Lennox International Inc Furnace G61MP User Manual

G61MP  
Corp. 0308−L6  
Revised 10−2004  
Service Literature  
G61MP SERIES UNITS  
G61MP series units are high−efficiency multi−position (up-  
flow, downflow, horizontal right and left) gas furnaces  
manufactured with Lennox Duralok Plust heat exchang-  
ers formed of aluminized steel. G61MP units are available  
in heating capacities of 44,000 to 132,000 Btuh (13.0.0 to  
38.6 kW) and cooling applications from 2 to 5 tons (7.0 kW  
to 17.5 kW)) up to 5 tons. Refer to Engineering Handbook  
for proper sizing.  
Units are factory equipped for use with natural gas. Kits are  
available for conversion to LPG operation. G61MP model  
units are equipped with the Two−Stage Integrated SureLight  
control. All G61MP units meet the California Nitrogen Ox-  
ides (NO ) Standards and California Seasonal Efficiency re-  
x
quirements. All units use a redundant gas valve to assure  
safety shut−off as required by C.S.A.  
All specifications in this manual are subject to change. Pro-  
cedures outlined in this manual are presented as a recom-  
mendation only and do not supersede or replace local or  
state codes. In the absence of local or state codes, the  
guidelines and procedures outlined in this manual (except  
where noted) are recommendations only and do not consti-  
tute code.  
IMPORTANT  
Improper installation, adjustment, alteration, service  
or maintenance can cause property damage, person-  
al injury or loss of life. Installation and service must  
be performed by a qualified installer, service agency  
or the gas supplier.  
TABLE OF CONTENTS  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Parts Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
I Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
II Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
III Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
IV Heating System Service Checks . . . . . . . . . . . . . . 31  
V Typical Operating Characteristics . . . . . . . . . . . . . . 34  
VI Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
VII Wiring and Sequence of Operation . . . . . . . . . . . . 38  
VIII Field Wiring and Jumper Setting . . . . . . . . . . . . . 46  
IX Control Board Troubleshooting . . . . . . . . . . . . . . . . 48  
WARNING  
Electric shock hazard. Can cause injury  
or death. Before attempting to perform  
any service or maintenance, turn the  
electrical power to unit OFF at discon-  
nect switch(es). Unit may have multiple  
power supplies.  
WARNING  
Sharp edges.  
Be careful when servicing unit to avoid sharp edges  
which may result in personal injury.  
Page 1  
© 2003 Lennox Industries Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
ModelꢀNo.  
Inputꢀ− Btuh (kW)  
Outputꢀ− Btuh (kW)  
G61MP−48C−110  
110,000 (32.2)  
104,000 (30.5)  
45 − 75 (25 − 42)  
75,000 (22.0)  
72,000 (21.1)  
30 − 60 (18 − 36)  
94.1%  
G61MP−60C−110  
110,000 (32.2)  
104,000 (30.5)  
35 − 65 (21 − 39)  
75,000 (22.0)  
72,000 (21.1)  
25 − 55 (14 − 31)  
94.1%  
G61MP−60D−135  
132,000 (38.7)  
124,000 (36.3)  
40 − 70 (24 − 42)  
90,000 (26.4)  
86,000 (25.2)  
30 − 60 (18 − 36)  
94.1%  
Gas  
Heating  
Performance  
High Fire  
Temperature rise range − _F (_C)  
Low Fire  
Inputꢀ− Btuh (kW)  
Outputꢀ− Btuh (kW)  
Temperature rise range − _F (_C)  
1
AFUE  
California Seasonal Efficiency  
Highꢀstaticꢀ(CSA)ꢀ− in.ꢀw.g. (Pa)  
88.4%  
87.0%  
87.7%  
0.5  
0.5  
0.5  
2
Connections  
in.  
Intake Pipe (PVC)  
2
2
3
2
Exhaust Pipe (PVC)  
2
2
3
Condensate Drain Trap (PVC pipe) − i.d.  
with field supplied (PVC coupling) − o.d.  
hose with hose clamp − i.d. x o.d.  
GasꢀpipeꢀsizeꢀIPS  
1/2  
1/2  
1/2  
3/4  
3/4  
3/4  
1−1/4 x 1  
1−1/4 x 1  
1−1/4 x 1  
1/2  
1/2  
1/2  
Indoor  
Blower  
Wheelꢀnominalꢀdiameter ꢀxꢀwidth −ꢀin. (mm)  
Motorꢀoutput − hp (W)  
10 x 10 (254 x 254)  
1/2 (373)  
3 − 4 (10.5 − 14.0)  
178 (81)  
11−1/2 x 10 (292 x 229)  
1 (746)  
11−1/2 x 10 (292 x 229)  
1 (746)  
Tonsꢀ(kW) ofꢀadd-onꢀcooling  
lbs. (kg) − 1 package  
4 − 5 (14.0 − 17.5)  
186 (84)  
4 − 5 (14.0 − 17.5)  
206 (93)  
ShippingꢀData  
Electricalꢀcharacteristics  
120 volts − 60 hertz − 1 phase (less than 12 amps)  
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA  
3, 4  
Air Filter and Rack Kit −  
Horizontal (end)  
87L97 − 20 x 25 x 1 in. (508 x 635 x 25 mm)  
87L98 − 25 x 25 x 1 in.  
(635 x 635 x 25 mm)  
Size of filter  
5
Side Return  
6 ft. (1.8 m)  
Single 44J22 or Ten Pack (66K63) − (1) 16 x 25 x 1 in. (406 x 635 x 25 mm)  
Condensate Drain Heat  
Cable  
26K68  
26K69  
26K70  
39G04  
39G03  
26K68  
26K69  
26K68  
26K69  
24 ft. (7.3 m)  
50 ft. (15.2 m)  
26K70  
26K70  
Heat Cable Tape  
39G04  
39G04  
Fiberglass − 1/2 in. (38 mm) x 66 ft. (20 m)  
Aluminum foil − 2 in. (25 mm) x 60 ft. (18 m)  
Catalog Number − Shipping Weight  
Dimensions − H x W x D − in. (mm)  
39G03  
39G03  
4
EZ Filter Base  
73P57 − 8 lbs. (4 kg)  
73P58 − 10 lbs. (5 kg)  
73P58 − 10 lbs. (5 kg)  
4 x 21−5/8 x 28−5/8  
(102 x 549 x 727)  
4 x 24−5/8 x 28−5/8  
(102 x 625 x 727)  
4 x 24−5/8 x 28−5/8  
(102 x 625 x 727)  
Size of field provided filter − in. (mm)  
20 x 25 x 1  
(508 x 635 x 25)  
24 x 24 x 1  
(610 x 610 x 25)  
24 x 24 x 1  
(610 x 610 x 25)  
Down−Flow Additive Base  
11M61  
59M16  
11M61  
59M16  
11M62  
59M16  
5
High Altitude Orifice Kit − Natural Gas Only  
6
High Altitude Pressure Switch Kit − Order two each  
− − −  
− − −  
56M93  
4501−10,000 ft. (1372−3048 m)  
Horizontal Support Frame Kit − Ship. Weight − lbs. (kg)  
56J18 − 18 (8)  
59M13  
59M14  
59M87  
− − − −  
56J18 − 18 (8)  
59M13  
56J18 − 18 (8)  
59M13  
LPG/Propane Kit  
0−7500 ft. (0−2286 m)  
7501−10,000ft. (2286−3048m)  
59M14  
59M14  
Natural to LPG/Propane Kit  
RAB Return Air Base  
59M87  
59M87  
RAB60C (12M71)  
33K97  
RAB60D (12M72)  
− − −  
7
Termination Kits − Concentric  
Roof/Wall  
2 inch (51 mm)  
3 inch (76 mm)  
33K97  
60L46  
Direct Vent  
Applications  
60L46  
60L46  
Wall  
Close−Coupled 3 inch (76 mm)  
2 inch (51 mm)  
44J40  
44J40  
44J40  
7,8  
Termination Kits Roof  
Direct Vent or Non−  
Direct Vent  
Wall  
15F75  
15F75  
− − −  
3 inch (76 mm)  
44J41  
44J41  
44J41  
9
Ring Kit 2 inch (51 mm)  
15F74  
15F74  
15F74  
NOTE − Filters and provisions for mounting are not furnished and must be field provided.  
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.  
Determine from venting tables proper exhaust pipe size and termination kit required.  
Cleanable polyurethane frame type filter.  
Not for use with RAB Return Air Base or with 60C and 60D size units with air flow requirements of 1800 cfm (850 L/s) or greater. See Blower Performance tables for additional  
information.  
2
3
4
5
6
7
8
9
Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).  
Required for proper operation at altitudes over 4500 ft. (1370 m).  
See Installation Instructions for specific venting information.  
Kits contain enough parts for two, non−direct vent installations.  
Non−direct vent applications only.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER DATA  
G61MP−36B−045 PERFORMANCE (Less Filter)  
External Static  
Pressure  
Air Volume / Watts at Different Blower Speeds  
High  
Medium−High  
Medium−Low  
Low  
in. w.g.  
Pa  
25  
cfm  
1555  
1515  
1470  
1410  
1350  
1290  
1220  
1145  
1050  
945  
L/s  
735  
715  
695  
665  
640  
610  
575  
540  
495  
445  
Watts  
630  
605  
580  
555  
535  
505  
485  
460  
425  
410  
cfm  
1410  
1385  
1345  
1310  
1250  
1205  
1145  
1080  
985  
L/s  
665  
655  
635  
620  
590  
570  
540  
510  
465  
425  
Watts  
585  
555  
520  
495  
465  
450  
420  
400  
365  
345  
cfm  
1190  
1190  
1170  
1155  
1120  
1080  
1020  
975  
L/s  
560  
560  
550  
545  
530  
510  
480  
460  
410  
390  
Watts  
520  
485  
455  
440  
410  
390  
365  
345  
320  
305  
cfm  
1030  
1020  
1010  
1000  
980  
L/s  
485  
480  
475  
470  
465  
450  
430  
405  
370  
345  
Watts  
435  
415  
400  
385  
360  
345  
320  
300  
285  
270  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
25  
50  
75  
100  
125  
150  
175  
200  
225  
950  
905  
860  
870  
785  
900  
825  
730  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
G61MP−36B−070 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
External Static  
Pressure  
High  
Medium−High  
Medium−Low  
Low  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
1640  
1600  
1540  
1495  
1420  
1360  
1275  
1170  
1080  
945  
L/s  
775  
755  
725  
705  
670  
640  
600  
555  
510  
445  
Watts  
660  
635  
605  
580  
545  
525  
490  
465  
440  
400  
cfm  
1415  
1395  
1370  
1345  
1275  
1245  
1165  
1085  
1010  
840  
L/s  
665  
660  
650  
635  
605  
590  
550  
515  
475  
395  
Watts  
575  
550  
525  
505  
480  
450  
410  
385  
360  
320  
cfm  
1160  
1160  
1160  
1145  
1125  
1080  
1025  
965  
L/s  
545  
545  
545  
540  
530  
510  
485  
430  
410  
360  
Watts  
485  
460  
445  
425  
395  
375  
350  
335  
310  
275  
cfm  
1005  
1000  
995  
990  
965  
945  
900  
860  
775  
710  
L/s  
475  
470  
470  
465  
455  
445  
425  
405  
365  
335  
Watts  
410  
385  
375  
365  
345  
325  
305  
295  
270  
245  
25  
50  
75  
100  
125  
150  
175  
200  
225  
865  
765  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
G61MP−48C−090 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
External Static  
Pressure  
High  
Medium−High  
Medium−Low  
Low  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
L/s  
1030  
1005  
985  
955  
915  
880  
820  
775  
725  
630  
Watts  
930  
885  
840  
800  
760  
725  
670  
640  
600  
540  
cfm  
1835  
1825  
1810  
1775  
1735  
1660  
1590  
1475  
1340  
1170  
L/s  
865  
860  
855  
835  
820  
785  
750  
695  
630  
555  
Watts  
790  
750  
720  
685  
650  
600  
575  
520  
465  
440  
cfm  
1520  
1510  
1505  
1500  
1480  
1430  
1380  
1290  
1175  
1070  
L/s  
715  
710  
710  
705  
700  
675  
650  
610  
555  
505  
Watts  
630  
610  
580  
565  
535  
505  
475  
450  
405  
375  
cfm  
1280  
1275  
1270  
1265  
1250  
1215  
1175  
1105  
1020  
950  
L/s  
605  
600  
600  
595  
590  
575  
555  
520  
480  
450  
Watts  
510  
495  
475  
460  
440  
425  
410  
375  
355  
330  
2180  
2135  
2085  
2030  
1940  
1865  
1740  
1645  
1540  
1335  
25  
50  
75  
100  
125  
150  
175  
200  
225  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
G61MP−48C−110 PERFORMANCE (Less Filter)  
Air Volume / Watts at Different Blower Speeds  
External Static  
Pressure  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
Watts  
880  
850  
805  
750  
725  
680  
660  
620  
550  
520  
cfm  
1880  
1855  
1815  
1755  
1715  
1630  
1550  
1410  
1230  
1120  
Watts  
755  
730  
690  
650  
625  
580  
550  
505  
450  
415  
cfm  
1490  
1480  
1475  
1475  
1465  
1420  
1360  
1210  
1125  
1050  
Watts  
602  
585  
560  
545  
510  
490  
460  
405  
380  
365  
cfm  
1235  
1230  
1225  
1220  
1215  
1150  
1110  
1035  
970  
Watts  
485  
475  
460  
445  
430  
400  
380  
350  
325  
310  
2160  
2100  
2035  
1965  
1885  
1780  
1690  
1575  
1375  
1225  
1020  
990  
960  
925  
890  
840  
800  
745  
650  
580  
890  
705  
580  
580  
580  
575  
575  
540  
525  
490  
460  
420  
25  
875  
700  
50  
860  
695  
75  
830  
695  
100  
125  
150  
175  
200  
225  
810  
690  
770  
670  
735  
640  
665  
570  
580  
530  
530  
495  
885  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER DATA  
G61MP−60C−090 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transi-  
tion to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.  
Air Volume / Watts at Different Blower Speeds  
External Static  
Pressure  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
Pa  
0
cfm  
Watts  
1495  
1475  
1435  
1380  
1350  
1305  
1270  
1205  
1190  
1150  
cfm  
Watts  
1155  
1135  
1080  
1035  
1015  
990  
cfm  
Watts  
895  
865  
845  
825  
815  
790  
775  
760  
745  
715  
cfm  
Watts  
695  
690  
685  
680  
670  
655  
640  
620  
605  
580  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
2835  
2785  
2715  
2620  
2550  
2450  
2365  
2240  
2185  
2015  
1335  
1315  
1280  
1235  
1205  
1155  
1115  
1060  
1030  
950  
2340  
2345  
2275  
2260  
2230  
2175  
2130  
2070  
1965  
1820  
1105  
1105  
1075  
1065  
1055  
1025  
1005  
975  
1800  
1805  
1825  
1840  
1845  
1850  
1830  
1815  
1775  
1690  
850  
1440  
1515  
1560  
1600  
1620  
1615  
1615  
1595  
1555  
1440  
680  
715  
735  
755  
765  
765  
760  
755  
735  
680  
25  
855  
50  
860  
75  
870  
100  
125  
150  
175  
200  
225  
870  
870  
940  
865  
915  
855  
925  
865  
840  
860  
820  
800  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
G61MP−60C−090 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base,  
Return Air from Both Sides or Return Air from Bottom and One Side.  
Air Volume / Watts at Different Blower Speeds  
External Static  
Pressure  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
Pa  
0
cfm  
Watts  
1450  
1415  
1385  
1335  
1300  
1260  
1220  
1190  
1140  
1090  
cfm  
Watts  
1105  
1080  
1050  
1030  
990  
cfm  
Watts  
900  
885  
870  
850  
825  
800  
775  
745  
715  
685  
cfm  
Watts  
700  
700  
695  
690  
675  
665  
650  
630  
615  
590  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
2840  
2765  
2695  
2605  
2530  
2420  
2330  
2250  
2135  
2030  
1340  
1305  
1270  
1230  
1195  
1140  
1100  
1060  
1010  
960  
2345  
2365  
2345  
2315  
2265  
2210  
2145  
2050  
2000  
1885  
1105  
1115  
1895  
1950  
1985  
1990  
1990  
1970  
1930  
1875  
1810  
1720  
895  
1515  
1580  
1620  
1645  
1665  
1675  
1665  
1645  
1620  
1560  
715  
745  
765  
775  
785  
790  
785  
775  
765  
735  
25  
920  
50  
1105  
1090  
1070  
1045  
1010  
965  
935  
75  
940  
100  
125  
150  
175  
200  
225  
940  
955  
930  
925  
910  
885  
885  
945  
865  
855  
890  
830  
810  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
G61MP−60C−110 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transi-  
tion to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.  
External Static  
Pressure  
Air Volume / Watts at Different Blower Speeds  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
2625  
2570  
2410  
2425  
2335  
2270  
2170  
2110  
2035  
1900  
Watts  
1350  
1330  
1305  
1265  
1220  
1195  
1155  
1130  
1090  
1055  
cfm  
Watts  
1080  
1060  
1035  
990  
cfm  
Watts  
885  
865  
845  
825  
810  
785  
765  
730  
705  
680  
cfm  
Watts  
700  
700  
690  
675  
660  
640  
630  
610  
580  
565  
1240  
1215  
1135  
1145  
1100  
1070  
1025  
995  
2310  
2325  
2285  
2230  
2175  
2120  
2045  
1950  
1885  
1760  
1090  
1095  
1080  
1055  
1025  
1000  
965  
1885  
1910  
1930  
1925  
1910  
1895  
1860  
1795  
1745  
1665  
890  
1515  
1575  
1620  
1635  
1640  
1640  
1630  
1590  
1540  
1470  
715  
745  
765  
770  
775  
775  
770  
750  
725  
695  
25  
900  
50  
910  
75  
905  
100  
125  
150  
175  
200  
225  
950  
900  
935  
895  
885  
875  
920  
855  
845  
960  
890  
820  
825  
895  
830  
780  
785  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER DATA  
G61MP−60C−110 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base,  
Return Air from Both Sides or Return Air from Bottom and One Side.  
External Static  
Pressure  
Air Volume / Watts at Different Blower Speeds  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
Watts  
1385  
1355  
1315  
1275  
1250  
1205  
1185  
1150  
1090  
1050  
cfm  
Watts  
1090  
1075  
1015  
990  
cfm  
Watts  
935  
885  
865  
840  
830  
790  
765  
730  
710  
675  
cfm  
Watts  
710  
735  
690  
675  
660  
665  
650  
635  
610  
590  
2720  
2665  
2585  
2505  
2435  
2350  
2255  
2160  
2020  
1910  
1285  
1255  
1220  
1180  
1150  
1110  
1065  
1020  
955  
2410  
2385  
2350  
2290  
2235  
2170  
2100  
2005  
1905  
1820  
1135  
1125  
1110  
2055  
2025  
2030  
2025  
2030  
1975  
1915  
1865  
1810  
1705  
970  
1620  
1730  
1680  
1695  
1695  
1735  
1720  
1680  
1625  
1540  
765  
815  
795  
800  
800  
820  
810  
795  
765  
725  
25  
955  
50  
955  
75  
1080  
1055  
1025  
990  
955  
100  
125  
150  
175  
200  
225  
940  
960  
930  
930  
895  
905  
945  
840  
880  
900  
825  
855  
900  
860  
795  
805  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
G61MP−60D−135 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transi-  
tion to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.  
External Static  
Pressure  
Air Volume / Watts at Different Blower Speeds  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
Watts  
1440  
1405  
1370  
1330  
1290  
1265  
1230  
1190  
1160  
1110  
cfm  
Watts  
1100  
1065  
1055  
1015  
985  
cfm  
Watts  
890  
865  
850  
825  
805  
790  
765  
740  
710  
685  
cfm  
Watts  
690  
685  
675  
670  
655  
645  
630  
605  
590  
570  
2665  
2615  
2530  
2470  
2380  
2310  
2200  
2120  
2025  
1930  
1260  
1235  
1195  
1165  
1125  
1090  
1035  
1000  
955  
2325  
2310  
2280  
2235  
2175  
2120  
2055  
1970  
1890  
1800  
1095  
1090  
1075  
1055  
1025  
1000  
970  
1865  
1915  
1925  
1920  
1910  
1890  
1835  
1790  
1720  
1655  
880  
1410  
1465  
1570  
1590  
1590  
1595  
1580  
1545  
1515  
1440  
665  
690  
740  
750  
750  
755  
745  
730  
715  
680  
25  
905  
50  
910  
75  
905  
100  
125  
150  
175  
200  
225  
900  
965  
890  
935  
865  
930  
900  
845  
890  
875  
810  
910  
850  
835  
780  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
G61MP−60D−135 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base,  
Return Air from Both Sides or Return Air from Bottom and One Side.  
External Static  
Pressure  
Air Volume / Watts at Different Blower Speeds  
High  
L/s  
Medium−High  
L/s  
Medium−Low  
L/s  
Low  
L/s  
in. w.g.  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
Pa  
0
cfm  
2730  
2670  
2600  
2525  
2445  
2360  
2290  
2205  
2110  
1970  
Watts  
1465  
1440  
1400  
1360  
1325  
1280  
1255  
1220  
1195  
1120  
cfm  
Watts  
1125  
1100  
1070  
1045  
1015  
985  
cfm  
Watts  
915  
890  
865  
845  
820  
790  
755  
730  
710  
690  
cfm  
Watts  
680  
675  
665  
655  
645  
635  
615  
600  
580  
545  
1290  
1260  
1225  
1190  
1155  
1115  
1080  
1040  
995  
2425  
2400  
2365  
2315  
2260  
2195  
2130  
2035  
1945  
1835  
1145  
1135  
1115  
2055  
2065  
2045  
2035  
2020  
1960  
1900  
1825  
1765  
1680  
970  
1560  
1590  
1620  
1615  
1615  
1610  
1600  
1570  
1540  
1540  
735  
750  
765  
760  
760  
760  
755  
740  
725  
725  
25  
975  
50  
965  
75  
1095  
1065  
1035  
1005  
960  
960  
100  
125  
150  
175  
200  
225  
955  
925  
965  
895  
910  
860  
915  
880  
830  
930  
865  
830  
795  
NOTES − All air data is measured external to unit without filter (not furnished − field provided).  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G61MP PARTS ARRANGEMENT  
TOP CAP  
DuralokPlusTM  
HEAT EXCHANGER  
ASSEMBLY  
CABINET  
BURNER BOX  
ASSEMBLY  
GAS VALVE  
AND MANIFOLD  
FLUE  
COLLAR  
COMBUSTION  
AIR PROVE PROVE  
SWITCHES*  
WARM HEADER  
(COLLECTOR)  
BOX  
COMBUSTION AIR  
INDUCER  
CONDENSER COIL  
BURNER  
ACCESS  
PANEL  
PRIMARY LIMIT  
COLD HEADER  
(COLLECTOR)  
BOX  
BLOWER  
ACCESS  
DOOR  
DOOR  
INTERLOCK  
SWITCH  
SECONDARY  
LIMITS (2)  
*G61MP−090 shown.  
G61MP−045 and −070  
are equipped with  
two switches.  
BLOWER  
ASSEMBLY  
SIGHT  
GLASS  
CONTROL BOX  
FIGURE 1  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
I−UNIT COMPONENTS  
3. Circuit Breaker (CB8)  
A 24V circuit breaker is also located in the control box.  
The switch provides overcurrent protection to the trans-  
former (T1). The breaker is rated 3A at 32V. If the current  
exceeds this limit the breaker will trip and all unit opera-  
tion will shutdown. The breaker can be manually reset  
by pressing the button on the face. See figure 3.  
valve, combustion air inducer and burners can be ac-  
cessed by removing the burner access panel. Electrical  
blower section.  
G61MP units are factory equipped with a bottom return air  
panel in place. The panel is designed to be field removed as  
required for bottom air return. Markings are provided for side  
return air and may be cut out in the field.  
CIRCUIT BREAKER CB8  
ELECTROSTATIC DISCHARGE (ESD)  
Precautions and Procedures  
PRESS TO RESET  
FIGURE 3  
CAUTION  
Electrostatic discharge can affect electronic  
components. Take precautions during furnace  
installation and service to protect the furnace’s  
electronic controls. Precautions will help to  
avoid control exposure to electrostatic dis-  
charge by putting the furnace, the control and  
the technician at the same electrostatic poten-  
tial. Neutralize electrostatic charge by touching  
hand and all tools on an unpainted unit surface,  
such as the gas valve or blower deck, before per-  
forming any service procedure.  
WARNING  
Shock hazard.  
Disconnect power before servicing. Integrated  
Control Board is not field repairable. If control is  
inoperable, simply replace entire control.  
Can cause injury or death. Unsafe operation will  
result if repair is attempted.  
4. Integrated Control Board (A92)  
All G61MP units are equipped with the Lennox Two−Stage  
Integrated control board. The system consists of a igni-  
tion control board (figure 4 with control terminal designa-  
tions in tables 3, 4 and 5) and ignitor (figure 7). The board  
and ignitor work in combination to ensure furnace ignition  
and ignitor durability. The board controls all major furnace  
operations. The board features two LED lights, DS1 and  
DS2 for troubleshooting. The board also has two accesso-  
ry terminals rated at (1) one amp. See table 6 for trouble-  
shooting diagnostic codes.  
A−Control Box  
1. Control Transformer (T1)  
A transformer located in the control box provides power to  
the low voltage section of the unit. Transformers on all  
models are rated 40VA with a 120V primary and a 24V sec-  
ondary.  
2. Door Interlock Switch (S51)  
A door interlock switch rated 14A at 125VAC is wired in se-  
ries with line voltage. When the blower door is removed the  
unit will shut down.  
Electronic Ignition  
At the beginning of the heat cycle, SureLight control moni-  
tors the first stage and second stage combustion air induc-  
er prove switch. The control will not begin the heating cycle  
if the first stage prove switch is closed (by−passed). Like-  
wise the control will not begin the second stage heating  
cycle if the second stage prove switch is closed, and will al-  
low first stage heat only. However if the second stage prove  
switch closes during the first stage pre−purge, the control  
will respond to second stage heat. Once the first stage  
prove switch is determined to be open, the combustion air  
inducer is energized on low (first stage) heat speed. When  
the differential in the prove switch is great enough, the  
prove switch closes and a 15−second pre−purge begins. If  
the switch is not proven within 2−1/2 minutes, the control  
goes into Watchguard−Pressure Switch mode for a 5−min-  
ute re−set period.  
CONTROL BOX G61MP  
CIRCUIT  
BREAKER  
DOOR INTERLOCK  
SWITCH  
TRANSFORMER  
After the 15−second pre−purge period, the SureLight ignitor  
warms up for 20 seconds after which the gas valve opens  
for a 4−second trial for ignition. The ignitor energizes during  
the trial until flame is sensed. If ignition is not proved during  
the 4−second period, the control will try four more times with  
an inter purge and warm−up time between trials of 35 sec-  
SURELIGHT  
CONTROL  
BOARD  
FIGURE 2  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
onds. After a total of five trials for ignition (including the ini-  
tial trial), the control goes into Watchguard−Flame Failure  
mode. After a 60−minute reset period, the control will begin  
the ignition sequence again.  
TABLE 1  
Heating Fan Off Delay  
Delay (Seconds)  
Switch 1  
Switch 2  
The SureLight control board has an added feature that pro-  
longs the life of the ignitor. After a successful ignition, the  
SureLight control utilizes less power to energize the ignitor  
on successive calls for heat. The control continues to ramp  
down the voltage to the ignitor until it finds the lowest  
amount of power that will provide a successful ignition. This  
amount of power is used for 255 cycles. On the 256th call  
for heat, the control will again ramp down until the lowest  
power is determined and the cycle begins again.  
60  
90  
Off  
Off  
On  
On  
Off  
On  
Off  
On  
120  
180  
Switch 3 − Second Stage Delay (Used with Single−Stage  
Thermostat Only) −− This switch is used to determine the  
second stage on delay when a single−stage thermostat is  
being used. The switch is factory−set in the ON position,  
which provides a 10−minute delay before second−stage  
heat is initiated. If the switch is toggled to the OFF position,  
it will provide a 15−minute delay before second−stage heat  
is initiated. This switch is only activated when the thermo-  
stat selector jumper is positioned for SINGLE−stage ther-  
mostat use.  
Two Stage Operation / Thermostat Selection Jumper  
The control can be utilized in two modes: SINGLE−STAGE  
thermostat or TWO−STAGE thermostat. The thermostat  
selection jumper E20, located just below dip switches 1  
through 4 (figure 4), must be positioned for the particular  
application. The jumper is factory set on ꢁTWO" for use  
with a two−stage thermostat with two stage heat. Re−posi-  
tion jumper to ꢁSINGLE" for use with a single stage thermo-  
stat with two stage heat.  
While in the single−stage thermostat mode (single jumper  
setting), the burners will always fire on first−stage heat. The  
combustion air inducer will operate on low speed and in-  
door blower will operate on low heat speed. After a 10 min-  
ute recognition period, the unit will switch to second stage  
heat. While in the two−stage thermostat mode (two jumper  
setting) the burners will fire on first−stage heat. The com-  
bustion air inducer will operate on low speed and indoor  
blower will operate on low heat speed. The unit will switch  
to second−stage heat on call from the indoor thermostat. If  
there is a simultaneous call for first and second stage heat,  
the unit will fire on first stage heat and switch to second  
stage heat after 30 seconds of operation. See Sequence of  
Operation flow charts in the back of this manual for more  
detail.  
Switch 4 − Cooling Fan off Delay − The fan on delay time  
of 2 seconds is not adjustable. Fan off time (time that the  
blower operates after the cool demand has been satisfied)  
can be adjusted by flipping dip switch 4. The unit is shipped  
with a factory fan off setting of 45 seconds. Fan off time will  
affect comfort and is adjustable to satisfy individual ap-  
plications. See table 2 for cool fan off time settings.  
TABLE 2  
Cooling Fan Off Delay  
Dip Switch Settings  
Delay (Seconds)  
Switch 4  
Off  
Dip Switches 1 and 2 − Heating Fan off Delay − The fan on  
time of 45 seconds is not adjustable. Fan off time (time that  
the blower operates after the heat demand has been satis-  
fied) can be adjusted by flipping the dip switches 1 and 2  
located on the SureLight integrated control. The unit is  
shipped with a factory fan off setting of 90 seconds. Fan off  
time will affect comfort and is adjustable to satisfy individual  
applications. For customized comfort, monitor the supply  
air temperature once the heat demand is satisfied. Note the  
supply air temperature at the instant the blower is de−ener-  
gized. Adjust the fan−off delay to achieve a supply air tem-  
perature between 90° − 110° at the instant the blower is de−  
energized. (Longer delay times allow for lower air tempera-  
ture, shorter delay times allow for higher air temperature).  
2
45  
On  
Diagnostic LED’s (DS1 and DS2)  
Two diagnostic LED’S are located on the two−stage inte-  
grated control board. See figure 4. These light flashes cor-  
respond with the codes detailed in table 6.  
Factory Installed Jumper Y1 to Y2  
A factory−installed jumper from Y1 to Y2 terminals on the  
integrated control board terminal strip must be clipped for  
two−stage cooling.  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 3  
TWO−STAGE INTEGRATED CONTROL BOARD  
Integrated Control Board Terminals  
120VAC Neutral  
LINE  
XFMR  
EAC  
Line  
Transformer  
LEDs  
Electronic Air Cleaner  
Indoor Blower  
Humidifier  
DIP  
SWITCHES  
1 − 4  
CIRC  
HUM  
120VAC Line  
HUM  
XMFR  
LINE  
Humidifier  
Transformer  
Line  
PARK  
For Unused Leads  
Cooling Speed  
Electronic Air Cleaner  
HIigh Heat Speed  
COOL  
EAC  
HI HEAT  
LO HEAT  
W915 FACTORY INSTALLED JUMPER  
(MUST CLIP FOR 2 STAGE COOL)  
Low Heat, Low Cool and Continuous Fan  
Speed  
TABLE 4  
Integrated Control Board 5 Pin Terminal  
PIN #  
Function  
Ignitor  
1
2
3
4
5
THERMOSTAT CONNECTIONS (TB1)  
Combustion Air Inducer High Speed  
Combustion Air Inducer Low Speed  
Combustion Air Inducer Neutral  
Ignitor Neutral  
TABLE 5  
Integrated Control Board 12Pin Terminal  
PIN #  
1
Function  
Gas Valve 2nd Stage (High Fire)  
Second Stage Prove Switch  
Not Used  
2
3
4
Ground  
5
24V Hot  
DIP SWITCH(ES)  
FUNCTION  
6
Primary Limit In  
1 and 2  
Blower Off Delay (Heating Mode)  
Second Stage ON Delay (Single−stage t’stat)  
Blower Off Delay (Cooling Mode)  
7
Gas Valve 1st stage (Low Fire)  
Gas Valve Common  
24V Neutral  
3
4
8
9
10  
11  
12  
Ground  
Primary Limit Out  
1st Stage Prove Switch  
FIGURE 4  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 6  
DIAGNOSTIC CODES  
Diagnostic LEDs are labeled DS1 and DS2. See figure 4 for location of diagnostic LEDs.  
DS1  
DS2  
DESCRIPTION  
SIMULTANEOUS  
SLOW FLASH  
SIMULTANEOUS  
FAST FLASH  
SIMULTANEOUS  
SLOW FLASH  
SIMULTANEOUS  
FAST FLASH  
Power on − Normal operation.  
Also signaled during cooling and continuous fan.  
Normal operation − signaled when heating demand initiated at thermostat.  
Primary, secondary, backup secondary or rollout limit switch open. Limits must  
close within 3 minutes or unit goes into 1 hour Watchguard.  
Low prove switch open;  
SLOW FLASH  
ON  
OFF  
SLOW FLASH  
OR: Blocked inlet/exhaust vent;  
OR: Low prove switch closed prior to activation of combustion air inducer.  
High prove switch open;  
OR: Blocked inlet/exhaust vent;  
OR: High prove switch closed prior to activation of combustion air inducer.  
OFF  
FAST FLASH  
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;  
OR lost flame sense 5 times in one heating cycle;  
OR pressure switch opened 5 times in one heating cycle.  
ALTERNATING  
SLOW FLASH  
ALTERNATING  
SLOW FLASH  
SLOW FLASH  
OFF  
Flame sensed without gas valve energized.  
ON  
ON  
ON  
OFF  
ON  
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.  
OFF  
FAST FLASH  
SLOW FLASH  
SLOW FLASH  
FAST FLASH  
Main power polarity reversed. Switch line and neutral.  
Low flame signal. Measures below 0.23 microAmps. Replace flame sense rod.  
The following conditions are sensed during the ignitor warm−up period only:  
1) Improper main ground;  
2) Broken ignitor; OR: Open ignitor circuit;  
ALTERNATING  
FAST FLASH  
ALTERNATING  
FAST FLASH  
3) Line voltage below 75 volts.  
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on  
call from thermostat, and will not respond.  
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).  
Low flame sense current = 0.17−0.22 microAmps.  
B−Blower Compartment  
SUPPLY AIR BLOWER  
AND SECONDARY LIMITS  
1. Blower Motor (B3) and Capacitor (C4)  
All G61MP units use direct drive blower motors. All motors  
are 120V permanent split capacitor motors to ensure maxi-  
mum efficiency. Ratings for capacitors will be on motor  
nameplate. See SPECIFICATIONS section for motor speci-  
fications.  
SECONDARY  
LIMIT (S)  
NOTE − Shafts on 1 HP motors have 2 flat sides and are  
matched with blower wheels with 2 set screws.  
2. Secondary Limit Controls (S21)  
MOTOR/BLOWER  
ASSEMBLY  
The secondary limits (S21) on G61MP units are located in the  
blower compartment on the back side of the blower housing.  
See figure 5. All G61MP units are equipped with two secon-  
dary limts. When excess heat is sensed in the blower compart-  
ment, the limit will open. If the limit is open, the furnace control  
energizes the supply air blower and closes the gas valve. The  
limit automatically resets when unit temperature returns to nor-  
mal. The switch is factory set to open at 125°F and cannot be  
adjusted.  
CAPACITOR  
To Remove Blower From Unit: Disconnect Power, Remove Control  
Box, Remove Bolts and Unplug Motor Wires From Control Board.  
Then Slide Out Front of Unit.  
FIGURE 5  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
C−Heating Components  
3. Flame Sensor  
4. Ignitor  
The SureLight ignitor is made of durable silicon nitride. Ig-  
nitor longevity is enhanced by controlling voltage to the ig-  
nitor. The board finds the lowest ignitor temperature which  
will successfully light the burner, thus increasing the life of  
the ignitor. Due to this feature of the board, voltage cannot  
be measured so ignitor must be ohmed. Ohme value  
A flame sensor is located on the left side of the burner sup-  
port. See figure 6. The sensor is mounted through the bot-  
tom of the burner box and the tip protrudes into the flame  
envelope of the left−most burner. The sensor can be re-  
moved for service without removing any part of the burn-  
ers. During operation, flame is sensed by current passed  
through the flame and sensing electrode. The SureLight  
control allows the gas valve to remain open as long as  
flame signal is sensed.  
NOTE − The G61MP furnace contains electronic com-  
ponents that are polarity sensitive. Make sure that the  
furnace is wired correctly and is properly grounded.  
All units use inshot burners. Burners are factory set and do not  
require adjustment. The manifold brackets are slotted so burn-  
ers can be removed as an assembly for service. Burner main-  
tenance and service is detailed in the MAINTENANCE sec-  
tion of this manual. Each burner uses an orifice which is pre-  
cisely matched to the burner input and is threaded into the  
burner manifold. All G61MP natural gas units are fitted with  
.089" sized orifices. See ꢁSPECIFICATIONS" tables for LP  
kits and high altitude.  
NORMAL FLAME SIGNAL > 0.23 MICROAMPS  
LOW FLAME SIGNAL  
DROP OUT SIGNAL  
< 0.22 MICROAMPS  
= 0.16 MICROAMPS  
5/16"  
A flame retention ring in the end of each burner maintains cor-  
rect flame length and shape and keeps the flame from lifting off  
the burner head. In addition, the burner entrance to each clam-  
shell is fitted with a corbel cup (orifice) used to direct the flow  
of combustion products.  
FIGURE 6  
SureLight Ignitor Location  
MEASUREMENT IS TO I.D.  
OF RETENTION RING  
5/8"  
13/32’  
5/16"  
BRACKET  
IGNITOR  
BURNERS FRONT VIEW  
BURNERS TOP VIEW  
FIGURE 7  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
24VAC terminals and gas control knob or switch are located  
on the valve. All terminals on the gas valve are connected to  
wires from the electronic ignition control. 24V applied to the ter-  
minals energizes the valve.  
6. Clamshell Heat Exchanger  
G61MP units use an aluminized steel primary and stain-  
less steel secondary heat exchanger assembly. Heat is  
transferred to the air stream from all surfaces of the heat  
exchanger. The shape of the heat exchanger ensures  
maximum efficiency.  
Inlet and outlet pressure taps are located on the valve. A regu-  
lator adjustment screw is located on the valve.  
LPG change over kit s are available from Lennox. Kits include  
burner orifices and a gas valve regulator conversion kit.  
The combustion air inducer pulls fresh air through the air  
intake box. This air is mixed with gas in the burner venturi  
and at the corbel orifices. The gas / air mixture is then  
burned at the entrance of each clamshell. Combustion  
gases are then pulled through the primary and secondary heat  
exchangers and exhausted out the exhaust vent pipe.  
The burner box is sealed and operates under a negative  
pressure. A pressure hose is connected from the burner  
box to the gas valve. The gas valve senses the pressure in  
the burner box and changes gas valve outlet (manifold)  
pressure based on changes in the burner box pressure.  
The intent is to compensate for different vent configura-  
tions which can greatly affect the rate of the unit.  
7. Flame Rollout Switches (S47)  
Flame rollout switch S47 is a high temperature limit located  
on each side of the burner box. Each furnace is equipped  
with two identical switches. The limit is a N.C. SPST manu-  
al-reset limit connected in series with the primary limit S10.  
When S47 senses rollout, the circuit breaks and the ignition  
control immediately stops ignition and closes the gas  
valve.  
PRIMARY LIMIT LOCATION  
If unit is running and flame rollout is detected, the gas valve  
will close and ignition control will be disabled. Rollout can  
be caused by a blocked heat exchanger, flue or lack of  
combustion air. The switch is factory set to trip (open) at  
250°F and cannot be adjusted. The switch can be manually  
reset. To manually reset a tripped switch, push the reset but-  
ton located on the control.  
limit shield  
090, −110 and  
−135 only  
8. Primary Limit Control (S10)  
Figure 8 shows the primary limit (S10) used on G61MP units  
located in the heating vestibule panel. S10 is provided with a  
shield on some models (figure 8) and must not be removed.  
Note orientation of shield and limit if limit is replaced. When ex-  
cess heat is sensed in the heat exchanger, the limit will open.  
Once the limit opens, the furnace control energizes the  
supply air blower and de−energizes the gas valve. The limit  
automatically resets when unit temperature returns to nor-  
mal. The switch is factory set and cannot be adjusted.  
limit faces shield  
FIGURE 8  
11. Combustion Air Inducer  
Prove Switch (S18)  
All G61MP units are equipped with combustion air prove  
switches located on the combustion air inducer housing.  
G61MP−045 and −070 (figure 10) units have two combustion  
air proving switches. G61MP−090, −110 and −135 units are  
equipped with two dual prove switch ꢁassemblies" consist-  
ing of two switches acting as one. See figure 9. The switches  
are connected to the cold end header box by means of a  
flexible hose that monitors negative air pressure in the cold  
end header box.  
9. Backup Secondary Limit Control (S113)  
(G61MP−090, 110, 135 only)  
Backup secondary limit control S113 is a N.C. auto−reset  
switch located on the combustion air inducer. S113 acts as  
a backup to primary limit S10 in the event of an indoor blow-  
er failure. S113 contacts open when temperature on the  
CAI reaches 142°.  
10. Gas Valve (GV1)  
The G61MP uses a two−stage gas valve manufactured by  
Honeywell (figure 35) or White Rodgers (figure 36). The  
valves are internally redundant to assure safety shut−off. If  
the gas valve must be replaced, the same type valve must  
be used.  
The switches are a single-pole single-throw proving switch  
electrically connected to the furnace control. The purpose of  
the switch is to prevent burner operation if the combustion  
air inducer is not operating or if the flue becomes obstructed.  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
On heat demand (first or second stage) the switch senses  
that the combustion air inducer is operating. It closes a cir-  
cuit to the furnace control when pressure inside the cold  
end header box decreases to a certain set point.  
1 − Remove thermostat demand and allow unit to cycle  
off.  
2 − Install a tee in the negative (−) line and a tee in the positive  
(+) line running from one of the prove switches to the cold  
end header box.  
Set points vary depending on unit size. See tables 8, 9 and  
10. The pressure sensed by the switch is negative. If the air  
intake vent pipe or outlet vent pipe becomes obstructed  
during operation, the switch senses a change of negative  
pressure and opens the circuit to the furnace control and  
gas valve. A bleed port on the switch allows relatively dry  
air in the vestibule to purge switch tubing, to prevent con-  
densate build up.  
3 − Install a manometer with hose from the negative (−)  
side of the manometer to the tee installed in the nega-  
tive (−) line and with hose from the positive (+) side of  
the manometer to the tee in the positive (+) line.  
NOTE − Both sides of the cold end header box are negative.  
However the (+) port reads less negative pressure than the  
(−) port.  
The switch is factory set and is not field adjustable. It is a  
safety shut-down control in the furnace and must not be by−  
passed for any reason. If switch is closed or by−passed, the  
control will not initiate ignition at start up.  
CAI & COLD END HEADER BOX ASSEMBLY  
(−045 & 070 SHOWN)  
Install tee’s in the  
negative line and  
positive line then  
connect hoses to  
manometer.  
DUAL COMBUSTION AIR PROVE SWITCH  
G61MP−090, −110 & −135  
negative  
pressure  
first stage  
_
_
+
+
second stage  
positive  
pressure  
orifice size  
FIGURE 9  
prove switches  
cold end header box  
To troubleshoot the prove switches, temporarily jumper them.  
The unit will not fire with the switches jumpered. Therefore, the  
prove switches must be bypassed after the combustion air in-  
ducer is activated. This will determine if the prove switches  
and furnace are operating properly. However, this may not in-  
dicate if the sealed combustion system is operating properly.  
FIGURE 10  
4 − Operate unit and observe manometer reading. Read-  
ings will change as heat exchanger warms.  
a. Take one reading immediately after start-up.  
b. Take a second reading after unit has reached steady  
state (approximately 5 minutes). This will be the pres-  
sure differential.  
Checks of pressure differential can aid in troubleshooting.  
When measuring the pressure differential, readings should be  
taken at the prove switch. Lack of differential usually indicates  
problems in the intake or exhaust piping, but may indicate  
problems in the heat exchanger, condensing coil, head-  
er boxes, combustion inducer or other components.  
The pressure differential should be greater  
than those listed in table 8, 9 or 10.  
5 − Remove thermostat demand and allow to cycle off.  
6 − Remove manometer and tee’s. Reinstall combustion air  
sensing hoses to the prove switch.  
Measuring pressure differential  
The differential pressure is the difference in pressure mea-  
sured across the cold end header box orifice.  
7 − Repeat steps 1 through 6 for the other prove switch.  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 8  
12. Combustion Air Inducer (B6)  
0’ to 4500’  
All G61MP units use a combustion air inducer to move air  
through the burners and heat exchanger during heating  
operation. The blower uses a PSC 120VAC motor. The  
motor operates during all heating operation and is con-  
trolled by the ignition control A3. Blower operates continu-  
ously while there is a call for heat. The burner ignition con-  
trol will not proceed with the ignition sequence until combus-  
tion air inducer operation is sensed by the proving switches.  
Set Point  
Second Stage  
Set Point  
First Stage  
G61MP Unit  
−045  
−070  
−090  
−110  
−135  
0.95"  
0.95"  
0.85"  
0.60"  
0.50"  
0.35"  
The CAI is installed on the cold end header box. The cold  
end header box is a single piece made of hard plastic.  
The box has an internal channel where the combustion  
air inducer creates negative pressure at unit start up. The  
channel contains an orifice used to regulate flow created  
by the CAI. The box has pressure taps for the CAI prove  
switch hoses.  
TABLE 9*  
4501’ to 7500’  
Set Point  
Second Stage  
Set Point  
First Stage  
G61MP Unit  
−045  
−070  
−090  
−110  
−135  
0.95"  
0.95"  
0.75"  
0.85"  
0.55"  
0.50"  
0.50"  
0.35"  
The prove switches measure the pressures across the  
CAI orifice or difference in the channel and the box. A  
window is provided on the bottom right hand side of the  
box to indicate orifice size. See figure 10. See table 7 for  
orifice size per unit. If replacement is necessary the  
gaskets used to seal the box to the vestbule panel  
and the CAI to the box, must also be replaced.  
*Unit may require conversion kit at this altitude. See High Altitude  
table.  
TABLE 10*  
7501’ to 10,000’  
Set Point  
Second Stage  
Set Point  
First Stage  
G61MP Unit  
TABLE 7  
G61MP Unit  
−045  
C.A.I. Orifice Size  
.719"  
−045  
−070  
−090  
−110  
−135  
0.95"  
0.85"  
0.60"  
0.85"  
0.55"  
0.95"  
0.85"  
0.35"  
0.50"  
0.35"  
−070  
.938"  
−090  
1.063"  
−110  
1.313"  
*Unit may require conversion kit at this altitude. See High Altitude  
table.  
−135  
1.688"  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
II−PLACEMENT AND INSTALLATION  
TABLE 11  
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES  
Vent Pipe Length Equivalency (feet)  
Outdoor  
Exhaust  
Accelerator Accelerator Concen-  
Outdoor  
Exhaust  
2" Wall  
Kit with  
Vent Ex-  
tension  
1−1/2"  
2" Con-  
centric  
Kit  
3" Con-  
centric  
Kit  
VENT  
PIPE  
DIA.  
(in.)  
2" Wall  
Plate Kit  
3" Wall  
Plate Kit  
2" Wall  
Ring Kit  
UNIT  
MODEL  
(Dia. X  
Length)  
(Dia. X  
Length)  
tric Kit  
44J40  
81J20  
1−1/2" X 12"  
2" X 12"  
71M80  
60M29  
60L46  
22G44  
30G28  
15F74  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
4
5
12  
15  
21  
42  
12  
15  
24  
42  
4
5
4*  
5*  
7*  
14*  
4*  
5*  
8*  
14*  
1
4
5
4
5
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
36B−045  
36B−070  
60C−090  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
7
7
7
7
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
14  
4
14  
4
14  
4
14  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
4
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
5
5
5
5
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
8
8
8
8
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
14  
14  
14  
14  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2
1
2
3
6
3
6
1**  
2**  
2**  
4**  
2***  
2***  
4***  
6***  
10***  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
2
6
6
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
4
12  
6
12  
6
4
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
2−1/2  
2
2
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
3
4
3
4
2
6
6
2
60C−110  
60D−135  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
4
12  
12  
15  
25  
4
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
6
6
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
Not  
Allowed  
10  
10  
*Requires field−provided and installed 1−1/2" exhaust accelerator.  
**Requires field−provided and installed 2" exhaust accelerator.  
***For use only in non−direct vent applications, when snow riser is  
not required. Requires field−provided and installed 2" exhaust ac-  
celerator.  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
*NOTE − The exhaust pipe should be offset a minimum of  
12 inches to avoid the possibility of water droplets being re-  
leased from the exhaust termination. The minimum ex-  
haust vent length is 15 ft. Shorter exhaust vent lengths may  
result in the discharge of water droplets from the exhaust  
termination, in spite of the 12−inch vertical offset.  
A−Vent Piping Guidelines  
The G61MP can be installed as either a Non−Direct Vent  
or a Direct Vent gas central furnace.  
NOTE − In Non-Direct Vent installations, combustion air is  
taken from indoors and flue gases are discharged outdoors.  
In Direct Vent installations, combustion air is taken from out-  
doors and flue gases are discharged outdoors.  
Each 90° elbow (including those provided with the furnace)  
of any diameter is equivalent to 5 feet (1.52m) of vent pipe  
of the same diameter. Two 45° elbows are equivalent to  
one 90° elbow of the same diameter. One 45° elbow is  
equal to 2.5 feet (.76m) of vent pipe of the same diameter.  
Intake and exhaust pipe sizing in Direct Vent applications  
and exhaust pipe sizing in Non-Direct Vent applications −−  
Size pipe according to tables 12 and 13. Table 12 lists the  
minimum equivalent vent pipe lengths permitted. Table 13  
lists the maximum equivalent pipe lengths permitted.  
In some applications which permit the use of several differ-  
ent sizes of vent pipe, a combination vent pipe may be  
used. Contact the Application Department for assistance in  
sizing vent pipe in these applications.  
Maximum vent length is defined as:  
Total length (linear feet) of pipe,  
NOTE − The flue collar on all models is sized to accommo-  
date 2" Schedule 40 flue pipe. When vent pipe which is  
larger than 2" must be used in an upflow application, a 2"  
elbow must be applied at the flue collar in order to proper-  
ly transition to the larger diameter flue pipe. This elbow  
must be added to the elbow count used to determine ac-  
ceptable vent lengths. Assign an equivalent feet value to  
this elbow according to the larger size pipe being used.  
Contact the Application Department for more information  
concerning sizing of vent systems which include multiple  
pipe sizes.  
Plus Equivalent length (feet) of fittings,  
Plus Equivalent length (feet) of termination.  
NOTE − Include ALL pipe and ALL fittings, both in  
doors and outdoors.  
Regardless of the diameter of pipe used, the standard roof  
and wall terminations described in section Exhaust Piping  
Terminations should be used. Exhaust vent termination  
pipe is sized to optimize the velocity of the exhaust gas as  
it exits the termination. Refer to table 14.  
Exhaust Pipe Offset  
12" Min.  
12" Min.  
Upflow and Downflow Application  
Rooftop Termination  
Upflow and Downflow Application  
Side Wall Termination  
12" Min.  
12" Min.  
Horizontal Application  
Rooftop Termination  
Horizontal Application  
Side Wall Termination  
FIGURE 11  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use the following steps to correctly size vent pipe diameter.  
1 − Determine the vent termination and its corresponding  
equivalent feet value according to table 11.  
B−PVC Joint Cementing Procedure  
All cementing of joints should be done according to the  
specifications outlined in ASTM D 2855.  
2 − Determine the number of 90° elbows required for both  
indoor and outdoor (e.g. snow riser) use. Calculate the  
corresponding equivalent feet of vent pipe.  
3 − Determine the number of 45° elbows required for both  
indoor and outdoor use. Calculate the corresponding  
equivalent feet of vent pipe.  
WARNING  
DANGER OF EXPLOSION!  
Fumes from PVC glue may ignite during system  
check. Allow fumes to dissipate for at least 5 minutes  
before placing unit into operation.  
4 − Determine the length of straight pipe required.  
5 − Add the total equivalent feet calculated in steps 1  
through 4 and compare that length to the maximum  
values given in table 12 for the proposed vent pipe di-  
ameter. If the total equivalent length required exceeds  
the maximum equivalent length listed in the appropri-  
ate table, evaluate the next larger size pipe.  
1 − Measure and cut vent pipe to desired length.  
2 − Debur and chamfer end of pipe, removing any ridges  
or rough edges. If end is not chamfered, edge of pipe  
may remove cement from fitting socket and result in a  
leaking joint.  
TABLE 12  
MINIMUM VENT PIPE LENGTHS  
G61MP  
MODEL  
MIN. EQUIV.  
VENT LENGTH  
EXAMPLE  
3 − Clean and dry surfaces to be joined.  
045, 070,  
090  
5 ft. plus 2 elbows of 2", 2−1/2", 3"  
or 4" diameter pipe  
4 − Test fit joint and mark depth of fitting on outside of pipe.  
5 ft. plus 2 elbows of 2−1/2" 3" or 4"  
diameter pipe  
110**  
15 ft.*  
5 − Uniformly apply liberal coat of PVC primer for PVC or  
ABS cleaner for ABS to inside socket surface of fitting  
and male end of pipe to depth of fitting socket.  
5 ft. plus 2 elbows of 3" or 4"  
diameter pipe  
135***  
*Any approved termination may be added to the minimum equivalent length  
listed.  
6 − Promptly apply solvent cement to end of pipe and in-  
side socket surface of fitting. Cement should be ap-  
plied lightly but uniformly to inside of socket. Take  
care to keep excess cement out of socket. Apply sec-  
ond coat to end of pipe.  
**G61MP−48C−110 and G61MP−60C−110 must have 90° street ell (supplied)  
installed directly into unit flue collar.  
***G61MP−60D−135 must have 3" to 2" reducing ell (supplied) installed directly  
into unit flue collar.  
TABLE 13  
MAXIMUM VENT PIPE LENGTHS  
MAXIMUM EQUIVALENT VENT  
G61MP  
MODEL  
NOTE − Time is critical at this stage. Do not allow prim-  
er to dry before applying cement.  
LENGTH FEET  
ALTITUDE  
2" dia. 2−1/2" dia. 3" dia. 4" dia.  
045  
070  
59  
59  
65  
65  
42  
32  
n/a  
65  
65  
42  
32  
n/a  
65  
65  
42  
32  
n/a  
77  
78  
234  
214  
204  
179  
160  
234  
214  
204  
179  
160  
234  
214  
204  
179  
160  
7 − Immediately after applying last coat of cement to pipe,  
and while both inside socket surface and end of pipe  
are wet with cement, forcefully insert end of pipe into  
socket until it bottoms out. Turn pipe 1/4 turn during as-  
sembly (but not after pipe is fully inserted) to distribute  
cement evenly.  
0 − 4500  
(0 − 1371 m)  
090  
26  
72  
110*  
135**  
045  
n/a  
n/a  
59  
72  
***61  
77  
070  
59  
78  
4501−7500  
(1372−2286 m)  
090  
26  
72  
110*  
135**  
045  
n/a  
n/a  
59  
72  
***46  
77  
NOTE − Assembly should be completed within 20 sec-  
onds after last application of cement. Hammer blows  
should not be used when inserting pipe.  
070  
59  
78  
7501 − 10000  
(2287 − 3048 m)  
090  
26  
72  
110*  
135**  
n/a  
n/a  
72  
8 − After assembly, wipe excess cement from pipe at end  
of fitting socket. A properly made joint will show a  
bead around its entire perimeter. Any gaps may indi-  
cate a defective assembly due to insufficient solvent.  
***46  
n/a −− Not allowed.  
*G61MP−48C−110 and G61MP−60C−110 must have 90° street ell (supplied)  
installed directly into unit flue collar.  
**G61MP−60D−135 must have 3" to 2" reducing ell (supplied) installed directly  
into unit flue collar.  
***90° elbows used in configuration of G61MP−60D−135 vent, must be lim-  
ited to 3" sweep elbows.  
9 − Handle joints carefully until completely set.  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. In areas where piping penetrates joists or interior  
walls, hole must be large enough to allow clearance on  
all sides of pipe through center of hole using a hanger.  
C− Venting Practices  
The thickness of construction through which vent pipes  
may be installed is 24" (610mm) maximum and 3" (76mm)  
minimum. If a G61MP furnace replaces a furnace which  
was commonly vented with another gas appliance, the size  
of the existing vent pipe for that gas appliance must be  
checked. Without the heat of the original furnace flue prod-  
ucts, the existing vent pipe is probably oversized for the  
single water heater or other appliance. The vent should be  
checked for proper draw with the remaining appliance.  
4. Isolate piping at the point where it exits the outside wall  
or roof in order to prevent transmission of vibration to  
the structure.  
5. When furnace is installed in a residence where unit is  
shut down for an extended period of time, such as a  
vacation home, make provisions for draining conden-  
sate collection trap and lines.  
Exhaust Piping  
1. Use recommended piping materials for exhaust pip-  
ing.  
NOTE − A 2" diameter street ell is strapped to the blower  
deck of 48C−110 and 60C−110 units. Street ell must be  
glued directly into the unit flue collar. See figure 13. A 3" to  
2" reducing ell is strapped to the blower deck of the  
60D−135 units. In upflow or downflow applications, the  
reducing ell must be glued directly into the unit flue collar.  
2. Secure all joints so that they are gas-tight using ap-  
proved cement.  
Suspend piping using hangers at a minimum of every 5  
feet (1.52m) for schedule  
1. Choose the appropriate side for venting in upflow or  
downflow positions. Exhaust piping exits from the top  
of the unit in horizontal air discharge applications.  
Glue the field−provided exhaust vent pipe (or provided  
street ell or reducing ell in upflow or downflow applica-  
tions) to the flue collar. All cement joints should be  
made according to the specifications outlined in ASTM  
D 2855. Refer to pipe and fittings specifications and  
gluing procedures.  
40 PVC and every 3 feet  
STRAPPING  
(metal, plastic  
or large wire  
ties)  
(.91m) for ABS−DWV, PVC−  
DWV, SPR−21 PVC, and  
SDR−26 PVC piping. A suit-  
able hanger can be fabri-  
cated by using metal or  
FIGURE 12  
plastic strapping or a large  
wire tie.  
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION  
IN UPFLOW OR DOWNFLOW DIRECT OR NON-DIRECT VENT APPLICATIONS  
(Right-Hand Exit in Upflow Application Shown)  
2−1/2",  
3", OR  
4"  
2”  
PLUG  
PLUG  
G61MP−045, 070  
or 090 with 2−1/2",  
3", or 4" vent pipe  
REDUCER  
2”  
2”  
VENT PLUG  
(Must be  
glued in  
2"  
2”  
4"  
place)  
2”  
2−1/2",  
3", OR  
4"  
REDUCER  
(use only if  
4" pipe is  
PLUG  
required)  
REDUCER  
2"***  
CONDENSATE  
TRAP  
3"  
(Must be installed  
on same side as  
exhaust piping)  
2"*  
3"**  
G61MP−110 with  
2−1/2", 3", OR 4"  
vent pipe  
G61MP−135 with  
3" OR 4" vent pipe  
*2" diameter street elbow provided.  
**3" diameter reducing elbow provided.  
***Limit pipe length to 2".  
FIGURE 13  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL EXHAUST PIPE CONNECTIONS  
HORIZONTAL DIRECT OR NON-DIRECT VENT  
APPLICATIONS  
CAUTION  
Do not discharge exhaust into an existing stack or  
stack that also serves another gas appliance. If verti-  
cal discharge through an existing unused stack is re-  
quired, insert PVC pipe inside the stack until the end  
is even with the top or outlet end of the metal stack.  
(Horizontal Right-Hand Air  
Discharge Application Shown)  
*Limit pipe length to 2"  
in G61MPV−110 and  
−135 applications.  
2−1/2",  
3", OR  
4"  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110*  
G61MP−60C−110*  
G61MP−60C−135*  
CAUTION  
The exhaust vent pipe operates under positive pres-  
sure and must be completely sealed to prevent leak-  
age of combustion products into the living space.  
REDUCER  
2"*  
2"  
2"  
Intake Piping  
DO NOT transition from  
smaller to larger pipe  
size in horizontal runs.  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
The G61MP furnace may be installed in either direct vent  
or non−direct vent applications. In non−direct vent applica-  
tions, when intake air will be drawn into the furnace from the  
surrounding space, the indoor air quality must be consid-  
ered and guidelines listed in Combustion, Dilution and Ven-  
tilation Air section must be followed.  
2"  
The G61MP unit is designed for either left−side or right−side  
air intake connections in either upflow or downflow applica-  
tions. In horizontal applications, air intake must be brought  
in through the top. Intake air piping is independent of ex-  
haust piping.  
Follow the next four steps when installing the unit in direct  
vent applications, where combustion air is taken from out-  
doors and flue gases are discharged outdoors. The pro-  
vided air intake screen must not be used in direct vent ap-  
plications.  
FIGURE 14  
IMPORTANT  
Exhaust piping and condensate trap must be  
installed on the same side of the unit.  
1 − Cement intake piping in slip connector located on the  
side of the burner box.  
2. All horizontal runs of exhaust pipe must slope back to-  
ward unit. A minimum of 1/4" (6mm) drop for each 12"  
(305mm) of horizontal run is mandatory for drainage.  
Horizontal runs of exhaust piping must be supported ev-  
ery 5 feet (1.52m) using hangers.  
2 − Use a #7 sheet metal screw to secure the intake pipe to  
the connector, if desired. A pilot indentation is provided in  
the slip connector to assist in locating and starting the fas-  
tener.  
NOTE − Exhaust piping should be checked carefully to  
make sure there are no sags or low spots.  
3 − Glue the provided 2" plug into the unused air intake con-  
nector on the opposite side of the cabinet.  
3. On the opposite side of the cabinet, glue the provided  
2" vent plug into the unused flue collar.  
4 − Route piping to outside of structure. Continue with instal-  
lation following instructions given in general guide lines for  
piping terminations and in intake and exhaust piping ter-  
minations for direct vent sections. Refer to figure 15 for  
pipe sizes.  
4. Route piping to outside of structure. Continue with  
installation following instructions given in piping ter-  
mination section.  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS  
(Right-Hand Exit in Upflow Application Shown)  
2−1/2",  
3" OR  
4ꢁ  
2−1/2",  
3" OR  
4ꢁ  
REDUCER  
2ꢁ  
2ꢁ*  
REDUCER  
2"*  
2ꢁ  
2ꢁ  
2ꢁ*  
2ꢁ  
PLUG  
(Must be  
glued in  
place)  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110*  
G61MP−60C−110*  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110*  
G61MP−60C−110*  
G61MP−60C−135*  
*Limit pipe length to 2"  
in G61MP−110 and  
−135 applications.  
FIGURE 15  
Follow the next three steps when installing the unit in Non-  
Direct Vent applications where combustion air is taken  
from indoors and flue gases are discharged outdoors.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
HORIZONTAL DIRECT VENT APPLICATIONS  
(Horizontal Right-Hand Air Discharge Application Shown)  
G61MP−36B−045  
G61MP−36B−070  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
UPFLOW OR HORIZONTAL NON-DIRECT  
VENT APPLICATIONS  
2-1/2”,  
*Limit pipe  
length to 2" in  
G51MP−110  
and −135  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110*  
G61MP−60C−110*  
G61MP−60C−135*  
3” OR 4”  
(Right-Hand Exit in Upflow Application Shown)  
REDUCER  
applications.  
6 in. Max.  
2”*  
2-1/2”,  
3” OR 4”  
2”*  
G61MP−36B−045  
2”  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110*  
G61MP−60C−110*  
PLUG  
(Must be  
glued in  
INTAKE  
place)  
REDUCER  
2”  
DEBRIS  
SCREEN  
(Provided)  
2”*  
2”  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
2”  
NOTE − Debris screen and elbow may be rotated, so that  
screen may be positioned to face forward, backward or  
downward.  
FIGURE 17  
FIGURE 16  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL AIR INTAKE PIPE CONNECTIONS  
DOWNFLOW NON-DIRECT VENT APPLICATIONS  
(Right-Hand Exit in Downflow Applications Shown)  
2" SWEEP  
ELL  
INTAKE  
DEBRIS  
SCREEN  
(Provided)  
6 in. Max.  
PLUG  
PLUG  
(Must be  
glued in  
place)  
(Must be  
glued in  
place)  
2"  
18 in.  
2" SWEEP ELL  
INTAKE DEBRIS  
SCREEN  
(Provided)  
Downflow Additive Flloor Base  
Downflow  
Evaporator  
Coil  
NOTE − Debris screen and sweep ell may be rotated, so that  
screen may be positioned to face forward, backward or to the side.  
FIGURE 18  
1 − Use field−provided materials and the factory−provided  
air intake screen to route the intake piping as shown in  
figures 17 and 18. Maintain a minimum clearance of 3"  
(76mm) around the air intake opening. The air intake  
opening (with the protective screen) should always be  
directed either downward or straight out. Use 2" pipe  
and fittings only and make sure that the air intake does  
not extend more than 6" beyond the G61MP cabinet.  
The air intake connector must not be located near  
the floor. To avoid this complication in downflow  
applications which do not include a downflow  
evaporator coil, the intake air routing should be modi-  
Testing for Proper Venting and Sufficient Combustion Air  
(Non−Direct Vent Applications Only)  
WARNING  
CARBON MONOXIDE POISONING HAZARD!  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon monox-  
ide poisoning or death.  
The following steps shall be followed for each ap-  
pliance connected to the venting system being  
placed into operation, while all other appliances con-  
nected to the venting system are not in operation.  
2 − Use a #7 sheet metal screw to secure the intake pipe to  
the connector, if desired. A pilot indentation is provided in  
the slip connector to assist in locating and starting the fas-  
tener.  
After the G61MP gas furnace has been started, the follow-  
ing test should be conducted to ensure proper venting and  
sufficient combustion air has been provided to the G61MP,  
as well as to other gas-fired appliances which are separate-  
ly vented. The test should be conducted while all ap-  
pliances (both in operation and those not in operation) are  
connected to the venting system being tested. If the vent-  
ing system has been installed improperly, or if provisions  
have not been made for sufficient amounts of combustion  
air, corrections must be made as outlined in the previous  
section.  
3 − Glue the provided 2" plug into the unused air intake con-  
nector on the opposite side of the cabinet.  
1 − Seal any unused openings in the venting system.  
2 − Visually inspect the venting system for proper size and  
horizontal pitch. Determine there is no blockage or re-  
striction, leakage, corrosion, or other deficiencies  
which could cause an unsafe condition.  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3 − To the extent that it is practical, close all building doors  
and windows and all doors between the space in which  
the appliances connected to the venting system are lo-  
cated and other spaces of the building.  
from any obstructions and above the level of snow accu-  
mulation (where applicable). The termination should be at  
least 12 inches (305mm) from any opening through which  
flue products could enter the building.  
4 − Close fireplace dampers.  
At vent termination, care must be taken to maintain  
protective coatings over building materials (prolonged  
exposure to exhaust condensate can destroy protective  
coatings). It is recommended that the exhaust outlet not be  
located within 6 feet (1.8m) of a condensing unit because  
the condensate can damage the painted coating.  
5 − Turn on clothes dryers and any appliances not con-  
nected to the venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhausts, so  
they will operate at maximum speed. Do not operate a  
summer exhaust fan.  
6 − Follow the lighting instruction to place the appliance  
being inspected into operation. Adjust thermostat so  
appliance will operate continuously.  
NOTE − If winter design temperature is below 32°F (0°C),  
exhaust piping should be insulated with 1/2" (13mm), Ar-  
maflex or equivalent when run through unheated space.  
Do not leave any surface area of exhaust pipe open to out-  
side air; exterior exhaust pipe should be insulated with 1/2"  
(13mm) Armaflex or equivalent. In extreme cold climate  
areas, 3/4" (19mm) Armaflex or equivalent may be neces-  
sary. Insulation on outside runs of exhaust pipe must be  
painted or wrapped to protect insulation from deterioration.  
Exhaust pipe insulation may not be necessary in some  
specific applications.  
7 − Test for spillage of flue gases at the draft hood relief  
opening after 5 minutes of main burner operation. Use  
the flame of match or candle, or smoke from a ciga-  
rette, cigar.  
8 − If improper venting is observed during any of the  
above tests, the venting system must be corrected or  
sufficient combustion/make-up air must be provided.  
The venting system should be re-sized to approach  
the minimum size as determined by using the ap-  
propriate tables in appendix G in the current standards  
of the National Fuel Gas Code ANSI−Z223.1/NPFA 54  
in the U.S.A., and the appropriate Natural Gas and  
Propane appliances venting sizing tables in the cur-  
rent standard of the CSA−B149 Natural Gas and Pro-  
pane Installation Codes in Canada.  
NOTE − During extremely cold temperatures, below  
approximately 20°F (6.7°C), units with long runs of vent  
pipe through unconditioned space, even when insulated,  
may form ice in the exhaust termination that prevents the  
unit from operating properly. Longer run times of at least 5  
minutes will alleviate most icing problems. Also, a heating  
cable may be installed on exhaust piping and termination to  
prevent freeze−ups. Heating cable installation kit is avail-  
able from Lennox. See Condensate Piping section for part  
numbers.  
9 − After determining that each appliance remaining  
connected to the common venting system properly  
vents when tested as indicated in step 3, return  
doors, windows, exhaust fans, fireplace dampers  
and any other gas-burning appliance to their previous  
condition of use.  
General Guidelines for Vent Terminations for Non-Direct  
Vent Installations.  
IMPORTANT  
Do not use screens or perforated metal in exhaust  
terminations. Doing so will cause freeze−ups and  
may block the terminations.  
In Non-Direct Vent applications, combustion air is taken  
from indoors and the flue gases are discharged to the out-  
doors. The G61MP is then classified as a non-direct vent,  
Category IV gas furnace. In Non-Direct Vent applications,  
the vent termination is limited by local building codes. In  
the absence of local codes, refer to the current National  
Fuel Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and cur-  
rent CSA−B149 Natural Gas and Propane Installation  
Codes in Canada for details.  
IMPORTANT  
For Canadian Installations Only:  
In accordance to CSA International B149 installation  
codes, the minimum allowed distance between the  
combustion air intake inlet and the exhaust outlet of  
other appliances shall not be less than 12 inches  
(305mm).  
Position termination end according to location given in fig-  
ure 19. In addition, position termination end so it is free  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT TERMINATION CLEARANCES  
FOR INSTALLATIONS IN THE USA AND CANADA*  
G61MP VENT TERMINATION  
AIR INLET OF OTHER APPLIANCE  
C
less than  
10 ft (3.048M)  
D
F
D
E
G
A − Clearance above grade − 12 in. (305mm) minimum.  
E − Clearance to non−mechanical air supply inlet or outlet  
for vent installations in USA − 48 in. (1219mm) minimum  
horizontal and below, 12 in. (305mm) minimum above.  
for vent installations in Canada − 12 in. (305mm) minimum  
for appliances 100,000 Btuh (30 kW);  
B − Clearance to window or door that may be opened −  
for vent installations in USA − 12 in. (305mm) minimum.  
for vent installations in Canada − 12 in. (305mm) minimum  
for appliances 100,000 Btuh (30 kW);  
36 in. (0.9m) minimum for appliances > 100,000 Btuh (30  
kW).  
36 in. (0.9m) minimum for appliances > 100,000 Btuh (30  
kW).  
F − Clearance to mechanical air supply inlet −−  
for vent installations in USA − 36 in. minimum (914mm).  
C − Do not position terminations directly under roof eaves.  
D − Clearance to electric meters, gas meters, regulators, and  
relief equipment −  
G − Clearance to mechanical air supply inlet −−  
for vent installations in Canada − 72 in. (1829mm) mini-  
mum.  
for vent installations in USA − 48 in (1219mm) minimum.  
for vent installations in Canada − see current edition of CSA  
B149 Code.  
H − Do not point terminations into recessed areas such as win-  
dow wells, stairwells or alcoves.  
J − Do not position terminations directly above a walkway.  
* Note −  
(I) Dimensions are from the current edition of The National Fuel Gas Code − ANSI-Z223.1/NFPA 54 for USA installa-  
tions. In Canada, refer to current edition of CSA B149 installation codes. Local codes or regulations may require dif-  
ferent clearances.  
(II) In Non-Direct Vent installations, combustion air is taken from indoors and the flue gases are discharged to the outdoors.  
FIGURE 19  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Details of Intake and Exhaust Piping Terminations for  
Direct Vent Installations  
9. Based on the recommendation of the manufacturer, a  
multiple furnace installation may use a group of up to  
four termination kits WTK assembled together hori-  
NOTE − In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged to outdoors.  
TABLE 14  
EXHAUST PIPE TERMINATION SIZE REDUCTION  
Intake and exhaust pipes may be routed either horizontally  
through an outside wall or vertically through the roof. In at-  
tic or closet installations, vertical termination through the  
roof is preferred. Figures 20 through 28 show typical ter-  
minations.  
G61MP  
MODEL  
Exhaust Pipe Size  
Termination Pipe Size  
045 and 070  
090  
2", 2−1/2", 3" or 4"  
2", 2−1/2", 3" or 4"  
2−1/2", 3" or 4"  
3" or 4"  
1−1/2"  
2"  
1. Exhaust and intake exits must be in same pressure  
zone. Do not exit one through the roof and one on the  
side. Also, do not exit the intake on one side and the  
exhaust on another side of the house or structure.  
110  
2"*  
135  
2"*  
*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.  
3(76) MAX.  
2. Intake and exhaust pipes should be placed as close  
together as possible at termination end (refer to il-  
lustrations). Maximum separation is 3" (76mm) on roof  
terminations and 6" (152mm) on side wall termina-  
tions.  
SIZE TERMINATION  
PIPE PER TABLE 14.  
Inches(mm)  
UNCONDITIONED  
ATTIC SPACE  
8" (203) MIN  
1/2" (13) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
3. If necessary, install a field−provided reducer to adapt  
larger vent pipe size to termination pipe size.  
12" (305) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
4. On roof terminations, the intake piping should termi-  
nate straight down using two 90° elbows (See figure  
20).  
3" (76) OR  
2" (51) PVC  
5. Exhaust piping must terminate straight out or up as  
shown. In rooftop applications, a reducer may be re-  
quired on the exhaust piping at the point where it exits  
the structure to improve the velocity of exhaust away  
from the intake piping. See table 14.  
PROVIDE SUPPORT  
FOR INTAKE AND  
EXHAUST LINES  
NOTE − Care must be taken to avoid recirculation of  
exhaust back into intake pipe.  
DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
6. On field supplied terminations for side wall exits, ex-  
haust piping should extend a minimum of 12 inches  
(305mm) beyond the outside wall. Intake piping  
FIGURE 20  
12" (305) MAX.  
(unless supported)  
1/2" (13) ARMAFLEX  
INSULATION IN  
UNCONDITIONED SPACE  
7. On field supplied terminations, a minimum separation  
distance between the end of the exhaust pipe and the  
end of the intake pipe is 8 inches (203mm).  
1/2" (13)  
ARMAFLEX  
INSULATION  
FIELD−  
PROVIDED  
REDUCER MAY  
BE REQUIRED  
TO ADAPT  
LARGER VENT  
PIPE SIZE TO  
TERMINATION  
SIZE  
8. If intake and exhaust piping must be run up a side wall  
to position above snow accumulation or other obstruc-  
tions, piping must be supported every 3 ft. (.9m) as  
shown in figure 12. Refer to figure 24 for proper piping  
method. In addition, WTK wall termination kit must be  
extended for use in this application. See figure 27.  
When exhaust and intake piping must be run up an  
outside wall, the exhaust piping is reduced to 1−1/2"  
(38mm) after the final elbow. The intake piping may be  
equipped with a 90° elbow turndown. Using turndown  
will add 5 feet (1.5m) to the equivalent length of the  
pipe.  
TERMINATION  
PIPE PER  
TABLE 14.  
6" (152)  
MAXIMUM  
OUTSIDE  
WALL  
8" (203)  
MINIMUM  
2" (51) PVC  
COUPLING  
Inches (mm)  
TOP VIEW WALL RING KIT  
(15F74)  
FIGURE 21  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXHAUST VENT  
EXHAUST  
TERMINATION  
12" (305) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
Inches (mm)  
Front View  
INTAKE  
VENT  
INTAKE  
TERMINATION  
1/2" (13) Foam Insulation  
in Unconditioned Space  
Side View  
FIELD−PROVIDED  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
FIELD−  
PROVIDED  
REDUCER MAY  
BE REQUIRED  
TO ADAPT  
EXHAUST VENT  
EXHAUST  
INTAKE  
LARGER VENT  
PIPE SIZE TO  
TERMINATION  
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION  
(71M80, 69M29 or 60L46)  
INTAKE VENT  
OUTSIDE WALL  
Inches (mm)  
FIGURE 22  
DIRECT VENT WALL TERMINATION KIT  
(22G44, 44J40, 30G28 or 81J20)  
INTAKE  
Inches (mm)  
TERMINATION  
EXHAUST  
TERMINATION  
FIGURE 25  
EXHAUST  
12"  
(305)  
INTAKE  
EXHAUST  
VENT  
12" (305) Min.  
above grade.  
5"  
(127)  
5−1/2"  
(140)  
FIELD−PROVIDED  
REDUCER MAY  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
INTAKE  
VENT  
18" MAX.  
(457)  
Front View  
EXHAUST VENT  
DIRECT VENT CONCENTRIC WALL TERMINATION  
(71M80, 69M29 or 60L46)  
Inches (mm)  
FIGURE 23  
INTAKE  
VENT  
Side View  
12" (305) MAX. for 2" (51)  
(unless supported)  
Inches(mm)  
UNCONDITIONED  
SPACE  
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT  
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT WTK  
8 (203)  
MIN.  
OUTSIDE WALL  
FIGURE 26  
SIZE  
TERMINATION  
PROVIDE SUPPORT  
FOR INTAKE AND  
PIPE PER  
EXHAUST LINES EVERY  
36" (914)  
TABLE 14.  
12" (305) ABOVE  
FIELD−PROVIDED  
AVERAGE SNOW  
REDUCER MAY  
ACCUMULATION  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
1/2" (13) FOAM  
INSULATION IN  
UNCONDITIONED  
SPACE  
1/2" (13) FOAM  
INSULATION  
SIDE VIEW  
DIRECT VENT WALL RING TERMINATION  
(15F74)  
See venting table 12 for maximum venting lengths with this arrange-  
ment.  
FIGURE 24  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
12" (305) MAX. for 2" (51)  
20" (508) MAX. for 3" (76)  
(unless supported)  
Inches (mm)  
EXHAUST  
AIR  
COVER EXHAUST  
VENT WITH  
1/2" (13)  
12"  
(305)  
FOAM  
INSULATION  
8" (203)  
INTAKE  
AIR  
INTAKE  
AIR  
Minimum  
EXHAUST  
12" (305)  
Minimum  
ABOVE GRADE  
AIR  
12" MIN.  
(305)  
5"  
(127)  
Above Grade  
5-1/2"  
(140)  
GRADE  
Side View  
GRADE  
Front View  
DIRECT VENT TERMINATION  
WALL TERMINATION KIT (22G44, 44J40, 30G28 or 81J20) EXTENDED VENT FOR GRADE CLEARANCE  
FIGURE 27  
G61MP DIRECT VENT APPLICATION  
USING EX
STRAIGHT−CUT OR  
ANGLE−CUT IN DIRECTION  
OF ROOF SLOPE *  
Inches(mm)  
SIZE TERMINATION  
PIPE PER TABLE  
14.  
12" (305mm)  
ABOVE AVE.  
SNOW  
ACCUMULATION  
3" − 8"  
(76mm−  
8" − 12"  
EXHAUST VENT  
1/2" (13mm)  
WEATHERPROOF  
INSULATION  
203mm)  
(203mm − 305mm)  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
INTAKE PIPE  
INSULATION (optional)  
3" (76) OR  
2" (51) PVC  
SHEET  
METAL TOP  
PLATE  
UNCONDITIONED  
ATTIC SPACE  
ALTERNATE  
INTAKE PIPE  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
MINIMUM 12"  
(305mm) ABOVE  
ROOF  
3" − 8"  
(76mm−  
203mm)  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
*SIZE TERMINATION  
PIPE PER TABLE 14.  
NON−DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
FIGURE 29  
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 28  
Details of Exhaust Piping Terminations for Non-Direct  
Vent Applications  
12" (305) Max. for 2" (51)  
Unless Supported  
1/2" (13) ARMAFLEX  
INSULATION IN  
UNCONDITIONED SPACE  
Exhaust pipes may be routed either horizontally through an  
outside wall or vertically through the roof. In attic or closet  
installations, vertical termination through the roof is pre-  
ferred. Figures 29 through 32 show typical terminations.  
1/2" (13)  
ARMAFLEX  
INSULATION  
FIELD−PROVIDED  
REDUCER MAY  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
1. Exhaust piping must terminate straight out or up as  
shown. The termination pipe must be sized as listed in  
table 14.The specified pipe size ensures proper ve-  
locity required to move the exhaust gases away from  
the building.  
PVC REDUCER  
SIZE TERMINATION  
PIPE PER TABLE 14.  
Inches (mm)  
TOP VIEW  
NON−DIRECT VENT WALL RING KIT  
(15F74)  
2. On field supplied terminations for side wall exits, ex-  
haust piping should extend a maximum of 12 inches  
(305mm) beyond the outside wall, unless support is  
provided in the horizontal section. See figure 30.  
FIGURE 30  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. If exhaust piping must be run up a side wall to position  
above snow accumulation or other obstructions, pip-  
ing must be supported every 3 feet (.9m) as shown in  
figure 12. Refer to figure 31 for proper piping method.  
When exhaust piping must be run up an outside wall,  
any reduction in exhaust pipe size must be done after  
the final elbow.  
CONDENSATE TRAP LOCATIONS  
(Unit shown in upflow position)  
Horizontal  
left and  
Horizontal  
right and  
optional  
optional  
downflow  
downflow  
12" (305) Max. for 2" (51)  
Unless Supported  
Inches(mm)  
UNCONDITIONED  
SPACE  
OUTSIDE WALL  
SIZE TER-  
MINATION  
PIPE PER  
TABLE 14.  
Optional  
upflow  
Optional  
upflow  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
EVERY 36" (914)  
12" (305) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
FIELD−PROVIDED  
REDUCER MAY BE  
REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE TO  
TERMINATION  
FIGURE 33  
1/2" (13) FOAM  
1 − Determine which side condensate piping will exit the  
unit. Remove plugs from the condensate collar at the  
appropriate location on the side of the unit.  
INSULATION IN  
UNCONDITIONED  
SPACE  
1/2" (13) FOAM  
INSULATION  
SIDE VIEW  
NON−DIRECT VENT WALL RING TERMINATION  
(15F74)  
NOTE − The condensate trap is factory−shipped with  
two rubber O−rings and two rubber clean−out caps  
installed. Check to make sure that these items are in  
place before installing the trap assembly.  
FIGURE 31  
G61MP NON−DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
2 − Install condensate trap onto the condensate collar.  
Use provided HI/LO screws to secure two upper  
flanges of the trap to the collar. Use provided sheet  
metal screw to secure bottom trap flange to side of  
unit. See figure 34.  
STRAIGHT−CUT OR  
ANGLE−CUT IN DIRECTION  
OF ROOF SLOPE  
SIZE TERMINATION  
PIPE PER TABLE 14.  
3" − 8"  
(76mm−  
203mm)  
EXHAUST VENT  
1/2" (13mm)  
WEATHERPROOF  
INSULATION  
NOTE − In upflow and downflow applications, con-  
densate trap must be installed on the same side as  
exhaust piping.  
MINIMUM12"  
(305mm) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
SHEET  
METAL TOP  
PLATE  
CAUTION  
DO NOT use a power driver to tighten screws which  
secure condensate trap to cabinet. Screws should  
be hand−tightened using a screw driver to avoid the  
possibility of damage to the trap assembly.  
3" − 8"  
(76mm−  
203mm)  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
3 − Glue the field−provided coupling or pipe to the trap.  
Install a tee and vent pipe near the trap.  
NOTE − The condensate trap drain stubs (both sides)  
have an outer diameter which will accept a standard  
3/4" PVC coupling. The inner diameter of each stub  
will accept standard 1/2" diameter PVC pipe.  
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 32  
NOTE − Vinyl tubing may be used for condensate  
drain. Tubing must be 1−1/4" OD X 1" ID and should be  
attached to the drain stubs on the trap using a hose  
clamp.  
Condensate Piping  
This unit is designed for either right- or left-side exit of con-  
densate piping in either upflow or downflow applications;  
however, it must be installed on the same side of the unit as  
the exhaust piping. In horizontal applications, the conden-  
sate trap should extend below the unit. A 5−1/2" service  
clearance is required for the condensate trap. Refer to fig-  
ure for condensate trap locations.  
4 − Glue the field−provided drain line to the tee. Route the  
drain line to an open drain. As an alternate, clear vinyl  
tubing may be used to drain condensate away from  
the trap. Secure the vinyl tubing to the drain stubs on  
the trap using a hose clamp. Do not overtighten the  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
hose clamp.  
5 − If unit will be started immediately upon completion of  
installation, prime trap per procedure outlined in Unit  
Start−Up section.  
Condensate line must be sloped downward away from  
condensate trap to drain. If drain level is above con-  
densate trap, condensate pump must be used. Con-  
densate drain line should be routed within the condi-  
tioned space to avoid freezing of condensate and  
blockage of drain line. If this is not possible, a heat  
cable kit may be used on the condensate trap and line.  
Heating cable kit is available from Lennox in various  
lengths; 6 ft. (1.8m) − kit no. 18K48; 24 ft. (7.3m) − kit  
no. 18K49; and 50 ft. (15.2m) − kit no. 18K50.  
6 − Glue the provided cap onto the unused condensate  
drain line stub.  
CONDENSATE ASSEMBLY  
HI/LO SCREWS  
(DO NOT use power  
driver. Hand−tighten  
using screw driver.)  
VENT  
NIPPLE  
O−RINGS  
CAUTION  
Do not use copper tubing or existing copper  
condensate lines for drain line.  
TEE  
CAP  
NIPPLE  
COUPLING  
CLEAN−OUT ACCESS  
(both sides)  
CONDENSATE TRAP  
SCREW  
FIGURE 34  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
III−START-UP  
WARNING  
If you do not follow these instructions exactly, a fire  
or explosion may result causing property damage,  
personal injury or death.  
A−Preliminary and Seasonal Checks  
1 − Inspect electrical wiring, both field and factory installed  
for loose connections. Tighten as required.  
2 − Check voltage at disconnect switch. Voltage must be  
within range listed on the nameplate. If not, consult the  
power company and have voltage condition corrected  
before starting unit.  
B−Heating Start-Up  
FOR YOUR SAFETY READ BEFORE OPERATING  
1 − STOP! Read the safety information at the beginning of  
this section.  
WARNING  
Shock and burn hazard.  
2 − Set the thermostat to the lowest setting.  
3 − Turn off all electrical power to the unit.  
G61MP units are equipped with a hot surface igni-  
tion system. Do not attempt to light manually.  
4 − This furnace is equipped with an ignition device which  
automatically lights the burners. Do not try to light the  
burners by hand.  
BEFORE LIGHTING the unit, smell all around the fur-  
nace area for gas. Be sure to smell next to the floor be-  
cause some gas is heavier than air and will settle on the  
floor.  
5 − Remove the upper access panel.  
The gas valve on the G61MP may be equipped with ei-  
ther a gas control knob or gas control lever. Use only your  
hand to push the lever or turn the gas control knob. Never  
use tools. If the the lever will not move or the knob will not  
push in or turn by hand, do not try to repair it. Force or at-  
tempted repair may result in a fire or explosion.  
6 − Honeywell VR8205 Gas Valve − Turn knob on gas  
valve clockwise  
35.  
to OFF. Do not force. See figure  
White Rodgers 36E Gas Valve − Switch gas valve le-  
ver to OFF. See figure 36 for the White Rodgers 36E  
valve.  
Placing the furnace into operation:  
®
G61MP units are equipped with a SureLight ignition  
system. Do not attempt to manually light burners on this  
furnace. Each time the thermostat calls for heat, the  
burners will automatically light. The ignitor does not get  
7 − Wait five minutes to clear out any gas. If you then smell  
gas, STOP! Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s instruc-  
tions. If you do not smell gas go to next step.  
®
hot when there is no call for heat on units with SureLight  
ignition system.  
Priming Condensate Trap  
The condensate trap should be primed with water prior to  
start−up to ensure proper condensate drainage. Either  
pour 10 fl. oz. (300 ml) of water into the trap, or follow  
these steps to prime the trap:  
HONEYWELL VR8205 Series Gas Valve  
REFERENCE TO  
BURNER BOX  
hose barb in place of cap  
1 − Follow the lighting instructions to place the unit into op-  
eration.  
MANIFOLD  
PRESSURE  
TAP  
HIGH FIRE  
ADJUSTMENT  
SCREW  
2 − Set the thermostat to initiate a heating demand.  
(under cap)  
3 − Allow the burners to fire for approximately 3 minutes.  
4 − Adjust the thermostat to deactivate the heating de-  
mand.  
5 − Wait for the combustion air inducer to stop. Set the  
thermostat to initiate a heating demand and again al-  
low the burners to fire for approximately 3 minutes.  
lOW FIRE  
ADJUSTMENT  
SCREW  
(under cap)  
6 − Adjust the thermostat to deactivate the heating de-  
mand and again wait for the combustion air inducer to  
stop. At this point, the trap should be primed with suffi-  
cient water to ensure proper condensate drain opera-  
tion.  
iNLET PRESSURE TAP  
GAS VALVE SHOWN IN OFF POSITION  
FIGURE 35  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IV−HEATING SYSTEM SERVICE CHECKS  
A−C.S.A. Certification  
All units are C.S.A. (formally A.G.A. and C.G.A. combined)  
design certified without modifications. Refer to the G61MP  
Installation Instruction.  
WHITE RODGERS 36E SERIES GAS VALVE  
HIGH FIRE  
MANIFOLD  
PRESSURE  
ADJUSTMENT  
ON SIDE  
B−Gas Piping  
(under cap)  
MANIFOLD  
PRESSURE  
TAP ON SIDE  
CAUTION  
If a flexible gas connector is required or allowed by  
the authority that has jurisdiction, black iron pipe  
shall be installed at the gas valve and extend outside  
the furnace cabinet.  
LOW FIRE MANIFOLD  
PRESSURE ADJUSTMENT  
ON SIDE (under cap)  
INLET PRESSURE  
TAP ON SIDE  
GAS VALVE SHOWN IN OFF POSITION  
FIGURE 36  
WARNING  
Do not exceed 600 in−lbs (50 ft−lbs) torque when  
attaching the gas piping to the gas valve.  
8 − Honeywell VR8205 Gas Valve − Turn knob on gas  
valve counterclockwise  
to ON. Do not force.  
White Rodgers 36E Gas Valve − Switch gas valve lever  
to ON. See figure 36 for the White Rodgers 36E  
valve.  
Gas supply piping should not allow more than 0.5"W.C. drop  
in pressure between gas meter and unit. Supply gas pipe  
must not be smaller than unit gas connection.  
9 − Replace the upper access panel.  
10− Turn on all electrical power to to the unit.  
11− Set the thermostat to desired setting.  
Compounds used on gas piping threaded joints should be  
resistant to action of liquefied petroleum gases.  
NOTE − When unit is initially started, steps 1 through 11  
may need to be repeated to purge air from gas line.  
C−Testing Gas Piping  
12− If the appliance will not operate, follow the instructions  
ꢁTurning Off Gas to Unit" and call your service techni-  
cian or gas supplier.  
IMPORTANT  
In case emergency shutdown is required, turn off  
the main shut-off valve and disconnect the main  
power to unit. These controls should be properly  
labeled by the installer.  
Turning Off Gas to Unit  
1 − Set the thermostat to the lowest setting.  
2 − Turn off all electrical power to the unit if service is to be  
performed.  
When pressure testing gas lines, the gas valve must be dis-  
connected and isolated. Gas valves can be damaged if  
subjected to more than 0.5psig (14" W.C.). See figure 37.  
3 − Remove the upper access panel.  
4 − Honeywell VR8205 Gas Valve − Turn knob on gas  
valve clockwise to OFF. Do not force.  
White Rodgers 36E Gas Valve Switch gas valve le-  
ver to OFF.  
GAS PIPING TEST PROCEDURE  
MANUAL MAIN SHUT−OFF VALVE  
5 − Replace the upper access panel.  
C−Safety or Emergency Shutdown  
Turn off unit power. Close manual and main gas valves.  
D−Extended Period Shutdown  
CAP  
Turn off thermostat or set to ꢁUNOCCUPIED" mode. Close  
all gas valves (both internal and external to unit) to guaran-  
tee no gas leak into combustion chamber. Turn off power to  
unit. All access panels and covers must be in place and se-  
cured.  
GAS VALVE  
FIGURE 37  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
When checking piping connections for gas leaks, use pre-  
ferred means. Kitchen detergents can cause harmful corro-  
sion on various metals used in gas piping. Use of a specialty  
Gas Leak Detector is strongly recommended. It is available  
through Lennox under part number 31B2001. See Corp.  
8411−L10, for further details.  
5 − After allowing unit to stabilize for 5 minutes, record  
manifold pressure and compare to value given in table  
19.  
6 − Repeat steps 3, 4 and 5 on high heat.  
NOTE − Shut unit off and remove manometer as soon as an  
accurate reading has been obtained. Take care to replace  
pressure tap plug.  
Do not use matches, candles, flame or any other source of  
ignition to check for gas leaks.  
NOTE − During this test procedure, the unit will be overfir-  
ing:  
D−Testing Gas Supply Pressure  
D Operate unit only long enough to obtain accurate read-  
ing to prevent overheating heat exchanger.  
When testing supply gas pressure, connect test gauge to  
inlet pressure tap on the gas valve. See figures and 35 and  
36. Check gas line pressure with unit firing at maximum  
rate. Low pressure may result in erratic operation or under-  
fire. High pressure can result in permanent damage to gas  
valve or overfire. See table 15 for operating pressure at unit  
gas connection (line).  
D Attempts to clock gas meter during this procedure will  
be inaccurate. Measure gas flow rate only during nor-  
mal unit operation.  
7 − When test is complete remove obstruction from hose  
and return hose to gas valve barbed fitting.  
On multiple unit installations, each unit should be checked  
separately, with and without units operating. Supply pres-  
sure must fall within range listed in table 15.  
TABLE 15  
F− Proper Gas Flow (Approximate)  
Furnace should operate at least 5 minutes before check-  
ing gas flow. Determine time in seconds for two revolu-  
tions of gas through the meter. (Two revolutions assures a  
more accurate time.) Divide by two and compare to time  
in table 16 below. If manifold pressure matches table 15  
and rate is incorrect, check gas orifices for proper size and  
restriction.  
All G61MP Units  
Natural  
LP  
Line Pressure WC"  
4.5 − 10.5  
11.0 − 13.0  
E−Check Manifold Pressure  
After line pressure has been checked and adjusted, check  
manifold pressure. Move pressure gauge to outlet pres-  
sure tap located on unit gas valve (GV1). Checks of man-  
ifold pressure are made as verification of proper regulator ad-  
justment. Manifold pressure for the G61MP can be measured  
at any time the gas valve is open and is supplying gas to the  
unit. See table 19 for manifold pressures.  
NOTE− To obtain accurate reading, shut off all other gas  
appliances connected to meter.  
TABLE 16  
GAS METER CLOCKING CHART  
Seconds for One Revolution  
Natural  
1 cu ft  
Dial  
82  
LP  
G61MP  
Unit  
2 cu ft  
Dial  
164  
110  
82  
1 cu ft  
Dial  
205  
136  
102  
82  
2 cu ft  
DIAL  
410  
−45  
−70  
IMPORTANT  
For safety, connect a shut-off valve between the  
manometer and the gas tap to permit shut off of  
gas pressure to the manometer.  
55  
272  
−90  
41  
204  
−110  
−135  
33  
66  
164  
27  
54  
68  
136  
Natural−1000 btu/cu ft  
LP−2500 btu/cu ft  
The gas valve is factory set and should not require adjust-  
ment. All gas valves are factory regulated sensing atmo-  
spheric pressure.  
IMPORTANT  
Manifold Pressure Measurement & Adjustment  
For safety, shut unit off and remove manometer as  
soon as an accurate reading has been obtained.  
Take care to replace pressure tap plug.  
NOTE − Pressure test adapter kit (10L34) is available from  
Lennox to facilitate manifold pressure measurement.  
1 − Connect test gauge to outlet tap on gas valve.  
G− Proper Combustion  
2 − Disconnect pressure sensing hose from gas valve.  
3 − Start unit on low heat and allow 5 minutes for unit to  
reach steady state.  
Furnace should operate minimum 15 minutes with correct  
manifold pressure and gas flow rate before checking com-  
bustion. See sections E− and F−. Take combustion sample  
beyond the flue outlet and compare to the tables below.  
The maximum carbon monoxide reading should not ex-  
ceed 100 ppm.  
4 − While waiting for the unit to stabilize, notice the flame.  
Flame should be stable and should not lift from burner.  
Natural gas should burn blue.  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 17  
High Heat  
CO %  
H− High Altitude  
NOTE − In Canada, certification for installations at eleva-  
tions over 4500 feet (1372 m) is the jurisdiction of local au-  
thorities.  
Unit  
CO %  
For L.P.  
2
For Nat  
2
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110  
G61MP−60C−110  
G61MP−60D−135  
6.5 − 7.5  
7.4 − 8.4  
6.5 − 7.5  
6.9 − 7.9  
6.9 − 7.9  
7.2 − 8.2  
7.2 − 8.2  
7.4 − 8.4  
7.4 − 8.4  
7.8 − 8.8  
7.8 − 8.8  
8.1 − 9.1  
8.1 − 9.1  
8.3 − 9.3  
The manifold pressure may require adjustment to ensure  
proper operation at higher altitudes. Refer to table 19 for  
proper manifold pressure settings at varying altitudes and  
required pressure switch changes and conversion kits at  
varying altitudes.  
The combustion air pressure switches are factory−set and  
require no adjustment.  
NOTE − A natural to L.P. propane gas changeover kit is nec-  
essary to convert this unit. Refer to the changeover kit  
installation instruction for the conversion procedure.  
TABLE 18  
Low Heat  
CO %  
Unit  
CO %  
For L.P.  
2
For Nat  
2
I− Condensate pH Range  
G61MP−36B−045  
G61MP−36B−070  
G61MP−48C−090  
G61MP−60C−090  
G61MP−48C−110  
G61MP−60C−110  
G61MP−60D−135  
4.8 − 5.8  
5.3 − 6.3  
5.3 − 6.3  
5.9 − 6.9  
5.9 − 6.9  
6.1 − 7.1  
6.1 − 7.1  
6.7 − 7.7  
The condensate is mildly acidic and can be measured with  
pH indicators. The pH scale is a measurement of acidity  
and alkalinity. The following scale shows the relative pH of  
some common liquids as compared with condensate of  
G61MP units. The concentration of the acidity of all these  
fluids including the condensate is very low and harmless.  
4.8 − 5.8  
5.1 − 6.1  
5.1 − 6.1  
5.3 − 6.3  
5.3 − 6.3  
5.7 − 6.7  
pH RANGE  
0
1
2
3
4
5
Vinegar  
Wine  
Orange Juice  
Tomato Juice  
Increasing  
Acidity  
G61 Condensate  
pH Range  
6
7
Tap Water  
8
Increasing  
Alkalinity  
9
10  
11  
TABLE 19  
Conversion Kit Requirements and Manifold Pressures  
Manifold Pressure at all  
altitudes  
Altitude  
0−4500 ft.  
(0−1372 m)  
4501−7500 ft.  
(1373−2286 m)  
7501−10,000  
(2287−3048 m)  
Model  
Input  
Size  
Low Fire  
High Fire  
Gas  
Required  
Conversion  
Kit  
Required  
Conversion  
Kit  
Required  
Conversion  
Kit  
Pressure  
Switch  
Pressure  
Switch  
Pressure  
Switch  
in.  
w.c.  
in.  
kPa  
kPa  
w.c.  
Nat  
N/A  
No Change  
N/A  
No Change  
59M16  
No Change  
1.7  
0.42  
3.5  
0.87  
−045  
−070  
−090  
−110  
−135  
LPG  
Nat  
59M13  
N/A  
No Change  
No Change  
59M13  
N/A  
No Change  
No Change  
59M14  
59M16  
No Change  
56M06  
4.9  
1.7  
1.22 10.0  
0.42 3.5  
2.5  
0.87  
LPG  
Nat  
59M13  
N/A  
No Change  
No Change  
59M13  
N/A  
No Change  
75M22  
59M14  
59M16  
56M06  
56M21  
4.9  
1.7  
1.22 10.0  
0.42 3.5  
2.5  
0.87  
LPG  
Nat  
59M13  
N/A  
No Change  
No Change  
59M13  
N/A  
75M22  
59M14  
59M16  
56M21  
4.9  
1.7  
1.22 10.0  
0.42 3.5  
2.5  
No Change  
No Change  
0.87  
LPG  
Nat  
59M13  
N/A  
No Change  
No Change  
59M13  
N/A  
No Change  
59M93  
59M14  
59M16  
No Change  
56M93  
4.9  
1.7  
1.22 10.0  
0.42 3.5  
2.5  
0.87  
LPG  
59M13  
No Change  
59M13  
59M93  
59M14  
56M93  
4.9  
1.22 10.0  
2.5  
Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0−4500 feet (0−1370 m).  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
J−Flame Signal  
V−TYPICAL OPERATING CHARACTERISTICS  
A−Blower Operation and Adjustment  
1 − Blower operation is dependent on thermostat control  
system.  
A microamp DC meter is needed to check the flame signal  
on the ignition control.  
Flame (microamp) signal is an electrical current which passes  
from the furnace control through the sensor during unit opera-  
tion. Current passes from the sensor through the flame to  
ground to complete a safety circuit.  
2 − Generally, blower operation is set at thermostat sub-  
base fan switch. With fan switch in ON position, blower  
operates continuously. With fan switch in AUTO position,  
blower cycles with demand or runs continuously while  
heating or cooling circuit cycles.  
To Measure Flame Signal − Ignition Control:  
A
transducer  
(Part  
3 − Depending on the type of indoor thermostat, blower  
and entire unit will be off when the system switch is in  
OFF position.  
TRANSDUCER  
(PART #78H5401)  
#78H5401 available from  
Lennox Repair Parts) is  
required to measure flame  
signal if meter used will not  
read a low micro amp sig-  
nal. ꢀSeeꢀfigureꢀ38. The  
transducer converts mi-  
B−Temperature Rise  
Temperature rise for G61MP units depends on unit input,  
blower speed, blower horsepower and static pressure as  
marked on the unit rating plate. The blower speed must be  
set for unit operation within the range of ꢁTEMP. RISE °F"  
listed on the unit rating plate.  
FIGURE 38  
croamps to volts on a 1:1 conversion. Flame signal for the  
SureLight control should read 0.23 or greater microamps with  
a lockout signal of 0.16 microamps. A digital readout meter  
must be used. The transducer plugs into most meters.  
See figure 39 for proper use of transducer.  
To Measure Temperature Rise:  
1 − Place plenum thermometers in the supply and return air  
plenums. Locate supply air thermometer in the first hori-  
zontal run of the plenum where it will not pick up radiant  
heat from the heat exchanger.  
1 − Set the volt meter to the DC voltage scale. Insert  
transducer into the VDC and common inputs. Ob-  
serve correct polarities. Failure to do so results in  
negative (−) values.  
2 − Set thermostat to highest setting.  
3 − After plenum thermometers have reached their high-  
est and steadiest readings, subtract the two readings.  
The difference should be in the range listed on the unit  
rating plate. If the temperature is too low, decrease  
blower speed. If temperature is too high, first check the  
firing rate. Provided the firing rate is acceptable, in-  
crease blower speed to reduce temperature. To  
change blower speed taps see the Blower Speed Taps  
section in this manual.  
2 − Turn off supply voltage to control.  
3 − Disconnect ignition control flame sensor wire from the  
flame sensor.  
4 − Connect (−) lead of the transducer to flame sensor.  
5 − Connect (+) lead of transducer to the ignition control sen-  
sor wire.  
6 − Turn supply voltage on and close thermostat contacts to  
cycle system.  
C−External Static Pressure  
1 − Tap locations shown in figure 40.  
7 − When main burners are in operation for two minutes, take  
reading. Remember 1 DC volt = 1 DC microamp.  
2 − Punch a 1/4" diameter hole  
STATIC PRESSURE TEST  
in supply and return air ple-  
nums. Insert manometer  
hose flush with inside edge  
of hole or insulation. Seal  
around the hose with perma-  
gum. Connect the zero end  
NOTE−MUST USE DIGITAL METER  
SET DIAL TO MEASURE  
VDC  
of the manometer to the dis-  
FIGURE 40  
charge (supply) side of the system. On ducted sys-  
tems, connect the other end of manometer to the return  
duct as above. For systems with non−ducted returns,  
leave the other end of the manometer open to the at-  
mosphere.  
RED COLLAR  
(+)  
INDICATES  
POSITIVE  
LEAD  
(−)  
(−) TO  
FLAME SENSOR  
3 − With only the blower motor running and the evaporator  
coil dry, observe the manometer reading. Adjust blow-  
er motor speed to deliver the air desired according to  
the job requirements.  
(+) TO  
IGNITION  
CONTROL  
SENSOR  
WIRE  
4 − External static pressure drop must not be more than  
0.8" W.C.  
FIGURE 39  
5 − Seal around the hole when the check is complete.  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Filters  
D−Blower Speed Taps  
Blower speed tap changes are made on the SureLight con-  
trol board. See figure 4. The unused tap must be secured  
on dummy terminals "PARK " on the SureLight board. The  
high heating tap is connected to the "HI HEAT " terminal  
and the low heating / continuous blower tap is connected to  
the "LO HEAT" terminal. The cooling tap is connected to the  
ꢁCOOL" tap.  
To change existing heat tap, turn off power then switch out  
speed tap on "HI HEAT" or ꢁLO HEAT" with tap connected  
to "PARK ". See table 20 for blower motor tap colors for  
each speed.  
Filters should be inspected monthly. Clean or replace the  
filters when necessary to ensure proper furnace opera-  
tion. Replacement filters must be rated for high velocity  
airflow. Table 21 lists recommended filter sizes.  
TABLE 21  
Filter Size  
Furnace  
Cabinet Size  
Side Return  
Bottom Return  
16 X 25 X 1 (1)  
20 X 25 X 1 (1)  
24 X 25 X 1 (1)  
17−1/2"  
21"  
24−1/2"  
16 X 25 X 1 (1)  
16 X 25 X 1 (1)  
16 X 25 X 1 (2)  
Exhaust and air intake pipes  
TABLE 20  
Check the exhaust and air intake pipes and all connections  
for tightness and to make sure there is no blockage.  
Electrical  
1 − Check all wiring for loose connections.  
2 − Check for the correct voltage at the furnace (furnace  
operating).  
3 − Check amp−draw on the blower motor.  
Motor Nameplate__________Actual__________  
Winterizing and Condensate Trap Care  
1 − Turn off power to the unit.  
2 − Have a shallow pan ready to empty condensate water.  
VI−MAINTENANCE  
3 − Remove the drain plug from the condensate trap and  
empty water. Inspect the trap then reinstall the drain  
plug.  
Cleaning Heat Exchanger  
WARNING  
ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD.  
If cleaning the heat exchanger becomes necessary, follow  
the below procedures and refer to figure 1 when disassem-  
bling unit. Use papers or protective covering in front of fur-  
nace while removing heat exchanger assembly.  
Failure to follow safety warnings exactly could result  
in dangerous operation, serious injury, death or  
property damage.  
Improper servicing could result in dangerous opera-  
tion, serious injury, death, or property damage.  
Before servicing, disconnect all electrical power to  
furnace.  
When servicing controls, label all wires prior to dis-  
connecting. Take care to reconnect wires correctly.  
Verify proper operation after servicing.  
IMPORTANT  
Safety glasses and surgical mask should be worn  
when cleaning heat exchanger and or burner  
assembly.  
1 − Turn off electrical and gas supplies to the furnace.  
2 − Remove the upper and lower furnace access panels.  
At the beginning of each heating season, system should be  
checked as follows by a qualified service technician:  
3 − Mark all gas valve wires and disconnect them from  
valve.  
Blower  
4 − Remove gas supply line connected to gas valve. Re-  
move gas valve/manifold assembly.  
Check the blower wheel for debris and clean if necessary.  
The blower motors are prelubricated for extended bearing  
life. No further lubrication is needed.  
5 − Remove sensor wire from sensor. Disconnect 2-pin  
plug from the ignitor.  
6 − Disconnect wires from flame roll−out switches.  
7 − Remove burner box cover and remove four burner box  
screws at the vestibule panel and remove burner box.  
Set burner box assembly aside. G61MP−135 only −  
Remove and discard two additional shipping screws.  
See figure 41.  
WARNING  
The blower access panel must be securely in place  
when the blower and burners are operating. Gas  
fumes, which could contain carbon monoxide, can  
be drawn into living space resulting in personal inju-  
ry or death.  
NOTE − If necessary, clean burners at this time. Follow  
procedures outlined in Burner Cleaning section.  
8 − Loosen three clamps and remove flexible exhaust tee.  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
20 − Back wash heat exchanger with soapy water solution  
or steam. If steam is used it must be below 275°F  
(135°C) .  
G61MP−135 ONLY  
21 − Thoroughly rinse and drain the heat exchanger. Soap  
solutions can be corrosive. Take care to rinse entire  
assembly.  
Remove and discard two shipping screws.  
22 − Reinstall heat exchanger into cabinet making sure that  
the clamshells of the heat exchanger assembly are  
resting on the support located at the rear of the cabi-  
net. Remove the indoor blower to view this area  
through the blower opening.  
23 − Re-secure the supporting screws along the vestibule  
sides and bottom to the cabinet.  
24 − Reinstall cabinet screws on front flange at blower  
deck.  
25 − Reinstall the primary limit on the vestibule panel.  
26 − Route heating component wiring through hole in blow-  
er deck and reinsert strain relief bushing.  
FIGURE 41  
27 − Reinstall electrical junction box.  
9 − Remove 3/8 inch rubber cap from condensate drain  
plug and drain. Replace cap after draining.  
28 − Reinstall the combustion air inducer. Reconnect the  
3−pin plug to the wire harness. Reconnect the two  
wires to the backup secondary limit, if applicable.  
10 − Disconnect condensate drain line from the conden-  
sate trap. Remove condensate trap (it may be neces-  
sary to cut drain pipe). Remove screws that secure  
condensate collars to either side of the furnace and re-  
move collars. Remove drain tubes from cold end  
header collector box.  
29 − Reinstall pressure switches and reconnect pressure  
switch wiring.  
30 − Carefully connect combustion air pressure switch  
hosing from pressure switches to proper stubs on  
cold end header collector box.  
11 − Disconnect condensate drain tubing from flue collar.  
Remove screws that secure both flue collars into  
place. Remove flue collars. It may be necessary to cut  
the exiting exhaust pipe for removal of the fittings.  
31 − Reinstall condensate collars on each side of the fur-  
nace. Reconnect drain tubing to collector box.  
32 − Reinstall condensate trap on same side as exhaust  
pipe. Reconnect condensate drain line to the conden-  
sate trap.  
12 − Mark and disconnect all combustion air pressure tub-  
ing from cold end header collector box.  
33 − Use securing screws to reinstall flue collars to either  
side of the furnace. Reconnect exhaust piping and ex-  
haust drain tubing.  
13 − Mark and remove wires from pressure switches. Re-  
move pressure switches. Keep tubing attached to  
pressure switches.  
34 − Replace flexible exhaust tee on combustion air induc-  
er and flue collars. Secure using three existing hose  
clamps.  
14 − Disconnect the 3-pin plug from the combustion air in-  
ducer. Disconnect the two wires to the backup secon-  
dary limit, if applicable. Remove four screws which se-  
cure combustion air inducer to collector box. Remove  
combustion air inducer assembly. Remove ground  
wire from vest panel.  
35 − Reinstall burner box assembly in vestibule area.  
36 − Reconnect flame roll−out switch wires.  
37 − Reconnect sensor wire and reconnect 2−pin plug from  
ignitor.  
15 − Remove electrical junction box from the side of the fur-  
nace.  
38 − Secure burner box assembly to vestibule panel using  
four existing screws. Make sure burners line up in  
center of burner ports.  
16 − Mark and disconnect any remaining wiring to heating  
compartment components. Disengage strain relief  
bushing and pull wiring and bushing through the hole in  
the blower deck.  
39 − Reinstall gas valve manifold assembly. Reconnect  
gas supply line to gas valve.  
40 − Reinstall burner box cover.  
17 − Remove the primary limit from the vestibule panel.  
41 − Reconnect wires to gas valve.  
18 − Remove two screws from the front cabinet flange at  
the blower deck. Spread cabinet sides slightly to allow  
clearance for removal of heat exchanger.  
42 − Replace the blower compartment access panel.  
43 − Refer to instruction on verifying gas and electrical con-  
nections when re−establishing supplies.  
19 − Remove screws along vestibule sides and bottom  
which secure vestibule panel and heat exchanger as-  
sembly to cabinet. Remove two screws from blower  
rail which secure bottom heat exchanger flange. Re-  
move heat exchanger from furnace cabinet.  
44 − Follow lighting instructions to light and operate fur-  
nace for 5 minutes to ensure that heat exchanger is  
clean and dry and that furnace is operating properly.  
45 − Replace heating compartment access panel.  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Cleaning the Burner Assembly  
1 − Turn off electrical and gas power supplies to furnace.  
Remove upper and lower furnace access panels.  
7 − Reconnect the sensor wire and reconnect the 2−pin  
plug to the ignitor wiring harness.  
8 − Reinstall the burner box assembly using the existing  
four screws. Make sure that the burners line up in the  
center of the burner ports.  
2 − Mark all gas valve wires and disconnect them from the  
valve.  
3 − Disconnect the gas supply line from the gas valve. Re-  
move gas valve/manifold assembly.  
9 − Reinstall the gas valve manifold assembly. Reconnect  
the gas supply line to the gas valve. Reinstall the burn-  
er box cover.  
4 − Mark and disconnect sensor wire from the sensor. Dis-  
connect 2-pin plug from the ignitor at the burner box.  
10 − Reconnect the gas valve wires to the gas valve.  
11 − Replace the blower compartment access panel.  
5 − Remove burner box cover and remove four screws  
which secure burner box assembly to vest panel. Re-  
move burner box from the unit. G61MP−135 only − Re-  
move and discard two additional shipping screws.  
See figure 41.  
12 − Refer to instruction on verifying gas and electrical con-  
nections when re−establishing supplies.  
13 − Follow lighting instructions to light and operate fur-  
nace for 5 minutes to ensure that heat exchanger is  
clean and dry and that furnace is operating properly.  
6 − Use the soft brush attachment on a vacuum cleaner to  
gently clean the face of the burners. Visually inspect  
the inside of the burners and crossovers for any block-  
age caused by foreign matter. Remove any blockage.  
14 − Replace heating compartment access panel.  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VII− Wiring and Sequence of Operation  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single−Stage Thermostat, Two Stage Heat. Jumper  
E20 set at ꢁSINGLE"  
Sequence of Operation  
Sequence depends on type thermostat used. G61MP  
units are applicable for single stage or two stage ther-  
mostats. Both type thermostats are described below.  
Thermostat jumper E20 dictates which mode unit will  
operate in. See flow chart for more sequence detail.  
SureLight Control Self Check  
1− SureLight control energizes combustion air inducer B6  
on low heat speed. Combustion air inducer runs until  
S128 low heat prove switch contacts close (switch  
must close within 2 1/2 minutes or control goes into  
Watchguard Pressure Switch mode High heat prove  
switch S102 may also close). A 15 second pre−purge  
follows once S128 closes.  
When there is a call for heat, the SureLight integrated con-  
trol runs a self check. The control checks for S10 primary  
limit, S21 secondary limit (s) and S47 rollout switch nor-  
mally closed contacts. The control also checks for S102  
high heat and S128 low heat prove switch normally open  
contacts. Once self check is complete and all safety  
switches are operational, heat call can continue.  
2− SureLight control begins 20 second ignitor warm up  
period.  
3− Gas valve opens on first stage for a 4 second trial for  
ignition. Ignitor stays energized during the trial or until  
flame sensed.  
4− Flame is sensed, gas valve remains on first stage heat,  
ignitor de−energizes.  
Two−Stage Thermostat, Two Stage Heat. Jumper E20  
set at ꢀTWO".  
5− After 45 second delay, indoor blower B3 is energized  
on low heat speed.  
1− SureLight control energizes combustion air inducer B6  
on low heat speed. Combustion air inducer runs until  
S128 low heat prove switch contacts close (switch  
must close within 2 1/2 minutes or control goes into  
Watchguard Pressure Switch mode. High heat prove  
switch S102 may also close). A 15 second pre−purge  
follows once S128 closes.  
6− A 10 minute (factory set) or 15 minute (field set) second  
stage heat delay period begins.  
7− After the delay the combustion air inducer ramps up to  
high heat speed.  
8− S102 high heat prove switch closes and the gas valve  
energizes second stage heat.  
2− SureLight control begins 20 second ignitor warm up  
period.  
9− B3 indoor blower energizes on high heat speed.  
3− Gas valve opens on first stage for a 4 second trial for  
ignition. Ignitor stays energized during the trial or until  
flame sensed.  
4− Flame is sensed, gas valve remains on first stage heat,  
ignitor de−energizes.  
5− After 45 second delay, indoor blower B3 is energized  
on low heat speed.  
The furnace will stay in this mode until first stage de-  
mand is satified OR a second stage heat demand is  
initiated.  
6− Second stage heat demand initiated. A 30 second sec-  
ond stage recognition period begins.  
7− The combustion air inducer ramps up to high heat  
speed.  
8− S102 high heat prove switch closes and the gas valve  
energizes second stage heat.  
9− B3 indoor blower energizes on high heat speed.  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING SEQUENCE OF OPERATION  
NORMAL AND ABNORMAL HEATING MODE  
GAS VALVE OFF. COMBUSTION AIR INDUCER  
POWER ON  
OFF. INDOOR BLOWER OFF. CHECK FOR  
BROKEN IGNITOR OR OPEN IGNITER CIRCUIT.  
DS1 AND DS2 ALTERNATING FAST FLASH.  
NO  
CONTROL SELF−CHECK OKAY?  
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF. (RESET CONTROL BY  
TURNING MAIN POWER OFF.) DS1 ON, DS2 ON  
POLARITY REVERSED.  
DS1 −− FAST FLASH  
DS2 −− SLOW FLASH  
NO  
POLARITY OKAY?  
YES  
NO  
IS THERE A  
PROPER GROUND?  
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.  
DS1 AND DS2 ALTERNATING FAST FLASH.  
YES  
NO  
IS VOLTAGE  
ABOVE 75 VOLTS?  
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS.  
DS1 AND DS2 ALTERNATING FAST FLASH.  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.  
INDOOR BLOWER ON HEATING SPEED.  
DS1 SLOW FLASH, DS2 OFF.  
NO  
BURNER OFF?  
(CONTINUOUS FLAME CHECK)  
YES  
A
NORMAL OPERATION:  
DS 1 −− SIMULTANEOUS SLOW FLASH  
DS 2 −− SIMULTANEOUS SLOW FLASH  
COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER ON. HAS PRIMARY OR  
YES  
SECONDARY LIMIT RESET WITHIN 3 MINUTES?  
DS1 SLOW FLASH, DS2 ON.  
B
NO  
THERMOSTAT CALLS FOR HEAT:  
DS 1 −− SIMULTANEOUS FAST FLASH  
DS 2 −− SIMULTANEOUS FAST FLASH  
NO  
NO  
60−MINUTE LIMIT WATCHGUARD MODE.  
GAS VALVE OFF, COMBUSTION AIR INDUCER  
OFF, INDOOR BLOWER OFF WITH DELAY.  
DS1 AND DS2 ALTERNATING SLOW FLASH.  
YES  
PRIMARY AND SECONDARY LIMIT  
SWITCHES CLOSED?  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.  
NO  
ROLLOUT SWITCH CLOSED?  
NO  
HAS MANUAL ROLLOUT SWITCH(ES) BEEN  
RESET (CLOSED) WITHIN 3 MINUTES?  
DS1 SLOW FLASH, DS2 ON.  
YES  
YES  
FIRST (LOW) STAGE PRESSURE  
SWITCHES OPEN?  
NO  
NO  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF. CONTROL REMAINS UNTIL  
PRESSURE SWITCH IS DETECTED OPEN.  
DS1 OFF, DS2 SLOW FLASH.  
SECOND (HIGH) STAGE PRESSURE  
SWITCHES OPEN?  
GAS VALVE OFF.  
COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF.  
TWO−STAGE OR SINGLE−STAGE THERMOSTAT  
CALL FOR HEAT  
CONTROL WILL NOT ATTEMPT SECOND−STAGE  
OPERATION DURING THIS HEAT DEMAND.  
FIRST−STAGE OPERATION WILL BE ATTEMPTED.  
DS1 OFF, DS2 FAST FLASH.  
COMBUSTION AIR INDUCER ON LOW SPEED.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH  
CONTINUED ON NEXT PAGE  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING SEQUENCE OF OPERATION  
CONTINUED  
THERMOSTAT CALLS FOR HEAT  
DS1 AND DS2 SIMULTANEOUS FAST FLASH  
(Refer to box A on previous page)  
NO  
FIRST−STAGE (LOW FIRE) PRESSURE  
SWITCH CLOSED WITHIN 2.5 MINUTES?  
GAS VALVE OFF. COMBUSTION AIR INDUCER  
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY  
AFTER 5−MINUTE WAIT PERIOD.  
YES  
DS1 OFF, DS2 SLOW FLASH.  
15−SECOND COMBUSTION AIR INDUCER  
PRE−PURGE INITIATED BY CLOSED FIRST−STAGE  
PRESSURE SWITCH (or 15 SECOND  
INTER−PURGE PERIOD.)  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
IGNITOR WARM−UP (20 SECONDS)  
DS1 AND DS2 SIMULTANEOUS FAST FLASH  
COMBUSTION AIR INDUCER OFF, IGNITER OFF.  
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS.  
DS1 AND DS2 ALTERNATING FAST FLASH.  
NO  
NO  
NO  
IS VOLTAGE ABOVE 75 VOLTS?  
YES  
COMBUSTION AIR INDUCER OFF, IGNITER OFF.  
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.  
DS1 AND DS2 ALTERNATING FAST FLASH.  
IS THERE A PROPER GROUND?  
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.  
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED  
OR RECONNECTED.  
IS IGNITOR INTACT AND CONNECTED?  
DS1 AND DS2 ALTERNATING FAST FLASH.  
YES  
AT END OF IGNITOR 20 SECOND WARM UP  
PERIOD, 4−SECOND TRIAL FOR IGNITION.  
GAS VALVE OPENS, IGNITOR ENERGIZED DURING  
4−SECOND TRIAL UNTIL FLAME SENSED.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
YES  
4−SECOND FLAME STABILIZATION PERIOD.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
GAS VALVE OFF. COMBUSTION AIR  
INDUCER ON. INDOOR BLOWER OFF.  
DS1 SLOW FLASH, DS2 FAST FLASHN.  
HAS CONTROL FAILED TO SENSE  
FLAME FOR FIVE CONSECUTIVE TRIES  
DURING A SINGLE HEAT DEMAND?  
FLAME RECTIFICATION CURRENT CHECK  
CAN FLAME BE PROVEN WITHIN 4  
SECONDS AFTER GAS VALVE OPENS?  
(u0.16 microamps)  
NO  
NO  
YES  
WATCHGUARD MODE. GAS VALVE OFF,  
COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER OFF.  
YES  
DS1 AND DS2 ALTERNATING SLOW FLASH.  
IS 60−MINUTE RESET PERIOD COMPLETE?  
YES  
NO  
HAS CONTROL RESET IGNITION SEQUENCE  
FOUR (4) TIMES?  
DS1 SLOW FLASH, DS2 FAST FLASH.  
FLAME PRESENT?  
NO  
YES  
CONTINUED ON NEXT PAGE  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING SEQUENCE OF OPERATION  
CONTINUED  
THERMOSTAT CALLS FOR HEAT.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
SEE BOX A.  
FLAME SIGNAL ABOVE  
(u0.22 microamps)  
NO  
LOW FLAME SIGNAL  
(Does not affect control operation)  
DS1 SLOW FLASH, DS2 FAST FLASH.  
YES  
YES  
SINGLE−STAGE THERMOSTAT MODE  
(E20 SET AT ꢁSINGLE")  
TWO STAGE THERMOSTAT MODE  
(E20 SET AT ꢁTWO")  
YES  
YES  
START SECOND−STAGE RECOGNITION  
ON DELAY (10 OR 15 MINUTES).  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
45−SECOND INDOOR BLOWER ON DELAY BEGINS.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
YES  
YES  
FIRST−STAGE (LOW FIRE)  
PRESSURE SWITCHES CLOSED?  
PRIMARY, SECONDARY, ROLLOUT AND BACKUP  
SECONDARY LIMIT SWITCHES CLOSED?  
YES  
NO  
NO  
NO  
C
FIRST−STAGE HEAT DEMAND SATISFIED?  
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.  
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,  
INDOOR BLOWER ON. DS1 SLOW FLASH, DS2 ON.  
YES  
GAS VALVE OFF, COMBUSTION AIR INDUCER  
OFF FOLLOWING POST PURGE.  
INDOOR BLOWER OFF WITH DELAY  
HAS PRIMARY, SECONDARY, ROLLOUT OR BACKUP  
SECONDARY LIMIT SWITCH CLOSED WITHIN 3 MINUTES?  
(Indoor blower on low speed during 3−minute period)  
YES  
DS1 AND DS2 SIMULTANEOUS SLOW FLASH  
NO  
SECOND−STAGE HEAT DEMAND.  
SECOND−STAGE HEAT DEMAND REQUIRED?  
DS1 AND DS2 SIMUTANEOUS SLOW FLASH.  
LIMIT SWITCH WATCHGUARD MODE.  
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,  
YES  
INDOOR BLOWER OFF WITH DELAY.  
DS1 AND DS2 ALTERNATING SLOW FLASH.  
IS 60−MINUTE RESET PERIOD COMPLETE?  
YES  
SECOND STAGE PRESSURE SWITCHES CLOSED?  
ABNORMAL FLASH CODE.  
NOTE − IF SECOND−STAGE PRESSURE SWITCHES  
WERE ORIGINALLY FOUND CLOSED,  
ABNORMAL CODE WILL FLASH.  
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.  
INDOOR BLOWER OFF AFTER DELAY.  
DS1 OFF, DS 2 SLOW FLASH.  
YES  
NO  
SECOND−STAGE PRESSURE SWITCHES CLOSED  
AT BEGINNING OF HEAT DEMAND?  
DS1 OFF, DS2 SLOW FLASH.  
NO  
SECOND−STAGE 30−SECOND DELAY ON BEGINS.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH  
YES  
SECOND STAGE HEAT DEMAND  
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.  
SECOND−STRAGE COMBUSTION AIR INDUCER  
ON. SECOND−STAGE GAS VALVE ON. HIGH  
HEAT INDOOR BLOWER SPEED ON.  
NO  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
RETURNS TO FIRST−STAGE HEAT MODE WHICH  
CONTINUES UNTIL SECOND−STAGE PRESSURE  
SWITCHES CAN BE PROVEN or HEAT DEMAND IS  
SATISFIED. FIVE (5) MINUTE WAIT PERIOD  
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS  
MADE FOR SECOND−STAGE HEAT?  
YES  
SECOND−STAGE PRESSURE SWITCHES CLOSED  
IN LESS THAN TEN (10) SECONDS?  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
NO  
YES  
YES  
NORMAL OPERATION.  
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.  
CONTINUED ON NEXT PAGE  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING SEQUENCE OF OPERATION  
CONTINUED  
SEE BOX A  
NORMAL OPERATION  
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.  
SEE BOX B  
THERMOSTAT CALLS FOR HEAT  
DS 1 AND DS 2 SIMULTANEOUS FAST FLASH  
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.  
INDOOR BLOWER ON.  
DS1 SLOW FLASH, DS2 ON.  
YES  
ARE PRIMARY, SECONDARY, ROLLOUT AND  
BACKUP SECONDARY LIMIT SWITCHES CLOSED?  
NO  
HAS PRIMARY, SECONDARY, ROLLOUT OR BACKUP  
SECONDARY LIMIT SWITCH CLOSED WITHIN 3 MINUTES?  
YES  
NO  
LIMIT SWITCH WATCHGUARD MODE. GAS VALVE  
OFF. COMBUSTION AIR INDUCER OFF. INDOOR  
BLOWER OFF WITH DELAY. IS 60−MINUTE RESET  
PERIOD COMPLETE? DS SLOW FLASH, DS2 ON.  
YES  
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF  
AFTER 15 SECOND POST PURGE, INDOOR  
BLOWER OFF AFTER DELAY.  
YES  
NO  
FIRST−STAGE (LOW FIRE) HEAT  
PRESSURE SWITCHES CLOSED?  
DS1 OFF, DS2 FAST FLASH.  
RETURN TO HEAT DEMAND?  
RETURN TO FIRST−STAGE HEAT MODE.  
FIRST−STAGE CONTINUES UNTIL SECOND−  
STAGE PRESSURE SWITCHES CAN BE PROV-  
EN or HEAT DEMAND IS SATISFIED. A FIVE (5)  
MINUTE WAIT PERIOD IS INITIATED BEFORE  
RETRY. WERE 5 ATTEMPTS MADE FOR  
SECOND−STAGE HEAT?  
SECOND−STAGE (HIGH FIRE) HEAT  
PRESSURE SWITCHES CLOSED?  
YES  
NO  
YES  
NO  
HEAT DEMAND SATISFIED?  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
SEE BOX C  
FIRST−STAGE HEAT DEMAND SATISFIED?  
YES  
YES  
SINGLE−STAGE THERMOSTAT MODE  
(E20 SET AT ꢁSINGLE")  
TWO STAGE THERMOSTAT MODE?  
(E20 SET AT ꢁTWO")  
YES  
YES  
SECOND STAGE HEAT  
FIRST AND SECOND STAGE HEAT  
DEMAND SATISFIED SIMULTANEOUSLY.  
DS1 & DS2 SIMULTANEOUS FAST FLASH.  
HEAT DEMAND SATISFIED?  
DS1 AND DS2  
SIMULTANEOUS FAST FLASH.  
DEMAND SASTISFIED?  
DS1 AND DS2  
SIMULTANEOUS FAST FLASH.  
NO  
YES  
YES  
YES  
GAS VALVE OFF, COMBUSTION AIR  
INDUCER OFF AFTER POST PURGE  
PERIOD, INDOOR BLOWER OFF AF-  
TER SELECTED DELAY.  
GAS VALVE, COMBUSTION AIR INDUCER  
AND INDOOR BLOWER RETURN TO FIRST−  
STAGE OPERATION.  
DS1 AND DS2 SIMULTANEOUS FAST FLASH.  
DS1 AND DS2  
SIMULTANEOUS FAST FLASH  
FIRST STAGE HEAT DEMAND SATISFIED?  
YES  
GAS VALVE OFF. COMBUSTION AIR INDUCER  
OFF AFTER 5−SECOND POST−PURGE PERIOD.  
INDOOR BLOWER OFF. DELAY INITIATED.  
DS1 & DS2 SIMULTANEOUS FAST FLASH.  
DEMAND FOR HEAT SATISFIED.  
POWER ON STAND BY.  
DS1 AND DS2  
SIMULTANEOUS SLOW FLASH  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING SEQUENCE OF OPERATION  
POWER ON  
YES  
IS POLARITY REVERSED?  
SIGNAL POLARITY REVERSED.  
DS1 FAST FLASH, DS2 SLOW FLASH.  
NO  
SIGNAL IMPROPER  
GROUND AT DS.  
SIGNAL HOLDS  
UNTIL UNIT IS  
PROPERLY  
NO  
NO  
YES  
IS THERE  
PROPER GROUND?  
IS VOLTAGE  
ABOVE 75 VOLTS?  
LOW VOLTAGE SIGNAL AT DS HOLDS  
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.  
YES  
GROUNDED.  
THERMOSTAT CALLS FOR FIRST−STAGE COOL.  
COMPRESSOR AND CONDENSER FAN  
ENERGIZED.  
INDOOR BLOWER ENERGIZED ON FIRST STAGE  
COOL SPEED AFTER 2 SECOND DELAY.  
YES  
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.  
INDOOR BLOWER DE−ENERGIZED.  
FIRST−STAGE DEMAND FOR COOL SATISFIED?  
NO  
THERMOSTAT CALLS FOR SECOND−STAGE COOL.  
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.  
SECOND−STAGE DEMAND FOR COOL SATISFIED?  
YES  
UNIT RETURNS TO FIRST STAGE COOL  
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION  
MANUAL FAN SELECTION MADE AT THERMOSTAT.  
AFTER 2 SECOND DELAY, INDOOR BLOWER IS  
ENERGIZED ON CONTINUOUS FAN SPEED  
(LOW HEAT / LOW COOL).  
YES  
YES  
THERMOSTAT CALLS FOR FIRST STAGE COOL.  
YES  
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.  
YES  
COMPRESSOR IS ENERGIZED AND INDOOR  
BLOWER CONTINUES TO OPERATE IN LOW  
COOL SPEED.  
BURNERS IGNITE AND INDOOR BLOWER  
CONTINUES TO OPERATE IN CONTINUOUS  
LOW (LOW HEAT / LOW COOL) MODE.  
FIRST−STAGE COOL DEMAND SATISFIED?  
FIRST−STAGE HEAT DEMAND SATISFIED.  
NO  
YES  
YES  
NO  
SECOND STAGE COOL DEMAND  
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.  
YES  
INDOOR BLOWER RAMPS TO SECOND  
STAGE COOL SPEED  
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED  
AFTER 30−SECOND RECOGNITION PERIOD.  
YES  
SECOND STAGE COOL DEMAND SATISFIED?  
YES  
SECOND−STAGE HEAT DEMAND SATISFIED.  
YES  
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE  
COOL SPEED.  
INDOOR BLOWER RAMPS DOWN TO LOW  
HEAT SPEED.  
NOTE − Continuous low speed fan and cooling low  
speed are equal to the low heat fan speed.  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIII− Field Wiring Applications and Jumper Settings  
Field Wiring Applications  
Thermostat  
1 Heat / 1 Cool  
Wiring Connections  
W915  
E20  
Y1 to Y2  
Leave Installed  
SINGLE  
SINGLE  
TWO  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
NOTE − Use dip switch 3  
to set second−stage heat  
ON delay.  
ON−10 minutes. OFF−15  
minutes.  
HSXB15  
(LSOM)  
1 Heat / 2 Cool  
Clip  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
NOTE − Use dip switch 3  
to set second−stage heat  
ON delay.  
ON−10 minutes. OFF−15  
minutes.  
HSXA19  
(LSOM)  
2 Heat / 2 Cool  
Clip  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
HSXA19  
(LSOM)  
2 Heat / 1 Cool  
TWO  
Leave Installed  
S1  
T’STAT  
CONTROL  
TERM. STRIP  
OUTDOOR  
UNIT  
HSXB15  
(LSOM)  
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Field Wiring Applications (Continued)  
Thermostat  
Wiring Connections  
W915  
E20  
Y1 to Y2  
Leave Installed  
FM21 Heat Pump / 1  
Cool  
SINGLE  
CONTROL  
TERM. STRIP  
FM21  
*Disconnect existing  
furnace transformer and re-  
place with 75VA, 24V trans-  
former if defrost option to be  
used.  
75VA, 24V  
TRANSFORMER*  
NOTE − Wiring connections to  
outdoor unit and thermostat  
made at FM21 control board  
per FM21 instructions.  
NOTE −  
Cut Y1/Y2 jumper  
for two−stage  
cooling.  
Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IX−SURELIGHT® CONTROL TROUBLESHOOTING CHART  
UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT  
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE  
Condition  
1.1  
Possible Cause  
1.1.1  
Corrective Action / Comments  
ACTION 1 − Check 120V main voltage.  
Determine cause of main power failure.  
Both diagnostic lights fail to light up. Main voltage 120V not supplied to unit.  
1.1.2  
ACTION 1 − Check for correct wiring of 120V to  
power make up box and transformer.  
ACTION 2 − Check 24V wiring to control board.  
LED#1−Off  
LED#2−Off  
Miswiring of furnace or improper con-  
nections.  
1.1.3  
ACTION 1 − Replace fuse.  
ACTION 2 − If fuse still blows, check for short.  
Blown fuse  
ACTION 1 − Check that door switch is activated  
when door is closed.  
ACTION 2Check wire connections to switch, re-  
place loose connectors.  
ACTION 3 − Check continuity of switch in closed  
position. Replace if defective.  
1.1.4  
Door interlock switch failure.  
1.1.5  
Transformer Failure.  
1.1.6  
ACTION 1 − Check that transformer output is  
24V. Replace if defective.  
ACTION 1 − If all the above items have been  
checked, replace board.  
Failed control board.  
ACTION 1 − Manually reset the roll−out switch  
by pushing the top button.  
1.2  
1.2.1  
ACTION 2 − Determine the cause of the roll−out  
switch activation before leaving furnace.  
Diagnostic lights flash the roll−out  
Roll−out switch open.  
code.  
ACTION 1 − Check continuity across roll−out  
switch. Replace roll−out switch if switch is reset  
but does not have continuity.  
1.2.2  
Roll−out switch failure.  
LED#1−On,  
1.2.3  
LED#2−Slow Flash  
ACTION 1 − Check wiring connections to switch.  
Miswiring or improper connections at  
roll−out switch.  
ACTION 1 − Check 9−pin connector for proper  
connection to control board.  
1.2.4  
ACTION 2 − Check continuity of the multi plug  
pin.  
9 pin connector failure  
1.3  
− On initial power−up the comb. air in-  
ducer does not energize.  
− Diagnostic lights flash the reverse  
polarity code.  
ACTION 1 − Check the 120V has line and neutral  
correctly input into control.  
ACTION 2 − Reverse the line and neutral at the  
120V field connection.  
1.3.1  
120V main power polarity reversed.  
LED#1−Fast Flash,  
LED#2−Slow Flash.  
1.4  
1.4.1  
ACTION 1 − Check for 120V to combustion air  
inducer. If no power, check wire and connec-  
tions.  
− On initial power up the combustion  
air inducer does not energize.  
− Diagnostic lights flash normal power  
on operation.  
Open combustion air inducer motor  
circuit.  
1.4.2  
ACTION 1 − If power is present at blower, replace  
blower.  
LED#1−Slow Flash  
LED#2−Slow Flash  
Failed combustion air inducer motor.  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE  
Condition  
1.5  
Possible Cause  
Corrective Action / Comments  
ACTION 1 − Check that the unit is properly  
ground.  
1.5.1  
Diagnostic lights flash the improper  
main ground.  
ACTION 2 − Install a proper main ground to the  
unit  
Improper ground to the unit.  
1.5.2  
ACTION 1 − Check 6−pin connector for proper  
installation. Correctly insert connector into con-  
trol.  
6−Pin connector is improperly  
attached to the circuit board.  
LED#1−Alternating Fast Flash  
LED#2−Alternating Fast Flash  
ACTION 1 − Check that the line voltage is above  
75V. Determine cause of voltage drop and supply  
correct voltage to the control.  
1.5.3  
Line voltage is below 75V.  
ACTION 1 − Check for correct wiring and loose  
connections in the ignitor circuit. Check mult−plug  
connections for correct installation.  
1.5.4  
Open ignitor circuit.  
ACTION 1 − Unplug ignitor and read resistance  
across ignitor. If resistance does not read be-  
tween 10.9 and 19.7 ohms, replace the ignitor.  
1.5.5  
Broken or failed ignitor.  
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES NOT  
ENERGIZE  
Condition  
2.1  
Possible Cause  
Corrective Action / Comments  
ACTION 1 − Check continuity across switch(es).  
Switches reset automatically upon cool down.  
ACTION 2Check for restrictions on blower inlet  
air (including filter) and outlet air. Determine  
cause for limit activation before placing unit back  
in operation.  
Unit operates with a cooling or contin-  
uous fan demand.  
Combustion air inducer will not start  
with a Heating demand.  
2.1.1  
Primary, secondary or backup secon-  
dary (if equipped ) limit open.  
− Diagnostic lights flash the limit failure  
mode.  
2.1.2  
ACTION 1 − Check for correct wiring and loose  
connections. Correct wiring and/or replace any  
loose connections.  
Miswiring of furnace or improper  
connections at limit switch(es).  
LED#1−Slow Flash,  
LED#2−On  
2.2  
2.2.1  
− Unit operates with a cooling and con-  
tinuous fan demand.  
− Combustion air inducer will not start  
with a Heating demand.  
ACTION 1 − Check for correct wiring and loose  
connections. Correct wiring and/or replace any  
loose connections.  
Miswiring of furnace or improper  
connections to combustion air  
inducer.  
Diagnostic lights flash the pressure  
switch failure code.  
ACTION 1 − Check that the prove switch is open  
without the combustion air inducer operating. Re-  
place if defective.  
2.2.2  
LED#1−Off,  
LED#2−Slow Flash  
Prove switch stuck closed.  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR INDUCER DOES  
NOT ENERGIZE (CONT.).  
Condition  
2.3  
Possible Cause  
Corrective Action/Comments  
2.3.1  
− Unit operates with a cooling and con-  
tinuous fan demand.  
Combustion air inducer will not start  
with a Heating demand.  
ACTION 1 − Check for correct wiring and loose  
connections. Correct wiring and/or replace any  
loose connections.  
Miswiring of furnace or improper  
connections to combustion air induc-  
er.  
Diagnostic lights flash the pressure  
switch failure code 2.5 minutes after  
heating demand.  
ACTION 1 − If there is 120V to combustion air in-  
ducer and it does not operate, replace combus-  
tion air inducer.  
2.3.2  
Combustion air inducer failure.  
LED#1−Off,  
LED#2−Slow Flash  
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR INDUCER  
ENERGIZES, IGNITOR IS NOT ENERGIZED.  
Condition  
3.1  
Possible Cause  
3.1.1  
Corrective Action/Comments  
ACTION 1Check that the prove switch lines are  
correctly routed. Correctly route pressure switch  
lines.  
Unit operates with a cooling and  
continuous fan demand.  
Combustion air inducer energizes  
with a heating demand.  
− Diagnostic lights flash the pressure  
switch failure code 2.5 minutes after  
heating demand.  
Prove switch does not close due to  
incorrect routing of the pressure  
switch lines.  
3.1.2  
ACTION 1 − Remove any obstructions from the  
the pressure lines and/or taps.  
Prove switch does not close due to  
obstructions in the pressure lines.  
3.1.3  
ACTION 1 − Check prove switch lines for leaks.  
Replace any broken lines.  
Prove switch lines damaged  
3.1.4  
LED#1−Off  
LED#2−Slow Flash  
ACTION 1Check prove switch lines for conden-  
sate. Remove condensate from lines.  
Condensate in prove switch line.  
ACTION 1 − Check the differential pressure  
across the prove switch. This pressure should  
exceed the set point listed on the switch.  
ACTION 2 − Check for restricted inlet vent. Re-  
move all blockage.  
3.1.5  
Prove switch does not close due to a  
low differential pressure across the  
prove switch.  
ACTION 3 − Check for proper vent sizing and  
run length.  
3.1.6  
ACTION 1 − Check that the proper prove switch  
is installed in the unit. Replace prove switch if  
necessary.  
Wrong prove switch installed in the  
unit, or prove switch is out of  
calibration.  
3.1.7  
ACTION 1 − Check for correct wiring and loose  
connections. Correct wiring and/or replace any  
loose connections.  
Miswiring of furnace or improper  
connections at prove switch.  
ACTION 1If all the above modes of failure have  
been checked, the prove switch may have failed.  
Replace prove switch and determine if unit will  
operate.  
3.1.8  
Prove switch failure.  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER  
ENERGIZES, IGNITOR IS ENERGIZED.  
Condition  
4.1  
Possible Cause  
Corrective Action/Comments  
ACTION 1Check line pressure at the gas valve.  
Pressure should not exceed 13" WC for both nat-  
ural and propane. Line pressure should read a  
minimum 4.5" WC for natural and 8.0"WC for pro-  
pane.  
4.1.1  
− Unit operates with a cooling and  
continuous fan demand.  
− Combustion air inducer energizes  
with Heating demand.  
Check that gas is being supplied to  
the unit.  
4.1.2  
ACTION 1 − Check for correct wiring and loose  
connections. Correct wiring and/or replace any  
loose connections.  
Miswiring of gas valve or loose-  
connections at multi−pin control amp  
plugs or valve.  
Ignitor is energized but unit fails to  
light.  
ACTION 1Check that 24V is supplied to the gas  
valve approximately 35 seconds after heat de-  
mand is initiated.  
ACTION 2 − Replace the valve if 24V is supplied  
but valve does not open.  
4.1.3  
LED#1−Alternating Slow Flash  
LED#2−Alternating Slow Flash  
Defective gas valve or ignition  
control.  
ACTION 3 − Replace the control board if 24V is  
not supplied to valve.  
PROBLEM 5: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN  
PREMATURELY  
Condition  
Possible Cause  
5.1.1  
Corrective Action/Comments  
ACTION 1 − Check for restricted intake and ex-  
haust vent. Remove all blockage.  
Low pressure differential at the prove  
switch.  
ACTION 2: Check for proper vent sizing. See  
installation instructions.  
5.1  
5.1.2  
− Burners fire with a heating demand.  
− Burners light but unit shuts off prior  
to satisfying T−stat demand.  
− Diagnostic lights flash the pressure  
switch code.  
ACTION 1 − Check vent termination kit installed.  
See Placement and Installation section.  
Wrong concentric vent kit used for  
terminating the unit.  
ACTION 1 − Check condensate line for proper  
vent slope, and any blockage. Condensate  
should flow freely during operation of furnace.  
Repair or replace any improperly installed con-  
densate lines.  
5.1.3  
Condensate drain line is not draining  
properly.  
LED#1−Off  
LED#2−Slow Flash  
ACTION 1 − Check for restricted intake and ex-  
haust. Remove all blockage.  
5.1.4  
Low pressure differential at the prove  
switch.  
ACTION 2: Check for proper vent sizing. See  
installation instructions.  
5.2  
5.2.1  
ACTION 1 − Check that sensor is properly lo-  
cated and that the sense wire is properly at-  
tached to both the sensor and the control.  
− Combustion air inducer energizes  
with a heating demand.  
Sensor or sense wire is improperly  
installed.  
− Burners light but fail to stay lit.  
− After 5 tries the control diagnostics  
flash the watchguard burners failed to  
ignite code.  
ACTION 1 − Check for a broken sensor.  
ACTION 2 − Test continuity across the sense  
wire. If wire or sensor are damaged replace the  
component.  
5.2.2  
Sensor or sense wire is broken.  
ACTION 1 − Check for resistance between the  
sensor rod and the unit ground.  
5.2.3  
ACTION 2 − Check for resistance between the  
sensor wire and the unit ground.  
ACTION 3 − Correct any shorts found in circuit.  
Sensor or sensor wire is grounded to  
the unit.  
LED#1−Alternating Slow Flash  
LED#2−Alternating Slow Flash  
ACTION 1 − Check the microamp signal from  
the burner flame. If the microamp signal is be-  
low normal, check the sense rod for proper  
location or contamination.  
ACTION 2 − Replace, clean, or relocate flame  
sense rod. If rod is to be cleaned, use steel  
wool or replace sensor. DO NOT CLEAN ROD  
WITH SAND PAPER. SAND PAPER WILL  
CONTRIBUTE TO THE CONTAMINATION  
PROBLEM. NOTE: Do not attempt to bend  
sense rod.  
5.2.4  
Control does not sense flame.  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROBLEM 5: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN  
PREMATURELY (CONT.)  
Condition  
5.3  
Possible Cause  
Corrective Action/Comments  
ACTION 1 − Check that the manifold pressure  
matches value listed on nameplate. See installa-  
tion instructions for proper procedure.  
ACTION 2 − Verify that the installed orifice size  
match the size listed on the nameplate or installa-  
tion instructions.  
− Combustion air inducer energizes  
with a heating demand.  
− Burners light.  
− Roll−out switch trips during the  
heating demand.  
5.3.1  
Unit is firing above 100% of the  
nameplate input.  
ACTION 3 − Check gas valve sensing hose to in-  
sure no leaks are present.  
ACTION 4 − Check the input rate to verify rate  
matches value listed on nameplate.  
− Diagnostic lights flash roll−out fail-  
ure.  
ACTION 1 − Tighten orifice until leak is sealed.  
NOTE: Be careful not to strip orifice threads.  
ACTION 2 − Check for gas leakage at the  
threaded orifice connection. Use approved meth-  
od for leak detection (see unit instructions).  
5.3.2  
Gas orifices leak at the manifold  
connection.  
LED#1−On  
LED#2−Slow Flash  
5.3.3  
ACTION 1 − Check for air leakage at all joints in  
the heat exchanger assembly. Condition will  
cause high CO2 with high CO.  
ACTION 2 − Seal leakage if possible, replace  
heat exchanger if necessary, tag and return heat  
exchanger to proper Lennox personnel.  
Air leakage at the connections  
between the primary heat exchanger,  
secondary heat exchanger, and  
combustion air blower.  
5.3.4  
ACTION 1 − Check for sooting deposits or other  
restrictions in the heat exchanger assembly.  
Clean assembly as outlined in instruction manu-  
al.  
Insufficient flow through the heat  
exchanger caused by a sooted or  
restricted heat exchanger.  
ACTION 2 − Check for proper combustion.  
5.3.5  
ACTION 1 − Check that the burners are firing into  
the center of the heat exchanger openings. Cor-  
rect the location of the burners if necessary.  
Burners are not properly located in  
the burner box.  
5.4  
5.4.1  
ACTION 1 − Check for proper flow of exhaust  
gases away from intake vent. Remove any ob-  
stacles in front of the intake and exhaust vent  
which would cause recirculation.  
ACTION 2Check for correct intake and exhaust  
vent installation. See instructions  
Combustion air inducer energizes  
with a heating demand.  
− Burners light roughly and the unit  
fails to stay lit.  
− Diagnostic lights flash watchguard  
flame failure.  
Recirculation of flue gases. This  
condition causes rough ignitions and  
operation. Problem is characterized  
by nuisance flame failures.  
ACTION 1 − Remove burner and inspect the  
cross−overs for burrs, or any restriction or if  
crossover is warped. Remove restriction or re-  
place burners.  
5.4.2  
LED#1−Alternating Slow Flash  
LED#2−Alternating Slow Flash  
Improper burner cross−overs  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROBLEM 6: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE  
Condition  
6.0  
Possible Cause  
6.1.1  
Corrective Action/Comments  
ACTION 1Check the sensor rod for proper loca-  
tion on the burner. Properly locate the sensor rod  
or replace if rod cannot be located correctly.  
− Unit operates correctly but the diag-  
nostic lights flash low flame sense  
code.  
Sensor rod is improperly located on  
the burner.  
ACTION 1 − Check sensor rod for contamination  
or coated surface. Clean the sensor rod with steel  
wool or replace sensor. DO NOT USE SAND PA-  
PER TO CLEAN ROD. SAND PAPER WILL  
CONTRIBUTE TO THE CONTAMINATION  
PROBLEM.  
6.1.2  
LED#1−Slow Flash  
LED#2−Fast Flash  
Sensor rod is contaminated.  
PROBLEM 7: INDOOR BLOWER FAILS TO OPERATE IN COOLING, HEATING, OR CONTINUOUS  
FAN MODE  
Condition  
7.0  
Possible Cause  
7.1.1  
Corrective Action/Comments  
ACTION 1− Correct wiring and/or replace any  
loose connections. Check for correct wiring and  
loose connections.  
− Indoor blower fails to operate in  
continuous fan, cooling, or heating  
mode.  
Miswiring of furnace or improper  
connections at control or indoor blow-  
er motor.  
ACTION 1 − Check for 120V at the various calls  
for indoor blower by energizing "Y", "G", and "W"  
individually on the low voltage terminal strip. Note  
that when "W’ is energized, the blower is delayed  
45 seconds. If there is 120V to each motor tap but  
the blower does not operate, replace the motor.  
7.1.2  
120V is not being supplied to the  
indoor air blower or blower motor fail-  
ure.  
7.1.3  
ACTION 1 − If there is not 120V when "Y", "G", or  
"W" is energized, replace the control.  
Defective control board  
7.1.4  
ACTION 1 − Replace capacitor  
Defective run capacitor  
PROBLEM 8: RF STATIC DURING TIME FOR IGNITION  
Condition  
8.0  
Possible Cause  
8.1.2  
Corrective Action/Comments  
ACTION 1 − Call Technical Support, Dallas.  
− AM radio interference.  
Ignitor operation  
Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE NOTES  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Land Pride Lawn Mower RB 15 User Manual
Leica Microscope Magnifier M695 User Manual
LG Electronics Camcorder VX9800 User Manual
LG Electronics Car Satellite TV System 20 23LS7DC User Manual
Logitech Computer Keyboard 920004569 User Manual
Magnavox DVD Recorder MDR513H User Manual
Makita Trimmer UMLOOOD User Manual
Mantis Trimmer DEHT19 User Manual
Melissa Hot Beverage Maker 645 103 User Manual
Mercedes Benz Automobile S 63 AMG User Manual