Nortec Industries Humidifier MES U User Manual

MES-U Electrode  
Steam Humidifiers  
Installation, Operation,  
Maintenance, Spare Parts, and  
Exploded Views Guide  
IMPORTANT: Read and save this guide for future  
reference. This guide to be left with equipment owner.  
Form 03-111 Rev. 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure #1  
Operation Schematic  
INSTALLATION  
RECEIVING EQUIPMENT  
1. Check packing slip to ensure ALL material has  
been received.  
CONDENSATE RETURN  
(OPTIONAL)  
2. Inspect box for damage and note on shipping  
waybill accordingly.  
FILL  
CUP  
STEAM HOSE  
1” AIR  
GAP  
1
2
3
3. After unpacking, inspect unit for damage and if  
damage is found, advise shipper as soon as  
possible.  
ELECTRODES  
1. INLET CHAMBER  
2. FILL CHAMBER  
4. Inspect unit (humidifier) to ensure it is the correct  
model, phase, and voltage. If any are incorrect,  
advise the factory or your local representative  
immediately.  
3. WATER OVERFLOW  
CHAMBER (SAFETY DRAIN  
IN CASE OF FILL VALVE/  
CONTROL BOARD FAILURE)  
CYLINDER  
NOTE: All products are shipped on an F.O.B.  
factory basis. Any and all damage, loss, or breakage  
claims are to be made directly to the shipping  
company.  
STRAINER  
FILL  
VALVE  
TAP  
WATER  
SUPPLY  
DRAIN  
VALVE  
DRAIN  
PAN  
DRAIN  
CONNECTION  
The NORTEC MES-U electrode humidifier is the  
culmination of many years of research and  
development in the electrode humidifier industry. This  
unit has been built by skilled craftspeople and  
thoroughly tested before shipment and should, if the  
following instructions are observed, provide many  
years of trouble-free operation.  
DRAIN CANAL  
(OPEN TO ATMOSPHERE)  
An electronic timer uses the rate of amp fall to  
determine the water level. The objective is to  
concentrate current-carrying minerals in the cylinder  
so that a smaller volume of water is required to  
produce the rated steam output.  
FOR HUMIDIFIERS INSTALLED IN THE CITY  
OF LOS ANGELES: A city of Los Angeles approved  
spring-loaded double ball CHECK VALVE should be  
supplied and installed by the contractor on each of the  
potable water inlets to each humidifier.  
This achieves the longest life for the disposable  
cylinder because of minimal electrode coverage and  
use of less energy because the high concentration  
allows a minimal drain rate.  
Recommended valve manufacturer: Watts  
Regulator (phone 508-688-1811), model #7, size 3/8”  
NPT inlet and outlet.  
When 90% F.L.A. is reached, the fill valve will  
open refilling cylinder to 110% F.L.A. On occasion,  
the drain valve will also come on if water level is too  
low, indicating too high a concentration and the  
requirement for a dilution of the water in the cylinder.  
Each drain line from these humidifiers shall be  
routed, without dips or sags, to terminate above the  
flood level rim of a City of Los Angeles approved  
indirect waste receptor.  
No combustible materials shall be placed in the  
duct and/or the air plenum.  
If the water reaches top of cylinder before 110%  
F.L.A., the fill valve shuts off via the sensor and  
fill-boil-fill-boil cycle continues, cycling off the red high  
water sensor light until the concentration becomes  
high enough to reach 110% F.L.A. The above  
described control process will then take over.  
PRINCIPAL OF OPERATION  
When the humidistat calls, the cylinder fills to  
110% of the Full Load Amperage (F.L.A.) or to the top  
of the cylinder, whichever comes first. See Figure #1.  
If it reaches 110% F.L.A. the water heats and boils  
away to a level giving 90% F.L.A.  
- 1 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
for water pressure from 30 to 85 psi and are  
protected by the built-in strainer.  
WATER SUPPLY AND PLUMBING  
1. The orifice in the fill valve is sized for an extended  
water pressure range of 30 to 85 psi.  
4. For inlet water pressure outside this range, the  
factory should be contacted. (See Water Supply  
and Plumbing section of this manual.)  
2. For water pressure between 15 and 30 psi, notify  
the factory and the next larger size fill valve will be  
supplied.  
START-UP AND OPERATION  
3. For cases below 15 psi, notify the factory and a fill  
valve with an oversized orifice will be supplied.  
Check to see that the unit is securely mounted on  
a level surface with the proper drain and water supply.  
Check for correct voltage with appropriately sized  
service. Check that the steam distributor, steam  
supply hose, and condensate line are correctly  
installed and routed back to the unit. Ensure that the  
external control humidistat is located in an area to  
properly sense the relative humidity to be maintained  
by the humidifier, and that the interconnecting low  
voltage wires between the humidistat and the unit’s  
control terminal strip are in accordance with the wiring  
diagram.  
4. For cases above 85 psi, install a pressure  
reducing valve in the water feed line to the unit.  
5. With extremely dirty or muddy water sources, e.g.,  
some well sources, ensure proper filtration by  
adding an external filter to the water line entering  
the unit. (Consult factory for accessories such as  
filters.)  
6. DO NOT use completely demineralized water with  
this unit as it is the minerals that allow the  
electrode principle to work.  
Check all electrical connections for wires which  
may have become loose in shipping. Components  
damaged due to loose connections are NOT under  
warranty.  
7. DO NOT use a hot water source as it will cause  
deposits that will eventually block the fill valve  
orifice.  
Check electrode plugs to ensure they are pressed  
firmly onto the electrode pins. Important: Loose  
connections will cause overheating of the cylinder  
plugs, possibly melting the plugs and/or cylinder.  
WATER CONNECTION  
Figure #2  
Bottom View of MES-U Unit  
Open the isolating valve in the feed water line to  
the unit.  
3/8" Cold Water  
Olive Connection  
Make sure the humidistat is set high enough to call  
for humidification.  
Turn on the main disconnect in the primary service  
feeding the unit and check that unit has power at the  
primary terminal block.  
PUSH THE AUTO ON/OFF/DRAIN SWITCH TO  
“ON”.  
7/8" Drain  
Connection  
Water will start to enter the cylinder through its  
bottom port and rise in the cylinder to a point  
determined by the solid-state control circuitry.  
Use 7/8" I.D. Hose From Factory  
1. A copper compression olive type coupling for 1/4"  
O.D. soft copper tubing is provided with unit and  
requires no soldering for the water connection to  
the unit. See Figure #2.  
It is not unusual upon initial start-up for the  
water to fill the cylinder and cycle on the red high  
water sensor light.  
The red light simply acts as a safety to shut off the  
fill valve and prevent over-filling. With the red light on,  
the water in the cylinder will continue to heat and, after  
a few minutes, start to boil. After the boiling action of  
the water has lowered the water level below the  
2. An isolating valve should ALWAYS be placed in  
the feed water line allowing service of the fill valve.  
3. Each unit is fitted with a fill solenoid valve located  
on the base drain pan. Flow orifices are designed  
sensor at the top of the cylinder, the red light will go  
- 2 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
out and the fill solenoid will again open until the  
cylinder is again full.  
cylinder is completely used as indicated by the red  
high water sensor light illuminated on the cabinet.  
When this condition is reached, a new replacement  
cylinder is to be installed.  
This cycling of the red light and fill valve will  
continue until the unit’s full output capacity is reached  
after which the water level will automatically lower  
itself in the cylinder. (The increased concentration  
allows for lower electrode coverage while maintaining  
the same output.) When a stabilized condition is  
reached the water will be boiling close to the cylinder  
seam level. The solid state circuitry will maintain the  
proper concentration in the cylinder by introducing  
short drains only when necessary.  
NOTE: Red light may come on during initial  
start-up but does not mean cylinder replacement. See  
Start Up and Operation section of this manual.  
Consult factory or agent for replacement. Quote  
the cylinder model from the white 3-digit label on the  
cylinder or quote model, voltage, and serial number  
from unit specification label.  
If the cylinder is manually drained the above  
process will repeat itself.  
WHEN TO REPLACE THE STEAM CYLINDER  
The steam cylinder is disposable and must be  
replaced at the end of cylinder life. Cylinder life is  
dependent on water supply conditions and humidifier  
usage. Failure to replace the cylinder at the end of  
cylinder life may result in unit damage. NORTEC is  
not responsible for any damages resulting from, or  
attributable to, the failure to replace a used cylinder  
(see Manufacturer’s Warranty).  
Low Water Conductivity  
Should normalization of the unit be required  
immediately after start-up, the installer may speed up  
the process by artificially increasing water conductivity.  
During a fillcycle, the installer should dissolve half a  
teaspoon of table salt (no more) in a cup of water and  
add it to the cylinder by means of the fill cup attached  
to the plumbing section.  
Figure #4  
Cylinder Removal  
Open the plumbing compartment and add salt  
solution through cylinder outlet. Excessive amounts of  
salt will result in erratic operation of the unit; however,  
normalization of the unit will occur automatically  
through the solid-state control sequence.  
CAPACITY ADJUSTMENT  
Figure #3  
Adjustable Pot  
Adjustable  
Capacity Pot  
The MES-U series of humidifiers come with  
adjustable capacity (AC) PC boards. These boards  
have a pot labeled 20 to 100%. See Figure # 3.  
REMOVING THE OLD CYLINDER  
CYLINDER REPLACEMENT  
n
See Figure # 4.  
After an extended period of operation, in  
accordance with life expectancy information, the  
1. Turn off the water supply to unit.  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. The old cylinder must be drained completely  
before removing. This is done by pushing the auto  
on/off/drain switch to the drainposition.  
3. The white sensor plug on all units is for the sensor  
pin, which always goes on the single pin offset  
from the others. See Figure # 5.  
3. When completely drained, push the auto  
4. Ensure that cylinder plugs are very snug on the  
pins.  
on/off/drain switch to the offposition.  
4. Open the main disconnect during the entire  
cylinder change operation.  
5. For loose fitting plugs, a temporary solution is to  
squeeze plugs with a pair of pliers before  
installing. Since loose plugs may generate  
enough heat to melt and destroy the plug and  
cylinder new plugs must be ordered.  
5. The power wires to the cylinder are attached by  
cylinder plugs to the electrode pins on top of the  
cylinder. Pull these plugs vertically off the pins.  
See Figure # 4.  
MAINTENANCE  
6. Using slot screwdriver, loosen the steam hose  
clamp(s) and pull steam hose off vertically.  
WARNING! The plumbing and electrical  
compartments contain high voltage components and  
wiring. The access cover is attached with screws.  
Access should be limited to authorized personnel only.  
7. The cylinder is now ready to be lifted out of the  
unit.  
EXTENDED SHUTDOWN  
INSTALLING THE NEW CYLINDER  
Figure #5  
Plugs  
Before disconnecting power to the humidifier for a  
period of extended shutdown, ALWAYS DRAIN the  
cylinder first. Otherwise, the electrodes are subject to  
harmful corrosion which drastically shortens the  
cylinder life. Do NOT leave the switch in the DRAIN  
position indefinitely as the drain coil could burn out.  
Leave the switch in the OFF position and openthe  
main external fused disconnect to stop power to the  
humidifier. Close the shut off valve in the water supply  
line feeding the humidifier.  
White  
Sensor Plug  
1Ø  
Sensor Pin  
Cylinder  
Plug  
TROUBLESHOOTING  
Cylinder Pin  
Cylinder Pin  
TERMS USED  
Sensor Pin  
F.L.A. (Full Load Amps): Refers to amps listed on  
the humidifier specification label.  
3Ø  
Cylinder Pin  
Cylinder Pin  
SHORT CYCLING: When the on timeof the  
humidifier is less than ten minutes upon a call for  
humidity. To correct short cycling, all humidifiers have  
a capacity adjustment which allows the output of the  
humidifier to be reduced to as low as 20% of rated  
output, thus extending the on timerequired to  
maintain output.  
Cylinder Pin  
1. The reverse procedure should be followed to  
install a new cylinder. The main disconnect is to  
be left open until the cylinder is completely  
installed and reconnected.  
FOAMING: The phenomenon which can occur in  
water when the impurities, already in the water reach  
an excess concentration as a result of boiling away  
pure water and the continued boiling action agitating  
the contained water. The humidifier electronics are  
designed to prevent this occurrence although in  
extreme cases, water will foam with little concentration  
making it necessary to have the drain time of the  
water, contained in the cylinder, increased. Foaming  
2. Ensure that the cylinder mounting stubs are  
seated properly in the allotted side mounting slots  
within the unit.  
- 4 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
is normally caused by short cycling, a restricted drain,  
or back pressure. The foam, generated in these  
instances, is conductive and may lead to false full  
cylinder indication if the level of the foam approaches  
the top of the cylinder.  
Recheck that the auto on/off/drainswitch is still  
at on. If it is, then shut off the main disconnect and  
check fuses or breaker of the main disconnect. If they  
are serviceable, turn power back on.  
To test for a defective auto on/off/drainswitch,  
connect a wire from the fuse directly to terminal 6 on  
the external controls strip. If the contactor activates,  
the onside of the switch is defective. If the contactor  
does not activate, the PC board could be defective.  
BACK PRESSURE: The restriction of steam flow  
caused by long steam runs, improperly sloped steam  
lines, elbows changing the direction of steam flow from  
horizontal to vertical without a drain leg, any plumbing  
detail allowing the accumulation of condensate,  
undersized steam line, improper steam distributor,  
downward air flow onto the distributor causing excess  
static pressure at the steam outlets, or high static  
pressure ducts (not probable). To overcome excess  
static pressure in the duct, a fill cup extension kit  
should be used. In down flow applications, a down  
flow distributor should be used, but in some cases the  
fill cup extension will also be required.  
If the 3 amp control fuse blows when the wire from  
the fuse touches terminal 6 on the external controls  
strip, contactor holding coil could be shorted. Replace  
contactor if necessary.  
Return wires to normal.  
After the necessary components have been  
replaced and the contactor pulls in, there is line  
voltage to the cylinder and the control sequence can  
begin.  
RESET UNIT (HUMIDIFIER): To reset the  
humidifier, the auto on/off/drain switch at the front of  
the humidifier should be switch to the Offposition for  
a minimum of five seconds and then switched back to  
the Onposition.  
Approximately 30 seconds after the contactor pulls  
in, the fill valve coil should energize. There is also a  
visible fill relay on the printed circuit board. It is the  
one located farthest from the C.T. core. The points on  
this relay must be touching in order for the fill valve  
coil to be energized.  
MONITORED LEG: Refers to the primary wire to  
the cylinder which loops through the current sensing  
devise of the main PCB. This wire is terminated at the  
red cylinder plug at the cylinder.  
If the points will not touch after the built-in time  
delay, then the sensor input may be interfering. To  
confirm, remove the black and red sensor wires from  
the terminals 6 and 10 on the PC board. Wait 30  
seconds and if the fill relay points not touch, then  
sensor should be replaced. If they do not touch, then  
the basic PC board could be faulty. To confirm,  
disconnect the red wire from terminal 18 and touch it  
to terminal 14. If the fill valve coil activates then the  
basic PC board should be replaced. If it still does not  
activate then the fill valve coil should be replaced.  
STARTING POINT  
Auto On/Off/Drain switch in “On” position - unit will  
not fill:  
When the on/off control circuit is made and the  
auto on/off/drainswitch is pushed to on, the 24 volt  
holding coil of the primary contactor should energize.  
The resulting magnetic pull closes the high voltage  
contacts with a distinct and audible clunk. If the  
contactor will not make, then inspect the following  
while referring to the wiring diagram:  
Having changed the necessary components, water  
starts filling the cylinder and begins to submerge the  
electrodes. Because of the high voltage across the  
electrodes, the water can now conduct electricity.  
1. Check for 24 Vac across terminals 18 and 26 on  
PC board.  
Red “Change Cylinder” light on - Water at top of cyl-  
inder:  
2. Jumper the humidistat on external control terminal  
strip. If contactor operates, then control system is  
at fault.  
This is a common occurrence on start-up. See  
Start-Up and Operation section of this manual.  
3. The low voltage 3 amp fuse located in the control  
box could be blown.  
If the cylinder is old, it indicates end of cylinder life.  
Time to replace the cylinder. See When To Replace  
The Steam Cylindersection of this manual.  
4. The contactor holding coil could be open or  
shorted.  
5. The switch could be defective.  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Red “Change Cylinder” light on - Water NOT at top of  
cylinder:  
Water foaming to top of cylinder causing false full  
cylinder indication. This also may be accompanied by  
arcing (flashing) inside cylinder. Refer to Terms  
Usedregarding foaming.  
Water remains at high level and won’t concentrate:  
This is normal on cold start-up and can be  
accelerated by adding maximum 1/2 tsp. of dissolved  
salt to the cylinder (through the plastic fill cup) on fill  
cycle. See Low Water Conductivitysection of this  
manual.  
If unit has been operating extensively, observe for  
normal fill-boil-fill-boil cycle; no drain should be  
occurring. If drain occuring, check for leaking drain  
valve or back pressure.  
Water beyond top of cylinder up into spout:  
If the red light is not on and fill is still activated,  
jumper across the connection of sensor on basic PC  
board. If fill remains on when connection is jumped,  
then basic PC board is faulty. If fill shuts off, then  
verify primary voltage to cylinder (contactor  
energized). If primary voltage is present, the high  
water sensor PCB is defective.  
Unit drains continually:  
May be caused by foaming and/or back pressure,  
or leaking drain valve.  
Cylinder is almost empty, check for magnetic pull  
on drain solenoid indicating miswiring. If no pull, drain  
actuator is blocked open; remove, disassemble and  
clean.  
If drain is occurring through activated drain valve,  
valve is miswired or electronics are faulty - consult  
factory.  
If drain is occurring through the overflow on the fill  
cup, this is due to abnormal restriction on the steam  
line and back pressure forces water out of the cylinder;  
therefore, water cannot concentrate and level must  
stay high; review installation of steam line to ensure no  
blockages or excessive static pressure in air system.  
- 6 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONS  
WIDTH in.(cm)  
MES-U / MES-P  
DEPTH  
WIDTH in.(cm)  
HEIGHT  
in.(cm)  
(REMOTE ELECTRICAL) (ATTACHED ELECTRICAL)  
in.(cm)  
5 *  
10  
15  
20  
25  
30  
6.6 (16.7 cm)  
6.6 (16.7 cm)  
8.4 (21.3 cm)  
8.4 (21.3 cm)  
10.5 (26.7 cm)  
10.5 (26.7 cm)  
8.6 (21.9 cm)  
8.6 (21.9 cm)  
10.5 (26.7 cm)  
10.5 (26.7 cm)  
10.5 (26.7 cm)  
10.5 (26.7 cm)  
10.7 (27.1 cm)  
10.7 (27.1 cm)  
12.6 (32.2 cm)  
12.6 (32.2 cm)  
12.6 (32.2 cm)  
12.6 (32.2 cm)  
13.5 (34.4 cm)  
17.3 (43.9 cm)  
19.4 (49.3 cm)  
19.4 (49.3 cm)  
21.3 (54.0 cm)  
21.3 (54.0 cm)  
WEIGHTS (DRY)  
3
CONFIGURATION  
1
2
4
5
6
7
8
9
MES-U / MES-P  
lbs(kg)  
lbs(kg)  
lbs(kg)  
lbs(kg)  
lbs(kg)  
lbs(kg)  
lbs(kg)  
lbs(kg)  
lbs(kg)  
5*  
8.2 (3.7) 9.6 (4.3) 9.0 (4.1) 10.4 (4.7) 13.7 (6.2) 13.1 (6.0) 14.5 (6.6) 8.8 (4.0) 13.0 (5.9)  
8.7 (4.0) 10.1 (4.6) 9.5 (4.3) 10.9 (4.9) 14.2 (6.4) 13.7 (6.2) 15.0 (6.8) 9.4 (4.2) 13.5 (6.1)  
12.6 (5.7) 13.9 (6.3) 13.4 (6.1) 14.8 (6.7) 22.0 (10.0) 21.5 (9.7) 22.9 (10.4) 13.2 (6.0) 21.3 (9.7)  
14.1 (6.4) 15.4 (7.0) 14.9 (6.7) 16.2 (7.4) 23.5 (10.7) 23.0 (10.4) 24.3 (11.0) 14.7 (6.7) 22.8 (10.3)  
10  
15/20  
25/30  
NOTES:  
1. FOR HEIGHT OF 5 LB PVC USE HEIGHT OF 10 LB MODEL.  
2. PVC = PRIMARY VOLTAGE CONNECTION.  
3. MODEL SHOWN: 163-91X5 (CONFIGURATION #5) WITH  
CP (CLOSED PLUMBING) COVER REMOVED.  
condair  
TOP VIEW  
AUTO/ON  
OFF  
condair  
DRAIN  
FRONT VIEW  
LEFT VIEW  
MES-U/MES-P HUMIDIFIER  
MESU DIM 10/19/98  
PHYSICAL DATA  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRIMARY  
POWER  
24 VAC  
INPUT  
(By Others)  
PRIMARY  
CONTACTOR  
24 vac  
ON/OFF  
CONTROLS  
(By Others)  
PRIMARY TERMINAL  
BLOCK  
.187 insulated fast-on  
For field connection  
(provided with  
PVC unit)  
3 AMP  
FUSE  
ON  
SWITCH OFF  
DRAIN  
HIGH WATER  
SENSOR PCB  
FILL  
VALVE  
DRAIN  
VALE  
HIGH VOLTAGE  
ELECTRODE LEADS  
(BY OTHERS OR  
INCLUDED WITH  
PVC UNIT)  
CHANGE  
CYLINDER  
LAMP  
-2 LEADS  
FOR SINGLE  
PHASE  
-3 LEADS  
FOR THREE  
PHASE  
CURRENT  
TRANSFORMER  
MES-U  
CONTROL  
BOARD  
STEAM CYLINDER  
NOTE: SOLID LINES WIRING BY OTHERS  
MES-U INTERNAL AND FIELD WIRING  
(For PVC or LVC unit with remote or attached electrical)  
WIRING DIAGRAM number 150-6240 REV. B  
- 8 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
NORTEC INDUSTRIES INCORPORATED and/or NORTEC AIR  
CONDITIONING INDUSTRIES LIMITED (hereinafter collectively referred to as THE  
COMPANY), warrant for a period of two years from date of shipment, that THE  
COMPANY’s manufactured and assembled products, not otherwise expressly  
warranted (with the exception of the cylinder) are free from defects in material and  
workmanship. No warranty is made against corrosion, deterioration, or suitability of  
substituted materials used as a result of compliance with government regulations.  
THE COMPANY’s obligations and liabilities under this warranty are limited to  
furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory,  
providing the defective part(s) is returned freight prepaid by the customer. Parts used  
for repairs are warranted for the balance of the term of the warranty on the original  
humidifier or 90 days, whichever is longer.  
The warranties set forth herein are in lieu of all other warranties expressed or  
implied by law. No liability whatsoever shall be attached to THE COMPANY until said  
products have been paid for in full and then said liability shall be limited to the original  
purchase price for the product. Any further warranty must be in writing, signed by an  
officer of THE COMPANY.  
THE COMPANY’s limited warranty on accessories, not of NORTEC’s  
manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the  
original equipment manufacturer from date of original shipment of humidifier.  
THE COMPANY makes no warranty and assumes no liability unless the  
equipment is installed in strict accordance with a copy of the catalog and installation  
manual in effect at the date of purchase and by a contractor approved by THE  
COMPANY to install such equipment.  
THE COMPANY makes no warranty and assumes no liability whatsoever for  
consequential damage or damage resulting directly from misapplication, incorrect sizing  
or lack of proper maintenance of the equipment.  
THE COMPANY retains the right to change the design, specification and  
performance criteria of its products without notice or obligation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model # :_________________________  
Serial # :_________________________  
Cylinder # :_______________________  
Cylinder Last Replaced:  
_________________________  
MTH/DAY/YR  
_________________________  
MTH/DAY/YR  
_________________________  
MTH/DAY/YR  
NORTEC INDUSTRIES INC.  
NORTEC AIR CONDITIONING  
INDUSTRIES LTD*.  
P.O. Box 698  
826 Proctor Avenue  
Ogdensburg, NY 13669  
2740 Fenton Road  
Ottawa, ON K1T 3T7  
A WMH COMPANY  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Clothes Dryer T 4422 C User Manual
Miele Washer W 1918 User Manual
Moulinex Vacuum Cleaner HAND HELD VACCUUM CLEANER User Manual
NordicTrack Treadmill NCTL09992 User Manual
Ocean Kayak Marine Instruments 14561 User Manual
Oki Printer 8480FB User Manual
Omnimount TV Video Accessories Verona 55FP User Manual
Omron Blood Pressure Monitor M1 Plus User Manual
Onkyo Speaker SKS HT530 User Manual
Panasonic Universal Remote CZ RWSC1U User Manual