Lincoln Impact Driver 1100 000 A SERIES SN 2038615 BELOW User Manual

SERVICE MANUAL  
(INTERNATIONAL)  
IMPINGER COUNTERTOP OVEN  
MODEL 1100-000-A SERIES  
(SN 2038615 & BELOW)  
SERVICE MANUAL  
Lincoln Foodservice Products, LLC  
1111 North Hadley Road  
Fort Wayne, Indiana 46804  
United States of America  
Phone: (800) 374-3004  
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735  
Technical Service Hot Line  
(800) 678-9511  
1100advexport  
REV 1/5/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEQUENCE OF OPERATIONS  
MODEL 1164-000-EA  
400/230 VAC  
50 HZ.  
3 PHASE  
POWER SUPPLY  
Electrical power to be supplied to the oven by a four conductor service.  
Brown conductor is Hot.  
Black conductor is Hot.  
Black conductor is Hot.  
Green conductor is ground.  
CONTROL BOX AUTO COOL DOWN  
When the temperature in the control box reaches 120° F, ± 3° (48.9°C, ± 1.7°C), the cooling fan thermostat will  
switch power to the control box cooling fan. The thermostat will interrupt power to the cooling fan when the control  
box temperature falls to 100° F, ± 3° (37.8°C, ± 1.7°C).  
MAIN FAN CIRCUIT  
Power is permanently supplied through the normally closed oven cavity hi-limit, through the 10A fuse, through the  
normally closed control box hi-limit thermostat, to the normally open main fan switch. Power is also supplied to the  
normally open cooling fan thermostat. Closing the main fan switch supplies 230 VAC to the main fan motor, the  
cooling fan motor, to the primary of the temperature display transformer and to the heat and conveyor circuits.  
HEAT CIRCUIT  
Closing the oven fan switch supplies 230VAC, through the normally open air pressure switch (closed by air  
pressure from the main fan) to the electronic temperature control. The 1K ohm temperature potentiometer is  
adjusted to desired temperature. The thermocouple will provide varying millivolts to the temperature control. The  
temperature control then supplies 230 VAC to the coil of the contactor at intermittent intervals to maintain the  
desired temperature. The heat lamp is energized with the contactor.  
CONVEYOR DRIVE  
Closing the oven fan switch supplies 230 VAC through the EMI filter to the motor control board. AC volts are  
converted to DC volts and are supplied to the conveyor motor at terminals A+ and A-. Adjustment of the speed  
control potentiometer will change resistance at terminals P1 and P2 varying the DC voltage to the motor. The  
speed of the conveyor motor will increase or decrease as the DC voltage from the board increases or decreases  
respectively.  
NOTE: The conveyor control uses a sensor and magnet, mounted on the conveyor motor, that senses the motor  
speed. Any change in motor load (± RPM) is detected by the sensor and the voltage to the motor is adjusted  
accordingly.  
TEMPERATURE DISPLAY  
Closing the main fan switch supplies 230 VAC to the primary of the temperature display transformer. The  
secondary of this transformer supplies 12 VAC to the temperature display. The thermocouple supplies DC  
millivolts to the temperature display. The display converts this millivolt reading to a temperature reading.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
SCHEMATIC DIAGRAM  
MODEL 1154-000-EA, 1155-000-EA  
4
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SCHEMATIC DIAGRAM  
MODEL 1164-000-EA  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDE  
GAS OVENS  
1154-000-EA  
1155-000-EA  
NAT. GAS 230VAC  
LP GAS 230VAC  
50 HZ.  
50 HZ.  
1 PHASE  
1 PHASE  
REFER TO PROPER SCHEMATIC FOR IDENTIFIED COMPONENTS  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming power supply  
EVALUATION  
Check breakers, reset if required. Check power  
plug to be sure it is firmly in receptacle.  
Measure incoming power, call power co. if  
needed  
Fuse, 10A  
Check, replace if necessary.  
Check, replace if necessary.  
Fuse holder  
Hi-limit thermostat, control  
box  
Check for voltage on both sides of the switch.  
Terminals are normally closed. If open, reset  
and test oven for proper operation. If  
thermostat will not hold, and control box  
temperature is not exceeding 140° F (60° C)  
replace thermostat.  
Main fan switch  
Main fan motor  
With power off, Check continuity between  
switch terminals. Replace as needed.  
Check for opens, shorts or grounds. With  
power off, turn fan blade to check for locked  
rotor.  
Capacitor  
Check for shorts or grounds.  
WARNING: Capacitor has a stored charge,  
discharge before testing.  
No control box cooling  
Incoming power supply  
Main fan switch  
Cooling fan  
Check main circuit breakers, reset if required.  
Call power co. if needed.  
With power off, Check continuity between  
switch terminals. Replace as needed.  
Line voltage should now be at the cooling fan.  
If voltage is present, check motor for shorts or  
opens. With power off, check for locked rotor.  
Check main circuit breakers, reset if required.  
Call power co. if needed.  
Check the cooling fan thermostat (thermostat  
closes at 120° F and opens at 100° F). With the  
cooling fan thermostat preheated, check for  
continuity. If switch is open, replace thermostat.  
Check for adequate gas supply and be sure  
that manual gas shut off valve is open. Also  
check flexible gas line connection.  
No automatic control box  
cooling  
Incoming power supply  
Cooling fan thermostat  
Oven will not heat  
Gas supply  
Main fan  
Gas pressure switch  
If not operating, refer to “Main fan will not run”  
This switch is located inside the gas valve and  
should close when gas pressure is present.  
WITH POWER OFF: Remove 3 prong plug (on  
gas valve) and measure continuity between  
terminals 2 and 3. If no continuity, check the  
following: Proper gas pressure supply to gas  
valve as marked on the oven specification  
plate. Check for proper adjustment of gas  
pressure switch, 10 for Nat. gas, 27 for LP gas  
or 4.5 for town gas. Check the filter in gas  
valve for blockage or damage. If above checks  
are okay, but pressure switch is still not closed,  
replace gas valve.  
6
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air pressure switch  
Check air switch terminals for supply voltage to  
terminals NO 2 and COM. If voltage is present  
on one side only, check for air tube blockage or  
misalignment. If these are okay, adjust switch  
or replace if necessary.  
Oven cavity hi-limit  
thermostat  
Terminals are normally closed, opens at 660° F  
(350° C). If open, push in reset button and  
retest. If thermostat will not hold for maximum  
oven temperature, and oven is not exceeding  
temperature dial setting, check for proper  
location of capillary bulb in its spring holder. If  
above checks are okay, replace hi-limit  
thermostat.  
Ignition control  
Check for proper supply voltage to ignition  
control. Check for proper line voltage to the  
burner blower motor. This can be checked at  
motor connecting plug terminals 2 and 5. If  
voltage is present, proceed with next step, if  
not, wait 30 seconds, push reset button and try  
to restart. If this fails, check wires from  
thermostat and burner blower motor to the  
ignition control. If all above checks okay,  
replace ignition control.  
Burner blower motor  
Check for supply voltage to motor. WITH  
POWER OFF: Turn blower wheel to check for  
locked rotor. If proper supply voltage is present  
at motor connecting plug, terminals 2 and 5,  
and motor does not run, replace motor.  
Check for proper supply voltage switching from  
“NC” to “NO” on ignition control. Check for air  
switch adjustment, air tube blockage or  
misalignment. If these fail, replace air pressure  
switch.  
Air pressure switch  
(burner blower)  
Spark generator  
A pre-purge time of 30 to 60 seconds occurs  
after blower motor starts. Check for supply  
voltage at spark generator. If voltage is not  
present, check reset button for the ignition  
control. If voltage is still not present, replace  
ignition control. If there is input voltage but  
there is no output voltage, replace spark  
generator.  
Igniter/sensor assembly  
Gas valve  
Check this assembly for visible damage.  
Replace as needed. If there is no visible  
damage, check for supply voltage to  
igniter/sensor assembly. If there is supply  
voltage to igniter/sensor assembly, but there is  
no spark, replace igniter/sensor assembly.  
Gas valve should open when proper supply  
voltage is present. If no voltage is present,  
check the reset button on ignition control, and  
all connections for tightness. If there is still no  
voltage at gas valve, replace the ignition  
control. If there is voltage present, check for  
gas pressure at the gas pressure tap (located  
in the gas piping just prior to the burner). If  
there is no gas pressure, replace the gas valve.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flame will not stay on  
Flame sensor  
To check for flame sensor operation, connect a  
digital multimeter (capable of measuring DC  
microamps) between the flame sensor wire and  
terminal #1 on the ignition control. Sensor  
current is to be 3 microamps, minimum. If  
these readings are not achieved, replace  
igniter sensor assembly. Also, check for any  
type of damage to flame sensor wire and  
connections. NOTE: The DC microamp test  
must be conducted with the oven in low flame  
(bypass) operation.  
Power supply  
Ignition control  
Turn the temperature to the lowest temperature  
setting. If there is sufficient microamp current,  
but the flame will not stay lit, check for proper  
polarity of the power supply.  
If there is sufficient flame sensor current, but  
the burner will not remain ignited, check the  
reset button on ignition control. If all above test  
okay, replace ignition control.  
NOTE: Flame should be lit at  
this time  
Temperature control  
Low flame is on, but no main  
flame  
Check for supply voltage at terminal #7 to L2  
on temperature control. If there is no voltage,  
trace wiring back to oven fan switch. Turn the  
temperature adjustment knob to maximum  
temperature position and check for supply  
voltage at the load terminal #8 and L2. If  
voltage is present and unit is not heating, refer  
to “Temperature regulation valve” for next  
check. If voltage is not present, proceed.  
With power on and thermocouple leads  
attached to the temperature control board:  
Measure the DC millivolt output of these leads.  
Refer to thermocouple chart in “removal and  
installation” section for proper readings. If  
these readings are not achieved, replace  
thermocouple.  
Thermocouple  
Temperature potentiometer  
Disconnect the potentiometer leads from the  
temperature control board. Place ohmmeter  
test leads on the blue and green pot. leads.  
Reading should be 1K ohms. Place meter  
leads on the blue and purple pot. leads and  
rotate knob from high to low. Repeat on green  
and purple leads. Check for an even rise and  
fall of ohms reading to insure that there are no  
open or dead spots in the potentiometer.  
Check each lead to ground for any short  
circuits to ground. Replace as needed.  
Temperature regulation valve If supply voltage is present on the temperature  
control board at load terminals #8 and L2,  
check for voltage at temperature regulation  
valve. If voltage is present, listen for valve to  
open and close. Also check for opens or shorts  
in the operating coil. Replace as needed.  
Thermal overload of main fan The main fan motor and burner blower motor  
Intermittent heating  
and burner blower motors  
are equipped with internal thermal protection  
and will cease to operate if overheating occurs.  
As these motors overheat and then cool, the  
burners will cycle on and off intermittently.  
Improper ventilation or a lack of preventive  
maintenance may cause this condition. Also,  
8
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
most of the problems listed under “Oven will  
not heat” can cause intermittent failure.  
Check incoming power supply, If no voltage is  
present, check circuit breakers.  
With power off, Check continuity between  
switch terminals. Replace as needed.  
Conveyor will not run  
Power supply  
Fan switch  
Speed adjustment  
potentiometer  
This is a 0 to 10K ohm, 1 turn potentiometer.  
With power off, remove the black and white  
pot. leads from the motor control board at  
terminals P1 and P2. Place the meter leads on  
the black and white pot. leads. Rotating the  
pot. slowly, from low to high, the meter reading  
should show an even transition from 0 to 10K  
ohms ± 5%. There should be no dead or open  
spots throughout the rotation of the  
potentiometer. Check both pot. leads to  
ground. There should be no continuity to  
ground. If any of the above checks fail, replace  
the potentiometer.  
Check for supply voltage input to the control  
board at terminals L1 and L2. If voltage is not  
present, check wiring back to the oven fan  
switch. If supply voltage is present, check both  
fuses on control board (8A line and 1A  
armature). Check the DC voltage output at  
terminals A+ and A-. If there is power in to the  
control board but no power at A+ and A-, check  
the following:  
DC motor control board  
Hall effect sensor  
Disconnect the Hall effect sensor from the DC  
motor control board. If the motor begins to run,  
replace the Hall effect sensor.  
DC motor control board  
If, after disconnecting the Hall effect sensor,  
the motor is still not running, check for DC  
voltage from terminals A+ and A-. If there is no  
DC voltage, replace the DC motor control  
board.  
Circuit breaker  
If there is DC voltage output from the DC motor  
control board, but the motor is still not running,  
check the 0.4 Amp circuit breaker. Disconnect  
wires from the circuit breaker and check for  
continuity through the circuit breaker. Reset  
circuit breaker or replace as needed.  
Conveyor gearmotor  
Check the leads to the motor for evidence of  
any shorts or opens, and each lead to ground.  
If the motor fails the above tests, replace  
motor. Rotate motor shaft to determine if there  
is a locked rotor or a locked gearbox (use care  
so that magnet and sensor are not damaged).  
Check motor brushes for damage or excessive  
wear, replace brushes if needed. Replace  
motor if needed. Also check to be sure that the  
conveyor drive coupling is tight and properly  
engaged to the conveyor shaft.  
Conveyor  
Check for any mechanical misalignment. Also,  
check for worn bearings. A conveyor belt that is  
too tight may cause excessive bearing wear  
and sometimes, irregular speed.  
Conveyor speed unsteady  
Power supply  
Check power supply at the DC motor control  
board for supply voltage at terminals L1 and  
L2. Supply voltage should be steady.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Speed adjustment  
potentiometer  
This is a 0 to 10K ohm, 1 turn potentiometer.  
With power off, remove the black and white  
pot. leads from the motor control board at  
terminals P1 and P2. Place the meter leads on  
the black and white pot. leads. Rotating the  
pot. slowly, from low to high, the meter reading  
should show an even transition from 0 to 10K  
ohms ± 5%. There should be no dead or open  
spots throughout the rotation of the  
potentiometer. Check both pot. leads to  
ground. There should be no continuity to  
ground. If any of the above checks fail, replace  
the potentiometer.  
Check to insure that the magnet (cemented to  
shaft of conveyor drive motor) has not been  
damaged, or come loose from the motor shaft.  
Re-glue or replace as needed.  
Magnet  
Hall effect sensor  
Check for any physical damage to hall effect  
sensor (mounted on conveyor drive motor).  
Check all wiring and connections for damage.  
Replace as needed.  
Hall effect sensor cable  
DC motor control board  
Check continuity through the wires in the cable.  
Check all wiring and connections for visible  
damage. Replace as needed.  
With motor running, measure DC voltage  
across the red wire and black wire in the hall  
effect cable (all wires must be connected  
during this test). Voltage reading should be  
approx. 12VDC and steady. If this reading is  
not achieved, replace DC motor control board.  
With the motor running at maximum speed,  
measure the frequency across the white wire  
and the black wire in the hall effect cable (all  
wires must be connected during this test).  
Reading should be approx. 327 Hz. And  
steady. If there is no reading, replace hall effect  
sensor. If the reading is unsteady, calibrate the  
DC motor control board.  
Hall effect sensor  
Temperature display  
inoperative  
Display transformer  
Measure the transformer primary for supply  
voltage input. If voltage is not present, trace  
wiring back to the oven fan switch. Measure  
the secondary output, which will normally be  
12-15VAC. Voltage across terminals 1-3  
should be 12-15VAC. Terminals 1-2 and 2-3  
should be ½ the voltage reading 1-3. If the  
above secondary readings are not achieved,  
replace transformer.  
Temperature display  
Thermocouple  
If proper voltage is present at terminals 1,2 and  
3 on temperature display, but the display is not  
lighted, recheck all connections for tightness. If  
temperature display is still not operating,  
replace the temperature display.  
Place the thermocouple of a pyrometer into the  
center of the top finger. The pyrometer will  
indicate oven temperature. Measure DC  
millivolts of thermocouple at the temperature  
display. See thermocouple chart in “Removal  
and Installation” section for proper readings.  
Replace thermocouple if proper readings are  
not achieved. If readings are correct on the  
thermocouple, recalibrate or replace  
Temperature display  
inaccurate, or erratic  
10  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
temperature display.  
TROUBLESHOOTING GUIDE  
ELECTRIC OVENS  
MODEL 1164-000-EA  
400/230 VAC  
50 HZ.  
3 PHASE  
REFER TO PROPER SCHEMATIC FOR IDENTIFIED COMPONENTS  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming power supply  
EVALUATION  
Check circuit breakers. Reset if required. Call  
power company if needed.  
Oven cavity hi-limit  
thermostat  
Terminals are normally closed. If open, reset  
and test oven for proper operation. If  
thermostat will not hold for maximum oven  
temperature, and oven is not exceeding  
temperature dial setting, check for proper  
location of capillary bulb in its spring holder. If  
above checks okay, replace hi-limit thermostat.  
Check, replace if necessary.  
Fuse, 10 Amp  
Fuse holder  
Check, replace if necessary.  
Control box hi-limit thermostat Check for voltage on both sides of the switch.  
Terminals are normally closed. If open, reset  
and test oven for proper operation. If  
thermostat will not hold, and control box  
temperature is not exceeding 140° F (60° C)  
replace thermostat.  
With power off, Check continuity between  
switch terminals. Replace as needed.  
Check for opens, shorts or grounds. With  
power off, turn fan blade to check for locked  
rotor.  
Main fan switch  
Main fan motor  
Capacitor  
Check for shorts or grounds.  
WARNING: Capacitor has a stored charge,  
discharge before testing.  
No control box cooling  
Check for main fan operation. If not operating,  
refer to “Oven fan will not run”.  
Cooling fan  
Line voltage should now be at the cooling fan.  
If voltage is present, check motor for shorts or  
opens. With power off, check for locked rotor.  
Check circuit breakers. Reset if required. Call  
power company if needed.  
No automatic control box  
cooling  
Incoming power supply  
Oven cavity hi-limit  
thermostat  
Terminals are normally closed. If open, reset  
and test oven for proper operation. If  
thermostat will not hold for maximum oven  
temperature, and oven is not exceeding  
temperature dial setting, check for proper  
location of capillary bulb in its spring holder. If  
above checks okay, replace hi-limit thermostat.  
Check the cooling fan thermostat (thermostat  
closes at 120° F and opens at 100° F). With the  
cooling fan thermostat preheated, check for  
continuity. If switch is open, replace thermostat.  
Line voltage should now be at the cooling fan.  
If voltage is present, check motor for shorts or  
opens. With power off, check for locked rotor.  
This normally open thermostat should close at  
120°F (48.9°C) and reopen at 100°F (37.8°C).  
Replace as needed.  
Cooling fan thermostat  
Cooling fan  
Control box cooling fan  
continues to run  
Cooling fan thermostat  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oven will not heat  
Main fan motor  
Check for main fan operation. If fan is not  
operating, refer to "Oven fan will not run".  
This normally open switch should close when  
the main fan is activated. Check air switch tube  
for blockage or obstructions. Adjust switch if  
necessary (see “Removal and installation”  
section for instructions). Replace air pressure  
switch as needed.  
Air pressure switch  
Temperature control  
Thermocouple probe  
Check for supply voltage at temperature  
control. If no voltage is present, trace wiring  
back to air pressure switch. Turn the  
temperature adjustment knob to maximum  
temperature position and check for 230VAC at  
the load terminals #8 and neutral. If 230VAC is  
present and unit is not heating, refer to  
“Mercury contactor” for next check. If 230VAC  
is not present, proceed.  
With power on and thermocouple leads  
attached to the temperature control board:  
measure DC millivolt output of these leads.  
Refer to “Removal and installation” for proper  
readings. If these readings are not achieved,  
replace thermocouple.  
Temperature control  
potentiometer  
Disconnect the potentiometer leads from the  
control board. Place ohmmeter test leads on  
the blue and green pot. wires. Reading should  
be 1K ohms. Place meter leads across the blue  
and purple pot. leads and rotate knob from low  
to high. Repeat on green and purple leads.  
Check for an even rise and fall of ohms reading  
to insure that there are no open or dead spots  
in the potentiometer. Check each lead to  
ground for short circuits. Replace  
potentiometer as needed.  
Mercury contactor  
Heater elements  
Check for supply voltage to the contactor coil. If  
voltage is present and the contactor will not  
activate, replace the contactor. Also, check  
each contactor for proper high voltage input  
and output.  
Check the amp draw on each leg of the power  
supply for proper load. Check the oven  
specification plate for rating information. If the  
amp draw is low or high, check the individual  
elements for opens, shorts and proper  
resistance. WITH POWER OFF: To check  
resistance of the elements, remove all wires  
from the elements. The element resistance  
should be:  
230VAC – 33 ohms approx.  
Oven heats with switch off  
Intermittent heating  
Mercury contactor  
The mercury contactor has probably  
malfunctioned in the closed position. If there is  
no voltage to the operating coil, but there is  
high voltage at the contactor output, replace  
the mercury contactor.  
Thermal overload of main fan The main fan motor is equipped with internal  
motor  
thermal protection and will cease to operate if  
overheating occurs. As the motor overheats  
and then cools, the heat circuit will cycle on  
and off intermittently. Improper ventilation or a  
lack of preventive maintenance may cause this  
condition. Also, most of the problems listed  
12  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
under “Oven will not heat” can cause  
intermittent failure.  
Check incoming power supply, If no voltage is  
present, check circuit breakers.  
Conveyor will not run  
Power supply  
Fan switch  
With power off, Check continuity between  
switch terminals. Replace as needed.  
This is a 0 to 10K ohm, 1 turn potentiometer.  
With power off, remove the black and white  
pot. leads from the motor control board at  
terminals P1 and P2. Place the meter leads on  
the black and white pot. leads. Rotating the  
pot. slowly, from low to high, the meter reading  
should show an even transition from 0 to 10K  
ohms ± 5%. There should be no dead or open  
spots throughout the rotation of the  
Speed adjustment  
potentiometer  
potentiometer. Check both pot. leads to  
ground. There should be no continuity to  
ground. If any of the above checks fail, replace  
the potentiometer.  
Check for supply voltage input to the control  
board at terminals L1 and L2. If voltage is not  
present, check wiring back to the oven fan  
switch. If supply voltage is present, check both  
fuses on control board (8A line and 1A  
armature). Check the DC voltage output at  
terminals A+ and A-. If there is power in to the  
control board but no power at A+ and A-, check  
the following:  
DC motor control board  
Hall effect sensor  
Disconnect the Hall effect sensor from the DC  
motor control board. If the motor begins to run,  
replace the Hall effect sensor.  
DC motor control board  
If, after disconnecting the Hall effect sensor,  
the motor is still not running, check for DC  
voltage from terminals A+ and A-. If there is no  
DC voltage, replace the DC motor control  
board.  
Circuit breaker  
If there is DC voltage output from the DC motor  
control board, but the motor is still not running,  
check the 0.4 Amp circuit breaker. Disconnect  
wires from the circuit breaker and check for  
continuity through the circuit breaker. Reset  
circuit breaker or replace as needed.  
Conveyor gearmotor  
Check the leads to the motor for evidence of  
any shorts or opens, and each lead to ground.  
If the motor fails the above tests, replace  
motor. Rotate motor shaft to determine if there  
is a locked rotor or a locked gearbox (use care  
so that magnet and sensor are not damaged).  
Check motor brushes for damage or excessive  
wear. Replace brushes if needed. Replace  
motor if needed. Also check to be sure that the  
conveyor drive coupling is tight and properly  
engaged to the conveyor shaft.  
Conveyor  
Check for any mechanical misalignment. Also,  
check for worn bearings. A conveyor belt that is  
too tight may cause excessive bearing wear  
and sometimes, irregular speed.  
Conveyor speed unsteady  
Power supply  
Check power supply at the DC motor control  
board for supply voltage at terminals L1 and  
L2. Supply voltage should be steady.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Speed adjustment  
potentiometer  
This is a 0 to 10K ohm, 1 turn potentiometer.  
With power off, remove the black and white  
pot. leads from the motor control board at  
terminals P1 and P2. Place the meter leads on  
the black and white pot. leads. Rotating the  
pot. slowly, from low to high, the meter reading  
should show an even transition from 0 to 10K  
ohms ± 5%. There should be no dead or open  
spots throughout the rotation of the  
potentiometer. Check both pot. leads to  
ground. There should be no continuity to  
ground. If any of the above checks fail, replace  
the potentiometer.  
Check to insure that the magnet (cemented to  
shaft of conveyor drive motor) has not been  
damaged, or come loose from the motor shaft.  
Re-glue or replace as needed.  
Magnet  
Hall effect sensor  
Check for any physical damage to hall effect  
sensor (mounted on conveyor drive motor).  
Check all wiring and connections for damage.  
Replace as needed.  
Hall effect sensor cable  
DC motor control board  
Check continuity through the wires in the cable.  
Check all wiring and connections for visible  
damage. Replace as needed.  
With motor running, measure DC voltage  
across the red wire and black wire in the hall  
effect cable (all wires must be connected  
during this test). Voltage reading should be  
approx. 12VDC and steady. If this reading is  
not achieved, replace DC motor control board.  
With the motor running at maximum speed,  
measure the frequency across the white wire  
and the black wire in the hall effect cable (all  
wires must be connected during this test).  
Reading should be approx. 327 Hz. And  
steady. If there is no reading, replace hall effect  
sensor. If the reading is unsteady, calibrate the  
DC motor control board.  
Hall effect sensor  
Temperature display  
inoperative  
Display transformer  
Measure the transformer primary for supply  
voltage input. If voltage is not present, trace  
wiring back to the oven fan switch. Measure  
the secondary output, which will normally be  
12-15VAC. Voltage across terminals 1-3  
should be 12-15VAC. Terminals 1-2 and 2-3  
should be ½ the voltage reading 1-3. If the  
above secondary readings are not achieved,  
replace transformer.  
Temperature display  
Thermocouple  
If proper voltage is present at terminals 1,2 and  
3 on temperature display, but the display is not  
lighted, recheck all connections for tightness. If  
temperature display is still not operating,  
replace the temperature display.  
Place the thermocouple of a pyrometer into the  
center of the top finger. The pyrometer will  
indicate oven temperature. Measure DC  
millivolts of thermocouple at the temperature  
display. See thermocouple chart in “Removal  
and Installation” section for proper readings.  
Replace thermocouple if proper readings are  
not achieved. If readings are correct on the  
thermocouple, recalibrate or replace  
Temperature display  
inaccurate, or erratic  
14  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
temperature display.  
REMOVAL, INSTALLATION AND ADJUSTMENT  
INTERNATIONAL IMPINGER II ADVANTAGE  
CAUTION!  
BEFORE REMOVING OR INSTALLING ANY COMPONENT IN THE IMPINGER  
OVEN, BE SURE TO DISCONNECT ELECTRICAL POWER AND GAS SUPPLY.  
MOTOR, MAIN FAN - REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove motor cover from back of oven.  
C. Remove wires for motor and mark for reassembly.  
D. Remove bolts from the oven back and slide oven back assembly straight out of the oven.  
E. Loosen bolt from fan hub and remove fan from motor shaft.  
NOTE: Measure distance from fan blade to rear wall assembly before removal to aid in reassembly.  
F. Remove the bolts from the motor mount and remove motor clamp. Slide the motor assembly out of the oven  
back.  
G. Remove motor by removing the four mounting nuts and washers.  
H. Reassemble in reverse order. When motor mount assembly is set on the oven back, align motor shaft in the  
center of the hole. Set fan assembly on the motor shaft.  
NOTE: It is recommended that anti-seize compound be applied to the bolts before assembly.  
MAIN FAN - REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove back assembly. (see “MOTOR, MAIN FAN”)  
C. Reinstall and locate fan so that the bottom of the fan spider is 1 ½ inches from the top of the oven back cone.  
(see drawing)  
CAPACITOR, MOTOR - REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control box cover and front panel.  
C. Discharge capacitor.  
D. Remove capacitor and reassemble in reverse order.  
ON/OFF SWITCH – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control box cover.  
C. Remove front panel.  
D. Depress spring clips on sides of switch and push switch out.  
E. Remove wires from switch, note wire numbers and location.  
F. Reassemble in reverse order and check system operation.  
NOTE: make sure that switch housing is fully seated in opening in control box.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FUSE HOLDER – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Remove wires from fuse holder and mark for reassembly.  
D. Remove mounting screws or mounting nut from fuse holder and remove fuse holder.  
E. Reassemble in reverse order and check system operation.  
THERMOSTAT, CONTROL BOX HI-LIMIT – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Remove wires from thermostat and mark for reassembly.  
D. Remove mounting screws and remove thermostat.  
E. Reassemble in reverse order and check system operation.  
NOTE: Push reset button on new thermostat.  
COOLING FAN, CONTROL BOX – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Remove four screws from fan frame.  
D. Disconnect cord and plug from fan and remove fan.  
E. Reassemble in reverse order and check system operation.  
THERMOSTAT, COOLING FAN – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Remove wires and mark for reassembly.  
D. Remove mounting screws and remove thermostat.  
E. Reassemble in reverse order and check system operation.  
BURNER BLOWER MOTOR – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Unplug motor connector.  
D. Remove three mounting screws at burner housing and remove motor.  
E. Remove air shutter assembly from old motor and install on new motor.  
F. Reassemble in reverse order and check system operation.  
NOTE: Set air shutter at approximately ½ open and adjust to get a good blue flame in high flame operation.  
THERMOSTAT, OVEN CAVITY HI-LIMIT – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Remove conveyor and bottom finger assembly.  
D. Remove capillary tube from mounting bracket in oven chamber and pull through tube into control box.  
E. Remove wires from thermostat and mark for reassembly.  
F. Remove mounting nut and remove thermostat.  
G. Reassemble in reverse order and check system operation. Make sure capillary tube is mounted in the  
mounting bracket.  
NOTE: Push reset button on new thermostat.  
16  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMOCOUPLE – REPLACEMENT  
A. Shut off power at main breaker.  
B. Remove control panel top and front cover.  
C. Remove conveyor and bottom finger assembly.  
D. Remove thermocouple from mounting bracket in oven chamber, pull through tube into control box.  
E. Remove two thermocouple wires from temperature control and mark for reassembly.  
F. Reassemble in reverse order and check system operation.  
THERMOCOUPLE MEASUREMENT CHART  
INFORMATION:  
When two wires composed of dissimilar metals are joined together and one of the ends is heated, a  
continuous current flow as generated. We use an iron constant (type J) thermocouple. The iron wire  
increases the number of dissimilar junctions.  
It is possible to check a thermocouple with a properly calibrated D. C. millivolt meter. At 32°F, the millivolt  
reading should be 0.00. Inserting the thermocouple into an ice bath can check this.  
The millivolt reading at 72°F should be 1.134.  
When using the following chart, the temperature at the terminal connections must be noted. This  
temperature is called the junction temperature.  
The following chart lists the thermocouple millivolt readings from 200°F to 600°F.  
Thermocouple Measurement Chart:  
Explanation: The junction temperature is the ambient air temperature where the thermocouple fastens to  
the electronic temperature control board.  
O
V
E
N
T
E
M
P
200°F 250°F 300°F 325°F 350°F 400°F 425°F 450°F 500°F 550°F 600°F  
J
90°F 3.26 4.77 6.30 7.06 7.83  
88°F 3.32 4.83 6.36 7.12 7.89  
86°F 3.37 4.88 6.41 7.17 7.94  
84°F 3.43 4.94 6.47 7.23 8.00  
82°F 3.49 5.00 6.53 7.29 8.06  
80°F 3.55 5.06 6.59 7.35 8.12  
78°F 3.60 5.11 6.64 7.40 8.17  
76°F 3.66 5.17 6.70 7.46 8.23  
75°F 3.69 5.20 6.73 7.49 8.26  
74°F 3.72 5.23 6.76 7.52 8.29  
72°F 3.78 5.29 6.82 7.58 8.35  
70°F 3.83 5.34 6.87 7.63 8.40  
9.37 10.14 10.91 12.46 14.00 15.53  
9.43 10.20 10.97 12.51 14.05 15.59  
9.49 10.26 11.03 12.57 14.11 15.65  
9.54 10.31 11.09 12.63 14.19 15.71  
9.60 10.37 11.14 12.69 14.23 15.76  
9.66 10.43 11.20 12.74 14.28 15.82  
9.72 10.49 11.26 12.80 14.34 15.86  
9.77 10.55 11.32 12.86 14.40 15.94  
9.80 10.57 11.35 12.89 14.43 15.97  
9.83 10.60 11.37 12.92 14.46 15.99  
9.89 10.66 11.43 12.97 14.51 16.05  
9.95 10.72 11.49 13.03 14.57 16.11  
U
N
C
T
I
O
N
T
E
M
P
68°F 3.89 5.40 6.93 7.69 8.46 10.00 10.78 11.55 13.09 14.63 16.17  
66°F 3.95 5.46 6.99 7.75 8.52 10.06 10.83 11.61 13.15 14.69 16.23  
64°F 4.01 5.52 7.05 7.81 8.58 10.12 10.89 11.66 13.20 14.74 16.28  
62°F 4.06 5.57 7.10 7.86 8.63 10.18 10.95 11.72 13.26 14.80 16.34  
60°F 4.12 5.63 7.16 7.92 8.69 10.24 11.01 11.78 13.32 14.86 16.40  
ELECTRONIC TEMPERATURE CONTROL – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect all wiring and mark for reassembly.  
Depress nylon clips and remove electronic temperature control from mounting bracket.  
Reassemble in reverse order and check system operation.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRONIC TEMPERATURE CONTROL – CALIBRATION  
.
.
Place the thermocouple of your test meter through a finger hole in the top center of the oven.  
With temperature dial fully counter clockwise, align red line on dial over the “CAL” mark on temperature scale  
and tighten dial knob.  
.
Turn temperature dial fully clockwise, adjust pot on temperature control to achieve 575° F on temperature  
meter. (There are two adjustment pots on control, adjust pot that is closest to the edge of the board.)  
Set dial to 500° F. Adjust dial to match actual temperature.  
.
.
Seal adjustment pot with glyptol or nail polish.  
TEMPERATURE CONTROL POTENTIOMETER – REPLACEMENT  
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Loosen two allen screws and remove knob by sliding off shaft.  
Remove mounting nut from potentiometer shaft and remove potentiometer.  
Disconnect potentiometer wires from temperature control and mark for reassembly.  
Reassemble in reverse order and check system operation.  
HEAT LIGHT – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove two wires from light and mark for reassembly.  
Grasp body of light and slide sideways to remove light.  
Reassemble in reverse order and check system operation.  
IGNITION CONTROL – REPLACEMENT  
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove front portion of control from base by releasing tabs on sides of control and pulling control from base.  
Remove wires from terminal strip on control base and mark for reassembly.  
Remove two mounting screws and remove control base.  
Reassemble in reverse order and check system operation.  
GAS VALVE – REPLACEMENT AND ADJUSTMENT  
.
.
.
.
.
.
.
.
Shut off power at main breaker and disconnect gas supply.  
Disconnect gas piping from back of unit.  
Remove four screws from the incoming piping nipple mounting bracket. Remove incoming piping nipple.  
Remove all wires from gas valve and mark for reassembly.  
Disconnect pilot tube from gas piping. Disconnect pipe union and remove gas valve.  
Remove piping from gas valve.  
Reassemble in reverse order and check system operation. Check all gas line fittings for leaks.  
Check for proper adjustment of gas pressure switch. Switch should be set as follows: 10 on dial for Nat. gas,  
27 for LP or 4.5 for town gas. Adjust as needed.  
.
.
Check and adjust manifold pressure. Remove pressure tap at burner manifold and install manometer. Adjust  
gas pressure as follows: 3.5” WC for Nat. gas, 10” WC for LP or 2.0” WC for town gas.  
If needed, check gas filter by removing cover plate on side of gas valve and sliding filter out of valve.  
Reassemble in reverse order and check system operation. Check for gas leaks.  
18  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BYPASS ORIFICE – REPLACEMENT  
.
.
.
.
.
.
Shut off power at main breaker.  
Shut off gas supply to oven.  
Remove control panel top and front cover.  
Remove pilot tube from bypass orifice and remove orifice.  
Reassemble in reverse order and check system operation.  
Check gas line fittings for leaks.  
TEMPERATURE REGULATION VALVE – REPLACEMENT  
.
.
.
.
.
.
.
.
Shut off power at main breaker.  
Shut off gas supply to oven.  
Remove control panel top and front cover.  
Remove bypass tube from burner.  
Disconnect wires from temperature regulation valve and mark for reassembly.  
Remove four nuts from burner manifold and disconnect pipe union.  
Remove temperature regulation valve and piping from oven.  
Remove piping from valve and reassemble in reverse order and check system operation. Check all gas line  
fittings for leaks.  
IGNITER/SENSOR ASSEMBLY – REPLACEMENT  
.
.
.
.
.
.
.
.
.
Shut off power at main breaker.  
Shut off gas supply to oven.  
Remove control panel top and front cover.  
Remove gas valve assembly.(see “GAS VALVE”)  
Remove temperature regulation valve. (see “TEMPERATURE REGULATION VALVE”)  
Disconnect all wires from burner and mark for reassembly.  
Remove screws from burner tube and remove burner venturi.  
Remove two mounting screws and remove igniter/sensor assembly from burner venturi.  
Reassemble in reverse order and check system operation. Check all gas line fittings for leaks.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BURNER ALARM – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove two wires from burner alarm and mark for reassembly.  
Remove mounting ring from burner alarm and remove from control box.  
Reassemble in reverse order and check system operation.  
SPARK GENERATOR – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front panel.  
Remove all wires from spark generator and mark for reassembly.  
Remove two mounting screws and remove spark generator.  
Reassemble in reverse order and check system operation.  
MAIN BURNER ORIFICE – REPLACEMENT  
.
.
.
.
.
.
Shut power at main breaker.  
Shut off gas supply to oven.  
Remove control panel top and front cover.  
Remove burner manifold. (See “TEMPERATURE REGULATION VALVE”)  
Remove main burner orifice from burner manifold.  
Reassemble in reverse order and check system operation. Check all gas line fittings for leaks.  
MERURY CONTACTOR – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect all wires from mercury contactor and mark for reassembly.  
Remove mounting screws and remove mercury contactor.  
Reassemble in reverse order and check system operation.  
AIR PRESSURE SWITCH – MAIN FAN - REPLACEMENT AND ADJUSTMENT  
.
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect all wires and mark for reassembly.  
Disconnect air switch tube from air pressure switch.  
Remove mounting screws and remove air pressure switch.  
Reassemble in reverse order and check system operation. Adjust air pressure switch as needed.  
To adjust air pressure switch, turn adjusting screw fully counter clockwise. With heat on, turn adjusting screw  
clockwise until heat shuts off. Turn adjusting screw ¼ turn counter clockwise and unit should heat.  
AIR PRESSURE SWITCH – BURNER MOTOR – REPLACEMENT AND CALIBRATION  
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect all wires and mark for reassembly.  
Remove air tube from air pressure switch and remove air pressure switch from hanger.  
Reassemble in reverse order and check system operation. Adjust air pressure switch as needed.  
To adjust air pressure switch, remove cover over terminals to access adjustment screw. To increase  
sensitivity, turn screw counter clockwise. Check for proper line voltage switching from N.C. to N.O. as the air  
pressure switch closes.  
HEATING ELEMENT – REPLACEMENT  
.
.
.
.
Shut off power at main breaker.  
Remove back cover.  
Disconnect motor wires and heating element wires and mark for reassembly.  
Remove oven back from oven.  
20  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
.
.
.
Remove fan shroud.  
Remove heating element(s) from oven back.  
Reassemble in reverse order and check system operation. Apply anti-seize compound to all mounting bolts  
on elements and back bolts.  
NOTE: Be sure all wiring connections are tight. Loose connections at on the elements may cause the  
terminals to burn off and damage the elements or wiring.  
CONVEYOR CONTROL POTENTIOMETER – REPLACEMENT  
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Loosen two allen screws and remove knob by sliding knob off of shaft.  
Remove mounting nut from potentiometer shaft and remove potentiometer.  
Disconnect potentiometer wires and mark for reassembly.  
Reassemble in reverse order and check system operation.  
CONVEYOR CONTROL BOARD – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect wiring from conveyor control board and mark for reassembly.  
Remove conveyor control board from its mounting bracket.  
Reassemble in reverse order. Calibrate new conveyor control board and check system operation.  
NOTE: Be sure that jumper (on conveyor control) is set to the proper input voltage (120/240) position.  
CONVEYOR CONTROL BOARD – CALIBRATION  
.
.
Connect digital voltmeter to the hall effect sensor. Black meter lead connected to black hall effect sensor lead,  
red meter lead to white hall effect sensor lead.  
Turn conveyor control knob fully counter clockwise. Loosen knob and align with calibration mark and tighten  
knob.  
.
.
Set conveyor control knob to the 1-minute setting. Adjust “MAX” pot on conveyor control to 327.5Hz.  
Set conveyor control knob to the 30-minute setting. Adjust “MIN” pot on conveyor control to 10.9 Hz. Recheck  
at 1 minute and 30 minute settings until proper readings are achieved. Seal pots with glyptol or nail polish.  
CIRCUIT BREAKER – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect two wires from circuit breaker and mark for reassembly.  
Remove mounting nut from circuit breaker and remove circuit breaker.  
Reassemble in reverse order and check system operation.  
NOTE: Be sure to reset circuit breaker before operation.  
CONVEYOR DRIVE MOTOR – REPLACEMENT  
.
.
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove conveyor.  
Disconnect wiring from motor and mark for reassembly.  
Remove coupling from motor drive shaft.  
Remove four mounting screws and remove conveyor motor and mounting bracket.  
Remove mounting bracket from conveyor motor.  
Reassemble in reverse order and check system operation.  
REVERSING CONVEYOR DIRECTION  
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Reverse wires fastened to terminals A+ and A- on conveyor control board. (See schematic diagram for wire  
numbers.)  
Reassemble in reverse order and check system operation.  
.
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HALL EFFECT SENSOR – REPLACEMENT  
.
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove conveyor motor assembly (see “CONVEYOR DRIVE MOTOR”).  
Remove two mounting screws and remove sensor and bracket from conveyor motor.  
Remove Hall effect sensor from mounting bracket.  
Reassemble in reverse order and check system operation.  
TEMPERATURE DISPLAY TRANSFORMER – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove all wires from transformer and mark for reassembly.  
Remove two mounting screws and remove transformer.  
Reassemble in reverse order and check system operation.  
TEMPERATURE DISPLAY – REPLACEMENT  
.
.
.
.
.
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove wires from temperature display and mark for reassembly.  
Gently pry temperature display from mounting tabs to remove display. (This is a pressure fit.)  
Reassemble in reverse order and check system operation.  
TEMPERATURE DISPLAY – CALIBRATION  
.
Place the thermocouple of your test meter through a finger hole in the top center of the oven. Pre- heat the  
oven to 500°F for 30 minutes.  
B. Set switch on back of temperature display to read desired temperature (°F or °C).  
C. Adjust “temp adj.” on back of temperature display until display matches actual oven temperature.  
BEARING, CONVEYOR – REPLACEMENT  
A. Remove conveyor from oven and place on a flat work surface.  
B. Remove connecting links from conveyor belt and remove belt from conveyor frame.  
C. Move drive shaft or idler shaft toward end of conveyor, and bearing will now slip out of holding bracket.  
D. Remove bearing from shaft.  
E. Reassemble in reverse order and check system operation.  
22  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This page intentionally left blank.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL VIEW  
IMPINGER II ADVANTAGE  
LETTER  
PART NUMBER  
DESCRIPTION  
A
B
C
369390  
369502  
Caster, 4” with mounting plate  
Bottom finger cover  
Columnating plate, see Installation Operations  
manual  
D
E
F
370010  
369504  
Bottom finger housing  
Top finger housing  
Columnating plate, see Installation Operations  
manual  
G
H
I
J
K
L
M
N
O
P
369503  
369511  
369659  
369225  
369211  
370118  
369231  
369232  
369919  
370066  
Top finger cover  
Oven top  
Conveyor hole cover  
Baffle  
Thumb screw  
Cross support  
Caster, 4” with threaded stem  
Adjustable leg  
Stand side  
Plug  
24  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROL BOX VIEW  
IMPINGER II ADVANTAGE  
MODELS 1154-000-EA, 1155-000-EA  
LETTER  
PART NUMBER  
370108  
369467  
370073  
370107  
370214  
369316  
350224  
369432  
369809  
369449  
369378  
369579  
369131  
370061  
DESCRIPTION  
Control box top  
Pilot light  
Temperature display  
Side panel  
Operation label  
Knob  
Lens, yellow  
On/off switch  
Conveyor potentiometer  
Temperature potentiometer  
Cooling fan  
Solid state alarm  
Thermocouple  
Conveyor motor assembly,  
includes “O” and “P”  
Hall effect sensor  
Magnet, 16 pole  
Manifold, burner  
Venturi, natural gas  
Venturi, LP gas  
Igniter/sensor assembly  
Temperature regulation valve  
Burner blower motor  
Air shutter assembly  
Transformer, temperature display  
Gas valve  
Bypass orifice, natural gas  
Bypass orifice, LP gas  
Ground lug  
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
369823  
370065  
369901  
369654  
369939  
369590  
370186  
369589  
369401  
369173  
369580  
370031  
369557  
353082  
370064  
357067  
369192  
369573  
369507  
369431  
369465  
370177  
369856  
369014  
357107  
369331  
369566  
369524  
369771  
369689  
369575  
369025  
369574  
370178  
369376  
369698  
370176  
370184  
S
T
U
V
W
X
Y
Z
AA  
BB  
CC  
DD  
EE  
FF  
GG  
HH  
II  
Circuit breaker, 0.4 A  
Thermostat, oven cavity hi-limit  
Capacitor  
Ignition control  
Thermostat, cooling fan  
Thermostat, control box hi-limit  
Electronic temperature control  
Conveyor control  
Stand-off, support  
Fuse, 10A  
JJ  
KK  
LL  
Fuse holder  
Finger guard  
MM  
Main burner orifice, natural gas  
Main burner orifice, LP gas  
Reset switch, ignition control  
Plug, pressure test  
Air pressure switch, Dungs  
Air pressure switch, Johnson  
Spark generator  
Junction box  
Terminal block, 3 pole  
Cover  
NN  
OO  
PP  
QQ  
RR  
SS  
TT  
UU  
VV  
Filter, E.M.I.  
Filter, R.F.I.  
26  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROL BOX VIEW  
IMPINGER II ADVANTAGE  
MODEL 1164-000-EA  
LETTER  
A
PART NUMBER  
DESCRIPTION  
Control box top  
Pilot light  
Temperature display  
Side panel  
Operations label  
Knob  
Lens, yellow  
370108  
369467  
370073  
370107  
370214  
369316  
350224  
369432  
369809  
369449  
370065  
369823  
370061  
369131  
369378  
369479  
370173  
369575  
369431  
369507  
369465  
369856  
370177  
369192  
369368  
370064  
369698  
370178  
370177  
357107  
369014  
369331  
370176  
353082  
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
AA  
BB  
CC  
DD  
EE  
FF  
GG  
HH  
On/off switch  
Conveyor potentiometer  
Temperature potentiometer  
Magnet, 16 pole  
Hall effect sensor  
Conveyor motor assembly, includes “K” and “L”  
Thermocouple  
Cooling fan  
Mercury contactor, 3 pole  
Transformer, temperature display  
Air pressure switch  
Thermostat, control box hi-limit  
Thermostat, cooling fan  
Electronic temperature control  
Stand-off, support  
Conveyor control  
Capacitor  
Thermostat, oven cavity hi-limit  
Circuit breaker  
Electric box  
Electric box cover  
Terminal block  
Fuse holder  
Fuse, 10A  
Finger guard  
Filter, E.M.I.  
Ground lug  
28  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONVEYOR/DOOR VIEW  
IMPINGER II ADVANTAGE  
LETTER  
PART NUMBER  
DESCRIPTION  
Coupler  
Coupling center  
Ball plunger  
Set screw  
Crumb pan, right  
Crumb pan, left  
Conveyor frame assembly  
Pan stop  
Conveyor bearing  
Idler shaft  
A
B
C
D
E
F
G
H
J
369611  
369664  
369269  
370116  
369223  
369224  
369666  
369226  
369516  
369514  
369515  
369978  
369238  
369513  
369510  
370016  
369501  
1123D  
K
L
Sprocket  
Set screw  
Drive shaft  
Hinge  
M
N
O
P
Q
R
S
Door assembly, includes “N”, “P” and “Q”  
Impinger nameplate  
Door latch & catch  
Door with window, includes “N”, “P” and “Q”  
Window frame top  
Glass, access window  
Window frame bottom  
Retainer, window  
Splice clip, conveyor belt  
Conveyor belt, complete  
Conveyor belt, 1ft. section  
369927  
369925  
369926  
369929  
369165  
369194  
369394  
T
U
W
X
Y
30  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVEN BACK VIEW  
IMPINGER II ADVANTAGE  
LETTER  
PART NUMBER  
DESCRIPTION  
Fan  
Fan shroud  
Stand-off  
Heating element, 230 volt  
Rear wall  
A
B
C
D
E
F
G
H
I
369182  
369899  
369655  
370164  
369549  
369581  
369196  
369695  
369033  
369681  
369979  
369227  
369541  
Motor mount  
Motor, 240 volt, 50Hz.  
Bracket, motor  
Clamp, motor  
Cover, back  
Bracket, hi-limit thermostat  
Spring  
J
K
L
M
Thermocouple bracket  
32  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This page intentionally left blank.  
34  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This page intentionally left blank.  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
36  
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lennox Hearth Indoor Fireplace RDI 42 User Manual
Leviton Switch RZCZ1 User Manual
Lincoln Electric Welding System 350 SA User Manual
Makita Impact Driver 6907DW User Manual
Marantz Projector VP4001 User Manual
Mark Levinson Stereo Amplifier JC 2 User Manual
Mazda Automobile 2007 SPEED6 User Manual
Memorex Computer Drive 53958662 User Manual
Memorex MP3 Player MC2862 User Manual
Metra Electronics Car Stereo System 99 7310 User Manual