OPERATING INSTRUCTIONS
FP-3000
FieldPoint Fieldbus Network Module
This document provides a quick guide to install and configure the
FP-3000 network module. For more detailed information on using
the network module, refer to the FP-3000 user manual.
Features
•
•
•
•
FOUNDATION Fieldbus H1 interface to control network
Runs on 11 to 30 VDC power
Built-in high efficiency power supply powers I/O modules
–40 to +60 °C operation
Kit Contents and Optional Equipment
Your kit contains the following items:
•
•
FP-3000 network module
Accessories: protective connector cover, two DIN rail stops,
Device Description diskette
You can order the following optional equipment from National
Instruments:
•
•
Panel mount accessory, part number 777609-01
Terminal bases and I/O modules, complete list of terminal
bases and I/O modules in the National Instruments online
catalog at www.natinst.com
•
•
Cables
24 VDC power supply
FieldPoint ™ is a trademark of National Instruments Corporation. Product and company names
mentioned herein are trademarks or trade names of their respective companies.
322170B-01
© Copyright 1999 National Instruments Corp. All rights reserved.
June 1999
Download from Www.Somanuals.com. All Manuals Search And Download.
b. Slide the FP-3000 to the desired position along the
DIN rail.
c. Lock the rail clip.
•
Installing onto a panel mount accessory, which you can
order separately from National Instruments:
a. Snap the panel mount accessory onto the module
as shown in Figure 3.
Press
Figure 3. Mounting the FP-3000 onto a Panel Mount Accessory
b. Lock the rail clip.
c. Mount the FP-3000 and panel mount accessory onto
the desired surface. You can drill pilot holes using the
directions in the FieldPoint Network Module Panel
Mount Accessory installation guide.
3. Add terminal bases with their local bus connectors firmly
mated to the FP-3000 local bus connector.
4. Place the protective cover over the local bus connector of the
last terminal base in the bank. Figure 4 shows an installed
FP-3000 network module on a DIN rail.
© National Instruments Corp.
3
FP-3000
Download from Www.Somanuals.com. All Manuals Search And Download.
Local Bus Connectors
Firmly Mated
Protective
Cover
Rail Clip
Locked
DIN
Rail
Figure 4. Network Module and Terminal Base Mounted on a DIN Rail
Network Connection
Connect the FP-3000 to a Fieldbus network using the 9-position
DSub connector on the FP-3000. The pinout of the DSub connector
is shown in Figure 5.
1
2
3
4
5
6
7
8
9
NC = No Connection
Figure 5. Dsub Connector Pinout
FP-3000
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Powering the FP-3000
Caution Connect the FP-3000 to the terminal base before
applying power to the FP-3000 to avoid damaging the
FP-3000 or a terminal base.
An 11-30 VDC power supply is required by each FP-3000 on your
network. The FP-3000 filters and regulates this supplied power and
provides power for all the I/O modules in the bank. Therefore, you
do not need to provide power separately to each FieldPoint I/O
module in the bank. If your field I/O devices need to be powered
separately, you can use the terminals provided on each terminal
base for such power supply connections.
The power connector is a 6-pin screw terminal connector whose
pinout is shown in Figure 6.
v
v
v
11-30 VDC
V
+
–
Backup Power
Supply
(optional)
c
To adjacent device
(optional connection)
c
c
C
11-30 VDC
Primary Power
Supply
+
–
Figure 6. FP-3000 Power Connector Pinout
Connect the primary power supply to the center V and C pair. You
can connect an optional backup power supply to the left V and
C pair. The right V and C pair provides a convenient means of
connecting power to the V and C terminals of a terminal base.
Figure 6 shows this optional connection.
Specifications
FP-3000.............................................FOUNDATION Fieldbus H1
Integrity.............................................Checksum
Power supply range...........................11 to 30 VDC
Maximum terminal bases/bank.........9
© National Instruments Corp.
5
FP-3000
Download from Www.Somanuals.com. All Manuals Search And Download.
Maximum banks/fieldbus
Segment (without repeaters).............32
Power consumption...........................6 W + 1.15 * ∑(I/O module
consumption)
Operating temperature ......................–40 to +60 °C
Storage temperature..........................–55 to +100 °C
Relative humidity..............................5% to 90% non-condensing
CE Mark Compliance
This product meets applicable EU directive(s) as follows:
EMC directive
Immunity....................................EN 50082-1:1994
Emissions ...................................EN 55011:1991 Group I
Class A at 10 meters
Mechanical Dimensions
Figure 7 shows the mechanical dimensions of the FP-3000.
Dimensions are given in inches [millimeters].
4.22 [107.19]
4.31
[109.5]
3.60 [91.44]
Figure 7. Mechanical Dimensions
FP-3000
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
|