Liebert Power Supply SERIES 600T User Manual

DISCONTINUED  
PRODUCT  
POWER PROTECTION  
Series 600T™ UPS  
Multi-Module Three Phase  
65 kVA to 750 kVA; 60 Hz  
Operation & Maintenance  
Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1.0  
1.1  
1.2  
1.3  
1.4  
INTRODUCTION  
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
1.4.1  
1.4.2  
1.4.3  
1.4.4  
1.4.5  
1.4.6  
1.4.7  
1.4.8  
Normal (Load on UPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Input Power Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Recharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Redundant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Bypass (Internal) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Off-Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
1.5  
1.6  
Operator Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
2.0  
2.1  
2.2  
THEORY OF OPERATION  
General Component Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Detailed Component Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
2.2.1  
2.2.2  
2.2.3  
2.2.4  
2.2.5  
2.2.6  
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Rectifier/Charger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Battery Charging Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18  
Static Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Redundant Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
3.0  
3.1  
OPERATION  
Display Screen and Operator Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
3.1.1  
3.1.2  
3.1.3  
3.1.4  
3.1.5  
3.1.6  
3.1.7  
3.1.8  
3.1.9  
Master Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
Monitor/Mimic Display Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
Walk-In Display Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40  
Status Reports Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41  
System Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48  
Alarm Limit Settings Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55  
Load Transfer Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57  
Start-Up Procedures Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58  
Shutdown Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60  
3.1.10 Battery Time Screen (Module Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62  
3.1.11 Meter Calibration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65  
3.1.12 Battery Equalize Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66  
3.1.13 Alarm and Status Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67  
3.1.14 Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75  
3.2  
Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78  
3.2.1  
3.2.2  
Load On Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78  
OK To Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79  
i
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.3  
3.2.4  
3.2.5  
3.2.6  
3.2.7  
3.2.8  
3.2.9  
Momentary Overloads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81  
Input Power Failure (Load On Battery) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82  
One Module Off-Line. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83  
Off Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84  
Emergency Modules Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85  
Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86  
System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87  
3.2.10 Maintenance Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88  
Manual Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90  
3.3  
3.4  
3.3.1  
3.3.2  
3.3.3  
Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91  
Load Transfer Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97  
Shutdown Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99  
Automatic Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103  
3.4.1  
3.4.2  
3.4.3  
3.4.4  
3.4.5  
Overloads (Without Transfer). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103  
Automatic Transfers to Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104  
Automatic Retransfers to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104  
Automatic Module Off-Line. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105  
Automatic Emergency Modules Off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105  
4.0  
4.1  
4.2  
4.3  
MAINTENANCE  
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106  
Liebert Customer Service and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108  
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109  
4.3.1  
4.3.2  
4.3.3  
4.3.4  
Record Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109  
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109  
Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110  
Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115  
4.4  
4.5  
4.6  
4.7  
Detection of Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115  
Reporting a Problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116  
Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116  
Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116  
5.0  
5.1  
5.2  
5.3  
5.4  
5.5  
SPECIFICATIONS AND RATINGS  
Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117  
Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118  
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119  
Battery Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119  
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120  
ii  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
Multi-Module UPS, 65-80 kVA (left) and 100-500 kVA (right) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Multi-Module 500-750 kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
System Control Cabinets (SCCs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
SCC Controls and Display Screen with Example of the Monitor/Mimic Screen . . . . . . . . . . . . . . . . . . . . .10  
Module Controls and Display Screen with Example of the Monitor/Mimic Screen . . . . . . . . . . . . . . . . . . . 11  
UPS Module Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
System Control Cabinet (SCC) Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Operator Controls, 65 to 80 kVA (left) and 100 to 500 kVA (right) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24  
System Control Cabinet Operator Controls (SCCB Pictured) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25  
Series 600T UPS and SCC Operator Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
Switches Behind SCC Control Panel Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27  
Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28  
Master Menu Screens, SCC (above) and Module (below). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
SCC Monitor/Mimic Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
Module Monitor/Mimic Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
Monitor/Mimic Display Screen Examples: Normal Power Flowe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35  
Monitor/Mimic Display Screen Examples: Utility Fail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36  
Monitor/Mimic Display Screen Examples: Load on Bypass, UPS Modules On and Charging Battery . . . .37  
Monitor/Mimic Display Screen Examples: Load on UPS, One UPS Module Off Line . . . . . . . . . . . . . . . .38  
Monitor/Mimic Display Screen Examples: Load on Bypass, All UPS Modules Off Line . . . . . . . . . . . . . .39  
Walk-In Display Screen During Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40  
Status Reports Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41  
Present Status Report Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42  
Event History Report Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43  
History Status Report Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44  
Battery Cycle Monitor Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46  
Battery Cycle Monitoring Summary Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47  
Typical Data on Discharge Cycles of 91 to 240 Seconds Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47  
SCC System Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48  
Date Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49  
Time Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50  
Auto Dial Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51  
Modem Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52  
Maximum Auto-Retransfer Attempts Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53  
Module Alarm Limit Settings Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55  
Load Transfer Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57  
SCC Start- Up Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58  
Module Start- Up Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59  
SCC Shutdown Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60  
Module Shutdown Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61  
Battery Time Screen Example - 15 Minute Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62  
Battery Time Screen Example - 45 Minute Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63  
Range of Values for Calculated Battery Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64  
Meter Calibration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65  
Battery Equalize Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66  
SCC Status and Alarm Message Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67  
Load on Bypass (UPS Not Available) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78  
Load on Bypass (UPS Available) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79  
Load on UPS (Bypass Available) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80  
Figure 2  
Figure 3  
Figure 4  
Figure 5  
Figure 6  
Figure 7  
Figure 8  
Figure 9  
Figure 10  
Figure 11  
Figure 12  
Figure 13  
Figure 14  
Figure 15  
Figure 16  
Figure 17  
Figure 18  
Figure 19  
Figure 20  
Figure 21  
Figure 22  
Figure 23  
Figure 24  
Figure 25  
Figure 26  
Figure 27  
Figure 28  
Figure 29  
Figure 30  
Figure 31  
Figure 32  
Figure 33  
Figure 34  
Figure 35  
Figure 36  
Figure 37  
Figure 38  
Figure 39  
Figure 40  
Figure 41  
Figure 42  
Figure 43  
Figure 44  
Figure 45  
Figure 46  
Figure 47  
Figure 48  
Figure 49  
iii  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 50  
Figure 51  
Figure 52  
Figure 53  
Figure 54  
Figure 55  
Figure 56  
Figure 57  
Figure 58  
Figure 59  
Figure 60  
Figure 61  
Figure 62  
Figure 63  
Figure 64  
Momentary Overload (Pulsed Static Bypass Switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81  
Input Power Fail (Load on Battery) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82  
One Module Off-Line (Load on UPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83  
Load on UPS (Battery Not Available) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84  
Emergency Modules Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85  
Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86  
System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87  
Load on Maintenance Bypass (Two Breakers) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88  
Load on Maintenance Bypass (Three Breakers) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89  
SCC Start-Up Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93  
Module Start-Up Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95  
Load Transfer Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97  
SCC Shutdown Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99  
Module Shutdown Procedures Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101  
Current-Versus-Time Curve of Module Overload Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103  
TABLES  
Table 1  
Table 2  
Table 3  
Table 4  
Table 5  
Alarm Messages - Meaning and Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Alarm Messages - Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74  
Series 600T Terminal Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
Torque Specifications (Unless Otherwise Labeled) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115  
Recommended Test Equipment and Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116  
iv  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Save These Instructions.  
This manual contains important instructions that should be followed during installation and maintenance of your  
Series 600T UPS and batteries.  
WARNING  
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO  
AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. REFER TO  
SEPARATE INSTALLATION MANUAL FOR EQUIPMENT HANDLING  
INFORMATION AND INSTALLATION PROCEDURES.  
FOLLOW ALL BATTERY SAFETY PRECAUTIONS IN 4.0 -  
MAINTENANCE WHEN INSTALLING, CHARGING, OR SERVICING  
BATTERIES. IN ADDITION TO THE HAZARD OF ELECTRIC SHOCK,  
GAS PRODUCED BY BATTERIES CAN BE EXPLOSIVE AND SULFURIC  
ACID CAN CAUSE SEVERE BURNS.  
IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT, USE ONLY  
CARBON DIOXIDE FIRE EXTINGUISHERS, OR OTHERS APPROVED  
FOR USE IN ELECTRICAL FIRE FIGHTING.  
EXTREME CAUTION IS REQUIRED WHEN PERFORMING  
MAINTENANCE.  
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS HIGH  
DC AS WELL AS AC VOLTAGES. WITH INPUT POWER OFF AND THE  
BATTERY DISCONNECTED, HIGH VOLTAGE AT FILTER CAPACITORS  
AND POWER CIRCUITS SHOULD BE DISCHARGED WITHIN 30  
SECONDS. HOWEVER, IF A POWER CIRCUIT FAILURE HAS  
OCCURRED, YOU SHOULD ASSUME THAT HIGH VOLTAGE MAY  
STILL EXIST AFTER SHUTDOWN. CHECK WITH A VOLTMETER  
BEFORE MAKING CONTACT.  
AC VOLTAGE WILL REMAIN ON THE SYSTEM BYPASS (SBB) AND UPS  
OUTPUT CIRCUIT BREAKERS, AND THE STATIC BYPASS SWITCH,  
UNLESS ASSOCIATED EXTERNAL CIRCUIT BREAKERS ARE OPENED.  
CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS PRIOR  
TO MAKING CONTACT.  
WHEN THE UPS SYSTEM IS UNDER POWER, BOTH THE OPERATOR  
AND ANY TEST EQUIPMENT MUST BE ISOLATED FROM DIRECT  
CONTACT WITH EARTH GROUND AND THE UPS CHASSIS FRAME BY  
USING RUBBER MATS.  
SOME COMPONENTS WITHIN THE CABINETS ARE NOT CONNECTED  
TO CHASSIS GROUND. ANY CONTACT BETWEEN FLOATING  
CIRCUITS AND THE CHASSIS IS A LETHAL SHOCK HAZARD.  
EXERCISE CAUTION THAT THE TEST INSTRUMENT EXTERIOR DOES  
NOT MAKE CONTACT EITHER PHYSICALLY OR ELECTRICALLY  
WITH EARTH GROUND.  
1
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVERVIEW OF THIS MANUAL  
The manual is organized so that information can be found quickly. Each major topic is separated by sections, and  
the Table of Contents contains major headings within each section. The names of the sections and their contents  
are described below.  
1.0 - Introduction is a summary of the Series 600T UPS System. It describes some of the unique features and  
benefits of the Series 600T, as well as the design principles and standards that Liebert follows in the manufacture  
of each system. Descriptions of the Series 600T system and an overview of its functions are also included.  
2.0 - Theory of Operation is an explanation of the major circuit groups of the Series 600T UPS. This section is  
for individuals who want to know both the basics and the specifics of each major component. The text explains  
how the UPS handles electrical disturbances and interruptions.  
3.0 - Operation is written for facility personnel responsible for the operation of the system. It details the proce-  
dures required to start-up each module and the system, to transfer the load between the available sources, and to  
shut down each module and the system. Both manual and automatic operations are described. Operator controls  
and displays, including the solid state liquid crystal display (LCD) screen, are illustrated and explained for the  
UPS Module and for the System Control Cabinet (SCC).  
4.0 - Maintenance lists routine maintenance checks and helps the user pinpoint and quickly resolve problems if  
they arise.  
5.0 - Specifications and Ratings gives detailed specifications about the Series 600T UPS System. This technical  
information is of use to installing contractors, engineers, and service personnel.  
If you require assistance for any reason, call the toll-free Liebert Global Services number: 1-800-543-2378. For  
LGS to assist you expediently, please have the following information available:  
Part Numbers:  
Serial Numbers:  
kVA Rating:  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
Date Purchased:  
Date Installed:  
Location:  
Input Voltage:  
Output Voltage:  
Battery Reserve Time:  
2
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 INTRODUCTION  
1.1  
System Description  
The role of the parallel-redundant multi-module UPS system is to supply uninterruptible, clean power to the crit-  
ical load. It maintains a full-voltage, low-distortion output, even if the utility source power sags or becomes dis-  
torted.  
If there is an outage of the source power, the UPS maintains power to the load until an alternate source of power  
is activated, or until the original power source is restored. If input AC power is not restored, the UPS maintains  
the load (with the battery plant) long enough that the critical equipment can be shut down in an orderly manner.  
The Series 600T UPS module displays the rate of battery discharge and calculates the amount of battery time  
remaining based on the actual connected load. The time that the battery will maintain the load depends on the  
capacity of the battery backup plant and the size of the load.  
The system control logic automatically manages critical bus operation. System logic is resident in Application  
Specific Integrated Circuits (ASICs) for precise control and improved reliability.  
If the critical load current exceeds the rated load of the Series 600T UPS system, the control logic determines the  
magnitude of the overload and reacts appropriately. Overloads are usually the result of inrush current require-  
ments. The UPS system supports loads that are 150% of the rated load for up to 30 seconds and 125% of the  
rated load for up to ten minutes. If the system is operating in the non-redundant mode (e.g., a UPS module is off  
line), the overload limits are automatically adjusted.  
Figure 1 Multi-Module UPS, 65-80 kVA (left) and 100-500 kVA (right)  
If the load surpasses the overload capacity of the UPS, the load is automatically transferred to bypass without  
interruption. When the load returns to within the UPS rating, it is either automatically or manually returned  
3
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(retransferred) to the UPS. How and when the load is returned to the UPS depends on several factors: how long  
the overload lasted, how many overload conditions occurred before transfer, whether there is an imminent failure  
of any part of the UPS, etc. Refer to 3.4 - Automatic Operations.  
In the unlikely event of a fault within the UPS, the SCC control logic, which continuously monitors all critical  
circuits within the UPS system, transfers the load to bypass without interruption and simultaneously sets off local  
and remote alarms. If a fault is detected in an individual UPS module, that module is automatically disconnected  
from the critical bus and shut down. A Module Off Line status message will appear at the SCC display. The  
module can be manually returned to service when the fault has been corrected.  
If the multi-module UPS system is operating in the redundant mode (at least one extra module is available for the  
connected critical load), the load will remain on the UPS system if one individual module is disconnected from  
the critical bus (off line). If the UPS system is operating in the non-redundant mode, the load will be automati-  
cally transferred to bypass if a module goes off line.  
The Series 600T UPS display system provides precise monitoring of the UPS, fast alarm response, and quick  
troubleshooting. For easy manual operations, menu-driven software provides access to several step-by-step help  
screens. All operator functions are performed using menu-prompted displays and a minimum number of operator  
controls. The System Control Cabinet includes external communication capability with both automatic dial-out  
and dial-in features for early warning and diagnosis of abnormal conditions.  
The system software allows the operator, or Liebert Global Services, to enter application specific information.  
Overload, overvoltage, battery discharge, and shutdown limits can be set by the operator. In effect, the software  
is tailored for each site.  
The UPS system protects critical equipment from source power disturbances and outages, load faults, and UPS  
malfunctions. This triple protection virtually eliminates computer and computing equipment downtime as a  
result of utility source power problems.  
4
Introduction  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 2 Multi-Module 500-750 kVA UPS  
5
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3 System Control Cabinets (SCCs)  
Types of System Control Cabinets (SCCs)  
SCCT -- A stand-alone cabinet containing system control logic for up to six UPS modules, a static bypass  
switch, manually operated disconnects for the static bypass switch, and two motor-operated system circuit  
breakers.  
SCCB -- Similar to the SCCT, except that external sheet metal matches that of the UPS modules.  
SCCP -- Similar to the SCCB, except narrower and designed for two UPS modules.  
SCCI -- System control logic and static bypass switch are integrated into a switchboard cabinet manufac-  
tured by others, which also includes the system circuit breakers.  
SCCC -- An integrated configuration like the SCCI, but with a static switch rated for continuous duty.  
6
Introduction  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.2  
Reliability  
Reliability is the most important design goal for Uninterruptible Power Systems. Liebert Series 600 UPS systems  
have demonstrated reliability by achieving a field-proven critical bus MTBF in excess of one million hours. In  
addition, our Quality Assurance program is certified to the requirements of ISO 9001 standards.  
Liebert Large UPS systems are ETL listed to the requirements of UL 1778. All equipment and components are  
manufactured to applicable UL, NEC, NEMA, ANSI, IEEE, and CSA standards and guidelines.  
Designed for Success  
The keys to reliability in the design of the UPS system are using conservatively rated components, minimizing  
transfers to bypass, making operator controls understandable, and providing easy access for maintenance and  
repair. Liebert UPS systems lead the industry in all these areas.  
For example, the Series 600T can clear substantial overloads through the solid state static bypass switch without  
transferring to the bypass source. By minimizing transfers to bypass, the Series 600T minimizes operation of cir-  
cuit breakers and enhances system reliability.  
As another example, the system control logic has been packaged into Application-Specific Integrated Circuits  
(ASICs) to eliminate the failure-prone discrete logic boards used in other brands of UPS products. Furthermore,  
these ASICs are isolated from heat-generating components to ensure optimal operating temperatures.  
Other Factors to Consider  
Reliability depends on more than just UPS module design. Improper installation can cause any system to fail. To  
prevent this, Customer Engineers from Liebert Global Services thoroughly inspect the installation of all our sys-  
tems to ensure they are installed properly and operating within performance specifications.  
Once a UPS is properly installed, you—the on-site equipment operator—are the most important factor in pre-  
venting critical bus failures or unplanned transfers to bypass. To make your task easier, the Series 600T UPS pro-  
vides easy-to-follow, prompted instructions on the industry’s largest operator display screen.  
If you ever need help, call Liebert Global Services (24 hours a day at 1-800-543-2378). Your attention to proper  
installation, operation, and periodic maintenance will ensure that your mission-critical operations receive the  
best possible protection from electrical disturbances and outages.  
7
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.3  
Safety Precautions  
Read this manual thoroughly, paying special attention to the sections that apply to you, before working with the  
UPS. Also read the battery manufacturer’s manual before working on or near the battery.  
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area  
around the UPS system and Battery should be kept free from puddles of water, excess moisture, or debris.  
Special safety precautions are required for procedures involving handling, installation, and maintenance of the  
UPS system or the battery. Observe precautions in the separate Installation Manual before handling or installing  
the UPS system. Observe precautions in 4.0 - Maintenance, before as well as during performance of all mainte-  
nance procedures. Observe all battery safety precautions in 4.0 - Maintenance before working on or near the  
battery.  
This equipment contains several circuits that are energized with high voltage. Only test equipment desig-  
nated for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC  
and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dan-  
gerously high potentials may exist at the capacitor banks. Observe all battery precautions when near the battery  
for any reason.  
ONLY qualified service personnel should perform maintenance on the UPS system. When performing  
maintenance with any part of the equipment under power, service personnel and test equipment should be stand-  
ing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the  
floor (earth ground).  
Unless all power is removed from the equipment, one person should never work alone. A second person should  
be standing by to assist and summon help in case an accident should occur. This is particularly true when work is  
performed on the battery.  
Three types of messages are used throughout the manual to stress important text. Carefully read the text below  
each Warning, Caution, and Note and use professional skills and prudent care when performing the actions  
described by that text.  
A Warning signals the presence of a possible serious, life-threatening condition. For example:  
WARNING  
LETHAL VOLTAGES MAY BE PRESENT WITHIN THIS UNIT EVEN  
WHEN IT IS APPARENTLY NOT OPERATING. OBSERVE ALL  
CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO SO  
COULD RESULT IN SERIOUS INJURY OR DEATH. DO NOT WORK ON  
OR OPERATE THIS EQUIPMENT UNLESS YOU ARE FULLY QUALIFIED  
TO DO SO!! NEVER WORK ALONE.  
A Caution indicates a condition that could seriously damage equipment and possibly injure personnel. For  
example:  
CAUTION  
Make sure you understand the proper sequence before operating any circuit  
breaker. Operating a Maintenance Bypass circuit breaker out of sequence could  
cut off power to the critical load.  
A Note emphasizes important text. If the note is not followed, equipment could be damaged or may not operate  
properly. For example:  
NOTE  
If the UPS system has a blown fuse, the cause should be determined before you  
replace the fuse. Contact Liebert Global Services.  
8
Introduction  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.4  
Modes of Operation  
Refer to 2.0 - Theory of Operation and 3.0 - Operation for more details.  
1.4.1 Normal (Load on UPS)  
The utility AC source provides power to the rectifier/charger in each UPS module. Each rectifier/charger con-  
verts the utility AC power to DC and supplies DC power to the UPS module inverter while simultaneously float  
charging the battery plant. Each UPS module inverter converts DC to AC and furnishes AC power to the critical  
bus. The System Control Cabinet (SCC) is the tie point for the paralleled modules and monitors and controls the  
critical bus performance.  
1.4.2 Input Power Failure  
If the utility source power fails or is outside the acceptable range, the battery plant becomes the primary supplier  
of DC power to the inverter.  
1.4.3 Recharge  
After the utility source power is restored, or an alternate power source becomes available, each rectifier/charger  
slowly walks-in to once again power the inverters and recharge the battery plant.  
1.4.4 Overload  
Overloads in critical systems may be caused by inrush currents during connected equipment start-up or by faults  
in the critical load. The Liebert Series 600T UPS system can maintain full output voltage regulation while sus-  
taining the following overloads:  
• Up to 150% for 30 seconds  
• Up to 125% for 10 minutes  
• Up to 104% for an indefinite period of time  
Also, for clearing momentary faults above 155% of rated SCC current, the static switch turns on for 40 millisec-  
onds to supply power from the bypass source. Up to 1000% of the rated current can be supplied for less than one  
cycle, while up to 500% of rated load can be sustained for the full 40 milliseconds of pulsed-parallel operation.  
The critical load remains on the UPS modules for the above conditions. If the UPS system overload capacity is  
exceeded, an automatic transfer to bypass is initiated, which closes the system bypass circuit breaker (SBB) and  
opens the UPS output circuit breaker.  
Whenever you have an overload condition, you should determine the cause of the overload.  
1.4.5 Redundant  
If the multi-module UPS system includes one more module than the number required to supply the critical load,  
the UPS system can operate in the redundant mode. This means that the load will remain on the UPS system if  
one of the modules is disconnected because of an overload, an internal fault, or for maintenance. If the additional  
module is not included in the system design, or if the additional module is disconnected from the critical bus, the  
UPS system operates in the non-redundant mode.  
1.4.6 Bypass (Internal)  
The SCC control logic initiates an automatic transfer to the bypass source if the overload-current-versus-time  
curve is exceeded or if specified UPS system faults occur. You can also manually transfer the load to the bypass  
(without interruption) if you must take the UPS module out of service for maintenance.  
The SCC internal maintenance bypass will allow most key components and operating modes to be checked with-  
out disturbing the critical bus. However, certain key power-carrying components, such as the output and bypass  
circuit breakers, will require complete system shutdown or isolation through an external maintenance bypass  
cabinet for 100% service.  
1.4.7 Maintenance Bypass  
The installation of a Maintenance Bypass Cabinet, Panelboard or Switchboard is recommended to allow you to  
totally isolate the UPS from all power sources. Use of the Maintenance Bypass is described in 3.0 - Operation.  
1.4.8 Off-Battery  
The battery plant can be disconnected from the rectifier/charger by using an external Module Battery Disconnect  
(MBD circuit breaker). The UPS module continues to function normally, though it does not have power outage  
back-up capability until the battery plant is reconnected.  
9
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.5  
Operator Controls  
The Liebert Series 600T UPS System Control Cabinet (SCC) and each individual module are equipped with a  
microprocessor-based Operator Display Screen and Control Panel designed for convenient and reliable opera-  
tion.  
The front panel location of the monitoring and control system enables the user to quickly identify the current sta-  
tus of the UPS and to perform most of the manual operations. The operator display screen is driven by an easy-  
to-follow menu-prompted software program that controls and monitors the UPS system.  
Figure 4 SCC Controls and Display Screen with Example of the Monitor/Mimic Screen  
The operator controls and Monitor/Mimic screen for the System Control Cabinet (SCC) are shown in Figure 4.  
The controls and display screen for each UPS module are shown in Figure 5. Each cabinet (SCC or module) has  
the displays and controls required to monitor and perform its functions.  
Figure 4 shows a three-module system designed for redundant operation. A multi-module UPS system may  
include up to six (6) modules for each SCC.  
Detailed instructions on how to interpret the displays and use the controls are in 3.0 - Operation.  
10  
Introduction  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 5 Module Controls and Display Screen with Example of the Monitor/Mimic Screen  
11  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.6  
Options  
A number of standard pre-designed options are available from Liebert for your UPS system. Described below are  
the most frequently provided options. Note that the battery items (1-3) are required to complete the UPS system.  
The remaining options provide improved system performance or convenience.  
1. Battery  
The batteries provide power in the event of a power outage. The Liebert UPS can use a variety of battery  
types, provided the battery plant is designed for the UPS DC voltage range and the load requirements of  
your application.  
2. Battery Racks or Cabinets  
The battery racks are specifically designed for stationary service batteries. They are painted with electrolyte-  
resistant paint for corrosion resistance. Battery cabinets are available for 150 through 600 kVA modules.  
3. Module Battery Disconnect  
The UPS system utilizes a separate Module Battery Disconnect for remotely located batteries. A sensing cir-  
cuit in the UPS module, set at the battery low voltage limit, trips the Module Battery Disconnect to safe-  
guard the battery from excessive discharge. The Module Battery Disconnect has an undervoltage release  
mechanism designed to ensure that during any shutdown or failure mode all battery potential is removed  
from the UPS system  
4. Input Distortion Filter  
This filter reduces rectifier input current reflected harmonic distortion to less than 7% THD, and less than  
4% THD for modules with the optional 12-pulse rectifier. The filter is factory installed within the UPS. This  
filter also improves the input power factor to better than 0.92 lagging.  
5. 12-Pulse Rectifier  
Certain models may be ordered with the optional 12-pulse rectifier section. This provides input isolation and  
reduces reflected input current THD to less than 9%, or less than 4% with optional input filter.  
6. Isolation Transformers  
An optional rectifier input isolation transformer is available in a matching transformer cabinet. A bypass iso-  
lation transformer is also available.  
7. Three Breaker Maintenance Bypass  
This switchboard provides make-before-break maintenance bypass. It includes: UPS Bypass Input Breaker  
(BIB), Maintenance Bypass Breaker (MBB), and Maintenance Isolation Breaker (MIB).  
8. Two Breaker Maintenance Bypass  
This switchboard provides make-before-break maintenance bypass. It includes: Maintenance Bypass  
Breaker (MBB) and Maintenance Isolation Breaker (MIB).  
9. Load Bus Synchronization (LBS)  
The Load Bus Sync (LBS) option keeps two independent UPS systems (and therefore their critical load  
buses) in sync, even when the modules are operating on batteries or asynchronous AC sources. This means  
that critical loads connected to both load buses through a Static Bus Transfer Switch can be switched seam-  
lessly between the two.  
10. SiteScan Central Monitoring System  
Liebert manufactures a central monitoring system that automatically displays key UPS measurements and  
alarms, as well as data from a variety of sensors. This monitoring system signals alarms so corrective action  
can be taken. Events and data can be printed in hard copy. Data can be logged for analysis.  
11. Remote Monitor Panel  
The UPS system may also be provided with an optional Remote Monitor Panel. This Panel provides eight  
LED indicators and may be placed at a convenient location near the critical load. A functional description of  
the Remote Monitor Panel is provided in 3.0 - Operation of this manual.  
12. Customer Alarm Interface  
This optional interface board allows the input and display of 8 alarms from customer-supplied contacts, each  
with a customer-selected name of up to 16 characters. The following attributes can be user programmed for  
each alarm: latching, summary, freeze history, sound horn, auto-dial, and time delay (0 to 999.9 seconds).  
12  
Introduction  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.0 THEORY OF OPERATION  
2.1  
General Component Descriptions  
The UPS system includes all of the equipment necessary to continuously provide computer-grade AC power to a  
critical load, even when there is an interruption of the utility line power. It consists of a System Control Cabinet  
(SCC), UPS modules, and a back-up battery plant. Refer to Figure 6 and Figure 7. Except where otherwise  
noted, the configuration is presumed to be parallel-redundant (with at least one more UPS module than required  
to support the rated load).  
System Control Cabinet  
The System Control Cabinet (SCC) includes system controls, static bypass switch, load transfer control, protec-  
tive devices, and other accessories. The system controls simultaneously monitor two or more parallel UPS mod-  
ules sharing a critical load for increased capacity and/or redundancy. The two (2) motor-operated system circuit  
breakers (system bypass breaker—SBB and UPS output breaker) may be contained within the SCC, depending  
on the configuration designed for your installation.  
System Controls: The system control logic automatically manages critical bus operation and monitors perfor-  
mance of the UPS modules. Microprocessor technology and dedicated firmware provide advanced logic control  
and a comprehensive display of information. The system control logic synchronizes the output of the UPS sys-  
tem to the bypass source. The SCC includes ports for communicating with external devices. Liebert Multi-Mod-  
ule Units do not require an SCC for load sharing. Automatic, parallel module load sharing is a function built into  
the modules themselves; however interconnection through the SCC enables the modules to share data for more  
precise control. Modules do not require master clocks or controls in order to load share or free-run at 60.0 Hz.  
Static Bypass Switch: The static (solid-state) bypass switch immediately transfers the load from the inverter to  
the bypass AC power source in the event of a severe overload on the system or a failure within the UPS. This  
transfer takes place without any interruption of the power supplied to the load. The system includes redundant  
circuits to detect and isolate shorted SCRs in the static switch.  
Fuses are installed in series with the static bypass circuit to ensure reliable overload protection in the unlikely  
event of a catastrophic output condition (e.g., a dropped wrench) electrically close to the output of your UPS sys-  
tem. The static switch SCRs themselves are rated to easily handle the fuse-blowing current.  
Bypass Circuit: The bypass circuit consists of electrically operated circuit breakers and associated synchroniz-  
ing and control circuitry to transfer the load to/from the bypass source.  
Theory
13  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 6 UPS Module Block Diagram  
MULTI-MODULE UPS SYSTEM  
Control  
Wiring  
To SCC  
CONTROL POWER  
Controls  
Utility  
Input  
Output  
Power  
Rectifier/  
Charger  
Inverter  
MBD  
Output  
CB  
Power  
Input  
CB  
To SCC  
Battery  
CB - Circuit Breaker  
MBD - Module Battery Disconnect  
SCC - System Control Cabinet  
UPS Module  
The UPS module consists of module controls, a rectifier/charger, an inverter, protective devices, and other acces-  
sories.  
Module Controls: The module control logic monitors performance of the UPS module. The UPS module status  
is displayed locally and is also sent to the System Control Cabinet.  
Rectifier/Charger: The rectifier/charger converts utility power from AC to DC to charge the battery and pro-  
vide the DC input to the inverter. Its design limits reflected harmonic current distortion to source power and pro-  
vides low-ripple DC power for charging batteries. Multiple rectifier/chargers can share a common battery plant,  
if that configuration is preferred for your application.  
Inverter: The inverter converts DC power into the precise AC power required to supply a sensitive critical load.  
The inverter converts DC power into a pulse-width-modulated (PWM)/six-step waveform that is easily filtered  
into a clean sine wave output. The PWM/stepwave also minimizes the harmonic voltage distortion caused by  
typical switching power supplies and other non-linear load components used in computers and related electron-  
ics.  
Battery Plant  
The battery is used as the alternate source of power to supply DC power to the inverter if the AC supply voltage  
is outside the acceptable range. The battery supplies power to the inverter until the utility power is restored or  
until an alternate power source is available. If AC source power is not restored or an alternate power source is not  
available, the battery can be sized to provide power long enough for an orderly shutdown of the load.  
14  
Theory of Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2  
Detailed Component Descriptions  
2.2.1 Controls  
Hardware  
The Series 600T UPS Operator Interface Display System is designed to provide all of the information that is  
required for the operation of each UPS cabinet (the System Control Cabinet and each module). The following is  
a list of the hardware features:  
1. The control logic performs automatic operations with minimal operator interface. The limited number of  
manual controls are easy-to-use.  
2. Each Series 600T UPS cabinet is equipped with an easy-to-read 640 x 200 pixel liquid crystal display (LCD)  
screen. It presents information in a way that is easy to understand at an eye-level front panel location.  
3. The display is controlled by a dedicated microprocessor with a non-volatile (EPROM) program and a  
battery-backed event memory.  
4. The Series 600T System Control Cabinet (SCC) has communication ports (terminal board connections) for:  
a. Transmission of present status information to remote terminals via resident auto-dial communications  
program and an external modem. This port also responds to inquiries of the UPS system status and  
history from the remote terminal.  
b. Reporting UPS system status and history information in response to inquiries from a local terminal (no  
modem required).  
c. Reporting to a local monitor the information requested from the local terminal.  
d. Reporting information to a Liebert SiteScan central monitoring system.  
e. Relaying selected alarm messages to a Liebert Remote Monitor Panel and to a separate terminal board  
for customer use.  
f. Relaying performance and status information to your network monitoring system via SNMP interface.  
NOTE  
All external communication devices are optional equipment.  
Firmware  
The Operator Interface Display System software enables the operator to monitor the UPS system status, to con-  
trol the power flow through the UPS, to monitor all of the meter readings, to execute the start-up, shutdown, and  
the load transfer procedures, to access the event history files, and to make adjustments to the programmable  
parameters. The following is a list of the firmware features:  
1. The menu-driven software prompts the operator for input.  
2. Step-by-step instructions assist the operator during start-up, shutdown, and load transfer procedures. This  
helps to eliminate operator errors.  
3. Graphics-based mimic diagrams illustrate circuit breaker status and the power flow through the UPS system.  
4. The Present Status screen reports information about the system’s present status. The History Status screen  
chronicles the events leading up to and immediately after a fault. The Event History screen lists all of the  
alarm messages that have been logged over a period of time.  
5. The Battery Cycle Monitor records information on up to 132 battery discharge events. Information includes  
date, time, length of discharge, highest current demand, lowest battery voltage, and cumulative battery amp  
hours discharged.  
Refer to 3.0 - Operation for a description of the controls and indicators located on the Operator Control Panel.  
2.2.2 Rectifier/Charger  
The UPS module rectifier/charger consists of an input circuit breaker, optional input isolation transformer, AC  
current limiting circuit, battery equalize charge circuit, DC filter, battery charge current limiting circuit, and  
bridge rectifiers.  
Operation  
The rectifier/charger converts the AC input power to DC power. This conversion is accomplished by 3-phase  
bridge rectifiers using SCRs. All phases are individually fused. Reflected input current THD is less than 7% at  
Theory
15  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
full load with optional input filter. For modules 500 kVA and larger, the optional 12-pulse rectifier reduces  
reflected THD to less than 4% with optional filter, or 9% without.  
The filtered output of the rectifier/charger provides regulated DC power to drive the inverter and charge the bat-  
tery.  
Input Circuit Breaker  
The input circuit breaker (CB1) is sized to allow enough current to recharge the battery and supply a full rated  
load at the same time. The circuit breaker contains a thermal magnetic trip mechanism and an undervoltage  
release that interrupts power, preventing damage to the system, if there is an internal AC over-current condition  
or a short circuit. The circuit breaker also opens during certain alarmed faults. This circuit breaker must be closed  
manually.  
Isolation Transformer  
The optional input isolation transformer has a dry type core, and copper windings with class H insulation. The  
transformer on modules with standard 6-pulse rectifier has wye primary and delta secondary windings. For mod-  
els with the optional 12-pulse rectifier, the transformer has a delta primary, with delta and wye secondary wind-  
ings. The isolation transformer provides the initial step of critical bus isolation. This reduces the AC shock  
hazard at the battery and at other DC components, and prevents a DC fault from disrupting upstream AC cir-  
cuitry.  
The transformer has a nominal tap and one tap 6% below the rated nominal input voltage (normally used for 460  
VAC input).  
Input Current Limit  
AC input current-sensing transformers (CTs) are used to measure current levels. Control circuitry connected to  
the CTs restricts the AC current to less than 125% of the full input current rating by reducing the battery charging  
voltage. This current limit is adjustable from 100 to 125% and is factory set at 115%. A second (optional) level  
of input current limit can be initiated by an external contact closure (field supplied for use with back-up genera-  
tor), and is adjustable from 85 to 100% (factory set at 100%).  
During a start-up procedure, the current slowly ramps up (walks-in) from 20% of the rated input current to 100%  
over a 15 to 21 second period. The maximum rate of change of the AC input current is 15% per second. The  
input current walk-in reduces the start-up surge distortion effects on all other equipment connected to the same  
source and prolongs the service life of internal components.  
Input Current Inrush  
The maximum sub-cycle of inrush current due to the optional input isolation transformer is less than 500-800%  
of the rated input current for the first 1/2 cycle. Without the optional transformer, inrush current is typically less  
than 2-3 times normal.  
Input Power Factor  
The rated input power factor is no less than 0.85 lagging at the nominal input voltage and the full rated UPS load.  
The optional input filter will improve the power factor to better than 0.92 lagging at full load. Refer to published  
specifications for your UPS model.  
2.2.3 Battery Charging Circuit  
The UPS module charging circuit is capable of recharging the battery plant to 95% of full capacity within 10  
times the discharge time. Recharging the last 5% takes longer because of characteristics inherent in the battery.  
DC ripple voltage is limited to less than 0.5% RMS to preserve battery life during long-term float charging while  
the UPS system is operating on utility source power.  
Multiple UPS module rectifier/chargers can share a common battery plant, if that configuration is preferred for  
your application.  
Operation After Discharge  
When commercial power is interrupted, the battery continues to supply DC power to the inverter without inter-  
ruption to the critical load. If the AC source power is restored before the battery has fully discharged, the rectifier  
automatically restarts and resumes carrying the inverter and battery recharge load requirements.  
16  
Theory of Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation After End-of-Discharge  
The battery time screen displayed on the control panel enables you to estimate when battery shutdown will occur.  
You will have enough time to energize an alternate AC power source or to initiate an orderly shutdown of the  
critical load. If the battery plant discharges to the shutdown point during an outage, the UPS automatically dis-  
connects the load, the AC input, and the battery. After AC input power is restored, the rectifier can be manually  
restarted by the user.  
Battery Disconnect  
The external module battery disconnect (MBD) circuit breaker is used to isolate the UPS module from the bat-  
tery during maintenance and to automatically disconnect the battery from the inverter at the end of battery dis-  
charge. The MBD circuit breaker can be opened or tripped automatically, from the control panel, or manually. It  
must be closed manually.  
Battery Charge Current Limiting  
The battery recharge current, after a battery discharge, is limited to between 1 and 25% (adjustable) of the full  
load discharge current. An additional (optional) charge-limiting circuit can be activated by external dry contact  
closure (field supplied) for use when operating on a back-up generator. These two levels of control regulate the  
amount of current that flows from the power source to the battery while the battery is recharging.  
The battery charge current limit is factory set at 10% for normal operation and at 1% for alternate power source  
recharge operation.  
Battery Equalize Charge Circuit  
The battery equalize charge feature can be manually initiated or it can be programmed to operate automatically.  
Either can be selected from the battery equalize screen displayed on the control panel.  
The battery equalizing charge circuit increases the rectifier/charger output voltage to charge the battery any time  
there is a power outage of 30 seconds or longer. The equalizing voltage is slightly higher than the float voltage.  
This decreases the time required to recharge the battery.  
NOTE  
Do not use equalize charging with valve-regulated lead-acid batteries  
Consult the battery manufacturer's manual for specific information about equalize  
charging.  
Theory
17  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2.4 Inverter  
The inverter is a solid state device that converts the DC output of the rectifier/charger or the battery to AC power.  
Operation  
The inverter converts DC power—from either the battery or the rectifier/charger—into three pulse-width-modu-  
lated/six-step waveforms. These waveforms are filtered into low-distortion sine wave power. The inverter is con-  
trolled by an Application-Specific Integrated Circuit (ASIC). This integrated circuit controls the precise  
synchronization, amplitude, and frequency of the output voltage.  
In addition to the inverter efficiently supplying a regulated AC output from a DC source, the output isolation  
transformer acts as a second stage of isolation between the critical load bus and the commercial source power.  
The inverter is configured to handle most critical load inrush surges. It maintains output voltage Total Harmonic  
Distortion (THD) within specifications even when handling non-linear computer loads. Refer to non-linear load  
characteristics.  
Output Regulation and Overload Performance  
The inverter is capable of sustaining full output voltage ±2% of the nominal voltage) for up to 150% overload at  
the output for as long as 30 seconds without reducing the output voltage. It can also handle at least 125% of the  
rated current for up to 10 minutes and 104% of the rated current continuously. The System Control Cabinet  
(SCC) will transfer the critical load to the bypass source if the overload exceeds the system capacity or the capac-  
ity of the modules on-line. The multi-module overload capacity (in terms of percent of rated full load current of  
modules on-line) is 140% for 20 seconds, 108% for 10 minutes, and 104% continuously.  
Note that in normal operation the SCC will transfer the load to bypass before a UPS module exceeds its overload  
capacity. If a module overload condition is sustained (beyond inverter capacity) the UPS module is automatically  
taken off-line (disconnected from the critical bus) and is shut down. If the UPS system is operating in the redun-  
dant mode, the load may remain on the UPS system. Refer to 3.4 - Automatic Operations.  
Non-Linear Load Characteristics  
Computers and computer equipment with switching power supplies generate non-linear currents rich in fifth and  
seventh harmonics.  
The inverter pulse-width-modulated/six-step waveform, coupled with the output filter, provides a natural path  
for reducing the fifth and seventh harmonic currents produced by the load. The inverter/filter limits the output  
voltage THD to less than 5% with up to 100% typical electronic data processing (EDP) loads. EDP equipment  
characteristically includes both non-linear and linear load components.  
Unbalanced Load Characteristics  
Unbalanced loads are actively regulated. The phase-to-phase voltage balance is maintained to within 2%, even  
with a 50% load imbalance.  
The three-phase, root mean square (RMS—approximately 70% of the peak) average voltage is also regulated  
through a separate control circuit (phase-to-phase sensing).  
18  
Theory of Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2.5 Static Bypass  
A static bypass is an integral part of the UPS System Control Cabinet (SCC). Refer to Figure 7. The static  
bypass consists of solid-state switching devices working in conjunction with the motor-operated System Bypass  
Breaker (SBB). An automatic transfer control circuit senses the status of the operator controls, UPS logic signals  
and alarm messages, and critical bus operating conditions. If the UPS modules can no longer supply the critical  
load, the static bypass switch (in conjunction with the SBB and UPS Output Breaker) automatically transfers the  
critical load to the bypass source without interruption.  
Figure 7 System Control Cabinet (SCC) Block Diagram  
Gate  
Driver  
Static  
Bypass  
Switch  
Static Switch  
Disconnects  
Static Bypass Breaker  
Bypass Line  
Sync &  
Transfer  
Control  
Power  
Supply  
Transfer  
Control  
UPS  
System  
Modules  
System  
Monitor  
Voltage  
Adjust  
Alarms  
To Critical  
Load  
UPS Output  
Fuse Protection  
The static bypass switch path uses two back-to-back SCRs per phase. Each phase is individually protected by a  
fuse sized to clear only in the event of a catastrophic fault. This is a more reliable method than depending on  
external protection devices. The fuses are in the circuit to protect the critical bus distribution equipment against  
catastrophic faults. The static switch SCRs are oversized to easily handle any current surges that may blow the  
fuses.  
Shorted SCR Monitoring  
The static bypass system has redundant shorted SCR sensing circuits and disconnects. This will prevent UPS out-  
put power backfeed to the distribution system even if two component failures exist simultaneously. If a shorted  
SCR is detected, the static bypass switch is isolated and annunciated at the SCC control panel, and the critical  
load remains on UPS output power.  
Static Switch Isolation  
The motor-operated system bypass circuit breaker (SBB), wired in parallel with the static switch, automatically  
closes in approximately 200 milliseconds after the load is transferred to the bypass power source, removing the  
static switch from the power flow.  
Theory
19  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Also, if required for maintenance, the static switch can be isolated from the bypass line by opening (to the OFF  
position) the Static Switch Disconnects.  
Pulsed Parallel Operation  
When an overload condition such as magnetic inrush current or a branch load circuit fault exceeds the overload  
capacity of the connected modules, the static bypass switch pulses on for 40 milliseconds. This allows up to  
1000% of the rated full load current from the bypass line to clear the overload without closing the bypass circuit  
breaker. The bypass source is briefly in parallel with the UPS system, permitting the bypass source to carry the  
initial overload current. If the overload clears before 40 milliseconds, a load transfer to bypass is not made. If the  
overload condition continues, the automatic transfer is made (maintaining the load voltage within the specified  
limits).  
This pulsed static switch operation reduces nuisance operation of motor-operated circuit breakers for such short-  
term conditions.  
Load Transfers  
Transfers to (transfer) or from (retransfer) the bypass may be performed automatically or manually in a make-  
before-break sequence. This is accomplished through the overlapping operation of the UPS output and the sys-  
tem bypass power switching devices.  
Manual load transfers and retransfers are initiated by the operator from the System Control Cabinet (SCC).  
In a manual operation, or an automatic retransfer, the two motorized circuit breakers—UPS output and system  
bypass—are both closed simultaneously for a short period of time (overlap).  
Automatic transfers are initiated by the SCC system control logic when an overload is beyond the specified capa-  
bilities of the UPS system or when a fault occurs within a non-redundant UPS module. An automatic retransfer is  
initiated if this function is enabled and if system conditions for a retransfer are present.  
In an automatic transfer, the circuit breakers do not overlap, but during the short time gap bypass power is sup-  
plied to the critical load through the solid state static switch.  
20  
Theory of Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transfer and Retransfer Conditions  
1. Automatic Transfers to Bypass  
Critical bus conditions that will initiate an automatic transfer of the critical load from the UPS system to the  
bypass source are:  
a. System Overload: overcurrent condition in excess of the overload rating of the System Control Cabinet  
(SCC).  
b. Output Overload: overcurrent condition in excess of the current-versus-time overload capacity of UPS  
modules ON LINE.  
c. Over/Under Voltage (OV/UV): critical bus voltage is outside the allowable tolerance.  
d. Non-redundant UPS Module Inoperative: an essential UPS module is taken OFF LINE for one of the  
reasons below.  
1. Battery discharged to the shutdown voltage.  
2. Inverter overload capacity exceeded.  
3. Inverter or rectifier fault condition (power, logic, or over-temperature) present or imminent.  
4. Failure of UPS module logic or logic power.  
e. SCC Logic:  
1. Emergency Module Off (EMO) circuit activated.  
2. Failure of UPS system logic or logic power.  
2. Manual Transfers  
Manual transfers may be initiated at any time provided no transfer inhibition conditions are present.  
3. Transfer Inhibited  
A manual transfer to the bypass source shall be inhibited if any of the following conditions exist:  
a. Bypass frequency deviates ±0.5 Hz from the nominal.  
b. UPS system to bypass voltage difference ( V) exceeds a predetermined percentage (normally 5%).  
c. Static switch disconnects (manual switches) open.  
d. OK to Transfer signal from the control logic is not present.  
NOTE  
A load transfer to the bypass line will be completed whenever an automatic transfer  
to bypass is initiated If the Static Switch Unable alarm message is present for any  
reason (including a ±20° phase lock synchronization error), the automatic transfer  
will be interrupted for 40 to 120 milliseconds. Because of the reliability of the UPS  
components, an interrupted load transfer is a very unlikely occurrence.  
4. Automatic Retransfers to UPS  
Critical bus conditions that must be present to initiate an automatic retransfer (Auto-Rexfer) of the critical  
load from the bypass source to the UPS system are:  
a. The number of Auto-Rexfer Attempts selected must be greater than zero (0). If zero (0) is selected, no  
automatic retransfer will occur.  
b. Critical load was initially transferred to the bypass source due to a system overload only.  
c. Overload has since dropped below 100% of the rated SCC current.  
d. Enough UPS modules are ON LINE to supply the critical load.  
e. OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes of the  
overload transfer. (A manually initiated retransfer from bypass is required for overloads lasting 5  
minutes or more.)  
f. Cyclic-type system overloads, which occur up to five (select range is 0 to 5) times in 60 minutes, are  
automatically returned to the UPS system for each event including the Nth overload. A manually  
initiated retransfer from bypass is required for the N+1 overload.  
Theory
21  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Manual Retransfers  
Manual retransfers may be initiated at any time provided no retransfer inhibition conditions are present.  
6. Retransfer Inhibited  
A retransfer from the bypass source to the UPS system shall be inhibited if any of the following conditions  
exist:  
a. Manual (and Automatic) Retransfer Inhibitions:  
1. Bypass frequency exceeds ±0.5 Hz of the nominal.  
2. UPS system-to-bypass voltage difference ( V) exceeds a predetermined percentage (normally  
5%).  
3. System circuit breaker (UPS output or SBB) is inoperative.  
4. OK to Transfer signal from the control logic is not present.  
5. Not enough UPS modules are ON LINE to supply the connected critical load.  
b. Automatic Retransfer Inhibitions (in addition to those above):  
1. The load transfer to bypass was not caused by a system overload.  
2. Excessive cyclical overloads within a one-hour period.  
3. Retransfer conditions are not satisfied within 5 minutes of the initial transfer.  
2.2.6 Redundant Mode  
The typical multi-module UPS system is configured with a back-up (redundant) UPS module, connected in par-  
allel to share the critical load with the other module(s). This parallel redundant system includes one more module  
than is required to supply the full critical load.  
A parallel redundant system will always be in the Redundant Mode if all modules are ON LINE. In addition, if  
the critical load is reduced so that not all ON LINE modules are required, the UPS system can also operate in the  
Redundant Mode with one or more modules OFF LINE. The critical load will remain on the UPS system—even  
if one or more of the modules is taken OFF LINE for maintenance or because of an internal fault—as long as the  
remaining ON LINE modules can carry the full connected system load.  
The system control logic monitors the connected critical load and the number of UPS modules ON LINE. If the  
UPS system is operating in the Redundant Mode, the REDUNDANT status message will be displayed at the  
System Control Cabinet (SCC). If the UPS system is operating in the Non-Redundant Mode (redundant module  
is OFF LINE or was not included in the system configuration), the NON-REDUNDANT status message is dis-  
played at the SCC. In the Non-Redundant Mode, the critical load will be transferred to bypass if any UPS module  
goes OFF LINE and the remaining ON LINE module(s) cannot carry the connected load without being over-  
loaded.  
The system control logic, located in the SCC, automatically adjusts the allowable overload limits based on the  
connected load and the number of modules ON LINE.  
22  
Theory of Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0 OPERATION  
3.1 Display Screen and Operator Controls  
Each Liebert Series 600T UPS cabinet is equipped with a microprocessor-based Operator Control Panel and Dis-  
play Screen and System Control Panel designed for convenient and reliable operation. The System Control Cab-  
inet (SCC) performs different functions than the UPS modules. Each cabinet has the controls and displays  
required to operate and monitor its functions. The locations of operator controls are shown in Figure 8 through  
Figure 11.  
The front location of the control panel enables the user to quickly identify the current status of the UPS system  
and to perform most of the manual operations. The operator display screen is driven by an easy-to-follow menu-  
prompted software program.  
Features  
The Series 600T interface display system enables the operator to easily perform the following:  
• Obtain a quick indication of operational status:  
• Is the critical bus OK?  
• Is the UPS system OK?  
• Which UPS modules are available?  
• Is the battery available?  
• Is the bypass line available?  
• Monitor the power flow through the UPS system and monitor all meter readings:  
• Is the critical load being supplied power from the UPS system or bypass?  
• Are input, battery, and output voltage, frequency, and current readings at nominal levels?  
• How much battery time is still available during an outage?  
• Is the battery recharging after discharge?  
• Execute operational procedures:  
• Perform critical bus transfer/retransfer between the UPS system and the bypass line.  
• Start-up and shut down the UPS system and each module.  
• Shutdown the system and all modules instantly in the event of an emergency.  
• Access status reports and history files:  
• Obtain a complete listing of the present status of the UPS system and all modules (input, output, and  
battery voltage, frequency, and current readings, and any alarms that may be present).  
• Review a complete history report of all events leading up to and immediately after a fault condition.  
• Examine an archive listing of all alarm conditions that have occurred over a period of time.  
• Make adjustments to programmable parameters (access limited by Security Access function):  
• Set the date and the time functions.  
• Change the auto-dial phone number and the modem options.  
• Select the number of auto-retransfer attempts.  
• Make adjustment to the UPS output voltage before performing a manual load transfer.  
23  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 8 Operator Controls, 65 to 80 kVA (left) and 100 to 500 kVA (right)  
2
2
5
5
Item  
Description  
Function  
1
Input Circuit Breaker  
(behind door of 65-80  
kVA) (CB1)  
This manually operated circuit breaker provides power to the UPS module rectifier.  
In 625-750 kVA modules and some 500 kVA modules, this breaker is located in the  
transformer cabinet.  
2
Module Output Circuit  
Breaker (behind door of  
65-80 kVA) (CB2)  
This manually operated circuit breaker connects the UPS module inverter output to  
the UPS System Control Cabinet.  
3
4
Operator Control Panel  
Refer to Figure 10 for controls available on this panel.  
Control Disconnect  
(behind inner door)  
These two fuses provide power to the controls. They are normally closed (ON).  
Turn Control Power OFF (by opening the two fuse holders) only for maintenance  
procedures.  
5
Interlock Button  
(on rear of Control Panel)  
Press this button to make authorized changes to any parameter protected by the  
Security Access function. This includes time, date, auto-dial phone numbers, etc.  
24  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 9 System Control Cabinet Operator Controls (SCCB Pictured)  
Item  
Description  
Function  
1
UPS Output Circuit  
Breaker  
This motorized circuit breaker connects the critical load to the UPS system output.  
2
System Bypass Circuit  
Breaker  
This motorized circuit breaker connects the critical load to the bypass line.  
3
4
Operator Control Panel  
Refer to Figure 10 for controls available on this panel.  
Interlock Button  
(on rear of Control Panel)  
Refer to Figure 11.  
5
6
7
Close Bypass Switch  
(behind door)  
Refer to Figure 11.  
Bypass Reset Switch  
(behind door)  
Refer to Figure 11.  
Static Switch Disconnects  
(behind door)  
These manually operated switches disconnect the static switch from the bypass  
line and from the critical load. They are normally ON (closed). Turn them OFF  
(open) only to isolate (disconnect) the static switch for maintenance procedures.  
8
9
Reset Switches (SW1) for  
Static Switch Disconnects  
(behind door)  
Press these two switches before closing Static Switch Disconnects when  
recovering from a shutdown that includes loss of Control Power. Green LED on  
means Control Power is available. Red LED on means Reset Switch needs to be  
pushed.  
Control Power Disconnect  
(behind door)  
Normally ON. Turn OFF Control Power only when required for maintenance  
procedures.  
25  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 10 Series 600T UPS and SCC Operator Control Panels  
Item Description (Location)  
Function  
1
Display Screen  
(SCC and modules)  
This screen displays all vital UPS information in one convenient location. All of the UPS  
monitoring functions and conditions are indicated here.  
2
Up  
This touch-sensitive pad (button) is used to move the cursor up through various  
selections present on the display screen. Note that all pads on this control panel have  
touch-sensitive switches behind them.  
(SCC and modules)  
3
4
Down  
Similar to the Up pad, this pad is used to move the cursor down through the various  
selections present on the display screen.  
(SCC and modules)  
Select  
(SCC and modules)  
After choosing the desired item (with highlighted cursor) from the display screen with  
the Up and Down pads, pushing this pad tells the microprocessor to go to the  
highlighted selection.  
5
Alarm Reset  
(SCC and modules)  
This pad is used to clear all of the alarm conditions that are no longer present.  
However, all active alarms remain in memory and on the applicable screens until they  
are corrected. This pad also resets the History Status Report memory buffer when held  
until the screen clears.  
6
7
8
Voltage Adjust  
(SCC only)  
This push-to-turn knob permits adjustment of the UPS output voltage to meet load  
requirements or to match the bypass voltage before transferring the load to or from  
bypass.  
UPS  
(SCC only)  
This pad activates the circuits that connect the UPS to the critical load (a retransfer).  
When this pad is pushed (along with Control Enable), the UPS output circuit breaker  
closes and the bypass circuit breaker opens.  
Bypass  
(SCC only)  
This pad activates the circuits that connect the bypass line to the critical load (a  
transfer). When this button is pushed (along with Control Enable), the bypass circuit  
breaker closes and the UPS output circuit breaker opens.  
9
Control Enable  
(SCC and modules)  
This pad must be pressed simultaneously with the UPS, Bypass, Battery Trip, or Output  
Trip pads to activate them.  
10  
Horn Off  
(SCC only)  
This pad is used to silence the alarm horn after it is activated. When this switch is  
pressed, the alarm horn is silenced but the active and latched alarm messages remain  
on the screen. The alarm messages still displayed stop flashing to indicate they have  
been acknowledged.  
11  
12  
Alarm Horn and  
This electronic horn sounds to alert nearby personnel whenever a new alarm occurs. A  
red LED (light emitting diode) is located in the middle of the alarm horn.  
Red LED (SCC only)  
Emergency Module  
Off (SCC only)  
During an emergency, pressing this guarded switch will transfer the load to bypass and  
then shut down the UPS modules. The load will remain on bypass power. (Refer to  
3.3.3 - Shutdown Procedures.)  
13  
14  
Battery Trip  
(modules only)  
This pad can be used (along with Control Enable) to trip the module battery disconnect  
(MBD) circuit breaker open (disconnecting the battery from the UPS module).  
Output Trip  
(modules only)  
This pad can be used (along with Control Enable) to trip the module output circuit  
breaker open (disconnecting the module from the UPS system).  
26  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 11 Switches Behind SCC Control Panel Door  
Item  
Description (Location)  
Function  
1
Interlock Button  
(on rear of Control Panel)  
Press this button to make authorized changes to any site parameter protected by  
the Security Access function. These include the time, date, auto-dial phone  
number, and other site parameters.  
2
3
Bypass Reset Switch  
(SW1, on Transfer  
Relay Board)  
Press this button to reset the transfer relays during start-up, after an Emergency  
Power Off shutdown. You must press this button before the Close Bypass Switch  
(Item 3).  
Close Bypass Switch  
(SW1, on System  
Interface Board)  
Press this button to close the Bypass circuit breaker during a start-up procedure, if  
it remains open after a shutdown procedure (refer to 3.3.1 - Start-Up Procedure).  
Note that the Static Switch Disconnects must be OFF to reset the Bypass circuit  
breaker. See also Bypass Reset Switch (Item 2).  
27  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 12 Menu Tree  
Figure 12 illustrates the primary screens that you can access through the Operator Interface Display System. The  
liquid crystal display (LCD) screen provides a full 80 characters by 25 lines of information for easy readability.  
The following subsections describe what these screens display and how and when to use them.  
Module status information is available on the display screen, provided Control Power is ON, even when the  
UPS module is not operating. System status information is available on the SCC display screen and at local and  
remote terminals when at least one module is on-line or when the bypass source is available.  
The screen will automatically display the Monitor/Mimic during normal operation. The System configuration  
screen will be displayed during start-up and whenever a system reset is required.  
If a module display screen is blank, either power is not available, the Rectifier Input (RIB) circuit breaker (exter-  
nal to the UPS module) is open, or the Control Power switch is OFF. If power is available and a display is blank,  
contact Liebert Global Services. Note that status information may be available at local and remote terminals. Use  
control touch pads at the SCC to manually transfer the critical load to the bypass line if the SCC display goes  
blank while load is on UPS (a very unlikely event).  
28  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.1 Master Menu Screen  
The Master Menu contains the primary menu selections that monitor and control the operation of the UPS.  
Figure 13 Master Menu Screens, SCC (above) and Module (below)  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
MASTER MENU  
MONITOR/MIMIC DISPLAY  
STATUS REPORTS  
START-UP PROCEDURES  
SHUTDOWN PROCEDURES  
METER CALIBRATION  
SYSTEM CONFIGURATION  
LIMIT SETTINGS  
BATTERY EQUALIZE  
LOAD TRANSFER PROCEDURES  
CUSTOMER ALARM DEFINITIONS  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
MASTER MENU  
MONITOR/MIMIC DISPLAY  
WALK-IN DISPLAY  
START-UP PROCEDURES  
SHUTDOWN PROCEDURES  
BATTERY TIME  
STATUS REPORTS  
SYSTEM CONFIGURATION  
LIMIT SETTINGS  
METER CALIBRATION  
BATTERY EQUALIZE  
From any primary screen (accessed directly from the Master Menu), pushing the Select pad once will return you  
to the Master Menu. From any secondary screen, pushing the Select pad twice will return you to the Master  
Menu.  
Please note that some screens have multiple pages. However, in each case instructions appear for accessing other  
pages.  
1. MONITOR/MIMIC DISPLAY.  
This graphic mimics the power flow through the UPS system. Input voltage and current readings, battery  
status, UPS ratings, load readings, circuit breaker indications, system status, and alarm messages are all dis-  
played on this screen.  
2. WALK-IN DISPLAY (modules only).  
This is a bar graph that shows DC bus voltage, input currents, and UPS module output voltage (all in percent  
of nominal).  
29  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. STATUS REPORTS.  
This display consists of three sub-menu selections: present status, history status, and event history. These  
screens display data on the system’s present and past performance. They also display information about any  
faults that have occurred in the system and total operating hours for the controls.  
4. SYSTEM CONFIGURATION.  
This screen displays the current configuration of the UPS system. It also enables the operator to reset the  
date, time, and dial-out phone numbers. The SCC current rating can also be adjusted lower than design max-  
imum. The operator can view, but cannot change, any of the settings unless the Interlock (Security Access)  
button is pressed.  
5. LIMIT SETTINGS.  
This security access display shows the present UPS system alarm limit settings. The operator can view the  
settings, but they should not be changed without consulting Liebert Global Services.  
6. LOAD TRANSFER PROCEDURES (SCC only).  
This screen specifies all of the steps required to manually transfer the critical load between the UPS system  
and the bypass source. Comparisons of the voltage frequency, and phase synchronization of the UPS system  
output and the bypass line are also illustrated to aid in the transfer or retransfer procedure.  
7. START-UP PROCEDURES.  
This two-page screen lists step-by-step procedures to start the UPS system and the modules.  
8. SHUTDOWN PROCEDURES.  
This two-page screen lists the proper sequence of steps to shutdown the UPS system and the modules for  
maintenance or repairs. The steps instruct the operator to transfer the critical load to bypass, open the battery  
circuit breakers, and open the UPS module output and input circuit breakers to shut down and isolate the  
modules. The critical load will remain on bypass power unless circuit breakers outside the UPS system are  
also opened.  
9. BATTERY TIME (modules only).  
This graph displays the projected battery voltage drop caused by a battery discharge over time. During a  
period of battery discharge, the Series 600T calculates the battery time remaining based on battery rating,  
initial battery condition, and actual connected load. The UPS continues to update and display both rated  
(theoretical) and calculated time every 6 seconds. This enables the operator to immediately see the effects of  
load shedding on time remaining and to accurately assess his power resources.  
10. METER CALIBRATION.  
This security access screen enables an authorized Liebert field-service engineer to adjust and calibrate the  
UPS metered functions. The operator can view, but should not change, any of the settings  
11. BATTERY EQUALIZE.  
The battery equalize screen lets the operator change the battery equalize recharging mode from manual to  
automatic and to observe or change the equalize time. Battery equalize charge voltage is higher than battery  
float (constant) charge voltage.  
12. CUSTOMER ALARM DEFINITIONS (SCC only).  
This optional screen allows the operator to define alarms for conditions external to the UPS, battery, or  
switchgear.  
NOTE  
Do not use battery equalize charging with sealed-cell batteries. Refer to the battery  
manufacturers manual for specific information about equalize charging.  
30  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.2 Monitor/Mimic Display Screen  
From SCC Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select pad  
and the Monitor/Mimic screen is displayed.  
The Monitor/Mimic display screen is a simplified block diagram of the UPS system. This screen gives the oper-  
ator an overall view of the power flow through the UPS system. The screen consists of three major sections: the  
input/UPS metering section, the load metering section, and the status and alarm message areas. The metered  
parameter values on the Monitor/Mimic screen are updated at one-second intervals.  
Figure 14 SCC Monitor/Mimic Display Screen  
4
1
2
BYPASS INPUT  
LOAD  
A-B  
B-C C-A  
627 KVA / 502 KW  
480V 480V 480V  
60.0 Hz  
A
B
C
3
UPS RATINGS  
SCCB 1600  
755A 755A 755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V 480V 480V  
A-B  
B-C C-A  
REDUNDANT  
480V 480V 480V  
60.0 Hz  
5
7
6
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
Input Metering Displays  
NOTE  
All voltage readings are phase-to-phase measurements (A-B, B-C, and C-A). All  
current readings are phase measurements (A, B, and C).  
Item 1 - Bypass Input. This block displays the bypass input voltage and the bypass input frequency. The System  
Bypass Breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or  
closed.  
Item 2 - UPS Input Pwr. This block displays the input voltage to the UPS modules.  
Output Metering Displays  
Item 3 - UPS Ratings. The SCC current rating is specified at the top of this block. The UPS system output volt-  
age and frequency are also displayed in this block. The UPS Output Breaker is shown to the right of this block.  
The status of the circuit breaker is illustrated as open or closed.  
Item 4 - Load. This block displays the total output power to the critical load in kVA and kW. The critical load  
current per phase is also displayed in this block. Note that kW is not displayed when the load is on the bypass  
line.  
The load block also indicates the number of modules connected and whether the UPS system is operating in the  
redundant or non-redundant mode.  
During an overload condition, the time remaining before shutdown or transfer is displayed at the bottom of the  
load box.  
31  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Status/Alarm Message Areas  
The status/alarm message areas display vital information about the operation of the UPS system. During normal  
operation no alarm messages should be present. Changes in the status of the system and possible alarm condi-  
tions can be monitored. Both the status and the alarm messages are displayed in reverse video (highlighted—  
light on dark). The alarm messages continue flashing until the Horn Off pad is pressed. To clear a latching  
alarm, you must also press the Alarm Reset pad after the alarm condition is corrected.  
NOTE  
The Alarm Reset pad also resets the History Status Report memory buffer when it is  
held for 15 seconds (or until the screen clears).  
The following lists show the status and alarm messages that may be displayed in these areas. For more informa-  
tion and the corrective actions for these messages, refer to Table 1 in this section.  
Item 5 - Module Status Messages  
Module On Line  
Module Off Line  
Module Summary Alarm  
Module Communication Failure  
Item 6 - System Status Messages  
Static Switch Connected  
Static Switch Disconnected  
OK To Transfer  
Not OK To Transfer  
Item 7 - Alarm Messages  
Load On Bypass  
Auto Retransfer Primed  
Manual Reset/Retransfer  
Static Switch Unable  
Bypass Not Available  
Bypass Phase Sequence Wrong  
Control Power Fail  
Output Over/Under Frequency  
Output Under-Voltage  
Output Over-Voltage  
Overload  
Overload Transfer  
Emergency Off  
Module Summary Alarm  
Battery Cycle Buffer Warning  
32  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
From module Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select  
pad and the Monitor/Mimic screen is displayed.  
The Monitor/Mimic display screen is a simplified block diagram of the UPS module and power connections.  
This screen gives the operator an overall view of the power flow through the UPS module. The screen consists of  
three major sections: the input/UPS metering section, the load metering section, and the status and alarm mes-  
sage areas. The metered parameter values on the Monitor/Mimic screen are updated at one second intervals.  
Figure 15 Module Monitor/Mimic Display Screen  
4
LOAD  
270 KVA / 217 KW  
A
B
C
3
UPS RATINGS  
AP648-84  
RATED 400 KVA  
OUTPUT VOLTAGE  
325A  
1
2
325A  
325A  
UPS INPUT PWR  
A-B  
480V  
350A  
B-C C-A  
480V  
480V  
350A  
A-B  
B-C C-A  
350A  
480V 480V 480V  
60.0 Hz  
5
BATTERY  
VOLTS 540  
AMPS 15 CHARG  
NOTE  
All voltage readings are phase-to-phase measurements (A-B, B-C, and C-A). All  
current readings are phase measurements (A, B, and C).  
Input Metering Displays  
Item 1 - UPS Input Pwr. This block displays the UPS module input voltage and current. The Module Input  
breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.  
Item 2 - Battery. The battery block displays the DC bus voltage and the charge or discharge current to or from  
the battery. This block reads MODULE DC BUS when the battery circuit breaker is open and BATTERY when  
the battery circuit breaker is closed during normal operation. This block reads BATTERY EQUALIZE when  
the battery equalize charge voltage is used to recharge the battery. The Module Battery Disconnect (MBD) is  
shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.  
Output Metering Displays  
Item 3 - UPS Ratings. The module part number and kVA rating are specified at the top of this block. The UPS  
output voltage and frequency are also displayed in this block. The Module Output breaker is shown to the right of  
this block. The status of the circuit breaker is illustrated as open or closed.  
Item 4 - Load. This block displays the module output power to the critical load in kVA and kW. The critical load  
current per phase is also displayed in this block.  
33  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm Messages  
The alarm message area displays vital information about the operation of the UPS system. During normal opera-  
tion no alarm messages should be present. Alarm conditions can be monitored. The alarm messages are dis-  
played in reverse video (highlighted— light on dark). To clear a latching alarm, you must also press the Alarm  
Reset pad after the alarm condition is corrected.  
NOTE  
The Alarm Reset pad also resets the History Status Report memory buffer when it is  
held for 15 second (or until screen clears).  
The following list shows the alarm messages that may be displayed in this area. For more information and the  
corrective actions for these messages, refer to Table 1 in this section.  
Item 5 - Alarm Messages  
Input Fail  
DC Ground Fault  
DC Capacitor Fuse Blown  
Battery CB Open  
Battery Discharging  
Low Battery Warning  
Low Battery Shutdown  
DC Over-Voltage Shutdown  
Control Power Fail  
Inverter Non-Synchronized  
Overload  
Overload Shutdown  
Reverse Power  
Rectifier Fuse Blown  
Inverter Fault  
Hardware Shutdown  
Emergency Off  
Ambient Over-Temperature  
Blower Failed  
Equipment Over-Temperature  
Over-Temperature Timeout  
34  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 16 through Figure 20 illustrate how the Monitor/Mimic Display screens on the SCC and on a module  
depict the power flow through the UPS system.  
A three module system designed for redundant operation is shown. A multi-module UPS system may include up  
to six (6) modules for each System Control Cabinet (SCC).  
Figure 16 Monitor/Mimic Display Screen Examples: Normal Power Flow, SCC (above) and Module  
BYPASS INPUT  
LOAD  
A-B  
480V 480V  
B-C C-A  
627 KVA / 502 KW  
480V  
60.0 Hz  
A
B
C
UPS RATINGS  
SCCB 1600  
755A  
755A  
755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V  
480V 480V  
A-B  
480V  
B-C C-A  
480V 480V  
60.0 Hz  
REDUNDANT  
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
LOAD  
270 KVA / 217 KW  
A
B
C
UPS RATINGS  
AP648-84  
RATED 400 KVA  
410A  
410A  
410A  
UPS INPUT PWR  
A-B  
480V 480V  
350A  
B-C C-A  
480V  
350A 350A  
OUTPUT VOLTAGE  
A-B  
B-C C-A  
480V 480V  
60.0 Hz  
480V  
BATTERY  
VOLTS 540  
AMPS 15 CHARG  
35  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 17 Monitor/Mimic Display Screen Examples: Utility Fail, SCC (above) and Module  
LOAD  
BYPASS INPUT  
A-B  
0V  
B-C C-A  
627 KVA / 502 KW  
0V  
0V  
0 Hz  
A
B
C
UPS RATINGS  
SCCB 1600  
755A 755A 755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
0V  
0V 0V  
A-B  
B-C C-A  
480V 480V  
60.0Hz  
REDUNDANT  
480V  
MOD 1 ON LINE SUM ALM  
MOD 2 ON LINE SUM ALM  
MOD 3 ON LINE SUM ALM  
Byp Not Avail  
Static Sw Unable  
Module Sum Alm  
Not OK to Transfer  
Static Switch Connected  
LOAD  
270 KVA / 217 KW  
A
B
C
UPS RATINGS  
AP648-84  
RATED 400 KVA  
OUTPUT VOLTAGE  
325A 325A 325A  
UPS INPUT PWR  
A-B  
B-C C-A  
0V  
0A  
0V  
0A  
0V  
0A  
A-B  
480V  
B-C C-A  
480V 480V  
60.0 Hz  
BATTERY  
VOLTS 480  
AMPS 645 DISCHARG  
Input Fail  
Batt Discharging  
Not OK to Transfer  
Static Switch Connected  
36  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 18 Monitor/Mimic Display Screen Examples: Load on Bypass, UPS Modules On and Charging  
Battery, SCC (above) and Module  
BYPASS INPUT  
LOAD  
A-B  
B-C C-A  
627 KVA / 502 KW  
480V 480V 480V  
60.0 Hz  
A
B
C
UPS RATINGS  
SCCB 1600  
755A  
755A  
755A  
UPS INPUT PWR  
3 OF 3 MODULES  
CONNECTED  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V 480V  
480V  
A-B  
B-C C-A  
REDUNDANT  
480V  
480V 480V  
60.0 Hz  
MOD 1 ON LINE  
MOD 2 ON LINE  
MOD 3 ON LINE  
Load On Bypass  
OK to Transfer  
Static Switch Connected  
LOAD  
0 KVA / 0 KW  
A
B
C
UPS RATINGS  
0A  
0A  
0A  
AP648-84  
UPS INPUT PWR  
RATED 400 KVA  
A-B  
480V  
90A  
B-C C-A  
480V 480V  
90A 90A  
OUTPUT VOLTAGE  
A-B  
B-C C-A  
480V  
480V 480V  
60.0 Hz  
BATTERY  
VOLTS 540  
AMPS 75 CHARG  
37  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 19 Monitor/Mimic Display Screen Examples: Load on UPS, One UPS Module Off Line  
SCC (above) and Module  
LOAD  
627 KVA / 502 KW  
BYPASS INPUT  
A-B  
B-C C-A  
480V  
480V  
480V  
60.0 Hz  
A
B
C
UPS RATINGS  
755A 755A  
755A  
SCCB 1600  
UPS INPUT PWR  
2 OF 3 MODULES  
CONNECTED  
480V  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V  
480V  
A-B  
B-C C-A  
NON-REDUNDANT  
480V 480V 340V  
60.0 Hz  
MOD 1 ON LINE  
Module Sum Alm  
MOD2OFF LINE SUM ALM  
MOD 3 ON LINE  
OK to Transfer  
Static Switch Connected  
LOAD  
314KVA/251KW  
A
B
C
UPS RATINGS  
378A 378A 378A  
AP648-84  
UPS INPUT PWR  
RATED 400 KVA  
A-B B-C C-A  
405A 405A 405A  
OUTPUT VOLTAGE  
480V480V
480V  
A-B  
480V  
B-C C-A  
60.0 Hz  
480V 480V  
BATTERY  
VOLTS 540
AMPS15CHARG  
38  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 20 Monitor/Mimic Display Screen Examples: Load on Bypass, All UPS Modules Off Line  
LOAD  
627 KVA / 502 KW  
BYPASS INPUT  
A-B  
B-C C-A  
480V  
480V  
480V  
60.0 Hz  
A
B
C
UPS RATINGS  
755A 755A  
755A  
SCCB 1600  
UPS INPUT PWR  
0 OF 3 MODULES  
CONNECTED  
480V  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V  
480V  
A-B  
0V  
B-C C-A  
NON-REDUNDANT  
0V  
0V  
0 Hz  
MOD 1 OFF LINE SUM ALM  
Load on Bypass  
Static Sw Unable  
Module Sum Alm  
MOD2OFF LINE SUM ALM  
MOD 3 OFF LINE SUM ALM  
Not OK to Transfer  
Static Switch Connected  
LOAD  
0KVA/0KW
A
B
C
UPSRATINGS
0A 0A 0A
AP646-84
UPS INPUT PWR  
RATED 375 KVA  
A-B  
B-C C-A  
OUTPUT VOLTAGE  
480V 480V 480V  
A-B  
0V  
B-C C-A  
0A 0A 0A  
0V  
0V
0 Hz  
MODULE DC BUS  
VOLTS  
AMPS  
0
0
Input Fail  
Batt CB Open  
39  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.3 Walk-In Display Screen  
From the module Master Menu, highlight WALK-IN DISPLAY and then press the Select pad. Note that this  
screen is displayed at the UPS modules but is not required at the System Control Cabinet (SCC).  
Figure 21 Walk-In Display Screen During Start-Up  
SELECT :  
DOWN :  
SELECT :  
D.C. VOLTS  
MASTER MENU  
INPUT AMPS  
OUTPUT VOLTS  
0%  
25%  
50%  
75%  
100%  
The Walk-In Display screen enables the operator to monitor the UPS module DC bus voltage, the input currents,  
and the output voltage. This is important during the start-up procedures.  
During start-up, the UPS module input circuit breaker is closed and power is applied to the UPS module. The  
Walk-In Display screen graphically shows the voltage increasing on the DC bus as the UPS module rectifier  
begins to walk-in.  
The DC Volts bar gradually moves to the right. After the DC Volts bar reaches the 90% level, the UPS module  
inverter starts-up and the Output Volts bar also moves to the right. Both the DC Volts and the Output Volts  
bars should settle near the 100% line as the UPS module becomes fully energized.  
The three Input Amps bars (one for each phase of input current) move to the right during the initial transformer  
inrush. They should return to the left after the momentary inrush has subsided, then increase to about 10% as the  
DC Volts increase.  
Modules equipped with the optional input filter will indicate more than 10% with no connected load.  
NOTE  
After the critical load is transferred from the bypass line to the UPS modules, the  
Input Amps bars continue to indicate the percent of the design input current to the  
UPS module rectifier.  
If any Input Amps bar differs from the average bar length by more than 10%, call  
Liebert Global Services.  
40  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.4 Status Reports Screens  
Go to the Master Menu and move the highlighted cursor to STATUS REPORTS. Press the Select button and the  
Status Reports screen is displayed.  
The Status Report screen is divided into four submenu reports: PRESENT STATUS, EVENT HISTORY,  
HISTORY STATUS, and SYSTEM STATUS.  
To look at any of the reports, do the following:  
1. From the Status Reports screen, press the Up or Down pad to move the highlighted cursor to the desired  
selection.  
2. Press the Select pad to view the desired report page.  
3. Use the Up and Down pads to move through a report that includes several screens (frames).  
4. Press the Select pad to exit the report.  
5. To return to the Master Menu, return to EXIT and press the Select pad.  
Each report screen includes the date, time, and a frame number. The frame number indicates the relationship  
sequence of a 4 millisecond time segment. The SCC and each module generate their own frame numbers inde-  
pendently. The clock in each module is synchronized to the SCC clock.  
NOTE  
Each of the four Status Reports can be displayed on a remote terminal. Refer to  
3.1.14 - Communication Interfaces.  
Figure 22 Status Reports Screen  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
EXIT  
PRESENT STATUS  
EVENT HISTORY  
HISTORY STATUS  
SYSTEM STATUS  
41  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Present Status  
The Present Status screen shows the current status of the UPS system (SCC) or module. This screen displays any  
alarm messages that are present and the values of the metered parameters for each cabinet. Battery values are dis-  
played only at the UPS modules.  
Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the upper right  
corner. The Present Status screen display is updated every two seconds.  
Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge. The value is  
on the Battery Volts line in the TIME column (far right side of the screen). For the first two minutes of discharge,  
the Rated Time Remaining is displayed. After that, the Calculated Time Remaining is displayed, and updated  
every six seconds.  
All the information on this screen, including Battery Time Remaining, is available to a local terminal or modem  
through the communications ports provided in the Series 600T UPS. Refer to Table 3 in this manual for key-  
board commands to use with the communication ports.  
Figure 23 Present Status Report Screens, SCC (above) and Module  
PRESENT STATUS  
MODULE-0  
01/12/98  
14:06:26  
FRAME 35  
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Batt Discharging  
DC  
HERTZ  
A
480  
325  
B
480  
325  
C
480  
325  
LOAD  
TIME  
0:06  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
LOAD KVA  
60.0  
270  
BYPASS VOLTS  
0
0
0
END OF REPORT  
EXIT  
SELECT :  
PRESENT STATUS  
MODULE-0  
01/12/98  
14:06:26  
FRAME 35  
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Batt Discharging  
DC  
HERTZ  
A
480  
325  
B
480  
325  
C
480  
325  
LOAD  
TIME  
0:09  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
BATTERYVOLTS  
BATTERYAMPS  
INPUT VOLTS  
60.0  
480  
0
0
0
0
0
0
-645  
INPUTAMPS
LOAD KVA  
270  
END OF REPORT  
SELECT : EXIT  
42  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Event History  
The Event History screen lists the active alarms present in the UPS system (SCC) or modules. This screen also  
displays the prior 128 alarm frames, in a first-in first-out (FIFO) sequence, that have taken place along with the  
date and the time that each alarm frame occurred. Use the Up and Down pads to look through the different alarm  
frames.  
Figure 24 Event History Report Screen  
EVENT HISTORY  
MODULE-0  
01/17/98  
15:06:41  
FRAME 175  
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Batt Discharging  
Low Batt Warning  
UP : NEXT FRAME  
DOWN : PREVIOUS FRAME  
SELECT : EXIT  
43  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
History Status  
The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen. Note that  
the values for output volts and amps are updated once each millisecond. Alarms are listed in the sequence they  
occurred, within 1 millisecond resolution. The frames are stored in a buffer (a computer information storage  
technique). The buffer stores the frames in a first-in first-out sequence. As a new frame enters the buffer the old-  
est one is released.  
When a designated fault occurs (see list below), the buffer stores information for the next 24 frames and then  
freezes (stops gathering information). At that time, the History Status screen contains 40 frames before the fault,  
the frame when the fault occurred, and 23 frames after the fault. This 64-page report is a very useful diagnostic  
tool for the operator or Liebert Global Services. Use the Up and Down pads to view the screens.  
Figure 25 History Status Report Screens  
HISTORY STATUS  
ORDER - 000000  
MODULE-0  
04/10/97  
16:49:21  
FRAME 36  
SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** Output Ov-volts  
DC  
A
480  
420  
B
480  
420  
C
480  
420  
LOAD  
349  
TIME  
HERTZ  
60.0  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
LOAD KVA  
BYPASS VOLTS  
480  
480  
480  
UP : NEXT FRAME  
DOWN : PREVIOUS FRAME  
SELECT : EXIT  
HISTORYSTATUS  
MODULE-0 01/17/98 11:21:59 FRAME100  
SITE ID - 00000 SITE TAG - 0000000  
**** ACTIVE ALARMS **** BattDischarging Low Batt Warning  
ORDER - 000000  
DC  
A
B
C
LOAD  
HERTZ  
TIME  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT FREQUENCY  
OUTPUTVOLTS  
OUTPUTAMPS
BATTERY VOLTS  
OUTPUT VOLTS  
OUPUT AMPS  
480  
325  
480  
325
480  
325
60.0  
480  
325  
480  
325
480  
325
390  
0:01  
480  
325  
480  
325  
480  
325  
-645  
BATTERY AMPS  
INPUT VOLTS  
0
0
0
INPUT AMPS  
0
480  
325  
0
480  
325  
0
480  
325  
UP : NEXT FRAME  
DOWN : PREVIOUS FRAME  
SELECT : EXIT  
OUPUT VOLTS  
OUTPUT AMPS  
LOAD KVA  
270  
44  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The alarm conditions that cause the History Status buffer to stop gathering new data are:  
SCC  
Module  
DC Cap Fuse Blown  
DC Over-Voltage Shutdown  
Inverter Fault  
Auto Transfer to Bypass  
Output Over-Voltage  
Output Under-Voltage  
Overload Transfer  
Low Battery Shutdown  
Overload Shutdown  
Over-Temperature Timeout  
Rectifier Fuse Blown  
Reverse Power  
Note that the Emergency Off alarm will also freeze the SCC History Status buffer with the Auto Transfer to  
Bypass alarm (if the load is on the UPS system when the alarm condition occurs).  
The History Status buffer does not resume collecting new frames until the fault is cleared and the Alarm Reset  
pad is pressed for 15 seconds (or until the screen clears).  
45  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Status  
The System Status screen displays the module Total Operating Hours and the Battery Cycle Monitor.  
Battery Cycle Monitor (Module Only)  
Selecting the Battery Cycle Monitor gives you access to detailed information about the module’s most recent  
battery discharge events. Periodic review of this data can give a good indication of battery performance and  
expected life.  
Each battery discharge cycle is put into one of four categories, depending on the length of the event:  
• 0-30 Seconds Discharge  
• 31-90 Seconds Discharge  
• 91-240 Seconds Discharge  
• Over 240 Seconds Discharge  
Each discharge cycle is sorted by time duration and tagged with the following system parameters:  
• System time and date  
• Event Number  
• Duration of cycle (seconds)  
• Lowest DC Bus Voltage  
• Highest DC Bus Current  
• kW carried by the batteries at the start of cycle  
• Battery Environment Ambient Temperature (when equipped with optional temperature sensor)  
Up to 132 discharge cycle events can be stored at any given time. When the buffer approaches its capacity, a  
warning message is broadcast via terminal and modem communication channels and a complete listing of all  
records (in order of occurrence) is sent to the terminal port. If a serial printer is attached to the terminal port, the  
operator can print a hard copy of the report. If a printer is not available, a terminal emulation program can cap-  
ture the report to disk for later review or printing. Once the buffer is filled, new data will replace the old on a  
First In, First Out basis as new cycles occur.  
To view this data, select the BATTERY CYCLE MONITOR option on the System Status screen. At the next  
screen (see Figure 26), you can select either the Battery Cycle Monitoring Summary screen or a screen showing  
detailed information on any one of the four categories of discharge (0-30 seconds, 31-90 seconds, 91-240 sec-  
onds and Over 240 seconds).  
Figure 26 Battery Cycle Monitor Screen  
UP : CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
E
EXIT  
...............................................  
Battery Cycle Monitor  
Battery Temperature  
Enable  
Enable  
...............................................  
Battery Cycle Monitoring Summary  
0-30 Seconds Discharge  
31-90 Seconds Discharge  
91-240 Seconds Discharge  
Over 240 Seconds Discharge  
Total Since 02/4/95  
................................  
................................  
................................  
................................  
11  
5
2
1
19  
The Summary screen (Figure 27) shows Total Number of Discharge Cycles, Accumulated Battery Time, Accu-  
mulated Battery Amp Hours, Accumulated Battery Kilowatt Hours, and Battery Temperature. During a battery  
discharge event, the screen changes to show information about the present discharge cycle. The screen displays  
46  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Active Cycle Time in place of Accumulated Battery Time, and shows Active Battery AH and Active Battery  
kWH instead of accumulated values.  
Figure 27 Battery Cycle Monitoring Summary Screen  
SELECT : EXIT  
Battery Cycle Monitoring Summary  
Total No. of Cycles . . . . . . . . . . . . .  
Accumulated Battery Time . . . . . . .  
Accumulated Battery AH . . . . . . . .  
Accumulated Battery KWH . . . . . . .  
Battery Temperature . . . . . . . . . . . .  
7
15 min. 32 sec.  
71  
34  
25°C / 77°F  
Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information can be col-  
lected remotely, through the optional communications board and modem, by a remote terminal or a personal  
computer equipped with a modem and communications program. See 3.1.14 - Communication Interfaces for  
more information.  
NOTE  
This information is applicable to systems with separate batteries for each module. If  
the modules share a common battery, select one module to do the monitoring and  
disregard the other(s).  
Figure 28 Typical Data on Discharge Cycles of 91 to 240 Seconds Duration During the Recording  
Period  
UP  
:
CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
Total 91-240 se c. Cycl  
EXIT  
5
Event  
Date  
Time Duration  
Min. Volt Max. Amp Start KW Start Temp  
15  
12  
9
5
2
4/12/95  
3/25/95  
3/13/95  
2/07/95  
11/24/94  
10:31  
20:21  
7:35  
17:22  
12:33  
235  
98  
139  
199  
95  
477  
479  
467  
478  
477  
110  
97  
173  
95  
70  
37  
69  
40  
39  
68  
65  
67  
70  
69  
83  
47  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.5 System Configuration Screens  
Go to the Master Menu and move the highlighted cursor to SYSTEM CONFIGURATION. Press the Select pad  
and the System Configuration screen is displayed.  
The System Configuration screen lists parameters that can be changed to adjust the “personality” of your UPS  
modules and the SCC to your site requirements. Some of the information displayed is factory set and should only  
be changed by Liebert Global Services. Parameters that should be adjusted by the user include date, time, auto  
dial number, and modem baud rate.  
The System Configuration screen is one of the displays that has controlled access to limit who is able to change  
site parameters. This type of screen is called a Security Access screen. This controlled access feature allows any-  
one to review the present parameters, but limits access for making changes. When you see Security Access dis-  
played on the screen (upper left corner), to make authorized changes you must open the control cabinet door (key  
required) and push the Interlock button on the back of the control panel (Figure 11). Close and lock the control  
cabinet door after making authorized changes.  
Figure 29 SCC System Configuration Screen  
UP  
:
CURSOR UP  
SECURITY ACCESS  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
SYSTEM CONFIGURATION  
EXIT  
Part Number .......................................  
Order Number ....................................  
Site ID Number ..................................  
Site TAG Number ..............................  
System Number .................................  
Number of Modules in System ..........  
Date ...................................................  
Time ...................................................  
Auto Dial ............................................  
Max Auto-Rexfer Attempts ................  
System Current Rating ......................  
System Options  
02-791112-14  
000000  
00000  
0000000  
1
2
01/17/96  
14:51:59  
YES  
5
1600  
NOTE  
If you accidentally set a site parameter digit to a wrong value, you must return to the  
System Configuration screen and go again to your desired screen.  
Part Number. This is a factory set part number of the UPS cabinet which determines many internal operating  
parameters. It cannot be changed.  
Order Number. This is a factory set number to identify your particular installation.  
System Number. This number is used to identify one or more UPS systems that may be present on one site.  
Number of Modules in System. This shows the total number of modules.  
48  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Date  
This is the system’s real-time date setting. The system control program sends to each module the date entered at  
the System Control Cabinet (SCC). You cannot change the system date from the control panel of a UPS module.  
Figure 30 Date Screen  
DATE  
01/17/96  
UP  
:
INCREASE VALUE  
DOWN : DECREASE VALUE  
SELECT : WALK-THRU/ EXIT  
To reset the date, do the following at the SCC.  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor to DATE.  
2. Press the Select pad. The Date screen will appear.  
3. Press the Select pad to move the arrow to the next digit to the right.  
4. When the arrow is on the digit to be changed, press the Up pad to increase the number or the Down pad to  
decrease it. Press Select to set the value and move to the next digit.  
5. After the correct month/day/year has been set, press the Select pad again to return to the System  
Configuration screen.  
NOTE  
Precise Date and Time functions are required for accurate archive and event history  
purposes.  
Both the Date and Time can be set from a remote terminal. Refer to 3.1.14 -  
Communication Interfaces.  
All Liebert Series 600T products can handle dates past the year 2000.  
49  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Time  
This is the system’s real-time clock. The system control program sends to each module the time entered at the  
System Control Cabinet (SCC).  
You cannot change the system time from the control panel of a UPS module.  
Figure 31 Time Screen  
TIME  
09:15:00  
UP  
:
INCREASE VALUE  
DOWN : DECREASE VALUE  
SELECT : WALK-THRU/ EXIT  
To reset the time do the following at the SCC:  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor to Time.  
2. Press the Select pad. The Time screen will appear.  
3. Press the Select pad to move the arrow to the next digit to the right.  
4. When the arrow is on the digit to be changed, press the Up or Down pad to increase or decrease the hour/  
minute/second number. Press Select to set the value and move to the next digit.  
5. After the correct hour/minute/second has been set, press the Select pad again to return to the System  
Configuration screen.  
NOTE  
Precise Date and Time functions are required for accurate archive and event history  
purposes.  
Both the Date and Time can be set from a remote terminal. Refer to 3.1.14 -  
Communication Interfaces.  
50  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auto Dial  
This is a feature that automatically dials (through a customer supplied PC-compatible modem) a pre-pro-  
grammed telephone number (up to 12 digits) when specified alarm conditions occur within the UPS system. The  
connection for the modem is at the SCC. Automatic dial attempts to the first number are made at periodic inter-  
vals for 30 minutes. If unanswered, the system rolls over to the second number and repeats the process until con-  
nection is made.  
Upon connection, the system transmits data, in RS-232C format, that includes the system identification code, the  
present alarm message(s) and the time that the alarm(s) occurred. Refer to 3.1.14 - Communication Interfaces.  
Refer to the Special Functions column in Table 1 to see which alarm messages will initiate an auto-dial call.  
Figure 32 Auto Dial Setting Screen  
UP  
:
CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
AUTO DIAL SETTING SCREEN  
EXIT  
Enable Auto Dial .....................................  
Modem Baud Rate ..................................  
Auto Dial Number ...................................  
Second Number ...............................  
YES  
2400  
1 800 555 - 1234  
0 000 000 - 0000  
xxxxxxxxxxxxxxxxxxx  
Modem Initialization String .....................  
If the auto-dial numbers were specified at time of order or installation, the numbers are pre-programmed into the  
system. However, if the numbers need to be changed, follow the steps listed below to reprogram the auto-dialer  
at the SCC.  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor to Auto  
Dial.  
2. Press the Select pad. The Auto Dial screen will appear.  
3. Move to and select the first Auto Dial Number.  
4. Press the Select pad to move the arrow to the next digit to the right.  
5. When the arrow is on the digit to be changed, press the Up pad to increase the number or press the Down  
pad to decrease it. Press Select to set the value and move to the next digit.  
6. After all of the changes have been made, press the Select pad again to return to the System Configuration  
screen.  
7. If required, go to the Second Number screen and enter the correct number.  
51  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Modem Baud Rate  
This sets the transmission rate at which the system relays data to a terminal through the modem.  
Figure 33 Modem Baud Rate  
UP  
:
CURSOR UP  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
AUTO DIAL SETTING SCREEN  
EXIT  
Enable Auto Dial .....................................  
Modem Baud Rate ..................................  
Auto Dial Number ...................................  
Second Number ...............................  
YES  
2400  
1 800 555 - 1234  
0 000 000 - 0000  
xxxxxxxxxxxxxxxxxxx  
Modem Initialization String .....................  
To change the modem baud rate, do the following at the SCC:  
1. From the System Configuration screen, press the Up or Down pad to move the highlighted cursor to Auto  
Dial.  
2. Move to and select the Modem Baud Rate.  
3. Press the Up or Down pad to display the desired baud rate.  
4. Press the Select pad to set the baud rate and to return to the System Configuration screen.  
52  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maximum Auto-Retransfer Attempts  
When a UPS output overload condition exceeds a pre-programmed current-versus-time window (based on the  
SCC current rating), the UPS automatically transfers the critical load to the bypass line. After the overload condi-  
tion has been corrected, the UPS attempts to automatically retransfer the critical load to the UPS output (unless  
zero attempts is selected). The Maximum Auto-Retransfer Attempts limits the number of times (0 to 5) that  
the UPS attempts to retransfer the load back to the UPS within a one-hour time period.  
If more than the selected number of overloads occurs during one hour, the critical load remains on the bypass line  
and must be manually retransferred to the UPS system. Note that you should determine the cause of any overload  
condition.  
Note that automatic retransfers are initiated only if the critical load was transferred to the bypass line because of  
a system overload. If an automatic transfer to bypass occurred for any other reason, an automatic retransfer will  
not be initiated. Refer to 3.4.3 - Automatic Retransfers to UPS.  
Figure 34 Maximum Auto-Retransfer Attempts Screen  
MAX AUTO-REXFER ATTEMPTS  
LOWER INPUT  
0
UPPER LIMIT  
5
VALUE  
3
UP  
:
INCREASE  
DOWN : DECREASE  
SELECT : EXIT  
To change the Maximum Auto-Retransfer Attempts parameter, do the following at the SCC:  
1. From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto-  
Retransfer Attempts.  
2. Press the Select pad. The screen above will appear.  
3. Press the Up pad to increase the value or the Down pad to decrease it.  
4. Press the Select pad to set the value and to return to the System Configuration screen.  
53  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Remote Monitor  
The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for customer use  
through a set of contacts on a separate terminal board.  
When the New Alarm, System Summary Alarm, or Module Summary Alarm is activated, you can get more  
information at the Operator Display Panel or through a remote terminal. Refer to 3.1.14 - Communication  
Interfaces.  
.
SCC and Module Remote Monitor Indications  
SCC Remote Monitor Indications  
Load On UPS  
Load On Bypass  
Battery Discharging  
Low Battery Warning  
Overload  
Channel Module Remote Monitor Indications  
CH1  
CH2  
CH3  
CH4  
CH5  
CH6  
CH7  
CH8  
Output CB Open  
Battery CB Open  
Battery Discharging  
Low Battery Warning  
Control Failure  
Ambient Over-Temp  
System Summary Alarm  
New Alarm  
Ambient Over-Temp  
Module Summary Alarm  
New Alarm  
The following alarms, as well as those listed above, will activate the System Summary Alarm or the Module  
Summary Alarm.  
Other Alarms That Activate Summary Alarms  
Other Alarms That Activate  
System Summary Alarm  
Other Alarms That Activate  
Module Summary Alarm  
Control Power Fail  
Blower Failed  
Emergency Off  
Control Power Fail  
DC Capacitor Fuse Blown  
DC Ground Fault  
DC Over-Voltage Shutdown  
Emergency Off  
Module Summary Alarm  
Output Over/Under Frequency  
Output Over-Voltage  
Output Under-Voltage  
Overload Transfer  
Equipment Over-Temperature  
Inverter Fault  
Static Switch Unable  
Low Battery Shutdown  
Overload  
Overload Shutdown  
Rectifier Fuse Blown  
Reverse Power  
54  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.6 Alarm Limit Settings Screen  
Go to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad and the  
Limit Settings screen is displayed.  
The Alarm Limit Settings screen has Security Access to enable an authorized Liebert field-service engineer to  
adjust the UPS system alarm limit settings.  
CAUTION  
All alarm limit settings are application matched and factory set. They should not  
be changed casually. Contact Liebert Global Services for changing the alarm  
limit settings.  
Figure 35 Module Alarm Limit Settings Screen  
UP  
:
CURSOR UP  
SECURITY ACCESS  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
ALARM SETTINGS  
EXIT  
Overload Alarm ...............................  
DC Over Voltage ...............................  
Battery Discharging ...........................  
Low Battery .......................................  
Battery Shutdown (15 minutes) ......  
Upper Point (60 minutes) ......  
104  
600 VDC  
480 VDC  
437 VDC  
384 VDC  
427 VDC  
%
Battery Rating (100%) .....................  
Battery Rating ...................................  
500 KW 15 min  
250 KW 45 min  
Overload Alarm (SCC and modules). This alarm setting initiates an alarm message on the display screen warn-  
ing the operator that the UPS system output current has exceeded the specified limit. This condition only acti-  
vates an alarm. The UPS does not shut down, but a separate control circuit will transfer the critical load to bypass  
if the current and time of the overload condition exceeds system capability.  
DC Over-Voltage (modules only). This setting limits the maximum permitted level of the DC bus voltage.  
When this setting is exceeded, an alarm indication appears on the module display screen. The UPS module is  
taken off-line (the module output circuit breaker is tripped open), and the input and battery circuit breakers trip  
open.  
Battery Discharging (modules only). When the battery voltage on the DC bus falls below this limit for 5 sec-  
onds, a Battery Discharging alarm message is displayed on the module screen. This means that the battery is dis-  
charging due to an input voltage sag or interruption, or a module output overload.  
Low Battery (modules only). While the battery is discharging, this alarm warns the operator that the Battery  
Shutdown level is approaching. This is typically set for a reserve time of approximately five minutes (10 volts  
above the 60-Minute Battery Shutdown Voltage), based on full load operation.  
Battery Shutdown (15 Minutes) (modules only). When the battery voltage decreases to this limit for five sec-  
onds during the first 15 minutes of the discharge, the battery circuit breaker opens to prevent over-discharge.  
Note that the rated battery reserve time at your site may be other than 15 minutes.  
Battery Shutdown (60 Minutes) (modules only). During extended outages or deep sags of more than 15 min-  
utes, the shutdown voltage limit will ramp up gradually to this 60-minute limit to prevent lengthy discharge and  
possible battery damage. The battery circuit breaker opens when the battery voltage and the shutdown limit are  
equal for five seconds. See the Battery Time screen for more information. Also refer to the battery manufac-  
turer’s manual.  
Battery Rating (100%) (modules only). This setting is the full load discharge rating of the battery in kilowatts  
for the rated backup period. A typical rating might be 500 kW for 15 minutes.  
55  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Rating (modules only). This setting is a battery discharge rating in kilowatts under partial load for an  
extended period, typically 60 minutes. The UPS uses the two battery shutdown voltage settings and the two bat-  
tery discharge ratings in computing rated and calculated time remaining during a discharge event.  
NOTE  
The Low Battery alarm setting is designed to be useful at full load battery discharge  
rates. It is typically set for 10 volts above the 60-Minute Battery Shutdown voltage, to  
provide some measure of warning under all circumstances. If the discharge period  
extends past 15 minutes (i. e., the load on the UPS is less than full capacity), the  
Battery Shutdown voltage setting is gradually and automatically increased to protect  
the batteries from deep discharge. The Low Battery alarm setting is not automatically  
increased and should not be relied upon as an accurate indicator of battery time  
remaining. Instead, the operator should consult the Battery Time screen or Present  
Status screen to see the calculated time remaining based on actual usage during the  
discharge period.  
56  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.7 Load Transfer Procedures Screen  
Go to the SCC Master Menu and move the highlighted cursor to LOAD TRANSFER PROCEDURES. Note  
that this screen is displayed at the System Control Cabinet but is not required at the UPS modules. Press the  
Select pad and the Load Transfer Procedures screen is displayed.  
The Load Transfer Procedures screen contains instructions to transfer the critical load between the UPS system  
and the bypass line. Comparisons of the UPS and bypass voltage, frequency, and phase synchronization are dis-  
played along with transfer status messages and an indication of circuit breaker overlap time. The metered param-  
eter values on the Load Transfer Procedures screen are updated at half-second intervals.  
Refer to 3.3.2 - Load Transfer Procedures for more details.  
Figure 36 Load Transfer Procedures Screen  
1
H
SELECT : MASTER MENU  
2
VOLTAGE COMPARISON  
SYNCHRONIZATION  
FREQUENCY  
A-B B-C C-A  
-30  
0
+30  
UPS  
BYPASS  
-
-
480 480 480  
60.0 Hz  
60.0 Hz  
4
481 480 479  
3
MANUAL  
UPS LEAD  
=
2 Deg  
TRANSFER INSTRUCTIONS  
Adjust the UPS voltage until it equals the  
ON UPS  
1.  
OK TO TRANSFER  
bypass voltage with the VOLTAGE ADJUST pot.  
If the OK TO TRANSFER message is highlighted,  
simultaneously press the BYPASS and CONTROL ENABLE  
TRANSFER PROHIBIT  
2.  
buttons.  
3.  
Verify that the transfer was successful by checking the  
breaker status on the "MONITOR/MIMIC" screen.  
4.  
Press the ALARM RESET button to clear alarms which  
are no longer active  
Item 1 - Voltage Comparisons. This chart shows the UPS and bypass voltage and frequency comparisons  
between each of the three phases. If the UPS and bypass voltages are not within specified tolerances, a manual  
transfer is not permitted and TRANSFER PROHIBIT is highlighted.  
The Voltage Adjust knob (push-to-turn), located on the SCC Operator Control Panel (Figure 10), is used to  
match the UPS output voltage to the bypass voltage. When the UPS and bypass voltages match within the spe-  
cific tolerance, a manual transfer is possible and OK TO TRANSFER is highlighted.  
CAUTION  
The UPS output voltage responds very slowly to inputs from the Voltage Adjust  
knob. Make small adjustments and wait several seconds each time for voltage to  
stabilize before continuing.  
Item 2 - Synchronization. This display shows the phase synchronization between the UPS output and bypass  
power. If the phase displacement is outside of the tolerance, a manual transfer is not permitted and TRANSFER  
PROHIBIT is highlighted.  
During normal operation, the synchronization display should read UPS LEAD from zero to 4 degrees.  
Item 3 - Status Messages. Three messages are constantly displayed here. Only the active message is high-  
lighted. If TRANSFER PROHIBIT is highlighted, manual transfers/retransfers cannot be performed, and auto-  
matic retransfers will not be initiated.  
Item 4 - Manual Transfer Instructions. These instructions assist the operator in transferring the critical load  
between the UPS system and the bypass line.  
If the load is on the bypass line, step 2 on the screen will instruct you to press the UPS and Control Enable but-  
tons to retransfer the load from the bypass line to the UPS system.  
57  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.8 Start-Up Procedures Screen  
From the SCC Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the Select pad  
and the SCC Start-Up Procedures screen is displayed.  
This screen contains the steps you must follow to start-up the UPS system. The instructions are listed so you can  
review them prior to performing the start-up.  
Figure 37 SCC Start- Up Procedures Screen  
SELECT :  
MASTER MENU  
START-UP PROCEDURES  
1.  
2.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model number is  
displayed.  
3.  
4.  
Go to the modules(s) and follow the module "STARTUP PROCEDURES".  
Select "MONITOR/MIMIC" screen, verify that the output voltages are at the  
proper nominal level and correct number of modules online is displayed.  
5.  
6.  
If the bypass or static switch breakers are open, refer to Start-up Procedures  
in the UPS manual for instructions on closing these breakers.  
System is now ready to assume load. Select "LOAD TRANSFER PROCEDURES"  
screen for this procedure.  
Prior to this procedure, supply power to the critical load through the bypass line. Start-up each UPS module  
according to the module start-up procedures. You can then transfer the load from bypass to the UPS system per  
instructions on the SCC Load Transfer Procedures Screen.  
Refer to 3.3.1 - Start-Up Procedure for more details.  
NOTE  
If the system was shut down in response to an “Emergency Off” signal (typically  
because of a load fault), there may be alarm messages on the LCD screen that  
describe system conditions before (or at the time of) the shutdown. Some or all of the  
alarm conditions may have already been resolved. To clear these alarm messages,  
make sure the critical load is on bypass power and turn off the control power (see  
Figure 8 and Figure 9). Wait at least ten minutes for the control power circuitry to  
completely de-energize. After ten minutes, turn control power back on and follow the  
start-up procedures on the UPS and SCC screens.  
58  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
From the module Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the Select  
pad and the module Start-Up Procedures screen is displayed.  
This two-page screen contains the steps you must follow to start-up each UPS system. The instructions are listed  
so you can review them prior to performing the start-up.  
Figure 38 Module Start- Up Procedures Screen  
DOWN : NEXT PAGE  
SELECT : MASTER MENU  
START-UP PROCEDURES  
1.  
Verify that the control power is applied to the system control cabinet (check the display  
on the system control cabinet).  
2.  
3.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model is  
displayed.  
4.  
Select "WALK-IN" screen and do the following:  
a)  
Close module input circuit breaker. Verify that the DC voltage bar on  
the display begins to gradually move to the right and the AC input  
current bars do not move to the right more than 10% (40% for modules  
with input filters) after the transformer inrush has subsided.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
START-UP PROCEDURES (Cont'd)  
b)  
c)  
Verify that the output voltage bar moves to the right after the DC  
bus bar has reached the 90% point. Both bars should settle near  
their respective 100% levels.  
If anything happens on the display not mentioned in (a) or (b),  
immediately open the module input circuit breaker and investigate.  
5.  
6.  
If step 4 is successful, select "MONITOR/MIMIC" screen and verify module  
DC bus and output voltages are at proper nominal level. If so, close  
module battery circuit breaker.  
If no alarms are present on the "MONITOR/MIMIC" screen, the module may be  
placed online by closing the module output breaker.  
Prior to this procedure, supply power to the critical load through the bypass line (at the SCC). When you close  
the UPS module input breaker, power is provided to the UPS rectifier. The module DC bus voltage ramps up to  
the nominal battery voltage and the UPS inverter turns on when the DC bus reaches the proper voltage. You can  
then close the battery circuit breaker (MBD) and the UPS module output circuit breaker to place the UPS module  
on-line.  
Refer to 3.3.1 - Start-Up Procedure for more details.  
59  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.9 Shutdown Procedures Screen  
Go to the SCC Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select pad and  
the SCC Shutdown Procedures screen is displayed.  
This screen contains the steps you must follow to perform a controlled shutdown of the UPS system. The instruc-  
tions are listed so you can review them before performing the controlled shutdown.  
Figure 39 SCC Shutdown Procedures Screen  
SHUTDOWN PROCEDURES  
1.  
If load is not already being supplied by the bypass line, select the  
"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer  
the load to bypass.  
2.  
3.  
4.  
Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES."  
Press the ALARM RESET button to clear alarms which are no longer active.  
If necessary for maintenance purposes, open the static switch disconnect  
circuit breakers.  
5.  
Wait approximately two (2) minutes before attempting any other action .  
To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line. Shut down  
each UPS module according to the module Shutdown Procedures.  
Refer to 3.3.3 - Shutdown Procedures for more details, including emergency shutdowns.  
60  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Go to the module Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select pad  
and the module Shutdown Procedures screen is displayed.  
This two-page screen contains the steps you must follow to perform a controlled shutdown of each UPS module.  
The instructions are listed so you can review them before performing the controlled shutdown.  
Figure 40 Module Shutdown Procedures Screen  
DOWN : NEXT PAGE  
SELECT : MASTER MENU  
SHUTDOWN PROCEDURES  
1.  
If load can not be supported by the remaining modules when this module  
is taken off line, go to the system control cabinet and select the "LOAD  
TRANSFER PROCEDURES" screen. Follow the instructions to transfer  
to bypass.  
2.  
3.  
4.  
Open the module output breaker by simultaneously pressing the OUTPUT TRIP  
and CONTROL ENABLE pushbuttons.  
Open the module battery breaker by simultaneously pressing the BATTERY TRIP  
and CONTROL ENABLE pushbuttons.  
Manually open the input breaker by moving the handle to the OFF position.  
UP : FIRST PAGE  
SELECT :  
MASTER MENU  
SHUTDOWN PROCEDURES (Cont'd)  
5.  
6.  
Verify breaker status on the "MONITOR / MIMIC" screen.  
If necessary for maintenance purposes, turn the control power switch (fuse  
disconnect on some models) to the OFF position.  
7.  
Wait a minimum of two (2) minutes before attempting any other action.  
To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line (at the  
SCC). Then trip open the UPS module output and battery circuit breaker (MBD), and manually open the UPS  
module input circuit breaker. The Control Power switch may be turned Off if required for maintenance proce-  
dures.  
Refer to 3.3.3 - Shutdown Procedures for more details, including module shutdowns for service and emergency  
shutdowns.  
61  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.10 Battery Time Screen (Module Only)  
At the Master Menu, move the highlighted cursor to BATTERY TIME. Press the Select pad and the Battery  
Time screen is displayed.  
When AC power is not available to the UPS module, the UPS inverter uses DC power from the battery to supply  
the critical load. This screen helps the operator assess his power resources to determine if and when the critical  
load shutdown procedures need to be started.  
The Battery Time screen is a line graph that tracks the present battery voltage versus the elapsed time that the  
battery has been discharging (Figure 41). As the battery voltage decreases, the line representing it moves closer  
to intersecting the line that represents the battery shutdown voltage. When the battery starts to discharge, the  
screen displays a 15-minute graph. If the battery has been providing power for more than 15 minutes, the screen  
displays a 30-minute graph. If battery power is still available after 30 minutes, a 60-minute graph is displayed  
(Figure 42).  
Figure 41 Battery Time Screen Example - 15 Minute Discharge  
VDC  
500  
SELECT : MASTER MENU  
Low Battery Warning  
Calculated Time (Hrs:Min)  
Total 00:15 Remain 0:01  
480  
460  
440  
420  
400  
380  
360  
340  
Battery Shutdown = 384  
Battery Charge = 5%  
Rated Time (Hrs:Min)  
Total 00:10 Remain 0:00  
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15  
Time (Minutes)  
NOTE  
If the UPS modules connect to independent battery plants, consult all the individual  
module screens to get the complete picture. If the modules share a common battery,  
select one module to do the monitoring and disregard the others.  
The screen also displays alarm messages (Battery Discharging, Low Battery Warning, and Battery Shutdown)  
and a set of five parameters that inform the operator of battery condition and time remaining. The five parameters  
describing battery resources are:  
• Rated Total Time, in hours and minutes, is the amount of battery backup time that should be available under  
full rated load, based on system design.  
• Rated Time Remaining is the Rated Total Time less the duration of the present discharge event.  
• Calculated Total Time is an estimate of the total battery backup time available, based on the initial battery  
condition and actual performance while powering the connected load during the discharge event.  
• Calculated Time Remaining is a real-time estimation of battery time remaining— with the actual connected  
load—before battery voltage drops to the Battery Shutdown setpoint.  
• Battery Charge is the approximate percentage of total designed ampere hours of battery capacity presently  
available based on recharge/discharge activity.  
Values for Calculated Total Time and Calculated Time Remaining will appear on the screen approximately two  
minutes after the beginning of the discharge event. Calculated Time Remaining also appears on the Present Sta-  
tus Report screen. Both Calculated Total Time and Calculated Time Remaining will be updated every six sec-  
onds, reflecting actual load changes and battery condition. When the Calculated Times become available, they  
will be displayed in place of the Battery Discharging message on this screen.  
62  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 42 Battery Time Screen Example - 45 Minute Discharge  
VDC  
500  
SELECT : MASTER MENU  
Low Battery Warning  
Calculated Time (Hrs:Min)  
480  
460  
440  
420  
400  
380  
360  
340  
Total 00:45 Remain 0:01  
Battery Shutdown = 417  
Battery Charge = 3%  
Rated Time (Hrs:Min)  
Total 00:25 Remain 0:00  
0
10  
20  
30  
40  
50  
60  
Time (Minutes)  
The Battery Time Remaining graph and the Calculated times are extremely helpful to the operator who has the  
discretionary authority to order load-shedding activities. The Series 600T automatically samples battery voltage  
and load current and recomputes every six seconds. This gives the operator fast and accurate feedback on efforts  
to extend battery time remaining by shutting down non-critical loads.  
NOTE  
While every effort has been made to make the Rated and Calculated Time Remaining  
values as accurate as practical, these values must be regarded as approximations. At  
the beginning of the discharge cycle, the Calculated times could be off by as much as  
±20% due to such variables as battery initial charge, age of battery, and the  
subsequent load-shedding activities of the operator. Within a few minutes, however,  
these calculations should settle into their design accuracy of ±10%, with the end-of-  
discharge tolerance being +0, -10% of actual observed time. In addition, the  
operator can adjust the settings affecting Rated Total Time after gaining experience  
with the actual battery and connected load.  
The Series 600T dynamically adjusts the Battery Shutdown voltage based on battery characteristics and the  
length of the current discharge event. If a discharge event extends past 15 minutes (i.e., the load is less than the  
full design rating), the Battery Shutdown voltage setting is gradually and automatically increased, to protect the  
batteries from deep discharge.  
When the battery voltage decreases to a preset limit (see 3.1.6 - Alarm Limit Settings Screen), the Low Battery  
Warning alarm message appears on the display screen. This warns the operator that the battery voltage is  
approaching the Battery Shutdown level—about five minutes of time remaining at full rated load.  
NOTE  
The Low Battery alarm setting is designed to be useful at full load battery discharge  
rates. Unlike the Battery Shutdown voltage, the Low Battery alarm setting is not  
automatically increased and should not be relied upon as an indicator of battery time  
remaining. Instead, the operator should consult the Battery Time screen or Present  
Status screen to see the Calculated Time Remaining based on actual usage during the  
discharge period.  
If the battery discharges to the Battery Shutdown level, represented by the lower line on the Battery Time screen,  
the battery and input circuit breakers trip open and the UPS module is shut down. This protects the battery from  
being damaged by an extended deep discharge.  
63  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 43 Range of Values for Calculated Battery Times  
2 5  
2 0  
1 5  
1 0  
5
0
2 .5  
5
7 .5  
1 0  
1 2 .5  
1 5  
1 7 .5  
2 0  
2 2 .5  
2 5  
Elapse d Tim e (M inu tes)  
Up p e r L im it  
A ctual  
L owe r L im it  
CAUTION  
When battery shutdown occurs, no power will be supplied to the critical load  
unless power is available through the bypass line from the utility source (or from  
an engine generator set). If you anticipate a battery shutdown (and an engine  
generator set is not available), either transfer the load to bypass (if available) or  
perform a controlled shutdown of the critical load.  
If the Battery Time screen is displayed while the battery is not discharging, it will display the present Battery  
Charge percentage and the results of the previous discharge event.  
NOTE  
1. During initial UPS start-up, the Battery Charge will display 100%, even though  
actual state of charge may be slightly less. It will normally take three to four days  
of operation to completely charge the battery. After the battery is fully charged  
the first time, Battery Charge will be an accurate indication of battery status.  
2. If Calculated Time Remaining is less than Rated Time Remaining, a battery  
problem may be indicated. Battery maintenance personnel should thoroughly  
examine the battery plant for factors that may reduce battery performance, such  
as:  
• Age of battery  
• Excessive battery discharge/recharge cycles  
• Bad or weak cells  
• Low acid levels in flooded cells  
• Loose electrical connections  
• Ambient temperature extremes  
• Dirty battery jar covers.  
3. If the battery plant has been thoroughly examined for proper maintenance and  
condition, and the Calculated value is still less than 80% of Rated value, contact  
Liebert Global Services.  
The Series 600T records information about each discharge event. This data can be reviewed on the Battery Cycle  
Monitor screen, as described in 3.1.4 - Status Reports Screens.  
64  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.11 Meter Calibration Screen  
Go to the Master Menu and move the highlighted cursor to METER CALIBRATION. Press the Select pad and  
the Meter Calibration screen is displayed.  
The Meter Calibration screen enables a Liebert field-service engineer to adjust the calibration of the UPS  
metered functions at each cabinet. Access to these settings is limited by the Security Access control.  
NOTE  
Bypass Volts are calibrated only at the System Control Cabinet (SCC). Input Amps,  
D.C. Volts, and D.C. Amps are calibrated only at the UPS modules.  
CAUTION  
Meter calibrations are factory set and should not require adjustment. Contact  
Liebert Global Services for meter calibration.  
WARNING  
DO NOT ATTEMPT TO CALIBRATE METERS WITHOUT ADEQUATE  
TRAINING. METER CALIBRATION REQUIRES SPECIAL TEST  
EQUIPMENT, ACCESS TO TEST POINTS IN SENSITIVE CIRCUITRY,  
AND EXPOSURE TO HAZARDOUS VOLTAGE.  
Figure 44 Meter Calibration Screen  
UP  
:
CURSOR UP  
SECURITY ACCESS  
DOWN : CURSOR DOWN  
SELECT : CHOOSE  
METER CALIBRATION  
D.C. VOLTS  
INPUT VOLTS  
PHASE A-B  
PHASE B-C  
PHASE C-A  
PHASE A  
D.C. AMPS  
INPUT VOLTS  
INPUT VOLTS  
INPUT AMPS  
INPUT AMPS  
INPUT AMPS  
PHASE A-B  
PHASE B-C  
PHASE C-A  
PHASE A  
OUTPUT VOLTS  
OUTPUT VOLTS  
OUTPUT VOLTS  
OUTPUT AMPS  
OUTPUT AMPS  
OUTPUT AMPS  
PHASE B  
PHASE C  
PHASE B  
PHASE C  
65  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.12 Battery Equalize Screen  
Go to the Master Menu and move the highlighted cursor to BATTERY EQUALIZE. Press the Select pad and  
the Battery Equalize screen is displayed.  
The Battery Equalize screen enables the operator to adjust the battery equalize time. It is also used to choose  
between auto and manual battery equalize recharging modes. Note that AUTO MODE can be selected only from  
the System Control Cabinet (SCC). Selections made at the SCC override previous selections made at the UPS  
modules.  
When the input utility power is interrupted, the battery supplies DC power to the UPS module inverters so there  
is no interruption of power to the critical load. When the AC input power is restored, the battery equalize  
recharging circuit can be activated automatically or manually to increase the module rectifier/charger output  
voltage to recharge the battery. The battery equalize circuit may also be manually activated at any time during  
normal float (constant) voltage operation. The equalizing time can be adjusted from 0 to 72 hours.  
Figure 45 Battery Equalize Screen  
UP  
DOWN :  
SELECT :  
:
CURSOR UP  
CURSOR DOWN  
CHOOSE  
SECURITY ACCESS  
BATTERY EQUALIZE RECHARGING  
EXIT  
EQUALIZE TIME PERIOD (hrs.) ...........  
STOP EQUALIZE CHARGE ...................  
MANUAL MODE .....................................  
AUTO MODE ..........................................  
MANUAL / RESET TO AUTO MODE ......  
0
NO  
NO  
YES  
NO  
CAUTION  
Do not use the Battery Equalize mode if you have valve-regulated, sealed-cell  
(maintenance-free) batteries. Refer to your battery manufacturer’s manual.  
EQUALIZE TIME PERIOD. This selection permits the operator to adjust the battery equalize time in one hour  
increments from 0 to 72. The battery equalize time must be greater than zero for the battery to begin recharging  
in both the AUTO and the MANUAL modes. This period is set by use of the Up/Down pads and Select pad.  
When the battery is at full voltage (not being recharged), this selection reads EQUALIZE TIME PERIOD  
(hrs). When the battery is recharging, this selection reads EQUALIZE TIME REMAINING (hrs). After the  
equalize recharge time has expired, the indication returns to the preset equalize time.  
STOP EQUALIZE CHARGE. This selection lets the operator halt the equalizing charge to the battery at any  
time, whether the circuit was activated automatically or manually.  
MANUAL MODE. This mode enables the operator to manually initiate a battery equalize charge to raise the DC  
bus voltage to correct a non-uniformity in the individual cell voltages or specific gravity readings.  
AUTO MODE (SCC only). When the battery recharge control logic is in the AUTO MODE, the UPS module  
battery chargers attempt the equalization process only if the EQUALIZE TIME PERIOD is greater than zero,  
the battery voltage has been at or below the Battery Discharging alarm limit for longer than 30 seconds, and the  
battery breakers (MBD) are closed.  
66  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.13 Alarm and Status Messages  
Module Status Messages  
The module status messages indicate how many UPS modules are included in the system and the present status  
of each module.  
The following status messages may appear in the module status area.  
1. MOD N. A module status message line is displayed for each UPS module in the system. Up to six (6)  
modules may be included in a multi-module system. The N in the message will indicate a specific UPS  
module number, 1 through 6.  
2. ON LINE. The UPS module output circuit breaker is closed and power from the module is available to the  
SCC. The module output is sharing the critical load if the UPS Output Breaker is closed.  
3. OFF-LINE. The UPS module output circuit breaker is open. More specific alarm messages are displayed at  
the UPS module.  
4. SUM ALM. The Module Summary Alarm has been activated by one of the alarm messages listed in two  
tablesSCC and Module Remote Monitor Indications and Other Alarms That Activate Summary  
Alarmsin 3.1.5 - System Configuration Screens. The specific alarm message is displayed at the UPS  
module.  
5. COM FAIL. The UPS module is not communicating with the SCC. This could mean loss of power to the  
UPS module controls, a disconnected cable, or a control logic failure (detected by watchdog timer. Call  
Liebert Global Services if you require assistance. To resume communication after control power is restored,  
sequence display to Master Menu.  
Figure 46 SCC Status and Alarm Message Areas  
LOAD  
BYPASS INPUT  
A-B  
0V  
B-C C-A  
627 KVA / 502 KW  
0V  
0V  
A
B
C
0 Hz  
755A 755A 755A  
UPS RATINGS  
SCCT 1600  
3 OF 3 MODULES  
CONNECTED  
REDUNDANT  
UPS INPUT PWR  
A-B  
0V  
B-C C-A  
0V 0V  
OUTPUT VOLTAGE  
Time To Overload  
Transfer: XXXX SEC  
A-B  
B-C C-A  
480V 480V 480V  
60.0 Hz  
MOD 1 ON LINE SUM ALM  
MOD 2 ON LINE SUM ALM  
MOD 3 ON LINE SUM ALM  
Byp Not Avail  
Static Sw Unable  
Module Sum Alm  
Not OK to Transfer  
Static Switch Connected  
MODULE STATUS  
MESSAGES  
SYSTEM STATUS  
MESSAGES  
LOAD BLOCK  
MESSAGES  
ALARM  
MESSAGES  
67  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Status Messages  
The system status messages indicate whether the static bypass switch is connected or disconnected, through the  
manually operated Static Switch Disconnects (see Figure 9). The status messages also advise the operator when  
a transfer or retransfer between the UPS system and bypass line is permitted, based on matching voltage, fre-  
quency, and phase.  
The following status messages may appear in the system status area.  
1. Static Switch Connected. The static switch is connected (the disconnect switches are closed—ON) and is  
ready provide a current path from the bypass input to the load.  
2. Static Switch Disconnected. The static switch is disconnected (the disconnect switches are open—OFF) for  
maintenance procedures.  
3. OK to Transfer. The UPS system voltage, frequency, and phase match the bypass line. This means that a  
transfer between the bypass line and the UPS system is permitted.  
4. Not OK to Transfer. Either the UPS or bypass voltage, frequency, or phase is not within the specified  
limits or the static bypass switch is not available. Therefore, manually initiated transfer between the bypass  
line and the UPS system is not permitted. Emergency or overload transfer to bypass may still be available  
provided the “static switch unable” alarm is not indicating.  
Load Block Messages  
Status messages in the Load block indicate how many modules are in the system, how many modules are ON  
LINE, and whether the system is operating in the redundant mode.  
The following status messages may appear in the load block.  
1. N OF X MODULES CONNECTED. The number N is the number of UPS modules ON LINE. This means  
the module output circuit breaker is closed. X is the number of UPS modules in the system (connected to this  
SCC). This number is set from the System Configuration screen.  
2. REDUNDANT. The capacity of the UPS modules ON LINE is sufficient to supply the critical load even if  
one module is taken OFF LINE. The critical load will remain on the UPS system if one module goes OFF  
LINE.  
3. NON-REDUNDANT. The critical load will be transferred to bypass if one module goes OFF LINE, and  
you must transfer the load to bypass in order to perform maintenance on any UPS module.  
4. TIME TO OVERLOAD TRANSFER. During an overload condition, the time remaining before transfer  
(in seconds) is displayed at the bottom of the load block. At each Module (MMU), the message is Time to  
Overload Shutdown.  
68  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm Messages  
The alarm message area displays the alarm conditions that are present within the UPS system. Alarm messages  
are displayed in flashing reverse video. During normal operation no alarm messages should be present. Up to  
four messages are displayed. To see if any additional alarm conditions are present in the UPS system, display the  
Present Status screen on the control panel.  
Table 1 is a complete list of all alarm messages and corrective actions, if any.  
The first column lists the alarm message, with related alarms grouped together.  
The third column indicates which special functions (if any) are initiated by the alarm.  
D - the alarm initiates an auto-dial call through a user-provided modem to a remote terminal.  
E - message displayed only on Status Report screens including Event History.  
F - the alarm freezes the History Status Report memory buffer in the cabinet where the alarm is displayed.  
Pressing the Alarm Reset pad for 15 seconds will unfreeze the memory buffer.  
L - the alarm latches the displayed alarm message. Some alarm conditions are temporary (transient) and  
may not last long enough to be noticed. Latching the display (keeping it on) lets you know that an alarm con-  
dition has occurred. A latching display alarm remains on the display screen until the alarm condition is  
removed and the Alarm Reset pad is pressed.  
R - the alarm is displayed on an (optional) Remote Monitor Panel. This information is also available for  
customer use through a set of contacts on a separate terminal board.  
S - the alarm initiates a summary alarm at the Remote Monitor Panel and at the SCC.  
The fourth column provides an explanation of the alarm condition, the critical bus status, and the corrective  
actions, if any, to remedy the alarm.  
Abbreviations Used in Alarm Messages  
Auto  
Automatic  
Available  
Battery  
Avail  
Batt  
Byp  
Bypass  
Cap Fuse  
Capacitor Fuse  
Cont Power Control Power  
Equip  
Equipment  
H/W  
Hardware  
Inv Fuse  
OF/UF  
Ov-temp  
O-volt  
Inverter Fuse  
Over/Under Frequency  
Over-Temperature  
Over-Voltage  
Over-Voltage  
Phase Sequence  
Rectifier Fuse  
Retransfer  
O-volts  
Ph Seq  
Rect Fuse  
Rexfer  
Shutdn  
Static Sw  
Un-volts  
Xfer  
Shutdown  
Static Switch  
Under-Voltage  
Transfer  
69  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1  
Alarm  
Message  
AC INPUT  
Alarm Messages - Meaning and Corrective Action  
Cabinet  
Special  
Functions  
Meaning and  
Corrective Action in Brackets [ ]  
Location  
Input Fail  
MMU  
The rectifier input line voltage is outside of specified limits or the  
input circuit breaker is opened while the battery circuit breaker  
remains closed. The battery supplies power to the critical load  
through the UPS inverter.  
DC BUS  
DC Ground Fault  
MMU  
MMU  
MMU  
L, S  
D, F, S  
R, S  
Either the positive (+) or negative (-) DC bus is grounded. No transfer  
or shutdown occurs.  
[Contact Liebert Global Services at once. Do not attempt to locate or  
repair the fault.]  
DC Capacitor  
Fuse Blown  
At least one DC capacitor fuse has opened. The UPS module is  
taken off-line and the input and battery circuit breakers trip open.  
[Contact Liebert Global Services at once. Do not attempt to reset the  
circuit breakers.]  
Battery CB Open  
The module battery circuit breaker (MBD) is open. This circuit  
breaker can be opened either manually or automatically in a UPS  
shutdown procedure. If the UPS is operating with this breaker open,  
the critical load is not protected from loss of the utility source  
power.  
[After AC power is restored and the DC bus is at 100% operating  
voltage, manually close the battery circuit breaker so the rectifier can  
charge the battery.]  
Battery  
Discharging  
MMU  
R, S  
The battery is discharging. This occurs whenever the battery  
supplies power to the load for more than 5 seconds because of input  
power failure, a rectifier problem, or an overload condition. If the  
input power or a source of auxiliary power is restored to the UPS  
module, the UPS automatically returns to normal operation.  
[Watch the battery voltage carefully. Reduce the load (begin  
controlled shutdown) to extend the battery back-up time. Reset the  
UPS alarms after the input power is restored. The message clears  
after 30 seconds.]  
Low Battery  
Warning  
MMU  
MMU  
R, S  
The battery voltage is approaching the minimum discharge voltage  
(approximately 5 minutes remaining).  
[Complete the controlled shutdown of the critical load. Reset the  
alarms if the input power is restored before shutdown.]  
Low Battery  
Shutdown  
D, F, L, S  
The battery voltage has decreased to the minimum discharge value.  
The UPS module is taken off-line (no power to the critical load)  
and the battery and input circuit breakers trip open.  
[Perform a UPS system start-up procedure when AC power  
becomes available.]  
DC Over-Voltage  
Shutdown  
MMU  
SCC  
D, F, L, S  
The maximum preset value of the DC Bus voltage has been  
exceeded. The UPS module is taken off-line and the input and  
battery circuit breakers trip open.  
[Contact Liebert Global Services at once. A fault may have occurred  
within the UPS. Do not attempt to reset the circuit breaker.]  
BYPASS  
Load On Bypass  
D, E, F  
The critical load is being supplied power from the bypass line, and is  
therefore exposed to utility power disturbances.  
[Clear all of the alarms before attempting to retransfer the load from  
the bypass line to the UPS.]  
Table 1 Abbreviations  
D = auto-dial;  
E = reports only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
70  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1  
Alarm Messages - Meaning and Corrective Action (continued)  
Alarm  
Message  
Cabinet  
Location  
Special  
Functions  
Meaning and  
Corrective Action in Brackets [ ]  
BYPASS (Contʼd.)  
Auto Transfer to  
Bypass  
SCC  
D, E, F  
The critical load has been automatically transferred to the bypass  
line.  
[Use the History Status screen to determine the cause for the  
transfer. Clear all of the alarms before attempting to retransfer the  
load from bypass to UPS.]  
Auto Retransfer  
Primed  
SCC  
SCC  
An automatic retransfer will be initiated when the OK to Transfer  
condition has been present for 10 seconds, if the overload has  
dropped below 100% of the rated SCC current and if enough UPS  
modules are on-line.  
Manual Reset/  
Retransfer  
A manual retransfer is required. Either a system overload condition  
has lasted more than 5 minutes, or no more auto-retransfer attempts  
are available. Note that this alarm is only used if auto-retransfer  
attempts are enabled.  
[Perform a manual retransfer if all necessary conditions are present.]  
Static Switch  
Unable  
SCC  
S
The UPS output is not synchronized to the bypass power source.  
The static bypass switch is disconnected, or it has failed internally.  
[Emergency and overload transfer to the bypass source is not  
available. Manually set the Static Switch Disconnects to ON (closed)  
if the static switch is disconnected. If the alarm conditions are  
automatically corrected, reset the alarm to clear it. Contact Liebert  
Global Services if the alarm stays on.]  
Bypass Not  
Available  
SCC  
SCC  
The bypass power source voltage is not within specifications.  
[Check the bypass power source.]  
Bypass Phase  
Sequence Wrong  
The power conductors on the bypass line are not wired to the UPS in  
the required sequence. This alarm should appear only during initial  
start-up or after a repair to the source power system.  
[Disconnect power from the bypass line and correct the wiring. A  
Liebert Global Services representative must be present during initial  
start-up of your UPS System.]  
UPS SYSTEM  
Input Current  
Unbalanced  
MMU  
E
At least one input phase differs from the average current by 10% or  
more for four (4) hours. Contact Liebert Global Services. If the  
condition persists, transfer the load to the bypass line.  
Control Power  
Fail  
SCC  
MMU  
L, S  
L, R, S  
The logic control power supply from the UPS output is not operating  
properly. The UPS module continues operating but will shut down if  
the input power fails. The SCC continues operating but will shut  
down if the bypass power fails. Contact Liebert Global Services  
immediately.  
Output Over/  
Under Frequency  
SCC  
SCC  
L, S  
Output frequency differs from the nominal (60 Hz) by more than 0.5  
Hz. No transfer or shutdown occurs.  
[Contact Liebert Global Services at once.]  
Output Under-  
Voltage  
D, F, L, S  
The UPS system output voltage is under the minimum (-12%)  
deviation from nominal. The load automatically transfers to the  
bypass line.  
[If the alarm condition is no longer present, reset the alarm and  
retransfer the load from bypass to UPS. Contact Liebert Global  
Services if alarm persists.]  
Output Over-  
Voltage  
SCC  
D, F, L, S  
The UPS system output voltage is above the maximum (+10%)  
deviation from nominal. The load automatically transfers to the  
bypass line. All UPS modules are taken off-line and are shut down.  
[Contact Liebert Global Services at once. Do not attempt to reset  
circuit breakers.]  
Table 1 Abbreviations  
D = auto-dial;  
E = reports only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
71  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1  
Alarm  
Message  
Alarm Messages - Meaning and Corrective Action (continued)  
Cabinet  
Special  
Functions  
Meaning and  
Corrective Action in Brackets [ ]  
Location  
UPS SYSTEM (Contʼd.)  
Overload  
SCC  
MMU  
R, S  
S
The UPS output current exceeds the rated system load current. This  
condition causes an alarm only, the UPS does not shut down.  
[Determine cause of the overload. Reduce the load until the overload  
condition is corrected. Reset the UPS alarm.]  
Overload Transfer  
SCC  
SCC  
D, F, L, S  
The load on the UPS has exceeded the current versus time window  
of system overload capacity. The UPS system transfers the load to  
bypass.  
[Reduce the load. If the system does not initiate an automatic load  
retransfer, manually retransfer the critical load from the bypass line  
to the UPS. Reset the alarm.]  
Module Summary  
Alarm  
S
An alarm message (see lists in SCC and Module Remote Monitor  
Indications and Other Alarms That Activate Summary Alarms in  
3.1.5 - System Configuration Screens) or the watchdog timer has  
activated the Module Summary Alarm.  
R (MMU)  
[Clear alarm conditions, if possible.]  
Module N Off Line  
SCC  
D
The output circuit breaker of Module N is open. The number N will  
identify the module (1 through 6).  
R (MMU)  
[Review active alarms at Module N and clear alarm conditions, if  
possible.]  
Inverter  
Nonsynchronized  
MMU  
Inverter output is not synchronized with the UPS system critical bus.  
This also means the output circuit breaker is open and should not be  
closed until the output is in sync. This condition may correct itself. If  
not, shut down the UPS module and then perform a start-up  
procedure.  
[Contact Liebert Global Services if condition persists.]  
Overload  
MMU  
MMU  
D, F, L, S  
D, F, L, S  
The UPS output current has exceeded 175% of the rated full load or  
the overload capacity has been exceeded. The UPS module is taken  
off-line and shut down.  
[Contact Liebert Global Services at once. Do not attempt to reset  
circuit breakers.]  
Shutdown  
Reverse Power  
Inverter Fault  
Excessive reverse power flow from the critical bus into the UPS  
inverter has occurred, probably because of low inverter output  
voltage or a phase mismatch. The UPS module is taken off-line and  
is shut down.  
[Contact Liebert Global Services immediately. Do not attempt to  
reset circuit breakers.]  
MMU  
D, F, S  
At least one of the fuses has opened or an inverter fault was  
detected. The UPS module is taken off-line and is shut down.  
[Contact Liebert Global Services immediately. Do not attempt to  
reset the circuit breakers.]  
Communication  
Failure  
SCC  
S
The COM FAIL status message is as important as an alarm  
message. Refer to 3.1.13 - Alarm and Status Messages.  
Battery Cycle  
Buffer Warning  
D, E  
The optional Battery Cycle Monitor can retain information about the  
last 132 battery discharge events. When the storage buffer  
approaches its capacity, this warning message is broadcast via  
terminal and modem communication channels, and a complete  
listing of all records is sent to the terminal port. The message clears  
after 30 seconds.  
Table 1 Abbreviations  
D = auto-dial;  
E = reports only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
72  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1  
Alarm  
Message  
Alarm Messages - Meaning and Corrective Action (continued)  
Cabinet  
Special  
Functions  
Meaning and  
Corrective Action in Brackets [ ]  
Location  
UPS SYSTEM (Contʼd.)  
Hardware  
Shutdown  
MMU  
D#  
At least one of the following alarm conditions is present: Inverter  
Fault, Rectifier Fuse Blown, Reverse Power, Overload Shutdown,  
logic power supply failure, or inverter output symmetry failure. The  
UPS module is taken off-line and is shut down.  
[Contact Liebert Global Services at once. Do not attempt to reset the  
circuit breakers.]  
Emergency Off  
SCC  
MMU  
D*, L, S  
The Emergency Module Off (or Emergency Power Off) switch has  
been pressed, which caused the UPS system to shut down and  
transfer the load to the bypass line (or all power to the critical load  
has been shutdown).  
[Determine the cause of the emergency condition and correct it if  
possible. Contact Liebert Global Services if you require assistance.]  
COOLING  
Ambient Over-  
Temperature  
MMU  
MMU  
R, S  
S
The intake air to the UPS module exceeds the specified maximum  
temperature.  
[This condition only causes an alarm, but should be corrected  
immediately to prevent damage to equipment due to overheating.]  
Blower Failed  
A fault in one or more of the blower motors has occurred. This  
condition only causes an alarm, but if not promptly corrected it could  
cause an equipment over-temperature condition that would shut  
down the UPS module.  
[Check the blowers for proper operation. Contact Liebert Global  
Services if you require assistance.]  
Equipment Over-  
Temperature  
MMU  
MMU  
S
Sensors on power semiconductor heatsinks detect temperatures  
above the steady state limits for these components. The control logic  
sets off the alarm but does not shut down the UPS module if the  
condition lasts less than 10 minutes.  
[Check the air intake, air exhaust, and filters. Reduce the load or  
transfer it to bypass. Contact Liebert Global Services if the alarm  
persists.]  
Over-Temperature  
Timeout  
D, F  
An Equipment Over-Temperature condition has persisted for more  
than 10 minutes. The UPS module is taken off-line and is shut down.  
[Check the air intake, air exhaust, and filters before attempting to  
start-up the UPS.]  
REMOTE MONITOR PANELS  
(Refer also to SCC and Module Remote Monitor Indications and Other Alarms That Activate Summary Alarms in  
3.1.5 - System Configuration Screens)  
Load On UPS  
New Alarm  
R (SCC)  
The UPS is operating properly. No corrective action is necessary.  
R (SCC)  
R (MMU)  
Another new alarm message has been registered on the UPS  
system.  
[Clear the new alarm condition, if possible.]  
System Summary  
Alarm  
R (SCC)  
One or more of the UPS system alarm messages has been activated  
or a control logic failure has been detected by a watchdog timer.  
[Use the Present Status screen to determine which alarms are  
active. Clear the new alarm condition if possible to do so.]  
Module Summary  
Alarm  
R (MMU)  
One or more of the UPS module alarm messages has been  
activated.  
[Use the Present Status screen to determine which alarms are  
active. Clear the new alarm condition, if possible to do so.]  
Table 1 Abbreviations  
D = auto-dial;  
E = reports only;  
F = freezes;  
L = latches  
R = remote  
S = summary  
D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs  
D# = auto-dial initiated through Module N (1-6) off-line  
73  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2  
Alarm Messages - Summary  
Alarm Message  
MMU  
X
SCC  
R
Special Functions  
Input Fail  
DC Ground Fault  
X
L, S  
DC Capacitor Fuse Blown  
Battery CB Open  
X
D, F, S  
X, R  
X, R  
X, R  
X
S
Battery Discharging  
Low Battery Warning  
Low Battery Shutdown  
DC Over-Voltage Shutdown  
Load On Bypass  
S
R
S
X, R  
E
D, F, L, S  
X
D, F, L, S  
E
Auto Transfer to Bypass  
Auto Retransfer Primed  
Manual Reset/Retransfer  
Static Switch Unable  
Bypass Not Available  
Bypass Phase Sequence Wrong  
Input Current Unbalanced  
Control Power Fail  
D, F  
X
X
X
S
X
X
X
X, R  
X
L, S  
Output Over/Under Frequency  
Output Under-Voltage  
Output Over-Voltage  
Overload  
X
L, S  
X
D, F, L, S  
X
D, F, L, S  
X, R  
X
S
Overload Transfer  
X
D, F, L, S  
Inverter Non-Synchronized  
Module N (1-6) Off Line  
Overload Shutdown  
Reverse Power  
X
R
D
X
X
D, F, L, S  
X
D, F, L, S  
Rectifier Fuse Blown  
Inverter Fault  
X
D, F, S  
X
D, F, S  
Hardware Shutdown  
Emergency Off  
X
D#  
X
D*, F, S  
Ambient Over-Temperature  
Blower Failed  
X, R  
X
R
S
S
R
Equipment Over-Temperature  
Over-Temperature Timeout  
Load On UPS  
X
S
X
D, F  
S
R
New Alarm  
R
Module Summary Alarm  
System Summary Alarm  
R
X
R
D = Auto-Dial initiated  
D* = Auto-Dial initiated through Auto Transfer  
to Bypass if load is on UPS  
D# = Auto-Dial initiated through Module N (1-6)  
off-line  
E = message displayed on Status Report screens  
F = freezes the History Status Report memory buffer  
L = latches the displayed alarm message  
R = Remote Alarm Contact (optional on MMU)  
S = Summary Alarm (System or Module) initiated  
X = message displayed on Monitor/Mimic screen  
and audible alarm  
74  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.14 Communication Interfaces  
Your Liebert Series 600T UPS includes the following communication ports:  
• Worldwide reporting to a remote terminal through a modem  
• Reporting to a local terminal (no modem required)  
• Reporting to a local monitor only  
• Site reporting to Liebert SiteScan Central Monitoring System  
• Reporting via SNMP interface to a building management or network management system  
• Selected alarm messages to a Liebert Remote Monitor Panel and to contact closures for customer use  
All external communication devices, including the modem, are optional equipment. Connections to communica-  
tion ports are made by wiring cables to terminal boards at the SCC. Connection points are shown on the Control  
Wiring Interconnect Diagram. Contact Liebert Global Services for assistance when attaching an external device  
to your UPS system.  
Any terminal that accepts the standard 7-bit ASCII codes and conforms to the data link requirements can be used  
to interface with the Series 600T UPS. If a printer is used, the terminal must support it. The UPS does not send or  
receive any printer control commands.  
Data link requirements are:  
• Asynchronous RS-232 communication  
• Terminals may be configured as DTE or DCE  
• Baud Rate:  
Modem: 1200 or 2400  
Terminal: 2400 only  
• Data Bits: 7  
• Stop Bits: 1  
• Parity: Odd  
• Handshaking: Not required  
• Full Duplex  
Worldwide Reporting  
This port transmits UPS system status and history information to a remote terminal in RS-232 format through a  
PC-compatible modem.  
Auto-Dial  
The Series 600T UPS communication program will automatically dial a pre-programmed (customer selected)  
phone number when specified alarm conditions occur. The auto-dial phone number, an alternate number, and the  
modem baud rate are programmed by using the SCC System Configuration screen. The alarm messages that ini-  
tiate an auto-dial call are identified in Table 1.  
When the auto-dial function is initiated, automatic dial attempts to the first phone number are made at periodic  
intervals for 30 minutes. If unanswered, the system rolls over to the second number and repeats calling until con-  
nection is made or returns to first phone number after 30 minutes.  
Once a connection is made to a terminal, the system transmits the information on the Present Status Report  
screen, then hangs up. The Present Status Report includes the UPS system identification number, date, time,  
alarm messages and metered parameter indications.  
Requesting Information  
If your Series 600T is equipped with a modem and telephone line, you can call the UPS and receive system status  
and historical information on discharge events. You can place the call from either a remote terminal or a personal  
computer with a communications program.  
Follow the instructions for your terminal or your communications program to call the UPS. When you make con-  
nection, the UPS will send you the greeting: “Hello, you are connected to a Series 600.” At this point, the UPS  
will respond to your specific requests for information, according to Table 3.  
For example, to see a copy of information on the Present Status Report screen from the SCC (see Present Status  
in this manual), press the A key (either upper or lower case can be used for all except the date and time com-  
75  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
mands) and then the Enter key. The Series 600T will send the data, which will be displayed on your screen. To  
see the Present Status Report screen from, say, Module 1, type A1 and press the Enter key. Please note that the  
data on the screen is like a snapshot—the status of the UPS at the moment you requested the information. The  
information sent remotely is not updated, although you can repeat the process at intervals to request the present  
information.  
Some screens, like the Battery Cycle Monitor information, contain data that you may wish to import into a  
spreadsheet for further calculations. To put this data into a usable format, use the screen-capture feature of your  
communications software (or a separate screen-capture program) to save all or part of the data to disk. Hint: If  
you save the file with an extension of “.txt,” it can then be imported into a spreadsheet program and converted to  
worksheet format.  
To terminate your connection to the Series 600T, press the H key and then the Enter key. The UPS will hang up  
its modem and await your next call.  
Local Reporting to a Terminal  
This port sends UPS system status and history information to a local terminal in RS-232 format. No modem is  
required. The Present Status Report screen is sent to the local terminal whenever a new alarm occurs. Commands  
for requesting information, and for changing the date and time, are in Table 2.  
Local Reporting to a Monitor  
A monitor connected to this port will display the same alarm information being sent to the local terminal. This  
monitor does not display information going out through the modem port.  
Site Reporting: SiteScan or SNMP  
The SiteScan port sends UPS system information to a Liebert SiteScan Central Monitoring System. UPS opera-  
tion, environmental control systems, and facility security can all be monitored from a single location. This infor-  
mation can also be sent via SNMP interface to a local network or building management system.  
If your site has SNMP communications, the optional Liebert SiteNet Integrator allows you to monitor the status  
of all the dry-contact outputs of the Series 600T. The Integrator module monitors up to ten digital inputs and two  
temperature/humidity sensors, and can control two external devices with contact closure outputs. It can be pro-  
grammed to activate local audible and visual alarms in addition to network “traps.”  
Remote Monitor Panel  
The Liebert Remote Monitor Panel provides an LED indication of the following conditions:  
Load On UPS  
Load On Bypass  
Battery Discharge  
Low Battery Warning  
Overload  
Ambient Overtemp  
System Summary Alarm  
New Alarm  
This information is also available for customer use through a set of contacts on a separate terminal board.  
Alarm messages that activate the System Summary Alarm are listed in two tablesSCC and Module Remote  
Monitor Indications and Other Alarms That Activate Summary Alarmsin 3.1.5 - System Configuration  
Screens.  
The Remote Monitor Panel housing is a NEMA Type 1 enclosure, available for either surface-mount or flush-  
mount installations.  
76  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Separate / Simultaneous Outputs  
The RS-232 interface can support a modem plus either a local terminal or a local monitor. Likewise, the SiteScan  
port can support either SiteScan or SNMP communications. Whatever interfaces you use will all operate simulta-  
neously.  
Table 3  
Series 600T Terminal Commands  
Key(s)  
Function  
A, return  
AN (N=1 to 6), return  
Displays Present Status Report screen. NOTE: For all three report screens, a  
number 1 through six in place of N will access an individual UPS module. If no  
number is entered, you will get a report from the SCC.  
^B (control-B), return  
^BN (N=1 to 6) return  
Displays Event History Report screen, starting with the most recent frame and then  
scrolling back through earlier frames.  
C, return  
Displays History Status Report screen starting with the most recent frame and then  
^CN (N=1 to 6), return scrolling back through the earlier frames.  
F (no return)  
Freezes data output. This stops the data scrolling on the monitor to allow closer  
study or a printout. This is a toggle switch command. Press the F key again to  
resume data scrolling.  
G, return  
Resets (unfreezes and clears) the History Status Report memory buffer. This erases  
the alarm messages and meter indications that were stored immediately before and  
after a significant system fault. NOTE: Do not reset the History Status Report  
memory buffer until operation and maintenance personnel have reviewed it as a  
troubleshooting tool.  
Q (no return)  
The data output stops (quits). The UPS communication system remains on stand-  
by, ready to receive the next communication command. NOTE: To return to the  
beginning of the Event History or History Status Report, press Q, then request your  
desired report again.  
d mm/dd/yy, return  
t hh:mm:ss, return  
H, Return  
This entry sets the date (month/day/year) in the UPS system clock. You must  
include the slash (/) as you key in the date. Note that the d command must be lower  
case.  
This entry sets the time (hour:minute:second) in the UPS system clock. You must  
include the colon (:) as you key in the time. Note that the t command must be lower  
case.  
Prompts the UPS system to hang up its modem (only applicable to the modem  
communications port).  
I, Return  
J, Return  
K, Return  
L, Return  
M, Return  
N, Return  
Display Battery Cycle Monitor information for 0-30 second discharge events.  
Display Battery Cycle Monitor information for 31-90 second discharge events.  
Display Battery Cycle Monitor information for 91-240 second discharge events.  
Display Battery Cycle Monitor information for over 240 second discharge events.  
Display Status Summary screen of battery discharge events.  
Show detail information on all battery discharge events in order of occurrence  
(Last-In, First-Out).  
backspace  
Moves cursor left to cancel previous entry or command.  
77  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2  
Modes of Operation  
This section illustrates the flow of power through circuit breakers, switches, and UPS components during various  
modes of operation. An SCCB with three modules is shown. The same modes of operation apply to all configu-  
rations of the Liebert Series 600T UPS multi-module system. Highlighted (thick) lines in the diagrams indicate  
power flow and power availability.  
These illustrations show a three-breaker maintenance bypass because it is most commonly used. Your installa-  
tion may have a two-breaker, three-breaker, or four-breaker maintenance bypass, or none at all.  
These illustrations do not show an alternate power source (generator) and automatic transfer switch (external to  
the UPS) that might be present at your installation.  
The following circuit breaker abbreviations are used:  
BFB  
BIB  
Bypass Feeder Breaker  
Bypass Input Breaker  
CB1  
CB2  
MBB  
MBD  
MIB  
RIB  
Module Input Breaker  
Module Output Breaker  
Maintenance Bypass Breaker  
Module Battery Disconnect  
Maintenance Isolation Breaker  
Rectifier Input Breaker  
SBB  
System Bypass Breaker  
3.2.1 Load On Bypass  
Load on Bypass, with the UPS not available, is shown in Figure 47. The UPS system could be in this mode of  
operation during either initial start-up or UPS system shutdown and isolation for maintenance.  
Figure 47 Load on Bypass (UPS Not Available)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
78  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.2 OK To Transfer  
The OK to Transfer status message will be displayed when the bypass line and UPS system output power are  
both available, their voltage, frequency, and phase synchronization are matched within specifications, and the  
Static Switch Disconnects are closed (ON). An alarm message may be displayed to indicate Load On Bypass. If  
no alarm is displayed, the operating status is Load On UPS.  
When the OK to Transfer message is displayed, you can perform a manual transfer of the load from the UPS sys-  
tem to bypass, or a manual retransfer of the load from bypass to the UPS system.  
Use the Load Transfer Procedures screen at the SCC when performing a manual transfer. Refer to 3.3.2 - Load  
Transfer Procedures.  
The UPS system control logic at the SCC will initiate an automatic transfer to bypass if an overload condition  
exceeds the system current versus time window, or if a UPS module is taken off line while the system is operat-  
ing in the non-redundant mode. An automatic retransfer to the UPS system may be initiated when recovering  
from system overloads lasting less than five minutes. Refer to 3.4 - Automatic Operations.  
NOTE  
When the critical load is being supplied power from the bypass line, it is exposed to  
utility power disturbances.  
Figure 48 Load on Bypass (UPS Available)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
79  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 49 Load on UPS (Bypass Available)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
80  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.3 Momentary Overloads  
An overload in the critical load will continue to be supplied by the UPS system if the overload condition does not  
exceed the current versus time curve of overload capacity for either the SCC rating or for the number of modules  
on-line.  
For momentary overloads exceeding 155% of rated system (SCC) current, the static switch turns on for 40 milli-  
seconds to provide current from the bypass line in parallel with current from the UPS system output. Up to  
1000% of rated current can be supplied for less than one cycle, while up to 500% of rated load can be sustained  
for the full 40 milliseconds of pulsed-parallel operation. By providing two power sources simultaneously, high  
current can be supplied to the critical load with full output voltage regulation. The critical load can be supported  
through inrush currents and momentary faults without operating the motorized circuit breakers.  
If an overload situation exceeds 40 milliseconds, the UPS system continues to supply power to the critical load if  
it remains within the current versus time curve of overload capacity. If the system overload capacity is exceeded,  
the UPS control logic at the SCC initiates an automatic transfer to the bypass line by operating the static bypass  
switch and the motorized system circuit breakers (SBB and UPS Output).  
Refer to 3.4 - Automatic Operations.  
Figure 50 Momentary Overload (Pulsed Static Bypass Switch)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
81  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.4 Input Power Failure (Load On Battery)  
If the utility AC power source fails, or is outside the acceptable range, the battery plant becomes the power  
source for the UPS module inverters. The UPS system continues to supply power to the critical load, and also to  
the controls of the UPS modules and the SCC.  
You can use the Battery Time screen at the UPS modules to monitor the present battery voltage compared to the  
shutdown value. The length of time the battery can sustain the load depends on the size of the load and the size  
and condition of the battery plant. The battery plant is usually large enough to supply a 100% rated load for 15  
minutes.  
Alarm messages that indicate battery status are Battery Discharge, Low Battery, and Battery Shutdown. The  
voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings screen. These limits were  
selected for your installation by Liebert Global Services during initial start-up.  
The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the current in  
Amperes. Maximum battery discharge current ranges from 324 amps (for 150 kVA) to 1620 amps (for 750  
kVA). Refer to the separate Installation Manual or drawings for specific data on your system.  
Figure 51 Input Power Fail (Load on Battery)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
82  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.5 One Module Off-Line  
A multi-module UPS system can be supplied with a back-up (redundant) UPS module, which is the typical con-  
figuration. A redundant system includes one more module than the number required to supply the critical load. A  
redundant system operates in the redundant mode if all modules are ON LINE. Note that the UPS system can  
also operate in the redundant mode with one module OFF LINE if the critical load is reduced so that not all ON  
LINE modules are required. The UPS modules share the load, and the critical load will remain on the UPS sys-  
tem if any one of the modules is disconnected (goes OFF LINE) for maintenance or because of an internal fault.  
The system control logic monitors the connected critical load and the number of UPS modules ON LINE. If the  
UPS system is operating in the redundant mode, the REDUNDANT status message will be displayed at the Sys-  
tem Control Cabinet (SCC). If the UPS system is operating in the non-redundant mode (redundant module is  
OFF LINE or was not included in the system configuration), the NON-REDUNDANT status message is dis-  
played at the SCC. In the Non-Redundant mode, the critical load will be transferred to bypass if any UPS module  
goes OFF LINE, and you must transfer the load to bypass in order to perform maintenance on any UPS module.  
Figure 52 One Module Off-Line (Load on UPS)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
83  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.6 Off Battery  
The battery plant can be disconnected from the UPS modules, if required for battery maintenance, by opening the  
module battery disconnect (MBD) circuit breaker(s). In this situation the UPS system will continue to supply  
conditioned power to the critical load, but if input power fails, the UPS system cannot supply power to the load.  
CAUTION  
When the UPS system is operating with the module battery disconnect (MBD)  
circuit breaker(s) open, the critical load is not protected from loss of the utility  
source power.  
Figure 53 Load on UPS (Battery Not Available)  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
84  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.7 Emergency Modules Off  
The Local Emergency Modules Off (LEMO) mode is used to remove power from all UPS system components,  
and the critical load will continue to be supplied through the bypass line.  
The Emergency Module Off control is a guarded pad on the SCC Control Panel (see Figure 10).  
Lift the cover and press the pad. The load will be transferred to bypass, and the battery (MBD), input, and output  
circuit breakers will be opened (tripped). This will remove power from all UPS system components except the  
controls, system bypass circuit breaker, and the static switch.  
Refer to 3.3.3 - Shutdown Procedures.  
Figure 54 Emergency Modules Off  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
85  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.8 Emergency Power Off  
The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.  
The Remote Emergency Power Off control is a switch located remotely from the UPS system. It will normally be  
in the same room as the critical load equipment. This mode can also be initiated by an automatic contact closure  
in the same external circuit as the manually operated switch.  
When you operate the Emergency Power Off switch, all UPS circuit breakers are opened including the bypass  
circuit breaker. All power through the UPS is removed from the load. Typically, the REPO circuit also opens the  
circuit breakers that provide power to the bypass lines and the UPS controls.  
Refer to 3.3.3 - Shutdown Procedures.  
Figure 55 Emergency Power Off  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
86  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.9 System Shutdown  
Perform a System Shutdown procedure when you must disconnect the UPS system components from all power  
sources when required for maintenance procedures.  
Use the Shutdown Procedures screen when performing a manual System Shutdown.  
Refer to 3.3.3 - Shutdown Procedures.  
Refer to 3.2.10 - Maintenance Bypass.  
Before performing any maintenance on your Liebert Series 600T UPS System, observe ALL of the WARN-  
INGS in 4.0 - Maintenance.  
WARNING  
LETHAL VOLTAGES ARE PRESENT WITHIN THIS SYSTEM EVEN  
WHEN IT IS NOT ON OR WHEN POWER IS NOT BEING SUPPLIED.  
OBSERVE ALL CAUTIONS AND WARNINGS IN THIS MANUAL.  
FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY OR DEATH.  
DO NOT WORK ON OR OPERATE THIS EQUIPMENT UNLESS YOU ARE  
FULLY QUALIFIED TO DO SO!! NEVER WORK ALONE.  
Figure 56 System Shutdown  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
87  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2.10 Maintenance Bypass  
Maintenance Bypass switchgear (cabinet, panelboard, switchboard or custom switchgear) allows you to totally  
isolate the UPS system from all power sources, while you maintain power to the critical load.  
Your installation may have a two-breaker, three-breaker, or four-breaker Maintenance Bypass, or none at all.  
The main differences are the locations of the Rectifier Input Breaker and the Bypass Input Breaker (BIB).  
Another option that may be present at your site is an alternate power source (generator) and an automatic transfer  
switch (ATS).  
Note that to totally isolate the UPS system from all power sources, the Main Input switchgear and battery circuit  
breakers must also be opened.  
CAUTION  
Instructions for operating the Maintenance Bypass circuit breakers are on the  
Maintenance Bypass cabinet. Make sure you understand the proper sequence  
before operating any circuit breaker. Operating a Maintenance Bypass circuit  
breaker out of sequence could cut off power to the critical load.  
Figure 57 Load on Maintenance Bypass (Two Breakers)  
RIB  
RIB  
RIB  
BIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
R
I
R
I
R
I
SBB  
MBB  
System  
SKRU  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
Battery  
Battery  
Battery  
(can accommodate up to 6 UPS modules)  
88  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 58 Load on Maintenance Bypass (Three Breakers)  
STANDBY GENERATOR  
AUTOMATIC  
TRANSFER SWITCH  
RIB  
RIB  
RIB  
BFB  
UPS #3  
CB1  
UPS #2  
CB1  
UPS #1  
CB1  
SBS  
BIB  
R
I
R
I
R
I
SBB  
MBB  
SKRU  
System  
CB2  
CB2  
CB2  
Controls  
Output  
MIB  
SCCT  
To Critical Load  
MBD  
MBD  
MBD  
SCCT  
(can accommodate up to 6 UPS modules)  
Battery  
Battery  
Battery  
89  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3  
Manual Procedures  
The Liebert Series 600T UPS system is designed to function while unattended by an operator. The system con-  
trol logic at the System Control Cabinet (SCC) monitors the performance of the UPS system, the availability of  
power sources, and the current required by the critical load.  
The system control logic at the SCC:  
1. Determines what overload conditions can be sustained without a transfer to bypass.  
2. Initiates an automatic transfer to bypass to sustain an overload.  
3. Can initiate an automatic retransfer to the UPS after a system overload has been cleared.  
4. Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS fault  
occurs.  
The control logic at each UPS module:  
1. Determines what overload conditions can be sustained by the module while it is on-line.  
2. Automatically takes the UPS module off line and initiates an emergency module shutdown when selected  
UPS faults occur.  
Refer to 3.4 - Automatic Operations for more details.  
Manual procedures available to the operator include Start-Up, Load Transfers, and Shutdowns. These procedures  
are performed by using the operator control panel and some manually operated circuit breakers and switches.  
The LCD display at each UPS cabinet includes a screen to help you with each manual procedure by listing each  
step you must perform.  
This section lists step-by-step controls to operate and conditions to observe in the following manual procedures:  
1. Start-Up: including initial start-up, recovering from input power failure, recovering from battery shutdown,  
and recovering from shutdowns for emergencies or maintenance procedures  
2. Load Transfers: including transfers from UPS system to bypass, and retransfers from bypass to the UPS  
system.  
3. Shutdowns: including module shutdowns for maintenance procedures and emergency shutdowns.  
90  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3.1 Start-Up Procedure  
SCC Start-Up  
When the UPS system has been shut down, for any reason, use this procedure to start-up the UPS system to pro-  
vide filtered, reliable  
power to the critical load. This procedure gives step-by-step instructions for controls to operate and conditions to  
observe. Your present situation could be initial start-up or recovering from input power failure, battery shut-  
down, maintenance shutdown, or an emergency shutdown.  
NOTE  
The following procedure assumes that the UPS installation inspection and initial  
start-up have been performed by Liebert Customer Service. A Liebert authorized  
representative must perform the initial system start-up to ensure proper system  
operation.  
CAUTION  
The following procedure provides power to the critical load distribution system.  
Verify that the critical load distribution is ready to accept power. Make sure that  
personnel and equipment are ready for the critical load distribution system to be  
energized.  
If your installation includes a Maintenance Bypass, you may already be supplying power to the critical load  
equipment through the Maintenance Bypass. If there is no power to the critical load, apply power through the  
UPS bypass line per the following procedure.  
During a start-up procedure, power is supplied to the critical load through the UPS (internal) bypass line while  
the UPS system is being energized. Depending on the reason for your UPS system shutdown, you may already  
have power through the bypass line. You can determine this by observing the Monitor/Mimic Display screen at  
the System Control Cabinet (SCC) after Control Power is available.  
Step 1. Before you apply power to the UPS modules, determine the position of the following circuit breakers and  
switches:  
a. Bypass Input Breaker (BIB) - If this circuit breaker is closed, you may already have power to the  
critical load through the bypass line. If this breaker is closed, leave it closed. If it is open, leave it open  
until you are ready to energize the bypass line.  
b. System Bypass Circuit Breaker (SBB) - This motorized circuit breaker (Figure 9) should be closed  
unless you are recovering from a Remote Emergency Power Off. You may already be supplying power  
to the critical load through this breaker. If this breaker is open, you will be instructed to reset it later in  
this procedure.  
c. UPS Output Circuit Breaker - This motorized circuit breaker (see Figure 9) should be open.  
d. Static Switch Disconnects - These manually operated switches (see Figure 9) will be in the ON  
(closed) position unless you are recovering from a shutdown. If these switches are OFF (open), you will  
be instructed to reset them and turn them on later in this procedure.  
NOTE  
Depending on SCC model, the static switch disconnects can be two circuit breakers,  
contactors, or plug-in connections on a drawout carriage assembly. The location  
could be at the front, right, or rear of the cabinet. Refer to the drawing of the SCC  
cabinet selected for your UPS system.  
91  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE  
If the system was shut down in response to an “Emergency Off, there may be alarm  
messages on the LCD screen that describe system conditions before (or at the time of)  
the shutdown. Some or all of the alarm conditions may have already been resolved.  
To clear these alarm messages, turn off the control power (see Figure 8 and  
Figure 9). Wait at least ten minutes for the control power circuitry to completely de-  
energize. After ten minutes, turn control power back on and wait two minutes before  
continuing.  
CAUTION  
If you are recovering from a UPS system shutdown for maintenance procedures,  
verify that all of the SCC doors are closed and latched. All test equipment must  
be removed from the system. All electrical connections must be secure.  
Power must be provided to the UPS controls so the operator can use the LCD display and so the system logic can  
perform its control functions. Note that you can use the LCD display to monitor UPS system status, even when  
the UPS modules are not operating.  
During a start-up procedure, power is supplied to the critical load through the UPS (internal) bypass line while  
the UPS modules are being energized. Depending on the reason for your UPS system shutdown, you may already  
have power through the bypass line. You can determine this by observing the Monitor/Mimic Display screen at  
the System Control Cabinet (SCC).  
Step 2. If the bypass line is not supplying the load, the LCD screen will be blank. Energize the bypass line by  
operating the following controls:  
a. Close the Bypass Input Breaker (BIB). This breaker may be in your Maintenance Bypass cabinet.  
NOTE  
Wait two minutes after applying bypass power before you operate any other UPS  
controls.  
CAUTION  
DO NOT assume that the UPS System Bypass Breaker (SBB) is closed.  
Instructions for operating the Maintenance Bypass circuit breakers are on the  
Maintenance Bypass cabinet.  
Make sure you understand the proper sequence before operating any circuit  
breaker. Operating a Maintenance Bypass circuit breaker out of sequence could  
cut off power to the critical load.  
b. Observe the Monitor/Mimic Display screen to determine if your System Bypass circuit breaker (SBB)  
is closed and whether the UPS Bypass line is supplying power to the critical load.  
If your System Bypass circuit breaker is open (as in recovering from an Emergency Power Off or Low  
Battery Shutdown), close this circuit breaker as follows:  
b1. Open the SCC control panel door and find the Transfer Relay Board (Figure 11). If the red LED  
(CR18) labeled TOT S/D (Total Shutdown) is on, press the Bypass Reset switch (SW1) on this  
board. The red LED should turn off.  
b2. Set the Static Switch Disconnects (Figure 9) OFF (open).  
NOTE  
Depending on SCC model, the static switch disconnects can be two circuit breakers,  
contactors or plug-in connections on a drawout carriage assembly. The location  
could be at the front, right, or rear of the cabinet. Refer to the drawing of the SCC  
cabinet selected for your UPS system.  
92  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b3. Find the Close Bypass switch (SW1) on the System Interface Board (Figure 11). Press this switch  
to reset the System Bypass circuit breaker. Check the Monitor/Mimic screen to verify the breaker is  
closed.  
b4. Press two Reset Switches for Static Switch Disconnects behind door below SCC control panel  
(see Figure 9).  
b5. Set the Static Switch Disconnects to ON (closed).  
c. If the UPS Bypass line is available, but not yet supplying power to the load, close the circuit breakers  
(external to the UPS) required to provide power to the critical load equipment. Follow the three steps  
shown below.  
CAUTION  
Be sure to operate Maintenance Bypass circuit breakers in the proper sequence.  
c1. Verify the Bypass Input Breaker (BIB) and System Bypass circuit breakers are closed.  
c2. Close the Maintenance Isolation Breaker (MIB).  
c3. Open the Maintenance Bypass Breaker (MBB).  
Observe the Monitor/Mimic Display screen to confirm that the UPS Bypass line is energized and supplying  
power to the critical load equipment.  
At the System Control Cabinet (SCC), press the Select pad to put the Master Menu on the LCD display. Move  
the highlighted cursor to Start-Up Procedures (use the Up and Down pads). Press the Select pad to display the  
Start-Up Procedures screen. Return to this screen whenever you need to see the start-up instructions.  
On the LCD display, select System Configuration from the Master Menu. Verify that all of the information con-  
tained in the System Configuration screen is correct. When the data is correct, press the Select pad until the dis-  
play returns to the Master Menu.  
Perform a module start-up procedure at each module in your UPS system until all required modules are on-line.  
Then return to the SCC to complete your UPS system start-up.  
Use the Monitor/Mimic Display screen at the SCC to determine the condition of the UPS system. Press the  
Alarm Reset pad to clear the Alarm Messages. Refer to Table 1 for an explanation of any remaining alarm mes-  
sages (except Load On Bypass). Call Liebert Global Services if you cannot clear the remaining alarm messages.  
If the only alarm message displayed is Load On Bypass, the UPS system is now ready to provide filtered, unin-  
terruptible power to the critical load equipment. Refer to 3.3.2 - Load Transfer Procedures to retransfer the  
load from the bypass line to the UPS system.  
Figure 59 SCC Start-Up Procedures Screen  
SELECT : MASTER MENU  
START-UP PROCEDURES  
1.  
2.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model number is  
displayed.  
3.  
4.  
Go to the modules(s) and follow the module "STARTUP PROCEDURES".  
Select "MONITOR/MIMIC" screen, verify that the output voltages are at the  
proper nominal level and correct number of modules online is displayed.  
5.  
6.  
If the bypass or static switch breakers are open, refer to Start-up Procedures  
in the UPS manual for instructions on closing these breakers.  
System is now ready to assume load. Select "LOAD TRANSFER PROCEDURES"  
screen for this procedure.  
93  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Module Start-Up  
When a UPS module has been shut down for any reason, use this procedure to start-up the UPS module to pro-  
vide filtered, reliable power to the critical bus. This procedure gives step-by-step instructions for controls to  
operate and conditions to observe. Your present situation could be initial start-up or recovering from input power  
failure, battery shutdown, maintenance shutdown, or an emergency shutdown.  
Perform this module start-up procedure at each module in your UPS system until all required modules are on-  
line.  
Step 1. Before you apply power to the UPS module, determine the position of the following circuit breakers and  
switches:  
a. Rectifier Input Breaker (RIB) - If this external circuit breaker is closed, you already have power to the  
UPS cabinet and possibly power to the controls. If this breaker is closed, leave it closed. If it is open,  
leave it open until you are ready to apply power to the UPS cabinet.  
b. Input Circuit Breaker (CB1) - Verify that this breaker on the front of the UPS module cabinet  
(Figure 8) is in the OFF position.  
c. Module Battery Disconnect (MBD) - Verify that this external breaker is open or tripped.  
d. Module Output Circuit Breaker (CB2) - Verify that this breaker on the front of the UPS module  
cabinet (Figure 8) is in the OFF position.  
e. Control Power - This manually operated switch (Figure 8) will be in the ON position unless you are  
recovering from a maintenance shutdown. If this switch is OFF, leave it OFF until you are ready to  
apply power to the UPS controls.  
CAUTION  
If you are recovering from a module shutdown for maintenance procedures,  
verify that all of the UPS system doors are closed and latched, AU test  
equipment must be removed from the system. AU electrical connections must be  
secure.  
Power must be provided to the UPS module controls so you can use the LCD display and so the system logic can  
perform its control functions. Note that you can use the LCD display to monitor UPS status, even when the UPS  
module is not on-line. If the LCD display is operating, you already have Control Power. This will be the usual  
condition, unless you are recovering from a maintenance shutdown.  
Step 2. If the LCD screen is not operating, energize Control Power by operating the following two controls:  
a. Close the Rectifier Input Breaker (RIB), which is outside the UPS cabinet. This will provide power to  
the UPS cabinet but not to any UPS components.  
b. Open the UPS cabinet door and close the Control Disconnect fuseholders to turn the Control Power ON.  
See Figure 8. Close the UPS cabinet door.  
NOTE  
Wait two minutes after applying Control Power before you operate any other UPS  
module controls.  
Press the Select pad on the UPS module to put the Master Menu on the LCD display. Move the highlighted cur-  
sor to Start-Up Procedures (use the Up and Down pads). Press the Select pad to display the Start-Up Procedures  
screen. Return to this screen whenever you need to see the start-up instructions.  
On the LCD display, select System Configuration from the Master Menu. Verify that all of the information con-  
tained in the System Configuration screen is correct. When the data is correct, press the Select pad until the dis-  
play returns to the Master Menu.  
94  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 60 Module Start-Up Procedures Screen  
DOWN : NEXT PAGE  
SELECT :  
MASTER MENU  
START-UP PROCEDURES  
1.  
Verify that the control power is applied to the system control cabinet (check the display  
on the system control cabinet).  
2.  
3.  
Wait approximately two (2) minutes before attempting any other action .  
Select "SYSTEM CONFIGURATION" screen to verify that the correct model is  
displayed.  
4.  
Select "WALK-IN" screen and do the following:  
a)  
Close module input circuit breaker. Verify that the DC voltage bar on  
the display begins to gradually move to the right and the AC input  
current bars do not move to the right more than 10% (40% for modules  
with input filters) after the transformer inrush has subsided.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
START-UP PROCEDURES (Cont'd)  
b)  
c)  
Verify that the output voltage bar moves to the right after the DC  
bus bar has reached the 90% point. Both bars should settle near  
their respective 100% levels.  
If anything happens on the display not mentioned in (a) or (b),  
immediately open the module input circuit breaker and investigate.  
5.  
6.  
If step 4 is successful, select "MONITOR/MIMIC" screen and verify module  
DC bus and output voltages are at proper nominal level. If so, close  
module battery circuit breaker.  
If no alarms are present on the "MONITOR/MIMIC" screen, the module may be  
placed online by closing the module output breaker.  
Select the Walk-In screen on the LCD display.  
Step 3. To energize the UPS module, manually close the input circuit breaker (CB1, Figure 8). This will provide  
power to the rectifier. Use the Walk-In screen to monitor the Module DC Bus voltage.  
WARNING  
IF ANY ABNORMAL SITUATION OCCURS DURING THIS WALK-IN  
PROCEDURE, OPEN THE INPUT CIRCUIT BREAKER AND  
INVESTIGATE THE PROBLEM. EACH INPUT AMPS BAR SHOULD BE  
WITHIN 10% OF THE AVERAGE BAR LENGTH. CALL LIEBERT  
GLOBAL SERVICES IF YOU NEED HELP.  
The Input Amps bars should settle at about 10% after the momentary inrush current has subsided.  
Verify that the DC Voltage bar begins to gradually move to the right.  
Verify that the Output Voltage bar moves to the right after the DC Voltage bar has reached the 90% level. Both  
bars should settle near the 100% line.  
Select the Monitor/Mimic display from the Master Menu and confirm that the module DC bus and AC output  
are at their proper operating voltages.  
Step 4. When the Module DC Bus voltage is at 100%, you can manually close the module battery disconnect  
(MBD) circuit breaker (external to the UPS).  
95  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Battery block in the Monitor/Mimic Display indicates the battery voltage and charge current.  
NOTE  
The battery charge current may increase quickly, but then should slowly decrease. A  
fully charged battery will require no more than 31 Amps of charge current. If you are  
recovering from a battery shutdown or an input power failure, the UPS rectifier will  
be recharging the battery. Recharge current can be more than 100 Amps. The  
maximum allowable recharge current for your unit will depend on the kVA rating and  
your factory-set battery recharge current limit.  
CAUTION  
Do not use equalize charging with valve-regulated, sealed-cell batteries. Refer to  
the battery manufacturer’s manual for specific information about equalize  
charging.  
Use the Monitor/Mimic Display screen to determine the condition of the UPS module. Press the Alarm Reset  
pad to clear the Alarm Messages. Refer to Table 1 for an explanation of any remaining alarm messages. Call  
Liebert Global Services if you cannot clear the remaining alarm messages.  
If no alarm messages are displayed, the UPS module is now ready to provide filtered, uninterruptible power to  
the critical bus. Manually close the module output circuit breaker (CB2, Figure 8) to place this UPS module on-  
line.  
When all required UPS modules are on-line, return to the SCC to complete your UPS system start-up.  
96  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3.2 Load Transfer Procedures  
Use the Monitor/Mimic Display at the SCC to determine the operating condition of the UPS system. Press the  
Alarm Reset pad to clear the Alarm Messages. Refer to Table 1 for an explanation of any remaining alarm mes-  
sages (except Load On Bypass). Call Liebert Global Services if you cannot clear the remaining alarm messages.  
If the only alarm message displayed is Load On Bypass (or no alarms), you can perform a manual transfer of the  
load between the UPS system and the UPS bypass line. Changing the load from the UPS system to the UPS  
bypass is called a transfer. Changing the load from UPS bypass to the UPS system is called a retransfer. Note  
that the UPS system control logic can initiate automatic load transfers and retransfers. Refer to 3.4 - Automatic  
Operations.  
Press the Select pad to display the Master Menu on the LCD display of the SCC. Move the highlighted cursor to  
Load Transfer Procedures (using the Up and Down pads). Press the Select pad to display the Load Transfer Pro-  
cedures screen.  
Step 1. Verify that the OK TO TRANSFER message is highlighted. If not (if the TRANSFER PROHIBIT  
message is highlighted instead), slowly rotate the Voltage Adjust knob (Figure 10, item 6) to match the UPS  
system voltage to the bypass voltage.  
NOTE  
1. UPS output voltage changes VERY slowly in response to movements of the  
Voltage Adjust knob. To avoid overshooting, allow at least a minute for UPS  
output voltage to stabilize before proceeding to the next step.  
2. If the TRANSFER PROHIBIT message remains, refer to Table 1 for corrective  
action for any alarm messages. Call Liebert Global Services if you cannot solve  
the problem.  
Figure 61 Load Transfer Procedures Screen  
SELECT : MASTER MENU  
SYNCHRONIZATION  
+30  
VOLTAGE COMPARISON  
A-B B-C C-A  
FREQUENCY  
-30  
0
UPS  
BYPASS  
-
-
380 380 380  
381 380 379  
50.0 Hz  
50.0 Hz  
MANUAL  
TRANSFER INSTRUCTIONS  
UPS LEAD  
=
2 Deg  
ON UPS  
1.  
2.  
Adjust the UPS voltage until it equals the  
bypass voltage with the VOLTAGE ADJUST pot.  
If the OK TO TRANSFER message is highlighted,  
OK TO TRANSFER  
TRANSFER PROHIBIT  
simultaneously press the BYPASS and CONTROL ENABLE  
buttons.  
3.  
4.  
Verify that the transfer was successful by checking the  
breaker status on the "MONITOR/MIMIC" screen.  
Press the ALARM RESET button to clear alarms which  
are no longer active  
Step 2. Perform Step 2 on the Load Transfer Procedures Screen.  
a. If the load is on the UPS system, simultaneously press the Bypass and Control Enable pads  
(Figure 10). This will close the motorized System Bypass circuit breaker (SBB) and open the  
motorized UPS Output circuit breaker in a make-before-break sequence.  
b. If the load is on the UPS bypass, simultaneously press the UPS and Control Enable pads (Figure 10).  
This will close the motorized UPS Output circuit breaker and open the motorized System Bypass circuit  
breaker (SBB) in a make-before-break sequence.  
Return to the Monitor/Mimic Display screen to monitor the operation of the UPS system. Press the Alarm Reset  
pad to clear any latched alarm messages removed by the new load status. Refer to Table 1 if an alarm message  
other than Load On Bypass is still displayed. Contact Liebert Global Services if you require assistance.  
97  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Bypass Load Transfers  
To manually transfer the load between Maintenance Bypass and the UPS system bypass line, carefully follow  
these instructions. Do not transfer the load between Maintenance Bypass and the UPS system (module inverters)  
output. Use the SCC Monitor/Mimic Display screen to verify the UPS system bypass line is available.  
CAUTION  
Make sure you understand the proper sequence before operating any circuit  
breaker. Operating a Maintenance Bypass circuit breaker out of sequence could  
cut off power to the critical load.  
If the load is on the UPS System Bypass:  
a. Close the Maintenance Bypass Breaker (MBB).  
b. Verify closure of the MBB. Then open the Maintenance Isolation Breaker (MIB). Load is now on  
Maintenance Bypass.  
c. If UPS bypass shutdown is required, open the Bypass Input Breaker (BIB).  
If the load is on Maintenance Bypass:  
a. Close the Bypass Input Breaker (BIB) or verify BIB is closed. Note that UPS System Bypass circuit  
breaker (motorized) must also be closed.  
b. Close the Maintenance Isolation Breaker (MIB).  
c. Verify closure of the MIB. Then open the Maintenance Bypass Breaker (MBB). Load is now on UPS  
System Bypass.  
98  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3.3 Shutdown Procedures  
System Shutdown Procedure  
Perform a System Shutdown Procedure when you want to remove power from the UPS system and System Con-  
trol Cabinet (SCC) when required for maintenance, or if you need to perform maintenance on a UPS module in a  
non-redundant system.  
Before performing any maintenance on your Liebert Series 600T UPS, observe ALL of the WARNINGS in  
4.0 - Maintenance.  
Use the SCC Monitor/Mimic Display to determine the operating condition of the UPS system.  
From the SCC Master Menu, select the Shutdown Procedures screen.  
Figure 62 SCC Shutdown Procedures Screen  
SHUTDOWN PROCEDURES  
1.  
If load is not already being supplied by the bypass line, select the  
"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer  
the load to bypass.  
2.  
3.  
4.  
Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES."  
Press the ALARM RESET button to clear alarms which are no longer active.  
If necessary for maintenance purposes, open the static switch disconnect  
circuit breakers.  
5.  
Wait approximately two (2) minutes before attempting any other action .  
Step 1. If the UPS system is supplying power to the load (Load On UPS), select the Load Transfer Procedures  
screen at the SCC and perform a manual transfer to the bypass line (Load On Bypass). This will open the motor-  
ized UPS Output circuit breaker (see Figure 9) and close the motorized System Bypass circuit breaker (SBB,  
Figure 9).  
Step 2. If maintenance is required on the Static Bypass Switch, set the Static Switch Disconnects to OFF (open).  
Refer to Figure 9.  
NOTE  
Depending on SCC model, the static switch disconnects can be two circuit breakers,  
contactors, or plug-in connections on a drawout carriage assembly. The location  
could be at the front, right, or rear of the cabinet. Refer to the drawing of the SCC  
cabinet selected for your UPS system.  
CAUTION  
The UPS bypass line is still energized.  
99  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3. If maintenance is required in the area of the SCC controls or the motorized system circuit breakers (UPS  
Output and SBB), transfer the load to the Maintenance Bypass, if available.  
a. Close the Maintenance Bypass Breaker (MBB).  
b. Open the Maintenance Isolation Breaker (MIB).  
c. Open the Bypass Input Breaker (BIB).  
CAUTION  
If your installation does not include a Maintenance Bypass, power must still be  
isolated from both sides of the UPS circuit breakers if maintenance is required.  
This will result in loss of power to the critical load. Perform an orderly load  
shutdown before isolating power.  
WARNING  
LETHAL VOLTAGES ARE PRESENT WITHIN THIS UNIT EVEN WHEN  
IT IS NOT ON OR WHEN UTILITY IS NOT BEING SUPPLIED. OBSERVE  
ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO  
SO COULD RESULT IN SERIOUS INJURY OR DEATH. DO NOT WORK  
ON OR OPERATE THIS EQUIPMENT UNLESS YOU ARE FULLY  
QUALIFIED TO DO SO!! NEVER WORK ALONE.  
Before performing any maintenance on your Liebert Series 600T UPS, observe ALL of the WARNINGS in  
4.0 - Maintenance.  
100  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Module Shutdown Procedure  
Perform a Module Shutdown Procedure when you want to remove power from a UPS module when required for  
maintenance.  
Before performing any maintenance on your Liebert Series 600T UPS, observe ALL of the WARNINGS in  
4.0 - Maintenance.  
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.  
From the module Master Menu, select the Shutdown Procedures screen. Note that this is a two-page screen.  
Figure 63 Module Shutdown Procedures Screen  
DOWN : NEXT PAGE  
SELECT :  
MASTER MENU  
SHUTDOWN PROCEDURES  
1.  
If load can not be supported by the remaining modules when this module  
is taken off line, go to the system control cabinet and select the "LOAD  
TRANSFER PROCEDURES" screen. Follow the instructions to transfer  
to bypass.  
2.  
3.  
4.  
Open the module output breaker by simultaneously pressing the OUTPUT TRIP  
and CONTROL ENABLE pushbuttons.  
Open the module battery breaker by simultaneously pressing the BATTERY TRIP  
and CONTROL ENABLE pushbuttons.  
Manually open the input breaker by moving the handle to the OFF position.  
UP : FIRST PAGE  
SELECT : MASTER MENU  
SHUTDOWN PROCEDURES (Cont'd)  
5.  
6.  
Verify breaker status on the "MONITOR / MIMIC" screen.  
If necessary for maintenance purposes, turn the control power switch (fuse  
disconnect on some models) to the OFF position.  
7.  
Wait a minimum of two (2) minutes before attempting any other action.  
Step 1. If the UPS module is on-line, simultaneously press the Output Trip and Control Enable pads  
(Figure 10). This will open the UPS module output circuit breaker (CB2, Figure 8).  
Step 2. Open the module battery disconnect (MBD) circuit breaker by simultaneously pressing the Battery Trip  
and Control Enable pads (Figure 10).  
101  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3. Manually open the UPS input circuit breaker by moving the handle to the OFF position (Figure 8).  
Return to the Monitor/Mimic Display to verify status of the circuit breakers. Press the Alarm Reset pad to clear  
alarm messages.  
Step 4. If maintenance is required on the UPS controls, turn the Control Power switch to the OFF position  
(Figure 8). You may also want to open the Rectifier Input Breaker (RIB), external to the UPS cabinet.  
WARNING  
LETHAL VOLTAGES ARE PRESENT WITHIN THIS UNIT EVEN WHEN  
IT IS NOT ON OR WHEN UTILITY IS NOT BEING SUPPLIED. OBSERVE  
ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO  
SO COULD RESULT IN SERIOUS INJURY OR DEATH. DO NOT WORK  
ON OR OPERATE THIS EQUIPMENT UNLESS YOU ARE FULLY  
QUALIFIED TO DO SO!! NEVER WORK ALONE.  
Before performing any maintenance on your Liebert Series 600T UPS, observe ALL of the WARNINGS in  
4.0 - Maintenance.  
Local Emergency Modules Off (LEMO)  
The UPS controls at the SCC include an Emergency Module Off pad (Figure 10, item 12). When this guarded  
pad is pressed, the load is automatically transferred to the bypass line and the module output, battery, and  
input circuit breakers trip open to isolate and shut down all the UPS modules. Control Power for indicators and  
alarms remains on.  
Remote Emergency Power Off (REPO)  
The Remote Emergency Power Off control (REPO) is a switch located remotely from the UPS system. It will  
normally be in the same room as the critical load equipment.  
The Remote Emergency Power Off switch removes all power to the critical load.  
When you trip the Remote Emergency Power Off switch, all UPS circuit breakers are opened, including the  
System Bypass circuit breaker (SBB). All power through the UPS is removed from the load. You will still have  
power to the UPS controls, and you may have power to the static switch.  
102  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4  
Automatic Operations  
The Liebert Series 600T UPS system is designed to function while unattended by an operator. The system con-  
trol logic monitors the performance of the UPS, the availability of power sources, and the current required by the  
critical load.  
The system control logic at the SCC  
1. Determines what overload conditions can be sustained without a transfer to bypass.  
2. Initiates an automatic transfer to bypass to sustain an overload.  
3. Can initiate an automatic retransfer to the UPS after a system overload has been cleared.  
4. Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS fault  
occurs.  
The control logic at each UPS module  
1. Determines what overload conditions can be sustained by the module while it is on-line.  
2. Automatically takes the UPS module off line and initiates an emergency module shutdown when selected  
UPS faults occur.  
3.4.1 Overloads (Without Transfer)  
The UPS system is capable of sustaining full output voltage (±2% of the nominal voltage) for overload condi-  
tions that remain within (under) the current versus time curve of system overload capacity and the capacity of  
modules on-line (Figure 64). Note that the time scale is not linear. Load On UPS is illustrated in Figure 49.  
For high current demands of short duration (momentary overloads) the critical load is supplied simultaneously  
by both the UPS system and the bypass line. Whenever the critical load requires more than 155% of the capacity  
of the modules on-line, the bypass line will supply up to 1000% rated system current through the solid state static  
switch for 40 milliseconds. Refer to 3.2.3 - Momentary Overloads.  
Whenever an overload condition occurs, you should determine the cause of the overload.  
If an overload condition exceeds the UPS system overload capacity or the capacity of the modules on-line, the  
UPS system initiates an automatic load transfer to the bypass line.  
Figure 64 Current-Versus-Time Curves of Module Overload Capacity  
103  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4.2 Automatic Transfers to Bypass  
The UPS system will initiate an automatic load transfer to the bypass line if an overload condition exceeds the  
current versus time curve of system overload capacity, or capacity of the modules on-line, or if specified UPS  
system faults occur. Note that when the UPS system is operating in the non-redundant mode, an automatic trans-  
fer to bypass will be initiated when any UPS module is taken off line, either automatically or manually. Load On  
Bypass is illustrated in Figure 48.  
The Overload Transfer and Output Undervoltage alarm messages will initiate an automatic transfer to bypass and  
the Load On Bypass message will be displayed. The status report screens will include the Automatic Transfer to  
Bypass message. Other UPS system faults will initiate an automatic transfer to bypass followed immediately by  
the shutdown and isolation of the UPS modules. Refer to 3.4.5 - Automatic Emergency Modules Off.  
In an automatic transfer to bypass the UPS Output and System Bypass circuit breakers do not overlap as they do  
in a manual transfer. The static bypass switch is fired (closed), the UPS Output circuit breaker is opened, and the  
System Bypass circuit breaker is closed.  
Bypass power is supplied to the critical load through the static bypass switch during the short time while both cir-  
cuit breakers are open.  
NOTE  
A load transfer to the bypass line will be completed whenever an automatic transfer  
to bypass is initiated If the OK to Transfer condition is present, the load transfer will  
be uninterrupted. If the Static Switch Unable alarm message is present for any  
reason, the automatic transfer will be interrupted for 40 to 120 milliseconds. Because  
of the reliability of the UPS components, an interrupted load transfer is a very  
unlikely occurrence.  
3.4.3 Automatic Retransfers to UPS  
Automatic Retransfer to UPS is an option that you can select from the SCC System Configuration screen. If you  
do not want the UPS system to initiate any automatic retransfers, set Max Auto-Rexfer Attempts to zero (0).  
In an automatic retransfer, the two motorized circuit breakers (System Bypass and UPS Output) are both closed  
simultaneously for a short period of time (overlap).  
The following critical bus conditions must be present to initiate an automatic retransfer of the critical load from  
the bypass source to the UPS system:  
1. The number of Auto-Rexfer Attempts selected must be greater than zero (0). If zero (0) is selected, no  
automatic retransfers will occur.  
2. Critical load was initially transferred to the bypass source due to a system overload only. (A manually  
initiated retransfer from bypass is required if the critical load exceeded the capacity of the modules on-line,  
or if a UPS fault occurred.).  
3. Overload has since dropped below 100% of the rated SCC current.  
4. Enough UPS modules are on-line to supply the critical load.  
5. OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes of the system  
overload transfer. (A manually initiated retransfer from bypass is required for overloads lasting 5 minutes or  
more.)  
6. Cyclic-type overloads, which occur up to five (select range is 0 to 5) times in 60 minutes, are automatically  
returned to the UPS system for each event including the Nth overload. A manually initiated retransfer from  
bypass is required for the N + 1 overload.  
104  
Operation  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4.4 Automatic Module Off-Line  
For specified UPS module faults, the control logic will initiate an automatic isolation and shutdown of the UPS  
module. In the Module Off-Line mode the output, battery (MBD), and input circuit breakers are open. If the UPS  
system was operating in the redundant mode when the module was taken off-line, the critical load will remain on  
the UPS system. If the UPS system was operating in the non-redundant mode, an automatic transfer to bypass  
will be initiated. Note that the bypass line is usually not available during Low Battery Shutdown. One Module  
Off-Line is illustrated in Figure 52.  
The following UPS module faults will initiate an automatic Module Off-Line:  
DC Over-Voltage Shutdown  
Hardware Shutdown  
Inverter Fault  
Low-Battery Shutdown  
Overload Shutdown  
Over-Temperature Timeout  
Rectifier Fuse Blown  
Reverse Power  
Refer to Table 1 for more information regarding these alarm messages.  
3.4.5 Automatic Emergency Modules Off  
For the specified UPS system fault, the control logic will initiate an automatic transfer to bypass followed imme-  
diately by a shutdown and isolation of the UPS system. In the Emergency Modules Off mode the output, battery  
(MBD), and input circuit breakers at each UPS module are open. The System Bypass Breaker (SBB) will be  
closed if the bypass line is available. Emergency Modules Off is illustrated in Figure 54.  
The following UPS system fault will initiate an automatic Emergency Modules Off:  
Output Over Voltage  
Refer to Table 1 for more information regarding alarm messages.  
NOTE  
A load transfer to the bypass line will be completed whenever an automatic transfer  
to bypass is initiated and the bypass line is available. If the OK to Transfer condition  
is present, the load transfer will be uninterrupted. If the Static Switch Unable alarm  
message is present for any reason, the automatic transfer will be interrupted for 40 to  
120 milliseconds. Because of the reliability of the UPS components, an interrupted  
load transfer is a very unlikely occurrence.  
Your installation may include a Remote Emergency Power Off mode that can be initiated automatically by a  
contact closure in the critical load equipment. Refer to 3.2.8 - Emergency Power Off.  
105  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 MAINTENANCE  
If you require assistance for any reason, call the toll-free Liebert Global Services number: 1-800-543-2378. For  
LGS to assist you expediently, please have the following information available:  
Part Numbers:  
Serial Numbers:  
kVA Rating:  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
______________________________________________________________  
Date Purchased:  
Date Installed:  
Location:  
Input Voltage:  
Output Voltage:  
Battery Reserve Time:  
4.1  
Safety Precautions  
Observe the safety precautions in 1.0 - Introduction.  
ONLY qualified service personnel should perform maintenance on the UPS system.  
Observe ALL of the WARNINGS below before performing ANY maintenance on the UPS System and associ-  
ated equipment. Also observe the manufacturer’s safety precautions pertaining to the battery, along with the bat-  
tery safety precautions in this section.  
CAUTION  
Always identify connecting wiring prior to disconnecting any wiring.  
Do not substitute parts except as authorized by Liebert Corporation.  
Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings,  
etc.  
Call the Liebert Global Services if you are not sure of the procedures to follow or  
if you are not familiar with the circuitry.  
106  
Maintenance  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
EXTREME CAUTION IS REQUIRED WHEN PERFORMING  
MAINTENANCE.  
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS HIGH  
DC AS WELL AS AC VOLTAGES. WITH INPUT POWER OFF AND THE  
BATTERY DISCONNECTED, HIGH VOLTAGE AT FILTER CAPACITORS  
AND POWER CIRCUITS SHOULD BE DISCHARGED WITHIN 30  
SECONDS. HOWEVER IF A POWER CIRCUIT FAILURE HAS  
OCCURRED, YOU SHOULD ASSUME THAT HIGH VOLTAGE MAY  
STILL EXIST AFTER SHUTDOWN. CHECK WITH A VOLTMETER  
BEFORE MAKING CONTACT.  
AC VOLTAGE WILL REMAIN ON THE BYPASS AND OUTPUT CIRCUIT  
BREAKERS, AND THE STATIC BYPASS SWITCH, UNLESS ASSOCIATED  
EXTERNAL CIRCUIT BREAKERS ARE OPENED.  
CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS PRIOR  
TO MAKING CONTACT.  
BE SURE TO READ THE BATTERY MANUFACTURER’S MANUAL  
BEFORE WORKING ON OR NEAR THE BATTERY. BATTERY  
TERMINALS WILL CONSTANTLY BE ENERGIZED, REGARDLESS OF  
WHETHER THE UPS IS OPERATING OR NOT.  
WHEN THE UPS SYSTEM IS UNDER POWER, BOTH THE OPERATOR  
AND ANY TEST EQUIPMENT MUST BE ISOLATED FROM DIRECT  
CONTACT WITH EARTH GROUND AND THE UPS CHASSIS FRAME BY  
USING RUBBER MATS.  
SOME COMPONENTS WITHIN THE: CABINETS ARE NOT CONNECTED  
TO CHASSIS GROUND.  
ANY CONTACT BETWEEN FLOATING CIRCUITS AND THE CHASSIS IS  
A LETHAL SHOCK HAZARD. — USE DIFFERENTIAL OSCILLOSCOPES  
WHEN MEASURING A FLOATING CIRCUIT. THE DIFFERENTIAL  
INPUT SHOULD HAVE AT LEAST 800 Vrms COMMON MODE INPUT  
RATING AND A COMMON MODE REJECTION RATIO OF AT LEAST  
80dB.  
EXERCISE CAUTION THAT THE TEST INSTRUMENT EXTERIOR DOES  
NOT MAKE CONTACT EITHER PHYSICALLY OR ELECTRICALLY  
WITH EARTH GROUND.  
IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT, USE ONLY  
CARBON DIOXIDE FIRE EXTINGUISHERS, OR OTHERS APPROVED  
FOR USE IN ELECTRICAL FIRE FIGHTING  
M
107  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2  
Liebert Global Services  
Start-up, UPS maintenance, battery maintenance, and training programs are available for the Series 600T UPS  
through your Liebert sales representative.  
Professional Start-Up  
UPS Start-Up - Liebert’s Customer Engineers perform a thorough non-powered inspection of the units, and will  
then conduct a complete electrical checkout which includes calibrating all components to published specifica-  
tions. The battery installation is also inspected and placed on an initialization charge to ensure cell equalization.  
Customer Operation training will be conducted during battery charge time.  
Load Bank Testing and Full Site Acceptance Testing are additional services that can be performed during a UPS  
Start-Up. One Preventive Maintenance Service Call can be added to the initial UPS Start-Up Agreement.  
Battery Installation/Start-Up - When purchased with a UPS Start-Up, this Agreement provides consistent, pro-  
fessional service for your entire UPS system. This one-source approach avoids conflicts that may occur during a  
multisource installation. Note that Liebert requires a mandatory installation inspection for all batteries not  
installed by Liebert Customer Engineers.  
Battery IEEE Certification Inspection - The Battery Specialist will perform a detailed inspection of the entire  
battery system to ensure it meets current IEEE standards.  
Maintenance Agreements: The Signature Program  
UPS Service Agreements - Liebert Global Services (LGS) has a variety of available maintenance agreements,  
depending on specific site needs. Choose the level of support appropriate for each installation. Mission-critical  
sites can have the standard parts-and-labor, around-the-clock coverage for their UPS, with or without scheduled  
preventive maintenance visits. Other sites can benefit from a variety of money-saving options.  
As a rule of thumb, Liebert recommends two preventive maintenance visits per year for the UPS. The first can be  
conducted with the UPS operational, and includes an infra-red scan of key UPS components. The annual visit  
will require taking the UPS off-line for a thorough nonpowered inspection. These visits are in addition to the  
general housekeeping tasks (changing air filters, etc.) that can be performed by customer personnel.  
Battery Service Agreements - The same flexible Signature Program can also be applied to contracts for battery  
maintenance. Again, the coverage needed will depend on the type of battery purchased and the degree of support  
required from Liebert Global Services.  
Training  
Customer training courses include the proper operation of the system, emergency procedures, preventive mainte-  
nance, and some corrective maintenance.  
Warranties  
Contact Liebert Global Services if you have any questions regarding the warranty on your Series 600T UPS or  
the batteries.  
108  
Maintenance  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3  
Routine Maintenance  
You are encouraged to become thoroughly familiar with the equipment, but at no time should you go beyond the  
specific procedures in this manual while performing maintenance or correcting a malfunction. If you have any  
doubt as to what must be done, call Liebert Global Services at 1-800-543-2378 for further instructions.  
The UPS is designed for unattended operation, but does require some common sense maintenance.  
• Keep good records.  
Troubleshooting is easier if you have historical background.  
• Keep it clean.  
Maintain the UPS free of dust and any moisture.  
• Keep it cool.  
Battery systems must be kept in the range of 72-77°F (22-26°C) in order to meet design specifications for  
capacity and longevity.  
The UPS will reliably meet all performance specifications at temperatures up to 104°F (40°C), and can be  
slightly aerated for operation at even higher temperatures. However, performance and longevity will be opti-  
mized when the UPS is operated at the same temperature as the batteries.  
• Keep connections tight.  
Tighten all connections at installation and at least annually thereafter. (See torque requirements, Table 4.)  
4.3.1 Record Log  
Set up a maintenance log to record scheduled checks and any abnormal conditions.  
The log should have space for all metered parameter indications including phase readings, alarm messages, UPS  
mode of operation, air filter replacement date, and observation notes. A second log should be maintained for the  
battery module as directed by the battery manufacturer.  
A periodic walk-through inspection of the UPS and battery rooms is advised to check for visible and audible  
indications of problems. Log the inspection, metered parameter indications, and any discrepancies.  
4.3.2 Air Filters  
A schedule for inspection of the air filters is required. The period between inspections will depend upon environ-  
mental conditions. Under normal conditions, the air filters will require service or replacement approximately  
every two months.  
All T-UPS models have replaceable filter elements built into the full-width grille across the front of the unit. This  
element can be changed from the front, with the UPS operating.  
Series 600T models rated 300 kVA and higher also have recyclable filters built into the front of their base assem-  
blies. These metal filter elements can be removed, washed in water, dried and returned to service.  
CAUTION  
Be certain recyclable filter elements are dry before reinstalling them in the UPS.  
Abnormal or dusty conditions will require more frequent cleaning and replacement of air filters. Inspect installa-  
tions in new buildings more often, then extend the inspection period as experience dictates.  
M
109  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.3 Battery Maintenance  
WARNING  
THESE MAINTENANCE PROCEDURES WILL EXPOSE HAZARDOUS  
LIVE PARTS. REFER SERVICING TO QUALIFIED PERSONNEL.  
DC FUSES OPERATE AT THE RATED BATTERY VOLTAGE AT ALL  
TIMES. A BLOWN DC BUS FUSE INDICATES A SERIOUS PROBLEM.  
SERIOUS INJURY OR DAMAGE TO THE EQUIPMENT CAN RESULT IF  
THE FUSE IS REPLACED WITHOUT KNOWING WHY IT FAILED. CALL  
LIEBERT GLOBAL SERVICES FOR ASSISTANCE.  
Battery Safety Precautions  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the  
required precautions. Keep unauthorized personnel away from batteries.  
When replacing batteries, use the same number and type of batteries.  
WARNING  
LEAD-ACID BATTERIES CONTAIN HAZARDOUS MATERIALS.  
BATTERIES MUST BE HANDLED, TRANSPORTED, AND RECYCLED OR  
DISCARDED IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL  
REGULATIONS. BECAUSE LEAD IS A TOXIC SUBSTANCE, LEAD-ACID  
BATTERIES SHOULD BE RECYCLED RATHER THAN DISCARDED.  
DO NOT DISPOSE OF BATTERY OR BATTERIES IN A FIRE. THE  
BATTERY MAY EXPLODE.  
DO NOT OPEN OR MUTILATE THE BATTERY OR BATTERIES.  
RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES. IT  
MAY BE TOXIC.  
A battery can present a risk of electrical shock and high short circuit current.  
The following precautions should be observed when working on batteries:  
1. Remove watches, rings, or other metal objects.  
2. Use tools with insulated handles.  
3. Wear rubber gloves and boots.  
4. Do not lay tools or metal parts on top of batteries.  
5. Disconnect charging source prior to connecting or disconnecting battery  
terminals.  
6. Determine if battery is inadvertently grounded. If inadvertently grounded,  
remove source of ground. Contact with any part of a grounded battery can  
result in electrical shock. The likelihood of such shock will be reduced if  
such grounds are removed during installation and maintenance.  
Lead-acid batteries can present a risk of fire because they generate hydrogen  
gas. The following procedures should be followed:  
1. DO NOT SMOKE when near batteries.  
2. DO NOT cause flame or spark in battery area.  
3. Discharge static electricity from body before touching batteries by first  
touching a grounded metal surface.  
110  
Maintenance  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Safety Precautions In French Per CSA Requirements  
Instructions Importantes Concernant La Securité  
Conserver Ces Instructions  
ADVERTISSEMENT  
DES PIECES SOUS ALIMENTATION SERONT LAISSEES SANS  
PROTECTION DURANT CES PROCEDURES D’ENTRETIEN. UN  
PERSONNEL QUALIFIE EST REQUIS POUR EFFECTUER CES  
TRAVAUX.  
LES FUSIBLES A C.C. DE LA BATTERIE D’ACCUMULATEURS  
OPERENT EN TOUT TEMPS A LA TENSION NOMINALE. LA PRESENCE  
D’UN FUSIBLE A C.C. BRULE INDIQUE UN PROBLEME SERIEUX. LE  
REMPLACEMENT DE CE FUSIBLE, SANS AVOIR DETERMINE LES  
RAISONS DE LA DEFECTUOSITE, PEUT ENTRAINER DES BLESSURES  
OU DES DOMMAGES SERIEUX A L’EQUIPEMENT. POUR ASSISTANCE,  
APPELER LE DEPARTEMENT DE SERVICE A LA CLIENTELE DE  
LIEBERT.  
DANGER  
Les accumulateurs plomb-acide contiennent de la matière comportant un  
certain risque. Les accumulateurs doivent être manipulés, transportés et  
recyclés ou éliminés en accord avec les lois fédérales, provinciales et locales.  
Parce que le plomb est une substance toxique, les accumulateurs plomb-acide  
devraient etre recyclés plutôt qu’éliminés.  
Il ne faut pas brûlé le ou les accumulateurs. L’accumulateur pourrait alors  
explosé.  
Il ne faut pas ouvrir ou endommager le ou les accumulateurs. L’électrolyte qui  
pourrait s’en échapper est dommageable pour la peau et les yeux.  
Un accumulateur représente un risque de choc électrique et de haut courant de  
court-circuit. Lorsque des accumulateurs sont manipules, les mesures  
préventives suivantes devraient être observées:  
1. Retirer toutes montre, bagues ou autres objets métalliques.  
2. Utiliser des outils avec manchon isolé.  
3. Porter des gants et des bottes de caoutchouc.  
4. Ne pas déposer les outils ou les pièces métalliques sur le dessus des  
accumulateurs.  
5. Interrompre la source de charge avant de raccorder ou de débrancher les  
bornes de la batterie d’accumulateurs.  
6. Déterminer si l’accumulateur est mis à la terre par erreur. Si oui, défaire  
cette mise à la terre. Tout contact avec un accumulateur mis à la terre peut  
se traduire en un choc électrique. La possibilitié de tels chocs sera réduité si  
de telles mises à la terre sont débranchées pour la durée de l’installation ou  
de l’entretien.  
Les accumulateurs plomb-acide présentent un risque d’incendie parce qu’ils  
génèrent des gaz à l’hydrogène. Les procédures suivantes devront être  
respectées.  
1. NE PAS FUMER lorsque près des accumulateurs.  
2. NE PAS produire de flammes ou d’étincelles près des accumulateurs.  
3. Décharger toute électricité statique présente sur votre corps avant de  
toucher un accumulateur en touchant d’abord une surface métallique mise à  
la terre.  
M
111  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DANGER  
L’électrolyte est un acide sulfurique dilué qui est dangereux au contact de la  
peau et des yeux. Ce produit est corrosif et aussi conducteur electrique. Les  
procédures suivantes devront être observées:  
1. Porter toujours des vêtements protecteurs ainsi que des lunettes de  
protection pour les yeux.  
2. Si l’électrolyte entre en contact avec la peau, nettoyer immédiatement en  
rincant avec de l’eau.  
3. Si l’électrolyte entre en contact avec les yeux, arroser immédiatement et  
généreusement avec de l’eau. Demander pour de l’aide medicale.  
4. Lorsque l’electrolyte est renversée, la surface affectée devrait être nettoyée  
en utilisant un agent neutralisant adéquat. Une pratique courante est  
d’utiliser un mélange d’approximativement une livre (500 grammes) de  
bicarbonate de soude dans approximativement un gallon (4 litres) d’eau. Le  
mélange de bicarbonate de soude devra être ajouté jusqu’à cc qu’il n’y ait  
plus apparence de reaction (mousse). Le liquide résiduel devra être nettoyé à  
l’eau et la surface concernée devra être asséchée.  
112  
Maintenance  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery and terminal  
voltages, specific gravity, and connection resistance should be made. Strictly follow the procedures outlined in  
the battery manufacturer’s manual.  
Valve-regulated lead-acid (sealed-top) batteries do require periodic maintenance. Though they do not require  
maintenance of electrolyte levels, battery voltage and connection resistance checks should be made.  
Since individual battery characteristics are not identical, and may change over time, the UPS module is equipped  
with circuitry to equalize battery cell voltages. This circuit increases charging voltage to maintain flooded type  
battery cells at full capacity.  
NOTE  
Do not use equalize charging with valve-regulated lead-acid batteries.  
Consult the battery manufacturer's manual for specific information about equalize  
charging.  
The equalizing charge time period is adjustable from zero to 72 hours and can be initiated automatically or man-  
ually. Refer to 3.0 - Operation.  
Battery Voltage Record  
Float Voltage  
(Volts DC)  
Nominal Voltage  
(Volts DC)  
Ambient Temp.  
(°F)  
Date  
*___________ *______________________ *______________________ *______________________  
___________  
___________  
___________  
___________  
___________  
___________  
___________  
___________  
___________  
___________  
___________  
___________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
______________________  
* To be completed by Liebert Customer Service Representative at time of start-up.  
M
113  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Matching Battery Cabinets (Optional)  
Although the individual battery cells are sealed (valve-regulated) and require only minimal maintenance, the  
Battery Cabinets should be given a periodic inspection and electrical check. Checks should be performed at least  
annually to ensure years of trouble-free service.  
Voltage Records. With the Battery Cabinet DC circuit breaker closed and the connected UPS operating, mea-  
sure and record battery float voltage. With the DC circuit breaker open, measure and record the nominal (open  
circuit) voltage. Both these measurements should be made across the final positive and negative terminal lugs.  
Compare these values with those shown below. The recorded nominal voltage should be no less than the value  
shown, while the recorded float voltage should be within the range shown. If a discrepancy is found, contact Lie-  
bert Global Services.  
Battery Voltage (VDC)  
Number of Cells  
Nominal  
Float  
240  
480  
527 - 576  
Power Connections. Check for corrosion and connection integrity. Visually inspect wiring for discolored or  
cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 4.  
Battery Cell Terminals. Check for discoloration, corrosion, and connection integrity. Clean and tighten if nec-  
essary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more than the retorque value.  
Retorque values are:  
Battery Manufacturer  
Johnson Controls Batteries  
Battery Model Number  
UPS12-270(FR)  
UPS12-310(FR)  
UPS12-370(FR)  
UPS12-475(FR)  
LS12-100  
Retorque Value  
32 lb-in.  
52 lb-in.  
52 lb-in.  
100 lb-in.  
100 lb-in.  
100 lb-in.  
65 lb-in.  
65 lb-in.  
85 lb-in.  
C&D Batteries  
12G-17  
Power Batteries  
PRC12110X  
PRC12120X  
PRC12150X  
PRC1290X  
65 lb-in.  
TC12110X  
65 lb-in.  
TC12120X  
65 lb-in.  
TC12150X  
85 lb-in.  
TC1290X  
65 lb-in.  
If you have a different model battery, contact Liebert Global Services for the required torque value.  
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once discon-  
nected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts. The battery shelf  
can now be pulled out. Tighten each terminal connection to the retorque value. When replacing a battery, the ter-  
minal connections must be cleaned and tightened. Disconnect and insulate the cables connected to the battery.  
Secure each battery shelf with retaining screws when maintenance is complete.  
Rack-Mounted Batteries  
If the UPS system uses a battery other than a factory-supplied Matching Battery Cabinet, perform maintenance  
on the battery as recommended in the battery manufacturer’s maintenance manual.  
4.3.4 Torque Requirements  
All electrical connections must be tight. Table 4 provides the torque values for the connections in the UPS.  
NOTE  
Refer to battery manufacturer's manual for the proper torque values required for the  
battery.  
114  
Maintenance  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4  
Torque Specifications (Unless Otherwise Labeled)  
Nut and Bolt Combinations  
Grade 2  
Standard  
Electrical Connections  
with Belleville Washers  
Bolt  
Shaft  
Size  
Lb-in  
53  
N-m  
6.0  
12  
Lb-in  
46  
N-m  
5.2  
6.8  
11  
1/4  
5/16  
3/8  
107  
192  
428  
60  
22  
95  
1/2  
48  
256  
29  
Circuit Breakers With Compression Lugs  
(For Power Wiring)  
Terminal Block Compression Lugs  
(For Control Wiring)  
AWG Wire  
Size or  
Range  
Current  
Rating  
Lb-in  
N-m  
Lb-in  
N-m  
400 - 1200  
Amps  
300  
34  
#22 - #14  
3.5 to 5.3  
0.4 to 0.6  
4.4  
Detection of Trouble  
There is no practical way to anticipate an impending malfunction. It is important that the operator check the  
instrument readings if abnormal equipment performance is suspected.  
Items to check include:  
1. Output voltage of all phases should be within 2% of normal voltage. Output currents on each phase should  
not normally differ by more than 20%. If a greater difference is noted, the load is unbalanced and corrective  
action should be taken to redistribute the load, if possible.  
2. If the UPS has not operated on battery power during the last 10 hours, the batteries should require little  
charging current. Battery mimic should indicate normal DC voltage with the battery charge current no more  
than 31 Amperes.  
3. Input current on each phase should be within 10% of the average input current.  
4. Alarm messages indicate malfunction or impending malfunction. A daily check of the Operator Control  
Panel will help to provide an early detection of problems. Refer to Table 1 and Table 2 in 3.0 - Operation  
to interpret alarm messages.  
5. Tracing a problem to a particular section is facilitated by alarm messages and the metered parameter  
indications. These are stored in the Status Reports and can be displayed at the Operator Control Panel or at  
an optional terminal. The Liebert Customer Service Engineer will also be familiar with test points inside the  
unit.  
NOTE  
If the UPS system has a blown fuse, the cause should be determined before you  
replace the fuse. Contact Liebert Global Services.  
M
115  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5  
Reporting a Problem  
If a problem occurs within the UPS, review all alarm messages along with other pertinent data. This information  
should be given via telephone to the Liebert Field Service Regional Office nearest you. This information can also  
be automatically sent by telephone modem. Call 1-800-543-2378 or your nearest LGS office to report a problem  
or to request assistance.  
4.6  
4.7  
Corrective Actions  
For each alarm message on the Operator Control Panel and the Remote Monitor Panel, you can find the recom-  
mended corrective action in Table 1 of 3.0 - Operation.  
Recommended Test Equipment  
A list of recommended test equipment and tools required to maintain, troubleshoot, and repair the UPS module is  
given in Table 5.You may substitute instruments of equivalent range and accuracy. All instruments should be  
calibrated and be within the current calibration cycle. Calibration data for the instruments should be maintained  
in historic files and the instruments labeled for audit and verification.  
Table 5  
Quantity  
Recommended Test Equipment and Tools  
Test Equipment  
Manufacturer  
Model or Type  
1
2
2
Oscilloscope  
Tektronix, H-P or  
Fluke  
DC to 50 MHz  
Voltage Probes  
Voltage Probes  
Tektronix, H-P or  
Fluke  
10X, with 10 ft Cable  
100X, with 10 ft Cable  
Tektronix, H-P or  
Fluke  
1
1
Digital Multi-Meter  
Tool Kit  
Fluke  
N/A  
8060, with Test Leads  
Standard electrical contractor tools  
116  
Maintenance  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.0 SPECIFICATIONS AND RATINGS  
5.1  
Rating  
The kVA and kW ratings and the nominal voltages and currents for continuous operation are listed on the unit  
nameplates (inside Operator Control Panel door) and on the System One-Line Diagram. The UPS is rated to  
deliver rated kVA and rated kW at 0.8 lagging power factor (pf), or 0.9 lagging pf for some models. However,  
the UPS will operate connected loads with power factors ranging from 0.7 lagging through 1.0 (unity).  
Connected load kW and kVA are both displayed on the LCD screen when the UPS is powering the load. Power  
factor may be easily calculated by kW ÷ kVA = pf.  
For load power factors between 0.7 lagging and the rated power factor (usually 0.8 or 0.9), the full kVA rating of  
the unit is available. However, above the rated pf the kW rating will become the limiting factor. Note that some  
models are specifically rated for a 0.9 lagging output power factor.  
For loads with power factors below 0.7 lagging or with leading power factors, the UPS output is kVA limited and  
the UPS System may not meet all of its output performance specifications. Consult your Liebert sales representa-  
tive for performance specifications for these applications.  
Specifications
117  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2  
Environmental Conditions  
Enclosure:  
The UPS is housed in a NEMA-1 enclosure. The enclosure is  
designed for indoor use only and is not to be subjected to falling  
objects or precipitation.  
Recommended Operating  
Temperature:  
25°C  
Maximum Operating Temperature:  
Minimum Operating Temperature:  
Storage Temperature:  
40°C (design temperature) without derating  
0°C  
-20°C to 70°C  
Typical Battery Temperature  
Requirements:  
Average annual temperature shall not exceed 27°C. Peak  
temperature shall not exceed 43°C during any 24-hour period. See  
battery manufacturerʼs recommendations.  
Relative Humidity:  
Operating Elevation:  
Storage Elevation:  
Audible Noise:  
0 to 95% without condensation  
Sea level to 1219 meters (4000 ft.) without derating  
Sea level to 12,192 meters (40,000 ft.)  
69 dBA typical, measured 5 feet from unit  
91% at 45°C  
Derating for Higher Ambient  
Temperatures:  
82% at 50°C  
73% at 55°C  
Consult your Liebert sales representative regarding applications in  
high ambient temperatures. Special temperature sensors must be  
installed at the factory.  
Derating for Higher Elevations:  
95% at 2000 meters  
94% at 2200 meters  
93% at 2400 meters  
92% at 2600 meters  
91% at 2800 meters  
90% at 3000 meters  
NOTE  
This category of electronic equipment is agency rated for use in an atmosphere free of  
conductive particles. Some industrial facilities may require a room air filtration  
system to keep the UPS free of excess moisture and contaminants.  
The UPS system is designed to operate continuously at 40°C. However, design  
equipment life expectancy will be extended with lower temperatures (25°C is  
recommended).  
118  
Specifications and Ratings  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.3  
Adjustments  
All adjustments are set at the factory or during start-up and normally do not have to be field readjusted.  
• Input Current Limit: Normal, 115%; on generator (with optional circuit), 100%.  
• Battery Charge Current Limit: Normal, 10%; on generator (with optional circuit), 1%.  
• Battery Equalize Charge: Set at start-up dependent on battery characteristics.  
• DC Over-Voltage: 600 volts for models with nominal 240 cell battery (High Link).  
• Overload Alarm: 104% normal load.  
• Output Frequency Tolerance: ±0.5 Hz.  
• Output Voltage: Nominal—operator adjustable ±5%.  
• Line Drop Compensation: 0 to +5%—Set at start-up to match load characteristics. If significant additional  
loads are connected, call Liebert Global Services.  
5.4  
Battery Operation  
The separate battery manufacturer’s manual provides the necessary information for the installation, operation,  
and maintenance of the battery. Use the battery manual in conjunction with this manual.  
The float charge voltage for a battery is equal to the number of cells in series making up the battery multiplied by  
the charge voltage for each cell.  
Since the charging voltage level is critical to proper battery operation, refer to your battery manual for informa-  
tion regarding your system.  
For 150-750 kVA models with nominal 240 cell battery, the DC bus nominal voltage range is 527 to 576 VDC.  
For 65-125 kVA models (with 240 cell battery only), the DC bus nominal voltage range is 534-574 VDC. Maxi-  
mum equalize voltage is 585 VDC. Battery voltage at end of discharge is 386 VDC at the UPS terminals (389  
VDC at the battery). The number of battery cells required will range from 236 to 244, depending on the UPS  
model and your application.  
Specifications
119  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.5  
Electrical Specifications  
RECTIFIER INPUT  
Input Voltage:  
Standard voltages—208 VAC, 480 VAC, 600 VAC. Other voltages available on  
request. 3-phase, 3-wire plus ground.  
Voltage Range:  
+10%, -15% (no battery discharge at -20%).  
Frequency Range:  
57 Hz to 63 Hz.  
Subcycle Magnetization Inrush:  
Less than 3 times normal full load input current for UPS models without  
optional input isolation transformer. Less than 8 times normal full load input  
current for T-UPS models with optional input isolation transformer or 12-pulse  
rectifier.  
Input Current Walk-In:  
Current Limit:  
From 20% to 100% in 15 seconds.  
Maximum of 125% normal full load input current.  
Current Distortion  
Less than 30% THD typical at normal full load input current. Less than 7%  
reflected THD typical at normal full load input current with optional input filter.  
500 kVA to 750 kVA models with optional 12-pulse rectifier: Less than 9% THD  
typical at normal full load input current. Less than 4% reflected THD typical at  
normal full load input current with optional input filter.  
Power Factor  
0.85 minimum lagging at full load.  
0.92 minimum lagging at full load with optional input filter.  
BYPASS INPUT  
Input Voltage:  
Standard voltages—208Y/120 VAC, 480Y/277 VAC, 600Y/346 VAC. Other  
voltages available on request. 3-phase, 4-wire plus ground or 3-phase, 3-wire  
plus ground.  
Optional voltages—208 VAC, 480 VAC, 600 VAC. Other optional voltages  
available on request. 3-phase, 3-wire plus ground (ungrounded or corner  
grounded delta).  
Voltage Range:  
±5% for manually initiated bypass transfer  
±10% for automatically initiated uninterrupted transfer.  
Frequency Range:  
Voltage Transient:  
59.5 Hz to 60.5 Hz.  
±4% for manually initiated bypass transfer.  
120  
Specifications and Ratings  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CRITICAL LOAD OUTPUT  
Output Voltage:  
Standard voltages—208Y/120 VAC, 480Y/277 VAC, 600Y/346 VAC. Other  
voltages available on request.  
SCC output: 3-phase, 3-wire plus ground or 3-phase, 4-wire plus ground.  
Module output to SCC: 3-phase, 4-wire plus ground (neutral required).  
Optional voltages—208 VAC, 480 VAC, 600 VAC. Other optional voltages  
available on request. 3-phase, 3-wire plus ground (ungrounded or corner  
grounded delta).  
Voltage Regulation:  
±0.5% for balanced load.  
±2% for unbalanced load.  
Voltage Adjustment Range:  
Line Drop Compensation Range:  
Frequency  
±5% manually.  
Up to +5% automatic load dependent.  
59.5 Hz to 60.5 Hz.  
Slew Rate:  
0.06 Hz per second.  
Phase Balancing:  
120° ±1° for balanced loads.  
120° ±3° for 50% unbalanced loads.  
Voltage Imbalance:  
20% Unbalanced Load  
50% Unbalanced Load  
±1% from the arithmetic average of the 3 phases.  
±2% from the arithmetic average of the 3 phases.  
Voltage Transient:  
20% Load Step  
30% Load Step  
100% Load Step  
Loss or Return of AC Input Power  
Manual Transfer of 100% Load  
±4% from the average peak voltage.  
±5% from the average peak voltage.  
±7% from the average peak voltage.  
±1% from the average peak voltage.  
±4% from the average peak voltage.  
Voltage Transient Recovery Time:  
Voltage Harmonic Content:  
To within 1% of steady state output voltage within 50 milliseconds.  
Maximum 5% RMS total, for any combination of linear and nonlinear loads.  
Maximum 3% RMS single, for linear loads.  
Module Overload Capacity at Full  
Output Voltage:  
(System overload capacity depends  
on the configuration of on-line  
modules.)  
104% of full load rating continuously.  
125% of full load rating for 10 minutes.  
150% of full load rating for 30 seconds.  
(with ±2% voltage regulation).  
Fault Clearing:  
300% of normal full load current subcycle.  
1000% of normal full load current up to 40 milliseconds with bypass available.  
Specifications
121  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 600T™ UPS  
Multi-Module Three Phase  
65 kVA to 750 kVA; 60 Hz  
Technical Support  
U.S.A. 1-800-222-5877  
Outside the U.S.A. 614-841-6755  
U.K. +44 (0) 1793 553355  
France +33 1 4 87 51 52  
Germany +49 89 99 19 220  
Italy +39 2 98250 1  
Netherlands +00 31 475 503333  
Web site http://www.liebert.com  
Worldwide FAX 614-841-5471  
tech support  
The Company Behind The Products  
With more than 500,000 installations around the globe, Liebert is the world leader in computer protection sys-  
tems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for  
sensitive electronics:  
• Environmental systems: close-control air conditioning from 1.5 to 60 tons.  
• Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA.  
• Integrated systems that provide both environmental and power protection in a single, flexible package.  
• Monitoring and control — on-site or remote — from systems of any size or location  
Service and support, through more than 100 service centers around the world, and a 24-hour  
Customer Response Center.  
While every precaution has been taken to ensure accuracy and completeness of this literature, Liebert Corpora-  
tion assumes no responsibility, and disclaims all liability for damages resulting from use of this information or  
for any errors or omissions.  
© 1999 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without  
notice.  
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trade-  
marks or registered trademarks of their respective owners.  
Printed in U.S.A.  
SL-30024  
Revised: February 1999  
Download from Www.Somanuals.com. All Manuals Search And Download.  

La Crosse Technology Clock WS 8117 User Manual
Lennox International Inc Heat Pump 67M41 User Manual
Lenovo Digital Camera 41N5719 User Manual
Lenovo Network Router TS140 User Manual
Link electronic Network Router 860 XL858V User Manual
Makita Impact Driver 6905H User Manual
Marshall Amplification Musical Instrument Amplifier AS80R User Manual
Maytag Washer MAH 2 User Manual
McCulloch Lawn Mower MC175H42ST User Manual
Middleby Marshall Welding Consumables PS360EWB User Manual