Category I are measurements performed on circuits not directly connected to the  
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50Vac/dc.  
This unit should not be used in Measurement Categories II, III, IV.  
Transients Overvoltage Surge (1.2 / 50uS pulse)  
Input Power:  
Input Power:  
(Low Voltage dc Power Option*)  
2500V  
1500V  
Ethernet:  
Input/Output Signals:  
1500V  
500V  
Note: *Units configured for external low power dc voltage, 12-36Vdc  
EMC EN61326:1997 + and A1:1998 + A2:2001  
Immunity and Emissions requirements for electrical equipment for measurement,  
control and laboratory.  
EMC Emissions Table 4, Class B of EN61326  
EMC Immunity** Table 1 of EN61326  
Note: **I/O signal and control lines require shielded cables and these cables  
must be located on conductive cable trays or in conduits. Furthermore,  
the length of these cables should not exceed 30 meters  
Refer to the EMC and Safety installation considerations (Guidelines) of this manual  
for additional information.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year  
from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty  
period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.  
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an  
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found  
to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any  
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits,  
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered  
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;  
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which  
wear are not warranted, including but not limited to contact points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes  
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its  
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the  
parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR  
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL  
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR  
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are  
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,  
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability  
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”  
under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on  
humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on  
humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER  
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage  
whatsoever arising out of the use of the Product(s) in such a manner.  
RETURN REQUESTS/INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING  
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM  
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR  
number should then be marked on the outside of the return package and on any correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in  
transit.  
FOR WARRANTY RETURNS, please have the following  
information available BEFORE contacting OMEGA:  
FOR NON-WARRANTY REPAIRS, consult OMEGA for current  
repair charges. Have the following information available  
BEFORE contacting OMEGA:  
1. Purchase Order number under which the product was  
PURCHASED,  
1. Purchase Order number to cover the COST of the repair,  
2. Model and serial number of the product under warranty,  
and  
2. Model and serial number of product, and  
3. Repair instructions and/or specific problems relative to the  
product.  
3. Repair instructions and/or specific problems relative to  
the product.  
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our  
customers the latest in technology and engineering.  
© Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,  
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior  
written consent of OMEGA ENGINEERING, INC.  
® , and  
®
are Trademarks of OMEGA ENGINEERING, INC.  
®
®
TRADEMARK NOTICE:  
, omega.com ,  
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577;  
6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150;  
2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Bezel Design” is a Trademark  
of NEWPORT Electronics, Inc. Used under License. Other US and International Patents pending or applied for.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
TEMPERATURE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
Wire: Thermocouple, RTD & Thermistor  
Calibrators & Ice Point References  
Recorders, Controllers & Process Monitors  
Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Transducers & Strain Gauges  
Load Cells & Pressure Gauges  
Displacement Transducers  
Instrumentation & Accessories  
FLOW/LEVEL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Rotameters, Gas Mass Flowmeters & Flow Computers  
Air Velocity Indicators  
Turbine/Paddlewheel Systems  
Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
pH Electrodes, Testers & Accessories  
Benchtop/Laboratory Meters  
Controllers, Calibrators, Simulators & Pumps  
Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Data Acquisition & Engineering Software  
Communications-Based Acquisition Systems  
Plug-in Cards for Apple, IBM & Compatibles  
Datalogging Systems  
Recorders, Printers & Plotters  
HEATERS  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Heating Cable  
Cartridge & Strip Heaters  
Immersion & Band Heaters  
Flexible Heaters  
Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Metering & Control Instrumentation  
Refractometers  
Pumps & Tubing  
Air, Soil & Water Monitors  
Industrial Water & Wastewater Treatment  
pH, Conductivity & Dissolved Oxygen Instruments  
M3355/0906  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Convection Oven H 394 User Manual
MTD Lawn Mower Series 54M User Manual
Multi Tech Systems Fax Machine MVP 800 User Manual
NAD DVD Player T 571 User Manual
Napoleon Fireplaces Furnace Model OS10 User Manual
Numark Industries All in One Printer TT500 User Manual
Omnimount Indoor Furnishings 10135 User Manual
Oreck Vacuum Cleaner 2005HH User Manual
Oricom Amplified Phone TP30 User Manual
Palsonic Home Theater System PMC 191 User Manual