National Instruments Network Card NI 9401 User Manual

OPERATING INSTRUCTIONS AND SPECIFICATIONS  
NI 9401  
8-Channel, TTL Digital Input/Output Module  
Français Deutsch  
ni.com/manuals  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Guidelines  
Operate the NI 9401 only as described in these operating  
instructions.  
Hot Surface This icon denotes that the component may be  
hot. Touching this component may result in bodily injury.  
Safety Guidelines for Hazardous Locations  
The NI 9401 is suitable for use in Class I, Division 2, Groups A, B,  
C, D, T4 hazardous locations; Class I, Zone 2, AEx nC IIC T4, and  
Ex nC IIC T4 hazardous locations; and nonhazardous locations  
only. Follow these guidelines if you are installing the NI 9401 in a  
potentially explosive environment. Not following these guidelines  
may result in serious injury or death.  
Caution Do not disconnect I/O-side wires or connectors  
unless power has been switched off or the area is known  
to be nonhazardous.  
Caution Do not remove modules unless power has been  
switched off or the area is known to be nonhazardous.  
© National Instruments Corp.  
3
NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Caution Substitution of components may impair  
suitability for Class I, Division 2.  
Caution For Zone 2 applications, install the system  
in an enclosure rated to at least IP 54 as defined by  
IEC 60529 and EN 60529.  
Caution For Zone 2 applications, connected signals must  
be within the following limit:  
Capacitance..........................0.2 μF max  
Special Conditions for Hazardous Locations Use in Europe  
This equipment has been evaluated as EEx nC IIC T4 equipment  
under DEMKO Certificate No. 03 ATEX 0324020X. Each module  
is marked  
II 3G and is suitable for use in Zone 2 hazardous  
locations. If you are using the NI 9401 in Gas Group IIC hazardous  
locations or in ambient temperatures of –40 °C Ta 70 °C, you  
must use the device in an NI chassis that has been evaluated as  
EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.  
NI 9401 Operating Instructions and Specifications  
4
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Special Conditions for Marine Applications  
Some modules are Lloyd’s Register (LR) Type Approved for  
marine applications. To verify Lloyd’s Register certification, visit  
ni.com/certification and search for the LR certificate, or  
look for the Lloyd’s Register mark on the module.  
Caution To meet radio frequency emission requirements  
for marine applications, use shielded cables and install  
the system in a metal enclosure. Suppression ferrites  
must be installed on power supply inputs near power  
entries to modules and controllers. Power supply and  
module cables must be separated on opposite sides of the  
enclosure and must enter and exit through opposing  
enclosure walls.  
© National Instruments Corp.  
5
NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the NI 9401  
The NI 9401 has a 25-pin DSUB connector that provides  
connections for eight digital input/output channels.  
1
2
COM  
NC  
DIO0  
NC  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
3
COM  
COM  
NC  
DIO1  
DIO2  
NC  
4
5
6
COM  
COM  
NC  
DIO3  
DIO4  
NC  
7
8
9
COM  
COM  
NC  
DIO5  
DIO6  
NC  
10  
11  
12  
13  
COM  
COM  
DIO7  
Figure 1. NI 9401 Pin Assignments  
NI 9401 Operating Instructions and Specifications  
6
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Each channel has a DIO pin to which you can connect a digital  
input or output device. The eight DIO channels are internally  
referenced to COM, so you can use any of the nine COM lines as  
a reference for the external signal.  
The DIO channels are grouped in two ports, one containing  
channels 0, 1, 2, and 3, and one containing channels 4, 5, 6, and 7.  
You can independently configure each digital port in software for  
input or output. Note that all four channels in the port must share  
the same line direction. Refer to the software help for information  
about configuring ports on the NI 9401.  
Each channel also has a pull-down resistor and includes  
overvoltage, overcurrent, and short-circuit protection. Refer to the  
Specifications section for more information about input thresholds  
and overvoltage protection. Refer to the Overcurrent Protection  
section for more information about overcurrent protection.  
© National Instruments Corp.  
7
NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 2 illustrates how to connect an SPI device to the NI 9401.  
In this example, the three channels assigned to output signals are  
on one port and the channel assigned to an input signal is on the  
other port.  
SS  
DIO3:0  
Configured  
for Output  
SCLK  
MOSI  
MISO  
DIO7:4  
Configured  
for Input  
SPI Device  
NI 9401  
Figure 2. Connecting an SPI Device to the NI 9401  
NI 9401 Operating Instructions and Specifications  
8
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 3 illustrates how to connect several types of digital devices  
to the NI 9401.  
DIO0 as Input  
TTL Signal  
Dev 1  
+5 V  
DIO1 as Input  
Dev 2  
+5 V  
COM  
LED  
DIO7 as Output  
Dev 3  
NI 9401  
Figure 3. Connecting Digital Devices to the NI 9401  
© National Instruments Corp.  
9
NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Overcurrent Protection  
Overcurrent protection on the NI 9401 allows only a specified  
amount of current for switching DIO channels or sourcing the  
output load. If the NI 9401 goes into an overcurrent state, by  
exceeding the specified maximum switching frequency or the  
output load, the module power supply begins to drop in voltage  
until it completely turns off or the overcurrent condition is  
removed. When the module is in this state, it can accept new line  
direction configuration and output state data but cannot pass valid  
input data to the software. Refer to the Specifications section for  
more information about the maximum switching frequency and  
output load for each channel.  
NI 9401 Operating Instructions and Specifications  
10  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Sleep Mode  
This module supports a low-power sleep mode. Support for sleep  
mode at the system level depends on the chassis that the module is  
plugged into. Refer to the chassis manual for information about  
support for sleep mode. If the chassis supports sleep mode, refer to  
the software help for information about enabling sleep mode. Visit  
ni.com/info and enter cseriesdoc for information about  
C Series documentation.  
Typically, when a system is in sleep mode, you cannot  
communicate with the modules. In sleep mode, the system  
consumes minimal power and may dissipate less heat than it does  
in normal mode. Refer to the Specifications section for more  
information about power consumption and thermal dissipation.  
© National Instruments Corp.  
11 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
The following specifications are typical for the range –40 to 70 °C  
unless otherwise noted. All voltages are relative to COM unless  
otherwise noted.  
Input/Output Characteristics  
Number of channels..........................8 DIO channels  
Default power-on line direction........Input  
Input/output type...............................TTL, single-ended  
NI 9401 Operating Instructions and Specifications  
12  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Digital logic levels  
Input  
Voltage .................................5.25 V max  
High, VIH..............................2 V min  
Low, VIL ...............................0.8 V max  
Output  
High, VOH.............................5.25 V max  
Sourcing 100 μA ...........4.7 V min  
Sourcing 2 mA...............4.3 V min  
Low, VOL  
Sinking 100 μA .............0.1 V max  
Sinking 2 mA.................0.4 V max  
© National Instruments Corp.  
13 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maximum input signal switching frequency by number of input  
channels, per channel  
8 input channels..........................9 MHz  
4 input channels..........................16 MHz  
2 input channels..........................30 MHz  
Maximum output signal switching frequency by number of output  
channels with an output load of 1 mA, 50 pF, per channel  
8 output channels........................5 MHz  
4 output channels........................10 MHz  
2 output channels........................20 MHz  
I/O propagation delay .......................100 ns max  
I/O pulse width distortion.................10 ns typ  
Input current (0 V Vin 4.5 V)...... 250 μA typ  
Input capacitance ..............................30 pF typ  
Input rise/fall time.............................500 ns max  
Overvoltage protection,  
channel-to-COM............................... 30 V max on one channel at  
a time; however, continued  
use at this level will degrade  
the life of the module.  
NI 9401 Operating Instructions and Specifications  
14  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MTBF ...............................................1,244,763 hours at 25 °C;  
Bellcore Issue 2, Method 1,  
Case 3, Limited Part Stress  
Method  
Note Contact NI for Bellcore MTBF specifications  
at other temperatures or for MIL-HDBK-217F  
specifications.  
Power Requirements  
Power consumption from chassis  
Active mode ...............................580 mW max  
Sleep mode .................................1 mW max  
Thermal dissipation (at 70 °C)  
Active mode ...............................580 mW max  
Sleep mode .................................1 mW max  
Physical Characteristics  
If you need to clean the module, wipe it with a dry towel.  
Weight...............................................145 g (5.1 oz)  
© National Instruments Corp.  
15 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
Maximum Voltage1  
Connect only voltages that are within the following limits.  
Channel-to-COM.............................. 30 V max on one channel  
at a time, Measurement  
Category I  
Isolation Voltages  
Channel-to-channel...........................None  
Channel-to-earth ground  
Continuous .................................60 VDC, Measurement  
Category I  
Withstand....................................1,000 Vrms, verified by a 5 s  
dielectric withstand test  
Measurement Category I is for measurements performed on  
circuits not directly connected to the electrical distribution system  
referred to as MAINS voltage. MAINS is a hazardous live electrical  
1
The maximum voltage that can be applied or output between any channel and COM  
without damaging the module or other devices.  
NI 9401 Operating Instructions and Specifications  
16  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
supply system that powers equipment. This category is for  
measurements of voltages from specially protected secondary  
circuits. Such voltage measurements include signal levels, special  
equipment, limited-energy parts of equipment, circuits powered by  
regulated low-voltage sources, and electronics.  
Caution Do not connect the NI 9401 to signals or use  
for measurements within Measurement Categories II,  
III, or IV.  
Safety Standards  
This product is designed to meet the requirements of the following  
standards of safety for electrical equipment for measurement,  
control, and laboratory use:  
IEC 61010-1, EN 61010-1  
UL 61010-1, CSA 61010-1  
Note For UL and other safety certifications, refer to the  
product label or visit ni.com/certification, search  
by module number or product line, and click the  
appropriate link in the Certification column.  
© National Instruments Corp.  
17 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hazardous Locations  
U.S. (UL) ..........................................Class I, Division 2,  
Groups A, B, C, D, T4;  
Class I, Zone 2,  
AEx nC IIC T4  
Canada (C-UL) .................................Class I, Division 2,  
Groups A, B, C, D, T4;  
Class I, Zone 2,  
Ex nC IIC T4  
Europe (DEMKO).............................EEx nC IIC T4  
Environmental  
National Instruments C Series modules are intended for indoor use  
only but may be used outdoors if installed in a suitable enclosure.  
Refer to the manual for the chassis you are using for more  
information about meeting these specifications.  
Operating temperature  
(IEC 60068-2-1, IEC 60068-2-2) .....40 to 70 °C  
Storage temperature  
(IEC 60068-2-1, IEC 60068-2-2) .....40 to 85 °C  
Ingress protection..............................IP 40  
NI 9401 Operating Instructions and Specifications  
18  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating humidity  
(IEC 60068-2-56)..............................10 to 90% RH,  
noncondensing  
Storage humidity  
(IEC 60068-2-56)..............................5 to 95% RH,  
noncondensing  
Maximum altitude.............................2,000 m  
Pollution Degree (IEC 60664)..........2  
Shock and Vibration  
To meet these specifications, you must panel mount the system.  
Operating vibration  
Random (IEC 60068-2-64).........5 grms, 10 to 500 Hz  
Sinusoidal (IEC 60068-2-6) .......5 g, 10 to 500 Hz  
Operating shock  
(IEC 60068-2-27)..............................30 g, 11 ms half sine,  
50 g, 3 ms half sine,  
18 shocks at 6 orientations  
© National Instruments Corp.  
19 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electromagnetic Compatibility  
This product is designed to meet the requirements of the following  
standards of EMC for electrical equipment for measurement,  
control, and laboratory use:  
EN 61326 EMC requirements; Industrial Immunity  
EN 55011 Emissions; Group 1, Class A  
CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A  
Note For EMC compliance, operate this device with  
shielded cabling.  
CE Compliance  
This product meets the essential requirements of applicable  
European directives, as amended for CE markings, as follows:  
2006/95/EC; Low-Voltage Directive (safety)  
2004/108/EC; Electromagnetic Compatibility Directive  
(EMC)  
Note Refer to the Declaration of Conformity (DoC) for  
this product for any additional regulatory compliance  
information. To obtain the DoC for this product, visit  
NI 9401 Operating Instructions and Specifications  
20  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ni.com/certification, search by module number or  
product line, and click the appropriate link in the  
Certification column.  
Environmental Management  
National Instruments is committed to designing and manufacturing  
products in an environmentally responsible manner. NI recognizes  
that eliminating certain hazardous substances from our products is  
beneficial not only to the environment but also to NI customers.  
For additional environmental information, refer to the NI and the  
Environment Web page at ni.com/environment. This page  
contains the environmental regulations and directives with which  
NI complies, as well as other environmental information not  
included in this document.  
Waste Electrical and Electronic Equipment (WEEE)  
EU Customers At the end of their life cycle, all products  
must be sent to a WEEE recycling center. For more  
information about WEEE recycling centers and National  
Instruments WEEE initiatives, visit ni.com/  
environment/weee.htm.  
© National Instruments Corp.  
21 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
⬉ᄤֵᙃѻક∵ᶧ᥻
ㅵ⧚
⊩ ˄Ё೑  
˅
RoHS  
ヺড়Ё೑⬉ᄤֵᙃ  
Ё೑ᅶ᠋  
National Instruments  
ѻકЁ䰤
Փ⫼ᶤѯ᳝ᆇ⠽䋼ᣛҸ  
DŽ݇Ѣ  
(RoHS)  
Ё೑  
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ  
RoHS  
National Instruments  
ni.com/environment/rohs_chinaDŽ  
about China RoHS compliance, go to  
environment/rohs_china  
(For information  
ni.com/  
.)  
Where to Go for Support  
The National Instruments Web site is your complete resource for  
technical support. At ni.com/support you have access to  
everything from troubleshooting and application development  
self-help resources to email and phone assistance from  
NI Application Engineers.  
National Instruments corporate headquarters is located at  
11500 North Mopac Expressway, Austin, Texas, 78759-3504.  
National Instruments also has offices located around the world to  
help address your support needs. For telephone support in the  
United States, create your service request at ni.com/support  
and follow the calling instructions or dial 512 795 8248. For  
NI 9401 Operating Instructions and Specifications  
22  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
telephone support outside the United States, contact your local  
branch office:  
Australia 1800 300 800, Austria 43 662 457990-0,  
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,  
Canada 800 433 3488, China 86 21 5050 9800,  
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,  
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,  
Germany 49 89 7413130, India 91 80 41190000,  
Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196,  
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,  
Malaysia 1800 887710, Mexico 01 800 010 0793,  
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,  
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,  
Portugal 351 210 311 210, Russia 7 495 783 6851,  
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,  
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,  
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,  
Taiwan 886 02 2377 2222, Thailand 662 278 6777,  
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545  
© National Instruments Corp.  
23 NI 9401 Operating Instructions and Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the  
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other  
product and company names mentioned herein are trademarks or trade names of their respective companies.  
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,  
the patents.txt file on your media, or ni.com/patents.  
© 2005–2008 National Instruments Corp. All rights reserved.  
374068D-01  
Jun08  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Dishwasher G 803 User Manual
Miele Ventilation Hood DA 3180 User Manual
Miele Washer w 3204 User Manual
NEC Switch N8406 022A User Manual
NetComm Network Card IG1000 User Manual
Nokia Cell Phone V 6016i User Manual
Oster Electric Steamer 4711 User Manual
Outdoor Gourmet Gas Grill CG3023E User Manual
OWI Speaker IC6 DVC User Manual
Panasonic Electric Shaver ES8094 User Manual