Liebert Clothes Dryer 1010 User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert® Air Cooled, Direct Drive Condensers  
Installation, Operation and Maintenance Manual - 50/60Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1.2.3 Liebert Lee-Temp Refrigerant Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
4.3  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure i  
TABLES  
Table 1  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1.0 INTRODUCTION  
1.1 Product Description and Features  
The Liebert condenser is low-profile direct-drive propeller fan-type air cooled unit suitable for mount-  
ing outdoors. It provides for the heat rejection of either one or two separate refrigeration circuits,  
matching heat rejection capacity varying with the outdoor ambient temperatures with each corre-  
sponding compressors heat rejection requirements. Constructed with an aluminum cabinet and a cop-  
per-tube aluminum fin coil, the unit is quiet and corrosion resistant. The condenser is quickly and  
easily installed, because all internal wiring is completed at the factory with only electrical connec-  
tions to be made at the job site. All electrical connections and controls are enclosed in an integral  
weatherproof section of the condenser.  
Figure 1 Liebert two-fan condenser  
1.2  
Head Pressure Control Types  
1.2.1 Fan Speed  
Fan speed control utilizes a wave-chopper control to vary the air volume over the condenser coil,  
based on refrigerant head pressure. The fan motor next to the electrical panel (two fans on 6-fan and  
8-fan models) is a single-phase, permanent split capacitor motor with motor speed adjusted in  
response to refrigerant pressure. The balance of fans on multi-fan units cycle on ambient thermostats.  
The control system provides refrigerant head pressure control for outdoor ambients as low as  
-20°F (-28.9 °C).  
1.2.2 Variable Frequency Drive  
VFD Condenser control system utilizes a variable frequency drive, inverter duty fan motor operating  
from 0% to 100% motor RPM based on head pressure, sensed by refrigerant pressure transducers.  
VFD, ambient-temperature thermostat(s), motor overload protection and electrical control circuit are  
factory-wired in the integral control panel. VFD controls the fan adjacent to the connection end of the  
condenser and remains energized with active compressor operation. The balance of fans on multi-fan  
units cycle on ambient thermostats. This system provides refrigerant head pressure control for out-  
door ambients as low as -20°F (-28.9°C).  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Introduction  
1.2.3 Liebert Lee-TempRefrigerant Control  
The Liebert Lee-Temp head pressure control system is designed to maintain proper operating head  
pressures in outdoor temperatures down to -30°F (-34.4°C). The condensers utilize head pressure con-  
trol valves, extra refrigerant and insulated refrigerant receivers with heater pads. It works by flood-  
ing the condenser coil with liquid refrigerant to a level that balances the system condensing  
requirements with the condenser coil surface available to reject the system heat. During the summer,  
the system requires the entire condenser coil surface for heat rejection and most of the refrigerant is  
stored in a receiver. In the winter, the same amount of heat can be rejected by only a fraction of the  
coil surface. As head pressure begins to fall, the control valve restricts the flow of liquid refrigerant  
exiting from the condenser. This extra liquid refrigerant reduces the effective condenser surface area  
available for heat transfer. The head pressure control valve also bypasses hot gas into the receiver to  
warm the liquid and maintain liquid pressure for proper operation of the expansion valve. Condenser  
fan controls are either fan cycling on ambient temperature or constant on. Lee-Temp control is  
required for Quiet-Line Condensers.  
1.3  
Sound Level Options  
1.3.1 Standard Condenser  
All Fan Speed and VFD Condensers are standard condensers with moderate operating sound levels.  
Lee-Temp Condensers with standard-size coils matching Fan Speed and VFD coil sizes are standard  
sound level condensers.  
1.3.2 Quiet-Line Condenser  
Quiet-Line condensers can help your facility meet the strictest noise codes and do so at less cost than  
traditional condensers with acoustical shielding. The Quiet-Line condensers utilize the same reliable  
construction features of the standard condensers and have oversized coils and slower speed fan  
motors which yield the required heat rejection needed at significantly lower sound levels. Lee-Temp  
control is required for Quiet-Line Condensers.  
1.4  
1.5  
Transient Voltage Surge Suppression Option  
Transient Voltage Surge Suppression (TVSS) panel is standard in the VFD Condenser models only.  
Surge protection is necessary because rooftop voltage supply often is not conditioned the same as the  
voltage supply inside the data center. The TVSS is designed to protect sensitive electronic condenser  
components from high voltage transients, up to 25kVA/phase.  
An illuminated green LED indicates power supply is On and panel status is OK. An illuminated red  
LED indicates conditions require service and the TVSS may require replacement to restore surge pro-  
tection to the condenser.  
Typical System Configurations  
Figure 2 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the  
outdoor condenser (VFD, Fan Speed Control or Lee-Temp) and field supplied interconnection piping.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Introduction  
Figure 2 Typical system configuration—indoor unit and outdoor condenser and field piping  
Relief  
Valve  
Service  
Valve  
Check  
Valve  
Inverted trap on discharge & liquid  
lines to extend above base of coil  
by a minimum of 7-1/2” (190mm).  
Liquid Return  
Head Pressure  
Control Valve  
Lee-Temp Receiver  
Fusible  
Plug  
Condenser Coil  
(Fan Speed  
and VFD)  
Condenser Coil  
(Lee-Temp)  
Hot Gas  
Discharge  
Lee-Temp  
Fan Speed and VFD  
Liquid  
* Traps every  
28-42kW Digital Solenoid Valve  
Sensing  
Bulb  
25ft (7.6m)  
of rise  
Evaporator Coil  
53-70kW Digital  
Solenoid Valve  
Suction  
Service  
Valve  
Field-installed relief valve(s) required  
for 50 Hz EU CE units rated maximum  
480 PSIG (33 Bar).  
Service  
External  
Equalizer  
Compressor Valve  
Check  
Valve  
* Isolation  
valve  
Pitch horizontal hot gas piping  
1/2" per 10 ft. (42mm per 10m)  
in direction of refrigerant/oil flow.  
Hot Gas Discharge  
Liquid Return  
Expansion Solenoid  
* Isolation  
valve  
Sight Glass  
Filter Dryer  
Valve  
Valve  
Factory Refrigerant Piping  
Field Refrigerant Piping  
Service/Schrader (Access) Connection No Valve Core  
*
Components are not supplied by  
Liebert, but are recommended  
for proper circuit operation and  
maintenance.  
Service/Schrader (Access) Connection With Valve Core  
Note: Schematic representation shown . Do not use for specific connection locations.  
Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .  
DPN000798  
Rev. 2  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation  
2.0 SITE PREPARATION  
2.1 Site Considerations  
The condensers should be installed in a location offering maximum security and access for mainte-  
nance.  
Avoid ground-level sites with public access and areas that contribute to heavy snow or ice accumula-  
tions. Utilize Piggyback condensers whenever interior building locations must be used. To ensure ade-  
quate air supply, Liebert recommends that condensers be installed in an area with clean air, away  
from loose dirt and foreign matter that might clog the coil. In addition, condensers should not be  
located near steam, hot air or fume exhausts. Also, the condensers should be located no closer than  
3 feet (1m) from a wall, obstruction or adjacent unit.  
The condenser must not be installed in a pit.  
The condenser must be installed on a level surface to ensure proper refrigerant flow.  
For roof installation, mount the condenser on suitable curbs or other supports in accordance with  
local codes.  
Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. Remote  
mounting of tanks must be within 10 feet of the condenser—Contact Liebert Application Engineering  
Department for assistance.  
2.2  
Dimensions and Weights  
Table 1  
Condenser shipping weights, dimensions and volume, approximate  
Domestic Packaging  
Export Packaging  
Dimensions  
(LxWxH)  
in. (mm)  
Dimensions  
(LxWxH)  
in. (mm)  
Number  
of Fans  
Weight  
lb (kg)  
Volume  
ft (m )  
Weight  
lb (kg)  
Volume  
ft (m )  
3
3
3
3
Model  
*C**083  
*C**104  
DC**063  
*C**165  
*C**205  
DC**119  
DC**127  
DC**143  
*C**251  
*C**308  
DC**214  
*C**415  
*C**510  
DC**286  
*C**616  
DC**409  
*CD*830  
*CD*1010  
DC**572  
1
1
1
2
2
2
2
2
3
3
3
4
4
4
6
6
8
8
8
330 (150)  
350 (159)  
350 (159)  
490 (222)  
560 (254)  
490 (222)  
560 (254)  
655 (297)  
590 (268)  
760 (345)  
885 (401)  
935 (424)  
1230 (558)  
1185 (537)  
1560 (708)  
1620 (735)  
1930 (875)  
415 (188)  
435 (197)  
435 (197)  
690 (313)  
760 (345)  
690 (313)  
760 (345)  
855 (388)  
870 (395)  
1040 (472)  
1165 (528)  
1235 (560)  
1530 (694)  
1485 (674)  
2010 (912)  
2070 (939)  
2430 (1102)  
59x30x51  
(1500x760x1300)  
60x31x52  
(1520x790x1320)  
52 (1.4)  
56 (1.5)  
97x30x51  
(2460x760x1300)  
98x31x52  
(2490x790x1320)  
86 (2.4)  
91 (2.5)  
139x30x51  
(3530x760x1300)  
140x31x52  
(3560x790x132)0  
123 (3.4)  
131 (3.5)  
179x30x51  
(4550x760x1300)  
180x31x52  
(4570x790x1320)  
158 (4.4)  
291 (8.3)  
168 (4.5)  
301 (8.4)  
384 (10.)  
144x36x97  
(3660x910x2460)  
145x37x97  
(3680x940x2460)  
184x36x97  
(4670x910x2460)  
185x37x97  
(4700x940x2460)  
2910 (1321)  
2575 (1168)  
372 (10.) 3410 (1548)  
3075 (1395)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Site Preparation  
Figure 3 Condenser planning dimensional data—One-fan and two-fan units  
43-9/16"  
51-1/2"  
(1106mm)  
(1308mm)  
43-9/16"  
(1106mm)  
91-1/2"  
(2324mm)  
37-7/8"  
(962mm)  
37-7/8"  
(962mm)  
18"  
(457mm)  
43-3/16"  
(1097mm)  
44"  
(1118mm)  
18"  
(457mm)  
84"  
Note:  
(2134mm)  
Overall height to the top of fan guard  
43-1/8" (1095mm)  
43-3/16"  
(1097mm)  
Liebert recommends a clearance  
of 36" (915mm) on each side for  
proper operation and component  
access.  
42"  
ANCHOR PLAN  
(1067mm)  
ANCHOR PLAN  
82" (2083mm)  
42"  
(1067mm)  
One-Fan  
41-3/16"  
Condenser  
(1046mm)  
Electric  
Box  
End  
Two-Fan  
Condenser  
Legs supplied with  
Lee-Temp option only  
41-3/16"  
(1046mm)  
See Figure 6 for typical condenser  
footprint dimensions.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation  
Figure 4 Condenser planning dimensional data—Three-fan and four-fan units  
43-9/16"  
(1106mm)  
131-1/2"  
(3340mm)  
43-9/16"  
(1106mm)  
37-7/8"  
(962mm)  
171-1/2"  
(4356mm)  
70"  
(1778mm)  
37-7/8"  
(962mm)  
18"  
(457mm)  
Eyebolts  
for Lifting  
124"  
(3150mm)  
18"  
(457mm)  
43-3/16"  
(1097mm)  
164"  
Note:  
(4166mm)  
Overall height to the top of fan guard  
43-1/8" (1095mm)  
Liebert recommends a clearance  
of 36" (915mm) on each side for  
proper operation and component  
access.  
43-3/16"  
(1097mm)  
ANCHOR PLAN  
122" (3099mm)  
See Figure 6 for typical  
condenser footprint  
dimensions.  
42"  
(1067mm)  
Electric  
Three-Fan  
Condenser  
Box  
End  
Legs supplied with  
Lee-Temp option only  
41-3/16"  
(1046mm)  
ANCHOR PLAN  
82" (2083mm)  
80"  
(2032mm)  
42"  
(1067mm)  
Electric  
Box  
End  
Four-Fan  
Condenser  
Legs supplied with  
Lee-Temp option only  
41-3/16"  
(1046mm)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation  
Figure 5 Condenser planning dimensional data—Six- and eight-fan units  
87-1/8"  
(2213mm)  
131-1/2"  
(3340mm)  
87-1/8"  
(2213mm)  
171-1/2"  
(4356mm)  
37-7/8"  
(962mm)  
37-7/8"  
(962mm)  
59"  
(1499mm)  
18"  
(457mm)  
18"  
(457mm)  
124"  
(3150mm)  
70" (1778mm)  
86-3/4"  
164"  
(4166mm)  
(2203mm)  
1-1/2" (38mm)  
diameter  
hole for rigging  
(typ.4)  
Liebert recommends a  
clearance of 36" (915mm)  
on each side for proper  
operation and component  
access.  
Overalll height to the top  
86-3/4"  
(2203mm)  
of the fan guard is 43-1/8” (1095mm).  
ANCHOR PLAN  
122" (3099mm)  
42"  
(1067mm)  
Electric  
Box  
End  
See Figure 6 for typical  
condenser footprint dimensions.  
Legs supplied with  
Lee-Temp option only  
84-3/4"  
(2153mm)  
Six-Fan  
Condenser  
ANCHOR PLAN  
82" (2083mm)  
42"  
(1067mm)  
80" (2032 mm)  
Electric  
Box  
End  
Eight-Fan  
Condenser  
Legs supplied with  
Lee-Temp option only  
84-3/4"  
(2153mm)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation  
Figure 6 Typical condenser footprint—dimensions  
1”  
(25.4mm)  
1-3/4”  
4-1/4”  
(44.5mm)  
(108mm)  
2”  
(50.8mm)  
1-3/4”  
(44.5mm)  
9/16" (14mm)  
Typical Diameter  
4-1/4”  
(108mm)  
2”  
(50.8mm)  
Figure 7 Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers  
Traps to extend above  
Entering  
coil base by a minimum  
Hot Gas Line  
of 7-1/2" (190mm)  
Inverted Traps  
(field-supplied)  
Leaving  
Liquid Line  
Metal  
clamp  
Fasten liquid and hot gas lines  
See  
to leg using flat surface clamps  
with isolators (field-supplied).  
Support field piping separately  
to avoid coil damage and loss  
of charge.  
Isolator  
Detail  
A-A  
Detail A-A  
DPN000665  
Rev. 02  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation  
Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers  
Inverted Traps (field-supplied)  
to extend 8" (203mm) above  
coil base  
Hot Gas  
Line  
Liquid  
Entering  
Line  
Hot Gas Line  
Fasten liquid and hot gas lines  
to leg using flat surface clamps  
with isolators (field-provided).  
Support field piping separately  
to avoid coil damage and loss  
of charge.  
Leaving  
Liquid  
Line  
See Detail A-A  
Position elbow  
to direct relief  
valve downward  
Metal clamp  
Isolator  
DPN001067  
Rev. 0  
Detail A-A  
Figure 9 Piping connections for 6- and 8-fan Fan Speed Condensers  
Access Valve (Hot Gas) on  
Condensers (Typ. 2)  
Inlet Connection  
Inverted traps (field-supplied)  
to extend above base of coil by  
a minimum of 7-1/2" (190mm).  
Upper Headers  
Entering  
(Typ.)  
Hot Gas  
Line  
Leaving  
Liquid Line  
Metal  
Clamp  
Condenser  
Connections,  
Typical  
See  
Detail  
A-A  
Isolator  
Detail A-A  
Fasten liquid and hot gas lines  
to leg using flat surface clamps  
with isolators (field-supplied).  
DPN000668  
Rev. 01  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation  
Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers  
Access Valve (Hot Gas) on  
Condensers (Typ. 2)  
Inverted traps (field-supplied)  
to extend above base of coil by  
a minimum of 7-1/2" (190mm).  
Inlet Connection  
Upper Headers (Typ.)  
Condenser  
Connections,  
Typical  
Entering Hot  
Gas Line  
Liquid  
Line  
Hot Gas Line  
Leaving  
Liquid Line  
Fasten liquid and hot gas lines  
to leg using flat surface clamps  
with isolators (field-supplied).  
Position elbow  
to direct relief  
See  
Detail  
A-A  
valve downward  
Metal  
Clamp  
Note: Two circuits supplied; single circuit shown for clarity.  
Isolator  
DPN000670  
Rev. 01  
Detail A-A  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Site Preparation  
Table 2  
Condenser physical data  
Connection Size, OD, In.  
Number  
of Fans  
Number  
of Circuits  
Net Weight  
lb (kg)  
Model #  
Hot Gas  
Liquid  
Standard Models  
CS*083  
CD*104  
CS*104  
CD*165  
CS*165  
CD*205  
CS*205  
CD*251  
CS*251  
CD* 308  
CS*308  
CD* 415  
CS*415  
CD*510  
CD*616  
1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
2
1
2
2
7/8  
7/8  
5/8  
1/2  
295 (134)  
315 (143)  
315 (143)  
425 (193)  
425 (193)  
495 (225)  
495 (225)  
500 (227)  
500 (227)  
670 (304)  
670 (304)  
840 (381)  
840 (381)  
1188 (539)  
1380 (626)  
1380 (626)  
1750 (794)  
2640 (1197)  
1
1
2
2
2
2
3
3
3
3
4
4
4
6
6
8
8
1-1/8  
7/8  
5/8  
5/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-3/8  
1-3/8  
1-5/8  
1-3/8  
1-5/8  
1-5/8  
1-5/8  
(2)1-5/8  
1-5/8  
2-1/8  
7/8  
7/8  
7/8  
7/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
(2)1-1/8  
1-1/8  
1-5/8  
CS*616  
CD*830  
CD*1010  
Quiet-Line Models  
DCS*063  
DCD*063  
DCS*119  
DCD*119  
DCS*127  
DCD*127  
DCS*143  
DCD*143  
DCS*214  
DCD*214  
DCS*286  
DCD*286  
DCD*409  
DCD*572  
1
1
2
2
2
2
2
2
3
3
4
4
6
8
1
2
1
1
1
2
1
2
1
2
1
2
2
2
1-1/8  
7/8  
5/8  
1/2  
315 (143)  
315 (143)  
425 (193)  
425 (193)  
495 (225)  
495 (225)  
515 (234)  
515 (234)  
840 (381)  
840 (381)  
1105 (501)  
1105 (501)  
1380 (626)  
2430 (1102)  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-1/8  
1-5/8  
1-1/8  
2-1/8  
1-1/8  
1-5/8  
2-1/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
1-1/8  
7/8  
1-1/8  
7/8  
1-1/8  
1-1/8  
1. Interconnection piping (field-supplied and installed) required. Configure piping for parallel  
refrigerant flow between condenser sections.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Site Preparation  
2.3  
Refrigerant Planning Values  
Planning for the refrigerant requirements of the completed system is the addition of the charges from  
Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping.  
Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting  
piping. Consult indoor unit manuals for indoor unit charge requirements.  
These values can be used for obtaining adequate refrigerant for the system, but should not be used for  
final charging. Consult indoor unit manual for charging procedures.  
Table 3  
R-22 and R-407C refrigerant required, approximate  
Approximate R-22 Refrigerant Needed Approximate R-407C Refrigerant Needed  
Single Circuit  
lb (kg)  
Dual Circuit  
lb/circuit (kg/circuit)  
Single Circuit  
lb (kg)  
Dual Circuit  
lb/circuit (kg/circuit)  
Standard  
Condenser FSC or  
Lee-Temp  
(includes  
receiver)  
Lee-Temp  
(includes  
receiver)  
Lee-Temp  
(includes  
receiver)  
Lee-Temp  
(includes  
receiver)  
FSC or  
VFD  
FSC or  
VFD  
FSC or  
VFD  
Models  
VFD  
83  
5 (2.3)  
8 (3.6)  
15 (6.8)  
20 (9.1)  
19 (8.6)  
27 (12.3)  
39 (17.7)  
53 (24.0)  
76 (34.5)  
75 (34.0)  
3 (1.4)  
7 (3.2)  
5 (2.3)  
7 (3.2)  
10 (4.6)  
11 (5.0)  
15 (6.8)  
15 (6.8)  
21 (9.5)  
5 (2.3)  
8 (3.6)  
26 (11.8)  
37 (16.8)  
50 (22.7)  
72 (32.7)  
71 (32.23)  
3 (1.4)  
7 (3.2)  
5 (2.3)  
7 (3.2)  
10 (4.6)  
11 (5.0)  
15 (6.8)  
15 (6.8)  
20 (9.0)  
104  
165  
205  
251  
308  
415  
510  
616  
830  
1010  
27 (12.3)  
38 (17.2)  
38 (17.2)  
58 (26.3)  
75 (34.0)  
15 (6.8)  
19 (8.6)  
18 (8.2)  
26 (11.8)  
36 (16.3)  
36 (16.3)  
55 (24.9)  
71 (32.2)  
29 (13.2) 113 (51.3)  
54 (24.5) 182 (82.6)  
28 (12.7) 107 (48.5)  
51 (23.1) 173 (78.4)  
72 (32.7)  
N/A  
N/A  
267 (121.3) 27 (12.3) 113 (51.3)  
30 (13.6) 149 (67.6) 68 (30.8)  
N/A  
254 (115.2) 26 (11.8) 108 (49.0)  
29 (13.2) 142 (64.4)  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
30 (13.6) 149 (67.6)  
60 (27.2) 154 (69.9)  
N/A  
N/A  
29 (13.2) 142 (64.4)  
57 (25.9) 147 (66.7)  
N/A  
Quiet-Line Condenser Models  
63  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
39 (17.7)  
50 (22.7)  
76 (34.5)  
126 (57.2)  
161 (73.0)  
196 (88.9)  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
21 (9.5)  
27 (12.3)  
38 (17.2)  
64 (29.0)  
81 (36.7)  
125 (56.7)  
129 (58.5)  
196 (88.9)  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
37 (16.8)  
48 (21.8)  
72 (32.6)  
120 (54.5)  
153 (69.4)  
186 (84.4)  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
20 (9.1)  
26 (11.8)  
36 (16.3)  
61 (27.7)  
77 (34.9)  
119 (54.0)  
125 (55.8)  
186 (84.4)  
119  
127  
143  
214  
286  
409  
572  
N/A  
N/A  
Table 4  
Interconnecting piping refrigerant charge  
R-22, lb/100 ft. (kg/30m) R-407C, lb/100 ft. (kg/30m)  
Line Size,  
O.D., in.  
Liquid Line  
3.8 (1.7)  
Hot Gas Line  
Liquid Line  
3.7 (1.7)  
6.9 (3.1)  
11.0 (5.0  
15.7 (7.1)  
23.0 (10.4)  
39.3 (17.8)  
59.8 (27.1  
Hot Gas Line  
3/8  
1/2  
7.3 (3.3)  
5/8  
11.7 (5.3)  
16.6 (7.5)  
24.4 (11.1)  
41.4 (18.9)  
63.3 (28.7)  
2.1 (1.0)  
3.0 (1.4)  
4.4 (2.0)  
7.8 (3.5)  
11.8 (5.4)  
16.7 (7.6)  
2.2 (1.0)  
3.1 (1.3)  
4.5 (1.9)  
7.8 (3.5)  
11.8 (5.4)  
16.7 (7.6)  
3/4  
7/8  
1-1/8  
1-3/8  
1-5/8  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Inspection and Installation  
3.0 INSPECTION AND INSTALLATION  
3.1 Equipment Inspection  
Before unpacking the condenser, verify that the labeled equipment matches the bill of lading. Care-  
fully inspect all items for damage, either visible or concealed. Report any damage immediately to the  
carrier and your local Liebert representative. File a damage claim with the carrier and send a copy to  
your local Liebert representative.  
3.1.1 Packing Material  
All material used to package this unit is recyclable. Please save it for future use or  
dispose of the material appropriately.  
R
SAFETY INFORMATION  
WARNING  
!
Risk of top-heavy unit falling over. Can cause equipment damage, injury or death.  
Read all of the following instructions before attempting to move, lift, remove packaging from  
or preparing unit for installation.  
WARNING  
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.  
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,  
shoes, glasses and protective clothing should attempt to move, lift, remove packaging from or  
prepare unit for installation.  
NOTICE  
Risk of overhead interference. Can cause unit and/or structure damage.  
Refer to the installation plans prior to moving the unit to verify clearances.  
NOTICE  
Risk of damage from forklift. Improper handling with the forklift. Can cause exterior and/or  
underside damage.  
Keep tines of the forklift level and at a height suitable to fit below the skid.  
NOTICE  
Risk of unit damage if improperly stored. Keep the unit upright, indoors and protected from  
dampness, freezing temperatures and contact damage.  
Figure 11 Equipment recommended for handling a Liebert condenser  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Inspection and Installation  
3.2  
Handling Unit on the Skid  
Transport the unit using a fork lift or a crane with sling and spreader bars.  
• If using a fork lift, make sure the forks (if adjustable) are spread to the widest allowable distance  
to still fit under the skid.  
• Ensure the fork length is suitable for the unit length.  
• When moving the packaged unit, do not lift the unit any higher than 6" (152mm) off the ground.  
Exercise great care if the unit must be lifted higher than 6" (152mm). Personnel not involved in  
moving the unit must be at least 20' (6m) from the lift point of the unit.  
3.3  
Unpacking the Unit  
Remove outer packaging when ready to install the unit. Be sure to locate, and set aside, the bag of  
mounting hardware that is to be used for mounting the support legs on the unit.  
Figure 12 Removing shipping crate  
Three-fan unit shown for illustration.  
Methods for other sizes of condensers are the same.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Inspection and Installation  
3.4  
Preparing a 1-, 2-, 3- or 4-Fan Condenser for Moving and Installation  
3.4.1 Removing the Skid and Attaching Slings  
1. Install the legs, provided by Liebert, on the condenser with the mounting bolts, also provided by  
Liebert. Liebert recommends using a 5/8" socket and ratchet.  
2. Place slings or equivalent items through holes in the legs on 1, 2- and 3-fan condensers (see Step  
2 and Step 3 in Figure 13). Use eyebolts for attaching a sling or similar equipment to 4-fan  
units.  
3. Using spreader bars and a crane, or similar lifting equipment, lift the condenser off the skid to  
allow safely turning the condenser upright.  
4. Lift the condenser and move it to the installation location.  
Figure 13 Attaching legs and sling to a 1-, 2-, 3- or 4-fan condenser for moving  
Step 1  
Step 2  
Step 3  
Three-fan unit shown for illustration.  
Method for 1-fan and 2--fan condensers is the same.  
Attach sling to 4-fan condensers with eyebolts.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Inspection and Installation  
3.5  
Preparing a 6-Fan or 8-Fan Condenser for Moving and Installation  
3.5.1 Removing the Skid and Attaching Slings  
The following procedure is one recommended process for removing a Liebert condenser from its ship-  
ping skid. Other methods may be used, provided that the methods are safe for personnel, the con-  
denser and equipment.  
1. Place a sling through to rigging attachment points as shown in Step 1 in Figure 14.  
2. Raise the condenser high enough that the skid can be safely removed.  
3. Place protective material under the unit to protect it from scrapes and gouges. Lower the  
condenser onto the material.  
4. Lower the condenser to an angle and distance that will allow attaching the legs to one side of the  
condenser. The number of legs varies according to the condenser model.  
5. Install the legs, provided by Liebert, on the condenser with the mounting bolts, also provided by  
Liebert. Liebert recommends using a 5/8" socket and ratchet.  
6. Turn the condenser so that the legs just installed support one side of the unit as shown in Step 3  
in Figure 14.  
7. Remove the sling and it attach it to the opposite side of the condenser as shown in Step 4 in  
8. Raise the condenser to an angle to safely install legs on the opposite side of the condenser.  
9. Lower the condenser so all legs support it.  
10. Place slings on both sides of the condenser to lift and move it to the installation location.  
Figure 14 Attaching legs to a 6-fan or 8-fan unit  
Step 1  
Step 2  
Step 3  
Protective Material  
Under the Condenser  
Six-fan unit shown for illustration.  
Method for eight-fan condenser is  
the same.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Inspection and Installation  
Figure 15 Attaching sling to a 6-fan or 8-fan unit for moving  
Step 4  
Step 5  
Six-fan unit shown for illustration.  
Method for 8-fan condenser is the same.  
3.5.2 Mounting the Condenser  
The condenser must be installed so that it is level within 1/2" (13mm) to ensure proper refrigerant  
flow. For roof installation, mount the condenser on suitable curbs or other supports; follow all local  
and national codes. Secure the legs to the mounting surface using a field-supplied 1/2" (13mm) diame-  
ter bolt in each of the two 5/8" (16mm) holes in each leg. See Figures 3, 4 and 5 for anchor dimen-  
sions.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Inspection and Installation  
3.6  
Electrical Supply Preparation  
Line voltage electrical service is required for all models. Refer to equipment nameplate regarding  
wire size and circuit protection requirements. Electrical service must conform to national and local  
electrical codes. Refer to Figures 19, 20 and 21 for electrical service entrances into unit. Refer to  
electrical schematic when making connections.  
Each unit is shipped from the factory with all internal unit wiring completed.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electrical power supplies before working within the electrical  
enclosure.  
The line side of the disconnect remains energized when the disconnect is Off.  
Use a voltmeter to verify that the electrical power is Off before performing any electrical  
and/or mechanical service and/or maintenance operations.  
WARNING  
!
Risk of high speed moving parts. Can cause injury or death.  
The fan(s) blades can start to rotate unexpectedly when the power is On. Disconnect all local  
and remote electrical power supplies before working within the fan compartment.  
Use a voltmeter to verify that the electrical power is Off before performing any electrical  
and/or mechanical service and/or maintenance operations.  
Each unit is shipped from the factory with all internal unit wiring completed. Refer to the electrical  
schematic supplied with the condenser when making line voltage supply, low voltage indoor unit  
interlock and any low voltage alarm connections. All wiring must be done in accordance with all appli-  
cable local, state and national electrical codes.  
3.6.1 Line Voltage Wiring  
WARNING  
!
Risk electrical fire and short circuit. Can cause property damage, injury or death.  
Select and install the electrical supply wire and overcurrent protection device(s) according to  
the specifications on the unit nameplate(s), per the instructions in this manual and according  
to the applicable national, state and local code requirements. Use copper conductors only.  
Make sure all electrical connections are tight. Unit-specific wiring diagrams are provided on  
each unit.  
Condenser-rated voltage should be verified with available power supply before installation. Refer to  
the unit’s electrical schematic and serial tag for specific electrical requirements.  
Line voltage electrical service is required for all condensers at the location of the condenser. The  
power supply does not necessarily have to be the same voltage supply as required by the indoor unit  
connected to the condenser. See the unit’s serial tag for specific condenser electrical requirements. A  
unit disconnect is standard on VFD and Quiet-Line Condensers and is optional on Fan Speed Control  
and standard Lee-Temp condensers. However, a site disconnect may be required per local code to iso-  
late the unit for maintenance. Route the supply power to the site disconnect switch and then to the  
unit. Route the conduit through the hole provided in the cabinet. Connect earth ground to lug pro-  
vided near terminal board.  
NOTE  
Lee-Temp and Quiet-Line Condensers require a separate line voltage electrical supply for the  
heated receivers. See Table 8 for power requirements.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Inspection and Installation  
Table 5  
Model #  
60Hz condenser data  
83, 104  
1
165, 205  
2
251, 308  
3
415, 510  
4
616  
830, 1010  
8
# of Fans  
6
Input  
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD  
Fan Speed Controlled  
208/230  
460  
4.8 6.0  
2.5 3.1  
1.9 2.4  
15  
15  
15  
1
3
575  
208/230  
460  
8.3 9.5  
4.2 4.8  
3.3 3.8  
15 11.8 13.0 15 15.3 16.5 20 23.6 24.8 25 30.6 31.8 35  
15 5.9 6.5  
15 4.7 5.2  
15 7.6 8.2  
15 6.1 6.6  
15 11.8 12.4 15 15.2 15.8 20  
15 9.4 9.9 15 12.2 12.7 15  
575  
VFD Controlled  
208/230  
460  
3.7 4.6  
1.8 2.3  
15 7.2 8.1  
15 3.5 4.0  
15 10.7 11.6 15 14.2 15.1 20 N/A N/A N/A N/A N/A N/A  
15 5.2 5.7 15 6.9 7.4 15 N/A N/A N/A N/A N/A N/A  
3
Lee-Temp Controlled/Fan-Cycling  
208/230  
460  
3.5 4.4  
1.7 2.1  
1.4 1.8  
15 7.0 7.9  
15 3.4 3.8  
15 2.8 3.2  
15 10.5 11.4 15 14.0 14.9 15 21.0 21.9 25 28.0 28.9 30  
3
15 5.1 5.5  
15 4.2 4.6  
15 6.8 7.2  
15 5.6 6.0  
15 10.2 10.6 15 13.6 14.0 15  
575  
15 8.4 8.8  
15 11.2 11.6 15  
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device  
Table 6  
Model # ph  
# of Fans  
Input  
60Hz condenser data, Quiet-Line (Lee-Temp controlled/fan-cycling)  
63  
1
119, 127, 143  
2
214  
3
286  
4
409  
6
572  
8
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD  
208/230  
460  
1.8 2.3  
0.9 1.1  
0.7 0.9  
15 3.6 4.1  
15 1.8 2.0  
15 1.4 1.6  
15 5.4 5.9  
15 2.7 2.9  
15 2.1 2.3  
15 7.2 7.7  
15 3.6 3.8  
15 2.8 3.0  
15 10.8 11.3 15 14.4 14.9 15  
3
15 5.4 5.6  
15 4.2 4.4  
15 7.2 7.4  
15 5.6 5.8  
15  
15  
575  
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device  
Table 7  
50Hz condenser full load amp values  
Condenser  
Control Type  
Fan Speed  
Controlled  
VFD  
Controlled  
Lee Temp  
Controlled/Fan-Cycling  
Quiet-Line (Lee Temp  
Controlled/Fan-Cycling)  
Input  
Voltage - Phase  
Input  
Voltage - Phase  
Input  
Voltage - Phase  
Input  
Voltage - Phase  
Model  
#
# of  
Model  
Fans 200/230-1 380/415-3 200/230-3 380/415-3 200/230-3 380/415-3  
#
200/230-3 380/415-3  
83, 104  
1
4.0  
-
3.7  
1.8  
3.5  
1.7  
63  
1.8  
0.9  
119,  
127,  
143  
165, 205  
2
3.7  
7.2  
3.5  
7.0  
3.4  
3.6  
1.8  
251, 308  
415, 510  
616  
3
4
6
8
5.4  
7.1  
10.7  
14.2  
5.2  
6.9  
10.5  
14.0  
21.0  
28.0  
5.1  
6.8  
214  
286  
409  
572  
5.4  
7.2  
2.7  
3.6  
5.4  
7.2  
10.8  
14.2  
10.2  
13.6  
10.8  
14.4  
830, 1010  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Inspection and Installation  
Table 8  
Lee-Temp receiver electrical data, 50Hz and 60Hz  
Rated Voltage - Single Phase  
Watts/Receiver  
120  
200/208/230  
150 300 450  
150  
1.4  
1.8  
300 450  
Full Load Amps  
2.8  
3.5  
4.2  
5.3  
0.7  
0.9  
1.4  
1.8  
2.1  
2.7  
Wire Size Amps  
Maximum Overcurrent  
Protection Device, Amps  
15  
15  
15  
15  
15  
15  
3.6.2 Low Voltage Control Wiring  
NOTICE  
Risk of control malfunction. Can cause improper unit operation. Make sure that all low  
voltage electrical wiring has been performed per the schematic diagram provided and that all  
low voltage wiring connections are tight.  
A control interlock between the condenser and the indoor cooling units is required. Field-supplied cop-  
per wire (Class 1 for TCDV models and Class 2 for all other condenser models) is required for connec-  
tion between like-numbered terminals 70 & 71 on both units. Wiring must be sized so that the voltage  
drop in the circuit does not exceed 1 volt. See Figures 19, 20 and 21 and indoor unit manual for loca-  
tion of terminals on condensers and indoor units.  
3.6.3 Low Voltage Monitoring Wiring—TCDV Only  
Condensers with monitoring terminals may be wired with Class 1 copper wire to the indoor cooling  
unit or other monitoring panel. Wiring must be sized so that the voltage drop in the circuit does not  
exceed 1 volt. Dry contacts close when a monitored event occurs. Consult condenser electrical sche-  
matic, supplied with the unit, for details.  
Contact closure on VFD Drive monitoring terminals indicates a permanent VFD fault. A factory-pro-  
grammed VFD must be used as the replacement.  
Contact closure on TVSS monitoring terminals may indicate unit trouble ranging from electrical sup-  
ply issues to TVSS replacement required. A properly trained and qualified electrician is required.  
3.7  
Electrical Connections  
Electrical service is required for all models. Electrical service shall conform to national and local elec-  
trical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements.  
Refer to electrical schematic when making connections. Refer to Figures 19, 20 and 21 for electrical  
service entrances into unit.  
A manual electrical disconnect switch should be installed in accordance with local codes. Consult local  
codes for external disconnect requirements.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working in the unit. Unit  
contains lethal voltage in some circuits. Use voltmeter to make sure power is turned Off  
before making any electrical connections.  
NOTICE  
Installation and service of this equipment should be done only by properly trained and  
qualified personnel who have been specially trained in the installation of air conditioning  
equipment.  
NOTICE  
Use copper wiring only. Make sure that all conections are tight.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Inspection and Installation  
3.7.1 VFD Control Condensers (TCDV) only  
The installer/startup technician must determine the type of 3-phase supply power being used for the  
VFD Control Condenser: Wye-connected power or Delta- connected power.  
Wye-connected power has two different voltages that can be measured: Phase-to-Phase voltage (this  
is equal to the nominal input voltage) and Phase-to-Neutral voltage (typically used for small single  
phase loads (120 VAC or 277 VAC). See Figure 16.  
Delta-connected power only has one voltage level that can be measured: Phase-to-Phase. See  
3.7.2 Wye-Connected Power Supply  
No control changes are required if the Liebert VFD Control Condenser will be operated with Wye-con-  
nected power.  
Figure 16 Wye-connected power diagram  
Phase A  
Winding  
Phase B  
B
Winding  
A
Neutral  
Winding  
Phase C  
C
3.7.3 Delta-Connected Power Supply  
Figure 17 Delta-connected power diagram  
Phase A  
Winding  
A-B  
Winding  
C-A  
Phase B  
Phase C  
Winding B-C  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Inspection and Installation  
Disconnect EMC Filter for Delta-Connected Power  
Installer/startup technician needs to disconnect the EMC filter on the VFD to ensure proper operation  
if the Liebert VFD Control Condenser will be operated with Delta-connected power.  
1. Disconnect the power supply before working on the unit.  
2. Open the electrical panel cover and locate the VFD (Refer to Figure 20).  
3. Using Figure 18, locate the small black plastic tab immediately to the right of the wiring  
connection block of the VFD control  
4. Pull the tab to fully extend it, disconnecting the EMC filter from the circuit.  
Figure 18 Disconnecting EMC filter for operation with Delta-connected power  
A
Internal  
EMC filter  
Tab fully inserted:  
EMC filter fitted  
B
Internal  
EMC filter  
Tab fully extended:  
EMC filter disconnected  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Inspection and Installation  
3.8  
Electrical Field Connection Descriptions  
Figure 19 Electrical field connections for Fan Speed Control Condensers  
Electric service connection  
terminals when factory  
disconnect is NOT supplied.  
Electric service connection  
and fuse block.  
Factory wired to 24V  
Class 2 control circuit.  
Electric service connection  
terminals when factory  
disconnect is supplied.  
Control interlock (70, 71)  
Field-supplied Class 2 wiring to  
interlock condenser 24V controls  
to Liebert room unit;  
Factory installed disconnect  
switch (optional).  
7/8 in. (22.2mm) diameter  
hole provided in bottom  
of electric box.  
Electric service entrance. A 7/8  
in. (22.2mm) diameter hole in a  
1 1/8 in (28.6mm) knockout  
Factory-wired to components  
on electric panel.  
Earth ground bar (optional on 50Hz only).  
Connection terminals with factory  
ground from each high voltage  
component for field-supplied  
earth grounding wire.  
provided in bottom of electric box.  
Electric service, not by Liebert.  
Single-phase for condenser  
models CSF, CDF with single  
fan motor. Three-phase for  
all other condenser models.  
Earth ground connection (60Hz).  
Connection terminals for field  
supplied earth grounding wire  
when factory disconnect is NOT  
supplied.  
Earth ground connection (60Hz).  
Connection terminal for field-  
supplied earth grounding wire  
when factory disconnect is  
supplied.  
DPN000666  
Rev. 0  
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Inspection and Installation  
Figure 20 Electrical field connections for VFD control condensers  
Factory-installed fuse block on  
60Hz units. Circuit breaker supplied  
in lieu of fuse block on 50Hz units.  
Factory-wired to 24V  
control circuit.  
Control interlock (70, 71)  
Field-supplied  
Class 1 wiring to  
Electric service connection  
interlock condenser 24V  
controls to Liebert  
room unit; 7/8 in.  
terminals with factory-  
supplied disconnect.  
(22.2mm) diameter  
hole provided in  
bottom of electric box.  
Factory-installed  
disconnect switch.  
Alarm Connections  
Field-supplied 24V Class 1  
wiring to remote alarm circuits  
Variable Frequency Drive (VFD)  
alarm contact connections (13, 14)  
Transient Voltage Surge Suppressor (TVSS)  
alarm contact connections (11, 12).  
Electric service entrance.  
A 7/8" (22.2mm) diameter  
hole in a 1-1/8 in (28.6mm)  
knockout provided in bottom  
of electric box.  
Factory-wired to components  
Earth ground connection (60Hz).  
on electric panel.  
Electric service,  
not by Liebert  
Connection terminal for  
Earth ground bar (optional on 50Hz only).  
Connection terminals with factory  
ground from each high voltage  
component for field-supplied  
earth grounding wire.  
field-supplied earth grounding wire  
when factory disconnect is supplied.  
DPN001051  
Rev. 0  
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Inspection and Installation  
Figure 21 Electrical field connections for Liebert Lee-Temp control condensers  
Lee-Temp receiver tank (1 per circuit).  
NOTE: Standard heater pads are 150 watts each.  
(Optional 300 watt heater pads are available.)  
Standard heater pad voltage is 230V. (120V  
heater pad voltage is optional.)  
Electrical connection box with cover.  
Electrical service connection.  
Pigtails in electric handy  
box are factory wired to Lee-  
Temp heater pads for field  
connection of separate  
continuous electric source,  
wiring not by Liebert.  
Electric service connection  
and fuse block.  
Electric service connection  
terminals when factory  
Factory wired to 24V  
Class 2 control circuit.  
disconnect is NOT supplied.  
Control interlock (70, 71)  
Field-supplied Class 2 wiring to  
interlock condenser 24V controls  
to Liebert room unit;  
7/8 in. (22.2mm) diameter  
hole provided in bottom  
of electric box.  
70  
71  
Electric service connection  
terminals when factory  
disconnect is supplied.  
Factory-installed disconnect  
switch (optional).  
Factory-wired to components  
on electric panel.  
Earth ground bar (optional on 50Hz only).  
Connection terminals with factory ground  
from each high-voltage component  
Electric service entrance. A  
7/8 in (22.2mm) diameter hole  
in a 1 1/8 in (28.6mm) knockout  
provided in bottom of electric box.  
for field-supplied earth grounding wire.  
Earth ground connection (60Hz).  
Connection terminal for field-supplied  
earth grounding wire when factory  
disconnect is NOT supplied.  
Electric service. Three-phase for  
all models. Wiring not by Liebert.  
Earth ground connection (60Hz).  
Connection terminal for field-supplied  
earth grounding wire when factory disconnect  
is supplied.  
DPN000683  
Rev. 0  
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Inspection and Installation  
3.9  
Refrigeration Piping Connections  
WARNING  
!
Risk of explosive discharge from high-pressure refrigerant. Can cause equipment damage,  
injury or death. Relieve pressure before working with piping.  
WARNING  
!
Risk of refrigerant system rupture or explosion from overpressurization. Can cause  
equipment damage, injury or death.  
If a pressure relief device is not provided with the condenser unit, the system installer must  
provide and install a discharge pressure relief valve rated for a maximum of 500 psig (34bar)  
in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and  
the field installed relief valve.  
One or more additional pressure relief valves are required downstream of any and all field  
installed isolation valves as shown in Figures 2 and 24. Do not isolate any refrigerant  
circuits from overpressurization protection.  
NOTE  
POE (polyol ester) oil, required with R407C and used with some R22 systems, is much more  
hygroscopic than mineral oils. This means that POE oil absorbs water at a much faster rate  
when exposed to air than previously used mineral oils. Because water is the enemy of a reliable  
refrigeration system, extreme care must be used when opening systems during installation or  
service. If water is absorbed into the POE oil, it will not be easily removed and will not be  
removed through the normal evacuation process. If the oil is too wet, it may require an oil  
change. POE oils also have a property that makes them act as a solvent in a refrigeration  
system. Maintaining system cleanliness is extremely important because the oil will tend to  
bring any foreign matter back to the compressor.  
3.9.1 Piping Guidelines  
Indoor units and condensers both ship with nitrogen holding charges. Do not vent the condenser until  
all refrigerant piping is in place, ready for connection to indoor unit and condenser.  
• Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as  
Sil-Fos. Use a flow of dry nitrogen through the piping to prevent the formation of copper oxide  
scale inside the piping. Avoid soft solders such as 50/50 or 95/5.  
• Isolate piping from building using vibration isolating supports.  
• Refer to indoor unit user manual for appropriate piping sizes.  
• Install traps on the hot gas (discharge) lines at the bottom of any rise over 5 feet high. If the rise  
exceeds 25 feet (7.5m), then install a trap in 20 foot (6m) increments or evenly divided.  
• Pitch horizontal hot gas piping at a minimum rate of 1/2" per 10 ft. (42mm per 10m) so that grav-  
ity will aid in moving oil in the direction of refrigerant/oil flow.  
• Consult factory if Lee-Temp condenser is located more than 15 ft (4.6m) below the evaporator or if  
Fan Speed/VFD Control Condenser is located more than 30 ft. (9.2m) below the evaporator.  
• Consult factory if piping run exceeds 150 feet (46m) equivalent length.  
• Keep piping clean and dry, especially on units with POE oil (R407C or R22 refrigerant).  
• Avoid piping runs through noise-sensitive areas.  
• Do not run piping directly in front of indoor unit discharge airstream.  
• Refrigerant oil – do not mix oil types or viscosities. Consult indoor unit for refrigerant type and oil  
requirements.  
NOTE  
Failure to use compressor oils recommended by compressor manufacturer will void compressor  
warranty. Consult Liebert or compressor manufacturer for further recommendations or if you  
have questions about compressor oils.  
Refer to ASHRAE Refrigeration Handbook for general good practices for refrigeration piping.  
A pressure relief valve is provided with Liebert Lee-Temp condensers. A fusible plug is  
provided on Liebert Fan Speed Control and VFD condensers. The Liebert indoor cooling unit  
has a factory-installed high-pressure safety switch in the high side refrigerant circuit.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Inspection and Installation  
3.9.2 Field Piping Installation  
One discharge line and one liquid line must be field-installed for each circuit of the indoor unit and  
the outdoor condenser(s). Dual circuit condensers are available for most dual circuit indoor unit appli-  
cations. Refer to Figures 22, 23 and 24 below for additional field-installed piping needed at the con-  
denser. This piping is needed for proper system performance and for installation/interconnecting  
receivers and head pressure control valves for Lee-Temp systems.  
NOTE  
Keep the evaporator unit and condenser closed with their factory charge of dry nitrogen while  
all field piping is installed. Keep the field piping clean and dry during installation, and do not  
allow it to stand open to the atmosphere.  
When all the field interconnecting piping is in place, vent the condenser’s dry nitrogen charge  
and connect to the field piping. Finally, vent the evaporator unit’s dry nitrogen charge and  
make its piping connections last.  
Follow all proper brazing practices, including a dry nitrogen purge to maintain system  
cleanliness.  
Figure 22 VFD and Fan Speed Control condenser piping  
Traps to Extend Above Base of  
Coil by a Minimum of 7-1/2" (190mm)  
Entering Hot  
Gas Line  
Leaving  
Liquid Line  
Inverted Traps  
(Field Supplied)  
Metal  
Clamp  
Fasten liquid and hot gas lines  
to leg using flat surface clamps  
with isolators ( field-supplied).  
Support field piping separately  
to avoid coil damage and loss of charge.  
See  
Detail  
A-A  
Isolator  
DPN001065  
Rev. 0  
Detail A-A  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Inspection and Installation  
Figure 23 Lee-Temp head pressure control condenser piping  
Inverted Traps (field-supplied)  
Hot Gas Line  
to extend 8" (203mm)  
above coil base  
Liquid  
Line  
Entering Hot  
Gas Line  
Fasten liquid and hot gas lines  
to leg using flat surface clamps  
with isolators (field-supplied).  
Support field piping separately  
to avoid coil damage and loss  
Leaving  
Liquid  
Line  
Position elbow to direct  
relief valve downward  
of charge.  
See Detail A-A  
DPN000669  
Rev. 2  
Metal  
Clamp  
Isolator  
Detail A-A  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Inspection and Installation  
Figure 24 General arrangement—Air cooled models with Lee-Temp control  
Condenser Coil  
Inverted Trap *  
on discharge line  
Piping Assembly **  
Rotalock Valve **  
to extend 7-1/2" (190mm)  
above coil base  
Check  
Valve  
Head Pressure  
1/4" (6.4mm)  
Pressure Relief  
Valve**  
Control with  
Integral Check  
Valve  
Sight Glass  
* Traps every 25 ft  
(7.6m) of rise on  
hot gas line only  
Evaporator  
Coil  
Liquid Return  
from  
Condenser  
Expansion  
Valve  
Solenoid  
Valves  
Sight  
Glass  
Shutoff *  
Sensing Bulb  
(Isolation)  
Valve  
Filter  
Dryer  
Liquid  
External  
Equalizers  
Return  
Service Valves  
Check  
Valve  
Hot Gas  
Bypass  
(optional)  
Compressor***  
*
Components are not supplied by Liebert  
but are recommended for proper  
circuit operation and maintenance.  
Hot Gas  
Discharge  
** Components supplied by Liebert and  
must be field-installed.  
*** Various compressor types may be available.  
Single Circuit Shown  
Factory Piping  
Optional Piping  
Field Piping  
DPN000681  
Rev. 0  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Inspection and Installation  
3.10 System Dehydration/Leak Test and Charging Procedures  
Procedures for leak check and evacuation of the entire refrigeration system are contained in the  
installation manual of the indoor unit. Use the proper manual section corresponding to the winter  
control system used on the condenser (VFD/Fan Speed Control or Lee-Temp Control) and the refriger-  
ant to be charged into the system.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Checklist for Completed Installation  
4.0 CHECKLIST FOR COMPLETED INSTALLATION  
4.1  
Moving and Placing Equipment  
___ 1. Unpack and check received material  
___ 2. Proper clearance for service access has been maintained around the equipment  
___ 3. Equipment is level and mounting fasteners are tight  
4.2  
Electrical  
___ 1. Line voltage connected and matches equipment nameplate  
___ 2. Power line circuit breakers or fuses have proper ratings for equipment installed  
___ 3. Control wiring connections completed between indoor cooling unit and condenser  
___ 4. All internal and external high and low voltage wiring connections are tight  
___ 5. TCDV condensers only—Check for Delta-Connected Power Supply and make any needed  
___ 6. Monitoring wiring connections completed, when equipped, to indoor cooling unit or external  
monitoring panel  
___ 7. Confirm that unit is properly grounded to an earth ground  
___ 8. Control transformer setting matches incoming power  
___ 9. Electrical service conforms to national and local codes  
___ 10. Check fans for proper phase rotation. Blades should rotate clockwise when viewing the unit  
from the fan guard side.  
4.3  
4.4  
Piping  
___ 1. Piping is completed to corresponding indoor cooling unit refrigeration circuit.  
___ 2. Piping leak-checked, evacuated and charged.  
___ 3. Piping is properly sized, sloped and trapped for proper oil return.  
___ 4. Piping is routed to reduce potential of rub-through or chaffing.  
Other  
___ 1. Fans rotate freely and in proper direction  
___ 2. Adjust ambient thermostat setpoints to match setpoints on the electrical schematic supplied  
with the condenser.  
___ 3. Foreign material removed from in and around all equipment installed (construction  
materials, construction debris, etc.).  
___ 4. Installation materials and tools have been removed from in and around all equipment  
(literature, shipping materials, tools, etc.).  
___ 5. Blank start-up sheet located, ready for completion by installer or start-up technician.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Operation  
5.0 OPERATION  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working within. Unit contains  
potentially lethal electrical voltage.  
Only properly trained and qualified personnel may perform repair, maintenance and cleaning  
operations.  
The fans may start unexpectedly. Disconnect power supply before working on unit. Line side  
of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure  
power is turned off before checking any electrical connections or functions.  
5.1  
5.2  
Startup Checklist  
Refer to 4.0 - Checklist for Completed Installation and verify that all installation items have  
been completed before beginning to start the condenser.  
Startup  
• Locate “Liebert Condensers and Drycoolers Warranty Inspection Check Sheet”  
(Document # SAFM-8542-54).  
• Turn the condenser disconnect ON. Indoor units should be turned on and set for cooling to allow  
operation of condenser.  
• Check the fans for proper rotation: Clockwise when viewing the unit from the fan guard (top) side.  
Check that air is being drawn through the coil and discharged out the fan assembly. Some ambi-  
ent thermostats may need to be temporarily adjusted to lower temperature settings to observe all  
fans operate. Readjust thermostat settings to correspond to setpoints shown on the electrical  
schematic supplied with the unit.  
• Complete “Liebert Condensers and Drycoolers Warranty Inspection Check Sheet”  
(Document # SAFM-8542-54).  
NOTE  
This document must be completed and forwarded to your local Liebert sales office to validate  
warranty.  
• Contact your local Liebert sales representative or Liebert Air Product Support if you have any  
questions or problems during unit startup and commissioning.  
• Local Liebert sales offices and Liebert air product support contacts can be found at  
calling 1-800-LIEBERT.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Maintenance  
6.0 SYSTEM MAINTENANCE  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working in the unit. Use  
voltmeter to make sure power is turned Off before making any electrical connections.  
Unit contains lethal voltage in some circuits.  
Only properly trained and qualified personnel may perform repair, maintenance and cleaning  
operations.  
The fans may start unexpectedly. Disconnect power supply before working on unit. Line side  
of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure  
power is turned off before checking any electrical connections or functions.  
6.1  
General Procedures  
NOTE  
When ordering replacement parts for equipment, it is necessary to specify unit model number,  
serial number, and voltage. Please record those numbers in the spaces below.  
• Model Number____________________________________________________  
• Serial Number ____________________________________________________  
• Voltage/Phase/Frequency _________________________________________  
Periodic attention is necessary for continued satisfactory operation of your unit. Restricted air flow  
through the condenser coil, reduced airflow from non-functioning fans and low refrigerant system  
charge levels will reduce the operating efficiency of the unit and can result in high condensing tem-  
peratures and loss of cooling. In winter, do not permit snow to accumulate around the sides or under-  
neath the condenser coil.  
Monthly and semi-annual inspections and maintenance are recommended for proper system opera-  
tion. Use copies of 6.2.2 - Maintenance Inspection Checklist for each of these inspections.  
If performance or operation problems are detected at anytime, refer to Table 9 - Troubleshooting  
for required action.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Maintenance  
6.2  
Special Procedures  
6.2.1 Condenser Cleaning  
Keeping the outdoor condenser coils clean is an important factor in maintaining peak efficiency, reli-  
ability and long life of the equipment. It is much easier to keep up on frequent cleanings rather than  
wait until heavy build up has occurred which may create head pressure problems with the evaporator  
units.  
When to Clean  
Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions  
such as cottonwood trees, construction, etc., can increase cleaning frequency. On your standard  
monthly preventive maintenance schedule, a visual inspection of the coil is recommended to monitor  
conditions.  
What to Use  
The best overall condenser coil cleaner to use is plain water. If the coil has been maintained and  
cleaned at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy build  
up on the exterior of the fins can be removed with a brush. Water pressure from a garden hose and  
sprayer usually works well. If a pressure washer is used, make sure the equipment is set to a lower  
pressure setting and that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins  
could result. If a cleaner is required, we recommend a non-acidic type cleaner be used. Acid-type  
cleaners can be aggressive to the coil fins as well as surrounding areas. Many sites do not allow the  
use of acidic cleaners for environmental reasons.  
How to Clean  
The absolute best way to clean coils is from the inside out. This requires disconnecting the power sup-  
ply from the condenser before working on the unit. The fan guards and fan blades must be removed to  
gain access to the coil surface. The sprayer can then be worked across the coil using the water/clean-  
ing solution, pushing the dirt and debris out the bottom of the coil. Although this does extend the time  
involved, the results are well worth it. This method should be used at least once a year. Spraying the  
coil from the outside repeatedly can push a majority of the dirt to the inner section of the fins and con-  
tinue to restrict air flow. Keep in mind you may not have the luxury of shutting the unit(s) down for  
an extended time. A pre-scheduled shutdown with the operator may be in order. If you are using a  
cleaner along with the spraying process, follow recommended manufacturer instructions and be sure  
to rinse the coil thoroughly. Any residue left on the coil can act as a magnet to dirt.  
Reinstall and secure the fan blades and fan guards after the cleaning is finished. Last, reconnect the  
power supply to the condenser.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Maintenance  
6.2.2 Maintenance Inspection Checklist  
Date:____________________________________  
Model #:_________________________________  
Prepared By:____________________________________  
Serial Number:__________________________________  
NOTE  
Regular inspections are necessary to ensure that the cooling fins are clean. Should inspection  
reveal dirt or corrosion, appropriate cleaning should be performed.  
Monthly  
Semiannually  
Condenser  
Condenser  
___ 1. Coil surfaces free of debris  
___ 1. Complete all monthly items  
___ 2. Piping in good condition  
___ 2. Fans free of debris  
___ 3. Fan motors securely mounted  
___ 3. Inspect refrigerant lines for signs of oil  
leaks. Repair leaks as found.  
___ 4. Motor bearings in good  
condition  
___ 4. Check refrigerant charge level in each  
receiver tank (if equipped), based on  
___ 5. Check all refrigerant lines and  
capillaries for vibration  
isolation. Support as  
procedures in the indoor unit’s manual.  
Continuous system operation required.  
necessary.  
___ 5. Wash coil as needed  
___ 6. No refrigerant leaks.  
___ 6. Repair bent or damaged fins.  
Condenser Electrical Panel  
Condenser Electric Panel  
___ 1. On TCDV models, check TVSS  
protection status indicator  
light.  
___ 1. Check all electrical connections  
___ 2. Check contactors for pitting  
___ 3. Operational sequence/setpoints  
Fan Motors  
___ 1. Motor #1 amp draw __________ amps  
___ 2. Motor #2 amp draw __________ amps  
___ 3. Motor #3 amp draw __________ amps  
___ 4. Motor #4 amp draw __________ amps  
___ 5. Motor #5 amp draw __________ amps  
___ 6. Motor #6 amp draw __________ amps  
___ 7. Motor #7 amp draw __________ amps  
___ 8. Motor #8 amp draw __________ amps  
Notes  
Signature: _________________________________________________________________________________________  
Make photocopies of this form for your records  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Maintenance  
Table 9  
Troubleshooting  
Possible Cause  
Symptom  
Check or Remedy  
No power to condenser  
Check voltage at input terminal block  
Circuit breaker for low voltage  
transformer in condenser is tripped  
Locate problem in condenser electrical  
panel and repair  
Condenser will not start  
No low voltage signal to/from indoor unit Locate open circuit and repair  
Insufficient refrigerant in system  
Check for leaks, repair, and add refrigerant  
Low indoor unit  
suction pressure  
Fan-cycling ambient thermostats  
setpoints too low  
Check schematic for recommended  
setpoints and adjust.  
Faulty head pressure control valve  
or condenser FSC/VFD control  
Low discharge pressure  
Replace if defective  
Dirty condenser fins  
Clean coil  
Check for low voltage signal from indoor unit  
Check fan motors and fuses  
High discharge pressure  
Condenser fans not operating  
High refrigerant charge  
Check for correct ambient thermostat  
setpoints, as applicable.  
Check refrigerant charge  
VFD Condenser trips out  
on overvoltage  
(OU displayed on VFD  
controller)  
Supply voltage is Delta configuration  
or is ungrounded/high impedance  
Shut off AC voltage, locate the VFD, pull out  
the EMC tab and reconnect power  
No voltage or improper phasing exists  
at condenser  
Check voltage at input terminal block  
Locate connection problem and repair  
TVSS indicator lights are  
extinguished or red LED is  
illuminated and monitoring  
terminals 11/12 are closed  
Electrical connections to TVSS are  
faulty  
Replace TVSS and inspect other  
components for damage and replace them if  
necessary  
A surge exceeding the rating  
of the TVSS has occurred  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Maintenance  
NOTES  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Maintenance  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2007 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-10066_REV0_12-07  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2007 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

La Crosse Technology Weather Radio WS 8300U User Manual
Life Fitness Elliptical Trainer Lifecycle 8500 User Manual
Life Fitness Home Gym TCWHL User Manual
Mackie Speaker SWA1501 User Manual
Magnavox Flat Panel Television 42MF7010 17 User Manual
Makita Grinder 9526PBH User Manual
Mamp;S Systems Speaker System WS5 User Manual
Melissa Iron 641 031 User Manual
Mercedes Benz Automobile 2003 C Class Wagon User Manual
Metra Electronics Car Amplifier 70 6504 User Manual