Linear Intercom System VMC 1 User Manual

VMC1  
Video Security Intercom System for the Home  
POWER  
BAND MEM ALARM DOWN UP  
+
3
4
5
5
ME-UP  
1
2
TUNER  
+
-
VOLUME  
AUX MUSIC  
RADIO FILTER  
4
2
AUX 2  
3
1
AUX 1  
INPUT FILTER  
6
VID 2  
7
5
VID 1  
GATE STATUS  
AUX OUTPUT 1  
VID 3  
MUS  
LOCK  
PRIV  
MON  
AUX OUTPUT 2  
AUX  
CLEAR  
DOOR  
HOUSE  
Rough - In Instructions  
USA & Canada (800) 421-1587 & (800) 392-0123  
(760) 438-7000 - Toll Free FAX (800) 468-1340  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT DO’S & DON’TS  
DO ensure that all instructions have been followed before  
DO NOT SPLICE CABLES. Splices are unreliable and  
defeat the signal isolation properties of the cable.  
DO keep cables at least 18 inches from fluorescent light  
fixtures, Dimmer controls, and all other wiring. This includes  
AC wiring, security cable, and other control wires. These can  
cause a “hum” or “buzzing” sound.  
power is applied to system. The installation shall be carried  
out in accordance with all applicable installation rules.  
DO use only Cat-5 & RG-6 and specified wires called out in  
these instructions. The cable is designed and constructed  
with electrical specifications necessary for proper audio  
performance.  
DO keep cables away from objects such as heating and air  
conditioning ducts, metal construction plates, and anything  
else with sharp edges that can damage the cables.  
DO follow the grounding and bonding requirements  
established by Electrical Code TIA standard 607, and  
equipment manufacturer’s specifications.  
DO use only a damp cloth to clean the exterior plastics on  
the VMC1 Master Station and Room Stations.  
DO NOT use liquid or aerosols.  
DO make gradual bends of the cable where necessary -- no  
sharper than 1” radius.  
DO NOT locate the VMC1 Master Station or Room Stations  
on an exterior wall.  
DO dress the cables neatly with cable ties or Velcro™  
wraps. Use loose or moderate pressure.  
DO NOT locate the VMC1 Master Station or Room Stations  
in any wall cavity with any other electrical wiring in the  
cavity.  
DO use cable-pulling lubricant only for cable runs that may  
otherwise require great force to install. When cable lubricant  
is used, read the instructions to be sure it is compatible with  
the cable jacket material (PVC or FEP).  
DO NOT attach non line-level audio devices or non M&S  
authorized equipment to the system.  
DO avoid stressing cable conductors, limit pulling tension to  
25 pounds or less as specified by EIA/TIA-568A standard.  
Pull cables gradually and with constant tension, taking care  
not to crush or pinch bundles.  
DO NOT power up Master Station until all stations are  
connected.  
DO NOT splice or repair cables damaged during wire  
pulling, install a new cable.  
DO use grommets to protect the cable where passing  
through metal studs or anything that can possibly damage  
them.  
DO NOT coil or bundle the cables. This can cause electronic  
feedback.  
DO test every installed cable run with a cable tester. “Toning”  
alone is not acceptable.  
DO NOT over-tighten the screws for the stations or the  
intercom Master Station to prevent cracking.  
DO NOT install any station or speaker cables inside the 120  
VAC transformer enclosure.  
DO label every termination point. Use a unique identifier  
for each cable run. It will make moves, adds, changes, and  
troubleshooting easier.  
DO NOT tie cables to electrical conduits or lay cables on  
electrical fixtures.  
DO support horizontal cable bundles using board supports,  
J-hooks, or cable trays.  
DO NOT allow the cable to be sharply bent or kinked at any  
time.  
DO have signal cables cross at right angles to power cables  
to minimize induced interference.  
DO NOT install cables “taut” anywhere. Good installation  
should have cables loose, but never sagging.  
DO NOT run signal and power cables parallel without  
adequate separation to minimize interference.  
DO NOT exert more than 25 pounds of tension on 4-pair  
cables.  
DO always obey all local and national fire and building  
codes. Be sure to “fire-stop” all cables that penetrate a fire-  
wall. Use plenum-rated cable where mandated.  
DO have a licensed electrician to run a 120 VAC line from A  
DEDICATED 15-AMP BREAKER to the VMC1 power supply.  
DO Use Cat-5 wire for all VMC1 wire runs.  
DO label all wire runs. Connecting the wires to the VMC1  
master, room station, or door station incorrectly may result  
in system damage.  
DO NOT step on Cat-5 cable during installation.  
DO NOT overtighten the cable ties, apply cable ties loosely,  
with random spacing.  
DO NOT untwist the wire pairs in Cat-5 cable more than 1/2”  
to avoid crosstalk.  
DO NOT STAPLE CABLES. Staples cause shorts.  
Keep this manual in a safe place for future reference.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Rough-in Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Materials Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
The VMC1 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Master Station. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Room Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Door Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Gates and Entrances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Cameras. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
AM & FM Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Wiring Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Cables and Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Maximum Length for Cable Runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Cable Type and Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Master Station Rough-In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
VMC1MB Master Station Mounting Bracket. . . . . . . . . . . . . . . . . . . . . . . . . . 8  
VMC1MB Installation - Unfinished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
VMC1MB Installation - Finished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Room Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Room Station Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Room Station Installation - Unfinished Wall . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Room Station Installation - Finished Wall . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Room Station Auxiliary Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Door Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
VMC1VDS Door Station Rough-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Door Station Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
VMC1VDS-S/BZ Door Station Rough-in . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
VMC1HR Rough-in Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Power Supply Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
TE6D Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Power Supply Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Data Hub Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
H628 Data Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Pull Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Antenna Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Radio Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
AM Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
FM Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Auxiliary Output Rough-In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Door Release Rough-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Chime Activated Control Output Rough-In . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Appendix A – Available Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18  
2 -Year Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Block Diagram  
ROOM STATION  
-
+
VOLUME  
2
3
4
1
5
PRIV  
6
7
AM ANTENNA  
FM ANTENNA  
MON  
MUS  
DOOR  
AUX  
CLEAR HOUSE  
ROOM STATION  
-
+
VOLUME  
2
3
4
1
5
6
7
PRIV  
MON  
MUS  
DOOR  
AUX  
CLEAR HOUSE  
POWER  
BAND MEM ALARM DOWN UP  
+5  
ME-UP  
DOOR STATION  
1
2
3
4
5
TUNER  
-
+
VOLUME  
AUX MUSIC  
RADIO FILTER  
2
AUX  
3
4
1
AUX  
1
2
INPUT FILTER  
5
VID  
6
VID  
7
GATE STATUS  
1
2
VID  
3
LOCK  
AUX OUTPUT  
AUX OUTPUT  
1
PRIV  
MON  
MUS  
2
CLEAR HOUSE DOOR  
AUX  
ROOM STATION  
-
+
VOLUME  
MASTER STATION  
2
3
4
1
5
6
7
PRIV  
MON  
MUS  
DOOR  
AUX  
CLEAR HOUSE  
DOOR LOCK  
H628 DATA HUB  
ROOM STATION  
-
+
VOLUME  
2
3
4
1
5
6
7
PRIV  
MON  
MUS  
DOOR  
AUX  
CLEAR HOUSE  
VIDEO DOOR  
STATION  
TE6D  
POWER SUPPLY  
ROOM STATION  
-
+
VOLUME  
2
3
4
1
5
6
7
PRIV  
MON  
MUS  
DOOR  
AUX  
CLEAR HOUSE  
DEDICATED POWER  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
The VMC1H installation rough-in prepares the home to  
accommodate the video intercom system. A VMC1MB  
mounting bracket is necessary for the Master Station. Room  
stations and the Alloy Color Video Door Station (VMC1VDS)  
can be mounted directly onto finished walls. All other door  
stations require a rough-in enclosure (VMC1HR).TheVMC1HR  
is also recommended for installing room stations in new  
construction or installations where the drywall has not yet  
been installed.  
Rough-in Kit  
The VMC1H Rough-in Kit includes:  
1 - (VMC1MB) Master Station mounting bracket  
1 - (TE6D) Power Supply  
VMC1MB  
1 - (101093) FM dipole antenna (#3)  
1 - (226804) 300 ohm to 75 ohm F female Balum  
1 - (250106-2) AM Antenna wire, Orange, 25 feet  
1 - (233103) H628 Data Hub (#4)  
TE6D  
233103  
101093  
250106-2  
226804  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Materials Required  
Tools  
Most are required for purposes of this installation, but may  
vary according to installer preferences.  
WIRE STRIPPERS/CUTTER  
POWER DRILL WITH 1” AUGER  
110 PUNCH-DOWN TOOL  
PHILLIPS SCREWDRIVER  
TAPE MEASURE  
14/18 GAUGE WIRE  
CAT-5 CABLE  
COAX CABLE  
LEVEL  
MOUNTING SCREWS  
(VARIOUS SIZES)  
DRYWALL SAW  
0-M  
0.5  
10  
50  
200  
50  
250  
500  
-
+
600  
10  
50  
250  
HAMMER  
VOLTMETER  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Overview  
TheVMC1 System  
Room Stations  
Designed for installation in new homes, the VMC1 is a Whole  
House Color Video Security Intercom system that provides  
room to room communication, multiple camera support,  
basic home automation controls, and video security for mid to  
large residential applications. VMC1 provide years of service  
and security for the homeowner as many people move into  
‘smart home’ environment. New housing takes advantage of  
state of the art electronics, internet, and security applications  
such as video surveillance and monitoring. VMC1 provides up  
to 20 remote intercom stations, three video camera stations,  
and offers music and communication for the whole house.  
With multiple 12 volt Control Outputs, VMC1 can trigger  
lights, monitors, voice and text message alerts, and e-mail  
door chime alerts delivered to a smart phone. VMC1 offers a  
wide range of capacities with expanded options, accessories,  
and recommended parts. (See Appendix A).  
To avoid audio feedback, Room Stations should be kept at least  
10 feet away from other stations. Never have more than one  
station in any one room and avoid mounting stations in the  
same wall cavity (i.e. directly below and above one another in  
a two-story house). A suitable height is generally 4.5 feet from  
the floor to the center of the unit. For Room Stations mounted  
on wood frame walls, place near a stud to allow for adequate  
support. For tiled surfaces, install a wall box before lining or  
tiling the walls. Cut the tiles to the inside dimensions of the  
wall box. Where Room Stations are mounted outside and are  
exposed to the weather, the fitting of weatherproof covers is  
recommended (p/n DSWS). Stations must not be installed in  
saunas.  
Door Stations  
Door Stations are best located adjacent to the front door  
or at the front gate at a suggested height of 4’-6” and may  
require a wall box depending upon the surface to which they  
are to be affixed. Door Stations are weather resistant, but  
should not be exposed directly to rain or extreme weather.  
Any station exposed to the weather requires a weather shield.  
When equipped with the appropriate weather shield the Door  
Station is designed to meet ANSI/IEC 60529 IP31 weather  
proof standards.  
It is important that each step of the installation be  
carefully completed by the installer. In the event you need  
troubleshooting assistance, please call our technical support  
staff at 1-800-421-1587.  
General Information  
The following general procedures must be observed in  
relation to the location and installation of VMC1 components:  
Where stations are to be installed outdoors, appropriate  
measures to provide protection from the weather are to be  
taken.  
Gates and Entrances  
Where stations are to be installed in brick or concrete columns  
at a front gate, the cable should be run in conduit from the  
station to below ground level and back to the house.  
The power supply should be located in an area with sufficient  
space for heat dissipation.  
Cameras  
Guidelines for maximum cable lengths as set out in this  
manual are to be observed to avoid the possibility of operating  
problems due to excessive cable voltage drop.  
For Door Stations fitted with cameras, consideration must be  
given to the viewing area of the camera taking factors such as  
lighting and sun exposure into account.  
Interference  
Power Supply  
The circuitry of the intercom is designed to minimize the  
effects of Radio Frequency Interference (RFI); and there will  
be minimal and occasional radio frequency interference as  
power outages, lightning storms, and any electrical apparatus  
can affect the system. To reduce instances of interference,  
reduce any unwanted audible buzz in audio appliances  
such as microphone amplifier, speaker amplifier, car radio,  
telephones etc, you add on-board EMI filters or special layout  
techniques to help bypass EMI or improving RF immunity.  
Most circuits have integrated RF filters or special design that  
prevents demodulation of high-frequency carriers.The use of  
microwaves, cell phones, cable television, bug zappers, even  
heating pads in close proximity, can create interference.  
The Power Supply should be attached to the VMC1MB as  
directed. Improper installation of the Power Supply can lead  
to unit malfunction and void the warranty.The Power Supply  
needs sufficient space to dissipate heat effectively.  
AM & FM Antennas  
Theantennaarrangementiscriticaltotheinstallationforquality  
radio reception. Place AM and FM antennas at the highest  
point of the roof and at least 6 feet away from any electrical  
or intercom wiring. Both AM and FM antennas are directional,  
and correct positioning requires some experimentation to  
achieve the best possible result. Antenna wires should also  
be positioned at the highest and most accessible point in  
the roof. Allow additional cable at the mounting bracket for  
termination, at least 3 feet for the Master Station.  
Master Station  
The Master Station should be positioned at a suggested  
height of 4-1/2’ to 5-1/2’ from the floor to the center of the  
unit. As all wiring from other stations is generally terminated  
at the rear of the Master Station, the wall should be no less  
than 3 inches in depth. Use the VMC1MB to provide adequate  
support for the unit.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Information  
CableType and Configuration  
Cables andWiring  
Excellent locations to run cables include:  
The general intercom functions for VMC1 can be cabled using  
Cat-5 or Cat-6 cables. If required, 6-conductor telephone  
cables can be used provided the system is configured for  
6-wire operation.  
Roof space  
False ceilings/ bulkhead area  
Through and/or around external walls  
Under floors (subject to access being available)  
Underground in conduit  
Be sure to clearly tag all cables to identify any damaged cables  
or other system faults. See the table below for Cat-5 wire color  
recommendations.  
NOTE: Keep Intercom cables far from any AC wiring. Avoid running  
intercom cable in parallel to AC or any other type of wiring. Avoid placing  
joins or splices in cables. Locate cables where there is access for future  
servicing.  
ROOM STATIONS SHOULD  
BE AT LEAST TEN FEET  
APART FROM ONE  
ANOTHER  
Maximum Length for Cable Runs  
The system can be “home-run wired” from a central point or  
“daisy chained” from station to station. However, the number  
of stations on a daisy chain run governs the overall length  
of the run. The tables below show the relationship between  
the length on a cable run and the number of room stations  
permitted and the maximum cable run to a Door Station.  
NOTE: The tables are based on the use of Cat-5 or Cat-6 cable. Where  
required, the wire lengths maximum distances can be doubled by  
running 12 AWG speaker wire in parallel with the POS & NEG wires. It  
is important that the POS and NEG wires are balanced in terms of the  
type of wire and the number of wires being used - i.e. if a Cat-5 wire and  
12 AWG speaker wire are being used for the positive connection, a Cat-5  
wire and a 12 AWG speaker wire should also be used for the negative  
connection.  
MAXIMUM CABLE LENGTH TO ROOM STATIONS  
NUMBER OF STATIONS ALLOWED  
1 Room Station  
100 yards  
50 yards  
33 yards  
25 yards  
2 Room Stations  
3 Room Stations  
4 Room Stations  
MAXIMUM CABLE LENGTH TO DOOR STATIONS  
NUMBER OF STATIONS ALLOWED  
80 yards  
1 Door Station  
MASTER STATION CONNECTION  
VIDEO DOOR STATION  
NON-VIDEO DOOR STATION  
ROOM STATION  
WIRING  
Green White  
Green  
Green White  
Green  
Green White  
Green  
POS  
NEG  
TC  
Orange White  
Orange White  
Orange White  
Orange  
VLC  
VLCx  
COM1  
COM2  
MUS1  
MUS2  
VIDx  
GND  
AUX  
Orange  
Blue White  
Blue  
Orange  
Blue White  
Blue  
Blue White  
Blue  
Brown White  
Brown  
Signal  
Ground  
Yellow  
Optional  
Cat-5/6  
Optional Video Signal  
Optional Video Ground  
Brown White  
Brown  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Station Rough-In  
VMC1MB Master Station Mounting Bracket  
VMC1MB Installation - UnfinishedWall  
The VMC1MB mounts flush with the wall stud and holds the  
Master Station and Power Supply (See Figure 1). Position the  
VMC1MB at a suggested height of 4-1/2 to 5-1/2 feet from the  
floor to center of the unit. As all wiring from other stations  
is generally terminated at the rear of the Master Station, the  
wall should be no less than 3 inches deep. If required, install  
additional wood shims or metal rough-in enclosures to allow  
for adequate support of the Master Station.  
Install the VMC1MB flush with the front of the wall stud and  
fasten in place with screws as shown. After drywall has been  
installed, cut out an opening to the inside dimensions of the  
VMC1MB (7-1/4” x 11.).  
IMPORTANT: Install the Master Station in a cavity wall to allow for the  
wiring behind it. Do not install in a brick wall. For wall tiling around the  
Master Station, ensure that it is mounted either completely within or  
clear of tile to avoid an uneven surface. Be sure to allow at least 10” of  
space below Master Station Bracket and firebreaks for Power Supply.  
This is also necessary for clearance when installing the Master Station  
Mounting Bracket into pre-cut drywall opening.  
The VMC1MB has a correct orientation, so review Figures 1  
and 2 to be sure it is right side up.  
WALL STUD  
VMC1MB  
MASTER STATION  
BRACKET  
TRACE THIS AREA  
AS A TEMPLATE  
FOR MASTER  
STATION OPENING  
ON DRYWALL  
MOUNT  
BRACKET  
FLUSH WITH  
FRONT OF  
WALL STUD  
POWER SUPPLY (TE6D)  
MOUNTS TO FLANGE ON  
MASTER STATION BRACKET  
(7-1/4” x 11”)  
MOUNT BRACKET AT LEAST  
10” FROM ANY FIREBREAK  
BRACKET  
FLANGE  
WALL STUDS  
FRONT VIEW  
VMC1MB  
MASTER  
STATION BRACKET  
FIREBREAK  
4’-5” to 5’-5”  
MOUNTING HEIGHT  
FROM FLOOR TO  
CENTER LINE OF  
BRACKET  
Figure 1. Installing Bracket - Unfinished Wall  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Master Station Rough-In  
VMC1MB Installation - FinishedWall  
Cut out an opening in the drywall (Height 7-1/4” x Width 11”)  
but do not cut right up against the wall stud. Allow 5/8”  
clearance between drywall opening and stud.This ensures that  
drywall will overlap bracket (See Figure 2). Slide theVMC1MB  
vertically, then turn clockwise 90˚. Mount in place onto stud  
using fasteners as shown. Hang Power Supply on VMC1MB  
in the lower right corner as shown. It may be necessary to  
lightly tap Power Supply in place onto VMC1MB flange with  
a hammer.  
STUD BEHIND  
DRYWALL  
TRACE THIS AREA  
AS A TEMPLATE  
FOR MASTER  
STATION OPENING  
ON DRYWALL  
11”  
(7-1/4” x 11”)  
CUT DRYWALL  
OPENING  
VMC1MB  
CUT OPENING  
5/8” FROM STUD  
7-1/4”  
FRONT VIEW  
DRYWALL  
DRYWALL OPENING  
IS 5/8” FROM STUD  
THEN TURN BRACKET 90°  
CLOCKWISE AND MOUNT  
TO STUD  
STUD  
DRYWALL  
FRONT VIEW  
SLIDE VMC1MB BRACKET  
VERTICALLY INTO DRYWALL  
OPENING  
DRYWALL  
DRYWALL  
OVERLAPS  
BRACKET  
HANG POWER  
SUPPLY ON VMC1MB  
BRACKET AS SHOWN.  
USE HAMMER TO LIGHTLY  
TAP INTO PLACE ON MASTER  
STATION BRACKET FLANGE  
DRYWALL  
FRONT VIEW  
Figure 2. Installing Bracket - Finished Wall  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Room Station Rough-In  
Room Station Mounting  
Room Station Installation - FinishedWall  
The Room Stations are normally mounted at a height from the  
floor of: 4-1/2’ to 5.The Room Stations are not designed to be  
installed outdoors.  
Identify the location where the Room Station is to be installed.  
Cut a 3-1/2” x 7-3/4” rectangular hole in the drywall. When  
possible, one short edge should be situated against a wall stud  
to provide added support when installing the Room Station.  
Room Station Installation - UnfinishedWall  
For an unfinished wall it is recommended that the VMC1HR  
rough-in enclosure be used. Identify the location where the  
Room Station is to be installed.  
Pull the wire through the hole and attach to the drywall so it  
will not fall back into the wall cavity.  
Room Station Auxiliary Activation  
Attach the Rough-In Enclosure to the stud using the two inner  
pre-punched holes (see Figure 3). The outside holes on the  
wings of the box are to be used to mount the room station  
and not to attach the Rough-in Enclosure to the stud.  
When operating in single digit mode, each Room Station  
can activate the Auxiliary Control Output (CO) triggers at the  
Master Station.  
Pull a yellow 18 gauge wire from the VMC1MB to the Room  
Station location. Following this color convention will assist in  
the final installation of the VMC1 system.  
Pull the Cat-5 wires through the hole in the back of the Rough-  
in Enclosure and make a knot so they do not fall back into the  
wall once the drywall is installed.  
Pull the yellow wire through the hole in the back of the  
Rough-In Enclosure and loop it through so it does not fall back  
into the wall once the drywall is installed.  
After drywall is installed, cut out an opening to the inside  
dimensions of the VMC1HR utilizing the inside of the box as a  
guide (see Figure 3 ).  
ROOM STATION ROUGH-IN  
ENCLOSURE (SEE DRAWING A)  
USE INNER HOLES FOR  
MOUNTING ROUGH-IN  
ENCLOSURE TO STUD  
7-3/4”  
VMC1HR  
VMC1RS-WH  
ROOM STATION  
MOUNTING PLATE  
3-1/2”  
CAT5 CABLE LOOPED  
WITH EXCESS AMOUNT  
STUDS  
ELECTRONICS  
PANEL  
DRYWALL  
ROOM STATION ROUGH-IN  
ENCLOSURE  
-
VOLUME  
VMC1HR  
1
+
2
3
5
4
PRIV  
6
MON  
4’-6” to 5’-0”  
MOUNTING HEIGHT  
FROM FLOOR LINE  
7
MUS  
CLEAR  
HOUSE  
DOOR  
AUX  
BEZEL  
DRYWALL  
ANCHORS  
DRAWING A  
GRILLE  
PRE-DRYWALL ROOM STATION  
INSTALLATION  
VMC1RS-WH  
-
VOLUME  
1
+
2
3
5
4
PRIV  
6
MON  
7
MUS  
CLEAR  
HOUSE  
DOOR  
AUX  
POST-DRYWALL ROOM STATION  
INSTALLATION  
Figure 3. Pre-Drywall and Post-Drywall Room Station Installation  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Door Station Rough-In  
1. Identify the location where the VMC1VDS is to be  
VMC1VDS Door Station Rough-in  
installed.  
The VMC1VDS is a metal door station with a 90 degree  
horizontal viewing area. It is normally mounted at a height  
from the floor of: 55” – 60. When installing the VMC1VDS be  
aware of the camera location and the direction of sunlight and  
other ambient light. Direct sun or lighting into the lens of the  
VMC1VDS camera may impact the video quality. Additionally,  
exposure to extreme weather conditions is not recommended.  
For added protection against weather, the VMC1VDS should  
be equipped with a VDSWS-T weather shield.The installation  
of the VDSWS-T is shown in Figure 4.  
2. Pull Cat-5 wire from the VMC1MB to this location.  
3. Label and tie off the wires so they do not fall back into the  
wall and are accessible when the VMC1VDS is installed.  
4. If the door strike or Chime activated Control Output is  
to be utilized, see “Door Release Rough-in” and “Chime  
Activated CO Rough-in.  
NOTE:When removing allen screw fromVideo Door Station front bezel, a  
small metal tab will drop out of the chassis. Be sure to re-install tab into  
camera chassis slot before re-assembly.  
ANCHORS  
DRYWALL  
PLEXIGLASS  
WEATHER  
SHIELD (OPTIONAL)  
VDSWS-T  
CAMERA  
CHASSIS  
MOUNTING  
HEIGHT  
4-1/2’ to 5’-0”  
FROM FLOOR  
LINE  
NOTE: METAL TAB  
DROPS OUT WHEN  
REMOVING ALLEN  
SCREW HOLDING  
FRONT BEZEL  
VMC1VDS  
BEZEL  
TO CAMERA CHASSIS  
ALLEN  
SCREW  
Figure 4. VMC1VDS Door Station Rough-In  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Door Station Rough-In  
VMC1HR Rough-in Enclosure  
VMC1VDS-S/BZ Door Station Rough-in  
1. Attach the VMC1HR flush to the exterior wall using the  
two inner pre-punched holes in theVMC1HR.The outside  
holes on the wings of the box are to be used to mount the  
VMC1VDS-S/BZ and not to be used to attach theVMC1HR  
to the exterior wall.  
The VMC1VDS-S and VMC1VDS-BZ incorporate a wide angle  
120 degree horizontal viewing camera into a Door Station. It  
is normally mounted at a height from the floor of: 55” – 60.  
Installation of this unit on an exterior wall requires 4 screws  
and anchors (See Figure 6). When installing these units, be  
aware of the camera location and the direction of sunlight and  
other ambient light. Direct sun or light pointed into the lens of  
the VMC1VDS camera may impact video quality. Additionally,  
exposure to extreme weather conditions is not recommended.  
For added protection against weather, the VMC1VDS-S and  
VMC1VDS-BZ should be equipped with a DSWS weather  
shield. The installation of the DSWS is provided in the VMC1  
Finish Out Guide.  
2. Pull the Cat-5 wires through the hole in the back of the  
VMC1HR and loop it through so they do not fall back into  
the wall.  
3. If the door strike or Chime activated Control Output is  
to be utilized, see “Door Release Rough-in and “Chime  
Activated CO Rough-in  
PRE-DRYWALL COLOR VIDEO DOOR  
STATION  
USE INNER HOLES FOR  
MOUNTING ROUGH-IN  
ENCLOSURE TO STUD  
7-3/4”  
VMC1HR  
VMC1VDS-BZ  
VMC1VDS-S  
3-1/2”  
CAT5 CABLE LOOPED  
WITH EXCESS AMOUNT  
COLOR VIDEO DOOR  
STATION WALL  
MOUNTING PLATE  
DRYWALL  
ELECTRONICS  
PANEL  
VMC1VDS-BZ  
VMC1VDS-S  
BEZEL  
ANCHORS  
GRILLE  
POST-DRYWALL COLOR  
VIDEO DOOR  
STATION  
Figure 5. VMC1VDS-S/BZ Door Station Rough-In  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Supply Rough-In  
TE6D Power Supply  
Power Supply Connections  
The Power Supply unit is pre-wired and self contained, and  
the wires are tucked inside.To access connection wires, open  
the Power Supply unit by removing four screws as shown  
in Figure 6. In the unlikely case that the TE6D electrical  
connectors become unplugged, the 3-pin and 6-pin connector  
blocks can be re-installed in their respective locations on the  
power supply board. Plug connectors in as shown.  
The 6-pin connector is the low voltage (13.8 VDC, 3.8 amp)  
output from theTE6D Power Supply unit:  
Position 3 is the Black Negative connection for the Master  
Station  
Position 5 is the Red Positive connection for the Master  
Station  
The 3-pin connector is for the 110/120 High Voltage input:  
Black wire is position 1  
White wire is position 3  
WARNING  
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE TE6D  
POWER SUPPLY MUST BE MADE BY A LICENSED ELECTRICIAN  
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL  
CODES  
PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY  
BOTTOM HOUSING  
REMOVE 4 SCREWS  
TO ACCESS POWER  
SUPPLY WIRES  
TOP HOUSING  
3-PIN  
CONNECTOR  
3
2
1
WHT  
BLK  
BOTTOM HOUSING  
6-PIN CONNECTOR  
6
5
RED  
4
3
2
BLACK  
1
STRAIN RELIEF  
TOP HOUSING  
STRAIN RELIEF  
Figure 6. Opening TE6D Power Supply  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Supply Rough-In  
5. Secure all power cables entering the Power Supply  
Power SupplyWiring  
enclosure with cable strain reliefs.  
1. Run a 14 AWG 120 VAC power cable (including ground)  
from a dedicated 15-amp circuit breaker to the Master  
Station Mounting Bracket location.The VMC1 requires a  
dedicated power source so theres no interference from  
other equipment.  
6. Tuck cables into the Power Supply enclosure.  
7. Pull the Red and Black low voltage wires out of the top  
of the TE6D for later connection to the Master Station.  
Re-assemble theTE6D housing with the provided screws  
(See Figure 7).  
2. Route incoming power cable into the Power Supply  
enclosure through the hole on the SIDE of the Power  
Supply.  
8. Hook the power supply onto the flange of the VMC1MB  
and attach the it with screw provided (See Figure 7).  
3. Use wire nuts to connect the incoming power cable  
to the TE6D Power Supply BLACK (HOT) and WHITE  
(NEUTRAL) input wires.  
NOTE: Be sure all power cables entering the power supply enclosure are  
secured with cable strain reliefs.  
4. Connect the GREEN (GROUND) wire to the ground  
conductor.  
PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY  
HOT WIRE  
(BLACK)  
BOTTOM HOUSING  
GROUND WIRE  
(GREEN)  
NEUTRAL WIRE  
(WHITE)  
WIRE NUTS  
INSERT  
WIRE FROM  
BREAKER INTO  
STRAIN RELIEF  
PLUS 13V WIRE (RED)  
NEGATIVE WIRE (BLACK)  
STRAIN RELIEF  
TOP HOUSING  
FEED WIRES THROUGH  
STRAIN RELIEFS ON TOP  
HOUSING AS SHOWN. CONNECT  
WIRES USING WIRE NUTS, THEN  
RE-INSTALL TOP HOUSING  
WITH 4 SCREWS  
STRAIN RELIEF  
POWER IDENTIFICATION  
AT MASTER STATION  
PLUS 13V  
WIRE (RED)  
NEGATIVE  
WIRE (BLACK))  
110/120V HIGH  
VOLTAGE INPUT  
(BLACK)  
SCREW  
(PROVIDED)  
RE-ASSEMBLED TE6D POWER SUPPLY  
WITH WIRES PROTRUDING  
NEUTRAL  
(WHITE)  
TE6D POWER SUPPLY  
GROUND  
(GREEN)  
Figure 7 - TE6D Power Supply Wiring  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Data Hub Wiring  
H628 Data Hub  
The H628 Data Hub is used to connect each station to the  
Master Station.  
TIA-568A WIRING STANDARD  
PullWires  
DATA HUB RJ-45  
MODULAR PLUG  
Pull all the Door and Room Station cables to the location of  
the Master Station Mounting Bracket (VMC1MB).  
Cat-5 WIRE COLOR  
If the installation consists of more than 5 room stations, Linear  
recommends using the optional Linear DMD-16 (16 stations)  
Data Distribution module and the Model H275 Universal  
Bracket (Optional, see Appendix A).  
Pin 1  
Pin 2  
Pin 3  
Pin 4  
Pin 5  
Pin 6  
Pin 7  
Pin 8  
White/Green  
Green  
White/Orange  
Blue  
1. Determine a mounting location for the H628 Data Hub. It  
is recommended to use a Model H275 Universal Bracket  
(Optional, see Appendix A).  
White/Blue  
Orange  
2. Terminate Cat-5 cables from stations with RJ-45 modular  
plugs wired to TIA-568A wiring standard (See Table at  
right).  
White/Brown  
Brown  
3. Cut a length of Cat-5 cable to run from the H628 Data Hub  
to the Master Station location.  
4. Strip back about 8” of cable insulation and use a 110  
Punch-down tool to bridge all of the punch-down  
connectors with the Cat-5 cable as shown in Figure 8.  
5. Plug all of the stations modular plugs into the RJ-45  
sockets on the H628 Data Hub.  
6. Route the bridged Cat-5 cable to the Master Station  
location and secure it so it won’t fall back into the wall.  
FROM  
FROM  
DOOR  
ROOM  
STATION STATION  
FROM FROM  
ROOM ROOM  
STATION STATION  
FROM  
NIGHTSTAND  
STATION  
RJ-45 PLUG SOCKETS  
CAREFULLY PUNCH  
WIRES INTO TERMINAL  
BLOCK USING A  
1 BROWN  
2 WHITE/BROWN  
3 GREEN  
4 WHITE/GREEN  
5 ORANGE  
6 WHITE/ORANGE  
CAT-5 CABLE  
TO MASTER STATION  
110 PUNCH-DOWN TOOL  
7 BLUE  
8 WHITE/BLUE  
110 PUNCH-DOWN TOOL  
110 PUNCHDOWN CONNECTORS  
8” OF CAT-5 CABLE INSULATION STRIPPED  
Figure 8. H628 Data Hub Wiring  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Antenna Installation  
Radio Antennas  
VMC1 requires two antennas, one for AM and one for FM  
reception.The AM antenna is a 25-foot wire the FM antenna is  
a 25-foot length of coax with a “T” shaped wire dipole at one  
end that attaches between rafters in the attic.  
ORIENTATE FM ANTENNA  
FOR STRONGEST RECEPTION  
Antenna arrangement is crucial to quality radio reception. AM  
and FM antennas should be placed at the highest point of the  
roof and at least six feet away from any electrical or intercom  
wiring.  
IMPORTANT! Isolate the antenna leads from the intercom station cables  
by running them through a separate hole in the ceiling plate. If grouped  
together, the intercom station cables can shield the antenna leads  
resulting in poor radio reception. Also keep the antenna leads away  
from metal duct work and aluminum backed insulation, which reduces  
reception.  
ATTIC  
AM Antenna  
1. Unroll the 25-foot AM antenna wire.  
2. Route the antenna wire to the best location, ideally in an  
attic.  
AM ANTENNA  
WIRING  
FM ANTENNA  
WIRING  
3. Route the antenna wire down through the hole in the  
ceiling plate, down the stud bay to where the VMC1MB  
was installed (see Figure 9).  
MASTER STATION  
PO
BAND MEM ALARM DOWN UP  
+5  
ME-UP  
1
2
3
4
5
NOTE: the overall length of the antenna wire may be extended by splicing  
on to the ‘openend of antenna with insulated wire.The gauge end of the  
wire should be strong enough to support it without breaking.  
TUNER  
-
+
VOLUME  
AUX MUSIC  
RADIO FILTER  
1
2
3
4
AUX  
1
AUX  
2
I
N
P
U
T
F
I
L
T
E
R
5
VID  
6
7
GATE STATUS  
1
VID  
2
VID  
3
LOCK  
AUX OUTPUT  
AUX OUTPUT  
1
2
PRIV  
MON  
MUS  
C
L
E
A
R
H
O
U
S
E
D
O
O
R
AUX  
NOTE: Some customers may want to use an external tuned loop antenna  
or vertical amplified broadband antenna. Refer to those manufacturer’s  
installation instructions for further information.  
75 OHM TO 300 OHM  
ADAPTER  
FM Antenna  
1. Unroll and examine the FM antenna. The antenna is  
formed by spreading the red and black wires at the end  
of the COAX.The terminal lug at the end of each wire is  
for screw mounting the wires outstretched.The antenna  
is provided with an F type connector allowing for easy  
connection of additional cable.  
Figure 9. Antenna Location  
2. Use screws to attach the red and black antenna leads to  
the structure outstretched (See Figure 9).  
3. Route the connector end of the antenna COAX down  
through the hole in the ceiling plate, down the stud bay,  
and on the right side of where theVMC1 Master Unit will  
be installed.  
4. Connect the included 75 Ohm to 300 Ohm adapter to the  
end of the cable.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auxiliary Output Rough-In  
Door Release Rough-in  
Chime Activated Control Output Rough-In  
The Door Release Trigger can be activated from the VMC1  
Master or any remote room station by pressing the Lock  
button.TheTrigger will deactivate after 4 seconds and can be  
activated multiple times while the intercom is active.  
The Chime Activated Control Output allows for any number of  
security related automation functions including 10 available  
door chimes.To connect an auxiliary Chime refer to Figure 10.  
Refer to the hook-up instructions supplied with the chime.  
To connect the optional Linear Model DRW Door Release  
Mechanism, refer to Figure 10 For controlling other door  
release devices, refer to the hook-up instructions supplied  
with the device.  
1. Route a blue and a black 18 gauge wire from the Door  
Station location or VMC1VDS to the optional 12V  
Model 284 relay. (See Appendix). Following this color  
convention will assist in the final installation of the Door  
Station.  
1. Route a blue and a white 18 gauge wire from the Door  
Station location or VMC1MB to the optional 12V Model  
284 relay. (See Appendix A). Following this color  
convention will assist in the final installation of the Door  
Station.  
2. Connect the blue wire to the red coil wire on the 284  
relay.  
3. Connect the black wire to the white coil wire on the 284  
relay.  
2. Connect the blue wire to the red coil wire on the 284  
4. Connect a red 18 gauge wire to the green Normally Open  
relay.  
wire on the 284 relay.  
3. Connect the white wire to the white coil wire on the 284  
5. Connect a red 18 gauge wire to the blue Common wire  
relay.  
on the 284 relay.  
4. Connect a red 18 gauge wire to the green Normally Open  
6. Connect the other end of the red wire from the relay to  
theYellow wire on the RT35 or either of the wires on the  
RT11.  
wire on the 284 relay.  
5. Connect a red 18 gauge wire to the blue Common wire  
on the 284 relay.  
7. Connect the other end of the red wire from the relay to  
6. Connect the other end of the red wire from the relay to  
theYellow wire on the RT35 or either of the wires on the  
RT11.  
one of the wires from the Chime.  
8. Connect the remaining wire on the Chime to theYellow/  
Red wire on the RT35 or the remaining wire on the RT11.  
7. Connect the other end of the red wire from the relay to  
9. Install the optional Auxiliary Chime following its  
one of the wires from the DRW.  
instructions.  
8. Connect the remaining wire on the DRW to the Yellow/  
Red wire on the RT35 or the remaining wire on the RT11.  
9. Install the optional DRW into the door frame following  
the included instructions.  
DRW  
MODEL DRW  
ELECTRONIC DOOR STRIKE  
OR CHIME  
VMC1VDS  
GRAY  
DOOR  
STATION  
N/C NORMALLY CLOSED  
BLUE  
COMMON  
GREEN  
BLUE  
RED  
NORMALLY OPEN  
WHITE  
WHITE  
BLACK  
MODEL 284  
12V 5 AMP RELAY  
USE WHITE WIRE FOR DOOR RELEASE  
USE BLACK WIRE FOR AUXILIARY CONTROL OUTPUT  
24VAC  
110VAC  
MODEL RT11 OR RT35  
PLUG-IN TRANSFORMER  
Figure 10. Electric Door Strike Wiring  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A – Available Components  
System Master Station  
with 5.6” TFT LED color screen  
supporting up to 20 remote stations.  
Point-to-Point, Point-to-Group and All Call  
intercom with hands free response.  
UL 60950 certified  
VMC1 (White pictured)  
VMC1-BK (Black)  
VMC1-BZ (Bronze)  
Color Video Door Station  
with 10 different door chimes, 90º horizontal  
and 50º degree vertical viewing angle. Standard  
weather resistance (IP30) Metal Alloy  
(VMC1VDS)  
Color video door station with 10 door chimes, a  
120º horizontal and 80º vertical viewing angle.  
Standard weather resistance IP30  
Bronze (pictured)(VMC1VDS-BZ)  
Silver (VMC1VDS-S)  
5 pack of alternative color room station  
faceplates  
VMC1RST-WH-5 White  
VMC1RST-AL-5 Almond (pictured)  
VMC1RST-BK-5 Black  
VMC1RST-BZ-5 Bronze  
Room station for all non-video intercom, home  
security and automation functions  
White (pictured)  
(VMC1RS-WH)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A – Available Components  
Starter Kit for VMC1 Security Intercom System  
one (1) Master, one (1) Alloy Door Station and  
four (4) room stations  
White(VMC1PACK)  
Non-video door station. Basic doorbell intercom  
station where video is not required. Standard  
weather resistance IP30  
(VMC1DS-BZ Bronze)  
(VMC1DS-S Silver) pictured  
Nightstand station.  
Provides all of the function of the intercom for  
use on a nightstand or desk  
Black (VMC1TTS)  
Plexiglas weather shield increases the weather  
resistance of VMC1VDS to IP31 Smoke Color  
(VDSWS-T)  
Plexiglas weather shield increases the weather  
resistance of VMC1VDS-BZ/S to IP31  
Clear (DSWS)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A – Available Components  
Mounting bracket for VMC1 Master  
Steel (VMC1MB)  
Rough in kit for the VMC1 Master.  
Includes mounting frame,  
TE6D power supply,  
FM Dipole antenna,  
AM antenna wire and  
installation hardware  
(VMC1H)  
Metal mounting box for room and video stations  
except VMC1VDS  
(VMC1HR Steel)  
Model H275 Universal Bracket for  
Data Hub Installation  
Indoor Box Color Camera  
(left) & Color Video Cameras w/nite vision (right)  
(MLTL2DN49IR)  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A – Available Components  
Electronic Door Release  
w/power supplies  
Remote Door Lock  
(DRW)  
12V Control Output switched 110V outlets for  
lights and other “notification” devices  
Remote Turn On for Lights  
AC1 (1 outlet) AC3 (2 outlets)  
MFG: Xantec/Niles  
2-Channel Receiver (DXR-702)  
Miniature door / window transmitter  
(DXS-32)  
Wire Relay  
The 284 Leaded Accessory Relay is a 5 amp  
Form C relay with wire leads pre-attached.  
(0-200284)  
Video Modulator and distribution hub to transmit  
door camera image to TV or get Video on TV  
Single channel video modulator  
(5415)  
For more parts and accessories, please go to  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 - Year Limited Warranty  
Linear LLC warrants these products to be free of defects for  
2 years. The warranty period begins on either (a) the date of  
purchase or installation date of this product or (b) the date  
of closing on a new residence in which this product was  
originally installed. The warranty extends to the original user  
of the product and to each subsequent owner of the product  
during the term of the warranty. Linear LLC will repair or  
replace, at its option, parts and materials at no charge. Parts  
supplied under this warranty may be new or rebuilt at the  
option of Linear LLC.  
ANY PRODUCT RETURNED TO LINEAR LLC WITHOUT A  
RPA NUMBER WILL BE REFUSED. This limited warranty is in  
lieu of any other warranties, express or implied, including  
any implied warranty of merchantability or fitness for a  
particular purpose or otherwise, and of any other obligations  
or liability on the sellers part. This limited warranty does  
not cover damage caused by improper installation, acts  
of God, criminal acts, the violation of applicable building  
or electrical codes or the use of non-recommended  
wire, cable (excluding Cat-5 and RG-6) or wall housings.  
Under no circumstances shall Linear LLC be liable for  
consequential, incidental or special damages arising in  
connection with use, or inability to use this product. In no  
event shall Linear LLC liability hereunder exceed the cost of the  
product covered hereby. No person is authorized to assume  
for us or obligate us for any other liability in connection  
with the sale of this product. Some states do not allow the  
exclusion or limitation of consequential, incidental or special  
damages, so the above limitation or exclusion may not apply  
to you. This limited warranty gives you specific legal rights,  
and you may also have other rights, which vary from state to  
state.This Linear LLCWarranty is in lieu of all other warranties  
express or implied.  
If during the warranty period the product appears to have a  
defect, please call our toll free service number (800-421-1587)  
prior to dismantling. Dismantling the product prior to  
calling our service number may void the warranty. Before  
returning any product to Linear LLC, contact your local dealer  
or distributor. Linear LLC will return the repaired product  
freight prepaid within the continental United States. There  
are no obligations or liabilities on the part of Linear LLC for  
consequential damages arising out of or in connection with  
use or performance of this product or other indirect damages  
with respect to loss of property, revenue, or profit, or cost of  
removal, installation, or reinstallation.  
USA & Canada (800) 421-1587 & (800) 392-0123  
(760) 438-7000 - Toll Free FAX (800) 468-1340  
Copyright © 2012 Linear LLC  
233254 AX3  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KTI Networks Computer Accessories 24 Port 10 100 Workgroup Switch User Manual
Learning Resources Baby Toy LER 2298 User Manual
Lenovo Computer Monitor L2062 User Manual
LG Electronics Air Conditioner LS090CPAS C0914DH0 User Manual
LG Electronics Cell Phone 370H User Manual
Liebert Power Supply PowerSure Personal User Manual
Manitowoc Ice Ice Maker K00042 User Manual
Master Lock Portable Generator MGY5000C User Manual
Melissa Coffeemaker 645 085 User Manual
Melissa Microwave Oven 253 023 User Manual