N Tron Switch 405FXE SC YY User Manual

400 Series  
Industrial Ethernet Switches  
Installation  
Guide  
(Revised 2010-11-15)  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright, © N-TRON Corp., 2008  
820 S. University Blvd., Suite 4E  
Mobile, AL 36609 USA  
All rights reserved. Reproduction, adaptation, or translation without prior written permission from N-TRON  
Corp. is prohibited, except as allowed under copyright laws.  
Ethernet is a registered trademark of Xerox Corporation. All other product names, company names, logos  
or other designations mentioned herein are trademarks of their respective owners.  
The information contained in this document is subject to change without notice. N-TRON Corp. makes no  
warranty of any kind with regard to this material, including, but not limited to, the implied warranties of  
merchantability or fitness for a particular purpose. In no event shall N-TRON Corp. be liable for any  
incidental, special, indirect or consequential damages whatsoever included but not limited to lost profits  
arising out of errors or omissions in this manual or the information contained herein.  
Warning  
Do not perform any services on the unit unless qualified to do so. Do not substitute unauthorized parts or  
make unauthorized modifications to the unit.  
Do not operate the unit with the top cover removed, as this could create a shock or fire hazard.  
Do not block the air vents on the sides or the top of the unit.  
Do not operate the equipment in the presence of flammable gasses or fumes. Operating electrical equipment  
in such an environment constitutes a definite safety hazard.  
(Revised 2010-11-15)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
ELECTRICAL SAFETY  
WARNING: Do not disconnect while circuit is live, unless area is known to be non-hazardous.  
WARNING: Disconnect the power cable before removing the enclosure top.  
WARNING: Do not operate the unit with the top cover removed.  
WARNING: Properly ground the unit before connecting anything else to the unit. Units not properly  
grounded may result in a safety risk and could be hazardous and may void the warranty. See the  
grounding technique section of this user manual for proper ways to ground the unit.  
WARNING: Do not work on equipment or cables during periods of lightning activity.  
WARNING: Do not perform any services on the unit unless qualified to do so.  
WARNING: Do not block the air vents.  
WARNING: Observe proper DC Voltage polarity when installing power input cables. Reversing  
voltage polarity can cause permanent damage to the unit and void the warranty.  
Power must be supplied by an isolating source, and a 0.5 A max rated UL recognized fuse must be  
installed immediately before the unit  
LASER SAFETY (405FXE Only)  
CAUTION: CLASS 1 LASER PRODUCT. Do not stare into the laser!)  
(Revised 2010-11-15)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
405FX, 405FXE, & 405TX Industrial Ethernet Switches  
The 405TX and 405FX Unmanaged Industrial Ethernet Switches support high speed layer 2 switching  
between ports.  
The 405TX is an affordable 5 port unmanaged switch that is capable of auto negotiating 10/100 Mb and  
half/full duplex communications. The N-TRON 405TX is housed in a ruggedized steel enclosure, and  
provides 5 Category 5 compliant 10/100-BaseT connections for high performance network design, and  
hub/repeater upgrades.  
The 405FX is a 5 port unmanaged switch that has 4 ports identical to the 405TX, plus an additional  
multimode fiber optic up-link port, capable of 2 Kilometers of 100 Mb communications without the use of  
repeaters.  
The 405FXE is a 5 port unmanaged switch that is similar to the 405FX, but with extended range. The N-  
TRON 405FXE utilizes a singlemode fiber transceiver that is capable of 15 Kilometers of 100 Mb  
communications.  
Both the 405FX and 405FXE utilize the IEEE compliant SC or ST duplex connector for fiber optic  
communications. The 4 10/100Base-TX ports utilize the RJ45 shielded connector.  
All N-TRON switches come housed in a steel ruggedized Din-Rail enclosure, designed to withstand the  
most demanding industrial applications, and have been fully tested and certified at industrial environmental  
extremes. All 405 Units operate on 10-30VDC @ 0.2A.  
Key Features  
Full IEEE 802.3 & 100BASE-FX Compliance  
Extended Environmental Specifications  
Support for Full/Half Duplex Operation  
LED Link/Activity Status Indication  
Auto Sensing Speed and Flow Control  
Up to 1.0 Gb/s Maximum Throughput  
Industry Standard DIN-Rail Enclosure  
(Revised 2010-11-15)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE CONTENTS  
Please make sure the Ethernet Switch package contains the following items:  
1. 405FX/405FXE/405TX Ethernet Switch  
2. This Installation Guide  
Contact your carrier if any items are damaged.  
INSTALLATION  
Read the following warning before beginning the installation:  
WARNING  
The 405FXE unit contains a Class 1 Laser. Do not stare into the laser beam (fiber optic connector)  
when installing or operating the product.  
Never install or work on electrical equipment or cabling during periods of lightning activity.  
Disconnect the power cable before removing the enclosure top.  
Do not operate the unit with the top cover removed  
UNPACKING  
Remove all the equipment from the packaging, and store the packaging in a safe place.  
File any damage claims with the carrier.  
(Revised 2010-11-15)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
405FX/405FXE HALF DUPLEX SETUP  
While all RJ45 ports are Autosensing, the 405FX/405FXE Fiber Optic Port is factory configured for full  
duplex operation. In the event half duplex operation is desired, follow these steps:  
1. Remove the Voltage Input Power Plugs.  
2. Remove the top cover (8 screws).  
3. Remove the jumper plug (JP1) from pins 1 and 2.  
4. Replace the top cover.  
5. Proceed with the installation.  
Full Duplex = Pins 1 and 2 shorted.  
Half Duplex = Remove jumper.  
In order to verify the jumper settings have been set correctly, for units which have the N-View option turned  
on, you should install N-ViewOPC Server software on a PC connected to the LAN. The software is freely  
distributed on the ProductCD and our web site ( http://www.n-tron.com/html/opc.html ). Once N-ViewOPC is  
installed, you should view the Ports Counter page to remotely monitor each connected port. You may find it  
helpful to Copy [Alt]+[PrintScreen] the Port Counter information for each port and Paste [Control]+[V] into a  
Windows document for further review. Please consult your N-View OPC Server Manual for additional  
information.  
(Revised 2010-11-15)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIN-Rail Mounting  
Install the unit in a standard DIN-Rail. Recess the unit to allow at least 5” of horizontal clearance for fiber optic  
cable bend radius (2” for TX models). Note: This unit may be mounted horizontally or vertically.  
To install the unit to 35 mm industrial DIN-Rail - Place the top edge of the included mounting bracket on  
the back of the unit against the top flange of the DIN-Rail at a 15° angle. Rotate the bottom of the unit to the  
back (away from you) until it snaps into place.  
To remove the unit from the 35 mm industrial DIN-Rail - Apply downward force to the unit until it  
disengages from the bottom of the unit from the DIN-Rail. Then, rotate the unit approximately 15° upward  
and towards you to completely remove the unit.  
Optional Mounting  
With the exception of the 524TX and 526FX2, all N-Tron™ products are designed to be mounted on  
industry standard 35mm DIN-Rail. However, DIN-Rail mounting may not be suitable for all applications.  
We offer two alternative mounting solutions.  
Our 900 Panel Mount Assembly (P/N: 900-PM) may be used to securely mount our 100, 200, 300, 400,  
500, or 900 Series products to a panel or other flat surface.  
Our Universal Rack Mount Kit (P/N: URMK) may be used to mount our products to standard 19" racks.  
(Revised 2010-11-15)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
FRONT PANEL  
From Left to Right:  
LNK  
Link LED for Fiber Optic Port (405FX/FXE only)  
TX  
RX  
ACT  
X
RJ45 Ports  
!
Fiber Optic Transmit Port (405FX/FXE Only)  
Fiber Optic Receive Port (405FX/FXE Only)  
Activity LED for Fiber Optic Port (405FX/FXE only)  
RJ45 Crossover Uplink Port (405TX Only)  
Auto sensing 10/100BaseT Connections  
Red LED indicates controller error  
Green LED lights when Power is connected  
NOTE: Each RJ45 data port has two LED’s located at the top of each connector. The left LED  
indicates LINK status, and the right LED indicates ACTIVITY.  
(Revised 2010-11-15)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
LED’s: The table below describes the operating modes:  
LED  
Color  
Description  
GREEN Power is Applied  
OFF  
RED  
OFF  
Power is OFF  
Controller HW Error  
!
No Errors. Normal  
Operation.  
GREEN Link between ports  
established  
LNK  
OFF  
No Link between ports  
GREEN Data is active between  
ports  
ACT  
OFF  
Data is inactive between  
ports  
APPLYING POWER (Side View)  
Unscrew & Remove the DC Voltage Input Plug(s) from the side header  
Install the DC Power Cables into the Plug(s) (observing polarity).  
Plug the Voltage Input Plug(s) back into the side header.  
Tightening torque for the terminal block power plug is 0.22 Nm/0.162 Pound Foot.  
All LED’s will flash ON Momentarily (including the Error LED)  
Verify the Power LED stays ON (GREEN).  
Verify the Error LED is OFF (after a few seconds).  
Note: Only 1 plug is required to be connected to power input for minimal operation. For redundant  
power operation, V1 and V2 plugs must be connected to separate DC Voltage sources. Use wire sizes  
16-28 gauge.  
Recommended 24V DC Power Supplies, similar to  
100VAC/240VAC:  
N-Tron’s NTPS-24-1.3, DC 24V/1.3A  
(Revised 2010-11-15)  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
N-TRON SWITCH GROUNDING TECHNIQUES  
The grounding philosophy of any control system is an integral part of the design. N-Tron switches are designed  
to be grounded, but the user has been given the flexibility to float the switch when required. The best noise  
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via  
a drain wire. Some N-Tron switches have metal din-rail brackets that can ground the switch if the din-rail is  
grounded. In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if  
isolation is required.  
Both V- legs of the power input connector are connected to  
chassis internally on the PCB. Connecting a drain wire to  
earth ground from one of the V- terminal plugs as shown here  
will ground the switch and the chassis. The power leads from  
the power source should be limited to 3 meters or less in  
length.  
As an alternate, users can run a drain wire & lug from any of the Din-Rail  
screws or empty PEM nuts on the enclosure. When using an unused PEM  
nut to connect a ground lug via a machine screw, care should be taken to  
limit the penetration of the outer skin by less than 1/4 in. Failure to do so  
may cause irreversible damage to the internal components of the switch.  
Note: Before applying power to the grounded switch, you must use a volt  
meter to verify there is no voltage difference between the power supply’s  
negative output terminal and the switch chassis grounding point.  
If the use of shielded cables is required, it is generally recommended to only connect the shield at one end to  
prevent ground loops and interfere with low level signals (i.e. thermocouples, RTD, etc.). Cat5e cables  
manufactured to EIA-568A or 568B specifications are required for use with N-Tron Switches.  
In the event all Cat5e patch cable distances are small (i.e. All Ethernet devices are located the same local  
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to  
chassis ground at both ends in systems void of low level analog signals.  
(Revised 2010-11-15)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RJ45 CONNECTOR CRIMP SPECIFICATIONS  
Please reference the illustration below for your Cat5 cable specifications:  
(Revised 2010-11-15)  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECTING THE UNIT  
For 405FX & 405FXE units, remove the dust cap from the fiber optic connectors and connect the fiber  
optic cables. The TX port on the 405FX should be connected to the RX port of the far end station. The  
RX port on the 405FX should be connected to the TX port of the far end station.  
For 10/100 Base-TX ports, plug a Category 5 twisted pair cable into the RJ45 connector. Connect the  
other end to the far end station. Verify that the LNK LED’s are ON once the connection has been  
completed. For Switch to Switch or Switch to Repeater connections, use the X-port and a standard  
Category 5 cable. To connect any other port (other than the X-Port) to another Switch or Repeater, use a  
standard Category 5 crossover cable.  
Warning: Creating a port to port connection on the same switch (i.e. loop) is an illegal operation and  
will create a broadcast storm which will crash the network!  
TROUBLESHOOTING  
1. Make sure the (Power LED) is ON.  
2. Make sure the ! (Error LED) remains OFF 3 seconds after initial power up.  
3. Verify that Link LED’s are ON for connected ports.  
4. Verify straight through cabling used between stations.  
5. Verify crossover cabling used between switches or repeaters (non X-Port only).  
6. Verify that cabling is Category 5 for 100Mbit Operation.  
7. Verify TX is connected to far end RX and vise versa (405FX/FXE only).  
SUPPORT  
Contact N-TRON Corp. at:  
TEL: 251-342-2164  
FAX: 251-342-6353  
FCC STATEMENT  
This product complies with Part 15 of the FCC-A Rules.  
Operation is subject to the following conditions:  
(1) This device may not cause harmful Interference  
(2) This device must accept any interference received, including interference that may cause undesired  
operation.  
(Revised 2010-11-15)  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
KEY SPECIFICATIONS  
Physical  
Height:  
Width:  
Depth:  
Weight:  
2.13" (5.41 cm)  
5.00" (12.70 cm)  
3.00" (7.62 cm)  
~ 1.2 lbs. (0.6 kg)  
(Note: can be mounted horizontally or vertically)  
Electrical  
Input Voltage:  
Input Current:  
Inrush Current:  
Input Ripple:  
10-30 VDC (Regulated)  
220mA max. @ 24VDC (Steady State)  
14.0Amp/0.9ms max. @ 24VDC  
Less than 100 mV  
Input Wire Size:  
16-28 AWG  
Environmental  
Operating Temperature:  
Storage Temperature:  
Operating Humidity:  
Operating Altitude:  
-20°C to 70°C  
-40°C to 85°C  
10% to 90% (Non Condensing)  
0 to 10,000 ft.  
Network Media  
10BaseT:  
100BaseT:  
100BaseFX:  
> Cat-3 Cable  
> Cat-5 Cable  
Multimode: 50-62.5/125µm Fiber  
Singlemode: 7-10/125µm Fiber  
Fiber Transceiver Characteristics  
Fiber Length:  
2km*  
15km**  
-15dBm  
40km**  
-5dBm  
80km**  
-5dBm  
TX Power Min  
-19dBm  
RX Sensitivity Max:  
Wavelength:  
-31dBm  
1310nm  
-31dBm  
1310nm  
-34dBm  
1310nm  
-34dBm  
1550nm  
*=Multimode ** =Singlemode  
Connectors  
10/100BaseT:  
5 (five) RJ45 UTP Ports  
4 (four) RJ45 UTP Ports  
SC or ST Duplex Port (405FX/FXE)  
(405TX)  
(405FX/FXE)  
100BaseFX:  
Recommended Minimum Wiring Clearance:  
Front:  
2" (5.08 cm)  
4” (10.16 cm)  
1" (2.54 cm)  
(405TX)  
(405FX/FXE)  
Side:  
(Revised 2010-11-15)  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Regulatory Approvals:  
Safety: Suitable for use in Class I, Division 2, Groups A, B, C, and D Hazardous Locations, or Non-hazardous  
locations only.  
EMI: EN55022 Class A  
FCC Part 15 Class A  
EMS: EN55024:1998  
EN61000-4-2:1995  
EN61000-4-3:1997  
EN61000-4-4:1995  
EN61000-4-5:1995  
EN61000-4-6:1996  
GOST-R Certified.  
Warranty: Effective January 1, 2008, all N-TRON products carry a 3 year limited warranty from the date of  
purchase.  
(Revised 2010-11-15)  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
N-TRON Limited Warranty  
N-TRON, Corp. warrants to the end user that this hardware product will be free from defects in workmanship and materials,  
under normal use and service, for the applicable warranty period from the date of purchase from N-TRON or its authorized  
reseller. If a product does not operate as warranted during the applicable warranty period, N-TRON shall, at its option and  
expense, repair the defective product or part, deliver to customer an equivalent product or part to replace the defective item, or  
refund to customer the purchase price paid for the defective product. All products that are replaced will become the property of  
N-TRON. Replacement products may be new or reconditioned. Any replaced or repaired product or part has a ninety (90) day  
warranty or the remainder of the initial warranty period, whichever is longer. N-TRON shall not be responsible for any custom  
software or firmware, configuration information, or memory data of customer contained in, stored on, or integrated with any  
products returned to N-TRON pursuant to any warranty.  
OBTAINING WARRANTY SERVICE: Customer must contact N-TRON within the applicable warranty period to obtain  
warranty service authorization. Dated proof of purchase from N-TRON or its authorized reseller may be required. Products  
returned to N-TRON must be pre-authorized by N-TRON with a Return Material Authorization (RMA) number marked on the  
outside of the package, and sent prepaid and packaged appropriately for safe shipment. Responsibility for loss or damage does not  
transfer to N-TRON until the returned item is received by N-TRON. The repaired or replaced item will be shipped to the  
customer, at N-TRON’s expense, not later than thirty (30) days after N-TRON receives the product. N-TRON shall not be  
responsible for any software, firmware, information, or memory data of customer contained in, stored on, or integrated with any  
products returned to N-TRON for repair, whether under warranty or not.  
ADVANCE REPLACEMENT OPTION: Upon registration, this product qualifies for advance replacement. A replacement  
product will be shipped within three (3) days after verification by N-TRON that the product is considered defective. The  
shipment of advance replacement products is subject to local legal requirements and may not be available in all locations. When  
an advance replacement is provided and customer fails to return the original product to N-TRON within fifteen (15) days after  
shipment of the replacement, N-TRON will charge customer for the replacement product, at list price.  
WARRANTIES EXCLUSIVE: IF AN N-TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE,  
CUSTOMER'S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR, REPLACEMENT, OR  
REFUND OF THE PURCHASE PRICE PAID, AT N-TRON'S OPTION. TO THE FULL EXTENT ALLOWED BY LAW, THE  
FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER WARRANTIES,  
TERMS, OR CONDITIONS, EXPRESS OR IMPLIED, EITHER IN FACT OR BY OPERATION OF LAW, STATUTORY OR  
OTHERWISE, INCLUDING WARRANTIES, TERMS, OR CONDITIONS OF MERCHANTABILITY, FITNESS FOR A  
PARTICULAR PURPOSE, SATISFACTORY QUALITY, CORRESPONDENCE WITH DESCRIPTION, AND NON-  
INFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED. N-TRON NEITHER ASSUMES NOR AUTHORIZES  
ANY OTHER PERSON TO ASSUME FOR IT ANY OTHER LIABILITY IN CONNECTION WITH THE SALE,  
INSTALLATION, MAINTENANCE OR USE OF ITS PRODUCTS. N-TRON SHALL NOT BE LIABLE UNDER THIS  
WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT OR MALFUNCTION  
IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY CUSTOMER'S OR ANY THIRD PERSON'S MISUSE,  
NEGLECT, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO OPEN, REPAIR OR MODIFY  
THE PRODUCT, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE,  
LIGHTNING, POWER CUTS OR OUTAGES, OTHER HAZARDS, OR ACTS OF GOD.  
LIMITATION OF LIABILITY: TO THE FULL EXTENT ALLOWED BY LAW, N-TRON ALSO EXCLUDES FOR ITSELF  
AND ITS SUPPLIERS ANY LIABILITY, WHETHER BASED IN CONTRACT OR TORT (INCLUDING NEGLIGENCE),  
FOR INCIDENTAL, CONSEQUENTIAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES OF ANY KIND, OR FOR  
LOSS OF REVENUE OR PROFITS, LOSS OF BUSINESS, LOSS OF INFORMATION OR DATA, OR OTHER FINANCIAL  
LOSS ARISING OUT OF OR IN CONNECTION WITH THE SALE, INSTALLATION, MAINTENANCE, USE,  
PERFORMANCE, FAILURE, OR INTERRUPTION OF ITS PRODUCTS, EVEN IF N-TRON OR ITS AUTHORIZED  
RESELLER HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES, AND LIMITS ITS LIABILITY TO  
REPAIR, REPLACEMENT, OR REFUND OF THE PURCHASE PRICE PAID, AT N-TRON'S OPTION. THIS DISCLAIMER  
OF LIABILITY FOR DAMAGES WILL NOT BE AFFECTED IF ANY REMEDY PROVIDED HEREIN SHALL FAIL OF  
ITS ESSENTIAL PURPOSE.  
DISCLAIMER: Some countries, states, or provinces do not allow the exclusion or limitation of implied warranties or the  
limitation of incidental or consequential damages for certain products supplied to consumers, or the limitation of liability for  
personal injury, so the above limitations and exclusions may be limited in their application to you. When the implied warranties  
are not allowed to be excluded in their entirety, they will be limited to the duration of the applicable written warranty. This  
warranty gives you specific legal rights which may vary depending on local law.  
GOVERNING LAW: This Limited Warranty shall be governed by the laws of the State of Delaware, U.S.A.  
(Revised 2010-11-15)  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Milwaukee Cordless Saw 2445 20 User Manual
MSi Laptop GP62LEOPO042 User Manual
MTD Chipper 243 645C000 User Manual
Multi Tech Systems Fax Machine MVP 800 User Manual
NETGEAR Marine GPS System GS116Ev2 User Manual
Nortel Networks Telephone CallPilot 100 User Manual
Olympus Microcassette Recorder DP 10 User Manual
Omega Engineering Thermometer OS PP User Manual
Oster Toaster TSSTTRWF2S User Manual
Panasonic Printer KX P7100 User Manual