Lightning Audio Speaker 7532 User Manual

IOM027FVAE0804  
7532 Radar Tank Gauge  
Smart transmitter for continuous and non-contact precision  
level measurement. For custody transfer and inventory-control  
applications with NMI and PTB approval.  
Installation and  
Operations Manual  
www.varec.com  
Varec, Inc.  
5834 Peachtree Corners East, Norcross (Atlanta), GA 30092 USA  
Tel: +1 (770) 447-9202 Fax: +1 (770) 662-8939  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Radar Tank Gauge  
Table of Contents  
Table of Contents  
Safety Instructions ....................................4  
Commissioning .........................................45  
Identification ................................................7  
Maintenance ...............................................73  
Accessories ................................................75  
Troubleshooting .......................................77  
Mounting .....................................................11  
Wiring ............................................................25  
10 Technical data ...........................................87  
11 Appendix .....................................................91  
11.1 Operating menu HART (Display modul), ToF Tool  
91  
Operation .....................................................31  
Index.......................................................................103  
IOM027FVAE0804  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Instructions  
Radar Tank Gauge  
1
Safety Instructions  
1.1  
Designated use  
The Varec Model 7532 Radar Tank Gauge (RTG) is a compact radar level transmitter for  
the continuous, contactless measurement of liquids, pastes and sludge in stilling wells.  
The device can also be freely mounted outside closed metal vessels because of its  
operating frequency of about 6 GHz and a maximum radiated pulsed energy of 1mW  
(average power output 1 µW). Operation is completely harmless to humans and animals.  
1.2  
Installation, commissioning and operation  
The 7532 RTG has been designed to operate safely in accordance with current technical,  
safety and EU standards. If installed incorrectly or used for applications for which it is  
not intended, however, it is possible that application-related dangers may arise, e.g.  
product overflow due to incorrect installation or calibration. For this reason, the  
instrument must be installed, connected, operated and maintained according to the  
instructions in this manual: personnel must be authorised and suitably qualified. The  
manual must have been read and understood, and the instructions followed.  
Modifications and repairs to the device are permissible only when they are expressly  
approved in the manual.  
1.3  
Operational safety  
Hazardous areas  
Measuring systems for use in hazardous environments are accompanied by separate “Ex  
documentation”, which is an integral part of this Operating Manual. Strict compliance  
with the installation instructions and ratings as stated in this supplementary  
documentation is mandatory.  
• Ensure that all personnel are suitably qualified.  
• Observe the specifications in the certificate as well as national and local regulations.  
FCC-approval  
This device complies with part 15 of the FCC Rules. Operation is subject to the following  
two conditions: (1) This device may not cause harmful interference, and (2) this device  
must accept any interference received, including interference that may cause undesired  
operation.  
Caution!  
Changes or modifications not expressly approved by the part responsible for  
compliance could void the user’s authority to operate the equipment.  
4
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Safety Instructions  
1.4  
Return  
The following procedures must be carried out before a transmitter is sent to Varec for  
repair:  
• Always enclose a duly completed “Declaration of contamination” form. Only then can  
Varec transport, examine and repair a returned device.  
• Enclose special handling instructions if necessary, for example a safety data sheet as  
per EN 91/155/EEC.  
• Remove all residue which may be present. Pay special attention to the gasket grooves  
and crevices where fluid may be present. This is especially important if the fluid is  
dangerous to health, e.g. corrosive, poisonous, carcinogenic, radioactive, etc.  
Caution!  
• No instrument should be sent back for repair without all dangerous material being  
completely removed first, e.g. in scratches or diffused through plastic.  
• Incomplete cleaning of the instrument may result in waste disposal or cause harm to  
personnel (burns, etc.). Any costs arising from this will be charged to the operator of  
the instrument.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Safety Instructions  
Radar Tank Gauge  
1.5  
Notes on safety conventions and symbols  
In order to highlight safety-relevant or alternative operating procedures in the manual,  
the following conventions have been used, each indicated by a corresponding symbol in  
the margin.  
Safety conventions  
Symbol  
Meaning  
A warning highlights actions or procedures which, if not performed correctly,  
will lead to personal injury, a safety hazard or destruction of the instrument  
Warning!  
Caution highlights actions or procedures which, if not performed correctly,  
may lead to personal injury or incorrect functioning of the instrument  
Caution!  
Note!  
A note highlights actions or procedures which, if not performed correctly, may  
indirectly affect operation or may lead to an instrument response which is not  
planned  
Explosion protection  
Device certified for use in explosion hazardous area  
If the 7532 RTG has this symbol embossed on its name plate it can be  
installed in an explosion hazardous area  
0
-
Explosion hazardous area  
Symbol used in drawings to indicate explosion hazardous areas.  
– Devices located in and wiring entering areas with the designation  
“explosion hazardous areas” must conform with the stated type of  
protection  
Safe area (non-explosion hazardous area)  
Symbol used in drawings to indicate, if necessary, non-explosion  
hazardous areas.  
.
– Devices located in safe areas still require a certificate if their outputs run  
into explosion hazardous areas.  
Electrical symbols  
Direct voltage  
A terminal to which or from which a direct current or voltage may be  
applied or supplied  
%
&
Alternating voltage  
A terminal to which or from which an alternating (sine-wave) current  
or voltage may be applied or supplied  
Grounded terminal  
A grounded terminal, which as far as the operator is concerned, is  
already grounded by means of an earth grounding system  
)
*
Protective grounding (earth) terminal  
A terminal which must be connected to earth ground prior to making  
any other connection to the equipment  
Equipotential connection (earth bonding)  
A connection made to the plant grounding system which may be of  
type e.g. neutral star or equipotential line according to national or  
company practice  
+
6
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
7532  
Identification  
2
Identification  
2.1  
Device designation  
2.1.1  
Nameplate and Certification Plates  
The following technical data are given on the instrument nameplate:  
Figure 1: Information on the nameplate of the 7500 RTG (example)  
Figure 2: Information on the NMi type plate for custody transfer applications of the  
7500 RTG (example)  
Figure 3: Information on the PTB type plate for custody transfer applications of the  
7500 RTG (example)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Identification  
Radar Tank Gauge  
2.1.2  
Ordering structure  
Ordering structure 7532 RTG  
10  
Certificates  
Basic weight  
6.5 kg  
A
S
U
1
For non-hazardous areas  
FM  
CSA  
IS - Class I, Division 1, Group A-D  
IS - Class I, Division 1, Group A-D  
ATEX II 1/2 G EEx ia IIC T6, note safety instruction (XA) for electrostatic charg-  
ing!  
Y
Special version  
Antenna type  
20  
Additional  
weight  
Type  
Size  
Material  
SS316L  
SS316L  
SS316L  
SS316L  
SS316L  
SS316L  
SS316L  
SS316L  
Sealing  
A
B
E
Planar antenna DN150 / 6"  
Planar antenna DN150 / 6"  
Planar antenna DN250 / 10"  
Planar antenna DN250 / 10"  
Planar antenna DN200 / 8"  
Planar antenna DN200 / 8"  
Planar antenna DN300 / 12"  
Planar antenna DN300 / 12"  
Special version  
FKM inside  
HNBR inside  
FKM inside  
HNBR inside  
FKM inside  
HNBR inside  
HNBR inside  
FKM inside  
F
2.1 kg  
1.1 kg  
2.5 kg  
U
V
W
X
Y
30  
Process connection  
Flange Dia/Pressure  
Standard  
ANSI B16.5  
ANSI B16.5  
ANSI B16.5  
ANSI B16.5  
ANSI B16.5  
ANSI B16.5  
Material  
316/316L  
316/316L  
316/316L  
316/316L  
316/316L  
316/316L  
316L  
316L  
316L  
316L  
316L  
AVJ  
A3J  
A5J  
AWJ  
AXJ  
A7J  
CWJ  
CXJ  
CZJ  
C1J  
C6J  
C8J  
XXJ  
XVU  
6"/150 lbs / RF  
8"/150 lbs / RF  
10"/150 lbs / RF  
6"/300 lbs / RF  
8"/300 lbs / RF  
12"/150 lbs / RF  
DN150 PN10 / 16 C  
DN200 PN16 C  
DN200 PN25 C  
DN150 PN25 C  
DN250 PN16 C  
DN300 PN16 C  
with flange hub  
11.4 kg  
19.6 kg  
28.8 kg  
20.9 kg  
34.3 kg  
43.2 kg  
10.6 kg  
16.5 kg  
22.7 kg  
14.7 kg  
25.6 kg  
36.1 kg  
EN 1092,1, B11)  
EN 1092,1, B11)  
EN 1092,1, B11)  
EN 1092,1, B11)  
EN 1092,1, B11)  
EN 1092,1, B11)  
316L  
316L  
304/1.4301  
Varec UNI-Flange 6"/  
3.5 kg  
5.2 kg  
7.5 kg  
10.8 kg  
DN150/150A,  
max. 14.5LBS/PN1/1K,  
compatible with:  
- 6" 150LBS  
- DN150 PN16  
- 10K 150A  
X3U  
X5U  
X7U  
Varec UNI-Flange 8"/  
DN200/200A,  
304/1.4301  
304/1.4301  
304/1.4301  
max. 14.5LBS/PN1/1K,  
compatible with:  
- 8" 150LBS  
- DN200 PN16  
- 10K 200A  
Varec UNI-Flange 10"/  
DN250/250A,  
max. 14.5LBS/PN1/1K,  
compatible with:  
- 10" 150LBS  
- DN250 PN16  
- 10K 250A  
Varec UNI-Flange 12"/  
DN300/300A,  
max. 14.5LBS/PN1/1K,  
compatible with:  
- 12" 150LBS  
- DN300 PN16  
- 10K 300A  
1) agreeable to DIN2527 Form C  
YY9  
Special version  
8
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Identification  
40  
Output and operation  
A
4…20 mA HART with VU 331, 4-line alphanumeric dis-  
play  
Y
Special version  
Housing  
50  
60  
C
Y
Aluminium T12-housing with separate connection compartment, coated, IP65  
Special version  
Gland / Entry  
2
4
9
M20x1.5 cable gland  
½ NPT cable entry  
Special version  
70  
Custody transfer approvals  
A
R
Y
NMi, PTB type and test rig approval,  
weights&measures approved (< 1 mm)  
Inventory Control Version,  
not weights&measures approved (3 mm)  
Special approval for custody transfer  
80  
Additional options  
A
Y
Without additional options  
Special version  
7532-  
Complete product designation  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Identification  
Radar Tank Gauge  
2.2  
Scope of delivery  
Caution!  
It is essential to follow the instructions concerning the unpacking, transport and storage  
of measuring instruments given in the section “Incoming acceptance, transport, storage”  
The scope of delivery consists of:  
• Assembled instrument  
• ToF Tool (operating program)  
• Accessories (Chapter 8)  
Accompanying documentation:  
• Short manual (basic equalization/troubleshooting): housed in the instrument  
• Operating manual (this manual)  
• Operating manual: Description of the instrument functions  
• Approval documentation: if this is not included in the operating manual.  
2.3  
Certificates and approvals  
CE mark, declaration of conformity  
The instrument is designed to meet state-of-the-art safety requirements, has been  
tested and left the factory in a condition in which it is safe to operate. The instrument  
complies with the applicable standards and regulations in accordance with EN 61010  
“Protection Measures for Electrical Equipment for Measurement, Control, Regulation and  
Laboratory Procedures”. The instrument described in this manual thus complies with the  
statutory requirements of the EG directives. Varec confirms the successful testing of the  
instrument by affixing to it the CE mark.  
2.4  
Registered trademarks  
KALREZ ®, VITON ®, TEFLON ®  
Registered trademark of the company E.I. Du Pont de Nemours & Co., Wilmington, USA  
TRI-CLAMP ®  
Registered trademark of the company Ladish & Co., Inc., Kenosha, USA  
HART ®  
Registered trademark of HART Communication Foundation, Austin, USA  
ToF ®  
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Ger-  
many  
PulseMaster ®  
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Ger-  
many  
PhaseMaster ®  
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Ger-  
many  
10  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Mounting  
3
Mounting  
3.1  
Quick installation guide  
Installation only in stilling well:  
Turn housing  
The housing can be turned  
in order to simplify access to the  
display and the terminal compartment  
T12 housing  
2
90˚  
3
1
Allen key  
4 mm  
tighten strongly  
by hand  
The performance of the 7532 RTG  
.
planar antenna is not dependent on the  
alignment or geometry of standard stilling  
wells.  
No special alignment is required.  
However, make sure that the planar  
antenna is installed vertically relative  
to the stilling well axis.  
.
Note!  
The 7532 RTG with planar antenna is designed for use on stilling-wells only!  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Mounting  
Radar Tank Gauge  
3.2  
Incoming acceptance, transport, storage  
3.2.1  
Incoming acceptance  
Check the packing and contents for any signs of damage.  
Check the shipment, make sure nothing is missing and that the scope of supply matches  
your order.  
3.2.2  
Transport  
Caution!  
Follow the safety instructions and transport conditions for instruments of more than  
18 kg. Do not lift the measuring instrument by its housing in order to transport it.  
3.2.3  
Storage  
Pack the measuring instrument so that is protected against impacts for storage and  
transport. The original packing material provides the optimum protection for this.  
The permissible storage temperature is -40 °C…+80 °C.  
12  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Mounting  
3.3  
Installation Conditions  
3.3.1  
Dimensions  
68 (2.68")  
94 (3.7")  
65 (2.56") 85 (3.35")  
ENDRESS+HAUSER  
Micropilot II  
E+H UNI flange  
(max. 1 bar)  
DIN, ANSI,  
JIS  
detail A:  
flange adapter  
(see under)  
Ø 150 (5.91")  
DN150 / 6”  
version without widening  
DN200…300 / 8…12”  
version with  
antenna widening  
detail A  
flange hub for the connection  
to flanges provided by the customer  
mounting:  
4 bolts M6 / 90°  
e.g. DIN 912  
Ø 78 (3.07")  
Ø 62,5 (2.46")  
Ø D  
O-Ring 85.3 x 3.53,  
included  
(same material as  
sensor seal)  
flange hub  
Ø 99,5 (3.92")  
Figure 4: Dimensions 7532 RTG  
Antenna version  
L [mm]  
DN150 / 6"  
93  
no horn  
DN200 / 8"  
337  
DN250 / 10"  
DN300 / 12"  
490  
240  
517  
290  
Ø D [mm]  
190  
Note!  
The inactive length of 60 mm prevents condensation effects to the antenna perfor-  
mance. Special versions with longer construction are available.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Mounting  
Radar Tank Gauge  
3.3.2  
Engineering tips  
Measuring conditions  
• The measuring range starts at the bottom end of the stilling well.  
• In case of media with a low dielectric constant (groups A and B), the pipe end can be  
visible through the medium at low levels. In order to guarantee the required accuracy  
in these cases, it is recommended to position the zero-point at a distance C above the  
tank bottom (see Fig.).  
• In applications with planar or parabolic antennas, especially for media with low  
dielectric constants (see page 15), the end of the measuring range should not be closer  
than 1 m (40”) to the flange.  
• For overspill protection, it is possible to define a safety distance (SD) additionally to  
the blocking distance (BD).  
• This safety distance (SD) is set to 0.5 m (20") by default and generating an alarm in  
case the level rises inside the safety distance.  
• Distance B defined the smallest recommended measurement range.  
• Depending on its consistence, foam can either absorb microwaves or reflect them off  
the foam surface. Measurement is possible under certain conditions.  
100%  
BD  
SD  
A
max. level  
B
C
0%  
reference: flange / BD  
(see picture)  
reference: antenna tip  
(see picture)  
Blocking  
distance  
Safety  
distance  
recommended additional settings  
BD [m / ft]  
SD [m / ft]  
A [mm / inch]  
1000 / 40  
B [m / ft]  
C [mm / inch]  
150…300 /  
6…12  
7532 RTG (planar)  
1 / 3.28  
0.5 / 1.6  
0.5 / 1.64  
Behaviour if measuring range is exceeded  
The behaviour in case of the measuring range being exceeded can be freely set: the  
default setting is a current of 22 mA and the generation of a digital warning (E681).  
14  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Mounting  
Measuring range  
The usable measuring range depends on the size of the antenna, the reflectivity of the  
medium, the mounting location, and eventual interference reflections.  
The following tables describe the groups of media as well as the achievable measuring  
range as a function of application and media group. If the dielectric constant of a  
medium is unknown, it is recommended to assume media group B to ensure a reliable  
measurement.  
Product class  
DK (εr)  
1.4 … 1.9  
1.9 … 4  
4 … 10  
Examples  
A
B
C
non-conducting liquids, e.g. liquefied gas 1)  
non-conducting liquids, e.g. benzene, oil, toluene, …  
e.g. concentrated acids, organic solvents, esters, aniline,  
alcohol, acetone, …  
D
> 10  
conducting liquids, e.g. aqueous solutions, dilute acids and  
alkalis  
1)Treat Ammonia NH3 as a medium of group A, e.g. always use a stilling well.  
Measuring range depending on product class for 7532 RTG:  
Product class  
Stilling well/ Bypass  
Measuring range  
7532 RTG  
> DN150  
A
B
DK(εr)=1,4…1,9  
DK(εr)=1,9…4  
DK(εr)=4…10  
DK(εr)>10  
38 m/124 ft  
38 m/124 ft  
38 m/124 ft  
38 m/124 ft  
C
D
max. measuring  
range with custody  
transfer approvals  
20 m/65 ft  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Mounting  
Radar Tank Gauge  
Blocking distance  
The blocking distance (= BD) is the minimum distance from the reference point of the  
measurement (mounting flange) to the medium surface at maximum level.  
referencepointof  
measurement  
BD  
20mA  
100%  
Max.  
Level  
Stilling well / Bypass  
7532 RTG  
Blocking distance  
(BD)  
from Flange  
1 m/40"  
Note!  
Inside the blocking distance a reliable measurement can not be guaranteed.  
16  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Mounting  
3.4  
Installation instructions  
3.4.1  
Mounting kit  
In addition to the tool needed for flange mounting, you will require the following tool:  
• 4 mm Allen wrench for turning the housing.  
3.4.2  
Installation in stilling well  
Optimum mounting position for 7532 RTG  
Standard installation  
When mounting in the stilling well, please  
observe engineering tips on page 14 and  
the following points:  
• After mounting, the housing can be  
turned 350° in order to simplify access to  
the display and the terminal  
compartment.  
• planar axis vertical to flange.  
• Measurements can be performed  
through an open ball valve without any  
problems.  
Recommendations for the stilling well  
• Metal (no enamel coating, plastic on request).  
• Constant diameter.  
• Weld seam as smooth as possible and on the same axis as the slots.  
• Slots offset 180° (not 90°).  
• Slot width respectively diameter of holes max. 1/10 of pipe diameter, de-burred.  
Length and number do not have any influence on the measurement.  
• Select antenna extension as big as possible. For intermediate sizes (e.g. 180 mm)  
select next larger antenna extension and adapt it mechanically. Maximum gap allowed  
between the antenna/horn of 7532 RTG and the inside of the stilling well is 5 mm (3/  
16").  
• The antennna extension of the 7532 RTG is mounted with defined pressure.  
It is strongly recommended not to dismantle this antenna.  
• Dimensions of a nozzle for manual gauging must be adapted to the dimensions of  
the horn antenna used, compare to page page 23.  
Stilling wells with pipe expansion  
• When using a 7532 RTG, a gradual pipe expansion from DN150 to DN200 / DN200  
to DN250 / DN250 to DN300 is acceptable. In such cases, the top end of the piping  
must have a minimum length of 0.5 m in front of the expansion (see table on page 18).  
Ideally, a dip socket is used for this.  
• Greater expansion of the piping (e.g. DN150 to DN300) is possible if the top end of  
the pipe is extended accordingly (see table on page 18).  
• Avoid pipe expansions at right angles.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
Mounting  
Radar Tank Gauge  
Examples for the construction of stilling wells  
7532 RTG  
7532 RTG  
18  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Mounting  
3.4.3  
Turn housing  
After mounting, the housing can be turned 350° in order to simplify access to the display  
and the terminal compartment. Proceed as follows to turn the housing to the required  
position:  
• Undo the fixing screws (1)  
• Turn the housing (2) in the required direction  
• Tighten up the fixing screws (1)  
T12 housing  
2
1
Allen key  
4 mm  
tighten strongly  
by hand  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Mounting  
Radar Tank Gauge  
3.4.4  
Installation with Varec UNI flange  
Installation tips  
Varec UNI flanges are designed for non-pressurized operation respectively max. 1 bar  
absolute pressure. The number of bolts has sometimes been reduced. The bolt-holes  
have been enlarged for adaption of dimensions, therefore, the flange needs to be  
properly aligned to the counterflange before the bolts are tightened.  
Version  
Compatible with  
D [mm]  
K [mm]  
Type plate no.  
1000  
DN150 PN16  
ANSI 6" 150lbs  
JIS 10K 150  
280  
240  
942455-3001  
2000  
3000  
4000  
DN200 PN16  
ANSI 8" 150lbs  
JIS 10K 200  
DN250 PN16  
ANSI 10" 150lbs  
JIS 10K 250  
DN300 PN16  
ANSI 12" 150lbs  
JIS 10K 300  
340  
405  
482  
294.5  
358  
942455-3002  
942455-3003  
942455-3004  
410 (for DIN), 431,8  
(for ANSI), 400 (for  
JIS),  
404,5 (for DIN + JIS)  
20  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Mounting  
Preparation for the installation of the Varec UNI flange  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
Radar Tank Gauge  
pull off housing  
16  
mount Varec UNI flange  
17  
Varec UNI flange  
(max. 1 bar)  
detail A:  
flange adapter  
(see under)  
detail A  
flange hub for the connection  
to flanges provided by the customer  
mounting:  
4 bolts M6 / 90˚  
e.g. DIN 912  
Ø 78  
Ø 62.5  
O-Ring 85.3 x 3.53,  
included  
(same material as  
sensor seal)  
flange hub  
Ø 99.5  
22  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Mounting  
3.4.5  
Mounting with Sample hatch on stilling well  
Installation tips  
For control and cleaning purposes as well as for hand dipping (tape), a sample hatch  
gauging is recommended. The sensor head can be easily checked in the area of the  
opening. Manual gauging with gauge rod or tape is possible without removal of the  
transmitter. The lower edge of the opening is the reference for the gauging. The  
construction is only suitable for non-pressurized operation.  
Note!  
The nozzle for manual gauging is not part of the standard offering from Varec. Please  
contact Varec for further information.  
Flange  
PN [lbs] 2)  
A [mm]  
L [mm}  
DN150  
16  
110  
DN200  
16  
140  
300  
DN250/300  
16  
Flange  
ANSI 6"  
150  
110  
ANSI 8"  
150  
140  
ANSI 10"  
150  
170  
2)  
PN [lbs]  
A [mm]  
L [mm]  
170  
450  
300  
450  
2)Only dimensions adapted to standard. Designed for non-pressurized operation only,  
therefore thickness of flange can be reduced (e.g. 8mm).  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Mounting  
Radar Tank Gauge  
3.4.6  
Mounting with Pivoting element  
Installation tips  
The Pivoting element serves to swivel the 7500 RTG from the measuring position, e.g.  
to clean the antenna or dip the tank.  
The pivoting element is not part of the standard offering from Varec, special offers  
available under ref. number MVTFM0422.  
3.5  
Post-installation check  
After the measuring instrument has been installed, perform the following checks:  
• Is the measuring instrument damaged (visual check)?  
• Does the measuring instrument correspond to the measuring point specifications  
such as process temperature/pressure, ambient temperature, measuring range, etc.?  
• Is the flange marking correctly aligned? (see page 11)  
• Have the flange screws been tightened up with the respective tightening torque?  
• Are the measuring point number and labeling correct (visual check)?  
• Is the measuring instrument adequately protected against rain and direct sunlight  
24  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Wiring  
4
Wiring  
4.1  
Quick wiring guide  
When grounding conductive screens, the corresponding directives EN 60079-14 and EN  
1127-1 must be observed. Recommendation for safe grounding of conductive screens:  
Wiring  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring  
Radar Tank Gauge  
Before connection please note the following:  
"
The power supply must be identical to the data on the  
nameplate (1).  
Caution!  
Switch off power supply before connecting up the device.  
1
Connect Equipotential bonding to transmitter ground terminal  
before connecting up the device.  
Tighten the locking screw:  
It forms the connection between the antenna and the housing  
ground potential.  
2
When you use the measuring system in hazardous areas, make sure you comply with  
national standards and the specifications in the safety instructions (XA’s).  
Make sure you use the specified cable gland.  
Connect up the 7500 RTG as follows:  
Before unscrew housing cover (2) at seperate connection room  
turn off the power supply!  
-
Insert cable through gland (3).  
Use screened, twisted wire pair.  
Only ground screening of the line (5) on sensor side.  
-
Make connection (see pin assignment).  
Tighten cable gland (4).  
Screw off housing cover (2).  
4
Switch on power supply.  
3
power:  
24 VDC  
signal:  
24 VDC  
(16…30 V)  
5
1
2
3
4
plant  
ground  
1 2 3 4 5  
1 2 3  
4 5  
A 7500 RTG situated in a hazardous area is connected as a single  
device to a power supply unit and transmitter situated outside of  
the hazardous area. In this case, it is recommended that the screen  
be connected directly to the 7500 RTG at the housing's earth,  
whereby the 7500 RTG and the power supply unit are connected to  
the same potential matching line (PML).  
26  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Wiring  
Wiring with Tank Side Monitor 4590  
Before connection please note the following:  
"
The power supply must be identical to the data on the  
nameplate (1).  
Caution!  
1
Switch off power supply before connecting up the device.  
Connect Equipotential bonding to transmitter ground terminal  
before connecting up the device.  
2
Tighten the locking screw:  
It forms the connection between the antenna and the housing  
ground potential.  
When you use the measuring system in hazardous areas, make sure you comply with  
national standards and the specifications in the safety instructions (XA’s).  
Make sure you use the specified cable gland.  
Connect up the 7500 RTG as follows:  
Before unscrew housing cover (2) at seperate connection room  
turn off the power supply!  
-
Insert cable through gland (3).  
Use screened, twisted wire pair.  
Make connection (see pin assignment).  
Tighten cable gland (4).  
Screw off housing cover (2).  
Tank Side Monitor  
4590 TSM  
Switch on power supply.  
4
3
intrinsicaly safe  
terminal board  
D+  
16  
S+  
17  
S-  
D-  
18  
19  
20  
21  
22  
23  
OPT1  
OPT2  
OPT3  
OPT4  
grounding not on  
7500 RTG  
grounding single sided  
on Tank Side Monitor  
4590 TSM  
+
24  
25  
26  
27  
H
-
+
1
2
3
4
HART  
sensor  
H
-
+
+
plant  
ground  
28  
29  
30  
31  
4
3
H
-
+
-
+
1 2 3 4 5  
2
1
P
-
-
1 2 3  
4 5  
only for  
7500 RTG  
The 7500 RTG is - possibly in combination with other devices - connected to a Tank  
Side Monitor in a hazardous area. In this case, it is recommended that you ground  
the cable screen centrally at the Tank Side Monitor and connect all devices to the  
same potential matching line (PML). If, for functional reasons, a capacitive coupling is  
required between local earth and screen (multiple grounding), ceramic condensers  
with a dielectric strength of min. 1500 Veff must be used, whereby the total capacitance  
of 10 nF must not be exceeded. Notes on grounding interconnected intrinsically safe  
devices are provided by the FISCO model  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Wiring  
Radar Tank Gauge  
4.2  
Connecting the measuring unit  
Terminal compartment  
The housing comes with a separate terminal compartment.  
Load HART  
Minimum load for Hart communication: 250 Ω  
Cable entry  
Cable gland: M20x1.5 or Pg13.5  
Cable entry: G ½ or ½ NPT  
Supply voltage  
Direct current voltage: 16…36 VDC  
.
Communication  
Terminal voltage  
U (20 mA) =  
U (20 mA) =  
U (4 mA) =  
minimal  
16 V  
maximal  
36 V  
Power supply  
Standard  
Ex  
16 V  
30 V  
Signal  
11,5 V  
11,5 V  
30 V  
Ex  
U (20 mA) =  
30 V  
Power consumption  
Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V.  
Current consumption  
Max. 21 mA (50 mA inrush current).  
Power supply  
For stand alone operation recommended via e.g. Varec RN 221N.  
mm accuracy  
For measurements with mm accuracy the measured variable must be transmitted  
using HART protocol to ensure the necessary resolution.  
28  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
7532  
Wiring  
4.2.1  
Connection to Tank Side Monitor 4590  
See page 27.  
4.2.2  
HART connection with two Varec RN 221 N  
- ToF Tool  
FXA 193  
RN 221N  
power supply  
signal  
4...20 mA  
df  
d
d
a
s
f
d
m
a
a
a
.
DEL  
ONLINE  
QUICK SETUP  
OPERATING MENU  
PV  
T
ABAR:  
*
*
*
*
*
*
*
*
1
2
3
352 mbar  
˚C  
4
SV  
0
HELP  
SAVE  
1
2
3
4
5
- COMMUWIN II  
6
Page  
Up  
9
Bksp  
Delete  
Page  
On  
- ToF Tool  
#
%
&
A
B
C
D
E
F
1
2
3
Copy  
Paste  
Hot Key  
G
H
I
J
K
L
M
N
O
4
5
6
Insert  
+
Hot Key  
P
)
Q
R
S
T
U
V
W
X
Y
Z
7
8
9
,
(
_
<
>
+
*
/
.
0
-
375  
FIELD COMMUNICATOR  
HART handheld  
DXR 375  
Commubox  
FXA 191  
4.2.3  
HART connection with other supplies  
- ToF Tool  
DC voltage  
FXA 193  
or  
PLC  
power supply  
signal  
4...20 mA  
250 Ω  
a
as  
df  
a
dsdmdm  
 d
  l
  a
 s
  f
DEL  
ONLINE  
QUICK SETUP  
OPERATING MENU  
PV  
T
ABAR:  
*
*
*
*
*
*
*
*
1
2
3
352 mbar  
°C  
4
SV  
0
HELP  
SAVE  
- COMMUWIN II  
- ToF Tool  
6
Page  
Up  
9
Bksp  
Delete  
Page  
On  
#
%
&
A
B
C
D
E
F
1
2
3
Copy  
Paste  
Hot Key  
G
H
I
J
K
L
M
N
O
4
5
6
Insert  
+
Hot Key  
P
)
Q
R
S
T
U
V
W
X
Y
Z
7
8
9
,
(
_
<
>
+
*
/
.
0
-
375  
FIELD COMMUNICATOR  
HART handheld  
DXR 375  
Commubox  
FXA 191  
Caution!  
If the HART communication resistor is not built into the supply unit, it is necessary to  
insert a communication resistor of 250 into the 2-wire line.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring  
Radar Tank Gauge  
4.3  
Equipotential bonding  
Connect the Equipotential bonding to the external ground terminal of the transmitter.  
Caution!  
In Ex applications, the instrument must only be grounded on the sensor side. Further  
safety instructions are given in the separate documentation for applications in explosion  
hazardous areas.  
4.4  
Degree of protection  
• housing: IP 65, NEMA 4X (open housing: IP20, NEMA 1)  
• antenna: IP 68 (NEMA 6P)  
4.5  
Overvoltage protector  
• The level transmitter 7500 RTG is equipped with an internal overvoltage protector  
(600 Vrms electrode). Connect the metallic housing of the 7500 RTG to the tank wall  
directly with an electrically conductive lead to ensure reliable potential matching.  
• Installation with additional overvoltage protector HAW 262 Z (see XA 081F-A  
"Safety instructions for electrical apparatus certified for use in explosion-hazardous  
areas").  
–Connect the external overvoltage protector and the 7500 RTG transmitter to the local  
potential matching system.  
–Potentials shall be equalised both inside and outside the explosion hazardous area.  
–The cable connecting the overvoltage protector and the 7500 RTG transmitter shall  
not exceed 1 m in length;  
–The cable shall be protected e.g. routed in an armoured hose.  
4.6  
Post-connection check  
After wiring the measuring instrument, perform the following checks:  
• Is the terminal allocation correct (see page 25)?  
• Is the cable gland tight?  
• Is the housing cover screwed tight?  
• If auxiliary power is available:  
Is the instrument ready for operation and does the liquid crystal display show any  
value?  
30  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Operation  
5
Operation  
5.1  
Quick operation guide  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Radar Tank Gauge  
+
E
X
F
2x  
X
>3 s  
X
F
X
...  
F
O
S
O
S
O
S
...  
...  
Selection and configuration in Operation menu:  
1.) Change from Measured Value Display to Group Selection by pressing F  
2.) Press S or O to select the required Function Group (e.g.. "basic setup (00)") and confirm by pressing  
F First function (e.g. "tank shape (002)") is selected.  
Note!  
The active selection is marked by a  
3.) Activate Edit mode with O or S.  
Selection menus:  
in front of the menu text.  
a) Select the required Parameter in selected function (e.g. "tank shape (002)") with S or O.  
b) F confirms selection appears in front of the selected parameter  
c) F confirms the edited value system quits Edit mode  
d) O + S (= X) interrupts selection system quits Edit mode  
Typing in numerals and text:  
a) Press O or S to edit the first character of the numeral / text (e.g. "empty calibr. (005)")  
b) F positions the cursor at the next character continue with (a) until you have completed your input  
c) if a  
symbol appears at the cursor, press F to accept the value entered  
system quits Edit mode  
d) O + S (= X) interrupts the input, system quits Edit mode  
4) Press F to select the next function (e.g. "medium property (003)")  
5) Press O + S (= X) once return to previous function (e.g. "tank shape (002)")  
Press O + S (= X) twice return to Group selection  
6) Press O + S (= X) to return to Measured value display  
32  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Operation  
5.1.1  
General structure of the operating menu  
The operating menu is made up of two levels:  
Function groups (00, 01, 03, …, 0C, 0D):  
The individual operating options of the instrument are split up roughly into different  
function groups. The function groups that are available include, e.g.: "basic setup",  
"safety settings", "output", "display", etc.  
Functions (001, 002, 003, …, 0D8, 0D9):  
Each function group consists of one or more functions. The functions perform the  
actual operation or parameterization of the instrument. Numerical values can be  
entered here and parameters can be selected and saved. The available functions of the  
basic setup (00)” function group include, e.g.: "tank shape (002)",  
"medium property (003)", "process cond. (004)", "empty calibr. (005)", etc.  
If, for example, the application of the instrument is to be changed, carry out the follow-  
ing procedure:  
1.Select the “basic setup (00)” function group.  
2.Select the "tank shape (002)" function (where the existing tank shape is selected).  
5.1.2  
Identifying the functions  
For simple orientation within the function menus (see page 91), for each function a  
position is shown on the display.  
The first two digits identify the function group:  
basic setup  
00  
01  
04  
safety settings  
linearization  
The third digit numbers the individual functions within the function group:  
basic setup  
00  
tank shape  
002  
003  
004  
medium property  
process cond.  
Here after the position is always given in brackets (e.g. "tank shape" (002)) after the  
described function.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Radar Tank Gauge  
5.2  
Display and operating elements  
Figure 5: Layout of the display and operating elements  
5.2.1  
Display  
Liquid crystal display (LCD):  
Four lines with 20 characters each. Display contrast adjustable through key  
combination.  
Headline  
Position indicator  
Symbol  
Main value Bargraph  
Unit  
+
E
Selection list  
Help text  
Envelope  
curve  
Figure 6: Display  
34  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Operation  
5.2.2  
Display symbols  
The following table describes the symbols that appear on the liquid crystal display:  
Symbols Meaning  
ALARM_SYMBOL  
This alarm symbol appears when the instrument is in an alarm state. If the symbol  
flashes, this indicates a warning.  
LOCK_SYMBOL  
This lock symbol appears when the instrument is locked,i.e. if no input is possible.  
COM_SYMBOL  
This communication symbol appears when a data transmission via e.g. HART,  
PFOFIBUS-PA or Foundation Fieldbus is in progress.  
Calibration to regulatory standards disturbed  
If the instrument is not locked or it cannot guarantee the calibration to regulatory  
standards, the situation will be indicated on the display via the symbol.  
Table 1: Meaning of the symbols  
Light emitting diodes (LEDs):  
There is a green and a red LED besides the Liquid Crystal Display.  
LED  
Meaning  
red LED continuously on  
red LED flashes  
red LED off  
Alarm  
Warning  
No alarm  
green LED continuously on  
Green LED flashes  
Operation  
Communication with external device  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Operation  
Radar Tank Gauge  
5.2.3  
Key assignment  
The operating elements are located inside the housing and are accessible for operation  
by opening the lid of the housing.  
Function of the keys  
Key(s)  
Meaning  
Navigate upwards in the selection list  
Edit numeric value within a function  
O
S
or  
or  
V
W
Navigate downwards in the selection list  
Edit numeric value within a function  
X
F
or  
or  
Z
M
Navigate to the left within a function group  
Navigate to the right within a function group, confirmation.  
O
S
and  
or  
F
F
Contrast settings of the LCD  
and  
Hardware lock / unlock  
After a hardware lock, an operation of the instrument via display or  
communication is not possible!  
The hardware can only be unlocked via the display. An unlock parameter must  
be entered to do so.  
O
and  
S
and  
F
Table 2: Function of the keys  
Custody locking switch  
Access to the electronics can be prevented by means of a custody locking switch that  
locks the device settings; see fig. 4 on Page 34.  
The custody locking switch can be sealed for custody transfer applications.  
Software reliability  
The software used in the 7500 RTG fulfills the requirements of  
OIML R85. This particularly includes:  
• cyclical test of data consistency  
• non-volatile memory  
• segmented data storage  
The 7500 RTG continuously monitor the compliance with accuracy requirements for  
custody transfer measurements according to OIML R85. If the accuracy cannot be  
maintained, a specific alarm is generated on the local display and via the digital  
communication  
36  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
7532  
Operation  
5.3  
Local operation  
5.3.1  
Locking of the configuration mode  
The 7500 RTG can be protected in two ways against unauthorized changing of instru-  
ment data, numerical values or factory settings:  
"unlock parameter" (0A4):  
A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the  
"diagnostics" (0A) function group. The lock is shown on the display by the symbol and  
can be released again either via the display or by communication.  
Hardware lock:  
The instrument is locked by pressing the O and S and F keys at the same time.  
The lock is shown on the display by the  
symbol and can only be unlocked again  
via the display by pressing the O and S and F keys at the same time again. It is not  
possible to unlock the hardware by communication.  
All parameters can de displayed even if the instrument is locked.  
+
E
O and S and F press simultaneous  
The LOCK_SYMBOL appears on the LCD.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Radar Tank Gauge  
5.3.2  
Unlocking of configuration mode  
If an attempt is made to change parameters when the instrument is locked, the user is  
automatically requested to unlock the instrument:  
"unlock parameter" (0A4):  
By entering the unlock parameter (on the display or via communication)  
100 = for HART devices  
the 7500 RTG is released for operation.  
Hardware lock:  
After pressing the O and S and F keys at the same time, the user is asked to enter the  
unlock parameter  
100 = for HART devices.  
O and S and F press simultaneous  
+
E
Please enter unlock code and confirm with F.  
Caution!  
Changing certain parameters such as all sensor characteristics, for example, influences  
numerous functions of the entire measuring system, particularly measuring accuracy.  
There is no need to change these parameters under normal circumstances and  
consequently, they are protected by a special code known only to the Varec service  
organization. Please contact Varec if you have any questions.  
38  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Operation  
5.3.3  
Factory settings (Reset)  
Caution!  
A reset sets the instrument back to the factory settings. This can lead to an impairment  
of the measurement. Generally, you should perform a basic setup again following a  
reset.  
A reset is only necessary:  
• if the instrument no longer functions  
• if the instrument must be moved from one measuring point to another  
• if the instrument is being de-installed /put into storage/installed  
+
E
User input ("reset" (0A3)):  
• 333 = customer parameters  
• 555 = History  
333 = reset customer parameters  
This reset is recommended whenever an instrument with an unknown 'history' is to be  
used in an application:  
• The 7500 RTG is reset to the default values.  
• The customer specific tank map is not deleted.  
• A linearization is switched to "linear" although the table values are retained. The table  
can be reactivated in the "linearization" (04) function group.  
List of functions that are affected by a reset:  
• tank shape (002)  
• linearization (041)  
• customer unit (042)  
• diameter vessel (047)  
• range of mapping (052)  
• pres. Map dist (054)  
• offset (057)  
• low output limit (062)  
• fixed current (063)  
• fixed cur. value (064)  
• simulation (065)  
• empty calibr. (005)  
• full calibr. (006)  
• pipe diameter (007)  
• output on alarm (010)  
• output on alarm (011)  
• outp. echo loss (012)  
• ramp %span/min (013)  
• delay time (014)  
• safety distance (015)  
• in safety dist. (016)  
• Tank Gauging (030)  
• auto correction (031)  
• level/ullage (040)  
• simulation value (066)  
• format display (094)  
• distance unit (0C5)  
• download mode (0C8)  
555 = History Reset  
After mounting and aligning the equipment, carry out a history reset before switching  
on the function "Auto-correction" (031) (see page 57).  
The tank map can also be reset in the "cust. tank map" (055) function of the  
"extended calibr." (05) function group.  
This reset is recommended whenever an instrument with an unknown 'history' is to be  
used in an application or if a faulty mapping was started:  
• The tank map is deleted. The mapping must be recommenced.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
Radar Tank Gauge  
5.4  
Display and acknowledging error messages  
Type of error  
Errors that occur during commissioning or measuring are displayed immediately on the  
local display. If two or more system or process errors occur, the error with the highest  
priority is the one shown on the display.  
The measuring system distinguishes between two types of error:  
A (Alarm):  
Instrument goes into a defined state (e.g. MAX 22 mA)  
Indicated by a constant  
symbol.  
(For a description of the codes, see Table 9.2 on Page 79)  
W (Warning):  
Instrument continue measuring, error message is displayed.  
Indicated by a flashing  
symbol.  
(For a description of the codes, see Table 9.2 on Page 79)  
E (Alarm / Warning):  
Configurable (e.g. loss of echo, level within the safety distance)  
Indicated by a constant/flashing  
symbol.  
(For a description of the codes, see Table 9.2 on Page 79)  
+
E
Error messages  
Error messages appear as four lines of plain text on the display. In addition, a unique  
error code is also output. A description of the error codes is given on page 79.  
• The "diagnostics (0A)" function group can display current errors as well as the last  
errors that occurred.  
• If several current errors occur, use O or S to page through the error messages.  
• The last occurring error can be deleted in the "diagnostics (0A)" function group  
with the function "clear last error" (0A2).  
40  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
7532  
Operation  
5.5  
HART communication  
Apart from local operation, you can also parameterize the measuring instrument and  
view measured values by means of a HART protocol. There are two options available for  
operation:  
• Operation via the universal handheld operating unit, the  
HART Communicator DXR 375.  
• Operation via the Personal Computer (PC) using the operating program  
(e.g. ToF Tool or Commuwin II) (For connections, see page 29).  
• Operation via the Tank Side Monitor 4590.  
5.5.1  
Handheld unit DXR 375  
All device functions can be adjusted via menu operation with the handheld unit  
DXR 375.  
dsdmdm  
df das.  
asdas fa  
asas la.  
dsdmdm  
df das.  
asdas fa  
asas la.  
FMR531: LIC0001  
ONLINE  
FMR531: LIC0001  
ONLINE  
1
2
GROUP SELECTION  
PV  
1
2
GROUP SELECT  
PV  
Delete  
8.7  
m
8.7 m  
HELP  
SAVE  
dsdmdm  
df das.  
asdas fa  
asas la.  
H
FMR531: LIC0001  
HELP  
SAVE  
6
Page  
Up  
GROUP SELECTION  
9
1
2
3
4
5
CALIBRATION  
Bksp  
Delete  
Delete  
LINEARISATION  
EXT. CALIBRATION  
SERVICE  
Page  
On  
Bksp  
OPERATING MODE  
#
%
&
A
B
C
D
E
F
1
2
3
dsdmdm  
df das.  
asdas fa  
asas la.  
Copy  
Paste  
Hot Key  
H
G
H
I
J
K
L
M
N
O
FMR531: LIC0001  
4
5
6
SAVE  
HOME  
Insert  
+
Hot Key  
CALIBRATION  
P
Q
R
S
T
_
U
V
W
X Y  
Z
Page  
Up  
1
2
3
4
5
MEASURED VALUE  
EMPTY CALIBRATION  
FULL CALIBRATION  
7
8
9
,
(
)
<
>
+
*
/
.
0
-
APPLICATION PARAMETER  
OUTPUT DAMPING  
Bksp  
Page  
On  
375  
FIELD COMMUNICATOR  
SAVE  
HOME  
Figure 7: Menu operation with the DXR 375 handheld instrument  
Note!  
• Further information on the HART handheld unit is given in the respective operating  
manual included in the transport bag of the instrument.  
5.5.2  
ToF Tool operating program  
The ToF Tool is a graphical operating software for instruments from Varec that operate  
based on the time-of-flight principle. It is used to support commissioning, securing of  
data, signal analysis and documentation of the instruments. It is compatible with the  
following operating systems: Win95, Win98, WinNT4.0, Win2000 and  
Windows XP.  
The ToF Tool supports the following functions:  
• Online configuration of transmitters  
• Signal analysis via envelope curve  
• Loading and saving of instrument data (Upload/Download)  
• Documentation of measuring point  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Radar Tank Gauge  
Note!  
Further information you may find on the CD-ROM, which is enclosed to the instrument.  
Menu-guided commissioning  
Signal analysis via envelope curve  
Connection options:  
• Service-interface with adapter FXA 193 (see page 29)  
• HART with Commubox FXA 191 (see page 29)  
42  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Operation  
5.5.3  
Commuwin II-Operating Program  
Commuwin II is an operating software with graphical support for intelligent transmitters  
with the communication protocols Rackbus, Rackbus RS 485, INTENSOR, HART or  
PROFIBUS-PA. It is compatible with the operating systems Win 3.1/3.11, Win95, Win98  
and WinNT4.0. All functions of Commuwin II are supported. The configuration is made  
via operating matrix or graphic surface. A envelope curve can be displayed in ToF Tool.  
Note!  
Further information on Commuwin II is given in the following Varec documentation:  
• System Information: SI 018F/00/en “Commuwin II”  
• Operating Manual: BA 124F/00/en “Commuwin II” operating program  
Connection  
The table provides an overview of the Commuwin connections.  
Interface  
Hardware  
Server  
Device list  
HART  
Commubox FXA 191 to HART  
HART  
Connected instrument  
Computer with RS-232C interface  
Interface FXN 672  
ZA 673 for  
PROFIBUS  
ZA 672 for  
other  
List of all rack bus modules:  
the required FXN 672 must  
be selected  
Gateway for MODBUS, PROFIBUS,  
FIP, INTERBUS, etc.  
Computer with  
RS-232C interface or  
PROFIBUS card  
Note!  
The 7500 RTG can also be operated locally using the keys. If operation is prevented by  
the keys being locked locally, parameter entry via communication is not possible either.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Radar Tank Gauge  
44  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Commissioning  
6
Commissioning  
6.1  
Function check  
Make sure that all final checks have been completed before you start up your measuring  
point:  
• Checklist “Post installation check” (see page 24).  
• Checklist “Post connection check” (see page 30).  
6.2  
Commissioning  
6.2.1  
Switching on the measuring device  
When the instrument is switched on for the first time, the following messages appear on  
the display:  
+
E
After 5 s, the following message appears  
After 5 s or after you have pressed F the follow-  
ing message appears  
Select the language  
(this message appears the first time the instrument  
is switched on)  
Select the basic unit  
(this message appears the first time the instrument  
is switched on)  
The current measured value is displayed  
After F is pressed, you reach the group selection.  
This selection enables you to perform the basic  
setup  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Commissioning  
Radar Tank Gauge  
6.3  
Basic Setup  
46  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Commissioning  
Commissioning  
flange:  
referencepointof  
measurement  
BD  
SD  
measuring cond.  
measuring cond.  
D
E
empty calibr.  
full calibr.  
F
L
pipe diameter  
(for bypass/stilling well)  
E
D
= empty calibr. (= zero)  
settings in 005  
F
L
= full calibr. (= span)  
settings in 006  
= level  
display in 0A6  
= distance (distance flange / product)  
display in 0A5  
mapping  
SD = safety settings  
settings in 015  
BD = blocking dist.  
settings in 059  
Automatic  
pipe diamter correction  
(option)  
first point corrects offset  
further points correct linearity  
safety settings  
linearisation  
extended calibr.  
...  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Commissioning  
Radar Tank Gauge  
To successfully commission a precise measurement to the nearest mm, it is important  
you carry out a history reset on first installation after mechanical installation and after  
the basic setup of the device (see Page 56). Only after a history reset the mounting cali-  
bration is carried out. Enter the measurement offset as the first point in the dip table for  
the mounting calibration. When a value is dipped at a later date, make a second entry  
into the dip table, again using the semi-automatic mode. This way, you can easily carry  
out a linearization of the measurement.  
When configuring the function in "basic setup" (00) please take into account the  
following notes:  
• Select the functions as described on page 31.  
• Some functions can only be used depending on the parameterization of the  
instrument. For example, the pipe diameter of a stilling well can only be entered if  
"stilling well" was selected beforehand in the "tank shape" (002) function.  
• Certain functions (e.g. starting an interference echo mapping (053)) prompt you to  
confirm your data entries. Press O or S to select "YES" and press F to confirm. The  
function is now started.  
• If you do not press a key during a configurable time period (function group  
"display (09)"), an automatic return is made to the home position (measured value  
display).  
Note!  
• The instrument continues to measure while data entry is in progress, i.e. the current  
measured values are output via the signal outputs in the normal way.  
• If the envelope curve mode is active on the display, the measured values are updated  
in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the  
measuring point has been optimized.  
• If the power supply fails, all preset and parameterized values remain safely stored in  
the EEPROM.  
Note!  
All functions are described in detail, as is the overview of the operating menu itself, in  
the 7500 RTG "Service manual and description of instrument functions".  
48  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Commissioning  
6.4  
Basic Setup with the VU 331  
Function "measured value" (000)  
+
E
This function displays the current measured value in the selected unit  
(see "customer unit" (042) function). The number of digits after decimal point can be  
selected in the "no.of decimals" (095) function. The length of the bargraph corresponds  
to the percentile value of the present measured value with regard to the span.  
6.4.1  
Function group "basic setup" (00)  
+
E
Function "tank shape" (002)  
+
E
This function is used to select the tank shape.  
Note!  
For the application of the 7532 RTG the selection "stilling well" has to be chosen in the  
function "tank shape" (002).  
Selection:  
• dome ceiling  
• horizontal cyl  
• bypass  
stilling well  
• flat ceiling (Typical ceiling of storage tanks: a slight slope of only a few degrees can  
be neglected.)  
• sphere  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Commissioning  
Radar Tank Gauge  
Function "medium property" (003)  
+
E
This function is used to select the dielectric constant.  
Selection:  
unknown  
• < 1.9  
• 1.9 ... 4  
• 4 ... 10  
• > 10  
Product class  
DK (er)  
1,4 … 1,9  
1,9 … 4  
4 … 10  
Examples  
A
B
C
non-conducting liquids, e.g. liquefied gas 3)  
non-conducting liquids, e.g. benzene, oil, toluene, …  
e.g. concentrated acids, organic solvents, esters, aniline,  
alcohol, acetone, …  
D
> 10  
conducting liquids, e.g. aqueous solutions, dilute acids and  
alkalis  
3)Treat Ammonia NH3 as a medium of group A, i.e. always use a stilling well.  
50  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Commissioning  
Function "process cond." (004)  
+
E
This function is used to select the process conditions.  
Selection:  
standard  
• calm surface  
• turb. surface  
• agitator  
• fast change  
• test:no filter  
standard  
calm surface  
For all applications that do  
not fit into any of the  
following groups.  
Storage tanks with immersion  
tube or bottom filling  
The filter and output  
damping are set to average  
values.  
The averaging filters and  
output damping are set to  
high values.  
-> steady meas. value  
-> precise measurement  
-> slower reaction time  
Note!  
page 57) is only activated if you select the measuring conditions "standard" or  
"calm surface". We strongly recommend that, in the case of rough product surfaces or  
rapid filling, you activate the appropriate application parameters.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Commissioning  
Radar Tank Gauge  
Function "empty calibr." (005)  
+
E
This function is used to enter the distance from the flange (reference point of the  
measurement) to the minimum level (=zero).  
Caution!  
For dish bottoms or conical outlets, the zero point should be no lower than the point at  
which the radar beam hits the bottom of the tank.  
Function "full calibr." (006)  
+
E
This function is used to enter the distance from the minimum level to the maximum level  
(=span).  
In principle, it is possible to measure up to the tip of the antenna. However, due to  
considerations regarding corrosion and build-up, the end of the measuring range  
should not be chosen any closer than 50 mm (2”) to the tip of the antenna.  
52  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
7532  
Commissioning  
Note!  
If bypass or stilling well was selected in the "tank shape" (002) function, the pipe  
diameter is requested in the following step.  
Function "pipe diameter" (007)  
+
E
This function is used to enter the pipe diameter of the stilling well or bypass pipe.  
100%  
100%  
0%  
0%  
ø
d2  
ø
Microwaves propagate slower in pipes than in free space. This effect depends on the  
inside diameter of the pipe and is automatically taken into account by the 7500 RTG. It  
is only necessary to enter the pipe diameter for applications in a bypass or stilling well.  
If mounting the 7532 RTG on stilling wells with a widening of the pipe, the inner diam-  
eter of the lower part of the pipe (d2 in the Fig.) must be entered. This is the part of the  
stilling well, where the measurement is actually performed.  
Function "dist./ meas. value (008)"  
+
E
The distance measured from the reference point to the product surface and the level  
calculated with the aid of the empty adjustment are displayed. Check whether the values  
correspond to the actual level or the actual distance. The following cases can occur:  
• Distance correct – level correct -> continue with the next function, "check  
distance" (051)  
• Distance correct – level incorrect -> Check "empty calibr." (005)  
• Distance incorrect – level incorrect -> continue with the next function, "check  
distance" (051)  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Commissioning  
Radar Tank Gauge  
Function "check distance" (051)  
+
E
This function triggers the mapping of interference echoes. To do so, the measured  
distance must be compared with the actual distance to the product surface. The  
following options are available for selection:  
Selection:  
• distance = ok  
• dist. too small  
• dist. too big  
dist. unknown  
• manual  
distance = ok  
• mapping is carried out up to the currently measured echo  
• The range to be suppressed is suggested in the "range of mapping (052)" function  
Anyway, it is wise to carry out a mapping even in this case.  
dist. too small  
• At the moment, an interference is being evaluated  
• Therefore, a mapping is carried out including the presently measured echoes  
• The range to be suppressed is suggested in the "range of mapping (052)" function  
dist. too big  
• This error cannot be remedied by interference echo mapping  
• Check the application parameters (002), (003), (004) and "empty calibr." (005)  
dist. unknown  
If the actual distance is not known, no mapping can be carried out.  
manual  
A mapping is also possible by manual entry of the range to be suppressed. This entry is  
made in the "range of mapping (052)" function.  
Caution!  
The range of mapping must end 0.5 m (20") before the echo of the actual level. For an  
empty tank, do not enter E, but E – 0.5 m (20").  
54  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
7532  
Commissioning  
Function "range of mapping" (052)  
+
E
This function displays the suggested range of mapping. The reference point is always  
the reference point of the measurement (see page 46). This value can be edited by the  
operator.  
For manual mapping, the default value is: 0 m.  
Function "start mapping" (053)  
+
E
This function is used to start the interference echo mapping up to the distance given in  
"range of mapping" (052).  
Selection:  
off: no mapping is carried out  
• on: mapping is started  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Commissioning  
Radar Tank Gauge  
Display "dist./meas.value (008)"  
+
E
The distance measured from the reference point to the product surface and the level  
calculated with the aid of the empty alignment are displayed again. Check whether the  
values correspond to the actual level or the actual distance. The following cases can  
occur:  
• Distance correct – level correct -> basic setup completed  
• Distance incorrect – level incorrect -> a further interference echo mapping must be  
carried out "check distance" (051).  
• Distance correct – level incorrect -> check "empty calibr." (005)  
Function "history reset" (009)  
+
E
By this function a history reset of the device is performed, i.e. the correspondence table  
between level an index values is deleted. A new correspondence table will be filled and  
stored after the history reset, see page 57.  
Caution!  
Perform only after first installation (see »Function "auto-correction" (031)« on page 57).  
In this case also effect a reset of the dip table in function "dip table mode" (033).  
+
E
After 3 s, the following message appears  
Note!  
After basic calibration, it is wise to evaluate the measurement using the envelope curve  
(function group "display" (09)).  
56  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Commissioning  
6.5  
Mounting calibration with VU 331  
6.5.1  
Function group "mounting calibr." (03)  
+
E
Function "tank gauging" (030)  
+
E
Using this function, you can either enter a dip table or carry out an auto-correction.  
Function "auto-correction" (031)  
+
E
When measuring levels with radar systems, so-called "multipath reflections" can affect  
the level signal giving rise to serious measuring errors. "Multipath reflections" also  
include radar beams which are received by the radar system, which have not been  
reflected directly by the medium surface. They may reach the antenna via the basin wall  
and the medium surface. This phenomenon is particularly noticeable with devices  
mounted near to walls, as soon as the conical radar beam strikes the basin wall.  
The 7500 RTG can automatically discover and correct measuring errors due to this  
"multiple path" propagation. This is because it uses two independent sets of information  
when evaluating reflection signals:  
• Firstly, it evaluates the amplitude of the reflected energy using the so-called envelope  
curve system.  
• Secondly, it evaluates the phase of the reflected energy.  
The decisive factor for a constant output signal is to assign the phase values to the  
associated level values. This assignment is ensured using a correspondence table (index  
correction table). The 7500 RTG learns this for the specific application after installation  
(learning period).  
Therefore, after mounting the device, and after completing the basic calibration, a  
history reset must be performed (enter "yes" in the "history reset" (009) function in the  
"basic setup " (00) function group).  
Do not switch off the radar system during filling and emptying operations during the  
teach-in phase. Switching off when there are only negligible level changes produces no  
error.  
Caution!  
"
During the learning period, fast filling/emptying or turbulent surfaces can result in  
switching off and on the phase evaluation. Subsequently observed measurement errors  
will disappear as soon as tank levels come back to areas measured by 7500 RTG  
previously with activated phase evaluation. If the observed measurement errors are  
curetted by dip table entries, the 7500 RTG will take care of these corrections and  
automatically adjust the index correction table. Do NOT correct any settings in the basic  
calibration or the extended calibration.  
Note!  
Immediately after installation, the 7500 RTG measures with the specified mm-accuracy.  
Until the level range has been completely covered by the medium (setting up the  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Commissioning  
Radar Tank Gauge  
correction table), the maximum permissible filling speed is 100 mm level  
change / min. After this, the fill speed has no limitation.  
Function "pipe diam. corr." (032)  
+
E
For level measurement in stilling wells, radar systems require highly precise pipe inner  
diameter data. An mm-exact level measurement cannot be guaranteed for deviations  
from the actual stilling well inner diameter of more than ± 0.1mm to the value entered  
in the function group "basic setup" (00). The errors which occur as a result are linear and  
can be corrected with a dip table containing at least two entries.  
The 7500 RTG also has an automatic pipe inner diameter correction. This adjusts the  
entered stilling well inner diameter (input in the function group  
"basic setup" (00)) to the actual values. However, this presupposes that the value entered  
in the function group "basic setup" (00) matches the actual pipe inner diameter  
accurately as possible. The user-defined value entered in the function group  
"basic setup" (00) can be corrected with this value. In order to do this, switch on the "pipe  
diam. corr." (032) function, after a level change of at least 5 m has occurred since start-  
up. The pipe diameter, which the instrument determines automatically, will then be  
transmitted to the "pipe diameter" (007) function.  
Note!  
Only if the "pipe diameter" (007) function has changed its value, it is necessary to per-  
form a "history reset" (009) and to delete the dip table after activation of the "pipe diam.  
corr." (032) function. Otherwise the level change of 5 m has not yet been exceeded. The  
"pipe diam. corr." (032) function must be deactivated again and the procedure should be  
repeated at a later point of time.  
58  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Commissioning  
Display "custody mode" (0A9)  
+
E
This indicates the instrument calibration mode. The calibration mode (active) can be set  
using the hardware security lock on the electronics (see Page 34).  
Selection:  
• inactive  
• active pos.  
• active neg.  
active pos.  
The custody mode (instrument is lead-sealed and accurate to the nearest mm) is active  
and is held.  
active neg.  
Custody mode (instrument is lead-sealed and accurate to the nearest mm) is activated  
and not held, e.g. because the signal-to-noise ratio is less than 10 dB (refer to  
function "echo quality" (056) in the function group "extended calibr." (05)).  
Caution!  
After entering all the values and completing mounting and aligning work, enter the  
Reset Code "555" in the function "history reset" (009) of the "basic setup" (00) function  
group to reset the instrument history for auto-correction.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Commissioning  
Radar Tank Gauge  
Dip table  
The dip table is used to correct the level readings of the 7500 RTG using independently  
taken hand dips. The dip table is used in particular to adapt the level gauge to the  
specific application conditions as mechanical offset and tank/stilling well design.  
Depending on national regulations, national inspectors will dip the tank at one to three  
levels during a calibration run and check the level readings.  
Only one value pair must be entered into the dip table to correct the measurement  
offset.  
If a second value pair is entered into the dip table, the 7500 RTG accepts the corrected  
measured values identically for both value pairs. All other measured values are  
determined by linear extrapolation.  
If you enter more than two value pairs, the system carries out a linear interpolation  
between adjacent value pairs. Outside these value pairs, extrapolation is also linear.  
basic setup  
history reset  
dip table  
alternatives  
preferred choice:  
hand dip and  
immediate  
offset correction in  
semi-automatic mode  
collect hand dip and  
measurement data over  
full measurement range  
collect further hand dip data;  
evaluate collected data;  
enter characteristic value  
pairs into the dip table  
using the manual mode  
if deviation from measurements  
> 4 mm and level change > 2 m:  
enter a new dip value  
into dip table using the  
semi-automatic mode  
Figure 8: Alternative procedures to fill the dip table.  
To collect and enter data into the dip table, two alternative procedures may be carried  
out. In order not to mix up measurement values corrected by the offset or linearization  
of the dip table with uncorrected measurement values, it is recommended to use the  
semi-automatic mode of the dip table to enter new data pairs. In this case, the first dip  
value should be entered immediately after the basic calibration. Further linearization  
points should be entered only after a level change of at least 2 m (see Figure 8:,  
preferred choice) and a deviation between the "uncorrected measurement value" and the  
hand dip value of at least 4mm.  
If this procedure can not be followed, then NO value pair should be entered into the dip  
table after basic calibration. Measurement data and hand dip values should be collected  
over the full measurement range and be evaluated with regard to a good linear fit. Only  
then characteristic value pairs should be entered into the dip table using the "manual  
mode" (see Figure 8:, right side). If further linearization is needed, further hand dip  
values should be entered using only the "semi-automatic mode".  
Note!  
The offset should NOT be determined and entered within the close range of the antenna  
(conf. definition of the safety distance) or immediately in the range of the tank bottom,  
because within these ranges interferences of the radar signal may occur.  
60  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Commissioning  
Note!  
The dip table can be printed out using the ToF-Tool. Before doing this, the ToF Tool  
must be reconnected to the instrument in order to update the values within the ToF Tool.  
Note!  
Make your inputs into the dip table in semi-automatic mode. We advise you to leave  
"auto correction" (031) activated ("on") while you enter your inputs.  
Caution!  
After entering one or more points into the dip table, make sure that the dip table is  
activated and left in the "table on" dip table mode.  
Function "dip table state" (037)  
+
E
This function displays the dip table status.  
Display:  
• table on  
table off  
table on  
Indicates whether the dip table is active.  
table off  
Indicates whether the dip table is not active.  
Function "dip table mode" (033)  
+
E
The dip table can be switched on or off using this function.  
Selection:  
• manual  
• semi-automatic  
• table on  
table off  
• clear table  
• view  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Commissioning  
Radar Tank Gauge  
manual  
The value pairs in the dip table can be read and written. You can enter the measured  
value and the dip value.  
–uncorrected measured value:  
This is the measured value supplied by the instrument, NOT corrected by the dip  
table. The choice of measured value, level or remaining fill height is dependent on  
the instrument setting.  
–Dip value:  
This is the level or distance to flange respectively, given by the hand dip. This value  
should be used to correct the measured value.  
The "manual mode" of the dip table can be used to enter collected data after a series  
of data pairs taken at different tank levels.  
Note!  
The bigger the distance between the different levels while taking hand dips, the more  
accurate the linearization of the dip table will be.  
semi-automatic  
The value pairs in the dip table can be read. You can enter the dip value only. When there  
are new value pairs, the current level or distance is accepted as the measured value.  
table on  
The dip table is switched on.  
table off  
The dip table is switched off.  
clear table  
The complete dip table is deleted. The table is switched off. The number of free table  
entries is set to the maximum value (= 32).  
View  
The value pairs in the dip table can only be read. You can still select this menu option,  
even if there is no dip table available. In this case, the number of free table entries is at  
maximum value (= 32).  
Function "dip table" (034)  
+
E
This function edits measured variable. The number behind the entry "remain" indicates  
the current number of remaining free value pairs. The maximum number of value pairs  
is 32; after each entry, the remaining number is decremented.  
Note!  
The uncorrected measured value is displayed in the "dip table" (034) function. This may  
differ considerably from the measured values when a dip table is activated.  
Function "dip table" (035)  
+
E
This function edits the dip value.  
62  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Commissioning  
Function "dip table handl." (036)  
+
E
Use this function to enter the dip value (level or distance) which will correct the mea-  
surement values.  
Selection:  
new point  
• edit point  
• store point  
• delete point  
• return  
• next point  
• previous point  
General procedure:  
To enter a new point into the dip table, use  
"new point" to enter the value (pairs),  
"store point" to sort the new value (pairs),  
"return" to go to the dip table mode and  
"table on" to activate the dip table.  
new point  
You can enter a new point. A suggested value is displayed for the measured variable, the  
dip value of the current level or the distance. With semi-automatic inputs, the current  
level or the current remaining fill height is displayed as proposed dip value. The new  
value pair can be altered without selecting the  
"edit point" parameter.  
If the table is full, you can still select this parameter. In this case, the number of free  
table entries stands at minimum value (= 0).  
edit point  
The displayed value pair can be changed. Only the dip value can be changed with semi-  
automatic input mode.  
Caution!  
To accept the value pair in the table, confirm it with "store point".  
store point  
The displayed value pair is sorted in the table.  
Note!  
For sorting, the following criteria must be met:  
• Measured variables may not be equal but have different dip values.  
• A measured variable available in the table is recognized as equal when it is closer than  
1 mm to the sorting value.  
• After successful sorting, the setting remains at "edit point" and the number of free  
table entries is decremented.  
Caution!  
If the value cannot be sorted, the setting remains at the previous menu option. No  
warning or error message is generated. However, the number of remaining table entries  
is not decremented.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Commissioning  
Radar Tank Gauge  
delete point  
The currently displayed point is deleted from the table. After deletion, the previous point  
is displayed. If the table only consisted of one point before deletion, then the current  
measured variable is displayed as a value pair.  
return  
By selecting this point, you return to the function "dip table mode" (033).  
next point  
This scrolls down in the table. If the table is empty, you can still select this option.  
However, the displayed value does not change.  
previous point  
This scrolls up in the table. If the table is empty, you can still select this option. However,  
the displayed value does not change.  
Caution!  
After entering one or more points into the dip table, make sure that the dip table is  
activated in the "table on" dip table mode.  
64  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Commissioning  
6.5.2  
Envelope curve with VU 331  
After the basic setup, an evaluation of the measurement with the aid of the envelope  
curve ("display" (09) function group) is recommended.  
Function "plot settings" (09A)  
+
E
Here you can select which information is shown on the display:  
• envelope curve  
• env. curve+FAC (for FAC see 7500 RTG "Service manual and description of  
instrument functions")  
• env. curve+suppress. (i.e. the tank map is also displayed)  
Function "recording curve" (09B)  
This function determines whether the envelope curve is read as:  
single curve  
or  
• cyclic  
+
E
Note!  
If the envelope curve mode is active on the display, the measured values are updated in  
a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the  
measuring point has been optimized.  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Commissioning  
Radar Tank Gauge  
6.6  
Basic Setup with the ToF Tool  
To carry out the basic setup with the ToF Tool operating program, proceed as follows:  
• Start the ToF Tool operating program and establish a connection  
• Select the "basic setup" function group in the navigation bar  
The following display appears on the screen:  
Basic Setup step 1/5:  
• Status image  
• Enter the measuring point description (TAG number).  
Change to the next page  
Note!  
• Each parameter that is changed must be confirmed with the RETURN key!  
• The "Next" button moves you to the next screen display:  
66  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Commissioning  
Basic Setup step 2/5:  
• Enter the application parameters:  
–tank shape (for a description, see page 49)  
–medium property (for a description, see page 50)  
–process cond. (for a description, see page 51)  
Basic Setup step 3/5:  
If "stilling well" or "bypass" is selected in the "tank shape" function, the following display  
appears on the screen:  
• empty calibr. (for a description, see page 52)  
• full calibr. (for a description, see page 52)  
• Diameter of bypass / stilling well (for a description, see page 53)  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Commissioning  
Radar Tank Gauge  
Note!  
You can also specify the pipe diameter in this display.  
Basic Setup step 4/5:  
• This step starts the tank mapping  
• The measured distance and the current measured value are always displayed in the  
header  
• A description is given on page 56  
measured value  
distance  
Step 5/5:  
After the first installation of the device, initialise the index correction table (compare  
page 57) by activating the history reset 555.  
68  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Commissioning  
6.6.1  
Envelope curve with the ToF Tool  
After the basic setup, an evaluation of the measurement using the envelope curve is  
recommended.  
6.6.2  
User-specific applications (operation)  
To set the parameters of user-specific applications, see the 7500 RTG "Service manual  
and description of instrument functions".  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Commissioning  
Radar Tank Gauge  
6.7  
Mounting calibration with the ToF Tool  
To carry out the basic setup with the ToF Tool operating program, proceed as follows:  
• Start the ToF Tool operating program and establish a connection  
• Select the "mounting calibr." function group in the navigation bar  
The following display appears on the screen:  
Mounting calibration step 1/2:  
• auto correction (description see page 57)  
• pipe diam. corr. (description see page 58)  
change to next page  
Note!  
• Each parameter that is changed must be confirmed with the RETURN key!  
• the "Next" button moves you to the next screen display:  
70  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Commissioning  
Mounting calibration step 2/2:  
• dip table mode (description see page 61)  
• meas. v. (description see page 62)  
• dip value (see page 62)  
• dip table handl. (description see page 63)  
• dip table state (description see page 61)  
• left dip t.entr. (description see page 61)  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Commissioning  
Radar Tank Gauge  
72  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Maintenance  
7
Maintenance  
The 7500 RTG measuring instrument requires no special maintenance.  
Exterior cleaning  
When cleaning the exterior of measuring devices, always use cleaning agents that do not  
attack the surface of the housing and the seals.  
Replacement  
After a complete 7500 RTG or electronic module has been replaced, the parameters can  
be downloaded into the instrument again via the communication interface. Prerequisite  
to this is that the data were uploaded to the PC beforehand using the ToF Tool /  
Commuwin II.  
Measurement can continue without having to carry out a new setup.  
• You may have to activate linearization  
• You may need to record the tank map again  
After an antenna component has been replaced, a new calibration must be carried out.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
Radar Tank Gauge  
74  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Accessories  
8
Accessories  
Various accessories, which can be ordered separately from Varec, are available for the  
7500 RTG.  
Weather protection cover  
A Weather protection cover made of stainless steel is available for outdoor mounting  
(order code: 543199-0001). The shipment includes the protective cover and tension  
clamp.  
Commubox FXA 191 HART  
For intrinsically safe communication with ToF Tool or Commuwin II via the RS 232C-  
interface.  
Service adapter FXA 193  
For communication with ToF Tool via the display connector. (Bestell-Nr.: 50095566).  
Commuwin II  
Operating software for intelligent instruments.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Accessories  
Radar Tank Gauge  
76  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Troubleshooting  
9
Troubleshooting  
9.1  
Troubleshooting instructions  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
Radar Tank Gauge  
7500 RTG - Troubleshooting  
78  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Troubleshooting  
9.2  
System error messages  
Code  
Description  
Possible cause  
Remedy  
A102  
checksum error  
general reset & new  
calibr.required  
device has been powered off  
before data could be stored;  
emc problem; E²PROM defect  
reset;  
avoid emc problem; if  
alarm prevails after reset,  
exchange electronics  
W103  
initialising - please  
wait  
E²PROM storage not yet  
finished  
wait some seconds; if  
warning prevails, exchange  
electronics  
A106  
A110  
downloading please  
wait  
processing data download  
wait until warning  
disappears  
checksum error  
general reset & new  
calibr.required  
device has been powered off  
before data could be stored;  
emc problem; E²PROM defect  
reset;  
avoid emc problem; if  
alarm prevails after reset,  
exchange electronics  
A111  
A113  
A114  
A115  
electronics defect  
electronics defect  
electronics defect  
electronics defect  
RAM defective  
reset;  
if alarm prevails after  
reset, exchange electronics  
ROM defective  
reset;  
if alarm prevails after  
reset, exchange electronics  
E2PROM defective  
general hardware problem  
reset;  
if alarm prevails after  
reset, exchange electronics  
reset;  
if alarm prevails after  
reset, exchange electronics  
A116  
A121  
W153  
download error  
repeat download  
checksum of stored data not  
correct  
restart download of data  
electronics defect  
no factory calibration existant;  
E²PROM defective  
contact service  
initialising - please  
wait  
initialisation of electronics  
wait some seconds; if  
warning prevails, power off  
device and power on again  
A155  
A160  
electronics defect  
hardware problem  
reset;  
if alarm prevails after  
reset, exchange electronics  
checksum error  
general reset & new  
calibr.required  
device has been powered off  
before data could be stored;  
emc problem; E²PROM defect  
reset;  
avoid emc problem; if  
alarm prevails after reset,  
exchange electronics  
A164  
A171  
A231  
electronics defect  
electronics defect  
hardware problem  
hardware problem  
reset;  
if alarm prevails after  
reset, exchange electronics  
reset;  
if alarm prevails after  
reset, exchange electronics  
sensor 1 defect  
HF module or electronics  
defective  
exchange HF module or  
electronics  
check connection  
Table 3: System error messages  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Radar Tank Gauge  
Code  
A270  
Description  
Possible cause  
Remedy  
custody switch  
undef  
switch for custody transfer  
may be defective  
check position of custody  
switch  
check position  
exchange electronics  
#
inconsistency between phase  
and amplitude evaluation  
inconsistent microfactor  
inconsistent index mapping  
check basic calibration  
check mounting calibration  
check echo quality  
reset history "555"  
check stilling pipe  
diameter  
switch off autocorrection  
A272  
W275  
W511  
A512  
W601  
W611  
electronics defect  
amplifier  
inconsistency in amplification  
offset drift of A/D commuter  
exchange electronics  
electronics defect  
factory setting  
exchange electronics  
no factory  
factory calibration has been  
deleted  
record new factory  
calibration  
calibration ch1  
recording of  
mapping active  
wait some seconds until  
alarm disappears  
mapping please wait  
linearization ch1  
linearization not  
correct linearization table  
curve not monotone  
monotonously increasing  
less than 2  
number of entered  
correct linearization table  
linearization points  
for channel 1  
linearization points < 2  
W621  
E641  
simulation ch. 1 on  
simulation mode is active  
switch off simulation mode  
no usable echo  
channel 1  
echo lost due to application  
conditions of built up on  
antenna  
check installation;  
optimize orientation of  
antenna; clean antenna  
check calibr.  
E651  
A671  
W681  
level in safety  
distance - risk of  
overspill  
level in safety distance  
alarm will disappear as  
soon as level leaves safety  
distance;  
linearization ch1 not  
complete, not  
usable  
linearization table is in edit  
mode  
activate linearization table  
current ch1 out of  
range  
current out of range (3,8 mA  
... 21,5 mA)  
check calibration and  
linearization  
Table 3: System error messages  
80  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Troubleshooting  
9.3  
Application errors  
Error  
Output  
Possible cause  
Remedy  
Depending on the configuration  
See table of  
1. See table of error messages  
A warning or  
alarm has  
occurred.  
error messages  
Measured distance yes 1. Check empty calibr. (005) and  
Measured  
value (00) is  
incorrect  
(008) OK?  
full calibr. (006).  
20 mA/100%  
expected  
F m/ft  
2. Check linearization:  
level/ullage (040)  
max. scale (046)  
diameter vessel (047)  
Check table  
no ↓  
actual  
E m/ft  
Measurement in  
bypass or stilling  
well?  
yes 1. Is bypass or stilling well  
selected  
4 mA/0%  
t
in tank shape (002)?  
2. Is the pipe diameter  
(007) correct?  
no  
Is an  
yes 1. offset (057)  
FAR 10 antenna  
extension  
correctly set?  
being used?  
no  
An interference  
echo  
yes 1. Carry out tank mapping  
basic setup  
may have been  
evaluated.  
Interference echo  
from  
1. Carry out tank mapping  
No change off  
measured  
value on  
basic setup  
installations,  
nozzle  
20 mA/100%  
2. If necessary, clean antenna  
filling/empty-  
ing  
or extension on  
the  
3. If necessary, select better  
mounting position  
actual  
antenna  
expected  
4 mA/0%  
t
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Radar Tank Gauge  
Error  
Output  
Possible cause  
Remedy  
Signal is weakened  
by the rough  
surface — the  
interference  
echoes  
1. Carry out tank mapping  
If the surface  
is not calm  
(e.g. filling,  
emptying, agi-  
tator run-  
ning), the  
measured  
value  
basic setup  
20 mA/100%  
actual  
2. Set the process cond. (004) to  
"turb. surface" or  
"agitator"  
are sometimes  
stronger  
3. Increase the output damping  
(058)  
expected  
jumps sporad-  
ically to a  
higher  
4. Optimize the orientation  
4 mA/0%  
t →  
5. If necessary, select a better  
mounting position  
level  
and/or larger antenna  
20 mA/100%  
actual  
expected  
4 mA/0%  
t →  
Multiple echoes  
yes 1. Check the tank shape (002),  
e.g. "dome ceiling" or  
During filling/  
emptying  
"horizontal cyl"  
the measured  
value jumps  
downwards  
20 mA/100%  
actual  
2. In the range of the blocking dist.  
(059) there is no echo evalua-  
tion  
Adapt the value  
expected  
3. If possible, do not select  
central installation position  
4 mA/0%  
t →  
4. Perhaps use a stilling well  
Level echo is too  
weak.  
yes 1. Check application parameters  
E 641 (loss of  
echo)  
(002), (003) and (004)  
Possible causes:  
• Rough surface  
due to filling/  
emptying  
20 mA/100%  
2. Optimize alignment  
3. If necessary, select a better  
installation position and/or  
larger antenna  
actual  
• Agitator running  
• Foam  
E 641  
expected  
4 mA/0%  
t  
noise level during  
the initialisation  
phase to high.  
Repeat once more empty calibr.  
(005).  
E 641 (loss of  
echo) after  
If the instrument is configured to Hold  
by loss of echo the output is set to any  
value/current.  
Caution!  
turn on the  
power supply  
Before conformation change with  
O or S to the edit mode.  
82  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Troubleshooting  
9.4  
Spare parts  
Note!  
You can order spare parts directly from your Varec service organization by giving the  
order code and the serial number which is printed on the measuring transducer  
nameplate (see page 7). The corresponding spare part number also appears on each  
spare part. Installation instructions are given on the instruction card that is also  
delivered.  
Note!  
If the calibration seal is broken, the national calibration authority should normally be  
informed within 24 hours.  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Radar Tank Gauge  
7532 RTG  
The customer may exchange  
modular assemblies in  
accordance with Varec  
instructions!  
84  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Troubleshooting  
Spare parts 7532 RTG  
Process connection without antenna  
Planar antenna  
7532 RTG-  
detailed order structure and variants  
see spare parts price list  
O-ring 49,21 x 3,53 EPDM  
(Seal set 52005628)  
O-ring 49,21 x 3,53 EPDM  
(Seal set 52005628)  
O-ring  
85,32 x 3,53 FKM (green)  
85,32 x 3,53 HNBR12-70  
(black)  
O-ring  
85,32 x 3,53 FKM (green)  
85,32 x 3,53 HNBR12-70  
(black)  
Antenna size  
Seal  
5200 6193  
DN 150 ( 6")  
DN 150 ( 6")  
DN 200 ( 8")  
DN 200 ( 8")  
DN 250 (10")  
DN 250 (10")  
HNBR  
FKM  
HNBR  
FKM  
HNBR  
FKM  
5200 6332  
5200 6194  
5200 6333  
5200 6195  
5200 6334  
Modification nameplate  
When ordering parts that are listed in the product structure (see page 8) , a check must  
be made as to whether the instrument description on the nameplate is still valid, e.g. for:  
• an antenna component,  
• an electronics module,  
• an RF module,  
• a VU 331 operating and display module,  
• a housing cover with window.  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Radar Tank Gauge  
Housing T12  
The complete order code must be specified when ordering the replacement housing so  
that the correct nameplate can be delivered, e.g.  
• 7532 RTG-AACWJAC1AA  
You must label the nameplate yourself.  
Caution!  
• It is not possible to convert a standard instrument into an Ex instrument by simply  
exchanging parts.  
• When repairing certified instruments, the relevant regulations must be followed.  
• For FM approved instruments, it is forbidden to make any changes to the instrument  
that are not expressly authorized in the operating manual. Contravening this  
prohibition can invalidate the approval for operation of the instrument.  
9.5  
Return  
If you need to send a 7500 RTG back to Varec for repair, please send a completed copy  
of the form printed on the last page.  
• An exact description of the application.  
• The chemical and physical characteristics of the product.  
• A short description of the error that occurred.  
• If necessary, give the error code.  
Please carry out the measures described in section 1.4, “Return” on page 5 before  
sending a 7500 RTG back for repair.  
9.6  
Disposal  
In case of disposal please separate the different components according to their material  
consistence.  
9.7  
Software history  
Software version  
/ Date  
Software changes  
Documentation changes  
V 1.00.00 /  
12.2000  
Original software.  
Operated via:  
– ToF Tool  
– Commuwin II (from version  
2.05.03)  
– HART communicator DXR 375  
with Rev. 1, DD 1.  
V 01.02.00 /  
03.2002  
simplified commissioning  
history reset in basic calibration.  
Operated via:  
– ToF Tool (V3.0)  
– Commuwin II (from version  
2.05.03)  
– HART communicator DXR 375  
with Rev. 1, DD 1.  
86  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Technical data  
10 Technical data  
10.1 Technical data at a glance  
Application  
Application  
The 7500 RTG is used for highly accurate level measurement in  
storage tanks and can be applied in custody transfer applications. It  
meets the relevant requirements according to OIML R85 and API 3.1B.  
• The 7532 RTG with planar antenna is specifically and only suited for  
stilling well applications with ranges up to 38 m (124 ft).  
Function and system design  
Measuring principle  
The 7500 RTG is a "downward-looking" measuring system, operating  
based on the time-of-flight method. It measures the distance from  
the reference point (process connection) to the product surface. Radar  
impulses are emitted by an antenna, reflected off the product surface  
and received again by the radar system.  
Equipment architecture  
The 7500 RTG can be used for measurement in a stilling well as well  
as in free space. The different instrument versions are applied as  
follows:  
• The 7532 RTG with planar antenna is the preferred device in stilling  
wells 150 mm.  
• The instruments are equipped with a passive 4…20 mA output with  
HART protocol.  
Input  
Measured variable  
The measured variable is the distance between a reference point  
(mounting flange) and a reflective surface (e.g. medium surface). The  
measured value and all parameters are displayed using either metrical  
SI-units or US/UK-units (inch, ft, …).  
The level is calculated based on the tank height entered.  
The level can be converted into other units (volume, mass) by means  
of a linearization.  
In order to compensate for non-linear effects like movement of the  
tank roof, an additional correction table (diptable) can be entered.  
Measuring range  
Output signal  
Output  
4…20 mA with HART protocol:  
this version can be operated via the PC operating software ToF Tool  
and Commuwin II. The instrument supports both point-to-point and  
multidrop operation.  
Signal on alarm  
Error information can be accessed via the following interfaces:  
• Local display:  
– Error symbol (see page 35)  
– Plain text display  
– LED’s: red LED continuously on = alarm, red LED flashes = warn-  
ing  
• Current output  
• Digital interface  
Galvanic isolation  
500 V towards ground.  
500 V between power supply and signal  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Technical data  
Radar Tank Gauge  
Auxiliary energy  
Electrical connection  
Load HART  
Housing T 12 with separate terminal compartment.  
Minimum load for HART communication: 250 Ω  
Cable entry  
Cable gland: M20x1.5 or Pg13.5  
Cable entry: G ½ or ½ NPT  
Supply voltage  
Power consumption  
Current consumption  
Power supply  
Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V.  
Max. 21 mA (50 mA inrush current).  
For stand alone operation recommended via e.g. Varec RN 221N/Z.  
Performance characteristics  
Reference operating  
conditions  
According to OIML R85:  
• Temperature = –25…+55 °C (-13…+131 °F)  
• Atmospheric pressure  
• Relative humidity (air) = 65 % ±15%  
• Medium properties: e.g. medium with good reflectivity and calm  
surface.  
• Tank diameter: signal beam hits the tank wall only at one side.  
Note!  
No major interference reflections inside the signal beam.  
Maximum measured  
error  
Absolute accuracy: 0.5 mm (2σ value)  
Inventory Control Versios: ±3 mm  
Proof of accuracy for  
custody transfer ver-  
sions  
The accuracy of each 7500 RTG is established through a calibration  
certificate that records the absolute and relative error at 10  
equidistant points during the final test. For stilling well measurements  
with 7532 RTG, a NMI / PTB calibrated tape with an absolute accuracy  
of 0.25 mm is used.  
Each 7500 RTG is delivered with the PTB and NMi type approval.  
Additional initial factory verifications for custody applications are  
available on demand for all 7500 RTG.  
Maximum fill speed  
By the first pass trough of measuring range: 100 mm/min., after it  
unlimited.  
Non-repeatability  
Hysteresis  
0,3 mm (1/64")  
0.3 mm  
Resolution  
digital: 0.1 mm  
analogue: 0.03 % of measuring range  
Settling time  
Typical 15 sec  
Long-term drift  
The long-term drift is within the specified accuracy.  
Within the specified accuracy according to OIML R85.  
Influence of ambient  
temperature  
Software reliability  
The software used in the 7500 RTG fulfills the requirements of OIML  
R85. This particularly includes:  
• cyclical test of data consistency  
• non-volatile memory  
• segmented data storage  
The 7500 RTG continuously monitor the compliance with accuracy  
requirements for custody transfer measurements according to OIML  
R85. If the accuracy cannot be maintained, a specific alarm is  
generated on the local display and via the digital communication.  
88  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Technical data  
Inventory Control Ver-  
sions  
All device types can be delivered as "Inventory Control Versions" with a  
reduced accuracy of ± 3mm (under reference conditions).  
To these versions, the calibration certificate or custody transfer type  
approval is NOT attached.  
The "Inventory Control Versions" can be selected by choosing the  
Operating conditions  
Operating conditions  
Engineering tips  
Environment  
Ambient temperature  
range  
Ambient temperature for the transmitter:  
• Standard: -40 °C … +80 °C (-40 °F … +176 °F)  
• For calibration to regulatory standards: -25 °C ... +60 °C (-30  
°F…+140 °F)  
With Tu<-20 °C and Tu>+60 °C the operability of the LC-display is  
reduced.  
A weather protection cover should be used for outdoor operation if  
the instrument is exposed to direct sunlight.  
Storage temperature  
Climate class  
-40 °C ... +80 °C (-40 °F … +176°F)  
DIN EN 60068-2-38 (test Z/AD)  
Degree of protection  
• housing: IP 65, NEMA 4X (open housing: IP20, NEMA 1)  
• antenna: IP 68 (NEMA 6P)  
Vibration resistance  
DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 5 (m/s²)²/Hz  
See »Technical Information« TEC028  
Cleaning of the antenna  
Electromagnetic com-  
patibility  
• emissions according to EN 61326; equipment class B  
• compatibility according to EN 61326; appendix A (industrial area,  
10 V/m) and Namur recommendation EMC (NE 21).  
Process conditions  
Process temperature  
range  
See »Technical Information« TEC028  
See »Technical Information« TEC028  
See »Technical Information« TEC028  
Process temperature  
limits  
Process pressure limits  
Dielectric constant  
• in a stilling well: εr 1.4  
• in free space: εr 1.9  
Wetted parts  
• Planar, gas-tight  
Wetted parts: 1.4435 / HNBR (Hydrated Nitrit Butadien Rubber,  
resistent to NH3) or FKM / PTFE glas fiber laminat  
Note!  
The planar antenna is not resistant to hot vapor!  
• Horn adapter for increase of diameter  
Wetted parts: 1.4435  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Technical data  
Radar Tank Gauge  
Mechanical construction  
Design, dimensions  
Weight  
Approx 6 kg + weight of flange  
Material  
Process connection  
All process connections dispose of a gas-tight glass feed-through to  
prevent any gas leakage to the inside of the housing.  
Human interface  
Operation concept  
Display  
Certificates and approvals  
CE approval  
The measuring system meets the legal requirements of the EC-  
guidelines. Varec confirms the instrument passing the required tests  
by attaching the CE-mark.  
RF approvals  
R&TTE 1999/5/EG, FCC CRF 47, part 15  
Overspill protection  
PTB , NMi and many other national approvals  
External standards and  
guidelines  
EN 60529  
Protection c3lass of housing (IP-code)  
EN 61010  
Safety regulations for electrical devices for measurement, control,  
regulation and laboratory use.  
EN 61326  
Emissions (equipment class B), compatibility (appendix A – industrial  
area)  
NAMUR  
Standards committee for measurement and control in the chemical  
industry  
API (American Petroleum Institute)  
Particularly "Manual of Petroleum Measurement Standards".  
OIML R85 (Organisation Internationale de Metrologie Legale)  
Ex approval  
XA 081F-A  
Installation 7500 RTG (T12 / EEx ia IIC T6…T1)  
PTB 00 ATEX 2067 X, Equipment marking: (II 1/2 G)  
Ordering Information  
The Varec service organisation can provide detailed ordering  
information an information on the order codes on request.  
Accessories  
Supplementary Documentation  
Supplementary  
Documentation  
• System Information  
• Technical Information  
• Operating Instructions  
90  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
7532  
Appendix  
11 Appendix  
11.1  
Operating menu HART (Display modul), ToF Tool  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Appendix  
Radar Tank Gauge  
basic setup  
00  
tank shape  
002  
010  
030  
medium property 003  
process cond.  
004  
empty calibr.  
enter value  
005  
full calibr.  
006  
dome ceiling  
horizontal cyl.  
bypass  
stilling well  
flat ceiling  
sphere  
unknown  
DK: < 1.9  
DK: 1.9 … 4  
DK: 4 … 10  
DK: > 10  
standard  
enter value  
calm surface  
turb. surface  
add. agitator  
fast change  
test: no filter  
pipe diameter  
enter value  
007  
safety settings  
01  
output on alarm  
outp. echo loss  
012  
delay time  
014  
MIN -10% 3.6mA  
MAX 110% 22mA  
hold  
alarm  
hold  
in case of echo loss  
max. 4000 sec.  
default: 30 s  
user specific  
ramp %MB/min  
ramp %/min  
enter value  
013  
output on alarm  
enter value  
011  
033  
tank gauging  
dip table  
dip table mode  
mounting calibr. 03  
view  
manual  
semi-automatic  
dip table state  
dip table state  
037  
037  
dip table  
meas.v.  
dip value  
034  
034  
035  
dip table handl.  
036  
next point  
previous point  
new point  
edit point  
store point  
delete point  
table on  
table off  
clear table  
auto correct.  
level/ullage  
return  
linearisation  
04  
040  
040  
linearisation  
041  
041  
level CU  
ullage CU  
manual  
semi-automatic  
table on  
customer unit  
042  
linearisation  
table no.  
input level  
input volume  
next point  
yes  
045  
043  
044  
045  
no  
horizontal cyl  
linear  
customer unit  
customer unit  
042  
042  
reset table  
level DU  
ullage DU  
040  
050  
extended calibr.  
05  
selection  
mapping  
dist./meas value  
008  
check distance  
051  
range of mapping 052  
start mapping  
053  
D and L  
are displayed  
distance = ok  
dist. too small  
manual  
input of  
mapping range  
off  
on  
dist. unknown  
dist. too big  
common  
extended map..  
pres. Map dist  
is displayed  
054  
063  
cust. Tank map  
055  
inactive  
active  
reset  
output  
06  
commun. address 060  
no. of preambels  
061  
low output limit  
062  
093  
fixed current  
off  
on  
off  
on  
fixed cur. value  
064  
095  
display  
09  
0A  
language  
092  
0A1  
back to home  
format display  
094  
no. of decimals  
enter time  
default: 100 s  
decimal  
1/16”  
x
x.x  
x.xx  
x.xxx  
diagnostics  
present error  
tag no.  
0A0  
0C0  
previous error  
clear last error  
0A2  
0C2  
reset  
0A3  
0C3  
unlock parameter 0A4  
for reset code  
see manual  
for reset code  
see manual  
software no.  
system parameter 0C  
protocol+sw-no.  
serial no.  
0C4  
custody transfer  
Note! The default values of the parameters are typed in boldface.  
92  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Appendix  
dist./meas.value  
008  
check distance  
051  
range of mapping  
052  
start mapping  
053  
history reset  
009  
distance = ok  
dist. too small  
dist. too big  
manual  
input of  
mapping range  
off  
on  
no  
yes  
D and L  
are displayed  
dist. unknown  
safety distance  
015  
in safety dist.  
016  
ackn. alarm  
017  
overspill protection 018  
from blocking  
distance  
default: 0.1m  
alarm  
warning  
self holding  
no  
yes  
standard  
german WHG  
auto correction  
031  
pipe diam. corr.  
032  
047  
off  
on  
off  
on  
max. scale  
max. scale  
046  
046  
diameter vessel  
dist./meas.value  
008  
D and L  
are displayed  
echo quality  
is displayed  
056  
offset  
057  
output damping  
058  
blocking dist.  
is displayed  
059  
will be added to the  
measured level  
enter value  
default: 5 s  
simulation  
065  
output current  
067  
sim. off  
sim. level  
sim. volume  
sim. current  
simulation value  
display test  
066  
097  
sep. character  
096  
plot settings  
09A  
recording curve  
09B  
0A8  
envelope curve  
env.curve+FAC  
env.curve+cust.map  
single curve  
cyclic  
. point  
, comma  
off  
on  
measured dist.  
distance unit  
0A5  
0C5  
measured level  
download mode  
0A6  
0C8  
application par.  
custody mode  
0A9  
not modified  
modified  
inaktiv  
aktiv positiv  
aktiv negativ  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Radar Tank Gauge  
11.2  
Operating matrix HART / Commuwin II  
94  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Appendix  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Radar Tank Gauge  
11.3  
Description of functions  
Note!  
A detailed description of the function groups, functions and parameters is given in the  
the 7500 RTG "Service manual and description of instrument functions".  
96  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7532  
Appendix  
11.4  
Function and system design  
11.4.1 Measuring principle  
The 7500 RTG is a "downward-looking" measuring system, operating based on the  
time-of-flight method. It measures the distance from the reference point (process  
connection) to the product surface. Radar impulses are emitted by an antenna, reflected  
off the product surface and received again by the radar system.  
Input  
The reflected radar impulses are received by the antenna and transmitted into the  
electronics. A microprocessor evaluates the signal and identifies the level echo caused  
by the reflection of the radar impulse at the product surface. The unambiguous signal  
identification is accomplished by the PulseMaster® software based on many years of  
experience with time-of-flight technology. The mm-accuracy of the 7500 RTG is  
achieved with the patented algorithms of the PhaseMaster® software.  
The distance D to the product surface is proportional to the travel time t of the impulse:  
D = c · t/2,  
with c being the speed of light.  
Based on the known empty distance E, the level L is calculated:  
L = E – D  
Reference point for "E" is the lower surface of the process connection.  
The 7500 RTG is equipped with functions to suppress interference echoes. The user can  
activate these functions. They ensure that interference echoes (e.g. from edges and weld  
seams) are not interpreted as level echo.  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix  
Radar Tank Gauge  
Output  
The 7500 RTG is commissioned by entering an empty distance E (=zero), a full distance  
F (=span), and an application parameter. The application parameter automatically  
adapts the instrument to the measuring conditions. The data points “E” and “F”  
correspond with 4mA and 20mA for instruments with current output. They correspond  
with 0 % and 100% for digital outputs and the display module.  
A linearization with max. 32 points, based on a table entered either manually or semi-  
automatically, can be activated locally or remotely. This function provides a  
measurement in engineering units and a linear output signal for spheres, horizontal  
cylindrical tanks, and vessels with conical outlet.  
11.4.2 Equipment architecture  
Stand-alone  
The 7500 RTG can be used for measurement in a stilling well as well as in free space.  
The different instrument versions are applied as follows:  
• The 7532 RTG with planar antenna is the preferred device in stilling wells 150 mm.  
• The 7530 RTG with horn antenna can be used in stilling wells with a diameter  
<150 mm. However, for these diameters no custody transfer approval is available.  
• The 7533 RTG with parabolic antenna is preferred for free-space measurements. The  
7530 RTG with horn antenna can be used as an alternative for small nozzle diameters.  
• The 7531 RTG with rod antenna (PTFE) should be used for measurements of highly  
aggressive media (e.g. sulphur).  
• The instruments are equipped with a passive 4…20 mA output with HART protocol.  
The complete measuring system consists of:  
SPS  
- COMMUWIN II  
- ToF Tool  
- ToF Tool  
Service-Adapter  
FXA 193  
Commubox  
FXA 191  
HART  
2x Messumformer-  
speisegerät  
RN 221 N  
Anzeige- und  
Bedienmodul  
VU 331  
ENDRESS  
+
HAUSER  
%
+
E
d
s
dmdm  
as  
a
df  
as  
  l
 .
  f
DEL  
ONLINE  
QUICK SETUP  
OPERATING MENU  
PV  
T
ABAR:  
*
*
*
*
*
*
*
*
1
2
3
352 mbar  
°C  
4
SV  
0
HELP  
SAVE  
6
Page  
Up  
9
Bksp  
Delete  
Page  
On  
#
%
&
A
B
C
D
E
F
1
2
3
Copy  
Paste  
Hot Key  
G
H
I
J
K
L
M
N
O
4
5
6
Insert  
+
Hot Key  
P
)
Q
R
S
T
U
V
W
X
Y
Z
7
8
9
,
(
_
<
>
+
*
/
.
0
-
HART-Handbediengerät  
DXR 375  
375  
FIELD COMMUNICATOR  
FXA 191  
oder  
DXR 375  
98  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Appendix  
On-site operation:  
• with display and operating module VU 331,  
• with a Personal Computer, FXA 193 and the operating software ToF Tool.  
The ToF Tool is a graphical operating software for instruments from Varec that operate  
based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It  
assists with commissioning, securing data, troubleshooting, and documentation of the  
measuring point.  
Remote operation:  
• with HART handheld DXR 35,  
• with a Personal Computer, Commubox FXA 191 and the operating software  
COMMUWIN II respectively ToF Tool.  
• With a Personal Computer, TSM (Tank Side Monitor) and the operating software  
FuelsManager.  
System integration via Rackbus  
Multiple 7500 RTG (or other instruments) can be connected to a higher-level bus system  
via a Gateway ZA:  
• Every HART transmitter via one interface module FXN 672 each.  
• Gateways are available for MODBUS, FIP, PROFIBUS, INTERBUS etc.  
• Both on-site as well as remote operation are possible.  
Integration into the Asset Management System  
The HART interface allows the integration into the AMS® (Asset Management System)  
from Fisher-Rosemount.  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Radar Tank Gauge  
11.4.3 Custody transfer mode  
7500 RTG is a weight and measure approved level transmitter. Either the innage or the  
ullage can be selected as the custody transfer variable.  
The selected variable is the basis for the subsequent calculation of the current amount  
of product in a tank, along with other measured variables such as (average) temperature  
and pressure.  
This opens up numerous application options in custody transfer:  
• Quantity calculation of mineral oils  
• Quantity calculation of alcohols  
11.4.4 Weight and measure approval, Standards Authorities ap-  
proval, Compulsory reapproval  
The type approvals for custody transfer issued by the PTB and NMi, a copy of which is  
enclosed with every device, prove the fundamental suitability of the various types for  
custody transfer.  
In addition to this, the accuracy of every single device is documented using a calibration  
certificate, which is issued in the factory after the device has been tested on a reference  
test rig.  
On request, a separate initial verification of the devices can be carried out with a  
National Standards Authorities inspector present, who issues a preliminary test certifi-  
cate for every device. In the initial verification, the device is tested to ensure that it com-  
plies with the limit of error in legal metrology, which lies at +-2mm for radar measuring  
devices in Germany.  
Essentially, this proves that the devices are weight and measure approved. The devices  
must not, however, be used in custody transfer mode straight away.  
The measuring device is not approved until after the approval after installation by the  
Standards Authorities. For this, the device's level measurement is compared with the  
tank gauging by a National Standards Authorities inspector using manual dips (also "Ini-  
tial verification"). As a rule, a quiescent tank gauging is dipped by hand three times in a  
row and then compared with the value displayed by the level radar. Depending on  
national regulations, the transfer error limit, calculated as the arithmetic mean of the  
absolute deviations of all three measurements, must not exceed double the limit of error  
in legal metrology (compare, for example, the German "Eichordnung" or the American  
"API 3.1B", in which the necessary procedures are also defined).  
Depending on national regulations, this test is repeated with various tank gaugings.  
Using linearization tables to compensate any non-linearities that occur in measurement  
is permitted. For this, the 7500 RTG level radar offers a special dip table, compare  
After the measurement has been approved by an inspector, he seals the level radar at  
the stamp position and thereby also secures the programming status of the device.  
Those operating an approved level transmitter are obligated to obtain reapproval in  
accordance with the applicable national regulations from the Standards Authorities.  
100  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
7532  
Appendix  
11.4.5 Particularities in "approved" operation  
The 7500 RTG level radar is set to custody transfer mode after commissioning using a  
custody locking switch (see page 36). The position of the custody locking switch is  
secured and sealed using the sealing pin.  
During custody transfer measurement, all custody transfer-relevant functions for  
operation are automatically locked, so that the device software can not be used, either  
via local operation or via digital communication settings. This locked status is displayed  
by the key symbol ( ).  
7500 RTG radar devices continuously monitor the compliance with accuracy  
requirements for custody transfer measurements according to OIML R85. If, for  
example, the accuracy cannot be maintained due to quick surface movements, this is  
reported via a separate alarm in the local display (displays "#" symbol) and via digital  
communication.  
11.4.6 Definition of terms  
For definitions and procedures please refer to the following documents:  
• Manual of Petroleum Measurement Standards, Chapter 3 - Tank Gauging,  
Section 1.B - Standard Practice for Level Measurement of Liquid Hydrocarbons in  
Stationary Tanks by Automatic Tank Gauging, American Petroleum Institute, second  
edition, 2001  
• OIML R 85, Organisation Internationale de Métrologie Légale, International  
Recommendation R 85, edition 1998 (E)  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix  
Radar Tank Gauge  
11.4.7 Integrated on tank gauging system  
The Varec Tank Side Monitor 4590 provides integrated communications for sites with  
multiple tanks, each with one or more sensors on the tank, such as radar, spot or  
average temperature, capacitive probe for water detection and/or pressure sensors.  
Multiple protocols out of the Tank Side Monitor guarantee connectivity to nearly any of  
the existing industry standard tank gauging protocols. Optional connectivity of analog  
4...20 mA sensors, digital I/O and analog output simplify full tank sensor integration.  
Use of the proven concept of the intrinsically safe HART bus for all on-tank sensors  
yields extremely low wiring costs, while at the same time providing maximum safety,  
reliability and data availability.  
Fuels Manager  
Software  
7500 RTG  
HART  
4 wire  
RTU 8130  
(remote  
terminal  
unit)  
Tank Side Monitor  
Supply voltage:  
16…253 VAC  
Pressure  
This product may be protected by at least one of the following patents.  
i
• US 5,689,265  
• US 5,387,918 i EP 0 535 196  
EP 0 626 063  
• US 5,659,321 i  
• US 5,594,449  
• US 6,047,598  
• US 5,880,698  
• US 5,926,152  
• US 5,969,666  
• US 5,948,979  
• US 6,054,946  
• US 6,087,978  
• US 6,014,100  
• US 5,614,911 i EP 0 670 048  
EP 0 676 037  
Further patents are pending.  
102  
Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Radar Tank Gauge  
Index  
Index  
A
G
H
B
I
C
K
L
M
D
N
E
O
F
IOM027FVAE0804  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Radar Tank Gauge  
P
W
Q
R
S
T
U
104 Installation and Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7532  
Notes  
IOM027FVAE0804  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Radar Tank Gauge  
Your offical representative  
www.varec.com  
Varec, Inc.  
5834 Peachtree Corners East, Norcross (Atlanta), GA 30092 USA  
Tel: +1 (770) 447-9202 Fax: +1 (770) 662-8939  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LaCie Computer Drive 2big Quadra User Manual
Lenovo Computer Hardware 3729 User Manual
LG Electronics Cell Phone 505C User Manual
LG Electronics Graphics Tablet MFL69080001 User Manual
Makita Cordless Drill 6222DE User Manual
Maytag Dishwasher MFS 25 35 User Manual
Maytag Oven W10304917A User Manual
Maytag Washer MAT14CS User Manual
McIntosh Projector MDLP2 User Manual
Melissa Scale 746 081 User Manual