Lochinvar Water Heater CW 645 User Manual

DESIGNER’S GUIDE COPPER-FIN® WATER HEATER  
4 9 5 , 0 0 0 – 2 , 0 6 5 , 0 0 0 B t u / h r  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Codes . . . . . . . . . . . . . . . . . . . . . . . . .2  
TABLE A. Clearances From  
Combustible . . . . . . . . . . . . .3  
Combustion & Ventilation Air . . . . . . . . .5  
Contaminants . . . . . . . . . . . . . . . . . . . .6  
Determining Total “Free Area” . . . . . . . .5  
Electrical Requirements . . . . . . . . . . . .14  
Gas Supply . . . . . . . . . . . . . . . . . . . .10  
General Venting . . . . . . . . . . . . . . . . . .6  
Location of Unit . . . . . . . . . . . . . . . . . .2  
Low Water Temperature Delivery . . . . .12  
Outdoor Use . . . . . . . . . . . . . . . . . . . .3  
Outdoor Installation . . . . . . . . . . . . . . .9  
Pump Operation . . . . . . . . . . . . . . . . .12  
Relief Valve . . . . . . . . . . . . . . . . . . . .14  
Venting Options . . . . . . . . . . . . . . . . . .8  
Water Connections . . . . . . . . . . . . . . .11  
Water Treatment . . . . . . . . . . . . . . . . .13  
Water Velocity Control . . . . . . . . . . . .12  
TABLE B. Flue Sizes . . . . . . . . . . . . . . . .8  
TABLE C. Outdoor Kits . . . . . . . . . . . .10  
TABLE D. Gas Supply Pipe Sizing . . . .11  
TABLE E. Inlet Gas Pressure . . . . . . . . .11  
TABLE F. Required Temperature Rise . . .12  
TABLE G. Required Pump Performance .13  
TABLE H. Common Water  
Manifold Sizes . . . . . . . . . . .14  
TABLE I. Amp Draw . . . . . . . . . . . . . .14  
Appendix A -  
Water Heater Piping Diagrams  
Single Heater – Single Tank . . . . . . . . .A1  
Single Heater – Two Tanks . . . . . . . . .A2  
Two Temperature Installation  
Figures & Tables Index  
Single Heater – Single Tank . . . . . . . . .A3  
Two Heaters – Single Tank . . . . . . . . .A4  
Two Heaters – Two Tanks . . . . . . . . . .A5  
Multi-Stack Frame  
FIG. 1  
Models CW 495-2066  
Requirements For Installation  
Over Combustible Floor . . . . .3  
FIG. 2  
Water Heater Equipment  
& Control Orientation . . . . . . .4  
Two Heaters – Single Tank . . . . . . . . .A6  
FIG. 3-6 Combustion &  
Ventilation Air . . . . . . . . . . .5,6  
FIG. 7  
Barometric Damper  
Installation . . . . . . . . . . . . . . .8  
FIG. 8  
Multiple Unit Barometric  
Damper Installation . . . . . . . .9  
FIG. 9 Outdoor Venting . . . . . . . . . . .9  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
CODES  
In designing  
The equipment shall be installed in  
accordance with those installation  
regulations in effect in the local area where  
the installation is to be made. These shall  
be carefully followed in all cases. Authorities  
having jurisdiction shall be consulted before  
installations are made.  
a water heater system,  
pay special attention to:  
o Water Velocity  
(See page 12 for Required Degree  
Rise chart.)  
In the absence of such requirements, the  
installation shall conform to the latest edition of  
the National Fuel Gas Code, ANSI Z223.1.  
Where required by the authority having  
jurisdiction, the installation must conform to  
American Society of Mechanical Engineers  
Safety Code for Controls and Safety Devices  
for Automatically Fired Boilers, ASME CSD-1.  
Where required by the authority having  
jurisdiction, the installation must comply with  
the Canadian Association Code, CAN/CGA-  
B149.1 and/or B149.2 and/or local codes.  
o Factory Supplied Pump  
Capacity  
(See page 12 for Pump Operation.)  
o Manifold Pipe Size  
When using more than one heater  
(See page 14 for Common Water  
Manifold Size for Multiple Water  
Heater Installation Table.)  
o Storage Tank Circulating  
Tappings  
(See page 14 for Manifold Pipe  
LOCATION OF UNIT  
Size.)  
Locate the unit so that if water connections  
should leak, water damage will not occur.  
When such locations cannot be avoided, it  
is recommended that a suitable drain pan,  
adequately drained, be installed under the  
unit. The pan must not restrict combustion  
air flow.  
1.  
o Placement of Cold Water  
Inlet and Building Return  
(See Appendix A for Water Heater  
Piping Diagrams.)  
Under no circumstances is the  
manufacturer to be held responsible  
for water damage in connection  
with this unit or any of its  
components.  
o Water Hardness  
See page 13 for Water Treatment  
(
Information.)  
2
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.  
The indoor units must be installed so that  
the ignition system components are  
protected from water (dripping, spraying,  
rain, etc.) during appliance operation and  
service (circulator replacement, control  
replacement, etc.).  
This procedure should also be  
followed if electrical conduit or  
radiant heat distribution piping  
runs through the floor and  
beneath the appliance.  
• Ensure that combustible floor base  
meets local fire code requirements.  
3.  
4.  
The appliance must be installed  
on a level, non-combustible floor.  
Concrete over wood is not considered a  
non-combustible floor. Maintain required  
clearances from combustible surfaces.  
5.  
Outdoor models require the installation of  
an optional vent cap. Instructions for  
placement of the vent cap are included in  
the venting section.  
For installation on a combustible  
floor only when installed on  
special base: Units installed over a  
combustible floor must use the Special  
Combustible Floor Base. The unit must be  
centered on the base as shown in FIG. 1.  
Outdoor models must not be installed  
directly on the ground. The outdoor unit  
must be installed on a concrete brick,  
block or other non-combustible pad.  
(TABLE A) – CLEARANCES FROM  
COMBUSTIBLE CONSTRUCTION  
CLEARANCES  
Right Side  
Rear  
CW495-2066  
• Provide a base of hollow clay tile or  
concrete blocks from 8to 12thick  
and extending 24beyond the sides.  
3"  
3"  
Left Side  
3"  
(24" for Service)  
ALCOVE*  
(30" for Service)  
3"  
Front  
Top  
Flue  
• The blocks must be placed in line so that  
the holes line up horizontally to provide a  
clear passage through the blocks.  
1"**  
* Alcove is a closet without a door.  
** Consult local codes and/or vent  
material manufacturer.  
SPECIAL LOCATION: OUTDOOR USE  
Outdoor models have additional location  
and clearance requirements. These  
requirements must be adhered to carefully,  
since wind, rain, snow and cold cannot be  
controlled in outdoor applications. See  
Outdoor Installation, on page 9.  
(FIG. 1) 495-2066 REQUIREMENTS FOR  
INSTALLATION OVER COMBUSTIBLE FLOOR  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
RIGHT SIDE  
INLET GAS  
FLUE PRODUCTS VENT  
CONNECTION  
OPERATOR  
FRESH AIR  
ON/OFF SWITCH  
INLET  
TERMINAL  
STRIP  
HOT WATER  
OUTLET  
120V ELECTRICAL  
CONNECTION  
RELIEF VALVE  
TAPPING  
BACK  
COLD WATER  
INLET  
FRONT  
DRAIN  
CW495-745  
BURNER INSPECTION PORT  
LEFT SIDE  
FLUE PRODUCTS VENT  
RIGHT SIDE  
OPERATOR  
GAS  
ON/OFF SWITCH  
AIR  
CONNECTION  
INLET  
TERMINAL STRIP  
HOT WATER  
OUTLET  
FRONT  
BACK  
COLD WATER  
LEFT SIDE  
INLET  
BURNER  
DRAIN  
CW986-2066  
INSPECTION PORT  
(FIG. 2) WATER HEATER EQUIPMENT AND CONTROL ORIENTATION.  
4
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This opening must be located within 12”  
(30 cm) of the bottom of the enclosure.  
EXAMPLE OF  
COMBUSTION & VENTILATION AIR  
Provisions for combustion and ventilation air  
must be in accordance with Section 5.3,  
Air for Combustion and Ventilation, of the  
latest edition of the National Fuel Gas  
Code, ANSI Z223.1; in Canada, the latest  
edition of CGA Standard B149 Installation  
Code for Gas Burning Appliances and  
Equipment; or applicable provisions of the  
local building codes.  
SIZING FOR  
COMBUSTION  
& VENTILATION  
AIR OPENINGS  
(WATER HEATER  
WITH 2,065,000  
Btu/hr INPUT):  
B. Ventilation air opening with a minimum  
free area of one square inch per 4000  
2
Btu input (5.5 cm per kW). This opening  
must be located within 12(30 cm) of the  
top of the enclosure.  
When combustion and  
ventilated air is taken  
from directly outside the  
building (FIG. 4), divide  
the total BTU’s by 4,000.  
This yields 516.25 sq.in.  
of “Free Area” without  
restriction.  
The equipment room must be provided with  
properly sized openings to assure adequate  
combustion air and proper ventilation when  
the unit is installed with conventional venting  
or sidewall venting.  
(2,065,000 ÷ 4000 =  
516.25 sq.in.)  
(FIG. 4) COMBUSTION AIR THROUGH DUCTWORK  
Since the air opening is  
50% closed due to  
screens and louvers, the  
total opening must be  
multiplied by 2.  
2.  
If combustion and ventilation air is  
taken from the outdoors using a  
duct to deliver the air to the  
CAUTION: Under no circumstances should  
the equipment room be under a negative  
pressure when atmospheric combustion  
equipment is installed in the room.  
mechanical room, each of the two  
openings should be sized based on a  
minimum free area of one square inch  
(516.25 sq. in. x 2 =  
1,032 sq.in.)  
This project requires one  
Ventilation Air Opening  
with net “Area” of  
1,032 square inches with  
louver dimensions of 30  
x 35and one  
2
per 2000 Btu input (11 cm per kW).  
Combustion Air Opening  
with net “Area” of  
1,032 square inches with  
louver dimensions  
(FIG. 3) COMBUSTION AIR DIRECT FROM OUTSIDE  
1.  
If air is taken directly from outside  
the building with no duct, provide two  
permanent openings:  
(FIG. 5) COMBUSTION AIR FROM AN  
INTERIOR SPACE  
of 30x 35.  
3.  
If air is taken from another interior  
space, each of the two openings  
specified above should have a net free  
area of one square inch for each 1000  
A. Combustion air opening with a  
minimum free area of one square inch per  
2
4000 Btu input (5.5 cm per kW).  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
2
Btu (22 cm per kW) of input, but not less  
than 100 square inches (645 cm ).  
VENTING  
General  
2
Copper-Fin II Water Heaters are classified as  
Category I appliances when tested to the  
latest ANSI Standard. This classification  
requires all conventionally vented  
combustion products to be vented using  
Category I listed vent pipe.  
(FIG. 6) COMBUSTION AIR FROM OUTSIDE,  
SINGLE OPENING  
Additionally, it is recommended that this vent  
material be double wall construction or  
insulated in the field. A Category I  
appliance operates with a non-positive static  
vent pressure and with flue loss greater than  
17 percent.  
4. If a single combustion air opening  
is provided to bring combustion  
air in directly from the outdoors,  
the opening must be sized based on a  
minimum free area of one square inch  
2
per 3000 Btu input (7 cm per kW). This  
Vent installations for connection to gas vents  
or chimneys must be in accordance with  
Part 7, “Venting of Equipment,” of the latest  
edition of the National Fuel Gas Code, ANSI  
Z223.1, or applicable provisions of the local  
building codes.  
opening must be located within 12”  
(30 cm) of the top of the enclosure.  
CAUTION!  
EXHAUST FANS:  
Any fan or equipment  
which exhausts air  
from the equipment  
room may deplete the  
combustion air supply  
and/or cause a down  
draft in the venting  
system. If a fan is used  
to supply combustion  
air to the equipment  
room, it must by sized  
such to make sure that  
it does not cause drafts  
which could lead to  
nuisance operational  
problems with the  
CONTAMINANTS  
Combustion air drawn from an interior  
or exterior space must be free of any  
chemical fumes which could be corrosive to  
the water heater.  
The connection from the appliance vent  
to the stack must be as direct as possible  
and sized correctly. The horizontal breeching  
of a vent must have at least 1/4rise per  
linear foot. The horizontal portions should  
also be supported for the design and weight  
of the material employed to maintain  
clearances, prevent physical damage and  
separation of joints.  
Burning chemical fumes results in the  
formation of corrosive acids which attack the  
water heater, cause improper combustion  
and premature failure of the water heater  
and vent.  
These fumes are often present in areas  
where refrigerants, salts, and solvents are  
used. Therefore, be aware of swimming  
pool equipment, water softening, and  
cooling system placement.  
The connection from the appliance vent  
to the stack or vent termination outside the  
building must be made with listed  
water heater.  
6
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Category I double wall vent (or equivalent)  
connectors and sized according to vent  
sizing tables (FAN column) in the latest  
edition of the National Fuel Gas Code.  
Vent Terminations  
The vent terminal should be vertical and  
exhaust outside the building at least 2 feet  
(0.6 m) above the highest point of the roof  
when within a 10 foot (3.05 m) radius.  
The Category I vent and accessories, such as  
firestop spacers, thimbles, caps, etc., must  
be installed in accordance with the vent  
manufacturer’s listing. The vent connector and  
firestop must provide correct spacing to  
combustible surfaces and seal to the vent  
connector on the upper and lower sides of  
each floor or ceiling through which the vent  
connector passes.  
Additionally, vertical terminations must be a  
minimum of 3 feet (0.9 m) above the roof  
line, and when less than 10 feet (3.05 m)  
from a parapet wall must be a minimum of  
2 feet (0.61 m) higher than the parapet wall.  
Vent caps should have a minimum clearance  
of 4 feet (1.2 m) horizontally from, and in no  
case above or below [unless a 4 feet (1.2 m)  
horizontal distance is maintained], electric  
meters, gas meters, regulators and relief  
equipment.  
Any improper operation of the common  
venting system in an existing building should  
be corrected when new equipment is  
installed, so the installation conforms to the  
latest edition of the National Fuel Gas Code,  
ANSI Z223.1.  
Maintain a distance of at least 3 feet  
(0.9 m) above any forced air inlet within  
10 feet (3.05 m) and a distance of at  
least 4 feet (1.2 m) below, 4 feet (1.2 m)  
horizontally from, or 1 foot (30 cm) above  
any door, window or gravity air inlet.  
When resizing any portion of the common  
venting system, it should be resized to  
approach the minimum size as determined  
using the appropriate tables in the National  
Fuel Gas Code.  
Do not terminate the vent in a window well,  
stairwell, alcove, courtyard or other recessed  
area. The vent can not terminate  
below grade. The bottom of the vent  
terminal shall be located at least 12 inches  
(30 cm) above grade and clear of snow,  
ice, leaves or other debris.  
The weight of the venting system must not  
rest on the water heater. The venting system  
must be adequately supported in  
compliance with local codes and other  
applicable codes.  
The distance of the vent terminal from  
adjacent public walkways, adjacent  
buildings, windows, and building openings  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
must be consistent with the National Fuel  
The minimum flue pipe diameters for  
Copper-Fin models, utilizing negative draft  
venting are as follows:  
NOTE:  
Gas Code Z223.1 or in Canada, the latest  
edition of CGA Standard B149 Installation  
Code for Gas Burning Appliances and  
Equipment.  
A vent system should  
never be sized based  
only on the vent  
(TABLE B)  
FLUE SIZES AND COMBUSTION AIR PIPE SIZES  
connection diameter of  
the appliance. For proper  
vent design and sizing,  
please consult the  
MODEL  
FLUE SIZE  
NUMBER  
CW 495  
CW 645  
CW 745  
CW 986  
CW 1256  
CW 1436  
CW 1796  
CW 2066  
6"  
8"  
VENTING OPTIONS  
Conventional Venting  
8"  
A conventional venting system utilizes  
the natural buoyancy of the heated flue  
products to generate a negative draft. This  
draft forces flue products to rise vertically  
through a rooftop flue termination. The vent  
connection is made directly to the top of the  
unit and combustion air supplied from the  
mechanical room. Properly sizing vent  
material and the use of a barometric  
damper (when required) will lead to proper  
vent operation.  
National Fuel Gas Code  
(ANSI Z223.1).  
10"  
12"  
12"  
14"  
14"  
Size vent material using the “FAN” category  
of vent sizing tables in the latest edition of  
the National Fuel Gas Code. “FAN” applies  
to fan-assisted combustion appliances in  
Category I.  
Barometric Dampers  
A barometric damper is required when draft  
exceeds 0.08 inches of negative water  
column. When installed and adjusted  
properly, a barometric damper will maintain  
draft between 0.02 and 0.08 inches of  
negative water column ensuring proper  
operation.  
Multiple unit installations with combined  
venting also require barometric dampers to  
regulate draft at each unit. Again, the  
negative draft must be within the range of  
0.02 to 0.08 inches of negative water  
column to ensure proper operation.  
(FIG. 7) BAROMETRIC DAMPER INSTALLATION  
8
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
condensing of flue products, damage of the  
masonry flue/tile, insufficient draft and  
possible spillage of flue products into an  
occupied living space.  
NOTE:  
Common venting  
systems may be too  
large when an existing  
unit is removed. Be  
careful to resize any  
common venting system  
when new appliances  
are installed or existing  
appliances are replaced.  
Carefully inspect all chimney systems during  
the project design phase. If there is any doubt  
about the sizing or condition of a masonry  
chimney, it is prudent to reline the chimney  
with a properly sized and approved chimney  
liner system. Metallic liner systems (Type “B”  
doublewall or flexible or rigid metallic liners)  
are recommended. Consult with local code  
(FIG. 8) MULTIPLE UNIT BAROMETRIC  
DAMPER INSTALLATION  
For this type of installation, it is best to use a  
draft control for each water heater located  
on the riser between the vent outlet and the  
breeching - Location “A”. When this riser is  
too short to permit the installation of a draft  
control, locate a separate control for each  
water heater on the main breeching as  
illustrated in Location “B”. If, because of  
general crowding or other reasons, neither  
of these locations are possible, use a single  
large control in the breeching between the  
water heater nearest the chimney and the  
chimney, as shown in Location “C”.  
NOTE:  
Flue gases will form a  
officials to determine code requirements or the white plume in winter.  
Plume could obstruct  
window view. Flue gas  
condensate can freeze  
on exterior surfaces or  
on the vent cap. Flue  
gas condensate can  
cause discoloration of  
exterior building  
advisability of using or relining a masonry  
chimney.  
OUTDOOR INSTALLATION  
surfaces. Adjacent brick  
or masonry surfaces  
should be protected with  
a rust resistant sheet  
metal plate.  
All draft readings are made while unit is in  
stable operation (approximately 5 minutes  
running time).  
(FIG. 9) OUTDOOR VENTING  
Masonry Chimney  
Units are self venting and can be used  
outdoors when installed with the optional  
Outdoor Cap. This cap mounts directly to  
the top of the water heater and covers the  
flue outlet and combustion air inlet openings  
on the jacket. No additional vent piping is  
required. Maintain a minimum clearance of  
3(76mm) to combustible surfaces and a  
minimum of 3(76 mm) clearance to the air  
inlet.  
NOTE:  
A masonry chimney must be properly sized  
for the installation of a high efficiency gas  
fired appliance. Exterior masonry chimneys,  
with one or more sides exposed to cold  
outdoor temperatures, are more likely to  
have venting problems. The temperature of  
the flue products from a high efficiency  
appliance may not be able to sufficiently  
heat the masonry structure of the chimney to  
generate proper draft. This will result in  
Venting of a high  
efficiency appliance into  
a cold or oversized  
masonry chimney can  
result in operational and  
safety problems.  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
An outdoor unit should not be located so  
(TABLE C) - OUTDOOR VENT KIT PART NUMBERS  
that high winds can deflect off of adjacent  
walls, buildings or shrubbery causing  
recirculation. Recirculation of flue products  
may cause operational problems, bad  
combustion or damage to controls. The unit  
should be located at least 3 feet (0.91m)  
from any wall or vertical surface to prevent  
adverse wind conditions from affecting  
performance.  
MODEL  
NUMBER  
PART NUMBER  
ODK3023  
ODK3024  
ODK3024  
ODK3046  
ODK3047  
ODK3047  
ODK3048  
ODK3048  
CW 495  
CW 645  
CW 745  
CW 986  
CW 1256  
CW 1436  
CW 1796  
CW 2066  
Freeze Protection-  
Outdoor Installation  
Multiple unit outdoor installations require  
48(1.22 m) clearance between each vent  
cap. The outdoor cap must be located 4  
feet (1.22 m) below and 4 feet (1.22 m)  
horizontally from any window, door,  
walkway or gravity air intake.  
A snow screen should be installed to prevent  
snow and ice accumulation around the  
appliance or its venting system.  
If for any reason the unit is to be shut off:  
(a.) Shut off water supply.  
(b.) Drain unit completely.  
(c.) Drain pump and piping.  
The combustion air inlet of the outdoor cap  
must be located at least one foot (0.30 m)  
above grade and above normal snow  
levels. The water heater must be at least 10  
feet (3.05 m) away from any forced air inlet  
and at least 3 feet (0.91 m) outside any  
overhang.  
If freeze protection is not provided for the  
system, a low ambient temperature alarm or  
automatic drain system is recommended.  
GAS SUPPLY  
The gas pressure regulator supplied is for  
low pressure service. If upstream pressure  
exceeds 6 oz. (10.5" water column), an  
intermediate gas pressure regulator, of the  
lock up type, must be installed.  
1.  
Do not install in locations where rain from  
building runoff drains will spill onto the  
water heater.  
The gas line should be a separate line  
direct from meter, unless the existing  
gas line is of sufficient capacity. Verify  
pipe size with your gas supplier.  
2.  
3.  
Lochinvar must furnish an outdoor vent kit  
in accordance with CSA international  
requirements. Each kit includes the flue  
outlet/combustion air inlet, assembly, gasket  
and pump cover.  
A trap (drip leg) should be provided in the  
inlet gas connection to the water heater.  
10  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.  
5.  
A manual main gas shutoff valve is  
provided outside the jacket, upstream  
of the main gas valve.  
of air. Therefore, heat input rate should be  
reduced in an appliance above 2000 feet.  
Ratings should be reduced at the rate of 4  
percent for each 1000 feet above sea level.  
EXAMPLE OF  
HIGH ALTITUDE  
APPLICATIONS  
For example, if a unit’s  
input is 100,000 Btu/hr  
at sea level, the rated  
input at 4000 feet of  
elevation can be calculated  
by derating input 4% per  
1000 feet above sea  
level.  
In Canada, derated10% from 2,000 -  
4,500 ft., over 4,500 ft. derate must be  
in accordance with local authorities.  
Consult factory for installations at  
higher elevations.  
(TABLE E) – INLET GAS PRESSURE  
LP GAS  
MODELS  
NAT. GAS  
CW 495-745  
Minimum Allowable  
Maximum Allowable  
4  
8”  
10.5”  
13”  
High Altitude Applications  
CW 986-2066  
Atmospheric pressure decreases as the  
height above sea level increases. At any  
altitude above sea level, a cubic foot will  
contain less gas than a cubic foot at sea  
level. Thus, the heating value of a cubic foot  
of fuel gas will decrease as height above  
sea level increases.  
[Btu/hr Input]  
Minimum Allowable  
Maximum Allowable  
4.5”  
8”  
[1.00 - (Elevation/ 1000  
ft. x 0.04)] = Btu/hr  
Input at specified  
10.5”  
13”  
WATER CONNECTIONS  
Inlet and Outlet Water Connections  
For ease of service, install unions on inlet and  
outlet of the water heater.  
elevation.  
[100,000][1.00 - (4000  
ft. /1000 ft. x 0.04)]  
= Btu/hr Input 4000’  
elevation.  
Specific gravity of a gas with respect to sea  
level also decreases with altitude. These  
changes in heating value and specific  
gravity tend to offset each other.  
[100,000][0.84] =  
84,000 Btu/hr Input at  
4000 ft. elevation.  
The connection on the unit marked “Inlet”  
should be used for return water from the  
storage tank. The connection on the header  
marked “Outlet” should be connected to the  
inlet of the storage tank. (See Appendix A for  
Water Heater Piping Diagrams).  
However, as elevation above sea level is  
increased, there is less oxygen per cubic foot  
(TABLE D) – GAS SUPPLY PIPE SIZING  
Length of Pipe In Straight Feet  
Nominal Iron  
Pipe Size, Inches  
10  
369  
697  
20  
256  
477  
30  
205  
384  
40  
174  
328  
50  
155  
292  
60  
141  
267  
70  
128  
256  
80  
121  
246  
90  
113  
210  
100  
106  
125  
95  
150 175 200  
3/4  
86  
79  
74  
1
200  
179  
164  
149  
138  
11/4  
11/2  
2
1,400  
2,150  
974  
789  
677  
595  
923  
543  
830  
502  
769  
472  
707  
441  
666  
410  
636  
369  
564  
333  
513  
308  
472  
287  
441  
1,500 1,210 1,020  
4,100  
6,460  
2,820 2,260 1,950 1,720 1,560  
4,460 3,610 3,100 2,720 2,460  
1,440 1,330  
2,310 2,100  
1,250  
2,000  
1,180  
1,900  
1,100  
1,700  
974  
871  
820  
21/2  
1,540 1,400 1,300  
3
11,200  
7,900 6,400 5,400 4,870 4,410  
4,000 3,800  
8,300 7,690  
3,540  
7,380  
3,300  
6,870  
3,000  
6,150  
2,720 2,500 2,340  
5,640 5,130 4,720  
31/2  
23,500 16,100 13,100 11,100 10,000 9,000  
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14” Inches Water Column (0.5 PSIG) or less and a total  
system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
1 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
assured of the proper velocity in the tubes  
and long life and economical operation from  
the water heater.  
LOW WATER  
TEMPERATURE DELIVERY  
A number of water heating applications may  
require delivered water temperature in a  
system below 140°F. Systems such as nursing  
homes and hospitals would be examples of  
this type of system.  
(TABLE F) - REQUIRED TEMPERATURE RISE  
MODEL NUMBER  
TEMPERATURE RISE °F  
CW 495  
15  
19  
22  
19  
24  
27  
34  
39  
CW 645  
CW 745  
A water heating system that will be operated  
at less than 140°F must use a mixing valve  
on the outlet side of the storage tank in order  
to ensure that the products of combustion do  
not condense inside the combustion chamber  
of the water heater.  
CW 986  
CW 1256  
CW 1436  
CW 1796  
CW 2066  
PUMP OPERATION  
The mixing valve allows the water heater to  
operate above 140°F to protect from  
1. The water heater MUST be connected  
with a properly sized and installed,  
intermittent operating, all bronze pump  
that circulates water between heater  
and storage tank.  
condensation, while still allowing a delivery of  
colder water to the system fixtures. Also  
inherent in this design is the protection of  
occupants from water containing bacteria  
such as Legionella. Legionella can be  
2.  
The pump is sized to heater input and  
water hardness. Should water hardness  
exceed 25 grains/350 TDS, consult  
factory for pump sizing.  
significantly reduced in the water storage  
vessel by heating the water to a minimum of  
140°F. (See Appendix A for piping details.)  
WATER VELOCITY CONTROL  
IMPORTANT  
The pump chart (TABLE H) is based on the  
following fittings:  
To ensure proper velocity through the heat  
exchanger, it is necessary to regulate the  
temperature rise across the heat exchanger  
from inlet to outlet. (This must be done on  
initial installation and periodically rechecked).  
6-90° elbows 2 ball valves  
2 unions  
1 cold water supply tee  
With the correct temperature rise across the  
heat exchanger (See TABLE F), you may be  
12  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Due to pump capacity the following  
specifications cannot be exceeded  
when using the standard pump:  
Standard production Lochinvar water heaters  
are designed to operate free of impurity  
build-up in the heat exchanger when  
properly installed and operated under the  
specified water quality conditions.  
NOTE:  
A larger pump must be  
utilized in situations  
when the distance  
between the water  
and tank exceed  
• Not more than 45 feet of straight pipe.  
those specified.  
• For every elbow and tee in excess of  
those shown above, DEDUCT 5 FEET  
from maximum allowable straight pipe  
in heater-to-tank circulating loop.  
For installation in areas outside these  
parameters, please consult the factory.  
Water Flow Switch  
Due to the low water content (between 1  
and 6 gallons) of the copper finned tube  
heat exchanger, a flow switch is factory  
installed as a low water cutoff device on  
models CW495 thru CW2066.  
The flow switch is installed in the outlet  
piping from the water heater and wired in  
series with the ignition system safety controls.  
WATER TREATMENT  
(TABLE G) – REQUIRED PUMP  
PERFORMANCE FOR WATER HARDNESS  
OF 5 TO 25 GRAINS  
NOTE:  
Care should be taken to  
measure temperature  
rise and maintain proper  
water velocity in the  
heat exchanger.  
MODEL  
GPM  
FT. HD  
AMP DRAW  
HORSE  
VOLTAGE/  
PHASE  
POWER  
CW 495-745  
60  
90  
10  
15  
5.8  
7.4  
1/4  
1/2  
120/1  
120/1  
CW 986-2066  
In most localities, a flow switch is acceptable  
as a low water cutoff device on water  
heaters requiring forced circulation. It is  
prudent to verify acceptance with the local  
code official.  
In hard water areas, water treatment  
should be used to reduce introduction  
of minerals into the system. Minerals  
in the water can collect in the heat  
exchanger tubes causing noise and  
inefficient operation. Excessive build-up  
of materials in the heat exchanger can  
cause a non-warrantable failure.  
NOTE:  
If a pressure reducing  
valve or check valve is  
in the system a properly  
sized expansion tank  
may be required.  
If the local water quality levels are slightly  
higher than recommended, it may be  
possible to use a copper-nickel heat  
exchanger. With copper-nickel being a  
harder alloy, flow rates can be safely  
increased to keep the greater water  
hardness and TDS in suspension. The flow  
rate can be increased up to 25% faster than  
the flow rates listed above.  
Acceptable Water Quality Levels  
Maximum Water Hardness = 25 Grains  
Minimum Water Hardness = 5 Grains  
Maximum Total Dissolved Solids = 350 PPM  
Range of Acceptable pH = 7.2 to 7.8  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
1 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar  
Relief Valve  
NOTE:  
ELECTRICAL REQUIREMENTS  
(North America)  
The appliance is wired for 120 volts.  
Incorrect piping  
This water heater is supplied with  
temperature and pressure relief valve(s)  
sized in accordance with ASME Boiler and  
Pressure Vessel Code, Section IV “Heating  
Boilers.”  
of the cold water  
supply to the  
system will result  
in condensate formation  
on the heat exchanger  
and operational  
1.  
All wiring between the unit and field  
installed devices shall be made of type  
T wire [63°F (35°C) rise].  
(TABLE H) – COMMON WATER MANIFOLD  
SIZE FOR MULTIPLE WATER HEATER  
INSTALLATION  
problems. Higher water  
temperatures reduce  
condensate formation.  
Refer to drawings in  
Appendix A.  
2.  
3.  
The pump must be wired to run  
continuously when unit is firing.  
Pipe sizing chart provides minimum pipe size for  
common manifold piping to ensure adequate flow.  
NUMBER OF  
UNITS  
COMMON MANIFOLD SIZE  
(Min.)  
It is recommended that the water heater  
and pump be wired on separate circuits  
with properly sized breakers.  
CW 495 thru 745  
1
2
3
4
5
6
2  
3”  
1
3
/
/
2
2
4”  
5”  
5”  
(TABLE I) – AMP DRAW DATA  
CW 986 thru 2066  
MODEL  
FAN(S)  
CONTROLS  
PUMP  
TOTAL AMPS  
w/PUMP  
1
1
2
3
4
5
6
2
NUMBER  
4”  
4”  
5”  
6”  
6”  
CW 495-745  
3.4  
3.4  
3.8  
4.6  
4.6  
4.6  
5.8  
7.4  
7.4  
13.8  
15.4  
15.8  
CW 986-1256  
CW 1436-2066  
NOTE:  
When the unit is  
installed in Canada, it  
must conform to the  
CAE C22.1, Canadian  
Electrical Code, Part 1,  
and/or local Electrical  
Codes.  
14  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WA T E R H E A T E R P I P I N G D I A G R A M S  
A P P E N D I X A  
PIPING DIAGRAM  
SINGLE HEATER - SINGLE TANK  
BUILDING HOT  
WATER SUPPLY  
COLD WATER SUPPLY  
LOCHINVAR  
WATER HEATER  
RELIEF  
VALVE  
INLET  
OUTLET  
LOCK-TEMP  
STORAGE  
TANK  
DRAIN  
BUILDING RETURN  
This illustration is for concept only and should not be used for any actual installation without engineering  
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.  
LIT0133  
L E G E N D  
FULL PORT  
BALL VALVE  
SYSTEM  
PUMP  
SYSTEM  
TEE  
ELBOW  
UNION  
EXPANSION  
TANK  
CHECK  
VALVE  
THERMOMETER  
RELIEF VALVE  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
A 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING DIAGRAM  
SINGLE HEATER - TWO TANK  
BUILDING HOT  
WATER SUPPLY  
COLD WATER  
SUPPLY  
RELIEF VALVE  
LOCHINVAR WATER  
HEATER  
OUTLET  
INLET  
LOCK-TEMP  
STORAGE TANK  
DRAIN  
BUILDING  
RETURN  
This illustration is for concept only and should not be used for any actual installation without engineering  
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.  
LIT0135  
L E G E N D  
FULL PORT  
BALL VALVE  
SYSTEM  
PUMP  
SYSTEM  
TEE  
ELBOW  
UNION  
EXPANSION  
TANK  
CHECK  
VALVE  
THERMOMETER  
RELIEF VALVE  
A2  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING DIAGRAM  
TWO TEMPERATURE INSTALLATION - SINGLE HEATER-SINGLE TANK  
1800F HOT WATER  
SUPPLY  
1400F HOT WATER  
SUPPLY  
LOCK-TEMP  
STORAGE TANK  
LOCHINVAR  
LOW TEMPERATURE  
BUILDING RETURN  
CHECK VALVE  
WATER HEATER  
RELIEF  
VALVE  
MIXING  
VALVE  
INLET  
OUTLET  
DRAIN  
HIGH TEMPERATURE  
BUILDING RETURN  
COLD WATER  
SUPPLY  
This illustration is for concept only and should not be used for any actual installation without engineering  
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.  
LIT0136  
L E G E N D  
FULL PORT  
BALL VALVE  
SYSTEM  
PUMP  
SYSTEM  
TEE  
ELBOW  
UNION  
EXPANSION  
TANK  
CHECK  
VALVE  
THERMOMETER  
RELIEF VALVE  
Lochinvar D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 615-889-8900  
A3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING DIAGRAM  
TWO HEATERS-SINGLE TANK  
LOCK-TEMP  
STORAGE TANK  
RELIEF  
VALVE  
BUILDING  
HOT WATER  
SUPPLY  
COLD WATER  
SUPPLY  
DRAIN  
OUTLET  
OUTLET  
BUILDING RETURN  
INLET  
INLET  
LOCHINVAR  
WATER HEATERS  
Gray shaded area represents common manifold piping.  
COMMON WATER MANIFOLD SIZE FOR MULTIPLE WATER HEATER INSTALLATION  
Pipe sizing chart provides minimum pipe size for common manifold piping to ensure adequate flow.  
NUMBER OF  
UNITS  
COMMON MANIFOLD SIZE  
(Min.)  
NUMBER OF  
UNITS  
COMMON MANIFOLD SIZE  
(Min.)  
CW 495-745  
CW 986-2066  
1
2
3
4
5
6
2”  
3”  
1
2
3
4
5
6
2-1/2”  
4”  
3-1/2”  
4”  
4”  
5”  
5”  
6”  
5”  
6”  
This illustration is for concept only and should not be used for any actual installation without engineering  
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.  
LIT0138  
L E G E N D  
SYSTEM  
TEE  
FULL PORT  
BALL VALVE  
SYSTEM  
PUMP  
ELBOW  
UNION  
EXPANSION  
TANK  
CHECK  
VALVE  
THERMOMETER  
REDUCING  
TEE  
REDUCING  
TEE  
RELIEF VALVE  
A4  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING DIAGRAM  
TWO HEATERS-TWO TANKS  
COLD WATER  
SUPPLY  
LOCHINVAR  
WATER HEATERS  
OUTLET  
RELIEF  
VALVE  
BUILDING  
HOT WATER  
SUPPLY  
INLET  
LOCK-TEMP  
STORAGE  
TANKS  
OUTLET  
DRAIN  
BUILDING  
RETURN  
Gray shaded area represents common manifold piping.  
COMMON WATER MANIFOLD SIZE FOR MULTIPLE WATER HEATER INSTALLATION  
Pipe sizing chart provides minimum pipe size for common manifold piping to ensure adequate flow.  
NUMBER OF  
UNITS  
COMMON MANIFOLD SIZE  
(Min.)  
NUMBER OF  
UNITS  
COMMON MANIFOLD SIZE  
(Min.)  
CW 495-745  
CW 986-2066  
1
2
3
4
5
6
2”  
3”  
1
2
3
4
5
6
2-1/2”  
4”  
3-1/2”  
4”  
4”  
5”  
5”  
6”  
5”  
6”  
This illustration is for concept only and should not be used for any actual installation without engineering  
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.  
LIT0451  
L E G E N D  
FULL PORT  
BALL VALVE  
SYSTEM  
PUMP  
SYSTEM  
TEE  
ELBOW  
UNION  
EXPANSION  
TANK  
CHECK  
VALVE  
THERMOMETER  
REDUCING  
TEE  
REDUCING  
TEE  
RELIEF VALVE  
Lochinvar D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 615-889-8900  
A5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING DIAGRAM  
MULTI-STACK FRAME W/ WATER HEATERS AND STORAGE TANK  
Heater  
Model  
Heater Inlet/  
Outlet Size  
Manifold  
Pipe Size  
CW495-745  
2”  
3”  
4”  
CW986-2066  
2-1/2”  
LIT0396  
A6  
L o c h i n v a r D E S I G N E RS G U I D E C O P P E R - F I N W A T E R H E AT E R 6 1 5 - 8 8 9 - 8 9 0 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lochinvar Corporation • Lebanon, TN • 615-889-8900 / Fax: 615-547-1000  
CW-DG-05 (Revised CW-DG-05 1/07)  
4/09-Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LG Electronics Air Compressor R 134a User Manual
Life Fitness Home Gym FZPEC User Manual
Lincoln Electric Welder SVM157 A User Manual
LSI Network Card SAS3041E User Manual
Magnavox VCR VCRVR401BMG User Manual
Magnavox VCR VRA431AT99 User Manual
Makita Cordless Drill LXDT08 User Manual
Makita Cordless Sander BO4555 User Manual
Makita Cordless Saw JRl80DWB User Manual
Marmitek Home Security System Telephone Alarm User Manual