ys6307
revision A, 21st October 2004
catalogue section 40
BC1524 and BC3012
Automatic Battery Chargers
Heavy duty float charging:
ꢀ
15A (24V) or 30A (12V) output
Simple, low cost design
Lead acid or Ni-Cd calibrations
Float or boost modes
ꢀ
ꢀ
ꢀ
ꢀ
Charge fail relay output
Description
Product specification
The BC1524 and BC3012 range provides fully automatic,
heavy duty charging of vented lead acid or NiCd batteries.
The chargers may be used in a wide range of industrial
battery applications, including standby engines, pumps
and generators.
power supply:
BC1524
BC3012
nominal operating voltages
permissible voltage variation
nominal operating frequency
230 VAC or 110 VAC (specify)
± 10% of nominal
50/60 Hz.
DC charge output:
The charger uses an open frame construction, designed
for surface mounting in an enclosed panel. Each unit
consists of a transformer, rectifier and control circuit.
The control circuit ensures that charger maintains the
battery voltage at the pre-calibrated float level, while
supplying any additional load current up to the specified
maximum.
maximum current, A DC
nominal voltage, V DC
float/boost voltages
15
24
30
12
see table overleaf
charge fail output:
relay type
volt free SPDT contacts, relay
de-energised on fault
A ‘boost’ operating mode can be used to provide increased
voltage output. Selection of normal or boost mode is via
three terminals, allowing activation by a remote panel
switch or time relay – see calibration table overleaf for
float and boost voltage levels.
contact rating
1A @ 30 VDC (resistive load)
general:
operating temperature
overall dimensions (w x h x d)
weight
–10 to +55 oC
185 x 175 x 135 mm
approx. 7.8 Kg
A self diagnostic ‘charge fail’ circuit and relay output is
provided as standard. The volt free relay de-energises
in the event of a charging fault.
Power for the charger is from a 230VAC or 110VAC
supply (please specify at order). All electrical connections
are to stripped panel wiring via spring-loaded clamp
terminals.
Warranty
A one year limited warranty on materials and workmanship
is given with this Murphy product. Details are available on
CONTROL SYSTEMS AND SERVICES DIVISION
PO Box 1819, Rosenberg, Texas 77471, USA
tel: +1 281 633 4500
FRANK W. MURPHY LTD.
Church Rd, Laverstock, Salisbury, SP1 1QZ, UK
tel: +44 1722 410055
MACQUARRIE CORPORATION
1620 Hume Highway,
Campbellfield, Victoria 3061, Australia
tel: +61 3 9358 5555
fax: +1 281 633 4588
fax: +44 1722 410088
email: sales@fwmurphy.com
email: sales@fwmurphy.co.uk
web: www.fwmurphy.co.uk
fax: +61 3 9358 5558
email: [email protected]
FW Murphy
PO Box 470248
Tulsa, Oklahoma 74147, USA
tel: +1 918 317 4100
fax: +1 918 317 4266
email: sales@fwmurphy.com
web: www.fwmurphy.com
MURPHY DE MEXICO S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje MURPHY SWITCH OF CALIFORNIA
San Luis Potosí, S.L.P. México 78384
tel: +52 444 8206264
fax: +52 444 8206336
Villahermosa office tel: +52 993 3162117
web: www.murphymex.com.mx
41343 12th Street West,
Palmdale, CA 93551-1442, USA
tel: +1 661 272 4700
fax: +1 661 947 7570
email: sales@murphyswitch.com
web: www.murphyswitch.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Download from Www.Somanuals.com. All Manuals Search And Download.
|