Liebert Electric Heater DPN002400 User Manual

Liebert DCP  
STANDARD FEATURES  
HEAT EXCHANGER - Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.  
PUMPS - Centrifugal type.  
STANDARD CONTROL PROCESSOR -  
The standard control system is microprocessor-based with an external LCD numerical display to allow  
observation of specified settable functions. Normal operating conditions are indicated on the LCD display panel,  
which is mounted to the unit. The control system also monitors unit operation and activates an alarm when any  
of the specified factory preset conditions are exceeded.  
CABINET AND FRAME -  
Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a  
protected enclosure for all high voltage components. Frame is constructed of 14 gauge heli-arc welded tubular steel  
and painted using an auto-deposition coating system.  
Page 1/5  
DPN002400  
REV DATE 11/11  
REV 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Liebert DCP  
Liebert DCP  
Bottom View  
Drip Tray Dimensions  
19.5”  
3.9”  
3.8”  
3.1”  
SECONDARY  
IN  
SECONDARY  
OUT  
7.2”  
6.5”  
BCW IN  
BCW OUT  
37”  
Unit Piping Outlet Connection Sizes, inches, Od Cu  
MODEL  
50/60 HZ  
DCP200  
Pipe Connection Point  
A
B
C
D
2-5/8  
2-5/8  
2-5/8  
2-5/8  
REV DATE 05/11  
PAGE 4/6  
Page 3/5  
DPN002400  
REV 0  
REV DATE 11/11  
REV 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Liebert DCP  
Liebert DCP  
Three phase electric service  
not provided by Liebert  
Monitoring panel  
Factory installed unit  
disconnect switch  
Field supplied disconnect switch may  
not be required, check local codes.  
ELECTRIC CONDUIT KNOCKOUTS  
On top of electric box. Knockout size  
2 in (51 mm)  
Three phase electric service  
not provided by Liebert  
THREE PHASE CONNECTION  
Electric service connection terminals  
CANBUS ISOLATOR  
ALARM AND WARNING OUTPUT RELAYS  
Field supplied 24V Class 2 wire for  
special alarms.  
EARTH GROUND LUG  
Connection terminal for  
field supplied earth  
grounding wire.  
(Not to exceed 1.0A @ 24v each.)  
REMOTE UNIT SHUTDOWN  
Factory installed disconnect switch  
Replace existing jumper between terminals  
37 & 38 with normally closed switch having  
a minimum 50VA rating. Use field supplied  
24V Class 2 wire.  
Factory wired to components  
on electric panel  
SITE MONITORING CONNECTION  
Terminals 77 (-) and 78 (+) are for  
connection of a 2 wire, twisted pair,  
communication cable (available from  
Liebert or others) for optional Sitescan.  
(see user's manual).  
INTELLISLOTS®  
Two Liebert Intellislots® for optional  
OCWEB-LBDS or OC485-LBDS card.  
60HZ COMPONETS SHOWN  
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.  
REV DATE 05/11  
PAGE 5/6  
Page 4/5  
DPN002400  
REV 0  
REV DATE 11/11  
REV 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Liebert DCP  
Liebert DCP  
Liebert DCP Extra Low Voltage field connection points  
TO P64 ON ICOM CONTROL BOARD  
RED ETHERNET CABLE  
TO P66 ON ICOM CONTROL BOARD  
TERMINATION PLUG  
TO REMOTE T/H SENSOR B  
TO REMOTE T/H SENSOR A  
COMMON WARNING OUTPUT  
TO OPTIONAL  
EXTERNAL  
FOR CONTACTS INDICATING AN  
ALARM CONDITION.  
(MAX) 1.0AMP @ 24V  
CONNECTIONS  
P66 P67  
P64  
K11  
K11  
K11NO K11COM K11NC  
TO REMOTE ALARM  
CIRCUIT BY OTHERS  
INPUT: REMOTE ALARM DEVICE  
FOR INDICATION OF ALARM, WIRE  
N.O. CONTACTS FROM REMOTE  
ALARM DEVICE AS SHOWN.  
UNIT DISPLAY(REARVIEW)  
24  
50  
N.O. CONTACT BY OTHERS  
FACTORY WIRED  
TEMPERATURE SENSOR.  
P67  
INPUT: CONDENSATION  
DETECTION  
ALARM WHEN CLOSED.  
DO NOT  
USE  
24  
51  
N.O. CONTACTS REQUIRED  
INPUT: FAN BREAKER STATUS  
1
ALARM WHEN CLOSED.  
24  
54  
N.O. CONTACTS REQUIRED  
COMMON ALARM OUTPUT  
FOR CONTACTS INDICATING AN  
ALARM CONDITION.  
(MAX) 1.0AMP @ 24V  
K3  
K3  
K3NO K3COM  
K3NC  
TO REMOTE ALARM  
CIRCUIT BY OTHERS  
1
INPUT: REMOTE SHUTDOWN  
NOTES:  
FOR SHUTDOWN OF CONTROL  
CIRCUIT, REMOVE JUMPER  
BETWEEN TERMINALS 37 & 38  
AND REPLACE WITH N.C. CONTACT  
1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN  
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).  
37  
38  
2. REQUIRES SHIELDED CABLE.  
N.C. CONTACTS BY OTHERS  
LIEBERT SITE MONITOR  
FOR DIGITAL COMMUNICATIONS  
WITH LIEBERT SITE MONITORS  
ONLY. CONNECT 2 WIRE TWISTED  
PAIR TO 77 & 78. ALSO SEE SITE  
MONITOR INSTALLATION MANUAL.  
2
77  
78  
(+)  
R or W  
(-)  
BK  
REV DATE 05/11  
PAGE 6/6  
Page 5/5  
DPN002400  
REV 0  
REV DATE 11/11  
REV 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Learning Resources Baby Toy LER 1883 User Manual
Lenoxx Electronics CD Player CDR1906 User Manual
LG Electronics CRT Television DU 27FB34C User Manual
Life Fitness Bicycle LC9100 User Manual
Lux Products Thermostat LV11 User Manual
Makita Router 3620A User Manual
M Audio Musical Instrument M71020QS EN User Manual
Maximatic Popcorn Poppers EPM 400 User Manual
Mellerware Coffeemaker 29500 User Manual
Mercury Automobile 2009 Mariner Hybrid User Manual