Liebert Network Card ITR User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert® ChallengerITR  
Installation Manual - Nominal Capacities 23 or 33 kW, 50 & 60Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
5.1  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.1  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLES  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1.0 INTRODUCTION  
1.1 System Descriptions  
Liebert Challenger ITR environmental control systems are available in three main system configu-  
rations:  
• self contained system with a scroll compressor in the room unit  
• self contained chilled water system  
• split system with an evaporator section and a remote condensing unit  
All three types are available in horizontal flow configurations. Each model requires three-phase  
power. Units are available in 208, 230, 460, or 575 V, 60 Hz; and 200, 230 or 380/415 V, 50 Hz.  
The following features are included as standard in all room units regardless of the type of system:  
V-frame coil, infrared humidifier, finned tubular stainless steel electric reheat, 2" filter, individual  
high voltage fused protection, and fan assembly.  
Each configuration can operate with either Advanced Microprocessor Controls (A), or Advanced  
Microprocessor Controls with Graphics (G). A brief description of each, including operational differ-  
ences, is listed below. Check model numbers to see what is supplied with your unit.  
1.1.1 Self Contained Systems  
Air-Cooled Models  
Complete refrigeration system including hot gas bypass and crankcase heater with standard con-  
denser and fan speed control for 95°F (35°C) ambient at sea level.  
Water-Cooled Models  
Compete refrigeration system including hot gas bypass with water/glycol-cooled condenser and two-  
way water regulating valve with bypass.  
Glycol-Cooled Models  
The water-cooled model as described above plus pump package and 95°F (35°C) design ambient dry-  
cooler.  
GLYCOOL Models  
Complete refrigeration system including hot gas bypass with glycol condenser and three-way water reg-  
ulating valve plus an integrally piped Econ-O-Coil with three-way modulating control valve.  
1.1.2 Chilled Water Models  
Chilled Water models include chilled water piping, three-way modulating valve and actuator assembly.  
1.1.3 Split Systems  
Each Air-Cooled split system consists of an evaporator section and one of the following condensing units.  
Prop Fan  
Includes scroll compressor, condenser coil, prop fan, high pressure switch, and Lee-Temp head pres-  
sure control. Unit is designed for outdoor location.  
Centrifugal Fan  
Includes scroll compressor, condenser coil, centrifugal blower assembly, high pressure switch, head  
pressure control valve, Lee-Temp receiver and liquid line solenoid valve. Unit must be mounted  
indoors. Duct flanges are optional.  
Water/Glycol Condensing Units  
Each water-cooled split system consists of an evaporator section and a water/glycol condensing unit,  
which includes scroll compressor, coaxial condenser, water regulating valve, and high pressure switch.  
Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) as optional.  
Each glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (as  
described above), a pump package and a 95°F (35°C) design ambient drycooler.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation  
2.0 INSTALLATION  
2.1  
Room Preparation  
The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the  
ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors.  
Doors should not be undercut or have grilles in them.  
Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating, cool-  
ing, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept  
below 5% of the total air circulated in the room and be preconditioned.  
2.2  
2.3  
Equipment Inspection  
Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be imme-  
diately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales  
representative.  
Location Considerations  
The Liebert Challenger ITR can sit on top of an accessible elevated flooring system. It may be neces-  
sary to furnish additional pedestal support below the unit to ensure maximum structural support (see  
Table 1). A separate floor stand for the unit may be used as support, independent of the elevated floor  
and installed prior to the flooring system.  
Provide approximately 34" (864 mm) service clearance in the front and rear of the unit.  
The unit can be installed between equipment racks or at the end of a row of racks. Consideration  
should be given before installing refrigerant and liquid lines next to, under or above electronic equip-  
ment. Avoid placing the Liebert Challenger ITR in an alcove. Placing units too close together will  
reduce the effectiveness of the air distribution.  
NOTE  
Locate and remove shipping screw on fan motor base.  
2.3.1 Remote Sensor Installation Location  
The remote temperature and humidity sensor should be installed in the cold aisle in front of the  
equipment to be cooled. It should be mounted at the farthest point from the cooling unit that supply  
air needs to reach but still within the unit's area of influence. The sensor should be installed at the  
highest point that equipment will draw in cooled air.  
2.4  
Equipment Handling  
WARNING  
!
Risk of equipment tipping over. Can cause damage, injury or death.  
The instructions listed below must be adhered to when handling this unit with or without the  
skid. There is the potential for this unit to tip over if handled improperly.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Installation  
2.4.1 Handling With Skid  
• Always keep the Liebert Challenger ITR upright, indoors and protected from damage.  
• Do not use the extended rear door frame to lift the unit.  
• If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables, avoid-  
ing pressing on the top edges of the packaging.  
• If using a fork lift, make sure that the forks, if adjustable, are spread to the widest allowable dis-  
tance to still fit under the skid.  
NOTICE  
Do not attempt to lift the Liebert Challenger ITR with the extended rear door frame.  
Attempting to do so will damage the unit. Lift the unit only from its main base.  
NOTICE  
While on the skid, the Liebert Challenger ITR is too tall to fit through a standard height  
doorway (83 inches or 2108 mm tall). Any attempt to move the unit, while on the skid,  
through a standard doorway will damage the unit.  
2.4.2 Removal of Skid  
1. Remove the plywood skirting that keeps the skid and unit in place.  
2. Raise the Liebert Challenger ITR off the skid. Liebert recommends using a fork lift (see Figure 1)  
or similar machine to ensure that the unit is lifted properly.  
NOTE  
Lift the Liebert Challenger ITR only from its main base. Do not use the extended rear door  
frame to lift the unit.  
3. Once the unit is raised, the skid can be removed.  
Figure 1 Removing Liebert Challenger ITR from skid  
Remove plywood skirting holding  
unit and skid in place.  
Raise unit with fork lift  
or similar machine.  
Table 1  
Model  
Unit shipping weights  
Domestic  
lb (kg)  
Export  
lb (kg)  
Domestic  
lb (kg)  
Export  
lb (kg)  
Model  
BR060E  
50Hz Models  
650 (295)  
745 (340)  
815 (370)  
855 (390)  
660 (300)  
60Hz Models  
650 (295)  
745 (340)  
815 (370)  
855 (390)  
660 (300)  
BR059E  
BR065A  
BR070WG  
BM058G  
BR101C  
750 (340)  
845 (385)  
915 (415)  
955 (435)  
760 (345)  
750 (340)  
845 (385)  
915 (415)  
955 (435)  
760 (345)  
BR067A  
BR071WG  
BM061G  
BR102C  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
Figure 2 Cabinet dimensions  
Unit Weight  
50 Hz Models  
BR059E  
60 Hz Models  
BR060E  
lb. (kg)  
649 (294)  
744 (337)  
814 (369)  
659 (299)  
854 (387)  
BR065A  
BR067A  
30-1/2"  
(775mm)  
BR070WG  
BR101C  
BR071WG  
BR102C  
31-1/2"  
UNIT  
(800mm)  
11-3/4"  
(298mm)  
TOP VIEW  
8-1/2"  
(216mm)  
BM058G  
BM061G  
9-5/8"  
(244mm)  
10-1/4"  
(260mm)  
1-5/8"  
(41mm)  
13"  
(330mm)  
43-5/16"  
(1100mm)  
30-1/2"  
(775mm)  
Standard Piping Location  
32-1/2"  
(826mm)  
12-1/2"  
(318mm)  
1-7/8"  
(48mm)  
5/8"  
(16mm)  
Projection of  
Display Bezel  
12-5/8"  
(321mm)  
Standard Electrical Outlet  
Location Through Unit  
5-1/2"  
(140mm)  
Plenum Overhang  
32-1/2"  
(826mm)  
45-1/8"  
(1147mm)  
15-1/16"  
(382mm)  
32-1/2"  
(826mm)  
Discharge Air Opening  
Remove Blocker Panel  
for Air Discharge Left  
and/or Right Side Panels  
Filter Access  
by Opening Door  
91-1/16"  
(2313mm)  
Shaded area indicates  
a recommended  
clearance of 34" (864mm)  
for component access  
Blower Outlet with  
1" (25.4mm) Flange  
76"  
(1930mm)  
7/8" (22.2mm) Flange for  
Duct or Plenum Connection  
UNIT DIMENSIONAL DATA  
REAR VIEW  
Shaded area indicates a recommended  
clearance of 34" (864mm) for component access  
UNIT DIMENSIONAL DATA  
FRONT VIEW  
DPN001523  
Pg. 2, Rev. 1  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Figure 3 Optional floor stand dimensions  
1"  
(25.4mm)  
30-1/2"  
(775mm)  
30-1/2"  
(775mm)  
See Specification Sheet  
for height of floor stand ordered.  
SL-11897  
Pg. 7  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
2.5  
Piping Considerations  
Consideration should be given before installing refrigerant and liquid lines next to, under or above  
electronic equipment.  
2.5.1 Drain Line  
A 3/4" (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate  
drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will  
not be exposed to freezing temperatures. The drain should be at least the full size of the drain connec-  
tion and pitched a minimum of 1/8" per ft. (11 mm per meter).  
NOTE  
This line may contain boiling water. Select appropriate drain system materials.  
The Challenger ITR comes standard with a condensate pump will require a field-supplied trap  
downstream from the pump. The drain line must comply with all applicable codes.  
Table 2  
Piping connection size  
Air-Cooled Unit Connection Sizes—in.  
Model No. BR/BM  
60Hz (50Hz)  
Liquid Line O.D. Copper  
Hot Gas Line O.D. Copper  
HG  
L
067A (065A)  
1/2  
7/8  
Split System Fan Coil Unit Connection Sizes—in.  
Model No. BR/BM  
60Hz (50 Hz)  
Liquid Line  
L
Suction Line  
SC  
060E (059E)  
1/2 O.D. Cu  
1-1/8 O.D. Cu  
All Units: Connection Sizes—in.  
Humidifier Line  
O.D. Copper  
H
Condensate  
Drain Line  
C
Condensate Pump Line  
Hot Water Reheat  
O.D. Copper  
O.D. Copper  
P
Supply HWS  
5/8  
Return HWR  
5/8  
1/4  
1/2 OD Cu  
1/2  
Water/Glycol-Cooled Unit Connection Sizes—in.  
Model No. BR/BM  
60Hz (50 Hz)  
Supply Line  
S
Return Line  
R
071WG (070WG)  
1-1/8  
1-1/8  
GLYCOOL Unit Connection Sizes —in.  
Model No. BR/BM  
60Hz (50 Hz)  
Supply Line  
S
Return Line  
R
061G (058G)  
1-1/8  
1-1/8  
Chilled Water Unit Connection Sizes—in.  
Model No. BR/BM  
60Hz (50 Hz)  
Supply Line  
CWS  
Return Line  
CWR  
102C (101C)  
1-1/8  
1-1/8  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
Figure 4 Piping connections for air-cooled units  
Piping outlet locations through the  
plenum are the same as the unit.  
See below for descriptions and  
connection sizes.  
Hot Water Return  
5/8" OD CU (optional)  
Humidifier Water  
Supply Line 1/4" OD CU  
Hot Gas Refrigerant Line  
7/8" OD CU on Models  
BR067A/BR065A  
Liquid Refrigerant Line  
1/2" OD CU on Models BR067A/BR065A  
Condensate Pump  
Line 1/2" OD CU  
Hot Water Supply  
5/8" OD CU (optional)  
Monitoring Panel  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
DPN001525  
REV 0  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Figure 5 Piping connections for split system fan coil units  
Piping outlet locations through the  
plenum are the same as the unit.  
See below for descriptions and  
connection sizes.  
Hot Water Return  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
Suction Refrigerant Line  
1 1/8" OD CU on  
Models BR060E/BR059E  
Liquid Refrigerant Line  
1/2" OD CU on Models  
BR060E/BR059E  
Condensate Pump Line  
1/2" OD CU  
Hot Water Supply  
5/8" OD CU (optional)  
Monitoring Panel  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
DPN001534  
REV 0  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Figure 6 Piping connections for water/glycol and GLYCOOL units  
Piping outlet locations through the  
plenum are the same as the unit.  
See below for descriptions and  
connection sizes.  
Hot Water Return  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
Condenser Supply Line  
1-1/8" OD CU on  
Models BR071WG/BR070WG  
Condenser Return Line  
1 1/8" OD CU on  
Models BR071WG/BR070WG  
Hot Water Supply  
5/8" OD CU (optional)  
Condensate Pump Line  
1/2" OD CU  
Monitoring Panel  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
DPN001528  
REV 0  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Figure 7 Piping connections for chilled water self-contained units  
Piping outlet locations through  
the plenum are the same as the  
unit. See below for descriptions  
and connection sizes.  
Humidifier Water Supply  
Line 1/4" OD CU  
Hot Water Return  
5/8" OD CU (optional)  
Chilled Water Supply Line  
1-1/8" OD CU  
Chilled Water Return Line  
1-1/8" OD CU  
Condensate Pump Line  
1/2" OD CU  
Hot Water Supply  
5/8" OD CU (optional)  
Monitoring Panel  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
DPN001531  
REV 0  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
2.6  
Electrical Connections  
Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or  
200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes.  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-  
trical schematic when making connections.  
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the Liebert Chal-  
lenger ITR in accordance with codes. A factory-supplied, locking disconnect switch is factory-mounted  
within the unit behind the front door.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power before working within the unit. Use a voltmeter  
to make sure power is turned off before making any electrical connections.  
NOTICE  
Three-phase power must be connected to the Liebert Challenger ITR line voltage terminals in  
the proper sequence so that scroll the compressor rotates in the proper direction.  
Figure 8 Electrical connections  
1
Electrical Handy Box*  
(factory-installed with cover)  
15  
70  
71  
2
3
4
7
1
5
6
Terminal Block*  
(for customer connections)  
12  
10  
13  
16  
11  
8
9
13  
8
14  
17  
9
38B  
2
3
37C 38C 37B  
37 38  
24 50 51 55 56  
77 78  
75 76 82 83 84 85 88 89 91 92 93 94 95 96 97  
1
4
DPN001524  
REV 0  
1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm).  
2. Three phase connection. Electric service connection terminals when factory disconnect switch  
is supplied.  
3. Factory-installed locking disconnect switch.  
4. Three-phase electric service not by Liebert.  
5. Earth ground connection (50/60Hz). Connection terminal for field-supplied earth grounding wire.  
6. Earth ground bar (50Hz only). Connection terminals with factory ground from each high  
voltage component for field supplied earth grounding wire.  
7. Control and monitoring section of electric box.  
8. Remote unit shutdown. Replace existing jumper between Terminals 37 + 38 with normally  
closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two  
additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace  
existing jumper for appropriate pair as done for 37 & 38.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation  
9. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection  
made by adding normally open contacts between terminals 24 + 50. Optional additional  
connections available with Advanced or Advanced with Graphics controls and appropriate  
optional accessories (connections 51, 55, and 56).  
®
10. Liebert SiteScan connection. Terminals 77 (-) and 78 (+) are for connection of a 2-wire, twisted  
pair, communication cable (available from Liebert or others) to optional Liebert SiteScan.  
11. Remote condensing unit connection. Field-supplied 24V Class 1 wiring to remote condensing  
unit terminals 1, 2, 3, & 4 from (R2) relay (split system only).  
12. Smoke detector alarm connections. Field-supplied 24V Class 1 wiring to remote alarm circuits.  
Factory-wired contacts from optional smoke detector are #91-comm., #92-NO, and #93-NC.  
13. Common alarm connection. Field-supplied 24V Class 1 wiring to common alarm terminals 75 + 76  
(and optional 94 + 95, and 96 + 97), which are factory-connected to common alarm relay (R3).  
14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier:  
connections provided for remote 24V AC source.  
15. Heat rejection connection. Field-supplied 24V Class 1 wiring to interlock heat rejection from  
pigtails 70 + 71 which are factory-connected to compressor side switch (self-contained units only  
and to Glycool relay (R5), Glycool units only).  
16. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field  
wiring compartment for remote indication that the evaporator fan motor/unit is on. Field to  
connect 24V maximum.  
17. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in field  
wiring compartment for remote indication.  
*Located inside Liebert Challenger ITR on top.  
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.  
2.7  
Balancing the Air Distribution  
2.7.1 Ducted Applications  
For ducted applications, the duct work may be attached to the top perimeter of the Liebert Challenger  
ITR (see Figure 2).  
The duct work must allow access to the motors/blowers for maintenance. The duct work must be  
designed within the capacity of the Liebert Challenger ITR, otherwise air flow and performance will  
be compromised.  
2.7.2 Plenum Installation  
A solid plenum or plenum with discharge grille(s) may be installed. The plenum and instructions for  
its installation ship separately from the Liebert Challenger ITR.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
2.8  
Checklist for Completed Installation  
___ 1. Unpack and check received material.  
___ 2. Proper clearance for service access has been maintained around the equipment.  
___ 3. Equipment is level and mounting fasteners are tight.  
___ 4. Piping completed to refrigerant or coolant loop (if required). Piping has been leak checked,  
evacuated and charged (if required).  
___ 5. Check piping within the Liebert Challenger ITR and outside of the unit. Remove potential of  
rub-through or chaffing.  
___ 6. Condensate pump installed.  
___ 7. Drain line connected.  
___ 8. Water supply line connected to humidifier (if required).  
___ 9. Field provided pan with drain installed under all ceiling mounted fluid condensing units (if  
installed).  
___ 10. Ducting completed (if applicable).  
___ 11. Filter(s) installed.  
___ 12. Line voltage to power wiring matches equipment serial tag.  
___ 13. Power wiring connections completed between disconnect switch, evaporator and condensing  
unit, including earth ground.  
___ 14. Power line circuit breakers or fuses have proper ratings for equipment installed.  
___ 15. Control wiring connections completed to evaporator and condensing unit.  
___ 16. Verify water detection is properly installed around all units (if installed).  
___ 17. All wiring connections are tight.  
___ 18. Control panel DIP switches set based on customer requirements.  
___ 19. Foreign materials have been removed from, in and around all equipment installed (literature,  
shipping materials, construction materials, tools, etc.).  
___ 20. Fans and blowers rotate freely.  
___ 21. Inspect all piping connections for leaks during initial operations. Correct as needed.  
___ 22. Verify that a blank start-up sheet has been sent with the unit(s) and is ready to be completed  
by the installer.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Air-Cooled Models  
3.0 AIR-COOLED MODELS  
3.1 Condenser Location  
The air-cooled condenser should be located for maximum security and maintenance accessibility.  
Avoid ground level sites with public access or areas that contribute to heavy snow or ice accumula-  
tions. Utilize centrifugal condensers whenever interior building locations must by used. To assure  
adequate air supply, it is recommended that condensers be located in a clean air area, away from  
loose dirt and foreign matter that may clog the coil. In addition, condensers should not be located in  
the vicinity of steam, hot air, or fume exhausts. Also, condensers should be located no closer than  
three feet (1 meter) from a wall, obstruction, or adjacent unit.  
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof instal-  
lation, mount condensers on steel supports in accordance with local codes. To minimize sound and  
vibration transmission, mount steel supports across load bearing walls. For ground installation, a  
concrete pad will provide adequate support. Condenser legs have mounting holes for securing the con-  
denser to the steel supports or concrete pad.  
3.2  
Electrical Connections  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-  
trical schematic when making connections. Make all wiring and electrical connection in accordance  
with local and national codes.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power before working within the unit. Use a voltmeter  
to make sure power is turned off before making any electrical connections.  
3.2.1 Line Voltage  
Line voltage electrical service is required for all air-cooled condensers at the location of the condenser.  
This power supply does not have to be the same voltage as the indoor unit. This separate power source  
may be 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch may be  
factory-supplied and mounted in the electrical panel or field-supplied and mounted per local and  
national codes.  
3.2.2 Low Voltage  
A control interlock between the condenser and the indoor unit is required and is connected between  
70 and 71 in the handy box of the indoor unit and the electric panel of the air-cooled condenser. NEC  
Class 1 wiring is required.  
3.2.3 Lee-Temp/Flood Back Head Pressure Control Condensers  
Lee-Temp condensers require a separate power supply for the heated receivers. This power supply is  
connected to the electrical connection box on the end of the receiver.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Air-Cooled Models  
Figure 9 Air-cooled condensers  
FAN SPEED CONDENSER  
LEE-TEMP CONDENSER  
* B  
Lee-Temp heater pad  
connection box  
Hot gas  
line  
Electric service  
supplied by  
others  
* B  
Electric  
service  
supplied by  
others  
Liquid line  
Hot gas line  
*B - Inverted traps are to be field-supplied and installed  
(typ). When installing traps, provide clearance for swing  
end of access door. Traps are to extend above base of  
coil by a minimum of 7-1/2" (190 mm)  
Liquid line  
Secure each leg to condenser frame at all  
points shown using hardware provided.  
SINGLE FAN  
AIR-COOLED CONDENSERS  
43-9/16"  
(1106mm)  
51-7/16"  
(1306.5mm)  
18" (457.2mm)  
37-7/8"  
(962mm)  
CONDENSER MOUNTING  
1" typ.  
(25.4mm)  
1-3/4"  
(44.5mm)  
43-3/16"  
44"  
(1097mm)  
(1118mm)  
9/16" (14.3mm)  
diameter holes  
8 places for  
1/2" (12.7mm)  
diameter bolts  
1" typ.  
(25.4mm)  
37-11/16"  
(957.3mm)  
1"  
1-3/4"  
4-1/4"  
(25.4mm) (44.5mm) (108mm)  
1-3/4"  
(44.5mm)  
1-3/4"  
(44.5mm)  
1-3/4"  
(44.5mm)  
4-1/4"  
(108mm)  
1"  
A
(25.4mm)  
Common to all models. See Table 3  
below for key to “A” dimension.  
TYPICAL FOOTPRINT  
Table 3  
Air-cooled condenser statistics  
Connection Sizes  
(OD Copper)  
Number  
of Fans  
Net Weight  
lb (kg)  
“A” Dimension  
in (mm)  
Model  
083  
Hot Gas (in.)  
7/8  
Liquid (in.)  
1
1
5/8  
5/8  
295 (133.8)  
315 (142.8)  
42 (1067)  
42 (1067)  
104  
1-1/8  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Air-Cooled Models  
3.3  
Refrigerant Piping  
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good  
refrigeration practices should be employed for piping supports, leak testing, dehydration and charg-  
ing of the refrigeration circuits.  
Unit refrigeration components and piping are shipped from the factory with a nitrogen holding  
charge.  
NOTE  
The refrigeration piping should be isolated from the building by the use of vibration isolating  
supports.  
NOTE  
Piping, including inverted trap(s), must be routed to allow unobstructed access to the panel  
per the NEC.  
NOTE  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand  
open to air for more than 15 minutes. Units designed for R407C have a compressor that  
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The  
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left  
open too long, the POE oil may need to be replaced before achieving the required vacuum level.  
NOTE  
Keep the evaporator unit and condenser closed with their factory charge of dry nitrogen while  
all field piping is installed. Keep the field piping clean and dry during installation, and do not  
allow it to stand open to the atmosphere. When all the field interconnecting piping is in place,  
vent the condenser dry nitrogen charge and connect to the field piping. Finally, vent the  
evaporator unit dry nitrogen charge and make its piping connections last.  
Follow all proper brazing practices including a dry nitrogen purge to maintain system  
cleanliness.  
Traps should be installed in the hot gas line on vertical risers at the base and every 25 feet (7.6  
meters) in elevation. These traps will collect condensed refrigerant and refrigerant oil during the off  
cycle of the unit and ensure flow of refrigerant oil during operation.  
A check valve is factory-supplied with the unit to be field-installed on the discharge side of the scroll  
compressor. Be sure to install the check valve with the refrigerant flow in the proper direction. When  
soldering or brazing the valve, it is very important to protect the internal parts by wrapping the valve  
with a damp cloth to keep the valve temperature below 250°F (121°C).  
Approval is required whenever:  
• a refrigerant piping run exceeds 150 ft. (46 m) equivalent length  
• an R22 system condenser must be located more than 15 ft. (4.6 m) below the level of the cooling  
coil  
• an R407C system condenser must be located below the level of the cooling coil.  
Total discharge line pressure drop must not exceed 10 PSIG (69 kPa).  
Consult your local Liebert representative when considering installations outside these guidelines.  
Table 4  
Recommended line sizes — OD copper (inches)*  
23 & 33 kW 067A (065A)  
Equivalent Length Hot Gas Line Liquid Line  
50 ft. (15 m)  
100 ft. (30 m)  
150 ft. (45 m)  
7/8  
7/8  
7/8  
1/2  
5/8  
5/8  
*Recommended vertical line sizes must be used for proper oil return at all cooling and dehumidification steps.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Air-Cooled Models  
Table 5  
Equivalent lengths (feet) for various pipe fittings  
Copper Pipe  
O.D. in.  
90 Degree  
Elbow Copper Elbow Cast  
90 Degree  
45 Degree  
Elbow  
Gate  
Tee Valve  
Globe Angle  
Valve  
Valve  
1/2  
5/8  
0.8  
0.9  
1.3  
1.4  
1.5  
1.8  
2.2  
2.9  
3.5  
0.4  
0.5  
0.6  
0.8  
1.0  
1.3  
1.6  
2.5  
2.5  
2.5  
3.6  
4.6  
6.4  
7.2  
0.26  
0.28  
0.3  
7.0  
4.0  
5.0  
9.5  
3/4  
1.0  
12.0  
17.2  
22.5  
32.0  
36.0  
6.5  
7/8  
1.45  
1.85  
2.4  
0.36  
0.48  
0.65  
0.72  
9.5  
1-1/8  
1-3/8  
1-5/8  
12.0  
16.0  
19.5  
2.9  
Refrigerant trap = 4 times equivalent length of pipe per this table.  
Table 6  
Indoor unit refrigerant charge lb (kg) R22 or R407C (per unit serial tag)  
R22  
R407C  
Approximate Charge  
lb (kg)  
Approximate Charge  
lb (kg)  
Model  
67A/65A  
1.5 (0.68)  
1.4 (0.6)  
Table 7  
Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube  
R22 R407C  
Hot Gas Line  
Liquid Line  
lb (kg)  
Liquid Line  
Hot Gas Line  
lb (kg)  
O.D.  
lbs (kg)  
lb (kg)  
1/2"  
5/8"  
3/4"  
7/8"  
7.3 (3.3)  
11.7 (5.3)  
16.6 (7.5)  
24.4 (11.1)  
1.3 (0.6)  
2.1 (1.0)  
3.0 (1.4)  
4.4 (2.0)  
6.9 (2.9)  
11.0 (4.6)  
15.7 (6.5)  
23.0 (9.6)  
-
2.2 (0.9)  
3.1 (1.3)  
4.5 (1.9)  
Table 8  
Condenser refrigerant (per serial tag)  
R22  
R407C  
Approximate Charge  
lb (kg)  
Approximate Charge  
lb (kg)  
Model  
Fan Speed  
Lee-Temp*  
Fan Speed  
Lee-Temp*  
083  
104  
5 (2.27)  
8 (3.63)  
27 (12.3)  
39 (17.7)  
8 (3)  
9 (4)  
25 (12)  
37 (17)  
* Charge includes the receiver charge.  
3.4  
Fan Speed Control Systems  
Fan Speed Control provides an infinite number of speed variations on specially designed, permanent  
split-capacitor motors. The control module varies the air quantity passing over the condenser coil by  
monitoring refrigerant pressure.  
3.4.1 Materials Supplied  
1. Built-in pre-wired condenser control box  
2. Air-cooled condenser  
3. Piping access cover to be reinstalled when piping is complete  
4. Bolts (four per leg) 3/8" x 5/8"  
5. Terminal block for two-wire, 24-volt interlock connection between unit and condenser  
6. Condenser legs, four on one-fan models  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Air-Cooled Models  
3.4.2 Dehydration/Leak Test and Charging Procedures for R22 (standard) or R407C (Optional)  
Fan Speed Control Type Condenser  
CAUTION  
!
All local codes for handling refrigerant must be followed.  
NOTE  
As R22 and R407C are similar in properties, proper safety equipment and proper  
refrigeration tools are required on both types. Check unit nameplate for correct refrigerant  
type before topping off or recharging a system.  
NOTE  
Refrigerant R407C uses a POE (polyol ester) lubricant. The R407C refrigerant must be  
introduced and charged from the cylinder only as a liquid.  
NOTE  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand  
open to air for more than 15 minutes. Units designed for R407C have a compressor which  
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The  
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left  
open too long, the POE oil may need to be replaced before achieving the required vacuum level.  
Dehydration/Leak Test  
1. Make sure unit is OFF. Open all disconnects and remove all fuses except control fuses. On units  
supplied with circuit breakers, open all breakers except for the transformer.  
2. Add a jumper to the Fan Safety Switch between Common and Normal Open and disconnect the  
wire connected to the Normally Closed. Turn unit disconnect ON. (Fan operation not required.)  
NOTE  
The above allows the technician to use unit 24 VAC power and controls to open liquid line  
solenoid valve(s) and hot gas bypass solenoid valve(s) for the dehydration process. If no  
power is at the unit disconnect, the technician is to use a separate 24 VAC source rated at  
75 VA and connect to the system liquid line solenoid valve(s) and hot gas bypass solenoid  
valve(s) directly.  
3. Connect refrigeration gauges to the suction and discharge service valves of the compressor. Open  
all compressor service valves.  
4. To energize the liquid line solenoid valves through the control system power, set the control  
temperature setpoint (see operation manual) to 60°F (15°C) and set the % relative humidity  
setpoint higher than the conditioned room ambient to ensure that solenoid valves and hot gas  
bypass valves are open during the dehydration process.  
5. Pressurize the system circuit(s) to 150 PSIG (1034 kPa) by using dry nitrogen with a trace of  
refrigerant. Check system for leaks with suitable leak finder.  
6. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum  
on the system with a suitable pump.  
7. After four hours, check the pressure readings, and if they have not changed, break vacuum with  
refrigerant. Pull another vacuum to 250 microns or less. Recheck the pressure after two hours.  
After completing this step, pressurize the circuits with refrigerant (R407C liquid or R22 vapor per  
unit nameplate) until suction and discharge pressures have equalized.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Air-Cooled Models  
Figure 10 Air-cooled fan speed control general arrangement  
Condenser  
Coil  
Schrader  
Valve  
Fusible  
Plug  
Inverted Traps* on discharge  
and return lines to extend  
above base of coil by a  
minimum of 7 1/2" (190mm)  
Evaporator  
Coil  
Traps* every  
25 ft. (7.6m)  
of rise  
Hot Gas  
Bypass  
Valve  
Expansion  
Valve  
Liquid Return  
Solenoid  
Valves  
Sensing  
Bulb  
Sight  
Glass  
Shutoff *  
Valve  
Filter  
Dryer  
External  
Equalizers  
Service  
Valves  
Hot Gas  
Bypass  
Scroll  
Compressor  
Check Valve  
(Shipped Loose for  
Field Installation)  
Hot Gas  
Discharge  
SINGLE CIRCUIT SHOWN  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
FACTORY  
PIPING  
FIELD  
SL-11897 PG 5  
PIPING  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Air-Cooled Models  
3.4.3 Charging  
1. Make sure unit is OFF. Open all disconnect switches and, on units supplied with circuit breakers,  
open all breakers. Replace all fuses for the Fan and Compressors or close breakers.  
2. Remove jumper on the Fan Safety Switch and reconnect the system wire connections. Ensure that  
all operational components are clear of debris. Turn unit ON. (Fan operation is required.) Check  
the evaporator fan for proper rotation and correct if necessary.  
3. Connect the refrigerant gauge charging hose to the drum of refrigerant and to the suction and  
discharge service valves of the compressor.  
4. Calculate the amount of charge for the system. Weigh in as much of the system charge as  
possible. Refer to the unit, condenser and refrigerant line charge tables.  
5. Set the control temperature setpoint (see operation manual) to 60°F (15°C) and set the % relative  
humidity setpoint higher than the conditioned room ambient to ensure that solenoid valves and  
hot gas bypass valves are open during the charging procedure. You may have to bypass the  
LP Switch (low pressure switch) to start the compressors and stop short cycling. Reset the Head  
Pressure switch(es) if open.  
6. Add refrigerant (R407C liquid, or R22 vapor per unit nameplate) to the suction side of the  
compressor until there is sufficient pressure to energize the low-pressure switch.  
NOTE  
When adding refrigerant to an operating system, it may be necessary to add the refrigerant  
through the compressor suction service valve. Because the refrigerant leaving the  
refrigerant cylinder must be in a liquid state, care must be exercised to avoid damage to the  
compressor. It is suggested that a sight glass be connected between the charging hose and  
the compressor suction service valve. This will permit adjustment of the cylinder hand  
valve so that liquid can leave the cylinder while allowing vapor to enter the compressor.  
Then you may remove the manual bypass you applied earlier.  
7. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound of  
refrigerant.  
8. As head pressure builds, the condenser fan starts rotating. The fan becomes fully energized when  
sufficient head pressure is developed. (Fan starts to rotate at 190 psi and is full speed at 250 psi.)  
Table 9  
Refrigerant control settings psi (kPa)  
Low Pressure  
Cut Out  
Low Pressure  
Cut In  
High Pressure  
Cut Out  
20 (137.9)  
65 (448.2)  
360 (2482)  
3.5  
Lee-Temp/Flood Back Head Pressure Control Systems  
The Lee-Temp system consists of a modulating type head pressure control valve and insulated  
receiver with heater pad to ensure operation at ambient temperatures as low as -30°F (-34.4°C).  
3.5.1 Piping  
Lee-Temp systems have two factory-supplied, field-installed check valves: one on the discharge side of  
the scroll compressor and one on the inlet side of the receiver. Be sure to install the check valves with  
the refrigerant flow in the proper direction. When soldering or brazing the valves, it is very important  
that the internal parts be protected by wrapping the valve with a damp cloth to keep the valve tem-  
perature below 250°F (121°C).  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Air-Cooled Models  
3.5.2 Materials Supplied  
1. Built-in pre-wired condenser control box  
2. Air-cooled condenser  
3. Piping access cover to be reinstalled when piping is complete  
4. Bolts (four per leg) 3/8" x 5/8"  
5. Terminal block for two-wire 24V interlock connection between the unit and the condenser  
6. Condenser legs: four on one-fan models  
7. Lee-Temp system:  
a. Insulated storage receiver  
b. Head pressure control valve with integral check valve  
c. Adapter assembly  
d. Rotalock valve  
e. Pressure relief valve  
f. Liquid level sight glass  
g. Check valve  
8. Bolts - (six per receiver) 3/8" x 1"  
NOTE  
Lee-Temp heater pad requires a separate, continuous electrical source of either 115 VAC or  
200/208/230 VAC.  
3.5.3 Dehydration/Leak Test and Charging Procedures for R22 (Standard) or R407C (Optional)  
Lee-Temp Control Type Condenser  
CAUTION  
!
All local codes for handling refrigerant must be followed.  
NOTE  
As R22 and R407C are similar in properties, proper safety equipment and proper refrigeration  
tools are required on both types. Check unit nameplate for correct refrigerant type and oil type  
before topping off or recharging a system.  
NOTE  
Refrigerant R407C uses a POE (polyol ester) lubricant. The R407C refrigerant must be  
introduced and charged from the cylinder only as a liquid.  
NOTE  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand  
open to air for more than 15 minutes. Units designed for R407C have a compressor which  
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The  
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left  
open too long, the POE oil may need to be replaced before achieving the required vacuum level.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Air-Cooled Models  
Dehydration/Leak Test  
1. Make sure unit is OFF. Open all disconnect switches and pull all fuses except control fuses. On  
units supplied with circuit breakers, open all breakers except for the transformer.  
2. Add a jumper to the Fan Safety Switch between Common and Normal Open and disconnect the  
wire connected to the Normally Closed. Turn unit disconnect ON. (Fan operation not required.)  
NOTE  
The above allows the technician to use unit 24 VAC power and controls to open liquid line  
solenoid valve(s) and hot gas bypass solenoid valve(s) for the dehydration process. If no power  
is at the unit disconnect, the technician is to use a separate 24 VAC source rated at 75 VA and  
connect to the system liquid line solenoid valve(s) and hot gas bypass solenoid valve(s) directly.  
3. Connect refrigeration gauges to the suction and discharge service valves of the compressor and open.  
4. Attach a “jumper” hose from the Rotalock fitting on the outlet of the receiver and the Schrader fitting  
on the liquid header of the condenser. Front seat the Rotalock valve approximately two turns.  
5. To energize the liquid line solenoid valve(s) through the control system, set the temperature  
setpoint (see operation manual) to 60°F (15°C) and set the % relative humidity setpoint higher  
than the conditioned room ambient to ensure that solenoid valves and hot gas bypass valves are  
open during the dehydration process.  
6. Pressurize system circuit(s) to 150 PSIG (1034 kPa) by using dry nitrogen with a trace of  
refrigerant. Check system for leaks with suitable leak finder.  
7. After completion of leak testing, release test pressure (per local code) and pull a vacuum on the  
system.  
8. After 4 hours, check pressure readings and, if they have not changed, break vacuum with  
refrigerant. Pull a second and third vacuum of 250 microns or less. Recheck pressure after  
2 hours.  
3.5.4 Charging  
1. Make sure unit is OFF. Open all disconnect switches and, on units supplied with circuit breakers,  
open all breakers. Replace all fuses for the Fan and Compressors or close breakers.  
2. Remove jumper on the Fan Safety Switch and reconnect the system wire connections. Ensure that  
all operational components are clear of debris. Turn unit ON. (Fan operation is required.) Check  
the evaporator fan for proper rotation and correct if necessary.  
3. Connect the refrigerant gauge charging hose to the drum of refrigerant and to the suction and  
discharge service valves of the compressor(s).  
4. Calculate the amount of charge for the system. Weigh in as much of the system charge as  
possible. Refer to the unit, condenser and refrigerant line charge tables.  
5. Set the control temperature setpoint (see operation manual) to 60°F (15°C) and set the % relative  
humidity setpoint higher than the conditioned room ambient to ensure that solenoid valves and  
hot gas bypass valves are open during the charging procedure. You may have to bypass the  
LP Switch (low pressure switch) to start the compressors and stop short cycling. Reset the Head  
Pressure switch(es) if open.  
6. Add refrigerant (R407C liquid or R22 vapor per unit nameplate) to the suction side of the  
compressor until there is sufficient pressure to energize the low pressure switch.  
NOTE  
When adding refrigerant to an operating system, it may be necessary to add the refrigerant  
through the compressor suction service valve. Because the refrigerant leaving the  
refrigerant cylinder must be in a liquid state, care must be exercised to avoid damage to the  
compressor. It is suggested that a sight glass be connected between the charging hose and  
the compressor suction service valve. This will permit adjustment of the cylinder hand  
valve so that liquid can leave the cylinder while allowing vapor to enter the compressor.  
Then you may remove the manual bypass you applied earlier.  
7. Charge the unit until the proper charge is weighed in.  
Table 10 Refrigerant control settings psi (kPa)  
Low Pressure Cut Out  
Low Pressure Cut In  
High Pressure Cut Out  
20 (137.9)  
65 (448.2)  
360 (2482)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Air-Cooled Models  
Figure 11 Air-cooled, Lee-Temp general arrangement  
InvertedTrap * on  
discharge line to  
extend abovebase  
of coil by a  
CondenserCoil  
minimum of 71/2"  
(190mm)  
PipingAssembly* *  
Rotalock Valve **  
Check Valve  
Head Pressure  
Control with  
IntegralCheck  
Valve  
1/4" ( 6.4mm)  
PressureRelief  
Valve * *  
Lee-Temp  
Receiver  
Sight Glass  
Evaporator Coil  
Traps * Every  
25 Ft. (7.6m)  
of rise onHot  
Gas Line only  
Liquid Return  
from Condenser  
Expansion Valve  
Hot Gas  
Bypass  
Valve  
Solenoid Valves  
Sight Glass  
SensingBulb  
Shutoff  
Valve *  
Filter Drier  
Liquid Return  
External Equalizers  
Service  
Valves  
Hot Gas  
Bypass  
Scroll Compressor  
SINGLE CIRCUIT SHOWN  
Check Valve* *  
FACTORY PIPING  
OPTIONAL PIPING  
FIELD PIPING  
Hot Gas Discharge  
* Components are not supplied by Liebert  
but arerecommended for proper  
circuit operatoi n and maintenance.  
* * Components supplied by Liebert  
SL-10061 PG 4 SL-10071 PG 4  
and mustbe field installed.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Water-Cooled Models  
4.0 WATER-COOLED MODELS  
4.1 Piping Considerations  
Manual shut-off valves should be installed at the supply and return lines of each unit. This will pro-  
vide for routine maintenance or emergency isolation of the unit.  
When the water source for the condenser is of poor quality, it is good practice to provide cleanable fil-  
ters in the supply line. These filters will trap the particles in the water supply and extend the service  
life of the water-cooled condenser.  
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains  
should be provided with wet traps or a water detection system such as a Liqui-tect sensor that is  
installed near the base of the unit or below the elevated floor.  
4.2  
Condenser  
The condenser is designed to operate in conjunction with either a cooling tower or city water. The  
maximum water pressure is 150 psig (1034 kPa). A high pressure system rated at 350 psig (2413 kPa)  
is available as an option.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Water-Cooled Models  
Figure 12 Water-cooled general arrangement  
Evaporator  
Coil  
Expansion  
Valve  
Sensing  
Bulb  
Sight  
Glass  
External  
Equalizers  
Hot Gas  
Bypass  
Valve  
Scroll  
Compressor  
Filter  
Drier  
Service  
Valves  
Hot Gas  
Bypass  
Solenoid  
Valve  
Hot Gas  
Bypass  
Tube  
in Tube  
Condenser  
Fluid  
Bypass  
Return  
Tube  
Valve  
From  
Unit  
in Tube  
Condenser  
Fluid  
Supply  
To  
Shutoff*  
Valves  
Unit  
2-Way Water  
Regulating  
Valve  
3-Way Water  
Regulating Valve  
(optional)  
Fluid  
Supply  
To  
Unit  
Fluid  
Return  
From  
Unit  
Hose Bibs*  
FACTORY  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
PIPING  
FIELD  
PIPING  
SL-11898 PG 5  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Water-Cooled Models  
4.3  
Water Regulating Valve  
The water regulating valve automatically regulates the amount of fluid necessary to remove the heat  
from the refrigeration system, permitting more fluid to flow when load conditions are high and less  
fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve  
seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.  
4.3.1 Water Regulating Valve Adjustment  
The Liebert Challenger ITR may be equipped with either a standard Johnson Controls valve, 150 psig  
(1034 kPa) or with a high-pressure Johnson Controls valve, 350 psig (2413 kPa).  
The valve may be adjusted with a standard refrigeration service valve wrench or screw driver.  
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure  
gauge indicates the desired setting.  
To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired set-  
ting is obtained.  
Figure 13 Johnson Controls valve adjustment  
Range  
spring  
Valve spring  
guide  
Range adjustment screw  
Top  
retainer  
Insert screwdrivers underneath  
the valve spring guide  
4.3.2 Water Regulating Valve Manual Flushing  
The valve may be flushed by inserting screwdrivers or similar tools under the opposing sides of the  
main spring and lifting. This action will open the valve seat and flush any dirt particles from the seat.  
If this fails, the valve must be disassembled for cleaning the seat.  
4.3.3 Testing Valve Function  
When the refrigeration system has been off for 10-15 minutes, the water flow should stop.  
Should the water continue to flow, the valve is either improperly adjusted or the pressure sensing  
capillary is not properly connected to the condenser.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Glycol/GLYCOOL-Cooled Models  
5.0 GLYCOL/GLYCOOL-COOLED MODELS  
5.1  
Drycooler Location  
The drycooler should be located for maximum security and maintenance accessibility. Avoid ground-  
level sites with public access or areas which contribute to heavy snow or ice accumulations. To assure  
adequate air supply, it is recommended that drycoolers be located in a clean air area, away from loose  
dirt and foreign matter that may clog the coil. In addition, drycoolers should not be located in the  
vicinity of steam, hot air or fume exhausts. Also, drycoolers should not be located closer than 3 feet  
(1 meter) from a wall, obstruction or adjacent unit.  
5.2  
5.3  
Drycooler Installation  
For roof installation, mount drycoolers on steel supports in accordance with local codes. To minimize  
sound and vibration transmission, mount steel supports across load bearing walls. For ground instal-  
lation, a concrete pad will provide adequate support. Drycooler legs have mounting holes for securing  
the drycooler to steel supports or concrete pad.  
Electrical Connections  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-  
trical schematic when making connections. Make all wiring and electrical connections in accordance  
with local and national codes.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power before working within the unit. Use a voltmeter  
to make sure power is turned off before making any electrical connections.  
5.3.1 Line Voltage  
Line voltage electrical service is required for all drycoolers at the location of the drycooler. This power  
supply does not have to be the same voltage as the indoor unit. This separate power source may be  
208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch is factory-sup-  
plied and mounted in the electric panel.  
5.3.2 Low Voltage  
A control interlock between the drycooler and the indoor unit is required and is connected between 70  
and 71 in the handy box of the indoor unit and the pump and drycooler control box of the drycooler.  
NEC Class 1 wiring is required.  
5.3.3 Pump and Drycooler  
All wiring to the pump and drycooler from the control box should be done in accordance with the elec-  
trical schematic on the inside lid of the drycooler control box and with local and national codes.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Glycol/GLYCOOL-Cooled Models  
5.4  
Glycol Piping  
NOTICE  
Galvanized pipe must not be used in or with systems or units that contain glycol. The  
phosphates in the inhibitor can react with the zinc in the galvanized pipe, precipitating an  
insoluble material that can eventually foul the system.  
To help prevent piping failures, supply and return lines must be supported in a way that  
keeps their weight from bearing on the piping of the unit, drycooler or pumps.  
To avoid the possibility of burst pipes, it is necessary to install a relief valve in the system.  
This valve may be obtained from the supplier as an option or obtained from another vendor.  
Fluid-cooled condensers have small internal flow passages. To avoid clogging and other  
resulting system operation problems, install a 16-20 mesh filter in the fluid supply line to the  
indoor unit. The filter should be located where it can be easily serviced or replaced.  
Do not install unit on open-loop systems. Debris carried by the fluid will clog the brazed plate  
condenser.  
It is recommended that manual service shut-off valves be installed at the supply and return connec-  
tions to each unit. This enables routine service and/or emergency isolation of the unit. In addition,  
multiple pump packages require a check valve at the discharge of each pump to prevent back flow  
through the standby pump(s).  
To facilitate filling, installation of hose bibs at the lowest point of the system is recommended.  
Consideration of the minimum glycol temperature to be supplied from the drycooler will determine if  
the need exists to insulate the glycol supply and return lines. Insulation will prevent condensation on  
the glycol lines in low ambient conditions.  
All fluid piping must comply with local codes. Care in sizing pipes will help reduce pumping power  
and operating costs.  
Table 11  
Room dew point temperatures  
Dry Bulb  
°F (°C)  
Wet Bulb  
°F (°C)  
Relative  
Humidity  
Dew Point*  
°F (°C)  
70 (21.1)  
70 (21.1)  
57.2 (14.0)  
58.5 (14.7)  
45  
50  
48.0 (8.9)  
50.5 (10.3)  
72 (22.2)  
72 (22.2)  
58.9 (24.9)  
60.0 (15.5)  
45  
50  
50.0 (10.0)  
52.4 (11.3)  
75 (23.8)  
75 (23.8)  
61.2 (16.2)  
62.5 (16.9)  
45  
50  
52.4 (11.3)  
55.0 (12.7)  
* Minimum glycol temperature before condensation will occur.  
5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices  
An expansion tank must be provided for expansion and contraction of the fluid due to temperature  
change in this closed system. Vents are required at system high points to vent trapped air when fill-  
ing the system. A relief valve is a also a necessary piping component.  
Depending on the complexity of the system, various other devices may be specified. Pressure gauges,  
flow switches, automatic air separator, tempering valves, standby pumps, sensors for electrical con-  
trols, and flow switches are just a few of these devices.  
NOTICE  
Immediately following the use of water for leak testing or system cleaning, charge the tested  
system with the proper percentage of glycol and water for the application’s coldest design  
ambient. Complete system drain-down cannot be assured, and equipment damage could  
result from freezing of residual water.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Glycol/GLYCOOL-Cooled Models  
5.5  
Filling Instructions  
5.5.1 Preparing the System for Filling  
It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping  
in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The  
system should be flushed thoroughly using a mild cleaning solution or high-quality water and then  
completely drained before charging with glycol. Cleaning new systems is just as important as clean-  
ing old ones. New systems can be coated with oil or a protective film; dirt and scale are also common.  
Any residual contaminants could adversely affect the heat transfer stability and performance of your  
system. In many cases, in both old and new systems, special cleaners are needed to remove scale, rust  
and hydrocarbon foulants from pipes, manifolds and passages. Clean heat transfer surfaces are  
important in maintaining the integrity of the heating/cooling system. For more information on clean-  
ers and degreasers, contact your sales representative. Follow the manufacturer's instructions when  
using these products.  
Calculate the internal volume of the system as closely as possible. See Table 12 and Table 14 for  
unit volumes. Use volume in Table 13 for glycol piping volumes.  
Table 12  
Indoor unit glycol volume approximate gallons (liters) max.  
Glycol-Cooled GLYCOOL  
Model (50 Hz)  
071WG/(070WG)  
061G/(058G)  
2.0 (7.5)  
4.0 (15.1)  
Table 13 Volume in standard Type “L” copper piping  
Diameter (in.)  
Outside  
Volume  
Inside  
0.123  
0.555  
0.666  
0.785  
1.025  
Gal/Ft L/M  
0.008 (0.01)  
0.012 (0.15)  
0.018 (0.22)  
0.025 (0.31)  
0.043 (0.53)  
1/2  
5/8  
3/4  
7/8  
1-1/8  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Glycol/GLYCOOL-Cooled Models  
5.5.2 Glycol Solutions  
NOTE  
Glycol solutions should be considered for protection of the coil. When it is not used, damage can  
occur from either freezing or corrosion from water.  
When considering the use of any glycol products in a particular application, you should review the lat-  
est Material Safety Data Sheets and ensure that the use you intend can be accomplished safely. For  
Material Safety Data Sheets and other product safety information, contact the supplier nearest you.  
Before handling any other products mentioned in the text, you should obtain available product safety  
information and take necessary steps to ensure safety of use.  
NOTICE  
When mishandled, glycol products pose a threat to the environment. Before using any glycol  
products, review the latest Material Safety Data Sheets and ensure that you can use the  
product safely.  
Glycol manufacturers request that the customer read, understand and comply with the  
information on the product packaging and in the current Material Safety Data Sheets. Make  
this information available to anyone responsible for operation, maintenance and repair of the  
drycooler and related equipment.  
No chemical should be used as or in a food, drug, medical device, or cosmetic, or in a product or pro-  
cess in which it may contact a food, drug, medical device, or cosmetic until the user has determined  
the suitability and legality of the use. Since government regulations and use conditions are subject to  
change, it is the user's responsibility to determine that this information is appropriate and suitable  
under current, applicable laws and regulations.  
NOTICE  
Automotive antifreeze is unacceptable and must NOT be used.  
Typical inhibited formula ethylene glycol and propylene glycol manufacturers and suppliers are  
Union Carbide (Ucartherm) or Dow Chemical (Dowtherm SR-1, Dowfrost). These glycols are supplied  
with corrosion inhibitors and do not contain a silicone anti-leak formula. Commercial ethylene glycol,  
when pure, is generally less corrosive to the common metals of construction than water itself. Aque-  
ous solutions of these glycols, however, assume the corrosivity of the water from which they are pre-  
pared and may become increasingly corrosive with use if not properly inhibited.  
There are two basic types of additives: corrosion inhibitors and environmental stabilizers. The corro-  
sion inhibitors function by forming a surface barrier that protects the metals from attack. Environ-  
mental stabilizers, while not corrosion inhibitors in the strictest sense of the word, decrease corrosion  
by stabilizing or favorably altering the overall environment. An alkaline buffer such as borax is a sim-  
ple example of an environmental stabilizer since its prime purpose is to maintain an alkaline condi-  
tion (pH above 7).  
The percentage of glycol to water must be determined by using the lowest design outdoor temperature  
in which the system is operating. Table 14 indicates the solution freeze point at several concentra-  
tion levels of ethylene glycol. Propylene glycol concentrations should be 1% higher than the ethylene  
glycol table values to find the freeze point. For example, 41% propylene glycol freezes at -10°F (-23°C).  
Table 14 Ethylene glycol concentrations  
% Glycol by Volume  
Freezing Point °F (°C)  
0 *  
10  
20  
30  
40  
50  
32 (0)  
25 (-3.9)  
16 (-8.9)  
5 (-15.0)  
-10 (-23.3)  
-32 (-35.5)  
Apparent Specific Gravity  
@ 50°F (10°C)  
1
1.014  
1.028  
1.042  
1.057  
1.071  
* A minimal amount of glycol should be considered for inhibitive coil protection.  
NOTICE  
The quality of water used for dilution must be considered because water may contain corrosive  
elements that reduce the effectiveness of the inhibited formulation. Water classified as soft  
(low in chloride and sulfate ion content less than 100 parts per million each) should be used.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Glycol/GLYCOOL-Cooled Models  
5.5.3 Filling the System  
Installation of hose bibs at the lowest point of the system is recommended. When filling a glycol sys-  
tem keep air to a minimum. Air in glycol turns to foam and is difficult and time-consuming to remove.  
(Anti-foam additives are available and may be considered.) Open all operating systems to the loop.  
With the top vent(s) open, fill the system from the bottom of the loop. This will allow the glycol to  
push the air out of the top of the system, minimizing trapped air. Fill to approximately 80% of calcu-  
lated capacity. Fill slowly from this point, checking fluid levels until full.  
NOTE  
For glycol solution preparation and periodic testing, follow manufacturer's recommendations.  
Do not mix products of different manufacturers.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Glycol/GLYCOOL-Cooled Models  
Figure 14 Drycoolers and pump packages  
43-9/16"  
(1105mm)  
DRYCOOLER  
A
GLYCOL PUMP PACKAGE  
See Note 1  
30-1/4"  
(768mm)  
37-7/8"  
(1095mm)  
19"  
(483mm)  
B
43-3/16"  
(1097mm)  
dimensions “A”, “B” and “C”.  
Provided on  
dual pump  
package only  
PUMP PACKAGE  
MOUNTING ANGLES  
1/2" diameter holes  
for mounting (4 typ)  
Notes  
1. Single pump packages are 17-1/4"  
(438 mm) wide. Dual pump packages are  
32-1/4" (819 mm) wide.  
2. Mounting holes are 15-1/4" (387 mm)  
apart on single pump packages and 30-  
1/4" (768 mm) apart on dual pump  
packages.  
Note: Angles located  
inside, bottom of pump  
package. View used for  
mounting reference.  
3/4"  
(19mm)  
3. Connection sizes apply to primary pump  
supplier.  
C
A
B
See Table 15 for keys to  
dimensions “A”, “B” and “C”.  
For expansion tank dimensions,  
1-3/4"  
4-1/4"  
(25.4mm) (25.4mm)  
1"  
(25.4mm)  
B
C
1-3/4"  
(25.4mm)  
1"  
(25.4mm)  
4-1/4"  
(25.4mm)  
37-11/16"  
(957mm)  
1/2" (12.7mm) diameter  
anchor bolts (typ)  
TYPICAL  
FOOTPRINT  
UNIT ANCHOR PLAN  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Glycol/GLYCOOL-Cooled Models  
Figure 15 Pump packages—expansion tank  
30-1/2"  
(774.7mm)  
O 9"  
(228.6mm)  
6-13/16"  
(173mm)  
17-1/4"  
(438.2mm)  
1/2" FPT  
1/2" FPT  
Fitting  
Fitting  
2-3/4"  
2-1/2"  
7"  
(69.9mm)  
(63.5mm)  
(177.8mm)  
4"  
O 1/2 " (12.7mm) (8) Holes  
1" (25.4mm)  
1" (25.4mm)  
(101.6mm)  
8.8 Gallon Expansion Tank  
(33.3 Liter)  
1-1/2"  
(38.1mm)  
3"  
1-1/2"  
(38.1mm)  
6-1/8"  
(155.6mm)  
(76.2mm)  
SL-10065 PG 7B SL-10070 PG 6B  
Table 15 Mounting hole dimensional data  
A
B
C
PUMP PACKAGE  
SINGLE (0.75 - 7.5 hp)  
DUAL (0.75 - 5 hp)  
DUAL (7.5 hp)  
in (mm)  
in (mm)  
in (mm)  
15-1/4 (387.4)  
30-1/4 (768.4)  
2-1/2 (63.5) 22-1/2 (571.5)  
2-1/2 (63.5) 22-1/2 (571.5)  
39-5/16 (998.5) 1-3/4 (44.5) 26-7/8 (682.6)  
Table 16 Drycooler data  
Model No. of Weight  
Drycooler  
Conn. Sizes  
(Suct. & Disc.) in.  
“A” Dimension “B” Dimension “C” Dimension  
Coil Internal  
Volume, gal. (l)  
No.  
-069  
-092  
-109  
-112  
-139  
-197  
Fans  
lb (kg)  
in. (mm)  
in. (mm)  
44 (1118)  
44 (1118)  
44 (1118)  
44 (1118)  
84 (2134)  
84 (2134)  
in. (mm)  
42 (1067)  
42 (1067)  
42 (1067)  
42 (1067)  
82 (2083)  
82 (2083)  
1
1
1
1
2
2
410 (186)  
430 (195)  
450 (204)  
470 (213)  
565 (256)  
605 (274)  
1-1/4  
51-1/2 (1308)  
51-1/2 (1308)  
51-1/2 (1308)  
51-1/2 (1308)  
91-1/2 (2324)  
91-1/2 (2324)  
2.4 (9.2)  
3.7 (13.9)  
4.9 (18.6)  
5.8 (22.0)  
4.8 (18.2)  
9.0 (34.1)  
1-1/2  
2
2
2
2
Table 17 Glycol pump data*  
Pump  
Pump Suction  
Connection in.  
Pump Discharge  
Connection in.  
Hp  
Hz  
1-1/2  
60  
60  
60  
60  
1-1/4  
1-1/4  
1-1/2  
1-1/2  
3/4  
3/4  
1
2
3
5
1-1/4  
1
1-1/2  
2
50  
50  
50  
50  
1-1/4  
1-1/4  
1-1/4  
1-1/2  
3/4  
3/4  
3/4  
3
1-1/4  
* Connection sizes apply to primary pump supplier  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Glycol/GLYCOOL-Cooled Models  
Figure 16 Glycol general arrangement  
Expansion Tank Field Installed at  
Drycooler  
Glycol  
Pump  
Highest Point in System.  
Electric  
Unions*  
Fill *  
Pump  
Housing  
Box  
Drycooler  
Coil  
Expansion  
Port*  
Fluid  
Return  
to Pump  
Evaporator  
Coil  
Isolation  
Valves*  
Unions*  
Expansion  
Valve  
Fluid  
Supply  
from  
Pump  
Sensing  
Bulb  
Hose  
Bibs*  
Air Vents*  
at Top of  
Risers  
Flow Regulating  
Valve*  
Sight  
Glass  
Pressure  
Port*  
Hot Gas  
Bypass  
Valve  
External  
Equalizers  
Scroll  
Compressor  
Filter  
Drier  
Service  
Valves  
Hot Gas  
Bypass  
Solenoid  
Valve  
Hot Gas  
Bypass  
Tube  
in Tube  
Condenser  
Tube  
in Tube  
Condenser  
Bypass  
Valve  
Fluid  
Supply  
to Unit  
Fluid  
Return  
from  
Isolation  
Valves*  
Unit  
2-Way Water  
Regulating  
Valve  
3-Way Water  
Regulating Valve  
(optional)  
Hose  
Bibs*  
Fluid  
Supply  
to Unit  
Fluid  
Return  
From  
Unit  
FACTORY  
PIPING  
FIELD  
Hose  
Bibs*  
PIPING  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
SL-11898 PG 6  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Glycol/GLYCOOL-Cooled Models  
Figure 17 GLYCOOL general arrangement  
Expansion Tank Field Installed at  
Highest Point in System  
Glycol  
Pump  
Unions*  
Pump  
Housing  
*
Drycooler  
Electric  
Box  
Fill  
Drycooler  
Coil  
Fluid  
Return to  
Pump  
Evaporator  
Coil  
Pressure  
Port*  
Isolation  
Valves*  
Unions*  
Expansion  
Valve  
Fluid  
Supply  
from  
Hose  
Bib*  
Sensing  
Bulb  
Pump  
Air Vents*  
at Top of  
Risers  
Flow Regulating  
Valve*  
Sight  
Glass  
Hot Gas  
Bypass  
Valve  
Pressure  
Port*  
External  
Equalizers  
Scroll  
Compressor  
Filter  
Drier  
Hot Gas  
Bypass  
Solenoid  
Valve  
Service  
Valves  
Hot Gas  
Bypass  
Econ-O-Coil  
Tube  
3-Way Water  
Regulating  
Valve  
in Tube  
Condenser  
Fluid  
Supply to  
Unit  
Valve  
Actuator  
Fluid  
Return  
from  
Econ-O-Cycle  
Comparator  
Unit  
Isolation  
Valves*  
3-Way Chilled  
Glycol Valve  
Econ-O-Coil  
Circuit  
PIPING  
FACTORY  
Hose  
Bibs*  
FIELD PIPING  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
SL-11901 PG 5  
and maintenance.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Glycol/GLYCOOL-Cooled Models  
5.6  
5.7  
Condenser  
The condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure  
is 350 psig (2413 kPa).  
NOTE  
For pressures above 150 psig (1034 kPa), the high pressure option for high pressure valve(s)  
is required.  
Glycol Regulating Valve  
The glycol regulating valve automatically regulates the amount of coolant necessary to remove the  
heat from the refrigeration system, permitting more fluid to flow when load conditions are high and  
less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring,  
valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.  
5.7.1 Glycol Regulating Valve Adjustment  
The Liebert Challenger ITR may be equipped with either a standard Johnson Controls valve, 150 psig  
(1034 kPa) or with a high-pressure Johnson Controls valve, 350 psig (2413 kPa). For details on adjust-  
ing the valve, refer to 4.3.1 - Water Regulating Valve Adjustment.  
5.7.2 Testing Valve Function  
When the refrigeration system has been off for approximately 10-15 minutes, the coolant flow should  
stop.  
Should the coolant continue to flow, the valve is either improperly adjusted or the pressure sensing  
capillary is not connected properly to the condenser.  
Table 18 Refrigerant control settings psi (kPa)  
Low Pressure  
Cut Out  
Low Pressure  
Cut In  
High Pressure  
Cut Out  
20 (137.9)  
65 (448.2)  
360 (2482)  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Chilled Water Models  
6.0 CHILLED WATER MODELS  
6.1 Piping Considerations  
Manual shut-off valves should be installed at the supply and return lines to each unit. This will pro-  
vide for routine service and emergency isolation of the unit.  
Consideration of the minimum water temperature to be supplied from the chiller will determine if the  
need exists to insulate supply and return lines. Insulation will prevent condensation on the supply  
and return lines.  
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains  
should be provided with wet traps or a water detection system, such as a Liqui-tect, that is installed  
near the base of the unit or below the elevated floor.  
Figure 18 Chilled water general arrangement - horizontal flow (BR)  
Air  
Flow  
Bleed  
Valve  
Chilled  
Water  
Supply  
Chilled  
Water  
Coil  
Valve  
Actuator  
Chilled  
Water  
Return  
3-WAY VALVE  
A
3-Way  
Chilled  
Water  
Valve  
Shutoff  
Valves*  
AB  
B
Flow  
Switch  
(optional)  
Air  
Flow  
Bleed  
Valve  
Hose  
Bibs*  
Valve  
Actuator  
Chilled  
Water  
Supply  
2-Way  
Chilled  
Water  
Return  
Chilled  
Water  
Coil  
Chilled  
Water  
Valve  
2-WAY VALVE  
Shutoff  
Valves*  
SINGLE CIRCUIT SHOWN  
FACTORY PIPING  
FIELD PIPING  
*Components are not supplied by Emerson but  
are recommended for proper circuit operation  
and maintenance.  
Hose  
Bibs*  
SL-11899  
Pg. 5  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Split System Models  
7.0 SPLIT SYSTEM MODELS  
Three (3) condensing unit styles are available: two (2) air-cooled and one (1) water/glycol-cooled con-  
densing unit.  
7.1  
Location Considerations  
7.1.1 Air-Cooled Condensing Units  
To assure an adequate air supply, it is recommended that all condensing units be located in a clean  
air area, away from loose dirt and foreign matter that may clog the coil.  
Condensing units must not be located in the vicinity of steam, hot air, or fume exhausts or closer than  
18" from a wall, obstruction, or adjacent unit.  
The outdoor condensing unit should be located for maximum security and maintenance accessibility.  
Avoid ground-level sites with public access or areas that will contribute to heavy snow accumulations.  
Do not allow the discharge air to blow into another condensing unit.  
A solid base, capable of supporting the weight of the condenser and at least 2" (51 mm) higher than  
the surrounding grade and at least 2" (51 mm) larger than the condensing unit base dimensions,  
should be installed at the pre-determined location. In snow areas, a base of sufficient height to clear  
snow accumulation must be installed.  
The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote  
indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal  
operating sound may be objectionable if the condensing unit is placed near quiet work areas.  
To mount the unit in the ceiling, refer to 7.5.1 - Installing the Indoor Condensing Unit for hang-  
ing guidelines and to Figure 23 - Detail of ceiling hanging bracket for dimensional data.  
7.1.2 Water/Glycol-Cooled Condensing Units  
The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of  
concern, the condensing unit should be located away from personnel. Normal operating sound may be  
objectionable if the condensing unit is placed near quiet work areas. To mount the unit the in ceiling,  
7.2  
Electrical Connections  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-  
trical schematic when making connections. Make all wiring and electrical connections in accordance  
with local and national codes.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power before working within the unit. Use a  
voltmeter to make sure power is turned off before making any electrical connections.  
7.2.1 Line Voltage  
Line voltage electrical service is required for all condensing units at the location of the condensing  
unit. This power supply does not have to be the same voltage as the indoor unit. This separate power  
source may be 208, 230, 460 or 575V, 60 Hz; or 200, 230, or 380/415V, 50 Hz. A disconnect switch is  
required and must be mounted per local and national codes to isolate the unit for maintenance.  
7.2.2 Low Voltage  
The control cable between the condensing unit and the evaporator unit is connected between termi-  
nals 1,2 and 3 on the terminal strip in the evaporator unit and the condensing unit control box. A  
fourth wire is required on systems with hot gas bypass. NEC Class 1 wiring is required. Glycol-cooled  
units also require a two-wire control connection to the drycooler and pump package.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Split System Models  
7.3  
Piping Considerations  
7.3.1 Refrigerant Loop  
CAUTION  
!
All local codes for handling refrigerant must be followed.  
NOTE  
As R22 and R407C are similar in properties, proper safety equipment and proper refrigeration  
tools are required on both types. Check unit nameplate for correct refrigerant type before  
topping off or recharging a system.  
NOTE  
Refrigerant R407C uses a POE (polyol ester) lubricant. The R407C refrigerant must be  
introduced and charged from the cylinder only as a liquid.  
NOTE  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand  
open to air for more than 15 minutes. Units designed for R407C have a compressor which  
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The  
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left  
open too long, the POE oil may need to be replaced before achieving the required vacuum level.  
NOTE  
Complete all piping and evacuate lines before connecting quick connects when using an  
optional sweat adapter kit and field installed hard piping.  
Follow all proper brazing practices including a dry nitrogen purge to maintain system  
cleanliness.  
All split systems require two refrigerant lines (an insulated copper suction line and a copper liquid  
line) between the evaporator and the condensing unit.  
Two possible methods exist for installing the copper suction and liquid lines.  
1. Using an optional Sweat Adapter Kit and hard piping between the two units.  
2. Using optional pre-charged line sets.  
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good  
refrigeration practices should be employed for piping supports, leak testing, evacuation, dehydration,  
and charging of the refrigeration circuits. The refrigeration piping should be isolated from the build-  
ing by the use of vibration isolating supports.  
It is important to handle the pre-charged lines with care so they will not get kinked or damaged. Use  
tube benders and make all bends before making connections to either end. Coil any excess tubing in a  
horizontal plane with the slope of the tubing toward the condensing unit.  
To prevent tube damage when sealing openings in walls and to reduce vibration transmission, use a  
soft flexible material to pack around the tubes.  
When installing remote condensing units mounted above the evaporator, the suction gas line should  
be trapped at the evaporator. This trap will retain refrigerant oil in the off cycle. When the unit  
starts, oil in the trap is carried up the vertical riser and returns to the compressor.  
Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated  
during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit.  
NOTE  
All condensing units and 3-ton evaporator units are fully charged with refrigerant. All  
23 and 33 kW evaporator units include a nitrogen holding charge only. See Table 19 for field  
charge required. If field-supplied refrigerant piping is installed, refrigerant must be added to  
the system.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Split System Models  
Once all piping is complete, check for leaks and dehydrate the field piping as follows:  
1. Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant.  
Check system for leaks with a suitable leak detector.  
2. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum  
on the field piping with a suitable pump.  
3. After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with  
dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.  
Table 19  
Unit refrigerant charge  
R22 Charge  
lb (kg)  
R407C Charge  
R22 Charge  
lb (kg)  
R407C Charge  
lb (kg)  
Model  
060E  
lb (kg)  
0.8 (0.4)  
Model  
0.81 (0.37)  
0.81 (0.37)  
27.00 (12.25)  
PF_Z67A-_L 51.69 (23.45)  
PF_Z66A-_L 51.69 (23.45)  
PF_067A-_H 51.69 (23.45)  
PF_066A-_H 51.69 (23.45)  
50.1 (22.7)  
50.1 (22.7)  
50.1 (22.7)  
50.1 (22.7)  
n/a  
059E  
0.8 (0.4)  
MC_65/64A  
26.1 (11.8)  
25.8 (11.7)  
25.8 (11.7)  
PF_067A-_L 26.63 (12.08)  
PF_066A-_L 26.63 (12.08)  
MC_69/68W  
5.88 (2.67)  
Table 20 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube  
R22 R407C  
Liquid Line Suction Line Liquid Line Suction Line  
O.D.  
lb (kg)  
lb (kg)  
0.2 (0.1)  
0.3 (0.2)  
0.7 (0.3)  
1.2 (0.6)  
1.9 (0.8)  
lb (kg)  
lb (kg)  
1/2"  
7.3 (3.3)  
6.9 (2.9)  
-
5/8"  
11.7 (5.3)  
24.4 (11.1)  
41.6 (18.9)  
63.3 (28.7)  
11.0 (4.6)  
23.0 (9.6)  
39.3 (16.3)  
59.8 (24.8)  
0.4 (0.2)  
1.0 (0.4)  
1.7 (0.7)  
2.7 (1.1)  
7/8"  
1-1/8"  
1-3/8"  
Table 21 Recommended refrigerant lines (R22 or R407C) sizes OD copper  
3.5 Tons  
036E (035E)  
23 & 33 kW  
060E (059E)  
Equivalent Feet (m)  
0-50 (0-15)  
Suction  
Liquid  
1/2"  
Suction  
Liquid  
1/2"  
7/8"  
1-1/8"  
1-1/8"  
1-3/8"  
51-100 (16-30)  
101-150 (31-45)  
1-1/8"  
1-1/8"  
1/2"  
5/8"  
5/8"  
5/8"  
Table 22 Line coupling sizes  
Line Size  
OD Cu, in.  
Coupling  
Torque  
Size  
#10  
#12  
lb-ft.  
35-45  
50-65  
1/2 & 5/8  
1-1/8  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Split System Models  
Table 23 Equivalent lengths (feet) for various pipe fittings  
Copper Pipe  
OD in.  
90 Degree  
Elbow Copper Elbow Cast  
90 Degree  
45 Degree  
Elbow  
Gate  
Tee Valve  
Globe Angle  
Valve  
Valve  
1/2  
5/8  
0.8  
0.9  
1.3  
1.4  
1.5  
1.8  
2.2  
2.9  
3.5  
0.4  
0.5  
0.6  
0.8  
1.0  
1.3  
1.6  
2.5  
2.5  
2.5  
3.6  
4.6  
6.4  
7.2  
0.26  
0.28  
0.3  
7.0  
4.0  
5.0  
9.5  
3/4  
1.0  
12.0  
17.2  
22.5  
32.0  
36.0  
6.5  
7/8  
1.45  
1.85  
2.4  
0.36  
0.48  
0.65  
0.72  
9.5  
1-1/8  
1-3/8  
1-5/8  
12.0  
16.0  
19.5  
2.9  
Refrigerant trap = 4 times equivalent length of pipe per this table  
Figure 19 Refrigerant piping diagram  
Evaporator  
Pitch down 1/2" (13mm) per 10 ft. (3m)  
NOTE  
When remote condensing units are installed below the  
evaporator, the suction gas line should be trapped with  
an inverted trap to the height of the evaporator. This  
prevents refrigerant migration to the compressors  
during off cycles. Maximum recommended vertical drop  
to condensing unit is15 ft. (4.6m).  
Suction Line Piping  
Condensing unit  
below evaporator  
Condensing  
Unit  
Evaporator  
Condensing  
Unit  
Suction Line Piping  
Condensing unit above evaporator .  
Traps recommended at the base of riser and  
every 25 feet (7.6m) of vertical rise.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Split System Models  
7.3.2 Quick Connect Fittings  
NOTE  
When hard piping is used, complete all piping and evacuate lines before  
connecting quick connects.  
Be especially careful when connecting the quick connect fittings. Read through the following steps  
before making the connections.  
1. Remove protector caps and plugs.  
2. Carefully wipe coupling seats and threaded surfaces with a clean cloth.  
3. Lubricate the male diaphragm and synthetic rubber seal with refrigerant oil.  
4. Thread the coupling halves together by hand to ensure that the threads mate properly.  
5. Tighten the coupling body hex nut and union nut with the proper sized wrench until the coupling  
bodies “bottom out” or until a definite resistance is felt.  
6. Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead.  
7. Tighten the nuts an additional quarter turn; the misalignment of the lines shows how much the  
coupling has been tightened. This final quarter turn is necessary to ensure that the joint will not  
leak. Refer to Table 22 for torque requirements.  
8. Add charge for the additional piping (refer to Table 20).  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
7.4  
Outdoor Air-Cooled Condensing Units  
Figure 20 Outdoor air-cooled condensing unit—horizontal air discharge models  
UNIT DIMENSIONS  
REMOVABLE (RIGHT) PANEL  
Fan Rotation  
CCW  
(left side)  
FOR ACCESS TO  
REFRIGERATION COMPONENT.  
A
RIGHT  
AIR  
DISCHARGE  
LEFT  
AIR  
INTAKE  
B
SHADED AREA  
INDICATES A MINIMUM  
CLEARANCE OF 18" (457mm)  
FOR PROPER AIR FLOW  
C
SHADED AREA  
INDICATES A RECOMMENDED  
CLEARANCE OF 24" (610mm)  
FOR COMPONENT ACCESS  
AND REMOVAL.  
SHADED AREA  
REMOVABLE (FRONT) PANEL FOR  
ACCESS TO HIGH VOLTAGE &  
LOW VOLTAGE CONNECTIONS,  
AND REFRIGERATION COMPONENTS.  
INDICATES A MINIMUM  
CLEARANCE OF 18" (457mm)  
FOR PROPER  
AIR FLOW.  
SL-11081 PG 4  
Liquid Line  
Quick Connect  
(Male Coupling .  
Suction Line  
Quick Connect  
(Male Coupling).  
Except as noted  
A
F
Electrical Entrance for  
High Voltage  
Connection  
G
B
C
Electrical Entrance for  
Low Voltage Connection  
D
E
SL-11081PG 6  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Split System Models  
Table 24 Horizontal air discharge cabinet and floor planning dimensional data  
Model Numbers  
Dimensional Data in. (mm)  
Module  
Weight  
60 Hz  
50 Hz  
A
B
C
lb (kg) net  
PFC067A-_L  
PFH067A-_L  
PFC066A-_L  
53 (1343) 36-1/4 (918) 18 (457)  
351 (159)  
Table 25 Horizontal air discharge piping and electrical connection data  
Model Numbers Dimensional Data in. (mm) Piping Connections in. (mm)  
60 Hz  
50 Hz  
A
B
C
D
E
F
G
PFC067A-_L  
PFH067A-_L  
PFC066A-_L  
2 (51)  
6 (152)  
8-1/2 (216) 4-3/4 (121) 7-3/4 (197)  
-
8-1/2 (216)  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Split System Models  
Figure 21 Outdoor air-cooled condensing unit—top air discharge models  
GUARD  
HEIGHT  
TOP  
AIR  
DISCHARGE  
D
RIGHT  
AIR  
INTAKE  
UNIT DIMENSIONS  
B
LEFT  
AIR  
INTAKE  
SHADED AREA  
INDICATES A RECOMMENDED  
CLEARANCE OF 18" (457mm)  
FOR PROPERAIRFLOW  
2 "  
(51mm)  
A
C
SHADED AREA  
INDICATES A RECOMMENDED  
CLEARANCE OF 18" (457mm)  
FOR PROPERAIRFLOW  
SHADED AREA  
INDICATES A RECOMMENDED  
CLEARANCE OF 24" (610mm)  
FOR COMPONENT ACCESS  
AND REMOVAL.  
REMOVABLE FRONT PANEL FOR  
ACCESS TO HIGH VOLTAGE &  
LOW VOTLAGE CONNECTIONS,  
AND REFRIGERATION COMPONENTS.  
36 1/8 "  
(918mm)  
4 " TYP.  
(102mm)  
53 3/16 "  
(1351mm)  
FOOTPRINT  
DIMENSIONS  
2 " TYP.  
(51mm)  
1/2" Bolt-Down Holes  
(6 places)  
4 23/32 "  
(120mm)  
2 "  
(51mm)  
32 1/8 "  
(816mm)  
25 3/32 "  
(637mm)  
2 "  
(51mm)  
46 7/32 "  
(1174mm)  
SL-11081PG 5  
* System 2 (23 & 33kW)  
Electrical Entrance for  
High Voltage Connection  
A
PIPING & ELECTRICAL  
CONNECTIONS  
F
G
(see Table 27)  
B
C
Liquid Line  
Quick Connect  
(Male Coupling)  
Electrical Entrance  
for Low Voltage  
Connection  
D
Suction Line  
* System 1 (3 Ton)  
E
Quick Connect  
(Male Coupling)  
* System 1 and System 2 on 8 Ton only.  
SL-11081 PG 7  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
Table 26 Cabinet and floor planning dimensional data - prop fan condensing modules, top air discharge  
Model Numbers  
Dimensional Data, in. (mm)  
Module  
Weight  
60 Hz  
50 Hz  
A
B
C
D
lb (kg) net  
PFC067A-_H  
PFH067A-_H  
PFCZ67A-_L  
PFC066A-_H  
53 (1343)  
36-1/4 (918)  
38-1/2 (978)  
5-1/2 (140)  
488 (222)  
PFCZ66A-_L  
Table 27 Piping and electrical connections - top air discharge  
Model Numbers Dimensional Data in. (mm) Piping Connections, in. (mm)  
60 Hz  
50 Hz  
A
B
C
D
E
F
PFC067A-_H  
PFH067A-_H  
PFCZ67A-_L  
PFC066A-_H  
2 (51)  
6 (152)  
8-1/2 (216)  
4-3/4 (121)  
7-3/4 (197)  
8-1/2 (216)  
PFCZ66A-_L  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Split System Models  
Figure 22 Electrical field connections, prop fan condensing module  
TOP AIR  
DISCHARGE MODELS  
(23 & 33kW High Ambient  
and 23 & 33kW Quiet-Line)  
Field-supplied unit  
disconnect switch  
HORIZONTAL AIR DISCHARGE MODELS  
Field-supplied 24V NEC  
Class 2 wiring to  
evaporator module  
Single- or  
3-phase  
electric  
service;  
SL-11081PG 8A  
not by Liebert  
Single- or  
3-phase  
electric  
service; not  
by Liebert  
Field-supplied 24V  
NEC Class 2 wiring  
to evaporator  
module  
Electric service  
connection to contactor  
or terminal block  
Factory-wired  
to components on  
electric panel.  
Single- or 3-phase  
electric service; not  
by Liebert  
High voltage electric  
power supply entrance  
Low voltage electric  
power supply entrance  
Heat rejection connection. Field-  
supplied 24V NEC class 2 wiring.  
Wire connections from evaporator module:  
1. 24V GND  
Earth ground connection  
terminal for field wiring.  
2. 24V Supply  
3 High Pressure Alarm  
4. Hot Gas Bypass Connection  
(only on units with hot gas bypass.  
If no hot gas bypass, connection is  
provided in the evaporator module.  
Connect wire 4 with wire 2 to the  
24V supply).  
NOTE: Refer to specification sheet for full load amp  
and wire size amp ratings.  
SL-11081 PG 8  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
7.5  
Centrifugal Air-Cooled Condensing Units  
7.5.1 Installing the Indoor Condensing Unit  
Refer to drawings for unit dimensions and component locations.  
WARNING  
!
Risk of structure collapse. Can cause equipment damage, injury or death.  
Before beginning installation, make sure that the supporting roof structure is capable of  
supporting the weight of the unit(s) and the accessories during installation and service. (See  
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight.  
The indoor condensing unit is usually mounted above the ceiling and must be securely mounted to the  
roof structure. The ceiling and ceiling supports of existing buildings may require reinforcements. Be  
sure to follow all applicable codes. Use field-supplied threaded suspension rods and  
3/8"-16 factory hardware kit.  
Recommended clearance between ceiling grids and building structural members is unit height plus  
three inches.  
Install the four field-supplied rods by suspending them from suitable building structural members.  
Locate the rods so that they will align with the four mounting holes in the flanges that are part of the  
unit base.  
Using a suitable lifting device, raise the unit up and pass the threaded rods through the four mount-  
ing holes in the flanges that are part of the unit base.  
Attach the threaded rods to the unit flanges using the supplied nuts and grommets. (See Figure 23 -  
Detail of ceiling hanging bracket, Threaded Rod and Hardware Kit Installation). The rubber  
grommets provide vibration isolation.  
1. Use the plain nuts to hold unit in place. Adjust these nuts so that the weight of the unit is  
supported evenly by the four rods, does not rest on the ceiling grid, and is level.  
NOTE  
The units must be level in order to operate properly.  
2. Use the Nylock nuts to “jam” the plain nuts.  
Table 28 Indoor centrifugal condensing unit  
Model  
Net Weight  
60 Hz  
50 Hz  
lb (kg)  
MC_65A  
MC_69W  
MC_64A  
MC_68W  
449 (204)  
282 (128)  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Split System Models  
Figure 23 Detail of ceiling hanging bracket  
3/8" threaded rod  
(field-supplied)  
3/8" hex nut  
3/8" washer  
Sleeve  
Isolator  
3/8" fender washer  
3/8" hex nut  
3/8" hex nut  
Nylock  
Unit base pan (ref)  
7.5.2 Ducting  
The total external static pressure for the inlet and outlet ducts, including grille, must not exceed  
0.5 inches of H O. Hood intake dimensions should be the same as the condensing unit duct dimen-  
2
sions.  
If the condensing unit is located close to the outside of the building, rain hoods must be installed. In  
addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of  
insects, birds, water, or debris entering the unit.  
Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control  
vibration transmission to the building. Attach the ductwork to the unit using the flanges provided.  
Locate the unit and ductwork so that the return air does not short circuit to the supply air inlet.  
Avoid directing the hot exhaust air toward adjacent doors or windows.  
Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work  
areas. Ductwork that runs through a conditioned space or is exposed to areas where condensation  
may occur must be insulated. Whenever possible, ductwork should be suspended using flexible hang-  
ers. Ductwork should not be fastened directly to the building structure. In applications where the ceil-  
ing plenum is used as the heat rejection domain, the discharge air must be directed away from the  
condensing unit air inlet and a screen must be added to the end of the discharge duct to protect ser-  
vice personnel.  
For multiple unit installations, space the units so that the hot condensing unit exhaust air is not  
directed toward the air inlet of an adjacent unit.  
Table 29 Airflow CFM (CMH)  
23 & 33 kW  
60 Hz  
50 Hz  
3500 (5947)  
3500 (5947)  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Split System Models  
Figure 24 Centrifugal air-cooled condensing unit dimensional data  
32 "  
(812.8mm)  
CABINET  
54 "  
DIMENSION  
(1371.6mm)  
CABINET  
1 5/8 "  
(41.1mm)  
DIMENSION  
15 3/4 "  
(400mm)  
8 15/16 "  
(227mm)  
48 "  
(1219.2mm)  
Customer-supplied  
threaded rods for module  
support from ceiling  
(typ. 4)  
3 3/8 "  
(85.7mm)  
14 1/2 "  
(368.3mm)  
24 "  
(610mm)  
CABINET  
21 1/4 "  
DIMENSION  
(539.8mm)  
1 3/4 "  
(44.5mm)  
Shaded area indicates a  
recommended clearance of  
30" (762mm) for component  
33 5/8 "  
51 13/16 "  
Hanger Bracket  
(854.1mm)  
(1316mm)  
access and  
removal.  
THREADED ROD  
THREADED ROD  
CENTERS  
CENTERS  
NOTE: Unit is spaced evenly in  
reference to threaded  
rod centers.  
1/2" (12.7mm) dia. holes for  
threaded rods (typ. 2 each end)  
7/8" (22.2mm) & 1 1/8" (28.6mm)  
7/8" (22.2mm) & 1 1/8" (28.6mm)  
dia. knockouts electrical entrance for high  
voltage connection (Single Point Power Kit).  
dia. knockouts electrical entrance for high  
voltage connection.  
Single Point Power Kit  
connection to Evaporator.  
Air Inlet  
Air  
Outlet  
Liquid Line male quick  
connect location  
Suction Line male quick  
conect location.  
7/8" (22.2mm) dia. electrical entrance  
for low voltage connection.  
7/8" (22.2mm) dia. knockout  
electrical entrance for altermate  
control panel low voltage routing.  
SL-11087 PG 4  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
Figure 25 Centrifugal air-cooled condensing unit dimensional data (con't.)  
Field-supplied unit disconnect  
switch when factory unit  
disconnect switch is not supplied.  
Electric service  
not by Emerson  
Optional factory-installed  
disconnect switch  
AIR COOLED  
Connection terminal  
for field supplied earth  
grounding wire  
Line voltage electric power  
supply conduit voltage  
Removable access panels  
Heat rejection connection. Field-supplied  
24V NEC Class 2 wiring. See Note 2.  
Wire connections from evaporator module.  
1. 24V GND  
Field-supplied 24V NEC  
Class 2 wiring  
between condensing  
unit and fan/coil unit  
Low voltage electric power  
supply conduit entrance  
2. 24V supply  
3. High pressure alarm (optional)  
4. Hot gas bypass connection (only on  
units with hot gas bypass)  
DPN000226  
Rev. 0  
NOTES:  
1. Refer to specification sheet for full load amp and wire size amp ratings.  
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m)  
or not to exceed 1 volt drop in control line.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
Figure 26 Split systems general arrangement  
Hot Gas  
Condenser  
Coil  
Bypass Solenoid  
High Pressure  
Switch  
Valve  
Scroll  
Compressor  
Liquid Injection  
Valve Bulb  
1/2" (12.7mm) NPT  
Pressure Relief Valve  
Suction Line  
Male Quick  
Connect  
Check Valve  
Sight  
AIR COOLED  
Glass  
Suction Line  
Coupling*  
Female Quick  
Connect  
Service  
Access  
Ports  
Head Pressure  
Control with  
Integral Check  
Valve  
Coupling*  
Lee-Temp  
Receiver  
1
Hot Gas  
Pressure Balancing  
Valve  
Tube in  
Tube  
Condenser  
External  
Sensing  
Bulb  
Bypass Control  
Valve  
Liquid Injection  
Receiver Heater  
Pressure Limiting  
Switch  
Equalizer  
Liquid Line  
Valve  
Male Quick  
Connect  
Filter  
Liquid Line  
Drier  
Solenoid Valve  
Coupling*  
High Pressure  
Switch  
Liquid Line  
Female Quick  
Connect  
Scroll  
Compressor  
Expansion  
Valve  
Coupling*  
Liquid Injection  
Hot Gas Bypass  
Solenoid Valve  
Valve Bulb  
Water/Glycol  
Return  
Evaporator  
Coil  
Suction Line  
Male Quick  
Connect  
Line  
Water/Glycol  
Supply  
WATER COOLED  
GLYCOL COOLED  
Line  
Fluid Return  
from Unit  
Coupling*  
Service  
Access  
Ports  
Suction Line  
Female Quick  
Connect  
Fluid Supply  
to Unit  
Coupling*  
1
External  
Hot Gas Bypass  
Control Valve  
Equalizer  
Sensing  
Bulb  
Shutoff  
Valves*  
Liquid Injection  
Valve  
Tube inTube  
Condenser  
2-Way Water  
Regulating  
Valve  
Liquid Line  
Male Quick  
Connect  
Filter  
Drier  
Hose Bibs*  
Liquid Line  
Female Quick  
Connect  
Coupling*  
Expansion  
Valve  
Coupling*  
SINGLE CIRCUIT SHOWN  
FACTORY  
Evaporator  
Coil  
PIPING  
OPTIONAL PIPING  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
NOTE: Refer to installation manual for  
field piping guidelines.  
1
Fluid  
Return  
from Unit  
SL-11900 PG 5  
Fluid Supply  
to Unit  
3-Way Water  
Regulating Valve (optional)  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
7.6  
Water and Glycol-Cooled Condensing Units  
For installation guidelines, refer to Installing the Indoor Condensing Unit on page 48.  
7.6.1 Piping Considerations  
It is recommended that manual service shut-off valves be installed at the supply and return line to  
each unit. This will provide for routine service or emergency isolation of the unit.  
When the water source for the condenser is of poor quality, it is good practice to provide cleanable fil-  
ters in the supply line. These filters will trap the particles in the water supply and extend the service  
life of the water-cooled condenser.  
Table 30 Water and glycol-cooled unit connection sizes  
Connection  
Size and Type  
Condenser Water Inlet 1-1/8" OD Cu  
Condenser Water Outlet 1-1/8" OD Cu  
Suction Line 1-7/16" - 16 male #12 quick connect  
Liquid Line 1-1/16" - 12 male #10 quick connect  
Table 31 Water and glycol-cooled condensing unit data  
Net Weight  
Glycol Volume  
Model  
lb  
kg  
gal  
liters  
MC_69W  
MC_68W  
282  
128  
2.0  
7.6  
7.6.2 Condenser Water Requirements  
The standard maximum water pressure is 150 psig (1034 kPa). For applications above this pressure,  
consult the factory about high pressure systems.  
The system will operate in conjunction with a cooling tower, city water, or drycooler.  
7.6.3 Regulating Valve Adjustment and Testing  
7.6.4 Glycol Systems  
For split system glycol systems, use drycooler and pump data found in 5.0 - Glycol/GLYCOOL-  
Electrical control interconnect to drycooler is wired from water/glycol condensing unit.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Split System Models  
Figure 27 Water/glycol-cooled condensing unit dimensions  
32 "  
(812.8mm)  
CABINET  
32 "  
(812.8mm)  
CABINET  
Customer supplied threaded rods  
for module support from ceiling  
(typ. 4).  
DIMENSION  
DIMENSION  
Removable Access Panel  
24 "  
1/2" (12.7mm) dia. holes for  
module rigging (typ. 2 each end).  
(610mm)  
CABINET  
DIMENSION  
Hanger Bracket  
Shaded area indicates a  
recommended clearance of  
33 5/8 "  
30" (762mm)  
and removal.  
for component access  
29 13/16 "  
(757.2mm)  
(854.1mm)  
THREADED ROD  
THREADED ROD  
CENTERS  
CENTERS  
NOTE: Unit is evenly spaced in reference  
to threaded rod centers.  
7/8" (22.2mm) & 1 1/8" (28.6mm)  
dia. knockouts electrical entrance for  
line voltage connection  
7/8" (22.2mm) & 1 1/8" (28.6mm)  
dia. knockouts electrical entrance for  
line voltage connection (Single Point  
Power Kit)  
8 7/16 "  
(214.4mm)  
3 3/4 "  
7 "  
(177.8mm)  
(95.2mm)  
Suction Line male quick  
connect location  
Liquid Line male quick  
connect location  
1" (25.4mm) NPT Female Water/Glycol  
Inlet Connection  
1" (25.4mm) NPT Female Water/Glycol  
Outlet Connection  
7/8" (22.2mm) dia. electrical entrance  
for low voltage connection.  
7/8" (22.2mm) dia. knockout electrical entrance  
for alternate control panel low voltage routing.  
SL-11087PG 6  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Split System Models  
Figure 28 Water/glycol-cooled condensing unit (con't.)  
Electric service;  
not by Liebert  
Field-supplied unit disconnect  
switch when factory unit  
disconnect switch is not supplied  
Optional factory-installed  
disconnect switch  
WATER/GLYCOL  
Field-supplied 24V NEC Class1  
wiring to fan/coil unit  
Field-supplied 24V NEC Class1  
wiring to drycooler  
(glycol-cooled units only)  
Line-voltage electric power  
supply conduit entrance  
Removable  
Access  
Panel  
Heat rejection connection.  
Field-supplied 24V NEC  
Class 2 wiring. Wire  
connections from evaporator  
mod:  
Connection terminal  
for field-supplied  
1. 24V ground  
earth grounding wire  
2. 24V supply  
3. High pressure alarm (optional)  
4. Hot gas bypass  
connection (only on units with  
hot gas bypass)  
Low-voltage electric  
power supply conduit entrance  
Field-supplied 24V NEC  
Class 1 wiring between  
glycol condensing unit  
and drycooler  
Remote drycooler  
connection; field-supplied  
24V NEC Class 1 wiring  
(glycol-cooled units only)  
DPN000228_Rev0  
NOTES  
1. Refer to specification sheet for full load amp. and wire size amp. ratings.  
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m)  
or not to exceed 1 volt drop in control line.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R407C Refrigerant  
8.0 R407C REFRIGERANT  
Table 32 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and suction  
gas)  
Temperature  
Gauge Pressure  
Temperature  
Gauge Pressure  
Temperature  
Gauge Pressure  
°F  
°C  
Psig  
18.9  
19.6  
20.4  
21.2  
22.0  
22.8  
23.6  
24.5  
25.4  
26.2  
27.1  
28.0  
28.9  
29.9  
30.8  
31.8  
32.8  
33.8  
34.8  
35.8  
36.9  
38.0  
39.0  
40.1  
41.3  
42.4  
43.6  
44.7  
45.9  
47.1  
48.4  
49.6  
50.9  
52.1  
53.5  
-
kPa  
130  
135  
141  
146  
152  
157  
163  
169  
175  
181  
187  
193  
200  
206  
213  
219  
226  
233  
240  
247  
254  
262  
269  
277  
284  
292  
300  
308  
317  
325  
333  
342  
351  
359  
369  
-
°F  
°C  
1.7  
Psig  
54.8  
56.1  
57.5  
58.9  
60.3  
62.2  
63.1  
64.6  
66.1  
67.6  
69.1  
70.7  
72.2  
73.8  
75.4  
77.1  
78.7  
80.4  
82.1  
83.9  
85.6  
87.4  
89.2  
91.0  
92.9  
94.8  
96.7  
98.6  
100.5  
102.5  
104.5  
106.5  
108.6  
110.7  
112.8  
-
kPa  
378  
387  
396  
406  
415  
429  
435  
445  
456  
466  
476  
487  
498  
509  
520  
531  
543  
554  
566  
578  
590  
603  
615  
628  
640  
653  
666  
680  
693  
707  
721  
735  
749  
763  
778  
-
°F  
°C  
Psig  
114.9  
119.3  
124  
128  
133  
138  
143  
148  
153  
158  
164  
169  
175  
181  
187  
193  
199  
205  
212  
219  
225  
232  
239  
247  
254  
262  
269  
277  
285  
294  
302  
311  
320  
329  
338  
347  
kPa  
792  
0.0  
-17.8  
-17.2  
-16.7  
-16.1  
-15.6  
-15.0  
-14.4  
-13.9  
-13.3  
-12.8  
-12.2  
-11.7  
-11.1  
-10.6  
-10.0  
-9.4  
-8.9  
-8.3  
-7.8  
-7.2  
-6.7  
-6.1  
-5.6  
-5.0  
-4.4  
-3.9  
-3.3  
-2.8  
-2.2  
-1.7  
-1.1  
-0.6  
0.0  
35.0  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
-
70.0  
21.1  
22.2  
23.3  
24.4  
25.6  
26.7  
27.8  
28.9  
30.0  
31.1  
32.2  
33.3  
34.4  
35.6  
36.7  
37.8  
38.9  
40.0  
41.1  
42.2  
43.3  
44.4  
45.6  
46.7  
47.8  
48.9  
50.0  
51.1  
52.2  
53.3  
54.4  
55.6  
56.7  
57.8  
58.9  
60.0  
1.0  
2.2  
72.0  
822  
2.0  
2.8  
74.0  
853  
3.0  
3.3  
76.0  
885  
4.0  
3.9  
78.0  
917  
5.0  
4.4  
80.0  
950  
6.0  
5.0  
82.0  
984  
7.0  
5.6  
84.0  
1019  
1054  
1091  
1128  
1167  
1206  
1246  
1287  
1329  
1372  
1416  
1461  
1507  
1553  
1601  
1650  
1701  
1752  
1804  
1858  
1912  
1968  
2025  
2083  
2143  
2203  
2265  
2329  
2393  
8.0  
6.1  
86.0  
9.0  
6.7  
88.0  
10.0  
11.0  
12.0  
13.0  
14.0  
15.0  
16.0  
17.0  
18.0  
19.0  
20.0  
21.0  
22.0  
23.0  
24.0  
25.0  
26.0  
27.0  
28.0  
29.0  
30.0  
31.0  
32.0  
33.0  
34.0  
-
7.2  
90.0  
7.8  
92.0  
8.3  
94.0  
8.9  
96.0  
9.4  
98.0  
10.0  
10.6  
11.1  
11.7  
12.2  
12.8  
13.3  
13.9  
14.4  
15.0  
15.6  
16.1  
16.7  
17.2  
17.8  
18.3  
18.9  
19.4  
20.0  
20.6  
-
100.0  
102.0  
104.0  
106.0  
108.0  
110.0  
112.0  
114.0  
116.0  
118.0  
120.0  
122.0  
124.0  
126.0  
128.0  
130.0  
132.0  
134.0  
136.0  
138.0  
140.0  
0.6  
1.1  
-
NOTE  
Use this table for superheat and for control adjustment (e.g., pressure switches). See  
Table 33 for subcooling.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
R407C Refrigerant  
Table 33 R407C pressure/temperature chart for subcooling only (liquid measurements)  
Temperature Pressure Gauge Temperature Pressure Gauge Temperature  
Pressure Gauge  
°F  
°C  
2.2  
Psig  
73  
kPa  
500  
511  
522  
533  
544  
556  
567  
579  
591  
602  
615  
627  
639  
652  
664  
677  
690  
704  
717  
730  
744  
758  
772  
-
°F  
°C  
Psig  
114  
116  
118  
120  
123  
125  
127  
129  
131  
134  
136  
138  
143  
148  
153  
158  
163  
169  
174  
180  
185  
191  
197  
-
kPa  
786  
°F  
°C  
Psig  
203  
209  
216  
222  
229  
236  
242  
249  
257  
264  
271  
279  
287  
294  
302  
310  
319  
327  
336  
345  
354  
363  
372  
381  
kPa  
1402  
1444  
1488  
1532  
1578  
1624  
1671  
1720  
1769  
1819  
1870  
1922  
1975  
2029  
2085  
2141  
2198  
2256  
2315  
2376  
2437  
2500  
2563  
2628  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
-
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
70.0  
72.0  
74.0  
76.0  
78.0  
80.0  
82.0  
84.0  
86.0  
88.0  
90.0  
92.0  
-
15.0  
15.6  
16.1  
16.7  
17.2  
17.8  
18.3  
18.9  
19.4  
20.0  
20.6  
21.1  
22.2  
23.3  
24.4  
25.6  
26.7  
27.8  
28.9  
30.0  
31.1  
32.2  
33.3  
-
94.0  
34.4  
35.6  
36.7  
37.8  
38.9  
40.0  
41.1  
42.2  
43.3  
44.4  
45.6  
46.7  
47.8  
48.9  
50.0  
51.1  
52.2  
53.3  
54.4  
55.6  
56.7  
57.8  
58.9  
60.0  
2.8  
74  
801  
96.0  
3.3  
76  
815  
98.0  
3.9  
77  
830  
100.0  
102.0  
104.0  
106.0  
108.0  
110.0  
112.0  
114.0  
116.0  
118.0  
120.0  
122.0  
124.0  
126.0  
128.0  
130.0  
132.0  
134.0  
136.0  
138.0  
140.0  
4.4  
79  
845  
5.0  
81  
860  
5.6  
82  
875  
6.1  
84  
891  
6.7  
86  
906  
7.2  
87  
922  
7.8  
89  
938  
8.3  
91  
954  
8.9  
93  
987  
9.4  
95  
1021  
1055  
1090  
1126  
1163  
1201  
1239  
1279  
1319  
1360  
-
10.0  
10.6  
11.1  
11.7  
12.2  
12.8  
13.3  
13.9  
14.4  
-
96  
98  
100  
102  
104  
106  
108  
110  
112  
-
NOTE  
Use this table for subcooling calculation ONLY. See Table 32 for superheat or control  
adjustment.  
8.1  
Calculating Subcooling  
Example  
Measure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that pressure  
on Table 33 (e.g., 93°F). Measure the temperature of the liquid line (e.g., 90°F). Subtract the actual  
temperature from the liquid saturation temperature to obtain the subcooling (e.g., 93 – 90 = 3°F). If  
the actual temperature is greater than the liquid saturation temperature, then there is no subcooling,  
and the fluid may be a mixture of liquid and vapor.  
Why There Are Two R407C Temperature and Pressure Tables  
R407C is a blend of refrigerants that exhibits a temperature “glide” of approximately 8 to 12°F  
(4 to 7°C. This “glide” is the difference between the liquid and vapor saturation temperatures at a  
given pressure. Use the correct table for the saturation temperature you need. Table 32 is for super-  
heat or operating controls. Table 33 is for subcooling only.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Ensuring The High Availability  
Of Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2008 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-11956_REV0_07-08  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2008 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Krown Manufacturing Universal Remote KA1000RR User Manual
Kyocera Telephone KPC680 User Manual
LG Electronics Cell Phone VX5300 User Manual
LG Electronics Range LRE30451 User Manual
Lindy Switch 32416 User Manual
Linksys Network Card WPC54GS User Manual
Manitowoc Ice Indoor Furnishings 7623123 User Manual
Marshall electronic Car Video System V R171P HDA User Manual
Maytag Dishwasher MDB7809AWB2 User Manual
Melissa Hair Dryer 235 009 User Manual