POWERSURE™ PERSONAL
300-500 VA
115V
USER MANUAL
English
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure Personal
Uninterruptible Power System (UPS).
It provides conditioned power to
microcomputers and other sensitive electronic equipment.
NOTE: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment uses, generates and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference with radio communications.
However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the
following measures:
-
-
-
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that which
the receiver is connected.
-
Consult the dealer or an experienced radio/TV technician for help.
MAJOR COMPONENTS
TM
PowerSure
Personal
DB-9 Interface for
SiteNet MultiLink Cable
Utility / Battery LED
Warning LED
Power ON / Standby
Output
Receptacles
Input Receptacle
Fuse Holder
R
Liebert
BACK
FRONT
Download from Www.Somanuals.com. All Manuals Search And Download.
TM
PowerSure Personal
Line Diagram
INPUT
L
OUTPUT
L
TVSS and
EMI / RFI
Filters
Transfer
Switch
Battery
Battery
Charger
Inverter
N
G
N
G
Normal Operation
During normal operation, incoming utility power is supplied to the load as shown
above. The utility power passes through the EMI/ RFI filters and TVSS circuitry
and then through the transfer switch to the connected loads. The battery charger
is operational whenever AC power is supplied, even when the unit is switched
off. PowerSure Personal continuously monitors the batteries.
Transfer Switch
In Normal mode the transfer switch passes utility AC power to the connected
load. When input utility or frequency is outside acceptable limits, the transfer
switch activates and transfers the UPS to battery.
Battery Charger
In normal operation, the battery charger converts utility AC power into regulated
DC power to float charge the battery.
Battery
The PowerSure Personal utilizes valve regulated, nonspillable, lead acid battery.
At typical room temperatures and with the UPS float charging, the battery system
will last many years.
Transient Voltage Surge Suppression (TVSS) & EMI / RFI Filters
These UPS components provide surge protection and filter electromagnetic
interference (EMI) and radio frequency interference (RFI). They minimize any
surges or interference present in the utility line and keep the sensitive equipment
protected.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
GENERAL INSTALLATION
T
M
PowerSure
Personal
T
M
PowerSure
Personal
R
Liebert
R
Liebert
Check for Damage
Remove from Box
T
M
PowerSure
Personal
4 Inches
110 mm
32° - 104° F
0° - 40° C
R
Liebert
Plug in Loads
T
M
PowerSure
Personal
T
M
PowerSure
Personal
R
R
Liebert
Liebert
Plug UPS into AC
Press ON Button
for 2 seconds
5
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
The PowerSure Personal UPS requires very little maintenance. The batteries
are valve regulated, nonspillable, lead acid, and require that they be kept
charged to obtain their designed life. The UPS continuously charges the
batteries when connected to the utility supply.
When storing the UPS for any length of time, it is recommended to plug in the
UPS for at least 24 hours every four to six months to ensure full recharge of the
batteries.
FUSE REPLACEMENT PROCEDURES
AC Inlet
Insert flat blade screw
driver into slot and pull
fuse holder out to remove
Fuse Holder
Input Fuse
Spare Fuse
CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the
input cord from the AC input power supply and from the UPS.
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and
pulling out as indicated in the figure above.
2. Remove the input fuse.
3. Remove the spare fuse from its position by using the screwdriver to push it
out.
4. Place spare fuse in the input fuse position, and replace the fuse holder. The
fuse holder will lock into position.
5. Reconnect the input power lead to the UPS, and the input power lead to the
input AC supply.
6. Restart the UPS. The UPS is ready for normal operation.
Personal Model #
PSP300-115
Fuse Type
5A / 125V
6A / 125V
PSP500-115
6
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATIONS
The PowerSure™ Personal UPS contains a standard DB-9 receptacle located on
the rear of the UPS unit. Several signals are provided on this port and are
assigned as follows:
PIN
1
2
ASSIGNMENT DESCRIPTION
Low Battery (open collector)
No connection
3
No connection
4
5
6
7
On Battery Mode Shutdown (5-12 DC)
On Battery Mode Shutdown Return
Utility Fail / Normally On (open collector)
Low Battery (open emitter)
8
9
Utility Fail (common) (pins 6 & 9)
Utility Fail / Normally Off (open collector)
Pin Assignment
Collector to Emitter*
Open Collector
(+)
(-)
Open Emitter
*Maximum voltage and current on pins 1, 6, 7, 8, 9 is 60V DC; 5.0 mA.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
If the UPS fails to operate properly, turn off the unit and repeat the steps in the
installation section of this manual. If the problem persists, refer to the chart
below:
PROBLEM
CAUSE
SOLUTION
UPS will not start
Overload/Short Circuit
Check fuse at rear of UPS. If blown, replace it
and restart the UPS. For further help, call your
Liebert representative
UPS starts on
battery, but will
not switch to AC
UPS not plugged in
Fuse blown
Plug in power cord securely
Replace fuse and restart UPS
Call a qualified electrician
Power not available at
utility receptacle
Input voltage below
threshold
Wait until voltage rises to appropriate level
Voltage must be higher than 90 VAC
AC overvoltage
AC voltage must be less than 132 VAC
UPS shuts down
Overload/Short Circuit
Check the fuse holder at rear of UPS. If fuse is
blown, replace it and restart the UPS. If problem
persists, disconnect some of the equipment from
your UPS - the total wattage of your equipment
may exceed the capacity of the UPS. For
further help, call your Liebert representative
Low Battery
Turn OFF equipment and recharge UPS battery
for at least 7 to 10 hours. If problem persists,
contact your Liebert representative
Sitenet 1 Shutdown
Consult the Sitenet 1 User Manual or contact
your LAN administrator
8
Download from Www.Somanuals.com. All Manuals Search And Download.
LED & ALARM INDICATIONS
Startup
Mode
Green
Red
Alarm
Action
Press ON
button for
2 seconds
Flash
1-2 sec.
Flash
1-2 sec.
Beep
1-2 sec.
UPS Start
AC Mode
Mode
Green
ON
Red
OFF
Flash 10 sec.
every 4 min.
Flash every
0.5 sec
Alarm
OFF
Flash 10 sec.
every 4 min.
2 Beeps every
0.5 sec
Indicates
UPS is on-line
Battery
Fault
Reduce loads
AC Normal
Check Battery
Overload
ON
ON
Continuous
Beep
UPS Fault
ON
ON
UPS Failure
Battery Mode
Mode
Green
Flash
every 3 sec
Flash
every 3 sec
Flash
Red
Alarm
Beep
every 3 sec
Continuous
Beep
Indicates
UPS is on
Battery
Back Up
OFF
UPS Fault
ON
OFF
OFF
No Output
Low Battery
Warning
Low Battery
Shutdown
Overload
Warning
Beep
every 0.5 sec
UPS is about
to shutdown
UPS
every 0.5 sec
Flash
5 sec
Flash
Beep
5 sec
2 Beeps
every 0.5 sec
Continuous
Beep
Shutdown
Flash
every 0.5 sec
Reduce loads
every 3 sec
Overload
Shutdown
Reduce loads
& restart
OFF
ON
Shutdown
Mode
Green
Red
Alarm
Action
Press ON
button for
2 seconds
UPS
Shutdown
OFF
OFF
OFF
9
Download from Www.Somanuals.com. All Manuals Search And Download.
115V SPECIFICATIONS
Model Number
PSP300-115
300 / 180
PSP500-115
500 / 300
Model Rating VA / W
DIMENSIONS: in (mm)
Unit H x W x D
7.0 x 3.0 x 9.4
(178 x 76 x 238)
10.6 x 4.3 x 12.3
(270 x 110 x 312)
7.0 x 3.0 x 9.4
(178 x 76 x 238)
10.6 x 4.3 x 12.3
(270 x 110 x 312)
Shipping H x W x D
WEIGHT: lbs (kg)
Unit
Shipping
6.2 (2.8)
7.7 (3.5)
8.0 (3.6)
9.5 (4.3)
INPUT AC PARAMETERS
Voltage Range
90-132 VAC
without Battery Operation
Low Line Transfer
High Line Transfer
Frequency
90 VAC
132 VAC
45-55 Hz or 54-66 Hz; auto sensing
Input Power Cord
6 ft. detachable, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles
Voltage (Battery Mode)
Output Current
(4) 5-15R
115 VAC + 5%
2.6 A
4.3 A
Waveform (Battery Mode)
Frequency
Stepped Sinewave
50 Hz or 60 Hz; auto sensing
Overload Warning
101 – 120%
(Utility and Battery Modes)
Overload Shutdown
(Utility and Battery Modes)
Overload Warning
+ (15 – 25 W)
Overload Warning
+ (20 – 45 W)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
(1) x 12V x 4.5 Ah
Quantity x Voltage x
Rating
(1) x 12V x 7.0 Ah
Approved Battery
Manufacturers:
Transfer Time
Back-up Time:
Full load
CSB, Panasonic, BB Battery, and Yuasa
2 – 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries:
> 4 minutes
12 minutes
Half load
Recharge Time
7-10 hours to 90% capacity, after full discharge into 100% resistive
load
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Audible Noise
+32° F to + 104° F (0° C to +40° C)
+5° F to + 122° F (-15° C to +50° C)
0% to 90%, non-condensing
Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating
< 40 dBA, at 1 meter
AGENCY
Safety
UL 1778, c-UL Listed
Surge
IEEE C62.41 Category A
ESD
IEC 801-2, Level 3, Criterion< 2
IEC 801-3, Level 3, Criterion< 2
IEC 801-4, Level 4, Criterion< 2
Susceptibility
Electrical Fast
Transient/Burst
Emissions
FCC Part 15, Subpart B, Class B
ISTA Project 1A
Transportation
10
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser
and to its customer (collectively referred to as the "Purchaser"): the enclosed
Uninterruptible Power System (UPS) and components are free from defects in
materials and workmanship under normal use, service, and maintenance FOR A
PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from
Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS THE
ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED, EXPRESS
OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not
applicable to consumer products acquired by individuals and used for personal,
family, or household purposes (as distinguished from industrial or other purposes).
Local laws may not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you. This warranty gives you specific legal rights,
and you may have other rights which vary according to local law.
Certain repairs or services are the responsibility of the Purchaser and the Purchaser
is expected to pay for them. This warranty does not extend either to products with
removed or altered serial numbers or to any losses or damages due to act of God or
source external to the product, misuse, accident, abuse, neglect, negligence,
unauthorized modification, alteration, or repair, use beyond rated capacity, or
improper installation, maintenance, application or use, including, without limitation,
use in a manner contrary to the accompanying instructions or applicable codes.
WARNING: Warranty is void if the battery is allowed to discharge below the minimum
battery cutoff point. To prevent such discharge DO NOT leave the unit power switch
"ON" for more than two (2) days without AC power being supplied to the UPS. The
battery must be recharged every four (4) to six (6) months when not in use.
If the UPS fails to conform with the above warranty within the two year warranty
period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or
replacements are warranted for the remainder of the original warranty period. To
make a warranty claim, purchaser should call a Liebert Representative to obtain a
Returned Goods Authorization number and shipping instructions. Return
transportation costs to Liebert are the responsibility of the Purchaser.
"LIFE SUPPORT" POLICY
This product is not recommended, and the Company will not knowingly sell this
product, for use with life support and other designated "critical" devices. ANY SUCH
USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL
WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY,
IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, AND
EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY
AFFIRMATION OR PROMISE, FOR THIS PRODUCT AND THE USER AGREES
THAT IN NO EVENT SHALL THE COMPANY BE LIABLE FOR CONSEQUENTIAL
OR INDIRECT DAMAGES.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
POWERSURE™ PERSONAL
300- 500 VA
115V
Technical Support
U.S.A.
1-800-222-5877
Outside the U.S.A.
+1 614-841-6755
+44 1628 403 200
+33 1 4 360 26 19
+49 21669649340
+39 2 98250 1
+00 31 475 504050
+614-841-5471
U.K.
France
Germany
Italy
Netherlands
E-mail
Web site
Worldwide FAX tech support
The Company Behind The Products
With more than 500,000 installations around
the globe, Liebert is the world leader in
While every precaution has been taken
to ensure accuracy and completeness of
this literature, Liebert Corporation
computer protection systems.
Since its
founding in 1965, Liebert has developed a
complete range of support and protection
systems for sensitive electronics:
assumes
no
responsibility,
and
disclaims all liability for damages
resulting from use of this information or
for any errors or omissions.
•
•
•
Environmental systems: close-control air
conditioning from 1.5 to 60 tons.
Power conditioning and UPS with power
ranges from 250 VA to more than 1000 kVA.
© 2001 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without
notice.
Integrated
systems that provide both
environmental and power protection in
single, flexible package.
a
®
Liebert and the Liebert logo are
registered trademarks of Liebert
•
•
Monitoring and control — on-site or remote —
from systems of any size or location
Service and support, through more than 100
service centers around the world, and a 24-
hour Customer Response Center.
Corporation. All names referred to are
trademarks or registered trademarks of
their respective owners.
SL-23265 (2/01) Rev. 2
12