Extinguishing Control Panel
BC06-1EXT, BC06-2EXT
• For application in single-zone
extinguishing systems
• 4 detector zones in conventional
technology
• Differentiation between the activation
of automatic detectors and manual
call points on the same detector line
• Clear display and operation on the
panel front
• Tested to EN 54-2, -4, EN 12094-1 by
VdS
Fire is a permanent threat to life and property. There- ted within LST premises, thus guaranteeing flexible and
fore, immediate response to a fire is imperative. The reliable individual solutions.
main objective of the Fire Detection Control Panel
Series BC06 is to alarm and to react in time and, con- Using a powerful processor system and a large number
sequently, save lives and protect property. For decades of integrated functions, the Fire/Extinguishing Control
LST have focused their aims to undertaking unrivaled Panels Series BC06 ensure topmost efficiency and
efforts in order to realise new innovations in the security speed – prerequisites for saving lives and minimising
area. Research, development and production are loca- damage to property.
Description
Already in the basic version the combined Fire/Extingu- The optional evacuation function serves for the actu-
ishing Control Panels BC06-1EXT and BC06-2EXT are ation of alarming devices independent from activated
equipped with four detector lines and the Extinguishing alarms.
Board EXB1-1 and, owing to its sophisticated factory
settings, are immediately ready for operation. This al- Thanks to the integrated extinguishing module, the
lows for quick and efficient application of the product.
BC06 can be used as an extinguishing control panel
according to EN 12094-1 with one flooding zone. The
The conventional technology allows for the connection module provides appropriate inputs and outputs for con-
of automatic and non-automatic fire detectors as well trolling and monitoring a flooding zone. The display and
as a wide range of special detectors with contact out- operating elements that are necessary for the status
put. Alarms from manual call points and from automatic indication and the operation of the extinguishing module
detectors that are connected together to one detector are integrated into the keypad.
line can be differentiated and thus evaluated differently A printer for the event log can be connected via the
by the fire/extinguishing control panel, by means of an optional Serial Interface Modul SIM06-1.
optional coding module.
The Fire/Extinguishing Control Panel BC06-2EXT dif-
Thanks to the two auxiliary inputs whose parameters fers from the BC06-1EXT by the additionally integrated
can be freely set as well as the eight open-collector out- 4-digit electronic alarm counter.
puts, manifold tasks in the field of fire alarm technology
0786–CPD–20300
can be realised.
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
Extinguishing control
By means of the Extinguishing Board EXB1-1, the
ents of the extinguishing system
Fire/Extinguishing Control Panels BC06-1EXT and • A disable device for the indication of the mechanical
BC06-2EXT provide numerous inputs and outputs with
fixed or parameterisable function. With that, the follo- • A flooding switch that indicates the flow of the extin-
wing components of an extinguishing system can be ac- guishing agent
blocking of the extinguishing agent‘s network
tuated and monitored in accordance with EN 12094-1: • A device for switching to the manual mode – for ex-
ample, a key switch
• Activation devices for the manual activation of the • Signalling devices for indicating the activated conditi-
flooding process
on and the released condition
• Emergency hold devices for the manual delay of the • The control device for activating the flooding – for
flooding process example, a solenoid valve
• Emergency abort devices for aborting the flooding • Auxiliary outputs for actuating flaps or for turning off
process
devices and systems
• Fault detection devices for monitoring the compon-
Display and operating elements
The operating field of the Fire/Extinguishing Control Pa-
nels BC06-1EXT and BC06-2EXT provides 13 LEDs for The buttons on the operating field have the following
displaying the operating conditions and 4 buttons for functions:
the operation of the extinguishing system.
• Disable/enable the extinguishing module
• Start/terminate the manual mode
• Disable/enable the activation devices
The LEDs indicate the following operating conditions:
• Pre-activation/activation of the extinguishing module • Disable/enable the signal output
• Released condition of the extinguishing output
• Extinguishing output fault
• Extinguishing module fault/disablement
• Extinguishing medium fault/fault of the fault input
• Emergency hold/emergency hold device fault
• Activation device fault/disablement
• Signal output activated/signal output faulty/disabled
• Manual mode of the extinguishing module
• Fault of the activated condition output
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 3
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions of EN 12094-1
All mandatory functions of EN 12094-1 are integrated • Monitoring of a disable device
into the Fire/Extinguishing Control Panels BC06-1EXT • Parameterisable flooding time
and BC06-2EXT. Furthermore, the most important opti- • Possibility to switch to the „manual only mode“
onal functions of this standard are supported:
• Parameterisable pre-discharge-warning time for the
delay of the activation
• Transmission of the triggering signal to further actu-
ations within the extinguishing system – for example,
warning devices
• Detector zone „extinguishing medium active“ se- • Transmission of the triggering signal to further actua-
lectable for detecting the flow of the extinguishing
medium
tions outside the extinguishing system – for example,
for turning off the air conditioning system
• Monitoring of components of the extinguishing sys- • Emergency abort device can be connected
tem
• Activation of alarming devices with different alarm
signals
• Input for connection of an emergency hold device
Specifications
Mains voltage
230VAC +10/-20%, 47...63Hz
typ. 27.6VDC
Output/nominal voltage
Output current
max. 2.2A
Output current siren outputs
output 1
output 2
max. 1A
max. 0.5A
(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Output current, extinguishing output
max. 1A
Output current, activated condition output/signal output
Own current consumption (incl. extinguishing board) at 24V
max. 500mA per output
typ. 80mA (without optional componentries, line termination 5.6kΩ)
typ. 65mA (without optional componentries, line termination 47µF)
Line voltage
typ. 20V (line termination 5.6kΩ)
typ. 23V (line termination 47µF)
Line current without fire detectors
typ. 3.7mA (line termination 5.6kΩ)
typ. 0mA (line termination 47µF)
Line termination
Line resistance
Ambient temperature
Relative humidity
Dimensions W × H × D
Colour
5.6kΩ or 47µF
max. 50Ω per core
-5°C to +50°C
max. 95% (no condensation)
330 × 330 × 90 (mm)
grey-white, RAL 9002
approx. 3kg
Weight without batteries
Approvals
0786-CPD-20300
VdS pending
Fire Detection Control Panel BC06-1EXT
Order number
Order name
210223
Fire Detection Control Panel BC06-1EXT/INT1
Fire Detection Control Panel BC06-2EXT
Order number
Order name
210224