Klaxalarm Terrier (18-980181)
Battery Operated Stand Alone Fire Alarms
Installation Instructions
1. General
2. Installation
3. Operation, Testing and maintenance
4. Tone and Sound Level Adjustment
5. Connecting External Manual Call Points
6. Interlinking Multiple Units
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Tone and Sound Level Adjustment
The Terrier model incorporates 3 user selectable tones. In order to change the tone
setting the front cover of the electronic sounder within the Klaxalarm must be
removed by undoing the two fixing screws. The tones are selected as follows:
Tone
Black Lead
Jumper
Continuous
Warble
Alternating
Cont (-) Terminal
Tone (-) Terminal
Tone (-) Terminal
Leave in factory setting
Leave in factory setting
Change position
The sound level can be reduced by changing the setting of the potentiometer on
the siren PCB.
5. Connecting External Manual Call Points
NOTE: For correct operation with external manual call points it is essential to use
a call point with a NORMALLY CLOSED CONTACT (i.e. an opening contact
or changeover contact). We strongly recommend the use of Klaxon Manual Call
Point Model No. 17-970073 to ensure correct operation.
The normally closed terminals of the call point should be connected to terminals
A and B in the Klaxalarm using two core cable. The factory fitted link between
the terminals A and B in the Klaxalarm must be removed. Several normally
closed manual call points can be connected in a series loop between these
terminals if desired.
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Interlinking Multiple Units
Multiple units can be interlinked and/or connected to external manual call points
using three core cable as in the example wiring diagram below.
NOTE: For correct operation with external manual call points it is essential to use
a call point with a NORMALLY CLOSED CONTACT (i.e. opening contact or
changeover contact). We strongly recommend the use of Klaxon Manual Call
Point Model No. 17-970073 to ensure correct operation.
If an external call point is not required a direct connection must be made from
terminal C in the first unit to terminal B in the next unit and so on. Standard
telecom type multi-core cable can be used.